MIB Viewer

PDU2-MIB

905 objects
This MIB describes the SNMP functions of the Dominion PX G2 Power Distribution Unit by Raritan Computer.
Imported Objects
OIDNameAccessStatusDescription
1.3.6.1.4.1.13742IdentityraritanforThis MIB describes the SNMP functions of the Dominion PX G2 Power Distribution Unit by Raritan Computer.
1.3.6.1.4.1.13742.6Nodepdu2
1.3.6.1.4.1.13742.6.0Nodetraps
1.3.6.1.4.1.13742.6.0.0NodetrapInformation
1.3.6.1.4.1.13742.6.0.0.1TabletrapInformationTablenot-accessiblecurrentA list of Trap Information entries. The number of entries is given by the value of pduCount.
1.3.6.1.4.1.13742.6.0.0.1.1RowtrapInformationEntrynot-accessiblecurrentAn entry containing objects used in traps.
1.3.6.1.4.1.13742.6.0.0.1.1.2ColumnuserNameread-onlycurrentThe user currently logged in.
1.3.6.1.4.1.13742.6.0.0.1.1.3ColumntargetUserread-onlycurrentThe user added, deleted, or modified.
1.3.6.1.4.1.13742.6.0.0.1.1.5ColumnimageVersionread-onlycurrentThe version of the upgrade image.
1.3.6.1.4.1.13742.6.0.0.1.1.6ColumnroleNameread-onlycurrentThe role added, deleted, or modified.
1.3.6.1.4.1.13742.6.0.0.1.1.7ColumnsmtpMessageRecipientsread-onlycurrentComma separated list of SMTP Message recipients
1.3.6.1.4.1.13742.6.0.0.1.1.8ColumnsmtpServerread-onlycurrentThe IP address/host name of the SMTP server
1.3.6.1.4.1.13742.6.0.0.2ScalaroldSensorStateaccessible-for-notifycurrentThe old sensor state used in Sensor State Transition traps.
1.3.6.1.4.1.13742.6.0.0.3ScalarpduNumberaccessible-for-notifycurrentA unique value for each PDU. Its value ranges between 1 and the value of pduCount.
1.3.6.1.4.1.13742.6.0.0.5ScalarinletPoleNumberaccessible-for-notifycurrentA unique value for each inlet Pole. Its value ranges between 1 and the value of inletPoleCount.
1.3.6.1.4.1.13742.6.0.0.7ScalaroutletPoleNumberaccessible-for-notifycurrentA unique value for each outlet Pole. Its value ranges between 1 and the value of outletPoleCount.
1.3.6.1.4.1.13742.6.0.0.8ScalarexternalSensorNumberaccessible-for-notifycurrentA unique value for each external sensor. Its value ranges between 1 and the value of externalSensorCount.
1.3.6.1.4.1.13742.6.0.0.10ScalartypeOfSensoraccessible-for-notifycurrentThe type of sensor.
1.3.6.1.4.1.13742.6.0.0.11ScalarerrorDescriptionaccessible-for-notifycurrentDescription of the Error
1.3.6.1.4.1.13742.6.0.0.12ScalardeviceChangedParameteraccessible-for-notifycurrentDescription of the parameter(s) that changed.
1.3.6.1.4.1.13742.6.0.0.13ScalarchangedParameterNewValueaccessible-for-notifycurrentThe new value of the changed parameter
1.3.6.1.4.1.13742.6.0.0.14ScalarlhxSupportEnabledaccessible-for-notifycurrentThe new enabled state for Schroff LHX Support.
1.3.6.1.4.1.13742.6.0.0.15ScalarwebcamModelaccessible-for-notifycurrentThe model of the Webcam
1.3.6.1.4.1.13742.6.0.0.16ScalarwebcamConnectionPortaccessible-for-notifycurrentThe port to which the Webcam is connected
1.3.6.1.4.1.13742.6.0.0.18ScalaragentInetPortNumberaccessible-for-notifycurrentThe UDP port number used for accessing the SNMP agent on the device. Examples: If deviceCascadeType is portForwarding, then master: 50500 slave 1:50501 slave 2…
1.3.6.1.4.1.13742.6.0.0.19ScalarperipheralDeviceRomcodeaccessible-for-notifycurrentThe Romcode of an peripheral device
1.3.6.1.4.1.13742.6.0.0.20ScalarperipheralDeviceFirmwareUpdateStateaccessible-for-notifycurrentThe firmware update state of an peripheral device
1.3.6.1.4.1.13742.6.0.0.21ScalarcircuitNumberaccessible-for-notifycurrentA unique value for each circuit. circuitId is defined as follows. circuitID = 1000*(panelId) + circuitPosition Examples: 1045 is the the circuit on panel 1 wit…
1.3.6.1.4.1.13742.6.0.0.22ScalarcircuitPoleNumberaccessible-for-notifycurrentA unique value for each circuit Pole.
1.3.6.1.4.1.13742.6.0.0.23ScalarphoneNumberaccessible-for-notifycurrentThe phone number of e.g. an SMS receiver.
1.3.6.1.4.1.13742.6.0.1NotificationsystemStartedcurrentThe system has started.
1.3.6.1.4.1.13742.6.0.2NotificationsystemResetcurrentThe system was reset. The conditions under which this trap is sent include, but are not limited to, the following. using the GUI - Maintenance->Reset Unit usin…
1.3.6.1.4.1.13742.6.0.3NotificationuserLogincurrentA user logged in.
1.3.6.1.4.1.13742.6.0.4NotificationuserLogoutcurrentA user logged out.
1.3.6.1.4.1.13742.6.0.5NotificationuserAuthenticationFailurecurrentA user authentication attempt failed.
1.3.6.1.4.1.13742.6.0.8NotificationuserSessionTimeoutcurrentA user session timed out.
1.3.6.1.4.1.13742.6.0.11NotificationuserAddedcurrentA user was added to the system.
1.3.6.1.4.1.13742.6.0.12NotificationuserModifiedcurrentA user was modified.
1.3.6.1.4.1.13742.6.0.13NotificationuserDeletedcurrentA user was deleted from the system.
1.3.6.1.4.1.13742.6.0.14NotificationroleAddedcurrentA role was added to the system.
1.3.6.1.4.1.13742.6.0.15NotificationroleModifiedcurrentA role was modified.
1.3.6.1.4.1.13742.6.0.16NotificationroleDeletedcurrentA role was deleted from the system.
1.3.6.1.4.1.13742.6.0.20NotificationdeviceUpdateStartedcurrentThe device update has started.
1.3.6.1.4.1.13742.6.0.21NotificationdeviceUpdateCompletedcurrentThe device update has completed.
1.3.6.1.4.1.13742.6.0.22NotificationuserBlockedcurrentA blocked user tried to log in.
1.3.6.1.4.1.13742.6.0.23NotificationpowerControlcurrentAn outlet switching operation has been performed. Note that measurementsOutletSensorState represents the state of the outlet at the time the trap was sent. Thi…
1.3.6.1.4.1.13742.6.0.24NotificationuserPasswordChangedcurrentUser password was changed.
1.3.6.1.4.1.13742.6.0.28NotificationpasswordSettingsChangedcurrentStrong password settings changed.
1.3.6.1.4.1.13742.6.0.38NotificationfirmwareValidationFailedcurrentFirmware validation failed.
1.3.6.1.4.1.13742.6.0.41NotificationlogFileClearedcurrentThe log file has been cleared.
1.3.6.1.4.1.13742.6.0.53NotificationbulkConfigurationSavedcurrentBulk Configuration saved.
1.3.6.1.4.1.13742.6.0.54NotificationbulkConfigurationCopiedcurrentBulk Configuration copied to the device.
1.3.6.1.4.1.13742.6.0.60NotificationpduSensorStateChangedeprecatedPDU Sensor State Change. Which value field to use depends on the metadata of the sensor. measurementsUnitSensorValue is undefined for sensors which can have ne…
1.3.6.1.4.1.13742.6.0.61NotificationinletSensorStateChangecurrentInlet Sensor State Change. Which value field to use depends on the metadata of the sensor. measurementsInletSensorValue is undefined for sensors which can have…
1.3.6.1.4.1.13742.6.0.62NotificationinletPoleSensorStateChangecurrentInlet Pole Sensor State Change. Which value field to use depends on the metadata of the sensor. measurementsInletPoleSensorValue is undefined for sensors which…
1.3.6.1.4.1.13742.6.0.63NotificationoutletSensorStateChangecurrentOutlet Sensor State Change. Which value field to use depends on the metadata of the sensor. measurementsOutletSensorValue is undefined for sensors which can ha…
1.3.6.1.4.1.13742.6.0.64NotificationoutletPoleSensorStateChangecurrentOutlet Pole Sensor State Change. Which value field to use depends on the metadata of the sensor. measurementsOutletPoleSensorValue is undefined for sensors whi…
1.3.6.1.4.1.13742.6.0.65NotificationoverCurrentProtectorSensorStateChangecurrentOvercurrent Protector Sensor State Change. Which value field to use depends on the metadata of the sensor. measurementsOverCurrentProtectorSensorValue is undef…
1.3.6.1.4.1.13742.6.0.66NotificationexternalSensorStateChangecurrentExternal Sensor State Change.
1.3.6.1.4.1.13742.6.0.67NotificationsmtpMessageTransmissionFailurecurrentSMTP message transmission failure
1.3.6.1.4.1.13742.6.0.68NotificationldapErrorcurrentLDAP Error occurred; errorDescription describes the error
1.3.6.1.4.1.13742.6.0.70NotificationdeviceUpdateFailedcurrentThe device update has failed.
1.3.6.1.4.1.13742.6.0.71NotificationloadSheddingModeEnteredcurrentThe PX has enetered Load Shedding Mode
1.3.6.1.4.1.13742.6.0.72NotificationloadSheddingModeExitedcurrentThe PX has exited Load Shedding Mode
1.3.6.1.4.1.13742.6.0.73NotificationpingServerEnabledcurrentThe ping feature has been enabled
1.3.6.1.4.1.13742.6.0.74NotificationpingServerDisabledcurrentThe ping feature has been disabled
1.3.6.1.4.1.13742.6.0.75NotificationserverNotReachablecurrentThe server is not reachable
1.3.6.1.4.1.13742.6.0.76NotificationserverReachablecurrentThe server is reachable
1.3.6.1.4.1.13742.6.0.77NotificationrfCodeTagConnectedcurrentThe RF Code Tag is Connected
1.3.6.1.4.1.13742.6.0.78NotificationrfCodeTagDisconnectedcurrentThe RF Code Tag is Disconnected
1.3.6.1.4.1.13742.6.0.79NotificationdeviceIdentificationChangedcurrentDevice identification has changed
1.3.6.1.4.1.13742.6.0.80NotificationusbSlaveConnectedcurrentUSB Connectivity to slave has been established
1.3.6.1.4.1.13742.6.0.81NotificationusbSlaveDisconnectedcurrentUSB Connectivity to slave has been lost
1.3.6.1.4.1.13742.6.0.82NotificationlhxSupportChangedcurrentThe Schroff LHX Support has been either enabled or disabled.
1.3.6.1.4.1.13742.6.0.83NotificationuserAcceptedRestrictedServiceAgreementcurrentThe user accepted the Restricted Service Agreement.
1.3.6.1.4.1.13742.6.0.84NotificationuserDeclinedRestrictedServiceAgreementcurrentThe user declined the Restricted Service Agreement.
1.3.6.1.4.1.13742.6.0.85NotificationwireSensorStateChangedeprecatedWire Sensor State Change.
1.3.6.1.4.1.13742.6.0.86NotificationtransferSwitchSensorStateChangecurrentTransfer Switch Sensor State Change. Which value field to use depends on the metadata of the sensor. measurementsTransferSwitchSensorValue is undefined for sen…
1.3.6.1.4.1.13742.6.0.88NotificationdeviceSettingsSavedcurrentDevice Settings have been saved.
1.3.6.1.4.1.13742.6.0.89NotificationdeviceSettingsRestoredcurrentDevice Settings have been restored.
1.3.6.1.4.1.13742.6.0.90NotificationwebcamInsertedcurrentA webcam has been inserted
1.3.6.1.4.1.13742.6.0.91NotificationwebcamRemovedcurrentA webcam has been removed
1.3.6.1.4.1.13742.6.0.92NotificationinletEnabledcurrentPDU operation has been enabled for an inlet
1.3.6.1.4.1.13742.6.0.93NotificationinletDisabledcurrentPDU operation has been disabled for an inlet
1.3.6.1.4.1.13742.6.0.94NotificationserverConnectivityUnrecoverablecurrentThe connection to the server could not be recovered
1.3.6.1.4.1.13742.6.0.95NotificationradiusErrorcurrentLDAP Error occurred; errorDescription describes the error
1.3.6.1.4.1.13742.6.0.96NotificationserverReachabilityErrorcurrentServer Reachability Error occurred; errorDescription describes the error. This trap is sent when the Error state is entered. Reasons for transitioning to the E…
1.3.6.1.4.1.13742.6.0.97NotificationinletSensorResetcurrentAn inlet sensor was reset.
1.3.6.1.4.1.13742.6.0.98NotificationoutletSensorResetcurrentAn outlet sensor was reset.
1.3.6.1.4.1.13742.6.0.99NotificationunknownPeripheralDeviceAttachedcurrentAn unknown peripheral device was attached.
1.3.6.1.4.1.13742.6.0.100NotificationperipheralDeviceFirmwareUpdatecurrentThe firmware update state of a peripheral device changed while performing update to peripheralDevicePackageFirmwareVersion.
1.3.6.1.4.1.13742.6.0.101NotificationunitSensorResetcurrentA global sensor was reset.
1.3.6.1.4.1.13742.6.0.102NotificationunitSensorStateChangecurrentUnit Sensor State Change. Which value field to use depends on the metadata of the sensor. measurementsUnitSensorValue is undefined for sensors which can have n…
1.3.6.1.4.1.13742.6.0.103NotificationcircuitSensorStateChangecurrentcircuit Sensor State Change. Which value field to use depends on the metadata of the sensor. measurementsOutletSensorValue is undefined for sensors which can h…
1.3.6.1.4.1.13742.6.0.104NotificationcircuitPoleSensorStateChangecurrentCircuit Pole Sensor State Change. Which value field to use depends on the metadata of the sensor. measurementsOutletPoleSensorValue is undefined for sensors wh…
1.3.6.1.4.1.13742.6.0.105NotificationcircuitAddedcurrentA Circuit has been added
1.3.6.1.4.1.13742.6.0.106NotificationcircuitDeletedcurrentA Circuit has been deleted
1.3.6.1.4.1.13742.6.0.107NotificationcircuitModifiedcurrentA Circuit has been modified
1.3.6.1.4.1.13742.6.0.108NotificationcircuitSensorResetcurrentAn ciruit sensor was reset.
1.3.6.1.4.1.13742.6.0.109NotificationpowerMeterAddedcurrentA Power Meter has been added
1.3.6.1.4.1.13742.6.0.110NotificationpowerMeterDeletedcurrentA Power Meter has been deleted
1.3.6.1.4.1.13742.6.0.111NotificationpowerMeterModifiedcurrentA Power Meter has been modified
1.3.6.1.4.1.13742.6.0.112NotificationsmsMessageTransmissionFailurecurrentSending an SMS message failed.
1.3.6.1.4.1.13742.6.1Nodeboard
1.3.6.1.4.1.13742.6.2Nodeenvironmental
1.3.6.1.4.1.13742.6.3Nodeconfiguration
1.3.6.1.4.1.13742.6.3.1ScalarpduCountread-onlycurrentFor a PX2/3 and transfer switch, pduCount = 1 For a BCM2, pduCount = number of power meters + 1 (for the main controller)
1.3.6.1.4.1.13742.6.3.2Nodeunit
1.3.6.1.4.1.13742.6.3.2.1TablenameplateTablenot-accessiblecurrentA list of PDU nameplate entries. The number of entries is given by the value of pduCount.
1.3.6.1.4.1.13742.6.3.2.1.1RownameplateEntrynot-accessiblecurrentAn entry providing PDU nameplate information.
1.3.6.1.4.1.13742.6.3.2.1.1.1ColumnpduIdnot-accessiblecurrentA unique value for each PDU/Power meter. PX2/3 and transfer switch: pduiId = 1 BCM2: main controller: pduId = 0 power meter: pduId = rotary switch setting for …
1.3.6.1.4.1.13742.6.3.2.1.1.2ColumnpduManufacturerread-onlycurrentThe PDU manaufacturer.
1.3.6.1.4.1.13742.6.3.2.1.1.3ColumnpduModelread-onlycurrentThe PDU model.
1.3.6.1.4.1.13742.6.3.2.1.1.4ColumnpduSerialNumberread-onlycurrentThe PDU serial Number.
1.3.6.1.4.1.13742.6.3.2.1.1.5ColumnpduRatedVoltageread-onlycurrentThe PDU voltage rating.
1.3.6.1.4.1.13742.6.3.2.1.1.6ColumnpduRatedCurrentread-onlycurrentThe PDU current rating.
1.3.6.1.4.1.13742.6.3.2.1.1.7ColumnpduRatedFrequencyread-onlycurrentThe PDU frequency rating.
1.3.6.1.4.1.13742.6.3.2.1.1.8ColumnpduRatedVAread-onlycurrentThe PDU VA (VoltAmps) rating.
1.3.6.1.4.1.13742.6.3.2.1.1.9ColumnpduImageread-onlycurrentThe URL of the wiring diagram for this PDU.
1.3.6.1.4.1.13742.6.3.2.2TableunitConfigurationTablenot-accessiblecurrentA list of PDU configuration entries. The number of entries is given by the value of pduCount.
1.3.6.1.4.1.13742.6.3.2.2.1RowunitConfigurationEntrynot-accessiblecurrentAn entry containing configuration objects for a particular PDU.
1.3.6.1.4.1.13742.6.3.2.2.1.2ColumninletCountread-onlycurrentThe number of inlets.
1.3.6.1.4.1.13742.6.3.2.2.1.3ColumnoverCurrentProtectorCountread-onlycurrentThe number of overcurrent protectors.
1.3.6.1.4.1.13742.6.3.2.2.1.4ColumnoutletCountread-onlycurrentThe number of outlets.
1.3.6.1.4.1.13742.6.3.2.2.1.5ColumninletControllerCountread-onlycurrentThe number of inlet controllers.
1.3.6.1.4.1.13742.6.3.2.2.1.6ColumnoutletControllerCountread-onlycurrentThe number of outlet controllers.
1.3.6.1.4.1.13742.6.3.2.2.1.7ColumnexternalSensorCountread-onlycurrentThe number of external sensors.
1.3.6.1.4.1.13742.6.3.2.2.1.8ColumnpxIPAddressread-onlydeprecatedThe current IP address. A value of 0.0.0.0 indicates an error or an unset option.
1.3.6.1.4.1.13742.6.3.2.2.1.9Columnnetmaskread-onlydeprecatedThe current netmask. A value of 0.0.0.0 indicates an error or an unset option.
1.3.6.1.4.1.13742.6.3.2.2.1.10Columngatewayread-onlydeprecatedThe current gateway. A value of 0.0.0.0 indicates an error or an unset option.
1.3.6.1.4.1.13742.6.3.2.2.1.11ColumnpxMACAddressread-onlycurrentThe current MAC address.
1.3.6.1.4.1.13742.6.3.2.2.1.12ColumnutcOffsetread-onlycurrentThe current UTC offset.
1.3.6.1.4.1.13742.6.3.2.2.1.13ColumnpduNameread-writecurrentThe user-defined name for the PDU.
1.3.6.1.4.1.13742.6.3.2.2.1.14ColumnnetworkInterfaceTyperead-onlycurrentThe network interface type: wired or wireless.
1.3.6.1.4.1.13742.6.3.2.2.1.34ColumnexternalSensorsZCoordinateUnitsread-writecurrentExternal Sensor Z Coordinate units: Freeform Text or Rack Units (U) Default is U.
1.3.6.1.4.1.13742.6.3.2.2.1.35ColumnunitDeviceCapabilitiesread-onlycurrentA bit string which indicates which unit sensors are available.
1.3.6.1.4.1.13742.6.3.2.2.1.36ColumnoutletSequencingDelayread-writedeprecatedIt is deprecated. This is an alias for inrushGuardDelay
1.3.6.1.4.1.13742.6.3.2.2.1.37ColumnglobalOutletPowerCyclingPowerOffPeriodread-writecurrentThe power-off period when an outlet is cycled; applies to all outlets unless overridden at the outlet level; specified in seconds; 0 <= value <= 3600 seconds.
1.3.6.1.4.1.13742.6.3.2.2.1.38ColumnglobalOutletStateOnStartupread-writecurrentThe outlet state on device startup; applies to all outlets unless overridden at the outlet level. Note that this value is ignored if relayBehaviorOnPowerLoss i…
1.3.6.1.4.1.13742.6.3.2.2.1.39ColumnoutletPowerupSequenceread-writecurrentThe sequence in which will the outlets will be switched on under the following conditions. 1) Switch all outlets on operation is executed 2) Power to the PDU i…
1.3.6.1.4.1.13742.6.3.2.2.1.40ColumnpduPowerCyclingPowerOffPeriodread-writecurrentWhen power to the PX is cycled (either manually or because of a temporary power loss), this number determines how many seconds the PX will wait before it provi…
1.3.6.1.4.1.13742.6.3.2.2.1.41ColumnpduDaisychainMemberTyperead-onlycurrentThe daisy chain member type.
1.3.6.1.4.1.13742.6.3.2.2.1.42ColumnmanagedExternalSensorCountread-onlycurrentThe number of managed external sensors
1.3.6.1.4.1.13742.6.3.2.2.1.50ColumnpxInetAddressTyperead-onlydeprecatedThe type of address format This object is deprecated in favor of ipAddressTable from the IP-MIB (rfc4293).
1.3.6.1.4.1.13742.6.3.2.2.1.51ColumnpxInetIPAddressread-onlydeprecatedThe current IP address. A value of 0.0.0.0 indicates an error or an unset option. This object is deprecated in favor of ipAddressTable from the IP-MIB (rfc4293…
1.3.6.1.4.1.13742.6.3.2.2.1.52ColumnpxInetNetmaskread-onlydeprecatedThe current netmask. A value of 0.0.0.0 indicates an error or an unset option. This object is deprecated in favor of ipAddressTable from the IP-MIB (rfc4293). …
1.3.6.1.4.1.13742.6.3.2.2.1.53ColumnpxInetGatewayread-onlydeprecatedThe current gateway. A value of 0.0.0.0 indicates an error or an unset option. This object is deprecated in favor of ipAddressTable from the IP-MIB (rfc4293). …
1.3.6.1.4.1.13742.6.3.2.2.1.55ColumnloadSheddingread-writecurrentEnter/Exit Load Shedding Mode
1.3.6.1.4.1.13742.6.3.2.2.1.56ColumnserverCountread-onlycurrentThe number of servers
1.3.6.1.4.1.13742.6.3.2.2.1.57ColumninrushGuardDelayread-writecurrentThe time interval between switching on two outlets; specified in milliseconds; 100 <= value <= 100000 milliseconds.
1.3.6.1.4.1.13742.6.3.2.2.1.58ColumncascadedDeviceConnectedread-onlycurrentIndicates whether another PX2 is connected using an USB cable to the USB-A port of this PX2 in a cascaded configuration. true: Connected false: Not Connected
1.3.6.1.4.1.13742.6.3.2.2.1.59ColumnsynchronizeWithNTPServerread-writecurrentWill time be obtained using NTP? true: time will be obtained using NTP servers false: time will not be obtained using NTP servers Deafault is false.
1.3.6.1.4.1.13742.6.3.2.2.1.60ColumnuseDHCPProvidedNTPServerread-writecurrentWill the NTP server addresses be provided by DHCP/BOOTP? This is used only if synchronizeWithNTPServer is enabled Default is enabled, i.e. DHCP provided NTP se…
1.3.6.1.4.1.13742.6.3.2.2.1.61ColumnfirstNTPServerAddressTyperead-writecurrentRepresents the type of the corresponding instance of firstNTPServerAddress object.
1.3.6.1.4.1.13742.6.3.2.2.1.62ColumnfirstNTPServerAddressread-writecurrentThe address of the primary ntp server.
1.3.6.1.4.1.13742.6.3.2.2.1.63ColumnsecondNTPServerAddressTyperead-writecurrentRepresents the type of the corresponding instance of secondNTPServerAddress object. Default is ipv4
1.3.6.1.4.1.13742.6.3.2.2.1.64ColumnsecondNTPServerAddressread-writecurrentThe address of the second ntp server.
1.3.6.1.4.1.13742.6.3.2.2.1.65ColumnwireCountread-onlydeprecatedThe number of wires.
1.3.6.1.4.1.13742.6.3.2.2.1.66ColumntransferSwitchCountread-onlycurrentThe number of transfer switches.
1.3.6.1.4.1.13742.6.3.2.2.1.67ColumnproductTyperead-onlycurrentThe product type. Is this product a PDU, STS, BCM,...?
1.3.6.1.4.1.13742.6.3.2.2.1.68ColumnmeteringControllerCountread-onlycurrentThe number of metering controllers.
1.3.6.1.4.1.13742.6.3.2.2.1.69ColumnrelayBehaviorOnPowerLossread-writecurrentThe relay behavior on power loss.
1.3.6.1.4.1.13742.6.3.2.2.1.70ColumndeviceCascadeTyperead-writecurrentThe configured type of cascading: default is bridging. This can be set only if the unit is the master.
1.3.6.1.4.1.13742.6.3.2.2.1.71ColumndeviceCascadePositionread-onlycurrentThe position of the device in the cascaded chain. 0: master >= 1: slaves
1.3.6.1.4.1.13742.6.3.2.2.1.72ColumnperipheralDevicesAutoManagementread-writecurrentAuto-management enabled state for peripheral devices.
1.3.6.1.4.1.13742.6.3.2.2.1.73ColumnfrontPanelOutletSwitchingread-writecurrentEnables/disables switching of outlets using the PDU front panel.
1.3.6.1.4.1.13742.6.3.2.2.1.74ColumnfrontPanelRCMSelfTestread-writecurrentEnables/disables front panel RCM self-test.
1.3.6.1.4.1.13742.6.3.2.2.1.75ColumnfrontPanelActuatorControlread-writecurrentEnables/disables front panel peripheral actuator control.
1.3.6.1.4.1.13742.6.3.2.2.1.76ColumncircuitCountread-onlycurrentThe number of user configured circuits in the panel.
1.3.6.1.4.1.13742.6.3.2.2.1.77ColumnactiveDNSServerCountread-onlycurrentThe number of active DNS Servers
1.3.6.1.4.1.13742.6.3.2.3TablecontrollerConfigurationTablenot-accessiblecurrentA list of entries for the boards in each PDU. The number of entries is given by the value of inletControllerCount + outletControllerCount + 1 (for main control…
1.3.6.1.4.1.13742.6.3.2.3.1RowcontrollerConfigurationEntrynot-accessiblecurrentAn entry containing objects for a controller.
1.3.6.1.4.1.13742.6.3.2.3.1.1ColumnboardTypenot-accessiblecurrentThe type of board.
1.3.6.1.4.1.13742.6.3.2.3.1.2ColumnboardIndexnot-accessiblecurrentA unique value for each controller. Its value ranges between 1 and the value of inletControllerCount + outletControllerCount + 1.
1.3.6.1.4.1.13742.6.3.2.3.1.4ColumnboardVersionread-onlycurrentThe board hardware version.
1.3.6.1.4.1.13742.6.3.2.3.1.6ColumnboardFirmwareVersionread-onlycurrentThe firmware version.
1.3.6.1.4.1.13742.6.3.2.3.1.8ColumnboardFirmwareTimeStampread-onlycurrentThe time when the board firmware was updated in UNIX(epoch)time. It is measured in seconds relative to January 1, 1970 (midnight UTC/GMT), i.e a value of 0 ind…
1.3.6.1.4.1.13742.6.3.2.4TablelogConfigurationTablenot-accessiblecurrentA table of parameters for the data logging feature. The number of entries is given by the value of pduCount.
1.3.6.1.4.1.13742.6.3.2.4.1RowlogConfigurationEntrynot-accessiblecurrentAn entry containing data logging parameters for a particular PDU.
1.3.6.1.4.1.13742.6.3.2.4.1.1ColumndataLoggingread-writecurrentData Retrieval: enabled/disabled.
1.3.6.1.4.1.13742.6.3.2.4.1.2ColumnmeasurementPeriodread-onlycurrentData Collection periodicity. This is the periodicity of the data collected by the PX. This value is fixed at 1 second.
1.3.6.1.4.1.13742.6.3.2.4.1.3ColumnmeasurementsPerLogEntryread-writecurrentThe number of measurements used for each entry in the log.
1.3.6.1.4.1.13742.6.3.2.4.1.4ColumnlogSizeread-onlycurrentThe number of entries in the log.
1.3.6.1.4.1.13742.6.3.2.4.1.5ColumndataLoggingEnableForAllSensorsread-writecurrentOperation to control data logging for all sensors. If this OID is set to true, then all xxxSensorLogAvailable are set to true If this OID is set to false, then…
1.3.6.1.4.1.13742.6.3.2.5TableunitSensorConfigurationTablenot-accessiblecurrentA list of unit level sensors for a PDU.
1.3.6.1.4.1.13742.6.3.2.5.1RowunitSensorConfigurationEntrynot-accessiblecurrentAn entry containing unit sensor parameters.
1.3.6.1.4.1.13742.6.3.2.5.1.1ColumnsensorTypenot-accessiblecurrentThe type of sensor.
1.3.6.1.4.1.13742.6.3.2.5.1.4ColumnunitSensorLogAvailableread-writecurrentIs logging enabled for the sensor?
1.3.6.1.4.1.13742.6.3.2.5.1.6ColumnunitSensorUnitsread-onlycurrentThe units in which the sensor data is reported.
1.3.6.1.4.1.13742.6.3.2.5.1.7ColumnunitSensorDecimalDigitsread-onlycurrentThe number of digits displayed to the right of the decimal point.
1.3.6.1.4.1.13742.6.3.2.5.1.8ColumnunitSensorAccuracyread-onlydeprecatedThe accuracy: how close (in percent) the measurement is to the actual value.
1.3.6.1.4.1.13742.6.3.2.5.1.9ColumnunitSensorResolutionread-onlycurrentThe resolution: the minimum difference between any two measured values The value of this OID variable should be scaled by unitSensorDecimalDigits. For example,…
1.3.6.1.4.1.13742.6.3.2.5.1.10ColumnunitSensorToleranceread-onlydeprecatedThe resolution: the difference between a sensor value and the actual value The value of this OID variable should be scaled by (unitSensorDecimalDigits + 1). Fo…
1.3.6.1.4.1.13742.6.3.2.5.1.11ColumnunitSensorMaximumread-onlycurrentThe largest possible reading as an unsigned integer. The value of this OID variable should be scaled by unitSensorDecimalDigits. For example, if the value is 1…
1.3.6.1.4.1.13742.6.3.2.5.1.12ColumnunitSensorMinimumread-onlycurrentThe smallest possible reading as an unsigned integer. The value of this OID variable should be scaled by unitSensorDecimalDigits. For example, if the value is …
1.3.6.1.4.1.13742.6.3.2.5.1.13ColumnunitSensorHysteresisread-writecurrentThe hysteresis used for deassertions The value of this OID variable should be scaled by unitSensorDecimalDigits. For example, if the value is 1 and unitSensorD…
1.3.6.1.4.1.13742.6.3.2.5.1.14ColumnunitSensorStateChangeDelayread-writecurrentThe delay measured in samples before a state is asserted. If the value is zero, then the state is asserted as soon as it is detected; if it is non-zero, say n,…
1.3.6.1.4.1.13742.6.3.2.5.1.21ColumnunitSensorLowerCriticalThresholdread-writecurrentThe lower critical threshold as an unsigned integer. The value of this OID variable should be scaled by unitSensorDecimalDigits. For example, if the value is 1…
1.3.6.1.4.1.13742.6.3.2.5.1.22ColumnunitSensorLowerWarningThresholdread-writecurrentThe lower warning threshold as an unsigned integer. The value of this OID variable should be scaled by unitSensorDecimalDigits. For example, if the value is 1 …
1.3.6.1.4.1.13742.6.3.2.5.1.23ColumnunitSensorUpperCriticalThresholdread-writecurrentThe upper critical threshold as an unsigned integer. The value of this OID variable should be scaled by unitSensorDecimalDigits. For example, if the value is 1…
1.3.6.1.4.1.13742.6.3.2.5.1.24ColumnunitSensorUpperWarningThresholdread-writecurrentThe upper warning threshold as an unsigned integer. The value of this OID variable should be scaled by unitSensorDecimalDigits. For example, if the value is 1 …
1.3.6.1.4.1.13742.6.3.2.5.1.25ColumnunitSensorEnabledThresholdsread-writecurrentA bit string which indicates which thresholds are enabled. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.2.5.1.26ColumnunitSensorSignedMaximumread-onlycurrentThe largest possible reading as a signed integer. The value of this OID variable should be scaled by unitSensorDecimalDigits. For example, if the value is 1 an…
1.3.6.1.4.1.13742.6.3.2.5.1.27ColumnunitSensorSignedMinimumread-onlycurrentThe smallest possible reading as a signed integer. The value of this OID variable should be scaled by unitSensorDecimalDigits. For example, if the value is 1 a…
1.3.6.1.4.1.13742.6.3.2.5.1.28ColumnunitSensorSignedLowerCriticalThresholdread-writecurrentThe lower critical threshold as a signed integer. The value of this OID variable should be scaled by unitSensorDecimalDigits. For example, if the value is 1 an…
1.3.6.1.4.1.13742.6.3.2.5.1.29ColumnunitSensorSignedLowerWarningThresholdread-writecurrentThe lower warning threshold as a signed integer. The value of this OID variable should be scaled by unitSensorDecimalDigits. For example, if the value is 1 and…
1.3.6.1.4.1.13742.6.3.2.5.1.30ColumnunitSensorSignedUpperCriticalThresholdread-writecurrentThe upper critical threshold as a signed integer. The value of this OID variable should be scaled by unitSensorDecimalDigits. For example, if the value is 1 an…
1.3.6.1.4.1.13742.6.3.2.5.1.31ColumnunitSensorSignedUpperWarningThresholdread-writecurrentThe upper warning threshold as a signed integer. The value of this OID variable should be scaled by unitSensorDecimalDigits. For example, if the value is 1 and…
1.3.6.1.4.1.13742.6.3.2.6TableactiveDNSServerTablenot-accessiblecurrentA list of active DNS server entries. The number of rows in the table is given by the value of activeDNSServerCount (from unitConfigurationTable). If activeDNSS…
1.3.6.1.4.1.13742.6.3.2.6.1RowactiveDNSServerEntrynot-accessiblecurrentAn entry containing the active DNS servers for a particular PDU.
1.3.6.1.4.1.13742.6.3.2.6.1.2ColumnactiveDNSServerIndexnot-accessiblecurrentA unique value for a dns Server. Its value ranges between 1 and activeDNSServerCount.
1.3.6.1.4.1.13742.6.3.2.6.1.3ColumnactiveDNSServerAddressTyperead-onlycurrentRepresents the type of the corresponding instance of activeDNSServerAddress object.
1.3.6.1.4.1.13742.6.3.2.6.1.4ColumnactiveDNSServerAddressread-onlycurrentThe address of the dns server.
1.3.6.1.4.1.13742.6.3.2.6.1.5ColumnactiveDNSServerAddressSourceread-onlycurrentHow was the address obtained: static, dhcp, dhcpv6?
1.3.6.1.4.1.13742.6.3.3Nodeinlets
1.3.6.1.4.1.13742.6.3.3.3TableinletConfigurationTablenot-accessiblecurrentA list of inlet configuration entries. The number of entries is given by the value of inletCount for the PDU.
1.3.6.1.4.1.13742.6.3.3.3.1RowinletConfigurationEntrynot-accessiblecurrentAn entry containing parametersfor a particular inlet.
1.3.6.1.4.1.13742.6.3.3.3.1.1ColumninletIdnot-accessiblecurrentA unique value for each inlet. Its value ranges between 1 and the value of inletCount.
1.3.6.1.4.1.13742.6.3.3.3.1.2ColumninletLabelread-onlycurrentThe label on the PDU identifying the inlet.
1.3.6.1.4.1.13742.6.3.3.3.1.3ColumninletNameread-writecurrentThe user-defined name.
1.3.6.1.4.1.13742.6.3.3.3.1.4ColumninletPlugread-onlycurrentThe type of plug/receptacle wired to the inlet.
1.3.6.1.4.1.13742.6.3.3.3.1.5ColumninletPoleCountread-onlycurrentThe number of poles. PDU: 2 for 1-phase circuits 3 for 3-phase DELTA wired models; 4 for 3-phase WYE wired models; Pole 4 is neutral; Note that sensors are not…
1.3.6.1.4.1.13742.6.3.3.3.1.6ColumninletRatedVoltageread-onlycurrentThe inlet voltage rating.
1.3.6.1.4.1.13742.6.3.3.3.1.7ColumninletRatedCurrentread-onlycurrentThe inlet current rating.
1.3.6.1.4.1.13742.6.3.3.3.1.8ColumninletRatedFrequencyread-onlydeprecatedThe inlet frequency rating. Deprecated: use pduRatedFrequency for unit nameplate information.
1.3.6.1.4.1.13742.6.3.3.3.1.9ColumninletRatedVAread-onlydeprecatedThe inlet VA (VoltAmps) rating. Deprecated: use pduRatedVA for unit nameplate information.
1.3.6.1.4.1.13742.6.3.3.3.1.10ColumninletDeviceCapabilitiesread-onlycurrentA bit string which indicates which inlet sensors are available.
1.3.6.1.4.1.13742.6.3.3.3.1.11ColumninletPoleCapabilitiesread-onlycurrentA bit string which indicates which inletpole sensors are available.
1.3.6.1.4.1.13742.6.3.3.3.1.12ColumninletPlugDescriptorread-onlycurrentDescription of the Plug
1.3.6.1.4.1.13742.6.3.3.3.1.13ColumninletEnableStateread-writecurrentIs this PDU operation is enabled for this inlet? When PDU operation is disabled the sensors for this inlet and all children will no longer be updated, and outl…
1.3.6.1.4.1.13742.6.3.3.3.1.14ColumninletRCMResidualOperatingCurrentread-writecurrentThe Residual Operating Current (Threshold) for the RCM State sensor. For inlets without an RCM, any attempt to access this OID will return NoSuchInstance error…
1.3.6.1.4.1.13742.6.3.3.4TableinletSensorConfigurationTablenot-accessiblecurrentA list of configuration entries for an inlet sensor.
1.3.6.1.4.1.13742.6.3.3.4.1RowinletSensorConfigurationEntrynot-accessiblecurrentAn entry containing objects for configuring an inlet sensor.
1.3.6.1.4.1.13742.6.3.3.4.1.4ColumninletSensorLogAvailableread-writecurrentIs logging enabled for the sensor?
1.3.6.1.4.1.13742.6.3.3.4.1.6ColumninletSensorUnitsread-onlycurrentThe base units. This parameter does not apply to sensors without numerical reading, e.g. surge protector status sensors.
1.3.6.1.4.1.13742.6.3.3.4.1.7ColumninletSensorDecimalDigitsread-onlycurrentThe number of digits displayed to the right of the decimal point. This parameter does not apply to sensors without numerical reading, e.g. surge protector stat…
1.3.6.1.4.1.13742.6.3.3.4.1.8ColumninletSensorAccuracyread-onlydeprecatedThe accuracy: how close (in percent) the measurement is to the actual value. This parameter does not apply to sensors without numerical reading, e.g. surge pro…
1.3.6.1.4.1.13742.6.3.3.4.1.9ColumninletSensorResolutionread-onlycurrentThe resolution: the minimum difference between any two measured values The value of this OID variable should be scaled by inletSensorDecimalDigits. For example…
1.3.6.1.4.1.13742.6.3.3.4.1.10ColumninletSensorToleranceread-onlydeprecatedThe resolution: the difference between a sensor value and the actual value The value of this OID variable should be scaled by (inletSensorDecimalDigits + 1). F…
1.3.6.1.4.1.13742.6.3.3.4.1.11ColumninletSensorMaximumread-onlycurrentThe largest possible reading as an unsigned integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is …
1.3.6.1.4.1.13742.6.3.3.4.1.12ColumninletSensorMinimumread-onlycurrentThe smallest possible reading as an unsigned integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is…
1.3.6.1.4.1.13742.6.3.3.4.1.13ColumninletSensorHysteresisread-writecurrentThe hysteresis used for deassertions The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1 and inletSenso…
1.3.6.1.4.1.13742.6.3.3.4.1.14ColumninletSensorStateChangeDelayread-writecurrentThe delay measured in samples before a state is asserted. If the value is zero, then the state is asserted as soon as it is detected; if it is non-zero, say n,…
1.3.6.1.4.1.13742.6.3.3.4.1.21ColumninletSensorLowerCriticalThresholdread-writecurrentThe lower critical threshold as an unsigned integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is …
1.3.6.1.4.1.13742.6.3.3.4.1.22ColumninletSensorLowerWarningThresholdread-writecurrentThe lower warning threshold as an unsigned integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1…
1.3.6.1.4.1.13742.6.3.3.4.1.23ColumninletSensorUpperCriticalThresholdread-writecurrentThe upper critical threshold as an unsigned integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is …
1.3.6.1.4.1.13742.6.3.3.4.1.24ColumninletSensorUpperWarningThresholdread-writecurrentThe upper warning threshold as an unsigned integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1…
1.3.6.1.4.1.13742.6.3.3.4.1.25ColumninletSensorEnabledThresholdsread-writecurrentA bit string which indicates which thresholds are enabled. This parameter does not apply to sensors without numerical reading, e.g. surge protector status sens…
1.3.6.1.4.1.13742.6.3.3.4.1.26ColumninletSensorSignedMaximumread-onlycurrentThe largest possible reading as a signed integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1 a…
1.3.6.1.4.1.13742.6.3.3.4.1.27ColumninletSensorSignedMinimumread-onlycurrentThe smallest possible reading as a signed integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1 …
1.3.6.1.4.1.13742.6.3.3.4.1.28ColumninletSensorSignedLowerCriticalThresholdread-writecurrentThe lower critical threshold as a signed integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1 a…
1.3.6.1.4.1.13742.6.3.3.4.1.29ColumninletSensorSignedLowerWarningThresholdread-writecurrentThe lower warning threshold as a signed integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1 an…
1.3.6.1.4.1.13742.6.3.3.4.1.30ColumninletSensorSignedUpperCriticalThresholdread-writecurrentThe upper critical threshold as a signed integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1 a…
1.3.6.1.4.1.13742.6.3.3.4.1.31ColumninletSensorSignedUpperWarningThresholdread-writecurrentThe upper warning threshold as a signed integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1 an…
1.3.6.1.4.1.13742.6.3.3.5TableinletPoleConfigurationTablenot-accessiblecurrentA list of inlet pole configuration entries. The number of entries is given by the value of inletPoleCount for the PDU.
1.3.6.1.4.1.13742.6.3.3.5.1RowinletPoleConfigurationEntrynot-accessiblecurrentAn entry containing parametersfor a particular inlet pole.
1.3.6.1.4.1.13742.6.3.3.5.1.1ColumninletPoleLineread-onlycurrentThe Phase for this inlet Pole.
1.3.6.1.4.1.13742.6.3.3.5.1.2ColumninletPoleNoderead-onlycurrentThe node to which this inlet pole is connected
1.3.6.1.4.1.13742.6.3.3.6TableinletPoleSensorConfigurationTablenot-accessiblecurrentA list of configuration entries for an inlet pole sensor.
1.3.6.1.4.1.13742.6.3.3.6.1RowinletPoleSensorConfigurationEntrynot-accessiblecurrentAn entry containing objects for configuring an inlet pole sensor.
1.3.6.1.4.1.13742.6.3.3.6.1.1ColumninletPoleIndexnot-accessiblecurrentA unique value for each inlet Pole. Its value ranges between 1 and the value of inletPoleCount.
1.3.6.1.4.1.13742.6.3.3.6.1.4ColumninletPoleSensorLogAvailableread-writecurrentIs logging enabled for the sensor?
1.3.6.1.4.1.13742.6.3.3.6.1.6ColumninletPoleSensorUnitsread-onlycurrentThe base units. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.3.6.1.7ColumninletPoleSensorDecimalDigitsread-onlycurrentThe number of digits displayed to the right of the decimal point. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.3.6.1.8ColumninletPoleSensorAccuracyread-onlydeprecatedThe accuracy: how close (in percent) the measurement is to the actual value. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.3.6.1.9ColumninletPoleSensorResolutionread-onlycurrentThe resolution: the minimum difference between any two measured values The value of this OID variable should be scaled by inletPoleSensorDecimalDigits. For exa…
1.3.6.1.4.1.13742.6.3.3.6.1.10ColumninletPoleSensorToleranceread-onlydeprecatedThe resolution: the difference between a sensor value and the actual value The value of this OID variable should be scaled by (inletPoleSensorDecimalDigits + 1…
1.3.6.1.4.1.13742.6.3.3.6.1.11ColumninletPoleSensorMaximumread-onlycurrentThe largest possible reading as an unsigned integer. The value of this OID variable should be scaled by inletPoleSensorDecimalDigits. For example, if the value…
1.3.6.1.4.1.13742.6.3.3.6.1.12ColumninletPoleSensorMinimumread-onlycurrentThe smallest possible reading as an unsigned integer. The value of this OID variable should be scaled by inletPoleSensorDecimalDigits. For example, if the valu…
1.3.6.1.4.1.13742.6.3.3.6.1.13ColumninletPoleSensorHysteresisread-writecurrentThe hysteresis used for deassertions The value of this OID variable should be scaled by inletPoleSensorDecimalDigits. For example, if the value is 1 and inletP…
1.3.6.1.4.1.13742.6.3.3.6.1.14ColumninletPoleSensorStateChangeDelayread-writecurrentThe delay measured in samples before a state is asserted. If the value is zero, then the state is asserted as soon as it is detected; if it is non-zero, say n,…
1.3.6.1.4.1.13742.6.3.3.6.1.21ColumninletPoleSensorLowerCriticalThresholdread-writecurrentThe lower critical threshold as an unsigned integer. The value of this OID variable should be scaled by inletPoleSensorDecimalDigits. For example, if the value…
1.3.6.1.4.1.13742.6.3.3.6.1.22ColumninletPoleSensorLowerWarningThresholdread-writecurrentThe lower warning threshold as an unsigned integer. The value of this OID variable should be scaled by inletPoleSensorDecimalDigits. For example, if the value …
1.3.6.1.4.1.13742.6.3.3.6.1.23ColumninletPoleSensorUpperCriticalThresholdread-writecurrentThe upper critical threshold as an unsigned integer. The value of this OID variable should be scaled by inletPoleSensorDecimalDigits. For example, if the value…
1.3.6.1.4.1.13742.6.3.3.6.1.24ColumninletPoleSensorUpperWarningThresholdread-writecurrentThe upper warning threshold as an unsigned integer. The value of this OID variable should be scaled by inletPoleSensorDecimalDigits. For example, if the value …
1.3.6.1.4.1.13742.6.3.3.6.1.25ColumninletPoleSensorEnabledThresholdsread-writecurrentA bit string which indicates which thresholds are enabled. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.3.6.1.26ColumninletPoleSensorSignedMaximumread-onlycurrentThe largest possible reading as a signed integer. The value of this OID variable should be scaled by inletPoleSensorDecimalDigits. For example, if the value is…
1.3.6.1.4.1.13742.6.3.3.6.1.27ColumninletPoleSensorSignedMinimumread-onlycurrentThe smallest possible reading as a signed integer. The value of this OID variable should be scaled by inletPoleSensorDecimalDigits. For example, if the value i…
1.3.6.1.4.1.13742.6.3.3.6.1.28ColumninletPoleSensorSignedLowerCriticalThresholdread-writecurrentThe lower critical threshold as a signed integer. The value of this OID variable should be scaled by inletPoleSensorDecimalDigits. For example, if the value is…
1.3.6.1.4.1.13742.6.3.3.6.1.29ColumninletPoleSensorSignedLowerWarningThresholdread-writecurrentThe lower warning threshold as a signed integer. The value of this OID variable should be scaled by inletPoleSensorDecimalDigits. For example, if the value is …
1.3.6.1.4.1.13742.6.3.3.6.1.30ColumninletPoleSensorSignedUpperCriticalThresholdread-writecurrentThe upper critical threshold as a signed integer. The value of this OID variable should be scaled by inletPoleSensorDecimalDigits. For example, if the value is…
1.3.6.1.4.1.13742.6.3.3.6.1.31ColumninletPoleSensorSignedUpperWarningThresholdread-writecurrentThe upper warning threshold as a signed integer. The value of this OID variable should be scaled by inletPoleSensorDecimalDigits. For example, if the value is …
1.3.6.1.4.1.13742.6.3.4NodeoverCurrentProtector
1.3.6.1.4.1.13742.6.3.4.3TableoverCurrentProtectorConfigurationTablenot-accessiblecurrentA list of overCurrentProtector configuration entries. The number of entries is given by the value of overCurrentProtectorCount for the PDU.
1.3.6.1.4.1.13742.6.3.4.3.1RowoverCurrentProtectorConfigurationEntrynot-accessiblecurrentAn entry containing objects for a particular overCurrentProtector.
1.3.6.1.4.1.13742.6.3.4.3.1.1ColumnoverCurrentProtectorIndexnot-accessiblecurrentA unique value for each overcurrent protector. Its value ranges between 1 and the value of overCurrentProtectorCount.
1.3.6.1.4.1.13742.6.3.4.3.1.2ColumnoverCurrentProtectorLabelread-onlycurrentThe label on the PDU identifying the overcurrent protector.
1.3.6.1.4.1.13742.6.3.4.3.1.3ColumnoverCurrentProtectorNameread-writecurrentThe user-defined name.
1.3.6.1.4.1.13742.6.3.4.3.1.4ColumnoverCurrentProtectorTyperead-onlycurrentThe type of overcurrent protector.
1.3.6.1.4.1.13742.6.3.4.3.1.5ColumnoverCurrentProtectorRatedCurrentread-onlycurrentThe current rating.
1.3.6.1.4.1.13742.6.3.4.3.1.6ColumnoverCurrentProtectorPoleCountread-onlycurrentThe number of overCurrentProtector poles.
1.3.6.1.4.1.13742.6.3.4.3.1.9ColumnoverCurrentProtectorCapabilitiesread-onlycurrentA bit string which indicates which overcurrent protector sensors are available.
1.3.6.1.4.1.13742.6.3.4.3.1.10ColumnoverCurrentProtectorPowerSourceread-onlycurrentThis object allows discovery of how the PDU is wired. It indicates the overCurrentProtector's power source which can one of the following: overCurrentProtector…
1.3.6.1.4.1.13742.6.3.4.4TableoverCurrentProtectorSensorConfigurationTablenot-accessiblecurrentA list of overCurrentProtectorSensor configuration entries.
1.3.6.1.4.1.13742.6.3.4.4.1RowoverCurrentProtectorSensorConfigurationEntrynot-accessiblecurrentAn overCurrentProtectorSensor entry containing objects for a particular overCurrentProtector Sensor.
1.3.6.1.4.1.13742.6.3.4.4.1.4ColumnoverCurrentProtectorSensorLogAvailableread-writecurrentIs logging available for this sensor?
1.3.6.1.4.1.13742.6.3.4.4.1.6ColumnoverCurrentProtectorSensorUnitsread-onlycurrentThe base units This parameter does not apply to sensors without numerical reading, e.g. trip sensors.
1.3.6.1.4.1.13742.6.3.4.4.1.7ColumnoverCurrentProtectorSensorDecimalDigitsread-onlycurrentThe number of digits displayed to the right of the decimal point. This parameter does not apply to sensors without numerical reading, e.g. trip sensors.
1.3.6.1.4.1.13742.6.3.4.4.1.8ColumnoverCurrentProtectorSensorAccuracyread-onlydeprecatedThe accuracy: how close (in percent) the measurement is to the actual value This parameter does not apply to sensors without numerical reading, e.g. trip senso…
1.3.6.1.4.1.13742.6.3.4.4.1.9ColumnoverCurrentProtectorSensorResolutionread-onlycurrentThe resolution: the minimum difference between any two measured values The value of this OID variable should be scaled by overCurrentProtectorSensorDecimalDigi…
1.3.6.1.4.1.13742.6.3.4.4.1.10ColumnoverCurrentProtectorSensorToleranceread-onlydeprecatedThe resolution: the difference between a sensor value and the actual value The value of this OID variable should be scaled by (overCurrentProtectorSensorDecima…
1.3.6.1.4.1.13742.6.3.4.4.1.11ColumnoverCurrentProtectorSensorMaximumread-onlycurrentThe largest possible reading as an unsigned integer. The value of this OID variable should be scaled by overCurrentProtectorSensorDecimalDigits. For example, i…
1.3.6.1.4.1.13742.6.3.4.4.1.12ColumnoverCurrentProtectorSensorMinimumread-onlycurrentThe smallest possible reading as an unsigned integer. The value of this OID variable should be scaled by overCurrentProtectorSensorDecimalDigits. For example, …
1.3.6.1.4.1.13742.6.3.4.4.1.13ColumnoverCurrentProtectorSensorHysteresisread-writecurrentThe hysteresis used for deassertions The value of this OID variable should be scaled by overCurrentProtectorSensorDecimalDigits. For example, if the value is 1…
1.3.6.1.4.1.13742.6.3.4.4.1.14ColumnoverCurrentProtectorSensorStateChangeDelayread-writecurrentThe delay measured in samples before a state is asserted. If the value is zero, then the state is asserted as soon as it is detected; if it is non-zero, say n,…
1.3.6.1.4.1.13742.6.3.4.4.1.21ColumnoverCurrentProtectorSensorLowerCriticalThresholdread-writecurrentThe lower critical threshold as an unsigned integer. The value of this OID variable should be scaled by overCurrentProtectorSensorDecimalDigits. For example, i…
1.3.6.1.4.1.13742.6.3.4.4.1.22ColumnoverCurrentProtectorSensorLowerWarningThresholdread-writecurrentThe lower warning threshold as an unsigned integer. The value of this OID variable should be scaled by overCurrentProtectorSensorDecimalDigits. For example, if…
1.3.6.1.4.1.13742.6.3.4.4.1.23ColumnoverCurrentProtectorSensorUpperCriticalThresholdread-writecurrentThe upper critical threshold as an unsigned integer. The value of this OID variable should be scaled by overCurrentProtectorSensorDecimalDigits. For example, i…
1.3.6.1.4.1.13742.6.3.4.4.1.24ColumnoverCurrentProtectorSensorUpperWarningThresholdread-writecurrentThe upper warning threshold as an unsigned integer. The value of this OID variable should be scaled by overCurrentProtectorSensorDecimalDigits. For example, if…
1.3.6.1.4.1.13742.6.3.4.4.1.25ColumnoverCurrentProtectorSensorEnabledThresholdsread-writecurrentA bit string which indicates which thresholds are enabled. This parameter does not apply to sensors without numerical reading, e.g. trip sensors.
1.3.6.1.4.1.13742.6.3.4.4.1.26ColumnoverCurrentProtectorSensorSignedMaximumread-onlycurrentThe largest possible reading as a signed integer. The value of this OID variable should be scaled by overCurrentProtectorSensorDecimalDigits. For example, if t…
1.3.6.1.4.1.13742.6.3.4.4.1.27ColumnoverCurrentProtectorSensorSignedMinimumread-onlycurrentThe smallest possible reading as a signed integer. The value of this OID variable should be scaled by overCurrentProtectorSensorDecimalDigits. For example, if …
1.3.6.1.4.1.13742.6.3.4.4.1.28ColumnoverCurrentProtectorSensorSignedLowerCriticalThresholdread-writecurrentThe lower critical threshold as a signed integer. The value of this OID variable should be scaled by overCurrentProtectorSensorDecimalDigits. For example, if t…
1.3.6.1.4.1.13742.6.3.4.4.1.29ColumnoverCurrentProtectorSensorSignedLowerWarningThresholdread-writecurrentThe lower warning threshold as a signed integer. The value of this OID variable should be scaled by overCurrentProtectorSensorDecimalDigits. For example, if th…
1.3.6.1.4.1.13742.6.3.4.4.1.30ColumnoverCurrentProtectorSensorSignedUpperCriticalThresholdread-writecurrentThe upper critical threshold as a signed integer. The value of this OID variable should be scaled by overCurrentProtectorSensorDecimalDigits. For example, if t…
1.3.6.1.4.1.13742.6.3.4.4.1.31ColumnoverCurrentProtectorSensorSignedUpperWarningThresholdread-writecurrentThe upper warning threshold as a signed integer. The value of this OID variable should be scaled by overCurrentProtectorSensorDecimalDigits. For example, if th…
1.3.6.1.4.1.13742.6.3.4.5TableoverCurrentProtectorPoleConfigurationTablenot-accessiblecurrentA list of overCurrentProtector pole configuration entries. The number of entries is given by the value of overCurrentProtectorPoleCount for the PDU.
1.3.6.1.4.1.13742.6.3.4.5.1RowoverCurrentProtectorPoleConfigurationEntrynot-accessiblecurrentAn entry containing parametersfor a particular overCurrentProtector pole.
1.3.6.1.4.1.13742.6.3.4.5.1.1ColumnoverCurrentProtectorPoleIndexnot-accessiblecurrentA unique value for each overCurrentProtector Pole. Its value ranges between 1 and the value of overCurrentProtectorPoleCount.
1.3.6.1.4.1.13742.6.3.4.5.1.2ColumnoverCurrentProtectorPoleLineread-onlycurrentThe Phase for this overCurrentProtector Pole.
1.3.6.1.4.1.13742.6.3.4.5.1.3ColumnoverCurrentProtectorPoleInNoderead-onlycurrentThe node to which this overCurrentProtector pole input is connected
1.3.6.1.4.1.13742.6.3.4.5.1.4ColumnoverCurrentProtectorPoleOutNoderead-onlycurrentThe node to which this overCurrentProtector pole output is connected
1.3.6.1.4.1.13742.6.3.5Nodeoutlets
1.3.6.1.4.1.13742.6.3.5.3TableoutletConfigurationTablenot-accessiblecurrentA list of outlet configuration entries. The number of entries is given by the value of outletCount for the PDU.
1.3.6.1.4.1.13742.6.3.5.3.1RowoutletConfigurationEntrynot-accessiblecurrentAn outlet entry containing parameters for a particular outlet.
1.3.6.1.4.1.13742.6.3.5.3.1.1ColumnoutletIdnot-accessiblecurrentA unique value for each outlet. Its value ranges between 1 and the value of outletCount.
1.3.6.1.4.1.13742.6.3.5.3.1.2ColumnoutletLabelread-onlycurrentThe label on the PDU identifying the outlet.
1.3.6.1.4.1.13742.6.3.5.3.1.3ColumnoutletNameread-writecurrentThe user-defined name.
1.3.6.1.4.1.13742.6.3.5.3.1.4ColumnoutletReceptacleread-onlycurrentThe plug.
1.3.6.1.4.1.13742.6.3.5.3.1.5ColumnoutletPoleCountread-onlycurrentThe number of poles.
1.3.6.1.4.1.13742.6.3.5.3.1.6ColumnoutletRatedVoltageread-onlycurrentThe outlet voltage rating.
1.3.6.1.4.1.13742.6.3.5.3.1.7ColumnoutletRatedCurrentread-onlycurrentThe outlet current rating.
1.3.6.1.4.1.13742.6.3.5.3.1.8ColumnoutletRatedVAread-onlycurrentThe outlet VA (VoltAmps) rating.
1.3.6.1.4.1.13742.6.3.5.3.1.10ColumnoutletDeviceCapabilitiesread-onlycurrentA bit string which indicates which outlet sensors are available.
1.3.6.1.4.1.13742.6.3.5.3.1.11ColumnoutletPoleCapabilitiesread-onlycurrentA bit string which indicates which outlet pole sensors are available.
1.3.6.1.4.1.13742.6.3.5.3.1.12ColumnoutletPowerCyclingPowerOffPeriodread-writecurrentThe power-off period when an outlet is cycled; overrides the global value; specified in seconds; 0 <= value <= 3600 seconds.
1.3.6.1.4.1.13742.6.3.5.3.1.13ColumnoutletStateOnStartupread-writecurrentThe outlet state on device startup; overrides the global value. Note that this value is ignored if relayBehaviorOnPowerLoss is set to latching.
1.3.6.1.4.1.13742.6.3.5.3.1.14ColumnoutletUseGlobalPowerCyclingPowerOffPeriodread-writecurrentIf this true, then use globalOutletPowerCyclingPowerOffPeriod.
1.3.6.1.4.1.13742.6.3.5.3.1.28ColumnoutletSwitchableread-onlycurrentIs this outlet switchable?
1.3.6.1.4.1.13742.6.3.5.3.1.29ColumnoutletReceptacleDescriptorread-onlycurrentDescription of the Receptacle
1.3.6.1.4.1.13742.6.3.5.3.1.30ColumnoutletNonCriticalread-writecurrentIs this outlet non-critical?
1.3.6.1.4.1.13742.6.3.5.3.1.32ColumnoutletSequenceDelayread-writecurrentThe time interval between switching on this outlet and the next outlet in the outlet sequence. This applies to the following operations. 1) Switch all outlets …
1.3.6.1.4.1.13742.6.3.5.3.1.33ColumnoutletPowerSourceread-onlycurrentThis object allows discovery of how the PDU is wired. It indicates the outlet's power source which can one of the following: overCurrentProtector transfer swit…
1.3.6.1.4.1.13742.6.3.5.4TableoutletSensorConfigurationTablenot-accessiblecurrentA list of outlet configuration entries. The number of entries is given by the value of outletCount for the PDU.
1.3.6.1.4.1.13742.6.3.5.4.1RowoutletSensorConfigurationEntrynot-accessiblecurrentAn entry containing parameters for an outlet sensor.
1.3.6.1.4.1.13742.6.3.5.4.1.4ColumnoutletSensorLogAvailableread-writecurrentIs logging available for this sensor?
1.3.6.1.4.1.13742.6.3.5.4.1.6ColumnoutletSensorUnitsread-onlycurrentThe base units. This parameter does not apply to sensors without numerical reading, e.g. outlet state sensors.
1.3.6.1.4.1.13742.6.3.5.4.1.7ColumnoutletSensorDecimalDigitsread-onlycurrentThe number of digits displayed to the right of the decimal point This parameter does not apply to sensors without numerical reading, e.g. outlet state sensors.
1.3.6.1.4.1.13742.6.3.5.4.1.8ColumnoutletSensorAccuracyread-onlydeprecatedThe accuracy: how close (in percent) the measurement is to the actual value This parameter does not apply to sensors without numerical reading, e.g. outlet sta…
1.3.6.1.4.1.13742.6.3.5.4.1.9ColumnoutletSensorResolutionread-onlycurrentThe resolution: the minimum difference between any two measured values The value of this OID variable should be scaled by outletSensorDecimalDigits. For exampl…
1.3.6.1.4.1.13742.6.3.5.4.1.10ColumnoutletSensorToleranceread-onlydeprecatedThe resolution: the difference between a sensor value and the actual value The value of this OID variable should be scaled by (outletSensorDecimalDigits + 1). …
1.3.6.1.4.1.13742.6.3.5.4.1.11ColumnoutletSensorMaximumread-onlycurrentThe largest possible reading as an unsigned integer. The value of this OID variable should be scaled by outletSensorDecimalDigits. For example, if the value is…
1.3.6.1.4.1.13742.6.3.5.4.1.12ColumnoutletSensorMinimumread-onlycurrentThe smallest possible reading as an unsigned integer. The value of this OID variable should be scaled by outletSensorDecimalDigits. For example, if the value i…
1.3.6.1.4.1.13742.6.3.5.4.1.13ColumnoutletSensorHysteresisread-writecurrentThe hysteresis used for deassertions The value of this OID variable should be scaled by outletSensorDecimalDigits. For example, if the value is 1 and outletSen…
1.3.6.1.4.1.13742.6.3.5.4.1.14ColumnoutletSensorStateChangeDelayread-writecurrentThe delay measured in samples before a state is asserted. If the value is zero, then the state is asserted as soon as it is detected; if it is non-zero, say n,…
1.3.6.1.4.1.13742.6.3.5.4.1.21ColumnoutletSensorLowerCriticalThresholdread-writecurrentThe lower critical threshold as an unsigned integer. The value of this OID variable should be scaled by outletSensorDecimalDigits. For example, if the value is…
1.3.6.1.4.1.13742.6.3.5.4.1.22ColumnoutletSensorLowerWarningThresholdread-writecurrentThe lower warning threshold as an unsigned integer. The value of this OID variable should be scaled by outletSensorDecimalDigits. For example, if the value is …
1.3.6.1.4.1.13742.6.3.5.4.1.23ColumnoutletSensorUpperCriticalThresholdread-writecurrentThe upper critical threshold as an unsigned integer. The value of this OID variable should be scaled by outletSensorDecimalDigits. For example, if the value is…
1.3.6.1.4.1.13742.6.3.5.4.1.24ColumnoutletSensorUpperWarningThresholdread-writecurrentThe upper warning threshold as an unsigned integer. The value of this OID variable should be scaled by outletSensorDecimalDigits. For example, if the value is …
1.3.6.1.4.1.13742.6.3.5.4.1.25ColumnoutletSensorEnabledThresholdsread-writecurrentA bit string which indicates which thresholds are enabled. This parameter does not apply to sensors without numerical reading, e.g. outlet state sensors.
1.3.6.1.4.1.13742.6.3.5.4.1.26ColumnoutletSensorSignedMaximumread-onlycurrentThe largest possible reading as a signed integer. The value of this OID variable should be scaled by outletSensorDecimalDigits. For example, if the value is 1 …
1.3.6.1.4.1.13742.6.3.5.4.1.27ColumnoutletSensorSignedMinimumread-onlycurrentThe smallest possible reading as a signed integer. The value of this OID variable should be scaled by outletSensorDecimalDigits. For example, if the value is 1…
1.3.6.1.4.1.13742.6.3.5.4.1.28ColumnoutletSensorSignedLowerCriticalThresholdread-writecurrentThe lower critical threshold as a signed integer. The value of this OID variable should be scaled by outletSensorDecimalDigits. For example, if the value is 1 …
1.3.6.1.4.1.13742.6.3.5.4.1.29ColumnoutletSensorSignedLowerWarningThresholdread-writecurrentThe lower warning threshold as a signed integer. The value of this OID variable should be scaled by outletSensorDecimalDigits. For example, if the value is 1 a…
1.3.6.1.4.1.13742.6.3.5.4.1.30ColumnoutletSensorSignedUpperCriticalThresholdread-writecurrentThe upper critical threshold as a signed integer. The value of this OID variable should be scaled by outletSensorDecimalDigits. For example, if the value is 1 …
1.3.6.1.4.1.13742.6.3.5.4.1.31ColumnoutletSensorSignedUpperWarningThresholdread-writecurrentThe upper warning threshold as a signed integer. The value of this OID variable should be scaled by outletSensorDecimalDigits. For example, if the value is 1 a…
1.3.6.1.4.1.13742.6.3.5.5TableoutletPoleConfigurationTablenot-accessiblecurrentA list of outlet pole configuration entries. The number of entries is given by the value of outletPoleCount for the PDU.
1.3.6.1.4.1.13742.6.3.5.5.1RowoutletPoleConfigurationEntrynot-accessiblecurrentAn entry containing parametersfor a particular outlet pole.
1.3.6.1.4.1.13742.6.3.5.5.1.1ColumnoutletPoleLineread-onlycurrentThe Phase for this inlet Pole.
1.3.6.1.4.1.13742.6.3.5.5.1.2ColumnoutletPoleNoderead-onlycurrentThe node to which this outlet pole is connected
1.3.6.1.4.1.13742.6.3.5.6TableoutletPoleSensorConfigurationTablenot-accessiblecurrentA list of outlet pole sensor configuration entries. The number of entries is given by the value of outletPoleCount.
1.3.6.1.4.1.13742.6.3.5.6.1RowoutletPoleSensorConfigurationEntrynot-accessiblecurrentAn entry containing objects for configuring an outlet pole sensor.
1.3.6.1.4.1.13742.6.3.5.6.1.1ColumnoutletPoleIndexnot-accessiblecurrentA unique value for each outlet Pole. Its value ranges between 1 and the value of outletPoleCount.
1.3.6.1.4.1.13742.6.3.5.6.1.4ColumnoutletPoleSensorLogAvailableread-writecurrentIs logging enabled for the sensor?
1.3.6.1.4.1.13742.6.3.5.6.1.6ColumnoutletPoleSensorUnitsread-onlycurrentThe base units. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.5.6.1.7ColumnoutletPoleSensorDecimalDigitsread-onlycurrentThe number of digits displayed to the right of the decimal point. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.5.6.1.8ColumnoutletPoleSensorAccuracyread-onlydeprecatedThe accuracy: how close (in percent) the measurement is to the actual value. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.5.6.1.9ColumnoutletPoleSensorResolutionread-onlycurrentThe resolution: the minimum difference between any two measured values The value of this OID variable should be scaled by outletPoleSensorDecimalDigits. For ex…
1.3.6.1.4.1.13742.6.3.5.6.1.10ColumnoutletPoleSensorToleranceread-onlydeprecatedThe resolution: the difference between a sensor value and the actual value The value of this OID variable should be scaled by (outletPoleSensorDecimalDigits + …
1.3.6.1.4.1.13742.6.3.5.6.1.11ColumnoutletPoleSensorMaximumread-onlycurrentThe largest possible reading as an unsigned integer. The value of this OID variable should be scaled by outletPoleSensorDecimalDigits. For example, if the valu…
1.3.6.1.4.1.13742.6.3.5.6.1.12ColumnoutletPoleSensorMinimumread-onlycurrentThe smallest possible reading as an unsigned integer. The value of this OID variable should be scaled by outletPoleSensorDecimalDigits. For example, if the val…
1.3.6.1.4.1.13742.6.3.5.6.1.13ColumnoutletPoleSensorHysteresisread-writecurrentThe hysteresis used for deassertions The value of this OID variable should be scaled by outletPoleSensorDecimalDigits. For example, if the value is 1 and outle…
1.3.6.1.4.1.13742.6.3.5.6.1.14ColumnoutletPoleSensorStateChangeDelayread-writecurrentThe delay measured in samples before a state is asserted. If the value is zero, then the state is asserted as soon as it is detected; if it is non-zero, say n,…
1.3.6.1.4.1.13742.6.3.5.6.1.21ColumnoutletPoleSensorLowerCriticalThresholdread-writecurrentThe lower critical threshold as an unsigned integer. The value of this OID variable should be scaled by outletPoleSensorDecimalDigits. For example, if the valu…
1.3.6.1.4.1.13742.6.3.5.6.1.22ColumnoutletPoleSensorLowerWarningThresholdread-writecurrentThe lower warning threshold as an unsigned integer. The value of this OID variable should be scaled by outletPoleSensorDecimalDigits. For example, if the value…
1.3.6.1.4.1.13742.6.3.5.6.1.23ColumnoutletPoleSensorUpperCriticalThresholdread-writecurrentThe upper critical threshold as an unsigned integer. The value of this OID variable should be scaled by outletPoleSensorDecimalDigits. For example, if the valu…
1.3.6.1.4.1.13742.6.3.5.6.1.24ColumnoutletPoleSensorUpperWarningThresholdread-writecurrentThe upper warning threshold as an unsigned integer. The value of this OID variable should be scaled by outletPoleSensorDecimalDigits. For example, if the value…
1.3.6.1.4.1.13742.6.3.5.6.1.25ColumnoutletPoleSensorEnabledThresholdsread-writecurrentA bit string which indicates which thresholds are enabled. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.5.6.1.26ColumnoutletPoleSensorSignedMaximumread-onlycurrentThe largest possible reading as a signed integer. The value of this OID variable should be scaled by outletPoleSensorDecimalDigits. For example, if the value i…
1.3.6.1.4.1.13742.6.3.5.6.1.27ColumnoutletPoleSensorSignedMinimumread-onlycurrentThe smallest possible reading as a signed integer. The value of this OID variable should be scaled by outletPoleSensorDecimalDigits. For example, if the value …
1.3.6.1.4.1.13742.6.3.5.6.1.28ColumnoutletPoleSensorSignedLowerCriticalThresholdread-writecurrentThe lower critical threshold as a signed integer. The value of this OID variable should be scaled by outletPoleSensorDecimalDigits. For example, if the value i…
1.3.6.1.4.1.13742.6.3.5.6.1.29ColumnoutletPoleSensorSignedLowerWarningThresholdread-writecurrentThe lower warning threshold as a signed integer. The value of this OID variable should be scaled by outletPoleSensorDecimalDigits. For example, if the value is…
1.3.6.1.4.1.13742.6.3.5.6.1.30ColumnoutletPoleSensorSignedUpperCriticalThresholdread-writecurrentThe upper critical threshold as a signed integer. The value of this OID variable should be scaled by outletPoleSensorDecimalDigits. For example, if the value i…
1.3.6.1.4.1.13742.6.3.5.6.1.31ColumnoutletPoleSensorSignedUpperWarningThresholdread-writecurrentThe upper warning threshold as a signed integer. The value of this OID variable should be scaled by outletPoleSensorDecimalDigits. For example, if the value is…
1.3.6.1.4.1.13742.6.3.6NodeexternalSensors
1.3.6.1.4.1.13742.6.3.6.3TableexternalSensorConfigurationTablenot-accessiblecurrentA list of externalSensor configuration entries. The number of entries is given by the value of externalSensorCount for the PDU.
1.3.6.1.4.1.13742.6.3.6.3.1RowexternalSensorConfigurationEntrynot-accessiblecurrentAn entry containing parameters for an external sensor.
1.3.6.1.4.1.13742.6.3.6.3.1.1ColumnsensorIDnot-accessiblecurrentA unique value for each sensor. Its value ranges between 1 and the value of externalSensorCount.
1.3.6.1.4.1.13742.6.3.6.3.1.2ColumnexternalSensorTyperead-onlycurrentThe type of sensor.
1.3.6.1.4.1.13742.6.3.6.3.1.3ColumnexternalSensorSerialNumberread-onlycurrentThe sensor serial number.
1.3.6.1.4.1.13742.6.3.6.3.1.4ColumnexternalSensorNameread-writecurrentThe user-defined name.
1.3.6.1.4.1.13742.6.3.6.3.1.5ColumnexternalSensorDescriptionread-writecurrentThe user-defined description.
1.3.6.1.4.1.13742.6.3.6.3.1.6ColumnexternalSensorXCoordinateread-writecurrentThe X coordinate.
1.3.6.1.4.1.13742.6.3.6.3.1.7ColumnexternalSensorYCoordinateread-writecurrentThe Y coordinate.
1.3.6.1.4.1.13742.6.3.6.3.1.8ColumnexternalSensorZCoordinateread-writecurrentThe Z coordinate.
1.3.6.1.4.1.13742.6.3.6.3.1.9ColumnexternalSensorChannelNumberread-onlycurrentThe channel number, applies only to contact sensors; -1 for other sensors
1.3.6.1.4.1.13742.6.3.6.3.1.10ColumnexternalOnOffSensorSubtyperead-writecurrentThe subtype of the binary sensor
1.3.6.1.4.1.13742.6.3.6.3.1.14ColumnexternalSensorLogAvailableread-writecurrentIs logging available for this sensor?
1.3.6.1.4.1.13742.6.3.6.3.1.16ColumnexternalSensorUnitsread-onlycurrentThe base units This parameter does not apply to onOff, trip, vibration, waterDetection, smokeDetection sensors.
1.3.6.1.4.1.13742.6.3.6.3.1.17ColumnexternalSensorDecimalDigitsread-onlycurrentThe number of digits displayed to the right of the decimal point This parameter does not apply to onOff, trip, vibration, waterDetection, smokeDetection sensor…
1.3.6.1.4.1.13742.6.3.6.3.1.18ColumnexternalSensorAccuracyread-onlydeprecatedThe accuracy: how close (in percent) the measurement is to the actual value This parameter does not apply to onOff, trip, vibration, waterDetection, smokeDetec…
1.3.6.1.4.1.13742.6.3.6.3.1.19ColumnexternalSensorResolutionread-onlycurrentThe resolution: the minimum difference between any two measured values The value of this OID variable should be scaled by externalSensorDecimalDigits. For exam…
1.3.6.1.4.1.13742.6.3.6.3.1.20ColumnexternalSensorToleranceread-onlydeprecatedThe resolution: the difference between a sensor value and the actual value The value of this OID variable should be scaled by (externalSensorDecimalDigits + 1)…
1.3.6.1.4.1.13742.6.3.6.3.1.21ColumnexternalSensorMaximumread-onlycurrentThe largest possible value The value of this OID variable should be scaled by externalSensorDecimalDigits. For example, if the value is 1 and externalSensorDec…
1.3.6.1.4.1.13742.6.3.6.3.1.22ColumnexternalSensorMinimumread-onlycurrentThe smallest possible value The value of this OID variable should be scaled by externalSensorDecimalDigits. For example, if the value is 1 and externalSensorDe…
1.3.6.1.4.1.13742.6.3.6.3.1.23ColumnexternalSensorHysteresisread-writecurrentThe hysteresis used for deassertions The value of this OID variable should be scaled by externalSensorDecimalDigits. For example, if the value is 1 and externa…
1.3.6.1.4.1.13742.6.3.6.3.1.24ColumnexternalSensorStateChangeDelayread-writecurrentThe delay measured in samples before a state is asserted. If the value is zero, then the state is asserted as soon as it is detected; if it is non-zero, say n,…
1.3.6.1.4.1.13742.6.3.6.3.1.31ColumnexternalSensorLowerCriticalThresholdread-writecurrentThe lower critical threshold The value of this OID variable should be scaled by externalSensorDecimalDigits. For example, if the value is 1 and externalSensorD…
1.3.6.1.4.1.13742.6.3.6.3.1.32ColumnexternalSensorLowerWarningThresholdread-writecurrentThe lower non-critical (warning) threshold The value of this OID variable should be scaled by externalSensorDecimalDigits. For example, if the value is 1 and e…
1.3.6.1.4.1.13742.6.3.6.3.1.33ColumnexternalSensorUpperCriticalThresholdread-writecurrentThe upper critical threshold The value of this OID variable should be scaled by externalSensorDecimalDigits. For example, if the value is 1 and externalSensorD…
1.3.6.1.4.1.13742.6.3.6.3.1.34ColumnexternalSensorUpperWarningThresholdread-writecurrentThe upper non-critical (warning) threshold The value of this OID variable should be scaled by externalSensorDecimalDigits. For example, if the value is 1 and e…
1.3.6.1.4.1.13742.6.3.6.3.1.35ColumnexternalSensorEnabledThresholdsread-writecurrentA bit string which indicates which thresholds are enabled. This parameter does not apply to onOff, trip, vibration, waterDetection, smokeDetection sensors
1.3.6.1.4.1.13742.6.3.6.3.1.36ColumnexternalSensorIsActuatorread-onlycurrentIs this an actuator? True: It is an actuator False: It is not an actuator
1.3.6.1.4.1.13742.6.3.6.3.1.37ColumnexternalSensorPositionread-onlycurrentThe position of the sensor. The format is a semicolon separated list of Keyword:value pairs - Keyword1:Value1;Keyword2:value2;... Keyword can be one of the fol…
1.3.6.1.4.1.13742.6.3.6.3.1.38ColumnexternalSensorUseDefaultThresholdsread-writecurrentUse default thresholds for this sensor? True: Use Default thresholds for this sensor False: Do not Use Default thresholds for this sensor
1.3.6.1.4.1.13742.6.3.6.3.1.39ColumnexternalSensorAlarmedToNormalDelayread-writecurrentThe delay in seconds for transitions from the alarmed state to the normal state. If the sensor type is motionDetection, then it can set to a value greater >= 0…
1.3.6.1.4.1.13742.6.3.6.4TableexternalSensorTypeDefaultThresholdsTablenot-accessiblecurrentA list of entries listing the default thresholds for each sensor type.
1.3.6.1.4.1.13742.6.3.6.4.1RowexternalSensorTypeDefaultThresholdsEntrynot-accessiblecurrentAn entry containing default thresholds for a sensor type.
1.3.6.1.4.1.13742.6.3.6.4.1.3ColumnexternalSensorTypeDefaultHysteresisread-writecurrentThe hysteresis used for deassertions The value of this OID variable should be scaled by externalSensorDecimalDigits. For example, if the value is 1 and externa…
1.3.6.1.4.1.13742.6.3.6.4.1.4ColumnexternalSensorTypeDefaultStateChangeDelayread-writecurrentThe delay measured in samples before a state is asserted. If the value is zero, then the state is asserted as soon as it is detected; if it is non-zero, say n,…
1.3.6.1.4.1.13742.6.3.6.4.1.5ColumnexternalSensorTypeDefaultLowerCriticalThresholdread-writecurrentThe lower critical threshold The value of this OID variable should be scaled by externalSensorDecimalDigits. For example, if the value is 1 and externalSensorD…
1.3.6.1.4.1.13742.6.3.6.4.1.6ColumnexternalSensorTypeDefaultLowerWarningThresholdread-writecurrentThe lower non-critical (warning) threshold The value of this OID variable should be scaled by externalSensorDecimalDigits. For example, if the value is 1 and e…
1.3.6.1.4.1.13742.6.3.6.4.1.7ColumnexternalSensorTypeDefaultUpperCriticalThresholdread-writecurrentThe upper critical threshold The value of this OID variable should be scaled by externalSensorDecimalDigits. For example, if the value is 1 and externalSensorD…
1.3.6.1.4.1.13742.6.3.6.4.1.8ColumnexternalSensorTypeDefaultUpperWarningThresholdread-writecurrentThe upper non-critical (warning) threshold The value of this OID variable should be scaled by externalSensorDecimalDigits. For example, if the value is 1 and e…
1.3.6.1.4.1.13742.6.3.6.4.1.9ColumnexternalSensorTypeDefaultEnabledThresholdsread-writecurrentA bit string which indicates which thresholds are enabled. This parameter does not apply to onOff, trip, vibration, waterDetection, smokeDetection sensors
1.3.6.1.4.1.13742.6.3.6.5TableperipheralDevicePackageTablenot-accessiblecurrentA list of entries for the peripheral Device Packages connected to each PDU. The number of entries is given by the value of peripheralDevicePackagesCount.
1.3.6.1.4.1.13742.6.3.6.5.1RowperipheralDevicePackageEntrynot-accessiblecurrentAn entry containing objects for a controller.
1.3.6.1.4.1.13742.6.3.6.5.1.1ColumnperipheralDevicePackageIdnot-accessiblecurrentA unique value for each peripheral device package.
1.3.6.1.4.1.13742.6.3.6.5.1.3ColumnperipheralDevicePackageSerialNumberread-onlycurrentThe peripheral device package serial number.
1.3.6.1.4.1.13742.6.3.6.5.1.4ColumnperipheralDevicePackageModelread-onlycurrentThe peripheral device package model. Examples are DX-D2C6, DPX2-T1, DPX2-T1H1, DPX2-T2H1, DPX2-T3H1
1.3.6.1.4.1.13742.6.3.6.5.1.5ColumnperipheralDevicePackageFirmwareVersionread-onlycurrentThe peripheral device package firmware version.
1.3.6.1.4.1.13742.6.3.6.5.1.6ColumnperipheralDevicePackageMinFirmwareVersionread-onlycurrentThe peripheral device package minimum firmware version. This field may be empty. If it is not empty, then it shall not be possible to downgrade the peripheral …
1.3.6.1.4.1.13742.6.3.6.5.1.7ColumnperipheralDevicePackageFirmwareTimeStampread-onlycurrentThe time when the peripheralDevicePackage firmware was updated in UNIX(epoch)time. It is measured in seconds relative to January 1, 1970 (midnight UTC/GMT), i.…
1.3.6.1.4.1.13742.6.3.6.5.1.8ColumnperipheralDevicePackagePositionread-onlycurrentThe position of the package. The format is a semicolon separated list of Keyword:value pairs - Keyword1:Value1;Keyword2:value2;... Keyword can be one of the fo…
1.3.6.1.4.1.13742.6.3.6.5.1.9ColumnperipheralDevicePackageStateread-onlycurrentThe state of the package.
1.3.6.1.4.1.13742.6.3.7NodeserverReachability
1.3.6.1.4.1.13742.6.3.7.3TableserverReachabilityTablenot-accessiblecurrentA list of server entries. The number of entries is given by the value of serverCount for the PDU.
1.3.6.1.4.1.13742.6.3.7.3.1RowserverReachabilityEntrynot-accessiblecurrentAn entry containing parameters for a server.
1.3.6.1.4.1.13742.6.3.7.3.1.1ColumnserverIDnot-accessiblecurrentA unique value for each server. Its value ranges between 1 and the value of serverCount for that PDU
1.3.6.1.4.1.13742.6.3.7.3.1.3ColumnserverIPAddressread-onlycurrentThe IP Address/host name of the server
1.3.6.1.4.1.13742.6.3.7.3.1.4ColumnserverPingEnabledread-writecurrentIs ping enabled for this server?
1.3.6.1.4.1.13742.6.3.8Nodewires
1.3.6.1.4.1.13742.6.3.8.3TablewireConfigurationTablenot-accessibledeprecatedA list of wire configuration entries. The number of entries is given by the value of wireCount for the PDU.
1.3.6.1.4.1.13742.6.3.8.3.1RowwireConfigurationEntrynot-accessibledeprecatedAn entry containing objects for a particular wire.
1.3.6.1.4.1.13742.6.3.8.3.1.1ColumnwireIdnot-accessibledeprecatedA unique value for each wire. Its value ranges between 1 and the value of wireCount.
1.3.6.1.4.1.13742.6.3.8.3.1.2ColumnwireLabelread-onlydeprecatedThe label on the PDU identifying the wire.
1.3.6.1.4.1.13742.6.3.8.3.1.3ColumnwireCapabilitiesread-onlydeprecatedA bit string which indicates which wire sensors are available.
1.3.6.1.4.1.13742.6.3.8.3.1.4ColumnwirePowerSourceread-onlydeprecatedThis object allows discovery of how the PDU is wired. It indicates the wire's power source which can one of the following: overCurrentProtector transfer switch…
1.3.6.1.4.1.13742.6.3.8.4TablewireSensorConfigurationTablenot-accessibledeprecatedA list of wireSensor configuration entries.
1.3.6.1.4.1.13742.6.3.8.4.1RowwireSensorConfigurationEntrynot-accessibledeprecatedAn wireSensor entry containing objects for a particular wire Sensor.
1.3.6.1.4.1.13742.6.3.8.4.1.4ColumnwireSensorLogAvailableread-writedeprecatedIs logging available for this sensor?
1.3.6.1.4.1.13742.6.3.8.4.1.6ColumnwireSensorUnitsread-onlydeprecatedThe base units
1.3.6.1.4.1.13742.6.3.8.4.1.7ColumnwireSensorDecimalDigitsread-onlydeprecatedThe number of digits displayed to the right of the decimal point.
1.3.6.1.4.1.13742.6.3.8.4.1.8ColumnwireSensorAccuracyread-onlydeprecatedThe accuracy: how close (in percent) the measurement is to the actual value
1.3.6.1.4.1.13742.6.3.8.4.1.9ColumnwireSensorResolutionread-onlydeprecatedThe resolution: the minimum difference between any two measured values The value of this OID variable should be scaled by wireSensorDecimalDigits. For example,…
1.3.6.1.4.1.13742.6.3.8.4.1.10ColumnwireSensorToleranceread-onlydeprecatedThe resolution: the difference between a sensor value and the actual value The value of this OID variable should be scaled by (wireSensorDecimalDigits + 1). Fo…
1.3.6.1.4.1.13742.6.3.8.4.1.11ColumnwireSensorMaximumread-onlydeprecatedThe largest possible value The value of this OID variable should be scaled by wireSensorDecimalDigits. For example, if the value is 1 and wireSensorDecimalDigi…
1.3.6.1.4.1.13742.6.3.8.4.1.12ColumnwireSensorMinimumread-onlydeprecatedThe smallest possible value The value of this OID variable should be scaled by wireSensorDecimalDigits. For example, if the value is 1 and wireSensorDecimalDig…
1.3.6.1.4.1.13742.6.3.8.4.1.13ColumnwireSensorHysteresisread-writedeprecatedThe hysteresis used for deassertions The value of this OID variable should be scaled by wireSensorDecimalDigits. For example, if the value is 1 and wireSensorD…
1.3.6.1.4.1.13742.6.3.8.4.1.14ColumnwireSensorStateChangeDelayread-writedeprecatedThe delay measured in samples before a state is asserted. If the value is zero, then the state is asserted as soon as it is detected; if it is non-zero, say n,…
1.3.6.1.4.1.13742.6.3.8.4.1.21ColumnwireSensorLowerCriticalThresholdread-writedeprecatedThe lower critical threshold The value of this OID variable should be scaled by wireSensorDecimalDigits. For example, if the value is 1 and wireSensorDecimalDi…
1.3.6.1.4.1.13742.6.3.8.4.1.22ColumnwireSensorLowerWarningThresholdread-writedeprecatedThe lower non-critical (warning) threshold The value of this OID variable should be scaled by wireSensorDecimalDigits. For example, if the value is 1 and wireS…
1.3.6.1.4.1.13742.6.3.8.4.1.23ColumnwireSensorUpperCriticalThresholdread-writedeprecatedThe upper critical threshold The value of this OID variable should be scaled by wireSensorDecimalDigits. For example, if the value is 1 and wireSensorDecimalDi…
1.3.6.1.4.1.13742.6.3.8.4.1.24ColumnwireSensorUpperWarningThresholdread-writedeprecatedThe upper non-critical (warning) threshold The value of this OID variable should be scaled by wireSensorDecimalDigits. For example, if the value is 1 and wireS…
1.3.6.1.4.1.13742.6.3.8.4.1.25ColumnwireSensorEnabledThresholdsread-writedeprecatedA bit string which indicates which thresholds are enabled.
1.3.6.1.4.1.13742.6.3.9NodetransferSwitch
1.3.6.1.4.1.13742.6.3.9.3TabletransferSwitchConfigurationTablenot-accessiblecurrentA list of transfer switch configuration entries. The number of entries is given by the value of transferSwitchCount.
1.3.6.1.4.1.13742.6.3.9.3.1RowtransferSwitchConfigurationEntrynot-accessiblecurrentAn entry containing objects for a particular transferSwitch.
1.3.6.1.4.1.13742.6.3.9.3.1.1ColumntransferSwitchIdnot-accessiblecurrentA unique value for each transfer switch. Its value ranges between 1 and the value of transferSwitchCount.
1.3.6.1.4.1.13742.6.3.9.3.1.2ColumntransferSwitchLabelread-onlycurrentThe label on the PDU identifying the TS.
1.3.6.1.4.1.13742.6.3.9.3.1.3ColumntransferSwitchNameread-writecurrentThe user-defined name of the transferSwitch.
1.3.6.1.4.1.13742.6.3.9.3.1.4ColumntransferSwitchPreferredInletread-onlycurrentThe preferred Inlet. The TS powers the outlet from the preferred inlet when acceptable power is available from the preferred inlet.
1.3.6.1.4.1.13742.6.3.9.3.1.5ColumntransferSwitchPoleCountread-onlycurrentThe number of poles.
1.3.6.1.4.1.13742.6.3.9.3.1.20ColumntransferSwitchAutoReTransferEnabledread-writecurrentThe TS can be configured to automatically retransfer back to the preferred inlet when power is restored. Re-transfer only occurs if this variable is true.
1.3.6.1.4.1.13742.6.3.9.3.1.21ColumntransferSwitchAutoReTransferWaitTimeread-writecurrentThe Auto Re-Transfer Wait Time. Re-transfer occurs this many seconds after the condition causing the original transfer has been corrected.
1.3.6.1.4.1.13742.6.3.9.3.1.22ColumntransferSwitchAutoReTransferRequiresPhaseSyncread-writecurrentIf this parameter is False, then do not retransfer if there is a PHASE_SYNC_FAULT in effect. A PHASE_SYNC_FAULT occurs when the phase difference between the in…
1.3.6.1.4.1.13742.6.3.9.3.1.23ColumntransferSwitchFrontPanelManualTransferButtonEnabledread-writecurrentIf this parameter is false, then manual transfers caused by pressing the front panel switch are disabled.
1.3.6.1.4.1.13742.6.3.9.3.1.24ColumntransferSwitchCapabilitiesread-onlycurrentA bit string which indicates which sensors are available for the transfer switch.
1.3.6.1.4.1.13742.6.3.9.3.1.31ColumntransferSwitchPowerSource1read-onlycurrentThis object allows discovery of how the PDU is wired. It indicates the transferSwitch's first power source which can one of the following: overCurrentProtector…
1.3.6.1.4.1.13742.6.3.9.3.1.32ColumntransferSwitchPowerSource2read-onlycurrentThis object allows discovery of how the PDU is wired. It indicates the transferSwitch's second power source which can one of the following: overCurrentProtecto…
1.3.6.1.4.1.13742.6.3.9.4TabletransferSwitchSensorConfigurationTablenot-accessiblecurrentA list of transfer switch sensor configuration entries.
1.3.6.1.4.1.13742.6.3.9.4.1RowtransferSwitchSensorConfigurationEntrynot-accessiblecurrentAn entry containing parameters for a transfer switch sensor.
1.3.6.1.4.1.13742.6.3.9.4.1.4ColumntransferSwitchSensorLogAvailableread-writecurrentIs logging available for this sensor?
1.3.6.1.4.1.13742.6.3.9.4.1.6ColumntransferSwitchSensorUnitsread-onlycurrentThe base units. This parameter does not apply to sensors without numerical reading, e.g. operational state or switch fault sensors.
1.3.6.1.4.1.13742.6.3.9.4.1.7ColumntransferSwitchSensorDecimalDigitsread-onlycurrentThe number of digits displayed to the right of the decimal point This parameter does not apply to sensors without numerical reading, e.g. operational state or …
1.3.6.1.4.1.13742.6.3.9.4.1.8ColumntransferSwitchSensorAccuracyread-onlydeprecatedThe accuracy: how close (in percent) the measurement is to the actual value This parameter does not apply to sensors without numerical reading, e.g. operationa…
1.3.6.1.4.1.13742.6.3.9.4.1.9ColumntransferSwitchSensorResolutionread-onlycurrentThe resolution: the minimum difference between any two measured values The value of this OID variable should be scaled by transferSwitchSensorDecimalDigits. Fo…
1.3.6.1.4.1.13742.6.3.9.4.1.10ColumntransferSwitchSensorToleranceread-onlydeprecatedThe resolution: the difference between a sensor value and the actual value The value of this OID variable should be scaled by (transferSwitchSensorDecimalDigit…
1.3.6.1.4.1.13742.6.3.9.4.1.11ColumntransferSwitchSensorMaximumread-onlycurrentThe largest possible reading as an unsigned integer. The value of this OID variable should be scaled by transferSwitchSensorDecimalDigits. For example, if the …
1.3.6.1.4.1.13742.6.3.9.4.1.12ColumntransferSwitchSensorMinimumread-onlycurrentThe smallest possible reading as an unsigned integer. The value of this OID variable should be scaled by transferSwitchSensorDecimalDigits. For example, if the…
1.3.6.1.4.1.13742.6.3.9.4.1.13ColumntransferSwitchSensorHysteresisread-writecurrentThe hysteresis used for deassertions The value of this OID variable should be scaled by transferSwitchSensorDecimalDigits. For example, if the value is 1 and t…
1.3.6.1.4.1.13742.6.3.9.4.1.14ColumntransferSwitchSensorStateChangeDelayread-writecurrentThe delay measured in samples before a state is asserted. If the value is zero, then the state is asserted as soon as it is detected; if it is non-zero, say n,…
1.3.6.1.4.1.13742.6.3.9.4.1.21ColumntransferSwitchSensorLowerCriticalThresholdread-writecurrentThe lower critical threshold as an unsigned integer. The value of this OID variable should be scaled by transferSwitchSensorDecimalDigits. For example, if the …
1.3.6.1.4.1.13742.6.3.9.4.1.22ColumntransferSwitchSensorLowerWarningThresholdread-writecurrentThe lower warning threshold as an unsigned integer. The value of this OID variable should be scaled by transferSwitchSensorDecimalDigits. For example, if the v…
1.3.6.1.4.1.13742.6.3.9.4.1.23ColumntransferSwitchSensorUpperCriticalThresholdread-writecurrentThe upper critical threshold as an unsigned integer. The value of this OID variable should be scaled by transferSwitchSensorDecimalDigits. For example, if the …
1.3.6.1.4.1.13742.6.3.9.4.1.24ColumntransferSwitchSensorUpperWarningThresholdread-writecurrentThe upper warning threshold as an unsigned integer. The value of this OID variable should be scaled by transferSwitchSensorDecimalDigits. For example, if the v…
1.3.6.1.4.1.13742.6.3.9.4.1.25ColumntransferSwitchSensorEnabledThresholdsread-writecurrentA bit string which indicates which thresholds are enabled. This parameter does not apply to sensors without numerical reading, e.g. operational state or switch…
1.3.6.1.4.1.13742.6.3.9.4.1.26ColumntransferSwitchSensorSignedMaximumread-onlycurrentThe largest possible reading as a signed integer. The value of this OID variable should be scaled by transferSwitchSensorDecimalDigits. For example, if the val…
1.3.6.1.4.1.13742.6.3.9.4.1.27ColumntransferSwitchSensorSignedMinimumread-onlycurrentThe smallest possible reading as a signed integer. The value of this OID variable should be scaled by transferSwitchSensorDecimalDigits. For example, if the va…
1.3.6.1.4.1.13742.6.3.9.4.1.28ColumntransferSwitchSensorSignedLowerCriticalThresholdread-writecurrentThe lower critical threshold as a signed integer. The value of this OID variable should be scaled by transferSwitchSensorDecimalDigits. For example, if the val…
1.3.6.1.4.1.13742.6.3.9.4.1.29ColumntransferSwitchSensorSignedLowerWarningThresholdread-writecurrentThe lower warning threshold as a signed integer. The value of this OID variable should be scaled by transferSwitchSensorDecimalDigits. For example, if the valu…
1.3.6.1.4.1.13742.6.3.9.4.1.30ColumntransferSwitchSensorSignedUpperCriticalThresholdread-writecurrentThe upper critical threshold as a signed integer. The value of this OID variable should be scaled by transferSwitchSensorDecimalDigits. For example, if the val…
1.3.6.1.4.1.13742.6.3.9.4.1.31ColumntransferSwitchSensorSignedUpperWarningThresholdread-writecurrentThe upper warning threshold as a signed integer. The value of this OID variable should be scaled by transferSwitchSensorDecimalDigits. For example, if the valu…
1.3.6.1.4.1.13742.6.3.9.5TabletransferSwitchPoleConfigurationTablenot-accessiblecurrentA list of transferSwitch pole configuration entries. The number of entries is given by the value of transferSwitchPoleCount.
1.3.6.1.4.1.13742.6.3.9.5.1RowtransferSwitchPoleConfigurationEntrynot-accessiblecurrentAn entry containing parametersfor a particular outlet pole.
1.3.6.1.4.1.13742.6.3.9.5.1.1ColumntransferSwitchPoleIndexnot-accessiblecurrentA unique value for each transferSwitch Pole. Its value ranges between 1 and the value of transferSwitchPoleCount.
1.3.6.1.4.1.13742.6.3.9.5.1.2ColumntransferSwitchPoleLineread-onlycurrentThe Phase for this transferSwitch Pole.
1.3.6.1.4.1.13742.6.3.9.5.1.3ColumntransferSwitchPoleIn1Noderead-onlycurrentThe node to which this transferSwitch pole Input 1 is connected
1.3.6.1.4.1.13742.6.3.9.5.1.4ColumntransferSwitchPoleIn2Noderead-onlycurrentThe node to which this transferSwitch pole Input 2 is connected
1.3.6.1.4.1.13742.6.3.9.5.1.5ColumntransferSwitchPoleOutNoderead-onlycurrentThe node to which this transferSwitch pole Output is connected
1.3.6.1.4.1.13742.6.3.10NodepowerMeter
1.3.6.1.4.1.13742.6.3.10.2TablepowerMeterConfigurationTablenot-accessiblecurrentA list of power meter and panel configuration entries.
1.3.6.1.4.1.13742.6.3.10.2.1RowpowerMeterConfigurationEntrynot-accessiblecurrentAn entry containing configuration objects for power meters and panels.
1.3.6.1.4.1.13742.6.3.10.2.1.2ColumnpowerMeterPhaseCTRatingread-writecurrentThe rating of the Phase CT in A, or 0 if the CT is disabled. At present, read-only access; see MIN-ACCESS in MODULE-COMPLIANCE ModulecomplianceRev2
1.3.6.1.4.1.13742.6.3.10.2.1.3ColumnpowerMeterNeutralCTRatingread-writecurrentThe rating of the Neutral CT in A, or 0 if the CT is disabled. At present, read-only access; see MIN-ACCESS in MODULE-COMPLIANCE ModulecomplianceRev2
1.3.6.1.4.1.13742.6.3.10.2.1.4ColumnpowerMeterEarthCTRatingread-writecurrentThe rating of the Earth CT in A, or 0 if the CT is disabled. At present, read-only access; see MIN-ACCESS in MODULE-COMPLIANCE ModulecomplianceRev2
1.3.6.1.4.1.13742.6.3.10.2.1.5ColumnpowerMeterBranchCountread-onlycurrentThe maximum number of circuits supported by the panel. (The number of user configured circuits is in unitConfigurationTable(pduId).circuitCount.) It can be use…
1.3.6.1.4.1.13742.6.3.10.2.1.6ColumnpowerMeterPanelPositionsread-onlycurrentThe number of circuit positions in the panel. Its value is specified by the user when configuring a panel
1.3.6.1.4.1.13742.6.3.10.2.1.7ColumnpowerMeterPanelLayoutread-onlycurrentvalid only for panels (powerMeterCircuitPositionCount > 0); invalid for power meters (powerMeterCircuitPositionCount = 0): value returned is invalid(-1). The p…
1.3.6.1.4.1.13742.6.3.10.2.1.8ColumnpowerMeterPanelNumberingread-onlycurrentvalid only for panels (powerMeterCircuitPositionCount > 0); invalid for power meters (powerMeterCircuitPositionCount = 0): value returned is invalid(-1). The p…
1.3.6.1.4.1.13742.6.3.10.2.1.9ColumnpowerMeterTyperead-onlycurrentThe power meter type: 3-phase, single-phase, split-phase.
1.3.6.1.4.1.13742.6.3.11Nodecircuit
1.3.6.1.4.1.13742.6.3.11.2TablecircuitConfigurationTablenot-accessiblecurrentA list of circuit configuration entries. The number of entries is given by the value of panelCircuitPositionCount.
1.3.6.1.4.1.13742.6.3.11.2.1RowcircuitConfigurationEntrynot-accessiblecurrentAn entry containing configuration objects for the circuit.
1.3.6.1.4.1.13742.6.3.11.2.1.1ColumncircuitIdnot-accessiblecurrentA unique value for each circuit. circuitId is defined as follows. It is the circuit position in the panel
1.3.6.1.4.1.13742.6.3.11.2.1.2ColumncircuitPoleCountread-onlycurrentThe number of circuit positions (poles) in the circuit.
1.3.6.1.4.1.13742.6.3.11.2.1.3ColumncircuitNameread-writecurrentThe user-defined name for the circuit. At present, read-only access; see MIN-ACCESS in MODULE-COMPLIANCE ModulecomplianceRev2
1.3.6.1.4.1.13742.6.3.11.2.1.4ColumncircuitTyperead-onlycurrentThe type of circuit: singlePhaseL_L, singlePhaseL_N, twoPhase,threePhase
1.3.6.1.4.1.13742.6.3.11.2.1.5ColumncircuitRatedCurrentread-writecurrentThe rating of the breaker for the circuit in A. At present, read-only access; see MIN-ACCESS in MODULE-COMPLIANCE ModulecomplianceRev2
1.3.6.1.4.1.13742.6.3.11.2.1.6ColumncircuitCTRatingread-writecurrentThe rating of the CTs metering this circuit in A. At present, read-only access; see MIN-ACCESS in MODULE-COMPLIANCE ModulecomplianceRev2
1.3.6.1.4.1.13742.6.3.11.2.1.7ColumncircuitCapabilitiesread-onlycurrentA bit string which indicates which sensors are available for the circuit.
1.3.6.1.4.1.13742.6.3.11.2.1.8ColumncircuitPoleCapabilitiesread-onlycurrentA bit string which indicates which sensors are available for the circuit pole.
1.3.6.1.4.1.13742.6.3.11.2.1.9ColumncircuitPowerSourceread-onlycurrentThis object allows discovery of how the circuit is wired. It indicates the circuit's power source which can one of the following: Inlet It contains the OID of …
1.3.6.1.4.1.13742.6.3.11.3TablecircuitPoleConfigurationTablenot-accessiblecurrentA list of Panel Circuit Pole configuration entries. The number of entries is given by the value of circuitPoleCount for the circuit.
1.3.6.1.4.1.13742.6.3.11.3.1RowcircuitPoleConfigurationEntrynot-accessiblecurrentAn entry containing configuration objects for the circuit poles.
1.3.6.1.4.1.13742.6.3.11.3.1.1ColumncircuitPoleIdnot-accessiblecurrentA unique value for each circuit Pole. Its value ranges between 1 and the value of circuitPoleCount.
1.3.6.1.4.1.13742.6.3.11.3.1.2ColumncircuitPolePanelPositionread-onlycurrentThe circuit position for this pole.
1.3.6.1.4.1.13742.6.3.11.3.1.3ColumncircuitPoleCTNumberread-writecurrentThe CT Number for this circuit Pole, or 0 if no CT is present. At present, read-only access; see MIN-ACCESS in MODULE-COMPLIANCE ModulecomplianceRev2
1.3.6.1.4.1.13742.6.3.11.3.1.4ColumncircuitPolePhaseread-writecurrentThe Phase for this circuit Pole. At present, read-only access; see MIN-ACCESS in MODULE-COMPLIANCE ModulecomplianceRev2
1.3.6.1.4.1.13742.6.3.11.4TablecircuitSensorConfigurationTablenot-accessiblecurrentA list of configuration entries for an inlet sensor.
1.3.6.1.4.1.13742.6.3.11.4.1RowcircuitSensorConfigurationEntrynot-accessiblecurrentAn entry containing objects for configuring an inlet sensor.
1.3.6.1.4.1.13742.6.3.11.4.1.4ColumncircuitSensorLogAvailableread-writecurrentIs logging enabled for the sensor?
1.3.6.1.4.1.13742.6.3.11.4.1.6ColumncircuitSensorUnitsread-onlycurrentThe base units. This parameter does not apply to sensors without numerical reading, e.g. surge protector status sensors.
1.3.6.1.4.1.13742.6.3.11.4.1.7ColumncircuitSensorDecimalDigitsread-onlycurrentThe number of digits displayed to the right of the decimal point. This parameter does not apply to sensors without numerical reading, e.g. surge protector stat…
1.3.6.1.4.1.13742.6.3.11.4.1.9ColumncircuitSensorResolutionread-onlycurrentThe resolution: the minimum difference between any two measured values The value of this OID variable should be scaled by inletSensorDecimalDigits. For example…
1.3.6.1.4.1.13742.6.3.11.4.1.11ColumncircuitSensorMaximumread-onlycurrentThe largest possible reading as an unsigned integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is …
1.3.6.1.4.1.13742.6.3.11.4.1.12ColumncircuitSensorMinimumread-onlycurrentThe smallest possible reading as an unsigned integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is…
1.3.6.1.4.1.13742.6.3.11.4.1.13ColumncircuitSensorHysteresisread-writecurrentThe hysteresis used for deassertions The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1 and inletSenso…
1.3.6.1.4.1.13742.6.3.11.4.1.14ColumncircuitSensorStateChangeDelayread-writecurrentThe delay measured in samples before a state is asserted. If the value is zero, then the state is asserted as soon as it is detected; if it is non-zero, say n,…
1.3.6.1.4.1.13742.6.3.11.4.1.21ColumncircuitSensorLowerCriticalThresholdread-writecurrentThe lower critical threshold as an unsigned integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is …
1.3.6.1.4.1.13742.6.3.11.4.1.22ColumncircuitSensorLowerWarningThresholdread-writecurrentThe lower warning threshold as an unsigned integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1…
1.3.6.1.4.1.13742.6.3.11.4.1.23ColumncircuitSensorUpperCriticalThresholdread-writecurrentThe upper critical threshold as an unsigned integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is …
1.3.6.1.4.1.13742.6.3.11.4.1.24ColumncircuitSensorUpperWarningThresholdread-writecurrentThe upper warning threshold as an unsigned integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1…
1.3.6.1.4.1.13742.6.3.11.4.1.25ColumncircuitSensorEnabledThresholdsread-writecurrentA bit string which indicates which thresholds are enabled. This parameter does not apply to sensors without numerical reading, e.g. surge protector status sens…
1.3.6.1.4.1.13742.6.3.11.4.1.26ColumncircuitSensorSignedMaximumread-onlycurrentThe largest possible reading as a signed integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1 a…
1.3.6.1.4.1.13742.6.3.11.4.1.27ColumncircuitSensorSignedMinimumread-onlycurrentThe smallest possible reading as a signed integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1 …
1.3.6.1.4.1.13742.6.3.11.4.1.28ColumncircuitSensorSignedLowerCriticalThresholdread-writecurrentThe lower critical threshold as a signed integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1 a…
1.3.6.1.4.1.13742.6.3.11.4.1.29ColumncircuitSensorSignedLowerWarningThresholdread-writecurrentThe lower warning threshold as a signed integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1 an…
1.3.6.1.4.1.13742.6.3.11.4.1.30ColumncircuitSensorSignedUpperCriticalThresholdread-writecurrentThe upper critical threshold as a signed integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1 a…
1.3.6.1.4.1.13742.6.3.11.4.1.31ColumncircuitSensorSignedUpperWarningThresholdread-writecurrentThe upper warning threshold as a signed integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1 an…
1.3.6.1.4.1.13742.6.3.11.6TablecircuitPoleSensorConfigurationTablenot-accessiblecurrentA list of configuration entries for a circuit's pole sensors.
1.3.6.1.4.1.13742.6.3.11.6.1RowcircuitPoleSensorConfigurationEntrynot-accessiblecurrentAn entry containing objects for configuring an inlet pole sensor.
1.3.6.1.4.1.13742.6.3.11.6.1.4ColumncircuitPoleSensorLogAvailableread-writecurrentIs logging enabled for the sensor?
1.3.6.1.4.1.13742.6.3.11.6.1.6ColumncircuitPoleSensorUnitsread-onlycurrentThe base units. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.11.6.1.7ColumncircuitPoleSensorDecimalDigitsread-onlycurrentThe number of digits displayed to the right of the decimal point. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.11.6.1.9ColumncircuitPoleSensorResolutionread-onlycurrentThe resolution: the minimum difference between any two measured values The value of this OID variable should be scaled by inletPoleSensorDecimalDigits. For exa…
1.3.6.1.4.1.13742.6.3.11.6.1.11ColumncircuitPoleSensorMaximumread-onlycurrentThe largest possible reading as an unsigned integer. The value of this OID variable should be scaled by inletPoleSensorDecimalDigits. For example, if the value…
1.3.6.1.4.1.13742.6.3.11.6.1.12ColumncircuitPoleSensorMinimumread-onlycurrentThe smallest possible reading as an unsigned integer. The value of this OID variable should be scaled by inletPoleSensorDecimalDigits. For example, if the valu…
1.3.6.1.4.1.13742.6.3.11.6.1.13ColumncircuitPoleSensorHysteresisread-writecurrentThe hysteresis used for deassertions The value of this OID variable should be scaled by inletPoleSensorDecimalDigits. For example, if the value is 1 and inletP…
1.3.6.1.4.1.13742.6.3.11.6.1.14ColumncircuitPoleSensorStateChangeDelayread-writecurrentThe delay measured in samples before a state is asserted. If the value is zero, then the state is asserted as soon as it is detected; if it is non-zero, say n,…
1.3.6.1.4.1.13742.6.3.11.6.1.21ColumncircuitPoleSensorLowerCriticalThresholdread-writecurrentThe lower critical threshold as an unsigned integer. The value of this OID variable should be scaled by inletPoleSensorDecimalDigits. For example, if the value…
1.3.6.1.4.1.13742.6.3.11.6.1.22ColumncircuitPoleSensorLowerWarningThresholdread-writecurrentThe lower warning threshold as an unsigned integer. The value of this OID variable should be scaled by inletPoleSensorDecimalDigits. For example, if the value …
1.3.6.1.4.1.13742.6.3.11.6.1.23ColumncircuitPoleSensorUpperCriticalThresholdread-writecurrentThe upper critical threshold as an unsigned integer. The value of this OID variable should be scaled by inletPoleSensorDecimalDigits. For example, if the value…
1.3.6.1.4.1.13742.6.3.11.6.1.24ColumncircuitPoleSensorUpperWarningThresholdread-writecurrentThe upper warning threshold as an unsigned integer. The value of this OID variable should be scaled by inletPoleSensorDecimalDigits. For example, if the value …
1.3.6.1.4.1.13742.6.3.11.6.1.25ColumncircuitPoleSensorEnabledThresholdsread-writecurrentA bit string which indicates which thresholds are enabled. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.11.6.1.26ColumncircuitPoleSensorSignedMaximumread-onlycurrentThe largest possible reading as a signed integer. The value of this OID variable should be scaled by inletPoleSensorDecimalDigits. For example, if the value is…
1.3.6.1.4.1.13742.6.3.11.6.1.27ColumncircuitPoleSensorSignedMinimumread-onlycurrentThe smallest possible reading as a signed integer. The value of this OID variable should be scaled by inletPoleSensorDecimalDigits. For example, if the value i…
1.3.6.1.4.1.13742.6.3.11.6.1.28ColumncircuitPoleSensorSignedLowerCriticalThresholdread-writecurrentThe lower critical threshold as a signed integer. The value of this OID variable should be scaled by inletPoleSensorDecimalDigits. For example, if the value is…
1.3.6.1.4.1.13742.6.3.11.6.1.29ColumncircuitPoleSensorSignedLowerWarningThresholdread-writecurrentThe lower warning threshold as a signed integer. The value of this OID variable should be scaled by inletPoleSensorDecimalDigits. For example, if the value is …
1.3.6.1.4.1.13742.6.3.11.6.1.30ColumncircuitPoleSensorSignedUpperCriticalThresholdread-writecurrentThe upper critical threshold as a signed integer. The value of this OID variable should be scaled by inletPoleSensorDecimalDigits. For example, if the value is…
1.3.6.1.4.1.13742.6.3.11.6.1.31ColumncircuitPoleSensorSignedUpperWarningThresholdread-writecurrentThe upper warning threshold as a signed integer. The value of this OID variable should be scaled by inletPoleSensorDecimalDigits. For example, if the value is …
1.3.6.1.4.1.13742.6.4Nodecontrol
1.3.6.1.4.1.13742.6.4.1NodeoutletControl
1.3.6.1.4.1.13742.6.4.1.2TableoutletSwitchControlTablenot-accessiblecurrentA list of outlets for a PDU. The number of entries is given by the value of outletCount.
1.3.6.1.4.1.13742.6.4.1.2.1RowoutletSwitchControlEntrynot-accessiblecurrentAn entry for implementing switching operations on an outlet.
1.3.6.1.4.1.13742.6.4.1.2.1.2ColumnswitchingOperationread-writecurrentThe switching operation.
1.3.6.1.4.1.13742.6.4.1.2.1.3ColumnoutletSwitchingStateread-onlycurrentThe outlet state at present
1.3.6.1.4.1.13742.6.4.1.2.1.4ColumnoutletSwitchingTimeStampread-onlycurrentThe timestamp indicating when the outlet was last switched
1.3.6.1.4.1.13742.6.4.2NodeexternalSensorControl
1.3.6.1.4.1.13742.6.4.3NodetransferSwitchControl
1.3.6.1.4.1.13742.6.4.3.1TabletransferSwitchControlTablenot-accessiblecurrentA list of transfer switches for a PDU. The number of entries is given by the value of transferSwitchCount.
1.3.6.1.4.1.13742.6.4.3.1.1RowtransferSwitchControlEntrynot-accessiblecurrentAn entry for implementing switching operations on a transfer switch.
1.3.6.1.4.1.13742.6.4.3.1.1.1ColumntransferSwitchActiveInletread-onlycurrentThe index of the currently active inlet.
1.3.6.1.4.1.13742.6.4.3.1.1.2ColumntransferSwitchTransferToInletread-writecurrentSelect the active inlet. If the new inlet is available, it will become both active and preferred, otherwise an inconsistentValue error will be returned. By def…
1.3.6.1.4.1.13742.6.4.3.1.1.3ColumntransferSwitchAlarmOverrideread-writecurrentForce transfer even if the phase difference between the inlets is too large. This may only be written together with transferSwitchTransferToInlet, otherwise an…
1.3.6.1.4.1.13742.6.4.3.1.1.4ColumntransferSwitchLastTransferReasonread-onlycurrentThe reason for the most recent transfer
1.3.6.1.4.1.13742.6.4.4NodeactuatorControl
1.3.6.1.4.1.13742.6.4.4.2TableactuatorControlTablenot-accessiblecurrentA list of actuators for a PDU.
1.3.6.1.4.1.13742.6.4.4.2.1RowactuatorControlEntrynot-accessiblecurrentAn entry for implementing user-initiated state changes for an actuator.
1.3.6.1.4.1.13742.6.4.4.2.1.2ColumnactuatorStateread-writecurrentThe actuator state. A Get operation retrieves the state of the actuator. A Set operation changes the stae of the sensor. The valid states for set operations ar…
1.3.6.1.4.1.13742.6.4.5NodercmControl
1.3.6.1.4.1.13742.6.4.5.2TablercmSelfTestTablenot-accessiblecurrentA list of RCMs.
1.3.6.1.4.1.13742.6.4.5.2.1RowrcmSelfTestEntrynot-accessiblecurrentAn entry for implementing self test of an RCM.
1.3.6.1.4.1.13742.6.4.5.2.1.2ColumnrcmStateread-writecurrentThe rcm state. A Get operation retrieves the state of the RCM State Sensor. A Set operation changes the state of the sensor. The valid state for set operations…
1.3.6.1.4.1.13742.6.4.6NodeinletSensorControl
1.3.6.1.4.1.13742.6.4.6.1TableinletSensorControlTablenot-accessiblecurrentA list of control entries for the inlet sensors of a PDU. The set of valid indexes is defined by the value of inletCount and the inletDeviceCapabilities entry …
1.3.6.1.4.1.13742.6.4.6.1.1RowinletSensorControlEntrynot-accessiblecurrentAn entry used for controlling an inlet sensor.
1.3.6.1.4.1.13742.6.4.6.1.1.1ColumninletSensorResetValueread-writecurrentWriting to this variable sets a new value for the addressed sensor. Only accumulating sensors (e.g. energy counters) can be reset, and currently the only suppo…
1.3.6.1.4.1.13742.6.4.7NodeoutletSensorControl
1.3.6.1.4.1.13742.6.4.7.1TableoutletSensorControlTablenot-accessiblecurrentA list of control entries for the outlet sensors of a PDU. The set of valid indexes is defined by the value of outletCount and the outletDeviceCapabilities ent…
1.3.6.1.4.1.13742.6.4.7.1.1RowoutletSensorControlEntrynot-accessiblecurrentAn entry used for controlling an outlet sensor.
1.3.6.1.4.1.13742.6.4.7.1.1.1ColumnoutletSensorResetValueread-writecurrentWriting to this variable sets a new value for the addressed sensor. Only accumulating sensors (e.g. energy counters) can be reset, and currently the only suppo…
1.3.6.1.4.1.13742.6.4.8NodeunitSensorControl
1.3.6.1.4.1.13742.6.4.8.1TableunitSensorControlTablenot-accessiblecurrentA list of control entries for the global sensors of a PDU. The set of valid indexes is defined by the value of pduCount and the pduDeviceCapabilities entry.
1.3.6.1.4.1.13742.6.4.8.1.1RowunitSensorControlEntrynot-accessiblecurrentAn entry used for controlling an global sensor.
1.3.6.1.4.1.13742.6.4.8.1.1.1ColumnunitSensorResetValueread-writecurrentWriting to this variable sets a new value for the addressed sensor. Only accumulating sensors (e.g. energy counters) can be reset, and currently the only suppo…
1.3.6.1.4.1.13742.6.4.9NodecircuitSensorControl
1.3.6.1.4.1.13742.6.4.9.1TablecircuitSensorControlTablenot-accessiblecurrentA list of control entries for the circuit sensors of a BCM2. The maximum number of entries is given by the value of panelCircuitPositionCount.
1.3.6.1.4.1.13742.6.4.9.1.1RowcircuitSensorControlEntrynot-accessiblecurrentAn entry used for controlling an circuit sensor.
1.3.6.1.4.1.13742.6.4.9.1.1.1ColumncircuitSensorResetValueread-writecurrentWriting to this variable sets a new value for the addressed sensor. Only accumulating sensors (e.g. energy counters) can be reset, and currently the only suppo…
1.3.6.1.4.1.13742.6.5Nodemeasurements
1.3.6.1.4.1.13742.6.5.1NodemeasurementsUnit
1.3.6.1.4.1.13742.6.5.1.3TableunitSensorMeasurementsTablenot-accessiblecurrentA list of unit sensor entries.
1.3.6.1.4.1.13742.6.5.1.3.1RowunitSensorMeasurementsEntrynot-accessiblecurrentAn entry containing measurement objects for an unit sensor.
1.3.6.1.4.1.13742.6.5.1.3.1.2ColumnmeasurementsUnitSensorIsAvailableread-onlycurrentIs the sensor available?
1.3.6.1.4.1.13742.6.5.1.3.1.3ColumnmeasurementsUnitSensorStateread-onlycurrentThe sensor state.
1.3.6.1.4.1.13742.6.5.1.3.1.4ColumnmeasurementsUnitSensorValueread-onlycurrentThe sensor reading as an unsigned integer. The value of this OID variable should be scaled by unitSensorDecimalDigits. For example, if the value is 1 and unitS…
1.3.6.1.4.1.13742.6.5.1.3.1.5ColumnmeasurementsUnitSensorTimeStampread-onlycurrentThe timestamp.
1.3.6.1.4.1.13742.6.5.1.3.1.6ColumnmeasurementsUnitSensorSignedValueread-onlycurrentThe sensor reading as a signed integer. The value of this OID variable should be scaled by unitSensorDecimalDigits. For example, if the value is 1 and unitSens…
1.3.6.1.4.1.13742.6.5.2NodemeasurementsInlet
1.3.6.1.4.1.13742.6.5.2.3TableinletSensorMeasurementsTablenot-accessiblecurrentA list of inlet sensor entries. The number of entries is given by the value of inletCount for the PDU.
1.3.6.1.4.1.13742.6.5.2.3.1RowinletSensorMeasurementsEntrynot-accessiblecurrentAn entry containing measurement objects for an inlet sensor.
1.3.6.1.4.1.13742.6.5.2.3.1.2ColumnmeasurementsInletSensorIsAvailableread-onlycurrentIs the sensor available?
1.3.6.1.4.1.13742.6.5.2.3.1.3ColumnmeasurementsInletSensorStateread-onlycurrentThe sensor state.
1.3.6.1.4.1.13742.6.5.2.3.1.4ColumnmeasurementsInletSensorValueread-onlycurrentThe sensor reading as an unsigned integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1 and inle…
1.3.6.1.4.1.13742.6.5.2.3.1.5ColumnmeasurementsInletSensorTimeStampread-onlycurrentThe timestamp.
1.3.6.1.4.1.13742.6.5.2.3.1.6ColumnmeasurementsInletSensorSignedValueread-onlycurrentThe sensor reading as a signed integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1 and inletSe…
1.3.6.1.4.1.13742.6.5.2.4TableinletPoleSensorMeasurementsTablenot-accessiblecurrentA list of inletPole sensor entries. The number of entries is given by the value of inletPoleCount for the inlet.
1.3.6.1.4.1.13742.6.5.2.4.1RowinletPoleSensorMeasurementsEntrynot-accessiblecurrentAn entry containing measurement objects for an inletPole sensor.
1.3.6.1.4.1.13742.6.5.2.4.1.2ColumnmeasurementsInletPoleSensorIsAvailableread-onlycurrentIs the sensor available?
1.3.6.1.4.1.13742.6.5.2.4.1.3ColumnmeasurementsInletPoleSensorStateread-onlycurrentThe sensor state.
1.3.6.1.4.1.13742.6.5.2.4.1.4ColumnmeasurementsInletPoleSensorValueread-onlycurrentThe sensor reading as an unsigned integer. The value of this OID variable should be scaled by inletPoleSensorDecimalDigits. For example, if the value is 1 and …
1.3.6.1.4.1.13742.6.5.2.4.1.5ColumnmeasurementsInletPoleSensorTimeStampread-onlycurrentThe timestamp.
1.3.6.1.4.1.13742.6.5.2.4.1.6ColumnmeasurementsInletPoleSensorSignedValueread-onlycurrentThe sensor reading as a signed integer. The value of this OID variable should be scaled by inletPoleSensorDecimalDigits. For example, if the value is 1 and inl…
1.3.6.1.4.1.13742.6.5.3NodemeasurementsOverCurrentProtector
1.3.6.1.4.1.13742.6.5.3.3TableoverCurrentProtectorSensorMeasurementsTablenot-accessiblecurrentA list of overCurrentProtector sensor entries. The number of entries is given by the value of overCurrentProtectorCount for the PDU.
1.3.6.1.4.1.13742.6.5.3.3.1RowoverCurrentProtectorSensorMeasurementsEntrynot-accessiblecurrentAn entry containing measurement objects for an overCurrentProtector.
1.3.6.1.4.1.13742.6.5.3.3.1.2ColumnmeasurementsOverCurrentProtectorSensorIsAvailableread-onlycurrentIs the sensor available?
1.3.6.1.4.1.13742.6.5.3.3.1.3ColumnmeasurementsOverCurrentProtectorSensorStateread-onlycurrentThe sensor state.
1.3.6.1.4.1.13742.6.5.3.3.1.4ColumnmeasurementsOverCurrentProtectorSensorValueread-onlycurrentThe sensor reading as an unsigned integer. The value of this OID variable should be scaled by overCurrentProtectorSensorDecimalDigits. For example, if the valu…
1.3.6.1.4.1.13742.6.5.3.3.1.5ColumnmeasurementsOverCurrentProtectorSensorTimeStampread-onlycurrentThe timestamp.
1.3.6.1.4.1.13742.6.5.3.3.1.6ColumnmeasurementsOverCurrentProtectorSensorSignedValueread-onlycurrentThe sensor reading as a signed integer. The value of this OID variable should be scaled by overCurrentProtectorSensorDecimalDigits. For example, if the value i…
1.3.6.1.4.1.13742.6.5.4NodemeasurementsOutlet
1.3.6.1.4.1.13742.6.5.4.3TableoutletSensorMeasurementsTablenot-accessiblecurrentA list of outlet sensor entries. The number of entries is given by the value of outletCount for the PDU.
1.3.6.1.4.1.13742.6.5.4.3.1RowoutletSensorMeasurementsEntrynot-accessiblecurrentAn entry containing measurement objects for an outlet sensor.
1.3.6.1.4.1.13742.6.5.4.3.1.2ColumnmeasurementsOutletSensorIsAvailableread-onlycurrentIs the sensor available?
1.3.6.1.4.1.13742.6.5.4.3.1.3ColumnmeasurementsOutletSensorStateread-onlycurrentThe sensor state.
1.3.6.1.4.1.13742.6.5.4.3.1.4ColumnmeasurementsOutletSensorValueread-onlycurrentThe sensor reading as an unsigned integer. The value of this OID variable should be scaled by outletSensorDecimalDigits. For example, if the value is 1 and out…
1.3.6.1.4.1.13742.6.5.4.3.1.5ColumnmeasurementsOutletSensorTimeStampread-onlycurrentThe timestamp.
1.3.6.1.4.1.13742.6.5.4.3.1.6ColumnmeasurementsOutletSensorSignedValueread-onlycurrentThe sensor reading as a signed integer. The value of this OID variable should be scaled by outletSensorDecimalDigits. For example, if the value is 1 and outlet…
1.3.6.1.4.1.13742.6.5.4.4TableoutletPoleSensorMeasurementsTablenot-accessiblecurrentA list of outletPole sensor entries. The number of entries is given by the value of outletPoletCount for the outlet.
1.3.6.1.4.1.13742.6.5.4.4.1RowoutletPoleSensorMeasurementsEntrynot-accessiblecurrentAn entry containing measurement objects for an outletPole sensor.
1.3.6.1.4.1.13742.6.5.4.4.1.2ColumnmeasurementsOutletPoleSensorIsAvailableread-onlycurrentIs the sensor available?
1.3.6.1.4.1.13742.6.5.4.4.1.3ColumnmeasurementsOutletPoleSensorStateread-onlycurrentThe sensor state.
1.3.6.1.4.1.13742.6.5.4.4.1.4ColumnmeasurementsOutletPoleSensorValueread-onlycurrentThe sensor reading as an unsigned integer. The value of this OID variable should be scaled by outletPoleSensorDecimalDigits. For example, if the value is 50 an…
1.3.6.1.4.1.13742.6.5.4.4.1.5ColumnmeasurementsOutletPoleSensorTimeStampread-onlycurrentThe timestamp.
1.3.6.1.4.1.13742.6.5.4.4.1.6ColumnmeasurementsOutletPoleSensorSignedValueread-onlycurrentThe sensor reading as a signed integer. The value of this OID variable should be scaled by outletPoleSensorDecimalDigits. For example, if the value is 50 and o…
1.3.6.1.4.1.13742.6.5.5NodemeasurementsExternalSensor
1.3.6.1.4.1.13742.6.5.5.3TableexternalSensorMeasurementsTablenot-accessiblecurrentA list of external sensor entries. The number of entries is given by the value of externalSensorCount for the PDU.
1.3.6.1.4.1.13742.6.5.5.3.1RowexternalSensorMeasurementsEntrynot-accessiblecurrentAn entry containing measurement objects for an external sensor.
1.3.6.1.4.1.13742.6.5.5.3.1.2ColumnmeasurementsExternalSensorIsAvailableread-onlycurrentIs the sensor available?
1.3.6.1.4.1.13742.6.5.5.3.1.3ColumnmeasurementsExternalSensorStateread-onlycurrentThe sensor state.
1.3.6.1.4.1.13742.6.5.5.3.1.4ColumnmeasurementsExternalSensorValueread-onlycurrentThe sensor reading as a signed integer. The value of this OID variable should be scaled by externalSensorDecimalDigits. For example, if the value is 1 and exte…
1.3.6.1.4.1.13742.6.5.5.3.1.5ColumnmeasurementsExternalSensorTimeStampread-onlycurrentThe sensor reading timestamp.
1.3.6.1.4.1.13742.6.5.6NodemeasurementsWire
1.3.6.1.4.1.13742.6.5.6.3TablewireSensorMeasurementsTablenot-accessibledeprecatedA list of wire sensor entries. The number of entries is given by the value of wireCount for the PDU.
1.3.6.1.4.1.13742.6.5.6.3.1RowwireSensorMeasurementsEntrynot-accessibledeprecatedAn entry containing measurement objects for a wire.
1.3.6.1.4.1.13742.6.5.6.3.1.2ColumnmeasurementsWireSensorIsAvailableread-onlydeprecatedIs the sensor available?
1.3.6.1.4.1.13742.6.5.6.3.1.3ColumnmeasurementsWireSensorStateread-onlydeprecatedThe sensor state.
1.3.6.1.4.1.13742.6.5.6.3.1.4ColumnmeasurementsWireSensorValueread-onlydeprecatedThe sensor value. The value of this OID variable should be scaled by wireSensorDecimalDigits. For example, if the value is 1 and wireSensorDecimalDigits is 2, …
1.3.6.1.4.1.13742.6.5.6.3.1.5ColumnmeasurementsWireSensorTimeStampread-onlydeprecatedThe timestamp.
1.3.6.1.4.1.13742.6.5.7NodemeasurementsTransferSwitch
1.3.6.1.4.1.13742.6.5.7.3TabletransferSwitchSensorMeasurementsTablenot-accessiblecurrentA list of transfer switch sensor entries. The number of entries is given by the value of transferSwitchCount for the PDU.
1.3.6.1.4.1.13742.6.5.7.3.1RowtransferSwitchSensorMeasurementsEntrynot-accessiblecurrentAn entry containing measurement objects for a transfer switch.
1.3.6.1.4.1.13742.6.5.7.3.1.2ColumnmeasurementsTransferSwitchSensorIsAvailableread-onlycurrentIs the sensor available?
1.3.6.1.4.1.13742.6.5.7.3.1.3ColumnmeasurementsTransferSwitchSensorStateread-onlycurrentThe sensor state.
1.3.6.1.4.1.13742.6.5.7.3.1.4ColumnmeasurementsTransferSwitchSensorValueread-onlycurrentThe sensor reading as an unsigned integer. The value of this OID variable should be scaled by transferSwitchSensorDecimalDigits. For example, if the value is 1…
1.3.6.1.4.1.13742.6.5.7.3.1.5ColumnmeasurementsTransferSwitchSensorTimeStampread-onlycurrentThe timestamp.
1.3.6.1.4.1.13742.6.5.7.3.1.6ColumnmeasurementsTransferSwitchSensorSignedValueread-onlycurrentThe sensor reading as a signed integer. The value of this OID variable should be scaled by transferSwitchSensorDecimalDigits. For example, if the value is 1 an…
1.3.6.1.4.1.13742.6.5.8NodemeasurementsCircuit
1.3.6.1.4.1.13742.6.5.8.3TablecircuitSensorMeasurementsTablenot-accessiblecurrentA list of circuit sensor entries.
1.3.6.1.4.1.13742.6.5.8.3.1RowcircuitSensorMeasurementsEntrynot-accessiblecurrentAn entry containing measurement objects for circuit sensor.
1.3.6.1.4.1.13742.6.5.8.3.1.2ColumnmeasurementsCircuitSensorIsAvailableread-onlycurrentIs the sensor available?
1.3.6.1.4.1.13742.6.5.8.3.1.3ColumnmeasurementsCircuitSensorStateread-onlycurrentThe sensor state.
1.3.6.1.4.1.13742.6.5.8.3.1.4ColumnmeasurementsCircuitSensorValueread-onlycurrentThe sensor reading as an unsigned integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1 and inle…
1.3.6.1.4.1.13742.6.5.8.3.1.5ColumnmeasurementsCircuitSensorTimeStampread-onlycurrentThe timestamp.
1.3.6.1.4.1.13742.6.5.8.3.1.6ColumnmeasurementsCircuitSensorSignedValueread-onlycurrentThe sensor reading as a signed integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1 and inletSe…
1.3.6.1.4.1.13742.6.5.8.4TablecircuitPoleSensorMeasurementsTablenot-accessiblecurrentA list of panel circuit pole sensor entries. The number of entries is given by the value of inletCount for the PDU.
1.3.6.1.4.1.13742.6.5.8.4.1RowcircuitPoleSensorMeasurementsEntrynot-accessiblecurrentAn entry containing measurement objects for a circuit pole sensor.
1.3.6.1.4.1.13742.6.5.8.4.1.2ColumnmeasurementsCircuitPoleSensorIsAvailableread-onlycurrentIs the sensor available?
1.3.6.1.4.1.13742.6.5.8.4.1.3ColumnmeasurementsCircuitPoleSensorStateread-onlycurrentThe sensor state.
1.3.6.1.4.1.13742.6.5.8.4.1.4ColumnmeasurementsCircuitPoleSensorValueread-onlycurrentThe sensor reading as an unsigned integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1 and inle…
1.3.6.1.4.1.13742.6.5.8.4.1.5ColumnmeasurementsCircuitPoleSensorTimeStampread-onlycurrentThe timestamp.
1.3.6.1.4.1.13742.6.5.8.4.1.6ColumnmeasurementsCircuitPoleSensorSignedValueread-onlycurrentThe sensor reading as a signed integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1 and inletSe…
1.3.6.1.4.1.13742.6.6Nodelog
1.3.6.1.4.1.13742.6.6.1NodelogUnit
1.3.6.1.4.1.13742.6.6.1.1TablelogIndexTablenot-accessiblecurrentA table of log entries.
1.3.6.1.4.1.13742.6.6.1.1.1RowlogIndexEntrynot-accessiblecurrentAn entry in the log containing sensor data.
1.3.6.1.4.1.13742.6.6.1.1.1.2ColumnoldestLogIDread-onlycurrentThe index of the oldest data in the buffer for this PDU.
1.3.6.1.4.1.13742.6.6.1.1.1.3ColumnnewestLogIDread-onlycurrentThe index of the newest data in the buffer for this PDU.
1.3.6.1.4.1.13742.6.6.1.2TablelogTimeStampTablenot-accessiblecurrentA list of entries containing the timestamps of the entries in the log.
1.3.6.1.4.1.13742.6.6.1.2.1RowlogTimeStampEntrynot-accessiblecurrentAn entry containing the timestamp for log entries.
1.3.6.1.4.1.13742.6.6.1.2.1.1ColumnlogIndexnot-accessiblecurrentA unique value for each entry in the log. Its value ranges between 1 and the value of logSize.
1.3.6.1.4.1.13742.6.6.1.2.1.2ColumnlogTimeStampread-onlycurrentThe time when the data was collected. It is measured in seconds relative to January 1, 1970 (midnight UTC/GMT), i.e a value of 0 indicates January 1, 1970 (mid…
1.3.6.1.4.1.13742.6.6.1.3TableunitSensorLogTablenot-accessiblecurrentA list of unit sensor entries in the log.
1.3.6.1.4.1.13742.6.6.1.3.1RowunitSensorLogEntrynot-accessiblecurrentAn entry containing log objects for an unit sensor.
1.3.6.1.4.1.13742.6.6.1.3.1.2ColumnlogUnitSensorDataAvailableread-onlycurrentIs data available for this sensor during this measurement period?
1.3.6.1.4.1.13742.6.6.1.3.1.3ColumnlogUnitSensorStateread-onlycurrentThe sensor state.
1.3.6.1.4.1.13742.6.6.1.3.1.4ColumnlogUnitSensorAvgValueread-onlycurrentThe average sensor reading for the log period as an unsigned integer. The value of this OID variable should be scaled by unitSensorDecimalDigits. For example, …
1.3.6.1.4.1.13742.6.6.1.3.1.5ColumnlogUnitSensorMaxValueread-onlycurrentThe maximum sensor reading for the log period as an unsigned integer. The value of this OID variable should be scaled by unitSensorDecimalDigits. For example, …
1.3.6.1.4.1.13742.6.6.1.3.1.6ColumnlogUnitSensorMinValueread-onlycurrentThe minimum sensor reading for the log period as an unsigned integer. The value of this OID variable should be scaled by unitSensorDecimalDigits. For example, …
1.3.6.1.4.1.13742.6.6.1.3.1.7ColumnlogUnitSensorSignedAvgValueread-onlycurrentThe average sensor reading for the log period as a signed integer. The value of this OID variable should be scaled by unitSensorDecimalDigits. For example, if …
1.3.6.1.4.1.13742.6.6.1.3.1.8ColumnlogUnitSensorSignedMaxValueread-onlycurrentThe maximum sensor reading for the log period as a signed integer. The value of this OID variable should be scaled by unitSensorDecimalDigits. For example, if …
1.3.6.1.4.1.13742.6.6.1.3.1.9ColumnlogUnitSensorSignedMinValueread-onlycurrentThe minimum sensor reading for the log period as a signed integer. The value of this OID variable should be scaled by unitSensorDecimalDigits. For example, if …
1.3.6.1.4.1.13742.6.6.2NodelogInlet
1.3.6.1.4.1.13742.6.6.2.3TableinletSensorLogTablenot-accessiblecurrentA list of inlet sensor entries. The number of entries is given by the value of inletCount for the PDU.
1.3.6.1.4.1.13742.6.6.2.3.1RowinletSensorLogEntrynot-accessiblecurrentAn entry containing log objects for an inlet sensor.
1.3.6.1.4.1.13742.6.6.2.3.1.2ColumnlogInletSensorDataAvailableread-onlycurrentIs data available for this sensor during this measurement period?
1.3.6.1.4.1.13742.6.6.2.3.1.3ColumnlogInletSensorStateread-onlycurrentThe sensor state.
1.3.6.1.4.1.13742.6.6.2.3.1.4ColumnlogInletSensorAvgValueread-onlycurrentThe average sensor reading for the log period as an unsigned integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example,…
1.3.6.1.4.1.13742.6.6.2.3.1.5ColumnlogInletSensorMaxValueread-onlycurrentThe maximum sensor reading for the log period as an unsigned integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example,…
1.3.6.1.4.1.13742.6.6.2.3.1.6ColumnlogInletSensorMinValueread-onlycurrentThe minimum sensor reading for the log period as an unsigned integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example,…
1.3.6.1.4.1.13742.6.6.2.3.1.7ColumnlogInletSensorSignedAvgValueread-onlycurrentThe average sensor reading for the log period as a signed integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if…
1.3.6.1.4.1.13742.6.6.2.3.1.8ColumnlogInletSensorSignedMaxValueread-onlycurrentThe maximum sensor reading for the log period as a signed integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if…
1.3.6.1.4.1.13742.6.6.2.3.1.9ColumnlogInletSensorSignedMinValueread-onlycurrentThe minimum sensor reading for the log period as a signed integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if…
1.3.6.1.4.1.13742.6.6.2.4TableinletPoleSensorLogTablenot-accessiblecurrentA list of inletPole sensor entries. The number of entries is given by the value of inletPoleCount for the inlet.
1.3.6.1.4.1.13742.6.6.2.4.1RowinletPoleSensorLogEntrynot-accessiblecurrentAn entry containing log objects for an inletPole sensor.
1.3.6.1.4.1.13742.6.6.2.4.1.2ColumnlogInletPoleSensorDataAvailableread-onlycurrentIs data available for this sensor during this measurement period?
1.3.6.1.4.1.13742.6.6.2.4.1.3ColumnlogInletPoleSensorStateread-onlycurrentThe sensor state.
1.3.6.1.4.1.13742.6.6.2.4.1.4ColumnlogInletPoleSensorAvgValueread-onlycurrentThe average sensor reading for the log period as an unsigned integer. The value of this OID variable should be scaled by inletPoleSensorDecimalDigits. For exam…
1.3.6.1.4.1.13742.6.6.2.4.1.5ColumnlogInletPoleSensorMaxValueread-onlycurrentThe maximum sensor reading for the log period as an unsigned integer. The value of this OID variable should be scaled by inletPoleSensorDecimalDigits. For exam…
1.3.6.1.4.1.13742.6.6.2.4.1.6ColumnlogInletPoleSensorMinValueread-onlycurrentThe minimum sensor reading for the log period as an unsigned integer. The value of this OID variable should be scaled by inletPoleSensorDecimalDigits. For exam…
1.3.6.1.4.1.13742.6.6.2.4.1.7ColumnlogInletPoleSensorSignedAvgValueread-onlycurrentThe average sensor reading for the log period as a signed integer. The value of this OID variable should be scaled by inletPoleSensorDecimalDigits. For example…
1.3.6.1.4.1.13742.6.6.2.4.1.8ColumnlogInletPoleSensorSignedMaxValueread-onlycurrentThe maximum sensor reading for the log period as a signed integer. The value of this OID variable should be scaled by inletPoleSensorDecimalDigits. For example…
1.3.6.1.4.1.13742.6.6.2.4.1.9ColumnlogInletPoleSensorSignedMinValueread-onlycurrentThe minimum sensor reading for the log period as a signed integer. The value of this OID variable should be scaled by inletPoleSensorDecimalDigits. For example…
1.3.6.1.4.1.13742.6.6.3NodelogOverCurrentProtector
1.3.6.1.4.1.13742.6.6.3.3TableoverCurrentProtectorSensorLogTablenot-accessiblecurrentA list of overCurrentProtector sensor entries. The number of entries is given by the value of overCurrentProtectorCount for the PDU.
1.3.6.1.4.1.13742.6.6.3.3.1RowoverCurrentProtectorSensorLogEntrynot-accessiblecurrentAn entry containing log objects for an overCurrentProtector sensor.
1.3.6.1.4.1.13742.6.6.3.3.1.2ColumnlogOverCurrentProtectorSensorDataAvailableread-onlycurrentIs data available for this sensor during this measurement period?
1.3.6.1.4.1.13742.6.6.3.3.1.3ColumnlogOverCurrentProtectorSensorStateread-onlycurrentThe sensor state.
1.3.6.1.4.1.13742.6.6.3.3.1.4ColumnlogOverCurrentProtectorSensorAvgValueread-onlycurrentThe average sensor reading for the log period as an unsigned integer. The value of this OID variable should be scaled by overCurrentProtectorSensorDecimalDigit…
1.3.6.1.4.1.13742.6.6.3.3.1.5ColumnlogOverCurrentProtectorSensorMaxValueread-onlycurrentThe maximum sensor reading for the log period as an unsigned integer. The value of this OID variable should be scaled by overCurrentProtectorSensorDecimalDigit…
1.3.6.1.4.1.13742.6.6.3.3.1.6ColumnlogOverCurrentProtectorSensorMinValueread-onlycurrentThe minimum sensor reading for the log period as an unsigned integer. The value of this OID variable should be scaled by overCurrentProtectorSensorDecimalDigit…
1.3.6.1.4.1.13742.6.6.3.3.1.7ColumnlogOverCurrentProtectorSensorSignedAvgValueread-onlycurrentThe average sensor reading for the log period as a signed integer. The value of this OID variable should be scaled by overCurrentProtectorSensorDecimalDigits. …
1.3.6.1.4.1.13742.6.6.3.3.1.8ColumnlogOverCurrentProtectorSensorSignedMaxValueread-onlycurrentThe maximum sensor reading for the log period as a signed integer. The value of this OID variable should be scaled by overCurrentProtectorSensorDecimalDigits. …
1.3.6.1.4.1.13742.6.6.3.3.1.9ColumnlogOverCurrentProtectorSensorSignedMinValueread-onlycurrentThe minimum sensor reading for the log period as a signed integer. The value of this OID variable should be scaled by overCurrentProtectorSensorDecimalDigits. …
1.3.6.1.4.1.13742.6.6.4NodelogOutlet
1.3.6.1.4.1.13742.6.6.4.3TableoutletSensorLogTablenot-accessiblecurrentA list of outlet sensor entries. The number of entries is given by the value of outletCount for the PDU.
1.3.6.1.4.1.13742.6.6.4.3.1RowoutletSensorLogEntrynot-accessiblecurrentAn entry containing log objects for an outlet sensor.
1.3.6.1.4.1.13742.6.6.4.3.1.2ColumnlogOutletSensorDataAvailableread-onlycurrentIs data available for this sensor during this measurement period?
1.3.6.1.4.1.13742.6.6.4.3.1.3ColumnlogOutletSensorStateread-onlycurrentThe sensor state.
1.3.6.1.4.1.13742.6.6.4.3.1.4ColumnlogOutletSensorAvgValueread-onlycurrentThe average sensor reading for the log period as an unsigned integer. The value of this OID variable should be scaled by outletSensorDecimalDigits. For example…
1.3.6.1.4.1.13742.6.6.4.3.1.5ColumnlogOutletSensorMaxValueread-onlycurrentThe maximum sensor reading for the log period as an unsigned integer. The value of this OID variable should be scaled by outletSensorDecimalDigits. For example…
1.3.6.1.4.1.13742.6.6.4.3.1.6ColumnlogOutletSensorMinValueread-onlycurrentThe minimum sensor reading for the log period as an unsigned integer. The value of this OID variable should be scaled by outletSensorDecimalDigits. For example…
1.3.6.1.4.1.13742.6.6.4.3.1.7ColumnlogOutletSensorSignedAvgValueread-onlycurrentThe average sensor reading for the log period as a signed integer. The value of this OID variable should be scaled by outletSensorDecimalDigits. For example, i…
1.3.6.1.4.1.13742.6.6.4.3.1.8ColumnlogOutletSensorSignedMaxValueread-onlycurrentThe maximum sensor reading for the log period as a signed integer. The value of this OID variable should be scaled by outletSensorDecimalDigits. For example, i…
1.3.6.1.4.1.13742.6.6.4.3.1.9ColumnlogOutletSensorSignedMinValueread-onlycurrentThe minimum sensor reading for the log period as a signed integer. The value of this OID variable should be scaled by outletSensorDecimalDigits. For example, i…
1.3.6.1.4.1.13742.6.6.4.4TableoutletPoleSensorLogTablenot-accessiblecurrentA list of outletPole sensor entries. The number of entries is given by the value of outletPoleCount for the outlet.
1.3.6.1.4.1.13742.6.6.4.4.1RowoutletPoleSensorLogEntrynot-accessiblecurrentAn entry containing log objects for an outletPole sensor.
1.3.6.1.4.1.13742.6.6.4.4.1.2ColumnlogOutletPoleSensorDataAvailableread-onlycurrentIs data available for this sensor during this measurement period?
1.3.6.1.4.1.13742.6.6.4.4.1.3ColumnlogOutletPoleSensorStateread-onlycurrentThe sensor state.
1.3.6.1.4.1.13742.6.6.4.4.1.4ColumnlogOutletPoleSensorAvgValueread-onlycurrentThe average sensor reading for the log period as an unsigned integer. The value of this OID variable should be scaled by outletPoleSensorDecimalDigits. For exa…
1.3.6.1.4.1.13742.6.6.4.4.1.5ColumnlogOutletPoleSensorMaxValueread-onlycurrentThe maximum sensor reading for the log period as an unsigned integer. The value of this OID variable should be scaled by outletPoleSensorDecimalDigits. For exa…
1.3.6.1.4.1.13742.6.6.4.4.1.6ColumnlogOutletPoleSensorMinValueread-onlycurrentThe minimum sensor reading for the log period as an unsigned integer. The value of this OID variable should be scaled by outletPoleSensorDecimalDigits. For exa…
1.3.6.1.4.1.13742.6.6.4.4.1.7ColumnlogOutletPoleSensorSignedAvgValueread-onlycurrentThe average sensor reading for the log period as a signed integer. The value of this OID variable should be scaled by outletPoleSensorDecimalDigits. For exampl…
1.3.6.1.4.1.13742.6.6.4.4.1.8ColumnlogOutletPoleSensorSignedMaxValueread-onlycurrentThe maximum sensor reading for the log period as a signed integer. The value of this OID variable should be scaled by outletPoleSensorDecimalDigits. For exampl…
1.3.6.1.4.1.13742.6.6.4.4.1.9ColumnlogOutletPoleSensorSignedMinValueread-onlycurrentThe minimum sensor reading for the log period as a signed integer. The value of this OID variable should be scaled by outletPoleSensorDecimalDigits. For exampl…
1.3.6.1.4.1.13742.6.6.5NodelogExternalSensor
1.3.6.1.4.1.13742.6.6.5.3TableexternalSensorLogTablenot-accessiblecurrentA list of external sensor entries. The number of entries is given by the value of externalSensorCount for the PDU.
1.3.6.1.4.1.13742.6.6.5.3.1RowexternalSensorLogEntrynot-accessiblecurrentAn entry containing log objects for an external sensor.
1.3.6.1.4.1.13742.6.6.5.3.1.2ColumnlogExternalSensorDataAvailableread-onlycurrentIs data available for this sensor during this measurement period?
1.3.6.1.4.1.13742.6.6.5.3.1.3ColumnlogExternalSensorStateread-onlycurrentThe sensor state.
1.3.6.1.4.1.13742.6.6.5.3.1.4ColumnlogExternalSensorAvgValueread-onlycurrentThe sensor reading average value. The value of this OID variable should be scaled by externalSensorDecimalDigits. For example, if the value is 1 and externalSe…
1.3.6.1.4.1.13742.6.6.5.3.1.5ColumnlogExternalSensorMaxValueread-onlycurrentThe sensor reading maximum value. The value of this OID variable should be scaled by externalSensorDecimalDigits. For example, if the value is 1 and externalSe…
1.3.6.1.4.1.13742.6.6.5.3.1.6ColumnlogExternalSensorMinValueread-onlycurrentThe sensor reading minimum value. The value of this OID variable should be scaled by externalSensorDecimalDigits. For example, if the value is 1 and externalSe…
1.3.6.1.4.1.13742.6.6.6NodelogWire
1.3.6.1.4.1.13742.6.6.6.3TablewireSensorLogTablenot-accessibledeprecatedA list of wire sensor entries. The number of entries is given by the value of wireCount for the PDU.
1.3.6.1.4.1.13742.6.6.6.3.1RowwireSensorLogEntrynot-accessibledeprecatedAn entry containing log objects for a wire sensor.
1.3.6.1.4.1.13742.6.6.6.3.1.2ColumnlogWireSensorDataAvailableread-onlydeprecatedIs data available for this sensor during this measurement period?
1.3.6.1.4.1.13742.6.6.6.3.1.3ColumnlogWireSensorStateread-onlydeprecatedThe sensor state.
1.3.6.1.4.1.13742.6.6.6.3.1.4ColumnlogWireSensorAvgValueread-onlydeprecatedThe sensor reading average value. The value of this OID variable should be scaled by wireSensorDecimalDigits. For example, if the value is 1 and wireSensorDeci…
1.3.6.1.4.1.13742.6.6.6.3.1.5ColumnlogWireSensorMaxValueread-onlydeprecatedThe sensor reading maximum value. The value of this OID variable should be scaled by wireSensorDecimalDigits. For example, if the value is 1 and wireSensorDeci…
1.3.6.1.4.1.13742.6.6.6.3.1.6ColumnlogWireSensorMinValueread-onlydeprecatedThe sensor reading minimum value. The value of this OID variable should be scaled by wireSensorDecimalDigits. For example, if the value is 1 and wireSensorDeci…
1.3.6.1.4.1.13742.6.6.7NodelogTransferSwitch
1.3.6.1.4.1.13742.6.6.7.3TabletransferSwitchSensorLogTablenot-accessiblecurrentA list of Transfer Switch sensor entries. The number of entries is given by the value of transferSwitchCount for the PDU.
1.3.6.1.4.1.13742.6.6.7.3.1RowtransferSwitchSensorLogEntrynot-accessiblecurrentAn entry containing log objects for a transfer switch sensor.
1.3.6.1.4.1.13742.6.6.7.3.1.2ColumnlogTransferSwitchSensorDataAvailableread-onlycurrentIs data available for this sensor during this measurement period?
1.3.6.1.4.1.13742.6.6.7.3.1.3ColumnlogTransferSwitchSensorStateread-onlycurrentThe sensor state.
1.3.6.1.4.1.13742.6.6.7.3.1.4ColumnlogTransferSwitchSensorAvgValueread-onlycurrentThe average sensor reading for the log period as an unsigned integer. The value of this OID variable should be scaled by transferSwitchSensorDecimalDigits. For…
1.3.6.1.4.1.13742.6.6.7.3.1.5ColumnlogTransferSwitchSensorMaxValueread-onlycurrentThe maximum sensor reading for the log period as an unsigned integer. The value of this OID variable should be scaled by transferSwitchSensorDecimalDigits. For…
1.3.6.1.4.1.13742.6.6.7.3.1.6ColumnlogTransferSwitchSensorMinValueread-onlycurrentThe minimum sensor reading for the log period as an unsigned integer. The value of this OID variable should be scaled by transferSwitchSensorDecimalDigits. For…
1.3.6.1.4.1.13742.6.6.7.3.1.7ColumnlogTransferSwitchSensorSignedAvgValueread-onlycurrentThe average sensor reading for the log period as a signed integer. The value of this OID variable should be scaled by transferSwitchSensorDecimalDigits. For ex…
1.3.6.1.4.1.13742.6.6.7.3.1.8ColumnlogTransferSwitchSensorSignedMaxValueread-onlycurrentThe maximum sensor reading for the log period as a signed integer. The value of this OID variable should be scaled by transferSwitchSensorDecimalDigits. For ex…
1.3.6.1.4.1.13742.6.6.7.3.1.9ColumnlogTransferSwitchSensorSignedMinValueread-onlycurrentThe minimum sensor reading for the log period as a signed integer. The value of this OID variable should be scaled by transferSwitchSensorDecimalDigits. For ex…
1.3.6.1.4.1.13742.6.6.8NodelogCircuit
1.3.6.1.4.1.13742.6.6.8.3TablecircuitSensorLogTablenot-accessiblecurrentA list of Circuit sensor log entries. The number of entries is given by the value of panelinletCount for the Floor PDU.
1.3.6.1.4.1.13742.6.6.8.3.1RowcircuitSensorLogEntrynot-accessiblecurrentAn entry containing log objects for a circuit sensor.
1.3.6.1.4.1.13742.6.6.8.3.1.2ColumnlogCircuitSensorDataAvailableread-onlycurrentIs data available for this sensor during this measurement period?
1.3.6.1.4.1.13742.6.6.8.3.1.3ColumnlogCircuitSensorStateread-onlycurrentThe sensor state.
1.3.6.1.4.1.13742.6.6.8.3.1.4ColumnlogCircuitSensorAvgValueread-onlycurrentThe average sensor reading for the log period as an unsigned integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example,…
1.3.6.1.4.1.13742.6.6.8.3.1.5ColumnlogCircuitSensorMaxValueread-onlycurrentThe maximum sensor reading for the log period as an unsigned integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example,…
1.3.6.1.4.1.13742.6.6.8.3.1.6ColumnlogCircuitSensorMinValueread-onlycurrentThe minimum sensor reading for the log period as an unsigned integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example,…
1.3.6.1.4.1.13742.6.6.8.3.1.7ColumnlogCircuitSensorSignedAvgValueread-onlycurrentThe average sensor reading for the log period as a signed integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if…
1.3.6.1.4.1.13742.6.6.8.3.1.8ColumnlogCircuitSensorSignedMaxValueread-onlycurrentThe maximum sensor reading for the log period as a signed integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if…
1.3.6.1.4.1.13742.6.6.8.3.1.9ColumnlogCircuitSensorSignedMinValueread-onlycurrentThe minimum sensor reading for the log period as a signed integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if…
1.3.6.1.4.1.13742.6.6.8.5TablecircuitPoleSensorLogTablenot-accessiblecurrentA list of circuit pole sensor log entries. The number of entries is given by the value of panelCircuitPoleCount for the circut.
1.3.6.1.4.1.13742.6.6.8.5.1RowcircuitPoleSensorLogEntrynot-accessiblecurrentAn entry containing log objects for a circuit pole sensor.
1.3.6.1.4.1.13742.6.6.8.5.1.2ColumnlogCircuitPoleSensorDataAvailableread-onlycurrentIs data available for this sensor during this measurement period?
1.3.6.1.4.1.13742.6.6.8.5.1.3ColumnlogCircuitPoleSensorStateread-onlycurrentThe sensor state.
1.3.6.1.4.1.13742.6.6.8.5.1.4ColumnlogCircuitPoleSensorAvgValueread-onlycurrentThe average sensor reading for the log period as an unsigned integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example,…
1.3.6.1.4.1.13742.6.6.8.5.1.5ColumnlogCircuitPoleSensorMaxValueread-onlycurrentThe maximum sensor reading for the log period as an unsigned integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example,…
1.3.6.1.4.1.13742.6.6.8.5.1.6ColumnlogCircuitPoleSensorMinValueread-onlycurrentThe minimum sensor reading for the log period as an unsigned integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example,…
1.3.6.1.4.1.13742.6.6.8.5.1.7ColumnlogCircuitPoleSensorSignedAvgValueread-onlycurrentThe average sensor reading for the log period as a signed integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if…
1.3.6.1.4.1.13742.6.6.8.5.1.8ColumnlogCircuitPoleSensorSignedMaxValueread-onlycurrentThe maximum sensor reading for the log period as a signed integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if…
1.3.6.1.4.1.13742.6.6.8.5.1.9ColumnlogCircuitPoleSensorSignedMinValueread-onlycurrentThe minimum sensor reading for the log period as a signed integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if…
1.3.6.1.4.1.13742.6.9Nodeconformance
1.3.6.1.4.1.13742.6.9.1Nodecompliances
1.3.6.1.4.1.13742.6.9.1.1CompliancecomplianceRev1deprecatedThe requirements for conformance to the PDU2-MIB.
1.3.6.1.4.1.13742.6.9.1.2CompliancecomplianceRev2read-onlycurrentThe requirements for conformance to the PDU2-MIB.
1.3.6.1.4.1.13742.6.9.2Nodegroups
1.3.6.1.4.1.13742.6.9.2.1GroupconfigGroupcurrentA collection of objects representing configuration data.
1.3.6.1.4.1.13742.6.9.2.2GrouplogGroupcurrentA collection of objects providing logging (history of readings) capabilities about the PDU.
1.3.6.1.4.1.13742.6.9.2.3GroupmeasurementsGroupcurrentA collection of objects providing measurements (most recent data) capabilities. about the PDU.
1.3.6.1.4.1.13742.6.9.2.4GroupcontrolGroupcurrentA collection of objects providing the ability to control various components of a PDU.
1.3.6.1.4.1.13742.6.9.2.5GrouptrapInformationGroupcurrentA collection of objects providing information in the traps.
1.3.6.1.4.1.13742.6.9.2.9GrouptrapsGroupcurrentA collection of traps.
1.3.6.1.4.1.13742.6.9.2.10GroupreliabilityGroupcurrentA collection of objects providing reliability data.
1.3.6.1.4.1.13742.6.9.2.12GroupipAddressGroupdeprecatedA collection of objects representing configuration data.
1.3.6.1.4.1.13742.6.9.2.13GroupoldConfigGroupdeprecatedA collection of objects representing old (deprecated) configuration data.
1.3.6.1.4.1.13742.6.9.2.14GroupoldLogGroupdeprecatedA collection of objects representing old (deprecated) logging data.
1.3.6.1.4.1.13742.6.9.2.15GroupoldMeasurementsGroupdeprecatedA collection of objects representing old (deprecated) measurement data.
1.3.6.1.4.1.13742.6.9.2.16GroupoldTrapsGroupdeprecatedA collection of objects representing old (deprecated) traps.
1.3.6.1.4.1.13742.6.10Nodereliability
1.3.6.1.4.1.13742.6.10.1NodereliabilityData
1.3.6.1.4.1.13742.6.10.1.1ScalarreliabilityDataTableSequenceNumberread-onlycurrentThe sequence number for updates to the reliability data table
1.3.6.1.4.1.13742.6.10.1.2TablereliabilityDataTablenot-accessiblecurrentA list of PDU reliability data entries.
1.3.6.1.4.1.13742.6.10.1.2.1RowreliabilityDataEntrynot-accessiblecurrentAn entry containing reliability data for a particular PDU.
1.3.6.1.4.1.13742.6.10.1.2.1.1ColumnreliabilityIndexnot-accessiblecurrentIndex of the entry in the table.
1.3.6.1.4.1.13742.6.10.1.2.1.2ColumnreliabilityIdread-onlycurrentUnique ID of the entry. POH Power on hours. CB.<label>.TRIPCNT Trip count of circuit breaker with label <label>. CTRL.<serial>.<addr>.MASTER.CSUMERRLASTHOUR Nu…
1.3.6.1.4.1.13742.6.10.1.2.1.3ColumnreliabilityDataValueread-onlycurrentThe normalized value
1.3.6.1.4.1.13742.6.10.1.2.1.4ColumnreliabilityDataMaxPossibleread-onlycurrentThe maximum possible normalized value
1.3.6.1.4.1.13742.6.10.1.2.1.5ColumnreliabilityDataWorstValueread-onlycurrentThe worst normalized value seen so far
1.3.6.1.4.1.13742.6.10.1.2.1.6ColumnreliabilityDataThresholdread-onlycurrentThe normalized Threshold value
1.3.6.1.4.1.13742.6.10.1.2.1.7ColumnreliabilityDataRawUpperBytesread-onlycurrentThe Upper 4 bytes of the raw ( not normalized) data. reliabilityDataRawUpperBytes and reliabilityDataRawLowerBytes should be combined and interpreted as a sign…
1.3.6.1.4.1.13742.6.10.1.2.1.8ColumnreliabilityDataRawLowerBytesread-onlycurrentThe lower 4 bytes of the raw ( not normalized) data. reliabilityDataRawUpperBytes and reliabilityDataRawLowerBytes should be combined and interpreted as a sign…
1.3.6.1.4.1.13742.6.10.1.2.1.9ColumnreliabilityDataFlagsread-onlycurrentFlags
1.3.6.1.4.1.13742.6.10.2NodereliabilityErrorLog
1.3.6.1.4.1.13742.6.10.2.2TablereliabilityErrorLogTablenot-accessiblecurrentA list of PDU reliability ErrorLog entries.
1.3.6.1.4.1.13742.6.10.2.2.1RowreliabilityErrorLogEntrynot-accessiblecurrentAn entry containing reliability ErrorLog data for a particular PDU.
1.3.6.1.4.1.13742.6.10.2.2.1.1ColumnreliabilityErrorLogIndexnot-accessiblecurrentIndex of the entry in the table.
1.3.6.1.4.1.13742.6.10.2.2.1.2ColumnreliabilityErrorLogIdread-onlycurrentUnique ID of the entry. POH Power on hours. CB.<label>.TRIPCNT Trip count of circuit breaker with label <label>. CTRL.<serial>.<addr>.MASTER.CSUMERRLASTHOUR Nu…
1.3.6.1.4.1.13742.6.10.2.2.1.3ColumnreliabilityErrorLogValueread-onlycurrentThe normalized value
1.3.6.1.4.1.13742.6.10.2.2.1.6ColumnreliabilityErrorLogThresholdread-onlycurrentThe normalized Threshold value
1.3.6.1.4.1.13742.6.10.2.2.1.7ColumnreliabilityErrorLogRawUpperBytesread-onlycurrentThe Upper 4 bytes of the raw ( not normalized) data. reliabilityDataRawUpperBytes and reliabilityDataRawLowerBytes should be combined and interpreted as a sign…
1.3.6.1.4.1.13742.6.10.2.2.1.8ColumnreliabilityErrorLogRawLowerBytesread-onlycurrentThe lower 4 bytes of the raw ( not normalized) data. reliabilityDataRawUpperBytes and reliabilityDataRawLowerBytes should be combined and interpreted as a sign…
1.3.6.1.4.1.13742.6.10.2.2.1.9ColumnreliabilityErrorLogPOHread-onlycurrentThe time of occurrence of the event measured from the last time the PDU was powered on
1.3.6.1.4.1.13742.6.10.2.2.1.10ColumnreliabilityErrorLogTimeread-onlycurrentThe UTC time of occurrence of the event
Type Definitions
NameSyntaxStatusDescription
AddressSourceEnumerationINTEGER { static(1), dhcp(2), dhcpv6(3) }currentHow was the address obtained?
BoardTypeEnumerationINTEGER { mainController(1), inletController(2), outletController(3), meteringController(4) }currentThe types of boards.
CircuitTypeEnumerationINTEGER { onePhaseLL(1), onePhaseLN(2), onePhaseLLN(3), threePhase(4) }currentThe panel circuit types.
DaisychainMemberTypeEnumerationINTEGER { standalone(0), master(1), slave(2) }currentThe daisy chain member type.
DeviceCascadeTypeEnumerationINTEGER { bridging(0), portForwarding(1) }currentThe type of configured cascading on this device.
DeviceIdentificationParameterEnumerationINTEGER { pduName(0), sysContact(1), sysName(2), sysLocation(3) }currentThe configurable parameters.
ExternalSensorsZCoordinateUnitsEnumerationINTEGER { rackUnits(0), text(1) }currentThe units of the external Sensor Z Coordinate. rackUnits implies that the Z Coordinate for all external sensors is in rack Units (U) text implies that the Z Coordinate for all external sensors is a text string (label)
GlobalOutletStateOnStartupEnumerationINTEGER { off(0), on(1), lastKnownState(2) }currentThe global outlet state on device start up; can be overridden per outlet.
HundredthsOfAPercentageUnsigned32 (0..10000)currentData type for reporting values in hundredths of percentage, i.e. 0.01 %.
LineEnumerationINTEGER { lineL1(1), lineL2(2), lineL3(3), lineNeutral(4) }currentThe Lines: L1, L2, L3, N.
NetworkInterfaceTypeEnumerationINTEGER { wired(0), wireless(1) }currentThe type of network interface.
OutletStateOnStartupEnumerationINTEGER { off(0), on(1), lastKnownState(2), globalOutletStateOnStartup(3) }currentThe outlet state on device start up; this overrides the global value.
OutletSwitchingOperationsEnumerationINTEGER { off(0), on(1), cycle(2) }currentThe switching operations on an outlet.
OverCurrentProtectorTypeEnumerationINTEGER { ocpBREAKER1POLE(1), ocpBREAKER2POLE(2), ocpBREAKER3POLE(3), ocpFUSE(4), ocpFUSEPAIR(5), ocpRCBO2POLE(6), ocpRCBO3POLE(7), ocpRCBO4POLE(8) }currentThe types of overcurrent protectors.
PanelLayoutEnumerationINTEGER { invalid(-1), oneColumn(1), twoColumns(2) }currentThe panel circuit position layout.
PanelNumberingEnumerationINTEGER { invalid(-1), oddEven(1), sequential(2) }currentThe panel circuit position numbering scheme.
PeripheralDeviceFirmwareUpdateStateEnumerationINTEGER { started(1), successful(2), failed(3) }currentThe state of an peripheral device firmware update.
PhaseEnumerationINTEGER { phaseA(1), phaseB(2), phaseC(3), neutral(4), earth(5) }currentThe power phase.
PlugTypeEnumerationINTEGER { plugOTHER(-1), plugNONE(0), plug56P320(1), plug56P520(2), plug56P532(3), plugCS8365C(4), plugIEC320C14(5), plugIEC320C20(6), plugIEC603093WIRE250V16A(7), plugIEC603093WIRE250V20A(8), plugIEC603093WIRE250V30A(9), plugIEC603093WIRE250V32A(10), plugIEC603093WIRE250V60A(11), plugIEC603093WIRE250V63A(12), plugIEC603093WIRE250V100A(13), plugIEC603093WIRE250V125A(14), plugIEC603094WIRE250V20A(15), plugIEC603094WIRE250V30A(16), plugIEC603094WIRE250V60A(17), plugIEC603094WIRE250V100A(18), plugIEC603095WIRE208V20A(23), plugIEC603095WIRE208V30A(24), plugIEC603095WIRE208V60A(25), plugIEC603095WIRE208V100A(26), plugIEC603095WIRE415V16A(27), plugIEC603095WIRE415V32A(28), plugIEC603095WIRE415V63A(29), plugIEC603095WIRE415V125A(30), plugIEC603095WIRE480V20A(31), plugIEC603095WIRE480V30A(32), plugIEC603095WIRE480V60A(33), plugIEC603095WIRE480V100A(34), plugNEMA515P(35), plugNEMAL515P(36), plugNEMA520P(37), plugNEMAL520P(38), plugNEMAL530P(39), plugNEMAL615P(40), plugNEMAL620P(41), plugNEMAL630P(42), plugNEMAL1520P(43), plugNEMAL1530P(44), plugNEMAL2120P(45), plugNEMAL2130P(46), plugNEMAL2230P(47), plug56P320F(48), plug56PA320(49) }currentThe types of inlet plug.
PowerMeterTypeEnumerationINTEGER { singlePhase(1), splitPhase(2), threePhase(3) }currentThe power meter types
ProductTypeEnumerationINTEGER { rackPdu(0), bcm(1), transferSwitch(2), powerMeter(3) }currentThe product types.
ReceptacleTypeEnumerationINTEGER { receptacleOTHER(-1), receptacleNONE(0), receptacleBS1363(1), receptacle56P532(3), receptacleCS8364C(4), receptacleIEC320C13(5), receptacleIEC320C19(6), receptacleIEC603093WIRE250V16A(7), receptacleIEC603093WIRE250V20A(8), receptacleIEC603093WIRE250V30A(9), receptacleIEC603093WIRE250V32A(10), receptacleIEC603093WIRE250V60A(11), receptacleIEC603093WIRE250V63A(12), receptacleIEC603093WIRE250V100A(13), receptacleIEC603093WIRE250V125A(14), receptacleIEC603094WIRE250V20A(15), receptacleIEC603094WIRE250V30A(16), receptacleIEC603094WIRE250V60A(17), receptacleIEC603094WIRE250V100A(18), receptacleIEC603095WIRE208V20A(23), receptacleIEC603095WIRE208V30A(24), receptacleIEC603095WIRE208V60A(25), receptacleIEC603095WIRE208V100A(26), receptacleIEC603095WIRE415V16A(27), receptacleIEC603095WIRE415V32A(28), receptacleIEC603095WIRE415V63A(29), receptacleIEC603095WIRE415V125A(30), receptacleIEC603095WIRE480V20A(31), receptacleIEC603095WIRE480V30A(32), receptacleIEC603095WIRE480V60A(33), receptacleIEC603095WIRE480V100A(34), receptacleNEMA515R(35), receptacleNEMAL515R(36), receptacleNEMA520R(37), receptacleNEMAL520R(38), receptacleNEMAL530R(39), receptacleNEMAL615R(40), receptacleNEMAL620R(41), receptacleNEMAL630R(42), receptacleNEMAL1520R(43), receptacleNEMAL1530R(44), receptacleNEMAL2120RP(45), receptacleNEMAL2130R(46), receptacleSCHUKOTYPEE(47), receptacleSCHUKOTYPEF(48) }currentThe types of outlet receptacle.
RelayPowerLossBehaviorEnumerationINTEGER { nonLatching(0), latching(1) }currentThe type of relay behavior on power loss.
SensorStateEnumerationINTEGER { unavailable(-1), open(0), closed(1), belowLowerCritical(2), belowLowerWarning(3), normal(4), aboveUpperWarning(5), aboveUpperCritical(6), on(7), off(8), detected(9), notDetected(10), alarmed(11), ok(12), fail(14), yes(15), no(16), standby(17), one(18), two(19), inSync(20), outOfSync(21), i1OpenFault(22), i1ShortFault(23), i2OpenFault(24), i2ShortFault(25), fault(26), warning(27), critical(28), selfTest(29), nonRedundant(30) }currentThe states a sensor can be in.
SensorTypeEnumerationINTEGER { rmsCurrent(1), peakCurrent(2), unbalancedCurrent(3), rmsVoltage(4), activePower(5), apparentPower(6), powerFactor(7), activeEnergy(8), apparentEnergy(9), temperature(10), humidity(11), airFlow(12), airPressure(13), onOff(14), trip(15), vibration(16), waterDetection(17), smokeDetection(18), binary(19), contact(20), fanSpeed(21), surgeProtectorStatus(22), frequency(23), phaseAngle(24), rmsVoltageLN(25), residualCurrent(26), rcmState(27), absoluteHumidity(28), reactivePower(29), other(30), none(31), powerQuality(32), overloadStatus(33), overheatStatus(34), displacementPowerFactor(35), fanStatus(37), inletPhaseSyncAngle(38), inletPhaseSync(39), operatingState(40), activeInlet(41), illuminance(42), doorContact(43), tamperDetection(44), motionDetection(45), i1smpsStatus(46), i2smpsStatus(47), switchStatus(48) }currentThe types a sensor can be.
SensorUnitsEnumerationINTEGER { none(-1), other(0), volt(1), amp(2), watt(3), voltamp(4), wattHour(5), voltampHour(6), degreeC(7), hertz(8), percent(9), meterpersec(10), pascal(11), psi(12), g(13), degreeF(14), feet(15), inches(16), cm(17), meters(18), rpm(19), degrees(20), lux(21), grampercubicmeter(22), var(23) }currentThe sensor units.
TransferSwitchTransferReasonEnumerationINTEGER { unknown(0), startup(1), manualTransfer(2), automaticReTransfer(3), powerFailure(4), powerQuality(5), overloadAlarm(6), overheatAlarm(7), internalFailure(8) }currentTransfer Switch Transfer Reason
URLOCTET STRING (SIZE (0..255))currentA Uniform Resource Locator (URL), as defined in RFC1738.