MIB Viewer

LIEBERT-GP-POWER-MIB

258 objects
The MIB module used to register Liebert POWER related SNMP OIDs. Copyright 2000-2008 Liebert Corporation. All rights reserved. Reproduction of this document is authorized on the condition that the forgoing copyright notice is included. This Specification is supplied 'AS IS' and Liebert Corporation makes no warranty, either express or implied, as to the use, operation, condition, or performance of the Specification.
Imported Objects
LIEBERT-GP-REGISTRATION-MIBlgpPower liebertPowerModuleReg
SNMPv2-SMIInteger32 MODULE-IDENTITY OBJECT-IDENTITY OBJECT-TYPE Unsigned32
OIDNameAccessStatusDescription
1.3.6.1.4.1.476.1.42.1.6.1IdentityliebertGlobalProductsPowerModuleThe MIB module used to register Liebert POWER related SNMP OIDs. Copyright 2000-2008 Liebert Corporation. All rights reserved. Reproduction of this document is…
1.3.6.1.4.1.476.1.42.3.5.1IdentitylgpPwrBatterycurrentThis sub-tree is used to register Liebert Power Battery object identifiers.
1.3.6.1.4.1.476.1.42.3.5.1.1ScalarlgpPwrNumberInstalledBatteryModulesread-onlycurrentThe number of battery modules installed in the device.
1.3.6.1.4.1.476.1.42.3.5.1.2ScalarlgpPwrNumberFailedBatteryModulesread-onlycurrentThe number of battery modules in the device that have failed.
1.3.6.1.4.1.476.1.42.3.5.1.3ScalarlgpPwrNumberRedundantBatteryModulesread-onlycurrentThe number of redundant battery modules in the device.
1.3.6.1.4.1.476.1.42.3.5.1.4ScalarlgpPwrNumberActiveBatteryModulesread-onlycurrentThe number of active battery modules in the device.
1.3.6.1.4.1.476.1.42.3.5.1.5ScalarlgpPwrConfigLowBatteryWarningTimeread-writecurrentThe value of the device's estimated minutes of remaining battery at which a lgpEventLowBatteryWarning notification will be sent.
1.3.6.1.4.1.476.1.42.3.5.1.6ScalarlgpPwrNumberBatteryModuleWarningsread-onlycurrentThe number of battery modules in the device that have a warning.
1.3.6.1.4.1.476.1.42.3.5.1.7ScalarlgpPwrBatteryCountread-onlycurrentThe number of batteries installed.
1.3.6.1.4.1.476.1.42.3.5.1.8ScalarlgpPwrBatteryTestResultread-onlycurrentThe outcome of the previous battery test.
1.3.6.1.4.1.476.1.42.3.5.1.9ScalarlgpPwrNominalBatteryCapacityread-writecurrentThe nominal battery capacity of the system (in minutes) at full load.
1.3.6.1.4.1.476.1.42.3.5.1.10ScalarlgpPwrBatteryFloatVoltageread-writecurrentThe battery float voltage of the system.
1.3.6.1.4.1.476.1.42.3.5.1.11ScalarlgpPwrBatteryEndOfDischargeVoltageread-writecurrentThe battery voltage threshold at which the batteries are considered completely discharged.
1.3.6.1.4.1.476.1.42.3.5.1.12ScalarlgpPwrAutomaticBatteryTestIntervalread-writecurrentThe automatic battery test interval.
1.3.6.1.4.1.476.1.42.3.5.1.13ScalarlgpPwrAutomaticBatteryTestCountdownread-writecurrentThe time remaining before the next battery test.
1.3.6.1.4.1.476.1.42.3.5.1.14ScalarlgpPwrBatteryChargeStatusread-onlycurrentThe present state of the system's battery charge. A value of 'charging' indicates the batteries are currently charging. A value of 'discharging' indicates the …
1.3.6.1.4.1.476.1.42.3.5.1.15ScalarlgpPwrBatteryLifeEnhancerread-onlycurrentThe state of the battery life enhancer. When 'on', it will preserve battery life.
1.3.6.1.4.1.476.1.42.3.5.1.16ScalarlgpPwrBatteryChargerread-onlycurrentThe state of the battery charger.
1.3.6.1.4.1.476.1.42.3.5.1.17ScalarlgpPwrBatteryChargeModeread-onlycurrentThe mode of the battery charger: 'float' charging or 'equalize' charging.
1.3.6.1.4.1.476.1.42.3.5.1.18ScalarlgpPwrBatteryTimeRemainingread-onlycurrentAn estimate of the time to battery charge depletion under the present load conditions if the utility power is off and remains off, or if it were to be lost and…
1.3.6.1.4.1.476.1.42.3.5.1.19ScalarlgpPwrBatteryCapacityread-onlycurrentThe present percentage of battery capacity.
1.3.6.1.4.1.476.1.42.3.5.1.20IdentitylgpPwrBatteryCabinetcurrentThis sub-tree contains items related to battery cabinets.
1.3.6.1.4.1.476.1.42.3.5.1.20.1ScalarlgpPwrBatteryCabinetCountread-writecurrentThe number of battery cabinets installed with this device. Note some devices may not permit writing a value to this object.
1.3.6.1.4.1.476.1.42.3.5.1.20.2ScalarlgpPwrBatteryCabinetTyperead-writecurrentThe type of battery cabinet(s) installed on this device. Enumeration definitions: notSpecified - The type has not been specified in the device's configuration.…
1.3.6.1.4.1.476.1.42.3.5.1.20.3ScalarlgpPwrBatteryCabinetRatedCapacityread-writecurrentBattery cabinet rated capacity (tenths of Amp-hours). This assumes that each cabinet is of the same type and capacity. This is not a sum of the rating for all …
1.3.6.1.4.1.476.1.42.3.5.1.20.4ScalarlgpPwrBatteryLeadAcidCellCountread-writecurrentBattery cell count - lead-acid. The number of cells that comprise the lead acid battery string.
1.3.6.1.4.1.476.1.42.3.5.1.20.5ScalarlgpPwrBatteryNiCadCellCountread-writecurrentBattery cell count - nickel-cadmium. The number of cells that comprise the nickel-cadmium battery string.
1.3.6.1.4.1.476.1.42.3.5.1.21ScalarlgpPwrBatteryAmpHoursConsumedread-writecurrentThe cumulative battery Amp-hours withdrawn over the life of the battery. This value persists across reboots. Typically, this value is reset back to zero when t…
1.3.6.1.4.1.476.1.42.3.5.1.22ScalarlgpPwrBatteryAmpHoursDischargeConsumedread-writecurrentThe battery Amp-hours withdrawn during the current/latest discharge. This value does not persist across reboots.
1.3.6.1.4.1.476.1.42.3.5.1.23ScalarlgpPwrBatteryLastDischargeTimeread-writecurrentThe date and time of the last battery discharge. Typically this is the time when the discharge starts. This value persists across reboots. The date and time ar…
1.3.6.1.4.1.476.1.42.3.5.1.24ScalarlgpPwrBatteryLastCommissionTimeread-writecurrentThe date and time when the battery system was put into service. This information persists across system reboot events. It is the responsibility of Service to r…
1.3.6.1.4.1.476.1.42.3.5.1.25ScalarlgpPwrBatteryPresentDischargeTimeread-onlycurrentThe total time spent on battery during the current or last discharge. NOTE: While not discharging, some systems may display zero instead of the last discharge.
1.3.6.1.4.1.476.1.42.3.5.1.26ScalarlgpPwrBatteryCapacityStatusread-onlycurrentThe indication of the capacity remaining in the UPS system's batteries. NOTE: In a single-module system, this point is intended to have the same behavior as th…
1.3.6.1.4.1.476.1.42.3.5.1.27ScalarlgpPwrBatteryCircuitBreakerStateread-onlycurrentThe state of the Battery Circuit Breaker.
1.3.6.1.4.1.476.1.42.3.5.2IdentitylgpPwrMeasurementscurrentThis sub-tree registers Liebert Power Measurement object identifiers. The sub-tree contains tables and well known power measurement points.
1.3.6.1.4.1.476.1.42.3.5.2.1IdentitylgpPwrWellKnownMeasurementPointscurrentThis sub-tree registers well known Liebert Power Measurement Points. The object identifier names usually imply locations where the measurement is taken and 'by…
1.3.6.1.4.1.476.1.42.3.5.2.1.1IdentitylgpPwrSource1InputcurrentThis sub-tree is used to register a source 1 input as a well known measurement point. It is intended that no sub-trees be created below this node. Power input …
1.3.6.1.4.1.476.1.42.3.5.2.1.2IdentitylgpPwrSource2InputcurrentThis sub-tree is used to register a source 2 input as a well known measurement point. It is intended that no sub-trees be created below this node. Power input …
1.3.6.1.4.1.476.1.42.3.5.2.1.3IdentitylgpPwrSourcePdu1InputcurrentThis sub-tree is used to register a source PDU 1 input as a well known measurement point. It is intended that no sub-trees be created below this node. Power in…
1.3.6.1.4.1.476.1.42.3.5.2.1.4IdentitylgpPwrSourcePdu2InputcurrentThis sub-tree is used to register a source PDU 2 input as a well known measurement point. It is intended that no sub-trees be created below this node. Power in…
1.3.6.1.4.1.476.1.42.3.5.2.1.5IdentitylgpPwrOutputToLoadcurrentThis sub-tree is used to register the output to the critical load as a well known measurement point. It is intended that no sub-trees be created below this nod…
1.3.6.1.4.1.476.1.42.3.5.2.1.6IdentitylgpPwrMeasBatterycurrentThis sub-tree is used to register a battery as a well known measurement point. It is intended that no sub-trees be created below this node.
1.3.6.1.4.1.476.1.42.3.5.2.1.7IdentitylgpPwrMeasBypasscurrentThis sub-tree is used to register a bypass as a well known measurement point. It is intended that no sub-trees be created below this node.
1.3.6.1.4.1.476.1.42.3.5.2.1.8IdentitylgpPwrMeasDcBuscurrentThis sub-tree is used to register a DC bus as a well known measurement point. It is intended that no sub-trees be created below this node.
1.3.6.1.4.1.476.1.42.3.5.2.1.9IdentitylgpPwrMeasSystemOutputcurrentThis sub-tree is used to register the output of a multi-module system as a well known measurement point. It is intended that no sub-trees be created below this…
1.3.6.1.4.1.476.1.42.3.5.2.1.10IdentitylgpPwrMeasBatteryCabinetcurrentThis sub-tree is used to register the voltage between the most negative and the most postive terminals of a battery cabinet. To determine the cabinet being des…
1.3.6.1.4.1.476.1.42.3.5.2.2TablelgpPwrMeasurementPointTablenot-accessiblecurrentThis table contains a list of AC power measurement point entries. The table contains zero, one, or many rows, depending upon the number of power related measur…
1.3.6.1.4.1.476.1.42.3.5.2.2.1RowlgpPwrMeasurementPointEntrynot-accessiblecurrentThis entry defines the measurements to be populated in the various columns of the 'lgpPwrMeasurementPointTable'.
1.3.6.1.4.1.476.1.42.3.5.2.2.1.1ColumnlgpPwrMeasurementPointIndexnot-accessiblecurrentThis is the index that indicates the row of the 'lgpPwrMeasurementPointTable' for a power measurement point.
1.3.6.1.4.1.476.1.42.3.5.2.2.1.2ColumnlgpPwrMeasurementPointIdread-onlycurrentAn OID representing a well known measurement point. These object identifiers indicate a point or location of power measurement in a power system. The OID's nam…
1.3.6.1.4.1.476.1.42.3.5.2.2.1.3ColumnlgpPwrMeasurementPointNumLinesread-onlycurrentThe number of lines on the indicated power measurement point. (i.e. the number of phases on the power source being measured.)
1.3.6.1.4.1.476.1.42.3.5.2.2.1.4ColumnlgpPwrMeasurementPointNomVoltsread-onlycurrentThe magnitude of the nominal voltage on the power source being measured.
1.3.6.1.4.1.476.1.42.3.5.2.2.1.5ColumnlgpPwrMeasurementPointNomFrequencyread-onlycurrentThe nominal or configured/expected frequency for the power source indicated by 'lgpPwrMeasurementPointId' in the corresponding row in the lgpPwrMeasurementPoin…
1.3.6.1.4.1.476.1.42.3.5.2.2.1.6ColumnlgpPwrMeasurementPointFrequencyread-onlycurrentThe present (actual) frequency for the power source indicated by 'lgpPwrMeasurementPointId' in the corresponding row in the lgpPwrMeasurementPointTable.
1.3.6.1.4.1.476.1.42.3.5.2.2.1.7ColumnlgpPwrMeasurementPointApparentPowerread-onlycurrentThe present apparent AC power for the power source indicated by 'lgpPwrMeasurementPointId' in the corresponding row in the lgpPwrMeasurementPointTable.
1.3.6.1.4.1.476.1.42.3.5.2.2.1.8ColumnlgpPwrMeasurementPointTruePowerread-onlycurrentThe present AC power for the power source indicated by 'lgpPwrMeasurementPointId' in the corresponding row in the lgpPwrMeasurementPointTable.
1.3.6.1.4.1.476.1.42.3.5.2.2.1.9ColumnlgpPwrMeasurementPointPowerFactorread-onlycurrentThe present Power Factor for the power source indicated by 'lgpPwrMeasurementPointId' in the corresponding row in the lgpPwrMeasurementPointTable.
1.3.6.1.4.1.476.1.42.3.5.2.2.1.10ColumnlgpPwrMeasurementPointWattHoursread-onlycurrentThe present number of Watt Hours for the power source indicated by 'lgpPwrMeasurementPointId' in the corresponding row in the lgpPwrMeasurementPointTable.
1.3.6.1.4.1.476.1.42.3.5.2.2.1.11ColumnlgpPwrMeasurementPointVAPercentread-onlycurrentThe percentage of the rated apparent AC power of the power source indicated by 'lgpPwrMeasurementPointId' in the corresponding row in the lgpPwrMeasurementPoin…
1.3.6.1.4.1.476.1.42.3.5.2.2.1.12ColumnlgpPwrMeasurementPointNeutralCurrentread-onlycurrentThe present neutral current of the power point indicated by 'lgpPwrMeasurementPointId' in the corresponding row in the lgpPwrMeasurementPointTable.
1.3.6.1.4.1.476.1.42.3.5.2.2.1.13ColumnlgpPwrMeasurementPointGroundCurrentread-onlycurrentThe present ground current of the power point indicated by 'lgpPwrMeasurementPointId' in the corresponding row in the lgpPwrMeasurementPointTable.
1.3.6.1.4.1.476.1.42.3.5.2.2.1.14ColumnlgpPwrMeasurementPointNomCurrentread-onlycurrentThe nominal or configured/expected current of the power point indicated by 'lgpPwrMeasurementPointId' in the corresponding row in the lgpPwrMeasurementPointTab…
1.3.6.1.4.1.476.1.42.3.5.2.2.1.15ColumnlgpPwrMeasurementPointNomPowerFactorread-onlycurrentThe nominal or configured/expected power factor of the power point indicated by 'lgpPwrMeasurementPointId' in the corresponding row in the lgpPwrMeasurementPoi…
1.3.6.1.4.1.476.1.42.3.5.2.2.1.16ColumnlgpPwrMeasurementPointNomVAread-writecurrentThe nominal or configured/expected apparent AC power for the power source indicated by 'lgpPwrMeasurementPointId' in the corresponding row in the lgpPwrMeasure…
1.3.6.1.4.1.476.1.42.3.5.2.2.1.17ColumnlgpPwrMeasurementPointNomWread-writecurrentThe nominal or configured/expected true AC power for the power source indicated by 'lgpPwrMeasurementPointId' in the corresponding row in the lgpPwrMeasurement…
1.3.6.1.4.1.476.1.42.3.5.2.2.1.19ColumnlgpPwrMeasurementPointPowerFactorTagread-onlycurrentThe present description of the Power Factor for the power source indicated by 'lgpPwrMeasurementPointId' in the corresponding row in the lgpPwrMeasurementPoint…
1.3.6.1.4.1.476.1.42.3.5.2.3TablelgpPwrLineMeasurementTablenot-accessiblecurrentA list of power measurements for each phase/line for a given power measurement point/location in the 'lgpPwrMeasurementPointTable'. The lgpPwrMeasurementPointI…
1.3.6.1.4.1.476.1.42.3.5.2.3.1RowlgpPwrLineMeasurementEntrynot-accessiblecurrentThis entry defines the contents of the columns for the table 'lgpPwrLineMeasurementTable'.
1.3.6.1.4.1.476.1.42.3.5.2.3.1.1ColumnlgpPwrMeasurementPtIndexnot-accessiblecurrentThis is the index indicating the row of the table 'lgpPwrMeasurementPointTable' for a power measurement point.
1.3.6.1.4.1.476.1.42.3.5.2.3.1.2ColumnlgpPwrLineMeasurementIndexnot-accessiblecurrentThis is the index indicating the row of the table 'lgpPwrLineMeasurementTable' for a power measurement point.
1.3.6.1.4.1.476.1.42.3.5.2.3.1.3ColumnlgpPwrMeasurementPointread-onlycurrentAn OID representing a well known measurement point. These object identifiers indicate a point or location of power measurement in a power system. The OID name …
1.3.6.1.4.1.476.1.42.3.5.2.3.1.4ColumnlgpPwrLineMeasurementVoltsLLread-onlycurrentThe present Line-to-Line voltage measurement for the indicated source. The line being measured is given by the lgpPwrLineMeasurementIndex [1 = AB, 2 = BC, 3 = …
1.3.6.1.4.1.476.1.42.3.5.2.3.1.5ColumnlgpPwrLineMeasurementVoltsLNread-onlycurrentThe present Line-to-neutral voltage measurement for the indicated source. The line being measured is given by the lgpPwrLineMeasurementIndex where [1 = A, 2 = …
1.3.6.1.4.1.476.1.42.3.5.2.3.1.6ColumnlgpPwrLineMeasurementCurrentread-onlycurrentThe present current measurement for the indicated source. The line being measured is given by the 'lgpPwrLineMeasurementIndex' where [1 = A, 2 = B, 3 = C].
1.3.6.1.4.1.476.1.42.3.5.2.3.1.7ColumnlgpPwrLineMeasurementCapacityread-onlycurrentThe percentage of the power capacity presently being used on this line.
1.3.6.1.4.1.476.1.42.3.5.2.3.1.8ColumnlgpPwrLineMeasurementVAread-onlycurrentThe present apparent AC line power.
1.3.6.1.4.1.476.1.42.3.5.2.3.1.9ColumnlgpPwrLineMeasurementTruePowerread-onlycurrentThe present AC line power measured in watts.
1.3.6.1.4.1.476.1.42.3.5.2.3.1.10ColumnlgpPwrLineMeasurementVoltageTHDread-onlycurrentThe present total harmonic distortion on the AC line voltage.
1.3.6.1.4.1.476.1.42.3.5.2.3.1.11ColumnlgpPwrLineMeasurementCurrentTHDread-onlycurrentThe present total harmonic distortion on the AC line current.
1.3.6.1.4.1.476.1.42.3.5.2.3.1.12ColumnlgpPwrLineMeasurementKFactorCurrentread-onlycurrentThe present line K Factor.
1.3.6.1.4.1.476.1.42.3.5.2.3.1.13ColumnlgpPwrLineMeasurementCrestFactorCurrentread-onlycurrentThe present crest factor of the line current.
1.3.6.1.4.1.476.1.42.3.5.2.3.1.14ColumnlgpPwrLineMeasurementPowerFactorread-onlycurrentThe present Power Factor for the line.
1.3.6.1.4.1.476.1.42.3.5.2.3.1.15ColumnlgpPwrLineMeasurementPowerFactorTagread-onlycurrentThe present description of the Power Factor for the line. If Leading, the load is said to be capacitive and the phase of the current leads the voltage. If Lagg…
1.3.6.1.4.1.476.1.42.3.5.2.3.1.16ColumnlgpPwrLineMeasurementMaxVoltsread-onlycurrentThe maximum voltage measurement recorded for the indicated source since the command 'lgpPwrStatisticsReset' was executed.
1.3.6.1.4.1.476.1.42.3.5.2.3.1.17ColumnlgpPwrLineMeasurementMinVoltsread-onlycurrentThe minimum voltage measurement recorded for the indicated source since the command 'lgpPwrStatisticsReset' was executed.
1.3.6.1.4.1.476.1.42.3.5.2.3.1.18ColumnlgpPwrLineMeasurementVARread-onlycurrentThe present reactive AC line power of the power source indicated by 'lgpPwrMeasurementPoint'.
1.3.6.1.4.1.476.1.42.3.5.2.3.1.19ColumnlgpPwrLineMeasurementPercentLoadread-onlycurrentThe present percent load of the AC line power.
1.3.6.1.4.1.476.1.42.3.5.2.3.1.20ColumnlgpPwrLineMeasurementVoltsread-onlycurrentThe present voltage measurement for the indicated source.
1.3.6.1.4.1.476.1.42.3.5.2.3.1.21ColumnlgpPwrLineMeasurementVACapacityread-onlycurrentThe percentage of the apparent power capacity presently being used on this line.
1.3.6.1.4.1.476.1.42.3.5.2.4TablelgpPwrDcMeasurementPointTablenot-accessiblecurrentThis table contains a list of DC power measurement point entries. The table contains zero, one, or many rows, depending upon the number of power related measur…
1.3.6.1.4.1.476.1.42.3.5.2.4.1RowlgpPwrDcMeasurementPointEntrynot-accessiblecurrentThis entry defines the measurements to be populated in the various columns of the 'lgpPwrDcMeasurementPointTable'.
1.3.6.1.4.1.476.1.42.3.5.2.4.1.1ColumnlgpPwrDcMeasurementPointIndexnot-accessiblecurrentThis is the index that indicates the row of the 'lgpPwrMeasurementPointTable' for a power measurement point.
1.3.6.1.4.1.476.1.42.3.5.2.4.1.2ColumnlgpPwrDcMeasurementPointIdread-onlycurrentAn OID representing a well known measurement point. These object identifiers indicate a point or location of power measurement in a power system. The OID's nam…
1.3.6.1.4.1.476.1.42.3.5.2.4.1.3ColumnlgpPwrDcMeasurementPointSubIDread-onlycurrentThe identifier used to differentiate between identical thresholds for a given point index and point ID in the DC measurements table.
1.3.6.1.4.1.476.1.42.3.5.2.4.1.4ColumnlgpPwrDcMeasurementPointVoltsread-onlycurrentThe present DC voltage for the power source indicated by 'lgpPwrDcMeasurementPointId' in the corresponding row in the lgpPwrDcMeasurementPointTable.
1.3.6.1.4.1.476.1.42.3.5.2.4.1.5ColumnlgpPwrDcMeasurementPointCurrentread-onlycurrentThe present DC current for the power source indicated by 'lgpPwrDcMeasurementPointId' in the corresponding row in the lgpPwrDcMeasurementPointTable.
1.3.6.1.4.1.476.1.42.3.5.2.4.1.6ColumnlgpPwrDcMeasurementPointNomVoltsread-onlycurrentThe nominal(configured/expected) DC voltage for the power source indicated by 'lgpPwrDcMeasurementPointId' in the corresponding row in the lgpPwrDcMeasurementP…
1.3.6.1.4.1.476.1.42.3.5.2.4.1.7ColumnlgpPwrDcMeasurementPointTruePowerread-onlycurrentThe present DC power for the power source indicated by 'lgpPwrDcMeasurementPointId' in the corresponding row in the lgpPwrDcMeasurementPointTable.
1.3.6.1.4.1.476.1.42.3.5.2.5IdentitylgpPwrWellKnownMeasurementTypescurrentThis sub-tree registers well known Liebert Power Measurement Types. The object identifier names usually encompass units of measure, lines of reference, and dev…
1.3.6.1.4.1.476.1.42.3.5.2.5.1IdentitylgpPwrVoltsAccurrentThis identifier represents an AC voltage.
1.3.6.1.4.1.476.1.42.3.5.2.5.2IdentitylgpPwrVoltsDccurrentThis identifier represents a DC voltage.
1.3.6.1.4.1.476.1.42.3.5.2.5.3IdentitylgpPwrAmpsNeutralcurrentThis identifier represents a current measurement in Amps on the neutral line.
1.3.6.1.4.1.476.1.42.3.5.3IdentitylgpPwrStatuscurrentThis sub-tree registers Liebert Power Status object identifiers. This is the location of power related status information that does not fit into a more specifi…
1.3.6.1.4.1.476.1.42.3.5.3.1ScalarlgpPwrTransferCountread-onlycurrentNumber of times that the output load has been transferred between the available input sources.
1.3.6.1.4.1.476.1.42.3.5.3.2ScalarlgpPwrAutoTransferTimerread-onlycurrentThe required wait time between output load auto transfer attempts between available input sources.
1.3.6.1.4.1.476.1.42.3.5.3.3ScalarlgpPwrAutoReTransferEnabledread-onlycurrentThe ability to retransfer the output load automatically to the well known measurement source from the 'lgpPwrWellKnownMeasurements' sub-tree that is the prefer…
1.3.6.1.4.1.476.1.42.3.5.3.4ScalarlgpPwrSyncPhaseAngleread-onlycurrentThe phase angle difference of source 1 in relation to source 2.
1.3.6.1.4.1.476.1.42.3.5.3.5ScalarlgpPwrParallelSystemOutputToLoadSourceread-onlycurrentThe source supporting the parallel system's load.
1.3.6.1.4.1.476.1.42.3.5.3.6ScalarlgpPwrDcToDcConverterread-onlycurrentThe state of the DC to DC converter.
1.3.6.1.4.1.476.1.42.3.5.3.7ScalarlgpPwrOutputToLoadOnInverterread-onlycurrentThe present source of output power is the Inverter.
1.3.6.1.4.1.476.1.42.3.5.3.8ScalarlgpPwrBatteryChargeCompensatingread-onlycurrentThe system is adjusting the battery charging algorithm to accommodate for the battery temperature.
1.3.6.1.4.1.476.1.42.3.5.3.9ScalarlgpPwrInverterReadyread-onlycurrentThe ability of the inverter to support the output load of the system.
1.3.6.1.4.1.476.1.42.3.5.3.10ScalarlgpPwrOutputToLoadOnBypassread-onlycurrentThe present source of output power is the Bypass.
1.3.6.1.4.1.476.1.42.3.5.3.11ScalarlgpPwrBoostread-onlycurrentThe present state of the boost circuitry
1.3.6.1.4.1.476.1.42.3.5.3.12ScalarlgpPwrBuckread-onlycurrentThe present state of the buck circuitry
1.3.6.1.4.1.476.1.42.3.5.3.13ScalarlgpPwrShutdownOverTemperatureread-onlycurrentThe system has previously shutdown due to an over temperature condition.
1.3.6.1.4.1.476.1.42.3.5.3.14ScalarlgpPwrShutdownOverloadread-onlycurrentThe system has previously shutdown due to an over load condition.
1.3.6.1.4.1.476.1.42.3.5.3.15ScalarlgpPwrShutdownDcBusOverloadread-onlycurrentThe system has previously shutdown due to a DC bus over load condition.
1.3.6.1.4.1.476.1.42.3.5.3.16ScalarlgpPwrShutdownOutputShortread-onlycurrentThe system has previously shutdown due to an output short condition.
1.3.6.1.4.1.476.1.42.3.5.3.17ScalarlgpPwrShutdownLineSwapread-onlycurrentThe system has previously shutdown due to a condition where the line and neutral were reversed.
1.3.6.1.4.1.476.1.42.3.5.3.18ScalarlgpPwrShutdownLowBatteryread-onlycurrentThe system has previously shutdown due to a low battery condition.
1.3.6.1.4.1.476.1.42.3.5.3.19ScalarlgpPwrShutdownRemoteread-onlycurrentThe system has previously shutdown due to a remote shutdown command.
1.3.6.1.4.1.476.1.42.3.5.3.20ScalarlgpPwrShutdownInputUnderVoltageread-onlycurrentThe system has previously shutdown due to an under voltage condition during startup.
1.3.6.1.4.1.476.1.42.3.5.3.21ScalarlgpPwrShutdownPowerFactorCorrectionFailureread-onlycurrentThe system has previously shutdown due to a power factor correction startup failure.
1.3.6.1.4.1.476.1.42.3.5.3.22ScalarlgpPwrShutdownHardwareread-onlycurrentThe system has previously shutdown due external shutdown signal.
1.3.6.1.4.1.476.1.42.3.5.3.23ScalarlgpPwrRedundantSubModuleread-onlycurrentThe system has a redundant battery module installed.
1.3.6.1.4.1.476.1.42.3.5.3.24ScalarlgpPwrBypassReadyread-onlycurrentThe ability of the bypass to support the output load of the system. If Yes, the bypass is available to transfer to.
1.3.6.1.4.1.476.1.42.3.5.3.25ScalarlgpPwrGeneratorStatusread-onlycurrentThe state of the system generator.
1.3.6.1.4.1.476.1.42.3.5.3.26ScalarlgpPwrRotaryBreakerStatusread-onlycurrentThe state of the system rotary breaker.
1.3.6.1.4.1.476.1.42.3.5.3.27ScalarlgpPwrPowerFactorCorrectionread-onlycurrentThe state of the power factor correction circuitry of the system.
1.3.6.1.4.1.476.1.42.3.5.3.28ScalarlgpPwrBypassSyncDiffread-onlycurrentThe phase angle difference between the inverter output and bypass source. A positive value means the inverter leads the bypass source. A negative value means t…
1.3.6.1.4.1.476.1.42.3.5.3.29ScalarlgpPwrBypassOverloadShutdownTimeread-onlycurrentThe calculated time remaining before bypass static switch shutdown due to the present overload condition. If the bypass is not in an overload condition, this o…
1.3.6.1.4.1.476.1.42.3.5.3.30ScalarlgpPwrInverterOverloadShutdownTimeread-onlycurrentThe calculated time remaining before inverter shutdown. The calculated time of inverter operation remaining for the present overload event. Note: If the invert…
1.3.6.1.4.1.476.1.42.3.5.3.31ScalarlgpPwrStateOutputSourceread-onlycurrentThe UPS's output power source (inverter, bypass, or none). NOTE: It is possible that the load still has power from the Maintenance Bypass.
1.3.6.1.4.1.476.1.42.3.5.3.32ScalarlgpPwrStateInputSourceread-onlycurrentThe system input power source (none, utility, generator).
1.3.6.1.4.1.476.1.42.3.5.3.33ScalarlgpPwrStateInputQualificationread-onlycurrentThe current state of the system input. The unit may or may not operate normally under 'marginalLow' and 'marginalHigh' states.
1.3.6.1.4.1.476.1.42.3.5.3.34ScalarlgpPwrStateBypassStaticSwitchStateread-onlycurrentThe current state of the bypass static switch.
1.3.6.1.4.1.476.1.42.3.5.3.35ScalarlgpPwrStateBypassQualificationread-onlycurrentThe current operational state of the bypass static switch. The unit may or may not operate normally under 'marginalLow' and 'marginalHigh' states.
1.3.6.1.4.1.476.1.42.3.5.3.36ScalarlgpPwrStateDCBusQualificationread-onlycurrentThe current operational state of the DC bus. The unit may or may not operate normally under 'marginalLow' and 'marginalHigh' states.
1.3.6.1.4.1.476.1.42.3.5.3.37ScalarlgpPwrStateOutQualificationread-onlycurrentThe current operational state of the output. The unit may or may not operate normally under 'marginalLow' and 'marginalHigh' states.
1.3.6.1.4.1.476.1.42.3.5.3.38ScalarlgpPwrStateInverterQualificationread-onlycurrentThe current operational state of the inverter. The unit may or may not operate normally under 'marginalLow' and 'marginalHigh' states.
1.3.6.1.4.1.476.1.42.3.5.3.39ScalarlgpPwrStateInverterStateread-onlycurrentThe current state of the inverter.
1.3.6.1.4.1.476.1.42.3.5.3.40ScalarlgpPwrStateRectifierStateread-onlycurrentThe current state of the rectifier.
1.3.6.1.4.1.476.1.42.3.5.3.41IdentitylgpPwrStateModuleGroupcurrentThis group contains UPS module information.
1.3.6.1.4.1.476.1.42.3.5.3.41.1ScalarlgpPwrStateUpsModuleCountread-writecurrentNumber of UPS modules in the system. In a single module system, this value is one.
1.3.6.1.4.1.476.1.42.3.5.3.41.2ScalarlgpPwrStateUpsModuleRedundantCountread-onlycurrentNumber of redundant UPS modules in the system. In a single module system, the value is zero. This value is dependent upon the present load and the number of mo…
1.3.6.1.4.1.476.1.42.3.5.3.42ScalarlgpPwrStateBackfeedBrkrStateread-onlycurrentThe state of the Static Bypass Switch Line Disconnect Breaker.
1.3.6.1.4.1.476.1.42.3.5.3.43ScalarlgpPwrStateLoadDisconnectStateread-onlycurrentThe state of the Static Bypass Switch Load Disconnect Breaker.
1.3.6.1.4.1.476.1.42.3.5.3.44ScalarlgpPwrStateInputBrkrStateread-onlycurrentThe state of the Input Disconnect Breaker.
1.3.6.1.4.1.476.1.42.3.5.3.45ScalarlgpPwrStateTrapFilterBrkrStateread-onlycurrentThe state of the Trap Filter Disconnect Breaker.
1.3.6.1.4.1.476.1.42.3.5.3.46ScalarlgpPwrStateInvOutputBrkrStateread-onlycurrentThe state of the Inverter Output Disconnect Breaker.
1.3.6.1.4.1.476.1.42.3.5.3.47ScalarlgpPwrStateIntBypassBrkrStateread-onlycurrentThe state of the Internal Bypass Breaker.
1.3.6.1.4.1.476.1.42.3.5.3.48ScalarlgpPwrStateBypassIsolBrkrStateread-onlycurrentThe state of the Bypass Isolation Breaker.
1.3.6.1.4.1.476.1.42.3.5.3.49ScalarlgpPwrStateRectifierIsolBrkrStateread-onlycurrentThe state of the Rectifier Isolation Breaker.
1.3.6.1.4.1.476.1.42.3.5.3.50ScalarlgpPwrStateMaintBypassBrkrStateread-onlycurrentThe state of the Maintenance Bypass Breaker.
1.3.6.1.4.1.476.1.42.3.5.3.51ScalarlgpPwrStateMaintIsolBrkrStateread-onlycurrentThe state of the Maintenance Isolation Breaker.
1.3.6.1.4.1.476.1.42.3.5.3.52ScalarlgpPwrStateOutStaticSwStateread-onlycurrentThe state of the Output Series Static Switch.
1.3.6.1.4.1.476.1.42.3.5.3.53ScalarlgpPwrStateModuleOutBrkrStateread-onlycurrentThe state of the Module Output Breaker.
1.3.6.1.4.1.476.1.42.3.5.3.54ScalarlgpPwrBypassReXfrRemainTimeread-onlycurrentThe time remaining before an inverter overload or inverter fault can be cleared and auto retransfer from the bypass to the inverter can take place. Note: If an…
1.3.6.1.4.1.476.1.42.3.5.3.55ScalarlgpPwrStateUpsOutputSourceread-onlycurrentThe present source of output power. The enumeration none(2) indicates that there is no source of output power (and therefore no output power), for example, the…
1.3.6.1.4.1.476.1.42.3.5.3.56ScalarlgpPwrStateLoadBusSynchronizationread-onlycurrentThe state of the Load Bus Synchronizer (LBS).
1.3.6.1.4.1.476.1.42.3.5.3.57IdentitylgpPwrStateCircuitBrkrStateGroupcurrentThis group contains Static Switch circuit breaker state information.
1.3.6.1.4.1.476.1.42.3.5.3.57.1ScalarlgpPwrStateSource1InputBrkrStateread-onlycurrentThe states of Source 1 Input Breaker.
1.3.6.1.4.1.476.1.42.3.5.3.57.2ScalarlgpPwrStateSource2InputBrkrStateread-onlycurrentThe states of Source 2 Input Breaker.
1.3.6.1.4.1.476.1.42.3.5.3.57.3ScalarlgpPwrStateSource1BypassBrkrStateread-onlycurrentThe states of Source 1 Bypass Breaker.
1.3.6.1.4.1.476.1.42.3.5.3.57.4ScalarlgpPwrStateSource2BypassBrkrStateread-onlycurrentThe states of Source 2 Bypass Breaker.
1.3.6.1.4.1.476.1.42.3.5.3.57.5ScalarlgpPwrStateOutputBrkrStateread-onlycurrentThe states of Output Breaker.
1.3.6.1.4.1.476.1.42.3.5.3.57.6ScalarlgpPwrStateAuxOutputBrkrStateread-onlycurrentThe states of Auxiliary Output Breaker.
1.3.6.1.4.1.476.1.42.3.5.3.57.7ScalarlgpPwrStateSource1PduInputBrkrStateread-onlycurrentThe states of Source 1 PDU Input Breaker.
1.3.6.1.4.1.476.1.42.3.5.3.57.8ScalarlgpPwrStateSource2PduInputBrkrStateread-onlycurrentThe states of Source 2 PDU Input Breaker.
1.3.6.1.4.1.476.1.42.3.5.3.58ScalarlgpPwrEconomicOperationread-onlycurrentThe present state of ECO mode operation, on(1) if system is on bypass due to ECO mode operation, off(0) any other time.
1.3.6.1.4.1.476.1.42.3.5.4IdentitylgpPwrSettingscurrentThis sub-tree registers Liebert Power Static Switch object identifiers.
1.3.6.1.4.1.476.1.42.3.5.4.1ScalarlgpPwrPreferredSourceread-onlycurrentThe well known measurement source from the 'lgpPwrWellKnownMeasurements' sub-tree that is the preferred input source of the system.
1.3.6.1.4.1.476.1.42.3.5.4.2ScalarlgpPwrLoadOnSourceread-onlycurrentThe well known measurement source from the 'lgpPwrWellKnownMeasurements' sub-tree that is currently powering the output (load).
1.3.6.1.4.1.476.1.42.3.5.4.3ScalarlgpPwrNominalVoltageDeviationread-onlycurrentThe nominal voltage deviation between the well known measurement source lgpPwrSource1Input and lgpPwrSource2Input.
1.3.6.1.4.1.476.1.42.3.5.4.4ScalarlgpPwrNominalVoltageDeviationPercentread-onlycurrentThe percentage of the nominal voltage deviation between the well known measurement source lgpPwrSource1Input and lgpPwrSource2Input.
1.3.6.1.4.1.476.1.42.3.5.4.5ScalarlgpPwrPhaseDifferenceLimitread-onlycurrentThe maximum phase difference (between the well known input sources ) in which a transfer to an available input source is permitted.
1.3.6.1.4.1.476.1.42.3.5.4.6ScalarlgpPwrFrequencyDeviationLimitread-onlycurrentThe maximum frequency deviation (between the well known input sources ) in which a transfer to an available input source is permitted.
1.3.6.1.4.1.476.1.42.3.5.4.7TablelgpPwrThresholdTablenot-accessiblecurrentA list of power thresholds for a given power measurement at a point/location in the system. The lgpPwrThresholdType in this table corresponds to the type of me…
1.3.6.1.4.1.476.1.42.3.5.4.7.1RowlgpPwrThresholdEntrynot-accessiblecurrentThis entry defines the contents of the columns for the table 'lgpPwrThresholdTable'.
1.3.6.1.4.1.476.1.42.3.5.4.7.1.1ColumnlgpPwrThresholdIndexnot-accessiblecurrentThis is the index indicating the row of the table 'lgpPwrLineMeasurementTable' for a power measurement point.
1.3.6.1.4.1.476.1.42.3.5.4.7.1.2ColumnlgpPwrThresholdPointread-onlycurrentAn OID representing a well known measurement point. These object identifiers indicate a point or location of power measurement in a power system. The OID's nam…
1.3.6.1.4.1.476.1.42.3.5.4.7.1.3ColumnlgpPwrThresholdSubIDread-onlycurrentThis is a sub identifier for the 'lgpPwrThresholdPoint'. It indicates the instance number of the well known threshold point.
1.3.6.1.4.1.476.1.42.3.5.4.7.1.4ColumnlgpPwrThresholdTyperead-onlycurrentAn OID representing a well known measurement type. These object identifiers indicate the type of measurement referenced by the row of the table. These object i…
1.3.6.1.4.1.476.1.42.3.5.4.7.1.5ColumnlgpPwrThresholdHighWarningread-writecurrentThe high warning threshold of a type of measurement designated by the 'lgpPwrThresholdType' at a location designated by the 'lgpPwrThresholdPoint'. If multiple…
1.3.6.1.4.1.476.1.42.3.5.4.7.1.6ColumnlgpPwrThresholdHighFailureread-writecurrentThe high failure threshold of a type of measurement designated by the 'lgpPwrThresholdType' at a location designated by the 'lgpPwrThresholdPoint'. If multiple…
1.3.6.1.4.1.476.1.42.3.5.4.7.1.7ColumnlgpPwrThresholdLowWarningread-writecurrentThe low warning threshold of a type of measurement designated by the 'lgpPwrThresholdType' at a location designated by the 'lgpPwrThresholdPoint'. If multiple …
1.3.6.1.4.1.476.1.42.3.5.4.7.1.8ColumnlgpPwrThresholdLowFailureread-writecurrentThe low failure threshold of a type of measurement designated by the 'lgpPwrThresholdType' at a location designated by the 'lgpPwrThresholdPoint'. If multiple …
1.3.6.1.4.1.476.1.42.3.5.4.8ScalarlgpPwrUpsAutoRestartread-writecurrentThe device will automatically restart when utility power is restored following a battery discharge.
1.3.6.1.4.1.476.1.42.3.5.4.9ScalarlgpPwrUpsAutoRestartDelayread-writecurrentThe device will automatically delay a certain number of seconds and then restart after utility power is restored following a battery discharge. The number of s…
1.3.6.1.4.1.476.1.42.3.5.4.10ScalarlgpPwrAutoRestartBatteryChargeThresholdread-writecurrentThe battery charge percentage required before the device can automatically restart.
1.3.6.1.4.1.476.1.42.3.5.4.11ScalarlgpPwrParallelModuleCountread-writecurrentThe number of modules in the parallel system.
1.3.6.1.4.1.476.1.42.3.5.4.12ScalarlgpPwrParallelRedundancyCountread-writecurrentThe number of redundant modules in the parallel system.
1.3.6.1.4.1.476.1.42.3.5.4.13ScalarlgpPwrLoadBusSyncModeread-writecurrentThe configuration of Load Bus Synchronization (LBS) between independent systems.
1.3.6.1.4.1.476.1.42.3.5.4.14ScalarlgpPwrEconomicOperationModeread-writecurrentThe configuration of the economic operation mode of the system.
1.3.6.1.4.1.476.1.42.3.5.4.15ScalarlgpPwrAutomaticBatteryTestread-writecurrentAutomatic battery test option. If enabled, the battery will be tested on a fixed interval. If disabled, the battery test must be initiated by a battery test co…
1.3.6.1.4.1.476.1.42.3.5.4.16ScalarlgpPwrMinimumRedundantPowerModuleread-writecurrentThe minimum number of redundant power modules that must be present before sending a loss of power redundancy alarm. If 0, there is no redundant power functiona…
1.3.6.1.4.1.476.1.42.3.5.4.17ScalarlgpPwrMinimumRedundantBatteryModuleread-writecurrentThe minimum number of redundant battery modules that must be present before sending an alarm. If 0, the redundant battery module alarm is disabled.
1.3.6.1.4.1.476.1.42.3.5.4.18ScalarlgpPwrOutputToLoadUserOverloadLimitread-writecurrentThis is the user specified maximum load the device can support without sending an alarm.
1.3.6.1.4.1.476.1.42.3.5.4.19ScalarlgpPwrNoLoadWarningLimitread-writecurrentThe minimum current draw on the output in which the device considers there to be a load present on the output. The condition lgpConditionWarningNoLoadDetected …
1.3.6.1.4.1.476.1.42.3.5.4.20ScalarlgpPwrNoLoadWarningDelayread-writecurrentThe amount of time to delay before annunciation of the condition lgpConditionNoLoadDetectedWarning after the output current load falls below the threshold lgpP…
1.3.6.1.4.1.476.1.42.3.5.4.21ScalarlgpPwrEconomicOperationModeControlread-writecurrentThe configuration of the economic operation mode of the system. Note that this supersedes lgpPwrEconomicOperationMode in newer devices.
1.3.6.1.4.1.476.1.42.3.5.5IdentitylgpPwrConversioncurrentThis sub-tree is used to register Liebert Power Conversion object identifiers.
1.3.6.1.4.1.476.1.42.3.5.5.1ScalarlgpPwrNumberInstalledPowerModulesread-onlycurrentThe number of power modules installed in the device.
1.3.6.1.4.1.476.1.42.3.5.5.2ScalarlgpPwrNumberFailedPowerModulesread-onlycurrentThe number of power modules in the device that have failed.
1.3.6.1.4.1.476.1.42.3.5.5.3ScalarlgpPwrNumberRedundantPowerModulesread-onlycurrentThe number of redundant power modules installed in the device.
1.3.6.1.4.1.476.1.42.3.5.5.4ScalarlgpPwrNumberActivePowerModulesread-onlycurrentThe number of active power modules in the device.
1.3.6.1.4.1.476.1.42.3.5.5.6ScalarlgpPwrNumberPowerModuleWarningsread-onlycurrentThe number of power modules in the device that have a warning.
1.3.6.1.4.1.476.1.42.3.5.5.7ScalarlgpPwrUpsInverterStandbyread-writecurrentThe output to the load is supported by the bypass and the inverter is on standby.
1.3.6.1.4.1.476.1.42.3.5.6IdentitylgpPwrControlcurrentThis sub-tree is used to register Liebert Power Control object identifiers.
1.3.6.1.4.1.476.1.42.3.5.6.1IdentitylgpPwrWellKnownControlPointscurrentThis sub-tree registers well known Liebert Power Control Points. The object identifier names usually imply locations where control of a device is available 'lo…
1.3.6.1.4.1.476.1.42.3.5.6.1.1IdentitylgpPwrLoadCircuitcurrentThe managed device's controllable load circuit. Many power systems contain more than one load circuit. This identifier represents one load circuit for the syst…
1.3.6.1.4.1.476.1.42.3.5.6.2TablelgpPwrLoadCircuitTablenot-accessiblecurrentA list of load circuits that can be controlled(opened or closed). The NMS cannot create or delete rows from the table. The rows are created by the agent based …
1.3.6.1.4.1.476.1.42.3.5.6.2.1RowlgpPwrLoadCircuitEntrynot-accessiblecurrentThis entry defines the contents of the columns for the table 'lgpPwrLoadCircuitTable'.
1.3.6.1.4.1.476.1.42.3.5.6.2.1.1ColumnlgpPwrLoadCircuitIndexnot-accessiblecurrentThis is the index indicating the row of the table 'lgpPwrLoadCircuitTable'.
1.3.6.1.4.1.476.1.42.3.5.6.2.1.2ColumnlgpPwrLoadCircuitIdread-onlycurrentAn OID representing a well known load circuit identifier. These load circuit identifiers indicate the name or type of load circuit reference in the table.
1.3.6.1.4.1.476.1.42.3.5.6.2.1.3ColumnlgpPwrLoadCircuitSubIDread-onlycurrentThis is a sub identifier for the 'lgpPwrLoadCircuitId'. It indicates the hardware identifier of the load control circuit.
1.3.6.1.4.1.476.1.42.3.5.6.2.1.4ColumnlgpPwrLoadCircuitStateread-writecurrentThis identifier indicates the state of the load circuit. When read, only a closed or open response will be returned. When written to, the state of the circuit …
1.3.6.1.4.1.476.1.42.3.5.6.2.1.5ColumnlgpPwrLoadCircuitStateAndControlread-writecurrentThis identifier indicates the state of the load circuit. When read, only a closed or open response will be returned. When written to, the state of the circuit …
1.3.6.1.4.1.476.1.42.3.5.6.3ScalarlgpPwrAlarmSilenceread-writecurrentAudible Alarm Silence Command. This command turns off the device's audible alarm. It will not affect the status of the alarm(s) that caused the audible alarm. …
1.3.6.1.4.1.476.1.42.3.5.6.4ScalarlgpPwrBatteryTestread-writecurrentBattery Test Command. This command will initiate a battery test if one is not already in progress, or abort the current test if it is in progress.
1.3.6.1.4.1.476.1.42.3.5.6.5ScalarlgpPwrUpsAbortCommandread-writecurrentUPS Abort command. This command will abort the pending command on the device. There is no guarantee a client using the abort command will cancel a command sent…
1.3.6.1.4.1.476.1.42.3.5.6.6ScalarlgpPwrTransferToBypassread-writecurrentTransfer to Bypass Command. This command will initiate a transfer of the load to the bypass of the system. This command should be sent with a parameter of 1. T…
1.3.6.1.4.1.476.1.42.3.5.6.7ScalarlgpPwrTransferToInverterread-writecurrentTransfer to Inverter Command. This command will initiate a transfer of the load to the inverter of the system. This command should be sent with a parameter of …
1.3.6.1.4.1.476.1.42.3.5.6.8ScalarlgpPwrOutputOnDelayread-writecurrentOutput On Delay Command. This command will turn on the output of the device after a user specified delay. The number of seconds to delay is subject to the prec…
1.3.6.1.4.1.476.1.42.3.5.6.9ScalarlgpPwrOutputOffDelayWithRestartread-writecurrentOutput Off Delay with Restart Command. This command will turn off the output of the device after a user specified delay. The number of seconds to delay is subj…
1.3.6.1.4.1.476.1.42.3.5.6.10ScalarlgpPwrOutputOffDelayWithoutRestartread-writecurrentOutput Off Delay without Restart Command. This command will turn off the output of the device after a specified delay. The number of seconds to delay is subjec…
1.3.6.1.4.1.476.1.42.3.5.7IdentitylgpPwrTopologycurrentThis sub-tree is used to register Liebert Power Topology object identifiers.
1.3.6.1.4.1.476.1.42.3.5.7.1ScalarlgpPwrUpsTopOfflineread-onlycurrentThe UPS has an offline topology. Under normal operating conditions, AC power from the utility passes straight through the UPS to the critical load. The inverte…
1.3.6.1.4.1.476.1.42.3.5.7.2ScalarlgpPwrUpsTopLineInteractiveread-onlycurrentThe UPS has a line-interactive topology. This topology resembles the offline product, but inserts a transformer or inductor in series between the utility power…
1.3.6.1.4.1.476.1.42.3.5.7.3ScalarlgpPwrUPSTopDualInputread-onlycurrentThe system has separate input sources for the bypass and inverter.
1.3.6.1.4.1.476.1.42.3.5.7.4ScalarlgpPwrTopFrequencyConverterread-onlycurrentThe system has a frequency converter.
1.3.6.1.4.1.476.1.42.3.5.7.5ScalarlgpPwrTopVoltageConverterread-onlycurrentThe system has a voltage converter.
1.3.6.1.4.1.476.1.42.3.5.7.6ScalarlgpPwrTopMaximumFrameCapacityread-writecurrentThe maximum device system capacity.
1.3.6.1.4.1.476.1.42.3.5.7.7ScalarlgpPwrTopRedundantControlModulesread-onlycurrentThe device has a redundant control module installed.
1.3.6.1.4.1.476.1.42.3.5.7.8ScalarlgpPwrInputIsolationTransformerInstalledread-onlycurrentIndicates whether the input isolation transformer is installed.
1.3.6.1.4.1.476.1.42.3.5.7.9ScalarlgpPwrStateStaticSwitchTyperead-onlycurrentStatic switch type (N/A, continous duty, or momentary duty).
1.3.6.1.4.1.476.1.42.3.5.7.10ScalarlgpPwrStateModuleTyperead-onlycurrent
1.3.6.1.4.1.476.1.42.3.5.7.11ScalarlgpPwrStateBypassInputConfigread-onlycurrentBypass input wire physical wiring configuration. singlePhase2WireL1WithReturn Single phase input with 2 wires (Line 1, and Return). twoPhase2WireL1L2 Two phase…
1.3.6.1.4.1.476.1.42.3.5.7.12ScalarlgpPwrStateOutputConfigread-onlycurrentOutput wire physical wiring configuration. singlePhase2WireL1WithReturn Single phase output with 2 wires (Line 1, and Return). twoPhase2WireL1L2 Two phase outp…
1.3.6.1.4.1.476.1.42.3.5.7.13ScalarlgpPwrRectifierPassiveFilterInstalledread-onlycurrentIndicates whether the rectifier passive filter is installed.
1.3.6.1.4.1.476.1.42.3.5.7.14ScalarlgpPwrRectifierTrapInstalledread-onlycurrentIndicates whether the rectifier input passive filter is installed.
1.3.6.1.4.1.476.1.42.3.5.7.15ScalarlgpPwrRectifierActiveFilterInstalledread-onlycurrentIndicates whether the rectifier active filter is installed.
1.3.6.1.4.1.476.1.42.3.5.8IdentitylgpPwrStatisticcurrentThis sub-tree is used to register Liebert Power Statistic object identifiers.
1.3.6.1.4.1.476.1.42.3.5.8.1ScalarlgpPwrBrownOutCountread-onlycurrentThe number of occurrences where the input line voltage has fallen below a pre-determined threshold for a specified amount of time. This number resets when the …
1.3.6.1.4.1.476.1.42.3.5.8.2ScalarlgpPwrBlackOutCountread-onlycurrentThe number of occurrences where there is a total loss of electric power. This number resets when the command 'lgpPwrStatisticsReset' is executed.
1.3.6.1.4.1.476.1.42.3.5.8.3ScalarlgpPwrTransientCountread-onlycurrentThe number of occurrences where the input line voltage spikes above a pre-determined threshold for a specified amount of time. This number resets when the comm…
1.3.6.1.4.1.476.1.42.3.5.8.4ScalarlgpPwrBatteryDischargeCountread-onlycurrentThe number of battery discharges since the last reset.
1.3.6.1.4.1.476.1.42.3.5.8.5ScalarlgpPwrBatteryDischargeTimeread-onlycurrentThe total accumulated time spent on battery since the last reset.
1.3.6.1.4.1.476.1.42.3.5.8.6ScalarlgpPwrBatteryAmpHoursread-onlycurrentThe total accumulated Amp-hours removed from the battery since last reset.
1.3.6.1.4.1.476.1.42.3.5.8.7ScalarlgpPwrBatteryWattHoursread-onlycurrentThe total accumulated Watt-Hours removed from the battery since last reset. This command should be sent with a parameter of 1. This variable doesn't return a v…
1.3.6.1.4.1.476.1.42.3.5.8.8ScalarlgpPwrBatteryStatisticsResetread-writecurrentBattery statistics clear command. The command to reset all battery statistics stored by the device. This command should be sent with a parameter of 1. This var…
1.3.6.1.4.1.476.1.42.3.5.8.9ScalarlgpPwrStatisticsResetread-writecurrentReset Power Statistics Command. This command will reset the power statistics stored in the system. This command should be sent with a parameter of 1. This vari…
1.3.6.1.4.1.476.1.42.3.5.9IdentitylgpPwrConfigcurrentThis sub-tree is used to register Liebert Power Configuration Object identifiers.
1.3.6.1.4.1.476.1.42.3.5.9.1ScalarlgpPwrSysCapacityread-writecurrentThe current device system capacity.
1.3.6.1.4.1.476.1.42.3.5.9.2ScalarlgpPwrUPSModuleModeread-writecurrentThe module mode of the UPS.
1.3.6.1.4.1.476.1.42.3.5.9.3ScalarlgpPwrMaxRatedCurrentread-onlycurrentSystem output maximum amperage rating. The maximum rated amperage for the system. This value is based upon the model type and is typically limited by the wirin…
1.3.6.1.4.1.476.1.42.3.5.9.4ScalarlgpPwrRectifierPulseCountread-onlycurrentRectifier pulse count per waveform cycle (6-, 12-, 18-, or 24-pulse).