MIB Viewer

NetBotz50-MIB

571 objects
NetBotz5-APC BotzWare MIB. Last modification Apr 2025 for webServiceAPIVersion object
Imported Objects
SNMPv2-CONFNOTIFICATION-GROUP OBJECT-GROUP
SNMPv2-SMICounter32 enterprises Integer32 MODULE-IDENTITY NOTIFICATION-TYPE OBJECT-TYPE
SNMPv2-TCDateAndTime DisplayString TEXTUAL-CONVENTION
OIDNameAccessStatusDescription
1.3.6.1.4.1.52674NodenetBotzAPC
1.3.6.1.4.1.52674.500NodenetBotz5
1.3.6.1.4.1.52674.500.1IdentitynetBotz5-APCNetBotz5-APC BotzWare MIB. Last modification Apr 2025 for webServiceAPIVersion object
1.3.6.1.4.1.52674.500.2NodenetBotzEnclosures
1.3.6.1.4.1.52674.500.2.1TableenclosureTablenot-accessiblecurrentA list of enclosures (base enclosure and pods).
1.3.6.1.4.1.52674.500.2.1.1RowenclosureEntrynot-accessiblecurrentEnclosure entry.
1.3.6.1.4.1.52674.500.2.1.1.1ColumnenclosureIdread-onlycurrentThe id of the physical enclosure.
1.3.6.1.4.1.52674.500.2.1.1.2ColumnenclosureStatusread-onlycurrentThe operational status of the enclosure.
1.3.6.1.4.1.52674.500.2.1.1.3ColumnenclosureErrorStatusread-onlycurrentThe error status of the enclosure. If there are no error conditions reported for the enclosure, the status is normal. Otherwise, the status is reported as the …
1.3.6.1.4.1.52674.500.2.1.1.4ColumnenclosureLabelread-onlycurrentThe unique label assigned to the enclosure (or pod).
1.3.6.1.4.1.52674.500.2.1.1.5ColumnenclosureParentEncIdread-onlycurrentThe id of the parent enclosure this enclosure is attached to.
1.3.6.1.4.1.52674.500.2.1.1.6ColumnenclosureSerialNumberread-onlycurrentThe serial number of this enclosure.
1.3.6.1.4.1.52674.500.2.1.1.7ColumnenclosureIndexread-onlycurrentThe index of the physical enclosure.
1.3.6.1.4.1.52674.500.2.2NodenetBotzSensorCounts
1.3.6.1.4.1.52674.500.2.2.1TablealinkSensorCountTablenot-accessiblecurrentA count of alink-related sensors.
1.3.6.1.4.1.52674.500.2.2.1.1RowalinkSensorCountEntrynot-accessiblecurrentA count-of-sensors entry.
1.3.6.1.4.1.52674.500.2.2.1.1.1ColumnalinkSensorCountIdread-onlycurrentThe unique id of the sensor.
1.3.6.1.4.1.52674.500.2.2.1.1.2ColumnalinkSensorCountValueread-onlycurrentThe number of known connected sensors.
1.3.6.1.4.1.52674.500.2.2.1.1.3ColumnalinkSensorCountLabelread-onlycurrentThe unique label assigned to the sensor count.
1.3.6.1.4.1.52674.500.2.2.1.1.4ColumnalinkSensorCountEncIdread-onlycurrentThe id of the physical enclosure represented by the sensor count.
1.3.6.1.4.1.52674.500.2.2.1.1.5ColumnalinkSensorCountValueStrread-onlycurrentThe sensor count value shown as a string.
1.3.6.1.4.1.52674.500.2.2.1.1.6ColumnalinkSensorCountValueIntread-onlycurrentThe sensor count as integer value.
1.3.6.1.4.1.52674.500.2.2.1.1.7ColumnalinkSensorCountIndexread-onlycurrentThe index of the sensor counter.
1.3.6.1.4.1.52674.500.3NodenetBotzPorts
1.3.6.1.4.1.52674.500.3.10TableotherPortTablenot-accessiblecurrentA list of other port entries.
1.3.6.1.4.1.52674.500.3.10.1RowotherPortEntrynot-accessiblecurrentOther port entry.
1.3.6.1.4.1.52674.500.3.10.1.1ColumnotherPortIdread-onlycurrentThe unique id of the port.
1.3.6.1.4.1.52674.500.3.10.1.2ColumnotherPortStatusread-onlycurrentThe operational status of the port.
1.3.6.1.4.1.52674.500.3.10.1.3ColumnotherPortLabelread-onlycurrentThe unique label assigned to the port.
1.3.6.1.4.1.52674.500.3.10.1.4ColumnotherPortEncIdread-onlycurrentThe id of the physical enclosure containing the port.
1.3.6.1.4.1.52674.500.3.10.1.5ColumnotherPortIndexread-onlycurrentThe index of the port.
1.3.6.1.4.1.52674.500.4NodenetBotzSensors
1.3.6.1.4.1.52674.500.4.1NodenetBotzNumericSensors
1.3.6.1.4.1.52674.500.4.1.1TabletempSensorTablenot-accessiblecurrentA list of temperature sensor entries.
1.3.6.1.4.1.52674.500.4.1.1.1RowtempSensorEntrynot-accessiblecurrentA temperature sensor entry.
1.3.6.1.4.1.52674.500.4.1.1.1.1ColumntempSensorIdread-onlycurrentThe unique id of the sensor.
1.3.6.1.4.1.52674.500.4.1.1.1.2ColumntempSensorValueread-onlycurrentThe temperature measured by the sensor in tenths of a degree Celsius.
1.3.6.1.4.1.52674.500.4.1.1.1.3ColumntempSensorErrorStatusread-onlycurrentThe error status of the sensor. If there are no error conditions reported for the sensor, the status is normal. Otherwise, the status is reported as the severi…
1.3.6.1.4.1.52674.500.4.1.1.1.4ColumntempSensorLabelread-onlycurrentThe unique label assigned to the sensor.
1.3.6.1.4.1.52674.500.4.1.1.1.5ColumntempSensorEncIdread-onlycurrentThe id of the physical enclosure containing the sensor.
1.3.6.1.4.1.52674.500.4.1.1.1.6ColumntempSensorPortIdread-onlycurrentThe id of the port the sensor is plugged into (or empty string if it is not plugged into a port).
1.3.6.1.4.1.52674.500.4.1.1.1.7ColumntempSensorValueStrread-onlycurrentThe temperature reading, in degrees Celsius, shown as a string (or empty string if it is not plugged into a port).
1.3.6.1.4.1.52674.500.4.1.1.1.8ColumntempSensorValueIntread-onlycurrentThe temperature measured by the sensor in degree Celsius.
1.3.6.1.4.1.52674.500.4.1.1.1.9ColumntempSensorValueIntFread-onlycurrentThe temperature measured by the sensor in degree Fahrenheit.
1.3.6.1.4.1.52674.500.4.1.1.1.10ColumntempSensorIndexread-onlycurrentThe index of the sensor.
1.3.6.1.4.1.52674.500.4.1.2TablehumiSensorTablenot-accessiblecurrentA list of humidity sensor entries.
1.3.6.1.4.1.52674.500.4.1.2.1RowhumiSensorEntrynot-accessiblecurrentA humidity sensor entry.
1.3.6.1.4.1.52674.500.4.1.2.1.1ColumnhumiSensorIdread-onlycurrentThe unique id of the sensor.
1.3.6.1.4.1.52674.500.4.1.2.1.2ColumnhumiSensorValueread-onlycurrentThe relative humidity measured by the sensor in tenths of a percent.
1.3.6.1.4.1.52674.500.4.1.2.1.3ColumnhumiSensorErrorStatusread-onlycurrentThe error status of the sensor. If there are no error conditions reported for the sensor, the status is normal. Otherwise, the status is reported as the severi…
1.3.6.1.4.1.52674.500.4.1.2.1.4ColumnhumiSensorLabelread-onlycurrentThe unique label assigned to the sensor.
1.3.6.1.4.1.52674.500.4.1.2.1.5ColumnhumiSensorEncIdread-onlycurrentThe id of the physical enclosure containing the sensor.
1.3.6.1.4.1.52674.500.4.1.2.1.6ColumnhumiSensorPortIdread-onlycurrentThe id of the port the sensor is plugged into (or empty string if it is not plugged into a port).
1.3.6.1.4.1.52674.500.4.1.2.1.7ColumnhumiSensorValueStrread-onlycurrentThe humidity reading, in percent, shown as a string (or empty string if it is not plugged into a port).
1.3.6.1.4.1.52674.500.4.1.2.1.8ColumnhumiSensorValueIntread-onlycurrentThe relative humidity measured by the sensor in percent.
1.3.6.1.4.1.52674.500.4.1.2.1.9ColumnhumiSensorIndexread-onlycurrentThe index of the sensor.
1.3.6.1.4.1.52674.500.4.1.3TabledewPointSensorTablenot-accessiblecurrentA list of dew point sensor entries.
1.3.6.1.4.1.52674.500.4.1.3.1RowdewPointSensorEntrynot-accessiblecurrentA dew point sensor entry.
1.3.6.1.4.1.52674.500.4.1.3.1.1ColumndewPointSensorIdread-onlycurrentThe unique id of the sensor.
1.3.6.1.4.1.52674.500.4.1.3.1.2ColumndewPointSensorValueread-onlycurrentThe dew point value measured by the sensor in tenths of a degree Celsius.
1.3.6.1.4.1.52674.500.4.1.3.1.3ColumndewPointSensorErrorStatusread-onlycurrentThe operational status of the sensor. If there are no error conditions reported for the sensor, the status is normal. Otherwise, the status is reported as the …
1.3.6.1.4.1.52674.500.4.1.3.1.4ColumndewPointSensorLabelread-onlycurrentThe unique label assigned to the sensor.
1.3.6.1.4.1.52674.500.4.1.3.1.5ColumndewPointSensorEncIdread-onlycurrentThe id of the physical enclosure containing the sensor.
1.3.6.1.4.1.52674.500.4.1.3.1.6ColumndewPointSensorPortIdread-onlycurrentThe id of the port the sensor is plugged into (or empty string if it is not plugged into a port).
1.3.6.1.4.1.52674.500.4.1.3.1.7ColumndewPointSensorValueStrread-onlycurrentThe dew point reading, in degrees Celsius, shown as a string (or empty string if it is not plugged into a port).
1.3.6.1.4.1.52674.500.4.1.3.1.8ColumndewPointSensorValueIntread-onlycurrentThe dew point value measured by the sensor in degrees Celsius.
1.3.6.1.4.1.52674.500.4.1.3.1.9ColumndewPointSensorValueIntFread-onlycurrentThe dew point reading in degrees Fahrenheit, measured by the sensor.
1.3.6.1.4.1.52674.500.4.1.3.1.10ColumndewPointSensorIndexread-onlycurrentThe index of the sensor.
1.3.6.1.4.1.52674.500.4.1.5TableairFlowSensorTablenot-accessiblecurrentA list of airflow sensor entries.
1.3.6.1.4.1.52674.500.4.1.5.1RowairFlowSensorEntrynot-accessiblecurrentAn air flow sensor entry.
1.3.6.1.4.1.52674.500.4.1.5.1.1ColumnairFlowSensorIdread-onlycurrentThe unique id of the sensor.
1.3.6.1.4.1.52674.500.4.1.5.1.2ColumnairFlowSensorValueread-onlycurrentThe air flow measured by the sensor in tenths of a meter per minute.
1.3.6.1.4.1.52674.500.4.1.5.1.3ColumnairFlowSensorErrorStatusread-onlycurrentThe error status of the sensor. If there are no error conditions reported for the sensor, the status is normal. Otherwise, the status is reported as the severi…
1.3.6.1.4.1.52674.500.4.1.5.1.4ColumnairFlowSensorLabelread-onlycurrentThe unique label assigned to the sensor.
1.3.6.1.4.1.52674.500.4.1.5.1.5ColumnairFlowSensorEncIdread-onlycurrentThe id of the physical enclosure containing the sensor.
1.3.6.1.4.1.52674.500.4.1.5.1.6ColumnairFlowSensorPortIdread-onlycurrentThe id of the port the sensor is plugged into (or empty string if it is not plugged into a port).
1.3.6.1.4.1.52674.500.4.1.5.1.7ColumnairFlowSensorValueStrread-onlycurrentThe airflow reading, in meters per minute, shown as a string (or empty string if it is not plugged into a port).
1.3.6.1.4.1.52674.500.4.1.5.1.8ColumnairFlowSensorValueIntread-onlycurrentThe air flow measured by the sensor in meters per minute.
1.3.6.1.4.1.52674.500.4.1.5.1.9ColumnairFlowSensorIndexread-onlycurrentThe index of the sensor.
1.3.6.1.4.1.52674.500.4.1.6TableampDetectSensorTablenot-accessiblecurrentA list of amp detect sensor entries.
1.3.6.1.4.1.52674.500.4.1.6.1RowampDetectSensorEntrynot-accessiblecurrentAn ampere sensor entry.
1.3.6.1.4.1.52674.500.4.1.6.1.1ColumnampDetectSensorIdread-onlycurrentThe unique id of the sensor.
1.3.6.1.4.1.52674.500.4.1.6.1.2ColumnampDetectSensorValueread-onlycurrentThe value measured by the sensor in tenths of an ampere.
1.3.6.1.4.1.52674.500.4.1.6.1.3ColumnampDetectSensorErrorStatusread-onlycurrentThe operational status of the sensor. If there are no error conditions reported for the sensor, the status is normal. Otherwise, the status is reported as the …
1.3.6.1.4.1.52674.500.4.1.6.1.4ColumnampDetectSensorLabelread-onlycurrentThe unique label assigned to the sensor.
1.3.6.1.4.1.52674.500.4.1.6.1.5ColumnampDetectSensorEncIdread-onlycurrentThe id of the physical enclosure containing the sensor.
1.3.6.1.4.1.52674.500.4.1.6.1.6ColumnampDetectSensorPortIdread-onlycurrentThe id of the port the sensor is plugged into (or empty string if it is not plugged into a port).
1.3.6.1.4.1.52674.500.4.1.6.1.7ColumnampDetectSensorValueStrread-onlycurrentThe amp detect reading, in amperes, shown as a string (or empty string if it is not plugged into a port).
1.3.6.1.4.1.52674.500.4.1.6.1.8ColumnampDetectSensorValueIntread-onlycurrentThe value measured by the sensor in amperes.
1.3.6.1.4.1.52674.500.4.1.6.1.9ColumnampDetectSensorIndexread-onlycurrentThe index of the sensor.
1.3.6.1.4.1.52674.500.4.1.10TableotherNumericSensorTablenot-accessiblecurrentA list of other numeric sensor entries.
1.3.6.1.4.1.52674.500.4.1.10.1RowotherNumericSensorEntrynot-accessiblecurrentOther numeric sensor entry.
1.3.6.1.4.1.52674.500.4.1.10.1.1ColumnotherNumericSensorIdread-onlycurrentThe unique id of the sensor.
1.3.6.1.4.1.52674.500.4.1.10.1.2ColumnotherNumericSensorValueread-onlycurrentThe value measured by the sensor in tenths of the unit of measure.
1.3.6.1.4.1.52674.500.4.1.10.1.3ColumnotherNumericSensorErrorStatusread-onlycurrentThe operational status of the sensor. If there are no error conditions reported for the sensor, the status is normal. Otherwise, the status is reported as the …
1.3.6.1.4.1.52674.500.4.1.10.1.4ColumnotherNumericSensorLabelread-onlycurrentThe unique label assigned to the sensor.
1.3.6.1.4.1.52674.500.4.1.10.1.5ColumnotherNumericSensorEncIdread-onlycurrentThe id of the physical enclosure containing the sensor.
1.3.6.1.4.1.52674.500.4.1.10.1.6ColumnotherNumericSensorPortIdread-onlycurrentThe id of the port the sensor is plugged into (or empty string if it is not plugged into a port).
1.3.6.1.4.1.52674.500.4.1.10.1.7ColumnotherNumericSensorValueStrread-onlycurrentThe sensor reading shown as a string (or empty string if it is not plugged into a port).
1.3.6.1.4.1.52674.500.4.1.10.1.8ColumnotherNumericSensorValueIntread-onlycurrentThe value measured by the sensor in the unit of measure (1/10 of otherNumericSensorValue)
1.3.6.1.4.1.52674.500.4.1.10.1.9ColumnotherNumericSensorUnitsread-onlycurrentThe unit of measure for the sensor value.
1.3.6.1.4.1.52674.500.4.1.10.1.10ColumnotherNumericSensorValueIntX1000read-onlycurrentThe value measured by the sensor in thousandths of the unit of measure (100 times otherNumericSensorValue)
1.3.6.1.4.1.52674.500.4.1.10.1.11ColumnotherNumericSensorValueIntX1000000read-onlycurrentThe value measured by the sensor in millionths of the unit of measure (100000 times otherNumericSensorValue)
1.3.6.1.4.1.52674.500.4.1.10.1.12ColumnotherNumericSensorIndexread-onlycurrentThe index of the sensor.
1.3.6.1.4.1.52674.500.4.1.11TablerssiSensorTablenot-accessiblecurrentA list of wireless network RSSI entries.
1.3.6.1.4.1.52674.500.4.1.11.1RowrssiSensorEntrynot-accessiblecurrentRSSI sensor entry.
1.3.6.1.4.1.52674.500.4.1.11.1.1ColumnrssiSensorIdread-onlycurrentThe unique id of the sensor.
1.3.6.1.4.1.52674.500.4.1.11.1.2ColumnrssiSensorValueread-onlycurrentThe value measured by the sensor in tenths of the unit of measure.
1.3.6.1.4.1.52674.500.4.1.11.1.3ColumnrssiSensorErrorStatusread-onlycurrentThe operational status of the sensor. If there are no error conditions reported for the sensor, the status is normal. Otherwise, the status is reported as the …
1.3.6.1.4.1.52674.500.4.1.11.1.4ColumnrssiSensorLabelread-onlycurrentThe unique label assigned to the sensor.
1.3.6.1.4.1.52674.500.4.1.11.1.5ColumnrssiSensorEncIdread-onlycurrentThe id of the physical enclosure containing the sensor.
1.3.6.1.4.1.52674.500.4.1.11.1.6ColumnrssiSensorPortIdread-onlycurrentThe id of the port the sensor is plugged into (or empty string if it is not plugged into a port).
1.3.6.1.4.1.52674.500.4.1.11.1.7ColumnrssiSensorValueStrread-onlycurrentThe sensor reading shown as a string (or empty string if it is not plugged into a port).
1.3.6.1.4.1.52674.500.4.1.11.1.8ColumnrssiSensorValueIntread-onlycurrentThe value measured by the sensor in the unit of measure (1/10 of rssiSensorValue)
1.3.6.1.4.1.52674.500.4.1.11.1.9ColumnrssiSensorUnitsread-onlycurrentThe unit of measure for the sensor value.
1.3.6.1.4.1.52674.500.4.1.11.1.10ColumnrssiSensorIndexread-onlycurrentThe index of the sensor.
1.3.6.1.4.1.52674.500.4.1.12TablecurrentInputSensorTablenot-accessiblecurrentA list of current input sensor entries.
1.3.6.1.4.1.52674.500.4.1.12.1RowcurrentInputSensorEntrynot-accessiblecurrentCurrent Input sensor entry.
1.3.6.1.4.1.52674.500.4.1.12.1.1ColumncurrentInputSensorIdread-onlycurrentThe unique id of the sensor.
1.3.6.1.4.1.52674.500.4.1.12.1.2ColumncurrentInputSensorValueread-onlycurrentThe value measured by the sensor in tenths of the unit of measure.
1.3.6.1.4.1.52674.500.4.1.12.1.3ColumncurrentInputSensorErrorStatusread-onlycurrentThe operational status of the sensor. If there are no error conditions reported for the sensor, the status is normal. Otherwise, the status is reported as the …
1.3.6.1.4.1.52674.500.4.1.12.1.4ColumncurrentInputSensorLabelread-onlycurrentThe unique label assigned to the sensor.
1.3.6.1.4.1.52674.500.4.1.12.1.5ColumncurrentInputSensorEncIdread-onlycurrentThe id of the physical enclosure containing the sensor.
1.3.6.1.4.1.52674.500.4.1.12.1.6ColumncurrentInputSensorPortIdread-onlycurrentThe id of the port the sensor is plugged into (or empty string if it is not plugged into a port).
1.3.6.1.4.1.52674.500.4.1.12.1.7ColumncurrentInputSensorValueStrread-onlycurrentThe sensor reading shown as a string (or empty string if it is not plugged into a port).
1.3.6.1.4.1.52674.500.4.1.12.1.8ColumncurrentInputSensorValueIntread-onlycurrentThe value measured by the sensor in the unit of measure (1/10 of currentInputSensorValue)
1.3.6.1.4.1.52674.500.4.1.12.1.9ColumncurrentInputSensorUnitsread-onlycurrentThe unit of measure for the sensor value.
1.3.6.1.4.1.52674.500.4.1.12.1.10ColumncurrentInputSensorValueIntX1000read-onlycurrentThe value measured by the sensor in thousandths of the unit of measure (100 times currentInputSensorValue)
1.3.6.1.4.1.52674.500.4.1.12.1.11ColumncurrentInputSensorValueIntX1000000read-onlycurrentThe value measured by the sensor in millionths of the unit of measure (100000 times currentInputSensorValue)
1.3.6.1.4.1.52674.500.4.1.12.1.12ColumncurrentInputSensorIndexread-onlycurrentThe index of the sensor.
1.3.6.1.4.1.52674.500.4.1.13TablevoltageSensorTablenot-accessiblecurrentA list of current input sensor entries.
1.3.6.1.4.1.52674.500.4.1.13.1RowvoltageSensorEntrynot-accessiblecurrentVoltage sensor entry.
1.3.6.1.4.1.52674.500.4.1.13.1.1ColumnvoltageSensorIdread-onlycurrentThe unique id of the sensor.
1.3.6.1.4.1.52674.500.4.1.13.1.2ColumnvoltageSensorValueread-onlycurrentThe value measured by the sensor in tenths of the unit of measure.
1.3.6.1.4.1.52674.500.4.1.13.1.3ColumnvoltageSensorErrorStatusread-onlycurrentThe operational status of the sensor. If there are no error conditions reported for the sensor, the status is normal. Otherwise, the status is reported as the …
1.3.6.1.4.1.52674.500.4.1.13.1.4ColumnvoltageSensorLabelread-onlycurrentThe unique label assigned to the sensor.
1.3.6.1.4.1.52674.500.4.1.13.1.5ColumnvoltageSensorEncIdread-onlycurrentThe id of the physical enclosure containing the sensor.
1.3.6.1.4.1.52674.500.4.1.13.1.6ColumnvoltageSensorPortIdread-onlycurrentThe id of the port the sensor is plugged into (or empty string if it is not plugged into a port).
1.3.6.1.4.1.52674.500.4.1.13.1.7ColumnvoltageSensorValueStrread-onlycurrentThe sensor reading shown as a string (or empty string if it is not plugged into a port).
1.3.6.1.4.1.52674.500.4.1.13.1.8ColumnvoltageSensorValueIntread-onlycurrentThe value measured by the sensor in the unit of measure (1/10 of voltageSensorValue)
1.3.6.1.4.1.52674.500.4.1.13.1.9ColumnvoltageSensorUnitsread-onlycurrentThe unit of measure for the sensor value.
1.3.6.1.4.1.52674.500.4.1.13.1.10ColumnvoltageSensorValueIntX1000read-onlycurrentThe value measured by the sensor in thousandths of the unit of measure (100 times voltageSensorValue)
1.3.6.1.4.1.52674.500.4.1.13.1.11ColumnvoltageSensorValueIntX1000000read-onlycurrentThe value measured by the sensor in millionths of the unit of measure (100000 times voltageSensorValue)
1.3.6.1.4.1.52674.500.4.1.13.1.12ColumnvoltageSensorIndexread-onlycurrentThe index of the sensor.
1.3.6.1.4.1.52674.500.4.1.14TablebatterySensorTablenot-accessiblecurrentA list of current input sensor entries.
1.3.6.1.4.1.52674.500.4.1.14.1RowbatterySensorEntrynot-accessiblecurrentBattery sensor entry.
1.3.6.1.4.1.52674.500.4.1.14.1.1ColumnbatterySensorIdread-onlycurrentThe unique id of the sensor.
1.3.6.1.4.1.52674.500.4.1.14.1.2ColumnbatterySensorValueread-onlycurrentThe value measured by the sensor in tenths of the unit of measure.
1.3.6.1.4.1.52674.500.4.1.14.1.3ColumnbatterySensorErrorStatusread-onlycurrentThe operational status of the sensor. If there are no error conditions reported for the sensor, the status is normal. Otherwise, the status is reported as the …
1.3.6.1.4.1.52674.500.4.1.14.1.4ColumnbatterySensorLabelread-onlycurrentThe unique label assigned to the sensor.
1.3.6.1.4.1.52674.500.4.1.14.1.5ColumnbatterySensorEncIdread-onlycurrentThe id of the physical enclosure containing the sensor.
1.3.6.1.4.1.52674.500.4.1.14.1.6ColumnbatterySensorPortIdread-onlycurrentThe id of the port the sensor is plugged into (or empty string if it is not plugged into a port).
1.3.6.1.4.1.52674.500.4.1.14.1.7ColumnbatterySensorValueStrread-onlycurrentThe sensor reading shown as a string (or empty string if it is not plugged into a port).
1.3.6.1.4.1.52674.500.4.1.14.1.8ColumnbatterySensorValueIntread-onlycurrentThe value measured by the sensor in the unit of measure (1/10 of batterySensorValue)
1.3.6.1.4.1.52674.500.4.1.14.1.9ColumnbatterySensorUnitsread-onlycurrentThe unit of measure for the sensor value.
1.3.6.1.4.1.52674.500.4.1.14.1.10ColumnbatterySensorValueIntX1000read-onlycurrentThe value measured by the sensor in thousandths of the unit of measure (100 times batterySensorValue)
1.3.6.1.4.1.52674.500.4.1.14.1.11ColumnbatterySensorValueIntX1000000read-onlycurrentThe value measured by the sensor in millionths of the unit of measure (100000 times batterySensorValue)
1.3.6.1.4.1.52674.500.4.1.14.1.12ColumnbatterySensorIndexread-onlycurrentThe index of the sensor.
1.3.6.1.4.1.52674.500.4.2NodenetBotzStateSensors
1.3.6.1.4.1.52674.500.4.2.1TabledryContactSensorTablenot-accessiblecurrentA list of dry contact sensor entries.
1.3.6.1.4.1.52674.500.4.2.1.1RowdryContactSensorEntrynot-accessiblecurrentDry contact sensor entry.
1.3.6.1.4.1.52674.500.4.2.1.1.1ColumndryContactSensorIdread-onlycurrentThe unique id of the sensor.
1.3.6.1.4.1.52674.500.4.2.1.1.2ColumndryContactSensorValueread-onlycurrentWhether the dry sensor contact is open or closed.
1.3.6.1.4.1.52674.500.4.2.1.1.3ColumndryContactSensorErrorStatusread-onlycurrentThe operational status of the sensor. If there are no error conditions reported for the sensor, the status is normal. Otherwise, the status is reported as the …
1.3.6.1.4.1.52674.500.4.2.1.1.4ColumndryContactSensorLabelread-onlycurrentThe unique label assigned to the sensor.
1.3.6.1.4.1.52674.500.4.2.1.1.5ColumndryContactSensorEncIdread-onlycurrentThe id of the physical enclosure containing the sensor.
1.3.6.1.4.1.52674.500.4.2.1.1.6ColumndryContactSensorPortIdread-onlycurrentThe id of the port the sensor is plugged into (or empty string if it is not plugged into a port).
1.3.6.1.4.1.52674.500.4.2.1.1.7ColumndryContactSensorValueStrread-onlycurrentThe enum value label for the state reported by the sensor.
1.3.6.1.4.1.52674.500.4.2.1.1.8ColumndryContactSensorIndexread-onlycurrentThe index of the sensor.
1.3.6.1.4.1.52674.500.4.2.2TabledoorSwitchSensorTablenot-accessiblecurrentA list of door switch sensor entries.
1.3.6.1.4.1.52674.500.4.2.2.1RowdoorSwitchSensorEntrynot-accessiblecurrentDoor switch sensor entry.
1.3.6.1.4.1.52674.500.4.2.2.1.1ColumndoorSwitchSensorIdread-onlycurrentThe unique id of the sensor.
1.3.6.1.4.1.52674.500.4.2.2.1.2ColumndoorSwitchSensorValueread-onlycurrentWhether the door is open or closed.
1.3.6.1.4.1.52674.500.4.2.2.1.3ColumndoorSwitchSensorErrorStatusread-onlycurrentThe operational status of the sensor. If there are no error conditions reported for the sensor, the status is normal. Otherwise, the status is reported as the …
1.3.6.1.4.1.52674.500.4.2.2.1.4ColumndoorSwitchSensorLabelread-onlycurrentThe unique label assigned to the sensor.
1.3.6.1.4.1.52674.500.4.2.2.1.5ColumndoorSwitchSensorEncIdread-onlycurrentThe id of the physical enclosure containing the sensor.
1.3.6.1.4.1.52674.500.4.2.2.1.6ColumndoorSwitchSensorPortIdread-onlycurrentThe id of the port the sensor is plugged into (or empty string if it is not plugged into a port).
1.3.6.1.4.1.52674.500.4.2.2.1.7ColumndoorSwitchSensorValueStrread-onlycurrentThe enum value label for the state reported by the sensor.
1.3.6.1.4.1.52674.500.4.2.2.1.8ColumndoorSwitchSensorIndexread-onlycurrentThe index of the sensor.
1.3.6.1.4.1.52674.500.4.2.3TablecameraMotionSensorTablenot-accessiblecurrentA list of camera motion sensor entries.
1.3.6.1.4.1.52674.500.4.2.3.1RowcameraMotionSensorEntrynot-accessiblecurrentCamera motion sensor entry.
1.3.6.1.4.1.52674.500.4.2.3.1.1ColumncameraMotionSensorIdread-onlycurrentThe unique id of the sensor.
1.3.6.1.4.1.52674.500.4.2.3.1.2ColumncameraMotionSensorValueread-onlycurrentWhether motion is detected by the camera sensor.
1.3.6.1.4.1.52674.500.4.2.3.1.3ColumncameraMotionSensorErrorStatusread-onlycurrentThe operational status of the sensor. If there are no error conditions reported for the sensor, the status is normal. Otherwise, the status is reported as the …
1.3.6.1.4.1.52674.500.4.2.3.1.4ColumncameraMotionSensorLabelread-onlycurrentThe unique label assigned to the sensor.
1.3.6.1.4.1.52674.500.4.2.3.1.5ColumncameraMotionSensorEncIdread-onlycurrentThe id of the physical enclosure containing the sensor.
1.3.6.1.4.1.52674.500.4.2.3.1.6ColumncameraMotionSensorPortIdread-onlycurrentThe id of the port the sensor is plugged into (or empty string if it is not plugged into a port).
1.3.6.1.4.1.52674.500.4.2.3.1.7ColumncameraMotionSensorValueStrread-onlycurrentThe enum value label for the state reported by the sensor.
1.3.6.1.4.1.52674.500.4.2.3.1.8ColumncameraMotionSensorIndexread-onlycurrentThe index of the sensor.
1.3.6.1.4.1.52674.500.4.2.10TableotherStateSensorTablenot-accessiblecurrentA list of other state sensor entries.
1.3.6.1.4.1.52674.500.4.2.10.1RowotherStateSensorEntrynot-accessiblecurrentOther state sensor entry.
1.3.6.1.4.1.52674.500.4.2.10.1.1ColumnotherStateSensorIdread-onlycurrentThe unique id of the sensor.
1.3.6.1.4.1.52674.500.4.2.10.1.2ColumnotherStateSensorValueread-onlycurrentState value reported by the sensor.
1.3.6.1.4.1.52674.500.4.2.10.1.3ColumnotherStateSensorErrorStatusread-onlycurrentThe operational status of the sensor. If there are no error conditions reported for the sensor, the status is normal. Otherwise, the status is reported as the …
1.3.6.1.4.1.52674.500.4.2.10.1.4ColumnotherStateSensorLabelread-onlycurrentThe unique label assigned to the sensor.
1.3.6.1.4.1.52674.500.4.2.10.1.5ColumnotherStateSensorEncIdread-onlycurrentThe id of the physical enclosure containing the sensor.
1.3.6.1.4.1.52674.500.4.2.10.1.6ColumnotherStateSensorPortIdread-onlycurrentThe id of port the sensor is plugged into (or empty string if it is not plugged into a port).
1.3.6.1.4.1.52674.500.4.2.10.1.7ColumnotherStateSensorValueStrread-onlycurrentThe enum value label for the state reported by the sensor.
1.3.6.1.4.1.52674.500.4.2.10.1.8ColumnotherStateSensorIndexread-onlycurrentThe index of the sensor.
1.3.6.1.4.1.52674.500.4.2.11TablevibrationSensorTablenot-accessiblecurrentA list of vibration sensor entries.
1.3.6.1.4.1.52674.500.4.2.11.1RowvibrationSensorEntrynot-accessiblecurrentVibration sensor entry.
1.3.6.1.4.1.52674.500.4.2.11.1.1ColumnvibrationSensorIdread-onlycurrentThe unique id of the sensor.
1.3.6.1.4.1.52674.500.4.2.11.1.2ColumnvibrationSensorValueread-onlycurrentWhether vibration is detected.
1.3.6.1.4.1.52674.500.4.2.11.1.3ColumnvibrationSensorErrorStatusread-onlycurrentThe operational status of the sensor. If there are no error conditions reported for the sensor, the status is normal. Otherwise, the status is reported as the …
1.3.6.1.4.1.52674.500.4.2.11.1.4ColumnvibrationSensorLabelread-onlycurrentThe unique label assigned to the sensor.
1.3.6.1.4.1.52674.500.4.2.11.1.5ColumnvibrationSensorEncIdread-onlycurrentThe id of the physical enclosure containing the sensor.
1.3.6.1.4.1.52674.500.4.2.11.1.6ColumnvibrationSensorPortIdread-onlycurrentThe id of the port the sensor is plugged into (or empty string if it is not plugged into a port).
1.3.6.1.4.1.52674.500.4.2.11.1.7ColumnvibrationSensorValueStrread-onlycurrentThe enum value label for the state reported by the sensor.
1.3.6.1.4.1.52674.500.4.2.11.1.8ColumnvibrationSensorIndexread-onlycurrentThe index of the sensor.
1.3.6.1.4.1.52674.500.4.2.12TablesmokeSensorTablenot-accessiblecurrentA list of smoke sensor entries.
1.3.6.1.4.1.52674.500.4.2.12.1RowsmokeSensorEntrynot-accessiblecurrentSmoke sensor entry.
1.3.6.1.4.1.52674.500.4.2.12.1.1ColumnsmokeSensorIdread-onlycurrentThe unique id of the sensor.
1.3.6.1.4.1.52674.500.4.2.12.1.2ColumnsmokeSensorValueread-onlycurrentWhether smoke is detected.
1.3.6.1.4.1.52674.500.4.2.12.1.3ColumnsmokeSensorErrorStatusread-onlycurrentThe operational status of the sensor. If there are no error conditions reported for the sensor, the status is normal. Otherwise, the status is reported as the …
1.3.6.1.4.1.52674.500.4.2.12.1.4ColumnsmokeSensorLabelread-onlycurrentThe unique label assigned to the sensor.
1.3.6.1.4.1.52674.500.4.2.12.1.5ColumnsmokeSensorEncIdread-onlycurrentThe id of the physical enclosure containing the sensor.
1.3.6.1.4.1.52674.500.4.2.12.1.6ColumnsmokeSensorPortIdread-onlycurrentThe id of the port the sensor is plugged into (or empty string if it is not plugged into a port).
1.3.6.1.4.1.52674.500.4.2.12.1.7ColumnsmokeSensorValueStrread-onlycurrentThe enum value label for the state reported by the sensor.
1.3.6.1.4.1.52674.500.4.2.12.1.8ColumnsmokeSensorIndexread-onlycurrentThe index of the sensor.
1.3.6.1.4.1.52674.500.4.2.13TableleakSensorTablenot-accessiblecurrentA list of leak sensor entries.
1.3.6.1.4.1.52674.500.4.2.13.1RowleakSensorEntrynot-accessiblecurrentLeak sensor entry.
1.3.6.1.4.1.52674.500.4.2.13.1.1ColumnleakSensorIdread-onlycurrentThe unique id of the sensor.
1.3.6.1.4.1.52674.500.4.2.13.1.2ColumnleakSensorValueread-onlycurrentWhether a leak is detected.
1.3.6.1.4.1.52674.500.4.2.13.1.3ColumnleakSensorErrorStatusread-onlycurrentThe operational status of the sensor. If there are no error conditions reported for the sensor, the status is normal. Otherwise, the status is reported as the …
1.3.6.1.4.1.52674.500.4.2.13.1.4ColumnleakSensorLabelread-onlycurrentThe unique label assigned to the sensor.
1.3.6.1.4.1.52674.500.4.2.13.1.5ColumnleakSensorEncIdread-onlycurrentThe id of the physical enclosure containing the sensor.
1.3.6.1.4.1.52674.500.4.2.13.1.6ColumnleakSensorPortIdread-onlycurrentThe id of the port the sensor is plugged into (or empty string if it is not plugged into a port).
1.3.6.1.4.1.52674.500.4.2.13.1.7ColumnleakSensorValueStrread-onlycurrentThe enum value label for the state reported by the sensor.
1.3.6.1.4.1.52674.500.4.2.13.1.8ColumnleakSensorIndexread-onlycurrentThe index of the sensor.
1.3.6.1.4.1.52674.500.4.2.14TablebeaconTablenot-accessiblecurrentA list of beacon entries.
1.3.6.1.4.1.52674.500.4.2.14.1RowbeaconEntrynot-accessiblecurrentBeacon entry.
1.3.6.1.4.1.52674.500.4.2.14.1.1ColumnbeaconIdread-onlycurrentThe unique id of the beacon.
1.3.6.1.4.1.52674.500.4.2.14.1.2ColumnbeaconValueread-onlycurrentWhether the beacon is flashing.
1.3.6.1.4.1.52674.500.4.2.14.1.3ColumnbeaconErrorStatusread-onlycurrentThe operational status of the beacon. If there are no error conditions reported for the beacon, the status is normal. Otherwise, the status is reported as the …
1.3.6.1.4.1.52674.500.4.2.14.1.4ColumnbeaconLabelread-onlycurrentThe unique label assigned to the beacon.
1.3.6.1.4.1.52674.500.4.2.14.1.5ColumnbeaconEncIdread-onlycurrentThe id of the physical enclosure containing the beacon.
1.3.6.1.4.1.52674.500.4.2.14.1.6ColumnbeaconPortIdread-onlycurrentThe id of the port the beacon is plugged into (or empty string if it is not plugged into a port).
1.3.6.1.4.1.52674.500.4.2.14.1.7ColumnbeaconValueStrread-onlycurrentThe enum value label for the state reported by the beacon.
1.3.6.1.4.1.52674.500.4.2.14.1.8ColumnbeaconIndexread-onlycurrentThe index of the beacon.
1.3.6.1.4.1.52674.500.4.2.15TableswitchedOutletTablenot-accessiblecurrentA list of switched outlet entries.
1.3.6.1.4.1.52674.500.4.2.15.1RowswitchedOutletEntrynot-accessiblecurrentSwitched outlet entry.
1.3.6.1.4.1.52674.500.4.2.15.1.1ColumnswitchedOutletIdread-onlycurrentThe unique id of the switched outlet.
1.3.6.1.4.1.52674.500.4.2.15.1.2ColumnswitchedOutletValueread-onlycurrentWhether the switched outlet is on or off.
1.3.6.1.4.1.52674.500.4.2.15.1.3ColumnswitchedOutletErrorStatusread-onlycurrentThe operational status of the switched outlet. If there are no error conditions reported for the switched outlet, the status is normal. Otherwise, the status i…
1.3.6.1.4.1.52674.500.4.2.15.1.4ColumnswitchedOutletLabelread-onlycurrentThe unique label assigned to the switched outlet.
1.3.6.1.4.1.52674.500.4.2.15.1.5ColumnswitchedOutletEncIdread-onlycurrentThe id of the physical enclosure containing the switched outlet.
1.3.6.1.4.1.52674.500.4.2.15.1.6ColumnswitchedOutletPortIdread-onlycurrentThe id of the port the switched outlet is plugged into (or empty string if it is not plugged into a port).
1.3.6.1.4.1.52674.500.4.2.15.1.7ColumnswitchedOutletValueStrread-onlycurrentThe enum value label for the state reported by the switchedOutlet.
1.3.6.1.4.1.52674.500.4.2.15.1.8ColumnswitchedOutletIndexread-onlycurrentThe index of the switched outlet.
1.3.6.1.4.1.52674.500.4.2.16TabledoorLockSensorTablenot-accessiblecurrentA list of door lock sensor entries.
1.3.6.1.4.1.52674.500.4.2.16.1RowdoorLockSensorEntrynot-accessiblecurrentDoor lock sensor entry.
1.3.6.1.4.1.52674.500.4.2.16.1.1ColumndoorLockSensorIdread-onlycurrentThe unique id of the sensor.
1.3.6.1.4.1.52674.500.4.2.16.1.2ColumndoorLockSensorValueread-writecurrentWhen setting this object only unlocked(0) or locked(1) is valid.
1.3.6.1.4.1.52674.500.4.2.16.1.3ColumndoorLockSensorErrorStatusread-onlycurrentThe operational status of the sensor. If there are no error conditions reported for the sensor, the status is normal. Otherwise, the status is reported as the …
1.3.6.1.4.1.52674.500.4.2.16.1.4ColumndoorLockSensorLabelread-onlycurrentThe unique label assigned to the sensor.
1.3.6.1.4.1.52674.500.4.2.16.1.5ColumndoorLockSensorEncIdread-onlycurrentThe id of the physical enclosure containing the sensor.
1.3.6.1.4.1.52674.500.4.2.16.1.6ColumndoorLockSensorPortIdread-onlycurrentThe id of the port the sensor is plugged into (or empty string if it is not plugged into a port).
1.3.6.1.4.1.52674.500.4.2.16.1.7ColumndoorLockSensorValueStrread-onlycurrentThe enum value label for the state reported by the sensor.
1.3.6.1.4.1.52674.500.4.2.16.1.8ColumndoorLockSensorIndexread-onlycurrentThe index of the sensor.
1.3.6.1.4.1.52674.500.4.2.17TablerackHandleSensorTablenot-accessiblecurrentA list of rack handle sensor entries.
1.3.6.1.4.1.52674.500.4.2.17.1RowrackHandleSensorEntrynot-accessiblecurrentRack door handle sensor entry.
1.3.6.1.4.1.52674.500.4.2.17.1.1ColumnrackHandleSensorIdread-onlycurrentThe unique id of the sensor.
1.3.6.1.4.1.52674.500.4.2.17.1.2ColumnrackHandleSensorValueread-onlycurrentWhether the door is open or closed.
1.3.6.1.4.1.52674.500.4.2.17.1.3ColumnrackHandleSensorErrorStatusread-onlycurrentThe operational status of the sensor. If there are no error conditions reported for the sensor, the status is normal. Otherwise, the status is reported as the …
1.3.6.1.4.1.52674.500.4.2.17.1.4ColumnrackHandleSensorLabelread-onlycurrentThe unique label assigned to the sensor.
1.3.6.1.4.1.52674.500.4.2.17.1.5ColumnrackHandleSensorEncIdread-onlycurrentThe id of the physical enclosure containing the sensor.
1.3.6.1.4.1.52674.500.4.2.17.1.6ColumnrackHandleSensorPortIdread-onlycurrentThe id of the port the sensor is plugged into (or empty string if it is not plugged into a port).
1.3.6.1.4.1.52674.500.4.2.17.1.7ColumnrackHandleSensorValueStrread-onlycurrentThe enum value label for the state reported by the sensor.
1.3.6.1.4.1.52674.500.4.2.17.1.8ColumnrackHandleSensorIndexread-onlycurrentThe index of the sensor.
1.3.6.1.4.1.52674.500.4.2.18TableoutputRelaySensorTablenot-accessiblecurrentA list of output relay entries.
1.3.6.1.4.1.52674.500.4.2.18.1RowoutputRelaySensorEntrynot-accessiblecurrentOutput relay sensor entry.
1.3.6.1.4.1.52674.500.4.2.18.1.1ColumnoutputRelaySensorIdread-onlycurrentThe unique id of the sensor.
1.3.6.1.4.1.52674.500.4.2.18.1.2ColumnoutputRelaySensorValueread-onlycurrentWhether the relay is open or closed.
1.3.6.1.4.1.52674.500.4.2.18.1.3ColumnoutputRelaySensorErrorStatusread-onlycurrentThe operational status of the sensor. If there are no error conditions reported for the sensor, the status is normal. Otherwise, the status is reported as the …
1.3.6.1.4.1.52674.500.4.2.18.1.4ColumnoutputRelaySensorLabelread-onlycurrentThe unique label assigned to the sensor.
1.3.6.1.4.1.52674.500.4.2.18.1.5ColumnoutputRelaySensorEncIdread-onlycurrentThe id of the physical enclosure containing the sensor.
1.3.6.1.4.1.52674.500.4.2.18.1.6ColumnoutputRelaySensorPortIdread-onlycurrentThe id of the port the sensor is plugged into (or empty string if it is not plugged into a port).
1.3.6.1.4.1.52674.500.4.2.18.1.7ColumnoutputRelaySensorValueStrread-onlycurrentThe enum value label for the state reported by the sensor.
1.3.6.1.4.1.52674.500.4.2.18.1.8ColumnoutputRelaySensorIndexread-onlycurrentThe index of the sensor.
1.3.6.1.4.1.52674.500.5NodenetBotzErrors
1.3.6.1.4.1.52674.500.5.1TableerrorCondTablenot-accessiblecurrentA list of active and resolved error conditions.
1.3.6.1.4.1.52674.500.5.1.1RowerrorCondEntrynot-accessiblecurrentError condition entry.
1.3.6.1.4.1.52674.500.5.1.1.1ColumnerrorCondIdread-onlycurrentThe unique id of the error condition.
1.3.6.1.4.1.52674.500.5.1.1.2ColumnerrorCondSeverityread-onlycurrentThe relative severity of the error condition.
1.3.6.1.4.1.52674.500.5.1.1.3ColumnerrorCondTypeIdread-onlycurrentThe error type id reported for the error condition.
1.3.6.1.4.1.52674.500.5.1.1.4ColumnerrorCondStartTimeread-onlycurrentThe start time of the error condition, in msec since 1/1/1970.
1.3.6.1.4.1.52674.500.5.1.1.5ColumnerrorCondStartTimeStrread-onlycurrentThe start time of the error condition, as ISO date-time formatted string (UTC).
1.3.6.1.4.1.52674.500.5.1.1.6ColumnerrorCondResolvedread-onlycurrentWhether the error condition was resolved.
1.3.6.1.4.1.52674.500.5.1.1.7ColumnerrorCondResolvedTimeread-onlycurrentThe time the error condition was resolved (if it was resolved), in msec since 1/1/1970.
1.3.6.1.4.1.52674.500.5.1.1.8ColumnerrorCondResolvedTimeStrread-onlycurrentThe time the error condition was resolved (if it was resolved), as ISO date-time formatted string (UTC).
1.3.6.1.4.1.52674.500.5.1.1.9ColumnerrorCondEncIdread-onlycurrentThe id of the physical enclosure associated with the error.
1.3.6.1.4.1.52674.500.5.1.1.10ColumnerrorCondPortIdread-onlycurrentThe id of the port associated with the error (or empty string if the error is not associated with a port).
1.3.6.1.4.1.52674.500.5.1.1.11ColumnerrorCondSensorIdread-onlycurrentThe id of the sensor associated with the error (or empty string if the error is not associated with a sensor.)
1.3.6.1.4.1.52674.500.5.1.1.12ColumnerrorCondIndexread-onlycurrentThe index of the error condition.
1.3.6.1.4.1.52674.500.6NodenetBotzCameras
1.3.6.1.4.1.52674.500.6.1TablecameraTablenot-accessiblecurrentA list of configured camera's.
1.3.6.1.4.1.52674.500.6.1.1RowcameraEntrynot-accessiblecurrentCamera entry.
1.3.6.1.4.1.52674.500.6.1.1.1ColumncameraIdread-onlycurrentThe id of the camera.
1.3.6.1.4.1.52674.500.6.1.1.2ColumncameraVendorread-onlycurrentThe vendor of the camera.
1.3.6.1.4.1.52674.500.6.1.1.3ColumncameraModelread-onlycurrentThe model of the camera.
1.3.6.1.4.1.52674.500.6.1.1.4ColumncameraConnectionStatusread-onlycurrentThe operational status of the camera.
1.3.6.1.4.1.52674.500.6.1.1.5ColumncameraErrorStatusread-onlycurrentThe error status of the camera. If there are no error conditions reported for the camera, the status is normal. Otherwise, the status is reported as the severi…
1.3.6.1.4.1.52674.500.6.1.1.6ColumncameraLabelread-onlycurrentThe unique label assigned to the camera.
1.3.6.1.4.1.52674.500.6.1.1.7ColumncameraAddressread-onlycurrentThe address or host name of the camera.
1.3.6.1.4.1.52674.500.6.1.1.8ColumncameraIndexread-onlycurrentThe index of the physical enclosure.
1.3.6.1.4.1.52674.500.7NodenetBotzFirmware
1.3.6.1.4.1.52674.500.7.1TablefirmwareTablenot-accessiblecurrentA list of firmware versions contained in the NetBotz distribution.
1.3.6.1.4.1.52674.500.7.1.1RowfirmwareEntrynot-accessiblecurrentFirmware entry.
1.3.6.1.4.1.52674.500.7.1.1.1ColumnfirmwareDescriptionread-onlycurrentName of of the firmware product.
1.3.6.1.4.1.52674.500.7.1.1.2ColumnfirmwareVersionread-onlycurrentVersion of of the firmware product.
1.3.6.1.4.1.52674.500.7.1.1.3ColumnfirmwareIndexread-onlycurrentThe index of the firmware.
1.3.6.1.4.1.52674.500.10NodenetBotzTraps
1.3.6.1.4.1.52674.500.10.1NodenetBotzSensorTraps
1.3.6.1.4.1.52674.500.10.1.1NodenetBotzTempSensorTraps
1.3.6.1.4.1.52674.500.10.1.1.0NodenetBotzTempSensorPrefix
1.3.6.1.4.1.52674.500.10.1.1.0.1NotificationnetBotzTempErrorcurrentTemperature sensor error.
1.3.6.1.4.1.52674.500.10.1.1.0.2NotificationnetBotzTempTooHighcurrentTemperature sensor value too high.
1.3.6.1.4.1.52674.500.10.1.1.0.3NotificationnetBotzTempTooLowcurrentTemperature sensor value too low.
1.3.6.1.4.1.52674.500.10.1.1.0.6NotificationnetBotzTempUnpluggedcurrentTemperature sensor unplugged.
1.3.6.1.4.1.52674.500.10.1.1.0.101NotificationnetBotzTempErrorRTNcurrentTemperature sensor error resolved.
1.3.6.1.4.1.52674.500.10.1.1.0.102NotificationnetBotzTempTooHighRTNcurrentTemperature sensor value is no longer too high.
1.3.6.1.4.1.52674.500.10.1.1.0.103NotificationnetBotzTempTooLowRTNcurrentTemperature sensor value is no longer too low.
1.3.6.1.4.1.52674.500.10.1.1.0.106NotificationnetBotzTempRepluggedcurrentTemperature sensor no longer unplugged.
1.3.6.1.4.1.52674.500.10.1.2NodenetBotzHumiditySensorTraps
1.3.6.1.4.1.52674.500.10.1.2.0NodenetBotzHumiditySensorPrefix
1.3.6.1.4.1.52674.500.10.1.2.0.1NotificationnetBotzHumidityErrorcurrentHumidity sensor error.
1.3.6.1.4.1.52674.500.10.1.2.0.2NotificationnetBotzHumidityTooHighcurrentHumidity sensor value too high.
1.3.6.1.4.1.52674.500.10.1.2.0.3NotificationnetBotzHumidityTooLowcurrentHumidity sensor value too low.
1.3.6.1.4.1.52674.500.10.1.2.0.6NotificationnetBotzHumidityUnpluggedcurrentHumidity sensor unplugged.
1.3.6.1.4.1.52674.500.10.1.2.0.101NotificationnetBotzHumidityErrorRTNcurrentHumidity sensor error resolved.
1.3.6.1.4.1.52674.500.10.1.2.0.102NotificationnetBotzHumidityTooHighRTNcurrentHumidity sensor value is no longer too high.
1.3.6.1.4.1.52674.500.10.1.2.0.103NotificationnetBotzHumidityTooLowRTNcurrentHumidity sensor value is no longer too low.
1.3.6.1.4.1.52674.500.10.1.2.0.106NotificationnetBotzHumidityRepluggedcurrentHumidity sensor no longer unplugged.
1.3.6.1.4.1.52674.500.10.1.3NodenetBotzDewPointSensorTraps
1.3.6.1.4.1.52674.500.10.1.3.0NodenetBotzDewPointSensorPrefix
1.3.6.1.4.1.52674.500.10.1.3.0.1NotificationnetBotzDewPointErrorcurrentDewPoint sensor error.
1.3.6.1.4.1.52674.500.10.1.3.0.2NotificationnetBotzDewPointTooHighcurrentDewPoint sensor value too high.
1.3.6.1.4.1.52674.500.10.1.3.0.3NotificationnetBotzDewPointTooLowcurrentDewPoint sensor value too low.
1.3.6.1.4.1.52674.500.10.1.3.0.6NotificationnetBotzDewPointUnpluggedcurrentDewPoint sensor unplugged.
1.3.6.1.4.1.52674.500.10.1.3.0.101NotificationnetBotzDewPointErrorRTNcurrentDewPoint sensor error resolved.
1.3.6.1.4.1.52674.500.10.1.3.0.102NotificationnetBotzDewPointTooHighRTNcurrentDewPoint sensor value is no longer too high.
1.3.6.1.4.1.52674.500.10.1.3.0.103NotificationnetBotzDewPointTooLowRTNcurrentDewPoint sensor value is no longer too low.
1.3.6.1.4.1.52674.500.10.1.3.0.106NotificationnetBotzDewPointRepluggedcurrentDewPoint sensor no longer unplugged.
1.3.6.1.4.1.52674.500.10.1.4NodenetBotzAirFlowSensorTraps
1.3.6.1.4.1.52674.500.10.1.4.0NodenetBotzAirFlowSensorPrefix
1.3.6.1.4.1.52674.500.10.1.4.0.1NotificationnetBotzAirFlowErrorcurrentAirFlow sensor error.
1.3.6.1.4.1.52674.500.10.1.4.0.2NotificationnetBotzAirFlowTooHighcurrentAirFlow sensor value too high.
1.3.6.1.4.1.52674.500.10.1.4.0.3NotificationnetBotzAirFlowTooLowcurrentAirFlow sensor value too low.
1.3.6.1.4.1.52674.500.10.1.4.0.6NotificationnetBotzAirFlowUnpluggedcurrentAirFlow sensor unplugged.
1.3.6.1.4.1.52674.500.10.1.4.0.101NotificationnetBotzAirFlowErrorRTNcurrentAirFlow sensor error resolved.
1.3.6.1.4.1.52674.500.10.1.4.0.102NotificationnetBotzAirFlowTooHighRTNcurrentAirFlow sensor value is no longer too high.
1.3.6.1.4.1.52674.500.10.1.4.0.103NotificationnetBotzAirFlowTooLowRTNcurrentAirFlow sensor value is no longer too low.
1.3.6.1.4.1.52674.500.10.1.4.0.106NotificationnetBotzAirFlowRepluggedcurrentAirFlow sensor no longer unplugged.
1.3.6.1.4.1.52674.500.10.1.5NodenetBotzAmpDetectSensorTraps
1.3.6.1.4.1.52674.500.10.1.5.0NodenetBotzAmpDetectSensorPrefix
1.3.6.1.4.1.52674.500.10.1.5.0.1NotificationnetBotzAmpDetectErrorcurrentAmp Detectsensor error.
1.3.6.1.4.1.52674.500.10.1.5.0.2NotificationnetBotzAmpDetectTooHighcurrentAmp Detectsensor value too high.
1.3.6.1.4.1.52674.500.10.1.5.0.3NotificationnetBotzAmpDetectTooLowcurrentAmp Detectsensor value too low.
1.3.6.1.4.1.52674.500.10.1.5.0.6NotificationnetBotzAmpDetectUnpluggedcurrentAmp Detectsensor unplugged.
1.3.6.1.4.1.52674.500.10.1.5.0.101NotificationnetBotzAmpDetectErrorRTNcurrentAmp Detectsensor error resolved.
1.3.6.1.4.1.52674.500.10.1.5.0.102NotificationnetBotzAmpDetectTooHighRTNcurrentAmp Detectsensor value is no longer too high.
1.3.6.1.4.1.52674.500.10.1.5.0.103NotificationnetBotzAmpDetectTooLowRTNcurrentAmp Detectsensor value is no longer too low.
1.3.6.1.4.1.52674.500.10.1.5.0.106NotificationnetBotzAmpDetectRepluggedcurrentAmp Detectsensor no longer unplugged.
1.3.6.1.4.1.52674.500.10.1.6NodenetBotzDryContactSensorTraps
1.3.6.1.4.1.52674.500.10.1.6.0NodenetBotzDryContactSensorPrefix
1.3.6.1.4.1.52674.500.10.1.6.0.1NotificationnetBotzDryContactErrorcurrentDry Contact sensor error.
1.3.6.1.4.1.52674.500.10.1.6.0.6NotificationnetBotzDryContactUnpluggedcurrentDry Contact sensor unplugged.
1.3.6.1.4.1.52674.500.10.1.6.0.10NotificationnetBotzDryContactValueErrorcurrentDry Contact sensor value error.
1.3.6.1.4.1.52674.500.10.1.6.0.101NotificationnetBotzDryContactErrorRTNcurrentDry Contact sensor error resolved.
1.3.6.1.4.1.52674.500.10.1.6.0.106NotificationnetBotzDryContactRepluggedcurrentDry Contact sensor no longer unplugged.
1.3.6.1.4.1.52674.500.10.1.6.0.110NotificationnetBotzDryContactValueErrorRTNcurrentDry Contact sensor value error resolved.
1.3.6.1.4.1.52674.500.10.1.7NodenetBotzCameraMotionSensorTraps
1.3.6.1.4.1.52674.500.10.1.7.0NodenetBotzCameraMotionSensorPrefix
1.3.6.1.4.1.52674.500.10.1.7.0.1NotificationnetBotzCameraMotionSensorErrorcurrentCamera Motion Sensor error.
1.3.6.1.4.1.52674.500.10.1.7.0.6NotificationnetBotzCameraMotionSensorUnpluggedcurrentCamera Motion Sensor unplugged.
1.3.6.1.4.1.52674.500.10.1.7.0.10NotificationnetBotzCameraMotionSensorValueErrorcurrentCamera Motion Sensor value error.
1.3.6.1.4.1.52674.500.10.1.7.0.101NotificationnetBotzCameraMotionSensorErrorRTNcurrentCamera Motion Sensor error resolved.
1.3.6.1.4.1.52674.500.10.1.7.0.106NotificationnetBotzCameraMotionSensorRepluggedcurrentCamera Motion Sensor no longer unplugged.
1.3.6.1.4.1.52674.500.10.1.7.0.110NotificationnetBotzCameraMotionSensorValueErrorRTNcurrentCamera Motion Sensor value error resolved.
1.3.6.1.4.1.52674.500.10.1.8NodenetBotzDoorSensorTraps
1.3.6.1.4.1.52674.500.10.1.8.0NodenetBotzDoorSensorPrefix
1.3.6.1.4.1.52674.500.10.1.8.0.1NotificationnetBotzDoorSensorErrorcurrentDoor Sensor error.
1.3.6.1.4.1.52674.500.10.1.8.0.6NotificationnetBotzDoorSensorUnpluggedcurrentDoor Sensor unplugged.
1.3.6.1.4.1.52674.500.10.1.8.0.10NotificationnetBotzDoorSensorValueErrorcurrentDoor Sensor value error.
1.3.6.1.4.1.52674.500.10.1.8.0.101NotificationnetBotzDoorSensorErrorRTNcurrentDoor Sensor error resolved.
1.3.6.1.4.1.52674.500.10.1.8.0.106NotificationnetBotzDoorSensorRepluggedcurrentDoor Sensor no longer unplugged.
1.3.6.1.4.1.52674.500.10.1.8.0.110NotificationnetBotzDoorSensorValueErrorRTNcurrentDoor Sensor value error resolved.
1.3.6.1.4.1.52674.500.10.1.9NodenetBotzWirelessStatusSensorTraps
1.3.6.1.4.1.52674.500.10.1.9.0NodenetBotzWirelessStatusSensorPrefix
1.3.6.1.4.1.52674.500.10.1.9.0.1NotificationnetBotzWirelessStatusSensorErrorcurrentWireless Status Sensor error.
1.3.6.1.4.1.52674.500.10.1.9.0.6NotificationnetBotzWirelessStatusSensorUnpluggedcurrentWireless Status Sensor unplugged.
1.3.6.1.4.1.52674.500.10.1.9.0.10NotificationnetBotzWirelessStatusSensorValueErrorcurrentWireless Status Sensor value error.
1.3.6.1.4.1.52674.500.10.1.9.0.101NotificationnetBotzWirelessStatusSensorErrorRTNcurrentWireless Status Sensor error resolved.
1.3.6.1.4.1.52674.500.10.1.9.0.106NotificationnetBotzWirelessStatusSensorRepluggedcurrentWireless Status Sensor no longer unplugged.
1.3.6.1.4.1.52674.500.10.1.9.0.110NotificationnetBotzWirelessStatusSensorValueErrorRTNcurrentWireless Status Sensor value error resolved.
1.3.6.1.4.1.52674.500.10.1.10NodenetBotzOutputControlSensorTraps
1.3.6.1.4.1.52674.500.10.1.10.0NodenetBotzOutputControlSensorPrefix
1.3.6.1.4.1.52674.500.10.1.10.0.1NotificationnetBotzOutputControlSensorErrorcurrentOutput Control Sensor error.
1.3.6.1.4.1.52674.500.10.1.10.0.6NotificationnetBotzOutputControlSensorUnpluggedcurrentOutput Control Sensor unplugged.
1.3.6.1.4.1.52674.500.10.1.10.0.10NotificationnetBotzOutputControlSensorValueErrorcurrentOutput Control Sensor value error.
1.3.6.1.4.1.52674.500.10.1.10.0.101NotificationnetBotzOutputControlSensorErrorRTNcurrentOutput Control Sensor error resolved.
1.3.6.1.4.1.52674.500.10.1.10.0.106NotificationnetBotzOutputControlSensorRepluggedcurrentOutput Control Sensor no longer unplugged.
1.3.6.1.4.1.52674.500.10.1.10.0.110NotificationnetBotzOutputControlSensorValueErrorRTNcurrentOutput Control Sensor value error resolved.
1.3.6.1.4.1.52674.500.10.1.11NodenetBotzLoopVoltageSensorTraps
1.3.6.1.4.1.52674.500.10.1.11.0NodenetBotzLoopVoltageSensorPrefix
1.3.6.1.4.1.52674.500.10.1.11.0.1NotificationnetBotzLoopVoltageErrorcurrentLoop Voltage sensor error.
1.3.6.1.4.1.52674.500.10.1.11.0.2NotificationnetBotzLoopVoltageTooHighcurrentLoop Voltage sensor value too high.
1.3.6.1.4.1.52674.500.10.1.11.0.3NotificationnetBotzLoopVoltageTooLowcurrentLoop Voltage sensor value too low.
1.3.6.1.4.1.52674.500.10.1.11.0.6NotificationnetBotzLoopVoltageUnpluggedcurrentLoop Voltage sensor unplugged.
1.3.6.1.4.1.52674.500.10.1.11.0.101NotificationnetBotzLoopVoltageErrorRTNcurrentLoop Voltage sensor error resolved.
1.3.6.1.4.1.52674.500.10.1.11.0.102NotificationnetBotzLoopVoltageTooHighRTNcurrentLoop Voltage sensor value is no longer too high.
1.3.6.1.4.1.52674.500.10.1.11.0.103NotificationnetBotzLoopVoltageTooLowRTNcurrentLoop Voltage sensor value is no longer too low.
1.3.6.1.4.1.52674.500.10.1.11.0.106NotificationnetBotzLoopVoltageRepluggedcurrentLoop Voltage sensor no longer unplugged.
1.3.6.1.4.1.52674.500.10.1.12NodenetBotzSpotLeakSensorTraps
1.3.6.1.4.1.52674.500.10.1.12.0NodenetBotzSpotLeakSensorPrefix
1.3.6.1.4.1.52674.500.10.1.12.0.1NotificationnetBotzSpotLeakSensorErrorcurrentSpot Leak sensor error.
1.3.6.1.4.1.52674.500.10.1.12.0.6NotificationnetBotzSpotLeakSensorUnpluggedcurrentSpot Leak Sensor unplugged.
1.3.6.1.4.1.52674.500.10.1.12.0.10NotificationnetBotzSpotLeakSensorValueErrorcurrentSpot Leak sensor value error.
1.3.6.1.4.1.52674.500.10.1.12.0.101NotificationnetBotzSpotLeakSensorErrorRTNcurrentSpot Leak sensor error resolved.
1.3.6.1.4.1.52674.500.10.1.12.0.106NotificationnetBotzSpotLeakSensorRepluggedcurrentSpot Leak sensor no longer unplugged.
1.3.6.1.4.1.52674.500.10.1.12.0.110NotificationnetBotzSpotLeakSensorValueErrorRTNcurrentSpot Leak sensor value error resolved.
1.3.6.1.4.1.52674.500.10.1.13NodenetBotzRopeLeakSensorTraps
1.3.6.1.4.1.52674.500.10.1.13.0NodenetBotzRopeLeakSensorPrefix
1.3.6.1.4.1.52674.500.10.1.13.0.1NotificationnetBotzRopeLeakSensorErrorcurrentRope Leak Sensor error.
1.3.6.1.4.1.52674.500.10.1.13.0.6NotificationnetBotzRopeLeakSensorUnpluggedcurrentRope Leak Sensor unplugged.
1.3.6.1.4.1.52674.500.10.1.13.0.10NotificationnetBotzRopeLeakSensorValueErrorcurrentRope Leak Sensor value error.
1.3.6.1.4.1.52674.500.10.1.13.0.101NotificationnetBotzRopeLeakSensorErrorRTNcurrentRope Leak Sensor error resolved.
1.3.6.1.4.1.52674.500.10.1.13.0.106NotificationnetBotzRopeLeakSensorRepluggedcurrentRope Leak Sensor no longer unplugged.
1.3.6.1.4.1.52674.500.10.1.13.0.110NotificationnetBotzRopeLeakSensorValueErrorRTNcurrentRope Leak Sensor value error resolved.
1.3.6.1.4.1.52674.500.10.1.14NodenetBotzRSSISensorTraps
1.3.6.1.4.1.52674.500.10.1.14.0NodenetBotzRSSISensorPrefix
1.3.6.1.4.1.52674.500.10.1.14.0.3NotificationnetBotzRSSITooLowcurrentRSSI sensor value too low.
1.3.6.1.4.1.52674.500.10.1.14.0.10NotificationnetBotzRSSISensorValueErrorcurrentRSSI sensor value error.
1.3.6.1.4.1.52674.500.10.1.14.0.103NotificationnetBotzRSSITooLowRTNcurrentRSSI sensor value is no longer too low.
1.3.6.1.4.1.52674.500.10.1.14.0.110NotificationnetBotzRSSISensorValueErrorRTNcurrentRSSI sensor value error resolved.
1.3.6.1.4.1.52674.500.10.1.15NodenetBotzBatterySensorTraps
1.3.6.1.4.1.52674.500.10.1.15.0NodenetBotzBatterySensorPrefix
1.3.6.1.4.1.52674.500.10.1.15.0.1NotificationnetBotzBatterySensorErrorcurrentBattery sensor error.
1.3.6.1.4.1.52674.500.10.1.15.0.3NotificationnetBotzBatteryTooLowcurrentBattery sensor value too low.
1.3.6.1.4.1.52674.500.10.1.15.0.10NotificationnetBotzBatterySensorValueErrorcurrentBattery sensor value error.
1.3.6.1.4.1.52674.500.10.1.15.0.101NotificationnetBotzBatterySensorErrorRTNcurrentBattery sensor error resolved.
1.3.6.1.4.1.52674.500.10.1.15.0.103NotificationnetBotzBatteryTooLowRTNcurrentBattery sensor value is no longer too low.
1.3.6.1.4.1.52674.500.10.1.15.0.110NotificationnetBotzBatterySensorValueErrorRTNcurrentBattery sensor value error resolved.
1.3.6.1.4.1.52674.500.10.1.16NodenetBotzOutletSensorTraps
1.3.6.1.4.1.52674.500.10.1.16.0NodenetBotzOutletSensorPrefix
1.3.6.1.4.1.52674.500.10.1.16.0.1NotificationnetBotzOutletSensorErrorcurrentOutlet sensor error.
1.3.6.1.4.1.52674.500.10.1.16.0.10NotificationnetBotzOutletSensorValueErrorcurrentOutlet sensor value error.
1.3.6.1.4.1.52674.500.10.1.16.0.101NotificationnetBotzOutletSensorErrorRTNcurrentOutlet sensor error resolved.
1.3.6.1.4.1.52674.500.10.1.16.0.110NotificationnetBotzOutletSensorValueErrorRTNcurrentOutlet sensor value error resolved.
1.3.6.1.4.1.52674.500.10.1.17NodenetBotzBeaconTraps
1.3.6.1.4.1.52674.500.10.1.17.0NodenetBotzBeaconPrefix
1.3.6.1.4.1.52674.500.10.1.17.0.1NotificationnetBotzBeaconErrorcurrentBeacon error.
1.3.6.1.4.1.52674.500.10.1.17.0.6NotificationnetBotzBeaconUnpluggedcurrentBeacon unplugged.
1.3.6.1.4.1.52674.500.10.1.17.0.10NotificationnetBotzBeaconValueErrorcurrentBeacon value error.
1.3.6.1.4.1.52674.500.10.1.17.0.101NotificationnetBotzBeaconErrorRTNcurrentBeacon error resolved.
1.3.6.1.4.1.52674.500.10.1.17.0.106NotificationnetBotzBeaconRepluggedcurrentBeacon no longer unplugged.
1.3.6.1.4.1.52674.500.10.1.17.0.110NotificationnetBotzBeaconValueErrorRTNcurrentBeacon value error resolved.
1.3.6.1.4.1.52674.500.10.1.18NodenetBotzSmokeSensorTraps
1.3.6.1.4.1.52674.500.10.1.18.0NodenetBotzSmokeSensorPrefix
1.3.6.1.4.1.52674.500.10.1.18.0.1NotificationnetBotzSmokeSensorErrorcurrentSmoke sensor error.
1.3.6.1.4.1.52674.500.10.1.18.0.6NotificationnetBotzSmokeSensorUnpluggedcurrentSmoke sensor unplugged.
1.3.6.1.4.1.52674.500.10.1.18.0.10NotificationnetBotzSmokeSensorValueErrorcurrentSmoke sensor value error.
1.3.6.1.4.1.52674.500.10.1.18.0.101NotificationnetBotzSmokeSensorErrorRTNcurrentSmoke sensor error resolved.
1.3.6.1.4.1.52674.500.10.1.18.0.106NotificationnetBotzSmokeSensorRepluggedcurrentSmoke sensor replugged.
1.3.6.1.4.1.52674.500.10.1.18.0.110NotificationnetBotzSmokeSensorValueErrorRTNcurrentSmoke sensor value error resolved.
1.3.6.1.4.1.52674.500.10.1.19NodenetBotzVibrationSensorTraps
1.3.6.1.4.1.52674.500.10.1.19.0NodenetBotzVibrationSensorPrefix
1.3.6.1.4.1.52674.500.10.1.19.0.1NotificationnetBotzVibrationSensorErrorcurrentVibration sensor error.
1.3.6.1.4.1.52674.500.10.1.19.0.6NotificationnetBotzVibrationSensorUnpluggedcurrentVibration sensor unplugged.
1.3.6.1.4.1.52674.500.10.1.19.0.10NotificationnetBotzVibrationSensorValueErrorcurrentVibration sensor value error.
1.3.6.1.4.1.52674.500.10.1.19.0.101NotificationnetBotzVibrationSensorErrorRTNcurrentVibration sensor error resolved.
1.3.6.1.4.1.52674.500.10.1.19.0.106NotificationnetBotzVibrationSensorRepluggedcurrentVibration sensor replugged.
1.3.6.1.4.1.52674.500.10.1.19.0.110NotificationnetBotzVibrationSensorValueErrorRTNcurrentVibration sensor value error resolved.
1.3.6.1.4.1.52674.500.10.1.20NodenetBotzRackAccessTraps
1.3.6.1.4.1.52674.500.10.1.20.0NodenetBotzRackAccessPrefix
1.3.6.1.4.1.52674.500.10.1.20.0.10NotificationnetBotzDoorSensorForcedEntryErrorcurrentDoor sensor forced entry detected. TrapErrorTypeLabel indicates rack access user label
1.3.6.1.4.1.52674.500.10.1.20.0.11NotificationnetBotzRackHandleSensorOpenErrorcurrentRack handle sensor open error. TrapErrorTypeLabel indicates rack access user label.
1.3.6.1.4.1.52674.500.10.1.20.0.12NotificationnetBotzCardReaderLocalAuthorizationErrorcurrentCard reader local authorization failure. TrapErrorTypeLabel indicates rack access user label.
1.3.6.1.4.1.52674.500.10.1.20.0.13NotificationnetBotzCardReaderLdapAuthorizationErrorcurrentCard reader LDAP authorization failure. TrapErrorTypeLabel indicates rack access user label.
1.3.6.1.4.1.52674.500.10.1.20.0.14NotificationnetBotzCardReaderUnpluggedcurrentCard reader unplugged. TrapErrorTypeLabel indicates rack access user label.
1.3.6.1.4.1.52674.500.10.1.20.0.15NotificationnetBotzCardReaderRepluggedcurrentCard reader replugged. TrapErrorTypeLabel indicates rack access user label.
1.3.6.1.4.1.52674.500.10.1.20.0.16NotificationnetBotzCardReaderErrorcurrentCard reader error. TrapErrorTypeLabel indicates rack access user label.
1.3.6.1.4.1.52674.500.10.1.20.0.17NotificationnetBotzCardReaderErrorRTNcurrentCard reader error resolved. TrapErrorTypeLabel indicates rack access user label.
1.3.6.1.4.1.52674.500.10.1.20.0.18NotificationnetBotzCardReaderValueErrorcurrentCard reader value error. TrapErrorTypeLabel indicates rack access user label.
1.3.6.1.4.1.52674.500.10.1.20.0.19NotificationnetBotzCardReaderValueErrorRTNcurrentCard reader value error resolved. TrapErrorTypeLabel indicates rack access user label.
1.3.6.1.4.1.52674.500.10.1.20.0.20NotificationnetBotzRackHandleSensorUnpluggedcurrentRack handle sensor unplugged. TrapErrorTypeLabel indicates rack access user label.
1.3.6.1.4.1.52674.500.10.1.20.0.21NotificationnetBotzRackHandleSensorRepluggedcurrentRack handle sensor replugged. TrapErrorTypeLabel indicates rack access user label.
1.3.6.1.4.1.52674.500.10.1.20.0.22NotificationnetBotzRackHandleSensorErrorcurrentRack handle sensor error. TrapErrorTypeLabel indicates rack access user label.
1.3.6.1.4.1.52674.500.10.1.20.0.23NotificationnetBotzRackHandleSensorErrorRTNcurrentRack handle sensor error resolved. TrapErrorTypeLabel indicates rack access user label.
1.3.6.1.4.1.52674.500.10.1.20.0.24NotificationnetBotzRackHandleSensorValueErrorcurrentRack handle sensor value error. TrapErrorTypeLabel indicates rack access user label.
1.3.6.1.4.1.52674.500.10.1.20.0.25NotificationnetBotzRackHandleSensorValueErrorRTNcurrentRack handle sensor value error resolved. TrapErrorTypeLabel indicates rack access user label.
1.3.6.1.4.1.52674.500.10.1.20.0.26NotificationnetBotzLockSensorUnpluggedcurrentLock sensor unplugged. TrapErrorTypeLabel indicates rack access user label.
1.3.6.1.4.1.52674.500.10.1.20.0.27NotificationnetBotzLockSensorRepluggedcurrentLock sensor replugged. TrapErrorTypeLabel indicates rack access user label.
1.3.6.1.4.1.52674.500.10.1.20.0.28NotificationnetBotzLockSensorErrorcurrentLock sensor error. TrapErrorTypeLabel indicates rack access user label.
1.3.6.1.4.1.52674.500.10.1.20.0.29NotificationnetBotzLockSensorErrorRTNcurrentLock sensor error resolved. TrapErrorTypeLabel indicates rack access user label.
1.3.6.1.4.1.52674.500.10.1.20.0.30NotificationnetBotzLockSensorValueErrorcurrentLock sensor value error. TrapErrorTypeLabel indicates rack access user label.
1.3.6.1.4.1.52674.500.10.1.20.0.31NotificationnetBotzLockSensorValueErrorRTNcurrentLock sensor value error resolved. TrapErrorTypeLabel indicates rack access user label.
1.3.6.1.4.1.52674.500.10.1.20.0.110NotificationnetBotzDoorSensorForcedEntryErrorRTNcurrentDoor sensor forced entry returned to normal. TrapErrorTypeLabel indicates rack access user label.
1.3.6.1.4.1.52674.500.10.1.20.0.111NotificationnetBotzRackHandleSensorOpenErrorRTNcurrentRack handle sensor open returned to normal. TrapErrorTypeLabel indicates rack access user label.
1.3.6.1.4.1.52674.500.10.1.20.0.112NotificationnetBotzCardReaderLocalAuthorizationErrorRTNcurrentCard reader local authorization succeeded. TrapErrorTypeLabel indicates rack access user label.
1.3.6.1.4.1.52674.500.10.1.20.0.113NotificationnetBotzCardReaderLdapAuthorizationErrorRTNcurrentCard reader LDAP authorization succeeded. TrapErrorTypeLabel indicates rack access user label.
1.3.6.1.4.1.52674.500.10.1.99NodenetBotzTestTraps
1.3.6.1.4.1.52674.500.10.1.99.0NodenetBotzTestPrefix
1.3.6.1.4.1.52674.500.10.1.99.0.1NotificationnetBotzTestNotificationcurrentDiagnostic Test Trap.
1.3.6.1.4.1.52674.500.10.2NodenetBotzPodTraps
1.3.6.1.4.1.52674.500.10.2.0NodenetBotzPodPrefix
1.3.6.1.4.1.52674.500.10.2.0.7NotificationnetBotzPodUnpluggedcurrentPod unplugged.
1.3.6.1.4.1.52674.500.10.2.0.11NotificationnetBotzLogonErrorcurrentMultiple failed logon attempts.
1.3.6.1.4.1.52674.500.10.2.0.13NotificationnetBotzRmtLinkErrorcurrentConfigured remote link has failed.
1.3.6.1.4.1.52674.500.10.2.0.107NotificationnetBotzPodRepluggedcurrentPod no longer unplugged.
1.3.6.1.4.1.52674.500.10.2.0.111NotificationnetBotzLogonErrorResolvedcurrentFailed logon attempts stopped, or logon succeeded.
1.3.6.1.4.1.52674.500.10.2.0.113NotificationnetBotzRmtLinkErrorResolvedcurrentConfigured remote link has returned to normal.
1.3.6.1.4.1.52674.500.10.2.1NodenetBotzSensorPodTraps
1.3.6.1.4.1.52674.500.10.2.1.0NodenetBotzSensorPodPrefix
1.3.6.1.4.1.52674.500.10.2.1.0.7NotificationnetBotzSensorPodUnpluggedcurrentSensor Pod unplugged.
1.3.6.1.4.1.52674.500.10.2.1.0.107NotificationnetBotzSensorPodRepluggedcurrentSensor Pod no longer unplugged.
1.3.6.1.4.1.52674.500.10.2.2NodenetBotzCameraTraps
1.3.6.1.4.1.52674.500.10.2.2.0NodenetBotzCameraPrefix
1.3.6.1.4.1.52674.500.10.2.2.0.7NotificationnetBotzCameraUnpluggedcurrentCamera Pod unplugged.
1.3.6.1.4.1.52674.500.10.2.2.0.107NotificationnetBotzCameraRepluggedcurrentCamera Pod no longer unplugged.
1.3.6.1.4.1.52674.500.10.2.3NodenetBotz4to20mAPodTraps
1.3.6.1.4.1.52674.500.10.2.3.0NodenetBotz4to20mAPodPrefix
1.3.6.1.4.1.52674.500.10.2.3.0.1NotificationnetBotzFourToTwentymAPodErrorcurrent4-20mA Pod error.
1.3.6.1.4.1.52674.500.10.2.3.0.3NotificationnetBotzFourToTwentymAPodTooHighcurrent4-20mA Pod value too high.
1.3.6.1.4.1.52674.500.10.2.3.0.7NotificationnetBotzFourToTwentymAPodUnpluggedcurrent4-20mA Pod unplugged.
1.3.6.1.4.1.52674.500.10.2.3.0.10NotificationnetBotzFourToTwentymAPodTooLowcurrent4-20mA Pod value too low.
1.3.6.1.4.1.52674.500.10.2.3.0.101NotificationnetBotzFourToTwentymAPodErrorRTNcurrent4-20mA Pod error resolved.
1.3.6.1.4.1.52674.500.10.2.3.0.103NotificationnetBotzFourToTwentymAPodTooHighRTNcurrent4-20mA Pod value is no longer too high.
1.3.6.1.4.1.52674.500.10.2.3.0.107NotificationnetBotzFourToTwentymAPodRepluggedcurrent4-20mA Pod no longer unplugged.
1.3.6.1.4.1.52674.500.10.2.3.0.110NotificationnetBotzFourToTwentymAPodTooLowRTNcurrent4-20mA Pod value is no longer too low.
1.3.6.1.4.1.52674.500.10.3NodenetBotzRpduTraps
1.3.6.1.4.1.52674.500.10.3.0NodenetBotzRpduPrefix
1.3.6.1.4.1.52674.500.10.3.0.101NotificationnetBotzRpduUnpluggedcurrentRPDU unplugged.
1.3.6.1.4.1.52674.500.10.3.0.102NotificationnetBotzRpduRepluggedcurrentRPDU no longer unplugged.
1.3.6.1.4.1.52674.500.10.4NodenetBotzUpsTraps
1.3.6.1.4.1.52674.500.10.4.0NodenetBotzUpsPrefix
1.3.6.1.4.1.52674.500.10.4.0.103NotificationnetBotzUpsUnpluggedcurrentUPS unplugged.
1.3.6.1.4.1.52674.500.10.4.0.104NotificationnetBotzUpsRepluggedcurrentUPS no longer unplugged.
1.3.6.1.4.1.52674.500.10.5NodenetBotzGenericTraps
1.3.6.1.4.1.52674.500.10.5.0NodenetBotzGenericPrefix
1.3.6.1.4.1.52674.500.10.5.0.1NotificationnetBotzGenericNotificationcurrentGeneric Trap.
1.3.6.1.4.1.52674.500.11NodenetBotzTrapParms
1.3.6.1.4.1.52674.500.11.1ScalarnetBotzTrapErrorIDread-onlycurrentUnique ID of error condition that produced the trap
1.3.6.1.4.1.52674.500.11.2ScalarnetBotzTrapErrorTyperead-onlycurrentSymbolic ID of error type
1.3.6.1.4.1.52674.500.11.3ScalarnetBotzTrapErrorTypeLabelread-onlycurrentLabel for error type
1.3.6.1.4.1.52674.500.11.4ScalarnetBotzTrapSensorIDread-onlycurrentID of sensor associated with error condition that produced the trap
1.3.6.1.4.1.52674.500.11.5ScalarnetBotzTrapSensorLabelread-onlycurrentLabel of sensor associated with error condition that produced the trap
1.3.6.1.4.1.52674.500.11.6ScalarnetBotzTrapContainerIDread-onlycurrentID of container associated with error condition that produced the trap
1.3.6.1.4.1.52674.500.11.7ScalarnetBotzTrapContainerLabelread-onlycurrentLabel of container associated with error condition that produced the trap
1.3.6.1.4.1.52674.500.11.8ScalarnetBotzTrapPortIDread-onlycurrentID of port associated with error condition that produced the trap
1.3.6.1.4.1.52674.500.11.9ScalarnetBotzTrapPortLabelread-onlycurrentLabel of port associated with error condition that produced the trap
1.3.6.1.4.1.52674.500.11.10ScalarnetBotzTrapStartTimeread-onlycurrentStart time (in UTC seconds) for error that produced the trap
1.3.6.1.4.1.52674.500.11.11ScalarnetBotzTrapNotifyTimeread-onlycurrentNotification time (in UTC seconds) for error that produced the trap
1.3.6.1.4.1.52674.500.11.12ScalarnetBotzTrapResolveTimeread-onlycurrentResolve time (in UTC seconds) for error that produced the trap
1.3.6.1.4.1.52674.500.11.13ScalarnetBotzTrapSeverityread-onlycurrentSeverity of error that produced the trap
1.3.6.1.4.1.52674.500.11.14ScalarnetBotzTrapSensorValueread-onlycurrentString presentation of value of sensor
1.3.6.1.4.1.52674.500.11.15ScalarnetBotzTrapSensorValueIntread-onlycurrentWhole integer representation of value of sensor (without decimal portion)
1.3.6.1.4.1.52674.500.11.16ScalarnetBotzTrapSensorValueFractionread-onlycurrentFractional portion of value of sensor (multiplied by 1000000)
1.3.6.1.4.1.52674.500.11.17ScalarnetBotzTrapDataread-onlycurrentGeneral Purpose Test Trap Data String Field
1.3.6.1.4.1.52674.500.20NodenetBotzProducts
1.3.6.1.4.1.52674.500.20.10NodenetBotzBotz
1.3.6.1.4.1.52674.500.20.10.1ScalarwebServiceAPIVersionread-onlycurrentA Comma Separated List (CSV) of integers indicating the Web Service API's this system supports
1.3.6.1.4.1.52674.500.20.10.3000NodenetBotz750Rack
1.3.6.1.4.1.52674.500.20.10.3001NodenetBotz755Wall
1.3.6.1.4.1.52674.500.30NodenetbotzBotzGroups
1.3.6.1.4.1.52674.500.30.1GroupnetbotzObjectGroupcurrentA collection of netbotz stuff
1.3.6.1.4.1.52674.500.30.2GroupnetbotzNotificationGroupcurrentA collection of netbotz stuff
1.3.6.1.4.1.52674.500.100ScalarnetBotzErrorStatusread-onlycurrentThe error status of the appliance. If there are no error conditions reported for the appliance, the status is normal. Otherwise, the status is reported as the …
Type Definitions
NameSyntaxStatusDescription
BoolValueINTEGER { no(0), yes(1), null(2) }currentA boolean value.
ErrorStatusINTEGER { normal(0), info(1), warning(2), error(3), critical(4), failure(5) }currentThe error status of the device entity. If there are no error conditions reported for the entity, the status is normal. Otherwise, the status is reported as the severity value of the highest severity error condition that…
OperStatusINTEGER { disconnected(0), error(1), normal(2) }currentThe operational status of the device entity.