MIB Viewer

HUAWEI-SITE-MONITOR-MIB

462 objects
Site Monitor MIB defines MIB objects which provides load and backup management, patch management NMS interfaces. The current version is V1.01
Imported Objects
HUAWEI-MIBhuaweiUtility
SNMPv2-CONFNOTIFICATION-GROUP OBJECT-GROUP
SNMPv2-SMIInteger32 MODULE-IDENTITY NOTIFICATION-TYPE OBJECT-TYPE Unsigned32
SNMPv2-TCTEXTUAL-CONVENTION
OIDNameAccessStatusDescription
1.3.6.1.4.1.2011.6.164IdentityhwSiteMonitorMIBSite Monitor MIB defines MIB objects which provides load and backup management, patch management NMS interfaces. The current version is V1.01
1.3.6.1.4.1.2011.6.164.1NodehwSiteMonitorMIBObjects
1.3.6.1.4.1.2011.6.164.1.1NodehwSiteInfo
1.3.6.1.4.1.2011.6.164.1.1.1NodehwSiteSummary
1.3.6.1.4.1.2011.6.164.1.1.1.1ScalarhwSiteIdread-onlycurrentSite ID, default value: 000,000. Naming rule of the site device ID (six digits): The first three digits indicate the device name and the last three digits indi…
1.3.6.1.4.1.2011.6.164.1.1.1.2ScalarhwSiteNameread-writecurrentSite name, which users can configure, is used to specify a site. Otherwise, the configured character can not be any other languages except English.
1.3.6.1.4.1.2011.6.164.1.1.1.3ScalarhwSiteAdminAddrread-writecurrentSite administrant address, which users can assigned, is the unique ID of a site. It is used for device management by NMS, and value range is 0 to 65535.
1.3.6.1.4.1.2011.6.164.1.1.1.4ScalarhwSiteDescriptionread-writecurrentSite description. It is of the character string type. It is used to describe the site information such as the site location, which users can configure. Otherwi…
1.3.6.1.4.1.2011.6.164.1.1.1.5ScalarhwNetIdentifierread-writecurrentNE ID. It is of the character string type. It is the unique ID of the site (an independent network element (NE)) on the network. Otherwise, the configured char…
1.3.6.1.4.1.2011.6.164.1.1.1.6ScalarhwSiteIpread-onlycurrentSite IP address, default value is 192.168.0.10. Users need to configure the site IP address.
1.3.6.1.4.1.2011.6.164.1.1.1.7ScalarhwSiteNetmaskread-onlycurrentSite netmask, default value is 255.255.0.0. Users need to configure the site netmask.
1.3.6.1.4.1.2011.6.164.1.1.1.8ScalarhwSiteGatewayread-onlycurrentSite gateway, default value: 192.168.0.1. Users need to configure the site gateway.
1.3.6.1.4.1.2011.6.164.1.1.1.9ScalarhwSiteDGWorkStatusread-onlycurrentState of the diesel working state. It is an enumeration type: If the enumeration value is 1, it indicates that the diesel is in the idle state; If the enumerat…
1.3.6.1.4.1.2011.6.164.1.1.2NodehwSiteAlarms
1.3.6.1.4.1.2011.6.164.1.1.2.1ScalarhwDeviceTrapOrdinalNumberread-writecurrentSite device event trap serial number (SN) is the unique ID of the device event trap. It is used to resend and synchronize event traps. Its value range is 0 to …
1.3.6.1.4.1.2011.6.164.1.1.2.2ScalarhwAlarmTrapOrdinalNumberread-writecurrentSite alarm serial number (SN) is the unique ID of the alarm Trap. It is used to resend and synchronize alarms. Its value range is 0 to 4294967296. When the val…
1.3.6.1.4.1.2011.6.164.1.1.2.3ScalarhwAlarmQuantityread-onlycurrentAlarm number in site alarm list which are support. It is used for alarm list management by NMS, and value range is 0 to 65535.
1.3.6.1.4.1.2011.6.164.1.1.2.100TablehwSiteAlarmTablenot-accessiblecurrentSite alarms table. The table containing alarm information on the site management. Use this table to get site alarm name, alarm level, alarm signal description,…
1.3.6.1.4.1.2011.6.164.1.1.2.100.1RowhwSiteAlarmEntrynot-accessiblecurrentSite alarms table entry.
1.3.6.1.4.1.2011.6.164.1.1.2.100.1.1ColumnhwAlarmIndexread-onlycurrentSite alarm table index. It is the unique ID of the site alarm.
1.3.6.1.4.1.2011.6.164.1.1.2.100.1.2ColumnhwAlarmTextread-onlycurrentAlarm name. It is of the character string type, and used to specify the content of a specific alarm.
1.3.6.1.4.1.2011.6.164.1.1.2.100.1.3ColumnhwAlarmLevelread-writecurrentAlarm level, which users can configure the alarm severity, is an enumeration type: If the enumeration value is 1, it indicates a critical alarm; If the enumera…
1.3.6.1.4.1.2011.6.164.1.1.2.100.1.4ColumnhwAlarmSigDescread-writecurrentAlarm signal description. It is used to add and describe alarm content. Users can define the description of the alarm. Otherwise, the configured character can …
1.3.6.1.4.1.2011.6.164.1.1.2.100.1.100ColumnhwAlarmRowStatusread-createcurrentRowStatus of site alarms table.
1.3.6.1.4.1.2011.6.164.1.2NodehwSiteMonitors
1.3.6.1.4.1.2011.6.164.1.2.1NodehwMonitorsGroup
1.3.6.1.4.1.2011.6.164.1.2.1.1ScalarhwMonsGroupIdread-onlycurrentSite monitor group ID, is the unique ID of the site monitors.
1.3.6.1.4.1.2011.6.164.1.2.1.2ScalarhwMonsGroupNameread-writecurrentSite monitor group name is of the character string type, used to specify the monitor group. Users can configure it. Otherwise, the configured character can not…
1.3.6.1.4.1.2011.6.164.1.2.1.3ScalarhwMonsQuantityread-onlycurrentTotal site intelligent monitors.
1.3.6.1.4.1.2011.6.164.1.2.2NodehwMonitor
1.3.6.1.4.1.2011.6.164.1.2.2.1TablehwMonitorTablenot-accessiblecurrentSite monitors table. Use this table to get site monitor equipment ID, site monitor equipment name, equipment software version, equipment PCB version, manufactu…
1.3.6.1.4.1.2011.6.164.1.2.2.1.1RowhwMonitorEntrynot-accessiblecurrentSite monitors table entry.
1.3.6.1.4.1.2011.6.164.1.2.2.1.1.1ColumnhwMonIndexread-onlycurrentTable index of the site monitors (hwSiteMonsTab) is restricted by the quantity of the site monitors (hwMonsQuantity). Value range: 1 to 100
1.3.6.1.4.1.2011.6.164.1.2.2.1.1.2ColumnhwMonEquipIdread-onlycurrentSite monitor ID. Value range: 001,001 to 001,100, in which the first three digits indicate the device type and the last three digits indicate the device SN.
1.3.6.1.4.1.2011.6.164.1.2.2.1.1.3ColumnhwMonEquipNameread-writecurrentMonitor name. It is of the character string type, and users can set the name of the monitor. Otherwise, the configured character can not be any other languages…
1.3.6.1.4.1.2011.6.164.1.2.2.1.1.4ColumnhwMonEquipDescriptionread-writecurrentMonitor description. It is of the character string type. Users can set the description of the monitor. Otherwise, the configured character can not be any other…
1.3.6.1.4.1.2011.6.164.1.2.2.1.1.5ColumnhwMonEquipSoftwareVersionread-onlycurrentMonitor software version. It is of the character string type.
1.3.6.1.4.1.2011.6.164.1.2.2.1.1.6ColumnhwMonEquipPcbVersionread-onlycurrentMonitor printed circuit board (PCB) hardware version. It is of the character string type.
1.3.6.1.4.1.2011.6.164.1.2.2.1.1.7ColumnhwMonEquipManufacturerread-onlycurrentMonitor manufacture. It is of the character string type, and is an inherent attribute of the device.
1.3.6.1.4.1.2011.6.164.1.2.2.1.1.8ColumnhwMonEquipManuDateread-onlycurrentMonitor production date. It is of the character string type, and is an inherent attribute of the device.
1.3.6.1.4.1.2011.6.164.1.2.2.1.1.9ColumnhwMonEquipSerialNoread-onlycurrentProduction SN of the monitor. It is the electronic tag of the products.
1.3.6.1.4.1.2011.6.164.1.2.2.1.1.10ColumnhwMonEquipOperTotalTimeread-onlycurrentTotal monitor runtime. The monitor counts the data in real time. The value is an integer (.0), and unit is hour (h). It is used for performance measurement and…
1.3.6.1.4.1.2011.6.164.1.2.2.1.1.11ColumnhwSetMonEquipCtrlStateread-writecurrentMonitor control status. It is an enumeration type: If the enumeration value is 1, it indicates the background control; If the enumeration value is 2, it indica…
1.3.6.1.4.1.2011.6.164.1.2.2.1.1.12ColumnhwCtrlMonEquipResetread-writecurrentWarm-reset control of the monitor. It is an enumeration type: If the network management system (NMS) notifies the SNMP agent that this node is set to 1, it ind…
1.3.6.1.4.1.2011.6.164.1.2.2.1.1.99ColumnhwMonitorOperStatusread-onlycurrentState of the site monitor module. It is an enumeration type: If the enumeration value is 1, it indicates that the site monitor module is in the normal state; I…
1.3.6.1.4.1.2011.6.164.1.2.2.1.1.100ColumnhwMonRowStatusread-createcurrentRowStatus of site monitor.
1.3.6.1.4.1.2011.6.164.1.3NodehwSiteRectifiers
1.3.6.1.4.1.2011.6.164.1.3.1NodehwRectsGroup
1.3.6.1.4.1.2011.6.164.1.3.1.1ScalarhwRectsGroupIdread-onlycurrentDevice group ID of the rectifier module. It is the unique ID of the rectifier module group, and its default value: 002,000. The first digits indicate the devic…
1.3.6.1.4.1.2011.6.164.1.3.1.2ScalarhwRectsGroupNameread-writecurrentName of the rectifier module group, character string type, is used to specify the rectifier module group. Users can configure it. Otherwise, the configured cha…
1.3.6.1.4.1.2011.6.164.1.3.1.3ScalarhwRectsTotalCurrentread-onlycurrentTotal current of the rectifier module group on the site. It indicates the real-time statistics of the rectifier module group on the site. unit: A, and the valu…
1.3.6.1.4.1.2011.6.164.1.3.1.4ScalarhwRectsTotalQuantityread-onlycurrentTotal quantity of the rectifier modules. Value range: 0 to 256.
1.3.6.1.4.1.2011.6.164.1.3.1.5ScalarhwRectsRatedVoltageread-onlycurrentRated voltage of the rectifier module group. It is an inherent attribute. Value range: 42 to 58, Unit: V, and the value is accurate to one decimal place (.1).
1.3.6.1.4.1.2011.6.164.1.3.1.6ScalarhwModifyRectsOutputVoltageread-writecurrentVoltage adjustment of the rectifier module, which users can configure it. Value range: 42 to 58, Unit: V, and the value is accurate to one decimal space (.1). …
1.3.6.1.4.1.2011.6.164.1.3.1.7ScalarhwSetRectsRedundEnableread-writecurrentSleep function of the rectifier module group on the site. It is an enumeration value: If the NMS notifies the SNMP agent that this node is set to 1, it means t…
1.3.6.1.4.1.2011.6.164.1.3.1.8ScalarhwCtrlRectsAllOnOffread-writecurrentPower-on or power-off of the rectifier module group (all the rectifier modules) on the site. It is an enumeration value: If the NMS notifies the SNMP agent tha…
1.3.6.1.4.1.2011.6.164.1.3.2NodehwRectifier
1.3.6.1.4.1.2011.6.164.1.3.2.1TablehwRectConfigTablenot-accessiblecurrentRectifier config information table. Use this table to get rectifiers equipment ID, software version, manufacturer, rated current, efficency, AC input type, and…
1.3.6.1.4.1.2011.6.164.1.3.2.1.1RowhwRectConfigEntrynot-accessiblecurrentRectifier config table entry.
1.3.6.1.4.1.2011.6.164.1.3.2.1.1.1ColumnhwRectConfigIndexread-onlycurrentIndex of the device configuration list for the rectifier modules, which value range: 1 to 256. Lines of the device list are restricted by the total quantity of…
1.3.6.1.4.1.2011.6.164.1.3.2.1.1.2ColumnhwRectEquipIdread-onlycurrentRectifier module ID. Value range: 002'001 to 002'255. The first digits indicate the device type and last three digits indicate the device SN.
1.3.6.1.4.1.2011.6.164.1.3.2.1.1.3ColumnhwRectEquipNameread-writecurrentDevice name of the rectifier module, character string type, is used to specify the rectifier module. Users can configure it. Otherwise, the configured characte…
1.3.6.1.4.1.2011.6.164.1.3.2.1.1.4ColumnhwRectTyperead-onlycurrentSpecific type of the rectifier module. It is an enumeration type: If the enumeration value is 1, it indicates a 5A rectifier module; If the enumeration value i…
1.3.6.1.4.1.2011.6.164.1.3.2.1.1.5ColumnhwRectSoftwareVersionread-onlycurrentSoftware version of the rectifier module. It indicates the software version ID of the module.
1.3.6.1.4.1.2011.6.164.1.3.2.1.1.6ColumnhwRectManufacturerread-onlycurrentManufacture of the rectifier module.
1.3.6.1.4.1.2011.6.164.1.3.2.1.1.7ColumnhwRectManuDateread-onlycurrentManufacture date of rectifiers is of string type.
1.3.6.1.4.1.2011.6.164.1.3.2.1.1.8ColumnhwRectSerialNoread-onlycurrentRectifier module SN. It indicates the electronic tag of the product.
1.3.6.1.4.1.2011.6.164.1.3.2.1.1.9ColumnhwRectRatedCurrentread-onlycurrentRated voltage of the rectifier module, is an inherent attribute. Value range: 0 to 100, Unit: A, and the value is accurate to one decimal place (.1).
1.3.6.1.4.1.2011.6.164.1.3.2.1.1.10ColumnhwRectEfficencyread-onlycurrentEfficiency of the rectifier module, is an inherent attribute. Value range: 80 to 100, Unit: %, and the value is accurate to one decimal place (.1).
1.3.6.1.4.1.2011.6.164.1.3.2.1.1.11ColumnhwRectInputAcTyperead-onlycurrentInput AC type of the rectifier module. It is an enumeration value: If the value of the node is 1, it indicates single-phase AC input; If the value of the node …
1.3.6.1.4.1.2011.6.164.1.3.2.1.1.12ColumnhwCtrlRectOnOffread-writecurrentPower-on or power-off of the rectifier module, is an enumeration value. Users can modify the enumeration value of this node, thus controlling of the power-on o…
1.3.6.1.4.1.2011.6.164.1.3.2.1.1.100ColumnhwRectConfigRowStatusread-createcurrentRowStatus of rectifier config table.
1.3.6.1.4.1.2011.6.164.1.3.2.2TablehwRectOperTablenot-accessiblecurrentRectifier runing information table. Use this table to get rectifiers output current, output voltage, totle runing time, and current run status. This table's in…
1.3.6.1.4.1.2011.6.164.1.3.2.2.1RowhwRectOperEntrynot-accessiblecurrentRectifier runing table entry.
1.3.6.1.4.1.2011.6.164.1.3.2.2.1.1ColumnhwRectOperIndexread-onlycurrentTable index of the running rectifier modules, which value range: 1 to 256. Lines of the device list are restricted by the total quantity of the rectifier modul…
1.3.6.1.4.1.2011.6.164.1.3.2.2.1.2ColumnhwRectOutputCurrentread-onlycurrentOutput current of the rectifier module. It is a real-time analog parameter. Value range: 0 to 200, Unit: A, and the value is accurate to one decimal place (.1).
1.3.6.1.4.1.2011.6.164.1.3.2.2.1.3ColumnhwRectOutputVoltageread-onlycurrentOutput voltage of the rectifier module. It is a real-time analog parameter. Value range: 0 to 60, Unit: V, the value is accurate to one decimal place (.1).
1.3.6.1.4.1.2011.6.164.1.3.2.2.1.4ColumnhwRectTotalOperTimeread-onlycurrentTotal runtime of the rectifier module. Value unit: minute (m), and the value is an integer (.0).
1.3.6.1.4.1.2011.6.164.1.3.2.2.1.99ColumnhwRectOperStatusread-onlycurrentState of the rectifier module. It is an enumeration type: If the enumeration value is 1, it indicates that the rectifier module is in the normal state; If the …
1.3.6.1.4.1.2011.6.164.1.3.2.2.1.100ColumnhwRectOperRowStatusread-createcurrentRowStatus of rectifier runing table.
1.3.6.1.4.1.2011.6.164.1.4NodehwSiteBatterys
1.3.6.1.4.1.2011.6.164.1.4.1NodehwBattsConfig
1.3.6.1.4.1.2011.6.164.1.4.1.1ScalarhwBattsGroupIdread-onlycurrentBattery group ID. It is the unique ID of the battery group device. The first digits indicate the device type and the last three digits indicate the device SN. …
1.3.6.1.4.1.2011.6.164.1.4.1.2ScalarhwBattsGroupNameread-writecurrentDevice name of the battery group. It is of the character string type, which can be configured by users. Otherwise, the configured character can not be any othe…
1.3.6.1.4.1.2011.6.164.1.4.1.3ScalarhwBattsTotalQuantityread-writecurrentTotal quantity of battery strings, which value range: 0 to 100.
1.3.6.1.4.1.2011.6.164.1.4.1.4ScalarhwSetBattsHighTempActionread-writecurrentBattery high-temperature protection mode. It is an enumeration value, and can be configured. If the enumeration value is 1, it indicates the power-off protecti…
1.3.6.1.4.1.2011.6.164.1.4.1.5ScalarhwSetBattsHighTempVoltLimitread-writecurrentBattery protection voltage under high temperature. It works with the low-voltage power-off protection in battery high-temperature protection mode, which can be…
1.3.6.1.4.1.2011.6.164.1.4.1.6ScalarhwSetBattsHTDLimitread-writecurrentUpper threshold of the battery high temperature disconnection(HTD), can be configured by users. Value range: 0 to 100, Unit: centigrade (°„C), and the value…
1.3.6.1.4.1.2011.6.164.1.4.1.7ScalarhwSetBattsHTDEnableread-writecurrentBattery high temperature disconnection enable. It is an enumeration type: If the enumeration value is 1, enable the operation of the battery disconnection in h…
1.3.6.1.4.1.2011.6.164.1.4.1.8ScalarhwSetBattsFloatVoltageread-writecurrentFloat charge voltage of the batteries, can be configured by users. Value range: 42 to 58, unit: V, and the value is accurate to one decimal place (.1)
1.3.6.1.4.1.2011.6.164.1.4.1.9ScalarhwSetBattsBoostVoltageread-writecurrentBoostcharge voltage of the batteries, can be configured by users. Value range: 42 to 58, unit: V, and the value is accurate to one decimal place (.1).
1.3.6.1.4.1.2011.6.164.1.4.1.10ScalarhwSetBattsCurrLimitCoefficientread-writecurrentCurrent-limiting point coefficient of the batteries, can be configured by users. Value range: 0.05 to 0.25, unit: C10, and the value is accurate to two decimal…
1.3.6.1.4.1.2011.6.164.1.4.1.11ScalarhwSetBattsCompFactorread-writecurrentTemperature compensated coefficient of the batteries, can be configured by user. Value range: 0 to 500, unit: mv per centigrade, and the value is an integer (.…
1.3.6.1.4.1.2011.6.164.1.4.1.12ScalarhwCtrlBattsBoostFloatread-writecurrentControl batteries charge mode between boost and float. It is an enumeration value. Users actively control the conversion. If the NMS notifies the SNMP agent th…
1.3.6.1.4.1.2011.6.164.1.4.2NodehwBattsOperate
1.3.6.1.4.1.2011.6.164.1.4.2.1ScalarhwBattsTotalCurrentread-onlycurrentTotal current of the battery group. It indicates the real-time statistics of the battery group on the site. Value range: -1000 to +1000, unit: A, and the value…
1.3.6.1.4.1.2011.6.164.1.4.2.2ScalarhwBattsPreDischargeTimeread-onlycurrentBattery group backup time. It indicates the real-time statistics of the battery group. Value range: 0 to 65536, Unit: minute (m), and the value is an integer (…
1.3.6.1.4.1.2011.6.164.1.4.2.3ScalarhwBattsChargeStatusread-onlycurrentBattery charging state, indicates the charging and discharging information about the battery group. It is an enumeration type. If the enumeration value is 1, i…
1.3.6.1.4.1.2011.6.164.1.4.2.4ScalarhwBattsCurrLimitStatusread-onlycurrentBattery group current-limiting state, indicates the state information about the battery group. It is an enumeration value. If the enumeration value is 1, it in…
1.3.6.1.4.1.2011.6.164.1.4.3NodehwBattsTest
1.3.6.1.4.1.2011.6.164.1.4.3.1ScalarhwBattsTestRecordCountread-onlycurrentBattery test records number.
1.3.6.1.4.1.2011.6.164.1.4.3.2ScalarhwSetBattsManuStdTestTimeread-writecurrentBattery standard test time, It can be configured by users, and its value is an integer (.0). Here, if battery manual test is standard mode, value range defines…
1.3.6.1.4.1.2011.6.164.1.4.3.3ScalarhwSetBattsManuStdTestEndVoltread-writecurrentVoltage when the battery test is ended, can be configured by users. Unit: V/cell, and the value is accurate to two decimal place (.2). Here, if battery manual …
1.3.6.1.4.1.2011.6.164.1.4.3.4ScalarhwSetBattsManuStdTestCellNumread-writecurrentBattery cell number in each Group, which is used in the battery standard manual test, can be configured by users. Unit: psc or cell, value range defines betwee…
1.3.6.1.4.1.2011.6.164.1.4.3.5ScalarhwSetBattsManuShortTestTimeread-writecurrentBattery short test time, It can be configured by users, and its value is an integer (.0). If battery manual test is simple mode, value range defines between 1 …
1.3.6.1.4.1.2011.6.164.1.4.3.6ScalarhwSetBattsManuShortTestEndVoltread-writecurrentVoltage when the battery short test is ended, can be configured by users. Unit: V, and the value is accurate to one decimal place (.1). Here, if battery manual…
1.3.6.1.4.1.2011.6.164.1.4.3.7ScalarhwCtrlBattsTestStartStopread-writecurrentBattery manualtest start and stop. It is an enumeration value. If the NMS notifies the SNMP agent that the node is set to 1, it means to start a standard manua…
1.3.6.1.4.1.2011.6.164.1.4.3.100TablehwBattsTestResultTablenot-accessiblecurrentBattery test result record table. Use this table to get battery test inital time, test result, battery efficiency, battery discharge time, terminated voltage, …
1.3.6.1.4.1.2011.6.164.1.4.3.100.1RowhwBattsTestResultEntrynot-accessiblecurrentBattery test result table entry.
1.3.6.1.4.1.2011.6.164.1.4.3.100.1.1ColumnhwBattsTestResultIndexread-onlycurrentTable index of the battery test results. Currently up to 10 times of the battery test results are saved by default.
1.3.6.1.4.1.2011.6.164.1.4.3.100.1.2ColumnhwBattsTestTyperead-onlycurrentRecord test type of the battery test. It is an enumeration value: If the NMS notifies the SNMP agent that this node is set to 1, it indicates a manual test; If…
1.3.6.1.4.1.2011.6.164.1.4.3.100.1.3ColumnhwBattsTestStartTimeread-onlycurrentTest start time of the record in the battery test. It is of the character string type.
1.3.6.1.4.1.2011.6.164.1.4.3.100.1.4ColumnhwBattsTestResultread-onlycurrentBattery test result. It is an enumeration value. If the enumeration value of the node is 1, it indicates that the battery test has no result: If the enumeratio…
1.3.6.1.4.1.2011.6.164.1.4.3.100.1.5ColumnhwBattsEfficiencyread-onlycurrentBattery efficiency test. Value range: 0 to 100, Unit: %, and the value is an integer (.0). If the value is -1, it indicates that the test value is inefficient.
1.3.6.1.4.1.2011.6.164.1.4.3.100.1.6ColumnhwBattsDischargeTimeread-onlycurrentDischarge time of the battery test records. Value range: 0 to 100, unit: hour (h), and the value is accurate to two decimal places (.2).
1.3.6.1.4.1.2011.6.164.1.4.3.100.1.7ColumnhwBattsDischargeEndVoltageread-onlycurrentDischarge termination voltage of the battery test. Value range: 0 to 60, unit: V, and the value is accurate to one decimal place (.1).
1.3.6.1.4.1.2011.6.164.1.4.3.100.1.8ColumnhwBattsDischargeAvCurrentread-onlycurrentAverage discharge current of the battery test. Value range: -10000 to 10000, unit: A, and the value is accurate to one decimal place (.1).
1.3.6.1.4.1.2011.6.164.1.4.3.100.1.9ColumnhwBattsDischargeAhValueread-onlycurrentDischarge ampere per hour the battery test. Value range: 0 to 5000, Unit: Ah, and the value is an integer (.0).
1.3.6.1.4.1.2011.6.164.1.4.3.100.1.10ColumnhwBattsTestTempratureread-onlycurrentBattery temperature of the battery test termination. Value range: -50 to +100, Unit: centigrade (°„C), and the value is an integer (.0). If the value is -10…
1.3.6.1.4.1.2011.6.164.1.4.3.100.1.11ColumnhwBattsTestEndCourseread-onlycurrentTermination factors of the battery test. It is an enumeration value. If the enumeration value is 1, it indicates that the voltage value of the battery test rea…
1.3.6.1.4.1.2011.6.164.1.4.3.100.1.100ColumnhwBattsTestResultRowStatusread-createcurrentRowStatus of battery test table.
1.3.6.1.4.1.2011.6.164.1.4.4NodehwBattString
1.3.6.1.4.1.2011.6.164.1.4.4.1TablehwBattStringConfigTablenot-accessiblecurrentBattery string config table. Use this table to get battery string equipment ID and equipment name, to set battery standard capacity and battery install time as…
1.3.6.1.4.1.2011.6.164.1.4.4.1.1RowhwBattStringConfigEntrynot-accessiblecurrentBattery string config table entry.
1.3.6.1.4.1.2011.6.164.1.4.4.1.1.1ColumnhwBattStringConfigIndexread-onlycurrentDevice table index of the battery string, which value range: 1 to 100.
1.3.6.1.4.1.2011.6.164.1.4.4.1.1.2ColumnhwBattStringEquipIdread-onlycurrentBatteries device ID, can be configured by users. Value range: 003,001 to 003,100, in which the first three digits specify the device type and the last three sp…
1.3.6.1.4.1.2011.6.164.1.4.4.1.1.3ColumnhwBattStringEquipNameread-writecurrentBatteries device name, of the character string type, is used to specify the batteries. Users can configure it. Otherwise, the configured character can not be a…
1.3.6.1.4.1.2011.6.164.1.4.4.1.1.4ColumnhwSetBattsTempUpperLimitread-writecurrentUpper threshold of the battery temperature alarm, can be configured by users. Value range: -50 to 100, Unit: centigrade (°„C), and the value is an integer (…
1.3.6.1.4.1.2011.6.164.1.4.4.1.1.5ColumnhwSetBattsTempLowerLimitread-writecurrentLower threshold of the battery temperature alarm, can be configured by users. Value range: -50 to 100, Unit: centigrade (°„C), and the value is an integer (…
1.3.6.1.4.1.2011.6.164.1.4.4.1.1.6ColumnhwSetBattsTempMeasureUpperLimitread-writecurrentUpper threshold of the battery temperature measurement, can be configured by users. Value range: 0 to 100, Unit: centigrade (°„C), and the value is an integ…
1.3.6.1.4.1.2011.6.164.1.4.4.1.1.7ColumnhwSetBattsTempMeasureLowerLimitread-writecurrentLower threshold of the battery temperature measurement, can be configured by users. Value range: -50 to 0, Unit: centigrade (°„C), and the value is an integ…
1.3.6.1.4.1.2011.6.164.1.4.4.1.1.8ColumnhwSetBattStdCapacityread-writecurrentSet battery standard capacity, is an inherent attribute of the device. Value range: 0 to 10000, unit: Ah, the value is an integer (.0).
1.3.6.1.4.1.2011.6.164.1.4.4.1.1.9ColumnhwSetBattInstallTimeread-writecurrentSet battery install time, of the character string type, can be configured by users. Otherwise, the configured character can not be any other languages except E…
1.3.6.1.4.1.2011.6.164.1.4.4.1.1.100ColumnhwBattStringConfigRowStatusread-createcurrentRowStatus of battery string config table.
1.3.6.1.4.1.2011.6.164.1.4.4.2TablehwBattStringOperTablenot-accessiblecurrentBattery string runing table. Use this table to get battery string current, persent of remain capacity, battery remain capacity, battery actual capacity, as wel…
1.3.6.1.4.1.2011.6.164.1.4.4.2.1RowhwBattStringOperEntrynot-accessiblecurrentBattery string runing table entry.
1.3.6.1.4.1.2011.6.164.1.4.4.2.1.1ColumnhwBattStringOperIndexread-onlycurrentDevice table index of the battery string, which value range: 1 to 100.
1.3.6.1.4.1.2011.6.164.1.4.4.2.1.2ColumnhwBattStringCurrentread-onlycurrentBatteries current. It is an analog parameter collected by the battery string in real time. Value range: -1000 to +1000, unit: A, and the value is accurate to o…
1.3.6.1.4.1.2011.6.164.1.4.4.2.1.3ColumnhwBattStringRemainCapacityPercentread-onlycurrentRemaining capacity percentage of the battery string. Value range: 0 to 100, unit: %, and the value is accurate to one decimal place (.1).
1.3.6.1.4.1.2011.6.164.1.4.4.2.1.4ColumnhwBattStringRemainCapacityread-onlycurrentRemaining capacity of the battery string. It is an analog parameter collected by the battery string in real time. Value range: 0 to 5000, unit: Ah, and the val…
1.3.6.1.4.1.2011.6.164.1.4.4.2.1.5ColumnhwBattStringActualCapacityread-onlycurrentBatteries actual capacity. It is an analog parameter collected by the battery string in real time.Value range: 0 to 5000, unit: Ah, the value is an integer (.0…
1.3.6.1.4.1.2011.6.164.1.4.4.2.1.6ColumnhwBattStringTempratureread-onlycurrentBattery temperature. It is a battery parameter collected in real time. Value range: -50 to +100, unit: centigrade (°„C), and the value is an integer (.1). I…
1.3.6.1.4.1.2011.6.164.1.4.4.2.1.99ColumnhwBattStringOperStatusread-onlycurrentState of the site battery string module. It is an enumeration type: If the enumeration value is 1, it indicates that the site battery string is in the normal s…
1.3.6.1.4.1.2011.6.164.1.4.4.2.1.100ColumnhwBattStringOperRowStatusread-createcurrentRowStatus of battery string runing table.
1.3.6.1.4.1.2011.6.164.1.5NodehwSiteAcDistributions
1.3.6.1.4.1.2011.6.164.1.5.1NodehwAcDistributionsGroup
1.3.6.1.4.1.2011.6.164.1.5.1.1ScalarhwAcsGroupIdread-onlycurrentAC group ID, is the unique ID of the AC group. The first three digits indicate the device type and the last three indicate the device SN. If the last three dig…
1.3.6.1.4.1.2011.6.164.1.5.1.2ScalarhwAcsGroupNameread-writecurrentDevice name of the AC group. It is of the character string type, and can be configured by users. Otherwise, the configured character can not be any other langu…
1.3.6.1.4.1.2011.6.164.1.5.1.3ScalarhwAcsTotalCurrentread-onlycurrentTotal current of the AC group. It indicates the real-time statistics of the AC group. Value range: 0 to 1000, unit: A, and the value is accurate to one decimal…
1.3.6.1.4.1.2011.6.164.1.5.1.4ScalarhwAcsTotalQuantityread-onlycurrentTotal quantity of the site ACUs. Value range: 0 to 100.
1.3.6.1.4.1.2011.6.164.1.5.1.5ScalarhwSetAcsUpperVoltLimitread-writecurrentUpper threshold of the AC voltage alarm, can be configured by users. Value range: 60 to 500, unit: V, and the value is an integer (.0).
1.3.6.1.4.1.2011.6.164.1.5.1.6ScalarhwSetAcsLowerVoltLimitread-writecurrentLower threshold of the AC voltage alarm, can be configured by users. Value range: 60 to 500, unit: V, and the value is an integer (.0).
1.3.6.1.4.1.2011.6.164.1.5.2NodehwAcDistribution
1.3.6.1.4.1.2011.6.164.1.5.2.1TablehwAcInputTablenot-accessiblecurrentAC input table. Use this table to get AC distribution unit ID, AC distribution unit name, A phase or AB line voltage, B phase or BC line voltage, C phase or CA…
1.3.6.1.4.1.2011.6.164.1.5.2.1.1RowhwAcInputEntrynot-accessiblecurrentAC input table entry.
1.3.6.1.4.1.2011.6.164.1.5.2.1.1.1ColumnhwAcInputIndexread-onlycurrentACU device table index, which value range: 1 to 100. Lines of the device list are restricted by the total quantity of ACUs (hwAcsInputQuantity).
1.3.6.1.4.1.2011.6.164.1.5.2.1.1.2ColumnhwAcEquipIdread-onlycurrentACU device ID, which users can configure. Value range: 004,001 to 004,100, in which The first digits indicate the device type and the last three digits indicat…
1.3.6.1.4.1.2011.6.164.1.5.2.1.1.3ColumnhwAcEquipNameread-writecurrentACU device name, of the character string type, is used to specify the alternating current unit (ACU). Users can configure it. Otherwise, the configured charact…
1.3.6.1.4.1.2011.6.164.1.5.2.1.1.4ColumnhwApOrAblVoltageread-onlycurrentACU A-phase or AB-line voltage. Value range: 0 to 500, unit: V, and the value is accurate to one decimal place (.1).
1.3.6.1.4.1.2011.6.164.1.5.2.1.1.5ColumnhwBpOrBclVoltageread-onlycurrentACU B-phase or BC-line voltage. Value range: 0 to 500, unit: V, and the value is accurate to one decimal place (.1).
1.3.6.1.4.1.2011.6.164.1.5.2.1.1.6ColumnhwCpOrCalVoltageread-onlycurrentACU C-phase or CA-line voltage. Value range: 0 to 500, unit: V, and the value is accurate to one decimal place (.1).
1.3.6.1.4.1.2011.6.164.1.5.2.1.1.7ColumnhwAphaseCurrentread-onlycurrentACU A-phase current. It is an analog parameter collected by the ACU in real time. Value range: 0 to 100, unit: A, and the value is accurate to one decimal plac…
1.3.6.1.4.1.2011.6.164.1.5.2.1.1.8ColumnhwBphaseCurrentread-onlycurrentACU B-phase current. It is an analog parameter collected by the ACU in real time. Value range: 0 to 100, unit: A, and the value is accurate to one decimal plac…
1.3.6.1.4.1.2011.6.164.1.5.2.1.1.9ColumnhwCphaseCurrentread-onlycurrentACU C-phase current. It is an analog parameter collected by the ACU in real time. Value range: 0 to 100, unit: A, and the value is accurate to one decimal plac…
1.3.6.1.4.1.2011.6.164.1.5.2.1.1.10ColumnhwAcInputBreakersQuantityread-onlycurrentQuantity of the AC air circuit breakers. As the ACU lower-level subset, the node indicates the quantity of the output air circuit breakers contained by each AC…
1.3.6.1.4.1.2011.6.164.1.5.2.1.1.99ColumnhwAcInputOperStatusread-onlycurrentState of the site AC distribution uint. It is an enumeration type: If the enumeration value is 1, it indicates that the site AC distribution uint is in the nor…
1.3.6.1.4.1.2011.6.164.1.5.2.1.1.100ColumnhwAcRowStatusread-createcurrentRowStatus of ACU.
1.3.6.1.4.1.2011.6.164.1.5.2.2TablehwAcInputBreakerTablenot-accessiblecurrentAc input breaker table. Use this table to get AC input breaker equipment ID, AC input breaker equipment name, and AC input breaker status. This table's index i…
1.3.6.1.4.1.2011.6.164.1.5.2.2.1RowhwAcInputBreakerEntrynot-accessiblecurrentAc input breaker table entry.
1.3.6.1.4.1.2011.6.164.1.5.2.2.1.1ColumnhwAcInputBreakerIndexread-onlycurrentDevice table index of the AC air circuit breaker. Value range: 1 to 100. An input air circuit breaker device can be uniquely identified through the ACU table i…
1.3.6.1.4.1.2011.6.164.1.5.2.2.1.2ColumnhwAcInputBreakerEquipIdread-onlycurrentAC input air circuit breaker ID. Value range: 005,001 to 005,100. The first digits indicate the device type and the last three digits indicate the device SN.
1.3.6.1.4.1.2011.6.164.1.5.2.2.1.3ColumnhwAcInputBreakerEquipNameread-writecurrentAC input air circuit breaker name, of the character string type, can configured by users. Otherwise, the configured character can not be any other languages ex…
1.3.6.1.4.1.2011.6.164.1.5.2.2.1.99ColumnhwAcInputBreakerOperStatusread-onlycurrentOperation state of the site AC input breaker. It is an enumeration type: If the enumeration value is 1, it indicates that the site AC input breaker is in the n…
1.3.6.1.4.1.2011.6.164.1.5.2.2.1.100ColumnhwAcInputBreakerRowStatusread-createcurrentRowStatus of AC input breaker.
1.3.6.1.4.1.2011.6.164.1.6NodehwSiteDcDistributions
1.3.6.1.4.1.2011.6.164.1.6.1NodehwDcDistributionsGroup
1.3.6.1.4.1.2011.6.164.1.6.1.1ScalarhwDcsGroupIdread-onlycurrentDC group ID: unique ID of the DC group. in which The first digits indicate the device type and the last three digits indicate the device SN. If the last three …
1.3.6.1.4.1.2011.6.164.1.6.1.2ScalarhwDcsGroupNameread-writecurrentDevice name of the DC group, of the character string type, can be configured by users. Otherwise, the configured character can not be any other languages excep…
1.3.6.1.4.1.2011.6.164.1.6.1.3ScalarhwDcsTotalVoltageread-onlycurrentTotal voltage of the DC group. Value range: 0 to 60, unit: V, and the value is accurate to one decimal place (.1).
1.3.6.1.4.1.2011.6.164.1.6.1.4ScalarhwDcsTotalCurrentread-onlycurrentTotal current of the DC group. Value range: 0 to 10000, unit: A, and the value is accurate to one decimal place (.1).
1.3.6.1.4.1.2011.6.164.1.6.1.5ScalarhwDcsTotalPowerread-onlycurrentTotal power of the DC group. Value range: 0 to 10000, unit: W, and the value is an integer (.0).
1.3.6.1.4.1.2011.6.164.1.6.1.6ScalarhwDcsTotalQuantityread-onlycurrentTotal quantity of the DC units, and its Value range: 0 to 100.
1.3.6.1.4.1.2011.6.164.1.6.1.7ScalarhwSetDcsUpperVoltLimitread-writecurrentUpper threshold of the DC voltage alarm, can be configued by users. Value range: 30 to 60, unit: V, and the value is accurate to one decimal space (.1).
1.3.6.1.4.1.2011.6.164.1.6.1.8ScalarhwSetDcsLowerVoltLimitread-writecurrentLower threshold of the DC voltage alarm, can be configued by users. Value range: 30 to 60, unit: V, and the value is accurate to one decimal space (.1).
1.3.6.1.4.1.2011.6.164.1.6.2NodehwDcDistribution
1.3.6.1.4.1.2011.6.164.1.6.2.1TablehwDcOutputTablenot-accessiblecurrentDC output table. Use this table to get DC distribution unit ID, DC distribution unit name, DC output voltage, DC output power, and loads quantity in each DC di…
1.3.6.1.4.1.2011.6.164.1.6.2.1.1RowhwDcOutputEntrynot-accessiblecurrentDc output table entry.
1.3.6.1.4.1.2011.6.164.1.6.2.1.1.1ColumnhwDcOutputIndexread-onlycurrentDevice table index of the DC units, which value range: 1 to 100. Lines of the device list are restricted by the total quantity of DC units (hwDcsQuantity).
1.3.6.1.4.1.2011.6.164.1.6.2.1.1.2ColumnhwDcOutputEquipIdread-onlycurrentDC unit device ID, which value range: 006,001 to 006,100. The first digits indicate the device type and the last three digits indicate the device SN.
1.3.6.1.4.1.2011.6.164.1.6.2.1.1.3ColumnhwDcOutputEquipNameread-writecurrentDC unit device name, of the character string type, can be configued by users. Otherwise, the configured character can not be any other languages except English.
1.3.6.1.4.1.2011.6.164.1.6.2.1.1.4ColumnhwDcOutputVoltageread-onlycurrentDC output voltage. It is an analog parameter collected by the DC power in real time. Value range: 0 to 60, unit: V, and the value is accurate to one decimal sp…
1.3.6.1.4.1.2011.6.164.1.6.2.1.1.5ColumnhwDcOutputCurrentread-onlycurrentDC output current. It is an analog parameter collected by the DC power in real time. Value range: 0 to 10000, unit: A, and the value is accurate to one decimal…
1.3.6.1.4.1.2011.6.164.1.6.2.1.1.6ColumnhwDcOutputPowerread-onlycurrentDC output power. It is an analog parameter collected by the DC power in real time. Value range: 0 to 600000, unit: W, and the value is an integer (.0).
1.3.6.1.4.1.2011.6.164.1.6.2.1.1.7ColumnhwLoadsQuantityread-onlycurrentQuantity of the DC load output branches, which value range: 0 to 100. As the DC unit lower-level subset, the node indicates the quantity of the DC load output …
1.3.6.1.4.1.2011.6.164.1.6.2.1.1.99ColumnhwDcOutputOperStatusread-onlycurrentState of the site DC distribution uint. It is an enumeration type: If the enumeration value is 1, it indicates that the site DC distribution uint is in the nor…
1.3.6.1.4.1.2011.6.164.1.6.2.1.1.100ColumnhwDcOutputRowStatusread-createcurrentRowStatus of Dc output equipments.
1.3.6.1.4.1.2011.6.164.1.6.2.2TablehwLoadBranchTablenot-accessiblecurrentLoads output table. Use this table to get load branch equipment ID, load branch equipment name, load branch current, and load branch power. This table's index …
1.3.6.1.4.1.2011.6.164.1.6.2.2.1RowhwLoadBranchEntrynot-accessiblecurrentLoads output table entry.
1.3.6.1.4.1.2011.6.164.1.6.2.2.1.1ColumnhwLoadBranchIndexread-onlycurrentDevice table index of the DC load output branch, which value range: 1 to 100. A DC load output branch can be uniquely identified through the DC unit table inde…
1.3.6.1.4.1.2011.6.164.1.6.2.2.1.2ColumnhwLoadBranchEquipIdread-onlycurrentDevice ID of the DC load output branch. Value range: 007,001 to 007,100. The first digits indicate the device type and the last three digits indicate the SN of…
1.3.6.1.4.1.2011.6.164.1.6.2.2.1.3ColumnhwLoadBranchEquipNameread-writecurrentDevice name of the DC load output branch, of the character string type, can be configured by users. Otherwise, the configured character can not be any other la…
1.3.6.1.4.1.2011.6.164.1.6.2.2.1.4ColumnhwLoadBranchCurrentread-onlycurrentDC load output branch current. It is an analog parameter collected by the load branch in real time. Value range: 0 to 10000, unit: A, and the value is accurate…
1.3.6.1.4.1.2011.6.164.1.6.2.2.1.5ColumnhwLoadBranchPowerread-onlycurrentDC load branch power. It is an analog parameter collected by the DC power in real time. Value range: 0 to 600000, unit: W, and the value is an integer (.0).
1.3.6.1.4.1.2011.6.164.1.6.2.2.1.99ColumnhwLoadBranchOperStatusread-onlycurrentState of the site load output branch. It is an enumeration type: If the enumeration value is 1, it indicates that the site load output branch is in the normal …
1.3.6.1.4.1.2011.6.164.1.6.2.2.1.100ColumnhwLoadBranchRowStatusread-createcurrentRowStatus of loads output branch.
1.3.6.1.4.1.2011.6.164.1.7NodehwLvdUnits
1.3.6.1.4.1.2011.6.164.1.7.1NodehwLvdsGroup
1.3.6.1.4.1.2011.6.164.1.7.1.1ScalarhwLvdsGroupIdread-onlycurrentLVD unit group ID. It is the unique ID of the LVD unit group. The first digits indicate the device type. The last three digits indicate the device SN. If the l…
1.3.6.1.4.1.2011.6.164.1.7.1.2ScalarhwLvdsGroupNameread-writecurrentLow-voltage power-off unit group name, of the character string type, can be configured by users. Otherwise, the configured character can not be any other langu…
1.3.6.1.4.1.2011.6.164.1.7.1.3ScalarhwLvdsTotalQuantityread-onlycurrentTotal quantity of power-off units. Value range: 0 to 100.
1.3.6.1.4.1.2011.6.164.1.7.2NodehwLvdUnit
1.3.6.1.4.1.2011.6.164.1.7.2.1TablehwLvdBranchTablenot-accessiblecurrentPower-off unit table. Use this table to get Lvd unit equipment ID and power-off unit equipment name, set power-off enable and power-off voltage, as well as con…
1.3.6.1.4.1.2011.6.164.1.7.2.1.1RowhwLvdBranchEntrynot-accessiblecurrentPower-off table entry.
1.3.6.1.4.1.2011.6.164.1.7.2.1.1.1ColumnhwLvdBranchIndexread-onlycurrentDevice table index of a power-off unit. Value range: 1 to 100. Lines of the device list are restricted by the total quantity of the power-off units (hwLvdsTota…
1.3.6.1.4.1.2011.6.164.1.7.2.1.1.2ColumnhwLvdUnitEquipIdread-onlycurrentDevice ID of a power-off unit. Value range: 8001 to 8100. The first digits indicate the device type and the last three digits indicate the device SN.
1.3.6.1.4.1.2011.6.164.1.7.2.1.1.3ColumnhwLvdUnitEquipNameread-writecurrentDevice name of a power-off unit, of the character string type, is used to specify the low-voltage power-off unit. Users can configure it. Otherwise, the config…
1.3.6.1.4.1.2011.6.164.1.7.2.1.1.4ColumnhwSetLvdEnableread-writecurrentControl power-off unit enabling. It is an enumeration value, and users actively set it. If the enumeration value is 1, it means to enable the power-off unit; I…
1.3.6.1.4.1.2011.6.164.1.7.2.1.1.5ColumnhwSetLvdVoltageread-writecurrentLow-voltage power-off voltage of a power-off unit can be configured by users. Its value range: 35 to 60, unit: V, and the value is accurate to one decimal spac…
1.3.6.1.4.1.2011.6.164.1.7.2.1.1.6ColumnhwCtrlLvdread-writecurrentControl of the power-off unit. It is an enumeration value, users control it manually. If the NMS notifies the SNMP agent that the node is set to 1, it means to…
1.3.6.1.4.1.2011.6.164.1.7.2.1.1.99ColumnhwLvdBranchOperStatusread-onlycurrentState of the site LVD uint. It is an enumeration type: If the enumeration value is 1, it indicates that the site LVD uint is in the normal state; If the enumer…
1.3.6.1.4.1.2011.6.164.1.7.2.1.1.100ColumnhwLvdBranchRowStatusread-createcurrentRowStatus of lvd table.
1.3.6.1.4.1.2011.6.164.1.8NodehwSiteEnvUnits
1.3.6.1.4.1.2011.6.164.1.8.1NodehwEnvUnitsGroup
1.3.6.1.4.1.2011.6.164.1.8.1.1ScalarhwEnvUnitsGroupIdread-onlycurrentUnit group ID of the site environment. It is the unique ID of the unit group on the site. The first digits indicate the device type. The last three digits indi…
1.3.6.1.4.1.2011.6.164.1.8.1.2ScalarhwEnvUnitsGroupNameread-writecurrentUnit group name of the site environment, of the character string type, can be configured by users. Otherwise, the configured character can not be any other lan…
1.3.6.1.4.1.2011.6.164.1.8.1.3ScalarhwCtrlSmokeResetread-writecurrentSmoke sensor reset. It manually controls clearance of the smoke sensor alarm, and this node is of the enumeration type. If the enumeration value is 1, it indic…
1.3.6.1.4.1.2011.6.164.1.8.1.4ScalarhwCtrlDoorResetread-writecurrentDoor actuator reset control. It manually controls clearance of the door actuator alarm. This node is of the enumeration type. If the enumeration value is 1, it…
1.3.6.1.4.1.2011.6.164.1.8.1.5ScalarhwCtrlBuzzerEnableread-writecurrentBuzzer enabling. It manually controls the enabling of the buzzer alarm. This node is of the enumeration type. When the enumeration value is 1, it means to enab…
1.3.6.1.4.1.2011.6.164.1.8.1.6ScalarhwEnvTempSensorsTotalQuantityread-onlycurrentQuantity of the environment temperature sensors, and its value range: 0 to 256.
1.3.6.1.4.1.2011.6.164.1.8.1.7ScalarhwEnvHumiSensorsTotalQuantityread-onlycurrentQuantity of the environment humidity sensors, and its value range: 0 to 256.
1.3.6.1.4.1.2011.6.164.1.8.1.8ScalarhwSpareDigitalsTotalQuantityread-onlycurrentQuantity of the Spare digitals, and its value range: 0 to 256.
1.3.6.1.4.1.2011.6.164.1.8.2NodehwEnvSensor
1.3.6.1.4.1.2011.6.164.1.8.2.1TablehwEnvTempSensorTablenot-accessiblecurrentSite environment temperature table. Use this table to get environment temperature equipment ID, environment temperature equipment name, and environment tempera…
1.3.6.1.4.1.2011.6.164.1.8.2.1.1RowhwEnvTempSensorEntrynot-accessiblecurrentSite environment temperature table entry.
1.3.6.1.4.1.2011.6.164.1.8.2.1.1.1ColumnhwEnvTempSensorIndexread-onlycurrentTable index of the environment temperature sensors. Value range: 1 to 256. Lines of the device table are restricted by the quantity of environment temperature …
1.3.6.1.4.1.2011.6.164.1.8.2.1.1.2ColumnhwEnvTempEquipIdread-onlycurrentEnvironment temperature sensor ID. Value range: 009'001 to 009'255, in which the first digits indicate the device type and the last three digits indicate the d…
1.3.6.1.4.1.2011.6.164.1.8.2.1.1.3ColumnhwEnvTempEquipNameread-writecurrentEnvironment temperature sensor name, of the character string type, is used to specify an environment temperature sensor. Users can configure it. Otherwise, the…
1.3.6.1.4.1.2011.6.164.1.8.2.1.1.4ColumnhwEnvTemperatureread-onlycurrentEnvironment temperature. It is an environment parameter collected in real time. Value range: -50 to +100, unit: centigrade (°„C), and the value is an intege…
1.3.6.1.4.1.2011.6.164.1.8.2.1.1.5ColumnhwSetEnvTempUpperLimitread-writecurrentUpper threshold of the environment temperature alarm, can be configured by users. Value range: -50 to 100, unit: centigrade (°„C), and the value is an integ…
1.3.6.1.4.1.2011.6.164.1.8.2.1.1.6ColumnhwSetEnvTempLowerLimitread-writecurrentLower threshold of the environment temperature alarm, can be configured by users. Value range: -50 to 100, unit: centigrade (°„C), and the value is an integ…
1.3.6.1.4.1.2011.6.164.1.8.2.1.1.7ColumnhwSetEnvTempMeasureUpperLimitread-writecurrentUpper threshold of the environment temperature measurement, can be configured by users. Value range: 0 to 100, unit: centigrade (°„C), and the value is an i…
1.3.6.1.4.1.2011.6.164.1.8.2.1.1.8ColumnhwSetEnvTempMeasureLowerLimitread-writecurrentLower threshold of the environment temperature measurement, can be configured by users. Value range: -50 to 0, unit: centigrade (°„C), and the value is an i…
1.3.6.1.4.1.2011.6.164.1.8.2.1.1.9ColumnhwSetEnvTempAlarmEnableread-writecurrentEnvironment temperature alarm. It is an enumeration type: If the enumeration value is 1, enable the alarm of the environment temperature; If the enumeration va…
1.3.6.1.4.1.2011.6.164.1.8.2.1.1.99ColumnhwEnvTempSensorOperStatusread-onlycurrentState of the site environment temperature sensor. It is an enumeration type: If the enumeration value is 1, it indicates that the site environment temperature …
1.3.6.1.4.1.2011.6.164.1.8.2.1.1.100ColumnhwEnvTempSensorRowStatusread-createcurrentRowStatus of Environment temperature table.
1.3.6.1.4.1.2011.6.164.1.8.2.2TablehwEnvHumiSensorTablenot-accessiblecurrentEnvironment humidity table. Use this table to get environment humidity equipment ID , environment humidity equipment name, and environment humidity, set enviro…
1.3.6.1.4.1.2011.6.164.1.8.2.2.1RowhwEnvHumiSensorEntrynot-accessiblecurrentEnvironment humidity table entry.
1.3.6.1.4.1.2011.6.164.1.8.2.2.1.1ColumnhwEnvHumiSensorIndexread-onlycurrentTable index of the environment humility sensors. Value range: 1 to 256. Lines of the device list are restricted by the quantity of environment humility sensors…
1.3.6.1.4.1.2011.6.164.1.8.2.2.1.2ColumnhwEnvHumiEquipIdread-onlycurrentEnvironment humility sensor ID, can be configured by users. Value range: 010'001 to 010'255, in which the first digits indicate the device type and the last th…
1.3.6.1.4.1.2011.6.164.1.8.2.2.1.3ColumnhwEnvHumiEquipNameread-writecurrentEnvironment humility sensor name, of the character string type, is used to specify an environment humility sensor. Users can configure it. Otherwise, the confi…
1.3.6.1.4.1.2011.6.164.1.8.2.2.1.4ColumnhwEnvHumidityread-onlycurrentEnvironment humility. It is an environment parameter collected in real time. Value range: 0 to 100, unit: %RH, and the value is an integer (.0). If the value i…
1.3.6.1.4.1.2011.6.164.1.8.2.2.1.5ColumnhwSetEnvHumidityUpperLimitread-writecurrentUpper threshold of the environment humility alarm, can be configured by users. Value range: 0 to 100, unit: %RH, and the value is an integer (.0).
1.3.6.1.4.1.2011.6.164.1.8.2.2.1.6ColumnhwSetEnvHumidityLowerLimitread-writecurrentLower threshold of the environment humility alarm, can be configured by users. Value range: 0 to 100, unit: %RH, and the value is an integer (.0).
1.3.6.1.4.1.2011.6.164.1.8.2.2.1.7ColumnhwSetEnvHumidityMeasureUpperLimitread-writecurrentUpper threshold of the environment humility measurement, can be configured by users. Value range: 0 to 100, unit: %RH, and the value is an integer (.0).
1.3.6.1.4.1.2011.6.164.1.8.2.2.1.8ColumnhwSetEnvHumidityMeasureLowerLimitread-writecurrentLower threshold of the environment humility measurement, can be configured by users. Value range: 0 to 100, unit: %RH, and the value is an integer (.0).
1.3.6.1.4.1.2011.6.164.1.8.2.2.1.9ColumnhwSetEnvHumiAlarmEnableread-writecurrentEnvironment humility alarm. It is an enumeration type: If the enumeration value is 1, enable the alarm of the environment humility; If the enumeration value is…
1.3.6.1.4.1.2011.6.164.1.8.2.2.1.99ColumnhwEnvHumiSensorOperStatusread-onlycurrentState of the site environment humidity sensor. It is an enumeration type: If the enumeration value is 1, it indicates that the site environment humidity sensor…
1.3.6.1.4.1.2011.6.164.1.8.2.2.1.100ColumnhwEnvHumiSensorRowStatusread-createcurrentRowStatus of Environment humidity table.
1.3.6.1.4.1.2011.6.164.1.8.2.3TablehwSpareDigitalTablenot-accessiblecurrentSpare digital table. Use this table to get Spare digital equipment ID , Spare digital equipment name, and current Spare digital alarm tension, ae well as to se…
1.3.6.1.4.1.2011.6.164.1.8.2.3.1RowhwSpareDigitalEntrynot-accessiblecurrentSpare digital table entry.
1.3.6.1.4.1.2011.6.164.1.8.2.3.1.1ColumnhwSpareDigitalIndexread-onlycurrentSpare digital table index, which value range: 1 to 256. Lines of the device list are restricted by the quantity of Spare digitals (hwSpareDigitalsTotalQuantity…
1.3.6.1.4.1.2011.6.164.1.8.2.3.1.2ColumnhwSpareDigitalEquipIdread-onlycurrentSpare digital device ID. Value range: 011'001 to 011'255, in which the first digits indicate the device type and the last three digits indicate the device SN.
1.3.6.1.4.1.2011.6.164.1.8.2.3.1.3ColumnhwSpareDigitalEquipNameread-writecurrentSpare digital name, of the character string type, is used to specify Spare digitals. Users can configure it. Otherwise, the configured character can not be any…
1.3.6.1.4.1.2011.6.164.1.8.2.3.1.4ColumnhwSetSpareDigitalAlarmTensionread-writecurrentSpare digital alarm state. It is an enumeration value. If the value of the node is 0, it indicates a low-tension alarm; If the value of the node is 1, it indic…
1.3.6.1.4.1.2011.6.164.1.8.2.3.1.5ColumnhwSetSpareDigitalAlarmEnableread-writecurrentSpare digital alarm enabling. It is an enumeration type: If the enumeration value is 1, it means to enable the alarm; If the enumeration value is 2, it means t…
1.3.6.1.4.1.2011.6.164.1.8.2.3.1.99ColumnhwSpareDigitalOperStatusread-onlycurrentState of the site Spare digital. It is an enumeration type: If the enumeration value is 1, it indicates that the Spare digital operation state is normal; If th…
1.3.6.1.4.1.2011.6.164.1.8.2.3.1.100ColumnhwSpareDigitalRowStatusread-createcurrentRowStatus of Spare digital device table.
1.3.6.1.4.1.2011.6.164.1.9NodehwSitePDEs
1.3.6.1.4.1.2011.6.164.1.9.1NodehwPDEGroup
1.3.6.1.4.1.2011.6.164.1.9.1.1ScalarhwPDEGroupIdread-onlycurrentPDE unit group ID. It is the unique ID of the PDE unit group. The first digits indicate the device type. The last three digits indicate the device SN. If the l…
1.3.6.1.4.1.2011.6.164.1.9.1.2ScalarhwPDEGroupNameread-writecurrentPDE unit group name, of the character string type, can be configured by users. Otherwise, the configured character can not be any other languages except Englis…
1.3.6.1.4.1.2011.6.164.1.9.1.3ScalarhwPDEGroupNumread-onlycurrentPDE Num,Value range: 0 to 100.
1.3.6.1.4.1.2011.6.164.1.9.1.4ScalarhwPDEGroupCommNumread-onlycurrentCommunication PDE Num,Value range: 0 to 100.
1.3.6.1.4.1.2011.6.164.1.9.1.5ScalarhwPDEGroupTotalPowerread-onlycurrentPDE Total Power,Value range: 0.0 to 10000.0.Unit: W.and the value is accurate to one decimal space (.1).
1.3.6.1.4.1.2011.6.164.1.9.1.6ScalarhwPDEGroupTotalCurrentread-onlycurrentPDE Total Current,Value range: 0.0 to 300.0.Unit: A.and the value is accurate to one decimal space (.1).
1.3.6.1.4.1.2011.6.164.1.9.1.7ScalarhwPDEGroupCommStatusread-onlycurrentPDE Communication Status. It is an enumeration type: If the enumeration value is 1, it indicates that communication is normal; If the enumeration value is 2, i…
1.3.6.1.4.1.2011.6.164.1.9.3NodehwPDE
1.3.6.1.4.1.2011.6.164.1.9.3.1TablehwPDETablenot-accessiblecurrentPDE table. Use this table to get PDE equipment ID , PDE equipment name, and current PDE status. This table's index is hwPDEIndex.
1.3.6.1.4.1.2011.6.164.1.9.3.1.1RowhwPDEEntrynot-accessiblecurrentPDE table entry.
1.3.6.1.4.1.2011.6.164.1.9.3.1.1.1ColumnhwPDEIndexread-onlycurrentPDE table index, which value range: 1 to 10. Lines of the device list are restricted by the quantity of PDE.
1.3.6.1.4.1.2011.6.164.1.9.3.1.1.2ColumnhwPDEEquipIdread-onlycurrentPDE device ID. Value range: 012'001 to 012'255, in which the first digits indicate the device type and the last three digits indicate the device SN.
1.3.6.1.4.1.2011.6.164.1.9.3.1.1.3ColumnhwPDEEquipNameread-writecurrentPDE name, of the character string type, is used to specify PDEs. Users can configure it. Otherwise, the configured character can not be any other languages exc…
1.3.6.1.4.1.2011.6.164.1.9.3.1.1.4ColumnhwPDETotalRunningTimeread-onlycurrentPDE Total Running Time,Value range: 0 to 876000.Unit: H.
1.3.6.1.4.1.2011.6.164.1.9.3.1.1.5ColumnhwPDEBranchNumread-onlycurrentPDE Branch Number,Value range: 0 to 6.
1.3.6.1.4.1.2011.6.164.1.9.3.1.1.6ColumnhwPDETotalPowerread-onlycurrentPDE Total Power,Value range: 0.0 to 10000.0.Unit: W.and the value is accurate to one decimal space (.1).
1.3.6.1.4.1.2011.6.164.1.9.3.1.1.7ColumnhwPDETotalCurrentread-onlycurrentPDE Total Current,Value range: 0.0 to 30000.0.Unit: A.and the value is accurate to one decimal space (.1).
1.3.6.1.4.1.2011.6.164.1.9.3.1.1.8ColumnhwPDEBranch1Powerread-onlycurrentPDE Branch1 Power,Value range: 0.0 to 100000.0.Unit: W.and the value is accurate to one decimal space (.1).
1.3.6.1.4.1.2011.6.164.1.9.3.1.1.9ColumnhwPDEBranch2Powerread-onlycurrentPDE Branch2 Power,Value range: 0.0 to 100000.0.Unit: W.and the value is accurate to one decimal space (.1).
1.3.6.1.4.1.2011.6.164.1.9.3.1.1.10ColumnhwPDEBranch3Powerread-onlycurrentPDE Branch3 Power,Value range: 0.0 to 100000.0.Unit: W.and the value is accurate to one decimal space (.1).
1.3.6.1.4.1.2011.6.164.1.9.3.1.1.11ColumnhwPDEBranch4Powerread-onlycurrentPDE Branch4 Power,Value range: 0.0 to 100000.0.Unit: W.and the value is accurate to one decimal space (.1).
1.3.6.1.4.1.2011.6.164.1.9.3.1.1.12ColumnhwPDEBranch1Currentread-onlycurrentPDE Branch1 Current,Value range: 0.0 to 1000.0.Unit: A.and the value is accurate to one decimal space (.1).
1.3.6.1.4.1.2011.6.164.1.9.3.1.1.13ColumnhwPDEBranch2Currentread-onlycurrentPDE Branch2 Current,Value range: 0.0 to 1000.0.Unit: A.and the value is accurate to one decimal space (.1).
1.3.6.1.4.1.2011.6.164.1.9.3.1.1.14ColumnhwPDEBranch3Currentread-onlycurrentPDE Branch3 Current,Value range: 0.0 to 1000.0.Unit: A.and the value is accurate to one decimal space (.1).
1.3.6.1.4.1.2011.6.164.1.9.3.1.1.15ColumnhwPDEBranch4Currentread-onlycurrentPDE Branch4 Current,Value range: 0.0 to 1000.0.Unit: A.and the value is accurate to one decimal space (.1).
1.3.6.1.4.1.2011.6.164.1.9.3.1.1.16ColumnhwPDEBranch1Voltageread-onlycurrentPDE Branch1 Voltage,Value range: 0.0 to 65.0.Unit: V.and the value is accurate to one decimal space (.1).
1.3.6.1.4.1.2011.6.164.1.9.3.1.1.17ColumnhwPDEBranch2Voltageread-onlycurrentPDE Branch2 Voltage,Value range: 0.0 to 65.0.Unit: V.and the value is accurate to one decimal space (.1).
1.3.6.1.4.1.2011.6.164.1.9.3.1.1.18ColumnhwPDEBranch3Voltageread-onlycurrentPDE Branch3 Voltage,Value range: 0.0 to 65.0.Unit: V.and the value is accurate to one decimal space (.1).
1.3.6.1.4.1.2011.6.164.1.9.3.1.1.19ColumnhwPDEBranch4Voltageread-onlycurrentPDE Branch4 Voltage,Value range: 0.0 to 65.0.Unit: V.and the value is accurate to one decimal space (.1).
1.3.6.1.4.1.2011.6.164.1.9.3.1.1.20ColumnhwPDEBranch1Temperatureread-onlycurrentPDE Branch1 Temperature,Value range: 0 to 300.Unit: deg.
1.3.6.1.4.1.2011.6.164.1.9.3.1.1.21ColumnhwPDEBranch2Temperatureread-onlycurrentPDE Branch2 Temperature,Value range: 0 to 300.Unit: deg.
1.3.6.1.4.1.2011.6.164.1.9.3.1.1.22ColumnhwPDEBranch3Temperatureread-onlycurrentPDE Branch3 Temperature,Value range: 0 to 300.Unit: deg.
1.3.6.1.4.1.2011.6.164.1.9.3.1.1.23ColumnhwPDEBranch4Temperatureread-onlycurrentPDE Branch4 Temperature,Value range: 0 to 300.Unit: deg.
1.3.6.1.4.1.2011.6.164.1.9.3.1.1.24ColumnhwPDEOperStatusread-onlycurrentState of the PDE. It is an enumeration type: If the enumeration value is 1, it indicates that the PDE is in the normal state; If the enumeration value is 2, it…
1.3.6.1.4.1.2011.6.164.1.9.3.1.1.100ColumnhwPDERowStatusread-createcurrentRowStatus of PDE table.
1.3.6.1.4.1.2011.6.164.1.9.3.2TablehwPDEConfigTablenot-accessiblecurrentPDE Config table. Use this table to get PDE equipment ID , PDE equipment name, and current PDE config parameter. This table's index is hwPDEConfigIndex.
1.3.6.1.4.1.2011.6.164.1.9.3.2.1RowhwPDEConfigEntrynot-accessiblecurrentPDE Config table entry.
1.3.6.1.4.1.2011.6.164.1.9.3.2.1.1ColumnhwPDEConfigIndexread-onlycurrentPDE Config table index, which value range: 1 to 10. Lines of the device list are restricted by the quantity of PDE.
1.3.6.1.4.1.2011.6.164.1.9.3.2.1.2ColumnhwPDEConfigEquipIdread-onlycurrentPDE device ID. Value range: 012'001 to 012'255, in which the first digits indicate the device type and the last three digits indicate the device SN.
1.3.6.1.4.1.2011.6.164.1.9.3.2.1.3ColumnhwPDEConfigEquipNameread-writecurrentPDE name, of the character string type, is used to specify PDEs. Users can configure it. Otherwise, the configured character can not be any other languages exc…
1.3.6.1.4.1.2011.6.164.1.9.3.2.1.4ColumnhwPDEOverTempProtectread-writecurrentPDE Over Temperature Protect,Value range: 100 to 120.Unit: deg.
1.3.6.1.4.1.2011.6.164.1.9.3.2.1.5ColumnhwPDEVolProtectEnableread-writecurrentPDE Over Protect Enable,It is an enumeration value, and users actively set it. If the enumeration value is 1, it means to enable the PDE voltage protect; If th…
1.3.6.1.4.1.2011.6.164.1.9.3.2.1.6ColumnhwPDEOverVoltageProtectread-writecurrentPDE Over Voltage Protect,Value range: 58 to 60.Unit: V.
1.3.6.1.4.1.2011.6.164.1.9.3.2.1.7ColumnhwPDEUnderVoltageProtectread-writecurrentPDE Under Voltage Protect,Value range: 40 to 48.Unit: V.
1.3.6.1.4.1.2011.6.164.1.9.3.2.1.8ColumnhwPDEHysteresisread-writecurrentPDE Hysteresis,Value range: 1 to 3.Unit: V.
1.3.6.1.4.1.2011.6.164.1.9.3.2.1.9ColumnhwPDEResetread-writecurrentPDE Reset Control,It is an enumeration value, and users actively set it. If the enumeration value is 1, it means to reset the PDE;
1.3.6.1.4.1.2011.6.164.1.9.3.2.1.10ColumnhwPDEBranch1Controlread-writecurrentPDE Branch1 Control,It is an enumeration value, and users actively set it. If the enumeration value is 1, it means to open the branch1; If the enumeration valu…
1.3.6.1.4.1.2011.6.164.1.9.3.2.1.11ColumnhwPDEBranch2Controlread-writecurrentPDE Branch2 Control,It is an enumeration value, and users actively set it. If the enumeration value is 1, it means to open the branch2; If the enumeration valu…
1.3.6.1.4.1.2011.6.164.1.9.3.2.1.12ColumnhwPDEBranch3Controlread-writecurrentPDE Branch3 Control,It is an enumeration value, and users actively set it. If the enumeration value is 1, it means to open the branch3; If the enumeration valu…
1.3.6.1.4.1.2011.6.164.1.9.3.2.1.13ColumnhwPDEBranch4Controlread-writecurrentPDE Branch4 Control,It is an enumeration value, and users actively set it. If the enumeration value is 1, it means to open the branch4; If the enumeration valu…
1.3.6.1.4.1.2011.6.164.1.9.3.2.1.14ColumnhwPDEBranch1CurrentLimitread-writecurrentPDE Branch1 Current Limit,Value range: 1 to 20.Unit: A.
1.3.6.1.4.1.2011.6.164.1.9.3.2.1.15ColumnhwPDEBranch2CurrentLimitread-writecurrentPDE Branch2 Current Limit,Value range: 1 to 30.Unit: A.
1.3.6.1.4.1.2011.6.164.1.9.3.2.1.16ColumnhwPDEBranch3CurrentLimitread-writecurrentPDE Branch3 Current Limit,Value range: 1 to 30.Unit: A.
1.3.6.1.4.1.2011.6.164.1.9.3.2.1.17ColumnhwPDEBranch4CurrentLimitread-writecurrentPDE Branch4 Current Limit,Value range: 1 to 20.Unit: A.
1.3.6.1.4.1.2011.6.164.1.9.3.2.1.100ColumnhwPDEConfigRowStatusread-createcurrentRowStatus of PDE config table.
1.3.6.1.4.1.2011.6.164.2NodehwSiteMonitorMIBTraps
1.3.6.1.4.1.2011.6.164.2.1NodehwSiteAlarmTraps
1.3.6.1.4.1.2011.6.164.2.1.0NodehwSiteAlarmTrapsPrefix
1.3.6.1.4.1.2011.6.164.2.1.0.1NotificationhwRectifierFaultAlarmTrapscurrentWhen rectifiers fault alarms happen, a alarm trap will be send. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Al…
1.3.6.1.4.1.2011.6.164.2.1.0.2NotificationhwRectifierFaultAlarmResumeTrapscurrentRectifier Fault alarm resolved.Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm por…
1.3.6.1.4.1.2011.6.164.2.1.0.3NotificationhwRectifierAbnormalAlarmTrapscurrentRectifier abnormal alarm, because of communication failure, module protection, or turnoff. Its correlation binding parameters: Site ID, Site name, Site descrip…
1.3.6.1.4.1.2011.6.164.2.1.0.4NotificationhwRectifierAbnormalAlarmResumeTrapscurrentRectifier abnormal alarm resume. Description.Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single descript…
1.3.6.1.4.1.2011.6.164.2.1.0.5NotificationhwBattLoopBreakAlarmTrapscurrentBattery loop disconnect. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port desc…
1.3.6.1.4.1.2011.6.164.2.1.0.6NotificationhwBattLoopBreakAlarmResumeTrapscurrentBattery loop break alarm resume. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm p…
1.3.6.1.4.1.2011.6.164.2.1.0.7NotificationhwBattLvdAlarmTrapscurrentBattery disconnect for low voltage. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alar…
1.3.6.1.4.1.2011.6.164.2.1.0.8NotificationhwBattLvdAlarmResumeTrapscurrentBattery LVD alarm resume. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port des…
1.3.6.1.4.1.2011.6.164.2.1.0.9NotificationhwBattOverCurrAlarmTrapscurrentBatterys charge in over current. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm p…
1.3.6.1.4.1.2011.6.164.2.1.0.10NotificationhwBattOverCurrAlarmResumeTrapscurrentBatterys over current alarm resume. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alar…
1.3.6.1.4.1.2011.6.164.2.1.0.11NotificationhwBattStringTempAlarmTrapscurrentBattery string temperature is too high or too low. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single de…
1.3.6.1.4.1.2011.6.164.2.1.0.12NotificationhwBattStringTempAlarmResumeTrapscurrentBattery string temperature alarm resume. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description,…
1.3.6.1.4.1.2011.6.164.2.1.0.13NotificationhwBattDischargeAlarmTrapscurrentBattery group discharge alarm. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm por…
1.3.6.1.4.1.2011.6.164.2.1.0.14NotificationhwBattDischargeAlarmResumeTrapscurrentBattery group discharge alarm resume. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Al…
1.3.6.1.4.1.2011.6.164.2.1.0.15NotificationhwAcInputAlarmTrapscurrentAC absent or AC power off alarms happened. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single descriptio…
1.3.6.1.4.1.2011.6.164.2.1.0.16NotificationhwAcInputAlarmResumeTrapscurrentAC input alarm resumed. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port descr…
1.3.6.1.4.1.2011.6.164.2.1.0.17NotificationhwAcVoltAlarmTrapscurrentAC voltage too high or too low. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm po…
1.3.6.1.4.1.2011.6.164.2.1.0.18NotificationhwAcVoltAlarmResumeTrapscurrentAC voltage alarm resume. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port desc…
1.3.6.1.4.1.2011.6.164.2.1.0.19NotificationhwDcVoltAlarmTrapscurrentDC voltage too high or too low. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm po…
1.3.6.1.4.1.2011.6.164.2.1.0.20NotificationhwDcVoltAlarmResumeTrapscurrentDC voltage alarm resume. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port desc…
1.3.6.1.4.1.2011.6.164.2.1.0.21NotificationhwLoadLvdAlarmTrapscurrentLoads disconnect for low voltage. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm …
1.3.6.1.4.1.2011.6.164.2.1.0.22NotificationhwLoadLvdAlarmResumeTrapscurrentLoad LVD alarm resume. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port descri…
1.3.6.1.4.1.2011.6.164.2.1.0.23NotificationhwLoadFuseAlarmTrapscurrentLoad fuse broken down. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port descri…
1.3.6.1.4.1.2011.6.164.2.1.0.24NotificationhwLoadFuseAlarmResumeTrapscurrentLoad fuse alarm resume. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port descr…
1.3.6.1.4.1.2011.6.164.2.1.0.25NotificationhwEnvTempAlarmTrapscurrentEnvironment temperature is too high or too low. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single descr…
1.3.6.1.4.1.2011.6.164.2.1.0.26NotificationhwEnvTempAlarmResumeTrapscurrentEnvironment temperature alarm resume. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Al…
1.3.6.1.4.1.2011.6.164.2.1.0.27NotificationhwEnvHumiAlarmTrapscurrentEnvironment humidity is too high or too low. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single descript…
1.3.6.1.4.1.2011.6.164.2.1.0.28NotificationhwEnvHumiAlarmResumeTrapscurrentEnvironment humidity alarm resume. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm…
1.3.6.1.4.1.2011.6.164.2.1.0.29NotificationhwSpareDigitalAlarmTrapscurrentSpare digital fault. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port descript…
1.3.6.1.4.1.2011.6.164.2.1.0.30NotificationhwSpareDigitalAlarmResumeTrapscurrentSpare digital alarm resume.Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port de…
1.3.6.1.4.1.2011.6.164.2.1.0.31NotificationhwDoorAlarmTrapscurrentDoor open. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm…
1.3.6.1.4.1.2011.6.164.2.1.0.32NotificationhwDoorAlarmResumeTrapscurrentDoor alarm resume. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port descriptio…
1.3.6.1.4.1.2011.6.164.2.1.0.33NotificationhwWaterAlarmTrapscurrentWater alarm. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Ala…
1.3.6.1.4.1.2011.6.164.2.1.0.34NotificationhwWaterAlarmResumeTrapscurrentWater alarm resume. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port descripti…
1.3.6.1.4.1.2011.6.164.2.1.0.35NotificationhwSmokeAlarmTrapscurrentSite is on fire, which is detected by smoke sensors. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single …
1.3.6.1.4.1.2011.6.164.2.1.0.36NotificationhwSmokeAlarmResumeTrapscurrentSmoke alarm resume. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port descripti…
1.3.6.1.4.1.2011.6.164.2.1.0.37NotificationhwWireAlarmTrapscurrentWire alarm.Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description, Alarm…
1.3.6.1.4.1.2011.6.164.2.1.0.38NotificationhwWireAlarmResumeTrapscurrentWire alarm resume. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port descriptio…
1.3.6.1.4.1.2011.6.164.2.1.0.39NotificationhwAcBreakerAlarmTrapscurrentAC breaker alarm.Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port description,…
1.3.6.1.4.1.2011.6.164.2.1.0.40NotificationhwAcBreakerAlarmResumeTrapscurrentAC breaker alarm resume.Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port descr…
1.3.6.1.4.1.2011.6.164.2.1.0.41NotificationhwMultiRectFailureAlarmTrapscurrentMore than one rectifier reported fault alarms in the same time. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Al…
1.3.6.1.4.1.2011.6.164.2.1.0.42NotificationhwMultiRectFailureAlarmResumeTrapscurrentMulti-rectifiers fault alarm resume. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Ala…
1.3.6.1.4.1.2011.6.164.2.1.0.43NotificationhwRectRedundAlarmTrapscurrentRectifiers work redundantly, in this case that some of rectifiers will going to sleep. Its correlation binding parameters: Site ID, Site name, Site description…
1.3.6.1.4.1.2011.6.164.2.1.0.44NotificationhwRectRedundAlarmResumeTrapscurrentRectifiers redundant alarm resume, when the power supply and requirement were in balance. Its correlation binding parameters: Site ID, Site name, Site descript…
1.3.6.1.4.1.2011.6.164.2.1.0.45NotificationhwBattUnbalanceAlarmTrapscurrentBattery works in unbalance state. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm …
1.3.6.1.4.1.2011.6.164.2.1.0.46NotificationhwBattUnbalanceAlarmResumeTrapscurrentBattery unbalance alarm resume. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm po…
1.3.6.1.4.1.2011.6.164.2.1.0.47NotificationhwAcFreqFaultAlarmTrapscurrentAC frequency is fault. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port descri…
1.3.6.1.4.1.2011.6.164.2.1.0.48NotificationhwAcFreqFaultAlarmResumeTrapscurrentAC frequency alarm resume. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port de…
1.3.6.1.4.1.2011.6.164.2.1.0.49NotificationhwXmuSelfFaultAlarmTrapscurrentThere are some fault in XMU itself. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alar…
1.3.6.1.4.1.2011.6.164.2.1.0.50NotificationhwXmuSelfFaultAlarmResumeTrapscurrentXMU fault alarm resume. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm port descr…
1.3.6.1.4.1.2011.6.164.2.1.0.51NotificationhwRs485CommAlarmTrapscurrentRS485 communication of monitors disconnect. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single descripti…
1.3.6.1.4.1.2011.6.164.2.1.0.52NotificationhwRs485CommAlarmResumeTrapscurrentRS485 communication alarm resume. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alarm …
1.3.6.1.4.1.2011.6.164.2.1.0.53NotificationhwNetCommAlarmTrapscurrentNetwork communication of monitors disconnect. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single descrip…
1.3.6.1.4.1.2011.6.164.2.1.0.54NotificationhwNetCommAlarmResumeTrapscurrentNetwork communication alarm resume. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single description, Alar…
1.3.6.1.4.1.2011.6.164.2.1.0.55NotificationhwAcOffLongTimeAlarmTrapscurrentAC power off for a long time alarms happened. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single descrip…
1.3.6.1.4.1.2011.6.164.2.1.0.56NotificationhwAcOffLongTimeAlarmResumeTrapscurrentAC power off for a long time alarms resume. Its correlation binding parameters: Site ID, Site name, Site description, NE ID, Alarm name, Alarm single descripti…
1.3.6.1.4.1.2011.6.164.2.1.0.57NotificationhwSpdAlarmTrapscurrentDescription.
1.3.6.1.4.1.2011.6.164.2.1.0.58NotificationhwSpdAlarmResumeTrapscurrentDescription.
1.3.6.1.4.1.2011.6.164.2.1.0.59NotificationhwBadBatteryTrapscurrentDescription.
1.3.6.1.4.1.2011.6.164.2.1.0.60NotificationhwBadBatteryResumeTrapscurrentDescription.
1.3.6.1.4.1.2011.6.164.2.1.0.61NotificationhwLvd2DisconnectingTrapscurrentDescription.
1.3.6.1.4.1.2011.6.164.2.1.0.62NotificationhwLvd2DisconnectingResumeTrapscurrentDescription.
1.3.6.1.4.1.2011.6.164.2.1.0.63NotificationhwBattHighTempTrapscurrentDescription.
1.3.6.1.4.1.2011.6.164.2.1.0.64NotificationhwBattHighTempResumeTrapscurrentDescription.
1.3.6.1.4.1.2011.6.164.2.1.0.65NotificationhwBattLowTempTrapscurrentDescription.
1.3.6.1.4.1.2011.6.164.2.1.0.66NotificationhwBattLowTempResumeTrapscurrentDescription.
1.3.6.1.4.1.2011.6.164.2.1.0.67NotificationhwDcUltraOverVoltageTrapscurrentDescription.
1.3.6.1.4.1.2011.6.164.2.1.0.68NotificationhwDcUltraOverVoltageResumeTrapscurrentDescription.
1.3.6.1.4.1.2011.6.164.2.1.0.69NotificationhwDcUltraUnderVoltageTrapscurrentDescription.
1.3.6.1.4.1.2011.6.164.2.1.0.70NotificationhwDcUltraUnderVoltageResumeTrapscurrentDescription.
1.3.6.1.4.1.2011.6.164.2.1.0.71NotificationhwUmiCommFailTrapscurrentDescription.
1.3.6.1.4.1.2011.6.164.2.1.0.72NotificationhwUmiCommFailResumeTrapscurrentDescription.
1.3.6.1.4.1.2011.6.164.2.1.0.73NotificationhwShortTestFailTrapscurrentDescription.
1.3.6.1.4.1.2011.6.164.2.1.0.74NotificationhwShortTestFailResumeTrapscurrentDescription.
1.3.6.1.4.1.2011.6.164.2.1.0.75NotificationhwMissingBattTempSensorTrapscurrentDescription.
1.3.6.1.4.1.2011.6.164.2.1.0.76NotificationhwMissingBattTempSensorResumeTrapscurrentDescription.
1.3.6.1.4.1.2011.6.164.2.1.0.77NotificationhwBattTempSensorFaultTrapscurrentDescription.
1.3.6.1.4.1.2011.6.164.2.1.0.78NotificationhwBattTempSensorFaultResumeTrapscurrentDescription.
1.3.6.1.4.1.2011.6.164.2.1.0.79NotificationhwAcOverVoltageTrapscurrentDescription.
1.3.6.1.4.1.2011.6.164.2.1.0.80NotificationhwAcOverVoltageResumeTrapscurrentDescription.
1.3.6.1.4.1.2011.6.164.2.1.0.81NotificationhwAcUnderVoltageTrapscurrentDescription.
1.3.6.1.4.1.2011.6.164.2.1.0.82NotificationhwAcUnderVoltageResumeTrapscurrentDescription.
1.3.6.1.4.1.2011.6.164.2.1.0.83NotificationhwPDELoadFaultTrapscurrentDescription.
1.3.6.1.4.1.2011.6.164.2.1.0.84NotificationhwPDELoadFaultResumeTrapscurrentDescription.
1.3.6.1.4.1.2011.6.164.2.1.0.85NotificationhwPDENoResponseTrapscurrentDescription.
1.3.6.1.4.1.2011.6.164.2.1.0.86NotificationhwPDENoResponseResumeTrapscurrentDescription.
1.3.6.1.4.1.2011.6.164.2.1.0.87NotificationhwPDEFailureTrapscurrentDescription.
1.3.6.1.4.1.2011.6.164.2.1.0.88NotificationhwPDEFailureResumeTrapscurrentDescription.
1.3.6.1.4.1.2011.6.164.2.1.0.89NotificationhwPDEBr1FailureTrapscurrentDescription.
1.3.6.1.4.1.2011.6.164.2.1.0.90NotificationhwPDEBr1FailureResumeTrapscurrentDescription.
1.3.6.1.4.1.2011.6.164.2.1.0.91NotificationhwPDEBr2FailureTrapscurrentDescription.
1.3.6.1.4.1.2011.6.164.2.1.0.92NotificationhwPDEBr2FailureResumeTrapscurrentDescription.
1.3.6.1.4.1.2011.6.164.2.1.0.93NotificationhwPDEBr3FailureTrapscurrentDescription.
1.3.6.1.4.1.2011.6.164.2.1.0.94NotificationhwPDEBr3FailureResumeTrapscurrentDescription.
1.3.6.1.4.1.2011.6.164.2.1.0.95NotificationhwPDEBr4FailureTrapscurrentDescription.
1.3.6.1.4.1.2011.6.164.2.1.0.96NotificationhwPDEBr4FailureResumeTrapscurrentDescription.
1.3.6.1.4.1.2011.6.164.2.1.0.97NotificationhwPDEBr1ProtectTrapscurrentDescription.
1.3.6.1.4.1.2011.6.164.2.1.0.98NotificationhwPDEBr1ProtectResumeTrapscurrentDescription.
1.3.6.1.4.1.2011.6.164.2.1.0.99NotificationhwPDEBr2ProtectTrapscurrentDescription.
1.3.6.1.4.1.2011.6.164.2.1.0.100NotificationhwPDEBr2ProtectResumeTrapscurrentDescription.
1.3.6.1.4.1.2011.6.164.2.1.0.101NotificationhwPDEBr3ProtectTrapscurrentDescription.
1.3.6.1.4.1.2011.6.164.2.1.0.102NotificationhwPDEBr3ProtectResumeTrapscurrentDescription.
1.3.6.1.4.1.2011.6.164.2.1.0.103NotificationhwPDEBr4ProtectTrapscurrentDescription.
1.3.6.1.4.1.2011.6.164.2.1.0.104NotificationhwPDEBr4ProtectResumeTrapscurrentDescription.
1.3.6.1.4.1.2011.6.164.2.1.0.105NotificationhwPDELostTrapscurrentDescription.
1.3.6.1.4.1.2011.6.164.2.1.0.106NotificationhwPDELostResumeTrapscurrentDescription.
1.3.6.1.4.1.2011.6.164.2.2NodehwSiteDevicesTraps
1.3.6.1.4.1.2011.6.164.2.2.0NodehwDevicesTrapsPrefix
1.3.6.1.4.1.2011.6.164.2.3NodehwV101SiteDevicesTraps
1.3.6.1.4.1.2011.6.164.2.3.1NodehwV101DevicesTrapsPrefix
1.3.6.1.4.1.2011.6.164.2.3.1.1NotificationhwRectifiersInslotChangecurrentWhen the presence status of a rectifier changes, the node reports an event. Then the NMS adds or deletes the corresponding entry to or from hwRectConfigTable o…
1.3.6.1.4.1.2011.6.164.2.3.1.2NotificationhwBatterysInslotChangecurrentWhen the presence status of a battery string changes, the node reports an event. Then the NMS adds or deletes the corresponding entry to or from hwBatttConfigT…
1.3.6.1.4.1.2011.6.164.2.3.1.3NotificationhwBattTestRecordsAddcurrentAfter a new discharge test is conducted on a battery group, the node reports an event. The bound information includes the site address, site name, site descrip…
1.3.6.1.4.1.2011.6.164.2.3.1.4NotificationhwEnvTempSensInslotChangecurrentWhen the presence status of an environment temperature sensor changes, the node reports an event. Then the NMS adds or deletes the corresponding entry to or fr…
1.3.6.1.4.1.2011.6.164.2.3.1.5NotificationhwEnvHumiSensInslotChangecurrentWhen the presence status of an environment humidity sensor changes, the trap reports an event. Then the NMS adds or deletes the corresponding entry to or from …
1.3.6.1.4.1.2011.6.164.2.3.1.6NotificationhwPDEsInslotChangecurrentDescription.
1.3.6.1.4.1.2011.6.164.3NodehwSiteMonitorMIBConformance
1.3.6.1.4.1.2011.6.164.3.1NodehwSiteMonitorGroups
1.3.6.1.4.1.2011.6.164.3.1.1GrouphwSiteInfoGroupcurrentSite information group.
1.3.6.1.4.1.2011.6.164.3.1.2GrouphwSiteMonitorsGroupcurrentSite monitor group.
1.3.6.1.4.1.2011.6.164.3.1.3GrouphwSiteRectifiersGroupcurrentSite rectifier group.
1.3.6.1.4.1.2011.6.164.3.1.4GrouphwSiteBatterysGroupcurrentSite battery group.
1.3.6.1.4.1.2011.6.164.3.1.5GrouphwSiteAcDistributionsGroupcurrentSite AC distribution group.
1.3.6.1.4.1.2011.6.164.3.1.6GrouphwSiteDcDistributionsGroupcurrentSite DC distribution group.
1.3.6.1.4.1.2011.6.164.3.1.7GrouphwSiteLvdUnitsGroupcurrentSite low voltage disconnection unit group.
1.3.6.1.4.1.2011.6.164.3.1.8GrouphwSiteEnvUnitsGroupcurrentSite envirenment unit group.
1.3.6.1.4.1.2011.6.164.3.1.9GrouphwSiteAlarmTrapsGroupcurrentSite alarm trap group.
1.3.6.1.4.1.2011.6.164.3.1.10GrouphwSiteDeviceTrapsGroupcurrentDescription.
1.3.6.1.4.1.2011.6.164.3.1.11GrouphwSiteEfusesGroupcurrentDescription.
Type Definitions
NameSyntaxStatusDescription
DateAndTimeOCTET STRING (SIZE (8..11))currentDescription.
DisplayStringOCTET STRING (SIZE (1..64))currentDescription.
MeasuresRangeInteger32currentDescription.
RowStatusINTEGER { active(1), notInService(2), notReady(3), createAndGo(4), createAndWait(5), destroy(6) }currentDescription.
RunStatusINTEGER { unknow(1), normal(2), alarm(3) }currentThis integer value represents running status of the system. Depending on situation there may be limits on allowed values. Operational values: (1) unknown - status has not yet been defined (2) normal - there are no activ…
TruthValueINTEGER { true(1), flase(2) }currentDescription.