LIEBERT-GP-PDU-MIB
198 objects
The MIB module used to register Liebert POWER related SNMP OIDs. Copyright 2008-2008 Liebert Corporation. All rights reserved. Reproduction of this document is authorized on the condition that the forgoing copyright notice is included. This Specification is supplied 'AS IS' and Liebert Corporation makes no warranty, either express or implied, as to the use, operation, condition, or performance of the Specification.
Imported Objects
| LIEBERT-GP-REGISTRATION-MIB | lgpPdu liebertPduModuleReg |
| SNMPv2-SMI | Integer32 MODULE-IDENTITY OBJECT-IDENTITY OBJECT-TYPE Unsigned32 |
| SNMPv2-TC | DisplayString |
| OID | Name | Access | Status | Description |
|---|---|---|---|---|
| 1.3.6.1.4.1.476.1.42.1.9.1 | IdentityliebertGlobalProductsPduModule | The MIB module used to register Liebert POWER related SNMP OIDs. Copyright 2008-2008 Liebert Corporation. All rights reserved. Reproduction of this document is… | ||
| 1.3.6.1.4.1.476.1.42.3.8.10 | IdentitylgpPduCluster | current | This sub-tree contains information about PDU clusters. Clusters are groups of PDU's under a single monitoring or control domain. | |
| 1.3.6.1.4.1.476.1.42.3.8.10.5 | ScalarlgpPduGrpSysStatus | read-only | current | This value represents a bit-field of the various operational states of the PDUs that are part of the cluster of PDUs being monitored by this agent. This value … |
| 1.3.6.1.4.1.476.1.42.3.8.19 | ScalarlgpPduTableCount | read-only | current | Number of PDUs being monitored by this agent. This is the number of entries in the lgpPduTable. |
| 1.3.6.1.4.1.476.1.42.3.8.20 | TablelgpPduTable | not-accessible | current | This table contains a list of PDU entries. The table contains zero, one, or many rows, depending upon the number of PDUs being monitored. The Network Managemen… |
| 1.3.6.1.4.1.476.1.42.3.8.20.1 | RowlgpPduEntry | not-accessible | current | This entry defines the columns to be populated in the 'lgpPduTable'. Each column represents an attribute of a PDU. This table is indexed by the PDU identifier … |
| 1.3.6.1.4.1.476.1.42.3.8.20.1.1 | ColumnlgpPduEntryIndex | not-accessible | current | This is the index that indicates the row of the 'lgpPduTable'. |
| 1.3.6.1.4.1.476.1.42.3.8.20.1.5 | ColumnlgpPduEntryId | read-only | current | This is an internal index representing a unique identifier for each PDU represented by this agent. The value is assigned by the agent. |
| 1.3.6.1.4.1.476.1.42.3.8.20.1.10 | ColumnlgpPduEntryUsrLabel | read-write | current | This is a user assigned label representing the PDU. |
| 1.3.6.1.4.1.476.1.42.3.8.20.1.15 | ColumnlgpPduEntrySysAssignLabel | read-only | current | System assigned identifier representing the PDU. The value is independent of any user assigned label or tag. The exact format of this label is system dependent… |
| 1.3.6.1.4.1.476.1.42.3.8.20.1.20 | ColumnlgpPduEntryPositionRelative | read-only | current | This is a one-based value that indicates the PDU's relative position within a rack or other enclosing entity. |
| 1.3.6.1.4.1.476.1.42.3.8.20.1.25 | ColumnlgpPduEntrySysStatus | read-only | current | This value represents a bit-field of the various operational states of the PDU. The value is a logical OR of all of the following potential states of the PDU. … |
| 1.3.6.1.4.1.476.1.42.3.8.20.1.35 | ColumnlgpPduEntryUsrTag1 | read-write | current | This is a user assigned Tag for the PDU. This value may be useful for end-user grouping or asset tracking purposes. The value for this tag does not need to be … |
| 1.3.6.1.4.1.476.1.42.3.8.20.1.40 | ColumnlgpPduEntryUsrTag2 | read-write | current | This is a user assigned Tag for the PDU. This value may be useful for end-user grouping or asset tracking purposes. The value for this tag does not need to be … |
| 1.3.6.1.4.1.476.1.42.3.8.20.1.45 | ColumnlgpPduEntrySerialNumber | read-only | current | System assigned serial number for this PDU. This number is assigned at time of manufacture, is globally unique with respect to all PDU units. |
| 1.3.6.1.4.1.476.1.42.3.8.20.1.50 | ColumnlgpPduEntryRbCount | read-only | current | Number of receptacle branches (Rb) within this PDU. |
| 1.3.6.1.4.1.476.1.42.3.8.30 | IdentitylgpPduPowerSource | current | This sub-tree contains information about PDU power sources. | |
| 1.3.6.1.4.1.476.1.42.3.8.30.19 | ScalarlgpPduPsTableCount | read-only | current | Number of power sources in the lgpPduPsTable. |
| 1.3.6.1.4.1.476.1.42.3.8.30.20 | TablelgpPduPsTable | not-accessible | current | This table contains a list of the PDU's power source(s). The table contains zero, one, or more rows, depending upon the number of PDUs being monitored and the … |
| 1.3.6.1.4.1.476.1.42.3.8.30.20.1 | RowlgpPduPsEntry | not-accessible | current | This entry defines the attributes to be populated in the various columns of the 'lgpPduPsTable' (Power Source Table). This table is indexed by both the 'lgpPdu… |
| 1.3.6.1.4.1.476.1.42.3.8.30.20.1.5 | ColumnlgpPduPsEntryIndex | not-accessible | current | This is a unique identifier for the Power Source within a given PDU. This is one of two indexes used to indicate the row of the 'lgpPduTable'. |
| 1.3.6.1.4.1.476.1.42.3.8.30.20.1.10 | ColumnlgpPduPsEntryId | read-only | current | This is a unique entry id representing a given PDU power source for the PDU. |
| 1.3.6.1.4.1.476.1.42.3.8.30.20.1.15 | ColumnlgpPduPsEntrySysAssignLabel | read-only | current | System assigned identifier for this power source. The value is independent of any user assigned label or tag. The exact format of this label is system dependen… |
| 1.3.6.1.4.1.476.1.42.3.8.30.20.1.20 | ColumnlgpPduPsEntryModel | read-only | current | This is the model name (identifier) of the power supply. |
| 1.3.6.1.4.1.476.1.42.3.8.30.20.1.25 | ColumnlgpPduPsEntryWiringType | read-write | current | The PDU's power supply physical wiring type. not-specified The type has not been specified/configured. The end_user must configure this object to specify the p… |
| 1.3.6.1.4.1.476.1.42.3.8.30.20.1.30 | ColumnlgpPduPsEntryEpInputRated | read-only | current | Rated Input Line Voltage for the power source (i.e. this is the nominal line input voltage; it is NOT a measured voltage). The value is defined to be the rated… |
| 1.3.6.1.4.1.476.1.42.3.8.30.20.1.35 | ColumnlgpPduPsEntryEcInputRated | read-only | current | This is the rated input line current for the module (it is NOT the measured current). |
| 1.3.6.1.4.1.476.1.42.3.8.30.20.1.40 | ColumnlgpPduPsEntryFreqRated | read-only | current | Rated input line frequency for this power source (i.e. This is the expected line frequency; it is NOT a measured frequency; it is typically 50 Hz or 60 Hz). |
| 1.3.6.1.4.1.476.1.42.3.8.30.20.1.50 | ColumnlgpPduPsEntryEnergyAccum | read-write | current | Total accumulated energy, measured at the power source input, since the last energy reset. Writing a value of 0 (zero) to this causes the accumulated energy to… |
| 1.3.6.1.4.1.476.1.42.3.8.30.20.1.55 | ColumnlgpPduPsEntrySerialNum | read-only | current | This is a unique serial number of the power supply. This number is assigned to the power supply at the time of manufacture. |
| 1.3.6.1.4.1.476.1.42.3.8.30.20.1.60 | ColumnlgpPduPsEntryFirmwareVersion | read-only | current | This is the version of the firmware installed on the PDU's power supply. |
| 1.3.6.1.4.1.476.1.42.3.8.30.20.1.65 | ColumnlgpPduPsEntryPwrTotal | read-only | current | Total input power for this power supply. This is the sum of the power for all phases |
| 1.3.6.1.4.1.476.1.42.3.8.30.20.1.70 | ColumnlgpPduPsEntryEcNeutral | read-only | current | The neutral current measured at the PDU's power source. |
| 1.3.6.1.4.1.476.1.42.3.8.30.20.1.75 | ColumnlgpPduPsEntryEcNeutralThrshldOvrWarn | read-write | current | The threshold at which an over current warning is activated. If the measured neutral current (lgpPduPsEntryEcNeutral) is above this percentage of the full scal… |
| 1.3.6.1.4.1.476.1.42.3.8.30.20.1.80 | ColumnlgpPduPsEntryEcNeutralThrshldOvrAlarm | read-write | current | The threshold at which an over current alarm is activated. If the measured neutral current (lgpPduPsEntryEcNeutral) is above this percentage of the full scale … |
| 1.3.6.1.4.1.476.1.42.3.8.30.40 | TablelgpPduPsLineTable | not-accessible | current | This table contains a list of PDU's power source line/phase measurements. The table contains zero, one, or many rows, depending upon the number of PDU's Power … |
| 1.3.6.1.4.1.476.1.42.3.8.30.40.1 | RowlgpPduPsLineEntry | not-accessible | current | This entry defines the attributes to be populated in the various columns of the 'lgpPduPsLineTable'. The table is index by three indexes which taken together u… |
| 1.3.6.1.4.1.476.1.42.3.8.30.40.1.5 | ColumnlgpPduPsLineEntryIndex | not-accessible | current | This is the index that indicates the line/phase of the measurements in the given row of the 'lgpPduPsLineTable'. |
| 1.3.6.1.4.1.476.1.42.3.8.30.40.1.10 | ColumnlgpPduPsLineEntryId | read-only | current | Unique identifier (within a PDU) for the PDU's power source. The object may not be available in non-modular systems. |
| 1.3.6.1.4.1.476.1.42.3.8.30.40.1.15 | ColumnlgpPduPsLineEntryLine | read-only | current | The line number (phase) that the measurement represents for all measurements in a given row of the table. Note that this always matches the lgpPduPsLineEntryIn… |
| 1.3.6.1.4.1.476.1.42.3.8.30.40.1.19 | ColumnlgpPduPsLineEntryEpLNTenths | read-only | current | Alternating Current RMS Line to Neutral Electrical Potential measurement. The line/phase being measured is indicated by the corresponding lgpPduPsLineEntryLine… |
| 1.3.6.1.4.1.476.1.42.3.8.30.40.1.20 | ColumnlgpPduPsLineEntryEpLN | read-only | current | Alternating Current RMS Line to Neutral Electrical Potential measurement. The line/phase being measured is indicated by the corresponding lgpPduPsLineEntryLine… |
| 1.3.6.1.4.1.476.1.42.3.8.30.40.1.21 | ColumnlgpPduPsLineEntryEc | read-only | current | Total input line-to-neutral electrical current. The line/phase being measured is indicated by the corresponding lgpPduPsLineEntryLine value of this row in the … |
| 1.3.6.1.4.1.476.1.42.3.8.30.40.1.22 | ColumnlgpPduPsLineEntryEcHundredths | read-only | current | Total input line-to-neutral electrical current. The line/phase being measured is indicated by the corresponding lgpPduPsLineEntryLine value of this row in the … |
| 1.3.6.1.4.1.476.1.42.3.8.30.40.1.35 | ColumnlgpPduPsLineEntryEcThrshldUndrAlarm | read-write | current | The threshold at which an under current alarm is activated. If the measured current (lgpPduPsLineEntryEc) is equal to or below this percentage of the full scal… |
| 1.3.6.1.4.1.476.1.42.3.8.30.40.1.36 | ColumnlgpPduPsLineEntryEcThrshldOvrWarn | read-write | current | The threshold at which an over current warning is activated. If the measured current (lgpPduPsLineEntryEc) is equal to or over this percentage of the full scal… |
| 1.3.6.1.4.1.476.1.42.3.8.30.40.1.37 | ColumnlgpPduPsLineEntryEcThrshldOvrAlarm | read-write | current | The threshold at which an over current alarm is activated. If the measured current (lgpPduPsLineEntryEc) is equal to or over this percentage of the full scale … |
| 1.3.6.1.4.1.476.1.42.3.8.30.40.1.38 | ColumnlgpPduPsLineEntryEcAvailBeforeAlarm | read-only | current | The amount that the current/amperage may increase from its present value before an over current alarm occurs. |
| 1.3.6.1.4.1.476.1.42.3.8.30.40.1.39 | ColumnlgpPduPsLineEntryEcUsedBeforeAlarm | read-only | current | The percent of current utilization relative to the over current alarm threshold. |
| 1.3.6.1.4.1.476.1.42.3.8.30.40.1.60 | ColumnlgpPduPsLineEntryEpLL | read-only | current | Line to Line Electrical Potential. The line/phase being measured is indicated by the corresponding lgpPduPsLineEntryLine value of this row in the table. |
| 1.3.6.1.4.1.476.1.42.3.8.30.40.1.61 | ColumnlgpPduPsLineEntryEpLLTenths | read-only | current | Line to Line Electrical Potential. The line/phase being measured is indicated by the corresponding lgpPduPsLineEntryLine value of this row in the table. |
| 1.3.6.1.4.1.476.1.42.3.8.30.40.1.62 | ColumnlgpPduPsLineEntryEcAvailBeforeAlarmHundredths | read-only | current | The amount that the current/amperage may increase from its present value before an over current alarm occurs. |
| 1.3.6.1.4.1.476.1.42.3.8.40 | IdentitylgpPduReceptacleBranch | current | This sub-tree contains information about PDU receptacle branches. | |
| 1.3.6.1.4.1.476.1.42.3.8.40.19 | ScalarlgpPduRbTableCount | read-only | current | Number of receptacle branches in the lgpPduRbTable. |
| 1.3.6.1.4.1.476.1.42.3.8.40.20 | TablelgpPduRbTable | not-accessible | current | This table contains a list of PDU Receptacle branches. The table contains zero, one, or many rows, depending upon the number of PDUs being managed and how many… |
| 1.3.6.1.4.1.476.1.42.3.8.40.20.1 | RowlgpPduRbEntry | not-accessible | current | This entry defines the attributes to be populated in the various columns of the 'lgpPduRbTable'. The table is indexed by both the 'lgpPduEntryIndex' and 'lgpPd… |
| 1.3.6.1.4.1.476.1.42.3.8.40.20.1.1 | ColumnlgpPduRbEntryIndex | not-accessible | current | This is the index that indicates the row of the 'lgpPduRbTable' |
| 1.3.6.1.4.1.476.1.42.3.8.40.20.1.5 | ColumnlgpPduRbEntryId | read-only | current | A unique id representing the receptacle branch within the collection of branches being monitored by this agent. The uniqueness of this id is within the PDUs be… |
| 1.3.6.1.4.1.476.1.42.3.8.40.20.1.8 | ColumnlgpPduRbEntryUsrLabel | read-write | current | A user assigned label representing the receptacle branch. |
| 1.3.6.1.4.1.476.1.42.3.8.40.20.1.20 | ColumnlgpPduRbEntrySysAssignLabel | read-only | current | System assigned identifier for this receptacle branch. The value is independent of any user assigned label or tag. The exact format of this label is system dep… |
| 1.3.6.1.4.1.476.1.42.3.8.40.20.1.25 | ColumnlgpPduRbEntryPositionRelative | read-only | current | This is a one-based value that indicates the relative position of the branch within the PDU. |
| 1.3.6.1.4.1.476.1.42.3.8.40.20.1.30 | ColumnlgpPduRbEntrySerialNum | read-only | current | A globally unique serial number for this branch. This number is assigned to the branch at the time of manufacture and can not be modified. NOTE: Generally only… |
| 1.3.6.1.4.1.476.1.42.3.8.40.20.1.35 | ColumnlgpPduRbEntryModel | read-only | current | This is the model designation for this receptacle branch. |
| 1.3.6.1.4.1.476.1.42.3.8.40.20.1.40 | ColumnlgpPduRbEntryFirmwareVersion | read-only | current | This is the firmware version number of the control software running on the receptacle branch. Only PDUs with replaceable receptacle branches will typically sup… |
| 1.3.6.1.4.1.476.1.42.3.8.40.20.1.41 | ColumnlgpPduRbEntryUsrTag1 | read-write | current | This is a user assigned Tag for the receptacle branch. This value may be useful for end-user grouping or asset tracking purposes. The value for this tag does n… |
| 1.3.6.1.4.1.476.1.42.3.8.40.20.1.42 | ColumnlgpPduRbEntryUsrTag2 | read-write | current | This is a user assigned Tag for the receptacle branch. This value may be useful for end-user grouping or asset tracking purposes. The value for this tag does n… |
| 1.3.6.1.4.1.476.1.42.3.8.40.20.1.45 | ColumnlgpPduRbEntryReceptacleType | read-only | current | This enumeration represents the type of receptacles installed on this receptacle branch. All receptacles on this branch are of this type/style. not-specified I… |
| 1.3.6.1.4.1.476.1.42.3.8.40.20.1.50 | ColumnlgpPduRbEntryCapabilities | read-only | current | Receptacle branch capabilities describes what an individual branch is capable of. no-optional-capabilities The branch is unable to report measurements and lack… |
| 1.3.6.1.4.1.476.1.42.3.8.40.20.1.55 | ColumnlgpPduRbEntryLineSource | read-only | current | This represents the line source that is supplying power to this receptacle branch. not-specified The line source supplying power to the load for this receptacl… |
| 1.3.6.1.4.1.476.1.42.3.8.40.20.1.60 | ColumnlgpPduRbEntryRcpCount | read-only | current | The number of receptacles on this receptacle branch. |
| 1.3.6.1.4.1.476.1.42.3.8.40.20.1.70 | ColumnlgpPduRbEntryEpRated | read-only | current | Rated Line Voltage for the receptacle branch and its associated receptacles (i.e. This is the nominal line voltage that is available to the connected load; it … |
| 1.3.6.1.4.1.476.1.42.3.8.40.20.1.75 | ColumnlgpPduRbEntryEcRated | read-only | current | This is the rated input line current for the module (it is NOT the measured current). |
| 1.3.6.1.4.1.476.1.42.3.8.40.20.1.80 | ColumnlgpPduRbEntryFreqRated | read-only | current | This is the rated electrical frequency for the receptacle branch and its associated receptacles |
| 1.3.6.1.4.1.476.1.42.3.8.40.20.1.85 | ColumnlgpPduRbEntryEnergyAccum | read-write | current | Total accumulated energy, measured at the receptacle branch input, since the last energy reset. Writing a value of 0 (zero) to this causes the accumulated ener… |
| 1.3.6.1.4.1.476.1.42.3.8.40.20.1.100 | ColumnlgpPduRbEntryEpLNTenths | read-only | current | The line-to-neutral measurement of the Electrical Potential measured in Volts RMS (Root Mean Squared). |
| 1.3.6.1.4.1.476.1.42.3.8.40.20.1.115 | ColumnlgpPduRbEntryPwr | read-only | current | The line-to-neutral measurement of the Real Power (Wattage) |
| 1.3.6.1.4.1.476.1.42.3.8.40.20.1.120 | ColumnlgpPduRbEntryAp | read-only | current | The line-to-neutral measurement of the Apparent Power (VA) |
| 1.3.6.1.4.1.476.1.42.3.8.40.20.1.125 | ColumnlgpPduRbEntryPf | read-only | current | The line-to-neutral measurement of the Power Factor of the receptacle branches' input. |
| 1.3.6.1.4.1.476.1.42.3.8.40.20.1.130 | ColumnlgpPduRbEntryEcHundredths | read-only | current | The line-to-neutral measurement of the Electrical Current measured in Amperes RMS (Root Mean Squared). |
| 1.3.6.1.4.1.476.1.42.3.8.40.20.1.135 | ColumnlgpPduRbEntryEcThrshldUndrAlm | read-write | current | The threshold at which an under current alarm is activated. If the measured current (lgpPduRbEntryEc) is equal to or below this percentage of the full scale ra… |
| 1.3.6.1.4.1.476.1.42.3.8.40.20.1.140 | ColumnlgpPduRbEntryEcThrshldOvrWarn | read-write | current | The threshold at which an over current warning is activated. If the measured current (lgpPduRbEntryEc) is equal to or over this percentage of the full scale ra… |
| 1.3.6.1.4.1.476.1.42.3.8.40.20.1.145 | ColumnlgpPduRbEntryEcThrshldOvrAlm | read-write | current | The threshold at which an over current alarm is activated. If the measured current (lgpPduRbEntryEcLN) is equal to or over this percentage of the full scale ra… |
| 1.3.6.1.4.1.476.1.42.3.8.40.20.1.150 | ColumnlgpPduRbEntryEcAvailBeforeAlarmHundredths | read-only | current | The amount that the current/amperage may increase from its present value before an over current alarm occurs. |
| 1.3.6.1.4.1.476.1.42.3.8.40.20.1.160 | ColumnlgpPduRbEntryEcUsedBeforeAlarm | read-only | current | The percent of current utilization relative to the over current alarm threshold. |
| 1.3.6.1.4.1.476.1.42.3.8.40.20.1.170 | ColumnlgpPduRbEntryEpLLTenths | read-only | current | The line-to-line measurement of the Electrical Potential measured in Volts RMS (Root Mean Squared). |
| 1.3.6.1.4.1.476.1.42.3.8.40.40 | TablelgpPduRbLineTable | not-accessible | deprecated | This table contains a list of PDU receptacle branch line/phase measurements. The table contains zero, one, or many rows, depending upon the number of PDUs and … |
| 1.3.6.1.4.1.476.1.42.3.8.40.40.1 | RowlgpPduRbLineEntry | not-accessible | deprecated | This entry defines the attributes to be populated in the various columns of the 'lgpPduRbLineTable'. The table is indexed by three indexes. The 'lgpPduEntryInd… |
| 1.3.6.1.4.1.476.1.42.3.8.40.40.1.1 | ColumnlgpPduRbLineEntryIndex | not-accessible | deprecated | This is the index that indicates the row of the 'lgpPduRbLineTable' |
| 1.3.6.1.4.1.476.1.42.3.8.40.40.1.5 | ColumnlgpPduRbLineEntryId | read-only | deprecated | Runtime assigned branch identifier. |
| 1.3.6.1.4.1.476.1.42.3.8.40.40.1.10 | ColumnlgpPduRbLineEntryLine | read-only | deprecated | The line number or phase that the measurement for this receptacle branch represents for each measurement in this row of the table. The phases are as follows: L… |
| 1.3.6.1.4.1.476.1.42.3.8.40.40.1.19 | ColumnlgpPduRbLineEntryEpLNTenths | read-only | deprecated | The line-to-neutral measurement of the Electrical Potential measured in Volts RMS (Root Mean Squared). |
| 1.3.6.1.4.1.476.1.42.3.8.40.40.1.20 | ColumnlgpPduRbLineEntryEpLN | read-only | deprecated | The line-to-neutral measurement of the Electrical Potential measured in Volts RMS (Root Mean Squared). |
| 1.3.6.1.4.1.476.1.42.3.8.40.40.1.21 | ColumnlgpPduRbLineEntryEc | read-only | deprecated | The line-to-neutral measurement of the Electrical Current measured in Amperes RMS (Root Mean Squared). |
| 1.3.6.1.4.1.476.1.42.3.8.40.40.1.22 | ColumnlgpPduRbLineEntryPwr | read-only | deprecated | The line-to-neutral measurement of the Real Power (Wattage) |
| 1.3.6.1.4.1.476.1.42.3.8.40.40.1.23 | ColumnlgpPduRbLineEntryAp | read-only | deprecated | The line-to-neutral measurement of the Apparent Power (VA) |
| 1.3.6.1.4.1.476.1.42.3.8.40.40.1.24 | ColumnlgpPduRbLineEntryPf | read-only | deprecated | The line-to-neutral measurement of the Power Factor of the receptacle branches' input. |
| 1.3.6.1.4.1.476.1.42.3.8.40.40.1.25 | ColumnlgpPduRbLineEntryEcHundredths | read-only | deprecated | The line-to-neutral measurement of the Electrical Current measured in Amperes RMS (Root Mean Squared). |
| 1.3.6.1.4.1.476.1.42.3.8.40.40.1.35 | ColumnlgpPduRbLineEntryEcThrshldUndrAlm | read-write | deprecated | The threshold at which an under current alarm is activated. If the measured current (lgpPduRbLineEntryEc) is equal to or below this percentage of the full scal… |
| 1.3.6.1.4.1.476.1.42.3.8.40.40.1.36 | ColumnlgpPduRbLineEntryEcThrshldOvrWarn | read-write | deprecated | The threshold at which an over current warning is activated. If the measured current (lgpPduRbLineEntryEc) is equal to or over this percentage of the full scal… |
| 1.3.6.1.4.1.476.1.42.3.8.40.40.1.37 | ColumnlgpPduRbLineEntryEcThrshldOvrAlm | read-write | deprecated | The threshold at which an over current alarm is activated. If the measured current (lgpPduRbLineEntryEcLN) is equal to or over this percentage of the full scal… |
| 1.3.6.1.4.1.476.1.42.3.8.40.40.1.39 | ColumnlgpPduRbLineEntryEcAvailBeforeAlarmHundredths | read-only | deprecated | The amount that the current/amperage may increase from its present value before an over current alarm occurs. |
| 1.3.6.1.4.1.476.1.42.3.8.40.40.1.40 | ColumnlgpPduRbLineEntryEcAvailBeforeAlarm | read-only | deprecated | The amount that the current/amperage may increase from its present value before an over current alarm occurs. |
| 1.3.6.1.4.1.476.1.42.3.8.40.40.1.41 | ColumnlgpPduRbLineEntryEcUsedBeforeAlarm | read-only | deprecated | The percent of current utilization relative to the over current alarm threshold. |
| 1.3.6.1.4.1.476.1.42.3.8.40.40.1.60 | ColumnlgpPduRbLineEntryEpLL | read-only | deprecated | The line-to-line measurement of the Electrical Potential measured in Volts RMS (Root Mean Squared). |
| 1.3.6.1.4.1.476.1.42.3.8.40.40.1.61 | ColumnlgpPduRbLineEntryEpLLTenths | read-only | deprecated | The line-to-line measurement of the Electrical Potential measured in Volts RMS (Root Mean Squared). |
| 1.3.6.1.4.1.476.1.42.3.8.50 | IdentitylgpPduReceptacle | current | This sub-tree contains information about PDU receptacles. | |
| 1.3.6.1.4.1.476.1.42.3.8.50.19 | ScalarlgpPduRcpTableCount | read-only | current | Number of receptacles in the lgpPduRcpTable. |
| 1.3.6.1.4.1.476.1.42.3.8.50.20 | TablelgpPduRcpTable | not-accessible | current | This table contains a list of PDU receptacle entries. The table contains numerous rows representing an individual receptacle, depending upon the number and con… |
| 1.3.6.1.4.1.476.1.42.3.8.50.20.1 | RowlgpPduRcpEntry | not-accessible | current | This entry defines the attributes to be populated in the various columns of the 'lgpPduRcpTable'. This table is indexed by three indexes. The 'lgpPduEntryIndex… |
| 1.3.6.1.4.1.476.1.42.3.8.50.20.1.1 | ColumnlgpPduRcpEntryIndex | not-accessible | current | This is the index that indicates the receptacle position on the receptacle branch. This along with the other two indexes on the lgpPduRcpTable uniquely identif… |
| 1.3.6.1.4.1.476.1.42.3.8.50.20.1.5 | ColumnlgpPduRcpEntryId | read-only | current | A runtime assigned receptacle identification number. |
| 1.3.6.1.4.1.476.1.42.3.8.50.20.1.10 | ColumnlgpPduRcpEntryUsrLabel | read-write | current | User assigned label for this receptacle. |
| 1.3.6.1.4.1.476.1.42.3.8.50.20.1.15 | ColumnlgpPduRcpEntryUsrTag1 | read-write | current | User assigned Tag to assist in identifying or grouping this receptacle within the end-users domain. |
| 1.3.6.1.4.1.476.1.42.3.8.50.20.1.20 | ColumnlgpPduRcpEntryUsrTag2 | read-write | current | User assigned Tag to assist in identifying or grouping this receptacle within the end-users domain. |
| 1.3.6.1.4.1.476.1.42.3.8.50.20.1.25 | ColumnlgpPduRcpEntrySysAssignLabel | read-only | current | System assigned identifier representing the receptacle. The value is independent of any user assigned label or tag. The exact format of this label is system de… |
| 1.3.6.1.4.1.476.1.42.3.8.50.20.1.30 | ColumnlgpPduRcpEntryPosition | read-only | current | A number representing the position of the receptacle within the receptacle branch. |
| 1.3.6.1.4.1.476.1.42.3.8.50.20.1.40 | ColumnlgpPduRcpEntryType | read-only | current | The type or form of receptacle. The enumerations are specified in well-known industry standard terms and abbreviations. |
| 1.3.6.1.4.1.476.1.42.3.8.50.20.1.45 | ColumnlgpPduRcpEntryLineSource | read-only | current | This represents the line source that is supplying power to this receptacle. not-specified The line source supplying power to the load for this receptacle has n… |
| 1.3.6.1.4.1.476.1.42.3.8.50.20.1.50 | ColumnlgpPduRcpEntryCapabilities | read-only | current | Receptacle capabilities describes what an individual receptacle is capable of. no-optional-capabilities The receptacle is unable to report measurements and lac… |
| 1.3.6.1.4.1.476.1.42.3.8.50.20.1.55 | ColumnlgpPduRcpEntryEp | read-only | current | Voltage being delivered to the load attached to the receptacle. Alternating Current RMS Electrical Potential measurement. |
| 1.3.6.1.4.1.476.1.42.3.8.50.20.1.56 | ColumnlgpPduRcpEntryEpTenths | read-only | current | Voltage being delivered to the load attached to the receptacle. Alternating Current RMS Electrical Potential measurement. |
| 1.3.6.1.4.1.476.1.42.3.8.50.20.1.60 | ColumnlgpPduRcpEntryEc | read-only | current | Current (amperage) being delivered to the load attached to the receptacle. Electrical Current is measured in Amperes RMS (Root Mean Squared). |
| 1.3.6.1.4.1.476.1.42.3.8.50.20.1.61 | ColumnlgpPduRcpEntryEcHundredths | read-only | current | Current (amperage) being delivered to the load attached to the receptacle. Electrical Current is measured in Amperes RMS (Root Mean Squared). |
| 1.3.6.1.4.1.476.1.42.3.8.50.20.1.65 | ColumnlgpPduRcpEntryPwrOut | read-only | current | Real Power (watts) being delivered to the load attached to the receptacle. |
| 1.3.6.1.4.1.476.1.42.3.8.50.20.1.70 | ColumnlgpPduRcpEntryApOut | read-only | current | Apparent Power (volt-amps) being delivered to the load attached to the receptacle. |
| 1.3.6.1.4.1.476.1.42.3.8.50.20.1.75 | ColumnlgpPduRcpEntryPf | read-only | current | Receptacle Power Factor, which is the ratio of real power to apparent power (i.e. ratio of watts to volts-amps). |
| 1.3.6.1.4.1.476.1.42.3.8.50.20.1.80 | ColumnlgpPduRcpEntryFreq | read-only | current | The measured line frequency being delivered to the load attached to the receptacle. |
| 1.3.6.1.4.1.476.1.42.3.8.50.20.1.85 | ColumnlgpPduRcpEntryEnergyAccum | read-write | current | Total accumulated energy, measured at the module input, since the last energy reset. Writing a value of 0 (zero) to this causes the accumulated energy to be re… |
| 1.3.6.1.4.1.476.1.42.3.8.50.20.1.90 | ColumnlgpPduRcpEntryPwrOnDelay | read-write | current | The amount of time to wait before power is applied to the receptacle after a power strip is turned on or rebooted. This can be used to stagger the powering of … |
| 1.3.6.1.4.1.476.1.42.3.8.50.20.1.95 | ColumnlgpPduRcpEntryPwrState | read-only | current | unknown The current power state is unknown. off The current power state of the receptacle is OFF. on The current power state of the receptacle is ON. off-pendi… |
| 1.3.6.1.4.1.476.1.42.3.8.50.20.1.100 | ColumnlgpPduRcpEntryControl | read-write | current | This object represents the current and persistent (configured) power state of the receptacle. The receptacle can also be controlled by writing to this object. … |
| 1.3.6.1.4.1.476.1.42.3.8.50.20.1.105 | ColumnlgpPduRcpEntryControlLock | read-write | current | This object represents the locked state of the receptacle. unknown The lock state of the receptacle is not known at this time. locked If the receptacle is 'loc… |
| 1.3.6.1.4.1.476.1.42.3.8.50.20.1.150 | ColumnlgpPduRcpEntryEcThrshldUnderAlarm | read-write | current | The threshold at which an under current alarm is activated. If the measured current (lgpPduRbLineEntryEcLL) is equal to or below this percentage of the full sc… |
| 1.3.6.1.4.1.476.1.42.3.8.50.20.1.151 | ColumnlgpPduRcpEntryEcThrshldOverWarn | read-write | current | The threshold at which an over current warning is activated. If the measured current (lgpPduRbLineEntryEcLL) is equal to or over this percentage of the full sc… |
| 1.3.6.1.4.1.476.1.42.3.8.50.20.1.152 | ColumnlgpPduRcpEntryEcThrshldOverAlarm | read-write | current | The threshold at which an over current alarm is activated. If the measured current (lgpPduRbLineEntryEcLL) is equal to or over this percentage of the full scal… |
| 1.3.6.1.4.1.476.1.42.3.8.50.20.1.159 | ColumnlgpPduRcpEntryEcAvailBeforeAlarmHundredths | read-only | current | The amount that the current/amperage may increase from its present value before an over current alarm occurs. |
| 1.3.6.1.4.1.476.1.42.3.8.50.20.1.160 | ColumnlgpPduRcpEntryEcAvailBeforeAlarm | read-only | current | The amount that the current/amperage may increase from its present value before an over current alarm occurs. |
| 1.3.6.1.4.1.476.1.42.3.8.50.20.1.161 | ColumnlgpPduRcpEntryEcUsedBeforeAlarm | read-only | current | The percent of current utilization relative to the over current alarm threshold. |
| 1.3.6.1.4.1.476.1.42.3.8.50.20.1.162 | ColumnlgpPduRcpEntryEcCrestFactor | read-only | current | Receptacle current crest factor, which is the peak amplitude of the current waveform divided by the RMS value of the waveform. |
| 1.3.6.1.4.1.476.1.42.3.8.50.20.1.200 | ColumnlgpPduRcpEntryBlinkLED | read-write | current | Blink the receptacle LED. Writing blinkLED(2) will cause the LED to blink for a predefined duration of time. Reading this object will always return noAction(1). |
| 1.3.6.1.4.1.476.1.42.3.8.60 | IdentitylgpPduAuxiliarySensors | current | This sub-tree contains information about PDU Auxiliary Sensors. | |
| 1.3.6.1.4.1.476.1.42.3.8.60.5 | ScalarlgpPduAuxSensorCount | read-only | current | Number of auxiliary sensors in the lgpPduAuxSensorTable. |
| 1.3.6.1.4.1.476.1.42.3.8.60.10 | TablelgpPduAuxSensorTable | not-accessible | deprecated | This table contains a list of the PDU's Auxiliary Sensors. The table contains zero, one, or more rows, depending upon the number of PDUs being monitored and th… |
| 1.3.6.1.4.1.476.1.42.3.8.60.10.1 | RowlgpPduAuxSensorEntry | not-accessible | deprecated | This entry defines the attributes to be populated in the various columns of the 'lgpPduAuxSensorTable'. This table is indexed by both the 'lgpPduEntryIndex' wh… |
| 1.3.6.1.4.1.476.1.42.3.8.60.10.1.1 | ColumnlgpPduAuxSensorIndex | not-accessible | deprecated | This is the index indicating the nth element of the table. |
| 1.3.6.1.4.1.476.1.42.3.8.60.10.1.5 | ColumnlgpPduAuxSensorMeasType | read-only | deprecated | not-specified The type of sensor is unknown. temperature The sensor in this row of the table measures temperature. humidity The sensor in this row of the table… |
| 1.3.6.1.4.1.476.1.42.3.8.60.10.1.10 | ColumnlgpPduAuxSensorId | read-only | deprecated | System assigned auxiliary sensor identification number. The value assigned is product specific. |
| 1.3.6.1.4.1.476.1.42.3.8.60.10.1.15 | ColumnlgpPduAuxSensorSysAssignLabel | read-only | deprecated | Label assigned to the auxiliary sensor at runtime by the system. The value is independent of any user assigned label or asset tag. |
| 1.3.6.1.4.1.476.1.42.3.8.60.10.1.20 | ColumnlgpPduAuxSensorPositionRelative | read-only | deprecated | Auxiliary sensor relative position. This is a one-based value that indicates the sensor's position relative to the sensor string connector. |
| 1.3.6.1.4.1.476.1.42.3.8.60.10.1.25 | ColumnlgpPduAuxSensorUsrLabel | read-write | deprecated | User assigned auxiliary sensor label. |
| 1.3.6.1.4.1.476.1.42.3.8.60.10.1.30 | ColumnlgpPduAuxSensorUsrTag1 | read-write | deprecated | User assigned Tag to assist in identifying or grouping this auxiliary sensor within the end-users domain. |
| 1.3.6.1.4.1.476.1.42.3.8.60.10.1.35 | ColumnlgpPduAuxSensorUsrTag2 | read-write | deprecated | User assigned Tag to assist in identifying or grouping this auxiliary sensor within the end-users domain. |
| 1.3.6.1.4.1.476.1.42.3.8.60.10.1.40 | ColumnlgpPduAuxSensorTempSerialNum | read-only | deprecated | The temperature sensor's globally unique serial number assigned at the time of manufacture. |
| 1.3.6.1.4.1.476.1.42.3.8.60.10.1.45 | ColumnlgpPduAuxSensorHumSerialNum | read-only | deprecated | The humidity sensor's globally unique serial number assigned at the time of manufacture. |
| 1.3.6.1.4.1.476.1.42.3.8.60.10.1.50 | ColumnlgpPduAuxSensorTempMeasurementDegF | read-only | deprecated | Temperature measured at the temperature sensor reported in degrees Fahrenheit. |
| 1.3.6.1.4.1.476.1.42.3.8.60.10.1.55 | ColumnlgpPduAuxSensorTempThrshldUndrAlmDegF | read-write | deprecated | Under temperature alarm threshold. An alarm is activated if the temperature is equal to or below this value. |
| 1.3.6.1.4.1.476.1.42.3.8.60.10.1.60 | ColumnlgpPduAuxSensorTempThrshldOvrAlmDegF | read-write | deprecated | Over temperature alarm threshold. An alarm is activated if the temperature is equal to or above this value. |
| 1.3.6.1.4.1.476.1.42.3.8.60.10.1.65 | ColumnlgpPduAuxSensorTempThrshldUndrWarnDegF | read-write | deprecated | Under temperature warning threshold. A warning is activated if the temperature is equal to or below this value. |
| 1.3.6.1.4.1.476.1.42.3.8.60.10.1.70 | ColumnlgpPduAuxSensorTempThrshldOvrWarnDegF | read-write | deprecated | Over temperature warning threshold. A warning is activated if the temperature is equal to or above this value. |
| 1.3.6.1.4.1.476.1.42.3.8.60.10.1.75 | ColumnlgpPduAuxSensorTempMeasurementDegC | read-only | deprecated | Temperature measured at the temperature sensor reported in degrees Celsius. |
| 1.3.6.1.4.1.476.1.42.3.8.60.10.1.80 | ColumnlgpPduAuxSensorTempThrshldUndrAlmDegC | read-write | deprecated | Under temperature alarm threshold. An alarm is activated if the temperature is equal to or below this value. |
| 1.3.6.1.4.1.476.1.42.3.8.60.10.1.85 | ColumnlgpPduAuxSensorTempThrshldOvrAlmDegC | read-write | deprecated | Over temperature alarm threshold. An alarm is activated if the temperature is equal to or above this value. |
| 1.3.6.1.4.1.476.1.42.3.8.60.10.1.90 | ColumnlgpPduAuxSensorTempThrshldUndrWarnDegC | read-write | deprecated | Under temperature warning threshold. A warning is activated if the temperature is equal to or below this value. |
| 1.3.6.1.4.1.476.1.42.3.8.60.10.1.95 | ColumnlgpPduAuxSensorTempThrshldOvrWarnDegC | read-write | deprecated | Over temperature warning threshold. A warning is activated if the temperature is equal to or above this value. |
| 1.3.6.1.4.1.476.1.42.3.8.60.10.1.100 | ColumnlgpPduAuxSensorHumMeasurement | read-only | deprecated | Relative Humidity measured at the humidity sensor. |
| 1.3.6.1.4.1.476.1.42.3.8.60.10.1.105 | ColumnlgpPduAuxSensorHumThrshldUndrAlm | read-write | deprecated | Under relative humidity alarm threshold. An alarm is activated if the relative humidity is equal to or below this value. |
| 1.3.6.1.4.1.476.1.42.3.8.60.10.1.110 | ColumnlgpPduAuxSensorHumThrshldOvrAlm | read-write | deprecated | Over relative humidity alarm threshold. An alarm is activated if the relative humidity is equal to or above this value. |
| 1.3.6.1.4.1.476.1.42.3.8.60.10.1.115 | ColumnlgpPduAuxSensorHumThrshldUndrWarn | read-write | deprecated | Under relative humidity warning threshold. A warning is activated if the relative humidity is equal to or below this value. |
| 1.3.6.1.4.1.476.1.42.3.8.60.10.1.120 | ColumnlgpPduAuxSensorHumThrshldOvrWarn | read-write | deprecated | Over relative humidity warning threshold. A warning is activated if the relative humidity is equal to or above this value. |
| 1.3.6.1.4.1.476.1.42.3.8.60.15 | TablelgpPduAuxMeasTable | not-accessible | current | This table contains a list of the PDU's Auxiliary Sensor Measurements. The table contains zero, one, or more rows, depending upon the number of PDUs being moni… |
| 1.3.6.1.4.1.476.1.42.3.8.60.15.1 | RowlgpPduAuxMeasEntry | not-accessible | current | This entry defines the attributes to be populated in the various columns of the 'lgpPduAuxMeasTable'. This table is indexed by 'lgpPduEntryIndex' which is the … |
| 1.3.6.1.4.1.476.1.42.3.8.60.15.1.1 | ColumnlgpPduAuxMeasSensorIndex | not-accessible | current | This is the index indicating the sensor the measurement is accessed from. |
| 1.3.6.1.4.1.476.1.42.3.8.60.15.1.5 | ColumnlgpPduAuxMeasSensorMeasurementIndex | not-accessible | current | This is the measurement's index identified on the sensor. |
| 1.3.6.1.4.1.476.1.42.3.8.60.15.1.10 | ColumnlgpPduAuxMeasType | read-only | current | not-specified The type of measurement is unknown. temperature The measurement in this row of the table measures temperature. humidity The measurement in this r… |
| 1.3.6.1.4.1.476.1.42.3.8.60.15.1.15 | ColumnlgpPduAuxMeasSensorSysAssignLabel | read-only | current | Label assigned to the auxiliary sensor at runtime by the system. The value is independent of any user assigned label or asset tag. |
| 1.3.6.1.4.1.476.1.42.3.8.60.15.1.20 | ColumnlgpPduAuxMeasUsrLabel | read-write | current | User assigned auxiliary sensor measurement label. |
| 1.3.6.1.4.1.476.1.42.3.8.60.15.1.25 | ColumnlgpPduAuxMeasUsrTag1 | read-write | current | User assigned Tag to assist in identifying or grouping this auxiliary sensor measurement within the end-users domain. |
| 1.3.6.1.4.1.476.1.42.3.8.60.15.1.30 | ColumnlgpPduAuxMeasUsrTag2 | read-write | current | User assigned Tag to assist in identifying or grouping this auxiliary sensor measurement within the end-users domain. |
| 1.3.6.1.4.1.476.1.42.3.8.60.15.1.35 | ColumnlgpPduAuxMeasSensorSerialNum | read-only | current | The sensor's globally unique serial number assigned at the time of manufacture. |
| 1.3.6.1.4.1.476.1.42.3.8.60.15.1.40 | ColumnlgpPduAuxMeasTempDegF | read-only | current | Temperature measured at the temperature sensor reported in degrees Fahrenheit. |
| 1.3.6.1.4.1.476.1.42.3.8.60.15.1.50 | ColumnlgpPduAuxMeasTempThrshldUndrAlmDegF | read-write | current | Under temperature alarm threshold. An alarm is activated if the temperature is equal to or below this value. |
| 1.3.6.1.4.1.476.1.42.3.8.60.15.1.55 | ColumnlgpPduAuxMeasTempThrshldOvrAlmDegF | read-write | current | Over temperature alarm threshold. An alarm is activated if the temperature is equal to or above this value. |
| 1.3.6.1.4.1.476.1.42.3.8.60.15.1.60 | ColumnlgpPduAuxMeasTempThrshldUndrWarnDegF | read-write | current | Under temperature warning threshold. A warning is activated if the temperature is equal to or below this value. |
| 1.3.6.1.4.1.476.1.42.3.8.60.15.1.65 | ColumnlgpPduAuxMeasTempThrshldOvrWarnDegF | read-write | current | Over temperature warning threshold. A warning is activated if the temperature is equal to or above this value. |
| 1.3.6.1.4.1.476.1.42.3.8.60.15.1.70 | ColumnlgpPduAuxMeasTempDegC | read-only | current | Temperature measured at the temperature sensor reported in degrees Celsius. |
| 1.3.6.1.4.1.476.1.42.3.8.60.15.1.75 | ColumnlgpPduAuxMeasTempThrshldUndrAlmDegC | read-write | current | Under temperature alarm threshold. An alarm is activated if the temperature is equal to or below this value. |
| 1.3.6.1.4.1.476.1.42.3.8.60.15.1.80 | ColumnlgpPduAuxMeasTempThrshldOvrAlmDegC | read-write | current | Over temperature alarm threshold. An alarm is activated if the temperature is equal to or above this value. |
| 1.3.6.1.4.1.476.1.42.3.8.60.15.1.85 | ColumnlgpPduAuxMeasTempThrshldUndrWarnDegC | read-write | current | Under temperature warning threshold. A warning is activated if the temperature is equal to or below this value. |
| 1.3.6.1.4.1.476.1.42.3.8.60.15.1.90 | ColumnlgpPduAuxMeasTempThrshldOvrWarnDegC | read-write | current | Over temperature warning threshold. A warning is activated if the temperature is equal to or above this value. |
| 1.3.6.1.4.1.476.1.42.3.8.60.15.1.95 | ColumnlgpPduAuxMeasHum | read-only | current | Relative Humidity measured at the humidity sensor. |
| 1.3.6.1.4.1.476.1.42.3.8.60.15.1.100 | ColumnlgpPduAuxMeasHumThrshldUndrAlm | read-write | current | Under relative humidity alarm threshold. An alarm is activated if the relative humidity is equal to or below this value. |
| 1.3.6.1.4.1.476.1.42.3.8.60.15.1.105 | ColumnlgpPduAuxMeasHumThrshldOvrAlm | read-write | current | Over relative humidity alarm threshold. An alarm is activated if the relative humidity is equal to or above this value. |
| 1.3.6.1.4.1.476.1.42.3.8.60.15.1.110 | ColumnlgpPduAuxMeasHumThrshldUndrWarn | read-write | current | Under relative humidity warning threshold. A warning is activated if the relative humidity is equal to or below this value. |
| 1.3.6.1.4.1.476.1.42.3.8.60.15.1.115 | ColumnlgpPduAuxMeasHumThrshldOvrWarn | read-write | current | Over relative humidity warning threshold. A warning is activated if the relative humidity is equal to or above this value. |
| 1.3.6.1.4.1.476.1.42.3.8.60.15.1.120 | ColumnlgpPduAuxMeasDrClosureState | read-only | current | The state of a door sensor measurement. not-specified The door state is unknown. open The door is in the open state. closed The door is in the closed state. |
| 1.3.6.1.4.1.476.1.42.3.8.60.15.1.125 | ColumnlgpPduAuxMeasDrClosureConfig | read-write | current | Configure door state alarms. This object provides the ability to select when a door closure measurement should cause an alarm. disabled The door state will nev… |
| 1.3.6.1.4.1.476.1.42.3.8.60.15.1.130 | ColumnlgpPduAuxMeasCntctClosureState | read-only | current | The state of a contact closure sensor measurement. not-specified The contact closure state is unknown. open The contact closure is in the open state. closed Th… |
| 1.3.6.1.4.1.476.1.42.3.8.60.15.1.135 | ColumnlgpPduAuxMeasCntctClosureConfig | read-write | current | Configure contact closure state alarms. This object provides the ability to select when a contact closure measurement should activate an alarm. disabled The co… |