MIB Viewer

LIEBERT-GP-CONDITIONS-MIB

650 objects
The MIB module used to register Liebert SNMP OIDs. Copyright 2000-2008,2013 Liebert Corporation. All rights reserved. Reproduction of this document is authorized on the condition that the forgoing copyright notice is included. This Specification is supplied 'AS IS' and Liebert Corporation makes no warranty, either express or implied, as to the use, operation, condition, or performance of the Specification.
OIDNameAccessStatusDescription
1.3.6.1.4.1.476.1.42.1.3.1IdentityliebertGlobalProductsConditionsModuleThe MIB module used to register Liebert SNMP OIDs. Copyright 2000-2008,2013 Liebert Corporation. All rights reserved. Reproduction of this document is authoriz…
1.3.6.1.4.1.476.1.42.3.2.1NodelgpConditionsWellKnown
1.3.6.1.4.1.476.1.42.3.2.1.1IdentitylgpConditionHighTemperaturecurrentThe temperature has exceeded the high temperature threshold.
1.3.6.1.4.1.476.1.42.3.2.1.2IdentitylgpConditionLowTemperaturecurrentThe temperature is below the low temperature threshold.
1.3.6.1.4.1.476.1.42.3.2.1.3IdentitylgpConditionHighHumiditycurrentThe humidity has exceeded the high humidity threshold.
1.3.6.1.4.1.476.1.42.3.2.1.4IdentitylgpConditionLowHumiditycurrentThe humidity is below the low humidity threshold.
1.3.6.1.4.1.476.1.42.3.2.1.5IdentitylgpConditionLossOfAirflowcurrentThe system has detected a loss of air flow.
1.3.6.1.4.1.476.1.42.3.2.1.5.1IdentitylgpConditionLossOfAirflow1currentThe system has detected a loss of air flow at sensor 1.
1.3.6.1.4.1.476.1.42.3.2.1.5.2IdentitylgpConditionLossOfAirflow2currentThe system has detected a loss of air flow at sensor 2.
1.3.6.1.4.1.476.1.42.3.2.1.5.3IdentitylgpConditionLossOfAirflowBlower1currentThe system has detected a loss of air flow from blower 1.
1.3.6.1.4.1.476.1.42.3.2.1.5.4IdentitylgpConditionLossOfAirflowAllBlowerscurrentNo air flow through the unit due to failure of all blowers.
1.3.6.1.4.1.476.1.42.3.2.1.6IdentitylgpConditionChangeFiltercurrentThe system has detected a condition indicating the air filter should be changed.
1.3.6.1.4.1.476.1.42.3.2.1.7IdentitylgpConditionCompressorHighHeadPressurecurrentThis system has detected an excessive head pressure condition.
1.3.6.1.4.1.476.1.42.3.2.1.7.1IdentitylgpConditionCompressor1HighHeadPressurecurrentThe system has detected excessive head pressure in compressor 1.
1.3.6.1.4.1.476.1.42.3.2.1.7.1.1IdentitylgpConditionCompressor1AHighHeadPressurecurrentThe system has detected excessive head pressure in compressor 1A.
1.3.6.1.4.1.476.1.42.3.2.1.7.1.2IdentitylgpConditionCompressor1BHighHeadPressurecurrentThe system has detected excessive head pressure in compressor 1B.
1.3.6.1.4.1.476.1.42.3.2.1.7.2IdentitylgpConditionCompressor2HighHeadPressurecurrentThe system has detected excessive head pressure in compressor 2.
1.3.6.1.4.1.476.1.42.3.2.1.7.2.1IdentitylgpConditionCompressor2AHighHeadPressurecurrentThe system has detected excessive head pressure in compressor 2A.
1.3.6.1.4.1.476.1.42.3.2.1.7.2.2IdentitylgpConditionCompressor2BHighHeadPressurecurrentThe system has detected excessive head pressure in compressor 2B.
1.3.6.1.4.1.476.1.42.3.2.1.7.3IdentitylgpConditionCompressor3HighHeadPressurecurrentThe system has detected excessive head pressure in compressor 3.
1.3.6.1.4.1.476.1.42.3.2.1.7.4IdentitylgpConditionCompressor4HighHeadPressurecurrentThe system has detected excessive head pressure in compressor 4.
1.3.6.1.4.1.476.1.42.3.2.1.8IdentitylgpConditionCompressorOverloadcurrentThis system has detected a compressor overload condition.
1.3.6.1.4.1.476.1.42.3.2.1.8.1IdentitylgpConditionCompressor1OverloadcurrentThe system has detected an overload condition on compressor 1.
1.3.6.1.4.1.476.1.42.3.2.1.8.2IdentitylgpConditionCompressor2OverloadcurrentThe system has detected an overload condition on compressor 2.
1.3.6.1.4.1.476.1.42.3.2.1.8.3IdentitylgpConditionCompressor3OverloadcurrentThe system has detected an overload condition on compressor 3.
1.3.6.1.4.1.476.1.42.3.2.1.8.4IdentitylgpConditionCompressor4OverloadcurrentThe system has detected an overload condition on compressor 4.
1.3.6.1.4.1.476.1.42.3.2.1.9IdentitylgpConditionCompressorShortCyclecurrentA compressor has exceeded the maximum number of starts in a minimum time period.
1.3.6.1.4.1.476.1.42.3.2.1.9.1IdentitylgpConditionCompressor1ShortCyclecurrentThe system has detected a short cycle event on compressor 1. The compressor has exceeded the maximum number of starts for specified amount of time.
1.3.6.1.4.1.476.1.42.3.2.1.9.1.1IdentitylgpConditionCompressor1AShortCyclecurrentThe system has detected a short cycle event on compressor 1A. The compressor has exceeded the maximum number of starts for specified amount of time.
1.3.6.1.4.1.476.1.42.3.2.1.9.1.2IdentitylgpConditionCompressor1BShortCyclecurrentThe system has detected a short cycle event on compressor 1B. The compressor has exceeded the maximum number of starts for specified amount of time.
1.3.6.1.4.1.476.1.42.3.2.1.9.2IdentitylgpConditionCompressor2ShortCyclecurrentThe system has detected a short cycle event on compressor 2. The compressor has exceeded the maximum number of starts for specified amount of time.
1.3.6.1.4.1.476.1.42.3.2.1.9.2.1IdentitylgpConditionCompressor2AShortCyclecurrentThe system has detected a short cycle event on compressor 2A. The compressor has exceeded the maximum number of starts for specified amount of time.
1.3.6.1.4.1.476.1.42.3.2.1.9.2.2IdentitylgpConditionCompressor2BShortCyclecurrentThe system has detected a short cycle event on compressor 2B. The compressor has exceeded the maximum number of starts for specified amount of time.
1.3.6.1.4.1.476.1.42.3.2.1.9.3IdentitylgpConditionCompressor3ShortCyclecurrentThe system has detected a short cycle event on compressor 3. The compressor has exceeded the maximum number of starts for specified amount of time.
1.3.6.1.4.1.476.1.42.3.2.1.9.4IdentitylgpConditionCompressor4ShortCyclecurrentThe system has detected a short cycle event on compressor 4. The compressor has exceeded the maximum number of starts for specified amount of time.
1.3.6.1.4.1.476.1.42.3.2.1.10IdentitylgpConditionCompressorLowSuctionPressurecurrentThe pressure at a compressor inlet has dropped below the minimum setting.
1.3.6.1.4.1.476.1.42.3.2.1.10.1IdentitylgpConditionCompressor1LowSuctionPressurecurrentThe pressure at compressor 1 inlet has dropped below the minimum setting.
1.3.6.1.4.1.476.1.42.3.2.1.10.2IdentitylgpConditionCompressor2LowSuctionPressurecurrentThe pressure at compressor 2 inlet has dropped below the minimum setting.
1.3.6.1.4.1.476.1.42.3.2.1.10.3IdentitylgpConditionCompressor3LowSuctionPressurecurrentThe pressure at compressor 3 inlet has dropped below the minimum setting.
1.3.6.1.4.1.476.1.42.3.2.1.10.4IdentitylgpConditionCompressor4LowSuctionPressurecurrentThe pressure at compressor 4 inlet has dropped below the minimum setting.
1.3.6.1.4.1.476.1.42.3.2.1.11IdentitylgpConditionMainFanOverLoadcurrentThe system has detected a main fan overload condition.
1.3.6.1.4.1.476.1.42.3.2.1.12IdentitylgpConditionManualOverridecurrentThe system has detected a manual override condition.
1.3.6.1.4.1.476.1.42.3.2.1.13IdentitylgpConditionStandbyGlycoolPumpOncurrentThe standby Glycol or Glycool pump is activated.
1.3.6.1.4.1.476.1.42.3.2.1.14IdentitylgpConditionWaterUnderFloorcurrentMoisture has been detected under the floor.
1.3.6.1.4.1.476.1.42.3.2.1.15IdentitylgpConditionHumidifierProblemcurrentThe system has detected a humidifier problem.
1.3.6.1.4.1.476.1.42.3.2.1.16IdentitylgpConditionLowWaterInHumidifiercurrentThe system has detected a low water condition in the humidifier reservoir.
1.3.6.1.4.1.476.1.42.3.2.1.17IdentitylgpConditionSmokeDetectedcurrentThe system has detected smoke.
1.3.6.1.4.1.476.1.42.3.2.1.18IdentitylgpConditionLowWaterFlowcurrentThe system has detected a low water flow rate condition.
1.3.6.1.4.1.476.1.42.3.2.1.19IdentitylgpConditionLostPowercurrentThe system has lost power before being switched off using the controls. This condition is activated when power is restored.
1.3.6.1.4.1.476.1.42.3.2.1.20IdentitylgpGeneralFaultcurrentA fault condition has been detected that is not identified in the well known list.
1.3.6.1.4.1.476.1.42.3.2.1.21IdentitylgpConditionLocalAlarmcurrentThis system has detected a local, or customer, alarm condition.
1.3.6.1.4.1.476.1.42.3.2.1.21.1IdentitylgpConditionLocalAlarm1currentThe system has detected that customer alarm condition 1 is active.
1.3.6.1.4.1.476.1.42.3.2.1.21.2IdentitylgpConditionLocalAlarm2currentThe system has detected that customer alarm condition 2 is active.
1.3.6.1.4.1.476.1.42.3.2.1.21.3IdentitylgpConditionLocalAlarm3currentThe system has detected that customer alarm condition 3 is active.
1.3.6.1.4.1.476.1.42.3.2.1.21.4IdentitylgpConditionLocalAlarm4currentThe system has detected that customer alarm condition 4 is active.
1.3.6.1.4.1.476.1.42.3.2.1.21.5IdentitylgpConditionLocalAlarm5currentThe system has detected that customer alarm condition 5 is active.
1.3.6.1.4.1.476.1.42.3.2.1.21.6IdentitylgpConditionLocalAlarm6currentThe system has detected that customer alarm condition 6 is active.
1.3.6.1.4.1.476.1.42.3.2.1.21.7IdentitylgpConditionLocalAlarm7currentThe system has detected that customer alarm condition 7 is active.
1.3.6.1.4.1.476.1.42.3.2.1.21.8IdentitylgpConditionLocalAlarm8currentThe system has detected that customer alarm condition 8 is active.
1.3.6.1.4.1.476.1.42.3.2.1.22IdentitylgpConditionStandbyUnitOncurrentThe system has detected the standby unit is operating.
1.3.6.1.4.1.476.1.42.3.2.1.23IdentitylgpConditionCompressorLowPressurecurrentThis system has detected a low head compressor condition.
1.3.6.1.4.1.476.1.42.3.2.1.23.1IdentitylgpConditionCompressor1LowPressurecurrentThe system has detected low pressure in compressor 1.
1.3.6.1.4.1.476.1.42.3.2.1.23.1.1IdentitylgpConditionTandemCompressorCircuit1LowPressurecurrentThe system has detected low pressure in tandem compressor circuit 1.
1.3.6.1.4.1.476.1.42.3.2.1.23.2IdentitylgpConditionCompressor2LowPressurecurrentThe system has detected low pressure in compressor 2.
1.3.6.1.4.1.476.1.42.3.2.1.23.2.1IdentitylgpConditionTandemCompressorCircuit2LowPressurecurrentThe system has detected low pressure in tandem compressor circuit 2.
1.3.6.1.4.1.476.1.42.3.2.1.23.3IdentitylgpConditionCompressor3LowPressurecurrentThe system has detected low pressure in compressor 3.
1.3.6.1.4.1.476.1.42.3.2.1.23.4IdentitylgpConditionCompressor4LowPressurecurrentThe system has detected low pressure in compressor 4.
1.3.6.1.4.1.476.1.42.3.2.1.24IdentitylgpConditionHighWaterInPancurrentThe system has detected a high water condition in the condenser pan.
1.3.6.1.4.1.476.1.42.3.2.1.25IdentitylgpConditionFaultySensorcurrentThe system has detected a faulty temperature/humidity sensor.
1.3.6.1.4.1.476.1.42.3.2.1.26IdentitylgpConditionServiceCoolingcurrentThe Cooling system requires scheduled maintenance.
1.3.6.1.4.1.476.1.42.3.2.1.27IdentitylgpConditionServiceHumidifiercurrentThe Humidifier requires scheduled maintenance.
1.3.6.1.4.1.476.1.42.3.2.1.28IdentitylgpConditionSystemControlBatteryLowcurrentCharge level of the system control's battery is below the alarm set point.
1.3.6.1.4.1.476.1.42.3.2.1.29IdentitylgpConditionGroundSystemFaultcurrentThe system has detected a ground system fault.
1.3.6.1.4.1.476.1.42.3.2.1.30IdentitylgpConditionGroundFailurecurrentThe system has detected a ground failure.
1.3.6.1.4.1.476.1.42.3.2.1.31IdentitylgpConditionSecurityBreachcurrentThe system has detected a security breach.
1.3.6.1.4.1.476.1.42.3.2.1.32IdentitylgpConditionEmergencyShutdowncurrentThe system has detected an emergency shutdown condition. The System is shutting down as a result of this emergency.
1.3.6.1.4.1.476.1.42.3.2.1.33IdentitylgpConditionOnBypasscurrentThis system has detected the load is being powered by a bypass source.
1.3.6.1.4.1.476.1.42.3.2.1.33.1IdentitylgpConditionLoadOnBypassobsoleteThe load is being powered by a bypass source.
1.3.6.1.4.1.476.1.42.3.2.1.33.2IdentitylgpConditionLoadOnMaintenceBypasscurrentThe load is being powered by a maintenance bypass source.
1.3.6.1.4.1.476.1.42.3.2.1.33.3IdentitylgpConditionParallelSysLoadOnBypasscurrentThe parallel system has transferred to bypass.
1.3.6.1.4.1.476.1.42.3.2.1.33.4IdentitylgpConditionLoadOnBypassByImpactcurrentThe system has detected a load impact and has transferred the load to the bypass source.
1.3.6.1.4.1.476.1.42.3.2.1.33.5IdentitylgpConditionLoadTransferedToBypasscurrentThe system has transferred to bypass. The load is being powered by the bypass source.
1.3.6.1.4.1.476.1.42.3.2.1.33.6IdentitylgpConditionEmergencyTransferToBypasscurrentThe system has performed an emergency transfer to bypass.
1.3.6.1.4.1.476.1.42.3.2.1.34IdentitylgpConditionOutputToLoadVoltTHDcurrentThe total harmonic distortion (THD) of the output voltage has exceeded a pre-determined threshold for a device, or system, defined amount of time.
1.3.6.1.4.1.476.1.42.3.2.1.35IdentitylgpConditionLogicFailurecurrentThe system has detected a control logic failure.
1.3.6.1.4.1.476.1.42.3.2.1.36IdentitylgpConditionPowerSupplyFaultcurrentThis system had detected a power supply fault condition.
1.3.6.1.4.1.476.1.42.3.2.1.36.1IdentitylgpConditionPowerSupply1FaultcurrentThe system has detected power supply 1 is in a fault condition.
1.3.6.1.4.1.476.1.42.3.2.1.36.2IdentitylgpConditionPowerSupply2FaultcurrentThe system has detected power supply 2 is in a fault condition.
1.3.6.1.4.1.476.1.42.3.2.1.37IdentitylgpConditionPowerSupplyFailurecurrentThis system has detected a power supply failure condition.
1.3.6.1.4.1.476.1.42.3.2.1.37.1IdentitylgpConditionPowerSupply1FailurecurrentThe system has detected power supply 1 has failed.
1.3.6.1.4.1.476.1.42.3.2.1.37.2IdentitylgpConditionPowerSupply2FailurecurrentThe system has detected power supply 2 has failed.
1.3.6.1.4.1.476.1.42.3.2.1.37.3IdentitylgpConditionSource1PowerSupplyInputFailurecurrentThe system has detected the source 1 Power supply input has failed.
1.3.6.1.4.1.476.1.42.3.2.1.37.4IdentitylgpConditionSource2PowerSupplyInputFailurecurrentThe system has detected the source 2 Power supply input has failed.
1.3.6.1.4.1.476.1.42.3.2.1.37.5IdentitylgpConditionPowerSupplyLogicFailurecurrentThe system has detected a power supply logic failure.
1.3.6.1.4.1.476.1.42.3.2.1.37.6IdentitylgpConditionCompressorPowerSupplyFailurecurrentThe system has detected the power supply to the compressors has failed.
1.3.6.1.4.1.476.1.42.3.2.1.38IdentitylgpConditionOverVoltagecurrentThis system has detected an over voltage condition.
1.3.6.1.4.1.476.1.42.3.2.1.38.1IdentitylgpConditionSource1OverVoltagecurrentThe system has detected an over voltage condition on source 1. The voltage measurement has risen above a pre-determined threshold for a device, or system, defi…
1.3.6.1.4.1.476.1.42.3.2.1.38.2IdentitylgpConditionSource2OverVoltagecurrentThe system has detected an over voltage condition on source 2. The voltage measurement has risen above a pre-determined threshold for a device, or system, defi…
1.3.6.1.4.1.476.1.42.3.2.1.38.3IdentitylgpConditionOutputToLoadOverVoltagecurrentThe system has detected the output to load is in an over-voltage condition. The voltage for the load has risen above a pre-determined threshold for a device, o…
1.3.6.1.4.1.476.1.42.3.2.1.38.4IdentitylgpConditionInputOverVoltagecurrentThe system has detected an input over voltage condition. The voltage measurement has risen above a pre-determined threshold for a specified amount of time.
1.3.6.1.4.1.476.1.42.3.2.1.38.5IdentitylgpConditionBypassOverVoltagecurrentThe system has detected an over voltage condition on the bypass. The voltage measurement has risen above a pre-determined threshold for a device, or system, de…
1.3.6.1.4.1.476.1.42.3.2.1.38.6IdentitylgpConditionBypassOverVoltageFailurecurrentThe system has detected an over voltage failure condition on the bypass. The voltage measurement has risen above a pre-determined threshold for a device, or sy…
1.3.6.1.4.1.476.1.42.3.2.1.38.7IdentitylgpConditionBatteryOverVoltagecurrentThe system has detected a battery over voltage condition.
1.3.6.1.4.1.476.1.42.3.2.1.38.8IdentitylgpConditionDcBusOverVoltagecurrentThis system has detected a DC Bus over voltage condition.
1.3.6.1.4.1.476.1.42.3.2.1.38.8.1IdentitylgpConditionDcBus1OverVoltagecurrentThe system has detected an over voltage condition on DC Bus 1.
1.3.6.1.4.1.476.1.42.3.2.1.38.8.2IdentitylgpConditionDcBus2OverVoltagecurrentThe system has detected an over voltage condition on DC Bus 2.
1.3.6.1.4.1.476.1.42.3.2.1.38.8.3IdentitylgpConditionDcBus1OverVoltageFailurecurrentThe system has detected an over voltage failure condition on DC Bus 1.
1.3.6.1.4.1.476.1.42.3.2.1.38.8.4IdentitylgpConditionDcBus2OverVoltageFailurecurrentThe system has detected an over voltage failure condition on DC Bus 2.
1.3.6.1.4.1.476.1.42.3.2.1.39IdentitylgpConditionUnderVoltagecurrentThis system has detected an under voltage condition.
1.3.6.1.4.1.476.1.42.3.2.1.39.1IdentitylgpConditionSource1UnderVoltagecurrentThe system has detected an under voltage condition on source 1. The voltage measurement has fallen below a pre-determined threshold for a device, or system, de…
1.3.6.1.4.1.476.1.42.3.2.1.39.2IdentitylgpConditionSource2UnderVoltagecurrentThe system has detected an under voltage condition on source 2. The voltage measurement has fallen below a pre-determined threshold for a device, or system, de…
1.3.6.1.4.1.476.1.42.3.2.1.39.3IdentitylgpConditionOutputToLoadUnderVoltagecurrentThe system has detected the output to load is in an under-voltage condition. The voltage for the load has fallen below a pre-determined threshold for a device,…
1.3.6.1.4.1.476.1.42.3.2.1.39.4IdentitylgpConditionSource1UnderVoltageRMScurrentThe system has detected an under voltage condition on source 1. The voltage measurement has fallen below a pre-determined threshold for a specified amount of t…
1.3.6.1.4.1.476.1.42.3.2.1.39.5IdentitylgpConditionSource2UnderVoltageRMScurrentThe system has detected an under voltage condition on source 2. The voltage measurement has fallen below a pre-determined threshold for a specified amount of t…
1.3.6.1.4.1.476.1.42.3.2.1.39.6IdentitylgpConditionInputUnderVoltagecurrentThe system has detected an input under voltage condition. The voltage measurement has fallen below a pre-determined threshold for a device, or system, defined …
1.3.6.1.4.1.476.1.42.3.2.1.39.7IdentitylgpConditionBypassUnderVoltagecurrentThe system has detected an under voltage condition on the bypass. The voltage measurement has fallen below a pre-determined threshold for a device, or system, …
1.3.6.1.4.1.476.1.42.3.2.1.39.8IdentitylgpConditionBypassUnderVoltageFailurecurrentThe system has detected an under voltage failure condition on the bypass. The voltage measurement has fallen below a pre-determined threshold for a device, or …
1.3.6.1.4.1.476.1.42.3.2.1.39.9IdentitylgpConditionBatteryUnderVoltagecurrentThe system has detected a battery under voltage condition.
1.3.6.1.4.1.476.1.42.3.2.1.39.10IdentitylgpConditionDcBusUnderVoltagecurrentThis system has detected a DC bus under voltage condition
1.3.6.1.4.1.476.1.42.3.2.1.39.10.1IdentitylgpConditionDcBus1UnderVoltagecurrentThe system has detected an under voltage condition on DC Bus 1.
1.3.6.1.4.1.476.1.42.3.2.1.39.10.2IdentitylgpConditionDcBus2UnderVoltagecurrentThe system has detected an under voltage condition on DC Bus 2.
1.3.6.1.4.1.476.1.42.3.2.1.39.10.3IdentitylgpConditionDcBus1UnderVoltageFailurecurrentThe system has detected an under voltage failure condition on DC Bus 1.
1.3.6.1.4.1.476.1.42.3.2.1.39.10.4IdentitylgpConditionDcBus2UnderVoltageFailurecurrentThe system has detected an under voltage failure condition on DC Bus 2.
1.3.6.1.4.1.476.1.42.3.2.1.40IdentitylgpConditionOverloadcurrentThis system has detected an overload condition.
1.3.6.1.4.1.476.1.42.3.2.1.40.1IdentitylgpConditionSource1OverloadcurrentThe system has detected an overload condition on source 1. The power requirement for this source has risen above a pre-determined threshold for a device, or sy…
1.3.6.1.4.1.476.1.42.3.2.1.40.2IdentitylgpConditionSystemOverloadcurrentThe system has detected an overload condition.
1.3.6.1.4.1.476.1.42.3.2.1.40.3IdentitylgpConditionSource1PeakCurrentOverLoadcurrentThe system has detected source 1 in is experiencing a peak over load condition. The current has risen above a pre-determined threshold for a specified amount o…
1.3.6.1.4.1.476.1.42.3.2.1.40.4IdentitylgpConditionSource2PeakCurrentOverLoadcurrentThe system has detected source 2 in is experiencing a peak over load condition. The current has risen above a pre-determined threshold for a specified amount o…
1.3.6.1.4.1.476.1.42.3.2.1.40.5IdentitylgpConditionOutputToLoadOverLimitcurrentThe system had detected that the output to the load has exceeded the lgpPwrOutputToLoadUserOverloadLimit.
1.3.6.1.4.1.476.1.42.3.2.1.40.6IdentitylgpConditionOutputToLoadOverloadcurrentThe system has detected an output overload condition.
1.3.6.1.4.1.476.1.42.3.2.1.40.7IdentitylgpConditionParallelSysOverloadcurrentThe parallel system has detected an overload condition.
1.3.6.1.4.1.476.1.42.3.2.1.40.8IdentitylgpConditionBypassCurrentOverloadcurrentWith the load on bypass static switch, the measured output RMS current has exceeded a specified percentage of the nominal RMS current.
1.3.6.1.4.1.476.1.42.3.2.1.40.8.1IdentitylgpConditionBypassCurrentOverloadPhsAcurrentWith the load on bypass static switch, the measured phase A output RMS current has exceeded a specified percentage of the nominal per-phase RMS current.
1.3.6.1.4.1.476.1.42.3.2.1.40.8.2IdentitylgpConditionBypassCurrentOverloadPhsBcurrentWith the load on bypass static switch, the measured phase B output RMS current has exceeded a specified percentage of the nominal per-phase RMS current.
1.3.6.1.4.1.476.1.42.3.2.1.40.8.3IdentitylgpConditionBypassCurrentOverloadPhsCcurrentWith the load on bypass static switch, the measured phase C output RMS current has exceeded a specified percentage of the nominal per-phase RMS current.
1.3.6.1.4.1.476.1.42.3.2.1.41IdentitylgpConditionScrShortcurrentThis system has detected a Silicon Controlled Rectifier (SCR) short condition.
1.3.6.1.4.1.476.1.42.3.2.1.41.1IdentitylgpConditionSource1ScrShortcurrentThe system has detected a source 1 Silicon Controlled Rectifier (SCR) short condition.
1.3.6.1.4.1.476.1.42.3.2.1.41.2IdentitylgpConditionSource2ScrShortcurrentThe system has detected a source 2 Silicon Controlled Rectifier (SCR) short condition.
1.3.6.1.4.1.476.1.42.3.2.1.41.3IdentitylgpConditionBypassScrShortcurrentThe system has detected a Silicon Controlled Rectifier (SCR) short condition on the bypass.
1.3.6.1.4.1.476.1.42.3.2.1.41.4IdentitylgpConditionInvStaticSwScrShortcurrentThe system has detected a short across one or more inverter static switch Silicon Controlled Rectifiers (SCRs).
1.3.6.1.4.1.476.1.42.3.2.1.41.5IdentitylgpConditionSource1NeutralScrShortcurrentThe system has detected a source 1 Silicon Controlled Rectifier (SCR) short condition on the neutral line.
1.3.6.1.4.1.476.1.42.3.2.1.41.6IdentitylgpConditionSource2NeutralScrShortcurrentThe system has detected a source 2 Silicon Controlled Rectifier (SCR) short condition on the neutral line.
1.3.6.1.4.1.476.1.42.3.2.1.42IdentitylgpConditionScrOpencurrentThis system has detected a Silicon Controlled Rectifier (SCR) open condition.
1.3.6.1.4.1.476.1.42.3.2.1.42.1IdentitylgpConditionSource1ScrOpencurrentThe system has detected a source 1 Silicon Controlled Rectifier (SCR) open condition.
1.3.6.1.4.1.476.1.42.3.2.1.42.2IdentitylgpConditionSource2ScrOpencurrentThe system has detected a source 2 Silicon Controlled Rectifier (SCR) open condition.
1.3.6.1.4.1.476.1.42.3.2.1.42.3IdentitylgpConditionBypassScrOpencurrentThe system has detected a Silicon Controlled Rectifier (SCR) open condition on the bypass.
1.3.6.1.4.1.476.1.42.3.2.1.42.4IdentitylgpConditionSource1NeutralScrOpencurrentThe system has detected a source 1 Silicon Controlled Rectifier (SCR) open condition on the neutral line.
1.3.6.1.4.1.476.1.42.3.2.1.42.5IdentitylgpConditionSource2NeutralScrOpencurrentThe system has detected a source 2 Silicon Controlled Rectifier (SCR) open condition on the neutral line.
1.3.6.1.4.1.476.1.42.3.2.1.43IdentitylgpConditionFanFailurecurrentThis system has detected a fan failure condition.
1.3.6.1.4.1.476.1.42.3.2.1.43.1IdentitylgpConditionFan1FailurecurrentThe system has detected a fan 1 failure condition.
1.3.6.1.4.1.476.1.42.3.2.1.43.2IdentitylgpConditionRedundantFanFailurecurrentA failure has occurred in a fan that cools the system's internal components and has resulted in a loss of fan redundancy.
1.3.6.1.4.1.476.1.42.3.2.1.43.3IdentitylgpConditionMultipleFanFailurecurrentMultiple fans have failed resulting in a decreased ability to cool the system's internal components.
1.3.6.1.4.1.476.1.42.3.2.1.43.4IdentitylgpConditionBlowerFanFailurecurrentThe system has detected a problem with one or more of the blower fans. These are not the system internal cooling fans.
1.3.6.1.4.1.476.1.42.3.2.1.43.4.1IdentitylgpConditionBottomBlowerFanFailurecurrentThe bottom environmental unit blower fan is not operating within its normal parameters.
1.3.6.1.4.1.476.1.42.3.2.1.43.4.2IdentitylgpConditionTopBlowerFanFailurecurrentThe top environmental unit blower fan is not operating within its normal parameters.
1.3.6.1.4.1.476.1.42.3.2.1.43.5IdentitylgpConditionCondenserFanVFDFailurecurrentThe system has detected a problem with the Variable Frequency Drive system for the condenser fan.
1.3.6.1.4.1.476.1.42.3.2.1.43.6IdentitylgpConditionFanPowerFailurecurrentThe system has detected a power failure on one or more fans.
1.3.6.1.4.1.476.1.42.3.2.1.44IdentitylgpConditionTransferInhibitedcurrentThe system is preventing a transfer of the load to the alternate source.
1.3.6.1.4.1.476.1.42.3.2.1.45IdentitylgpConditionAutoReTransferPrimedcurrentThe system is capable to retransfer to the preferred source.
1.3.6.1.4.1.476.1.42.3.2.1.46IdentitylgpConditionSourcesOutOfSynccurrentThe system has detected that the input sources are not within the specified phase difference (synchronization window).
1.3.6.1.4.1.476.1.42.3.2.1.47IdentitylgpConditionSourceFailurecurrentThis system has detected an input source failure condition.
1.3.6.1.4.1.476.1.42.3.2.1.47.1IdentitylgpConditionSource1FailurecurrentThe system has detected source 1 has failed.
1.3.6.1.4.1.476.1.42.3.2.1.47.2IdentitylgpConditionSource2FailurecurrentThe system has detected source 2 has failed.
1.3.6.1.4.1.476.1.42.3.2.1.48IdentitylgpConditionAutoReTransferInhibitedcurrentThe system is preventing a retransfer of the load back to the preferred source.
1.3.6.1.4.1.476.1.42.3.2.1.49IdentitylgpConditionAutoReTransferFailedcurrentThe system is failing to automatically retransfer the load back to the preferred source.
1.3.6.1.4.1.476.1.42.3.2.1.50IdentitylgpConditionFuseOpencurrentThis system has detected an open fuse condition.
1.3.6.1.4.1.476.1.42.3.2.1.50.1IdentitylgpConditionControlFuse1OpencurrentThe system has detected a control power fuse 1 open condition.
1.3.6.1.4.1.476.1.42.3.2.1.50.2IdentitylgpConditionControlFuse2OpencurrentThe system has detected a control power fuse 2 open condition.
1.3.6.1.4.1.476.1.42.3.2.1.50.3IdentitylgpConditionRectifierFuseOpencurrentThe system has detected a rectifier fuse open condition.
1.3.6.1.4.1.476.1.42.3.2.1.50.4IdentitylgpConditionInverterFuseOpencurrentThe system has detected an inverter fuse open condition.
1.3.6.1.4.1.476.1.42.3.2.1.50.5IdentitylgpConditionOutputToLoadFuseOpencurrentThe system has detected an output to load fuse open condition.
1.3.6.1.4.1.476.1.42.3.2.1.50.6IdentitylgpConditionDcCapacitorFuseOpencurrentThe system has detected a DC capacitor fuse open condition.
1.3.6.1.4.1.476.1.42.3.2.1.51IdentitylgpConditionDisconnectcurrentThe system has detected a disconnect condition.
1.3.6.1.4.1.476.1.42.3.2.1.51.1IdentitylgpConditionSource1DisconnectOpencurrentThe system has detected the source 1 disconnect is open. A disconnect is a device which disconnects a conductor of a circuit from its supply (ex. circuit break…
1.3.6.1.4.1.476.1.42.3.2.1.51.2IdentitylgpConditionSource2DisconnectOpencurrentThe system has detected the source 2 disconnect is open. A disconnect is a device which disconnects a conductor of a circuit from its supply (ex. circuit break…
1.3.6.1.4.1.476.1.42.3.2.1.51.3IdentitylgpConditionSource1PduDisconnectOpencurrentThe system has detected the source 1 PDU (Power Distribution Unit) disconnect is open. A disconnect is a device which disconnects a conductor of a circuit from…
1.3.6.1.4.1.476.1.42.3.2.1.51.4IdentitylgpConditionSource2PduDisconnectOpencurrentThe system has detected the source 2 PDU (Power Distribution Unit) disconnect is open. A disconnect is a device which disconnects a conductor of a circuit from…
1.3.6.1.4.1.476.1.42.3.2.1.51.5IdentitylgpConditionOutputToLoadDisconnect1OpencurrentThe system has detected Output to load disconnect 1 is open. A disconnect is a device which disconnects a conductor of a circuit from its supply (ex. circuit b…
1.3.6.1.4.1.476.1.42.3.2.1.51.6IdentitylgpConditionOutputToLoadDisconnect2OpencurrentThe system has detected Output to load disconnect 2 is open. A disconnect is a device which disconnects a conductor of a circuit from its supply (ex. circuit b…
1.3.6.1.4.1.476.1.42.3.2.1.51.7IdentitylgpConditionSource1BypassDisconnectClosedcurrentThe system has detected the source 1 bypass disconnect is closed. A disconnect is a device which disconnects a conductor of a circuit from its supply (ex. circ…
1.3.6.1.4.1.476.1.42.3.2.1.51.8IdentitylgpConditionSource2BypassDisconnectClosedcurrentThe system has detected the source 2 bypass disconnect is closed. A disconnect is a device which disconnects a conductor of a circuit from its supply (ex. circ…
1.3.6.1.4.1.476.1.42.3.2.1.51.9IdentitylgpConditionOutputToLoadNeutralDisconnectOpencurrentThe system has detected the output to load neutral disconnect is open. A disconnect is a device which disconnects a conductor of a circuit from its supply (ex.…
1.3.6.1.4.1.476.1.42.3.2.1.51.10IdentitylgpConditionBatteryDisconnectOpencurrentThe system has detected the battery disconnect is open. A disconnect is a device which disconnects a conductor of a circuit from its supply (ex. circuit breake…
1.3.6.1.4.1.476.1.42.3.2.1.51.10.1IdentitylgpConditionBatteryDiscOpenCab01currentThe system has detected the cabinet 1 battery disconnect is open.
1.3.6.1.4.1.476.1.42.3.2.1.51.10.2IdentitylgpConditionBatteryDiscOpenCab02currentThe system has detected the cabinet 2 battery disconnect is open.
1.3.6.1.4.1.476.1.42.3.2.1.51.10.3IdentitylgpConditionBatteryDiscOpenCab03currentThe system has detected the cabinet 3 battery disconnect is open.
1.3.6.1.4.1.476.1.42.3.2.1.51.10.4IdentitylgpConditionBatteryDiscOpenCab04currentThe system has detected the cabinet 4 battery disconnect is open.
1.3.6.1.4.1.476.1.42.3.2.1.51.10.5IdentitylgpConditionBatteryDiscOpenCab05currentThe system has detected the cabinet 5 battery disconnect is open.
1.3.6.1.4.1.476.1.42.3.2.1.51.10.6IdentitylgpConditionBatteryDiscOpenCab06currentThe system has detected the cabinet 6 battery disconnect is open.
1.3.6.1.4.1.476.1.42.3.2.1.51.10.7IdentitylgpConditionBatteryDiscOpenCab07currentThe system has detected the cabinet 7 battery disconnect is open.
1.3.6.1.4.1.476.1.42.3.2.1.51.10.8IdentitylgpConditionBatteryDiscOpenCab08currentThe system has detected the cabinet 8 battery disconnect is open.
1.3.6.1.4.1.476.1.42.3.2.1.51.11IdentitylgpConditionInputDisconnectOpencurrentThe system has detected the input disconnect is open. A disconnect is a device which disconnects a conductor of a circuit from its supply (ex. circuit breaker,…
1.3.6.1.4.1.476.1.42.3.2.1.51.12IdentitylgpConditionOutputToLoadDisconnectOpencurrentThe system has detected the Output to load disconnect is open. A disconnect is a device which disconnects a conductor of a circuit from its supply (ex. circuit…
1.3.6.1.4.1.476.1.42.3.2.1.51.13IdentitylgpConditionBypassDisconnectOpencurrentThe system has detected the bypass disconnect is open. A disconnect is a device which disconnects a conductor of a circuit from its supply (ex. circuit breaker…
1.3.6.1.4.1.476.1.42.3.2.1.51.14IdentitylgpConditionStaticSwitchDisconnectOpencurrentThe system has detected the static switch disconnect is open. A disconnect is a device which disconnects a conductor of a circuit from its supply (ex. circuit …
1.3.6.1.4.1.476.1.42.3.2.1.51.15IdentitylgpConditionBreakerOpenFailurecurrentA breaker in the system has failed to respond to an Open signal.
1.3.6.1.4.1.476.1.42.3.2.1.51.16IdentitylgpConditionBreakerCloseFailurecurrentA breaker in the system has failed to respond to a Close signal.
1.3.6.1.4.1.476.1.42.3.2.1.52IdentitylgpConditionFrequencyDeviationcurrentThis system has detected a frequency deviation condition. The frequency of a source is outside of the pre-determined thresholds for a specified amount of time.
1.3.6.1.4.1.476.1.42.3.2.1.52.1IdentitylgpConditionSource1FrequencyDeviationcurrentThe frequency for source 1 has been outside of the pre-determined thresholds for a specified period of time.
1.3.6.1.4.1.476.1.42.3.2.1.52.2IdentitylgpConditionSource2FrequencyDeviationcurrentThe frequency for source 2 has been outside of the pre-determined thresholds for a specified period of time.
1.3.6.1.4.1.476.1.42.3.2.1.52.3IdentitylgpConditionInputFrequencyDeviationcurrentThe frequency for the input has been outside of the pre-determined thresholds for a specified period of time.
1.3.6.1.4.1.476.1.42.3.2.1.52.4IdentitylgpConditionOutputToLoadFrequencyDeviationcurrentThe frequency for the output has been outside of the pre-determined thresholds for a specified period of time.
1.3.6.1.4.1.476.1.42.3.2.1.52.5IdentitylgpConditionBypassFrequencyDeviationcurrentThe frequency for the bypass input has been outside of the pre-determined thresholds for a specified period of time.
1.3.6.1.4.1.476.1.42.3.2.1.53IdentitylgpConditionOverCurrentcurrentThis system has detected an over-current condition. The current of a source has risen above a pre-determined threshold for a device, or system, defined amount …
1.3.6.1.4.1.476.1.42.3.2.1.53.1IdentitylgpConditionSource1OverCurrentcurrentThe system has detected an over current condition on source 1. The current of a source has risen above a pre-determined threshold for a device, or system, defi…
1.3.6.1.4.1.476.1.42.3.2.1.53.2IdentitylgpConditionSource2OverCurrentcurrentThe system has detected an over current condition on source 2. The current of a source has risen above a pre-determined threshold for a device, or system, defi…
1.3.6.1.4.1.476.1.42.3.2.1.53.3IdentitylgpConditionOutputToLoadOverCurrentcurrentThe system has detected the output to load is in an over-current condition. The current for the load has risen above a pre-determined threshold for a device, o…
1.3.6.1.4.1.476.1.42.3.2.1.53.3.1IdentitylgpConditionOutputToLoadOverCurrentPhsAcurrentThe system has detected the output to load on phase A is in an over-current condition. The current on this phase has risen above a pre-determined threshold for…
1.3.6.1.4.1.476.1.42.3.2.1.53.3.2IdentitylgpConditionOutputToLoadOverCurrentPhsBcurrentThe system has detected the output to load on phase B is in an over-current condition. The current on this phase has risen above a pre-determined threshold for…
1.3.6.1.4.1.476.1.42.3.2.1.53.3.3IdentitylgpConditionOutputToLoadOverCurrentPhsCcurrentThe system has detected the output to load on phase C is in an over-current condition. The current on this phase has risen above a pre-determined threshold for…
1.3.6.1.4.1.476.1.42.3.2.1.53.4IdentitylgpConditionGroundOverCurrentcurrentA ground source is experiencing an over-current condition. The current for the ground line has risen above a pre-determined threshold for a device, or system, …
1.3.6.1.4.1.476.1.42.3.2.1.53.5IdentitylgpConditionRectifierOverCurrentcurrentThe system has detected a rectifier over current condition. The current for the rectifier has risen above a pre-determined threshold for a device, or system, d…
1.3.6.1.4.1.476.1.42.3.2.1.53.6IdentitylgpConditionInverterOverCurrentcurrentThe system has detected an inverter over current condition. The current for the inverter has risen above a pre-determined threshold for a device, or system, de…
1.3.6.1.4.1.476.1.42.3.2.1.53.6.1IdentitylgpConditionInverterOverCurrentPhsAcurrentThe system has detected an inverter over current condition on phase A. The current for the this phase in the inverter has risen above a pre-determined threshol…
1.3.6.1.4.1.476.1.42.3.2.1.53.6.2IdentitylgpConditionInverterOverCurrentPhsBcurrentThe system has detected an inverter over current condition on phase B. The current for the this phase in the inverter has risen above a pre-determined threshol…
1.3.6.1.4.1.476.1.42.3.2.1.53.6.3IdentitylgpConditionInverterOverCurrentPhsCcurrentThe system has detected an inverter over current condition on phase C. The current for the this phase in the inverter has risen above a pre-determined threshol…
1.3.6.1.4.1.476.1.42.3.2.1.53.7IdentitylgpConditionBatteryConverterOverCurrentcurrentThe system has detected an over current condition on the battery converter. The current of the converter has risen above a pre-determined threshold for a devic…
1.3.6.1.4.1.476.1.42.3.2.1.53.8IdentitylgpConditionBatteryBalancerOverCurrentcurrentThe system has detected a battery balancer over current condition. The current at this point has risen above a pre-determined threshold for a device, or system…
1.3.6.1.4.1.476.1.42.3.2.1.53.9IdentitylgpConditionHumidifierOverCurrentcurrentThe system has detected an over current condition on the humidifier. The current of the humidifier has risen above a pre-determined threshold for a defined amo…
1.3.6.1.4.1.476.1.42.3.2.1.53.10IdentitylgpConditionInputOverCurrentcurrentThere is an over current condition on the system input power. The input current has risen above a pre-determined threshold for a pre-defined amount of time.
1.3.6.1.4.1.476.1.42.3.2.1.53.11IdentitylgpConditionSource1NeutralOverCurrentcurrentThe system has detected an over current condition on the neutral line of source 1. The neutral current at source 1 has risen above a pre-determined threshold f…
1.3.6.1.4.1.476.1.42.3.2.1.53.12IdentitylgpConditionSource2NeutralOverCurrentcurrentThe system has detected an over current condition on the neutral line of source 2. The neutral current at source 2 has risen above a pre-determined threshold f…
1.3.6.1.4.1.476.1.42.3.2.1.54IdentitylgpConditionSensorFailurecurrentThis system has detected a sensor failure condition.
1.3.6.1.4.1.476.1.42.3.2.1.54.1IdentitylgpConditionOutputToLoadVoltageSensorFailurecurrentThe system had detected an output to load voltage sensor failure.
1.3.6.1.4.1.476.1.42.3.2.1.54.2IdentitylgpConditionSource1VoltageSensorFailurecurrentThe system had detected a source 1 voltage sensor failure.
1.3.6.1.4.1.476.1.42.3.2.1.54.3IdentitylgpConditionSource2VoltageSensorFailurecurrentThe system had detected a source 2 voltage sensor failure.
1.3.6.1.4.1.476.1.42.3.2.1.54.4IdentitylgpConditionSource1ScrSensorFailurecurrentThe system had detected a source 1 SCR (Silicon Controlled Rectifier) sensor failure.
1.3.6.1.4.1.476.1.42.3.2.1.54.5IdentitylgpConditionSource2ScrSensorFailurecurrentThe system had detected a source 2 SCR (Silicon Controlled Rectifier) sensor failure.
1.3.6.1.4.1.476.1.42.3.2.1.54.6IdentitylgpConditionSource1CurrentSensorFailurecurrentThe system has detected a source 1 current sensor failure.
1.3.6.1.4.1.476.1.42.3.2.1.54.7IdentitylgpConditionSource2CurrentSensorFailurecurrentThe system has detected a source 2 current sensor failure.
1.3.6.1.4.1.476.1.42.3.2.1.54.8IdentitylgpConditionRoomTempHumiditySensorFailurecurrentThe system has detected a device temperature and humidity sensor failure.
1.3.6.1.4.1.476.1.42.3.2.1.54.9IdentitylgpConditionGlycolTempSensorFailurecurrentThe system has detected a glycol temperature sensor failure.
1.3.6.1.4.1.476.1.42.3.2.1.54.10IdentitylgpConditionLocal1SensorFailurecurrentThe system has detected a local 1 sensor failure.
1.3.6.1.4.1.476.1.42.3.2.1.54.11IdentitylgpConditionCompressor1SensorFailurecurrentThe system has detected a compressor 1 digital scroll sensor failure condition.
1.3.6.1.4.1.476.1.42.3.2.1.54.12IdentitylgpConditionCompressor2SensorFailurecurrentThe system has detected a compressor 2 digital scroll sensor failure condition.
1.3.6.1.4.1.476.1.42.3.2.1.54.13IdentitylgpConditionSupplySensorFailurecurrentThe system has detected a supply sensor failure.
1.3.6.1.4.1.476.1.42.3.2.1.54.14IdentitylgpConditionCabinetTemperatureSensorFailurecurrentThe system has detected a cabinet temperature sensor failure.
1.3.6.1.4.1.476.1.42.3.2.1.54.15IdentitylgpConditionCabinetHumiditySensorFailurecurrentThe system has detected a cabinet humidity sensor failure.
1.3.6.1.4.1.476.1.42.3.2.1.54.16IdentitylgpConditionRoomTempSensorFailurecurrentThe system has detected a room temperature sensor failure.
1.3.6.1.4.1.476.1.42.3.2.1.54.17IdentitylgpConditionBatteryTempSensorFailurecurrentThe system has detected a battery temperature sensor failure.
1.3.6.1.4.1.476.1.42.3.2.1.54.18IdentitylgpConditionAirSensorAFailurecurrentThe system has detected a failure with air sensor A. The sensor may have been disconnected or the signal is out of range.
1.3.6.1.4.1.476.1.42.3.2.1.54.19IdentitylgpConditionAirSensorBFailurecurrentThe system has detected a failure with air sensor B. The sensor may have been disconnected or the signal is out of range.
1.3.6.1.4.1.476.1.42.3.2.1.54.20IdentitylgpConditionChilledWaterSupplySensorFailurecurrentThe system has detected a failure with the chilled water supply sensor. The sensor may have been disconnected or the signal is out of range.
1.3.6.1.4.1.476.1.42.3.2.1.54.21IdentitylgpConditionRefrigerantSupplySensorFailurecurrentThe system has detected a failure with the refrigerant supply sensor. The sensor may have been disconnected or the signal is out of range.
1.3.6.1.4.1.476.1.42.3.2.1.54.22IdentitylgpConditionFluidSupplySensorFailurecurrentThe system has detected a failure with the fluid supply sensor. The sensor may have been disconnected or the signal is out of range.
1.3.6.1.4.1.476.1.42.3.2.1.54.23IdentitylgpConditionCompressorLowPressureSensorFailurecurrentThe system has detected that a compressor low pressure transducer is disconnected or the signal is out of range.
1.3.6.1.4.1.476.1.42.3.2.1.54.23.1IdentitylgpConditionCompressor1LowPressureSensorFailurecurrentThe system has detected that compressor 1 low pressure transducer is disconnected or the signal is out of range.
1.3.6.1.4.1.476.1.42.3.2.1.54.24IdentitylgpConditionRemoteSensorFailurecurrentThe system has detected that a remote sensor is disconnected or the signal is out of range.
1.3.6.1.4.1.476.1.42.3.2.1.54.25IdentitylgpConditionAirSupplyTempSensorFailurecurrentThe system has detected that the supply air temperature sensor is disconnected or the signal is out of range.
1.3.6.1.4.1.476.1.42.3.2.1.54.26IdentitylgpConditionAirReturnTempSensorFailurecurrentThe system has detected that the return air temperature sensor is disconnected or the signal is out of range.
1.3.6.1.4.1.476.1.42.3.2.1.54.27IdentitylgpConditionCompressorHighPressureSensorFailurecurrentThe system has detected that a compressor high pressure transducer is disconnected or the signal is out of range.
1.3.6.1.4.1.476.1.42.3.2.1.54.27.2IdentitylgpConditionCompressor2HighPressureSensorFailurecurrentThe system has detected that compressor 2 high pressure transducer is disconnected or the signal is out of range.
1.3.6.1.4.1.476.1.42.3.2.1.54.27.3IdentitylgpConditionCompressor3HighPressureSensorFailurecurrentThe system has detected that compressor 3 high pressure transducer is disconnected or the signal is out of range.
1.3.6.1.4.1.476.1.42.3.2.1.54.27.4IdentitylgpConditionCompressor4HighPressureSensorFailurecurrentThe system has detected that compressor 4 high pressure transducer is disconnected or the signal is out of range.
1.3.6.1.4.1.476.1.42.3.2.1.55IdentitylgpConditionInternalCommunicationFailurecurrentThis system has detected an internal communication failure condition.
1.3.6.1.4.1.476.1.42.3.2.1.56IdentitylgpConditionExternalCommunicationFailurecurrentThis system has detected an external communication failure condition.
1.3.6.1.4.1.476.1.42.3.2.1.57IdentitylgpConditionSourceGateDriveFailurecurrentThis system has detected a source gate drive failure condition.
1.3.6.1.4.1.476.1.42.3.2.1.57.1IdentitylgpConditionSource1GateDriveFailurecurrentThe system has detected a source 1 gate drive failure.
1.3.6.1.4.1.476.1.42.3.2.1.57.2IdentitylgpConditionSource2GateDriveFailurecurrentThe system has detected a source 2 gate drive failure.
1.3.6.1.4.1.476.1.42.3.2.1.58IdentitylgpConditionDisconnectFailurecurrentThis system has detected a disconnect failure condition. A disconnect is a device which disconnects a conductor of a circuit from its supply (ex. circuit break…
1.3.6.1.4.1.476.1.42.3.2.1.58.1IdentitylgpConditionOutputToLoadNeutralDisconnectFailurecurrentThe system has detected the output to load neutral disconnect has failed. A disconnect is a device which disconnects a conductor of a circuit from its supply (…
1.3.6.1.4.1.476.1.42.3.2.1.58.2IdentitylgpConditionSource1DisconnectShuntTripFailurecurrentThe system has detected a shunt trip failure of a disconnecting device on source 1. A disconnect is a device which disconnects a conductor of a circuit from it…
1.3.6.1.4.1.476.1.42.3.2.1.58.3IdentitylgpConditionSource2DisconnectShuntTripFailurecurrentThe system has detected a shunt trip failure of a disconnecting device on source 2. A disconnect is a device which disconnects a conductor of a circuit from it…
1.3.6.1.4.1.476.1.42.3.2.1.58.4IdentitylgpConditionInverterDisconnectFailurecurrentThe system has detected an inverter disconnect failure. A disconnect is a device which disconnects a conductor of a circuit from its supply (ex. circuit breake…
1.3.6.1.4.1.476.1.42.3.2.1.58.5IdentitylgpConditionBatteryDisconnectFailurecurrentThe system has detected a battery disconnect failure. A disconnect is a device which disconnects a conductor of a circuit from its supply (ex. circuit breaker,…
1.3.6.1.4.1.476.1.42.3.2.1.58.6IdentitylgpConditionRectifierDisconnectFailurecurrentThe system has detected a rectifier disconnect failure. A disconnect is a device which disconnects a conductor of a circuit from its supply (ex. circuit breake…
1.3.6.1.4.1.476.1.42.3.2.1.59IdentitylgpConditionOverTemperaturecurrentThis system has detected an over temperature condition.
1.3.6.1.4.1.476.1.42.3.2.1.59.1IdentitylgpConditionHeatSink1OverTemperaturecurrentThe system has detected a heat sink 1 over temperature condition.
1.3.6.1.4.1.476.1.42.3.2.1.59.2IdentitylgpConditionAmbient1OverTemperaturecurrentThe system has detected an ambient over temperature condition at location 1.
1.3.6.1.4.1.476.1.42.3.2.1.59.3IdentitylgpConditionSystemOverTemperaturecurrentThe system or a component of the system has detected an over temperature condition. The temperature measurement has risen above a pre-determined threshold for …
1.3.6.1.4.1.476.1.42.3.2.1.59.4IdentitylgpConditionTransformerOverTemperaturecurrentThe transformer is experiencing an over temperature condition. The transformer's temperature has exceeded a pre-determined threshold for a device, or system, d…
1.3.6.1.4.1.476.1.42.3.2.1.59.5IdentitylgpConditionBatteryOverTemperaturecurrentThe battery is experiencing an over temperature condition. The battery's temperature has exceeded a pre-determined threshold for a device, or system, defined a…
1.3.6.1.4.1.476.1.42.3.2.1.59.6IdentitylgpConditionRectifierOverTemperaturecurrentThe system has detected a rectifier over temperature condition. The rectifier's temperature has exceeded a pre-determined threshold for a device, or system, de…
1.3.6.1.4.1.476.1.42.3.2.1.59.7IdentitylgpConditionInverterOverTemperaturecurrentThe system has detected an inverter over temperature condition. The inverter's temperature has exceeded a pre-determined threshold for a device, or system, def…
1.3.6.1.4.1.476.1.42.3.2.1.59.8IdentitylgpConditionRectifierInductorOverTemperaturecurrentThe system has detected a rectifier inductor over temperature condition. The rectifier's inductor temperature has exceeded a pre-determined threshold for a dev…
1.3.6.1.4.1.476.1.42.3.2.1.59.9IdentitylgpConditionInverterInductorOverTemperaturecurrentThe system has detected an inverter inductor over temperature condition. The inverter's inductor temperature has exceeded a pre-determined threshold for a devi…
1.3.6.1.4.1.476.1.42.3.2.1.59.10IdentitylgpConditionBatteryConverterOverTemperaturecurrentThe system has detected a battery converter over temperature condition. The battery converter's temperature has exceeded a pre-determined threshold for a devic…
1.3.6.1.4.1.476.1.42.3.2.1.59.11IdentitylgpConditionBatteryBalancerInductorOverTemperaturecurrentThe system has detected a battery balancer Inductor over temperature condition. The battery balancer Inductor's temperature has exceeded a pre-determined thres…
1.3.6.1.4.1.476.1.42.3.2.1.59.12IdentitylgpConditionChilledWaterOverTemperaturecurrentThe system has detected a chilled water over temperature condition.
1.3.6.1.4.1.476.1.42.3.2.1.59.13IdentitylgpConditionElectricHeatersOverTemperaturecurrentThe system has detected an electric heater over temperature condition.
1.3.6.1.4.1.476.1.42.3.2.1.59.14IdentitylgpConditionInletAirOverTemperaturecurrentThe system has detected an inlet air over temperature condition.
1.3.6.1.4.1.476.1.42.3.2.1.59.15IdentitylgpConditionSystemOverTempWarningcurrentThe system or a component of the system has detected an over temperature condition. The temperature measurement has risen above a normal operating range for a …
1.3.6.1.4.1.476.1.42.3.2.1.59.16IdentitylgpConditionHighTemperatureBattStringcurrentThe system has detected a high temperature on a battery string. The temperature has exceeded a specified temperature threshold.
1.3.6.1.4.1.476.1.42.3.2.1.60IdentitylgpConditionLoadOnAlternateSourcecurrentThe system has detected that the load is being supplied by the alternate source.
1.3.6.1.4.1.476.1.42.3.2.1.61IdentitylgpConditionPhaseRotationErrorcurrentThis system has detected a phase rotation error condition.
1.3.6.1.4.1.476.1.42.3.2.1.61.1IdentitylgpConditionSource1PhaseRotationErrorcurrentThe system has detected a phase rotation error on source 1.
1.3.6.1.4.1.476.1.42.3.2.1.61.2IdentitylgpConditionSource2PhaseRotationErrorcurrentThe system has detected a phase rotation error on source 2.
1.3.6.1.4.1.476.1.42.3.2.1.61.3IdentitylgpConditionBypassPhaseRotationErrorcurrentThe system has detected a phase rotation error on the bypass.
1.3.6.1.4.1.476.1.42.3.2.1.61.4IdentitylgpConditionInputPhaseRotationErrorcurrentThe system has detected a phase rotation error on the input.
1.3.6.1.4.1.476.1.42.3.2.1.62IdentitylgpConditionControlModuleFailurecurrentThis system has detected a control module failure condition.
1.3.6.1.4.1.476.1.42.3.2.1.62.1IdentitylgpConditionControlModule1FailurecurrentThe system has detected a control module 1 failure.
1.3.6.1.4.1.476.1.42.3.2.1.63IdentitylgpConditionHistoryLogFullcurrentThe system has detected the history log is full.
1.3.6.1.4.1.476.1.42.3.2.1.64IdentitylgpConditionConfigurationModifiedcurrentThe system has detected the configuration has been modified.
1.3.6.1.4.1.476.1.42.3.2.1.65IdentitylgpConditionPasswordModifiedcurrentThe system has detected the password has been modified.
1.3.6.1.4.1.476.1.42.3.2.1.66IdentitylgpConditionTimeModifiedcurrentThe system has detected the time has been modified.
1.3.6.1.4.1.476.1.42.3.2.1.67IdentitylgpConditionDateModifiedcurrentThe system has detected the date has been modified.
1.3.6.1.4.1.476.1.42.3.2.1.68IdentitylgpConditionEventLogClearedcurrentThe system has detected the event log has been cleared.
1.3.6.1.4.1.476.1.42.3.2.1.69IdentitylgpConditionHistoryLogClearedcurrentThe system has detected the history log has been cleared.
1.3.6.1.4.1.476.1.42.3.2.1.70IdentitylgpConditionUtilityFailurecurrentThe system has detected a utility failure.
1.3.6.1.4.1.476.1.42.3.2.1.71IdentitylgpConditionBatteryTestInProgresscurrentThe system is performing a battery test at this time.
1.3.6.1.4.1.476.1.42.3.2.1.72IdentitylgpConditionLoadOnBatterycurrentThe system load is being supported by the battery.
1.3.6.1.4.1.476.1.42.3.2.1.74IdentitylgpConditionReplaceBatterycurrentThe system has detected the batteries are due to be replaced.
1.3.6.1.4.1.476.1.42.3.2.1.75IdentitylgpConditionUpsShutdownPendingcurrentThe system is in a shutdown pending condition.
1.3.6.1.4.1.476.1.42.3.2.1.76IdentitylgpConditionBatteryChargerFailedcurrentThe system has detected the battery charger has failed.
1.3.6.1.4.1.476.1.42.3.2.1.77IdentitylgpConditionBypassVoltageUnqualifiedcurrentThe system has detected the bypass voltage is unqualified. The voltage measurement is outside a pre-determined threshold range for a specified amount of time.
1.3.6.1.4.1.476.1.42.3.2.1.78IdentitylgpConditionCheckAirFiltercurrentThe system has detected it is time to check the air filter.
1.3.6.1.4.1.476.1.42.3.2.1.79IdentitylgpConditionBrownOutcurrentThe system has detected a brown out condition.
1.3.6.1.4.1.476.1.42.3.2.1.80IdentitylgpConditionMultipleTransferLockoutcurrentThe system has locked out transfers to bypass. Too many transfers have occurred over a specified amount of time.
1.3.6.1.4.1.476.1.42.3.2.1.81IdentitylgpConditionBypassPhaseLostcurrentThe system has detected one or more bypass phases are missing.
1.3.6.1.4.1.476.1.42.3.2.1.82IdentitylgpConditionMaintenceBypassInhibitedcurrentThe system is preventing a transfer of the load to maintenance bypass.
1.3.6.1.4.1.476.1.42.3.2.1.83IdentitylgpConditionLoadLockedOnBypasscurrentAn error has been detected requiring the system to be put into a 'locked on bypass' state.
1.3.6.1.4.1.476.1.42.3.2.1.84IdentitylgpConditionOutputToLoadShortcurrentThe system has detected an output to load short circuit condition.
1.3.6.1.4.1.476.1.42.3.2.1.85IdentitylgpConditionEmergencyTransferToInvertercurrentThe system has detected an emergency transfer of the load to inverter.
1.3.6.1.4.1.476.1.42.3.2.1.86IdentitylgpConditonEmergencyPowerOffcurrentThe system has detected an Emergency Power Off (EPO) condition. An external EPO switch has cut off the power source to the system.
1.3.6.1.4.1.476.1.42.3.2.1.87IdentitylgpConditionInverterBackFeedcurrentThe system has detected an inverter back-feed condition. The inverter is feeding power through the bypass back to the input.
1.3.6.1.4.1.476.1.42.3.2.1.88IdentitylgpConditionDcGroundFaultcurrentThe system has detected a DC ground fault.
1.3.6.1.4.1.476.1.42.3.2.1.88.1IdentitylgpConditionDcGroundFaultPoscurrentGround fault current has been detected in the positive DC link to ground.
1.3.6.1.4.1.476.1.42.3.2.1.88.2IdentitylgpConditionDcGroundFaultNegcurrentGround fault current has been detected in the negative DC link to ground.
1.3.6.1.4.1.476.1.42.3.2.1.89IdentitylgpConditionStaticTransferSwitchInhibitedcurrentThe system is preventing the use of the static transfer switch.
1.3.6.1.4.1.476.1.42.3.2.1.90IdentitylgpConditionBatteryLogFullWarningcurrentThe system has detected the battery log is approaching the maximum record limit.
1.3.6.1.4.1.476.1.42.3.2.1.91IdentitylgpConditionInputCurrentUnbalancedcurrentThe system has detected an unbalanced input current condition. The currents of input phases are out of tolerance.
1.3.6.1.4.1.476.1.42.3.2.1.92IdentitylgpConditionSelfTestFailedcurrentThe system has detected a self-test failure.
1.3.6.1.4.1.476.1.42.3.2.1.93IdentitylgpConditionInverterOutOfSynchronizationcurrentThe system has detected an Inverter out of sync condition.
1.3.6.1.4.1.476.1.42.3.2.1.94IdentitylgpConditionModuleAlarmcurrentThis system has detected an alarm within the multi-module system.
1.3.6.1.4.1.476.1.42.3.2.1.94.1IdentitylgpConditioniModuleUnit1AlarmcurrentThe multi-module system has detected an alarm condition on unit 1.
1.3.6.1.4.1.476.1.42.3.2.1.94.2IdentitylgpConditioniModuleUnit2AlarmcurrentThe multi-module system has detected an alarm condition on unit 2.
1.3.6.1.4.1.476.1.42.3.2.1.94.3IdentitylgpConditioniModuleUnit3AlarmcurrentThe multi-module system has detected an alarm condition on unit 3.
1.3.6.1.4.1.476.1.42.3.2.1.94.4IdentitylgpConditioniModuleUnit4AlarmcurrentThe multi-module system has detected an alarm condition on unit 4.
1.3.6.1.4.1.476.1.42.3.2.1.94.5IdentitylgpConditioniModuleUnit5AlarmcurrentThe multi-module system has detected an alarm condition on unit 5.
1.3.6.1.4.1.476.1.42.3.2.1.94.6IdentitylgpConditioniModuleUnit6AlarmcurrentThe multi-module system has detected an alarm condition on unit 6.
1.3.6.1.4.1.476.1.42.3.2.1.94.7IdentitylgpConditioniModuleUnit7AlarmcurrentThe multi-module system has detected an alarm condition on unit 7.
1.3.6.1.4.1.476.1.42.3.2.1.94.8IdentitylgpConditioniModuleUnit8AlarmcurrentThe multi-module system has detected an alarm condition on unit 8.
1.3.6.1.4.1.476.1.42.3.2.1.95IdentitylgpConditionActiveModuleAlarmcurrentThe system has detected an active alarm in one, or more, of the sub-modules of the multi-module system.
1.3.6.1.4.1.476.1.42.3.2.1.96IdentitylgpConditionControlFailurecurrentThis system has detected a control failure condition.
1.3.6.1.4.1.476.1.42.3.2.1.96.1IdentitylgpConditionMainControlFailurecurrentThe system has detected a main control failure condition.
1.3.6.1.4.1.476.1.42.3.2.1.96.2IdentitylgpConditionRedundantControlFailurecurrentThe system has detected a redundant control failure condition.
1.3.6.1.4.1.476.1.42.3.2.1.96.3IdentitylgpConditionParallelSysControlFailurecurrentThe parallel system has detected a control failure condition with one of the controls.
1.3.6.1.4.1.476.1.42.3.2.1.96.4IdentitylgpConditionMainControlCommFailurecurrentOne or more communications failures have occurred in the main control.
1.3.6.1.4.1.476.1.42.3.2.1.96.5IdentitylgpConditionControlBoardFailurecurrentThe system has detected a control board failure.
1.3.6.1.4.1.476.1.42.3.2.1.96.5.1IdentitylgpConditionHumidifierControlBdFailurecurrentHumidifier control board is required to be connected, but no signal is detected.
1.3.6.1.4.1.476.1.42.3.2.1.97IdentitylgpConditionControlWarningcurrentThis system has detected a control warning conditions.
1.3.6.1.4.1.476.1.42.3.2.1.97.1IdentitylgpConditionMainControlWarningcurrentThe system has detected a main control warning condition.
1.3.6.1.4.1.476.1.42.3.2.1.97.2IdentitylgpConditionRedundantControlWarningcurrentThe system has detected a redundant control warning condition.
1.3.6.1.4.1.476.1.42.3.2.1.98IdentitylgpConditionUserInterfaceFailurecurrentThe system has detected a user interface control failure condition.
1.3.6.1.4.1.476.1.42.3.2.1.99IdentitylgpConditionLostPowerRedundancycurrentThe system has detected the number of redundant power modules has fallen below the minimum redundant power module setting.
1.3.6.1.4.1.476.1.42.3.2.1.100IdentitylgpConditionPowerModuleFailurecurrentThe system has detected a power module failure condition in the system.
1.3.6.1.4.1.476.1.42.3.2.1.101IdentitylgpConditionBatteryModuleFailurecurrentThe system has detected a battery module failure condition in the system.
1.3.6.1.4.1.476.1.42.3.2.1.102IdentitylgpConditionOutputToLoadOffcurrentThe system has detected that there is no power being supplied to the load.
1.3.6.1.4.1.476.1.42.3.2.1.103IdentitylgpConditionSystemOffcurrentThe system is off.
1.3.6.1.4.1.476.1.42.3.2.1.104IdentitylgpConditionRectifierStartupFailurecurrentThe system has detected a rectifier under voltage start-up failure condition.
1.3.6.1.4.1.476.1.42.3.2.1.105IdentitylgpConditionRectifierFaultcurrentThe system has detected a rectifier fault condition.
1.3.6.1.4.1.476.1.42.3.2.1.106IdentitylgpConditionInverterShutdownLowDccurrentThe system has shutdown the inverter due to a DC bus under voltage.
1.3.6.1.4.1.476.1.42.3.2.1.107IdentitylgpConditionInverterFaultcurrentThe system has detected an inverter fault condition.
1.3.6.1.4.1.476.1.42.3.2.1.108IdentitylgpConditionInverterDcOffsetOverruncurrentThe system has detected an over run of the inverter DC offset voltage.
1.3.6.1.4.1.476.1.42.3.2.1.109IdentitylgpConditionParallelSysLowBatteryWarningcurrentThe parallel system has detected a low battery warning condition.
1.3.6.1.4.1.476.1.42.3.2.1.110IdentitylgpConditionParallelSysLoadShareFaultcurrentThe parallel system has detected a load share fault condition.
1.3.6.1.4.1.476.1.42.3.2.1.111IdentitylgpConditionBatteryFaultcurrentThe system has detected a battery fault condition. The battery conductors are either reversed or disconnected.
1.3.6.1.4.1.476.1.42.3.2.1.112IdentitylgpConditionBatteryConverterFailurecurrentThe system has detected a battery converter failure condition.
1.3.6.1.4.1.476.1.42.3.2.1.113IdentitylgpConditionBatteryBalancerFaultcurrentThe system has detected a battery balancer fault condition.
1.3.6.1.4.1.476.1.42.3.2.1.114IdentitylgpConditionpsUpsOperationFaultdeprecatedThe system has detected an operation fault. The UPS attempted to transfer to maintenance bypass without following the proper sequence.
1.3.6.1.4.1.476.1.42.3.2.1.115IdentitylgpConditionOutputToLoadOnJointModecurrentThe system load is being supported by both the battery and rectifier.
1.3.6.1.4.1.476.1.42.3.2.1.116IdentitylgpConditionInputNeutralLostcurrentThe system had detected the main input neutral is disconnected.
1.3.6.1.4.1.476.1.42.3.2.1.117IdentitylgpConditionLowBatteryWarningcurrentThe battery's remaining charge is less than or equal to the configured low threshold.
1.3.6.1.4.1.476.1.42.3.2.1.118IdentitylgpConditionInternalFaultcurrentThe system has detected an internal fault.
1.3.6.1.4.1.476.1.42.3.2.1.119IdentitylgpConditionBatteryTestFailedcurrentThe system has detected a battery self-test failure.
1.3.6.1.4.1.476.1.42.3.2.1.120IdentitylgpConditionPowerModuleWarningcurrentThe system has detected an alarm condition on one, or more, power modules.
1.3.6.1.4.1.476.1.42.3.2.1.121IdentitylgpConditionBatteryModuleWarningcurrentThe system has detected an alarm condition on one, or more, battery modules.
1.3.6.1.4.1.476.1.42.3.2.1.122IdentitylgpConditionControlModuleWarningcurrentThe system has detected a control module warning.
1.3.6.1.4.1.476.1.42.3.2.1.123IdentitylgpConditionUpsOperationFaultcurrentThe system has detected an operation fault. The UPS attempted to transfer to maintenance bypass without following the proper sequence.
1.3.6.1.4.1.476.1.42.3.2.1.124IdentitylgpConditionActiveAlarmcurrentThe system has detected an alarm condition.
1.3.6.1.4.1.476.1.42.3.2.1.125IdentitylgpConditionRectifierCommunicationFailurecurrentThe system has detected an internal communication failure condition with the rectifier.
1.3.6.1.4.1.476.1.42.3.2.1.126IdentitylgpConditionInverterCommunicationFailurecurrentThe system has detected an internal communication failure condition with the inverter.
1.3.6.1.4.1.476.1.42.3.2.1.127IdentitylgpConditionParallelSysConnectionFaultcurrentThe parallel system has detected a connection fault. One or more of the devices are not properly connected.
1.3.6.1.4.1.476.1.42.3.2.1.128IdentitylgpConditionParallelSysCommunicationFailurecurrentThe parallel system has detected a communication failure.
1.3.6.1.4.1.476.1.42.3.2.1.129IdentitylgpConditionLostBatteryRedundancycurrentThe system has detected the number of redundant battery modules has fallen below the configured redundant battery module threshold.
1.3.6.1.4.1.476.1.42.3.2.1.130IdentitylgpConditionCompPumpDownFailurecurrentThe system has detected that a compressor has failed to pump down.
1.3.6.1.4.1.476.1.42.3.2.1.130.1IdentitylgpConditionComp1PumpDownFailurecurrentThe system has detected that compressor 1 has failed to pump down.
1.3.6.1.4.1.476.1.42.3.2.1.130.2IdentitylgpConditionComp2PumpDownFailurecurrentThe system has detected that compressor 2 has failed to pump down.
1.3.6.1.4.1.476.1.42.3.2.1.130.3IdentitylgpConditionComp3PumpDownFailurecurrentThe system has detected that compressor 3 has failed to pump down.
1.3.6.1.4.1.476.1.42.3.2.1.130.4IdentitylgpConditionComp4PumpDownFailurecurrentThe system has detected that compressor 4 has failed to pump down.
1.3.6.1.4.1.476.1.42.3.2.1.131IdentitylgpConditionChilledWaterLowWaterFlowcurrentThe system has detected a chilled water low water flow condition.
1.3.6.1.4.1.476.1.42.3.2.1.131.2IdentitylgpConditionChilledWaterLowWaterFlowCircuit2currentThe system has detected a chilled water low water flow condition for circuit 2.
1.3.6.1.4.1.476.1.42.3.2.1.132IdentitylgpConditionAirFilterCloggeddeprecatedThe system has detected a air filter clogged condition.
1.3.6.1.4.1.476.1.42.3.2.1.133IdentitylgpConditionHumidifierFailurecurrentThe system has detected a humidifier failure condition.
1.3.6.1.4.1.476.1.42.3.2.1.134IdentitylgpConditionRunHoursExceededcurrentThe system has detected a pre-determined run hours threshold has been exceeded.
1.3.6.1.4.1.476.1.42.3.2.1.134.1IdentitylgpConditionUnitRunHrsExceededcurrentThe system has detected the system run hours has exceeded the pre-determined threshold.
1.3.6.1.4.1.476.1.42.3.2.1.134.2IdentitylgpConditionComp1RunHrsExceededcurrentThe system has detected the compressor 1 run hours has exceeded the pre-determined threshold.
1.3.6.1.4.1.476.1.42.3.2.1.134.3IdentitylgpConditionComp2RunHrsExceededcurrentThe system has detected the compressor 2 run hours has exceeded the pre-determined threshold.
1.3.6.1.4.1.476.1.42.3.2.1.134.4IdentitylgpConditionFreeCoolRunHrsExceededcurrentThe system has detected the free cooling run hours has exceeded the pre-determined threshold.
1.3.6.1.4.1.476.1.42.3.2.1.134.5IdentitylgpConditionElectricalHeater1RunHrsExceededcurrentThe system has detected the electrical heater's run hours have exceeded the pre-determined threshold.
1.3.6.1.4.1.476.1.42.3.2.1.134.6IdentitylgpConditionElectricalHeater2RunHrsExceededcurrentThe system has detected the electrical heater's run hours have exceeded the pre-determined limit.
1.3.6.1.4.1.476.1.42.3.2.1.134.7IdentitylgpConditionElectricalHeater3RunHrsExceededcurrentThe system has detected the electrical heater's run hours have exceeded the pre-determined limit.
1.3.6.1.4.1.476.1.42.3.2.1.134.8IdentitylgpConditionHotWaterRunHrsExceededcurrentThe system has detected the hot water run hours have exceeded the pre-determined threshold.
1.3.6.1.4.1.476.1.42.3.2.1.134.9IdentitylgpConditionHotGasRunHrsExceededcurrentThe system has detected the hot gas run hours have exceeded the pre-determined threshold.
1.3.6.1.4.1.476.1.42.3.2.1.134.10IdentitylgpConditionHumidifierRunHrsExceededcurrentThe system has detected the humidifier run hours have exceeded the pre-determined threshold.
1.3.6.1.4.1.476.1.42.3.2.1.134.11IdentitylgpConditionDehumidiferRunHrsExceededcurrentThe system has detected the dehumidifier run hours have exceeded the pre-determined threshold.
1.3.6.1.4.1.476.1.42.3.2.1.134.12IdentitylgpConditionFanRunHrsExceededcurrentThe system has detected the unit blower fan run hours have exceeded the pre-determined threshold.
1.3.6.1.4.1.476.1.42.3.2.1.135IdentitylgpConditionCommWarningcurrentThe system has detected a loss of communications with another module.
1.3.6.1.4.1.476.1.42.3.2.1.135.1IdentitylgpConditionCommWarningUnit1currentThe system has detected a loss of communications with unit 1.
1.3.6.1.4.1.476.1.42.3.2.1.135.2IdentitylgpConditionCommWarningUnit2currentThe system has detected a loss of communications with unit 2.
1.3.6.1.4.1.476.1.42.3.2.1.135.3IdentitylgpConditionCommWarningUnit3currentThe system has detected a loss of communications with unit 3.
1.3.6.1.4.1.476.1.42.3.2.1.135.4IdentitylgpConditionCommWarningUnit4currentThe system has detected a loss of communications with unit 4.
1.3.6.1.4.1.476.1.42.3.2.1.135.5IdentitylgpConditionCommWarningUnit5currentThe system has detected a loss of communications with unit 5.
1.3.6.1.4.1.476.1.42.3.2.1.135.6IdentitylgpConditionCommWarningUnit6currentThe system has detected a loss of communications with unit 6.
1.3.6.1.4.1.476.1.42.3.2.1.135.7IdentitylgpConditionCommWarningUnit7currentThe system has detected a loss of communications with unit 7.
1.3.6.1.4.1.476.1.42.3.2.1.135.8IdentitylgpConditionCommWarningUnit8currentThe system has detected a loss of communications with unit 8.
1.3.6.1.4.1.476.1.42.3.2.1.135.9IdentitylgpConditionCommWarningUnit9currentThe system has detected a loss of communications with unit 9.
1.3.6.1.4.1.476.1.42.3.2.1.135.10IdentitylgpConditionCommWarningUnit10currentThe system has detected a loss of communications with unit 10.
1.3.6.1.4.1.476.1.42.3.2.1.135.11IdentitylgpConditionCommWarningUnit11currentThe system has detected a loss of communications with unit 11.
1.3.6.1.4.1.476.1.42.3.2.1.135.12IdentitylgpConditionCommWarningUnit12currentThe system has detected a loss of communications with unit 12.
1.3.6.1.4.1.476.1.42.3.2.1.135.13IdentitylgpConditionCommWarningUnit13currentThe system has detected a loss of communications with unit 13.
1.3.6.1.4.1.476.1.42.3.2.1.135.14IdentitylgpConditionCommWarningUnit14currentThe system has detected a loss of communications with unit 14.
1.3.6.1.4.1.476.1.42.3.2.1.135.15IdentitylgpConditionCommWarningUnit15currentThe system has detected a loss of communications with unit 15.
1.3.6.1.4.1.476.1.42.3.2.1.135.16IdentitylgpConditionCommWarningUnit16currentThe system has detected a loss of communications with unit 16.
1.3.6.1.4.1.476.1.42.3.2.1.136IdentitylgpConditionUnitOncurrentThe unit is on.
1.3.6.1.4.1.476.1.42.3.2.1.137IdentitylgpConditionUnitOffcurrentThe unit is off.
1.3.6.1.4.1.476.1.42.3.2.1.138IdentitylgpConditionSleepModeOffcurrentThe system sleep mode operation has been turned off.
1.3.6.1.4.1.476.1.42.3.2.1.139IdentitylgpConditionPowerOncurrentThe system power is on.
1.3.6.1.4.1.476.1.42.3.2.1.140IdentitylgpConditionSystemOnStanbycurrentThe system is on standby.
1.3.6.1.4.1.476.1.42.3.2.1.141IdentitylgpConditionPowerOffcurrentThe system power is off.
1.3.6.1.4.1.476.1.42.3.2.1.142IdentitylgpConditionHighTemperatureGroupcurrentThe system has detected a high temperature condition. This group contains various high temperature conditions.
1.3.6.1.4.1.476.1.42.3.2.1.142.1IdentitylgpConditionHighTemperatureSensor1currentThe temperature has exceeded the high temperature threshold for sensor 1.
1.3.6.1.4.1.476.1.42.3.2.1.142.2IdentitylgpConditionHighTemperatureDigitalScroll1currentThe system has detected a high temperature event on Digital Scroll Compressor 1. The temperature has exceeded a specified temperature threshold.
1.3.6.1.4.1.476.1.42.3.2.1.142.3IdentitylgpConditionHighTemperatureDigitalScroll2currentThe system has detected a high temperature event on Digital Scroll Compressor 2. The temperature has exceeded a specified temperature threshold.
1.3.6.1.4.1.476.1.42.3.2.1.142.4IdentitylgpConditionHighTemperatureUser1currentThe temperature has exceeded the high temperature threshold for user configured temperature sensor 1.
1.3.6.1.4.1.476.1.42.3.2.1.142.5IdentitylgpConditionHighTemperatureInternalcurrentThe system has detected a high internal temperature condition. The temperature has exceeded a specified temperature threshold.
1.3.6.1.4.1.476.1.42.3.2.1.142.6IdentitylgpConditionHighTemperatureExternalAirSensorAcurrentThe temperature has exceeded the high temperature threshold for external air sensor A.
1.3.6.1.4.1.476.1.42.3.2.1.142.7IdentitylgpConditionHighTemperatureExternalAirSensorBcurrentThe temperature has exceeded the high temperature threshold for external air sensor B.
1.3.6.1.4.1.476.1.42.3.2.1.142.8IdentitylgpConditionHighTemperatureRefrigerantSupplycurrentThe temperature has exceeded the high temperature threshold for the refrigerant supply.
1.3.6.1.4.1.476.1.42.3.2.1.142.9IdentitylgpConditionHighTemperatureFluidSupplycurrentThe temperature has exceeded the high temperature threshold for the fluid supply.
1.3.6.1.4.1.476.1.42.3.2.1.142.10IdentitylgpConditionHighTemperatureSupplyAircurrentThe temperature has exceeded the high temperature threshold for the supply air.
1.3.6.1.4.1.476.1.42.3.2.1.142.11IdentitylgpConditionHighTemperatureReturnAircurrentThe temperature has exceeded the high temperature threshold for the return air.
1.3.6.1.4.1.476.1.42.3.2.1.143IdentitylgpConditionLowTemperatureGroupcurrentThe system has detected a low temperature condition. This group contains various low temperature conditions.
1.3.6.1.4.1.476.1.42.3.2.1.143.1IdentitylgpConditionLowTemperatureSensor1currentThe temperature is below the low temperature threshold for sensor 1.
1.3.6.1.4.1.476.1.42.3.2.1.143.2IdentitylgpConditionLowTemperatureInternalcurrentThe system has detected a low internal temperature condition. The temperature is below a specified temperature threshold.
1.3.6.1.4.1.476.1.42.3.2.1.143.3IdentitylgpConditionLowTemperatureExternalAirSensorAcurrentThe temperature is below the low temperature threshold for external air sensor A.
1.3.6.1.4.1.476.1.42.3.2.1.143.4IdentitylgpConditionLowTemperatureExternalAirSensorBcurrentThe temperature is below the low temperature threshold for external air sensor B.
1.3.6.1.4.1.476.1.42.3.2.1.143.5IdentitylgpConditionLowTemperatureRefrigerantSupplycurrentThe temperature is below the low temperature threshold for the refrigerant supply.
1.3.6.1.4.1.476.1.42.3.2.1.143.6IdentitylgpConditionLowTemperatureFluidSupplycurrentThe temperature is below the low temperature threshold for the fluid supply.
1.3.6.1.4.1.476.1.42.3.2.1.143.7IdentitylgpConditionLowTemperatureSupplyAircurrentThe temperature is below the low temperature threshold for the supply air.
1.3.6.1.4.1.476.1.42.3.2.1.144IdentitylgpConditionHighHumidityGroupcurrentThe system has detected a high humidity condition. This group contains various high humidity conditions.
1.3.6.1.4.1.476.1.42.3.2.1.144.1IdentitylgpConditionHighHumiditySensor1currentThe humidity has exceeded the high humidity threshold for sensor 1.
1.3.6.1.4.1.476.1.42.3.2.1.144.2IdentitylgpConditionHighHumidityReturnAircurrentThe humidity has exceeded the high humidity threshold for the return air.
1.3.6.1.4.1.476.1.42.3.2.1.145IdentitylgpConditionLowHumidityGroupcurrentThe system has detected a low humidity condition. This group contains various high humidity conditions.
1.3.6.1.4.1.476.1.42.3.2.1.145.1IdentitylgpConditionLowHumiditySensor1currentThe humidity is below the low humidity threshold for sensor 1.
1.3.6.1.4.1.476.1.42.3.2.1.145.2IdentitylgpConditionLowHumidityReturnAircurrentThe humidity is below the low humidity threshold for the return air.
1.3.6.1.4.1.476.1.42.3.2.1.146IdentitylgpConditionPeerNetworkNoMastercurrentThe system is unable to communicate with the master on the peer to peer network.
1.3.6.1.4.1.476.1.42.3.2.1.147IdentitylgpConditionNoOnOffPermissionscurrentThe system lacks the permissions to execute the on/off operation.
1.3.6.1.4.1.476.1.42.3.2.1.148IdentitylgpConditionPeerNetworkFailurecurrentThe system has detected a communication failure on the peer to peer network.
1.3.6.1.4.1.476.1.42.3.2.1.149IdentitylgpConditionUnitDisabledcurrentThe unit is disabled.
1.3.6.1.4.1.476.1.42.3.2.1.150IdentitylgpConditionUnitShutdowncurrentThe system has shutdown.
1.3.6.1.4.1.476.1.42.3.2.1.151IdentitylgpConditionPeerNetworkDiscoveredcurrentThe system has established communications on the peer to peer network.
1.3.6.1.4.1.476.1.42.3.2.1.152IdentitylgpConditionLossOfWaterFlowcurrentThe system has detected a loss of water flow condition.
1.3.6.1.4.1.476.1.42.3.2.1.153IdentitylgpConditionCondensatePumpHighWatercurrentThe system has detected high water in the condensate pump.
1.3.6.1.4.1.476.1.42.3.2.1.154IdentitylgpConditionGeneralAlarmcurrentThe system has detected a general alarm condition.
1.3.6.1.4.1.476.1.42.3.2.1.155IdentitylgpConditionProductSpecificcurrentThe system has detected a product specific condition. This condition is not currently available via the agent card.
1.3.6.1.4.1.476.1.42.3.2.1.156IdentitylgpConditionReheatLockoutcurrentThe system has locked out the electrical reheat operation for a specified amount of time.
1.3.6.1.4.1.476.1.42.3.2.1.157IdentitylgpConditionHumidifierLockoutcurrentThe system has locked out the humidifier operation for a specified amount of time.
1.3.6.1.4.1.476.1.42.3.2.1.158IdentitylgpConditionCompressorsLockoutcurrentThe system has locked out compressor operation for a specified amount of time.
1.3.6.1.4.1.476.1.42.3.2.1.159IdentitylgpConditionCallServicecurrentThe system has detected a condition that requires a service representative be contacted.
1.3.6.1.4.1.476.1.42.3.2.1.160IdentitylgpConditionLowMemoryGroupcurrentThis group contains various low memory conditions.
1.3.6.1.4.1.476.1.42.3.2.1.160.1IdentitylgpConditionLowMemory1currentThe system has detected a low memory condition. The control board is low in memory resources.
1.3.6.1.4.1.476.1.42.3.2.1.161IdentitylgpConditionMemoryFailureGroupcurrentThis group contains various memory device failure conditions.
1.3.6.1.4.1.476.1.42.3.2.1.161.1IdentitylgpConditionMemory1FailurecurrentThe system has detected a memory 1 module failure.
1.3.6.1.4.1.476.1.42.3.2.1.161.2IdentitylgpConditionMemory2FailurecurrentThe system has detected a memory 2 module failure.
1.3.6.1.4.1.476.1.42.3.2.1.162IdentitylgpConditionUnitCodeErrorGroupcurrentThis group contains various memory device failure conditions.
1.3.6.1.4.1.476.1.42.3.2.1.162.1IdentitylgpConditionUnitCodeNotConfiguredcurrentThe system has detected the unit code is not configured. The unit code must be configured before system start-up.
1.3.6.1.4.1.476.1.42.3.2.1.162.2IdentitylgpConditionUnitCode01OutOfRangecurrentThe system has detected a unit code error. This digit of the unit code value is out of range.
1.3.6.1.4.1.476.1.42.3.2.1.162.3IdentitylgpConditionUnitCode02OutOfRangecurrentThe system has detected a unit code error. This digit of the unit code value is out of range.
1.3.6.1.4.1.476.1.42.3.2.1.162.4IdentitylgpConditionUnitCode03OutOfRangecurrentThe system has detected a unit code error. This digit of the unit code value is out of range.
1.3.6.1.4.1.476.1.42.3.2.1.162.5IdentitylgpConditionUnitCode04OutOfRangecurrentThe system has detected a unit code error. This digit of the unit code value is out of range.
1.3.6.1.4.1.476.1.42.3.2.1.162.6IdentitylgpConditionUnitCode05OutOfRangecurrentThe system has detected a unit code error. This digit of the unit code value is out of range.
1.3.6.1.4.1.476.1.42.3.2.1.162.7IdentitylgpConditionUnitCode06OutOfRangecurrentThe system has detected a unit code error. This digit of the unit code value is out of range.
1.3.6.1.4.1.476.1.42.3.2.1.162.8IdentitylgpConditionUnitCode07OutOfRangecurrentThe system has detected a unit code error. This digit of the unit code value is out of range.
1.3.6.1.4.1.476.1.42.3.2.1.162.9IdentitylgpConditionUnitCode08OutOfRangecurrentThe system has detected a unit code error. This digit of the unit code value is out of range.
1.3.6.1.4.1.476.1.42.3.2.1.162.10IdentitylgpConditionUnitCode09OutOfRangecurrentThe system has detected a unit code error. This digit of the unit code value is out of range.
1.3.6.1.4.1.476.1.42.3.2.1.162.11IdentitylgpConditionUnitCode10OutOfRangecurrentThe system has detected a unit code error. This digit of the unit code value is out of range.
1.3.6.1.4.1.476.1.42.3.2.1.162.12IdentitylgpConditionUnitCode11OutOfRangecurrentThe system has detected a unit code error. This digit of the unit code value is out of range.
1.3.6.1.4.1.476.1.42.3.2.1.162.13IdentitylgpConditionUnitCode12OutOfRangecurrentThe system has detected a unit code error. This digit of the unit code value is out of range.
1.3.6.1.4.1.476.1.42.3.2.1.162.14IdentitylgpConditionUnitCode13OutOfRangecurrentThe system has detected a unit code error. This digit of the unit code value is out of range.
1.3.6.1.4.1.476.1.42.3.2.1.162.15IdentitylgpConditionUnitCode14OutOfRangecurrentThe system has detected a unit code error. This digit of the unit code value is out of range.
1.3.6.1.4.1.476.1.42.3.2.1.162.16IdentitylgpConditionUnitCode15OutOfRangecurrentThe system has detected a unit code error. This digit of the unit code value is out of range.
1.3.6.1.4.1.476.1.42.3.2.1.162.17IdentitylgpConditionUnitCode16OutOfRangecurrentThe system has detected a unit code error. This digit of the unit code value is out of range.
1.3.6.1.4.1.476.1.42.3.2.1.162.18IdentitylgpConditionUnitCode17OutOfRangecurrentThe system has detected a unit code error. This digit of the unit code value is out of range.
1.3.6.1.4.1.476.1.42.3.2.1.162.19IdentitylgpConditionUnitCode18OutOfRangecurrentThe system has detected a unit code error. This digit of the unit code value is out of range.
1.3.6.1.4.1.476.1.42.3.2.1.163IdentitylgpConditionHighExternalDewPointcurrentThe system has detected a high external dew point condition. The room dew point has exceeded the specified threshold.
1.3.6.1.4.1.476.1.42.3.2.1.164IdentitylgpConditionHcbDisconnectedcurrentThe system has detected the humidifier control board is disconnected or not installed.
1.3.6.1.4.1.476.1.42.3.2.1.165IdentitylgpConditionBmsResetTimerExpiredcurrentThe BMS fan speed control reset counter has timed out.
1.3.6.1.4.1.476.1.42.3.2.1.166IdentitylgpConditionAgentFirmwareCorruptcurrentThe firmware update to the agent card has failed and the firmware is now corrupt.
1.3.6.1.4.1.476.1.42.3.2.1.175IdentitylgpConditionSystemAccessGroupcurrentThis group contains various system access conditions. An examples is an open access panel.
1.3.6.1.4.1.476.1.42.3.2.1.175.1IdentitylgpConditionFrontAccessOpencurrentThe system has detected the front access panel/door is open.
1.3.6.1.4.1.476.1.42.3.2.1.175.2IdentitylgpConditionRearAccessOpencurrentThe system has detected the rear access panel/door is open.
1.3.6.1.4.1.476.1.42.3.2.1.176IdentitylgpConditionsDamperFailurecurrentThis group contains various damper failure conditions.
1.3.6.1.4.1.476.1.42.3.2.1.176.1IdentitylgpConditionEmergencyDamperFailurecurrentThe system has detected an emergency damper failure. The damper is in the wrong position.
1.3.6.1.4.1.476.1.42.3.2.1.177IdentitylgpConditionRemoteShutdowncurrentA remote shutdown occurred.
1.3.6.1.4.1.476.1.42.3.2.1.178IdentitylgpConditionFireAlarmcurrentFire Alarm.
1.3.6.1.4.1.476.1.42.3.2.1.179IdentitylgpConditionHeatersOverheatedcurrentHeaters Overheated.
1.3.6.1.4.1.476.1.42.3.2.1.180IdentitylgpConditionCondenserFailureGroupcurrentThis group contains condenser failure conditions.
1.3.6.1.4.1.476.1.42.3.2.1.180.1IdentitylgpConditionCondenser1FailurecurrentCondenser 1 Failure.
1.3.6.1.4.1.476.1.42.3.2.1.180.2IdentitylgpConditionCondenser2FailurecurrentCondenser 2 Failure.
1.3.6.1.4.1.476.1.42.3.2.1.180.3IdentitylgpConditionCondenserTVSSFailurecurrentThe condenser Transient Voltage Surge Suppressor or Surge Protection Device has failed.
1.3.6.1.4.1.476.1.42.3.2.1.181IdentitylgpConditionHumidifierCyclinderWorncurrentThe system has detected the humidifier cylinder is worn.
1.3.6.1.4.1.476.1.42.3.2.1.182IdentitylgpConditionUnderCurrentcurrentThe system has detected a low current condition. The current of one or more sources in the system has fallen below a threshold for a specified amount of time. …
1.3.6.1.4.1.476.1.42.3.2.1.182.1IdentitylgpConditionHumidifierUnderCurrentcurrentThe system has detected a low current condition on the humidifier. The current of the humidifier has fallen below a pre-determined threshold for a defined amou…
1.3.6.1.4.1.476.1.42.3.2.1.182.2IdentitylgpConditionInputUnderCurrentcurrentThere is a low current condition on the input power source. The current of the input power source has fallen below a pre-determined threshold for a defined amo…
1.3.6.1.4.1.476.1.42.3.2.1.183IdentitylgpConditionHeatRejectorGroupcurrentThis group contains failure conditions for the heat rejection unit.
1.3.6.1.4.1.476.1.42.3.2.1.183.1IdentitylgpConditionHeatRejectorFanFailurecurrentThe heat rejecter fan has failed.
1.3.6.1.4.1.476.1.42.3.2.1.183.2IdentitylgpConditionHeatRejectorVoltageSuppressionFailurecurrentThe heat rejecter voltage suppression has failed and is no longer able to protect the unit from power fluctuations.
1.3.6.1.4.1.476.1.42.3.2.1.184IdentitylgpConditionFreeCoolLockoutcurrentThe free cooling capability has been disabled.
1.3.6.1.4.1.476.1.42.3.2.1.185IdentitylgpConditionWaterLeakSensorFailurecurrentThe sensor used to detect water leaks is not connected or has failed.
1.3.6.1.4.1.476.1.42.3.2.1.186IdentitylgpConditionNoLoadDetectedWarningcurrentThere is no load detected on the output. This can be an indication that the output is being powered by an external bypass source and has inadvertently been lef…
1.3.6.1.4.1.476.1.42.3.2.1.187IdentitylgpConditionFirmwareGroupcurrentGrouping level for firmware related conditions.
1.3.6.1.4.1.476.1.42.3.2.1.187.3IdentitylgpConditionFirmwareUpdateRequiredcurrentThe firmware on the system or one or more components of the system must be updated. This typically indicates that one or more components of the system contain …
1.3.6.1.4.1.476.1.42.3.2.1.188IdentitylgpConditionTestGroupcurrentObjects in this group of conditions are related to testing or test events. This object is never active.
1.3.6.1.4.1.476.1.42.3.2.1.188.5IdentitylgpConditionTest01currentThis is a 'test' condition. It is a generic test event that can be utilized to evaluate system handling of events. Some products will support the activation of…
1.3.6.1.4.1.476.1.42.3.2.1.190IdentitylgpConditionReceptacleBranchGroupcurrentGrouping level for receptacle branch conditions.
1.3.6.1.4.1.476.1.42.3.2.1.190.5IdentitylgpConditionRcpBranchFailurecurrentThe receptacle branch module or control system has failed. Service is required.
1.3.6.1.4.1.476.1.42.3.2.1.190.10IdentitylgpConditionRcpBranchBreakerOpencurrentThe receptacle branch breaker is open.
1.3.6.1.4.1.476.1.42.3.2.1.192IdentitylgpConditionInputUnqualifiedcurrentThe input is not qualified to provide power to the system. This may be due to system input over-voltage, system input under-voltage, system input frequency out…
1.3.6.1.4.1.476.1.42.3.2.1.193IdentitylgpConditionBypassUnavailablecurrentThis summary event is asserted when the bypass is not available. Possible causes include: Bypass Sync Error, Bypass Line Fail, Bypass Overvoltage, Bypass Under…
1.3.6.1.4.1.476.1.42.3.2.1.194IdentitylgpConditionAutoTransferFailedcurrentThe system is failing to automatically transfer the load to the alternate source.
1.3.6.1.4.1.476.1.42.3.2.1.195IdentitylgpConditionSBSUnavailablecurrentA Static Bypass Switch (SBS) Failure has been detected. Possible causes include: SBS Phase Open, SBS SCR (Silicon Controlled Rectifier) Shorted, SBS Overload E…
1.3.6.1.4.1.476.1.42.3.2.1.196IdentitylgpConditionSBSOverloadcurrentOn at least one phase of the static bypass switch (SBS), the power dissipation limit has been exceeded.
1.3.6.1.4.1.476.1.42.3.2.1.197IdentitylgpConditionExcessPulseParallelcurrentThe system has performed too many pulse parallel operations within the specified time interval. A pulse parallel operation is a momentary operation of the stat…
1.3.6.1.4.1.476.1.42.3.2.1.198IdentitylgpConditionRemoteBypassSwitchOffExtcurrentThe static bypass switch is off due to the state of an external signal.
1.3.6.1.4.1.476.1.42.3.2.1.199IdentitylgpConditionManTransferInhibitedcurrentManual transfer from inverter to bypass is inhibited. Bypass is not qualified.
1.3.6.1.4.1.476.1.42.3.2.1.200IdentitylgpConditionManReTransferInhibitedcurrentManual retransfer from bypass to inverter is inhibited.
1.3.6.1.4.1.476.1.42.3.2.1.201IdentitylgpConditionBatteryChargeErrorcurrentThe battery is not charging properly. Some reasons for this condition include, but are not limited to: battery charger failure, battery failure, etc.
1.3.6.1.4.1.476.1.42.3.2.1.202IdentitylgpConditionBatteryAutoTestInhibitedcurrentAutomatic (scheduled) battery tests are inhibited.
1.3.6.1.4.1.476.1.42.3.2.1.203IdentitylgpConditionBatteryChargeReducedExtcurrentA reduced battery charging algorithm is being used due to an external signal.
1.3.6.1.4.1.476.1.42.3.2.1.204IdentitylgpConditionBatteryCapacityLowcurrentThe battery capacity is low. Some reasons for this condition include, but are not limited to: a battery is offline, the battery age has reduced its capabilitie…
1.3.6.1.4.1.476.1.42.3.2.1.205IdentitylgpConditionBatteryTempImbalancecurrentThe temperature difference between two batteries in the system exceeds the predefined threshold.
1.3.6.1.4.1.476.1.42.3.2.1.206IdentitylgpConditionBatteryEqualizecurrentThe rectifier output voltage has been increased to equalize the battery voltage level.
1.3.6.1.4.1.476.1.42.3.2.1.207IdentitylgpConditionBatteryChargeInhibitedExtcurrentBattery charging is inhibited due to an external inhibit signal.
1.3.6.1.4.1.476.1.42.3.2.1.208IdentitylgpConditionServiceExtBatteryMonitorGroupcurrentThis group contains battery monitor service conditions.
1.3.6.1.4.1.476.1.42.3.2.1.208.1IdentitylgpConditionServiceExtBatteryMonitor1currentExternal battery monitor 1 indicates battery maintenance is required.
1.3.6.1.4.1.476.1.42.3.2.1.208.2IdentitylgpConditionServiceExtBatteryMonitor2currentExternal battery monitor 2 indicates battery maintenance is required.
1.3.6.1.4.1.476.1.42.3.2.1.209IdentitylgpConditionBatteryGroundFaultcurrentBattery system ground fault amperage exceeds the threshold.
1.3.6.1.4.1.476.1.42.3.2.1.210IdentitylgpConditionBatteryLowShutdowncurrentWith the battery breaker closed, the battery voltage has dropped below the calculated End-Of-Discharge (EOD) limit.
1.3.6.1.4.1.476.1.42.3.2.1.211IdentitylgpConditionEmergencyPowerOffLocalcurrentThe system has detected an Emergency Power Off (EPO) condition. The local EPO switch has cut off the power source to the system.
1.3.6.1.4.1.476.1.42.3.2.1.212IdentitylgpConditionOutputLowPFLaggingcurrentThe system has detected a lagging output power factor below the threshold, resulting in reduced load capacity.
1.3.6.1.4.1.476.1.42.3.2.1.213IdentitylgpConditionOutputLowPFLeadingcurrentThe system has detected a leading output power factor below the threshold, resulting in reduced load capacity.
1.3.6.1.4.1.476.1.42.3.2.1.214IdentitylgpConditionOutputToLoadFaultcurrentThe system has detected an output to load fault. This could be caused by over or under voltage, or by over or under frequency.
1.3.6.1.4.1.476.1.42.3.2.1.215IdentitylgpConditionInvRestartInhibitedExtcurrentRestart of the inverter is inhibited by an external signal.
1.3.6.1.4.1.476.1.42.3.2.1.216IdentitylgpConditionInverterShutdownOverloadcurrentThe system has shutdown the inverter due to a sustained overload. This event does not indicate if the load has been dropped or transferred to bypass. At least …
1.3.6.1.4.1.476.1.42.3.2.1.217IdentitylgpConditionInverterOffExtcurrentThe inverter is off due to the state of an external signal.
1.3.6.1.4.1.476.1.42.3.2.1.218IdentitylgpConditionInputContactGroupcurrentThe system has detected an active input contact.
1.3.6.1.4.1.476.1.42.3.2.1.218.1IdentitylgpConditionInputContact01currentThe system has detected that input contact 1 is active.
1.3.6.1.4.1.476.1.42.3.2.1.218.2IdentitylgpConditionInputContact02currentThe system has detected that input contact 2 is active.
1.3.6.1.4.1.476.1.42.3.2.1.218.3IdentitylgpConditionInputContact03currentThe system has detected that input contact 3 is active.
1.3.6.1.4.1.476.1.42.3.2.1.218.4IdentitylgpConditionInputContact04currentThe system has detected that input contact 4 is active.
1.3.6.1.4.1.476.1.42.3.2.1.218.5IdentitylgpConditionInputContact05currentThe system has detected that input contact 5 is active.
1.3.6.1.4.1.476.1.42.3.2.1.218.6IdentitylgpConditionInputContact06currentThe system has detected that input contact 6 is active.
1.3.6.1.4.1.476.1.42.3.2.1.218.7IdentitylgpConditionInputContact07currentThe system has detected that input contact 7 is active.
1.3.6.1.4.1.476.1.42.3.2.1.218.8IdentitylgpConditionInputContact08currentThe system has detected that input contact 8 is active.
1.3.6.1.4.1.476.1.42.3.2.1.218.9IdentitylgpConditionInputContact09currentThe system has detected that input contact 9 is active.
1.3.6.1.4.1.476.1.42.3.2.1.218.10IdentitylgpConditionInputContact10currentThe system has detected that input contact 10 is active.
1.3.6.1.4.1.476.1.42.3.2.1.218.11IdentitylgpConditionInputContact11currentThe system has detected that input contact 11 is active.
1.3.6.1.4.1.476.1.42.3.2.1.218.12IdentitylgpConditionInputContact12currentThe system has detected that input contact 12 is active.
1.3.6.1.4.1.476.1.42.3.2.1.218.13IdentitylgpConditionInputContact13currentThe system has detected that input contact 13 is active.
1.3.6.1.4.1.476.1.42.3.2.1.218.14IdentitylgpConditionInputContact14currentThe system has detected that input contact 14 is active.
1.3.6.1.4.1.476.1.42.3.2.1.218.15IdentitylgpConditionInputContact15currentThe system has detected that input contact 15 is active.
1.3.6.1.4.1.476.1.42.3.2.1.218.16IdentitylgpConditionInputContact16currentThe system has detected that input contact 16 is active.
1.3.6.1.4.1.476.1.42.3.2.1.219IdentitylgpConditionRectifierOperInhibitedcurrentThe operation of the rectifier is inhibited by an external signal.
1.3.6.1.4.1.476.1.42.3.2.1.220IdentitylgpConditionBypassBackFeedBrkrOpencurrentThe bypass backfeed breaker is in the open position.
1.3.6.1.4.1.476.1.42.3.2.1.221IdentitylgpConditionAutoRestartInProgresscurrentAuto restart is in progress. Becomes inactive when auto restart completes or fails.
1.3.6.1.4.1.476.1.42.3.2.1.222IdentitylgpConditionAutoRestartInhibitedExtcurrentAuto restart is inhibited due to an external signal.
1.3.6.1.4.1.476.1.42.3.2.1.223IdentitylgpConditionAutoRestartFailedcurrentAuto restart has failed.
1.3.6.1.4.1.476.1.42.3.2.1.224IdentitylgpConditionInputOnGeneratorcurrentA generator is supplying the power to the system.
1.3.6.1.4.1.476.1.42.3.2.1.225IdentitylgpConditionInputFilterCycleLockcurrentThe input filter disconnect has opened too many times within a given period of time.
1.3.6.1.4.1.476.1.42.3.2.1.226IdentitylgpConditionServiceCodeActivecurrentThe system is in an operational mode intended for testing. In normal operating conditions, the system should not be in this state.
1.3.6.1.4.1.476.1.42.3.2.1.227IdentitylgpConditionLoadBusSyncActivecurrentLoad Bus Sync Operation is active. This synchronizes the UPS output with the output of another UPS.
1.3.6.1.4.1.476.1.42.3.2.1.228IdentitylgpConditionLoadBusSyncInhibitedcurrentThe system has detected that conditions to perform Load Bus Sync Operation are not satisfied.
1.3.6.1.4.1.476.1.42.3.2.1.229IdentitylgpConditionControlsResetRequiredcurrentA controls reset is required because one or more critical settings have changed.
1.3.6.1.4.1.476.1.42.3.2.1.230IdentitylgpConditionEquipTempSensorFailedcurrentA temperature sensor is reporting a value outside the bounds of a properly operating sensor.
1.3.6.1.4.1.476.1.42.3.2.1.231IdentitylgpConditionInputCurrentImbalancecurrentThe current on one input phase is much greater or lower than the average current of all the phases. This may indicate improper operation of the rectifier or in…
1.3.6.1.4.1.476.1.42.3.2.1.232IdentitylgpConditionPumpGroupcurrentThe system has detected an alarm with one of the pumps.
1.3.6.1.4.1.476.1.42.3.2.1.232.1IdentitylgpConditionPumpFlowLosscurrentThe system has detected a loss of flow with one or more pumps.
1.3.6.1.4.1.476.1.42.3.2.1.232.1.1IdentitylgpConditionPump1FlowLosscurrentThe system has detected a loss of flow with pump 1.
1.3.6.1.4.1.476.1.42.3.2.1.232.1.2IdentitylgpConditionPump2FlowLosscurrentThe system has detected a loss of flow with pump 2.
1.3.6.1.4.1.476.1.42.3.2.1.232.2IdentitylgpConditionPumpShortCyclecurrentThe system has detected a short cycling of the pumps. One or more of the pumps has been turned on and off a number of times within a specified time period.
1.3.6.1.4.1.476.1.42.3.2.1.232.3IdentitylgpConditionPumpInverterShortCyclecurrentThe system has detected a short cycling of one or more pump inverters and has temporarily locked out further pump operation to protect from thermal overload. A…
1.3.6.1.4.1.476.1.42.3.2.1.232.3.1IdentitylgpConditionPump1InverterShortCyclecurrentThe system has detected a short cycling of the inverter for pump 1 and has temporarily locked out further pump operation to protect from thermal overload. A sh…
1.3.6.1.4.1.476.1.42.3.2.1.232.3.2IdentitylgpConditionPump2InverterShortCyclecurrentThe system has detected a short cycling of the inverter for pump 2 and has temporarily locked out further pump operation to protect from thermal overload. A sh…
1.3.6.1.4.1.476.1.42.3.2.1.233IdentitylgpConditionValveGroupcurrentThe system has detected an alarm with one of the valves.
1.3.6.1.4.1.476.1.42.3.2.1.233.1IdentitylgpConditionChilledWaterValvePositioncurrentThe system has detected a problem with the chilled water valve position. The position of the chilled water control valve does not match an expected value.
1.3.6.1.4.1.476.1.42.3.2.1.234IdentitylgpConditionCondensationDetectedcurrentThe system has detected condensation.
1.3.6.1.4.1.476.1.42.3.2.1.235IdentitylgpConditionMaintenanceGroupcurrentThe system has detected a maintenance condition. This group contains various maintenance conditions.
1.3.6.1.4.1.476.1.42.3.2.1.235.1IdentitylgpConditionMaintenanceDuecurrentSystem is due for maintenance.
1.3.6.1.4.1.476.1.42.3.2.1.235.2IdentitylgpConditionMaintenanceCompletecurrentThe system maintenance has been completed.
1.3.6.1.4.1.476.1.42.3.2.1.236IdentitylgpConditionExternalEventSignalGroupcurrentThis group contains various conditions signalled by external inputs. Each event is deactivated when the signal is inactive.
1.3.6.1.4.1.476.1.42.3.2.1.236.1IdentitylgpConditionExternalFireDetectcurrentFire detected, as indicated by an external input signal.
1.3.6.1.4.1.476.1.42.3.2.1.236.2IdentitylgpConditionExternalFlowLosscurrentLoss of flow is detected, as indicated by an external input signal.
1.3.6.1.4.1.476.1.42.3.2.1.236.3IdentitylgpConditionExternalReheatLockoutcurrentThe reheater is shut down and disabled by an external input signal.
1.3.6.1.4.1.476.1.42.3.2.1.236.4IdentitylgpConditionExternalOverTempcurrentA temperature has exceeded its threshold, as indicated by an external input signal.
1.3.6.1.4.1.476.1.42.3.2.1.236.5IdentitylgpConditionExternalCompLockoutcurrentThe compressor is shut down and disabled by an external input signal.
1.3.6.1.4.1.476.1.42.3.2.1.236.6IdentitylgpConditionExternalHumidifierLockoutcurrentThe humidifier is shut down and disabled by an external input signal.
1.3.6.1.4.1.476.1.42.3.2.1.237IdentitylgpConditionComponentShutdownGroupcurrentThis group contains conditions signaling shutdown of various system components.
1.3.6.1.4.1.476.1.42.3.2.1.237.1IdentitylgpConditionComponentShutdownPartialcurrentAn event has occurred requiring some system components to be shutdown and disabled.
1.3.6.1.4.1.476.1.42.3.2.1.237.2IdentitylgpConditionComponentShutdownHighPowercurrentSupply to high power components has been shutdown.
1.3.6.1.4.1.476.1.42.3.2.1.238IdentitylgpConditionCondenserProblemGroupcurrentThis group contains condenser conditions.
1.3.6.1.4.1.476.1.42.3.2.1.238.1IdentitylgpConditionCondenser1ProblemcurrentCondenser 1 is not operating within its normal parameters.
1.3.6.1.4.1.476.1.42.3.2.1.239IdentitylgpConditionHumidityOutOfPropBandcurrentThe system has detected a humidity reading that remained outside of the proportional control band for an extended period of time.
1.3.6.1.4.1.476.1.42.3.2.1.240IdentitylgpConditionEnvRemoteSensorGroupcurrentThis group contains remote sensors.
1.3.6.1.4.1.476.1.42.3.2.1.240.1IdentitylgpConditionEnvRemoteSensor1IssuecurrentRemote sensor is disconnected or the signal is out of range. The event is deactivated when sensor signal is re-established.
1.3.6.1.4.1.476.1.42.3.2.1.240.2IdentitylgpConditionEnvRemoteSensor2IssuecurrentRemote sensor is disconnected or the signal is out of range. The event is deactivated when sensor signal is re-established.
1.3.6.1.4.1.476.1.42.3.2.1.240.3IdentitylgpConditionEnvRemoteSensor3IssuecurrentRemote sensor is disconnected or the signal is out of range. The event is deactivated when sensor signal is re-established.
1.3.6.1.4.1.476.1.42.3.2.1.240.4IdentitylgpConditionEnvRemoteSensor4IssuecurrentRemote sensor is disconnected or the signal is out of range. The event is deactivated when sensor signal is re-established.
1.3.6.1.4.1.476.1.42.3.2.1.240.5IdentitylgpConditionEnvRemoteSensor5IssuecurrentRemote sensor is disconnected or the signal is out of range. The event is deactivated when sensor signal is re-established.
1.3.6.1.4.1.476.1.42.3.2.1.240.6IdentitylgpConditionEnvRemoteSensor6IssuecurrentRemote sensor is disconnected or the signal is out of range. The event is deactivated when sensor signal is re-established.
1.3.6.1.4.1.476.1.42.3.2.1.240.7IdentitylgpConditionEnvRemoteSensor7IssuecurrentRemote sensor is disconnected or the signal is out of range. The event is deactivated when sensor signal is re-established.
1.3.6.1.4.1.476.1.42.3.2.1.240.8IdentitylgpConditionEnvRemoteSensor8IssuecurrentRemote sensor is disconnected or the signal is out of range. The event is deactivated when sensor signal is re-established.
1.3.6.1.4.1.476.1.42.3.2.1.240.9IdentitylgpConditionEnvRemoteSensor9IssuecurrentRemote sensor is disconnected or the signal is out of range. The event is deactivated when sensor signal is re-established.
1.3.6.1.4.1.476.1.42.3.2.1.240.10IdentitylgpConditionEnvRemoteSensor10IssuecurrentRemote sensor is disconnected or the signal is out of range. The event is deactivated when sensor signal is re-established.
1.3.6.1.4.1.476.1.42.3.2.1.241IdentitylgpConditionNeutralSnubberBoardCommFailurecurrentThe Neutral Snubber board has stopped communicating.
1.3.6.1.4.1.476.1.42.3.2.1.242IdentitylgpConditionRedundantChargerFailurecurrentThe redundant charger has failed.
1.3.6.1.4.1.476.1.42.3.2.1.243IdentitylgpConditionBoardInputContactorPowerFailurecurrentBoard input contactor power failure.
1.3.6.1.4.1.476.1.42.3.2.1.243.1IdentitylgpConditionBoard1InputContactorPowerFailurecurrentBoard1 input contactor power failure.
1.3.6.1.4.1.476.1.42.3.2.1.243.2IdentitylgpConditionBoard2InputContactorPowerFailurecurrentBoard2 input contactor power failure.
1.3.6.1.4.1.476.1.42.3.2.1.5423IdentitylgpConditionTooManySensorscurrentThe number of sensors installed on the device has exceeded the pre-determined limit.
1.3.6.1.4.1.476.1.42.3.2.1.5471IdentitylgpConditionDoorSwitchOpencurrentAn open door has been detected.
1.3.6.1.4.1.476.1.42.3.2.1.5479IdentitylgpConditionContactClosureOpencurrentAn open circuit has been detected.
1.3.6.1.4.1.476.1.42.3.2.1.5480IdentitylgpConditionContactClosureClosedcurrentA closed circuit has been detected.
1.3.6.1.4.1.476.1.42.3.2.1.6119IdentitylgpConditionSensorsNotDisplayedcurrentThe number of sensors that can be displayed (monitored) on the device has exceeded the pre-determined limit. Note this condition differs from the lgpConditionT…
1.3.6.1.4.1.476.1.42.3.2.2ScalarlgpConditionsPresentread-onlycurrentThe present number of conditions (rows) in the lgpConditionsTable.
1.3.6.1.4.1.476.1.42.3.2.3TablelgpConditionsTablenot-accessiblecurrentA list of condition table entries. The table contains zero, one, or many rows at any moment, depending upon the number of conditions in effect. The number of r…
1.3.6.1.4.1.476.1.42.3.2.3.1RowlgpConditionEntrynot-accessiblecurrentThis entry defines the contents of the rows for the table 'lgpConditionsTable'. A row in this table cannot be created or deleted by SNMP operations on columns …
1.3.6.1.4.1.476.1.42.3.2.3.1.1ColumnlgpConditionIdread-onlycurrentA unique identifier for a condition. This value must remain constant between agent initializations. This OID is used as an index to identify a row in the table…
1.3.6.1.4.1.476.1.42.3.2.3.1.2ColumnlgpConditionDescrread-onlycurrentA reference to a condition description object. The object referenced should not be accessible, but rather be used to provide a unique description.
1.3.6.1.4.1.476.1.42.3.2.3.1.3ColumnlgpConditionTimeread-onlycurrentThe value of sysUpTime when the condition occurred (became active).
1.3.6.1.4.1.476.1.42.3.2.3.1.5ColumnlgpConditionTableRefread-onlycurrentThis object will be included as a varbind in some rows of the table. It is a reference to a table object in the MIB. The value of this object will be the OID o…
1.3.6.1.4.1.476.1.42.3.2.3.1.6ColumnlgpConditionTableRowRefread-onlycurrentThis is a reference to the (cell) in the table specified by the companion varbind (lgpConditionTableRef) in this condition. The row in the table where this cel…
1.3.6.1.4.1.476.1.42.3.2.3.1.10ColumnlgpConditionTyperead-onlycurrentThe type of condition in this row in the table.
1.3.6.1.4.1.476.1.42.3.2.3.1.12ColumnlgpConditionCurrentStateread-onlycurrentIndication of the current state of the event. If the state is 'active' then the condition currently exists. If the state is 'inactive' then the condition no lo…
1.3.6.1.4.1.476.1.42.3.2.3.1.14ColumnlgpConditionSeverityread-onlycurrentThis represents the relative severity of the condition.
1.3.6.1.4.1.476.1.42.3.2.3.1.18ColumnlgpConditionAcknowledgedread-writecurrentThis indicates if the condition has been acknowledged. If the value is 'notAcknowledged' then the condition has not been acknowledged. If the value is 'acknowl…
1.3.6.1.4.1.476.1.42.3.2.3.1.19ColumnlgpConditionAckReqread-onlycurrentThis indicates if the corresponding condition does or does not require user acknowledgement. Conditions that require user acknowledgement will have a value of …
1.3.6.1.4.1.476.1.42.3.2.4NodelgpConditionControl
1.3.6.1.4.1.476.1.42.3.2.4.1ScalarlgpConditionControlEventResetread-writecurrentEvent Reset Command. This command will reset all of the device's events. On some units, when an event is activated, a 'set' field is also marked and maintained…
1.3.6.1.4.1.476.1.42.3.2.4.2ScalarlgpConditionControlEventAckread-writecurrentEvent Acknowledge Command. This command will acknowledge all of the device's events.
1.3.6.1.4.1.476.1.42.3.2.4.20TablelgpConditionControlTablenot-accessiblecurrentA list of condition control table entries. The table contains zero, one, or many rows at any moment, depending upon the number of conditions that are controlla…
1.3.6.1.4.1.476.1.42.3.2.4.20.1RowlgpConditionControlEntrynot-accessiblecurrentThis entry defines the contents of the rows for the table 'lgpConditionControlTable'. A row in this table cannot be created or deleted by user initiated SNMP o…
1.3.6.1.4.1.476.1.42.3.2.4.20.1.1ColumnlgpConditionControlIndexnot-accessiblecurrentThis is the index indicating the nth element of the table.
1.3.6.1.4.1.476.1.42.3.2.4.20.1.2ColumnlgpConditionControlDescrread-onlycurrentA reference to an Object Identifier (OID) representing a unique condition. The referenced OID is used solely for identification purposes. The object identifier…
1.3.6.1.4.1.476.1.42.3.2.4.20.1.3ColumnlgpConditionControlEnableStatusread-writecurrentThe value in this column determines if the device is currently capable of generating this event. If the value is 'enabled' then the event will be generated if …
1.3.6.1.4.1.476.1.42.3.2.4.20.1.4ColumnlgpConditionControlTyperead-writecurrentThe 'type' assigned or configured for this condition. The value assigned to the condition here is displayed in the lgpConditionsTable (column: lgpConditionType…
1.3.6.1.4.1.476.1.42.3.2.4.20.1.5ColumnlgpConditionControlEnableCapabilityread-onlycurrentSome devices do not allow write access to some entries in the 'lgpConditionControlEnableStatus' column. This column indicates whether the 'lgpConditionControlE…
1.3.6.1.4.1.476.1.42.3.2.5ScalarlgpConditionDescriptionread-onlycurrentThe ASCII text description for the condition.
1.3.6.1.4.1.476.1.42.3.2.6ScalarlgpNetworkNameread-onlycurrentThe network name in a node.domain.com like format. This object is intended to be used as a varbind object by other notifications that have a context of a netwo…
1.3.6.1.4.1.476.1.42.3.2.7NodelgpFlexConditions