MIB Viewer

NETTRACK-E3METER-SNMP-MIB

106 objects
Management Information for E3METER IPM products www.e3meter.com
Imported Objects
SNMPv2-SMIenterprises Integer32 MODULE-IDENTITY OBJECT-TYPE
SNMPv2-TCTEXTUAL-CONVENTION TruthValue
OIDNameAccessStatusDescription
1.3.6.1.4.1.21695Nodenettrack
1.3.6.1.4.1.21695.1Nodepublic
1.3.6.1.4.1.21695.1.10Identitye3MibManagement Information for E3METER IPM products www.e3meter.com
1.3.6.1.4.1.21695.1.10.7Nodee3Ipm
1.3.6.1.4.1.21695.1.10.7.1Nodee3IpmInfo
1.3.6.1.4.1.21695.1.10.7.1.1Scalare3IpmInfoSerialread-onlycurrentSerial number.
1.3.6.1.4.1.21695.1.10.7.1.2Scalare3IpmInfoModelread-onlycurrentModel number.
1.3.6.1.4.1.21695.1.10.7.1.3Scalare3IpmInfoHWVersionread-onlycurrentHardware revision.
1.3.6.1.4.1.21695.1.10.7.1.4Scalare3IpmInfoFWVersionread-onlycurrentInteger representation of the firmware revision (major.minor) represented as a 16 bit integer.
1.3.6.1.4.1.21695.1.10.7.1.5Scalare3IpmInfoMetersread-onlycurrentNumber of power meters in this IPS.
1.3.6.1.4.1.21695.1.10.7.2Tablee3IpmMeterTablenot-accessiblecurrentThe e3IpmMeterTable holds information related to the powermeters of all IPS nodes.
1.3.6.1.4.1.21695.1.10.7.2.1Rowe3IpmMeterEntrynot-accessiblecurrentHolds the information related to one specific powermeter.
1.3.6.1.4.1.21695.1.10.7.2.1.1Columne3IpmMeterread-onlycurrentNumber of the powermeter of this IPS.
1.3.6.1.4.1.21695.1.10.7.2.1.2Columne3IpmEnergyPread-onlycurrentActive energy in watt hours.
1.3.6.1.4.1.21695.1.10.7.2.1.3Columne3IpmEnergyQread-onlycurrentReactive energy in volt-ampere reactives hours.
1.3.6.1.4.1.21695.1.10.7.2.1.4Columne3IpmEnergySread-onlycurrentApparent energy in volt-ampere hours.
1.3.6.1.4.1.21695.1.10.7.2.1.5Columne3IpmPowerPread-onlycurrentActive power at a given instant.
1.3.6.1.4.1.21695.1.10.7.2.1.6Columne3IpmPowerQread-onlycurrentReactive power at a given instant.
1.3.6.1.4.1.21695.1.10.7.2.1.7Columne3IpmPowerSread-onlycurrentApparent power at a given instant.
1.3.6.1.4.1.21695.1.10.7.2.1.8Columne3IpmUrmsread-onlycurrentRMS voltage at a given instant.
1.3.6.1.4.1.21695.1.10.7.2.1.9Columne3IpmIrmsread-onlycurrentRMS current at a given instant.
1.3.6.1.4.1.21695.1.10.7.2.1.10Columne3IpmFrequencyread-onlycurrentFrequency measured a given instant.
1.3.6.1.4.1.21695.1.10.7.2.1.11Columne3IpmChannelNameread-onlycurrentChannel name.
1.3.6.1.4.1.21695.1.10.7.2.1.12Columne3IpmChannelTyperead-onlycurrentChannel type: For neutral wire channels, only I_rms will contain meaningful values.
1.3.6.1.4.1.21695.1.10.7.3Tablee3IpmSensorTablenot-accessiblecurrentThe e3IpmSensorTable holds information related to the sensor of this IPM.
1.3.6.1.4.1.21695.1.10.7.3.1Rowe3IpmSensorEntrynot-accessiblecurrentHolds the information related to one specific sensor.
1.3.6.1.4.1.21695.1.10.7.3.1.1Columne3IpmSensorread-onlycurrentSensor port number.
1.3.6.1.4.1.21695.1.10.7.3.1.2Columne3IpmSensorTyperead-onlycurrentSensor type.
1.3.6.1.4.1.21695.1.10.7.3.1.3Columne3IpmSensorVersionread-onlycurrentSensor version.
1.3.6.1.4.1.21695.1.10.7.3.1.4Columne3IpmSensorTemperatureCelsiusread-onlycurrentTemperature in tenth degrees.
1.3.6.1.4.1.21695.1.10.7.3.1.5Columne3IpmSensorHumidityread-onlycurrentRelative humidity in per mil.
1.3.6.1.4.1.21695.1.10.7.4Tablee3IpmPGroupTablenot-accessiblecurrentThe e3IpmPGroupTable holds information related to predefined channel groups.
1.3.6.1.4.1.21695.1.10.7.4.1Rowe3IpmPGroupEntrynot-accessiblecurrentHolds the information related to one specific group.
1.3.6.1.4.1.21695.1.10.7.4.1.1Columne3IpmPGroupread-onlycurrentPredefined channel group number.
1.3.6.1.4.1.21695.1.10.7.4.1.2Columne3IpmPGNameread-onlycurrentChannel group name.
1.3.6.1.4.1.21695.1.10.7.4.1.3Columne3IpmPGMembersread-onlycurrentA bit set specifying the channels which are members of this channel group. If bit 0 is set, this means that channel CH1 is member of this group. Bit 1 stands f…
1.3.6.1.4.1.21695.1.10.7.4.1.4Columne3IpmPGEnergyPread-onlycurrentChannel group active energy in watt hours.
1.3.6.1.4.1.21695.1.10.7.4.1.5Columne3IpmPGEnergyQread-onlycurrentChannel group reactive energy in volt-ampere reactives hours.
1.3.6.1.4.1.21695.1.10.7.4.1.6Columne3IpmPGEnergySread-onlycurrentChannel group apparent energy in volt-ampere hours.
1.3.6.1.4.1.21695.1.10.7.4.1.7Columne3IpmPGPowerPread-onlycurrentChannel group active power at a given instant.
1.3.6.1.4.1.21695.1.10.7.4.1.8Columne3IpmPGPowerQread-onlycurrentChannel group reactive power at a given instant.
1.3.6.1.4.1.21695.1.10.7.4.1.9Columne3IpmPGPowerSread-onlycurrentChannel group apparent power at a given instant.
1.3.6.1.4.1.21695.1.10.7.4.1.10Columne3IpmPGIrmsread-onlycurrentChannel group RMS current at a given instant.
1.3.6.1.4.1.21695.1.10.7.5Tablee3IpmUGroupTablenot-accessiblecurrentThe e3IpmUGroupTable holds information related to user defined channel groups.
1.3.6.1.4.1.21695.1.10.7.5.1Rowe3IpmUGroupEntrynot-accessiblecurrentHolds the information related to one specific group.
1.3.6.1.4.1.21695.1.10.7.5.1.1Columne3IpmUGroupread-onlycurrentUser defined channel group number.
1.3.6.1.4.1.21695.1.10.7.5.1.2Columne3IpmUGNameread-onlycurrentChannel group name.
1.3.6.1.4.1.21695.1.10.7.5.1.3Columne3IpmUGMembersread-onlycurrentA bit set specifying the channels which are members of this channel group. If bit 0 is set, this means that channel CH1 is member of this group. Bit 1 stands f…
1.3.6.1.4.1.21695.1.10.7.5.1.4Columne3IpmUGEnergyPread-onlycurrentChannel group active energy in watt hours.
1.3.6.1.4.1.21695.1.10.7.5.1.5Columne3IpmUGEnergyQread-onlycurrentChannel group reactive energy in volt-ampere reactives hours.
1.3.6.1.4.1.21695.1.10.7.5.1.6Columne3IpmUGEnergySread-onlycurrentChannel group apparent energy in volt-ampere hours.
1.3.6.1.4.1.21695.1.10.7.5.1.7Columne3IpmUGPowerPread-onlycurrentChannel group active power at a given instant.
1.3.6.1.4.1.21695.1.10.7.5.1.8Columne3IpmUGPowerQread-onlycurrentChannel group reactive power at a given instant.
1.3.6.1.4.1.21695.1.10.7.5.1.9Columne3IpmUGPowerSread-onlycurrentChannel group apparent power at a given instant.
1.3.6.1.4.1.21695.1.10.7.5.1.10Columne3IpmUGIrmsread-onlycurrentChannel group RMS current at a given instant.
1.3.6.1.4.1.21695.1.10.7.6Tablee3IpmAlarmTablenot-accessiblecurrentHolds alarm settings.
1.3.6.1.4.1.21695.1.10.7.6.1Rowe3IpmAlarmTableEntrynot-accessiblecurrentHolds alarm settings for one specific measured value.
1.3.6.1.4.1.21695.1.10.7.6.1.1Columne3IpmAlarmIndexread-onlycurrentDefines the alarm described by the current entry. There are alarms for the current of all phases, for the temperature and the relative humidity.
1.3.6.1.4.1.21695.1.10.7.6.1.2Columne3IpmAlarmStateread-onlycurrentShows this alarm entries' state. If no alarm settings are defined, the state is unknown.
1.3.6.1.4.1.21695.1.10.7.6.1.3Columne3IpmAlarmCritLowSetread-onlycurrentTrue if a 'critical low' alarm level for the current entry is defined, false otherwise.
1.3.6.1.4.1.21695.1.10.7.6.1.4Columne3IpmAlarmCritLowread-onlycurrentThe 'critical low' alarm level for the current entry in hundredths of the relevant unit (i.e. amperes, degrees celsius and %RH). If no alarm level is configure…
1.3.6.1.4.1.21695.1.10.7.6.1.5Columne3IpmAlarmWarnLowSetread-onlycurrentTrue if a 'warn low' alarm level for the current entry is defined, false otherwise.
1.3.6.1.4.1.21695.1.10.7.6.1.6Columne3IpmAlarmWarnLowread-onlycurrentThe 'warn low' alarm level for the current entry in hundredths of the relevant unit (i.e. amperes, degrees celsius and %RH). If no alarm level is configured, t…
1.3.6.1.4.1.21695.1.10.7.6.1.7Columne3IpmAlarmWarnHighSetread-onlycurrentTrue if a 'warn high' alarm level for the current entry is defined, false otherwise.
1.3.6.1.4.1.21695.1.10.7.6.1.8Columne3IpmAlarmWarnHighread-onlycurrentThe 'warn high' alarm level for the current entry in hundredths of the relevant unit (i.e. amperes, degrees celsius and %RH). If no alarm level is configured, …
1.3.6.1.4.1.21695.1.10.7.6.1.9Columne3IpmAlarmCritHighSetread-onlycurrentTrue if a 'critical high' alarm level for the current entry is defined, false otherwise.
1.3.6.1.4.1.21695.1.10.7.6.1.10Columne3IpmAlarmCritHighread-onlycurrentThe 'critical high' alarm level for the current entry in hundredths of the relevant unit (i.e. amperes, degrees celsius and %RH). If no alarm level is configur…
1.3.6.1.4.1.21695.1.10.7.7Scalare3IpmRcmTableread-onlycurrentTable holding all residual current monitoring (RCM) data of this IPS.
1.3.6.1.4.1.21695.1.10.7.7.1Scalare3IpmRcmTableEntrynot-accessiblecurrentOne entry in the RCM table.
1.3.6.1.4.1.21695.1.10.7.7.1.1Scalare3IpmRcmChannelread-onlycurrentRCM channel: 0 (total) is the total of all phases in this IPS.
1.3.6.1.4.1.21695.1.10.7.7.1.2Scalare3IpmRcmAcLimitread-onlycurrentThe factory configured AC RCM limit. Any measurement higher than this limit is considered a critical problem.
1.3.6.1.4.1.21695.1.10.7.7.1.3Scalare3IpmRcmDcLimitread-onlycurrentThe factory configured DC RCM limit. Any measurement higher than this limit is considered a critical problem.
1.3.6.1.4.1.21695.1.10.7.7.1.4Scalare3IpmRcmStatusread-onlycurrentStatus of the RcmAc/RcmDc data. If the residual current cannot be measured, 0 (unknown) is signalled here, otherwise 1 (valid).
1.3.6.1.4.1.21695.1.10.7.7.1.5Scalare3IpmRcmAcread-onlycurrentThe latest AC RCM measurement.
1.3.6.1.4.1.21695.1.10.7.7.1.6Scalare3IpmRcmDcread-onlycurrentThe latest DC RCM measurement.
1.3.6.1.4.1.21695.1.10.8Nodee3IpmTraps
1.3.6.1.4.1.21695.1.10.8.1Notificatione3IpmCurrentCritLowcurrentThe e3IpmCurrentCritLow is triggered when the current on the given channel is less than or equal to the configured critical low threshold.
1.3.6.1.4.1.21695.1.10.8.2Notificatione3IpmCurrentWarnLowcurrentThe e3IpmCurrentWarnLow is triggered when the current on the given channel is less than or equal to the configured warn low threshold.
1.3.6.1.4.1.21695.1.10.8.3Notificatione3IpmCurrentNormalcurrentThe e3IpmCurrentNormal is triggered when the current on the given channel is not outside any configured limits.
1.3.6.1.4.1.21695.1.10.8.4Notificatione3IpmCurrentWarnHighcurrentThe e3IpmCurrentWarnHigh is triggered when the current on the given channel is greater than or equal to the configured warn high threshold.
1.3.6.1.4.1.21695.1.10.8.5Notificatione3IpmCurrentCritHighcurrentThe e3IpmCurrentCritHigh is triggered when the current on the given channel is greater than or equal to the configured critical high threshold.
1.3.6.1.4.1.21695.1.10.8.6Notificatione3IpmTempCritLowcurrentThe e3IpmTempCritLow is triggered when the temperature on the given sensor is less than or equal to the configured critical low threshold.
1.3.6.1.4.1.21695.1.10.8.7Notificatione3IpmTempWarnLowcurrentThe e3IpmTempWarnLow is triggered when the temperature on the given sensor is less than or equal to the configured warn low threshold.
1.3.6.1.4.1.21695.1.10.8.8Notificatione3IpmTempNormalcurrentThe e3IpmTempNormal is triggered when the temperature on the given sensor is not outside any configured limits.
1.3.6.1.4.1.21695.1.10.8.9Notificatione3IpmTempWarnHighcurrentThe e3IpmTempWarnHigh is triggered when the temperature on the given sensor is greater than or equal to the configured warn high threshold.
1.3.6.1.4.1.21695.1.10.8.10Notificatione3IpmTempCritHighcurrentThe e3IpmTempCritHigh is triggered when the temperature on the given sensor is greater than or equal to the configured critical high threshold.
1.3.6.1.4.1.21695.1.10.8.11Notificatione3IpmRHCritLowcurrentThe e3IpmRHCritLow is triggered when the relative humidity on the given sensor is less than or equal to the configured critical low threshold.
1.3.6.1.4.1.21695.1.10.8.12Notificatione3IpmRHWarnLowcurrentThe e3IpmRHWarnLow is triggered when the relative humidity on the given sensor is less than or equal to the configured warn low threshold.
1.3.6.1.4.1.21695.1.10.8.13Notificatione3IpmRHNormalcurrentThe e3IpmRHNormal is triggered when the relative humidity on the given sensor is not outside any configured limits.
1.3.6.1.4.1.21695.1.10.8.14Notificatione3IpmRHWarnHighcurrentThe e3IpmRHWarnHigh is triggered when the relative humidity on the given sensor is greater than or equal to the configured warn high threshold.
1.3.6.1.4.1.21695.1.10.8.15Notificatione3IpmRHCritHighcurrentThe e3IpmRHCritHigh is triggered when the relative humidity on the given sensor is greater than or equal to the configured critical high threshold.
1.3.6.1.4.1.21695.1.10.8.16Notificatione3IpmRcmAcNormalcurrentThe e3IpmRcmAcNormal is triggered when the AC part of the residual current falls below the factory-configured limit.
1.3.6.1.4.1.21695.1.10.8.17Notificatione3IpmRcmAcCritHighcurrentThe e3IpmRcmAcCritHigh is triggered when the AC part of the residual current is greater than the factory-configured limit.
1.3.6.1.4.1.21695.1.10.8.18Notificatione3IpmRcmDcNormalcurrentThe e3IpmRcmDcNormal is triggered when the DC part of the residual current falls below the factory-configured limit.
1.3.6.1.4.1.21695.1.10.8.19Notificatione3IpmRcmDcCritHighcurrentThe e3IpmRcmDcCritHigh is triggered when the DC part of the residual current is greater than the factory-configured limit.
Type Definitions
NameSyntaxStatusDescription
DeciDegreesCelsiusInteger32currentDeci-degrees celsius
MilliAmperesInteger32currentMilli-amperes
MilliHertzInteger32currentMilli-hertz
MilliVoltsInteger32currentMilli-volts
PermilINTEGERcurrentPer mil
VoltAmpereHoursInteger32currentVolt-ampere hours
VoltAmpereReactiveHoursInteger32currentVolt-ampere reactive hours
VoltAmpereReactivesInteger32currentVolt-ampere reactives
VoltAmperesInteger32currentVolt-amperes
WattHoursInteger32currentWatt hours
WattsINTEGERcurrentWatts