NETSURE-DISTRIB-MIB
148 objects
Vertiv Co. Distribution MIB, revision A.
Imported Objects
| SNMPv2-SMI | Counter32 enterprises Integer32 IpAddress mgmt MODULE-IDENTITY NOTIFICATION-TYPE OBJECT-TYPE TimeTicks |
| SNMPv2-TC | DateAndTime DisplayString TEXTUAL-CONVENTION |
| OID | Name | Access | Status | Description |
|---|---|---|---|---|
| 1.3.6.1.2.1 | Nodestdmib-2 | |||
| 1.3.6.1.2.1.1 | Nodesystem | |||
| 1.3.6.1.2.1.1.1 | ScalarsysDescr | read-only | current | A textual description of the Power System entity. |
| 1.3.6.1.2.1.1.2 | ScalarsysObjectID | read-only | current | 1.3.6.1.4.1.6302.3.1 which is the base OID for the information in this MIB . |
| 1.3.6.1.2.1.1.3 | ScalarsysUpTime | read-only | current | The time (in hundredths of a second) since the network management portion of the system was last re-initialized. |
| 1.3.6.1.2.1.1.4 | ScalarsysContact | read-write | current | The textual identification of the contact person for this managed node, together with information on how to contact this person. |
| 1.3.6.1.2.1.1.5 | ScalarsysName | read-write | current | An administratively-assigned name for this managed node. By convention, this is the node's fully-qualified domain name. |
| 1.3.6.1.2.1.1.6 | ScalarsysLocation | read-write | current | The physical location of this node (e.g., `telephone closet, 3rd floor'). |
| 1.3.6.1.2.1.1.7 | ScalarsysServices | read-only | current | A value which indicates the set of services that this entity primarily offers. The value is a sum. This sum initially takes the value zero, Then, for each laye… |
| 1.3.6.1.4.1.6302 | Nodeees | |||
| 1.3.6.1.4.1.6302.4 | Nodeglobal | |||
| 1.3.6.1.4.1.6302.4.1 | IdentitydistribMIB | Vertiv Co. Distribution MIB, revision A. | ||
| 1.3.6.1.4.1.6302.4.1.1 | Nodeident | |||
| 1.3.6.1.4.1.6302.4.1.1.1 | ScalaridentManufacturer | read-only | current | The name of the equipment manufacturer. |
| 1.3.6.1.4.1.6302.4.1.1.2 | ScalaridentModel | read-only | current | The manufacturers model designation of the controller. |
| 1.3.6.1.4.1.6302.4.1.1.3 | ScalaridentControllerFirmwareVersion | read-only | current | The firmware (software) version of the controller. |
| 1.3.6.1.4.1.6302.4.1.1.4 | ScalaridentName | read-write | current | The name of the distribution bay. This object should be set by the administrator. |
| 1.3.6.1.4.1.6302.4.1.1.5 | ScalaridentControllerSerialNumber | read-only | current | The serial number of this controller |
| 1.3.6.1.4.1.6302.4.1.2 | Nodesys | |||
| 1.3.6.1.4.1.6302.4.1.2.1 | Nodebay | |||
| 1.3.6.1.4.1.6302.4.1.2.1.1 | ScalarbaySiteName | read-write | current | User-provided, 32 characters |
| 1.3.6.1.4.1.6302.4.1.2.1.2 | ScalarbayTotalCurrentOutput | read-only | current | Total current (sum of all feeds) in mA |
| 1.3.6.1.4.1.6302.4.1.2.1.3 | ScalarbayTotalPower | read-only | current | Output power (sum of all feeds) in Watts |
| 1.3.6.1.4.1.6302.4.1.2.1.4 | ScalarbayPeakPowerLast24hrs | read-only | current | Maximum output power over the past 24 hours in Watts |
| 1.3.6.1.4.1.6302.4.1.2.1.5 | ScalarbayPeakPowerLastWeek | read-only | current | Maximum output power over the past 7 days in Watts |
| 1.3.6.1.4.1.6302.4.1.2.1.6 | ScalarbayPeakPowerLastMonth | read-only | current | Maximum output power over the past 30 days in Watts |
| 1.3.6.1.4.1.6302.4.1.2.1.7 | ScalarbayTotalEnergyLast24hrs | read-only | current | Total output energy over the past 24 hours in 0.001 kWh |
| 1.3.6.1.4.1.6302.4.1.2.1.8 | ScalarbayTotalEnergyLastWeek | read-only | current | Total output energy over the past 7 days in 0.001 kWh |
| 1.3.6.1.4.1.6302.4.1.2.1.9 | ScalarbayTotalEnergyLastMonth | read-only | current | Total output energy over the past 30 days in 0.001 kWh |
| 1.3.6.1.4.1.6302.4.1.2.1.10 | ScalarbayTotalEnergy | read-only | current | Total/cumulative output energy since last reset, stored as 0.001kWh |
| 1.3.6.1.4.1.6302.4.1.2.1.11 | ScalarbayRelay1Status | read-only | current | On/Off status of relay 1. 0=off 1=on |
| 1.3.6.1.4.1.6302.4.1.2.1.12 | ScalarbayRelay2Status | read-only | current | On/Off status of relay 2. 0=off 1=on |
| 1.3.6.1.4.1.6302.4.1.2.1.13 | ScalarbayRelay3Status | read-only | current | On/Off status of relay 3. 0=off 1=on |
| 1.3.6.1.4.1.6302.4.1.2.1.14 | ScalarbayRelay4Status | read-only | current | On/Off status of relay 4. 0=off 1=on |
| 1.3.6.1.4.1.6302.4.1.2.1.15 | ScalarbayFACBStatus | read-only | current | FA-CB for all panels in the bay. 0=ok 1=alarm |
| 1.3.6.1.4.1.6302.4.1.2.1.16 | ScalarbayClearAccumulatedValues | read-write | current | Used to clear values peak power and total energy, for all accumulated values in this the bay Write 1 to clear values |
| 1.3.6.1.4.1.6302.4.1.2.1.17 | ScalarbayCurrentBreakerSize | read-write | current | Rated current for the bay in mA |
| 1.3.6.1.4.1.6302.4.1.2.1.18 | ScalarbayHighCurrentLimit1 | read-write | current | Threshold for high current alarm in 0.001 % |
| 1.3.6.1.4.1.6302.4.1.2.1.19 | ScalarbayHighCurrentLimit2 | read-write | current | Threshold for high-high current alarm in 0.001 % |
| 1.3.6.1.4.1.6302.4.1.2.1.20 | ScalarbayPanelConfiguration | read-write | current | Number of panels positions: 0=2 1=4 2=6 3=8 |
| 1.3.6.1.4.1.6302.4.1.2.2 | Nodepanel | |||
| 1.3.6.1.4.1.6302.4.1.2.2.1 | TablepanelTable | not-accessible | current | Panel Table. |
| 1.3.6.1.4.1.6302.4.1.2.2.1.1 | RowpanelEntry | not-accessible | current | Panel Table Entry. |
| 1.3.6.1.4.1.6302.4.1.2.2.1.1.1 | ColumnpanelIndex | read-only | current | Automatically generated index object. |
| 1.3.6.1.4.1.6302.4.1.2.2.1.1.2 | ColumnpanelPosition | read-only | current | A through H (assigned by the controller),a(0) or b(1) or c(2) or d(3) or e(4) or f(5) or g(6) or h(7) |
| 1.3.6.1.4.1.6302.4.1.2.2.1.1.3 | ColumnpanelName | read-write | current | User-provided, 32 characters |
| 1.3.6.1.4.1.6302.4.1.2.2.1.1.4 | ColumnpanelEnabled | read-write | current | Enabled (0) or Disabled (1) |
| 1.3.6.1.4.1.6302.4.1.2.2.1.1.5 | ColumnpanelType | read-write | current | Standard (0) or Advanced (1) |
| 1.3.6.1.4.1.6302.4.1.2.2.1.1.6 | ColumnpanelFeed | read-write | current | FeedID of Panel |
| 1.3.6.1.4.1.6302.4.1.2.2.1.1.7 | ColumnpanelClearAccumulatedValues | read-write | current | Used to clear accumulated values for all distribution devices in this this panel Write 1 to clear values |
| 1.3.6.1.4.1.6302.4.1.2.2.1.1.8 | ColumnpanelDistributionMeasurementType | read-write | current | Hall (0) or Shunt (1) (advanced panels only) |
| 1.3.6.1.4.1.6302.4.1.2.2.1.1.9 | ColumnpanelNumberDistributionElements | read-write | current | Number of distributions points in this panel |
| 1.3.6.1.4.1.6302.4.1.2.3 | Nodefeed | |||
| 1.3.6.1.4.1.6302.4.1.2.3.1 | TablefeedTable | not-accessible | current | Feed Table. |
| 1.3.6.1.4.1.6302.4.1.2.3.1.1 | RowfeedEntry | not-accessible | current | Feed Table Entry. |
| 1.3.6.1.4.1.6302.4.1.2.3.1.1.1 | ColumnfeedIndex | read-only | current | Automatically generated index object. |
| 1.3.6.1.4.1.6302.4.1.2.3.1.1.2 | ColumnfeedID | read-only | current | 1 through 8 (assigned by the controller) |
| 1.3.6.1.4.1.6302.4.1.2.3.1.1.3 | ColumnfeedName | read-write | current | User-provided, 32 characters |
| 1.3.6.1.4.1.6302.4.1.2.3.1.1.4 | ColumnfeedOutputVoltage | read-only | current | Output voltage in mV |
| 1.3.6.1.4.1.6302.4.1.2.3.1.1.5 | ColumnfeedTotalCurrent | read-only | current | Output current in mA |
| 1.3.6.1.4.1.6302.4.1.2.3.1.1.6 | ColumnfeedTotalPower | read-only | current | Output power in Watts |
| 1.3.6.1.4.1.6302.4.1.2.3.1.1.7 | ColumnfeedPeakPowerLast24hrs | read-only | current | Maximum output power over the past 24 hours in Watts |
| 1.3.6.1.4.1.6302.4.1.2.3.1.1.8 | ColumnfeedPeakPowerLastWeek | read-only | current | Maximum output power over the past 7 days in Watts |
| 1.3.6.1.4.1.6302.4.1.2.3.1.1.9 | ColumnfeedPeakPowerLastMonth | read-only | current | Maximum output power over the past 30 days in Watts |
| 1.3.6.1.4.1.6302.4.1.2.3.1.1.10 | ColumnfeedTotalEnergyLast24hrs | read-only | current | Total output energy over the past 24 hours in 0.001 kWh |
| 1.3.6.1.4.1.6302.4.1.2.3.1.1.11 | ColumnfeedTotalEnergyLastWeek | read-only | current | Total output energy over the past 7 days in 0.001 kWh |
| 1.3.6.1.4.1.6302.4.1.2.3.1.1.12 | ColumnfeedTotalEnergyLastMonth | read-only | current | Total output energy over the past 30 days in 0.001 kWh |
| 1.3.6.1.4.1.6302.4.1.2.3.1.1.13 | ColumnfeedTotalEnergy | read-only | current | Total/cumulative output energy since last reset, stored as 0.001 kWh |
| 1.3.6.1.4.1.6302.4.1.2.3.1.1.14 | ColumnfeedFACBStatus | read-only | current | FA-CB Status 0=ok 1=alarm |
| 1.3.6.1.4.1.6302.4.1.2.3.1.1.15 | ColumnfeedClearAccumulatedValues | read-write | current | Used to clear accumulated values in the feed Write 1 to clear values |
| 1.3.6.1.4.1.6302.4.1.2.3.1.1.16 | ColumnfeedOverVoltage1 | read-write | current | Threshold for over-voltage alarm 1 in mV |
| 1.3.6.1.4.1.6302.4.1.2.3.1.1.17 | ColumnfeedOverVoltage2 | read-write | current | Threshold for over-voltage alarm 2 in mV |
| 1.3.6.1.4.1.6302.4.1.2.3.1.1.18 | ColumnfeedUnderVoltage1 | read-write | current | Threshold for the low voltage alarm 1 in mV |
| 1.3.6.1.4.1.6302.4.1.2.3.1.1.19 | ColumnfeedUnderVoltage2 | read-write | current | Threshold for the low voltage alarm 2 in mV |
| 1.3.6.1.4.1.6302.4.1.2.3.1.1.20 | ColumnfeedCurrentBreakerSize | read-write | current | Rating of the fuse/CB in Amps |
| 1.3.6.1.4.1.6302.4.1.2.3.1.1.21 | ColumnfeedCurrent1Limit | read-write | current | Threshold for high current alarm in 0.001 % |
| 1.3.6.1.4.1.6302.4.1.2.3.1.1.22 | ColumnfeedCurrent2Limit | read-write | current | Threshold for very high current alarm in 0.001 % |
| 1.3.6.1.4.1.6302.4.1.2.3.1.1.23 | ColumnfeedShuntVoltage | read-write | current | Shunt voltage rating in mV |
| 1.3.6.1.4.1.6302.4.1.2.3.1.1.24 | ColumnfeedShuntCurrent | read-write | current | Shunt current rating in mA |
| 1.3.6.1.4.1.6302.4.1.2.4 | Nodedevice | |||
| 1.3.6.1.4.1.6302.4.1.2.4.1 | TabledeviceTable | not-accessible | current | Device Table. |
| 1.3.6.1.4.1.6302.4.1.2.4.1.1 | RowdeviceEntry | not-accessible | current | Device Table Entry. |
| 1.3.6.1.4.1.6302.4.1.2.4.1.1.1 | ColumndeviceIndex | read-only | current | Automatically generated index object |
| 1.3.6.1.4.1.6302.4.1.2.4.1.1.2 | ColumndevicePanel | read-only | current | The panel containing this device (A=1, B=2, etc.). |
| 1.3.6.1.4.1.6302.4.1.2.4.1.1.3 | ColumndeviceID | read-only | current | The distribution device's ID/position |
| 1.3.6.1.4.1.6302.4.1.2.4.1.1.4 | ColumndeviceName | read-write | current | User-provided, 32 characters |
| 1.3.6.1.4.1.6302.4.1.2.4.1.1.5 | ColumndeviceExists | read-write | current | Used (0) or not Used (1) |
| 1.3.6.1.4.1.6302.4.1.2.4.1.1.6 | ColumndeviceTotalCurrent | read-only | current | Total output current in mA |
| 1.3.6.1.4.1.6302.4.1.2.4.1.1.7 | ColumndeviceTotalPower | read-only | current | Total output power in Watts |
| 1.3.6.1.4.1.6302.4.1.2.4.1.1.8 | ColumndevicePeakPowerLast24hrs | read-only | current | Maximum output power over the past 24 hours in Watts |
| 1.3.6.1.4.1.6302.4.1.2.4.1.1.9 | ColumndevicePeakPowerLastWeek | read-only | current | Maximum output power over the past 7 days in Watts |
| 1.3.6.1.4.1.6302.4.1.2.4.1.1.10 | ColumndevicePeakPowerLastMonth | read-only | current | Maximum output power over the past 30 days in Watts |
| 1.3.6.1.4.1.6302.4.1.2.4.1.1.11 | ColumndeviceTotalEnergyLast24hrs | read-only | current | Total output power over the past 24 hours in 0.001 kWh |
| 1.3.6.1.4.1.6302.4.1.2.4.1.1.12 | ColumndeviceTotalEnergyLastWeek | read-only | current | Total output power over the past 7 days in 0.001 kWh |
| 1.3.6.1.4.1.6302.4.1.2.4.1.1.13 | ColumndeviceTotalEnergyLastMonth | read-only | current | Total output power over the past 30 days in 0.001 kWh |
| 1.3.6.1.4.1.6302.4.1.2.4.1.1.14 | ColumndeviceTotalEnergy | read-only | current | Total/cumulative output energy since last reset, stored as 0.001 kWh |
| 1.3.6.1.4.1.6302.4.1.2.4.1.1.15 | ColumndeviceFACBStatus | read-only | current | FA-CB Status 0=ok 1=alarm |
| 1.3.6.1.4.1.6302.4.1.2.4.1.1.16 | ColumndeviceClearAccumulatedValues | read-write | current | Used to clear accumulated values Write 1 to clear values |
| 1.3.6.1.4.1.6302.4.1.2.4.1.1.17 | ColumndeviceCurrentBreakerSize | read-write | current | Rating of the fuse/CB in mA |
| 1.3.6.1.4.1.6302.4.1.2.4.1.1.18 | ColumndeviceHighCurrentLimit1 | read-write | current | Threshold for high current alarm in 0.001 % |
| 1.3.6.1.4.1.6302.4.1.2.4.1.1.19 | ColumndeviceHighCurrentLimit2 | read-write | current | Threshold for very high current alarm in 0.001 % |
| 1.3.6.1.4.1.6302.4.1.2.4.1.1.20 | ColumndeviceNumberofBreakerPositions | read-write | current | Number of breaker positions (1 to 3). The positions are contiguous. Contiguous breaker positions are treated as one distribution device. one=(0) or two=(1) or … |
| 1.3.6.1.4.1.6302.4.1.2.5 | Nodeload | |||
| 1.3.6.1.4.1.6302.4.1.2.5.1 | TableloadTable | not-accessible | current | Load Table. |
| 1.3.6.1.4.1.6302.4.1.2.5.1.1 | RowloadEntry | not-accessible | current | Load Table Entry. |
| 1.3.6.1.4.1.6302.4.1.2.5.1.1.1 | ColumnloadIndex | read-only | current | Automatically generated index object. |
| 1.3.6.1.4.1.6302.4.1.2.5.1.1.2 | ColumnloadName | read-write | current | User-provided, 32 characters |
| 1.3.6.1.4.1.6302.4.1.2.5.1.1.3 | ColumnloadTotalCurrent | read-only | current | Total output current in mA |
| 1.3.6.1.4.1.6302.4.1.2.5.1.1.4 | ColumnloadTotalPower | read-only | current | Total output power in Watts |
| 1.3.6.1.4.1.6302.4.1.2.5.1.1.5 | ColumnloadPeakPowerLast24hrs | read-only | current | Maximum output power over the past 24 hours in Watts |
| 1.3.6.1.4.1.6302.4.1.2.5.1.1.6 | ColumnloadPeakPowerLastWeek | read-only | current | Maximum output power over the past 7 days in Watts |
| 1.3.6.1.4.1.6302.4.1.2.5.1.1.7 | ColumnloadPeakPowerLastMonth | read-only | current | Maximum output power over the past 30 days in Watts |
| 1.3.6.1.4.1.6302.4.1.2.5.1.1.8 | ColumnloadTotalEnergyLast24hrs | read-only | current | Total output power over the past 24 hours in 0.001 kWh |
| 1.3.6.1.4.1.6302.4.1.2.5.1.1.9 | ColumnloadTotalEnergyLastWeek | read-only | current | Total output power over the past 7 days in 0.001 kWh |
| 1.3.6.1.4.1.6302.4.1.2.5.1.1.10 | ColumnloadTotalEnergyLastMonth | read-only | current | Total output power over the past 30 days in 0.001 kWh |
| 1.3.6.1.4.1.6302.4.1.2.5.1.1.11 | ColumnloadTotalEnergy | read-only | current | Total/cumulative output energy since last reset in 0.001 kWh |
| 1.3.6.1.4.1.6302.4.1.2.5.1.1.12 | ColumnloadClearAccumulatedValues | read-write | current | Used to clear accumulated values Write 1 value to clear values |
| 1.3.6.1.4.1.6302.4.1.2.5.1.1.13 | ColumnloadMaximumCurrent | read-write | current | Maximum current in amps for the load; the total current is never expected to exceed this value |
| 1.3.6.1.4.1.6302.4.1.2.5.1.1.14 | ColumnloadHighCurrentLimit1 | read-write | current | Threshold for high current alarm in 0.001 % |
| 1.3.6.1.4.1.6302.4.1.2.5.1.1.15 | ColumnloadHighCurrentLimit2 | read-write | current | Threshold for very high current alarm in 0.001 % |
| 1.3.6.1.4.1.6302.4.1.2.15 | TablepsEquipmentSignalTable | not-accessible | current | Table of indexed equipment signal values. |
| 1.3.6.1.4.1.6302.4.1.2.15.1 | RowequipmentSignalTableEntry | not-accessible | current | An entry (conceptual row) in the psEquipment Signal Table. |
| 1.3.6.1.4.1.6302.4.1.2.15.1.1 | ColumnpsEquipmentSignalTableEntryIndex | read-only | current | The unique sequence number of this equipment signal. |
| 1.3.6.1.4.1.6302.4.1.2.15.1.2 | ColumnpsEquipmentSignalValue | read-only | current | Indexed equipment signal value. |
| 1.3.6.1.4.1.6302.4.1.3 | ScalaralarmLastTrapNo | read-only | current | The sequence number of last submitted alarm trap, also last row in alarmTrapTable. |
| 1.3.6.1.4.1.6302.4.1.4 | TablealarmActiveAlarmTable | not-accessible | current | Table holding information about the currently active alarms. |
| 1.3.6.1.4.1.6302.4.1.4.1 | RowactiveAlarmEntry | not-accessible | current | An entry (conceptual row) in the alarmTrapTable. |
| 1.3.6.1.4.1.6302.4.1.4.1.1 | ColumnalarmIndex | read-only | current | The unique sequence number of this alarm trap. |
| 1.3.6.1.4.1.6302.4.1.4.1.2 | ColumnalarmTime | read-only | current | Date and time when event occured (local time), including timezone if supported by controller. |
| 1.3.6.1.4.1.6302.4.1.4.1.3 | ColumnalarmStatusChange | read-only | current | The type of alarm change. One of (1) activated (2) deactivated |
| 1.3.6.1.4.1.6302.4.1.4.1.4 | ColumnalarmSeverity | read-only | current | The severity of the alarm. One of (3) warning - OA, lowest level of alarm severity (4) minor - A3 (5) major - MA (6) critical - CA, highest level of alarm seve… |
| 1.3.6.1.4.1.6302.4.1.4.1.5 | ColumnalarmDescription | read-only | current | Free-text description of alarm. |
| 1.3.6.1.4.1.6302.4.1.4.1.6 | ColumnalarmType | read-only | current | Alarm type, i.e. an integer specifying the type of alarm. |
| 1.3.6.1.4.1.6302.4.1.5 | NodepowerEvents | |||
| 1.3.6.1.4.1.6302.4.1.5.1 | NotificationalarmTrap | current | An alarm trap is sent when an alarm occurs (activated) or returns to normal state (deactivated). Alarm traps are logged in alarmTrapTable. Variables in this tr… | |
| 1.3.6.1.4.1.6302.4.1.5.2 | NotificationalarmActiveTrap | current | An alarm trap is sent when an alarm occurs (activated) Variables in this trap * alarmTime - Date and time when event occured (local time), including timezone i… | |
| 1.3.6.1.4.1.6302.4.1.5.3 | NotificationalarmCeaseTrap | current | An alarm trap is sent when an alarm returns to normal state (clear, deactivated). Variables in this trap: * alarmTime - Date and time when event occured (local… |
Type Definitions
| Name | Syntax | Status | Description |
|---|---|---|---|
| ClearDataOptions | INTEGER { clear(1) } | current | Indicates 'Clear' (1) |
| DeviceNumberofBreaker | INTEGER { one(0), two(1), three(2), four(3) } | current | Indicates 'one' (0) or 'two' (1) or 'three' (2) or 'four' (3) |
| EnableState | INTEGER { enabled(0), disabled(1) } | current | Indicates 'enabled' (0) or 'disabled' (1) |
| FACBState | INTEGER { ok(0), alarm(1) } | current | Indicates 'ok' (0) or 'alarm' (1) |
| MeasurementType | INTEGER { hall(0), shunt(1) } | current | Indicates'Hall' (0) or 'Shunt' (1) |
| PanelPositionNum | INTEGER { two(0), four(1), six(2), eight(3) } | current | Indicates 'two' (0) or 'four' (1) or 'six' (2) or 'eight' (3) |
| PanelPositionString | INTEGER { a(0), b(1), c(2), d(3), e(4), f(5), g(6), h(7) } | current | Indicates 'a' (0) or 'b' (1) or 'c' (2) or 'd' (3) or 'e' (4) or 'f' (5) or 'g' (6) or 'h' (7) |
| PanelTypeOptions | INTEGER { standard(0), advanced(1) } | current | Indicates 'Standard' (0) or 'Advanced' (1) |
| RelayState | INTEGER { off(0), on(1) } | current | Indicates 'off' (0) or 'on' (1) |
| Status | INTEGER { unknown(1), normal(2), warning(3), minor(4), major(5), critical(6), unmanaged(7), restricted(8), testing(9), disabled(10) } | current | This integer value represents the operational or administrative status of the system. Also used as alarm severity. Depending on situation there may be limits on allowed values. Operational values: (1) unknown - status h… |
| StatusChange | INTEGER { activated(1), deactivated(2) } | current | Indicates 'activated' (1) or 'deactivated' (2) alarm events. |