LHX-MIB
93 objects
This MIB describes the SNMP functions of the Schroff Varistar LHX heat exchanger supported by Raritan devices.
Imported Objects
| INET-ADDRESS-MIB | InetAddress InetAddressType InetPortNumber |
| RFC1213-MIB | sysContact sysLocation sysName |
| SNMPv2-CONF | MODULE-COMPLIANCE NOTIFICATION-GROUP OBJECT-GROUP |
| SNMPv2-SMI | enterprises Integer32 MODULE-IDENTITY NOTIFICATION-TYPE OBJECT-TYPE Unsigned32 |
| SNMPv2-TC | DisplayString TEXTUAL-CONVENTION TruthValue |
| OID | Name | Access | Status | Description |
|---|---|---|---|---|
| 1.3.6.1.4.1.13742 | Identityraritan | This MIB describes the SNMP functions of the Schroff Varistar LHX heat exchanger supported by Raritan devices. | ||
| 1.3.6.1.4.1.13742.9 | Nodelhxgw | |||
| 1.3.6.1.4.1.13742.9.0 | Nodetraps | |||
| 1.3.6.1.4.1.13742.9.0.0 | NodetrapInformation | |||
| 1.3.6.1.4.1.13742.9.0.0.1 | ScalardeviceName | accessible-for-notify | current | The user-defined name for the Device. |
| 1.3.6.1.4.1.13742.9.0.0.2 | ScalardeviceInetAddressType | accessible-for-notify | current | The type of address format |
| 1.3.6.1.4.1.13742.9.0.0.3 | ScalardeviceInetIPAddress | accessible-for-notify | current | The current IP address. A value of 0.0.0.0 indicates an error or an unset option. |
| 1.3.6.1.4.1.13742.9.0.0.4 | ScalarlhxErrorCode | accessible-for-notify | current | The LHX error code (F1 - F25, EP). |
| 1.3.6.1.4.1.13742.9.0.0.5 | ScalarportId | accessible-for-notify | current | A unique value for the physical port, the LHX controlller is connected to. Its value ranges between 1 and the value of portCount. |
| 1.3.6.1.4.1.13742.9.0.0.6 | ScalarprobeId | accessible-for-notify | current | The physical Sensor ID (F1 - F7). |
| 1.3.6.1.4.1.13742.9.0.0.7 | ScalarfanId | accessible-for-notify | current | The Fan ID (M1 - M6). |
| 1.3.6.1.4.1.13742.9.0.0.8 | ScalarpowerSupplyId | accessible-for-notify | current | The Power Supply ID (1, 2). |
| 1.3.6.1.4.1.13742.9.0.0.9 | ScalaroldSensorState | accessible-for-notify | current | The old sensor state used in Sensor State Transition traps. |
| 1.3.6.1.4.1.13742.9.0.0.10 | ScalarsensorTypeId | accessible-for-notify | current | A unique value for the type of sensor. |
| 1.3.6.1.4.1.13742.9.0.0.11 | ScalarsensorId | accessible-for-notify | current | A unique value for each sensor. Its value ranges between 1 and the value of sensorCount. |
| 1.3.6.1.4.1.13742.9.0.0.12 | ScalaroldOperationalState | read-only | current | The old operational state used in Operational State Transition traps. |
| 1.3.6.1.4.1.13742.9.0.0.13 | ScalaragentInetPortNumber | accessible-for-notify | current | The UDP port number used for accessing the SNMP agent on the device. Examples: If the associated device MIB (PX2-MIB, EMD-MIB) has deviceCascadeType set to por… |
| 1.3.6.1.4.1.13742.9.0.1 | NotificationlhxSensorFailure | current | A sensor failure (broken or short circuit) occurred. | |
| 1.3.6.1.4.1.13742.9.0.2 | NotificationlhxFanFailure | current | A fan motor failure occurred. | |
| 1.3.6.1.4.1.13742.9.0.3 | NotificationlhxPowerSupplyFailure | current | A power supply failure occurred. | |
| 1.3.6.1.4.1.13742.9.0.4 | NotificationlhxThresholdAirOutlet | current | The air outlet temperature threshold was crossed. | |
| 1.3.6.1.4.1.13742.9.0.5 | NotificationlhxThresholdAirInlet | current | The air inlet temperature threshold was crossed. | |
| 1.3.6.1.4.1.13742.9.0.6 | NotificationlhxThresholdWaterInlet | current | The water inlet temperature threshold was crossed. | |
| 1.3.6.1.4.1.13742.9.0.7 | NotificationlhxDoorOpened | current | The door was opened. | |
| 1.3.6.1.4.1.13742.9.0.8 | NotificationlhxMaximumCoolingRequest | current | Maximum cooling was requested. | |
| 1.3.6.1.4.1.13742.9.0.9 | NotificationlhxEmergencyCooling | current | Emergency cooling was activated. | |
| 1.3.6.1.4.1.13742.9.0.10 | NotificationlhxWaterLeak | current | Water leakage was detected. | |
| 1.3.6.1.4.1.13742.9.0.11 | NotificationlhxThresholdHumidity | current | The humidity threshold was crossed. | |
| 1.3.6.1.4.1.13742.9.0.12 | NotificationlhxExternalWaterCoolingFailure | current | An external water cooling failure occurred. | |
| 1.3.6.1.4.1.13742.9.0.13 | NotificationlhxThresholdWaterOutlet | current | The water outlet temperature threshold was crossed. | |
| 1.3.6.1.4.1.13742.9.0.14 | NotificationlhxParameterDataLoss | current | Data loss in parameter memory was detected. | |
| 1.3.6.1.4.1.13742.9.0.15 | NotificationlhxStBusError | current | An ST-Bus communication error was detected. | |
| 1.3.6.1.4.1.13742.9.0.16 | NotificationlhxCollectiveFault | current | An error was detected. | |
| 1.3.6.1.4.1.13742.9.0.17 | NotificationgwSensorStateChange | current | Sensor State Change. | |
| 1.3.6.1.4.1.13742.9.0.18 | NotificationgwLhxOperationalStateChange | current | Operational State Change. | |
| 1.3.6.1.4.1.13742.9.0.19 | NotificationlhxVoltageLow | current | The supply voltage of an LHX became low. | |
| 1.3.6.1.4.1.13742.9.0.20 | NotificationlhxBaseElectronicsFailure | current | The base electronics of an LHX controller failed. | |
| 1.3.6.1.4.1.13742.9.0.21 | NotificationlhxCondenserPumpFailure | current | An LHX condenser pump failed. | |
| 1.3.6.1.4.1.13742.9.1 | Nodeconfiguration | |||
| 1.3.6.1.4.1.13742.9.1.1 | ScalarportCount | read-only | current | The number of lhx units supported. |
| 1.3.6.1.4.1.13742.9.1.2 | TablesensorCountTable | not-accessible | current | A list of lhx sensor count extries. |
| 1.3.6.1.4.1.13742.9.1.2.1 | RowsensorCountEntry | not-accessible | current | An entry containing the number of lhx sensors of a certain type. |
| 1.3.6.1.4.1.13742.9.1.2.1.1 | ColumnsensorCount | read-only | current | The number of sensors. |
| 1.3.6.1.4.1.13742.9.1.3 | Nodelhx | |||
| 1.3.6.1.4.1.13742.9.1.3.1 | TablelhxConfigurationTable | not-accessible | current | A list of lhx controller configuration extries. The number of entries is given by the value of portCount. |
| 1.3.6.1.4.1.13742.9.1.3.1.1 | RowlhxConfigurationEntry | not-accessible | current | An entry containing parameters for an lhx. |
| 1.3.6.1.4.1.13742.9.1.3.1.1.1 | ColumnoperationalState | read-write | current | The operational state of the lhx controller. To switch LHX power state while controller is connected, set operationalState to 1 (off) or 2 (on). Switching powe… |
| 1.3.6.1.4.1.13742.9.1.3.1.1.2 | ColumnsetpointVentilators | read-write | current | The setpoint of the ventilators. |
| 1.3.6.1.4.1.13742.9.1.3.1.1.3 | ColumnsetpointWaterValve | read-write | current | The setpoint of the water valve. |
| 1.3.6.1.4.1.13742.9.1.3.1.1.4 | ColumndefaultFanSpeed | read-write | current | The 'default' fan speed during normal operation in per mill. Default is 80% (= 800). |
| 1.3.6.1.4.1.13742.9.1.3.1.1.5 | ColumnmaximumCoolingState | read-write | current | Indicates whether maximum cooling was requested or not. To request maximum cooling, set maximumCoolingState to 1 (true). Setting maximumCoolingState to 2 (fals… |
| 1.3.6.1.4.1.13742.9.1.3.1.1.6 | ColumnalertState | read-write | current | Indicates whether LHX controler is in alert state or not. To acknowledge alert status, set alertState to 2 (false). Setting alertState to 1 (true) is undefined. |
| 1.3.6.1.4.1.13742.9.1.3.1.1.7 | Columnmodel | read-only | current | The model indentifier of an LHX controller. |
| 1.3.6.1.4.1.13742.9.1.3.1.1.8 | ColumnfwVersion | read-only | current | The firmware version of an LHX controller. |
| 1.3.6.1.4.1.13742.9.1.4 | NodegwSensors | |||
| 1.3.6.1.4.1.13742.9.1.4.1 | TablesensorConfigurationTable | not-accessible | current | A list of lhx sensor configuration extries. The number of entries is given by the value of portCount. |
| 1.3.6.1.4.1.13742.9.1.4.1.1 | RowsensorConfigurationEntry | not-accessible | current | An entry containing parameters for an lhx. |
| 1.3.6.1.4.1.13742.9.1.4.1.1.1 | ColumnportIdx | not-accessible | current | A unique value for each port. Its value ranges between 1 and the value of portCount. |
| 1.3.6.1.4.1.13742.9.1.4.1.1.2 | ColumnsensorTypeIdx | not-accessible | current | A unique value for the type of sensor. |
| 1.3.6.1.4.1.13742.9.1.4.1.1.3 | ColumnsensorIdx | not-accessible | current | A unique value for each sensor. Its value ranges between 1 and the value of sensorCount. |
| 1.3.6.1.4.1.13742.9.1.4.1.1.4 | ColumnsensorLabel | read-only | current | The short ID of the sensor (e.g. F1, M2). |
| 1.3.6.1.4.1.13742.9.1.4.1.1.5 | ColumnsensorUnit | read-only | current | The base units. This parameter does not apply to state sensors. |
| 1.3.6.1.4.1.13742.9.1.4.1.1.6 | ColumnsensorDecimalDigits | read-only | current | The number of digits displayed to the right of the decimal point. This parameter does not apply to state sensors. |
| 1.3.6.1.4.1.13742.9.1.4.1.1.7 | ColumnsensorMaximum | read-only | current | The largest possible value. The value of this OID variable should be scaled by sensorDecimalDigits. For example, if the value is 1 and sensorDecimalDigits is 2… |
| 1.3.6.1.4.1.13742.9.1.4.1.1.8 | ColumnsensorMinimum | read-only | current | The smallest possible value. The value of this OID variable should be scaled by sensorDecimalDigits. For example, if the value is 1 and sensorDecimalDigits is … |
| 1.3.6.1.4.1.13742.9.1.4.1.1.9 | ColumnsensorHysteresis | read-write | current | The hysteresis used for deassertions. The value of this OID variable should be scaled by sensorDecimalDigits. For example, if the value is 1 and sensorDecimalD… |
| 1.3.6.1.4.1.13742.9.1.4.1.1.10 | ColumnsensorLowerCriticalThreshold | read-write | current | The lower critical threshold. The value of this OID variable should be scaled by sensorDecimalDigits. For example, if the value is 1 and sensorDecimalDigits is… |
| 1.3.6.1.4.1.13742.9.1.4.1.1.11 | ColumnsensorLowerWarningThreshold | read-write | current | The lower non-critical (warning) threshold. The value of this OID variable should be scaled by sensorDecimalDigits. For example, if the value is 1 and sensorDe… |
| 1.3.6.1.4.1.13742.9.1.4.1.1.12 | ColumnsensorUpperCriticalThreshold | read-write | current | The upper critical threshold. The value of this OID variable should be scaled by sensorDecimalDigits. For example, if the value is 1 and sensorDecimalDigits is… |
| 1.3.6.1.4.1.13742.9.1.4.1.1.13 | ColumnsensorUpperWarningThreshold | read-write | current | The upper non-critical (warning) threshold. The value of this OID variable should be scaled by sensorDecimalDigits. For example, if the value is 1 and sensorDe… |
| 1.3.6.1.4.1.13742.9.1.4.1.1.14 | ColumnsensorEnabledThresholds | read-write | current | A bit string which indicates which thresholds are enabled. This parameter does not apply to state sensors. |
| 1.3.6.1.4.1.13742.9.1.4.1.1.15 | ColumnsensorThresholdMaximum | read-only | current | The largest possible threshold value. The value of this OID variable should be scaled by sensorDecimalDigits. For example, if the value is 1 and sensorDecimalD… |
| 1.3.6.1.4.1.13742.9.1.4.1.1.16 | ColumnsensorThresholdMinimum | read-only | current | The smallest possible threshold value. The value of this OID variable should be scaled by sensorDecimalDigits. For example, if the value is 1 and sensorDecimal… |
| 1.3.6.1.4.1.13742.9.1.4.1.1.17 | ColumnsensorName | read-only | current | The descriptive ID of the sensor (e.g. Fan Speed 1). |
| 1.3.6.1.4.1.13742.9.2 | Nodemeasurements | |||
| 1.3.6.1.4.1.13742.9.2.1 | TablesensorMeasurementsTable | not-accessible | current | A list of external sensor entries. The number of entries is given by the value of sensorCount for the LHX. |
| 1.3.6.1.4.1.13742.9.2.1.1 | RowsensorMeasurementsEntry | not-accessible | current | An entry containing measurement objects for an external sensor. |
| 1.3.6.1.4.1.13742.9.2.1.1.1 | ColumnmeasurementsSensorIsAvailable | read-only | current | Is the sensor available? |
| 1.3.6.1.4.1.13742.9.2.1.1.2 | ColumnmeasurementsSensorState | read-only | current | The sensor state. |
| 1.3.6.1.4.1.13742.9.2.1.1.3 | ColumnmeasurementsSensorValue | read-only | current | The sensor reading. This parameter does not apply to state sensors. |
| 1.3.6.1.4.1.13742.9.2.1.1.4 | ColumnmeasurementsSensorTimeStamp | read-only | current | The sensor reading timestamp. |
| 1.3.6.1.4.1.13742.9.3 | Nodeconformance | |||
| 1.3.6.1.4.1.13742.9.3.1 | Nodecompliances | |||
| 1.3.6.1.4.1.13742.9.3.1.1 | CompliancecomplianceRev1 | current | The requirements for conformance to the LHX-MIB. | |
| 1.3.6.1.4.1.13742.9.3.2 | Nodegroups | |||
| 1.3.6.1.4.1.13742.9.3.2.1 | GroupconfigurationGroup | current | A collection of objects representing configuration data. | |
| 1.3.6.1.4.1.13742.9.3.2.2 | GroupmeasurementsGroup | current | A collection of objects providing the measurement capability of LHX. | |
| 1.3.6.1.4.1.13742.9.3.2.3 | GrouptrapInformationGroup | current | A collection of objects providing information in the traps. | |
| 1.3.6.1.4.1.13742.9.3.2.4 | GrouptrapsGroup | current | A collection of traps. |
Type Definitions
| Name | Syntax | Status | Description |
|---|---|---|---|
| GwSensorTypeEnumeration | INTEGER { airTemperature(0), waterTemperature(1), fanSpeed(2), doorContact(3), valvePosition(4) } | current | The types an lhx sensor can be. |
| OperationalStateEnumeration | INTEGER { disconnected(0), offline(1), online(2) } | current | The operational states of an lhx controller. |
| SensorStateEnumeration | INTEGER { unavailable(-1), open(0), closed(1), belowLowerCritical(2), belowLowerWarning(3), normal(4), aboveUpperWarning(5), aboveUpperCritical(6), on(7), off(8), detected(9), notDetected(10), alarmed(11) } | current | The states a sensor can be in. |
| SensorUnitsEnumeration | INTEGER { none(-1), other(0), volt(1), amp(2), watt(3), voltamp(4), wattHour(5), voltampHour(6), degreeC(7), hertz(8), percent(9), meterpersec(10), pascal(11), psi(12), g(13), degreeF(14), feet(15), inches(16), cm(17), meters(18), rpm(19) } | current | The units an lhx sensor can be. |