MITSUBISHI-UPS-MIB

119 objects
No module-level DESCRIPTION found.
Imported Objects
RFC-1212OBJECT-TYPE
RFC-1215TRAP-TYPE
RFC1155-SMICounter Gauge mgmt TimeTicks
RFC1213-MIBDisplayString
OIDNameAccessStatusDescription
1.3.6.1.4.1.13891NodeTag
1.3.6.1.4.1.13891.101NodeMitsubishiUPS
1.3.6.1.4.1.13891.101.1NodealarmCriticalCritical alarm.
1.3.6.1.4.1.13891.101.1NodeupsIdent
1.3.6.1.4.1.13891.101.1.1ScalarupsIdentManufacturerread-onlymandatoryThe name of the UPS manufacturer.
1.3.6.1.4.1.13891.101.1.2ScalarupsIdentModelread-onlymandatoryThe UPS Model designation.
1.3.6.1.4.1.13891.101.1.3ScalarupsIdentUPSSoftwareVersionread-onlymandatoryThe UPS firmware/software version(s). This variable may or may not have the same value as upsIdentAgentSoftwareVersion in some implementations.
1.3.6.1.4.1.13891.101.1.4ScalarupsIdentAgentSoftwareVersionread-onlymandatoryThe UPS agent software version. This variable may or may not have the same value as upsIdentUPSSoftwareVersion in some implementations.
1.3.6.1.4.1.13891.101.1.5ScalarupsIdentNameread-writemandatoryA string identifying the UPS. This object should be set by the administrator.
1.3.6.1.4.1.13891.101.1.6ScalarupsIdentAttachedDevicesread-writemandatoryA string identifying the devices attached to the output of the UPS. This object should be set by the administrator.
1.3.6.1.4.1.13891.101.2NodealarmWarningWarning alarm.
1.3.6.1.4.1.13891.101.2NodeupsBattery
1.3.6.1.4.1.13891.101.2.1ScalarupsBatteryStatusread-onlymandatoryThe indication of the capacity remaining in the UPS batteries. A value of batteryNormal indicates a normal battery condition. A value of batteryLow indicates t…
1.3.6.1.4.1.13891.101.2.2ScalarupsSecondsOnBatteryread-onlymandatoryIf the unit is on battery power, the elapsed time in seconds since the UPS last switched to battery power, or the time since the network management system was …
1.3.6.1.4.1.13891.101.2.3ScalarupsEstimatedMinutesRemainingread-onlymandatoryAn estimate of the time in minutes until the battery is depleted under the present load conditions if the utility power is off and remains off, or if it were t…
1.3.6.1.4.1.13891.101.2.4ScalarupsEstimatedChargeRemainingread-onlymandatoryAn estimate of the battery charge remaining expressed as a percent of full charge.
1.3.6.1.4.1.13891.101.2.5ScalarupsBatteryVoltageread-onlymandatoryThe magnitude of the present battery voltage (0.1 Volt DC).
1.3.6.1.4.1.13891.101.2.6ScalarupsBatteryCurrentread-onlymandatoryThe present battery current (0.1 Amp DC).
1.3.6.1.4.1.13891.101.2.7ScalarupsBatteryTemperatureread-onlymandatoryThe ambient temperature at or near the UPS Battery casing (degrees Centigrade).
1.3.6.1.4.1.13891.101.3NodealarmInformationInformation alarm.
1.3.6.1.4.1.13891.101.3NodeupsInput
1.3.6.1.4.1.13891.101.3.1ScalarupsInputLineBadsread-onlymandatoryA count of the number of times the input entered an out-of-tolerance condition as defined by the manufacturer. This count is incremented by one each time the i…
1.3.6.1.4.1.13891.101.3.2ScalarupsInputNumLinesread-onlymandatoryThe number of input lines utilized in this device. This variable indicates the number of rows in the input table.
1.3.6.1.4.1.13891.101.3.3TableupsInputTablenot-accessiblemandatoryA list of input table entries. The number of entries is given by the value of upsInputNumLines.
1.3.6.1.4.1.13891.101.3.3.1RowupsInputEntrynot-accessiblemandatoryAn entry containing information applicable to a particular input line.
1.3.6.1.4.1.13891.101.3.3.1.1ColumnupsInputLineIndexread-onlymandatoryThe input line identifier.
1.3.6.1.4.1.13891.101.3.3.1.2ColumnupsInputFrequencyread-onlymandatoryThe present input frequency (0.1 Hertz).
1.3.6.1.4.1.13891.101.3.3.1.3ColumnupsInputVoltageread-onlymandatoryThe magnitude of the present input voltage (0.1 RMS Volt).
1.3.6.1.4.1.13891.101.3.3.1.4ColumnupsInputCurrentread-onlymandatoryThe magnitude of the present input current (0.1 RMS Amp).
1.3.6.1.4.1.13891.101.3.3.1.5ColumnupsInputTruePowerread-onlymandatoryThe magnitude of the present input true power (watts).
1.3.6.1.4.1.13891.101.4NodeupsAlarmClearedAlarm cleared.
1.3.6.1.4.1.13891.101.4NodeupsOutput
1.3.6.1.4.1.13891.101.4.1ScalarupsOutputSourceread-onlymandatoryThe present source of output power. A value of none (2) indicates there is no source of output power (and therefore no output power), for example, the system h…
1.3.6.1.4.1.13891.101.4.2ScalarupsOutputFrequencyread-onlymandatoryThe present output frequency (0.1 Hertz).
1.3.6.1.4.1.13891.101.4.3ScalarupsOutputNumLinesread-onlymandatoryThe number of output lines utilized in this device. This variable indicates the number of rows in the output table.
1.3.6.1.4.1.13891.101.4.4TableupsOutputTablenot-accessiblemandatoryA list of output table entries. The number of entries is given by the value of upsOutputNumLines.
1.3.6.1.4.1.13891.101.4.4.1RowupsOutputEntrynot-accessiblemandatoryAn entry containing information applicable to a particular output line.
1.3.6.1.4.1.13891.101.4.4.1.1ColumnupsOutputLineIndexread-onlymandatoryThe output line identifier.
1.3.6.1.4.1.13891.101.4.4.1.2ColumnupsOutputVoltageread-onlymandatoryThe present output voltage (0.1 RMS Volt).
1.3.6.1.4.1.13891.101.4.4.1.3ColumnupsOutputCurrentread-onlymandatoryThe present output current (0.1 RMS Amp).
1.3.6.1.4.1.13891.101.4.4.1.4ColumnupsOutputPowerread-onlymandatoryThe present output true power (watts).
1.3.6.1.4.1.13891.101.4.4.1.5ColumnupsOutputPercentLoadread-onlymandatoryThe percentage of the UPS power capacity presently being used on this output line (the greater of the percent load of true power capacity and the percent load …
1.3.6.1.4.1.13891.101.5NodeupsBypass
1.3.6.1.4.1.13891.101.5NodeupsTrapInitializationThis trap is sent each time a NetCom device is initialized.
1.3.6.1.4.1.13891.101.5.1ScalarupsBypassFrequencyread-onlymandatoryThe present bypass frequency.
1.3.6.1.4.1.13891.101.5.2ScalarupsBypassNumLinesread-onlymandatoryThe number of bypass lines utilized in this device. This entry indicates the number of rows in the bypass table.
1.3.6.1.4.1.13891.101.5.3TableupsBypassTablenot-accessiblemandatoryA list of bypass table entries. The number of entries is given by the value of upsBypassNumLines.
1.3.6.1.4.1.13891.101.5.3.1RowupsBypassEntrynot-accessiblemandatoryAn entry containing information applicable to a particular bypass input.
1.3.6.1.4.1.13891.101.5.3.1.1ColumnupsBypassLineIndexread-onlymandatoryThe bypass line identifier.
1.3.6.1.4.1.13891.101.5.3.1.2ColumnupsBypassVoltageread-onlymandatoryThe present bypass voltage (0.1 RMS Volt).
1.3.6.1.4.1.13891.101.5.3.1.3ColumnupsBypassCurrentread-onlymandatoryThe present bypass current (0.1 RMS Amp).
1.3.6.1.4.1.13891.101.5.3.1.4ColumnupsBypassPowerread-onlymandatoryThe present true power conveyed by the bypass (watts).
1.3.6.1.4.1.13891.101.6NodeupsAlarm
1.3.6.1.4.1.13891.101.6.1ScalarupsAlarmsPresentread-onlymandatoryThe present number of active alarm conditions.
1.3.6.1.4.1.13891.101.6.2TableupsAlarmTablenot-accessiblemandatoryA list of alarm table entries. Alarms are named by an OBJECT IDENTIFIER, upsAlarmDescr, to allow a single table to reflect well known alarms plus alarms define…
1.3.6.1.4.1.13891.101.6.2.1RowupsAlarmEntrynot-accessiblemandatoryAn entry containing information applicable to a particular alarm.
1.3.6.1.4.1.13891.101.6.2.1.1ColumnupsAlarmIdread-onlymandatoryA unique identifier for an alarm condition. This value must remain constant.
1.3.6.1.4.1.13891.101.6.2.1.2ColumnupsAlarmDescrread-onlymandatoryA reference to an alarm description object. The object referenced should not be accessible, but rather be used to provide a unique description of the alarm con…
1.3.6.1.4.1.13891.101.6.2.1.3ColumnupsAlarmTimeread-onlymandatoryThe value of sysUpTime when the alarm condition was detected. If the alarm condition was detected at the time of agent startup and presumably existed before ag…
1.3.6.1.4.1.13891.101.6.3NodeupsWellKnownAlarms
1.3.6.1.4.1.13891.101.6.3.1ScalarupsAlarmBatteryBadread-onlymandatoryOne or more batteries have been determined to require replacement.
1.3.6.1.4.1.13891.101.6.3.2ScalarupsAlarmOnBatteryread-onlymandatoryThe UPS is drawing power from the batteries.
1.3.6.1.4.1.13891.101.6.3.3ScalarupsAlarmLowBatteryread-onlymandatoryThe remaining battery run-time is less than or equal to upsConfigLowBattTime.
1.3.6.1.4.1.13891.101.6.3.4ScalarupsAlarmDepletedBatteryread-onlymandatoryThe UPS will be unable to sustain the present load when and if the utility power is lost.
1.3.6.1.4.1.13891.101.6.3.5ScalarupsAlarmTempBadread-onlymandatoryA temperature is out of tolerance.
1.3.6.1.4.1.13891.101.6.3.6ScalarupsAlarmInputBadread-onlymandatoryAn input condition is out of tolerance.
1.3.6.1.4.1.13891.101.6.3.7ScalarupsAlarmOutputBadread-onlymandatoryAn output condition (other than OutputOverload) is out of tolerance.
1.3.6.1.4.1.13891.101.6.3.8ScalarupsAlarmOutputOverloadread-onlymandatoryThe output load exceeds the UPS output capacity.
1.3.6.1.4.1.13891.101.6.3.9ScalarupsAlarmOnBypassread-onlymandatoryThe Bypass is presently engaged on the UPS.
1.3.6.1.4.1.13891.101.6.3.10ScalarupsAlarmBypassBadread-onlymandatoryThe Bypass is out of tolerance.
1.3.6.1.4.1.13891.101.6.3.11ScalarupsAlarmOutputOffAsRequestedread-onlymandatoryThe UPS has shut down as requested, i.e., the output is off.
1.3.6.1.4.1.13891.101.6.3.12ScalarupsAlarmUpsOffAsRequestedread-onlymandatoryThe entire UPS has shutdown as commanded.
1.3.6.1.4.1.13891.101.6.3.13ScalarupsAlarmChargerFailedread-onlymandatoryAn uncorrected problem has been detected within the UPS charger subsystem.
1.3.6.1.4.1.13891.101.6.3.14ScalarupsAlarmUpsOutputOffread-onlymandatoryThe output of the UPS is in the off state.
1.3.6.1.4.1.13891.101.6.3.15ScalarupsAlarmUpsSystemOffread-onlymandatoryThe UPS system is in the off state.
1.3.6.1.4.1.13891.101.6.3.16ScalarupsAlarmFanFailureread-onlymandatoryThe failure of one or more fans in the UPS has been detected.
1.3.6.1.4.1.13891.101.6.3.17ScalarupsAlarmFuseFailureread-onlymandatoryThe failure of one or more fuses has been detected.
1.3.6.1.4.1.13891.101.6.3.18ScalarupsAlarmGeneralFaultread-onlymandatoryA general fault in the UPS has been detected.
1.3.6.1.4.1.13891.101.6.3.19ScalarupsAlarmDiagnosticTestFailedread-onlymandatoryThe result of the last diagnostic test indicates a failure.
1.3.6.1.4.1.13891.101.6.3.20ScalarupsAlarmCommunicationsLostread-onlymandatoryA problem has been encountered in the communications between the agent and the UPS.
1.3.6.1.4.1.13891.101.6.3.21ScalarupsAlarmAwaitingPowerread-onlymandatoryThe UPS output is off and the UPS is awaiting the return of input power.
1.3.6.1.4.1.13891.101.6.3.22ScalarupsAlarmShutdownPendingread-onlymandatoryA upsShutdownAfterDelay countdown is underway.
1.3.6.1.4.1.13891.101.6.3.23ScalarupsAlarmShutdownImminentread-onlymandatoryThe UPS will turn off power to the load in less than 5 seconds; this may be either a timed shutdown or a low battery shutdown.
1.3.6.1.4.1.13891.101.6.3.24ScalarupsAlarmTestInProgressread-onlymandatoryA test is in progress, as initiated and indicated by the Test Group. Tests initiated via other implementation-specific mechanisms can indicate the presence of …
1.3.6.1.4.1.13891.101.6.4ScalarupsAlarmIDread-onlymandatoryA unique identifier for an alarm condition. This value must remain constant.
1.3.6.1.4.1.13891.101.6.5ScalarupsAlarmDESCRread-onlymandatoryA reference to an alarm description object. The object references should not be accessible, but rather be used to provide a unique description of the alarm con…
1.3.6.1.4.1.13891.101.7NodeupsTest
1.3.6.1.4.1.13891.101.7.1ScalarupsTestIdread-writemandatoryThe test named by an OBJECT IDENTIFIER which allows a standard mechanism for the initiation of a test, including the well known tests identified in this docume…
1.3.6.1.4.1.13891.101.7.2ScalarupsTestSpinLockread-writemandatoryA spin lock on the test subsystem.
1.3.6.1.4.1.13891.101.7.3ScalarupsTestResultsSummaryread-onlymandatoryThe results of the current or last UPS diagnostics test performed. The values for donePass(1), doneWarning(2), and doneError(3) indicate that the test complete…
1.3.6.1.4.1.13891.101.7.4ScalarupsTestResultsDetailread-onlymandatoryAdditional information about upsTestResultsSummary. If no additional information available, a zero length string is returned.
1.3.6.1.4.1.13891.101.7.5ScalarupsTestStartTimeread-onlymandatoryThe value of sysUpTime at the time the test in progress was initiated, or, if no test is in progress, the time the previous test was initiated. If the value of…
1.3.6.1.4.1.13891.101.7.6ScalarupsTestElapsedTimeread-onlymandatoryThe amount of time, in TimeTicks, since the test in progress was initiated, or, if no test is in progress, the previous test took to complete. If the value of …
1.3.6.1.4.1.13891.101.7.7NodeupsWellKnownTests
1.3.6.1.4.1.13891.101.7.7.1ScalarupsTestNoTestsInitiatedread-onlymandatoryNo tests have been initiated and no test is in progress.
1.3.6.1.4.1.13891.101.7.7.2ScalarupsTestAbortTestInProgressread-onlymandatoryThe test in progress is to be aborted / the test in progress was aborted.
1.3.6.1.4.1.13891.101.7.7.3ScalarupsTestGeneralSystemsTestread-onlymandatoryThe manufacturer's standard test of UPS device systems.
1.3.6.1.4.1.13891.101.7.7.4ScalarupsTestQuickBatteryTestread-onlymandatoryA test that is sufficient to determine if the battery needs replacement.
1.3.6.1.4.1.13891.101.7.7.5ScalarupsTestDeepBatteryCalibrationread-onlymandatoryThe system is placed on battery to a discharge level, set by the manufacturer, sufficient to determine battery replacement and battery run-time with a high deg…
1.3.6.1.4.1.13891.101.8NodeupsControl
1.3.6.1.4.1.13891.101.8.1ScalarupsShutdownTyperead-writemandatoryThis object determines the nature of the action to be taken at the time when the countdown of the upsShutdownAfterDelay and upsRebootWithDuration objects reach…
1.3.6.1.4.1.13891.101.8.2ScalarupsShutdownAfterDelayread-writemandatorySetting this object will shutdown (i.e., turn off) either the UPS output or the UPS system (as determined by the value of upsShutdownType at the time of shutdo…
1.3.6.1.4.1.13891.101.8.3ScalarupsStartupAfterDelayread-writemandatorySetting this object will start the output after the indicated number of seconds, including starting the UPS, if necessary. Setting this object to 0 will cause …
1.3.6.1.4.1.13891.101.8.4ScalarupsRebootWithDurationread-writemandatorySetting this object will immediately shutdown (i.e., turn off) either the UPS output or the UPS system (as determined by the value of upsShutdownType at the ti…
1.3.6.1.4.1.13891.101.8.5ScalarupsAutoRestartread-writemandatorySetting this object to 'on' will cause the UPS system to restart after a shutdown if the shutdown occurred during a power loss as a result of either a upsShutd…
1.3.6.1.4.1.13891.101.9NodeupsConfig
1.3.6.1.4.1.13891.101.9.1ScalarupsConfigInputVoltageread-writemandatoryThe magnitude of the nominal input voltage (RMS Volts). On those systems which support read-write access to this object, if there is an attempt to set this var…
1.3.6.1.4.1.13891.101.9.2ScalarupsConfigInputFreqread-writemandatoryThe nominal input frequency (0.1 Hertz). On those systems which support read-write access to this object, if there is an attempt to set this variable to a valu…
1.3.6.1.4.1.13891.101.9.3ScalarupsConfigOutputVoltageread-writemandatoryThe magnitude of the nominal output voltage (RMS Volts). On those systems which support read-write access to this object, if there is an attempt to set this va…
1.3.6.1.4.1.13891.101.9.4ScalarupsConfigOutputFreqread-writemandatoryThe nominal output frequency (0.1 Hertz). On those systems which support read-write access to this object, if there is an attempt to set this variable to a val…
1.3.6.1.4.1.13891.101.9.5ScalarupsConfigOutputVAread-onlymandatoryThe magnitude of the nominal Volt-Amp rating (Volt-Amps).
1.3.6.1.4.1.13891.101.9.6ScalarupsConfigOutputPowerread-onlymandatoryThe magnitude of the nominal true power rating (watts).
1.3.6.1.4.1.13891.101.9.7ScalarupsConfigLowBattTimeread-writemandatoryThe value of upsEstimatedMinutesRemaining at which a lowBattery condition is declared. For agents which support only discrete (discontinuous) values, then the …
1.3.6.1.4.1.13891.101.9.8ScalarupsConfigAudibleStatusread-writemandatoryThe requested state of the audible alarm. When in the disabled state, the audible alarm should never sound. The enabled state is self-describing. Setting this …
1.3.6.1.4.1.13891.101.9.9ScalarupsConfigLowVoltageTransferPointread-writemandatoryThe minimum input line voltage (RMS Volts) allowed before the UPS system transfers to battery backup.
1.3.6.1.4.1.13891.101.9.10ScalarupsConfigHighVoltageTransferPointread-writemandatoryThe maximum line voltage (RMS Volts) allowed before the UPS system transfers to battery backup.
1.3.6.1.4.1.13891.101.10NodeupsTrapInfo
1.3.6.1.4.1.13891.101.10.1ScalartrapCoderead-onlymandatoryA number identifying the event for that last trap that was sent.
1.3.6.1.4.1.13891.101.10.2ScalartrapDescriptionread-onlymandatoryA string identifying the event for that last trap that was sent.