MIB Viewer

PM-MIB

293 objects
This module defines the Avocent MIB extensions to PM-PDU products.
OIDNameAccessStatusDescription
1.3.6.1.4.1.10418.17IdentitypmThis module defines the Avocent MIB extensions to PM-PDU products.
1.3.6.1.4.1.10418.17.1NodepmProducts
1.3.6.1.4.1.10418.17.1.1Nodepm1024
1.3.6.1.4.1.10418.17.1.2Nodepm2003
1.3.6.1.4.1.10418.17.1.3Nodepm2006
1.3.6.1.4.1.10418.17.1.4Nodepm2024
1.3.6.1.4.1.10418.17.1.5Nodepm3003
1.3.6.1.4.1.10418.17.1.6Nodepm3006
1.3.6.1.4.1.10418.17.1.7Nodepm3024
1.3.6.1.4.1.10418.17.1.8Nodepm1010
1.3.6.1.4.1.10418.17.1.9Nodepm2010
1.3.6.1.4.1.10418.17.1.10Nodepm3010
1.3.6.1.4.1.10418.17.1.11Nodepm1020
1.3.6.1.4.1.10418.17.1.12Nodepm2020
1.3.6.1.4.1.10418.17.1.13Nodepm3020
1.3.6.1.4.1.10418.17.2NodepmManagement
1.3.6.1.4.1.10418.17.2.1NodepmAppliance
1.3.6.1.4.1.10418.17.2.1.1ScalarpmHostNameread-onlycurrentThe appliance name
1.3.6.1.4.1.10418.17.2.1.2ScalarpmProductModelread-onlycurrentThe appliance product model
1.3.6.1.4.1.10418.17.2.1.3ScalarpmPartNumberread-onlycurrentThe part number of this appliance as shown on the label attached or imprinted on the appliance.
1.3.6.1.4.1.10418.17.2.1.4ScalarpmSerialNumberread-onlycurrentThe serial number of this appliance as shown on the label attached or imprinted on the appliance.
1.3.6.1.4.1.10418.17.2.1.5ScalarpmEIDNumberread-onlycurrentThe electronic ID number (EID) of this appliance as shown on the label attached or imprinted on the appliance.
1.3.6.1.4.1.10418.17.2.1.6ScalarpmBootcodeVersionread-onlycurrentThe version of the bootcode of this appliance.
1.3.6.1.4.1.10418.17.2.1.7ScalarpmFirmwareVersionread-onlycurrentThe version of the firmware of this appliance.
1.3.6.1.4.1.10418.17.2.1.9ScalarpmRebootread-writecurrentA set value of reboot(2) will reboot the appliance. noAction(1) = always returned in a GET. Does nothing if SET. reboot(2) = when SET the appliance immediately…
1.3.6.1.4.1.10418.17.2.2NodepmSessions
1.3.6.1.4.1.10418.17.2.2.1ScalarpmActiveSessionsNumberOfSessionread-onlycurrentNumber of active sessions.
1.3.6.1.4.1.10418.17.2.2.2TablepmActiveSessionsTablenot-accessiblecurrentThis table contains the list of active sessions.
1.3.6.1.4.1.10418.17.2.2.2.1RowpmActiveSessionsTableEntrynot-accessiblecurrenteach entry has the information about the active session
1.3.6.1.4.1.10418.17.2.2.2.1.1ColumnpmActiveSessionsTableIndexread-onlycurrentA unique index representing an entry in this table.
1.3.6.1.4.1.10418.17.2.2.2.1.2ColumnpmActiveSessionsTableUserread-onlycurrentThe name of the user that opens this session.
1.3.6.1.4.1.10418.17.2.2.2.1.3ColumnpmActiveSessionsTableGroupread-onlycurrentThe name of the group that the user belongs to.
1.3.6.1.4.1.10418.17.2.2.2.1.4ColumnpmActiveSessionsTableTyperead-onlycurrentThe session type.
1.3.6.1.4.1.10418.17.2.2.2.1.5ColumnpmActiveSessionsTableConnectionread-onlycurrentConnection type.
1.3.6.1.4.1.10418.17.2.2.2.1.6ColumnpmActiveSessionsTableSessionTimeread-onlycurrentTime of the session
1.3.6.1.4.1.10418.17.2.2.2.1.7ColumnpmActiveSessionsTableFromread-onlycurrentThe source IP address of the session.
1.3.6.1.4.1.10418.17.2.2.2.1.8ColumnpmActiveSessionsTableKillread-writecurrentA set value of killSession(2) will kill the session. noAction(1) = always returned in a GET. Does nothing if SET. killSession(2)= when SET the appliance immedi…
1.3.6.1.4.1.10418.17.2.5NodepmPowerMgmt
1.3.6.1.4.1.10418.17.2.5.1ScalarpmPowerMgmtNumSerialPortsread-onlycurrentThe number of Serial Ports that has PDU connected on the appliance.
1.3.6.1.4.1.10418.17.2.5.2TablepmPowerMgmtSerialTablenot-accessiblecurrentInformation about each serial port thas has PDU connect.
1.3.6.1.4.1.10418.17.2.5.2.1RowpmPowerMgmtSerialTableEntrynot-accessiblecurrentInformation about each serial port thas has PDU connect.
1.3.6.1.4.1.10418.17.2.5.2.1.1ColumnpmPowerMgmtSerialTableIndexread-onlycurrentThe index of the register.
1.3.6.1.4.1.10418.17.2.5.2.1.2ColumnpmPowerMgmtSerialTablePortNumberread-onlycurrentThe number of the serial port when the PDU is connected.
1.3.6.1.4.1.10418.17.2.5.2.1.3ColumnpmPowerMgmtSerialTableDeviceNameread-onlycurrentThe device name of this serial port.
1.3.6.1.4.1.10418.17.2.5.2.1.4ColumnpmPowerMgmtSerialTableNumberPDUsread-onlycurrentTotal number of units connected in this serial port.
1.3.6.1.4.1.10418.17.2.5.2.1.10ColumnpmPowerMgmtSerialTableBuzzerread-writecurrentset/get buzzer(s) on or off for the chain. Returns 0 if not supported.
1.3.6.1.4.1.10418.17.2.5.2.1.11ColumnpmPowerMgmtSerialTableSyslogread-writecurrentset/get syslog on or off for the chain. Returns 0 if not supported.
1.3.6.1.4.1.10418.17.2.5.2.1.12ColumnpmPowerMgmtSerialTableOverCurrentread-writecurrentset/get over current proctection on or off for the chain. Returns 0 if not supported.
1.3.6.1.4.1.10418.17.2.5.2.1.13ColumnpmPowerMgmtSerialTableCycleIntervalread-writecurrentset/get cycle interval for the chain in whole seconds. Returns 0 if not supported.
1.3.6.1.4.1.10418.17.2.5.2.1.14ColumnpmPowerMgmtSerialTablePollRateread-writecurrentset/get the poll rate for the chain in whole seconds. Returns 0 if not supported.
1.3.6.1.4.1.10418.17.2.5.2.1.15ColumnpmPowerMgmtSerialTablePassWordread-writecurrentset the global password for admin user
1.3.6.1.4.1.10418.17.2.5.2.1.20ColumnpmPowerMgmtSerialTableSaveread-writecurrentnoAction(1) = always returned in a GET. Does nothing if SET. save(2) = when SET the save command is sent to PDU.
1.3.6.1.4.1.10418.17.2.5.2.1.21ColumnpmPowerMgmtSerialTableRestoreread-writecurrentnoAction(1) = always returned in a GET. Does nothing if SET. restore(2) = when SET the restore command is sent to PDU.
1.3.6.1.4.1.10418.17.2.5.3TablepmPowerMgmtPDUTablenot-accessiblecurrentThis table contains the list of detected PDUs.
1.3.6.1.4.1.10418.17.2.5.3.1RowpmPowerMgmtPDUTableEntrynot-accessiblecurrenteach entry has the information about the PDU.
1.3.6.1.4.1.10418.17.2.5.3.1.1ColumnpmPowerMgmtPDUTablePortNumberread-onlycurrentNumber of serial port when the PDU is connected.
1.3.6.1.4.1.10418.17.2.5.3.1.2ColumnpmPowerMgmtPDUTablePduIndexread-onlycurrentA PDU position in the chain.
1.3.6.1.4.1.10418.17.2.5.3.1.3ColumnpmPowerMgmtPDUTablePduIdread-writecurrentPDU identification.
1.3.6.1.4.1.10418.17.2.5.3.1.4ColumnpmPowerMgmtPDUTablePortNameread-onlycurrentName of serial port when the PDU is connected.
1.3.6.1.4.1.10418.17.2.5.3.1.5ColumnpmPowerMgmtPDUTableModelread-onlycurrentModel of the PDU. Returns N/A if not applicable.
1.3.6.1.4.1.10418.17.2.5.3.1.6ColumnpmPowerMgmtPDUTableVendorread-onlycurrentVendor of the PDU. Returns N/A if not applicable.
1.3.6.1.4.1.10418.17.2.5.3.1.7ColumnpmPowerMgmtPDUTableFirmwareVersionread-onlycurrentVersion of the PDU firmware. Returns N/A if not applicable.
1.3.6.1.4.1.10418.17.2.5.3.1.8ColumnpmPowerMgmtPDUTableNumberOfOutletsread-onlycurrentNumber of outlets of the PDU.
1.3.6.1.4.1.10418.17.2.5.3.1.9ColumnpmPowerMgmtPDUTableCurrentNOSread-onlyobsoleteNumber of current sensors in the PDU.
1.3.6.1.4.1.10418.17.2.5.3.1.10ColumnpmPowerMgmtPDUTableCurrent1Valueread-onlyobsoleteCurrent of the sensor 1 in this PDU unit in AMP. The value of this object is the actual current in AMP * 10. You need to translate the readed value (Ex. : valu…
1.3.6.1.4.1.10418.17.2.5.3.1.11ColumnpmPowerMgmtPDUTableCurrent1Maxread-writeobsoleteMaximum current of the sensor 1 in this PDU unit in AMP. When the PDU does not have support for maximum value, the value will be 0. The value of this object is…
1.3.6.1.4.1.10418.17.2.5.3.1.12ColumnpmPowerMgmtPDUTableCurrent2Valueread-onlyobsoleteCurrent of the sensor 2 in this PDU unit in AMP. The value of this object is the actual current in AMP * 10. You need to translate the readed value (Ex. : valu…
1.3.6.1.4.1.10418.17.2.5.3.1.13ColumnpmPowerMgmtPDUTableCurrent2Maxread-writeobsoleteMaximum current of the sensor 2 in this PDU unit in AMP. When the PDU does not have support for maximum value, the value will be 0. The value of this object is…
1.3.6.1.4.1.10418.17.2.5.3.1.14ColumnpmPowerMgmtPDUTableCurrent3Valueread-onlyobsoleteCurrent of the sensor 3 in this PDU unit in AMP. The value of this object is the actual current in AMP * 10. You need to translate the readed value (Ex. : valu…
1.3.6.1.4.1.10418.17.2.5.3.1.15ColumnpmPowerMgmtPDUTableCurrent3Maxread-writeobsoleteMaximum current of the sensor 3 in this PDU unit in AMP. When the PDU does not have support for maximum value, the value will be 0. The value of this object is…
1.3.6.1.4.1.10418.17.2.5.3.1.16ColumnpmPowerMgmtPDUTableTemperatureNOSread-onlyobsoleteNumber of temperature sensors in the PDU.
1.3.6.1.4.1.10418.17.2.5.3.1.17ColumnpmPowerMgmtPDUTableTemperature1Valueread-onlyobsoleteTemperature of this PM unit in Celsius degrees. The value of this object is the actual temperature in degrees C * 10. You need to translate the readed value (E…
1.3.6.1.4.1.10418.17.2.5.3.1.18ColumnpmPowerMgmtPDUTableTemperature1Maxread-writeobsoleteMaximum temperature detected in this PM unit in Celsius degrees. The value will be Zero when the PDU does not have support for maximum value. The value of this…
1.3.6.1.4.1.10418.17.2.5.3.1.19ColumnpmPowerMgmtPDUTableTemperature2Valueread-onlyobsoleteTemperature of this PM unit in Celsius degrees. The value of this object is the actual temperature in degrees C * 10. You need to translate the readed value (E…
1.3.6.1.4.1.10418.17.2.5.3.1.20ColumnpmPowerMgmtPDUTableTemperature2Maxread-writeobsoleteMaximum temperature detected in this PM unit in Celsius degrees. The value will be Zero when the PDU does not have support for maximum value. The value of this…
1.3.6.1.4.1.10418.17.2.5.3.1.21ColumnpmPowerMgmtPDUTableTemperature3Valueread-onlyobsoleteTemperature of this PM unit in Celsius degrees. The value of this object is the actual temperature in degrees C * 10. You need to translate the readed value (E…
1.3.6.1.4.1.10418.17.2.5.3.1.22ColumnpmPowerMgmtPDUTableTemperature3Maxread-writeobsoleteMaximum temperature detected in this PM unit in Celsius degrees. The value will be Zero when the PDU does not have support for maximum value. The value of this…
1.3.6.1.4.1.10418.17.2.5.3.1.23ColumnpmPowerMgmtPDUTableHumidityNOSread-onlyobsoleteNumber of humidity sensors in the PDU.
1.3.6.1.4.1.10418.17.2.5.3.1.24ColumnpmPowerMgmtPDUTableHumidity1Valueread-onlyobsoleteHumidity of this PM unit . If the humidity measurement is not installed this value will be 0.
1.3.6.1.4.1.10418.17.2.5.3.1.25ColumnpmPowerMgmtPDUTableHumidity1Maxread-writeobsoleteMaximum humidity detected in this PM unit. If the humidity measurement is not installed or the PDU does not have support for maximum value this value will be 0…
1.3.6.1.4.1.10418.17.2.5.3.1.26ColumnpmPowerMgmtPDUTableHumidity2Valueread-onlyobsoleteHumidity of this PM unit . If the humidity measurement is not installed this value will be 0.
1.3.6.1.4.1.10418.17.2.5.3.1.27ColumnpmPowerMgmtPDUTableHumidity2Maxread-writeobsoleteMaximum humidity detected in this PM unit. If the humidity measurement is not installed or the PDU does not have support for maximum value this value will be 0…
1.3.6.1.4.1.10418.17.2.5.3.1.28ColumnpmPowerMgmtPDUTableHumidity3Valueread-onlyobsoleteHumidity of this PM unit . If the humidity measurement is not installed this value will be 0.
1.3.6.1.4.1.10418.17.2.5.3.1.29ColumnpmPowerMgmtPDUTableHumidity3Maxread-writeobsoleteMaximum humidity detected in this PM unit. If the humidity measurement is not installed or the PDU does not have support for maximum value this value will be 0…
1.3.6.1.4.1.10418.17.2.5.3.1.30ColumnpmPowerMgmtPDUTableVoltageNOSread-onlyobsoleteNumber of voltage sensors in the PDU.
1.3.6.1.4.1.10418.17.2.5.3.1.31ColumnpmPowerMgmtPDUTableVoltage1Valueread-onlyobsoleteVoltage of this sensor in this PDU unit. This OID is obsoleted. The value can be retrieved from pmPowerMgmtPDUTableVoltageValue, pmPowerMgmtPhasesTableVoltageV…
1.3.6.1.4.1.10418.17.2.5.3.1.32ColumnpmPowerMgmtPDUTableVoltage1Maxread-writeobsoleteMaximum voltage of this sensor in this PDU unit. Set with Zero value to clear the maximum voltage. This OID is obsoleted. The value can be retrieved from pmPow…
1.3.6.1.4.1.10418.17.2.5.3.1.33ColumnpmPowerMgmtPDUTableVoltage2Valueread-onlyobsoleteVoltage of this sensor in this PDU unit. This OID is obsoleted. The value can be retrieved from pmPowerMgmtPDUTableVoltageValue, pmPowerMgmtPhasesTableVoltageV…
1.3.6.1.4.1.10418.17.2.5.3.1.34ColumnpmPowerMgmtPDUTableVoltage2Maxread-writeobsoleteMaximum voltage of this sensor in this PDU unit. Set with Zero value to clear the maximum voltage. This OID is obsoleted. The value can be retrieved from pmPow…
1.3.6.1.4.1.10418.17.2.5.3.1.35ColumnpmPowerMgmtPDUTableVoltage3Valueread-onlyobsoleteVoltage of this sensor in this PDU unit. This OID is obsoleted. The value can be retrieved from pmPowerMgmtPDUTableVoltageValue, pmPowerMgmtPhasesTableVoltageV…
1.3.6.1.4.1.10418.17.2.5.3.1.36ColumnpmPowerMgmtPDUTableVoltage3Maxread-writeobsoleteMaximum voltage of this sensor in this PDU unit. Set with Zero value to clear the maximum voltage. This OID is obsoleted. The value can be retrieved from pmPow…
1.3.6.1.4.1.10418.17.2.5.3.1.37ColumnpmPowerMgmtPDUTableNumberOfPhasesread-onlycurrentNumber of phases of the PDU.
1.3.6.1.4.1.10418.17.2.5.3.1.38ColumnpmPowerMgmtPDUTableNumberOfBanksread-onlycurrentNumber of banks in the PDU.
1.3.6.1.4.1.10418.17.2.5.3.1.40ColumnpmPowerMgmtPDUTableNumberOfSensorsread-onlycurrentNumber of sensors in the PDU.
1.3.6.1.4.1.10418.17.2.5.3.1.41ColumnpmPowerMgmtPDUTableFactoryDefaultread-writecurrentA set value of 2 will set the PDU to factory default settings. noAction(1) = always returned in a GET. Does nothing if SET. reset(2) = when SET the factory def…
1.3.6.1.4.1.10418.17.2.5.3.1.42ColumnpmPowerMgmtPDUTableColdStartDelayread-writecurrentPDUs cold start delay in whole seconds (0-60). Returns 0 if not supported.
1.3.6.1.4.1.10418.17.2.5.3.1.43ColumnpmPowerMgmtPDUTableRebootread-writecurrentA set value of power*(2) will send command to PDU. noAction(1) = always returned in a GET. Does nothing if SET. reboot(2) = when SET the reboot command is sent…
1.3.6.1.4.1.10418.17.2.5.3.1.44ColumnpmPowerMgmtPDUTableMaxCurrentread-onlycurrentMaximum value of current allowed in the PDU (A x 10).
1.3.6.1.4.1.10418.17.2.5.3.1.45ColumnpmPowerMgmtPDUTableAlarmread-onlycurrentShow the PDU alarm status. Returns 0 if not supported.
1.3.6.1.4.1.10418.17.2.5.3.1.50ColumnpmPowerMgmtPDUTableCurrentValueread-onlycurrentActual value of current in the PDU (A x 10). Returns 0 if not supported.
1.3.6.1.4.1.10418.17.2.5.3.1.51ColumnpmPowerMgmtPDUTableCurrentMaxread-onlycurrentMaximum value of current in the PDU (A x 10). Returns 0 if not supported.
1.3.6.1.4.1.10418.17.2.5.3.1.52ColumnpmPowerMgmtPDUTableCurrentMinread-onlycurrentMinimum value of current in the PDU (A x 10). Returns 0 if not supported.
1.3.6.1.4.1.10418.17.2.5.3.1.53ColumnpmPowerMgmtPDUTableCurrentAvgread-onlycurrentAverage value of current in the PDU (A x 10). Returns 0 if not supported.
1.3.6.1.4.1.10418.17.2.5.3.1.54ColumnpmPowerMgmtPDUTableCurrentResetread-writecurrentnoAction(1) = always returned in a GET. Does nothing if SET. reset(2) = when SET the reset command is sent to PDU.
1.3.6.1.4.1.10418.17.2.5.3.1.60ColumnpmPowerMgmtPDUTablePowerValueread-onlycurrentActual value of power in the PDU (W x 10). Returns 0 if not supported.
1.3.6.1.4.1.10418.17.2.5.3.1.61ColumnpmPowerMgmtPDUTablePowerMaxread-onlycurrentMaximum value of power in the PDU (W x 10). Returns 0 if not supported.
1.3.6.1.4.1.10418.17.2.5.3.1.62ColumnpmPowerMgmtPDUTablePowerMinread-onlycurrentMinimum value of power in the PDU (W x 10). Returns 0 if not supported.
1.3.6.1.4.1.10418.17.2.5.3.1.63ColumnpmPowerMgmtPDUTablePowerAvgread-onlycurrentAverage value of power in the PDU (W x 10). Returns 0 if not supported.
1.3.6.1.4.1.10418.17.2.5.3.1.64ColumnpmPowerMgmtPDUTablePowerResetread-writecurrentnoAction(1) = always returned in a GET. Does nothing if SET. reset(2) = when SET the reset command is sent to PDU.
1.3.6.1.4.1.10418.17.2.5.3.1.65ColumnpmPowerMgmtPDUTablePowerTyperead-onlycurrentType of power values. Returns 0 if not supported.
1.3.6.1.4.1.10418.17.2.5.3.1.70ColumnpmPowerMgmtPDUTableVoltageValueread-onlycurrentActual value of voltage in the PDU (V). Returns 0 if not supported.
1.3.6.1.4.1.10418.17.2.5.3.1.71ColumnpmPowerMgmtPDUTableVoltageMaxread-onlycurrentMaximum value of voltage in the PDU (V). Returns 0 if not supported.
1.3.6.1.4.1.10418.17.2.5.3.1.72ColumnpmPowerMgmtPDUTableVoltageMinread-onlycurrentMinimum value of voltage in the PDU (V). Returns 0 if not supported.
1.3.6.1.4.1.10418.17.2.5.3.1.73ColumnpmPowerMgmtPDUTableVoltageAvgread-onlycurrentAverage value of voltage in the PDU (V). Returns 0 if not supported.
1.3.6.1.4.1.10418.17.2.5.3.1.74ColumnpmPowerMgmtPDUTableVoltageResetread-writecurrentnoAction(1) = always returned in a GET. Does nothing if SET. reset(2) = when SET the reset command is sent to PDU.
1.3.6.1.4.1.10418.17.2.5.3.1.75ColumnpmPowerMgmtPDUTableVoltageTyperead-onlycurrentType of voltage values. Returns 0 if not supported.
1.3.6.1.4.1.10418.17.2.5.3.1.80ColumnpmPowerMgmtPDUTablePowerFactorValueread-onlycurrentActual value of power factor in the PDU (Pf x 100). Returns 0 if not supported.
1.3.6.1.4.1.10418.17.2.5.3.1.81ColumnpmPowerMgmtPDUTablePowerFactorMaxread-onlycurrentMaximum value of power factor in the PDU (Pf x 100). Returns 0 if not supported.
1.3.6.1.4.1.10418.17.2.5.3.1.82ColumnpmPowerMgmtPDUTablePowerFactorMinread-onlycurrentMinimum value of power factor in the PDU (Pf x 100). Returns 0 if not supported.
1.3.6.1.4.1.10418.17.2.5.3.1.83ColumnpmPowerMgmtPDUTablePowerFactorAvgread-onlycurrentAverage value of power factor in the PDU (Pf x 100). Returns 0 if not supported.
1.3.6.1.4.1.10418.17.2.5.3.1.84ColumnpmPowerMgmtPDUTablePowerFactorResetread-writecurrentnoAction(1) = always returned in a GET. Does nothing if SET. reset(2) = when SET the reset command is sent to PDU.
1.3.6.1.4.1.10418.17.2.5.3.1.85ColumnpmPowerMgmtPDUTablePowerFactorTyperead-onlycurrentType of power values. Returns 0 if not supported.
1.3.6.1.4.1.10418.17.2.5.3.1.90ColumnpmPowerMgmtPDUTablePowerControlread-writecurrentA set value of power*(2-4) will send command to PDU. noAction(1) = always returned in a GET. Does nothing if SET. powerOn(2) = when SET the power On command is…
1.3.6.1.4.1.10418.17.2.5.3.1.91ColumnpmPowerMgmtPDUTableResetOCPread-writecurrentA set value of power*(2) will send command to PDU. noAction(1) = always returned in a GET. Does nothing if SET. reset(2) = when SET the reset command is sent t…
1.3.6.1.4.1.10418.17.2.5.3.1.100ColumnpmPowerMgmtPDUTableCurrentHighCriticalread-writecurrentoutlet high critical (alarm) current threshold (A x 10). Set fails if value is lower that CurrentHighWarning. Returns 0 if not supported.
1.3.6.1.4.1.10418.17.2.5.3.1.101ColumnpmPowerMgmtPDUTableCurrentHighWarningread-writecurrentoutlet high warning current threshold (A x 10). Set fails if value is higher than CurrentHighCritical or lower than CurrentLowWarning. Returns 0 if not support…
1.3.6.1.4.1.10418.17.2.5.3.1.102ColumnpmPowerMgmtPDUTableCurrentLowWarningread-writecurrentoutlet low warning current threshold (A x 10). Set fails if value is higher than CurrentHighWarning or lower than CurrentLowCritical. Returns 0 if not supporte…
1.3.6.1.4.1.10418.17.2.5.3.1.103ColumnpmPowerMgmtPDUTableCurrentLowCriticalread-writecurrentoutlet low critical current threshold (A x 10). Set fails if value is higher than CurrentLowWarning. Returns 0 if not supported.
1.3.6.1.4.1.10418.17.2.5.3.1.105ColumnpmPowerMgmtPDUTableEnergyValueread-onlycurrentpdu energy value (Wh). Returns 0 if not supported.
1.3.6.1.4.1.10418.17.2.5.3.1.106ColumnpmPowerMgmtPDUTableEnergyStartTimeread-onlycurrenttime at which energy calculation commenced (ISO8601 format). Returns N/A if not applicable.
1.3.6.1.4.1.10418.17.2.5.3.1.107ColumnpmPowerMgmtPDUTableEnergyResetread-writecurrentnoAction(1) = always returned in a GET. Does nothing if SET. reset(2) = when SET the reset command is sent to PDU.
1.3.6.1.4.1.10418.17.2.5.4ScalarpmPowerMgmtTotalNumberOfOutletsread-onlycurrentNumber of outlets managed by the appliance.
1.3.6.1.4.1.10418.17.2.5.5TablepmPowerMgmtOutletsTablenot-accessiblecurrentThis table contains the information about outlets.
1.3.6.1.4.1.10418.17.2.5.5.1RowpmPowerMgmtOutletsTableEntrynot-accessiblecurrenteach entry has the information about the outlet.
1.3.6.1.4.1.10418.17.2.5.5.1.1ColumnpmPowerMgmtOutletsTablePortNumberread-onlycurrentSerial Port number.
1.3.6.1.4.1.10418.17.2.5.5.1.2ColumnpmPowerMgmtOutletsTablePduNumberread-onlycurrentIndex.
1.3.6.1.4.1.10418.17.2.5.5.1.3ColumnpmPowerMgmtOutletsTableNumberread-onlycurrentNumber of the outlet in the PDU.
1.3.6.1.4.1.10418.17.2.5.5.1.4ColumnpmPowerMgmtOutletsTableNameread-writecurrentName of the outlet.
1.3.6.1.4.1.10418.17.2.5.5.1.5ColumnpmPowerMgmtOutletsTableStatusread-onlycurrentStatus of the outlet. Returns 0 if not supported.
1.3.6.1.4.1.10418.17.2.5.5.1.6ColumnpmPowerMgmtOutletsTablePowerControlread-writecurrentA set value of power*(2-6) will send command to PDU. noAction(1) = always returned in a GET. Does nothing if SET. powerOn(2) = when SET the power On command is…
1.3.6.1.4.1.10418.17.2.5.5.1.7ColumnpmPowerMgmtOutletsTablePortNameread-onlycurrentSerial Port Name where the PDU is connected.
1.3.6.1.4.1.10418.17.2.5.5.1.8ColumnpmPowerMgmtOutletsTablePduIdread-onlycurrentPDU identification.
1.3.6.1.4.1.10418.17.2.5.5.1.9ColumnpmPowerMgmtOutletsTablePostOnDelayread-writecurrentpost on delay for the outlet (seconds x 10) Returns 0 if not supported.
1.3.6.1.4.1.10418.17.2.5.5.1.10ColumnpmPowerMgmtOutletsTablePostOffDelayread-writecurrentpost off delay for the outlet (seconds x 10) Returns 0 if not supported.
1.3.6.1.4.1.10418.17.2.5.5.1.45ColumnpmPowerMgmtOutletsTableAlarmread-onlycurrentShow the outlet alarm status. Returns 0 if not supported.
1.3.6.1.4.1.10418.17.2.5.5.1.50ColumnpmPowerMgmtOutletsTableCurrentValueread-onlycurrentActual value of current in the outlet (A x 10). Returns 0 if not supported.
1.3.6.1.4.1.10418.17.2.5.5.1.51ColumnpmPowerMgmtOutletsTableCurrentMaxread-onlycurrentMaximum value of current in the outlet (A x 10). Returns 0 if not supported.
1.3.6.1.4.1.10418.17.2.5.5.1.52ColumnpmPowerMgmtOutletsTableCurrentMinread-onlycurrentMinimum value of current in the outlet (A x 10). Returns 0 if not supported.
1.3.6.1.4.1.10418.17.2.5.5.1.53ColumnpmPowerMgmtOutletsTableCurrentAvgread-onlycurrentAverage value of current in the outlet (A x 10). Returns 0 if not supported.
1.3.6.1.4.1.10418.17.2.5.5.1.54ColumnpmPowerMgmtOutletsTableCurrentResetread-writecurrentnoAction(1) = always returned in a GET. Does nothing if SET. reset(2) = when SET the reset command is sent to PDU.
1.3.6.1.4.1.10418.17.2.5.5.1.60ColumnpmPowerMgmtOutletsTablePowerValueread-onlycurrentActual value of power in the outlet (W x 10). Returns 0 if not supported.
1.3.6.1.4.1.10418.17.2.5.5.1.61ColumnpmPowerMgmtOutletsTablePowerMaxread-onlycurrentMaximum value of power in the outlet (W x 10). Returns 0 if not supported.
1.3.6.1.4.1.10418.17.2.5.5.1.62ColumnpmPowerMgmtOutletsTablePowerMinread-onlycurrentMinimum value of power in the outlet (W x 10). Returns 0 if not supported.
1.3.6.1.4.1.10418.17.2.5.5.1.63ColumnpmPowerMgmtOutletsTablePowerAvgread-onlycurrentAverage value of power in the outlet (W x 10). Returns 0 if not supported.
1.3.6.1.4.1.10418.17.2.5.5.1.64ColumnpmPowerMgmtOutletsTablePowerResetread-writecurrentnoAction(1) = always returned in a GET. Does nothing if SET. reset(2) = when SET the reset command is sent to PDU.
1.3.6.1.4.1.10418.17.2.5.5.1.65ColumnpmPowerMgmtOutletsTablePowerTyperead-onlycurrentType of power values. Returns 0 if not supported.
1.3.6.1.4.1.10418.17.2.5.5.1.70ColumnpmPowerMgmtOutletsTableVoltageValueread-onlycurrentActual value of voltage in the outlet (V). Returns 0 if not supported.
1.3.6.1.4.1.10418.17.2.5.5.1.71ColumnpmPowerMgmtOutletsTableVoltageMaxread-onlycurrentMaximum value of voltage in the outlet (V). Returns 0 if not supported.
1.3.6.1.4.1.10418.17.2.5.5.1.72ColumnpmPowerMgmtOutletsTableVoltageMinread-onlycurrentMinimum value of voltage in the outlet (V). Returns 0 if not supported.
1.3.6.1.4.1.10418.17.2.5.5.1.73ColumnpmPowerMgmtOutletsTableVoltageAvgread-onlycurrentAverage value of voltage in the outlet (V). Returns 0 if not supported.
1.3.6.1.4.1.10418.17.2.5.5.1.74ColumnpmPowerMgmtOutletsTableVoltageResetread-writecurrentnoAction(1) = always returned in a GET. Does nothing if SET. reset(2) = when SET the reset command is sent to PDU.
1.3.6.1.4.1.10418.17.2.5.5.1.75ColumnpmPowerMgmtOutletsTableVoltageTyperead-onlycurrentType of voltage values. Returns 0 if not supported.
1.3.6.1.4.1.10418.17.2.5.5.1.80ColumnpmPowerMgmtOutletsTablePowerFactorValueread-onlycurrentActual value of power factor in the outlet (Pf x 100). Returns 0 if not supported.
1.3.6.1.4.1.10418.17.2.5.5.1.81ColumnpmPowerMgmtOutletsTablePowerFactorMaxread-onlycurrentMaximum value of power factor in the outlet (Pf x 100). Returns 0 if not supported.
1.3.6.1.4.1.10418.17.2.5.5.1.82ColumnpmPowerMgmtOutletsTablePowerFactorMinread-onlycurrentMinimum value of power factor in the outlet (Pf x 100). Returns 0 if not supported.
1.3.6.1.4.1.10418.17.2.5.5.1.83ColumnpmPowerMgmtOutletsTablePowerFactorAvgread-onlycurrentAverage value of power factor in the outlet (Pf x 100). Returns 0 if not supported.
1.3.6.1.4.1.10418.17.2.5.5.1.84ColumnpmPowerMgmtOutletsTablePowerFactorResetread-writecurrentnoAction(1) = always returned in a GET. Does nothing if SET. reset(2) = when SET the reset command is sent to PDU.
1.3.6.1.4.1.10418.17.2.5.5.1.85ColumnpmPowerMgmtOutletsTablePowerFactorTyperead-onlycurrentType of power factor values. Returns 0 if not supported.
1.3.6.1.4.1.10418.17.2.5.5.1.100ColumnpmPowerMgmtOutletsTableCurrentHighCriticalread-writecurrentoutlet high critical (alarm) current threshold (A x 10). Set fails if value is lower that CurrentHighWarning. Returns 0 if not supported.
1.3.6.1.4.1.10418.17.2.5.5.1.101ColumnpmPowerMgmtOutletsTableCurrentHighWarningread-writecurrentoutlet high warning current threshold (A x 10). Set fails if value is higher than CurrentHighCritical or lower than CurrentLowWarning. Returns 0 if not support…
1.3.6.1.4.1.10418.17.2.5.5.1.102ColumnpmPowerMgmtOutletsTableCurrentLowWarningread-writecurrentoutlet low warning current threshold (A x 10). Set fails if value is higher than CurrentHighWarning or lower than CurrentLowCritical. Returns 0 if not supporte…
1.3.6.1.4.1.10418.17.2.5.5.1.103ColumnpmPowerMgmtOutletsTableCurrentLowCriticalread-writecurrentoutlet low critical current threshold (A x 10). Set fails if value is higher than CurrentLowWarning. Returns 0 if not supported.
1.3.6.1.4.1.10418.17.2.5.5.1.105ColumnpmPowerMgmtOutletsTableEnergyValueread-onlycurrentoutlet energy value (Wh). Returns 0 if not supported.
1.3.6.1.4.1.10418.17.2.5.5.1.106ColumnpmPowerMgmtOutletsTableEnergyStartTimeread-onlycurrenttime at which energy calculation commenced (ISO8601 format). Returns N/A if not applicable.
1.3.6.1.4.1.10418.17.2.5.5.1.107ColumnpmPowerMgmtOutletsTableEnergyResetread-writecurrentnoAction(1) = always returned in a GET. Does nothing if SET. reset(2) = when SET the reset command is sent to PDU.
1.3.6.1.4.1.10418.17.2.5.6ScalarpmPowerMgmtNumberOfOutletGroupread-onlycurrentNumber of configured group of outlets.
1.3.6.1.4.1.10418.17.2.5.7TablepmPowerMgmtGroupTablenot-accessiblecurrentThis table contains the information about group of outlets.
1.3.6.1.4.1.10418.17.2.5.7.1RowpmPowerMgmtGroupTableEntrynot-accessiblecurrenteach entry has the information about group of outlets.
1.3.6.1.4.1.10418.17.2.5.7.1.1ColumnpmPowerMgmtGroupTableIndexread-onlycurrentIndex of the group.
1.3.6.1.4.1.10418.17.2.5.7.1.2ColumnpmPowerMgmtGroupTableNameread-onlycurrentName of the group of outlets.
1.3.6.1.4.1.10418.17.2.5.7.1.3ColumnpmPowerMgmtGroupTableStatusread-onlycurrentStatus of the group of outlet.
1.3.6.1.4.1.10418.17.2.5.7.1.4ColumnpmPowerMgmtGroupTablePowerControlread-writecurrentA set value of power*(2-4) will send command to PDU. noAction(1) = always returned in a GET. Does nothing if SET. powerOn(2) = when SET the power On command is…
1.3.6.1.4.1.10418.17.2.5.8ScalarpmPowerMgmtTotalNumberOfPhasesread-onlycurrentNumber of phases managed by the appliance.
1.3.6.1.4.1.10418.17.2.5.9TablepmPowerMgmtPhasesTablenot-accessiblecurrentThis table contains the information about phases.
1.3.6.1.4.1.10418.17.2.5.9.1RowpmPowerMgmtPhasesTableEntrynot-accessiblecurrenteach entry has the information about the phases.
1.3.6.1.4.1.10418.17.2.5.9.1.1ColumnpmPowerMgmtPhasesTablePortNumberread-onlycurrentSerial Port number.
1.3.6.1.4.1.10418.17.2.5.9.1.2ColumnpmPowerMgmtPhasesTablePduNumberread-onlycurrentIndex.
1.3.6.1.4.1.10418.17.2.5.9.1.3ColumnpmPowerMgmtPhasesTableNumberread-onlycurrentNumber of the phase in the PDU.
1.3.6.1.4.1.10418.17.2.5.9.1.4ColumnpmPowerMgmtPhasesTableNameread-onlycurrentName of the phase. Returns N/A if not applicable.
1.3.6.1.4.1.10418.17.2.5.9.1.5ColumnpmPowerMgmtPhasesTablePortNameread-onlycurrentSerial Port Name where the PDU is connected.
1.3.6.1.4.1.10418.17.2.5.9.1.6ColumnpmPowerMgmtPhasesTablePduIdread-onlycurrentPDU identification.
1.3.6.1.4.1.10418.17.2.5.9.1.45ColumnpmPowerMgmtPhasesTableAlarmread-onlycurrentShow the phase alarm status. Returns 0 if not supported.
1.3.6.1.4.1.10418.17.2.5.9.1.50ColumnpmPowerMgmtPhasesTableCurrentValueread-onlycurrentActual value of current in the phase (A x 10). Returns 0 if not supported.
1.3.6.1.4.1.10418.17.2.5.9.1.51ColumnpmPowerMgmtPhasesTableCurrentMaxread-onlycurrentMaximum value of current in the phase (A x 10). Returns 0 if not supported.
1.3.6.1.4.1.10418.17.2.5.9.1.52ColumnpmPowerMgmtPhasesTableCurrentMinread-onlycurrentMinimum value of current in the phase (A x 10). Returns 0 if not supported.
1.3.6.1.4.1.10418.17.2.5.9.1.53ColumnpmPowerMgmtPhasesTableCurrentAvgread-onlycurrentAverage value of current in the phase (A x 10). Returns 0 if not supported.
1.3.6.1.4.1.10418.17.2.5.9.1.54ColumnpmPowerMgmtPhasesTableCurrentResetread-writecurrentnoAction(1) = always returned in a GET. Does nothing if SET. reset(2) = when SET the reset command is sent to PDU.
1.3.6.1.4.1.10418.17.2.5.9.1.60ColumnpmPowerMgmtPhasesTablePowerValueread-onlycurrentActual value of power in the phase (W x 10). Returns 0 if not supported.
1.3.6.1.4.1.10418.17.2.5.9.1.61ColumnpmPowerMgmtPhasesTablePowerMaxread-onlycurrentMaximum value of power in the phase (W x 10). Returns 0 if not supported.
1.3.6.1.4.1.10418.17.2.5.9.1.62ColumnpmPowerMgmtPhasesTablePowerMinread-onlycurrentMinimum value of power in the phase (W x 10). Returns 0 if not supported.
1.3.6.1.4.1.10418.17.2.5.9.1.63ColumnpmPowerMgmtPhasesTablePowerAvgread-onlycurrentAverage value of power in the phase (W x 10). Returns 0 if not supported.
1.3.6.1.4.1.10418.17.2.5.9.1.64ColumnpmPowerMgmtPhasesTablePowerResetread-writecurrentnoAction(1) = always returned in a GET. Does nothing if SET. reset(2) = when SET the reset command is sent to PDU.
1.3.6.1.4.1.10418.17.2.5.9.1.65ColumnpmPowerMgmtPhasesTablePowerTyperead-onlycurrentType of power values. Returns 0 if not supported.
1.3.6.1.4.1.10418.17.2.5.9.1.70ColumnpmPowerMgmtPhasesTableVoltageValueread-onlycurrentActual value of voltage in the phase (V). Returns 0 if not supported.
1.3.6.1.4.1.10418.17.2.5.9.1.71ColumnpmPowerMgmtPhasesTableVoltageMaxread-onlycurrentMaximum value of voltage in the phase (V). Returns 0 if not supported.
1.3.6.1.4.1.10418.17.2.5.9.1.72ColumnpmPowerMgmtPhasesTableVoltageMinread-onlycurrentMinimum value of voltage in the phase (V). Returns 0 if not supported.
1.3.6.1.4.1.10418.17.2.5.9.1.73ColumnpmPowerMgmtPhasesTableVoltageAvgread-onlycurrentAverage value of voltage in the phase (V). Returns 0 if not supported.
1.3.6.1.4.1.10418.17.2.5.9.1.74ColumnpmPowerMgmtPhasesTableVoltageResetread-writecurrentnoAction(1) = always returned in a GET. Does nothing if SET. reset(2) = when SET the reset command is sent to PDU.
1.3.6.1.4.1.10418.17.2.5.9.1.75ColumnpmPowerMgmtPhasesTableVoltageTyperead-onlycurrentType of voltage values. Returns 0 if not supported.
1.3.6.1.4.1.10418.17.2.5.9.1.80ColumnpmPowerMgmtPhasesTablePowerFactorValueread-onlycurrentActual value of power factor in the phase (Pf x 100). Returns 0 if not supported.
1.3.6.1.4.1.10418.17.2.5.9.1.81ColumnpmPowerMgmtPhasesTablePowerFactorMaxread-onlycurrentMaximum value of power factor in the phase (Pf x 100). Returns 0 if not supported.
1.3.6.1.4.1.10418.17.2.5.9.1.82ColumnpmPowerMgmtPhasesTablePowerFactorMinread-onlycurrentMinimum value of power factor in the phase (Pf x 100). Returns 0 if not supported.
1.3.6.1.4.1.10418.17.2.5.9.1.83ColumnpmPowerMgmtPhasesTablePowerFactorAvgread-onlycurrentAverage value of power factor in the phase (Pf x 100). Returns 0 if not supported.
1.3.6.1.4.1.10418.17.2.5.9.1.84ColumnpmPowerMgmtPhasesTablePowerFactorResetread-writecurrentnoAction(1) = always returned in a GET. Does nothing if SET. reset(2) = when SET the reset command is sent to PDU.
1.3.6.1.4.1.10418.17.2.5.9.1.85ColumnpmPowerMgmtPhasesTablePowerFactorTyperead-onlycurrentType of power factor values. Returns 0 if not supported.
1.3.6.1.4.1.10418.17.2.5.9.1.100ColumnpmPowerMgmtPhasesTableCurrentHighCriticalread-writecurrentphase high critical (alarm) current threshold (A x 10). Set fails if value is lower that CurrentHighWarning. Returns 0 if not supported.
1.3.6.1.4.1.10418.17.2.5.9.1.101ColumnpmPowerMgmtPhasesTableCurrentHighWarningread-writecurrentphase high warning current threshold (A x 10). Set fails if value is higher than CurrentHighCritical or lower than CurrentLowWarning. Returns 0 if not supporte…
1.3.6.1.4.1.10418.17.2.5.9.1.102ColumnpmPowerMgmtPhasesTableCurrentLowWarningread-writecurrentphase low warning current threshold (A x 10). Set fails if value is higher than CurrentHighWarning or lower than CurrentLowCritical. Returns 0 if not supported.
1.3.6.1.4.1.10418.17.2.5.9.1.103ColumnpmPowerMgmtPhasesTableCurrentLowCriticalread-writecurrentphase low critical current threshold (A x 10). Set fails if value is higher than CurrentLowWarning. Returns 0 if not supported.
1.3.6.1.4.1.10418.17.2.5.10ScalarpmPowerMgmtTotalNumberOfBanksread-onlycurrentNumber of banks managed by the appliance.
1.3.6.1.4.1.10418.17.2.5.11TablepmPowerMgmtBanksTablenot-accessiblecurrentThis table contains the information about banks.
1.3.6.1.4.1.10418.17.2.5.11.1RowpmPowerMgmtBanksTableEntrynot-accessiblecurrenteach entry has the information about the banks.
1.3.6.1.4.1.10418.17.2.5.11.1.1ColumnpmPowerMgmtBanksTablePortNumberread-onlycurrentSerial Port number.
1.3.6.1.4.1.10418.17.2.5.11.1.2ColumnpmPowerMgmtBanksTablePduNumberread-onlycurrentIndex.
1.3.6.1.4.1.10418.17.2.5.11.1.3ColumnpmPowerMgmtBanksTableNumberread-onlycurrentNumber of the bank in the PDU.
1.3.6.1.4.1.10418.17.2.5.11.1.4ColumnpmPowerMgmtBanksTableNameread-onlycurrentName of the bank.
1.3.6.1.4.1.10418.17.2.5.11.1.5ColumnpmPowerMgmtBanksTablePortNameread-onlycurrentSerial Port Name where the PDU is connected.
1.3.6.1.4.1.10418.17.2.5.11.1.6ColumnpmPowerMgmtBanksTablePduIdread-onlycurrentPDU identification.
1.3.6.1.4.1.10418.17.2.5.11.1.45ColumnpmPowerMgmtBanksTableAlarmread-onlycurrentShow the bank alarm status. Returns 0 if not supported.
1.3.6.1.4.1.10418.17.2.5.11.1.50ColumnpmPowerMgmtBanksTableCurrentValueread-onlycurrentActual value of current in the bank (A x 10). Returns 0 if not supported.
1.3.6.1.4.1.10418.17.2.5.11.1.51ColumnpmPowerMgmtBanksTableCurrentMaxread-onlycurrentMaximum value of current in the bank (A x 10). Returns 0 if not supported.
1.3.6.1.4.1.10418.17.2.5.11.1.52ColumnpmPowerMgmtBanksTableCurrentMinread-onlycurrentMinimum value of current in the bank (A x 10). Returns 0 if not supported.
1.3.6.1.4.1.10418.17.2.5.11.1.53ColumnpmPowerMgmtBanksTableCurrentAvgread-onlycurrentAverage value of current in the bank (A x 10). Returns 0 if not supported.
1.3.6.1.4.1.10418.17.2.5.11.1.54ColumnpmPowerMgmtBanksTableCurrentResetread-writecurrentnoAction(1) = always returned in a GET. Does nothing if SET. reset(2) = when SET the reset command is sent to PDU.
1.3.6.1.4.1.10418.17.2.5.11.1.60ColumnpmPowerMgmtBanksTablePowerValueread-onlycurrentActual value of power in the bank (W x 10). Returns 0 if not supported.
1.3.6.1.4.1.10418.17.2.5.11.1.61ColumnpmPowerMgmtBanksTablePowerMaxread-onlycurrentMaximum value of power in the bank (W x 10). Returns 0 if not supported.
1.3.6.1.4.1.10418.17.2.5.11.1.62ColumnpmPowerMgmtBanksTablePowerMinread-onlycurrentMinimum value of power in the bank (W x 10). Returns 0 if not supported.
1.3.6.1.4.1.10418.17.2.5.11.1.63ColumnpmPowerMgmtBanksTablePowerAvgread-onlycurrentAverage value of power in the bank (W x 10). Returns 0 if not supported.
1.3.6.1.4.1.10418.17.2.5.11.1.64ColumnpmPowerMgmtBanksTablePowerResetread-writecurrentnoAction(1) = always returned in a GET. Does nothing if SET. reset(2) = when SET the reset command is sent to PDU.
1.3.6.1.4.1.10418.17.2.5.11.1.65ColumnpmPowerMgmtBanksTablePowerTyperead-onlycurrentType of power values. Returns 0 if not supported.
1.3.6.1.4.1.10418.17.2.5.11.1.70ColumnpmPowerMgmtBanksTableVoltageValueread-onlycurrentActual value of voltage in the bank (V). Returns 0 if not supported.
1.3.6.1.4.1.10418.17.2.5.11.1.71ColumnpmPowerMgmtBanksTableVoltageMaxread-onlycurrentMaximum value of voltage in the bank (V). Returns 0 if not supported.
1.3.6.1.4.1.10418.17.2.5.11.1.72ColumnpmPowerMgmtBanksTableVoltageMinread-onlycurrentMinimum value of voltage in the bank (V). Returns 0 if not supported.
1.3.6.1.4.1.10418.17.2.5.11.1.73ColumnpmPowerMgmtBanksTableVoltageAvgread-onlycurrentAverage value of voltage in the bank (V). Returns 0 if not supported.
1.3.6.1.4.1.10418.17.2.5.11.1.74ColumnpmPowerMgmtBanksTableVoltageResetread-writecurrentnoAction(1) = always returned in a GET. Does nothing if SET. reset(2) = when SET the reset command is sent to PDU.
1.3.6.1.4.1.10418.17.2.5.11.1.75ColumnpmPowerMgmtBanksTableVoltageTyperead-onlycurrentType of voltage values. Returns 0 if not supported.
1.3.6.1.4.1.10418.17.2.5.11.1.80ColumnpmPowerMgmtBanksTablePowerFactorValueread-onlycurrentActual value of power factor in the bank (Pf x 100). Returns 0 if not supported.
1.3.6.1.4.1.10418.17.2.5.11.1.81ColumnpmPowerMgmtBanksTablePowerFactorMaxread-onlycurrentMaximum value of power factor in the bank (Pf x 100). Returns 0 if not supported.
1.3.6.1.4.1.10418.17.2.5.11.1.82ColumnpmPowerMgmtBanksTablePowerFactorMinread-onlycurrentMinimum value of power factor in the bank (Pf x 100). Returns 0 if not supported.
1.3.6.1.4.1.10418.17.2.5.11.1.83ColumnpmPowerMgmtBanksTablePowerFactorAvgread-onlycurrentAverage value of power factor in the bank (Pf x 100). Returns 0 if not supported.
1.3.6.1.4.1.10418.17.2.5.11.1.84ColumnpmPowerMgmtBanksTablePowerFactorResetread-writecurrentnoAction(1) = always returned in a GET. Does nothing if SET. reset(2) = when SET the reset command is sent to PDU.
1.3.6.1.4.1.10418.17.2.5.11.1.85ColumnpmPowerMgmtBanksTablePowerFactorTyperead-onlycurrentType of power factor values. Returns 0 if not supported.
1.3.6.1.4.1.10418.17.2.5.11.1.100ColumnpmPowerMgmtBanksTableCurrentHighCriticalread-writecurrentbank high critical (alarm) current threshold (A x 10). Set fails if value is lower that CurrentHighWarning. Returns 0 if not supported.
1.3.6.1.4.1.10418.17.2.5.11.1.101ColumnpmPowerMgmtBanksTableCurrentHighWarningread-writecurrentbank high warning current threshold (A x 10). Set fails if value is higher than CurrentHighCritical or lower than CurrentLowWarning. Returns 0 if not supported.
1.3.6.1.4.1.10418.17.2.5.11.1.102ColumnpmPowerMgmtBanksTableCurrentLowWarningread-writecurrentbank low warning current threshold (A x 10). Set fails if value is higher than CurrentHighWarning or lower than CurrentLowCritical. Returns 0 if not supported.
1.3.6.1.4.1.10418.17.2.5.11.1.103ColumnpmPowerMgmtBanksTableCurrentLowCriticalread-writecurrentbank low critical current threshold (A x 10). Set fails if value is higher than CurrentLowWarning. Returns 0 if not supported.
1.3.6.1.4.1.10418.17.2.5.11.1.105ColumnpmPowerMgmtBanksTableEnergyValueread-onlycurrentbank energy value (Wh). Returns 0 if not supported.
1.3.6.1.4.1.10418.17.2.5.11.1.106ColumnpmPowerMgmtBanksTableEnergyStartTimeread-onlycurrenttime at which energy calculation commenced (ISO8601 format). Returns N/A if not applicable.
1.3.6.1.4.1.10418.17.2.5.11.1.107ColumnpmPowerMgmtBanksTableEnergyResetread-writecurrentnoAction(1) = always returned in a GET. Does nothing if SET. reset(2) = when SET the reset command is sent to PDU.
1.3.6.1.4.1.10418.17.2.5.12ScalarpmPowerMgmtTotalNumberOfSensorsread-onlycurrentNumber of Sensors managed by the appliance.
1.3.6.1.4.1.10418.17.2.5.13TablepmPowerMgmtSensorsTablenot-accessiblecurrentThis table contains the information about sensors.
1.3.6.1.4.1.10418.17.2.5.13.1RowpmPowerMgmtSensorsTableEntrynot-accessiblecurrenteach entry has the information about the sensors.
1.3.6.1.4.1.10418.17.2.5.13.1.1ColumnpmPowerMgmtSensorsTablePortNumberread-onlycurrentSerial Port number.
1.3.6.1.4.1.10418.17.2.5.13.1.2ColumnpmPowerMgmtSensorsTablePduNumberread-onlycurrentIndex.
1.3.6.1.4.1.10418.17.2.5.13.1.3ColumnpmPowerMgmtSensorsTableNumberread-onlycurrentNumber of the sensor in the PDU.
1.3.6.1.4.1.10418.17.2.5.13.1.4ColumnpmPowerMgmtSensorsTableNameread-writecurrentName of the sensor.
1.3.6.1.4.1.10418.17.2.5.13.1.5ColumnpmPowerMgmtSensorsTablePortNameread-onlycurrentSerial Port Name where the PDU is connected.
1.3.6.1.4.1.10418.17.2.5.13.1.6ColumnpmPowerMgmtSensorsTablePduIdread-onlycurrentPDU identification.
1.3.6.1.4.1.10418.17.2.5.13.1.7ColumnpmPowerMgmtSensorsTableTyperead-onlycurrentThe type of environmental monitor. Returns 0 if not supported.
1.3.6.1.4.1.10418.17.2.5.13.1.8ColumnpmPowerMgmtSensorsTableStatusread-onlycurrentStatus of digital sensors: Dry-Contact, Water level, Smoke sensor, Motion sensor. Returns 0 if not supported.
1.3.6.1.4.1.10418.17.2.5.13.1.20ColumnpmPowerMgmtSensorsTableValueread-onlycurrentActual value of the sensor. Returns N/A if not applicable.
1.3.6.1.4.1.10418.17.2.5.13.1.21ColumnpmPowerMgmtSensorsTableValueMaxread-onlycurrentMaximum value of the sensor. Returns N/A if not applicable.
1.3.6.1.4.1.10418.17.2.5.13.1.22ColumnpmPowerMgmtSensorsTableValueMinread-onlycurrentMinimum value of the sensor. Returns N/A if not applicable.
1.3.6.1.4.1.10418.17.2.5.13.1.23ColumnpmPowerMgmtSensorsTableValueAvgread-onlycurrentAverage value of the sensor. Returns N/A if not applicable.
1.3.6.1.4.1.10418.17.2.5.13.1.25ColumnpmPowerMgmtSensorsTableValueIntread-onlycurrentActual value of the sensor. Returns 0 if not supported.
1.3.6.1.4.1.10418.17.2.5.13.1.26ColumnpmPowerMgmtSensorsTableValueMaxIntread-onlycurrentMaximum value of the sensor. Returns 0 if not supported.
1.3.6.1.4.1.10418.17.2.5.13.1.27ColumnpmPowerMgmtSensorsTableValueMinIntread-onlycurrentMinimum value of the sensor. Returns 0 if not supported.
1.3.6.1.4.1.10418.17.2.5.13.1.28ColumnpmPowerMgmtSensorsTableValueAvgIntread-onlycurrentAverage value of the sensor. Returns 0 if not supported.
1.3.6.1.4.1.10418.17.2.5.13.1.30ColumnpmPowerMgmtSensorsTableValueResetread-writecurrentnoAction(1) = always returned in a GET. Does nothing if SET. reset(2) = when SET the reset command is sent to sensor.
1.3.6.1.4.1.10418.17.2.5.13.1.40ColumnpmPowerMgmtSensorsTableHighCriticalread-writecurrentsensor high critical (alarm) threshold (unit x 10) - use unit as returned by pmPowerMgmtSensorsTableUnit. Set fails if value is lower that CurrentHighWarning. …
1.3.6.1.4.1.10418.17.2.5.13.1.41ColumnpmPowerMgmtSensorsTableHighWarningread-writecurrentsensor high warning threshold (unit x 10) - use unit as returned by pmPowerMgmtSensorsTableUnit. Set fails if value is higher than HighCritical or lower than L…
1.3.6.1.4.1.10418.17.2.5.13.1.42ColumnpmPowerMgmtSensorsTableLowWarningread-writecurrentsensor low warning threshold (unit x 10) - use unit as returned by pmPowerMgmtSensorsTableUnit. Set fails if value is higher than HighWarning or lower than Low…
1.3.6.1.4.1.10418.17.2.5.13.1.43ColumnpmPowerMgmtSensorsTableLowCriticalread-writecurrentsensor low critical threshold (unit x 10) - use unit as returned by pmPowerMgmtSensorsTableUnit. Set fails if value is higher than LowWarning. Returns 0 if not…
1.3.6.1.4.1.10418.17.2.5.13.1.45ColumnpmPowerMgmtSensorsTableUnitread-writecurrentsensor unit. Returns 0 if not supported.
1.3.6.1.4.1.10418.17.2.5.13.1.50ColumnpmPowerMgmtSensorsTableHighCriticalCread-onlycurrentsensor high critical (alarm) threshold (Celcius x 10). to SET: use pmPowerMgmtSensorsTableHighCritical in proper units (pmPowerMgmtSensorsTableUnit). Returns 0…
1.3.6.1.4.1.10418.17.2.5.13.1.51ColumnpmPowerMgmtSensorsTableHighWarningCread-onlycurrentsensor high warning threshold (Celcius x 10). to SET: use pmPowerMgmtSensorsTableHighWarning in proper units (pmPowerMgmtSensorsTableUnit). Returns 0 if not su…
1.3.6.1.4.1.10418.17.2.5.13.1.52ColumnpmPowerMgmtSensorsTableLowWarningCread-onlycurrentsensor low warning threshold (Celcius x 10). to SET: use pmPowerMgmtSensorsTableLowWarning in proper units (pmPowerMgmtSensorsTableUnit). Returns 0 if not supp…
1.3.6.1.4.1.10418.17.2.5.13.1.53ColumnpmPowerMgmtSensorsTableLowCriticalCread-onlycurrentsensor low critical threshold (Celcius x 10). to SET: use pmPowerMgmtSensorsTableLowCritical in proper units (pmPowerMgmtSensorsTableUnit). Returns 0 if not su…
1.3.6.1.4.1.10418.17.2.5.13.1.60ColumnpmPowerMgmtSensorsTableHighCriticalFread-onlycurrentsensor high critical (alarm) threshold (Fahrenheit x 10). to SET: use pmPowerMgmtSensorsTableHighCritical in proper units (pmPowerMgmtSensorsTableUnit). Return…
1.3.6.1.4.1.10418.17.2.5.13.1.61ColumnpmPowerMgmtSensorsTableHighWarningFread-onlycurrentsensor high warning threshold (Fahrenheit x 10). to SET: use pmPowerMgmtSensorsTableHighWarning in proper units (pmPowerMgmtSensorsTableUnit). Returns 0 if not…
1.3.6.1.4.1.10418.17.2.5.13.1.62ColumnpmPowerMgmtSensorsTableLowWarningFread-onlycurrentsensor low warning threshold (Fahrenheit x 10). to SET: use pmPowerMgmtSensorsTableLowWarning in proper units (pmPowerMgmtSensorsTableUnit). Returns 0 if not s…
1.3.6.1.4.1.10418.17.2.5.13.1.63ColumnpmPowerMgmtSensorsTableLowCriticalFread-onlycurrentsensor low critical threshold (Fahrenheit x 10). to SET: use pmPowerMgmtSensorsTableLowCritical in proper units (pmPowerMgmtSensorsTableUnit). Returns 0 if not…
1.3.6.1.4.1.10418.17.2.6NodepmTrapObject