MIB Viewer

KMX-RACK

104 objects
No module-level DESCRIPTION found.
Imported Objects
RFC-1212OBJECT-TYPE
RFC-1215TRAP-TYPE
RFC1155-SMIenterprises
RFC1213-MIBDisplayString
OIDNameAccessStatusDescription
1.3.6.1.4.1.37954Nodekentix
1.3.6.1.4.1.37954.1NodewrongLoginwrong login of a user
1.3.6.1.4.1.37954.2Nodeloginlogin of user
1.3.6.1.4.1.37954.3NodealarmSNMP Trap for each multisensor alarm
1.3.6.1.4.1.37954.3NodemultisensorRack
1.3.6.1.4.1.37954.3.1Nodedatapoints
1.3.6.1.4.1.37954.3.1.1NodetemperatureEntry
1.3.6.1.4.1.37954.3.1.1.1ScalartemperatureValueread-onlymandatoryTemperature on the Kentix KMS-RACK for that datatpoint (Factor 0.1)
1.3.6.1.4.1.37954.3.1.1.2ScalartemperatureMinread-writemandatoryTemperature Min on the Kentix KMS-RACK for that datatpoint
1.3.6.1.4.1.37954.3.1.1.3ScalartemperatureMaxread-writemandatoryTemperature Max on the Kentix KMS-RACK for that datatpoint
1.3.6.1.4.1.37954.3.1.1.4ScalartemperatureAlarmread-onlymandatoryAlarm on the Kentix KMS-RACK for that datatpoint
1.3.6.1.4.1.37954.3.1.1.5ScalartemperatureAlarmtextread-onlymandatoryAlarmmessage on the Kentix KMS-RACK for that datatpoint
1.3.6.1.4.1.37954.3.1.1.6ScalartemperatureAlarmArmread-writemandatoryArm/Disarm TemperatureAlarm on the Kentix KMS-RACK
1.3.6.1.4.1.37954.3.1.2NodehumidityEntry
1.3.6.1.4.1.37954.3.1.2.1ScalarhumidityValueread-onlymandatoryHumidity on the Kentix KMS-RACK for that datatpoint (Factor 0.1)
1.3.6.1.4.1.37954.3.1.2.2ScalarhumidityMinread-writemandatoryHumidity Min on the Kentix KMS-RACK for that datatpoint
1.3.6.1.4.1.37954.3.1.2.3ScalarhumidityMaxread-writemandatoryHumidity Max on the Kentix KMS-RACK for that datatpoint
1.3.6.1.4.1.37954.3.1.2.4ScalarhumidityAlarmread-onlymandatoryAlarm on the Kentix KMS-RACK for that datatpoint
1.3.6.1.4.1.37954.3.1.2.5ScalarhumidityAlarmtextread-onlymandatoryAlarmmessage on the Kentix KMS-RACK for that datatpoint
1.3.6.1.4.1.37954.3.1.2.6ScalarhumidityAlarmArmread-writemandatoryArm/Disarm HumidityAlarm on the Kentix KMS-RACK
1.3.6.1.4.1.37954.3.1.3NodedewpointEntry
1.3.6.1.4.1.37954.3.1.3.1ScalardewpointValueread-onlymandatoryDewpoint on the Kentix KMS-RACK for that datatpoint (Factor 0.1)
1.3.6.1.4.1.37954.3.1.3.2ScalardewpointMinread-writemandatoryDewpoint Min on the Kentix KMS-RACK for that datatpoint
1.3.6.1.4.1.37954.3.1.3.3ScalardewpointAlarmread-onlymandatoryAlarm on the Kentix KMS-RACK for that datatpoint
1.3.6.1.4.1.37954.3.1.3.4ScalardewpointAlarmtextread-onlymandatoryAlarmmessage on the Kentix KMS-RACK for that datatpoint
1.3.6.1.4.1.37954.3.1.3.6ScalardewpointAlarmArmread-writemandatoryArm/Disarm DewpointAlarm on the Kentix KMS-RACK
1.3.6.1.4.1.37954.3.1.4NodecoEntry
1.3.6.1.4.1.37954.3.1.4.1ScalarcoValueread-onlymandatoryCarbon Monoxide on the Kentix KMS-RACK for that datatpoint
1.3.6.1.4.1.37954.3.1.4.2ScalarcoMaxread-writemandatoryCarbon Monoxide Min on the Kentix KMS-RACK for that datatpoint
1.3.6.1.4.1.37954.3.1.4.3ScalarcoAlarmread-onlymandatoryAlarm on the Kentix KMS-RACK for that datatpoint
1.3.6.1.4.1.37954.3.1.4.4ScalarcoAlarmtextread-onlymandatoryAlarmmessage on the Kentix KMS-RACK for that datatpoint
1.3.6.1.4.1.37954.3.1.4.6ScalarcoAlarmArmread-writemandatoryArm/Disarm COAlarm on the Kentix KMS-RACK
1.3.6.1.4.1.37954.3.1.5NodemotionEntry
1.3.6.1.4.1.37954.3.1.5.1ScalarmotionValueread-onlymandatoryMotion on the Kentix KMS-RACK for that datatpoint
1.3.6.1.4.1.37954.3.1.5.2ScalarmotionMaxread-writemandatoryMotion Min on the Kentix KMS-RACK for that datatpoint
1.3.6.1.4.1.37954.3.1.5.3ScalarmotionAlarmread-onlymandatoryAlarm on the Kentix KMS-RACK for that datatpoint
1.3.6.1.4.1.37954.3.1.5.4ScalarmotionAlarmtextread-onlymandatoryAlarmmessage on the Kentix KMS-RACK for that datatpoint
1.3.6.1.4.1.37954.3.1.5.6ScalarmotionAlarmArmread-writemandatoryArm/Disarm MotionAlarm on the Kentix KMS-RACK
1.3.6.1.4.1.37954.3.1.6NodedigitalIn1
1.3.6.1.4.1.37954.3.1.6.1ScalardigitalIn1Valueread-onlymandatoryDigital IN 1 on the Kentix KMS-RACK for that datatpoint
1.3.6.1.4.1.37954.3.1.6.2ScalardigitalIn1Nameread-onlymandatoryDigital IN 1 on the Kentix KMS-RACK for that datatpoint
1.3.6.1.4.1.37954.3.1.7NodedigitalIn2
1.3.6.1.4.1.37954.3.1.7.1ScalardigitalIn2Valueread-onlymandatoryDigital IN 2 on the Kentix KMS-RACK for that datatpoint
1.3.6.1.4.1.37954.3.1.7.2ScalardigitalIn2Nameread-onlymandatoryDigital IN 2 on the Kentix KMS-RACK for that datatpoint
1.3.6.1.4.1.37954.3.1.8NodedigitalOut2
1.3.6.1.4.1.37954.3.1.8.1ScalardigitalOut2Valueread-writemandatoryDigital OUT 2 on the Kentix KMS-RACK for that datatpoint
1.3.6.1.4.1.37954.3.1.9NodebuzzerTime
1.3.6.1.4.1.37954.3.1.9.1ScalarbuzzerTimeValueread-writemandatoryBuzzer on the Kentix KMS-RACK for that datatpoint
1.3.6.1.4.1.37954.3.1.10NoderelayTime
1.3.6.1.4.1.37954.3.1.10.1ScalarrelayTimeValueread-writemandatoryBuzzer Time on the Kentix KMS-RACK for that datatpoint
1.3.6.1.4.1.37954.3.1.11NoderearmMotion
1.3.6.1.4.1.37954.3.1.11.1ScalarrearmMotionValueread-writemandatoryArm-Disarm Motion on the Kentix KMS-RACK for that datatpoint
1.3.6.1.4.1.37954.3.1.12Nodepdu1
1.3.6.1.4.1.37954.3.1.12.1Scalarpdu1activepowerValueread-onlymandatoryActive power value of pdu1 on the Kentix KMS-RACK (Factor 0.1)
1.3.6.1.4.1.37954.3.1.12.2Scalarpdu1apparentpowerValueread-onlymandatoryApparrnt power value of pdu1 on the Kentix KMS-RACK (Factor 0.1)
1.3.6.1.4.1.37954.3.1.12.3Scalarpdu1energyValueread-onlymandatoryEnergy value of pdu1 on the Kentix KMS-RACK (Factor 0.1)
1.3.6.1.4.1.37954.3.1.12.4Scalarpdu1energycostsValueread-onlymandatoryEnergy costs value of pdu1 on the Kentix KMS-RACK (Factor 0.1)
1.3.6.1.4.1.37954.3.1.12.5Scalarpdu1currentValueread-onlymandatoryCurrent value of pdu1 on the Kentix KMS-RACK (Factor 0.1)
1.3.6.1.4.1.37954.3.1.12.6Scalarpdu1voltageValueread-onlymandatoryVoltage value of pdu1 on the Kentix KMS-RACK (Factor 0.1)
1.3.6.1.4.1.37954.3.1.12.7Scalarpdu1powerfactorValueread-onlymandatoryPower factor of pdu1 on the Kentix KMS-RACK (Factor 0.1)
1.3.6.1.4.1.37954.3.1.12.8Scalarpdu1frequencyValueread-onlymandatoryFrequency of pdu1 on the Kentix KMS-RACK (Factor 0.1)
1.3.6.1.4.1.37954.3.1.12.9Nodepdu1VoltageFlicker
1.3.6.1.4.1.37954.3.1.12.9.1Scalarpdu1VoltageFlickerValueread-onlymandatoryFlicker (low voltage) value of pdu1 on the Kentix KMS-RACK.
1.3.6.1.4.1.37954.3.1.12.9.2Scalarpdu1VoltageFlickerTimeread-onlymandatoryLast Flicker (low voltage) time of pdu1 on the Kentix KMS-RACK.
1.3.6.1.4.1.37954.3.1.12.9.3Scalarpdu1VoltageFlickerStateread-onlymandatoryAlarmstate Flicker (low voltage) of pdu1 on the Kentix KMS-RACK.
1.3.6.1.4.1.37954.3.1.12.10Nodepdu1VoltageSwell
1.3.6.1.4.1.37954.3.1.12.10.1Scalarpdu1VoltageSwellValueread-onlymandatoryVoltage swell value of pdu1 on the Kentix KMS-RACK.
1.3.6.1.4.1.37954.3.1.12.10.2Scalarpdu1VoltageSwellTimeread-onlymandatoryLast voltage swell time of pdu1 on the Kentix KMS-RACK.
1.3.6.1.4.1.37954.3.1.12.10.3Scalarpdu1VoltageSwellStateread-onlymandatoryAlarmstate voltage swell of pdu1 on the Kentix KMS-RACK.
1.3.6.1.4.1.37954.3.1.12.11Nodepdu1VoltagePeak
1.3.6.1.4.1.37954.3.1.12.11.1Scalarpdu1VoltagePeakValueread-onlymandatoryVoltagePeakvoltage value of pdu1 on the Kentix KMS-RACK.
1.3.6.1.4.1.37954.3.1.12.11.2Scalarpdu1VoltagePeakTimeread-onlymandatoryLast peakvoltage time of pdu1 on the Kentix KMS-RACK.
1.3.6.1.4.1.37954.3.1.12.11.3Scalarpdu1VoltagePeakStateread-onlymandatoryAlarmstate peakvoltage of pdu1 on the Kentix KMS-RACK.
1.3.6.1.4.1.37954.3.1.13Nodepdu2
1.3.6.1.4.1.37954.3.1.13.1Scalarpdu2activepowerValueread-onlymandatoryActive power value of pdu2 on the Kentix KMS-RACK (Factor 0.1)
1.3.6.1.4.1.37954.3.1.13.2Scalarpdu2apparentpowerValueread-onlymandatoryApparrnt power value of pdu2 on the Kentix KMS-RACK (Factor 0.1)
1.3.6.1.4.1.37954.3.1.13.3Scalarpdu2energyValueread-onlymandatoryEnergy value of pdu2 on the Kentix KMS-RACK (Factor 0.1)
1.3.6.1.4.1.37954.3.1.13.4Scalarpdu2energycostsValueread-onlymandatoryEnergy costs value of pdu2 on the Kentix KMS-RACK (Factor 0.1)
1.3.6.1.4.1.37954.3.1.13.5Scalarpdu2currentValueread-onlymandatoryCurrent value of pdu2 on the Kentix KMS-RACK (Factor 0.1)
1.3.6.1.4.1.37954.3.1.13.6Scalarpdu2voltageValueread-onlymandatoryVoltage value of pdu2 on the Kentix KMS-RACK (Factor 0.1)
1.3.6.1.4.1.37954.3.1.13.7Scalarpdu2powerfactorValueread-onlymandatoryPower factor of pdu2 on the Kentix KMS-RACK (Factor 0.1)
1.3.6.1.4.1.37954.3.1.13.8Scalarpdu2frequencyValueread-onlymandatoryFrequency of pdu2 on the Kentix KMS-RACK (Factor 0.1)
1.3.6.1.4.1.37954.3.1.13.9Nodepdu2VoltageFlicker
1.3.6.1.4.1.37954.3.1.13.9.1Scalarpdu2VoltageFlickerValueread-onlymandatoryFlicker (low voltage) value of pdu2 on the Kentix KMS-RACK.
1.3.6.1.4.1.37954.3.1.13.9.2Scalarpdu2VoltageFlickerTimeread-onlymandatoryLast Flicker (low voltage) time of pdu2 on the Kentix KMS-RACK.
1.3.6.1.4.1.37954.3.1.13.9.3Scalarpdu2VoltageFlickerStateread-onlymandatoryAlarmstate Flicker (low voltage) of pdu2 on the Kentix KMS-RACK.
1.3.6.1.4.1.37954.3.1.13.10Nodepdu2VoltageSwell
1.3.6.1.4.1.37954.3.1.13.10.1Scalarpdu2VoltageSwellValueread-onlymandatoryVoltage swell value of pdu2 on the Kentix KMS-RACK.
1.3.6.1.4.1.37954.3.1.13.10.2Scalarpdu2VoltageSwellTimeread-onlymandatoryLast voltage swell time of pdu2 on the Kentix KMS-RACK.
1.3.6.1.4.1.37954.3.1.13.10.3Scalarpdu2VoltageSwellStateread-onlymandatoryAlarmstate voltage swell of pdu2 on the Kentix KMS-RACK.
1.3.6.1.4.1.37954.3.1.13.11Nodepdu2VoltagePeak
1.3.6.1.4.1.37954.3.1.13.11.1Scalarpdu2VoltagePeakValueread-onlymandatoryPeakvoltage value of pdu2 on the Kentix KMS-RACK.
1.3.6.1.4.1.37954.3.1.13.11.2Scalarpdu2VoltagePeakTimeread-onlymandatoryLast peakvoltage time of pdu2 on the Kentix KMS-RACK.
1.3.6.1.4.1.37954.3.1.13.11.3Scalarpdu2VoltagePeakStateread-onlymandatoryAlarmstate peakvoltage of pdu2 on the Kentix KMS-RACK.
1.3.6.1.4.1.37954.3.1.14Nodepdusum
1.3.6.1.4.1.37954.3.1.14.1ScalarpdusumactivepowerValueread-onlymandatoryActive power value of all pdus the Kentix KMS-RACK (Factor 0.1)
1.3.6.1.4.1.37954.3.1.14.2ScalarpdusumapparentpowerValueread-onlymandatoryApparrnt power value of all pdus the Kentix KMS-RACK (Factor 0.1)
1.3.6.1.4.1.37954.3.1.14.3ScalarpdusumenergyValueread-onlymandatoryEnergy value of all pdus the Kentix KMS-RACK (Factor 0.1)
1.3.6.1.4.1.37954.3.1.14.4ScalarpdusumenergycostsValueread-onlymandatoryEnergy costs value of all pdus the Kentix KMS-RACK (Factor 0.1)
1.3.6.1.4.1.37954.3.1.14.5ScalarpdusumcurrentValueread-onlymandatoryCurrent value of all pdus the Kentix KMS-RACK (Factor 0.1)
1.3.6.1.4.1.37954.3.1.14.6ScalarpdusumvoltageValueread-onlymandatoryVoltage value of all pdus the Kentix KMS-RACK (Factor 0.1)
1.3.6.1.4.1.37954.3.1.14.7ScalarpdusumpowerfactorValueread-onlymandatoryPower factor of all pdus the Kentix KMS-RACK (Factor 0.1)
1.3.6.1.4.1.37954.3.1.14.8ScalarpdusumfrequencyValueread-onlymandatoryFrequency of all pdus the Kentix KMS-RACK (Factor 0.1)
1.3.6.1.4.1.37954.3.2ScalaralarmTextread-onlymandatoryAlarm Text send to the Manager