NETSURE-NCU-MIB

247 objects
Vertiv Tech Co. Ltd Power MIB, revision S.
Imported Objects
SNMPv2-SMICounter32 enterprises Integer32 MODULE-IDENTITY NOTIFICATION-TYPE OBJECT-TYPE
SNMPv2-TCDateAndTime DisplayString TEXTUAL-CONVENTION
OIDNameAccessStatusDescription
1.3.6.1.4.1.6302Nodeees
1.3.6.1.4.1.6302.2Nodeglobal
1.3.6.1.4.1.6302.2.1IdentitypowerMIBVertiv Tech Co. Ltd Power MIB, revision S.
1.3.6.1.4.1.6302.2.1.1Nodeident
1.3.6.1.4.1.6302.2.1.1.1ScalaridentManufacturerread-onlycurrentThe name of the equipment manufacturer.
1.3.6.1.4.1.6302.2.1.1.2ScalaridentModelread-onlycurrentThe manufacturers model designation of the power system.
1.3.6.1.4.1.6302.2.1.1.3ScalaridentControllerFirmwareVersionread-onlycurrentThe firmware (software) version of the controller.
1.3.6.1.4.1.6302.2.1.1.4ScalaridentNameread-writecurrentThe name of the power plant. This object should be set by the administrator.
1.3.6.1.4.1.6302.2.1.1.5ScalaridentSNMPCfgVerread-onlycurrentSNMP Config Version.
1.3.6.1.4.1.6302.2.1.1.6ScalaridentControllerSerialNumberread-onlycurrentThe serial number of this controller
1.3.6.1.4.1.6302.2.1.1.7ScalaridentHWerVersionread-onlycurrentThe Hardware version of the controller.
1.3.6.1.4.1.6302.2.1.1.8ScalaridentSiteLocationread-writecurrentThe Site Location of the controller.
1.3.6.1.4.1.6302.2.1.1.9ScalaridentControllerConfigVerread-onlycurrentThe Configuration Version for the controller.
1.3.6.1.4.1.6302.2.1.1.10ScalaridentMacIDread-onlycurrentThe MAC ID for the controller.
1.3.6.1.4.1.6302.2.1.1.11ScalaridentSystemNameread-writecurrentThe System Name for the controller.
1.3.6.1.4.1.6302.2.1.1.12ScalaridentProductModelread-onlycurrentThe Product Model of the controller.
1.3.6.1.4.1.6302.2.1.1.13ScalaridentCriticalAlarmsread-onlycurrentThe Critical Alarm Count for the controller.
1.3.6.1.4.1.6302.2.1.1.14ScalaridentPrimaryIpread-onlycurrentPrimary IP of the controller.
1.3.6.1.4.1.6302.2.1.1.15ScalaridentNTPModeread-onlycurrentNTP mode of the controller.
1.3.6.1.4.1.6302.2.1.1.17ScalaridentSystemDateTimeread-onlycurrentSystem date and Time of the controller.
1.3.6.1.4.1.6302.2.1.1.18ScalaridentLocalZoneread-onlycurrentLocal Time zone for the controller.
1.3.6.1.4.1.6302.2.1.2Nodesystem
1.3.6.1.4.1.6302.2.1.2.1ScalarsystemStatusread-onlycurrentStatus of the complete plant (highest alarm). One of (1) unknown - status has not yet been defined (2) normal - there are no activated alarms (3) warning - OA,…
1.3.6.1.4.1.6302.2.1.2.2ScalarsystemVoltageread-onlycurrentSystem voltage, stored as mV, including positive or negative sign. The integer 2147483647 represents invalid value.
1.3.6.1.4.1.6302.2.1.2.3ScalarsystemCurrentread-onlycurrentSystem current, stored as mA, including positive or negative sign. The integer 2147483647 represents invalid value.
1.3.6.1.4.1.6302.2.1.2.4ScalarsystemUsedCapacityread-onlycurrentUsed capacity, stored as % of the total capacity. The integer 2147483647 represents invalid value.
1.3.6.1.4.1.6302.2.1.2.5NodepsBattery
1.3.6.1.4.1.6302.2.1.2.5.1ScalarpsBatteryVoltageread-onlycurrentBattery voltage, stored as mV, including positive or negative sign. The integer 2147483647 represents invalid value.
1.3.6.1.4.1.6302.2.1.2.5.2ScalarpsTotalBatteryCurrentread-onlycurrentBattery current, stored as mA, including positive or negative sign. The integer 2147483647 represents invalid value.
1.3.6.1.4.1.6302.2.1.2.5.3ScalarpsLowestBatteryCapacityread-onlycurrentCalculated capacity, stored as % of the total capacity. Lowest available capacity for multiple battery strings. The integer 2147483647 represents invalid value.
1.3.6.1.4.1.6302.2.1.2.5.4ScalarpsNominalBatteryCapacityread-onlycurrentnominal installed capacity, stored as mAh. The integer 2147483647 represents invalid value.
1.3.6.1.4.1.6302.2.1.2.5.5TablepsBatteryTablenot-accessiblecurrentBattery Table.
1.3.6.1.4.1.6302.2.1.2.5.5.1RowpsBatteryEntrynot-accessiblecurrentBattery Measurement Table Entry.
1.3.6.1.4.1.6302.2.1.2.5.5.1.1ColumnpsBatteryIndexread-onlycurrentAutomatically generated index object.
1.3.6.1.4.1.6302.2.1.2.5.5.1.2ColumnpsBatteryCurrentread-onlycurrentBattery current in mA.
1.3.6.1.4.1.6302.2.1.2.5.5.1.3ColumnpsBatteryNameread-onlycurrentBattery shunt name.
1.3.6.1.4.1.6302.2.1.2.5.5.1.4ColumnpsBatteryCapacityread-onlycurrentBattery capacity in Ah.
1.3.6.1.4.1.6302.2.1.2.5.5.1.5ColumnpsBatteryCapacityPercentread-onlycurrentBattery capacity in percent.
1.3.6.1.4.1.6302.2.1.2.5.5.1.6ColumnpsBatteryRatedCapacityread-writecurrentBattery capacity in Ah * 1000.
1.3.6.1.4.1.6302.2.1.2.5.20TablepsBmsTablenot-accessiblecurrentBMS Table.
1.3.6.1.4.1.6302.2.1.2.5.20.1RowpsBmsEntrynot-accessiblecurrentBMS Measurement Table Entry.
1.3.6.1.4.1.6302.2.1.2.5.20.1.1ColumnpsBmsIndexread-onlycurrentAutomatically generated index object.
1.3.6.1.4.1.6302.2.1.2.5.20.1.2ColumnpsBmsVoltageread-onlycurrentBMS voltage in mV.
1.3.6.1.4.1.6302.2.1.2.5.20.1.3ColumnpsBmsCurrentread-onlycurrentBMS Current in mA.
1.3.6.1.4.1.6302.2.1.2.5.20.1.4ColumnpsBmsRatedCapacityread-writecurrentBMS rated capacity.
1.3.6.1.4.1.6302.2.1.2.5.20.1.5ColumnpsBmsStateOfChargeread-writecurrentBMS State Of Charge in percent.
1.3.6.1.4.1.6302.2.1.2.5.20.1.6ColumnpsBmsCapacityread-onlycurrentBMS capacity in Ah.
1.3.6.1.4.1.6302.2.1.2.5.20.1.7ColumnpsBmsAverageTemperatureread-onlycurrentBMS cell average temperature, stored as 0.001 Celsius degree. The integer 2147483647 represents invalid value.
1.3.6.1.4.1.6302.2.1.2.5.20.1.8ColumnpsBmsAmbientTemperatureread-onlycurrentBMS ambient temperature, stored as 0.001 Celsius degree. The integer 2147483647 represents invalid value..
1.3.6.1.4.1.6302.2.1.2.6NodepsInput
1.3.6.1.4.1.6302.2.1.2.6.1ScalarpsInputLineAVoltageread-onlycurrentThe AC line A voltage, stored as mV. The integer 2147483647 represents invalid value.
1.3.6.1.4.1.6302.2.1.2.6.2ScalarpsInputLineBVoltageread-onlycurrentThe AC line B voltage, stored as mV. The integer 2147483647 represents invalid value.
1.3.6.1.4.1.6302.2.1.2.6.3ScalarpsInputLineCVoltageread-onlycurrentThe AC line C voltage, stored as mV. The integer 2147483647 represents invalid value.
1.3.6.1.4.1.6302.2.1.2.6.4ScalarpsInputPhaseACurrentread-onlycurrentThe AC Phase A current, stored as mA. The integer 2147483647 represents invalid value.
1.3.6.1.4.1.6302.2.1.2.6.5ScalarpsInputPhaseBCurrentread-onlycurrentThe AC Phase B current, stored as mA. The integer 2147483647 represents invalid value.
1.3.6.1.4.1.6302.2.1.2.6.6ScalarpsInputPhaseCCurrentread-onlycurrentThe AC Phase C current, stored as mA. The integer 2147483647 represents invalid value.
1.3.6.1.4.1.6302.2.1.2.7NodepsTemperature
1.3.6.1.4.1.6302.2.1.2.7.1ScalarpsTemperature1read-onlycurrentThe first route temperature, stored as 0.001 Celsius degree. The integer 2147483647 represents invalid value.
1.3.6.1.4.1.6302.2.1.2.7.2ScalarpsTemperature2read-onlycurrentThe second route temperature, stored as 0.001 Celsius degree. The integer 2147483647 represents invalid value..
1.3.6.1.4.1.6302.2.1.2.7.3TablepsTemperatureTablenot-accessiblecurrentTemperature Measurement Table.
1.3.6.1.4.1.6302.2.1.2.7.3.1RowpsTemperatureEntrynot-accessiblecurrentTemperature Measurement Table Entry.
1.3.6.1.4.1.6302.2.1.2.7.3.1.1ColumnpsTemperatureIndexread-onlycurrentTemperature Probe Number
1.3.6.1.4.1.6302.2.1.2.7.3.1.2ColumnpsTemperatureMeasurementread-onlycurrentTemperature Value In degrees Centigrade * 1000.
1.3.6.1.4.1.6302.2.1.2.7.3.1.3ColumnpsTemperatureNameread-onlycurrentConfigured Temperature Probe Name.
1.3.6.1.4.1.6302.2.1.2.7.3.1.4ColumnpsTemperatureTyperead-writecurrentTemperature Probe Type
1.3.6.1.4.1.6302.2.1.2.7.3.1.5ColumnpsTemperatureAlarmStatusread-onlycurrentTemperature Probe Alarm Status
1.3.6.1.4.1.6302.2.1.2.7.3.1.6ColumnpsTemperatureMeasurementFread-onlycurrentTemperature Value In degrees Fahrenheit * 1000.
1.3.6.1.4.1.6302.2.1.2.8ScalarpsStatusCommunicationread-onlycurrentThe status of communication with the Power System. interrupt(3) indicates some errors occurred between Power System and agent.
1.3.6.1.4.1.6302.2.1.2.9ScalarpsStatusBatteryModeread-onlycurrentThe status of battery modes, FloatCharging(2), ShortTest(3), BoostChargingForTest(4), ManualTesting(5), PlanTesting(6), ACFailTesting(7), ACFail(8), ManualBoos…
1.3.6.1.4.1.6302.2.1.2.10NodepsSMNumber
1.3.6.1.4.1.6302.2.1.2.10.1ScalarpsSMACNumberread-onlycurrentThe number of SM AC module.
1.3.6.1.4.1.6302.2.1.2.10.2ScalarpsSMBATNumberread-onlycurrentThe number of SM BAT module.
1.3.6.1.4.1.6302.2.1.2.10.3ScalarpsSMIONumberread-onlycurrentThe number of SM IO module.
1.3.6.1.4.1.6302.2.1.2.11NodepsRectifier
1.3.6.1.4.1.6302.2.1.2.11.1ScalarnumberOfInstalledRectifiersread-onlycurrentnumber of rectifiers, stored as integer. The integer 2147483647 represents invalid value.
1.3.6.1.4.1.6302.2.1.2.11.2ScalarnumberOfRectifiersCommunicatingread-onlycurrentnumber of rectifiers communicating, stored as integer. The integer 2147483647 represents invalid value.
1.3.6.1.4.1.6302.2.1.2.11.3ScalarrectifiersUsedCapacityread-onlycurrentUsed capacity, stored as % of the total capacity. The integer 2147483647 represents invalid value.
1.3.6.1.4.1.6302.2.1.2.11.4TablepsRectifierTablenot-accessiblecurrentTable holding information about indivual rectifiers.
1.3.6.1.4.1.6302.2.1.2.11.4.1RowpsRectifierEntrynot-accessiblecurrentAn entry (conceptual row) in the rectifierInfoTable.
1.3.6.1.4.1.6302.2.1.2.11.4.1.1ColumnpsRectifierIndexread-onlycurrentAutomatically generated index object.
1.3.6.1.4.1.6302.2.1.2.11.4.1.2ColumnpsRectifierProductNumberread-onlycurrentRectifier Product Number.
1.3.6.1.4.1.6302.2.1.2.11.4.1.3ColumnpsRectifierHWVersionread-onlycurrentRectifier Hardware Revision.
1.3.6.1.4.1.6302.2.1.2.11.4.1.4ColumnpsRectifierSWVersionread-onlycurrentRectifier Software Revision.
1.3.6.1.4.1.6302.2.1.2.11.4.1.5ColumnpsRectifierSerialNumberread-onlycurrentRectifier Serial Number.
1.3.6.1.4.1.6302.2.1.2.11.4.1.6ColumnpsRectifierCurrentread-onlycurrentRectifier Current.
1.3.6.1.4.1.6302.2.1.2.11.4.1.7ColumnpsRectifierIdentread-onlycurrentRectifier physical location identifier.
1.3.6.1.4.1.6302.2.1.2.11.4.1.8ColumnpsRectifierFailread-onlycurrentThe type of alarm change. One of (1) activated (2) deactivated
1.3.6.1.4.1.6302.2.1.2.12NodepsDistribution
1.3.6.1.4.1.6302.2.1.2.12.1ScalarpsTotalLoadCurrentread-onlycurrentTotal Load current, stored as mA. The integer 2147483647 represents invalid value.
1.3.6.1.4.1.6302.2.1.2.12.2TablepsDistributionLoadTablenot-accessiblecurrentDistribution Table.
1.3.6.1.4.1.6302.2.1.2.12.2.1RowpsDistributionLoadEntrynot-accessiblecurrentDistribution Measurement Table Entry.
1.3.6.1.4.1.6302.2.1.2.12.2.1.1ColumnpsDistributionLoadIndexnot-accessiblecurrentAutomatically generated index object.
1.3.6.1.4.1.6302.2.1.2.12.2.1.2ColumnpsDistributionLoadCurrentread-onlycurrentDistribution current in mA.
1.3.6.1.4.1.6302.2.1.2.12.2.1.3ColumnpsDistributionLoadNameread-onlycurrentDistribution name.
1.3.6.1.4.1.6302.2.1.2.12.3TablepsDistributionGeneralTablenot-accessiblecurrentDistribution Table.
1.3.6.1.4.1.6302.2.1.2.12.3.1RowpsDistributionGeneralEntrynot-accessiblecurrentDistribution Measurement Table Entry.
1.3.6.1.4.1.6302.2.1.2.12.3.1.1ColumnpsDistributionGeneralIndexnot-accessiblecurrentAutomatically generated index object.
1.3.6.1.4.1.6302.2.1.2.12.3.1.2ColumnpsDistributionGeneralCurrentread-onlycurrentDistribution current in mA.
1.3.6.1.4.1.6302.2.1.2.12.3.1.3ColumnpsDistributionGeneralNameread-onlycurrentDistribution name.
1.3.6.1.4.1.6302.2.1.2.13NodepsConverter
1.3.6.1.4.1.6302.2.1.2.13.1ScalarnumberOfInstalledConvertersread-onlycurrentnumber of converters, stored as integer. The integer 2147483647 represents invalid value.
1.3.6.1.4.1.6302.2.1.2.13.2ScalarnumberOfConvertersCommunicatingread-onlycurrentnumber of converters communicating, stored as integer. The integer 2147483647 represents invalid value.
1.3.6.1.4.1.6302.2.1.2.13.3ScalarconvertersUsedCapacityread-onlycurrentUsed capacity, stored as % of the total capacity. The integer 2147483647 represents invalid value.
1.3.6.1.4.1.6302.2.1.2.13.4ScalarpsConverterVoltageread-onlycurrentConverter voltage in mV. The integer 2147483647 represents invalid value.
1.3.6.1.4.1.6302.2.1.2.13.5ScalarpsTotalConverterCurrentread-onlycurrentTotal Converter current in mA. The integer 2147483647 represents invalid value.
1.3.6.1.4.1.6302.2.1.2.13.6TablepsConverterTablenot-accessiblecurrentTable holding information about indivual converters.
1.3.6.1.4.1.6302.2.1.2.13.6.1RowpsConverterEntrynot-accessiblecurrentAn entry (conceptual row) in the ConverterInfoTable.
1.3.6.1.4.1.6302.2.1.2.13.6.1.1ColumnpsConverterIndexread-onlycurrentAutomatically generated index object.
1.3.6.1.4.1.6302.2.1.2.13.6.1.2ColumnpsConverterProductNumberread-onlycurrentConverter Product Number.
1.3.6.1.4.1.6302.2.1.2.13.6.1.3ColumnpsConverterHWVersionread-onlycurrentConverter Hardware Revision.
1.3.6.1.4.1.6302.2.1.2.13.6.1.4ColumnpsConverterSWVersionread-onlycurrentConverter Software Revision.
1.3.6.1.4.1.6302.2.1.2.13.6.1.5ColumnpsConverterSerialNumberread-onlycurrentConverter Serial Number.
1.3.6.1.4.1.6302.2.1.2.13.6.1.6ColumnpsConverterCurrentread-onlycurrentConverter Current.
1.3.6.1.4.1.6302.2.1.2.13.6.1.7ColumnpsConverterIdentread-onlycurrentConverter physical location identifier.
1.3.6.1.4.1.6302.2.1.2.13.6.1.8ColumnpsConverterFailread-onlycurrentThe type of alarm change. One of (1) activated (2) deactivated
1.3.6.1.4.1.6302.2.1.2.14NodepsControl
1.3.6.1.4.1.6302.2.1.2.14.1ScalarcontrolBatteryTestread-writecurrentControl battery test, start(1), stop(0).
1.3.6.1.4.1.6302.2.1.2.14.2ScalarcontrolRelay8read-writecurrentControl relay8, close(1), open(0).
1.3.6.1.4.1.6302.2.1.2.14.3ScalarcontrolRelay7read-writecurrentControl relay7, close(1), open(0).
1.3.6.1.4.1.6302.2.1.2.14.4ScalarcontrolRelay6read-writecurrentControl relay6, close(1), open(0).
1.3.6.1.4.1.6302.2.1.2.14.5ScalarcontrolRelayTestread-writecurrentControl Relay test, auto(2), manual(1), disabled(0).
1.3.6.1.4.1.6302.2.1.2.15TablepsEquipmentSignalTablenot-accessiblecurrentTable of indexed equipment signal values.
1.3.6.1.4.1.6302.2.1.2.15.1RowequipmentSignalTableEntrynot-accessiblecurrentAn entry (conceptual row) in the psEquipment Signal Table.
1.3.6.1.4.1.6302.2.1.2.15.1.1ColumnpsEquipmentSignalTableEntryIndexread-onlycurrentThe unique sequence number of this equipment signal.
1.3.6.1.4.1.6302.2.1.2.15.1.2ColumnpsEquipmentSignalValueread-onlycurrentIndexed equipment signal value.
1.3.6.1.4.1.6302.2.1.2.16NodepsSetting
1.3.6.1.4.1.6302.2.1.2.16.1ScalarsettingFloatVoltageread-writecurrentFloat voltage stored as mV
1.3.6.1.4.1.6302.2.1.2.16.6ScalarsettingEQChargeVoltageread-writecurrentEqualize charge voltage stored as mV
1.3.6.1.4.1.6302.2.1.2.16.7ScalarsettingBatteryCurrentLimitread-writecurrentBattery charge current limit stored as thousandths of C10
1.3.6.1.4.1.6302.2.1.2.16.8ScalarsettingResetBatteryCapacityread-writecurrentReset Battery Capacity, Yes(1)
1.3.6.1.4.1.6302.2.1.2.16.9ScalarsettingAutoEqualizeread-writecurrentAutomatic Equalize, disabled(0), enabled(1)
1.3.6.1.4.1.6302.2.1.2.16.10ScalarsettingEQStartCurrentread-writecurrentEqualize start current stored as thousandths of C10(0.04 to 0.08)
1.3.6.1.4.1.6302.2.1.2.16.11ScalarsettingEQStartCapacityread-writecurrentAuto Equalize start capacity in percent(0 - 99).
1.3.6.1.4.1.6302.2.1.2.16.12ScalarsettingEQStopCurrentread-writecurrentEqualize stop current stored as thousandths of C10(0.002 to 0.02)
1.3.6.1.4.1.6302.2.1.2.16.13ScalarsettingEQStopDelayread-writecurrentEqualize stop delay time stored as minutes.
1.3.6.1.4.1.6302.2.1.2.16.14ScalarsettingMaxEQChargeTimeread-writecurrentMaximum Equalize charge time stored as minutes.
1.3.6.1.4.1.6302.2.1.2.16.15ScalarsettingSolarModeread-writecurrentSolar mode, Disabled(0), RECT-SOLAR(1), Solar(2)
1.3.6.1.4.1.6302.2.1.2.16.16ScalarsettingSolarFloatVoltageread-writecurrentSolar Float voltage stored as mV
1.3.6.1.4.1.6302.2.1.2.16.17ScalarsettingSolarEQChargeVoltageread-writecurrentSolar Equalize voltage stored as mV
1.3.6.1.4.1.6302.2.1.2.16.18ScalarsettingRectifierFloatVoltageread-writecurrentRectifier Float voltage stored as mV
1.3.6.1.4.1.6302.2.1.2.16.19ScalarsettingRectifierEQChargeVoltageread-writecurrentRectifier Equalize voltage stored as mV
1.3.6.1.4.1.6302.2.1.2.16.20ScalarsettingGeneratorFunctionread-writecurrentAutomatic Generator Control, Disabled(0), Voltage(1), BatteryCapacity(2)
1.3.6.1.4.1.6302.2.1.2.16.21ScalarsettingGeneratorStartVoltageread-writecurrentGenerator start voltage stored in mV
1.3.6.1.4.1.6302.2.1.2.16.22ScalarsettingGeneratorManualStartread-writecurrentGenerator Manual Start, Disabled(0), Active(1)
1.3.6.1.4.1.6302.2.1.2.16.23ScalarsettingGeneratorStartCapacityread-writecurrentBattery capacity in % * 1000
1.3.6.1.4.1.6302.2.1.2.16.24ScalarsettingDIforGeneratorread-writecurrentDigital input for Generator, None(0), DI2(1), DI3(2), DI4(3), DI5(4), DI6(5), DI7(6)
1.3.6.1.4.1.6302.2.1.2.16.25ScalarsettingUtilityPowerPresentread-writecurrentUtility Power is present, No(0), Yes(1)
1.3.6.1.4.1.6302.2.1.2.16.26ScalarsettingBatteryCurrentLimitEnableread-writecurrentBattery Current Limit Enable, Disabled(0), Current Mode(1), Voltage Mode(2)
1.3.6.1.4.1.6302.2.1.2.16.27ScalarsettingRectifierCurrentLimitEnableread-writecurrentRectifier Current Limit Enable, Disabled(0), Active(1)
1.3.6.1.4.1.6302.2.1.2.16.28ScalarsettingRectifierCurrentLimitread-writecurrentRectifier current limit stored as mA
1.3.6.1.4.1.6302.2.1.2.16.29ScalarsettingCalculateBatteryCurrentread-writecurrentCalculate Battery Current, no(0), yes(1)
1.3.6.1.4.1.6302.2.1.2.16.30ScalarsettingTemperatureCompProberead-writecurrentTemperature Compensation Probe, None(0), Maximum Probe Temperature(1), Average Probe Temperature(2), Minimum Probe Temperature(99), System Temp1(4), System Tem…
1.3.6.1.4.1.6302.2.1.2.16.31NodepsRelayAlarmLevel
1.3.6.1.4.1.6302.2.1.2.16.31.1ScalarsettingGeneratorRunAlarmLevelread-writecurrentGenerator Run Alarm Level, None(0), Minor Alarm(1), Major Alarm(2), Critical Alarm(3)
1.3.6.1.4.1.6302.2.1.2.16.31.2ScalarsettingGeneratorRunRelayread-writecurrentRelay IDs, None(0), IB2-1 Digital Output 1(1), IB2-1 Digital Output 2(2), IB2-1 Digital Output 3(3), IB2-1 Digital Output 4(4), IB2-1 Digital Output 5(5), IB2-…
1.3.6.1.4.1.6302.2.1.2.16.32NodepsECOMode
1.3.6.1.4.1.6302.2.1.2.16.32.1ScalarsettingECOModeEnableread-writecurrentECO Mode Enable, Disabled(0), Active(1)
1.3.6.1.4.1.6302.2.1.2.16.32.2ScalarsettingECORunModeread-writecurrentECO Operation Mode, Standard(0), Legacy(1)
1.3.6.1.4.1.6302.2.1.2.16.32.3ScalarsettingInhibitECOStopread-writecurrentInhibit ECO Stop, Disabled(0), Active(1)
1.3.6.1.4.1.6302.2.1.2.16.32.4ScalarsettingMinimumOperatingRectifiersread-writecurrentMinimum Operating Rectifiers
1.3.6.1.4.1.6302.2.1.2.16.32.5ScalarsettingBestOperatingPointread-writecurrentBest Operating Point in percent
1.3.6.1.4.1.6302.2.1.2.16.32.6ScalarsettingLoadFluctuationRangeread-writecurrentLoad Fluctuation Range in percent
1.3.6.1.4.1.6302.2.1.2.16.32.7ScalarsettingEnergySavingPointread-writecurrentSystem Energy Saving Point in percent
1.3.6.1.4.1.6302.2.1.2.16.32.8ScalarsettingCyclePeriodread-writecurrentCycle Period in hours
1.3.6.1.4.1.6302.2.1.2.16.32.9ScalarsettingAllRectifiersOnTimeread-writecurrentAll Rectifiers On Time in minutes
1.3.6.1.4.1.6302.2.1.2.16.32.10ScalarsettingTurnOffDelayread-writecurrentTurn Off Delay in minutes
1.3.6.1.4.1.6302.2.1.2.16.32.11ScalarsettingResetCycleAlarmread-writecurrentReset Cycle Alarm, Yes(1)
1.3.6.1.4.1.6302.2.1.2.16.33ScalarsettingRectifierDefaultVoltageread-writecurrentRectifier Default voltage stored in mV
1.3.6.1.4.1.6302.2.1.2.16.34ScalarsettingRectifierDefaultVoltage24Vread-writecurrentRectifier Default voltage stored in mV
1.3.6.1.4.1.6302.2.1.2.16.35ScalarsettingDefaultVoltageSelectread-writecurrentSelect Rectifier default voltage setpoint source, float(0), default(1)
1.3.6.1.4.1.6302.2.1.2.16.36ScalarsettingRectifierInputCurrentLimitread-writecurrentRectifier Input Current Limit stored in mA
1.3.6.1.4.1.6302.2.1.2.16.37ScalarsettingConverterDefaultVoltageread-writecurrentConverter Default voltage stored in mV
1.3.6.1.4.1.6302.2.1.2.16.38ScalarsettingConverterDefaultVoltage24Vread-writecurrentConverter Default voltage stored in mV
1.3.6.1.4.1.6302.2.1.2.19NodepsFCUPlus
1.3.6.1.4.1.6302.2.1.2.19.1TablepsFCUPlusTablenot-accessiblecurrentTable holding information about indivual FCU Plus equipment.
1.3.6.1.4.1.6302.2.1.2.19.1.1RowpsFCUPlusEntrynot-accessiblecurrentAn entry (conceptual row) in the FCUPlus InfoTable.
1.3.6.1.4.1.6302.2.1.2.19.1.1.1ColumnpsFCUPlusIndexread-onlycurrentAutomatically generated index object.
1.3.6.1.4.1.6302.2.1.2.19.1.1.2ColumnpsFCUPlusTemperature1read-onlycurrentFCUPlus Temperature1 stored as milli Celsius.
1.3.6.1.4.1.6302.2.1.2.19.1.1.3ColumnpsFCUPlusTemperature2read-onlycurrentFCUPlus Temperature2 stored as milli Celsius.
1.3.6.1.4.1.6302.2.1.2.19.1.1.4ColumnpsFCUPlusTemperature3read-onlycurrentFCUPlus Temperature3 stored as milli Celsius.
1.3.6.1.4.1.6302.2.1.2.19.1.1.5ColumnpsFCUPlusHumidityread-onlycurrentFCUPlus Humidity percent.
1.3.6.1.4.1.6302.2.1.2.19.1.1.6ColumnpsFCUPlusFanTyperead-onlycurrentFCUPlus fan type, HeatChange(0), ForcedVent(1)
1.3.6.1.4.1.6302.2.1.2.19.1.1.7ColumnpsFCUPlusWithHeaterread-onlycurrentFCUPlus with heater, no(0), yes(1)
1.3.6.1.4.1.6302.2.1.2.19.1.1.8ColumnpsFCUPlusFanGroup1Stateread-onlycurrentFCUPlus fan group 1 state, stop(0), start(1)
1.3.6.1.4.1.6302.2.1.2.19.1.1.9ColumnpsFCUPlusFanGroup2Stateread-onlycurrentFCUPlus fan group 2 state, stop(0), start(1)
1.3.6.1.4.1.6302.2.1.2.19.1.1.10ColumnpsFCUPlusFanGroup3Stateread-onlycurrentFCUPlus fan group 3 state, stop(0), start(1)
1.3.6.1.4.1.6302.2.1.2.19.1.1.11ColumnpsFCUPlusHeater1Stateread-onlycurrentFCUPlus heater 1 state, stop(0), start(1)
1.3.6.1.4.1.6302.2.1.2.19.1.1.12ColumnpsFCUPlusHeater2Stateread-onlycurrentFCUPlus heater 2 state, stop(0), start(1)
1.3.6.1.4.1.6302.2.1.2.19.1.1.13ColumnpsFCUPlusRunningModeread-onlycurrentFCUPlus running mode, Normal(0), Test(1)
1.3.6.1.4.1.6302.2.1.2.21NodepsInverter
1.3.6.1.4.1.6302.2.1.2.21.1ScalarnumberOfInstalledInvertersread-onlycurrentnumber of Inverters, stored as integer. The integer 2147483647 represents invalid value.
1.3.6.1.4.1.6302.2.1.2.21.2ScalarnumberOfInvertersCommunicatingread-onlycurrentnumber of rectifiers communicating, stored as integer. The integer 2147483647 represents invalid value.
1.3.6.1.4.1.6302.2.1.2.21.3ScalarinvertersUsedCapacityread-onlycurrentUsed capacity, stored as % of the total capacity. The integer 2147483647 represents invalid value.
1.3.6.1.4.1.6302.2.1.2.21.4TablepsInverterTablenot-accessiblecurrentTable holding information about indivual rectifiers.
1.3.6.1.4.1.6302.2.1.2.21.4.1RowpsInverterEntrynot-accessiblecurrentAn entry (conceptual row) in the rectifierInfoTable.
1.3.6.1.4.1.6302.2.1.2.21.4.1.1ColumnpsInverterIndexread-onlycurrentAutomatically generated index object.
1.3.6.1.4.1.6302.2.1.2.21.4.1.2ColumnpsInverterProductNumberread-onlycurrentInverter Product Number.
1.3.6.1.4.1.6302.2.1.2.21.4.1.3ColumnpsInverterHWVersionread-onlycurrentInverter Hardware Revision.
1.3.6.1.4.1.6302.2.1.2.21.4.1.4ColumnpsInverterSWVersionread-onlycurrentInverter Software Revision.
1.3.6.1.4.1.6302.2.1.2.21.4.1.5ColumnpsInverterSerialNumberread-onlycurrentInverter Serial Number.
1.3.6.1.4.1.6302.2.1.2.21.4.1.6ColumnpsInverterVoltageread-onlycurrentInverter Output Voltage.
1.3.6.1.4.1.6302.2.1.2.21.4.1.7ColumnpsInverterCurrentread-onlycurrentInverter Output Current.
1.3.6.1.4.1.6302.2.1.2.21.4.1.8ColumnpsInverterIdentread-onlycurrentInverter physical location identifier.
1.3.6.1.4.1.6302.2.1.2.21.4.1.9ColumnpsInverterFrequencyread-onlycurrentInverter Output Frequency
1.3.6.1.4.1.6302.2.1.2.25NodepsSolar
1.3.6.1.4.1.6302.2.1.2.25.1ScalarnumberOfInstalledSolarread-onlycurrentnumber of Solar converters, stored as integer. The integer 2147483647 represents invalid value.
1.3.6.1.4.1.6302.2.1.2.25.2ScalarnumberOfSolarCommunicatingread-onlycurrentnumber of Solar converters communicating, stored as integer. The integer 2147483647 represents invalid value.
1.3.6.1.4.1.6302.2.1.2.25.3ScalarsolarsUsedCapacityread-onlycurrentUsed capacity, stored as % of the total capacity. The integer 2147483647 represents invalid value.
1.3.6.1.4.1.6302.2.1.2.25.4ScalarpsSolarTotalCurrentread-onlycurrentSolar Converter Total output current in mA. The integer 2147483647 represents invalid value.
1.3.6.1.4.1.6302.2.1.2.25.5ScalarpsSolarTotalPowerread-onlycurrentSolar Converter Total Output Power in W * 1000.
1.3.6.1.4.1.6302.2.1.2.25.6ScalarpsSolarTotalInputCurrentread-onlycurrentSolar Converter Total input current in mA. The integer 2147483647 represents invalid value.
1.3.6.1.4.1.6302.2.1.2.25.7ScalarpsSolarTotalInputPowerread-onlycurrentSolar Converter Total input Power in kW * 1000.
1.3.6.1.4.1.6302.2.1.2.25.8ScalarpsSolarModeread-writecurrentSolar mode, Disabled(0), RECT-SOLAR(1), Solar(2)
1.3.6.1.4.1.6302.2.1.2.25.9ScalarpsSolarRunningWayread-writecurrentSolar mode, Disabled(0), RECT-SOLAR(1), Solar(2)
1.3.6.1.4.1.6302.2.1.2.25.10TablepsSolarTablenot-accessiblecurrentTable holding information about indivual solar converters.
1.3.6.1.4.1.6302.2.1.2.25.10.1RowpsSolarEntrynot-accessiblecurrentAn entry (conceptual row) in the solar converter InfoTable.
1.3.6.1.4.1.6302.2.1.2.25.10.1.1ColumnpsSolarIndexread-onlycurrentAutomatically generated index object.
1.3.6.1.4.1.6302.2.1.2.25.10.1.2ColumnpsSolarProductNumberread-onlycurrentSolar Converter Product Number.
1.3.6.1.4.1.6302.2.1.2.25.10.1.3ColumnpsSolarHWVersionread-onlycurrentSolar Converter Hardware Revision.
1.3.6.1.4.1.6302.2.1.2.25.10.1.4ColumnpsSolarSWVersionread-onlycurrentSolar Converter Software Revision.
1.3.6.1.4.1.6302.2.1.2.25.10.1.5ColumnpsSolarSerialNumberread-onlycurrentSolar Converter Serial Number.
1.3.6.1.4.1.6302.2.1.2.25.10.1.6ColumnpsSolarIdentread-onlycurrentSolar Converter physical location identifier.
1.3.6.1.4.1.6302.2.1.2.25.10.1.7ColumnpsSolarRatedIoutAtMaxVoutread-onlycurrentSolar converter rated Iout milliamps at Max Vout.
1.3.6.1.4.1.6302.2.1.2.25.10.1.8ColumnpsSolarInputVoltageread-onlycurrentSolar converter rated input voltage in millivolts.
1.3.6.1.4.1.6302.2.1.2.25.10.1.9ColumnpsSolarInputCurrentread-onlycurrentSolar converter input current in milliamps.
1.3.6.1.4.1.6302.2.1.2.25.10.1.10ColumnpsSolarInputPowerread-onlycurrentSolar converter input power in W.
1.3.6.1.4.1.6302.2.1.2.25.10.1.11ColumnpsSolarOutputVoltageread-onlycurrentSolar converter output voltage in millivolts.
1.3.6.1.4.1.6302.2.1.2.25.10.1.12ColumnpsSolarOutputCurrentread-onlycurrentSolar converter output current in milliamps.
1.3.6.1.4.1.6302.2.1.2.25.10.1.13ColumnpsSolarOutputPowerread-onlycurrentSolar converter output power in W.
1.3.6.1.4.1.6302.2.1.2.25.10.1.14ColumnpsSolarUsedCapacityread-onlycurrentSolar converter used capacity in percent.
1.3.6.1.4.1.6302.2.1.2.25.10.1.15ColumnpsSolarTotalRunningTimeread-onlycurrentSolar converter total running time in hours * 1000.
1.3.6.1.4.1.6302.2.1.2.25.10.1.16ColumnpsSolarFailread-onlycurrentThe type of alarm change. One of (1) activated (2) deactivated
1.3.6.1.4.1.6302.2.1.3ScalaralarmLastTrapNoread-onlycurrentThe sequence number of last submitted alarm trap, also last row in alarmTrapTable.
1.3.6.1.4.1.6302.2.1.4TablealarmActiveAlarmTablenot-accessiblecurrentTable holding information about the currently active alarms.
1.3.6.1.4.1.6302.2.1.4.1RowactiveAlarmEntrynot-accessiblecurrentAn entry (conceptual row) in the alarmTrapTable.
1.3.6.1.4.1.6302.2.1.4.1.1ColumnalarmIndexread-onlycurrentThe unique sequence number of this alarm trap.
1.3.6.1.4.1.6302.2.1.4.1.2ColumnalarmTimeread-onlycurrentDate and time when event occured (local time), including timezone if supported by controller.
1.3.6.1.4.1.6302.2.1.4.1.3ColumnalarmStatusChangeread-onlycurrentThe type of alarm change. One of (1) activated (2) deactivated
1.3.6.1.4.1.6302.2.1.4.1.4ColumnalarmSeverityread-onlycurrentThe severity of the alarm. One of (3) warning - OA, lowest level of alarm severity (4) minor - A3 (5) major - MA (6) critical - CA, highest level of alarm seve…
1.3.6.1.4.1.6302.2.1.4.1.5ColumnalarmDescriptionread-onlycurrentFree-text description of alarm.
1.3.6.1.4.1.6302.2.1.4.1.6ColumnalarmTyperead-onlycurrentAlarm type, i.e. an integer specifying the type of alarm.
1.3.6.1.4.1.6302.2.1.5NodepowerEvents
1.3.6.1.4.1.6302.2.1.5.1NotificationalarmTrapcurrentAn alarm trap is sent when an alarm occurs (activated) or returns to normal state (deactivated). Alarm traps are logged in alarmTrapTable. Variables in this tr…
1.3.6.1.4.1.6302.2.1.5.2NotificationalarmActiveTrapcurrentAn alarm trap is sent when an alarm occurs (activated) Variables in this trap * alarmTime - Date and time when event occured (local time), including timezone i…
1.3.6.1.4.1.6302.2.1.5.3NotificationalarmCeaseTrapcurrentAn alarm trap is sent when an alarm returns to normal state (clear, deactivated). Variables in this trap: * alarmTime - Date and time when event occured (local…
Type Definitions
NameSyntaxStatusDescription
StatusINTEGER { unknown(1), normal(2), warning(3), minor(4), major(5), critical(6), unmanaged(7), restricted(8), testing(9), disabled(10) }currentThis integer value represents the operational or administrative status of the system. Also used as alarm severity. Depending on situation there may be limits on allowed values. Operational values: (1) unknown - status h…
StatusChangeINTEGER { activated(1), deactivated(2) }currentIndicates 'activated' (1) or 'deactivated' (2) alarm events.