MIB Viewer

ISPRO-MIB

138 objects
No module-level DESCRIPTION found.
Imported Objects
RFC-1212OBJECT-TYPE
RFC1155-SMIenterprises IpAddress
RFC1213-MIBDisplayString
OIDNameAccessStatusDescription
1.3.6.1.4.1.19011Nodejacarta
1.3.6.1.4.1.19011.1Nodeproduct
1.3.6.1.4.1.19011.1.3NodewebAppliance
1.3.6.1.4.1.19011.1.3.2Nodeispro
1.3.6.1.4.1.19011.1.3.2.1NodeisObjects
1.3.6.1.4.1.19011.1.3.2.1.1NodeisIdent
1.3.6.1.4.1.19011.1.3.2.1.1.1ScalarisIdentManufacturerread-onlymandatoryThe name of the ispro manufacturer.
1.3.6.1.4.1.19011.1.3.2.1.1.2ScalarisIdentModelread-onlymandatoryThe ispro Model designation.
1.3.6.1.4.1.19011.1.3.2.1.1.3ScalarisIdentAgentSoftwareVersionread-onlymandatoryThe ispro software/firmware version. This variable may or may not have the same value as upsIdentUPSSoftwareVersion in some implementations.
1.3.6.1.4.1.19011.1.3.2.1.1.4ScalarisIdentNameread-writemandatoryA string identifying the ispro. This object should be set by the administrator.
1.3.6.1.4.1.19011.1.3.2.1.2NodeisConfig
1.3.6.1.4.1.19011.1.3.2.1.2.1ScalarisConfigMibVersionread-onlymandatoryThe version of MIB spec.
1.3.6.1.4.1.19011.1.3.2.1.2.2NodeisConfigNetwork
1.3.6.1.4.1.19011.1.3.2.1.2.2.1ScalarisConfigIpAddressread-writemandatoryThe ip address that NMS can identify the managed device
1.3.6.1.4.1.19011.1.3.2.1.2.2.2ScalarisConfigGatewayread-writemandatoryThe default gateway that allow device managed through routers
1.3.6.1.4.1.19011.1.3.2.1.2.2.3ScalarisConfigSubnetMaskread-writemandatoryInternet address subnet mask
1.3.6.1.4.1.19011.1.3.2.1.2.3NodeisConfigDateTime
1.3.6.1.4.1.19011.1.3.2.1.2.3.1ScalarisConfigDateread-writemandatoryThe date in ispro, format ask the Date Format of references
1.3.6.1.4.1.19011.1.3.2.1.2.3.2ScalarisConfigTimeread-writemandatoryThe time of ispro, format is (hh:mm:ss)
1.3.6.1.4.1.19011.1.3.2.1.2.3.3ScalarisConfigTimeFromNtpread-writemandatoryEnable/disable update date/time from NTP server.
1.3.6.1.4.1.19011.1.3.2.1.2.3.4ScalarisConfigNtpIpAddressread-writemandatoryNTP IP address.
1.3.6.1.4.1.19011.1.3.2.1.2.3.5ScalarisConfigNtpTimeZoneread-writemandatoryConfigure the time zone of ispro to access NTP server.
1.3.6.1.4.1.19011.1.3.2.1.2.3.6ScalarisConfigDayLightSavingread-writemandatoryEnable/disable daylight saving for NTP time, if enabled, the time get from NTP will be set set one hour in advance to reflect daylight saving status.
1.3.6.1.4.1.19011.1.3.2.1.2.4NodeisConfigLog
1.3.6.1.4.1.19011.1.3.2.1.2.4.1ScalarisConfigHistoryLogFrequencyread-writemandatoryThe frequency of the history log updates. The value is in seconds
1.3.6.1.4.1.19011.1.3.2.1.2.4.2ScalarisConfigExtHistoryLogFrequencyread-writemandatoryThe frequency of the extended history log updates. The value is in seconds
1.3.6.1.4.1.19011.1.3.2.1.2.4.3ScalarisConfigConfigurationLogread-writemandatoryEnable/disable ispro to log parameters change.
1.3.6.1.4.1.19011.1.3.2.1.2.4.4ScalarisConfigLogTyperead-onlymandatoryThe type of log in agent
1.3.6.1.4.1.19011.1.3.2.1.2.5ScalarisConfigDhcpStateread-writemandatoryEnable or disable DHCP/BootP capability
1.3.6.1.4.1.19011.1.3.2.1.2.6ScalarisConfigPingStateread-writemandatoryEnable or disable Ping Echo capability
1.3.6.1.4.1.19011.1.3.2.1.2.7ScalarisConfigTftpStateread-writemandatoryEnable or disable TFTP network upgrade capability
1.3.6.1.4.1.19011.1.3.2.1.2.8NodeisConfigTelnet
1.3.6.1.4.1.19011.1.3.2.1.2.8.1ScalarisConfigTelnetStateread-writemandatoryEnable or disable telnet access
1.3.6.1.4.1.19011.1.3.2.1.2.8.2ScalarisConfigTelnetPortNumberread-writemandatorySetting the server port of telnet.
1.3.6.1.4.1.19011.1.3.2.1.2.9NodeisConfigHttp
1.3.6.1.4.1.19011.1.3.2.1.2.9.1ScalarisConfigHttpStateread-writemandatoryEnable or disable HTTP access
1.3.6.1.4.1.19011.1.3.2.1.2.9.2ScalarisConfigHttpPortNumberread-writemandatorySetting the server port of HTTP.
1.3.6.1.4.1.19011.1.3.2.1.2.9.3ScalarisConfigHttpSecurityread-writemandatoryEnable/disable HTTP access for read-only users
1.3.6.1.4.1.19011.1.3.2.1.2.10NodeisConfigSnmp
1.3.6.1.4.1.19011.1.3.2.1.2.10.1ScalarisConfigSnmpStateread-writemandatoryEnable or disable SNMP access
1.3.6.1.4.1.19011.1.3.2.1.2.10.2ScalarisConfigSnmpPortNumberread-writemandatorySetting the server port of SNMP.
1.3.6.1.4.1.19011.1.3.2.1.2.11NodeisConfigControl
1.3.6.1.4.1.19011.1.3.2.1.2.11.1ScalarisConfigResetToDefaultread-writemandatoryReset all parameters of ispro to default value
1.3.6.1.4.1.19011.1.3.2.1.2.11.2ScalarisConfigRestartread-writemandatoryRestart ispro
1.3.6.1.4.1.19011.1.3.2.1.2.12NodeisConfigTrap
1.3.6.1.4.1.19011.1.3.2.1.2.12.1ScalarisConfigTrapRetryCountread-writemandatoryThe count of repeat traps to send to NMS before trap acknowledge received.
1.3.6.1.4.1.19011.1.3.2.1.2.12.2ScalarisConfigTrapRetryTimeread-writemandatoryThe time between retry traps send to NMS.
1.3.6.1.4.1.19011.1.3.2.1.2.12.3ScalarisConfigTrapAckSignatureread-writemandatoryThe signature of trap acknowledge.
1.3.6.1.4.1.19011.1.3.2.1.2.13ScalarisConfigRefreshRateread-writemandatoryThe frequency that ispro refresh web page from agent (unit : second).
1.3.6.1.4.1.19011.1.3.2.1.2.14TableisConfigTrapReceiverTablenot-accessiblemandatoryA list of managers to send traps to. The number of entries is given by the value of isConfigNumTrapReceivers
1.3.6.1.4.1.19011.1.3.2.1.2.14.1RowisConfigTrapReceiverEntrynot-accessiblemandatoryThe managers to send traps to.
1.3.6.1.4.1.19011.1.3.2.1.2.14.1.1ColumnisReceiverIndexread-onlymandatoryThe index to a trap receiver entry.
1.3.6.1.4.1.19011.1.3.2.1.2.14.1.2ColumnisReceiverAddrread-writemandatoryThe IP address of the manager to send a trap to.
1.3.6.1.4.1.19011.1.3.2.1.2.14.1.3ColumnisReceiverCommunityStringread-writemandatoryThe community name to use in the trap when sent to the manager.
1.3.6.1.4.1.19011.1.3.2.1.2.14.1.4ColumnisReceiverSeverityLevelread-writemandatoryThe severity level of traps to be received by this manager.
1.3.6.1.4.1.19011.1.3.2.1.2.14.1.5ColumnisReceiverDescriptionread-writemandatoryDescription of trap receivers
1.3.6.1.4.1.19011.1.3.2.1.2.15TableisConfigAccessControlTablenot-accessiblemandatoryA list of managers which can access ispro with private community string.
1.3.6.1.4.1.19011.1.3.2.1.2.15.1RowisConfigAccessControlEntrynot-accessiblemandatoryThe managers.
1.3.6.1.4.1.19011.1.3.2.1.2.15.1.1ColumnisAccessIndexread-onlymandatoryThe index to an access control entry.
1.3.6.1.4.1.19011.1.3.2.1.2.15.1.2ColumnisAccessControlAddrread-writemandatoryThe IP address of the manager to access ispro
1.3.6.1.4.1.19011.1.3.2.1.2.15.1.3ColumnisAccessCommunityStringread-writemandatoryThe community name to use in the manager when access ispro
1.3.6.1.4.1.19011.1.3.2.1.2.15.1.4ColumnisAccessControlModeread-writemandatoryAccess type, only read/Write access type can change parameter of ispro
1.3.6.1.4.1.19011.1.3.2.1.2.15.1.5ColumnisAccessAccountread-writemandatoryAccess account, the account for web login to access ispro
1.3.6.1.4.1.19011.1.3.2.1.2.16ScalarisConfigTemperatureUnitread-writemandatoryThe temperature unit of the system, can be Celsius or Fahrenheit
1.3.6.1.4.1.19011.1.3.2.1.2.17ScalarisConfigDateFormatread-writemandatoryThe date format of the system, can be dd/mm/yyyy or mm/dd/yyyy
1.3.6.1.4.1.19011.1.3.2.1.3NodeisDevice
1.3.6.1.4.1.19011.1.3.2.1.3.1NodeisDeviceMonitor
1.3.6.1.4.1.19011.1.3.2.1.3.1.1TableisDeviceMonitorTemperatureTablenot-accessiblemandatoryThe temperature monitoring table, to provides overall status of temperature.
1.3.6.1.4.1.19011.1.3.2.1.3.1.1.1RowisDeviceMonitorTemperatureEntrynot-accessiblemandatoryThe temperature monitoring table, to provides overall status of temperature.
1.3.6.1.4.1.19011.1.3.2.1.3.1.1.1.1ColumnisDeviceMonitorTemperatureIndexread-onlymandatoryThe index to a temperature entry.
1.3.6.1.4.1.19011.1.3.2.1.3.1.1.1.2ColumnisDeviceMonitorTemperatureNameread-onlymandatoryThe temperature sensor name.
1.3.6.1.4.1.19011.1.3.2.1.3.1.1.1.3ColumnisDeviceMonitorTemperatureread-onlymandatoryThe temperature of sensor on device Ispro, the unit is 0.01 degree.
1.3.6.1.4.1.19011.1.3.2.1.3.1.1.1.4ColumnisDeviceMonitorTemperatureAlarmread-onlymandatoryThe status of temperature sensor in Ispro.
1.3.6.1.4.1.19011.1.3.2.1.3.1.2TableisDeviceMonitorHumidityTablenot-accessiblemandatoryThe humidity monitoring table, to provides overall status of humidity.
1.3.6.1.4.1.19011.1.3.2.1.3.1.2.1RowisDeviceMonitorHumidityEntrynot-accessiblemandatoryThe humidity monitoring table, to provides overall status of humidity.
1.3.6.1.4.1.19011.1.3.2.1.3.1.2.1.1ColumnisDeviceMonitorHumidityIndexread-onlymandatoryThe index to a humidity entry.
1.3.6.1.4.1.19011.1.3.2.1.3.1.2.1.2ColumnisDeviceMonitorHumidityNameread-onlymandatoryThe humidity sensor name.
1.3.6.1.4.1.19011.1.3.2.1.3.1.2.1.3ColumnisDeviceMonitorHumidityread-onlymandatoryThe humidity of sensor on device Ispro, the unit is 0.01 %.
1.3.6.1.4.1.19011.1.3.2.1.3.1.2.1.4ColumnisDeviceMonitorHumidityAlarmread-onlymandatoryThe status of humidity sensor in Ispro.
1.3.6.1.4.1.19011.1.3.2.1.3.1.3TableisDeviceMonitorDigitalInTablenot-accessiblemandatoryThe digital input monitoring table, to provides overall status of digital input.
1.3.6.1.4.1.19011.1.3.2.1.3.1.3.1RowisDeviceMonitorDigitalInEntrynot-accessiblemandatoryThe digital input monitoring table, to provides overall status of digital input.
1.3.6.1.4.1.19011.1.3.2.1.3.1.3.1.1ColumnisDeviceMonitorDigitalInIndexread-onlymandatoryThe index to a digital input entry.
1.3.6.1.4.1.19011.1.3.2.1.3.1.3.1.2ColumnisDeviceMonitorDigitalInNameread-onlymandatoryThe digital input sensor name.
1.3.6.1.4.1.19011.1.3.2.1.3.1.3.1.3ColumnisDeviceMonitorDigitalInread-onlymandatoryThe digital input of sensor on device Ispro.
1.3.6.1.4.1.19011.1.3.2.1.3.1.3.1.4ColumnisDeviceMonitorDigitalInAlarmread-onlymandatoryThe status of digital alarm sensor.
1.3.6.1.4.1.19011.1.3.2.1.3.2NodeisDeviceConfig
1.3.6.1.4.1.19011.1.3.2.1.3.2.1TableisDeviceConfigTablenot-accessiblemandatoryThe device configuration table.
1.3.6.1.4.1.19011.1.3.2.1.3.2.1.1RowisDeviceConfigEntrynot-accessiblemandatoryThe device configuration table.
1.3.6.1.4.1.19011.1.3.2.1.3.2.1.1.1ColumnisDeviceConfigIndexread-onlymandatoryThe index to a sensor entry.
1.3.6.1.4.1.19011.1.3.2.1.3.2.1.1.2ColumnisDeviceConfigNameread-writemandatoryThe name of sensor device.
1.3.6.1.4.1.19011.1.3.2.1.3.2.1.1.3ColumnisDeviceConfigStateread-writemandatoryThe setup of device type.
1.3.6.1.4.1.19011.1.3.2.1.3.2.1.1.4ColumnisDeviceConfigDisplayread-writemandatoryEnable or disable of displaying this sensor in Comprehensive webpage.
1.3.6.1.4.1.19011.1.3.2.1.3.2.2TableisDeviceConfigTemperatureTablenot-accessiblemandatoryThe temperature configuration table of Device.
1.3.6.1.4.1.19011.1.3.2.1.3.2.2.1RowisDeviceConfigTemperatureEntrynot-accessiblemandatoryThe sensor configuration table of Device.
1.3.6.1.4.1.19011.1.3.2.1.3.2.2.1.1ColumnisDeviceConfigTemperatureIndexread-onlymandatoryThe index to a temperature device entry.
1.3.6.1.4.1.19011.1.3.2.1.3.2.2.1.2ColumnisDeviceConfigTemperatureNameread-writemandatoryThe temperature sensor name.
1.3.6.1.4.1.19011.1.3.2.1.3.2.2.1.3ColumnisDeviceConfigTemperatureLowWarningread-writemandatoryThe set point to trigger low warning alarm. the unit is 0.01 degree.
1.3.6.1.4.1.19011.1.3.2.1.3.2.2.1.4ColumnisDeviceConfigTemperatureLowCriticalread-writemandatoryThe threshold to trigger low critical alarm. the unit is 0.01 degree.
1.3.6.1.4.1.19011.1.3.2.1.3.2.2.1.5ColumnisDeviceConfigTemperatureHighWarningread-writemandatoryThe threshold to trigger high warning alarm. the unit is 0.01 degree.
1.3.6.1.4.1.19011.1.3.2.1.3.2.2.1.6ColumnisDeviceConfigTemperatureHighCriticalread-writemandatoryThe threshold to trigger high critical alarm. the unit is 0.01 degree.
1.3.6.1.4.1.19011.1.3.2.1.3.2.2.1.7ColumnisDeviceConfigTemperatureHysteresisread-writemandatoryThe set value to prevent too many alarms when temperature is hovering around the set threshold. The unit is 0.01
1.3.6.1.4.1.19011.1.3.2.1.3.2.2.1.8ColumnisDeviceConfigTemperatureCalibrationread-writemandatoryThe set value to get the correct temperature according to your reference temperature.
1.3.6.1.4.1.19011.1.3.2.1.3.2.2.1.9ColumnisDeviceConfigTemperatureLowWarningStateread-writemandatoryEnable/disable the set point to trigger low warning alarm.
1.3.6.1.4.1.19011.1.3.2.1.3.2.2.1.10ColumnisDeviceConfigTemperatureLowCriticalStateread-writemandatoryEnable/disable the set point to trigger low critical alarm.
1.3.6.1.4.1.19011.1.3.2.1.3.2.2.1.11ColumnisDeviceConfigTemperatureHighWarningStateread-writemandatoryEnable/disable the set point to trigger high warning alarm.
1.3.6.1.4.1.19011.1.3.2.1.3.2.2.1.12ColumnisDeviceConfigTemperatureHighCriticalStateread-writemandatoryEnable/disable the set point to trigger high critical alarm.
1.3.6.1.4.1.19011.1.3.2.1.3.2.2.1.13ColumnisDeviceConfigTemperatureEventDOread-writemandatorySet the trigger action of temperature events. If event asserted, this will invert the digital output #1 or #2.
1.3.6.1.4.1.19011.1.3.2.1.3.2.3TableisDeviceConfigHumidityTablenot-accessiblemandatoryThe humidity configuration table of Device.
1.3.6.1.4.1.19011.1.3.2.1.3.2.3.1RowisDeviceConfigHumidityEntrynot-accessiblemandatoryThe humidity configuration table of Device.
1.3.6.1.4.1.19011.1.3.2.1.3.2.3.1.1ColumnisDeviceConfigHumidityIndexread-onlymandatoryThe index to a humidity device entry.
1.3.6.1.4.1.19011.1.3.2.1.3.2.3.1.2ColumnisDeviceConfigHumidityNameread-writemandatoryThe humidity sensor name.
1.3.6.1.4.1.19011.1.3.2.1.3.2.3.1.3ColumnisDeviceConfigHumidityLowWarningread-writemandatoryThe set point to trigger low warning alarm. the unit is 0.01 %.
1.3.6.1.4.1.19011.1.3.2.1.3.2.3.1.4ColumnisDeviceConfigHumidityLowCriticalread-writemandatoryThe threshold to trigger low critical alarm. the unit is 0.01 %.
1.3.6.1.4.1.19011.1.3.2.1.3.2.3.1.5ColumnisDeviceConfigHumidityHighWarningread-writemandatoryThe threshold to trigger high warning alarm. the unit is 0.01 %.
1.3.6.1.4.1.19011.1.3.2.1.3.2.3.1.6ColumnisDeviceConfigHumidityHighCriticalread-writemandatoryThe threshold to trigger high critical alarm. the unit is 0.01 %.
1.3.6.1.4.1.19011.1.3.2.1.3.2.3.1.7ColumnisDeviceConfigHumidityHysteresisread-writemandatoryThe set value to prevent too many alarms when Humidity is hovering around the set threshold. The unit is 0.01
1.3.6.1.4.1.19011.1.3.2.1.3.2.3.1.8ColumnisDeviceConfigHumidityCalibrationread-writemandatoryThe set value to get the correct temperature according to your reference temperature.
1.3.6.1.4.1.19011.1.3.2.1.3.2.3.1.9ColumnisDeviceConfigHumidityLowWarningStateread-writemandatoryEnable/disable the set point to trigger low warning alarm.
1.3.6.1.4.1.19011.1.3.2.1.3.2.3.1.10ColumnisDeviceConfigHumidityLowCriticalStateread-writemandatoryEnable/disable the set point to trigger low critical alarm.
1.3.6.1.4.1.19011.1.3.2.1.3.2.3.1.11ColumnisDeviceConfigHumidityHighWarningStateread-writemandatoryEnable/disable the set point to trigger high warning alarm.
1.3.6.1.4.1.19011.1.3.2.1.3.2.3.1.12ColumnisDeviceConfigHumidityHighCriticalStateread-writemandatoryEnable/disable the set point to trigger high critical alarm.
1.3.6.1.4.1.19011.1.3.2.1.3.2.3.1.13ColumnisDeviceConfigHumidityEventDOread-writemandatorySet the trigger action of humidity events. If event asserted, this will invert the digital output #1 or #2.
1.3.6.1.4.1.19011.1.3.2.1.3.2.4TableisDeviceConfigDigitalInTablenot-accessiblemandatoryThe digital input configuration table of Device.
1.3.6.1.4.1.19011.1.3.2.1.3.2.4.1RowisDeviceConfigDigitalInEntrynot-accessiblemandatoryThe digital input configuration table of Device.
1.3.6.1.4.1.19011.1.3.2.1.3.2.4.1.1ColumnisDeviceConfigDigitalInIndexread-onlymandatoryThe index to a digital input device entry.
1.3.6.1.4.1.19011.1.3.2.1.3.2.4.1.2ColumnisDeviceConfigDigitalInNameread-writemandatoryThe name of digital input.
1.3.6.1.4.1.19011.1.3.2.1.3.2.4.1.3ColumnisDeviceConfigDigitalInStateread-writemandatorySetup the signal type to trigger alarm.
1.3.6.1.4.1.19011.1.3.2.1.3.2.4.1.4ColumnisDeviceConfigDigitalInHysteresisread-writemandatoryThe set value to delay the alarm triggered when event occurs.
1.3.6.1.4.1.19011.1.3.2.1.3.2.4.1.5ColumnisDeviceConfigDigitalInEventDOread-writemandatorySet the trigger action of digital alarm #1 events. If event asserted, this will invert the digital output #1 or #2.
1.3.6.1.4.1.19011.1.3.2.1.3.2.5TableisDeviceDigitalOutTablenot-accessiblemandatoryThe configuration table of Device digital output.
1.3.6.1.4.1.19011.1.3.2.1.3.2.5.1RowisDeviceDigitalOutEntrynot-accessiblemandatoryThe configuration table of Device digital output.
1.3.6.1.4.1.19011.1.3.2.1.3.2.5.1.1ColumnisDeviceDigitalOutIndexread-onlymandatoryThe index is 1 and 2, it maps to digital output 1 and 2.
1.3.6.1.4.1.19011.1.3.2.1.3.2.5.1.2ColumnisDeviceDigitalOutStartStateread-writemandatoryTurn power on/off specific digital output when system start up.
1.3.6.1.4.1.19011.1.3.2.1.3.2.5.1.3ColumnisDeviceDigitalOutEventActionread-writemandatoryIf select yes, it will invert the current status of specific digital output when Ispro event occurred.
1.3.6.1.4.1.19011.1.3.2.1.3.2.5.1.4ColumnisDeviceDigitalOutManualControlread-writemandatoryInvert current status of specific digital output manually.
1.3.6.1.4.1.19011.1.3.2.1.3.3ScalarisDeviceIDread-onlymandatoryThe device board id.
1.3.6.1.4.1.19011.1.3.2.2NodeisTraps
1.3.6.1.4.1.19011.1.3.2.2.1ScalarisTrapsDescriptionread-onlymandatoryThe description of current trap