MITSUBISHI-UPS-MIB
119 objects
No module-level DESCRIPTION found.
Imported Objects
| RFC-1212 | OBJECT-TYPE |
| RFC-1215 | TRAP-TYPE |
| RFC1155-SMI | Counter Gauge mgmt TimeTicks |
| RFC1213-MIB | DisplayString |
| OID | Name | Access | Status | Description |
|---|---|---|---|---|
| 1.3.6.1.4.1.13891 | NodeTag | |||
| 1.3.6.1.4.1.13891.101 | NodeMitsubishiUPS | |||
| 1.3.6.1.4.1.13891.101.1 | NodealarmCritical | Critical alarm. | ||
| 1.3.6.1.4.1.13891.101.1 | NodeupsIdent | |||
| 1.3.6.1.4.1.13891.101.1.1 | ScalarupsIdentManufacturer | read-only | mandatory | The name of the UPS manufacturer. |
| 1.3.6.1.4.1.13891.101.1.2 | ScalarupsIdentModel | read-only | mandatory | The UPS Model designation. |
| 1.3.6.1.4.1.13891.101.1.3 | ScalarupsIdentUPSSoftwareVersion | read-only | mandatory | The UPS firmware/software version(s). This variable may or may not have the same value as upsIdentAgentSoftwareVersion in some implementations. |
| 1.3.6.1.4.1.13891.101.1.4 | ScalarupsIdentAgentSoftwareVersion | read-only | mandatory | The UPS agent software version. This variable may or may not have the same value as upsIdentUPSSoftwareVersion in some implementations. |
| 1.3.6.1.4.1.13891.101.1.5 | ScalarupsIdentName | read-write | mandatory | A string identifying the UPS. This object should be set by the administrator. |
| 1.3.6.1.4.1.13891.101.1.6 | ScalarupsIdentAttachedDevices | read-write | mandatory | A string identifying the devices attached to the output of the UPS. This object should be set by the administrator. |
| 1.3.6.1.4.1.13891.101.2 | NodealarmWarning | Warning alarm. | ||
| 1.3.6.1.4.1.13891.101.2 | NodeupsBattery | |||
| 1.3.6.1.4.1.13891.101.2.1 | ScalarupsBatteryStatus | read-only | mandatory | The indication of the capacity remaining in the UPS batteries. A value of batteryNormal indicates a normal battery condition. A value of batteryLow indicates t… |
| 1.3.6.1.4.1.13891.101.2.2 | ScalarupsSecondsOnBattery | read-only | mandatory | If the unit is on battery power, the elapsed time in seconds since the UPS last switched to battery power, or the time since the network management system was … |
| 1.3.6.1.4.1.13891.101.2.3 | ScalarupsEstimatedMinutesRemaining | read-only | mandatory | An estimate of the time in minutes until the battery is depleted under the present load conditions if the utility power is off and remains off, or if it were t… |
| 1.3.6.1.4.1.13891.101.2.4 | ScalarupsEstimatedChargeRemaining | read-only | mandatory | An estimate of the battery charge remaining expressed as a percent of full charge. |
| 1.3.6.1.4.1.13891.101.2.5 | ScalarupsBatteryVoltage | read-only | mandatory | The magnitude of the present battery voltage (0.1 Volt DC). |
| 1.3.6.1.4.1.13891.101.2.6 | ScalarupsBatteryCurrent | read-only | mandatory | The present battery current (0.1 Amp DC). |
| 1.3.6.1.4.1.13891.101.2.7 | ScalarupsBatteryTemperature | read-only | mandatory | The ambient temperature at or near the UPS Battery casing (degrees Centigrade). |
| 1.3.6.1.4.1.13891.101.3 | NodealarmInformation | Information alarm. | ||
| 1.3.6.1.4.1.13891.101.3 | NodeupsInput | |||
| 1.3.6.1.4.1.13891.101.3.1 | ScalarupsInputLineBads | read-only | mandatory | A count of the number of times the input entered an out-of-tolerance condition as defined by the manufacturer. This count is incremented by one each time the i… |
| 1.3.6.1.4.1.13891.101.3.2 | ScalarupsInputNumLines | read-only | mandatory | The number of input lines utilized in this device. This variable indicates the number of rows in the input table. |
| 1.3.6.1.4.1.13891.101.3.3 | TableupsInputTable | not-accessible | mandatory | A list of input table entries. The number of entries is given by the value of upsInputNumLines. |
| 1.3.6.1.4.1.13891.101.3.3.1 | RowupsInputEntry | not-accessible | mandatory | An entry containing information applicable to a particular input line. |
| 1.3.6.1.4.1.13891.101.3.3.1.1 | ColumnupsInputLineIndex | read-only | mandatory | The input line identifier. |
| 1.3.6.1.4.1.13891.101.3.3.1.2 | ColumnupsInputFrequency | read-only | mandatory | The present input frequency (0.1 Hertz). |
| 1.3.6.1.4.1.13891.101.3.3.1.3 | ColumnupsInputVoltage | read-only | mandatory | The magnitude of the present input voltage (0.1 RMS Volt). |
| 1.3.6.1.4.1.13891.101.3.3.1.4 | ColumnupsInputCurrent | read-only | mandatory | The magnitude of the present input current (0.1 RMS Amp). |
| 1.3.6.1.4.1.13891.101.3.3.1.5 | ColumnupsInputTruePower | read-only | mandatory | The magnitude of the present input true power (watts). |
| 1.3.6.1.4.1.13891.101.4 | NodeupsAlarmCleared | Alarm cleared. | ||
| 1.3.6.1.4.1.13891.101.4 | NodeupsOutput | |||
| 1.3.6.1.4.1.13891.101.4.1 | ScalarupsOutputSource | read-only | mandatory | The present source of output power. A value of none (2) indicates there is no source of output power (and therefore no output power), for example, the system h… |
| 1.3.6.1.4.1.13891.101.4.2 | ScalarupsOutputFrequency | read-only | mandatory | The present output frequency (0.1 Hertz). |
| 1.3.6.1.4.1.13891.101.4.3 | ScalarupsOutputNumLines | read-only | mandatory | The number of output lines utilized in this device. This variable indicates the number of rows in the output table. |
| 1.3.6.1.4.1.13891.101.4.4 | TableupsOutputTable | not-accessible | mandatory | A list of output table entries. The number of entries is given by the value of upsOutputNumLines. |
| 1.3.6.1.4.1.13891.101.4.4.1 | RowupsOutputEntry | not-accessible | mandatory | An entry containing information applicable to a particular output line. |
| 1.3.6.1.4.1.13891.101.4.4.1.1 | ColumnupsOutputLineIndex | read-only | mandatory | The output line identifier. |
| 1.3.6.1.4.1.13891.101.4.4.1.2 | ColumnupsOutputVoltage | read-only | mandatory | The present output voltage (0.1 RMS Volt). |
| 1.3.6.1.4.1.13891.101.4.4.1.3 | ColumnupsOutputCurrent | read-only | mandatory | The present output current (0.1 RMS Amp). |
| 1.3.6.1.4.1.13891.101.4.4.1.4 | ColumnupsOutputPower | read-only | mandatory | The present output true power (watts). |
| 1.3.6.1.4.1.13891.101.4.4.1.5 | ColumnupsOutputPercentLoad | read-only | mandatory | The percentage of the UPS power capacity presently being used on this output line (the greater of the percent load of true power capacity and the percent load … |
| 1.3.6.1.4.1.13891.101.5 | NodeupsBypass | |||
| 1.3.6.1.4.1.13891.101.5 | NodeupsTrapInitialization | This trap is sent each time a NetCom device is initialized. | ||
| 1.3.6.1.4.1.13891.101.5.1 | ScalarupsBypassFrequency | read-only | mandatory | The present bypass frequency. |
| 1.3.6.1.4.1.13891.101.5.2 | ScalarupsBypassNumLines | read-only | mandatory | The number of bypass lines utilized in this device. This entry indicates the number of rows in the bypass table. |
| 1.3.6.1.4.1.13891.101.5.3 | TableupsBypassTable | not-accessible | mandatory | A list of bypass table entries. The number of entries is given by the value of upsBypassNumLines. |
| 1.3.6.1.4.1.13891.101.5.3.1 | RowupsBypassEntry | not-accessible | mandatory | An entry containing information applicable to a particular bypass input. |
| 1.3.6.1.4.1.13891.101.5.3.1.1 | ColumnupsBypassLineIndex | read-only | mandatory | The bypass line identifier. |
| 1.3.6.1.4.1.13891.101.5.3.1.2 | ColumnupsBypassVoltage | read-only | mandatory | The present bypass voltage (0.1 RMS Volt). |
| 1.3.6.1.4.1.13891.101.5.3.1.3 | ColumnupsBypassCurrent | read-only | mandatory | The present bypass current (0.1 RMS Amp). |
| 1.3.6.1.4.1.13891.101.5.3.1.4 | ColumnupsBypassPower | read-only | mandatory | The present true power conveyed by the bypass (watts). |
| 1.3.6.1.4.1.13891.101.6 | NodeupsAlarm | |||
| 1.3.6.1.4.1.13891.101.6.1 | ScalarupsAlarmsPresent | read-only | mandatory | The present number of active alarm conditions. |
| 1.3.6.1.4.1.13891.101.6.2 | TableupsAlarmTable | not-accessible | mandatory | A list of alarm table entries. Alarms are named by an OBJECT IDENTIFIER, upsAlarmDescr, to allow a single table to reflect well known alarms plus alarms define… |
| 1.3.6.1.4.1.13891.101.6.2.1 | RowupsAlarmEntry | not-accessible | mandatory | An entry containing information applicable to a particular alarm. |
| 1.3.6.1.4.1.13891.101.6.2.1.1 | ColumnupsAlarmId | read-only | mandatory | A unique identifier for an alarm condition. This value must remain constant. |
| 1.3.6.1.4.1.13891.101.6.2.1.2 | ColumnupsAlarmDescr | read-only | mandatory | A reference to an alarm description object. The object referenced should not be accessible, but rather be used to provide a unique description of the alarm con… |
| 1.3.6.1.4.1.13891.101.6.2.1.3 | ColumnupsAlarmTime | read-only | mandatory | The value of sysUpTime when the alarm condition was detected. If the alarm condition was detected at the time of agent startup and presumably existed before ag… |
| 1.3.6.1.4.1.13891.101.6.3 | NodeupsWellKnownAlarms | |||
| 1.3.6.1.4.1.13891.101.6.3.1 | ScalarupsAlarmBatteryBad | read-only | mandatory | One or more batteries have been determined to require replacement. |
| 1.3.6.1.4.1.13891.101.6.3.2 | ScalarupsAlarmOnBattery | read-only | mandatory | The UPS is drawing power from the batteries. |
| 1.3.6.1.4.1.13891.101.6.3.3 | ScalarupsAlarmLowBattery | read-only | mandatory | The remaining battery run-time is less than or equal to upsConfigLowBattTime. |
| 1.3.6.1.4.1.13891.101.6.3.4 | ScalarupsAlarmDepletedBattery | read-only | mandatory | The UPS will be unable to sustain the present load when and if the utility power is lost. |
| 1.3.6.1.4.1.13891.101.6.3.5 | ScalarupsAlarmTempBad | read-only | mandatory | A temperature is out of tolerance. |
| 1.3.6.1.4.1.13891.101.6.3.6 | ScalarupsAlarmInputBad | read-only | mandatory | An input condition is out of tolerance. |
| 1.3.6.1.4.1.13891.101.6.3.7 | ScalarupsAlarmOutputBad | read-only | mandatory | An output condition (other than OutputOverload) is out of tolerance. |
| 1.3.6.1.4.1.13891.101.6.3.8 | ScalarupsAlarmOutputOverload | read-only | mandatory | The output load exceeds the UPS output capacity. |
| 1.3.6.1.4.1.13891.101.6.3.9 | ScalarupsAlarmOnBypass | read-only | mandatory | The Bypass is presently engaged on the UPS. |
| 1.3.6.1.4.1.13891.101.6.3.10 | ScalarupsAlarmBypassBad | read-only | mandatory | The Bypass is out of tolerance. |
| 1.3.6.1.4.1.13891.101.6.3.11 | ScalarupsAlarmOutputOffAsRequested | read-only | mandatory | The UPS has shut down as requested, i.e., the output is off. |
| 1.3.6.1.4.1.13891.101.6.3.12 | ScalarupsAlarmUpsOffAsRequested | read-only | mandatory | The entire UPS has shutdown as commanded. |
| 1.3.6.1.4.1.13891.101.6.3.13 | ScalarupsAlarmChargerFailed | read-only | mandatory | An uncorrected problem has been detected within the UPS charger subsystem. |
| 1.3.6.1.4.1.13891.101.6.3.14 | ScalarupsAlarmUpsOutputOff | read-only | mandatory | The output of the UPS is in the off state. |
| 1.3.6.1.4.1.13891.101.6.3.15 | ScalarupsAlarmUpsSystemOff | read-only | mandatory | The UPS system is in the off state. |
| 1.3.6.1.4.1.13891.101.6.3.16 | ScalarupsAlarmFanFailure | read-only | mandatory | The failure of one or more fans in the UPS has been detected. |
| 1.3.6.1.4.1.13891.101.6.3.17 | ScalarupsAlarmFuseFailure | read-only | mandatory | The failure of one or more fuses has been detected. |
| 1.3.6.1.4.1.13891.101.6.3.18 | ScalarupsAlarmGeneralFault | read-only | mandatory | A general fault in the UPS has been detected. |
| 1.3.6.1.4.1.13891.101.6.3.19 | ScalarupsAlarmDiagnosticTestFailed | read-only | mandatory | The result of the last diagnostic test indicates a failure. |
| 1.3.6.1.4.1.13891.101.6.3.20 | ScalarupsAlarmCommunicationsLost | read-only | mandatory | A problem has been encountered in the communications between the agent and the UPS. |
| 1.3.6.1.4.1.13891.101.6.3.21 | ScalarupsAlarmAwaitingPower | read-only | mandatory | The UPS output is off and the UPS is awaiting the return of input power. |
| 1.3.6.1.4.1.13891.101.6.3.22 | ScalarupsAlarmShutdownPending | read-only | mandatory | A upsShutdownAfterDelay countdown is underway. |
| 1.3.6.1.4.1.13891.101.6.3.23 | ScalarupsAlarmShutdownImminent | read-only | mandatory | The UPS will turn off power to the load in less than 5 seconds; this may be either a timed shutdown or a low battery shutdown. |
| 1.3.6.1.4.1.13891.101.6.3.24 | ScalarupsAlarmTestInProgress | read-only | mandatory | A test is in progress, as initiated and indicated by the Test Group. Tests initiated via other implementation-specific mechanisms can indicate the presence of … |
| 1.3.6.1.4.1.13891.101.6.4 | ScalarupsAlarmID | read-only | mandatory | A unique identifier for an alarm condition. This value must remain constant. |
| 1.3.6.1.4.1.13891.101.6.5 | ScalarupsAlarmDESCR | read-only | mandatory | A reference to an alarm description object. The object references should not be accessible, but rather be used to provide a unique description of the alarm con… |
| 1.3.6.1.4.1.13891.101.7 | NodeupsTest | |||
| 1.3.6.1.4.1.13891.101.7.1 | ScalarupsTestId | read-write | mandatory | The test named by an OBJECT IDENTIFIER which allows a standard mechanism for the initiation of a test, including the well known tests identified in this docume… |
| 1.3.6.1.4.1.13891.101.7.2 | ScalarupsTestSpinLock | read-write | mandatory | A spin lock on the test subsystem. |
| 1.3.6.1.4.1.13891.101.7.3 | ScalarupsTestResultsSummary | read-only | mandatory | The results of the current or last UPS diagnostics test performed. The values for donePass(1), doneWarning(2), and doneError(3) indicate that the test complete… |
| 1.3.6.1.4.1.13891.101.7.4 | ScalarupsTestResultsDetail | read-only | mandatory | Additional information about upsTestResultsSummary. If no additional information available, a zero length string is returned. |
| 1.3.6.1.4.1.13891.101.7.5 | ScalarupsTestStartTime | read-only | mandatory | The value of sysUpTime at the time the test in progress was initiated, or, if no test is in progress, the time the previous test was initiated. If the value of… |
| 1.3.6.1.4.1.13891.101.7.6 | ScalarupsTestElapsedTime | read-only | mandatory | The amount of time, in TimeTicks, since the test in progress was initiated, or, if no test is in progress, the previous test took to complete. If the value of … |
| 1.3.6.1.4.1.13891.101.7.7 | NodeupsWellKnownTests | |||
| 1.3.6.1.4.1.13891.101.7.7.1 | ScalarupsTestNoTestsInitiated | read-only | mandatory | No tests have been initiated and no test is in progress. |
| 1.3.6.1.4.1.13891.101.7.7.2 | ScalarupsTestAbortTestInProgress | read-only | mandatory | The test in progress is to be aborted / the test in progress was aborted. |
| 1.3.6.1.4.1.13891.101.7.7.3 | ScalarupsTestGeneralSystemsTest | read-only | mandatory | The manufacturer's standard test of UPS device systems. |
| 1.3.6.1.4.1.13891.101.7.7.4 | ScalarupsTestQuickBatteryTest | read-only | mandatory | A test that is sufficient to determine if the battery needs replacement. |
| 1.3.6.1.4.1.13891.101.7.7.5 | ScalarupsTestDeepBatteryCalibration | read-only | mandatory | The system is placed on battery to a discharge level, set by the manufacturer, sufficient to determine battery replacement and battery run-time with a high deg… |
| 1.3.6.1.4.1.13891.101.8 | NodeupsControl | |||
| 1.3.6.1.4.1.13891.101.8.1 | ScalarupsShutdownType | read-write | mandatory | This object determines the nature of the action to be taken at the time when the countdown of the upsShutdownAfterDelay and upsRebootWithDuration objects reach… |
| 1.3.6.1.4.1.13891.101.8.2 | ScalarupsShutdownAfterDelay | read-write | mandatory | Setting this object will shutdown (i.e., turn off) either the UPS output or the UPS system (as determined by the value of upsShutdownType at the time of shutdo… |
| 1.3.6.1.4.1.13891.101.8.3 | ScalarupsStartupAfterDelay | read-write | mandatory | Setting this object will start the output after the indicated number of seconds, including starting the UPS, if necessary. Setting this object to 0 will cause … |
| 1.3.6.1.4.1.13891.101.8.4 | ScalarupsRebootWithDuration | read-write | mandatory | Setting this object will immediately shutdown (i.e., turn off) either the UPS output or the UPS system (as determined by the value of upsShutdownType at the ti… |
| 1.3.6.1.4.1.13891.101.8.5 | ScalarupsAutoRestart | read-write | mandatory | Setting this object to 'on' will cause the UPS system to restart after a shutdown if the shutdown occurred during a power loss as a result of either a upsShutd… |
| 1.3.6.1.4.1.13891.101.9 | NodeupsConfig | |||
| 1.3.6.1.4.1.13891.101.9.1 | ScalarupsConfigInputVoltage | read-write | mandatory | The magnitude of the nominal input voltage (RMS Volts). On those systems which support read-write access to this object, if there is an attempt to set this var… |
| 1.3.6.1.4.1.13891.101.9.2 | ScalarupsConfigInputFreq | read-write | mandatory | The nominal input frequency (0.1 Hertz). On those systems which support read-write access to this object, if there is an attempt to set this variable to a valu… |
| 1.3.6.1.4.1.13891.101.9.3 | ScalarupsConfigOutputVoltage | read-write | mandatory | The magnitude of the nominal output voltage (RMS Volts). On those systems which support read-write access to this object, if there is an attempt to set this va… |
| 1.3.6.1.4.1.13891.101.9.4 | ScalarupsConfigOutputFreq | read-write | mandatory | The nominal output frequency (0.1 Hertz). On those systems which support read-write access to this object, if there is an attempt to set this variable to a val… |
| 1.3.6.1.4.1.13891.101.9.5 | ScalarupsConfigOutputVA | read-only | mandatory | The magnitude of the nominal Volt-Amp rating (Volt-Amps). |
| 1.3.6.1.4.1.13891.101.9.6 | ScalarupsConfigOutputPower | read-only | mandatory | The magnitude of the nominal true power rating (watts). |
| 1.3.6.1.4.1.13891.101.9.7 | ScalarupsConfigLowBattTime | read-write | mandatory | The value of upsEstimatedMinutesRemaining at which a lowBattery condition is declared. For agents which support only discrete (discontinuous) values, then the … |
| 1.3.6.1.4.1.13891.101.9.8 | ScalarupsConfigAudibleStatus | read-write | mandatory | The requested state of the audible alarm. When in the disabled state, the audible alarm should never sound. The enabled state is self-describing. Setting this … |
| 1.3.6.1.4.1.13891.101.9.9 | ScalarupsConfigLowVoltageTransferPoint | read-write | mandatory | The minimum input line voltage (RMS Volts) allowed before the UPS system transfers to battery backup. |
| 1.3.6.1.4.1.13891.101.9.10 | ScalarupsConfigHighVoltageTransferPoint | read-write | mandatory | The maximum line voltage (RMS Volts) allowed before the UPS system transfers to battery backup. |
| 1.3.6.1.4.1.13891.101.10 | NodeupsTrapInfo | |||
| 1.3.6.1.4.1.13891.101.10.1 | ScalartrapCode | read-only | mandatory | A number identifying the event for that last trap that was sent. |
| 1.3.6.1.4.1.13891.101.10.2 | ScalartrapDescription | read-only | mandatory | A string identifying the event for that last trap that was sent. |