MG-SNMP-UPS-MIB
307 objects
No module-level DESCRIPTION found.
Imported Objects
| RFC-1212 | OBJECT-TYPE |
| RFC-1215 | TRAP-TYPE |
| RFC1155-SMI | enterprises IpAddress TimeTicks |
| RFC1213-MIB | DisplayString |
| OID | Name | Access | Status | Description |
|---|---|---|---|---|
| 1.3.6.1.4.1.705 | NodemerlinGerin | |||
| 1.3.6.1.4.1.705.1 | Nodeupsmg | |||
| 1.3.6.1.4.1.705.1.1 | NodeupsmgIdent | |||
| 1.3.6.1.4.1.705.1.1.1 | ScalarupsmgIdentFamilyName | read-write | mandatory | The UPS family name (e.g. `PULSAR', `COMET', `GALAXY', ...). |
| 1.3.6.1.4.1.705.1.1.2 | ScalarupsmgIdentModelName | read-write | mandatory | The UPS model name (e.g. `PSX20', `SV9', ... ). |
| 1.3.6.1.4.1.705.1.1.3 | ScalarupsmgIdentRevisionLevel | read-write | mandatory | The UPS revision level. |
| 1.3.6.1.4.1.705.1.1.4 | ScalarupsmgIdentFirmwareVersion | read-write | mandatory | The UPS microprocessor firmware version number. |
| 1.3.6.1.4.1.705.1.1.5 | ScalarupsmgIdentUserID | read-write | mandatory | The UPS user identification (set by administrator). |
| 1.3.6.1.4.1.705.1.1.6 | ScalarupsmgIdentInstallationDate | read-write | mandatory | The UPS installation date in dd/mm/yy format. |
| 1.3.6.1.4.1.705.1.1.7 | ScalarupsmgIdentSerialNumber | read-write | mandatory | The UPS manufacturing serial number. |
| 1.3.6.1.4.1.705.1.2 | NodeupsmgManagement | |||
| 1.3.6.1.4.1.705.1.2.1 | ScalarupsmgManagersNum | read-only | mandatory | The number of managers that could manage the UPS. |
| 1.3.6.1.4.1.705.1.2.2 | TableupsmgManagersTable | not-accessible | mandatory | The table of managers. |
| 1.3.6.1.4.1.705.1.2.2.1 | RowupsmgManagersEntry | not-accessible | mandatory | The description of a manager entry in the managers table. |
| 1.3.6.1.4.1.705.1.2.2.1.1 | ColumnmgmanagerIndex | read-only | mandatory | A unique value for each manager. Its value ranges between 1 and the value of upsmgManagersNum. |
| 1.3.6.1.4.1.705.1.2.2.1.2 | ColumnmgmanagerDeviceNumber | read-write | mandatory | This object is the number of the manager device in the DevicesTable of the Config group. This means that the manager is powered by the UPS. If not the default … |
| 1.3.6.1.4.1.705.1.2.2.1.3 | ColumnmgmanagerNMSType | read-write | mandatory | The type of manager according to the NMS platform. We include in the manager class all systems which will be notified by the agent via receiving traps (e.g. ba… |
| 1.3.6.1.4.1.705.1.2.2.1.4 | ColumnmgmanagerCommType | read-write | mandatory | The level of communication protocol for that manager. Setting this object to value invalid(2) has the effect of invalidating the corresponding entry in the ups… |
| 1.3.6.1.4.1.705.1.2.2.1.5 | ColumnmgmanagerDescr | read-write | mandatory | A textual string containing information about the manager. (manufacturer and version description). |
| 1.3.6.1.4.1.705.1.2.2.1.6 | ColumnmgmanagerAddress | read-write | mandatory | The IP address of the manager station receiving traps. The value of this object is meaningful if and only if the value of the relevant mgmanagerCommType object… |
| 1.3.6.1.4.1.705.1.2.2.1.7 | ColumnmgmanagerCommunity | read-write | mandatory | The manager community string. |
| 1.3.6.1.4.1.705.1.2.2.1.8 | ColumnmgmanagerSeverityLevel | read-write | mandatory | The severity level of traps to be received by this manager. |
| 1.3.6.1.4.1.705.1.2.2.1.9 | ColumnmgmanagerTrapAck | read-write | mandatory | The manager Trap Acknowledgement status. Setting this object to mgnoack(2) or stdnomg(3) or cpqnoack(5) disables the trap acknowledgement from the related mana… |
| 1.3.6.1.4.1.705.1.3 | NodeupsmgReceptacle | |||
| 1.3.6.1.4.1.705.1.3.1 | ScalarupsmgReceptaclesNum | read-only | mandatory | The total number of receptacles controlled by the UPS. |
| 1.3.6.1.4.1.705.1.3.2 | TableupsmgReceptaclesTable | not-accessible | mandatory | The table of receptacles that are controlled by the UPS. |
| 1.3.6.1.4.1.705.1.3.2.1 | RowupsmgReceptaclesEntry | not-accessible | mandatory | The description of a receptacle in the table. |
| 1.3.6.1.4.1.705.1.3.2.1.1 | ColumnmgreceptacleIndex | read-only | mandatory | A unique value for each receptacle. Its value ranges between 1 and the value of upsmgReceptaclesNum. |
| 1.3.6.1.4.1.705.1.3.2.1.2 | ColumnmgreceptacleLevel | read-write | mandatory | The level of receptacle. Setting this object to value invalid(2) has the effect of invalidating the corresponding entry in the upsmgReceptaclesTable. It is an … |
| 1.3.6.1.4.1.705.1.3.2.1.3 | ColumnmgreceptacleType | read-write | mandatory | A textual string for the receptacle type. |
| 1.3.6.1.4.1.705.1.3.2.1.4 | ColumnmgreceptacleIdent | read-write | mandatory | A textual string identification for the user. |
| 1.3.6.1.4.1.705.1.3.2.1.5 | ColumnmgreceptacleState | read-only | mandatory | The ON/OFF status of the receptacle. |
| 1.3.6.1.4.1.705.1.3.2.1.6 | ColumnmgreceptacleReceptacle | read-write | mandatory | The receptacle number of the second level receptacle father. The value of this object is meaningful if and only if the value of the relevant mgreceptacleType o… |
| 1.3.6.1.4.1.705.1.3.2.1.7 | ColumnmgreceptaclePowerCons | read-write | mandatory | The volt-ampere rating of the receptacle. The value of this object is meaningful if and only if the value of the relevant mgreceptacleType object is related to… |
| 1.3.6.1.4.1.705.1.3.2.1.8 | ColumnmgreceptacleOverload | read-write | mandatory | The overload status of the receptacle. The value of this object is meaningful if and only if the value of the relevant mgreceptacleType object is related to a … |
| 1.3.6.1.4.1.705.1.3.2.1.9 | ColumnmgreceptacleAutonomy | read-write | mandatory | The receptacle autonomy. The value of this object is meaningful if and only if the value of the relevant mgreceptacleType object is related to a two-level rece… |
| 1.3.6.1.4.1.705.1.4 | NodeupsmgConfig | |||
| 1.3.6.1.4.1.705.1.4.1 | ScalarupsmgConfigBatteryInstalled | read-write | mandatory | The battery installed status. |
| 1.3.6.1.4.1.705.1.4.2 | ScalarupsmgConfigNominalBatteryVoltage | read-write | mandatory | The nominal battery voltage. |
| 1.3.6.1.4.1.705.1.4.3 | ScalarupsmgConfigNominalBatteryTime | read-write | mandatory | The full load battery autonomy time. |
| 1.3.6.1.4.1.705.1.4.4 | ScalarupsmgConfigNominalRechargeTime | read-write | mandatory | The recharge time to go from low battery cut off to full charge at full load. |
| 1.3.6.1.4.1.705.1.4.5 | ScalarupsmgConfigMinRechargeLevel | read-write | mandatory | The minimum battery level required to supply power on the loads after low battery condition turn off and restart on main return. |
| 1.3.6.1.4.1.705.1.4.6 | ScalarupsmgConfigMaxRechargeTime | read-write | mandatory | The maximum time delay of battery recharge before supply power to the loads. |
| 1.3.6.1.4.1.705.1.4.7 | ScalarupsmgConfigLowBatteryTime | read-write | mandatory | To set remaining time value for low battery condition. |
| 1.3.6.1.4.1.705.1.4.8 | ScalarupsmgConfigLowBatteryLevel | read-write | mandatory | To set battery level value for low battery condition. |
| 1.3.6.1.4.1.705.1.4.9 | ScalarupsmgConfigAutoRestart | read-write | mandatory | The automatic restart enabling status. |
| 1.3.6.1.4.1.705.1.4.10 | ScalarupsmgConfigShutdownTimer | read-write | mandatory | To set ups shutdown timer from on battery condition. |
| 1.3.6.1.4.1.705.1.4.11 | ScalarupsmgConfigSysShutDuration | read-write | mandatory | To set ups shutdown delay (Sn delay). |
| 1.3.6.1.4.1.705.1.4.12 | ScalarupsmgConfigVARating | read-write | mandatory | The UPS nominal VA rating. |
| 1.3.6.1.4.1.705.1.4.13 | ScalarupsmgConfigLowTransfer | read-write | mandatory | The low voltage transfer point. |
| 1.3.6.1.4.1.705.1.4.14 | ScalarupsmgConfigHighTransfer | read-write | mandatory | The high voltage transfer point. |
| 1.3.6.1.4.1.705.1.4.15 | ScalarupsmgConfigOutputNominalVoltage | read-write | mandatory | The nominal output voltage. |
| 1.3.6.1.4.1.705.1.4.16 | ScalarupsmgConfigOutputNominalCurrent | read-write | mandatory | The nominal output current. |
| 1.3.6.1.4.1.705.1.4.17 | ScalarupsmgConfigOutputNomFrequency | read-write | mandatory | The nominal output frequency. |
| 1.3.6.1.4.1.705.1.4.18 | ScalarupsmgConfigByPassType | read-write | mandatory | The UPS by pass switch type. |
| 1.3.6.1.4.1.705.1.4.19 | ScalarupsmgConfigAlarmAudible | read-write | mandatory | To set audible alarm status. |
| 1.3.6.1.4.1.705.1.4.20 | ScalarupsmgConfigAlarmTimeDelay | read-write | mandatory | To set audible alarm time delay. |
| 1.3.6.1.4.1.705.1.4.21 | ScalarupsmgConfigDevicesNum | read-write | mandatory | The number of devices that are powered by the UPS. |
| 1.3.6.1.4.1.705.1.4.22 | TableupsmgConfigDevicesTable | not-accessible | mandatory | The table of devices that are powered by the UPS. |
| 1.3.6.1.4.1.705.1.4.22.1 | RowupsmgConfigDevicesEntry | not-accessible | mandatory | The description of a device entry in the devices table. |
| 1.3.6.1.4.1.705.1.4.22.1.1 | ColumnmgdeviceIndex | read-only | mandatory | A unique value for each device. Its value ranges between 1 and the value of upsmgDevicesNum. |
| 1.3.6.1.4.1.705.1.4.22.1.2 | ColumnmgdeviceReceptacleNum | read-write | mandatory | The receptacle number of the device plugged into the UPS. This value gives index entry in the ReceptaclesTable object of the Receptacle group. A value of 0 inv… |
| 1.3.6.1.4.1.705.1.4.22.1.3 | ColumnmgdeviceIdent | read-write | mandatory | A textual string for device user identification. |
| 1.3.6.1.4.1.705.1.4.22.1.4 | ColumnmgdeviceVaRating | read-write | mandatory | The volt-ampere rating of the device plugged into the UPS. |
| 1.3.6.1.4.1.705.1.4.22.1.5 | ColumnmgdeviceSequenceOff | read-write | mandatory | To set the device position in the remote shutdown sequence. |
| 1.3.6.1.4.1.705.1.4.22.1.6 | ColumnmgdeviceSequenceOn | read-write | mandatory | To set the device position in the remote reboot sequence. |
| 1.3.6.1.4.1.705.1.4.22.1.7 | ColumnmgdeviceShutdownDuration | read-write | mandatory | To set the duration from start of computer shut-down to complete. |
| 1.3.6.1.4.1.705.1.4.22.1.8 | ColumnmgdeviceBootUpDuration | read-write | mandatory | To set the duration from start of computer boot-up to complete. |
| 1.3.6.1.4.1.705.1.4.23 | TableupsmgConfigReceptaclesTable | not-accessible | mandatory | The table of receptacles. |
| 1.3.6.1.4.1.705.1.4.23.1 | RowupsmgConfigReceptaclesEntry | not-accessible | mandatory | The description of a receptacle entry in the table. |
| 1.3.6.1.4.1.705.1.4.23.1.1 | ColumnmgreceptacleIndexb | read-only | mandatory | A unique value for each receptacle. Its value ranges between 1 and the value of upsmgReceptaclesNum. |
| 1.3.6.1.4.1.705.1.4.23.1.2 | ColumnmgreceptacleStateTurnOn | read-write | mandatory | Default return state at turn on. |
| 1.3.6.1.4.1.705.1.4.23.1.3 | ColumnmgreceptacleStateMainReturn | read-write | mandatory | Default return state on main return. |
| 1.3.6.1.4.1.705.1.4.23.1.4 | ColumnmgreceptacleStateDischarge | read-write | mandatory | Default return state on main return from battery discharge. |
| 1.3.6.1.4.1.705.1.4.23.1.5 | ColumnmgreceptacleShutoffLevel | read-write | mandatory | Battery level for starting shutoff sequence. |
| 1.3.6.1.4.1.705.1.4.23.1.6 | ColumnmgreceptacleShutoffTimer | read-write | mandatory | Time delay from on battery for starting shutoff sequence. |
| 1.3.6.1.4.1.705.1.4.23.1.7 | ColumnmgreceptacleRestartLevel | read-write | mandatory | Battery level for starting restart sequence. |
| 1.3.6.1.4.1.705.1.4.23.1.8 | ColumnmgreceptacleRestartDelay | read-write | mandatory | Time delay for starting restart sequence. |
| 1.3.6.1.4.1.705.1.4.23.1.9 | ColumnmgreceptacleShutdownDuration | read-only | mandatory | Maximum Shutdown Duration for systems powered by this plug. |
| 1.3.6.1.4.1.705.1.4.23.1.10 | ColumnmgreceptacleBootUpDuration | read-only | mandatory | Maximum Reboot Duration for systems powered by this plug. |
| 1.3.6.1.4.1.705.1.4.24 | ScalarupsmgConfigExtAlarmNum | read-only | mandatory | The number of environ external alarm, value is between 8 and 32.. |
| 1.3.6.1.4.1.705.1.4.25 | TableupsmgConfigExtAlarmTable | not-accessible | mandatory | The table of environmental external alarms. |
| 1.3.6.1.4.1.705.1.4.25.1 | RowupsmgConfigExtAlarmEntry | not-accessible | mandatory | The description of an external alarm in the table. |
| 1.3.6.1.4.1.705.1.4.25.1.1 | ColumnmgextAlarmIndex | read-only | mandatory | A unique value for each external alarm. Its value ranges between 1 and the value of upsmgConfigExtAlarmNum. |
| 1.3.6.1.4.1.705.1.4.25.1.2 | ColumnmgextAlarmUID | read-write | mandatory | A textual string for alarm state user identification. |
| 1.3.6.1.4.1.705.1.4.26 | ScalarupsmgConfigEmergencyTestFail | read-write | mandatory | The emergency condition status on Battery test fail. |
| 1.3.6.1.4.1.705.1.4.27 | ScalarupsmgConfigEmergencyOnByPass | read-write | mandatory | The emergency condition status on By Pass. |
| 1.3.6.1.4.1.705.1.4.28 | ScalarupsmgConfigEmergencyOverload | read-write | mandatory | The emergency condition status on overload. |
| 1.3.6.1.4.1.705.1.4.29 | TableupsmgConfigControlDayTable | not-accessible | mandatory | The table of daily on/off time. |
| 1.3.6.1.4.1.705.1.4.29.1 | RowupsmgConfigControlDayEntry | not-accessible | mandatory | The description of a daily on/off time schedule in the table. |
| 1.3.6.1.4.1.705.1.4.29.1.1 | ColumnmgcontrolDayIndex | read-only | mandatory | The day index. It is a number between 1 and 7, 1 for Sunday, 2 for Monday, ... |
| 1.3.6.1.4.1.705.1.4.29.1.2 | ColumnmgcontrolDayOn | read-write | mandatory | To set daily power on time. Any value greater than 86400 is to disable the Day On. |
| 1.3.6.1.4.1.705.1.4.29.1.3 | ColumnmgcontrolDayOff | read-write | mandatory | To set daily power off time. Any value greater than 86400 is to disable the Day Off. |
| 1.3.6.1.4.1.705.1.4.30 | ScalarupsmgConfigLowBooster | read-write | mandatory | To set UPS booster low threshold. |
| 1.3.6.1.4.1.705.1.4.31 | ScalarupsmgConfigHighBooster | read-write | mandatory | To set UPS booster high threshold. |
| 1.3.6.1.4.1.705.1.4.32 | ScalarupsmgConfigLowFader | read-write | mandatory | To set UPS fader low threshold. |
| 1.3.6.1.4.1.705.1.4.33 | ScalarupsmgConfigHighFader | read-write | mandatory | To set UPS fader high threshold. |
| 1.3.6.1.4.1.705.1.4.34 | TableupsmgConfigEnvironmentTable | not-accessible | mandatory | The table containing the configuration of the environment sensor. |
| 1.3.6.1.4.1.705.1.4.34.1 | RowupsmgConfigEnvironmentEntry | not-accessible | mandatory | The description of an entry in the table. |
| 1.3.6.1.4.1.705.1.4.34.1.1 | ColumnupsmgConfigSensorIndex | read-only | mandatory | The sensor index, ranging from 1 to upsmgEnvironmentNum. |
| 1.3.6.1.4.1.705.1.4.34.1.2 | ColumnupsmgConfigSensorName | read-write | mandatory | The sensor user-friendly name. |
| 1.3.6.1.4.1.705.1.4.34.1.3 | ColumnupsmgConfigTemperatureLow | read-write | mandatory | The low temperature threshold in unit 0.1 Cel. |
| 1.3.6.1.4.1.705.1.4.34.1.4 | ColumnupsmgConfigTemperatureHigh | read-write | mandatory | The high temperature threshold in unit 0.1 Cel. |
| 1.3.6.1.4.1.705.1.4.34.1.5 | ColumnupsmgConfigTemperatureHysteresis | read-write | mandatory | The temperature hysteresys used for threshold test in unit 0.1 Cel. |
| 1.3.6.1.4.1.705.1.4.34.1.6 | ColumnupsmgConfigHumidityLow | read-write | mandatory | The low humidity threshold in unit 1 %. |
| 1.3.6.1.4.1.705.1.4.34.1.7 | ColumnupsmgConfigHumidityHigh | read-write | mandatory | The high humidity threshold in unit 1 %. |
| 1.3.6.1.4.1.705.1.4.34.1.8 | ColumnupsmgConfigHumidityHysteresis | read-write | mandatory | The humidity hysteresys used for threshold test in unit 1 %. |
| 1.3.6.1.4.1.705.1.4.34.1.9 | ColumnupsmgConfigInput1Name | read-write | mandatory | The Input #1 user-friendly name. |
| 1.3.6.1.4.1.705.1.4.34.1.10 | ColumnupsmgConfigInput1ClosedLabel | read-write | mandatory | The Input #1 label for closed position. |
| 1.3.6.1.4.1.705.1.4.34.1.11 | ColumnupsmgConfigInput1OpenLabel | read-write | mandatory | The Input #1 label for open position. |
| 1.3.6.1.4.1.705.1.4.34.1.12 | ColumnupsmgConfigInput2Name | read-write | mandatory | The Input #2 user-friendly name. |
| 1.3.6.1.4.1.705.1.4.34.1.13 | ColumnupsmgConfigInput2ClosedLabel | read-write | mandatory | The Input #2 label for closed position. |
| 1.3.6.1.4.1.705.1.4.34.1.14 | ColumnupsmgConfigInput2OpenLabel | read-write | mandatory | The Input #2 label for open position. |
| 1.3.6.1.4.1.705.1.5 | NodeupsmgBattery | |||
| 1.3.6.1.4.1.705.1.5.1 | ScalarupsmgBatteryRemainingTime | read-only | mandatory | The time remaining actual charge vs actual load (dynamic). |
| 1.3.6.1.4.1.705.1.5.2 | ScalarupsmgBatteryLevel | read-only | mandatory | The battery level as a percentage of charge. |
| 1.3.6.1.4.1.705.1.5.3 | ScalarupsmgBatteryRechargeTime | read-only | mandatory | The actual operational battery recharge time to set point equal to upsmgConfigRechargeLevel. This value is computed from upsmgConfigRechargeLevel (level to rea… |
| 1.3.6.1.4.1.705.1.5.4 | ScalarupsmgBatteryRechargeLevel | read-only | mandatory | The actual value of the battery recharge level that will be reached during the time delay necessary to restart after power returns. This value is computed from… |
| 1.3.6.1.4.1.705.1.5.5 | ScalarupsmgBatteryVoltage | read-only | mandatory | The actual battery voltage. |
| 1.3.6.1.4.1.705.1.5.6 | ScalarupsmgBatteryCurrent | read-only | mandatory | The actual battery current. |
| 1.3.6.1.4.1.705.1.5.7 | ScalarupsmgBatteryTemperature | read-only | mandatory | The battery temperature. |
| 1.3.6.1.4.1.705.1.5.8 | ScalarupsmgBatteryFullRechargeTime | read-only | mandatory | The battery full recharge time (from 0 to 100 percent) at current load. |
| 1.3.6.1.4.1.705.1.5.9 | ScalarupsmgBatteryFaultBattery | read-only | mandatory | The battery fault status. |
| 1.3.6.1.4.1.705.1.5.10 | ScalarupsmgBatteryNoBattery | read-only | mandatory | The UPS has no Battery status. |
| 1.3.6.1.4.1.705.1.5.11 | ScalarupsmgBatteryReplacement | read-only | mandatory | The UPS Battery to be replaced status. |
| 1.3.6.1.4.1.705.1.5.12 | ScalarupsmgBatteryUnavailableBattery | read-only | mandatory | The UPS Battery is unavailable status. |
| 1.3.6.1.4.1.705.1.5.13 | ScalarupsmgBatteryNotHighCharge | read-only | mandatory | The UPS Battery quit high condition status. |
| 1.3.6.1.4.1.705.1.5.14 | ScalarupsmgBatteryLowBattery | read-only | mandatory | The battery low status. |
| 1.3.6.1.4.1.705.1.5.15 | ScalarupsmgBatteryChargerFault | read-only | mandatory | The UPS Battery is not charging status. |
| 1.3.6.1.4.1.705.1.5.16 | ScalarupsmgBatteryLowCondition | read-only | mandatory | The UPS is at low condition status. |
| 1.3.6.1.4.1.705.1.5.17 | ScalarupsmgBatteryLowRecharge | read-only | mandatory | The UPS Battery is not recharged status. |
| 1.3.6.1.4.1.705.1.6 | NodeupsmgInput | |||
| 1.3.6.1.4.1.705.1.6.1 | ScalarupsmgInputPhaseNum | read-only | mandatory | The number of input phases. |
| 1.3.6.1.4.1.705.1.6.2 | TableupsmgInputPhaseTable | not-accessible | mandatory | The table of input phases. |
| 1.3.6.1.4.1.705.1.6.2.1 | RowupsmgInputPhaseEntry | not-accessible | mandatory | The description of an input phase. |
| 1.3.6.1.4.1.705.1.6.2.1.1 | ColumnmginputIndex | read-only | mandatory | The input phase voltage index. It is a number between 1 and upsmgInputPhaseNum. |
| 1.3.6.1.4.1.705.1.6.2.1.2 | ColumnmginputVoltage | read-only | mandatory | The input phase voltage. |
| 1.3.6.1.4.1.705.1.6.2.1.3 | ColumnmginputFrequency | read-only | mandatory | The input phase frequency. |
| 1.3.6.1.4.1.705.1.6.2.1.4 | ColumnmginputMinimumVoltage | read-only | mandatory | The input phase minimum voltage over the last minute. |
| 1.3.6.1.4.1.705.1.6.2.1.5 | ColumnmginputMaximumVoltage | read-only | mandatory | The input phase maximum voltage over the last minute. |
| 1.3.6.1.4.1.705.1.6.2.1.6 | ColumnmginputCurrent | read-only | mandatory | The input phase current. |
| 1.3.6.1.4.1.705.1.6.3 | ScalarupsmgInputBadStatus | read-only | mandatory | The utility power bad voltage or bad frequency status. |
| 1.3.6.1.4.1.705.1.6.4 | ScalarupsmgInputLineFailCause | read-only | mandatory | The utility power failure cause: no(1) is for no utility failure, outoftolvolt(2) is for voltage out of tolerance, outoftolfreq(3) is for frequency out of tole… |
| 1.3.6.1.4.1.705.1.7 | NodeupsmgOutput | |||
| 1.3.6.1.4.1.705.1.7.1 | ScalarupsmgOutputPhaseNum | read-only | mandatory | The number of output phases. |
| 1.3.6.1.4.1.705.1.7.2 | TableupsmgOutputPhaseTable | not-accessible | mandatory | The table of output phases. |
| 1.3.6.1.4.1.705.1.7.2.1 | RowupsmgOutputPhaseEntry | not-accessible | mandatory | The description of an output phase. |
| 1.3.6.1.4.1.705.1.7.2.1.1 | ColumnmgoutputPhaseIndex | read-only | mandatory | The output phase voltage index. It is a number between 1 and upsmgOutputPhaseNum. |
| 1.3.6.1.4.1.705.1.7.2.1.2 | ColumnmgoutputVoltage | read-only | mandatory | The output phase voltage. |
| 1.3.6.1.4.1.705.1.7.2.1.3 | ColumnmgoutputFrequency | read-only | mandatory | The output phase frequency. |
| 1.3.6.1.4.1.705.1.7.2.1.4 | ColumnmgoutputLoadPerPhase | read-only | mandatory | The output load per phase. |
| 1.3.6.1.4.1.705.1.7.2.1.5 | ColumnmgoutputCurrent | read-only | mandatory | The output phase current. |
| 1.3.6.1.4.1.705.1.7.3 | ScalarupsmgOutputOnBattery | read-only | mandatory | The UPS on battery / on main status. |
| 1.3.6.1.4.1.705.1.7.4 | ScalarupsmgOutputOnByPass | read-only | mandatory | The UPS on bypass status. |
| 1.3.6.1.4.1.705.1.7.5 | ScalarupsmgOutputUnavailableByPass | read-only | mandatory | The by pass unavailable status. |
| 1.3.6.1.4.1.705.1.7.6 | ScalarupsmgOutputNoByPass | read-only | mandatory | The UPS bypass installed status. |
| 1.3.6.1.4.1.705.1.7.7 | ScalarupsmgOutputUtilityOff | read-only | mandatory | The UPS utility off status. |
| 1.3.6.1.4.1.705.1.7.8 | ScalarupsmgOutputOnBoost | read-only | mandatory | The UPS on booster status. |
| 1.3.6.1.4.1.705.1.7.9 | ScalarupsmgOutputInverterOff | read-only | mandatory | The UPS Inverter on / off status. |
| 1.3.6.1.4.1.705.1.7.10 | ScalarupsmgOutputOverLoad | read-only | mandatory | The output over load status. |
| 1.3.6.1.4.1.705.1.7.11 | ScalarupsmgOutputOverTemp | read-only | mandatory | The ups over temperature status. |
| 1.3.6.1.4.1.705.1.7.12 | ScalarupsmgOutputOnBuck | read-only | mandatory | The UPS on fader status. |
| 1.3.6.1.4.1.705.1.8 | NodeupsmgEnviron | |||
| 1.3.6.1.4.1.705.1.8.1 | ScalarupsmgEnvironAmbientTemp | read-only | mandatory | The ambient temperature. |
| 1.3.6.1.4.1.705.1.8.2 | ScalarupsmgEnvironAmbientHumidity | read-only | mandatory | The ambient humidity. |
| 1.3.6.1.4.1.705.1.8.3 | TableupsmgEnvironExtAlarmTable | not-accessible | mandatory | The table of external alarms. |
| 1.3.6.1.4.1.705.1.8.3.1 | RowupsmgEnvironExtAlarmEntry | not-accessible | mandatory | The description of an external alarm. |
| 1.3.6.1.4.1.705.1.8.3.1.1 | ColumnmgalarmNum | read-only | mandatory | The external alarm number. A number between 1 and upsmgConfigExtAlarmNum. |
| 1.3.6.1.4.1.705.1.8.3.1.2 | ColumnmgalarmState | read-only | mandatory | The external alarm state (active or inactive). |
| 1.3.6.1.4.1.705.1.8.4 | ScalarupsmgEnvironSensorNum | read-only | mandatory | The sensor unit number (0 to 4). |
| 1.3.6.1.4.1.705.1.8.5 | TableupsmgEnvironSensorTable | not-accessible | mandatory | The table of sensor units. |
| 1.3.6.1.4.1.705.1.8.5.1 | RowupsmgEnvironSensorEntry | not-accessible | mandatory | The description of a sensor unit. |
| 1.3.6.1.4.1.705.1.8.5.1.1 | ColumnmgsensorNum | read-only | mandatory | The unit number. A number between 1 and 4. |
| 1.3.6.1.4.1.705.1.8.5.1.2 | ColumnmgsensorTemp | read-only | mandatory | The measured temperature of the unit. |
| 1.3.6.1.4.1.705.1.8.5.1.3 | ColumnmgsensorHumidity | read-only | mandatory | The measured humidity of the unit. |
| 1.3.6.1.4.1.705.1.8.6 | ScalarupsmgEnvironmentNum | read-only | mandatory | Number of Environment sensor connected. |
| 1.3.6.1.4.1.705.1.8.7 | TableupsmgEnvironmentSensorTable | not-accessible | mandatory | The table containing the measurements and alarms made by Environment sensor units. |
| 1.3.6.1.4.1.705.1.8.7.1 | RowupsmgEnvironmentSensorEntry | not-accessible | mandatory | The description of an entry in the measurement table. |
| 1.3.6.1.4.1.705.1.8.7.1.1 | ColumnupsmgEnvironmentIndex | read-only | mandatory | The sensor index, ranging from 1 to upsmgEnvironmentNum. |
| 1.3.6.1.4.1.705.1.8.7.1.2 | ColumnupsmgEnvironmentComFailure | read-only | mandatory | The sensor communication failure : yes(1), no(2). |
| 1.3.6.1.4.1.705.1.8.7.1.3 | ColumnupsmgEnvironmentTemperature | read-only | mandatory | The temperature measurement in unit 0.1 Cel. |
| 1.3.6.1.4.1.705.1.8.7.1.4 | ColumnupsmgEnvironmentTemperatureLow | read-only | mandatory | Temperature is below low theshold : yes(1), no(2). |
| 1.3.6.1.4.1.705.1.8.7.1.5 | ColumnupsmgEnvironmentTemperatureHigh | read-only | mandatory | Temperature is above high threshold : yes(1), no(2). |
| 1.3.6.1.4.1.705.1.8.7.1.6 | ColumnupsmgEnvironmentHumidity | read-only | mandatory | The humidity measurement in unit 0.1 %. |
| 1.3.6.1.4.1.705.1.8.7.1.7 | ColumnupsmgEnvironmentHumidityLow | read-only | mandatory | Humidity is below low threshold : yes(1), no(2). |
| 1.3.6.1.4.1.705.1.8.7.1.8 | ColumnupsmgEnvironmentHumidityHigh | read-only | mandatory | Humidity is above high threshold : yes(1), no(2). |
| 1.3.6.1.4.1.705.1.8.7.1.9 | ColumnupsmgEnvironmentInput1State | read-only | mandatory | State of Input#1 : closed(1), open(2). |
| 1.3.6.1.4.1.705.1.8.7.1.10 | ColumnupsmgEnvironmentInput2State | read-only | mandatory | State of Input#2 : closed(1), open(2). |
| 1.3.6.1.4.1.705.1.9 | NodeupsmgControl | |||
| 1.3.6.1.4.1.705.1.9.1 | TableupsmgControlReceptaclesTable | not-accessible | mandatory | The table of receptacles. |
| 1.3.6.1.4.1.705.1.9.1.1 | RowupsmgControlReceptaclesEntry | not-accessible | mandatory | The description of a receptacle entry in the table. |
| 1.3.6.1.4.1.705.1.9.1.1.1 | ColumnmgreceptacleIndexc | read-only | mandatory | A unique value for each receptacle. Its value ranges between 1 and the value of upsmgReceptaclesNum. |
| 1.3.6.1.4.1.705.1.9.1.1.2 | ColumnmgreceptacleOnDelay | read-write | mandatory | Turn on UPS receptacle w/delay=?. |
| 1.3.6.1.4.1.705.1.9.1.1.3 | ColumnmgreceptacleOnCtrl | read-write | mandatory | The receptacle control on action. |
| 1.3.6.1.4.1.705.1.9.1.1.4 | ColumnmgreceptacleOnStatus | read-only | mandatory | The receptacle control on status. |
| 1.3.6.1.4.1.705.1.9.1.1.5 | ColumnmgreceptacleOffDelay | read-write | mandatory | Turn off UPS receptacle w/delay=?. |
| 1.3.6.1.4.1.705.1.9.1.1.6 | ColumnmgreceptacleOffCtrl | read-write | mandatory | The receptacle control off action. |
| 1.3.6.1.4.1.705.1.9.1.1.7 | ColumnmgreceptacleOffStatus | read-only | mandatory | The receptacle control off status. |
| 1.3.6.1.4.1.705.1.9.1.1.8 | ColumnmgreceptacleToggleDelay | read-write | mandatory | Turn off then on UPS receptacle w/delay=?. |
| 1.3.6.1.4.1.705.1.9.1.1.9 | ColumnmgreceptacleToggleCtrl | read-write | mandatory | The receptacle control toggle action. |
| 1.3.6.1.4.1.705.1.9.1.1.10 | ColumnmgreceptacleToggleStatus | read-only | mandatory | The receptacle control toggle status. |
| 1.3.6.1.4.1.705.1.9.1.1.11 | ColumnmgreceptacleToggleDuration | read-write | mandatory | Turn off then on UPS receptacle w/duration=?. |
| 1.3.6.1.4.1.705.1.9.2 | ScalarupsmgControlDayOff | read-write | mandatory | The schedule off control object. Default value is none(8). Value 1 means to start scheduled off on Sunday, value 2 to start scheduled off on Monday, and so on. |
| 1.3.6.1.4.1.705.1.9.3 | ScalarupsmgControlDayOn | read-write | mandatory | The schedule on control object. Default value is none(8). Value 1 means to start scheduled on on Sunday, value 2 to start scheduled on on Monday, and so on. Th… |
| 1.3.6.1.4.1.705.1.10 | NodeupsmgTest | |||
| 1.3.6.1.4.1.705.1.10.1 | ScalarupsmgTestBatterySchedule | read-write | mandatory | The automatic battery test schedule. |
| 1.3.6.1.4.1.705.1.10.2 | ScalarupsmgTestDiagnostics | read-write | mandatory | To run self test diagnostics. |
| 1.3.6.1.4.1.705.1.10.3 | ScalarupsmgTestDiagResult | read-only | mandatory | The automatic test diagnostic result. |
| 1.3.6.1.4.1.705.1.10.4 | ScalarupsmgTestBatteryCalibration | read-write | mandatory | To run battery test calibration. |
| 1.3.6.1.4.1.705.1.10.5 | ScalarupsmgTestLastCalibration | read-only | mandatory | The last battery calibration test date. |
| 1.3.6.1.4.1.705.1.10.6 | ScalarupsmgTestIndicators | read-write | mandatory | To run UPS indicators test. |
| 1.3.6.1.4.1.705.1.10.7 | ScalarupsmgTestCommandLine | read-write | mandatory | To send ASCII command line to UPS. |
| 1.3.6.1.4.1.705.1.10.8 | ScalarupsmgTestCommandReady | read-write | mandatory | To advise UPS that command line has been prepared. |
| 1.3.6.1.4.1.705.1.10.9 | ScalarupsmgTestResponseLine | read-only | mandatory | To get ASCII protocol response from UPS. |
| 1.3.6.1.4.1.705.1.10.10 | ScalarupsmgTestResponseReady | read-only | mandatory | To advise agent that response line has been received. |
| 1.3.6.1.4.1.705.1.10.11 | ScalarupsmgTestBatteryResult | read-only | mandatory | The test battery result: msuccess(1) is for manual battery test success, ssuccess(3) is for scheduled battery test success, mfailed(2) is for manual battery te… |
| 1.3.6.1.4.1.705.1.11 | NodeupsmgTraps | |||
| 1.3.6.1.4.1.705.1.11.1 | NodeupsmgBatteryFault | Trap UPS Battery entering Fault status. | ||
| 1.3.6.1.4.1.705.1.11.2 | NodeupsmgBatteryOK | Trap UPS Battery returned to OK status. | ||
| 1.3.6.1.4.1.705.1.11.3 | NodeupsmgBatteryReplacementIndicated | Trap UPS battery need to be replaced. | ||
| 1.3.6.1.4.1.705.1.11.4 | NodeupsmgBatteryReplaceNotIndicated | Trap UPS battery does not need to be replaced. | ||
| 1.3.6.1.4.1.705.1.11.5 | NodeupsmgAtLowBattery | Trap UPS battery reached low condition. | ||
| 1.3.6.1.4.1.705.1.11.6 | NodeupsmgFromLowBattery | Trap UPS battery returned from low condition. | ||
| 1.3.6.1.4.1.705.1.11.7 | NodeupsmgChargerFault | Trap UPS battery charger is not active. | ||
| 1.3.6.1.4.1.705.1.11.8 | NodeupsmgChargerOK | Trap UPS battery charger is active. | ||
| 1.3.6.1.4.1.705.1.11.9 | NodeupsmgAtLowCondition | Trap UPS entering low condition. | ||
| 1.3.6.1.4.1.705.1.11.10 | NodeupsmgFromLowCondition | Trap UPS exiting low condition. | ||
| 1.3.6.1.4.1.705.1.11.11 | NodeupsmgOnBattery | Trap UPS is on Battery. | ||
| 1.3.6.1.4.1.705.1.11.12 | NodeupsmgReturnFromBattery | Trap UPS returned from battery. | ||
| 1.3.6.1.4.1.705.1.11.13 | NodeupsmgOnByPass | Trap UPS is on by pass. | ||
| 1.3.6.1.4.1.705.1.11.14 | NodeupsmgReturnFromByPass | Trap UPS return from by pass. | ||
| 1.3.6.1.4.1.705.1.11.15 | NodeupsmgByPassUnavailable | Trap UPS by pass unavailable. | ||
| 1.3.6.1.4.1.705.1.11.16 | NodeupsmgByPassAvailable | Trap UPS by pass available. | ||
| 1.3.6.1.4.1.705.1.11.17 | NodeupsmgUtilityFailure | Trap UPS utility power failed. | ||
| 1.3.6.1.4.1.705.1.11.18 | NodeupsmgUtilityRestored | Trap UPS utility power restored. | ||
| 1.3.6.1.4.1.705.1.11.19 | NodeupsmgOnBoost | Trap UPS is on boost. | ||
| 1.3.6.1.4.1.705.1.11.20 | NodeupsmgReturnFromBoost | Trap UPS has returned from boost. | ||
| 1.3.6.1.4.1.705.1.11.21 | NodeupsmgOverLoad | Trap UPS has overload condition. | ||
| 1.3.6.1.4.1.705.1.11.22 | NodeupsmgLoadOK | Trap UPS quit overload condition. | ||
| 1.3.6.1.4.1.705.1.11.23 | NodeupsmgOverTemperature | Trap UPS has overtemperature condition. | ||
| 1.3.6.1.4.1.705.1.11.24 | NodeupsmgTemperatureOK | Trap UPS quit overtemperature condition. | ||
| 1.3.6.1.4.1.705.1.11.25 | NodeupsmgOnToStart | Trap UPS on sequence started. | ||
| 1.3.6.1.4.1.705.1.11.26 | NodeupsmgOnAbort | Trap UPS on sequence cancelled. | ||
| 1.3.6.1.4.1.705.1.11.27 | NodeupsmgOnInProgress | Trap UPS on sequence in progress in ups. | ||
| 1.3.6.1.4.1.705.1.11.28 | NodeupsmgOnComplete | Trap UPS on sequence completed. | ||
| 1.3.6.1.4.1.705.1.11.29 | NodeupsmgOffToStart | Trap UPS off sequence started. | ||
| 1.3.6.1.4.1.705.1.11.30 | NodeupsmgOffAbort | Trap UPS off sequence cancelled. | ||
| 1.3.6.1.4.1.705.1.11.31 | NodeupsmgOffInProgress | Trap UPS off sequence in progress in ups. | ||
| 1.3.6.1.4.1.705.1.11.32 | NodeupsmgOffComplete | Trap UPS off sequence completed. | ||
| 1.3.6.1.4.1.705.1.11.33 | NodeupsmgToggleToStart | Trap UPS toggle (off/on) sequence started. | ||
| 1.3.6.1.4.1.705.1.11.34 | NodeupsmgToggleAbort | Trap UPS toggle (off/on) sequence cancelled. | ||
| 1.3.6.1.4.1.705.1.11.35 | NodeupsmgToggleInProgress | Trap UPS toggle (off/on) sequence in progress in ups. | ||
| 1.3.6.1.4.1.705.1.11.36 | NodeupsmgToggleComplete | Trap UPS toggle (off/on) sequence completed. | ||
| 1.3.6.1.4.1.705.1.11.37 | NodeupsmgCommunicationFailure | Trap UPS serial communication failed. | ||
| 1.3.6.1.4.1.705.1.11.38 | NodeupsmgCommunicationRestored | Trap UPS serial communication restored. | ||
| 1.3.6.1.4.1.705.1.11.39 | NodeupsmgInputBad | Trap UPS input has bad condition. | ||
| 1.3.6.1.4.1.705.1.11.40 | NodeupsmgInputOK | Trap UPS input quit bad condition. | ||
| 1.3.6.1.4.1.705.1.11.41 | NodeupsmgBatteryUnavailable | Trap UPS battery is unavailable. | ||
| 1.3.6.1.4.1.705.1.11.42 | NodeupsmgBatteryAvailable | Trap UPS battery return from unavailable condition. | ||
| 1.3.6.1.4.1.705.1.11.43 | NodeupsmgAtLowRecharge | Trap UPS waiting for battery charging condition. | ||
| 1.3.6.1.4.1.705.1.11.44 | NodeupsmgFromLowRecharge | Trap UPS reached battery charging condition. | ||
| 1.3.6.1.4.1.705.1.11.45 | NodeupsmgDiagnosticTestFail | Trap UPS self test failed. | ||
| 1.3.6.1.4.1.705.1.11.46 | NodeupsmgDiagnosticTestOK | Trap UPS self test succeeded. | ||
| 1.3.6.1.4.1.705.1.11.47 | NodeupsmgBatteryTestOK | Trap UPS passed battery test. | ||
| 1.3.6.1.4.1.705.1.11.48 | NodeupsmgBatteryTestFail | Trap UPS failed battery test. | ||
| 1.3.6.1.4.1.705.1.11.49 | NodeupsmgExternalAlarmActive | Trap UPS enter environment external alarm. | ||
| 1.3.6.1.4.1.705.1.11.50 | NodeupsmgExternalAlarmInactive | Trap UPS exit environment external alarm. | ||
| 1.3.6.1.4.1.705.1.11.51 | NodeupsmgOnBuck | Trap UPS is on buck. | ||
| 1.3.6.1.4.1.705.1.11.52 | NodeupsmgReturnFromBuck | Trap UPS has returned from buck. | ||
| 1.3.6.1.4.1.705.1.11.53 | NodeupsmgEnvironComFailure | Environment Probe communication failure. | ||
| 1.3.6.1.4.1.705.1.11.54 | NodeupsmgEnvironComOK | Environment Probe communication restored. | ||
| 1.3.6.1.4.1.705.1.11.55 | NodeupsmgEnvironTemperatureLow | Temperature is below low threshold. | ||
| 1.3.6.1.4.1.705.1.11.56 | NodeupsmgEnvironTemperatureHigh | Temperature is above high threshold. | ||
| 1.3.6.1.4.1.705.1.11.57 | NodeupsmgEnvironTemperatureOK | Temperature is in normal range. | ||
| 1.3.6.1.4.1.705.1.11.58 | NodeupsmgEnvironHumidityLow | Humidity is below low threshold. | ||
| 1.3.6.1.4.1.705.1.11.59 | NodeupsmgEnvironHumidityHigh | Humidity is above high threshold. | ||
| 1.3.6.1.4.1.705.1.11.60 | NodeupsmgEnvironHumidityOK | Humidity is in normal range. | ||
| 1.3.6.1.4.1.705.1.11.61 | NodeupsmgEnvironInput1Closed | Input #1 is Closed. | ||
| 1.3.6.1.4.1.705.1.11.62 | NodeupsmgEnvironInput1Open | Input #1 is Open. | ||
| 1.3.6.1.4.1.705.1.11.63 | NodeupsmgEnvironInput2Closed | Input #2 is Closed. | ||
| 1.3.6.1.4.1.705.1.11.64 | NodeupsmgEnvironInput2Open | Input #2 is Open. | ||
| 1.3.6.1.4.1.705.1.11.65 | NodeupsRedundancyLost | Redundancy Lost. | ||
| 1.3.6.1.4.1.705.1.11.66 | NodeupsRedundancyOK | Redundancy Recovered. | ||
| 1.3.6.1.4.1.705.1.11.67 | NodeupsProtectionLost | Protection Lost. | ||
| 1.3.6.1.4.1.705.1.11.68 | NodeupsProtectionOK | Protection Recovered. | ||
| 1.3.6.1.4.1.705.1.12 | NodeupsmgAgent | |||
| 1.3.6.1.4.1.705.1.12.1 | ScalarupsmgAgentIpaddress | read-write | mandatory | The ip address that NMS can identify the managed device |
| 1.3.6.1.4.1.705.1.12.2 | ScalarupsmgAgentSubnetMask | read-write | mandatory | Internet address subnet mask |
| 1.3.6.1.4.1.705.1.12.3 | ScalarupsmgAgentDefGateway | read-write | mandatory | The default gateway that allow device managed through routers |
| 1.3.6.1.4.1.705.1.12.4 | ScalarupsmgAgentBaudRate | read-write | mandatory | the serial port communication speed. only 2400, 4800, and 9600 allowed |
| 1.3.6.1.4.1.705.1.12.5 | ScalarupsmgAgentPollRate | read-write | mandatory | The frequency that proxy agent polls the connected UPS in ASCII protocol. (unit : second) |
| 1.3.6.1.4.1.705.1.12.6 | ScalarupsmgAgentType | read-write | mandatory | The type of agent. |
| 1.3.6.1.4.1.705.1.12.7 | ScalarupsmgAgentTrapAlarmDelay | read-write | mandatory | The interval for the Trap packet retransmission, while the TRAP Acknowledge is implemented and the ack is received within the interval. |
| 1.3.6.1.4.1.705.1.12.8 | ScalarupsmgAgentTrapAlarmRetry | read-write | mandatory | The retry count for retransmitting Trap packet while the TRAP acknowledge is implemented. |
| 1.3.6.1.4.1.705.1.12.9 | ScalarupsmgAgentReset | read-write | mandatory | The variable initiates reset operation in agent software, ie. warm start. write reset(1) to any one of UPS MIB array, will result in the same reset operation. |
| 1.3.6.1.4.1.705.1.12.10 | ScalarupsmgAgentFactReset | read-write | mandatory | The variable initiates reset operation in agent software, ie. warm start, and load default data (Factory setting) to EEPROM and to runtime parameters associate… |
| 1.3.6.1.4.1.705.1.12.11 | ScalarupsmgAgentMibVersion | read-only | mandatory | The version of the MIB implemented in agent. |
| 1.3.6.1.4.1.705.1.12.12 | ScalarupsmgAgentFirmwareVersion | read-only | mandatory | The agent firmware version. |
| 1.3.6.1.4.1.705.1.12.13 | ScalarupsmgAgentCommUPS | read-only | mandatory | The status of communication between agent and ups. Even value means no communication, and odd value means a certain level of communication with devices daisy-c… |
| 1.3.6.1.4.1.705.1.12.14 | ScalarupsmgAgentTrapAck | read-write | mandatory | The last Trap number that has been received by UM-View. |
| 1.3.6.1.4.1.705.1.12.15 | ScalarupsmgAgentAutoLearning | read-write | mandatory | The enabled/disabled configuration of the Auto Learning process of the agent, default value is yes(1) e.g. enabled. |
| 1.3.6.1.4.1.705.1.12.16 | ScalarupsmgAgentBootP | read-write | mandatory | The enabled/disabled configuration of the BootP process, default value is yes(1) e.g. enabled. |
| 1.3.6.1.4.1.705.1.12.17 | ScalarupsmgAgentTFTP | read-write | mandatory | The enabled/disabled configuration of the TFTP process, default value is no(2) e.g. disabled. |
| 1.3.6.1.4.1.705.1.12.18 | ScalarupsmgAgentTrapSignature | read-only | mandatory | The signature of the trap acknowledged by a manager. |
| 1.3.6.1.4.1.705.1.13 | NodeupsmgRemote | |||
| 1.3.6.1.4.1.705.1.13.1 | ScalarupsmgRemoteOnBattery | read-write | mandatory | An object to inform an ups-less agent that the remote UPS is on autonomy. This object could be set by a management application. |
| 1.3.6.1.4.1.705.1.13.2 | ScalarupsmgRemoteIpAddress | read-write | mandatory | An object to give the IP address of the agent managing the remote UPS. This object could be read by managers to perform management of receptacle dependencies b… |