NETSURE-DISTRIB-MIB

148 objects
Vertiv Co. Distribution MIB, revision A.
Imported Objects
SNMPv2-SMICounter32 enterprises Integer32 IpAddress mgmt MODULE-IDENTITY NOTIFICATION-TYPE OBJECT-TYPE TimeTicks
SNMPv2-TCDateAndTime DisplayString TEXTUAL-CONVENTION
OIDNameAccessStatusDescription
1.3.6.1.2.1Nodestdmib-2
1.3.6.1.2.1.1Nodesystem
1.3.6.1.2.1.1.1ScalarsysDescrread-onlycurrentA textual description of the Power System entity.
1.3.6.1.2.1.1.2ScalarsysObjectIDread-onlycurrent1.3.6.1.4.1.6302.3.1 which is the base OID for the information in this MIB .
1.3.6.1.2.1.1.3ScalarsysUpTimeread-onlycurrentThe time (in hundredths of a second) since the network management portion of the system was last re-initialized.
1.3.6.1.2.1.1.4ScalarsysContactread-writecurrentThe textual identification of the contact person for this managed node, together with information on how to contact this person.
1.3.6.1.2.1.1.5ScalarsysNameread-writecurrentAn administratively-assigned name for this managed node. By convention, this is the node's fully-qualified domain name.
1.3.6.1.2.1.1.6ScalarsysLocationread-writecurrentThe physical location of this node (e.g., `telephone closet, 3rd floor').
1.3.6.1.2.1.1.7ScalarsysServicesread-onlycurrentA value which indicates the set of services that this entity primarily offers. The value is a sum. This sum initially takes the value zero, Then, for each laye…
1.3.6.1.4.1.6302Nodeees
1.3.6.1.4.1.6302.4Nodeglobal
1.3.6.1.4.1.6302.4.1IdentitydistribMIBVertiv Co. Distribution MIB, revision A.
1.3.6.1.4.1.6302.4.1.1Nodeident
1.3.6.1.4.1.6302.4.1.1.1ScalaridentManufacturerread-onlycurrentThe name of the equipment manufacturer.
1.3.6.1.4.1.6302.4.1.1.2ScalaridentModelread-onlycurrentThe manufacturers model designation of the controller.
1.3.6.1.4.1.6302.4.1.1.3ScalaridentControllerFirmwareVersionread-onlycurrentThe firmware (software) version of the controller.
1.3.6.1.4.1.6302.4.1.1.4ScalaridentNameread-writecurrentThe name of the distribution bay. This object should be set by the administrator.
1.3.6.1.4.1.6302.4.1.1.5ScalaridentControllerSerialNumberread-onlycurrentThe serial number of this controller
1.3.6.1.4.1.6302.4.1.2Nodesys
1.3.6.1.4.1.6302.4.1.2.1Nodebay
1.3.6.1.4.1.6302.4.1.2.1.1ScalarbaySiteNameread-writecurrentUser-provided, 32 characters
1.3.6.1.4.1.6302.4.1.2.1.2ScalarbayTotalCurrentOutputread-onlycurrentTotal current (sum of all feeds) in mA
1.3.6.1.4.1.6302.4.1.2.1.3ScalarbayTotalPowerread-onlycurrentOutput power (sum of all feeds) in Watts
1.3.6.1.4.1.6302.4.1.2.1.4ScalarbayPeakPowerLast24hrsread-onlycurrentMaximum output power over the past 24 hours in Watts
1.3.6.1.4.1.6302.4.1.2.1.5ScalarbayPeakPowerLastWeekread-onlycurrentMaximum output power over the past 7 days in Watts
1.3.6.1.4.1.6302.4.1.2.1.6ScalarbayPeakPowerLastMonthread-onlycurrentMaximum output power over the past 30 days in Watts
1.3.6.1.4.1.6302.4.1.2.1.7ScalarbayTotalEnergyLast24hrsread-onlycurrentTotal output energy over the past 24 hours in 0.001 kWh
1.3.6.1.4.1.6302.4.1.2.1.8ScalarbayTotalEnergyLastWeekread-onlycurrentTotal output energy over the past 7 days in 0.001 kWh
1.3.6.1.4.1.6302.4.1.2.1.9ScalarbayTotalEnergyLastMonthread-onlycurrentTotal output energy over the past 30 days in 0.001 kWh
1.3.6.1.4.1.6302.4.1.2.1.10ScalarbayTotalEnergyread-onlycurrentTotal/cumulative output energy since last reset, stored as 0.001kWh
1.3.6.1.4.1.6302.4.1.2.1.11ScalarbayRelay1Statusread-onlycurrentOn/Off status of relay 1. 0=off 1=on
1.3.6.1.4.1.6302.4.1.2.1.12ScalarbayRelay2Statusread-onlycurrentOn/Off status of relay 2. 0=off 1=on
1.3.6.1.4.1.6302.4.1.2.1.13ScalarbayRelay3Statusread-onlycurrentOn/Off status of relay 3. 0=off 1=on
1.3.6.1.4.1.6302.4.1.2.1.14ScalarbayRelay4Statusread-onlycurrentOn/Off status of relay 4. 0=off 1=on
1.3.6.1.4.1.6302.4.1.2.1.15ScalarbayFACBStatusread-onlycurrentFA-CB for all panels in the bay. 0=ok 1=alarm
1.3.6.1.4.1.6302.4.1.2.1.16ScalarbayClearAccumulatedValuesread-writecurrentUsed to clear values peak power and total energy, for all accumulated values in this the bay Write 1 to clear values
1.3.6.1.4.1.6302.4.1.2.1.17ScalarbayCurrentBreakerSizeread-writecurrentRated current for the bay in mA
1.3.6.1.4.1.6302.4.1.2.1.18ScalarbayHighCurrentLimit1read-writecurrentThreshold for high current alarm in 0.001 %
1.3.6.1.4.1.6302.4.1.2.1.19ScalarbayHighCurrentLimit2read-writecurrentThreshold for high-high current alarm in 0.001 %
1.3.6.1.4.1.6302.4.1.2.1.20ScalarbayPanelConfigurationread-writecurrentNumber of panels positions: 0=2 1=4 2=6 3=8
1.3.6.1.4.1.6302.4.1.2.2Nodepanel
1.3.6.1.4.1.6302.4.1.2.2.1TablepanelTablenot-accessiblecurrentPanel Table.
1.3.6.1.4.1.6302.4.1.2.2.1.1RowpanelEntrynot-accessiblecurrentPanel Table Entry.
1.3.6.1.4.1.6302.4.1.2.2.1.1.1ColumnpanelIndexread-onlycurrentAutomatically generated index object.
1.3.6.1.4.1.6302.4.1.2.2.1.1.2ColumnpanelPositionread-onlycurrentA through H (assigned by the controller),a(0) or b(1) or c(2) or d(3) or e(4) or f(5) or g(6) or h(7)
1.3.6.1.4.1.6302.4.1.2.2.1.1.3ColumnpanelNameread-writecurrentUser-provided, 32 characters
1.3.6.1.4.1.6302.4.1.2.2.1.1.4ColumnpanelEnabledread-writecurrentEnabled (0) or Disabled (1)
1.3.6.1.4.1.6302.4.1.2.2.1.1.5ColumnpanelTyperead-writecurrentStandard (0) or Advanced (1)
1.3.6.1.4.1.6302.4.1.2.2.1.1.6ColumnpanelFeedread-writecurrentFeedID of Panel
1.3.6.1.4.1.6302.4.1.2.2.1.1.7ColumnpanelClearAccumulatedValuesread-writecurrentUsed to clear accumulated values for all distribution devices in this this panel Write 1 to clear values
1.3.6.1.4.1.6302.4.1.2.2.1.1.8ColumnpanelDistributionMeasurementTyperead-writecurrentHall (0) or Shunt (1) (advanced panels only)
1.3.6.1.4.1.6302.4.1.2.2.1.1.9ColumnpanelNumberDistributionElementsread-writecurrentNumber of distributions points in this panel
1.3.6.1.4.1.6302.4.1.2.3Nodefeed
1.3.6.1.4.1.6302.4.1.2.3.1TablefeedTablenot-accessiblecurrentFeed Table.
1.3.6.1.4.1.6302.4.1.2.3.1.1RowfeedEntrynot-accessiblecurrentFeed Table Entry.
1.3.6.1.4.1.6302.4.1.2.3.1.1.1ColumnfeedIndexread-onlycurrentAutomatically generated index object.
1.3.6.1.4.1.6302.4.1.2.3.1.1.2ColumnfeedIDread-onlycurrent1 through 8 (assigned by the controller)
1.3.6.1.4.1.6302.4.1.2.3.1.1.3ColumnfeedNameread-writecurrentUser-provided, 32 characters
1.3.6.1.4.1.6302.4.1.2.3.1.1.4ColumnfeedOutputVoltageread-onlycurrentOutput voltage in mV
1.3.6.1.4.1.6302.4.1.2.3.1.1.5ColumnfeedTotalCurrentread-onlycurrentOutput current in mA
1.3.6.1.4.1.6302.4.1.2.3.1.1.6ColumnfeedTotalPowerread-onlycurrentOutput power in Watts
1.3.6.1.4.1.6302.4.1.2.3.1.1.7ColumnfeedPeakPowerLast24hrsread-onlycurrentMaximum output power over the past 24 hours in Watts
1.3.6.1.4.1.6302.4.1.2.3.1.1.8ColumnfeedPeakPowerLastWeekread-onlycurrentMaximum output power over the past 7 days in Watts
1.3.6.1.4.1.6302.4.1.2.3.1.1.9ColumnfeedPeakPowerLastMonthread-onlycurrentMaximum output power over the past 30 days in Watts
1.3.6.1.4.1.6302.4.1.2.3.1.1.10ColumnfeedTotalEnergyLast24hrsread-onlycurrentTotal output energy over the past 24 hours in 0.001 kWh
1.3.6.1.4.1.6302.4.1.2.3.1.1.11ColumnfeedTotalEnergyLastWeekread-onlycurrentTotal output energy over the past 7 days in 0.001 kWh
1.3.6.1.4.1.6302.4.1.2.3.1.1.12ColumnfeedTotalEnergyLastMonthread-onlycurrentTotal output energy over the past 30 days in 0.001 kWh
1.3.6.1.4.1.6302.4.1.2.3.1.1.13ColumnfeedTotalEnergyread-onlycurrentTotal/cumulative output energy since last reset, stored as 0.001 kWh
1.3.6.1.4.1.6302.4.1.2.3.1.1.14ColumnfeedFACBStatusread-onlycurrentFA-CB Status 0=ok 1=alarm
1.3.6.1.4.1.6302.4.1.2.3.1.1.15ColumnfeedClearAccumulatedValuesread-writecurrentUsed to clear accumulated values in the feed Write 1 to clear values
1.3.6.1.4.1.6302.4.1.2.3.1.1.16ColumnfeedOverVoltage1read-writecurrentThreshold for over-voltage alarm 1 in mV
1.3.6.1.4.1.6302.4.1.2.3.1.1.17ColumnfeedOverVoltage2read-writecurrentThreshold for over-voltage alarm 2 in mV
1.3.6.1.4.1.6302.4.1.2.3.1.1.18ColumnfeedUnderVoltage1read-writecurrentThreshold for the low voltage alarm 1 in mV
1.3.6.1.4.1.6302.4.1.2.3.1.1.19ColumnfeedUnderVoltage2read-writecurrentThreshold for the low voltage alarm 2 in mV
1.3.6.1.4.1.6302.4.1.2.3.1.1.20ColumnfeedCurrentBreakerSizeread-writecurrentRating of the fuse/CB in Amps
1.3.6.1.4.1.6302.4.1.2.3.1.1.21ColumnfeedCurrent1Limitread-writecurrentThreshold for high current alarm in 0.001 %
1.3.6.1.4.1.6302.4.1.2.3.1.1.22ColumnfeedCurrent2Limitread-writecurrentThreshold for very high current alarm in 0.001 %
1.3.6.1.4.1.6302.4.1.2.3.1.1.23ColumnfeedShuntVoltageread-writecurrentShunt voltage rating in mV
1.3.6.1.4.1.6302.4.1.2.3.1.1.24ColumnfeedShuntCurrentread-writecurrentShunt current rating in mA
1.3.6.1.4.1.6302.4.1.2.4Nodedevice
1.3.6.1.4.1.6302.4.1.2.4.1TabledeviceTablenot-accessiblecurrentDevice Table.
1.3.6.1.4.1.6302.4.1.2.4.1.1RowdeviceEntrynot-accessiblecurrentDevice Table Entry.
1.3.6.1.4.1.6302.4.1.2.4.1.1.1ColumndeviceIndexread-onlycurrentAutomatically generated index object
1.3.6.1.4.1.6302.4.1.2.4.1.1.2ColumndevicePanelread-onlycurrentThe panel containing this device (A=1, B=2, etc.).
1.3.6.1.4.1.6302.4.1.2.4.1.1.3ColumndeviceIDread-onlycurrentThe distribution device's ID/position
1.3.6.1.4.1.6302.4.1.2.4.1.1.4ColumndeviceNameread-writecurrentUser-provided, 32 characters
1.3.6.1.4.1.6302.4.1.2.4.1.1.5ColumndeviceExistsread-writecurrentUsed (0) or not Used (1)
1.3.6.1.4.1.6302.4.1.2.4.1.1.6ColumndeviceTotalCurrentread-onlycurrentTotal output current in mA
1.3.6.1.4.1.6302.4.1.2.4.1.1.7ColumndeviceTotalPowerread-onlycurrentTotal output power in Watts
1.3.6.1.4.1.6302.4.1.2.4.1.1.8ColumndevicePeakPowerLast24hrsread-onlycurrentMaximum output power over the past 24 hours in Watts
1.3.6.1.4.1.6302.4.1.2.4.1.1.9ColumndevicePeakPowerLastWeekread-onlycurrentMaximum output power over the past 7 days in Watts
1.3.6.1.4.1.6302.4.1.2.4.1.1.10ColumndevicePeakPowerLastMonthread-onlycurrentMaximum output power over the past 30 days in Watts
1.3.6.1.4.1.6302.4.1.2.4.1.1.11ColumndeviceTotalEnergyLast24hrsread-onlycurrentTotal output power over the past 24 hours in 0.001 kWh
1.3.6.1.4.1.6302.4.1.2.4.1.1.12ColumndeviceTotalEnergyLastWeekread-onlycurrentTotal output power over the past 7 days in 0.001 kWh
1.3.6.1.4.1.6302.4.1.2.4.1.1.13ColumndeviceTotalEnergyLastMonthread-onlycurrentTotal output power over the past 30 days in 0.001 kWh
1.3.6.1.4.1.6302.4.1.2.4.1.1.14ColumndeviceTotalEnergyread-onlycurrentTotal/cumulative output energy since last reset, stored as 0.001 kWh
1.3.6.1.4.1.6302.4.1.2.4.1.1.15ColumndeviceFACBStatusread-onlycurrentFA-CB Status 0=ok 1=alarm
1.3.6.1.4.1.6302.4.1.2.4.1.1.16ColumndeviceClearAccumulatedValuesread-writecurrentUsed to clear accumulated values Write 1 to clear values
1.3.6.1.4.1.6302.4.1.2.4.1.1.17ColumndeviceCurrentBreakerSizeread-writecurrentRating of the fuse/CB in mA
1.3.6.1.4.1.6302.4.1.2.4.1.1.18ColumndeviceHighCurrentLimit1read-writecurrentThreshold for high current alarm in 0.001 %
1.3.6.1.4.1.6302.4.1.2.4.1.1.19ColumndeviceHighCurrentLimit2read-writecurrentThreshold for very high current alarm in 0.001 %
1.3.6.1.4.1.6302.4.1.2.4.1.1.20ColumndeviceNumberofBreakerPositionsread-writecurrentNumber of breaker positions (1 to 3). The positions are contiguous. Contiguous breaker positions are treated as one distribution device. one=(0) or two=(1) or …
1.3.6.1.4.1.6302.4.1.2.5Nodeload
1.3.6.1.4.1.6302.4.1.2.5.1TableloadTablenot-accessiblecurrentLoad Table.
1.3.6.1.4.1.6302.4.1.2.5.1.1RowloadEntrynot-accessiblecurrentLoad Table Entry.
1.3.6.1.4.1.6302.4.1.2.5.1.1.1ColumnloadIndexread-onlycurrentAutomatically generated index object.
1.3.6.1.4.1.6302.4.1.2.5.1.1.2ColumnloadNameread-writecurrentUser-provided, 32 characters
1.3.6.1.4.1.6302.4.1.2.5.1.1.3ColumnloadTotalCurrentread-onlycurrentTotal output current in mA
1.3.6.1.4.1.6302.4.1.2.5.1.1.4ColumnloadTotalPowerread-onlycurrentTotal output power in Watts
1.3.6.1.4.1.6302.4.1.2.5.1.1.5ColumnloadPeakPowerLast24hrsread-onlycurrentMaximum output power over the past 24 hours in Watts
1.3.6.1.4.1.6302.4.1.2.5.1.1.6ColumnloadPeakPowerLastWeekread-onlycurrentMaximum output power over the past 7 days in Watts
1.3.6.1.4.1.6302.4.1.2.5.1.1.7ColumnloadPeakPowerLastMonthread-onlycurrentMaximum output power over the past 30 days in Watts
1.3.6.1.4.1.6302.4.1.2.5.1.1.8ColumnloadTotalEnergyLast24hrsread-onlycurrentTotal output power over the past 24 hours in 0.001 kWh
1.3.6.1.4.1.6302.4.1.2.5.1.1.9ColumnloadTotalEnergyLastWeekread-onlycurrentTotal output power over the past 7 days in 0.001 kWh
1.3.6.1.4.1.6302.4.1.2.5.1.1.10ColumnloadTotalEnergyLastMonthread-onlycurrentTotal output power over the past 30 days in 0.001 kWh
1.3.6.1.4.1.6302.4.1.2.5.1.1.11ColumnloadTotalEnergyread-onlycurrentTotal/cumulative output energy since last reset in 0.001 kWh
1.3.6.1.4.1.6302.4.1.2.5.1.1.12ColumnloadClearAccumulatedValuesread-writecurrentUsed to clear accumulated values Write 1 value to clear values
1.3.6.1.4.1.6302.4.1.2.5.1.1.13ColumnloadMaximumCurrentread-writecurrentMaximum current in amps for the load; the total current is never expected to exceed this value
1.3.6.1.4.1.6302.4.1.2.5.1.1.14ColumnloadHighCurrentLimit1read-writecurrentThreshold for high current alarm in 0.001 %
1.3.6.1.4.1.6302.4.1.2.5.1.1.15ColumnloadHighCurrentLimit2read-writecurrentThreshold for very high current alarm in 0.001 %
1.3.6.1.4.1.6302.4.1.2.15TablepsEquipmentSignalTablenot-accessiblecurrentTable of indexed equipment signal values.
1.3.6.1.4.1.6302.4.1.2.15.1RowequipmentSignalTableEntrynot-accessiblecurrentAn entry (conceptual row) in the psEquipment Signal Table.
1.3.6.1.4.1.6302.4.1.2.15.1.1ColumnpsEquipmentSignalTableEntryIndexread-onlycurrentThe unique sequence number of this equipment signal.
1.3.6.1.4.1.6302.4.1.2.15.1.2ColumnpsEquipmentSignalValueread-onlycurrentIndexed equipment signal value.
1.3.6.1.4.1.6302.4.1.3ScalaralarmLastTrapNoread-onlycurrentThe sequence number of last submitted alarm trap, also last row in alarmTrapTable.
1.3.6.1.4.1.6302.4.1.4TablealarmActiveAlarmTablenot-accessiblecurrentTable holding information about the currently active alarms.
1.3.6.1.4.1.6302.4.1.4.1RowactiveAlarmEntrynot-accessiblecurrentAn entry (conceptual row) in the alarmTrapTable.
1.3.6.1.4.1.6302.4.1.4.1.1ColumnalarmIndexread-onlycurrentThe unique sequence number of this alarm trap.
1.3.6.1.4.1.6302.4.1.4.1.2ColumnalarmTimeread-onlycurrentDate and time when event occured (local time), including timezone if supported by controller.
1.3.6.1.4.1.6302.4.1.4.1.3ColumnalarmStatusChangeread-onlycurrentThe type of alarm change. One of (1) activated (2) deactivated
1.3.6.1.4.1.6302.4.1.4.1.4ColumnalarmSeverityread-onlycurrentThe severity of the alarm. One of (3) warning - OA, lowest level of alarm severity (4) minor - A3 (5) major - MA (6) critical - CA, highest level of alarm seve…
1.3.6.1.4.1.6302.4.1.4.1.5ColumnalarmDescriptionread-onlycurrentFree-text description of alarm.
1.3.6.1.4.1.6302.4.1.4.1.6ColumnalarmTyperead-onlycurrentAlarm type, i.e. an integer specifying the type of alarm.
1.3.6.1.4.1.6302.4.1.5NodepowerEvents
1.3.6.1.4.1.6302.4.1.5.1NotificationalarmTrapcurrentAn alarm trap is sent when an alarm occurs (activated) or returns to normal state (deactivated). Alarm traps are logged in alarmTrapTable. Variables in this tr…
1.3.6.1.4.1.6302.4.1.5.2NotificationalarmActiveTrapcurrentAn alarm trap is sent when an alarm occurs (activated) Variables in this trap * alarmTime - Date and time when event occured (local time), including timezone i…
1.3.6.1.4.1.6302.4.1.5.3NotificationalarmCeaseTrapcurrentAn alarm trap is sent when an alarm returns to normal state (clear, deactivated). Variables in this trap: * alarmTime - Date and time when event occured (local…
Type Definitions
NameSyntaxStatusDescription
ClearDataOptionsINTEGER { clear(1) }currentIndicates 'Clear' (1)
DeviceNumberofBreakerINTEGER { one(0), two(1), three(2), four(3) }currentIndicates 'one' (0) or 'two' (1) or 'three' (2) or 'four' (3)
EnableStateINTEGER { enabled(0), disabled(1) }currentIndicates 'enabled' (0) or 'disabled' (1)
FACBStateINTEGER { ok(0), alarm(1) }currentIndicates 'ok' (0) or 'alarm' (1)
MeasurementTypeINTEGER { hall(0), shunt(1) }currentIndicates'Hall' (0) or 'Shunt' (1)
PanelPositionNumINTEGER { two(0), four(1), six(2), eight(3) }currentIndicates 'two' (0) or 'four' (1) or 'six' (2) or 'eight' (3)
PanelPositionStringINTEGER { a(0), b(1), c(2), d(3), e(4), f(5), g(6), h(7) }currentIndicates 'a' (0) or 'b' (1) or 'c' (2) or 'd' (3) or 'e' (4) or 'f' (5) or 'g' (6) or 'h' (7)
PanelTypeOptionsINTEGER { standard(0), advanced(1) }currentIndicates 'Standard' (0) or 'Advanced' (1)
RelayStateINTEGER { off(0), on(1) }currentIndicates 'off' (0) or 'on' (1)
StatusINTEGER { unknown(1), normal(2), warning(3), minor(4), major(5), critical(6), unmanaged(7), restricted(8), testing(9), disabled(10) }currentThis integer value represents the operational or administrative status of the system. Also used as alarm severity. Depending on situation there may be limits on allowed values. Operational values: (1) unknown - status h…
StatusChangeINTEGER { activated(1), deactivated(2) }currentIndicates 'activated' (1) or 'deactivated' (2) alarm events.