MIB Viewer

LIEBERT-GP-FLEXIBLE-MIB

17 objects
The MIB module used to register Liebert Flexible related SNMP OIDs. Copyright 2013 Liebert Corporation. All rights reserved. Reproduction of this document is authorized on the condition that the forgoing copyright notice is included. This Specification is supplied 'AS IS' and Liebert Corporation makes no warranty, either express or implied, as to the use, operation, condition, or performance of the Specification.
Imported Objects
OIDNameAccessStatusDescription
1.3.6.1.4.1.476.1.42.1.10.1IdentityliebertGlobalProductsFlexibleModuleThe MIB module used to register Liebert Flexible related SNMP OIDs. Copyright 2013 Liebert Corporation. All rights reserved. Reproduction of this document is a…
1.3.6.1.4.1.476.1.42.3.9.10ScalarlgpFlexibleTableCountread-onlycurrentThis is the number of entries in the lgpFlexibleBasicTable.
1.3.6.1.4.1.476.1.42.3.9.20TablelgpFlexibleBasicTablenot-accessiblecurrentThis table contains data points supported by the managed device. The data in this table is formatted in string form. This data is also available in numerical f…
1.3.6.1.4.1.476.1.42.3.9.20.1RowlgpFlexibleBasicEntrynot-accessiblecurrentThis entry defines the columns to be populated in the 'lgpFlexibleBasicTable'.
1.3.6.1.4.1.476.1.42.3.9.20.1.1ColumnlgpFlexibleEntryIndexnot-accessiblecurrentThis is the index which defines a specific row in the lgpFlexibleBasicTable. Each row index is associated with a unique data point ID which fixes the data poin…
1.3.6.1.4.1.476.1.42.3.9.20.1.10ColumnlgpFlexibleEntryDataLabelread-onlycurrentA short description of the data reported in this row.
1.3.6.1.4.1.476.1.42.3.9.20.1.20ColumnlgpFlexibleEntryValueread-writecurrentA string representation of any data available. This is the preferred method of data access, since this will give fully scaled data for both integer and floatin…
1.3.6.1.4.1.476.1.42.3.9.20.1.30ColumnlgpFlexibleEntryUnitsOfMeasureread-onlycurrentThe unit of measure that the value will be presented in. This is not populated when the data does not have a unit of measure associated with it.
1.3.6.1.4.1.476.1.42.3.9.30TablelgpFlexibleExtendedTablenot-accessiblecurrentThis table contains data points supported by the managed device. This table augments the lgpFlexibleBasicTable, providing additional information that may be re…
1.3.6.1.4.1.476.1.42.3.9.30.1RowlgpFlexibleExtendedEntrynot-accessiblecurrentThis entry defines the columns to be populated in the 'lgpFlexibleExtendedTable'.
1.3.6.1.4.1.476.1.42.3.9.30.1.10ColumnlgpFlexibleEntryIntegerValueread-writecurrentThis is the data point value formatted as a signed integer. This column is populated only for numerical data points whose type requires a signed value. To conv…
1.3.6.1.4.1.476.1.42.3.9.30.1.20ColumnlgpFlexibleEntryUnsignedIntegerValueread-writecurrentThis is the data point value formatted as an unsigned integer. This column is populated only for numerical data points whose type does not require a signed val…
1.3.6.1.4.1.476.1.42.3.9.30.1.30ColumnlgpFlexibleEntryDecimalPositionread-onlycurrentThis is a power of ten divider needed to convert values from the signed and unsigned integer columns (lgpFlexibleEntryIntegerValue or lgpFlexibleEntryUnsignedI…
1.3.6.1.4.1.476.1.42.3.9.30.1.40ColumnlgpFlexibleEntryDataTyperead-onlycurrentThe format that the data will appear as. This can be used to determine which field the numerical data will appear in. Data of type int16 and int32 will appear …
1.3.6.1.4.1.476.1.42.3.9.30.1.50ColumnlgpFlexibleEntryAccessibilityread-onlycurrentThis describes the read/write access that is available for the data in the row.
1.3.6.1.4.1.476.1.42.3.9.30.1.60ColumnlgpFlexibleEntryUnitsOfMeasureEnumread-onlycurrentThe unit of measurement that the value will be in.
1.3.6.1.4.1.476.1.42.3.9.30.1.70ColumnlgpFlexibleEntryDataDescriptionread-onlycurrentA description of the data reported in this row. This is generally longer and more thorough than the simple label described by lgpFlexibleEntryDataLabel.