LIEBERT-GP-ENVIRONMENTAL-MIB

295 objects
The MIB module used to register Liebert SNMP OIDs. Copyright 2000-2015 Liebert Corporation. All rights reserved. Reproduction of this document is authorized on the condition that the forgoing copyright notice is included. This Specification is supplied 'AS IS' and Liebert Corporation makes no warranty, either express or implied, as to the use, operation, condition, or performance of the Specification.
OIDNameAccessStatusDescription
1.3.6.1.4.1.476.1.42.1.5.1IdentityliebertGlobalProductsEnvironmentalModuleThe MIB module used to register Liebert SNMP OIDs. Copyright 2000-2015 Liebert Corporation. All rights reserved. Reproduction of this document is authorized on…
1.3.6.1.4.1.476.1.42.3.4.1IdentitylgpEnvTemperaturecurrentThis sub-tree is used to register Liebert temperature object identifiers.
1.3.6.1.4.1.476.1.42.3.4.1.1IdentitylgpEnvTemperatureWellKnowncurrentLiebert well known temperature objects are identified by OIDs that reside in this sub-tree.
1.3.6.1.4.1.476.1.42.3.4.1.1.1IdentitylgpEnvControlTemperaturecurrentTemperature measurement used as control feedback.
1.3.6.1.4.1.476.1.42.3.4.1.1.2IdentitylgpEnvReturnAirTemperaturecurrentTemperature measurement of return air.
1.3.6.1.4.1.476.1.42.3.4.1.1.3IdentitylgpEnvSupplyAirTemperaturecurrentTemperature measurement of supply air.
1.3.6.1.4.1.476.1.42.3.4.1.1.4IdentitylgpAmbientTemperaturecurrentAmbient temperature measurement.
1.3.6.1.4.1.476.1.42.3.4.1.1.5IdentitylgpInverterTemperaturecurrentTemperature measurement of the inverter.
1.3.6.1.4.1.476.1.42.3.4.1.1.6IdentitylgpBatteryTempteraturecurrentTemperature measurement of the battery.
1.3.6.1.4.1.476.1.42.3.4.1.1.7IdentitylgpAcDcConverterTemperaturecurrentTemperature measurement of the AC-to-DC Converter.
1.3.6.1.4.1.476.1.42.3.4.1.1.8IdentitylgpPfcTemperaturecurrentTemperature measurement of the power factor correction circuitry.
1.3.6.1.4.1.476.1.42.3.4.1.1.9IdentitylgpTransformerTemperaturecurrentTemperature measurement of the transformer.
1.3.6.1.4.1.476.1.42.3.4.1.1.10IdentitylgpLocalTemperaturecurrentTemperature measurement of local temperature sensor.
1.3.6.1.4.1.476.1.42.3.4.1.1.10.1IdentitylgpLocal1TemperaturecurrentTemperature and humidity measurements of Local Sensor 1.
1.3.6.1.4.1.476.1.42.3.4.1.1.10.2IdentitylgpLocal2TemperaturecurrentTemperature and humidity measurements of Local Sensor 2.
1.3.6.1.4.1.476.1.42.3.4.1.1.10.3IdentitylgpLocal3TemperaturecurrentTemperature and humidity measurements of Local Sensor 3.
1.3.6.1.4.1.476.1.42.3.4.1.1.11IdentitylgpDigitalScrollCompressorTemperaturecurrentTemperature and humidity measurements of a digital Scroll Compressor.
1.3.6.1.4.1.476.1.42.3.4.1.1.11.1IdentitylgpDigitalScrollCompressor1TemperaturecurrentTemperature and humidity measurements of a digital Scroll Compressor 1.
1.3.6.1.4.1.476.1.42.3.4.1.1.11.2IdentitylgpDigitalScrollCompressor2TemperaturecurrentTemperature and humidity measurements of a digital Scroll Compressor 2.
1.3.6.1.4.1.476.1.42.3.4.1.1.12IdentitylgpChillWaterTemperaturecurrentTemperature measurements of a chill water system.
1.3.6.1.4.1.476.1.42.3.4.1.1.13IdentitylgpCoolantTemperaturecurrentTemperature measurements of an environmental system's coolant.
1.3.6.1.4.1.476.1.42.3.4.1.1.14IdentitylgpEnvEnclosureTemperatureSensorscurrentEnclosure temperature sensors
1.3.6.1.4.1.476.1.42.3.4.1.1.14.1IdentitylgpEnvEnclosureTemperatureSensor1currentEnclosure temperature sensor 1
1.3.6.1.4.1.476.1.42.3.4.1.1.14.2IdentitylgpEnvEnclosureTemperatureSensor2currentEnclosure temperature sensor 2
1.3.6.1.4.1.476.1.42.3.4.1.1.14.3IdentitylgpEnvEnclosureTemperatureSensor3currentEnclosure temperature sensor 3
1.3.6.1.4.1.476.1.42.3.4.1.1.14.4IdentitylgpEnvEnclosureTemperatureSensor4currentEnclosure temperature sensor 4
1.3.6.1.4.1.476.1.42.3.4.1.1.15IdentitylgpEnvValueAmbientRoomTemperaturecurrentTemperature outside enclosure.
1.3.6.1.4.1.476.1.42.3.4.1.1.16IdentitylgpEnvDewPointTemperaturecurrentThe calculated temperature outside of the enclosure at which condensation is likely to occur.
1.3.6.1.4.1.476.1.42.3.4.1.1.17IdentitylgpEnvEnclosureTemperaturecurrentTemperature inside of enclosure.
1.3.6.1.4.1.476.1.42.3.4.1.1.18IdentitylgpEnvAdjustedTemperaturecurrentThe current temperature set-point which is computed by the system and may be temporarily different from the user set-point because of external factors.
1.3.6.1.4.1.476.1.42.3.4.1.1.19IdentitylgpEnvExternalSensorscurrentExternal sensors to monitor environmental variables such as temperature and humidity
1.3.6.1.4.1.476.1.42.3.4.1.1.19.1IdentitylgpEnvExternalAirSensorAcurrentTemperature and humidity measurements from external air sensor A.
1.3.6.1.4.1.476.1.42.3.4.1.1.19.2IdentitylgpEnvExternalAirSensorADewPointcurrentDewpoint temperature for External Air Sensor A.
1.3.6.1.4.1.476.1.42.3.4.1.1.19.3IdentitylgpEnvExternalAirSensorBcurrentTemperature and humidity measurements from external air sensor B.
1.3.6.1.4.1.476.1.42.3.4.1.1.19.4IdentitylgpEnvExternalAirSensorBDewPointcurrentDewpoint temperature for External Air Sensor B.
1.3.6.1.4.1.476.1.42.3.4.1.1.20IdentitylgpEnvSupplyFluidTemperaturecurrentThe current temperature of the fluid being supplied.
1.3.6.1.4.1.476.1.42.3.4.1.1.21IdentitylgpEnvSupplyRefrigerantTemperaturecurrentThe current temperature of the refrigerant being supplied.
1.3.6.1.4.1.476.1.42.3.4.1.1.22IdentitylgpEnvMinDesiredRoomAirTemperaturecurrentThe minimum desired room air temperature. If the room air temperature falls below this set point, the unit will reduce the cooling.
1.3.6.1.4.1.476.1.42.3.4.1.1.23IdentitylgpEnvDewPointTemperaturescurrentThis sub-tree identifies well-known dew point temperatures in the system.
1.3.6.1.4.1.476.1.42.3.4.1.1.23.1IdentitylgpEnvInletDewPointTemperaturecurrentDew point temperature measured at the inlet of the unit.
1.3.6.1.4.1.476.1.42.3.4.1.2IdentitylgpEnvTemperatureFahrenheitcurrentThis sub-tree contains OIDs that are used to control and monitor temperature using the Fahrenheit temperature scale.
1.3.6.1.4.1.476.1.42.3.4.1.2.1ScalarlgpEnvTemperatureSettingDegFread-writecurrentThe temperature setting used to control the well known temperature object 'lgpEnvControlTemperature'. This setting is cloned in 'lgpEnvTemperatureSettingDegC' …
1.3.6.1.4.1.476.1.42.3.4.1.2.2ScalarlgpEnvTemperatureToleranceDegFread-writecurrentThe acceptable variance from 'lgpEnvTemperatureSettingDegF', without initiating a control action. This setting is cloned in 'lgpEnvTemperatureToleranceDegC' wi…
1.3.6.1.4.1.476.1.42.3.4.1.2.3TablelgpEnvTemperatureTableDegFnot-accessiblecurrentA list of temperature table entries. The table contains zero, one, or many rows, depending upon the number of temperature objects available. The NMS cannot cre…
1.3.6.1.4.1.476.1.42.3.4.1.2.3.1RowlgpEnvTemperatureEntryDegFnot-accessiblecurrentThis entry defines the contents of the rows for the table 'lgpEnvTemperatureTableDegF'.
1.3.6.1.4.1.476.1.42.3.4.1.2.3.1.1ColumnlgpEnvTemperatureIdDegFread-onlycurrentThis OID is used as an index to identify a row in the table 'lgpEnvTemperatureTableDegF'.
1.3.6.1.4.1.476.1.42.3.4.1.2.3.1.2ColumnlgpEnvTemperatureDescrDegFread-onlycurrentA reference to a temperature description object. The object referenced should not be accessible, but rather be used to provide a unique description of the temp…
1.3.6.1.4.1.476.1.42.3.4.1.2.3.1.3ColumnlgpEnvTemperatureMeasurementDegFread-onlycurrentThe measured temperature value.
1.3.6.1.4.1.476.1.42.3.4.1.2.3.1.4ColumnlgpEnvTemperatureHighThresholdDegFread-writecurrentThe high temperature notification threshold. This is the maximum value of 'lgpEnvTemperatureMeasurementDegF' before the agent sends a notification.
1.3.6.1.4.1.476.1.42.3.4.1.2.3.1.5ColumnlgpEnvTemperatureLowThresholdDegFread-writecurrentThe low temperature notification threshold. This is the minimum value of 'lgpEnvTemperatureMeasurementDegF' before the agent sends a notification.
1.3.6.1.4.1.476.1.42.3.4.1.2.3.1.6ColumnlgpEnvTemperatureSetPointDegFread-writecurrentThe temperature setting for the well known 'lgpEnvTemperatureDescrDegF' point. This setting may or may not be the setting used from control. Some systems have …
1.3.6.1.4.1.476.1.42.3.4.1.2.3.1.7ColumnlgpEnvTemperatureDailyHighDegFread-onlycurrentThe daily high temperature measurement.
1.3.6.1.4.1.476.1.42.3.4.1.2.3.1.8ColumnlgpEnvTemperatureDailyLowDegFread-onlycurrentThe daily low temperature measurement.
1.3.6.1.4.1.476.1.42.3.4.1.2.3.1.9ColumnlgpEnvTempDailyHighTimeHourDegFread-onlycurrentThe hours digit of the time corresponding to the daily high temperature measurement.
1.3.6.1.4.1.476.1.42.3.4.1.2.3.1.10ColumnlgpEnvTempDailyHighTimeMinuteDegFread-onlycurrentThe minutes digit of the time corresponding to the daily high temperature measurement.
1.3.6.1.4.1.476.1.42.3.4.1.2.3.1.11ColumnlgpEnvTempDailyHighTimeSecondDegFread-onlycurrentThe seconds digit of the time corresponding to the daily high temperature measurement.
1.3.6.1.4.1.476.1.42.3.4.1.2.3.1.12ColumnlgpEnvTempDailyLowTimeHourDegFread-onlycurrentThe hours digit of the time corresponding to the daily low temperature measurement.
1.3.6.1.4.1.476.1.42.3.4.1.2.3.1.13ColumnlgpEnvTempDailyLowTimeMinuteDegFread-onlycurrentThe minutes digit of the time corresponding to the daily low temperature measurement.
1.3.6.1.4.1.476.1.42.3.4.1.2.3.1.14ColumnlgpEnvTempDailyLowTimeSecondDegFread-onlycurrentThe seconds digit of the time corresponding to the daily low temperature measurement.
1.3.6.1.4.1.476.1.42.3.4.1.2.3.1.50ColumnlgpEnvTemperatureMeasurementTenthsDegFread-onlycurrentThe measured temperature value.
1.3.6.1.4.1.476.1.42.3.4.1.2.3.1.51ColumnlgpEnvTemperatureHighThresholdTenthsDegFread-writecurrentThe high temperature notification threshold. This is the maximum value of 'lgpEnvTemperatureMeasurementTenthsDegF' before the agent sends a notification.
1.3.6.1.4.1.476.1.42.3.4.1.2.3.1.52ColumnlgpEnvTemperatureLowThresholdTenthsDegFread-writecurrentThe low temperature notification threshold. This is the minimum value of 'lgpEnvTemperatureMeasurementTenthsDegF' before the agent sends a notification.
1.3.6.1.4.1.476.1.42.3.4.1.2.3.1.53ColumnlgpEnvTemperatureSetPointTenthsDegFread-writecurrentThe temperature setting for the well known 'lgpEnvTemperatureDescrDegF' point. This setting may or may not be the setting used from control. Some systems have …
1.3.6.1.4.1.476.1.42.3.4.1.2.3.1.60ColumnlgpEnvTemperatureDeadBandTenthsDegFread-writecurrentThe deadband region around the setpoint value (lgpEnvTemperatureSetPointTenthsDegF) where no heating or cooling will occur.
1.3.6.1.4.1.476.1.42.3.4.1.2.3.1.61ColumnlgpEnvTempHeatingPropBandTenthsDegFread-writecurrentThe proportional region below the setpoint value (lgpEnvTemperatureSetPointTenthsDegF) where heating will be proportionally controlled.
1.3.6.1.4.1.476.1.42.3.4.1.2.3.1.62ColumnlgpEnvTempCoolingPropBandTenthsDegFread-writecurrentThe proportional region above the setpoint value (lgpEnvTemperatureSetPointTenthsDegF) where cooling will be proportionally controlled.
1.3.6.1.4.1.476.1.42.3.4.1.2.4ScalarlgpEnvTemperatureDeadbandRangeDegFread-writecurrentThe allowable deviation above and below the temperature set point used to create a no control region, a dead-band, where heating and cooling control are disabl…
1.3.6.1.4.1.476.1.42.3.4.1.3IdentitylgpEnvTemperatureCelsiuscurrentThis sub-tree contains OIDs that are used to control and monitor temperature using the Celsius temperature scale.
1.3.6.1.4.1.476.1.42.3.4.1.3.1ScalarlgpEnvTemperatureSettingDegCread-writecurrentThe temperature setting used to control the well known temperature object 'lgpEnvControlTemperature'. This setting is cloned in 'lgpEnvTemperatureSettingDegF' …
1.3.6.1.4.1.476.1.42.3.4.1.3.2ScalarlgpEnvTemperatureToleranceDegCread-writecurrentThe acceptable variance from 'lgpEnvTemperatureSettingDegC', without initiating a control action. This setting is cloned in 'lgpEnvTemperatureToleranceDegF' wi…
1.3.6.1.4.1.476.1.42.3.4.1.3.3TablelgpEnvTemperatureTableDegCnot-accessiblecurrentA list of temperature table entries. The table contains zero, one, or many rows, depending upon the number of temperature objects available. The NMS cannot cre…
1.3.6.1.4.1.476.1.42.3.4.1.3.3.1RowlgpEnvTemperatureEntryDegCnot-accessiblecurrentThis entry defines the contents of the rows for the table 'lgpEnvTemperatureTableDegC'.
1.3.6.1.4.1.476.1.42.3.4.1.3.3.1.1ColumnlgpEnvTemperatureIdDegCread-onlycurrentThis OID is used as an index to identify a row in the table 'lgpEnvTemperatureTableDegC'.
1.3.6.1.4.1.476.1.42.3.4.1.3.3.1.2ColumnlgpEnvTemperatureDescrDegCread-onlycurrentA reference to a temperature description object. The object referenced should not be accessible, but rather be used to provide a unique description of the temp…
1.3.6.1.4.1.476.1.42.3.4.1.3.3.1.3ColumnlgpEnvTemperatureMeasurementDegCread-onlycurrentThe measured temperature value.
1.3.6.1.4.1.476.1.42.3.4.1.3.3.1.4ColumnlgpEnvTemperatureHighThresholdDegCread-writecurrentThe high temperature notification threshold. This is the maximum value of 'lgpEnvTemperatureMeasurementDegC' before the agent sends a notification.
1.3.6.1.4.1.476.1.42.3.4.1.3.3.1.5ColumnlgpEnvTemperatureLowThresholdDegCread-writecurrentThe low temperature notification threshold. This is the minimum value of 'lgpEnvTemperatureMeasurementDegC' before the agent sends a notification.
1.3.6.1.4.1.476.1.42.3.4.1.3.3.1.6ColumnlgpEnvTemperatureSetPointDegCread-writecurrentThe temperature setting for the well known 'lgpEnvTemperatureDescrDegC' point. This setting may or may not be the setting used from control. Some systems have …
1.3.6.1.4.1.476.1.42.3.4.1.3.3.1.7ColumnlgpEnvTemperatureDailyHighDegCread-onlycurrentThe daily high temperature measurement.
1.3.6.1.4.1.476.1.42.3.4.1.3.3.1.8ColumnlgpEnvTemperatureDailyLowDegCread-onlycurrentThe daily low temperature measurement.
1.3.6.1.4.1.476.1.42.3.4.1.3.3.1.9ColumnlgpEnvTempDailyHighTimeHourDegCread-onlycurrentThe hours digit of the time corresponding to the daily high temperature measurement.
1.3.6.1.4.1.476.1.42.3.4.1.3.3.1.10ColumnlgpEnvTempDailyHighTimeMinuteDegCread-onlycurrentThe minutes digit of the time corresponding to the daily high temperature measurement.
1.3.6.1.4.1.476.1.42.3.4.1.3.3.1.11ColumnlgpEnvTempDailyHighTimeSecondDegCread-onlycurrentThe seconds digit of the time corresponding to the daily high temperature measurement.
1.3.6.1.4.1.476.1.42.3.4.1.3.3.1.12ColumnlgpEnvTempDailyLowTimeHourDegCread-onlycurrentThe hours digit of the time corresponding to the daily low temperature measurement.
1.3.6.1.4.1.476.1.42.3.4.1.3.3.1.13ColumnlgpEnvTempDailyLowTimeMinuteDegCread-onlycurrentThe minutes digit of the time corresponding to the daily low temperature measurement.
1.3.6.1.4.1.476.1.42.3.4.1.3.3.1.14ColumnlgpEnvTempDailyLowTimeSecondDegCread-onlycurrentThe seconds digit of the time corresponding to the daily low temperature measurement.
1.3.6.1.4.1.476.1.42.3.4.1.3.3.1.50ColumnlgpEnvTemperatureMeasurementTenthsDegCread-onlycurrentThe measured temperature value.
1.3.6.1.4.1.476.1.42.3.4.1.3.3.1.51ColumnlgpEnvTemperatureHighThresholdTenthsDegCread-writecurrentThe high temperature notification threshold. This is the maximum value of 'lgpEnvTemperatureMeasurementTenthsDegC' before the agent sends a notification.
1.3.6.1.4.1.476.1.42.3.4.1.3.3.1.52ColumnlgpEnvTemperatureLowThresholdTenthsDegCread-writecurrentThe low temperature notification threshold. This is the minimum value of 'lgpEnvTemperatureMeasurementTenthsDegC' before the agent sends a notification.
1.3.6.1.4.1.476.1.42.3.4.1.3.3.1.53ColumnlgpEnvTemperatureSetPointTenthsDegCread-writecurrentThe temperature setting for the well known 'lgpEnvTemperatureDescrDegC' point. This setting may or may not be the setting used from control. Some systems have …
1.3.6.1.4.1.476.1.42.3.4.1.3.3.1.60ColumnlgpEnvTemperatureDeadBandTenthsDegCread-writecurrentThe deadband region around the setpoint value (lgpEnvTemperatureSetPointTenthsDegC) where no heating or cooling will occur.
1.3.6.1.4.1.476.1.42.3.4.1.3.3.1.61ColumnlgpEnvTempHeatingPropBandTenthsDegCread-writecurrentThe proportional region below the setpoint value (lgpEnvTemperatureSetPointTenthsDegC) where heating will be proportionally controlled.
1.3.6.1.4.1.476.1.42.3.4.1.3.3.1.62ColumnlgpEnvTempCoolingPropBandTenthsDegCread-writecurrentThe proportional region above the setpoint value (lgpEnvTemperatureSetPointTenthsDegC) where cooling will be proportionally controlled.
1.3.6.1.4.1.476.1.42.3.4.1.3.4ScalarlgpEnvTemperatureDeadbandRangeDegCread-writecurrentThe allowable deviation above and below the temperature set point used to create a no control region, a dead-band, where heating and cooling control are disabl…
1.3.6.1.4.1.476.1.42.3.4.1.4ScalarlgpEnvTemperatureControlModeread-onlycurrentA reference to a temperature description object. The object referenced should not be accessible, but rather be used to provide a unique description of the temp…
1.3.6.1.4.1.476.1.42.3.4.2IdentitylgpEnvHumiditycurrentThis sub-tree is used to register Liebert humidity object identifiers.
1.3.6.1.4.1.476.1.42.3.4.2.1IdentitylgpEnvHumidityWellKnowncurrentLiebert well known humidity objects are defined by OIDs that reside in this sub-tree.
1.3.6.1.4.1.476.1.42.3.4.2.1.1IdentitylgpEnvControlHumiditycurrentHumidity measurement used as control feedback.
1.3.6.1.4.1.476.1.42.3.4.2.1.2IdentitylgpEnvReturnAirHumiditycurrentHumidity measurement of return air.
1.3.6.1.4.1.476.1.42.3.4.2.1.3IdentitylgpEnvSupplyAirHumiditycurrentHumidity measurement of supply air.
1.3.6.1.4.1.476.1.42.3.4.2.1.4IdentitylgpEnvValueAmbientHumiditycurrentHumidity outside enclosure.
1.3.6.1.4.1.476.1.42.3.4.2.2IdentitylgpEnvHumidityRelativecurrentThis sub-tree contains OIDs that are used to control and monitor relative humidity.
1.3.6.1.4.1.476.1.42.3.4.2.2.1ScalarlgpEnvHumiditySettingRelread-writecurrentThe humidity setting used to control the well known humidity point.
1.3.6.1.4.1.476.1.42.3.4.2.2.2ScalarlgpEnvHumidityToleranceRelread-writecurrentAcceptable variance from lgpEnvHumiditySettingRel, without initiating a control action.
1.3.6.1.4.1.476.1.42.3.4.2.2.3TablelgpEnvHumidityTableRelnot-accessiblecurrentA list of humidity table entries. The table contains zero, one, or many rows, depending upon the number of humidity objects available. The NMS cannot create or…
1.3.6.1.4.1.476.1.42.3.4.2.2.3.1RowlgpEnvHumidityEntryRelnot-accessiblecurrentThis entry defines the contents of the rows for the table 'lgpEnvHumidityTableRel'.
1.3.6.1.4.1.476.1.42.3.4.2.2.3.1.1ColumnlgpEnvHumidityIdRelread-onlycurrentThis OID is used as an index to identify a row in the table 'lgpEnvHumidityTableRel'.
1.3.6.1.4.1.476.1.42.3.4.2.2.3.1.2ColumnlgpEnvHumidityDescrRelread-onlycurrentA reference to a humidity description object. The object referenced should not be accessible, but rather be used to provide a unique description of the humidit…
1.3.6.1.4.1.476.1.42.3.4.2.2.3.1.3ColumnlgpEnvHumidityMeasurementRelread-onlycurrentThe measured humidity value.
1.3.6.1.4.1.476.1.42.3.4.2.2.3.1.4ColumnlgpEnvHumidityHighThresholdRelread-writecurrentThe high humidity notification threshold. This is the maximum value of 'lgpEnvHumidityMeasurementRel' before the agent sends a notification.
1.3.6.1.4.1.476.1.42.3.4.2.2.3.1.5ColumnlgpEnvHumidityLowThresholdRelread-writecurrentThe low humidity notification threshold. This is the minimum value of 'lgpEnvHumidityMeasurementRel' before the agent sends a notification.
1.3.6.1.4.1.476.1.42.3.4.2.2.3.1.6ColumnlgpEnvHumiditySetPointread-writecurrentThe humidity setting used to control the well known humidity object 'lgpEnvHumidityDescrRel'. This setting may or may not be the setting used from control. Som…
1.3.6.1.4.1.476.1.42.3.4.2.2.3.1.7ColumnlgpEnvHumidityDailyHighread-onlycurrentThe daily high relative humidity measurement.
1.3.6.1.4.1.476.1.42.3.4.2.2.3.1.8ColumnlgpEnvHumidityDailyLowread-onlycurrentThe daily low relative humidity measurement.
1.3.6.1.4.1.476.1.42.3.4.2.2.3.1.9ColumnlgpEnvHumidityDailyHighTimeHourread-onlycurrentThe hours digit of the time corresponding to the daily high humidity measurement.
1.3.6.1.4.1.476.1.42.3.4.2.2.3.1.10ColumnlgpEnvHumidityDailyHighTimeMinuteread-onlycurrentThe minutes digit of the time corresponding to the daily high humidity measurement.
1.3.6.1.4.1.476.1.42.3.4.2.2.3.1.11ColumnlgpEnvHumidityDailyHighTimeSecondread-onlycurrentThe seconds digit of the time corresponding to the daily high humidity measurement.
1.3.6.1.4.1.476.1.42.3.4.2.2.3.1.12ColumnlgpEnvHumidityDailyLowTimeHourread-onlycurrentThe hours digit of the time corresponding to the daily low humidity measurement.
1.3.6.1.4.1.476.1.42.3.4.2.2.3.1.13ColumnlgpEnvHumidityDailyLowTimeMinuteread-onlycurrentThe minutes digit of the time corresponding to the daily low humidity measurement.
1.3.6.1.4.1.476.1.42.3.4.2.2.3.1.14ColumnlgpEnvHumidityDailyLowTimeSecondread-onlycurrentThe seconds digit of the time corresponding to the daily low humidity measurement.
1.3.6.1.4.1.476.1.42.3.4.2.2.3.1.15ColumnlgpEnvHumidityDeadBandread-writecurrentThe deadband region around the setpoint value (lgpEnvHumiditySetPoint) where no humidifying or dehumidifying will occur.
1.3.6.1.4.1.476.1.42.3.4.2.2.3.1.16ColumnlgpEnvHumidifyPropBandread-writecurrentThe proportional region below the setpoint value (lgpEnvHumiditySetPoint) where humidifying will be proportionally controlled.
1.3.6.1.4.1.476.1.42.3.4.2.2.3.1.17ColumnlgpEnvDehumidifyPropBandread-writecurrentThe proportional region above the setpoint value (lgpEnvHumiditySetPoint) where dehumidifying will be proportionally controlled.
1.3.6.1.4.1.476.1.42.3.4.2.2.3.1.50ColumnlgpEnvHumidityMeasurementRelTenthsread-onlycurrentThe measured humidity value.
1.3.6.1.4.1.476.1.42.3.4.2.2.3.1.51ColumnlgpEnvHumidityHighThresholdRelTenthsread-writecurrentThe high humidity notification threshold. This is the maximum value of 'lgpEnvHumidityMeasurementRelTenths' before the agent sends a notification.
1.3.6.1.4.1.476.1.42.3.4.2.2.3.1.52ColumnlgpEnvHumidityLowThresholdRelTenthsread-writecurrentThe low humidity notification threshold. This is the minimum value of 'lgpEnvHumidityMeasurementRelTenths' before the agent sends a notification.
1.3.6.1.4.1.476.1.42.3.4.2.2.4ScalarlgpEnvHumidityDeadbandRangeread-writecurrentThe allowable deviation above and below the humidity set point used to create a no control region, a dead-band, where humidifying and dehumidifying control are…
1.3.6.1.4.1.476.1.42.3.4.3IdentitylgpEnvStatecurrentThis sub-tree is used to register Liebert environmental state object identifiers.
1.3.6.1.4.1.476.1.42.3.4.3.1ScalarlgpEnvStateSystemread-onlycurrentThe present state of the system.
1.3.6.1.4.1.476.1.42.3.4.3.2ScalarlgpEnvStateCoolingread-onlycurrentThe present state of the cooling subsystem.
1.3.6.1.4.1.476.1.42.3.4.3.3ScalarlgpEnvStateHeatingread-onlycurrentThe present state of the heating subsystem.
1.3.6.1.4.1.476.1.42.3.4.3.4ScalarlgpEnvStateHumidifyingread-onlycurrentThe present state of the humidifier subsystem.
1.3.6.1.4.1.476.1.42.3.4.3.5ScalarlgpEnvStateDehumidifyingread-onlycurrentThe present state of the dehumidifier subsystem
1.3.6.1.4.1.476.1.42.3.4.3.6ScalarlgpEnvStateEconoCycleread-onlycurrentThe present state of the Econ-o-cycle subsystem.
1.3.6.1.4.1.476.1.42.3.4.3.7ScalarlgpEnvStateFanread-onlycurrentThe present state of the system fan.
1.3.6.1.4.1.476.1.42.3.4.3.8ScalarlgpEnvStateGeneralAlarmOutputread-onlycurrentThe present state of the general alarm output. This indicates if an alarm is active in the system.
1.3.6.1.4.1.476.1.42.3.4.3.9ScalarlgpEnvStateCoolingCapacityread-onlycurrentThe percentage of the cooling capacity presently in use.
1.3.6.1.4.1.476.1.42.3.4.3.10ScalarlgpEnvStateHeatingCapacityread-onlycurrentThe percentage of the heating capacity presently in use.
1.3.6.1.4.1.476.1.42.3.4.3.11ScalarlgpEnvStateAudibleAlarmread-onlycurrentThe present state of the audible alarm output.
1.3.6.1.4.1.476.1.42.3.4.3.12IdentitylgpEnvStateCoolingUnitscurrentThis sub-tree contains OIDs that are used to indicate the status of cooling units.
1.3.6.1.4.1.476.1.42.3.4.3.12.2ScalarlgpEnvStateCoolingUnit1read-onlycurrentThe present state of cooling unit 1.
1.3.6.1.4.1.476.1.42.3.4.3.12.3ScalarlgpEnvStateCoolingUnit2read-onlycurrentThe present state of cooling unit 2.
1.3.6.1.4.1.476.1.42.3.4.3.12.4ScalarlgpEnvStateCoolingUnit3read-onlycurrentThe present state of cooling unit 3.
1.3.6.1.4.1.476.1.42.3.4.3.12.5ScalarlgpEnvStateCoolingUnit4read-onlycurrentThe present state of cooling unit 4.
1.3.6.1.4.1.476.1.42.3.4.3.13IdentitylgpEnvStateHeatingUnitscurrentThis sub-tree contains OIDs that are used to indicate the status of heating units.
1.3.6.1.4.1.476.1.42.3.4.3.13.2ScalarlgpEnvStateHeatingUnit1read-onlycurrentThe present state of heating unit 1.
1.3.6.1.4.1.476.1.42.3.4.3.13.3ScalarlgpEnvStateHeatingUnit2read-onlycurrentThe present state of heating unit 2.
1.3.6.1.4.1.476.1.42.3.4.3.13.4ScalarlgpEnvStateHeatingUnit3read-onlycurrentThe present state of heating unit 3.
1.3.6.1.4.1.476.1.42.3.4.3.13.5ScalarlgpEnvStateHeatingUnit4read-onlycurrentThe present state of heating unit 4.
1.3.6.1.4.1.476.1.42.3.4.3.14ScalarlgpEnvStateOperatingReasonread-onlycurrentThe reason for the current operating state of the system.
1.3.6.1.4.1.476.1.42.3.4.3.15ScalarlgpEnvStateOperatingModeread-onlycurrentThe present operating mode of the system.
1.3.6.1.4.1.476.1.42.3.4.3.16ScalarlgpEnvStateFanCapacityread-onlycurrentThe percentage of the fan capacity presently in use.
1.3.6.1.4.1.476.1.42.3.4.3.17ScalarlgpEnvStateFreeCoolingCapacityread-onlycurrentThe percentage of the free cooling capacity presently in use.
1.3.6.1.4.1.476.1.42.3.4.3.18ScalarlgpEnvStateDehumidifyingCapacityread-onlycurrentThe percentage of the dehumidifying capacity presently in use.
1.3.6.1.4.1.476.1.42.3.4.3.19ScalarlgpEnvStateHumidifyingCapacityread-onlycurrentThe percentage of the humidifying capacity presently in use.
1.3.6.1.4.1.476.1.42.3.4.3.20ScalarlgpEnvStateFreeCoolingread-onlycurrentThe present state of the system free cooling process of heat exchange. When 'off', free cooling is not in use. When 'on' free cooling is in use. When 'start', …
1.3.6.1.4.1.476.1.42.3.4.3.21ScalarlgpEnvStateElectricHeaterread-onlycurrentThe present state of the electric heaters.
1.3.6.1.4.1.476.1.42.3.4.3.22ScalarlgpEnvStateHotWaterread-onlycurrentThe present state of hot water system.
1.3.6.1.4.1.476.1.42.3.4.3.23ScalarlgpEnvStateOperatingEfficiencyread-onlycurrentThe ratio of cooling energy provided to the amount of total energy being used.
1.3.6.1.4.1.476.1.42.3.4.3.50TablelgpEnvComponentStateTablenot-accessiblecurrentThis table contains a list of the units components that have a state associated with them. The table contains zero, one, or more rows, depending upon the numbe…
1.3.6.1.4.1.476.1.42.3.4.3.50.1RowlgpEnvComponentStateEntrynot-accessiblecurrentThis entry defines the attributes to be populated in the various columns of the 'lgpEnvComponentStateTable'.
1.3.6.1.4.1.476.1.42.3.4.3.50.1.1ColumnlgpEnvComponentStateIndexnot-accessiblecurrentThis is the index indicating the nth element of the table.
1.3.6.1.4.1.476.1.42.3.4.3.50.1.2ColumnlgpEnvComponentStateDescrread-onlycurrentA reference to a component description object. The object referenced should not be accessible, but rather be used to provide a unique description of the compon…
1.3.6.1.4.1.476.1.42.3.4.3.50.1.3ColumnlgpEnvComponentStateread-onlycurrentnot-specified The state of the component is unknown. on The component is on. off The component is off.
1.3.6.1.4.1.476.1.42.3.4.3.70TablelgpEnvValveTablenot-accessiblecurrentThis table contains a list of the unit valves that have information associated with them. The table contains zero, one, or more rows, depending upon the number…
1.3.6.1.4.1.476.1.42.3.4.3.70.1RowlgpEnvValveEntrynot-accessiblecurrentThis entry defines the attributes to be populated in the various columns of the 'lgpEnvValveTable'.
1.3.6.1.4.1.476.1.42.3.4.3.70.1.1ColumnlgpEnvValveIndexnot-accessiblecurrentThis is the index indicating the nth element of the table.
1.3.6.1.4.1.476.1.42.3.4.3.70.1.2ColumnlgpEnvValveDescrread-onlycurrentA reference to a valve description object. The object referenced should not be accessible, but rather be used to provide a unique description of the valve bein…
1.3.6.1.4.1.476.1.42.3.4.3.70.1.3ColumnlgpEnvValveStateread-onlycurrentnot-specified The state of the component is unknown. open The valve is open. off The valve is closed.
1.3.6.1.4.1.476.1.42.3.4.3.70.1.20ColumnlgpEnvValvePositionTenthsread-onlycurrentThis gives a value describing the position of the valve.
1.3.6.1.4.1.476.1.42.3.4.4IdentitylgpEnvConfigcurrentThis sub-tree is used to register Liebert environmental configuration object identifiers.
1.3.6.1.4.1.476.1.42.3.4.4.1ScalarlgpEnvConfigReheatLockoutread-writecurrentIf locked-out the reheats will not operate even if controller calls for its operation.
1.3.6.1.4.1.476.1.42.3.4.4.2ScalarlgpEnvConfigHumLockoutread-writecurrentIf locked-out the humidifier will not operate even if controller calls for its operation.
1.3.6.1.4.1.476.1.42.3.4.4.4ScalarlgpEnvConfigRestartDelayread-writecurrentWhen utility power is disrupted, this is the delay interval to wait before restarting the system after the utility power is restored. A Restart Delay of zero d…
1.3.6.1.4.1.476.1.42.3.4.4.7ScalarlgpEnvConfigRemoteShutdownread-writecurrentWhen in the disabled state, the remote shutdown feature should be locked out. The enabled state is self-describing.
1.3.6.1.4.1.476.1.42.3.4.4.8ScalarlgpEnvConfigCoolingServiceIntervalread-writecurrentThe amount of time, in hours, between scheduled maintenance of the cooling system. When the cooling service timer reaches this value an lgpConditionServiceCool…
1.3.6.1.4.1.476.1.42.3.4.4.9ScalarlgpEnvConfigHumidifierServiceIntervalread-writecurrentThe amount of time, in hours, between scheduled maintenance of the humidifier. When the humidifier service timer reaches this value an lgpConditionServiceHumid…
1.3.6.1.4.1.476.1.42.3.4.4.10ScalarlgpEnvConfigFilterServiceIntervalread-writecurrentThe amount of time, in hours, between scheduled maintenance of the system filter. When the filter service timer reaches this value an lgpConditionChangeFilter …
1.3.6.1.4.1.476.1.42.3.4.4.11ScalarlgpEnvConfigSleepModeDeadbandRangeDegCread-writecurrentThe allowable deviation above and below the temperature set point used to create a no control region, a dead-band, where heating and cooling control are disabl…
1.3.6.1.4.1.476.1.42.3.4.4.12ScalarlgpEnvConfigSleepModeDeadbandRangeDegFread-writecurrentThe allowable deviation above and below the temperature set point used to create a no control region, a dead-band, where heating and cooling control are disabl…
1.3.6.1.4.1.476.1.42.3.4.4.13ScalarlgpEnvConfigSupplyTempLowLimitDegFread-writecurrentThe minimum allowable supply temperature.
1.3.6.1.4.1.476.1.42.3.4.4.14ScalarlgpEnvConfigSupplyTempLowLimitDegCread-writecurrentThe minimum allowable supply temperature.
1.3.6.1.4.1.476.1.42.3.4.4.15ScalarlgpEnvConfigTemperatureIntegTimeread-writecurrentThe value used as the integration factor in the proportional integral derivative (PID) temperature calculation.
1.3.6.1.4.1.476.1.42.3.4.4.16ScalarlgpEnvConfigLocalTemperatureUnitread-writecurrentThe local temperature unit of the system.
1.3.6.1.4.1.476.1.42.3.4.4.17ScalarlgpEnvConfigSleepModeread-writecurrentThe configured mode of the device's sleep function. If 'enabled', the device will sleep, or not operate, for each 'lgpEnvSleepDay' that is enabled and also dur…
1.3.6.1.4.1.476.1.42.3.4.4.18ScalarlgpEnvConfigHumidityIntegTimeread-writecurrentThe value used as the integration factor in the proportional integral derivative (PID) humidity calculation.
1.3.6.1.4.1.476.1.42.3.4.4.19ScalarlgpEnvConfigFreecoolingDeltaDegFread-writecurrentThe minimum temperature differential between the control temperature measurement and the coolant required to utilize free-cooling.
1.3.6.1.4.1.476.1.42.3.4.4.20ScalarlgpEnvConfigFreecoolingDeltaDegCread-writecurrentThe minimum temperature differential between the control temperature measurement and the coolant required to utilize free-cooling.
1.3.6.1.4.1.476.1.42.3.4.4.21ScalarlgpEnvConfigSupplyTempLowLimitread-writecurrentThe system configuration parameter to enable or disable the supply air low temperature limit.
1.3.6.1.4.1.476.1.42.3.4.4.22ScalarlgpEnvConfigSensorEventsStandardread-writecurrentThe system configuration parameter to enable or disable the standard sensor events.
1.3.6.1.4.1.476.1.42.3.4.4.23ScalarlgpEnvConfigSensorEvents1read-writecurrentThe system configuration parameter to enable or disable sensor 1 events.
1.3.6.1.4.1.476.1.42.3.4.4.24ScalarlgpEnvConfigSleepModeDeadbandRangeread-writecurrentThe system configuration parameter to enable or disable the use of the sleep interval dead-band range in the sleep mode temperature calculations and control al…
1.3.6.1.4.1.476.1.42.3.4.4.25ScalarlgpEnvConfigAutoConfigurationread-writecurrentThe system configuration parameter to enable or disable the auto configuration feature. This feature configures temperature and humidity control parameters.
1.3.6.1.4.1.476.1.42.3.4.4.26ScalarlgpEnvConfigDeltaGlycolTyperead-writecurrentThe system configuration parameter that specifies how the system will determine if there is enough capacity to initiate free cooling. If 'disabled', the system…
1.3.6.1.4.1.476.1.42.3.4.4.27ScalarlgpEnvConfigChillWaterControlread-writecurrentThe system configuration parameter to enable or disable the minimum chill water temperature control.
1.3.6.1.4.1.476.1.42.3.4.4.28ScalarlgpEnvConfigInfaredFlushRateread-writecurrentThe Infrared humidifier pan overfill rate. This parameter configures the amount of water that flows into the humidifier pan when the 'humidifier is in operatio…
1.3.6.1.4.1.476.1.42.3.4.4.29ScalarlgpEnvConfigHumidityControlread-writecurrentThe present configured state of the automatic humidity compensation algorithm.
1.3.6.1.4.1.476.1.42.3.4.4.30ScalarlgpEnvConfigCompressorLockoutread-writecurrentThe system as locked out the compressor(s). If locked-out, the compressor(s) will not operate even if the controller calls for their operation.
1.3.6.1.4.1.476.1.42.3.4.4.31ScalarlgpEnvConfigReheatAndHumidifierLockoutread-writecurrentThe system as locked out the compressor(s). If locked-out, the electrical reheats and humidifier will not operate even if the controller calls for their operat…
1.3.6.1.4.1.476.1.42.3.4.4.32TablelgpEnvOperationalTimeTablenot-accessiblecurrentA list of environmental operational time ranges for a given environmental unit. The entries in this table may be duplicated from values in the 'lgpEnvStatistic…
1.3.6.1.4.1.476.1.42.3.4.4.32.1RowlgpEnvOperationalTimeEntrynot-accessiblecurrentThis entry defines the contents of the columns for the table 'lgpEnvOperationalTimeTable'.
1.3.6.1.4.1.476.1.42.3.4.4.32.1.1ColumnlgpEnvOperationTimeIndexnot-accessiblecurrentThis is the index indicating the nth element of the table.
1.3.6.1.4.1.476.1.42.3.4.4.32.1.2ColumnlgpEnvOperationTimePointread-onlycurrentAn OID representing a well known operation point. These object identifiers can indicate a point, location, or mode of an operation for which a measurement is r…
1.3.6.1.4.1.476.1.42.3.4.4.32.1.3ColumnlgpEnvOperationTimeSubIDread-onlycurrentThis is a sub identifier for the 'lgpEnvOperationPoint'. It indicates the instance number of the well known operation point. For example, a system could have t…
1.3.6.1.4.1.476.1.42.3.4.4.32.1.4ColumnlgpEnvOperationTimeUnitread-onlycurrentAn OID representing a well known operation time unit type. These object identifiers indicate the units of the operation time. The OID's name usually implies a …
1.3.6.1.4.1.476.1.42.3.4.4.32.1.5ColumnlgpEnvOperationTimeValueread-writecurrentThe actual operation time value of the 'lgpEnvOperationTimePoint'. If multiple operation times are available for a 'lgpEnvOperationTimePoint' the 'lgpEnvOperat…
1.3.6.1.4.1.476.1.42.3.4.4.32.1.6ColumnlgpEnvOperationTimeHighWarningread-writecurrentThe high warning time of the operation designated by the 'lgpEnvOperationTimePoint'. If operation times are available at a single 'lgpEnvOperationTimePoint' th…
1.3.6.1.4.1.476.1.42.3.4.4.33ScalarlgpEnvConfigTempControlAlgorithmread-writecurrentSelects the algorithm for controlling temperature.
1.3.6.1.4.1.476.1.42.3.4.4.34ScalarlgpEnvConfigFanSpeedModeread-writecurrentChanges the function of the fan speed output. If auto, then the fan speed is modulated. If manual, the fan speed output follows lgpEnvConfigFanSpeedCapacity.
1.3.6.1.4.1.476.1.42.3.4.4.35ScalarlgpEnvConfigFanSpeedCapacityread-writecurrentSets the fan speed output if lgpEnvConfigFanSpeedMode is set to 'manual'. Typical values range from 0 to 100% (actual valid ranges may differ from unit to unit…
1.3.6.1.4.1.476.1.42.3.4.4.36ScalarlgpEnvConfigBmsResetTimerread-writecurrentThe current count-down time for a BMS to continue controlling the fan speed. If this value reaches 0, then the condition lgpConditionBmsResetTimerExpired will …
1.3.6.1.4.1.476.1.42.3.4.4.37ScalarlgpEnvConfigDisableSensorOffsetDegCread-writecurrentIf any of the enclosure temperature sensors (lgpEnvEnclosureTemperatureSensors) are outside the average reading by this amount, that sensor's readings will not…
1.3.6.1.4.1.476.1.42.3.4.4.38ScalarlgpEnvConfigDisableSensorOffsetDegFread-writecurrentIf any of the enclosure temperature sensors (lgpEnvEnclosureTemperatureSensors) are outside the average reading by this amount, that sensor's readings will not…
1.3.6.1.4.1.476.1.42.3.4.4.39ScalarlgpEnvConfigCabinetSensorAlarmsread-writecurrentEnable or Disable Cabinet Sensor Alarms.
1.3.6.1.4.1.476.1.42.3.4.4.42ScalarlgpEnvConfigAirTemperatureControlSensorread-writecurrentSensor from which air temperature measurements will be used for cooling and heating control.
1.3.6.1.4.1.476.1.42.3.4.4.43ScalarlgpEnvConfigFanSpeedControlSensorread-writecurrentSensor from which air temperature measurements will be used for fan speed control.
1.3.6.1.4.1.476.1.42.3.4.4.44ScalarlgpEnvConfigMinFanSpeedread-writecurrentSets the minimum fan speed output if lgpEnvConfigFanSpeedMode is set to 'Auto'.
1.3.6.1.4.1.476.1.42.3.4.4.45ScalarlgpEnvConfigMaxFanSpeedread-writecurrentSets the maximum fan speed output if lgpEnvConfigFanSpeedMode is set to 'Auto'.
1.3.6.1.4.1.476.1.42.3.4.4.46ScalarlgpEnvConfigFanSpeedPropBandDegCread-writecurrentTemperature control band above the temperature set point calculated for proportional fan speed control. If measured air temperature is within this band, fan sp…
1.3.6.1.4.1.476.1.42.3.4.4.47ScalarlgpEnvConfigFanSpeedPropBandDegFread-writecurrentTemperature control band above the temperature set point calculated for proportional fan speed control. If measured air temperature is within this band, fan sp…
1.3.6.1.4.1.476.1.42.3.4.5IdentitylgpEnvControlcurrentThis sub-tree is used to register Liebert environmental control object identifiers.
1.3.6.1.4.1.476.1.42.3.4.5.1ScalarlgpEnvControlShutdownAfterDelayread-writecurrentSetting this object will shutdown (i.e., turn off) the system after the indicated number of seconds. Setting this object to 0 will cause the shutdown to occur …
1.3.6.1.4.1.476.1.42.3.4.5.2ScalarlgpEnvControlStartupAfterDelayread-writecurrentSetting this object will start the system after the indicated number of seconds. Setting this object to 0 will cause the startup to occur immediately. Setting …
1.3.6.1.4.1.476.1.42.3.4.5.3TablelgpEnvSleepIntervalTimeTablenot-accessiblecurrentA sleep time interval table containing a list of the start and stop times to be used to take a device online or offline. The NMS cannot create or delete rows f…
1.3.6.1.4.1.476.1.42.3.4.5.3.1RowlgpEnvSleepIntervalTimeEntrynot-accessiblecurrentThis entry defines the contents of the columns for the table 'lgpEnvSleepIntervalTimeTable'.
1.3.6.1.4.1.476.1.42.3.4.5.3.1.1ColumnlgpEnvSleepTimeIndexnot-accessiblecurrentThis is the index indicating the row of the table 'lgpEnvSleepIntervalTimeTable'.
1.3.6.1.4.1.476.1.42.3.4.5.3.1.2ColumnlgpEnvSleepTimeSubIDread-onlycurrentThis is a sub identifier for each 'lgpEnvSleepIntervalTimeEntry'. It indicates the instance number of the 'lgpEnvSleepIntervalTimeEntry'. For example, a system…
1.3.6.1.4.1.476.1.42.3.4.5.3.1.3ColumnlgpEnvSleepTimeStartHourread-writecurrentThis is the hours digit of the time when the system will be put online.
1.3.6.1.4.1.476.1.42.3.4.5.3.1.4ColumnlgpEnvSleepTimeStartMinuteread-writecurrentThis is the minutes digit of the time when the system will be put online.
1.3.6.1.4.1.476.1.42.3.4.5.3.1.5ColumnlgpEnvSleepTimeStopHourread-writecurrentThis is the hours digit containing the time when the system will be taken offline.
1.3.6.1.4.1.476.1.42.3.4.5.3.1.6ColumnlgpEnvSleepTimeStopMinuteread-writecurrentThis is the minutes digit containing the time when the system will be taken offline.
1.3.6.1.4.1.476.1.42.3.4.5.4TablelgpEnvSleepDayTablenot-accessiblecurrentA sleep table containing a list of the days of the week the system will be offline. The NMS cannot create or delete rows from the table. The rows are created b…
1.3.6.1.4.1.476.1.42.3.4.5.4.1RowlgpEnvSleepDayEntrynot-accessiblecurrentThis entry defines the contents of the columns for the table 'lgpEnvSleepDayTable'.
1.3.6.1.4.1.476.1.42.3.4.5.4.1.1ColumnlgpEnvSleepDayIndexnot-accessiblecurrentThis is the index indicating the row of the table 'lgpEnvSleepDayTable'.
1.3.6.1.4.1.476.1.42.3.4.5.4.1.2ColumnlgpEnvSleepDayread-onlycurrentThis is a sub identifier for the day of the week within 'lgpEnvSleepDayTable'.
1.3.6.1.4.1.476.1.42.3.4.5.4.1.3ColumnlgpEnvSleepAllDayEnabledread-writecurrentThe all day sleep functionality has been enabled for the corresponding 'lgpEnvSleepDay' in the 'lgpEnvSleepDayTable'.
1.3.6.1.4.1.476.1.42.3.4.6IdentitylgpEnvStatisticscurrentThis sub-tree is used to register Liebert environmental statistic object identifiers.
1.3.6.1.4.1.476.1.42.3.4.6.1ScalarlgpEnvStatisticsComp1RunHrread-onlycurrentAccumulated run hours of compressor 1. This value may be duplicated in the 'lgpEnvOperationalTimeTable'.
1.3.6.1.4.1.476.1.42.3.4.6.2ScalarlgpEnvStatisticsComp2RunHrread-onlycurrentAccumulated run hours of compressor 2. This value may be duplicated in the 'lgpEnvOperationalTimeTable'.
1.3.6.1.4.1.476.1.42.3.4.6.3ScalarlgpEnvStatisticsFanRunHrread-onlycurrentAccumulated run hours of the main fan. This value may be duplicated in the 'lgpEnvOperationalTimeTable'.
1.3.6.1.4.1.476.1.42.3.4.6.4ScalarlgpEnvStatisticsHumRunHrread-onlycurrentAccumulated run hours of the humidifier. This value may be duplicated in the 'lgpEnvOperationalTimeTable'.
1.3.6.1.4.1.476.1.42.3.4.6.7ScalarlgpEnvStatisticsReheat1RunHrread-onlycurrentAccumulated run hours of reheat element 1. This value may be duplicated in the 'lgpEnvOperationalTimeTable'.
1.3.6.1.4.1.476.1.42.3.4.6.8ScalarlgpEnvStatisticsReheat2RunHrread-onlycurrentAccumulated run hours of reheat element 2. This value may be duplicated in the 'lgpEnvOperationalTimeTable'.
1.3.6.1.4.1.476.1.42.3.4.6.9ScalarlgpEnvStatisticsReheat3RunHrread-onlycurrentAccumulated run hours of reheat element 3. This value may be duplicated in the 'lgpEnvOperationalTimeTable'.
1.3.6.1.4.1.476.1.42.3.4.6.10ScalarlgpEnvStatisticsCoolingModeHrsread-onlycurrentAccumulated run hours while lgpEnvStateCooling is on(1). This value may be duplicated in the 'lgpEnvOperationalTimeTable'.
1.3.6.1.4.1.476.1.42.3.4.6.11ScalarlgpEnvStatisticsHeatingModeHrsread-onlycurrentAccumulated run hours while lgpEnvStateHeating is on(1). This value may be duplicated in the 'lgpEnvOperationalTimeTable'.
1.3.6.1.4.1.476.1.42.3.4.6.12ScalarlgpEnvStatisticsHumidifyModeHrsread-onlycurrentAccumulated run hours of the humidifying process of the system. This value may be duplicated in the 'lgpEnvOperationalTimeTable'.
1.3.6.1.4.1.476.1.42.3.4.6.13ScalarlgpEnvStatisticsDehumidifyModeHrsread-onlycurrentAccumulated run hours of the dehumidifying process of the system. This value may be duplicated in the 'lgpEnvOperationalTimeTable'.
1.3.6.1.4.1.476.1.42.3.4.6.14ScalarlgpEnvStatisticsHotGasRunHrread-onlycurrentAccumulated run hours of the hot gas system. This value may be duplicated in the 'lgpEnvOperationalTimeTable'.
1.3.6.1.4.1.476.1.42.3.4.6.15ScalarlgpEnvStatisticsHotWaterRunHrread-onlycurrentAccumulated run hours of the hot water system. This value may be duplicated in the 'lgpEnvOperationalTimeTable'.
1.3.6.1.4.1.476.1.42.3.4.6.16ScalarlgpEnvStatisticsFreeCoolRunHrread-onlycurrentAccumulated run hours of the free cooling process. This value may be duplicated in the 'lgpEnvOperationalTimeTable'.
1.3.6.1.4.1.476.1.42.3.4.6.17ScalarlgpEnvStatisticsComp3RunHrread-onlycurrentAccumulated run hours of compressor 3.
1.3.6.1.4.1.476.1.42.3.4.6.18ScalarlgpEnvStatisticsComp4RunHrread-onlycurrentAccumulated run hours of compressor 4.
1.3.6.1.4.1.476.1.42.3.4.7IdentitylgpEnvPointscurrentThis sub-tree is used to register Liebert environmental point object identifiers.
1.3.6.1.4.1.476.1.42.3.4.7.1IdentitylgpEnvWellKnownPointscurrentThis sub-tree registers well known Liebert Environmental Points. The object identifier names usually encompass a process, or location, where measurements are r…
1.3.6.1.4.1.476.1.42.3.4.7.1.1IdentitylgpEnvFanPointcurrentThis identifier represents a well known fan measurement point.
1.3.6.1.4.1.476.1.42.3.4.7.1.2IdentitylgpEnvCompressorPointcurrentThis identifier represents a well known compressor measurement point.
1.3.6.1.4.1.476.1.42.3.4.7.1.3IdentitylgpEnvElectricHeaterPointcurrentThis identifier represents a well known electric heater measurement point.
1.3.6.1.4.1.476.1.42.3.4.7.1.4IdentitylgpEnvChilledWaterPointcurrentThis identifier represents a well known chilled water measurement point.
1.3.6.1.4.1.476.1.42.3.4.7.1.5IdentitylgpEnvHumidifierPointcurrentThis identifier represents a well known humidifier measurement point.
1.3.6.1.4.1.476.1.42.3.4.7.1.6IdentitylgpEnvDehumidifierPointcurrentThis identifier represents a well known dehumidifier measurement point.
1.3.6.1.4.1.476.1.42.3.4.7.1.7IdentitylgpEnvFreeCoolingPointcurrentThis identifier represents a well known free-cooling measurement process.
1.3.6.1.4.1.476.1.42.3.4.7.1.8IdentitylgpEnvHotWaterPointcurrentThis identifier represents a well known hot water measurement point.
1.3.6.1.4.1.476.1.42.3.4.7.1.9IdentitylgpEnvHotGasPointcurrentThis identifier represents a well known hot gas measurement point.
1.3.6.1.4.1.476.1.42.3.4.7.1.10IdentitylgpEnvBatteryCabinetPointcurrentThis identifier represents a well known cabinet point. To determine the cabinet being described in a multi-cabinet system, this point implements two additional…
1.3.6.1.4.1.476.1.42.3.4.7.1.11IdentitylgpEnvPumpPointscurrentThis sub-tree identifies well-known pumps in the system.
1.3.6.1.4.1.476.1.42.3.4.7.1.11.1IdentitylgpEnvPump1PointcurrentThis identifier represents pump 1.
1.3.6.1.4.1.476.1.42.3.4.7.1.11.2IdentitylgpEnvPump2PointcurrentThis identifier represents pump 2.
1.3.6.1.4.1.476.1.42.3.4.7.1.12IdentitylgpEnvCompressorPointscurrentThis sub-tree identifies well-known compressors in the system.
1.3.6.1.4.1.476.1.42.3.4.7.1.12.1IdentitylgpEnvCompressor1PointcurrentThis identifier represents compressor 1.
1.3.6.1.4.1.476.1.42.3.4.7.1.12.1.1IdentitylgpEnvCompressor1APointcurrentThis identifier represents compressor 1A.
1.3.6.1.4.1.476.1.42.3.4.7.1.12.1.2IdentitylgpEnvCompressor1BPointcurrentThis identifier represents compressor 1B.
1.3.6.1.4.1.476.1.42.3.4.7.1.12.2IdentitylgpEnvCompressor2PointcurrentThis identifier represents compressor 2.
1.3.6.1.4.1.476.1.42.3.4.7.1.12.2.1IdentitylgpEnvCompressor2APointcurrentThis identifier represents compressor 2A.
1.3.6.1.4.1.476.1.42.3.4.7.1.12.2.2IdentitylgpEnvCompressor2BPointcurrentThis identifier represents compressor 2B.
1.3.6.1.4.1.476.1.42.3.4.7.1.13IdentitylgpEnvValvePointscurrentThis sub-tree identifies well-known valves in the system.
1.3.6.1.4.1.476.1.42.3.4.7.1.13.1IdentitylgpEnvHotGasValve1PointcurrentThis identifier represents hot gas valve 1.
1.3.6.1.4.1.476.1.42.3.4.7.1.13.2IdentitylgpEnvHotGasValve2PointcurrentThis identifier represents hot gas valve 2.
1.3.6.1.4.1.476.1.42.3.4.7.1.14IdentitylgpEnvRemoteSensorStatisticPointscurrentThis sub-tree identifies well-known remote sensor statistics in the system.
1.3.6.1.4.1.476.1.42.3.4.7.1.14.1IdentitylgpEnvRemoteSensorMinimumPointcurrentThis identifier represents the minimum value for remote sensor readings.
1.3.6.1.4.1.476.1.42.3.4.7.1.14.2IdentitylgpEnvRemoteSensorMaximumPointcurrentThis identifier represents the maximum value for remote sensor readings.
1.3.6.1.4.1.476.1.42.3.4.7.1.14.3IdentitylgpEnvRemoteSensorAveragePointcurrentThis identifier represents the average value for remote sensor readings.
1.3.6.1.4.1.476.1.42.3.4.8IdentitylgpEnvUnitscurrentThis sub-tree is used to register Liebert environmental unit object identifiers.
1.3.6.1.4.1.476.1.42.3.4.8.1IdentitylgpEnvWellKnownUnitscurrentThis sub-tree registers well known Liebert Environmental Units. The object identifier names usually encompass a process, or location, where measurements are re…
1.3.6.1.4.1.476.1.42.3.4.8.1.1IdentitylgpEnvHourscurrentThis identifier represents well known time unit of hours.
1.3.6.1.4.1.476.1.42.3.4.9IdentitylgpEnvRemoteSensorscurrentThis sub-tree is used to register Liebert environmental remote sensor object identifiers.
1.3.6.1.4.1.476.1.42.3.4.9.1ScalarlgpEnvRemoteSensorCalcread-writecurrentCalculation method applied to temperature readings from the remote sensors to determine a single temperature measurement value for cooling and heating control.
1.3.6.1.4.1.476.1.42.3.4.9.10TablelgpEnvRemoteSensorTablenot-accessiblecurrentThis table contains a list of remote sensors attached to the environmental unit. The table contains zero, one, or more rows, depending upon the number of senso…
1.3.6.1.4.1.476.1.42.3.4.9.10.1RowlgpEnvRemoteSensorEntrynot-accessiblecurrentThis entry defines the attributes to be populated in the various columns of the 'lgpEnvRemoteSensorTable'.
1.3.6.1.4.1.476.1.42.3.4.9.10.1.1ColumnlgpEnvRemoteSensorIndexnot-accessiblecurrentThis is the index indicating the nth element of the table.
1.3.6.1.4.1.476.1.42.3.4.9.10.1.2ColumnlgpEnvRemoteSensorIdread-onlycurrentThis is the sensor number identifying the sensor.
1.3.6.1.4.1.476.1.42.3.4.9.10.1.3ColumnlgpEnvRemoteSensorModeread-writecurrentFunction assigned to remote sensor. When set to control(2) the sensor will be used in calculation of remote sensor temperature which may be used for heating an…
1.3.6.1.4.1.476.1.42.3.4.9.10.1.4ColumnlgpEnvRemoteSensorUsrLabelread-writecurrentUser assigned remote sensor label.
1.3.6.1.4.1.476.1.42.3.4.9.10.1.5ColumnlgpEnvRemoteSensorTempMeasurementDegFread-onlycurrentTemperature measured at the temperature sensor reported in degrees Fahrenheit.
1.3.6.1.4.1.476.1.42.3.4.9.10.1.6ColumnlgpEnvRemoteSensorTempMeasurementDegCread-onlycurrentTemperature measured at the temperature sensor reported in degrees Celsius.