PDU2-MIB

920 objects
This MIB describes the SNMP functions of the Raritan PX2, PX3 and BCM2 series power distribution units by Raritan.
Imported Objects
INET-ADDRESS-MIBInetAddress InetAddressType InetPortNumber
RFC1213-MIBsysContact sysLocation sysName
SNMPv2-CONFMODULE-COMPLIANCE NOTIFICATION-GROUP OBJECT-GROUP
SNMPv2-SMIenterprises Integer32 IpAddress MODULE-IDENTITY NOTIFICATION-TYPE OBJECT-TYPE Unsigned32
SNMPv2-TCDisplayString MacAddress RowPointer TEXTUAL-CONVENTION TruthValue
OIDNameAccessStatusDescription
1.3.6.1.4.1.13742IdentityraritanforofThis MIB describes the SNMP functions of the Raritan PX2, PX3 and BCM2 series power distribution units by Raritan.
1.3.6.1.4.1.13742.6Nodepdu2
1.3.6.1.4.1.13742.6.0Nodetraps
1.3.6.1.4.1.13742.6.0.0NodetrapInformation
1.3.6.1.4.1.13742.6.0.0.1TabletrapInformationTablenot-accessiblecurrentA group of objects used exclusively in traps. This is a table for historic reasons; it can't be queried from the SNMP agent.
1.3.6.1.4.1.13742.6.0.0.1.1RowtrapInformationEntrynot-accessiblecurrentAn entry containing objects used in traps.
1.3.6.1.4.1.13742.6.0.0.1.1.2ColumnuserNameread-onlycurrentThe user currently logged in.
1.3.6.1.4.1.13742.6.0.0.1.1.3ColumntargetUserread-onlycurrentThe user added, deleted, or modified.
1.3.6.1.4.1.13742.6.0.0.1.1.5ColumnimageVersionread-onlycurrentThe version of the upgrade image.
1.3.6.1.4.1.13742.6.0.0.1.1.6ColumnroleNameread-onlycurrentThe role added, deleted, or modified.
1.3.6.1.4.1.13742.6.0.0.1.1.7ColumnsmtpMessageRecipientsread-onlycurrentComma separated list of SMTP message recipients
1.3.6.1.4.1.13742.6.0.0.1.1.8ColumnsmtpServerread-onlycurrentThe IP address/host name of the SMTP server
1.3.6.1.4.1.13742.6.0.0.2ScalaroldSensorStateaccessible-for-notifycurrentThe old sensor state used in sensor state transition traps.
1.3.6.1.4.1.13742.6.0.0.3ScalarpduNumberaccessible-for-notifycurrentA unique value for each PDU. Its value ranges between 1 and the value of pduCount.
1.3.6.1.4.1.13742.6.0.0.5ScalarinletPoleNumberaccessible-for-notifycurrentA unique value for each inlet pole. Its value ranges between 1 and the value of inletPoleCount.
1.3.6.1.4.1.13742.6.0.0.7ScalaroutletPoleNumberaccessible-for-notifycurrentA unique value for each outlet pole. Its value ranges between 1 and the value of outletPoleCount.
1.3.6.1.4.1.13742.6.0.0.8ScalarexternalSensorNumberaccessible-for-notifycurrentA unique value for each external sensor. Its value ranges between 1 and the value of externalSensorCount.
1.3.6.1.4.1.13742.6.0.0.10ScalartypeOfSensoraccessible-for-notifycurrentThe type of sensor.
1.3.6.1.4.1.13742.6.0.0.11ScalarerrorDescriptionaccessible-for-notifycurrentDescription of the error
1.3.6.1.4.1.13742.6.0.0.12ScalardeviceChangedParameteraccessible-for-notifycurrentIdentifies the parameter that has changed.
1.3.6.1.4.1.13742.6.0.0.13ScalarchangedParameterNewValueaccessible-for-notifycurrentThe new value of the changed parameter
1.3.6.1.4.1.13742.6.0.0.14ScalarlhxSupportEnabledaccessible-for-notifycurrentThe new enabled state for Schroff LHX support.
1.3.6.1.4.1.13742.6.0.0.15ScalarwebcamModelaccessible-for-notifycurrentThe model of the webcam
1.3.6.1.4.1.13742.6.0.0.16ScalarwebcamConnectionPortaccessible-for-notifycurrentThe port to which the webcam is connected
1.3.6.1.4.1.13742.6.0.0.18ScalaragentInetPortNumberaccessible-for-notifycurrentThe UDP port number used for accessing the SNMP agent on the device. This is necessary to identify the slave in a port forwarding cascade.
1.3.6.1.4.1.13742.6.0.0.19ScalarperipheralDeviceRomcodeaccessible-for-notifycurrentThe 1-wire romcode of a peripheral device
1.3.6.1.4.1.13742.6.0.0.20ScalarperipheralDeviceFirmwareUpdateStateaccessible-for-notifycurrentThe firmware update state of a peripheral device
1.3.6.1.4.1.13742.6.0.0.21ScalarcircuitNumberaccessible-for-notifycurrentA unique value for each circuit. Defined as follows: circuitNumber = 1000 * panelId + circuitPosition Examples: 1045 is the the circuit on panel 1 with lowest …
1.3.6.1.4.1.13742.6.0.0.22ScalarcircuitPoleNumberaccessible-for-notifycurrentA unique value for each circuit pole.
1.3.6.1.4.1.13742.6.0.0.23ScalarphoneNumberaccessible-for-notifycurrentThe phone number of e.g. an SMS receiver.
1.3.6.1.4.1.13742.6.0.0.24ScalarsmartCardReaderIdaccessible-for-notifycurrentThe ID of a smartcard reader.
1.3.6.1.4.1.13742.6.0.0.25ScalarsmartCardTimestampaccessible-for-notifycurrentThe timestamp indicating when the smartcard was inserted or removed. It is measured in seconds since January 1, 1970 UTC
1.3.6.1.4.1.13742.6.0.0.26ScalarsmartCardTypeaccessible-for-notifycurrentThe type of a smartcard.
1.3.6.1.4.1.13742.6.0.0.27ScalarsmartCardIdaccessible-for-notifycurrentThe ID/serial number of a smartcard.
1.3.6.1.4.1.13742.6.0.0.28ScalarsuspectedTripCauseLabelaccessible-for-notifycurrentThe label of the outlet that likely caused the OCP trip, if it can be determined.
1.3.6.1.4.1.13742.6.0.1NotificationsystemStartedcurrentThe system has started.
1.3.6.1.4.1.13742.6.0.2NotificationsystemResetcurrentThe system was rebooted.
1.3.6.1.4.1.13742.6.0.3NotificationuserLogincurrentA user logged in.
1.3.6.1.4.1.13742.6.0.4NotificationuserLogoutcurrentA user logged out.
1.3.6.1.4.1.13742.6.0.5NotificationuserAuthenticationFailurecurrentA user authentication attempt failed.
1.3.6.1.4.1.13742.6.0.8NotificationuserSessionTimeoutcurrentA user session timed out.
1.3.6.1.4.1.13742.6.0.11NotificationuserAddedcurrentA user account was added to the system.
1.3.6.1.4.1.13742.6.0.12NotificationuserModifiedcurrentA user account was modified.
1.3.6.1.4.1.13742.6.0.13NotificationuserDeletedcurrentA user account was deleted from the system.
1.3.6.1.4.1.13742.6.0.14NotificationroleAddedcurrentA role was added to the system.
1.3.6.1.4.1.13742.6.0.15NotificationroleModifiedcurrentA role was modified.
1.3.6.1.4.1.13742.6.0.16NotificationroleDeletedcurrentA role was deleted from the system.
1.3.6.1.4.1.13742.6.0.20NotificationdeviceUpdateStartedcurrentThe device firmware update has started.
1.3.6.1.4.1.13742.6.0.21NotificationdeviceUpdateCompletedcurrentThe device firmware update has completed.
1.3.6.1.4.1.13742.6.0.22NotificationuserBlockedcurrentA blocked user tried to log in.
1.3.6.1.4.1.13742.6.0.23NotificationpowerControlcurrentAn outlet switching operation has been performed. Note that measurementsOutletSensorState represents the state of the outlet at the time the trap was sent. Thi…
1.3.6.1.4.1.13742.6.0.24NotificationuserPasswordChangedcurrentUser password was changed.
1.3.6.1.4.1.13742.6.0.28NotificationpasswordSettingsChangedcurrentStrong password settings changed.
1.3.6.1.4.1.13742.6.0.38NotificationfirmwareValidationFailedcurrentValidation of an uploaded firmware image failed.
1.3.6.1.4.1.13742.6.0.41NotificationlogFileClearedcurrentThe event log has been cleared.
1.3.6.1.4.1.13742.6.0.53NotificationbulkConfigurationSavedcurrentA bulk configuration file was downloaded from the device.
1.3.6.1.4.1.13742.6.0.54NotificationbulkConfigurationCopiedcurrentA bulk configuration file was copied to the device.
1.3.6.1.4.1.13742.6.0.60NotificationpduSensorStateChangedeprecatedUnit-level sensor state change. Which value field to use depends on the metadata of the sensor. measurementsUnitSensorValue is undefined for sensors which can …
1.3.6.1.4.1.13742.6.0.61NotificationinletSensorStateChangecurrentInlet sensor state change. Which value field to use depends on the metadata of the sensor. measurementsInletSensorValue is undefined for sensors which can have…
1.3.6.1.4.1.13742.6.0.62NotificationinletPoleSensorStateChangecurrentInlet pole sensor state change. Which value field to use depends on the metadata of the sensor. measurementsInletPoleSensorValue is undefined for sensors which…
1.3.6.1.4.1.13742.6.0.63NotificationoutletSensorStateChangecurrentOutlet sensor state change. Which value field to use depends on the metadata of the sensor. measurementsOutletSensorValue is undefined for sensors which can ha…
1.3.6.1.4.1.13742.6.0.64NotificationoutletPoleSensorStateChangecurrentOutlet pole sensor state change. Which value field to use depends on the metadata of the sensor. measurementsOutletPoleSensorValue is undefined for sensors whi…
1.3.6.1.4.1.13742.6.0.65NotificationoverCurrentProtectorSensorStateChangecurrentOvercurrent protector sensor state change. Which value field to use depends on the metadata of the sensor. measurementsOverCurrentProtectorSensorValue is undef…
1.3.6.1.4.1.13742.6.0.66NotificationexternalSensorStateChangecurrentExternal sensor state change.
1.3.6.1.4.1.13742.6.0.67NotificationsmtpMessageTransmissionFailurecurrentSMTP message transmission failure
1.3.6.1.4.1.13742.6.0.68NotificationldapErrorcurrentAn LDAP error occurred; errorDescription describes the error
1.3.6.1.4.1.13742.6.0.70NotificationdeviceUpdateFailedcurrentThe device firmware update has failed.
1.3.6.1.4.1.13742.6.0.71NotificationloadSheddingModeEnteredcurrentThe PDU has entered load shedding mode
1.3.6.1.4.1.13742.6.0.72NotificationloadSheddingModeExitedcurrentThe PDU has exited load shedding mode
1.3.6.1.4.1.13742.6.0.73NotificationpingServerEnabledcurrentThe ping feature has been enabled for a server.
1.3.6.1.4.1.13742.6.0.74NotificationpingServerDisabledcurrentThe ping feature has been disabled for a server.
1.3.6.1.4.1.13742.6.0.75NotificationserverNotReachablecurrentA monitored server has become unreachable.
1.3.6.1.4.1.13742.6.0.76NotificationserverReachablecurrentA monitored server has become reachable.
1.3.6.1.4.1.13742.6.0.77NotificationrfCodeTagConnecteddeprecatedAn RF-Code tag has been connected.
1.3.6.1.4.1.13742.6.0.78NotificationrfCodeTagDisconnecteddeprecatedAn RF-Code tag has been disconnected.
1.3.6.1.4.1.13742.6.0.79NotificationdeviceIdentificationChangedcurrentA device identification parameter has been changed.
1.3.6.1.4.1.13742.6.0.80NotificationusbSlaveConnectedcurrentConnectivity to downstream slave has been established. It applies to the following interfaces: USB Ethernet This trap is sent only if deviceCascadeType is port…
1.3.6.1.4.1.13742.6.0.81NotificationusbSlaveDisconnectedcurrentConnectivity to downstream slave has been lost It applies to the following interfaces: USB Ethernet This trap is sent only if deviceCascadeType is portForwardi…
1.3.6.1.4.1.13742.6.0.82NotificationlhxSupportChangedcurrentSchroff LHX support has been enabled or disabled.
1.3.6.1.4.1.13742.6.0.83NotificationuserAcceptedRestrictedServiceAgreementcurrentA user accepted the Restricted Service Agreement.
1.3.6.1.4.1.13742.6.0.84NotificationuserDeclinedRestrictedServiceAgreementcurrentA user declined the Restricted Service Agreement.
1.3.6.1.4.1.13742.6.0.85NotificationwireSensorStateChangedeprecatedWire sensor state change.
1.3.6.1.4.1.13742.6.0.86NotificationtransferSwitchSensorStateChangecurrentTransfer switch sensor state change. Which value field to use depends on the metadata of the sensor. measurementsTransferSwitchSensorValue is undefined for sen…
1.3.6.1.4.1.13742.6.0.88NotificationdeviceSettingsSavedcurrentA configuration backup has been downloaded from the device.
1.3.6.1.4.1.13742.6.0.89NotificationdeviceSettingsRestoredcurrentA configuration backup has been restored to the device.
1.3.6.1.4.1.13742.6.0.90NotificationwebcamInsertedcurrentA webcam has been connected.
1.3.6.1.4.1.13742.6.0.91NotificationwebcamRemovedcurrentA webcam has been disconnected.
1.3.6.1.4.1.13742.6.0.92NotificationinletEnabledcurrentPDU operation has been enabled for an inlet
1.3.6.1.4.1.13742.6.0.93NotificationinletDisabledcurrentPDU operation has been disabled for an inlet
1.3.6.1.4.1.13742.6.0.94NotificationserverConnectivityUnrecoverablecurrentThe connection to a monitored server could not be recovered.
1.3.6.1.4.1.13742.6.0.95NotificationradiusErrorcurrentA Radius error occurred; errorDescription describes the error
1.3.6.1.4.1.13742.6.0.96NotificationserverReachabilityErrorcurrentServer reachability error occurred; errorDescription describes the error. This trap is sent when the Error state is entered. Reasons for transitioning to the E…
1.3.6.1.4.1.13742.6.0.97NotificationinletSensorResetcurrentAn inlet sensor was reset.
1.3.6.1.4.1.13742.6.0.98NotificationoutletSensorResetcurrentAn outlet sensor was reset.
1.3.6.1.4.1.13742.6.0.99NotificationunknownPeripheralDeviceAttachedcurrentAn unsupported peripheral device was attached.
1.3.6.1.4.1.13742.6.0.100NotificationperipheralDeviceFirmwareUpdatecurrentThe firmware update state of a peripheral device changed while performing update to peripheralDevicePackageFirmwareVersion.
1.3.6.1.4.1.13742.6.0.101NotificationunitSensorResetcurrentA unit-level sensor was reset.
1.3.6.1.4.1.13742.6.0.102NotificationunitSensorStateChangecurrentUnit-level sensor state change. Which value field to use depends on the metadata of the sensor. measurementsUnitSensorValue is undefined for sensors which can …
1.3.6.1.4.1.13742.6.0.103NotificationcircuitSensorStateChangecurrentBCM2/PMC branch circuit sensor state change. Which value field to use depends on the metadata of the sensor. measurementsCircuitSensorValue is undefined for se…
1.3.6.1.4.1.13742.6.0.104NotificationcircuitPoleSensorStateChangecurrentBCM2/PMC circuit pole sensor state change. Which value field to use depends on the metadata of the sensor. measurementsCircuitPoleSensorValue is undefined for …
1.3.6.1.4.1.13742.6.0.105NotificationcircuitAddedcurrentA new branch circuit has been configured
1.3.6.1.4.1.13742.6.0.106NotificationcircuitDeletedcurrentA configured branch circuit has been deleted
1.3.6.1.4.1.13742.6.0.107NotificationcircuitModifiedcurrentA configured branch circuit has been modified
1.3.6.1.4.1.13742.6.0.108NotificationcircuitSensorResetcurrentAn BCM2/PMC branch circuit sensor was reset.
1.3.6.1.4.1.13742.6.0.109NotificationpowerMeterAddedcurrentA new power meter or panel has been configured
1.3.6.1.4.1.13742.6.0.110NotificationpowerMeterDeletedcurrentA configured power meter has been deleted
1.3.6.1.4.1.13742.6.0.111NotificationpowerMeterModifiedcurrentA configured power meter has been modified
1.3.6.1.4.1.13742.6.0.112NotificationsmsMessageTransmissionFailurecurrentSending an SMS message failed.
1.3.6.1.4.1.13742.6.0.113NotificationsmartCardInsertedcurrentA smartcard was inserted into a card reader.
1.3.6.1.4.1.13742.6.0.114NotificationsmartCardRemovedcurrentA smartcard was removed from a card reader.
1.3.6.1.4.1.13742.6.1Nodeboard
1.3.6.1.4.1.13742.6.2Nodeenvironmental
1.3.6.1.4.1.13742.6.3Nodeconfiguration
1.3.6.1.4.1.13742.6.3.1ScalarpduCountread-onlycurrentThe number of PDUs managed by this MIB. For PX2, PX3 and PX3TS, pduCount is always 1 For BCM2, pduCount is the number of power meters plus 1 (for the main cont…
1.3.6.1.4.1.13742.6.3.2Nodeunit
1.3.6.1.4.1.13742.6.3.2.1TablenameplateTablenot-accessiblecurrentA list of PDU nameplate entries. The number of entries is given by the value of pduCount.
1.3.6.1.4.1.13742.6.3.2.1.1RownameplateEntrynot-accessiblecurrentAn entry providing PDU nameplate information.
1.3.6.1.4.1.13742.6.3.2.1.1.1ColumnpduIdnot-accessiblecurrentA unique value for each PDU or power meter. For PX2, PX3 and PX3TS, pduId is always 1 For BCM2, pduId can be: - 0 for the main controller - The meter ID (rotar…
1.3.6.1.4.1.13742.6.3.2.1.1.2ColumnpduManufacturerread-onlycurrentThe PDU manufacturer.
1.3.6.1.4.1.13742.6.3.2.1.1.3ColumnpduModelread-onlycurrentThe PDU model name.
1.3.6.1.4.1.13742.6.3.2.1.1.4ColumnpduSerialNumberread-onlycurrentThe PDU serial number.
1.3.6.1.4.1.13742.6.3.2.1.1.5ColumnpduRatedVoltageread-onlycurrentThe PDU voltage rating.
1.3.6.1.4.1.13742.6.3.2.1.1.6ColumnpduRatedCurrentread-onlycurrentThe PDU current rating.
1.3.6.1.4.1.13742.6.3.2.1.1.7ColumnpduRatedFrequencyread-onlycurrentThe PDU frequency rating.
1.3.6.1.4.1.13742.6.3.2.1.1.8ColumnpduRatedVAread-onlycurrentThe PDU VA (VoltAmps) rating.
1.3.6.1.4.1.13742.6.3.2.1.1.9ColumnpduImageread-onlycurrentThe URL of the wiring diagram for this PDU.
1.3.6.1.4.1.13742.6.3.2.2TableunitConfigurationTablenot-accessiblecurrentA list of PDU configuration entries. The number of entries is given by the value of pduCount.
1.3.6.1.4.1.13742.6.3.2.2.1RowunitConfigurationEntrynot-accessiblecurrentAn entry containing configuration objects for a particular PDU.
1.3.6.1.4.1.13742.6.3.2.2.1.2ColumninletCountread-onlycurrentThe number of inlets.
1.3.6.1.4.1.13742.6.3.2.2.1.3ColumnoverCurrentProtectorCountread-onlycurrentThe number of overcurrent protectors.
1.3.6.1.4.1.13742.6.3.2.2.1.4ColumnoutletCountread-onlycurrentThe number of outlets.
1.3.6.1.4.1.13742.6.3.2.2.1.5ColumninletControllerCountread-onlycurrentThe number of inlet controllers.
1.3.6.1.4.1.13742.6.3.2.2.1.6ColumnoutletControllerCountread-onlycurrentThe number of outlet controllers.
1.3.6.1.4.1.13742.6.3.2.2.1.7ColumnexternalSensorCountread-onlycurrentThe maximum supported number of external sensors. This value is fixed and does not reflect how many sensors are actually connected.
1.3.6.1.4.1.13742.6.3.2.2.1.8ColumnpxIPAddressread-onlydeprecatedThe current IP address. A value of 0.0.0.0 indicates an error or an unset option.
1.3.6.1.4.1.13742.6.3.2.2.1.9Columnnetmaskread-onlydeprecatedThe current netmask. A value of 0.0.0.0 indicates an error or an unset option.
1.3.6.1.4.1.13742.6.3.2.2.1.10Columngatewayread-onlydeprecatedThe current gateway. A value of 0.0.0.0 indicates an error or an unset option.
1.3.6.1.4.1.13742.6.3.2.2.1.11ColumnpxMACAddressread-onlydeprecatedThe current MAC address. If bridge interface is enabled, then equal to the MAC address of Ethernet 1 else if Ethernet 1 is enabled, then equal to the MAC addre…
1.3.6.1.4.1.13742.6.3.2.2.1.12ColumnutcOffsetread-onlycurrentThe current UTC offset.
1.3.6.1.4.1.13742.6.3.2.2.1.13ColumnpduNameread-writecurrentThe user-defined name for the PDU.
1.3.6.1.4.1.13742.6.3.2.2.1.14ColumnnetworkInterfaceTyperead-onlydeprecatedThe network interface type: wired or wireless. If only the Wireless interface is enabled, then equal to wireless else equal to wired
1.3.6.1.4.1.13742.6.3.2.2.1.34ColumnexternalSensorsZCoordinateUnitsread-writecurrentExternal sensor Z coordinate units: freeform text or rack units (U) Default is U.
1.3.6.1.4.1.13742.6.3.2.2.1.35ColumnunitDeviceCapabilitiesread-onlycurrentA bit string indicating which unit sensors are available.
1.3.6.1.4.1.13742.6.3.2.2.1.36ColumnoutletSequencingDelayread-writedeprecatedIt is deprecated. This is an alias for inrushGuardDelay
1.3.6.1.4.1.13742.6.3.2.2.1.37ColumnglobalOutletPowerCyclingPowerOffPeriodread-writecurrentThe power-off period when an outlet is cycled; applies to all outlets unless overridden at the outlet level; specified in seconds; 1 <= value <= 3600 seconds.
1.3.6.1.4.1.13742.6.3.2.2.1.38ColumnglobalOutletStateOnStartupread-writecurrentThe outlet state on device startup; applies to all outlets unless overridden at the outlet level. Note that this value is ignored if relayBehaviorOnPowerLoss i…
1.3.6.1.4.1.13742.6.3.2.2.1.39ColumnoutletPowerupSequenceread-writecurrentThe sequence in which will the outlets will be switched on under the following conditions. 1) Switch all outlets on operation is executed 2) Power to the PDU i…
1.3.6.1.4.1.13742.6.3.2.2.1.40ColumnpduPowerCyclingPowerOffPeriodread-writecurrentWhen power to the PX is cycled (either manually or because of a temporary power loss), this number determines how many seconds the PX will wait before it provi…
1.3.6.1.4.1.13742.6.3.2.2.1.41ColumnpduDaisychainMemberTyperead-onlycurrentThe daisy chain member type.
1.3.6.1.4.1.13742.6.3.2.2.1.42ColumnmanagedExternalSensorCountread-onlycurrentThe number of managed external sensors
1.3.6.1.4.1.13742.6.3.2.2.1.50ColumnpxInetAddressTyperead-onlydeprecatedThe type of address format This object is deprecated in favor of ipAddressTable from the IP-MIB (rfc4293).
1.3.6.1.4.1.13742.6.3.2.2.1.51ColumnpxInetIPAddressread-onlydeprecatedThe current IP address. A value of 0.0.0.0 indicates an error or an unset option. This object is deprecated in favor of ipAddressTable from the IP-MIB (rfc4293…
1.3.6.1.4.1.13742.6.3.2.2.1.52ColumnpxInetNetmaskread-onlydeprecatedThe current netmask. A value of 0.0.0.0 indicates an error or an unset option. This object is deprecated in favor of ipAddressTable from the IP-MIB (rfc4293). …
1.3.6.1.4.1.13742.6.3.2.2.1.53ColumnpxInetGatewayread-onlydeprecatedThe current gateway. A value of 0.0.0.0 indicates an error or an unset option. This object is deprecated in favor of ipAddressTable from the IP-MIB (rfc4293). …
1.3.6.1.4.1.13742.6.3.2.2.1.55ColumnloadSheddingread-writecurrentEnter/Exit Load Shedding Mode
1.3.6.1.4.1.13742.6.3.2.2.1.56ColumnserverCountread-onlycurrentThe number of servers monitored with the server reachability feature
1.3.6.1.4.1.13742.6.3.2.2.1.57ColumninrushGuardDelayread-writecurrentThe time interval between switching on two outlets; specified in milliseconds; 100 <= value <= 100000 milliseconds.
1.3.6.1.4.1.13742.6.3.2.2.1.58ColumncascadedDeviceConnectedread-onlycurrentIndicates whether another PX2 is connected using an USB cable to the USB-A port of this PX2 in a cascaded configuration.
1.3.6.1.4.1.13742.6.3.2.2.1.59ColumnsynchronizeWithNTPServerread-writecurrentIndicates whether time is synchronized with an NTP server.
1.3.6.1.4.1.13742.6.3.2.2.1.60ColumnuseDHCPProvidedNTPServerread-writeobsolete**NOTE: This object is obsolete. Its functionality has been replaced by the following: - If at least one of firstNTPServerAddress and secondNTPServerAddress ha…
1.3.6.1.4.1.13742.6.3.2.2.1.61ColumnfirstNTPServerAddressTyperead-writecurrentRepresents the type of the corresponding instance of firstNTPServerAddress object. When setting this value, be sure that firstNTPServerAddress is of this addre…
1.3.6.1.4.1.13742.6.3.2.2.1.62ColumnfirstNTPServerAddressread-writecurrentThe address of the primary NTP server. When setting this value, be sure that it is of the type specified in firstNTPServerAddressType, e.g. by setting both of …
1.3.6.1.4.1.13742.6.3.2.2.1.63ColumnsecondNTPServerAddressTyperead-writecurrentRepresents the type of the corresponding instance of secondNTPServerAddress object. When setting this value, be sure that secondNTPServerAddress is of this add…
1.3.6.1.4.1.13742.6.3.2.2.1.64ColumnsecondNTPServerAddressread-writecurrentThe address of the second NTP server. When setting this value, be sure that it is of the type specified in secondNTPServerAddressType, e.g. by setting both of …
1.3.6.1.4.1.13742.6.3.2.2.1.65ColumnwireCountread-onlydeprecatedThe number of wire objects in the PDU topology. This feature is no longer used, the returned value is always 0.
1.3.6.1.4.1.13742.6.3.2.2.1.66ColumntransferSwitchCountread-onlycurrentThe number of transfer switches.
1.3.6.1.4.1.13742.6.3.2.2.1.67ColumnproductTyperead-onlycurrentThe product type (PDU, BCM, transfer switch or power meter).
1.3.6.1.4.1.13742.6.3.2.2.1.68ColumnmeteringControllerCountread-onlycurrentThe number of metering controllers.
1.3.6.1.4.1.13742.6.3.2.2.1.69ColumnrelayBehaviorOnPowerLossread-writecurrentThe relay behavior on power loss (latching or non-latching).
1.3.6.1.4.1.13742.6.3.2.2.1.70ColumndeviceCascadeTyperead-writecurrentThe type of network cascade this device is part of (none, bridging or port forwarding).
1.3.6.1.4.1.13742.6.3.2.2.1.71ColumndeviceCascadePositionread-onlycurrentThe position of the device in the cascade chain. Only supported in port forwarding mode, 0 otherwise.
1.3.6.1.4.1.13742.6.3.2.2.1.72ColumnperipheralDevicesAutoManagementread-writecurrentDefines whether newly-connected peripheral devices are automatically assigned to an unused slot.
1.3.6.1.4.1.13742.6.3.2.2.1.73ColumnfrontPanelOutletSwitchingread-writecurrentEnables/disables switching of outlets using the PDU front panel.
1.3.6.1.4.1.13742.6.3.2.2.1.74ColumnfrontPanelRCMSelfTestread-writecurrentEnables/disables front panel RCM self-test.
1.3.6.1.4.1.13742.6.3.2.2.1.75ColumnfrontPanelActuatorControlread-writecurrentEnables/disables front panel peripheral actuator control.
1.3.6.1.4.1.13742.6.3.2.2.1.76ColumncircuitCountread-onlycurrentThe number of branch circuits in a panel.
1.3.6.1.4.1.13742.6.3.2.2.1.77ColumnactiveDNSServerCountread-onlycurrentThe number of active DNS servers
1.3.6.1.4.1.13742.6.3.2.2.1.78ColumnactiveNTPServerCountread-onlycurrentThe number of active NTP servers
1.3.6.1.4.1.13742.6.3.2.3TablecontrollerConfigurationTablenot-accessiblecurrentA list of entries for the boards in a PDU. The number of entries is one more than the sum of inletControllerCount, outletControllerCount and meterControllerCou…
1.3.6.1.4.1.13742.6.3.2.3.1RowcontrollerConfigurationEntrynot-accessiblecurrentAn entry containing objects for a controller.
1.3.6.1.4.1.13742.6.3.2.3.1.1ColumnboardTypenot-accessiblecurrentThe type of board.
1.3.6.1.4.1.13742.6.3.2.3.1.2ColumnboardIndexnot-accessiblecurrentA unique value for each controller.
1.3.6.1.4.1.13742.6.3.2.3.1.4ColumnboardVersionread-onlycurrentThe board hardware version.
1.3.6.1.4.1.13742.6.3.2.3.1.6ColumnboardFirmwareVersionread-onlycurrentThe firmware version.
1.3.6.1.4.1.13742.6.3.2.3.1.8ColumnboardFirmwareTimeStampread-onlycurrentThe time when the board firmware was updated as UNIX timestamp. It is measured in seconds since January 1, 1970 (midnight UTC/GMT)
1.3.6.1.4.1.13742.6.3.2.4TablelogConfigurationTablenot-accessiblecurrentA table of parameters for the data logging feature. The number of entries is given by the value of pduCount.
1.3.6.1.4.1.13742.6.3.2.4.1RowlogConfigurationEntrynot-accessiblecurrentAn entry containing data logging parameters for a particular PDU.
1.3.6.1.4.1.13742.6.3.2.4.1.1ColumndataLoggingread-writecurrentDefines whether sensor data logging is enabled.
1.3.6.1.4.1.13742.6.3.2.4.1.2ColumnmeasurementPeriodread-onlycurrentData collection periodicity. This is the periodicity of the data collected by the PDU. This value is fixed at 1 second.
1.3.6.1.4.1.13742.6.3.2.4.1.3ColumnmeasurementsPerLogEntryread-writecurrentThe number of measurements aggregated into a data log entry.
1.3.6.1.4.1.13742.6.3.2.4.1.4ColumnlogSizeread-onlycurrentThe capacity (number of entries) of the data log.
1.3.6.1.4.1.13742.6.3.2.4.1.5ColumndataLoggingEnableForAllSensorsread-writecurrentOperation to control data logging for all sensors: - when set to true, all *SensorLogAvailable OIDs are set to true - when set to false, all *SensorLogAvailabl…
1.3.6.1.4.1.13742.6.3.2.5TableunitSensorConfigurationTablenot-accessiblecurrentA list of unit-level sensors for a PDU.
1.3.6.1.4.1.13742.6.3.2.5.1RowunitSensorConfigurationEntrynot-accessiblecurrentAn entry containing unit sensor parameters.
1.3.6.1.4.1.13742.6.3.2.5.1.1ColumnsensorTypenot-accessiblecurrentThe type of sensor.
1.3.6.1.4.1.13742.6.3.2.5.1.4ColumnunitSensorLogAvailableread-writecurrentIs data logging enabled for the sensor?
1.3.6.1.4.1.13742.6.3.2.5.1.6ColumnunitSensorUnitsread-onlycurrentThe unit in which the sensor reading is reported. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.2.5.1.7ColumnunitSensorDecimalDigitsread-onlycurrentThe number of digits displayed to the right of the decimal point.
1.3.6.1.4.1.13742.6.3.2.5.1.8ColumnunitSensorAccuracyread-onlydeprecatedThe accuracy: the maximum relative difference (in percent) between measurement and the actual value. This parameter does not apply to sensors without numerical…
1.3.6.1.4.1.13742.6.3.2.5.1.9ColumnunitSensorResolutionread-onlycurrentThe resolution: the minimum difference between any two measured values The value of this OID variable should be scaled by unitSensorDecimalDigits. For example,…
1.3.6.1.4.1.13742.6.3.2.5.1.10ColumnunitSensorToleranceread-onlydeprecatedThe tolerance: the maximum difference between measurement and the actual value. The value of this OID variable should be scaled by (unitSensorDecimalDigits + 1…
1.3.6.1.4.1.13742.6.3.2.5.1.11ColumnunitSensorMaximumread-onlycurrentThe largest possible reading as an unsigned integer. The value of this OID variable should be scaled by unitSensorDecimalDigits. For example, if the value is 1…
1.3.6.1.4.1.13742.6.3.2.5.1.12ColumnunitSensorMinimumread-onlycurrentThe smallest possible reading as an unsigned integer. The value of this OID variable should be scaled by unitSensorDecimalDigits. For example, if the value is …
1.3.6.1.4.1.13742.6.3.2.5.1.13ColumnunitSensorHysteresisread-writecurrentThe hysteresis used when crossing a threshold towards the normal state. The value of this OID variable should be scaled by unitSensorDecimalDigits. For example…
1.3.6.1.4.1.13742.6.3.2.5.1.14ColumnunitSensorStateChangeDelayread-writecurrentThe delay measured in samples before a state is asserted. If the value is zero, then the state is asserted as soon as it is detected; if it is non-zero, say n,…
1.3.6.1.4.1.13742.6.3.2.5.1.21ColumnunitSensorLowerCriticalThresholdread-writecurrentThe lower critical threshold as an unsigned integer. The value of this OID variable should be scaled by unitSensorDecimalDigits. For example, if the value is 1…
1.3.6.1.4.1.13742.6.3.2.5.1.22ColumnunitSensorLowerWarningThresholdread-writecurrentThe lower warning threshold as an unsigned integer. The value of this OID variable should be scaled by unitSensorDecimalDigits. For example, if the value is 1 …
1.3.6.1.4.1.13742.6.3.2.5.1.23ColumnunitSensorUpperCriticalThresholdread-writecurrentThe upper critical threshold as an unsigned integer. The value of this OID variable should be scaled by unitSensorDecimalDigits. For example, if the value is 1…
1.3.6.1.4.1.13742.6.3.2.5.1.24ColumnunitSensorUpperWarningThresholdread-writecurrentThe upper warning threshold as an unsigned integer. The value of this OID variable should be scaled by unitSensorDecimalDigits. For example, if the value is 1 …
1.3.6.1.4.1.13742.6.3.2.5.1.25ColumnunitSensorEnabledThresholdsread-writecurrentA bit string indicating which thresholds are enabled. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.2.5.1.26ColumnunitSensorSignedMaximumread-onlycurrentThe largest possible reading as a signed integer. The value of this OID variable should be scaled by unitSensorDecimalDigits. For example, if the value is 1 an…
1.3.6.1.4.1.13742.6.3.2.5.1.27ColumnunitSensorSignedMinimumread-onlycurrentThe smallest possible reading as a signed integer. The value of this OID variable should be scaled by unitSensorDecimalDigits. For example, if the value is 1 a…
1.3.6.1.4.1.13742.6.3.2.5.1.28ColumnunitSensorSignedLowerCriticalThresholdread-writecurrentThe lower critical threshold as a signed integer. The value of this OID variable should be scaled by unitSensorDecimalDigits. For example, if the value is 1 an…
1.3.6.1.4.1.13742.6.3.2.5.1.29ColumnunitSensorSignedLowerWarningThresholdread-writecurrentThe lower warning threshold as a signed integer. The value of this OID variable should be scaled by unitSensorDecimalDigits. For example, if the value is 1 and…
1.3.6.1.4.1.13742.6.3.2.5.1.30ColumnunitSensorSignedUpperCriticalThresholdread-writecurrentThe upper critical threshold as a signed integer. The value of this OID variable should be scaled by unitSensorDecimalDigits. For example, if the value is 1 an…
1.3.6.1.4.1.13742.6.3.2.5.1.31ColumnunitSensorSignedUpperWarningThresholdread-writecurrentThe upper warning threshold as a signed integer. The value of this OID variable should be scaled by unitSensorDecimalDigits. For example, if the value is 1 and…
1.3.6.1.4.1.13742.6.3.2.6TableactiveDNSServerTablenot-accessiblecurrentA list of active DNS server entries. The number of rows in the table is given by the value of activeDNSServerCount in unitConfigurationTable.
1.3.6.1.4.1.13742.6.3.2.6.1RowactiveDNSServerEntrynot-accessiblecurrentAn entry containing an active DNS server for a particular PDU.
1.3.6.1.4.1.13742.6.3.2.6.1.2ColumnactiveDNSServerIndexnot-accessiblecurrentA unique value for a DNS server. Its value ranges between 1 and activeDNSServerCount.
1.3.6.1.4.1.13742.6.3.2.6.1.3ColumnactiveDNSServerAddressTyperead-onlycurrentRepresents the type of the corresponding instance of activeDNSServerAddress object.
1.3.6.1.4.1.13742.6.3.2.6.1.4ColumnactiveDNSServerAddressread-onlycurrentThe address of the DNS server.
1.3.6.1.4.1.13742.6.3.2.6.1.5ColumnactiveDNSServerAddressSourceread-onlydeprecatedHow was the address obtained: static, DHCP, DHCPv6? No longer used, always set to static.
1.3.6.1.4.1.13742.6.3.2.7TableactiveNTPServerTablenot-accessiblecurrentA list of active NTP server entries. The number of rows in the table is given by the value of activeNTPServerCount in unitConfigurationTable.
1.3.6.1.4.1.13742.6.3.2.7.1RowactiveNTPServerEntrynot-accessiblecurrentAn entry containing an active NTP server for a particular PDU.
1.3.6.1.4.1.13742.6.3.2.7.1.2ColumnactiveNTPServerIndexnot-accessiblecurrentA unique value for an NTP server. Its value ranges between 1 and activeNTPServerCount.
1.3.6.1.4.1.13742.6.3.2.7.1.3ColumnactiveNTPServerAddressTyperead-onlycurrentRepresents the type of the corresponding instance of activeNTPServerAddress object, e.g. IPv4, IPv6, DNS Name
1.3.6.1.4.1.13742.6.3.2.7.1.4ColumnactiveNTPServerAddressread-onlycurrentThe address of the NTP server.
1.3.6.1.4.1.13742.6.3.2.7.1.5ColumnactiveNTPServerAddressSourceread-onlydeprecatedHow was the address obtained: static, DHCP, DHCPv6? No longer used, always set to static.
1.3.6.1.4.1.13742.6.3.3Nodeinlets
1.3.6.1.4.1.13742.6.3.3.3TableinletConfigurationTablenot-accessiblecurrentA list of inlet configuration entries. The number of entries is given by the value of inletCount for the PDU.
1.3.6.1.4.1.13742.6.3.3.3.1RowinletConfigurationEntrynot-accessiblecurrentAn entry containing parametersfor a particular inlet.
1.3.6.1.4.1.13742.6.3.3.3.1.1ColumninletIdnot-accessiblecurrentA unique value for each inlet. Its value ranges between 1 and the value of inletCount.
1.3.6.1.4.1.13742.6.3.3.3.1.2ColumninletLabelread-onlycurrentThe label on the PDU identifying the inlet.
1.3.6.1.4.1.13742.6.3.3.3.1.3ColumninletNameread-writecurrentThe user-defined name.
1.3.6.1.4.1.13742.6.3.3.3.1.4ColumninletPlugread-onlycurrentThe type of plug/receptacle wired to the inlet. Note: PlugTypeEnumeration is no longer updated, unlisted plugs will be reported as plugOTHER. Use inletPlugDesc…
1.3.6.1.4.1.13742.6.3.3.3.1.5ColumninletPoleCountread-onlycurrentThe number of poles. PDU: 2 for 1-phase circuits 3 for 3-phase delta-wired models 4 for 3-phase wye-wired models, pole 4 is neutral Power Meter: 2 to 5 dependi…
1.3.6.1.4.1.13742.6.3.3.3.1.6ColumninletRatedVoltageread-onlycurrentThe inlet voltage rating.
1.3.6.1.4.1.13742.6.3.3.3.1.7ColumninletRatedCurrentread-onlycurrentThe inlet current rating.
1.3.6.1.4.1.13742.6.3.3.3.1.8ColumninletRatedFrequencyread-onlydeprecatedThe inlet frequency rating. Deprecated: use pduRatedFrequency for unit nameplate information.
1.3.6.1.4.1.13742.6.3.3.3.1.9ColumninletRatedVAread-onlydeprecatedThe inlet VA (VoltAmps) rating. Deprecated: use pduRatedVA for unit nameplate information.
1.3.6.1.4.1.13742.6.3.3.3.1.10ColumninletDeviceCapabilitiesread-onlycurrentA bit string indicating which inlet sensors are available.
1.3.6.1.4.1.13742.6.3.3.3.1.11ColumninletPoleCapabilitiesread-onlycurrentA bit string indicating which inlet pole sensors are available.
1.3.6.1.4.1.13742.6.3.3.3.1.12ColumninletPlugDescriptorread-onlycurrentThe inlet plug type as a string.
1.3.6.1.4.1.13742.6.3.3.3.1.13ColumninletEnableStateread-writecurrentEnable/disable PDU operation for this inlet. When PDU operation is disabled the sensors for this inlet and all children will no longer be updated, and outlet s…
1.3.6.1.4.1.13742.6.3.3.3.1.14ColumninletRCMResidualOperatingCurrentread-writeobsolete**NOTE:This object is obsolete. Its functionality was implemented by existing RCM sensor thresholds. The Residual Operating Current (Threshold) for the RCM Sta…
1.3.6.1.4.1.13742.6.3.3.4TableinletSensorConfigurationTablenot-accessiblecurrentA list of configuration entries for an inlet sensor.
1.3.6.1.4.1.13742.6.3.3.4.1RowinletSensorConfigurationEntrynot-accessiblecurrentAn entry containing objects for configuring an inlet sensor.
1.3.6.1.4.1.13742.6.3.3.4.1.4ColumninletSensorLogAvailableread-writecurrentIs data logging enabled for the sensor?
1.3.6.1.4.1.13742.6.3.3.4.1.6ColumninletSensorUnitsread-onlycurrentThe unit in which the sensor reading is reported. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.3.4.1.7ColumninletSensorDecimalDigitsread-onlycurrentThe number of digits displayed to the right of the decimal point. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.3.4.1.8ColumninletSensorAccuracyread-onlydeprecatedThe accuracy: the maximum relative difference (in percent) between measurement and the actual value. This parameter does not apply to sensors without numerical…
1.3.6.1.4.1.13742.6.3.3.4.1.9ColumninletSensorResolutionread-onlycurrentThe resolution: the minimum difference between any two measured values The value of this OID variable should be scaled by inletSensorDecimalDigits. For example…
1.3.6.1.4.1.13742.6.3.3.4.1.10ColumninletSensorToleranceread-onlydeprecatedThe tolerance: the maximum difference between measurement and the actual value. The value of this OID variable should be scaled by (inletSensorDecimalDigits + …
1.3.6.1.4.1.13742.6.3.3.4.1.11ColumninletSensorMaximumread-onlycurrentThe largest possible reading as an unsigned integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is …
1.3.6.1.4.1.13742.6.3.3.4.1.12ColumninletSensorMinimumread-onlycurrentThe smallest possible reading as an unsigned integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is…
1.3.6.1.4.1.13742.6.3.3.4.1.13ColumninletSensorHysteresisread-writecurrentThe hysteresis used when crossing a threshold towards the normal state. The value of this OID variable should be scaled by inletSensorDecimalDigits. For exampl…
1.3.6.1.4.1.13742.6.3.3.4.1.14ColumninletSensorStateChangeDelayread-writecurrentThe delay measured in samples before a state is asserted. If the value is zero, then the state is asserted as soon as it is detected; if it is non-zero, say n,…
1.3.6.1.4.1.13742.6.3.3.4.1.21ColumninletSensorLowerCriticalThresholdread-writecurrentThe lower critical threshold as an unsigned integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is …
1.3.6.1.4.1.13742.6.3.3.4.1.22ColumninletSensorLowerWarningThresholdread-writecurrentThe lower warning threshold as an unsigned integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1…
1.3.6.1.4.1.13742.6.3.3.4.1.23ColumninletSensorUpperCriticalThresholdread-writecurrentThe upper critical threshold as an unsigned integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is …
1.3.6.1.4.1.13742.6.3.3.4.1.24ColumninletSensorUpperWarningThresholdread-writecurrentThe upper warning threshold as an unsigned integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1…
1.3.6.1.4.1.13742.6.3.3.4.1.25ColumninletSensorEnabledThresholdsread-writecurrentA bit string indicating which thresholds are enabled. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.3.4.1.26ColumninletSensorSignedMaximumread-onlycurrentThe largest possible reading as a signed integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1 a…
1.3.6.1.4.1.13742.6.3.3.4.1.27ColumninletSensorSignedMinimumread-onlycurrentThe smallest possible reading as a signed integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1 …
1.3.6.1.4.1.13742.6.3.3.4.1.28ColumninletSensorSignedLowerCriticalThresholdread-writecurrentThe lower critical threshold as a signed integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1 a…
1.3.6.1.4.1.13742.6.3.3.4.1.29ColumninletSensorSignedLowerWarningThresholdread-writecurrentThe lower warning threshold as a signed integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1 an…
1.3.6.1.4.1.13742.6.3.3.4.1.30ColumninletSensorSignedUpperCriticalThresholdread-writecurrentThe upper critical threshold as a signed integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1 a…
1.3.6.1.4.1.13742.6.3.3.4.1.31ColumninletSensorSignedUpperWarningThresholdread-writecurrentThe upper warning threshold as a signed integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1 an…
1.3.6.1.4.1.13742.6.3.3.5TableinletPoleConfigurationTablenot-accessiblecurrentA list of inlet pole configuration entries. The number of entries is given by the value of inletPoleCount for the inlet.
1.3.6.1.4.1.13742.6.3.3.5.1RowinletPoleConfigurationEntrynot-accessiblecurrentAn entry containing parameters for a particular inlet pole.
1.3.6.1.4.1.13742.6.3.3.5.1.1ColumninletPoleLineread-onlycurrentThe phase for this inlet pole.
1.3.6.1.4.1.13742.6.3.3.5.1.2ColumninletPoleNoderead-onlycurrentThe node to which this inlet pole is connected
1.3.6.1.4.1.13742.6.3.3.6TableinletPoleSensorConfigurationTablenot-accessiblecurrentA list of configuration entries for an inlet pole sensor.
1.3.6.1.4.1.13742.6.3.3.6.1RowinletPoleSensorConfigurationEntrynot-accessiblecurrentAn entry containing objects for configuring an inlet pole sensor.
1.3.6.1.4.1.13742.6.3.3.6.1.1ColumninletPoleIndexnot-accessiblecurrentA unique value for each inlet pole. Its value ranges between 1 and the value of inletPoleCount.
1.3.6.1.4.1.13742.6.3.3.6.1.4ColumninletPoleSensorLogAvailableread-writecurrentIs data logging enabled for the sensor?
1.3.6.1.4.1.13742.6.3.3.6.1.6ColumninletPoleSensorUnitsread-onlycurrentThe unit in which the sensor reading is reported. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.3.6.1.7ColumninletPoleSensorDecimalDigitsread-onlycurrentThe number of digits displayed to the right of the decimal point. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.3.6.1.8ColumninletPoleSensorAccuracyread-onlydeprecatedThe accuracy: the maximum relative difference (in percent) between measurement and the actual value. This parameter does not apply to sensors without numerical…
1.3.6.1.4.1.13742.6.3.3.6.1.9ColumninletPoleSensorResolutionread-onlycurrentThe resolution: the minimum difference between any two measured values The value of this OID variable should be scaled by inletPoleSensorDecimalDigits. For exa…
1.3.6.1.4.1.13742.6.3.3.6.1.10ColumninletPoleSensorToleranceread-onlydeprecatedThe tolerance: the maximum difference between measurement and the actual value. The value of this OID variable should be scaled by (inletPoleSensorDecimalDigit…
1.3.6.1.4.1.13742.6.3.3.6.1.11ColumninletPoleSensorMaximumread-onlycurrentThe largest possible reading as an unsigned integer. The value of this OID variable should be scaled by inletPoleSensorDecimalDigits. For example, if the value…
1.3.6.1.4.1.13742.6.3.3.6.1.12ColumninletPoleSensorMinimumread-onlycurrentThe smallest possible reading as an unsigned integer. The value of this OID variable should be scaled by inletPoleSensorDecimalDigits. For example, if the valu…
1.3.6.1.4.1.13742.6.3.3.6.1.13ColumninletPoleSensorHysteresisread-writecurrentThe hysteresis used when crossing a threshold towards the normal state. The value of this OID variable should be scaled by inletPoleSensorDecimalDigits. For ex…
1.3.6.1.4.1.13742.6.3.3.6.1.14ColumninletPoleSensorStateChangeDelayread-writecurrentThe delay measured in samples before a state is asserted. If the value is zero, then the state is asserted as soon as it is detected; if it is non-zero, say n,…
1.3.6.1.4.1.13742.6.3.3.6.1.21ColumninletPoleSensorLowerCriticalThresholdread-writecurrentThe lower critical threshold as an unsigned integer. The value of this OID variable should be scaled by inletPoleSensorDecimalDigits. For example, if the value…
1.3.6.1.4.1.13742.6.3.3.6.1.22ColumninletPoleSensorLowerWarningThresholdread-writecurrentThe lower warning threshold as an unsigned integer. The value of this OID variable should be scaled by inletPoleSensorDecimalDigits. For example, if the value …
1.3.6.1.4.1.13742.6.3.3.6.1.23ColumninletPoleSensorUpperCriticalThresholdread-writecurrentThe upper critical threshold as an unsigned integer. The value of this OID variable should be scaled by inletPoleSensorDecimalDigits. For example, if the value…
1.3.6.1.4.1.13742.6.3.3.6.1.24ColumninletPoleSensorUpperWarningThresholdread-writecurrentThe upper warning threshold as an unsigned integer. The value of this OID variable should be scaled by inletPoleSensorDecimalDigits. For example, if the value …
1.3.6.1.4.1.13742.6.3.3.6.1.25ColumninletPoleSensorEnabledThresholdsread-writecurrentA bit string indicating which thresholds are enabled. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.3.6.1.26ColumninletPoleSensorSignedMaximumread-onlycurrentThe largest possible reading as a signed integer. The value of this OID variable should be scaled by inletPoleSensorDecimalDigits. For example, if the value is…
1.3.6.1.4.1.13742.6.3.3.6.1.27ColumninletPoleSensorSignedMinimumread-onlycurrentThe smallest possible reading as a signed integer. The value of this OID variable should be scaled by inletPoleSensorDecimalDigits. For example, if the value i…
1.3.6.1.4.1.13742.6.3.3.6.1.28ColumninletPoleSensorSignedLowerCriticalThresholdread-writecurrentThe lower critical threshold as a signed integer. The value of this OID variable should be scaled by inletPoleSensorDecimalDigits. For example, if the value is…
1.3.6.1.4.1.13742.6.3.3.6.1.29ColumninletPoleSensorSignedLowerWarningThresholdread-writecurrentThe lower warning threshold as a signed integer. The value of this OID variable should be scaled by inletPoleSensorDecimalDigits. For example, if the value is …
1.3.6.1.4.1.13742.6.3.3.6.1.30ColumninletPoleSensorSignedUpperCriticalThresholdread-writecurrentThe upper critical threshold as a signed integer. The value of this OID variable should be scaled by inletPoleSensorDecimalDigits. For example, if the value is…
1.3.6.1.4.1.13742.6.3.3.6.1.31ColumninletPoleSensorSignedUpperWarningThresholdread-writecurrentThe upper warning threshold as a signed integer. The value of this OID variable should be scaled by inletPoleSensorDecimalDigits. For example, if the value is …
1.3.6.1.4.1.13742.6.3.4NodeoverCurrentProtector
1.3.6.1.4.1.13742.6.3.4.3TableoverCurrentProtectorConfigurationTablenot-accessiblecurrentA list of overcurrent protector configuration entries. The number of entries is given by the value of overCurrentProtectorCount for the PDU.
1.3.6.1.4.1.13742.6.3.4.3.1RowoverCurrentProtectorConfigurationEntrynot-accessiblecurrentAn entry containing objects for a particular overcurrent protector.
1.3.6.1.4.1.13742.6.3.4.3.1.1ColumnoverCurrentProtectorIndexnot-accessiblecurrentA unique value for each overcurrent protector. Its value ranges between 1 and the value of overCurrentProtectorCount.
1.3.6.1.4.1.13742.6.3.4.3.1.2ColumnoverCurrentProtectorLabelread-onlycurrentThe label on the PDU identifying the overcurrent protector.
1.3.6.1.4.1.13742.6.3.4.3.1.3ColumnoverCurrentProtectorNameread-writecurrentThe user-defined name.
1.3.6.1.4.1.13742.6.3.4.3.1.4ColumnoverCurrentProtectorTyperead-onlycurrentThe type of overcurrent protector.
1.3.6.1.4.1.13742.6.3.4.3.1.5ColumnoverCurrentProtectorRatedCurrentread-onlycurrentThe current rating.
1.3.6.1.4.1.13742.6.3.4.3.1.6ColumnoverCurrentProtectorPoleCountread-onlycurrentThe number of overcurrent protector poles.
1.3.6.1.4.1.13742.6.3.4.3.1.9ColumnoverCurrentProtectorCapabilitiesread-onlycurrentA bit string indicating which overcurrent protector sensors are available.
1.3.6.1.4.1.13742.6.3.4.3.1.10ColumnoverCurrentProtectorPowerSourceread-onlycurrentThis object allows discovery of how the PDU is wired. It indicates the overcurrent protector's power source which can be one of the following: - an inlet - ano…
1.3.6.1.4.1.13742.6.3.4.4TableoverCurrentProtectorSensorConfigurationTablenot-accessiblecurrentA list of overcurrent protector sensor configuration entries.
1.3.6.1.4.1.13742.6.3.4.4.1RowoverCurrentProtectorSensorConfigurationEntrynot-accessiblecurrentAn overcurrent protector sensor entry containing objects for a particular overcurrent protector sensor.
1.3.6.1.4.1.13742.6.3.4.4.1.4ColumnoverCurrentProtectorSensorLogAvailableread-writecurrentIs data logging enabled for this sensor?
1.3.6.1.4.1.13742.6.3.4.4.1.6ColumnoverCurrentProtectorSensorUnitsread-onlycurrentThe unit in which the sensor reading is reported. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.4.4.1.7ColumnoverCurrentProtectorSensorDecimalDigitsread-onlycurrentThe number of digits displayed to the right of the decimal point. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.4.4.1.8ColumnoverCurrentProtectorSensorAccuracyread-onlydeprecatedThe accuracy: the maximum relative difference (in percent) between measurement and the actual value. This parameter does not apply to sensors without numerical…
1.3.6.1.4.1.13742.6.3.4.4.1.9ColumnoverCurrentProtectorSensorResolutionread-onlycurrentThe resolution: the minimum difference between any two measured values The value of this OID variable should be scaled by overCurrentProtectorSensorDecimalDigi…
1.3.6.1.4.1.13742.6.3.4.4.1.10ColumnoverCurrentProtectorSensorToleranceread-onlydeprecatedThe tolerance: the maximum difference between measurement and the actual value. The value of this OID variable should be scaled by (overCurrentProtectorSensorD…
1.3.6.1.4.1.13742.6.3.4.4.1.11ColumnoverCurrentProtectorSensorMaximumread-onlycurrentThe largest possible reading as an unsigned integer. The value of this OID variable should be scaled by overCurrentProtectorSensorDecimalDigits. For example, i…
1.3.6.1.4.1.13742.6.3.4.4.1.12ColumnoverCurrentProtectorSensorMinimumread-onlycurrentThe smallest possible reading as an unsigned integer. The value of this OID variable should be scaled by overCurrentProtectorSensorDecimalDigits. For example, …
1.3.6.1.4.1.13742.6.3.4.4.1.13ColumnoverCurrentProtectorSensorHysteresisread-writecurrentThe hysteresis used when crossing a threshold towards the normal state. The value of this OID variable should be scaled by overCurrentProtectorSensorDecimalDig…
1.3.6.1.4.1.13742.6.3.4.4.1.14ColumnoverCurrentProtectorSensorStateChangeDelayread-writecurrentThe delay measured in samples before a state is asserted. If the value is zero, then the state is asserted as soon as it is detected; if it is non-zero, say n,…
1.3.6.1.4.1.13742.6.3.4.4.1.21ColumnoverCurrentProtectorSensorLowerCriticalThresholdread-writecurrentThe lower critical threshold as an unsigned integer. The value of this OID variable should be scaled by overCurrentProtectorSensorDecimalDigits. For example, i…
1.3.6.1.4.1.13742.6.3.4.4.1.22ColumnoverCurrentProtectorSensorLowerWarningThresholdread-writecurrentThe lower warning threshold as an unsigned integer. The value of this OID variable should be scaled by overCurrentProtectorSensorDecimalDigits. For example, if…
1.3.6.1.4.1.13742.6.3.4.4.1.23ColumnoverCurrentProtectorSensorUpperCriticalThresholdread-writecurrentThe upper critical threshold as an unsigned integer. The value of this OID variable should be scaled by overCurrentProtectorSensorDecimalDigits. For example, i…
1.3.6.1.4.1.13742.6.3.4.4.1.24ColumnoverCurrentProtectorSensorUpperWarningThresholdread-writecurrentThe upper warning threshold as an unsigned integer. The value of this OID variable should be scaled by overCurrentProtectorSensorDecimalDigits. For example, if…
1.3.6.1.4.1.13742.6.3.4.4.1.25ColumnoverCurrentProtectorSensorEnabledThresholdsread-writecurrentA bit string indicating which thresholds are enabled. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.4.4.1.26ColumnoverCurrentProtectorSensorSignedMaximumread-onlycurrentThe largest possible reading as a signed integer. The value of this OID variable should be scaled by overCurrentProtectorSensorDecimalDigits. For example, if t…
1.3.6.1.4.1.13742.6.3.4.4.1.27ColumnoverCurrentProtectorSensorSignedMinimumread-onlycurrentThe smallest possible reading as a signed integer. The value of this OID variable should be scaled by overCurrentProtectorSensorDecimalDigits. For example, if …
1.3.6.1.4.1.13742.6.3.4.4.1.28ColumnoverCurrentProtectorSensorSignedLowerCriticalThresholdread-writecurrentThe lower critical threshold as a signed integer. The value of this OID variable should be scaled by overCurrentProtectorSensorDecimalDigits. For example, if t…
1.3.6.1.4.1.13742.6.3.4.4.1.29ColumnoverCurrentProtectorSensorSignedLowerWarningThresholdread-writecurrentThe lower warning threshold as a signed integer. The value of this OID variable should be scaled by overCurrentProtectorSensorDecimalDigits. For example, if th…
1.3.6.1.4.1.13742.6.3.4.4.1.30ColumnoverCurrentProtectorSensorSignedUpperCriticalThresholdread-writecurrentThe upper critical threshold as a signed integer. The value of this OID variable should be scaled by overCurrentProtectorSensorDecimalDigits. For example, if t…
1.3.6.1.4.1.13742.6.3.4.4.1.31ColumnoverCurrentProtectorSensorSignedUpperWarningThresholdread-writecurrentThe upper warning threshold as a signed integer. The value of this OID variable should be scaled by overCurrentProtectorSensorDecimalDigits. For example, if th…
1.3.6.1.4.1.13742.6.3.4.5TableoverCurrentProtectorPoleConfigurationTablenot-accessiblecurrentA list of overcurrent protector pole configuration entries. The number of entries is given by the value of overCurrentProtectorPoleCount.
1.3.6.1.4.1.13742.6.3.4.5.1RowoverCurrentProtectorPoleConfigurationEntrynot-accessiblecurrentAn entry containing parameters for a particular overcurrent protector pole.
1.3.6.1.4.1.13742.6.3.4.5.1.1ColumnoverCurrentProtectorPoleIndexnot-accessiblecurrentA unique value for each overcurrent protector pole. Its value ranges between 1 and the value of overCurrentProtectorPoleCount.
1.3.6.1.4.1.13742.6.3.4.5.1.2ColumnoverCurrentProtectorPoleLineread-onlycurrentThe phase for this overcurrent protector pole.
1.3.6.1.4.1.13742.6.3.4.5.1.3ColumnoverCurrentProtectorPoleInNoderead-onlycurrentThe node to which this overcurrent protector pole input is connected
1.3.6.1.4.1.13742.6.3.4.5.1.4ColumnoverCurrentProtectorPoleOutNoderead-onlycurrentThe node to which this overcurrent protector pole output is connected
1.3.6.1.4.1.13742.6.3.5Nodeoutlets
1.3.6.1.4.1.13742.6.3.5.3TableoutletConfigurationTablenot-accessiblecurrentA list of outlet configuration entries. The number of entries is given by the value of outletCount for the PDU.
1.3.6.1.4.1.13742.6.3.5.3.1RowoutletConfigurationEntrynot-accessiblecurrentAn outlet entry containing parameters for a particular outlet.
1.3.6.1.4.1.13742.6.3.5.3.1.1ColumnoutletIdnot-accessiblecurrentA unique value for each outlet. Its value ranges between 1 and the value of outletCount.
1.3.6.1.4.1.13742.6.3.5.3.1.2ColumnoutletLabelread-onlycurrentThe label on the PDU identifying the outlet.
1.3.6.1.4.1.13742.6.3.5.3.1.3ColumnoutletNameread-writecurrentThe user-defined name.
1.3.6.1.4.1.13742.6.3.5.3.1.4ColumnoutletReceptacleread-onlycurrentThe receptacle type. Note: ReceptacleTypeEnumeration is no longer updated, unlisted receptacles will be listed as receptacleOTHER. Use outletReceptacleDescript…
1.3.6.1.4.1.13742.6.3.5.3.1.5ColumnoutletPoleCountread-onlycurrentThe number of poles.
1.3.6.1.4.1.13742.6.3.5.3.1.6ColumnoutletRatedVoltageread-onlycurrentThe outlet voltage rating.
1.3.6.1.4.1.13742.6.3.5.3.1.7ColumnoutletRatedCurrentread-onlycurrentThe outlet current rating.
1.3.6.1.4.1.13742.6.3.5.3.1.8ColumnoutletRatedVAread-onlycurrentThe outlet VA (VoltAmps) rating.
1.3.6.1.4.1.13742.6.3.5.3.1.10ColumnoutletDeviceCapabilitiesread-onlycurrentA bit string indicating which outlet sensors are available.
1.3.6.1.4.1.13742.6.3.5.3.1.11ColumnoutletPoleCapabilitiesread-onlycurrentA bit string indicating which outlet pole sensors are available.
1.3.6.1.4.1.13742.6.3.5.3.1.12ColumnoutletPowerCyclingPowerOffPeriodread-writecurrentThe power-off period when an outlet is cycled. Overrides the global value if outletUseGlobalPowerCyclingPowerOffPeriod is false. Specified in seconds, 1 <= val…
1.3.6.1.4.1.13742.6.3.5.3.1.13ColumnoutletStateOnStartupread-writecurrentThe outlet state on device startup. This value is ignored if relayBehaviorOnPowerLoss is set to latching.
1.3.6.1.4.1.13742.6.3.5.3.1.14ColumnoutletUseGlobalPowerCyclingPowerOffPeriodread-writecurrentIndicates which power-off period to use when the outlet is cycled: - true: use globalOutletPowerCyclingPowerOffPeriod - false: use outletPowerCyclingPowerOffPe…
1.3.6.1.4.1.13742.6.3.5.3.1.28ColumnoutletSwitchableread-onlycurrentIs this outlet switchable?
1.3.6.1.4.1.13742.6.3.5.3.1.29ColumnoutletReceptacleDescriptorread-onlycurrentThe outlet receptacle type as a string.
1.3.6.1.4.1.13742.6.3.5.3.1.30ColumnoutletNonCriticalread-writecurrentIs this outlet non-critical? Non-critical outlets will be switched off when load shedding is enabled.
1.3.6.1.4.1.13742.6.3.5.3.1.32ColumnoutletSequenceDelayread-writecurrentThe time interval between switching on this outlet and the next outlet in the outlet sequence. This applies to the following operations. 1) Switch all outlets …
1.3.6.1.4.1.13742.6.3.5.3.1.33ColumnoutletPowerSourceread-onlycurrentThis object allows discovery of how the PDU is wired. It indicates the outlet's power source which can one of the following: - an inlet - an overcurrent protec…
1.3.6.1.4.1.13742.6.3.5.4TableoutletSensorConfigurationTablenot-accessiblecurrentA list of outlet sensor configuration entries.
1.3.6.1.4.1.13742.6.3.5.4.1RowoutletSensorConfigurationEntrynot-accessiblecurrentAn entry containing parameters for an outlet sensor.
1.3.6.1.4.1.13742.6.3.5.4.1.4ColumnoutletSensorLogAvailableread-writecurrentIs data logging enabled for this sensor?
1.3.6.1.4.1.13742.6.3.5.4.1.6ColumnoutletSensorUnitsread-onlycurrentThe unit in which the sensor reading is reported. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.5.4.1.7ColumnoutletSensorDecimalDigitsread-onlycurrentThe number of digits displayed to the right of the decimal point This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.5.4.1.8ColumnoutletSensorAccuracyread-onlydeprecatedThe accuracy: the maximum relative difference (in percent) between measurement and the actual value. This parameter does not apply to sensors without numerical…
1.3.6.1.4.1.13742.6.3.5.4.1.9ColumnoutletSensorResolutionread-onlycurrentThe resolution: the minimum difference between any two measured values The value of this OID variable should be scaled by outletSensorDecimalDigits. For exampl…
1.3.6.1.4.1.13742.6.3.5.4.1.10ColumnoutletSensorToleranceread-onlydeprecatedThe tolerance: the maximum difference between measurement and the actual value. The value of this OID variable should be scaled by (outletSensorDecimalDigits +…
1.3.6.1.4.1.13742.6.3.5.4.1.11ColumnoutletSensorMaximumread-onlycurrentThe largest possible reading as an unsigned integer. The value of this OID variable should be scaled by outletSensorDecimalDigits. For example, if the value is…
1.3.6.1.4.1.13742.6.3.5.4.1.12ColumnoutletSensorMinimumread-onlycurrentThe smallest possible reading as an unsigned integer. The value of this OID variable should be scaled by outletSensorDecimalDigits. For example, if the value i…
1.3.6.1.4.1.13742.6.3.5.4.1.13ColumnoutletSensorHysteresisread-writecurrentThe hysteresis used when crossing a threshold towards the normal state. The value of this OID variable should be scaled by outletSensorDecimalDigits. For examp…
1.3.6.1.4.1.13742.6.3.5.4.1.14ColumnoutletSensorStateChangeDelayread-writecurrentThe delay measured in samples before a state is asserted. If the value is zero, then the state is asserted as soon as it is detected; if it is non-zero, say n,…
1.3.6.1.4.1.13742.6.3.5.4.1.21ColumnoutletSensorLowerCriticalThresholdread-writecurrentThe lower critical threshold as an unsigned integer. The value of this OID variable should be scaled by outletSensorDecimalDigits. For example, if the value is…
1.3.6.1.4.1.13742.6.3.5.4.1.22ColumnoutletSensorLowerWarningThresholdread-writecurrentThe lower warning threshold as an unsigned integer. The value of this OID variable should be scaled by outletSensorDecimalDigits. For example, if the value is …
1.3.6.1.4.1.13742.6.3.5.4.1.23ColumnoutletSensorUpperCriticalThresholdread-writecurrentThe upper critical threshold as an unsigned integer. The value of this OID variable should be scaled by outletSensorDecimalDigits. For example, if the value is…
1.3.6.1.4.1.13742.6.3.5.4.1.24ColumnoutletSensorUpperWarningThresholdread-writecurrentThe upper warning threshold as an unsigned integer. The value of this OID variable should be scaled by outletSensorDecimalDigits. For example, if the value is …
1.3.6.1.4.1.13742.6.3.5.4.1.25ColumnoutletSensorEnabledThresholdsread-writecurrentA bit string indicating which thresholds are enabled. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.5.4.1.26ColumnoutletSensorSignedMaximumread-onlycurrentThe largest possible reading as a signed integer. The value of this OID variable should be scaled by outletSensorDecimalDigits. For example, if the value is 1 …
1.3.6.1.4.1.13742.6.3.5.4.1.27ColumnoutletSensorSignedMinimumread-onlycurrentThe smallest possible reading as a signed integer. The value of this OID variable should be scaled by outletSensorDecimalDigits. For example, if the value is 1…
1.3.6.1.4.1.13742.6.3.5.4.1.28ColumnoutletSensorSignedLowerCriticalThresholdread-writecurrentThe lower critical threshold as a signed integer. The value of this OID variable should be scaled by outletSensorDecimalDigits. For example, if the value is 1 …
1.3.6.1.4.1.13742.6.3.5.4.1.29ColumnoutletSensorSignedLowerWarningThresholdread-writecurrentThe lower warning threshold as a signed integer. The value of this OID variable should be scaled by outletSensorDecimalDigits. For example, if the value is 1 a…
1.3.6.1.4.1.13742.6.3.5.4.1.30ColumnoutletSensorSignedUpperCriticalThresholdread-writecurrentThe upper critical threshold as a signed integer. The value of this OID variable should be scaled by outletSensorDecimalDigits. For example, if the value is 1 …
1.3.6.1.4.1.13742.6.3.5.4.1.31ColumnoutletSensorSignedUpperWarningThresholdread-writecurrentThe upper warning threshold as a signed integer. The value of this OID variable should be scaled by outletSensorDecimalDigits. For example, if the value is 1 a…
1.3.6.1.4.1.13742.6.3.5.5TableoutletPoleConfigurationTablenot-accessiblecurrentA list of outlet pole configuration entries. The number of entries is given by the value of outletPoleCount for the PDU.
1.3.6.1.4.1.13742.6.3.5.5.1RowoutletPoleConfigurationEntrynot-accessiblecurrentAn entry containing parameters for a particular outlet pole.
1.3.6.1.4.1.13742.6.3.5.5.1.1ColumnoutletPoleLineread-onlycurrentThe phase for this outlet pole.
1.3.6.1.4.1.13742.6.3.5.5.1.2ColumnoutletPoleNoderead-onlycurrentThe node to which this outlet pole is connected
1.3.6.1.4.1.13742.6.3.5.6TableoutletPoleSensorConfigurationTablenot-accessiblecurrentA list of outlet pole sensor configuration entries.
1.3.6.1.4.1.13742.6.3.5.6.1RowoutletPoleSensorConfigurationEntrynot-accessiblecurrentAn entry containing objects for configuring an outlet pole sensor.
1.3.6.1.4.1.13742.6.3.5.6.1.1ColumnoutletPoleIndexnot-accessiblecurrentA unique value for each outlet pole. Its value ranges between 1 and the value of outletPoleCount.
1.3.6.1.4.1.13742.6.3.5.6.1.4ColumnoutletPoleSensorLogAvailableread-writecurrentIs data logging enabled for the sensor?
1.3.6.1.4.1.13742.6.3.5.6.1.6ColumnoutletPoleSensorUnitsread-onlycurrentThe unit in which the sensor reading is reported. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.5.6.1.7ColumnoutletPoleSensorDecimalDigitsread-onlycurrentThe number of digits displayed to the right of the decimal point. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.5.6.1.8ColumnoutletPoleSensorAccuracyread-onlydeprecatedThe accuracy: the maximum relative difference (in percent) between measurement and the actual value. This parameter does not apply to sensors without numerical…
1.3.6.1.4.1.13742.6.3.5.6.1.9ColumnoutletPoleSensorResolutionread-onlycurrentThe resolution: the minimum difference between any two measured values The value of this OID variable should be scaled by outletPoleSensorDecimalDigits. For ex…
1.3.6.1.4.1.13742.6.3.5.6.1.10ColumnoutletPoleSensorToleranceread-onlydeprecatedThe tolerance: the maximum difference between measurement and the actual value. The value of this OID variable should be scaled by (outletPoleSensorDecimalDigi…
1.3.6.1.4.1.13742.6.3.5.6.1.11ColumnoutletPoleSensorMaximumread-onlycurrentThe largest possible reading as an unsigned integer. The value of this OID variable should be scaled by outletPoleSensorDecimalDigits. For example, if the valu…
1.3.6.1.4.1.13742.6.3.5.6.1.12ColumnoutletPoleSensorMinimumread-onlycurrentThe smallest possible reading as an unsigned integer. The value of this OID variable should be scaled by outletPoleSensorDecimalDigits. For example, if the val…
1.3.6.1.4.1.13742.6.3.5.6.1.13ColumnoutletPoleSensorHysteresisread-writecurrentThe hysteresis used when crossing a threshold towards the normal state. The value of this OID variable should be scaled by outletPoleSensorDecimalDigits. For e…
1.3.6.1.4.1.13742.6.3.5.6.1.14ColumnoutletPoleSensorStateChangeDelayread-writecurrentThe delay measured in samples before a state is asserted. If the value is zero, then the state is asserted as soon as it is detected; if it is non-zero, say n,…
1.3.6.1.4.1.13742.6.3.5.6.1.21ColumnoutletPoleSensorLowerCriticalThresholdread-writecurrentThe lower critical threshold as an unsigned integer. The value of this OID variable should be scaled by outletPoleSensorDecimalDigits. For example, if the valu…
1.3.6.1.4.1.13742.6.3.5.6.1.22ColumnoutletPoleSensorLowerWarningThresholdread-writecurrentThe lower warning threshold as an unsigned integer. The value of this OID variable should be scaled by outletPoleSensorDecimalDigits. For example, if the value…
1.3.6.1.4.1.13742.6.3.5.6.1.23ColumnoutletPoleSensorUpperCriticalThresholdread-writecurrentThe upper critical threshold as an unsigned integer. The value of this OID variable should be scaled by outletPoleSensorDecimalDigits. For example, if the valu…
1.3.6.1.4.1.13742.6.3.5.6.1.24ColumnoutletPoleSensorUpperWarningThresholdread-writecurrentThe upper warning threshold as an unsigned integer. The value of this OID variable should be scaled by outletPoleSensorDecimalDigits. For example, if the value…
1.3.6.1.4.1.13742.6.3.5.6.1.25ColumnoutletPoleSensorEnabledThresholdsread-writecurrentA bit string indicating which thresholds are enabled. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.5.6.1.26ColumnoutletPoleSensorSignedMaximumread-onlycurrentThe largest possible reading as a signed integer. The value of this OID variable should be scaled by outletPoleSensorDecimalDigits. For example, if the value i…
1.3.6.1.4.1.13742.6.3.5.6.1.27ColumnoutletPoleSensorSignedMinimumread-onlycurrentThe smallest possible reading as a signed integer. The value of this OID variable should be scaled by outletPoleSensorDecimalDigits. For example, if the value …
1.3.6.1.4.1.13742.6.3.5.6.1.28ColumnoutletPoleSensorSignedLowerCriticalThresholdread-writecurrentThe lower critical threshold as a signed integer. The value of this OID variable should be scaled by outletPoleSensorDecimalDigits. For example, if the value i…
1.3.6.1.4.1.13742.6.3.5.6.1.29ColumnoutletPoleSensorSignedLowerWarningThresholdread-writecurrentThe lower warning threshold as a signed integer. The value of this OID variable should be scaled by outletPoleSensorDecimalDigits. For example, if the value is…
1.3.6.1.4.1.13742.6.3.5.6.1.30ColumnoutletPoleSensorSignedUpperCriticalThresholdread-writecurrentThe upper critical threshold as a signed integer. The value of this OID variable should be scaled by outletPoleSensorDecimalDigits. For example, if the value i…
1.3.6.1.4.1.13742.6.3.5.6.1.31ColumnoutletPoleSensorSignedUpperWarningThresholdread-writecurrentThe upper warning threshold as a signed integer. The value of this OID variable should be scaled by outletPoleSensorDecimalDigits. For example, if the value is…
1.3.6.1.4.1.13742.6.3.6NodeexternalSensors
1.3.6.1.4.1.13742.6.3.6.3TableexternalSensorConfigurationTablenot-accessiblecurrentA list of external sensor configuration entries. The number of entries is given by the value of externalSensorCount for the PDU.
1.3.6.1.4.1.13742.6.3.6.3.1RowexternalSensorConfigurationEntrynot-accessiblecurrentAn entry containing parameters for an external sensor.
1.3.6.1.4.1.13742.6.3.6.3.1.1ColumnsensorIDnot-accessiblecurrentA unique value for each sensor. Its value ranges between 1 and the value of externalSensorCount.
1.3.6.1.4.1.13742.6.3.6.3.1.2ColumnexternalSensorTyperead-onlycurrentThe type of sensor.
1.3.6.1.4.1.13742.6.3.6.3.1.3ColumnexternalSensorSerialNumberread-onlycurrentThe sensor serial number.
1.3.6.1.4.1.13742.6.3.6.3.1.4ColumnexternalSensorNameread-writecurrentThe user-defined name.
1.3.6.1.4.1.13742.6.3.6.3.1.5ColumnexternalSensorDescriptionread-writecurrentThe user-defined description.
1.3.6.1.4.1.13742.6.3.6.3.1.6ColumnexternalSensorXCoordinateread-writecurrentThe X coordinate.
1.3.6.1.4.1.13742.6.3.6.3.1.7ColumnexternalSensorYCoordinateread-writecurrentThe Y coordinate.
1.3.6.1.4.1.13742.6.3.6.3.1.8ColumnexternalSensorZCoordinateread-writecurrentThe Z coordinate. The value must be a number if externalSensorsZCoordinateUnits is rackUnits.
1.3.6.1.4.1.13742.6.3.6.3.1.9ColumnexternalSensorChannelNumberread-onlycurrentThe channel number. This applies only to contact sensors, -1 for other sensors.
1.3.6.1.4.1.13742.6.3.6.3.1.10ColumnexternalOnOffSensorSubtyperead-writecurrentThe subtype of the binary sensor.
1.3.6.1.4.1.13742.6.3.6.3.1.14ColumnexternalSensorLogAvailableread-writecurrentIs data logging enabled for this sensor?
1.3.6.1.4.1.13742.6.3.6.3.1.16ColumnexternalSensorUnitsread-onlycurrentThe unit in which the sensor reading is reported. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.6.3.1.17ColumnexternalSensorDecimalDigitsread-onlycurrentThe number of digits displayed to the right of the decimal point. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.6.3.1.18ColumnexternalSensorAccuracyread-onlydeprecatedThe accuracy: the maximum relative difference (in percent) between measurement and the actual value. This parameter does not apply to sensors without numerical…
1.3.6.1.4.1.13742.6.3.6.3.1.19ColumnexternalSensorResolutionread-onlycurrentThe resolution: the minimum difference between any two measured values The value of this OID variable should be scaled by externalSensorDecimalDigits. For exam…
1.3.6.1.4.1.13742.6.3.6.3.1.20ColumnexternalSensorToleranceread-onlydeprecatedThe tolerance: the maximum difference between measurement and the actual value. The value of this OID variable should be scaled by (externalSensorDecimalDigits…
1.3.6.1.4.1.13742.6.3.6.3.1.21ColumnexternalSensorMaximumread-onlycurrentThe largest possible value The value of this OID variable should be scaled by externalSensorDecimalDigits. For example, if the value is 1 and externalSensorDec…
1.3.6.1.4.1.13742.6.3.6.3.1.22ColumnexternalSensorMinimumread-onlycurrentThe smallest possible value The value of this OID variable should be scaled by externalSensorDecimalDigits. For example, if the value is 1 and externalSensorDe…
1.3.6.1.4.1.13742.6.3.6.3.1.23ColumnexternalSensorHysteresisread-writecurrentThe hysteresis used when crossing a threshold towards the normal state. The value of this OID variable should be scaled by externalSensorDecimalDigits. For exa…
1.3.6.1.4.1.13742.6.3.6.3.1.24ColumnexternalSensorStateChangeDelayread-writecurrentThe delay measured in samples before a state is asserted. If the value is zero, then the state is asserted as soon as it is detected; if it is non-zero, say n,…
1.3.6.1.4.1.13742.6.3.6.3.1.31ColumnexternalSensorLowerCriticalThresholdread-writecurrentThe lower critical threshold The value of this OID variable should be scaled by externalSensorDecimalDigits. For example, if the value is 1 and externalSensorD…
1.3.6.1.4.1.13742.6.3.6.3.1.32ColumnexternalSensorLowerWarningThresholdread-writecurrentThe lower warning threshold The value of this OID variable should be scaled by externalSensorDecimalDigits. For example, if the value is 1 and externalSensorDe…
1.3.6.1.4.1.13742.6.3.6.3.1.33ColumnexternalSensorUpperCriticalThresholdread-writecurrentThe upper critical threshold The value of this OID variable should be scaled by externalSensorDecimalDigits. For example, if the value is 1 and externalSensorD…
1.3.6.1.4.1.13742.6.3.6.3.1.34ColumnexternalSensorUpperWarningThresholdread-writecurrentThe upper warning threshold The value of this OID variable should be scaled by externalSensorDecimalDigits. For example, if the value is 1 and externalSensorDe…
1.3.6.1.4.1.13742.6.3.6.3.1.35ColumnexternalSensorEnabledThresholdsread-writecurrentA bit string indicating which thresholds are enabled. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.6.3.1.36ColumnexternalSensorIsActuatorread-onlycurrentIndicates whether the sensor is an actuator.
1.3.6.1.4.1.13742.6.3.6.3.1.37ColumnexternalSensorPositionread-onlycurrentThe position of the sensor in the bus topology. The format is a semicolon separated list of Keyword:value pairs. Keyword can be one of the following: ONBOARD, …
1.3.6.1.4.1.13742.6.3.6.3.1.38ColumnexternalSensorUseDefaultThresholdsread-writecurrentUse default thresholds for this sensor? True: Use default thresholds from externalSensorTypeDefaultThresholdsTable False: Use sensor-specific thresholds from t…
1.3.6.1.4.1.13742.6.3.6.3.1.39ColumnexternalSensorAlarmedToNormalDelayread-writecurrentThe delay (in seconds) before the sensor returns from alarmed to normal. This is supported for motion detectors only. For all other sensors the value is 0 and …
1.3.6.1.4.1.13742.6.3.6.4TableexternalSensorTypeDefaultThresholdsTablenot-accessiblecurrentA table listing the default thresholds for each sensor type. The table contains a row for each supported type of external sensor with a numeric reading.
1.3.6.1.4.1.13742.6.3.6.4.1RowexternalSensorTypeDefaultThresholdsEntrynot-accessiblecurrentAn entry containing default thresholds for a sensor type.
1.3.6.1.4.1.13742.6.3.6.4.1.3ColumnexternalSensorTypeDefaultHysteresisread-writecurrentThe hysteresis used when crossing a threshold towards the normal state. The value of this OID variable should be scaled by externalSensorDecimalDigits. For exa…
1.3.6.1.4.1.13742.6.3.6.4.1.4ColumnexternalSensorTypeDefaultStateChangeDelayread-writecurrentThe delay measured in samples before a state is asserted. If the value is zero, then the state is asserted as soon as it is detected; if it is non-zero, say n,…
1.3.6.1.4.1.13742.6.3.6.4.1.5ColumnexternalSensorTypeDefaultLowerCriticalThresholdread-writecurrentThe lower critical threshold The value of this OID variable should be scaled by externalSensorDecimalDigits. For example, if the value is 1 and externalSensorD…
1.3.6.1.4.1.13742.6.3.6.4.1.6ColumnexternalSensorTypeDefaultLowerWarningThresholdread-writecurrentThe lower warning threshold The value of this OID variable should be scaled by externalSensorDecimalDigits. For example, if the value is 1 and externalSensorDe…
1.3.6.1.4.1.13742.6.3.6.4.1.7ColumnexternalSensorTypeDefaultUpperCriticalThresholdread-writecurrentThe upper critical threshold The value of this OID variable should be scaled by externalSensorDecimalDigits. For example, if the value is 1 and externalSensorD…
1.3.6.1.4.1.13742.6.3.6.4.1.8ColumnexternalSensorTypeDefaultUpperWarningThresholdread-writecurrentThe upper warning threshold The value of this OID variable should be scaled by externalSensorDecimalDigits. For example, if the value is 1 and externalSensorDe…
1.3.6.1.4.1.13742.6.3.6.4.1.9ColumnexternalSensorTypeDefaultEnabledThresholdsread-writecurrentA bit string indicating which thresholds are enabled.
1.3.6.1.4.1.13742.6.3.6.5TableperipheralDevicePackageTablenot-accessiblecurrentA list of entries for the peripheral device packages connected to a PDU. The number of entries is given by the value of peripheralDevicePackagesCount. A periph…
1.3.6.1.4.1.13742.6.3.6.5.1RowperipheralDevicePackageEntrynot-accessiblecurrentAn entry containing objects for a peripheral device package.
1.3.6.1.4.1.13742.6.3.6.5.1.1ColumnperipheralDevicePackageIdnot-accessiblecurrentA unique value for each peripheral device package.
1.3.6.1.4.1.13742.6.3.6.5.1.3ColumnperipheralDevicePackageSerialNumberread-onlycurrentThe peripheral device package serial number.
1.3.6.1.4.1.13742.6.3.6.5.1.4ColumnperipheralDevicePackageModelread-onlycurrentThe peripheral device package model. Examples are DX-D2C6, DPX2-T1, DPX2-T1H1, DPX2-T2H1, DPX2-T3H1
1.3.6.1.4.1.13742.6.3.6.5.1.5ColumnperipheralDevicePackageFirmwareVersionread-onlycurrentThe peripheral device package firmware version.
1.3.6.1.4.1.13742.6.3.6.5.1.6ColumnperipheralDevicePackageMinFirmwareVersionread-onlycurrentThe peripheral device package minimum firmware version. This field may be empty. If it is not empty, then it shall not be possible to downgrade the peripheral …
1.3.6.1.4.1.13742.6.3.6.5.1.7ColumnperipheralDevicePackageFirmwareTimeStampread-onlycurrentThe time when the peripheral device package firmware was last updated. It is measured in seconds since January 1, 1970 (midnight UTC/GMT).
1.3.6.1.4.1.13742.6.3.6.5.1.8ColumnperipheralDevicePackagePositionread-onlycurrentThe position of the package in the bus topology. The format is a semicolon separated list of Keyword:value pairs. Keyword can be one of the following: ONBOARD,…
1.3.6.1.4.1.13742.6.3.6.5.1.9ColumnperipheralDevicePackageStateread-onlycurrentThe state of the package.
1.3.6.1.4.1.13742.6.3.7NodeserverReachability
1.3.6.1.4.1.13742.6.3.7.3TableserverReachabilityTablenot-accessiblecurrentA list of server entries. The number of entries is given by the value of serverCount for the PDU.
1.3.6.1.4.1.13742.6.3.7.3.1RowserverReachabilityEntrynot-accessiblecurrentAn entry containing parameters for a server.
1.3.6.1.4.1.13742.6.3.7.3.1.1ColumnserverIDnot-accessiblecurrentA unique value for each server. Its value ranges between 1 and the value of serverCount for that PDU
1.3.6.1.4.1.13742.6.3.7.3.1.3ColumnserverIPAddressread-onlycurrentThe IP Address/host name of the server
1.3.6.1.4.1.13742.6.3.7.3.1.4ColumnserverPingEnabledread-writecurrentIs ping enabled for this server?
1.3.6.1.4.1.13742.6.3.8Nodewires
1.3.6.1.4.1.13742.6.3.8.3TablewireConfigurationTablenot-accessibledeprecatedA list of wire configuration entries. The number of entries is given by the value of wireCount for the PDU. Note: This feature is no longer used, the table is …
1.3.6.1.4.1.13742.6.3.8.3.1RowwireConfigurationEntrynot-accessibledeprecatedAn entry containing objects for a particular wire.
1.3.6.1.4.1.13742.6.3.8.3.1.1ColumnwireIdnot-accessibledeprecatedA unique value for each wire. Its value ranges between 1 and the value of wireCount.
1.3.6.1.4.1.13742.6.3.8.3.1.2ColumnwireLabelread-onlydeprecatedThe label on the PDU identifying the wire.
1.3.6.1.4.1.13742.6.3.8.3.1.3ColumnwireCapabilitiesread-onlydeprecatedA bit string indicating which wire sensors are available.
1.3.6.1.4.1.13742.6.3.8.3.1.4ColumnwirePowerSourceread-onlydeprecatedThis object allows discovery of how the PDU is wired. It indicates the wire's power source which can one of the following: - an inlet - an overcurrent protecto…
1.3.6.1.4.1.13742.6.3.8.4TablewireSensorConfigurationTablenot-accessibledeprecatedA list of wire sensor configuration entries. Note: This feature is no longer used, the table is always empty.
1.3.6.1.4.1.13742.6.3.8.4.1RowwireSensorConfigurationEntrynot-accessibledeprecatedAn wireSensor entry containing objects for a particular wire Sensor.
1.3.6.1.4.1.13742.6.3.8.4.1.4ColumnwireSensorLogAvailableread-writedeprecatedIs data logging enabled for this sensor?
1.3.6.1.4.1.13742.6.3.8.4.1.6ColumnwireSensorUnitsread-onlydeprecatedThe unit in which the sensor reading is reported. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.8.4.1.7ColumnwireSensorDecimalDigitsread-onlydeprecatedThe number of digits displayed to the right of the decimal point. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.8.4.1.8ColumnwireSensorAccuracyread-onlydeprecatedThe accuracy: the maximum relative difference (in percent) between measurement and the actual value. This parameter does not apply to sensors without numerical…
1.3.6.1.4.1.13742.6.3.8.4.1.9ColumnwireSensorResolutionread-onlydeprecatedThe resolution: the minimum difference between any two measured values The value of this OID variable should be scaled by wireSensorDecimalDigits. For example,…
1.3.6.1.4.1.13742.6.3.8.4.1.10ColumnwireSensorToleranceread-onlydeprecatedThe tolerance: the maximum difference between measurement and the actual value. The value of this OID variable should be scaled by (wireSensorDecimalDigits + 1…
1.3.6.1.4.1.13742.6.3.8.4.1.11ColumnwireSensorMaximumread-onlydeprecatedThe largest possible value The value of this OID variable should be scaled by wireSensorDecimalDigits. For example, if the value is 1 and wireSensorDecimalDigi…
1.3.6.1.4.1.13742.6.3.8.4.1.12ColumnwireSensorMinimumread-onlydeprecatedThe smallest possible value The value of this OID variable should be scaled by wireSensorDecimalDigits. For example, if the value is 1 and wireSensorDecimalDig…
1.3.6.1.4.1.13742.6.3.8.4.1.13ColumnwireSensorHysteresisread-writedeprecatedThe hysteresis used when crossing a threshold towards the normal state. The value of this OID variable should be scaled by wireSensorDecimalDigits. For example…
1.3.6.1.4.1.13742.6.3.8.4.1.14ColumnwireSensorStateChangeDelayread-writedeprecatedThe delay measured in samples before a state is asserted. If the value is zero, then the state is asserted as soon as it is detected; if it is non-zero, say n,…
1.3.6.1.4.1.13742.6.3.8.4.1.21ColumnwireSensorLowerCriticalThresholdread-writedeprecatedThe lower critical threshold The value of this OID variable should be scaled by wireSensorDecimalDigits. For example, if the value is 1 and wireSensorDecimalDi…
1.3.6.1.4.1.13742.6.3.8.4.1.22ColumnwireSensorLowerWarningThresholdread-writedeprecatedThe lower non-critical (warning) threshold The value of this OID variable should be scaled by wireSensorDecimalDigits. For example, if the value is 1 and wireS…
1.3.6.1.4.1.13742.6.3.8.4.1.23ColumnwireSensorUpperCriticalThresholdread-writedeprecatedThe upper critical threshold The value of this OID variable should be scaled by wireSensorDecimalDigits. For example, if the value is 1 and wireSensorDecimalDi…
1.3.6.1.4.1.13742.6.3.8.4.1.24ColumnwireSensorUpperWarningThresholdread-writedeprecatedThe upper non-critical (warning) threshold The value of this OID variable should be scaled by wireSensorDecimalDigits. For example, if the value is 1 and wireS…
1.3.6.1.4.1.13742.6.3.8.4.1.25ColumnwireSensorEnabledThresholdsread-writedeprecatedA bit string indicating which thresholds are enabled. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.9NodetransferSwitch
1.3.6.1.4.1.13742.6.3.9.3TabletransferSwitchConfigurationTablenot-accessiblecurrentA list of transfer switch configuration entries. The number of entries is given by the value of transferSwitchCount.
1.3.6.1.4.1.13742.6.3.9.3.1RowtransferSwitchConfigurationEntrynot-accessiblecurrentAn entry containing objects for a particular transfer switch.
1.3.6.1.4.1.13742.6.3.9.3.1.1ColumntransferSwitchIdnot-accessiblecurrentA unique value for each transfer switch. Its value ranges between 1 and the value of transferSwitchCount.
1.3.6.1.4.1.13742.6.3.9.3.1.2ColumntransferSwitchLabelread-onlycurrentThe label on the PDU identifying the transfer switch.
1.3.6.1.4.1.13742.6.3.9.3.1.3ColumntransferSwitchNameread-writecurrentThe user-defined name of the transfer switch.
1.3.6.1.4.1.13742.6.3.9.3.1.4ColumntransferSwitchPreferredInletread-onlycurrentThe preferred inlet. This is the inlet to be selected in case both inlets have acceptable power.
1.3.6.1.4.1.13742.6.3.9.3.1.5ColumntransferSwitchPoleCountread-onlycurrentThe number of poles.
1.3.6.1.4.1.13742.6.3.9.3.1.20ColumntransferSwitchAutoReTransferEnabledread-writecurrentEnables or disables automatic retransfer from the standby inlet to the preferred inlet after power has been restored.
1.3.6.1.4.1.13742.6.3.9.3.1.21ColumntransferSwitchAutoReTransferWaitTimeread-writecurrentThe delay for automatic retransfers. Retransfer occurs this many seconds after the condition causing the original transfer has been corrected.
1.3.6.1.4.1.13742.6.3.9.3.1.22ColumntransferSwitchAutoReTransferRequiresPhaseSyncread-writecurrentEnables or disables automatic retransfer in case the two inlets are not synchronized. If set to True, automatic retransfer is inhibited while a phase sync alar…
1.3.6.1.4.1.13742.6.3.9.3.1.23ColumntransferSwitchFrontPanelManualTransferButtonEnabledread-writecurrentEnables or disables the Manual Transfer button on the unit's front panel.
1.3.6.1.4.1.13742.6.3.9.3.1.24ColumntransferSwitchCapabilitiesread-onlycurrentA bit string indicating which sensors are available for the transfer switch.
1.3.6.1.4.1.13742.6.3.9.3.1.31ColumntransferSwitchPowerSource1read-onlycurrentThis object allows discovery of how the PDU is wired. It indicates the transfer switch's first power source, typically a fuse. It contains the OID of an overCu…
1.3.6.1.4.1.13742.6.3.9.3.1.32ColumntransferSwitchPowerSource2read-onlycurrentThis object allows discovery of how the PDU is wired. It indicates the transfer switch's second power source, typically a fuse. It contains the OID of an overC…
1.3.6.1.4.1.13742.6.3.9.4TabletransferSwitchSensorConfigurationTablenot-accessiblecurrentA list of transfer switch sensor configuration entries.
1.3.6.1.4.1.13742.6.3.9.4.1RowtransferSwitchSensorConfigurationEntrynot-accessiblecurrentAn entry containing parameters for a transfer switch sensor.
1.3.6.1.4.1.13742.6.3.9.4.1.4ColumntransferSwitchSensorLogAvailableread-writecurrentIs data logging enabled for this sensor?
1.3.6.1.4.1.13742.6.3.9.4.1.6ColumntransferSwitchSensorUnitsread-onlycurrentThe unit in which the sensor reading is reported. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.9.4.1.7ColumntransferSwitchSensorDecimalDigitsread-onlycurrentThe number of digits displayed to the right of the decimal point This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.9.4.1.8ColumntransferSwitchSensorAccuracyread-onlydeprecatedThe accuracy: how close (in percent) the measurement is to the actual value This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.9.4.1.9ColumntransferSwitchSensorResolutionread-onlycurrentThe resolution: the minimum difference between any two measured values The value of this OID variable should be scaled by transferSwitchSensorDecimalDigits. Fo…
1.3.6.1.4.1.13742.6.3.9.4.1.10ColumntransferSwitchSensorToleranceread-onlydeprecatedThe tolerance: the maximum difference between measurement and the actual value. The value of this OID variable should be scaled by (transferSwitchSensorDecimal…
1.3.6.1.4.1.13742.6.3.9.4.1.11ColumntransferSwitchSensorMaximumread-onlycurrentThe largest possible reading as an unsigned integer. The value of this OID variable should be scaled by transferSwitchSensorDecimalDigits. For example, if the …
1.3.6.1.4.1.13742.6.3.9.4.1.12ColumntransferSwitchSensorMinimumread-onlycurrentThe smallest possible reading as an unsigned integer. The value of this OID variable should be scaled by transferSwitchSensorDecimalDigits. For example, if the…
1.3.6.1.4.1.13742.6.3.9.4.1.13ColumntransferSwitchSensorHysteresisread-writecurrentThe hysteresis used when crossing a threshold towards the normal state. The value of this OID variable should be scaled by transferSwitchSensorDecimalDigits. F…
1.3.6.1.4.1.13742.6.3.9.4.1.14ColumntransferSwitchSensorStateChangeDelayread-writecurrentThe delay measured in samples before a state is asserted. If the value is zero, then the state is asserted as soon as it is detected; if it is non-zero, say n,…
1.3.6.1.4.1.13742.6.3.9.4.1.21ColumntransferSwitchSensorLowerCriticalThresholdread-writecurrentThe lower critical threshold as an unsigned integer. The value of this OID variable should be scaled by transferSwitchSensorDecimalDigits. For example, if the …
1.3.6.1.4.1.13742.6.3.9.4.1.22ColumntransferSwitchSensorLowerWarningThresholdread-writecurrentThe lower warning threshold as an unsigned integer. The value of this OID variable should be scaled by transferSwitchSensorDecimalDigits. For example, if the v…
1.3.6.1.4.1.13742.6.3.9.4.1.23ColumntransferSwitchSensorUpperCriticalThresholdread-writecurrentThe upper critical threshold as an unsigned integer. The value of this OID variable should be scaled by transferSwitchSensorDecimalDigits. For example, if the …
1.3.6.1.4.1.13742.6.3.9.4.1.24ColumntransferSwitchSensorUpperWarningThresholdread-writecurrentThe upper warning threshold as an unsigned integer. The value of this OID variable should be scaled by transferSwitchSensorDecimalDigits. For example, if the v…
1.3.6.1.4.1.13742.6.3.9.4.1.25ColumntransferSwitchSensorEnabledThresholdsread-writecurrentA bit string indicating which thresholds are enabled. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.9.4.1.26ColumntransferSwitchSensorSignedMaximumread-onlycurrentThe largest possible reading as a signed integer. The value of this OID variable should be scaled by transferSwitchSensorDecimalDigits. For example, if the val…
1.3.6.1.4.1.13742.6.3.9.4.1.27ColumntransferSwitchSensorSignedMinimumread-onlycurrentThe smallest possible reading as a signed integer. The value of this OID variable should be scaled by transferSwitchSensorDecimalDigits. For example, if the va…
1.3.6.1.4.1.13742.6.3.9.4.1.28ColumntransferSwitchSensorSignedLowerCriticalThresholdread-writecurrentThe lower critical threshold as a signed integer. The value of this OID variable should be scaled by transferSwitchSensorDecimalDigits. For example, if the val…
1.3.6.1.4.1.13742.6.3.9.4.1.29ColumntransferSwitchSensorSignedLowerWarningThresholdread-writecurrentThe lower warning threshold as a signed integer. The value of this OID variable should be scaled by transferSwitchSensorDecimalDigits. For example, if the valu…
1.3.6.1.4.1.13742.6.3.9.4.1.30ColumntransferSwitchSensorSignedUpperCriticalThresholdread-writecurrentThe upper critical threshold as a signed integer. The value of this OID variable should be scaled by transferSwitchSensorDecimalDigits. For example, if the val…
1.3.6.1.4.1.13742.6.3.9.4.1.31ColumntransferSwitchSensorSignedUpperWarningThresholdread-writecurrentThe upper warning threshold as a signed integer. The value of this OID variable should be scaled by transferSwitchSensorDecimalDigits. For example, if the valu…
1.3.6.1.4.1.13742.6.3.9.5TabletransferSwitchPoleConfigurationTablenot-accessiblecurrentA list of transfer switch pole configuration entries. The number of entries is given by the value of transferSwitchPoleCount.
1.3.6.1.4.1.13742.6.3.9.5.1RowtransferSwitchPoleConfigurationEntrynot-accessiblecurrentAn entry containing parameters for a particular transfer switch pole.
1.3.6.1.4.1.13742.6.3.9.5.1.1ColumntransferSwitchPoleIndexnot-accessiblecurrentA unique value for each transfer switch pole. Its value ranges between 1 and the value of transferSwitchPoleCount.
1.3.6.1.4.1.13742.6.3.9.5.1.2ColumntransferSwitchPoleLineread-onlycurrentThe phase for this transfer switch pole.
1.3.6.1.4.1.13742.6.3.9.5.1.3ColumntransferSwitchPoleIn1Noderead-onlycurrentThe node to which this transfer switch pole input 1 is connected
1.3.6.1.4.1.13742.6.3.9.5.1.4ColumntransferSwitchPoleIn2Noderead-onlycurrentThe node to which this transfer switch pole input 2 is connected
1.3.6.1.4.1.13742.6.3.9.5.1.5ColumntransferSwitchPoleOutNoderead-onlycurrentThe node to which this transfer switch pole output is connected
1.3.6.1.4.1.13742.6.3.10NodepowerMeter
1.3.6.1.4.1.13742.6.3.10.2TablepowerMeterConfigurationTablenot-accessiblecurrentA list of power meter and panel configuration entries. Note: Also see inlet tables for settings and sensor information.
1.3.6.1.4.1.13742.6.3.10.2.1RowpowerMeterConfigurationEntrynot-accessiblecurrentAn entry containing configuration objects for power meters and panels.
1.3.6.1.4.1.13742.6.3.10.2.1.2ColumnpowerMeterPhaseCTRatingread-writecurrentThe rating of the phase CT in Amps, or 0 if no CT is present. At present, read-only access; see MIN-ACCESS in MODULE-COMPLIANCE ModulecomplianceRev2
1.3.6.1.4.1.13742.6.3.10.2.1.3ColumnpowerMeterNeutralCTRatingread-writecurrentThe rating of the neutral CT in Amps, or 0 if no CT is present. At present, read-only access; see MIN-ACCESS in MODULE-COMPLIANCE ModulecomplianceRev2
1.3.6.1.4.1.13742.6.3.10.2.1.4ColumnpowerMeterEarthCTRatingread-writecurrentThe rating of the earth CT in Amps, or 0 if no CT is present. At present, read-only access; see MIN-ACCESS in MODULE-COMPLIANCE ModulecomplianceRev2
1.3.6.1.4.1.13742.6.3.10.2.1.5ColumnpowerMeterBranchCountread-onlycurrentThe maximum number of circuits supported by the panel. This can be used to distinguish between panels (>0) and power meters (0). See circuitCount for the numbe…
1.3.6.1.4.1.13742.6.3.10.2.1.6ColumnpowerMeterPanelPositionsread-onlycurrentThe number of circuit positions in the panel. Its value is specified by the user when configuring a panel
1.3.6.1.4.1.13742.6.3.10.2.1.7ColumnpowerMeterPanelLayoutread-onlycurrentThe panel circuit position layout: one or two columns. This is valid only for panels, the value is -1 for power meters.
1.3.6.1.4.1.13742.6.3.10.2.1.8ColumnpowerMeterPanelNumberingread-onlycurrentThe panel circuit position numbering scheme: odd/even or sequential. This is valid only for panels, the value is -1 for power meters.
1.3.6.1.4.1.13742.6.3.10.2.1.9ColumnpowerMeterTyperead-onlycurrentThe power meter type: 3-phase, single-phase or split-phase.
1.3.6.1.4.1.13742.6.3.11Nodecircuit
1.3.6.1.4.1.13742.6.3.11.2TablecircuitConfigurationTablenot-accessiblecurrentA list of circuit configuration entries. The number of entries is given by the value of panelCircuitPositionCount.
1.3.6.1.4.1.13742.6.3.11.2.1RowcircuitConfigurationEntrynot-accessiblecurrentAn entry containing configuration objects for the circuit.
1.3.6.1.4.1.13742.6.3.11.2.1.1ColumncircuitIdnot-accessiblecurrentA unique value for each circuit. Its value is the smallest panel position occupied by the circuit.
1.3.6.1.4.1.13742.6.3.11.2.1.2ColumncircuitPoleCountread-onlycurrentThe number of panel positions occupied by the circuit.
1.3.6.1.4.1.13742.6.3.11.2.1.3ColumncircuitNameread-writecurrentThe user-defined name for the circuit. At present, read-only access; see MIN-ACCESS in MODULE-COMPLIANCE ModulecomplianceRev2
1.3.6.1.4.1.13742.6.3.11.2.1.4ColumncircuitTyperead-onlycurrentThe circuit type: line-line, line-neutral, line-line-neutral or 3-phase
1.3.6.1.4.1.13742.6.3.11.2.1.5ColumncircuitRatedCurrentread-writecurrentThe rating of the breaker for the circuit in Amps. At present, read-only access; see MIN-ACCESS in MODULE-COMPLIANCE ModulecomplianceRev2
1.3.6.1.4.1.13742.6.3.11.2.1.6ColumncircuitCTRatingread-writecurrentThe rating of the CTs metering this circuit in Amps. At present, read-only access; see MIN-ACCESS in MODULE-COMPLIANCE ModulecomplianceRev2
1.3.6.1.4.1.13742.6.3.11.2.1.7ColumncircuitCapabilitiesread-onlycurrentA bit string indicating which sensors are available for the circuit.
1.3.6.1.4.1.13742.6.3.11.2.1.8ColumncircuitPoleCapabilitiesread-onlycurrentA bit string indicating which sensors are available for each circuit pole.
1.3.6.1.4.1.13742.6.3.11.2.1.9ColumncircuitPowerSourceread-onlycurrentThis object allows discovery of how the circuit is wired. It indicates the circuit's power source, typically an inlet. It contains the OID of an inletLabel in …
1.3.6.1.4.1.13742.6.3.11.3TablecircuitPoleConfigurationTablenot-accessiblecurrentA list of branch circuit pole configuration entries. The number of entries is given by the value of circuitPoleCount for the circuit.
1.3.6.1.4.1.13742.6.3.11.3.1RowcircuitPoleConfigurationEntrynot-accessiblecurrentAn entry containing configuration objects for the circuit poles.
1.3.6.1.4.1.13742.6.3.11.3.1.1ColumncircuitPoleIdnot-accessiblecurrentA unique value for each circuit pole. Its value ranges between 1 and the value of circuitPoleCount.
1.3.6.1.4.1.13742.6.3.11.3.1.2ColumncircuitPolePanelPositionread-onlycurrentThe panel position for this pole.
1.3.6.1.4.1.13742.6.3.11.3.1.3ColumncircuitPoleCTNumberread-writecurrentThe CT number for this circuit pole, or 0 if no CT is present. At present, read-only access; see MIN-ACCESS in MODULE-COMPLIANCE ModulecomplianceRev2
1.3.6.1.4.1.13742.6.3.11.3.1.4ColumncircuitPolePhaseread-writecurrentThe phase for this circuit pole. At present, read-only access; see MIN-ACCESS in MODULE-COMPLIANCE ModulecomplianceRev2
1.3.6.1.4.1.13742.6.3.11.4TablecircuitSensorConfigurationTablenot-accessiblecurrentA list of configuration entries for branch circuit sensor.
1.3.6.1.4.1.13742.6.3.11.4.1RowcircuitSensorConfigurationEntrynot-accessiblecurrentAn entry containing objects for configuring a branch circuit sensor.
1.3.6.1.4.1.13742.6.3.11.4.1.4ColumncircuitSensorLogAvailableread-writecurrentIs data logging enabled for the sensor?
1.3.6.1.4.1.13742.6.3.11.4.1.6ColumncircuitSensorUnitsread-onlycurrentThe unit in which the sensor reading is reported. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.11.4.1.7ColumncircuitSensorDecimalDigitsread-onlycurrentThe number of digits displayed to the right of the decimal point. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.11.4.1.9ColumncircuitSensorResolutionread-onlycurrentThe resolution: the minimum difference between any two measured values The value of this OID variable should be scaled by inletSensorDecimalDigits. For example…
1.3.6.1.4.1.13742.6.3.11.4.1.11ColumncircuitSensorMaximumread-onlycurrentThe largest possible reading as an unsigned integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is …
1.3.6.1.4.1.13742.6.3.11.4.1.12ColumncircuitSensorMinimumread-onlycurrentThe smallest possible reading as an unsigned integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is…
1.3.6.1.4.1.13742.6.3.11.4.1.13ColumncircuitSensorHysteresisread-writecurrentThe hysteresis used when crossing a threshold towards the normal state. The value of this OID variable should be scaled by inletSensorDecimalDigits. For exampl…
1.3.6.1.4.1.13742.6.3.11.4.1.14ColumncircuitSensorStateChangeDelayread-writecurrentThe delay measured in samples before a state is asserted. If the value is zero, then the state is asserted as soon as it is detected; if it is non-zero, say n,…
1.3.6.1.4.1.13742.6.3.11.4.1.21ColumncircuitSensorLowerCriticalThresholdread-writecurrentThe lower critical threshold as an unsigned integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is …
1.3.6.1.4.1.13742.6.3.11.4.1.22ColumncircuitSensorLowerWarningThresholdread-writecurrentThe lower warning threshold as an unsigned integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1…
1.3.6.1.4.1.13742.6.3.11.4.1.23ColumncircuitSensorUpperCriticalThresholdread-writecurrentThe upper critical threshold as an unsigned integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is …
1.3.6.1.4.1.13742.6.3.11.4.1.24ColumncircuitSensorUpperWarningThresholdread-writecurrentThe upper warning threshold as an unsigned integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1…
1.3.6.1.4.1.13742.6.3.11.4.1.25ColumncircuitSensorEnabledThresholdsread-writecurrentA bit string indicating which thresholds are enabled. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.11.4.1.26ColumncircuitSensorSignedMaximumread-onlycurrentThe largest possible reading as a signed integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1 a…
1.3.6.1.4.1.13742.6.3.11.4.1.27ColumncircuitSensorSignedMinimumread-onlycurrentThe smallest possible reading as a signed integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1 …
1.3.6.1.4.1.13742.6.3.11.4.1.28ColumncircuitSensorSignedLowerCriticalThresholdread-writecurrentThe lower critical threshold as a signed integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1 a…
1.3.6.1.4.1.13742.6.3.11.4.1.29ColumncircuitSensorSignedLowerWarningThresholdread-writecurrentThe lower warning threshold as a signed integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1 an…
1.3.6.1.4.1.13742.6.3.11.4.1.30ColumncircuitSensorSignedUpperCriticalThresholdread-writecurrentThe upper critical threshold as a signed integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1 a…
1.3.6.1.4.1.13742.6.3.11.4.1.31ColumncircuitSensorSignedUpperWarningThresholdread-writecurrentThe upper warning threshold as a signed integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1 an…
1.3.6.1.4.1.13742.6.3.11.6TablecircuitPoleSensorConfigurationTablenot-accessiblecurrentA list of configuration entries for a circuit's pole sensors.
1.3.6.1.4.1.13742.6.3.11.6.1RowcircuitPoleSensorConfigurationEntrynot-accessiblecurrentAn entry containing objects for configuring a circuit pole sensor.
1.3.6.1.4.1.13742.6.3.11.6.1.4ColumncircuitPoleSensorLogAvailableread-writecurrentIs data logging enabled for the sensor?
1.3.6.1.4.1.13742.6.3.11.6.1.6ColumncircuitPoleSensorUnitsread-onlycurrentThe unit in which the sensor reading is reported. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.11.6.1.7ColumncircuitPoleSensorDecimalDigitsread-onlycurrentThe number of digits displayed to the right of the decimal point. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.11.6.1.9ColumncircuitPoleSensorResolutionread-onlycurrentThe resolution: the minimum difference between any two measured values The value of this OID variable should be scaled by inletPoleSensorDecimalDigits. For exa…
1.3.6.1.4.1.13742.6.3.11.6.1.11ColumncircuitPoleSensorMaximumread-onlycurrentThe largest possible reading as an unsigned integer. The value of this OID variable should be scaled by inletPoleSensorDecimalDigits. For example, if the value…
1.3.6.1.4.1.13742.6.3.11.6.1.12ColumncircuitPoleSensorMinimumread-onlycurrentThe smallest possible reading as an unsigned integer. The value of this OID variable should be scaled by inletPoleSensorDecimalDigits. For example, if the valu…
1.3.6.1.4.1.13742.6.3.11.6.1.13ColumncircuitPoleSensorHysteresisread-writecurrentThe hysteresis used when crossing a threshold towards the normal state. The value of this OID variable should be scaled by inletPoleSensorDecimalDigits. For ex…
1.3.6.1.4.1.13742.6.3.11.6.1.14ColumncircuitPoleSensorStateChangeDelayread-writecurrentThe delay measured in samples before a state is asserted. If the value is zero, then the state is asserted as soon as it is detected; if it is non-zero, say n,…
1.3.6.1.4.1.13742.6.3.11.6.1.21ColumncircuitPoleSensorLowerCriticalThresholdread-writecurrentThe lower critical threshold as an unsigned integer. The value of this OID variable should be scaled by inletPoleSensorDecimalDigits. For example, if the value…
1.3.6.1.4.1.13742.6.3.11.6.1.22ColumncircuitPoleSensorLowerWarningThresholdread-writecurrentThe lower warning threshold as an unsigned integer. The value of this OID variable should be scaled by inletPoleSensorDecimalDigits. For example, if the value …
1.3.6.1.4.1.13742.6.3.11.6.1.23ColumncircuitPoleSensorUpperCriticalThresholdread-writecurrentThe upper critical threshold as an unsigned integer. The value of this OID variable should be scaled by inletPoleSensorDecimalDigits. For example, if the value…
1.3.6.1.4.1.13742.6.3.11.6.1.24ColumncircuitPoleSensorUpperWarningThresholdread-writecurrentThe upper warning threshold as an unsigned integer. The value of this OID variable should be scaled by inletPoleSensorDecimalDigits. For example, if the value …
1.3.6.1.4.1.13742.6.3.11.6.1.25ColumncircuitPoleSensorEnabledThresholdsread-writecurrentA bit string indicating which thresholds are enabled. This parameter does not apply to sensors without numerical reading.
1.3.6.1.4.1.13742.6.3.11.6.1.26ColumncircuitPoleSensorSignedMaximumread-onlycurrentThe largest possible reading as a signed integer. The value of this OID variable should be scaled by inletPoleSensorDecimalDigits. For example, if the value is…
1.3.6.1.4.1.13742.6.3.11.6.1.27ColumncircuitPoleSensorSignedMinimumread-onlycurrentThe smallest possible reading as a signed integer. The value of this OID variable should be scaled by inletPoleSensorDecimalDigits. For example, if the value i…
1.3.6.1.4.1.13742.6.3.11.6.1.28ColumncircuitPoleSensorSignedLowerCriticalThresholdread-writecurrentThe lower critical threshold as a signed integer. The value of this OID variable should be scaled by inletPoleSensorDecimalDigits. For example, if the value is…
1.3.6.1.4.1.13742.6.3.11.6.1.29ColumncircuitPoleSensorSignedLowerWarningThresholdread-writecurrentThe lower warning threshold as a signed integer. The value of this OID variable should be scaled by inletPoleSensorDecimalDigits. For example, if the value is …
1.3.6.1.4.1.13742.6.3.11.6.1.30ColumncircuitPoleSensorSignedUpperCriticalThresholdread-writecurrentThe upper critical threshold as a signed integer. The value of this OID variable should be scaled by inletPoleSensorDecimalDigits. For example, if the value is…
1.3.6.1.4.1.13742.6.3.11.6.1.31ColumncircuitPoleSensorSignedUpperWarningThresholdread-writecurrentThe upper warning threshold as a signed integer. The value of this OID variable should be scaled by inletPoleSensorDecimalDigits. For example, if the value is …
1.3.6.1.4.1.13742.6.4Nodecontrol
1.3.6.1.4.1.13742.6.4.1NodeoutletControl
1.3.6.1.4.1.13742.6.4.1.2TableoutletSwitchControlTablenot-accessiblecurrentA list of outlets for a PDU. The number of entries is given by the value of outletCount.
1.3.6.1.4.1.13742.6.4.1.2.1RowoutletSwitchControlEntrynot-accessiblecurrentAn entry for implementing switching operations on an outlet.
1.3.6.1.4.1.13742.6.4.1.2.1.2ColumnswitchingOperationread-writecurrentThe switching operation: switch on, switch off or power-cycle.
1.3.6.1.4.1.13742.6.4.1.2.1.3ColumnoutletSwitchingStateread-onlycurrentThe outlet state at present
1.3.6.1.4.1.13742.6.4.1.2.1.4ColumnoutletSwitchingTimeStampread-onlycurrentThe timestamp indicating when the outlet was last switched
1.3.6.1.4.1.13742.6.4.2NodeexternalSensorControl
1.3.6.1.4.1.13742.6.4.3NodetransferSwitchControl
1.3.6.1.4.1.13742.6.4.3.1TabletransferSwitchControlTablenot-accessiblecurrentA list of transfer switches for a PDU. The number of entries is given by the value of transferSwitchCount.
1.3.6.1.4.1.13742.6.4.3.1.1RowtransferSwitchControlEntrynot-accessiblecurrentAn entry for implementing switching operations on a transfer switch.
1.3.6.1.4.1.13742.6.4.3.1.1.1ColumntransferSwitchActiveInletread-onlycurrentThe index of the currently active inlet.
1.3.6.1.4.1.13742.6.4.3.1.1.2ColumntransferSwitchTransferToInletread-writecurrentSelect the active inlet. If the new inlet is available, it will become both active and preferred, otherwise an inconsistentValue error will be returned. By def…
1.3.6.1.4.1.13742.6.4.3.1.1.3ColumntransferSwitchAlarmOverrideread-writecurrentForce transfer even if the phase difference between the inlets is too large. This may only be written together with transferSwitchTransferToInlet, otherwise an…
1.3.6.1.4.1.13742.6.4.3.1.1.4ColumntransferSwitchLastTransferReasonread-onlycurrentThe reason for the most recent transfer
1.3.6.1.4.1.13742.6.4.4NodeactuatorControl
1.3.6.1.4.1.13742.6.4.4.2TableactuatorControlTablenot-accessiblecurrentA list of actuators for a PDU.
1.3.6.1.4.1.13742.6.4.4.2.1RowactuatorControlEntrynot-accessiblecurrentAn entry for implementing user-initiated state changes for an actuator.
1.3.6.1.4.1.13742.6.4.4.2.1.2ColumnactuatorStateread-writecurrentThe actuator state. A get operation retrieves the state of the actuator. A set operation changes the state of the sensor. The valid states for set operations a…
1.3.6.1.4.1.13742.6.4.5NodercmControl
1.3.6.1.4.1.13742.6.4.5.2TablercmSelfTestTablenot-accessiblecurrentA list of RCMs.
1.3.6.1.4.1.13742.6.4.5.2.1RowrcmSelfTestEntrynot-accessiblecurrentAn entry for initiating the self test of an RCM.
1.3.6.1.4.1.13742.6.4.5.2.1.2ColumnrcmStateread-writecurrentThe rcm state. A Get operation retrieves the state of the RCM State Sensor. A Set operation changes the state of the sensor. The only valid state for set opera…
1.3.6.1.4.1.13742.6.4.6NodeinletSensorControl
1.3.6.1.4.1.13742.6.4.6.1TableinletSensorControlTablenot-accessiblecurrentA list of control entries for the inlet sensors of a PDU. The set of valid indices is defined by the value of inletCount and the inletDeviceCapabilities entry …
1.3.6.1.4.1.13742.6.4.6.1.1RowinletSensorControlEntrynot-accessiblecurrentAn entry used for controlling an inlet sensor.
1.3.6.1.4.1.13742.6.4.6.1.1.1ColumninletSensorResetValueread-writecurrentWriting to this variable sets a new value for the addressed sensor. Only accumulating sensors (e.g. energy counters) can be reset, and currently the only suppo…
1.3.6.1.4.1.13742.6.4.7NodeoutletSensorControl
1.3.6.1.4.1.13742.6.4.7.1TableoutletSensorControlTablenot-accessiblecurrentA list of control entries for the outlet sensors of a PDU. The set of valid indices is defined by the value of outletCount and the outletDeviceCapabilities ent…
1.3.6.1.4.1.13742.6.4.7.1.1RowoutletSensorControlEntrynot-accessiblecurrentAn entry used for controlling an outlet sensor.
1.3.6.1.4.1.13742.6.4.7.1.1.1ColumnoutletSensorResetValueread-writecurrentWriting to this variable sets a new value for the addressed sensor. Only accumulating sensors (e.g. energy counters) can be reset, and currently the only suppo…
1.3.6.1.4.1.13742.6.4.8NodeunitSensorControl
1.3.6.1.4.1.13742.6.4.8.1TableunitSensorControlTablenot-accessiblecurrentA list of control entries for the global sensors of a PDU. The set of valid indices is defined by the value of pduCount and the pduDeviceCapabilities entry.
1.3.6.1.4.1.13742.6.4.8.1.1RowunitSensorControlEntrynot-accessiblecurrentAn entry used for controlling an global sensor.
1.3.6.1.4.1.13742.6.4.8.1.1.1ColumnunitSensorResetValueread-writecurrentWriting to this variable sets a new value for the addressed sensor. Only accumulating sensors (e.g. energy counters) can be reset, and currently the only suppo…
1.3.6.1.4.1.13742.6.4.9NodecircuitSensorControl
1.3.6.1.4.1.13742.6.4.9.1TablecircuitSensorControlTablenot-accessiblecurrentA list of control entries for the circuit sensors of a BCM2. The maximum number of entries is given by the value of panelCircuitPositionCount.
1.3.6.1.4.1.13742.6.4.9.1.1RowcircuitSensorControlEntrynot-accessiblecurrentAn entry used for controlling an circuit sensor.
1.3.6.1.4.1.13742.6.4.9.1.1.1ColumncircuitSensorResetValueread-writecurrentWriting to this variable sets a new value for the addressed sensor. Only accumulating sensors (e.g. energy counters) can be reset, and currently the only suppo…
1.3.6.1.4.1.13742.6.5Nodemeasurements
1.3.6.1.4.1.13742.6.5.1NodemeasurementsUnit
1.3.6.1.4.1.13742.6.5.1.3TableunitSensorMeasurementsTablenot-accessiblecurrentA list of unit sensor entries.
1.3.6.1.4.1.13742.6.5.1.3.1RowunitSensorMeasurementsEntrynot-accessiblecurrentAn entry containing measurement objects for an unit sensor.
1.3.6.1.4.1.13742.6.5.1.3.1.2ColumnmeasurementsUnitSensorIsAvailableread-onlycurrentIs the sensor available?
1.3.6.1.4.1.13742.6.5.1.3.1.3ColumnmeasurementsUnitSensorStateread-onlycurrentThe sensor state.
1.3.6.1.4.1.13742.6.5.1.3.1.4ColumnmeasurementsUnitSensorValueread-onlycurrentThe sensor reading as an unsigned integer. The value of this OID variable should be scaled by unitSensorDecimalDigits. For example, if the value is 1 and unitS…
1.3.6.1.4.1.13742.6.5.1.3.1.5ColumnmeasurementsUnitSensorTimeStampread-onlycurrentThe timestamp.
1.3.6.1.4.1.13742.6.5.1.3.1.6ColumnmeasurementsUnitSensorSignedValueread-onlycurrentThe sensor reading as a signed integer. The value of this OID variable should be scaled by unitSensorDecimalDigits. For example, if the value is 1 and unitSens…
1.3.6.1.4.1.13742.6.5.2NodemeasurementsInlet
1.3.6.1.4.1.13742.6.5.2.3TableinletSensorMeasurementsTablenot-accessiblecurrentA list of inlet sensor entries.
1.3.6.1.4.1.13742.6.5.2.3.1RowinletSensorMeasurementsEntrynot-accessiblecurrentAn entry containing measurement objects for an inlet sensor.
1.3.6.1.4.1.13742.6.5.2.3.1.2ColumnmeasurementsInletSensorIsAvailableread-onlycurrentIs the sensor available?
1.3.6.1.4.1.13742.6.5.2.3.1.3ColumnmeasurementsInletSensorStateread-onlycurrentThe sensor state.
1.3.6.1.4.1.13742.6.5.2.3.1.4ColumnmeasurementsInletSensorValueread-onlycurrentThe sensor reading as an unsigned integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1 and inle…
1.3.6.1.4.1.13742.6.5.2.3.1.5ColumnmeasurementsInletSensorTimeStampread-onlycurrentThe timestamp.
1.3.6.1.4.1.13742.6.5.2.3.1.6ColumnmeasurementsInletSensorSignedValueread-onlycurrentThe sensor reading as a signed integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1 and inletSe…
1.3.6.1.4.1.13742.6.5.2.4TableinletPoleSensorMeasurementsTablenot-accessiblecurrentA list of inlet pole sensor entries.
1.3.6.1.4.1.13742.6.5.2.4.1RowinletPoleSensorMeasurementsEntrynot-accessiblecurrentAn entry containing measurement objects for an inlet pole sensor.
1.3.6.1.4.1.13742.6.5.2.4.1.2ColumnmeasurementsInletPoleSensorIsAvailableread-onlycurrentIs the sensor available?
1.3.6.1.4.1.13742.6.5.2.4.1.3ColumnmeasurementsInletPoleSensorStateread-onlycurrentThe sensor state.
1.3.6.1.4.1.13742.6.5.2.4.1.4ColumnmeasurementsInletPoleSensorValueread-onlycurrentThe sensor reading as an unsigned integer. The value of this OID variable should be scaled by inletPoleSensorDecimalDigits. For example, if the value is 1 and …
1.3.6.1.4.1.13742.6.5.2.4.1.5ColumnmeasurementsInletPoleSensorTimeStampread-onlycurrentThe timestamp.
1.3.6.1.4.1.13742.6.5.2.4.1.6ColumnmeasurementsInletPoleSensorSignedValueread-onlycurrentThe sensor reading as a signed integer. The value of this OID variable should be scaled by inletPoleSensorDecimalDigits. For example, if the value is 1 and inl…
1.3.6.1.4.1.13742.6.5.3NodemeasurementsOverCurrentProtector
1.3.6.1.4.1.13742.6.5.3.3TableoverCurrentProtectorSensorMeasurementsTablenot-accessiblecurrentA list of overcurrent protector sensor entries.
1.3.6.1.4.1.13742.6.5.3.3.1RowoverCurrentProtectorSensorMeasurementsEntrynot-accessiblecurrentAn entry containing measurement objects for an overcurrent protector sensor.
1.3.6.1.4.1.13742.6.5.3.3.1.2ColumnmeasurementsOverCurrentProtectorSensorIsAvailableread-onlycurrentIs the sensor available?
1.3.6.1.4.1.13742.6.5.3.3.1.3ColumnmeasurementsOverCurrentProtectorSensorStateread-onlycurrentThe sensor state.
1.3.6.1.4.1.13742.6.5.3.3.1.4ColumnmeasurementsOverCurrentProtectorSensorValueread-onlycurrentThe sensor reading as an unsigned integer. The value of this OID variable should be scaled by overCurrentProtectorSensorDecimalDigits. For example, if the valu…
1.3.6.1.4.1.13742.6.5.3.3.1.5ColumnmeasurementsOverCurrentProtectorSensorTimeStampread-onlycurrentThe timestamp.
1.3.6.1.4.1.13742.6.5.3.3.1.6ColumnmeasurementsOverCurrentProtectorSensorSignedValueread-onlycurrentThe sensor reading as a signed integer. The value of this OID variable should be scaled by overCurrentProtectorSensorDecimalDigits. For example, if the value i…
1.3.6.1.4.1.13742.6.5.4NodemeasurementsOutlet
1.3.6.1.4.1.13742.6.5.4.3TableoutletSensorMeasurementsTablenot-accessiblecurrentA list of outlet sensor entries.
1.3.6.1.4.1.13742.6.5.4.3.1RowoutletSensorMeasurementsEntrynot-accessiblecurrentAn entry containing measurement objects for an outlet sensor.
1.3.6.1.4.1.13742.6.5.4.3.1.2ColumnmeasurementsOutletSensorIsAvailableread-onlycurrentIs the sensor available?
1.3.6.1.4.1.13742.6.5.4.3.1.3ColumnmeasurementsOutletSensorStateread-onlycurrentThe sensor state.
1.3.6.1.4.1.13742.6.5.4.3.1.4ColumnmeasurementsOutletSensorValueread-onlycurrentThe sensor reading as an unsigned integer. The value of this OID variable should be scaled by outletSensorDecimalDigits. For example, if the value is 1 and out…
1.3.6.1.4.1.13742.6.5.4.3.1.5ColumnmeasurementsOutletSensorTimeStampread-onlycurrentThe timestamp.
1.3.6.1.4.1.13742.6.5.4.3.1.6ColumnmeasurementsOutletSensorSignedValueread-onlycurrentThe sensor reading as a signed integer. The value of this OID variable should be scaled by outletSensorDecimalDigits. For example, if the value is 1 and outlet…
1.3.6.1.4.1.13742.6.5.4.4TableoutletPoleSensorMeasurementsTablenot-accessiblecurrentA list of outlet pole sensor entries.
1.3.6.1.4.1.13742.6.5.4.4.1RowoutletPoleSensorMeasurementsEntrynot-accessiblecurrentAn entry containing measurement objects for an outlet pole sensor.
1.3.6.1.4.1.13742.6.5.4.4.1.2ColumnmeasurementsOutletPoleSensorIsAvailableread-onlycurrentIs the sensor available?
1.3.6.1.4.1.13742.6.5.4.4.1.3ColumnmeasurementsOutletPoleSensorStateread-onlycurrentThe sensor state.
1.3.6.1.4.1.13742.6.5.4.4.1.4ColumnmeasurementsOutletPoleSensorValueread-onlycurrentThe sensor reading as an unsigned integer. The value of this OID variable should be scaled by outletPoleSensorDecimalDigits. For example, if the value is 1 and…
1.3.6.1.4.1.13742.6.5.4.4.1.5ColumnmeasurementsOutletPoleSensorTimeStampread-onlycurrentThe timestamp.
1.3.6.1.4.1.13742.6.5.4.4.1.6ColumnmeasurementsOutletPoleSensorSignedValueread-onlycurrentThe sensor reading as a signed integer. The value of this OID variable should be scaled by outletPoleSensorDecimalDigits. For example, if the value is 1 and ou…
1.3.6.1.4.1.13742.6.5.5NodemeasurementsExternalSensor
1.3.6.1.4.1.13742.6.5.5.3TableexternalSensorMeasurementsTablenot-accessiblecurrentA list of external sensor entries. The number of entries is given by the value of externalSensorCount for the PDU.
1.3.6.1.4.1.13742.6.5.5.3.1RowexternalSensorMeasurementsEntrynot-accessiblecurrentAn entry containing measurement objects for an external sensor.
1.3.6.1.4.1.13742.6.5.5.3.1.2ColumnmeasurementsExternalSensorIsAvailableread-onlycurrentIs the sensor available?
1.3.6.1.4.1.13742.6.5.5.3.1.3ColumnmeasurementsExternalSensorStateread-onlycurrentThe sensor state.
1.3.6.1.4.1.13742.6.5.5.3.1.4ColumnmeasurementsExternalSensorValueread-onlycurrentThe sensor reading as a signed integer. The value of this OID variable should be scaled by externalSensorDecimalDigits. For example, if the value is 1 and exte…
1.3.6.1.4.1.13742.6.5.5.3.1.5ColumnmeasurementsExternalSensorTimeStampread-onlycurrentThe sensor reading timestamp.
1.3.6.1.4.1.13742.6.5.6NodemeasurementsWire
1.3.6.1.4.1.13742.6.5.6.3TablewireSensorMeasurementsTablenot-accessibledeprecatedA list of wire sensor entries. Note: This feature is no longer used, the table is always empty.
1.3.6.1.4.1.13742.6.5.6.3.1RowwireSensorMeasurementsEntrynot-accessibledeprecatedAn entry containing measurement objects for a wire.
1.3.6.1.4.1.13742.6.5.6.3.1.2ColumnmeasurementsWireSensorIsAvailableread-onlydeprecatedIs the sensor available?
1.3.6.1.4.1.13742.6.5.6.3.1.3ColumnmeasurementsWireSensorStateread-onlydeprecatedThe sensor state.
1.3.6.1.4.1.13742.6.5.6.3.1.4ColumnmeasurementsWireSensorValueread-onlydeprecatedThe sensor value. The value of this OID variable should be scaled by wireSensorDecimalDigits. For example, if the value is 1 and wireSensorDecimalDigits is 2, …
1.3.6.1.4.1.13742.6.5.6.3.1.5ColumnmeasurementsWireSensorTimeStampread-onlydeprecatedThe timestamp.
1.3.6.1.4.1.13742.6.5.7NodemeasurementsTransferSwitch
1.3.6.1.4.1.13742.6.5.7.3TabletransferSwitchSensorMeasurementsTablenot-accessiblecurrentA list of transfer switch sensor entries.
1.3.6.1.4.1.13742.6.5.7.3.1RowtransferSwitchSensorMeasurementsEntrynot-accessiblecurrentAn entry containing measurement objects for a transfer switch sensor.
1.3.6.1.4.1.13742.6.5.7.3.1.2ColumnmeasurementsTransferSwitchSensorIsAvailableread-onlycurrentIs the sensor available?
1.3.6.1.4.1.13742.6.5.7.3.1.3ColumnmeasurementsTransferSwitchSensorStateread-onlycurrentThe sensor state.
1.3.6.1.4.1.13742.6.5.7.3.1.4ColumnmeasurementsTransferSwitchSensorValueread-onlycurrentThe sensor reading as an unsigned integer. The value of this OID variable should be scaled by transferSwitchSensorDecimalDigits. For example, if the value is 1…
1.3.6.1.4.1.13742.6.5.7.3.1.5ColumnmeasurementsTransferSwitchSensorTimeStampread-onlycurrentThe timestamp.
1.3.6.1.4.1.13742.6.5.7.3.1.6ColumnmeasurementsTransferSwitchSensorSignedValueread-onlycurrentThe sensor reading as a signed integer. The value of this OID variable should be scaled by transferSwitchSensorDecimalDigits. For example, if the value is 1 an…
1.3.6.1.4.1.13742.6.5.8NodemeasurementsCircuit
1.3.6.1.4.1.13742.6.5.8.3TablecircuitSensorMeasurementsTablenot-accessiblecurrentA list of circuit sensor entries.
1.3.6.1.4.1.13742.6.5.8.3.1RowcircuitSensorMeasurementsEntrynot-accessiblecurrentAn entry containing measurement objects for a circuit sensor.
1.3.6.1.4.1.13742.6.5.8.3.1.2ColumnmeasurementsCircuitSensorIsAvailableread-onlycurrentIs the sensor available?
1.3.6.1.4.1.13742.6.5.8.3.1.3ColumnmeasurementsCircuitSensorStateread-onlycurrentThe sensor state.
1.3.6.1.4.1.13742.6.5.8.3.1.4ColumnmeasurementsCircuitSensorValueread-onlycurrentThe sensor reading as an unsigned integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1 and inle…
1.3.6.1.4.1.13742.6.5.8.3.1.5ColumnmeasurementsCircuitSensorTimeStampread-onlycurrentThe timestamp.
1.3.6.1.4.1.13742.6.5.8.3.1.6ColumnmeasurementsCircuitSensorSignedValueread-onlycurrentThe sensor reading as a signed integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1 and inletSe…
1.3.6.1.4.1.13742.6.5.8.4TablecircuitPoleSensorMeasurementsTablenot-accessiblecurrentA list of panel circuit pole sensor entries.
1.3.6.1.4.1.13742.6.5.8.4.1RowcircuitPoleSensorMeasurementsEntrynot-accessiblecurrentAn entry containing measurement objects for a circuit pole sensor.
1.3.6.1.4.1.13742.6.5.8.4.1.2ColumnmeasurementsCircuitPoleSensorIsAvailableread-onlycurrentIs the sensor available?
1.3.6.1.4.1.13742.6.5.8.4.1.3ColumnmeasurementsCircuitPoleSensorStateread-onlycurrentThe sensor state.
1.3.6.1.4.1.13742.6.5.8.4.1.4ColumnmeasurementsCircuitPoleSensorValueread-onlycurrentThe sensor reading as an unsigned integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1 and inle…
1.3.6.1.4.1.13742.6.5.8.4.1.5ColumnmeasurementsCircuitPoleSensorTimeStampread-onlycurrentThe timestamp.
1.3.6.1.4.1.13742.6.5.8.4.1.6ColumnmeasurementsCircuitPoleSensorSignedValueread-onlycurrentThe sensor reading as a signed integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if the value is 1 and inletSe…
1.3.6.1.4.1.13742.6.6Nodelog
1.3.6.1.4.1.13742.6.6.1NodelogUnit
1.3.6.1.4.1.13742.6.6.1.1TablelogIndexTablenot-accessiblecurrentA table containing current indices for the data log buffer.
1.3.6.1.4.1.13742.6.6.1.1.1RowlogIndexEntrynot-accessiblecurrentAn entry containing the current indices for a PDU's data log buffer.
1.3.6.1.4.1.13742.6.6.1.1.1.2ColumnoldestLogIDread-onlycurrentThe index of the oldest data in the buffer for this PDU.
1.3.6.1.4.1.13742.6.6.1.1.1.3ColumnnewestLogIDread-onlycurrentThe index of the newest data in the buffer for this PDU.
1.3.6.1.4.1.13742.6.6.1.2TablelogTimeStampTablenot-accessiblecurrentA list of entries containing the timestamps of the entries in the log.
1.3.6.1.4.1.13742.6.6.1.2.1RowlogTimeStampEntrynot-accessiblecurrentAn entry containing the timestamp for log entries.
1.3.6.1.4.1.13742.6.6.1.2.1.1ColumnlogIndexnot-accessiblecurrentA unique value for each entry in the log. Its value ranges between 1 and the value of logSize.
1.3.6.1.4.1.13742.6.6.1.2.1.2ColumnlogTimeStampread-onlycurrentThe time when the data was collected. It is measured in seconds since January 1, 1970 (midnight UTC/GMT).
1.3.6.1.4.1.13742.6.6.1.3TableunitSensorLogTablenot-accessiblecurrentA list of unit sensor entries in the log.
1.3.6.1.4.1.13742.6.6.1.3.1RowunitSensorLogEntrynot-accessiblecurrentAn entry containing log objects for a unit sensor.
1.3.6.1.4.1.13742.6.6.1.3.1.2ColumnlogUnitSensorDataAvailableread-onlycurrentIs data available for this sensor during this measurement period?
1.3.6.1.4.1.13742.6.6.1.3.1.3ColumnlogUnitSensorStateread-onlycurrentThe most critical sensor state during this measurement period.
1.3.6.1.4.1.13742.6.6.1.3.1.4ColumnlogUnitSensorAvgValueread-onlycurrentThe average sensor reading for the log period as an unsigned integer. The value of this OID variable should be scaled by unitSensorDecimalDigits. For example, …
1.3.6.1.4.1.13742.6.6.1.3.1.5ColumnlogUnitSensorMaxValueread-onlycurrentThe maximum sensor reading for the log period as an unsigned integer. The value of this OID variable should be scaled by unitSensorDecimalDigits. For example, …
1.3.6.1.4.1.13742.6.6.1.3.1.6ColumnlogUnitSensorMinValueread-onlycurrentThe minimum sensor reading for the log period as an unsigned integer. The value of this OID variable should be scaled by unitSensorDecimalDigits. For example, …
1.3.6.1.4.1.13742.6.6.1.3.1.7ColumnlogUnitSensorSignedAvgValueread-onlycurrentThe average sensor reading for the log period as a signed integer. The value of this OID variable should be scaled by unitSensorDecimalDigits. For example, if …
1.3.6.1.4.1.13742.6.6.1.3.1.8ColumnlogUnitSensorSignedMaxValueread-onlycurrentThe maximum sensor reading for the log period as a signed integer. The value of this OID variable should be scaled by unitSensorDecimalDigits. For example, if …
1.3.6.1.4.1.13742.6.6.1.3.1.9ColumnlogUnitSensorSignedMinValueread-onlycurrentThe minimum sensor reading for the log period as a signed integer. The value of this OID variable should be scaled by unitSensorDecimalDigits. For example, if …
1.3.6.1.4.1.13742.6.6.2NodelogInlet
1.3.6.1.4.1.13742.6.6.2.3TableinletSensorLogTablenot-accessiblecurrentA list of inlet sensor entries in the log.
1.3.6.1.4.1.13742.6.6.2.3.1RowinletSensorLogEntrynot-accessiblecurrentAn entry containing log objects for an inlet sensor.
1.3.6.1.4.1.13742.6.6.2.3.1.2ColumnlogInletSensorDataAvailableread-onlycurrentIs data available for this sensor during this measurement period?
1.3.6.1.4.1.13742.6.6.2.3.1.3ColumnlogInletSensorStateread-onlycurrentThe most critical sensor state during this measurement period.
1.3.6.1.4.1.13742.6.6.2.3.1.4ColumnlogInletSensorAvgValueread-onlycurrentThe average sensor reading for the log period as an unsigned integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example,…
1.3.6.1.4.1.13742.6.6.2.3.1.5ColumnlogInletSensorMaxValueread-onlycurrentThe maximum sensor reading for the log period as an unsigned integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example,…
1.3.6.1.4.1.13742.6.6.2.3.1.6ColumnlogInletSensorMinValueread-onlycurrentThe minimum sensor reading for the log period as an unsigned integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example,…
1.3.6.1.4.1.13742.6.6.2.3.1.7ColumnlogInletSensorSignedAvgValueread-onlycurrentThe average sensor reading for the log period as a signed integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if…
1.3.6.1.4.1.13742.6.6.2.3.1.8ColumnlogInletSensorSignedMaxValueread-onlycurrentThe maximum sensor reading for the log period as a signed integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if…
1.3.6.1.4.1.13742.6.6.2.3.1.9ColumnlogInletSensorSignedMinValueread-onlycurrentThe minimum sensor reading for the log period as a signed integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if…
1.3.6.1.4.1.13742.6.6.2.4TableinletPoleSensorLogTablenot-accessiblecurrentA list of inletPole sensor entries in the log.
1.3.6.1.4.1.13742.6.6.2.4.1RowinletPoleSensorLogEntrynot-accessiblecurrentAn entry containing log objects for an inlet pole sensor.
1.3.6.1.4.1.13742.6.6.2.4.1.2ColumnlogInletPoleSensorDataAvailableread-onlycurrentIs data available for this sensor during this measurement period?
1.3.6.1.4.1.13742.6.6.2.4.1.3ColumnlogInletPoleSensorStateread-onlycurrentThe most critical sensor state during this measurement period.
1.3.6.1.4.1.13742.6.6.2.4.1.4ColumnlogInletPoleSensorAvgValueread-onlycurrentThe average sensor reading for the log period as an unsigned integer. The value of this OID variable should be scaled by inletPoleSensorDecimalDigits. For exam…
1.3.6.1.4.1.13742.6.6.2.4.1.5ColumnlogInletPoleSensorMaxValueread-onlycurrentThe maximum sensor reading for the log period as an unsigned integer. The value of this OID variable should be scaled by inletPoleSensorDecimalDigits. For exam…
1.3.6.1.4.1.13742.6.6.2.4.1.6ColumnlogInletPoleSensorMinValueread-onlycurrentThe minimum sensor reading for the log period as an unsigned integer. The value of this OID variable should be scaled by inletPoleSensorDecimalDigits. For exam…
1.3.6.1.4.1.13742.6.6.2.4.1.7ColumnlogInletPoleSensorSignedAvgValueread-onlycurrentThe average sensor reading for the log period as a signed integer. The value of this OID variable should be scaled by inletPoleSensorDecimalDigits. For example…
1.3.6.1.4.1.13742.6.6.2.4.1.8ColumnlogInletPoleSensorSignedMaxValueread-onlycurrentThe maximum sensor reading for the log period as a signed integer. The value of this OID variable should be scaled by inletPoleSensorDecimalDigits. For example…
1.3.6.1.4.1.13742.6.6.2.4.1.9ColumnlogInletPoleSensorSignedMinValueread-onlycurrentThe minimum sensor reading for the log period as a signed integer. The value of this OID variable should be scaled by inletPoleSensorDecimalDigits. For example…
1.3.6.1.4.1.13742.6.6.3NodelogOverCurrentProtector
1.3.6.1.4.1.13742.6.6.3.3TableoverCurrentProtectorSensorLogTablenot-accessiblecurrentA list of overcurrent protector sensor entries in the log.
1.3.6.1.4.1.13742.6.6.3.3.1RowoverCurrentProtectorSensorLogEntrynot-accessiblecurrentAn entry containing log objects for an overcurrent protector sensor.
1.3.6.1.4.1.13742.6.6.3.3.1.2ColumnlogOverCurrentProtectorSensorDataAvailableread-onlycurrentIs data available for this sensor during this measurement period?
1.3.6.1.4.1.13742.6.6.3.3.1.3ColumnlogOverCurrentProtectorSensorStateread-onlycurrentThe most critical sensor state during this measurement period.
1.3.6.1.4.1.13742.6.6.3.3.1.4ColumnlogOverCurrentProtectorSensorAvgValueread-onlycurrentThe average sensor reading for the log period as an unsigned integer. The value of this OID variable should be scaled by overCurrentProtectorSensorDecimalDigit…
1.3.6.1.4.1.13742.6.6.3.3.1.5ColumnlogOverCurrentProtectorSensorMaxValueread-onlycurrentThe maximum sensor reading for the log period as an unsigned integer. The value of this OID variable should be scaled by overCurrentProtectorSensorDecimalDigit…
1.3.6.1.4.1.13742.6.6.3.3.1.6ColumnlogOverCurrentProtectorSensorMinValueread-onlycurrentThe minimum sensor reading for the log period as an unsigned integer. The value of this OID variable should be scaled by overCurrentProtectorSensorDecimalDigit…
1.3.6.1.4.1.13742.6.6.3.3.1.7ColumnlogOverCurrentProtectorSensorSignedAvgValueread-onlycurrentThe average sensor reading for the log period as a signed integer. The value of this OID variable should be scaled by overCurrentProtectorSensorDecimalDigits. …
1.3.6.1.4.1.13742.6.6.3.3.1.8ColumnlogOverCurrentProtectorSensorSignedMaxValueread-onlycurrentThe maximum sensor reading for the log period as a signed integer. The value of this OID variable should be scaled by overCurrentProtectorSensorDecimalDigits. …
1.3.6.1.4.1.13742.6.6.3.3.1.9ColumnlogOverCurrentProtectorSensorSignedMinValueread-onlycurrentThe minimum sensor reading for the log period as a signed integer. The value of this OID variable should be scaled by overCurrentProtectorSensorDecimalDigits. …
1.3.6.1.4.1.13742.6.6.4NodelogOutlet
1.3.6.1.4.1.13742.6.6.4.3TableoutletSensorLogTablenot-accessiblecurrentA list of outlet sensor entries in the log.
1.3.6.1.4.1.13742.6.6.4.3.1RowoutletSensorLogEntrynot-accessiblecurrentAn entry containing log objects for an outlet sensor.
1.3.6.1.4.1.13742.6.6.4.3.1.2ColumnlogOutletSensorDataAvailableread-onlycurrentIs data available for this sensor during this measurement period?
1.3.6.1.4.1.13742.6.6.4.3.1.3ColumnlogOutletSensorStateread-onlycurrentThe most critical sensor state during this measurement period.
1.3.6.1.4.1.13742.6.6.4.3.1.4ColumnlogOutletSensorAvgValueread-onlycurrentThe average sensor reading for the log period as an unsigned integer. The value of this OID variable should be scaled by outletSensorDecimalDigits. For example…
1.3.6.1.4.1.13742.6.6.4.3.1.5ColumnlogOutletSensorMaxValueread-onlycurrentThe maximum sensor reading for the log period as an unsigned integer. The value of this OID variable should be scaled by outletSensorDecimalDigits. For example…
1.3.6.1.4.1.13742.6.6.4.3.1.6ColumnlogOutletSensorMinValueread-onlycurrentThe minimum sensor reading for the log period as an unsigned integer. The value of this OID variable should be scaled by outletSensorDecimalDigits. For example…
1.3.6.1.4.1.13742.6.6.4.3.1.7ColumnlogOutletSensorSignedAvgValueread-onlycurrentThe average sensor reading for the log period as a signed integer. The value of this OID variable should be scaled by outletSensorDecimalDigits. For example, i…
1.3.6.1.4.1.13742.6.6.4.3.1.8ColumnlogOutletSensorSignedMaxValueread-onlycurrentThe maximum sensor reading for the log period as a signed integer. The value of this OID variable should be scaled by outletSensorDecimalDigits. For example, i…
1.3.6.1.4.1.13742.6.6.4.3.1.9ColumnlogOutletSensorSignedMinValueread-onlycurrentThe minimum sensor reading for the log period as a signed integer. The value of this OID variable should be scaled by outletSensorDecimalDigits. For example, i…
1.3.6.1.4.1.13742.6.6.4.4TableoutletPoleSensorLogTablenot-accessiblecurrentA list of outlet pole sensor entries in the log.
1.3.6.1.4.1.13742.6.6.4.4.1RowoutletPoleSensorLogEntrynot-accessiblecurrentAn entry containing log objects for an outlet pole sensor.
1.3.6.1.4.1.13742.6.6.4.4.1.2ColumnlogOutletPoleSensorDataAvailableread-onlycurrentIs data available for this sensor during this measurement period?
1.3.6.1.4.1.13742.6.6.4.4.1.3ColumnlogOutletPoleSensorStateread-onlycurrentThe most critical sensor state during this measurement period.
1.3.6.1.4.1.13742.6.6.4.4.1.4ColumnlogOutletPoleSensorAvgValueread-onlycurrentThe average sensor reading for the log period as an unsigned integer. The value of this OID variable should be scaled by outletPoleSensorDecimalDigits. For exa…
1.3.6.1.4.1.13742.6.6.4.4.1.5ColumnlogOutletPoleSensorMaxValueread-onlycurrentThe maximum sensor reading for the log period as an unsigned integer. The value of this OID variable should be scaled by outletPoleSensorDecimalDigits. For exa…
1.3.6.1.4.1.13742.6.6.4.4.1.6ColumnlogOutletPoleSensorMinValueread-onlycurrentThe minimum sensor reading for the log period as an unsigned integer. The value of this OID variable should be scaled by outletPoleSensorDecimalDigits. For exa…
1.3.6.1.4.1.13742.6.6.4.4.1.7ColumnlogOutletPoleSensorSignedAvgValueread-onlycurrentThe average sensor reading for the log period as a signed integer. The value of this OID variable should be scaled by outletPoleSensorDecimalDigits. For exampl…
1.3.6.1.4.1.13742.6.6.4.4.1.8ColumnlogOutletPoleSensorSignedMaxValueread-onlycurrentThe maximum sensor reading for the log period as a signed integer. The value of this OID variable should be scaled by outletPoleSensorDecimalDigits. For exampl…
1.3.6.1.4.1.13742.6.6.4.4.1.9ColumnlogOutletPoleSensorSignedMinValueread-onlycurrentThe minimum sensor reading for the log period as a signed integer. The value of this OID variable should be scaled by outletPoleSensorDecimalDigits. For exampl…
1.3.6.1.4.1.13742.6.6.5NodelogExternalSensor
1.3.6.1.4.1.13742.6.6.5.3TableexternalSensorLogTablenot-accessiblecurrentA list of external sensor entries in the log.
1.3.6.1.4.1.13742.6.6.5.3.1RowexternalSensorLogEntrynot-accessiblecurrentAn entry containing log objects for an external sensor.
1.3.6.1.4.1.13742.6.6.5.3.1.2ColumnlogExternalSensorDataAvailableread-onlycurrentIs data available for this sensor during this measurement period?
1.3.6.1.4.1.13742.6.6.5.3.1.3ColumnlogExternalSensorStateread-onlycurrentThe most critical sensor state during this measurement period.
1.3.6.1.4.1.13742.6.6.5.3.1.4ColumnlogExternalSensorAvgValueread-onlycurrentThe sensor reading average value. The value of this OID variable should be scaled by externalSensorDecimalDigits. For example, if the value is 1 and externalSe…
1.3.6.1.4.1.13742.6.6.5.3.1.5ColumnlogExternalSensorMaxValueread-onlycurrentThe sensor reading maximum value. The value of this OID variable should be scaled by externalSensorDecimalDigits. For example, if the value is 1 and externalSe…
1.3.6.1.4.1.13742.6.6.5.3.1.6ColumnlogExternalSensorMinValueread-onlycurrentThe sensor reading minimum value. The value of this OID variable should be scaled by externalSensorDecimalDigits. For example, if the value is 1 and externalSe…
1.3.6.1.4.1.13742.6.6.6NodelogWire
1.3.6.1.4.1.13742.6.6.6.3TablewireSensorLogTablenot-accessibledeprecatedA list of wire sensor entries in the log. Note: This feature is no longer used, the table is always empty.
1.3.6.1.4.1.13742.6.6.6.3.1RowwireSensorLogEntrynot-accessibledeprecatedAn entry containing log objects for a wire sensor.
1.3.6.1.4.1.13742.6.6.6.3.1.2ColumnlogWireSensorDataAvailableread-onlydeprecatedIs data available for this sensor during this measurement period?
1.3.6.1.4.1.13742.6.6.6.3.1.3ColumnlogWireSensorStateread-onlydeprecatedThe most critical sensor state during this measurement period.
1.3.6.1.4.1.13742.6.6.6.3.1.4ColumnlogWireSensorAvgValueread-onlydeprecatedThe sensor reading average value. The value of this OID variable should be scaled by wireSensorDecimalDigits. For example, if the value is 1 and wireSensorDeci…
1.3.6.1.4.1.13742.6.6.6.3.1.5ColumnlogWireSensorMaxValueread-onlydeprecatedThe sensor reading maximum value. The value of this OID variable should be scaled by wireSensorDecimalDigits. For example, if the value is 1 and wireSensorDeci…
1.3.6.1.4.1.13742.6.6.6.3.1.6ColumnlogWireSensorMinValueread-onlydeprecatedThe sensor reading minimum value. The value of this OID variable should be scaled by wireSensorDecimalDigits. For example, if the value is 1 and wireSensorDeci…
1.3.6.1.4.1.13742.6.6.7NodelogTransferSwitch
1.3.6.1.4.1.13742.6.6.7.3TabletransferSwitchSensorLogTablenot-accessiblecurrentA list of transfer switch sensor entries in the log.
1.3.6.1.4.1.13742.6.6.7.3.1RowtransferSwitchSensorLogEntrynot-accessiblecurrentAn entry containing log objects for a transfer switch sensor.
1.3.6.1.4.1.13742.6.6.7.3.1.2ColumnlogTransferSwitchSensorDataAvailableread-onlycurrentIs data available for this sensor during this measurement period?
1.3.6.1.4.1.13742.6.6.7.3.1.3ColumnlogTransferSwitchSensorStateread-onlycurrentThe most critical sensor state during this measurement period.
1.3.6.1.4.1.13742.6.6.7.3.1.4ColumnlogTransferSwitchSensorAvgValueread-onlycurrentThe average sensor reading for the log period as an unsigned integer. The value of this OID variable should be scaled by transferSwitchSensorDecimalDigits. For…
1.3.6.1.4.1.13742.6.6.7.3.1.5ColumnlogTransferSwitchSensorMaxValueread-onlycurrentThe maximum sensor reading for the log period as an unsigned integer. The value of this OID variable should be scaled by transferSwitchSensorDecimalDigits. For…
1.3.6.1.4.1.13742.6.6.7.3.1.6ColumnlogTransferSwitchSensorMinValueread-onlycurrentThe minimum sensor reading for the log period as an unsigned integer. The value of this OID variable should be scaled by transferSwitchSensorDecimalDigits. For…
1.3.6.1.4.1.13742.6.6.7.3.1.7ColumnlogTransferSwitchSensorSignedAvgValueread-onlycurrentThe average sensor reading for the log period as a signed integer. The value of this OID variable should be scaled by transferSwitchSensorDecimalDigits. For ex…
1.3.6.1.4.1.13742.6.6.7.3.1.8ColumnlogTransferSwitchSensorSignedMaxValueread-onlycurrentThe maximum sensor reading for the log period as a signed integer. The value of this OID variable should be scaled by transferSwitchSensorDecimalDigits. For ex…
1.3.6.1.4.1.13742.6.6.7.3.1.9ColumnlogTransferSwitchSensorSignedMinValueread-onlycurrentThe minimum sensor reading for the log period as a signed integer. The value of this OID variable should be scaled by transferSwitchSensorDecimalDigits. For ex…
1.3.6.1.4.1.13742.6.6.8NodelogCircuit
1.3.6.1.4.1.13742.6.6.8.3TablecircuitSensorLogTablenot-accessiblecurrentA list of circuit sensor entries in the log.
1.3.6.1.4.1.13742.6.6.8.3.1RowcircuitSensorLogEntrynot-accessiblecurrentAn entry containing log objects for a circuit sensor.
1.3.6.1.4.1.13742.6.6.8.3.1.2ColumnlogCircuitSensorDataAvailableread-onlycurrentIs data available for this sensor during this measurement period?
1.3.6.1.4.1.13742.6.6.8.3.1.3ColumnlogCircuitSensorStateread-onlycurrentThe most critical sensor state during this measurement period.
1.3.6.1.4.1.13742.6.6.8.3.1.4ColumnlogCircuitSensorAvgValueread-onlycurrentThe average sensor reading for the log period as an unsigned integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example,…
1.3.6.1.4.1.13742.6.6.8.3.1.5ColumnlogCircuitSensorMaxValueread-onlycurrentThe maximum sensor reading for the log period as an unsigned integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example,…
1.3.6.1.4.1.13742.6.6.8.3.1.6ColumnlogCircuitSensorMinValueread-onlycurrentThe minimum sensor reading for the log period as an unsigned integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example,…
1.3.6.1.4.1.13742.6.6.8.3.1.7ColumnlogCircuitSensorSignedAvgValueread-onlycurrentThe average sensor reading for the log period as a signed integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if…
1.3.6.1.4.1.13742.6.6.8.3.1.8ColumnlogCircuitSensorSignedMaxValueread-onlycurrentThe maximum sensor reading for the log period as a signed integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if…
1.3.6.1.4.1.13742.6.6.8.3.1.9ColumnlogCircuitSensorSignedMinValueread-onlycurrentThe minimum sensor reading for the log period as a signed integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if…
1.3.6.1.4.1.13742.6.6.8.5TablecircuitPoleSensorLogTablenot-accessiblecurrentA list of circuit pole sensor entries in the log.
1.3.6.1.4.1.13742.6.6.8.5.1RowcircuitPoleSensorLogEntrynot-accessiblecurrentAn entry containing log objects for a circuit pole sensor.
1.3.6.1.4.1.13742.6.6.8.5.1.2ColumnlogCircuitPoleSensorDataAvailableread-onlycurrentIs data available for this sensor during this measurement period?
1.3.6.1.4.1.13742.6.6.8.5.1.3ColumnlogCircuitPoleSensorStateread-onlycurrentThe most critical sensor state during this measurement period.
1.3.6.1.4.1.13742.6.6.8.5.1.4ColumnlogCircuitPoleSensorAvgValueread-onlycurrentThe average sensor reading for the log period as an unsigned integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example,…
1.3.6.1.4.1.13742.6.6.8.5.1.5ColumnlogCircuitPoleSensorMaxValueread-onlycurrentThe maximum sensor reading for the log period as an unsigned integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example,…
1.3.6.1.4.1.13742.6.6.8.5.1.6ColumnlogCircuitPoleSensorMinValueread-onlycurrentThe minimum sensor reading for the log period as an unsigned integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example,…
1.3.6.1.4.1.13742.6.6.8.5.1.7ColumnlogCircuitPoleSensorSignedAvgValueread-onlycurrentThe average sensor reading for the log period as a signed integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if…
1.3.6.1.4.1.13742.6.6.8.5.1.8ColumnlogCircuitPoleSensorSignedMaxValueread-onlycurrentThe maximum sensor reading for the log period as a signed integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if…
1.3.6.1.4.1.13742.6.6.8.5.1.9ColumnlogCircuitPoleSensorSignedMinValueread-onlycurrentThe minimum sensor reading for the log period as a signed integer. The value of this OID variable should be scaled by inletSensorDecimalDigits. For example, if…
1.3.6.1.4.1.13742.6.9Nodeconformance
1.3.6.1.4.1.13742.6.9.1Nodecompliances
1.3.6.1.4.1.13742.6.9.1.1CompliancecomplianceRev1deprecatedThe requirements for conformance to the PDU2-MIB.
1.3.6.1.4.1.13742.6.9.1.2CompliancecomplianceRev2read-onlycurrentThe requirements for conformance to the PDU2-MIB.
1.3.6.1.4.1.13742.6.9.2Nodegroups
1.3.6.1.4.1.13742.6.9.2.1GroupconfigGroupcurrentA collection of objects representing configuration data.
1.3.6.1.4.1.13742.6.9.2.2GrouplogGroupcurrentA collection of objects providing logging (history of readings) capabilities about the PDU.
1.3.6.1.4.1.13742.6.9.2.3GroupmeasurementsGroupcurrentA collection of objects providing measurements (most recent data) capabilities. about the PDU.
1.3.6.1.4.1.13742.6.9.2.4GroupcontrolGroupcurrentA collection of objects providing the ability to control various components of a PDU.
1.3.6.1.4.1.13742.6.9.2.5GrouptrapInformationGroupcurrentA collection of objects providing information in the traps.
1.3.6.1.4.1.13742.6.9.2.9GrouptrapsGroupcurrentA collection of traps.
1.3.6.1.4.1.13742.6.9.2.10GroupreliabilityGroupcurrentA collection of objects providing reliability data.
1.3.6.1.4.1.13742.6.9.2.12GroupipAddressGroupdeprecatedA collection of objects representing configuration data.
1.3.6.1.4.1.13742.6.9.2.13GroupoldConfigGroupdeprecatedA collection of objects representing old (deprecated) configuration data.
1.3.6.1.4.1.13742.6.9.2.14GroupoldLogGroupdeprecatedA collection of objects representing old (deprecated) logging data.
1.3.6.1.4.1.13742.6.9.2.15GroupoldMeasurementsGroupdeprecatedA collection of objects representing old (deprecated) measurement data.
1.3.6.1.4.1.13742.6.9.2.16GroupoldTrapsGroupdeprecatedA collection of objects representing old (deprecated) traps.
1.3.6.1.4.1.13742.6.9.2.20GroupobsoleteObjectsGroupobsoleteA collection of obsolete objects.
1.3.6.1.4.1.13742.6.10Nodereliability
1.3.6.1.4.1.13742.6.10.1NodereliabilityData
1.3.6.1.4.1.13742.6.10.1.1ScalarreliabilityDataTableSequenceNumberread-onlycurrentThe sequence number for updates to the reliability data table
1.3.6.1.4.1.13742.6.10.1.2TablereliabilityDataTablenot-accessiblecurrentA list of PDU reliability data entries.
1.3.6.1.4.1.13742.6.10.1.2.1RowreliabilityDataEntrynot-accessiblecurrentAn entry containing reliability data for a particular PDU.
1.3.6.1.4.1.13742.6.10.1.2.1.1ColumnreliabilityIndexnot-accessiblecurrentIndex of the entry in the reliability data table.
1.3.6.1.4.1.13742.6.10.1.2.1.2ColumnreliabilityIdread-onlycurrentUnique ID of the entry. POH Power on hours. CB.<label>.TRIPCNT Trip count of circuit breaker with label <label>. CTRL.<serial>.<addr>.MASTER.CSUMERRLASTHOUR Nu…
1.3.6.1.4.1.13742.6.10.1.2.1.3ColumnreliabilityDataValueread-onlycurrentThe normalized value
1.3.6.1.4.1.13742.6.10.1.2.1.4ColumnreliabilityDataMaxPossibleread-onlycurrentThe maximum possible normalized value
1.3.6.1.4.1.13742.6.10.1.2.1.5ColumnreliabilityDataWorstValueread-onlycurrentThe worst normalized value seen so far
1.3.6.1.4.1.13742.6.10.1.2.1.6ColumnreliabilityDataThresholdread-onlycurrentThe normalized Threshold value
1.3.6.1.4.1.13742.6.10.1.2.1.7ColumnreliabilityDataRawUpperBytesread-onlycurrentThe upper 4 bytes of the raw (not normalized) data. reliabilityDataRawUpperBytes and reliabilityDataRawLowerBytes should be combined and interpreted as a signe…
1.3.6.1.4.1.13742.6.10.1.2.1.8ColumnreliabilityDataRawLowerBytesread-onlycurrentThe lower 4 bytes of the raw (not normalized) data. reliabilityDataRawUpperBytes and reliabilityDataRawLowerBytes should be combined and interpreted as a signe…
1.3.6.1.4.1.13742.6.10.1.2.1.9ColumnreliabilityDataFlagsread-onlycurrentFlags
1.3.6.1.4.1.13742.6.10.2NodereliabilityErrorLog
1.3.6.1.4.1.13742.6.10.2.2TablereliabilityErrorLogTablenot-accessiblecurrentA list of PDU reliability error log entries.
1.3.6.1.4.1.13742.6.10.2.2.1RowreliabilityErrorLogEntrynot-accessiblecurrentAn entry containing reliability error log data for a particular PDU.
1.3.6.1.4.1.13742.6.10.2.2.1.1ColumnreliabilityErrorLogIndexnot-accessiblecurrentIndex of the entry in the reliability error log table.
1.3.6.1.4.1.13742.6.10.2.2.1.2ColumnreliabilityErrorLogIdread-onlycurrentUnique ID of the entry. POH Power on hours. CB.<label>.TRIPCNT Trip count of circuit breaker with label <label>. CTRL.<serial>.<addr>.MASTER.CSUMERRLASTHOUR Nu…
1.3.6.1.4.1.13742.6.10.2.2.1.3ColumnreliabilityErrorLogValueread-onlycurrentThe normalized value
1.3.6.1.4.1.13742.6.10.2.2.1.6ColumnreliabilityErrorLogThresholdread-onlycurrentThe normalized threshold value
1.3.6.1.4.1.13742.6.10.2.2.1.7ColumnreliabilityErrorLogRawUpperBytesread-onlycurrentThe upper 4 bytes of the raw (not normalized) data. reliabilityErrorLogRawUpperBytes and reliabilityErrorLogRawLowerBytes should be combined and interpreted as…
1.3.6.1.4.1.13742.6.10.2.2.1.8ColumnreliabilityErrorLogRawLowerBytesread-onlycurrentThe lower 4 bytes of the raw (not normalized) data. reliabilityErrorLogRawUpperBytes and reliabilityErrorLogRawLowerBytes should be combined and interpreted as…
1.3.6.1.4.1.13742.6.10.2.2.1.9ColumnreliabilityErrorLogPOHread-onlycurrentThe time of occurrence of the event measured from the last time the PDU was powered on
1.3.6.1.4.1.13742.6.10.2.2.1.10ColumnreliabilityErrorLogTimeread-onlycurrentThe UTC time of occurrence of the event
Type Definitions
NameSyntaxStatusDescription
AddressSourceEnumerationINTEGER { static(1), dhcp(2), dhcpv6(3) }currentHow was the address obtained?
BoardTypeEnumerationINTEGER { mainController(1), inletController(2), outletController(3), meteringController(4) }currentThe types of boards.
CircuitTypeEnumerationINTEGER { onePhaseLL(1), onePhaseLN(2), onePhaseLLN(3), threePhase(4) }currentThe panel circuit types.
DaisychainMemberTypeEnumerationINTEGER { standalone(0), master(1), slave(2) }currentThe daisy chain member type.
DeviceCascadeTypeEnumerationINTEGER { bridging(0), portForwarding(1), none(2) }currentThe type of configured cascading on this device.
DeviceIdentificationParameterEnumerationINTEGER { pduName(0), sysContact(1), sysName(2), sysLocation(3) }currentThe configurable parameters.
ExternalSensorsZCoordinateUnitsEnumerationINTEGER { rackUnits(0), text(1) }currentThe units of the external sensor Z coordinate. rackUnits implies that the Z coordinate for all external sensors is in rack units (U) text implies that the Z coordinate for all external sensors is a text string (label)
GlobalOutletStateOnStartupEnumerationINTEGER { off(0), on(1), lastKnownState(2) }currentThe global outlet state on device start up; can be overridden per outlet.
HundredthsOfAPercentageUnsigned32 (0..10000)currentData type for reporting values in hundredths of percentage, i.e. 0.01 %.
LineEnumerationINTEGER { lineL1(1), lineL2(2), lineL3(3), lineNeutral(4) }currentThe Lines: L1, L2, L3, N.
NetworkInterfaceTypeEnumerationINTEGER { wired(0), wireless(1) }currentThe type of network interface.
OutletStateOnStartupEnumerationINTEGER { off(0), on(1), lastKnownState(2), globalOutletStateOnStartup(3) }currentThe outlet state on device start up; this overrides the global value.
OutletSwitchingOperationsEnumerationINTEGER { off(0), on(1), cycle(2) }currentThe switching operations on an outlet.
OverCurrentProtectorTypeEnumerationINTEGER { ocpBREAKER1POLE(1), ocpBREAKER2POLE(2), ocpBREAKER3POLE(3), ocpFUSE(4), ocpFUSEPAIR(5), ocpRCBO2POLE(6), ocpRCBO3POLE(7), ocpRCBO4POLE(8) }currentThe types of overcurrent protectors.
PanelLayoutEnumerationINTEGER { invalid(-1), oneColumn(1), twoColumns(2) }currentThe panel circuit position layout.
PanelNumberingEnumerationINTEGER { invalid(-1), oddEven(1), sequential(2) }currentThe panel circuit position numbering scheme.
PeripheralDeviceFirmwareUpdateStateEnumerationINTEGER { started(1), successful(2), failed(3) }currentThe state of a peripheral device firmware update.
PhaseEnumerationINTEGER { phaseA(1), phaseB(2), phaseC(3), neutral(4), earth(5) }currentThe power phase.
PlugTypeEnumerationINTEGER { plugOTHER(-1), plugNONE(0), plug56P320(1), plug56P520(2), plug56P532(3), plugCS8365C(4), plugIEC320C14(5), plugIEC320C20(6), plugIEC603093WIRE250V16A(7), plugIEC603093WIRE250V20A(8), plugIEC603093WIRE250V30A(9), plugIEC603093WIRE250V32A(10), plugIEC603093WIRE250V60A(11), plugIEC603093WIRE250V63A(12), plugIEC603093WIRE250V100A(13), plugIEC603093WIRE250V125A(14), plugIEC603094WIRE250V20A(15), plugIEC603094WIRE250V30A(16), plugIEC603094WIRE250V60A(17), plugIEC603094WIRE250V100A(18), plugIEC603095WIRE208V20A(23), plugIEC603095WIRE208V30A(24), plugIEC603095WIRE208V60A(25), plugIEC603095WIRE208V100A(26), plugIEC603095WIRE415V16A(27), plugIEC603095WIRE415V32A(28), plugIEC603095WIRE415V63A(29), plugIEC603095WIRE415V125A(30), plugIEC603095WIRE480V20A(31), plugIEC603095WIRE480V30A(32), plugIEC603095WIRE480V60A(33), plugIEC603095WIRE480V100A(34), plugNEMA515P(35), plugNEMAL515P(36), plugNEMA520P(37), plugNEMAL520P(38), plugNEMAL530P(39), plugNEMAL615P(40), plugNEMAL620P(41), plugNEMAL630P(42), plugNEMAL1520P(43), plugNEMAL1530P(44), plugNEMAL2120P(45), plugNEMAL2130P(46), plugNEMAL2230P(47), plug56P320F(48), plug56PA320(49) }currentThe types of inlet plug.
PowerMeterTypeEnumerationINTEGER { singlePhase(1), splitPhase(2), threePhase(3) }currentThe power meter types
ProductTypeEnumerationINTEGER { rackPdu(0), bcm(1), transferSwitch(2), powerMeter(3) }currentThe product types.
ReceptacleTypeEnumerationINTEGER { receptacleOTHER(-1), receptacleNONE(0), receptacleBS1363(1), receptacle56P532(3), receptacleCS8364C(4), receptacleIEC320C13(5), receptacleIEC320C19(6), receptacleIEC603093WIRE250V16A(7), receptacleIEC603093WIRE250V20A(8), receptacleIEC603093WIRE250V30A(9), receptacleIEC603093WIRE250V32A(10), receptacleIEC603093WIRE250V60A(11), receptacleIEC603093WIRE250V63A(12), receptacleIEC603093WIRE250V100A(13), receptacleIEC603093WIRE250V125A(14), receptacleIEC603094WIRE250V20A(15), receptacleIEC603094WIRE250V30A(16), receptacleIEC603094WIRE250V60A(17), receptacleIEC603094WIRE250V100A(18), receptacleIEC603095WIRE208V20A(23), receptacleIEC603095WIRE208V30A(24), receptacleIEC603095WIRE208V60A(25), receptacleIEC603095WIRE208V100A(26), receptacleIEC603095WIRE415V16A(27), receptacleIEC603095WIRE415V32A(28), receptacleIEC603095WIRE415V63A(29), receptacleIEC603095WIRE415V125A(30), receptacleIEC603095WIRE480V20A(31), receptacleIEC603095WIRE480V30A(32), receptacleIEC603095WIRE480V60A(33), receptacleIEC603095WIRE480V100A(34), receptacleNEMA515R(35), receptacleNEMAL515R(36), receptacleNEMA520R(37), receptacleNEMAL520R(38), receptacleNEMAL530R(39), receptacleNEMAL615R(40), receptacleNEMAL620R(41), receptacleNEMAL630R(42), receptacleNEMAL1520R(43), receptacleNEMAL1530R(44), receptacleNEMAL2120RP(45), receptacleNEMAL2130R(46), receptacleSCHUKOTYPEE(47), receptacleSCHUKOTYPEF(48) }currentThe types of outlet receptacle.
RelayPowerLossBehaviorEnumerationINTEGER { nonLatching(0), latching(1) }currentThe type of relay behavior on power loss.
SensorStateEnumerationINTEGER { unavailable(-1), open(0), closed(1), belowLowerCritical(2), belowLowerWarning(3), normal(4), aboveUpperWarning(5), aboveUpperCritical(6), on(7), off(8), detected(9), notDetected(10), alarmed(11), ok(12), fail(14), yes(15), no(16), standby(17), one(18), two(19), inSync(20), outOfSync(21), i1OpenFault(22), i1ShortFault(23), i2OpenFault(24), i2ShortFault(25), fault(26), warning(27), critical(28), selfTest(29), nonRedundant(30) }currentThe states a sensor can be in.
SensorTypeEnumerationINTEGER { rmsCurrent(1), peakCurrent(2), unbalancedCurrent(3), rmsVoltage(4), activePower(5), apparentPower(6), powerFactor(7), activeEnergy(8), apparentEnergy(9), temperature(10), humidity(11), airFlow(12), airPressure(13), onOff(14), trip(15), vibration(16), waterDetection(17), smokeDetection(18), binary(19), contact(20), fanSpeed(21), surgeProtectorStatus(22), frequency(23), phaseAngle(24), rmsVoltageLN(25), residualCurrent(26), rcmState(27), absoluteHumidity(28), reactivePower(29), other(30), none(31), powerQuality(32), overloadStatus(33), overheatStatus(34), displacementPowerFactor(35), fanStatus(37), inletPhaseSyncAngle(38), inletPhaseSync(39), operatingState(40), activeInlet(41), illuminance(42), doorContact(43), tamperDetection(44), motionDetection(45), i1smpsStatus(46), i2smpsStatus(47), switchStatus(48), doorLockState(49), doorHandleLock(50) }currentThe types a sensor can be.
SensorUnitsEnumerationINTEGER { none(-1), other(0), volt(1), amp(2), watt(3), voltamp(4), wattHour(5), voltampHour(6), degreeC(7), hertz(8), percent(9), meterpersec(10), pascal(11), psi(12), g(13), degreeF(14), feet(15), inches(16), cm(17), meters(18), rpm(19), degrees(20), lux(21), grampercubicmeter(22), var(23) }currentThe sensor units.
TransferSwitchTransferReasonEnumerationINTEGER { unknown(0), startup(1), manualTransfer(2), automaticReTransfer(3), powerFailure(4), powerQuality(5), overloadAlarm(6), overheatAlarm(7), internalFailure(8) }currentTransfer Switch Transfer Reason
URLOCTET STRING (SIZE (0..255))currentA Uniform Resource Locator (URL), as defined in RFC1738.