NETSURE-NCU-MIB
247 objects
Vertiv Tech Co. Ltd Power MIB, revision S.
Imported Objects
| SNMPv2-SMI | Counter32 enterprises Integer32 MODULE-IDENTITY NOTIFICATION-TYPE OBJECT-TYPE |
| SNMPv2-TC | DateAndTime DisplayString TEXTUAL-CONVENTION |
| OID | Name | Access | Status | Description |
|---|---|---|---|---|
| 1.3.6.1.4.1.6302 | Nodeees | |||
| 1.3.6.1.4.1.6302.2 | Nodeglobal | |||
| 1.3.6.1.4.1.6302.2.1 | IdentitypowerMIB | Vertiv Tech Co. Ltd Power MIB, revision S. | ||
| 1.3.6.1.4.1.6302.2.1.1 | Nodeident | |||
| 1.3.6.1.4.1.6302.2.1.1.1 | ScalaridentManufacturer | read-only | current | The name of the equipment manufacturer. |
| 1.3.6.1.4.1.6302.2.1.1.2 | ScalaridentModel | read-only | current | The manufacturers model designation of the power system. |
| 1.3.6.1.4.1.6302.2.1.1.3 | ScalaridentControllerFirmwareVersion | read-only | current | The firmware (software) version of the controller. |
| 1.3.6.1.4.1.6302.2.1.1.4 | ScalaridentName | read-write | current | The name of the power plant. This object should be set by the administrator. |
| 1.3.6.1.4.1.6302.2.1.1.5 | ScalaridentSNMPCfgVer | read-only | current | SNMP Config Version. |
| 1.3.6.1.4.1.6302.2.1.1.6 | ScalaridentControllerSerialNumber | read-only | current | The serial number of this controller |
| 1.3.6.1.4.1.6302.2.1.1.7 | ScalaridentHWerVersion | read-only | current | The Hardware version of the controller. |
| 1.3.6.1.4.1.6302.2.1.1.8 | ScalaridentSiteLocation | read-write | current | The Site Location of the controller. |
| 1.3.6.1.4.1.6302.2.1.1.9 | ScalaridentControllerConfigVer | read-only | current | The Configuration Version for the controller. |
| 1.3.6.1.4.1.6302.2.1.1.10 | ScalaridentMacID | read-only | current | The MAC ID for the controller. |
| 1.3.6.1.4.1.6302.2.1.1.11 | ScalaridentSystemName | read-write | current | The System Name for the controller. |
| 1.3.6.1.4.1.6302.2.1.1.12 | ScalaridentProductModel | read-only | current | The Product Model of the controller. |
| 1.3.6.1.4.1.6302.2.1.1.13 | ScalaridentCriticalAlarms | read-only | current | The Critical Alarm Count for the controller. |
| 1.3.6.1.4.1.6302.2.1.1.14 | ScalaridentPrimaryIp | read-only | current | Primary IP of the controller. |
| 1.3.6.1.4.1.6302.2.1.1.15 | ScalaridentNTPMode | read-only | current | NTP mode of the controller. |
| 1.3.6.1.4.1.6302.2.1.1.17 | ScalaridentSystemDateTime | read-only | current | System date and Time of the controller. |
| 1.3.6.1.4.1.6302.2.1.1.18 | ScalaridentLocalZone | read-only | current | Local Time zone for the controller. |
| 1.3.6.1.4.1.6302.2.1.2 | Nodesystem | |||
| 1.3.6.1.4.1.6302.2.1.2.1 | ScalarsystemStatus | read-only | current | Status of the complete plant (highest alarm). One of (1) unknown - status has not yet been defined (2) normal - there are no activated alarms (3) warning - OA,… |
| 1.3.6.1.4.1.6302.2.1.2.2 | ScalarsystemVoltage | read-only | current | System voltage, stored as mV, including positive or negative sign. The integer 2147483647 represents invalid value. |
| 1.3.6.1.4.1.6302.2.1.2.3 | ScalarsystemCurrent | read-only | current | System current, stored as mA, including positive or negative sign. The integer 2147483647 represents invalid value. |
| 1.3.6.1.4.1.6302.2.1.2.4 | ScalarsystemUsedCapacity | read-only | current | Used capacity, stored as % of the total capacity. The integer 2147483647 represents invalid value. |
| 1.3.6.1.4.1.6302.2.1.2.5 | NodepsBattery | |||
| 1.3.6.1.4.1.6302.2.1.2.5.1 | ScalarpsBatteryVoltage | read-only | current | Battery voltage, stored as mV, including positive or negative sign. The integer 2147483647 represents invalid value. |
| 1.3.6.1.4.1.6302.2.1.2.5.2 | ScalarpsTotalBatteryCurrent | read-only | current | Battery current, stored as mA, including positive or negative sign. The integer 2147483647 represents invalid value. |
| 1.3.6.1.4.1.6302.2.1.2.5.3 | ScalarpsLowestBatteryCapacity | read-only | current | Calculated capacity, stored as % of the total capacity. Lowest available capacity for multiple battery strings. The integer 2147483647 represents invalid value. |
| 1.3.6.1.4.1.6302.2.1.2.5.4 | ScalarpsNominalBatteryCapacity | read-only | current | nominal installed capacity, stored as mAh. The integer 2147483647 represents invalid value. |
| 1.3.6.1.4.1.6302.2.1.2.5.5 | TablepsBatteryTable | not-accessible | current | Battery Table. |
| 1.3.6.1.4.1.6302.2.1.2.5.5.1 | RowpsBatteryEntry | not-accessible | current | Battery Measurement Table Entry. |
| 1.3.6.1.4.1.6302.2.1.2.5.5.1.1 | ColumnpsBatteryIndex | read-only | current | Automatically generated index object. |
| 1.3.6.1.4.1.6302.2.1.2.5.5.1.2 | ColumnpsBatteryCurrent | read-only | current | Battery current in mA. |
| 1.3.6.1.4.1.6302.2.1.2.5.5.1.3 | ColumnpsBatteryName | read-only | current | Battery shunt name. |
| 1.3.6.1.4.1.6302.2.1.2.5.5.1.4 | ColumnpsBatteryCapacity | read-only | current | Battery capacity in Ah. |
| 1.3.6.1.4.1.6302.2.1.2.5.5.1.5 | ColumnpsBatteryCapacityPercent | read-only | current | Battery capacity in percent. |
| 1.3.6.1.4.1.6302.2.1.2.5.5.1.6 | ColumnpsBatteryRatedCapacity | read-write | current | Battery capacity in Ah * 1000. |
| 1.3.6.1.4.1.6302.2.1.2.5.20 | TablepsBmsTable | not-accessible | current | BMS Table. |
| 1.3.6.1.4.1.6302.2.1.2.5.20.1 | RowpsBmsEntry | not-accessible | current | BMS Measurement Table Entry. |
| 1.3.6.1.4.1.6302.2.1.2.5.20.1.1 | ColumnpsBmsIndex | read-only | current | Automatically generated index object. |
| 1.3.6.1.4.1.6302.2.1.2.5.20.1.2 | ColumnpsBmsVoltage | read-only | current | BMS voltage in mV. |
| 1.3.6.1.4.1.6302.2.1.2.5.20.1.3 | ColumnpsBmsCurrent | read-only | current | BMS Current in mA. |
| 1.3.6.1.4.1.6302.2.1.2.5.20.1.4 | ColumnpsBmsRatedCapacity | read-write | current | BMS rated capacity. |
| 1.3.6.1.4.1.6302.2.1.2.5.20.1.5 | ColumnpsBmsStateOfCharge | read-write | current | BMS State Of Charge in percent. |
| 1.3.6.1.4.1.6302.2.1.2.5.20.1.6 | ColumnpsBmsCapacity | read-only | current | BMS capacity in Ah. |
| 1.3.6.1.4.1.6302.2.1.2.5.20.1.7 | ColumnpsBmsAverageTemperature | read-only | current | BMS cell average temperature, stored as 0.001 Celsius degree. The integer 2147483647 represents invalid value. |
| 1.3.6.1.4.1.6302.2.1.2.5.20.1.8 | ColumnpsBmsAmbientTemperature | read-only | current | BMS ambient temperature, stored as 0.001 Celsius degree. The integer 2147483647 represents invalid value.. |
| 1.3.6.1.4.1.6302.2.1.2.6 | NodepsInput | |||
| 1.3.6.1.4.1.6302.2.1.2.6.1 | ScalarpsInputLineAVoltage | read-only | current | The AC line A voltage, stored as mV. The integer 2147483647 represents invalid value. |
| 1.3.6.1.4.1.6302.2.1.2.6.2 | ScalarpsInputLineBVoltage | read-only | current | The AC line B voltage, stored as mV. The integer 2147483647 represents invalid value. |
| 1.3.6.1.4.1.6302.2.1.2.6.3 | ScalarpsInputLineCVoltage | read-only | current | The AC line C voltage, stored as mV. The integer 2147483647 represents invalid value. |
| 1.3.6.1.4.1.6302.2.1.2.6.4 | ScalarpsInputPhaseACurrent | read-only | current | The AC Phase A current, stored as mA. The integer 2147483647 represents invalid value. |
| 1.3.6.1.4.1.6302.2.1.2.6.5 | ScalarpsInputPhaseBCurrent | read-only | current | The AC Phase B current, stored as mA. The integer 2147483647 represents invalid value. |
| 1.3.6.1.4.1.6302.2.1.2.6.6 | ScalarpsInputPhaseCCurrent | read-only | current | The AC Phase C current, stored as mA. The integer 2147483647 represents invalid value. |
| 1.3.6.1.4.1.6302.2.1.2.7 | NodepsTemperature | |||
| 1.3.6.1.4.1.6302.2.1.2.7.1 | ScalarpsTemperature1 | read-only | current | The first route temperature, stored as 0.001 Celsius degree. The integer 2147483647 represents invalid value. |
| 1.3.6.1.4.1.6302.2.1.2.7.2 | ScalarpsTemperature2 | read-only | current | The second route temperature, stored as 0.001 Celsius degree. The integer 2147483647 represents invalid value.. |
| 1.3.6.1.4.1.6302.2.1.2.7.3 | TablepsTemperatureTable | not-accessible | current | Temperature Measurement Table. |
| 1.3.6.1.4.1.6302.2.1.2.7.3.1 | RowpsTemperatureEntry | not-accessible | current | Temperature Measurement Table Entry. |
| 1.3.6.1.4.1.6302.2.1.2.7.3.1.1 | ColumnpsTemperatureIndex | read-only | current | Temperature Probe Number |
| 1.3.6.1.4.1.6302.2.1.2.7.3.1.2 | ColumnpsTemperatureMeasurement | read-only | current | Temperature Value In degrees Centigrade * 1000. |
| 1.3.6.1.4.1.6302.2.1.2.7.3.1.3 | ColumnpsTemperatureName | read-only | current | Configured Temperature Probe Name. |
| 1.3.6.1.4.1.6302.2.1.2.7.3.1.4 | ColumnpsTemperatureType | read-write | current | Temperature Probe Type |
| 1.3.6.1.4.1.6302.2.1.2.7.3.1.5 | ColumnpsTemperatureAlarmStatus | read-only | current | Temperature Probe Alarm Status |
| 1.3.6.1.4.1.6302.2.1.2.7.3.1.6 | ColumnpsTemperatureMeasurementF | read-only | current | Temperature Value In degrees Fahrenheit * 1000. |
| 1.3.6.1.4.1.6302.2.1.2.8 | ScalarpsStatusCommunication | read-only | current | The status of communication with the Power System. interrupt(3) indicates some errors occurred between Power System and agent. |
| 1.3.6.1.4.1.6302.2.1.2.9 | ScalarpsStatusBatteryMode | read-only | current | The status of battery modes, FloatCharging(2), ShortTest(3), BoostChargingForTest(4), ManualTesting(5), PlanTesting(6), ACFailTesting(7), ACFail(8), ManualBoos… |
| 1.3.6.1.4.1.6302.2.1.2.10 | NodepsSMNumber | |||
| 1.3.6.1.4.1.6302.2.1.2.10.1 | ScalarpsSMACNumber | read-only | current | The number of SM AC module. |
| 1.3.6.1.4.1.6302.2.1.2.10.2 | ScalarpsSMBATNumber | read-only | current | The number of SM BAT module. |
| 1.3.6.1.4.1.6302.2.1.2.10.3 | ScalarpsSMIONumber | read-only | current | The number of SM IO module. |
| 1.3.6.1.4.1.6302.2.1.2.11 | NodepsRectifier | |||
| 1.3.6.1.4.1.6302.2.1.2.11.1 | ScalarnumberOfInstalledRectifiers | read-only | current | number of rectifiers, stored as integer. The integer 2147483647 represents invalid value. |
| 1.3.6.1.4.1.6302.2.1.2.11.2 | ScalarnumberOfRectifiersCommunicating | read-only | current | number of rectifiers communicating, stored as integer. The integer 2147483647 represents invalid value. |
| 1.3.6.1.4.1.6302.2.1.2.11.3 | ScalarrectifiersUsedCapacity | read-only | current | Used capacity, stored as % of the total capacity. The integer 2147483647 represents invalid value. |
| 1.3.6.1.4.1.6302.2.1.2.11.4 | TablepsRectifierTable | not-accessible | current | Table holding information about indivual rectifiers. |
| 1.3.6.1.4.1.6302.2.1.2.11.4.1 | RowpsRectifierEntry | not-accessible | current | An entry (conceptual row) in the rectifierInfoTable. |
| 1.3.6.1.4.1.6302.2.1.2.11.4.1.1 | ColumnpsRectifierIndex | read-only | current | Automatically generated index object. |
| 1.3.6.1.4.1.6302.2.1.2.11.4.1.2 | ColumnpsRectifierProductNumber | read-only | current | Rectifier Product Number. |
| 1.3.6.1.4.1.6302.2.1.2.11.4.1.3 | ColumnpsRectifierHWVersion | read-only | current | Rectifier Hardware Revision. |
| 1.3.6.1.4.1.6302.2.1.2.11.4.1.4 | ColumnpsRectifierSWVersion | read-only | current | Rectifier Software Revision. |
| 1.3.6.1.4.1.6302.2.1.2.11.4.1.5 | ColumnpsRectifierSerialNumber | read-only | current | Rectifier Serial Number. |
| 1.3.6.1.4.1.6302.2.1.2.11.4.1.6 | ColumnpsRectifierCurrent | read-only | current | Rectifier Current. |
| 1.3.6.1.4.1.6302.2.1.2.11.4.1.7 | ColumnpsRectifierIdent | read-only | current | Rectifier physical location identifier. |
| 1.3.6.1.4.1.6302.2.1.2.11.4.1.8 | ColumnpsRectifierFail | read-only | current | The type of alarm change. One of (1) activated (2) deactivated |
| 1.3.6.1.4.1.6302.2.1.2.12 | NodepsDistribution | |||
| 1.3.6.1.4.1.6302.2.1.2.12.1 | ScalarpsTotalLoadCurrent | read-only | current | Total Load current, stored as mA. The integer 2147483647 represents invalid value. |
| 1.3.6.1.4.1.6302.2.1.2.12.2 | TablepsDistributionLoadTable | not-accessible | current | Distribution Table. |
| 1.3.6.1.4.1.6302.2.1.2.12.2.1 | RowpsDistributionLoadEntry | not-accessible | current | Distribution Measurement Table Entry. |
| 1.3.6.1.4.1.6302.2.1.2.12.2.1.1 | ColumnpsDistributionLoadIndex | not-accessible | current | Automatically generated index object. |
| 1.3.6.1.4.1.6302.2.1.2.12.2.1.2 | ColumnpsDistributionLoadCurrent | read-only | current | Distribution current in mA. |
| 1.3.6.1.4.1.6302.2.1.2.12.2.1.3 | ColumnpsDistributionLoadName | read-only | current | Distribution name. |
| 1.3.6.1.4.1.6302.2.1.2.12.3 | TablepsDistributionGeneralTable | not-accessible | current | Distribution Table. |
| 1.3.6.1.4.1.6302.2.1.2.12.3.1 | RowpsDistributionGeneralEntry | not-accessible | current | Distribution Measurement Table Entry. |
| 1.3.6.1.4.1.6302.2.1.2.12.3.1.1 | ColumnpsDistributionGeneralIndex | not-accessible | current | Automatically generated index object. |
| 1.3.6.1.4.1.6302.2.1.2.12.3.1.2 | ColumnpsDistributionGeneralCurrent | read-only | current | Distribution current in mA. |
| 1.3.6.1.4.1.6302.2.1.2.12.3.1.3 | ColumnpsDistributionGeneralName | read-only | current | Distribution name. |
| 1.3.6.1.4.1.6302.2.1.2.13 | NodepsConverter | |||
| 1.3.6.1.4.1.6302.2.1.2.13.1 | ScalarnumberOfInstalledConverters | read-only | current | number of converters, stored as integer. The integer 2147483647 represents invalid value. |
| 1.3.6.1.4.1.6302.2.1.2.13.2 | ScalarnumberOfConvertersCommunicating | read-only | current | number of converters communicating, stored as integer. The integer 2147483647 represents invalid value. |
| 1.3.6.1.4.1.6302.2.1.2.13.3 | ScalarconvertersUsedCapacity | read-only | current | Used capacity, stored as % of the total capacity. The integer 2147483647 represents invalid value. |
| 1.3.6.1.4.1.6302.2.1.2.13.4 | ScalarpsConverterVoltage | read-only | current | Converter voltage in mV. The integer 2147483647 represents invalid value. |
| 1.3.6.1.4.1.6302.2.1.2.13.5 | ScalarpsTotalConverterCurrent | read-only | current | Total Converter current in mA. The integer 2147483647 represents invalid value. |
| 1.3.6.1.4.1.6302.2.1.2.13.6 | TablepsConverterTable | not-accessible | current | Table holding information about indivual converters. |
| 1.3.6.1.4.1.6302.2.1.2.13.6.1 | RowpsConverterEntry | not-accessible | current | An entry (conceptual row) in the ConverterInfoTable. |
| 1.3.6.1.4.1.6302.2.1.2.13.6.1.1 | ColumnpsConverterIndex | read-only | current | Automatically generated index object. |
| 1.3.6.1.4.1.6302.2.1.2.13.6.1.2 | ColumnpsConverterProductNumber | read-only | current | Converter Product Number. |
| 1.3.6.1.4.1.6302.2.1.2.13.6.1.3 | ColumnpsConverterHWVersion | read-only | current | Converter Hardware Revision. |
| 1.3.6.1.4.1.6302.2.1.2.13.6.1.4 | ColumnpsConverterSWVersion | read-only | current | Converter Software Revision. |
| 1.3.6.1.4.1.6302.2.1.2.13.6.1.5 | ColumnpsConverterSerialNumber | read-only | current | Converter Serial Number. |
| 1.3.6.1.4.1.6302.2.1.2.13.6.1.6 | ColumnpsConverterCurrent | read-only | current | Converter Current. |
| 1.3.6.1.4.1.6302.2.1.2.13.6.1.7 | ColumnpsConverterIdent | read-only | current | Converter physical location identifier. |
| 1.3.6.1.4.1.6302.2.1.2.13.6.1.8 | ColumnpsConverterFail | read-only | current | The type of alarm change. One of (1) activated (2) deactivated |
| 1.3.6.1.4.1.6302.2.1.2.14 | NodepsControl | |||
| 1.3.6.1.4.1.6302.2.1.2.14.1 | ScalarcontrolBatteryTest | read-write | current | Control battery test, start(1), stop(0). |
| 1.3.6.1.4.1.6302.2.1.2.14.2 | ScalarcontrolRelay8 | read-write | current | Control relay8, close(1), open(0). |
| 1.3.6.1.4.1.6302.2.1.2.14.3 | ScalarcontrolRelay7 | read-write | current | Control relay7, close(1), open(0). |
| 1.3.6.1.4.1.6302.2.1.2.14.4 | ScalarcontrolRelay6 | read-write | current | Control relay6, close(1), open(0). |
| 1.3.6.1.4.1.6302.2.1.2.14.5 | ScalarcontrolRelayTest | read-write | current | Control Relay test, auto(2), manual(1), disabled(0). |
| 1.3.6.1.4.1.6302.2.1.2.15 | TablepsEquipmentSignalTable | not-accessible | current | Table of indexed equipment signal values. |
| 1.3.6.1.4.1.6302.2.1.2.15.1 | RowequipmentSignalTableEntry | not-accessible | current | An entry (conceptual row) in the psEquipment Signal Table. |
| 1.3.6.1.4.1.6302.2.1.2.15.1.1 | ColumnpsEquipmentSignalTableEntryIndex | read-only | current | The unique sequence number of this equipment signal. |
| 1.3.6.1.4.1.6302.2.1.2.15.1.2 | ColumnpsEquipmentSignalValue | read-only | current | Indexed equipment signal value. |
| 1.3.6.1.4.1.6302.2.1.2.16 | NodepsSetting | |||
| 1.3.6.1.4.1.6302.2.1.2.16.1 | ScalarsettingFloatVoltage | read-write | current | Float voltage stored as mV |
| 1.3.6.1.4.1.6302.2.1.2.16.6 | ScalarsettingEQChargeVoltage | read-write | current | Equalize charge voltage stored as mV |
| 1.3.6.1.4.1.6302.2.1.2.16.7 | ScalarsettingBatteryCurrentLimit | read-write | current | Battery charge current limit stored as thousandths of C10 |
| 1.3.6.1.4.1.6302.2.1.2.16.8 | ScalarsettingResetBatteryCapacity | read-write | current | Reset Battery Capacity, Yes(1) |
| 1.3.6.1.4.1.6302.2.1.2.16.9 | ScalarsettingAutoEqualize | read-write | current | Automatic Equalize, disabled(0), enabled(1) |
| 1.3.6.1.4.1.6302.2.1.2.16.10 | ScalarsettingEQStartCurrent | read-write | current | Equalize start current stored as thousandths of C10(0.04 to 0.08) |
| 1.3.6.1.4.1.6302.2.1.2.16.11 | ScalarsettingEQStartCapacity | read-write | current | Auto Equalize start capacity in percent(0 - 99). |
| 1.3.6.1.4.1.6302.2.1.2.16.12 | ScalarsettingEQStopCurrent | read-write | current | Equalize stop current stored as thousandths of C10(0.002 to 0.02) |
| 1.3.6.1.4.1.6302.2.1.2.16.13 | ScalarsettingEQStopDelay | read-write | current | Equalize stop delay time stored as minutes. |
| 1.3.6.1.4.1.6302.2.1.2.16.14 | ScalarsettingMaxEQChargeTime | read-write | current | Maximum Equalize charge time stored as minutes. |
| 1.3.6.1.4.1.6302.2.1.2.16.15 | ScalarsettingSolarMode | read-write | current | Solar mode, Disabled(0), RECT-SOLAR(1), Solar(2) |
| 1.3.6.1.4.1.6302.2.1.2.16.16 | ScalarsettingSolarFloatVoltage | read-write | current | Solar Float voltage stored as mV |
| 1.3.6.1.4.1.6302.2.1.2.16.17 | ScalarsettingSolarEQChargeVoltage | read-write | current | Solar Equalize voltage stored as mV |
| 1.3.6.1.4.1.6302.2.1.2.16.18 | ScalarsettingRectifierFloatVoltage | read-write | current | Rectifier Float voltage stored as mV |
| 1.3.6.1.4.1.6302.2.1.2.16.19 | ScalarsettingRectifierEQChargeVoltage | read-write | current | Rectifier Equalize voltage stored as mV |
| 1.3.6.1.4.1.6302.2.1.2.16.20 | ScalarsettingGeneratorFunction | read-write | current | Automatic Generator Control, Disabled(0), Voltage(1), BatteryCapacity(2) |
| 1.3.6.1.4.1.6302.2.1.2.16.21 | ScalarsettingGeneratorStartVoltage | read-write | current | Generator start voltage stored in mV |
| 1.3.6.1.4.1.6302.2.1.2.16.22 | ScalarsettingGeneratorManualStart | read-write | current | Generator Manual Start, Disabled(0), Active(1) |
| 1.3.6.1.4.1.6302.2.1.2.16.23 | ScalarsettingGeneratorStartCapacity | read-write | current | Battery capacity in % * 1000 |
| 1.3.6.1.4.1.6302.2.1.2.16.24 | ScalarsettingDIforGenerator | read-write | current | Digital input for Generator, None(0), DI2(1), DI3(2), DI4(3), DI5(4), DI6(5), DI7(6) |
| 1.3.6.1.4.1.6302.2.1.2.16.25 | ScalarsettingUtilityPowerPresent | read-write | current | Utility Power is present, No(0), Yes(1) |
| 1.3.6.1.4.1.6302.2.1.2.16.26 | ScalarsettingBatteryCurrentLimitEnable | read-write | current | Battery Current Limit Enable, Disabled(0), Current Mode(1), Voltage Mode(2) |
| 1.3.6.1.4.1.6302.2.1.2.16.27 | ScalarsettingRectifierCurrentLimitEnable | read-write | current | Rectifier Current Limit Enable, Disabled(0), Active(1) |
| 1.3.6.1.4.1.6302.2.1.2.16.28 | ScalarsettingRectifierCurrentLimit | read-write | current | Rectifier current limit stored as mA |
| 1.3.6.1.4.1.6302.2.1.2.16.29 | ScalarsettingCalculateBatteryCurrent | read-write | current | Calculate Battery Current, no(0), yes(1) |
| 1.3.6.1.4.1.6302.2.1.2.16.30 | ScalarsettingTemperatureCompProbe | read-write | current | Temperature Compensation Probe, None(0), Maximum Probe Temperature(1), Average Probe Temperature(2), Minimum Probe Temperature(99), System Temp1(4), System Tem… |
| 1.3.6.1.4.1.6302.2.1.2.16.31 | NodepsRelayAlarmLevel | |||
| 1.3.6.1.4.1.6302.2.1.2.16.31.1 | ScalarsettingGeneratorRunAlarmLevel | read-write | current | Generator Run Alarm Level, None(0), Minor Alarm(1), Major Alarm(2), Critical Alarm(3) |
| 1.3.6.1.4.1.6302.2.1.2.16.31.2 | ScalarsettingGeneratorRunRelay | read-write | current | Relay IDs, None(0), IB2-1 Digital Output 1(1), IB2-1 Digital Output 2(2), IB2-1 Digital Output 3(3), IB2-1 Digital Output 4(4), IB2-1 Digital Output 5(5), IB2-… |
| 1.3.6.1.4.1.6302.2.1.2.16.32 | NodepsECOMode | |||
| 1.3.6.1.4.1.6302.2.1.2.16.32.1 | ScalarsettingECOModeEnable | read-write | current | ECO Mode Enable, Disabled(0), Active(1) |
| 1.3.6.1.4.1.6302.2.1.2.16.32.2 | ScalarsettingECORunMode | read-write | current | ECO Operation Mode, Standard(0), Legacy(1) |
| 1.3.6.1.4.1.6302.2.1.2.16.32.3 | ScalarsettingInhibitECOStop | read-write | current | Inhibit ECO Stop, Disabled(0), Active(1) |
| 1.3.6.1.4.1.6302.2.1.2.16.32.4 | ScalarsettingMinimumOperatingRectifiers | read-write | current | Minimum Operating Rectifiers |
| 1.3.6.1.4.1.6302.2.1.2.16.32.5 | ScalarsettingBestOperatingPoint | read-write | current | Best Operating Point in percent |
| 1.3.6.1.4.1.6302.2.1.2.16.32.6 | ScalarsettingLoadFluctuationRange | read-write | current | Load Fluctuation Range in percent |
| 1.3.6.1.4.1.6302.2.1.2.16.32.7 | ScalarsettingEnergySavingPoint | read-write | current | System Energy Saving Point in percent |
| 1.3.6.1.4.1.6302.2.1.2.16.32.8 | ScalarsettingCyclePeriod | read-write | current | Cycle Period in hours |
| 1.3.6.1.4.1.6302.2.1.2.16.32.9 | ScalarsettingAllRectifiersOnTime | read-write | current | All Rectifiers On Time in minutes |
| 1.3.6.1.4.1.6302.2.1.2.16.32.10 | ScalarsettingTurnOffDelay | read-write | current | Turn Off Delay in minutes |
| 1.3.6.1.4.1.6302.2.1.2.16.32.11 | ScalarsettingResetCycleAlarm | read-write | current | Reset Cycle Alarm, Yes(1) |
| 1.3.6.1.4.1.6302.2.1.2.16.33 | ScalarsettingRectifierDefaultVoltage | read-write | current | Rectifier Default voltage stored in mV |
| 1.3.6.1.4.1.6302.2.1.2.16.34 | ScalarsettingRectifierDefaultVoltage24V | read-write | current | Rectifier Default voltage stored in mV |
| 1.3.6.1.4.1.6302.2.1.2.16.35 | ScalarsettingDefaultVoltageSelect | read-write | current | Select Rectifier default voltage setpoint source, float(0), default(1) |
| 1.3.6.1.4.1.6302.2.1.2.16.36 | ScalarsettingRectifierInputCurrentLimit | read-write | current | Rectifier Input Current Limit stored in mA |
| 1.3.6.1.4.1.6302.2.1.2.16.37 | ScalarsettingConverterDefaultVoltage | read-write | current | Converter Default voltage stored in mV |
| 1.3.6.1.4.1.6302.2.1.2.16.38 | ScalarsettingConverterDefaultVoltage24V | read-write | current | Converter Default voltage stored in mV |
| 1.3.6.1.4.1.6302.2.1.2.19 | NodepsFCUPlus | |||
| 1.3.6.1.4.1.6302.2.1.2.19.1 | TablepsFCUPlusTable | not-accessible | current | Table holding information about indivual FCU Plus equipment. |
| 1.3.6.1.4.1.6302.2.1.2.19.1.1 | RowpsFCUPlusEntry | not-accessible | current | An entry (conceptual row) in the FCUPlus InfoTable. |
| 1.3.6.1.4.1.6302.2.1.2.19.1.1.1 | ColumnpsFCUPlusIndex | read-only | current | Automatically generated index object. |
| 1.3.6.1.4.1.6302.2.1.2.19.1.1.2 | ColumnpsFCUPlusTemperature1 | read-only | current | FCUPlus Temperature1 stored as milli Celsius. |
| 1.3.6.1.4.1.6302.2.1.2.19.1.1.3 | ColumnpsFCUPlusTemperature2 | read-only | current | FCUPlus Temperature2 stored as milli Celsius. |
| 1.3.6.1.4.1.6302.2.1.2.19.1.1.4 | ColumnpsFCUPlusTemperature3 | read-only | current | FCUPlus Temperature3 stored as milli Celsius. |
| 1.3.6.1.4.1.6302.2.1.2.19.1.1.5 | ColumnpsFCUPlusHumidity | read-only | current | FCUPlus Humidity percent. |
| 1.3.6.1.4.1.6302.2.1.2.19.1.1.6 | ColumnpsFCUPlusFanType | read-only | current | FCUPlus fan type, HeatChange(0), ForcedVent(1) |
| 1.3.6.1.4.1.6302.2.1.2.19.1.1.7 | ColumnpsFCUPlusWithHeater | read-only | current | FCUPlus with heater, no(0), yes(1) |
| 1.3.6.1.4.1.6302.2.1.2.19.1.1.8 | ColumnpsFCUPlusFanGroup1State | read-only | current | FCUPlus fan group 1 state, stop(0), start(1) |
| 1.3.6.1.4.1.6302.2.1.2.19.1.1.9 | ColumnpsFCUPlusFanGroup2State | read-only | current | FCUPlus fan group 2 state, stop(0), start(1) |
| 1.3.6.1.4.1.6302.2.1.2.19.1.1.10 | ColumnpsFCUPlusFanGroup3State | read-only | current | FCUPlus fan group 3 state, stop(0), start(1) |
| 1.3.6.1.4.1.6302.2.1.2.19.1.1.11 | ColumnpsFCUPlusHeater1State | read-only | current | FCUPlus heater 1 state, stop(0), start(1) |
| 1.3.6.1.4.1.6302.2.1.2.19.1.1.12 | ColumnpsFCUPlusHeater2State | read-only | current | FCUPlus heater 2 state, stop(0), start(1) |
| 1.3.6.1.4.1.6302.2.1.2.19.1.1.13 | ColumnpsFCUPlusRunningMode | read-only | current | FCUPlus running mode, Normal(0), Test(1) |
| 1.3.6.1.4.1.6302.2.1.2.21 | NodepsInverter | |||
| 1.3.6.1.4.1.6302.2.1.2.21.1 | ScalarnumberOfInstalledInverters | read-only | current | number of Inverters, stored as integer. The integer 2147483647 represents invalid value. |
| 1.3.6.1.4.1.6302.2.1.2.21.2 | ScalarnumberOfInvertersCommunicating | read-only | current | number of rectifiers communicating, stored as integer. The integer 2147483647 represents invalid value. |
| 1.3.6.1.4.1.6302.2.1.2.21.3 | ScalarinvertersUsedCapacity | read-only | current | Used capacity, stored as % of the total capacity. The integer 2147483647 represents invalid value. |
| 1.3.6.1.4.1.6302.2.1.2.21.4 | TablepsInverterTable | not-accessible | current | Table holding information about indivual rectifiers. |
| 1.3.6.1.4.1.6302.2.1.2.21.4.1 | RowpsInverterEntry | not-accessible | current | An entry (conceptual row) in the rectifierInfoTable. |
| 1.3.6.1.4.1.6302.2.1.2.21.4.1.1 | ColumnpsInverterIndex | read-only | current | Automatically generated index object. |
| 1.3.6.1.4.1.6302.2.1.2.21.4.1.2 | ColumnpsInverterProductNumber | read-only | current | Inverter Product Number. |
| 1.3.6.1.4.1.6302.2.1.2.21.4.1.3 | ColumnpsInverterHWVersion | read-only | current | Inverter Hardware Revision. |
| 1.3.6.1.4.1.6302.2.1.2.21.4.1.4 | ColumnpsInverterSWVersion | read-only | current | Inverter Software Revision. |
| 1.3.6.1.4.1.6302.2.1.2.21.4.1.5 | ColumnpsInverterSerialNumber | read-only | current | Inverter Serial Number. |
| 1.3.6.1.4.1.6302.2.1.2.21.4.1.6 | ColumnpsInverterVoltage | read-only | current | Inverter Output Voltage. |
| 1.3.6.1.4.1.6302.2.1.2.21.4.1.7 | ColumnpsInverterCurrent | read-only | current | Inverter Output Current. |
| 1.3.6.1.4.1.6302.2.1.2.21.4.1.8 | ColumnpsInverterIdent | read-only | current | Inverter physical location identifier. |
| 1.3.6.1.4.1.6302.2.1.2.21.4.1.9 | ColumnpsInverterFrequency | read-only | current | Inverter Output Frequency |
| 1.3.6.1.4.1.6302.2.1.2.25 | NodepsSolar | |||
| 1.3.6.1.4.1.6302.2.1.2.25.1 | ScalarnumberOfInstalledSolar | read-only | current | number of Solar converters, stored as integer. The integer 2147483647 represents invalid value. |
| 1.3.6.1.4.1.6302.2.1.2.25.2 | ScalarnumberOfSolarCommunicating | read-only | current | number of Solar converters communicating, stored as integer. The integer 2147483647 represents invalid value. |
| 1.3.6.1.4.1.6302.2.1.2.25.3 | ScalarsolarsUsedCapacity | read-only | current | Used capacity, stored as % of the total capacity. The integer 2147483647 represents invalid value. |
| 1.3.6.1.4.1.6302.2.1.2.25.4 | ScalarpsSolarTotalCurrent | read-only | current | Solar Converter Total output current in mA. The integer 2147483647 represents invalid value. |
| 1.3.6.1.4.1.6302.2.1.2.25.5 | ScalarpsSolarTotalPower | read-only | current | Solar Converter Total Output Power in W * 1000. |
| 1.3.6.1.4.1.6302.2.1.2.25.6 | ScalarpsSolarTotalInputCurrent | read-only | current | Solar Converter Total input current in mA. The integer 2147483647 represents invalid value. |
| 1.3.6.1.4.1.6302.2.1.2.25.7 | ScalarpsSolarTotalInputPower | read-only | current | Solar Converter Total input Power in kW * 1000. |
| 1.3.6.1.4.1.6302.2.1.2.25.8 | ScalarpsSolarMode | read-write | current | Solar mode, Disabled(0), RECT-SOLAR(1), Solar(2) |
| 1.3.6.1.4.1.6302.2.1.2.25.9 | ScalarpsSolarRunningWay | read-write | current | Solar mode, Disabled(0), RECT-SOLAR(1), Solar(2) |
| 1.3.6.1.4.1.6302.2.1.2.25.10 | TablepsSolarTable | not-accessible | current | Table holding information about indivual solar converters. |
| 1.3.6.1.4.1.6302.2.1.2.25.10.1 | RowpsSolarEntry | not-accessible | current | An entry (conceptual row) in the solar converter InfoTable. |
| 1.3.6.1.4.1.6302.2.1.2.25.10.1.1 | ColumnpsSolarIndex | read-only | current | Automatically generated index object. |
| 1.3.6.1.4.1.6302.2.1.2.25.10.1.2 | ColumnpsSolarProductNumber | read-only | current | Solar Converter Product Number. |
| 1.3.6.1.4.1.6302.2.1.2.25.10.1.3 | ColumnpsSolarHWVersion | read-only | current | Solar Converter Hardware Revision. |
| 1.3.6.1.4.1.6302.2.1.2.25.10.1.4 | ColumnpsSolarSWVersion | read-only | current | Solar Converter Software Revision. |
| 1.3.6.1.4.1.6302.2.1.2.25.10.1.5 | ColumnpsSolarSerialNumber | read-only | current | Solar Converter Serial Number. |
| 1.3.6.1.4.1.6302.2.1.2.25.10.1.6 | ColumnpsSolarIdent | read-only | current | Solar Converter physical location identifier. |
| 1.3.6.1.4.1.6302.2.1.2.25.10.1.7 | ColumnpsSolarRatedIoutAtMaxVout | read-only | current | Solar converter rated Iout milliamps at Max Vout. |
| 1.3.6.1.4.1.6302.2.1.2.25.10.1.8 | ColumnpsSolarInputVoltage | read-only | current | Solar converter rated input voltage in millivolts. |
| 1.3.6.1.4.1.6302.2.1.2.25.10.1.9 | ColumnpsSolarInputCurrent | read-only | current | Solar converter input current in milliamps. |
| 1.3.6.1.4.1.6302.2.1.2.25.10.1.10 | ColumnpsSolarInputPower | read-only | current | Solar converter input power in W. |
| 1.3.6.1.4.1.6302.2.1.2.25.10.1.11 | ColumnpsSolarOutputVoltage | read-only | current | Solar converter output voltage in millivolts. |
| 1.3.6.1.4.1.6302.2.1.2.25.10.1.12 | ColumnpsSolarOutputCurrent | read-only | current | Solar converter output current in milliamps. |
| 1.3.6.1.4.1.6302.2.1.2.25.10.1.13 | ColumnpsSolarOutputPower | read-only | current | Solar converter output power in W. |
| 1.3.6.1.4.1.6302.2.1.2.25.10.1.14 | ColumnpsSolarUsedCapacity | read-only | current | Solar converter used capacity in percent. |
| 1.3.6.1.4.1.6302.2.1.2.25.10.1.15 | ColumnpsSolarTotalRunningTime | read-only | current | Solar converter total running time in hours * 1000. |
| 1.3.6.1.4.1.6302.2.1.2.25.10.1.16 | ColumnpsSolarFail | read-only | current | The type of alarm change. One of (1) activated (2) deactivated |
| 1.3.6.1.4.1.6302.2.1.3 | ScalaralarmLastTrapNo | read-only | current | The sequence number of last submitted alarm trap, also last row in alarmTrapTable. |
| 1.3.6.1.4.1.6302.2.1.4 | TablealarmActiveAlarmTable | not-accessible | current | Table holding information about the currently active alarms. |
| 1.3.6.1.4.1.6302.2.1.4.1 | RowactiveAlarmEntry | not-accessible | current | An entry (conceptual row) in the alarmTrapTable. |
| 1.3.6.1.4.1.6302.2.1.4.1.1 | ColumnalarmIndex | read-only | current | The unique sequence number of this alarm trap. |
| 1.3.6.1.4.1.6302.2.1.4.1.2 | ColumnalarmTime | read-only | current | Date and time when event occured (local time), including timezone if supported by controller. |
| 1.3.6.1.4.1.6302.2.1.4.1.3 | ColumnalarmStatusChange | read-only | current | The type of alarm change. One of (1) activated (2) deactivated |
| 1.3.6.1.4.1.6302.2.1.4.1.4 | ColumnalarmSeverity | read-only | current | The severity of the alarm. One of (3) warning - OA, lowest level of alarm severity (4) minor - A3 (5) major - MA (6) critical - CA, highest level of alarm seve… |
| 1.3.6.1.4.1.6302.2.1.4.1.5 | ColumnalarmDescription | read-only | current | Free-text description of alarm. |
| 1.3.6.1.4.1.6302.2.1.4.1.6 | ColumnalarmType | read-only | current | Alarm type, i.e. an integer specifying the type of alarm. |
| 1.3.6.1.4.1.6302.2.1.5 | NodepowerEvents | |||
| 1.3.6.1.4.1.6302.2.1.5.1 | NotificationalarmTrap | current | An alarm trap is sent when an alarm occurs (activated) or returns to normal state (deactivated). Alarm traps are logged in alarmTrapTable. Variables in this tr… | |
| 1.3.6.1.4.1.6302.2.1.5.2 | NotificationalarmActiveTrap | current | An alarm trap is sent when an alarm occurs (activated) Variables in this trap * alarmTime - Date and time when event occured (local time), including timezone i… | |
| 1.3.6.1.4.1.6302.2.1.5.3 | NotificationalarmCeaseTrap | current | An alarm trap is sent when an alarm returns to normal state (clear, deactivated). Variables in this trap: * alarmTime - Date and time when event occured (local… |
Type Definitions
| Name | Syntax | Status | Description |
|---|---|---|---|
| Status | INTEGER { unknown(1), normal(2), warning(3), minor(4), major(5), critical(6), unmanaged(7), restricted(8), testing(9), disabled(10) } | current | This integer value represents the operational or administrative status of the system. Also used as alarm severity. Depending on situation there may be limits on allowed values. Operational values: (1) unknown - status h… |
| StatusChange | INTEGER { activated(1), deactivated(2) } | current | Indicates 'activated' (1) or 'deactivated' (2) alarm events. |