NETIO-PRODUCTS-NETIO-MIB
22 objects
Netio specific data structures
Imported Objects
| SNMPv2-SMI | enterprises MODULE-IDENTITY OBJECT-TYPE |
| SNMPv2-TC | DateAndTime |
| OID | Name | Access | Status | Description |
|---|---|---|---|---|
| 1.3.6.1.4.1.47952 | IdentitynetioProducts | Netio specific data structures | ||
| 1.3.6.1.4.1.47952.1 | Nodenetio4 | |||
| 1.3.6.1.4.1.47952.1.1 | TablenetioOutputTable | not-accessible | current | This table contains current status of Netio outputs. |
| 1.3.6.1.4.1.47952.1.1.1 | RownetioOutputEntry | not-accessible | current | A row describing one netio output. |
| 1.3.6.1.4.1.47952.1.1.1.1 | ColumnnetioOutputID | read-only | current | Output number. |
| 1.3.6.1.4.1.47952.1.1.1.2 | ColumnnetioOutputName | read-only | current | Description of the output given by user. |
| 1.3.6.1.4.1.47952.1.1.1.3 | ColumnnetioOutputState | read-only | current | Current output state. |
| 1.3.6.1.4.1.47952.1.1.1.4 | ColumnnetioOutputStateString | read-only | current | Current output state (string). |
| 1.3.6.1.4.1.47952.1.1.1.5 | ColumnnetioOutputAction | read-write | current | Command to control output. |
| 1.3.6.1.4.1.47952.1.1.1.25 | ColumnnetioOutputLoad | read-only | current | Current power consumption in Watts. 0 when power meters are not available |
| 1.3.6.1.4.1.47952.1.1.1.26 | ColumnnetioOutputEnergy | read-only | current | Cumulated consumption from netioOutputEnergyStart. In Wh. 0 when power meters are not available. |
| 1.3.6.1.4.1.47952.1.1.1.27 | ColumnnetioOutputEnergyStart | read-only | current | Start time from which energy is counted. UTC based. for backward compatibility only, is the same for all outputs. use netioGlobalMeasure.netioEnergyStart inste… |
| 1.3.6.1.4.1.47952.1.1.1.28 | ColumnnetioOutputCurrent | read-only | current | Current current in mA. 0 when power meters are not available |
| 1.3.6.1.4.1.47952.1.1.1.29 | ColumnnetioOutputPowerFactor | read-only | current | Current power factor * 1000. 0 when power meters are not available |
| 1.3.6.1.4.1.47952.1.2 | NodenetioGlobalMeasure | |||
| 1.3.6.1.4.1.47952.1.2.1 | ScalarnetioVoltage | read-only | current | Voltage in the power grid in mV. 0 when power meters are not available |
| 1.3.6.1.4.1.47952.1.2.2 | ScalarnetioFrequency | read-only | current | Frequency in the power grid in mHz. 0 when power meters are not available |
| 1.3.6.1.4.1.47952.1.2.3 | ScalarnetioTotalCurrent | read-only | current | Total current for all outputs in mA. 0 when power meters are not available |
| 1.3.6.1.4.1.47952.1.2.4 | ScalarnetioOverallPowerFactor | read-only | current | Overall power factor across all outputs. 0 when power meters are not available |
| 1.3.6.1.4.1.47952.1.2.5 | ScalarnetioTotalLoad | read-only | current | Total load for all outputs in W. 0 when power meters are not available |
| 1.3.6.1.4.1.47952.1.2.6 | ScalarnetioTotalEnergy | read-only | current | Total energy for all outputs in Wh starting from netioEnergyStart. 0 when power meters are not available |
| 1.3.6.1.4.1.47952.1.2.7 | ScalarnetioEnergyStart | read-only | current | Start time from which energy is counted. UTC based. |