MIB Viewer

MG-SNMP-UPS-MIB

307 objects
No module-level DESCRIPTION found.
Imported Objects
RFC-1212OBJECT-TYPE
RFC-1215TRAP-TYPE
RFC1155-SMIenterprises IpAddress TimeTicks
RFC1213-MIBDisplayString
OIDNameAccessStatusDescription
1.3.6.1.4.1.705NodemerlinGerin
1.3.6.1.4.1.705.1Nodeupsmg
1.3.6.1.4.1.705.1.1NodeupsmgIdent
1.3.6.1.4.1.705.1.1.1ScalarupsmgIdentFamilyNameread-writemandatoryThe UPS family name (e.g. `PULSAR', `COMET', `GALAXY', ...).
1.3.6.1.4.1.705.1.1.2ScalarupsmgIdentModelNameread-writemandatoryThe UPS model name (e.g. `PSX20', `SV9', ... ).
1.3.6.1.4.1.705.1.1.3ScalarupsmgIdentRevisionLevelread-writemandatoryThe UPS revision level.
1.3.6.1.4.1.705.1.1.4ScalarupsmgIdentFirmwareVersionread-writemandatoryThe UPS microprocessor firmware version number.
1.3.6.1.4.1.705.1.1.5ScalarupsmgIdentUserIDread-writemandatoryThe UPS user identification (set by administrator).
1.3.6.1.4.1.705.1.1.6ScalarupsmgIdentInstallationDateread-writemandatoryThe UPS installation date in dd/mm/yy format.
1.3.6.1.4.1.705.1.1.7ScalarupsmgIdentSerialNumberread-writemandatoryThe UPS manufacturing serial number.
1.3.6.1.4.1.705.1.2NodeupsmgManagement
1.3.6.1.4.1.705.1.2.1ScalarupsmgManagersNumread-onlymandatoryThe number of managers that could manage the UPS.
1.3.6.1.4.1.705.1.2.2TableupsmgManagersTablenot-accessiblemandatoryThe table of managers.
1.3.6.1.4.1.705.1.2.2.1RowupsmgManagersEntrynot-accessiblemandatoryThe description of a manager entry in the managers table.
1.3.6.1.4.1.705.1.2.2.1.1ColumnmgmanagerIndexread-onlymandatoryA unique value for each manager. Its value ranges between 1 and the value of upsmgManagersNum.
1.3.6.1.4.1.705.1.2.2.1.2ColumnmgmanagerDeviceNumberread-writemandatoryThis object is the number of the manager device in the DevicesTable of the Config group. This means that the manager is powered by the UPS. If not the default …
1.3.6.1.4.1.705.1.2.2.1.3ColumnmgmanagerNMSTyperead-writemandatoryThe type of manager according to the NMS platform. We include in the manager class all systems which will be notified by the agent via receiving traps (e.g. ba…
1.3.6.1.4.1.705.1.2.2.1.4ColumnmgmanagerCommTyperead-writemandatoryThe level of communication protocol for that manager. Setting this object to value invalid(2) has the effect of invalidating the corresponding entry in the ups…
1.3.6.1.4.1.705.1.2.2.1.5ColumnmgmanagerDescrread-writemandatoryA textual string containing information about the manager. (manufacturer and version description).
1.3.6.1.4.1.705.1.2.2.1.6ColumnmgmanagerAddressread-writemandatoryThe IP address of the manager station receiving traps. The value of this object is meaningful if and only if the value of the relevant mgmanagerCommType object…
1.3.6.1.4.1.705.1.2.2.1.7ColumnmgmanagerCommunityread-writemandatoryThe manager community string.
1.3.6.1.4.1.705.1.2.2.1.8ColumnmgmanagerSeverityLevelread-writemandatoryThe severity level of traps to be received by this manager.
1.3.6.1.4.1.705.1.2.2.1.9ColumnmgmanagerTrapAckread-writemandatoryThe manager Trap Acknowledgement status. Setting this object to mgnoack(2) or stdnomg(3) or cpqnoack(5) disables the trap acknowledgement from the related mana…
1.3.6.1.4.1.705.1.3NodeupsmgReceptacle
1.3.6.1.4.1.705.1.3.1ScalarupsmgReceptaclesNumread-onlymandatoryThe total number of receptacles controlled by the UPS.
1.3.6.1.4.1.705.1.3.2TableupsmgReceptaclesTablenot-accessiblemandatoryThe table of receptacles that are controlled by the UPS.
1.3.6.1.4.1.705.1.3.2.1RowupsmgReceptaclesEntrynot-accessiblemandatoryThe description of a receptacle in the table.
1.3.6.1.4.1.705.1.3.2.1.1ColumnmgreceptacleIndexread-onlymandatoryA unique value for each receptacle. Its value ranges between 1 and the value of upsmgReceptaclesNum.
1.3.6.1.4.1.705.1.3.2.1.2ColumnmgreceptacleLevelread-writemandatoryThe level of receptacle. Setting this object to value invalid(2) has the effect of invalidating the corresponding entry in the upsmgReceptaclesTable. It is an …
1.3.6.1.4.1.705.1.3.2.1.3ColumnmgreceptacleTyperead-writemandatoryA textual string for the receptacle type.
1.3.6.1.4.1.705.1.3.2.1.4ColumnmgreceptacleIdentread-writemandatoryA textual string identification for the user.
1.3.6.1.4.1.705.1.3.2.1.5ColumnmgreceptacleStateread-onlymandatoryThe ON/OFF status of the receptacle.
1.3.6.1.4.1.705.1.3.2.1.6ColumnmgreceptacleReceptacleread-writemandatoryThe receptacle number of the second level receptacle father. The value of this object is meaningful if and only if the value of the relevant mgreceptacleType o…
1.3.6.1.4.1.705.1.3.2.1.7ColumnmgreceptaclePowerConsread-writemandatoryThe volt-ampere rating of the receptacle. The value of this object is meaningful if and only if the value of the relevant mgreceptacleType object is related to…
1.3.6.1.4.1.705.1.3.2.1.8ColumnmgreceptacleOverloadread-writemandatoryThe overload status of the receptacle. The value of this object is meaningful if and only if the value of the relevant mgreceptacleType object is related to a …
1.3.6.1.4.1.705.1.3.2.1.9ColumnmgreceptacleAutonomyread-writemandatoryThe receptacle autonomy. The value of this object is meaningful if and only if the value of the relevant mgreceptacleType object is related to a two-level rece…
1.3.6.1.4.1.705.1.4NodeupsmgConfig
1.3.6.1.4.1.705.1.4.1ScalarupsmgConfigBatteryInstalledread-writemandatoryThe battery installed status.
1.3.6.1.4.1.705.1.4.2ScalarupsmgConfigNominalBatteryVoltageread-writemandatoryThe nominal battery voltage.
1.3.6.1.4.1.705.1.4.3ScalarupsmgConfigNominalBatteryTimeread-writemandatoryThe full load battery autonomy time.
1.3.6.1.4.1.705.1.4.4ScalarupsmgConfigNominalRechargeTimeread-writemandatoryThe recharge time to go from low battery cut off to full charge at full load.
1.3.6.1.4.1.705.1.4.5ScalarupsmgConfigMinRechargeLevelread-writemandatoryThe minimum battery level required to supply power on the loads after low battery condition turn off and restart on main return.
1.3.6.1.4.1.705.1.4.6ScalarupsmgConfigMaxRechargeTimeread-writemandatoryThe maximum time delay of battery recharge before supply power to the loads.
1.3.6.1.4.1.705.1.4.7ScalarupsmgConfigLowBatteryTimeread-writemandatoryTo set remaining time value for low battery condition.
1.3.6.1.4.1.705.1.4.8ScalarupsmgConfigLowBatteryLevelread-writemandatoryTo set battery level value for low battery condition.
1.3.6.1.4.1.705.1.4.9ScalarupsmgConfigAutoRestartread-writemandatoryThe automatic restart enabling status.
1.3.6.1.4.1.705.1.4.10ScalarupsmgConfigShutdownTimerread-writemandatoryTo set ups shutdown timer from on battery condition.
1.3.6.1.4.1.705.1.4.11ScalarupsmgConfigSysShutDurationread-writemandatoryTo set ups shutdown delay (Sn delay).
1.3.6.1.4.1.705.1.4.12ScalarupsmgConfigVARatingread-writemandatoryThe UPS nominal VA rating.
1.3.6.1.4.1.705.1.4.13ScalarupsmgConfigLowTransferread-writemandatoryThe low voltage transfer point.
1.3.6.1.4.1.705.1.4.14ScalarupsmgConfigHighTransferread-writemandatoryThe high voltage transfer point.
1.3.6.1.4.1.705.1.4.15ScalarupsmgConfigOutputNominalVoltageread-writemandatoryThe nominal output voltage.
1.3.6.1.4.1.705.1.4.16ScalarupsmgConfigOutputNominalCurrentread-writemandatoryThe nominal output current.
1.3.6.1.4.1.705.1.4.17ScalarupsmgConfigOutputNomFrequencyread-writemandatoryThe nominal output frequency.
1.3.6.1.4.1.705.1.4.18ScalarupsmgConfigByPassTyperead-writemandatoryThe UPS by pass switch type.
1.3.6.1.4.1.705.1.4.19ScalarupsmgConfigAlarmAudibleread-writemandatoryTo set audible alarm status.
1.3.6.1.4.1.705.1.4.20ScalarupsmgConfigAlarmTimeDelayread-writemandatoryTo set audible alarm time delay.
1.3.6.1.4.1.705.1.4.21ScalarupsmgConfigDevicesNumread-writemandatoryThe number of devices that are powered by the UPS.
1.3.6.1.4.1.705.1.4.22TableupsmgConfigDevicesTablenot-accessiblemandatoryThe table of devices that are powered by the UPS.
1.3.6.1.4.1.705.1.4.22.1RowupsmgConfigDevicesEntrynot-accessiblemandatoryThe description of a device entry in the devices table.
1.3.6.1.4.1.705.1.4.22.1.1ColumnmgdeviceIndexread-onlymandatoryA unique value for each device. Its value ranges between 1 and the value of upsmgDevicesNum.
1.3.6.1.4.1.705.1.4.22.1.2ColumnmgdeviceReceptacleNumread-writemandatoryThe receptacle number of the device plugged into the UPS. This value gives index entry in the ReceptaclesTable object of the Receptacle group. A value of 0 inv…
1.3.6.1.4.1.705.1.4.22.1.3ColumnmgdeviceIdentread-writemandatoryA textual string for device user identification.
1.3.6.1.4.1.705.1.4.22.1.4ColumnmgdeviceVaRatingread-writemandatoryThe volt-ampere rating of the device plugged into the UPS.
1.3.6.1.4.1.705.1.4.22.1.5ColumnmgdeviceSequenceOffread-writemandatoryTo set the device position in the remote shutdown sequence.
1.3.6.1.4.1.705.1.4.22.1.6ColumnmgdeviceSequenceOnread-writemandatoryTo set the device position in the remote reboot sequence.
1.3.6.1.4.1.705.1.4.22.1.7ColumnmgdeviceShutdownDurationread-writemandatoryTo set the duration from start of computer shut-down to complete.
1.3.6.1.4.1.705.1.4.22.1.8ColumnmgdeviceBootUpDurationread-writemandatoryTo set the duration from start of computer boot-up to complete.
1.3.6.1.4.1.705.1.4.23TableupsmgConfigReceptaclesTablenot-accessiblemandatoryThe table of receptacles.
1.3.6.1.4.1.705.1.4.23.1RowupsmgConfigReceptaclesEntrynot-accessiblemandatoryThe description of a receptacle entry in the table.
1.3.6.1.4.1.705.1.4.23.1.1ColumnmgreceptacleIndexbread-onlymandatoryA unique value for each receptacle. Its value ranges between 1 and the value of upsmgReceptaclesNum.
1.3.6.1.4.1.705.1.4.23.1.2ColumnmgreceptacleStateTurnOnread-writemandatoryDefault return state at turn on.
1.3.6.1.4.1.705.1.4.23.1.3ColumnmgreceptacleStateMainReturnread-writemandatoryDefault return state on main return.
1.3.6.1.4.1.705.1.4.23.1.4ColumnmgreceptacleStateDischargeread-writemandatoryDefault return state on main return from battery discharge.
1.3.6.1.4.1.705.1.4.23.1.5ColumnmgreceptacleShutoffLevelread-writemandatoryBattery level for starting shutoff sequence.
1.3.6.1.4.1.705.1.4.23.1.6ColumnmgreceptacleShutoffTimerread-writemandatoryTime delay from on battery for starting shutoff sequence.
1.3.6.1.4.1.705.1.4.23.1.7ColumnmgreceptacleRestartLevelread-writemandatoryBattery level for starting restart sequence.
1.3.6.1.4.1.705.1.4.23.1.8ColumnmgreceptacleRestartDelayread-writemandatoryTime delay for starting restart sequence.
1.3.6.1.4.1.705.1.4.23.1.9ColumnmgreceptacleShutdownDurationread-onlymandatoryMaximum Shutdown Duration for systems powered by this plug.
1.3.6.1.4.1.705.1.4.23.1.10ColumnmgreceptacleBootUpDurationread-onlymandatoryMaximum Reboot Duration for systems powered by this plug.
1.3.6.1.4.1.705.1.4.24ScalarupsmgConfigExtAlarmNumread-onlymandatoryThe number of environ external alarm, value is between 8 and 32..
1.3.6.1.4.1.705.1.4.25TableupsmgConfigExtAlarmTablenot-accessiblemandatoryThe table of environmental external alarms.
1.3.6.1.4.1.705.1.4.25.1RowupsmgConfigExtAlarmEntrynot-accessiblemandatoryThe description of an external alarm in the table.
1.3.6.1.4.1.705.1.4.25.1.1ColumnmgextAlarmIndexread-onlymandatoryA unique value for each external alarm. Its value ranges between 1 and the value of upsmgConfigExtAlarmNum.
1.3.6.1.4.1.705.1.4.25.1.2ColumnmgextAlarmUIDread-writemandatoryA textual string for alarm state user identification.
1.3.6.1.4.1.705.1.4.26ScalarupsmgConfigEmergencyTestFailread-writemandatoryThe emergency condition status on Battery test fail.
1.3.6.1.4.1.705.1.4.27ScalarupsmgConfigEmergencyOnByPassread-writemandatoryThe emergency condition status on By Pass.
1.3.6.1.4.1.705.1.4.28ScalarupsmgConfigEmergencyOverloadread-writemandatoryThe emergency condition status on overload.
1.3.6.1.4.1.705.1.4.29TableupsmgConfigControlDayTablenot-accessiblemandatoryThe table of daily on/off time.
1.3.6.1.4.1.705.1.4.29.1RowupsmgConfigControlDayEntrynot-accessiblemandatoryThe description of a daily on/off time schedule in the table.
1.3.6.1.4.1.705.1.4.29.1.1ColumnmgcontrolDayIndexread-onlymandatoryThe day index. It is a number between 1 and 7, 1 for Sunday, 2 for Monday, ...
1.3.6.1.4.1.705.1.4.29.1.2ColumnmgcontrolDayOnread-writemandatoryTo set daily power on time. Any value greater than 86400 is to disable the Day On.
1.3.6.1.4.1.705.1.4.29.1.3ColumnmgcontrolDayOffread-writemandatoryTo set daily power off time. Any value greater than 86400 is to disable the Day Off.
1.3.6.1.4.1.705.1.4.30ScalarupsmgConfigLowBoosterread-writemandatoryTo set UPS booster low threshold.
1.3.6.1.4.1.705.1.4.31ScalarupsmgConfigHighBoosterread-writemandatoryTo set UPS booster high threshold.
1.3.6.1.4.1.705.1.4.32ScalarupsmgConfigLowFaderread-writemandatoryTo set UPS fader low threshold.
1.3.6.1.4.1.705.1.4.33ScalarupsmgConfigHighFaderread-writemandatoryTo set UPS fader high threshold.
1.3.6.1.4.1.705.1.4.34TableupsmgConfigEnvironmentTablenot-accessiblemandatoryThe table containing the configuration of the environment sensor.
1.3.6.1.4.1.705.1.4.34.1RowupsmgConfigEnvironmentEntrynot-accessiblemandatoryThe description of an entry in the table.
1.3.6.1.4.1.705.1.4.34.1.1ColumnupsmgConfigSensorIndexread-onlymandatoryThe sensor index, ranging from 1 to upsmgEnvironmentNum.
1.3.6.1.4.1.705.1.4.34.1.2ColumnupsmgConfigSensorNameread-writemandatoryThe sensor user-friendly name.
1.3.6.1.4.1.705.1.4.34.1.3ColumnupsmgConfigTemperatureLowread-writemandatoryThe low temperature threshold in unit 0.1 Cel.
1.3.6.1.4.1.705.1.4.34.1.4ColumnupsmgConfigTemperatureHighread-writemandatoryThe high temperature threshold in unit 0.1 Cel.
1.3.6.1.4.1.705.1.4.34.1.5ColumnupsmgConfigTemperatureHysteresisread-writemandatoryThe temperature hysteresys used for threshold test in unit 0.1 Cel.
1.3.6.1.4.1.705.1.4.34.1.6ColumnupsmgConfigHumidityLowread-writemandatoryThe low humidity threshold in unit 1 %.
1.3.6.1.4.1.705.1.4.34.1.7ColumnupsmgConfigHumidityHighread-writemandatoryThe high humidity threshold in unit 1 %.
1.3.6.1.4.1.705.1.4.34.1.8ColumnupsmgConfigHumidityHysteresisread-writemandatoryThe humidity hysteresys used for threshold test in unit 1 %.
1.3.6.1.4.1.705.1.4.34.1.9ColumnupsmgConfigInput1Nameread-writemandatoryThe Input #1 user-friendly name.
1.3.6.1.4.1.705.1.4.34.1.10ColumnupsmgConfigInput1ClosedLabelread-writemandatoryThe Input #1 label for closed position.
1.3.6.1.4.1.705.1.4.34.1.11ColumnupsmgConfigInput1OpenLabelread-writemandatoryThe Input #1 label for open position.
1.3.6.1.4.1.705.1.4.34.1.12ColumnupsmgConfigInput2Nameread-writemandatoryThe Input #2 user-friendly name.
1.3.6.1.4.1.705.1.4.34.1.13ColumnupsmgConfigInput2ClosedLabelread-writemandatoryThe Input #2 label for closed position.
1.3.6.1.4.1.705.1.4.34.1.14ColumnupsmgConfigInput2OpenLabelread-writemandatoryThe Input #2 label for open position.
1.3.6.1.4.1.705.1.5NodeupsmgBattery
1.3.6.1.4.1.705.1.5.1ScalarupsmgBatteryRemainingTimeread-onlymandatoryThe time remaining actual charge vs actual load (dynamic).
1.3.6.1.4.1.705.1.5.2ScalarupsmgBatteryLevelread-onlymandatoryThe battery level as a percentage of charge.
1.3.6.1.4.1.705.1.5.3ScalarupsmgBatteryRechargeTimeread-onlymandatoryThe actual operational battery recharge time to set point equal to upsmgConfigRechargeLevel. This value is computed from upsmgConfigRechargeLevel (level to rea…
1.3.6.1.4.1.705.1.5.4ScalarupsmgBatteryRechargeLevelread-onlymandatoryThe actual value of the battery recharge level that will be reached during the time delay necessary to restart after power returns. This value is computed from…
1.3.6.1.4.1.705.1.5.5ScalarupsmgBatteryVoltageread-onlymandatoryThe actual battery voltage.
1.3.6.1.4.1.705.1.5.6ScalarupsmgBatteryCurrentread-onlymandatoryThe actual battery current.
1.3.6.1.4.1.705.1.5.7ScalarupsmgBatteryTemperatureread-onlymandatoryThe battery temperature.
1.3.6.1.4.1.705.1.5.8ScalarupsmgBatteryFullRechargeTimeread-onlymandatoryThe battery full recharge time (from 0 to 100 percent) at current load.
1.3.6.1.4.1.705.1.5.9ScalarupsmgBatteryFaultBatteryread-onlymandatoryThe battery fault status.
1.3.6.1.4.1.705.1.5.10ScalarupsmgBatteryNoBatteryread-onlymandatoryThe UPS has no Battery status.
1.3.6.1.4.1.705.1.5.11ScalarupsmgBatteryReplacementread-onlymandatoryThe UPS Battery to be replaced status.
1.3.6.1.4.1.705.1.5.12ScalarupsmgBatteryUnavailableBatteryread-onlymandatoryThe UPS Battery is unavailable status.
1.3.6.1.4.1.705.1.5.13ScalarupsmgBatteryNotHighChargeread-onlymandatoryThe UPS Battery quit high condition status.
1.3.6.1.4.1.705.1.5.14ScalarupsmgBatteryLowBatteryread-onlymandatoryThe battery low status.
1.3.6.1.4.1.705.1.5.15ScalarupsmgBatteryChargerFaultread-onlymandatoryThe UPS Battery is not charging status.
1.3.6.1.4.1.705.1.5.16ScalarupsmgBatteryLowConditionread-onlymandatoryThe UPS is at low condition status.
1.3.6.1.4.1.705.1.5.17ScalarupsmgBatteryLowRechargeread-onlymandatoryThe UPS Battery is not recharged status.
1.3.6.1.4.1.705.1.6NodeupsmgInput
1.3.6.1.4.1.705.1.6.1ScalarupsmgInputPhaseNumread-onlymandatoryThe number of input phases.
1.3.6.1.4.1.705.1.6.2TableupsmgInputPhaseTablenot-accessiblemandatoryThe table of input phases.
1.3.6.1.4.1.705.1.6.2.1RowupsmgInputPhaseEntrynot-accessiblemandatoryThe description of an input phase.
1.3.6.1.4.1.705.1.6.2.1.1ColumnmginputIndexread-onlymandatoryThe input phase voltage index. It is a number between 1 and upsmgInputPhaseNum.
1.3.6.1.4.1.705.1.6.2.1.2ColumnmginputVoltageread-onlymandatoryThe input phase voltage.
1.3.6.1.4.1.705.1.6.2.1.3ColumnmginputFrequencyread-onlymandatoryThe input phase frequency.
1.3.6.1.4.1.705.1.6.2.1.4ColumnmginputMinimumVoltageread-onlymandatoryThe input phase minimum voltage over the last minute.
1.3.6.1.4.1.705.1.6.2.1.5ColumnmginputMaximumVoltageread-onlymandatoryThe input phase maximum voltage over the last minute.
1.3.6.1.4.1.705.1.6.2.1.6ColumnmginputCurrentread-onlymandatoryThe input phase current.
1.3.6.1.4.1.705.1.6.3ScalarupsmgInputBadStatusread-onlymandatoryThe utility power bad voltage or bad frequency status.
1.3.6.1.4.1.705.1.6.4ScalarupsmgInputLineFailCauseread-onlymandatoryThe utility power failure cause: no(1) is for no utility failure, outoftolvolt(2) is for voltage out of tolerance, outoftolfreq(3) is for frequency out of tole…
1.3.6.1.4.1.705.1.7NodeupsmgOutput
1.3.6.1.4.1.705.1.7.1ScalarupsmgOutputPhaseNumread-onlymandatoryThe number of output phases.
1.3.6.1.4.1.705.1.7.2TableupsmgOutputPhaseTablenot-accessiblemandatoryThe table of output phases.
1.3.6.1.4.1.705.1.7.2.1RowupsmgOutputPhaseEntrynot-accessiblemandatoryThe description of an output phase.
1.3.6.1.4.1.705.1.7.2.1.1ColumnmgoutputPhaseIndexread-onlymandatoryThe output phase voltage index. It is a number between 1 and upsmgOutputPhaseNum.
1.3.6.1.4.1.705.1.7.2.1.2ColumnmgoutputVoltageread-onlymandatoryThe output phase voltage.
1.3.6.1.4.1.705.1.7.2.1.3ColumnmgoutputFrequencyread-onlymandatoryThe output phase frequency.
1.3.6.1.4.1.705.1.7.2.1.4ColumnmgoutputLoadPerPhaseread-onlymandatoryThe output load per phase.
1.3.6.1.4.1.705.1.7.2.1.5ColumnmgoutputCurrentread-onlymandatoryThe output phase current.
1.3.6.1.4.1.705.1.7.3ScalarupsmgOutputOnBatteryread-onlymandatoryThe UPS on battery / on main status.
1.3.6.1.4.1.705.1.7.4ScalarupsmgOutputOnByPassread-onlymandatoryThe UPS on bypass status.
1.3.6.1.4.1.705.1.7.5ScalarupsmgOutputUnavailableByPassread-onlymandatoryThe by pass unavailable status.
1.3.6.1.4.1.705.1.7.6ScalarupsmgOutputNoByPassread-onlymandatoryThe UPS bypass installed status.
1.3.6.1.4.1.705.1.7.7ScalarupsmgOutputUtilityOffread-onlymandatoryThe UPS utility off status.
1.3.6.1.4.1.705.1.7.8ScalarupsmgOutputOnBoostread-onlymandatoryThe UPS on booster status.
1.3.6.1.4.1.705.1.7.9ScalarupsmgOutputInverterOffread-onlymandatoryThe UPS Inverter on / off status.
1.3.6.1.4.1.705.1.7.10ScalarupsmgOutputOverLoadread-onlymandatoryThe output over load status.
1.3.6.1.4.1.705.1.7.11ScalarupsmgOutputOverTempread-onlymandatoryThe ups over temperature status.
1.3.6.1.4.1.705.1.7.12ScalarupsmgOutputOnBuckread-onlymandatoryThe UPS on fader status.
1.3.6.1.4.1.705.1.8NodeupsmgEnviron
1.3.6.1.4.1.705.1.8.1ScalarupsmgEnvironAmbientTempread-onlymandatoryThe ambient temperature.
1.3.6.1.4.1.705.1.8.2ScalarupsmgEnvironAmbientHumidityread-onlymandatoryThe ambient humidity.
1.3.6.1.4.1.705.1.8.3TableupsmgEnvironExtAlarmTablenot-accessiblemandatoryThe table of external alarms.
1.3.6.1.4.1.705.1.8.3.1RowupsmgEnvironExtAlarmEntrynot-accessiblemandatoryThe description of an external alarm.
1.3.6.1.4.1.705.1.8.3.1.1ColumnmgalarmNumread-onlymandatoryThe external alarm number. A number between 1 and upsmgConfigExtAlarmNum.
1.3.6.1.4.1.705.1.8.3.1.2ColumnmgalarmStateread-onlymandatoryThe external alarm state (active or inactive).
1.3.6.1.4.1.705.1.8.4ScalarupsmgEnvironSensorNumread-onlymandatoryThe sensor unit number (0 to 4).
1.3.6.1.4.1.705.1.8.5TableupsmgEnvironSensorTablenot-accessiblemandatoryThe table of sensor units.
1.3.6.1.4.1.705.1.8.5.1RowupsmgEnvironSensorEntrynot-accessiblemandatoryThe description of a sensor unit.
1.3.6.1.4.1.705.1.8.5.1.1ColumnmgsensorNumread-onlymandatoryThe unit number. A number between 1 and 4.
1.3.6.1.4.1.705.1.8.5.1.2ColumnmgsensorTempread-onlymandatoryThe measured temperature of the unit.
1.3.6.1.4.1.705.1.8.5.1.3ColumnmgsensorHumidityread-onlymandatoryThe measured humidity of the unit.
1.3.6.1.4.1.705.1.8.6ScalarupsmgEnvironmentNumread-onlymandatoryNumber of Environment sensor connected.
1.3.6.1.4.1.705.1.8.7TableupsmgEnvironmentSensorTablenot-accessiblemandatoryThe table containing the measurements and alarms made by Environment sensor units.
1.3.6.1.4.1.705.1.8.7.1RowupsmgEnvironmentSensorEntrynot-accessiblemandatoryThe description of an entry in the measurement table.
1.3.6.1.4.1.705.1.8.7.1.1ColumnupsmgEnvironmentIndexread-onlymandatoryThe sensor index, ranging from 1 to upsmgEnvironmentNum.
1.3.6.1.4.1.705.1.8.7.1.2ColumnupsmgEnvironmentComFailureread-onlymandatoryThe sensor communication failure : yes(1), no(2).
1.3.6.1.4.1.705.1.8.7.1.3ColumnupsmgEnvironmentTemperatureread-onlymandatoryThe temperature measurement in unit 0.1 Cel.
1.3.6.1.4.1.705.1.8.7.1.4ColumnupsmgEnvironmentTemperatureLowread-onlymandatoryTemperature is below low theshold : yes(1), no(2).
1.3.6.1.4.1.705.1.8.7.1.5ColumnupsmgEnvironmentTemperatureHighread-onlymandatoryTemperature is above high threshold : yes(1), no(2).
1.3.6.1.4.1.705.1.8.7.1.6ColumnupsmgEnvironmentHumidityread-onlymandatoryThe humidity measurement in unit 0.1 %.
1.3.6.1.4.1.705.1.8.7.1.7ColumnupsmgEnvironmentHumidityLowread-onlymandatoryHumidity is below low threshold : yes(1), no(2).
1.3.6.1.4.1.705.1.8.7.1.8ColumnupsmgEnvironmentHumidityHighread-onlymandatoryHumidity is above high threshold : yes(1), no(2).
1.3.6.1.4.1.705.1.8.7.1.9ColumnupsmgEnvironmentInput1Stateread-onlymandatoryState of Input#1 : closed(1), open(2).
1.3.6.1.4.1.705.1.8.7.1.10ColumnupsmgEnvironmentInput2Stateread-onlymandatoryState of Input#2 : closed(1), open(2).
1.3.6.1.4.1.705.1.9NodeupsmgControl
1.3.6.1.4.1.705.1.9.1TableupsmgControlReceptaclesTablenot-accessiblemandatoryThe table of receptacles.
1.3.6.1.4.1.705.1.9.1.1RowupsmgControlReceptaclesEntrynot-accessiblemandatoryThe description of a receptacle entry in the table.
1.3.6.1.4.1.705.1.9.1.1.1ColumnmgreceptacleIndexcread-onlymandatoryA unique value for each receptacle. Its value ranges between 1 and the value of upsmgReceptaclesNum.
1.3.6.1.4.1.705.1.9.1.1.2ColumnmgreceptacleOnDelayread-writemandatoryTurn on UPS receptacle w/delay=?.
1.3.6.1.4.1.705.1.9.1.1.3ColumnmgreceptacleOnCtrlread-writemandatoryThe receptacle control on action.
1.3.6.1.4.1.705.1.9.1.1.4ColumnmgreceptacleOnStatusread-onlymandatoryThe receptacle control on status.
1.3.6.1.4.1.705.1.9.1.1.5ColumnmgreceptacleOffDelayread-writemandatoryTurn off UPS receptacle w/delay=?.
1.3.6.1.4.1.705.1.9.1.1.6ColumnmgreceptacleOffCtrlread-writemandatoryThe receptacle control off action.
1.3.6.1.4.1.705.1.9.1.1.7ColumnmgreceptacleOffStatusread-onlymandatoryThe receptacle control off status.
1.3.6.1.4.1.705.1.9.1.1.8ColumnmgreceptacleToggleDelayread-writemandatoryTurn off then on UPS receptacle w/delay=?.
1.3.6.1.4.1.705.1.9.1.1.9ColumnmgreceptacleToggleCtrlread-writemandatoryThe receptacle control toggle action.
1.3.6.1.4.1.705.1.9.1.1.10ColumnmgreceptacleToggleStatusread-onlymandatoryThe receptacle control toggle status.
1.3.6.1.4.1.705.1.9.1.1.11ColumnmgreceptacleToggleDurationread-writemandatoryTurn off then on UPS receptacle w/duration=?.
1.3.6.1.4.1.705.1.9.2ScalarupsmgControlDayOffread-writemandatoryThe schedule off control object. Default value is none(8). Value 1 means to start scheduled off on Sunday, value 2 to start scheduled off on Monday, and so on.
1.3.6.1.4.1.705.1.9.3ScalarupsmgControlDayOnread-writemandatoryThe schedule on control object. Default value is none(8). Value 1 means to start scheduled on on Sunday, value 2 to start scheduled on on Monday, and so on. Th…
1.3.6.1.4.1.705.1.10NodeupsmgTest
1.3.6.1.4.1.705.1.10.1ScalarupsmgTestBatteryScheduleread-writemandatoryThe automatic battery test schedule.
1.3.6.1.4.1.705.1.10.2ScalarupsmgTestDiagnosticsread-writemandatoryTo run self test diagnostics.
1.3.6.1.4.1.705.1.10.3ScalarupsmgTestDiagResultread-onlymandatoryThe automatic test diagnostic result.
1.3.6.1.4.1.705.1.10.4ScalarupsmgTestBatteryCalibrationread-writemandatoryTo run battery test calibration.
1.3.6.1.4.1.705.1.10.5ScalarupsmgTestLastCalibrationread-onlymandatoryThe last battery calibration test date.
1.3.6.1.4.1.705.1.10.6ScalarupsmgTestIndicatorsread-writemandatoryTo run UPS indicators test.
1.3.6.1.4.1.705.1.10.7ScalarupsmgTestCommandLineread-writemandatoryTo send ASCII command line to UPS.
1.3.6.1.4.1.705.1.10.8ScalarupsmgTestCommandReadyread-writemandatoryTo advise UPS that command line has been prepared.
1.3.6.1.4.1.705.1.10.9ScalarupsmgTestResponseLineread-onlymandatoryTo get ASCII protocol response from UPS.
1.3.6.1.4.1.705.1.10.10ScalarupsmgTestResponseReadyread-onlymandatoryTo advise agent that response line has been received.
1.3.6.1.4.1.705.1.10.11ScalarupsmgTestBatteryResultread-onlymandatoryThe test battery result: msuccess(1) is for manual battery test success, ssuccess(3) is for scheduled battery test success, mfailed(2) is for manual battery te…
1.3.6.1.4.1.705.1.11NodeupsmgTraps
1.3.6.1.4.1.705.1.11.1NodeupsmgBatteryFaultTrap UPS Battery entering Fault status.
1.3.6.1.4.1.705.1.11.2NodeupsmgBatteryOKTrap UPS Battery returned to OK status.
1.3.6.1.4.1.705.1.11.3NodeupsmgBatteryReplacementIndicatedTrap UPS battery need to be replaced.
1.3.6.1.4.1.705.1.11.4NodeupsmgBatteryReplaceNotIndicatedTrap UPS battery does not need to be replaced.
1.3.6.1.4.1.705.1.11.5NodeupsmgAtLowBatteryTrap UPS battery reached low condition.
1.3.6.1.4.1.705.1.11.6NodeupsmgFromLowBatteryTrap UPS battery returned from low condition.
1.3.6.1.4.1.705.1.11.7NodeupsmgChargerFaultTrap UPS battery charger is not active.
1.3.6.1.4.1.705.1.11.8NodeupsmgChargerOKTrap UPS battery charger is active.
1.3.6.1.4.1.705.1.11.9NodeupsmgAtLowConditionTrap UPS entering low condition.
1.3.6.1.4.1.705.1.11.10NodeupsmgFromLowConditionTrap UPS exiting low condition.
1.3.6.1.4.1.705.1.11.11NodeupsmgOnBatteryTrap UPS is on Battery.
1.3.6.1.4.1.705.1.11.12NodeupsmgReturnFromBatteryTrap UPS returned from battery.
1.3.6.1.4.1.705.1.11.13NodeupsmgOnByPassTrap UPS is on by pass.
1.3.6.1.4.1.705.1.11.14NodeupsmgReturnFromByPassTrap UPS return from by pass.
1.3.6.1.4.1.705.1.11.15NodeupsmgByPassUnavailableTrap UPS by pass unavailable.
1.3.6.1.4.1.705.1.11.16NodeupsmgByPassAvailableTrap UPS by pass available.
1.3.6.1.4.1.705.1.11.17NodeupsmgUtilityFailureTrap UPS utility power failed.
1.3.6.1.4.1.705.1.11.18NodeupsmgUtilityRestoredTrap UPS utility power restored.
1.3.6.1.4.1.705.1.11.19NodeupsmgOnBoostTrap UPS is on boost.
1.3.6.1.4.1.705.1.11.20NodeupsmgReturnFromBoostTrap UPS has returned from boost.
1.3.6.1.4.1.705.1.11.21NodeupsmgOverLoadTrap UPS has overload condition.
1.3.6.1.4.1.705.1.11.22NodeupsmgLoadOKTrap UPS quit overload condition.
1.3.6.1.4.1.705.1.11.23NodeupsmgOverTemperatureTrap UPS has overtemperature condition.
1.3.6.1.4.1.705.1.11.24NodeupsmgTemperatureOKTrap UPS quit overtemperature condition.
1.3.6.1.4.1.705.1.11.25NodeupsmgOnToStartTrap UPS on sequence started.
1.3.6.1.4.1.705.1.11.26NodeupsmgOnAbortTrap UPS on sequence cancelled.
1.3.6.1.4.1.705.1.11.27NodeupsmgOnInProgressTrap UPS on sequence in progress in ups.
1.3.6.1.4.1.705.1.11.28NodeupsmgOnCompleteTrap UPS on sequence completed.
1.3.6.1.4.1.705.1.11.29NodeupsmgOffToStartTrap UPS off sequence started.
1.3.6.1.4.1.705.1.11.30NodeupsmgOffAbortTrap UPS off sequence cancelled.
1.3.6.1.4.1.705.1.11.31NodeupsmgOffInProgressTrap UPS off sequence in progress in ups.
1.3.6.1.4.1.705.1.11.32NodeupsmgOffCompleteTrap UPS off sequence completed.
1.3.6.1.4.1.705.1.11.33NodeupsmgToggleToStartTrap UPS toggle (off/on) sequence started.
1.3.6.1.4.1.705.1.11.34NodeupsmgToggleAbortTrap UPS toggle (off/on) sequence cancelled.
1.3.6.1.4.1.705.1.11.35NodeupsmgToggleInProgressTrap UPS toggle (off/on) sequence in progress in ups.
1.3.6.1.4.1.705.1.11.36NodeupsmgToggleCompleteTrap UPS toggle (off/on) sequence completed.
1.3.6.1.4.1.705.1.11.37NodeupsmgCommunicationFailureTrap UPS serial communication failed.
1.3.6.1.4.1.705.1.11.38NodeupsmgCommunicationRestoredTrap UPS serial communication restored.
1.3.6.1.4.1.705.1.11.39NodeupsmgInputBadTrap UPS input has bad condition.
1.3.6.1.4.1.705.1.11.40NodeupsmgInputOKTrap UPS input quit bad condition.
1.3.6.1.4.1.705.1.11.41NodeupsmgBatteryUnavailableTrap UPS battery is unavailable.
1.3.6.1.4.1.705.1.11.42NodeupsmgBatteryAvailableTrap UPS battery return from unavailable condition.
1.3.6.1.4.1.705.1.11.43NodeupsmgAtLowRechargeTrap UPS waiting for battery charging condition.
1.3.6.1.4.1.705.1.11.44NodeupsmgFromLowRechargeTrap UPS reached battery charging condition.
1.3.6.1.4.1.705.1.11.45NodeupsmgDiagnosticTestFailTrap UPS self test failed.
1.3.6.1.4.1.705.1.11.46NodeupsmgDiagnosticTestOKTrap UPS self test succeeded.
1.3.6.1.4.1.705.1.11.47NodeupsmgBatteryTestOKTrap UPS passed battery test.
1.3.6.1.4.1.705.1.11.48NodeupsmgBatteryTestFailTrap UPS failed battery test.
1.3.6.1.4.1.705.1.11.49NodeupsmgExternalAlarmActiveTrap UPS enter environment external alarm.
1.3.6.1.4.1.705.1.11.50NodeupsmgExternalAlarmInactiveTrap UPS exit environment external alarm.
1.3.6.1.4.1.705.1.11.51NodeupsmgOnBuckTrap UPS is on buck.
1.3.6.1.4.1.705.1.11.52NodeupsmgReturnFromBuckTrap UPS has returned from buck.
1.3.6.1.4.1.705.1.11.53NodeupsmgEnvironComFailureEnvironment Probe communication failure.
1.3.6.1.4.1.705.1.11.54NodeupsmgEnvironComOKEnvironment Probe communication restored.
1.3.6.1.4.1.705.1.11.55NodeupsmgEnvironTemperatureLowTemperature is below low threshold.
1.3.6.1.4.1.705.1.11.56NodeupsmgEnvironTemperatureHighTemperature is above high threshold.
1.3.6.1.4.1.705.1.11.57NodeupsmgEnvironTemperatureOKTemperature is in normal range.
1.3.6.1.4.1.705.1.11.58NodeupsmgEnvironHumidityLowHumidity is below low threshold.
1.3.6.1.4.1.705.1.11.59NodeupsmgEnvironHumidityHighHumidity is above high threshold.
1.3.6.1.4.1.705.1.11.60NodeupsmgEnvironHumidityOKHumidity is in normal range.
1.3.6.1.4.1.705.1.11.61NodeupsmgEnvironInput1ClosedInput #1 is Closed.
1.3.6.1.4.1.705.1.11.62NodeupsmgEnvironInput1OpenInput #1 is Open.
1.3.6.1.4.1.705.1.11.63NodeupsmgEnvironInput2ClosedInput #2 is Closed.
1.3.6.1.4.1.705.1.11.64NodeupsmgEnvironInput2OpenInput #2 is Open.
1.3.6.1.4.1.705.1.11.65NodeupsRedundancyLostRedundancy Lost.
1.3.6.1.4.1.705.1.11.66NodeupsRedundancyOKRedundancy Recovered.
1.3.6.1.4.1.705.1.11.67NodeupsProtectionLostProtection Lost.
1.3.6.1.4.1.705.1.11.68NodeupsProtectionOKProtection Recovered.
1.3.6.1.4.1.705.1.12NodeupsmgAgent
1.3.6.1.4.1.705.1.12.1ScalarupsmgAgentIpaddressread-writemandatoryThe ip address that NMS can identify the managed device
1.3.6.1.4.1.705.1.12.2ScalarupsmgAgentSubnetMaskread-writemandatoryInternet address subnet mask
1.3.6.1.4.1.705.1.12.3ScalarupsmgAgentDefGatewayread-writemandatoryThe default gateway that allow device managed through routers
1.3.6.1.4.1.705.1.12.4ScalarupsmgAgentBaudRateread-writemandatorythe serial port communication speed. only 2400, 4800, and 9600 allowed
1.3.6.1.4.1.705.1.12.5ScalarupsmgAgentPollRateread-writemandatoryThe frequency that proxy agent polls the connected UPS in ASCII protocol. (unit : second)
1.3.6.1.4.1.705.1.12.6ScalarupsmgAgentTyperead-writemandatoryThe type of agent.
1.3.6.1.4.1.705.1.12.7ScalarupsmgAgentTrapAlarmDelayread-writemandatoryThe interval for the Trap packet retransmission, while the TRAP Acknowledge is implemented and the ack is received within the interval.
1.3.6.1.4.1.705.1.12.8ScalarupsmgAgentTrapAlarmRetryread-writemandatoryThe retry count for retransmitting Trap packet while the TRAP acknowledge is implemented.
1.3.6.1.4.1.705.1.12.9ScalarupsmgAgentResetread-writemandatoryThe variable initiates reset operation in agent software, ie. warm start. write reset(1) to any one of UPS MIB array, will result in the same reset operation.
1.3.6.1.4.1.705.1.12.10ScalarupsmgAgentFactResetread-writemandatoryThe variable initiates reset operation in agent software, ie. warm start, and load default data (Factory setting) to EEPROM and to runtime parameters associate…
1.3.6.1.4.1.705.1.12.11ScalarupsmgAgentMibVersionread-onlymandatoryThe version of the MIB implemented in agent.
1.3.6.1.4.1.705.1.12.12ScalarupsmgAgentFirmwareVersionread-onlymandatoryThe agent firmware version.
1.3.6.1.4.1.705.1.12.13ScalarupsmgAgentCommUPSread-onlymandatoryThe status of communication between agent and ups. Even value means no communication, and odd value means a certain level of communication with devices daisy-c…
1.3.6.1.4.1.705.1.12.14ScalarupsmgAgentTrapAckread-writemandatoryThe last Trap number that has been received by UM-View.
1.3.6.1.4.1.705.1.12.15ScalarupsmgAgentAutoLearningread-writemandatoryThe enabled/disabled configuration of the Auto Learning process of the agent, default value is yes(1) e.g. enabled.
1.3.6.1.4.1.705.1.12.16ScalarupsmgAgentBootPread-writemandatoryThe enabled/disabled configuration of the BootP process, default value is yes(1) e.g. enabled.
1.3.6.1.4.1.705.1.12.17ScalarupsmgAgentTFTPread-writemandatoryThe enabled/disabled configuration of the TFTP process, default value is no(2) e.g. disabled.
1.3.6.1.4.1.705.1.12.18ScalarupsmgAgentTrapSignatureread-onlymandatoryThe signature of the trap acknowledged by a manager.
1.3.6.1.4.1.705.1.13NodeupsmgRemote
1.3.6.1.4.1.705.1.13.1ScalarupsmgRemoteOnBatteryread-writemandatoryAn object to inform an ups-less agent that the remote UPS is on autonomy. This object could be set by a management application.
1.3.6.1.4.1.705.1.13.2ScalarupsmgRemoteIpAddressread-writemandatoryAn object to give the IP address of the agent managing the remote UPS. This object could be read by managers to perform management of receptacle dependencies b…