OIDNameAccessStatusDescription
1.3.6.1.4.1.5528NodenetBotz
1.3.6.1.4.1.5528.10NodenetBotz-reg
1.3.6.1.4.1.5528.20NodenetBotz-generic
1.3.6.1.4.1.5528.30NodenetBotz-products
1.3.6.1.4.1.5528.30.10NodenetBotz-prd-bot
1.3.6.1.4.1.5528.30.10.1NodenetBotz-prd-bot-low-trapNetBotz Low Trap. This trap indicates that a lower limit has been exceeded.
1.3.6.1.4.1.5528.30.10.1ScalarnetBotz-prd-bot-tempread-onlymandatoryThe reading of the temperature probe, in degrees F or degrees C (depends on netBotz-ismetric).
1.3.6.1.4.1.5528.30.10.2NodenetBotz-prd-bot-high-trapNetBotz High Trap. This trap indicates that an upper limit has been exceeded.
1.3.6.1.4.1.5528.30.10.2ScalarnetBotz-prd-bot-humidityread-onlymandatoryThe reading of the humidity probe, in percent.
1.3.6.1.4.1.5528.30.10.3ScalarnetBotz-prd-bot-airflowread-onlymandatoryThe reading of the airflow probe. Each unit represents approximately 40 feet/minute or 13 meters/minute of airflow velocity.
1.3.6.1.4.1.5528.30.10.3NodenetBotz-prd-bot-trap-clearNetBotz Cleared Trap. The trap has been cleared because the value has returned to acceptable limits.
1.3.6.1.4.1.5528.30.10.4ScalarnetBotz-prd-bot-audioread-onlymandatoryThe reading of the audio alarm probe on/off.
1.3.6.1.4.1.5528.30.10.4NodenetBotz-prd-bot-offline-trapNetBotz Device Offline Trap. This trap indicates that a device or function has been determined to be offline.
1.3.6.1.4.1.5528.30.10.5ScalarnetBotz-prd-bot-doorajarread-onlymandatoryThe reading of the door switch probe open(1) or closed(0).
1.3.6.1.4.1.5528.30.10.5NodenetBotz-prd-bot-online-trapNetBotz Device Online Trap. This trap indicates that a device or function has been determined to be online.
1.3.6.1.4.1.5528.30.10.6ScalarnetBotz-prd-bot-temp-minread-writemandatoryThe temperature probe minimum, from 35 to 120 degrees F, or 1 to 50 degrees C (depends on netBotz-ismetric).
1.3.6.1.4.1.5528.30.10.7ScalarnetBotz-prd-bot-temp-maxread-writemandatoryThe temperature probe maximum, from 35 to 120 degrees F, or 1 to 50 degrees C (depends on netBotz-ismetric).
1.3.6.1.4.1.5528.30.10.8ScalarnetBotz-prd-bot-humidity-minread-writemandatoryThe humidity probe minimum, from 10 to 90 percent.
1.3.6.1.4.1.5528.30.10.9ScalarnetBotz-prd-bot-humidity-maxread-writemandatoryThe humidity probe maximum, from 10 to 90 percent.
1.3.6.1.4.1.5528.30.10.10ScalarnetBotz-prd-bot-airflow-minsread-writemandatoryMinutes without airflow before alarm set.
1.3.6.1.4.1.5528.30.10.11ScalarnetBotz-prd-bot-audio-secsread-writemandatorySeconds of alarm audio before alarm set.
1.3.6.1.4.1.5528.30.10.12ScalarnetBotz-prd-bot-temp-enabledread-writemandatoryTemperature probe alarm enabled(1) or disabled(0).
1.3.6.1.4.1.5528.30.10.13ScalarnetBotz-prd-bot-hum-enabledread-writemandatoryHumidity probe alarm enabled(1) or disabled(0).
1.3.6.1.4.1.5528.30.10.14ScalarnetBotz-prd-bot-air-enabledread-writemandatoryAirflow probe alarm enabled(1) or disabled(0).
1.3.6.1.4.1.5528.30.10.15ScalarnetBotz-prd-bot-audio-enabledread-writemandatoryAudio probe alarm enabled(1) or disabled(0).
1.3.6.1.4.1.5528.30.10.16ScalarnetBotz-prd-bot-switch-stateread-writemandatorySwitch state setting. The state controls which condition of the door switch indicates an alarm. If set to 0, alarm is set when the switch is closed. If set to …
1.3.6.1.4.1.5528.30.10.17ScalarnetBotz-prd-bot-switch-enabledread-writemandatoryDoor switch enabled(1) or disabled(0).
1.3.6.1.4.1.5528.30.10.18ScalarnetBotz-prd-bot-audio-levelread-writemandatoryAudio level setting. This is the relative audio level, from 0-11, above which an alarm will be sent.
1.3.6.1.4.1.5528.30.10.20ScalarnetBotz-prd-bot-trap-indexread-onlymandatoryThe crawler ID of the last trap.
1.3.6.1.4.1.5528.30.10.21ScalarnetBotz-prd-bot-trap-addressread-onlymandatoryThe IP address of the last trap.
1.3.6.1.4.1.5528.30.10.22ScalarnetBotz-prd-bot-trap-oidread-onlymandatoryThe object id of the last trap.
1.3.6.1.4.1.5528.30.10.23ScalarnetBotz-prd-bot-trap-valueread-onlymandatoryThe value of the last object trap.
1.3.6.1.4.1.5528.30.10.24ScalarnetBotz-prd-bot-trap-dateread-onlymandatoryThe date and time of a specific trap. This field contains the number of seconds elapsed since midnight (00:00:00), January 1, 1970
1.3.6.1.4.1.5528.30.10.26ScalarnetBotz-prd-bot-refreshread-writemandatoryRate of web page refresh, in seconds. This must be greater than 5 seconds.
1.3.6.1.4.1.5528.30.10.27ScalarnetBotz-prd-bot-airflow-levelread-writemandatoryAirflow alert level. This is the relative level of airflow below which an alarm will be sent. The range is 1-11. Each unit is approximately 40 feet/second or 1…
1.3.6.1.4.1.5528.30.10.28ScalarnetBotz-prd-bot-doorpic-countread-writemandatoryNumber of pictures to take when door activated. These pictures will be sent as attachments to the door alert e-mail. The range is from 0 to 5 pictures.
1.3.6.1.4.1.5528.30.10.29ScalarnetBotz-prd-bot-amps1read-onlymandatoryThe reading of the first amperage probe, in milliamps.
1.3.6.1.4.1.5528.30.10.30ScalarnetBotz-prd-bot-amps1-enabledread-writemandatoryAmperage[1] probe alarm enabled(1) or disabled(0).
1.3.6.1.4.1.5528.30.10.31ScalarnetBotz-prd-bot-amps1-minread-writemandatoryThe amperage[1] probe minimum, from 0 to 30000 milliamps.
1.3.6.1.4.1.5528.30.10.32ScalarnetBotz-prd-bot-amps1-maxread-writemandatoryThe amperage[1] probe maximum, from 0 to 30000 milliamps.
1.3.6.1.4.1.5528.30.10.34ScalarnetBotz-prd-bot-amps2read-onlymandatoryThe reading of the second amperage probe, in milliamps.
1.3.6.1.4.1.5528.30.10.35ScalarnetBotz-prd-bot-amps2-enabledread-writemandatoryAmperage[2] probe alarm enabled(1) or disabled(0).
1.3.6.1.4.1.5528.30.10.36ScalarnetBotz-prd-bot-amps2-minread-writemandatoryThe amperage[2] probe minimum, from 0 to 30000 milliamps.
1.3.6.1.4.1.5528.30.10.37ScalarnetBotz-prd-bot-amps2-maxread-writemandatoryThe amperage[2] probe maximum, from 0 to 30000 milliamps.
1.3.6.1.4.1.5528.30.10.39ScalarnetBotz-prd-bot-amps3read-onlymandatoryThe reading of the third amperage probe, in milliamps.
1.3.6.1.4.1.5528.30.10.40ScalarnetBotz-prd-bot-amps3-enabledread-writemandatoryAmperage[3] probe alarm enabled(1) or disabled(0).
1.3.6.1.4.1.5528.30.10.41ScalarnetBotz-prd-bot-amps3-minread-writemandatoryThe amperage[3] probe minimum, from 0 to 30000 milliamps.
1.3.6.1.4.1.5528.30.10.42ScalarnetBotz-prd-bot-amps3-maxread-writemandatoryThe amperage[3] probe maximum, from 0 to 30000 milliamps.
1.3.6.1.4.1.5528.30.10.44ScalarnetBotz-prd-bot-amps-totalread-onlymandatoryThe total of the readings of all amperage probes, in milliamps.
1.3.6.1.4.1.5528.30.10.45ScalarnetBotz-prd-bot-amps-total-enabledread-writemandatoryTotal amperage alarm enabled(1) or disabled(0).
1.3.6.1.4.1.5528.30.10.46ScalarnetBotz-prd-bot-amps-total-minread-writemandatoryThe total amperage minimum, from 0 to 90000 milliamps.
1.3.6.1.4.1.5528.30.10.47ScalarnetBotz-prd-bot-amps-total-maxread-writemandatoryThe total amperage maximum, from 0 to 90000 milliamps.
1.3.6.1.4.1.5528.30.10.48ScalarnetBotz-prd-bot-amps-total-support-enabledread-writemandatoryTotal Amperage Support enabled(Y) or disabled(N).
1.3.6.1.4.1.5528.30.10.49ScalarnetBotz-prd-bot-amps1-uV-per-10mAread-writemandatoryThe scaling factor used for the first amperage probe to convert microvolts measured from the Amp Detect into 10s of milliamps of current. Needs to be set based…
1.3.6.1.4.1.5528.30.10.50ScalarnetBotz-prd-bot-amps2-uV-per-10mAread-writemandatoryThe scaling factor used for the second amperage probe to convert microvolts measured from the Amp Detect into 10s of milliamps of current. Needs to be set base…
1.3.6.1.4.1.5528.30.10.51ScalarnetBotz-prd-bot-amps3-uV-per-mAread-writemandatoryThe scaling factor used for the third amperage probe to convert microvolts measured from the Amp Detect into 10s of milliamps of current. Needs to be set based…
1.3.6.1.4.1.5528.30.10.52ScalarnetBotz-prd-bot-amps1-max-rangeread-writemandatoryThe maximum RMS milliamps measureable by the first Amp Detect.
1.3.6.1.4.1.5528.30.10.53ScalarnetBotz-prd-bot-amps2-max-rangeread-writemandatoryThe maximum RMS milliamps measureable by the second Amp Detect.
1.3.6.1.4.1.5528.30.10.54ScalarnetBotz-prd-bot-amps3-max-rangeread-writemandatoryThe maximum RMS milliamps measureable by the third Amp Detect.
1.3.6.1.4.1.5528.30.10.55ScalarnetBotz-prd-bot-amps4read-onlymandatoryThe reading of the fourth amperage probe, in milliamps.
1.3.6.1.4.1.5528.30.10.56ScalarnetBotz-prd-bot-amps4-enabledread-writemandatoryAmperage[4] probe alarm enabled(1) or disabled(0).
1.3.6.1.4.1.5528.30.10.57ScalarnetBotz-prd-bot-amps4-minread-writemandatoryThe amperage[4] probe minimum, in milliamps.
1.3.6.1.4.1.5528.30.10.58ScalarnetBotz-prd-bot-amps4-maxread-writemandatoryThe amperage[4] probe maximum, in milliamps.
1.3.6.1.4.1.5528.30.10.60ScalarnetBotz-prd-bot-amps4-uV-per-10mAread-writemandatoryThe scaling factor used for the fourth amperage probe to convert microvolts measured from the Amp Detect into 10s of milliamps of current. Needs to be set base…
1.3.6.1.4.1.5528.30.10.61ScalarnetBotz-prd-bot-amps4-max-rangeread-writemandatoryThe maximum RMS milliamps measureable by the fourth Amp Detect.
1.3.6.1.4.1.5528.30.10.62ScalarnetBotz-prd-bot-ext-temp1read-onlymandatoryThe reading of the external temperature probe on port 1, in degrees F or degrees C (depends on netBotz-ismetric).
1.3.6.1.4.1.5528.30.10.63ScalarnetBotz-prd-bot-ext-temp2read-onlymandatoryThe reading of the external temperature probe on port 2, in degrees F or degrees C (depends on netBotz-ismetric).
1.3.6.1.4.1.5528.30.10.64ScalarnetBotz-prd-bot-ext-temp3read-onlymandatoryThe reading of the external temperature probe on port 3, in degrees F or degrees C (depends on netBotz-ismetric).
1.3.6.1.4.1.5528.30.10.66ScalarnetBotz-prd-bot-ext-temp1-enabledread-writemandatoryExternal temperature probe on port 1 alarm enabled(1) or disabled(0).
1.3.6.1.4.1.5528.30.10.67ScalarnetBotz-prd-bot-ext-temp1-minread-writemandatoryThe external temperature probe on port 1 probe minimum, in degrees F or degrees C (depends on netBotz-ismetric).
1.3.6.1.4.1.5528.30.10.68ScalarnetBotz-prd-bot-ext-temp1-maxread-writemandatoryThe external temperature probe on port 1 probe maximum, in degrees F or degrees C (depends on netBotz-ismetric).
1.3.6.1.4.1.5528.30.10.69ScalarnetBotz-prd-bot-ext-temp2-enabledread-writemandatoryExternal temperature probe on port 2 alarm enabled(1) or disabled(0).
1.3.6.1.4.1.5528.30.10.70ScalarnetBotz-prd-bot-ext-temp2-minread-writemandatoryThe external temperature probe on port 2 probe minimum, in degrees F or degrees C (depends on netBotz-ismetric).
1.3.6.1.4.1.5528.30.10.71ScalarnetBotz-prd-bot-ext-temp2-maxread-writemandatoryThe external temperature probe on port 2 probe maximum, in degrees F or degrees C (depends on netBotz-ismetric).
1.3.6.1.4.1.5528.30.10.72ScalarnetBotz-prd-bot-ext-temp3-enabledread-writemandatoryExternal temperature probe on port 3 alarm enabled(1) or disabled(0).
1.3.6.1.4.1.5528.30.10.73ScalarnetBotz-prd-bot-ext-temp3-minread-writemandatoryThe external temperature probe on port 3 probe minimum, in degrees F or degrees C (depends on netBotz-ismetric).
1.3.6.1.4.1.5528.30.10.74ScalarnetBotz-prd-bot-ext-temp3-maxread-writemandatoryThe external temperature probe on port 3 probe maximum, in degrees F or degrees C (depends on netBotz-ismetric).
1.3.6.1.4.1.5528.30.10.78ScalarnetBotz-prd-bot-ext-temp1-uV-per-degreeCread-writemandatoryThe scaling factor used for the external temperature probe on port 1 to convert microvolts measured from the temperature sensor into degrees C. Needs to be set…
1.3.6.1.4.1.5528.30.10.79ScalarnetBotz-prd-bot-ext-temp1-uV-at-0-degreeCread-writemandatoryThe offset used for the external temperature probe on port 1 of microvolts measured from the temperature sensor at zero degrees C. Needs to be set based on the…
1.3.6.1.4.1.5528.30.10.80ScalarnetBotz-prd-bot-ext-temp1-min-rangeread-writemandatoryThe minimum temperature measureable by the temperature sensor installed on port 1, in tenths of a degree C. Needs to be set based on the type of temperature se…
1.3.6.1.4.1.5528.30.10.81ScalarnetBotz-prd-bot-ext-temp1-max-rangeread-writemandatoryThe maximum temperature measureable by the temperature sensor installed on port 1, in tenths of a degree C. Needs to be set based on the type of temperature se…
1.3.6.1.4.1.5528.30.10.82ScalarnetBotz-prd-bot-ext-temp2-uV-per-degreeCread-writemandatoryThe scaling factor used for the external temperature probe on port 2 to convert microvolts measured from the temperature sensor into degrees C. Needs to be set…
1.3.6.1.4.1.5528.30.10.83ScalarnetBotz-prd-bot-ext-temp2-uV-at-0-degreeCread-writemandatoryThe offset used for the external temperature probe on port 2 of microvolts measured from the temperature sensor at zero degrees C. Needs to be set based on the…
1.3.6.1.4.1.5528.30.10.84ScalarnetBotz-prd-bot-ext-temp2-min-rangeread-writemandatoryThe minimum temperature measureable by the temperature sensor installed on port 2, in tenths of a degree C. Needs to be set based on the type of temperature se…
1.3.6.1.4.1.5528.30.10.85ScalarnetBotz-prd-bot-ext-temp2-max-rangeread-writemandatoryThe maximum temperature measureable by the temperature sensor installed on port 2, in tenths of a degree C. Needs to be set based on the type of temperature se…
1.3.6.1.4.1.5528.30.10.86ScalarnetBotz-prd-bot-ext-temp3-uV-per-degreeCread-writemandatoryThe scaling factor used for the external temperature probe on port 3 to convert microvolts measured from the temperature sensor into degrees C. Needs to be set…
1.3.6.1.4.1.5528.30.10.87ScalarnetBotz-prd-bot-ext-temp3-uV-at-0-degreeCread-writemandatoryThe offset used for the external temperature probe on port 3 of microvolts measured from the temperature sensor at zero degrees C. Needs to be set based on the…
1.3.6.1.4.1.5528.30.10.88ScalarnetBotz-prd-bot-ext-temp3-min-rangeread-writemandatoryThe minimum temperature measureable by the temperature sensor installed on port 3, in tenths of a degree C. Needs to be set based on the type of temperature se…
1.3.6.1.4.1.5528.30.10.89ScalarnetBotz-prd-bot-ext-temp3-max-rangeread-writemandatoryThe maximum temperature measureable by the temperature sensor installed on port 3, in tenths of a degree C. Needs to be set based on the type of temperature se…
1.3.6.1.4.1.5528.30.10.94ScalarnetBotz-prd-bot-ext-port1-module-idread-writemandatoryThe module ID of the sensor module installed on port 1. Blank string indicates that no module is installed.
1.3.6.1.4.1.5528.30.10.95ScalarnetBotz-prd-bot-ext-port1-module-typeread-writemandatoryThe type of sensor module installed on port 1. NONE=no module, AMP=AmpDetect module, TEMP=temperature sensor, DRY=dry contact sensor.
1.3.6.1.4.1.5528.30.10.96ScalarnetBotz-prd-bot-ext-port2-module-idread-writemandatoryThe module ID of the sensor module installed on port 2. Blank string indicates that no module is installed.
1.3.6.1.4.1.5528.30.10.97ScalarnetBotz-prd-bot-ext-port2-module-typeread-writemandatoryThe type of sensor module installed on port 2. NONE=no module, AMP=AmpDetect module, TEMP=temperature sensor, DRY=dry contact sensor.
1.3.6.1.4.1.5528.30.10.98ScalarnetBotz-prd-bot-ext-port3-module-idread-writemandatoryThe module ID of the sensor module installed on port 3. Blank string indicates that no module is installed.
1.3.6.1.4.1.5528.30.10.99ScalarnetBotz-prd-bot-ext-port3-module-typeread-writemandatoryThe type of sensor module installed on port 3. NONE=no module, AMP=AmpDetect module, TEMP=temperature sensor, DRY=dry contact sensor.
1.3.6.1.4.1.5528.30.10.102ScalarnetBotz-prd-bot-amp1-total-amp-secondsread-onlymandatoryThe accumulated total of amp-seconds on the AmpDetect on port 1.
1.3.6.1.4.1.5528.30.10.103ScalarnetBotz-prd-bot-amp1-total-amp-seconds-since-timeread-writemandatoryThe UTC time (seconds since 1/1/1970) of the beginning of the accumulated total of amp-seconds on the AmpDetect on port 1. Writing a value to this attribute re…
1.3.6.1.4.1.5528.30.10.104ScalarnetBotz-prd-bot-amp2-total-amp-secondsread-onlymandatoryThe accumulated total of amp-seconds on the AmpDetect on port 2.
1.3.6.1.4.1.5528.30.10.105ScalarnetBotz-prd-bot-amp2-total-amp-seconds-since-timeread-writemandatoryThe UTC time (seconds since 1/1/1970) of the beginning of the accumulated total of amp-seconds on the AmpDetect on port 2. Writing a value to this attribute re…
1.3.6.1.4.1.5528.30.10.106ScalarnetBotz-prd-bot-amp3-total-amp-secondsread-onlymandatoryThe accumulated total of amp-seconds on the AmpDetect on port 3.
1.3.6.1.4.1.5528.30.10.107ScalarnetBotz-prd-bot-amp3-total-amp-seconds-since-timeread-writemandatoryThe UTC time (seconds since 1/1/1970) of the beginning of the accumulated total of amp-seconds on the AmpDetect on port 3. Writing a value to this attribute re…
1.3.6.1.4.1.5528.30.10.108ScalarnetBotz-prd-bot-amp4-total-amp-secondsread-onlymandatoryThe accumulated total of amp-seconds on the AmpDetect on port 4.
1.3.6.1.4.1.5528.30.10.109ScalarnetBotz-prd-bot-amp4-total-amp-seconds-since-timeread-writemandatoryThe UTC time (seconds since 1/1/1970) of the beginning of the accumulated total of amp-seconds on the AmpDetect on port 4. Writing a value to this attribute re…
1.3.6.1.4.1.5528.30.10.110ScalarnetBotz-prd-bot-amptotal-total-amp-secondsread-onlymandatoryThe accumulated total of amp-seconds on the total of all AmpDetects.
1.3.6.1.4.1.5528.30.10.111ScalarnetBotz-prd-bot-amptotal-total-amp-seconds-since-timeread-writemandatoryThe UTC time (seconds since 1/1/1970) of the beginning of the accumulated total of amp-seconds for all AmpDetects. Writing a value to this attribute resets the…
1.3.6.1.4.1.5528.30.10.112ScalarnetBotz-prd-bot-ext-dry1read-onlymandatoryThe current value of the external dry contact sensor on Ext1: 0=Open, 1=Closed, -1=N/A
1.3.6.1.4.1.5528.30.10.113ScalarnetBotz-prd-bot-ext-dry2read-onlymandatoryThe current value of the external dry contact sensor on Ext2: 0=Open, 1=Closed, -1=N/A
1.3.6.1.4.1.5528.30.10.114ScalarnetBotz-prd-bot-ext-dry3read-onlymandatoryThe current value of the external dry contact sensor on Ext3: 0=Open, 1=Closed, -1=N/A
1.3.6.1.4.1.5528.30.10.115ScalarnetBotz-prd-bot-ext-dry4read-onlymandatoryThe current value of the external dry contact sensor on Ext4: 0=Open, 1=Closed, -1=N/A
1.3.6.1.4.1.5528.30.10.116ScalarnetBotz-prd-bot-ext-dry1-alarm-valueread-writemandatoryThe value to generate alarms on for the external dry contact sensor on Ext1: 0=Open, 1=Closed
1.3.6.1.4.1.5528.30.10.117ScalarnetBotz-prd-bot-ext-dry1-enabledread-writemandatoryExternal dry contact sensor on Ext1 alarm enabled(1) or disabled(0).
1.3.6.1.4.1.5528.30.10.118ScalarnetBotz-prd-bot-ext-dry2-alarm-valueread-writemandatoryThe value to generate alarms on for the external dry contact sensor on Ext2: 0=Open, 1=Closed
1.3.6.1.4.1.5528.30.10.119ScalarnetBotz-prd-bot-ext-dry2-enabledread-writemandatoryExternal dry contact sensor on Ext2 alarm enabled(1) or disabled(0).
1.3.6.1.4.1.5528.30.10.120ScalarnetBotz-prd-bot-ext-dry3-alarm-valueread-writemandatoryThe value to generate alarms on for the external dry contact sensor on Ext3: 0=Open, 1=Closed
1.3.6.1.4.1.5528.30.10.121ScalarnetBotz-prd-bot-ext-dry3-enabledread-writemandatoryExternal dry contact sensor on Ext3 alarm enabled(1) or disabled(0).
1.3.6.1.4.1.5528.30.10.122ScalarnetBotz-prd-bot-ext-dry4-alarm-valueread-writemandatoryThe value to generate alarms on for the external dry contact sensor on Ext4: 0=Open, 1=Closed
1.3.6.1.4.1.5528.30.10.123ScalarnetBotz-prd-bot-ext-dry4-enabledread-writemandatoryExternal dry contact sensor on Ext4 alarm enabled(1) or disabled(0).
1.3.6.1.4.1.5528.30.10.124ScalarnetBotz-prd-bot-ext-dry1-labelread-writemandatoryThe sensor name/label for the dry contact sensor on Ext1
1.3.6.1.4.1.5528.30.10.125ScalarnetBotz-prd-bot-ext-dry1-open-labelread-writemandatoryThe sensor name/label for the open(0) state for the dry contact sensor on Ext1
1.3.6.1.4.1.5528.30.10.126ScalarnetBotz-prd-bot-ext-dry1-closed-labelread-writemandatoryThe sensor name/label for the closed(0) state for the dry contact sensor on Ext1
1.3.6.1.4.1.5528.30.10.127ScalarnetBotz-prd-bot-ext-dry1-open-to-close-millisread-writemandatoryThe minimum number of milliseconds that the dry contact sensor on Ext1 must read closed before the state is changed from open to closed.
1.3.6.1.4.1.5528.30.10.128ScalarnetBotz-prd-bot-ext-dry1-close-to-open-millisread-writemandatoryThe minimum number of milliseconds that the dry contact sensor on Ext1 must read openbefore the state is changed from closed to open.
1.3.6.1.4.1.5528.30.10.129ScalarnetBotz-prd-bot-ext-dry1-responseread-writemandatoryThe type of alert response for the dry contact sensor on Ext1: ALERT=e-mail with no pictures, CAMERA=e-mail with pictures from camera.
1.3.6.1.4.1.5528.30.10.130ScalarnetBotz-prd-bot-ext-dry2-labelread-writemandatoryThe sensor name/label for the dry contact sensor on Ext2
1.3.6.1.4.1.5528.30.10.131ScalarnetBotz-prd-bot-ext-dry2-open-labelread-writemandatoryThe sensor name/label for the open(0) state for the dry contact sensor on Ext2
1.3.6.1.4.1.5528.30.10.132ScalarnetBotz-prd-bot-ext-dry2-closed-labelread-writemandatoryThe sensor name/label for the closed(0) state for the dry contact sensor on Ext2
1.3.6.1.4.1.5528.30.10.133ScalarnetBotz-prd-bot-ext-dry2-open-to-close-millisread-writemandatoryThe minimum number of milliseconds that the dry contact sensor on Ext2 must read closed before the state is changed from open to closed.
1.3.6.1.4.1.5528.30.10.134ScalarnetBotz-prd-bot-ext-dry2-close-to-open-millisread-writemandatoryThe minimum number of milliseconds that the dry contact sensor on Ext2 must read openbefore the state is changed from closed to open.
1.3.6.1.4.1.5528.30.10.135ScalarnetBotz-prd-bot-ext-dry2-responseread-writemandatoryThe type of alert response for the dry contact sensor on Ext2: ALERT=e-mail with no pictures, CAMERA=e-mail with pictures from camera.
1.3.6.1.4.1.5528.30.10.136ScalarnetBotz-prd-bot-ext-dry3-labelread-writemandatoryThe sensor name/label for the dry contact sensor on Ext3
1.3.6.1.4.1.5528.30.10.137ScalarnetBotz-prd-bot-ext-dry3-open-labelread-writemandatoryThe sensor name/label for the open(0) state for the dry contact sensor on Ext3
1.3.6.1.4.1.5528.30.10.138ScalarnetBotz-prd-bot-ext-dry3-closed-labelread-writemandatoryThe sensor name/label for the closed(0) state for the dry contact sensor on Ext3
1.3.6.1.4.1.5528.30.10.139ScalarnetBotz-prd-bot-ext-dry3-open-to-close-millisread-writemandatoryThe minimum number of milliseconds that the dry contact sensor on Ext3 must read closed before the state is changed from open to closed.
1.3.6.1.4.1.5528.30.10.140ScalarnetBotz-prd-bot-ext-dry3-close-to-open-millisread-writemandatoryThe minimum number of milliseconds that the dry contact sensor on Ext3 must read openbefore the state is changed from closed to open.
1.3.6.1.4.1.5528.30.10.141ScalarnetBotz-prd-bot-ext-dry3-responseread-writemandatoryThe type of alert response for the dry contact sensor on Ext3: ALERT=e-mail with no pictures, CAMERA=e-mail with pictures from camera.
1.3.6.1.4.1.5528.30.10.148ScalarnetBotz-prd-bot-cam-motionread-onlymandatoryThe current motion reading for the camera motion sensor (0=none, 1=motion detected)
1.3.6.1.4.1.5528.30.10.149ScalarnetBotz-prd-bot-cam-motion-enabledread-writemandatoryCamera motion sensor alarm enabled(1) or disabled(0).
1.3.6.1.4.1.5528.30.10.150ScalarnetBotz-prd-bot-cam-motion-sensitivityread-writemandatoryCamera motion sensor sensitivity: 1=max, 15=min, 0=disabled.
1.3.6.1.4.1.5528.30.10.151ScalarnetBotz-prd-bot-cam-motion-delayread-writemandatoryCamera motion sensor delay. This is the minimum number of milliseconds of detected motion required before the alarm is triggered.
1.3.6.1.4.1.5528.30.10.152ScalarnetBotz-prd-bot-camera-event-autocycleread-writemandatoryEnables (1) or disables (0) the option to have the camera-based responses to alarm conditions automatically cycle as long as the condition persists.
1.3.6.1.4.1.5528.30.10.153ScalarnetBotz-prd-bot-num-pix-before-alarmread-writemandatoryControls the number of pictures to be captured before any triggered alarm.
1.3.6.1.4.1.5528.30.10.154ScalarnetBotz-prd-bot-delay-before-event-pixread-writemandatoryControls the number of milliseconds before the first picture is captured after any triggered alarm.
1.3.6.1.4.1.5528.30.10.155ScalarnetBotz-prd-bot-delay-between-event-pixread-writemandatoryControls the number of milliseconds between pictures captured after any triggered alarm.
1.3.6.1.4.1.5528.30.10.156ScalarnetBotz-prd-bot-cam-motion-area-of-motionread-writemandatoryCamera motion sensor area of motion: 1=max, 15=min, 0=disabled.
1.3.6.1.4.1.5528.30.10.157ScalarnetBotz-prd-bot-cam-pix-for-duration-of-alertsread-writemandatoryCamera images gathered for duration of camera related alert: 0=no, 1=yes.
1.3.6.1.4.1.5528.30.10.158ScalarnetBotz-prd-bot-camera-enabledread-writemandatoryControls whether the camera is enabled or not: 0=no, 1=yes. Changing this will reboot the appliance.
1.3.6.1.4.1.5528.30.10.159ScalarnetBotz-prd-bot-camera-is-flippedread-writemandatoryControls whether the camera image is flipped 180 degress or not: 0=no, 1=yes. Changing this will reboot the appliance.
1.3.6.1.4.1.5528.30.10.160ScalarnetBotz-prd-bot-camera-brightnessread-writemandatorySets the brightness on the camera, from 20 to 180 (20 is low, 180 is high).
1.3.6.1.4.1.5528.30.20NodenetBotz-prd-crawlers
1.3.6.1.4.1.5528.30.20.5528Nodenetbotz-crawlers
1.3.6.1.4.1.5528.30.20.5528.1NodenetBotz-prd-crl-mib2
1.3.6.1.4.1.5528.30.20.5528.1.3ScalarnetBotz-prd-crl-mib2-pingread-onlymandatoryNetBotz device ping. This object indicates the status of a ping on a device monitored by a NetBotz device.
1.3.6.1.4.1.5528.30.20.5528.1.3.4NodenetBotz-prd-crl-ping-offline-trapNetBotz Ping Trap. This trap indicates that replies to a set of pings were not received from a monitored IP address.
1.3.6.1.4.1.5528.30.20.5528.1.3.5NodenetBotz-prd-crl-ping-online-trapNetBotz Ping Trap. This trap indicates that replies to a set of pings were received from a monitored IP address after a period when no replies had been receive…
1.3.6.1.4.1.5528.30.20.5528.1.8ScalarnetBotz-prd-crl-mib2-uptimeread-onlymandatoryThe uptime of a device monitored by a NetBotz device.
1.3.6.1.4.1.5528.30.20.5528.1.8.5NodenetBotz-prd-crl-uptime-online-trapNetBotz Uptime Trap. This trap indicates that a device restart has been detected due to the uptime of the device being reported as less than the previously rep…
1.3.6.1.4.1.5528.30.20.5528.1.9ScalarnetBotz-prd-crl-mib2-snmpstatusread-onlymandatoryThe SNMP status of a device monitored by a NetBotz device.
1.3.6.1.4.1.5528.30.20.5528.1.9.4NodenetBotz-prd-crl-snmp-offline-trapNetBotz SNMP Offline Trap. This trap indicates that an SNMP request was not possible on an IP address.
1.3.6.1.4.1.5528.30.20.5528.1.9.5NodenetBotz-prd-crl-snmp-online-trapNetBotz SNMP Online Trap. This trap indicates that an SNMP request succeeded on an IP address where it had previously failed.
1.3.6.1.4.1.5528.30.20.5528.2NodenetBotz-prd-crl-mib2if
1.3.6.1.4.1.5528.30.20.5528.2.6ScalarnetBotz-prd-crl-mib2if-opstatusread-onlymandatoryThe operational status of a device monitored by a NetBotz device.
1.3.6.1.4.1.5528.30.20.5528.2.6.1NodenetBotz-prd-crl-opstatus-mismatch-trapNetBotz Interface Status Mismatch Trap. This trap indicates that the operational status of a device interface does not match the administrative status.
1.3.6.1.4.1.5528.30.20.5528.2.6.2NodenetBotz-prd-crl-opstatus-match-trapNetBotz Interface Status Match Trap. This trap indicates that the operational status of a device interface now matches the administrative status. This trap ind…
1.3.6.1.4.1.5528.30.20.5528.2.6.4NodenetBotz-prd-crl-opstatus-offline-trapNetBotz Interface Offline Trap. This trap indicates that an interface on a device did not respond to an SNMP query on the ifAdminStatus or ifOperStatus objects.
1.3.6.1.4.1.5528.30.21NodenetBotz-prd-crltrap
1.3.6.1.4.1.5528.30.21.20ScalarnetBotz-prd-crl-trap-indexread-onlymandatoryThe ID of the crawler which sent the last trap.
1.3.6.1.4.1.5528.30.21.21ScalarnetBotz-prd-crl-trap-addressread-onlymandatoryThe IP address of the last trap.
1.3.6.1.4.1.5528.30.21.22ScalarnetBotz-prd-crl-trap-oidread-onlymandatoryThe object id of the attribute on the target device which is the concern of the last trap.
1.3.6.1.4.1.5528.30.21.23ScalarnetBotz-prd-crl-trap-botoidread-onlymandatoryThe object id of the attribute on the NetBotz device which is the concern of the last trap.
1.3.6.1.4.1.5528.30.21.24ScalarnetBotz-prd-crl-trap-valueread-onlymandatoryThe value of the attribute associated with the last trap.
1.3.6.1.4.1.5528.30.21.25ScalarnetBotz-prd-crl-trap-dateread-onlymandatoryThe date and time of a specific trap. This field contains the number of seconds elapsed since midnight (00:00:00), January 1, 1970
1.3.6.1.4.1.5528.30.21.26ScalarnetBotz-prd-crl-trap-attribread-onlymandatoryThe identification number of the attribute in error
1.3.6.1.4.1.5528.30.21.27ScalarnetBotz-prd-crl-trap-descread-onlymandatoryDescription or name of the attribute in error
1.3.6.1.4.1.5528.30.100NodenetBotz-prd-bot-traps
1.3.6.1.4.1.5528.30.100.1NodenetBotz-prd-bot-temperature-traps
1.3.6.1.4.1.5528.30.100.1.1NodenetBotz-prd-bot-temperature-low-trapNetBotz Temperature Low Trap. This trap indicates that the lower limit for temperature has been exceeded.
1.3.6.1.4.1.5528.30.100.1.2NodenetBotz-prd-bot-temperature-high-trapNetBotz Temperature High Trap. This trap indicates that the upper limit for temperature has been exceeded.
1.3.6.1.4.1.5528.30.100.1.3NodenetBotz-prd-bot-temperature-trap-clearNetBotz Temperature Cleared Trap. The trap has been cleared because the temperature value has returned to acceptable limits.
1.3.6.1.4.1.5528.30.100.2NodenetBotz-prd-bot-humidity-traps
1.3.6.1.4.1.5528.30.100.2.1NodenetBotz-prd-bot-humidity-low-trapNetBotz Humidity Low Trap. This trap indicates that the lower limit for humidity has been exceeded.
1.3.6.1.4.1.5528.30.100.2.2NodenetBotz-prd-bot-humidity-high-trapNetBotz Humidity High Trap. This trap indicates that the upper limit for humidity has been exceeded.
1.3.6.1.4.1.5528.30.100.2.3NodenetBotz-prd-bot-humidity-trap-clearNetBotz Humidity Cleared Trap. The trap has been cleared because the humidity value has returned to acceptable limits.
1.3.6.1.4.1.5528.30.100.3NodenetBotz-prd-bot-airflow-traps
1.3.6.1.4.1.5528.30.100.3.1NodenetBotz-prd-bot-airflow-low-trapNetBotz Airflow Low Trap. This trap indicates that the lower limit for airflow has been exceeded.
1.3.6.1.4.1.5528.30.100.3.3NodenetBotz-prd-bot-airflow-trap-clearNetBotz Airflow Cleared Trap. The trap has been cleared because the airflow value has returned to acceptable limits.
1.3.6.1.4.1.5528.30.100.4NodenetBotz-prd-bot-audio-traps
1.3.6.1.4.1.5528.30.100.4.2NodenetBotz-prd-bot-audio-high-trapNetBotz Audio High Trap. This trap indicates that the upper limit for audio has been exceeded.
1.3.6.1.4.1.5528.30.100.4.3NodenetBotz-prd-bot-audio-trap-clearNetBotz Audio Cleared Trap. The trap has been cleared because the audio value has returned to acceptable limits.
1.3.6.1.4.1.5528.30.100.5NodenetBotz-prd-bot-door-traps
1.3.6.1.4.1.5528.30.100.5.2NodenetBotz-prd-bot-door-trap-trippedNetBotz Door Sensor Tripped Trap. This trap indicates that the door sensor has been triggered (i.e. opened, if the thresdhold has been set to trip on open, clo…
1.3.6.1.4.1.5528.30.100.5.3NodenetBotz-prd-bot-door-trap-clearNetBotz Door Cleared Trap. The trap has been cleared because the door sensor has returned to normal (i.e. been closed, if the threshold has been set to trip on…
1.3.6.1.4.1.5528.30.100.6NodenetBotz-prd-bot-amp1-traps
1.3.6.1.4.1.5528.30.100.6.1NodenetBotz-prd-bot-amp1-low-trapNetBotz Amp1 Low Trap. This trap indicates that the lower limit for the first amp detect has been exceeded.
1.3.6.1.4.1.5528.30.100.6.2NodenetBotz-prd-bot-amp1-high-trapNetBotz Amp1 High Trap. This trap indicates that the upper limit for the first amp detect has been exceeded.
1.3.6.1.4.1.5528.30.100.6.3NodenetBotz-prd-bot-amp1-trap-clearNetBotz Amp1 Cleared Trap. The trap has been cleared because the first amp detect value has returned to acceptable limits.
1.3.6.1.4.1.5528.30.100.6.6NodenetBotz-prd-bot-amp1-sensor-unpluggedNetBotz Amp 1 Sensor Unplugged Trap. The sensor for the first AmpDetect is unplugged or malfunctioning.
1.3.6.1.4.1.5528.30.100.6.7NodenetBotz-prd-bot-amp1-sensor-repluggedNetBotz Amp 1 Sensor Replugged Trap. The sensor for the first AmpDetect was unplugged, but has been reconnected.
1.3.6.1.4.1.5528.30.100.7NodenetBotz-prd-bot-amp2-traps
1.3.6.1.4.1.5528.30.100.7.1NodenetBotz-prd-bot-amp2-low-trapNetBotz Amp2 Low Trap. This trap indicates that the lower limit for the second amp detect has been exceeded.
1.3.6.1.4.1.5528.30.100.7.2NodenetBotz-prd-bot-amp2-high-trapNetBotz Amp2 High Trap. This trap indicates that the upper limit for the second amp detect has been exceeded.
1.3.6.1.4.1.5528.30.100.7.3NodenetBotz-prd-bot-amp2-trap-clearNetBotz Amp2 Cleared Trap. The trap has been cleared because the second amp detect value has returned to acceptable limits.
1.3.6.1.4.1.5528.30.100.7.6NodenetBotz-prd-bot-amp2-sensor-unpluggedNetBotz Amp 2 Sensor Unplugged Trap. The sensor for the second AmpDetect is unplugged or malfunctioning.
1.3.6.1.4.1.5528.30.100.7.7NodenetBotz-prd-bot-amp2-sensor-repluggedNetBotz Amp 2 Sensor Replugged Trap. The sensor for the second AmpDetect was unplugged, but has been reconnected.
1.3.6.1.4.1.5528.30.100.8NodenetBotz-prd-bot-amp3-traps
1.3.6.1.4.1.5528.30.100.8.1NodenetBotz-prd-bot-amp3-low-trapNetBotz Amp3 Low Trap. This trap indicates that the lower limit for the third amp detect has been exceeded.
1.3.6.1.4.1.5528.30.100.8.2NodenetBotz-prd-bot-amp3-high-trapNetBotz Amp3 High Trap. This trap indicates that the upper limit for the third amp detect has been exceeded.
1.3.6.1.4.1.5528.30.100.8.3NodenetBotz-prd-bot-amp3-trap-clearNetBotz Amp3 Cleared Trap. The trap has been cleared because the third amp detect value has returned to acceptable limits.
1.3.6.1.4.1.5528.30.100.8.6NodenetBotz-prd-bot-amp3-sensor-unpluggedNetBotz Amp 3 Sensor Unplugged Trap. The sensor for the third AmpDetect is unplugged or malfunctioning.
1.3.6.1.4.1.5528.30.100.8.7NodenetBotz-prd-bot-amp3-sensor-repluggedNetBotz Amp 3 Sensor Replugged Trap. The sensor for the third AmpDetect was unplugged, but has been reconnected.
1.3.6.1.4.1.5528.30.100.9NodenetBotz-prd-bot-amp4-traps
1.3.6.1.4.1.5528.30.100.9.1NodenetBotz-prd-bot-amp4-low-trapNetBotz Amp4 Low Trap. This trap indicates that the lower limit for the fourth amp detect has been exceeded.
1.3.6.1.4.1.5528.30.100.9.2NodenetBotz-prd-bot-amp4-high-trapNetBotz Amp4 High Trap. This trap indicates that the upper limit for the fourth amp detect has been exceeded.
1.3.6.1.4.1.5528.30.100.9.3NodenetBotz-prd-bot-amp4-trap-clearNetBotz Amp4 Cleared Trap. The trap has been cleared because the fourth amp detect value has returned to acceptable limits.
1.3.6.1.4.1.5528.30.100.9.6NodenetBotz-prd-bot-amp4-sensor-unpluggedNetBotz Amp 4 Sensor Unplugged Trap. The sensor for the fourth AmpDetect is unplugged or malfunctioning.
1.3.6.1.4.1.5528.30.100.9.7NodenetBotz-prd-bot-amp4-sensor-repluggedNetBotz Amp 4 Sensor Replugged Trap. The sensor for the fourth AmpDetect was unplugged, but has been reconnected.
1.3.6.1.4.1.5528.30.100.10NodenetBotz-prd-bot-amp-total-traps
1.3.6.1.4.1.5528.30.100.10.1NodenetBotz-prd-bot-amp-total-low-trapNetBotz Total Amps Low Trap. This trap indicates that the lower limit for the total amperage has been exceeded.
1.3.6.1.4.1.5528.30.100.10.2NodenetBotz-prd-bot-amp-total-high-trapNetBotz Total Amps High Trap. This trap indicates that the upper limit for the total amperage has been exceeded.
1.3.6.1.4.1.5528.30.100.10.3NodenetBotz-prd-bot-amp-total-trap-clearNetBotz Total Amps Cleared Trap. The trap has been cleared because the total amperage value has returned to acceptable limits.
1.3.6.1.4.1.5528.30.100.11NodenetBotz-prd-bot-ext-temp1-traps
1.3.6.1.4.1.5528.30.100.11.1NodenetBotz-prd-bot-ext-temp1-low-trapNetBotz External Temperature 1 Low Trap. This trap indicates that the lower limit for external temperature probe on port 1 has been exceeded.
1.3.6.1.4.1.5528.30.100.11.2NodenetBotz-prd-bot-ext-temp1-high-trapNetBotz External Temperature 1 High Trap. This trap indicates that the upper limit for external temperature probe on port 1 has been exceeded.
1.3.6.1.4.1.5528.30.100.11.3NodenetBotz-prd-bot-ext-temp1-trap-clearNetBotz External Temperature 1 Cleared Trap. The trap has been cleared because the temperature value for the temperature probe on port 1 has returned to accept…
1.3.6.1.4.1.5528.30.100.11.6NodenetBotz-prd-bot-ext-temp1-sensor-unpluggedNetBotz External Temperature 1 Sensor Unplugged Trap. The sensor is unplugged or malfunctioning.
1.3.6.1.4.1.5528.30.100.11.7NodenetBotz-prd-bot-ext-temp1-sensor-repluggedNetBotz External Temperature 1 Sensor Replugged Trap. The sensor was unplugged, but has been reconnected.
1.3.6.1.4.1.5528.30.100.12NodenetBotz-prd-bot-ext-temp2-traps
1.3.6.1.4.1.5528.30.100.12.1NodenetBotz-prd-bot-ext-temp2-low-trapNetBotz External Temperature 2 Low Trap. This trap indicates that the lower limit for external temperature probe on port 2 has been exceeded.
1.3.6.1.4.1.5528.30.100.12.2NodenetBotz-prd-bot-ext-temp2-high-trapNetBotz External Temperature 2 High Trap. This trap indicates that the upper limit for external temperature probe on port 2 has been exceeded.
1.3.6.1.4.1.5528.30.100.12.3NodenetBotz-prd-bot-ext-temp2-trap-clearNetBotz External Temperature 2 Cleared Trap. The trap has been cleared because the temperature value for the temperature probe on port 2 has returned to accept…
1.3.6.1.4.1.5528.30.100.12.6NodenetBotz-prd-bot-ext-temp2-sensor-unpluggedNetBotz External Temperature 2 Sensor Unplugged Trap. The sensor is unplugged or malfunctioning.
1.3.6.1.4.1.5528.30.100.12.7NodenetBotz-prd-bot-ext-temp2-sensor-repluggedNetBotz External Temperature 2 Sensor Replugged Trap. The sensor was unplugged, but has been reconnected.
1.3.6.1.4.1.5528.30.100.13NodenetBotz-prd-bot-ext-temp3-traps
1.3.6.1.4.1.5528.30.100.13.1NodenetBotz-prd-bot-ext-temp3-low-trapNetBotz External Temperature 3 Low Trap. This trap indicates that the lower limit for external temperature probe on port 3 has been exceeded.
1.3.6.1.4.1.5528.30.100.13.2NodenetBotz-prd-bot-ext-temp3-high-trapNetBotz External Temperature 3 High Trap. This trap indicates that the upper limit for external temperature probe on port 3 has been exceeded.
1.3.6.1.4.1.5528.30.100.13.3NodenetBotz-prd-bot-ext-temp3-trap-clearNetBotz External Temperature 3 Cleared Trap. The trap has been cleared because the temperature value for the temperature probe on port 3 has returned to accept…
1.3.6.1.4.1.5528.30.100.13.6NodenetBotz-prd-bot-ext-temp3-sensor-unpluggedNetBotz External Temperature 3 Sensor Unplugged Trap. The sensor is unplugged or malfunctioning.
1.3.6.1.4.1.5528.30.100.13.7NodenetBotz-prd-bot-ext-temp3-sensor-repluggedNetBotz External Temperature 3 Sensor Replugged Trap. The sensor was unplugged, but has been reconnected.
1.3.6.1.4.1.5528.30.100.14NodenetBotz-prd-bot-ext-temp4-traps
1.3.6.1.4.1.5528.30.100.14.1NodenetBotz-prd-bot-ext-temp4-low-trapNetBotz External Temperature 4 Low Trap. This trap indicates that the lower limit for external temperature probe on port 4 has been exceeded.
1.3.6.1.4.1.5528.30.100.14.2NodenetBotz-prd-bot-ext-temp4-high-trapNetBotz External Temperature 4 High Trap. This trap indicates that the upper limit for external temperature probe on port 4 has been exceeded.
1.3.6.1.4.1.5528.30.100.14.3NodenetBotz-prd-bot-ext-temp4-trap-clearNetBotz External Temperature 4 Cleared Trap. The trap has been cleared because the temperature value for the temperature probe on port 4 has returned to accept…
1.3.6.1.4.1.5528.30.100.14.6NodenetBotz-prd-bot-ext-temp4-sensor-unpluggedNetBotz External Temperature 4 Sensor Unplugged Trap. The sensor is unplugged or malfunctioning.
1.3.6.1.4.1.5528.30.100.14.7NodenetBotz-prd-bot-ext-temp4-sensor-repluggedNetBotz External Temperature 4 Sensor Replugged Trap. The sensor was unplugged, but has been reconnected.
1.3.6.1.4.1.5528.30.100.15NodenetBotz-prd-bot-ext-dry1-traps
1.3.6.1.4.1.5528.30.100.15.2NodenetBotz-prd-bot-ext-dry1-triggered-trapNetBotz External Dry Contact 1 Triggered Trap. This trap indicates that the state of the dry contact sensor on Ext1 matches the alarm value.
1.3.6.1.4.1.5528.30.100.15.3NodenetBotz-prd-bot-ext-dry1-trap-clearNetBotz External Dry Contact 1 Cleared Trap. The trap has been cleared because the state of the dry contact sensor on Ext1 no longer matches the alarm value.
1.3.6.1.4.1.5528.30.100.16NodenetBotz-prd-bot-ext-dry2-traps
1.3.6.1.4.1.5528.30.100.16.2NodenetBotz-prd-bot-ext-dry2-triggered-trapNetBotz External Dry Contact 2 Triggered Trap. This trap indicates that the state of the dry contact sensor on Ext2 matches the alarm value.
1.3.6.1.4.1.5528.30.100.16.3NodenetBotz-prd-bot-ext-dry2-trap-clearNetBotz External Dry Contact 2 Cleared Trap. The trap has been cleared because the state of the dry contact sensor on Ext2 no longer matches the alarm value.
1.3.6.1.4.1.5528.30.100.17NodenetBotz-prd-bot-ext-dry3-traps
1.3.6.1.4.1.5528.30.100.17.2NodenetBotz-prd-bot-ext-dry3-triggered-trapNetBotz External Dry Contact 3 Triggered Trap. This trap indicates that the state of the dry contact sensor on Ext3 matches the alarm value.
1.3.6.1.4.1.5528.30.100.17.3NodenetBotz-prd-bot-ext-dry3-trap-clearNetBotz External Dry Contact 3 Cleared Trap. The trap has been cleared because the state of the dry contact sensor on Ext3 no longer matches the alarm value.
1.3.6.1.4.1.5528.30.100.18NodenetBotz-prd-bot-ext-dry4-traps
1.3.6.1.4.1.5528.30.100.18.2NodenetBotz-prd-bot-ext-dry4-triggered-trapNetBotz External Dry Contact 4 Triggered Trap. This trap indicates that the state of the dry contact sensor on Ext4 matches the alarm value.
1.3.6.1.4.1.5528.30.100.18.3NodenetBotz-prd-bot-ext-dry4-trap-clearNetBotz External Dry Contact 4 Cleared Trap. The trap has been cleared because the state of the dry contact sensor on Ext4 no longer matches the alarm value.
1.3.6.1.4.1.5528.30.100.19NodenetBotz-prd-bot-amp5-traps
1.3.6.1.4.1.5528.30.100.19.1NodenetBotz-prd-bot-amp5-low-trapNetBotz Amp 5 Low Trap. This trap indicates that the lower limit for the fifth amp detect has been exceeded.
1.3.6.1.4.1.5528.30.100.19.2NodenetBotz-prd-bot-amp5-high-trapNetBotz Amp 5 High Trap. This trap indicates that the upper limit for the fifth amp detect has been exceeded.
1.3.6.1.4.1.5528.30.100.19.3NodenetBotz-prd-bot-amp5-trap-clearNetBotz Amp 5 Cleared Trap. The trap has been cleared because the fifth amp detect value has returned to acceptable limits.
1.3.6.1.4.1.5528.30.100.19.6NodenetBotz-prd-bot-amp5-sensor-unpluggedNetBotz Amp 5 Sensor Unplugged Trap. The sensor for the fifth AmpDetect is unplugged or malfunctioning.
1.3.6.1.4.1.5528.30.100.19.7NodenetBotz-prd-bot-amp5-sensor-repluggedNetBotz Amp 5 Sensor Replugged Trap. The sensor for the fifth AmpDetect was unplugged, but has been reconnected.
1.3.6.1.4.1.5528.30.100.20NodenetBotz-prd-bot-amp6-traps
1.3.6.1.4.1.5528.30.100.20.1NodenetBotz-prd-bot-amp6-low-trapNetBotz Amp 6 Low Trap. This trap indicates that the lower limit for the sixth amp detect has been exceeded.
1.3.6.1.4.1.5528.30.100.20.2NodenetBotz-prd-bot-amp6-high-trapNetBotz Amp 6 High Trap. This trap indicates that the upper limit for the sixth amp detect has been exceeded.
1.3.6.1.4.1.5528.30.100.20.3NodenetBotz-prd-bot-amp6-trap-clearNetBotz Amp 6 Cleared Trap. The trap has been cleared because the sixth amp detect value has returned to acceptable limits.
1.3.6.1.4.1.5528.30.100.20.6NodenetBotz-prd-bot-amp6-sensor-unpluggedNetBotz Amp 6 Sensor Unplugged Trap. The sensor for the sixth AmpDetect is unplugged or malfunctioning.
1.3.6.1.4.1.5528.30.100.20.7NodenetBotz-prd-bot-amp6-sensor-repluggedNetBotz Amp 6 Sensor Replugged Trap. The sensor for the sixth AmpDetect was unplugged, but has been reconnected.
1.3.6.1.4.1.5528.30.100.21NodenetBotz-prd-bot-amp7-traps
1.3.6.1.4.1.5528.30.100.21.1NodenetBotz-prd-bot-amp7-low-trapNetBotz Amp 7 Low Trap. This trap indicates that the lower limit for the seventh amp detect has been exceeded.
1.3.6.1.4.1.5528.30.100.21.2NodenetBotz-prd-bot-amp7-high-trapNetBotz Amp 7 High Trap. This trap indicates that the upper limit for the seventh amp detect has been exceeded.
1.3.6.1.4.1.5528.30.100.21.3NodenetBotz-prd-bot-amp7-trap-clearNetBotz Amp 7 Cleared Trap. The trap has been cleared because the seventh amp detect value has returned to acceptable limits.
1.3.6.1.4.1.5528.30.100.21.6NodenetBotz-prd-bot-amp7-sensor-unpluggedNetBotz Amp 7 Sensor Unplugged Trap. The sensor for the seventh AmpDetect is unplugged or malfunctioning.
1.3.6.1.4.1.5528.30.100.21.7NodenetBotz-prd-bot-amp7-sensor-repluggedNetBotz Amp 7 Sensor Replugged Trap. The sensor for the seventh AmpDetect was unplugged, but has been reconnected.
1.3.6.1.4.1.5528.30.100.22NodenetBotz-prd-bot-ext-temp5-traps
1.3.6.1.4.1.5528.30.100.22.1NodenetBotz-prd-bot-ext-temp5-low-trapNetBotz External Temperature 5 Low Trap. This trap indicates that the lower limit for external temperature probe on port 5 has been exceeded.
1.3.6.1.4.1.5528.30.100.22.2NodenetBotz-prd-bot-ext-temp5-high-trapNetBotz External Temperature 5 High Trap. This trap indicates that the upper limit for external temperature probe on port 5 has been exceeded.
1.3.6.1.4.1.5528.30.100.22.3NodenetBotz-prd-bot-ext-temp5-trap-clearNetBotz External Temperature 5 Cleared Trap. The trap has been cleared because the temperature value for the temperature probe on port 5 has returned to accept…
1.3.6.1.4.1.5528.30.100.22.6NodenetBotz-prd-bot-ext-temp5-sensor-unpluggedNetBotz External Temperature 5 Sensor Unplugged Trap. The sensor is unplugged or malfunctioning.
1.3.6.1.4.1.5528.30.100.22.7NodenetBotz-prd-bot-ext-temp5-sensor-repluggedNetBotz External Temperature 5 Sensor Replugged Trap. The sensor was unplugged, but has been reconnected.
1.3.6.1.4.1.5528.30.100.23NodenetBotz-prd-bot-ext-temp6-traps
1.3.6.1.4.1.5528.30.100.23.1NodenetBotz-prd-bot-ext-temp6-low-trapNetBotz External Temperature 6 Low Trap. This trap indicates that the lower limit for external temperature probe on port 6 has been exceeded.
1.3.6.1.4.1.5528.30.100.23.2NodenetBotz-prd-bot-ext-temp6-high-trapNetBotz External Temperature 6 High Trap. This trap indicates that the upper limit for external temperature probe on port 6 has been exceeded.
1.3.6.1.4.1.5528.30.100.23.3NodenetBotz-prd-bot-ext-temp6-trap-clearNetBotz External Temperature 6 Cleared Trap. The trap has been cleared because the temperature value for the temperature probe on port 6 has returned to accept…
1.3.6.1.4.1.5528.30.100.23.6NodenetBotz-prd-bot-ext-temp6-sensor-unpluggedNetBotz External Temperature 6 Sensor Unplugged Trap. The sensor is unplugged or malfunctioning.
1.3.6.1.4.1.5528.30.100.23.7NodenetBotz-prd-bot-ext-temp6-sensor-repluggedNetBotz External Temperature 6 Sensor Replugged Trap. The sensor was unplugged, but has been reconnected.
1.3.6.1.4.1.5528.30.100.24NodenetBotz-prd-bot-ext-temp7-traps
1.3.6.1.4.1.5528.30.100.24.1NodenetBotz-prd-bot-ext-temp7-low-trapNetBotz External Temperature 7 Low Trap. This trap indicates that the lower limit for external temperature probe on port 7 has been exceeded.
1.3.6.1.4.1.5528.30.100.24.2NodenetBotz-prd-bot-ext-temp7-high-trapNetBotz External Temperature 7 High Trap. This trap indicates that the upper limit for external temperature probe on port 7 has been exceeded.
1.3.6.1.4.1.5528.30.100.24.3NodenetBotz-prd-bot-ext-temp7-trap-clearNetBotz External Temperature 7 Cleared Trap. The trap has been cleared because the temperature value for the temperature probe on port 7 has returned to accept…
1.3.6.1.4.1.5528.30.100.24.6NodenetBotz-prd-bot-ext-temp7-sensor-unpluggedNetBotz External Temperature 7 Sensor Unplugged Trap. The sensor is unplugged or malfunctioning.
1.3.6.1.4.1.5528.30.100.24.7NodenetBotz-prd-bot-ext-temp7-sensor-repluggedNetBotz External Temperature 7 Sensor Replugged Trap. The sensor was unplugged, but has been reconnected.
1.3.6.1.4.1.5528.30.100.25NodenetBotz-prd-bot-ext-dry5-traps
1.3.6.1.4.1.5528.30.100.25.2NodenetBotz-prd-bot-ext-dry5-triggered-trapNetBotz External Dry Contact 5 Triggered Trap. This trap indicates that the state of the dry contact sensor on Ext5 matches the alarm value.
1.3.6.1.4.1.5528.30.100.25.3NodenetBotz-prd-bot-ext-dry5-trap-clearNetBotz External Dry Contact 5 Cleared Trap. The trap has been cleared because the state of the dry contact sensor on Ext5 no longer matches the alarm value.
1.3.6.1.4.1.5528.30.100.26NodenetBotz-prd-bot-ext-dry6-traps
1.3.6.1.4.1.5528.30.100.26.2NodenetBotz-prd-bot-ext-dry6-triggered-trapNetBotz External Dry Contact 6 Triggered Trap. This trap indicates that the state of the dry contact sensor on Ext6 matches the alarm value.
1.3.6.1.4.1.5528.30.100.26.3NodenetBotz-prd-bot-ext-dry6-trap-clearNetBotz External Dry Contact 6 Cleared Trap. The trap has been cleared because the state of the dry contact sensor on Ext6 no longer matches the alarm value.
1.3.6.1.4.1.5528.30.100.27NodenetBotz-prd-bot-ext-dry7-traps
1.3.6.1.4.1.5528.30.100.27.2NodenetBotz-prd-bot-ext-dry7-triggered-trapNetBotz External Dry Contact 7 Triggered Trap. This trap indicates that the state of the dry contact sensor on Ext7 matches the alarm value.
1.3.6.1.4.1.5528.30.100.27.3NodenetBotz-prd-bot-ext-dry7-trap-clearNetBotz External Dry Contact 7 Cleared Trap. The trap has been cleared because the state of the dry contact sensor on Ext7 no longer matches the alarm value.
1.3.6.1.4.1.5528.30.100.28NodenetBotz-prd-bot-camera-motion-traps
1.3.6.1.4.1.5528.30.100.28.2NodenetBotz-prd-bot-camera-motion-trap-trippedNetBotz Camera Motion Sensor Tripped Trap. This trap indicates that the camera motion sensor has been triggered (motion has been detected).
1.3.6.1.4.1.5528.30.100.28.3NodenetBotz-prd-bot-camera-motion-trap-clearNetBotz Camera Motion Cleared Trap. The trap has been cleared because the camera motion sensor has returned to normal (no longer is detecting motion).
1.3.6.1.4.1.5528.30.100.29NodenetBotz-prd-bot-ext-humi1-traps
1.3.6.1.4.1.5528.30.100.29.1NodenetBotz-prd-bot-ext-humi1-low-trapNetBotz External Humidity 1 Low Trap. This trap indicates that the lower limit for external humidity probe on port 1 has been exceeded.
1.3.6.1.4.1.5528.30.100.29.2NodenetBotz-prd-bot-ext-humi1-high-trapNetBotz External Humidity 1 High Trap. This trap indicates that the upper limit for external humidity probe on port 1 has been exceeded.
1.3.6.1.4.1.5528.30.100.29.3NodenetBotz-prd-bot-ext-humi1-trap-clearNetBotz External Humidity 1 Cleared Trap. The trap has been cleared because the humidity value for the humidity probe on port 1 has returned to acceptable limi…
1.3.6.1.4.1.5528.30.100.29.6NodenetBotz-prd-bot-ext-humi1-sensor-unpluggedNetBotz External Humidity 1 Sensor Unplugged Trap. The sensor is unplugged or malfunctioning.
1.3.6.1.4.1.5528.30.100.29.7NodenetBotz-prd-bot-ext-humi1-sensor-repluggedNetBotz External Humidity 1 Sensor Replugged Trap. The sensor was unplugged, but has been reconnected.
1.3.6.1.4.1.5528.30.100.30NodenetBotz-prd-bot-ext-humi2-traps
1.3.6.1.4.1.5528.30.100.30.1NodenetBotz-prd-bot-ext-humi2-low-trapNetBotz External Humidity 2 Low Trap. This trap indicates that the lower limit for external humidity probe on port 2 has been exceeded.
1.3.6.1.4.1.5528.30.100.30.2NodenetBotz-prd-bot-ext-humi2-high-trapNetBotz External Humidity 2 High Trap. This trap indicates that the upper limit for external humidity probe on port 2 has been exceeded.
1.3.6.1.4.1.5528.30.100.30.3NodenetBotz-prd-bot-ext-humi2-trap-clearNetBotz External Humidity 2 Cleared Trap. The trap has been cleared because the humidity value for the humidity probe on port 2 has returned to acceptable limi…
1.3.6.1.4.1.5528.30.100.30.6NodenetBotz-prd-bot-ext-humi2-sensor-unpluggedNetBotz External Humidity 2 Sensor Unplugged Trap. The sensor is unplugged or malfunctioning.
1.3.6.1.4.1.5528.30.100.30.7NodenetBotz-prd-bot-ext-humi2-sensor-repluggedNetBotz External Humidity 2 Sensor Replugged Trap. The sensor was unplugged, but has been reconnected.
1.3.6.1.4.1.5528.30.100.31NodenetBotz-prd-bot-ext-humi3-traps
1.3.6.1.4.1.5528.30.100.31.1NodenetBotz-prd-bot-ext-humi3-low-trapNetBotz External Humidity 3 Low Trap. This trap indicates that the lower limit for external humidity probe on port 3 has been exceeded.
1.3.6.1.4.1.5528.30.100.31.2NodenetBotz-prd-bot-ext-humi3-high-trapNetBotz External Humidity 3 High Trap. This trap indicates that the upper limit for external humidity probe on port 3 has been exceeded.
1.3.6.1.4.1.5528.30.100.31.3NodenetBotz-prd-bot-ext-humi3-trap-clearNetBotz External Humidity 3 Cleared Trap. The trap has been cleared because the humidity value for the humidity probe on port 3 has returned to acceptable limi…
1.3.6.1.4.1.5528.30.100.31.6NodenetBotz-prd-bot-ext-humi3-sensor-unpluggedNetBotz External Humidity 3 Sensor Unplugged Trap. The sensor is unplugged or malfunctioning.
1.3.6.1.4.1.5528.30.100.31.7NodenetBotz-prd-bot-ext-humi3-sensor-repluggedNetBotz External Humidity 3 Sensor Replugged Trap. The sensor was unplugged, but has been reconnected.
1.3.6.1.4.1.5528.30.100.32NodenetBotz-prd-bot-ext-humi4-traps
1.3.6.1.4.1.5528.30.100.32.1NodenetBotz-prd-bot-ext-humi4-low-trapNetBotz External Humidity 4 Low Trap. This trap indicates that the lower limit for external humidity probe on port 4 has been exceeded.
1.3.6.1.4.1.5528.30.100.32.2NodenetBotz-prd-bot-ext-humi4-high-trapNetBotz External Humidity 4 High Trap. This trap indicates that the upper limit for external humidity probe on port 4 has been exceeded.
1.3.6.1.4.1.5528.30.100.32.3NodenetBotz-prd-bot-ext-humi4-trap-clearNetBotz External Humidity 4 Cleared Trap. The trap has been cleared because the humidity value for the humidity probe on port 4 has returned to acceptable limi…
1.3.6.1.4.1.5528.30.100.32.6NodenetBotz-prd-bot-ext-humi4-sensor-unpluggedNetBotz External Humidity 4 Sensor Unplugged Trap. The sensor is unplugged or malfunctioning.
1.3.6.1.4.1.5528.30.100.32.7NodenetBotz-prd-bot-ext-humi4-sensor-repluggedNetBotz External Humidity 4 Sensor Replugged Trap. The sensor was unplugged, but has been reconnected.
1.3.6.1.4.1.5528.30.100.33NodenetBotz-prd-bot-ext-humi5-traps
1.3.6.1.4.1.5528.30.100.33.1NodenetBotz-prd-bot-ext-humi5-low-trapNetBotz External Humidity 5 Low Trap. This trap indicates that the lower limit for external humidity probe on port 5 has been exceeded.
1.3.6.1.4.1.5528.30.100.33.2NodenetBotz-prd-bot-ext-humi5-high-trapNetBotz External Humidity 5 High Trap. This trap indicates that the upper limit for external humidity probe on port 5 has been exceeded.
1.3.6.1.4.1.5528.30.100.33.3NodenetBotz-prd-bot-ext-humi5-trap-clearNetBotz External Humidity 5 Cleared Trap. The trap has been cleared because the humidity value for the humidity probe on port 5 has returned to acceptable limi…
1.3.6.1.4.1.5528.30.100.33.6NodenetBotz-prd-bot-ext-humi5-sensor-unpluggedNetBotz External Humidity 5 Sensor Unplugged Trap. The sensor is unplugged or malfunctioning.
1.3.6.1.4.1.5528.30.100.33.7NodenetBotz-prd-bot-ext-humi5-sensor-repluggedNetBotz External Humidity 5 Sensor Replugged Trap. The sensor was unplugged, but has been reconnected.
1.3.6.1.4.1.5528.30.100.34NodenetBotz-prd-bot-ext-humi6-traps
1.3.6.1.4.1.5528.30.100.34.1NodenetBotz-prd-bot-ext-humi6-low-trapNetBotz External Humidity 6 Low Trap. This trap indicates that the lower limit for external humidity probe on port 6 has been exceeded.
1.3.6.1.4.1.5528.30.100.34.2NodenetBotz-prd-bot-ext-humi6-high-trapNetBotz External Humidity 6 High Trap. This trap indicates that the upper limit for external humidity probe on port 6 has been exceeded.
1.3.6.1.4.1.5528.30.100.34.3NodenetBotz-prd-bot-ext-humi6-trap-clearNetBotz External Humidity 6 Cleared Trap. The trap has been cleared because the humidity value for the humidity probe on port 6 has returned to acceptable limi…
1.3.6.1.4.1.5528.30.100.34.6NodenetBotz-prd-bot-ext-humi6-sensor-unpluggedNetBotz External Humidity 6 Sensor Unplugged Trap. The sensor is unplugged or malfunctioning.
1.3.6.1.4.1.5528.30.100.34.7NodenetBotz-prd-bot-ext-humi6-sensor-repluggedNetBotz External Humidity 6 Sensor Replugged Trap. The sensor was unplugged, but has been reconnected.
1.3.6.1.4.1.5528.30.100.35NodenetBotz-prd-bot-ext-humi7-traps
1.3.6.1.4.1.5528.30.100.35.1NodenetBotz-prd-bot-ext-humi7-low-trapNetBotz External Humidity 7 Low Trap. This trap indicates that the lower limit for external humidity probe on port 7 has been exceeded.
1.3.6.1.4.1.5528.30.100.35.2NodenetBotz-prd-bot-ext-humi7-high-trapNetBotz External Humidity 7 High Trap. This trap indicates that the upper limit for external humidity probe on port 7 has been exceeded.
1.3.6.1.4.1.5528.30.100.35.3NodenetBotz-prd-bot-ext-humi7-trap-clearNetBotz External Humidity 7 Cleared Trap. The trap has been cleared because the humidity value for the humidity probe on port 7 has returned to acceptable limi…
1.3.6.1.4.1.5528.30.100.35.6NodenetBotz-prd-bot-ext-humi7-sensor-unpluggedNetBotz External Humidity 7 Sensor Unplugged Trap. The sensor is unplugged or malfunctioning.
1.3.6.1.4.1.5528.30.100.35.7NodenetBotz-prd-bot-ext-humi7-sensor-repluggedNetBotz External Humidity 7 Sensor Replugged Trap. The sensor was unplugged, but has been reconnected.
1.3.6.1.4.1.5528.30.1000NodenetBotz-prd-WallBotz-300
1.3.6.1.4.1.5528.30.1001NodenetBotz-prd-RackBotz-300
1.3.6.1.4.1.5528.30.1002NodenetBotz-prd-RackBotz-300U
1.3.6.1.4.1.5528.30.1003NodenetBotz-prd-WallBotz-400
1.3.6.1.4.1.5528.30.1004NodenetBotz-prd-RackBotz-400
1.3.6.1.4.1.5528.30.1006NodenetBotz-prd-RackBotz-303
1.3.6.1.4.1.5528.30.1007NodenetBotz-prd-WallBotz-310
1.3.6.1.4.1.5528.30.1008NodenetBotz-prd-RackBotz-310
1.3.6.1.4.1.5528.30.1009NodenetBotz-prd-WallBotz-300B
1.3.6.1.4.1.5528.30.1100NodenetBotz-prd-WallBotz-300C
1.3.6.1.4.1.5528.30.1101NodenetBotz-prd-RackBotz-300C
1.3.6.1.4.1.5528.30.1102NodenetBotz-prd-RackBotz-300UC
1.3.6.1.4.1.5528.30.1103NodenetBotz-prd-WallBotz-400C
1.3.6.1.4.1.5528.30.1104NodenetBotz-prd-RackBotz-400C
1.3.6.1.4.1.5528.30.1106NodenetBotz-prd-RackBotz-303C
1.3.6.1.4.1.5528.30.1107NodenetBotz-prd-WallBotz-310C
1.3.6.1.4.1.5528.30.1108NodenetBotz-prd-RackBotz-310C
1.3.6.1.4.1.5528.30.1109NodenetBotz-prd-WallBotz-300BC
1.3.6.1.4.1.5528.30.1200NodenetBotz-prd-WallBotz-300E
1.3.6.1.4.1.5528.30.1201NodenetBotz-prd-RackBotz-300E
1.3.6.1.4.1.5528.30.1202NodenetBotz-prd-RackBotz-300UE
1.3.6.1.4.1.5528.30.1203NodenetBotz-prd-WallBotz-400E
1.3.6.1.4.1.5528.30.1204NodenetBotz-prd-RackBotz-400E
1.3.6.1.4.1.5528.30.1206NodenetBotz-prd-RackBotz-303E
1.3.6.1.4.1.5528.30.1207NodenetBotz-prd-WallBotz-310E
1.3.6.1.4.1.5528.30.1208NodenetBotz-prd-RackBotz-310E
1.3.6.1.4.1.5528.30.1209NodenetBotz-prd-WallBotz-300BE
1.3.6.1.4.1.5528.31TableexpPortTablenot-accessiblemandatoryA list of expansion port entries.
1.3.6.1.4.1.5528.31.1RowexpPortEntrynot-accessiblemandatoryAn expansion port entry for a single port
1.3.6.1.4.1.5528.31.1.1ColumnexpPort-module-idread-writemandatoryThe module ID of the sensor module installed. Blank string indicates that no module is installed.
1.3.6.1.4.1.5528.31.1.2ColumnexpPort-module-typeread-writemandatoryThe type of sensor module installed. NONE=no module, AMP=AmpDetect module, TEMP=temperature sensor, DRY=dry contact sensor.
1.3.6.1.4.1.5528.31.1.3ColumnexpPort-labelread-writemandatoryThe label for the expansion port. Ports default to the label 'Extn', for port n.
1.3.6.1.4.1.5528.31.1.20ColumnexpPort-ampsread-onlymandatoryThe reading of the amperage probe, in milliamps.
1.3.6.1.4.1.5528.31.1.21ColumnexpPort-total-amp-secondsread-onlymandatoryThe accumulated total of amp-seconds on the AmpDetect.
1.3.6.1.4.1.5528.31.1.22ColumnexpPort-total-amp-seconds-since-timeread-writemandatoryThe UTC time (seconds since 1/1/1970) of the beginning of the accumulated total of amp-seconds on the AmpDetect. Writing a value to this attribute resets the a…
1.3.6.1.4.1.5528.31.1.23ColumnexpPort-amps-enabledread-writemandatoryAmperage probe alarm enabled(1) or disabled(0).
1.3.6.1.4.1.5528.31.1.24ColumnexpPort-amps-minread-writemandatoryThe amperage probe minimum, from 0 to 30000 milliamps.
1.3.6.1.4.1.5528.31.1.25ColumnexpPort-amps-maxread-writemandatoryThe amperage probe maximum, from 0 to 30000 milliamps.
1.3.6.1.4.1.5528.31.1.26ColumnexpPort-amps-uV-per-10mAread-writemandatoryThe scaling factor used for the amperage probe to convert microvolts measured from the Amp Detect into 10s of milliamps of current. Needs to be set based on th…
1.3.6.1.4.1.5528.31.1.27ColumnexpPort-amps-max-rangeread-writemandatoryThe maximum RMS milliamps measureable by the AmpDetect.
1.3.6.1.4.1.5528.31.1.40ColumnexpPort-ext-tempread-onlymandatoryThe reading of the external temperature probe, in degrees F or degrees C (depends on netBotz-ismetric).
1.3.6.1.4.1.5528.31.1.41ColumnexpPort-ext-temp-enabledread-writemandatoryExternal temperature probe alarm enabled(1) or disabled(0).
1.3.6.1.4.1.5528.31.1.42ColumnexpPort-ext-temp-minread-writemandatoryThe external temperature probe minimum, in degrees F or degrees C (depends on netBotz-ismetric).
1.3.6.1.4.1.5528.31.1.43ColumnexpPort-ext-temp-maxread-writemandatoryThe external temperature probe maximum, in degrees F or degrees C (depends on netBotz-ismetric).
1.3.6.1.4.1.5528.31.1.44ColumnexpPort-ext-temp-uV-per-degreeCread-writemandatoryThe scaling factor used for the external temperature probe to convert microvolts measured from the temperature sensor into degrees C. Needs to be set based on …
1.3.6.1.4.1.5528.31.1.45ColumnexpPort-ext-temp-uV-at-0-degreeCread-writemandatoryThe offset used for the external temperature probe of microvolts measured from the temperature sensor at zero degrees C. Needs to be set based on the type of t…
1.3.6.1.4.1.5528.31.1.46ColumnexpPort-ext-temp-min-rangeread-writemandatoryThe minimum temperature measureable by the temperature sensor, in tenths of a degree C. Needs to be set based on the type of temperature sensor module installe…
1.3.6.1.4.1.5528.31.1.47ColumnexpPort-ext-temp-max-rangeread-writemandatoryThe maximum temperature measureable by the temperature sensor, in tenths of a degree C. Needs to be set based on the type of temperature sensor module installe…
1.3.6.1.4.1.5528.31.1.60ColumnexpPort-ext-dryread-onlymandatoryThe current value of the external dry contact sensor: 0=Open, 1=Closed, -1=N/A
1.3.6.1.4.1.5528.31.1.61ColumnexpPort-ext-dry-alarm-valueread-writemandatoryThe value to generate alarms on for the external dry contact sensor: 0=Open, 1=Closed
1.3.6.1.4.1.5528.31.1.62ColumnexpPort-ext-dry-enabledread-writemandatoryExternal dry contact sensor alarm enabled(1) or disabled(0).
1.3.6.1.4.1.5528.31.1.63ColumnexpPort-ext-dry-labelread-writemandatoryThe sensor name/label for the dry contact sensor
1.3.6.1.4.1.5528.31.1.64ColumnexpPort-ext-dry-open-labelread-writemandatoryThe sensor name/label for the open(0) state for the dry contact sensor
1.3.6.1.4.1.5528.31.1.65ColumnexpPort-ext-dry-closed-labelread-writemandatoryThe sensor name/label for the closed(0) state for the dry contact sensor
1.3.6.1.4.1.5528.31.1.66ColumnexpPort-ext-dry-open-to-close-millisread-writemandatoryThe minimum number of milliseconds that the dry contact sensor must read closed before the state is changed from open to closed.
1.3.6.1.4.1.5528.31.1.67ColumnexpPort-ext-dry-close-to-open-millisread-writemandatoryThe minimum number of milliseconds that the dry contact sensor must read openbefore the state is changed from closed to open.
1.3.6.1.4.1.5528.31.1.68ColumnexpPort-ext-dry-responseread-writemandatoryThe type of alert response for the dry contact sensor: ALERT=e-mail with no pictures, CAMERA=e-mail with pictures from camera.
1.3.6.1.4.1.5528.31.1.80ColumnexpPort-ext-humiread-onlymandatoryThe reading of the external humidity probe, in percent.
1.3.6.1.4.1.5528.31.1.81ColumnexpPort-ext-humi-enabledread-writemandatoryExternal humidity probe alarm enabled(1) or disabled(0).
1.3.6.1.4.1.5528.31.1.82ColumnexpPort-ext-humi-minread-writemandatoryThe external humidity probe minimum, in percent.
1.3.6.1.4.1.5528.31.1.83ColumnexpPort-ext-humi-maxread-writemandatoryThe external humidity probe maximum, in percent.
1.3.6.1.4.1.5528.31.1.84ColumnexpPort-ext-humi-uV-per-percentread-writemandatoryThe scaling factor used for the external humidity probe to convert microvolts measured from the humidity sensor into percent. Needs to be set based on the type…
1.3.6.1.4.1.5528.31.1.85ColumnexpPort-ext-humi-uV-at-0-percentread-writemandatoryThe offset used for the external humidity probe of microvolts measured from the humidity sensor at zero percent. Needs to be set based on the type of humidity …
1.3.6.1.4.1.5528.31.1.86ColumnexpPort-ext-humi-min-rangeread-writemandatoryThe minimum humidity measureable by the humidity sensor, in percent. Needs to be set based on the type of humidity sensor module installed.
1.3.6.1.4.1.5528.31.1.87ColumnexpPort-ext-humi-max-rangeread-writemandatoryThe maximum humidity measureable by the humidity sensor, in percent. Needs to be set based on the type of humidity sensor module installed.
1.3.6.1.4.1.5528.32NodenetBotz-metric
1.3.6.1.4.1.5528.32.10NodenetBotz-metric-onboard
1.3.6.1.4.1.5528.32.10.1ScalarnetBotz-metric-onboard-modelread-onlymandatoryThe model description of the appliance.
1.3.6.1.4.1.5528.32.10.2ScalarnetBotz-metric-onboard-tempread-onlymandatoryThe reading of the built-in temperature probe, in tenths of a degree C.
1.3.6.1.4.1.5528.32.10.3ScalarnetBotz-metric-onboard-humidityread-onlymandatoryThe reading of the built-in humidity probe, in percent.
1.3.6.1.4.1.5528.32.10.4ScalarnetBotz-metric-onboard-airflowread-onlymandatoryThe reading of the built-in airflow probe, in meters/minute.
1.3.6.1.4.1.5528.32.10.5ScalarnetBotz-metric-onboard-audioread-onlymandatoryThe reading of the built-in audio alarm probe on/off.
1.3.6.1.4.1.5528.32.10.6ScalarnetBotz-metric-onboard-doorajarread-onlymandatoryThe reading of the door switch probe open(1) or closed(0).
1.3.6.1.4.1.5528.32.10.7ScalarnetBotz-metric-onboard-temp-minread-onlymandatoryThe temperature probe minimum, from 1 to 50 degrees C in tenths of a degree C.
1.3.6.1.4.1.5528.32.10.8ScalarnetBotz-metric-onboard-temp-maxread-onlymandatoryThe temperature probe maximum, from 1 to 50 degrees C in tenths of a degree C.
1.3.6.1.4.1.5528.32.10.9ScalarnetBotz-metric-onboard-humidity-minread-onlymandatoryThe humidity probe minimum, from 10 to 90 percent.
1.3.6.1.4.1.5528.32.10.10ScalarnetBotz-metric-onboard-humidity-maxread-onlymandatoryThe humidity probe maximum, from 10 to 90 percent.
1.3.6.1.4.1.5528.32.10.11ScalarnetBotz-metric-onboard-airflow-minsread-onlymandatoryMinutes without airflow before alarm set.
1.3.6.1.4.1.5528.32.10.12ScalarnetBotz-metric-onboard-audio-secsread-onlymandatorySeconds of alarm audio before alarm set.
1.3.6.1.4.1.5528.32.10.13ScalarnetBotz-metric-onboard-switch-stateread-onlymandatorySwitch state setting. The state controls which condition of the door switch indicates an alarm. If set to 0, alarm is set when the switch is closed. If set to …
1.3.6.1.4.1.5528.32.10.14ScalarnetBotz-metric-onboard-audio-levelread-onlymandatoryAudio level setting, this is the relative audio level, from 0-11, above which an alarm will be sent.
1.3.6.1.4.1.5528.32.10.15ScalarnetBotz-metric-onboard-airflow-levelread-onlymandatoryAirflow alert level. This is the level, in meters per second, below which an alarm will be sent.
1.3.6.1.4.1.5528.32.10.16ScalarnetBotz-metric-onboard-cam-motionread-onlymandatoryThe current motion reading for the camera motion sensor (0=none, 1=motion detected, -1=not licensed).
1.3.6.1.4.1.5528.32.10.17ScalarnetBotz-metric-onboard-cam-motion-sensitivityread-onlymandatoryCamera motion sensor sensitivity: 1=max, 15=min, 0=disabled.
1.3.6.1.4.1.5528.40NodenetBotz-snmp
1.3.6.1.4.1.5528.40.1ScalarnetBotz-snmp-traptargetread-writemandatoryTarget of traps from the NetBotz device. This field contains the IP address where NetBotz traps are to be sent.
1.3.6.1.4.1.5528.40.2ScalarnetBotz-snmp-communityread-writemandatoryThe read/write community of the NetBotz device.
1.3.6.1.4.1.5528.40.3ScalarnetBotz-snmp-timeoutread-writemandatorySNMP Timeout period.
1.3.6.1.4.1.5528.40.4ScalarnetBotz-snmp-retriesread-writemandatorySNMP Retry count.
1.3.6.1.4.1.5528.40.5ScalarnetBotz-userid-1read-writemandatoryThe userID of the supervisor account (write-only).
1.3.6.1.4.1.5528.40.6ScalarnetBotz-password-1read-writemandatoryThe password of the supervisor account (write-only).
1.3.6.1.4.1.5528.40.7ScalarnetBotz-userid-2read-writemandatoryThe userID of the full read access account (write-only).
1.3.6.1.4.1.5528.40.8ScalarnetBotz-password-2read-writemandatoryThe password of the full read access account (write-only).
1.3.6.1.4.1.5528.40.9ScalarnetBotz-userid-3read-writemandatoryThe userID of the minimum read access account (write-only).
1.3.6.1.4.1.5528.40.10ScalarnetBotz-password-3read-writemandatoryThe password of the minimum read access account (write-only).
1.3.6.1.4.1.5528.40.11ScalarnetBotz-snmp-traptarget2read-writemandatorySecond target of traps from the NetBotz device. This field contains an additional IP address where NetBotz traps are to be sent.
1.3.6.1.4.1.5528.40.12ScalarnetBotz-snmp-read-communityread-writemandatoryThe read-only community of the NetBotz device.
1.3.6.1.4.1.5528.50NodenetBotz-device
1.3.6.1.4.1.5528.50.1ScalarnetBotz-dev-hostread-writemandatoryNetBotz device's host name.
1.3.6.1.4.1.5528.50.2ScalarnetBotz-dev-domainread-writemandatoryNetBotz device's default DNS domain.
1.3.6.1.4.1.5528.50.3ScalarnetBotz-dev-ipread-writemandatoryNetBotz device's IP address.
1.3.6.1.4.1.5528.50.4ScalarnetBotz-dev-netmaskread-writemandatoryNetBotz device's netmask.
1.3.6.1.4.1.5528.50.5ScalarnetBotz-dev-gatewayread-writemandatoryNetBotz device's default gateway/router. 0.0.0.0 if not defined.
1.3.6.1.4.1.5528.50.6ScalarnetBotz-dev-primarydnsread-writemandatoryPrimary Domain Name Server. 0.0.0.0 if not defined.
1.3.6.1.4.1.5528.50.7ScalarnetBotz-dev-secondarydnsread-writemandatorySecondary Domain Name Server. 0.0.0.0 if not defined.
1.3.6.1.4.1.5528.50.8ScalarnetBotz-dev-smtpread-writemandatorySMTP server address. This is the mail server used for sending alert e-mails.
1.3.6.1.4.1.5528.50.9ScalarnetBotz-dev-smtpportread-writemandatorySMTP port. Port number of SMTP server used for sending alert e-mails.
1.3.6.1.4.1.5528.50.10ScalarnetBotz-dev-popportread-writemandatoryPOP port. Currently, not used.
1.3.6.1.4.1.5528.50.11ScalarnetBotz-dev-loglevelread-writemandatoryThis field contains the log level of the NetBotz device. Log messages will be filtered, so that only same or lower-level messages will be passed. The default l…
1.3.6.1.4.1.5528.50.14ScalarnetBotz-dev-primaryemailread-writemandatoryThe primary email addresses for alerts and messages (list separated by commas for multiple addresses).
1.3.6.1.4.1.5528.50.15ScalarnetBotz-dev-secondaryemailread-writemandatoryThe secondary email address for alerts and messages (list separated by commas for multiple addresses).
1.3.6.1.4.1.5528.50.17ScalarnetBotz-dev-serialnoread-onlymandatoryThe serial number of the NetBotz device.
1.3.6.1.4.1.5528.50.18ScalarnetBotz-dev-popread-writemandatoryPOP server name. Currently, not used.
1.3.6.1.4.1.5528.50.19ScalarnetBotz-dev-versionread-onlymandatoryThe current NetBotz device firmware version.
1.3.6.1.4.1.5528.50.20ScalarnetBotz-dev-registeredread-onlymandatoryIndicates if the device has been registered with NetBotz, Inc. 1=registered, 0=not registered.
1.3.6.1.4.1.5528.50.21ScalarnetBotz-default-appletread-writemandatorySetting to control if default web page should launch applet by default(1) or the HTML status page(0).
1.3.6.1.4.1.5528.50.22ScalarnetBotz-guibar-colorread-writemandatorySetting for color of GUI bar (RGB). Value = 0xRRGGBB.
1.3.6.1.4.1.5528.50.23ScalarnetBotz-localeread-writemandatoryThe locale ID of the NetBotz device. Format is ISO 639 language (lower case), an underscore, and ISO 3166 country (upper case). Some locales are just the ISO 6…
1.3.6.1.4.1.5528.50.24ScalarnetBotz-timezoneread-writemandatoryThe timezone ID of the NetBotz device.
1.3.6.1.4.1.5528.50.25ScalarnetBotz-24hourpreferredread-writemandatoryIndicates if 24-hour(1) versus 12-hour(0) time format is preferred.
1.3.6.1.4.1.5528.50.26ScalarnetBotz-utc-clockread-writemandatoryCurrent time of clock on NetBotz device, in UTC seconds (seconds since 1/1/1970 12:00am GMT).
1.3.6.1.4.1.5528.50.27ScalarnetBotz-ismetricread-onlymandatoryUnits are metric (1) or U.S. (0). Applies to temperature and airflow rate.
1.3.6.1.4.1.5528.50.28ScalarnetBotz-alert-urlread-writemandatoryThe URL, if defined, to which non-picture alerts are HTTP POSTed
1.3.6.1.4.1.5528.50.29ScalarnetBotz-picture-alert-urlread-writemandatoryThe URL, if defined, to which picture alerts are HTTP POSTed, using multipart/form-data encoding.
1.3.6.1.4.1.5528.50.30ScalarnetBotz-sensor-data-urlread-writemandatoryThe URL, if defined, to which sensor data is periodically HTTP POSTed.
1.3.6.1.4.1.5528.50.31ScalarnetBotz-alert-url-logonread-writemandatoryThe user ID and password, if defined, used for POSTing non-picture alerts. Field is write-only, and formatted /
1.3.6.1.4.1.5528.50.32ScalarnetBotz-picture-alert-url-logonread-writemandatoryThe user ID and password, if defined, used for POSTing picture alerts. Field is write-only, and formatted /
1.3.6.1.4.1.5528.50.33ScalarnetBotz-sensor-data-url-logonread-writemandatoryThe user ID and password, if defined, used for POSTing sensor data. Field is write-only, and formatted /
1.3.6.1.4.1.5528.50.34ScalarnetBotz-sensor-data-url-periodread-writemandatoryDefault number of minutes between periodic sensor data HTTP POSTs.
1.3.6.1.4.1.5528.50.35ScalarnetBotz-sensor-data-url-flagsread-writemandatoryOption flags for data POSTs of sensor data. Bit 0=1 if current picture should be included. Bits 1-31 are reserved.
1.3.6.1.4.1.5528.50.36ScalarnetBotz-dev-backup-smtpread-writemandatoryBackup SMTP server address. This is the backup mail server used for sending alert e-mails.
1.3.6.1.4.1.5528.50.37ScalarnetBotz-dev-tertiarydnsread-writemandatoryTertiary Domain Name Server. 0.0.0.0 if not defined.
1.3.6.1.4.1.5528.50.38ScalarnetBotz-dev-ntp-serverread-writemandatoryNTP (Network Time Protocol) Server configured for appliance.
1.3.6.1.4.1.5528.50.39ScalarnetBotz-dev-ntp-periodread-writemandatoryHours between automatic refreshes of the appliance clock using the NTP server.
1.3.6.1.4.1.5528.50.40ScalarnetBotz-dev-socks-serverread-writemandatorySocks V4 or V5 proxy server configured for appliance.
1.3.6.1.4.1.5528.50.41ScalarnetBotz-dev-socks-portnumread-writemandatoryPort number of Socks Proxy.
1.3.6.1.4.1.5528.50.42ScalarnetBotz-dev-socks-user-idread-writemandatoryUser ID for Socks V4 or V5 proxy server configured for appliance.
1.3.6.1.4.1.5528.50.43ScalarnetBotz-dev-socks-passwordread-writemandatoryPassword for Socks V4 or V5 proxy server configured for appliance.
1.3.6.1.4.1.5528.50.44ScalarnetBotz-alert-ftp-siteread-writemandatoryThe hostname or dotted-decimal IP address of the FTP server to deliver alerts to
1.3.6.1.4.1.5528.50.45ScalarnetBotz-alert-ftp-pathread-writemandatoryThe directory on the FTP server to store alerts in.
1.3.6.1.4.1.5528.50.46ScalarnetBotz-alert-ftp-filenameread-writemandatoryThe base filename for the files on the FTP server to store alerts in.
1.3.6.1.4.1.5528.50.47ScalarnetBotz-alert-ftp-logonread-writemandatoryThe user-id and password on the FTP server to store alerts in. Field is write-only, and formatted /
1.3.6.1.4.1.5528.50.48ScalarnetBotz-sensor-ftp-siteread-writemandatoryThe hostname or dotted-decimal IP address of the FTP server to deliver periodic sensor reports to
1.3.6.1.4.1.5528.50.49ScalarnetBotz-sensor-ftp-pathread-writemandatoryThe directory on the FTP server to store periodic sensor reports in.
1.3.6.1.4.1.5528.50.50ScalarnetBotz-sensor-ftp-filenameread-writemandatoryThe base filename for the files on the FTP server to store periodic sensor reports in.
1.3.6.1.4.1.5528.50.51ScalarnetBotz-sensor-ftp-logonread-writemandatoryThe user-id and password on the FTP server to store sensor reports in. Field is write-only, and formatted /
1.3.6.1.4.1.5528.50.52ScalarnetBotz-sensor-ftp-periodread-writemandatoryThe period, in minutes, between delivery of sensor data reports.
1.3.6.1.4.1.5528.50.53ScalarnetBotz-use-syslogread-writemandatoryEnable syslog
1.3.6.1.4.1.5528.50.54ScalarnetBotz-syslog-addressread-writemandatoryHost address to use for syslogging
1.3.6.1.4.1.5528.50.55ScalarnetBotz-syslog-facilityread-writemandatorySyslog facility code
1.3.6.1.4.1.5528.50.56ScalarnetBotz-color-balanceread-writemandatoryColor balance for color camera. AUTO=automatic, FLUOR=fluorescent, DAY=daylight, INCAND=incandescent, x/y=Custom (scale red by x/64, scale blue by y/64)
1.3.6.1.4.1.5528.60NodenetBotz-addonapp
1.3.6.1.4.1.5528.60.2Nodedevice-crawlers-trap-target-index
1.3.6.1.4.1.5528.60.3Nodebranch-checker-trap-target-index
1.3.6.1.4.1.5528.60.5528Nodevendor-netBotz
1.3.6.1.4.1.5528.60.5528.2Nodedevice-crawlers-trap
1.3.6.1.4.1.5528.60.5528.2.1NodenetBotz-device-crawlers-value-low-alert-trapNetBotz Device Crawlers Value Low Trap. This trap indicates that the lower limit on a monitored value has been exceeded.
1.3.6.1.4.1.5528.60.5528.2.2NodenetBotz-device-crawlers-value-high-alert-trapNetBotz Device Crawlers Value High Trap. This trap indicates that the upper limit on a monitored value has been exceeded.
1.3.6.1.4.1.5528.60.5528.2.3NodenetBotz-device-crawlers-clear-alert-trapNetBotz Device Crawlers Clear Trap. This trap indicates that the previous alert condition has been cleared.
1.3.6.1.4.1.5528.60.5528.2.4NodenetBotz-device-crawlers-offline-alert-trapNetBotz Device Crawlers Offline Trap. This trap indicates that a monitored target could not be contacted.
1.3.6.1.4.1.5528.60.5528.2.5NodenetBotz-device-crawlers-online-alert-trapNetBotz Device Crawlers Online Trap. This trap indicates that a monitored target that previously could not be contacted has now been contacted successfully.
1.3.6.1.4.1.5528.60.5528.2.8NodenetBotz-device-crawlers-ifopstatus-alert-trapNetBotz Device Crawlers Interface Operational Status Trap. This trap indicates that one or more of a monitored target's network interfaces operational status i…
1.3.6.1.4.1.5528.60.5528.3Nodebranch-checker-trap
1.3.6.1.4.1.5528.60.5528.3.3NodenetBotz-branch-checker-clear-alert-trapNetBotz Branch Checker Clear Trap. This trap indicates that the previous alert condition has been cleared.
1.3.6.1.4.1.5528.60.5528.3.4NodenetBotz-branch-checker-offline-alert-trapNetBotz Branch Checker Offline Trap. This trap indicates that a monitored target could not be contacted.
1.3.6.1.4.1.5528.60.5528.3.5NodenetBotz-branch-checker-online-alert-trapNetBotz Branch Checker Online Trap. This trap indicates that a monitored target that previously could not be contacted has now been contacted successfully.
1.3.6.1.4.1.5528.60.5528.3.12NodenetBotz-branch-checker-target-error-trapNetBotz Branch Target Error Trap. This trap indicates that a monitored target could be contacted, but not withing the timeout period specified.
1.3.6.1.4.1.5528.61NodenetBotz-addonapp-trap
1.3.6.1.4.1.5528.61.2Nodedevice-crawlers-trap-attrib
1.3.6.1.4.1.5528.61.2.20Scalardevice-crawlers-trap-indexread-onlymandatoryThe ID of the device crawler which sent the last trap.
1.3.6.1.4.1.5528.61.2.21Scalardevice-crawlers-trap-addressread-onlymandatoryThe IP address of the appliance actually creating the last trap.
1.3.6.1.4.1.5528.61.2.22Scalardevice-crawlers-trap-oidread-onlymandatoryThe object id of the attribute on the device crawlers target device which is the concern of the last trap. The second to last element indicates the index of th…
1.3.6.1.4.1.5528.61.2.23Scalardevice-crawlers-trap-botoidread-onlymandatoryThe object id of the device crawlers attribute on the NetBotz device which is the concern of the last trap.
1.3.6.1.4.1.5528.61.2.24Scalardevice-crawlers-trap-valueread-onlymandatoryThe integer value of the device crawlers attribute associated with the last trap.
1.3.6.1.4.1.5528.61.2.25Scalardevice-crawlers-trap-stringvalueread-onlymandatoryThe string representation of the value of the device crawlers attribute associated with the last trap.
1.3.6.1.4.1.5528.61.2.26Scalardevice-crawlers-trap-dateread-onlymandatoryThe date and time of a specific device crawlers trap. This field contains the number of seconds elapsed since midnight (00:00:00), January 1, 1970
1.3.6.1.4.1.5528.61.2.27Scalardevice-crawlers-trap-attrib-indexread-onlymandatoryThe identification number of the device crawlers attribute in error
1.3.6.1.4.1.5528.61.2.28Scalardevice-crawlers-crawlers-trap-descread-onlymandatoryDescription of the Device Crawlers Trap Attribute
1.3.6.1.4.1.5528.61.3Nodebranch-checker-trap-attrib
1.3.6.1.4.1.5528.61.3.20Scalarbranch-checker-trap-indexread-onlymandatoryThe ID of the branch checker which sent the last trap.
1.3.6.1.4.1.5528.61.3.21Scalarbranch-checker-trap-addressread-onlymandatoryThe IP address of the appliance actually creating the last trap.
1.3.6.1.4.1.5528.61.3.22Scalarbranch-checker-trap-oidread-onlymandatoryThe object id of the attribute on the branch checker target device which is the concern of the last trap The second to last element is the index of the source …
1.3.6.1.4.1.5528.61.3.23Scalarbranch-checker-trap-botoidread-onlymandatoryThe object id of the branch checker attribute on the NetBotz device which is the concern of the last trap. The second to last element is the index of the sourc…
1.3.6.1.4.1.5528.61.3.24Scalarbranch-checker-trap-valueread-onlymandatoryThe integer value of the branch checker attribute associated with the last trap.
1.3.6.1.4.1.5528.61.3.25Scalarbranch-checker-trap-stringvalueread-onlymandatoryThe string representation of the value of the branch checker attribute associated with the last trap.
1.3.6.1.4.1.5528.61.3.26Scalarbranch-checker-trap-dateread-onlymandatoryThe date and time of a specific branch checker trap. This field contains the number of seconds elapsed since midnight (00:00:00), January 1, 1970
1.3.6.1.4.1.5528.61.3.27Scalarbranch-checker-trap-attrib-indexread-onlymandatoryThe identification number of the branch checker attribute in error
1.3.6.1.4.1.5528.61.3.28Scalarbranch-checker-trap-descread-onlymandatoryDescription of the Branch Checker Trap Attribute