KELVIN-pCOWeb-Chiller-MIB
373 objects
This is the MIB module for the kelvin-pCOWeb-Chiller device.
Imported Objects
| SNMPv2-CONF | OBJECT-GROUP |
| SNMPv2-MIB | sysContact sysLocation sysName |
| SNMPv2-SMI | enterprises Integer32 MODULE-IDENTITY NOTIFICATION-TYPE OBJECT-TYPE |
| OID | Name | Access | Status | Description |
|---|---|---|---|---|
| 1.3.6.1.4.1.9839 | Nodecarel | |||
| 1.3.6.1.4.1.9839.1 | Nodesystm | |||
| 1.3.6.1.4.1.9839.1.1 | ScalaragentRelease | read-only | current | Release of the Agent. |
| 1.3.6.1.4.1.9839.1.2 | ScalaragentCode | read-only | current | Code of the Agent. 2=pCOWeb. |
| 1.3.6.1.4.1.9839.2 | Nodeinstruments | |||
| 1.3.6.1.4.1.9839.2.0 | NodepCOWebInfo | |||
| 1.3.6.1.4.1.9839.2.0.10 | NodepCOStatusgroup | |||
| 1.3.6.1.4.1.9839.2.0.10.1 | ScalarpCOId1-Status | read-only | current | Status of pCOId1. 0=Offline, 1=Init, 2=Online |
| 1.3.6.1.4.1.9839.2.0.11 | NodepCOErrorsNumbergroup | |||
| 1.3.6.1.4.1.9839.2.0.11.1 | ScalarpCOId1-ErrorsNumber | read-only | current | Number of Communication Errors from pCOId1 to pCOWeb. |
| 1.3.6.1.4.1.9839.2.1 | Identitykelvin-pCOWebMIB-Chiller | This is the MIB module for the kelvin-pCOWeb-Chiller device. | ||
| 1.3.6.1.4.1.9839.2.1.1 | NodedigitalObjects | |||
| 1.3.6.1.4.1.9839.2.1.1.1 | Scalaral-pa1 | read-only | current | High pressure switch 1 alarm |
| 1.3.6.1.4.1.9839.2.1.1.2 | Scalaral-pa2 | read-only | current | High pressure switch 2 alarm |
| 1.3.6.1.4.1.9839.2.1.1.3 | Scalaral-pb1 | read-only | current | Low pressure switch 1 alarm |
| 1.3.6.1.4.1.9839.2.1.1.4 | Scalaral-pb2 | read-only | current | Low pressure switch 2 alarm |
| 1.3.6.1.4.1.9839.2.1.1.6 | Scalaral-le | read-only | current | Water level alarm |
| 1.3.6.1.4.1.9839.2.1.1.8 | Scalaral-idrofrigo-fl1 | read-only | current | Flow switch alarm |
| 1.3.6.1.4.1.9839.2.1.1.9 | Scalarstatic-press-alarm | read-only | current | Water static pressure alarm |
| 1.3.6.1.4.1.9839.2.1.1.10 | Scalarw-static-press-alarm | read-only | current | Water static pressure warning |
| 1.3.6.1.4.1.9839.2.1.1.11 | Scalarflow-value-alarm | read-only | current | Flow rate alarm |
| 1.3.6.1.4.1.9839.2.1.1.12 | Scalaral-q-comp1 | read-only | current | Overload compressor 1 circuit 1 alarm |
| 1.3.6.1.4.1.9839.2.1.1.13 | Scalaral-q-comp2 | read-only | current | Overload compressor 2 circuit 1 alarm |
| 1.3.6.1.4.1.9839.2.1.1.14 | Scalaral-q-comp3 | read-only | current | Overload compressor 3 circuit 1 alarm |
| 1.3.6.1.4.1.9839.2.1.1.15 | Scalaral-q-comp4 | read-only | current | Overload compressor 1 circuit 2 alarm |
| 1.3.6.1.4.1.9839.2.1.1.16 | Scalaral-q-comp5 | read-only | current | Overload compressor 2 circuit 2 alarm |
| 1.3.6.1.4.1.9839.2.1.1.17 | Scalaral-q-comp6 | read-only | current | Overload compressor 3 circuit 2 alarm |
| 1.3.6.1.4.1.9839.2.1.1.18 | Scalaral-q-fan-1 | read-only | current | Overload fans circuit 1 |
| 1.3.6.1.4.1.9839.2.1.1.19 | Scalaral-q-fan-2 | read-only | current | Overload fans circuit 2 |
| 1.3.6.1.4.1.9839.2.1.1.20 | Scalaral-q-fan11 | read-only | current | Overload fan 1 circuit 1 alarm |
| 1.3.6.1.4.1.9839.2.1.1.21 | Scalaral-q-fan12 | read-only | current | Overload fan 2 circuit 1 alarm |
| 1.3.6.1.4.1.9839.2.1.1.22 | Scalaral-q-fan13 | read-only | current | Overload fan 3 circuit 1 alarm |
| 1.3.6.1.4.1.9839.2.1.1.23 | Scalaral-q-fan14 | read-only | current | Overload fan 4 circuit 1 alarm |
| 1.3.6.1.4.1.9839.2.1.1.24 | Scalaral-q-fan21 | read-only | current | Overload fan 1 circuit 2 alarm |
| 1.3.6.1.4.1.9839.2.1.1.25 | Scalaral-q-fan22 | read-only | current | Overload fan 2 circuit 2 alarm |
| 1.3.6.1.4.1.9839.2.1.1.26 | Scalaral-q-fan-23 | read-only | current | Overload fan 3 circuit 2 alarm |
| 1.3.6.1.4.1.9839.2.1.1.27 | Scalaral-q-fan24 | read-only | current | Overload fan 4 circuit 2 alarm |
| 1.3.6.1.4.1.9839.2.1.1.28 | Scalaral-idrofrigo-pump1 | read-only | current | Overload pump 1 alarm |
| 1.3.6.1.4.1.9839.2.1.1.29 | Scalaral-idrofrigo-pump2 | read-only | current | Overload pump 2 alarm |
| 1.3.6.1.4.1.9839.2.1.1.30 | Scalaral-phase-cont | read-only | current | Wrong phase rotation alarm |
| 1.3.6.1.4.1.9839.2.1.1.31 | Scalaral-door-sw | read-only | current | Back Door open alarm |
| 1.3.6.1.4.1.9839.2.1.1.32 | Scalarcompressor-FlowRate | read-write | current | Compressor FlowRate Management |
| 1.3.6.1.4.1.9839.2.1.1.33 | Scalarsetpoint-inv-pumps | read-write | current | Setpoint Type for Inverter pumps |
| 1.3.6.1.4.1.9839.2.1.1.34 | Scalarenable-pumps-redundance | read-write | current | Enable Pumps redundance |
| 1.3.6.1.4.1.9839.2.1.1.35 | Scalarenable-chiller-redundance | read-write | current | Enable Chiller redundance |
| 1.3.6.1.4.1.9839.2.1.1.36 | Scalarstatus-in-alarm | read-write | current | Status in alarm |
| 1.3.6.1.4.1.9839.2.1.1.37 | Scalarcompressor-recovery | read-write | current | Compressor Recovery |
| 1.3.6.1.4.1.9839.2.1.1.38 | Scalarenable-thermal-redundance | read-write | current | Enable Thermal redundance |
| 1.3.6.1.4.1.9839.2.1.1.39 | Scalarenable-multi-pumps-function | read-write | current | Enable multi-pumps function |
| 1.3.6.1.4.1.9839.2.1.1.40 | Scalarenable-pumps-offline | read-write | current | Enable function pumps-Offline |
| 1.3.6.1.4.1.9839.2.1.1.41 | Scalarenable-3way-valve | read-write | current | Enable 3way valve |
| 1.3.6.1.4.1.9839.2.1.1.42 | Scalarenable-speed-up-FCM | read-write | current | Enable speed-up FCM |
| 1.3.6.1.4.1.9839.2.1.1.43 | Scalarenable-soft-start-FCM | read-write | current | Enable soft-start FCM |
| 1.3.6.1.4.1.9839.2.1.1.44 | Scalarenable-freecooling | read-write | current | Enable Freecooling |
| 1.3.6.1.4.1.9839.2.1.1.45 | Scalarenable-rot-FIFO-FC | read-write | current | Enable rotation FIFO Freecooling |
| 1.3.6.1.4.1.9839.2.1.1.46 | Scalarenable-HT-function | read-write | current | Enable HT-function |
| 1.3.6.1.4.1.9839.2.1.1.47 | Scalarenable-PID-Fc-valve | read-write | current | Enable PID-regulation for Freecooling valve |
| 1.3.6.1.4.1.9839.2.1.1.48 | Scalarenable-Fc-Thermal-Exclusion | read-write | current | Enable Freecooling Thermal Exclusion |
| 1.3.6.1.4.1.9839.2.1.1.49 | Scalarmanual-Reset-Ext-Drycooler-Alarm | read-write | current | Manual Reset External Dry-cooler Alarm |
| 1.3.6.1.4.1.9839.2.1.1.50 | Scalarenable-static-press-Alarm | read-write | current | Enable static pressure Alarm |
| 1.3.6.1.4.1.9839.2.1.1.51 | Scalarmanual-reset-static-press-Alarm | read-write | current | Manual reset static pressure Alarm |
| 1.3.6.1.4.1.9839.2.1.1.52 | Scalarenable-static-press-Warning | read-write | current | Enable static pressure Warning |
| 1.3.6.1.4.1.9839.2.1.1.53 | Scalarmanual-reset-static-press-Warning | read-write | current | Manual reset static pressure Warning |
| 1.3.6.1.4.1.9839.2.1.1.54 | Scalarenable-diff-press-Alarm | read-write | current | Enable differential pressure Alarm |
| 1.3.6.1.4.1.9839.2.1.1.55 | Scalarmanual-reset-diff-press-Alarm | read-write | current | Manual reset differential pressure Alarm |
| 1.3.6.1.4.1.9839.2.1.1.56 | Scalarenable-pressure-recovery | read-write | current | Enable pressure recovery |
| 1.3.6.1.4.1.9839.2.1.1.57 | Scalarenable-Flow-Rate-Alarm | read-write | current | Enable Flow-Rate Alarm |
| 1.3.6.1.4.1.9839.2.1.1.58 | Scalarmanual-reset-Flow-Rate-Alarm | read-write | current | Manual reset Flow-Rate Alarm |
| 1.3.6.1.4.1.9839.2.1.1.59 | Scalarenable-Flow-Rate-recovery | read-write | current | Enable Flow-Rate recovery |
| 1.3.6.1.4.1.9839.2.1.1.60 | Scalarenable-pCOWeb | read-write | current | Enable pCOWeb |
| 1.3.6.1.4.1.9839.2.1.1.61 | Scalarfc-single-chiller | read-write | current | Freecooling single chiller function |
| 1.3.6.1.4.1.9839.2.1.1.75 | Scalaral-idrofrigo-pump-c-1 | read-only | current | Condensation pump 1 breaker switch alarm |
| 1.3.6.1.4.1.9839.2.1.1.76 | Scalaral-idrofrigo-pump-c-2 | read-only | current | Condensation pump 2 breaker switch alarm |
| 1.3.6.1.4.1.9839.2.1.1.80 | Scalaral-idrofrigo-fl-C | read-only | current | Condensation flow switch alarm |
| 1.3.6.1.4.1.9839.2.1.1.100 | Scalarc11-on | read-only | current | Compressor 1 circuit 1 ON |
| 1.3.6.1.4.1.9839.2.1.1.101 | Scalarc12-on | read-only | current | Compressor 2 circuit 1 ON |
| 1.3.6.1.4.1.9839.2.1.1.102 | Scalarc13-on | read-only | current | Compressor 3 circuit 1 ON |
| 1.3.6.1.4.1.9839.2.1.1.103 | Scalarc21-on | read-only | current | Compressor 1 circuit 2 ON |
| 1.3.6.1.4.1.9839.2.1.1.104 | Scalarc22-on | read-only | current | Compressor 2 circuit 2 ON |
| 1.3.6.1.4.1.9839.2.1.1.105 | Scalarc23-on | read-only | current | Compressor 3 circuit 2 ON |
| 1.3.6.1.4.1.9839.2.1.1.106 | Scalarpump1-on | read-only | current | Pump 1 ON |
| 1.3.6.1.4.1.9839.2.1.1.107 | Scalarpump2-on | read-only | current | Pump 2 ON |
| 1.3.6.1.4.1.9839.2.1.1.108 | Scalaron-fan-gr1 | read-only | current | Fans group 1 ON |
| 1.3.6.1.4.1.9839.2.1.1.109 | Scalaron-fan-gr2 | read-only | current | Fans group 2 ON |
| 1.3.6.1.4.1.9839.2.1.1.110 | Scalarfc-on | read-only | current | Freecooling or external dry-cooler 1 ON |
| 1.3.6.1.4.1.9839.2.1.1.130 | Scalaren-on-off-rem | read-write | current | Remote on-off |
| 1.3.6.1.4.1.9839.2.1.1.131 | Scalarunit-on | read-write | current | Chiller ON |
| 1.3.6.1.4.1.9839.2.1.1.148 | Scalardisch-alarm-scw-1 | read-only | current | Discharge screw compressor 1 alarm |
| 1.3.6.1.4.1.9839.2.1.1.149 | Scalardisch-alarm-scw-2 | read-only | current | Discharge screw compressor 2 alarm |
| 1.3.6.1.4.1.9839.2.1.1.150 | Scalaral-probe-inlet | read-only | current | Inlet probe alarm (broken or disconnected) |
| 1.3.6.1.4.1.9839.2.1.1.151 | Scalaral-probe-amb | read-only | current | Ambient probe alarm (broken or disconnected) |
| 1.3.6.1.4.1.9839.2.1.1.152 | Scalaral-frigo-fl1 | read-only | current | Flow switch alarm (cooling alarm) |
| 1.3.6.1.4.1.9839.2.1.1.153 | Scalaral-idro-pump1 | read-only | current | Pump 1 hydraulic alarm |
| 1.3.6.1.4.1.9839.2.1.1.154 | Scalaral-idro-pump2 | read-only | current | Pump 2 hydraulic alarm |
| 1.3.6.1.4.1.9839.2.1.1.155 | Scalaral-idro-fl1 | read-only | current | Flow switch alarm (hydraulic alarm) |
| 1.3.6.1.4.1.9839.2.1.1.156 | Scalaral-warning-fl1 | read-only | current | Flow switch alarm (warning alarm) |
| 1.3.6.1.4.1.9839.2.1.1.157 | Scalaral-hi-water-temp | read-only | current | High Temperature alarm |
| 1.3.6.1.4.1.9839.2.1.1.158 | Scalaral-lo-water-temp | read-only | current | Low Temperature alarm |
| 1.3.6.1.4.1.9839.2.1.1.159 | Scalaral-ta-probe1 | read-only | current | Antifreeze/evaporator probe 1 alarm |
| 1.3.6.1.4.1.9839.2.1.1.160 | Scalaral-hi-press | read-only | current | High condensation pressure alarm |
| 1.3.6.1.4.1.9839.2.1.1.161 | Scalaral-lo-press | read-only | current | Low condensation pressure alarm |
| 1.3.6.1.4.1.9839.2.1.1.162 | Scalaral-probe-evap-1 | read-only | current | Antifreeze/evaporator probe 1 alarm (broken or disconnected) |
| 1.3.6.1.4.1.9839.2.1.1.163 | Scalaral-probe-evap-2 | read-only | current | Antifreeze/evaporator probe 2 alarm (broken or disconnected) |
| 1.3.6.1.4.1.9839.2.1.1.164 | Scalaral-hi-press-1 | read-only | current | High condensation pressure 1 alarm |
| 1.3.6.1.4.1.9839.2.1.1.165 | Scalaral-hi-press-2 | read-only | current | High condensation pressure 2 alarm |
| 1.3.6.1.4.1.9839.2.1.1.166 | Scalaral-lo-press-1 | read-only | current | Low condensation pressure 1 alarm |
| 1.3.6.1.4.1.9839.2.1.1.167 | Scalaral-lo-press-2 | read-only | current | Low condensation pressure 2 alarm |
| 1.3.6.1.4.1.9839.2.1.1.168 | Scalaral-probe-tank | read-only | current | Tank/Out probe alarm (broken or disconnected) |
| 1.3.6.1.4.1.9839.2.1.1.169 | Scalaroff-line-1 | read-only | current | Chiller 1 offline |
| 1.3.6.1.4.1.9839.2.1.1.170 | Scalaroff-line-2 | read-only | current | Chiller 2 offline |
| 1.3.6.1.4.1.9839.2.1.1.171 | Scalaroff-line-3 | read-only | current | Chiller 3 offline |
| 1.3.6.1.4.1.9839.2.1.1.172 | Scalaroff-line-4 | read-only | current | Chiller 4 offline |
| 1.3.6.1.4.1.9839.2.1.1.173 | Scalaroff-line-5 | read-only | current | Chiller 5 offline |
| 1.3.6.1.4.1.9839.2.1.1.174 | Scalaroff-line-6 | read-only | current | Chiller 6 offline |
| 1.3.6.1.4.1.9839.2.1.1.175 | Scalaroff-line-7 | read-only | current | Chiller 7 offline |
| 1.3.6.1.4.1.9839.2.1.1.176 | Scalaroff-line-8 | read-only | current | Chiller 8 offline |
| 1.3.6.1.4.1.9839.2.1.1.177 | Scalaral-ta-probe2 | read-only | current | Antifreeze/evaporator probe 2 alarm |
| 1.3.6.1.4.1.9839.2.1.1.178 | Scalaral-sms | read-only | current | SMS alarm |
| 1.3.6.1.4.1.9839.2.1.1.179 | Scalaral-modem | read-only | current | Modem alarm |
| 1.3.6.1.4.1.9839.2.1.1.180 | Scalarsms-coda-alarm | read-only | current | SMS coda alarm |
| 1.3.6.1.4.1.9839.2.1.1.181 | Scalaral-probe-fc | read-only | current | Freecooling probe alarm (broken or disconnected) |
| 1.3.6.1.4.1.9839.2.1.1.182 | Scalaral-maint-pw1 | read-only | current | Maintenance pump 1 alarm) |
| 1.3.6.1.4.1.9839.2.1.1.183 | Scalaral-maint-pw2 | read-only | current | Maintenance pump 2 alarm) |
| 1.3.6.1.4.1.9839.2.1.1.184 | Scalaral-hi-temp-rid | read-only | current | High temperature alarm (redundance) |
| 1.3.6.1.4.1.9839.2.1.1.185 | Scalaral-q-fc-sep | read-only | current | DryCooler breaker switch alarm |
| 1.3.6.1.4.1.9839.2.1.1.186 | Scalaral-p-wat2 | read-only | current | Water pressure 2 alarm |
| 1.3.6.1.4.1.9839.2.1.1.187 | Scalaral-p-wat1 | read-only | current | Water pressure 1 alarm |
| 1.3.6.1.4.1.9839.2.1.1.188 | Scalaral-foult-flow-p1 | read-only | current | Pump 1 flow alarm |
| 1.3.6.1.4.1.9839.2.1.1.189 | Scalaral-foult-flow-p2 | read-only | current | Pump 2 flow alarm |
| 1.3.6.1.4.1.9839.2.1.1.190 | Scalaral-foult-fl1-p1 | read-only | current | Pump 1 flow-switch alarm |
| 1.3.6.1.4.1.9839.2.1.1.191 | Scalaral-foult-fl1-p2 | read-only | current | Pump 2 flow-switch alarm |
| 1.3.6.1.4.1.9839.2.1.1.192 | Scalaral-warning-le | read-only | current | Water level warning |
| 1.3.6.1.4.1.9839.2.1.1.193 | Scalaral-frigo-fl-C | read-only | current | Flow switch condensation alarm (cooling alarm) |
| 1.3.6.1.4.1.9839.2.1.1.194 | Scalaral-idro-pump-c-1 | read-only | current | Pump 1 condensation hydraulic alarm |
| 1.3.6.1.4.1.9839.2.1.1.195 | Scalaral-idro-pump-c-2 | read-only | current | Pump 2 condensation hydraulic alarm |
| 1.3.6.1.4.1.9839.2.1.1.196 | Scalaral-idro-fl-C | read-only | current | Flow switch condensation alarm (hydraulic alarm) |
| 1.3.6.1.4.1.9839.2.1.1.197 | Scalaral-warning-fl-C | read-only | current | Flow switch condensation alarm (warning alarm) |
| 1.3.6.1.4.1.9839.2.1.1.198 | Scalaral-foul-fl-C-p1 | read-only | current | Pump 1 condensation flow-switch alarm |
| 1.3.6.1.4.1.9839.2.1.1.199 | Scalaral-foul-fl-C-p2 | read-only | current | Pump 2 condensation flow-switch alarm |
| 1.3.6.1.4.1.9839.2.1.2 | NodeanalogObjects | |||
| 1.3.6.1.4.1.9839.2.1.2.1 | Scalarsetpoint-antifreeze1 | read-write | current | Setpoint Antifreeze 1 |
| 1.3.6.1.4.1.9839.2.1.2.2 | Scalarsetpoint-antifreeze2 | read-write | current | Setpoint Antifreeze 2 |
| 1.3.6.1.4.1.9839.2.1.2.3 | Scalarsetpoint-Compensation | read-write | current | Setpoint Compensation |
| 1.3.6.1.4.1.9839.2.1.2.4 | Scalarhysteresis-Compensation | read-write | current | Hysteresis Compensation |
| 1.3.6.1.4.1.9839.2.1.2.5 | Scalarmax-Compensation | read-write | current | Max. Compensation |
| 1.3.6.1.4.1.9839.2.1.2.6 | Scalarsetpoint-Differential | read-write | current | Setpoint Differential |
| 1.3.6.1.4.1.9839.2.1.2.7 | Scalarhigh-Limit | read-write | current | High Limit |
| 1.3.6.1.4.1.9839.2.1.2.8 | Scalarlow-Limit | read-write | current | Low Limit |
| 1.3.6.1.4.1.9839.2.1.2.9 | Scalarmax-Setpoint-Differential | read-write | current | Max. Setpoint Differential |
| 1.3.6.1.4.1.9839.2.1.2.10 | Scalarmin-Setpoint-Differential | read-write | current | Min. Setpoint Differential |
| 1.3.6.1.4.1.9839.2.1.2.11 | Scalarsetpoint-ASB-Inverter-pumps | read-write | current | Setpoint ASB Inverter pumps |
| 1.3.6.1.4.1.9839.2.1.2.12 | Scalarsetpoint-DIFF-Inverter-pumps | read-write | current | Setpoint DIFF Inverter pumps |
| 1.3.6.1.4.1.9839.2.1.2.13 | Scalarpressure-Out | read-only | current | Pressure Out |
| 1.3.6.1.4.1.9839.2.1.2.14 | Scalarproportional-Band-Inverter-Pumps-PID | read-write | current | Proportional Band Inverter Pumps PID |
| 1.3.6.1.4.1.9839.2.1.2.15 | Scalarintegral-Time-Inverter-Pumps-PID | read-write | current | Integral Time Inverter Pumps PID |
| 1.3.6.1.4.1.9839.2.1.2.16 | Scalarderivative-Time-Inverter-Pumps-PID | read-write | current | Derivative Time Inverter Pumps PID |
| 1.3.6.1.4.1.9839.2.1.2.17 | Scalarhysteresis-Thermal-redundance | read-write | current | Hysteresis Thermal redundance |
| 1.3.6.1.4.1.9839.2.1.2.18 | Scalarmin-Opening-3Way-Valve-Hydraulic | read-write | current | Min. Opening 3Way Valve Hydraulic |
| 1.3.6.1.4.1.9839.2.1.2.19 | Scalarmax-Opening-3Way-Valve-Hydraulic | read-write | current | Max. Opening 3Way Valve Hydraulic |
| 1.3.6.1.4.1.9839.2.1.2.20 | Scalarproportional-Band-3Way-Valve-Hydrauli-PID | read-write | current | Proportional Band 3Way Valve Hydraulic PID |
| 1.3.6.1.4.1.9839.2.1.2.21 | Scalarsetpoint-FCM | read-write | current | Setpoint FCM |
| 1.3.6.1.4.1.9839.2.1.2.22 | Scalarhysteresis-FCM | read-write | current | Hysteresis FCM |
| 1.3.6.1.4.1.9839.2.1.2.23 | Scalarmax-Out-Speed-FCM | read-write | current | Max. Out Speed FCM |
| 1.3.6.1.4.1.9839.2.1.2.24 | Scalarmin-Out-Speed-FCM | read-write | current | Min. Out Speed FCM |
| 1.3.6.1.4.1.9839.2.1.2.25 | Scalarhysteresis-Cut-off-FCM | read-write | current | Hysteresis Cut-off FCM |
| 1.3.6.1.4.1.9839.2.1.2.26 | Scalarmax-Pressure-Alarm-FCM | read-write | current | Max. Pressure Alarm FCM |
| 1.3.6.1.4.1.9839.2.1.2.27 | Scalarhysteresis-Max-Pressure-Alarm-FCM | read-write | current | Hysteresis Max.Pressure Alarm FCM |
| 1.3.6.1.4.1.9839.2.1.2.28 | Scalarmax-Out-FCM | read-write | current | Max. Out FCM |
| 1.3.6.1.4.1.9839.2.1.2.29 | Scalarmin-Pressure-Alarm-FCM | read-write | current | Min. Pressure Alarm FCM |
| 1.3.6.1.4.1.9839.2.1.2.30 | Scalarhysteresis-Min-Pressure-Alarm-FCM | read-write | current | Hysteresis Min.Pressure Alarm FCM |
| 1.3.6.1.4.1.9839.2.1.2.31 | Scalarmin-Out-FCM | read-write | current | Min. Out FCM |
| 1.3.6.1.4.1.9839.2.1.2.32 | Scalardelta-Freecooling | read-write | current | Delta Freecooling |
| 1.3.6.1.4.1.9839.2.1.2.33 | Scalarhysteresis-Freecooling | read-write | current | Hysteresis Freecooling |
| 1.3.6.1.4.1.9839.2.1.2.34 | Scalarproportional-Band-Freecooling-PID | read-write | current | Proportional Band Freecooling PID |
| 1.3.6.1.4.1.9839.2.1.2.35 | Scalaroffset-Freecooling-PID | read-write | current | Offset Freecooling PID |
| 1.3.6.1.4.1.9839.2.1.2.36 | Scalartemperature-Overlap-Freecooling | read-write | current | Temperature Overlap Freecooling |
| 1.3.6.1.4.1.9839.2.1.2.37 | Scalarmin-out-freecooling | read-write | current | Min. out freecooling |
| 1.3.6.1.4.1.9839.2.1.2.38 | Scalarneutral-zone-K-costant | read-write | current | Neutral zone K costant |
| 1.3.6.1.4.1.9839.2.1.2.39 | Scalarneutral-zone-V-variable | read-write | current | Neutral zone V variable |
| 1.3.6.1.4.1.9839.2.1.2.40 | Scalarproportional-Band-freecooling-Valve-PID | read-write | current | Proportional Band freecooling Valve PID |
| 1.3.6.1.4.1.9839.2.1.2.41 | Scalaroffset-Freecooling-Valve-PID | read-write | current | Offset Freecooling Valve PID |
| 1.3.6.1.4.1.9839.2.1.2.42 | Scalartemperature-A-B | read-only | current | Temperature A-B |
| 1.3.6.1.4.1.9839.2.1.2.43 | Scalardelta-Thermal-Excusion-Freecoling | read-write | current | Delta Thermal Excusion Freecoling |
| 1.3.6.1.4.1.9839.2.1.2.44 | Scalarhysteresis-Thermal-Excusion-Freecoling | read-write | current | hysteresis Thermal Excusion Freecoling |
| 1.3.6.1.4.1.9839.2.1.2.45 | Scalaralarm-Setpoint-Static-Pressure-Hydraulic-circuit | read-write | current | Alarm Setpoint Static Pressure Hydraulic circuit |
| 1.3.6.1.4.1.9839.2.1.2.46 | Scalarwarnig-Setpoint-Static-Pressure-Hydraulic-circuit | read-write | current | Warnig Setpoint Static Pressure Hydraulic circuit |
| 1.3.6.1.4.1.9839.2.1.2.47 | Scalaralarm-Setpoint-Differential-Pressure-Hydraulic-circuit | read-write | current | Alarm Setpoint Differential Pressure Hydraulic circuit |
| 1.3.6.1.4.1.9839.2.1.2.48 | Scalaralarm-Setpoint-Flow-Rate-Hydraulic-circuit | read-write | current | Alarm Setpoint Flow-Rate Hydraulic circuit |
| 1.3.6.1.4.1.9839.2.1.2.50 | Scalartempertaure-Cut-off-FCM | read-write | current | Tempertaure Cut-off FCM |
| 1.3.6.1.4.1.9839.2.1.2.59 | Scalarset-effective | read-only | current | Set-effective |
| 1.3.6.1.4.1.9839.2.1.2.60 | Scalarset-fc | read-only | current | Freecooling or drycooler Set-point |
| 1.3.6.1.4.1.9839.2.1.2.61 | Scalarsetpoint-a-us | read-write | current | Set-point MAIN |
| 1.3.6.1.4.1.9839.2.1.2.62 | Scalarmax-setpoint | read-write | current | Max.setpoint |
| 1.3.6.1.4.1.9839.2.1.2.63 | Scalarmin-setpoint | read-write | current | Min.setpoint |
| 1.3.6.1.4.1.9839.2.1.2.64 | Scalardiff | read-write | current | differential |
| 1.3.6.1.4.1.9839.2.1.2.65 | Scalarmax-diff | read-write | current | Max. differential |
| 1.3.6.1.4.1.9839.2.1.2.66 | Scalarmin-diff | read-write | current | Min.Differential |
| 1.3.6.1.4.1.9839.2.1.2.67 | Scalarfcs-out | read-only | current | Fans speed controller output % |
| 1.3.6.1.4.1.9839.2.1.2.70 | Scalarwater-temp | read-only | current | Tank - Process water temperature |
| 1.3.6.1.4.1.9839.2.1.2.71 | Scalartemp-inlet | read-only | current | Water inlet temperature |
| 1.3.6.1.4.1.9839.2.1.2.72 | Scalartemp-outlet | read-only | current | Water outlet temperature |
| 1.3.6.1.4.1.9839.2.1.2.73 | Scalarflow-value | read-only | current | Flow rate value |
| 1.3.6.1.4.1.9839.2.1.2.74 | Scalaramp-value | read-only | current | Current cunsumption |
| 1.3.6.1.4.1.9839.2.1.2.75 | Scalarta-probe-temp-1 | read-only | current | Antifreeze 1 temperature monitoring |
| 1.3.6.1.4.1.9839.2.1.2.76 | Scalarta-probe-temp-2 | read-only | current | Antifreeze 2 temperature monitoring |
| 1.3.6.1.4.1.9839.2.1.2.77 | Scalarpressione1 | read-only | current | Condensation pressure circuit 1 |
| 1.3.6.1.4.1.9839.2.1.2.78 | Scalarpressione2 | read-only | current | Condensation pressure circuit 2 |
| 1.3.6.1.4.1.9839.2.1.2.79 | Scalarpump-sp-press | read-only | current | Pump discharge pressure |
| 1.3.6.1.4.1.9839.2.1.2.80 | Scalarp-wat2 | read-only | current | Pump suction or static pressure |
| 1.3.6.1.4.1.9839.2.1.2.81 | Scalartemp-amb | read-only | current | Ambient temperature |
| 1.3.6.1.4.1.9839.2.1.2.82 | Scalartemp-fc | read-only | current | Inlet - freecooling temperature |
| 1.3.6.1.4.1.9839.2.1.2.90 | Scalarpp1 | read-only | current | Pump 1 speed |
| 1.3.6.1.4.1.9839.2.1.2.91 | Scalarpp2 | read-only | current | Pump 2 speed |
| 1.3.6.1.4.1.9839.2.1.2.100 | Scalarcooling-capacity | read-only | current | Cooling Capacity |
| 1.3.6.1.4.1.9839.2.1.2.101 | Scalarfreecooling-capacity | read-only | current | FreeCooling Capacity |
| 1.3.6.1.4.1.9839.2.1.2.102 | Scalartotal-capacity | read-only | current | TotalCooling Capacity |
| 1.3.6.1.4.1.9839.2.1.3 | NodeintegerObjects | |||
| 1.3.6.1.4.1.9839.2.1.3.6 | Scalarip-Address1 | read-only | current | IP Address 1 (XXX.xxx.xxx.xxx) |
| 1.3.6.1.4.1.9839.2.1.3.7 | Scalarip-Address2 | read-only | current | IP Address 2 (xxx.XXX.xxx.xxx) |
| 1.3.6.1.4.1.9839.2.1.3.8 | Scalarip-Address3 | read-only | current | IP Address 3 (xxx.xxx.XXX.xxx) |
| 1.3.6.1.4.1.9839.2.1.3.9 | Scalarip-Address4 | read-only | current | IP Address 4 (xxx.xxx.xxx.XXX) |
| 1.3.6.1.4.1.9839.2.1.3.10 | ScalarnetMask | read-only | current | NetMask 8-16-24-32 |
| 1.3.6.1.4.1.9839.2.1.3.11 | Scalargateway1 | read-only | current | Gateway 1 (XXX.xxx.xxx.xxx) |
| 1.3.6.1.4.1.9839.2.1.3.12 | Scalargateway2 | read-only | current | Gateway 2 (xxx.XXX.xxx.xxx) |
| 1.3.6.1.4.1.9839.2.1.3.13 | Scalargateway3 | read-only | current | Gateway 3 (xxx.xxx.XXX.xxx) |
| 1.3.6.1.4.1.9839.2.1.3.14 | Scalargateway4 | read-only | current | Gateway 4 (xxx.xxx.xxx.XXX) |
| 1.3.6.1.4.1.9839.2.1.3.15 | Scalardns1-1 | read-only | current | DNS (1) 1 (XXX.xxx.xxx.xxx) |
| 1.3.6.1.4.1.9839.2.1.3.16 | Scalardns1-2 | read-only | current | DNS (1) 2 (xxx.XXX.xxx.xxx) |
| 1.3.6.1.4.1.9839.2.1.3.17 | Scalardns1-3 | read-only | current | DNS (1) 3 (xxx.xxx.XXX.xxx) |
| 1.3.6.1.4.1.9839.2.1.3.18 | Scalardns1-4 | read-only | current | DNS (1) 4 (xxx.xxx.xxx.XXX) |
| 1.3.6.1.4.1.9839.2.1.3.19 | Scalardns2-1 | read-only | current | DNS (2) 1 (XXX.xxx.xxx.xxx) |
| 1.3.6.1.4.1.9839.2.1.3.20 | Scalardns2-2 | read-only | current | DNS (2) 2 (xxx.XXX.xxx.xxx) |
| 1.3.6.1.4.1.9839.2.1.3.21 | Scalardns2-3 | read-only | current | DNS (2) 3 (xxx.xxx.XXX.xxx) |
| 1.3.6.1.4.1.9839.2.1.3.22 | Scalardns2-4 | read-only | current | DNS (2) 4 (xxx.xxx.xxx.XXX) |
| 1.3.6.1.4.1.9839.2.1.3.26 | Scalarip-Address1-Out | read-only | current | IP Address Out 1 (XXX.xxx.xxx.xxx) |
| 1.3.6.1.4.1.9839.2.1.3.27 | Scalarip-Address2-Out | read-only | current | IP Address Out 2 (xxx.XXX.xxx.xxx) |
| 1.3.6.1.4.1.9839.2.1.3.28 | Scalarip-Address3-Out | read-only | current | IP Address Out 3 (xxx.xxx.XXX.xxx) |
| 1.3.6.1.4.1.9839.2.1.3.29 | Scalarip-Address4-Out | read-only | current | IP Address Out 4 (xxx.xxx.xxx.XXX) |
| 1.3.6.1.4.1.9839.2.1.3.30 | Scalarstarting-delay-Second-Pump | read-write | current | Starting delay Second Pump |
| 1.3.6.1.4.1.9839.2.1.3.31 | Scalarstarting-delay-btw-Pump-Compressor | read-write | current | Starting delay btw Pump - Compressor |
| 1.3.6.1.4.1.9839.2.1.3.32 | Scalaroverlap-time-Pumps | read-write | current | Overlap time Pumps |
| 1.3.6.1.4.1.9839.2.1.3.33 | Scalarworking-time-Pumps | read-write | current | Working time Pumps |
| 1.3.6.1.4.1.9839.2.1.3.34 | Scalarrunning-time-Chillers | read-write | current | Running time Chillers |
| 1.3.6.1.4.1.9839.2.1.3.35 | Scalaroverlap-time-Chillers | read-write | current | Overlap time Chillers |
| 1.3.6.1.4.1.9839.2.1.3.36 | Scalarn-chillers-Max | read-write | current | N chillers Max |
| 1.3.6.1.4.1.9839.2.1.3.37 | Scalarn-chillers-ON | read-write | current | N chillers ON |
| 1.3.6.1.4.1.9839.2.1.3.38 | Scalarn-pumps-ON | read-write | current | N pumps ON |
| 1.3.6.1.4.1.9839.2.1.3.39 | Scalartime-Enable-Pumps-Chiller-Offline | read-write | current | Time Enable Pumps - Chiller Offline |
| 1.3.6.1.4.1.9839.2.1.3.40 | Scalartime-Running-Pumps-Chiller-Offline | read-write | current | Time Running Pumps - Chiller Offline |
| 1.3.6.1.4.1.9839.2.1.3.41 | Scalarintegral-Time-3Way-Valve-Hydraulic-PID | read-write | current | Integral Time 3Way Valve Hydraulic (PID) |
| 1.3.6.1.4.1.9839.2.1.3.42 | Scalarderivative-Time-3Way-Valve-Hydraulic-PID | read-write | current | Derivative Time 3Way Valve Hydraulic (PID) |
| 1.3.6.1.4.1.9839.2.1.3.43 | Scalaroutput-Address-3Way-Valve-Hydraulic | read-write | current | Output Address 3Way Valve Hydraulic |
| 1.3.6.1.4.1.9839.2.1.3.44 | Scalartime-Speed-Up-FCM | read-write | current | Time Speed-Up (FCM) |
| 1.3.6.1.4.1.9839.2.1.3.45 | Scalartime-Soft-Start-FCM | read-write | current | Time Soft-Start (FCM) |
| 1.3.6.1.4.1.9839.2.1.3.47 | Scalardelay-Freecooling | read-write | current | Delay Freecooling |
| 1.3.6.1.4.1.9839.2.1.3.48 | Scalarintegral-Time-Freeccoling-PID | read-write | current | Integral Time Freeccoling (PID) |
| 1.3.6.1.4.1.9839.2.1.3.49 | Scalarderivative-Time-Freeccoling-PID | read-write | current | Derivative Time Freeccoling (PID) |
| 1.3.6.1.4.1.9839.2.1.3.50 | Scalartime-Min-On-Freecooling-Chiller-timing | read-write | current | Time Min. On (Freecooling - Chiller timing) |
| 1.3.6.1.4.1.9839.2.1.3.51 | Scalartime-Min-Off-Freecooling-Chiller-timing | read-write | current | Time Min. Off (Freecooling - Chiller timing) |
| 1.3.6.1.4.1.9839.2.1.3.52 | Scalartime-Min-Different-Freecooling-Chiller-timing | read-write | current | Time Min. Different (Freecooling - Chiller timing) |
| 1.3.6.1.4.1.9839.2.1.3.53 | Scalartime-Min-Same-Freecooling-Chiller-timing | read-write | current | Time Min. Same (Freecooling - Chiller timing) |
| 1.3.6.1.4.1.9839.2.1.3.54 | Scalarintegral-Time-Freeccoling-Valve-PID | read-write | current | Integral Time Freeccoling Valve (PID) |
| 1.3.6.1.4.1.9839.2.1.3.55 | Scalarderivative-Time-Freeccoling-Valve-PID | read-write | current | Derivative Time Freeccoling Valve (PID) |
| 1.3.6.1.4.1.9839.2.1.3.56 | Scalaroutput-Address-Valve-Freecooling | read-write | current | Output Address Valve Freecooling |
| 1.3.6.1.4.1.9839.2.1.3.57 | Scalardelay-Freecooling-Thermal-Exclusion | read-write | current | Delay Freecoolimg Thermal Exclusion |
| 1.3.6.1.4.1.9839.2.1.3.58 | Scalarn-of-alarm-External-Dry-Cooler | read-write | current | N of alarm (External Dry-Cooler) |
| 1.3.6.1.4.1.9839.2.1.3.59 | Scalardelay-Alarm-Static-Pressure | read-write | current | Delay Alarm (Static Pressure) |
| 1.3.6.1.4.1.9839.2.1.3.60 | Scalarn-of-Alarm-Static-Pressure | read-write | current | N of Alarm (Static Pressure) |
| 1.3.6.1.4.1.9839.2.1.3.61 | Scalardelay-Warning-Static-Pressure | read-write | current | Delay Warning (Static Pressure) |
| 1.3.6.1.4.1.9839.2.1.3.62 | Scalarn-of-Warning-Static-Pressure | read-write | current | N of Warning (Static Pressure) |
| 1.3.6.1.4.1.9839.2.1.3.63 | Scalarn-of-Alarm-Differential-Pressure | read-write | current | N of Alarm (Differential Pressure) |
| 1.3.6.1.4.1.9839.2.1.3.64 | Scalarpriming-Time-Hydraulic-Pressure | read-write | current | Priming Time (Hydraulic Pressure) |
| 1.3.6.1.4.1.9839.2.1.3.65 | Scalardelay-priming-Time-Hydraulic-Pressure | read-write | current | Delay Priming Time (Hydraulic Pressure) |
| 1.3.6.1.4.1.9839.2.1.3.66 | Scalaroutput-Address-Alarm-Static-Pressure | read-write | current | Output Address Alarm (Static Pressure) |
| 1.3.6.1.4.1.9839.2.1.3.67 | Scalarn-of-Alarm-Flow-Rate | read-write | current | N of Alarm (Flow Rate) |
| 1.3.6.1.4.1.9839.2.1.3.68 | Scalarpriming-Time-Flow-Rate | read-write | current | Priming Time (Flow Rate) |
| 1.3.6.1.4.1.9839.2.1.3.69 | Scalardelay-priming-Time-Flow-Rate | read-write | current | Delay Priming Time (Flow Rate) |
| 1.3.6.1.4.1.9839.2.1.3.70 | Scalarbms-address-IDENT | read-only | current | BMS address (IDENT) |
| 1.3.6.1.4.1.9839.2.1.3.99 | Scalarchiller-name0 | read-only | current | Chiller Model - Article Number - 0 |
| 1.3.6.1.4.1.9839.2.1.3.100 | Scalarchiller-name1 | read-only | current | Chiller Model - Article Number - 1 |
| 1.3.6.1.4.1.9839.2.1.3.123 | Scalarcurrent-day | read-only | current | Current Day |
| 1.3.6.1.4.1.9839.2.1.3.124 | Scalarcurrent-month | read-only | current | Current Month |
| 1.3.6.1.4.1.9839.2.1.3.125 | Scalarcurrent-year | read-only | current | Current Year |
| 1.3.6.1.4.1.9839.2.1.3.126 | Scalarcurrent-hour | read-only | current | Current Hour |
| 1.3.6.1.4.1.9839.2.1.3.127 | Scalarcurrent-minute | read-only | current | Current Minute |
| 1.3.6.1.4.1.9839.2.1.3.150 | Scalarchiller-mode-operation | read-only | current | Chiller mode operation |
| 1.3.6.1.4.1.9839.2.1.100 | NodetrapObjects | |||
| 1.3.6.1.4.1.9839.2.1.100.1 | Notificationhigh-pressure-switch-1-alarm | current | High pressure switch 1 alarm | |
| 1.3.6.1.4.1.9839.2.1.100.2 | Notificationhigh-pressure-switch-2-alarm | current | High pressure switch 2 alarm | |
| 1.3.6.1.4.1.9839.2.1.100.3 | Notificationlow-pressure-switch-1-alarm | current | Low pressure switch 1 alarm | |
| 1.3.6.1.4.1.9839.2.1.100.4 | Notificationlow-pressure-switch-2-alarm | current | Low pressure switch 2 alarm | |
| 1.3.6.1.4.1.9839.2.1.100.6 | Notificationwater-level-alarm | current | Water level alarm | |
| 1.3.6.1.4.1.9839.2.1.100.8 | Notificationflow-switch-alarm | current | Flow switch alarm | |
| 1.3.6.1.4.1.9839.2.1.100.9 | Notificationwater-static-pressure-alarm | current | Water static pressure alarm | |
| 1.3.6.1.4.1.9839.2.1.100.10 | Notificationwater-static-pressure-warning | current | Water static pressure warning | |
| 1.3.6.1.4.1.9839.2.1.100.11 | Notificationflow-rate-alarm | current | Flow rate alarm | |
| 1.3.6.1.4.1.9839.2.1.100.12 | Notificationoverload-compressor1-circuit1-alarm | current | Overload compressor 1 circuit 1 alarm | |
| 1.3.6.1.4.1.9839.2.1.100.13 | Notificationoverload-compressor2-circuit1-alarm | current | Overload compressor 2 circuit 1 alarm | |
| 1.3.6.1.4.1.9839.2.1.100.14 | Notificationoverload-compressor3-circuit1-alarm | current | Overload compressor 3 circuit 1 alarm | |
| 1.3.6.1.4.1.9839.2.1.100.15 | Notificationoverload-compressor1-circuit2-alarm | current | Overload compressor 1 circuit 2 alarm | |
| 1.3.6.1.4.1.9839.2.1.100.16 | Notificationoverload-compressor2-circuit2-alarm | current | Overload compressor 2 circuit 2 alarm | |
| 1.3.6.1.4.1.9839.2.1.100.17 | Notificationoverload-compressor3-circuit2-alarm | current | Overload compressor 3 circuit 2 alarm | |
| 1.3.6.1.4.1.9839.2.1.100.18 | Notificationoverload-fans-circuit1 | current | Overload fans circuit 1 | |
| 1.3.6.1.4.1.9839.2.1.100.19 | Notificationoverload-fans-circuit2 | current | Overload fans circuit 2 | |
| 1.3.6.1.4.1.9839.2.1.100.20 | Notificationoverload-fan1-circuit1-alarm | current | Overload fan 1 circuit 1 alarm | |
| 1.3.6.1.4.1.9839.2.1.100.21 | Notificationoverload-fan2-circuit1-alarm | current | Overload fan 2 circuit 1 alarm | |
| 1.3.6.1.4.1.9839.2.1.100.22 | Notificationoverload-fan3-circuit1-alarm | current | Overload fan 3 circuit 1 alarm | |
| 1.3.6.1.4.1.9839.2.1.100.23 | Notificationoverload-fan4-circuit1-alarm | current | Overload fan 4 circuit 1 alarm | |
| 1.3.6.1.4.1.9839.2.1.100.24 | Notificationoverload-fan1-circuit-2-alarm | current | Overload fan 1 circuit 2 alarm | |
| 1.3.6.1.4.1.9839.2.1.100.25 | Notificationoverload-fan2-circuit2-alarm | current | Overload fan 2 circuit 2 alarm | |
| 1.3.6.1.4.1.9839.2.1.100.26 | Notificationoverload-fan3-circuit2-alarm | current | Overload fan 3 circuit 2 alarm | |
| 1.3.6.1.4.1.9839.2.1.100.27 | Notificationoverload-fan4-circuit2-alarm | current | Overload fan 4 circuit 2 alarm | |
| 1.3.6.1.4.1.9839.2.1.100.28 | Notificationoverload-pump1-alarm | current | Overload pump 1 alarm | |
| 1.3.6.1.4.1.9839.2.1.100.29 | Notificationoverload-pump2-alarm | current | Overload pump 2 alarm | |
| 1.3.6.1.4.1.9839.2.1.100.30 | Notificationwrong-phase-rotation-alarm | current | Wrong phase rotation alarm | |
| 1.3.6.1.4.1.9839.2.1.100.31 | Notificationback-Door-open-alarm | current | Back Door open alarm | |
| 1.3.6.1.4.1.9839.2.1.100.75 | Notificationalarm-idrofrigo-pump-c-1 | current | Condensation pump 1 breaker switch alarm | |
| 1.3.6.1.4.1.9839.2.1.100.76 | Notificationalarm-idrofrigo-pump-c-2 | current | Condensation pump 2 breaker switch alarm | |
| 1.3.6.1.4.1.9839.2.1.100.80 | Notificationalarm-idrofrigo-fl-C | current | Condensation flow switch alarm | |
| 1.3.6.1.4.1.9839.2.1.100.130 | Notificationremote-on-off | current | Remote on-off | |
| 1.3.6.1.4.1.9839.2.1.100.131 | Notificationchiller-ON-OFF | current | Chiller ON/OFF | |
| 1.3.6.1.4.1.9839.2.1.100.148 | Notificationalarm-disch-scw-1 | current | Discharge screw compressor 1 alarm | |
| 1.3.6.1.4.1.9839.2.1.100.149 | Notificationalarm-disch-scw-2 | current | Discharge screw compressor 2 alarm | |
| 1.3.6.1.4.1.9839.2.1.100.150 | Notificationalarm-probe-inlet | current | Inlet probe alarm (broken or disconnected) | |
| 1.3.6.1.4.1.9839.2.1.100.151 | Notificationalarm-probe-amb | current | Ambient probe alarm (broken or disconnected) | |
| 1.3.6.1.4.1.9839.2.1.100.152 | Notificationalarm-frigo-fl1 | current | Flow switch alarm (cooling alarm) | |
| 1.3.6.1.4.1.9839.2.1.100.153 | Notificationalarm-idro-pump1 | current | Pump 1 hydraulic alarm | |
| 1.3.6.1.4.1.9839.2.1.100.154 | Notificationalarm-idro-pump2 | current | Pump 2 hydraulic alarm | |
| 1.3.6.1.4.1.9839.2.1.100.155 | Notificationalarm-idro-fl1 | current | Flow switch alarm (hydraulic alarm) | |
| 1.3.6.1.4.1.9839.2.1.100.156 | Notificationalarm-warning-fl1 | current | Flow switch alarm (warning alarm) | |
| 1.3.6.1.4.1.9839.2.1.100.157 | Notificationalarm-hi-water-temp | current | High Temperature alarm | |
| 1.3.6.1.4.1.9839.2.1.100.158 | Notificationalarm-lo-water-temp | current | Low Temperature alarm | |
| 1.3.6.1.4.1.9839.2.1.100.159 | Notificationalarm-ta-probe1 | current | Antifreeze/evaporator probe 1 alarm | |
| 1.3.6.1.4.1.9839.2.1.100.160 | Notificationalarm-hi-press | current | High condensation pressure alarm | |
| 1.3.6.1.4.1.9839.2.1.100.161 | Notificationalarm-lo-press | current | Low condensation pressure alarm | |
| 1.3.6.1.4.1.9839.2.1.100.162 | Notificationalarm-probe-evap-1 | current | Antifreeze/evaporator probe 1 alarm (broken or disconnected) | |
| 1.3.6.1.4.1.9839.2.1.100.163 | Notificationalarm-probe-evap-2 | current | Antifreeze/evaporator probe 2 alarm (broken or disconnected) | |
| 1.3.6.1.4.1.9839.2.1.100.164 | Notificationalarm-hi-press-1 | current | High condensation pressure 1 alarm | |
| 1.3.6.1.4.1.9839.2.1.100.165 | Notificationalarm-hi-press-2 | current | High condensation pressure 2 alarm | |
| 1.3.6.1.4.1.9839.2.1.100.166 | Notificationalarm-lo-press-1 | current | Low condensation pressure 1 alarm | |
| 1.3.6.1.4.1.9839.2.1.100.167 | Notificationalarm-lo-press-2 | current | Low condensation pressure 2 alarm | |
| 1.3.6.1.4.1.9839.2.1.100.168 | Notificationalarm-probe-tank | current | Tank/Out probe alarm (broken or disconnected) | |
| 1.3.6.1.4.1.9839.2.1.100.169 | Notificationalarm-off-line-1 | current | Chiller 1 offline | |
| 1.3.6.1.4.1.9839.2.1.100.170 | Notificationalarm-off-line-2 | current | Chiller 2 offline | |
| 1.3.6.1.4.1.9839.2.1.100.171 | Notificationalarm-off-line-3 | current | Chiller 3 offline | |
| 1.3.6.1.4.1.9839.2.1.100.172 | Notificationalarm-off-line-4 | current | Chiller 4 offline | |
| 1.3.6.1.4.1.9839.2.1.100.173 | Notificationalarm-off-line-5 | current | Chiller 5 offline | |
| 1.3.6.1.4.1.9839.2.1.100.174 | Notificationalarm-off-line-6 | current | Chiller 6 offline | |
| 1.3.6.1.4.1.9839.2.1.100.175 | Notificationalarm-off-line-7 | current | Chiller 7 offline | |
| 1.3.6.1.4.1.9839.2.1.100.176 | Notificationalarm-off-line-8 | current | Chiller 8 offline | |
| 1.3.6.1.4.1.9839.2.1.100.177 | Notificationalarm-ta-probe2 | current | Antifreeze/evaporator probe 2 alarm | |
| 1.3.6.1.4.1.9839.2.1.100.178 | Notificationalarm-sms | current | SMS alarm | |
| 1.3.6.1.4.1.9839.2.1.100.179 | Notificationalarm-modem | current | Modem alarm | |
| 1.3.6.1.4.1.9839.2.1.100.180 | Notificationalarm-sms-coda | current | SMS coda alarm | |
| 1.3.6.1.4.1.9839.2.1.100.181 | Notificationalarm-probe-fc | current | Freecooling probe alarm (broken or disconnected) | |
| 1.3.6.1.4.1.9839.2.1.100.182 | Notificationalarm-maint-pw1 | current | Maintenance pump 1 alarm) | |
| 1.3.6.1.4.1.9839.2.1.100.183 | Notificationalarm-maint-pw2 | current | Maintenance pump 2 alarm) | |
| 1.3.6.1.4.1.9839.2.1.100.184 | Notificationalarm-hi-temp-rid | current | High temperature alarm (redundance) | |
| 1.3.6.1.4.1.9839.2.1.100.185 | Notificationalarm-q-fc-sep | current | DryCooler breaker switch alarm | |
| 1.3.6.1.4.1.9839.2.1.100.186 | Notificationalarm-p-wat2 | current | Water pressure 2 alarm | |
| 1.3.6.1.4.1.9839.2.1.100.187 | Notificationalarm-p-wat1 | current | Water pressure 1 alarm | |
| 1.3.6.1.4.1.9839.2.1.100.188 | Notificationalarm-foult-flow-p1 | current | Pump 1 flow alarm | |
| 1.3.6.1.4.1.9839.2.1.100.189 | Notificationalarm-foult-flow-p2 | current | Pump 2 flow alarm | |
| 1.3.6.1.4.1.9839.2.1.100.190 | Notificationalarm-foult-fl1-p1 | current | Pump 1 flow-switch alarm | |
| 1.3.6.1.4.1.9839.2.1.100.191 | Notificationalarm-foult-fl1-p2 | current | Pump 2 flow-switch alarm | |
| 1.3.6.1.4.1.9839.2.1.100.192 | Notificationalarm-warning-le | current | Water level warning | |
| 1.3.6.1.4.1.9839.2.1.100.193 | Notificationalarm-frigo-fl-C | current | Flow switch condensation alarm (cooling alarm) | |
| 1.3.6.1.4.1.9839.2.1.100.194 | Notificationalarm-idro-pump-c-1 | current | Pump 1 condensation hydraulic alarm | |
| 1.3.6.1.4.1.9839.2.1.100.195 | Notificationalarm-idro-pump-c-2 | current | Pump 2 condensation hydraulic alarm | |
| 1.3.6.1.4.1.9839.2.1.100.196 | Notificationalarm-idro-fl-C | current | Flow switch condensation alarm (hydraulic alarm) | |
| 1.3.6.1.4.1.9839.2.1.100.197 | Notificationalarm-warning-fl-C | current | Flow switch condensation alarm (warning alarm) | |
| 1.3.6.1.4.1.9839.2.1.100.198 | Notificationalarm-foul-fl-C-p1 | current | Pump 1 condensation flow-switch alarm | |
| 1.3.6.1.4.1.9839.2.1.100.199 | Notificationalarm-foul-fl-C-p2 | current | Pump 2 condensation flow-switch alarm |