OIDNameAccessStatusDescription
1.3.6.1.3Nodeexperimental
1.3.6.1.4.1.318Nodeapc
1.3.6.1.4.1.318.1NodecommunicationLostSEVERE: Communication to the UPS has been lost. Steps to reestablish communication are in progress.
1.3.6.1.4.1.318.1Nodeproducts
1.3.6.1.4.1.318.1.1Nodehardware
1.3.6.1.4.1.318.1.1.1Nodeups
1.3.6.1.4.1.318.1.1.1.1NodeupsIdent
1.3.6.1.4.1.318.1.1.1.1.1NodeupsBasicIdent
1.3.6.1.4.1.318.1.1.1.1.1.1ScalarupsBasicIdentModelread-onlymandatoryThe UPS model name (e.g. 'APC Smart-UPS 600').
1.3.6.1.4.1.318.1.1.1.1.1.2ScalarupsBasicIdentNameread-writemandatoryAn 8 byte ID string identifying the UPS. This object can be set by the administrator.
1.3.6.1.4.1.318.1.1.1.1.2NodeupsAdvIdent
1.3.6.1.4.1.318.1.1.1.1.2.1ScalarupsAdvIdentFirmwareRevisionread-onlymandatoryThe firmware revision of the UPS system's microprocessor.
1.3.6.1.4.1.318.1.1.1.1.2.2ScalarupsAdvIdentDateOfManufactureread-onlymandatoryThe date when the UPS was manufactured in mm/dd/yy (or yyyy) format.
1.3.6.1.4.1.318.1.1.1.1.2.3ScalarupsAdvIdentSerialNumberread-onlymandatoryAn 8-character string identifying the serial number of the UPS internal microprocessor. This number is set at the factory. NOTE: This number does NOT correspon…
1.3.6.1.4.1.318.1.1.1.1.2.4ScalarupsAdvIdentFirmwareRevision2read-onlymandatoryThe firmware revision of a UPS system co-microprocessor.
1.3.6.1.4.1.318.1.1.1.1.2.5ScalarupsAdvIdentSkuNumberread-onlymandatoryThe SKU number of a UPS system.
1.3.6.1.4.1.318.1.1.1.1.2.6ScalarupsAdvIdentHardwareRevisionread-onlymandatoryThe hardware revision of a UPS system.
1.3.6.1.4.1.318.1.1.1.2NodeupsBattery
1.3.6.1.4.1.318.1.1.1.2.1NodeupsBasicBattery
1.3.6.1.4.1.318.1.1.1.2.1.1ScalarupsBasicBatteryStatusread-onlymandatoryThe status of the UPS batteries. A batteryLow(3) value indicates the UPS will be unable to sustain the current load, and its services will be lost if power is …
1.3.6.1.4.1.318.1.1.1.2.1.2ScalarupsBasicBatteryTimeOnBatteryread-onlymandatoryThe elapsed time since the UPS has switched to battery power.
1.3.6.1.4.1.318.1.1.1.2.1.3ScalarupsBasicBatteryLastReplaceDateread-writemandatoryThe date when the UPS system's batteries were last replaced in mm/dd/yy (or yyyy) format. For Smart-UPS models, this value is originally set in the factory. Wh…
1.3.6.1.4.1.318.1.1.1.2.2NodeupsAdvBattery
1.3.6.1.4.1.318.1.1.1.2.2.1ScalarupsAdvBatteryCapacityread-onlymandatoryThe remaining battery capacity expressed in percent of full capacity.
1.3.6.1.4.1.318.1.1.1.2.2.2ScalarupsAdvBatteryTemperatureread-onlymandatoryThe current internal UPS temperature expressed in Celsius.
1.3.6.1.4.1.318.1.1.1.2.2.3ScalarupsAdvBatteryRunTimeRemainingread-onlymandatoryThe UPS battery run time remaining before battery exhaustion.
1.3.6.1.4.1.318.1.1.1.2.2.4ScalarupsAdvBatteryReplaceIndicatorread-onlymandatoryIndicates whether the UPS batteries need replacing.
1.3.6.1.4.1.318.1.1.1.2.2.5ScalarupsAdvBatteryNumOfBattPacksread-onlymandatoryThe number of external battery packs connected to the UPS. If the UPS does not use smart cells then the agent reports ERROR_NO_SUCH_NAME.
1.3.6.1.4.1.318.1.1.1.2.2.6ScalarupsAdvBatteryNumOfBadBattPacksread-onlymandatoryThe number of external battery packs connected to the UPS that are defective. If the UPS does not use smart cells then the agent reports ERROR_NO_SUCH_NAME.
1.3.6.1.4.1.318.1.1.1.2.2.7ScalarupsAdvBatteryNominalVoltageread-onlymandatoryThe nominal battery voltage in Volts.
1.3.6.1.4.1.318.1.1.1.2.2.8ScalarupsAdvBatteryActualVoltageread-onlymandatoryThe actual battery bus voltage in Volts.
1.3.6.1.4.1.318.1.1.1.2.2.9ScalarupsAdvBatteryCurrentread-onlymandatoryThe battery current in Amps.
1.3.6.1.4.1.318.1.1.1.2.2.10ScalarupsAdvTotalDCCurrentread-onlymandatoryThe total DC current in Amps.
1.3.6.1.4.1.318.1.1.1.2.2.11ScalarupsAdvBatteryFullCapacityread-onlymandatoryThe full chargeable capacity of the battery which is expressed in percentage.
1.3.6.1.4.1.318.1.1.1.2.2.12TableupsAdvBatteryActualVoltageTablenot-accessiblemandatoryA list of battery table entries. The number of battery frames present in UPS.
1.3.6.1.4.1.318.1.1.1.2.2.12.1RowupsAdvBatteryActualVoltageEntrynot-accessiblemandatoryInformation applicable to each of the Battery frames.
1.3.6.1.4.1.318.1.1.1.2.2.12.1.1ColumnupsAdvBatteryActualVoltageTableIndexread-onlymandatoryThe Battery Frame identifier. Battery Frame index.
1.3.6.1.4.1.318.1.1.1.2.2.12.1.2ColumnupsAdvBatteryActualVoltagePolarityread-onlymandatoryThe selected Battery Voltage Polarity. 0 indicates positive polarity. 1 indicates negative polarity.
1.3.6.1.4.1.318.1.1.1.2.2.12.1.3ColumnupsAdvBatteryFrameActualVoltageread-onlymandatoryThe actual battery bus voltage in Volts.
1.3.6.1.4.1.318.1.1.1.2.2.13TableupsAdvTotalDCCurrentTablenot-accessiblemandatoryA list of Battery Frame table entries. The number of entries is given by the value of Number of Battery Frames.
1.3.6.1.4.1.318.1.1.1.2.2.13.1RowupsAdvTotalDCCurrentEntrynot-accessiblemandatoryAn entry containing information applicable to a particular Battery Frame.
1.3.6.1.4.1.318.1.1.1.2.2.13.1.1ColumnupsAdvTotalDCCurrentTableIndexread-onlymandatoryThe Battery Frame identifier. Total DC Current Table Index.
1.3.6.1.4.1.318.1.1.1.2.2.13.1.2ColumnupsAdvTotalDCCurrentPolarityread-onlymandatoryThe selected Battery Current Polarity. 0 indicates positive polarity. 1 indicates negative polarity.
1.3.6.1.4.1.318.1.1.1.2.2.13.1.3ColumnupsAdvTotalFrameDCCurrentread-onlymandatoryThe Total DC Current of battery in Amperes.
1.3.6.1.4.1.318.1.1.1.2.2.14TableupsAdvBatteryCurrentTablenot-accessiblemandatoryA list of Battery Frame table entries. The number of entries is given by number of Battery frames present.
1.3.6.1.4.1.318.1.1.1.2.2.14.1RowupsAdvBatteryCurrentEntrynot-accessiblemandatoryAn entry containing information applicable to a particular battery frame.
1.3.6.1.4.1.318.1.1.1.2.2.14.1.1ColumnupsAdvBatteryCurrentTableIndexread-onlymandatoryThe Battery Frame identifier. Battery Current Table Index.
1.3.6.1.4.1.318.1.1.1.2.2.14.1.2ColumnupsAdvBatteryCurrentIndexread-onlymandatoryThe battery frame identifier.
1.3.6.1.4.1.318.1.1.1.2.2.14.1.3ColumnupsAdvBatteryCurrentPolarityread-onlymandatoryThe selected Battery current polarity. 0 indicates positive polarity. 1 indicates negative polarity
1.3.6.1.4.1.318.1.1.1.2.2.14.1.4ColumnupsAdvBatteryFrameCurrentread-onlymandatoryThe Battery current measured in Amperes
1.3.6.1.4.1.318.1.1.1.2.2.15ScalarupsAdvBatteryEstimatedChargeTimeread-onlymandatoryThe estimated remaining time required to charge the UPS to a full state of charge.
1.3.6.1.4.1.318.1.1.1.2.2.16ScalarupsAdvBatteryPowerread-onlymandatoryThe measured battery power in kW.
1.3.6.1.4.1.318.1.1.1.2.2.17ScalarupsAdvBatteryChargerStatusread-onlymandatoryThe status of the battery charger. If the UPS is unable to find the state of charger, this variable is set to unknown(1).
1.3.6.1.4.1.318.1.1.1.2.2.19ScalarupsAdvBatteryInternalSKUread-onlymandatoryThe SKU of the internal battery.
1.3.6.1.4.1.318.1.1.1.2.2.20ScalarupsAdvBatteryExternalSKUread-onlymandatoryThe SKU of the external battery.
1.3.6.1.4.1.318.1.1.1.2.2.21ScalarupsAdvBatteryRecommendedReplaceDateread-onlymandatoryThe recommended replacement date for the battery based on the UPS internal battery life algorithm.
1.3.6.1.4.1.318.1.1.1.2.2.22ScalarupsAdvBatteryNominalBackupTimeread-onlymandatoryDefines the runtime of the user supplied battery in minutes, when battery is new.
1.3.6.1.4.1.318.1.1.1.2.2.23ScalarupsAdvBatteryConditionread-onlymandatoryHealth of the battries based on the battery test.
1.3.6.1.4.1.318.1.1.1.2.2.24ScalarupsAdvBatteryChargingCurrentRestrictedread-onlymandatoryIndicates whether battery charging current is restricted or not. The value of yes(1) indicates that battery charging current is restricted . The value of no(2)…
1.3.6.1.4.1.318.1.1.1.2.3NodeupsHighPrecBattery
1.3.6.1.4.1.318.1.1.1.2.3.1ScalarupsHighPrecBatteryCapacityread-onlymandatoryThe remaining battery capacity expressed in tenths of percent of full capacity.
1.3.6.1.4.1.318.1.1.1.2.3.2ScalarupsHighPrecBatteryTemperatureread-onlymandatoryThe current internal UPS temperature expressed in tenths of degrees Celsius.
1.3.6.1.4.1.318.1.1.1.2.3.3ScalarupsHighPrecBatteryNominalVoltageread-onlymandatoryThe nominal battery voltage in tenths of Volts.
1.3.6.1.4.1.318.1.1.1.2.3.4ScalarupsHighPrecBatteryActualVoltageread-onlymandatoryThe actual battery bus voltage in tenths of Volts.
1.3.6.1.4.1.318.1.1.1.2.3.5ScalarupsHighPrecBatteryCurrentread-onlymandatoryThe battery current in tenths of Amps.
1.3.6.1.4.1.318.1.1.1.2.3.6ScalarupsHighPrecTotalDCCurrentread-onlymandatoryThe total DC current in tenths of Amps.
1.3.6.1.4.1.318.1.1.1.2.3.7TableupsHighPrecBatteryActualVoltageTablenot-accessiblemandatoryA list of Battery frame table entries. The number of entries is given by the number of Battery frames.
1.3.6.1.4.1.318.1.1.1.2.3.7.1RowupsHighPrecBatteryActualVoltageEntrynot-accessiblemandatoryAn entry containing information applicable to a particular battery frame.
1.3.6.1.4.1.318.1.1.1.2.3.7.1.1ColumnupsHighPrecBatteryActualVoltageTableIndexread-onlymandatoryThe Battery Frame identifier. High Precision Actual Voltage Table Index.
1.3.6.1.4.1.318.1.1.1.2.3.7.1.2ColumnupsHighPrecBatteryActualVoltagePolarityread-onlymandatoryThe selected Battery Voltage polarity. 0 indicates positive polarity. 1 indicates negative polarity.
1.3.6.1.4.1.318.1.1.1.2.3.7.1.3ColumnupsHighPrecBatteryVoltageread-onlymandatoryThe actual battery bus voltage expressed as tenths of Volts.
1.3.6.1.4.1.318.1.1.1.2.3.8TableupsHighPrecTotalDCCurrentTablenot-accessiblemandatoryA list of Battery Frame table entries. The number of entries is given by the number of battery frames.
1.3.6.1.4.1.318.1.1.1.2.3.8.1RowupsHighPrecTotalDCCurrentEntrynot-accessiblemandatoryAn entry containing information applicable to a particular battery frame.
1.3.6.1.4.1.318.1.1.1.2.3.8.1.1ColumnupsHighPrecTotalDCCurrentTableIndexread-onlymandatoryThe Battery Frame identifier. High precision Total DC Current index.
1.3.6.1.4.1.318.1.1.1.2.3.8.1.2ColumnupsHighPrecTotalDCCurrentPolarityread-onlymandatoryThe selected Battery Current polarity. 0 indicates positive polarity. 1 indicates negative polarity.
1.3.6.1.4.1.318.1.1.1.2.3.8.1.3ColumnupsHighPrecTotalDCFrameCurrentread-onlymandatoryThe total DC current in tenths of Amperes.
1.3.6.1.4.1.318.1.1.1.2.3.9TableupsHighPrecBatteryCurrentTablenot-accessiblemandatoryA list of Battery Frame table entries. The number of entries is given by the number of battery frames.
1.3.6.1.4.1.318.1.1.1.2.3.9.1RowupsHighPrecBatteryCurrentEntrynot-accessiblemandatoryAn entry containing information applicable to a particular battery frame.
1.3.6.1.4.1.318.1.1.1.2.3.9.1.1ColumnupsHighPrecBatteryCurrentTableIndexread-onlymandatoryThe Battery frame identifier. Battery Frame index.
1.3.6.1.4.1.318.1.1.1.2.3.9.1.2ColumnupsHighPrecBatteryCurrentIndexread-onlymandatoryThe Battery frame identifier. Battery Index for each frame.
1.3.6.1.4.1.318.1.1.1.2.3.9.1.3ColumnupsHighPrecBatteryCurrentPolarityread-onlymandatoryThe selected Battery Current polarity. 0 indicates positive polarity. 1 indicates negative polarity.
1.3.6.1.4.1.318.1.1.1.2.3.9.1.4ColumnupsHighPrecBatteryFrameCurrentread-onlymandatoryThe Battery current in tenths of Amperes.
1.3.6.1.4.1.318.1.1.1.2.3.10NodeupsHighPrecBatteryPacks
1.3.6.1.4.1.318.1.1.1.2.3.10.1ScalarupsHighPrecBatteryPackTableSizeread-onlymandatoryThe number of entries in the upsHighPrecBatteryPacks.
1.3.6.1.4.1.318.1.1.1.2.3.10.2TableupsHighPrecBatteryPackTablenot-accessiblemandatoryA list of Battery Pack table entries. The number of entries is given by number of Battery Packs present.
1.3.6.1.4.1.318.1.1.1.2.3.10.2.1RowupsHighPrecBatteryPackEntrynot-accessiblemandatoryAn entry containing information applicable to a particular battery pack.
1.3.6.1.4.1.318.1.1.1.2.3.10.2.1.1ColumnupsHighPrecBatteryPackIndexread-onlymandatoryThe battery pack identifier.
1.3.6.1.4.1.318.1.1.1.2.3.10.2.1.2ColumnupsHighPrecBatteryCartridgeIndexread-onlymandatoryThe battery cartridge identifier.
1.3.6.1.4.1.318.1.1.1.2.3.10.2.1.3ColumnupsHighPrecBatteryPackFirmwareRevisionread-onlymandatoryThe battery pack firmware revision.
1.3.6.1.4.1.318.1.1.1.2.3.10.2.1.4ColumnupsHighPrecBatteryPackSerialNumberread-onlymandatoryThe battery pack serial number.
1.3.6.1.4.1.318.1.1.1.2.3.10.2.1.5ColumnupsHighPrecBatteryPackTemperatureread-onlymandatoryThe battery pack temperature measured in 10ths of degree Celcius
1.3.6.1.4.1.318.1.1.1.2.3.10.2.1.6ColumnupsHighPrecBatteryPackStatusread-onlymandatoryThe battery status for the pack only. bit 0 Disconnected bit 1 Overvoltage bit 2 NeedsReplacement bit 3 OvertemperatureCritical bit 4 Charger bit 5 Temperature…
1.3.6.1.4.1.318.1.1.1.2.3.10.2.1.7ColumnupsHighPrecBatteryPackCartridgeHealthread-onlymandatoryThe battery cartridge health. bit 0 Battery lifetime okay bit 1 Battery lifetime near end, order replacement cartridge bit 2 Battery lifetime exceeded, replace…
1.3.6.1.4.1.318.1.1.1.2.3.10.2.1.8ColumnupsHighPrecBatteryPackCartridgeReplaceDateread-onlymandatoryThe battery cartridge estimated battery replace date.
1.3.6.1.4.1.318.1.1.1.2.3.10.2.1.9ColumnupsHighPrecBatteryPackCartridgeInstallDateread-writemandatoryThe battery cartridge install date.
1.3.6.1.4.1.318.1.1.1.2.3.10.2.1.10ColumnupsHighPrecBatteryPackCartridgeStatusread-onlymandatoryThe battery cartridge status. bit 0 Disconnected bit 1 Overvoltage bit 2 NeedsReplacement bit 3 OvertemperatureCritical bit 4 Charger bit 5 TemperatureSensor b…
1.3.6.1.4.1.318.1.1.1.2.3.10.3ScalarupsHighPrecBatteryPackOnlyTableSizeread-onlymandatoryThe number of entries in the upsHighPrecBatteryPacks.
1.3.6.1.4.1.318.1.1.1.2.3.10.4TableupsHighPrecBatteryPackOnlyTablenot-accessiblemandatoryA list of Battery Pack table entries. The number of entries is given by number of Battery Packs present.
1.3.6.1.4.1.318.1.1.1.2.3.10.4.1RowupsHighPrecBatteryPackOnlyEntrynot-accessiblemandatoryAn entry containing information applicable to a particular battery pack.
1.3.6.1.4.1.318.1.1.1.2.3.10.4.1.1ColumnupsHighPrecBatteryPackOnlyIndexread-onlymandatoryThe battery pack identifier.
1.3.6.1.4.1.318.1.1.1.2.3.10.4.1.2ColumnupsHighPrecBatteryPackOnlyFirmwareRevisionread-onlymandatoryThe battery pack firmware revision.
1.3.6.1.4.1.318.1.1.1.2.3.10.4.1.3ColumnupsHighPrecBatteryPackOnlySerialNumberread-onlymandatoryThe battery pack serial number.
1.3.6.1.4.1.318.1.1.1.2.3.10.4.1.4ColumnupsHighPrecBatteryPackOnlyTemperatureread-onlymandatoryThe battery pack temperature measured in 10ths of degree Celcius
1.3.6.1.4.1.318.1.1.1.2.3.10.4.1.5ColumnupsHighPrecBatteryPackOnlyStatusread-onlymandatoryThe battery status for the pack only. bit 0 Disconnected bit 1 Overvoltage bit 2 NeedsReplacement bit 3 OvertemperatureCritical bit 4 Charger bit 5 Temperature…
1.3.6.1.4.1.318.1.1.1.2.3.10.4.1.6ColumnupsHighPrecBatteryPackOnlyHealthread-onlymandatoryThe battery pack health. bit 0 Battery lifetime okay bit 1 Battery lifetime near end, order replacement pack bit 2 Battery lifetime exceeded, replace battery b…
1.3.6.1.4.1.318.1.1.1.2.3.10.4.1.7ColumnupsHighPrecBatteryPackOnlyReplaceDateread-onlymandatoryThe battery pack estimated battery replace date.
1.3.6.1.4.1.318.1.1.1.2.3.10.4.1.8ColumnupsHighPrecBatteryPackOnlyInstallDateread-writemandatoryThe battery pack install date.
1.3.6.1.4.1.318.1.1.1.2.3.11ScalarupsHighPrecBatteryHealthread-onlymandatoryThe battery health. Bit 0 Battery life okay Bit 1 Battery life near end, order battery cartridge Bit 2 Battery life exceeded, replace battery cartridge Bit 3 B…
1.3.6.1.4.1.318.1.1.1.3NodeupsInput
1.3.6.1.4.1.318.1.1.1.3.1NodeupsBasicInput
1.3.6.1.4.1.318.1.1.1.3.1.1ScalarupsBasicInputPhaseread-onlymandatoryThe current AC input phase.
1.3.6.1.4.1.318.1.1.1.3.2NodeupsAdvInput
1.3.6.1.4.1.318.1.1.1.3.2.1ScalarupsAdvInputLineVoltageread-onlymandatoryThe current utility line voltage in VAC.
1.3.6.1.4.1.318.1.1.1.3.2.2ScalarupsAdvInputMaxLineVoltageread-onlymandatoryThe maximum utility line voltage in VAC over the previous 1 minute period.
1.3.6.1.4.1.318.1.1.1.3.2.3ScalarupsAdvInputMinLineVoltageread-onlymandatoryThe minimum utility line voltage in VAC over the previous 1 minute period.
1.3.6.1.4.1.318.1.1.1.3.2.4ScalarupsAdvInputFrequencyread-onlymandatoryThe current input frequency to the UPS system in Hz.
1.3.6.1.4.1.318.1.1.1.3.2.5ScalarupsAdvInputLineFailCauseread-onlymandatoryThe reason for the occurrence of the last transfer to UPS battery power. The variable is set to: - noTransfer(1) - highLineVoltage(2) by an over voltage greate…
1.3.6.1.4.1.318.1.1.1.3.2.6ScalarupsAdvInputNominalFrequencyread-onlymandatoryThe nominal input frequency of the UPS system in Hz.
1.3.6.1.4.1.318.1.1.1.3.2.7ScalarupsAdvInputNominalVoltageread-onlymandatoryThe nominal input voltage of the UPS system in VAC.
1.3.6.1.4.1.318.1.1.1.3.2.8ScalarupsAdvInputBypassNominalFrequencyread-onlymandatoryThe nominal bypass input frequency of the UPS system in Hz.
1.3.6.1.4.1.318.1.1.1.3.2.9ScalarupsAdvInputBypassNominalVoltageread-onlymandatoryThe nominal bypass input voltage of the UPS system in VAC.
1.3.6.1.4.1.318.1.1.1.3.2.10TableupsAdvInputStatisticsTablenot-accessiblemandatoryA list of input table entries. The number of entries is given by the value of upsPhaseNumInputs.
1.3.6.1.4.1.318.1.1.1.3.2.10.1RowupsAdvInputStatisticsEntrynot-accessiblemandatoryAn entry containing information applicable to a particular input.
1.3.6.1.4.1.318.1.1.1.3.2.10.1.1ColumnupsAdvInputStatisticsIndexread-onlymandatoryThe input identifier.
1.3.6.1.4.1.318.1.1.1.3.2.10.1.2ColumnupsAdvInputApparentPowerread-onlymandatoryThe input apparent power(sum of all of the three phases) measured in kVA.
1.3.6.1.4.1.318.1.1.1.3.2.10.1.3ColumnupsAdvInputVoltageTHDread-onlymandatoryThe input voltage Total Harmonic Distortion in percent.
1.3.6.1.4.1.318.1.1.1.3.2.10.1.4ColumnupsAdvInputBypassVoltageTHDread-onlymandatoryThe bypass input voltage Total Harmonic Distortion in percent.
1.3.6.1.4.1.318.1.1.1.3.2.10.1.5ColumnupsAdvInputPeakCurrentread-onlymandatoryThe input peak current in Amperes.
1.3.6.1.4.1.318.1.1.1.3.2.10.1.6ColumnupsAdvInputBypassPeakCurrentread-onlymandatoryThe bypass input peak current in Amperes.
1.3.6.1.4.1.318.1.1.1.3.2.10.1.7ColumnupsAdvInputActivePowerread-onlymandatoryThe input active power measured in kW.
1.3.6.1.4.1.318.1.1.1.3.2.11ScalarupsAdvInputTotalApparentPowerread-onlymandatoryThe input total apparent power(sum of all three phases) of the UPS system in kVA.
1.3.6.1.4.1.318.1.1.1.3.2.12ScalarupsAdvInputTotalActivePowerread-onlymandatoryThe input total active power(sum of all three phases) of the UPS system in kW.
1.3.6.1.4.1.318.1.1.1.3.2.13ScalarupsAdvInputBypassTotalApparentPowerread-onlymandatoryThe input bypass total apparent power(sum of all three phases) of the UPS system in kVA.
1.3.6.1.4.1.318.1.1.1.3.2.14ScalarupsAdvInputBypassTotalActivePowerread-onlymandatoryThe input bypass total active power(sum of all three phases) of the UPS system in kW.
1.3.6.1.4.1.318.1.1.1.3.2.15ScalarupsAdvInputEnergyUsageread-onlymandatoryThe input energy usage of the UPS in kWh.
1.3.6.1.4.1.318.1.1.1.3.3NodeupsHighPrecInput
1.3.6.1.4.1.318.1.1.1.3.3.1ScalarupsHighPrecInputLineVoltageread-onlymandatoryThe current utility line voltage in tenths of VAC.
1.3.6.1.4.1.318.1.1.1.3.3.2ScalarupsHighPrecInputMaxLineVoltageread-onlymandatoryThe maximum utility line voltage in tenths of VAC over the previous 1 minute period.
1.3.6.1.4.1.318.1.1.1.3.3.3ScalarupsHighPrecInputMinLineVoltageread-onlymandatoryThe minimum utility line voltage in tenths of VAC over the previous 1 minute period.
1.3.6.1.4.1.318.1.1.1.3.3.4ScalarupsHighPrecInputFrequencyread-onlymandatoryThe current input frequency to the UPS system in tenths of Hz.
1.3.6.1.4.1.318.1.1.1.3.3.5ScalarupsHighPrecInputEnergyUsageread-onlymandatoryThe input energy usage of the UPS in hundredths of kWh.
1.3.6.1.4.1.318.1.1.1.3.3.6ScalarupsHighPrecInputBypassVoltageread-onlymandatoryThe current bypass line voltage in tenths of VAC.
1.3.6.1.4.1.318.1.1.1.3.3.7ScalarupsHighPrecInputBypassFrequencyread-onlymandatoryThe current input bypass frequency to the UPS system in tenths of Hz.
1.3.6.1.4.1.318.1.1.1.4NodeupsOutput
1.3.6.1.4.1.318.1.1.1.4.1NodeupsBasicOutput
1.3.6.1.4.1.318.1.1.1.4.1.1ScalarupsBasicOutputStatusread-onlymandatoryThe current state of the UPS. If the UPS is unable to determine the state of the UPS this variable is set to unknown(1).
1.3.6.1.4.1.318.1.1.1.4.1.2ScalarupsBasicOutputPhaseread-onlymandatoryThe current output phase.
1.3.6.1.4.1.318.1.1.1.4.1.3ScalarupsBasicSystemStatusread-onlymandatoryCurrent state for the whole system (UPS and surrounding breakers). If the UPS is unable to determine the state of the system, this variable is set to unknown(1…
1.3.6.1.4.1.318.1.1.1.4.1.4ScalarupsBasicSystemInternalTemperatureread-onlymandatoryThe actual internal temperature of the UPS system in Celsius.
1.3.6.1.4.1.318.1.1.1.4.1.5ScalarupsBasicSystemInverterStatusread-onlymandatoryThe current state of the UPS inverter. If the UPS is unable to determine the state of the inverter, this variable is set to unknown(1).
1.3.6.1.4.1.318.1.1.1.4.1.6ScalarupsBasicSystemPFCStatusread-onlymandatoryThe general status of the power factor correction (AC input stage of the UPS). If the UPS is unable to determine the state of PFC, this variable is set to unkn…
1.3.6.1.4.1.318.1.1.1.4.1.7ScalarupsBasicOutputACwiringConfigurationread-onlymandatoryIndicates if neutral wire on output side of the UPS is used (load wired line to neutral). If the UPS is unable to determine the state of neutral, this variable…
1.3.6.1.4.1.318.1.1.1.4.2NodeupsAdvOutput
1.3.6.1.4.1.318.1.1.1.4.2.1ScalarupsAdvOutputVoltageread-onlymandatoryThe output voltage of the UPS system in VAC.
1.3.6.1.4.1.318.1.1.1.4.2.2ScalarupsAdvOutputFrequencyread-onlymandatoryThe current output frequency of the UPS system in Hz.
1.3.6.1.4.1.318.1.1.1.4.2.3ScalarupsAdvOutputLoadread-onlymandatoryThe current UPS load expressed in percent of rated capacity.
1.3.6.1.4.1.318.1.1.1.4.2.4ScalarupsAdvOutputCurrentread-onlymandatoryThe current in amperes drawn by the load on the UPS.
1.3.6.1.4.1.318.1.1.1.4.2.5ScalarupsAdvOutputRedundancyread-onlymandatoryThe number of power modules which can fail or be removed without causing the UPS to generate a Minimum Redundancy Lost event.
1.3.6.1.4.1.318.1.1.1.4.2.6ScalarupsAdvOutputKVACapacityread-onlymandatoryThe maximum load that this UPS can support.
1.3.6.1.4.1.318.1.1.1.4.2.7ScalarupsAdvOutputNominalFrequencyread-onlymandatoryThe nominal output frequency of the UPS system in Hz.
1.3.6.1.4.1.318.1.1.1.4.2.8ScalarupsAdvOutputActivePowerread-onlymandatoryThe total output active power of the UPS system in W. The total active power is the sum of phase 1, phase 2 and phase 3 power.
1.3.6.1.4.1.318.1.1.1.4.2.9ScalarupsAdvOutputApparentPowerread-onlymandatoryThe total output apparent power of all phases of the UPS system in VA.
1.3.6.1.4.1.318.1.1.1.4.2.10TableupsAdvOutputStatisticsTablenot-accessiblemandatoryA list of input table entries. The number of entries is given by the value of upsPhaseNumOutputs.
1.3.6.1.4.1.318.1.1.1.4.2.10.1RowupsAdvOutputStatisticsEntrynot-accessiblemandatoryAn entry containing information applicable to a particular output.
1.3.6.1.4.1.318.1.1.1.4.2.10.1.1ColumnupsAdvOutputStatisticsIndexread-onlymandatoryThe output identifier.
1.3.6.1.4.1.318.1.1.1.4.2.10.1.2ColumnupsAdvOutputPeakCurrentread-onlymandatoryThe output peak current in Amperes.
1.3.6.1.4.1.318.1.1.1.4.2.10.1.3ColumnupsAdvOutputCurrentTHDread-onlymandatoryThe output current Total Harmonic Distortion in percent.
1.3.6.1.4.1.318.1.1.1.4.2.10.1.4ColumnupsAdvOutputCrestFactorread-onlymandatoryThe output current crest factor expressed in tenths.
1.3.6.1.4.1.318.1.1.1.4.2.11ScalarupsAdvOutputNeutralCurrentread-onlymandatoryThe neutral current in amperes.
1.3.6.1.4.1.318.1.1.1.4.2.12ScalarupsAdvOutputEnergyUsageread-onlymandatoryThe output energy usage of the UPS in kWh.
1.3.6.1.4.1.318.1.1.1.4.2.13ScalarupsAdvOutputSourceSynchronizationread-onlymandatoryIndicates the synchronization source for the inverter output frequency. 1. Main 2. Internal 3. External 4. On AC Bypass. 5. External / On Bypass For other valu…
1.3.6.1.4.1.318.1.1.1.4.2.14ScalarupsAdvOutputInverterFrequencyread-onlymandatoryOutput frequency in Hz measured at the output of inverter.
1.3.6.1.4.1.318.1.1.1.4.3NodeupsHighPrecOutput
1.3.6.1.4.1.318.1.1.1.4.3.1ScalarupsHighPrecOutputVoltageread-onlymandatoryThe output voltage of the UPS system in tenths of VAC.
1.3.6.1.4.1.318.1.1.1.4.3.2ScalarupsHighPrecOutputFrequencyread-onlymandatoryThe current output frequency of the UPS system in tenths of Hz.
1.3.6.1.4.1.318.1.1.1.4.3.3ScalarupsHighPrecOutputLoadread-onlymandatoryThe current UPS load expressed in tenths of percent of rated capacity.
1.3.6.1.4.1.318.1.1.1.4.3.4ScalarupsHighPrecOutputCurrentread-onlymandatoryThe current in tenths of amperes drawn by the load on the UPS.
1.3.6.1.4.1.318.1.1.1.4.3.5ScalarupsHighPrecOutputEfficiencyread-onlymandatoryThe positive values represent efficiency of the UPS in tenths of percent. -1 If UPS supports this OID but the result is not available -2 Load is too low to rep…
1.3.6.1.4.1.318.1.1.1.4.3.6ScalarupsHighPrecOutputEnergyUsageread-onlymandatoryThe output energy usage of the UPS in hundredths of kWh.
1.3.6.1.4.1.318.1.1.1.5NodeupsConfig
1.3.6.1.4.1.318.1.1.1.5.1NodeupsBasicConfig
1.3.6.1.4.1.318.1.1.1.5.1.1ScalarupsBasicConfigNumDevicesread-onlymandatoryThe number of devices that are plugged into the UPS. This value is customer configurable from the device entry table
1.3.6.1.4.1.318.1.1.1.5.1.2TableupsBasicConfigDeviceTablenot-accessiblemandatoryA list of devices that are plugged into the UPS. The number of entries is given by the value of upsBasicConfigNumDevices.
1.3.6.1.4.1.318.1.1.1.5.1.2.1RowupsBasicConfigDeviceEntrynot-accessiblemandatoryThe devices plugged in to the UPS.
1.3.6.1.4.1.318.1.1.1.5.1.2.1.1ColumndeviceIndexread-onlymandatoryThe index of the device that is plugged into the UPS.
1.3.6.1.4.1.318.1.1.1.5.1.2.1.2ColumndeviceNameread-writemandatoryThe name/description of the device plugged into the UPS.
1.3.6.1.4.1.318.1.1.1.5.1.2.1.3ColumnvaRatingread-writemandatoryThe volt-amp rating of the device plugged into the UPS.
1.3.6.1.4.1.318.1.1.1.5.1.2.1.4ColumnacceptThisDeviceread-writemandatoryAn entry is added if yes, the entry is deleted if no.
1.3.6.1.4.1.318.1.1.1.5.2NodeupsAdvConfig
1.3.6.1.4.1.318.1.1.1.5.2.1ScalarupsAdvConfigRatedOutputVoltageread-writemandatoryThe nominal output voltage from the UPS in VAC. For a list of allowed values supported by your UPS model, see the UPS User's Manual. If a value other than a su…
1.3.6.1.4.1.318.1.1.1.5.2.2ScalarupsAdvConfigHighTransferVoltread-writemandatoryThe maximum line voltage in VAC allowed before the UPS system transfers to battery backup. For a list of allowed values supported by your UPS model, see the UP…
1.3.6.1.4.1.318.1.1.1.5.2.3ScalarupsAdvConfigLowTransferVoltread-writemandatoryThe minimum line voltage in VAC allowed before the UPS system transfers to battery backup. For a list of allowed values supported by your UPS model, see the UP…
1.3.6.1.4.1.318.1.1.1.5.2.4ScalarupsAdvConfigAlarmread-writemandatoryA flag indicating how the UPS should handle audible line fail alarms: timed(1): UPS alarm will sound after a preset timed duration starting from the line fail …
1.3.6.1.4.1.318.1.1.1.5.2.5ScalarupsAdvConfigAlarmTimerread-writemandatoryThe time after initial line failure at which the UPS begins emitting audible alarms (beeping). This timer is observed only if the value of extControlAlarm is t…
1.3.6.1.4.1.318.1.1.1.5.2.6ScalarupsAdvConfigMinReturnCapacityread-writemandatoryThe minimum battery capacity required before the UPS will return from a low battery shutdown condition. The capacity is measured from 0% battery capacity (or L…
1.3.6.1.4.1.318.1.1.1.5.2.7ScalarupsAdvConfigSensitivityread-writemandatoryThe sensitivity of the UPS to utility line abnormalities or noises.
1.3.6.1.4.1.318.1.1.1.5.2.8ScalarupsAdvConfigLowBatteryRunTimeread-writemandatoryThe desired run time of the UPS, in seconds, once the low battery condition is reached. During this time the UPS will produce a constant warning tone which can…
1.3.6.1.4.1.318.1.1.1.5.2.9ScalarupsAdvConfigReturnDelayread-writemandatoryThe delay in seconds after utility line power returns before the UPS will turn on. This value is also used when the UPS comes out of a reboot and before the UP…
1.3.6.1.4.1.318.1.1.1.5.2.10ScalarupsAdvConfigShutoffDelayread-writemandatoryThe delay in seconds the UPS remains on after being told to turn off. For a list of allowed values supported by your UPS model, see the UPS User's Manual. If a…
1.3.6.1.4.1.318.1.1.1.5.2.11ScalarupsAdvConfigUpsSleepTimeread-writemandatoryThe time in seconds for the UPS to go to 'sleep' when instructed. When in sleep mode, the UPS will not provide output power regardless of the input line state.…
1.3.6.1.4.1.318.1.1.1.5.2.12ScalarupsAdvConfigSetEEPROMDefaultsread-writemandatoryWRITE: Resets the UPS EEPROM variables to default values. READ: returns 1
1.3.6.1.4.1.318.1.1.1.5.2.13TableupsAdvConfigDipSwitchTablenot-accessiblemandatoryCurrent settings of UPS dip switches.
1.3.6.1.4.1.318.1.1.1.5.2.13.1RowupsAdvConfigDipSwitchEntrynot-accessiblemandatoryThe current setting of one dip switch.
1.3.6.1.4.1.318.1.1.1.5.2.13.1.1ColumndipSwitchIndexread-onlymandatoryThe index of a UPS dip switch.
1.3.6.1.4.1.318.1.1.1.5.2.13.1.2ColumndipSwitchStatusread-onlymandatoryThe setting of a UPS dip switch.
1.3.6.1.4.1.318.1.1.1.5.2.14ScalarupsAdvConfigBattExhaustThreshread-writemandatoryThe number of seconds prior to battery exhaustion when the UPS will switch off power to its load.
1.3.6.1.4.1.318.1.1.1.5.2.15ScalarupsAdvConfigPasswordread-writemandatoryThe password entered at the UPS front panel to enable local configuration of the EEProm. If the password is disabled or is not supported, then the agent return…
1.3.6.1.4.1.318.1.1.1.5.2.16TableupsAdvConfigAllowedSetTablenot-accessiblemandatoryThe table listing the allowed values for all discrete configurable UPS variables.
1.3.6.1.4.1.318.1.1.1.5.2.16.1RowupsAdvConfigAllowedSetEntrynot-accessiblemandatoryThe table entry for a configurable UPS variable.
1.3.6.1.4.1.318.1.1.1.5.2.16.1.1ColumnapcUpsConfigFieldIndexread-onlymandatoryThe index to an eeprom field entry.
1.3.6.1.4.1.318.1.1.1.5.2.16.1.2ColumnapcUpsConfigFieldOIDread-onlymandatoryThe OID of the current configurable value.
1.3.6.1.4.1.318.1.1.1.5.2.16.1.3ColumnapcUpsConfigFieldValueRangeread-onlymandatoryThe discrete set of allowed values of a configurable register. Individual values are delimited by a comma.
1.3.6.1.4.1.318.1.1.1.5.2.17ScalarupsAdvConfigBattCabAmpHourread-writemandatoryConfigure the amp-hour setting of the UPS battery cabinet.
1.3.6.1.4.1.318.1.1.1.5.2.18ScalarupsAdvConfigPositionSelectorread-writemandatoryConfigure UPS position selector. If the UPS doesn't support this configuration it will report unknown (1). The positions are either rack (2) for rack mounted o…
1.3.6.1.4.1.318.1.1.1.5.2.19ScalarupsAdvConfigOutputFreqRangeread-writemandatoryConfigure the output frequency tolerance range. unknown(1) indicates the output frequency is unknown. freqRangeAUTO(2) configure the output frequency range for…
1.3.6.1.4.1.318.1.1.1.5.2.20ScalarupsAdvConfigUPSFailread-writemandatoryConfigure the UPS fail action. If UPS fails, and frequency or voltage is out of range it will either GotoBypass (2) or DropLoad (3). This OID will report unkno…
1.3.6.1.4.1.318.1.1.1.5.2.21ScalarupsAdvConfigAlarmRedundancyread-writemandatoryConfigure settings of UPS alarm if the redundancy is under the current redundancy. Use 0 for never.
1.3.6.1.4.1.318.1.1.1.5.2.22ScalarupsAdvConfigAlarmLoadOverread-writemandatoryConfigure settings of UPS alarm if the load is over the current load in kVA. Use -1 for never.
1.3.6.1.4.1.318.1.1.1.5.2.23ScalarupsAdvConfigAlarmRuntimeUnderread-writemandatoryConfigure settings of UPS alarm if the runtime is under the current time of minutes. Use -1 for never.
1.3.6.1.4.1.318.1.1.1.5.2.24ScalarupsAdvConfigVoutReportingread-writemandatoryConfigure the way the UPS scales its output voltage readings. unknown(1) indicates the Vout Reporting is unknown. voutAUTO(2) configure the Vout Reporting for …
1.3.6.1.4.1.318.1.1.1.5.2.25ScalarupsAdvConfigNumExternalBatteriesread-writemandatoryConfigure the number of external batteries connected to the UPS.
1.3.6.1.4.1.318.1.1.1.5.2.26ScalarupsAdvConfigSimpleSignalShutdownsread-writemandatoryConfigure Simple Signal shutdown commands from the Simple Signal port to be issued to the UPS. unknown(1) indicates the Simple Signal Shutdown setting is unkno…
1.3.6.1.4.1.318.1.1.1.5.2.27ScalarupsAdvConfigMaxShutdownTimeread-writemandatoryThe maximum amount of time for server shutdown to complete before a UPS shutdown occurs.
1.3.6.1.4.1.318.1.1.1.5.2.28ScalarupsAsiUpsControlServerRequestShutdownread-writemandatoryStart a server shutdown sequence: serverShutdownOff: Shutdown server and turn off UPS serverShutdownReboot: Shutdown server and turn reboot UPS.
1.3.6.1.4.1.318.1.1.1.5.2.29ScalarupsAdvConfigMinReturnRuntimeread-writemandatoryThe minimum amount of run time in seconds required before the output will be turned on, using power calculation captured at start of last shutdown.
1.3.6.1.4.1.318.1.1.1.5.2.30ScalarupsAdvConfigBasicSignalLowBatteryDurationread-writemandatoryThe duration of runtime in seconds during an on-battery condition at which the UPS will signal the basic low battery shutdown condition.
1.3.6.1.4.1.318.1.1.1.5.2.31ScalarupsAdvConfigBypassPhaseLockRequiredread-writemandatorySets the condition for when bypass is an acceptable mode of operation as a requirement.
1.3.6.1.4.1.318.1.1.1.5.2.32ScalarupsAdvConfigOutputFreqSlewRateread-writemandatoryThe rate at which the UPS will change its output frequency in response to utility frequency changes.
1.3.6.1.4.1.318.1.1.1.5.2.33ScalarupsAdvConfigChargerLevelread-writemandatorySets the rate at which the UPS charges its batteries.
1.3.6.1.4.1.318.1.1.1.5.2.34ScalarupsAdvConfigBypassToleranceSettingread-writemandatoryThis setting allows selecting from standard bypass tolerance configurations to suit their situation.
1.3.6.1.4.1.318.1.1.1.5.2.35ScalarupsAdvConfigMainsSettingread-onlymandatoryConfigure the type of mains supply system. singleInput (1) indicates a single supply system. dualInput (2) indicates a dual supply system.
1.3.6.1.4.1.318.1.1.1.5.2.36ScalarupsAdvConfigACWiringSettingread-onlymandatoryConfigure the AC wiring of the system. threeWire (1) indicates 3-wire system configuration. fourWire (2) indicates 4-wire system configuration.
1.3.6.1.4.1.318.1.1.1.5.2.37ScalarupsAdvConfigUpperOutputVoltToleranceread-writemandatoryUpper tolerance of the output RMS voltage before transferring to bypass. Expressed as percent of nominal voltage.
1.3.6.1.4.1.318.1.1.1.5.2.38ScalarupsAdvConfigLowerOutputVoltToleranceread-writemandatoryLower tolerance of the output RMS voltage before transferring to bypass. Expressed as percent of nominal voltage.
1.3.6.1.4.1.318.1.1.1.5.2.39ScalarupsAdvConfigUpperBypassVoltToleranceread-writemandatoryUpper tolerance of the bypass voltage that allows transfer to bypass by user. Expressed as percent of nominal voltage.
1.3.6.1.4.1.318.1.1.1.5.2.40ScalarupsAdvConfigLowerBypassVoltToleranceread-writemandatoryLower tolerance of the bypass voltage that allows transfer to bypass by user. Expressed as percent of nominal voltage.
1.3.6.1.4.1.318.1.1.1.5.2.41ScalarupsAdvConfigOutofSyncBypassTransferDelayread-writemandatoryConfigure the time (in milliseconds), indicating the gap in output voltage if an asynchronous transfer to bypass needs to occur.
1.3.6.1.4.1.318.1.1.1.5.2.43ScalarupsAdvConfigWarningAlarmDelayread-writemandatoryConfigure the time delay for reporting warning alarms (in seconds).
1.3.6.1.4.1.318.1.1.1.5.2.44ScalarupsAdvConfigInformationalAlarmDelayread-writemandatoryConfigure the time delay for reporting informational alarms (in seconds).
1.3.6.1.4.1.318.1.1.1.5.2.45ScalarupsAdvConfigGreenModeread-writemandatoryEnable/Disable UPS green mode feature.
1.3.6.1.4.1.318.1.1.1.5.2.46ScalarupsAdvConfigLCDLocalLanguageread-writemandatoryConfigure the language setting of the UPS LCD display information.
1.3.6.1.4.1.318.1.1.1.5.2.47ScalarupsAdvConfigLCDLockOutread-writemandatoryEnable/Disable the control function of the UPS via the LCD Display.
1.3.6.1.4.1.318.1.1.1.5.2.48ScalarupsAdvConfigChargerRateread-writemandatoryChange the maximum allowed UPS charge rate on select products where 100% represents the manufacturer's recommended rate. A charge/discharge rate of C/10 for a …
1.3.6.1.4.1.318.1.1.1.5.2.49ScalarupsAdvConfigBatterySelectionread-writemandatoryConfigure the installed battery type on select products where VRLA is Valve Regulated Lead Acid type battery, Vented Cell is a wet cell type (car) battery, NiC…
1.3.6.1.4.1.318.1.1.1.5.2.50ScalarupsAdvConfigBatteryHealthAlarmWarningTimeread-writemandatoryConfigure the number of days before the battery health is depleted that the battery health alarm is activated. Setting this to -1, if supported by the UPS, wil…
1.3.6.1.4.1.318.1.1.1.5.2.51ScalarupsAdvConfigBatteryHealthAlarmSleepTimeread-writemandatoryConfigure the number of days that the UPS's battery health alarm should sleep before being activated again after being acknowledged. Setting this to -1, if sup…
1.3.6.1.4.1.318.1.1.1.5.2.52ScalarupsAdvConfigSignalFlashVoltageread-writemandatoryConfigure the signal flash voltage in tenths of volts.
1.3.6.1.4.1.318.1.1.1.5.2.53ScalarupsAdvConfigBatteryTemperatureCompensationread-writemandatoryConfigure the battery temperature compensation voltage in hundreds of volts per degree C. On products which support this field, the charger voltage is reduced …
1.3.6.1.4.1.318.1.1.1.5.2.54ScalarupsAdvConfigBatteryChargerTyperead-writemandatoryThis OID describes type of battery charger used: standard or extended. 1 - Internal charger, 2 - Extended (CLA), 3 - Large extension (other cases), 4 - Extra l…
1.3.6.1.4.1.318.1.1.1.5.2.55ScalarupsAdvConfigAutomaticRestartread-writemandatoryIndicates whether Automatic Restart is enabled or disabled.
1.3.6.1.4.1.318.1.1.1.5.2.56ScalarupsAdvConfigDeepDischargeProtectionread-writemandatoryIndicates whether protection against deep discharge is enabled or disabled.
1.3.6.1.4.1.318.1.1.1.5.2.57ScalarupsAdvConfigFreqBypassTransferRangeread-writemandatoryTolerance of bypass AC frequency to switch on bypass. The frequency must be in range of -X% to +X% around the nominal value.
1.3.6.1.4.1.318.1.1.1.5.2.58ScalarupsAdvConfigUpsPowerconverterTyperead-writemandatoryThis value indicates the type of UPS in terms of output phase and redundancy. 2 - Galaxy 7000 Unitary 3:3 3 - Galaxy 7000 Redundant 3:3 4 - Galaxy 7000 Paralle…
1.3.6.1.4.1.318.1.1.1.5.2.59ScalarupsAdvConfigFrequencyConverterModeread-writemandatoryIndicates whether the output frequency is in Auto Ranging or Frequency converter mode. In Auto Ranging mode the inverter provides output frequency in the same …
1.3.6.1.4.1.318.1.1.1.5.2.60ScalarupsAdvConfigACQualificationTimeread-writemandatoryThe time in seconds that the voltage is required to be in the acceptable range before being declared to be acceptable.
1.3.6.1.4.1.318.1.1.1.6NodeupsControl
1.3.6.1.4.1.318.1.1.1.6.1NodeupsBasicControl
1.3.6.1.4.1.318.1.1.1.6.1.1ScalarupsBasicControlConserveBatteryread-writemandatorySetting this variable to turnUpsOffToConserveBattery(2) causes a UPS on battery to be put into 'sleep' mode. The UPS will turn back on when utility power is re…
1.3.6.1.4.1.318.1.1.1.6.2NodeupsAdvControl
1.3.6.1.4.1.318.1.1.1.6.2.1ScalarupsAdvControlUpsOffread-writemandatorySetting this variable to turnUpsOff(2) causes the UPS to shut off. When in this state, the UPS will not provide output power regardless of the input line state…
1.3.6.1.4.1.318.1.1.1.6.2.2ScalarupsAdvControlRebootShutdownUpsread-writemandatorySetting this variable to rebootShutdownUps(2) causes the UPS to shut off and turn back on (as long as good AC input power is available, otherwise the UPS will …
1.3.6.1.4.1.318.1.1.1.6.2.3ScalarupsAdvControlUpsSleepread-writemandatorySetting this variable to putUpsToSleep(2) causes the UPS to go to sleep for the time specified by upsAdvConfigUpsSleepTime. Setting this variable to putUpsToSl…
1.3.6.1.4.1.318.1.1.1.6.2.4ScalarupsAdvControlSimulatePowerFailread-writemandatorySetting this variable to simulatePowerFailure(2) causes the UPS switch to battery power. Setting this value to noSimulatePowerFailure(1) has no effect. The val…
1.3.6.1.4.1.318.1.1.1.6.2.5ScalarupsAdvControlFlashAndBeepread-writemandatorySetting this variable to flashAndBeep(2) causes the UPS to beep and simultaneously turn on the UPS front panel lights (Smart-UPS only). If this UPS is an activ…
1.3.6.1.4.1.318.1.1.1.6.2.6ScalarupsAdvControlTurnOnUPSread-writemandatorySetting this variable to turnOnUPS(2) causes the UPS to be turned on immediately. If this UPS is an active member of a Synchronized Control Group (SCG), the tu…
1.3.6.1.4.1.318.1.1.1.6.2.7ScalarupsAdvControlBypassSwitchread-writemandatoryThis switch puts the UPS in or out of bypass mode.
1.3.6.1.4.1.318.1.1.1.6.2.8ScalarupsAdvControlRebootUpsWithOrWithoutACread-writemandatorySetting this variable to rebootUpsImmediatelyWithOrWithoutAC (2) causes the UPS to turn off immediately, wait for a minimum time (typically 8 seconds), and the…
1.3.6.1.4.1.318.1.1.1.6.2.9ScalarupsAdvControlFirmwareUpdateread-writemandatorySetting this variable to firmwareUpdate(2) causes the UPS to begin a firmware update if possible. Setting this value to noFirmwareUpdate(1) will clear the prev…
1.3.6.1.4.1.318.1.1.1.7NodeupsTest
1.3.6.1.4.1.318.1.1.1.7.1NodeupsBasicTest
1.3.6.1.4.1.318.1.1.1.7.2NodeupsAdvTest
1.3.6.1.4.1.318.1.1.1.7.2.1ScalarupsAdvTestDiagnosticScheduleread-writemandatoryThe UPS system's automatic battery test schedule.
1.3.6.1.4.1.318.1.1.1.7.2.2ScalarupsAdvTestDiagnosticsread-writemandatorySetting this variable to testDiagnostics(2) causes the UPS to perform a diagnostic self test. Setting this value to noTestDiagnostics(1) has no effect. The val…
1.3.6.1.4.1.318.1.1.1.7.2.3ScalarupsAdvTestDiagnosticsResultsread-onlymandatoryThe results of the last UPS diagnostics test performed.
1.3.6.1.4.1.318.1.1.1.7.2.4ScalarupsAdvTestLastDiagnosticsDateread-onlymandatoryThe date the last UPS diagnostics test was performed in mm/dd/yy format.
1.3.6.1.4.1.318.1.1.1.7.2.5ScalarupsAdvTestRuntimeCalibrationread-writemandatorySetting this variable to performCalibration(2) causes the UPS to discharge to calibrate the UPS. The test will only start if the battery capacity is 100%. The …
1.3.6.1.4.1.318.1.1.1.7.2.6ScalarupsAdvTestCalibrationResultsread-onlymandatoryThe results of the last runtime calibration. Value ok(1) means a successful runtime calibration. Value invalidCalibration(2) indicates last calibration did not…
1.3.6.1.4.1.318.1.1.1.7.2.7ScalarupsAdvTestCalibrationDateread-onlymandatoryThe date the last UPS runtime calibration was performed in mm/dd/yy format.
1.3.6.1.4.1.318.1.1.1.7.2.8ScalarupsAdvTestDiagnosticTimeread-writemandatoryThe time of the day to perform automatic battery test. Expressed in 24 hour notation - hh:mm.
1.3.6.1.4.1.318.1.1.1.7.2.9ScalarupsAdvTestDiagnosticDayread-writemandatoryThe day of the week to perform automatic battery test.
1.3.6.1.4.1.318.1.1.1.7.2.10ScalarupsAdvTestBatteryIntervalread-writemandatoryThe UPS system's automatic battery test period.
1.3.6.1.4.1.318.1.1.1.8NodeupsComm
1.3.6.1.4.1.318.1.1.1.8.1ScalarupsCommStatusread-onlymandatoryThe status of agent's communication with UPS.
1.3.6.1.4.1.318.1.1.1.9NodeupsPhase
1.3.6.1.4.1.318.1.1.1.9.1NodeupsPhaseResetValues
1.3.6.1.4.1.318.1.1.1.9.1.1ScalarupsPhaseResetMaxMinValuesread-writemandatoryReset the maximum and minimum UPS values: upsPhaseInputMaxVoltage, upsPhaseInputMinVoltage, upsPhaseInputMaxCurrent, upsPhaseInputMinCurrent, upsPhaseInputMaxP…
1.3.6.1.4.1.318.1.1.1.9.2NodeupsPhaseInput
1.3.6.1.4.1.318.1.1.1.9.2.1ScalarupsPhaseNumInputsread-onlymandatoryThe number of input feeds to this device. This variable indicates the number of rows in the input table.
1.3.6.1.4.1.318.1.1.1.9.2.2TableupsPhaseInputTablenot-accessiblemandatoryA list of input table entries. The number of entries is given by the value of upsPhaseNumInputs.
1.3.6.1.4.1.318.1.1.1.9.2.2.1RowupsPhaseInputEntrynot-accessiblemandatoryAn entry containing information applicable to a particular input.
1.3.6.1.4.1.318.1.1.1.9.2.2.1.1ColumnupsPhaseInputTableIndexread-onlymandatoryThe input identifier.
1.3.6.1.4.1.318.1.1.1.9.2.2.1.2ColumnupsPhaseNumInputPhasesread-onlymandatoryThe number of input phases utilized in this device. The sum of all the upsPhaseNumInputPhases variable indicates the number of rows in the input phase table.
1.3.6.1.4.1.318.1.1.1.9.2.2.1.3ColumnupsPhaseInputVoltageOrientationread-onlymandatoryThe input voltage orientation: 1: unknown for this UPS 2: singlePhase - phase 1 voltage is between Phase 1 and Neutral. 3: splitPhase - phase 1 voltage is betw…
1.3.6.1.4.1.318.1.1.1.9.2.2.1.4ColumnupsPhaseInputFrequencyread-onlymandatoryThe input frequency in 0.1 Hertz, or -1 if it's unsupported by this UPS.
1.3.6.1.4.1.318.1.1.1.9.2.2.1.5ColumnupsPhaseInputTyperead-onlymandatoryThe input type.
1.3.6.1.4.1.318.1.1.1.9.2.2.1.6ColumnupsPhaseInputNameread-writemandatoryA name given to a particular input.
1.3.6.1.4.1.318.1.1.1.9.2.3TableupsPhaseInputPhaseTablenot-accessiblemandatoryA list of input table entries. The number of entries is given by the sum of the upsPhaseNumInputPhases.
1.3.6.1.4.1.318.1.1.1.9.2.3.1RowupsPhaseInputPhaseEntrynot-accessiblemandatoryAn entry containing information applicable to a particular input phase.
1.3.6.1.4.1.318.1.1.1.9.2.3.1.1ColumnupsPhaseInputPhaseTableIndexread-onlymandatoryThe input identifier.
1.3.6.1.4.1.318.1.1.1.9.2.3.1.2ColumnupsPhaseInputPhaseIndexread-onlymandatoryThe input phase identifier.
1.3.6.1.4.1.318.1.1.1.9.2.3.1.3ColumnupsPhaseInputVoltageread-onlymandatoryThe input voltage in VAC, or -1 if it's unsupported by this UPS.
1.3.6.1.4.1.318.1.1.1.9.2.3.1.4ColumnupsPhaseInputMaxVoltageread-onlymandatoryThe maximum input voltage in VAC measured since the last reset (upsPhaseResetMaxMinValues), or -1 if it's unsupported by this UPS. Sampled every 30 seconds.
1.3.6.1.4.1.318.1.1.1.9.2.3.1.5ColumnupsPhaseInputMinVoltageread-onlymandatoryThe minimum input voltage in VAC measured since the last reset (upsPhaseResetMaxMinValues), or -1 if it's unsupported by this UPS. Sampled every 30 seconds.
1.3.6.1.4.1.318.1.1.1.9.2.3.1.6ColumnupsPhaseInputCurrentread-onlymandatoryThe input current in 0.1 amperes, or -1 if it's unsupported by this UPS.
1.3.6.1.4.1.318.1.1.1.9.2.3.1.7ColumnupsPhaseInputMaxCurrentread-onlymandatoryThe maximum input current in 0.1 amperes measured since the last reset (upsPhaseResetMaxMinValues), or -1 if it's unsupported by this UPS. Sampled every 30 sec…
1.3.6.1.4.1.318.1.1.1.9.2.3.1.8ColumnupsPhaseInputMinCurrentread-onlymandatoryThe minimum input current in 0.1 amperes measured since the last reset (upsPhaseResetMaxMinValues), or -1 if it's unsupported by this UPS. Sampled every 30 sec…
1.3.6.1.4.1.318.1.1.1.9.2.3.1.9ColumnupsPhaseInputPowerread-onlymandatoryThe input power in Watts, or -1 if it's unsupported by this UPS.
1.3.6.1.4.1.318.1.1.1.9.2.3.1.10ColumnupsPhaseInputMaxPowerread-onlymandatoryThe maximum input power in Watts measured since the last reset (upsPhaseResetMaxMinValues), or -1 if it's unsupported by this UPS. Sampled every 30 seconds.
1.3.6.1.4.1.318.1.1.1.9.2.3.1.11ColumnupsPhaseInputMinPowerread-onlymandatoryThe minimum input power in Watts measured since the last reset (upsPhaseResetMaxMinValues), or -1 if it's unsupported by this UPS. Sampled every 30 seconds.
1.3.6.1.4.1.318.1.1.1.9.2.3.1.12ColumnupsPhaseInputApparentPowerread-onlymandatoryThe input apparent power of the UPS in kVA.
1.3.6.1.4.1.318.1.1.1.9.2.3.1.13ColumnupsPhaseInputPowerFactorread-onlymandatoryThe input power factor measured in hundredth.
1.3.6.1.4.1.318.1.1.1.9.3NodeupsPhaseOutput
1.3.6.1.4.1.318.1.1.1.9.3.1ScalarupsPhaseNumOutputsread-onlymandatoryThe number of output feeds to this device. This variable indicates the number of rows in the output table.
1.3.6.1.4.1.318.1.1.1.9.3.2TableupsPhaseOutputTablenot-accessiblemandatoryA list of output table entries. The number of entries is given by the value of upsOutputNumPhases.
1.3.6.1.4.1.318.1.1.1.9.3.2.1RowupsPhaseOutputEntrynot-accessiblemandatoryAn entry containing information applicable to a particular output.
1.3.6.1.4.1.318.1.1.1.9.3.2.1.1ColumnupsPhaseOutputTableIndexread-onlymandatoryThe output identifier.
1.3.6.1.4.1.318.1.1.1.9.3.2.1.2ColumnupsPhaseNumOutputPhasesread-onlymandatoryThe number of output phases utilized in this device. The sum of all the upsPhaseNumOutputPhases variable indicates the number of rows in the output phase table.
1.3.6.1.4.1.318.1.1.1.9.3.2.1.3ColumnupsPhaseOutputVoltageOrientationread-onlymandatoryThe output voltage orientation: 1: unknown for this UPS 2: singlePhase - phase 1 voltage is between Phase 1 and Neutral. 3: splitPhase - phase 1 voltage is bet…
1.3.6.1.4.1.318.1.1.1.9.3.2.1.4ColumnupsPhaseOutputFrequencyread-onlymandatoryThe output frequency in 0.1 Hertz, or -1 if it's unsupported by this UPS.
1.3.6.1.4.1.318.1.1.1.9.3.3TableupsPhaseOutputPhaseTablenot-accessiblemandatoryA list of output table entries. The number of entries is given by the sum of the upsPhaseNumOutputPhases.
1.3.6.1.4.1.318.1.1.1.9.3.3.1RowupsPhaseOutputPhaseEntrynot-accessiblemandatoryAn entry containing information applicable to a particular output phase.
1.3.6.1.4.1.318.1.1.1.9.3.3.1.1ColumnupsPhaseOutputPhaseTableIndexread-onlymandatoryThe output identifier.
1.3.6.1.4.1.318.1.1.1.9.3.3.1.2ColumnupsPhaseOutputPhaseIndexread-onlymandatoryThe output phase identifier.
1.3.6.1.4.1.318.1.1.1.9.3.3.1.3ColumnupsPhaseOutputVoltageread-onlymandatoryThe output voltage in VAC, or -1 if it's unsupported by this UPS.
1.3.6.1.4.1.318.1.1.1.9.3.3.1.4ColumnupsPhaseOutputCurrentread-onlymandatoryThe output current in 0.1 amperes drawn by the load on the UPS, or -1 if it's unsupported by this UPS.
1.3.6.1.4.1.318.1.1.1.9.3.3.1.5ColumnupsPhaseOutputMaxCurrentread-onlymandatoryThe maximum output current in 0.1 amperes measured since the last reset (upsPhaseResetMaxMinValues), or -1 if it's unsupported by this UPS. Sampled every 30 se…
1.3.6.1.4.1.318.1.1.1.9.3.3.1.6ColumnupsPhaseOutputMinCurrentread-onlymandatoryThe minimum output current in 0.1 amperes measured since the last reset (upsPhaseResetMaxMinValues), or -1 if it's unsupported by this UPS. Sampled every 30 se…
1.3.6.1.4.1.318.1.1.1.9.3.3.1.7ColumnupsPhaseOutputLoadread-onlymandatoryThe output load in VA, or -1 if it's unsupported by this UPS.
1.3.6.1.4.1.318.1.1.1.9.3.3.1.8ColumnupsPhaseOutputMaxLoadread-onlymandatoryThe maximum output load in VA measured since the last reset (upsPhaseResetMaxMinValues), or -1 if it's unsupported by this UPS. Sampled every 30 seconds.
1.3.6.1.4.1.318.1.1.1.9.3.3.1.9ColumnupsPhaseOutputMinLoadread-onlymandatoryThe minimum output load in VA measured since the last reset (upsPhaseResetMaxMinValues), or -1 if it's unsupported by this UPS. Sampled every 30 seconds.
1.3.6.1.4.1.318.1.1.1.9.3.3.1.10ColumnupsPhaseOutputPercentLoadread-onlymandatoryThe percentage of the UPS load capacity in VA at redundancy @ (n + x) presently being used on this output phase, or -1 if it's unsupported by this UPS.
1.3.6.1.4.1.318.1.1.1.9.3.3.1.11ColumnupsPhaseOutputMaxPercentLoadread-onlymandatoryThe maximum percentage of the UPS load capacity in VA measured at redundancy @ (n + x) presently being used on this output phase since the last reset (upsPhase…
1.3.6.1.4.1.318.1.1.1.9.3.3.1.12ColumnupsPhaseOutputMinPercentLoadread-onlymandatoryThe minimum percentage of the UPS load capacity in VA measured at redundancy @ (n + x) presently being used on this output phase since the last reset (upsPhase…
1.3.6.1.4.1.318.1.1.1.9.3.3.1.13ColumnupsPhaseOutputPowerread-onlymandatoryThe output power in Watts, or -1 if it's unsupported by this UPS.
1.3.6.1.4.1.318.1.1.1.9.3.3.1.14ColumnupsPhaseOutputMaxPowerread-onlymandatoryThe maximum output power in Watts measured since the last reset (upsPhaseResetMaxMinValues), or -1 if it's unsupported by this UPS. Sampled every 30 seconds.
1.3.6.1.4.1.318.1.1.1.9.3.3.1.15ColumnupsPhaseOutputMinPowerread-onlymandatoryThe minimum output power in Watts measured since the last reset (upsPhaseResetMaxMinValues), or -1 if it's unsupported by this UPS. Sampled every 30 seconds.
1.3.6.1.4.1.318.1.1.1.9.3.3.1.16ColumnupsPhaseOutputPercentPowerread-onlymandatoryThe percentage of the UPS power capacity in Watts at redundancy @ (n + x) presently being used on this output phase, or -1 if it's unsupported by this UPS.
1.3.6.1.4.1.318.1.1.1.9.3.3.1.17ColumnupsPhaseOutputMaxPercentPowerread-onlymandatoryThe maximum percentage of the UPS power capacity in Watts measured at redundancy @ (n + x) presently being used on this output phase since the last reset (upsP…
1.3.6.1.4.1.318.1.1.1.9.3.3.1.18ColumnupsPhaseOutputMinPercentPowerread-onlymandatoryThe maximum percentage of the UPS power capacity in Watts measured at redundancy @ (n + x) presently being used on this output phase since the last reset (upsP…
1.3.6.1.4.1.318.1.1.1.9.3.3.1.19ColumnupsPhaseOutputPowerFactorread-onlymandatoryThe Output power factor of the UPS in hundredth.
1.3.6.1.4.1.318.1.1.1.9.3.3.1.20ColumnupsPhaseOutputApparentPowerread-onlymandatoryApparent power in kVA
1.3.6.1.4.1.318.1.1.1.9.3.3.1.21ColumnupsPhaseOutputInverterVoltageread-onlymandatoryOutput voltage in VAC measured at the output of inverter.
1.3.6.1.4.1.318.1.1.1.10NodeupsSyncCtrlGroup
1.3.6.1.4.1.318.1.1.1.10.1NodeupsSyncCtrlGroupConfig
1.3.6.1.4.1.318.1.1.1.10.1.1ScalarupsSCGMembershipGroupNumberread-writemandatoryThe SCG Membership Group number (MGN) is a 16-bit number allowing up to 65534 separate groups that can be identified and distinguished per IP subnet. Zero and …
1.3.6.1.4.1.318.1.1.1.10.1.2ScalarupsSCGActiveMembershipStatusread-writemandatoryMembership in the configured SCG can be enabled and disabled. If an NMC is configured for an SCG, but has its membership disabled, all synchronized control com…
1.3.6.1.4.1.318.1.1.1.10.1.3ScalarupsSCGPowerSynchronizationDelayTimeread-writemandatoryThe Power Synchronization Delay Time (PSD) setting is the maximum number of seconds an SCG Initiator will wait for all SCG members to recover utility power bef…
1.3.6.1.4.1.318.1.1.1.10.1.4ScalarupsSCGReturnBatteryCapacityOffsetread-writemandatoryA reboot command uses the Initiator's Return battery Capacity (RBC) to control when the SCG completes this operation. In a Normal Control Operation (NCC) the U…
1.3.6.1.4.1.318.1.1.1.10.1.5ScalarupsSCGMultiCastIPread-writemandatoryThe MultiCast IP address of the SCG Group.
1.3.6.1.4.1.318.1.1.1.10.2NodeupsSyncCtrlGroupStatus
1.3.6.1.4.1.318.1.1.1.10.2.1ScalarupsSCGNumOfGroupMembersread-onlymandatoryThe number of active, communicating members in the Sync Control Group (SCG). This variable indicates the number of rows in the SCG Status Table.
1.3.6.1.4.1.318.1.1.1.10.2.2TableupsSCGStatusTablenot-accessiblemandatoryA list of SCG status table entries. The number of entries is given by the value of upsSCGNumOfGroupMembers.
1.3.6.1.4.1.318.1.1.1.10.2.2.1RowupsSCGStatusEntrynot-accessiblemandatoryAn entry containing information applicable to a particular SCG Member.
1.3.6.1.4.1.318.1.1.1.10.2.2.1.1ColumnupsSCGStatusTableIndexread-onlymandatoryThe index of a status entry for an active, communicating SCG member.
1.3.6.1.4.1.318.1.1.1.10.2.2.1.2ColumnupsSCGMemberIPread-onlymandatoryThe IP address of an active, communicating SCG Member.
1.3.6.1.4.1.318.1.1.1.10.2.2.1.3ColumnupsSCGACInputStatusread-onlymandatoryThis OID indicates the AC Input Status of the SCG Member. acInGood(1) indicates the AC Input is within tolerance. acInBad(2) indicates the AC Input is not with…
1.3.6.1.4.1.318.1.1.1.10.2.2.1.4ColumnupsSCGACOutputStatusread-onlymandatoryThis OID indicates the AC Output Status of the SCG Member. acOutOn(1) indicates the UPS output is providing power to the load. acOutOff(2) indicates the UPS ou…
1.3.6.1.4.1.318.1.1.1.11NodeupsState
1.3.6.1.4.1.318.1.1.1.11.1NodeupsBasicState
1.3.6.1.4.1.318.1.1.1.11.1.1ScalarupsBasicStateOutputStateread-onlymandatoryAn ASCII string containing the 64 flags representing the current state(s) of the UPS. If the Network Card is unable to determine the state of the UPS, this var…
1.3.6.1.4.1.318.1.1.1.11.1.2ScalarupsBasicStateAlarmStatusread-onlymandatoryThe alarm status of the Power Module. noAlarms(1) indicates the device has no alarms present. infoAlarm (2) indicates the device has alarms and the highest sev…
1.3.6.1.4.1.318.1.1.1.11.2NodeupsAdvState
1.3.6.1.4.1.318.1.1.1.11.2.1ScalarupsAdvStateAbnormalConditionsread-onlymandatoryAn ASCII string containing the 32 flags representing the current active UPS faults. If the Network Card is unable to determine the values of the flags, this va…
1.3.6.1.4.1.318.1.1.1.11.2.2ScalarupsAdvStateSymmetra3PhaseSpecificFaultsread-onlymandatoryAn ASCII string containing the 64 flags representing the current active UPS specific faults for the Symmetra 3-Phase UPS models. If the Network Card is unable …
1.3.6.1.4.1.318.1.1.1.11.2.3ScalarupsAdvStateDP300ESpecificFaultsread-onlymandatoryAn ASCII string containing the 64 flags representing the current active UPS specific faults for the Silcon DP300E UPS models. If the Network Card is unable to …
1.3.6.1.4.1.318.1.1.1.11.2.4ScalarupsAdvStateSymmetraSpecificFaultsread-onlymandatoryAn ASCII string containing the 64 flags representing the current active UPS specific faults for the Symmetra UPS models. If the Network Card is unable to deter…
1.3.6.1.4.1.318.1.1.1.11.2.5ScalarupsAdvStateSmartUPSSpecificFaultsread-onlymandatoryAn ASCII string containing the 64 flags representing the current active UPS specific faults for the Smart-UPS UPS models. If the Network Card is unable to dete…
1.3.6.1.4.1.318.1.1.1.11.2.6ScalarupsAdvStateSystemMessagesread-onlymandatoryAn ASCII string containing the 3 digit Decimal code representing the current active message from the System Message Register. Each code should remain active fo…
1.3.6.1.4.1.318.1.1.1.11.2.7ScalarupsAdvStateTotaltimeonbatteryread-onlymandatoryTotal time the UPS has been in battery operation.
1.3.6.1.4.1.318.1.1.1.11.2.8ScalarupsAdvStateTotaltimeonbypassread-onlymandatoryTotal time the UPS has been in bypass operation.
1.3.6.1.4.1.318.1.1.1.11.2.9ScalarupsAdvStateTotaltimeonNormalread-onlymandatoryTotal time the UPS has been in normal operation.
1.3.6.1.4.1.318.1.1.1.11.2.10ScalarupsAdvStateNumberoftimesonbatteryread-onlymandatoryNumber of times the UPS was on battery. Since the last reset of statistical data.
1.3.6.1.4.1.318.1.1.1.11.2.11ScalarupsAdvStateNumberoftimesbypassread-onlymandatoryNumber of times the UPS was in bypass. Since the last reset of statistical data.
1.3.6.1.4.1.318.1.1.1.11.2.12ScalarupsAdvStateNumberoftimesNormalread-onlymandatoryNumber of times the UPS was in normal operation. Since the last reset of statistical data.
1.3.6.1.4.1.318.1.1.1.11.2.13ScalarupsAdvStateEcomoderead-onlymandatoryEco mode status. 1: UPS is on Eco-mode 2: UPS is not on Eco-mode.
1.3.6.1.4.1.318.1.1.1.11.2.14ScalarupsAdvStateLifeCycleManagementread-onlymandatoryAn ASCII string containing the 16 flags representing the life cycle management alerts for the device. If the Network Card is unable to determine the values of …
1.3.6.1.4.1.318.1.1.1.12NodeupsOutletGroups
1.3.6.1.4.1.318.1.1.1.12.1NodeupsOutletGroupStatus
1.3.6.1.4.1.318.1.1.1.12.1.1ScalarupsOutletGroupStatusTableSizeread-onlymandatoryThe number of outlet groups for the UPS.
1.3.6.1.4.1.318.1.1.1.12.1.2TableupsOutletGroupStatusTablenot-accessiblemandatoryAllows for getting status of the outlet groups. The number of entries is contained in the upsOutletGroupStatusTableSize OID.
1.3.6.1.4.1.318.1.1.1.12.1.2.1RowupsOutletGroupStatusEntrynot-accessiblemandatoryThe outlet group status to get.
1.3.6.1.4.1.318.1.1.1.12.1.2.1.1ColumnupsOutletGroupStatusIndexread-onlymandatoryThe index to the outlet group entry.
1.3.6.1.4.1.318.1.1.1.12.1.2.1.2ColumnupsOutletGroupStatusNameread-onlymandatoryThe name of the outlet group. This OID is provided for informational purposes only. This value is set by the upsOutletGroupConfigName OID.
1.3.6.1.4.1.318.1.1.1.12.1.2.1.3ColumnupsOutletGroupStatusGroupStateread-onlymandatoryGetting this variable will return the outlet group state. If the outlet group is on, the upsOutletGroupStatusOn (1) value will be returned. If the outlet group…
1.3.6.1.4.1.318.1.1.1.12.1.2.1.4ColumnupsOutletGroupStatusCommandPendingread-onlymandatoryGetting this variable will return the command pending state of the outlet group. If a command is pending on the outlet group, the upsOutletGroupCommandPending …
1.3.6.1.4.1.318.1.1.1.12.1.2.1.5ColumnupsOutletGroupStatusOutletTyperead-onlymandatoryGetting this variable will return the type of outlet group. If present in the system, the main outlet group is 'unswitched' and must be on in order for any of …
1.3.6.1.4.1.318.1.1.1.12.1.2.1.6ColumnupsOutletGroupStatusGroupFullStateread-onlymandatoryAn ASCII string containing the 32 flags representing the current state(s) of the outlet group. If the Network Card is unable to determine the state of the outl…
1.3.6.1.4.1.318.1.1.1.12.2NodeupsOutletGroupConfig
1.3.6.1.4.1.318.1.1.1.12.2.1ScalarupsOutletGroupConfigTableSizeread-onlymandatoryThe number of outlet groups for the UPS.
1.3.6.1.4.1.318.1.1.1.12.2.2TableupsOutletGroupConfigTablenot-accessiblemandatoryThe list of outlet groups to configure. The number of entries is defined by the upsOutletGroupConfigTableSize OID.
1.3.6.1.4.1.318.1.1.1.12.2.2.1RowupsOutletGroupConfigEntrynot-accessiblemandatoryThe outlet groups to configure.
1.3.6.1.4.1.318.1.1.1.12.2.2.1.1ColumnupsOutletGroupConfigIndexread-onlymandatoryThe index to the outlet group entry.
1.3.6.1.4.1.318.1.1.1.12.2.2.1.2ColumnupsOutletGroupConfigNameread-writemandatoryThe name of the outlet group.
1.3.6.1.4.1.318.1.1.1.12.2.2.1.3ColumnupsOutletGroupConfigPowerOnDelayread-writemandatoryThe amount of time (seconds) the outlet group will delay powering on when the delayed on, reboot, or shutdown command is applied. Allowed values vary by UPS mo…
1.3.6.1.4.1.318.1.1.1.12.2.2.1.4ColumnupsOutletGroupConfigPowerOffDelayread-writemandatoryThe amount of time (seconds) the outlet group will delay powering off when the delayed off, reboot, or shutdown command is applied. Allowed values vary by UPS …
1.3.6.1.4.1.318.1.1.1.12.2.2.1.5ColumnupsOutletGroupConfigRebootDurationread-writemandatoryDuring a reboot sequence, power is turned off and then back on. This OID defines the amount of time to wait (seconds) after turning the power off, at the start…
1.3.6.1.4.1.318.1.1.1.12.2.2.1.6ColumnupsOutletGroupConfigMinReturnRuntimeread-writemandatoryIn an Outlet Group shutdown sequence, the Outlet Group cycles power off then on. This OID defines the minimum amount of UPS runtime (seconds) that is required …
1.3.6.1.4.1.318.1.1.1.12.2.2.1.7ColumnupsOutletGroupConfigOutletTyperead-onlymandatoryGetting this variable will return the type of outlet group. If present in the system, the main outlet group is 'unswitched' and must be on in order for any of …
1.3.6.1.4.1.318.1.1.1.12.2.2.1.8ColumnupsOutletGroupConfigLoadShedControlSkipOffDelayread-writemandatoryConfigures whether the outlet group's off delay setting (upsOutletGroupConfigPowerOffDelay) will be used in a load shedding situation, where applicable.
1.3.6.1.4.1.318.1.1.1.12.2.2.1.9ColumnupsOutletGroupConfigLoadShedControlAutoRestartread-writemandatoryConfigures whether the outlet group will automatically restart after a load shedding situation, where applicable.
1.3.6.1.4.1.318.1.1.1.12.2.2.1.10ColumnupsOutletGroupConfigLoadShedControlTimeOnBatteryread-writemandatoryConfigures whether the outlet group will load shed (turn off) after the UPS's time on battery has exceeded the upsOutletGroupConfigLoadShedTimeOnBattery OID se…
1.3.6.1.4.1.318.1.1.1.12.2.2.1.11ColumnupsOutletGroupConfigLoadShedControlRuntimeRemainingread-writemandatoryConfigures whether the outlet group will load shed (turn off) when the UPS is on battery and the remaining runtime is less than the upsOutletGroupConfigLoadShe…
1.3.6.1.4.1.318.1.1.1.12.2.2.1.12ColumnupsOutletGroupConfigLoadShedControlInOverloadread-writemandatoryConfigures whether the outlet group will load shed (turn off) when the UPS is in an overload condition. The setting for upsOutletGroupConfigLoadShedControlSkip…
1.3.6.1.4.1.318.1.1.1.12.2.2.1.13ColumnupsOutletGroupConfigLoadShedTimeOnBatteryread-writemandatoryWhen the UPS has been on battery for more time than this value, the outlet group will turn off if this condition is enabled by the upsOutletGroupConfigLoadShed…
1.3.6.1.4.1.318.1.1.1.12.2.2.1.14ColumnupsOutletGroupConfigLoadShedRuntimeRemainingread-writemandatoryWhen the runtime remaining is less than this value, the outlet group will turn off if this condition is enabled by the upsOutletGroupConfigLoadShedControlRunti…
1.3.6.1.4.1.318.1.1.1.12.3NodeupsOutletGroupControl
1.3.6.1.4.1.318.1.1.1.12.3.1ScalarupsOutletGroupControlTableSizeread-onlymandatoryThe number of outlet groups for the UPS.
1.3.6.1.4.1.318.1.1.1.12.3.2TableupsOutletGroupControlTablenot-accessiblemandatoryAllows for control of individual outlet groups. The number of entries is contained in the upsOutletGroupControlTableSize OID.
1.3.6.1.4.1.318.1.1.1.12.3.2.1RowupsOutletGroupControlEntrynot-accessiblemandatoryThe outlet group to control.
1.3.6.1.4.1.318.1.1.1.12.3.2.1.1ColumnupsOutletGroupControlIndexread-onlymandatoryThe index to the outlet group entry.
1.3.6.1.4.1.318.1.1.1.12.3.2.1.2ColumnupsOutletGroupControlNameread-onlymandatoryThe name of the outlet group. This OID is provided for informational purposes only. This value is set by the upsOutletGroupConfigName OID.
1.3.6.1.4.1.318.1.1.1.12.3.2.1.3ColumnupsOutletGroupControlCommandread-writemandatoryGetting this variable will return the outlet group state. If the outlet group is on, the upsOutletGroupImmediateOn (1) value will be returned. If the outlet gr…
1.3.6.1.4.1.318.1.1.1.12.3.2.1.4ColumnupsOutletGroupControlOutletTyperead-onlymandatoryGetting this variable will return the type of outlet group. If present in the system, the main outlet group is 'unswitched' and must be on in order for any of …
1.3.6.1.4.1.318.1.1.1.13NodeupsDiagnostics
1.3.6.1.4.1.318.1.1.1.13.1NodeupsDiagnosticIM
1.3.6.1.4.1.318.1.1.1.13.1.1ScalarupsDiagIMTableSizeread-onlymandatoryThe number of Intelligence Modules in or attached to the UPS.
1.3.6.1.4.1.318.1.1.1.13.1.2TableupsDiagIMTablenot-accessiblemandatoryAllows for diagnostics of individual Intelligence Modules. The number of entries is contained in the upsDiagIMTableSize OID.
1.3.6.1.4.1.318.1.1.1.13.1.2.1RowupsDiagIMEntrynot-accessiblemandatoryThe diagnostics and information of an Intelligence Module.
1.3.6.1.4.1.318.1.1.1.13.1.2.1.1ColumnupsDiagIMIndexread-onlymandatoryThe index to the Intelligence Module entry.
1.3.6.1.4.1.318.1.1.1.13.1.2.1.2ColumnupsDiagIMTyperead-onlymandatoryThe type of the Intelligence Module. imUnknown(1) indicates the IM type is unknown. imMIM(2) indicates the IM type is a Main Intelligence Module. imRIM(3) indi…
1.3.6.1.4.1.318.1.1.1.13.1.2.1.3ColumnupsDiagIMStatusread-onlymandatoryThe status of the Intelligence Module. unknown(1) indicates the device status is unknown. notInstalled(2) indicates the device is not installed. offOk(3) indic…
1.3.6.1.4.1.318.1.1.1.13.1.2.1.4ColumnupsDiagIMFirmwareRevread-onlymandatoryThe firmware revision of the Intelligence Module.
1.3.6.1.4.1.318.1.1.1.13.1.2.1.5ColumnupsDiagIMSlaveFirmwareRevread-onlymandatoryThe slave firmware revision of the Intelligence Module.
1.3.6.1.4.1.318.1.1.1.13.1.2.1.6ColumnupsDiagIMHardwareRevread-onlymandatoryThe hardware revision of the Intelligence Module.
1.3.6.1.4.1.318.1.1.1.13.1.2.1.7ColumnupsDiagIMSerialNumread-onlymandatoryThe serial number of the Intelligence Module.
1.3.6.1.4.1.318.1.1.1.13.1.2.1.8ColumnupsDiagIMManufactureDateread-onlymandatoryThe manufacture date of the Intelligence Module.
1.3.6.1.4.1.318.1.1.1.13.1.2.1.9ColumnupsDiagIMInControlread-onlymandatoryThe Intelligence Module state. activeInControl(1) indicates the IM is active and in control. passive(2) indicates the IM is in passive state. unknown(3) indica…
1.3.6.1.4.1.318.1.1.1.13.2NodeupsDiagnosticPowerModules
1.3.6.1.4.1.318.1.1.1.13.2.1ScalarupsDiagPMTableSizeread-onlymandatoryThe maximum number of Power Modules supported by the UPS.
1.3.6.1.4.1.318.1.1.1.13.2.2TableupsDiagPMTablenot-accessiblemandatoryAllows for diagnostics of Individual Power modules. The number of entries is contained in the upsDiagPMTableSize OID.
1.3.6.1.4.1.318.1.1.1.13.2.2.1RowupsDiagPMEntrynot-accessiblemandatoryThe diagnostics of an Power Module.
1.3.6.1.4.1.318.1.1.1.13.2.2.1.1ColumnupsDiagPMIndexread-onlymandatoryThe index to the Power Module entry.
1.3.6.1.4.1.318.1.1.1.13.2.2.1.2ColumnupsDiagPMStatusread-onlymandatoryThe status of the Power Module. unknown(1) indicates the device status is unknown. notInstalled(2) indicates the device is not installed. offOk(3) indicates th…
1.3.6.1.4.1.318.1.1.1.13.2.2.1.3ColumnupsDiagPMFirmwareRevread-onlymandatoryThe firmware revision of the Power Module.
1.3.6.1.4.1.318.1.1.1.13.2.2.1.4ColumnupsDiagPMHardwareRevread-onlymandatoryThe hardware revision of the Power Module.
1.3.6.1.4.1.318.1.1.1.13.2.2.1.5ColumnupsDiagPMSerialNumread-onlymandatoryThe serial number of the Power Module.
1.3.6.1.4.1.318.1.1.1.13.2.2.1.6ColumnupsDiagPMManufactureDateread-onlymandatoryThe manufacture date of the Power Module.
1.3.6.1.4.1.318.1.1.1.13.2.2.1.7ColumnupsDiagPMModelNumread-onlymandatoryThe model number of the Power Module.
1.3.6.1.4.1.318.1.1.1.13.2.3TableupsDiagPMLifetimeInfoTablenot-accessiblemandatoryAllows for diagnostics of individual power module's lifetime information. The number of entries is contained in the upsDiagPMTableSize OID.
1.3.6.1.4.1.318.1.1.1.13.2.3.1RowupsDiagPMLifetimeInfoEntrynot-accessiblemandatoryThe diagnostics of a Power Module lifetime information.
1.3.6.1.4.1.318.1.1.1.13.2.3.1.1ColumnupsDiagPMLifetimeInfoIndexread-onlymandatoryThe index to the Power Module lifetime information entry.
1.3.6.1.4.1.318.1.1.1.13.2.3.1.2ColumnupsDiagPMLifetimeStatusread-onlymandatoryThe status of the Power Module lifetime information. ok(1) indicates the device lifetime status is OK. nearEnd(2) indicates the device lifetime status is near …
1.3.6.1.4.1.318.1.1.1.13.2.3.1.3ColumnupsDiagPMEstmtdLifetimeRmngread-onlymandatoryDisplays the time remaining for the module before it should be replaced. Measured in months. This value is set when you originally install the module.
1.3.6.1.4.1.318.1.1.1.13.2.3.1.4ColumnupsDiagPMEstmtdLifetimeRmngPctread-onlymandatoryDisplays the percentage of the total lifetime remaining for the module before it should be replaced.
1.3.6.1.4.1.318.1.1.1.13.2.3.1.5ColumnupsDiagPMFanLifetimeStatusread-onlymandatoryThe status of the Power Module Fan lifetime information. ok(1) indicates the device lifetime status is OK. nearEnd(2) indicates the device lifetime status is n…
1.3.6.1.4.1.318.1.1.1.13.2.3.1.6ColumnupsDiagPMFanEstmtdLifetimeRmngread-onlymandatoryDisplays the time remaining, measured in months, before the module's fan should be replaced. It is reset by the field service engineer when a new fan is instal…
1.3.6.1.4.1.318.1.1.1.13.2.3.1.7ColumnupsDiagPMFanEstmtdLifetimeRmngPctread-onlymandatoryDisplays the percentage of the total lifetime remaining before the module's fan should be replaced.
1.3.6.1.4.1.318.1.1.1.13.2.4ScalarupsDiagPMEnclDoorFltrTableSizeread-onlymandatoryThe maximum number of power module enclosures attached to the UPS.
1.3.6.1.4.1.318.1.1.1.13.2.5TableupsDiagPMEnclDoorFltrTablenot-accessiblemandatoryAllows for the diagnostics of individual power module enclosure door filters. The number of entries is contained in the upsDiagPMEnclDoorFltrTableSize OID.
1.3.6.1.4.1.318.1.1.1.13.2.5.1RowupsDiagPMEnclDoorFltrEntrynot-accessiblemandatoryPower module door filter diagnostics info.
1.3.6.1.4.1.318.1.1.1.13.2.5.1.1ColumnupsDiagPMEnclIndexread-onlymandatoryThe index to the power module enclosure entry. Enclosure 0 indicates the Power enclosure 1. Enclosure 1 indicates the Power enclosure 2.
1.3.6.1.4.1.318.1.1.1.13.2.5.1.2ColumnupsDiagPMEnclDoorFltrLifetimeread-onlymandatoryDoor filter replacement time interval, based on the installation enivironment. heavyFiltration15days (1) indicates door filter needs to be replaced within 15 d…
1.3.6.1.4.1.318.1.1.1.13.2.5.1.3ColumnupsDiagPMEnclDoorFltrStatusread-onlymandatoryIndicates the current status of the door filter. ok(1) indicates the device lifetime status is OK. nearEnd(2) indicates the device lifetime status is near end.…
1.3.6.1.4.1.318.1.1.1.13.2.5.1.4ColumnupsDiagPMEnclDoorFltrEstmtdLifetimeRmngread-onlymandatoryDisplays the time remaining, measured in days, before the module door filter should be replaced. This value is set when you originally install the module.
1.3.6.1.4.1.318.1.1.1.13.2.5.1.5ColumnupsDiagPMEnclDoorFltrEstmtdLifetimeRmngPctread-onlymandatoryDisplays the percentage of the total lifetime remaining for the module door filter before it should be replaced.
1.3.6.1.4.1.318.1.1.1.13.3NodeupsDiagnosticBatteries
1.3.6.1.4.1.318.1.1.1.13.3.1ScalarupsDiagBatteryTableSizeread-onlymandatoryThe maximum number of batteries supported by the UPS.
1.3.6.1.4.1.318.1.1.1.13.3.2TableupsDiagBatteryTablenot-accessiblemandatoryAllows for diagnostics of individual batteries. The number of entries is contained in the upsDiagBattTableSize OID.
1.3.6.1.4.1.318.1.1.1.13.3.2.1RowupsDiagBatteryEntrynot-accessiblemandatoryThe diagnostics of a battery.
1.3.6.1.4.1.318.1.1.1.13.3.2.1.1ColumnupsDiagBatteryFrameIndexread-onlymandatoryThe index to the battery frame entry. Frame 0 indicates the Main frame. Extended Run (XR) frames start from index 1.
1.3.6.1.4.1.318.1.1.1.13.3.2.1.2ColumnupsDiagBatteryIndexread-onlymandatoryThe index to the battery entry.
1.3.6.1.4.1.318.1.1.1.13.3.2.1.3ColumnupsDiagBatteryStatusread-onlymandatoryThe status of the battery. unknown(1) indicates the device status is unknown. notInstalled(2) indicates the device is not installed. ok(3) indicates the batter…
1.3.6.1.4.1.318.1.1.1.13.3.2.1.4ColumnupsDiagBatterySerialNumberread-onlymandatoryThe serial number of the battery.
1.3.6.1.4.1.318.1.1.1.13.3.2.1.5ColumnupsDiagBatteryFirmwareRevread-onlymandatoryThe firmware revision of the battery.
1.3.6.1.4.1.318.1.1.1.13.3.2.1.6ColumnupsDiagBatteryManufactureDateread-onlymandatoryThe manufacture date of the battery.
1.3.6.1.4.1.318.1.1.1.13.3.2.1.7ColumnupsDiagBatteryTyperead-onlymandatoryThe battery type or rating for the battery.
1.3.6.1.4.1.318.1.1.1.13.3.2.1.8ColumnupsDiagBatteryFramePresentread-onlymandatoryThe battery frame/cabinet status. 0 indicates frame/cabinet is not present. 1 indicates frame/cabinet is present.
1.3.6.1.4.1.318.1.1.1.13.3.2.1.9ColumnupsDiagBatteryFrameTemperatureread-onlymandatoryThe battery frame/cabinet temperature in tenths of degrees celsius. If the frame/cabinet is not present, this variable is set to (-1).
1.3.6.1.4.1.318.1.1.1.13.3.3ScalarupsDiagBatteryFrameTableSizeread-onlymandatoryThe maximum number of battery frames supported by the UPS.
1.3.6.1.4.1.318.1.1.1.13.3.4TableupsDiagBatteryFrameTablenot-accessiblemandatoryAllows for diagnostics of individual battery frame. The number of entries is contained in the upsDiagBatteryFrameTableSize OID.
1.3.6.1.4.1.318.1.1.1.13.3.4.1RowupsDiagBatteryFrameEntrynot-accessiblemandatoryThe diagnostics of a battery frame.
1.3.6.1.4.1.318.1.1.1.13.3.4.1.1ColumnupsDiagBatteryFrameTableIndexread-onlymandatoryThe index to the battery frame entry.
1.3.6.1.4.1.318.1.1.1.13.3.4.1.2ColumnupsDiagBatteryModuleStatusPerFrameread-onlymandatoryAn ASCII string containing the 64 flags representing the status of battery modules. 1 indicates battery module installed, 0 indicates battery module not instal…
1.3.6.1.4.1.318.1.1.1.13.3.4.1.3ColumnupsDiagBatteryPositiveVoltageread-onlymandatoryThe battery positive voltage, in Volts.
1.3.6.1.4.1.318.1.1.1.13.3.4.1.4ColumnupsDiagBatteryNegativeVoltageread-onlymandatoryThe battery negative voltage, in Volts.
1.3.6.1.4.1.318.1.1.1.13.3.4.1.5ColumnupsDiagBatteryTemperatureread-onlymandatoryThe battery frame/cabinet temperature in tenths of degrees celsius. If the frame/cabinet is not present, this variable is set to (-1).
1.3.6.1.4.1.318.1.1.1.13.4NodeupsDiagnosticSubsystem
1.3.6.1.4.1.318.1.1.1.13.4.1ScalarupsDiagSubSysFrameTableSizeread-onlymandatoryThe number of frames attached to the UPS including the Main frame.
1.3.6.1.4.1.318.1.1.1.13.4.2TableupsDiagSubSysFrameTablenot-accessiblemandatoryAllows for diagnostics of individual XR Frames.
1.3.6.1.4.1.318.1.1.1.13.4.2.1RowupsDiagSubSysFrameEntrynot-accessiblemandatoryThe diagnostics of an XR Frame.
1.3.6.1.4.1.318.1.1.1.13.4.2.1.1ColumnupsDiagSubSysFrameIndexread-onlymandatoryThe frame index entry.
1.3.6.1.4.1.318.1.1.1.13.4.2.1.2ColumnupsDiagSubSysFrameTyperead-onlymandatoryThe type of Frame. unknown(1) indicates the device status is unknown. notInstalled(2) indicates the device is not installed. frameTypeMain(3) indicates the fra…
1.3.6.1.4.1.318.1.1.1.13.4.2.1.3ColumnupsDiagSubSysFrameFirmwareRevread-onlymandatoryThe firmware revision of the frame.
1.3.6.1.4.1.318.1.1.1.13.4.2.1.4ColumnupsDiagSubSysFrameHardwareRevread-onlymandatoryThe hardware revision of the frame.
1.3.6.1.4.1.318.1.1.1.13.4.2.1.5ColumnupsDiagSubSysFrameSerialNumread-onlymandatoryThe serial number of the frame.
1.3.6.1.4.1.318.1.1.1.13.4.2.1.6ColumnupsDiagSubSysFrameManufactureDateread-onlymandatoryThe manufacture date of the frame.
1.3.6.1.4.1.318.1.1.1.13.4.3ScalarupsDiagSubSysIntBypSwitchTableSizeread-onlymandatoryThe number of Internal Bypass switches attached to the UPS.
1.3.6.1.4.1.318.1.1.1.13.4.4TableupsDiagSubSysIntBypSwitchTablenot-accessiblemandatoryAllows for diagnostics of the Internal Bypass Switch.
1.3.6.1.4.1.318.1.1.1.13.4.4.1RowupsDiagSubSysIntBypSwitchEntrynot-accessiblemandatoryThe diagnostics of the Internal Bypass Switch.
1.3.6.1.4.1.318.1.1.1.13.4.4.1.1ColumnupsDiagSubSysIntBypSwitchFrameIndexread-onlymandatoryThe frame index entry.
1.3.6.1.4.1.318.1.1.1.13.4.4.1.2ColumnupsDiagSubSysIntBypSwitchIndexread-onlymandatoryThe Internal Bypass Switch index entry.
1.3.6.1.4.1.318.1.1.1.13.4.4.1.3ColumnupsDiagSubSysIntBypSwitchStatusread-onlymandatoryThe Internal Bypass Switch status. unknown(1) indicates the device status is unknown. notInstalled(2) indicates the device is not installed. offOk(3) indicates…
1.3.6.1.4.1.318.1.1.1.13.4.4.1.4ColumnupsDiagSubSysIntBypSwitchFirmwareRevread-onlymandatoryThe firmware revision of the Internal Bypass Switch.
1.3.6.1.4.1.318.1.1.1.13.4.4.1.5ColumnupsDiagSubSysIntBypSwitchHardwareRevread-onlymandatoryThe hardware revision of the Internal Bypass Switch.
1.3.6.1.4.1.318.1.1.1.13.4.4.1.6ColumnupsDiagSubSysIntBypSwitchSerialNumread-onlymandatoryThe serial number of the Internal Bypass Switch.
1.3.6.1.4.1.318.1.1.1.13.4.4.1.7ColumnupsDiagSubSysIntBypSwitchManufactureDateread-onlymandatoryThe manufacture date of the Internal Bypass Switch.
1.3.6.1.4.1.318.1.1.1.13.4.4.1.8ColumnupsDiagSubSysIntBypSwitchModelNumread-onlymandatoryThe model number of the Internal Bypass Switch.
1.3.6.1.4.1.318.1.1.1.13.4.5ScalarupsDiagSubSysBattMonitorTableSizeread-onlymandatoryThe number of Battery Monitor Boards attached to the UPS.
1.3.6.1.4.1.318.1.1.1.13.4.6TableupsDiagSubSysBattMonitorTablenot-accessiblemandatoryAllows for diagnostics of the Battery Monitor Board.
1.3.6.1.4.1.318.1.1.1.13.4.6.1RowupsDiagSubSysBattMonitorEntrynot-accessiblemandatoryThe diagnostics of the Battery Monitor Board.
1.3.6.1.4.1.318.1.1.1.13.4.6.1.1ColumnupsDiagSubSysBattMonitorFrameIndexread-onlymandatoryThe frame index entry.
1.3.6.1.4.1.318.1.1.1.13.4.6.1.2ColumnupsDiagSubSysBattMonitorIndexread-onlymandatoryThe index of the Battery Monitor Board.
1.3.6.1.4.1.318.1.1.1.13.4.6.1.3ColumnupsDiagSubSysBattMonitorStatusread-onlymandatoryThe status of the Battery Monitor Board. unknown(1) indicates the device status is unknown. notInstalled(2) indicates the device is not installed. offOk(3) ind…
1.3.6.1.4.1.318.1.1.1.13.4.6.1.4ColumnupsDiagSubSysBattMonitorFirmwareRevread-onlymandatoryThe firmware revision of the Battery Monitor Board.
1.3.6.1.4.1.318.1.1.1.13.4.6.1.5ColumnupsDiagSubSysBattMonitorHardwareRevread-onlymandatoryThe hardware revision of the Battery Monitor Board.
1.3.6.1.4.1.318.1.1.1.13.4.6.1.6ColumnupsDiagSubSysBattMonitorSerialNumread-onlymandatoryThe serial number of the Battery Monitor Board.
1.3.6.1.4.1.318.1.1.1.13.4.6.1.7ColumnupsDiagSubSysBattMonitorManufactureDateread-onlymandatoryThe date of the manufacture for the Battery Monitor Board.
1.3.6.1.4.1.318.1.1.1.13.4.7ScalarupsDiagSubSysExternalSwitchGearTableSizeread-onlymandatoryThe number of External Switch Gears attached to the UPS.
1.3.6.1.4.1.318.1.1.1.13.4.8TableupsDiagSubSysExternalSwitchGearTablenot-accessiblemandatoryAllows for diagnostics of the individual External Switch Gear.
1.3.6.1.4.1.318.1.1.1.13.4.8.1RowupsDiagSubSysExternalSwitchGearEntrynot-accessiblemandatoryThe diagnostics of an individual External Switch Gear.
1.3.6.1.4.1.318.1.1.1.13.4.8.1.1ColumnupsDiagSubSysExternalSwitchGearFrameIndexread-onlymandatoryThe frame index entry.
1.3.6.1.4.1.318.1.1.1.13.4.8.1.2ColumnupsDiagSubSysExternalSwitchGearIndexread-onlymandatoryThe index of the External Switch Gear.
1.3.6.1.4.1.318.1.1.1.13.4.8.1.3ColumnupsDiagSubSysExternalSwitchGearStatusread-onlymandatoryThe status of the External Switch Gear. unknown(1) indicates the device status is unknown. notInstalled(2) indicates the device is not installed. offOk(3) indi…
1.3.6.1.4.1.318.1.1.1.13.4.8.1.4ColumnupsDiagSubSysExternalSwitchGearFirmwareRevread-onlymandatoryThe firmware revision of the External Switch Gear monitor card.
1.3.6.1.4.1.318.1.1.1.13.4.8.1.5ColumnupsDiagSubSysExternalSwitchGearHardwareRevread-onlymandatoryThe hardware revision of the External Switch Gear monitor card.
1.3.6.1.4.1.318.1.1.1.13.4.8.1.6ColumnupsDiagSubSysExternalSwitchGearSerialNumread-onlymandatoryThe serial number of the External Switch Gear monitor card.
1.3.6.1.4.1.318.1.1.1.13.4.8.1.7ColumnupsDiagSubSysExternalSwitchGearManufactureDateread-onlymandatoryThe date of the manufacture for the External Switch Gear monitor card.
1.3.6.1.4.1.318.1.1.1.13.4.8.1.8ColumnupsDiagSubSysExternalSwitchGearTemperatureread-onlymandatoryThe temperature of the air around the External Switch Gear monitor card in tenths of degrees Celsius.
1.3.6.1.4.1.318.1.1.1.13.4.9ScalarupsDiagSubSysDisplayInterfaceCardTableSizeread-onlymandatoryThe number of Display Interface Cards attached to the UPS.
1.3.6.1.4.1.318.1.1.1.13.4.10TableupsDiagSubSysDisplayInterfaceCardTablenot-accessiblemandatoryAllows for diagnostics of individual Display Interface Cards.
1.3.6.1.4.1.318.1.1.1.13.4.10.1RowupsDiagSubSysDisplayInterfaceCardEntrynot-accessiblemandatoryThe diagnostics of a Display Interface Card.
1.3.6.1.4.1.318.1.1.1.13.4.10.1.1ColumnupsDiagSubSysDisplayInterfaceCardFrameIndexread-onlymandatoryThe frame index entry.
1.3.6.1.4.1.318.1.1.1.13.4.10.1.2ColumnupsDiagSubSysDisplayInterfaceCardIndexread-onlymandatoryThe index of the Display Interface Card.
1.3.6.1.4.1.318.1.1.1.13.4.10.1.3ColumnupsDiagSubSysDisplayInterfaceCardStatusread-onlymandatoryThe status of the Display Interface Card. unknown(1) indicates the device status is unknown. notInstalled(2) indicates the device is not installed. offOk(3) in…
1.3.6.1.4.1.318.1.1.1.13.4.11ScalarupsDiagSubSysDCCircuitBreakerTableSizeread-onlymandatoryThe number of DC Circuit Breakers attached to the UPS.
1.3.6.1.4.1.318.1.1.1.13.4.12TableupsDiagSubSysDCCircuitBreakerTablenot-accessiblemandatoryAllows for diagnostics of individual DC Circuit Breakers.
1.3.6.1.4.1.318.1.1.1.13.4.12.1RowupsDiagSubSysDCCircuitBreakerEntrynot-accessiblemandatoryThe diagnostics of a DC Circuit Breaker.
1.3.6.1.4.1.318.1.1.1.13.4.12.1.1ColumnupsDiagSubSysDCCircuitBreakerFrameIndexread-onlymandatoryThe frame index entry.
1.3.6.1.4.1.318.1.1.1.13.4.12.1.2ColumnupsDiagSubSysDCCircuitBreakerIndexread-onlymandatoryThe index of the DC Circuit Breaker.
1.3.6.1.4.1.318.1.1.1.13.4.12.1.3ColumnupsDiagSubSysDCCircuitBreakerStatusread-onlymandatoryThe status of the DC Circuit Breaker. unknown(1) indicates the circuit breaker status is unknown. notInstalled(2) indicates the circuit breaker is not installe…
1.3.6.1.4.1.318.1.1.1.13.4.13ScalarupsDiagSubSysSystemPowerSupplyTableSizeread-onlymandatoryThe number of System Power Supplies attached to the UPS.
1.3.6.1.4.1.318.1.1.1.13.4.14TableupsDiagSubSysSystemPowerSupplyTablenot-accessiblemandatoryAllows for diagnostics of individual System Power Supplies.
1.3.6.1.4.1.318.1.1.1.13.4.14.1RowupsDiagSubSysSystemPowerSupplyEntrynot-accessiblemandatoryThe diagnostics of a System Power Supply.
1.3.6.1.4.1.318.1.1.1.13.4.14.1.1ColumnupsDiagSubSysSystemPowerSupplyFrameIndexread-onlymandatoryThe frame index entry.
1.3.6.1.4.1.318.1.1.1.13.4.14.1.2ColumnupsDiagSubSysSystemPowerSupplyIndexread-onlymandatoryThe index of a System Power Supply.
1.3.6.1.4.1.318.1.1.1.13.4.14.1.3ColumnupsDiagSubSysSystemPowerSupplyStatusread-onlymandatoryThe status of the System Power Supply. unknown(1) indicates the device status is unknown. notInstalled(2) indicates the device is not installed. offOk(3) indic…
1.3.6.1.4.1.318.1.1.1.13.4.14.1.4ColumnupsDiagSubSysSystemPowerSupplyFirmwareRevread-onlymandatoryThe firmware revision of the System Power Supply monitor card.
1.3.6.1.4.1.318.1.1.1.13.4.14.1.5ColumnupsDiagSubSysSystemPowerSupplyHardwareRevread-onlymandatoryThe hardware revision of the System Power Supply monitor card.
1.3.6.1.4.1.318.1.1.1.13.4.14.1.6ColumnupsDiagSubSysSystemPowerSupplySerialNumread-onlymandatoryThe serial number of the System Power Supply monitor card.
1.3.6.1.4.1.318.1.1.1.13.4.14.1.7ColumnupsDiagSubSysSystemPowerSupplyManufactureDateread-onlymandatoryThe date of the manufacture for the System Power Supply monitor card.
1.3.6.1.4.1.318.1.1.1.13.4.15ScalarupsDiagSubSysXRCommunicationCardTableSizeread-onlymandatoryThe number of XR Communication Cards attached to the UPS.
1.3.6.1.4.1.318.1.1.1.13.4.16TableupsDiagSubSysXRCommunicationCardTablenot-accessiblemandatoryAllows for diagnostics of individual XR Communication Cards.
1.3.6.1.4.1.318.1.1.1.13.4.16.1RowupsDiagSubSysXRCommunicationCardEntrynot-accessiblemandatoryThe diagnostics of an XR Communication Card.
1.3.6.1.4.1.318.1.1.1.13.4.16.1.1ColumnupsDiagSubSysXRCommunicationCardFrameIndexread-onlymandatoryThe frame index entry.
1.3.6.1.4.1.318.1.1.1.13.4.16.1.2ColumnupsDiagSubSysXRCommunicationCardIndexread-onlymandatoryThe index of an XR Communication Card.
1.3.6.1.4.1.318.1.1.1.13.4.16.1.3ColumnupsDiagSubSysXRCommunicationCardStatusread-onlymandatoryThe status of the XR Communication Card. unknown(1) indicates the device status is unknown. notInstalled(2) indicates the device is not installed. offOk(3) ind…
1.3.6.1.4.1.318.1.1.1.13.4.16.1.4ColumnupsDiagSubSysXRCommunicationCardFirmwareRevread-onlymandatoryThe firmware revision of the XR Communication card.
1.3.6.1.4.1.318.1.1.1.13.4.16.1.5ColumnupsDiagSubSysXRCommunicationCardSerialNumread-onlymandatoryThe serial number of the XR Communication card.
1.3.6.1.4.1.318.1.1.1.13.4.17ScalarupsDiagSubSysExternalPowerFrameBoardTableSizeread-onlymandatoryThe number of External Power Frame Boards attached to the UPS.
1.3.6.1.4.1.318.1.1.1.13.4.18TableupsDiagSubSysExternalPowerFrameBoardTablenot-accessiblemandatoryAllows for diagnostics of individual External Power Frame Boards.
1.3.6.1.4.1.318.1.1.1.13.4.18.1RowupsDiagSubSysExternalPowerFrameBoardEntrynot-accessiblemandatoryThe diagnostics of an External Power Frame Board.
1.3.6.1.4.1.318.1.1.1.13.4.18.1.1ColumnupsDiagSubSysExternalPowerFrameBoardFrameIndexread-onlymandatoryThe frame index entry.
1.3.6.1.4.1.318.1.1.1.13.4.18.1.2ColumnupsDiagSubSysExternalPowerFrameBoardIndexread-onlymandatoryThe index of an External Power Frame Board.
1.3.6.1.4.1.318.1.1.1.13.4.18.1.3ColumnupsDiagSubSysExternalPowerFrameBoardStatusread-onlymandatoryThe status of the External Power Frame Board. unknown(1) indicates the device status is unknown. notInstalled(2) indicates the device is not installed. offOk(3…
1.3.6.1.4.1.318.1.1.1.13.4.19ScalarupsDiagSubSysChargerTableSizeread-onlymandatoryThe number of Chargers attached to the UPS.
1.3.6.1.4.1.318.1.1.1.13.4.20TableupsDiagSubSysChargerTablenot-accessiblemandatoryAllows for diagnostics of individual chargers.
1.3.6.1.4.1.318.1.1.1.13.4.20.1RowupsDiagSubSysChargerEntrynot-accessiblemandatoryThe diagnostics of a charger.
1.3.6.1.4.1.318.1.1.1.13.4.20.1.1ColumnupsDiagSubSysChargerFrameIndexread-onlymandatoryThe frame index entry.
1.3.6.1.4.1.318.1.1.1.13.4.20.1.2ColumnupsDiagSubSysChargerIndexread-onlymandatoryThe index of a charger.
1.3.6.1.4.1.318.1.1.1.13.4.20.1.3ColumnupsDiagSubSysChargerStatusread-onlymandatoryThe status of the Charger. unknown(1) indicates the device status is unknown. notInstalled(2) indicates the device is not installed. offOk(3) indicates the dev…
1.3.6.1.4.1.318.1.1.1.13.4.21ScalarupsDiagSubSysInverterTableSizeread-onlymandatoryThe number of Inverters attached to the UPS.
1.3.6.1.4.1.318.1.1.1.13.4.22TableupsDiagSubSysInverterTablenot-accessiblemandatoryAllows for diagnostics of individual Inverters.
1.3.6.1.4.1.318.1.1.1.13.4.22.1RowupsDiagSubSysInverterEntrynot-accessiblemandatoryThe diagnostics of an Inverter.
1.3.6.1.4.1.318.1.1.1.13.4.22.1.1ColumnupsDiagSubSysInverterFrameIndexread-onlymandatoryThe frame index entry.
1.3.6.1.4.1.318.1.1.1.13.4.22.1.2ColumnupsDiagSubSysInverterIndexread-onlymandatoryThe index of an Inverter.
1.3.6.1.4.1.318.1.1.1.13.4.22.1.3ColumnupsDiagSubSysInverterStatusread-onlymandatoryThe status of the Inverter. unknown(1) indicates the device status is unknown. notInstalled(2) indicates the device is not installed. offOk(3) indicates the de…
1.3.6.1.4.1.318.1.1.1.13.4.22.1.4ColumnupsDiagSubSysInverterFirmwareRevread-onlymandatoryThe firmware revision of the Inverter monitor.
1.3.6.1.4.1.318.1.1.1.13.4.22.1.5ColumnupsDiagSubSysInverterHardwareRevread-onlymandatoryThe hardware revision of the Inverter monitor.
1.3.6.1.4.1.318.1.1.1.13.4.22.1.6ColumnupsDiagSubSysInverterSerialNumread-onlymandatoryThe serial number of the Inverter monitor.
1.3.6.1.4.1.318.1.1.1.13.4.22.1.7ColumnupsDiagSubSysInverterManufactureDateread-onlymandatoryThe date of manufacture for the Inverter monitor.
1.3.6.1.4.1.318.1.1.1.13.4.23ScalarupsDiagSubSysPowerFactorCorrectionTableSizeread-onlymandatoryThe number of Power Factor Correction devices attached to the UPS.
1.3.6.1.4.1.318.1.1.1.13.4.24TableupsDiagSubSysPowerFactorCorrectionTablenot-accessiblemandatoryAllows for diagnostics of individual PowerFactorCorrections.
1.3.6.1.4.1.318.1.1.1.13.4.24.1RowupsDiagSubSysPowerFactorCorrectionEntrynot-accessiblemandatoryThe diagnostics of a Power Factor Correction.
1.3.6.1.4.1.318.1.1.1.13.4.24.1.1ColumnupsDiagSubSysPowerFactorCorrectionFrameIndexread-onlymandatoryThe frame index entry.
1.3.6.1.4.1.318.1.1.1.13.4.24.1.2ColumnupsDiagSubSysPowerFactorCorrectionIndexread-onlymandatoryThe index of a Power Factor Correction.
1.3.6.1.4.1.318.1.1.1.13.4.24.1.3ColumnupsDiagSubSysPowerFactorCorrectionStatusread-onlymandatoryThe status of the Power Factor Correction. unknown(1) indicates the device status is unknown. notInstalled(2) indicates the device is not installed. offOk(3) i…
1.3.6.1.4.1.318.1.1.1.13.4.24.1.4ColumnupsDiagSubSysPowerFactorCorrectionFirmwareRevread-onlymandatoryThe firmware revision of the Power Factor Correction monitor.
1.3.6.1.4.1.318.1.1.1.13.4.24.1.5ColumnupsDiagSubSysPowerFactorCorrectionHardwareRevread-onlymandatoryThe hardware revision of the Power Factor Correction monitor.
1.3.6.1.4.1.318.1.1.1.13.4.24.1.6ColumnupsDiagSubSysPowerFactorCorrectionSerialNumread-onlymandatoryThe serial number of the Power Factor Correction monitor.
1.3.6.1.4.1.318.1.1.1.13.4.24.1.7ColumnupsDiagSubSysPowerFactorCorrectionManufactureDateread-onlymandatoryThe date of the manufacture for the Power Factor Correction monitor.
1.3.6.1.4.1.318.1.1.1.13.4.25ScalarupsDiagSubSysNetworkComCardTableSizeread-onlymandatoryThe number of Network Communication Cards attached to the UPS.
1.3.6.1.4.1.318.1.1.1.13.4.26TableupsDiagSubSysNetworkComCardTablenot-accessiblemandatoryAllows for getting diagnostics information of an individual Network Communication Card.
1.3.6.1.4.1.318.1.1.1.13.4.26.1RowupsDiagSubSysNetworkComCardEntrynot-accessiblemandatoryThe diagnostics of a Network Communication Card.
1.3.6.1.4.1.318.1.1.1.13.4.26.1.1ColumnupsDiagSubSysNetworkComCardIndexread-onlymandatoryThe UPS network and display interface communication card index entry.
1.3.6.1.4.1.318.1.1.1.13.4.26.1.2ColumnupsDiagSubSysNetworkComCardModelNumberread-onlymandatoryA character string identifying the model number of the UPS network and display interface communication card. This value is set at the factory.
1.3.6.1.4.1.318.1.1.1.13.4.26.1.3ColumnupsDiagSubSysNetworkComCardSerialNumberread-onlymandatoryA character string identifying the serial number of the UPS network and display interface communication card. This value is set at the factory.
1.3.6.1.4.1.318.1.1.1.13.4.26.1.4ColumnupsDiagSubSysNetworkComCardDateOfManufactureread-onlymandatoryThe date when the UPS network and display interface communication card was manufactured in mm/dd/yyyy format. This value is set at the factory.
1.3.6.1.4.1.318.1.1.1.13.4.26.1.5ColumnupsDiagSubSysNetworkComCardHardwareRevread-onlymandatoryThe hardware revision of the UPS network and display interface communication card. This value is set at the factory.
1.3.6.1.4.1.318.1.1.1.13.4.26.1.6ColumnupsDiagSubSysNetworkComCardFirmwareAppRevread-onlymandatoryAn ID string identifying the application firmware revision of the UPS network and display interface communication card.
1.3.6.1.4.1.318.1.1.1.13.4.26.1.7ColumnupsDiagSubSysNetworkComCardFirmwareAppOSRevread-onlymandatoryAn ID string identifying the application operating system firmware revision of the UPS network and display interface communication card.
1.3.6.1.4.1.318.1.1.1.13.4.27ScalarupsDiagSubSysUsrSuppBattMonitorTableSizeread-onlymandatoryThe number of user supplied Battery Monitor Boards attached to the UPS.
1.3.6.1.4.1.318.1.1.1.13.4.28TableupsDiagSubSysUsrSuppBattMonitorTablenot-accessiblemandatoryAllows for diagnostics of the user supplied Battery Monitor Board.
1.3.6.1.4.1.318.1.1.1.13.4.28.1RowupsDiagSubSysUsrSuppBattMonitorEntrynot-accessiblemandatoryThe diagnostics of the user supplied Battery Monitor Board.
1.3.6.1.4.1.318.1.1.1.13.4.28.1.1ColumnupsDiagSubSysUsrSuppBattMonitorIndexread-onlymandatoryThe index of the user supplied Battery Monitor Board.
1.3.6.1.4.1.318.1.1.1.13.4.28.1.2ColumnupsDiagSubSysUsrSuppBattMonitorStatusread-onlymandatoryThe status of the user supplied Battery Monitor Board. unknown(1) indicates the device status is unknown. notInstalled(2) indicates the device is not installed…
1.3.6.1.4.1.318.1.1.1.13.4.28.1.3ColumnupsDiagSubSysUsrSuppBattMonitorFirmwareRevread-onlymandatoryThe firmware revision of the user supplied Battery Monitor Board.
1.3.6.1.4.1.318.1.1.1.13.4.28.1.4ColumnupsDiagSubSysUsrSuppBattMonitorHardwareRevread-onlymandatoryThe hardware revision of the user supplied Battery Monitor Board.
1.3.6.1.4.1.318.1.1.1.13.4.28.1.5ColumnupsDiagSubSysUsrSuppBattMonitorSerialNumread-onlymandatoryThe serial number of the user supplied Battery Monitor Board.
1.3.6.1.4.1.318.1.1.1.13.4.28.1.6ColumnupsDiagSubSysUsrSuppBattMonitorTemperatureread-onlymandatoryThe temperature of the air around the user supplied Battery Monitor Board in tenths of degrees Celsius.
1.3.6.1.4.1.318.1.1.1.13.4.29ScalarupsDiagSubSysUsrSuppBattBreakerStatusread-onlymandatoryThe status of the user supplied Battery Breaker. unknown(1) indicates the circuit breaker status is unknown. notInstalled(2) indicates the circuit breaker is n…
1.3.6.1.4.1.318.1.1.1.13.4.30ScalarupsDiagSubSysPSUTableSizeread-onlymandatoryThe number of Power Supply Units in the UPS.
1.3.6.1.4.1.318.1.1.1.13.4.31TableupsDiagSubSysPSUTablenot-accessiblemandatoryAllows for diagnostics of individual Power Supply Units. The number of entries is contained in the upsDiagSubSysPSUTableSize OID.
1.3.6.1.4.1.318.1.1.1.13.4.31.1RowupsDiagSubSysPSUEntrynot-accessiblemandatoryThe diagnostics information of a Power Supply Unit.
1.3.6.1.4.1.318.1.1.1.13.4.31.1.1ColumnupsDiagSubSysPSUIndexread-onlymandatoryThe index to the Power Supply Unit entry.
1.3.6.1.4.1.318.1.1.1.13.4.31.1.2ColumnupsDiagSubSysPSUStatusread-onlymandatoryThe status of the Power Supply Unit. unknown(1) indicates the device status is unknown. notInstalled(2) indicates the device is not installed. offOk(3) indicat…
1.3.6.1.4.1.318.1.1.1.13.4.32ScalarupsDiagSubSysIDRCTableSizeread-onlymandatoryThe number of ID and Relay Controller Cards attached to the UPS.
1.3.6.1.4.1.318.1.1.1.13.4.33TableupsDiagSubSysIDRCTablenot-accessiblemandatoryAllows for diagnostics of the ID and Relay Controller Card.
1.3.6.1.4.1.318.1.1.1.13.4.33.1RowupsDiagSubSysIDRCEntrynot-accessiblemandatoryThe diagnostics of the ID and Relay Controller Card.
1.3.6.1.4.1.318.1.1.1.13.4.33.1.1ColumnupsDiagSubSysIDRCIndexread-onlymandatoryThe index of the ID and Relay Controller Card.
1.3.6.1.4.1.318.1.1.1.13.4.33.1.2ColumnupsDiagSubSysIDRCStatusread-onlymandatoryThe status of the ID and Relay Controller Card. unknown(1) indicates the device status is unknown. notInstalled(2) indicates the device is not installed. offOk…
1.3.6.1.4.1.318.1.1.1.13.4.33.1.3ColumnupsDiagSubSysIDRCFirmwareRevread-onlymandatoryThe firmware revision of the ID and Relay Controller Card.
1.3.6.1.4.1.318.1.1.1.13.4.33.1.4ColumnupsDiagSubSysIDRCHardwareRevread-onlymandatoryThe hardware revision of the ID and Relay Controller Card.
1.3.6.1.4.1.318.1.1.1.13.4.33.1.5ColumnupsDiagSubSysIDRCSerialNumread-onlymandatoryThe serial number of the ID and Relay Controller Card.
1.3.6.1.4.1.318.1.1.1.13.4.34ScalarupsDiagSubSysExternalConnectorStatusread-onlymandatoryThe status of the external connector board. unknown(1) indicates the device status is unknown. notInstalled(2) indicates the device is not installed. offOk(3) …
1.3.6.1.4.1.318.1.1.1.13.4.35ScalarupsDiagSubSysBackfeedContactorTableSizeread-onlymandatoryThe number of backfeed protection contactor attached to the UPS.
1.3.6.1.4.1.318.1.1.1.13.4.36TableupsDiagSubSysBackfeedContactorTablenot-accessiblemandatoryBackfeed protection contactor table.
1.3.6.1.4.1.318.1.1.1.13.4.36.1RowupsDiagSubSysBackfeedContactorEntrynot-accessiblemandatoryA list of backfeed protection contactors.
1.3.6.1.4.1.318.1.1.1.13.4.36.1.1ColumnupsDiagSubSysbackfeedContactorIndexread-onlymandatoryThe index of the backfeed protection contactor.
1.3.6.1.4.1.318.1.1.1.13.4.36.1.2ColumnupsDiagSubSysbackfeedContactorNameread-writemandatoryThe name of the backfeed protection contactor.
1.3.6.1.4.1.318.1.1.1.13.4.36.1.3ColumnupsDiagSubSysbackfeedContactorTyperead-onlymandatoryIndicates the backfeed protection contactor types available in the UPS system. If the UPS is unable to find any attached contactors, this variable is set to un…
1.3.6.1.4.1.318.1.1.1.13.4.36.1.4ColumnupsDiagSubSysbackfeedContactorStatusread-onlymandatoryThe status of backfeed protection contactor. unknown(1) indicates the contactor status is unknown. opened (2) indicates the contactor is opened. closed (3) ind…
1.3.6.1.4.1.318.1.1.1.13.4.37ScalarupsDiagSubSysIntBypSwitchFanLifetimeInfoTableSizeread-onlymandatoryThe number of backfeed protection contactor attached to the UPS.
1.3.6.1.4.1.318.1.1.1.13.4.38TableupsDiagSubSysIntBypSwitchFanLifetimeInfoTablenot-accessiblemandatoryAllows for diagnostics of the Internal Bypass Switch life time infomation.
1.3.6.1.4.1.318.1.1.1.13.4.38.1RowupsDiagSubSysIntBypSwitchFanLifetimeInfoEntrynot-accessiblemandatoryThe diagnostics of the Internal Bypass Switch.
1.3.6.1.4.1.318.1.1.1.13.4.38.1.1ColumnupsDiagSubSysIntBypSwitchFanLifetimeInfoIndexread-onlymandatoryThe index to the Internal Bypass Switch Fan liftime information entry
1.3.6.1.4.1.318.1.1.1.13.4.38.1.2ColumnupsDiagSubSysIntBypSwitchFanLifetimeStatusread-onlymandatoryThe status of the Internal Bypass Switch Fan lifetime information. ok(1) indicates the device lifetime status is OK. nearEnd(2) indicates the device lifetime s…
1.3.6.1.4.1.318.1.1.1.13.4.38.1.3ColumnupsDiagSubSysIntBypSwitchFanEstmtdLifetimeRmngread-onlymandatoryDisplays the time remaining for the module before it should be replaced. Measured in months. This value is set when you originally install the module.
1.3.6.1.4.1.318.1.1.1.13.4.38.1.4ColumnupsDiagSubSysIntBypSwitchFanEstmtdLifetimeRmngPctread-onlymandatoryDisplays the percentage of the total lifetime remaining for the module before it should be replaced.
1.3.6.1.4.1.318.1.1.1.13.5NodeupsDiagnosticExternalDevices
1.3.6.1.4.1.318.1.1.1.13.5.1NodeupsDiagSwitchGear
1.3.6.1.4.1.318.1.1.1.13.5.1.1ScalarupsDiagSwitchGearStatusread-onlymandatoryThe status of the Switch Gear. unknown(1) indicates the device status is unknown. notInstalled(2) indicates the device is not installed. ok(3) indicates the de…
1.3.6.1.4.1.318.1.1.1.13.5.1.2ScalarupsDiagSwitchGearInputSwitchStatusread-onlymandatoryThe status of the Switch Gear Input Switch. unknown(1) indicates the switch status is unknown. notInstalled(2) indicates the switch is not installed. opened(3)…
1.3.6.1.4.1.318.1.1.1.13.5.1.3ScalarupsDiagSwitchGearOutputSwitchStatusread-onlymandatoryThe status of the Switch Gear Output Switch. unknown(1) indicates the switch status is unknown. notInstalled(2) indicates the switch is not installed. opened(3…
1.3.6.1.4.1.318.1.1.1.13.5.1.4ScalarupsDiagSwitchGearBypassSwitchStatusread-onlymandatoryThe status of the Switch Gear Bypass Switch. unknown(1) indicates the switch status is unknown. notInstalled(2) indicates the switch is not installed. opened(3…
1.3.6.1.4.1.318.1.1.1.13.5.1.5ScalarupsDiagSwitchGearBypassInputSwitchStatusread-onlymandatoryThe status of the Switch Gear Bypass Input Switch. unknown(1) indicates the switch status is unknown. notInstalled(2) indicates the switch is not installed. op…
1.3.6.1.4.1.318.1.1.1.13.5.1.6ScalarupsDiagSwitchGearBreakerTableSizeread-onlymandatoryThe number of switchgear breakers attached to the UPS.
1.3.6.1.4.1.318.1.1.1.13.5.1.7TableupsDiagSwitchGearBreakerTablenot-accessiblemandatorySwitchgear breaker table.
1.3.6.1.4.1.318.1.1.1.13.5.1.7.1RowupsDiagSwitchGearBreakerEntrynot-accessiblemandatoryA list of switchgear breakers.
1.3.6.1.4.1.318.1.1.1.13.5.1.7.1.1ColumnswitchgearBreakerIndexread-onlymandatoryThe index of the switchgear breaker.
1.3.6.1.4.1.318.1.1.1.13.5.1.7.1.2ColumnswitchgearBreakerPresentread-onlymandatoryIndicates if the switchgear breaker is present. notPresent(1) indicates that the breaker is not present. present(2) indicates that the breaker is present.
1.3.6.1.4.1.318.1.1.1.13.5.1.7.1.3ColumnswitchgearBreakerNameread-writemandatoryThe name of the switchgear breaker.
1.3.6.1.4.1.318.1.1.1.13.5.1.7.1.4ColumnswitchgearBreakerTyperead-onlymandatoryIndicates the switchgear breaker types available in the UPS system. If the UPS is unable to find any attached breakers, this variable is set to unknown(1).
1.3.6.1.4.1.318.1.1.1.13.5.1.7.1.5ColumnswitchgearBreakerStatusread-onlymandatoryThe status of switchgear breaker. unknown(1) indicates the breaker status is unknown. opened (2) indicates the breaker is opened. closed (3) indicates the brea…
1.3.6.1.4.1.318.1.1.1.13.5.1.8ScalarupsDiagSubFeedBreakerTableSizeread-onlymandatoryThe number of subfeed breakers attached to the UPS.
1.3.6.1.4.1.318.1.1.1.13.5.1.9TableupsDiagSubFeedBreakerTablenot-accessiblemandatorySubfeed breaker table.
1.3.6.1.4.1.318.1.1.1.13.5.1.9.1RowupsDiagSubFeedBreakerEntrynot-accessiblemandatoryA list of subfeed breakers.
1.3.6.1.4.1.318.1.1.1.13.5.1.9.1.1ColumnsubfeedBreakerIndexread-onlymandatoryThe index of the subfeed breakers.
1.3.6.1.4.1.318.1.1.1.13.5.1.9.1.2ColumnsubfeedBreakerPresentread-onlymandatoryIndicates if the subfeed breaker is present. notPresent (1) indicates that the breaker is not present. present (2) indicates that the breaker is present.
1.3.6.1.4.1.318.1.1.1.13.5.1.9.1.3ColumnsubfeedBreakerRatingread-onlymandatoryThe current rating of the installed subfeed breaker.
1.3.6.1.4.1.318.1.1.1.13.5.1.9.1.4ColumnsubfeedBreakerUpperAcceptPowerWarningread-writemandatoryThe maximum acceptable load before warning is issued. Expressed as percent of the subfeed breaker rating.
1.3.6.1.4.1.318.1.1.1.13.5.1.9.1.5ColumnsubfeedBreakerUpperAcceptPowerCriticalread-writemandatoryThe maximum load before a critical alarm occurs. Expressed as percent of the subfeed breaker rating.
1.3.6.1.4.1.318.1.1.1.13.5.1.9.1.6ColumnsubfeedBreakerStatusread-onlymandatoryThe status of the Circuit Breaker. unknown(1) indicates the circuit breaker status is unknown. notInstalled(2) indicates the circuit breaker is not installed. …
1.3.6.1.4.1.318.1.1.1.13.5.1.9.1.7ColumnsubfeedBreakerNameread-writemandatoryThe name of the subfeed breaker.
1.3.6.1.4.1.318.1.1.1.13.5.1.9.1.8ColumnsubfeedBreakerCurrentread-onlymandatoryThe subfeed current in tenths of Amps.
1.3.6.1.4.1.318.1.1.1.13.5.1.10ScalarupsDiagSwitchGearInstallationLoadPctread-onlymandatoryThe actual output load expressed as a percentage of the rating of the UPS.
1.3.6.1.4.1.318.1.1.1.13.5.1.11TableupsDiagSubFeedPhaseTablenot-accessiblemandatoryA list of subfeed phase table.
1.3.6.1.4.1.318.1.1.1.13.5.1.11.1RowupsDiagSubFeedPhaseEntrynot-accessiblemandatoryAn entry containing information applicable to a particular phase.
1.3.6.1.4.1.318.1.1.1.13.5.1.11.1.1ColumnupsDiagSubFeedBreakerIndexread-onlymandatoryThe subfeed breaker index.
1.3.6.1.4.1.318.1.1.1.13.5.1.11.1.2ColumnupsDiagSubFeedPhaseIndexread-onlymandatoryThe subfeed phase index.
1.3.6.1.4.1.318.1.1.1.13.5.1.11.1.3ColumnupsDiagSubFeedPhaseCurrentread-onlymandatoryThe subfeed phase current in Amps.
1.3.6.1.4.1.318.1.1.1.13.5.1.11.1.4ColumnupsDiagSubFeedPhaseCurrentAlternateread-onlymandatoryThe subfeed phase current in tenths of Amps.
1.3.6.1.4.1.318.1.1.1.13.5.1.12ScalarupsDiagSwitchgearSerialNumberread-onlymandatoryThe serial number of the UPS I/O Cabinet.
1.3.6.1.4.1.318.1.1.1.13.5.1.13ScalarupsDiagSwitchgearAmbientTemperatureread-onlymandatoryThe ambient temperature of I/O Cabinet in tenths of degrees Celsius.
1.3.6.1.4.1.318.1.1.1.13.5.1.14ScalarupsDiagUsrSuppSwitchgearMonitorTableSizeread-onlymandatoryThe number of user supplied Switch Gear Monitor Boards attached to the UPS.
1.3.6.1.4.1.318.1.1.1.13.5.1.15TableupsDiagUsrSuppSwitchgearMonitorTablenot-accessiblemandatoryAllows for diagnostics of the user supplied Switch Gear Monitor Board.
1.3.6.1.4.1.318.1.1.1.13.5.1.15.1RowupsDiagUsrSuppSwitchgearMonitorEntrynot-accessiblemandatoryThe diagnostics of the user supplied Switch Gear Monitor Board.
1.3.6.1.4.1.318.1.1.1.13.5.1.15.1.1ColumnupsDiagUsrSuppSwitchgearMonitorIndexread-onlymandatoryThe index of the user supplied Switch Gear Monitor Board.
1.3.6.1.4.1.318.1.1.1.13.5.1.15.1.2ColumnupsDiagUsrSuppSwitchgearMonitorStatusread-onlymandatoryThe status of the user supplied Switch Gear Monitor Board. unknown(1) indicates the device status is unknown. notInstalled(2) indicates the device is not insta…
1.3.6.1.4.1.318.1.1.1.13.5.1.15.1.3ColumnupsDiagUsrSuppSwitchgearMonitorFirmwareRevread-onlymandatoryThe firmware revision of the user supplied Switch Gear Monitor Board.
1.3.6.1.4.1.318.1.1.1.13.5.1.15.1.4ColumnupsDiagUsrSuppSwitchgearMonitorHardwareRevread-onlymandatoryThe hardware revision of the user supplied Switch Gear Monitor Board.
1.3.6.1.4.1.318.1.1.1.13.5.1.15.1.5ColumnupsDiagUsrSuppSwitchgearMonitorSerialNumread-onlymandatoryThe serial number of the user supplied Switch Gear Monitor Board.
1.3.6.1.4.1.318.1.1.1.13.5.1.15.1.6ColumnupsDiagUsrSuppSwitchgearMonitorTemperatureread-onlymandatoryThe temperature of the air around the user supplied Switch Gear Monitor Board in tenths of degrees Celsius.
1.3.6.1.4.1.318.1.1.1.13.5.2NodeupsDiagMCCBBox
1.3.6.1.4.1.318.1.1.1.13.5.2.1ScalarupsDiagMCCBBoxStatusread-onlymandatoryThe status of the MCCB Box (Molded Case Circuit Breaker Box) external device. unknown(1) indicates the device status is unknown. notInstalled(2) indicates the …
1.3.6.1.4.1.318.1.1.1.13.5.3NodeupsDiagTransformer
1.3.6.1.4.1.318.1.1.1.13.5.3.1ScalarupsDiagTransformerStatusread-onlymandatoryThe status of the External Transformer. unknown(1) indicates the device status is unknown. notInstalled(2) indicates the device is not installed. ok(3) indicat…
1.3.6.1.4.1.318.1.1.1.13.5.4NodeupsDiagFlyWheel
1.3.6.1.4.1.318.1.1.1.13.5.4.1ScalarupsDiagFlyWheelStatusread-onlymandatoryIndicates the status of flywheel connected to UPS. If the UPS is unable to determine the state of flywheel, this variable is set to unknown(1).
1.3.6.1.4.1.318.1.1.1.13.6NodeupsDiagnosticComBus
1.3.6.1.4.1.318.1.1.1.13.6.1ScalarupsDiagComBusInternalMIMStatusread-onlymandatoryThe status of the internal MIM communication bus. unknown(1) indicates the device status is unknown. notInstalled(2) indicates the device is not installed. ok(…
1.3.6.1.4.1.318.1.1.1.13.6.2ScalarupsDiagComBusInternalRIMStatusread-onlymandatoryThe status of the internal RIM communication bus. unknown(1) indicates the device status is unknown. notInstalled(2) indicates the device is not installed. ok(…
1.3.6.1.4.1.318.1.1.1.13.6.3ScalarupsDiagComBusMIMtoRIMStatusread-onlymandatoryThe status of the MIM to RIM communication bus. unknown(1) indicates the device status is unknown. notInstalled(2) indicates the device is not installed. ok(3)…
1.3.6.1.4.1.318.1.1.1.13.6.4ScalarupsDiagComBusExternalMIMStatusread-onlymandatoryThe status of the external MIM communication bus. unknown(1) indicates the device status is unknown. notInstalled(2) indicates the device is not installed. ok(…
1.3.6.1.4.1.318.1.1.1.13.6.5ScalarupsDiagComBusExternalRIMStatusread-onlymandatoryThe status of the external RIM communication bus. unknown(1) indicates the device status is unknown. notInstalled(2) indicates the device is not installed. ok(…
1.3.6.1.4.1.318.1.1.1.13.7NodeupsDiagnosticPowerCabinet
1.3.6.1.4.1.318.1.1.1.13.7.1ScalarupsDiagnosticPowerCabinetTableSizeread-onlymandatoryThe maximum number of Power Cabinets supported by the UPS.
1.3.6.1.4.1.318.1.1.1.13.7.2TableupsDiagnosticPowerCabinetTablenot-accessiblemandatoryAllows for diagnostics of individual Power Cabinets. The number of entries is contained in the upsDiagnosticPowerCabinetTableSize OID.
1.3.6.1.4.1.318.1.1.1.13.7.2.1RowupsDiagnosticPowerCabinetEntrynot-accessiblemandatoryThe diagnostics of a Power Cabinet.
1.3.6.1.4.1.318.1.1.1.13.7.2.1.1ColumnupsDiagnosticPowerCabinetIndexread-onlymandatoryThe index to the Power Cabinet.
1.3.6.1.4.1.318.1.1.1.13.7.2.1.2ColumnupsDiagnosticPowerCabinetAmbientTemperatureread-onlymandatoryThe ambient temperature of Power Cabinet in tenths of degrees Celsius. If the Power Cabinet is not present, this variable is set to (-1).
1.3.6.1.4.1.318.1.1.1.13.8NodeupsDiagnosticDisplay
1.3.6.1.4.1.318.1.1.1.13.8.1ScalarupsDiagnosticDisplayHardwareRevread-onlymandatoryThe hardware revision of the Display.
1.3.6.1.4.1.318.1.1.1.13.8.2ScalarupsDiagnosticDisplaySerialNumread-onlymandatoryThe serial number of the Display.
1.3.6.1.4.1.318.1.1.1.13.8.3ScalarupsDiagnosticDisplayFirmwareRevread-onlymandatoryThe firmware revision of the Display.
1.3.6.1.4.1.318.1.1.1.13.8.4ScalarupsDiagnosticDisplayModelNumread-onlymandatoryThe model number of the Display.
1.3.6.1.4.1.318.1.1.1.13.8.5ScalarupsDiagnosticDisplayStatusread-onlymandatoryThe System Level Controller Status. unknown(1) indicates the device status is unknown. notInstalled(2) indicates the device is not installed. offOk(3) indicate…
1.3.6.1.4.1.318.1.1.1.13.9NodeupsDiagnosticUnitController
1.3.6.1.4.1.318.1.1.1.13.9.1ScalarupsDiagUnitControllerTableSizeread-onlymandatoryThe number of Unit Controllers in or attached to the UPS.
1.3.6.1.4.1.318.1.1.1.13.9.2TableupsDiagUnitControllerTablenot-accessiblemandatoryAllows for diagnostics of individual Intelligence Modules. The number of entries is contained in the upsDiagUnitControllerTableSize OID.
1.3.6.1.4.1.318.1.1.1.13.9.2.1RowupsDiagUnitControllerEntrynot-accessiblemandatoryThe diagnostics and information of an Intelligence Module.
1.3.6.1.4.1.318.1.1.1.13.9.2.1.1ColumnupsDiagUnitControllerIndexread-onlymandatoryThe index to the Unit Controller entry.
1.3.6.1.4.1.318.1.1.1.13.9.2.1.2ColumnupsDiagUnitControllerStatusread-onlymandatoryThe status of the Unit Controller. unknown(1) indicates the device status is unknown. notInstalled(2) indicates the device is not installed. offOk(3) indicates…
1.3.6.1.4.1.318.1.1.1.13.9.2.1.3ColumnupsDiagUnitControllerFirmwareRevread-onlymandatoryThe firmware revision of the Unit Controller.
1.3.6.1.4.1.318.1.1.1.13.9.2.1.4ColumnupsDiagUnitControllerHardwareRevread-onlymandatoryThe hardware revision of the Unit Controller.
1.3.6.1.4.1.318.1.1.1.13.9.2.1.5ColumnupsDiagUnitControllerSerialNumread-onlymandatoryThe serial number of the Unit Controller.
1.3.6.1.4.1.318.1.1.1.13.9.2.1.6ColumnupsDiagUnitControllerModelNumread-onlymandatoryThe model number of the Unit Controller.
1.3.6.1.4.1.318.1.1.1.13.10NodeupsDiagnosticSLC
1.3.6.1.4.1.318.1.1.1.13.10.1ScalarupsDiagnosticSLCHardwareRevread-onlymandatoryThe hardware revision of the System Level Controller.
1.3.6.1.4.1.318.1.1.1.13.10.2ScalarupsDiagnosticSLCSerialNumread-onlymandatoryThe serial number of the System Level Controller.
1.3.6.1.4.1.318.1.1.1.13.10.3ScalarupsDiagnosticSLCFirmwareRevread-onlymandatoryThe firmware revision of the System Level Controller.
1.3.6.1.4.1.318.1.1.1.13.10.4ScalarupsDiagnosticSLCModelNumberread-onlymandatoryThe Model number of the System Level Controller.
1.3.6.1.4.1.318.1.1.1.13.10.5ScalarupsDiagSLCStatusread-onlymandatoryThe System Level Controller Status. unknown(1) indicates the device status is unknown. notInstalled(2) indicates the device is not installed. offOk(3) indicate…
1.3.6.1.4.1.318.1.1.1.14NodeupsParallelSystem
1.3.6.1.4.1.318.1.1.1.14.1ScalarupsParallelSysLocalAddressread-writemandatoryDefines the UPS ID number in the parallel system.
1.3.6.1.4.1.318.1.1.1.14.2ScalarupsParallelSysRemoteAddressread-writemandatoryDefines the total number of UPSs in parallel.
1.3.6.1.4.1.318.1.1.1.14.3ScalarupsParallelSysRedundancyread-writemandatoryThe redundancy warning level for paralleled UPS nplus0 (1) indicates that there are no redundant units. nplus1 (2) indicates that there is one redundant unit. …
1.3.6.1.4.1.318.1.1.1.14.4ScalarupsParallelInputMaximumCurrentread-onlymandatoryMaximum input RMS current of the parallel system measured in Amperes.
1.3.6.1.4.1.318.1.1.1.14.5ScalarupsParallelTotalOutputPowerread-onlymandatoryThe Total Ouptut power of UPS in KW when UPS are configured in parallel or -1 if it's unsupported by this UPS.
1.3.6.1.4.1.318.1.1.1.14.6ScalarupsParallelTotalOutputApparentPowerread-onlymandatoryThe Total Ouptut Apparent power of UPS in kVA when UPS are configured in parallel or -1 if it's unsupported by this UPS.
1.3.6.1.4.1.318.1.1.1.14.7TableupsParallelInputPhaseTablenot-accessiblemandatoryA list of input table entries.
1.3.6.1.4.1.318.1.1.1.14.7.1RowupsParallelInputPhaseEntrynot-accessiblemandatoryAn entry containing information applicable to a particular input phase.
1.3.6.1.4.1.318.1.1.1.14.7.1.1ColumnupsParallelInputPhaseTableIndexread-onlymandatoryThe parallel unit identifier.
1.3.6.1.4.1.318.1.1.1.14.7.1.2ColumnupsParallelInputPhaseIndexread-onlymandatoryThe input phase identifier.
1.3.6.1.4.1.318.1.1.1.14.7.1.3ColumnupsParallelInputCurrentread-onlymandatoryThe input current in amperes, or -1 if it's unsupported by this UPS.
1.3.6.1.4.1.318.1.1.1.14.7.1.4ColumnupsParallelInputActivePowerread-onlymandatoryThe input power in kW, or -1 if it's unsupported by this UPS.
1.3.6.1.4.1.318.1.1.1.14.7.1.5ColumnupsParallelInputApparentPowerread-onlymandatoryThe input apparent power in kVA, or -1 if it's unsupported by this UPS.
1.3.6.1.4.1.318.1.1.1.14.7.1.6ColumnupsParallelInputVoltageread-onlymandatoryThe input voltage of UPS in volts, or -1 if it's unsupported by this UPS.
1.3.6.1.4.1.318.1.1.1.14.7.1.7ColumnupsParallelInputMaxVoltageread-onlymandatoryThe peak input voltage in VAC measured since the last reset, or -1 if it's unsupported by this UPS.
1.3.6.1.4.1.318.1.1.1.14.7.1.8ColumnupsParallelInputMaxCurrentread-onlymandatoryThe peak input current in amperes measured since last reset, or -1 if it's unsupported by this UPS.
1.3.6.1.4.1.318.1.1.1.14.7.1.9ColumnupsParallelInputTotalActivePowerread-onlymandatoryTotal active input power of the parallel system in kW.
1.3.6.1.4.1.318.1.1.1.14.7.1.10ColumnupsParallelInputTotalApparentPowerread-onlymandatoryTotal apparent input power of the parallel system in kVA.
1.3.6.1.4.1.318.1.1.1.14.8TableupsParallelOutputPhaseTablenot-accessiblemandatoryA list of output table entries. The number of entries is given by the sum of the upsPhaseNumOutputPhases.
1.3.6.1.4.1.318.1.1.1.14.8.1RowupsParallelOutputPhaseEntrynot-accessiblemandatoryAn entry containing information applicable to a particular output phase.
1.3.6.1.4.1.318.1.1.1.14.8.1.1ColumnupsParallelOutputPhaseTableIndexread-onlymandatoryThe output identifier.
1.3.6.1.4.1.318.1.1.1.14.8.1.2ColumnupsParallelOutputPhaseIndexread-onlymandatoryThe output phase identifier.
1.3.6.1.4.1.318.1.1.1.14.8.1.3ColumnupsParallelOutputCurrentread-onlymandatoryThe output current in amperes drawn by the load on the UPS, or -1 if it's unsupported by this UPS.
1.3.6.1.4.1.318.1.1.1.14.8.1.4ColumnupsParallelOutputLoadread-onlymandatoryThe output load in VA, or -1 if it's unsupported by this UPS.
1.3.6.1.4.1.318.1.1.1.14.8.1.5ColumnupsParallelOutputPercentLoadread-onlymandatoryThe percentage of the UPS load capacity in VA at present redundancy being used on this output phase, or -1 if it's unsupported by this UPS.
1.3.6.1.4.1.318.1.1.1.14.8.1.6ColumnupsParallelOutputPowerread-onlymandatoryThe output power in Watts, or -1 if it's unsupported by this UPS.
1.3.6.1.4.1.318.1.1.1.14.9TableupsParallelOutputApparentPowerTablenot-accessiblemandatoryA list of output table entries. The number of entries is given by the value of upsOutputNumPhases.
1.3.6.1.4.1.318.1.1.1.14.9.1RowupsParallelOutputApparentPowerEntrynot-accessiblemandatoryAn entry containing information applicable to a particular output.
1.3.6.1.4.1.318.1.1.1.14.9.1.1ColumnupsParallelOutputApparentPowerTableIndexread-onlymandatoryThe UPS parallel output identifier.
1.3.6.1.4.1.318.1.1.1.14.9.1.2ColumnupsParallelOutputApparentPowerread-onlymandatoryThe apparent power of each of UPS in kVA when UPS are configured in parallel.
1.3.6.1.4.1.318.1.1.1.14.10TableupsParallelDiagSubSysBreakerTablenot-accessiblemandatoryAllows for diagnostics of parallel Circuit Breakers.
1.3.6.1.4.1.318.1.1.1.14.10.1RowupsParallelDiagSubSysBreakerEntrynot-accessiblemandatoryThe diagnostics of Circuit Breaker.
1.3.6.1.4.1.318.1.1.1.14.10.1.1ColumnupsParallelDiagSubSysBreakerFrameIndexread-onlymandatoryThe Parallel UPS index entry.
1.3.6.1.4.1.318.1.1.1.14.10.1.2ColumnupsParallelDiagSubSysBreakerIndexread-onlymandatoryThe index of the Circuit Breaker.
1.3.6.1.4.1.318.1.1.1.14.10.1.3ColumnupsParallelDiagSubSysBreakerStatusread-onlymandatoryThe status of the Circuit Breaker. unknown(1) indicates the circuit breaker status is unknown. notInstalled(2) indicates the circuit breaker is not installed. …
1.3.6.1.4.1.318.1.1.1.14.10.1.4ColumnupsParallelDiagSubSysBreakerNameread-onlymandatoryThe name of Circuit Breaker.
1.3.6.1.4.1.318.1.1.1.14.11ScalarupsParallelOutputTotalPercentLoadread-onlymandatoryThe percentage of the UPS total load capacity in kVA or -1 if it's unsupported by this UPS.
1.3.6.1.4.1.318.1.1.1.14.12TableupsParallelOutputActivePowerTablenot-accessiblemandatoryA list of output table entries. The number of entries is given by the value of upsParallelSysRemoteAddress.
1.3.6.1.4.1.318.1.1.1.14.12.1RowupsParallelOutputActivePowerEntrynot-accessiblemandatoryAn entry containing information applicable to a particular output.
1.3.6.1.4.1.318.1.1.1.14.12.1.1ColumnupsParallelOutputActivePowerTableIndexread-onlymandatoryThe UPS parallel output identifier.
1.3.6.1.4.1.318.1.1.1.14.12.1.2ColumnupsParallelOutputActivePowerread-onlymandatoryThe active power of each UPS in kW when UPSs are configured in parallel.
1.3.6.1.4.1.318.1.1.1.14.13ScalarupsParallelSysSwitchGearInstallationLoadPctread-onlymandatoryThe actual output load expressed as a percentage of the rating of the Parallel UPS system.
1.3.6.1.4.1.318.1.1.1.14.14ScalarupsParallelSysRedundancyStatusread-onlymandatoryDisplays the number of backup or redundant UPSs set up on the parallel system. nplus0 (1) no redundant units. nplus1 (2) one redundant unit. nplus2 (3) two red…
1.3.6.1.4.1.318.1.1.1.14.15ScalarupsParallelSysNameread-writemandatoryAn ID string for the group of UPS units in the same parallel system. Some products do not allow write operations for this OID.
1.3.6.1.4.1.318.1.1.1.14.16ScalarupsParallelSysUpsTableSizeread-onlymandatoryThe number of UPSs in parallel.
1.3.6.1.4.1.318.1.1.1.14.17TableupsParallelSysUpsTablenot-accessiblemandatoryA list of UPS table entries. The number of entries is given by the value of upsParallelSysUpsTableize.
1.3.6.1.4.1.318.1.1.1.14.17.1RowupsParallelSysUpsEntrynot-accessiblemandatoryAn entry containing information applicable to a particular UPS in parallel.
1.3.6.1.4.1.318.1.1.1.14.17.1.1ColumnupsParallelSysUpsIndexread-onlymandatoryThe index to the Parallel System UPS table entry.
1.3.6.1.4.1.318.1.1.1.14.17.1.2ColumnupsParallelSysUpsNameread-onlymandatoryThe UPS id as assigned by the system.
1.3.6.1.4.1.318.1.1.1.14.17.1.3ColumnupsParallelSysUpsAlarmStatusread-onlymandatoryThe alarm status of the UPS. unknown(1) indicates the UPS status is unknown. normal(2) indicates UPS is functioning normally. informational(3) indicates inform…
1.3.6.1.4.1.318.1.1.1.14.17.1.4ColumnupsParallelSysUpsModeread-onlymandatoryThe current operating mode of the UPS. If the UPS is unable to determine the state of the UPS, this variable is set to unknown(1).
1.3.6.1.4.1.318.1.1.1.14.18ScalarupsParallelNumOfUpsPoweringLoadread-onlymandatoryNumber of UPS powered and protecting the load which are not defective (no battery fault, no internal fault).
1.3.6.1.4.1.318.1.1.1.14.19ScalarupsParallelMinNumOfRequiredUpsread-onlymandatoryMinimal number of UPS required to guarantee the availability of power.
1.3.6.1.4.1.318.1.1.1.15NodeupsPhysicalLayout
1.3.6.1.4.1.318.1.1.1.15.1ScalarupsIOFrameLayoutPositionIDread-onlymandatoryDefines the position ID of UPS frame.
1.3.6.1.4.1.318.1.1.1.15.2ScalarupsBottomFeedFrameLayoutPositionIDread-onlymandatoryDefines the position ID of bottom feed frame.
1.3.6.1.4.1.318.1.1.1.15.3ScalarupsSwitchGearLayoutPositionIDread-onlymandatoryDefines the position ID of switchgear.
1.3.6.1.4.1.318.1.1.1.15.4ScalarupsBatteryFrameLayoutTableSizeread-onlymandatoryThe number of battery frames.
1.3.6.1.4.1.318.1.1.1.15.5TableupsBatteryFrameLayoutTablenot-accessiblemandatoryBattery frame layout position ID table.
1.3.6.1.4.1.318.1.1.1.15.5.1RowupsBatteryFrameLayoutEntrynot-accessiblemandatoryA list of layout position IDs of battery frames.
1.3.6.1.4.1.318.1.1.1.15.5.1.1ColumnbatteryFrameIndexread-onlymandatoryThe index of the battery frame.
1.3.6.1.4.1.318.1.1.1.15.5.1.2ColumnbatteryFramePositionIDread-onlymandatoryDefines the position ID of each of the battery frames in the row.
1.3.6.1.4.1.318.1.1.1.15.6ScalarupsSideCarFrameLayoutTableSizeread-onlymandatoryThe number of sidecar frames.
1.3.6.1.4.1.318.1.1.1.15.7TableupsSideCarFrameLayoutTablenot-accessiblemandatorySidecar frame layout position ID table.
1.3.6.1.4.1.318.1.1.1.15.7.1RowupsSideCarFrameLayoutEntrynot-accessiblemandatoryA list of sidecar frame layout position IDs.
1.3.6.1.4.1.318.1.1.1.15.7.1.1ColumnsideCarFrameIndexread-onlymandatoryThe index of the sidecar frame.
1.3.6.1.4.1.318.1.1.1.15.7.1.2ColumnsideCarFramePositionIDread-onlymandatoryDefines the position ID of each of the sidecar frames in the row.
1.3.6.1.4.1.318.1.1.1.15.8ScalarupsPowerFrameLayoutTableSizeread-onlymandatoryThe number of power frames.
1.3.6.1.4.1.318.1.1.1.15.9TableupsPowerFrameLayoutTablenot-accessiblemandatoryPower frame layout position ID table.
1.3.6.1.4.1.318.1.1.1.15.9.1RowupsPowerFrameLayoutEntrynot-accessiblemandatoryA list of power frame layout position IDs.
1.3.6.1.4.1.318.1.1.1.15.9.1.1ColumnpowerFrameIndexread-onlymandatoryThe index of the power frame.
1.3.6.1.4.1.318.1.1.1.15.9.1.2ColumnpowerFramePositionIDread-onlymandatoryDefines the position ID of each of the power frames in the row.
1.3.6.1.4.1.318.1.1.1.16NodeupsIntegratedATS
1.3.6.1.4.1.318.1.1.1.16.1ScalarupsIntegratedATSSelectedSourceread-onlymandatoryThe source which is currently selected by the ATS to supply the UPS.
1.3.6.1.4.1.318.1.1.1.16.2ScalarupsIntegratedATSPreferredSourceread-writemandatoryThe preferred source of power when both sources are OK.
1.3.6.1.4.1.318.1.1.1.16.3ScalarupsIntegratedATSUpsReturnStaggeringread-writemandatoryThis is a delay factor applied to the retransfer of this UPS with integrated ATS. When multiple UPSs are in use from a single source, each UPS can have a uniqu…
1.3.6.1.4.1.318.1.1.1.16.4ScalarupsIntegratedATSSourceTableSizeread-onlymandatoryThe number of input sources for this integrated ATS.
1.3.6.1.4.1.318.1.1.1.16.5TableupsIntegratedATSSourceTablenot-accessiblemandatoryAllows for getting status and settings for the ATS input sources. The number of entries is contained in the upsIntegratedATSSourceTableSize OID.
1.3.6.1.4.1.318.1.1.1.16.5.1RowupsIntegratedATSSourceEntrynot-accessiblemandatoryThe input source status to get.
1.3.6.1.4.1.318.1.1.1.16.5.1.1ColumnupsIntegratedATSSourceIndexread-onlymandatoryThe index to the input source entry.
1.3.6.1.4.1.318.1.1.1.16.5.1.2ColumnupsIntegratedATSSourceNameread-onlymandatoryThe name of the input source. This OID is provided for informational purposes only.
1.3.6.1.4.1.318.1.1.1.16.5.1.3ColumnupsIntegratedATSSourceStatusread-onlymandatoryGetting this variable will return the input source status.
1.3.6.1.4.1.318.1.1.1.16.5.1.4ColumnupsIntegratedATSLineFailDelayread-writemandatoryThe delay between a selected input source becoming bad, and the ATS switching away from that source. This delay is used to make sure that the line has truly fa…
1.3.6.1.4.1.318.1.1.1.16.5.1.5ColumnupsIntegratedATSLineStabilityDelayread-writemandatoryThe delay between an unselected input source becoming good, and the ATS switching to that source. This delay is used to make sure that the line has truly retur…
1.3.6.1.4.1.318.1.1.1.17NodeupsDCOutput
1.3.6.1.4.1.318.1.1.1.17.1NodeupsDCOutputStatus
1.3.6.1.4.1.318.1.1.1.17.1.1ScalarupsDCOutputStatusTableSizeread-onlymandatoryThe number of DC outputs on the UPS.
1.3.6.1.4.1.318.1.1.1.17.1.2TableupsDCOutputStatusTablenot-accessiblemandatoryProvides status information on UPS DC outputs. The number of entries is contained in the upsDCOutputStatusTableSize OID.
1.3.6.1.4.1.318.1.1.1.17.1.2.1RowupsDCOutputStatusEntrynot-accessiblemandatoryThe DC output.
1.3.6.1.4.1.318.1.1.1.17.1.2.1.1ColumnupsDCOutputStatusTableIndexread-onlymandatoryThe index to the DC output status entry.
1.3.6.1.4.1.318.1.1.1.17.1.2.1.2ColumnupsDCOutputStatusVoltageNominalread-onlymandatoryThe desired voltage for this output in tenths of VDC. When the output is on and there are no fault conditions, the actual voltage should be near the nominal.
1.3.6.1.4.1.318.1.1.1.17.1.2.1.3ColumnupsDCOutputStatusCurrentRatingread-onlymandatoryThe amount of current this output is able to supply in tenths of amperes.
1.3.6.1.4.1.318.1.1.1.17.1.2.1.4ColumnupsDCOutputStatusVoltageread-onlymandatoryThe voltage measured on this output in tenths of VDC.
1.3.6.1.4.1.318.1.1.1.17.1.2.1.5ColumnupsDCOutputStatusCurrentread-onlymandatoryThe current drawn by the load measured on this output in tenths of amperes.
1.3.6.1.4.1.318.1.1.1.17.1.2.1.6ColumnupsDCOutputStatusAbnormalConditionsread-onlymandatoryAn ASCII string containing flags representing active output faults. If the Network Card is unable to determine the state of the faults, this variable is set to…
1.3.6.1.4.1.318.1.1.1.18NodeupsIntegratedUIO
1.3.6.1.4.1.318.1.1.1.18.1NodeupsOutputRelays
1.3.6.1.4.1.318.1.1.1.18.1.1ScalarupsOutputRelayStatusTableSizeread-onlymandatoryThe number of integrated output relays on the UPS.
1.3.6.1.4.1.318.1.1.1.18.1.2TableupsOutputRelayStatusTablenot-accessiblemandatoryAllows for access of individual relays.
1.3.6.1.4.1.318.1.1.1.18.1.2.1RowupsOutputRelayStatusEntrynot-accessiblemandatoryThe output relays to access.
1.3.6.1.4.1.318.1.1.1.18.1.2.1.1ColumnupsOutputRelayIndexread-onlymandatoryThe index to the output relay entry.
1.3.6.1.4.1.318.1.1.1.18.1.2.1.2ColumnupsOutputRelayStateread-onlymandatoryGetting this variable will return the output relay state. 1 - normal state 2 - abnormal state
1.3.6.1.4.1.318.1.1.1.20NodeupsEnergyEfficiency
1.3.6.1.4.1.318.1.1.1.20.1NodeupsECOmode
1.3.6.1.4.1.318.1.1.1.20.1.1ScalarupsEcoModeFreqTransferRangeread-onlymandatoryIndicates tolerance of bypass AC frequency in Hz to switch on ECO mode.
1.3.6.1.4.1.318.1.1.1.20.1.2ScalarupsEcoModeHighVoltThresholdread-onlymandatoryIndicates high threshold on AC voltage in volts to switch on ECO mode.
1.3.6.1.4.1.318.1.1.1.20.1.3ScalarupsEcoModeLowVoltThresholdread-onlymandatoryIndicates low threshold on AC voltage in volts to switch on ECO mode.
1.3.6.1.4.1.318.1.1.1.20.1.4ScalarupsEcoModeSettingread-onlymandatoryIndicates whether ECO feature is avaiable to this UPS or not.
1.3.6.1.4.1.318.1.1.1.20.1.5ScalarupsEcoModeStatusread-onlymandatoryIndicates whether UPS is running in ECO mode or not.
1.3.6.1.4.1.318.1.1.1.20.1.6ScalarupsEcoModeCountSinceResetread-onlymandatoryNumber of times UPS entered into ECO mode since maintenance reset.
1.3.6.1.4.1.318.1.1.1.20.1.7ScalarupsEcoModeOnlineSinceCommissionread-onlymandatoryTotal runtime in online mode with ECO feature enabled once product is authorized to use (in minutes).
1.3.6.1.4.1.318.1.1.1.20.1.8ScalarupsEcoModeOnlineSinceResetread-onlymandatoryTotal runtime in online mode with ECO feature enabled since maintenance reset (in minutes).
1.3.6.1.4.1.318.1.1.1.20.1.9ScalarupsEcoModeTotalPercentTimeSinceResetread-onlymandatoryIndicates percentage of runtime in ECO mode since maintenance reset.
1.3.6.1.4.1.318.1.1.1.20.1.10ScalarupsEcoModePercentTimeSinceCommissionread-onlymandatoryIndicates percentage of operation time in ECO mode once product is authorized to use.
1.3.6.1.4.1.318.1.1.1.20.1.11ScalarupsEcoModeTotalTimeSinceResetread-onlymandatoryTotal runtime of UPS in ECO mode since maintenance reset (in minutes).
1.3.6.1.4.1.318.1.1.1.20.1.12ScalarupsEcoModeTotalTimeSinceCommissionread-onlymandatoryTotal runtime in ECO mode once product is authorized to use (in minutes).
1.3.6.1.4.1.318.1.1.1.20.1.13ScalarupsEcoModeTotalTimeInMonthread-onlymandatoryTotal runtime of UPS in ECO mode since beginning of month (in minutes).
1.3.6.1.4.1.318.1.1.1.20.2NodeupsEBMmode
1.3.6.1.4.1.318.1.1.1.20.2.1ScalarupsEbmModeSettingread-onlymandatoryIndicates whether efficiency booster mode feature is avaiable to this UPS or not.
1.3.6.1.4.1.318.1.1.1.20.2.2ScalarupsEbmModeStatusread-onlymandatoryIndicates whether UPS is running on EBM mode or not.
1.3.6.1.4.1.318.1.1.1.20.2.3ScalarupsEbmModeCountSinceResetread-onlymandatoryNumber of times UPS entered into efficiency booster mode since maintenance reset.
1.3.6.1.4.1.318.1.1.1.20.2.4ScalarupsEbmModeTotalTimeInMonthread-onlymandatoryTotal runtime of UPS in efficiency booster mode since beginning of month (in minutes).
1.3.6.1.4.1.318.1.1.1.20.2.5ScalarupsEbmModeTotalTimeSinceResetread-onlymandatoryTotal runtime of UPS in efficiency booster mode since maintenance reset (in minutes).
1.3.6.1.4.1.318.1.1.1.20.2.6ScalarupsEbmModeTotalPercentTimeSinceResetread-onlymandatoryIndicates percentage of runtime in efficiency booster mode since maintenance reset.
1.3.6.1.4.1.318.1.1.1.20.2.7ScalarupsEbmModeOnlineSinceCommissionread-onlymandatoryIndicates runtime in online mode with EBM feature enabled once product is authorized to use (in minutes).
1.3.6.1.4.1.318.1.1.1.20.2.8ScalarupsEbmModePercentTimeSinceCommissionread-onlymandatoryIndicates percentage of operation time in efficiency booster mode once product is authorized to use.
1.3.6.1.4.1.318.1.1.1.20.2.9ScalarupsEbmModeRuntimeSinceCommissionread-onlymandatoryTotal runtime in efficiency booster mode once product is authorized to use (in minutes).
1.3.6.1.4.1.318.1.1.1.20.2.10ScalarupsEbmModeOnlineSinceResetread-onlymandatoryTotal runtime in online mode with EBM feature enabled since maintenance reset (in minutes).
1.3.6.1.4.1.318.1.1.1.20.2.11ScalarupsEbmModeUpsCountread-onlymandatoryNumber of UPS's running in efficiency booster mode.
1.3.6.1.4.1.318.1.1.2NodemeasureUps
1.3.6.1.4.1.318.1.1.2.1NodemUpsEnviron
1.3.6.1.4.1.318.1.1.2.1.1ScalarmUpsEnvironAmbientTemperatureread-onlymandatoryThe ambient temperature in Celsius for Probe 1.
1.3.6.1.4.1.318.1.1.2.1.2ScalarmUpsEnvironRelativeHumidityread-onlymandatoryThe relative humidity as a percentage for Probe 1.
1.3.6.1.4.1.318.1.1.2.1.3ScalarmUpsEnvironAmbientTemperature2read-onlymandatoryThe ambient temperature in Celsius for Probe 2.
1.3.6.1.4.1.318.1.1.2.1.4ScalarmUpsEnvironRelativeHumidity2read-onlymandatoryThe relative humidity as a percentage for Probe 2.
1.3.6.1.4.1.318.1.1.2.2NodemUpsContact
1.3.6.1.4.1.318.1.1.2.2.1ScalarmUpsContactNumContactsread-onlymandatoryThe number of contacts supported by the Measure-UPS.
1.3.6.1.4.1.318.1.1.2.2.2TablemUpsContactTablenot-accessiblemandatoryA list of contacts supported by the Measure-UPS.
1.3.6.1.4.1.318.1.1.2.2.2.1RowmUpsContactEntrynot-accessiblemandatoryA contact entry containing information for a given contact.
1.3.6.1.4.1.318.1.1.2.2.2.1.1ColumncontactNumberread-onlymandatoryAn index identifying the contact on the Measure-UPS.
1.3.6.1.4.1.318.1.1.2.2.2.1.2ColumnnormalStateread-writemandatoryThe normal operating position of the contact. If the normal operating position cannot be set then it is controlled via the dip switch on the Measure-UPS and is…
1.3.6.1.4.1.318.1.1.2.2.2.1.3Columndescriptionread-writemandatoryThe description of the purpose/use of the contact.
1.3.6.1.4.1.318.1.1.2.2.2.1.4ColumnmonitoringStatusread-writemandatoryA flag indicating whether this contact is monitored, or not.
1.3.6.1.4.1.318.1.1.2.2.2.1.5ColumncurrentStatusread-onlymandatoryThis value indicates the current state of the contact. If the contact is not in its normal state. This value is set to fault(2).
1.3.6.1.4.1.318.1.1.3NodeminiSNMPadapter
1.3.6.1.4.1.318.1.1.3.1NodeserialPort
1.3.6.1.4.1.318.1.1.3.1.1NodeserialPort1
1.3.6.1.4.1.318.1.1.3.1.2NodeserialPort2
1.3.6.1.4.1.318.1.1.3.1.2.1NodeserialPort2Config
1.3.6.1.4.1.318.1.1.3.1.2.1.1ScalarserialPort2Moderead-writeobsoleteSetting this variable to passthrough will enable mini's port2 behave like a UPS port. Choosing localConsole will enable the port to be used as local console.
1.3.6.1.4.1.318.1.1.3.1.2.2NodeserialPort2Control
1.3.6.1.4.1.318.1.1.3.1.2.2.1ScalarsetPulseOnTXDread-writeobsoleteSetting this variable to setPulseOnTXD(2) causes adapter to generate a PULSE on TXD pin of serial port 2. The duration in the prototype implementation will be …
1.3.6.1.4.1.318.1.1.4Nodemasterswitch
1.3.6.1.4.1.318.1.1.4.1NodesPDUIdent
1.3.6.1.4.1.318.1.1.4.1.1ScalarsPDUIdentHardwareRevread-onlymandatoryThe hardware revision of the PDU. This value is set at the factory.
1.3.6.1.4.1.318.1.1.4.1.2ScalarsPDUIdentFirmwareRevread-onlymandatoryAn 8 byte ID string identifying the PDU firmware revision. This value is set at the factory.
1.3.6.1.4.1.318.1.1.4.1.3ScalarsPDUIdentDateOfManufactureread-onlymandatoryThe date when the PDU was manufactured in mm/dd/yy format. This value is set at the factory. The year 2000 will be represented by 00.
1.3.6.1.4.1.318.1.1.4.1.4ScalarsPDUIdentModelNumberread-onlymandatoryA 10-character string identifying the model number of the PDU internal. This value is set at the factory.
1.3.6.1.4.1.318.1.1.4.1.5ScalarsPDUIdentSerialNumberread-onlymandatoryA 12-character string identifying the serial number of the PDU internal microprocessor. This value is set at the factory.
1.3.6.1.4.1.318.1.1.4.2NodesPDUMasterControl
1.3.6.1.4.1.318.1.1.4.2.1ScalarsPDUMasterControlSwitchread-writemandatorySetting this OID to turnAllOnNow (1) will turn all outlets on immediately. Setting this OID to turnAllOnSequence (2) will turn all outlets on as defined by eac…
1.3.6.1.4.1.318.1.1.4.2.2ScalarsPDUMasterStateread-onlymandatoryGetting this OID will cause the status of all outlets to be returned. This OID is provided for informational purposes only. To change the outlet state, the use…
1.3.6.1.4.1.318.1.1.4.2.3ScalarsPDUMasterPendingread-onlymandatoryGetting this OID will cause the command pending status of all outlets to be returned. The format of the data returned is a character string consisting of the w…
1.3.6.1.4.1.318.1.1.4.3NodesPDUMasterConfig
1.3.6.1.4.1.318.1.1.4.3.1ScalarsPDUMasterConfigPowerOnread-writemandatoryThe amount of delay, in seconds, between when power is provided to the PDU and when the PDU provides basic master power to the outlets. Allowed values are: -1 …
1.3.6.1.4.1.318.1.1.4.3.2ScalarsPDUMasterConfigRebootread-writemandatoryDuring a reboot sequence, power is turned off and then back on. This OID defines the amount of time to wait, in seconds, after turning the power off, at the st…
1.3.6.1.4.1.318.1.1.4.3.3ScalarsPDUMasterConfigPDUNameread-writemandatoryThe name of the PDU.
1.3.6.1.4.1.318.1.1.4.4NodesPDUOutletControl
1.3.6.1.4.1.318.1.1.4.4.1ScalarsPDUOutletControlTableSizeread-onlymandatoryThe number of outlets for the PDU.
1.3.6.1.4.1.318.1.1.4.4.2TablesPDUOutletControlTablenot-accessiblemandatoryAllows for control of individual outlet switches. The number of entries is contained in the sPDUOutletControlTableSize OID.
1.3.6.1.4.1.318.1.1.4.4.2.1RowsPDUOutletControlEntrynot-accessiblemandatoryThe outlets to control.
1.3.6.1.4.1.318.1.1.4.4.2.1.1ColumnsPDUOutletControlIndexread-onlymandatoryThe index to the outlet entry.
1.3.6.1.4.1.318.1.1.4.4.2.1.2ColumnsPDUOutletPendingread-onlymandatoryReports whether the current outlet has a pending command. If the commandPendingUnknown (3) value is returned, all devices powered by the PDU should be shut dow…
1.3.6.1.4.1.318.1.1.4.4.2.1.3ColumnsPDUOutletCtlread-writemandatoryGetting this variable will return the outlet state. If the outlet is on, the outletOn (1) value will be returned. If the outlet is off, the outletOff (2) value…
1.3.6.1.4.1.318.1.1.4.4.2.1.4ColumnsPDUOutletCtlNameread-onlymandatoryThe name of the outlet. Maximum size is 20 characters. This OID is provided for informational purposes only. This value is set by the sPDUOutletName OID.
1.3.6.1.4.1.318.1.1.4.5NodesPDUOutletConfig
1.3.6.1.4.1.318.1.1.4.5.1ScalarsPDUOutletConfigTableSizeread-onlymandatoryThe number of outlets for the PDU.
1.3.6.1.4.1.318.1.1.4.5.2TablesPDUOutletConfigTablenot-accessiblemandatoryThe list of outlets to configure. The number of entries is defined by the sPDUOutletConfigTableSize OID.
1.3.6.1.4.1.318.1.1.4.5.2.1RowsPDUOutletConfigEntrynot-accessiblemandatoryThe outlets to control.
1.3.6.1.4.1.318.1.1.4.5.2.1.1ColumnsPDUOutletConfigIndexread-onlymandatoryThe index to the outlet entry.
1.3.6.1.4.1.318.1.1.4.5.2.1.2ColumnsPDUOutletPowerOnTimeread-writemandatoryThe amount of time (in seconds) the outlet will delay powering on when the MasterSwitch is powered on. Allowed values are: -1 never power on automatically. 0 p…
1.3.6.1.4.1.318.1.1.4.5.2.1.3ColumnsPDUOutletNameread-writemandatoryThe name of the outlet. Maximum size is 20 characters.
1.3.6.1.4.1.318.1.1.4.5.2.1.4ColumnsPDUOutletPowerOffTimeread-writemandatoryThe amount of time (in seconds) the outlet will delay powering off. Allowed values are: -1 never power off automatically. 0 power off with the MasterSwitch. 15…
1.3.6.1.4.1.318.1.1.4.5.2.1.5ColumnsPDUOutletRebootDurationread-writemandatoryDuring a reboot sequence, power is turned off and then back on. This OID defines the amount of time to wait, in seconds, after turning the power off, at the st…
1.3.6.1.4.1.318.1.1.5NodemasterswitchVM
1.3.6.1.4.1.318.1.1.5.1NodesPDUIdentVM
1.3.6.1.4.1.318.1.1.5.1.1ScalarsPDUIdentVMTableSizeread-onlymandatoryThe number of MasterSwitch VMs controllable by this IP address.
1.3.6.1.4.1.318.1.1.5.1.2TablesPDUIdentVMTablenot-accessiblemandatoryAllows for query of the individual MasterSwitch VMs. The number of entries is contained in the sPDUIdentVMTableSize OID.
1.3.6.1.4.1.318.1.1.5.1.2.1RowsPDUIdentVMEntrynot-accessiblemandatoryThe MasterSwitch VMs to query.
1.3.6.1.4.1.318.1.1.5.1.2.1.1ColumnsPDUIdentVMIndexread-onlymandatoryThe index to the MasterSwitch VM entry.
1.3.6.1.4.1.318.1.1.5.1.2.1.2ColumnsPDUIdentNameVMread-onlymandatoryA 23-character string identifying the MasterSwitch VM.
1.3.6.1.4.1.318.1.1.5.1.2.1.3ColumnsPDUIdentHardwareRevVMread-onlymandatoryThe hardware version of the MasterSwitch VM. This value is set at the factory.
1.3.6.1.4.1.318.1.1.5.1.2.1.4ColumnsPDUIdentFirmwareRevVMread-onlymandatoryAn 6-character ID string identifying the MasterSwitch VM firmware version. This value is set at the factory.
1.3.6.1.4.1.318.1.1.5.1.2.1.5ColumnsPDUIdentDateOfManufactureVMread-onlymandatoryThe date when the MasterSwitch VM was manufactured in mm/dd/yyyy format. This value is set at the factory.
1.3.6.1.4.1.318.1.1.5.1.2.1.6ColumnsPDUIdentModelNumberVMread-onlymandatoryA 17-character string identifying the model number of the MasterSwitch VM. This value is set at the factory.
1.3.6.1.4.1.318.1.1.5.1.2.1.7ColumnsPDUIdentSerialNumberVMread-onlymandatoryA 17-character string identifying the serial number of the MasterSwitch VM. This value is set at the factory.
1.3.6.1.4.1.318.1.1.5.2NodesPDUMasterControlVM
1.3.6.1.4.1.318.1.1.5.2.1ScalarsPDUMasterControlVMTableSizeread-onlymandatoryThe number of MasterSwitch VMs controllable by this IP address.
1.3.6.1.4.1.318.1.1.5.2.2TablesPDUMasterControlVMTablenot-accessiblemandatoryAllows for control of the individual MasterSwitch VMs. The number of entries is contained in the sPDUMasterControlVMTableSize OID.
1.3.6.1.4.1.318.1.1.5.2.2.1RowsPDUMasterControlVMEntrynot-accessiblemandatoryThe MasterSwitch VMs to control.
1.3.6.1.4.1.318.1.1.5.2.2.1.1ColumnsPDUMasterControlVMIndexread-onlymandatoryThe index to the MasterSwitch VM entry.
1.3.6.1.4.1.318.1.1.5.2.2.1.2ColumnsPDUMasterControlVMNameread-onlymandatoryThe name of the MasterSwitch VM. The maximum value is 23 characters. The name is set by using the sPDUMasterConfigVMName OID.
1.3.6.1.4.1.318.1.1.5.2.2.1.3ColumnsPDUMasterControlVMCommandread-writemandatorySetting this OID to immediateAllOnVM (2) will turn all outlets on immediately. Setting this OID to immediateAllOffVM (3) will turn all outlets off immediately.…
1.3.6.1.4.1.318.1.1.5.3NodesPDUMasterConfigVM
1.3.6.1.4.1.318.1.1.5.3.1ScalarsPDUMasterConfigVMTableSizeread-onlymandatoryThe number of MasterSwitch VMs configurable by this IP address.
1.3.6.1.4.1.318.1.1.5.3.2TablesPDUMasterConfigVMTablenot-accessiblemandatoryAllows for configuration of the individual MasterSwitch VMs. The number of entries is contained in the sPDUMasterConfigVMTableSize OID.
1.3.6.1.4.1.318.1.1.5.3.2.1RowsPDUMasterConfigVMEntrynot-accessiblemandatoryThe MasterSwitch VMs to configure.
1.3.6.1.4.1.318.1.1.5.3.2.1.1ColumnsPDUMasterConfigVMIndexread-onlymandatoryThe index to the MasterSwitch VM entry.
1.3.6.1.4.1.318.1.1.5.3.2.1.2ColumnsPDUMasterConfigVMNameread-writemandatoryThe name of the MasterSwitch VM. Maximum size is 23 characters.
1.3.6.1.4.1.318.1.1.5.3.2.1.3ColumnsPDUMasterConfigVMColdstartDelayread-writemandatoryThe amount of delay, in seconds, between when power is provided to the MasterSwitch VM and when the MasterSwitch VM provides basic master power to the outlets.…
1.3.6.1.4.1.318.1.1.5.3.2.1.4ColumnsPDUMasterConfigVMAudioAlarmActivatedread-writemandatorySetting this OID to audioAlarmActiveNever (1) will disable the audio alarm on the MasterSwitch VM. Setting this OID to audioAlarmActiveOnOverload (2) will acti…
1.3.6.1.4.1.318.1.1.5.3.2.1.5ColumnsPDUMasterConfigVMHighLoadWarningThresholdread-writemandatoryA threshold that indicates the power consumption of the load is nearing an overload condition. It is represented as a percentage of full load.
1.3.6.1.4.1.318.1.1.5.3.2.1.6ColumnsPDUMasterConfigVMLowLoadWarningThresholdread-writemandatoryA threshold that indicates the power consumption of the load is nearing a low consumption condition. It is represented as a percentage of full load.
1.3.6.1.4.1.318.1.1.5.3.2.1.7ColumnsPDUMasterConfigVMOverloadRestrictionread-writemandatoryThis OID controls the behavior of the MasterSwitch VM when an overload condition is possible and additional outlets are requested to be turned on. Setting this…
1.3.6.1.4.1.318.1.1.5.4NodesPDUMasterStatusVM
1.3.6.1.4.1.318.1.1.5.4.1ScalarsPDUMasterStatusVMTableSizeread-onlymandatoryThe number of MasterSwitch VMs at this IP address.
1.3.6.1.4.1.318.1.1.5.4.2TablesPDUMasterStatusVMTablenot-accessiblemandatoryAllows for gathering of status from the individual MasterSwitch VMs. The number of entries is contained in the sPDUMasterStatusVMTableSize OID.
1.3.6.1.4.1.318.1.1.5.4.2.1RowsPDUMasterStatusVMEntrynot-accessiblemandatoryThe MasterSwitch VMs to gather status from.
1.3.6.1.4.1.318.1.1.5.4.2.1.1ColumnsPDUMasterStatusVMIndexread-onlymandatoryThe index to the MasterSwitch VM entry.
1.3.6.1.4.1.318.1.1.5.4.2.1.2ColumnsPDUMasterStatusVMNameread-onlymandatoryThe name of the MasterSwitch VM. Maximum size is 23 characters.
1.3.6.1.4.1.318.1.1.5.4.2.1.3ColumnsPDUMasterStatusVMCommandPendingread-onlymandatoryGetting this OID will return commandPendingMasterTrueVM (1) if the MasterSwitch VM has a pending command on any of its outlets. commandPendingMasterFalseVM (2)…
1.3.6.1.4.1.318.1.1.5.4.2.1.4ColumnsPDUMasterStatusVMOverloadConditionread-onlymandatoryGetting this OID will return overloadConditionTrueVM (1) if the sPDUMasterConfigVMHighLoadWarningThreshold OID is violated. overloadConditionFalseVM (2) will b…
1.3.6.1.4.1.318.1.1.5.4.2.1.5ColumnsPDUMasterStatusVMLowLoadConditionread-onlymandatoryGetting this OID will return lowLoadConditionTrueVM (1) if the sPDUMasterConfigVMLowLoadWarningThreshold OID is violated. lowLoadConditionFalseVM (2) will be r…
1.3.6.1.4.1.318.1.1.5.4.2.1.6ColumnsPDUMasterStatusVMCurrentLoadread-onlymandatoryGetting this OID will return the total amount of power being consumed by the load. It is represented as a percentage of full load.
1.3.6.1.4.1.318.1.1.5.4.2.1.7ColumnsPDUMasterStatusVMMaxLoadread-onlymandatoryGetting this OID will return the total amount of power that this MasterSwitch VM can provide. It is represented in Amps.
1.3.6.1.4.1.318.1.1.5.4.2.1.8ColumnsPDUMasterStatusVMOutletCountread-onlymandatoryGetting this OID will return the number of controllable outlets for this MasterSwitch VM.
1.3.6.1.4.1.318.1.1.5.4.2.1.9ColumnsPDUMasterStatusVMRebootDurationread-onlymandatoryGetting this OID will return the largest sPDUOutletConfigVMRebootDuration OID time for this MasterSwitch VM.
1.3.6.1.4.1.318.1.1.5.5NodesPDUOutletControlVM
1.3.6.1.4.1.318.1.1.5.5.1TablesPDUOutletControlVMTablenot-accessiblemandatoryAllows for control of individual outlet switches. The number of entries is contained in the sPDUMasterStatusOutletCount OID.
1.3.6.1.4.1.318.1.1.5.5.1.1RowsPDUOutletControlVMEntrynot-accessiblemandatoryThe outlets to control.
1.3.6.1.4.1.318.1.1.5.5.1.1.1ColumnsPDUOutletControlVMIndexread-onlymandatoryThe index to the MasterSwitch VM.
1.3.6.1.4.1.318.1.1.5.5.1.1.2ColumnsPDUOutletControlVMNameread-onlymandatoryThe name of the MasterSwitch VM. Maximum size is 23 characters. This OID is provided for informational purposes only.
1.3.6.1.4.1.318.1.1.5.5.1.1.3ColumnsPDUOutletControlVMOutletIndexread-onlymandatoryThe index to the outlet entry.
1.3.6.1.4.1.318.1.1.5.5.1.1.4ColumnsPDUOutletControlVMOutletNameread-onlymandatoryThe name of the outlet. Maximum size is 23 characters. This OID is provided for informational purposes only.
1.3.6.1.4.1.318.1.1.5.5.1.1.5ColumnsPDUOutletControlVMOutletCommandread-writemandatoryGetting this variable will return the outlet state. If the outlet is on, the immediateOnVM (1) value will be returned. If the outlet is off, the immediateOffVM…
1.3.6.1.4.1.318.1.1.5.6NodesPDUOutletConfigVM
1.3.6.1.4.1.318.1.1.5.6.1TablesPDUOutletConfigVMTablenot-accessiblemandatoryAllows for configuration of individual outlets. The number of entries is contained in the sPDUMasterStatusOutletCount OID.
1.3.6.1.4.1.318.1.1.5.6.1.1RowsPDUOutletConfigVMEntrynot-accessiblemandatoryThe outlets to configure.
1.3.6.1.4.1.318.1.1.5.6.1.1.1ColumnsPDUOutletConfigVMIndexread-onlymandatoryThe index to the MasterSwitch VM.
1.3.6.1.4.1.318.1.1.5.6.1.1.2ColumnsPDUOutletConfigVMNameread-onlymandatoryThe name of the MasterSwitch VM. Maximum size is 23 characters.
1.3.6.1.4.1.318.1.1.5.6.1.1.3ColumnsPDUOutletConfigVMOutletIndexread-onlymandatoryThe index to the outlet entry.
1.3.6.1.4.1.318.1.1.5.6.1.1.4ColumnsPDUOutletConfigVMOutletNameread-writemandatoryThe name of the outlet. Maximum size is 23 characters.
1.3.6.1.4.1.318.1.1.5.6.1.1.5ColumnsPDUOutletConfigVMPowerOnTimeread-writemandatoryThe amount of time (in seconds) the outlet will delay powering on at coldstart or when a command that requires a turn-on delay is issued. Allowed values are: -…
1.3.6.1.4.1.318.1.1.5.6.1.1.6ColumnsPDUOutletConfigVMPowerOffTimeread-writemandatoryThe amount of time (in seconds) the outlet will delay powering off when a command that requires a turn-off delay is issued. Allowed values are: -1 never power …
1.3.6.1.4.1.318.1.1.5.6.1.1.7ColumnsPDUOutletConfigVMRebootDurationread-writemandatoryDuring a reboot sequence, power is turned off and then back on. This OID defines the amount of time to wait, in seconds, after turning the power off, at the st…
1.3.6.1.4.1.318.1.1.5.7NodesPDUOutletStatusVM
1.3.6.1.4.1.318.1.1.5.7.1TablesPDUOutletStatusVMTablenot-accessiblemandatoryAllows for getting of status of individual outlets. The number of entries is contained in the sPDUMasterStatusOutletCount OID.
1.3.6.1.4.1.318.1.1.5.7.1.1RowsPDUOutletStatusVMEntrynot-accessiblemandatoryThe outlets to gather status from.
1.3.6.1.4.1.318.1.1.5.7.1.1.1ColumnsPDUOutletStatusVMIndexread-onlymandatoryThe index to the MasterSwitch VM.
1.3.6.1.4.1.318.1.1.5.7.1.1.2ColumnsPDUOutletStatusVMNameread-onlymandatoryThe name of the MasterSwitch VM. Maximum size is 23 characters.
1.3.6.1.4.1.318.1.1.5.7.1.1.3ColumnsPDUOutletStatusVMOutletIndexread-onlymandatoryThe index to the outlet entry.
1.3.6.1.4.1.318.1.1.5.7.1.1.4ColumnsPDUOutletStatusVMOutletNameread-onlymandatoryThe name of the outlet. Maximum size is 23 characters.
1.3.6.1.4.1.318.1.1.5.7.1.1.5ColumnsPDUOutletStatusVMOutletStateread-onlymandatoryGetting this variable will return the outlet state. If the outlet is on, the outletStatusOnVM (1) value will be returned. If the outlet is off, the outletStatu…
1.3.6.1.4.1.318.1.1.5.7.1.1.6ColumnsPDUOutletStatusVMCommandPendingread-onlymandatoryGetting this variable will return the command pending state of the outlet. If a command is pending on the outlet, the outletStatusVMCommandPending (1) value wi…
1.3.6.1.4.1.318.1.1.6NodemasterswitchMSP
1.3.6.1.4.1.318.1.1.6.1NodesPDUIdentMSP
1.3.6.1.4.1.318.1.1.6.1.1ScalarsPDUIdentMSPTableSizeread-onlymandatoryThe number of MasterSwitch pluses controllable by this IP address.
1.3.6.1.4.1.318.1.1.6.1.2TablesPDUIdentMSPTablenot-accessiblemandatoryAllows for query of the individual MasterSwitch pluses. The number of entries is contained in the sPDUIdentMSPTableSize OID.
1.3.6.1.4.1.318.1.1.6.1.2.1RowsPDUIdentMSPEntrynot-accessiblemandatoryThe MasterSwitch pluses to query.
1.3.6.1.4.1.318.1.1.6.1.2.1.1ColumnsPDUIdentMSPIndexread-onlymandatoryThe index to the MasterSwitch plus entry.
1.3.6.1.4.1.318.1.1.6.1.2.1.2ColumnsPDUIdentNameMSPread-onlymandatoryThe name of the MasterSwitch plus. The maximum value is 23 characters. The name is set by using the sPDUMasterConfigMSPName OID.
1.3.6.1.4.1.318.1.1.6.1.2.1.3ColumnsPDUIdentHardwareRevMSPread-onlymandatoryThe hardware version of the MasterSwitch plus. This value is set at the factory.
1.3.6.1.4.1.318.1.1.6.1.2.1.4ColumnsPDUIdentFirmwareRevMSPread-onlymandatoryAn 6-character ID string identifying the MasterSwitch plus firmware version. This value is set at the factory.
1.3.6.1.4.1.318.1.1.6.1.2.1.5ColumnsPDUIdentDateOfManufactureMSPread-onlymandatoryThe date when the MasterSwitch plus was manufactured in mm/dd/yyyy format. This value is set at the factory.
1.3.6.1.4.1.318.1.1.6.1.2.1.6ColumnsPDUIdentModelNumberMSPread-onlymandatoryA 17-character string identifying the model number of the MasterSwitch plus. This value is set at the factory.
1.3.6.1.4.1.318.1.1.6.1.2.1.7ColumnsPDUIdentSerialNumberMSPread-onlymandatoryA 17-character string identifying the serial number of the MasterSwitch plus. This value is set at the factory.
1.3.6.1.4.1.318.1.1.6.2NodesPDUMasterControlMSP
1.3.6.1.4.1.318.1.1.6.2.1ScalarsPDUMasterControlMSPTableSizeread-onlymandatoryThe number of MasterSwitch pluses controllable by this IP address.
1.3.6.1.4.1.318.1.1.6.2.2TablesPDUMasterControlMSPTablenot-accessiblemandatoryAllows for control of the individual MasterSwitch pluses. The number of entries is contained in the sPDUMasterControlMSPTableSize OID.
1.3.6.1.4.1.318.1.1.6.2.2.1RowsPDUMasterControlMSPEntrynot-accessiblemandatoryThe MasterSwitch pluses to control.
1.3.6.1.4.1.318.1.1.6.2.2.1.1ColumnsPDUMasterControlMSPIndexread-onlymandatoryThe index to the MasterSwitch plus entry.
1.3.6.1.4.1.318.1.1.6.2.2.1.2ColumnsPDUMasterControlMSPNameread-onlymandatoryThe name of the MasterSwitch plus. The maximum value is 23 characters. The name is set by using the sPDUMasterConfigMSPName OID.
1.3.6.1.4.1.318.1.1.6.2.2.1.3ColumnsPDUMasterControlMSPCommandread-writemandatorySetting this OID to immediateAllOnMSP (2) will turn all outlets on immediately. Setting this OID to sequencedAllOnMSP (3) will turn all outlets on as defined b…
1.3.6.1.4.1.318.1.1.6.3NodesPDUMasterConfigMSP
1.3.6.1.4.1.318.1.1.6.3.1ScalarsPDUMasterConfigMSPTableSizeread-onlymandatoryThe number of MasterSwitch pluses configurable by this IP address.
1.3.6.1.4.1.318.1.1.6.3.2TablesPDUMasterConfigMSPTablenot-accessiblemandatoryAllows for configuration of the individual MasterSwitch pluses. The number of entries is contained in the sPDUMasterConfigMSPTableSize OID.
1.3.6.1.4.1.318.1.1.6.3.2.1RowsPDUMasterConfigMSPEntrynot-accessiblemandatoryThe MasterSwitch pluses to configure.
1.3.6.1.4.1.318.1.1.6.3.2.1.1ColumnsPDUMasterConfigMSPIndexread-onlymandatoryThe index to the MasterSwitch plus entry.
1.3.6.1.4.1.318.1.1.6.3.2.1.2ColumnsPDUMasterConfigMSPNameread-writemandatoryThe name of the MasterSwitch plus. Maximum size is 23 characters.
1.3.6.1.4.1.318.1.1.6.3.2.1.3ColumnsPDUMasterConfigMSPPowerOnTimeDelayread-writemandatoryThe amount of delay, in seconds, between when power is provided to the MasterSwitch plus and when the MasterSwitch plus provides basic master power to the outl…
1.3.6.1.4.1.318.1.1.6.3.2.1.4ColumnsPDUMasterConfigMSPManualButtonread-writemandatorySetting this OID to manualButtonDisabled (1) will disable the manual button on the MasterSwitch plus. Setting this OID to manualButtonEnabled (2) will enable t…
1.3.6.1.4.1.318.1.1.6.4NodesPDUMasterStatusMSP
1.3.6.1.4.1.318.1.1.6.4.1ScalarsPDUMasterStatusMSPTableSizeread-onlymandatoryThe number of MasterSwitch pluses at this IP address.
1.3.6.1.4.1.318.1.1.6.4.2TablesPDUMasterStatusMSPTablenot-accessiblemandatoryAllows for gathering of status from the individual MasterSwitch pluses. The number of entries is contained in the sPDUMasterStatusMSPTableSize OID.
1.3.6.1.4.1.318.1.1.6.4.2.1RowsPDUMasterStatusMSPEntrynot-accessiblemandatoryThe MasterSwitch pluses to gather status from.
1.3.6.1.4.1.318.1.1.6.4.2.1.1ColumnsPDUMasterStatusMSPIndexread-onlymandatoryThe index to the MasterSwitch plus entry.
1.3.6.1.4.1.318.1.1.6.4.2.1.2ColumnsPDUMasterStatusMSPNameread-onlymandatoryThe name of the MasterSwitch plus. The maximum value is 23 characters. The name is set by using the sPDUMasterConfigMSPName OID.
1.3.6.1.4.1.318.1.1.6.4.2.1.3ColumnsPDUMasterStatusMSPOutletCountread-onlymandatoryGetting this OID will return the number of controllable outlets for this MasterSwitch plus.
1.3.6.1.4.1.318.1.1.6.5NodesPDUOutletControlMSP
1.3.6.1.4.1.318.1.1.6.5.1TablesPDUOutletControlMSPTablenot-accessiblemandatoryAllows for control of individual outlet switches. The number of entries is contained in the sPDUMasterStatusMSPOutletCount OID.
1.3.6.1.4.1.318.1.1.6.5.1.1RowsPDUOutletControlMSPEntrynot-accessiblemandatoryThe outlets to control.
1.3.6.1.4.1.318.1.1.6.5.1.1.1ColumnsPDUOutletControlMSPIndexread-onlymandatoryThe index to the MasterSwitch plus.
1.3.6.1.4.1.318.1.1.6.5.1.1.2ColumnsPDUOutletControlMSPNameread-onlymandatoryThe name of the MasterSwitch plus. The maximum value is 23 characters. The name is set by using the sPDUMasterConfigMSPName OID.
1.3.6.1.4.1.318.1.1.6.5.1.1.3ColumnsPDUOutletControlMSPOutletIndexread-onlymandatoryThe index to the outlet entry.
1.3.6.1.4.1.318.1.1.6.5.1.1.4ColumnsPDUOutletControlMSPOutletNameread-onlymandatoryThe name of the outlet. The maximum size is 23 characters. The name is set by using the sPDUOutletConfigMSPallOutletName OID. This OID is provided for informat…
1.3.6.1.4.1.318.1.1.6.5.1.1.5ColumnsPDUOutletControlMSPOutletCommandread-writemandatoryGetting this variable will return the outlet state. If the outlet is on, the immediateOnMSP (1) value will be returned. If the outlet is off, the immediateOffM…
1.3.6.1.4.1.318.1.1.6.6NodesPDUOutletConfigMSP
1.3.6.1.4.1.318.1.1.6.6.1NodesPDUOutletConfigMSPall
1.3.6.1.4.1.318.1.1.6.6.1.1TablesPDUOutletConfigMSPallTablenot-accessiblemandatoryAllows for configuration of individual outlets. The number of entries is contained in the sPDUMasterStatusMSPOutletCount OID.
1.3.6.1.4.1.318.1.1.6.6.1.1.1RowsPDUOutletConfigMSPallEntrynot-accessiblemandatoryThe outlets to configure.
1.3.6.1.4.1.318.1.1.6.6.1.1.1.1ColumnsPDUOutletConfigMSPallIndexread-onlymandatoryThe index to the MasterSwitch plus.
1.3.6.1.4.1.318.1.1.6.6.1.1.1.2ColumnsPDUOutletConfigMSPallNameread-onlymandatoryThe name of the MasterSwitch plus. The maximum value is 23 characters. The name is set by using the sPDUMasterConfigMSPName OID.
1.3.6.1.4.1.318.1.1.6.6.1.1.1.3ColumnsPDUOutletConfigMSPallOutletIndexread-onlymandatoryThe index to the outlet entry.
1.3.6.1.4.1.318.1.1.6.6.1.1.1.4ColumnsPDUOutletConfigMSPallOutletNameread-writemandatoryThe name of the outlet. Maximum size is 23 characters.
1.3.6.1.4.1.318.1.1.6.6.1.1.1.5ColumnsPDUOutletConfigMSPallOutletCtrlModeread-writemandatorySetting this OID to modeGracefulShutdown (1) will put this outlet into the Graceful Shutdown control mode. Setting this OID to modeAnnunciator (2) will put thi…
1.3.6.1.4.1.318.1.1.6.6.2NodesPDUOutletConfigMSPgs
1.3.6.1.4.1.318.1.1.6.6.2.1TablesPDUOutletConfigMSPgsTablenot-accessiblemandatoryAllows for configuration of individual outlets. The number of entries is contained in the sPDUMasterStatusMSPOutletCount OID.
1.3.6.1.4.1.318.1.1.6.6.2.1.1RowsPDUOutletConfigMSPgsEntrynot-accessiblemandatoryThe outlets to configure.
1.3.6.1.4.1.318.1.1.6.6.2.1.1.1ColumnsPDUOutletConfigMSPgsIndexread-onlymandatoryThe index to the MasterSwitch plus.
1.3.6.1.4.1.318.1.1.6.6.2.1.1.2ColumnsPDUOutletConfigMSPgsNameread-onlymandatoryThe name of the MasterSwitch plus. The maximum value is 23 characters. The name is set by using the sPDUMasterConfigMSPName OID.
1.3.6.1.4.1.318.1.1.6.6.2.1.1.3ColumnsPDUOutletConfigMSPgsOutletIndexread-onlymandatoryThe index to the outlet entry.
1.3.6.1.4.1.318.1.1.6.6.2.1.1.4ColumnsPDUOutletConfigMSPgsOutletNameread-onlymandatoryThe name of the outlet. The maximum size is 23 characters. The name is set by using the sPDUOutletConfigMSPallOutletName OID. This OID is provided for informat…
1.3.6.1.4.1.318.1.1.6.6.2.1.1.5ColumnsPDUOutletConfigMSPgsOutletCtrlModeread-onlymandatoryThe Control Mode of the outlet. This OID is provided for informational purposes only.
1.3.6.1.4.1.318.1.1.6.6.2.1.1.6ColumnsPDUOutletConfigMSPgsDeviceConfirmread-writemandatorySetting this OID to deviceConfirmNo (1) cause the outlet to NOT wait for device confirmation while performing graceful operations. Setting this OID to deviceCo…
1.3.6.1.4.1.318.1.1.6.6.2.1.1.7ColumnsPDUOutletConfigMSPgsLowBattWarningread-writemandatoryThe amount of delay, in 6 second intervals, between when the UPS goes on battery and the power down sequence for the outlet is initiated. Allowed values are: -…
1.3.6.1.4.1.318.1.1.6.6.2.1.1.8ColumnsPDUOutletConfigMSPgsLowBattMultread-writemandatoryOnly applicable if sPDUOutletConfigMSPgsLowBattWarning OID is set to -1 (On Runtime Remaining). Allows you to set the value to stagger the shutdown sequence of…
1.3.6.1.4.1.318.1.1.6.6.2.1.1.9ColumnsPDUOutletConfigMSPgsRestartDelayread-writemandatoryThe amount of delay, in 6 minute intervals, between when the outlet is turned off and the outlet is turned back on when performing a Graceful Shutdown. Allowed…
1.3.6.1.4.1.318.1.1.6.6.2.1.1.10ColumnsPDUOutletConfigMSPgsPowerOnDelayread-writemandatoryThe amount of delay, in seconds, between the UPS entering normal (on-line) state and the outlet being powered on. Allowed values are: -1 - Remain Off when the …
1.3.6.1.4.1.318.1.1.6.6.2.1.1.11ColumnsPDUOutletConfigMSPgsPowerOffDelayread-writemandatoryThe amount of delay, in seconds, between when the server shuts down and the outlet is powered off. Allowed values are: 0 - 9999 seconds (0 - 2 hrs, 46 mins, 39…
1.3.6.1.4.1.318.1.1.6.6.2.1.1.12ColumnsPDUOutletConfigMSPgsBattCapThreshread-writemandatoryThe minimum battery capacity, as a percent (0-100%), required of the UPS before an outlet will be allowed to power on. Allowed values are: 0 - 100 percent.
1.3.6.1.4.1.318.1.1.6.6.2.1.1.13ColumnsPDUOutletConfigMSPgsRebootDurationread-writemandatoryThe amount of delay, in seconds, from outlet off until outlet on during a reboot. Allowed values are: 0 - 9999 seconds (0 - 2 hrs, 46 mins, 39 secs).
1.3.6.1.4.1.318.1.1.6.6.3NodesPDUOutletConfigMSPannun
1.3.6.1.4.1.318.1.1.6.6.3.1TablesPDUOutletConfigMSPannunTablenot-accessiblemandatoryAllows for configuration of individual outlets. The number of entries is contained in the sPDUMasterStatusMSPOutletCount OID.
1.3.6.1.4.1.318.1.1.6.6.3.1.1RowsPDUOutletConfigMSPannunEntrynot-accessiblemandatoryThe outlets to configure.
1.3.6.1.4.1.318.1.1.6.6.3.1.1.1ColumnsPDUOutletConfigMSPannunIndexread-onlymandatoryThe index to the MasterSwitch plus.
1.3.6.1.4.1.318.1.1.6.6.3.1.1.2ColumnsPDUOutletConfigMSPannunNameread-onlymandatoryThe name of the MasterSwitch plus. The maximum value is 23 characters. The name is set by using the sPDUMasterConfigMSPName OID.
1.3.6.1.4.1.318.1.1.6.6.3.1.1.3ColumnsPDUOutletConfigMSPannunOutletIndexread-onlymandatoryThe index to the outlet entry.
1.3.6.1.4.1.318.1.1.6.6.3.1.1.4ColumnsPDUOutletConfigMSPannunOutletNameread-onlymandatoryThe name of the outlet. The maximum size is 23 characters. The name is set by using the sPDUOutletConfigMSPallOutletName OID. This OID is provided for informat…
1.3.6.1.4.1.318.1.1.6.6.3.1.1.5ColumnsPDUOutletConfigMSPannunOutletCtrlModeread-onlymandatoryThe Control Mode of the outlet. This OID is provided for informational purposes only.
1.3.6.1.4.1.318.1.1.6.6.3.1.1.6ColumnsPDUOutletConfigMSPannunInitialStateread-writemandatorySetting this OID to initialStateOff (1) causes the outlet to default to off when in the non-alarmed condition. Setting this OID to initialStateOn (2) causes th…
1.3.6.1.4.1.318.1.1.6.6.3.1.1.7ColumnsPDUOutletConfigMSPannunAlarmActionDlyread-writemandatoryThe amount of time, in seconds, that an enabled Measure-UPS alarm must be asserted before an alarm condition is recognized. Allowed values are: 0 - 9999 second…
1.3.6.1.4.1.318.1.1.6.6.4NodesPDUOutletConfigMSPmups
1.3.6.1.4.1.318.1.1.6.6.4.1TablesPDUOutletConfigMSPmupsTablenot-accessiblemandatoryAllows for configuration of individual outlets. The number of entries is contained in the sPDUMasterStatusMSPOutletCount OID.
1.3.6.1.4.1.318.1.1.6.6.4.1.1RowsPDUOutletConfigMSPmupsEntrynot-accessiblemandatoryThe outlets to configure.
1.3.6.1.4.1.318.1.1.6.6.4.1.1.1ColumnsPDUOutletConfigMSPmupsIndexread-onlymandatoryThe index to the MasterSwitch plus.
1.3.6.1.4.1.318.1.1.6.6.4.1.1.2ColumnsPDUOutletConfigMSPmupsNameread-onlymandatoryThe name of the MasterSwitch plus. The maximum value is 23 characters. The name is set by using the sPDUMasterConfigMSPName OID.
1.3.6.1.4.1.318.1.1.6.6.4.1.1.3ColumnsPDUOutletConfigMSPmupsOutletIndexread-onlymandatoryThe index to the outlet entry.
1.3.6.1.4.1.318.1.1.6.6.4.1.1.4ColumnsPDUOutletConfigMSPmupsOutletNameread-onlymandatoryThe name of the outlet. The maximum size is 23 characters. The name is set by using the sPDUOutletConfigMSPallOutletName OID. This OID is provided for informat…
1.3.6.1.4.1.318.1.1.6.6.4.1.1.5ColumnsPDUOutletConfigMSPmupsZone1read-writemandatorySetting this OID to disableAlarm (1) disables the Zone 1 alarm for this outlet. Setting this OID to enableAlarm (2) enables the Zone 1 alarm for this outlet.
1.3.6.1.4.1.318.1.1.6.6.4.1.1.6ColumnsPDUOutletConfigMSPmupsZone2read-writemandatorySetting this OID to disableAlarm (1) disables the Zone 2 alarm for this outlet. Setting this OID to enableAlarm (2) enables the Zone 2 alarm for this outlet.
1.3.6.1.4.1.318.1.1.6.6.4.1.1.7ColumnsPDUOutletConfigMSPmupsZone3read-writemandatorySetting this OID to disableAlarm (1) disables the Zone 3 alarm for this outlet. Setting this OID to enableAlarm (2) enables the Zone 3 alarm for this outlet.
1.3.6.1.4.1.318.1.1.6.6.4.1.1.8ColumnsPDUOutletConfigMSPmupsZone4read-writemandatorySetting this OID to disableAlarm (1) disables the Zone 4 alarm for this outlet. Setting this OID to enableAlarm (2) enables the Zone 4 alarm for this outlet.
1.3.6.1.4.1.318.1.1.6.6.4.1.1.9ColumnsPDUOutletConfigMSPmupsP1LowHumread-writemandatorySetting this OID to disableAlarm (1) disables the Probe 1 low humidity alarm for this outlet. Setting this OID to enableAlarm (2) enables the Probe 1 low humid…
1.3.6.1.4.1.318.1.1.6.6.4.1.1.10ColumnsPDUOutletConfigMSPmupsP1HiHumread-writemandatorySetting this OID to disableAlarm (1) disables the Probe 1 high humidity alarm for this outlet. Setting this OID to enableAlarm (2) enables the Probe 1 high hum…
1.3.6.1.4.1.318.1.1.6.6.4.1.1.11ColumnsPDUOutletConfigMSPmupsP1LowTempread-writemandatorySetting this OID to disableAlarm (1) disables the Probe 1 low temperature alarm for this outlet. Setting this OID to enableAlarm (2) enables the Probe 1 low te…
1.3.6.1.4.1.318.1.1.6.6.4.1.1.12ColumnsPDUOutletConfigMSPmupsP1HiTempread-writemandatorySetting this OID to disableAlarm (1) disables the Probe 1 high temperature alarm for this outlet. Setting this OID to enableAlarm (2) enables the Probe 1 high …
1.3.6.1.4.1.318.1.1.6.6.4.1.1.13ColumnsPDUOutletConfigMSPmupsP2LowHumread-writemandatorySetting this OID to disableAlarm (1) disables the Probe 2 low humidity alarm for this outlet. Setting this OID to enableAlarm (2) enables the Probe 2 low humid…
1.3.6.1.4.1.318.1.1.6.6.4.1.1.14ColumnsPDUOutletConfigMSPmupsP2HiHumread-writemandatorySetting this OID to disableAlarm (1) disables the Probe 2 high humidity alarm for this outlet. Setting this OID to enableAlarm (2) enables the Probe 2 high hum…
1.3.6.1.4.1.318.1.1.6.6.4.1.1.15ColumnsPDUOutletConfigMSPmupsP2LowTempread-writemandatorySetting this OID to disableAlarm (1) disables the Probe 2 low temperature alarm for this outlet. Setting this OID to enableAlarm (2) enables the Probe 2 low te…
1.3.6.1.4.1.318.1.1.6.6.4.1.1.16ColumnsPDUOutletConfigMSPmupsP2HiTempread-writemandatorySetting this OID to disableAlarm (1) disables the Probe 2 high temperature alarm for this outlet. Setting this OID to enableAlarm (2) enables the Probe 2 high …
1.3.6.1.4.1.318.1.1.6.7NodesPDUOutletStatusMSP
1.3.6.1.4.1.318.1.1.6.7.1TablesPDUOutletStatusMSPTablenot-accessiblemandatoryAllows for getting of status of individual outlets. The number of entries is contained in the sPDUMasterStatusOutletCount OID.
1.3.6.1.4.1.318.1.1.6.7.1.1RowsPDUOutletStatusMSPEntrynot-accessiblemandatoryThe outlets to gather status from.
1.3.6.1.4.1.318.1.1.6.7.1.1.1ColumnsPDUOutletStatusMSPIndexread-onlymandatoryThe index to the MasterSwitch MSP.
1.3.6.1.4.1.318.1.1.6.7.1.1.2ColumnsPDUOutletStatusMSPNameread-onlymandatoryThe name of the MasterSwitch plus. The maximum value is 23 characters. The name is set by using the sPDUMasterConfigMSPName OID.
1.3.6.1.4.1.318.1.1.6.7.1.1.3ColumnsPDUOutletStatusMSPOutletIndexread-onlymandatoryThe index to the outlet entry.
1.3.6.1.4.1.318.1.1.6.7.1.1.4ColumnsPDUOutletStatusMSPOutletNameread-onlymandatoryThe name of the outlet. The maximum size is 23 characters. The name is set by using the sPDUOutletConfigMSPallOutletName OID. This OID is provided for informat…
1.3.6.1.4.1.318.1.1.6.7.1.1.5ColumnsPDUOutletStatusMSPOutletStateread-onlymandatoryGetting this variable will return the outlet state. If the outlet is on, the outletStatusMSPOn (1) value will be returned. If the outlet is off, the outletStat…
1.3.6.1.4.1.318.1.1.6.7.1.1.6ColumnsPDUOutletStatusMSPCommandPendingread-onlymandatoryGetting this variable will return the command pending state of the outlet. If a command is pending on the outlet, the outletStatusMSPCommandPending (1) value w…
1.3.6.1.4.1.318.1.1.6.7.1.1.7ColumnsPDUOutletStatusMSPOutletCtrlModeread-onlymandatoryThe Control Mode of the outlet. This OID is provided for informational purposes only.
1.3.6.1.4.1.318.1.1.7NodedcDM3
1.3.6.1.4.1.318.1.1.7.1Nodedm3Ident
1.3.6.1.4.1.318.1.1.7.1.1Nodedm3IdentSystem
1.3.6.1.4.1.318.1.1.7.1.1.1Scalardm3IdentSysDescriptionTableSizeread-onlymandatoryThe number of DC description records.
1.3.6.1.4.1.318.1.1.7.1.1.2Tabledm3IdentSysDescriptionTablenot-accessiblemandatoryAllows for accessing description records of the powerplant. The number of entries is contained in the dm3IdentSysDescriptionTableSize OID.
1.3.6.1.4.1.318.1.1.7.1.1.2.1Rowdm3IdentSysDescriptionEntrynot-accessiblemandatoryThe powerplant description record to reference.
1.3.6.1.4.1.318.1.1.7.1.1.2.1.1Columndm3IdentSysDescriptionIndexread-onlymandatoryThe index to the DC powerplant description record.
1.3.6.1.4.1.318.1.1.7.1.1.2.1.2Columndm3IdentSysDescriptionTextread-onlymandatoryA 16 character text field describing the DC power plant device. This field can be configured from the dm3ConfigSysDescriptionText OID.
1.3.6.1.4.1.318.1.1.7.1.1.3Scalardm3IdentSysModelread-onlymandatoryModel type of the DC power plant.
1.3.6.1.4.1.318.1.1.7.1.1.4Scalardm3IdentSysCntrlRevread-onlymandatoryInteger representation of the hardware revision of the Master Controller board.
1.3.6.1.4.1.318.1.1.7.1.1.5Scalardm3IdentSysFWVersionread-onlymandatoryInteger representation of the power plant Master Controller firmware revision.
1.3.6.1.4.1.318.1.1.7.2Nodedm3Config
1.3.6.1.4.1.318.1.1.7.2.1Nodedm3ConfigSystem
1.3.6.1.4.1.318.1.1.7.2.1.1Scalardm3ConfigSysDescriptionTableSizeread-onlymandatoryThe number of DC description records.
1.3.6.1.4.1.318.1.1.7.2.1.2Tabledm3ConfigSysDescriptionTablenot-accessiblemandatoryAllows for accessing description records of the powerplant. The number of entries is contained in the dm3ConfigSysDescriptionTableSize OID.
1.3.6.1.4.1.318.1.1.7.2.1.2.1Rowdm3ConfigSysDescriptionEntrynot-accessiblemandatoryThe powerplant description record to reference.
1.3.6.1.4.1.318.1.1.7.2.1.2.1.1Columndm3ConfigSysDescriptionIndexread-onlymandatoryThe index to the DC powerplant description record.
1.3.6.1.4.1.318.1.1.7.2.1.2.1.2Columndm3ConfigSysDescriptionTextread-writemandatory16 character text field describing the DC power plant device.
1.3.6.1.4.1.318.1.1.7.2.1.3Scalardm3ConfigSysHighTempThreshread-writemandatoryAmbient high temperature threshold. Temperature sensor located on Master Controller board. Values are represented in thousandths of a degree. Units are display…
1.3.6.1.4.1.318.1.1.7.2.1.4Scalardm3ConfigSysHighTempAlarmread-writemandatoryFor the System High Temperature Alarm; Setting this OID to alarmIgnore (1) results in the alarm condition being ignored. Setting this OID to alarmRelay1 (2) ca…
1.3.6.1.4.1.318.1.1.7.2.1.5Scalardm3ConfigSysLowTempThreshread-writemandatoryAmbient low temperature threshold. Temperature sensor located on Master Controller board. Values are represented in thousandths of a degree. Units are displaye…
1.3.6.1.4.1.318.1.1.7.2.1.6Scalardm3ConfigSysLowTempAlarmread-writemandatoryFor the System Low Temperature Alarm; Setting this OID to alarmIgnore (1) results in the alarm condition being ignored. Setting this OID to alarmRelay1 (2) cau…
1.3.6.1.4.1.318.1.1.7.2.1.7Scalardm3ConfigSysHardwareTempAlarmread-writemandatoryFor the System Hardware Temperature Alarm; Setting this OID to alarmIgnore (1) results in the alarm condition being ignored. Setting this OID to alarmRelay1 (2…
1.3.6.1.4.1.318.1.1.7.2.1.8Scalardm3ConfigSysRemoteAccessread-writemandatoryThis OID is used to disable remote write access to the power plant. Setting this OID to accessEnabled (1) will have no affect. Setting this OID to accessDisabl…
1.3.6.1.4.1.318.1.1.7.2.2Nodedm3ConfigLVD
1.3.6.1.4.1.318.1.1.7.2.2.1Scalardm3ConfigLVDTableSizeread-onlymandatoryThe number of DC powerplant LVDs controllable by this IP address.
1.3.6.1.4.1.318.1.1.7.2.2.2Tabledm3ConfigLVDTablenot-accessiblemandatoryAllows for accessing settings of the LVDs. The number of entries is contained in the dm3ConfigLVDTableSize OID.
1.3.6.1.4.1.318.1.1.7.2.2.2.1Rowdm3ConfigLVDEntrynot-accessiblemandatoryThe LVD to configure.
1.3.6.1.4.1.318.1.1.7.2.2.2.1.1Columndm3ConfigLVDIndexread-onlymandatoryThe index to the DC powerplant LVD.
1.3.6.1.4.1.318.1.1.7.2.2.2.1.2Columndm3ConfigLVDNameread-writemandatoryThe name of the LVD. The maximum value is 16 characters.
1.3.6.1.4.1.318.1.1.7.2.2.2.1.3Columndm3ConfigLVDEnableread-writemandatoryThis OID is used to control and indicate if the LVD is on or off. Setting this OID to enabledYes (1) will enable (turn on) the LVD. Setting this OID to enabled…
1.3.6.1.4.1.318.1.1.7.2.2.2.1.4Columndm3ConfigLVDTripThreshread-writemandatoryLVD Trip threshold. If voltage exceeds threshold, the LVD will trip. Values are represented in thousandths of Volts (mV). Attempts to set the value above or be…
1.3.6.1.4.1.318.1.1.7.2.2.2.1.5Columndm3ConfigLVDResetThreshread-writemandatoryLVD Reset threshold. If voltage exceeds threshold, the LVD will reset. Values are represented in thousandths of Volts (mV). Attempts to set the value above or …
1.3.6.1.4.1.318.1.1.7.2.2.2.1.6Columndm3ConfigLVDOpenAlarmread-writemandatoryFor the LVD Open Alarm; Setting this OID to alarmIgnore (1) results in the alarm condition being ignored. Setting this OID to alarmRelay1 (2) causes relay 1 to…
1.3.6.1.4.1.318.1.1.7.2.2.2.1.7Columndm3ConfigLVDHWAlarmread-writemandatoryFor the LVD Hardware Alarm; Setting this OID to alarmIgnore (1) results in the alarm condition being ignored. Setting this OID to alarmRelay1 (2) causes relay …
1.3.6.1.4.1.318.1.1.7.2.3Nodedm3ConfigBattery
1.3.6.1.4.1.318.1.1.7.2.3.1Scalardm3ConfigBattFloatVoltread-writemandatoryBattery Float Voltage. This setting controls the power plant voltage. Values are represented in thousandths of Volts (mV). Attempts to set the value above or b…
1.3.6.1.4.1.318.1.1.7.2.3.2Scalardm3ConfigBattMaxRechargeread-writemandatoryBattery Maximum Recharge Rate. This setting controls the battery max recharge rate. The value is based on C/20 for 240 AHr battery string. Values are represent…
1.3.6.1.4.1.318.1.1.7.2.3.3Scalardm3ConfigBattDischargeThreshread-writemandatoryBattery discharge threshold. If battery output current exceeds threshold a battery discharge alarm will occur. Values are represented in thousandths of Amps (m…
1.3.6.1.4.1.318.1.1.7.2.3.4Scalardm3ConfigBattDischargeAlarmread-writemandatoryFor the Battery Discharge Alarm; Setting this OID to alarmIgnore (1) results in the alarm condition being ignored. Setting this OID to alarmRelay1 (2) causes r…
1.3.6.1.4.1.318.1.1.7.2.3.5Scalardm3ConfigBattHighVoltThreshread-writemandatoryBattery high voltage threshold. If system battery voltage exceeds threshold a battery high voltage alarm will occur. Values are represented in thousandths of V…
1.3.6.1.4.1.318.1.1.7.2.3.6Scalardm3ConfigBattHighVoltAlarmread-writemandatoryFor the Battery High Voltage Alarm; Setting this OID to alarmIgnore (1) results in the alarm condition being ignored. Setting this OID to alarmRelay1 (2) cause…
1.3.6.1.4.1.318.1.1.7.2.3.7Scalardm3ConfigBattLowVoltThreshread-writemandatoryBattery low voltage threshold. If system battery voltage is under threshold a battery low voltage alarm will occur. Values are represented in thousandths of Vo…
1.3.6.1.4.1.318.1.1.7.2.3.8Scalardm3ConfigBattLowVoltAlarmread-writemandatoryFor the Battery Low Voltage Alarm; Setting this OID to alarmIgnore (1) results in the alarm condition being ignored. Setting this OID to alarmRelay1 (2) causes…
1.3.6.1.4.1.318.1.1.7.2.3.9Scalardm3ConfigBattHighTempThreshread-writemandatoryBattery high temperature threshold. If system battery temperature exceeds threshold a battery high temperature alarm will occur. Values are represented in thou…
1.3.6.1.4.1.318.1.1.7.2.3.10Scalardm3ConfigBattHighTempAlarmread-writemandatoryFor the Battery High Temperature Alarm; Setting this OID to alarmIgnore (1) results in the alarm condition being ignored. Setting this OID to alarmRelay1 (2) c…
1.3.6.1.4.1.318.1.1.7.2.3.11Scalardm3ConfigBattLowTempThreshread-writemandatoryBattery low temperature threshold. If system battery temperature is under threshold a battery low temperature alarm will occur. Values are represented in thous…
1.3.6.1.4.1.318.1.1.7.2.3.12Scalardm3ConfigBattLowTempAlarmread-writemandatoryFor the Battery Low Temperature Alarm; Setting this OID to alarmIgnore (1) results in the alarm condition being ignored. Setting this OID to alarmRelay1 (2) ca…
1.3.6.1.4.1.318.1.1.7.2.3.13Scalardm3ConfigBattAmpHourread-writemandatoryBattery Amp-Hour Size. Units are thousandths of Amp hours (mAHr). Attempts to set the value above or below the acceptable range of the powerplant will cause th…
1.3.6.1.4.1.318.1.1.7.2.3.14Scalardm3ConfigCompMethodread-writemandatoryThis OID is used to configure and get the state of the battery temperature compensation. Setting this OID to tempcompOn (1) will enable/turn on the battery tem…
1.3.6.1.4.1.318.1.1.7.2.3.15Scalardm3ConfigCompTempCoeffread-writemandatoryCompensation Temperature Coefficient. (uV/degC/cell). Units are presented in microvolts. Attempts to set the value above or below the acceptable range of the p…
1.3.6.1.4.1.318.1.1.7.2.3.16Scalardm3ConfigHighKneeTempread-writemandatoryHigh Knee for temperature compensation: Compensation temperature coefficient becomes 0mV/degC/cell. Values are represented in thousandths of degrees Celsius. A…
1.3.6.1.4.1.318.1.1.7.2.3.17Scalardm3ConfigLowKneeTempread-writemandatoryLow Knee for temperature compensation: Compensation temperature coefficient becomes 0mV/degC/cell. Values are represented in thousandths of degrees Celsius. At…
1.3.6.1.4.1.318.1.1.7.2.3.18Scalardm3ConfigBattHwCurrentAlarmread-writemandatoryFor the Battery Current Hardware Alarm (indicating current is outside realistic limits, or a possible measurement fault; Setting this OID to alarmIgnore (1) re…
1.3.6.1.4.1.318.1.1.7.2.3.19Scalardm3ConfigBattHwTempAlarmread-writemandatoryFor the Battery Temperature Hardware Alarm (indicating temperature is outside realistic limits, or a possible measurement fault; Setting this OID to alarmIgnor…
1.3.6.1.4.1.318.1.1.7.2.4Nodedm3ConfigPowerModules
1.3.6.1.4.1.318.1.1.7.2.4.1Nodedm3ConfigRectifier
1.3.6.1.4.1.318.1.1.7.2.4.1.1Nodedm3ConfigRectThresh
1.3.6.1.4.1.318.1.1.7.2.4.1.1.1Scalardm3ConfigRectHighVoltThreshread-writemandatoryRectifier high voltage threshold. If rectifier voltage exceeds threshold a rectifier high voltage alarm will occur. Values are represented in thousandths of Vo…
1.3.6.1.4.1.318.1.1.7.2.4.1.1.2Scalardm3ConfigRectLowVoltThreshread-writemandatoryRectifier low voltage threshold. If rectifier voltage is under threshold a rectifier low voltage alarm will occur. Values are represented in thousandths of Vol…
1.3.6.1.4.1.318.1.1.7.2.4.1.1.3Scalardm3ConfigRectFailSaferead-writemandatoryRectifier Fail Safe point. This OID represents the value sent to rectifier controllers to use in the event of communications loss with the Master Controller or…
1.3.6.1.4.1.318.1.1.7.2.4.1.1.4Scalardm3ConfigRectFailCommread-writemandatoryRectifier Communication Fail timeout. This OID represents the time interval in which there is no communication between the rectifier and the master controller …
1.3.6.1.4.1.318.1.1.7.2.4.1.2Nodedm3ConfigRectAlarms
1.3.6.1.4.1.318.1.1.7.2.4.1.2.1Scalardm3ConfigRectHighVoltAlarmread-writemandatoryFor the Rectifier High Voltage Alarm; Setting this OID to alarmIgnore (1) results in the alarm condition being ignored. Setting this OID to alarmRelay1 (2) cau…
1.3.6.1.4.1.318.1.1.7.2.4.1.2.2Scalardm3ConfigRectLowVoltAlarmread-writemandatoryFor the Rectifier Low Voltage Alarm; Setting this OID to alarmIgnore (1) results in the alarm condition being ignored. Setting this OID to alarmRelay1 (2) caus…
1.3.6.1.4.1.318.1.1.7.2.4.1.2.3Scalardm3ConfigRectConfigAlarmread-writemandatoryThis alarm is activated when a new rectifier is detected; Setting this OID to alarmIgnore (1) results in the alarm condition being ignored. Setting this OID to…
1.3.6.1.4.1.318.1.1.7.2.4.1.2.4Scalardm3ConfigRect1ofNAlarmread-writemandatoryThis setting indicates the action if ONE rectifier of a N+1 system has failed; Setting this OID to alarmIgnore (1) results in the alarm condition being ignored…
1.3.6.1.4.1.318.1.1.7.2.4.1.2.5Scalardm3ConfigRect2ofNAlarmread-writemandatoryThis setting indicates the action if TWO OR MORE rectifiers of a N+1 system have failed; Setting this OID to alarmIgnore (1) results in the alarm condition bei…
1.3.6.1.4.1.318.1.1.7.2.4.1.2.6Scalardm3ConfigRectDiagAlarmread-writemandatoryFor the Rectifier Controller Diagnostics Alarm; Setting this OID to alarmIgnore (1) results in the alarm condition being ignored. Setting this OID to alarmRela…
1.3.6.1.4.1.318.1.1.7.2.4.1.2.7Scalardm3ConfigRectImbalanceAlarmread-writemandatoryFor the Rectifier Imbalance Alarm; Setting this OID to alarmIgnore (1) results in the alarm condition being ignored. Setting this OID to alarmRelay1 (2) causes…
1.3.6.1.4.1.318.1.1.7.2.4.1.2.8Scalardm3ConfigRectCurrLimitAlarmread-writemandatoryFor the Rectifier Current Limit Alarm (indicating rectifier in the Current Limit state); Setting this OID to alarmIgnore (1) results in the alarm condition bei…
1.3.6.1.4.1.318.1.1.7.2.4.1.2.9Scalardm3ConfigRectStandbyAlarmread-writemandatoryFor the Rectifier Standby Alarm (indicating output DC has been turned off); Setting this OID to alarmIgnore (1) results in the alarm condition being ignored. S…
1.3.6.1.4.1.318.1.1.7.2.4.1.2.10Scalardm3ConfigRectFanFailAlarmread-writemandatoryFor the Rectifier Fan Fail Alarm; Setting this OID to alarmIgnore (1) results in the alarm condition being ignored. Setting this OID to alarmRelay1 (2) causes …
1.3.6.1.4.1.318.1.1.7.2.4.1.2.11Scalardm3ConfigRectFailAlarmread-writemandatoryFor the Rectifier Fail Alarm; Setting this OID to alarmIgnore (1) results in the alarm condition being ignored. Setting this OID to alarmRelay1 (2) causes rela…
1.3.6.1.4.1.318.1.1.7.2.4.1.2.12Scalardm3ConfigRectHwVoltAlarmread-writemandatoryFor the Rectifier Hardware Voltage Alarm (indicating voltage outside realistic limits, or a possible measurement fault); Setting this OID to alarmIgnore (1) re…
1.3.6.1.4.1.318.1.1.7.2.4.2Nodedm3ConfigConverter
1.3.6.1.4.1.318.1.1.7.2.4.2.1Nodedm3ConfigConvThresh
1.3.6.1.4.1.318.1.1.7.2.4.2.1.1Scalardm3ConfigConvHighVoltThreshread-writemandatoryConverter high voltage threshold. If converter voltage exceeds threshold a converter high voltage alarm will occur. Values are represented in thousandths of Vo…
1.3.6.1.4.1.318.1.1.7.2.4.2.1.2Scalardm3ConfigConvLowVoltThreshread-writemandatoryConverter low voltage threshold. If converter voltage exceeds threshold a converter low voltage alarm will occur. Values are represented in thousandths of Volt…
1.3.6.1.4.1.318.1.1.7.2.4.2.1.3Scalardm3ConfigConvFailSaferead-writemandatoryConverter Fail Safe point. This OID represents the value sent to converter controllers to use in the event of communications loss with the Master Controller or…
1.3.6.1.4.1.318.1.1.7.2.4.2.1.4Scalardm3ConfigConvSetPointread-writemandatoryConverter Set point. This OID represents the initial set point used in the voltage control loop. Units are thousandths of Volts (mV). Attempts to set the value…
1.3.6.1.4.1.318.1.1.7.2.4.2.1.5Scalardm3ConfigConvFailMaxread-writemandatoryConverter Fail Maximum limit. This OID represents the value sent to the converter controllers to define the maximum set point allowed. Units are thousandths of…
1.3.6.1.4.1.318.1.1.7.2.4.2.1.6Scalardm3ConfigConvFailMinread-writemandatoryConverter Fail Minimum limit. This OID represents the value sent to the converter controllers to define the minimum set point allowed. Units are thousandths of…
1.3.6.1.4.1.318.1.1.7.2.4.2.1.7Scalardm3ConfigConvFailCommread-writemandatoryConverter Communication Fail timeout. This OID represents the time interval in which there is no communication between the converter and the master controller …
1.3.6.1.4.1.318.1.1.7.2.4.2.2Nodedm3ConfigConvAlarms
1.3.6.1.4.1.318.1.1.7.2.4.2.2.1Scalardm3ConfigConvHighVoltAlarmread-writemandatoryFor the Converter High Voltage Alarm; Setting this OID to alarmIgnore (1) results in the alarm condition being ignored. Setting this OID to alarmRelay1 (2) cau…
1.3.6.1.4.1.318.1.1.7.2.4.2.2.2Scalardm3ConfigConvLowVoltAlarmread-writemandatoryFor the Converter Low Voltage Alarm; Setting this OID to alarmIgnore (1) results in the alarm condition being ignored. Setting this OID to alarmRelay1 (2) caus…
1.3.6.1.4.1.318.1.1.7.2.4.2.2.3Scalardm3ConfigConvConfigAlarmread-writemandatoryFor the Converter Configuration Alarm (indicating a new converter has been detected); Setting this OID to alarmIgnore (1) results in the alarm condition being …
1.3.6.1.4.1.318.1.1.7.2.4.2.2.4Scalardm3ConfigConv1ofNAlarmread-writemandatoryFor the Converter 1ofN Alarm (indicating action if ONE converter of a N+1 system has failed); Setting this OID to alarmIgnore (1) results in the alarm conditio…
1.3.6.1.4.1.318.1.1.7.2.4.2.2.5Scalardm3ConfigConv2ofNAlarmread-writemandatoryFor the Converter 2ofN Alarm (indicating action if TWO OR MORE converters of a N+1 system has failed); Setting this OID to alarmIgnore (1) results in the alarm…
1.3.6.1.4.1.318.1.1.7.2.4.2.2.6Scalardm3ConfigConvDiagAlarmread-writemandatoryFor the Converter Diagnostics Alarm; Setting this OID to alarmIgnore (1) results in the alarm condition being ignored. Setting this OID to alarmRelay1 (2) caus…
1.3.6.1.4.1.318.1.1.7.2.4.2.2.7Scalardm3ConfigConvImbalanceAlarmread-writemandatoryFor the Converter Imbalance Alarm; Setting this OID to alarmIgnore (1) results in the alarm condition being ignored. Setting this OID to alarmRelay1 (2) causes…
1.3.6.1.4.1.318.1.1.7.2.4.2.2.8Scalardm3ConfigConvCurrLimitAlarmread-writemandatoryFor the Converter Current Limit Alarm (indicating the converter is in the Current Limit state); Setting this OID to alarmIgnore (1) results in the alarm condit…
1.3.6.1.4.1.318.1.1.7.2.4.2.2.9Scalardm3ConfigConvStandbyAlarmread-writemandatoryFor the Converter Standby Alarm (indicating the converter is in the Standby state); Setting this OID to alarmIgnore (1) results in the alarm condition being ig…
1.3.6.1.4.1.318.1.1.7.2.4.2.2.10Scalardm3ConfigConvFanFailAlarmread-writemandatoryFor the Converter Fan Fail Alarm; Setting this OID to alarmIgnore (1) results in the alarm condition being ignored. Setting this OID to alarmRelay1 (2) causes …
1.3.6.1.4.1.318.1.1.7.2.4.2.2.11Scalardm3ConfigConvFailAlarmread-writemandatoryFor the Converter Fail Alarm; Setting this OID to alarmIgnore (1) results in the alarm condition being ignored. Setting this OID to alarmRelay1 (2) causes rela…
1.3.6.1.4.1.318.1.1.7.2.4.2.2.12Scalardm3ConfigConvHwVoltAlarmread-writemandatoryFor the Converter Voltage Alarm (indicating voltage outside realistic limits, or a possible measurement fault); Setting this OID to alarmIgnore (1) results in …
1.3.6.1.4.1.318.1.1.7.2.5Nodedm3ConfigRelays
1.3.6.1.4.1.318.1.1.7.2.5.1Nodedm3ConfigOutputRelays
1.3.6.1.4.1.318.1.1.7.2.5.1.1Scalardm3ConfigOutRlyTableSizeread-onlymandatoryThe number of DC powerplant Output Relays controllable by this IP address.
1.3.6.1.4.1.318.1.1.7.2.5.1.2Tabledm3ConfigOutRlyTablenot-accessiblemandatoryAllows for accessing settings of the Output Relays. The number of entries is contained in the dm3ConfigOutRlyTableSize OID.
1.3.6.1.4.1.318.1.1.7.2.5.1.2.1Rowdm3ConfigOutRlyEntrynot-accessiblemandatoryThe output relay to configure.
1.3.6.1.4.1.318.1.1.7.2.5.1.2.1.1Columndm3ConfigOutRlyIndexread-onlymandatoryThe index to the DC powerplant output relay.
1.3.6.1.4.1.318.1.1.7.2.5.1.2.1.2Columndm3ConfigOutRlyNameread-writemandatoryThe name of the output relay. The maximum value is 16 characters.
1.3.6.1.4.1.318.1.1.7.2.5.1.2.1.3Columndm3ConfigOutRlyDelayread-writemandatoryOutput Relay Delay. This OID represents the time delay from the initiation of an output relay action to when the output relay action does occur. If the alarm c…
1.3.6.1.4.1.318.1.1.7.2.5.1.2.1.4Columndm3ConfigOutRlyAlarmread-writemandatoryOutput Relay Alarm. This setting indicates what action to perform in the event of an output relay alarm condition; Setting this OID to alarmIgnore (1) results …
1.3.6.1.4.1.318.1.1.7.2.5.2Nodedm3ConfigInputRelays
1.3.6.1.4.1.318.1.1.7.2.5.2.1Scalardm3ConfigInRlyTableSizeread-onlymandatoryThe number of DC powerplant Input Relays controllable by this IP address.
1.3.6.1.4.1.318.1.1.7.2.5.2.2Tabledm3ConfigInRlyTablenot-accessiblemandatoryAllows for accessing settings of the Input Relays. The number of entries is contained in the dm3ConfigInRlyTableSize OID.
1.3.6.1.4.1.318.1.1.7.2.5.2.2.1Rowdm3ConfigInRlyEntrynot-accessiblemandatoryThe input relay to configure.
1.3.6.1.4.1.318.1.1.7.2.5.2.2.1.1Columndm3ConfigInRlyIndexread-onlymandatoryThe index to the DC powerplant input relay.
1.3.6.1.4.1.318.1.1.7.2.5.2.2.1.2Columndm3ConfigInRlyNameread-writemandatoryThe name of the input relay. The maximum value is 16 characters.
1.3.6.1.4.1.318.1.1.7.2.5.2.2.1.3Columndm3ConfigInRlyDelayread-writemandatoryInput Relay Delay. This OID represents the time delay from the initiation of an input relay action to when the input relay action does occur. If the alarm cond…
1.3.6.1.4.1.318.1.1.7.2.5.2.2.1.4Columndm3ConfigInRlyAlarmread-writemandatoryInput Relay Alarm. This setting indicates what action to perform in the event of an input relay alarm condition; Setting this OID to alarmIgnore (1) results in…
1.3.6.1.4.1.318.1.1.7.2.6Nodedm3ConfigDistribution
1.3.6.1.4.1.318.1.1.7.2.6.1Nodedm3ConfigBreakers
1.3.6.1.4.1.318.1.1.7.2.6.1.1Scalardm3ConfigBreakersTableSizeread-onlymandatoryThe number of DC powerplant circuit breakers controllable by this IP address.
1.3.6.1.4.1.318.1.1.7.2.6.1.2Tabledm3ConfigBreakersTablenot-accessiblemandatoryAllows for accessing settings of the circuit breakers. The number of entries is contained in the dm3ConfigBreakersTableSize OID.
1.3.6.1.4.1.318.1.1.7.2.6.1.2.1Rowdm3ConfigBreakersEntrynot-accessiblemandatoryThe circuit breaker to configure.
1.3.6.1.4.1.318.1.1.7.2.6.1.2.1.1Columndm3ConfigBreakersIndexread-onlymandatoryThe index to the DC powerplant circuit breaker.
1.3.6.1.4.1.318.1.1.7.2.6.1.2.1.2Columndm3ConfigBreakersNameread-writemandatoryThe name of the circuit breaker. The maximum value is 16 characters.
1.3.6.1.4.1.318.1.1.7.2.6.1.2.1.3Columndm3ConfigBreakersAlarmread-writemandatoryCircuit Breaker Alarm. This setting indicates what action to perform in the event of a circuit breaker alarm condition; Setting this OID to alarmIgnore (1) res…
1.3.6.1.4.1.318.1.1.7.2.6.2Nodedm3ConfigFuses
1.3.6.1.4.1.318.1.1.7.2.6.2.1Scalardm3ConfigFusesTableSizeread-onlymandatoryThe number of DC powerplant Fuses controllable by this IP address.
1.3.6.1.4.1.318.1.1.7.2.6.2.2Tabledm3ConfigFusesTablenot-accessiblemandatoryAllows for accessing settings of the Fuses. The number of entries is contained in the dm3ConfigFusesTableSize OID.
1.3.6.1.4.1.318.1.1.7.2.6.2.2.1Rowdm3ConfigFusesEntrynot-accessiblemandatoryThe fuse to configure.
1.3.6.1.4.1.318.1.1.7.2.6.2.2.1.1Columndm3ConfigFusesIndexread-onlymandatoryThe index to the DC powerplant fuse.
1.3.6.1.4.1.318.1.1.7.2.6.2.2.1.2Columndm3ConfigFusesNameread-writemandatoryThe name of the fuse. The maximum value is 16 characters.
1.3.6.1.4.1.318.1.1.7.2.6.2.2.1.3Columndm3ConfigFusesAlarmread-writemandatoryFuses Alarm. This setting indicates what action to perform in the event of a Fuse alarm condition; Setting this OID to alarmIgnore (1) results in the alarm con…
1.3.6.1.4.1.318.1.1.7.3Nodedm3Status
1.3.6.1.4.1.318.1.1.7.3.1Nodedm3StatusSystem
1.3.6.1.4.1.318.1.1.7.3.1.1Scalardm3StatusSystemTempread-onlymandatorySystem temperature based on sensor on Master Controller PCB. Values are represented in thousandths of a degree. Units are displayed in the scale shown in the '…
1.3.6.1.4.1.318.1.1.7.3.1.2Scalardm3StatusSystemStartread-onlymandatoryTime stamp at DC powerplant initialization. The time is represented as MMM,DD,YYYY,HH:MM:SS.
1.3.6.1.4.1.318.1.1.7.3.1.3Scalardm3StatusSysRemoteAccessread-onlymandatoryRemote Access indicator This setting indicates if configuration (write) access to the powerplant is enabled or disabled at the powerplant level. This value wil…
1.3.6.1.4.1.318.1.1.7.3.1.4Scalardm3StatusSysSecurityLevelread-onlymandatoryThis variable shows the current active security access level of controller. This can only be changed directly from the front panel.
1.3.6.1.4.1.318.1.1.7.3.1.5Scalardm3StatusSysTempSanityread-onlymandatorySystem temperature sanity indicator. Indicates if the system temperature is reasonable. Reasonable is defined based on powerplant type. A value of saneYes (1) …
1.3.6.1.4.1.318.1.1.7.3.1.6Scalardm3StatusSysAlarmStateread-onlymandatorySystem Alarm State. Reflects the alarm status of the overall DC system. If a minor alarm is present, the value will be alarmMinor(1). If a major alarm is prese…
1.3.6.1.4.1.318.1.1.7.3.1.7Scalardm3StatusSysTempUnitsread-onlymandatoryThe temperature scale used to display the temperature in the DC system, Celsius(1) or Fahrenheit(2). This setting is based on the system preferences configurat…
1.3.6.1.4.1.318.1.1.7.3.2Nodedm3StatusAlarms
1.3.6.1.4.1.318.1.1.7.3.2.1Scalardm3StatusAlarmsTableSizeread-onlymandatoryThe number of DC powerplant alarms viewable by this IP address.
1.3.6.1.4.1.318.1.1.7.3.2.2Tabledm3StatusAlarmsTablenot-accessiblemandatoryAllows for accessing system alarms. The number of entries is contained in the dm3StatusAlarmsTableSize OID.
1.3.6.1.4.1.318.1.1.7.3.2.2.1Rowdm3StatusAlarmsEntrynot-accessiblemandatoryThe alarm to display.
1.3.6.1.4.1.318.1.1.7.3.2.2.1.1Columndm3StatusAlarmsIndexread-onlymandatoryThe index of the system alarm.
1.3.6.1.4.1.318.1.1.7.3.2.2.1.2Columndm3StatusAlarmsTextread-onlymandatoryThe 16 character text describing the active alarm condition.
1.3.6.1.4.1.318.1.1.7.3.3Nodedm3StatusBattery
1.3.6.1.4.1.318.1.1.7.3.3.1Scalardm3StatusBattCurrentread-onlymandatoryBattery Current: This OID shows the battery current in thousandths of Amps (mA).
1.3.6.1.4.1.318.1.1.7.3.3.2Scalardm3StatusBattTempread-onlymandatoryBattery Temperature: Values are represented in thousandths of a degree. Units are displayed in the scale shown in the 'dm3StatusSysTempUnits' OID (Celsius or F…
1.3.6.1.4.1.318.1.1.7.3.3.3Scalardm3StatusBattCurrentSanityread-onlymandatoryBattery current sanity indicator. Indicates if the battery current is reasonable. Reasonable is defined based on powerplant type. A value of saneYes (1) indica…
1.3.6.1.4.1.318.1.1.7.3.3.4Scalardm3StatusBattTempSanityread-onlymandatoryBattery temperature sanity indicator. Indicates if the battery temperature is reasonable. Reasonable is defined based on powerplant type. A value of saneYes (1…
1.3.6.1.4.1.318.1.1.7.3.4Nodedm3StatusOEM
1.3.6.1.4.1.318.1.1.7.3.4.1Scalardm3StatusOEMrectOffsetread-onlymandatoryThis OID shows the rectifier offset value in thousandths of Volts (mV).
1.3.6.1.4.1.318.1.1.7.3.4.2Scalardm3StatusOEMrectGainread-onlymandatoryThis OID shows the rectifier gain value in thousandths of Volts (mV/V).
1.3.6.1.4.1.318.1.1.7.3.4.3Scalardm3StatusOEMconvOffsetread-onlymandatoryThis OID shows the converter offset value in thousandths of Volts (mV).
1.3.6.1.4.1.318.1.1.7.3.4.4Scalardm3StatusOEMconvGainread-onlymandatoryThis OID shows the converter gain value in thousandths of Volts (mV/V).
1.3.6.1.4.1.318.1.1.7.3.4.5Scalardm3StatusOEMshuntOffsetread-onlymandatoryThis OID shows the shunt offset value in thousandths of Amps (mA).
1.3.6.1.4.1.318.1.1.7.3.4.6Scalardm3StatusOEMshuntGainread-onlymandatoryThis OID shows the shunt gain value in thousandths of Amps (mA/A).
1.3.6.1.4.1.318.1.1.7.3.5Nodedm3StatusLVD
1.3.6.1.4.1.318.1.1.7.3.5.1Scalardm3StatusLVDTableSizeread-onlymandatoryThe number of DC powerplant LVDs viewable by this IP address.
1.3.6.1.4.1.318.1.1.7.3.5.2Tabledm3StatusLVDTablenot-accessiblemandatoryAllows for accessing settings of the LVDs. The number of entries is contained in the dm3StatusLVDTableSize OID.
1.3.6.1.4.1.318.1.1.7.3.5.2.1Rowdm3StatusLVDEntrynot-accessiblemandatoryThe LVD to gather status from.
1.3.6.1.4.1.318.1.1.7.3.5.2.1.1Columndm3StatusLVDIndexread-onlymandatoryThe index to the DC powerplant LVD.
1.3.6.1.4.1.318.1.1.7.3.5.2.1.2Columndm3StatusLVDNameread-onlymandatoryThe name of the LVD. The maximum size is 16 characters. The name is set by using the dm3ConfigLVDName OID. This OID is provided for informational purposes only.
1.3.6.1.4.1.318.1.1.7.3.5.2.1.3Columndm3StatusLVDStateread-onlymandatoryGetting this OID will return statusClosed (1) if the LVD is closed. statusOpened (2) will be returned if the LVD is opened.
1.3.6.1.4.1.318.1.1.7.3.5.2.1.4Columndm3StatusLVDHwFaultread-onlymandatoryGetting this OID will return statusFault (1) if the LVD is faulted. statusNofault (2) will be returned if the LVD is not faulted.
1.3.6.1.4.1.318.1.1.7.3.6Nodedm3StatusPowerModules
1.3.6.1.4.1.318.1.1.7.3.6.1Nodedm3StatusRectifier
1.3.6.1.4.1.318.1.1.7.3.6.1.1Scalardm3StatusRectTableSizeread-onlymandatoryThe number of DC powerplant rectifiers viewable by this IP address.
1.3.6.1.4.1.318.1.1.7.3.6.1.2Tabledm3StatusRectTablenot-accessiblemandatoryAllows for accessing settings of the rectifiers. The number of entries is contained in the dm3StatusRectTableSize OID.
1.3.6.1.4.1.318.1.1.7.3.6.1.2.1Rowdm3StatusRectEntrynot-accessiblemandatoryThe rectifier to gather status from.
1.3.6.1.4.1.318.1.1.7.3.6.1.2.1.1Columndm3StatusRectIndexread-onlymandatoryThe index to the DC powerplant rectifier.
1.3.6.1.4.1.318.1.1.7.3.6.1.2.1.2Columndm3StatusRectIDread-onlymandatoryThis OID shows the rectifier ID. This enumerates the number of the rectifier within a group of rectifiers.
1.3.6.1.4.1.318.1.1.7.3.6.1.2.1.3Columndm3StatusRectDescread-onlymandatoryThis OID shows the 16-character rectifier description.
1.3.6.1.4.1.318.1.1.7.3.6.1.2.1.4Columndm3StatusRectCurrentread-onlymandatoryThis OID shows the rectifier current in thousandths of Amps (mA).
1.3.6.1.4.1.318.1.1.7.3.6.1.2.1.5Columndm3StatusRectCurrentLimitread-onlymandatoryGetting this OID will return statusTrue (1) if the rectifier is in the Current Limit state. statusFalse (2) will be returned if the rectifier is not in the Cur…
1.3.6.1.4.1.318.1.1.7.3.6.1.2.1.6Columndm3StatusRectStandbyread-onlymandatoryGetting this OID will return statusTrue (1) if the rectifier is in the Standby state. statusFalse (2) will be returned if the rectifier is not in the Standby s…
1.3.6.1.4.1.318.1.1.7.3.6.1.2.1.7Columndm3StatusRectFanFailread-onlymandatoryGetting this OID will return statusTrue (1) if the rectifier Fan has failed. statusFalse (2) will be returned if the rectifier Fan has not failed.
1.3.6.1.4.1.318.1.1.7.3.6.1.2.1.8Columndm3StatusRectFailread-onlymandatoryGetting this OID will return statusTrue (1) if the rectifier has failed. statusFalse (2) will be returned if the rectifier has not failed.
1.3.6.1.4.1.318.1.1.7.3.6.1.2.1.9Columndm3StatusRectDevTyperead-onlymandatoryThis OID shows the rectifier device type.
1.3.6.1.4.1.318.1.1.7.3.6.1.2.1.10Columndm3StatusRectPhyAddrread-onlymandatoryThis OID shows the rectifier physical address (the address on the bus).
1.3.6.1.4.1.318.1.1.7.3.6.1.2.1.11Columndm3StatusRectCfgread-onlymandatoryGetting this OID will return statusTrue (1) if the rectifier is present after power-up or set-configuration. statusFalse (2) will be returned if the rectifier …
1.3.6.1.4.1.318.1.1.7.3.6.1.2.1.12Columndm3StatusRectPcbRevread-onlymandatoryThis OID shows the rectifier device PCB serial number.
1.3.6.1.4.1.318.1.1.7.3.6.1.2.1.13Columndm3StatusRectFwVerread-onlymandatoryThis OID shows the rectifier device firmware revision.
1.3.6.1.4.1.318.1.1.7.3.6.1.2.1.14Columndm3StatusRectPresentread-onlymandatoryGetting this OID will return statusTrue (1) if the rectifier is present. statusFalse (2) will be returned if the rectifier is not present.
1.3.6.1.4.1.318.1.1.7.3.6.1.2.1.15Columndm3StatusRectDiagPassread-onlymandatoryGetting this OID will return statusTrue (1) if the rectifier diagnostics have passed. statusFalse (2) will be returned if the rectifier diagnostics have not pa…
1.3.6.1.4.1.318.1.1.7.3.6.1.2.1.16Columndm3StatusRectStateread-onlymandatoryThis OID shows the rectifier device state as defined by the device status register.
1.3.6.1.4.1.318.1.1.7.3.6.1.3Scalardm3StatusSysRectVoltSanityread-onlymandatoryRectifier voltage sanity indicator. Indicates if the rectifier voltage is reasonable. Reasonable is defined based on powerplant type. A value of saneYes (1) in…
1.3.6.1.4.1.318.1.1.7.3.6.1.4Scalardm3StatusSysRectAvailableread-onlymandatoryGetting this OID will return statusTrue (1) if the rectifier is available. statusFalse (2) will be returned if the rectifier is not available.
1.3.6.1.4.1.318.1.1.7.3.6.1.5Scalardm3StatusSysRectTyperead-onlymandatoryThis OID shows the type of rectifier the system has. There can only be a single type of rectifier in the power plant
1.3.6.1.4.1.318.1.1.7.3.6.1.6Scalardm3StatusSysRectVoltageread-onlymandatoryThis OID shows the system level rectifier voltage in thousandths of Volts (mV).
1.3.6.1.4.1.318.1.1.7.3.6.1.7Scalardm3StatusSysRectCurrentread-onlymandatoryThis OID shows the system level rectifier current in thousandths of Amps (mA).
1.3.6.1.4.1.318.1.1.7.3.6.2Nodedm3StatusConverter
1.3.6.1.4.1.318.1.1.7.3.6.2.1Scalardm3StatusConvTableSizeread-onlymandatoryThe number of DC powerplant converters viewable by this IP address.
1.3.6.1.4.1.318.1.1.7.3.6.2.2Tabledm3StatusConvTablenot-accessiblemandatoryAllows for viewing status of the converters. The number of entries is contained in the dm3StatusConvTableSize OID.
1.3.6.1.4.1.318.1.1.7.3.6.2.2.1Rowdm3StatusConvEntrynot-accessiblemandatoryThe converter to gather status from.
1.3.6.1.4.1.318.1.1.7.3.6.2.2.1.1Columndm3StatusConvIndexread-onlymandatoryThe index to the DC powerplant converter.
1.3.6.1.4.1.318.1.1.7.3.6.2.2.1.2Columndm3StatusConvIDread-onlymandatoryThis OID shows the converter ID. This enumerates the number of the converter within a group of converters.
1.3.6.1.4.1.318.1.1.7.3.6.2.2.1.3Columndm3StatusConvDescread-onlymandatoryThis OID shows the 16 character converter description.
1.3.6.1.4.1.318.1.1.7.3.6.2.2.1.4Columndm3StatusConvCurrentread-onlymandatoryThis OID shows the converter current in thousandths of Amps (mA).
1.3.6.1.4.1.318.1.1.7.3.6.2.2.1.5Columndm3StatusConvCurrentLimitread-onlymandatoryGetting this OID will return statusTrue (1) if the converter is in the Current Limit state. statusFalse (2) will be returned if the converter is not in the Cur…
1.3.6.1.4.1.318.1.1.7.3.6.2.2.1.6Columndm3StatusConvStandbyread-onlymandatoryGetting this OID will return statusTrue (1) if the converter is in the Standby state. statusFalse (2) will be returned if the converter is not in the Standby s…
1.3.6.1.4.1.318.1.1.7.3.6.2.2.1.7Columndm3StatusConvFanFailread-onlymandatoryGetting this OID will return statusTrue (1) if the converter Fan has failed. statusFalse (2) will be returned if the converter Fan has not failed.
1.3.6.1.4.1.318.1.1.7.3.6.2.2.1.8Columndm3StatusConvFailread-onlymandatoryGetting this OID will return statusTrue (1) if the converter has failed. statusFalse (2) will be returned if the converter has not failed.
1.3.6.1.4.1.318.1.1.7.3.6.2.2.1.9Columndm3StatusConvDevTyperead-onlymandatoryThis OID shows the converter device type.
1.3.6.1.4.1.318.1.1.7.3.6.2.2.1.10Columndm3StatusConvPhyAddrread-onlymandatoryThis OID shows the converter physical address (the address on the bus).
1.3.6.1.4.1.318.1.1.7.3.6.2.2.1.11Columndm3StatusConvCfgread-onlymandatoryGetting this OID will return statusTrue (1) if the converter is present after power-up or set-configuration. statusFalse (2) will be returned if the converter …
1.3.6.1.4.1.318.1.1.7.3.6.2.2.1.12Columndm3StatusConvPcbRevread-onlymandatoryThis OID shows the converter device PCB serial number.
1.3.6.1.4.1.318.1.1.7.3.6.2.2.1.13Columndm3StatusConvFwVerread-onlymandatoryThis OID shows the converter device firmware version.
1.3.6.1.4.1.318.1.1.7.3.6.2.2.1.14Columndm3StatusConvPresentread-onlymandatoryGetting this OID will return statusTrue (1) if the converter is present. statusFalse (2) will be returned if the converter is not present.
1.3.6.1.4.1.318.1.1.7.3.6.2.2.1.15Columndm3StatusConvDiagPassread-onlymandatoryGetting this OID will return statusTrue (1) if the converter diagnostics have passed. statusFalse (2) will be returned if the converter diagnostics have not pa…
1.3.6.1.4.1.318.1.1.7.3.6.2.2.1.16Columndm3StatusConvStateread-onlymandatoryThis OID shows the converter state as defined by the device status register.
1.3.6.1.4.1.318.1.1.7.3.6.2.3Scalardm3StatusSysConvVoltSanityread-onlymandatoryConverter voltage sanity indicator. Indicates if the converter voltage is reasonable. Reasonable is defined based on powerplant type. A value of saneYes (1) in…
1.3.6.1.4.1.318.1.1.7.3.6.2.4Scalardm3StatusSysConvAvailableread-onlymandatoryGetting this OID will return statusTrue (1) if the converter is available. statusFalse (2) will be returned if the converter is not available.
1.3.6.1.4.1.318.1.1.7.3.6.2.5Scalardm3StatusSysConvTyperead-onlymandatoryThis OID shows the converter type.
1.3.6.1.4.1.318.1.1.7.3.6.2.6Scalardm3StatusSysConvVoltageread-onlymandatoryThis OID shows the system level converter voltage in thousandths of volts (mV).
1.3.6.1.4.1.318.1.1.7.3.6.2.7Scalardm3StatusSysConvCurrentread-onlymandatoryThis OID shows the system level converter current in thousandths of Amps (mA).
1.3.6.1.4.1.318.1.1.7.3.7Nodedm3StatusRelays
1.3.6.1.4.1.318.1.1.7.3.7.1Nodedm3StatusOutputRelays
1.3.6.1.4.1.318.1.1.7.3.7.1.1Scalardm3StatusOutRlyTableSizeread-onlymandatoryThe number of DC powerplant output relays viewable by this IP address.
1.3.6.1.4.1.318.1.1.7.3.7.1.2Tabledm3StatusOutRlyTablenot-accessiblemandatoryAllows for viewing status of the output relays. The number of entries is contained in the dm3StatusOutRlyTableSize OID.
1.3.6.1.4.1.318.1.1.7.3.7.1.2.1Rowdm3StatusOutRlyEntrynot-accessiblemandatoryThe output relay to gather status from.
1.3.6.1.4.1.318.1.1.7.3.7.1.2.1.1Columndm3StatusOutRlyIndexread-onlymandatoryThe index to the DC powerplant output relay.
1.3.6.1.4.1.318.1.1.7.3.7.1.2.1.2Columndm3StatusOutRlyNameread-onlymandatoryThe name of the output relay. The maximum size is 16 characters. The name is set by using the dm3ConfigOutRlyName OID. This OID is provided for informational p…
1.3.6.1.4.1.318.1.1.7.3.7.1.2.1.3Columndm3StatusOutRlyStatusread-onlymandatoryGetting this OID will return statusOn (1) if the output relay is enabled/on. statusOff (2) will be returned if the output relay is disabled/off.
1.3.6.1.4.1.318.1.1.7.3.7.2Nodedm3StatusInputRelays
1.3.6.1.4.1.318.1.1.7.3.7.2.1Scalardm3StatusInRlyTableSizeread-onlymandatoryThe number of DC powerplant input relays viewable by this IP address.
1.3.6.1.4.1.318.1.1.7.3.7.2.2Tabledm3StatusInRlyTablenot-accessiblemandatoryAllows for viewing status of the input relays. The number of entries is contained in the dm3StatusInRlyTableSize OID.
1.3.6.1.4.1.318.1.1.7.3.7.2.2.1Rowdm3StatusInRlyEntrynot-accessiblemandatoryThe input relays to gather status from.
1.3.6.1.4.1.318.1.1.7.3.7.2.2.1.1Columndm3StatusInRlyIndexread-onlymandatoryThe index to the DC powerplant input relay.
1.3.6.1.4.1.318.1.1.7.3.7.2.2.1.2Columndm3StatusInRlyNameread-onlymandatoryThe name of the input relay. The maximum size is 16 characters. The name is set by using the dm3ConfigInRlyName OID. This OID is provided for informational pur…
1.3.6.1.4.1.318.1.1.7.3.7.2.2.1.3Columndm3StatusInRlyStatusread-onlymandatoryGetting this OID will return statusOn (1) if the input relay is enabled/on. statusOff (2) will be returned if the input relay is disabled/off.
1.3.6.1.4.1.318.1.1.7.3.8Nodedm3StatusDistribution
1.3.6.1.4.1.318.1.1.7.3.8.1Nodedm3StatusBreakers
1.3.6.1.4.1.318.1.1.7.3.8.1.1Scalardm3StatusBreakersTableSizeread-onlymandatoryThe number of DC powerplant circuit breakers viewable by this IP address.
1.3.6.1.4.1.318.1.1.7.3.8.1.2Tabledm3StatusBreakersTablenot-accessiblemandatoryAllows for viewing status of the circuit breakers. The number of entries is contained in the dm3StatusBreakersTableSize OID.
1.3.6.1.4.1.318.1.1.7.3.8.1.2.1Rowdm3StatusBreakersEntrynot-accessiblemandatoryThe circuit breaker to gather status from.
1.3.6.1.4.1.318.1.1.7.3.8.1.2.1.1Columndm3StatusBreakersIndexread-onlymandatoryThe index to the DC powerplant circuit breaker.
1.3.6.1.4.1.318.1.1.7.3.8.1.2.1.2Columndm3StatusBreakersNameread-onlymandatoryThe name of the circuit breaker. The maximum size is 16 characters. The name is set by using the dm3ConfigBreakersName OID. This OID is provided for informatio…
1.3.6.1.4.1.318.1.1.7.3.8.1.2.1.3Columndm3StatusBreakersStatusread-onlymandatoryGetting this OID will return statusClosed (1) if the circuit breaker is closed. statusOpen (2) will be returned if the circuit breaker is open.
1.3.6.1.4.1.318.1.1.7.3.8.2Nodedm3StatusFuses
1.3.6.1.4.1.318.1.1.7.3.8.2.1Scalardm3StatusFusesTableSizeread-onlymandatoryThe number of DC powerplant fuses controllable by this IP address.
1.3.6.1.4.1.318.1.1.7.3.8.2.2Tabledm3StatusFusesTablenot-accessiblemandatoryAllows for viewing status of the fuses. The number of entries is contained in the dm3StatusFusesTableSize OID.
1.3.6.1.4.1.318.1.1.7.3.8.2.2.1Rowdm3StatusFusesEntrynot-accessiblemandatoryThe fuse to gather status from.
1.3.6.1.4.1.318.1.1.7.3.8.2.2.1.1Columndm3StatusFusesIndexread-onlymandatoryThe index to the DC powerplant fuse.
1.3.6.1.4.1.318.1.1.7.3.8.2.2.1.2Columndm3StatusFusesNameread-onlymandatoryThe name of the fuse. The maximum size is 16 characters. The name is set by using the dm3ConfigFuseName OID. This OID is provided for informational purposes on…
1.3.6.1.4.1.318.1.1.7.3.8.2.2.1.3Columndm3StatusFusesStatusread-onlymandatoryGetting this OID will return statusClosed (1) if the fuse is closed. statusOpen (2) will be returned if the fuse is open.
1.3.6.1.4.1.318.1.1.8NodeautomaticTransferSwitch
1.3.6.1.4.1.318.1.1.8.1NodeatsIdent
1.3.6.1.4.1.318.1.1.8.1.1ScalaratsIdentHardwareRevread-onlymandatoryThe hardware revision of the Automatic Transfer Switch. This value is set at the factory.
1.3.6.1.4.1.318.1.1.8.1.2ScalaratsIdentFirmwareRevread-onlymandatoryA string identifying the Automatic Transfer Switch firmware revision.
1.3.6.1.4.1.318.1.1.8.1.3ScalaratsIdentFirmwareDateread-onlymandatoryThe date of release for this Automatic Transfer Switch firmware revision.
1.3.6.1.4.1.318.1.1.8.1.4ScalaratsIdentDateOfManufactureread-onlymandatoryThe date when the Automatic Transfer Switch was manufactured in mm/dd/yyyy format. This value is set at the factory.
1.3.6.1.4.1.318.1.1.8.1.5ScalaratsIdentModelNumberread-onlymandatoryA string identifying the model number of the Automatic Transfer Switch. This value is set at the factory.
1.3.6.1.4.1.318.1.1.8.1.6ScalaratsIdentSerialNumberread-onlymandatoryA string identifying the serial number of the Automatic Transfer Switch. This value is set at the factory.
1.3.6.1.4.1.318.1.1.8.1.7ScalaratsIdentNominalLineVoltageread-onlymandatoryRMS Utility Voltage measured in Volts.
1.3.6.1.4.1.318.1.1.8.1.8ScalaratsIdentNominalLineFrequencyread-onlymandatoryUtility Power Frequency measured in Hertz.
1.3.6.1.4.1.318.1.1.8.1.9ScalaratsIdentDeviceRatingread-onlymandatoryThis gives the device rating in Amps
1.3.6.1.4.1.318.1.1.8.2NodeatsCalibration
1.3.6.1.4.1.318.1.1.8.2.1NodeatsCalibrationInput
1.3.6.1.4.1.318.1.1.8.2.1.1ScalaratsCalibrationNumInputsread-onlymandatoryThe number of inputs to this device.
1.3.6.1.4.1.318.1.1.8.2.1.2ScalaratsCalibrationNumInputPhasesread-onlymandatoryThe number of phases per input for this device.
1.3.6.1.4.1.318.1.1.8.2.1.3TableatsCalibrationInputPhaseTablenot-accessiblemandatoryThe number of phases per input line to this device.
1.3.6.1.4.1.318.1.1.8.2.1.3.1RowatsCalibrationInputPhaseEntrynot-accessiblemandatoryAn entry containing calibration information applicable to a particular input phase.
1.3.6.1.4.1.318.1.1.8.2.1.3.1.1ColumnatsCalibrationInputTableIndexread-onlymandatoryThe input identifier.
1.3.6.1.4.1.318.1.1.8.2.1.3.1.2ColumnatsCalibrationInputPhaseTableIndexread-onlymandatoryThe input phase identifier.
1.3.6.1.4.1.318.1.1.8.2.1.3.1.3ColumnatsLineVoltageCalibrationFactorread-onlymandatoryThe Line Voltage Calibration factor. This value is set at the factory.
1.3.6.1.4.1.318.1.1.8.2.2NodeatsCalibrationPowerSupply
1.3.6.1.4.1.318.1.1.8.2.2.1ScalaratsCalibrationPowerSupplyVoltagesread-onlymandatoryThe number of power supply voltages supported by this device. This variable indicates the number of rows in the atsCalibrationPowerSupplyTable.
1.3.6.1.4.1.318.1.1.8.2.2.2TableatsCalibrationPowerSupplyVoltageTablenot-accessiblemandatoryA list of Power Supply table entries.
1.3.6.1.4.1.318.1.1.8.2.2.2.1RowatsCalibrationPowerSupplyVoltageEntrynot-accessiblemandatoryAn entry containing information applicable to a particular Power Supply Voltage.
1.3.6.1.4.1.318.1.1.8.2.2.2.1.1ColumnatsCalibrationPowerSupplyVoltageTableIndexread-onlymandatoryThe power supply voltage identifier.
1.3.6.1.4.1.318.1.1.8.2.2.2.1.2ColumnatsCalibrationPowerSupplyVoltageread-onlymandatoryThis value describes the power supply voltage of 24V Source A, 24V Source B, +12V, -12V and 5V.
1.3.6.1.4.1.318.1.1.8.2.2.2.1.3ColumnatsPowerSupplyVoltageCalibrationFactorread-onlymandatoryThe Line Voltage Calibration factor. This value is set at the factory.
1.3.6.1.4.1.318.1.1.8.2.2.3Tableats4gCalibrationPowerSupplyVoltageTablenot-accessiblemandatoryA list of Power Supply table entries. It is not applicable to AP77xx ATS units.
1.3.6.1.4.1.318.1.1.8.2.2.3.1Rowats4gCalibrationPowerSupplyVoltageEntrynot-accessiblemandatoryAn entry containing information applicable to a particular Power Supply Voltage. It is not applicable to AP77xx ATS units.
1.3.6.1.4.1.318.1.1.8.2.2.3.1.1Columnats4gCalibrationPowerSupplyVoltageTableIndexread-onlymandatoryThe power supply voltage identifier. It is not applicable to AP77xx ATS units.
1.3.6.1.4.1.318.1.1.8.2.2.3.1.2Columnats4gCalibrationPowerSupplyVoltageread-onlymandatoryThis value describes the power supply voltage of 24V Source A, 24V Source B, VBoost Source A, VBoost Source B, 3.3V, 1.0V. It is not applicable to AP77xx ATS u…
1.3.6.1.4.1.318.1.1.8.2.2.3.1.3Columnats4gPowerSupplyVoltageCalibrationFactorread-onlymandatoryThe Line Voltage Calibration factor. This value is set at the factory. It is not applicable to AP77xx ATS units.
1.3.6.1.4.1.318.1.1.8.2.3NodeatsCalibrationOutput
1.3.6.1.4.1.318.1.1.8.2.3.1ScalaratsCalibrationNumOutputsread-onlymandatoryThe number of output lines from this device. This variable indicates the number of rows in the atsCalibrationOutputTable.
1.3.6.1.4.1.318.1.1.8.2.3.2ScalaratsCalibrationNumOutputPhasesread-onlymandatoryThe number of output phases utilized in this device.
1.3.6.1.4.1.318.1.1.8.2.3.3TableatsCalibrationOutputTablenot-accessiblemandatoryA list of output table entries.
1.3.6.1.4.1.318.1.1.8.2.3.3.1RowatsCalibrationOutputEntrynot-accessiblemandatoryAn entry containing information applicable to a particular output.
1.3.6.1.4.1.318.1.1.8.2.3.3.1.1ColumnatsCalibrationOutputTableIndexread-onlymandatoryThe output identifier.
1.3.6.1.4.1.318.1.1.8.2.3.3.1.2ColumnatsCalibrationOutputPhasesTableIndexread-onlymandatoryDescription of each calibration factor for each output phase utilized in this device and one for neutral.
1.3.6.1.4.1.318.1.1.8.2.3.3.1.3ColumnatsOutputCurrentCalibrationFactorread-onlymandatoryThe output current calibration factor measured in Amps.
1.3.6.1.4.1.318.1.1.8.2.3.4Tableats4gCalibrationOutputTablenot-accessiblemandatoryA list of output table entries. It is not applicable to AP77xx ATS units.
1.3.6.1.4.1.318.1.1.8.2.3.4.1Rowats4gCalibrationOutputEntrynot-accessiblemandatoryAn entry containing information applicable to a particular output.
1.3.6.1.4.1.318.1.1.8.2.3.4.1.1Columnats4gCalibrationOutputTableIndexread-onlymandatoryThe output identifier.
1.3.6.1.4.1.318.1.1.8.2.3.4.1.2Columnats4gCalibrationOutputPhasesTableIndexread-onlymandatoryDescription of each calibration factor for each output phase utilized in this device and one for neutral. Bank 1 and Bank 2 are for units with two circuit brea…
1.3.6.1.4.1.318.1.1.8.2.3.4.1.3Columnats4gOutputCurrentCalibrationFactorread-onlymandatoryThe output current calibration factor measured in Amps. It is not applicable to AP7xxx ATS units.
1.3.6.1.4.1.318.1.1.8.3NodeatsControl
1.3.6.1.4.1.318.1.1.8.3.1ScalaratsControlResetATSread-writemandatorySetting this variable will cause the Automatic Transfer Switch to perform a power-on reset. It is not applicable to AP44xx units.
1.3.6.1.4.1.318.1.1.8.3.2ScalaratsControlClearAllAlarmsread-writemandatorySetting this variable will clear all alarms in the Automatic Transfer Switch. Returns (-1) if unsupported.
1.3.6.1.4.1.318.1.1.8.4NodeatsConfig
1.3.6.1.4.1.318.1.1.8.4.1ScalaratsConfigProductNameread-writemandatoryA configurable character string.
1.3.6.1.4.1.318.1.1.8.4.2ScalaratsConfigPreferredSourceread-writemandatoryThis variable returns the preferred source of power when both sources are OK.
1.3.6.1.4.1.318.1.1.8.4.3ScalaratsConfigFrontPanelLockoutread-writemandatorySetting this variable to disableFrontPanel(1), prevents source preference configuration of the Automatic Transfer Switch via the Front Panel. Setting this vari…
1.3.6.1.4.1.318.1.1.8.4.4ScalaratsConfigVoltageSensitivityread-writemandatoryThis variable defines the sensitivity to changes in voltage: high(1) for best protection, low(2) for frequent small line voltage changes.
1.3.6.1.4.1.318.1.1.8.4.5ScalaratsConfigTransferVoltageRangeread-writemandatoryThis variable defines the range of acceptable voltage from a power source. If the voltage measured from the selected input source is not within this range, the…
1.3.6.1.4.1.318.1.1.8.4.6ScalaratsConfigCurrentLimitread-writemandatoryThe threshold (in Amps) at which an Over Current Alarm will be generated. This OID returns the overload threshold value of the OID atsConfigPhaseOverLoadThresh…
1.3.6.1.4.1.318.1.1.8.4.7ScalaratsConfigResetValuesread-writemandatoryResets the ATS configuration to its default values. Returns (-1) if not supported.
1.3.6.1.4.1.318.1.1.8.4.8ScalaratsConfigLineVRMSread-writemandatoryTo configure the input RMS voltage.
1.3.6.1.4.1.318.1.1.8.4.9ScalaratsConfigLineVRMSNarrowLimitread-writemandatoryTo configure the Line VRMS Narrow Limit.
1.3.6.1.4.1.318.1.1.8.4.10ScalaratsConfigLineVRMSMediumLimitread-writemandatoryTo configure the Line VRMS Medium Limit.
1.3.6.1.4.1.318.1.1.8.4.11ScalaratsConfigLineVRMSWideLimitread-writemandatoryTo configure the Line VRMS Wide Limit.
1.3.6.1.4.1.318.1.1.8.4.12ScalaratsConfigFrequencyDeviationread-writemandatoryTo configure the frequency deviation. AP77xx units uses the options of 1, 2, or 3. AP44xx units uses the options of 3, 5, or 10.
1.3.6.1.4.1.318.1.1.8.4.13ScalaratsConfigBankTableSizeread-onlymandatoryThe size of the bank table.
1.3.6.1.4.1.318.1.1.8.4.14TableatsConfigBankTablenot-accessiblemandatoryAllows for configuration of each ATS bank.
1.3.6.1.4.1.318.1.1.8.4.14.1RowatsConfigBankEntrynot-accessiblemandatoryThis gives access to bank current threshold
1.3.6.1.4.1.318.1.1.8.4.14.1.1ColumnatsConfigBankTableIndexread-onlymandatoryAn index to the bank table entry.
1.3.6.1.4.1.318.1.1.8.4.14.1.2ColumnatsConfigBankread-onlymandatoryThe bank number of an ATS
1.3.6.1.4.1.318.1.1.8.4.14.1.3ColumnatsConfigBankLowLoadThresholdread-writemandatoryA threshold that indicates the current drawn is nearing a low consumption condition. It is represented in Amps. A warning will be issued when the load is less …
1.3.6.1.4.1.318.1.1.8.4.14.1.4ColumnatsConfigBankNearOverLoadThresholdread-writemandatoryA threshold that indicates the current drawn is nearing an overload condition. It is represented in Amps. A warning will be issued when the load is greater tha…
1.3.6.1.4.1.318.1.1.8.4.14.1.5ColumnatsConfigBankOverLoadThresholdread-writemandatoryA threshold that indicates the current drawn has entered an overload condition. It is represented in Amps. A warning will be issued when the load is greater th…
1.3.6.1.4.1.318.1.1.8.4.15ScalaratsConfigPhaseTableSizeread-onlymandatoryThe size of the phase table.
1.3.6.1.4.1.318.1.1.8.4.16TableatsConfigPhaseTablenot-accessiblemandatoryAllows for configuration of each ATS phase.
1.3.6.1.4.1.318.1.1.8.4.16.1RowatsConfigPhaseEntrynot-accessiblemandatoryThis gives access to phase threshold
1.3.6.1.4.1.318.1.1.8.4.16.1.1ColumnatsConfigPhaseTableIndexread-onlymandatoryThe index to the phase table entry.
1.3.6.1.4.1.318.1.1.8.4.16.1.2ColumnatsConfigPhaseread-onlymandatoryThe phase number of an ATS
1.3.6.1.4.1.318.1.1.8.4.16.1.3ColumnatsConfigPhaseLowLoadThresholdread-writemandatoryA threshold that indicates the current drawn is nearing a low consumption condition. It is represented in Amps. A warning will be issued when the load is less …
1.3.6.1.4.1.318.1.1.8.4.16.1.4ColumnatsConfigPhaseNearOverLoadThresholdread-writemandatoryA threshold that indicates the current drawn is nearing an overload condition. It is represented in Amps. A warning will be issued when the load is greater tha…
1.3.6.1.4.1.318.1.1.8.4.16.1.5ColumnatsConfigPhaseOverLoadThresholdread-writemandatoryA threshold that indicates the current drawn has entered an overload condition. It is represented in Amps. A warning will be issued when the load is greater th…
1.3.6.1.4.1.318.1.1.8.5NodeatsStatus
1.3.6.1.4.1.318.1.1.8.5.1NodeatsStatusDeviceStatus
1.3.6.1.4.1.318.1.1.8.5.1.1ScalaratsStatusCommStatusread-onlymandatoryThis variable returns the current communication status of the Automatic Transfer Switch.
1.3.6.1.4.1.318.1.1.8.5.1.2ScalaratsStatusSelectedSourceread-onlymandatoryThis variable returns the current source of power.
1.3.6.1.4.1.318.1.1.8.5.1.3ScalaratsStatusRedundancyStateread-onlymandatoryThis variable returns the current redundancy state of the ATS. atsRedundancyLost(1) indicates that the ATS is unable to switch over to the alternate power sour…
1.3.6.1.4.1.318.1.1.8.5.1.4ScalaratsStatusOverCurrentStateread-onlymandatoryThis variable returns the output current state of the ATS. atsOverCurrent(1) indicates that the ATS has exceeded the output current threshold and will not allo…
1.3.6.1.4.1.318.1.1.8.5.1.5ScalaratsStatus5VPowerSupplyread-onlymandatoryThis variable returns the present state of the ATS 5V power supply. atsPowerSupplyFailure(1) indicates the 5V power supply has failed and that the ATS serial p…
1.3.6.1.4.1.318.1.1.8.5.1.6ScalaratsStatus24VPowerSupplyread-onlymandatoryThis variable returns the present state of the ATS 24V power supply for Source A. atsPowerSupplyFailure(1) indicates the 24V power supply has failed and the AT…
1.3.6.1.4.1.318.1.1.8.5.1.7ScalaratsStatus24VSourceBPowerSupplyread-onlymandatoryThis variable returns the present state of the ATS 24V power supply for Source B. atsPowerSupplyFailure(1) indicates the 24V power supply has failed and the AT…
1.3.6.1.4.1.318.1.1.8.5.1.8ScalaratsStatusPlus12VPowerSupplyread-onlymandatoryThis variable returns the present state of the ATS 12V power supply. atsPowerSupplyFailure(1) indicates the 12V power supply has failed and the ATS is unable t…
1.3.6.1.4.1.318.1.1.8.5.1.9ScalaratsStatusMinus12VPowerSupplyread-onlymandatoryThis variable returns the present state of the ATS -12V power supply. atsPowerSupplyFailure(1) indicates the -12V power supply has failed and the ATS is unable…
1.3.6.1.4.1.318.1.1.8.5.1.10ScalaratsStatusSwitchStatusread-onlymandatoryThis variable returns the status of the ATS.
1.3.6.1.4.1.318.1.1.8.5.1.11ScalaratsStatusFrontPanelread-onlymandatoryThis variable returns the present state of the ATS front panel. locked(1): Front panel button cannot be used to change the sources. unlocked(2): Front panel bu…
1.3.6.1.4.1.318.1.1.8.5.1.12ScalaratsStatusSourceAStatusread-onlymandatoryThis variable returns the status of the Source A.
1.3.6.1.4.1.318.1.1.8.5.1.13ScalaratsStatusSourceBStatusread-onlymandatoryThis variable returns the status of the Source B.
1.3.6.1.4.1.318.1.1.8.5.1.14ScalaratsStatusPhaseSyncStatusread-onlymandatoryThis variable returns the status of the phase synch.
1.3.6.1.4.1.318.1.1.8.5.1.15ScalaratsStatusVoltageOutStatusread-onlymandatoryThis variable returns the output voltage status.
1.3.6.1.4.1.318.1.1.8.5.1.16ScalaratsStatusHardwareStatusread-onlymandatoryThis variable returns the status of display board hardware.
1.3.6.1.4.1.318.1.1.8.5.1.17ScalaratsStatus3dot3VPowerSupplyread-onlymandatoryThis variable returns the present state of the ATS 3.3V power supply. atsPowerSupplyFailure(1) indicates the 3.3V power supply has failed. atsPowerSupplyOK(2) …
1.3.6.1.4.1.318.1.1.8.5.1.18ScalaratsStatus1Dot0VPowerSupplyread-onlymandatoryThis variable returns the present state of the ATS 1.0V power supply. atsPowerSupplyFailure(1) indicates the 1V power supply has failed. atsPowerSupplyOK(2) in…
1.3.6.1.4.1.318.1.1.8.5.1.19ScalaratsStatusVBoostSourceAread-onlymandatoryThis variable returns the present state of the ATS Source A Boost 48V voltage. atsPowerSupplyFailure(1) indicates the ATS Source A Boost 48V voltage has failed…
1.3.6.1.4.1.318.1.1.8.5.1.20ScalaratsStatusVBoostSourceBread-onlymandatoryThis variable returns the present state of the ATS Source B Boost 48V voltage. atsPowerSupplyFailure(1) indicates the ATS Source B Boost 48V voltage has failed…
1.3.6.1.4.1.318.1.1.8.5.2NodeatsStatusResetValues
1.3.6.1.4.1.318.1.1.8.5.2.1ScalaratsStatusResetMaxMinValuesread-writemandatoryResets the maximum and minimum ATS values: atsInputMaxVoltage, atsInputMinVoltage, atsInputMaxCurrent, atsInputMinCurrent, atsInputMaxPower, atsInputMinPower, …
1.3.6.1.4.1.318.1.1.8.5.3NodeatsStatusInput
1.3.6.1.4.1.318.1.1.8.5.3.1ScalaratsNumInputsread-onlymandatoryThe number of input feeds to this device. This variable indicates the number of rows in the input table.
1.3.6.1.4.1.318.1.1.8.5.3.2TableatsInputTablenot-accessiblemandatoryA list of input table entries. The number of entries is given by the value of atsNumInputs.
1.3.6.1.4.1.318.1.1.8.5.3.2.1RowatsInputEntrynot-accessiblemandatoryAn entry containing information applicable to a particular input.
1.3.6.1.4.1.318.1.1.8.5.3.2.1.1ColumnatsInputTableIndexread-onlymandatoryThe input identifier.
1.3.6.1.4.1.318.1.1.8.5.3.2.1.2ColumnatsNumInputPhasesread-onlymandatoryThe number of input phases utilized in this device. The sum of all the atsNumInputPhases variable indicates the number of rows in the input phase table.
1.3.6.1.4.1.318.1.1.8.5.3.2.1.3ColumnatsInputVoltageOrientationread-onlymandatoryThe input voltage orientation: 1: unknown for this Source 2: singlePhase - phase 1 voltage is between Phase 1 and Neutral. 3: splitPhase - phase 1 voltage is b…
1.3.6.1.4.1.318.1.1.8.5.3.2.1.4ColumnatsInputFrequencyread-onlymandatoryThe input frequency in Hertz, or -1 if it's unsupported by this Source.
1.3.6.1.4.1.318.1.1.8.5.3.2.1.5ColumnatsInputTyperead-onlymandatoryThe input type.
1.3.6.1.4.1.318.1.1.8.5.3.2.1.6ColumnatsInputNameread-writemandatoryA name given to a particular input.
1.3.6.1.4.1.318.1.1.8.5.3.3TableatsInputPhaseTablenot-accessiblemandatoryA list of input table entries. The number of entries is given by the sum of the atsNumInputPhases.
1.3.6.1.4.1.318.1.1.8.5.3.3.1RowatsInputPhaseEntrynot-accessiblemandatoryAn entry containing information applicable to a particular input phase.
1.3.6.1.4.1.318.1.1.8.5.3.3.1.1ColumnatsInputPhaseTableIndexread-onlymandatoryThe input identifier.
1.3.6.1.4.1.318.1.1.8.5.3.3.1.2ColumnatsInputPhaseIndexread-onlymandatoryThe input phase identifier.
1.3.6.1.4.1.318.1.1.8.5.3.3.1.3ColumnatsInputVoltageread-onlymandatoryThe input voltage in VAC, or -1 if it's unsupported by this Source.
1.3.6.1.4.1.318.1.1.8.5.3.3.1.4ColumnatsInputMaxVoltageread-onlymandatoryThe maximum input voltage in VAC measured since the last time this variable was read or reset (atsStatusResetMaxMinValues). Returns (-1) if unsupported.
1.3.6.1.4.1.318.1.1.8.5.3.3.1.5ColumnatsInputMinVoltageread-onlymandatoryThe minimum input voltage in VAC measured since the last time this variable was read or reset (atsStatusResetMaxMinValues). Returns (-1) if unsupported.
1.3.6.1.4.1.318.1.1.8.5.3.3.1.6ColumnatsInputCurrentread-onlymandatoryThe input current in amperes, or -1 if it's unsupported by this Source.
1.3.6.1.4.1.318.1.1.8.5.3.3.1.7ColumnatsInputMaxCurrentread-onlymandatoryThe maximum input current in amperes measured since the last time this variable was read or reset (atsStatusResetMaxMinValues). Returns (-1) if unsupported.
1.3.6.1.4.1.318.1.1.8.5.3.3.1.8ColumnatsInputMinCurrentread-onlymandatoryThe minimum input current in amperes measured since the last time this variable was read or reset (atsStatusResetMaxMinValues). Returns (-1) if unsupported.
1.3.6.1.4.1.318.1.1.8.5.3.3.1.9ColumnatsInputPowerread-onlymandatoryThe input power in Watts, or -1 if it's unsupported by this Source.
1.3.6.1.4.1.318.1.1.8.5.3.3.1.10ColumnatsInputMaxPowerread-onlymandatoryThe maximum input power in Watts measured since the last time this variable was read or reset (atsStatusResetMaxMinValues). Returns (-1) if unsupported.
1.3.6.1.4.1.318.1.1.8.5.3.3.1.11ColumnatsInputMinPowerread-onlymandatoryThe minimum input power in Watts measured since the last time this variable was read or reset (atsStatusResetMaxMinValues). Returns (-1) if unsupported.
1.3.6.1.4.1.318.1.1.8.5.4NodeatsStatusOutput
1.3.6.1.4.1.318.1.1.8.5.4.1ScalaratsNumOutputsread-onlymandatoryThe number of output feeds to this device. This variable indicates the number of rows in the output table.
1.3.6.1.4.1.318.1.1.8.5.4.2TableatsOutputTablenot-accessiblemandatoryA list of output table entries. The number of entries is given by the value of atsOutputNumPhases.
1.3.6.1.4.1.318.1.1.8.5.4.2.1RowatsOutputEntrynot-accessiblemandatoryAn entry containing information applicable to a particular output.
1.3.6.1.4.1.318.1.1.8.5.4.2.1.1ColumnatsOutputTableIndexread-onlymandatoryThe output identifier.
1.3.6.1.4.1.318.1.1.8.5.4.2.1.2ColumnatsNumOutputPhasesread-onlymandatoryThe number of output phases utilized in this device. The sum of all the atsNumOutputPhases variable indicates the number of rows in the output phase table.
1.3.6.1.4.1.318.1.1.8.5.4.2.1.3ColumnatsOutputVoltageOrientationread-onlymandatoryThe output voltage orientation: 1: unknown for this ATS 2: singlePhase - phase 1 voltage is between Phase 1 and Neutral. 3: splitPhase - phase 1 voltage is bet…
1.3.6.1.4.1.318.1.1.8.5.4.2.1.4ColumnatsOutputFrequencyread-onlymandatoryThe output frequency in Hertz, or -1 if it's unsupported by this ATS.
1.3.6.1.4.1.318.1.1.8.5.4.3TableatsOutputPhaseTablenot-accessiblemandatoryA list of output table entries. The number of entries is given by the sum of the atsNumOutputPhases.
1.3.6.1.4.1.318.1.1.8.5.4.3.1RowatsOutputPhaseEntrynot-accessiblemandatoryAn entry containing information applicable to a particular output phase.
1.3.6.1.4.1.318.1.1.8.5.4.3.1.1ColumnatsOutputPhaseTableIndexread-onlymandatoryThe output identifier.
1.3.6.1.4.1.318.1.1.8.5.4.3.1.2ColumnatsOutputPhaseIndexread-onlymandatoryDescription of each output phase utilized in this device and one for neutral.
1.3.6.1.4.1.318.1.1.8.5.4.3.1.3ColumnatsOutputVoltageread-onlymandatoryThe output voltage in VAC, or -1 if it's unsupported by this ATS.
1.3.6.1.4.1.318.1.1.8.5.4.3.1.4ColumnatsOutputCurrentread-onlymandatoryThe output current in 0.1 amperes drawn by the load on the ATS, or -1 if it's unsupported by this ATS.
1.3.6.1.4.1.318.1.1.8.5.4.3.1.5ColumnatsOutputMaxCurrentread-onlymandatoryThe maximum output current in 0.1 amperes measured since the last time this variable was read or reset (atsStatusResetMaxMinValues). Returns (-1) if unsupporte…
1.3.6.1.4.1.318.1.1.8.5.4.3.1.6ColumnatsOutputMinCurrentread-onlymandatoryThe minimum output current in 0.1 amperes measured since the last time this variable was read or reset (atsStatusResetMaxMinValues). Returns (-1) if unsupporte…
1.3.6.1.4.1.318.1.1.8.5.4.3.1.7ColumnatsOutputLoadread-onlymandatoryThe output load in VA, or -1 if it's unsupported by this ATS.
1.3.6.1.4.1.318.1.1.8.5.4.3.1.8ColumnatsOutputMaxLoadread-onlymandatoryThe maximum output load in VA measured since the last time this variable was read or reset (atsStatusResetMaxMinValues). Returns (-1) if unsupported.
1.3.6.1.4.1.318.1.1.8.5.4.3.1.9ColumnatsOutputMinLoadread-onlymandatoryThe minimum output load in VA measured since the last time this variable was read or reset (atsStatusResetMaxMinValues). Returns (-1) if unsupported.
1.3.6.1.4.1.318.1.1.8.5.4.3.1.10ColumnatsOutputPercentLoadread-onlymandatoryThe percentage of the ATS load capacity in VA at redundancy @ (n + x) presently being used on this output phase, or -1 if it's unsupported by this ATS.
1.3.6.1.4.1.318.1.1.8.5.4.3.1.11ColumnatsOutputMaxPercentLoadread-onlymandatoryThe maximum percentage of the ATS load capacity in VA measured at redundancy @ (n + x) presently being used on this output phase since the last time this varia…
1.3.6.1.4.1.318.1.1.8.5.4.3.1.12ColumnatsOutputMinPercentLoadread-onlymandatoryThe minimum percentage of the ATS load capacity in VA measured at redundancy @ (n + x) presently being used on this output phase since the last time this varia…
1.3.6.1.4.1.318.1.1.8.5.4.3.1.13ColumnatsOutputPowerread-onlymandatoryThe output power in VA, or -1 if it's unsupported by this ATS.
1.3.6.1.4.1.318.1.1.8.5.4.3.1.14ColumnatsOutputMaxPowerread-onlymandatoryThe maximum output power in VAs measured since the last time this variable was read or reset (atsStatusResetMaxMinValues). Returns (-1) if unsupported.
1.3.6.1.4.1.318.1.1.8.5.4.3.1.15ColumnatsOutputMinPowerread-onlymandatoryThe minimum output power in VA measured since the last time this variable was read or reset (atsStatusResetMaxMinValues). Returns (-1) if unsupported.
1.3.6.1.4.1.318.1.1.8.5.4.3.1.16ColumnatsOutputPercentPowerread-onlymandatoryThe percentage of the ATSpower capacity in VA at redundancy @ (n + x) presently being used on this output phase, or -1 if it's unsupported by this ATS.
1.3.6.1.4.1.318.1.1.8.5.4.3.1.17ColumnatsOutputMaxPercentPowerread-onlymandatoryThe maximum percentage of the ATSpower capacity in VA measured at redundancy @ (n + x) presently being used on this output phase since the last time this varia…
1.3.6.1.4.1.318.1.1.8.5.4.3.1.18ColumnatsOutputMinPercentPowerread-onlymandatoryThe minimum percentage of the ATSpower capacity in VA measured at redundancy @ (n + x) presently being used on this output phase since the last time this varia…
1.3.6.1.4.1.318.1.1.8.5.4.3.1.19ColumnatsOutputPhaseStateread-onlymandatoryGetting this OID will return the phase load state. normal(1) indicates that the bank is operating properly within the atsConfigPhaseLowLoadThreshold and atsCon…
1.3.6.1.4.1.318.1.1.8.5.4.4ScalaratsOutputBankTableSizeread-onlymandatoryThe size of the bank table.
1.3.6.1.4.1.318.1.1.8.5.4.5TableatsOutputBankTablenot-accessiblemandatoryAllows for getting table entries.
1.3.6.1.4.1.318.1.1.8.5.4.5.1RowatsOutputBankEntrynot-accessiblemandatoryThis gives access to bank table entries
1.3.6.1.4.1.318.1.1.8.5.4.5.1.1ColumnatsOutputBankTableIndexread-onlymandatoryThe index to the bank table entry.
1.3.6.1.4.1.318.1.1.8.5.4.5.1.2ColumnatsOutputPhaseread-onlymandatoryThe phase number of an ATS
1.3.6.1.4.1.318.1.1.8.5.4.5.1.3ColumnatsOutputBankread-onlymandatoryThe bank number of an ATS
1.3.6.1.4.1.318.1.1.8.5.4.5.1.4ColumnatsOutputBankCurrentread-onlymandatoryGetting this OID will return the bank current measured in tenths of Amps.
1.3.6.1.4.1.318.1.1.8.5.4.5.1.5ColumnatsOutputBankStateread-onlymandatoryGetting this OID will return the bank load state. normal(1) indicates that the bank is operating properly within the atsConfigBankLowLoadThreshold and atsConfi…
1.3.6.1.4.1.318.1.1.8.5.4.5.1.6ColumnatsOutputBankOutputVoltageread-onlymandatoryThe output voltage in VAC, or -1 if it's unsupported by this ATS.
1.3.6.1.4.1.318.1.1.8.5.4.5.1.7ColumnatsOutputBankMaxCurrentread-onlymandatoryThe maximum output current, on the bank represented by OID atsOutputBank, in 0.1 amperes measured since the last time this variable was read or reset (atsStatu…
1.3.6.1.4.1.318.1.1.8.5.4.5.1.8ColumnatsOutputBankMinCurrentread-onlymandatoryThe minimum output current, on the bank represented by OID atsOutputBank, in 0.1 amperes measured since the last time this variable was read or reset (atsStatu…
1.3.6.1.4.1.318.1.1.8.5.4.5.1.9ColumnatsOutputBankLoadread-onlymandatoryThe output load, on the bank represented by OID atsOutputBank, in VA, or -1 if it's unsupported by this ATS.
1.3.6.1.4.1.318.1.1.8.5.4.5.1.10ColumnatsOutputBankMaxLoadread-onlymandatoryThe maximum output load, on the bank represented by OID atsOutputBank, in VA measured since the last time this variable was read or reset (atsStatusResetMaxMin…
1.3.6.1.4.1.318.1.1.8.5.4.5.1.11ColumnatsOutputBankMinLoadread-onlymandatoryThe minimum output load, on the bank represented by OID atsOutputBank, in VA measured since the last time this variable was read or reset (atsStatusResetMaxMin…
1.3.6.1.4.1.318.1.1.8.5.4.5.1.12ColumnatsOutputBankPercentLoadread-onlymandatoryThe percentage of the ATS load capacity in VA at redundancy @ (n + x) presently being used on this bank, represented by OID atsOutputBank. Returns (-1) if unsu…
1.3.6.1.4.1.318.1.1.8.5.4.5.1.13ColumnatsOutputBankMaxPercentLoadread-onlymandatoryThe maximum percentage of the ATS load capacity in VA measured at redundancy @ (n + x) presently being used on this bank, represented by OID atsOutputBank, sin…
1.3.6.1.4.1.318.1.1.8.5.4.5.1.14ColumnatsOutputBankMinPercentLoadread-onlymandatoryThe minimum percentage of the ATS load capacity in VA measured at redundancy @ (n + x) presently being used on this bank, represented by OID atsOutputBank, sin…
1.3.6.1.4.1.318.1.1.8.5.4.5.1.15ColumnatsOutputBankPowerread-onlymandatoryThe output power in VA on the bank represented by OID atsOutputBank or -1 if it's unsupported by this ATS.
1.3.6.1.4.1.318.1.1.8.5.4.5.1.16ColumnatsOutputBankMaxPowerread-onlymandatoryThe maximum output power in VA measured on the bank represented by OID atsOutputBank since the last time this variable was read or reset (atsStatusResetMaxMinV…
1.3.6.1.4.1.318.1.1.8.5.4.5.1.17ColumnatsOutputBankMinPowerread-onlymandatoryThe minimum output power in VA measured on the bank represented by OID atsOutputBank since the last time this variable was read or reset (atsStatusResetMaxMinV…
1.3.6.1.4.1.318.1.1.8.5.4.5.1.18ColumnatsOutputBankPercentPowerread-onlymandatoryThe percentage of the ATSpower capacity in Watts at redundancy @ (n + x) presently being used on this bank, represented by OID atsOutputBank, or -1 if it's uns…
1.3.6.1.4.1.318.1.1.8.5.4.5.1.19ColumnatsOutputBankMaxPercentPowerread-onlymandatoryThe maximum percentage of the ATSpower capacity in VA measured at redundancy @ (n + x) presently being used on this bank, represented by OID atsOutputBank, sin…
1.3.6.1.4.1.318.1.1.8.5.4.5.1.20ColumnatsOutputBankMinPercentPowerread-onlymandatoryThe minimum percentage of the ATSpower capacity in VA measured at redundancy @ (n + x) presently being used on this bank, represented by OID atsOutputBank sinc…
1.3.6.1.4.1.318.1.1.9Nodedc2
1.3.6.1.4.1.318.1.1.9.1Nodedcmim2Ident
1.3.6.1.4.1.318.1.1.9.1.1Nodedcmim2IdentSystem
1.3.6.1.4.1.318.1.1.9.1.1.1Scalardcmim2IdentSysFWVersionread-onlymandatoryInteger representation of the power plant Master Controller firmware revision.
1.3.6.1.4.1.318.1.1.9.2Nodedcmim2Control
1.3.6.1.4.1.318.1.1.9.2.1Nodedcmim2ControlSystem
1.3.6.1.4.1.318.1.1.9.2.1.1Scalardcmim2ControlRunFunctBatteryTestread-writemandatoryGetting this OID will return the battery functional test state. If the test is off, the battTestOff (1) value will be returned. If the test is on, the battTest…
1.3.6.1.4.1.318.1.1.9.2.1.2Scalardcmim2ControlRunCapacityBatteryTestread-writemandatoryGetting this OID will return the battery capacity test state. If the test is off, the battTestOff (1) value will be returned. If the test is on, the battTestOn…
1.3.6.1.4.1.318.1.1.9.3Nodedcmim2Config
1.3.6.1.4.1.318.1.1.9.3.1Nodedcmim2ConfigSystem
1.3.6.1.4.1.318.1.1.9.3.1.1Scalardcmim2ConfigSysHighTempTripread-writemandatoryTrip level (threshold) at which System High Temp alarm condition is created. Range 28 to 100 (degC). Values are represented in thousandths of a degree. Units a…
1.3.6.1.4.1.318.1.1.9.3.1.2Scalardcmim2ConfigSysHighTempResetread-writemandatoryLevel at which System High Temp alarm condition is reset (cleared). Range 25 to (upper temp - 3) (degC). Values are represented in thousandths of a degree. Uni…
1.3.6.1.4.1.318.1.1.9.3.1.3Scalardcmim2ConfigSysLowTempTripread-writemandatoryTrip level (threshold) at which System Low Temp alarm condition is created. Range -100 to 10 (degC). Values are represented in thousandths of a degree. Units a…
1.3.6.1.4.1.318.1.1.9.3.1.4Scalardcmim2ConfigSysLowTempResetread-writemandatoryLevel at which System Low Temp alarm condition is reset (cleared). Range (lower temp + 3) to 13 (degC). Values are represented in thousandths of a degree. Unit…
1.3.6.1.4.1.318.1.1.9.3.2Nodedcmim2ConfigBattery
1.3.6.1.4.1.318.1.1.9.3.2.1Scalardcmim2ConfigBattFloatVoltread-writemandatoryBattery Float Voltage defined at 25 degrees Celsius. Values are represented in thousandths of Volts (mV).
1.3.6.1.4.1.318.1.1.9.3.2.2Scalardcmim2ConfigBattMaxRechargeread-writemandatoryBattery Maximum Recharge Rate. This is the maximum current used during battery charging. Values are represented in thousandths of Amps (mA).
1.3.6.1.4.1.318.1.1.9.3.2.3Scalardcmim2ConfigBattMfgCapacityread-writemandatoryBattery capacity (Amp-Hour Size) as specified by the battery manufacturer. Values are represented in thousandths of Amp hours (mAHr).
1.3.6.1.4.1.318.1.1.9.3.2.4Scalardcmim2ConfigBattTyperead-writemandatoryType of battery in the powerplant Valid values range from 0 to 254.
1.3.6.1.4.1.318.1.1.9.3.2.5Scalardcmim2ConfigBattFunctTestDurationread-writemandatoryDuration of the battery functional test. Values are represented in thousandths of seconds (mSecs).
1.3.6.1.4.1.318.1.1.9.3.2.6Scalardcmim2ConfigBattFunctTestThreshread-writemandatoryThreshold the battery voltage of the system must remain above in order to pass the battery functional test. Values are represented in thousandths of Volts (mV).
1.3.6.1.4.1.318.1.1.9.3.2.7Scalardcmim2ConfigBattCapacityTestPercentread-writemandatoryThreshold for good battery capacity test results. Values range from 0 to 100 percent.
1.3.6.1.4.1.318.1.1.9.3.2.8Scalardcmim2ConfigBattCapacityTestEndThreshread-writemandatorySafeguard voltage at which battery capacity test will end if there is a battery problem. Values are represented in thousandths of Volts (mV).
1.3.6.1.4.1.318.1.1.9.3.2.9Scalardcmim2ConfigBattCapacityTestCurrentread-writemandatoryConstant current value used during battery capacity testing. Values are represented in thousandths of Amps (mA).
1.3.6.1.4.1.318.1.1.9.3.3Nodedcmim2ConfigLVD
1.3.6.1.4.1.318.1.1.9.3.3.1Scalardcmim2ConfigLVDTableSizeread-onlymandatoryThe number of DC powerplant LVDs controllable by this IP address.
1.3.6.1.4.1.318.1.1.9.3.3.2Tabledcmim2ConfigLVDTablenot-accessiblemandatoryAllows for accessing settings of the LVDs. The number of entries is contained in the dcmim2ConfigLVDTableSize OID.
1.3.6.1.4.1.318.1.1.9.3.3.2.1Rowdcmim2ConfigLVDEntrynot-accessiblemandatoryThe LVD to configure.
1.3.6.1.4.1.318.1.1.9.3.3.2.1.1Columndcmim2ConfigLVDIndexread-onlymandatoryThe index to the DC powerplant LVD.
1.3.6.1.4.1.318.1.1.9.3.3.2.1.2Columndcmim2ConfigLVDTripread-writemandatoryLVD Trip threshold. System bus voltage at which LVD will trip (open) during a battery backup operation. Values are represented in thousandths of Volts (mV).
1.3.6.1.4.1.318.1.1.9.3.3.2.1.3Columndcmim2ConfigLVDResetread-writemandatoryLVD Reset threshold. System bus voltage at which LVD will reset (close) after AC power has been restored. Values are represented in thousandths of Volts (mV).
1.3.6.1.4.1.318.1.1.9.3.3.2.1.4Columndcmim2ConfigLVDStateread-onlymandatoryGetting this OID will return statusClosed (1) if the LVD is closed. statusOpened (2) will be returned if the LVD is opened.
1.3.6.1.4.1.318.1.1.9.4Nodedcmim2Status
1.3.6.1.4.1.318.1.1.9.4.1Nodedcmim2StatusSystem
1.3.6.1.4.1.318.1.1.9.4.1.1Scalardcmim2StatusSysRectCurrentread-onlymandatorySystem (Total Rectifier) current in thousandths of Amps (mA).
1.3.6.1.4.1.318.1.1.9.4.1.2Scalardcmim2StatusSysLoadCurrentread-onlymandatoryLoad current in thousandths of Amps (mA).
1.3.6.1.4.1.318.1.1.9.4.1.3Scalardcmim2StatusSysBusVoltageread-onlymandatorySystem bus voltage in thousandths of Volts (mV).
1.3.6.1.4.1.318.1.1.9.4.1.4Scalardcmim2StatusSysAmbientTempread-onlymandatorySystem temperature based on sensor on Master Controller PCB. Values are represented in thousandths of a degree. Units are displayed in the scale shown in the '…
1.3.6.1.4.1.318.1.1.9.4.1.5Scalardcmim2StatusSysUpTimeread-onlymandatoryLength of time since the DC Powerplant controller has been powered up.
1.3.6.1.4.1.318.1.1.9.4.1.6Scalardcmim2StatusSysTempUnitsread-onlymandatoryThe temperature scale used to display the temperature in the DC system, Celsius(1) or Fahrenheit(2). This setting is based on the system preferences configurat…
1.3.6.1.4.1.318.1.1.9.4.2Nodedcmim2StatusRectifier
1.3.6.1.4.1.318.1.1.9.4.2.1Scalardcmim2StatusRectTableSizeread-onlymandatoryThe number of DC powerplant rectifiers viewable by this IP address.
1.3.6.1.4.1.318.1.1.9.4.2.2Tabledcmim2StatusRectTablenot-accessiblemandatoryAllows for accessing settings of the rectifiers. The number of entries is contained in the dcmim2StatusRectTableSize OID.
1.3.6.1.4.1.318.1.1.9.4.2.2.1Rowdcmim2StatusRectEntrynot-accessiblemandatoryThe rectifier to gather status from.
1.3.6.1.4.1.318.1.1.9.4.2.2.1.1Columndcmim2StatusRectIndexread-onlymandatoryThe index to the DC powerplant rectifier.
1.3.6.1.4.1.318.1.1.9.4.2.2.1.2Columndcmim2StatusRectDevTyperead-onlymandatoryThis OID shows the rectifier device type.
1.3.6.1.4.1.318.1.1.9.4.2.2.1.3Columndcmim2StatusRectIDread-onlymandatoryThis OID shows the rectifier ID. This enumerates the number of the rectifier within a group of rectifiers.
1.3.6.1.4.1.318.1.1.9.4.2.2.1.4Columndcmim2StatusRectPhyAddrread-onlymandatoryThis OID shows the rectifier physical address (the address on the bus).
1.3.6.1.4.1.318.1.1.9.4.2.2.1.5Columndcmim2StatusRectFailread-onlymandatoryGetting this OID will return statusTrue (1) if the rectifier has failed. statusFalse (2) will be returned if the rectifier has not failed.
1.3.6.1.4.1.318.1.1.9.4.2.2.1.6Columndcmim2StatusRectCurrentread-onlymandatoryThis OID shows the individual rectifier current in thousandths of Amps (mA).
1.3.6.1.4.1.318.1.1.9.4.3Nodedcmim2StatusBattery
1.3.6.1.4.1.318.1.1.9.4.3.1Scalardcmim2StatusBattFloatVoltread-onlymandatoryBattery Float Voltage represented in thousandths of Volts (mV).
1.3.6.1.4.1.318.1.1.9.4.3.2Scalardcmim2StatusBattCurrentread-onlymandatoryBattery Current: This OID shows the battery current in thousandths of Amps (mA).
1.3.6.1.4.1.318.1.1.9.4.3.3Scalardcmim2StatusBattTempread-onlymandatoryBattery Temperature: Values are represented in thousandths of a degree. Units are displayed in the scale shown in the 'dcmim2StatusSysTempUnits' OID (Celsius o…
1.3.6.1.4.1.318.1.1.9.4.3.4Scalardcmim2StatusBattMfgCapacityread-onlymandatoryBattery capacity (Amp-Hour Size) as specified by the battery manufacturer. Values are represented in thousandths of Amp hours (mAHr).
1.3.6.1.4.1.318.1.1.9.4.3.5Scalardcmim2StatusBattTestCapacityread-onlymandatoryBattery capacity (Amp-Hour Size) as determined by the battery capacity test. Values are represented in thousandths of Amp hours (mAHr).
1.3.6.1.4.1.318.1.1.9.4.3.6Scalardcmim2StatusBattFunctTestResultread-onlymandatoryResults of the last battery functional test that was run.
1.3.6.1.4.1.318.1.1.9.4.3.7Scalardcmim2StatusBattCapacityTestResultread-onlymandatoryResults of the last battery capacity test that was run.
1.3.6.1.4.1.318.1.1.9.4.4Nodedcmim2StatusLVD
1.3.6.1.4.1.318.1.1.9.4.4.1Scalardcmim2StatusLVDTableSizeread-onlymandatoryThe number of DC powerplant LVDs accessible by this IP address.
1.3.6.1.4.1.318.1.1.9.4.4.2Tabledcmim2StatusLVDTablenot-accessiblemandatoryAllows for accessing the LVDs. The number of entries is contained in the dcmim2StatusLVDTableSize OID.
1.3.6.1.4.1.318.1.1.9.4.4.2.1Rowdcmim2StatusLVDEntrynot-accessiblemandatoryThe LVD to access.
1.3.6.1.4.1.318.1.1.9.4.4.2.1.1Columndcmim2StatusLVDIndexread-onlymandatoryThe index to the DC powerplant LVD.
1.3.6.1.4.1.318.1.1.9.4.4.2.1.2Columndcmim2StatusLVDStateread-onlymandatoryGetting this OID will return statusClosed (1) if the LVD is closed. statusOpened (2) will be returned if the LVD is opened.
1.3.6.1.4.1.318.1.1.9.4.5Nodedcmim2StatusAlarms
1.3.6.1.4.1.318.1.1.9.4.5.1Scalardcmim2StatusAlarmsTableSizeread-onlymandatoryThe number of DC powerplant alarms viewable by this IP address.
1.3.6.1.4.1.318.1.1.9.4.5.2Tabledcmim2StatusAlarmsTablenot-accessiblemandatoryAllows for accessing system alarms. The number of entries is contained in the dcmim2StatusAlarmsTableSize OID.
1.3.6.1.4.1.318.1.1.9.4.5.2.1Rowdcmim2StatusAlarmsEntrynot-accessiblemandatoryThe alarm to display.
1.3.6.1.4.1.318.1.1.9.4.5.2.1.1Columndcmim2StatusAlarmsIndexread-onlymandatoryThe index of the system alarm.
1.3.6.1.4.1.318.1.1.9.4.5.2.1.2Columndcmim2StatusAlarmsTextread-onlymandatoryThe 16 character text describing the active alarm condition.
1.3.6.1.4.1.318.1.1.10NodeenvironmentalMonitor
1.3.6.1.4.1.318.1.1.10.1Nodeexternal
1.3.6.1.4.1.318.1.1.10.1.1NodeemIdent
1.3.6.1.4.1.318.1.1.10.1.1.1ScalaremIdentFirmwareRevisionread-onlymandatoryThe firmware revision of the Environmental Monitor.
1.3.6.1.4.1.318.1.1.10.1.2NodeemConfig
1.3.6.1.4.1.318.1.1.10.1.2.1ScalaremConfigProbesNumProbesread-onlymandatoryThe number of temperature and humidity probes available.
1.3.6.1.4.1.318.1.1.10.1.2.2TableemConfigProbesTablenot-accessiblemandatoryA list of probes supported by the Environmental Monitor and their configurations.
1.3.6.1.4.1.318.1.1.10.1.2.2.1RowemConfigProbesEntrynot-accessiblemandatoryThe Environmental Monitor probe configurations.
1.3.6.1.4.1.318.1.1.10.1.2.2.1.1ColumnemConfigProbeNumberread-onlymandatoryThe index into an Environmental Monitor probe entry.
1.3.6.1.4.1.318.1.1.10.1.2.2.1.2ColumnemConfigProbeNameread-writemandatoryA descriptive name of the probe set by the user, possibly denoting its location or purpose.
1.3.6.1.4.1.318.1.1.10.1.2.2.1.3ColumnemConfigProbeHighTempThresholdread-writemandatoryThe high temperature alarm threshold for the probe. Units are displayed in the scale selected in the 'emConfigProbeTempUnits' OID (Celsius or Fahrenheit).
1.3.6.1.4.1.318.1.1.10.1.2.2.1.4ColumnemConfigProbeLowTempThresholdread-writemandatoryThe low temperature alarm threshold for the probe. Units are displayed in the scale selected in the 'emConfigProbeTempUnits' OID (Celsius or Fahrenheit).
1.3.6.1.4.1.318.1.1.10.1.2.2.1.5ColumnemConfigProbeTempUnitsread-onlymandatoryThe temperature scale used to display the temperature thresholds of the probe, Celsius(1) or Fahrenheit(2). This setting is based on the system preferences con…
1.3.6.1.4.1.318.1.1.10.1.2.2.1.6ColumnemConfigProbeHighHumidThresholdread-writemandatoryThe high humidity alarm threshold for the probe in percent relative humidity.
1.3.6.1.4.1.318.1.1.10.1.2.2.1.7ColumnemConfigProbeLowHumidThresholdread-writemandatoryThe low humidity alarm threshold for the probe in percent relative humidity.
1.3.6.1.4.1.318.1.1.10.1.2.2.1.8ColumnemConfigProbeHighTempEnableread-writemandatoryThe high temperature alarm enable/disable for the probe. No alarm will be generated if this value is set to disabled(1). The alarm will be generated if this va…
1.3.6.1.4.1.318.1.1.10.1.2.2.1.9ColumnemConfigProbeLowTempEnableread-writemandatoryThe low temperature alarm enable/disable for the probe. No alarm will be generated if this value is set to disabled(1). The alarm will be generated if this val…
1.3.6.1.4.1.318.1.1.10.1.2.2.1.10ColumnemConfigProbeHighHumidEnableread-writemandatoryThe high humidity alarm enable/disable for the probe. No alarm will be generated if this value is set to disabled(1). The alarm will be generated if this value…
1.3.6.1.4.1.318.1.1.10.1.2.2.1.11ColumnemConfigProbeLowHumidEnableread-writemandatoryThe low humidity alarm enable/disable for the probe. No alarm will be generated if this value is set to disabled(1). The alarm will be generated if this value …
1.3.6.1.4.1.318.1.1.10.1.2.2.1.12ColumnemConfigProbeMaxTempThresholdread-writemandatoryThe maximum temperature alarm threshold for the probe. Units are displayed in the scale selected in the 'emConfigProbeTempUnits' OID (Celsius or Fahrenheit).
1.3.6.1.4.1.318.1.1.10.1.2.2.1.13ColumnemConfigProbeMinTempThresholdread-writemandatoryThe minimum temperature alarm threshold for the probe. Units are displayed in the scale selected in the 'emConfigProbeTempUnits' OID (Celsius or Fahrenheit).
1.3.6.1.4.1.318.1.1.10.1.2.2.1.14ColumnemConfigProbeMaxHumidThresholdread-writemandatoryThe maximun humidity alarm threshold for the probe in percent relative humidity.
1.3.6.1.4.1.318.1.1.10.1.2.2.1.15ColumnemConfigProbeMinHumidThresholdread-writemandatoryThe minimum humidity alarm threshold for the probe in percent relative humidity.
1.3.6.1.4.1.318.1.1.10.1.2.2.1.16ColumnemConfigProbeMaxTempEnableread-writemandatoryThe maximum temperature alarm enable/disable for the probe. No alarm will be generated if this value is set to disabled(1). The alarm will be generated if this…
1.3.6.1.4.1.318.1.1.10.1.2.2.1.17ColumnemConfigProbeMinTempEnableread-writemandatoryThe minimum temperature alarm enable/disable for the probe. No alarm will be generated if this value is set to disabled(1). The alarm will be generated if this…
1.3.6.1.4.1.318.1.1.10.1.2.2.1.18ColumnemConfigProbeMaxHumidEnableread-writemandatoryThe maximum humidity alarm enable/disable for the probe. No alarm will be generated if this value is set to disabled(1). The alarm will be generated if this va…
1.3.6.1.4.1.318.1.1.10.1.2.2.1.19ColumnemConfigProbeMinHumidEnableread-writemandatoryThe minimum humidity alarm enable/disable for the probe. No alarm will be generated if this value is set to disabled(1). The alarm will be generated if this va…
1.3.6.1.4.1.318.1.1.10.1.2.2.1.20ColumnemConfigProbeTempHysteresisread-writemandatoryThe number of degrees beyond the temperature thresholds at which an active temperature alarm will be cleared. This configuration setting applies to all tempera…
1.3.6.1.4.1.318.1.1.10.1.2.2.1.21ColumnemConfigProbeHumidHysteresisread-writemandatoryThe number of percent RH points beyond the humidity thresholds at which an active humidity alarm will be cleared. This configuration setting applies to all hum…
1.3.6.1.4.1.318.1.1.10.1.2.2.1.22ColumnemConfigProbeLocationread-writemandatoryA string describing the location of the probe.
1.3.6.1.4.1.318.1.1.10.1.2.3ScalaremConfigContactsNumContactsread-onlymandatoryThe number of contacts supported by the Environmental Monitor.
1.3.6.1.4.1.318.1.1.10.1.2.4TableemConfigContactsTablenot-accessiblemandatoryA list of contacts supported by the Environmental Monitor and their configurations.
1.3.6.1.4.1.318.1.1.10.1.2.4.1RowemConfigContactsEntrynot-accessiblemandatoryThe Environmental Monitor contact configurations.
1.3.6.1.4.1.318.1.1.10.1.2.4.1.1ColumnemConfigContactNumberread-onlymandatoryThe index of an Environmental Monitor contact.
1.3.6.1.4.1.318.1.1.10.1.2.4.1.2ColumnemConfigContactNameread-writemandatoryA descriptive name for an Environmental Monitor contact set by the user, possibly denoting its location or purpose.
1.3.6.1.4.1.318.1.1.10.1.2.4.1.3ColumnemConfigContactEnableread-writemandatoryAn Environmental Monitor contact alarm enable/disable. No alarm will be generated if the contact is disabled(1). An alarm will be generated if the contact is e…
1.3.6.1.4.1.318.1.1.10.1.2.4.1.4ColumnemConfigContactSeverityread-writemandatoryThe severity of the alarm that will be triggered when the input contact is activated. The alarms can be critical(1), warning(2) or informational(3).
1.3.6.1.4.1.318.1.1.10.1.2.4.1.5ColumnemConfigContactNormalStateread-writemandatoryThe contact state that will be considered normal, i.e. will not trigger an alarm. The states are open(1) or closed(2).
1.3.6.1.4.1.318.1.1.10.1.2.4.1.6ColumnemConfigContactLocationread-writemandatoryA descriptive label for the contact denoting its location or purpose.
1.3.6.1.4.1.318.1.1.10.1.3NodeemStatus
1.3.6.1.4.1.318.1.1.10.1.3.1ScalaremStatusCommStatusread-onlymandatoryThe communication status between the agent and the Environmental Monitor. noComm(1), Communication has never been established. comm(2), Communication has been …
1.3.6.1.4.1.318.1.1.10.1.3.2ScalaremStatusProbesNumProbesread-onlymandatoryThe number of available probes on the Environmental Monitor.
1.3.6.1.4.1.318.1.1.10.1.3.3TableemStatusProbesTablenot-accessiblemandatoryA list of probes supported by the Environmental Monitor and their status.
1.3.6.1.4.1.318.1.1.10.1.3.3.1RowemStatusProbesEntrynot-accessiblemandatoryThe status of the probe.
1.3.6.1.4.1.318.1.1.10.1.3.3.1.1ColumnemStatusProbeNumberread-onlymandatoryThe index of the probe.
1.3.6.1.4.1.318.1.1.10.1.3.3.1.2ColumnemStatusProbeNameread-onlymandatoryA descriptive name for the probe set by the user, possibly denoting its location or purpose.
1.3.6.1.4.1.318.1.1.10.1.3.3.1.3ColumnemStatusProbeStatusread-onlymandatoryThe connected status of the probe, either disconnected(1) or connected(2).
1.3.6.1.4.1.318.1.1.10.1.3.3.1.4ColumnemStatusProbeCurrentTempread-onlymandatoryThe current temperature reading from the probe displayed in the units shown in the 'emStatusProbeTempUnits' OID (Celsius or Fahrenheit).
1.3.6.1.4.1.318.1.1.10.1.3.3.1.5ColumnemStatusProbeTempUnitsread-onlymandatoryThe temperature scale used to display the temperature thresholds of the probe, Celsius(1) or Fahrenheit(2). This setting is based on the system preferences con…
1.3.6.1.4.1.318.1.1.10.1.3.3.1.6ColumnemStatusProbeCurrentHumidread-onlymandatoryThe current humidity reading from the probe in percent relative humidity.
1.3.6.1.4.1.318.1.1.10.1.3.3.1.7ColumnemStatusProbeHighTempViolationread-onlymandatoryThe high temperature violation status of the probe temperature reading. This OID will show a highTempViolation(2) if the current temperature reading shown in t…
1.3.6.1.4.1.318.1.1.10.1.3.3.1.8ColumnemStatusProbeLowTempViolationread-onlymandatoryThe high temperature violation status of the probe temperature reading. This OID will show a lowTempViolation(2) if the current temperature reading shown in th…
1.3.6.1.4.1.318.1.1.10.1.3.3.1.9ColumnemStatusProbeHighHumidViolationread-onlymandatoryThe high humidity violation status of the probe humidity reading. This OID will show a highTempViolation(2) if the current humidity reading shown in the 'emSta…
1.3.6.1.4.1.318.1.1.10.1.3.3.1.10ColumnemStatusProbeLowHumidViolationread-onlymandatoryThe low humidity violation status of the probe humidity reading. This OID will show a lowTempViolation(2) if the current humidity reading shown in the 'emStatu…
1.3.6.1.4.1.318.1.1.10.1.3.3.1.11ColumnemStatusProbeMaxTempViolationread-onlymandatoryThe max temperature violation status of the probe temperature reading. This OID will show a maxTempViolation(2) if the current temperature reading shown in the…
1.3.6.1.4.1.318.1.1.10.1.3.3.1.12ColumnemStatusProbeMinTempViolationread-onlymandatoryThe minimum temperature violation status of the probe temperature reading. This OID will show a minTempViolation(2) if the current temperature reading shown in…
1.3.6.1.4.1.318.1.1.10.1.3.3.1.13ColumnemStatusProbeMaxHumidViolationread-onlymandatoryThe maximum humidity violation status of the probe humidity reading. This OID will show a maxTempViolation(2) if the current humidity reading shown in the 'emS…
1.3.6.1.4.1.318.1.1.10.1.3.3.1.14ColumnemStatusProbeMinHumidViolationread-onlymandatoryThe minimum humidity violation status of the probe humidity reading. This OID will show a minTempViolation(2) if the current humidity reading shown in the 'emS…
1.3.6.1.4.1.318.1.1.10.1.3.4ScalaremStatusContactsNumContactsread-onlymandatoryThe number of contacts supported by the Environmental Monitor.
1.3.6.1.4.1.318.1.1.10.1.3.5TableemStatusContactsTablenot-accessiblemandatoryA list of contacts supported by the Environmental Monitor and their status.
1.3.6.1.4.1.318.1.1.10.1.3.5.1RowemStatusContactsEntrynot-accessiblemandatoryThe status of the contact.
1.3.6.1.4.1.318.1.1.10.1.3.5.1.1ColumnemStatusContactNumberread-onlymandatoryThe index of the Environmental Monitor contact.
1.3.6.1.4.1.318.1.1.10.1.3.5.1.2ColumnemStatusContactNameread-onlymandatoryA descriptive name for the Environmental Monitor contact set by the user, possibly denoting its location or purpose.
1.3.6.1.4.1.318.1.1.10.1.3.5.1.3ColumnemStatusContactStatusread-onlymandatoryThe status of the Environmental Monitor contact. The status will show noFault(1) if the contact is in the normal state and the 'emConfigContactEnable' OID is e…
1.3.6.1.4.1.318.1.1.10.2Nodeintegrated
1.3.6.1.4.1.318.1.1.10.2.1NodeiemIdent
1.3.6.1.4.1.318.1.1.10.2.1.1ScalariemIdentHardwareRevisionread-onlymandatoryThe hardware revision of the Integrated Environmental Monitor.
1.3.6.1.4.1.318.1.1.10.2.2NodeiemConfig
1.3.6.1.4.1.318.1.1.10.2.2.1ScalariemConfigProbesNumProbesread-onlymandatoryThe number of temperature and humidity probes available.
1.3.6.1.4.1.318.1.1.10.2.2.2TableiemConfigProbesTablenot-accessiblemandatoryA list of probes supported by the Environmental Monitor and their configurations.
1.3.6.1.4.1.318.1.1.10.2.2.2.1RowiemConfigProbesEntrynot-accessiblemandatoryThe Environmental Monitor probe configurations.
1.3.6.1.4.1.318.1.1.10.2.2.2.1.1ColumniemConfigProbeNumberread-onlymandatoryThe index to a Environmental Monitor probe entry.
1.3.6.1.4.1.318.1.1.10.2.2.2.1.2ColumniemConfigProbeNameread-writemandatoryA descriptive name for the probe set by the user, possibly denoting its location or purpose.
1.3.6.1.4.1.318.1.1.10.2.2.2.1.3ColumniemConfigProbeHighTempThresholdread-writemandatoryThe high temperature alarm threshold for the probe. Units are displayed in the scale selected in the 'iemConfigProbeTempUnits' OID (Celsius or Fahrenheit).
1.3.6.1.4.1.318.1.1.10.2.2.2.1.4ColumniemConfigProbeLowTempThresholdread-writemandatoryThe low temperature alarm threshold for the probe. Units are displayed in the scale selected in the 'iemConfigProbeTempUnits' OID (Celsius or Fahrenheit).
1.3.6.1.4.1.318.1.1.10.2.2.2.1.5ColumniemConfigProbeTempUnitsread-onlymandatoryThe temperature scale used to display the temperature thresholds of the probe, Celsius(1) or Fahrenheit(2). This setting is based on the system preferences con…
1.3.6.1.4.1.318.1.1.10.2.2.2.1.6ColumniemConfigProbeHighHumidThresholdread-writemandatoryThe high humidity alarm threshold for the probe in percent relative humidity.
1.3.6.1.4.1.318.1.1.10.2.2.2.1.7ColumniemConfigProbeLowHumidThresholdread-writemandatoryThe low humidity alarm threshold for the probe in percent relative humidity.
1.3.6.1.4.1.318.1.1.10.2.2.2.1.8ColumniemConfigProbeHighTempEnableread-writemandatoryThe high temperature alarm enable/disable for the probe. No alarm will be generated if this value is set to disabled(1). The alarm will be generated if this va…
1.3.6.1.4.1.318.1.1.10.2.2.2.1.9ColumniemConfigProbeLowTempEnableread-writemandatoryThe low temperature alarm enable/disable for the probe. No alarm will be generated if this value is set to disabled(1). The alarm will be generated if this val…
1.3.6.1.4.1.318.1.1.10.2.2.2.1.10ColumniemConfigProbeHighHumidEnableread-writemandatoryThe high humidity alarm enable/disable for the probe. No alarm will be generated if this value is set to disabled(1). The alarm will be generated if this value…
1.3.6.1.4.1.318.1.1.10.2.2.2.1.11ColumniemConfigProbeLowHumidEnableread-writemandatoryThe low humidity alarm enable/disable for the probe. No alarm will be generated if this value is set to disabled(1). The alarm will be generated if this value …
1.3.6.1.4.1.318.1.1.10.2.2.2.1.12ColumniemConfigProbeMaxTempThresholdread-writemandatoryThe maximun temperature alarm threshold for the probe. Units are displayed in the scale selected in the 'iemConfigProbeTempUnits' OID (Celsius or Fahrenheit).
1.3.6.1.4.1.318.1.1.10.2.2.2.1.13ColumniemConfigProbeMinTempThresholdread-writemandatoryThe minimun temperature alarm threshold for the probe. Units are displayed in the scale selected in the 'iemConfigProbeTempUnits' OID (Celsius or Fahrenheit).
1.3.6.1.4.1.318.1.1.10.2.2.2.1.14ColumniemConfigProbeMaxHumidThresholdread-writemandatoryThe maximum humidity alarm threshold for the probe in percent relative humidity.
1.3.6.1.4.1.318.1.1.10.2.2.2.1.15ColumniemConfigProbeMinHumidThresholdread-writemandatoryThe minimum humidity alarm threshold for the probe in percent relative humidity.
1.3.6.1.4.1.318.1.1.10.2.2.2.1.16ColumniemConfigProbeMaxTempEnableread-writemandatoryThe maximum temperature alarm enable/disable for the probe. No alarm will be generated if this value is set to disabled(1). The alarm will be generated if this…
1.3.6.1.4.1.318.1.1.10.2.2.2.1.17ColumniemConfigProbeMinTempEnableread-writemandatoryThe low temperature alarm enable/disable for the probe. No alarm will be generated if this value is set to disabled(1). The alarm will be generated if this val…
1.3.6.1.4.1.318.1.1.10.2.2.2.1.18ColumniemConfigProbeMaxHumidEnableread-writemandatoryThe maximum humidity alarm enable/disable for the probe. No alarm will be generated if this value is set to disabled(1). The alarm will be generated if this va…
1.3.6.1.4.1.318.1.1.10.2.2.2.1.19ColumniemConfigProbeMinHumidEnableread-writemandatoryThe minimum humidity alarm enable/disable for the probe. No alarm will be generated if this value is set to disabled(1). The alarm will be generated if this va…
1.3.6.1.4.1.318.1.1.10.2.2.2.1.20ColumniemConfigProbeTempHysteresisread-writemandatoryThe number of degrees beyond the temperature thresholds at which an active temperature alarm will be cleared. This configuration setting applies to all tempera…
1.3.6.1.4.1.318.1.1.10.2.2.2.1.21ColumniemConfigProbeHumidHysteresisread-writemandatoryThe number of percent RH points beyond the humidity thresholds at which an active humidity alarm will be cleared. This configuration setting applies to all hum…
1.3.6.1.4.1.318.1.1.10.2.2.2.1.22ColumniemConfigProbeLocationread-writemandatoryA string describing the location of the probe.
1.3.6.1.4.1.318.1.1.10.2.2.3ScalariemConfigContactsNumContactsread-onlymandatoryThe number of contacts available on the Environmental Monitor.
1.3.6.1.4.1.318.1.1.10.2.2.4TableiemConfigContactsTablenot-accessiblemandatoryA list of contacts supported by the Environmental Monitor and their configurations.
1.3.6.1.4.1.318.1.1.10.2.2.4.1RowiemConfigContactsEntrynot-accessiblemandatoryThe Environmental Monitor contact configurations.
1.3.6.1.4.1.318.1.1.10.2.2.4.1.1ColumniemConfigContactNumberread-onlymandatoryThe index of an Environmental Monitor contact.
1.3.6.1.4.1.318.1.1.10.2.2.4.1.2ColumniemConfigContactNameread-writemandatoryA descriptive name for the Environmental Monitor contact set by the user, possibly denoting its location or purpose.
1.3.6.1.4.1.318.1.1.10.2.2.4.1.3ColumniemConfigContactEnableread-writemandatoryAn Environmental Monitor contact alarm enable/disable.
1.3.6.1.4.1.318.1.1.10.2.2.4.1.4ColumniemConfigContactSeverityread-writemandatoryThe severtity of the alarm that will be triggered when the input contact is activated. The alarms can be critical(1), warning(2) or informational(3). NOTE: inf…
1.3.6.1.4.1.318.1.1.10.2.2.4.1.5ColumniemConfigContactNormalStateread-writemandatoryThe contact state that will be considered normal, i.e. will not trigger an alarm. The states are open(1) or closed(2).
1.3.6.1.4.1.318.1.1.10.2.2.4.1.6ColumniemConfigContactLocationread-writemandatoryA descriptive label for the contact denoting its location or purpose.
1.3.6.1.4.1.318.1.1.10.2.2.5ScalariemConfigConfigRelaysNumRelaysread-onlymandatoryThe number of output relays supported by the Environmental Monitor.
1.3.6.1.4.1.318.1.1.10.2.2.6TableiemConfigRelaysTablenot-accessiblemandatoryA list of output relays supported by the Environmental Monitor and their configurations.
1.3.6.1.4.1.318.1.1.10.2.2.6.1RowiemConfigRelaysEntrynot-accessiblemandatoryThe Environmental Monitor output relay configurations.
1.3.6.1.4.1.318.1.1.10.2.2.6.1.1ColumniemConfigRelayNumberread-onlymandatoryThe index of an Environmental Monitor output relay.
1.3.6.1.4.1.318.1.1.10.2.2.6.1.2ColumniemConfigRelayNameread-writemandatoryA descriptive name of an Environmental Monitor output relay, set by the user, describing its location or purpose.
1.3.6.1.4.1.318.1.1.10.2.2.6.1.3ColumniemConfigRelayNormalStateread-writemandatoryThe normal state (non-fault state) of an Environmental Monitor output relay, either open(1) or closed(2).
1.3.6.1.4.1.318.1.1.10.2.2.6.1.4ColumniemConfigRelayFaultConditionread-writemandatoryThe fault condition used to activate the output relay.
1.3.6.1.4.1.318.1.1.10.2.3NodeiemStatus
1.3.6.1.4.1.318.1.1.10.2.3.1ScalariemStatusProbesNumProbesread-onlymandatoryThe number of available probes on the Environmental Monitor.
1.3.6.1.4.1.318.1.1.10.2.3.2TableiemStatusProbesTablenot-accessiblemandatoryA list of probes supported by the Environmental Monitor and their status.
1.3.6.1.4.1.318.1.1.10.2.3.2.1RowiemStatusProbesEntrynot-accessiblemandatoryThe status of the probe.
1.3.6.1.4.1.318.1.1.10.2.3.2.1.1ColumniemStatusProbeNumberread-onlymandatoryThe index of the probe.
1.3.6.1.4.1.318.1.1.10.2.3.2.1.2ColumniemStatusProbeNameread-onlymandatoryA descriptive name for the probe set by the user.
1.3.6.1.4.1.318.1.1.10.2.3.2.1.3ColumniemStatusProbeStatusread-onlymandatoryThe connected status of the probe, either disconnected(1) or connected(2).
1.3.6.1.4.1.318.1.1.10.2.3.2.1.4ColumniemStatusProbeCurrentTempread-onlymandatoryThe current temperature reading from the probe displayed in the units shown in the 'iemStatusProbeTempUnits' OID (Celsius or Fahrenheit).
1.3.6.1.4.1.318.1.1.10.2.3.2.1.5ColumniemStatusProbeTempUnitsread-onlymandatoryThe temperature scale used to display the temperature thresholds of the probe, Celsius(1) or Fahrenheit(2). This setting is based on the system preferences con…
1.3.6.1.4.1.318.1.1.10.2.3.2.1.6ColumniemStatusProbeCurrentHumidread-onlymandatoryThe current humidity reading from the probe in percent relative humidity.
1.3.6.1.4.1.318.1.1.10.2.3.2.1.7ColumniemStatusProbeHighTempViolationread-onlymandatoryThe high temperature violation status of the probe temperature reading. This OID will show a highTempViolation(2) if the current temperature reading shown in t…
1.3.6.1.4.1.318.1.1.10.2.3.2.1.8ColumniemStatusProbeLowTempViolationread-onlymandatoryThe high temperature violation status of the probe temperature reading. This OID will show a lowTempViolation(2) if the current temperature reading shown in th…
1.3.6.1.4.1.318.1.1.10.2.3.2.1.9ColumniemStatusProbeHighHumidViolationread-onlymandatoryThe high humidity violation status of the probe humidity reading. This OID will show a highTempViolation(2) if the current humidity reading shown in the 'iemSt…
1.3.6.1.4.1.318.1.1.10.2.3.2.1.10ColumniemStatusProbeLowHumidViolationread-onlymandatoryThe low humidity violation status of the probe humidity reading. This OID will show a lowTempViolation(2) if the current humidity reading shown in the 'iemStat…
1.3.6.1.4.1.318.1.1.10.2.3.2.1.11ColumniemStatusProbeMaxTempViolationread-onlymandatoryThe max temperature violation status of the probe temperature reading. This OID will show a maxTempViolation(2) if the current temperature reading shown in the…
1.3.6.1.4.1.318.1.1.10.2.3.2.1.12ColumniemStatusProbeMinTempViolationread-onlymandatoryThe minimum temperature violation status of the probe temperature reading. This OID will show a minTempViolation(2) if the current temperature reading shown in…
1.3.6.1.4.1.318.1.1.10.2.3.2.1.13ColumniemStatusProbeMaxHumidViolationread-onlymandatoryThe maximum humidity violation status of the probe humidity reading. This OID will show a maxTempViolation(2) if the current humidity reading shown in the 'iem…
1.3.6.1.4.1.318.1.1.10.2.3.2.1.14ColumniemStatusProbeMinHumidViolationread-onlymandatoryThe minimum humidity violation status of the probe humidity reading. This OID will show a minTempViolation(2) if the current humidity reading shown in the 'iem…
1.3.6.1.4.1.318.1.1.10.2.3.2.1.15ColumniemStatusProbeLocationread-onlymandatoryA descriptive location for the probe set by the user.
1.3.6.1.4.1.318.1.1.10.2.3.3ScalariemStatusContactsNumContactsread-onlymandatoryThe number of contacts supported on the Environmental Monitor.
1.3.6.1.4.1.318.1.1.10.2.3.4TableiemStatusContactsTablenot-accessiblemandatoryA list of contacts supported by the Environmental Monitor and their status.
1.3.6.1.4.1.318.1.1.10.2.3.4.1RowiemStatusContactsEntrynot-accessiblemandatoryThe status of the contact.
1.3.6.1.4.1.318.1.1.10.2.3.4.1.1ColumniemStatusContactNumberread-onlymandatoryThe index of the Environmental Monitor contact.
1.3.6.1.4.1.318.1.1.10.2.3.4.1.2ColumniemStatusContactNameread-onlymandatoryA descriptive name for the Environmental Monitor contact set by the user, denoting its location or purpose.
1.3.6.1.4.1.318.1.1.10.2.3.4.1.3ColumniemStatusContactStatusread-onlymandatoryThe status of the Environmental Monitor contact. The status will show noFault(1) if the contact is in the normal state and the 'iemConfigContactEnable' OID is …
1.3.6.1.4.1.318.1.1.10.2.3.6ScalariemStatusRelaysNumRelaysread-onlymandatoryThe number of output relays supported on the Environmental Monitor.
1.3.6.1.4.1.318.1.1.10.2.3.7TableiemStatusRelaysTablenot-accessiblemandatoryA list of output relays supported by the Environmental Monitor and their status.
1.3.6.1.4.1.318.1.1.10.2.3.7.1RowiemStatusRelaysEntrynot-accessiblemandatoryThe status of the relay.
1.3.6.1.4.1.318.1.1.10.2.3.7.1.1ColumniemStatusRelayNumberread-onlymandatoryThe index of the output relay.
1.3.6.1.4.1.318.1.1.10.2.3.7.1.2ColumniemStatusRelayNameread-onlymandatoryA descriptive name for the output relay set by the user, denoting its location or purpose.
1.3.6.1.4.1.318.1.1.10.2.3.7.1.3ColumniemStatusRelayStatusread-onlymandatoryThe status of the output relay, either faultState(1) or normalState(2).
1.3.6.1.4.1.318.1.1.10.3NodeenvMgtSystem
1.3.6.1.4.1.318.1.1.10.3.1NodeemsIdent
1.3.6.1.4.1.318.1.1.10.3.1.1ScalaremsIdentEMSNameread-onlymandatoryA character string identifying the device.
1.3.6.1.4.1.318.1.1.10.3.1.2ScalaremsIdentProductNumberread-onlymandatoryA character string identifying the model number of the device. This value is set at the factory.
1.3.6.1.4.1.318.1.1.10.3.1.3ScalaremsIdentFirmwareRevread-onlymandatoryThe firmware revision of the device.
1.3.6.1.4.1.318.1.1.10.3.1.4ScalaremsIdentHardwareRevread-onlymandatoryThe hardware revision of the device. This value is set at the factory.
1.3.6.1.4.1.318.1.1.10.3.1.5ScalaremsIdentDateOfManufactureread-onlymandatoryThe date when the device was manufactured in mm/dd/yyyy format. This value is set at the factory.
1.3.6.1.4.1.318.1.1.10.3.1.6ScalaremsIdentSerialNumberread-onlymandatoryA character string identifying the serial number of the device. This value is set at the factory.
1.3.6.1.4.1.318.1.1.10.3.2NodeemsOutputRelayControl
1.3.6.1.4.1.318.1.1.10.3.2.1TableemsOutputRelayControlTablenot-accessiblemandatoryAllows for control of individual output relays. The number of entries is contained in the emsStatusOutputRelayCount OID.
1.3.6.1.4.1.318.1.1.10.3.2.1.1RowemsOutputRelayControlEntrynot-accessiblemandatoryThe output relays to control.
1.3.6.1.4.1.318.1.1.10.3.2.1.1.1ColumnemsOutputRelayControlOutputRelayIndexread-onlymandatoryThe index to the output relay entry.
1.3.6.1.4.1.318.1.1.10.3.2.1.1.2ColumnemsOutputRelayControlOutputRelayNameread-onlymandatoryThe name of the output relay. This OID is provided for informational purposes only.
1.3.6.1.4.1.318.1.1.10.3.2.1.1.3ColumnemsOutputRelayControlOutputRelayCommandread-writemandatoryGetting this variable will return the output relay state. If the output relay is closed, the immediateCloseEMS (1) value will be returned. If the output relay …
1.3.6.1.4.1.318.1.1.10.3.3NodeemsOutletControl
1.3.6.1.4.1.318.1.1.10.3.3.1TableemsOutletControlTablenot-accessiblemandatoryAllows for control of individual outlet switches. The number of entries is contained in the emsStatusOutletCount OID.
1.3.6.1.4.1.318.1.1.10.3.3.1.1RowemsOutletControlEntrynot-accessiblemandatoryThe outlets to control.
1.3.6.1.4.1.318.1.1.10.3.3.1.1.1ColumnemsOutletControlOutletIndexread-onlymandatoryThe index to the outlet entry.
1.3.6.1.4.1.318.1.1.10.3.3.1.1.2ColumnemsOutletControlOutletNameread-onlymandatoryThe name of the outlet. This OID is provided for informational purposes only.
1.3.6.1.4.1.318.1.1.10.3.3.1.1.3ColumnemsOutletControlOutletCommandread-writemandatoryGetting this variable will return the outlet state. If the outlet is on, the immediateOnEMS (1) value will be returned. If the outlet is off, the immediateOffE…
1.3.6.1.4.1.318.1.1.10.3.4NodeemsSensorControl
1.3.6.1.4.1.318.1.1.10.3.4.1TableemsSensorControlTablenot-accessiblemandatoryAllows for control/reset of individual sensors. The number of entries is contained in the emsStatusSensorCount OID.
1.3.6.1.4.1.318.1.1.10.3.4.1.1RowemsSensorControlEntrynot-accessiblemandatoryThe sensors to control/reset.
1.3.6.1.4.1.318.1.1.10.3.4.1.1.1ColumnemsSensorControlSensorIndexread-onlymandatoryThe index to the sensor entry.
1.3.6.1.4.1.318.1.1.10.3.4.1.1.2ColumnemsSensorControlSensorSystemNameread-onlymandatoryThe system name of the sensor. This describes the hardware system intent of this sensor.
1.3.6.1.4.1.318.1.1.10.3.4.1.1.3ColumnemsSensorControlSensorUserNameread-onlymandatoryThe name of the sensor as given by the system user.
1.3.6.1.4.1.318.1.1.10.3.4.1.1.4ColumnemsSensorControlSensorCommandread-writemandatoryGetting this variable will return noCommandEMS(1). Setting this variable to resetCommandEMS(2) will issue a reset command to the sensor. Some sensors cannot be…
1.3.6.1.4.1.318.1.1.10.3.5NodeemsAlarmDeviceControl
1.3.6.1.4.1.318.1.1.10.3.5.1TableemsAlarmDeviceControlTablenot-accessiblemandatoryAllows for control of individual alarm devices. Note: Some alarm devices are not controllable. The number of entries is contained in the emsStatusAlarmDeviceCo…
1.3.6.1.4.1.318.1.1.10.3.5.1.1RowemsAlarmDeviceControlEntrynot-accessiblemandatoryThe alarm devices to control.
1.3.6.1.4.1.318.1.1.10.3.5.1.1.1ColumnemsAlarmDeviceControlDeviceIndexread-onlymandatoryThe index to the alarm device entry.
1.3.6.1.4.1.318.1.1.10.3.5.1.1.2ColumnemsAlarmDeviceControlDeviceNameread-onlymandatoryThe name of the alarm device. This OID is provided for informational purposes only.
1.3.6.1.4.1.318.1.1.10.3.5.1.1.3ColumnemsAlarmDeviceControlDeviceCommandread-writemandatoryGetting this variable will return the device state. If the device is active, the alarmDeviceOnEMS (1) value will be returned. If the device is inactive, the al…
1.3.6.1.4.1.318.1.1.10.3.6NodeemsConfig
1.3.6.1.4.1.318.1.1.10.3.6.1ScalaremsConfigNameread-writemandatoryThe name of the device.
1.3.6.1.4.1.318.1.1.10.3.6.2ScalaremsConfigCheckLogLightread-writemandatoryThe setting of this OID determines the level of event that will trigger the check-log light on the EMS. This is not available on the EMU2. lightDisabled (1) di…
1.3.6.1.4.1.318.1.1.10.3.7NodeemsProbeConfig
1.3.6.1.4.1.318.1.1.10.3.7.1TableemsProbeConfigTablenot-accessiblemandatoryAllows for configuration of individual probes. The number of entries is contained in the emsStatusProbeCount OID.
1.3.6.1.4.1.318.1.1.10.3.7.1.1RowemsProbeConfigEntrynot-accessiblemandatoryThe probes to configure.
1.3.6.1.4.1.318.1.1.10.3.7.1.1.1ColumnemsProbeConfigProbeIndexread-onlymandatoryThe index to the probe entry.
1.3.6.1.4.1.318.1.1.10.3.7.1.1.2ColumnemsProbeConfigProbeNameread-writemandatoryThe name of the probe.
1.3.6.1.4.1.318.1.1.10.3.7.1.1.3ColumnemsProbeConfigProbeHighTempThreshread-writemandatoryProbe high temperature threshold. Values are represented in whole number degrees. Units are displayed in the scale shown in the emsStatusSysTempUnits OID (Cels…
1.3.6.1.4.1.318.1.1.10.3.7.1.1.4ColumnemsProbeConfigProbeLowTempThreshread-writemandatoryProbe low temperature threshold. Values are represented in whole number degrees. Units are displayed in the scale shown in the emsStatusSysTempUnits OID (Celsi…
1.3.6.1.4.1.318.1.1.10.3.7.1.1.5ColumnemsProbeConfigProbeHighHumidityThreshread-writemandatoryProbe high humidity threshold. Values are represented in whole number percentage.
1.3.6.1.4.1.318.1.1.10.3.7.1.1.6ColumnemsProbeConfigProbeLowHumidityThreshread-writemandatoryProbe low humidity threshold. Values are represented in whole number percentage.
1.3.6.1.4.1.318.1.1.10.3.7.1.1.7ColumnemsProbeConfigProbeMaxTempThreshread-writemandatoryProbe maximum temperature threshold. Values are represented in whole number degrees. Units are displayed in the scale shown in the emsStatusSysTempUnits OID (C…
1.3.6.1.4.1.318.1.1.10.3.7.1.1.8ColumnemsProbeConfigProbeMinTempThreshread-writemandatoryProbe minimum temperature threshold. Values are represented in whole number degrees. Units are displayed in the scale shown in the emsStatusSysTempUnits OID (C…
1.3.6.1.4.1.318.1.1.10.3.7.1.1.9ColumnemsProbeConfigProbeDeltaTempread-writemandatoryProbe delta temperature. Values are represented in whole number degrees. Units are displayed in the scale shown in the emsStatusSysTempUnits OID (Celsius or Fa…
1.3.6.1.4.1.318.1.1.10.3.7.1.1.10ColumnemsProbeConfigProbeMaxHumidityThreshread-writemandatoryProbe maximum humidity threshold. Values are represented in whole number percentage.
1.3.6.1.4.1.318.1.1.10.3.7.1.1.11ColumnemsProbeConfigProbeMinHumidityThreshread-writemandatoryProbe minimum humidity threshold. Values are represented in whole number percentage.
1.3.6.1.4.1.318.1.1.10.3.7.1.1.12ColumnemsProbeConfigProbeDeltaHumidityread-writemandatoryProbe delta humidity. Values are represented in whole number percentage.
1.3.6.1.4.1.318.1.1.10.3.7.1.1.13ColumnemsProbeConfigProbeSTIncTempVarianceread-writemandatoryProbe short-term increasing temperature variance used for rate of change alarms. Values are represented in whole number degrees. Units are displayed in the sca…
1.3.6.1.4.1.318.1.1.10.3.7.1.1.14ColumnemsProbeConfigProbeSTIncTempTimeread-writemandatoryProbe short-term increasing temperature time used for rate of change alarms. Values are represented in whole number minutes.
1.3.6.1.4.1.318.1.1.10.3.7.1.1.15ColumnemsProbeConfigProbeSTDecTempVarianceread-writemandatoryProbe short-term decreasing temperature variance used for rate of change alarms. Values are represented in whole number degrees. Units are displayed in the sca…
1.3.6.1.4.1.318.1.1.10.3.7.1.1.16ColumnemsProbeConfigProbeSTDecTempTimeread-writemandatoryProbe short-term decreasing temperature time used for rate of change alarms. Values are represented in whole number minutes.
1.3.6.1.4.1.318.1.1.10.3.7.1.1.17ColumnemsProbeConfigProbeLTIncTempVarianceread-writemandatoryProbe long-term increasing temperature variance used for rate of change alarms. Values are represented in whole number degrees. Units are displayed in the scal…
1.3.6.1.4.1.318.1.1.10.3.7.1.1.18ColumnemsProbeConfigProbeLTIncTempTimeread-writemandatoryProbe long-term increasing temperature time used for rate of change alarms. Values are represented in whole number hours.
1.3.6.1.4.1.318.1.1.10.3.7.1.1.19ColumnemsProbeConfigProbeLTDecTempVarianceread-writemandatoryProbe long-term decreasing temperature variance used for rate of change alarms. Values are represented in whole number degrees. Units are displayed in the scal…
1.3.6.1.4.1.318.1.1.10.3.7.1.1.20ColumnemsProbeConfigProbeLTDecTempTimeread-writemandatoryProbe long-term decreasing temperature time used for rate of change alarms. Values are represented in whole number hours.
1.3.6.1.4.1.318.1.1.10.3.8NodeemsInputContactConfig
1.3.6.1.4.1.318.1.1.10.3.8.1TableemsInputContactConfigTablenot-accessiblemandatoryAllows for configuration of individual input contacts. The number of entries is contained in the emsStatusInputContactCount OID.
1.3.6.1.4.1.318.1.1.10.3.8.1.1RowemsInputContactConfigEntrynot-accessiblemandatoryThe input contacts to configure.
1.3.6.1.4.1.318.1.1.10.3.8.1.1.1ColumnemsInputContactConfigInputContactIndexread-onlymandatoryThe index to the input contact entry.
1.3.6.1.4.1.318.1.1.10.3.8.1.1.2ColumnemsInputContactConfigInputContactNameread-writemandatoryThe name of the input contact.
1.3.6.1.4.1.318.1.1.10.3.8.1.1.3ColumnemsInputContactConfigInputContactNormalStateread-writemandatoryGetting this variable will return the normal state of the input contact. If the normal state is closed, the normallyClosedEMS (1) value will be returned. If th…
1.3.6.1.4.1.318.1.1.10.3.9NodeemsOutputRelayConfig
1.3.6.1.4.1.318.1.1.10.3.9.1TableemsOutputRelayConfigTablenot-accessiblemandatoryAllows for configuration of individual output relays. The number of entries is contained in the emsStatusOutputRelayCount OID.
1.3.6.1.4.1.318.1.1.10.3.9.1.1RowemsOutputRelayConfigEntrynot-accessiblemandatoryThe output relays to configure.
1.3.6.1.4.1.318.1.1.10.3.9.1.1.1ColumnemsOutputRelayConfigOutputRelayIndexread-onlymandatoryThe index to the output relay entry.
1.3.6.1.4.1.318.1.1.10.3.9.1.1.2ColumnemsOutputRelayConfigOutputRelayNameread-writemandatoryThe name of the output relay.
1.3.6.1.4.1.318.1.1.10.3.9.1.1.3ColumnemsOutputRelayConfigOutputRelayNormalStateread-writemandatoryGetting this variable will return the normal state of the output relay. If the normal state is closed, the normallyClosedEMS (1) value will be returned. If the…
1.3.6.1.4.1.318.1.1.10.3.10NodeemsOutletConfig
1.3.6.1.4.1.318.1.1.10.3.10.1TableemsOutletConfigTablenot-accessiblemandatoryAllows for configuration of individual outlets. The number of entries is contained in the emsStatusOutletCount OID.
1.3.6.1.4.1.318.1.1.10.3.10.1.1RowemsOutletConfigEntrynot-accessiblemandatoryThe outlets to configure.
1.3.6.1.4.1.318.1.1.10.3.10.1.1.1ColumnemsOutletConfigOutletIndexread-onlymandatoryThe index to the outlet entry.
1.3.6.1.4.1.318.1.1.10.3.10.1.1.2ColumnemsOutletConfigOutletNameread-writemandatoryThe name of the outlet.
1.3.6.1.4.1.318.1.1.10.3.10.1.1.3ColumnemsOutletConfigOutletNormalStateread-writemandatoryGetting this variable will return the normal state of the outlet. If the normal state is on, the normallyOnEMS (1) value will be returned. If the normal state …
1.3.6.1.4.1.318.1.1.10.3.11NodeemsSensorConfig
1.3.6.1.4.1.318.1.1.10.3.11.1TableemsSensorConfigTablenot-accessiblemandatoryAllows for configuration of individual sensors. The number of entries is contained in the emsStatusSensorCount OID.
1.3.6.1.4.1.318.1.1.10.3.11.1.1RowemsSensorConfigEntrynot-accessiblemandatoryThe sensors to configure.
1.3.6.1.4.1.318.1.1.10.3.11.1.1.1ColumnemsSensorConfigSensorIndexread-onlymandatoryThe index to the sensor entry.
1.3.6.1.4.1.318.1.1.10.3.11.1.1.2ColumnemsSensorConfigSensorSystemNameread-onlymandatoryThe system name of the sensor. This describes the hardware system intent of this sensor.
1.3.6.1.4.1.318.1.1.10.3.11.1.1.3ColumnemsSensorConfigSensorUserNameread-writemandatoryThe name of the sensor as given by the system user.
1.3.6.1.4.1.318.1.1.10.3.11.1.1.4ColumnemsSensorConfigSensorNormalStateread-writemandatoryGetting this variable will return the normal state of the sensor. If the normal state is closed, the normallyClosedEMS (1) value will be returned. If the norma…
1.3.6.1.4.1.318.1.1.10.3.11.1.1.5ColumnemsSensorConfigSensorAlarmDelayread-writemandatoryThe delay (in seconds) after a sensor detects an alarm condition before the condition is reported.
1.3.6.1.4.1.318.1.1.10.3.12NodeemsStatus
1.3.6.1.4.1.318.1.1.10.3.12.1ScalaremsStatusEMSNameread-onlymandatoryA character string identifying the device.
1.3.6.1.4.1.318.1.1.10.3.12.2ScalaremsStatusCommStatusread-onlymandatoryThe communication status between the agent and the device. noComm(1), Communication has never been established. comm(2), Communication has been established. co…
1.3.6.1.4.1.318.1.1.10.3.12.3ScalaremsStatusProbeCountread-onlymandatoryThe total number of T/H probes (both local and remote) that is supported by this device.
1.3.6.1.4.1.318.1.1.10.3.12.4ScalaremsStatusInputContactCountread-onlymandatoryThe total number of Input Contacts that is supported by this device.
1.3.6.1.4.1.318.1.1.10.3.12.5ScalaremsStatusOutputRelayCountread-onlymandatoryThe total number of Output Relays that is supported by this device.
1.3.6.1.4.1.318.1.1.10.3.12.6ScalaremsStatusOutletCountread-onlymandatoryThe total number of AC Outlets that is supported by this device.
1.3.6.1.4.1.318.1.1.10.3.12.7ScalaremsStatusSensorCountread-onlymandatoryThe total number of Sensors that is supported by this device.
1.3.6.1.4.1.318.1.1.10.3.12.8ScalaremsStatusAlinkAruDeviceCountread-onlymandatoryThe total number of remote Aru's supported by this device.
1.3.6.1.4.1.318.1.1.10.3.12.9ScalaremsStatusAlinkProbeDeviceCountread-onlymandatoryThe total number of remote T/H probes supported by this device.
1.3.6.1.4.1.318.1.1.10.3.12.10ScalaremsStatusAlarmDeviceCountread-onlymandatoryThe number of alarm devices supported by this device.
1.3.6.1.4.1.318.1.1.10.3.12.11ScalaremsStatusSysTempUnitsread-onlymandatoryThe temperature scale used to display the temperature in the system, Celsius(1) or Fahrenheit(2). This setting is based on the system preferences configuration…
1.3.6.1.4.1.318.1.1.10.3.12.12ScalaremsStatusCheckLogLightread-onlymandatoryThe status of the check-log light on the device. For the EMU2, this will always indicate lightOff(1). lightOff (1) indicates the light is off (no new log entri…
1.3.6.1.4.1.318.1.1.10.3.12.13ScalaremsStatusHardwareStatusread-onlymandatoryThe status of the EMS hardware. This integer should be interpreted as a bit map, with each bit representing the presence or absence of a specific hardware erro…
1.3.6.1.4.1.318.1.1.10.3.13NodeemsProbeStatus
1.3.6.1.4.1.318.1.1.10.3.13.1TableemsProbeStatusTablenot-accessiblemandatoryAllows for access of individual probes. The number of entries is contained in the emsStatusProbeCount OID.
1.3.6.1.4.1.318.1.1.10.3.13.1.1RowemsProbeStatusEntrynot-accessiblemandatoryThe probes to access.
1.3.6.1.4.1.318.1.1.10.3.13.1.1.1ColumnemsProbeStatusProbeIndexread-onlymandatoryThe index to the probe entry.
1.3.6.1.4.1.318.1.1.10.3.13.1.1.2ColumnemsProbeStatusProbeNameread-onlymandatoryThe name of the probe.
1.3.6.1.4.1.318.1.1.10.3.13.1.1.3ColumnemsProbeStatusProbeTemperatureread-onlymandatoryProbe temperature reading. Values are represented in whole number degrees. Units are displayed in the scale shown in the emsStatusSysTempUnits OID (Celsius or …
1.3.6.1.4.1.318.1.1.10.3.13.1.1.4ColumnemsProbeStatusProbeHighTempThreshread-onlymandatoryProbe high temperature threshold. Values are represented in whole number degrees. Units are displayed in the scale shown in the emsStatusSysTempUnits OID (Cels…
1.3.6.1.4.1.318.1.1.10.3.13.1.1.5ColumnemsProbeStatusProbeLowTempThreshread-onlymandatoryProbe low temperature threshold. Values are represented in whole number degrees. Units are displayed in the scale shown in the emsStatusSysTempUnits OID (Celsi…
1.3.6.1.4.1.318.1.1.10.3.13.1.1.6ColumnemsProbeStatusProbeHumidityread-onlymandatoryProbe humidity reading. Values are represented in whole number percentage.
1.3.6.1.4.1.318.1.1.10.3.13.1.1.7ColumnemsProbeStatusProbeHighHumidityThreshread-onlymandatoryProbe high humidity threshold. Values are represented in whole number percentage.
1.3.6.1.4.1.318.1.1.10.3.13.1.1.8ColumnemsProbeStatusProbeLowHumidityThreshread-onlymandatoryProbe low humidity threshold. Values are represented in whole number percentage.
1.3.6.1.4.1.318.1.1.10.3.13.1.1.9ColumnemsProbeStatusProbeSerialNumberread-onlymandatoryA label indicating the type (Local[L] or Remote[R]) and Number of the probe. For example, the first local probe would be L1 and the third remote probe would be…
1.3.6.1.4.1.318.1.1.10.3.13.1.1.10ColumnemsProbeStatusProbeCommStatusread-onlymandatoryThe state of communications to the probe. commNeverDiscovered(1) indicates there has never been communications with this device. commsEstablished(2) indicates …
1.3.6.1.4.1.318.1.1.10.3.13.1.1.11ColumnemsProbeStatusProbeAlarmStatusread-onlymandatoryThe alarm status of the probe. This integer should be interpreted as a bit map, with each bit representing the presence or absence of the specific alarm condit…
1.3.6.1.4.1.318.1.1.10.3.13.1.1.12ColumnemsProbeStatusProbeMaxTempThreshread-onlymandatoryProbe maximum temperature threshold. Values are represented in whole number degrees. Units are displayed in the scale shown in the emsStatusSysTempUnits OID (C…
1.3.6.1.4.1.318.1.1.10.3.13.1.1.13ColumnemsProbeStatusProbeMinTempThreshread-onlymandatoryProbe minimum temperature threshold. Values are represented in whole number degrees. Units are displayed in the scale shown in the emsStatusSysTempUnits OID (C…
1.3.6.1.4.1.318.1.1.10.3.13.1.1.14ColumnemsProbeStatusProbeMaxHumidityThreshread-onlymandatoryProbe maximum humidity threshold. Values are represented in whole number percentage.
1.3.6.1.4.1.318.1.1.10.3.13.1.1.15ColumnemsProbeStatusProbeMinHumidityThreshread-onlymandatoryProbe minimum humidity threshold. Values are represented in whole number percentage.
1.3.6.1.4.1.318.1.1.10.3.14NodeemsInputContactStatus
1.3.6.1.4.1.318.1.1.10.3.14.1TableemsInputContactStatusTablenot-accessiblemandatoryAllows for access of individual input contacts. The number of entries is contained in the emsStatusInputContactCount OID.
1.3.6.1.4.1.318.1.1.10.3.14.1.1RowemsInputContactStatusEntrynot-accessiblemandatoryThe input contacts to access.
1.3.6.1.4.1.318.1.1.10.3.14.1.1.1ColumnemsInputContactStatusInputContactIndexread-onlymandatoryThe index to the input contact entry.
1.3.6.1.4.1.318.1.1.10.3.14.1.1.2ColumnemsInputContactStatusInputContactNameread-onlymandatoryThe name of the input contact.
1.3.6.1.4.1.318.1.1.10.3.14.1.1.3ColumnemsInputContactStatusInputContactStateread-onlymandatoryGetting this variable will return the state of the input contact. If the input contact is closed, the contactClosedEMS (1) value will be returned. If the input…
1.3.6.1.4.1.318.1.1.10.3.14.1.1.4ColumnemsInputContactStatusInputContactNormalStateread-onlymandatoryGetting this variable will return the normal state of the input contact. If the normal state is closed, the normallyClosedEMS (1) value will be returned. If th…
1.3.6.1.4.1.318.1.1.10.3.15NodeemsOutputRelayStatus
1.3.6.1.4.1.318.1.1.10.3.15.1TableemsOutputRelayStatusTablenot-accessiblemandatoryAllows for access of individual output relays. The number of entries is contained in the emsStatusOutputRelayCount OID.
1.3.6.1.4.1.318.1.1.10.3.15.1.1RowemsOutputRelayStatusEntrynot-accessiblemandatoryThe output relays to access.
1.3.6.1.4.1.318.1.1.10.3.15.1.1.1ColumnemsOutputRelayStatusOutputRelayIndexread-onlymandatoryThe index to the output relay entry.
1.3.6.1.4.1.318.1.1.10.3.15.1.1.2ColumnemsOutputRelayStatusOutputRelayNameread-onlymandatoryThe name of the output relay.
1.3.6.1.4.1.318.1.1.10.3.15.1.1.3ColumnemsOutputRelayStatusOutputRelayStateread-onlymandatoryGetting this variable will return the state of the output relay. If the output relay is closed, the relayClosedEMS (1) value will be returned. If the output re…
1.3.6.1.4.1.318.1.1.10.3.15.1.1.4ColumnemsOutputRelayStatusOutputRelayNormalStateread-onlymandatoryGetting this variable will return the normal state of the output relay. If the normal state is closed, the normallyClosedEMS (1) value will be returned. If the…
1.3.6.1.4.1.318.1.1.10.3.16NodeemsOutletStatus
1.3.6.1.4.1.318.1.1.10.3.16.1TableemsOutletStatusTablenot-accessiblemandatoryAllows for access of individual outlets. The number of entries is contained in the emsStatusOutletCount OID.
1.3.6.1.4.1.318.1.1.10.3.16.1.1RowemsOutletStatusEntrynot-accessiblemandatoryThe outlets to access.
1.3.6.1.4.1.318.1.1.10.3.16.1.1.1ColumnemsOutletStatusOutletIndexread-onlymandatoryThe index to the outlet entry.
1.3.6.1.4.1.318.1.1.10.3.16.1.1.2ColumnemsOutletStatusOutletNameread-onlymandatoryThe name of the outlet.
1.3.6.1.4.1.318.1.1.10.3.16.1.1.3ColumnemsOutletStatusOutletStateread-onlymandatoryGetting this variable will return the state of the outlet. If the outlet is on, the outletOnEMS (1) value will be returned. If the outlet is off, the outletOff…
1.3.6.1.4.1.318.1.1.10.3.16.1.1.4ColumnemsOutletStatusOutletNormalStateread-onlymandatoryGetting this variable will return the normal state of the outlet. If the normal state is on, the normallyOnEMS (1) value will be returned. If the normal state …
1.3.6.1.4.1.318.1.1.10.3.17NodeemsAlarmDeviceStatus
1.3.6.1.4.1.318.1.1.10.3.17.1TableemsAlarmDeviceStatusTablenot-accessiblemandatoryAllows for access of individual alarm devices. The number of entries is contained in the emsStatusAlarmDeviceCount OID.
1.3.6.1.4.1.318.1.1.10.3.17.1.1RowemsAlarmDeviceStatusEntrynot-accessiblemandatoryThe alarm devices to access.
1.3.6.1.4.1.318.1.1.10.3.17.1.1.1ColumnemsAlarmDeviceStatusDeviceIndexread-onlymandatoryThe index to the alarm device entry.
1.3.6.1.4.1.318.1.1.10.3.17.1.1.2ColumnemsAlarmDeviceStatusDeviceNameread-onlymandatoryThe name of the alarm device. This OID is provided for informational purposes only.
1.3.6.1.4.1.318.1.1.10.3.17.1.1.3ColumnemsAlarmDeviceStatusDeviceStateread-onlymandatoryGetting this variable will return the device state. If the device is active, the alarmDeviceOnEMS (1) value will be returned. If the device is inactive, the al…
1.3.6.1.4.1.318.1.1.10.3.18NodeemsSensorStatus
1.3.6.1.4.1.318.1.1.10.3.18.1TableemsSensorStatusTablenot-accessiblemandatoryAllows for access of individual sensors. The number of entries is contained in the emsStatusSensorCount OID.
1.3.6.1.4.1.318.1.1.10.3.18.1.1RowemsSensorStatusEntrynot-accessiblemandatoryThe sensors to access.
1.3.6.1.4.1.318.1.1.10.3.18.1.1.1ColumnemsSensorStatusSensorIndexread-onlymandatoryThe index to the sensor entry.
1.3.6.1.4.1.318.1.1.10.3.18.1.1.2ColumnemsSensorStatusSensorSystemNameread-onlymandatoryThe system name of the sensor. This describes the hardware system intent of this sensor.
1.3.6.1.4.1.318.1.1.10.3.18.1.1.3ColumnemsSensorStatusSensorNameread-onlymandatoryThe name of the sensor as given by the system user.
1.3.6.1.4.1.318.1.1.10.3.18.1.1.4ColumnemsSensorStatusSensorStateread-onlymandatoryGetting this variable will return the sensor state. If the sensor is faulted, the sensorFaultedEMS (1) value will be returned. If the sensor is not faulted, th…
1.3.6.1.4.1.318.1.1.10.3.18.1.1.5ColumnemsSensorStatusSensorNormalStateread-onlymandatoryGetting this variable will return the normal state of the sensor. If the normal state is closed, the normallyClosedEMS (1) value will be returned. If the norma…
1.3.6.1.4.1.318.1.1.10.3.18.1.1.6ColumnemsSensorStatusSensorAlarmDelayread-onlymandatoryThe delay (in seconds) after a sensor detects an alarm condition before the condition is reported.
1.3.6.1.4.1.318.1.1.10.3.19NodeemsInputStateSensorConfig
1.3.6.1.4.1.318.1.1.10.3.19.1TableemsSmokeSensorConfigTablenot-accessiblemandatoryAllows for the configuration of individual sensors.
1.3.6.1.4.1.318.1.1.10.3.19.1.1RowemsSmokeSensorConfigEntrynot-accessiblemandatoryThe sensors to configure.
1.3.6.1.4.1.318.1.1.10.3.19.1.1.1ColumnemsSmokeSensorConfigSensorIndexread-onlymandatoryThe index to the sensor entry.
1.3.6.1.4.1.318.1.1.10.3.19.1.1.2ColumnemsSmokeSensorConfigSensorNameread-writemandatoryThe user defined name of the smoke sensor.
1.3.6.1.4.1.318.1.1.10.3.19.1.1.3ColumnemsSmokeSensorConfigSensorLocationread-writemandatoryThe user defined location of the smoke sensor.
1.3.6.1.4.1.318.1.1.10.3.19.1.1.4ColumnemsSmokeSensorConfigSensorSeverityread-writemandatoryThe severity of the alarm that will be triggered when the smoke sensor is activated. The alarms can be critical(1), warning(2) or informational(3).
1.3.6.1.4.1.318.1.1.10.3.19.2TableemsVibrationSensorConfigTablenot-accessiblemandatoryAllows for the configuration of individual sensors.
1.3.6.1.4.1.318.1.1.10.3.19.2.1RowemsVibrationSensorConfigEntrynot-accessiblemandatoryThe sensors to configure.
1.3.6.1.4.1.318.1.1.10.3.19.2.1.1ColumnemsVibrationSensorConfigSensorIndexread-onlymandatoryThe index to the sensor entry.
1.3.6.1.4.1.318.1.1.10.3.19.2.1.2ColumnemsVibrationSensorConfigSensorNameread-writemandatoryThe user defined name of the vibration sensor.
1.3.6.1.4.1.318.1.1.10.3.19.2.1.3ColumnemsVibrationSensorConfigSensorLocationread-writemandatoryThe user defined location of the vibration sensor.
1.3.6.1.4.1.318.1.1.10.3.19.2.1.4ColumnemsVibrationSensorConfigSensorSeverityread-writemandatoryThe severity of the alarm that will be triggered when the vibration sensor is activated. The alarms can be critical(1), warning(2) or informational(3).
1.3.6.1.4.1.318.1.1.10.3.19.3TableemsFluidSensorConfigTablenot-accessiblemandatoryAllows for the configuration of individual sensors.
1.3.6.1.4.1.318.1.1.10.3.19.3.1RowemsFluidSensorConfigEntrynot-accessiblemandatoryThe sensors to configure.
1.3.6.1.4.1.318.1.1.10.3.19.3.1.1ColumnemsFluidSensorConfigSensorIndexread-onlymandatoryThe index to the sensor entry.
1.3.6.1.4.1.318.1.1.10.3.19.3.1.2ColumnemsFluidSensorConfigSensorNameread-writemandatoryThe user defined name of the fluid sensor.
1.3.6.1.4.1.318.1.1.10.3.19.3.1.3ColumnemsFluidSensorConfigSensorLocationread-writemandatoryThe user defined location of the fluid sensor.
1.3.6.1.4.1.318.1.1.10.3.19.3.1.4ColumnemsFluidSensorConfigSensorSeverityread-writemandatoryThe severity of the alarm that will be triggered when the fluid sensor is activated. The alarms can be critical(1), warning(2) or informational(3).
1.3.6.1.4.1.318.1.1.10.3.19.4TableemsDoorSensorConfigTablenot-accessiblemandatoryAllows for the configuration of individual sensors.
1.3.6.1.4.1.318.1.1.10.3.19.4.1RowemsDoorSensorConfigEntrynot-accessiblemandatoryThe sensors to configure.
1.3.6.1.4.1.318.1.1.10.3.19.4.1.1ColumnemsDoorSensorConfigSensorIndexread-onlymandatoryThe index to the sensor entry.
1.3.6.1.4.1.318.1.1.10.3.19.4.1.2ColumnemsDoorSensorConfigSensorNameread-writemandatoryThe user defined name of the door sensor.
1.3.6.1.4.1.318.1.1.10.3.19.4.1.3ColumnemsDoorSensorConfigSensorLocationread-writemandatoryThe user defined location of the door sensor.
1.3.6.1.4.1.318.1.1.10.3.19.4.1.4ColumnemsDoorSensorConfigSensorSeverityread-writemandatoryThe severity of the alarm that will be triggered when the door sensor is activated. The alarms can be critical(1), warning(2) or informational(3).
1.3.6.1.4.1.318.1.1.10.3.20NodeemsInputStateSensorStatus
1.3.6.1.4.1.318.1.1.10.3.20.1ScalaremsSmokeSensorStatusTableSizeread-onlymandatoryThe number of entries in the emsSmokeSensorStatusTable.
1.3.6.1.4.1.318.1.1.10.3.20.2TableemsSmokeSensorStatusTablenot-accessiblemandatoryAllows for the access of individual sensors.
1.3.6.1.4.1.318.1.1.10.3.20.2.1RowemsSmokeSensorStatusEntrynot-accessiblemandatoryThe sensor to access.
1.3.6.1.4.1.318.1.1.10.3.20.2.1.1ColumnemsSmokeSensorStatusSensorIndexread-onlymandatoryThe index to the sensor entry.
1.3.6.1.4.1.318.1.1.10.3.20.2.1.2ColumnemsSmokeSensorStatusSensorNameread-onlymandatoryThe user defined name of the smoke sensor.
1.3.6.1.4.1.318.1.1.10.3.20.2.1.3ColumnemsSmokeSensorStatusSensorLocationread-onlymandatoryThe user defined location of the smoke sensor.
1.3.6.1.4.1.318.1.1.10.3.20.2.1.4ColumnemsSmokeSensorStatusSensorStateread-onlymandatoryThe state of the smoke sensor. smokeDetected (1) indicates there is smoke. noSmoke (2) indicates there is no smoke. unknown (3) indicates the state is unknown.
1.3.6.1.4.1.318.1.1.10.3.20.2.1.5ColumnemsSmokeSensorStatusSensorSeverityread-onlymandatoryThe severity of the alarm that will be triggered when the smoke sensor is activated. The alarms can be critical(1), warning(2) or informational(3).
1.3.6.1.4.1.318.1.1.10.3.20.2.1.6ColumnemsSmokeSensorCommStatusread-onlymandatoryThe communication status of the smoke sensor.
1.3.6.1.4.1.318.1.1.10.3.20.3ScalaremsVibrationSensorStatusTableSizeread-onlymandatoryThe number of entries in the emsVibrationSensorStatusTable.
1.3.6.1.4.1.318.1.1.10.3.20.4TableemsVibrationSensorStatusTablenot-accessiblemandatoryAllows for the access of individual sensors.
1.3.6.1.4.1.318.1.1.10.3.20.4.1RowemsVibrationSensorStatusEntrynot-accessiblemandatoryThe sensor to access.
1.3.6.1.4.1.318.1.1.10.3.20.4.1.1ColumnemsVibrationSensorStatusSensorIndexread-onlymandatoryThe index to the sensor entry.
1.3.6.1.4.1.318.1.1.10.3.20.4.1.2ColumnemsVibrationSensorStatusSensorNameread-onlymandatoryThe user defined name of the vibration sensor.
1.3.6.1.4.1.318.1.1.10.3.20.4.1.3ColumnemsVibrationSensorStatusSensorLocationread-onlymandatoryThe user defined location of the vibration sensor.
1.3.6.1.4.1.318.1.1.10.3.20.4.1.4ColumnemsVibrationSensorStatusSensorStateread-onlymandatoryThe state of the vibration sensor. vibrationDetected (1) indicates there is vibration. noVibration (2) indicates there is no vibration. unknown (3) indicates t…
1.3.6.1.4.1.318.1.1.10.3.20.4.1.5ColumnemsVibrationSensorStatusSensorSeverityread-onlymandatoryThe severity of the alarm that will be triggered when the vibration sensor is activated. The alarms can be critical(1), warning(2) or informational(3).
1.3.6.1.4.1.318.1.1.10.3.20.4.1.6ColumnemsVibrationSensorCommStatusread-onlymandatoryThe communication status of the vibration sensor.
1.3.6.1.4.1.318.1.1.10.3.20.5ScalaremsFluidSensorStatusTableSizeread-onlymandatoryThe number of entries in the emsFluidSensorStatusTable.
1.3.6.1.4.1.318.1.1.10.3.20.6TableemsFluidSensorStatusTablenot-accessiblemandatoryAllows for the access of individual sensors.
1.3.6.1.4.1.318.1.1.10.3.20.6.1RowemsFluidSensorStatusEntrynot-accessiblemandatoryThe sensors to access.
1.3.6.1.4.1.318.1.1.10.3.20.6.1.1ColumnemsFluidSensorStatusSensorIndexread-onlymandatoryThe index to the sensor entry.
1.3.6.1.4.1.318.1.1.10.3.20.6.1.2ColumnemsFluidSensorStatusSensorNameread-onlymandatoryThe user defined name of the fluid sensor.
1.3.6.1.4.1.318.1.1.10.3.20.6.1.3ColumnemsFluidSensorStatusSensorLocationread-onlymandatoryThe user defined location of the fluid sensor.
1.3.6.1.4.1.318.1.1.10.3.20.6.1.4ColumnemsFluidSensorStatusSensorStateread-onlymandatoryThe state of the fluid sensor. fluidDetected (1) indicates there is fluid leak. noFluid (2) indicates there is no fluid leak. unknown (3) indicates the state i…
1.3.6.1.4.1.318.1.1.10.3.20.6.1.5ColumnemsFluidSensorStatusSensorSeverityread-onlymandatoryThe severity of the alarm that will be triggered when the fluid sensor is activated. The alarms can be critical(1), warning(2) or informational(3).
1.3.6.1.4.1.318.1.1.10.3.20.6.1.6ColumnemsFluidSensorCommStatusread-onlymandatoryThe communication status of the fluid sensor.
1.3.6.1.4.1.318.1.1.10.3.20.7ScalaremsDoorSensorStatusTableSizeread-onlymandatoryThe number of entries in the emsDoorSensorStatusTable.
1.3.6.1.4.1.318.1.1.10.3.20.8TableemsDoorSensorStatusTablenot-accessiblemandatoryAllows for the access of individual sensors.
1.3.6.1.4.1.318.1.1.10.3.20.8.1RowemsDoorSensorStatusEntrynot-accessiblemandatoryThe sensor to access.
1.3.6.1.4.1.318.1.1.10.3.20.8.1.1ColumnemsDoorSensorStatusSensorIndexread-onlymandatoryThe index to the sensor entry.
1.3.6.1.4.1.318.1.1.10.3.20.8.1.2ColumnemsDoorSensorStatusSensorNameread-onlymandatoryThe user defined name of the door sensor.
1.3.6.1.4.1.318.1.1.10.3.20.8.1.3ColumnemsDoorSensorStatusSensorLocationread-onlymandatoryThe user defined location of the door sensor.
1.3.6.1.4.1.318.1.1.10.3.20.8.1.4ColumnemsDoorSensorStatusSensorStateread-onlymandatoryThe state of the door sensor. open (1) indicates door open. closed (2) indicates door closed. unknown (3) indicates the state is unknown.
1.3.6.1.4.1.318.1.1.10.3.20.8.1.5ColumnemsDoorSensorStatusSensorSeverityread-onlymandatoryThe severity of the alarm that will be triggered when the door sensor is activated. The alarms can be critical(1), warning(2) or informational(3).
1.3.6.1.4.1.318.1.1.10.3.20.8.1.6ColumnemsDoorSensorCommStatusread-onlymandatoryThe communication status of the door sensor.
1.3.6.1.4.1.318.1.1.10.4NodemodEnvMgr
1.3.6.1.4.1.318.1.1.10.4.1NodememModules
1.3.6.1.4.1.318.1.1.10.4.1.1ScalarmemModulesStatusTableSizeread-onlymandatoryThe number of entries in the memModulesStatusTable.
1.3.6.1.4.1.318.1.1.10.4.1.2TablememModulesStatusTablenot-accessiblemandatoryAllows for getting status information from the modules attached to the system.
1.3.6.1.4.1.318.1.1.10.4.1.2.1RowmemModulesStatusEntrynot-accessiblemandatoryThe unit to get data from.
1.3.6.1.4.1.318.1.1.10.4.1.2.1.1ColumnmemModulesStatusModuleNumberread-onlymandatoryThe module number.
1.3.6.1.4.1.318.1.1.10.4.1.2.1.2ColumnmemModulesStatusModuleNameread-onlymandatoryThe module name.
1.3.6.1.4.1.318.1.1.10.4.1.2.1.3ColumnmemModulesStatusModuleLocationread-onlymandatoryThe location of the module.
1.3.6.1.4.1.318.1.1.10.4.1.2.1.4ColumnmemModulesStatusModelNumberread-onlymandatoryThe model number of the module.
1.3.6.1.4.1.318.1.1.10.4.1.2.1.5ColumnmemModulesStatusSerialNumberread-onlymandatoryThe serial number of the module.
1.3.6.1.4.1.318.1.1.10.4.1.2.1.6ColumnmemModulesStatusFirmwareRevread-onlymandatoryThe firmware revision of the module.
1.3.6.1.4.1.318.1.1.10.4.1.2.1.7ColumnmemModulesStatusHardwareRevread-onlymandatoryThe hardware revision.
1.3.6.1.4.1.318.1.1.10.4.1.3ScalarmemModulesConfigTableSizeread-onlymandatoryThe number of entries in the memModulesConfigTable.
1.3.6.1.4.1.318.1.1.10.4.1.4TablememModulesConfigTablenot-accessiblemandatoryAllows for getting status information from the modules attached to the system.
1.3.6.1.4.1.318.1.1.10.4.1.4.1RowmemModulesConfigEntrynot-accessiblemandatoryThe unit to get data from.
1.3.6.1.4.1.318.1.1.10.4.1.4.1.1ColumnmemModulesConfigModuleNumberread-onlymandatoryThe module number.
1.3.6.1.4.1.318.1.1.10.4.1.4.1.2ColumnmemModulesConfigModuleNameread-writemandatoryThe module name.
1.3.6.1.4.1.318.1.1.10.4.1.4.1.3ColumnmemModulesConfigModuleLocationread-writemandatoryThe location of the module.
1.3.6.1.4.1.318.1.1.10.4.2NodememSensors
1.3.6.1.4.1.318.1.1.10.4.2.1ScalarmemSensorsStatusSysTempUnitsread-onlymandatoryThe temperature scale used to display the temperature in the system, Celsius(1) or Fahrenheit(2). This setting is based on the system preferences configuration…
1.3.6.1.4.1.318.1.1.10.4.2.2ScalarmemSensorsStatusTableSizeread-onlymandatoryThe number of entries in the memSensorsStatusTable.
1.3.6.1.4.1.318.1.1.10.4.2.3TablememSensorsStatusTablenot-accessiblemandatoryAllows for getting sensor status information.
1.3.6.1.4.1.318.1.1.10.4.2.3.1RowmemSensorsStatusEntrynot-accessiblemandatoryThe unit to get data from.
1.3.6.1.4.1.318.1.1.10.4.2.3.1.1ColumnmemSensorsStatusModuleNumberread-onlymandatoryThe number of the module that the sensor is attached to.
1.3.6.1.4.1.318.1.1.10.4.2.3.1.2ColumnmemSensorsStatusSensorNumberread-onlymandatoryThe number of this sensor on the module.
1.3.6.1.4.1.318.1.1.10.4.2.3.1.3ColumnmemSensorsStatusSensorNameread-onlymandatoryThe sensor name.
1.3.6.1.4.1.318.1.1.10.4.2.3.1.4ColumnmemSensorsStatusSensorLocationread-onlymandatoryThe location of the sensor.
1.3.6.1.4.1.318.1.1.10.4.2.3.1.5ColumnmemSensorsTemperatureread-onlymandatoryThe sensor's current temperature reading. Units are displayed in the scale shown in the memSensorsStatusSysTempUnits OID (Celsius or Fahrenheit).
1.3.6.1.4.1.318.1.1.10.4.2.3.1.6ColumnmemSensorsHumidityread-onlymandatoryThe current humidity reading from the sensor.
1.3.6.1.4.1.318.1.1.10.4.2.3.1.7ColumnmemSensorsCommStatusread-onlymandatoryThe communications status of the sensor.
1.3.6.1.4.1.318.1.1.10.4.2.3.1.8ColumnmemSensorsAlarmStatusread-onlymandatoryThe alarm status of the sensor.
1.3.6.1.4.1.318.1.1.10.4.2.3.1.9ColumnmemSensorsTemperatureHighPrecread-onlymandatoryThe current temperature is displayed in tenths of degrees in the scale shown in the memSensorsStatusSysTempUnits OID (Celsius or Fahrenheit).
1.3.6.1.4.1.318.1.1.10.4.2.4ScalarmemSensorsConfigTableSizeread-onlymandatoryThe number of entries in the memSensorsConfigTable.
1.3.6.1.4.1.318.1.1.10.4.2.5TablememSensorsConfigTablenot-accessiblemandatoryAllows for getting configuration information from sensors attached to the system.
1.3.6.1.4.1.318.1.1.10.4.2.5.1RowmemSensorsConfigEntrynot-accessiblemandatoryThe unit to get data from.
1.3.6.1.4.1.318.1.1.10.4.2.5.1.1ColumnmemSensorsConfigModuleNumberread-onlymandatoryThe number of the module that the sensor is attached to.
1.3.6.1.4.1.318.1.1.10.4.2.5.1.2ColumnmemSensorsConfigSensorNumberread-onlymandatoryThe number of this sensor on the module.
1.3.6.1.4.1.318.1.1.10.4.2.5.1.3ColumnmemSensorsNameread-writemandatoryA descriptive name for the sensor.
1.3.6.1.4.1.318.1.1.10.4.2.5.1.4ColumnmemSensorsLocationread-writemandatoryThe location of the sensor.
1.3.6.1.4.1.318.1.1.10.4.2.5.1.5ColumnmemSensorsAlarmGenerationread-writemandatoryEnable or disable alarm generation on this sensor.
1.3.6.1.4.1.318.1.1.10.4.2.5.1.6ColumnmemSensorsTempMaxThreshread-writemandatoryThe temperature at which the MEM will generate a maximum temperature threshold violation alarm on this sensor. The temperature scale is based on the memSensors…
1.3.6.1.4.1.318.1.1.10.4.2.5.1.7ColumnmemSensorsTempHighThreshread-writemandatoryThe temperature at which the MEM will generate a high temperature threshold violation alarm on this sensor. The temperature scale is based on the memSensorsSta…
1.3.6.1.4.1.318.1.1.10.4.2.5.1.8ColumnmemSensorsTempLowThreshread-writemandatoryThe temperature at which the MEM will generate a low temperature threshold violation alarm on this sensor. The temperature scale is based on the memSensorsStat…
1.3.6.1.4.1.318.1.1.10.4.2.5.1.9ColumnmemSensorsTempMinThreshread-writemandatoryThe temperature at which the MEM will generate a minimum temperature threshold violation alarm on this sensor. The temperature scale is based on the memSensors…
1.3.6.1.4.1.318.1.1.10.4.2.5.1.10ColumnmemSensorsTempThreshHysteresisread-writemandatoryThe change in temperature required to cause a temperature alarm to change from an active to an inactive state. The temperature scale is based on the memSensors…
1.3.6.1.4.1.318.1.1.10.4.2.5.1.11ColumnmemSensorsTempShortDecRateThreshValueread-writemandatoryThe value of the temperature short-term decreasing rate time that will cause an alarm to be generated. The temperature scale is based on the memSensorsStatusSy…
1.3.6.1.4.1.318.1.1.10.4.2.5.1.12ColumnmemSensorsTempShortDecRateThreshTimeread-writemandatoryThe time over which the temperature may not decrease beyond the value specified by the temperature short-term decreasing rate threshold value.
1.3.6.1.4.1.318.1.1.10.4.2.5.1.13ColumnmemSensorsTempShortIncRateThreshValueread-writemandatoryThe value of the temperature short-term increasing rate time that will cause an alarm to be generated. The temperature scale is based on the memSensorsStatusSy…
1.3.6.1.4.1.318.1.1.10.4.2.5.1.14ColumnmemSensorsTempShortIncRateThreshTimeread-writemandatoryThe time over which the temperature may not increase beyond the value specified by the temperature short-term increasing rate threshold value.
1.3.6.1.4.1.318.1.1.10.4.2.5.1.15ColumnmemSensorsTempLongDecRateThreshValueread-writemandatoryThe value of the temperature long-term decreasing rate time that will cause an alarm to be generated. The temperature scale is based on the memSensorsStatusSys…
1.3.6.1.4.1.318.1.1.10.4.2.5.1.16ColumnmemSensorsTempLongDecRateThreshTimeread-writemandatoryThe time over which the temperature may not decrease beyond the value specified by the temperature long-term decreasing rate threshold value.
1.3.6.1.4.1.318.1.1.10.4.2.5.1.17ColumnmemSensorsTempLongIncRateThreshValueread-writemandatoryThe value of the temperature long-term increasing rate time that will cause an alarm to be generated. The temperature scale is based on the memSensorsStatusSys…
1.3.6.1.4.1.318.1.1.10.4.2.5.1.18ColumnmemSensorsTempLongIncRateThreshTimeread-writemandatoryThe time over which the temperature may not increase beyond the value specified by the temperature long-term increasing rate threshold value.
1.3.6.1.4.1.318.1.1.10.4.2.5.1.19ColumnmemSensorsHumidityMaxThreshread-writemandatoryThe humidity at which the maximum humidity threshold alarm will be generated.
1.3.6.1.4.1.318.1.1.10.4.2.5.1.20ColumnmemSensorsHumidityHighThreshread-writemandatoryThe humidity at which the high humidity threshold alarm will be generated.
1.3.6.1.4.1.318.1.1.10.4.2.5.1.21ColumnmemSensorsHumidityLowThreshread-writemandatoryThe humidity at which the low humidity threshold alarm will be generated.
1.3.6.1.4.1.318.1.1.10.4.2.5.1.22ColumnmemSensorsHumidityMinThreshread-writemandatoryThe humidity at which the minimum humidity threshold alarm will be generated.
1.3.6.1.4.1.318.1.1.10.4.2.5.1.23ColumnmemSensorsHumidityThreshHysteresisread-writemandatoryThe change in humidity required to cause an active humidity alarm to change to the inactive state.
1.3.6.1.4.1.318.1.1.10.4.3NodememInputs
1.3.6.1.4.1.318.1.1.10.4.3.1ScalarmemInputsStatusTableSizeread-onlymandatoryThe number of entries in the memInputsStatusTable.
1.3.6.1.4.1.318.1.1.10.4.3.2TablememInputsStatusTablenot-accessiblemandatoryAllows for getting input status information.
1.3.6.1.4.1.318.1.1.10.4.3.2.1RowmemInputsStatusEntrynot-accessiblemandatoryThe unit to get data from.
1.3.6.1.4.1.318.1.1.10.4.3.2.1.1ColumnmemInputsStatusModuleNumberread-onlymandatoryThe number of the module that the input is attached to.
1.3.6.1.4.1.318.1.1.10.4.3.2.1.2ColumnmemInputsStatusInputNumberread-onlymandatoryThe number of this input on the module.
1.3.6.1.4.1.318.1.1.10.4.3.2.1.3ColumnmemInputsStatusInputNameread-onlymandatoryThe input name.
1.3.6.1.4.1.318.1.1.10.4.3.2.1.4ColumnmemInputsStatusInputLocationread-onlymandatoryThe location of the input.
1.3.6.1.4.1.318.1.1.10.4.3.2.1.5ColumnmemInputsStatusCurrentStateread-onlymandatoryThe current state of the input. This OID will return inputStateNotAplicable(4) for analog input types.
1.3.6.1.4.1.318.1.1.10.4.3.2.1.6ColumnmemInputsStatusCurrentAnalogValueread-onlymandatoryThe current analog value of the input in the units defined by the user.
1.3.6.1.4.1.318.1.1.10.4.3.2.1.7ColumnmemInputsStatusAlarmStatusread-onlymandatoryThe alarm status of the input.
1.3.6.1.4.1.318.1.1.10.4.3.2.1.8ColumnmemInputsCommStatusread-onlymandatoryThe communications status of the input. This OID is only supported by NBRK0200.
1.3.6.1.4.1.318.1.1.10.4.3.3ScalarmemInputsConfigTableSizeread-onlymandatoryThe number of entries in the memInputsConfigTable.
1.3.6.1.4.1.318.1.1.10.4.3.4TablememInputsConfigTablenot-accessiblemandatoryAllows for getting input configuration information.
1.3.6.1.4.1.318.1.1.10.4.3.4.1RowmemInputsConfigEntrynot-accessiblemandatoryThe unit to get data from.
1.3.6.1.4.1.318.1.1.10.4.3.4.1.1ColumnmemInputsConfigModuleNumberread-onlymandatoryThe number of the module that the input is attached to.
1.3.6.1.4.1.318.1.1.10.4.3.4.1.2ColumnmemInputsConfigInputNumberread-onlymandatoryThe number of this input on the module.
1.3.6.1.4.1.318.1.1.10.4.3.4.1.3ColumnmemInputNameread-writemandatoryThe name of the input.
1.3.6.1.4.1.318.1.1.10.4.3.4.1.4ColumnmemInputLocationread-writemandatoryThe location of the input.
1.3.6.1.4.1.318.1.1.10.4.3.4.1.5ColumnmemInputTyperead-writemandatoryThe type of input this contact will take.
1.3.6.1.4.1.318.1.1.10.4.3.4.1.6ColumnmemInputAlarmGenerationread-writemandatoryEnable or disable alarm generation on this input.
1.3.6.1.4.1.318.1.1.10.4.3.4.1.7ColumnmemInputNormalStateread-writemandatoryDefines the normal (no alarm) state of the input.
1.3.6.1.4.1.318.1.1.10.4.3.4.1.8ColumnmemInputAbnormalSeverityread-writemandatoryDefines the severity of the event that is associated with the abnormal state of the input. This OID will return inputSeverityNotApplicable(4) for analog input …
1.3.6.1.4.1.318.1.1.10.4.3.4.1.9ColumnmemInputNumberCalibrationPointsread-writemandatoryThe number of calibration points that are required for this input.
1.3.6.1.4.1.318.1.1.10.4.3.4.1.10ColumnmemInputAnalogCalibrationPoint1read-writemandatoryThe electrical value that the input sensor will measure at the first calibration point. This OID is relevant only for inputs configured as analog type (ma or V…
1.3.6.1.4.1.318.1.1.10.4.3.4.1.11ColumnmemInputAnalogCalibrationPoint2read-writemandatoryThe electrical value that the input sensor will measure at the second calibration point. This OID is relevant only for inputs configured as analog type (ma or …
1.3.6.1.4.1.318.1.1.10.4.3.4.1.12ColumnmemInputAnalogCalibrationPoint3read-writemandatoryThe electrical value that the input sensor will measure at the third calibration point. This OID is relevant only for inputs configured as analog type (ma or V…
1.3.6.1.4.1.318.1.1.10.4.3.4.1.13ColumnmemInputAnalogCalibrationPoint4read-writemandatoryThe electrical value that the input sensor will measure at the fourth calibration point. This OID is relevant only for inputs configured as analog type (ma or …
1.3.6.1.4.1.318.1.1.10.4.3.4.1.14ColumnmemInputAnalogCalibrationPoint5read-writemandatoryThe electrical value that the input sensor will measure at the fifth calibration point. This OID is relevant only for inputs configured as analog type (ma or V…
1.3.6.1.4.1.318.1.1.10.4.3.4.1.15ColumnmemInputAnalogCalibrationPoint1Valueread-writemandatoryThe value of the input, in units of measure defined by the user, that corresponds to the current setting at the first calibration point.
1.3.6.1.4.1.318.1.1.10.4.3.4.1.16ColumnmemInputAnalogCalibrationPoint2Valueread-writemandatoryThe value of the input, in units of measure defined by the user, that corresponds to the current setting at the second calibration point.
1.3.6.1.4.1.318.1.1.10.4.3.4.1.17ColumnmemInputAnalogCalibrationPoint3Valueread-writemandatoryThe value of the input, in units of measure defined by the user, that corresponds to the current setting at the third calibration point.
1.3.6.1.4.1.318.1.1.10.4.3.4.1.18ColumnmemInputAnalogCalibrationPoint4Valueread-writemandatoryThe value of the input, in units of measure defined by the user, that corresponds to the current setting at the fourth calibration point.
1.3.6.1.4.1.318.1.1.10.4.3.4.1.19ColumnmemInputAnalogCalibrationPoint5Valueread-writemandatoryThe value of the input, in units of measure defined by the user, that corresponds to the current setting at the fifth calibration point.
1.3.6.1.4.1.318.1.1.10.4.3.4.1.20ColumnmemInputAnalogMeasurementUnitsread-writemandatoryThe units of measure to be used for this input.
1.3.6.1.4.1.318.1.1.10.4.3.4.1.21ColumnmemInputAnalogMaxThreshread-writemandatoryThe input value at which a maximum threshold violation alarm will be generated on this input.
1.3.6.1.4.1.318.1.1.10.4.3.4.1.22ColumnmemInputAnalogHighThreshread-writemandatoryThe input value at which a high threshold violation alarm will be generated on this input.
1.3.6.1.4.1.318.1.1.10.4.3.4.1.23ColumnmemInputAnalogLowThreshread-writemandatoryThe input value at which a low threshold violation alarm will be generated on this input.
1.3.6.1.4.1.318.1.1.10.4.3.4.1.24ColumnmemInputAnalogMinThreshread-writemandatoryThe input value at which a minimum threshold violation alarm will be generated on this input.
1.3.6.1.4.1.318.1.1.10.4.3.4.1.25ColumnmemInputAnalogThreshHysteresisread-writemandatoryThe change in value required to cause an alarm on this input to change from active to inactive.
1.3.6.1.4.1.318.1.1.10.4.4NodememOutputs
1.3.6.1.4.1.318.1.1.10.4.4.1ScalarmemOutputStatusTableSizeread-onlymandatoryThe number of entries in the memOutputStatusTable.
1.3.6.1.4.1.318.1.1.10.4.4.2TablememOutputStatusTablenot-accessiblemandatoryAllows for getting output status information.
1.3.6.1.4.1.318.1.1.10.4.4.2.1RowmemOutputStatusEntrynot-accessiblemandatoryThe unit to get data from.
1.3.6.1.4.1.318.1.1.10.4.4.2.1.1ColumnmemOutputStatusModuleNumberread-onlymandatoryThe number of the module that the output is attached to.
1.3.6.1.4.1.318.1.1.10.4.4.2.1.2ColumnmemOutputStatusOutputNumberread-onlymandatoryThe number of this output on the module.
1.3.6.1.4.1.318.1.1.10.4.4.2.1.3ColumnmemOutputStatusOutputNameread-onlymandatoryThe output name.
1.3.6.1.4.1.318.1.1.10.4.4.2.1.4ColumnmemOutputStatusOutputLocationread-onlymandatoryThe location of the output.
1.3.6.1.4.1.318.1.1.10.4.4.2.1.5ColumnmemOutputStatusCurrentStateread-onlymandatoryThe state of the output.
1.3.6.1.4.1.318.1.1.10.4.4.2.1.6ColumnmemOutputStatusAlarmStateread-onlymandatoryThe alarm state of the output.
1.3.6.1.4.1.318.1.1.10.4.4.3ScalarmemOutputConfigTableSizeread-onlymandatoryThe number of entries in the memOutputConfigTable.
1.3.6.1.4.1.318.1.1.10.4.4.4TablememOutputConfigTablenot-accessiblemandatoryAllows for getting output configuration information.
1.3.6.1.4.1.318.1.1.10.4.4.4.1RowmemOutputConfigEntrynot-accessiblemandatoryThe unit to get data from.
1.3.6.1.4.1.318.1.1.10.4.4.4.1.1ColumnmemOutputConfigModuleNumberread-onlymandatoryThe number of the module that the output is attached to.
1.3.6.1.4.1.318.1.1.10.4.4.4.1.2ColumnmemOutputConfigOutputNumberread-onlymandatoryThe number of this output on the module.
1.3.6.1.4.1.318.1.1.10.4.4.4.1.3ColumnmemOutputNameread-writemandatoryThe name of the output.
1.3.6.1.4.1.318.1.1.10.4.4.4.1.4ColumnmemOutputLocationread-writemandatoryThe location of the output.
1.3.6.1.4.1.318.1.1.10.4.4.4.1.5ColumnmemOutputNormalStateread-writemandatoryThe state of the output that will not generate an alarm.
1.3.6.1.4.1.318.1.1.10.4.4.4.1.6ColumnmemOutputActionread-writemandatoryManual control actions for the output. SNMP get command will return the state of the output, SNMP set of this OID controls the output.
1.3.6.1.4.1.318.1.1.10.4.5NodememOutlets
1.3.6.1.4.1.318.1.1.10.4.5.1ScalarmemOutletStatusTableSizeread-onlymandatoryThe number of entries in the memOutletStatusTable.
1.3.6.1.4.1.318.1.1.10.4.5.2TablememOutletStatusTablenot-accessiblemandatoryAllows for getting outlet status information.
1.3.6.1.4.1.318.1.1.10.4.5.2.1RowmemOutletStatusEntrynot-accessiblemandatoryThe unit to get data from.
1.3.6.1.4.1.318.1.1.10.4.5.2.1.1ColumnmemOutletStatusModuleNumberread-onlymandatoryThe number of the module that the outlet is attached to.
1.3.6.1.4.1.318.1.1.10.4.5.2.1.2ColumnmemOutletStatusOutletNumberread-onlymandatoryThe number of this outlet on the module.
1.3.6.1.4.1.318.1.1.10.4.5.2.1.3ColumnmemOutletStatusOutletNameread-onlymandatoryThe outlet name.
1.3.6.1.4.1.318.1.1.10.4.5.2.1.4ColumnmemOutletStatusOutletLocationread-onlymandatoryThe location of the outlet.
1.3.6.1.4.1.318.1.1.10.4.5.2.1.5ColumnmemOutletStatusCurrentStateread-onlymandatoryThe state of the outlet.
1.3.6.1.4.1.318.1.1.10.4.5.2.1.6ColumnmemOutletStatusAlarmStateread-onlymandatoryThe alarm state of the outlet.
1.3.6.1.4.1.318.1.1.10.4.5.3ScalarmemOutletConfigTableSizeread-onlymandatoryThe number of entries in the memOutletConfigTable.
1.3.6.1.4.1.318.1.1.10.4.5.4TablememOutletConfigTablenot-accessiblemandatoryAllows for getting outlet configuration information.
1.3.6.1.4.1.318.1.1.10.4.5.4.1RowmemOutletConfigEntrynot-accessiblemandatoryThe unit to get data from.
1.3.6.1.4.1.318.1.1.10.4.5.4.1.1ColumnmemOutletConfigModuleNumberread-onlymandatoryThe number of the module that the Outlet is attached to.
1.3.6.1.4.1.318.1.1.10.4.5.4.1.2ColumnmemOutletConfigOutletNumberread-onlymandatoryThe number of this Outlet on the module.
1.3.6.1.4.1.318.1.1.10.4.5.4.1.3ColumnmemOutletNameread-writemandatoryThe name of the Outlet.
1.3.6.1.4.1.318.1.1.10.4.5.4.1.4ColumnmemOutletLocationread-writemandatoryThe location of the Outlet.
1.3.6.1.4.1.318.1.1.10.4.5.4.1.5ColumnmemOutletNormalStateread-writemandatoryThe state of the Outlet that will not generate an alarm.
1.3.6.1.4.1.318.1.1.10.4.5.4.1.6ColumnmemOutletActionread-writemandatoryManual control actions for the Outlet. Get displays state of outlet, set controls outlet.
1.3.6.1.4.1.318.1.1.10.4.6NodememBeacons
1.3.6.1.4.1.318.1.1.10.4.6.1ScalarmemBeaconStatusTableSizeread-onlymandatoryThe number of entries in the memBeaconStatusTable.
1.3.6.1.4.1.318.1.1.10.4.6.2TablememBeaconStatusTablenot-accessiblemandatoryAllows for getting beacon status information.
1.3.6.1.4.1.318.1.1.10.4.6.2.1RowmemBeaconStatusEntrynot-accessiblemandatoryThe unit to get data from.
1.3.6.1.4.1.318.1.1.10.4.6.2.1.1ColumnmemBeaconStatusModuleNumberread-onlymandatoryThe number of the module that the beacon is attached to.
1.3.6.1.4.1.318.1.1.10.4.6.2.1.2ColumnmemBeaconStatusBeaconNumberread-onlymandatoryThe number of this beacon on the module.
1.3.6.1.4.1.318.1.1.10.4.6.2.1.3ColumnmemBeaconStatusBeaconNameread-onlymandatoryThe beacon name.
1.3.6.1.4.1.318.1.1.10.4.6.2.1.4ColumnmemBeaconStatusBeaconLocationread-onlymandatoryThe location of the beacon.
1.3.6.1.4.1.318.1.1.10.4.6.2.1.5ColumnmemBeaconStatusCurrentStateread-onlymandatoryThe state of the beacon.
1.3.6.1.4.1.318.1.1.10.4.6.2.1.6ColumnmemBeaconStatusAlarmStateread-onlymandatoryThe alarm state of the beacon.
1.3.6.1.4.1.318.1.1.10.4.6.3ScalarmemBeaconConfigTableSizeread-onlymandatoryThe number of entries in the memBeaconConfigTable.
1.3.6.1.4.1.318.1.1.10.4.6.4TablememBeaconConfigTablenot-accessiblemandatoryAllows for getting beacon configuration information.
1.3.6.1.4.1.318.1.1.10.4.6.4.1RowmemBeaconConfigEntrynot-accessiblemandatoryThe unit to get data from.
1.3.6.1.4.1.318.1.1.10.4.6.4.1.1ColumnmemBeaconConfigModuleNumberread-onlymandatoryThe number of the module that the beacon is attached to.
1.3.6.1.4.1.318.1.1.10.4.6.4.1.2ColumnmemBeaconConfigBeaconNumberread-onlymandatoryThe number of this beacon on the module.
1.3.6.1.4.1.318.1.1.10.4.6.4.1.3ColumnmemBeaconConfigNameread-writemandatoryThe name of the beacon.
1.3.6.1.4.1.318.1.1.10.4.6.4.1.4ColumnmemBeaconConfigLocationread-writemandatoryThe location of the beacon.
1.3.6.1.4.1.318.1.1.10.4.6.4.1.5ColumnmemBeaconActionread-writemandatoryControl action (on/off) for the beacon. Setting this OID will turn the beacon on/off. Getting this OID will respond with the current state.
1.3.6.1.4.1.318.1.1.10.4.7NodememInputStateSensors
1.3.6.1.4.1.318.1.1.10.4.7.1ScalarmemSmokeSensorStatusTableSizeread-onlymandatoryThe number of entries in the memSmokeSensorStatusTable.
1.3.6.1.4.1.318.1.1.10.4.7.2TablememSmokeSensorStatusTablenot-accessiblemandatoryAllows for the access of individual sensors.
1.3.6.1.4.1.318.1.1.10.4.7.2.1RowmemSmokeSensorStatusEntrynot-accessiblemandatoryThe sensor to access.
1.3.6.1.4.1.318.1.1.10.4.7.2.1.1ColumnmemSmokeSensorStatusModuleIndexread-onlymandatoryThe index to the module entry.
1.3.6.1.4.1.318.1.1.10.4.7.2.1.2ColumnmemSmokeSensorStatusSensorIndexread-onlymandatoryThe index to the sensor entry.
1.3.6.1.4.1.318.1.1.10.4.7.2.1.3ColumnmemSmokeSensorStatusSensorNameread-onlymandatoryThe user defined name of the smoke sensor.
1.3.6.1.4.1.318.1.1.10.4.7.2.1.4ColumnmemSmokeSensorStatusSensorLocationread-onlymandatoryThe user defined location of the smoke sensor.
1.3.6.1.4.1.318.1.1.10.4.7.2.1.5ColumnmemSmokeSensorStatusSensorStateread-onlymandatoryThe state of the smoke sensor. smokeDetected (1) indicates there is smoke. noSmoke (2) indicates there is no smoke. unknown (3) indicates the state is unknown.
1.3.6.1.4.1.318.1.1.10.4.7.2.1.6ColumnmemSmokeSensorStatusSensorSeverityread-onlymandatoryThe severity of the alarm that will be triggered when the smoke sensor is activated. The alarms can be critical(1), warning(2) or informational(3).
1.3.6.1.4.1.318.1.1.10.4.7.2.1.7ColumnmemSmokeStatusAlarmStatusread-onlymandatoryThe alarm status of the smoke sensor.
1.3.6.1.4.1.318.1.1.10.4.7.2.1.8ColumnmemSmokeSensorCommStatusread-onlymandatoryThe communication status of the smoke sensor.
1.3.6.1.4.1.318.1.1.10.4.7.3ScalarmemVibrationSensorStatusTableSizeread-onlymandatoryThe number of entries in the memVibrationSensorStatusTable.
1.3.6.1.4.1.318.1.1.10.4.7.4TablememVibrationSensorStatusTablenot-accessiblemandatoryAllows for the access of individual sensors.
1.3.6.1.4.1.318.1.1.10.4.7.4.1RowmemVibrationSensorStatusEntrynot-accessiblemandatoryThe sensors to access.
1.3.6.1.4.1.318.1.1.10.4.7.4.1.1ColumnmemVibrationSensorStatusModuleIndexread-onlymandatoryThe index to the sensor module entry.
1.3.6.1.4.1.318.1.1.10.4.7.4.1.2ColumnmemVibrationSensorStatusSensorIndexread-onlymandatoryThe index to the sensor entry.
1.3.6.1.4.1.318.1.1.10.4.7.4.1.3ColumnmemVibrationSensorStatusSensorNameread-onlymandatoryThe user defined name of the vibration sensor.
1.3.6.1.4.1.318.1.1.10.4.7.4.1.4ColumnmemVibrationSensorStatusSensorLocationread-onlymandatoryThe user defined location of the vibration sensor.
1.3.6.1.4.1.318.1.1.10.4.7.4.1.5ColumnmemVibrationSensorStatusSensorStateread-onlymandatoryThe state of the vibration sensor. vibrationDetected (1) indicates there is vibration. noVibration (2) indicates there is no vibration. unknown (3) indicates t…
1.3.6.1.4.1.318.1.1.10.4.7.4.1.6ColumnmemVibrationSensorStatusSensorSeverityread-onlymandatoryThe severity of the alarm that will be triggered when the vibration sensor is activated. The alarms can be critical(1), warning(2) or informational(3).
1.3.6.1.4.1.318.1.1.10.4.7.4.1.7ColumnmemVibrationStatusAlarmStatusread-onlymandatoryThe alarm status of the vibration sensor.
1.3.6.1.4.1.318.1.1.10.4.7.4.1.8ColumnmemVibrationSensorCommStatusread-onlymandatoryThe communication status of the vibration sensor.
1.3.6.1.4.1.318.1.1.10.4.7.5ScalarmemFluidSensorStatusTableSizeread-onlymandatoryThe number of entries in the memFluidSensorStatusTable.
1.3.6.1.4.1.318.1.1.10.4.7.6TablememFluidSensorStatusTablenot-accessiblemandatoryAllows for access of individual sensors.
1.3.6.1.4.1.318.1.1.10.4.7.6.1RowmemFluidSensorStatusEntrynot-accessiblemandatoryThe sensor to access.
1.3.6.1.4.1.318.1.1.10.4.7.6.1.1ColumnmemFluidSensorStatusModuleIndexread-onlymandatoryThe index to the sensor module entry.
1.3.6.1.4.1.318.1.1.10.4.7.6.1.2ColumnmemFluidSensorStatusSensorIndexread-onlymandatoryThe index to the sensor entry.
1.3.6.1.4.1.318.1.1.10.4.7.6.1.3ColumnmemFluidSensorStatusSensorNameread-onlymandatoryThe user defined name of the fluid sensor.
1.3.6.1.4.1.318.1.1.10.4.7.6.1.4ColumnmemFluidSensorStatusSensorLocationread-onlymandatoryThe user defined location of the fluid sensor.
1.3.6.1.4.1.318.1.1.10.4.7.6.1.5ColumnmemFluidSensorStatusSensorStateread-onlymandatoryThe state of the fluid sensor. fluidDetected (1) indicates there is fluid leak. noFluid (2) indicates there is no fluid leak. unknown (3) indicates the state i…
1.3.6.1.4.1.318.1.1.10.4.7.6.1.6ColumnmemFluidSensorStatusSensorSeverityread-onlymandatoryThe severity of the alarm that will be triggered when the fluid sensor is activated. The alarms can be critical(1), warning(2) or informational(3).
1.3.6.1.4.1.318.1.1.10.4.7.6.1.7ColumnmemFluidStatusAlarmStatusread-onlymandatoryThe alarm status of the fluid sensor.
1.3.6.1.4.1.318.1.1.10.4.7.6.1.8ColumnmemFluidSensorCommStatusread-onlymandatoryThe communication status of the fluid sensor.
1.3.6.1.4.1.318.1.1.10.4.7.7ScalarmemDoorSensorStatusTableSizeread-onlymandatoryThe number of entries in the memDoorSensorStatusTable.
1.3.6.1.4.1.318.1.1.10.4.7.8TablememDoorSensorStatusTablenot-accessiblemandatoryAllows for the access of individual sensors.
1.3.6.1.4.1.318.1.1.10.4.7.8.1RowmemDoorSensorStatusEntrynot-accessiblemandatoryThe sensor to access.
1.3.6.1.4.1.318.1.1.10.4.7.8.1.1ColumnmemDoorSensorStatusModuleIndexread-onlymandatoryThe index to the sensor module entry.
1.3.6.1.4.1.318.1.1.10.4.7.8.1.2ColumnmemDoorSensorStatusSensorIndexread-onlymandatoryThe index to the sensor entry.
1.3.6.1.4.1.318.1.1.10.4.7.8.1.3ColumnmemDoorSensorStatusSensorNameread-onlymandatoryThe user defined name of the door sensor.
1.3.6.1.4.1.318.1.1.10.4.7.8.1.4ColumnmemDoorSensorStatusSensorLocationread-onlymandatoryThe user defined location of the door sensor.
1.3.6.1.4.1.318.1.1.10.4.7.8.1.5ColumnmemDoorSensorStatusSensorStateread-onlymandatoryThe state of the door sensor. open (1) indicates door open. closed (2) indicates door closed. unknown (3) indicates the state is unknown.
1.3.6.1.4.1.318.1.1.10.4.7.8.1.6ColumnmemDoorSensorStatusSensorSeverityread-onlymandatoryThe severity of the alarm that will be triggered when the door sensor is activated. The alarms can be critical(1), warning(2) or informational(3).
1.3.6.1.4.1.318.1.1.10.4.7.8.1.7ColumnmemDoorStatusAlarmStatusread-onlymandatoryThe alarm status of the door sensor.
1.3.6.1.4.1.318.1.1.10.4.7.8.1.8ColumnmemDoorSensorCommStatusread-onlymandatoryThe communication status of the door sensor.
1.3.6.1.4.1.318.1.1.10.4.7.9TablememSmokeSensorConfigTablenot-accessiblemandatoryAllows for the configuration of individual sensors.
1.3.6.1.4.1.318.1.1.10.4.7.9.1RowmemSmokeSensorConfigEntrynot-accessiblemandatoryThe sensors to configure.
1.3.6.1.4.1.318.1.1.10.4.7.9.1.1ColumnmemSmokeSensorConfigSensorModuleIndexread-onlymandatoryThe index to the sensor module entry.
1.3.6.1.4.1.318.1.1.10.4.7.9.1.2ColumnmemSmokeSensorConfigSensorIndexread-onlymandatoryThe index to the sensor entry.
1.3.6.1.4.1.318.1.1.10.4.7.9.1.3ColumnmemSmokeSensorConfigSensorNameread-writemandatoryThe user defined name of the smoke sensor.
1.3.6.1.4.1.318.1.1.10.4.7.9.1.4ColumnmemSmokeSensorConfigSensorLocationread-writemandatoryThe user defined location of the smoke sensor.
1.3.6.1.4.1.318.1.1.10.4.7.9.1.5ColumnmemSmokeSensorConfigSensorSeverityread-writemandatoryThe severity of the alarm that will be triggered when the smoke sensor is activated. The alarms can be critical(1), warning(2) or informational(3).
1.3.6.1.4.1.318.1.1.10.4.7.9.1.6ColumnmemSmokeSensorConfigAlarmGenerationread-writemandatoryEnable or disable alarm generation on this input.
1.3.6.1.4.1.318.1.1.10.4.7.10TablememVibrationSensorConfigTablenot-accessiblemandatoryAllows for the configuration of individual sensors.
1.3.6.1.4.1.318.1.1.10.4.7.10.1RowmemVibrationSensorConfigEntrynot-accessiblemandatoryThe sensor to configure.
1.3.6.1.4.1.318.1.1.10.4.7.10.1.1ColumnmemVibrationSensorModuleConfigIndexread-onlymandatoryThe index to the sensor module entry.
1.3.6.1.4.1.318.1.1.10.4.7.10.1.2ColumnmemVibrationSensorConfigSensorIndexread-onlymandatoryThe index to the sensor entry.
1.3.6.1.4.1.318.1.1.10.4.7.10.1.3ColumnmemVibrationSensorConfigSensorNameread-writemandatoryThe user defined name of the vibration sensor.
1.3.6.1.4.1.318.1.1.10.4.7.10.1.4ColumnmemVibrationSensorConfigSensorLocationread-writemandatoryThe user defined location of the vibration sensor.
1.3.6.1.4.1.318.1.1.10.4.7.10.1.5ColumnmemVibrationSensorConfigSensorSeverityread-writemandatoryThe severity of the alarm that will be triggered when the vibration sensor is activated. The alarms can be critical(1), warning(2) or informational(3).
1.3.6.1.4.1.318.1.1.10.4.7.10.1.6ColumnmemVibrationSensorConfigAlarmGenerationread-writemandatoryEnable or disable alarm generation on this input.
1.3.6.1.4.1.318.1.1.10.4.7.11TablememFluidSensorConfigTablenot-accessiblemandatoryAllows for the configuration of individual sensors.
1.3.6.1.4.1.318.1.1.10.4.7.11.1RowmemFluidSensorConfigEntrynot-accessiblemandatoryThe sensor to configure.
1.3.6.1.4.1.318.1.1.10.4.7.11.1.1ColumnmemFluidSensorModuleConfigIndexread-onlymandatoryThe index to the sensor module entry.
1.3.6.1.4.1.318.1.1.10.4.7.11.1.2ColumnmemFluidSensorConfigSensorIndexread-onlymandatoryThe index to the sensor entry.
1.3.6.1.4.1.318.1.1.10.4.7.11.1.3ColumnmemFluidSensorConfigSensorNameread-writemandatoryThe user defined name of the fluid sensor.
1.3.6.1.4.1.318.1.1.10.4.7.11.1.4ColumnmemFluidSensorConfigSensorLocationread-writemandatoryThe user defined location of the fluid sensor.
1.3.6.1.4.1.318.1.1.10.4.7.11.1.5ColumnmemFluidSensorConfigSensorSeverityread-writemandatoryThe severity of the alarm that will be triggered when the fluid sensor is activated. The alarms can be critical(1), warning(2) or informational(3).
1.3.6.1.4.1.318.1.1.10.4.7.11.1.6ColumnmemFluidSensorConfigAlarmGenerationread-writemandatoryEnable or disable alarm generation on this input.
1.3.6.1.4.1.318.1.1.10.4.7.12TablememDoorSensorConfigTablenot-accessiblemandatoryAllows for the configuration of individual sensors.
1.3.6.1.4.1.318.1.1.10.4.7.12.1RowmemDoorSensorConfigEntrynot-accessiblemandatoryThe sensors to configure.
1.3.6.1.4.1.318.1.1.10.4.7.12.1.1ColumnmemDoorSensorModuleConfigIndexread-onlymandatoryThe index to the sensor module entry.
1.3.6.1.4.1.318.1.1.10.4.7.12.1.2ColumnmemDoorSensorConfigSensorIndexread-onlymandatoryThe index to the sensor entry.
1.3.6.1.4.1.318.1.1.10.4.7.12.1.3ColumnmemDoorSensorConfigSensorNameread-writemandatoryThe user defined name of the door sensor.
1.3.6.1.4.1.318.1.1.10.4.7.12.1.4ColumnmemDoorSensorConfigSensorLocationread-writemandatoryThe user defined location of the door sensor.
1.3.6.1.4.1.318.1.1.10.4.7.12.1.5ColumnmemDoorSensorConfigSensorSeverityread-writemandatoryThe severity of the alarm that will be triggered when the door sensor is activated. The alarms can be critical(1), warning(2) or informational(3).
1.3.6.1.4.1.318.1.1.10.4.7.12.1.6ColumnmemDoorSensorConfigAlarmGenerationread-writemandatoryEnable or disable alarm generation on this input.
1.3.6.1.4.1.318.1.1.10.5NodeenvWireless
1.3.6.1.4.1.318.1.1.10.5.1NodewirelessSensorStatus
1.3.6.1.4.1.318.1.1.10.5.1.1TablewirelessSensorStatusTablenot-accessiblemandatoryAllows for the access of individual sensors.
1.3.6.1.4.1.318.1.1.10.5.1.1.1RowwirelessSensorStatusEntrynot-accessiblemandatoryA list of wireless sensor status table entries.
1.3.6.1.4.1.318.1.1.10.5.1.1.1.1ColumnwirelessSensorStatusIndexread-onlymandatoryThe index to the sensor entry.
1.3.6.1.4.1.318.1.1.10.5.1.1.1.2ColumnwirelessSensorStatusExtAddrread-onlymandatoryThe extended address is the combination of the unique 10 byte MAC address of the sensor concatenated with its short address.
1.3.6.1.4.1.318.1.1.10.5.1.1.1.3ColumnwirelessSensorStatusNameread-onlymandatoryThe name of the wireless sensor.
1.3.6.1.4.1.318.1.1.10.5.1.1.1.4ColumnwirelessSensorStatusAlarmGenerationread-onlymandatoryIndicates whether alarm generation is enabled or disabled for the sensor.
1.3.6.1.4.1.318.1.1.10.5.1.1.1.5ColumnwirelessSensorStatusTemperatureread-onlymandatoryThe current temperature are displayed in tenths of degrees in the scale shown in the emsStatusSysTempUnits OID (Celsius or Fahrenheit).
1.3.6.1.4.1.318.1.1.10.5.1.1.1.6ColumnwirelessSensorStatusHighTempThreshread-onlymandatoryValues are displayed in tenths of degrees in the scale shown in the emsStatusSysTempUnits OID (Celsius or Fahrenheit).
1.3.6.1.4.1.318.1.1.10.5.1.1.1.7ColumnwirelessSensorStatusLowTempThreshread-onlymandatoryValues are displayed in tenths of degrees in the scale shown in the emsStatusSysTempUnits OID (Celsius or Fahrenheit).
1.3.6.1.4.1.318.1.1.10.5.1.1.1.8ColumnwirelessSensorStatusHumidityread-onlymandatoryValues are represented in whole number percentage.
1.3.6.1.4.1.318.1.1.10.5.1.1.1.9ColumnwirelessSensorStatusHighHumidityThreshread-onlymandatoryValues are represented in whole number percentage.
1.3.6.1.4.1.318.1.1.10.5.1.1.1.10ColumnwirelessSensorStatusLowHumidityThreshread-onlymandatoryValues are represented in whole number percentage.
1.3.6.1.4.1.318.1.1.10.5.1.1.1.11ColumnwirelessSensorStatusCommStatusread-onlymandatoryThe communication status of the wireless sensor. inactive(0) indicates sensor is in the wireless network but not sending information. active(1) indicates wirel…
1.3.6.1.4.1.318.1.1.10.5.1.1.1.12ColumnwirelessSensorStatusMaxTempThreshread-onlymandatoryValues are displayed in tenths of degrees in the scale shown in the emsStatusSysTempUnits OID (Celsius or Fahrenheit).
1.3.6.1.4.1.318.1.1.10.5.1.1.1.13ColumnwirelessSensorStatusMinTempThreshread-onlymandatoryValues are displayed in tenths of degrees in the scale shown in the emsStatusSysTempUnits OID (Celsius or Fahrenheit).
1.3.6.1.4.1.318.1.1.10.5.1.1.1.14ColumnwirelessSensorStatusMaxHumidityThreshread-onlymandatoryValues are represented in whole number percentage.
1.3.6.1.4.1.318.1.1.10.5.1.1.1.15ColumnwirelessSensorStatusMinHumidityThreshread-onlymandatoryValues are represented in whole number percentage.
1.3.6.1.4.1.318.1.1.10.5.1.1.1.16ColumnwirelessSensorStatusBatteryread-onlymandatoryValues are displayed in tenths of Volts DC.
1.3.6.1.4.1.318.1.1.10.5.1.1.1.17ColumnwirelessSensorStatusLowBatteryThreshread-onlymandatoryValues are displayed in tenths of Volts DC.
1.3.6.1.4.1.318.1.1.10.5.1.1.1.18ColumnwirelessSensorStatusMinBatteryThreshread-onlymandatoryValues are displayed in tenths of Volts DC.
1.3.6.1.4.1.318.1.1.10.5.1.1.1.19ColumnwirelessSensorStatusRssiread-onlymandatoryValues are represented in whole number percentage.
1.3.6.1.4.1.318.1.1.10.5.1.1.1.20ColumnwirelessSensorStatusLowRssiThreshread-onlymandatoryValues are represented in whole number percentage.
1.3.6.1.4.1.318.1.1.10.5.1.1.1.21ColumnwirelessSensorStatusMinRssiThreshread-onlymandatoryValues are represented in whole number percentage.
1.3.6.1.4.1.318.1.1.10.5.1.1.1.22ColumnwirelessSensorStatusLocationread-onlymandatoryA user-defined string identifying the location of the wireless sensor.
1.3.6.1.4.1.318.1.1.10.5.1.1.1.23ColumnwirelessSensorStatusAlarmStatusread-onlymandatoryThe alarm status of the wireless sensor. This integer should be interpreted as a bit map, with each bit representing the presence or absence of the specific al…
1.3.6.1.4.1.318.1.1.10.5.2NodewirelessSensorPodStatus
1.3.6.1.4.1.318.1.1.10.5.2.1TablewirelessSensorPodStatusTablenot-accessiblemandatoryAllows for the access of individual pod sensors.
1.3.6.1.4.1.318.1.1.10.5.2.1.1RowwirelessSensorPodStatusEntrynot-accessiblemandatoryThe sensor pod to access.
1.3.6.1.4.1.318.1.1.10.5.2.1.1.1ColumnwirelessSensorPodStatusIndexread-onlymandatoryThe index to the pod sensor entry.
1.3.6.1.4.1.318.1.1.10.5.2.1.1.2ColumnwirelessSensorPodPortIndexread-onlymandatoryThe pod sensor port index.
1.3.6.1.4.1.318.1.1.10.5.2.1.1.3ColumnwirelessSensorPodStatusExtAddrread-onlymandatoryThe extended address is the combination of the unique 10 byte MAC address of the sensor concatenated with its short address.
1.3.6.1.4.1.318.1.1.10.5.2.1.1.4ColumnwirelessSensorPodStatusNameread-onlymandatoryThe name of the sensor pod.
1.3.6.1.4.1.318.1.1.10.5.2.1.1.5ColumnwirelessSensorPodStatusAlarmGenerationread-onlymandatoryStatus of whether alarm generation is enabled or disabled.
1.3.6.1.4.1.318.1.1.10.5.2.1.1.6ColumnwirelessSensorPodStatusTemperatureread-onlymandatoryValues are displayed in tenths of degrees in the scale shown in the emsStatusSysTempUnits OID (Celsius or Fahrenheit).
1.3.6.1.4.1.318.1.1.10.5.2.1.1.7ColumnwirelessSensorPodStatusHighTempThreshread-onlymandatoryValues are displayed in tenths of degrees in the scale shown in the emsStatusSysTempUnits OID (Celsius or Fahrenheit).
1.3.6.1.4.1.318.1.1.10.5.2.1.1.8ColumnwirelessSensorPodStatusLowTempThreshread-onlymandatoryValues are displayed in tenths of degrees in the scale shown in the emsStatusSysTempUnits OID (Celsius or Fahrenheit).
1.3.6.1.4.1.318.1.1.10.5.2.1.1.9ColumnwirelessSensorPodStatusHumidityread-onlymandatoryValues are represented in whole number percentage.
1.3.6.1.4.1.318.1.1.10.5.2.1.1.10ColumnwirelessSensorPodStatusHighHumidityThreshread-onlymandatoryValues are represented in whole number percentage.
1.3.6.1.4.1.318.1.1.10.5.2.1.1.11ColumnwirelessSensorPodStatusLowHumidityThreshread-onlymandatoryValues are represented in whole number percentage.
1.3.6.1.4.1.318.1.1.10.5.2.1.1.12ColumnwirelessSensorPodStatusCommStatusread-onlymandatoryThe communication status of the wireless sensor. inactive(0) indicates pod sensor is in the wireless network but not sending information. active(1) indicates w…
1.3.6.1.4.1.318.1.1.10.5.2.1.1.13ColumnwirelessSensorPodStatusMaxTempThreshread-onlymandatoryValues are displayed in tenths of degrees in the scale shown in the emsStatusSysTempUnits OID (Celsius or Fahrenheit).
1.3.6.1.4.1.318.1.1.10.5.2.1.1.14ColumnwirelessSensorPodStatusMinTempThreshread-onlymandatoryValues are displayed in tenths of degrees in the scale shown in the emsStatusSysTempUnits OID (Celsius or Fahrenheit).
1.3.6.1.4.1.318.1.1.10.5.2.1.1.15ColumnwirelessSensorPodStatusMaxHumidityThreshread-onlymandatoryValues are represented in whole number percentage.
1.3.6.1.4.1.318.1.1.10.5.2.1.1.16ColumnwirelessSensorPodStatusMinHumidityThreshread-onlymandatoryValues are represented in whole number percentage.
1.3.6.1.4.1.318.1.1.10.5.2.1.1.17ColumnwirelessSensorPodStatusDryContactStateread-onlymandatoryState of the dry contact. If the dry contact is closed, the drycontactClosed (1) value will be returned. If the dry contact state is open, the drycontactOpen (…
1.3.6.1.4.1.318.1.1.10.5.2.1.1.18ColumnwirelessSensorPodStatusDryContactNormalStateread-onlymandatoryThe normal state of the dry contact. If the normal state is closed, the normallyClosed (1) value will be returned. If the normal state is open, the normallyOpe…
1.3.6.1.4.1.318.1.1.10.5.2.1.1.19ColumnwirelessSensorPodStatusBatteryread-onlymandatoryValues are displayed in tenths of Volts DC.
1.3.6.1.4.1.318.1.1.10.5.2.1.1.20ColumnwirelessSensorPodStatusLowBatteryThreshread-onlymandatoryValues are displayed in tenths of Volts DC.
1.3.6.1.4.1.318.1.1.10.5.2.1.1.21ColumnwirelessSensorPodStatusMinBatteryThreshread-onlymandatoryValues are displayed in tenths of Volts DC.
1.3.6.1.4.1.318.1.1.10.5.2.1.1.22ColumnwirelessSensorPodStatusRssiread-onlymandatoryValues are represented in whole number percentage.
1.3.6.1.4.1.318.1.1.10.5.2.1.1.23ColumnwirelessSensorPodStatusLowRssiThreshread-onlymandatoryValues are represented in whole number percentage.
1.3.6.1.4.1.318.1.1.10.5.2.1.1.24ColumnwirelessSensorPodStatusMinRssiThreshread-onlymandatoryValues are represented in whole number percentage.
1.3.6.1.4.1.318.1.1.10.5.2.1.1.25ColumnwirelessSensorPodStatusLocationread-onlymandatoryThe location of the wireless sensor pod.
1.3.6.1.4.1.318.1.1.10.5.2.1.1.26ColumnwirelessSensorPodStatusAlarmStatusread-onlymandatoryThe alarm status of the wireless pod sensor. This integer should be interpreted as a bit map, with each bit representing the presence or absence of the specifi…
1.3.6.1.4.1.318.1.1.10.5.3NodewirelessSensorConfig
1.3.6.1.4.1.318.1.1.10.5.3.1TablewirelessSensorConfigTablenot-accessiblemandatoryAllows for the configuration of individual sensors.
1.3.6.1.4.1.318.1.1.10.5.3.1.1RowwirelessSensorConfigEntrynot-accessiblemandatoryThe sensor to configure.
1.3.6.1.4.1.318.1.1.10.5.3.1.1.1ColumnwirelessSensorConfigIndexread-onlymandatoryThe index to the entry.
1.3.6.1.4.1.318.1.1.10.5.3.1.1.2ColumnwirelessSensorConfigNameread-writemandatoryThe user-defined wireless sensor ID string.
1.3.6.1.4.1.318.1.1.10.5.3.1.1.3ColumnwirelessSensorConfigAlarmGenerationread-writemandatoryEnable or disable alarm generation for this sensor.
1.3.6.1.4.1.318.1.1.10.5.3.1.1.4ColumnwirelessSensorConfigHighTempThreshread-writemandatoryValues are displayed in tenths of degrees in the scale shown in the emsStatusSysTempUnits OID (Celsius or Fahrenheit).
1.3.6.1.4.1.318.1.1.10.5.3.1.1.5ColumnwirelessSensorConfigLowTempThreshread-writemandatoryValues are displayed in tenths of degrees in the scale shown in the emsStatusSysTempUnits OID (Celsius or Fahrenheit).
1.3.6.1.4.1.318.1.1.10.5.3.1.1.6ColumnwirelessSensorConfigHighHumidityThreshread-writemandatoryValues are represented in whole number percentage.
1.3.6.1.4.1.318.1.1.10.5.3.1.1.7ColumnwirelessSensorConfigLowHumidityThreshread-writemandatoryValues are represented in whole number percentage.
1.3.6.1.4.1.318.1.1.10.5.3.1.1.8ColumnwirelessSensorConfigMaxTempThreshread-writemandatoryValues are displayed in tenths of degrees in the scale shown in the emsStatusSysTempUnits OID (Celsius or Fahrenheit).
1.3.6.1.4.1.318.1.1.10.5.3.1.1.9ColumnwirelessSensorConfigMinTempThreshread-writemandatoryValues are displayed in tenths of degrees in the scale shown in the emsStatusSysTempUnits OID (Celsius or Fahrenheit).
1.3.6.1.4.1.318.1.1.10.5.3.1.1.10ColumnwirelessSensorConfigMaxHumidityThreshread-writemandatoryValues are represented in whole number percentage.
1.3.6.1.4.1.318.1.1.10.5.3.1.1.11ColumnwirelessSensorConfigMinHumidityThreshread-writemandatoryValues are represented in whole number percentage.
1.3.6.1.4.1.318.1.1.10.5.3.1.1.12ColumnwirelessSensorConfigLowBatteryThreshread-writemandatoryValues are displayed in tenths of Volts DC.
1.3.6.1.4.1.318.1.1.10.5.3.1.1.13ColumnwirelessSensorConfigMinBatteryThreshread-writemandatoryValues are displayed in tenths of Volts DC.
1.3.6.1.4.1.318.1.1.10.5.3.1.1.14ColumnwirelessSensorConfigLowRssiThreshread-writemandatoryValues are represented in whole number percentage.
1.3.6.1.4.1.318.1.1.10.5.3.1.1.15ColumnwirelessSensorConfigMinRssiThreshread-writemandatoryValues are represented in whole number percentage.
1.3.6.1.4.1.318.1.1.10.5.3.1.1.16ColumnwirelessSensorConfigLocationread-writemandatoryA user-defined string identifying the location of the wireless sensor. Maximum text input is 20 characters.
1.3.6.1.4.1.318.1.1.10.5.4NodewirelessSensorPodConfig
1.3.6.1.4.1.318.1.1.10.5.4.1TablewirelessSensorPodConfigTablenot-accessiblemandatoryAllows for the configuration of individual sensors.
1.3.6.1.4.1.318.1.1.10.5.4.1.1RowwirelessSensorPodConfigEntrynot-accessiblemandatoryThe sensor to configure.
1.3.6.1.4.1.318.1.1.10.5.4.1.1.1ColumnwirelessSensorPodConfigIndexread-onlymandatoryThe index to the entry.
1.3.6.1.4.1.318.1.1.10.5.4.1.1.2ColumnwirelessSensorPodConfigPortIndexread-onlymandatoryThe sensor pod port index.
1.3.6.1.4.1.318.1.1.10.5.4.1.1.3ColumnwirelessSensorPodConfigNameread-writemandatoryThe user defined name of the sensor pod.
1.3.6.1.4.1.318.1.1.10.5.4.1.1.4ColumnwirelessSensorPodConfigAlarmGenerationread-writemandatoryEnable or disable alarm generation for this sensor.
1.3.6.1.4.1.318.1.1.10.5.4.1.1.5ColumnwirelessSensorPodConfigDryContactNormalStateread-writemandatoryThe normal state of the dry contact. If the normal state is closed, the normallyClosed (1) value will be returned. If the normal state is open, the normallyOpe…
1.3.6.1.4.1.318.1.1.10.5.4.1.1.6ColumnwirelessSensorPodConfigHighTempThreshread-writemandatoryValues are displayed in tenths of degrees in the scale shown in the emsStatusSysTempUnits OID (Celsius or Fahrenheit).
1.3.6.1.4.1.318.1.1.10.5.4.1.1.7ColumnwirelessSensorPodConfigLowTempThreshread-writemandatoryValues are displayed in tenths of degrees in the scale shown in the emsStatusSysTempUnits OID (Celsius or Fahrenheit).
1.3.6.1.4.1.318.1.1.10.5.4.1.1.8ColumnwirelessSensorPodConfigHighHumidityThreshread-writemandatoryValues are represented in whole number percentage.
1.3.6.1.4.1.318.1.1.10.5.4.1.1.9ColumnwirelessSensorPodConfigLowHumidityThreshread-writemandatoryValues are represented in whole number percentage.
1.3.6.1.4.1.318.1.1.10.5.4.1.1.10ColumnwirelessSensorPodConfigMaxTempThreshread-writemandatoryValues are displayed in tenths of degrees in the scale shown in the emsStatusSysTempUnits OID (Celsius or Fahrenheit).
1.3.6.1.4.1.318.1.1.10.5.4.1.1.11ColumnwirelessSensorPodConfigMinTempThreshread-writemandatoryValues are represented in whole number degrees. Units are displayed in the scale shown in the emsStatusSysTempUnits OID (Celsius or Fahrenheit).
1.3.6.1.4.1.318.1.1.10.5.4.1.1.12ColumnwirelessSensorPodConfigMaxHumidityThreshread-writemandatoryValues are represented in whole number percentage.
1.3.6.1.4.1.318.1.1.10.5.4.1.1.13ColumnwirelessSensorPodConfigMinHumidityThreshread-writemandatoryValues are represented in whole number percentage.
1.3.6.1.4.1.318.1.1.10.5.4.1.1.14ColumnwirelessSensorPodConfigLowBatteryThreshread-writemandatoryValues are displayed in tenths of Volts DC.
1.3.6.1.4.1.318.1.1.10.5.4.1.1.15ColumnwirelessSensorPodConfigMinBatteryThreshread-writemandatoryValues are displayed in tenths of Volts DC.
1.3.6.1.4.1.318.1.1.10.5.4.1.1.16ColumnwirelessSensorPodConfigLowRssiThreshread-writemandatoryValues are represented in whole number percentage.
1.3.6.1.4.1.318.1.1.10.5.4.1.1.17ColumnwirelessSensorPodConfigMinRssiThreshread-writemandatoryValues are represented in whole number percentage.
1.3.6.1.4.1.318.1.1.10.5.4.1.1.18ColumnwirelessSensorPodConfigLocationread-writemandatoryA user-defined string identifying the location of the wireless pod sensor. Maximum text input is 20 characters.
1.3.6.1.4.1.318.1.1.11Nodenetlock
1.3.6.1.4.1.318.1.1.11.1NodenlIdent
1.3.6.1.4.1.318.1.1.11.2NodenlStatus
1.3.6.1.4.1.318.1.1.12NoderPDU
1.3.6.1.4.1.318.1.1.12.1NoderPDUIdent
1.3.6.1.4.1.318.1.1.12.1.1ScalarrPDUIdentNameread-writemandatoryThe name of the Rack PDU. The maximum string size is device dependent.
1.3.6.1.4.1.318.1.1.12.1.2ScalarrPDUIdentHardwareRevread-onlymandatoryThe hardware revision of the Rack PDU. This value is set at the factory.
1.3.6.1.4.1.318.1.1.12.1.3ScalarrPDUIdentFirmwareRevread-onlymandatoryAn 8-byte ID string identifying the Rack PDU firmware revision. This value is set at the factory.
1.3.6.1.4.1.318.1.1.12.1.4ScalarrPDUIdentDateOfManufactureread-onlymandatoryThe date when the Rack PDU was manufactured in mm/dd/yyyy format. This value is set at the factory. The year 2000 will be represented by 00.
1.3.6.1.4.1.318.1.1.12.1.5ScalarrPDUIdentModelNumberread-onlymandatoryA 10-character string identifying the model number of the Rack PDU. This value is set at the factory.
1.3.6.1.4.1.318.1.1.12.1.6ScalarrPDUIdentSerialNumberread-onlymandatoryA 12-character string identifying the serial number of the Rack PDU. This value is set at the factory.
1.3.6.1.4.1.318.1.1.12.1.7ScalarrPDUIdentDeviceRatingread-onlymandatoryGetting this OID will return the electrical rating of the device in Amps.
1.3.6.1.4.1.318.1.1.12.1.8ScalarrPDUIdentDeviceNumOutletsread-onlymandatoryGetting this OID will return the number of outlets contained in the device.
1.3.6.1.4.1.318.1.1.12.1.9ScalarrPDUIdentDeviceNumPhasesread-onlymandatoryGetting this OID will return the number of phases supported by the device.
1.3.6.1.4.1.318.1.1.12.1.10ScalarrPDUIdentDeviceNumBreakersread-onlymandatoryGetting this OID will return the number of circuit breakers supported by the device. This is the same as the number of banks of outlets. 0 will be returned if …
1.3.6.1.4.1.318.1.1.12.1.11ScalarrPDUIdentDeviceBreakerRatingread-onlymandatoryGetting this OID will return rating of the circuit breakers on the device in Amps if it has any.
1.3.6.1.4.1.318.1.1.12.1.12ScalarrPDUIdentDeviceOrientationread-onlymandatoryGetting this OID will return the intended physical orientation of the device. OrientHorizonatal(1) indicates Horizontal. OrientVertical(2) indicates Vertical.
1.3.6.1.4.1.318.1.1.12.1.13ScalarrPDUIdentDeviceOutletLayoutread-onlymandatoryGetting this OID will return outlet layout for the device. seqPhaseToNeutral(1) indicates outlet layout as follows: 1:1-N,2:2-N,3:3-N,4:1-N,5:2-N,... seqPhaseT…
1.3.6.1.4.1.318.1.1.12.1.14ScalarrPDUIdentDeviceDisplayOrientationread-writemandatoryGetting this OID will return the intended physical orientation of the Seven-Segment Display. Normal(1) indicates Normal. Reverse(2)indicates Upside-Down.
1.3.6.1.4.1.318.1.1.12.1.15ScalarrPDUIdentDeviceLinetoLineVoltageread-writemandatoryGetting/Setting this OID will return/set the Line to Line Voltage. This OID defaults to the nominal input line voltage in volts AC. This setting is used to cal…
1.3.6.1.4.1.318.1.1.12.1.16ScalarrPDUIdentDevicePowerWattsread-onlymandatoryGetting this OID will return the Power in Watts.
1.3.6.1.4.1.318.1.1.12.1.17ScalarrPDUIdentDevicePowerFactorread-writemandatoryGetting/setting this OID will return/set the Power Factor in thousanths (1000 is power factor of 1). For AP8XXX SKUs, this OID is read-only Valid range is from…
1.3.6.1.4.1.318.1.1.12.1.18ScalarrPDUIdentDevicePowerVAread-onlymandatoryGetting this OID will return the Power in VA.
1.3.6.1.4.1.318.1.1.12.1.19ScalarrPDUIdentDeviceLinetoNeutralVoltageread-writemandatoryGetting/Setting this OID will return/set the Line to Neutral Voltage. This OID defaults to the nominal line to neutral voltage in volts AC. This setting is use…
1.3.6.1.4.1.318.1.1.12.2NoderPDULoad
1.3.6.1.4.1.318.1.1.12.2.1NoderPDULoadDevice
1.3.6.1.4.1.318.1.1.12.2.1.1ScalarrPDULoadDevMaxPhaseLoadread-onlymandatoryGetting this OID will return the maximum rated power that each phase of the Rack PDU can provide. It is represented in Amps. 0 will be returned if the unit is …
1.3.6.1.4.1.318.1.1.12.2.1.2ScalarrPDULoadDevNumPhasesread-onlymandatoryThe number of phases available with this Rack PDU.
1.3.6.1.4.1.318.1.1.12.2.1.3ScalarrPDULoadDevMaxBankLoadread-onlymandatoryGetting this OID will return the maximum rated power that a bank of the Rack PDU can provide. It is represented in Amps. 0 will be returned if the device does …
1.3.6.1.4.1.318.1.1.12.2.1.4ScalarrPDULoadDevNumBanksread-onlymandatoryThe number of banks of outlets available with this Rack PDU. A bank of outlets has a unique circuit breaker for a subset of the total number of outlets on the …
1.3.6.1.4.1.318.1.1.12.2.1.5ScalarrPDULoadDevBankTableSizeread-onlymandatoryThe size of the Bank Table.
1.3.6.1.4.1.318.1.1.12.2.1.6TablerPDULoadDevBankTablenot-accessiblemandatoryAllows for getting the Bank Max Load in the Rack PDU.
1.3.6.1.4.1.318.1.1.12.2.1.6.1RowrPDULoadDevBankEntrynot-accessiblemandatoryThe Rack PDU Banks Access.
1.3.6.1.4.1.318.1.1.12.2.1.6.1.1ColumnrPDULoadDevBankIndexread-onlymandatoryThe index to the Rack PDU bank entry.
1.3.6.1.4.1.318.1.1.12.2.1.6.1.2ColumnrPDULoadDevBankNumberread-onlymandatoryGetting this OID will return the bank number.
1.3.6.1.4.1.318.1.1.12.2.1.6.1.3ColumnrPDULoadDevBankMaxLoadread-onlymandatoryGetting this OID will return the maximum rated power that each bank of the Rack PDU can provide. It is represented in Amps.
1.3.6.1.4.1.318.1.1.12.2.1.7ScalarrPDULoadDevMaxOutletTableSizeread-onlymandatoryThe size of the Outlet Table.
1.3.6.1.4.1.318.1.1.12.2.1.8TablerPDULoadDevMaxOutletTablenot-accessiblemandatoryAllows for getting the Max Outlet Load in an Outlet Monitored Rack PDU.
1.3.6.1.4.1.318.1.1.12.2.1.8.1RowrPDULoadDevMaxOutletEntrynot-accessiblemandatoryThis gives access to Max Outlet Load of an Outlet Monitored Rack PDU
1.3.6.1.4.1.318.1.1.12.2.1.8.1.1ColumnrPDULoadDevOutletIndexread-onlymandatoryThe index to the Outlet Monitored Rack PDU Max Outlet Load entry.
1.3.6.1.4.1.318.1.1.12.2.1.8.1.2ColumnrPDULoadDevOutletNumberread-onlymandatoryGetting this OID will return the Outlet number.
1.3.6.1.4.1.318.1.1.12.2.1.8.1.3ColumnrPDULoadDevMaxOutletLoadread-onlymandatoryGetting this OID will return the maximum rated power that each Outlet of an Outlet Monitored Rack PDU can provide. It is represented in Amps.
1.3.6.1.4.1.318.1.1.12.2.2NoderPDULoadPhaseConfig
1.3.6.1.4.1.318.1.1.12.2.2.1TablerPDULoadPhaseConfigTablenot-accessiblemandatoryAllows for configuration of each Rack PDU phase. The number of entries is contained in the rPDULoadDevNumPhases OID.
1.3.6.1.4.1.318.1.1.12.2.2.1.1RowrPDULoadPhaseConfigEntrynot-accessiblemandatoryThe Rack PDU phase to configure.
1.3.6.1.4.1.318.1.1.12.2.2.1.1.1ColumnrPDULoadPhaseConfigIndexread-onlymandatoryThe index to the Rack PDU phase entry.
1.3.6.1.4.1.318.1.1.12.2.2.1.1.2ColumnrPDULoadPhaseConfigLowLoadThresholdread-writemandatoryA threshold that indicates the power consumption of the load is nearing a low consumption condition. It is represented in Amps. A warning will be issued when t…
1.3.6.1.4.1.318.1.1.12.2.2.1.1.3ColumnrPDULoadPhaseConfigNearOverloadThresholdread-writemandatoryA threshold that indicates the power consumption of the load is nearing an overload condition. It is represented in Amps. A warning will be issued when the loa…
1.3.6.1.4.1.318.1.1.12.2.2.1.1.4ColumnrPDULoadPhaseConfigOverloadThresholdread-writemandatoryA threshold that indicates the power consumption of the load has entered an overload condition. It is represented in Amps. A warning will be issued when the lo…
1.3.6.1.4.1.318.1.1.12.2.2.1.1.5ColumnrPDULoadPhaseConfigAlarmread-onlymandatoryGetting this OID will return the current Phase Alarm.
1.3.6.1.4.1.318.1.1.12.2.3NoderPDULoadStatus
1.3.6.1.4.1.318.1.1.12.2.3.1TablerPDULoadStatusTablenot-accessiblemandatoryAllows for getting of status of each Rack PDU phase/bank. The number of entries is calculated by adding the number of phases (rPDULoadDevNumPhases OID) and the…
1.3.6.1.4.1.318.1.1.12.2.3.1.1RowrPDULoadStatusEntrynot-accessiblemandatoryThe Rack PDU phase/bank to gather status from.
1.3.6.1.4.1.318.1.1.12.2.3.1.1.1ColumnrPDULoadStatusIndexread-onlymandatoryThe index to the Rack PDU phase/bank entry. All phase information will precede any bank information
1.3.6.1.4.1.318.1.1.12.2.3.1.1.2ColumnrPDULoadStatusLoadread-onlymandatoryGetting this OID will return the phase/bank load measured in tenths of Amps.
1.3.6.1.4.1.318.1.1.12.2.3.1.1.3ColumnrPDULoadStatusLoadStateread-onlymandatoryGetting this OID will return the phase/bank load state. phaseLoadNormal(1) indicates that the phase/bank is operating properly within the rPDULoadConfigLowLoad…
1.3.6.1.4.1.318.1.1.12.2.3.1.1.4ColumnrPDULoadStatusPhaseNumberread-onlymandatoryThe phase number to which this record refers.
1.3.6.1.4.1.318.1.1.12.2.3.1.1.5ColumnrPDULoadStatusBankNumberread-onlymandatoryThe bank number to which this record refers. A value of 0 will be returned if any bank is not present or if it is phase related.
1.3.6.1.4.1.318.1.1.12.2.4NoderPDULoadBankConfig
1.3.6.1.4.1.318.1.1.12.2.4.1TablerPDULoadBankConfigTablenot-accessiblemandatoryAllows for configuration of each Rack PDU bank. The number of entries is contained in the rPDULoadDevNumBanks OID.
1.3.6.1.4.1.318.1.1.12.2.4.1.1RowrPDULoadBankConfigEntrynot-accessiblemandatoryThe Rack PDU bank to configure.
1.3.6.1.4.1.318.1.1.12.2.4.1.1.1ColumnrPDULoadBankConfigIndexread-onlymandatoryThe index to the Rack PDU bank entry.
1.3.6.1.4.1.318.1.1.12.2.4.1.1.2ColumnrPDULoadBankConfigLowLoadThresholdread-writemandatoryA threshold that indicates the power consumption of the load is nearing a low consumption condition. It is represented in Amps. A warning will be issued when t…
1.3.6.1.4.1.318.1.1.12.2.4.1.1.3ColumnrPDULoadBankConfigNearOverloadThresholdread-writemandatoryA threshold that indicates the power consumption of the load is nearing an overload condition. It is represented in Amps. A warning will be issued when the loa…
1.3.6.1.4.1.318.1.1.12.2.4.1.1.4ColumnrPDULoadBankConfigOverloadThresholdread-writemandatoryA threshold that indicates the power consumption of the load has entered an overload condition. It is represented in Amps. A warning will be issued when the lo…
1.3.6.1.4.1.318.1.1.12.2.4.1.1.5ColumnrPDULoadBankConfigAlarmread-onlymandatoryGetting this OID will return the current Bank Alarm.
1.3.6.1.4.1.318.1.1.12.3NoderPDUOutlet
1.3.6.1.4.1.318.1.1.12.3.1NoderPDUOutletDevice
1.3.6.1.4.1.318.1.1.12.3.1.1ScalarrPDUOutletDevCommandread-writemandatorySetting this OID to immediateAllOn (2) will turn all outlets on immediately. Setting this OID to immediateAllOff (3) will turn all outlets off immediately. Set…
1.3.6.1.4.1.318.1.1.12.3.1.2ScalarrPDUOutletDevColdstartDelayread-writemandatoryThe amount of delay, in seconds, between when power is provided to the Switched Rack PDU and when the Switched Rack PDU provides basic master power to the outl…
1.3.6.1.4.1.318.1.1.12.3.1.3ScalarrPDUOutletDevNumCntrlOutletsread-onlymandatoryThe number of controlled outlets on this Switched Rack PDU.
1.3.6.1.4.1.318.1.1.12.3.1.4ScalarrPDUOutletDevNumTotalOutletsread-onlymandatoryThe total number of outlets on this Rack PDU.
1.3.6.1.4.1.318.1.1.12.3.1.5ScalarrPDUOutletDevMonitoredOutletsread-onlymandatoryThe total number of monitored outlets on this Rack PDU.
1.3.6.1.4.1.318.1.1.12.3.2NoderPDUOutletPhase
1.3.6.1.4.1.318.1.1.12.3.2.1TablerPDUOutletPhaseTablenot-accessiblemandatoryAllows for management of outlets on a per phase basis.
1.3.6.1.4.1.318.1.1.12.3.2.1.1RowrPDUOutletPhaseEntrynot-accessiblemandatoryThe phase to manage.
1.3.6.1.4.1.318.1.1.12.3.2.1.1.1ColumnrPDUOutletPhaseIndexread-onlymandatoryThe index to the Switched Rack PDU phase entry.
1.3.6.1.4.1.318.1.1.12.3.2.1.1.2ColumnrPDUOutletPhaseOverloadRestrictionread-writemandatoryThis OID controls the behavior of a Switched Rack PDU phase when an overload condition is possible and additional outlets are requested to be turned on. Settin…
1.3.6.1.4.1.318.1.1.12.3.3NoderPDUOutletControl
1.3.6.1.4.1.318.1.1.12.3.3.1TablerPDUOutletControlTablenot-accessiblemandatoryAllows for control of the individual outlets. The number of entries is contained in the rPDUOutletDevNumCntrlOutlets OID.
1.3.6.1.4.1.318.1.1.12.3.3.1.1RowrPDUOutletControlEntrynot-accessiblemandatoryThe outlet to control.
1.3.6.1.4.1.318.1.1.12.3.3.1.1.1ColumnrPDUOutletControlIndexread-onlymandatoryThe index to the outlet entry.
1.3.6.1.4.1.318.1.1.12.3.3.1.1.2ColumnrPDUOutletControlOutletNameread-onlymandatoryThe name of the outlet. The maximum string size is device dependent. An error will be returned if the set request exceeds the max size. This OID is provided fo…
1.3.6.1.4.1.318.1.1.12.3.3.1.1.3ColumnrPDUOutletControlOutletPhaseread-onlymandatoryThe phase/s associated with this outlet. For single phase devices, this object will always return phase1(1). For 3-phase devices, this object will return phase…
1.3.6.1.4.1.318.1.1.12.3.3.1.1.4ColumnrPDUOutletControlOutletCommandread-writemandatoryGetting this variable will return the outlet state. If the outlet is on, the immediateOn (1) value will be returned. If the outlet is off, the immediateOff (2)…
1.3.6.1.4.1.318.1.1.12.3.3.1.1.5ColumnrPDUOutletControlOutletBankread-onlymandatoryThe bank associated with this outlet.
1.3.6.1.4.1.318.1.1.12.3.4NoderPDUOutletConfig
1.3.6.1.4.1.318.1.1.12.3.4.1TablerPDUOutletConfigTablenot-accessiblemandatoryAllows for configuration of individual outlets. The number of entries is contained in the rPDUOutletDevNumCntrlOutlets OID.
1.3.6.1.4.1.318.1.1.12.3.4.1.1RowrPDUOutletConfigEntrynot-accessiblemandatoryThe outlet to configure.
1.3.6.1.4.1.318.1.1.12.3.4.1.1.1ColumnrPDUOutletConfigIndexread-onlymandatoryThe index to the outlet entry.
1.3.6.1.4.1.318.1.1.12.3.4.1.1.2ColumnrPDUOutletConfigOutletNameread-writemandatoryThe name of the outlet. The maximum string size is device dependent. An error will be returned if the set request exceeds the max size.
1.3.6.1.4.1.318.1.1.12.3.4.1.1.3ColumnrPDUOutletConfigOutletPhaseread-onlymandatoryThe phase/s associated with this outlet. For single phase devices, this object will always return phase1(1). For 3-phase devices, this object will return phase…
1.3.6.1.4.1.318.1.1.12.3.4.1.1.4ColumnrPDUOutletConfigPowerOnTimeread-writemandatoryThe amount of time (in seconds) the outlet will delay powering on at coldstart or when a command that requires a turn-on delay is issued. Allowed values are: -…
1.3.6.1.4.1.318.1.1.12.3.4.1.1.5ColumnrPDUOutletConfigPowerOffTimeread-writemandatoryThe amount of time (in seconds) the outlet will delay powering off when a command that requires a turn-off delay is issued. Allowed values are: -1 - never powe…
1.3.6.1.4.1.318.1.1.12.3.4.1.1.6ColumnrPDUOutletConfigRebootDurationread-writemandatoryDuring a reboot sequence, power is turned off and then back on. This OID defines the amount of time to wait, in seconds, after turning the power off, at the st…
1.3.6.1.4.1.318.1.1.12.3.4.1.1.7ColumnrPDUOutletConfigOutletBankread-onlymandatoryThe bank associated with this outlet.
1.3.6.1.4.1.318.1.1.12.3.4.2ScalarrPDUOutletConfigMonitoredTableSizeread-onlymandatoryThe size of the Outlet Config Monitored Table
1.3.6.1.4.1.318.1.1.12.3.4.3TablerPDUOutletConfigMonitoredTablenot-accessiblemandatoryAllows for getting/setting of outlet thresholds of an Outlet Monitored Rack PDU.
1.3.6.1.4.1.318.1.1.12.3.4.3.1RowrPDUOutletConfigMonitoredEntrynot-accessiblemandatoryThis gives access to Monitored Outlet entries
1.3.6.1.4.1.318.1.1.12.3.4.3.1.1ColumnrPDUOutletConfigMonitoredIndexread-onlymandatoryThe index to the RACK PDU Phase entry.
1.3.6.1.4.1.318.1.1.12.3.4.3.1.2ColumnrPDUOutletConfigMonitoredNameread-writemandatoryThe name of the Monitored Outlet. The maximum string size is device dependent. An error will be returned if the set request exceeds the max size.
1.3.6.1.4.1.318.1.1.12.3.4.3.1.3ColumnrPDUOutletConfigMonitoredNumberread-onlymandatoryThe outlet number of an Outlet Monitored RACK PDU.
1.3.6.1.4.1.318.1.1.12.3.4.3.1.4ColumnrPDUOutletConfigMonitoredLowLoadThresholdread-writemandatoryA threshold that indicates the power consumption of the load is nearing a low consumption condition. It is represented in Amps. A warning will be issued when t…
1.3.6.1.4.1.318.1.1.12.3.4.3.1.5ColumnrPDUOutletConfigMonitoredNearOverloadThresholdread-writemandatoryA threshold that indicates the power consumption of the load is nearing an overload condition. It is represented in Amps. A warning will be issued when the loa…
1.3.6.1.4.1.318.1.1.12.3.4.3.1.6ColumnrPDUOutletConfigMonitoredOverloadThresholdread-writemandatoryA threshold that indicates the power consumption of the load has entered an overload condition. It is represented in Amps. A warning will be issued when the lo…
1.3.6.1.4.1.318.1.1.12.3.5NoderPDUOutletStatus
1.3.6.1.4.1.318.1.1.12.3.5.1TablerPDUOutletStatusTablenot-accessiblemandatoryAllows for getting of status of individual outlets. The number of entries is contained in the rPDUOutletDevNumCntrlOutlets OID or rPDUOutletDevMonitoredOutlets…
1.3.6.1.4.1.318.1.1.12.3.5.1.1RowrPDUOutletStatusEntrynot-accessiblemandatoryThe outlet to gather status from.
1.3.6.1.4.1.318.1.1.12.3.5.1.1.1ColumnrPDUOutletStatusIndexread-onlymandatoryThe index to the outlet entry.
1.3.6.1.4.1.318.1.1.12.3.5.1.1.2ColumnrPDUOutletStatusOutletNameread-onlymandatoryThe name of the outlet. The maximum string size is device dependent. This OID is provided for informational purposes only.
1.3.6.1.4.1.318.1.1.12.3.5.1.1.3ColumnrPDUOutletStatusOutletPhaseread-onlymandatoryThe phase/s associated with this outlet. For single phase devices, this object will always return phase1(1). For 3-phase devices, this object will return phase…
1.3.6.1.4.1.318.1.1.12.3.5.1.1.4ColumnrPDUOutletStatusOutletStateread-onlymandatoryGetting this variable will return the outlet state. If the outlet is on, the outletStatusOn (1) value will be returned. If the outlet is off, the outletStatusO…
1.3.6.1.4.1.318.1.1.12.3.5.1.1.5ColumnrPDUOutletStatusCommandPendingread-onlymandatoryGetting this variable will return the command pending state of the outlet. If a command is pending on the outlet, the outletStatusCommandPending (1) value will…
1.3.6.1.4.1.318.1.1.12.3.5.1.1.6ColumnrPDUOutletStatusOutletBankread-onlymandatoryThe bank associated with this outlet.
1.3.6.1.4.1.318.1.1.12.3.5.1.1.7ColumnrPDUOutletStatusLoadread-onlymandatoryGetting this OID will return the measured Outlet load for an Outlet Monitored Rack PDU in tenths of Amps. For other models this OID is not supported.
1.3.6.1.4.1.318.1.1.12.3.6NoderPDUOutletBank
1.3.6.1.4.1.318.1.1.12.3.6.1TablerPDUOutletBankTablenot-accessiblemandatoryAllows for management of outlets on a per bank basis.
1.3.6.1.4.1.318.1.1.12.3.6.1.1RowrPDUOutletBankEntrynot-accessiblemandatoryThe bank to manage.
1.3.6.1.4.1.318.1.1.12.3.6.1.1.1ColumnrPDUOutletBankIndexread-onlymandatoryThe index to the Switched Rack PDU bank entry.
1.3.6.1.4.1.318.1.1.12.3.6.1.1.2ColumnrPDUOutletBankOverloadRestrictionread-writemandatoryThis OID controls the behavior of a Switched Rack PDU bank when an overload condition is possible and additional outlets are requested to be turned on. Setting…
1.3.6.1.4.1.318.1.1.12.4NoderPDUPowerSupply
1.3.6.1.4.1.318.1.1.12.4.1NoderPDUPowerSupplyDevice
1.3.6.1.4.1.318.1.1.12.4.1.1ScalarrPDUPowerSupply1Statusread-onlymandatoryGetting this OID will return powerSupply1Ok(1) if power supply 1 is functioning normally. If not functioning normally, this OID will return powerSupply1Failed(…
1.3.6.1.4.1.318.1.1.12.4.1.2ScalarrPDUPowerSupply2Statusread-onlymandatoryGetting this OID will return powerSupply2Ok(1) if power supply 2 is functioning normally. If not functioning normally, this OID will return powerSupply2Failed(…
1.3.6.1.4.1.318.1.1.12.4.1.3ScalarrPDUPowerSupplyAlarmread-onlymandatoryGetting this OID will return powerSupply Alarm
1.3.6.1.4.1.318.1.1.12.5NoderPDUStatus
1.3.6.1.4.1.318.1.1.12.5.1ScalarrPDUStatusBankTableSizeread-onlymandatoryThe size of the Status Bank Table
1.3.6.1.4.1.318.1.1.12.5.2TablerPDUStatusBankTablenot-accessiblemandatoryAllows for getting of status of each Rack PDU Bank
1.3.6.1.4.1.318.1.1.12.5.2.1RowrPDUStatusBankEntrynot-accessiblemandatoryThis gives access to Bank entries
1.3.6.1.4.1.318.1.1.12.5.2.1.1ColumnrPDUStatusBankIndexread-onlymandatoryThe index to the RACK PDU Bank entry.
1.3.6.1.4.1.318.1.1.12.5.2.1.2ColumnrPDUStatusBankNumberread-onlymandatoryGetting this OID will return the bank number.
1.3.6.1.4.1.318.1.1.12.5.2.1.3ColumnrPDUStatusBankStateread-onlymandatoryGetting this OID will return the bank load state. bankLoadNormal(1) indicates that the bank is operating properly within the rPDULoadBankConfigLowLoadThreshold…
1.3.6.1.4.1.318.1.1.12.5.3ScalarrPDUStatusPhaseTableSizeread-onlymandatoryThe size of the Status Phase Table
1.3.6.1.4.1.318.1.1.12.5.4TablerPDUStatusPhaseTablenot-accessiblemandatoryAllows for getting of status of each Rack PDU Phase
1.3.6.1.4.1.318.1.1.12.5.4.1RowrPDUStatusPhaseEntrynot-accessiblemandatoryThis gives access to Phase entries
1.3.6.1.4.1.318.1.1.12.5.4.1.1ColumnrPDUStatusPhaseIndexread-onlymandatoryThe index to the RACK PDU Phase entry.
1.3.6.1.4.1.318.1.1.12.5.4.1.2ColumnrPDUStatusPhaseNumberread-onlymandatoryGetting this OID will return the phase number.
1.3.6.1.4.1.318.1.1.12.5.4.1.3ColumnrPDUStatusPhaseStateread-onlymandatoryGetting this OID will return the Phase load state. phaseLoadNormal(1) indicates that the Phase is operating properly within the rPDULoadPhaseConfigLowLoadThres…
1.3.6.1.4.1.318.1.1.12.5.5ScalarrPDUStatusOutletTableSizeread-onlymandatoryThe size of the Status Outlet Table
1.3.6.1.4.1.318.1.1.12.5.6TablerPDUStatusOutletTablenot-accessiblemandatoryAllows for getting of status of each Outlet of an Outlet Monitored Rack PDU.
1.3.6.1.4.1.318.1.1.12.5.6.1RowrPDUStatusOutletEntrynot-accessiblemandatoryThis gives access to Outlet entries
1.3.6.1.4.1.318.1.1.12.5.6.1.1ColumnrPDUStatusOutletIndexread-onlymandatoryThe index to the RACK PDU Outlet entry.
1.3.6.1.4.1.318.1.1.12.5.6.1.2ColumnrPDUStatusOutletNumberread-onlymandatoryGetting this OID will return the Outlet number.
1.3.6.1.4.1.318.1.1.12.5.6.1.3ColumnrPDUStatusOutletStateread-onlymandatoryGetting this OID will return the Outlet load state. outletLoadNormal(1) indicates that the Outlet is operating properly within the rPDUOutletConfigMonitoredLow…
1.3.6.1.4.1.318.1.1.13NodeairConditioners
1.3.6.1.4.1.318.1.1.13.1NodeairFM
1.3.6.1.4.1.318.1.1.13.1.1NodeairFMIdent
1.3.6.1.4.1.318.1.1.13.1.1.1ScalarairFMIdentNameread-writemandatoryA character string identifying the device.
1.3.6.1.4.1.318.1.1.13.1.1.2ScalarairFMIdentTableSizeread-onlymandatoryThe number of entries in the airFMIdentTable.
1.3.6.1.4.1.318.1.1.13.1.1.3TableairFMIdentTablenot-accessiblemandatoryAllows for getting identification information from each module in the system.
1.3.6.1.4.1.318.1.1.13.1.1.3.1RowairFMIdentEntrynot-accessiblemandatoryThe module to get information from.
1.3.6.1.4.1.318.1.1.13.1.1.3.1.1ColumnairFMIdentModuleIndexread-onlymandatoryThe index of the module information.
1.3.6.1.4.1.318.1.1.13.1.1.3.1.2ColumnairFMIdentModuleModelNumberread-onlymandatoryA character string identifying the model number.
1.3.6.1.4.1.318.1.1.13.1.1.3.1.3ColumnairFMIdentModuleDateOfMfgread-onlymandatoryA character string identifying the manufacture date.
1.3.6.1.4.1.318.1.1.13.1.1.3.1.4ColumnairFMIdentModuleSerialNumberread-onlymandatoryA character string identifying the unit serial number.
1.3.6.1.4.1.318.1.1.13.1.1.3.1.5ColumnairFMIdentModuleFirmwareRevread-onlymandatoryA character string identifying the firmware revision.
1.3.6.1.4.1.318.1.1.13.1.1.3.1.6ColumnairFMIdentModuleHardwareRevread-onlymandatoryA character string identifying the hardware revision.
1.3.6.1.4.1.318.1.1.13.1.1.4ScalarairFMIdentLocationread-writemandatoryA character string identifying the location of the device.
1.3.6.1.4.1.318.1.1.13.1.1.5ScalarairFMIdentContactread-writemandatoryA character string identifying the person to contact regarding the device.
1.3.6.1.4.1.318.1.1.13.1.2NodeairFMStatus
1.3.6.1.4.1.318.1.1.13.1.2.1ScalarairFMStatusSystemOnread-onlymandatoryThe operating state of the system. This OID has been deprecated in favor of airFMGroupSysStatus.
1.3.6.1.4.1.318.1.1.13.1.2.2ScalarairFMStatusSystemAverageRetTempCread-onlymandatoryThe system average return air temperature in tenths of degrees Celsius. This OID has been deprecated in favor of airFMSysAvgReturnTempC.
1.3.6.1.4.1.318.1.1.13.1.2.3ScalarairFMStatusSystemAverageRetTempFread-onlymandatoryThe system average return air temperature in tenths of degrees Fahrenheit. This OID has been deprecated in favor of airFMSysAvgReturnTempF.
1.3.6.1.4.1.318.1.1.13.1.2.4ScalarairFMStatusSystemAverageRetHumread-onlymandatoryThe system average return air humidity in tenths of percent RH. This OID has been deprecated in favor of airFMSysAvgReturnHum.
1.3.6.1.4.1.318.1.1.13.1.2.5ScalarairFMStatusSystemActionTempCread-onlymandatoryThe system action air temperature in tenths of degrees Celsius. This OID has been deprecated in favor of airFMSysCtrlTempC.
1.3.6.1.4.1.318.1.1.13.1.2.6ScalarairFMStatusSystemActionTempFread-onlymandatoryThe system action air temperature in tenths of degrees Fahrenheit. This OID has been deprecated in favor of airFMSysCtrlTempF.
1.3.6.1.4.1.318.1.1.13.1.2.7ScalarairFMStatusSystemActionHumread-onlymandatoryThe system action air humidity in tenths of percent RH. This OID has been deprecated in favor of airFMSysCtrlHum.
1.3.6.1.4.1.318.1.1.13.1.2.8ScalarairFMStatusSystemRemoteHighTempCread-onlymandatoryThe system remote high air temperature in tenths of degrees Celsius. This OID has been deprecated in favor of airFMSysMaxRemoteTempC.
1.3.6.1.4.1.318.1.1.13.1.2.9ScalarairFMStatusSystemRemoteHighTempFread-onlymandatoryThe system remote high air temperature in tenths of degrees Fahrenheit. This OID has been deprecated in favor of airFMSysMaxRemoteTempF.
1.3.6.1.4.1.318.1.1.13.1.2.10ScalarairFMStatusSystemRemoteAvgTempCread-onlymandatoryThe system remote average air temperature in tenths of degrees Celsius. This OID has been deprecated in favor of airFMSysAvgRemoteTempC.
1.3.6.1.4.1.318.1.1.13.1.2.11ScalarairFMStatusSystemRemoteAvgTempFread-onlymandatoryThe system remote average air temperature in tenths of degrees Fahrenheit. This OID has been deprecated in favor of airFMSysAvgRemoteTempF.
1.3.6.1.4.1.318.1.1.13.1.2.12ScalarairFMStatusSystemRemoteAvgHumread-onlymandatoryThe system remote average air humidity in tenths of percent RH. This OID has been deprecated in favor of airFMSysAvgRemoteHum.
1.3.6.1.4.1.318.1.1.13.1.2.13ScalarairFMStatusSystemRemoteLowTempCread-onlymandatoryThe system remote low air temperature in tenths of degrees Celsius. This OID has been deprecated in favor of airFMSysMinRemoteTempC.
1.3.6.1.4.1.318.1.1.13.1.2.14ScalarairFMStatusSystemRemoteLowTempFread-onlymandatoryThe system remote low air temperature in tenths of degrees Fahrenheit. This OID has been deprecated in favor of airFMSysMinRemoteTempF.
1.3.6.1.4.1.318.1.1.13.1.2.15ScalarairFMStatusSystemCoolingEnabledread-onlymandatoryThe state of the system cooling function enable. This OID has been deprecated in favor of airFMSysCoolState.
1.3.6.1.4.1.318.1.1.13.1.2.16ScalarairFMStatusSystemReheatingEnabledread-onlymandatoryThe state of the system reheating function enable. This OID has been deprecated in favor of airFMSysReheatState.
1.3.6.1.4.1.318.1.1.13.1.2.17ScalarairFMStatusSystemHumidifyEnabledread-onlymandatoryThe state of the system humidify function enable. This OID has been deprecated in favor of airFMSysHumState.
1.3.6.1.4.1.318.1.1.13.1.2.18ScalarairFMStatusSystemDehumidifyEnabledread-onlymandatoryThe state of the system dehumidify function enable. This OID has been deprecated in favor of airFMSysDehumState.
1.3.6.1.4.1.318.1.1.13.1.2.19ScalarairFMStatusModuleTableSizeread-onlymandatoryThe number of entries in the airFMStatusModuleTable.
1.3.6.1.4.1.318.1.1.13.1.2.20TableairFMStatusModuleTablenot-accessiblemandatoryAllows for getting information from each module in the system.
1.3.6.1.4.1.318.1.1.13.1.2.20.1RowairFMStatusModuleEntrynot-accessiblemandatoryThe module to get status from.
1.3.6.1.4.1.318.1.1.13.1.2.20.1.1ColumnairFMStatusModuleIndexread-onlymandatoryThe index of the module information.
1.3.6.1.4.1.318.1.1.13.1.2.20.1.2ColumnairFMStatusModuleOutputCapacityread-onlymandatoryThe module output capacity in kilowatts. This OID has been deprecated in favor of airFMModOutputCapacity.
1.3.6.1.4.1.318.1.1.13.1.2.20.1.3ColumnairFMStatusModuleSupplyTempCread-onlymandatoryThe module supply air temperature in tenths of degrees Celsius. This OID has been deprecated in favor of airFMModSupplyTempC.
1.3.6.1.4.1.318.1.1.13.1.2.20.1.4ColumnairFMStatusModuleSupplyTempFread-onlymandatoryThe module supply air temperature in tenths of degrees Fahrenheit. This OID has been deprecated in favor of airFMModSupplyTempF.
1.3.6.1.4.1.318.1.1.13.1.2.20.1.5ColumnairFMStatusModuleSupplyHumread-onlymandatoryThe module supply air humidity in tenths of percent RH. This OID has been deprecated in favor of airFMModSupplyHum.
1.3.6.1.4.1.318.1.1.13.1.2.20.1.6ColumnairFMStatusModuleReturnTempCread-onlymandatoryThe module return air temperature in tenths of degrees Celsius. This OID has been deprecated in favor of airFMModReturnTempC.
1.3.6.1.4.1.318.1.1.13.1.2.20.1.7ColumnairFMStatusModuleReturnTempFread-onlymandatoryThe module return air temperature in tenths of degrees Fahrenheit. This OID has been deprecated in favor of airFMModReturnTempF.
1.3.6.1.4.1.318.1.1.13.1.2.20.1.8ColumnairFMStatusModuleReturnHumread-onlymandatoryThe module return air humidity in tenths of percent RH. This OID has been deprecated in favor of airFMModReturnHum.
1.3.6.1.4.1.318.1.1.13.1.3NodeairFMGroup
1.3.6.1.4.1.318.1.1.13.1.3.1ScalarairFMGroupSysStatusread-onlymandatoryThe status of this system within the group.
1.3.6.1.4.1.318.1.1.13.1.3.2ScalarairFMGroupSysRuntimeread-onlymandatoryThe number of hours the system has been running.
1.3.6.1.4.1.318.1.1.13.1.3.3ScalarairFMGroupSysRoleread-onlymandatoryThe role of this system within the group.
1.3.6.1.4.1.318.1.1.13.1.3.4NodeairFMGroupSysRoles
1.3.6.1.4.1.318.1.1.13.1.3.4.1ScalarairFMGroupSysRolesTableSizeread-onlymandatoryThe number of entries in the airFMGroupSysRolesTable.
1.3.6.1.4.1.318.1.1.13.1.3.4.2TableairFMGroupSysRolesTablenot-accessiblemandatoryAllows for getting information from each system in the group.
1.3.6.1.4.1.318.1.1.13.1.3.4.2.1RowairFMGroupSysRolesEntrynot-accessiblemandatoryThe system to get status from.
1.3.6.1.4.1.318.1.1.13.1.3.4.2.1.1ColumnairFMGroupSysIndexread-onlymandatoryThe index of the system information.
1.3.6.1.4.1.318.1.1.13.1.3.4.2.1.2ColumnairFMGroupSysRoleStatusread-onlymandatoryThe present mode of the System.
1.3.6.1.4.1.318.1.1.13.1.3.4.2.1.3ColumnairFMGroupSysPresentRoleread-onlymandatoryThe present role of the System in a Group.
1.3.6.1.4.1.318.1.1.13.1.3.4.2.1.4ColumnairFMGroupSysManualRoleSettingread-writemandatoryThe manual role setting of the System in a Group. Only applies if Role Assignment Method is set to static (Manually Assigned Roles).
1.3.6.1.4.1.318.1.1.13.1.3.4.2.1.5ColumnairFMGroupSysRunHoursread-onlymandatoryThe total number of hours the System has been contributing to environmental control.
1.3.6.1.4.1.318.1.1.13.1.3.4.2.1.6ColumnairFMGroupSysCommread-onlymandatoryIndicates whether a system is communicating with the other Systems in the Group.
1.3.6.1.4.1.318.1.1.13.1.3.4.2.1.7ColumnairFMGroupSysIPAddressread-onlymandatoryThe IP Address of the System.
1.3.6.1.4.1.318.1.1.13.1.3.4.3ScalarairFMGroupSysRoleAssignmentread-writemandatoryThe method used to assign roles (i.e. Primary, Backup) to the Systems in a Group. staticManual: Manually assign Primary or Backup to regulate run hours across …
1.3.6.1.4.1.318.1.1.13.1.3.4.4ScalarairFMGroupAutoRoleNumPrimaryread-writemandatoryThe number of Systems assigned the 'primary' role in this Group. Only applies if Role Assignment Method is set to dynamic (Automatic Run Hour Balancing).
1.3.6.1.4.1.318.1.1.13.1.3.5NodeairFMGroupCfg
1.3.6.1.4.1.318.1.1.13.1.3.5.1ScalarairFMGroupCfgNameread-writemandatoryA character string identifying the group name.
1.3.6.1.4.1.318.1.1.13.1.3.5.2ScalarairFMGroupCfgNumSystemsread-writemandatoryThe number of Systems in this Group.
1.3.6.1.4.1.318.1.1.13.1.3.5.3ScalarairFMGroupCfgIdleBlowerread-writemandatoryBlower behavior for backup Systems and Systems that have entered a failure mode.
1.3.6.1.4.1.318.1.1.13.1.3.5.4ScalarairFMGroupCfgShutdownSmokeread-writemandatoryIf enabled, all Systems in the Group will shut down if smoke is detected.
1.3.6.1.4.1.318.1.1.13.1.3.5.5ScalarairFMGroupCfgShutdownFireread-writemandatoryIf enabled, all Systems in the Group will shut down if fire is detected.
1.3.6.1.4.1.318.1.1.13.1.3.5.6ScalarairFMGroupCfgFailoverCommLossread-writemandatoryFailover on Comm Loss enables an available backup System to run in place of a System that has lost communication with the Group.
1.3.6.1.4.1.318.1.1.13.1.3.5.7ScalarairFMGroupCfgDmdFightStatusread-onlymandatoryDemand Fighting and Setpoint Sharing are automatically enabled when a System is responding to a Load Sharing Request.
1.3.6.1.4.1.318.1.1.13.1.3.5.8ScalarairFMGroupCfgDmdFightSettingread-writemandatoryDemand Fighting prevents a System from engaging reheat in a Group where any System is cooling.
1.3.6.1.4.1.318.1.1.13.1.3.5.9ScalarairFMGroupCfgSetpointShareStatusread-onlymandatoryDemand Fighting and Setpoint Sharing are automatically enabled when a System is responding to Load Sharing Request.
1.3.6.1.4.1.318.1.1.13.1.3.5.10ScalarairFMGroupCfgSetpointShareSettingread-writemandatoryAll Systems in the Group use the same setpoints.
1.3.6.1.4.1.318.1.1.13.1.3.5.11ScalarairFMGroupCfgResetFieldServiceDefaultsread-writemandatorySetting this OID to reset(2) will reset all Group parameters, which can only be edited by a field service engineer, to their factory default values. Getting th…
1.3.6.1.4.1.318.1.1.13.1.3.6NodeairFMGroupLoadShare
1.3.6.1.4.1.318.1.1.13.1.3.6.1ScalarairFMGroupLoadShareCoolRequestsread-writemandatorySystems that are cooling may request assistance from other Systems in the Group.
1.3.6.1.4.1.318.1.1.13.1.3.6.2ScalarairFMGroupLoadShareCoolThreshCread-writemandatoryTemperature threshold at which a System will generate a load sharing request for cooling. Measured in tenths of degrees Celsius.
1.3.6.1.4.1.318.1.1.13.1.3.6.3ScalarairFMGroupLoadShareCoolThreshFread-writemandatoryTemperature threshold at which a System will generate a load sharing request for cooling. Measured in tenths of degrees Fahrenheit.
1.3.6.1.4.1.318.1.1.13.1.3.6.4ScalarairFMGroupLoadShareReheatRequestsread-writemandatorySystems that are reheating may request assistance from other Systems in the Group.
1.3.6.1.4.1.318.1.1.13.1.3.6.5ScalarairFMGroupLoadShareReheatThreshCread-writemandatoryTemperature threshold at which a System will generate a load sharing request for reheating. Measured in tenths of degrees Celsius.
1.3.6.1.4.1.318.1.1.13.1.3.6.6ScalarairFMGroupLoadShareReheatThreshFread-writemandatoryTemperature threshold at which a System will generate a load sharing request for reheating. Measured in tenths of degrees Fahrenheit.
1.3.6.1.4.1.318.1.1.13.1.3.6.7ScalarairFMGroupLoadShareHumRequestsread-writemandatorySystems that are humidifying may request humidification assistance from other Systems in the Group.
1.3.6.1.4.1.318.1.1.13.1.3.6.8ScalarairFMGroupLoadShareHumThreshread-writemandatoryHumidity threshold at which a System will generate a load sharing request for humidification. Measured in tenths of percent relative humidity.
1.3.6.1.4.1.318.1.1.13.1.3.6.9ScalarairFMGroupLoadShareDehumRequestsread-writemandatorySystems that are dehumidifying may request assistance from other Systems in the Group.
1.3.6.1.4.1.318.1.1.13.1.3.6.10ScalarairFMGroupLoadShareDehumThreshread-writemandatoryHumidity threshold at which a System will generate a load sharing request for dehumidification. Measured in tenths of percent relative humidity.
1.3.6.1.4.1.318.1.1.13.1.3.7NodeairFMGroupFailover
1.3.6.1.4.1.318.1.1.13.1.3.7.1NodeairFMGroupFailoverSys
1.3.6.1.4.1.318.1.1.13.1.3.7.1.1ScalarairFMGroupFailoverSysAnyMinorAlarmread-writemandatoryEnabling this OID will cause the system to enter a failure state if any minor system alarm is active. Once in the failure state, environmental control ceases f…
1.3.6.1.4.1.318.1.1.13.1.3.7.1.2ScalarairFMGroupFailoverSysAnyMajorAlarmread-writemandatoryEnabling this OID will cause the system to enter a failure state if any major system alarm is active. Once in the failure state, environmental control ceases f…
1.3.6.1.4.1.318.1.1.13.1.3.7.1.3ScalarairFMGroupFailoverSysHighEnvTempread-writemandatoryEnabling this OID will cause the system to enter a failure state if the high environmental temperature alarm is active. Once in the failure state, environmenta…
1.3.6.1.4.1.318.1.1.13.1.3.7.1.4ScalarairFMGroupFailoverSysLowEnvTempread-writemandatoryEnabling this OID will cause the system to enter a failure state if the low environmental temperature alarm is active. Once in the failure state, environmental…
1.3.6.1.4.1.318.1.1.13.1.3.7.1.5ScalarairFMGroupFailoverSysHighEnvHumread-writemandatoryEnabling this OID will cause the system to enter a failure state if the high environmental humidity alarm is active. Once in the failure state, environmental c…
1.3.6.1.4.1.318.1.1.13.1.3.7.1.6ScalarairFMGroupFailoverSysLowEnvHumread-writemandatoryEnabling this OID will cause the system to enter a failure state if the low environmental humidity alarm is active. Once in the failure state, environmental co…
1.3.6.1.4.1.318.1.1.13.1.3.7.1.7ScalarairFMGroupFailoverSysFireAlarmread-writemandatoryEnabling this OID will cause the system to enter a failure state if the fire alarm is active. Once in the failure state, environmental control ceases for the s…
1.3.6.1.4.1.318.1.1.13.1.3.7.1.8ScalarairFMGroupFailoverSysSmokeAlarmread-writemandatoryEnabling this OID will cause the system to enter a failure state if the smoke alarm is active. Once in the failure state, environmental control ceases for the …
1.3.6.1.4.1.318.1.1.13.1.3.7.1.9ScalarairFMGroupFailoverSysCommLostread-writemandatoryEnabling this OID will cause the system to enter a failure state if the system has lost comm. Once in the failure state, environmental control ceases for the s…
1.3.6.1.4.1.318.1.1.13.1.3.7.1.10ScalarairFMGroupFailoverSysSupplySensorFailread-writemandatoryEnabling this OID will cause the system to enter a failure state if the supply sensor has failed. Once in the failure state, environmental control ceases for t…
1.3.6.1.4.1.318.1.1.13.1.3.7.1.11ScalarairFMGroupFailoverSysReturnSensorFailread-writemandatoryEnabling this OID will cause the system to enter a failure state if the return sensor has failed. Once in the failure state, environmental control ceases for t…
1.3.6.1.4.1.318.1.1.13.1.3.7.1.12ScalarairFMGroupFailoverSysPrimarySensorFailread-writemandatoryEnabling this OID will cause the system to enter a failure state if the primary sensor has failed. Once in the failure state, environmental control ceases for …
1.3.6.1.4.1.318.1.1.13.1.3.7.1.13ScalarairFMGroupFailoverSysSecondarySensorFailread-writemandatoryEnabling this OID will cause the system to enter a failure state if the secondary sensor has failed. Once in the failure state, environmental control ceases fo…
1.3.6.1.4.1.318.1.1.13.1.3.7.1.14ScalarairFMGroupFailoverSysNoSensorsAvailableread-writemandatoryEnabling this OID will cause the system to enter a failure state if no sensors are available. Once in the failure state, environmental control ceases for the s…
1.3.6.1.4.1.318.1.1.13.1.3.7.2NodeairFMGroupFailoverMod
1.3.6.1.4.1.318.1.1.13.1.3.7.2.1ScalarairFMGroupFailoverModMaintRequiredread-writemandatoryEnabling this OID will cause the system to enter a failure state if maintenance is required on a module. Once in the failure state, environmental control cease…
1.3.6.1.4.1.318.1.1.13.1.3.7.2.2ScalarairFMGroupFailoverModCoolFailread-writemandatoryEnabling this OID will cause the system to enter a failure state if cooling has failed on a module. Once in the failure state, environmental control ceases for…
1.3.6.1.4.1.318.1.1.13.1.3.7.2.3ScalarairFMGroupFailoverModHumFailread-writemandatoryEnabling this OID will cause the system to enter a failure state if the humidifier has failed on a module. Once in the failure state, environmental control cea…
1.3.6.1.4.1.318.1.1.13.1.3.7.2.4ScalarairFMGroupFailoverModBlwrCntrl1Failread-writemandatoryEnabling this OID will cause the system to enter a failure state if blower controller 1 has failed on a module. Once in the failure state, environmental contro…
1.3.6.1.4.1.318.1.1.13.1.3.7.2.5ScalarairFMGroupFailoverModBlwrCntrl2Failread-writemandatoryEnabling this OID will cause the system to enter a failure state if blower controller 2 has failed on a module. Once in the failure state, environmental contro…
1.3.6.1.4.1.318.1.1.13.1.3.7.2.6ScalarairFMGroupFailoverModHighFilterDPread-writemandatoryEnabling this OID will cause the system to enter a failure state if a high filter differential pressure is present on a module. Once in the failure state, envi…
1.3.6.1.4.1.318.1.1.13.1.3.7.2.7ScalarairFMGroupFailoverModHighSupplyTempread-writemandatoryEnabling this OID will cause the system to enter a failure state if a high supply temperature is active on a module. Once in the failure state, environmental c…
1.3.6.1.4.1.318.1.1.13.1.3.7.2.8ScalarairFMGroupFailoverModLowSupplyTempread-writemandatoryEnabling this OID will cause the system to enter a failure state if a low supply temperature is active on a module. Once in the failure state, environmental co…
1.3.6.1.4.1.318.1.1.13.1.3.7.2.9ScalarairFMGroupFailoverModLossOrLowAirFlowread-writemandatoryEnabling this OID will cause the system to enter a failure state if there is a loss of air flow or low air flow on a module. Once in the failure state, environ…
1.3.6.1.4.1.318.1.1.13.1.3.7.2.10ScalarairFMGroupFailoverModHumReplaceCylinderread-writemandatoryEnabling this OID will cause the system to enter a failure state if a humidifier needs its cylinder replaced on a module. Once in the failure state, environmen…
1.3.6.1.4.1.318.1.1.13.1.3.7.2.11ScalarairFMGroupFailoverModAirBlockInterlockOpenread-writemandatoryEnabling this OID will cause the system to enter a failure state if the air block interlock is open on a module. Once in the failure state, environmental contr…
1.3.6.1.4.1.318.1.1.13.1.3.7.2.12ScalarairFMGroupFailoverModWaterDetectedread-writemandatoryEnabling this OID will cause the system to enter a failure state if water is detected by a module. Once in the failure state, environmental control ceases for …
1.3.6.1.4.1.318.1.1.13.1.3.7.2.13ScalarairFMGroupFailoverModCondensatePumpFailread-writemandatoryEnabling this OID will cause the system to enter a failure state if the condensate pump has failed in a module. Once in the failure state, environmental contro…
1.3.6.1.4.1.318.1.1.13.1.4NodeairFMSystem
1.3.6.1.4.1.318.1.1.13.1.4.1NodeairFMSysStatus
1.3.6.1.4.1.318.1.1.13.1.4.1.1ScalarairFMSysNumberread-onlymandatoryThe number of the system within the group. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
1.3.6.1.4.1.318.1.1.13.1.4.1.2ScalarairFMSysPresentStatusread-onlymandatoryThe present mode of the System. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
1.3.6.1.4.1.318.1.1.13.1.4.1.3ScalarairFMSysPresentRoleread-onlymandatoryThe present role of the System in the Group. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
1.3.6.1.4.1.318.1.1.13.1.4.1.4ScalarairFMSysRunHoursread-onlymandatoryThe total number of hours the System has been contributing to environmental control. A value of -2147483648 indicates that this OID does not apply to this devi…
1.3.6.1.4.1.318.1.1.13.1.4.1.5ScalarairFMSysCoilFluidTempCread-onlymandatoryThe temperature of the coolant at the fluid coil inlet. Measured in degrees Celsius. A value of -2147483648 indicates that this OID does not apply to this devi…
1.3.6.1.4.1.318.1.1.13.1.4.1.6ScalarairFMSysCoilFluidTempFread-onlymandatoryThe temperature of the coolant at the fluid coil inlet. Measured in degrees Fahrenheit. A value of -2147483648 indicates that this OID does not apply to this d…
1.3.6.1.4.1.318.1.1.13.1.4.1.7ScalarairFMSysHotWaterTempCread-onlymandatoryThe hot water temperature. Measured in degrees Celsius. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration.
1.3.6.1.4.1.318.1.1.13.1.4.1.8ScalarairFMSysHotWaterTempFread-onlymandatoryThe hot water temperature. Measured in degrees Fahrenheit. A value of -2147483648 indicates that this OID does not apply to this device due to its configuratio…
1.3.6.1.4.1.318.1.1.13.1.4.1.9ScalarairFMSysAvgReturnTempCread-onlymandatoryThe average return temperature calculated from all present modules. Measured in tenths of degrees Celsius. A value of -2147483648 indicates that this OID does …
1.3.6.1.4.1.318.1.1.13.1.4.1.10ScalarairFMSysAvgReturnTempFread-onlymandatoryThe average return temperature calculated from all present modules. Measured in tenths of degrees Fahrenheit. A value of -2147483648 indicates that this OID do…
1.3.6.1.4.1.318.1.1.13.1.4.1.11ScalarairFMSysAvgReturnHumread-onlymandatoryThe average return humidity calculated from all present modules. Measured in tenths of percent RH. A value of -2147483648 indicates that this OID does not appl…
1.3.6.1.4.1.318.1.1.13.1.4.1.12ScalarairFMSysAvgRemoteTempCread-onlymandatoryThe average temperature calculated from all operational remote sensors. Measured in tenths of degrees Celsius. A value of -2147483648 indicates that this OID d…
1.3.6.1.4.1.318.1.1.13.1.4.1.13ScalarairFMSysAvgRemoteTempFread-onlymandatoryThe average temperature calculated from all operational remote sensors. Measured in tenths of degrees Fahrenheit. A value of -2147483648 indicates that this OI…
1.3.6.1.4.1.318.1.1.13.1.4.1.14ScalarairFMSysAvgRemoteHumread-onlymandatoryThe average return humidity calculated from all present modules. Measured in tenths of percent RH. A value of -2147483648 indicates that this OID does not appl…
1.3.6.1.4.1.318.1.1.13.1.4.1.15ScalarairFMSysMaxRemoteTempCread-onlymandatoryThe maximum temperature reading from all operational remote sensors. Measured in tenths of degrees Celsius. A value of -2147483648 indicates that this OID does…
1.3.6.1.4.1.318.1.1.13.1.4.1.16ScalarairFMSysMaxRemoteTempFread-onlymandatoryThe maximum temperature reading from all operational remote sensors. Measured in tenths of degrees Fahrenheit. A value of -2147483648 indicates that this OID d…
1.3.6.1.4.1.318.1.1.13.1.4.1.17ScalarairFMSysMinRemoteTempCread-onlymandatoryThe minimum temperature reading from all operational remote sensors. Measured in tenths of degrees Celsius. A value of -2147483648 indicates that this OID does…
1.3.6.1.4.1.318.1.1.13.1.4.1.18ScalarairFMSysMinRemoteTempFread-onlymandatoryThe minimum temperature reading from all operational remote sensors. Measured in tenths of degrees Fahrenheit. A value of -2147483648 indicates that this OID d…
1.3.6.1.4.1.318.1.1.13.1.4.1.19ScalarairFMSysTempCtrlMethodread-onlymandatoryThe method of environment temperature control selected to regulate the temperature. A value of notApplicable indicates that this OID does not apply to this dev…
1.3.6.1.4.1.318.1.1.13.1.4.1.20ScalarairFMSysActualTempCtrlMethodread-onlymandatoryThe actual method of environment temperature control being used to regulate the temperature. A value of notApplicable indicates that this OID does not apply to…
1.3.6.1.4.1.318.1.1.13.1.4.1.21ScalarairFMSysHumCtrlMethodread-onlymandatoryThe method of environment humidity control selected to regulate the humidity. A value of notApplicable indicates that this OID does not apply to this device du…
1.3.6.1.4.1.318.1.1.13.1.4.1.22ScalarairFMSysActualHumCtrlMethodread-onlymandatoryThe actual method of environment humidity control being used to regulate the humidity. A value of notApplicable indicates that this OID does not apply to this …
1.3.6.1.4.1.318.1.1.13.1.4.1.23ScalarairFMSysCtrlTempCread-onlymandatoryThe system environmental control air temperature from the sensor denoted by airFMSysActualTempCtrl. Measured in tenths of degrees Celsius. A value of -21474836…
1.3.6.1.4.1.318.1.1.13.1.4.1.24ScalarairFMSysCtrlTempFread-onlymandatoryThe system environmental control air temperature from the sensor denoted by airFMSysActualTempCtrl. Measured in tenths of degrees Fahrenheit. A value of -21474…
1.3.6.1.4.1.318.1.1.13.1.4.1.25ScalarairFMSysCtrlHumread-onlymandatoryThe system environmental control air humidity from the sensor denoted by airFMSysActualHumCtrl. Measured in percent relative humidity. A value of -2147483648 i…
1.3.6.1.4.1.318.1.1.13.1.4.2NodeairFMSysDemands
1.3.6.1.4.1.318.1.1.13.1.4.2.1ScalarairFMSysDXCoolingDmdread-onlymandatoryThe direct expansion cooling output demanded by the System. Measured in percent. A value of -2147483648 indicates that this OID does not apply to this device d…
1.3.6.1.4.1.318.1.1.13.1.4.2.2ScalarairFMSysDXDehumDmdread-onlymandatoryThe direct expansion dehumidification output demanded by the System. Measured in percent. A value of -2147483648 indicates that this OID does not apply to this…
1.3.6.1.4.1.318.1.1.13.1.4.2.3ScalarairFMSysDXActualCoolDehumread-onlymandatoryThe direct expansion cooling or dehumidification output measured by the System. Measured in percent. A value of -2147483648 indicates that this OID does not ap…
1.3.6.1.4.1.318.1.1.13.1.4.2.4ScalarairFMSysCoilFluidCoolDmdread-onlymandatoryThe fluid coil cooling output demanded by the System. Measured in percent. A value of -2147483648 indicates that this OID does not apply to this device due to …
1.3.6.1.4.1.318.1.1.13.1.4.2.5ScalarairFMSysCoilFluidDehumDmdread-onlymandatoryThe fluid coil dehumidification output demanded by the System. Measured in percent. A value of -2147483648 indicates that this OID does not apply to this devic…
1.3.6.1.4.1.318.1.1.13.1.4.2.6ScalarairFMSysCoilFluidActualCoolDehumread-onlymandatoryThe fluid coil cooling or dehumidification output measured by the System. Measured in percent. A value of -2147483648 indicates that this OID does not apply to…
1.3.6.1.4.1.318.1.1.13.1.4.2.7ScalarairFMSysElectricReheatDmdread-onlymandatoryThe electric reheating output demanded by the System. Measured in percent. A value of -2147483648 indicates that this OID does not apply to this device due to …
1.3.6.1.4.1.318.1.1.13.1.4.2.8ScalarairFMSysActualElectricReheatread-onlymandatoryThe electric reheating output of the System. Measured in percent. A value of -2147483648 indicates that this OID does not apply to this device due to its confi…
1.3.6.1.4.1.318.1.1.13.1.4.2.9ScalarairFMSysSteamHotGasReheatDmdread-onlymandatoryThe steam, hot water, or hot gas reheating output demanded by the System. A value of notApplicable indicates that this OID does not apply to this device due to…
1.3.6.1.4.1.318.1.1.13.1.4.2.10ScalarairFMSysActualSteamHotGasReheatread-onlymandatoryThe steam, hot water, or hot gas reheating output of the System. A value of notApplicable indicates that this OID does not apply to this device due to its conf…
1.3.6.1.4.1.318.1.1.13.1.4.2.11ScalarairFMSysSteamElectrodeHumDmdread-onlymandatoryThe steam electrode humidification output demanded by the System. Measured in percent. A value of -2147483648 indicates that this OID does not apply to this de…
1.3.6.1.4.1.318.1.1.13.1.4.2.12ScalarairFMSysActualSteamElectrodeHumread-onlymandatoryThe average steam electrode humidification output measured for the Modules in the System. Measured in percent. A value of -2147483648 indicates that this OID d…
1.3.6.1.4.1.318.1.1.13.1.4.2.13ScalarairFMSysSteamHumDmdread-onlymandatoryThe steam humidification output demanded by the System. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
1.3.6.1.4.1.318.1.1.13.1.4.2.14ScalarairFMSysActualSteamHumread-onlymandatoryThe steam humidification output for the System. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
1.3.6.1.4.1.318.1.1.13.1.4.3NodeairFMSysSetup
1.3.6.1.4.1.318.1.1.13.1.4.3.1ScalarairFMSysNumModulesread-onlymandatoryThe number of Modules in this System. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
1.3.6.1.4.1.318.1.1.13.1.4.3.2ScalarairFMSysNumPCIOMsread-onlymandatoryThe number of Programmable Customer Input/Output Modules (PCIOMs) installed in the Main Module of this System. Each PCIOM adds four input contacts and four out…
1.3.6.1.4.1.318.1.1.13.1.4.3.3ScalarairFMSysMainsVltread-onlymandatoryThe mains voltage for the Modules in this System. A value of N/A indicates that this OID does not apply to this device due to its configuration.
1.3.6.1.4.1.318.1.1.13.1.4.3.4ScalarairFMSysUPSVltread-onlymandatoryThe UPS voltage for the Modules in this System. A value of N/A indicates that this OID does not apply to this device due to its configuration.
1.3.6.1.4.1.318.1.1.13.1.4.3.5ScalarairFMSysCoilCfgread-onlymandatoryThe type of cooling coils installed in the Modules in this System: DX coil, DX and MultiCool (chilled water) coils, DX and Economizer coils, or only a Chilled …
1.3.6.1.4.1.318.1.1.13.1.4.3.6ScalarairFMSysRefrigTyperead-onlymandatoryThe type of refrigerant used by each compressor in the system. A value of notApplicable indicates that this OID does not apply to this device due to its config…
1.3.6.1.4.1.318.1.1.13.1.4.3.7ScalarairFMSysHeatRejectionread-onlymandatoryThe method the Modules in this System use to transfer heat away from the refrigerant. A value of notApplicable indicates that this OID does not apply to this d…
1.3.6.1.4.1.318.1.1.13.1.4.3.8ScalarairFMSysDischAirPtrnread-onlymandatoryThe discharge air pattern for the Modules in this System. A value of notApplicable indicates that this OID does not apply to this device due to its configurati…
1.3.6.1.4.1.318.1.1.13.1.4.3.9ScalarairFMSysAirFltrread-onlymandatoryThe type of air filters (standard or high efficiency) installed in the Modules of this System. A value of notApplicable indicates that this OID does not apply …
1.3.6.1.4.1.318.1.1.13.1.4.3.10ScalarairFMSysFlowSwitchread-onlymandatoryThe location of the optional flow switch. None: No flow switch is installed in this System. DX: Coolant input to the heat exchanger (condenser). MultiCool: Chi…
1.3.6.1.4.1.318.1.1.13.1.4.3.11ScalarairFMSysCoilFluidVlvActread-onlymandatoryThe type of valve actuator installed on the coil fluid valve. The coil fluid valve controls the flow of coolant into a fluid cooling coil, such as a MultiCool …
1.3.6.1.4.1.318.1.1.13.1.4.3.12ScalarairFMSysCoilFluidVlvTyperead-onlymandatoryThe type of coil fluid valve installed for the Modules in this System. A value of notApplicable indicates that this OID does not apply to this device due to it…
1.3.6.1.4.1.318.1.1.13.1.4.3.13ScalarairFMSysCndsrFluidVlvActread-onlymandatoryThe type of valve actuator installed on the Condenser fluid valve. The Condenser fluid valve controls the flow of coolant into the heat exchanger (condenser) t…
1.3.6.1.4.1.318.1.1.13.1.4.3.14ScalarairFMSysCndsrFluidVlvTyperead-onlymandatoryThe type of Condenser fluid valve installed for the Modules in this System. A value of notApplicable indicates that this OID does not apply to this device due …
1.3.6.1.4.1.318.1.1.13.1.4.3.15ScalarairFMSysHotWaterVlvActread-onlymandatoryThe type of valve actuator installed on the hot water valve. A value of notApplicable indicates that this OID does not apply to this device due to its configur…
1.3.6.1.4.1.318.1.1.13.1.4.3.16ScalarairFMSysNumRemoteSensorsread-onlymandatoryThe number of remote sensors detected by the system.
1.3.6.1.4.1.318.1.1.13.1.4.4NodeairFMSysConfig
1.3.6.1.4.1.318.1.1.13.1.4.4.1ScalarairFMSysPrimaryControlSensorread-writemandatorySelects whether return or remote sensors will control the system. A value of notApplicable indicates that this OID does not apply to this device due to its con…
1.3.6.1.4.1.318.1.1.13.1.4.4.2ScalarairFMSysRemoteSensorDataread-writemandatorySelects whether average temperature or max temperature will be used when remote sensors are selected for control of the system. A value of notApplicable indica…
1.3.6.1.4.1.318.1.1.13.1.4.4.3ScalarairFMSysFastStartupread-writemandatoryMinimizes the time for the cooling process to begin after other delay constraints have been met. A value of notApplicable indicates that this OID does not appl…
1.3.6.1.4.1.318.1.1.13.1.4.4.4ScalarairFMSysStartupDelayread-writemandatorySet the delay that begins when power is applied and ends when the System starts. This allows you to create a staged restart among your Systems after a power lo…
1.3.6.1.4.1.318.1.1.13.1.4.4.5ScalarairFMSysModeDelayread-writemandatorySet the delay between starting the blowers and engaging the modes. It allows the sensors to read room conditions accurately and allows the controller to check …
1.3.6.1.4.1.318.1.1.13.1.4.4.6ScalarairFMSysCommLossShutdownDelayread-writemandatorySet the delay between an Expansion Module losing communication with the Main Module and the Expansion Module shutting down. A value of -1 will keep the Expansi…
1.3.6.1.4.1.318.1.1.13.1.4.4.7ScalarairFMSysResetSysFailureread-writemandatorySetting this OID to reset(2) will allows the system to return from any failure condition, if the failure(s) have cleared. Getting this OID will do nothing and …
1.3.6.1.4.1.318.1.1.13.1.4.4.8ScalarairFMSysResetUserDfltsread-writemandatorySetting this OID to reset(2) will reset all system parameters that can be edited by the user to their factory default values. Getting this OID will do nothing …
1.3.6.1.4.1.318.1.1.13.1.4.4.9ScalarairFMSysResetFldSrvcDfltsread-writemandatorySetting this OID to reset(2) will reset all system parameters that can only be edited by the field service engineer to their factory default values. Getting th…
1.3.6.1.4.1.318.1.1.13.1.4.4.10ScalarairFMSysResetRunHoursread-writemandatorySetting this OID to reset(2) will reset the system Run Hours. Getting this OID will do nothing and return the noOperation(1) value. A value of notApplicable in…
1.3.6.1.4.1.318.1.1.13.1.4.5NodeairFMSysCooling
1.3.6.1.4.1.318.1.1.13.1.4.5.1ScalarairFMSysCompMinOnTimeread-writemandatorySet the minimum time the compressor continues to operate after it is started. The delay protects the compressor from damage. Caution: Reducing this delay short…
1.3.6.1.4.1.318.1.1.13.1.4.5.2ScalarairFMSysCompMinOffTimeread-writemandatorySet the minimum time the compressor will remain off after it ceases operation. The delay protects the compressor from damage. Caution: Reducing this delay shor…
1.3.6.1.4.1.318.1.1.13.1.4.5.3ScalarairFMSysCompRotPeriodread-writemandatorySet how often to perform compressor runtime balancing. Measured in hours. A value of -2147483648 indicates that this OID does not apply to this device due to i…
1.3.6.1.4.1.318.1.1.13.1.4.5.4ScalarairFMSysEconIsolVlvOpenDelayread-writemandatorySet the delay between opening the Economizer Isolator output relay and engaging the compressors. Measured in seconds. A value of -2147483648 indicates that thi…
1.3.6.1.4.1.318.1.1.13.1.4.5.5ScalarairFMSysEconIsolVlvCloseDelayread-writemandatorySet the delay between disengaging the compressor and closing the Economizer Isolator output relay. Measured in seconds. A value of -2147483648 indicates that t…
1.3.6.1.4.1.318.1.1.13.1.4.5.6ScalarairFMSysCndsrFluidVlvCloseDelayread-writemandatorySet the time the condenser valve remains open after the compressors disengage. Measured in seconds. A value of -2147483648 indicates that this OID does not app…
1.3.6.1.4.1.318.1.1.13.1.4.5.7ScalarairFMSysInterstageDelayread-writemandatoryThe DX interstage delay allows the first compressor's cooling to take effect before engaging the second compressor. This prevents the second compressor from cy…
1.3.6.1.4.1.318.1.1.13.1.4.5.8ScalarairFMSysCoolStateread-writemandatorySet the mode to enabled or disabled. Disabled modes will not operate, and you cannot make changes to their settings while they are disabled. A value of notAppl…
1.3.6.1.4.1.318.1.1.13.1.4.5.9ScalarairFMSysCoolEssFunctionread-writemandatorySet the priority of the mode for alarms and events with the nonessential stop behavior. Nonessential modes are disabled during nonessential stop alarms and eve…
1.3.6.1.4.1.318.1.1.13.1.4.5.10ScalarairFMSysCoolSetpointCread-writemandatoryThe target value for the selected control sensor air for this mode. It must be at least 1.0 C above the reheat setpoint if a heater is installed. Measured in t…
1.3.6.1.4.1.318.1.1.13.1.4.5.11ScalarairFMSysCoolSetpointFread-writemandatoryThe target value for the selected control sensor air for this mode. It must be at least 1.0 C above the reheat setpoint if a heater is installed. Measured in t…
1.3.6.1.4.1.318.1.1.13.1.4.5.12ScalarairFMSysCoolDeadbandCread-writemandatoryThe temperature range that controls output when the selected control sensor temperature is above the setpoint. At the top of this range, the cool mode outputs …
1.3.6.1.4.1.318.1.1.13.1.4.5.13ScalarairFMSysCoolDeadbandFread-writemandatoryThe temperature range that controls output when the selected control sensor temperature is above the setpoint. At the top of this range, the cool mode outputs …
1.3.6.1.4.1.318.1.1.13.1.4.5.14ScalarairFMSysCoolEconIsolFunctionread-writemandatorySet the Economizer Automatic Coolant Isolation valve to enabled or disabled. This valve anticipates a cooling demand and opens the coil fluid valve. A value of…
1.3.6.1.4.1.318.1.1.13.1.4.5.15ScalarairFMSysSuctPresCompensationread-writemandatorySet the Suction Pressure Compensation to enabled or disabled. This function attempts to keep the suction pressure from exceeding 95 psi. A value of notApplicab…
1.3.6.1.4.1.318.1.1.13.1.4.5.16ScalarairFMSysCoilFluidActivThreshCread-writemandatoryThe minimum coolant temperature required to use the optional MultiCool or Economizer coil. Measured in tenths of degrees Celsius. A value of -2147483648 indica…
1.3.6.1.4.1.318.1.1.13.1.4.5.17ScalarairFMSysCoilFluidActivThreshFread-writemandatoryThe minimum coolant temperature required to use the optional MultiCool or Economizer coil. Measured in tenths of degrees Fahrenheit. A value of -2147483648 ind…
1.3.6.1.4.1.318.1.1.13.1.4.5.18ScalarairFMSysCoilFluidActivDeadbandCread-writemandatoryThe controller will disengage the MultiCool or Economizer coil when the coolant temperature reaches the coil fluid temperature activation threshold plus the de…
1.3.6.1.4.1.318.1.1.13.1.4.5.19ScalarairFMSysCoilFluidActivDeadbandFread-writemandatoryThe controller will disengage the MultiCool or Economizer coil when the coolant temperature reaches the coil fluid temperature activation threshold plus the de…
1.3.6.1.4.1.318.1.1.13.1.4.5.20ScalarairFMSysCoolPIDMethodread-writemandatorySet the multipliers that the PID algorithm will use to calculate the cool output. Proportional, Proportional + Integral, or Proportional + Integral + Derivativ…
1.3.6.1.4.1.318.1.1.13.1.4.5.21ScalarairFMSysCoolPIDGainPread-writemandatorySet the proportional multiplier to correct for differences between the selected control sensor actual temperature and the setpoint. Measured in %/C. A value of…
1.3.6.1.4.1.318.1.1.13.1.4.5.22ScalarairFMSysCoolPIDResetRateIread-writemandatorySet the integral multiplier to correct for the proportional offset. Measured in %/(C * min). A value of -2147483648 indicates that this OID does not apply to t…
1.3.6.1.4.1.318.1.1.13.1.4.5.23ScalarairFMSysCoolPIDDerivativeDread-writemandatorySet the derivative multiplier to counteract overshoot and droop during changes in the room load. Measured in %/(C / min). A value of -2147483648 indicates that…
1.3.6.1.4.1.318.1.1.13.1.4.6NodeairFMSysHumidify
1.3.6.1.4.1.318.1.1.13.1.4.6.1ScalarairFMSysHumStateread-writemandatorySet the mode to enabled or disabled. Disabled modes will not operate, and you cannot make changes to their settings while they are disabled. A value of notAppl…
1.3.6.1.4.1.318.1.1.13.1.4.6.2ScalarairFMSysHumEssFunctionread-writemandatorySet the priority of the mode for alarms and events with the nonessential stop behavior. Nonessential modes are disabled during nonessential stop alarms and eve…
1.3.6.1.4.1.318.1.1.13.1.4.6.3ScalarairFMSysHumSetpointread-writemandatoryThe target value for the selected control sensor air for this mode. It must be at least 1.0 % RH below the dehumidification setpoint. Measured in tenths of per…
1.3.6.1.4.1.318.1.1.13.1.4.6.4ScalarairFMSysHumDeadbandread-writemandatoryThe humidity range that controls output when the selected control sensor humidity is below the setpoint. At the top of this range, the humidification mode outp…
1.3.6.1.4.1.318.1.1.13.1.4.6.5ScalarairFMSysHumCtrlSettingread-writemandatorySet the method to control the humidity in the room. The two methods are Relative Humidity (RH) or Dew Point of the selected control sensor air. The dew point m…
1.3.6.1.4.1.318.1.1.13.1.4.6.6ScalarairFMSysActualHumCtrlread-onlymandatoryThe humidity control method the system is using. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
1.3.6.1.4.1.318.1.1.13.1.4.6.7ScalarairFMSysHumSensBandread-writemandatoryThe percentage of relative humidity below the setpoint at which the humidifier will output at 100% of capacity. Measured in percent relative humidity. A value …
1.3.6.1.4.1.318.1.1.13.1.4.7NodeairFMSysDehumidify
1.3.6.1.4.1.318.1.1.13.1.4.7.1ScalarairFMSysDehumStateread-writemandatorySet the mode to enabled or disabled. Disabled modes will not operate, and you cannot make changes to their settings while they are disabled. A value of notAppl…
1.3.6.1.4.1.318.1.1.13.1.4.7.2ScalarairFMSysDehumEssFunctionread-writemandatorySet the priority of the mode for alarms and events with the nonessential stop behavior. Nonessential modes are disabled during nonessential stop alarms and eve…
1.3.6.1.4.1.318.1.1.13.1.4.7.3ScalarairFMSysDehumSetpointread-writemandatoryThe target value for the selected control sensor air for this mode. It must be at least 1.0 % RH above the humidification setpoint if a humidifier is installed…
1.3.6.1.4.1.318.1.1.13.1.4.7.4ScalarairFMSysDehumDeadbandread-writemandatoryThe humidity range above the setpoint at which the dehumidification mode will output at 100%. The deadband does not apply to PID controlled modes. Measured in …
1.3.6.1.4.1.318.1.1.13.1.4.7.5ScalarairFMSysDehumCapacityread-writemandatorySet the dehumidification mode to use either half of the cooling coil or the full coil when dehumidifying the room. A value of notApplicable indicates that this…
1.3.6.1.4.1.318.1.1.13.1.4.7.6ScalarairFMSysDehumPIDMethodread-writemandatorySet the multipliers that the PID algorithm will use to calculate the output. Proportional, Proportional + Integral, or Proportional + Integral + Derivative. A …
1.3.6.1.4.1.318.1.1.13.1.4.7.7ScalarairFMSysDehumPIDGainPread-writemandatorySet the proportional multiplier to correct for differences between the selected control sensor actual humidity and the setpoint. Measured in %/%RH. A value of …
1.3.6.1.4.1.318.1.1.13.1.4.7.8ScalarairFMSysDehumPIDResetRateIread-writemandatorySet the integral multiplier to correct for the proportional offset. Measured in %/(%RH * min). A value of -2147483648 indicates that this OID does not apply to…
1.3.6.1.4.1.318.1.1.13.1.4.7.9ScalarairFMSysDehumPIDDerivativeDread-writemandatorySet the derivative multiplier to counteract overshoot and droop during changes in the room humidity. Measure in %/(%RH / min). A value of -2147483648 indicates…
1.3.6.1.4.1.318.1.1.13.1.4.8NodeairFMSysReheat
1.3.6.1.4.1.318.1.1.13.1.4.8.1ScalarairFMSysReheatStateread-writemandatorySet the mode to enabled or disabled. Disabled modes will not operate, and you cannot make changes to their settings while they are disabled. A value of notAppl…
1.3.6.1.4.1.318.1.1.13.1.4.8.2ScalarairFMSysReheatEssFunctionread-writemandatorySet the priority of the mode for alarms and events with the nonessential stop behavior. Nonessential modes are disabled during nonessential stop alarms and eve…
1.3.6.1.4.1.318.1.1.13.1.4.8.3ScalarairFMSysReheatSetpointCread-writemandatoryThe target value for the selected control sensor air for this mode. It must be at least 1.0 C below the cooling setpoint. Measured in tenths of degrees Celsius…
1.3.6.1.4.1.318.1.1.13.1.4.8.4ScalarairFMSysReheatSetpointFread-writemandatoryThe target value for the selected control sensor air for this mode. It must be at least 1.0 C below the cooling setpoint. Measured in tenths of degrees Fahrenh…
1.3.6.1.4.1.318.1.1.13.1.4.8.5ScalarairFMSysReheatDeadbandCread-writemandatoryThe temperature range that controls output when the selected control sensor temperature is below the setpoint. At the bottom of this range, the reheat mode out…
1.3.6.1.4.1.318.1.1.13.1.4.8.6ScalarairFMSysReheatDeadbandFread-writemandatoryThe temperature range that controls output when the selected control sensor temperature is below the setpoint. At the bottom of this range, the reheat mode out…
1.3.6.1.4.1.318.1.1.13.1.4.8.7ScalarairFMSysReheatPIDMethodread-writemandatorySet the multipliers that the PID algorithm will use to calculate the output. Proportional, Proportional + Integral, or Proportional + Integral + Derivative. A …
1.3.6.1.4.1.318.1.1.13.1.4.8.8ScalarairFMSysReheatPIDGainPread-writemandatorySet the proportional multiplier to correct for differences between the selected control sensor actual temperature and the setpoint. Measured in %/C. A value of…
1.3.6.1.4.1.318.1.1.13.1.4.8.9ScalarairFMSysReheatPIDResetRateIread-writemandatorySet the integral multiplier to correct for the proportional offset. Measured in %/(C * min). A value of -2147483648 indicates that this OID does not apply to t…
1.3.6.1.4.1.318.1.1.13.1.4.8.10ScalarairFMSysReheatPIDDerivativeDread-writemandatorySet the derivative multiplier to counteract overshoot and droop during changes in the room load. Measured in %/(C / min). A value of -2147483648 indicates that…
1.3.6.1.4.1.318.1.1.13.1.4.9NodeairFMSysThresholds
1.3.6.1.4.1.318.1.1.13.1.4.9.1ScalarairFMSysHighSplyTempCread-writemandatoryThe high temperature threshold for air blown into the room (supply). If the supply temperature exceeds the threshold, an alarm will occur. Measured in tenths o…
1.3.6.1.4.1.318.1.1.13.1.4.9.2ScalarairFMSysHighSplyTempFread-writemandatoryThe high temperature threshold for air blown into the room (supply). If the supply temperature exceeds the threshold, an alarm will occur. Measured in tenths o…
1.3.6.1.4.1.318.1.1.13.1.4.9.3ScalarairFMSysLowSplyTempCread-writemandatoryThe low temperature threshold for air blown into the room (supply). If the supply temperature drops below the threshold, an alarm will occur. Measured in tenth…
1.3.6.1.4.1.318.1.1.13.1.4.9.4ScalarairFMSysLowSplyTempFread-writemandatoryThe low temperature threshold for air blown into the room (supply). If the supply temperature drops below the threshold, an alarm will occur. Measured in tenth…
1.3.6.1.4.1.318.1.1.13.1.4.9.5ScalarairFMSysHighCoilFluidTempCread-writemandatoryThe high temperature threshold for coolant at the inlet to the fluid coil. If the fluid coil coolant temperature exceeds the threshold, an alarm will occur. Me…
1.3.6.1.4.1.318.1.1.13.1.4.9.6ScalarairFMSysHighCoilFluidTempFread-writemandatoryThe high temperature threshold for coolant at the inlet to the fluid coil. If the fluid coil coolant temperature exceeds the threshold, an alarm will occur. Me…
1.3.6.1.4.1.318.1.1.13.1.4.9.7ScalarairFMSysLowCoilFluidTempCread-writemandatoryThe low temperature threshold for coolant at the inlet to the fluid coil. If the fluid coil coolant temperature drops below the threshold, an alarm will occur.…
1.3.6.1.4.1.318.1.1.13.1.4.9.8ScalarairFMSysLowCoilFluidTempFread-writemandatoryThe low temperature threshold for coolant at the inlet to the fluid coil. If the fluid coil coolant temperature drops below the threshold, an alarm will occur.…
1.3.6.1.4.1.318.1.1.13.1.4.9.9ScalarairFMSysHighCtrlTempCread-writemandatoryThe high temperature threshold for air monitored by the System. If the temperature exceeds the threshold, an alarm will occur. Measured in tenths of degrees Ce…
1.3.6.1.4.1.318.1.1.13.1.4.9.10ScalarairFMSysHighCtrlTempFread-writemandatoryThe high temperature threshold for air monitored by the System. If the temperature exceeds the threshold, an alarm will occur. Measured in tenths of degrees Fa…
1.3.6.1.4.1.318.1.1.13.1.4.9.11ScalarairFMSysLowCtrlTempCread-writemandatoryThe low temperature threshold for air monitored by the System. If the temperature drops below the threshold, an alarm will occur. Measured in tenths of degrees…
1.3.6.1.4.1.318.1.1.13.1.4.9.12ScalarairFMSysLowCtrlTempFread-writemandatoryThe low temperature threshold for air monitored by the System. If the temperature drops below the threshold, an alarm will occur. Measured in tenths of degrees…
1.3.6.1.4.1.318.1.1.13.1.4.9.13ScalarairFMSysHighCtrlHumread-writemandatoryThe high humidity threshold for air monitored by the System. If the humidity exceeds the threshold, an alarm will occur. Measured in tenths of percent relative…
1.3.6.1.4.1.318.1.1.13.1.4.9.14ScalarairFMSysLowCtrlHumread-writemandatoryThe low humidity threshold for air monitored by the System. If the humidity drops below the threshold, an alarm will occur. Measured in tenths of percent relat…
1.3.6.1.4.1.318.1.1.13.1.4.9.15ScalarairFMSysTempAlarmDelayread-writemandatoryThe amount of time the blower must be on before a temperature alarm can be issued. Measured in seconds. A value of -2147483648 indicates that this OID does not…
1.3.6.1.4.1.318.1.1.13.1.4.9.16ScalarairFMSysHumAlarmDelayread-writemandatoryThe amount of time the blower must be on before a humidity alarm can be issued. Measured in seconds. A value of -2147483648 indicates that this OID does not ap…
1.3.6.1.4.1.318.1.1.13.1.4.10NodeairFMSysInputs
1.3.6.1.4.1.318.1.1.13.1.4.10.1ScalarairFMSysInputTableSizeread-onlymandatoryThe number of entries in the airFMSysInputTable.
1.3.6.1.4.1.318.1.1.13.1.4.10.2TableairFMSysInputTablenot-accessiblemandatoryAllows for getting information from each input contact.
1.3.6.1.4.1.318.1.1.13.1.4.10.2.1RowairFMSysInputEntrynot-accessiblemandatoryThe input contact to obtain status from.
1.3.6.1.4.1.318.1.1.13.1.4.10.2.1.1ColumnairFMSysInputIndexread-onlymandatoryThe number designator of the Input Contact.
1.3.6.1.4.1.318.1.1.13.1.4.10.2.1.2ColumnairFMSysInputNameread-writemandatoryThe configurable name for the Input Contact. Maximum text input is 13 characters.
1.3.6.1.4.1.318.1.1.13.1.4.10.2.1.3ColumnairFMSysInputStatusread-onlymandatoryThe state of this contact: Open or Closed. A violation will occur when this relay is not in its normal state.
1.3.6.1.4.1.318.1.1.13.1.4.10.2.1.4ColumnairFMSysInputNormalStateread-writemandatorySet the normal state of this contact (the state when no alarm/event exists).
1.3.6.1.4.1.318.1.1.13.1.4.10.2.1.5ColumnairFMSysInputDelayread-writemandatorySet the delay between this contact exiting its normal state and an alarm being triggered. Measured in seconds.
1.3.6.1.4.1.318.1.1.13.1.4.10.2.1.6ColumnairFMSysInputAlarmActionread-writemandatorySets the behavior for this contact when it exits its normal state.
1.3.6.1.4.1.318.1.1.13.1.4.11NodeairFMSysOutputs
1.3.6.1.4.1.318.1.1.13.1.4.11.1ScalarairFMSysOutputTableSizeread-onlymandatoryThe number of entries in the airFMSysOutputTable.
1.3.6.1.4.1.318.1.1.13.1.4.11.2TableairFMSysOutputTablenot-accessiblemandatoryAllows for getting information from each output relay.
1.3.6.1.4.1.318.1.1.13.1.4.11.2.1RowairFMSysOutputEntrynot-accessiblemandatoryThe output relay to obtain status from.
1.3.6.1.4.1.318.1.1.13.1.4.11.2.1.1ColumnairFMSysOutputIndexread-onlymandatoryThe number designator of the output relay.
1.3.6.1.4.1.318.1.1.13.1.4.11.2.1.2ColumnairFMSysOutputStatusread-onlymandatoryThe state of this relay: Open or Closed. A violation will occur when this relay is not in its normal state.
1.3.6.1.4.1.318.1.1.13.1.4.11.2.1.3ColumnairFMSysOutputNormalStateread-writemandatorySet the normal state of this relay (the state when no alarm/event exists).
1.3.6.1.4.1.318.1.1.13.1.4.12NodeairFMSysAlarmMap
1.3.6.1.4.1.318.1.1.13.1.4.12.1NodeairFMSysAlarmMapSys
1.3.6.1.4.1.318.1.1.13.1.4.12.1.1ScalarairFMSysAlarmMapSysTableSizeread-onlymandatoryThe number of entries in the airFMSysAlarmMapSysTable.
1.3.6.1.4.1.318.1.1.13.1.4.12.1.2TableairFMSysAlarmMapSysTablenot-accessiblemandatoryAllows for getting alarm map information.
1.3.6.1.4.1.318.1.1.13.1.4.12.1.2.1RowairFMSysAlarmMapSysEntrynot-accessiblemandatoryThe system alarm map type to reference.
1.3.6.1.4.1.318.1.1.13.1.4.12.1.2.1.1ColumnairFMSysAlarmMapSysOutputIndexread-onlymandatoryThe index of the output relay.
1.3.6.1.4.1.318.1.1.13.1.4.12.1.2.1.2ColumnairFMSysAlarmMapSysAnyAlarmread-writemandatorySystem alarm map setting for Any Alarm. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
1.3.6.1.4.1.318.1.1.13.1.4.12.1.2.1.3ColumnairFMSysAlarmMapSystemOnread-writemandatorySystem alarm map setting for System On. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
1.3.6.1.4.1.318.1.1.13.1.4.12.1.2.1.4ColumnairFMSysAlarmMapSystemOfflineread-writemandatorySystem alarm map setting for System Offline. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
1.3.6.1.4.1.318.1.1.13.1.4.12.1.2.1.5ColumnairFMSysAlarmMapSysHighEnvTempread-writemandatorySystem alarm map setting for High Environmental Temperature. A value of notApplicable indicates that this OID does not apply to this device due to its configur…
1.3.6.1.4.1.318.1.1.13.1.4.12.1.2.1.6ColumnairFMSysAlarmMapSysLowEnvTempread-writemandatorySystem alarm map setting for Low Environmental Temperature. A value of notApplicable indicates that this OID does not apply to this device due to its configura…
1.3.6.1.4.1.318.1.1.13.1.4.12.1.2.1.7ColumnairFMSysAlarmMapSysHighEnvHumread-writemandatorySystem alarm map setting for High Environmental Humidity. A value of notApplicable indicates that this OID does not apply to this device due to its configurati…
1.3.6.1.4.1.318.1.1.13.1.4.12.1.2.1.8ColumnairFMSysAlarmMapSysLowEnvHumread-writemandatorySystem alarm map setting for Low Environmental Humidity. A value of notApplicable indicates that this OID does not apply to this device due to its configuratio…
1.3.6.1.4.1.318.1.1.13.1.4.12.1.2.1.9ColumnairFMSysAlarmMapSysFireDetread-writemandatorySystem alarm map setting for Fire Detected. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
1.3.6.1.4.1.318.1.1.13.1.4.12.1.2.1.10ColumnairFMSysAlarmMapSysSmokeDetread-writemandatorySystem alarm map setting for Smoke Detected. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
1.3.6.1.4.1.318.1.1.13.1.4.12.1.2.1.11ColumnairFMSysAlarmMapSysEconIsolread-writemandatorySystem alarm map setting for Econ Isolator. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
1.3.6.1.4.1.318.1.1.13.1.4.12.1.2.1.12ColumnairFMSysAlarmMapSysSupplySensFailread-writemandatorySystem alarm map setting for Supply Sensor Failure. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
1.3.6.1.4.1.318.1.1.13.1.4.12.1.2.1.13ColumnairFMSysAlarmMapSysReturnSensFailread-writemandatorySystem alarm map setting for Return Sensor Failure. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
1.3.6.1.4.1.318.1.1.13.1.4.12.1.2.1.14ColumnairFMSysAlarmMapSysRemSensRemovedread-writemandatorySystem alarm map setting for Remote Sensor Removed. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
1.3.6.1.4.1.318.1.1.13.1.4.12.1.2.1.15ColumnairFMSysAlarmMapSysPrimSensFailread-writemandatorySystem alarm map setting for Primary Sensor Failure. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
1.3.6.1.4.1.318.1.1.13.1.4.12.1.2.1.16ColumnairFMSysAlarmMapSysSecSensFailread-writemandatorySystem alarm map setting for Secondary Sensor Failure. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
1.3.6.1.4.1.318.1.1.13.1.4.12.1.2.1.17ColumnairFMSysAlarmMapSysSecSensActiveread-writemandatorySystem alarm map setting for Secondary Sensor Active. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
1.3.6.1.4.1.318.1.1.13.1.4.12.2NodeairFMSysAlarmMapMainMod
1.3.6.1.4.1.318.1.1.13.1.4.12.2.1ScalarairFMSysAlarmMapMainModTableSizeread-onlymandatoryThe number of entries in the airFMSysAlarmMapMainModTable.
1.3.6.1.4.1.318.1.1.13.1.4.12.2.2TableairFMSysAlarmMapMainModTablenot-accessiblemandatoryAllows for getting alarm map information.
1.3.6.1.4.1.318.1.1.13.1.4.12.2.2.1RowairFMSysAlarmMapMainModEntrynot-accessiblemandatoryThe main module alarm map type to reference.
1.3.6.1.4.1.318.1.1.13.1.4.12.2.2.1.1ColumnairFMSysAlarmMapMainModOutputIndexread-onlymandatoryThe index of the output relay.
1.3.6.1.4.1.318.1.1.13.1.4.12.2.2.1.2ColumnairFMSysAlarmMapMainModAnyAlarmread-writemandatoryMain Module alarm map setting for Any Alarm. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
1.3.6.1.4.1.318.1.1.13.1.4.12.2.2.1.3ColumnairFMSysAlarmMapMainModMaintReqread-writemandatoryMain Module alarm map setting for Module Maintenance Required. A value of notApplicable indicates that this OID does not apply to this device due to its config…
1.3.6.1.4.1.318.1.1.13.1.4.12.2.2.1.4ColumnairFMSysAlarmMapMainModCoolFailread-writemandatoryMain Module alarm map setting for Module Cooling Failure. A value of notApplicable indicates that this OID does not apply to this device due to its configurati…
1.3.6.1.4.1.318.1.1.13.1.4.12.2.2.1.5ColumnairFMSysAlarmMapMainModHighSupplyTempread-writemandatoryMain Module alarm map setting for High Supply Temperature. A value of notApplicable indicates that this OID does not apply to this device due to its configurat…
1.3.6.1.4.1.318.1.1.13.1.4.12.2.2.1.6ColumnairFMSysAlarmMapMainModLowSupplyTempread-writemandatoryMain Module alarm map setting for Low Supply Temperature. A value of notApplicable indicates that this OID does not apply to this device due to its configurati…
1.3.6.1.4.1.318.1.1.13.1.4.12.2.2.1.7ColumnairFMSysAlarmMapMainModHumFailread-writemandatoryMain Module alarm map setting for Humidifier Failure. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
1.3.6.1.4.1.318.1.1.13.1.4.12.2.2.1.8ColumnairFMSysAlarmMapMainModHumReplCylread-writemandatoryMain Module alarm map setting for Humidifier Replace Cylinder. A value of notApplicable indicates that this OID does not apply to this device due to its config…
1.3.6.1.4.1.318.1.1.13.1.4.12.2.2.1.9ColumnairFMSysAlarmMapMainModCondPumpFailread-writemandatoryMain Module alarm map setting for Condensate Pump Failure. A value of notApplicable indicates that this OID does not apply to this device due to its configurat…
1.3.6.1.4.1.318.1.1.13.1.4.12.2.2.1.10ColumnairFMSysAlarmMapMainModBlwrCntl1Failread-writemandatoryMain Module alarm map setting for Blower Controller 1 Failure. A value of notApplicable indicates that this OID does not apply to this device due to its config…
1.3.6.1.4.1.318.1.1.13.1.4.12.2.2.1.11ColumnairFMSysAlarmMapMainModBlwrCntl2Failread-writemandatoryMain Module alarm map setting for Blower Controller 2 Failure. A value of notApplicable indicates that this OID does not apply to this device due to its config…
1.3.6.1.4.1.318.1.1.13.1.4.12.2.2.1.12ColumnairFMSysAlarmMapMainModHighFltrDPread-writemandatoryMain Module alarm map setting for High Filter Differential Pressure. A value of notApplicable indicates that this OID does not apply to this device due to its …
1.3.6.1.4.1.318.1.1.13.1.4.12.2.2.1.13ColumnairFMSysAlarmMapMainModLowAirFlowread-writemandatoryMain Module alarm map setting for Low Air Flow. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
1.3.6.1.4.1.318.1.1.13.1.4.12.2.2.1.14ColumnairFMSysAlarmMapMainModAirBlckIntOpenread-writemandatoryMain Module alarm map setting for Air Block Interlock Open. A value of notApplicable indicates that this OID does not apply to this device due to its configura…
1.3.6.1.4.1.318.1.1.13.1.4.12.2.2.1.15ColumnairFMSysAlarmMapMainModWaterDetectedread-writemandatoryMain Module alarm map setting for Water Detected. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
1.3.6.1.4.1.318.1.1.13.1.4.12.3NodeairFMSysAlarmMapExpMod1
1.3.6.1.4.1.318.1.1.13.1.4.12.3.1ScalarairFMSysAlarmMapExpMod1TableSizeread-onlymandatoryThe number of entries in the airFMSysAlarmMapExpMod1Table.
1.3.6.1.4.1.318.1.1.13.1.4.12.3.2TableairFMSysAlarmMapExpMod1Tablenot-accessiblemandatoryAllows for getting alarm map information.
1.3.6.1.4.1.318.1.1.13.1.4.12.3.2.1RowairFMSysAlarmMapExpMod1Entrynot-accessiblemandatoryThe expansion module 1 alarm map type to reference.
1.3.6.1.4.1.318.1.1.13.1.4.12.3.2.1.1ColumnairFMSysAlarmMapExpMod1OutputIndexread-onlymandatoryThe index of the output relay.
1.3.6.1.4.1.318.1.1.13.1.4.12.3.2.1.2ColumnairFMSysAlarmMapExpMod1AnyAlarmread-writemandatoryExp Module 1 alarm map setting for Any Alarm. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
1.3.6.1.4.1.318.1.1.13.1.4.12.3.2.1.3ColumnairFMSysAlarmMapExpMod1MaintReqread-writemandatoryExp Module 1 alarm map setting for Module Maintenance Required. A value of notApplicable indicates that this OID does not apply to this device due to its confi…
1.3.6.1.4.1.318.1.1.13.1.4.12.3.2.1.4ColumnairFMSysAlarmMapExpMod1CoolFailread-writemandatoryExp Module 1 alarm map setting for Module Cooling Failure. A value of notApplicable indicates that this OID does not apply to this device due to its configurat…
1.3.6.1.4.1.318.1.1.13.1.4.12.3.2.1.5ColumnairFMSysAlarmMapExpMod1HighSupplyTempread-writemandatoryExp Module 1 alarm map setting for High Supply Temperature. A value of notApplicable indicates that this OID does not apply to this device due to its configura…
1.3.6.1.4.1.318.1.1.13.1.4.12.3.2.1.6ColumnairFMSysAlarmMapExpMod1LowSupplyTempread-writemandatoryExp Module 1 alarm map setting for Low Supply Temperature. A value of notApplicable indicates that this OID does not apply to this device due to its configurat…
1.3.6.1.4.1.318.1.1.13.1.4.12.3.2.1.7ColumnairFMSysAlarmMapExpMod1HumFailread-writemandatoryExp Module 1 alarm map setting for Humidifier Failure. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
1.3.6.1.4.1.318.1.1.13.1.4.12.3.2.1.8ColumnairFMSysAlarmMapExpMod1HumReplCylread-writemandatoryExp Module 1 alarm map setting for Humidifier Replace Cylinder. A value of notApplicable indicates that this OID does not apply to this device due to its confi…
1.3.6.1.4.1.318.1.1.13.1.4.12.3.2.1.9ColumnairFMSysAlarmMapExpMod1CondPumpFailread-writemandatoryExp Module 1 alarm map setting for Condensate Pump Failure. A value of notApplicable indicates that this OID does not apply to this device due to its configura…
1.3.6.1.4.1.318.1.1.13.1.4.12.3.2.1.10ColumnairFMSysAlarmMapExpMod1BlwrCntl1Failread-writemandatoryExp Module 1 alarm map setting for Blower Controller 1 Failure. A value of notApplicable indicates that this OID does not apply to this device due to its confi…
1.3.6.1.4.1.318.1.1.13.1.4.12.3.2.1.11ColumnairFMSysAlarmMapExpMod1BlwrCntl2Failread-writemandatoryExp Module 1 alarm map setting for Blower Controller 2 Failure. A value of notApplicable indicates that this OID does not apply to this device due to its confi…
1.3.6.1.4.1.318.1.1.13.1.4.12.3.2.1.12ColumnairFMSysAlarmMapExpMod1HighFltrDPread-writemandatoryExp Module 1 alarm map setting for High Filter Differential Pressure. A value of notApplicable indicates that this OID does not apply to this device due to its…
1.3.6.1.4.1.318.1.1.13.1.4.12.3.2.1.13ColumnairFMSysAlarmMapExpMod1LowAirFlowread-writemandatoryExp Module 1 alarm map setting for Low Air Flow. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
1.3.6.1.4.1.318.1.1.13.1.4.12.3.2.1.14ColumnairFMSysAlarmMapExpMod1AirBlckIntOpenread-writemandatoryExp Module 1 alarm map setting for Air Block Interlock Open. A value of notApplicable indicates that this OID does not apply to this device due to its configur…
1.3.6.1.4.1.318.1.1.13.1.4.12.3.2.1.15ColumnairFMSysAlarmMapExpMod1WaterDetectedread-writemandatoryExp Module 1 alarm map setting for Water Detected. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
1.3.6.1.4.1.318.1.1.13.1.4.12.4NodeairFMSysAlarmMapExpMod2
1.3.6.1.4.1.318.1.1.13.1.4.12.4.1ScalarairFMSysAlarmMapExpMod2TableSizeread-onlymandatoryThe number of entries in the airFMSysAlarmMapExpMod2Table.
1.3.6.1.4.1.318.1.1.13.1.4.12.4.2TableairFMSysAlarmMapExpMod2Tablenot-accessiblemandatoryAllows for getting alarm map information.
1.3.6.1.4.1.318.1.1.13.1.4.12.4.2.1RowairFMSysAlarmMapExpMod2Entrynot-accessiblemandatoryThe expansion module 2 alarm map type to reference.
1.3.6.1.4.1.318.1.1.13.1.4.12.4.2.1.1ColumnairFMSysAlarmMapExpMod2OutputIndexread-onlymandatoryThe index of the output relay.
1.3.6.1.4.1.318.1.1.13.1.4.12.4.2.1.2ColumnairFMSysAlarmMapExpMod2AnyAlarmread-writemandatoryExp Module 2 alarm map setting for Any Alarm. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
1.3.6.1.4.1.318.1.1.13.1.4.12.4.2.1.3ColumnairFMSysAlarmMapExpMod2MaintReqread-writemandatoryExp Module 2 alarm map setting for Module Maintenance Required. A value of notApplicable indicates that this OID does not apply to this device due to its confi…
1.3.6.1.4.1.318.1.1.13.1.4.12.4.2.1.4ColumnairFMSysAlarmMapExpMod2CoolFailread-writemandatoryExp Module 2 alarm map setting for Module Cooling Failure. A value of notApplicable indicates that this OID does not apply to this device due to its configurat…
1.3.6.1.4.1.318.1.1.13.1.4.12.4.2.1.5ColumnairFMSysAlarmMapExpMod2HighSupplyTempread-writemandatoryExp Module 2 alarm map setting for High Supply Temperature. A value of notApplicable indicates that this OID does not apply to this device due to its configura…
1.3.6.1.4.1.318.1.1.13.1.4.12.4.2.1.6ColumnairFMSysAlarmMapExpMod2LowSupplyTempread-writemandatoryExp Module 2 alarm map setting for Low Supply Temperature. A value of notApplicable indicates that this OID does not apply to this device due to its configurat…
1.3.6.1.4.1.318.1.1.13.1.4.12.4.2.1.7ColumnairFMSysAlarmMapExpMod2HumFailread-writemandatoryExp Module 2 alarm map setting for Humidifier Failure. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
1.3.6.1.4.1.318.1.1.13.1.4.12.4.2.1.8ColumnairFMSysAlarmMapExpMod2HumReplCylread-writemandatoryExp Module 2 alarm map setting for Humidifier Replace Cylinder. A value of notApplicable indicates that this OID does not apply to this device due to its confi…
1.3.6.1.4.1.318.1.1.13.1.4.12.4.2.1.9ColumnairFMSysAlarmMapExpMod2CondPumpFailread-writemandatoryExp Module 2 alarm map setting for Condensate Pump Failure. A value of notApplicable indicates that this OID does not apply to this device due to its configura…
1.3.6.1.4.1.318.1.1.13.1.4.12.4.2.1.10ColumnairFMSysAlarmMapExpMod2BlwrCntl1Failread-writemandatoryExp Module 2 alarm map setting for Blower Controller 1 Failure. A value of notApplicable indicates that this OID does not apply to this device due to its confi…
1.3.6.1.4.1.318.1.1.13.1.4.12.4.2.1.11ColumnairFMSysAlarmMapExpMod2BlwrCntl2Failread-writemandatoryExp Module 2 alarm map setting for Blower Controller 2 Failure. A value of notApplicable indicates that this OID does not apply to this device due to its confi…
1.3.6.1.4.1.318.1.1.13.1.4.12.4.2.1.12ColumnairFMSysAlarmMapExpMod2HighFltrDPread-writemandatoryExp Module 2 alarm map setting for High Filter Differential Pressure. A value of notApplicable indicates that this OID does not apply to this device due to its…
1.3.6.1.4.1.318.1.1.13.1.4.12.4.2.1.13ColumnairFMSysAlarmMapExpMod2LowAirFlowread-writemandatoryExp Module 2 alarm map setting for Low Air Flow. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
1.3.6.1.4.1.318.1.1.13.1.4.12.4.2.1.14ColumnairFMSysAlarmMapExpMod2AirBlckIntOpenread-writemandatoryExp Module 2 alarm map setting for Air Block Interlock Open. A value of notApplicable indicates that this OID does not apply to this device due to its configur…
1.3.6.1.4.1.318.1.1.13.1.4.12.4.2.1.15ColumnairFMSysAlarmMapExpMod2WaterDetectedread-writemandatoryExp Module 2 alarm map setting for Water Detected. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
1.3.6.1.4.1.318.1.1.13.1.4.12.5NodeairFMSysAlarmMapInput
1.3.6.1.4.1.318.1.1.13.1.4.12.5.1ScalarairFMSysAlarmMapInputTableSizeread-onlymandatoryThe number of entries in the airFMSysAlarmMapInputTable.
1.3.6.1.4.1.318.1.1.13.1.4.12.5.2TableairFMSysAlarmMapInputTablenot-accessiblemandatoryAllows for getting alarm map information.
1.3.6.1.4.1.318.1.1.13.1.4.12.5.2.1RowairFMSysAlarmMapInputEntrynot-accessiblemandatoryThe input contact alarm map type to reference.
1.3.6.1.4.1.318.1.1.13.1.4.12.5.2.1.1ColumnairFMSysAlarmMapInputOutputIndexread-onlymandatoryThe index of the output relay.
1.3.6.1.4.1.318.1.1.13.1.4.12.5.2.1.2ColumnairFMSysAlarmMapInput1read-writemandatoryInput contact 1 alarm map setting. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
1.3.6.1.4.1.318.1.1.13.1.4.12.5.2.1.3ColumnairFMSysAlarmMapInput2read-writemandatoryInput contact 2 alarm map setting. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
1.3.6.1.4.1.318.1.1.13.1.4.12.5.2.1.4ColumnairFMSysAlarmMapInput3read-writemandatoryInput contact 3 alarm map setting. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
1.3.6.1.4.1.318.1.1.13.1.4.12.5.2.1.5ColumnairFMSysAlarmMapInput4read-writemandatoryInput contact 4 alarm map setting. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
1.3.6.1.4.1.318.1.1.13.1.4.12.5.2.1.6ColumnairFMSysAlarmMapInput5read-writemandatoryInput contact 5 alarm map setting. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
1.3.6.1.4.1.318.1.1.13.1.4.12.5.2.1.7ColumnairFMSysAlarmMapInput6read-writemandatoryInput contact 6 alarm map setting. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
1.3.6.1.4.1.318.1.1.13.1.4.12.5.2.1.8ColumnairFMSysAlarmMapInput7read-writemandatoryInput contact 7 alarm map setting. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
1.3.6.1.4.1.318.1.1.13.1.4.12.5.2.1.9ColumnairFMSysAlarmMapInput8read-writemandatoryInput contact 8 alarm map setting. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
1.3.6.1.4.1.318.1.1.13.1.4.12.5.2.1.10ColumnairFMSysAlarmMapInput9read-writemandatoryInput contact 9 alarm map setting. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
1.3.6.1.4.1.318.1.1.13.1.4.12.5.2.1.11ColumnairFMSysAlarmMapInput10read-writemandatoryInput contact 10 alarm map setting. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
1.3.6.1.4.1.318.1.1.13.1.4.12.5.2.1.12ColumnairFMSysAlarmMapInput11read-writemandatoryInput contact 11 alarm map setting. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
1.3.6.1.4.1.318.1.1.13.1.4.12.5.2.1.13ColumnairFMSysAlarmMapInput12read-writemandatoryInput contact 12 alarm map setting. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
1.3.6.1.4.1.318.1.1.13.1.4.12.5.2.1.14ColumnairFMSysAlarmMapInput13read-writemandatoryInput contact 13 alarm map setting. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
1.3.6.1.4.1.318.1.1.13.1.4.12.5.2.1.15ColumnairFMSysAlarmMapInput14read-writemandatoryInput contact 14 alarm map setting. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
1.3.6.1.4.1.318.1.1.13.1.4.12.5.2.1.16ColumnairFMSysAlarmMapInput15read-writemandatoryInput contact 15 alarm map setting. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
1.3.6.1.4.1.318.1.1.13.1.4.12.5.2.1.17ColumnairFMSysAlarmMapInput16read-writemandatoryInput contact 16 alarm map setting. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
1.3.6.1.4.1.318.1.1.13.1.4.12.6NodeairFMSysAlarmMapOutput
1.3.6.1.4.1.318.1.1.13.1.4.12.6.1ScalarairFMSysAlarmMapOutputTableSizeread-onlymandatoryThe number of entries in the airFMSysAlarmMapOutputTable.
1.3.6.1.4.1.318.1.1.13.1.4.12.6.2TableairFMSysAlarmMapOutputTablenot-accessiblemandatoryAllows for getting alarm map information.
1.3.6.1.4.1.318.1.1.13.1.4.12.6.2.1RowairFMSysAlarmMapOutputEntrynot-accessiblemandatoryThe input contact alarm map type to reference.
1.3.6.1.4.1.318.1.1.13.1.4.12.6.2.1.1ColumnairFMSysAlarmMapOutputIndexread-onlymandatoryThe index of the output relay.
1.3.6.1.4.1.318.1.1.13.1.4.12.6.2.1.2ColumnairFMSysAlarmMapOutput1read-writemandatoryOutput relay 1 alarm map setting. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
1.3.6.1.4.1.318.1.1.13.1.4.12.6.2.1.3ColumnairFMSysAlarmMapOutput2read-writemandatoryOutput relay 2 alarm map setting. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
1.3.6.1.4.1.318.1.1.13.1.4.12.6.2.1.4ColumnairFMSysAlarmMapOutput3read-writemandatoryOutput relay 3 alarm map setting. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
1.3.6.1.4.1.318.1.1.13.1.4.12.6.2.1.5ColumnairFMSysAlarmMapOutput4read-writemandatoryOutput relay 4 alarm map setting. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
1.3.6.1.4.1.318.1.1.13.1.4.12.6.2.1.6ColumnairFMSysAlarmMapOutput5read-writemandatoryOutput relay 5 alarm map setting. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
1.3.6.1.4.1.318.1.1.13.1.4.12.6.2.1.7ColumnairFMSysAlarmMapOutput6read-writemandatoryOutput relay 6 alarm map setting. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
1.3.6.1.4.1.318.1.1.13.1.4.12.6.2.1.8ColumnairFMSysAlarmMapOutput7read-writemandatoryOutput relay 7 alarm map setting. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
1.3.6.1.4.1.318.1.1.13.1.4.12.6.2.1.9ColumnairFMSysAlarmMapOutput8read-writemandatoryOutput relay 8 alarm map setting. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
1.3.6.1.4.1.318.1.1.13.1.4.12.6.2.1.10ColumnairFMSysAlarmMapOutput9read-writemandatoryOutput relay 9 alarm map setting. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
1.3.6.1.4.1.318.1.1.13.1.4.12.6.2.1.11ColumnairFMSysAlarmMapOutput10read-writemandatoryOutput relay 10 alarm map setting. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
1.3.6.1.4.1.318.1.1.13.1.4.12.6.2.1.12ColumnairFMSysAlarmMapOutput11read-writemandatoryOutput relay 11 alarm map setting. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
1.3.6.1.4.1.318.1.1.13.1.4.12.6.2.1.13ColumnairFMSysAlarmMapOutput12read-writemandatoryOutput relay 12 alarm map setting. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
1.3.6.1.4.1.318.1.1.13.1.4.12.6.2.1.14ColumnairFMSysAlarmMapOutput13read-writemandatoryOutput relay 13 alarm map setting. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
1.3.6.1.4.1.318.1.1.13.1.4.12.6.2.1.15ColumnairFMSysAlarmMapOutput14read-writemandatoryOutput relay 14 alarm map setting. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
1.3.6.1.4.1.318.1.1.13.1.4.12.6.2.1.16ColumnairFMSysAlarmMapOutput15read-writemandatoryOutput relay 15 alarm map setting. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
1.3.6.1.4.1.318.1.1.13.1.4.12.6.2.1.17ColumnairFMSysAlarmMapOutput16read-writemandatoryOutput relay 16 alarm map setting. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
1.3.6.1.4.1.318.1.1.13.1.5NodeairFMModule
1.3.6.1.4.1.318.1.1.13.1.5.1NodeairFMModIdent
1.3.6.1.4.1.318.1.1.13.1.5.1.1ScalarairFMModIdentTableSizeread-onlymandatoryThe number of entries in the airFMModIdentTable.
1.3.6.1.4.1.318.1.1.13.1.5.1.2TableairFMModIdentTablenot-accessiblemandatoryAllows for getting information from each module in the system.
1.3.6.1.4.1.318.1.1.13.1.5.1.2.1RowairFMModIdentEntrynot-accessiblemandatoryThe module to get information from.
1.3.6.1.4.1.318.1.1.13.1.5.1.2.1.1ColumnairFMModIdentModuleIndexread-onlymandatoryThe index of the module.
1.3.6.1.4.1.318.1.1.13.1.5.1.2.1.2ColumnairFMModModelNumberread-onlymandatoryModel number of the Module.
1.3.6.1.4.1.318.1.1.13.1.5.1.2.1.3ColumnairFMModSerialNumberread-onlymandatoryUnique identification number for this Module.
1.3.6.1.4.1.318.1.1.13.1.5.1.2.1.4ColumnairFMModManufactureDateread-onlymandatoryDate the Module was manufactured.
1.3.6.1.4.1.318.1.1.13.1.5.1.2.1.5ColumnairFMModFirmwareRevread-onlymandatoryRevision number of the firmware installed on this Module.
1.3.6.1.4.1.318.1.1.13.1.5.1.2.1.6ColumnairFMModHardwareRevread-onlymandatoryRevision number of the hardware installed on this Module.
1.3.6.1.4.1.318.1.1.13.1.5.2NodeairFMModStatus
1.3.6.1.4.1.318.1.1.13.1.5.2.1ScalarairFMModStatusTableSizeread-onlymandatoryThe number of entries in the airFMModStatusTable.
1.3.6.1.4.1.318.1.1.13.1.5.2.2TableairFMModStatusTablenot-accessiblemandatoryAllows for getting information from each module in the system.
1.3.6.1.4.1.318.1.1.13.1.5.2.2.1RowairFMModStatusEntrynot-accessiblemandatoryThe module to get information from.
1.3.6.1.4.1.318.1.1.13.1.5.2.2.1.1ColumnairFMModStatusModuleIndexread-onlymandatoryThe index of the module.
1.3.6.1.4.1.318.1.1.13.1.5.2.2.1.2ColumnairFMModSupplyTempCread-onlymandatoryThe temperature measured at the supply sensor. Measured in tenths of degrees Celsius. A value of -2147483648 indicates that this OID does not apply to this dev…
1.3.6.1.4.1.318.1.1.13.1.5.2.2.1.3ColumnairFMModSupplyTempFread-onlymandatoryThe temperature measured at the supply sensor. Measured in tenths of degrees Fahrenheit. A value of -2147483648 indicates that this OID does not apply to this …
1.3.6.1.4.1.318.1.1.13.1.5.2.2.1.4ColumnairFMModSupplyHumread-onlymandatoryThe humidity measured at the supply sensor. Measured in tenths of percent relative humidity. A value of -2147483648 indicates that this OID does not apply to t…
1.3.6.1.4.1.318.1.1.13.1.5.2.2.1.5ColumnairFMModReturnTempCread-onlymandatoryThe temperature measured at the return sensor. Measured in tenths of degrees Celsius. A value of -2147483648 indicates that this OID does not apply to this dev…
1.3.6.1.4.1.318.1.1.13.1.5.2.2.1.6ColumnairFMModReturnTempFread-onlymandatoryThe temperature measured at the return sensor. Measured in tenths of degrees Fahrenheit. A value of -2147483648 indicates that this OID does not apply to this …
1.3.6.1.4.1.318.1.1.13.1.5.2.2.1.7ColumnairFMModReturnHumread-onlymandatoryThe humidity measured at the return sensor. Measured in tenths of percent relative humidity. A value of -2147483648 indicates that this OID does not apply to t…
1.3.6.1.4.1.318.1.1.13.1.5.2.2.1.8ColumnairFMModFilterDiffPresParead-onlymandatoryThe difference in pressure on either side of the air filters. A high differential pressure indicates a clogged filter. Measured in Pascals. A value of -2147483…
1.3.6.1.4.1.318.1.1.13.1.5.2.2.1.9ColumnairFMModFilterDiffPresInWCread-onlymandatoryThe difference in pressure on either side of the air filters. A high differential pressure indicates a clogged filter. Measured in hundredths of inches water c…
1.3.6.1.4.1.318.1.1.13.1.5.2.2.1.10ColumnairFMModCoilDiffPresParead-onlymandatoryThe difference in pressure on either side of the cooling/dehumidification coils. Measured in Pascals. A value of -2147483648 indicates that this OID does not a…
1.3.6.1.4.1.318.1.1.13.1.5.2.2.1.11ColumnairFMModCoilDiffPresInWCread-onlymandatoryThe difference in pressure on either side of the cooling/dehumidification coils. Measured in hundredths of inches water column. A value of -2147483648 indicate…
1.3.6.1.4.1.318.1.1.13.1.5.3NodeairFMModProperties
1.3.6.1.4.1.318.1.1.13.1.5.3.1ScalarairFMModPropTableSizeread-onlymandatoryThe number of entries in the airFMModPropTable.
1.3.6.1.4.1.318.1.1.13.1.5.3.2TableairFMModPropTablenot-accessiblemandatoryAllows for getting information from each module in the system.
1.3.6.1.4.1.318.1.1.13.1.5.3.2.1RowairFMModPropEntrynot-accessiblemandatoryThe module to get information from.
1.3.6.1.4.1.318.1.1.13.1.5.3.2.1.1ColumnairFMModPropModuleIndexread-onlymandatoryThe index of the module.
1.3.6.1.4.1.318.1.1.13.1.5.3.2.1.2ColumnairFMModOutputCapacityread-onlymandatoryThe cooling capacity (in Kilowatts) of the displayed Module. A value of notApplicable indicates that this OID does not apply to this device due to its configur…
1.3.6.1.4.1.318.1.1.13.1.5.3.2.1.3ColumnairFMModCapacityCtrlread-onlymandatoryThe method used to load and unload the compressors. Tandem compressor Modules use two stages (one compressor each). Single compressor Modules use hot gas bypas…
1.3.6.1.4.1.318.1.1.13.1.5.3.2.1.4ColumnairFMModHeaterTyperead-onlymandatoryThe type of reheating device installed in this Module. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
1.3.6.1.4.1.318.1.1.13.1.5.3.2.1.5ColumnairFMModElectricHeaterTyperead-onlymandatoryThe type/capacity of the electric heater, if installed. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
1.3.6.1.4.1.318.1.1.13.1.5.3.2.1.6ColumnairFMModHumidifierTyperead-onlymandatoryThe type of equipment installed in the Module to run the humidification mode. A value of notApplicable indicates that this OID does not apply to this device du…
1.3.6.1.4.1.318.1.1.13.1.5.3.2.1.7ColumnairFMModBlwrFreqSettingread-onlymandatoryFrequency of the blower in tenths of hertz. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration.
1.3.6.1.4.1.318.1.1.13.1.5.3.2.1.8ColumnairFMModNomCoilDiffPresParead-onlymandatoryThe difference in pressure on either side of the cooling/dehumidification coils. Measured in Pascals. A value of -2147483648 indicates that this OID does not a…
1.3.6.1.4.1.318.1.1.13.1.5.3.2.1.9ColumnairFMModNomCoilDiffPresInWCread-onlymandatoryThe difference in pressure on either side of the cooling/dehumidification coils. Measured in hundredths of inches water column. A value of -2147483648 indicate…
1.3.6.1.4.1.318.1.1.13.1.5.3.2.1.10ColumnairFMModCondPumpread-onlymandatoryIndicates the presence of a condensate pump in the Modules of this System. A value of notApplicable indicates that this OID does not apply to this device due t…
1.3.6.1.4.1.318.1.1.13.1.5.3.2.1.11ColumnairFMModFireDetectorread-onlymandatoryIndicates the presence of a fire detector for each of the Modules in this System. A value of notApplicable indicates that this OID does not apply to this devic…
1.3.6.1.4.1.318.1.1.13.1.5.3.2.1.12ColumnairFMModSmokeDetectorread-onlymandatoryIndicates the presence of a smoke detector for each of the Modules in this System. A value of notApplicable indicates that this OID does not apply to this devi…
1.3.6.1.4.1.318.1.1.13.1.5.3.2.1.13ColumnairFMModWaterDetectorread-onlymandatoryIndicates the presence of a water leak detector for each of the Modules in this System. A value of notApplicable indicates that this OID does not apply to this…
1.3.6.1.4.1.318.1.1.13.1.5.4NodeairFMModCooling
1.3.6.1.4.1.318.1.1.13.1.5.4.1ScalarairFMModCoolTableSizeread-onlymandatoryThe number of entries in the airFMModCoolTable.
1.3.6.1.4.1.318.1.1.13.1.5.4.2TableairFMModCoolTablenot-accessiblemandatoryAllows for getting information from each module in the system.
1.3.6.1.4.1.318.1.1.13.1.5.4.2.1RowairFMModCoolEntrynot-accessiblemandatoryThe module to get information from.
1.3.6.1.4.1.318.1.1.13.1.5.4.2.1.1ColumnairFMModCoolModuleIndexread-onlymandatoryThe index of the module.
1.3.6.1.4.1.318.1.1.13.1.5.4.2.1.2ColumnairFMModComp1read-onlymandatoryThe status of compressor 1 of the tandem compressor unit (on or off). A value of notApplicable indicates that this OID does not apply to this device due to its…
1.3.6.1.4.1.318.1.1.13.1.5.4.2.1.3ColumnairFMModComp2read-onlymandatoryThe status of compressor 2 of the tandem compressor unit (on or off). A value of notApplicable indicates that this OID does not apply to this device due to its…
1.3.6.1.4.1.318.1.1.13.1.5.4.2.1.4ColumnairFMModSuctPresKParead-onlymandatoryThe refrigerant pressure measured at the suction inlet of the compressor. Measured in kiloPascals. A value of -2147483648 indicates that this OID does not appl…
1.3.6.1.4.1.318.1.1.13.1.5.4.2.1.5ColumnairFMModSuctPresPSIread-onlymandatoryThe refrigerant pressure measured at the suction inlet of the compressor. Measured in pounds per square inch. A value of -2147483648 indicates that this OID do…
1.3.6.1.4.1.318.1.1.13.1.5.4.2.1.6ColumnairFMModDischPresKParead-onlymandatoryThe refrigerant pressure measured at the discharge outlet of the compressor. Measured in kiloPascals. A value of -2147483648 indicates that this OID does not a…
1.3.6.1.4.1.318.1.1.13.1.5.4.2.1.7ColumnairFMModDischPresPSIread-onlymandatoryThe refrigerant pressure measured at the discharge outlet of the compressor. Measured in pounds per square inch. A value of -2147483648 indicates that this OID…
1.3.6.1.4.1.318.1.1.13.1.5.4.2.1.8ColumnairFMModCondFluidVlvPosread-onlymandatoryThe position of the condenser fluid valve. The valve regulates the flow of liquid coolant into the heat exchanger (condenser). 100% indicates the valve is comp…
1.3.6.1.4.1.318.1.1.13.1.5.4.2.1.9ColumnairFMModCoilFluidVlvPosread-onlymandatoryThe position of the coil fluid valve. The valve regulates the flow of liquid coolant in the fluid cooling coil (MultiCool, Economizer, or Chilled Water). 100% …
1.3.6.1.4.1.318.1.1.13.1.5.5NodeairFMModHumidity
1.3.6.1.4.1.318.1.1.13.1.5.5.1ScalarairFMModHumTableSizeread-onlymandatoryThe number of entries in the airFMModHumTable.
1.3.6.1.4.1.318.1.1.13.1.5.5.2TableairFMModHumTablenot-accessiblemandatoryAllows for getting information from each module in the system.
1.3.6.1.4.1.318.1.1.13.1.5.5.2.1RowairFMModHumEntrynot-accessiblemandatoryThe module to get information from.
1.3.6.1.4.1.318.1.1.13.1.5.5.2.1.1ColumnairFMModHumModuleIndexread-onlymandatoryThe index of the module.
1.3.6.1.4.1.318.1.1.13.1.5.5.2.1.2ColumnairFMModHumidifierread-onlymandatoryThe type of equipment installed in the Module to run the humidification mode. A value of notApplicable indicates that this OID does not apply to this device du…
1.3.6.1.4.1.318.1.1.13.1.5.5.2.1.3ColumnairFMModElectrodeCurrentread-onlymandatoryThe current drawn by the electrodes of the steam cylinder humidifier. Measured in tenths of amps. A value of -2147483648 indicates that this OID does not apply…
1.3.6.1.4.1.318.1.1.13.1.5.5.2.1.4ColumnairFMModHumActualOutputread-onlymandatoryThe humidification output of an individual Module. Measured in percent. A value of -2147483648 indicates that this OID does not apply to this device due to its…
1.3.6.1.4.1.318.1.1.13.1.5.5.2.1.5ColumnairFMModWaterConductivityread-onlymandatoryThe conductivity of the water in the humidifier cylinder. Measured in microSiemens per centimeter. A value of -2147483648 indicates that this OID does not appl…
1.3.6.1.4.1.318.1.1.13.1.5.5.2.1.6ColumnairFMModHotWaterVlvPosread-onlymandatoryThe position of the hot water valve. 100% indicates the valve is completely open, and 0% indicates that the valve is closed. Measured in percent. A value of -2…
1.3.6.1.4.1.318.1.1.13.1.5.5.2.1.7ColumnairFMModStmElectHumModeread-writemandatorySet the humidifier function mode. Off: Remove power from electrodes. Auto: Humidifier controlled by Module controller. Drain: Remove power from electrodes and …
1.3.6.1.4.1.318.1.1.13.1.5.6NodeairFMModBlower1
1.3.6.1.4.1.318.1.1.13.1.5.6.1ScalarairFMModBlwr1TableSizeread-onlymandatoryThe number of entries in the airFMModBlwr1Table.
1.3.6.1.4.1.318.1.1.13.1.5.6.2TableairFMModBlwr1Tablenot-accessiblemandatoryAllows for getting information from each module in the system.
1.3.6.1.4.1.318.1.1.13.1.5.6.2.1RowairFMModBlwr1Entrynot-accessiblemandatoryThe module to get information from.
1.3.6.1.4.1.318.1.1.13.1.5.6.2.1.1ColumnairFMModBlwr1ModuleIndexread-onlymandatoryThe index of the module.
1.3.6.1.4.1.318.1.1.13.1.5.6.2.1.2ColumnairFMModBlwr1CtrlTyperead-onlymandatoryThe type of blower controller. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
1.3.6.1.4.1.318.1.1.13.1.5.6.2.1.3ColumnairFMModBlwr1CmdFreqread-onlymandatoryThe requested operating frequency for the blower. Measured in tenths of hertz. A value of -2147483648 indicates that this OID does not apply to this device due…
1.3.6.1.4.1.318.1.1.13.1.5.6.2.1.4ColumnairFMModBlwr1ActFreqread-onlymandatoryThe frequency at which the blower controller is operating. Measured in tenths of hertz. A value of -2147483648 indicates that this OID does not apply to this d…
1.3.6.1.4.1.318.1.1.13.1.5.6.2.1.5ColumnairFMModBlwr1Polesread-onlymandatoryThe number of poles of the blower motor that the blower controller is controlling. A value of -2147483648 indicates that this OID does not apply to this device…
1.3.6.1.4.1.318.1.1.13.1.5.6.2.1.6ColumnairFMModBlwr1RatedHorsePowerread-onlymandatoryThe power rating of the blower motor. Measured in hundredths of horsepower. A value of -2147483648 indicates that this OID does not apply to this device due to…
1.3.6.1.4.1.318.1.1.13.1.5.6.2.1.7ColumnairFMModBlwr1RatedCurrentread-onlymandatoryThe current rating of the blower motor. Measured in hundredths of amps. A value of -2147483648 indicates that this OID does not apply to this device due to its…
1.3.6.1.4.1.318.1.1.13.1.5.6.2.1.8ColumnairFMModBlwr1ActTorqread-onlymandatoryThe actual torque of the blower motor. Measured in hundredths of percent. A value of -2147483648 indicates that this OID does not apply to this device due to i…
1.3.6.1.4.1.318.1.1.13.1.5.6.2.1.9ColumnairFMModBlwr1Currentread-onlymandatoryThe percent of rated current drawn by the blower motor. Measured in hundredths of percent. A value of -2147483648 indicates that this OID does not apply to thi…
1.3.6.1.4.1.318.1.1.13.1.5.6.2.1.10ColumnairFMModBlwr1Vltread-onlymandatoryThe voltage supplied to the blower motor. Measured in tenths of volts RMS. A value of -2147483648 indicates that this OID does not apply to this device due to …
1.3.6.1.4.1.318.1.1.13.1.5.6.2.1.11ColumnairFMModBlwr1DCLinkVltread-onlymandatoryThe voltage of the blower controller's DC bus. Measured in volts DC. A value of -2147483648 indicates that this OID does not apply to this device due to its co…
1.3.6.1.4.1.318.1.1.13.1.5.6.2.1.12ColumnairFMModBlwr1AccTimeread-onlymandatoryThe time to accelerate the blower to the specified frequency. Measured in tenths of seconds. A value of -2147483648 indicates that this OID does not apply to t…
1.3.6.1.4.1.318.1.1.13.1.5.6.2.1.13ColumnairFMModBlwr1DecTimeread-onlymandatoryThe time to decelerate the blower frequency to zero. Measured in tenths of seconds. A value of -2147483648 indicates that this OID does not apply to this devic…
1.3.6.1.4.1.318.1.1.13.1.5.6.2.1.14ColumnairFMModBlwr1CapLiferead-onlymandatoryThe remaining life of the main circuit capacitor. Measured in tenths of percent. A value of -2147483648 indicates that this OID does not apply to this device d…
1.3.6.1.4.1.318.1.1.13.1.5.6.2.1.15ColumnairFMModBlwr1CtrlCoolFanLiferead-onlymandatoryThe total operation time of the blower controller cooling fan. Measured in hours. A value of -2147483648 indicates that this OID does not apply to this device …
1.3.6.1.4.1.318.1.1.13.1.5.6.2.1.16ColumnairFMModBlwr1ElOvModeread-onlymandatoryEnables or disables the electronic overload relay. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
1.3.6.1.4.1.318.1.1.13.1.5.6.2.1.17ColumnairFMModBlwr1ElOvSettingread-onlymandatoryThe electronic overload relay is activated when the current exceeds this threshold. Measured in hundredths of amps. A value of -2147483648 indicates that this …
1.3.6.1.4.1.318.1.1.13.1.5.6.2.1.18ColumnairFMModBlwr1ElOvTimeConstread-onlymandatoryThe delay between the current exceeding the overload threshold and the activation of the electronic overload relay. Measured in tenths of minutes. A value of -…
1.3.6.1.4.1.318.1.1.13.1.5.6.2.1.19ColumnairFMModBlwr1FanPowerread-onlymandatoryThe actual power of the blower motor. Measured in tenths of percent. A value of -2147483648 indicates that this OID does not apply to this device due to its co…
1.3.6.1.4.1.318.1.1.13.1.5.6.2.1.20ColumnairFMModBlwr1HeatsinkTempCread-onlymandatoryThe temperature of the heatsink on the blower controller. Measured in degrees Celsius. A value of -2147483648 indicates that this OID does not apply to this de…
1.3.6.1.4.1.318.1.1.13.1.5.6.2.1.21ColumnairFMModBlwr1HeatsinkTempFread-onlymandatoryThe temperature of the heatsink on the blower controller. Measured in degrees Fahrenheit. A value of -2147483648 indicates that this OID does not apply to this…
1.3.6.1.4.1.318.1.1.13.1.5.6.2.1.22ColumnairFMModBlwr1ChokeTempCread-onlymandatoryThe temperature of the choke on the blower controller. Measured in degrees Celsius. A value of -2147483648 indicates that this OID does not apply to this devic…
1.3.6.1.4.1.318.1.1.13.1.5.6.2.1.23ColumnairFMModBlwr1ChokeTempFread-onlymandatoryThe temperature of the choke on the blower controller. Measured in degrees Fahrenheit. A value of -2147483648 indicates that this OID does not apply to this de…
1.3.6.1.4.1.318.1.1.13.1.5.6.2.1.24ColumnairFMModBlwr1InverterTempCread-onlymandatoryThe temperature of the inverter on the blower controller. Measured in degrees Celsius. A value of -2147483648 indicates that this OID does not apply to this de…
1.3.6.1.4.1.318.1.1.13.1.5.6.2.1.25ColumnairFMModBlwr1InverterTempFread-onlymandatoryThe temperature of the inverter on the blower controller. Measured in degrees Fahrenheit. A value of -2147483648 indicates that this OID does not apply to this…
1.3.6.1.4.1.318.1.1.13.1.5.7NodeairFMModBlower2
1.3.6.1.4.1.318.1.1.13.1.5.7.1ScalarairFMModBlwr2TableSizeread-onlymandatoryThe number of entries in the airFMModBlwr2Table.
1.3.6.1.4.1.318.1.1.13.1.5.7.2TableairFMModBlwr2Tablenot-accessiblemandatoryAllows for getting information from each module in the system.
1.3.6.1.4.1.318.1.1.13.1.5.7.2.1RowairFMModBlwr2Entrynot-accessiblemandatoryThe module to get information from.
1.3.6.1.4.1.318.1.1.13.1.5.7.2.1.1ColumnairFMModBlwr2ModuleIndexread-onlymandatoryThe index of the module.
1.3.6.1.4.1.318.1.1.13.1.5.7.2.1.2ColumnairFMModBlwr2CtrlTyperead-onlymandatoryThe type of blower controller. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
1.3.6.1.4.1.318.1.1.13.1.5.7.2.1.3ColumnairFMModBlwr2CmdFreqread-onlymandatoryThe requested operating frequency for the blower. Measured in tenths of hertz. A value of -2147483648 indicates that this OID does not apply to this device due…
1.3.6.1.4.1.318.1.1.13.1.5.7.2.1.4ColumnairFMModBlwr2ActFreqread-onlymandatoryThe frequency at which the blower controller is operating. Measured in tenths of hertz. A value of -2147483648 indicates that this OID does not apply to this d…
1.3.6.1.4.1.318.1.1.13.1.5.7.2.1.5ColumnairFMModBlwr2Polesread-onlymandatoryThe number of poles of the blower motor that the blower controller is controlling. A value of -2147483648 indicates that this OID does not apply to this device…
1.3.6.1.4.1.318.1.1.13.1.5.7.2.1.6ColumnairFMModBlwr2RatedHorsePowerread-onlymandatoryThe power rating of the blower motor. Measured in hundredths of horsepower. A value of -2147483648 indicates that this OID does not apply to this device due to…
1.3.6.1.4.1.318.1.1.13.1.5.7.2.1.7ColumnairFMModBlwr2RatedCurrentread-onlymandatoryThe current rating of the blower motor. Measured in hundredths of amps. A value of -2147483648 indicates that this OID does not apply to this device due to its…
1.3.6.1.4.1.318.1.1.13.1.5.7.2.1.8ColumnairFMModBlwr2ActTorqread-onlymandatoryThe actual torque of the blower motor. Measured in hundredths of percent. A value of -2147483648 indicates that this OID does not apply to this device due to i…
1.3.6.1.4.1.318.1.1.13.1.5.7.2.1.9ColumnairFMModBlwr2Currentread-onlymandatoryThe percent of rated current drawn by the blower motor. Measured in hundredths of percent. A value of -2147483648 indicates that this OID does not apply to thi…
1.3.6.1.4.1.318.1.1.13.1.5.7.2.1.10ColumnairFMModBlwr2Vltread-onlymandatoryThe voltage supplied to the blower motor. Measured in tenths of volts RMS. A value of -2147483648 indicates that this OID does not apply to this device due to …
1.3.6.1.4.1.318.1.1.13.1.5.7.2.1.11ColumnairFMModBlwr2DCLinkVltread-onlymandatoryThe voltage of the blower controller's DC bus. Measured in volts DC. A value of -2147483648 indicates that this OID does not apply to this device due to its co…
1.3.6.1.4.1.318.1.1.13.1.5.7.2.1.12ColumnairFMModBlwr2AccTimeread-onlymandatoryThe time to accelerate the blower to the specified frequency. Measured in tenths of seconds. A value of -2147483648 indicates that this OID does not apply to t…
1.3.6.1.4.1.318.1.1.13.1.5.7.2.1.13ColumnairFMModBlwr2DecTimeread-onlymandatoryThe time to decelerate the blower frequency to zero. Measured in tenths of seconds. A value of -2147483648 indicates that this OID does not apply to this devic…
1.3.6.1.4.1.318.1.1.13.1.5.7.2.1.14ColumnairFMModBlwr2CapLiferead-onlymandatoryThe remaining life of the main circuit capacitor. Measured in tenths of percent. A value of -2147483648 indicates that this OID does not apply to this device d…
1.3.6.1.4.1.318.1.1.13.1.5.7.2.1.15ColumnairFMModBlwr2CtrlCoolFanLiferead-onlymandatoryThe total operation time of the blower controller cooling fan. Measured in hours. A value of -2147483648 indicates that this OID does not apply to this device …
1.3.6.1.4.1.318.1.1.13.1.5.7.2.1.16ColumnairFMModBlwr2ElOvModeread-onlymandatoryEnables or disables the electronic overload relay. A value of notApplicable indicates that this OID does not apply to this device due to its configuration.
1.3.6.1.4.1.318.1.1.13.1.5.7.2.1.17ColumnairFMModBlwr2ElOvSettingread-onlymandatoryThe electronic overload relay is activated when the current exceeds this threshold. Measured in hundredths of amps. A value of -2147483648 indicates that this …
1.3.6.1.4.1.318.1.1.13.1.5.7.2.1.18ColumnairFMModBlwr2ElOvTimeConstread-onlymandatoryThe delay between the current exceeding the overload threshold and the activation of the electronic overload relay. Measured in tenths of minutes. A value of -…
1.3.6.1.4.1.318.1.1.13.1.5.7.2.1.19ColumnairFMModBlwr2FanPowerread-onlymandatoryThe actual power of the blower motor. Measured in tenths of percent. A value of -2147483648 indicates that this OID does not apply to this device due to its co…
1.3.6.1.4.1.318.1.1.13.1.5.7.2.1.20ColumnairFMModBlwr2HeatsinkTempCread-onlymandatoryThe temperature of the heatsink on the blower controller. Measured in degrees Celsius. A value of -2147483648 indicates that this OID does not apply to this de…
1.3.6.1.4.1.318.1.1.13.1.5.7.2.1.21ColumnairFMModBlwr2HeatsinkTempFread-onlymandatoryThe temperature of the heatsink on the blower controller. Measured in degrees Fahrenheit. A value of -2147483648 indicates that this OID does not apply to this…
1.3.6.1.4.1.318.1.1.13.1.5.7.2.1.22ColumnairFMModBlwr2ChokeTempCread-onlymandatoryThe temperature of the choke on the blower controller. Measured in degrees Celsius. A value of -2147483648 indicates that this OID does not apply to this devic…
1.3.6.1.4.1.318.1.1.13.1.5.7.2.1.23ColumnairFMModBlwr2ChokeTempFread-onlymandatoryThe temperature of the choke on the blower controller. Measured in degrees Fahrenheit. A value of -2147483648 indicates that this OID does not apply to this de…
1.3.6.1.4.1.318.1.1.13.1.5.7.2.1.24ColumnairFMModBlwr2InverterTempCread-onlymandatoryThe temperature of the inverter on the blower controller. Measured in degrees Celsius. A value of -2147483648 indicates that this OID does not apply to this de…
1.3.6.1.4.1.318.1.1.13.1.5.7.2.1.25ColumnairFMModBlwr2InverterTempFread-onlymandatoryThe temperature of the inverter on the blower controller. Measured in degrees Fahrenheit. A value of -2147483648 indicates that this OID does not apply to this…
1.3.6.1.4.1.318.1.1.13.1.5.8NodeairFMModRunHours
1.3.6.1.4.1.318.1.1.13.1.5.8.1ScalarairFMModRHTableSizeread-onlymandatoryThe number of entries in the airFMModRHTable.
1.3.6.1.4.1.318.1.1.13.1.5.8.2TableairFMModRHTablenot-accessiblemandatoryAllows for getting information from each module in the system.
1.3.6.1.4.1.318.1.1.13.1.5.8.2.1RowairFMModRHEntrynot-accessiblemandatoryThe module to get information from.
1.3.6.1.4.1.318.1.1.13.1.5.8.2.1.1ColumnairFMModRHModuleIndexread-onlymandatoryThe index of the module.
1.3.6.1.4.1.318.1.1.13.1.5.8.2.1.2ColumnairFMModRHComp1read-onlymandatoryCompressor 1 run hours. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration.
1.3.6.1.4.1.318.1.1.13.1.5.8.2.1.3ColumnairFMModRHComp2read-onlymandatoryCompressor 2 run hours. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration.
1.3.6.1.4.1.318.1.1.13.1.5.8.2.1.4ColumnairFMModRHHeaterread-onlymandatoryHeater run hours. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration.
1.3.6.1.4.1.318.1.1.13.1.5.8.2.1.5ColumnairFMModRHHumread-onlymandatoryHumidifier run hours A value of -2147483648 indicates that this OID does not apply to this device due to its configuration.
1.3.6.1.4.1.318.1.1.13.1.5.8.2.1.6ColumnairFMModRHBlwr1read-onlymandatoryBlower 1 run hours. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration.
1.3.6.1.4.1.318.1.1.13.1.5.8.2.1.7ColumnairFMModRHBlwr2read-onlymandatoryBlower 2 run hours. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration.
1.3.6.1.4.1.318.1.1.13.1.5.8.2.1.8ColumnairFMModRHBlwrCtrl1read-onlymandatoryBlower Controller 1 run hours. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration.
1.3.6.1.4.1.318.1.1.13.1.5.8.2.1.9ColumnairFMModRHBlwrCtrl2read-onlymandatoryBlower Controller 2 run hours. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration.
1.3.6.1.4.1.318.1.1.13.1.5.8.2.1.10ColumnairFMModRHComp1Resetread-writemandatoryReset the compressor 1 run hours. Getting this OID will do nothing and return the noOperation value. A value of notApplicable indicates that this OID does not …
1.3.6.1.4.1.318.1.1.13.1.5.8.2.1.11ColumnairFMModRHComp2Resetread-writemandatoryReset the compressor 2 run hours. Getting this OID will do nothing and return the noOperation value. A value of notApplicable indicates that this OID does not …
1.3.6.1.4.1.318.1.1.13.1.5.8.2.1.12ColumnairFMModRHHeaterResetread-writemandatoryReset the heater run hours. Getting this OID will do nothing and return the noOperation value. A value of notApplicable indicates that this OID does not apply …
1.3.6.1.4.1.318.1.1.13.1.5.8.2.1.13ColumnairFMModRHHumResetread-writemandatoryReset the humidifier run hours. Getting this OID will do nothing and return the noOperation value. A value of notApplicable indicates that this OID does not ap…
1.3.6.1.4.1.318.1.1.13.1.5.8.2.1.14ColumnairFMModRHBlwr1Resetread-writemandatoryReset the blower 1 run hours. Getting this OID will do nothing and return the noOperation value. A value of notApplicable indicates that this OID does not appl…
1.3.6.1.4.1.318.1.1.13.1.5.8.2.1.15ColumnairFMModRHBlwr2Resetread-writemandatoryReset the blower 2 run hours. Getting this OID will do nothing and return the noOperation value. A value of notApplicable indicates that this OID does not appl…
1.3.6.1.4.1.318.1.1.13.1.5.9NodeairFMModServIntervals
1.3.6.1.4.1.318.1.1.13.1.5.9.1ScalarairFMModServIntComp1read-writemandatoryThe interval at which to generate a maintenance alarm for compressor 1. Values stored in increments of 100 hours. A value of -2147483648 indicates that this OI…
1.3.6.1.4.1.318.1.1.13.1.5.9.2ScalarairFMModServIntComp2read-writemandatoryThe interval at which to generate a maintenance alarm for compressor 2. Values stored in increments of 100 hours. A value of -2147483648 indicates that this OI…
1.3.6.1.4.1.318.1.1.13.1.5.9.3ScalarairFMModServIntHeaterread-writemandatoryThe interval at which to generate a maintenance alarm for the reheat components. Values stored in increments of 100 hours. A value of -2147483648 indicates tha…
1.3.6.1.4.1.318.1.1.13.1.5.9.4ScalarairFMModServIntHumread-writemandatoryThe interval at which to generate a maintenance alarm for the humidifier. Values stored in increments of 100 hours. A value of -2147483648 indicates that this …
1.3.6.1.4.1.318.1.1.13.1.5.9.5ScalarairFMModServIntBlwr1read-writemandatoryThe interval at which to generate a maintenance alarm for blower 1. Values stored in increments of 100 hours. A value of -2147483648 indicates that this OID do…
1.3.6.1.4.1.318.1.1.13.1.5.9.6ScalarairFMModServIntBlwr2read-writemandatoryThe interval at which to generate a maintenance alarm for blower 2. Values stored in increments of 100 hours. A value of -2147483648 indicates that this OID do…
1.3.6.1.4.1.318.1.1.13.1.5.9.7ScalarairFMModServIntBlwrCtrl1read-writemandatoryThe interval at which to generate a maintenance alarm for blower controller 1. Values stored in increments of 100 hours. A value of -2147483648 indicates that …
1.3.6.1.4.1.318.1.1.13.1.5.9.8ScalarairFMModServIntBlwrCtrl2read-writemandatoryThe interval at which to generate a maintenance alarm for blower controller 2. Values stored in increments of 100 hours. A value of -2147483648 indicates that …
1.3.6.1.4.1.318.1.1.13.1.5.10NodeairFMModServIntResets
1.3.6.1.4.1.318.1.1.13.1.5.10.1ScalarairFMModServIntResetTableSizeread-onlymandatoryThe number of entries in the airFMModServIntTable.
1.3.6.1.4.1.318.1.1.13.1.5.10.2TableairFMModServIntResetTablenot-accessiblemandatoryAllows for getting information from each module in the system.
1.3.6.1.4.1.318.1.1.13.1.5.10.2.1RowairFMModServIntResetEntrynot-accessiblemandatoryThe module to get information from.
1.3.6.1.4.1.318.1.1.13.1.5.10.2.1.1ColumnairFMModServIntResetModuleIndexread-onlymandatoryThe index of the module.
1.3.6.1.4.1.318.1.1.13.1.5.10.2.1.2ColumnairFMModServIntComp1Resetread-writemandatoryReset the compressor 1 service interval maintenance alarm. Getting this OID will do nothing and return the noOperation value. A value of notApplicable indicate…
1.3.6.1.4.1.318.1.1.13.1.5.10.2.1.3ColumnairFMModServIntComp2Resetread-writemandatoryReset the compressor 2 service interval maintenance alarm. Getting this OID will do nothing and return the noOperation value. A value of notApplicable indicate…
1.3.6.1.4.1.318.1.1.13.1.5.10.2.1.4ColumnairFMModServIntHeaterResetread-writemandatoryReset the heater service interval maintenance alarm. Getting this OID will do nothing and return the noOperation value. A value of notApplicable indicates that…
1.3.6.1.4.1.318.1.1.13.1.5.10.2.1.5ColumnairFMModServIntHumResetread-writemandatoryReset the humidifier service interval maintenance alarm. Getting this OID will do nothing and return the noOperation value. A value of notApplicable indicates …
1.3.6.1.4.1.318.1.1.13.1.5.10.2.1.6ColumnairFMModServIntBlwr1Resetread-writemandatoryReset the blower 1 service interval maintenance alarm. Getting this OID will do nothing and return the noOperation value. A value of notApplicable indicates th…
1.3.6.1.4.1.318.1.1.13.1.5.10.2.1.7ColumnairFMModServIntBlwr2Resetread-writemandatoryReset the blower 2 service interval maintenance alarm. Getting this OID will do nothing and return the noOperation value. A value of notApplicable indicates th…
1.3.6.1.4.1.318.1.1.13.1.5.10.2.1.8ColumnairFMModServIntBlwrCtrl1Resetread-writemandatoryReset the blower controller 1 service interval maintenance alarm. Getting this OID will do nothing and return the noOperation value. A value of notApplicable i…
1.3.6.1.4.1.318.1.1.13.1.5.10.2.1.9ColumnairFMModServIntBlwrCtrl2Resetread-writemandatoryReset the blower controller 2 service interval maintenance alarm. Getting this OID will do nothing and return the noOperation value. A value of notApplicable i…
1.3.6.1.4.1.318.1.1.13.1.6NodeairFMAlarms
1.3.6.1.4.1.318.1.1.13.1.6.1ScalarairFMAlarmClearActiveGroupAlarmsread-writemandatoryClear active group alarms. If alarm conditions are still present, new alarms will be generated for those conditions. Getting this OID will do nothing and retur…
1.3.6.1.4.1.318.1.1.13.1.6.2ScalarairFMAlarmClearActiveSysModAlarmsread-writemandatoryClear active system and module alarms. If alarm conditions are still present, new alarms will be generated for those conditions. Getting this OID will do nothi…
1.3.6.1.4.1.318.1.1.13.1.6.3ScalarairFMAlarmConditionsTableSizeread-onlymandatoryThe number of active alarm conditions in the airFMAlarmConditionTable.
1.3.6.1.4.1.318.1.1.13.1.6.4TableairFMAlarmConditionsTablenot-accessiblemandatoryTable of active alarm conditions for the device.
1.3.6.1.4.1.318.1.1.13.1.6.4.1RowairFMAlarmConditionsEntrynot-accessiblemandatoryAlarm condition specification
1.3.6.1.4.1.318.1.1.13.1.6.4.1.1ColumnairFMAlarmConditionsIndexread-onlymandatoryAlarm condition index.
1.3.6.1.4.1.318.1.1.13.1.6.4.1.2ColumnairFMAlarmSeverityread-onlymandatorySeverity of the alarm.
1.3.6.1.4.1.318.1.1.13.1.6.4.1.3ColumnairFMAlarmTyperead-onlymandatoryType of alarm.
1.3.6.1.4.1.318.1.1.13.1.6.4.1.4ColumnairFMEventCoderead-onlymandatoryAPC event code for the alarm.
1.3.6.1.4.1.318.1.1.13.1.6.4.1.5ColumnairFMAlarmDateread-onlymandatoryDate the alarm was recorded.
1.3.6.1.4.1.318.1.1.13.1.6.4.1.6ColumnairFMAlarmTimeread-onlymandatoryTime the alarm was recorded.
1.3.6.1.4.1.318.1.1.13.1.6.4.1.7ColumnairFMAlarmDescriptionread-onlymandatoryDescription of the alarm.
1.3.6.1.4.1.318.1.1.13.2NodeairPA
1.3.6.1.4.1.318.1.1.13.2.1NodeairPAIdent
1.3.6.1.4.1.318.1.1.13.2.1.1ScalarairPAIdentNameread-onlymandatoryA character string identifying the device name.
1.3.6.1.4.1.318.1.1.13.2.1.2ScalarairPAModelNumberread-onlymandatoryA character string identifying the device model number.
1.3.6.1.4.1.318.1.1.13.2.1.3ScalarairPADateOfManufactureread-onlymandatoryA character string identifying when the device was produced.
1.3.6.1.4.1.318.1.1.13.2.1.4ScalarairPASerialNumberread-onlymandatoryA character string identifying the device serial number.
1.3.6.1.4.1.318.1.1.13.2.1.5ScalarairPAFirmwareRevisionread-onlymandatoryA character string identifying the device firmware revision.
1.3.6.1.4.1.318.1.1.13.2.1.6ScalarairPAHardwareRevisionread-onlymandatoryA character string identifying the device hardware revision.
1.3.6.1.4.1.318.1.1.13.2.2NodeairPAStatus
1.3.6.1.4.1.318.1.1.13.2.2.1ScalarairPASystemPowerread-onlymandatoryThe status of the unit's system power setting. ON(1) The system power is turned on. OFF(2) The system power is turned off.
1.3.6.1.4.1.318.1.1.13.2.2.2ScalarairPAOperatingModeread-onlymandatoryThe current operating mode of the unit. OFF(1) The system is off. VENTING(2) The system's venting function is active. COOLING(3) The system's cooling function …
1.3.6.1.4.1.318.1.1.13.2.2.3ScalarairPASetpointTempFread-onlymandatoryThe temperature setpoint in Fahrenheit to which the unit is controlling.
1.3.6.1.4.1.318.1.1.13.2.2.4ScalarairPASetpointTempCread-onlymandatoryThe temperature setpoint in Celsius to which the unity is controlling.
1.3.6.1.4.1.318.1.1.13.2.2.5ScalarairPABlowerSpeedread-onlymandatoryThe unit's blower speed setting. LOW(1) The blower speed is low. HIGH(2) The blower speed is high.
1.3.6.1.4.1.318.1.1.13.2.2.6ScalarairPACompressorread-onlymandatoryThe unit's compressor status. ON(1) The compressor is turned on. OFF(2) The compressor is turned off.
1.3.6.1.4.1.318.1.1.13.2.2.7ScalarairPACondenserFanread-onlymandatoryThe unit's condenser fan status. ON(1) The condenser fan is turned on. OFF(2) The condenser fan is turned off.
1.3.6.1.4.1.318.1.1.13.2.2.8ScalarairPACondensatePumpread-onlymandatoryThe unit's condensate pump status. ON(1) The condensate pump is turned on. OFF(2) The condensate pump is turned off.
1.3.6.1.4.1.318.1.1.13.2.2.9ScalarairPASupplyTempFread-onlymandatoryThe supply temperature in degrees Fahrenheit.
1.3.6.1.4.1.318.1.1.13.2.2.10ScalarairPASupplyTempCread-onlymandatoryThe supply temperature in degrees Celsius.
1.3.6.1.4.1.318.1.1.13.2.2.11ScalarairPAReturnTempFread-onlymandatoryThe return temperature in degrees Fahrenheit.
1.3.6.1.4.1.318.1.1.13.2.2.12ScalarairPAReturnTempCread-onlymandatoryThe return temperature in degrees Celsius.
1.3.6.1.4.1.318.1.1.13.2.2.13ScalarairPARemoteTempFread-onlymandatoryThe remote temperature in degrees Fahrenheit.
1.3.6.1.4.1.318.1.1.13.2.2.14ScalarairPARemoteTempCread-onlymandatoryThe remote temperature in degrees Celsius.
1.3.6.1.4.1.318.1.1.13.2.2.15ScalarairPARemoteHumidityread-onlymandatoryThe remote humidity.
1.3.6.1.4.1.318.1.1.13.3NodeairIR
1.3.6.1.4.1.318.1.1.13.3.1NodeairIRAlarms
1.3.6.1.4.1.318.1.1.13.3.1.1ScalarairIRAlarmConditionsTableSizeread-onlymandatoryThe number of active alarm conditions in the airIRAlarmConditionTable.
1.3.6.1.4.1.318.1.1.13.3.1.2TableairIRAlarmConditionsTablenot-accessiblemandatoryTable of active alarm conditions for the device.
1.3.6.1.4.1.318.1.1.13.3.1.2.1RowairIRAlarmConditionsEntrynot-accessiblemandatoryAlarm condition specification
1.3.6.1.4.1.318.1.1.13.3.1.2.1.1ColumnairIRAlarmConditionsIndexread-onlymandatoryAlarm condition index.
1.3.6.1.4.1.318.1.1.13.3.1.2.1.2ColumnairIREventCoderead-onlymandatoryCode for the alarm.
1.3.6.1.4.1.318.1.1.13.3.1.2.1.3ColumnairIRAlarmDescriptionread-onlymandatoryDescription of the alarm.
1.3.6.1.4.1.318.1.1.13.3.2NodeairIRRC
1.3.6.1.4.1.318.1.1.13.3.2.1NodeairIRRCGroup
1.3.6.1.4.1.318.1.1.13.3.2.1.1NodeairIRRCGroupStatus
1.3.6.1.4.1.318.1.1.13.3.2.1.1.1ScalarairIRRCGroupStatusCoolOutputread-onlymandatoryGroup coolant output in tenths of kW.
1.3.6.1.4.1.318.1.1.13.3.2.1.1.2ScalarairIRRCGroupStatusCoolDemandread-onlymandatoryGroup coolant demand in tenths of kW.
1.3.6.1.4.1.318.1.1.13.3.2.1.1.3ScalarairIRRCGroupStatusAirFlowUSread-onlymandatoryGroup air flow in cubic feet per minute.
1.3.6.1.4.1.318.1.1.13.3.2.1.1.4ScalarairIRRCGroupStatusAirFlowMetricread-onlymandatoryGroup air flow in liters per second.
1.3.6.1.4.1.318.1.1.13.3.2.1.1.5ScalarairIRRCGroupStatusMaxRackInletTempUSread-onlymandatoryGroup maximum rack inlet temperature in tenths of degrees Fahrenheit.
1.3.6.1.4.1.318.1.1.13.3.2.1.1.6ScalarairIRRCGroupStatusMaxRackInletTempMetricread-onlymandatoryGroup maximum rack inlet temperature in tenths of degrees Celsius.
1.3.6.1.4.1.318.1.1.13.3.2.1.1.7ScalarairIRRCGroupStatusMinRackInletTempUSread-onlymandatoryGroup minimum rack inlet temperature in tenths of degrees Fahrenheit.
1.3.6.1.4.1.318.1.1.13.3.2.1.1.8ScalarairIRRCGroupStatusMinRackInletTempMetricread-onlymandatoryGroup minimum rack inlet temperature in tenths of degrees Celsius.
1.3.6.1.4.1.318.1.1.13.3.2.1.1.9ScalarairIRRCGroupStatusActiveFlowControlStatusread-onlymandatoryStatus of the active flow control system.
1.3.6.1.4.1.318.1.1.13.3.2.1.2NodeairIRRCGroupSetpoints
1.3.6.1.4.1.318.1.1.13.3.2.1.2.1ScalarairIRRCGroupSetpointsCoolUSread-writemandatoryGroup cooling setpoint in tenths of degrees Fahrenheit.
1.3.6.1.4.1.318.1.1.13.3.2.1.2.2ScalarairIRRCGroupSetpointsCoolMetricread-writemandatoryGroup cooling setpoint in tenths of degrees Celsius.
1.3.6.1.4.1.318.1.1.13.3.2.1.2.3ScalarairIRRCGroupSetpointsSupplyAirUSread-writemandatoryGroup supply air setpoint in tenths of degrees Fahrenheit.
1.3.6.1.4.1.318.1.1.13.3.2.1.2.4ScalarairIRRCGroupSetpointsSupplyAirMetricread-writemandatoryGroup supply air setpoint in tenths of degrees Celsius.
1.3.6.1.4.1.318.1.1.13.3.2.1.2.5ScalarairIRRCGroupSetpointsFanSpeedPreferenceread-writemandatoryThe preferred fan speed setting.
1.3.6.1.4.1.318.1.1.13.3.2.1.2.6ScalarairIRRCGroupSetpointsFanSpeedControlread-writemandatoryThe fan speed control setting. Automatic(1) - controller manages fan speed. Manual(2) - fan speed is fixed and set by the fan speed preference. See airIRRCGrou…
1.3.6.1.4.1.318.1.1.13.3.2.1.2.7ScalarairIRRCGroupSetpointsActiveFlowControlBiasread-writemandatoryThe active flow control bias setting.
1.3.6.1.4.1.318.1.1.13.3.2.1.3NodeairIRRCGroupConfig
1.3.6.1.4.1.318.1.1.13.3.2.1.3.1ScalarairIRRCGroupConfigNumberofCoolingUnitsread-writemandatoryThe number of cooling units present in the group.
1.3.6.1.4.1.318.1.1.13.3.2.1.3.2ScalarairIRRCGroupConfigConfigurationTyperead-writemandatoryThe group configuration type.
1.3.6.1.4.1.318.1.1.13.3.2.1.3.3ScalarairIRRCGroupConfigPctGlycolread-writemandatoryThe glycol mixture in percent.
1.3.6.1.4.1.318.1.1.13.3.2.1.3.4ScalarairIRRCGroupConfigCoolGainPread-writemandatoryThe gain component of the PID in hundredths.
1.3.6.1.4.1.318.1.1.13.3.2.1.3.5ScalarairIRRCGroupConfigCoolResetRateIread-writemandatoryThe integral component of the PID in hundredths.
1.3.6.1.4.1.318.1.1.13.3.2.1.3.6ScalarairIRRCGroupConfigCoolDerivativeDread-writemandatoryThe derivative component of the PID in hundredths.
1.3.6.1.4.1.318.1.1.13.3.2.1.3.7ScalarairIRRCGroupConfigMaxFanSpeedread-writemandatoryThe maximum desired fan speed setting in percent.
1.3.6.1.4.1.318.1.1.13.3.2.1.3.8ScalarairIRRCGroupConfigNumberOfActiveFlowControllersread-writemandatoryThe number of active flow controllers present in the group.
1.3.6.1.4.1.318.1.1.13.3.2.1.3.9ScalarairIRRCGroupConfigActiveFlowControllerLampTestread-writemandatoryTurns off/on the active flow controller lamp test.
1.3.6.1.4.1.318.1.1.13.3.2.1.3.10ScalarairIRRCGroupConfigAltitudeUSread-writemandatoryThe group altitude of the units above sea level in feet.
1.3.6.1.4.1.318.1.1.13.3.2.1.3.11ScalarairIRRCGroupConfigAltitudeMetricread-writemandatoryThe group altitude of the units above sea level in meters.
1.3.6.1.4.1.318.1.1.13.3.2.2NodeairIRRCUnit
1.3.6.1.4.1.318.1.1.13.3.2.2.1NodeairIRRCUnitIdent
1.3.6.1.4.1.318.1.1.13.3.2.2.1.1ScalarairIRRCUnitIdentIDread-writemandatoryThe unit identification number.
1.3.6.1.4.1.318.1.1.13.3.2.2.1.2ScalarairIRRCUnitIdentNameread-writemandatoryA character string identifying the unit name.
1.3.6.1.4.1.318.1.1.13.3.2.2.1.3ScalarairIRRCUnitIdentLocationread-writemandatoryA character string identifying the unit location.
1.3.6.1.4.1.318.1.1.13.3.2.2.1.4ScalarairIRRCUnitIdentModelNumberread-onlymandatoryA character string identifying the unit model number.
1.3.6.1.4.1.318.1.1.13.3.2.2.1.5ScalarairIRRCUnitIdentSerialNumberread-onlymandatoryA character string identifying the unit serial number.
1.3.6.1.4.1.318.1.1.13.3.2.2.1.6ScalarairIRRCUnitIdentFirmwareRevisionread-onlymandatoryA character string identifying the unit firmware version.
1.3.6.1.4.1.318.1.1.13.3.2.2.1.7ScalarairIRRCUnitIdentHardwareRevisionread-onlymandatoryA character string identifying the unit controller hardware revision.
1.3.6.1.4.1.318.1.1.13.3.2.2.1.8ScalarairIRRCUnitIdentManufactureDateread-onlymandatoryA character string identifying the unit manufacture date.
1.3.6.1.4.1.318.1.1.13.3.2.2.2NodeairIRRCUnitStatus
1.3.6.1.4.1.318.1.1.13.3.2.2.2.1ScalarairIRRCUnitStatusOperateModeread-onlymandatoryThe cooling unit operating mode.
1.3.6.1.4.1.318.1.1.13.3.2.2.2.2ScalarairIRRCUnitStatusCoolOutputread-onlymandatoryThe unit cooling output in tenths of kW.
1.3.6.1.4.1.318.1.1.13.3.2.2.2.3ScalarairIRRCUnitStatusCoolDemandread-onlymandatoryThe unit cooling demand in tenths of kW.
1.3.6.1.4.1.318.1.1.13.3.2.2.2.4ScalarairIRRCUnitStatusAirFlowUSread-onlymandatoryThe unit air flow in cubic feet per minute.
1.3.6.1.4.1.318.1.1.13.3.2.2.2.5ScalarairIRRCUnitStatusAirFlowMetricread-onlymandatoryThe unit air flow in hundredths of liters per second.
1.3.6.1.4.1.318.1.1.13.3.2.2.2.6ScalarairIRRCUnitStatusRackInletTempUSread-onlymandatoryThe unit rack inlet temperature in tenths of degrees Fahrenheit.
1.3.6.1.4.1.318.1.1.13.3.2.2.2.7ScalarairIRRCUnitStatusRackInletTempMetricread-onlymandatoryThe unit rack inlet temperature in tenths of degrees Celsius.
1.3.6.1.4.1.318.1.1.13.3.2.2.2.8ScalarairIRRCUnitStatusSupplyAirTempUSread-onlymandatoryThe unit supply air temperature in tenths of degrees Fahrenheit.
1.3.6.1.4.1.318.1.1.13.3.2.2.2.9ScalarairIRRCUnitStatusSupplyAirTempMetricread-onlymandatoryThe unit supply air temperature in tenths of degrees Celsius.
1.3.6.1.4.1.318.1.1.13.3.2.2.2.10ScalarairIRRCUnitStatusReturnAirTempUSread-onlymandatoryThe unit return air temperature in tenths of degrees Fahrenheit.
1.3.6.1.4.1.318.1.1.13.3.2.2.2.11ScalarairIRRCUnitStatusReturnAirTempMetricread-onlymandatoryThe unit return air temperature in tenths of degrees Celsius.
1.3.6.1.4.1.318.1.1.13.3.2.2.2.12ScalarairIRRCUnitStatusContainmtDPUSread-onlymandatoryThe unit containment differential pressure in hundredths of inches of water.
1.3.6.1.4.1.318.1.1.13.3.2.2.2.13ScalarairIRRCUnitStatusContainmtDPMetricread-onlymandatoryThe unit containment differential pressure in Pa.
1.3.6.1.4.1.318.1.1.13.3.2.2.2.14ScalarairIRRCUnitStatusFilterDPUSread-onlymandatoryThe unit air filter differential pressure in hundredths of inches of water.
1.3.6.1.4.1.318.1.1.13.3.2.2.2.15ScalarairIRRCUnitStatusFilterDPMetricread-onlymandatoryThe unit air filter differential pressure in Pa.
1.3.6.1.4.1.318.1.1.13.3.2.2.2.16ScalarairIRRCUnitStatusFanSpeedread-onlymandatoryThe unit average fan speed in tenths of percent.
1.3.6.1.4.1.318.1.1.13.3.2.2.2.17ScalarairIRRCUnitStatusInputStateread-onlymandatoryThe state of the input contact.
1.3.6.1.4.1.318.1.1.13.3.2.2.2.18ScalarairIRRCUnitStatusOutputStateread-onlymandatoryThe state of the output relay.
1.3.6.1.4.1.318.1.1.13.3.2.2.2.19ScalarairIRRCUnitStatusActivePowerSourceread-onlymandatoryThe power source that is powering the unit.
1.3.6.1.4.1.318.1.1.13.3.2.2.2.20ScalarairIRRCUnitStatusFluidValvePositionread-onlymandatoryThe fluid valve position in percent open.
1.3.6.1.4.1.318.1.1.13.3.2.2.2.21ScalarairIRRCUnitStatusFluidFlowUSread-onlymandatoryThe fluid flow in tenths of gallons per minute.
1.3.6.1.4.1.318.1.1.13.3.2.2.2.22ScalarairIRRCUnitStatusFluidFlowMetricread-onlymandatoryThe fluid flow in hundredths of liters per second.
1.3.6.1.4.1.318.1.1.13.3.2.2.2.23ScalarairIRRCUnitStatusEnteringFluidTemperatureUSread-onlymandatoryThe temperature of the entering fluid in tenths of degrees Fahrenheit.
1.3.6.1.4.1.318.1.1.13.3.2.2.2.24ScalarairIRRCUnitStatusEnteringFluidTemperatureMetricread-onlymandatoryThe temperature of the entering fluid in tenths of degrees Celsius.
1.3.6.1.4.1.318.1.1.13.3.2.2.2.25ScalarairIRRCUnitStatusLeavingFluidTemperatureUSread-onlymandatoryThe temperature of the Leaving fluid in tenths of degrees Fahrenheit.
1.3.6.1.4.1.318.1.1.13.3.2.2.2.26ScalarairIRRCUnitStatusLeavingFluidTemperatureMetricread-onlymandatoryThe temperature of the Leaving fluid in tenths of degrees Celsius.
1.3.6.1.4.1.318.1.1.13.3.2.2.2.27ScalarairIRRCUnitStatusLeakSensorread-onlymandatoryThe state (no-leak/leak) of the leak sensor.
1.3.6.1.4.1.318.1.1.13.3.2.2.3NodeairIRRCUnitRunHours
1.3.6.1.4.1.318.1.1.13.3.2.2.3.1ScalarairIRRCUnitRunHoursAirFilterread-onlymandatoryUnit air filter run hours.
1.3.6.1.4.1.318.1.1.13.3.2.2.3.2ScalarairIRRCUnitRunHoursFan1read-onlymandatoryUnit fan 1 run hours.
1.3.6.1.4.1.318.1.1.13.3.2.2.3.3ScalarairIRRCUnitRunHoursFan2read-onlymandatoryUnit fan 2 run hours.
1.3.6.1.4.1.318.1.1.13.3.2.2.3.4ScalarairIRRCUnitRunHoursFan3read-onlymandatoryUnit fan 3 run hours.
1.3.6.1.4.1.318.1.1.13.3.2.2.3.5ScalarairIRRCUnitRunHoursFan4read-onlymandatoryUnit fan 4 run hours.
1.3.6.1.4.1.318.1.1.13.3.2.2.3.6ScalarairIRRCUnitRunHoursFan5read-onlymandatoryUnit fan 5 run hours.
1.3.6.1.4.1.318.1.1.13.3.2.2.3.7ScalarairIRRCUnitRunHoursFan6read-onlymandatoryUnit fan 6 run hours.
1.3.6.1.4.1.318.1.1.13.3.2.2.3.8ScalarairIRRCUnitRunHoursFan7read-onlymandatoryUnit fan 7 run hours.
1.3.6.1.4.1.318.1.1.13.3.2.2.3.9ScalarairIRRCUnitRunHoursFan8read-onlymandatoryUnit fan 8 run hours.
1.3.6.1.4.1.318.1.1.13.3.2.2.3.10ScalarairIRRCUnitRunHoursFanPowerSupplyLeftread-onlymandatoryUnit fan left power supply run hours.
1.3.6.1.4.1.318.1.1.13.3.2.2.3.11ScalarairIRRCUnitRunHoursFanPowerSupplyRightread-onlymandatoryUnit fan right power supply run hours.
1.3.6.1.4.1.318.1.1.13.3.2.2.3.12ScalarairIRRCUnitRunHoursCondensatePumpread-onlymandatoryUnit condensate pump run hours.
1.3.6.1.4.1.318.1.1.13.3.2.2.3.13ScalarairIRRCUnitRunHoursFanPowerSupplyFeedALeftread-onlymandatoryUnit fan, DC power feed A, left power supply run hours. This is only valid for a DC input unit.
1.3.6.1.4.1.318.1.1.13.3.2.2.3.14ScalarairIRRCUnitRunHoursFanPowerSupplyFeedARightread-onlymandatoryUnit fan, DC power feed A, right power supply run hours. This is only valid for a DC input unit.
1.3.6.1.4.1.318.1.1.13.3.2.2.3.15ScalarairIRRCUnitRunHoursFanPowerSupplyFeedBLeftread-onlymandatoryUnit fan, DC power feed B, left power supply run hours. This is only valid for a DC input unit.
1.3.6.1.4.1.318.1.1.13.3.2.2.3.16ScalarairIRRCUnitRunHoursFanPowerSupplyFeedBRightread-onlymandatoryUnit fan, DC power feed B, right power supply run hours. This is only valid for a DC input unit.
1.3.6.1.4.1.318.1.1.13.3.2.2.4NodeairIRRCUnitServiceIntervals
1.3.6.1.4.1.318.1.1.13.3.2.2.4.1ScalarairIRRCUnitServiceIntervalsAirFilterread-writemandatoryAir filter service interval in weeks.
1.3.6.1.4.1.318.1.1.13.3.2.2.4.2ScalarairIRRCUnitServiceIntervalsAirFilterAlarmread-writemandatoryThe air filter service interval alarm enable/disable.
1.3.6.1.4.1.318.1.1.13.3.2.2.5NodeairIRRCUnitThresholds
1.3.6.1.4.1.318.1.1.13.3.2.2.5.1ScalarairIRRCUnitThresholdsRackInletHighTempUSread-writemandatoryUnit rack inlet air high temperature threshold in tenths of degrees Fahrenheit.
1.3.6.1.4.1.318.1.1.13.3.2.2.5.2ScalarairIRRCUnitThresholdsRackInletHighTempMetricread-writemandatoryUnit rack inlet air high temperature threshold in tenths of degrees Celsius.
1.3.6.1.4.1.318.1.1.13.3.2.2.5.3ScalarairIRRCUnitThresholdsSupplyAirHighTempUSread-writemandatoryUnit supply air high temperature threshold in tenths of degrees Fahrenheit.
1.3.6.1.4.1.318.1.1.13.3.2.2.5.4ScalarairIRRCUnitThresholdsSupplyAirHighTempMetricread-writemandatoryUnit supply air high temperature threshold in tenths of degrees Celsius.
1.3.6.1.4.1.318.1.1.13.3.2.2.5.5ScalarairIRRCUnitThresholdsReturnAirHighTempUSread-writemandatoryUnit return air high temperature threshold in tenths of degrees Fahrenheit.
1.3.6.1.4.1.318.1.1.13.3.2.2.5.6ScalarairIRRCUnitThresholdsReturnAirHighTempMetricread-writemandatoryUnit return air high temperature threshold in tenths of degrees Celsius.
1.3.6.1.4.1.318.1.1.13.3.2.2.5.7ScalarairIRRCUnitThresholdsEnteringFluidHighTempUSread-writemandatoryUnit entering fluid high temperature threshold in tenths of degrees Fahrenheit.
1.3.6.1.4.1.318.1.1.13.3.2.2.5.8ScalarairIRRCUnitThresholdsEnteringFluidHighTempMetricread-writemandatoryUnit incoming fluid high temperature threshold in tenths of degrees Celsius.
1.3.6.1.4.1.318.1.1.13.3.2.2.6NodeairIRRCUnitConfig
1.3.6.1.4.1.318.1.1.13.3.2.2.6.1ScalarairIRRCUnitConfigCoolCapacityread-writemandatoryThe cooling capacity options setting.
1.3.6.1.4.1.318.1.1.13.3.2.2.6.2ScalarairIRRCUnitConfigStartupDelayread-writemandatoryThe startup delay in seconds.
1.3.6.1.4.1.318.1.1.13.3.2.2.6.3ScalarairIRRCUnitConfigIdleOnLeakDetectread-writemandatoryThe idle on leak options setting.
1.3.6.1.4.1.318.1.1.13.3.2.2.6.4ScalarairIRRCUnitConfigPowerSourceread-writemandatoryThe configured power source of the unit.
1.3.6.1.4.1.318.1.1.13.3.2.2.6.5ScalarairIRRCUnitConfigInputNormalStateread-writemandatoryThe normal state of the input contact.
1.3.6.1.4.1.318.1.1.13.3.2.2.6.6ScalarairIRRCUnitConfigOutputNormalStateread-writemandatoryThe normal state of the output relay.
1.3.6.1.4.1.318.1.1.13.3.2.2.6.7ScalarairIRRCUnitConfigOutputSourceread-writemandatoryThe source of output relay change.
1.3.6.1.4.1.318.1.1.13.3.2.2.6.8ScalarairIRRCUnitConfigIdleOnCoolFailread-writemandatoryThe idle on cool fail options setting. If yes, the system will go into idle mode when a cooling failure is detected. If no, the system will not go into idle mo…
1.3.6.1.4.1.318.1.1.13.3.3NodeairIRRP
1.3.6.1.4.1.318.1.1.13.3.3.1NodeairIRRP100
1.3.6.1.4.1.318.1.1.13.3.3.1.1NodeairIRRP100Group
1.3.6.1.4.1.318.1.1.13.3.3.1.1.1NodeairIRRP100GroupStatus
1.3.6.1.4.1.318.1.1.13.3.3.1.1.1.1ScalarairIRRP100GroupStatusAirFlowUSread-onlymandatoryGroup air flow in cubic feet per minute.
1.3.6.1.4.1.318.1.1.13.3.3.1.1.1.2ScalarairIRRP100GroupStatusAirFlowMetricread-onlymandatoryGroup air flow in liters per second.
1.3.6.1.4.1.318.1.1.13.3.3.1.1.1.3ScalarairIRRP100GroupStatusMaxRackInletTempUSread-onlymandatoryGroup maximum rack inlet temperature in tenths of degrees Fahrenheit.
1.3.6.1.4.1.318.1.1.13.3.3.1.1.1.4ScalarairIRRP100GroupStatusMaxRackInletTempMetricread-onlymandatoryGroup maximum rack inlet temperature in tenths of degrees Celsius.
1.3.6.1.4.1.318.1.1.13.3.3.1.1.1.5ScalarairIRRP100GroupStatusMinRackInletTempUSread-onlymandatoryGroup minimum rack inlet temperature in tenths of degrees Fahrenheit.
1.3.6.1.4.1.318.1.1.13.3.3.1.1.1.6ScalarairIRRP100GroupStatusMinRackInletTempMetricread-onlymandatoryGroup minimum rack inlet temperature in tenths of degrees Celsius.
1.3.6.1.4.1.318.1.1.13.3.3.1.1.1.7ScalarairIRRP100GroupStatusCoolDemandread-onlymandatoryGroup coolant demand in tenths of kiloWatts.
1.3.6.1.4.1.318.1.1.13.3.3.1.1.1.8ScalarairIRRP100GroupStatusCoolOutputread-onlymandatoryGroup coolant output in tenths of kiloWatts.
1.3.6.1.4.1.318.1.1.13.3.3.1.1.1.9ScalarairIRRP100GroupStatusHumidifyDemandread-onlymandatoryThe amount of humidification the group is demanding from the humidifiers in percent.
1.3.6.1.4.1.318.1.1.13.3.3.1.1.1.10ScalarairIRRP100GroupStatusHumidifyOutputread-onlymandatoryThe actual amount of humidification the group is supplying in percent.
1.3.6.1.4.1.318.1.1.13.3.3.1.1.1.11ScalarairIRRP100GroupStatusDehumidifyDemandread-onlymandatoryThe amount of dehumidification the group is demanding from the electric heaters in percent.
1.3.6.1.4.1.318.1.1.13.3.3.1.1.1.12ScalarairIRRP100GroupStatusDehumidifyOutputread-onlymandatoryThe actual amount of dehumidification the group is supplying in percent.
1.3.6.1.4.1.318.1.1.13.3.3.1.1.1.13ScalarairIRRP100GroupStatusReheatDemandread-onlymandatoryThe amount of heating the group is demanding from the electric heaters in percent.
1.3.6.1.4.1.318.1.1.13.3.3.1.1.1.14ScalarairIRRP100GroupStatusReheatOutputread-onlymandatoryThe actual amount of heating the group is supplying in percent.
1.3.6.1.4.1.318.1.1.13.3.3.1.1.1.15ScalarairIRRP100GroupStatusActiveFlowControlStatusread-onlymandatoryStatus of the active flow control system.
1.3.6.1.4.1.318.1.1.13.3.3.1.1.1.16ScalarairIRRP100GroupStatusDewPointTempUSread-onlymandatoryGroup average dew point temperature in tenths of degrees Fahrenheit.
1.3.6.1.4.1.318.1.1.13.3.3.1.1.1.17ScalarairIRRP100GroupStatusDewPointTempMetricread-onlymandatoryGroup average dew point temperature in tenths of degrees Celsius.
1.3.6.1.4.1.318.1.1.13.3.3.1.1.2NodeairIRRP100GroupSetpoints
1.3.6.1.4.1.318.1.1.13.3.3.1.1.2.1ScalarairIRRP100GroupSetpointsCoolUSread-writemandatoryGroup cooling setpoint in tenths of degrees Fahrenheit.
1.3.6.1.4.1.318.1.1.13.3.3.1.1.2.2ScalarairIRRP100GroupSetpointsCoolMetricread-writemandatoryGroup cooling setpoint in tenths of degrees Celsius.
1.3.6.1.4.1.318.1.1.13.3.3.1.1.2.3ScalarairIRRP100GroupSetpointsSupplyAirUSread-writemandatoryGroup supply air setpoint in tenths of degrees Fahrenheit.
1.3.6.1.4.1.318.1.1.13.3.3.1.1.2.4ScalarairIRRP100GroupSetpointsSupplyAirMetricread-writemandatoryGroup supply air setpoint in tenths of degrees Celsius.
1.3.6.1.4.1.318.1.1.13.3.3.1.1.2.5ScalarairIRRP100GroupSetpointsHumidifyread-writemandatoryGroup humidify setpoint in tenths of percent relative humidity.
1.3.6.1.4.1.318.1.1.13.3.3.1.1.2.6ScalarairIRRP100GroupSetpointsDehumidifyread-writemandatoryGroup dehumidify setpoint in tenths of percent relative humidity.
1.3.6.1.4.1.318.1.1.13.3.3.1.1.2.7ScalarairIRRP100GroupSetpointsDehumidifyDeadbandread-writemandatoryGroup dehumidify deadband in percent relative humidity.
1.3.6.1.4.1.318.1.1.13.3.3.1.1.2.8ScalarairIRRP100GroupSetpointsReheatUSread-writemandatoryGroup supply air setpoint in tenths of degrees Fahrenheit.
1.3.6.1.4.1.318.1.1.13.3.3.1.1.2.9ScalarairIRRP100GroupSetpointsReheatMetricread-writemandatoryGroup supply air setpoint in tenths of degrees Celsius.
1.3.6.1.4.1.318.1.1.13.3.3.1.1.2.10ScalarairIRRP100GroupSetpointsFanSpeedPreferenceread-writemandatoryThe preferred fan speed setting.
1.3.6.1.4.1.318.1.1.13.3.3.1.1.2.11ScalarairIRRP100GroupSetpointsFanSpeedControlread-writemandatoryThe fan speed control setting.
1.3.6.1.4.1.318.1.1.13.3.3.1.1.2.12ScalarairIRRP100GroupSetpointsActiveFlowControlBiasread-writemandatoryThe active flow control bias setting.
1.3.6.1.4.1.318.1.1.13.3.3.1.1.3NodeairIRRP100GroupConfig
1.3.6.1.4.1.318.1.1.13.3.3.1.1.3.1ScalarairIRRP100GroupConfigNumberofCoolingUnitsread-writemandatoryThe number of cooling units present in the group.
1.3.6.1.4.1.318.1.1.13.3.3.1.1.3.2ScalarairIRRP100GroupConfigConfigurationTyperead-writemandatoryThe group configuration type.
1.3.6.1.4.1.318.1.1.13.3.3.1.1.3.3ScalarairIRRP100GroupConfigCoolGainPread-writemandatoryThe gain component of the cool PID in hundredths.
1.3.6.1.4.1.318.1.1.13.3.3.1.1.3.4ScalarairIRRP100GroupConfigCoolResetRateIread-writemandatoryThe integral component of the cool PID in hundredths.
1.3.6.1.4.1.318.1.1.13.3.3.1.1.3.5ScalarairIRRP100GroupConfigCoolDerivativeDread-writemandatoryThe derivative component of the cool PID in hundredths.
1.3.6.1.4.1.318.1.1.13.3.3.1.1.3.6ScalarairIRRP100GroupConfigHumidifySensitivityBandread-writemandatoryThe percent relative humidity below the setpoint that will cause the humidifier to run at 100% capacity.
1.3.6.1.4.1.318.1.1.13.3.3.1.1.3.7ScalarairIRRP100GroupConfigReheatGainPread-writemandatoryThe gain component of the reheat PID in hundredths.
1.3.6.1.4.1.318.1.1.13.3.3.1.1.3.8ScalarairIRRP100GroupConfigReheatResetRateIread-writemandatoryThe integral component of the reheat PID in hundredths.
1.3.6.1.4.1.318.1.1.13.3.3.1.1.3.9ScalarairIRRP100GroupConfigReheatDerivativeDread-writemandatoryThe derivative component of the reheat PID in hundredths.
1.3.6.1.4.1.318.1.1.13.3.3.1.1.3.10ScalarairIRRP100GroupConfigNumberofBackupUnitsread-writemandatoryThe number of backup units.
1.3.6.1.4.1.318.1.1.13.3.3.1.1.3.11ScalarairIRRP100GroupConfigRuntimeBalancingEnableread-writemandatoryEnable or disable runtime balancing feature.
1.3.6.1.4.1.318.1.1.13.3.3.1.1.3.12ScalarairIRRP100GroupConfigLoadAssistEnableread-writemandatoryEnable or disable load assist feature.
1.3.6.1.4.1.318.1.1.13.3.3.1.1.3.13ScalarairIRRP100GroupConfigFullRPBackupsread-writemandatoryThe number of full featured RPs that can be used as backup units.
1.3.6.1.4.1.318.1.1.13.3.3.1.1.3.14ScalarairIRRP100GroupConfigMaxFanSpeedread-writemandatoryThe maximum desired fan speed setting in percent.
1.3.6.1.4.1.318.1.1.13.3.3.1.1.3.15ScalarairIRRP100GroupConfigNumberOfActiveFlowControllersread-writemandatoryThe number of active flow controllers present in the group.
1.3.6.1.4.1.318.1.1.13.3.3.1.1.3.16ScalarairIRRP100GroupConfigActiveFlowControllerLampTestread-writemandatoryTurns off/on the active flow controller lamp test.
1.3.6.1.4.1.318.1.1.13.3.3.1.1.3.17ScalarairIRRP100GroupConfigAltitudeUSread-writemandatoryThe group altitude of the units above sea level in feet.
1.3.6.1.4.1.318.1.1.13.3.3.1.1.3.18ScalarairIRRP100GroupConfigAltitudeMetricread-writemandatoryThe group altitude of the units above sea level in meters.
1.3.6.1.4.1.318.1.1.13.3.3.1.2NodeairIRRP100Unit
1.3.6.1.4.1.318.1.1.13.3.3.1.2.1NodeairIRRP100UnitIdent
1.3.6.1.4.1.318.1.1.13.3.3.1.2.1.1ScalarairIRRP100UnitIdentIDread-writemandatoryThe unit identification number.
1.3.6.1.4.1.318.1.1.13.3.3.1.2.1.2ScalarairIRRP100UnitIdentNameread-writemandatoryA character string identifying the unit name.
1.3.6.1.4.1.318.1.1.13.3.3.1.2.1.3ScalarairIRRP100UnitIdentLocationread-writemandatoryA character string identifying the unit location.
1.3.6.1.4.1.318.1.1.13.3.3.1.2.1.4ScalarairIRRP100UnitIdentModelNumberread-onlymandatoryA character string identifying the unit model number.
1.3.6.1.4.1.318.1.1.13.3.3.1.2.1.5ScalarairIRRP100UnitIdentSerialNumberread-onlymandatoryA character string identifying the unit serial number.
1.3.6.1.4.1.318.1.1.13.3.3.1.2.1.6ScalarairIRRP100UnitIdentFirmwareRevisionread-onlymandatoryA character string identifying the unit firmware version.
1.3.6.1.4.1.318.1.1.13.3.3.1.2.1.7ScalarairIRRP100UnitIdentHardwareRevisionread-onlymandatoryA character string identifying the unit controller hardware revision.
1.3.6.1.4.1.318.1.1.13.3.3.1.2.1.8ScalarairIRRP100UnitIdentManufactureDateread-onlymandatoryA character string identifying the unit manufacture date.
1.3.6.1.4.1.318.1.1.13.3.3.1.2.2NodeairIRRP100UnitStatus
1.3.6.1.4.1.318.1.1.13.3.3.1.2.2.1ScalarairIRRP100UnitStatusOperateModeread-onlymandatoryThe cooling unit operating mode.
1.3.6.1.4.1.318.1.1.13.3.3.1.2.2.2ScalarairIRRP100UnitStatusRackInletTempUSread-onlymandatoryThe unit rack inlet temperature in tenths of degrees Fahrenheit.
1.3.6.1.4.1.318.1.1.13.3.3.1.2.2.3ScalarairIRRP100UnitStatusRackInletTempMetricread-onlymandatoryThe unit rack inlet temperature in tenths of degrees Celsius.
1.3.6.1.4.1.318.1.1.13.3.3.1.2.2.4ScalarairIRRP100UnitStatusSupplyAirTempUSread-onlymandatoryThe unit supply air temperature in tenths of degrees Fahrenheit.
1.3.6.1.4.1.318.1.1.13.3.3.1.2.2.5ScalarairIRRP100UnitStatusSupplyAirTempMetricread-onlymandatoryThe unit supply air temperature in tenths of degrees Celsius.
1.3.6.1.4.1.318.1.1.13.3.3.1.2.2.6ScalarairIRRP100UnitStatusReturnAirTempUSread-onlymandatoryThe unit return air temperature in tenths of degrees Fahrenheit.
1.3.6.1.4.1.318.1.1.13.3.3.1.2.2.7ScalarairIRRP100UnitStatusReturnAirTempMetricread-onlymandatoryThe unit return air temperature in tenths of degrees Celsius.
1.3.6.1.4.1.318.1.1.13.3.3.1.2.2.8ScalarairIRRP100UnitStatusSupplyHumidityread-onlymandatoryThe relative humidity of the supply air in tenths of percent.
1.3.6.1.4.1.318.1.1.13.3.3.1.2.2.9ScalarairIRRP100UnitStatusReturnHumidityread-onlymandatoryThe relative humidity of the return air in tenths of percent.
1.3.6.1.4.1.318.1.1.13.3.3.1.2.2.10ScalarairIRRP100UnitStatusAirFlowUSread-onlymandatoryThe unit air flow in cubic feet per minute.
1.3.6.1.4.1.318.1.1.13.3.3.1.2.2.11ScalarairIRRP100UnitStatusAirFlowMetricread-onlymandatoryThe unit air flow in hundredths of liters per second.
1.3.6.1.4.1.318.1.1.13.3.3.1.2.2.12ScalarairIRRP100UnitStatusFanSpeedread-onlymandatoryThe unit average fan speed in tenths of percent.
1.3.6.1.4.1.318.1.1.13.3.3.1.2.2.13ScalarairIRRP100UnitStatusCoolDemandread-onlymandatoryThe unit cooling demand in tenths of kiloWatts.
1.3.6.1.4.1.318.1.1.13.3.3.1.2.2.14ScalarairIRRP100UnitStatusCoolOutputread-onlymandatoryThe unit cooling output in tenths of kiloWatts.
1.3.6.1.4.1.318.1.1.13.3.3.1.2.2.15ScalarairIRRP100UnitStatusHumidifyDemandread-onlymandatoryThe amount of humidification the unit is demanding from the humidifier in percent.
1.3.6.1.4.1.318.1.1.13.3.3.1.2.2.16ScalarairIRRP100UnitStatusHumidifyOutputread-onlymandatoryThe actual humidification output of the unit in percent.
1.3.6.1.4.1.318.1.1.13.3.3.1.2.2.17ScalarairIRRP100UnitStatusDehumidifyDemandread-onlymandatoryThe amount of dehumidification the unit is demanding in percent.
1.3.6.1.4.1.318.1.1.13.3.3.1.2.2.18ScalarairIRRP100UnitStatusDehumidifyOutputread-onlymandatoryThe actual dehumidification output of the unit in percent.
1.3.6.1.4.1.318.1.1.13.3.3.1.2.2.19ScalarairIRRP100UnitStatusReheatDemandread-onlymandatoryThe amount of heating the unit is demanding from the electric heater in percent.
1.3.6.1.4.1.318.1.1.13.3.3.1.2.2.20ScalarairIRRP100UnitStatusReheatOutputread-onlymandatoryThe actual heating output of the unit in percent.
1.3.6.1.4.1.318.1.1.13.3.3.1.2.2.21ScalarairIRRP100UnitStatusInputStateread-onlymandatoryThe state of the input contact.
1.3.6.1.4.1.318.1.1.13.3.3.1.2.2.22ScalarairIRRP100UnitStatusOutputStateread-onlymandatoryThe state of the output relay.
1.3.6.1.4.1.318.1.1.13.3.3.1.2.2.23ScalarairIRRP100UnitStatusRackInletTemperature1USread-onlymandatoryThe unit rack inlet temperature sensor in tenths of degrees Fahrenheit.
1.3.6.1.4.1.318.1.1.13.3.3.1.2.2.24ScalarairIRRP100UnitStatusRackInletTemperature1Metricread-onlymandatoryThe unit rack inlet temperature sensor in tenths of degrees Celsius.
1.3.6.1.4.1.318.1.1.13.3.3.1.2.2.25ScalarairIRRP100UnitStatusRackInletTemperature2USread-onlymandatoryThe unit rack inlet temperature sensor in tenths of degrees Fahrenheit.
1.3.6.1.4.1.318.1.1.13.3.3.1.2.2.26ScalarairIRRP100UnitStatusRackInletTemperature2Metricread-onlymandatoryThe unit rack inlet temperature sensor in tenths of degrees Celsius.
1.3.6.1.4.1.318.1.1.13.3.3.1.2.2.27ScalarairIRRP100UnitStatusRackInletTemperature3USread-onlymandatoryThe unit rack inlet temperature sensor in tenths of degrees Fahrenheit.
1.3.6.1.4.1.318.1.1.13.3.3.1.2.2.28ScalarairIRRP100UnitStatusRackInletTemperature3Metricread-onlymandatoryThe unit rack inlet temperature sensor in tenths of degrees Celsius.
1.3.6.1.4.1.318.1.1.13.3.3.1.2.2.29ScalarairIRRP100UnitStatusFilterDPUSread-onlymandatoryThe unit air filter differential pressure in hundredths of inches of water.
1.3.6.1.4.1.318.1.1.13.3.3.1.2.2.30ScalarairIRRP100UnitStatusFilterDPMetricread-onlymandatoryThe unit air filter differential pressure in Pa.
1.3.6.1.4.1.318.1.1.13.3.3.1.2.2.31ScalarairIRRP100UnitStatusContainmtDPUSread-onlymandatoryThe unit containment differential pressure in hundredths of inches of water.
1.3.6.1.4.1.318.1.1.13.3.3.1.2.2.32ScalarairIRRP100UnitStatusContainmtDPMetricread-onlymandatoryThe unit containment differential pressure in Pa.
1.3.6.1.4.1.318.1.1.13.3.3.1.2.2.33ScalarairIRRP100UnitStatusHumidifierCurrentread-onlymandatoryThe humidifier current of the unit in tenths of amperes.
1.3.6.1.4.1.318.1.1.13.3.3.1.2.2.34ScalarairIRRP100UnitStatusHumidifierWaterConductivityread-onlymandatoryThe water conductivity in the humidifier of the unit in microSiemens/cm.
1.3.6.1.4.1.318.1.1.13.3.3.1.2.2.35ScalarairIRRP100UnitStatusCompressorDriveSpeedread-onlymandatoryThe compressor drive speed in hundredths of Hertz.
1.3.6.1.4.1.318.1.1.13.3.3.1.2.2.36ScalarairIRRP100UnitStatusCompressorDrivePowerread-onlymandatoryThe compressor drive power consumption in tenths of kiloWatts.
1.3.6.1.4.1.318.1.1.13.3.3.1.2.2.37ScalarairIRRP100UnitStatusCompressorDriveVoltageread-onlymandatoryThe compressor drive voltage consumption in tenths of volts.
1.3.6.1.4.1.318.1.1.13.3.3.1.2.2.38ScalarairIRRP100UnitStatusCompressorDriveCurrentread-onlymandatoryThe compressor drive voltage consumption in tenths of amperes.
1.3.6.1.4.1.318.1.1.13.3.3.1.2.2.39ScalarairIRRP100UnitStatusCompressorDriveDCLinkVoltageread-onlymandatoryThe compressor drive DC link voltage in tenths of volts.
1.3.6.1.4.1.318.1.1.13.3.3.1.2.2.40ScalarairIRRP100UnitStatusCompressorDriveHeatSinkTempUSread-onlymandatoryThe temperature of the compressor drive heatsink in tenths of degrees Fahrenheit.
1.3.6.1.4.1.318.1.1.13.3.3.1.2.2.41ScalarairIRRP100UnitStatusCompressorDriveHeatSinkTempMetricread-onlymandatoryThe temperature of the compressor drive heatsink in tenths of degrees Celsius.
1.3.6.1.4.1.318.1.1.13.3.3.1.2.2.42ScalarairIRRP100UnitStatusCompressorDriveControlCardTempUSread-onlymandatoryThe temperature of the compressor drive control card in tenths of degrees Fahrenheit.
1.3.6.1.4.1.318.1.1.13.3.3.1.2.2.43ScalarairIRRP100UnitStatusCompressorDriveControlCardTempMetricread-onlymandatoryThe temperature of the compressor drive control card in tenths of degrees Celsius.
1.3.6.1.4.1.318.1.1.13.3.3.1.2.2.44ScalarairIRRP100UnitStatusCompressorDriveWarningStatusread-onlymandatoryThe four byte warning status of the compressor drive in hexadecimal.
1.3.6.1.4.1.318.1.1.13.3.3.1.2.2.45ScalarairIRRP100UnitStatusCompressorDriveAlarmStatusread-onlymandatoryThe four byte alarm status of the compressor drive in hexadecimal.
1.3.6.1.4.1.318.1.1.13.3.3.1.2.2.46ScalarairIRRP100UnitStatusSuctionPressureUSread-onlymandatoryUnit suction pressure in pounds per square inch (PSI).
1.3.6.1.4.1.318.1.1.13.3.3.1.2.2.47ScalarairIRRP100UnitStatusSuctionPressureMetricread-onlymandatoryUnit suction pressure in kiloPascals (kPa).
1.3.6.1.4.1.318.1.1.13.3.3.1.2.2.48ScalarairIRRP100UnitStatusDischargePressureUSread-onlymandatoryUnit discharge pressure in pounds per square inch (PSI).
1.3.6.1.4.1.318.1.1.13.3.3.1.2.2.49ScalarairIRRP100UnitStatusDischargePressureMetricread-onlymandatoryUnit discharge pressure in kiloPascals (kPa).
1.3.6.1.4.1.318.1.1.13.3.3.1.2.2.50ScalarairIRRP100UnitStatusLeakSensorread-onlymandatoryThe state (no-leak/leak) of the leak sensor.
1.3.6.1.4.1.318.1.1.13.3.3.1.2.3NodeairIRRP100UnitRunHours
1.3.6.1.4.1.318.1.1.13.3.3.1.2.3.1ScalarairIRRP100UnitRunHoursAirFilterread-onlymandatoryUnit air filter run hours.
1.3.6.1.4.1.318.1.1.13.3.3.1.2.3.2ScalarairIRRP100UnitRunHoursCondensatePumpread-onlymandatoryUnit condensate pump run hours.
1.3.6.1.4.1.318.1.1.13.3.3.1.2.3.3ScalarairIRRP100UnitRunHoursHumidifierread-onlymandatoryUnit fan right power supply run hours.
1.3.6.1.4.1.318.1.1.13.3.3.1.2.3.4ScalarairIRRP100UnitRunHoursFan1read-onlymandatoryUnit fan 1 run hours.
1.3.6.1.4.1.318.1.1.13.3.3.1.2.3.5ScalarairIRRP100UnitRunHoursHeater1read-onlymandatoryUnit heater 1 run hours.
1.3.6.1.4.1.318.1.1.13.3.3.1.2.3.6ScalarairIRRP100UnitRunHoursFan2read-onlymandatoryUnit fan 2 run hours.
1.3.6.1.4.1.318.1.1.13.3.3.1.2.3.7ScalarairIRRP100UnitRunHoursHeater2read-onlymandatoryUnit Heater 2 run hours.
1.3.6.1.4.1.318.1.1.13.3.3.1.2.3.8ScalarairIRRP100UnitRunHoursCompressorread-onlymandatoryUnit compressor run hours.
1.3.6.1.4.1.318.1.1.13.3.3.1.2.3.9ScalarairIRRP100UnitRunHoursSystemread-onlymandatoryTotal system run hours.
1.3.6.1.4.1.318.1.1.13.3.3.1.2.4NodeairIRRP100UnitServiceIntervals
1.3.6.1.4.1.318.1.1.13.3.3.1.2.4.1ScalarairIRRP100UnitServiceIntervalAirFilterread-writemandatoryAir filter service interval in weeks.
1.3.6.1.4.1.318.1.1.13.3.3.1.2.4.2ScalarairIRRP100UnitServiceIntervalAirFilterAlarmread-writemandatoryThe air filter service interval alarm enable/disable.
1.3.6.1.4.1.318.1.1.13.3.3.1.2.4.3ScalarairIRRP100UnitServiceIntervalHumidifierread-writemandatoryHumidifier service interval in weeks.
1.3.6.1.4.1.318.1.1.13.3.3.1.2.4.4ScalarairIRRP100UnitServiceIntervalHumidifierAlarmread-writemandatoryThe humidifier service interval alarm enable/disable.
1.3.6.1.4.1.318.1.1.13.3.3.1.2.4.5ScalarairIRRP100UnitServiceIntervalHeaterread-writemandatoryHeater service interval in weeks.
1.3.6.1.4.1.318.1.1.13.3.3.1.2.4.6ScalarairIRRP100UnitServiceIntervalHeaterAlarmread-writemandatoryThe heater service interval alarm enable/disable.
1.3.6.1.4.1.318.1.1.13.3.3.1.2.4.7ScalarairIRRP100UnitServiceIntervalCompressorread-writemandatoryCompressor service interval in weeks.
1.3.6.1.4.1.318.1.1.13.3.3.1.2.4.8ScalarairIRRP100UnitServiceIntervalCompressorAlarmread-writemandatoryThe compressor service interval alarm enable/disable.
1.3.6.1.4.1.318.1.1.13.3.3.1.2.4.9ScalarairIRRP100UnitServiceIntervalCondensatePumpread-writemandatoryCondensate pump service interval in weeks.
1.3.6.1.4.1.318.1.1.13.3.3.1.2.4.10ScalarairIRRP100UnitServiceIntervalCondensatePumpAlarmread-writemandatoryThe condensate pump service interval alarm enable/disable.
1.3.6.1.4.1.318.1.1.13.3.3.1.2.4.11ScalarairIRRP100UnitServiceIntervalFansread-writemandatoryFans service interval in weeks.
1.3.6.1.4.1.318.1.1.13.3.3.1.2.4.12ScalarairIRRP100UnitServiceIntervalFansAlarmread-writemandatoryThe fans service interval alarm enable/disable.
1.3.6.1.4.1.318.1.1.13.3.3.1.2.5NodeairIRRP100UnitThresholds
1.3.6.1.4.1.318.1.1.13.3.3.1.2.5.1ScalarairIRRP100UnitThresholdsRackInletHighTempUSread-writemandatoryUnit rack inlet air high temperature threshold in tenths of degrees Fahrenheit.
1.3.6.1.4.1.318.1.1.13.3.3.1.2.5.2ScalarairIRRP100UnitThresholdsRackInletHighTempMetricread-writemandatoryUnit rack inlet air high temperature threshold in tenths of degrees Celsius.
1.3.6.1.4.1.318.1.1.13.3.3.1.2.5.3ScalarairIRRP100UnitThresholdsSupplyAirHighTempUSread-writemandatoryUnit supply air high temperature threshold in tenths of degrees Fahrenheit.
1.3.6.1.4.1.318.1.1.13.3.3.1.2.5.4ScalarairIRRP100UnitThresholdsSupplyAirHighTempMetricread-writemandatoryUnit supply air high temperature threshold in tenths of degrees Celsius.
1.3.6.1.4.1.318.1.1.13.3.3.1.2.5.5ScalarairIRRP100UnitThresholdsReturnAirHighTempUSread-writemandatoryUnit return air high temperature threshold in tenths of degrees Fahrenheit.
1.3.6.1.4.1.318.1.1.13.3.3.1.2.5.6ScalarairIRRP100UnitThresholdsReturnAirHighTempMetricread-writemandatoryUnit return air high temperature threshold in tenths of degrees Celsius.
1.3.6.1.4.1.318.1.1.13.3.3.1.2.5.7ScalarairIRRP100UnitThresholdsSupplyHumidityHighread-writemandatoryUnit supply humidity high threshold in tenths of percent relative humidity.
1.3.6.1.4.1.318.1.1.13.3.3.1.2.5.8ScalarairIRRP100UnitThresholdsSupplyHumidityLowread-writemandatoryUnit supply humidity low threshold in tenths of percent relative humidity.
1.3.6.1.4.1.318.1.1.13.3.3.1.2.6NodeairIRRP100UnitConfig
1.3.6.1.4.1.318.1.1.13.3.3.1.2.6.1ScalarairIRRP100UnitConfigStartupDelayread-writemandatoryThe startup delay in seconds.
1.3.6.1.4.1.318.1.1.13.3.3.1.2.6.2ScalarairIRRP100UnitConfigCoolCapacityread-writemandatoryThe cooling capacity options setting.
1.3.6.1.4.1.318.1.1.13.3.3.1.2.6.3ScalarairIRRP100UnitConfigIdleOnLeakDetectread-writemandatoryThe idle on leak options setting.
1.3.6.1.4.1.318.1.1.13.3.3.1.2.6.4ScalarairIRRP100UnitConfigInputNormalStateread-writemandatoryThe normal state of the input contact.
1.3.6.1.4.1.318.1.1.13.3.3.1.2.6.5ScalarairIRRP100UnitConfigOutputNormalStateread-writemandatoryThe normal state of the output relay.
1.3.6.1.4.1.318.1.1.13.3.3.1.2.6.6ScalarairIRRP100UnitConfigOutputSourceread-writemandatoryThe source of output relay change.
1.3.6.1.4.1.318.1.1.13.3.3.1.2.6.7ScalarairIRRP100UnitConfigHumidifyEnableread-writemandatoryEnable/disable humidification.
1.3.6.1.4.1.318.1.1.13.3.3.1.2.6.8ScalarairIRRP100UnitConfigHumidifierControlread-writemandatoryThe humidifier drain control.
1.3.6.1.4.1.318.1.1.13.3.3.1.2.6.9ScalarairIRRP100UnitConfigDehumidifyEnableread-writemandatoryEnable/disable dehumidification.
1.3.6.1.4.1.318.1.1.13.3.3.1.2.6.10ScalarairIRRP100UnitConfigReheatEnableread-writemandatoryEnable/disable reheat.
1.3.6.1.4.1.318.1.1.13.3.3.1.2.6.11ScalarairIRRP100UnitConfigHeatAssistEnableread-writemandatoryEnable/disable heat assist.
1.3.6.1.4.1.318.1.1.13.3.3.1.2.6.12ScalarairIRRP100UnitConfigPowerSourceConfigread-writemandatoryConfigure the input power source: (1) single feed or (2) dual feed.
1.3.6.1.4.1.318.1.1.13.3.3.1.2.6.13ScalarairIRRP100UnitConfigUnitRoleOverrideread-writemandatoryWhen this OID value is (1) automatic, the system determines which units are used as primary units and which units are used as backups. When this OID value is (…
1.3.6.1.4.1.318.1.1.13.3.3.1.2.6.14ScalarairIRRP100UnitConfigSecondaryPowerFeedCapabilityread-writemandatoryAvailable on chilled water units. When the power source config setting is set to dual, setting this value to reduced (2) will inhibit the heater and humdifier …
1.3.6.1.4.1.318.1.1.13.3.3.1.2.6.15ScalarairIRRP100UnitConfigIdleOnCoolFailread-writemandatoryWhen this OID value is (1) enable, the unit idles if it detects that it is blowing warm air into the cold aisle. The unit will attempt to restart at 5 minute i…
1.3.6.1.4.1.318.1.1.13.3.3.2NodeairIRRP500
1.3.6.1.4.1.318.1.1.13.3.3.2.1NodeairIRRP500Group
1.3.6.1.4.1.318.1.1.13.3.3.2.1.1NodeairIRRP500GroupStatus
1.3.6.1.4.1.318.1.1.13.3.3.2.1.1.1ScalarairIRRP500GroupStatusAirFlowUSread-onlymandatoryGroup air flow in cubic feet per minute.
1.3.6.1.4.1.318.1.1.13.3.3.2.1.1.2ScalarairIRRP500GroupStatusAirFlowMetricread-onlymandatoryGroup air flow in liters per second.
1.3.6.1.4.1.318.1.1.13.3.3.2.1.1.3ScalarairIRRP500GroupStatusMaxRackInletTempUSread-onlymandatoryGroup maximum rack inlet temperature in tenths of degrees Fahrenheit.
1.3.6.1.4.1.318.1.1.13.3.3.2.1.1.4ScalarairIRRP500GroupStatusMaxRackInletTempMetricread-onlymandatoryGroup maximum rack inlet temperature in tenths of degrees Celsius.
1.3.6.1.4.1.318.1.1.13.3.3.2.1.1.5ScalarairIRRP500GroupStatusMinRackInletTempUSread-onlymandatoryGroup minimum rack inlet temperature in tenths of degrees Fahrenheit.
1.3.6.1.4.1.318.1.1.13.3.3.2.1.1.6ScalarairIRRP500GroupStatusMinRackInletTempMetricread-onlymandatoryGroup minimum rack inlet temperature in tenths of degrees Celsius.
1.3.6.1.4.1.318.1.1.13.3.3.2.1.1.7ScalarairIRRP500GroupStatusCoolDemandread-onlymandatoryGroup coolant demand in tenths of kiloWatts.
1.3.6.1.4.1.318.1.1.13.3.3.2.1.1.8ScalarairIRRP500GroupStatusCoolOutputread-onlymandatoryGroup coolant output in tenths of kiloWatts.
1.3.6.1.4.1.318.1.1.13.3.3.2.1.1.9ScalarairIRRP500GroupStatusHumidifyDemandread-onlymandatoryThe amount of humidification the group is demanding from the humidifiers in percent.
1.3.6.1.4.1.318.1.1.13.3.3.2.1.1.10ScalarairIRRP500GroupStatusHumidifyOutputread-onlymandatoryThe actual amount of humidification the group is supplying in percent.
1.3.6.1.4.1.318.1.1.13.3.3.2.1.1.11ScalarairIRRP500GroupStatusDehumidifyDemandread-onlymandatoryThe amount of dehumidification the group is demanding from the electric heaters in percent.
1.3.6.1.4.1.318.1.1.13.3.3.2.1.1.12ScalarairIRRP500GroupStatusDehumidifyOutputread-onlymandatoryThe actual amount of dehumidification the group is supplying in percent.
1.3.6.1.4.1.318.1.1.13.3.3.2.1.1.13ScalarairIRRP500GroupStatusReheatDemandread-onlymandatoryThe amount of heating the group is demanding from the electric heaters in percent.
1.3.6.1.4.1.318.1.1.13.3.3.2.1.1.14ScalarairIRRP500GroupStatusReheatOutputread-onlymandatoryThe actual amount of heating the group is supplying in percent.
1.3.6.1.4.1.318.1.1.13.3.3.2.1.1.15ScalarairIRRP500GroupStatusActiveFlowControlStatusread-onlymandatoryStatus of the active flow control system.
1.3.6.1.4.1.318.1.1.13.3.3.2.1.1.16ScalarairIRRP500GroupStatusDewPointTempUSread-onlymandatoryGroup average dew point temperature in tenths of degrees Fahrenheit.
1.3.6.1.4.1.318.1.1.13.3.3.2.1.1.17ScalarairIRRP500GroupStatusDewPointTempMetricread-onlymandatoryGroup average dew point temperature in tenths of degrees Celsius.
1.3.6.1.4.1.318.1.1.13.3.3.2.1.2NodeairIRRP500GroupSetpoints
1.3.6.1.4.1.318.1.1.13.3.3.2.1.2.1ScalarairIRRP500GroupSetpointsCoolUSread-writemandatoryGroup cooling setpoint in tenths of degrees Fahrenheit.
1.3.6.1.4.1.318.1.1.13.3.3.2.1.2.2ScalarairIRRP500GroupSetpointsCoolMetricread-writemandatoryGroup cooling setpoint in tenths of degrees Celsius.
1.3.6.1.4.1.318.1.1.13.3.3.2.1.2.3ScalarairIRRP500GroupSetpointsSupplyAirUSread-writemandatoryGroup supply air setpoint in tenths of degrees Fahrenheit.
1.3.6.1.4.1.318.1.1.13.3.3.2.1.2.4ScalarairIRRP500GroupSetpointsSupplyAirMetricread-writemandatoryGroup supply air setpoint in tenths of degrees Celsius.
1.3.6.1.4.1.318.1.1.13.3.3.2.1.2.5ScalarairIRRP500GroupSetpointsHumidifyread-writemandatoryGroup humidify setpoint in tenths of percent relative humidity.
1.3.6.1.4.1.318.1.1.13.3.3.2.1.2.6ScalarairIRRP500GroupSetpointsDehumidifyread-writemandatoryGroup dehumidify setpoint in tenths of percent relative humidity.
1.3.6.1.4.1.318.1.1.13.3.3.2.1.2.7ScalarairIRRP500GroupSetpointsDehumidifyDeadbandread-writemandatoryGroup dehumidify deadband in percent relative humidity.
1.3.6.1.4.1.318.1.1.13.3.3.2.1.2.8ScalarairIRRP500GroupSetpointsReheatUSread-writemandatoryGroup supply air setpoint in tenths of degrees Fahrenheit.
1.3.6.1.4.1.318.1.1.13.3.3.2.1.2.9ScalarairIRRP500GroupSetpointsReheatMetricread-writemandatoryGroup supply air setpoint in tenths of degrees Celsius.
1.3.6.1.4.1.318.1.1.13.3.3.2.1.2.10ScalarairIRRP500GroupSetpointsFanSpeedPreferenceread-writemandatoryThe preferred fan speed setting.
1.3.6.1.4.1.318.1.1.13.3.3.2.1.2.11ScalarairIRRP500GroupSetpointsFanSpeedControlread-writemandatoryThe fan speed control setting.
1.3.6.1.4.1.318.1.1.13.3.3.2.1.2.12ScalarairIRRP500GroupSetpointsActiveFlowControlBiasread-writemandatoryThe active flow control bias setting.
1.3.6.1.4.1.318.1.1.13.3.3.2.1.3NodeairIRRP500GroupConfig
1.3.6.1.4.1.318.1.1.13.3.3.2.1.3.1ScalarairIRRP500GroupConfigNumberofCoolingUnitsread-writemandatoryThe number of cooling units.
1.3.6.1.4.1.318.1.1.13.3.3.2.1.3.2ScalarairIRRP500GroupConfigConfigurationTyperead-writemandatoryThe group configuration type.
1.3.6.1.4.1.318.1.1.13.3.3.2.1.3.3ScalarairIRRP500GroupConfigPercentGlycolread-writemandatoryThe glycol mixture in percent.
1.3.6.1.4.1.318.1.1.13.3.3.2.1.3.4ScalarairIRRP500GroupConfigCoolGainPread-writemandatoryThe gain component of the cool PID in hundredths.
1.3.6.1.4.1.318.1.1.13.3.3.2.1.3.5ScalarairIRRP500GroupConfigCoolResetRateIread-writemandatoryThe integral component of the cool PID in hundredths.
1.3.6.1.4.1.318.1.1.13.3.3.2.1.3.6ScalarairIRRP500GroupConfigCoolDerivativeDread-writemandatoryThe derivative component of the cool PID in hundredths.
1.3.6.1.4.1.318.1.1.13.3.3.2.1.3.7ScalarairIRRP500GroupConfigHumidifySensitivityBandread-writemandatoryThe percent relative humidity below the setpoint that will cause the humidifier to run at 100% capacity.
1.3.6.1.4.1.318.1.1.13.3.3.2.1.3.8ScalarairIRRP500GroupConfigReheatGainPread-writemandatoryThe gain component of the reheat PID in hundredths.
1.3.6.1.4.1.318.1.1.13.3.3.2.1.3.9ScalarairIRRP500GroupConfigReheatResetRateIread-writemandatoryThe integral component of the reheat PID in hundredths.
1.3.6.1.4.1.318.1.1.13.3.3.2.1.3.10ScalarairIRRP500GroupConfigReheatDerivativeDread-writemandatoryThe derivative component of the reheat PID in hundredths.
1.3.6.1.4.1.318.1.1.13.3.3.2.1.3.11ScalarairIRRP500GroupConfigMaxFanSpeedread-writemandatoryThe maximum desired fan speed setting in percent.
1.3.6.1.4.1.318.1.1.13.3.3.2.1.3.12ScalarairIRRP500GroupConfigNumberofBackupUnitsread-writemandatoryThe number of backup units.
1.3.6.1.4.1.318.1.1.13.3.3.2.1.3.13ScalarairIRRP500GroupConfigRuntimeBalancingEnableread-writemandatoryEnable or disable runtime balancing feature.
1.3.6.1.4.1.318.1.1.13.3.3.2.1.3.14ScalarairIRRP500GroupConfigLoadAssistEnableread-writemandatoryEnable or disable load assist feature.
1.3.6.1.4.1.318.1.1.13.3.3.2.1.3.15ScalarairIRRP500GroupConfigFullRPBackupsread-writemandatoryThe number of full featured RPs that can be used as backup units.
1.3.6.1.4.1.318.1.1.13.3.3.2.1.3.16ScalarairIRRP500GroupConfigNumberOfActiveFlowControllersread-writemandatoryThe number of active flow controllers present in the group.
1.3.6.1.4.1.318.1.1.13.3.3.2.1.3.17ScalarairIRRP500GroupConfigActiveFlowControllerLampTestread-writemandatoryTurns off/on the active flow controller lamp test.
1.3.6.1.4.1.318.1.1.13.3.3.2.1.3.18ScalarairIRRP500GroupConfigAltitudeUSread-writemandatoryThe group altitude of the units above sea level in feet.
1.3.6.1.4.1.318.1.1.13.3.3.2.1.3.19ScalarairIRRP500GroupConfigAltitudeMetricread-writemandatoryThe group altitude of the units above sea level in meters.
1.3.6.1.4.1.318.1.1.13.3.3.2.2NodeairIRRP500Unit
1.3.6.1.4.1.318.1.1.13.3.3.2.2.1NodeairIRRP500UnitIdent
1.3.6.1.4.1.318.1.1.13.3.3.2.2.1.1ScalarairIRRP500UnitIdentIDread-writemandatoryThe unit identification number.
1.3.6.1.4.1.318.1.1.13.3.3.2.2.1.2ScalarairIRRP500UnitIdentNameread-writemandatoryA character string identifying the unit name.
1.3.6.1.4.1.318.1.1.13.3.3.2.2.1.3ScalarairIRRP500UnitIdentLocationread-writemandatoryA character string identifying the unit location.
1.3.6.1.4.1.318.1.1.13.3.3.2.2.1.4ScalarairIRRP500UnitIdentModelNumberread-onlymandatoryA character string identifying the unit model number.
1.3.6.1.4.1.318.1.1.13.3.3.2.2.1.5ScalarairIRRP500UnitIdentSerialNumberread-onlymandatoryA character string identifying the unit serial number.
1.3.6.1.4.1.318.1.1.13.3.3.2.2.1.6ScalarairIRRP500UnitIdentFirmwareRevisionread-onlymandatoryA character string identifying the unit firmware version.
1.3.6.1.4.1.318.1.1.13.3.3.2.2.1.7ScalarairIRRP500UnitIdentHardwareRevisionread-onlymandatoryA character string identifying the unit controller hardware revision.
1.3.6.1.4.1.318.1.1.13.3.3.2.2.1.8ScalarairIRRP500UnitIdentManufactureDateread-onlymandatoryA character string identifying the unit manufacture date.
1.3.6.1.4.1.318.1.1.13.3.3.2.2.2NodeairIRRP500UnitStatus
1.3.6.1.4.1.318.1.1.13.3.3.2.2.2.1ScalarairIRRP500UnitStatusOperateModeread-onlymandatoryThe cooling unit operating mode.
1.3.6.1.4.1.318.1.1.13.3.3.2.2.2.2ScalarairIRRP500UnitStatusMaximumRackInletTempUSread-onlymandatoryThe maximum unit rack inlet temperature in tenths of degrees Fahrenheit.
1.3.6.1.4.1.318.1.1.13.3.3.2.2.2.3ScalarairIRRP500UnitStatusMaximumRackInletTempMetricread-onlymandatoryThe maximum unit rack inlet temperature in tenths of degrees Celsius.
1.3.6.1.4.1.318.1.1.13.3.3.2.2.2.4ScalarairIRRP500UnitStatusSupplyAirTempUSread-onlymandatoryThe unit supply air temperature in tenths of degrees Fahrenheit.
1.3.6.1.4.1.318.1.1.13.3.3.2.2.2.5ScalarairIRRP500UnitStatusSupplyAirTempMetricread-onlymandatoryThe unit supply air temperature in tenths of degrees Celsius.
1.3.6.1.4.1.318.1.1.13.3.3.2.2.2.6ScalarairIRRP500UnitStatusReturnAirTempUSread-onlymandatoryThe unit return air temperature in tenths of degrees Fahrenheit.
1.3.6.1.4.1.318.1.1.13.3.3.2.2.2.7ScalarairIRRP500UnitStatusReturnAirTempMetricread-onlymandatoryThe unit return air temperature in tenths of degrees Celsius.
1.3.6.1.4.1.318.1.1.13.3.3.2.2.2.8ScalarairIRRP500UnitStatusSupplyHumidityread-onlymandatoryThe relative humidity of the supply air in tenths of percent.
1.3.6.1.4.1.318.1.1.13.3.3.2.2.2.9ScalarairIRRP500UnitStatusReturnHumidityread-onlymandatoryThe relative humidity of the return air in tenths of percent.
1.3.6.1.4.1.318.1.1.13.3.3.2.2.2.10ScalarairIRRP500UnitStatusAirFlowUSread-onlymandatoryThe unit air flow in cubic feet per minute.
1.3.6.1.4.1.318.1.1.13.3.3.2.2.2.11ScalarairIRRP500UnitStatusAirFlowMetricread-onlymandatoryThe unit air flow in hundredths of liters per second.
1.3.6.1.4.1.318.1.1.13.3.3.2.2.2.12ScalarairIRRP500UnitStatusFanSpeedread-onlymandatoryThe unit average fan speed in tenths of percent.
1.3.6.1.4.1.318.1.1.13.3.3.2.2.2.13ScalarairIRRP500UnitStatusCoolDemandread-onlymandatoryThe unit cooling demand in tenths of kiloWatts.
1.3.6.1.4.1.318.1.1.13.3.3.2.2.2.14ScalarairIRRP500UnitStatusCoolOutputread-onlymandatoryThe unit cooling output in tenths of kiloWatts.
1.3.6.1.4.1.318.1.1.13.3.3.2.2.2.15ScalarairIRRP500UnitStatusHumidifyDemandread-onlymandatoryThe amount of humidification the unit is demanding from the humidifier in percent.
1.3.6.1.4.1.318.1.1.13.3.3.2.2.2.16ScalarairIRRP500UnitStatusHumidifyOutputread-onlymandatoryThe actual humidification output of the unit in percent.
1.3.6.1.4.1.318.1.1.13.3.3.2.2.2.17ScalarairIRRP500UnitStatusDehumidifyDemandread-onlymandatoryThe amount of dehumidification the unit is demanding in percent.
1.3.6.1.4.1.318.1.1.13.3.3.2.2.2.18ScalarairIRRP500UnitStatusDehumidifyOutputread-onlymandatoryThe actual dehumidification output of the unit in percent.
1.3.6.1.4.1.318.1.1.13.3.3.2.2.2.19ScalarairIRRP500UnitStatusReheatDemandread-onlymandatoryThe amount of heating the unit is demanding from the electric heater in percent.
1.3.6.1.4.1.318.1.1.13.3.3.2.2.2.20ScalarairIRRP500UnitStatusReheatOutputread-onlymandatoryThe actual heating output of the unit in percent.
1.3.6.1.4.1.318.1.1.13.3.3.2.2.2.21ScalarairIRRP500UnitStatusInputStateread-onlymandatoryThe state of the input contact.
1.3.6.1.4.1.318.1.1.13.3.3.2.2.2.22ScalarairIRRP500UnitStatusOutputStateread-onlymandatoryThe state of the output relay.
1.3.6.1.4.1.318.1.1.13.3.3.2.2.2.23ScalarairIRRP500UnitStatusRackInletTemperature1USread-onlymandatoryThe unit rack inlet temperature sensor in tenths of degrees Fahrenheit.
1.3.6.1.4.1.318.1.1.13.3.3.2.2.2.24ScalarairIRRP500UnitStatusRackInletTemperature1Metricread-onlymandatoryThe unit rack inlet temperature sensor in tenths of degrees Celsius.
1.3.6.1.4.1.318.1.1.13.3.3.2.2.2.25ScalarairIRRP500UnitStatusRackInletTemperature2USread-onlymandatoryThe unit rack inlet temperature sensor in tenths of degrees Fahrenheit.
1.3.6.1.4.1.318.1.1.13.3.3.2.2.2.26ScalarairIRRP500UnitStatusRackInletTemperature2Metricread-onlymandatoryThe unit rack inlet temperature sensor in tenths of degrees Celsius.
1.3.6.1.4.1.318.1.1.13.3.3.2.2.2.27ScalarairIRRP500UnitStatusRackInletTemperature3USread-onlymandatoryThe unit rack inlet temperature sensor in tenths of degrees Fahrenheit.
1.3.6.1.4.1.318.1.1.13.3.3.2.2.2.28ScalarairIRRP500UnitStatusRackInletTemperature3Metricread-onlymandatoryThe unit rack inlet temperature sensor in tenths of degrees Celsius.
1.3.6.1.4.1.318.1.1.13.3.3.2.2.2.29ScalarairIRRP500UnitStatusContainmtDPUSread-onlymandatoryThe unit containment differential pressure in hundredths of inches of water.
1.3.6.1.4.1.318.1.1.13.3.3.2.2.2.30ScalarairIRRP500UnitStatusContainmtDPMetricread-onlymandatoryThe unit containment differential pressure in Pa.
1.3.6.1.4.1.318.1.1.13.3.3.2.2.2.31ScalarairIRRP500UnitStatusFilterDPUSread-onlymandatoryThe unit air filter differential pressure in hundredths of inches of water.
1.3.6.1.4.1.318.1.1.13.3.3.2.2.2.32ScalarairIRRP500UnitStatusFilterDPMetricread-onlymandatoryThe unit air filter differential pressure in Pa.
1.3.6.1.4.1.318.1.1.13.3.3.2.2.2.33ScalarairIRRP500UnitStatusHumidifierCurrentread-onlymandatoryThe humidifier current of the unit in tenths of amperes.
1.3.6.1.4.1.318.1.1.13.3.3.2.2.2.34ScalarairIRRP500UnitStatusHumidifierWaterConductivityread-onlymandatoryThe water conductivity in the humidifier of the unit in microSiemens/cm.
1.3.6.1.4.1.318.1.1.13.3.3.2.2.2.35ScalarairIRRP500UnitStatusActivePowerSourceread-onlymandatoryThe power source that is powering the unit.
1.3.6.1.4.1.318.1.1.13.3.3.2.2.2.36ScalarairIRRP500UnitStatusFluidValvePositionread-onlymandatoryThe fluid valve position in percent open.
1.3.6.1.4.1.318.1.1.13.3.3.2.2.2.37ScalarairIRRP500UnitStatusFluidFlowUSread-onlymandatoryThe fluid flow in tenths of gallons per minute.
1.3.6.1.4.1.318.1.1.13.3.3.2.2.2.38ScalarairIRRP500UnitStatusFluidFlowMetricread-onlymandatoryThe fluid flow in hundredths of liters per second.
1.3.6.1.4.1.318.1.1.13.3.3.2.2.2.39ScalarairIRRP500UnitStatusEnteringFluidTemperatureUSread-onlymandatoryThe temperature of the entering fluid in tenths of degrees Fahrenheit.
1.3.6.1.4.1.318.1.1.13.3.3.2.2.2.40ScalarairIRRP500UnitStatusEnteringFluidTemperatureMetricread-onlymandatoryThe temperature of the entering fluid in tenths of degrees Celsius.
1.3.6.1.4.1.318.1.1.13.3.3.2.2.2.41ScalarairIRRP500UnitStatusLeavingFluidTemperatureUSread-onlymandatoryThe temperature of the Leaving fluid in tenths of degrees Fahrenheit.
1.3.6.1.4.1.318.1.1.13.3.3.2.2.2.42ScalarairIRRP500UnitStatusLeavingFluidTemperatureMetricread-onlymandatoryThe temperature of the Leaving fluid in tenths of degrees Celsius.
1.3.6.1.4.1.318.1.1.13.3.3.2.2.2.43ScalarairIRRP500UnitStatusLeakSensorread-onlymandatoryThe state (no-leak/leak) of the leak sensor.
1.3.6.1.4.1.318.1.1.13.3.3.2.2.3NodeairIRRP500UnitRunHours
1.3.6.1.4.1.318.1.1.13.3.3.2.2.3.1ScalarairIRRP500UnitRunHoursAirFilterread-onlymandatoryUnit air filter run hours in hours.
1.3.6.1.4.1.318.1.1.13.3.3.2.2.3.2ScalarairIRRP500UnitRunHoursCondensatePumpread-onlymandatoryUnit condensate pump run hours in hours.
1.3.6.1.4.1.318.1.1.13.3.3.2.2.3.3ScalarairIRRP500UnitRunHoursHumidifierread-onlymandatoryUnit fan right power supply run hours in hours.
1.3.6.1.4.1.318.1.1.13.3.3.2.2.3.4ScalarairIRRP500UnitRunHoursFan1read-onlymandatoryUnit fan 1 run hours in hours.
1.3.6.1.4.1.318.1.1.13.3.3.2.2.3.5ScalarairIRRP500UnitRunHoursHeater1read-onlymandatoryUnit heater 1 run hours in hours.
1.3.6.1.4.1.318.1.1.13.3.3.2.2.3.6ScalarairIRRP500UnitRunHoursFan2read-onlymandatoryUnit fan 2 run hours in hours.
1.3.6.1.4.1.318.1.1.13.3.3.2.2.3.7ScalarairIRRP500UnitRunHoursHeater2read-onlymandatoryUnit Heater 2 run hours in hours.
1.3.6.1.4.1.318.1.1.13.3.3.2.2.3.8ScalarairIRRP500UnitRunHoursFan3read-onlymandatoryUnit fan 3 run hours in hours.
1.3.6.1.4.1.318.1.1.13.3.3.2.2.3.9ScalarairIRRP500UnitRunHoursHeater3read-onlymandatoryUnit heater 3 run hours in hours.
1.3.6.1.4.1.318.1.1.13.3.3.2.2.3.10ScalarairIRRP500UnitRunHoursSystemread-onlymandatoryTotal system run hours.
1.3.6.1.4.1.318.1.1.13.3.3.2.2.4NodeairIRRP500UnitServiceIntervals
1.3.6.1.4.1.318.1.1.13.3.3.2.2.4.1ScalarairIRRP500UnitServiceIntervalAirFilterread-writemandatoryAir filter service interval in weeks.
1.3.6.1.4.1.318.1.1.13.3.3.2.2.4.2ScalarairIRRP500UnitServiceIntervalAirFilterAlarmread-writemandatoryThe air filter service interval alarm enable/disable.
1.3.6.1.4.1.318.1.1.13.3.3.2.2.4.3ScalarairIRRP500UnitServiceIntervalHumidifierread-writemandatoryHumidifier service interval in weeks.
1.3.6.1.4.1.318.1.1.13.3.3.2.2.4.4ScalarairIRRP500UnitServiceIntervalHumidifierAlarmread-writemandatoryThe humidifier service interval alarm enable/disable.
1.3.6.1.4.1.318.1.1.13.3.3.2.2.4.5ScalarairIRRP500UnitServiceIntervalHeaterread-writemandatoryHeater service interval in weeks.
1.3.6.1.4.1.318.1.1.13.3.3.2.2.4.6ScalarairIRRP500UnitServiceIntervalHeaterAlarmread-writemandatoryThe heater service interval alarm enable/disable.
1.3.6.1.4.1.318.1.1.13.3.3.2.2.4.7ScalarairIRRP500UnitServiceIntervalCondensatePumpread-writemandatoryCondensate pump service interval in weeks.
1.3.6.1.4.1.318.1.1.13.3.3.2.2.4.8ScalarairIRRP500UnitServiceIntervalCondensatePumpAlarmread-writemandatoryThe condensate pump service interval alarm enable/disable.
1.3.6.1.4.1.318.1.1.13.3.3.2.2.4.9ScalarairIRRP500UnitServiceIntervalFansread-writemandatoryFans service interval in weeks.
1.3.6.1.4.1.318.1.1.13.3.3.2.2.4.10ScalarairIRRP500UnitServiceIntervalFansAlarmread-writemandatoryThe fans service interval alarm enable/disable.
1.3.6.1.4.1.318.1.1.13.3.3.2.2.5NodeairIRRP500UnitThresholds
1.3.6.1.4.1.318.1.1.13.3.3.2.2.5.1ScalarairIRRP500UnitThresholdsRackInletHighTempUSread-writemandatoryUnit rack inlet air high temperature threshold in tenths of degrees Fahrenheit.
1.3.6.1.4.1.318.1.1.13.3.3.2.2.5.2ScalarairIRRP500UnitThresholdsRackInletHighTempMetricread-writemandatoryUnit rack inlet air high temperature threshold in tenths of degrees Celsius.
1.3.6.1.4.1.318.1.1.13.3.3.2.2.5.3ScalarairIRRP500UnitThresholdsSupplyAirHighTempUSread-writemandatoryUnit supply air temperature high threshold in tenths of degrees Fahrenheit.
1.3.6.1.4.1.318.1.1.13.3.3.2.2.5.4ScalarairIRRP500UnitThresholdsSupplyAirHighTempMetricread-writemandatoryUnit supply air high temperature high threshold in tenths of degrees Celsius.
1.3.6.1.4.1.318.1.1.13.3.3.2.2.5.5ScalarairIRRP500UnitThresholdsReturnAirHighTempUSread-writemandatoryUnit return air high temperature threshold in tenths of degrees Fahrenheit.
1.3.6.1.4.1.318.1.1.13.3.3.2.2.5.6ScalarairIRRP500UnitThresholdsReturnAirHighTempMetricread-writemandatoryUnit return air high temperature threshold in tenths of degrees Celsius.
1.3.6.1.4.1.318.1.1.13.3.3.2.2.5.7ScalarairIRRP500UnitThresholdsReturnHumidityHighread-writemandatoryUnit return humidity high threshold in tenths of percent relative humidity.
1.3.6.1.4.1.318.1.1.13.3.3.2.2.5.8ScalarairIRRP500UnitThresholdsReturnHumidityLowread-writemandatoryUnit return humidity low threshold in tenths of percent relative humidity.
1.3.6.1.4.1.318.1.1.13.3.3.2.2.5.9ScalarairIRRP500UnitThresholdsEnteringFluidHighTempUSread-writemandatoryEntering fluid high temperature threshold in tenths of degrees Fahrenheit.
1.3.6.1.4.1.318.1.1.13.3.3.2.2.5.10ScalarairIRRP500UnitThresholdsEnteringFluidHighTempMetricread-writemandatoryEntering fluid high temperature threshold in tenths of degrees Celsius.
1.3.6.1.4.1.318.1.1.13.3.3.2.2.6NodeairIRRP500UnitConfig
1.3.6.1.4.1.318.1.1.13.3.3.2.2.6.1ScalarairIRRP500UnitConfigStartupDelayread-writemandatoryThe startup delay in seconds.
1.3.6.1.4.1.318.1.1.13.3.3.2.2.6.2ScalarairIRRP500UnitConfigCoolCapacityread-writemandatoryThe cooling capacity options setting.
1.3.6.1.4.1.318.1.1.13.3.3.2.2.6.3ScalarairIRRP500UnitConfigIdleOnLeakDetectread-writemandatoryThe idle on leak options setting.
1.3.6.1.4.1.318.1.1.13.3.3.2.2.6.4ScalarairIRRP500UnitConfigInputNormalStateread-writemandatoryThe normal state of the input contact.
1.3.6.1.4.1.318.1.1.13.3.3.2.2.6.5ScalarairIRRP500UnitConfigOutputNormalStateread-writemandatoryThe normal state of the output relay.
1.3.6.1.4.1.318.1.1.13.3.3.2.2.6.6ScalarairIRRP500UnitConfigOutputSourceread-writemandatoryThe source of output relay change.
1.3.6.1.4.1.318.1.1.13.3.3.2.2.6.7ScalarairIRRP500UnitConfigHumidifyEnableread-writemandatoryEnable/disable humidification.
1.3.6.1.4.1.318.1.1.13.3.3.2.2.6.8ScalarairIRRP500UnitConfigHumidifierControlread-writemandatoryThe humidifier drain control.
1.3.6.1.4.1.318.1.1.13.3.3.2.2.6.9ScalarairIRRP500UnitConfigDehumidifyEnableread-writemandatoryEnable/disable dehumidification.
1.3.6.1.4.1.318.1.1.13.3.3.2.2.6.10ScalarairIRRP500UnitConfigReheatEnableread-writemandatoryEnable/disable reheat.
1.3.6.1.4.1.318.1.1.13.3.3.2.2.6.11ScalarairIRRP500UnitConfigHeatAssistEnableread-writemandatoryEnable/disable heat assist.
1.3.6.1.4.1.318.1.1.13.3.3.2.2.6.12ScalarairIRRP500UnitConfigPowerSourceConfigread-writemandatoryConfigure the input power source: (1) single feed or (2) dual feed.
1.3.6.1.4.1.318.1.1.13.3.3.2.2.6.13ScalarairIRRP500UnitConfigUnitRoleOverrideread-writemandatoryWhen this OID value is (1) automatic, the system determines which units are used as primary units and which units are used as backups. When this OID value is (…
1.3.6.1.4.1.318.1.1.13.3.3.2.2.6.14ScalarairIRRP500UnitConfigSecondaryPowerFeedCapabilityread-writemandatoryAvailable on chilled water units. When the power source config setting is set to dual, setting this value to reduced (2) will inhibit the heater and humdifier …
1.3.6.1.4.1.318.1.1.13.3.3.2.2.6.15ScalarairIRRP500UnitConfigIdleOnCoolFailread-writemandatoryWhen this OID value is (1) enable, the unit idles if it detects that it is blowing warm air into the cold aisle. The unit will attempt to restart at 5 minute i…
1.3.6.1.4.1.318.1.1.13.3.4NodeairIRSC
1.3.6.1.4.1.318.1.1.13.3.4.1NodeairIRSCUnit
1.3.6.1.4.1.318.1.1.13.3.4.1.1NodeairIRSCUnitIdent
1.3.6.1.4.1.318.1.1.13.3.4.1.1.1ScalarairIRSCUnitIdentNameread-writemandatoryA character string identifying the unit name.
1.3.6.1.4.1.318.1.1.13.3.4.1.1.2ScalarairIRSCUnitIdentLocationread-writemandatoryA character string identifying the unit location.
1.3.6.1.4.1.318.1.1.13.3.4.1.1.3ScalarairIRSCUnitIdentModelNumberread-onlymandatoryA character string identifying the unit model number.
1.3.6.1.4.1.318.1.1.13.3.4.1.1.4ScalarairIRSCUnitIdentSerialNumberread-onlymandatoryA character string identifying the unit serial number.
1.3.6.1.4.1.318.1.1.13.3.4.1.1.5ScalarairIRSCUnitIdentFirmwareRevisionread-onlymandatoryA character string identifying the unit firmware version.
1.3.6.1.4.1.318.1.1.13.3.4.1.1.6ScalarairIRSCUnitIdentHardwareRevisionread-onlymandatoryA character string identifying the unit controller hardware revision.
1.3.6.1.4.1.318.1.1.13.3.4.1.1.7ScalarairIRSCUnitIdentManufactureDateread-onlymandatoryA character string identifying the unit manufacture date.
1.3.6.1.4.1.318.1.1.13.3.4.1.2NodeairIRSCUnitStatus
1.3.6.1.4.1.318.1.1.13.3.4.1.2.1ScalarairIRSCUnitStatusOperateModeread-onlymandatoryThe cooling unit operating mode.
1.3.6.1.4.1.318.1.1.13.3.4.1.2.2ScalarairIRSCUnitStatusCoolOutputread-onlymandatoryThe unit cooling output in tenths of kW.
1.3.6.1.4.1.318.1.1.13.3.4.1.2.3ScalarairIRSCUnitStatusCoolDemandread-onlymandatoryThe unit cooling demand in tenths of kW.
1.3.6.1.4.1.318.1.1.13.3.4.1.2.4ScalarairIRSCUnitStatusAirFlowUSread-onlymandatoryThe unit air flow in cubic feet per minute.
1.3.6.1.4.1.318.1.1.13.3.4.1.2.5ScalarairIRSCUnitStatusAirFlowMetricread-onlymandatoryThe unit air flow in liters per second.
1.3.6.1.4.1.318.1.1.13.3.4.1.2.6ScalarairIRSCUnitStatusRackInletTempUSread-onlymandatoryThe unit rack inlet temperature in tenths of degrees Fahrenheit.
1.3.6.1.4.1.318.1.1.13.3.4.1.2.7ScalarairIRSCUnitStatusRackInletTempMetricread-onlymandatoryThe unit rack inlet temperature in tenths of degrees Celsius.
1.3.6.1.4.1.318.1.1.13.3.4.1.2.8ScalarairIRSCUnitStatusSupplyAirTempUSread-onlymandatoryThe unit supply air temperature in tenths of degrees Fahrenheit.
1.3.6.1.4.1.318.1.1.13.3.4.1.2.9ScalarairIRSCUnitStatusSupplyAirTempMetricread-onlymandatoryThe unit supply air temperature in tenths of degrees Celsius.
1.3.6.1.4.1.318.1.1.13.3.4.1.2.10ScalarairIRSCUnitStatusReturnAirTempUSread-onlymandatoryThe unit return air temperature in tenths of degrees Fahrenheit.
1.3.6.1.4.1.318.1.1.13.3.4.1.2.11ScalarairIRSCUnitStatusReturnAirTempMetricread-onlymandatoryThe unit return air temperature in tenths of degrees Celsius.
1.3.6.1.4.1.318.1.1.13.3.4.1.2.12ScalarairIRSCUnitStatusSuctionTempUSread-onlymandatoryThe unit suction temperature in tenths of degrees Fahrenheit.
1.3.6.1.4.1.318.1.1.13.3.4.1.2.13ScalarairIRSCUnitStatusSuctionTempMetricread-onlymandatoryThe unit suction temperature in tenths of degrees Celsius.
1.3.6.1.4.1.318.1.1.13.3.4.1.2.14ScalarairIRSCUnitStatusSuperheatTempUSread-onlymandatoryThe unit superheat temperature in tenths of degrees Fahrenheit.
1.3.6.1.4.1.318.1.1.13.3.4.1.2.15ScalarairIRSCUnitStatusSuperheatTempMetricread-onlymandatoryThe unit superheat temperature in tenths of degrees Celsius.
1.3.6.1.4.1.318.1.1.13.3.4.1.2.16ScalarairIRSCUnitStatusContainmtDPUSread-onlymandatoryThe unit containment differential pressure in hundredths of inches of water.
1.3.6.1.4.1.318.1.1.13.3.4.1.2.17ScalarairIRSCUnitStatusContainmtDPMetricread-onlymandatoryThe unit containment differential pressure in Pa.
1.3.6.1.4.1.318.1.1.13.3.4.1.2.18ScalarairIRSCUnitStatusFilterDPUSread-onlymandatoryThe unit air filter differential pressure in hundredths of inches of water.
1.3.6.1.4.1.318.1.1.13.3.4.1.2.19ScalarairIRSCUnitStatusFilterDPMetricread-onlymandatoryThe unit air filter differential pressure in Pa.
1.3.6.1.4.1.318.1.1.13.3.4.1.2.20ScalarairIRSCUnitStatusSuctionPressureUSread-onlymandatoryUnit suction pressure in pounds per square inch (PSI).
1.3.6.1.4.1.318.1.1.13.3.4.1.2.21ScalarairIRSCUnitStatusSuctionPressureMetricread-onlymandatoryUnit suction pressure in kiloPascals (kPa).
1.3.6.1.4.1.318.1.1.13.3.4.1.2.22ScalarairIRSCUnitStatusDischargePressureUSread-onlymandatoryUnit discharge pressure in pounds per square inch (PSI).
1.3.6.1.4.1.318.1.1.13.3.4.1.2.23ScalarairIRSCUnitStatusDischargePressureMetricread-onlymandatoryUnit discharge pressure in kiloPascals (kPa).
1.3.6.1.4.1.318.1.1.13.3.4.1.2.24ScalarairIRSCUnitStatusEvaporatorFanSpeedread-onlymandatoryThe unit average evaporator fan speed in tenths of percent.
1.3.6.1.4.1.318.1.1.13.3.4.1.2.25ScalarairIRSCUnitStatusCondenserFanSpeedread-onlymandatoryThe unit average condenser fan speed in tenths of percent.
1.3.6.1.4.1.318.1.1.13.3.4.1.2.26ScalarairIRSCUnitStatusInputStateread-onlymandatoryThe state of the input contact.
1.3.6.1.4.1.318.1.1.13.3.4.1.2.27ScalarairIRSCUnitStatusOutputStateread-onlymandatoryThe state of the output relay.
1.3.6.1.4.1.318.1.1.13.3.4.1.2.28ScalarairIRSCUnitStatusCondOutletTempUSread-onlymandatoryThe unit condenser outlet air temperature in tenths of degrees Fahrenheit.
1.3.6.1.4.1.318.1.1.13.3.4.1.2.29ScalarairIRSCUnitStatusCondOutletTempMetricread-onlymandatoryThe unit condenser outlet air temperature in tenths of degrees Celsius.
1.3.6.1.4.1.318.1.1.13.3.4.1.2.30ScalarairIRSCUnitStatusCondInletTempUSread-onlymandatoryThe unit condenser inlet air temperature in tenths of degrees Fahrenheit.
1.3.6.1.4.1.318.1.1.13.3.4.1.2.31ScalarairIRSCUnitStatusCondInletTempMetricread-onlymandatoryThe unit condenser inlet air temperature in tenths of degrees Celsius.
1.3.6.1.4.1.318.1.1.13.3.4.1.2.32ScalarairIRSCUnitStatusCompressorread-onlymandatoryThe state (off/on) of the compressor.
1.3.6.1.4.1.318.1.1.13.3.4.1.2.33ScalarairIRSCUnitStatusLeakSensorread-onlymandatoryThe state (no-leak/leak) of the leak sensor.
1.3.6.1.4.1.318.1.1.13.3.4.1.3NodeairIRSCUnitRunHours
1.3.6.1.4.1.318.1.1.13.3.4.1.3.1ScalarairIRSCUnitRunHoursAirFilterread-onlymandatoryUnit air filter run hours.
1.3.6.1.4.1.318.1.1.13.3.4.1.3.2ScalarairIRSCUnitRunHoursEvaporatorFan1read-onlymandatoryUnit evaporator fan 1 run hours.
1.3.6.1.4.1.318.1.1.13.3.4.1.3.3ScalarairIRSCUnitRunHoursEvaporatorFan2read-onlymandatoryUnit evaporator fan 2 run hours.
1.3.6.1.4.1.318.1.1.13.3.4.1.3.4ScalarairIRSCUnitRunHoursEvaporatorFan3read-onlymandatoryUnit evaporator fan 3 run hours.
1.3.6.1.4.1.318.1.1.13.3.4.1.3.5ScalarairIRSCUnitRunHoursCondenserFan1read-onlymandatoryUnit condenser fan 1 run hours.
1.3.6.1.4.1.318.1.1.13.3.4.1.3.6ScalarairIRSCUnitRunHoursCondenserFan2read-onlymandatoryUnit condenser fan 2 run hours.
1.3.6.1.4.1.318.1.1.13.3.4.1.3.7ScalarairIRSCUnitRunHoursCondenserFan3read-onlymandatoryUnit condenser fan 3 run hours.
1.3.6.1.4.1.318.1.1.13.3.4.1.3.8ScalarairIRSCUnitRunHoursFanPowerSupplyLeftread-onlymandatoryUnit fan left power supply run hours.
1.3.6.1.4.1.318.1.1.13.3.4.1.3.9ScalarairIRSCUnitRunHoursFanPowerSupplyRightread-onlymandatoryUnit fan right power supply run hours.
1.3.6.1.4.1.318.1.1.13.3.4.1.3.10ScalarairIRSCUnitRunHoursCondensatePumpread-onlymandatoryUnit condensate pump run hours.
1.3.6.1.4.1.318.1.1.13.3.4.1.3.11ScalarairIRSCUnitRunHoursCompressorread-onlymandatoryUnit compressor run hours.
1.3.6.1.4.1.318.1.1.13.3.4.1.4NodeairIRSCUnitServiceIntervals
1.3.6.1.4.1.318.1.1.13.3.4.1.4.1ScalarairIRSCUnitServiceIntervalsAirFilterread-writemandatoryAir filter service interval in weeks.
1.3.6.1.4.1.318.1.1.13.3.4.1.4.2ScalarairIRSCUnitServiceIntervalsAirFilterAlarmread-writemandatoryThe air filter service interval alarm enable/disable.
1.3.6.1.4.1.318.1.1.13.3.4.1.5NodeairIRSCUnitThresholds
1.3.6.1.4.1.318.1.1.13.3.4.1.5.1ScalarairIRSCUnitThresholdsRackInletHighTempUSread-writemandatoryUnit rack inlet air high temperature threshold in tenths of degrees Fahrenheit.
1.3.6.1.4.1.318.1.1.13.3.4.1.5.2ScalarairIRSCUnitThresholdsRackInletHighTempMetricread-writemandatoryUnit rack inlet air high temperature threshold in tenths of degrees Celsius.
1.3.6.1.4.1.318.1.1.13.3.4.1.5.3ScalarairIRSCUnitThresholdsSupplyAirHighTempUSread-writemandatoryUnit supply air high temperature threshold in tenths of degrees Fahrenheit.
1.3.6.1.4.1.318.1.1.13.3.4.1.5.4ScalarairIRSCUnitThresholdsSupplyAirHighTempMetricread-writemandatoryUnit supply air high temperature threshold in tenths of degrees Celsius.
1.3.6.1.4.1.318.1.1.13.3.4.1.5.5ScalarairIRSCUnitThresholdsReturnAirHighTempUSread-writemandatoryUnit return air high temperature threshold in tenths of degrees Fahrenheit.
1.3.6.1.4.1.318.1.1.13.3.4.1.5.6ScalarairIRSCUnitThresholdsReturnAirHighTempMetricread-writemandatoryUnit return air high temperature threshold in tenths of degrees Celsius.
1.3.6.1.4.1.318.1.1.13.3.4.1.6NodeairIRSCUnitSetpoints
1.3.6.1.4.1.318.1.1.13.3.4.1.6.1ScalarairIRSCUnitSetptsCoolSetpointUSread-writemandatoryUnit cooling setpoint in tenths of degrees Fahrenheit.
1.3.6.1.4.1.318.1.1.13.3.4.1.6.2ScalarairIRSCUnitSetptsCoolSetpointMetricread-writemandatoryUnit cooling setpoint in tenths of degrees Celsius.
1.3.6.1.4.1.318.1.1.13.3.4.1.6.3ScalarairIRSCUnitSetptsCoolDeadbandUSread-writemandatoryUnit cooling deadband in tenths of degrees Fahrenheit.
1.3.6.1.4.1.318.1.1.13.3.4.1.6.4ScalarairIRSCUnitSetptsCoolDeadbandMetricread-writemandatoryUnit cooling deadband in tenths of degrees Celsius.
1.3.6.1.4.1.318.1.1.13.3.4.1.6.5ScalarairIRSCUnitSetptsFanSpeedPreferenceread-writemandatoryThe preferred fan speed setting.
1.3.6.1.4.1.318.1.1.13.3.4.1.6.6ScalarairIRSCUnitSetptsSupplyAirSetpointUSread-writemandatoryUnit supply air setpoint in tenths of degrees Fahrenheit.
1.3.6.1.4.1.318.1.1.13.3.4.1.6.7ScalarairIRSCUnitSetptsSupplyAirSetpointMetricread-writemandatoryUnit supply air setpoint in tenths of degrees Celsius.
1.3.6.1.4.1.318.1.1.13.3.4.1.7NodeairIRSCUnitConfig
1.3.6.1.4.1.318.1.1.13.3.4.1.7.1ScalarairIRSCUnitConfigConfigurationTyperead-writemandatoryThe unit configuration type.
1.3.6.1.4.1.318.1.1.13.3.4.1.7.2ScalarairIRSCUnitConfigCapacityControlTyperead-writemandatoryThe unit capacity control.
1.3.6.1.4.1.318.1.1.13.3.4.1.7.3ScalarairIRSCUnitConfigStartupDelayread-writemandatoryThe startup delay in seconds.
1.3.6.1.4.1.318.1.1.13.3.4.1.7.4ScalarairIRSCUnitConfigIdleOnLeakDetectread-writemandatoryThe idle on leak options setting.
1.3.6.1.4.1.318.1.1.13.3.4.1.7.5ScalarairIRSCUnitConfigInputNormalStateread-writemandatoryThe normal state of the input contact.
1.3.6.1.4.1.318.1.1.13.3.4.1.7.6ScalarairIRSCUnitConfigOutputNormalStateread-writemandatoryThe normal state of the output relay.
1.3.6.1.4.1.318.1.1.13.3.4.1.7.7ScalarairIRSCUnitConfigOutputSourceread-writemandatoryThe source of output relay change.
1.3.6.1.4.1.318.1.1.13.3.4.1.7.8ScalarairIRSCUnitConfigAltitudeUSread-writemandatoryThe altitude of the unit above sea level in feet.
1.3.6.1.4.1.318.1.1.13.3.4.1.7.9ScalarairIRSCUnitConfigAltitudeMetricread-writemandatoryThe altitude of the unit above sea level in meters.
1.3.6.1.4.1.318.1.1.13.3.4.1.7.10ScalarairIRSCUnitConfigOpControlread-writemandatoryThe unit operational control.
1.3.6.1.4.1.318.1.1.13.3.4.2NodeairIRSCGroup
1.3.6.1.4.1.318.1.1.13.3.4.2.1NodeairIRSCGroupStatus
1.3.6.1.4.1.318.1.1.13.3.4.2.1.1ScalarairIRSCGroupStatusCoolOutputread-onlymandatoryThe group cooling output in tenths of kW.
1.3.6.1.4.1.318.1.1.13.3.4.2.1.2ScalarairIRSCGroupStatusCoolDemandread-onlymandatoryThe group cooling demand in tenths of kW.
1.3.6.1.4.1.318.1.1.13.3.4.2.1.3ScalarairIRSCGroupStatusAirFlowUSread-onlymandatoryThe group air flow in cubic feet per minute.
1.3.6.1.4.1.318.1.1.13.3.4.2.1.4ScalarairIRSCGroupStatusAirFlowMetricread-onlymandatoryThe group air flow in liters per second.
1.3.6.1.4.1.318.1.1.13.3.4.2.1.5ScalarairIRSCGroupStatusMaxRackInletTempUSread-onlymandatoryThe group maximum rack inlet temperature in tenths of degrees Fahrenheit.
1.3.6.1.4.1.318.1.1.13.3.4.2.1.6ScalarairIRSCGroupStatusMaxRackInletTempMetricread-onlymandatoryThe group maximum rack inlet temperature in tenths of degrees Celsius.
1.3.6.1.4.1.318.1.1.13.3.4.2.1.7ScalarairIRSCGroupStatusMinRackInletTempUSread-onlymandatoryThe group minimum rack inlet temperature in tenths of degrees Fahrenheit.
1.3.6.1.4.1.318.1.1.13.3.4.2.1.8ScalarairIRSCGroupStatusMinRackInletTempMetricread-onlymandatoryThe group minimum rack inlet temperature in tenths of degrees Celsius.
1.3.6.1.4.1.318.1.1.13.3.4.2.1.9ScalarairIRSCGroupStatusMaxReturnAirTempUSread-onlymandatoryThe group maximum return air temperature in tenths of degrees Fahrenheit.
1.3.6.1.4.1.318.1.1.13.3.4.2.1.10ScalarairIRSCGroupStatusMaxReturnAirTempMetricread-onlymandatoryThe group maximum return air temperature in tenths of degrees Celsius.
1.3.6.1.4.1.318.1.1.13.3.4.2.1.11ScalarairIRSCGroupStatusMinReturnAirTempUSread-onlymandatoryThe group minimum return air temperature in tenths of degrees Fahrenheit.
1.3.6.1.4.1.318.1.1.13.3.4.2.1.12ScalarairIRSCGroupStatusMinReturnAirTempMetricread-onlymandatoryThe group minimum return air temperature in tenths of degrees Celsius.
1.3.6.1.4.1.318.1.1.13.3.4.2.1.13ScalarairIRSCGroupStatusActiveFlowControlStatusread-onlymandatoryStatus of the active flow control system.
1.3.6.1.4.1.318.1.1.13.3.4.2.2NodeairIRSCGroupSetpoints
1.3.6.1.4.1.318.1.1.13.3.4.2.2.1ScalarairIRSCGroupSetptsCoolSetpointUSread-writemandatoryGroup cooling setpoint in tenths of degrees Fahrenheit.
1.3.6.1.4.1.318.1.1.13.3.4.2.2.2ScalarairIRSCGroupSetptsCoolSetpointMetricread-writemandatoryGroup cooling setpoint in tenths of degrees Celsius.
1.3.6.1.4.1.318.1.1.13.3.4.2.2.3ScalarairIRSCGroupSetptsCoolDeadbandUSread-writemandatoryGroup cooling deadband in tenths of degrees Fahrenheit.
1.3.6.1.4.1.318.1.1.13.3.4.2.2.4ScalarairIRSCGroupSetptsCoolDeadbandMetricread-writemandatoryGroup cooling deadband in tenths of degrees Celsius.
1.3.6.1.4.1.318.1.1.13.3.4.2.2.5ScalarairIRSCGroupSetptsFanSpeedPreferenceread-writemandatoryThe group preferred fan speed setting.
1.3.6.1.4.1.318.1.1.13.3.4.2.2.6ScalarairIRSCGroupSetptsSupplyAirSetpointUSread-writemandatoryGroup supply air setpoint in tenths of degrees Fahrenheit.
1.3.6.1.4.1.318.1.1.13.3.4.2.2.7ScalarairIRSCGroupSetptsSupplyAirSetpointMetricread-writemandatoryGroup supply air setpoint in tenths of degrees Celsius.
1.3.6.1.4.1.318.1.1.13.3.4.2.2.8ScalarairIRSCGroupSetpointsActiveFlowControlBiasread-writemandatoryThe active flow control bias setting.
1.3.6.1.4.1.318.1.1.13.3.4.2.3NodeairIRSCGroupConfig
1.3.6.1.4.1.318.1.1.13.3.4.2.3.1ScalarairIRSCGroupConfigNumberofCoolingUnitsread-writemandatoryThe number of cooling units.
1.3.6.1.4.1.318.1.1.13.3.4.2.3.2ScalarairIRSCGroupConfigConfigurationTyperead-writemandatoryThe group configuration type.
1.3.6.1.4.1.318.1.1.13.3.4.2.3.3ScalarairIRSCGroupConfigCapacityControlTyperead-writemandatoryThe group capacity control.
1.3.6.1.4.1.318.1.1.13.3.4.2.3.4ScalarairIRSCGroupConfigAltitudeUSread-writemandatoryThe group altitude of the units above sea level in feet.
1.3.6.1.4.1.318.1.1.13.3.4.2.3.5ScalarairIRSCGroupConfigAltitudeMetricread-writemandatoryThe group altitude of the units above sea level in meters.
1.3.6.1.4.1.318.1.1.13.3.4.2.3.6ScalarairIRSCGroupConfigFanSpeedControlread-writemandatoryThe group fan speed control.
1.3.6.1.4.1.318.1.1.13.3.4.2.3.7ScalarairIRSCGroupConfigNumberOfActiveFlowControllersread-writemandatoryThe number of active flow controllers present in the group.
1.3.6.1.4.1.318.1.1.13.3.4.2.3.8ScalarairIRSCGroupConfigActiveFlowControllerLampTestread-writemandatoryTurns off/on the active flow controller lamp test.
1.3.6.1.4.1.318.1.1.13.4NodeairIRGen2
1.3.6.1.4.1.318.1.1.13.4.1NodeairIRG2Ident
1.3.6.1.4.1.318.1.1.13.4.1.1ScalarairIRG2IdentNameread-writemandatoryA character string identifying the unit name.
1.3.6.1.4.1.318.1.1.13.4.1.2ScalarairIRG2IdentLocationread-writemandatoryA character string identifying the unit location.
1.3.6.1.4.1.318.1.1.13.4.1.3ScalarairIRG2IdentModelNumberread-onlymandatoryA character string identifying the unit model number.
1.3.6.1.4.1.318.1.1.13.4.1.4ScalarairIRG2IdentSerialNumberread-onlymandatoryA character string identifying the unit serial number.
1.3.6.1.4.1.318.1.1.13.4.1.5ScalarairIRG2IdentFirmwareRevisionread-onlymandatoryA character string identifying the unit firmware version.
1.3.6.1.4.1.318.1.1.13.4.1.6ScalarairIRG2IdentHardwareRevisionread-onlymandatoryA character string identifying the unit controller hardware revision.
1.3.6.1.4.1.318.1.1.13.4.1.7ScalarairIRG2IdentManufactureDateread-onlymandatoryA character string identifying the unit manufacture date.
1.3.6.1.4.1.318.1.1.13.4.1.8ScalarairIRG2IdentUnitSysOIDread-onlymandatoryThis OID contains an OID path to the device's top level unit data.
1.3.6.1.4.1.318.1.1.13.4.1.9ScalarairIRG2IdentGroupSysOIDread-onlymandatoryThis OID contains an OID path to the device's top level group data.
1.3.6.1.4.1.318.1.1.13.4.2NodeairIRG2Group
1.3.6.1.4.1.318.1.1.13.4.2.1NodeairIRG2GroupStatus
1.3.6.1.4.1.318.1.1.13.4.2.1.1ScalarairIRG2GroupStatusCoolOutputread-onlymandatoryThe group cooling output in tenths of kilowatts (kW).
1.3.6.1.4.1.318.1.1.13.4.2.1.2ScalarairIRG2GroupStatusCoolDemandread-onlymandatoryThe group cooling demand in tenths of kilowatts (kW).
1.3.6.1.4.1.318.1.1.13.4.2.1.3ScalarairIRG2GroupStatusAirFlowUSread-onlymandatoryThe group air flow in cubic feet per minute.
1.3.6.1.4.1.318.1.1.13.4.2.1.4ScalarairIRG2GroupStatusAirFlowMetricread-onlymandatoryThe group air flow in hundredths of liters per second.
1.3.6.1.4.1.318.1.1.13.4.2.1.5ScalarairIRG2GroupStatusMaxRackInletTempUSread-onlymandatoryThe group maximum rack inlet temperature in tenths of degrees Fahrenheit.
1.3.6.1.4.1.318.1.1.13.4.2.1.6ScalarairIRG2GroupStatusMaxRackInletTempMetricread-onlymandatoryThe group maximum rack inlet temperature in tenths of degrees Celsius.
1.3.6.1.4.1.318.1.1.13.4.2.1.7ScalarairIRG2GroupStatusMinRackInletTempUSread-onlymandatoryThe group minimum rack inlet temperature in tenths of degrees Fahrenheit.
1.3.6.1.4.1.318.1.1.13.4.2.1.8ScalarairIRG2GroupStatusMinRackInletTempMetricread-onlymandatoryThe group minimum rack inlet temperature in tenths of degrees Celsius.
1.3.6.1.4.1.318.1.1.13.4.2.1.9ScalarairIRG2GroupStatusMaxReturnAirTempUSread-onlymandatoryThe group maximum return air temperature in tenths of degrees Fahrenheit.
1.3.6.1.4.1.318.1.1.13.4.2.1.10ScalarairIRG2GroupStatusMaxReturnAirTempMetricread-onlymandatoryThe group maximum return air temperature in tenths of degrees Celsius.
1.3.6.1.4.1.318.1.1.13.4.2.1.11ScalarairIRG2GroupStatusMinReturnAirTempUSread-onlymandatoryThe group minimum return air temperature in tenths of degrees Fahrenheit.
1.3.6.1.4.1.318.1.1.13.4.2.1.12ScalarairIRG2GroupStatusMinReturnAirTempMetricread-onlymandatoryThe group minimum return air temperature in tenths of degrees Celsius.
1.3.6.1.4.1.318.1.1.13.4.2.1.13ScalarairIRG2GroupStatusActiveFlowControlStatusread-onlymandatoryStatus of the active flow control system.
1.3.6.1.4.1.318.1.1.13.4.2.2NodeairIRG2GroupSetpoints
1.3.6.1.4.1.318.1.1.13.4.2.2.1ScalarairIRG2GroupSetptsCoolSetpointUSread-writemandatoryGroup cooling setpoint in tenths of degrees Fahrenheit.
1.3.6.1.4.1.318.1.1.13.4.2.2.2ScalarairIRG2GroupSetptsCoolSetpointMetricread-writemandatoryGroup cooling setpoint in tenths of degrees Celsius.
1.3.6.1.4.1.318.1.1.13.4.2.2.3ScalarairIRG2GroupSetptsCoolDeadbandUSread-writemandatoryGroup cooling deadband in tenths of degrees Fahrenheit.
1.3.6.1.4.1.318.1.1.13.4.2.2.4ScalarairIRG2GroupSetptsCoolDeadbandMetricread-writemandatoryGroup cooling deadband in tenths of degrees Celsius.
1.3.6.1.4.1.318.1.1.13.4.2.2.5ScalarairIRG2GroupSetptsFanSpeedPreferenceread-writemandatoryThe group preferred fan speed setting.
1.3.6.1.4.1.318.1.1.13.4.2.2.6ScalarairIRG2GroupSetptsSupplyAirSetpointUSread-writemandatoryGroup supply air setpoint in tenths of degrees Fahrenheit.
1.3.6.1.4.1.318.1.1.13.4.2.2.7ScalarairIRG2GroupSetptsSupplyAirSetpointMetricread-writemandatoryGroup supply air setpoint in tenths of degrees Celsius.
1.3.6.1.4.1.318.1.1.13.4.2.2.8ScalarairIRG2GroupSetpointsActiveFlowControlBiasread-writemandatoryThe active flow control bias setting.
1.3.6.1.4.1.318.1.1.13.4.2.3NodeairIRG2GroupConfig
1.3.6.1.4.1.318.1.1.13.4.2.3.1ScalarairIRG2GroupConfigNumberofCoolingUnitsread-writemandatoryThe number of cooling units.
1.3.6.1.4.1.318.1.1.13.4.2.3.2ScalarairIRG2GroupConfigConfigurationTyperead-writemandatoryThe group configuration type.
1.3.6.1.4.1.318.1.1.13.4.2.3.3ScalarairIRG2GroupConfigCapacityControlTyperead-writemandatoryThe group capacity control.
1.3.6.1.4.1.318.1.1.13.4.2.3.4ScalarairIRG2GroupConfigFanSpeedControlread-writemandatoryThe group fan speed control.
1.3.6.1.4.1.318.1.1.13.4.2.3.5ScalarairIRG2GroupConfigCoolGainPread-writemandatoryThe gain component of the PID in hundredths.
1.3.6.1.4.1.318.1.1.13.4.2.3.6ScalarairIRG2GroupConfigCoolResetRateIread-writemandatoryThe integral component of the PID in hundredths.
1.3.6.1.4.1.318.1.1.13.4.2.3.7ScalarairIRG2GroupConfigCoolDerivativeDread-writemandatoryThe derivative component of the PID in hundredths.
1.3.6.1.4.1.318.1.1.13.4.2.3.8ScalarairIRG2GroupConfigCoolPIDResetread-writemandatoryWill reset the PID coefficients back to the factory defaults.
1.3.6.1.4.1.318.1.1.13.4.2.3.9ScalarairIRG2GroupConfigNumberofBackupUnitsread-writemandatoryThe number of backup units.
1.3.6.1.4.1.318.1.1.13.4.2.3.10ScalarairIRG2GroupConfigRuntimeBalancingEnableread-writemandatoryEnable or disable runtime balancing feature.
1.3.6.1.4.1.318.1.1.13.4.2.3.11ScalarairIRG2GroupConfigLoadAssistEnableread-writemandatoryEnable or disable load assist feature.
1.3.6.1.4.1.318.1.1.13.4.2.3.12ScalarairIRG2GroupConfigNumberOfActiveFlowControllersread-writemandatoryThe number of active flow controllers present in the group.
1.3.6.1.4.1.318.1.1.13.4.2.3.13ScalarairIRG2GroupConfigActiveFlowControllerLampTestread-writemandatoryTurns off/on the active flow controller lamp test.
1.3.6.1.4.1.318.1.1.13.4.2.3.14ScalarairIRG2GroupConfigAltitudeUSread-writemandatoryThe group altitude of the units above sea level in feet.
1.3.6.1.4.1.318.1.1.13.4.2.3.15ScalarairIRG2GroupConfigAltitudeMetricread-writemandatoryThe group altitude of the units above sea level in meters.
1.3.6.1.4.1.318.1.1.13.4.3NodeairIRG2Alarms
1.3.6.1.4.1.318.1.1.13.4.3.1ScalarairIRG2AlarmsTableSizeread-onlymandatoryThe number of active alarms in the airIRG2AlarmsTable.
1.3.6.1.4.1.318.1.1.13.4.3.2TableairIRG2AlarmsTablenot-accessiblemandatoryTable of active alarms for the device.
1.3.6.1.4.1.318.1.1.13.4.3.2.1RowairIRG2AlarmsEntrynot-accessiblemandatoryAlarms specification
1.3.6.1.4.1.318.1.1.13.4.3.2.1.1ColumnairIRG2AlarmsIndexread-onlymandatoryAlarm index.
1.3.6.1.4.1.318.1.1.13.4.3.2.1.2ColumnairIRG2AlarmsEventCoderead-onlymandatoryCode for the alarm.
1.3.6.1.4.1.318.1.1.13.4.3.2.1.3ColumnairIRG2AlarmsDescriptionread-onlymandatoryDescription of the alarm.
1.3.6.1.4.1.318.1.1.13.4.4NodeairIRG2RC
1.3.6.1.4.1.318.1.1.13.4.5NodeairIRG2RD
1.3.6.1.4.1.318.1.1.13.4.5.1NodeairIRG2RDType1
1.3.6.1.4.1.318.1.1.13.4.5.2NodeairIRG2RDType2
1.3.6.1.4.1.318.1.1.13.4.5.2.1NodeairIRG2RDT2Status
1.3.6.1.4.1.318.1.1.13.4.5.2.1.1ScalarairIRG2RDT2StatusOperateModeread-onlymandatoryThe cooling unit operating mode.
1.3.6.1.4.1.318.1.1.13.4.5.2.1.2ScalarairIRG2RDT2StatusCoolOutputread-onlymandatoryThe unit cooling output in tenths of kilowatts (kW).
1.3.6.1.4.1.318.1.1.13.4.5.2.1.3ScalarairIRG2RDT2StatusCoolDemandread-onlymandatoryThe unit cooling demand in tenths of kilowatts (kW).
1.3.6.1.4.1.318.1.1.13.4.5.2.1.4ScalarairIRG2RDT2StatusAirFlowUSread-onlymandatoryThe unit air flow in cubic feet per minute.
1.3.6.1.4.1.318.1.1.13.4.5.2.1.5ScalarairIRG2RDT2StatusAirFlowMetricread-onlymandatoryThe unit air flow in liters per second.
1.3.6.1.4.1.318.1.1.13.4.5.2.1.6ScalarairIRG2RDT2StatusRackInletTempUSread-onlymandatoryThe unit rack inlet temperature in tenths of degrees Fahrenheit.
1.3.6.1.4.1.318.1.1.13.4.5.2.1.7ScalarairIRG2RDT2StatusRackInletTempMetricread-onlymandatoryThe unit rack inlet temperature in tenths of degrees Celsius.
1.3.6.1.4.1.318.1.1.13.4.5.2.1.8ScalarairIRG2RDT2StatusSupplyAirTempUSread-onlymandatoryThe unit supply air temperature in tenths of degrees Fahrenheit.
1.3.6.1.4.1.318.1.1.13.4.5.2.1.9ScalarairIRG2RDT2StatusSupplyAirTempMetricread-onlymandatoryThe unit supply air temperature in tenths of degrees Celsius.
1.3.6.1.4.1.318.1.1.13.4.5.2.1.10ScalarairIRG2RDT2StatusReturnAirTempUSread-onlymandatoryThe unit return air temperature in tenths of degrees Fahrenheit.
1.3.6.1.4.1.318.1.1.13.4.5.2.1.11ScalarairIRG2RDT2StatusReturnAirTempMetricread-onlymandatoryThe unit return air temperature in tenths of degrees Celsius.
1.3.6.1.4.1.318.1.1.13.4.5.2.1.12ScalarairIRG2RDT2StatusSuctionTempUSread-onlymandatoryThe unit suction temperature in tenths of degrees Fahrenheit.
1.3.6.1.4.1.318.1.1.13.4.5.2.1.13ScalarairIRG2RDT2StatusSuctionTempMetricread-onlymandatoryThe unit suction temperature in tenths of degrees Celsius.
1.3.6.1.4.1.318.1.1.13.4.5.2.1.14ScalarairIRG2RDT2StatusSuperheatTempUSread-onlymandatoryThe unit superheat temperature in tenths of degrees Fahrenheit.
1.3.6.1.4.1.318.1.1.13.4.5.2.1.15ScalarairIRG2RDT2StatusSuperheatTempMetricread-onlymandatoryThe unit superheat temperature in tenths of degrees Celsius.
1.3.6.1.4.1.318.1.1.13.4.5.2.1.16ScalarairIRG2RDT2StatusFilterDPUSread-onlymandatoryThe unit air filter differential pressure in hundredths of inches of water.
1.3.6.1.4.1.318.1.1.13.4.5.2.1.17ScalarairIRG2RDT2StatusFilterDPMetricread-onlymandatoryThe unit air filter differential pressure in pascals (Pa).
1.3.6.1.4.1.318.1.1.13.4.5.2.1.18ScalarairIRG2RDT2StatusSuctionPressureUSread-onlymandatoryUnit suction pressure in pounds per square inch (PSI).
1.3.6.1.4.1.318.1.1.13.4.5.2.1.19ScalarairIRG2RDT2StatusSuctionPressureMetricread-onlymandatoryUnit suction pressure in kiloPascals (kPa).
1.3.6.1.4.1.318.1.1.13.4.5.2.1.20ScalarairIRG2RDT2StatusDischargePressureUSread-onlymandatoryUnit discharge pressure in pounds per square inch (PSI).
1.3.6.1.4.1.318.1.1.13.4.5.2.1.21ScalarairIRG2RDT2StatusDischargePressureMetricread-onlymandatoryUnit discharge pressure in kiloPascals (kPa).
1.3.6.1.4.1.318.1.1.13.4.5.2.1.22ScalarairIRG2RDT2StatusEvaporatorFanSpeedread-onlymandatoryThe unit average evaporator fan speed in tenths of percent.
1.3.6.1.4.1.318.1.1.13.4.5.2.1.23ScalarairIRG2RDT2StatusInputStateread-onlymandatoryThe state of the input contact.
1.3.6.1.4.1.318.1.1.13.4.5.2.1.24ScalarairIRG2RDT2StatusOutputStateread-onlymandatoryThe state of the output relay.
1.3.6.1.4.1.318.1.1.13.4.5.2.1.25ScalarairIRG2RDT2StatusOHEInputStateread-onlymandatoryThe state of the outside heat exchanger(OHE) input contact.
1.3.6.1.4.1.318.1.1.13.4.5.2.1.26ScalarairIRG2RDT2StatusOHEOutputStateread-onlymandatoryThe state of the outside heat exchanger(OHE) output relay.
1.3.6.1.4.1.318.1.1.13.4.5.2.1.27ScalarairIRG2RDT2StatusCompressorread-onlymandatoryThe state (off/on) of the compressor.
1.3.6.1.4.1.318.1.1.13.4.5.2.1.28ScalarairIRG2RDT2StatusFluidValvePosread-onlymandatoryThe position of the fluid valve in percent. This OID is only valid when airIRG2RDT2ConfigUnitType indicates fluidCooled(1).
1.3.6.1.4.1.318.1.1.13.4.5.2.1.29ScalarairIRG2RDT2StatusHotGasBypassValvePosread-onlymandatoryThe position of the hot gas bypass valve in hundredths of percent.
1.3.6.1.4.1.318.1.1.13.4.5.2.1.30ScalarairIRG2RDT2StatusLeakSensorread-onlymandatoryThe state (no-leak/leak) of the leak sensor.
1.3.6.1.4.1.318.1.1.13.4.5.2.2NodeairIRG2RDT2RunHours
1.3.6.1.4.1.318.1.1.13.4.5.2.2.1ScalarairIRG2RDT2RunHoursAirFilterread-onlymandatoryUnit air filter run hours.
1.3.6.1.4.1.318.1.1.13.4.5.2.2.2ScalarairIRG2RDT2RunHoursCondensatePumpread-onlymandatoryUnit condensate pump run hours.
1.3.6.1.4.1.318.1.1.13.4.5.2.2.3ScalarairIRG2RDT2RunHoursCompressorread-onlymandatoryUnit compressor run hours.
1.3.6.1.4.1.318.1.1.13.4.5.2.2.4ScalarairIRG2RDT2RunHoursFanPSTableSizeread-onlymandatoryThe number of entries in the run hour fan power supply table (airIRG2RDT2RunHoursFanPSTable).
1.3.6.1.4.1.318.1.1.13.4.5.2.2.5TableairIRG2RDT2RunHoursFanPSTablenot-accessiblemandatoryAllows for getting run hour information from each power supply.
1.3.6.1.4.1.318.1.1.13.4.5.2.2.5.1RowairIRG2RDT2RunHoursFanPSEntrynot-accessiblemandatoryThe run hours fan power supply table entry.
1.3.6.1.4.1.318.1.1.13.4.5.2.2.5.1.1ColumnairIRG2RDT2RunHoursFanPSIndexread-onlymandatoryIndex of run hours fan power supply table.
1.3.6.1.4.1.318.1.1.13.4.5.2.2.5.1.2ColumnairIRG2RDT2RunHoursFanPSHoursread-onlymandatoryFan power supply run time in hours.
1.3.6.1.4.1.318.1.1.13.4.5.2.2.5.1.3ColumnairIRG2RDT2RunHoursFanPSPositionread-onlymandatoryPosition of fan power supply within the unit.
1.3.6.1.4.1.318.1.1.13.4.5.2.2.6ScalarairIRG2RDT2RunHoursEvapFanTableSizeread-onlymandatoryThe number of entries in the run hour evaporator fan table (airIRG2RDT2RunHoursEvapFanTable).
1.3.6.1.4.1.318.1.1.13.4.5.2.2.7TableairIRG2RDT2RunHoursEvapFanTablenot-accessiblemandatoryAllows for getting information from each evaporator fan run hour in the system.
1.3.6.1.4.1.318.1.1.13.4.5.2.2.7.1RowairIRG2RDT2RunHoursEvapFanEntrynot-accessiblemandatoryAllows for getting information from each evaporator fan run hour in the system.
1.3.6.1.4.1.318.1.1.13.4.5.2.2.7.1.1ColumnairIRG2RDT2RunHoursEvapFanIndexread-onlymandatoryIndex of run hours evaporator fan table.
1.3.6.1.4.1.318.1.1.13.4.5.2.2.7.1.2ColumnairIRG2RDT2RunHoursEvapFanHoursread-onlymandatoryEvaporator fan run time in hours.
1.3.6.1.4.1.318.1.1.13.4.5.2.2.8ScalarairIRG2RDT2RunHoursUnitread-onlymandatoryUnit run time in hours.
1.3.6.1.4.1.318.1.1.13.4.5.2.3NodeairIRG2RDT2ServiceIntervals
1.3.6.1.4.1.318.1.1.13.4.5.2.3.1ScalarairIRG2RDT2ServiceIntervalsAirFilterread-writemandatoryAir filter service interval in weeks.
1.3.6.1.4.1.318.1.1.13.4.5.2.3.2ScalarairIRG2RDT2ServiceIntervalsAirFilterAlarmread-writemandatoryThe air filter service interval alarm enable/disable.
1.3.6.1.4.1.318.1.1.13.4.5.2.4NodeairIRG2RDT2Thresholds
1.3.6.1.4.1.318.1.1.13.4.5.2.4.1ScalarairIRG2RDT2ThresholdsRackInletHighTempUSread-writemandatoryUnit rack inlet air high temperature threshold in tenths of degrees Fahrenheit.
1.3.6.1.4.1.318.1.1.13.4.5.2.4.2ScalarairIRG2RDT2ThresholdsRackInletHighTempMetricread-writemandatoryUnit rack inlet air high temperature threshold in tenths of degrees Celsius.
1.3.6.1.4.1.318.1.1.13.4.5.2.4.3ScalarairIRG2RDT2ThresholdsSupplyAirHighTempUSread-writemandatoryUnit supply air high temperature threshold in tenths of degrees Fahrenheit.
1.3.6.1.4.1.318.1.1.13.4.5.2.4.4ScalarairIRG2RDT2ThresholdsSupplyAirHighTempMetricread-writemandatoryUnit supply air high temperature threshold in tenths of degrees Celsius.
1.3.6.1.4.1.318.1.1.13.4.5.2.4.5ScalarairIRG2RDT2ThresholdsReturnAirHighTempUSread-writemandatoryUnit return air high temperature threshold in tenths of degrees Fahrenheit.
1.3.6.1.4.1.318.1.1.13.4.5.2.4.6ScalarairIRG2RDT2ThresholdsReturnAirHighTempMetricread-writemandatoryUnit return air high temperature threshold in tenths of degrees Celsius.
1.3.6.1.4.1.318.1.1.13.4.5.2.5NodeairIRG2RDT2Setpoints
1.3.6.1.4.1.318.1.1.13.4.5.2.6NodeairIRG2RDT2Config
1.3.6.1.4.1.318.1.1.13.4.5.2.6.1ScalarairIRG2RDT2ConfigUnitTyperead-onlymandatoryThe type of the unit.
1.3.6.1.4.1.318.1.1.13.4.5.2.6.2ScalarairIRG2RDT2ConfigStartupDelayread-writemandatoryThe startup delay in seconds.
1.3.6.1.4.1.318.1.1.13.4.5.2.6.3ScalarairIRG2RDT2ConfigIdleOnLeakDetectread-writemandatoryThe idle on leak options setting.
1.3.6.1.4.1.318.1.1.13.4.5.2.6.4ScalarairIRG2RDT2ConfigInputNormalStateread-writemandatoryThe normal state of the input contact.
1.3.6.1.4.1.318.1.1.13.4.5.2.6.5ScalarairIRG2RDT2ConfigOutputNormalStateread-writemandatoryThe normal state of the output relay.
1.3.6.1.4.1.318.1.1.13.4.5.2.6.6ScalarairIRG2RDT2ConfigOutputSourceread-writemandatoryThe source of output relay change.
1.3.6.1.4.1.318.1.1.13.4.5.2.6.7ScalarairIRG2RDT2ConfigOHEInputNormalStateread-writemandatoryThe normal state of the outside heat exchanger(OHE) input relay.
1.3.6.1.4.1.318.1.1.13.4.5.2.6.8ScalarairIRG2RDT2ConfigUnitRoleOverrideread-writemandatoryWhen this OID value is (1) automatic, the system determines which units are used as primary units and which units are used as backups. When this OID value is (…
1.3.6.1.4.1.318.1.1.13.4.5.2.6.9ScalarairIRG2RDT2ConfigUnitIdleOnCoolFailread-writemandatoryWhen this OID value is (2) yes, the unit idles if it detects that it is blowing warm air into the cold aisle. The unit will attempt to restart at 5 minute inte…
1.3.6.1.4.1.318.1.1.13.4.6NodeairIRG2SC
1.3.6.1.4.1.318.1.1.13.4.7NodeairIRG2RA
1.3.6.1.4.1.318.1.1.13.5NodeairInRoom
1.3.6.1.4.1.318.1.1.13.5.1NodeairIRmIdent
1.3.6.1.4.1.318.1.1.13.5.1.1ScalarairIRmIdentNameread-writemandatoryA character string identifying the unit name.
1.3.6.1.4.1.318.1.1.13.5.1.2ScalarairIRmIdentLocationread-writemandatoryA character string identifying the unit location.
1.3.6.1.4.1.318.1.1.13.5.1.3ScalarairIRmIdentModelNumberread-onlymandatoryA character string identifying the unit model number.
1.3.6.1.4.1.318.1.1.13.5.1.4ScalarairIRmIdentSerialNumberread-onlymandatoryA character string identifying the unit serial number.
1.3.6.1.4.1.318.1.1.13.5.1.5ScalarairIRmIdentFirmwareRevisionread-onlymandatoryA character string identifying the unit firmware version.
1.3.6.1.4.1.318.1.1.13.5.1.6ScalarairIRmIdentHardwareRevisionread-onlymandatoryA character string identifying the unit controller hardware revision.
1.3.6.1.4.1.318.1.1.13.5.1.7ScalarairIRmIdentManufactureDateread-onlymandatoryA character string identifying the unit manufacture date.
1.3.6.1.4.1.318.1.1.13.5.1.8ScalarairIRmIdentSysOIDread-onlymandatoryThis OID contains an OID path to the device's top level data.
1.3.6.1.4.1.318.1.1.13.5.2NodeairIRmAlarms
1.3.6.1.4.1.318.1.1.13.5.2.1ScalarairIRmAlarmsTableSizeread-onlymandatoryThe number of active alarms in the airIRG2AlarmsTable.
1.3.6.1.4.1.318.1.1.13.5.2.2TableairIRmAlarmsTablenot-accessiblemandatoryTable of active alarms for the device.
1.3.6.1.4.1.318.1.1.13.5.2.2.1RowairIRmAlarmsEntrynot-accessiblemandatoryAlarms specification
1.3.6.1.4.1.318.1.1.13.5.2.2.1.1ColumnairIRmAlarmsIndexread-onlymandatoryAlarm index.
1.3.6.1.4.1.318.1.1.13.5.2.2.1.2ColumnairIRmAlarmsEventCoderead-onlymandatoryCode for the alarm.
1.3.6.1.4.1.318.1.1.13.5.2.2.1.3ColumnairIRmAlarmsDescriptionread-onlymandatoryDescription of the alarm.
1.3.6.1.4.1.318.1.1.13.5.3NodeairIRmPerimeter
1.3.6.1.4.1.318.1.1.13.5.3.2NodeairIRmPmCommon1
1.3.6.1.4.1.318.1.1.13.5.3.2.1ScalarairIRmPmUnitTyperead-onlymandatoryUnit type (1).
1.3.6.1.4.1.318.1.1.13.5.3.2.3ScalarairIRmPmSwVersionread-onlymandatorySoftware version (3).
1.3.6.1.4.1.318.1.1.13.5.3.2.5ScalarairIRmPmBusAddressread-onlymandatoryBus addresss of unit (5).
1.3.6.1.4.1.318.1.1.13.5.3.2.7ScalarairIRmPmControllerTyperead-onlymandatoryController type (7).
1.3.6.1.4.1.318.1.1.13.5.3.2.8ScalarairIRmPmGeneralErrorread-onlymandatoryGeneral Error (8)
1.3.6.1.4.1.318.1.1.13.5.3.2.9ScalarairIRmPmErrorOnBusread-onlymandatoryError On Bus (9)
1.3.6.1.4.1.318.1.1.13.5.3.3NodeairIRmPmCommon2
1.3.6.1.4.1.318.1.1.13.5.3.3.1ScalarairIRmPmPCStopread-onlymandatoryPC-STOP (1000)
1.3.6.1.4.1.318.1.1.13.5.3.3.2ScalarairIRmPmRemoteStopread-onlymandatoryRemote Stop (1001)
1.3.6.1.4.1.318.1.1.13.5.3.3.3ScalarairIRmPmLocalStopread-onlymandatoryLocal Stop (1002)
1.3.6.1.4.1.318.1.1.13.5.3.3.4ScalarairIRmPmTimerStopread-onlymandatoryTimer Stop (1003)
1.3.6.1.4.1.318.1.1.13.5.3.3.5ScalarairIRmPmSeqStopread-onlymandatorySeq. Stop (1004)
1.3.6.1.4.1.318.1.1.13.5.3.3.7ScalarairIRmPmRemoteUPSread-onlymandatoryRemote UPS (1006)
1.3.6.1.4.1.318.1.1.13.5.3.3.8ScalarairIRmPmLocalUPSread-onlymandatoryLocal UPS (1007)
1.3.6.1.4.1.318.1.1.13.5.3.3.11ScalarairIRmPmCommonAlarmread-onlymandatoryCommon alarm (1010).
1.3.6.1.4.1.318.1.1.13.5.3.3.12ScalarairIRmPmResetAllAlarmsread-writemandatoryReset all alarms control (1011).
1.3.6.1.4.1.318.1.1.13.5.3.3.14ScalarairIRmPmUnitOnOffread-onlymandatoryUnit running state (1013).
1.3.6.1.4.1.318.1.1.13.5.3.3.15ScalarairIRmPmMaintenanceread-onlymandatoryMaintenance necessary state (1014).
1.3.6.1.4.1.318.1.1.13.5.3.3.23ScalarairIRmPmUnitTemperatureScaleread-onlymandatoryCurrent Unit Temperature Scale (1022).
1.3.6.1.4.1.318.1.1.13.5.3.3.24ScalarairIRmPmUnitWinterModeread-onlymandatoryWinter or summer configuration mode (1023).
1.3.6.1.4.1.318.1.1.13.5.3.3.25ScalarairIRmPmDayNightModeread-onlymandatoryDay or night configuration mode (1024).
1.3.6.1.4.1.318.1.1.13.5.3.4NodeairIRmPmCommon3
1.3.6.1.4.1.318.1.1.13.5.3.4.1ScalarairIRmPmLastMaintenanceYearread-onlymandatoryLast maintenance year (1160).
1.3.6.1.4.1.318.1.1.13.5.3.4.2ScalarairIRmPmLastMaintenanceMonthread-onlymandatoryLast maintenance month (1161).
1.3.6.1.4.1.318.1.1.13.5.3.4.3ScalarairIRmPmLastMaintenanceDayread-onlymandatoryLast maintenance day (1162).
1.3.6.1.4.1.318.1.1.13.5.3.4.4ScalarairIRmPmUnitMaintenanceIntervalread-onlymandatoryUnit maintenance interval in months (1163).
1.3.6.1.4.1.318.1.1.13.5.3.4.5ScalarairIRmPmRuntimeUnitread-onlymandatoryRuntime unit in hours (1164).
1.3.6.1.4.1.318.1.1.13.5.3.4.6ScalarairIRmPmStoptimeUnitread-onlymandatoryUnit stoptime in hours (1165)
1.3.6.1.4.1.318.1.1.13.5.3.4.7ScalarairIRmPmRuntimeCoolingread-onlymandatoryCooling runtime in hours (1166)
1.3.6.1.4.1.318.1.1.13.5.3.4.8ScalarairIRmPmRuntimeHeatingread-onlymandatoryHeating runtime in hours (1167)
1.3.6.1.4.1.318.1.1.13.5.3.4.9ScalarairIRmPmRuntimeHumidificationread-onlymandatoryHumidification runtime in hours (1168)
1.3.6.1.4.1.318.1.1.13.5.3.4.10ScalarairIRmPmRuntimeDehumidificationread-onlymandatoryDehumidification runtime in hours (1169)
1.3.6.1.4.1.318.1.1.13.5.3.4.11NodeairIRmPmUnitTemperature
1.3.6.1.4.1.318.1.1.13.5.3.4.11.1ScalarairIRmPmUnitTemperatureCread-onlymandatoryUnit temperature in tenths of degrees Celsius (1170).
1.3.6.1.4.1.318.1.1.13.5.3.4.11.2ScalarairIRmPmUnitTemperatureFread-onlymandatoryUnit temperature in tenths of degrees Fahrenheit (1170).
1.3.6.1.4.1.318.1.1.13.5.3.4.12ScalarairIRmPmUnitHumidityread-onlymandatoryUnit humidity in tenths of %RH (1171).
1.3.6.1.4.1.318.1.1.13.5.3.4.14NodeairIRmPmSetpointTemperatureDay
1.3.6.1.4.1.318.1.1.13.5.3.4.14.1ScalarairIRmPmSetpointTemperatureDayCread-writemandatorySetpoint daytime temperature in tenths of degrees Celsius (1173).
1.3.6.1.4.1.318.1.1.13.5.3.4.14.2ScalarairIRmPmSetpointTemperatureDayFread-writemandatorySetpoint daytime temperature in tenths of degrees Fahrenheit (1173).
1.3.6.1.4.1.318.1.1.13.5.3.4.15NodeairIRmPmSetpointTemperatureNight
1.3.6.1.4.1.318.1.1.13.5.3.4.15.1ScalarairIRmPmSetpointTemperatureNightCread-writemandatorySetpoint nighttime temperature in tenths of degrees Celsius (1174).
1.3.6.1.4.1.318.1.1.13.5.3.4.15.2ScalarairIRmPmSetpointTemperatureNightFread-writemandatorySetpoint nighttime temperature in tenths of degrees Fahrenheit (1174).
1.3.6.1.4.1.318.1.1.13.5.3.4.17ScalarairIRmPmSetpointHumidityread-writemandatorySetpoint humidity in tenths of %RH (1176).
1.3.6.1.4.1.318.1.1.13.5.3.4.24ScalarairIRmPmUnitControlTyperead-onlymandatoryCurrent unit control type (1183).
1.3.6.1.4.1.318.1.1.13.5.3.4.29NodeairIRmPmWinterModeStartTemp
1.3.6.1.4.1.318.1.1.13.5.3.4.29.1ScalarairIRmPmWinterModeStartTempCread-onlymandatoryWinter mode start temperature in tenths of degrees Celsius (1188).
1.3.6.1.4.1.318.1.1.13.5.3.4.29.2ScalarairIRmPmWinterModeStartTempFread-onlymandatoryWinter mode start temperature in tenths of degrees Fahrenheit (1188).
1.3.6.1.4.1.318.1.1.13.5.3.4.30NodeairIRmPmWinterModeHysteresis
1.3.6.1.4.1.318.1.1.13.5.3.4.30.1ScalarairIRmPmWinterModeHysteresisKread-onlymandatoryWinter mode hysteresis in tenths of Kelvins (1189)
1.3.6.1.4.1.318.1.1.13.5.3.4.30.2ScalarairIRmPmWinterModeHysteresisFread-onlymandatoryWinter mode hysteresis in tenths of degrees Fahrenheit (1189)
1.3.6.1.4.1.318.1.1.13.5.3.4.32NodeairIRmPmWaterTemperature
1.3.6.1.4.1.318.1.1.13.5.3.4.32.1ScalarairIRmPmWaterTemperatureCread-onlymandatoryWater temperature in tenths of degrees Celsius (1191).
1.3.6.1.4.1.318.1.1.13.5.3.4.32.2ScalarairIRmPmWaterTemperatureFread-onlymandatoryWater temperature in tenths of degrees Fahrenheit (1191).
1.3.6.1.4.1.318.1.1.13.5.3.4.33NodeairIRmPmReturnAirTemperature
1.3.6.1.4.1.318.1.1.13.5.3.4.33.1ScalarairIRmPmReturnAirTemperatureCread-onlymandatoryReturn air temperature in tenths of degrees Celsius (1192).
1.3.6.1.4.1.318.1.1.13.5.3.4.33.2ScalarairIRmPmReturnAirTemperatureFread-onlymandatoryReturn air temperature in tenths of degrees Fahrenheit (1192).
1.3.6.1.4.1.318.1.1.13.5.3.4.34NodeairIRmPmSupplyAirTemperature
1.3.6.1.4.1.318.1.1.13.5.3.4.34.1ScalarairIRmPmSupplyAirTemperatureCread-onlymandatorySupply air temperature in tenths of degrees Celsius (1193).
1.3.6.1.4.1.318.1.1.13.5.3.4.34.2ScalarairIRmPmSupplyAirTemperatureFread-onlymandatorySupply air temperature in tenths of degrees Fahrenheit (1193).
1.3.6.1.4.1.318.1.1.13.5.3.4.35ScalarairIRmPmReturnAirHumidityread-onlymandatoryReturn air humidity in tenths of %RH (1194).
1.3.6.1.4.1.318.1.1.13.5.3.4.36ScalarairIRmPmSupplyAirHumidityread-onlymandatorySupply air humidity in tenths of %RH (1195).
1.3.6.1.4.1.318.1.1.13.5.3.4.37NodeairIRmPmOutsideAirTemperature
1.3.6.1.4.1.318.1.1.13.5.3.4.37.1ScalarairIRmPmOutsideAirTemperatureCread-onlymandatoryOutside air temperature in tenths of degrees Celsius (1196)
1.3.6.1.4.1.318.1.1.13.5.3.4.37.2ScalarairIRmPmOutsideAirTemperatureFread-onlymandatoryOutside air temperature in tenths of degrees Fahrenheit (1196)
1.3.6.1.4.1.318.1.1.13.5.3.4.38ScalarairIRmPmOutsideAirHumidityread-onlymandatoryOutside air humidity in tenths of percent relative humidity (1197)
1.3.6.1.4.1.318.1.1.13.5.3.4.39ScalarairIRmPmCoolingPriorityread-writemandatoryCooling priority (1198).
1.3.6.1.4.1.318.1.1.13.5.3.4.43NodeairIRmPmWaterTemperature2
1.3.6.1.4.1.318.1.1.13.5.3.4.43.1ScalarairIRmPmWaterTemperature2Cread-onlymandatoryWater temperature 2 in tenths of degrees Celsius (1202).
1.3.6.1.4.1.318.1.1.13.5.3.4.43.2ScalarairIRmPmWaterTemperature2Fread-onlymandatoryWater temperature 2 in tenths of degrees Fahrenheit (1202).
1.3.6.1.4.1.318.1.1.13.5.3.4.44ScalarairIRmPmRuntimeFreeCoolingread-onlymandatoryFreecooling runtime in hours (1203)
1.3.6.1.4.1.318.1.1.13.5.3.4.45ScalarairIRmPmRuntimeMixedModeFreeCoolingread-onlymandatoryMixed mode freecooling runtime in hours (1203)
1.3.6.1.4.1.318.1.1.13.5.3.5NodeairIRmPmCommon4
1.3.6.1.4.1.318.1.1.13.5.3.5.4ScalarairIRmPmNumberOfCompressorsread-onlymandatoryNumber of compressors (1761)
1.3.6.1.4.1.318.1.1.13.5.3.5.5ScalarairIRmPmNumberOfSuctionValvesread-onlymandatoryNumber of suction valves (1762)
1.3.6.1.4.1.318.1.1.13.5.3.5.6ScalarairIRmPmNumberOfDryCoolersread-onlymandatoryNumber of drycoolers (1763)
1.3.6.1.4.1.318.1.1.13.5.3.5.7ScalarairIRmPmNumberOfPumpsread-onlymandatoryNumber of pumps (1764)
1.3.6.1.4.1.318.1.1.13.5.3.5.8ScalarairIRmPmNumberOfElectricHeatersread-onlymandatoryNumber of electric heaters (1765)
1.3.6.1.4.1.318.1.1.13.5.3.5.9ScalarairIRmPmNumberOfHumidifiersread-onlymandatoryNumber of humidifiers (1766)
1.3.6.1.4.1.318.1.1.13.5.3.5.10ScalarairIRmPmNumberOfFansread-onlymandatoryNumber of fans (1767)
1.3.6.1.4.1.318.1.1.13.5.3.5.11ScalarairIRmPmNumberOfLouversread-onlymandatoryNumber of louvers (1768)
1.3.6.1.4.1.318.1.1.13.5.3.5.12ScalarairIRmPmNumberOfSensorsread-onlymandatoryNumber of sensors (1769)
1.3.6.1.4.1.318.1.1.13.5.3.5.13ScalarairIRmPmNumberOfExternalAlarmInputsread-onlymandatoryNumber of external alarm inputs (1770)
1.3.6.1.4.1.318.1.1.13.5.3.5.14ScalarairIRmPmNumberOfGECWValvesread-onlymandatoryNumber of GE/CW valves (1771)
1.3.6.1.4.1.318.1.1.13.5.3.5.15ScalarairIRmPmNumberOfHotGasReheatread-onlymandatoryNumber of hot gas reheaters (1772)
1.3.6.1.4.1.318.1.1.13.5.3.5.16ScalarairIRmPmNumberOfPWWReheatread-onlymandatoryNumber of PWW reheaters (1773)
1.3.6.1.4.1.318.1.1.13.5.3.5.17ScalarairIRmPmNumberOfDehumidifiersread-onlymandatoryNumber of dehumidifiers (1774)
1.3.6.1.4.1.318.1.1.13.5.3.6NodeairIRmPmCommon5
1.3.6.1.4.1.318.1.1.13.5.3.6.1NodeairIRmPmUnitEvaporationTemperature1
1.3.6.1.4.1.318.1.1.13.5.3.6.1.1ScalarairIRmPmUnitEvaporationTemperature1Cread-onlymandatoryUnit evaporation temperature 1 in tenths of degrees Celsius (2232)
1.3.6.1.4.1.318.1.1.13.5.3.6.1.2ScalarairIRmPmUnitEvaporationTemperature1Fread-onlymandatoryUnit evaporation temperature 1 in tenths of degrees Fahrenheit (2232)
1.3.6.1.4.1.318.1.1.13.5.3.6.2ScalarairIRmPmUnitEvaporationPressure1read-onlymandatoryUnit evaporation pressure 1 in tenths of Bars (2233)
1.3.6.1.4.1.318.1.1.13.5.3.6.3NodeairIRmPmUnitCondensationTemperature1
1.3.6.1.4.1.318.1.1.13.5.3.6.3.1ScalarairIRmPmUnitCondensationTemperature1Cread-onlymandatoryUnit condensation temperature 1 in tenths of degrees Celsius (2234)
1.3.6.1.4.1.318.1.1.13.5.3.6.3.2ScalarairIRmPmUnitCondensationTemperature1Fread-onlymandatoryUnit condensation temperature 1 in tenths of degrees Fahrenheit (2234)
1.3.6.1.4.1.318.1.1.13.5.3.6.4ScalarairIRmPmUnitCondensationPressure1read-onlymandatoryUnit condensation pressure 1 in tenths of Bars (2235)
1.3.6.1.4.1.318.1.1.13.5.3.6.8NodeairIRmPmMaxLimitReturnAirTemperature
1.3.6.1.4.1.318.1.1.13.5.3.6.8.1ScalarairIRmPmMaxLimitReturnAirTemperatureCread-writemandatoryMaximum limit return air temperature in tenths of degrees Celsius (2239).
1.3.6.1.4.1.318.1.1.13.5.3.6.8.2ScalarairIRmPmMaxLimitReturnAirTemperatureFread-writemandatoryMaximum limit return air temperature in tenths of degrees Fahrenheit (2239).
1.3.6.1.4.1.318.1.1.13.5.3.6.9NodeairIRmPmMinLimitReturnAirTemperature
1.3.6.1.4.1.318.1.1.13.5.3.6.9.1ScalarairIRmPmMinLimitReturnAirTemperatureCread-writemandatoryMinimum limit return air temperature in tenths of degrees Celsius (2240).
1.3.6.1.4.1.318.1.1.13.5.3.6.9.2ScalarairIRmPmMinLimitReturnAirTemperatureFread-writemandatoryMinimum limit return air temperature in tenths of degrees Fahrenheit (2240).
1.3.6.1.4.1.318.1.1.13.5.3.6.10NodeairIRmPmMaxLimitSupplyAirTemperature
1.3.6.1.4.1.318.1.1.13.5.3.6.10.1ScalarairIRmPmMaxLimitSupplyAirTemperatureCread-writemandatoryMaximum limit supply air temperature in tenths of degrees Celsius (2241).
1.3.6.1.4.1.318.1.1.13.5.3.6.10.2ScalarairIRmPmMaxLimitSupplyAirTemperatureFread-writemandatoryMaximum limit supply air temperature in tenths of degrees Fahrenheit (2241).
1.3.6.1.4.1.318.1.1.13.5.3.6.11NodeairIRmPmMinLimitSupplyAirTemperature
1.3.6.1.4.1.318.1.1.13.5.3.6.11.1ScalarairIRmPmMinLimitSupplyAirTemperatureCread-writemandatoryMinimum limit supply air temperature in tenths of degrees Celsius (2242).
1.3.6.1.4.1.318.1.1.13.5.3.6.11.2ScalarairIRmPmMinLimitSupplyAirTemperatureFread-writemandatoryMinimum limit supply air temperature in tenths of degrees Fahrenheit (2242).
1.3.6.1.4.1.318.1.1.13.5.3.6.12NodeairIRmPmMaxLimitWaterTemperature
1.3.6.1.4.1.318.1.1.13.5.3.6.12.1ScalarairIRmPmMaxLimitWaterTemperatureCread-writemandatoryMaximum limit water temperature in tenths of degrees Celsius (2243).
1.3.6.1.4.1.318.1.1.13.5.3.6.12.2ScalarairIRmPmMaxLimitWaterTemperatureFread-writemandatoryMaximum limit water temperature in tenths of degrees Fahrenheit (2243).
1.3.6.1.4.1.318.1.1.13.5.3.6.13NodeairIRmPmMinLimitWaterTemperature
1.3.6.1.4.1.318.1.1.13.5.3.6.13.1ScalarairIRmPmMinLimitWaterTemperatureCread-writemandatoryMinimum limit water temperature in tenths of degrees Celsius (2244).
1.3.6.1.4.1.318.1.1.13.5.3.6.13.2ScalarairIRmPmMinLimitWaterTemperatureFread-writemandatoryMinimum limit water temperature in tenths of degrees Fahrenheit (2244).
1.3.6.1.4.1.318.1.1.13.5.3.6.14ScalarairIRmPmMaxLimitReturnAirHumidityread-writemandatoryMaximum limit return air humidity in tenths of %RH (2245).
1.3.6.1.4.1.318.1.1.13.5.3.6.15ScalarairIRmPmMinLimitReturnAirHumidityread-writemandatoryMinimum limit return air humidity in tenths of %RH (2246).
1.3.6.1.4.1.318.1.1.13.5.3.6.16ScalarairIRmPmMaxLimitSupplyAirHumidityread-writemandatoryMaximum limit supply air humidity in tenths of %RH (2247).
1.3.6.1.4.1.318.1.1.13.5.3.6.17ScalarairIRmPmMinLimitSupplyAirHumidityread-writemandatoryMinimum limit supply air humidity in tenths of %RH (2248).
1.3.6.1.4.1.318.1.1.13.5.3.6.18ScalarairIRmPmLowPressureWinterDelayread-onlymandatoryWinter mode low pressure delay in seconds (2249)
1.3.6.1.4.1.318.1.1.13.5.3.6.19ScalarairIRmPmUnitCondensationPressure2read-onlymandatoryUnit condensation pressure 2 in tenths of Bars (2250)
1.3.6.1.4.1.318.1.1.13.5.3.6.20ScalarairIRmPmUnitOverloadSwitchread-onlymandatoryUnit overload switch setting in tenths of Kelvins (2251)
1.3.6.1.4.1.318.1.1.13.5.3.6.41NodeairIRmPmUnitCondensationTemperature2
1.3.6.1.4.1.318.1.1.13.5.3.6.41.1ScalarairIRmPmUnitCondensationTemperature2Cread-onlymandatoryUnit condensation temperature 2 in tenths of degrees Celsius (2272)
1.3.6.1.4.1.318.1.1.13.5.3.6.41.2ScalarairIRmPmUnitCondensationTemperature2Fread-onlymandatoryUnit condensation temperature 2 in tenths of degrees Fahrenheit (2272)
1.3.6.1.4.1.318.1.1.13.5.3.6.42ScalarairIRmPmUnitEvaporationPressure2read-onlymandatoryUnit evaporation pressure 2 in tenths of Bars (2273)
1.3.6.1.4.1.318.1.1.13.5.3.6.43NodeairIRmPmUnitEvaporationTemperature2
1.3.6.1.4.1.318.1.1.13.5.3.6.43.1ScalarairIRmPmUnitEvaporationTemperature2Cread-onlymandatoryUnit evaporation temperature 2 in tenths of degrees Celsius (2274)
1.3.6.1.4.1.318.1.1.13.5.3.6.43.2ScalarairIRmPmUnitEvaporationTemperature2Fread-onlymandatoryUnit evaporation temperature 2 in tenths of degrees Fahrenheit (2274)
1.3.6.1.4.1.318.1.1.13.5.3.7NodeairIRmPmCompressor1
1.3.6.1.4.1.318.1.1.13.5.3.7.2ScalarairIRmPmCmp1ManOperationActiveread-onlymandatoryCompressor 1 manual operation active (4401)
1.3.6.1.4.1.318.1.1.13.5.3.7.3ScalarairIRmPmCmp1ManOperationStateread-onlymandatoryCompressor 1 manual operation state (4402)
1.3.6.1.4.1.318.1.1.13.5.3.7.4ScalarairIRmPmCmp1Runningread-onlymandatoryCompressor 1 running (4403)
1.3.6.1.4.1.318.1.1.13.5.3.7.17NodeairIRmPmCmp1StartTempSummer
1.3.6.1.4.1.318.1.1.13.5.3.7.17.1ScalarairIRmPmCmp1StartTempSummerKread-writemandatoryCompressor 1 summer mode start temperature in tenths of Kelvins (4416)
1.3.6.1.4.1.318.1.1.13.5.3.7.17.2ScalarairIRmPmCmp1StartTempSummerFread-writemandatoryCompressor 1 summer mode start temperature in tenths of degrees Fahrenheit (4416)
1.3.6.1.4.1.318.1.1.13.5.3.7.18NodeairIRmPmCmp1HysteresisSummer
1.3.6.1.4.1.318.1.1.13.5.3.7.18.1ScalarairIRmPmCmp1HysteresisSummerKread-writemandatoryCompressor 1 summer mode hysteresis setting in tenths of Kelvins (4417)
1.3.6.1.4.1.318.1.1.13.5.3.7.18.2ScalarairIRmPmCmp1HysteresisSummerFread-writemandatoryCompressor 1 summer mode hysteresis setting in tenths of Fahrenheit (4417)
1.3.6.1.4.1.318.1.1.13.5.3.7.19NodeairIRmPmCmp1StartTempWinter
1.3.6.1.4.1.318.1.1.13.5.3.7.19.1ScalarairIRmPmCmp1StartTempWinterKread-writemandatoryCompressor 1 winter mode start temperature in tenths of Kelvins (4418)
1.3.6.1.4.1.318.1.1.13.5.3.7.19.2ScalarairIRmPmCmp1StartTempWinterFread-writemandatoryCompressor 1 winter mode start temperature in tenths of degrees Fahrenheit (4418)
1.3.6.1.4.1.318.1.1.13.5.3.7.20NodeairIRmPmCmp1HysteresisWinter
1.3.6.1.4.1.318.1.1.13.5.3.7.20.1ScalarairIRmPmCmp1HysteresisWinterKread-writemandatoryCompressor 1 Winter mode hysteresis setting in tenths of Kelvins (4419)
1.3.6.1.4.1.318.1.1.13.5.3.7.20.2ScalarairIRmPmCmp1HysteresisWinterFread-writemandatoryCompressor 1 Winter mode hysteresis setting in tenths of Fahrenheit (4419)
1.3.6.1.4.1.318.1.1.13.5.3.7.29ScalarairIRmPmCmp1Runtimeread-onlymandatoryCompressor 1 runtime in hours (4428)
1.3.6.1.4.1.318.1.1.13.5.3.8NodeairIRmPmCompressor2
1.3.6.1.4.1.318.1.1.13.5.3.8.2ScalarairIRmPmCmp2ManOperationActiveread-onlymandatoryCompressor 2 manual operation active (4501)
1.3.6.1.4.1.318.1.1.13.5.3.8.3ScalarairIRmPmCmp2ManOperationStateread-onlymandatoryCompressor 2 manual operation state (4502)
1.3.6.1.4.1.318.1.1.13.5.3.8.4ScalarairIRmPmCmp2Runningread-onlymandatoryCompressor 2 running (4503)
1.3.6.1.4.1.318.1.1.13.5.3.8.17NodeairIRmPmCmp2StartTempSummer
1.3.6.1.4.1.318.1.1.13.5.3.8.17.1ScalarairIRmPmCmp2StartTempSummerKread-writemandatoryCompressor 2 summer mode start temperature in tenths of Kelvins (4516)
1.3.6.1.4.1.318.1.1.13.5.3.8.17.2ScalarairIRmPmCmp2StartTempSummerFread-writemandatoryCompressor 2 summer mode start temperature in tenths of degrees Fahrenheit (4516)
1.3.6.1.4.1.318.1.1.13.5.3.8.18NodeairIRmPmCmp2HysteresisSummer
1.3.6.1.4.1.318.1.1.13.5.3.8.18.1ScalarairIRmPmCmp2HysteresisSummerKread-writemandatoryCompressor 2 summer mode hysteresis setting in tenths of Kelvins (4517)
1.3.6.1.4.1.318.1.1.13.5.3.8.18.2ScalarairIRmPmCmp2HysteresisSummerFread-writemandatoryCompressor 2 summer mode hysteresis setting in tenths of Fahrenheit (4517)
1.3.6.1.4.1.318.1.1.13.5.3.8.19NodeairIRmPmCmp2StartTempWinter
1.3.6.1.4.1.318.1.1.13.5.3.8.19.1ScalarairIRmPmCmp2StartTempWinterKread-writemandatoryCompressor 2 winter mode start temperature in tenths of Kelvins (4518)
1.3.6.1.4.1.318.1.1.13.5.3.8.19.2ScalarairIRmPmCmp2StartTempWinterFread-writemandatoryCompressor 2 winter mode start temperature in tenths of degrees Fahrenheit (4518)
1.3.6.1.4.1.318.1.1.13.5.3.8.20NodeairIRmPmCmp2HysteresisWinter
1.3.6.1.4.1.318.1.1.13.5.3.8.20.1ScalarairIRmPmCmp2HysteresisWinterKread-writemandatoryCompressor 2 Winter mode hysteresis setting in tenths of Kelvins (4519)
1.3.6.1.4.1.318.1.1.13.5.3.8.20.2ScalarairIRmPmCmp2HysteresisWinterFread-writemandatoryCompressor 2 Winter mode hysteresis setting in tenths of Fahrenheit (4519)
1.3.6.1.4.1.318.1.1.13.5.3.8.29ScalarairIRmPmCmp2Runtimeread-onlymandatoryCompressor 2 runtime in hours (4528)
1.3.6.1.4.1.318.1.1.13.5.3.9NodeairIRmPmSuctionValve1
1.3.6.1.4.1.318.1.1.13.5.3.10NodeairIRmPmSuctionValve2
1.3.6.1.4.1.318.1.1.13.5.3.11NodeairIRmPmEheating1
1.3.6.1.4.1.318.1.1.13.5.3.11.2ScalarairIRmPmEheating1ManOpEnableread-onlymandatoryElectric heater #1 manual operation enable (4801)
1.3.6.1.4.1.318.1.1.13.5.3.11.4ScalarairIRmPmEheating1Runningread-onlymandatoryElectric heater #1 running state (4803)
1.3.6.1.4.1.318.1.1.13.5.3.11.5ScalarairIRmPmEheating1ManOpRunningread-onlymandatoryElectric heater #1 running in manual operation mode (4804)
1.3.6.1.4.1.318.1.1.13.5.3.11.9ScalarairIRmPmEheating1Typeread-onlymandatoryElectric heater #1 type (4808)
1.3.6.1.4.1.318.1.1.13.5.3.11.10NodeairIRmPmEheating1StartTemperature
1.3.6.1.4.1.318.1.1.13.5.3.11.10.1ScalarairIRmPmEheating1StartTemperatureKread-writemandatoryElectric heater #1 start temperature in tenths of Kelvins (4809)
1.3.6.1.4.1.318.1.1.13.5.3.11.10.2ScalarairIRmPmEheating1StartTemperatureFread-writemandatoryElectric heater #1 start temperature in tenths of degrees Fahrenheit (4809)
1.3.6.1.4.1.318.1.1.13.5.3.11.11NodeairIRmPmEheating1Hysteresis
1.3.6.1.4.1.318.1.1.13.5.3.11.11.1ScalarairIRmPmEheating1HysteresisKread-writemandatoryElectric heater #1 hysteresis in tenths of Kelvins (4810)
1.3.6.1.4.1.318.1.1.13.5.3.11.11.2ScalarairIRmPmEheating1HysteresisFread-writemandatoryElectric heater #1 hysteresis in tenths of degrees Fahrenheit (4810)
1.3.6.1.4.1.318.1.1.13.5.3.11.17ScalarairIRmPmEheating1Runtimeread-onlymandatoryElectric heater #1 runtime in hours (4816)
1.3.6.1.4.1.318.1.1.13.5.3.12NodeairIRmPmEheating2
1.3.6.1.4.1.318.1.1.13.5.3.12.2ScalarairIRmPmEheating2ManOpEnableread-onlymandatoryElectric heater #2 manual operation enable (4901)
1.3.6.1.4.1.318.1.1.13.5.3.12.4ScalarairIRmPmEheating2Runningread-onlymandatoryElectric heater #2 running state (4903)
1.3.6.1.4.1.318.1.1.13.5.3.12.5ScalarairIRmPmEheating2ManOpRunningread-onlymandatoryElectric heater #2 running in manual operation mode (4904)
1.3.6.1.4.1.318.1.1.13.5.3.12.9ScalarairIRmPmEheating2Typeread-onlymandatoryElectric heater #2 type (4908)
1.3.6.1.4.1.318.1.1.13.5.3.12.10NodeairIRmPmEheating2StartTemperature
1.3.6.1.4.1.318.1.1.13.5.3.12.10.1ScalarairIRmPmEheating2StartTemperatureKread-writemandatoryElectric heater #2 start temperature in tenths of Kelvins (4909)
1.3.6.1.4.1.318.1.1.13.5.3.12.10.2ScalarairIRmPmEheating2StartTemperatureFread-writemandatoryElectric heater #2 start temperature in tenths of degrees Fahrenheit (4909)
1.3.6.1.4.1.318.1.1.13.5.3.12.11NodeairIRmPmEheating2Hysteresis
1.3.6.1.4.1.318.1.1.13.5.3.12.11.1ScalarairIRmPmEheating2HysteresisKread-writemandatoryElectric heater #2 hysteresis in tenths of Kelvins (4910)
1.3.6.1.4.1.318.1.1.13.5.3.12.11.2ScalarairIRmPmEheating2HysteresisFread-writemandatoryElectric heater #2 hysteresis in tenths of degrees Fahrenheit (4910)
1.3.6.1.4.1.318.1.1.13.5.3.12.17ScalarairIRmPmEheating2Runtimeread-onlymandatoryElectric heater #2 runtime in hours (4916)
1.3.6.1.4.1.318.1.1.13.5.3.13NodeairIRmPmEheating3
1.3.6.1.4.1.318.1.1.13.5.3.13.2ScalarairIRmPmEheating3ManOpEnableread-onlymandatoryElectric heater #3 manual operation enable (5001)
1.3.6.1.4.1.318.1.1.13.5.3.13.4ScalarairIRmPmEheating3Runningread-onlymandatoryElectric heater #3 running state (5003)
1.3.6.1.4.1.318.1.1.13.5.3.13.5ScalarairIRmPmEheating3ManOpRunningread-onlymandatoryElectric heater #3 running in manual operation mode (5004)
1.3.6.1.4.1.318.1.1.13.5.3.13.9ScalarairIRmPmEheating3Typeread-onlymandatoryElectric heater #3 type (5008)
1.3.6.1.4.1.318.1.1.13.5.3.13.10NodeairIRmPmEheating3StartTemperature
1.3.6.1.4.1.318.1.1.13.5.3.13.10.1ScalarairIRmPmEheating3StartTemperatureKread-writemandatoryElectric heater #3 start temperature in tenths of Kelvins (5009)
1.3.6.1.4.1.318.1.1.13.5.3.13.10.2ScalarairIRmPmEheating3StartTemperatureFread-writemandatoryElectric heater #3 start temperature in tenths of degrees Fahrenheit (5009)
1.3.6.1.4.1.318.1.1.13.5.3.13.11NodeairIRmPmEheating3Hysteresis
1.3.6.1.4.1.318.1.1.13.5.3.13.11.1ScalarairIRmPmEheating3HysteresisKread-writemandatoryElectric heater #3 hysteresis in tenths of Kelvins (5010)
1.3.6.1.4.1.318.1.1.13.5.3.13.11.2ScalarairIRmPmEheating3HysteresisFread-writemandatoryElectric heater #3 hysteresis in tenths of degrees Fahrenheit (5010)
1.3.6.1.4.1.318.1.1.13.5.3.13.17ScalarairIRmPmEheating3Runtimeread-onlymandatoryElectric heater #3 runtime in hours (5016)
1.3.6.1.4.1.318.1.1.13.5.3.14NodeairIRmPmEheating4
1.3.6.1.4.1.318.1.1.13.5.3.14.2ScalarairIRmPmEheating4ManOpEnableread-onlymandatoryElectric heater #4 manual operation enable (5101)
1.3.6.1.4.1.318.1.1.13.5.3.14.4ScalarairIRmPmEheating4Runningread-onlymandatoryElectric heater #4 running state (5103)
1.3.6.1.4.1.318.1.1.13.5.3.14.5ScalarairIRmPmEheating4ManOpRunningread-onlymandatoryElectric heater #4 running in manual operation mode (5104)
1.3.6.1.4.1.318.1.1.13.5.3.14.9ScalarairIRmPmEheating4Typeread-onlymandatoryElectric heater #4 type (5108)
1.3.6.1.4.1.318.1.1.13.5.3.14.10NodeairIRmPmEheating4StartTemperature
1.3.6.1.4.1.318.1.1.13.5.3.14.10.1ScalarairIRmPmEheating4StartTemperatureKread-writemandatoryElectric heater #4 start temperature in tenths of Kelvins (5109)
1.3.6.1.4.1.318.1.1.13.5.3.14.10.2ScalarairIRmPmEheating4StartTemperatureFread-writemandatoryElectric heater #4 start temperature in tenths of degrees Fahrenheit (5109)
1.3.6.1.4.1.318.1.1.13.5.3.14.11NodeairIRmPmEheating4Hysteresis
1.3.6.1.4.1.318.1.1.13.5.3.14.11.1ScalarairIRmPmEheating4HysteresisKread-writemandatoryElectric heater #4 hysteresis in tenths of Kelvins (5110)
1.3.6.1.4.1.318.1.1.13.5.3.14.11.2ScalarairIRmPmEheating4HysteresisFread-writemandatoryElectric heater #4 hysteresis in tenths of degrees Fahrenheit (5110)
1.3.6.1.4.1.318.1.1.13.5.3.14.17ScalarairIRmPmEheating4Runtimeread-onlymandatoryElectric heater #4 runtime in hours (5116)
1.3.6.1.4.1.318.1.1.13.5.3.15NodeairIRmPmGECWvalve
1.3.6.1.4.1.318.1.1.13.5.3.15.2ScalarairIRmPmGECWvalveManOpEnableread-onlymandatoryGE/CW valve manual operation enable (5201)
1.3.6.1.4.1.318.1.1.13.5.3.15.9NodeairIRmPmGECWvalveStartTemperature
1.3.6.1.4.1.318.1.1.13.5.3.15.9.1ScalarairIRmPmGECWvalveStartTemperatureKread-writemandatoryGE/CW valve start temperature in tenths of Kelvins (5208)
1.3.6.1.4.1.318.1.1.13.5.3.15.9.2ScalarairIRmPmGECWvalveStartTemperatureFread-writemandatoryGE/CW valve start temperature in tenths of degrees Fahrenheit (5208)
1.3.6.1.4.1.318.1.1.13.5.3.15.10NodeairIRmPmGECWvalveLinearRange
1.3.6.1.4.1.318.1.1.13.5.3.15.10.1ScalarairIRmPmGECWvalveLinearRangeKread-writemandatoryGE/CW valve linear range in tenths of Kelvins (5209)
1.3.6.1.4.1.318.1.1.13.5.3.15.10.2ScalarairIRmPmGECWvalveLinearRangeFread-writemandatoryGE/CW valve linear range in tenths of degrees Fahrenheit (5209)
1.3.6.1.4.1.318.1.1.13.5.3.15.12NodeairIRmPmGECWvalveGEOffTemp
1.3.6.1.4.1.318.1.1.13.5.3.15.12.1ScalarairIRmPmGECWvalveGEOffTempCread-writemandatoryGE/CW valve GE off temperature in tenths of degrees Celsius (5211)
1.3.6.1.4.1.318.1.1.13.5.3.15.12.2ScalarairIRmPmGECWvalveGEOffTempFread-writemandatoryGE/CW valve GE off temperature in tenths of degrees Fahrenheit (5211)
1.3.6.1.4.1.318.1.1.13.5.3.15.15ScalarairIRmPmGECWvalveOpeningGraderead-onlymandatoryGE/CW valve opening grade in percent (5214)
1.3.6.1.4.1.318.1.1.13.5.3.15.16ScalarairIRmPmGECWvalveManOpOpeningGraderead-onlymandatoryGE/CW valve manual operation opening grade in percent (5215)
1.3.6.1.4.1.318.1.1.13.5.3.16NodeairIRmPmGvalve
1.3.6.1.4.1.318.1.1.13.5.3.16.2ScalarairIRmPmGvalveManOperationEnableread-onlymandatoryG-valve manual operation enable (5301)
1.3.6.1.4.1.318.1.1.13.5.3.16.11ScalarairIRmPmGvalvePreOpeningTimeread-onlymandatoryG-valve pre-opening time in seconds (5310)
1.3.6.1.4.1.318.1.1.13.5.3.16.12ScalarairIRmPmGvalvePreOpeningGraderead-onlymandatoryG-valve pre-opening grade in percent (5311)
1.3.6.1.4.1.318.1.1.13.5.3.16.13ScalarairIRmPmGvalveOpeningGraderead-onlymandatoryG-valve opening grade in percent (5312)
1.3.6.1.4.1.318.1.1.13.5.3.16.14ScalarairIRmPmGvalveManOpOpeningGraderead-onlymandatoryG-valve manual operation opening grade in percent (5313)
1.3.6.1.4.1.318.1.1.13.5.3.17NodeairIRmPmDrycooler1
1.3.6.1.4.1.318.1.1.13.5.3.17.2ScalarairIRmPmDrycooler1ManOpEnableread-onlymandatoryDrycooler 1 manual operation enable setting (5401)
1.3.6.1.4.1.318.1.1.13.5.3.17.3ScalarairIRmPmDrycooler1Runningread-onlymandatoryDrycooler 1 running (5402)
1.3.6.1.4.1.318.1.1.13.5.3.17.5ScalarairIRmPmDrycooler1ManOpRunningread-onlymandatoryDrycooler 1 manual operation running (5404)
1.3.6.1.4.1.318.1.1.13.5.3.17.9NodeairIRmPmDrycooler1WinterStartTemp
1.3.6.1.4.1.318.1.1.13.5.3.17.9.1ScalarairIRmPmDrycooler1WinterStartTempCread-writemandatoryDrycooler 1 winter mode start temperature in tenths of degrees Celsius (5408)
1.3.6.1.4.1.318.1.1.13.5.3.17.9.2ScalarairIRmPmDrycooler1WinterStartTempFread-writemandatoryDrycooler 1 winter mode start temperature in tenths of degrees Fahrenheit (5408)
1.3.6.1.4.1.318.1.1.13.5.3.17.10NodeairIRmPmDrycooler1SummerStartTemp
1.3.6.1.4.1.318.1.1.13.5.3.17.10.1ScalarairIRmPmDrycooler1SummerStartTempCread-writemandatoryDrycooler 1 summer mode start temperature in tenths of degrees Celsius (5409)
1.3.6.1.4.1.318.1.1.13.5.3.17.10.2ScalarairIRmPmDrycooler1SummerStartTempFread-writemandatoryDrycooler 1 summer mode start temperature in tenths of degrees Fahrenheit (5409)
1.3.6.1.4.1.318.1.1.13.5.3.17.11NodeairIRmPmDrycooler1Hysteresis
1.3.6.1.4.1.318.1.1.13.5.3.17.11.1ScalarairIRmPmDrycooler1HysteresisKread-writemandatoryDrycooler 1 hysteresis in tenths of Kelvins (5410)
1.3.6.1.4.1.318.1.1.13.5.3.17.11.2ScalarairIRmPmDrycooler1HysteresisFread-writemandatoryDrycooler 1 hysteresis in tenths of degrees Fahrenheit (5410)
1.3.6.1.4.1.318.1.1.13.5.3.17.16ScalarairIRmPmDrycooler1Runtimeread-onlymandatoryDrycooler 1 runtime in hours (5415)
1.3.6.1.4.1.318.1.1.13.5.3.18NodeairIRmPmDrycooler2
1.3.6.1.4.1.318.1.1.13.5.3.18.2ScalarairIRmPmDrycooler2ManOpEnableread-onlymandatoryDrycooler 2 manual operation enable setting (5501)
1.3.6.1.4.1.318.1.1.13.5.3.18.3ScalarairIRmPmDrycooler2Runningread-onlymandatoryDrycooler 2 running (5502)
1.3.6.1.4.1.318.1.1.13.5.3.18.5ScalarairIRmPmDrycooler2ManOpRunningread-onlymandatoryDrycooler 2 manual operation running (5504)
1.3.6.1.4.1.318.1.1.13.5.3.18.9NodeairIRmPmDrycooler2WinterStartTemp
1.3.6.1.4.1.318.1.1.13.5.3.18.9.1ScalarairIRmPmDrycooler2WinterStartTempCread-writemandatoryDrycooler 2 winter mode start temperature in tenths of degrees Celsius (5508)
1.3.6.1.4.1.318.1.1.13.5.3.18.9.2ScalarairIRmPmDrycooler2WinterStartTempFread-writemandatoryDrycooler 2 winter mode start temperature in tenths of degrees Fahrenheit (5508)
1.3.6.1.4.1.318.1.1.13.5.3.18.10NodeairIRmPmDrycooler2SummerStartTemp
1.3.6.1.4.1.318.1.1.13.5.3.18.10.1ScalarairIRmPmDrycooler2SummerStartTempCread-writemandatoryDrycooler 2 summer mode start temperature in tenths of degrees Celsius (5509)
1.3.6.1.4.1.318.1.1.13.5.3.18.10.2ScalarairIRmPmDrycooler2SummerStartTempFread-writemandatoryDrycooler 2 summer mode start temperature in tenths of degrees Fahrenheit (5509)
1.3.6.1.4.1.318.1.1.13.5.3.18.11NodeairIRmPmDrycooler2Hysteresis
1.3.6.1.4.1.318.1.1.13.5.3.18.11.1ScalarairIRmPmDrycooler2HysteresisKread-writemandatoryDrycooler 2 hysteresis in tenths of Kelvins (5510)
1.3.6.1.4.1.318.1.1.13.5.3.18.11.2ScalarairIRmPmDrycooler2HysteresisFread-writemandatoryDrycooler 2 hysteresis in tenths of degrees Fahrenheit (5510)
1.3.6.1.4.1.318.1.1.13.5.3.18.16ScalarairIRmPmDrycooler2Runtimeread-onlymandatoryDrycooler 2 runtime in hours (5515)
1.3.6.1.4.1.318.1.1.13.5.3.19NodeairIRmPmDrycooler3
1.3.6.1.4.1.318.1.1.13.5.3.19.2ScalarairIRmPmDrycooler3ManOpEnableread-onlymandatoryDrycooler 3 manual operation enable setting (5601)
1.3.6.1.4.1.318.1.1.13.5.3.19.3ScalarairIRmPmDrycooler3Runningread-onlymandatoryDrycooler 3 running (5602)
1.3.6.1.4.1.318.1.1.13.5.3.19.5ScalarairIRmPmDrycooler3ManOpRunningread-onlymandatoryDrycooler 3 manual operation running (5604)
1.3.6.1.4.1.318.1.1.13.5.3.19.9NodeairIRmPmDrycooler3WinterStartTemp
1.3.6.1.4.1.318.1.1.13.5.3.19.9.1ScalarairIRmPmDrycooler3WinterStartTempCread-writemandatoryDrycooler 3 winter mode start temperature in tenths of degrees Celsius (5608)
1.3.6.1.4.1.318.1.1.13.5.3.19.9.2ScalarairIRmPmDrycooler3WinterStartTempFread-writemandatoryDrycooler 3 winter mode start temperature in tenths of degrees Fahrenheit (5608)
1.3.6.1.4.1.318.1.1.13.5.3.19.10NodeairIRmPmDrycooler3SummerStartTemp
1.3.6.1.4.1.318.1.1.13.5.3.19.10.1ScalarairIRmPmDrycooler3SummerStartTempCread-writemandatoryDrycooler 3 summer mode start temperature in tenths of degrees Celsius (5609)
1.3.6.1.4.1.318.1.1.13.5.3.19.10.2ScalarairIRmPmDrycooler3SummerStartTempFread-writemandatoryDrycooler 3 summer mode start temperature in tenths of degrees Fahrenheit (5609)
1.3.6.1.4.1.318.1.1.13.5.3.19.11NodeairIRmPmDrycooler3Hysteresis
1.3.6.1.4.1.318.1.1.13.5.3.19.11.1ScalarairIRmPmDrycooler3HysteresisKread-writemandatoryDrycooler 3 hysteresis in tenths of Kelvins (5610)
1.3.6.1.4.1.318.1.1.13.5.3.19.11.2ScalarairIRmPmDrycooler3HysteresisFread-writemandatoryDrycooler 3 hysteresis in tenths of degrees Fahrenheit (5610)
1.3.6.1.4.1.318.1.1.13.5.3.19.16ScalarairIRmPmDrycooler3Runtimeread-onlymandatoryDrycooler 3 runtime in hours (5615)
1.3.6.1.4.1.318.1.1.13.5.3.20NodeairIRmPmDrycooler4
1.3.6.1.4.1.318.1.1.13.5.3.20.2ScalarairIRmPmDrycooler4ManOpEnableread-onlymandatoryDrycooler 4 manual operation enable setting (5701)
1.3.6.1.4.1.318.1.1.13.5.3.20.3ScalarairIRmPmDrycooler4Runningread-onlymandatoryDrycooler 4 running (5702)
1.3.6.1.4.1.318.1.1.13.5.3.20.5ScalarairIRmPmDrycooler4ManOpRunningread-onlymandatoryDrycooler 4 manual operation running (5704)
1.3.6.1.4.1.318.1.1.13.5.3.20.9NodeairIRmPmDrycooler4WinterStartTemp
1.3.6.1.4.1.318.1.1.13.5.3.20.9.1ScalarairIRmPmDrycooler4WinterStartTempCread-writemandatoryDrycooler 4 winter mode start temperature in tenths of degrees Celsius (5708)
1.3.6.1.4.1.318.1.1.13.5.3.20.9.2ScalarairIRmPmDrycooler4WinterStartTempFread-writemandatoryDrycooler 4 winter mode start temperature in tenths of degrees Fahrenheit (5708)
1.3.6.1.4.1.318.1.1.13.5.3.20.10NodeairIRmPmDrycooler4SummerStartTemp
1.3.6.1.4.1.318.1.1.13.5.3.20.10.1ScalarairIRmPmDrycooler4SummerStartTempCread-writemandatoryDrycooler 4 summer mode start temperature in tenths of degrees Celsius (5709)
1.3.6.1.4.1.318.1.1.13.5.3.20.10.2ScalarairIRmPmDrycooler4SummerStartTempFread-writemandatoryDrycooler 4 summer mode start temperature in tenths of degrees Fahrenheit (5709)
1.3.6.1.4.1.318.1.1.13.5.3.20.11NodeairIRmPmDrycooler4Hysteresis
1.3.6.1.4.1.318.1.1.13.5.3.20.11.1ScalarairIRmPmDrycooler4HysteresisKread-writemandatoryDrycooler 4 hysteresis in tenths of Kelvins (5710)
1.3.6.1.4.1.318.1.1.13.5.3.20.11.2ScalarairIRmPmDrycooler4HysteresisFread-writemandatoryDrycooler 4 hysteresis in tenths of degrees Fahrenheit (5710)
1.3.6.1.4.1.318.1.1.13.5.3.20.16ScalarairIRmPmDrycooler4Runtimeread-onlymandatoryDrycooler 4 runtime in hours (5715)
1.3.6.1.4.1.318.1.1.13.5.3.21NodeairIRmPmPump1
1.3.6.1.4.1.318.1.1.13.5.3.21.2ScalarairIRmPmPump1ManOpEnableread-onlymandatoryPump 1 manual operation enable state (5801)
1.3.6.1.4.1.318.1.1.13.5.3.21.3ScalarairIRmPmPump1Runningread-onlymandatoryPump 1 running (5802)
1.3.6.1.4.1.318.1.1.13.5.3.21.6ScalarairIRmPmPump1ManOpRunningread-onlymandatoryPump 1 manual operation running (5805)
1.3.6.1.4.1.318.1.1.13.5.3.21.10NodeairIRmPmPump1StartTemperature
1.3.6.1.4.1.318.1.1.13.5.3.21.10.1ScalarairIRmPmPump1StartTemperatureKread-writemandatoryPump 1 starting temperature in tenths of Kelvins (5809)
1.3.6.1.4.1.318.1.1.13.5.3.21.10.2ScalarairIRmPmPump1StartTemperatureFread-writemandatoryPump 1 starting temperature in tenths of degrees Fahrenheit (5809)
1.3.6.1.4.1.318.1.1.13.5.3.21.11NodeairIRmPmPump1Hysteresis
1.3.6.1.4.1.318.1.1.13.5.3.21.11.1ScalarairIRmPmPump1HysteresisKread-writemandatoryPump 1 hysteresis in tenths of Kelvins (5810)
1.3.6.1.4.1.318.1.1.13.5.3.21.11.2ScalarairIRmPmPump1HysteresisFread-writemandatoryPump 1 hysteresis in tenths of degrees Fahrenheit (5810)
1.3.6.1.4.1.318.1.1.13.5.3.21.12NodeairIRmPmPump1LinearRange
1.3.6.1.4.1.318.1.1.13.5.3.21.12.1ScalarairIRmPmPump1LinearRangeKread-writemandatoryPump 1 linear range in tenths of Kelvins (5811)
1.3.6.1.4.1.318.1.1.13.5.3.21.12.2ScalarairIRmPmPump1LinearRangeFread-writemandatoryPump 1 linear range in tenths of degrees Fahrenheit (5811)
1.3.6.1.4.1.318.1.1.13.5.3.21.13ScalarairIRmPmPump1PressureSetpointread-writemandatoryPump 1 pressure setpoint in tenths of Bars (5812)
1.3.6.1.4.1.318.1.1.13.5.3.21.21ScalarairIRmPmPump1Runtimeread-onlymandatoryPump 1 runtime in hours (5820)
1.3.6.1.4.1.318.1.1.13.5.3.21.22ScalarairIRmPmPump1Speedread-onlymandatoryPump 1 speed in percent (5821)
1.3.6.1.4.1.318.1.1.13.5.3.21.28ScalarairIRmPmPump1ControlCycleread-writemandatoryPump 1 control cycle length in seconds (5827)
1.3.6.1.4.1.318.1.1.13.5.3.21.29ScalarairIRmPmPump1MaxAdjustread-writemandatoryPump 1 maximum adjustment in percent (5828)
1.3.6.1.4.1.318.1.1.13.5.3.21.30ScalarairIRmPmPump1ControlFactorread-writemandatoryPump 1 control factor setting (5829)
1.3.6.1.4.1.318.1.1.13.5.3.22NodeairIRmPmPump2
1.3.6.1.4.1.318.1.1.13.5.3.22.2ScalarairIRmPmPump2ManOpEnableread-onlymandatoryPump 2 manual operation enable state (5901)
1.3.6.1.4.1.318.1.1.13.5.3.22.3ScalarairIRmPmPump2Runningread-onlymandatoryPump 2 running (5902)
1.3.6.1.4.1.318.1.1.13.5.3.22.6ScalarairIRmPmPump2ManOpRunningread-onlymandatoryPump 2 manual operation running (5905)
1.3.6.1.4.1.318.1.1.13.5.3.22.10NodeairIRmPmPump2StartTemperature
1.3.6.1.4.1.318.1.1.13.5.3.22.10.1ScalarairIRmPmPump2StartTemperatureKread-writemandatoryPump 2 starting temperature in tenths of Kelvins (5909)
1.3.6.1.4.1.318.1.1.13.5.3.22.10.2ScalarairIRmPmPump2StartTemperatureFread-writemandatoryPump 2 starting temperature in tenths of degrees Fahrenheit (5909)
1.3.6.1.4.1.318.1.1.13.5.3.22.11NodeairIRmPmPump2Hysteresis
1.3.6.1.4.1.318.1.1.13.5.3.22.11.1ScalarairIRmPmPump2HysteresisKread-writemandatoryPump 2 hysteresis in tenths of Kelvins (5910)
1.3.6.1.4.1.318.1.1.13.5.3.22.11.2ScalarairIRmPmPump2HysteresisFread-writemandatoryPump 2 hysteresis in tenths of degrees Fahrenheit (5910)
1.3.6.1.4.1.318.1.1.13.5.3.22.12NodeairIRmPmPump2LinearRange
1.3.6.1.4.1.318.1.1.13.5.3.22.12.1ScalarairIRmPmPump2LinearRangeKread-writemandatoryPump 2 linear range in tenths of Kelvins (5911)
1.3.6.1.4.1.318.1.1.13.5.3.22.12.2ScalarairIRmPmPump2LinearRangeFread-writemandatoryPump 2 linear range in tenths of degrees Fahrenheit (5911)
1.3.6.1.4.1.318.1.1.13.5.3.22.13ScalarairIRmPmPump2PressureSetpointread-writemandatoryPump 2 pressure setpoint in tenths of Bars (5912)
1.3.6.1.4.1.318.1.1.13.5.3.22.21ScalarairIRmPmPump2Runtimeread-onlymandatoryPump 2 runtime in hours (5920)
1.3.6.1.4.1.318.1.1.13.5.3.22.22ScalarairIRmPmPump2Speedread-onlymandatoryPump 2 speed in percent (5921)
1.3.6.1.4.1.318.1.1.13.5.3.22.28ScalarairIRmPmPump2ControlCycleread-writemandatoryPump 2 control cycle length in seconds (5927)
1.3.6.1.4.1.318.1.1.13.5.3.22.29ScalarairIRmPmPump2MaxAdjustread-writemandatoryPump 2 maximum adjustment in percent (5928)
1.3.6.1.4.1.318.1.1.13.5.3.22.30ScalarairIRmPmPump2ControlFactorread-writemandatoryPump 2 control factor setting (5929)
1.3.6.1.4.1.318.1.1.13.5.3.23NodeairIRmPmPump3
1.3.6.1.4.1.318.1.1.13.5.3.23.2ScalarairIRmPmPump3ManOpEnableread-onlymandatoryPump 3 manual operation enable state (6001)
1.3.6.1.4.1.318.1.1.13.5.3.23.3ScalarairIRmPmPump3Runningread-onlymandatoryPump 3 running (6002)
1.3.6.1.4.1.318.1.1.13.5.3.23.6ScalarairIRmPmPump3ManOpRunningread-onlymandatoryPump 3 manual operation running (6005)
1.3.6.1.4.1.318.1.1.13.5.3.23.10NodeairIRmPmPump3StartTemperature
1.3.6.1.4.1.318.1.1.13.5.3.23.10.1ScalarairIRmPmPump3StartTemperatureKread-writemandatoryPump 3 starting temperature in tenths of Kelvins (6009)
1.3.6.1.4.1.318.1.1.13.5.3.23.10.2ScalarairIRmPmPump3StartTemperatureFread-writemandatoryPump 3 starting temperature in tenths of degrees Fahrenheit (6009)
1.3.6.1.4.1.318.1.1.13.5.3.23.11NodeairIRmPmPump3Hysteresis
1.3.6.1.4.1.318.1.1.13.5.3.23.11.1ScalarairIRmPmPump3HysteresisKread-writemandatoryPump 3 hysteresis in tenths of Kelvins (6010)
1.3.6.1.4.1.318.1.1.13.5.3.23.11.2ScalarairIRmPmPump3HysteresisFread-writemandatoryPump 3 hysteresis in tenths of degrees Fahrenheit (6010)
1.3.6.1.4.1.318.1.1.13.5.3.23.12NodeairIRmPmPump3LinearRange
1.3.6.1.4.1.318.1.1.13.5.3.23.12.1ScalarairIRmPmPump3LinearRangeKread-writemandatoryPump 3 linear range in tenths of Kelvins (6011)
1.3.6.1.4.1.318.1.1.13.5.3.23.12.2ScalarairIRmPmPump3LinearRangeFread-writemandatoryPump 3 linear range in tenths of degrees Fahrenheit (6011)
1.3.6.1.4.1.318.1.1.13.5.3.23.13ScalarairIRmPmPump3PressureSetpointread-writemandatoryPump 3 pressure setpoint in tenths of Bars (6012)
1.3.6.1.4.1.318.1.1.13.5.3.23.21ScalarairIRmPmPump3Runtimeread-onlymandatoryPump 3 runtime in hours (6020)
1.3.6.1.4.1.318.1.1.13.5.3.23.22ScalarairIRmPmPump3Speedread-onlymandatoryPump 3 speed in percent (6021)
1.3.6.1.4.1.318.1.1.13.5.3.23.28ScalarairIRmPmPump3ControlCycleread-writemandatoryPump 3 control cycle length in seconds (6027)
1.3.6.1.4.1.318.1.1.13.5.3.23.29ScalarairIRmPmPump3MaxAdjustread-writemandatoryPump 3 maximum adjustment in percent (6028)
1.3.6.1.4.1.318.1.1.13.5.3.23.30ScalarairIRmPmPump3ControlFactorread-writemandatoryPump 3 control factor setting (6029)
1.3.6.1.4.1.318.1.1.13.5.3.24NodeairIRmPmPump4
1.3.6.1.4.1.318.1.1.13.5.3.24.2ScalarairIRmPmPump4ManOpEnableread-onlymandatoryPump 4 manual operation enable state (6101)
1.3.6.1.4.1.318.1.1.13.5.3.24.3ScalarairIRmPmPump4Runningread-onlymandatoryPump 4 running (6102)
1.3.6.1.4.1.318.1.1.13.5.3.24.6ScalarairIRmPmPump4ManOpRunningread-onlymandatoryPump 4 manual operation running (6105)
1.3.6.1.4.1.318.1.1.13.5.3.24.10NodeairIRmPmPump4StartTemperature
1.3.6.1.4.1.318.1.1.13.5.3.24.10.1ScalarairIRmPmPump4StartTemperatureKread-writemandatoryPump 4 starting temperature in tenths of Kelvins (6109)
1.3.6.1.4.1.318.1.1.13.5.3.24.10.2ScalarairIRmPmPump4StartTemperatureFread-writemandatoryPump 4 starting temperature in tenths of degrees Fahrenheit (6109)
1.3.6.1.4.1.318.1.1.13.5.3.24.11NodeairIRmPmPump4Hysteresis
1.3.6.1.4.1.318.1.1.13.5.3.24.11.1ScalarairIRmPmPump4HysteresisKread-writemandatoryPump 4 hysteresis in tenths of Kelvins (6110)
1.3.6.1.4.1.318.1.1.13.5.3.24.11.2ScalarairIRmPmPump4HysteresisFread-writemandatoryPump 4 hysteresis in tenths of degrees Fahrenheit (6110)
1.3.6.1.4.1.318.1.1.13.5.3.24.12NodeairIRmPmPump4LinearRange
1.3.6.1.4.1.318.1.1.13.5.3.24.12.1ScalarairIRmPmPump4LinearRangeKread-writemandatoryPump 4 linear range in tenths of Kelvins (6111)
1.3.6.1.4.1.318.1.1.13.5.3.24.12.2ScalarairIRmPmPump4LinearRangeFread-writemandatoryPump 4 linear range in tenths of degrees Fahrenheit (6111)
1.3.6.1.4.1.318.1.1.13.5.3.24.13ScalarairIRmPmPump4PressureSetpointread-writemandatoryPump 4 pressure setpoint in tenths of Bars (6112)
1.3.6.1.4.1.318.1.1.13.5.3.24.21ScalarairIRmPmPump4Runtimeread-onlymandatoryPump 4 runtime in hours (6120)
1.3.6.1.4.1.318.1.1.13.5.3.24.22ScalarairIRmPmPump4Speedread-onlymandatoryPump 4 speed in percent (6121)
1.3.6.1.4.1.318.1.1.13.5.3.24.28ScalarairIRmPmPump4ControlCycleread-writemandatoryPump 4 control cycle length in seconds (6127)
1.3.6.1.4.1.318.1.1.13.5.3.24.29ScalarairIRmPmPump4MaxAdjustread-writemandatoryPump 4 maximum adjustment in percent (6128)
1.3.6.1.4.1.318.1.1.13.5.3.24.30ScalarairIRmPmPump4ControlFactorread-writemandatoryPump 4 control factor setting (6129)
1.3.6.1.4.1.318.1.1.13.5.3.25NodeairIRmPmHotgasHeating
1.3.6.1.4.1.318.1.1.13.5.3.25.3ScalarairIRmPmHotgasHeatRunningread-onlymandatoryHotgas heat running state. (6202)
1.3.6.1.4.1.318.1.1.13.5.3.26NodeairIRmPmPWWHeating
1.3.6.1.4.1.318.1.1.13.5.3.26.2ScalarairIRmPmPWWHeatingManOpEnableread-onlymandatoryPWW-heating manual operation enable (6301)
1.3.6.1.4.1.318.1.1.13.5.3.26.3ScalarairIRmPmPWWHeatingRunningread-onlymandatoryPWW-heating running (6302)
1.3.6.1.4.1.318.1.1.13.5.3.26.4ScalarairIRmPmPWWHeatingManOpRunningread-onlymandatoryPWW-heating manual operation running (6303)
1.3.6.1.4.1.318.1.1.13.5.3.26.9ScalarairIRmPmPWWHeatingTyperead-onlymandatoryPWW-heating type (6308)
1.3.6.1.4.1.318.1.1.13.5.3.26.10NodeairIRmPmPWWHeatingStartTemp
1.3.6.1.4.1.318.1.1.13.5.3.26.10.1ScalarairIRmPmPWWHeatingStartTempKread-writemandatoryPWW-heating starting temperature in Kelvins (6309)
1.3.6.1.4.1.318.1.1.13.5.3.26.10.2ScalarairIRmPmPWWHeatingStartTempFread-writemandatoryPWW-heating starting temperature in degrees Fahrenheit (6309)
1.3.6.1.4.1.318.1.1.13.5.3.26.12NodeairIRmPmPWWHeatingHysteresis
1.3.6.1.4.1.318.1.1.13.5.3.26.12.1ScalarairIRmPmPWWHeatingHysteresisKread-writemandatoryPWW-heating hysteresis in Kelvins (6311)
1.3.6.1.4.1.318.1.1.13.5.3.26.12.2ScalarairIRmPmPWWHeatingHysteresisFread-writemandatoryPWW-heating hysteresis in degrees Fahrenheit (6311)
1.3.6.1.4.1.318.1.1.13.5.3.26.13NodeairIRmPmPWWHeatingLinearRange
1.3.6.1.4.1.318.1.1.13.5.3.26.13.1ScalarairIRmPmPWWHeatingLinearRangeKread-writemandatoryPWW-heating linear range in Kelvins (6312)
1.3.6.1.4.1.318.1.1.13.5.3.26.13.2ScalarairIRmPmPWWHeatingLinearRangeFread-writemandatoryPWW-heating linear range in degrees Fahrenheit (6312)
1.3.6.1.4.1.318.1.1.13.5.3.26.16ScalarairIRmPmPWWHeatingCurrentValueread-writemandatoryPWW-heating current value in percent (6315)
1.3.6.1.4.1.318.1.1.13.5.3.26.17ScalarairIRmPmPWWHeatingManOpValueread-writemandatoryPWW-heating manual operation value in percent (6316)
1.3.6.1.4.1.318.1.1.13.5.3.27NodeairIRmPmHumidifier1
1.3.6.1.4.1.318.1.1.13.5.3.27.2ScalarairIRmPmHumidifier1ManOpEnableread-onlymandatoryHumidifier #1 manual operation enable (6401)
1.3.6.1.4.1.318.1.1.13.5.3.27.3ScalarairIRmPmHumidifier1Runningread-onlymandatoryHumidifier #1 running state (6402)
1.3.6.1.4.1.318.1.1.13.5.3.27.5ScalarairIRmPmHumidifier1ManOpRunningread-onlymandatoryHumidifier #1 manual operation running state (6404)
1.3.6.1.4.1.318.1.1.13.5.3.27.17ScalarairIRmPmHumidifier1Typeread-onlymandatoryHumidifier #1 type (6416)
1.3.6.1.4.1.318.1.1.13.5.3.27.18ScalarairIRmPmHumidifier1StartHumidityread-writemandatoryHumidifier #1 start humidity in tenths of percent relative humidity (6417)
1.3.6.1.4.1.318.1.1.13.5.3.27.20ScalarairIRmPmHumidifier1Hysteresisread-writemandatoryHumidifier #1 hysteresis in tenths of percent relative humidity (6419)
1.3.6.1.4.1.318.1.1.13.5.3.27.21ScalarairIRmPmHumidifier1LinearRangeread-writemandatoryHumidifier #1 linear range in tenths of percent relative humidity per Kelvin (6420)
1.3.6.1.4.1.318.1.1.13.5.3.27.27ScalarairIRmPmHumidifier1Runtimeread-onlymandatoryHumidifier #1 runtime in hours (6426)
1.3.6.1.4.1.318.1.1.13.5.3.27.28ScalarairIRmPmHumidifier1CurrentValueread-onlymandatoryHumidifier #1 current value in percent (6427)
1.3.6.1.4.1.318.1.1.13.5.3.27.29ScalarairIRmPmHumidifier1ManOpValueread-writemandatoryHumidifier #1 manual operation value in percent (6428)
1.3.6.1.4.1.318.1.1.13.5.3.28NodeairIRmPmHumidifier2
1.3.6.1.4.1.318.1.1.13.5.3.28.2ScalarairIRmPmHumidifier2ManOpEnableread-onlymandatoryHumidifier #2 manual operation enable (6501)
1.3.6.1.4.1.318.1.1.13.5.3.28.3ScalarairIRmPmHumidifier2Runningread-onlymandatoryHumidifier #2 running state (6502)
1.3.6.1.4.1.318.1.1.13.5.3.28.5ScalarairIRmPmHumidifier2ManOpRunningread-onlymandatoryHumidifier #2 manual operation running state (6504)
1.3.6.1.4.1.318.1.1.13.5.3.28.17ScalarairIRmPmHumidifier2Typeread-onlymandatoryHumidifier #2 type (6516)
1.3.6.1.4.1.318.1.1.13.5.3.28.18ScalarairIRmPmHumidifier2StartHumidityread-writemandatoryHumidifier #2 start humidity in tenths of percent relative humidity (6517)
1.3.6.1.4.1.318.1.1.13.5.3.28.20ScalarairIRmPmHumidifier2Hysteresisread-writemandatoryHumidifier #2 hysteresis in tenths of percent relative humidity (6519)
1.3.6.1.4.1.318.1.1.13.5.3.28.21ScalarairIRmPmHumidifier2LinearRangeread-writemandatoryHumidifier #2 linear range in tenths of percent relative humidity per Kelvin (6520)
1.3.6.1.4.1.318.1.1.13.5.3.28.27ScalarairIRmPmHumidifier2Runtimeread-onlymandatoryHumidifier #2 runtime in hours (6526)
1.3.6.1.4.1.318.1.1.13.5.3.28.28ScalarairIRmPmHumidifier2CurrentValueread-onlymandatoryHumidifier #2 current value in percent (6527)
1.3.6.1.4.1.318.1.1.13.5.3.28.29ScalarairIRmPmHumidifier2ManOpValueread-writemandatoryHumidifier #2 manual operation value in percent (6528)
1.3.6.1.4.1.318.1.1.13.5.3.31NodeairIRmPmDehumidification
1.3.6.1.4.1.318.1.1.13.5.3.31.2ScalarairIRmPmDehumidificManOpEnableread-onlymandatoryDehumidifier manual operation enable setting (6801)
1.3.6.1.4.1.318.1.1.13.5.3.31.3ScalarairIRmPmDehumidificRunningread-onlymandatoryDehumidifier running state (6802)
1.3.6.1.4.1.318.1.1.13.5.3.31.5ScalarairIRmPmDehumidificManOpRunningread-onlymandatoryDehumidifier manual operation running (6804)
1.3.6.1.4.1.318.1.1.13.5.3.31.10ScalarairIRmPmDehumidificStartHumidityread-writemandatoryDehumidifier start humidity in tenths of percent relative humidity (6809)
1.3.6.1.4.1.318.1.1.13.5.3.31.12ScalarairIRmPmDehumidificHysteresisread-writemandatoryDehumidifier hysteresis in tenths of percent relative humidity (6811)
1.3.6.1.4.1.318.1.1.13.5.3.31.18NodeairIRmPmDehumidificMinWaterTemp
1.3.6.1.4.1.318.1.1.13.5.3.31.18.1ScalarairIRmPmDehumidificMinWaterTempCread-writemandatoryDehumidifier minimum water temperature in tenths of degrees Celsius (6817)
1.3.6.1.4.1.318.1.1.13.5.3.31.18.2ScalarairIRmPmDehumidificMinWaterTempFread-writemandatoryDehumidifier minimum water temperature in tenths of degrees Fahrenheit (6817)
1.3.6.1.4.1.318.1.1.13.5.3.31.19NodeairIRmPmDehumidificMaxWaterTemp
1.3.6.1.4.1.318.1.1.13.5.3.31.19.1ScalarairIRmPmDehumidificMaxWaterTempCread-writemandatoryDehumidifier maximum water temperature in tenths of degrees Celsius (6818)
1.3.6.1.4.1.318.1.1.13.5.3.31.19.2ScalarairIRmPmDehumidificMaxWaterTempFread-writemandatoryDehumidifier maximum water temperature in tenths of degrees Fahrenheit (6818)
1.3.6.1.4.1.318.1.1.13.5.3.31.21ScalarairIRmPmDehumidificRuntimeread-writemandatoryDehumidifier runtime in hours (6820)
1.3.6.1.4.1.318.1.1.13.5.3.32NodeairIRmPmFan1
1.3.6.1.4.1.318.1.1.13.5.3.32.2ScalarairIRmPmFan1ManOpEnableread-onlymandatoryFan 1 manual operation enable (6901)
1.3.6.1.4.1.318.1.1.13.5.3.32.3ScalarairIRmPmFan1Runningread-onlymandatoryFan 1 running (6902)
1.3.6.1.4.1.318.1.1.13.5.3.32.6ScalarairIRmPmFan1ManOpRunningread-onlymandatoryFan 1 manual operation running (6905)
1.3.6.1.4.1.318.1.1.13.5.3.32.9ScalarairIRmPmFan1Typeread-onlymandatoryFan 1 type (6908)
1.3.6.1.4.1.318.1.1.13.5.3.32.32ScalarairIRmPmFan1Runtimeread-onlymandatoryFan 1 runtime in hours (6931)
1.3.6.1.4.1.318.1.1.13.5.3.32.33ScalarairIRmPmFan1Speedread-onlymandatoryFan 1 speed in percent (6932)
1.3.6.1.4.1.318.1.1.13.5.3.32.34ScalarairIRmPmFan1ManOpSpeedread-onlymandatoryFan 1 manual operation speed in percent (6933)
1.3.6.1.4.1.318.1.1.13.5.3.33NodeairIRmPmFan2
1.3.6.1.4.1.318.1.1.13.5.3.33.2ScalarairIRmPmFan2ManOpEnableread-onlymandatoryFan 1 manual operation enable (7001)
1.3.6.1.4.1.318.1.1.13.5.3.33.3ScalarairIRmPmFan2Runningread-onlymandatoryFan 1 running (7002)
1.3.6.1.4.1.318.1.1.13.5.3.33.6ScalarairIRmPmFan2ManOpRunningread-onlymandatoryFan 1 manual operation running (7005)
1.3.6.1.4.1.318.1.1.13.5.3.33.9ScalarairIRmPmFan2Typeread-onlymandatoryFan 2 type (7008)
1.3.6.1.4.1.318.1.1.13.5.3.33.32ScalarairIRmPmFan2Runtimeread-onlymandatoryFan 1 runtime in hours (7031)
1.3.6.1.4.1.318.1.1.13.5.3.33.33ScalarairIRmPmFan2Speedread-onlymandatoryFan 1 speed in percent (7032)
1.3.6.1.4.1.318.1.1.13.5.3.33.34ScalarairIRmPmFan2ManOpSpeedread-onlymandatoryFan 1 manual operation speed in percent (7033)
1.3.6.1.4.1.318.1.1.13.5.3.34NodeairIRmPmFan3
1.3.6.1.4.1.318.1.1.13.5.3.34.2ScalarairIRmPmFan3ManOpEnableread-onlymandatoryFan 1 manual operation enable (7101)
1.3.6.1.4.1.318.1.1.13.5.3.34.3ScalarairIRmPmFan3Runningread-onlymandatoryFan 1 running (7102)
1.3.6.1.4.1.318.1.1.13.5.3.34.6ScalarairIRmPmFan3ManOpRunningread-onlymandatoryFan 1 manual operation running (7105)
1.3.6.1.4.1.318.1.1.13.5.3.34.9ScalarairIRmPmFan3Typeread-onlymandatoryFan 3 type (7108)
1.3.6.1.4.1.318.1.1.13.5.3.34.32ScalarairIRmPmFan3Runtimeread-onlymandatoryFan 1 runtime in hours (7131)
1.3.6.1.4.1.318.1.1.13.5.3.34.33ScalarairIRmPmFan3Speedread-onlymandatoryFan 1 speed in percent (7132)
1.3.6.1.4.1.318.1.1.13.5.3.34.34ScalarairIRmPmFan3ManOpSpeedread-onlymandatoryFan 1 manual operation speed in percent (7133)
1.3.6.1.4.1.318.1.1.13.5.3.35NodeairIRmPmLouver1
1.3.6.1.4.1.318.1.1.13.5.3.35.2ScalarairIRmPmLouver1ManOpEnableread-onlymandatoryLouver 1 manual operation enable (7201)
1.3.6.1.4.1.318.1.1.13.5.3.35.3ScalarairIRmPmLouver1Positionread-onlymandatoryLouver 1 position (7202)
1.3.6.1.4.1.318.1.1.13.5.3.35.4ScalarairIRmPmLouver1ManOpPositionread-onlymandatoryLouver 1 manual operation position setting (7203)
1.3.6.1.4.1.318.1.1.13.5.3.36NodeairIRmPmLouver2
1.3.6.1.4.1.318.1.1.13.5.3.36.2ScalarairIRmPmLouver2ManOpEnableread-onlymandatoryLouver 2 manual operation enable (7301)
1.3.6.1.4.1.318.1.1.13.5.3.36.3ScalarairIRmPmLouver2Positionread-onlymandatoryLouver 2 position (7302)
1.3.6.1.4.1.318.1.1.13.5.3.36.4ScalarairIRmPmLouver2ManOpPositionread-onlymandatoryLouver 2 manual operation position setting (7303)
1.3.6.1.4.1.318.1.1.13.5.3.37NodeairIRmPmLouver3
1.3.6.1.4.1.318.1.1.13.5.3.37.2ScalarairIRmPmLouver3ManOpEnableread-onlymandatoryLouver 3 manual operation enable (7401)
1.3.6.1.4.1.318.1.1.13.5.3.37.3ScalarairIRmPmLouver3Positionread-onlymandatoryLouver 3 position (7402)
1.3.6.1.4.1.318.1.1.13.5.3.37.4ScalarairIRmPmLouver3ManOpPositionread-onlymandatoryLouver 3 manual operation position setting (7403)
1.3.6.1.4.1.318.1.1.13.5.3.38NodeairIRmPmAuxAlarm1
1.3.6.1.4.1.318.1.1.13.5.3.39NodeairIRmPmAuxAlarm2
1.3.6.1.4.1.318.1.1.13.5.3.40NodeairIRmPmAuxAlarm3
1.3.6.1.4.1.318.1.1.13.5.3.41NodeairIRmPmAuxAlarm4
1.3.6.1.4.1.318.1.1.13.5.3.42NodeairIRmPmAuxAlarm5
1.3.6.1.4.1.318.1.1.13.5.3.43NodeairIRmPmAlarmBits
1.3.6.1.4.1.318.1.1.13.5.3.43.1ScalarairIRmPmFan1Failureread-onlymandatoryFan #1 failure (8500).
1.3.6.1.4.1.318.1.1.13.5.3.43.2ScalarairIRmPmFan2Failureread-onlymandatoryFan #2 failure (8501).
1.3.6.1.4.1.318.1.1.13.5.3.43.3ScalarairIRmPmFan3Failureread-onlymandatoryFan #3 failure (8502).
1.3.6.1.4.1.318.1.1.13.5.3.43.4ScalarairIRmPmCompressor1Failureread-onlymandatoryCompressor #1 failure (8503).
1.3.6.1.4.1.318.1.1.13.5.3.43.5ScalarairIRmPmCompressor2Failureread-onlymandatoryCompressor #2 failure (8504).
1.3.6.1.4.1.318.1.1.13.5.3.43.6ScalarairIRmPmWaterDetectorread-onlymandatoryWater detector alarm (8505).
1.3.6.1.4.1.318.1.1.13.5.3.43.7ScalarairIRmPmPhaseFailureread-onlymandatoryPhase failure (8506).
1.3.6.1.4.1.318.1.1.13.5.3.43.8ScalarairIRmPmFireSmokeDetectorread-onlymandatoryFire/smoke detector (8507).
1.3.6.1.4.1.318.1.1.13.5.3.43.9ScalarairIRmPmReturnAirTemperatureTooHighread-onlymandatoryReturn air temperature too high (8508).
1.3.6.1.4.1.318.1.1.13.5.3.43.10ScalarairIRmPmReturnAirHumidityTooHighread-onlymandatoryReturn air humidity too high (8509).
1.3.6.1.4.1.318.1.1.13.5.3.43.11ScalarairIRmPmSupplyAirTemperatureTooHighread-onlymandatorySupply air temperature too high (8510).
1.3.6.1.4.1.318.1.1.13.5.3.43.12ScalarairIRmPmSupplyAirHumidityTooHighread-onlymandatorySupply air humidity too high (8511).
1.3.6.1.4.1.318.1.1.13.5.3.43.13ScalarairIRmPmWaterTemperatureTooHighread-onlymandatoryWater temperature too high (8512).
1.3.6.1.4.1.318.1.1.13.5.3.43.14ScalarairIRmPmReturnAirTemperatureTooLowread-onlymandatoryReturn air temperature too low (8513).
1.3.6.1.4.1.318.1.1.13.5.3.43.15ScalarairIRmPmReturnAirHumidityTooLowread-onlymandatoryReturn air humidity too low (8514).
1.3.6.1.4.1.318.1.1.13.5.3.43.16ScalarairIRmPmSupplyAirTemperatureTooLowread-onlymandatorySupply air temperature too low (8515).
1.3.6.1.4.1.318.1.1.13.5.3.43.17ScalarairIRmPmSupplyAirHumidityTooLowread-onlymandatorySupply air humidity too low (8516).
1.3.6.1.4.1.318.1.1.13.5.3.43.18ScalarairIRmPmWaterTemperatureTooLowread-onlymandatoryWater temperature too low (8517).
1.3.6.1.4.1.318.1.1.13.5.3.43.19ScalarairIRmPmSensor1Failureread-onlymandatorySensor #1 failure (8518).
1.3.6.1.4.1.318.1.1.13.5.3.43.20ScalarairIRmPmSensor2Failureread-onlymandatorySensor #2 failure (8519).
1.3.6.1.4.1.318.1.1.13.5.3.43.21ScalarairIRmPmSensor3Failureread-onlymandatorySensor #3 failure (8520).
1.3.6.1.4.1.318.1.1.13.5.3.43.22ScalarairIRmPmSensor4Failureread-onlymandatorySensor #4 failure (8521).
1.3.6.1.4.1.318.1.1.13.5.3.43.23ScalarairIRmPmSensor5Failureread-onlymandatorySensor #5 failure (8522).
1.3.6.1.4.1.318.1.1.13.5.3.43.24ScalarairIRmPmSensor6Failureread-onlymandatorySensor #6 failure (8523).
1.3.6.1.4.1.318.1.1.13.5.3.43.25ScalarairIRmPmSensor7Failureread-onlymandatorySensor #7 failure (8524).
1.3.6.1.4.1.318.1.1.13.5.3.43.26ScalarairIRmPmSensor8Failureread-onlymandatorySensor #8 failure (8525).
1.3.6.1.4.1.318.1.1.13.5.3.43.27ScalarairIRmPmSensor9Failureread-onlymandatorySensor #9 failure (8526).
1.3.6.1.4.1.318.1.1.13.5.3.43.28ScalarairIRmPmSensor10Failureread-onlymandatorySensor #10 failure (8527).
1.3.6.1.4.1.318.1.1.13.5.3.43.29ScalarairIRmPmSensor11Failureread-onlymandatorySensor #11 failure (8528).
1.3.6.1.4.1.318.1.1.13.5.3.43.30ScalarairIRmPmSensor12Failureread-onlymandatorySensor #12 failure (8529).
1.3.6.1.4.1.318.1.1.13.5.3.43.31ScalarairIRmPmSensor13Failureread-onlymandatorySensor #13 failure (8530).
1.3.6.1.4.1.318.1.1.13.5.3.43.32ScalarairIRmPmSensor14Failureread-onlymandatorySensor #14 failure (8531).
1.3.6.1.4.1.318.1.1.13.5.3.43.33ScalarairIRmPmSensor15Failureread-onlymandatorySensor #15 failure (8532).
1.3.6.1.4.1.318.1.1.13.5.3.43.34ScalarairIRmPmSensor16Failureread-onlymandatorySensor #16 failure (8533).
1.3.6.1.4.1.318.1.1.13.5.3.43.35ScalarairIRmPmSensor17Failureread-onlymandatorySensor #17 failure (8534).
1.3.6.1.4.1.318.1.1.13.5.3.43.36ScalarairIRmPmSensor18Failureread-onlymandatorySensor #18 failure (8535).
1.3.6.1.4.1.318.1.1.13.5.3.43.37ScalarairIRmPmSensor19Failureread-onlymandatorySensor #19 failure (8536).
1.3.6.1.4.1.318.1.1.13.5.3.43.38ScalarairIRmPmSensor20Failureread-onlymandatorySensor #20 failure (8537).
1.3.6.1.4.1.318.1.1.13.5.3.43.39ScalarairIRmPmSensor21Failureread-onlymandatorySensor #21 failure (8538).
1.3.6.1.4.1.318.1.1.13.5.3.43.40ScalarairIRmPmSensor1Defectread-onlymandatorySensor #1 defect (8539).
1.3.6.1.4.1.318.1.1.13.5.3.43.41ScalarairIRmPmSensor2Defectread-onlymandatorySensor #2 defect (8540).
1.3.6.1.4.1.318.1.1.13.5.3.43.42ScalarairIRmPmSensor3Defectread-onlymandatorySensor #3 defect (8541).
1.3.6.1.4.1.318.1.1.13.5.3.43.43ScalarairIRmPmSensor4Defectread-onlymandatorySensor #4 defect (8542).
1.3.6.1.4.1.318.1.1.13.5.3.43.44ScalarairIRmPmSensor5Defectread-onlymandatorySensor #5 defect (8543).
1.3.6.1.4.1.318.1.1.13.5.3.43.45ScalarairIRmPmSensor6Defectread-onlymandatorySensor #6 defect (8544).
1.3.6.1.4.1.318.1.1.13.5.3.43.46ScalarairIRmPmSensor7Defectread-onlymandatorySensor #7 defect (8545).
1.3.6.1.4.1.318.1.1.13.5.3.43.47ScalarairIRmPmSensor8Defectread-onlymandatorySensor #8 defect (8546).
1.3.6.1.4.1.318.1.1.13.5.3.43.48ScalarairIRmPmSensor9Defectread-onlymandatorySensor #9 defect (8547).
1.3.6.1.4.1.318.1.1.13.5.3.43.49ScalarairIRmPmSensor10Defectread-onlymandatorySensor #10 defect (8548).
1.3.6.1.4.1.318.1.1.13.5.3.43.50ScalarairIRmPmSensor11Defectread-onlymandatorySensor #11 defect (8549).
1.3.6.1.4.1.318.1.1.13.5.3.43.51ScalarairIRmPmSensor12Defectread-onlymandatorySensor #12 defect (8550).
1.3.6.1.4.1.318.1.1.13.5.3.43.52ScalarairIRmPmSensor13Defectread-onlymandatorySensor #13 defect (8551).
1.3.6.1.4.1.318.1.1.13.5.3.43.53ScalarairIRmPmSensor14Defectread-onlymandatorySensor #14 defect (8552).
1.3.6.1.4.1.318.1.1.13.5.3.43.54ScalarairIRmPmSensor15Defectread-onlymandatorySensor #15 defect (8553).
1.3.6.1.4.1.318.1.1.13.5.3.43.55ScalarairIRmPmSensor16Defectread-onlymandatorySensor #16 defect (8554).
1.3.6.1.4.1.318.1.1.13.5.3.43.56ScalarairIRmPmSensor17Defectread-onlymandatorySensor #17 defect (8555).
1.3.6.1.4.1.318.1.1.13.5.3.43.57ScalarairIRmPmSensor18Defectread-onlymandatorySensor #18 defect (8556)
1.3.6.1.4.1.318.1.1.13.5.3.43.58ScalarairIRmPmSensor19Defectread-onlymandatorySensor #19 defect (8557).
1.3.6.1.4.1.318.1.1.13.5.3.43.59ScalarairIRmPmSensor20Defectread-onlymandatorySensor #20 defect (8558).
1.3.6.1.4.1.318.1.1.13.5.3.43.60ScalarairIRmPmSensor21Defectread-onlymandatorySensor #21 defect (8559).
1.3.6.1.4.1.318.1.1.13.5.3.43.61ScalarairIRmPmCompressor1Alarmread-onlymandatoryCompressor #1 alarm (8560).
1.3.6.1.4.1.318.1.1.13.5.3.43.62ScalarairIRmPmCompressor2Alarmread-onlymandatoryCompressor #2 alarm (8561).
1.3.6.1.4.1.318.1.1.13.5.3.43.63ScalarairIRmPmCompressor1LowPressureread-onlymandatoryCompressor #1 low pressure (8562).
1.3.6.1.4.1.318.1.1.13.5.3.43.64ScalarairIRmPmCompressor2LowPressureread-onlymandatoryCompressor #2 low pressure (8563).
1.3.6.1.4.1.318.1.1.13.5.3.43.65ScalarairIRmPmReheat1Failureread-onlymandatoryReheat #1 failure (8564).
1.3.6.1.4.1.318.1.1.13.5.3.43.66ScalarairIRmPmReheat2Failureread-onlymandatoryReheat #2 failure (8565).
1.3.6.1.4.1.318.1.1.13.5.3.43.67ScalarairIRmPmReheat3Failureread-onlymandatoryReheat #3 failure (8566).
1.3.6.1.4.1.318.1.1.13.5.3.43.68ScalarairIRmPmReheat4Failureread-onlymandatoryReheat #4 failure (8567).
1.3.6.1.4.1.318.1.1.13.5.3.43.69ScalarairIRmPmDrycooler1Failureread-onlymandatoryDrycooler #1 failure (8568).
1.3.6.1.4.1.318.1.1.13.5.3.43.70ScalarairIRmPmDrycooler2Failureread-onlymandatoryDrycooler #2 failure (8569).
1.3.6.1.4.1.318.1.1.13.5.3.43.71ScalarairIRmPmDrycooler3Failureread-onlymandatoryDrycooler #3 failure (8570).
1.3.6.1.4.1.318.1.1.13.5.3.43.72ScalarairIRmPmDrycooler4Failureread-onlymandatoryDrycooler #4 failure (8571).
1.3.6.1.4.1.318.1.1.13.5.3.43.73ScalarairIRmPmPump1Failureread-onlymandatoryPump #1 failure (8572).
1.3.6.1.4.1.318.1.1.13.5.3.43.74ScalarairIRmPmPump2Failureread-onlymandatoryPump #2 failure (8573).
1.3.6.1.4.1.318.1.1.13.5.3.43.75ScalarairIRmPmPump3Failureread-onlymandatoryPump #3 failure (8574).
1.3.6.1.4.1.318.1.1.13.5.3.43.76ScalarairIRmPmPump4Failureread-onlymandatoryPump #4 failure (8575).
1.3.6.1.4.1.318.1.1.13.5.3.43.77ScalarairIRmPmHumidifier1Failureread-onlymandatoryHumidifier #1 failure (8576).
1.3.6.1.4.1.318.1.1.13.5.3.43.78ScalarairIRmPmHumidifier2Failureread-onlymandatoryHumidifier #2 failure (8577).
1.3.6.1.4.1.318.1.1.13.5.3.43.79ScalarairIRmPmHumidifier3Failureread-onlymandatoryHumidifier #3 failure (8578).
1.3.6.1.4.1.318.1.1.13.5.3.43.80ScalarairIRmPmHumidifier1Alarm5usread-onlymandatoryHumidifier #1 5us alarm (8579).
1.3.6.1.4.1.318.1.1.13.5.3.43.81ScalarairIRmPmHumidifier2Alarm5usread-onlymandatoryHumidifier #2 5us alarm (8580).
1.3.6.1.4.1.318.1.1.13.5.3.43.82ScalarairIRmPmHumidifier3Alarm5usread-onlymandatoryHumidifier #3 5us alarm (8581).
1.3.6.1.4.1.318.1.1.13.5.3.43.83ScalarairIRmPmHumidifier1Alarm20usread-onlymandatoryHumidifier #1 20us alarm (8582).
1.3.6.1.4.1.318.1.1.13.5.3.43.84ScalarairIRmPmHumidifier2Alarm20usread-onlymandatoryHumidifier #2 20us alarm (8583).
1.3.6.1.4.1.318.1.1.13.5.3.43.85ScalarairIRmPmHumidifier3Alarm20usread-onlymandatoryHumidifier #3 20us alarm (8584).
1.3.6.1.4.1.318.1.1.13.5.3.43.86ScalarairIRmPmFan1Alarmread-onlymandatoryFan #1 alarm (8585).
1.3.6.1.4.1.318.1.1.13.5.3.43.87ScalarairIRmPmFan2Alarmread-onlymandatoryFan #2 alarm (8586).
1.3.6.1.4.1.318.1.1.13.5.3.43.88ScalarairIRmPmFan3Alarmread-onlymandatoryFan #3 alarm (8587).
1.3.6.1.4.1.318.1.1.13.5.3.43.89ScalarairIRmPmFilter1Cloggedread-onlymandatoryFilter #1 clogged (8588).
1.3.6.1.4.1.318.1.1.13.5.3.43.90ScalarairIRmPmFilter2Cloggedread-onlymandatoryFilter #2 clogged (8589).
1.3.6.1.4.1.318.1.1.13.5.3.43.91ScalarairIRmPmFilter3Cloggedread-onlymandatoryFilter #3 clogged (8590).
1.3.6.1.4.1.318.1.1.13.5.3.43.92ScalarairIRmPmAuxiliaryAlarm1read-onlymandatoryAuxiliary #1 alarm (8591).
1.3.6.1.4.1.318.1.1.13.5.3.43.93ScalarairIRmPmAuxiliaryAlarm2read-onlymandatoryAuxiliary #2 alarm (8592).
1.3.6.1.4.1.318.1.1.13.5.3.43.94ScalarairIRmPmAuxiliaryAlarm3read-onlymandatoryAuxiliary #3 alarm (8593).
1.3.6.1.4.1.318.1.1.13.5.3.43.95ScalarairIRmPmAuxiliaryAlarm4read-onlymandatoryAuxiliary #4 alarm (8594).
1.3.6.1.4.1.318.1.1.13.5.3.43.96ScalarairIRmPmAuxiliaryAlarm5read-onlymandatoryAuxiliary #5 alarm (8595).
1.3.6.1.4.1.318.1.1.13.5.3.43.97ScalarairIRmPmAuxiliaryAlarm6read-onlymandatoryAuxiliary #6 alarm (8596).
1.3.6.1.4.1.318.1.1.13.5.3.43.98ScalarairIRmPmAuxiliaryAlarm7read-onlymandatoryAuxiliary #7 alarm (8597).
1.3.6.1.4.1.318.1.1.13.5.3.43.99ScalarairIRmPmAuxiliaryAlarm8read-onlymandatoryAuxiliary #8 alarm (8598).
1.3.6.1.4.1.318.1.1.13.5.3.43.100ScalarairIRmPmAuxiliaryAlarm9read-onlymandatoryAuxiliary #9 alarm (8599).
1.3.6.1.4.1.318.1.1.13.5.3.43.101ScalarairIRmPmAuxiliaryAlarm10read-onlymandatoryAuxiliary #10 alarm (8600).
1.3.6.1.4.1.318.1.1.13.5.3.43.102ScalarairIRmPmHotGasHeatingAlarmread-onlymandatoryHot gas heating alarm (8601).
1.3.6.1.4.1.318.1.1.13.5.3.43.103ScalarairIRmPmEEV1PressureSensorErrorread-onlymandatoryEEV1 pressure sensor error (8602).
1.3.6.1.4.1.318.1.1.13.5.3.43.104ScalarairIRmPmEEV1TemperatureSensorErrorread-onlymandatoryEEV1 temperature sensor error (8603).
1.3.6.1.4.1.318.1.1.13.5.3.43.105ScalarairIRmPmEEV1StepperMotorErrorread-onlymandatoryEEV1 stepper motor error (8604).
1.3.6.1.4.1.318.1.1.13.5.3.43.106ScalarairIRmPmEEV2PressureSensorErrorread-onlymandatoryEEV2 pressure sensor error (8605).
1.3.6.1.4.1.318.1.1.13.5.3.43.107ScalarairIRmPmEEV2TemperatureSensorErrorread-onlymandatoryEEV2 temperature sensor error (8606).
1.3.6.1.4.1.318.1.1.13.5.3.43.108ScalarairIRmPmEEV2StepperMotorErrorread-onlymandatoryEEV2 stepper motor error (8607).
1.3.6.1.4.1.318.1.1.13.5.3.44NodeairIRmPmMyZone
1.3.6.1.4.1.318.1.1.13.5.3.44.1ScalarairIRmPmMyZoneNumberread-onlymandatoryMy zone number (11700).
1.3.6.1.4.1.318.1.1.13.5.3.44.2NodeairIRmPmMyZoneRoomTemperature
1.3.6.1.4.1.318.1.1.13.5.3.44.2.1ScalarairIRmPmMyZoneRoomTemperatureCread-onlymandatoryMy zone room temperature in tenths of degrees Celsius (11701).
1.3.6.1.4.1.318.1.1.13.5.3.44.2.2ScalarairIRmPmMyZoneRoomTemperatureFread-onlymandatoryMy zone room temperature in tenths of degrees Fahrenheit (11701).
1.3.6.1.4.1.318.1.1.13.5.3.44.3ScalarairIRmPmMyZoneRoomHumidityread-onlymandatoryMy zone room humidity in tenths of %RH (11702).
1.3.6.1.4.1.318.1.1.13.5.3.44.4NodeairIRmPmMyZoneSupplyTemperature
1.3.6.1.4.1.318.1.1.13.5.3.44.4.1ScalarairIRmPmMyZoneSupplyTemperatureCread-onlymandatoryMy zone supply temperature in tenths of degrees Celsius (11703).
1.3.6.1.4.1.318.1.1.13.5.3.44.4.2ScalarairIRmPmMyZoneSupplyTemperatureFread-onlymandatoryMy zone supply temperature in tenths of degrees Fahrenheit (11703).
1.3.6.1.4.1.318.1.1.13.5.3.44.5ScalarairIRmPmMyZoneSupplyHumidityread-onlymandatoryMy zone supply humidity in tenths of %RH (11704).
1.3.6.1.4.1.318.1.1.13.5.3.44.6ScalarairIRmPmMyZoneSequencingTimeread-onlymandatoryMy zone sequencing time in minutes (11705).
1.3.6.1.4.1.318.1.1.13.5.3.44.7ScalarairIRmPmMyZoneNumberOfErrorUnitsread-onlymandatoryNumber of error units in my zone (11706).
1.3.6.1.4.1.318.1.1.13.5.3.44.8NodeairIRmPmMyZoneEmergencyTemperature
1.3.6.1.4.1.318.1.1.13.5.3.44.8.1ScalarairIRmPmMyZoneEmergencyTemperatureCread-onlymandatoryMy zone emergency temperature in tenths of degrees Celsius (11707).
1.3.6.1.4.1.318.1.1.13.5.3.44.8.2ScalarairIRmPmMyZoneEmergencyTemperatureFread-onlymandatoryMy zone emergency temperature in tenths of degrees Fahrenheit (11707).
1.3.6.1.4.1.318.1.1.13.5.3.44.9ScalarairIRmPmMyZoneCWEnergySaveModeread-onlymandatoryMy zone CW energy save mode (11708).
1.3.6.1.4.1.318.1.1.13.5.3.45NodeairIRmPmGlobalZoneData
1.3.6.1.4.1.318.1.1.13.5.3.45.1ScalarairIRmPmGlobalZoneDataEmergencyOpModeread-onlymandatoryEmergency operation mode (11800).
1.3.6.1.4.1.318.1.1.13.6NodeairIRGen3
1.3.6.1.4.1.318.1.1.13.6.1NodeairIRG3Ident
1.3.6.1.4.1.318.1.1.13.6.1.1ScalarairIRG3IdentTableSizeread-onlymandatoryThe ident table size.
1.3.6.1.4.1.318.1.1.13.6.1.2TableairIRG3IdentTablenot-accessiblemandatoryAllows to get ident information of current RDU and its assigned CM's.
1.3.6.1.4.1.318.1.1.13.6.1.2.1RowairIRG3IdentEntrynot-accessiblemandatoryThe ident table entry.
1.3.6.1.4.1.318.1.1.13.6.1.2.1.1ColumnairIRG3IdentIndexread-onlymandatoryIndex of ident table.
1.3.6.1.4.1.318.1.1.13.6.1.2.1.2ColumnairIRG3IdentNameread-writemandatoryA character string identifying the unit name.
1.3.6.1.4.1.318.1.1.13.6.1.2.1.3ColumnairIRG3IdentLocationread-writemandatoryA character string identifying the unit location.
1.3.6.1.4.1.318.1.1.13.6.1.2.1.4ColumnairIRG3IdentModelNumberread-onlymandatoryA character string identifying the unit model number.
1.3.6.1.4.1.318.1.1.13.6.1.2.1.5ColumnairIRG3IdentSerialNumberread-onlymandatoryA character string identifying the unit serial number.
1.3.6.1.4.1.318.1.1.13.6.1.2.1.6ColumnairIRG3IdentFirmwareRevisionread-onlymandatoryA character string identifying the unit firmware version.
1.3.6.1.4.1.318.1.1.13.6.1.2.1.7ColumnairIRG3IdentHardwareRevisionread-onlymandatoryA character string identifying the unit controller hardware revision.
1.3.6.1.4.1.318.1.1.13.6.1.2.1.8ColumnairIRG3IdentManufactureDateread-onlymandatoryA character string identifying the unit manufacture date.
1.3.6.1.4.1.318.1.1.13.6.1.2.1.9ColumnairIRG3IdentRDUSysOIDread-onlymandatoryThis OID contains an OID path to the RDU data.
1.3.6.1.4.1.318.1.1.13.6.1.2.1.10ColumnairIRG3IdentCMSysOIDread-onlymandatoryThis OID contains an OID path to the cooling module data.
1.3.6.1.4.1.318.1.1.13.6.1.2.1.11ColumnairIRG3IdentGroupSysOIDread-onlymandatoryThis OID contains an OID path to the group data.
1.3.6.1.4.1.318.1.1.13.6.2NodeairIRG3Group
1.3.6.1.4.1.318.1.1.13.6.2.1ScalarairIRG3GroupTableSizeread-onlymandatoryThe group table size.
1.3.6.1.4.1.318.1.1.13.6.2.2TableairIRG3GroupStatusTablenot-accessiblemandatoryAllows to get group status information.
1.3.6.1.4.1.318.1.1.13.6.2.2.1RowairIRG3GroupStatusEntrynot-accessiblemandatoryThe group staus table entry.
1.3.6.1.4.1.318.1.1.13.6.2.2.1.1ColumnairIRG3GroupStatusIndexread-onlymandatoryIndex of group status table.
1.3.6.1.4.1.318.1.1.13.6.2.2.1.2ColumnairIRG3GroupStatusCoolOutputread-onlymandatoryThe group cooling output in tenths of kilowatts (kW). Returns (-1) if not supported.
1.3.6.1.4.1.318.1.1.13.6.2.2.1.3ColumnairIRG3GroupStatusCoolDemandread-onlymandatoryThe group cooling demand in tenths of kilowatts (kW). Returns (-1) if not supported.
1.3.6.1.4.1.318.1.1.13.6.2.2.1.4ColumnairIRG3GroupStatusAirFlowUSread-onlymandatoryThe group air flow in cubic feet per minute (CFM). Returns (-1) if not supported.
1.3.6.1.4.1.318.1.1.13.6.2.2.1.5ColumnairIRG3GroupStatusAirFlowMetricread-onlymandatoryThe group air flow in liters per second (L/s). Returns (-1) if not supported.
1.3.6.1.4.1.318.1.1.13.6.2.2.1.6ColumnairIRG3GroupStatusMaxRackInletTempUSread-onlymandatoryThe group maximum rack inlet temperature in tenths of degrees Fahrenheit. Returns (-1) if not supported.
1.3.6.1.4.1.318.1.1.13.6.2.2.1.7ColumnairIRG3GroupStatusMaxRackInletTempMetricread-onlymandatoryThe group maximum rack inlet temperature in tenths of degrees Celsius. Returns (-1) if not supported.
1.3.6.1.4.1.318.1.1.13.6.2.2.1.8ColumnairIRG3GroupStatusMinRackInletTempUSread-onlymandatoryThe group minimum rack inlet temperature in tenths of degrees Fahrenheit. Returns (-1) if not supported.
1.3.6.1.4.1.318.1.1.13.6.2.2.1.9ColumnairIRG3GroupStatusMinRackInletTempMetricread-onlymandatoryThe group minimum rack inlet temperature in tenths of degrees Celsius. Returns (-1) if not supported.
1.3.6.1.4.1.318.1.1.13.6.2.2.1.10ColumnairIRG3GroupStatusMaxReturnAirTempUSread-onlymandatoryThe group maximum return air temperature in tenths of degrees Fahrenheit. Returns (-1) if not supported.
1.3.6.1.4.1.318.1.1.13.6.2.2.1.11ColumnairIRG3GroupStatusMaxReturnAirTempMetricread-onlymandatoryThe group maximum return air temperature in tenths of degrees Celsius. Returns (-1) if not supported.
1.3.6.1.4.1.318.1.1.13.6.2.2.1.12ColumnairIRG3GroupStatusMinReturnAirTempUSread-onlymandatoryThe group minimum return air temperature in tenths of degrees Fahrenheit. Returns (-1) if not supported.
1.3.6.1.4.1.318.1.1.13.6.2.2.1.13ColumnairIRG3GroupStatusMinReturnAirTempMetricread-onlymandatoryThe group minimum return air temperature in tenths of degrees Celsius. Returns (-1) if not supported.
1.3.6.1.4.1.318.1.1.13.6.2.2.1.14ColumnairIRG3GroupStatusAvgSupplyTempUSread-onlymandatoryThe group average supply air temperature in tenths of degrees Fahrenheit. Returns (-1) if not supported.
1.3.6.1.4.1.318.1.1.13.6.2.2.1.15ColumnairIRG3GroupStatusAvgSupplyTempMetricread-onlymandatoryThe group average supply air temperature in tenths of degrees Celsius. Returns (-1) if not supported.
1.3.6.1.4.1.318.1.1.13.6.2.2.1.16ColumnairIRG3GroupStatusAvgReturnTempUSread-onlymandatoryThe group average return air temperature in tenths of degrees Fahrenheit. Returns (-1) if not supported.
1.3.6.1.4.1.318.1.1.13.6.2.2.1.17ColumnairIRG3GroupStatusAvgReturnTempMetricread-onlymandatoryThe group average return air temperature in tenths of degrees Celsius. Returns (-1) if not supported.
1.3.6.1.4.1.318.1.1.13.6.2.2.1.18ColumnairIRG3GroupStatusAvgFanSpeedread-onlymandatoryThe group average fan speed in revolutions per minute (RPM). Returns (-1) if not supported.
1.3.6.1.4.1.318.1.1.13.6.2.2.1.19ColumnairIRG3GroupStatusAvgAirFlowUSread-onlymandatoryThe group average air flow in cubic feet per minute (CFM). Returns (-1) if not supported.
1.3.6.1.4.1.318.1.1.13.6.2.2.1.20ColumnairIRG3GroupStatusAvgAirFlowMetricread-onlymandatoryThe group average air flow in liters per second (L/s). Returns (-1) if not supported.
1.3.6.1.4.1.318.1.1.13.6.2.2.1.21ColumnairIRG3GroupStatusTotalAirFlowUSread-onlymandatoryThe group total air flow in cubic feet per minute (CFM). Returns (-1) if not supported.
1.3.6.1.4.1.318.1.1.13.6.2.2.1.22ColumnairIRG3GroupStatusTotalAirFlowMetricread-onlymandatoryThe group total air flow in liters per second (L/s). Returns (-1) if not supported.
1.3.6.1.4.1.318.1.1.13.6.2.3TableairIRG3GroupSetpointsTablenot-accessiblemandatoryAllows to access the group setpoints.
1.3.6.1.4.1.318.1.1.13.6.2.3.1RowairIRG3GroupSetpointsEntrynot-accessiblemandatoryThe group setpoints table entry.
1.3.6.1.4.1.318.1.1.13.6.2.3.1.1ColumnairIRG3GroupSetpointsIndexread-onlymandatoryIndex of group setpoints table.
1.3.6.1.4.1.318.1.1.13.6.2.3.1.2ColumnairIRG3GroupSetpointsCoolSetpointUSread-writemandatoryGroup cooling setpoint in tenths of degrees Fahrenheit.
1.3.6.1.4.1.318.1.1.13.6.2.3.1.3ColumnairIRG3GroupSetpointsCoolSetpointMetricread-writemandatoryGroup cooling setpoint in tenths of degrees Celsius.
1.3.6.1.4.1.318.1.1.13.6.2.3.1.4ColumnairIRG3GroupSetpointsCoolDeadbandUSread-writemandatoryGroup cooling deadband in tenths of degrees Fahrenheit. Returns (-1) if not supported.
1.3.6.1.4.1.318.1.1.13.6.2.3.1.5ColumnairIRG3GroupSetpointsCoolDeadbandMetricread-writemandatoryGroup cooling deadband in tenths of degrees Celsius. Returns (-1) if not supported.
1.3.6.1.4.1.318.1.1.13.6.2.3.1.6ColumnairIRG3GroupSetpointsFanSpeedPreferenceread-writemandatoryThe group preferred fan speed setting.
1.3.6.1.4.1.318.1.1.13.6.2.3.1.7ColumnairIRG3GroupSetpointsSupplyAirSetpointUSread-writemandatoryGroup supply air setpoint in tenths of degrees Fahrenheit.
1.3.6.1.4.1.318.1.1.13.6.2.3.1.8ColumnairIRG3GroupSetpointsSupplyAirSetpointMetricread-writemandatoryGroup supply air setpoint in tenths of degrees Celsius.
1.3.6.1.4.1.318.1.1.13.6.2.3.1.9ColumnairIRG3GroupSetpointsAirFlowControlread-writemandatoryThe group air flow control.
1.3.6.1.4.1.318.1.1.13.6.2.3.1.10ColumnairIRG3GroupSetpointsLightingOnTimeread-writemandatoryThe group lighting on time in minutes.
1.3.6.1.4.1.318.1.1.13.6.2.4TableairIRG3GroupConfigTablenot-accessiblemandatoryAllows to access group configuration table.
1.3.6.1.4.1.318.1.1.13.6.2.4.1RowairIRG3GroupConfigEntrynot-accessiblemandatoryThe group config table entry.
1.3.6.1.4.1.318.1.1.13.6.2.4.1.1ColumnairIRG3GroupConfigIndexread-onlymandatoryIndex of group config table.
1.3.6.1.4.1.318.1.1.13.6.2.4.1.2ColumnairIRG3GroupConfigNumberofCoolingUnitsread-writemandatoryThe number of cooling units.
1.3.6.1.4.1.318.1.1.13.6.2.4.1.3ColumnairIRG3GroupConfigConfigurationTyperead-writemandatoryThe group configuration type. The spot configuration type is not supported. Returns (-1) if not supported.
1.3.6.1.4.1.318.1.1.13.6.2.4.1.4ColumnairIRG3GroupConfigCapacityControlTyperead-writemandatoryThe group capacity control. Returns (-1) if not supported.
1.3.6.1.4.1.318.1.1.13.6.2.4.1.5ColumnairIRG3GroupConfigFanSpeedControlread-writemandatoryThe group fan speed control.
1.3.6.1.4.1.318.1.1.13.6.2.4.1.6ColumnairIRG3GroupConfigCoolGainPread-writemandatoryThe gain component of the PID in hundredths.
1.3.6.1.4.1.318.1.1.13.6.2.4.1.7ColumnairIRG3GroupConfigCoolResetRateIread-writemandatoryThe integral component of the PID in hundredths.
1.3.6.1.4.1.318.1.1.13.6.2.4.1.8ColumnairIRG3GroupConfigCoolDerivativeDread-writemandatoryThe derivative component of the PID in hundredths.
1.3.6.1.4.1.318.1.1.13.6.2.4.1.9ColumnairIRG3GroupConfigCoolPIDResetread-writemandatoryWill reset the PID coefficients back to the factory defaults. Readback is not supported, returns -1.
1.3.6.1.4.1.318.1.1.13.6.2.4.1.10ColumnairIRG3GroupConfigNumberofBackupUnitsread-writemandatoryThe number of backup units.
1.3.6.1.4.1.318.1.1.13.6.2.4.1.11ColumnairIRG3GroupConfigRuntimeBalancingEnableread-writemandatoryEnable or disable runtime balancing feature.
1.3.6.1.4.1.318.1.1.13.6.2.4.1.12ColumnairIRG3GroupConfigLoadAssistEnableread-writemandatoryEnable or disable load assist feature.
1.3.6.1.4.1.318.1.1.13.6.3NodeairIRG3Alarms
1.3.6.1.4.1.318.1.1.13.6.3.1ScalarairIRG3AlarmsTableSizeread-onlymandatoryThe number of active alarms in the airIRG3AlarmsTable.
1.3.6.1.4.1.318.1.1.13.6.3.2TableairIRG3AlarmsTablenot-accessiblemandatoryTable of active alarms for the device.
1.3.6.1.4.1.318.1.1.13.6.3.2.1RowairIRG3AlarmsEntrynot-accessiblemandatoryAlarms specification
1.3.6.1.4.1.318.1.1.13.6.3.2.1.1ColumnairIRG3AlarmsIndexread-onlymandatoryAlarm index.
1.3.6.1.4.1.318.1.1.13.6.3.2.1.2ColumnairIRG3AlarmsEventCoderead-onlymandatoryEvent Code for the alarm. Returns (-1) if not supported.
1.3.6.1.4.1.318.1.1.13.6.3.2.1.3ColumnairIRG3AlarmsDescriptionread-onlymandatoryDescription of the alarm. Returns (-1) if not supported.
1.3.6.1.4.1.318.1.1.13.6.4NodeairIRG3RDU
1.3.6.1.4.1.318.1.1.13.6.4.1ScalarairIRG3RDUTableSizeread-onlymandatoryThe RDU table size.
1.3.6.1.4.1.318.1.1.13.6.4.2TableairIRG3RDUStatusTablenot-accessiblemandatoryAllows to access RDU status table.
1.3.6.1.4.1.318.1.1.13.6.4.2.1RowairIRG3RDUStatusEntrynot-accessiblemandatoryThe RDU status table entry.
1.3.6.1.4.1.318.1.1.13.6.4.2.1.1ColumnairIRG3RDUStatusDeviceIndexread-onlymandatoryIndex of RDU status table.
1.3.6.1.4.1.318.1.1.13.6.4.2.1.2ColumnairIRG3RDUIDread-onlymandatoryThe current RDU ID (1 to F). Configured RDU only shall display ID, else return -1.
1.3.6.1.4.1.318.1.1.13.6.4.2.1.3ColumnairIRG3RDUStatusOnReadyStandbyread-onlymandatoryThe RDU current status.
1.3.6.1.4.1.318.1.1.13.6.4.2.1.4ColumnairIRG3RDUStatusOperatingModeread-onlymandatoryThe RDU actual operating mode.
1.3.6.1.4.1.318.1.1.13.6.4.2.1.5ColumnairIRG3RDUStatusLeadPumpread-onlymandatoryThe RDU lead pump.
1.3.6.1.4.1.318.1.1.13.6.4.2.1.6ColumnairIRG3RDUStatusStartupDelayread-onlymandatoryThe RDU start up delay in seconds.
1.3.6.1.4.1.318.1.1.13.6.4.2.1.7ColumnairIRG3RDUStatusPumpChangeOverIntervalread-onlymandatoryThe RDU pump change over interval in days.
1.3.6.1.4.1.318.1.1.13.6.4.2.1.8ColumnairIRG3RDUStatusStopOnLeakDetectread-onlymandatoryThe RDU status of stop on leak detect.
1.3.6.1.4.1.318.1.1.13.6.4.2.1.9ColumnairIRG3RDUStatusPowerSourceread-onlymandatoryThe RDU power source status.
1.3.6.1.4.1.318.1.1.13.6.4.2.1.10ColumnairIRG3RDUStatusTotalRDUOutputPowerread-onlymandatoryThe RDU output power in tenths of kilowatts (kW).
1.3.6.1.4.1.318.1.1.13.6.4.2.1.11ColumnairIRG3RDUStatusInletWaterTempUSread-onlymandatoryThe RDU inlet water temperature in tenths of degrees Fahrenheit.
1.3.6.1.4.1.318.1.1.13.6.4.2.1.12ColumnairIRG3RDUStatusInletWaterTempMetricread-onlymandatoryThe RDU inlet water temperature in tenths of degrees Celsius.
1.3.6.1.4.1.318.1.1.13.6.4.2.1.13ColumnairIRG3RDUStatusOutletWaterTempUSread-onlymandatoryThe RDU outlet water temperature in tenths of degrees Fahrenheit.
1.3.6.1.4.1.318.1.1.13.6.4.2.1.14ColumnairIRG3RDUStatusOutletWaterTempMetricread-onlymandatoryThe RDU outlet water temperature in tenths of degrees Celsius.
1.3.6.1.4.1.318.1.1.13.6.4.2.1.15ColumnairIRG3RDUStatusCondenserSaturationTempUSread-onlymandatoryThe RDU condenser saturation temperature in tenths of degrees Fahrenheit.
1.3.6.1.4.1.318.1.1.13.6.4.2.1.16ColumnairIRG3RDUStatusCondenserSaturationTempMetricread-onlymandatoryThe RDU condenser saturation temperature in tenths of degrees Celsius.
1.3.6.1.4.1.318.1.1.13.6.4.2.1.17ColumnairIRG3RDUStatusDewPointTempUSread-onlymandatoryThe RDU dew point temperature in tenths of degrees Fahrenheit.
1.3.6.1.4.1.318.1.1.13.6.4.2.1.18ColumnairIRG3RDUStatusDewPointTempMetricread-onlymandatoryThe RDU dew point temperature in tenths of degrees Celsius.
1.3.6.1.4.1.318.1.1.13.6.4.2.1.19ColumnairIRG3RDUStatusPumpOutletTempUSread-onlymandatoryThe RDU pump outlet temperature in tenths of degrees Fahrenheit.
1.3.6.1.4.1.318.1.1.13.6.4.2.1.20ColumnairIRG3RDUStatusPumpOutletTempMetricread-onlymandatoryThe RDU pump outlet temperature in tenths of degrees Celsius.
1.3.6.1.4.1.318.1.1.13.6.4.2.1.21ColumnairIRG3RDUStatusSubcoolerOutletTempUSread-onlymandatoryThe RDU sub cooler outlet temperature in tenths of degrees Fahrenheit.
1.3.6.1.4.1.318.1.1.13.6.4.2.1.22ColumnairIRG3RDUStatusSubcoolerOutletTempMetricread-onlymandatoryThe RDU sub cooler outlet temperature in tenths of degrees Celsius.
1.3.6.1.4.1.318.1.1.13.6.4.2.1.23ColumnairIRG3RDUStatusCondenserOutletTempUSread-onlymandatoryThe RDU condenser outlet temperature in tenths of degrees Fahrenheit.
1.3.6.1.4.1.318.1.1.13.6.4.2.1.24ColumnairIRG3RDUStatusCondenserOutletTempMetricread-onlymandatoryThe RDU condenser outlet temperature in tenths of degrees Celsius.
1.3.6.1.4.1.318.1.1.13.6.4.2.1.25ColumnairIRG3RDUStatusCondenserInletTempUSread-onlymandatoryThe RDU condenser inlet temperature in tenths of degrees Fahrenheit.
1.3.6.1.4.1.318.1.1.13.6.4.2.1.26ColumnairIRG3RDUStatusCondenserInletTempMetricread-onlymandatoryThe RDU condenser inlet temperature in tenths of degrees Celsius.
1.3.6.1.4.1.318.1.1.13.6.4.2.1.27ColumnairIRG3RDUStatusCondenserOutletPressureUSread-onlymandatoryThe RDU condenser outlet pressure in pounds per square inch (PSI).
1.3.6.1.4.1.318.1.1.13.6.4.2.1.28ColumnairIRG3RDUStatusCondenserOutletPressureMetricread-onlymandatoryThe RDU condenser outlet pressure in kiloPascals (KPa).
1.3.6.1.4.1.318.1.1.13.6.4.2.1.29ColumnairIRG3RDUStatusPump1HeadPressureUSread-onlymandatoryThe RDU Pump 1 head pressure in pounds per square inch (PSI).
1.3.6.1.4.1.318.1.1.13.6.4.2.1.30ColumnairIRG3RDUStatusPump1HeadPressureMetricread-onlymandatoryThe RDU Pump 1 head pressure in kiloPascals (KPa).
1.3.6.1.4.1.318.1.1.13.6.4.2.1.31ColumnairIRG3RDUStatusPump2HeadPressureUSread-onlymandatoryThe RDU Pump 2 head pressure in pounds per square inch (PSI).
1.3.6.1.4.1.318.1.1.13.6.4.2.1.32ColumnairIRG3RDUStatusPump2HeadPressureMetricread-onlymandatoryThe RDU Pump 2 head pressure in kiloPascals (KPa).
1.3.6.1.4.1.318.1.1.13.6.4.2.1.33ColumnairIRG3RDUStatusPump1Speedread-onlymandatoryThe RDU Pump 1 speed in revolutions per minute (RPM).
1.3.6.1.4.1.318.1.1.13.6.4.2.1.34ColumnairIRG3RDUStatusPump2Speedread-onlymandatoryThe RDU Pump 2 speed in revolutions per minute (RPM).
1.3.6.1.4.1.318.1.1.13.6.4.2.1.35ColumnairIRG3RDUStatusCWValvePositionread-onlymandatoryThe RDU CW Valve position in % open
1.3.6.1.4.1.318.1.1.13.6.4.2.1.36ColumnairIRG3RDUStatusReceiverLiquidLevelread-onlymandatoryThe RDU receiver liquid level in % Full
1.3.6.1.4.1.318.1.1.13.6.4.2.1.37ColumnairIRG3RDUStatusDCPowerSupply1Currentread-onlymandatoryThe RDU DC Power Supply 1 Current in Amps
1.3.6.1.4.1.318.1.1.13.6.4.2.1.38ColumnairIRG3RDUStatusDCPowerSupply2Currentread-onlymandatoryThe RDU DC Power Supply 2 Current in Amps
1.3.6.1.4.1.318.1.1.13.6.4.2.1.39ColumnairIRG3RDUStatusTotalDCPowerSupplyCurrentread-onlymandatoryThe RDU Total DC Power Supply Current in Amps
1.3.6.1.4.1.318.1.1.13.6.4.2.1.40ColumnairIRG3RDUStatusInputStateread-onlymandatoryThe RDU Input state.
1.3.6.1.4.1.318.1.1.13.6.4.2.1.41ColumnairIRG3RDUStatusOutputStateread-onlymandatoryThe RDU Output state
1.3.6.1.4.1.318.1.1.13.6.4.2.1.42ColumnairIRG3RDUStatusByPassValvePositionread-onlymandatoryThe RDU By Pass Valve position in % open
1.3.6.1.4.1.318.1.1.13.6.4.2.1.43ColumnairIRG3RDUStatusRefrigerantLeakDetectorread-onlymandatoryThe RDU refrigerant leak detector status.
1.3.6.1.4.1.318.1.1.13.6.4.3TableairIRG3RDURunHoursTablenot-accessiblemandatoryAllows to access RDU run hours table.
1.3.6.1.4.1.318.1.1.13.6.4.3.1RowairIRG3RDURunHoursEntrynot-accessiblemandatoryThe RDU run hours table entry.
1.3.6.1.4.1.318.1.1.13.6.4.3.1.1ColumnairIRG3RDURunHoursDeviceIndexread-onlymandatoryIndex of RDU run hours table.
1.3.6.1.4.1.318.1.1.13.6.4.3.1.2ColumnairIRG3RDURunHoursRDUIDread-onlymandatoryThe current RDU ID (1 to F). Configured RDU only shall display ID, else return -1.
1.3.6.1.4.1.318.1.1.13.6.4.3.1.3ColumnairIRG3RDURunHoursPump1read-onlymandatoryThe RDU run hours of Pump 1.
1.3.6.1.4.1.318.1.1.13.6.4.3.1.4ColumnairIRG3RDURunHoursPump2read-onlymandatoryThe RDU run hours of Pump 2.
1.3.6.1.4.1.318.1.1.13.6.4.3.1.5ColumnairIRG3RDURunHoursPowerSupply1read-onlymandatoryThe RDU run hours of power supply 1.
1.3.6.1.4.1.318.1.1.13.6.4.3.1.6ColumnairIRG3RDURunHoursPowerSupply2read-onlymandatoryThe RDU run hours of power supply 2.
1.3.6.1.4.1.318.1.1.13.6.4.4TableairIRG3RDUServiceIntervalsTablenot-accessiblemandatoryAllows to access RDU service intervals table.
1.3.6.1.4.1.318.1.1.13.6.4.4.1RowairIRG3RDUServiceIntervalsEntrynot-accessiblemandatoryThe service interval table entry.
1.3.6.1.4.1.318.1.1.13.6.4.4.1.1ColumnairIRG3RDUServiceIntervalsDeviceIndexread-onlymandatoryIndex of service interval table.
1.3.6.1.4.1.318.1.1.13.6.4.4.1.2ColumnairIRG3RDUServiceIntervalsRDUIDread-onlymandatoryThe current RDU ID (1 to F). Configured RDU only shall display ID, else return -1.
1.3.6.1.4.1.318.1.1.13.6.4.4.1.3ColumnairIRG3RDUServiceIntervalsAirFilterIntervalread-writemandatoryThe RDU service interval for air filter in hours. Returns -1 if not supported.
1.3.6.1.4.1.318.1.1.13.6.4.4.1.4ColumnairIRG3RDUServiceIntervalsAirFilterAlarmread-writemandatoryThe RDU service interval air filter alarm status. Returns -1 if not supported.
1.3.6.1.4.1.318.1.1.13.6.4.5TableairIRG3RDUThresholdsTablenot-accessiblemandatoryAllows to access RDU thresholds table.
1.3.6.1.4.1.318.1.1.13.6.4.5.1RowairIRG3RDUThresholdsEntrynot-accessiblemandatoryThe RDU thresholds table entry.
1.3.6.1.4.1.318.1.1.13.6.4.5.1.1ColumnairIRG3RDUThresholdsDeviceIndexread-onlymandatoryIndex of RDU thresholds table.
1.3.6.1.4.1.318.1.1.13.6.4.5.1.2ColumnairIRG3RDUThresholdsRDUIDread-onlymandatoryThe current RDU ID (1 to F). Configured RDU only shall display ID, else return -1.
1.3.6.1.4.1.318.1.1.13.6.4.5.1.3ColumnairIRG3RDUThresholdsEnteringFluidTempHighUSread-writemandatoryThe RDU threshold for entering fluid temperature in tenths of degrees Fahrenheit.
1.3.6.1.4.1.318.1.1.13.6.4.5.1.4ColumnairIRG3RDUThresholdsEnteringFluidTempHighMetricread-writemandatoryThe RDU threshold for entering fluid temperature in tenths of degrees Celsius.
1.3.6.1.4.1.318.1.1.13.6.4.6TableairIRG3RDUSetpointsTablenot-accessiblemandatoryAllows to access RDU set points table.
1.3.6.1.4.1.318.1.1.13.6.4.6.1RowairIRG3RDUSetpointsEntrynot-accessiblemandatoryThe RDU set points table entry.
1.3.6.1.4.1.318.1.1.13.6.4.6.1.1ColumnairIRG3RDUSetpointsDeviceIndexread-onlymandatoryIndex of RDU set points table.
1.3.6.1.4.1.318.1.1.13.6.4.7TableairIRG3RDUConfigTablenot-accessiblemandatoryAllows to access RDU configuration table.
1.3.6.1.4.1.318.1.1.13.6.4.7.1RowairIRG3RDUConfigEntrynot-accessiblemandatoryThe RDU configuration table entry.
1.3.6.1.4.1.318.1.1.13.6.4.7.1.1ColumnairIRG3RDUConfigDeviceIndexread-onlymandatoryIndex of RDU configuration table.
1.3.6.1.4.1.318.1.1.13.6.4.7.1.2ColumnairIRG3RDUConfigRDUIDread-onlymandatoryThe current RDU ID (1 to F). Configured RDU only shall display ID, else return -1.
1.3.6.1.4.1.318.1.1.13.6.4.7.1.3ColumnairIRG3RDUConfigStopOnLeakDetectread-writemandatoryThe RDU stop on leak detect set.
1.3.6.1.4.1.318.1.1.13.6.4.7.1.4ColumnairIRG3RDUConfigStartupDelayread-writemandatoryThe RDU start up delay in seconds.
1.3.6.1.4.1.318.1.1.13.6.4.7.1.5ColumnairIRG3RDUConfigPumpChangeOverIntervalread-writemandatoryThe RDU pump change over interval in days.
1.3.6.1.4.1.318.1.1.13.6.4.7.1.6ColumnairIRG3RDUConfigPowerSourceread-writemandatoryThe RDU power source.
1.3.6.1.4.1.318.1.1.13.6.4.7.1.7ColumnairIRG3RDUConfigOutputSourceread-writemandatoryThe RDU output source.
1.3.6.1.4.1.318.1.1.13.6.4.7.1.8ColumnairIRG3RDUConfigInputNormalStateread-writemandatoryThe RDU Input Normal State.
1.3.6.1.4.1.318.1.1.13.6.4.7.1.9ColumnairIRG3RDUConfigOutputNormalStateread-writemandatoryThe RDU Output Normal State.
1.3.6.1.4.1.318.1.1.13.6.4.7.1.10ColumnairIRG3RDUConfigByPassValveEnabledread-writemandatoryThe RDU By Pass Valve Enabled State.
1.3.6.1.4.1.318.1.1.13.6.4.7.1.11ColumnairIRG3RDUConfigRefrigerantLeakDetectorEnabledread-writemandatoryThe RDU Refrigerant Leak Detector Enabled State.
1.3.6.1.4.1.318.1.1.13.6.4.7.1.12ColumnairIRG3RDUConfigCalibrateRefrigerantLeakDetectorread-writemandatoryThis parameter allows to calibrate the RDU Refrigerant Leak Detector and is write only. The read returns -1. Only 'yes' is supported.
1.3.6.1.4.1.318.1.1.13.6.4.7.1.13ColumnairIRG3RDUConfigOnReadyStandbyread-writemandatoryThis parameter allows to configure RDU on/standby parameter. Ready is currently not supported. If unsupported returns -1.
1.3.6.1.4.1.318.1.1.13.6.5NodeairIRG3CM
1.3.6.1.4.1.318.1.1.13.6.5.1ScalarairIRG3CMTableSizeread-onlymandatoryThe cooling module table size.
1.3.6.1.4.1.318.1.1.13.6.5.2TableairIRG3CMStatusTablenot-accessiblemandatoryAllows to access CM status table.
1.3.6.1.4.1.318.1.1.13.6.5.2.1RowairIRG3CMStatusEntrynot-accessiblemandatoryThe CM status table entry.
1.3.6.1.4.1.318.1.1.13.6.5.2.1.1ColumnairIRG3CMStatusDeviceIndexread-onlymandatoryIndex of CM status table.
1.3.6.1.4.1.318.1.1.13.6.5.2.1.2ColumnairIRG3CMStatusCMIDread-onlymandatoryThe CM ID (RDU Number - Group Number - CM Unit Number).
1.3.6.1.4.1.318.1.1.13.6.5.2.1.3ColumnairIRG3CMStatusOperatingModeread-onlymandatoryThe current operating mode of the CM.
1.3.6.1.4.1.318.1.1.13.6.5.2.1.4ColumnairIRG3CMStatusUnitTyperead-onlymandatoryThe current CM unit type.
1.3.6.1.4.1.318.1.1.13.6.5.2.1.5ColumnairIRG3CMStatusRackInletTempUSread-onlymandatoryThe CM rack inlet temperature in tenths of degrees Fahrenheit.
1.3.6.1.4.1.318.1.1.13.6.5.2.1.6ColumnairIRG3CMStatusRackInletTempMetricread-onlymandatoryThe CM rack inlet temperature in tenths of degrees Celsius.
1.3.6.1.4.1.318.1.1.13.6.5.2.1.7ColumnairIRG3CMStatusReturnAirTempUSread-onlymandatoryThe CM return air temperature in tenths of degrees Fahrenheit.
1.3.6.1.4.1.318.1.1.13.6.5.2.1.8ColumnairIRG3CMStatusReturnAirTempMetricread-onlymandatoryThe CM return air temperature in tenths of degrees Celsius.
1.3.6.1.4.1.318.1.1.13.6.5.2.1.9ColumnairIRG3CMStatusLiquidTempUSread-onlymandatoryThe CM liquid temperature in tenths of degrees Fahrenheit.
1.3.6.1.4.1.318.1.1.13.6.5.2.1.10ColumnairIRG3CMStatusLiquidTempMetricread-onlymandatoryThe CM liquid temperature in tenths of degrees Celsius.
1.3.6.1.4.1.318.1.1.13.6.5.2.1.11ColumnairIRG3CMStatusVaporTempUSread-onlymandatoryThe CM vapor temperature in tenths of degrees Fahrenheit.
1.3.6.1.4.1.318.1.1.13.6.5.2.1.12ColumnairIRG3CMStatusVaporTempMetricread-onlymandatoryThe CM vapor temperature in tenths of degrees Celsius.
1.3.6.1.4.1.318.1.1.13.6.5.2.1.13ColumnairIRG3CMStatusEvaporatorTempUSread-onlymandatoryThe CM saturation temperature in tenths of degrees Fahrenheit.
1.3.6.1.4.1.318.1.1.13.6.5.2.1.14ColumnairIRG3CMStatusEvaporatorTempMetricread-onlymandatoryThe CM saturation temperature in tenths of degrees Celsius.
1.3.6.1.4.1.318.1.1.13.6.5.2.1.15ColumnairIRG3CMStatusLiquidInletPressureUSread-onlymandatoryThe CM Liquid Inlet pressure in pounds per square inch (PSI).
1.3.6.1.4.1.318.1.1.13.6.5.2.1.16ColumnairIRG3CMStatusLiquidInletPressureMetricread-onlymandatoryThe CM Liquid Inlet pressure in kiloPascals (kPa).
1.3.6.1.4.1.318.1.1.13.6.5.2.1.17ColumnairIRG3CMStatusVaporOutletPressureUSread-onlymandatoryThe CM Vapor Outlet pressure in pounds per square inch (PSI).
1.3.6.1.4.1.318.1.1.13.6.5.2.1.18ColumnairIRG3CMStatusVaporOutletPressureMetricread-onlymandatoryThe CM Vapor Outlet pressure in kiloPascals (kPa).
1.3.6.1.4.1.318.1.1.13.6.5.2.1.19ColumnairIRG3CMStatusExpansionValvePositionread-onlymandatoryThe CM expansion valve position in % open
1.3.6.1.4.1.318.1.1.13.6.5.2.1.20ColumnairIRG3CMStatusEPRValvePositionread-onlymandatoryThe CM Evaporator Pressure Regulator Valve Position in tenths of percent open
1.3.6.1.4.1.318.1.1.13.6.5.2.1.21ColumnairIRG3CMStatusLocalDisplayOnOffEnabledread-onlymandatoryThe status of the on/off control on the CM local display.
1.3.6.1.4.1.318.1.1.13.6.5.2.1.22ColumnairIRG3CMStatusAverageFanSpeedread-onlymandatoryThe CM Average Fan Speed.
1.3.6.1.4.1.318.1.1.13.6.5.3TableairIRG3CMRunHoursTablenot-accessiblemandatoryAllows to access CM run hours table.
1.3.6.1.4.1.318.1.1.13.6.5.3.1RowairIRG3CMRunHoursEntrynot-accessiblemandatoryThe CM run hours table entry.
1.3.6.1.4.1.318.1.1.13.6.5.3.1.1ColumnairIRG3CMRunHoursDeviceIndexread-onlymandatoryIndex of CM run hours table.
1.3.6.1.4.1.318.1.1.13.6.5.3.1.2ColumnairIRG3CMRunHoursCMIDread-onlymandatoryThe CM ID (RDU Number - Group Number - CM Unit Number).
1.3.6.1.4.1.318.1.1.13.6.5.3.1.3ColumnairIRG3CMRunHoursFan1read-onlymandatoryThe CM run hours for Fan1. Returns (-1) if not appilcable.
1.3.6.1.4.1.318.1.1.13.6.5.3.1.4ColumnairIRG3CMRunHoursFan2read-onlymandatoryThe CM run hours for Fan2. Returns (-1) if not appilcable.
1.3.6.1.4.1.318.1.1.13.6.5.3.1.5ColumnairIRG3CMRunHoursFan3read-onlymandatoryThe CM run hours for Fan3. Returns (-1) if not appilcable.
1.3.6.1.4.1.318.1.1.13.6.5.3.1.6ColumnairIRG3CMRunHoursFan4read-onlymandatoryThe CM run hours for Fan4. Returns (-1) if not appilcable.
1.3.6.1.4.1.318.1.1.13.6.5.3.1.7ColumnairIRG3CMRunHoursFan5read-onlymandatoryThe CM run hours for Fan5. Returns (-1) if not appilcable.
1.3.6.1.4.1.318.1.1.13.6.5.3.1.8ColumnairIRG3CMRunHoursAirFilterread-onlymandatoryThe CM run hours for air filter.
1.3.6.1.4.1.318.1.1.13.6.5.4TableairIRG3CMServiceIntervalsTablenot-accessiblemandatoryAllows to access CM service intervals table.
1.3.6.1.4.1.318.1.1.13.6.5.4.1RowairIRG3CMServiceIntervalsEntrynot-accessiblemandatoryThe CM service interval table entry.
1.3.6.1.4.1.318.1.1.13.6.5.4.1.1ColumnairIRG3CMServiceIntervalsDeviceIndexread-onlymandatoryIndex of CM service intervals table.
1.3.6.1.4.1.318.1.1.13.6.5.4.1.2ColumnairIRG3CMServiceIntervalsCMIDread-onlymandatoryThe CM ID (RDU Number - Group Number - CM Unit Number).
1.3.6.1.4.1.318.1.1.13.6.5.4.1.3ColumnairIRG3CMServiceIntervalsAirFilterIntervalread-writemandatoryThe CM service interval for air filter in weeks. Supported only for RA. Returns -1 if not supported.
1.3.6.1.4.1.318.1.1.13.6.5.4.1.4ColumnairIRG3CMServiceIntervalsAirFilterAlarmread-writemandatoryThe CM service interval air filter alarm status. Supported only for RA. Returns -1 if not supported.
1.3.6.1.4.1.318.1.1.13.6.5.5TableairIRG3CMThresholdsTablenot-accessiblemandatoryAllows to access CM thresholds table.
1.3.6.1.4.1.318.1.1.13.6.5.5.1RowairIRG3CMThresholdsEntrynot-accessiblemandatoryThe CM thresholds table entry.
1.3.6.1.4.1.318.1.1.13.6.5.5.1.1ColumnairIRG3CMThresholdsDeviceIndexread-onlymandatoryIndex for CM thresholds table.
1.3.6.1.4.1.318.1.1.13.6.5.5.1.2ColumnairIRG3CMThresholdsCMIDread-onlymandatoryThe CM ID (RDU Number - Group Number - CM Unit Number).
1.3.6.1.4.1.318.1.1.13.6.5.5.1.3ColumnairIRG3CMThresholdsRackInletTempHighUSread-writemandatoryThe CM high threshold for rack inlet temperature in tenths of degrees Fahrenheit.
1.3.6.1.4.1.318.1.1.13.6.5.5.1.4ColumnairIRG3CMThresholdsRackInletTempHighMetricread-writemandatoryThe CM high threshold for rack inlet temperature in tenths of degrees Celsius.
1.3.6.1.4.1.318.1.1.13.6.5.5.1.5ColumnairIRG3CMThresholdsSupplyAirTempHighUSread-writemandatoryThe CM high threshold for supply air temperature in tenths of degrees Fahrenheit.
1.3.6.1.4.1.318.1.1.13.6.5.5.1.6ColumnairIRG3CMThresholdsSupplyAirTempHighMetricread-writemandatoryThe CM high threshold for supply air temperature in tenths of degrees Celsius.
1.3.6.1.4.1.318.1.1.13.6.5.5.1.7ColumnairIRG3CMThresholdsReturnAirTempHighUSread-writemandatoryThe CM high threshold for return air temperature in tenths of degrees Fahrenheit.
1.3.6.1.4.1.318.1.1.13.6.5.5.1.8ColumnairIRG3CMThresholdsReturnAirTempHighMetricread-writemandatoryThe CM high threshold for return air temperature in tenths of degrees Celsius.
1.3.6.1.4.1.318.1.1.13.6.5.6TableairIRG3CMSetpointsTablenot-accessiblemandatoryAllows to access CM set points table.
1.3.6.1.4.1.318.1.1.13.6.5.6.1RowairIRG3CMSetpointsEntrynot-accessiblemandatoryThe CM set points table entry.
1.3.6.1.4.1.318.1.1.13.6.5.6.1.1ColumnairIRG3CMSetpointsDeviceIndexread-onlymandatoryIndex of CM set points table.
1.3.6.1.4.1.318.1.1.13.6.5.7TableairIRG3CMConfigTablenot-accessiblemandatoryAllows to access CM configuration table.
1.3.6.1.4.1.318.1.1.13.6.5.7.1RowairIRG3CMConfigEntrynot-accessiblemandatoryThe CM configuration table entry.
1.3.6.1.4.1.318.1.1.13.6.5.7.1.1ColumnairIRG3CMConfigDeviceIndexread-onlymandatoryIndex of CM configuration table.
1.3.6.1.4.1.318.1.1.13.6.5.7.1.2ColumnairIRG3CMConfigCMIDread-onlymandatoryThe CM ID (RDU Number - Group Number - CM Unit Number).
1.3.6.1.4.1.318.1.1.13.6.5.7.1.3ColumnairIRG3CMConfigStopOnCoolFailread-writemandatoryEnable/Disable Stop On cool fail. When enabled, stops the unit if it detects that it is blowing warm air into the cold aisle.
1.3.6.1.4.1.318.1.1.13.6.5.7.1.4ColumnairIRG3CMConfigStartupDelayread-writemandatoryThe CM start up delay in seconds.
1.3.6.1.4.1.318.1.1.13.6.5.7.1.5ColumnairIRG3CMConfigRemoteOnStandbyread-writemandatoryThe CM configuration for operating mode.
1.3.6.1.4.1.318.1.1.13.6.5.7.1.6ColumnairIRG3CMConfigPowerSourceread-writemandatoryThe CM power source.
1.3.6.1.4.1.318.1.1.14NoderARU
1.3.6.1.4.1.318.1.1.14.1NoderARUIdent
1.3.6.1.4.1.318.1.1.14.1.1TablerARUIdentTablenot-accessiblemandatoryAllows for query of the individual devices. The number of entries is contained in the rARUStatusAruDeviceCount OID.
1.3.6.1.4.1.318.1.1.14.1.1.1RowrARUIdentEntrynot-accessiblemandatoryThe device to query.
1.3.6.1.4.1.318.1.1.14.1.1.1.1ColumnrARUIdentAruIndexread-onlymandatoryThe index to the ARU entry.
1.3.6.1.4.1.318.1.1.14.1.1.1.2ColumnrARUIdentNameread-onlymandatoryA character string identifying the device.
1.3.6.1.4.1.318.1.1.14.2NoderARUConfig
1.3.6.1.4.1.318.1.1.14.2.1TablerARUConfigTablenot-accessiblemandatoryAllows for configuration of the individual ARU devices accessible from this IP address. The number of entries is contained in the rARUStatusAruDeviceCount OID.
1.3.6.1.4.1.318.1.1.14.2.1.1RowrARUConfigEntrynot-accessiblemandatoryThe ARUs to configure.
1.3.6.1.4.1.318.1.1.14.2.1.1.1ColumnrARUConfigAruIndexread-onlymandatoryThe index to the ARU entry.
1.3.6.1.4.1.318.1.1.14.2.1.1.2ColumnrARUConfigAruNameread-writemandatoryThe name of the ARU.
1.3.6.1.4.1.318.1.1.14.2.1.1.3ColumnrARUConfigAruRemoteSetpointread-writemandatoryThis OID defines the desired base airflow of the ARU, and sets the speed of the ARU fans when the temperature override is inactive. Values specified in cfm (cu…
1.3.6.1.4.1.318.1.1.14.2.1.1.4ColumnrARUConfigAruTempOvrdEnableDisableread-writemandatoryThis OID is used to enable/disable the remote temperature override setting of the ARU. If this OID is set to 1, the remote setting for temperature override is …
1.3.6.1.4.1.318.1.1.14.2.1.1.5ColumnrARUConfigAruTempOvrdSetpointread-writemandatoryThis OID is the Temperature Override setpoint of the ARU. NOTE: -1 will be returned if the ARU is not communicating. Values are represented in whole number deg…
1.3.6.1.4.1.318.1.1.14.2.1.1.6ColumnrARUConfigAruMasterControlread-writemandatoryThis is the master on/off control for the ARU.
1.3.6.1.4.1.318.1.1.14.3NoderARUStatus
1.3.6.1.4.1.318.1.1.14.3.1ScalarrARUStatusAruDeviceCountread-onlymandatoryThe total number of ARUs accessible from this IP.
1.3.6.1.4.1.318.1.1.14.3.2ScalarrARUStatusSysTempUnitsread-onlymandatoryThe temperature scale used to display the temperature in the system, Celsius(1) or Fahrenheit(2). This setting is based on the system preferences configuration…
1.3.6.1.4.1.318.1.1.14.3.3TablerARUStatusTablenot-accessiblemandatoryAllows for query of the individual ARUs accessible from this IP address. The number of entries is contained in the rARUStatusAruDeviceCount OID.
1.3.6.1.4.1.318.1.1.14.3.3.1RowrARUStatusEntrynot-accessiblemandatoryThe ARUs to access.
1.3.6.1.4.1.318.1.1.14.3.3.1.1ColumnrARUStatusAruIndexread-onlymandatoryThe index to the ARU entry.
1.3.6.1.4.1.318.1.1.14.3.3.1.2ColumnrARUStatusAruNameread-onlymandatoryThe name of the ARU.
1.3.6.1.4.1.318.1.1.14.3.3.1.3ColumnrARUStatusAruRemoteSetpointread-onlymandatoryThis OID defines the desired base airflow of the ARU, or the speed of the ARU fans when the temperature override is inactive. See also the rARUConfigAruRemoteS…
1.3.6.1.4.1.318.1.1.14.3.3.1.4ColumnrARUStatusAruManualSetpointread-onlymandatoryManual operating setpoint of the ARU, which is set on the panel of the ARU. If the ARU doesn't have a manual , the OID will always return a value of aruRem (10…
1.3.6.1.4.1.318.1.1.14.3.3.1.5ColumnrARUStatusAruTemp1read-onlymandatoryARU temperature probe #1 reading. The summary exhaust temperature on 2nd generation ARUs. NOTE: -1 will be returned if the ARU is not communicating. Values are…
1.3.6.1.4.1.318.1.1.14.3.3.1.6ColumnrARUStatusAruTemp2read-onlymandatoryARU temperature probe #2 reading. The exhaust temperature in the upper plenum on 2nd generation ARUs. NOTE: -1 will be returned if the ARU is not communicating…
1.3.6.1.4.1.318.1.1.14.3.3.1.7ColumnrARUStatusAruTemp3read-onlymandatoryARU temperature probe #3 reading. The exhaust temperature in the lower plenum on 2nd generation ARUs. NOTE: -1 will be returned if the ARU is not communicating…
1.3.6.1.4.1.318.1.1.14.3.3.1.8ColumnrARUStatusAruTempOvrdEnableDisableread-onlymandatoryThis OID indicates whether the ARU remote temperature override is enabled or disabled. If this OID is a 1, the remote setting for temperature override is disab…
1.3.6.1.4.1.318.1.1.14.3.3.1.9ColumnrARUStatusAruTempOvrdSetpointread-onlymandatoryARU remote temperature override setpoint setting. NOTE: -1 will be returned if the ARU is not communicating. Values are represented in whole number degrees. Un…
1.3.6.1.4.1.318.1.1.14.3.3.1.10ColumnrARUStatusAruAlarmStateread-onlymandatoryAn ASCII string containing the 8 flags representing the current alarm state of the ARU. If the state of the ARU is unknown, this variable is set to 'UNKNOWN'. …
1.3.6.1.4.1.318.1.1.14.3.3.1.11ColumnrARUStatusAruCommStatusread-onlymandatoryThe state of communications to the device. commNeverDiscovered(1) indicates there has never been communications with this device. commsEstablished(2) indicates…
1.3.6.1.4.1.318.1.1.14.3.3.1.12ColumnrARUStatusAruTempOvrdStatusread-onlymandatorySpecifies whether the ARU is increasing airflow because exhaust air temperature has exceeded the setting specified in the rARUConfigAruTempOvrdSetpoint OID.
1.3.6.1.4.1.318.1.1.14.3.3.1.13ColumnrARUStatusAruMasterControlread-onlymandatoryThis is the master on/off control for the ARU.
1.3.6.1.4.1.318.1.1.14.3.3.1.14ColumnrARUStatusAruTotalAirflowread-onlymandatoryThe total airflow provided by the aru. Specified in cfm (cubic feet per minute). Can be converted to metric values using the conversion factor: 1 cfm = 1.70 m^…
1.3.6.1.4.1.318.1.1.14.4NoderARUFanStatus
1.3.6.1.4.1.318.1.1.14.4.1TablerARUFanStatusTablenot-accessiblemandatoryAllows for query of the individual devices. The number of entries is contained in the rARUStatusAruDeviceCount OID.
1.3.6.1.4.1.318.1.1.14.4.1.1RowrARUFanStatusEntrynot-accessiblemandatoryThe device to query.
1.3.6.1.4.1.318.1.1.14.4.1.1.1ColumnrARUFanStatusAruIndexread-onlymandatoryThe index to the ARU entry.
1.3.6.1.4.1.318.1.1.14.4.1.1.2ColumnrARUFanStatusNominalFanSpeedread-onlymandatoryThe nominal rotational speed (RPM) of the fans when they are operating at the 100% level.
1.3.6.1.4.1.318.1.1.14.4.1.1.3ColumnrARUFanStatusSelectedFanLevelread-onlymandatoryThe currently selected ARU speed level, specified in percent of full capacity.
1.3.6.1.4.1.318.1.1.14.4.1.1.4ColumnrARUFanStatusReplacementThresholdread-writemandatoryThreshold above which a run hour alarm will exist, indicating that it might be time to proactively replace a fan.
1.3.6.1.4.1.318.1.1.14.4.1.1.5ColumnrARUFanStatusFanIndexread-onlymandatoryThe index to an individual fan table entry.
1.3.6.1.4.1.318.1.1.14.4.1.1.6ColumnrARUFanStatusFanOperatingStatusread-onlymandatoryThe current operating state of the fan.
1.3.6.1.4.1.318.1.1.14.4.1.1.7ColumnrARUFanStatusFanRpmSpeedread-onlymandatoryThe current rotational speed of the fan, specified in rotations per minute (RPM).
1.3.6.1.4.1.318.1.1.14.4.1.1.8ColumnrARUFanStatusFanFlowRateread-onlymandatoryThe flow rate provided by the fan, based on its measured rotational speed. Specified in cfm (cubic feet per minute). Can be converted to metric values using th…
1.3.6.1.4.1.318.1.1.14.4.1.1.9ColumnrARUFanStatusFanInServiceDateread-writemandatoryThe installation/replacement date of the fan.
1.3.6.1.4.1.318.1.1.14.4.1.1.10ColumnrARUFanStatusFanRunhourCounterread-onlymandatoryThe total time for which the fan has been running. Specified in 10ths of hours.
1.3.6.1.4.1.318.1.1.14.4.1.1.11ColumnrARUFanStatusFanRunhourResetread-writemandatoryWriting yes to this This OID will reset a fan's total run hour counter, which is shown in the rARUFanStatusFanRunhourCounter OID.
1.3.6.1.4.1.318.1.1.14.5NoderARUPower
1.3.6.1.4.1.318.1.1.14.5.1TablerARUPowerStatusTablenot-accessiblemandatoryAllows for query of the individual ARUs accessible from this IP address. The number of entries is contained in the rARUStatusAruDeviceCount OID.
1.3.6.1.4.1.318.1.1.14.5.1.1RowrARUPowerStatusEntrynot-accessiblemandatoryThe device to query.
1.3.6.1.4.1.318.1.1.14.5.1.1.1ColumnrARUPowerStatusAruIndexread-onlymandatoryThe index to the ARU entry.
1.3.6.1.4.1.318.1.1.14.5.1.1.2ColumnrARUPowerStatusPrimaryAcPresentread-onlymandatoryIndicates whether or not line voltage is present on AC input 1.
1.3.6.1.4.1.318.1.1.14.5.1.1.3ColumnrARUPowerStatusAuxiliaryAcPresentread-onlymandatoryIndicates whether or not line voltage is present on AC input 2.
1.3.6.1.4.1.318.1.1.14.5.1.1.4ColumnrARUPowerStatusRedundantAcConfigread-writemandatoryIndicates whether or not a dual cord is in use. When this setting is set to dualCord (2), aruRedundantPowerLostAlarm traps will be generated when either primar…
1.3.6.1.4.1.318.1.1.14.6NoderARUSensors
1.3.6.1.4.1.318.1.1.14.6.1ScalarrARUSensorsStatusTableSizeread-onlymandatoryThe number of entries in the rARUSensorsStatusTable.
1.3.6.1.4.1.318.1.1.14.6.2TablerARUSensorsStatusTablenot-accessiblemandatoryAllows for getting environmental sensor status information.
1.3.6.1.4.1.318.1.1.14.6.2.1RowrARUSensorsStatusEntrynot-accessiblemandatoryThe unit to get data from.
1.3.6.1.4.1.318.1.1.14.6.2.1.1ColumnrARUSensorsStatusAruIndexread-onlymandatoryThe index to the ARU entry.
1.3.6.1.4.1.318.1.1.14.6.2.1.2ColumnrARUSensorsStatusSensorNumberread-onlymandatoryThe number of the sensor on the device.
1.3.6.1.4.1.318.1.1.14.6.2.1.3ColumnrARUSensorsTemperatureread-onlymandatoryThe sensor's current temperature reading. The temperature scale is based on the system preferences configuration.
1.3.6.1.4.1.318.1.1.14.6.3ScalarrARUSensorsConfigTableSizeread-onlymandatoryThe number of entries in the rARUSensorsConfigTable.
1.3.6.1.4.1.318.1.1.14.6.4TablerARUSensorsConfigTablenot-accessiblemandatoryAllows for getting configuration information from environmental sensors attached to the device.
1.3.6.1.4.1.318.1.1.14.6.4.1RowrARUSensorsConfigEntrynot-accessiblemandatoryThe unit to get data from.
1.3.6.1.4.1.318.1.1.14.6.4.1.1ColumnrARUSensorsConfigAruIndexread-onlymandatoryThe index to the ARU entry.
1.3.6.1.4.1.318.1.1.14.6.4.1.2ColumnrARUSensorsConfigSensorNumberread-onlymandatoryThe number of the sensor on the device.
1.3.6.1.4.1.318.1.1.14.6.4.1.3ColumnrARUSensorsNameread-writemandatoryA descriptive name for the sensor.
1.3.6.1.4.1.318.1.1.14.6.4.1.4ColumnrARUSensorsLocationread-writemandatoryThe location of the sensor.
1.3.6.1.4.1.318.1.1.14.6.4.1.5ColumnrARUSensorsTempMaxThreshread-writemandatoryThe temperature at which a maximum temperature threshold violation alarm will be generated for this sensor. The temperature scale is based on the system prefer…
1.3.6.1.4.1.318.1.1.14.6.4.1.6ColumnrARUSensorsTempHighThreshread-writemandatoryThe temperature at which a high temperature threshold violation alarm will be generated for this sensor. The temperature scale is based on the system preferenc…
1.3.6.1.4.1.318.1.1.14.6.4.1.7ColumnrARUSensorsTempLowThreshread-writemandatoryThe temperature at which a low temperature threshold violation alarm will be generated for this sensor. The temperature scale is based on the system preference…
1.3.6.1.4.1.318.1.1.14.6.4.1.8ColumnrARUSensorsTempMinThreshread-writemandatoryThe temperature at which a min temperature threshold violation alarm will be generated for this sensor. The temperature scale is based on the system preference…
1.3.6.1.4.1.318.1.1.14.6.4.1.9ColumnrARUSensorsTempThreshHysteresisread-writemandatoryThe change in temperature required to cause a temperature alarm to change from an active to an inactive state. The temperature scale is based on the system pre…
1.3.6.1.4.1.318.1.1.14.6.4.1.10ColumnrARUSensorsTempShortDecRateThreshValueread-writemandatoryThe value of the temperature short-term decreasing rate time that will cause an alarm to be generated. The temperature scale is based on the system preferences…
1.3.6.1.4.1.318.1.1.14.6.4.1.11ColumnrARUSensorsTempShortDecRateThreshTimeread-writemandatoryThe time over which the temperature may not decrease beyond the value specified by the temperature short-term decreasing rate threshold value.
1.3.6.1.4.1.318.1.1.14.6.4.1.12ColumnrARUSensorsTempShortIncRateThreshValueread-writemandatoryThe value of the temperature short-term increasing rate time that will cause an alarm to be generated. The temperature scale is based on the system preferences…
1.3.6.1.4.1.318.1.1.14.6.4.1.13ColumnrARUSensorsTempShortIncRateThreshTimeread-writemandatoryThe time over which the temperature may not increase beyond the value specified by the temperature short-term increasing rate threshold value.
1.3.6.1.4.1.318.1.1.14.6.4.1.14ColumnrARUSensorsTempLongDecRateThreshValueread-writemandatoryThe value of the temperature long-term decreasing rate time that will cause an alarm to be generated. The temperature scale is based on the system preferences …
1.3.6.1.4.1.318.1.1.14.6.4.1.15ColumnrARUSensorsTempLongDecRateThreshTimeread-writemandatoryThe time over which the temperature may not decrease beyond the value specified by the temperature long-term decreasing rate threshold value.
1.3.6.1.4.1.318.1.1.14.6.4.1.16ColumnrARUSensorsTempLongIncRateThreshValueread-writemandatoryThe value of the temperature long-term increasing rate time that will cause an alarm to be generated. The temperature scale is based on the system preferences …
1.3.6.1.4.1.318.1.1.14.6.4.1.17ColumnrARUSensorsTempLongIncRateThreshTimeread-writemandatoryThe time over which the temperature may not increase beyond the value specified by the temperature long-term increasing rate threshold value.
1.3.6.1.4.1.318.1.1.15NodexPDU
1.3.6.1.4.1.318.1.1.15.1NodexPDUIdent
1.3.6.1.4.1.318.1.1.15.1.1ScalarxPDUIdentProductNameread-writemandatoryThe name of the PDU.
1.3.6.1.4.1.318.1.1.15.1.2ScalarxPDUIdentHardwareRevread-onlymandatoryThe hardware revision of the PDU. This value is set at the factory.
1.3.6.1.4.1.318.1.1.15.1.3ScalarxPDUIdentFirmwareAppRevread-onlymandatoryAn ID string identifying the application firmware revision of the PDU.
1.3.6.1.4.1.318.1.1.15.1.4ScalarxPDUIdentFirmwareAppOSRevread-onlymandatoryAn ID string identifying the application operating system firmware revision of the PDU.
1.3.6.1.4.1.318.1.1.15.1.5ScalarxPDUIdentFirmwareControllerRevread-onlymandatoryAn ID string identifying the PDU controller firmware revision.
1.3.6.1.4.1.318.1.1.15.1.6ScalarxPDUIdentDateOfManufactureread-onlymandatoryThe date when the PDU was manufactured in mm/dd/yyyy format. This value is set at the factory.
1.3.6.1.4.1.318.1.1.15.1.7ScalarxPDUIdentModelNumberread-onlymandatoryA character string identifying the model number of the PDU. This value is set at the factory.
1.3.6.1.4.1.318.1.1.15.1.8ScalarxPDUIdentSerialNumberread-onlymandatoryA character string identifying the serial number of the PDU. This value is set at the factory.
1.3.6.1.4.1.318.1.1.15.2NodexPDUDevice
1.3.6.1.4.1.318.1.1.15.2.1ScalarxPDUDeviceNominalMainInputVoltageread-onlymandatoryThe nominal main input voltage to the PDU. Measured in Volts, line-to-line for a 3-wire (delta) service or line-to-neutral for a 4-wire (wye) service.
1.3.6.1.4.1.318.1.1.15.2.2ScalarxPDUDeviceServiceTyperead-onlymandatoryThe type of utility input to the PDU. Either 3 wires (delta), or 4 wires (wye).
1.3.6.1.4.1.318.1.1.15.2.3ScalarxPDUDeviceNominalOutputVoltageread-onlymandatoryThe nominal line-to-neutral output voltage to the load measured in Volts.
1.3.6.1.4.1.318.1.1.15.2.4ScalarxPDUDeviceMainInputBreakerRatingread-onlymandatoryThe rating of the main input breaker measured in Amps.
1.3.6.1.4.1.318.1.1.15.2.5ScalarxPDUDevicePanelBreakerRatingread-onlymandatoryThe rating of the panel breaker measured in Amps.
1.3.6.1.4.1.318.1.1.15.2.6ScalarxPDUDeviceTransformerPresentread-onlymandatoryIndicates whether or not a transformer is installed in the PDU.
1.3.6.1.4.1.318.1.1.15.2.7ScalarxPDUDeviceLoadTieBreakerPresentread-onlymandatoryIndicates whether or not a load tie breaker is installed in the PDU.
1.3.6.1.4.1.318.1.1.15.2.8ScalarxPDUDeviceLoadTestPortPresentread-onlymandatoryIndicates whether or not a load test port is installed in the PDU.
1.3.6.1.4.1.318.1.1.15.2.9ScalarxPDUDeviceFusesPresentread-onlymandatoryIndicates whether or not the UPS feed from the PDU includes fuses.
1.3.6.1.4.1.318.1.1.15.2.10ScalarxPDUDeviceFansPresentread-onlymandatoryIndicates whether or not cooling fans are installed in the PDU.
1.3.6.1.4.1.318.1.1.15.2.11ScalarxPDUDeviceBypassInputPresentread-onlymandatoryIndicates whether or not the PDU is equipped with a second feed for the UPS's bypass input.
1.3.6.1.4.1.318.1.1.15.2.12ScalarxPDUDeviceCrossTieOutputPresentread-onlymandatoryIndicates whether or not the PDU is equipped with a cross-tie output.
1.3.6.1.4.1.318.1.1.15.2.13ScalarxPDUDeviceEarthGroundMonitorPresentread-onlymandatoryIndicates whether or not the PDU can provide ground current measurements.
1.3.6.1.4.1.318.1.1.15.2.14ScalarxPDUDeviceInfraStruXureTyperead-onlymandatoryIndicates the configuration of this PDU system. Type-B PDU is in a distributed UPS system and has bypass capabilities. Type-C PDU receives power from a larger …
1.3.6.1.4.1.318.1.1.15.3NodexPDUACMonitoringPoint
1.3.6.1.4.1.318.1.1.15.3.1NodexPDUMainInput
1.3.6.1.4.1.318.1.1.15.3.1.1ScalarxPDUMainInputOverVoltThresholdread-writemandatoryThreshold above which an input over voltage condition will be generated. Specified as percent deviation from nominal.
1.3.6.1.4.1.318.1.1.15.3.1.2ScalarxPDUMainInputUnderVoltThresholdread-writemandatoryThreshold below which an input under voltage condition will be generated. Specified as percent deviation from nominal. A value of zero indicates that the thres…
1.3.6.1.4.1.318.1.1.15.3.1.3ScalarxPDUMainInputVoltageTableSizeread-onlymandatoryThe number of Main input voltage entries.
1.3.6.1.4.1.318.1.1.15.3.1.4TablexPDUMainInputVoltagePhaseTablenot-accessiblemandatoryA list of input voltage table entries. The number of entries are the phase entries. The number of entries is contained in the xPDUMainInputVoltageTableSize OID.
1.3.6.1.4.1.318.1.1.15.3.1.4.1RowxPDUMainInputVoltagePhaseEntrynot-accessiblemandatoryAn entry containing information applicable to a particular main input voltage phase.
1.3.6.1.4.1.318.1.1.15.3.1.4.1.1ColumnxPDUMainInputVoltagePhaseIndexread-onlymandatoryDescription of each input phase entry in the table.
1.3.6.1.4.1.318.1.1.15.3.1.4.1.2ColumnxPDUMainInputVoltageLtoLread-onlymandatoryLine-to-line PDU input voltage when an isolation transformer is present, or -1 if no transformer present in this PDU. Measured in tenths of Volts.
1.3.6.1.4.1.318.1.1.15.3.1.4.1.3ColumnxPDUMainInputVoltageLtoNread-onlymandatoryLine-to-neutral PDU input voltage when an isolation transformer is not present, or -1 if a transformer is present in this PDU. Measured in tenths of Volts.
1.3.6.1.4.1.318.1.1.15.3.2NodexPDUBypassInput
1.3.6.1.4.1.318.1.1.15.3.2.1ScalarxPDUBypassInputOverVoltThresholdread-writemandatoryThreshold above which a bypass input over voltage condition will be generated. Specified as percent deviation from nominal.
1.3.6.1.4.1.318.1.1.15.3.2.2ScalarxPDUBypassInputUnderVoltThresholdread-writemandatoryThreshold below which an bypass input under voltage condition will be generated. Specified as percent deviation from nominal. A value of zero indicates that th…
1.3.6.1.4.1.318.1.1.15.3.2.3ScalarxPDUBypassInputVoltagePhaseTableSizeread-onlymandatoryThe number of bypass input voltage entries.
1.3.6.1.4.1.318.1.1.15.3.2.4TablexPDUBypassInputVoltagePhaseTablenot-accessiblemandatoryA list of output table entries. The number of entries are the phase entries. The number of entries is contained in the xPDUBypassInputVoltagePhaseTableSize OID.
1.3.6.1.4.1.318.1.1.15.3.2.4.1RowxPDUBypassInputVoltagePhaseEntrynot-accessiblemandatoryAn entry containing information applicable to a particular bypass input voltage phase.
1.3.6.1.4.1.318.1.1.15.3.2.4.1.1ColumnxPDUBypassInputVoltagePhaseIndexread-onlymandatoryIndex of each bypass input phase entry in the table.
1.3.6.1.4.1.318.1.1.15.3.2.4.1.2ColumnxPDUBypassInputVoltageLtoLread-onlymandatoryLine-to-line bypass input voltage, or -1 if no bypass feed is present in this PDU. Measured in tenths of Volts.
1.3.6.1.4.1.318.1.1.15.3.2.4.1.3ColumnxPDUBypassInputVoltageLtoNread-onlymandatoryLine-to-neutral bypass input voltage, or -1 if no bypass feed is present in this PDU. Measured in tenths of Volts.
1.3.6.1.4.1.318.1.1.15.3.3NodexPDUUPSInput
1.3.6.1.4.1.318.1.1.15.3.3.1ScalarxPDUUPSInputVoltagePhaseTableSizeread-onlymandatoryThe number of UPS input voltage entries.
1.3.6.1.4.1.318.1.1.15.3.3.2TablexPDUUPSInputVoltagePhaseTablenot-accessiblemandatoryA list of UPS input table entries. The number of entries are the phase entries. The number of entries is contained in the xPDUUPSInputVoltagePhaseTableSize OID.
1.3.6.1.4.1.318.1.1.15.3.3.2.1RowxPDUUPSInputVoltagePhaseEntrynot-accessiblemandatoryAn entry containing information applicable to a particular UPS input voltage phase.
1.3.6.1.4.1.318.1.1.15.3.3.2.1.1ColumnxPDUUPSInputVoltagePhaseIndexread-onlymandatoryDescription of each UPS input phase entry in the table.
1.3.6.1.4.1.318.1.1.15.3.3.2.1.2ColumnxPDUUPSInputVoltageLtoNPresentread-onlymandatoryIndicates whether or not voltage is present at the UPS feed.
1.3.6.1.4.1.318.1.1.15.3.4NodexPDUSystemOutput
1.3.6.1.4.1.318.1.1.15.3.4.1ScalarxPDUSystemOutputFrequencyread-onlymandatoryThe system output frequency in tenths of Hertz.
1.3.6.1.4.1.318.1.1.15.3.4.2ScalarxPDUSystemOutputNeutralCurrentread-onlymandatoryShows the neutral current measured at the system output in tenths of Amps.
1.3.6.1.4.1.318.1.1.15.3.4.3ScalarxPDUSystemOutputTotalPowerread-onlymandatoryShows the total system output power in tenths of kW.
1.3.6.1.4.1.318.1.1.15.3.4.4ScalarxPDUSystemOutputTotalApparentPowerread-onlymandatoryShows the total system output power in tenths of kVA.
1.3.6.1.4.1.318.1.1.15.3.4.5ScalarxPDUSystemOutputTotalPowerFactorread-onlymandatoryIndicates the total power factor of the system output. A value of 100 representing a unity power factor (1.00). Measured in hundredths.
1.3.6.1.4.1.318.1.1.15.3.4.6ScalarxPDUSystemOutputFrequencyToleranceread-writemandatoryShows the circuit panel output frequency tolerance in Hertz.
1.3.6.1.4.1.318.1.1.15.3.4.7ScalarxPDUSystemOutputMaxKWPowerread-writemandatoryDefines 100% load in kW. Purpose is to set to match UPS capabilities.
1.3.6.1.4.1.318.1.1.15.3.4.8ScalarxPDUSystemOutputOverVoltThresholdread-writemandatoryThreshold above which an output over voltage condition will be generated. Specified as percent deviation from nominal.
1.3.6.1.4.1.318.1.1.15.3.4.9ScalarxPDUSystemOutputUnderVoltThresholdread-writemandatoryThreshold below which an output under voltage condition will be generated. Specified as percent deviation from nominal. A value of zero indicates that the thre…
1.3.6.1.4.1.318.1.1.15.3.4.10ScalarxPDUSystemOutputOverCurrentThresholdread-writemandatoryThreshold above which an over current condition will be generated. Specified as a percent of the panel breaker rating. A value of zero indicates that the thres…
1.3.6.1.4.1.318.1.1.15.3.4.11ScalarxPDUSystemOutputOverCurrentNeutralThresholdread-writemandatoryThreshold above which an Over current neutral condition will be generated. Specified as a percent of the panel breaker rating. A value of zero indicates that t…
1.3.6.1.4.1.318.1.1.15.3.4.12ScalarxPDUSystemOutputUnderCurrentThresholdread-writemandatoryThreshold below which an under current condition will be generated. Specified as a percent of the panel breaker rating. A value of zero indicates that the thre…
1.3.6.1.4.1.318.1.1.15.3.4.13ScalarxPDUSystemOutputTableSizeread-onlymandatoryThe number of System Output phase entries.
1.3.6.1.4.1.318.1.1.15.3.4.14TablexPDUSystemOutputPhaseTablenot-accessiblemandatoryA list of system output table entries. The number of entries is contained in the xPDUSystemOutputTableSize OID.
1.3.6.1.4.1.318.1.1.15.3.4.14.1RowxPDUSystemOutputPhaseEntrynot-accessiblemandatoryAn entry containing information applicable to a particular system output phase.
1.3.6.1.4.1.318.1.1.15.3.4.14.1.1ColumnxPDUSystemOutputPhaseIndexread-onlymandatoryDescription of each output phase entry in the table.
1.3.6.1.4.1.318.1.1.15.3.4.14.1.2ColumnxPDUSystemOutputVoltageLtoLread-onlymandatoryLine-to-line system output voltage available at the circuit panel. Measured in tenths of Volts.
1.3.6.1.4.1.318.1.1.15.3.4.14.1.3ColumnxPDUSystemOutputVoltageLtoNread-onlymandatoryLine-to-neutral system output voltage available at the circuit panel. Measured in tenths of Volts.
1.3.6.1.4.1.318.1.1.15.3.4.14.1.4ColumnxPDUSystemOutputPhaseCurrentread-onlymandatorySystem load current per phase. Measured in tenths of Amps.
1.3.6.1.4.1.318.1.1.15.3.4.14.1.5ColumnxPDUSystemOutputPowerread-onlymandatorySystem output power per phase. Measured in tenths of kW.
1.3.6.1.4.1.318.1.1.15.3.4.14.1.6ColumnxPDUSystemOutputApparentPowerread-onlymandatorySystem output power per phase. Measured in tenths of kVA.
1.3.6.1.4.1.318.1.1.15.3.4.14.1.7ColumnxPDUSystemOutputPowerFactorread-onlymandatoryIndicates the Power Factor of the system output per phase. A value of 100 representing a unity Power Factor (1.00). Measured in hundredths.
1.3.6.1.4.1.318.1.1.15.3.5NodexPDUGroundMonitorPoint
1.3.6.1.4.1.318.1.1.15.3.5.1ScalarxPDUGroundCurrentread-onlymandatoryShows the current measured in the earth ground conductor. Measured in tenths of Amps, or -1 if not available.
1.3.6.1.4.1.318.1.1.15.3.5.2ScalarxPDUGroundCurrentThresholdread-writemandatoryThreshold above which a ground current over current condition will be generated. Specified in tenths of Amps.
1.3.6.1.4.1.318.1.1.15.4NodexPDUCircuitBreakers
1.3.6.1.4.1.318.1.1.15.4.1NodexPDUSystemBreakers
1.3.6.1.4.1.318.1.1.15.4.1.1ScalarxPDUSystemBreakerTableSizeread-onlymandatoryThe number of system breaker entries.
1.3.6.1.4.1.318.1.1.15.4.1.2TablexPDUSystemBreakerTablenot-accessiblemandatoryA list of system breaker entries. The number of entries is contained in the xPDUSystemBreakerTableSize OID.
1.3.6.1.4.1.318.1.1.15.4.1.2.1RowxPDUSystemBreakerEntrynot-accessiblemandatoryAn entry containing information applicable to a particular system breaker.
1.3.6.1.4.1.318.1.1.15.4.1.2.1.1ColumnxPDUSystemBreakerTableIndexread-onlymandatoryIndex of system breaker entries in the table.
1.3.6.1.4.1.318.1.1.15.4.1.2.1.2ColumnxPDUSystemBreakerDescriptionread-onlymandatoryA brief description of the system breakers.
1.3.6.1.4.1.318.1.1.15.4.1.2.1.3ColumnxPDUSystemBreakerPositionread-onlymandatoryIndicates whether this breaker is open(1) or closed(2).
1.3.6.1.4.1.318.1.1.15.4.2NodexPDUBranchBreakers
1.3.6.1.4.1.318.1.1.15.4.2.1ScalarxPDUNumOfBranchBreakersread-onlymandatoryThe number of branch breakers (panel positions) in the Panel. returns 42 for a 1-panel or 84 for a 2-panel system.
1.3.6.1.4.1.318.1.1.15.4.2.2ScalarxPDUBranchBreakerTableSizeread-onlymandatoryThe number of branch breaker entries determined by the xPDUNumOfBranchBreakers OID.
1.3.6.1.4.1.318.1.1.15.4.2.3TablexPDUBranchBreakerTablenot-accessiblemandatoryA list of branch breaker table entries. The number of entries is given by the value of xPDUBranchBreakerTableSize The number of entries is contained in the xPD…
1.3.6.1.4.1.318.1.1.15.4.2.3.1RowxPDUBranchBreakerEntrynot-accessiblemandatoryAn entry containing information applicable to a particular branch breaker (panel position).
1.3.6.1.4.1.318.1.1.15.4.2.3.1.1ColumnxPDUBranchBreakerTableIndexread-onlymandatoryIndex of branch breaker entries in the table.
1.3.6.1.4.1.318.1.1.15.4.2.3.1.2ColumnxPDUBranchBreakerRatingread-writemandatoryIndicates current rating of this breaker. 0=Breaker is not present. 1=Earth leakage connection. 2=Neutral connection. A value greater than 2 indicates breaker …
1.3.6.1.4.1.318.1.1.15.4.2.3.1.3ColumnxPDUBranchBreakerRDPFeedread-onlymandatoryIndicates that a breaker position is feeding a remote distribution panel.
1.3.6.1.4.1.318.1.1.15.4.2.3.1.4ColumnxPDUBranchBreakerTieIndicatorread-writemandatoryIndicates whether or not the breaker in this position is logically associated with the breaker immediately below it. This setting is used grouping the breakers…
1.3.6.1.4.1.318.1.1.15.4.2.3.1.5ColumnxPDUBranchBreakerCurrentread-onlymandatoryIndicates the branch current in tenths of Amps or -1 when not available.
1.3.6.1.4.1.318.1.1.15.4.2.3.1.6ColumnxPDUBranchBreakerOverCurrentThresholdread-writemandatoryThreshold above which a branch circuit high current condition will be generated. Specified as a percent of the branch breaker rating. A value of zero indicates…
1.3.6.1.4.1.318.1.1.15.4.2.3.1.7ColumnxPDUBranchBreakerUnderCurrentThresholdread-writemandatoryThreshold below which a branch circuit low current condition will be generated. Specified as a percent of the branch breaker rating. A value of zero indicates …
1.3.6.1.4.1.318.1.1.15.4.2.3.1.8ColumnxPDUBranchBreakerMaxCurrentThresholdread-writemandatoryThreshold above which a branch circuit maximum current condition will be generated. Specified as a percent of the branch breaker rating. A value of zero indica…
1.3.6.1.4.1.318.1.1.15.4.2.3.1.9ColumnxPDUBranchBreakerMinCurrentThresholdread-writemandatoryThreshold below which a branch circuit minimum current condition will be generated. Specified as a percent of the branch breaker rating. A value of zero indica…
1.3.6.1.4.1.318.1.1.15.4.2.3.1.10ColumnxPDUBranchBreakerNameread-writemandatoryThe description of the purpose/use of the breaker.
1.3.6.1.4.1.318.1.1.15.4.2.3.1.11ColumnxPDUBranchBreakerLocationread-writemandatoryThe description of the location of the breaker.
1.3.6.1.4.1.318.1.1.15.5NodexPDUInputContacts
1.3.6.1.4.1.318.1.1.15.5.1ScalarxPDUInputContactNumContactsread-onlymandatoryThe number of contacts supported by the PDU.
1.3.6.1.4.1.318.1.1.15.5.2ScalarxPDUInputContactTableSizeread-onlymandatoryThe number of input contact entries.
1.3.6.1.4.1.318.1.1.15.5.3TablexPDUInputContactTablenot-accessiblemandatoryA list of contacts supported by the PDU. The number of entries is contained in the xPDUInputContactTableSize OID.
1.3.6.1.4.1.318.1.1.15.5.3.1RowxPDUInputContactEntrynot-accessiblemandatoryA contact entry containing information for a given contact.
1.3.6.1.4.1.318.1.1.15.5.3.1.1ColumnxPDUInputContactNumberread-onlymandatoryAn index identifying the contact on the PDU.
1.3.6.1.4.1.318.1.1.15.5.3.1.2ColumnxPDUInputContactNameread-writemandatoryThe description of the purpose/use of the contact.
1.3.6.1.4.1.318.1.1.15.5.3.1.3ColumnxPDUInputContactNormalStateread-writemandatoryThe normal operating position of the contact.
1.3.6.1.4.1.318.1.1.15.5.3.1.4ColumnxPDUInputContactCurrentStateread-onlymandatoryThis value indicates the current state of the contact.
1.3.6.1.4.1.318.1.1.15.6NodexPDUOutputRelays
1.3.6.1.4.1.318.1.1.15.6.1ScalarxPDUOutputRelaysNumRelaysread-onlymandatoryThe number of output relays supported by the PDU.
1.3.6.1.4.1.318.1.1.15.6.2ScalarxPDUOutputRelaysTableSizeread-onlymandatoryThe number of output relay entries.
1.3.6.1.4.1.318.1.1.15.6.3TablexPDUOutputRelayTablenot-accessiblemandatoryA list of output relays supported by the PDU. The number of entries is contained in the xPDUOutputRelayTableSize OID.
1.3.6.1.4.1.318.1.1.15.6.3.1RowxPDUOutputRelayEntrynot-accessiblemandatoryA output relay entry containing information for a given contact.
1.3.6.1.4.1.318.1.1.15.6.3.1.1ColumnxPDUOutputRelayNumberread-onlymandatoryAn index identifying the output relay on the PDU.
1.3.6.1.4.1.318.1.1.15.6.3.1.2ColumnxPDUOutputRelayNameread-writemandatoryThe description of the purpose/use of the output relay.
1.3.6.1.4.1.318.1.1.15.6.3.1.3ColumnxPDUOutputRelayNormalStateread-writemandatoryThe normal operating position of the output relay.
1.3.6.1.4.1.318.1.1.15.6.3.1.4ColumnxPDUOutputRelayCurrentStateread-onlymandatoryThis value indicates the current state of the output relay.
1.3.6.1.4.1.318.1.1.15.7NodexPDUMiscGroup
1.3.6.1.4.1.318.1.1.15.7.1ScalarxPDUEPOModeread-onlymandatoryIndicates whether the EPO System is armed(1) or disarmed(2).
1.3.6.1.4.1.318.1.1.15.7.2ScalarxPDUTransformTempStatusread-onlymandatoryIndicates if the PDU's isolation transformer is over temperature.
1.3.6.1.4.1.318.1.1.15.7.3ScalarxPDUCoolingFanStatusread-onlymandatoryIndicates if one or more of the PDU's cooling fans have failed.
1.3.6.1.4.1.318.1.1.16NodebattMan
1.3.6.1.4.1.318.1.1.16.1NodebattManIdent
1.3.6.1.4.1.318.1.1.16.1.1ScalarbattManIdentProductNameread-writemandatoryThe name of the battery manager.
1.3.6.1.4.1.318.1.1.16.1.2ScalarbattManIdentHardwareRevread-onlymandatoryThe battery manager network interface hardware revision. This value is set at the factory.
1.3.6.1.4.1.318.1.1.16.1.3ScalarbattManIdentFirmwareRevread-onlymandatoryThe battery manager network interface firmware revision. This value is set at the factory and can change with firmware update.
1.3.6.1.4.1.318.1.1.16.1.4ScalarbattManIdentDateOfManufactureread-onlymandatoryThe date the battery manager was manufactured in mm/dd/yyyy format. This value is set at the factory.
1.3.6.1.4.1.318.1.1.16.1.5ScalarbattManIdentModelNumberread-onlymandatoryThe battery manager model number character string. This value is set at the factory.
1.3.6.1.4.1.318.1.1.16.1.6ScalarbattManIdentSerialNumberread-onlymandatoryThe battery manager serial number character string. This value is set at the factory.
1.3.6.1.4.1.318.1.1.16.2NodebattManSystemCalib
1.3.6.1.4.1.318.1.1.16.2.1ScalarbattManOhmicValueCorrectionFactorread-writemandatoryThe system ohmic value correction factor in percent.
1.3.6.1.4.1.318.1.1.16.3NodebattManUnitCalib
1.3.6.1.4.1.318.1.1.16.3.1ScalarbattManUnitCalibTableSizeread-onlymandatoryThe number of entries in the battManUnitCalibTable.
1.3.6.1.4.1.318.1.1.16.3.2TablebattManUnitCalibTablenot-accessiblemandatoryAllows for getting calibration information from each unit in the system.
1.3.6.1.4.1.318.1.1.16.3.2.1RowbattManUnitCalibEntrynot-accessiblemandatoryThe unit to get data from.
1.3.6.1.4.1.318.1.1.16.3.2.1.1ColumnbattManUnitCalibIndexread-onlymandatoryIndex of unit calibration entries in the table.
1.3.6.1.4.1.318.1.1.16.3.2.1.2ColumnbattManUnitSerialNumberread-onlymandatoryThe serial number of the unit.
1.3.6.1.4.1.318.1.1.16.3.2.1.3ColumnbattManBatteryVoltageZeroCalibread-writemandatoryThe unit battery voltage zero calibration in millivolts.
1.3.6.1.4.1.318.1.1.16.3.2.1.4ColumnbattManBatteryVoltageSpanCalibread-writemandatoryThe unit battery voltage span calibration in hundredths of percent.
1.3.6.1.4.1.318.1.1.16.4NodebattManStringCalib
1.3.6.1.4.1.318.1.1.16.4.1ScalarbattManStringCalibTableSizeread-onlymandatoryThe number of entries in the battManStringCalibTable.
1.3.6.1.4.1.318.1.1.16.4.2TablebattManStringCalibTablenot-accessiblemandatoryAllows for getting calibration information from each string in the system.
1.3.6.1.4.1.318.1.1.16.4.2.1RowbattManStringCalibEntrynot-accessiblemandatoryThe string to get data from.
1.3.6.1.4.1.318.1.1.16.4.2.1.1ColumnbattManStringCalibIndexread-onlymandatoryIndex of string calibration entries in the table.
1.3.6.1.4.1.318.1.1.16.4.2.1.2ColumnbattManDCCurrentZeroCalibread-writemandatoryThe string DC current zero calibration in tenths of amps.
1.3.6.1.4.1.318.1.1.16.4.2.1.3ColumnbattManACCurrentZeroCalibread-writemandatoryThe string AC current zero calibration in tenths of amps.
1.3.6.1.4.1.318.1.1.16.4.2.1.4ColumnbattManProbeRangeread-writemandatoryThe string probe range in amps.
1.3.6.1.4.1.318.1.1.16.5NodebattManBatteryCalib
1.3.6.1.4.1.318.1.1.16.5.1ScalarbattManString1BatteryCalibTableSizeread-onlymandatoryThe number of entries in the battManString1BatteryCalibTable.
1.3.6.1.4.1.318.1.1.16.5.2TablebattManString1BatteryCalibTablenot-accessiblemandatoryAllows for getting calibration information from each battery in String 1.
1.3.6.1.4.1.318.1.1.16.5.2.1RowbattManString1BatteryCalibEntrynot-accessiblemandatoryThe string to get data from.
1.3.6.1.4.1.318.1.1.16.5.2.1.1ColumnbattManString1BatteryCalibIndexread-onlymandatoryIndex of battery calibration entries in the table.
1.3.6.1.4.1.318.1.1.16.5.2.1.2ColumnbattManString1BatteryInterTierOhmicValueread-writemandatoryThe battery inter-tier ohmic value in ohms. This corresponds to the ohmic value for the positive terminal of the battery.
1.3.6.1.4.1.318.1.1.16.5.3ScalarbattManString2BatteryCalibTableSizeread-onlymandatoryThe number of entries in the battManString2BatteryCalibTable.
1.3.6.1.4.1.318.1.1.16.5.4TablebattManString2BatteryCalibTablenot-accessiblemandatoryAllows for getting calibration information from each battery in String 2.
1.3.6.1.4.1.318.1.1.16.5.4.1RowbattManString2BatteryCalibEntrynot-accessiblemandatoryThe string to get data from.
1.3.6.1.4.1.318.1.1.16.5.4.1.1ColumnbattManString2BatteryCalibIndexread-onlymandatoryIndex of battery calibration entries in the table.
1.3.6.1.4.1.318.1.1.16.5.4.1.2ColumnbattManString2BatteryInterTierOhmicValueread-writemandatoryThe battery inter-tier ohmic value in ohms.
1.3.6.1.4.1.318.1.1.16.6NodebattManConfig
1.3.6.1.4.1.318.1.1.16.6.1ScalarbattManConfigApplicationread-writedeprecatedThis OID has been deprecated.
1.3.6.1.4.1.318.1.1.16.6.2ScalarbattManConfigBatteryChemistryread-writemandatoryThe battery chemistry of the monitored batteries: LeadAcid(1) Lead Acid or Nickel-Cadmium(2) Nickel-Cadmium.
1.3.6.1.4.1.318.1.1.16.6.3ScalarbattManConfigBatteryAHCapacityread-writemandatoryThe amp hour capacity of the monitored batteries 5-4000 AH.
1.3.6.1.4.1.318.1.1.16.6.4ScalarbattManConfigNumberofStringsread-writemandatoryThe number of strings in the battery manager system.
1.3.6.1.4.1.318.1.1.16.6.5ScalarbattManConfigBatteriesperStringread-writemandatoryThe number of batteries per string.
1.3.6.1.4.1.318.1.1.16.6.6ScalarbattManConfigCellsperBatteryread-writemandatoryThe number of cells per battery (1, 2, 4 or 6 for lead-acid, 1 or 2 for NiCd.
1.3.6.1.4.1.318.1.1.16.6.7ScalarbattManConfigMinCellVoltageread-writemandatoryThe minimum battery cell voltage alarm limit in millivolts DC.
1.3.6.1.4.1.318.1.1.16.6.8ScalarbattManConfigMaxCellVoltageread-writemandatoryThe maximum battery cell voltage alarm limit in millivolts DC.
1.3.6.1.4.1.318.1.1.16.6.9ScalarbattManConfigMaxPilotTempFread-writemandatoryThe maximum pilot battery temperature alarm limit in tenths of degrees Fahrenheit.
1.3.6.1.4.1.318.1.1.16.6.10ScalarbattManConfigMaxPilotTempCread-writemandatoryThe maximum pilot battery temperature alarm limit in tenths of degrees Celsius.
1.3.6.1.4.1.318.1.1.16.6.11ScalarbattManConfigMaxAmbientTempFread-writemandatoryThe maximum ambient temperature alarm limit in tenths of degrees Fahrenheit.
1.3.6.1.4.1.318.1.1.16.6.12ScalarbattManConfigMaxAmbientTempCread-writemandatoryThe maximum ambient temperature alarm limit in tenths of degrees Celsius.
1.3.6.1.4.1.318.1.1.16.6.13ScalarbattManConfigMinAmbientTempFread-writemandatoryThe Minimum Ambient Temperature alarm limit in tenths of degrees Fahrenheit.
1.3.6.1.4.1.318.1.1.16.6.14ScalarbattManConfigMinAmbientTempCread-writemandatoryThe Minimum Ambient Temperature alarm limit in tenths of degrees Celsius.
1.3.6.1.4.1.318.1.1.16.6.15ScalarbattManConfigMaxRippleCurrentread-writemandatoryThe maximum ripple current alarm limit for the monitored battery strings in percent of AH capacity.
1.3.6.1.4.1.318.1.1.16.6.16ScalarbattManConfigMaxCurrentAcceptanceDeviationread-writemandatoryThe maximum current acceptance deviation alarm limit in percent.
1.3.6.1.4.1.318.1.1.16.6.17ScalarbattManConfigMonitorWireLengthread-writemandatoryThe monitor wire length: fiftyFeetOrLess (1) indicates that the wire length is less than or equal to 50 feet. moreThanFiftyFeet (2) indicates that the wire len…
1.3.6.1.4.1.318.1.1.16.6.18ScalarbattManConfigDischargeVoltageAlarmLevelread-writemandatoryThe discharge voltage alarm level in percent.
1.3.6.1.4.1.318.1.1.16.6.19ScalarbattManConfigAutoAnnunciatorResetread-writemandatoryThe annunciator output signal reset method: disabled(1) means the annunciator signal output will be reset when the reset button is pressed. enabled(2) means th…
1.3.6.1.4.1.318.1.1.16.6.20ScalarbattManConfigSuspendCellVoltageread-writemandatoryThis is used along with the number of cells per battery and the number of batteries per string to determine if a battery string has violated the low voltage li…
1.3.6.1.4.1.318.1.1.16.6.21ScalarbattManConfigOhmicTestWaitTimeread-writemandatoryThe amount of time in seconds after a discharge event before data will be collected for the ohmic value calculation.
1.3.6.1.4.1.318.1.1.16.6.22ScalarbattManConfigNumberOfBoostsread-writemandatoryThe number of consecutive times the Battery Management System applies a charge to each battery during a boost cycle. Batteries with a Rated Battery AH Capacity…
1.3.6.1.4.1.318.1.1.16.7NodebattManAlarm
1.3.6.1.4.1.318.1.1.16.7.1ScalarbattManAlarmManagementControllerread-onlymandatoryThe Management Controller Alarm is : normal(1) no alarm conditions identified alarm(2) an alarm condition exists.
1.3.6.1.4.1.318.1.1.16.7.2ScalarbattManAlarmBatteriesread-onlymandatoryThe Batteries Alarm is : normal(1) no alarm conditions identified alarm(2) an alarm condition exists.
1.3.6.1.4.1.318.1.1.16.7.3ScalarbattManAlarmChargerread-onlymandatoryThe Charger Alarm is : normal(1) no alarm conditions identified alarm(2) an alarm condition exists.
1.3.6.1.4.1.318.1.1.16.7.4ScalarbattManAlarmEnvironmentread-onlymandatoryThe Environment Alarm is : normal(1) no alarm conditions identified alarm(2) an alarm condition exists.
1.3.6.1.4.1.318.1.1.16.8NodebattManSystemStatus
1.3.6.1.4.1.318.1.1.16.8.1ScalarbattManSystemAmbientTempCread-onlymandatoryThe system ambient temperature in tenths of degrees Celsius.
1.3.6.1.4.1.318.1.1.16.8.2ScalarbattManSystemAmbientTempFread-onlymandatoryThe system ambient temperature in tenths of degrees Fahrenheit.
1.3.6.1.4.1.318.1.1.16.8.3ScalarbattManSystemPilotTempCread-onlymandatoryThe system pilot temperature in tenths of degrees Celsius.
1.3.6.1.4.1.318.1.1.16.8.4ScalarbattManSystemPilotTempFread-onlymandatoryThe system pilot temperature in tenths of degrees Fahrenheit.
1.3.6.1.4.1.318.1.1.16.8.5ScalarbattManSystemAmbientHighTempAlarmread-onlymandatoryWhen set to alarm(2), indicates that the system has a high temperature alarm.
1.3.6.1.4.1.318.1.1.16.8.6ScalarbattManSystemAmbientLowTempAlarmread-onlymandatoryWhen set to alarm(2), indicates that the system has a low temperature alarm.
1.3.6.1.4.1.318.1.1.16.8.7ScalarbattManSystemPilotBatteryHighTempAlarmread-onlymandatoryWhen set to alarm(2), indicates that the system has a pilot battery high temperature alarm.
1.3.6.1.4.1.318.1.1.16.8.8ScalarbattManSystemPilotProbeDisconnectedread-onlymandatoryWhen set to alarm(2), indicates that the system pilot probe is disconnected.
1.3.6.1.4.1.318.1.1.16.8.9ScalarbattManSystemAmbientProbeDisconnectedread-onlymandatoryWhen set to alarm(2), indicates that the system ambient probe is disconnected.
1.3.6.1.4.1.318.1.1.16.8.10ScalarbattManSystemConfigurationInvalidread-onlymandatoryWhen set to alarm(2), indicates that the system is not configured correctly.
1.3.6.1.4.1.318.1.1.16.8.11ScalarbattManSystemSuspendVoltageread-onlymandatoryWhen set to alarm(2), indicates that the system has suspended voltage scans.
1.3.6.1.4.1.318.1.1.16.9NodebattManStringStatus
1.3.6.1.4.1.318.1.1.16.9.1ScalarbattManStringTableSizeread-onlymandatoryThe number of entries in the battManStringTable.
1.3.6.1.4.1.318.1.1.16.9.2TablebattManStringTablenot-accessiblemandatoryAllows for getting information from each string in the system.
1.3.6.1.4.1.318.1.1.16.9.2.1RowbattManStringEntrynot-accessiblemandatoryThe string to get data from.
1.3.6.1.4.1.318.1.1.16.9.2.1.1ColumnbattManStringIndexread-onlymandatoryIndex of string entries in the table.
1.3.6.1.4.1.318.1.1.16.9.2.1.2ColumnbattManStringCurrentread-onlymandatoryThe string current in tenths of amps.
1.3.6.1.4.1.318.1.1.16.9.2.1.3ColumnbattManStringRippleCurrentread-onlymandatoryThe string ripple current in tenths of amps.
1.3.6.1.4.1.318.1.1.16.9.2.1.4ColumnbattManStringChargerHighVoltageAlarmread-onlymandatoryWhen set to alarm(2), indicates that the string charger has a high voltage alarm.
1.3.6.1.4.1.318.1.1.16.9.2.1.5ColumnbattManStringChargerLowVoltageAlarmread-onlymandatoryWhen set to alarm(2), indicates that the string charger has a low voltage alarm.
1.3.6.1.4.1.318.1.1.16.9.2.1.6ColumnbattManStringCurrentProbeDisconnectedread-onlymandatoryWhen set to alarm(2), indicates that the string charger probe is disconnected.
1.3.6.1.4.1.318.1.1.16.9.2.1.7ColumnbattManStringOnBatteryread-onlymandatoryWhen set to alarm(2), indicates that the string is in the on-battery state.
1.3.6.1.4.1.318.1.1.16.9.2.1.8ColumnbattManStringHighRippleCurrentread-onlymandatoryWhen set to alarm(2), indicates that the string has a high ripple current.
1.3.6.1.4.1.318.1.1.16.9.2.1.9ColumnbattManStringVoltageread-onlymandatoryThe sum of the voltages for all of the batteries on a string in millivolts DC.
1.3.6.1.4.1.318.1.1.16.9.2.1.10ColumnbattManStringDischargeLess5Secondsread-onlymandatoryThe number of recorded discharges lasting less than 5 seconds.
1.3.6.1.4.1.318.1.1.16.9.2.1.11ColumnbattManStringDischarge5to10Secondsread-onlymandatoryThe number of recorded discharges lasting between 5 and 10 seconds.
1.3.6.1.4.1.318.1.1.16.9.2.1.12ColumnbattManStringDischarge10to60Secondsread-onlymandatoryThe number of recorded discharges lasting between 10 and 60 seconds.
1.3.6.1.4.1.318.1.1.16.9.2.1.13ColumnbattManStringDischargeMore60Secondsread-onlymandatoryThe number of recorded discharges lasting more than 60 seconds (1 minute).
1.3.6.1.4.1.318.1.1.16.10NodebattManBatteryStatus
1.3.6.1.4.1.318.1.1.16.10.1ScalarbattManString1BatteryTableSizeread-onlymandatoryThe number of entries in the battManString1BatteryTable.
1.3.6.1.4.1.318.1.1.16.10.2TablebattManString1BatteryTablenot-accessiblemandatoryAllows for getting information from each string in the system.
1.3.6.1.4.1.318.1.1.16.10.2.1RowbattManString1BatteryEntrynot-accessiblemandatoryThe string to get data from.
1.3.6.1.4.1.318.1.1.16.10.2.1.1ColumnbattManString1BatteryIndexread-onlymandatoryIndex of string entries in the table.
1.3.6.1.4.1.318.1.1.16.10.2.1.2ColumnbattManString1BatteryVoltageread-onlymandatoryThe battery voltage in millivolts DC.
1.3.6.1.4.1.318.1.1.16.10.2.1.3ColumnbattManString1BatteryLowestVoltageread-onlymandatoryThe lowest battery discharge voltage during the last power event in millivolts DC.
1.3.6.1.4.1.318.1.1.16.10.2.1.4ColumnbattManString1BatteryCellShortedread-onlymandatoryWhen set to alarm(2), indicates that a battery cell is shorted.
1.3.6.1.4.1.318.1.1.16.10.2.1.5ColumnbattManString1BatteryOpenFuseOrConnectionread-onlymandatoryWhen set to alarm(2), indicates that a fuse or connection is open.
1.3.6.1.4.1.318.1.1.16.10.2.1.6ColumnbattManString1BatteryLowCapacityread-onlymandatoryWhen set to alarm(2), indicates a battery has low capacity.
1.3.6.1.4.1.318.1.1.16.10.2.1.7ColumnbattManString1BatteryHighOhmicValueread-onlymandatoryWhen set to alarm(2), indicates a battery has a high ohmic value.
1.3.6.1.4.1.318.1.1.16.10.2.1.8ColumnbattManString1BatteryThermalRunawayread-onlymandatoryWhen set to alarm(2), indicates a battery has a thermal runaway condition.
1.3.6.1.4.1.318.1.1.16.10.2.1.9ColumnbattManString1BatteryDryoutread-onlymandatoryWhen set to alarm(2), indicates a battery has a dryout condition.
1.3.6.1.4.1.318.1.1.16.10.2.1.10ColumnbattManString1BatteryUserHighVoltageAlarmread-onlymandatoryWhen set to alarm(2), indicates a battery has violated the user level high voltage limit.
1.3.6.1.4.1.318.1.1.16.10.2.1.11ColumnbattManString1BatteryUserLowVoltageAlarmread-onlymandatoryWhen set to alarm(2), indicates a battery has violated the user level low voltage limit.
1.3.6.1.4.1.318.1.1.16.10.2.1.12ColumnbattManString1BatteryChemHighVoltageAlarmread-onlymandatoryWhen set to alarm(2), indicates a battery has violated the chemistry level high voltage limit.
1.3.6.1.4.1.318.1.1.16.10.2.1.13ColumnbattManString1BatteryChemLowVoltageAlarmread-onlymandatoryWhen set to alarm(2), indicates a battery has violated the chemistry level low voltage limit.
1.3.6.1.4.1.318.1.1.16.10.2.1.14ColumnbattManString1BatteryOpenCellread-onlymandatoryWhen set to alarm(2), indicates the battery has an open cell or an inter-connection is abnormal.
1.3.6.1.4.1.318.1.1.16.10.3ScalarbattManString2BatteryTableSizeread-onlymandatoryThe number of entries in the battManString2BatteryTable.
1.3.6.1.4.1.318.1.1.16.10.4TablebattManString2BatteryTablenot-accessiblemandatoryAllows for getting information from each string in the system.
1.3.6.1.4.1.318.1.1.16.10.4.1RowbattManString2BatteryEntrynot-accessiblemandatoryThe string to get data from.
1.3.6.1.4.1.318.1.1.16.10.4.1.1ColumnbattManString2BatteryIndexread-onlymandatoryIndex of string entries in the table.
1.3.6.1.4.1.318.1.1.16.10.4.1.2ColumnbattManString2BatteryVoltageread-onlymandatoryThe battery voltage in millivolts DC.
1.3.6.1.4.1.318.1.1.16.10.4.1.3ColumnbattManString2BatteryLowestVoltageread-onlymandatoryThe lowest battery discharge voltage during the last power event in millivolts DC.
1.3.6.1.4.1.318.1.1.16.10.4.1.4ColumnbattManString2BatteryCellShortedread-onlymandatoryWhen set to alarm(2), indicates that a battery cell is shorted.
1.3.6.1.4.1.318.1.1.16.10.4.1.5ColumnbattManString2BatteryOpenFuseOrConnectionread-onlymandatoryWhen set to alarm(2), indicates that a fuse or connection is open.
1.3.6.1.4.1.318.1.1.16.10.4.1.6ColumnbattManString2BatteryLowCapacityread-onlymandatoryWhen set to alarm(2), indicates a battery has low capacity.
1.3.6.1.4.1.318.1.1.16.10.4.1.7ColumnbattManString2BatteryHighOhmicValueread-onlymandatoryWhen set to alarm(2), indicates a battery has a high ohmic value.
1.3.6.1.4.1.318.1.1.16.10.4.1.8ColumnbattManString2BatteryThermalRunawayread-onlymandatoryWhen set to alarm(2), indicates a battery has a thermal runaway condition.
1.3.6.1.4.1.318.1.1.16.10.4.1.9ColumnbattManString2BatteryDryoutread-onlymandatoryWhen set to alarm(2), indicates a battery has a dryout condition.
1.3.6.1.4.1.318.1.1.16.10.4.1.10ColumnbattManString2BatteryUserHighVoltageAlarmread-onlymandatoryWhen set to alarm(2), indicates a battery has violated the user level high voltage limit.
1.3.6.1.4.1.318.1.1.16.10.4.1.11ColumnbattManString2BatteryUserLowVoltageAlarmread-onlymandatoryWhen set to alarm(2), indicates a battery has violated the user level low voltage limit.
1.3.6.1.4.1.318.1.1.16.10.4.1.12ColumnbattManString2BatteryChemHighVoltageAlarmread-onlymandatoryWhen set to alarm(2), indicates a battery has violated the chemistry level high voltage limit.
1.3.6.1.4.1.318.1.1.16.10.4.1.13ColumnbattManString2BatteryChemLowVoltageAlarmread-onlymandatoryWhen set to alarm(2), indicates a battery has violated the chemistry level low voltage limit.
1.3.6.1.4.1.318.1.1.16.10.4.1.14ColumnbattManString2BatteryOpenCellread-onlymandatoryWhen set to alarm(2), indicates the battery has an open cell or an inter-connection is abnormal.
1.3.6.1.4.1.318.1.1.16.11NodebattManInputContactStatus
1.3.6.1.4.1.318.1.1.16.11.1ScalarbattManInputContactTableSizeread-onlymandatoryThe number of entries in the battManInputContactTable.
1.3.6.1.4.1.318.1.1.16.11.2TablebattManInputContactTablenot-accessiblemandatoryAllows for getting information from each contact in the system.
1.3.6.1.4.1.318.1.1.16.11.2.1RowbattManInputContactEntrynot-accessiblemandatoryThe contact to get data from.
1.3.6.1.4.1.318.1.1.16.11.2.1.1ColumnbattManInputContactIndexread-onlymandatoryIndex of contact entries in the table.
1.3.6.1.4.1.318.1.1.16.11.2.1.2ColumnbattManInputContactNameread-writemandatoryThe name of the input contact.
1.3.6.1.4.1.318.1.1.16.11.2.1.3ColumnbattManInputContactAlarmStateread-onlymandatoryWhen set to alarm(2), indicates that the alarm condition is active for this contact.
1.3.6.1.4.1.318.1.1.16.11.2.1.4ColumnbattManInputContactStateread-onlymandatoryWhen set to open(1), the input contact is in the open state. When set to closed(2), the input contact is in the closed state.
1.3.6.1.4.1.318.1.1.16.11.2.1.5ColumnbattManInputContactNormalStateread-writemandatoryWhen set to open(1), the input contact is normally open. When set to closed(2), the input contact is normally closed.
1.3.6.1.4.1.318.1.1.16.11.2.1.6ColumnbattManInputContactAlarmDelayread-writemandatoryThe input contact alarm delay time in seconds.
1.3.6.1.4.1.318.1.1.16.12NodebattManControl
1.3.6.1.4.1.318.1.1.16.12.1ScalarbattManRemoteAnnunciatorResetread-writemandatorySetting this OID to reset(2) will reset the user interface annunciator. Getting this OID will do nothing and return the noOperation(1) value.
1.3.6.1.4.1.318.1.1.16.12.2ScalarbattManResetChargeCurrentDeviationBenchmarkread-writemandatorySetting this OID to reset(2) will reset the charge current deviation benchmark. Getting this OID will do nothing and return the noOperation(1) value.
1.3.6.1.4.1.318.1.1.16.12.3ScalarbattManResetLowestDischargeVoltagesread-writemandatorySetting this OID to reset(2) will reset the lowest discharge voltages. Getting this OID will do nothing and return the noOperation(1) value.
1.3.6.1.4.1.318.1.1.16.12.4ScalarbattManResetDischargeCountersread-writemandatorySetting this OID to reset(2) will reset all discharge event counters. Getting this OID will do nothing and return the noOperation(1) value.
1.3.6.1.4.1.318.1.1.16.13NodebattManTestResults
1.3.6.1.4.1.318.1.1.16.13.1ScalarbattManString1OhmicValueLastDischargeInforead-onlymandatoryInformational text showing the date/time, load, and pilot temperature for the string during the last discharge when ohmic values were recorded.
1.3.6.1.4.1.318.1.1.16.13.2ScalarbattManString1OhmicValueTableSizeread-onlymandatoryThe number of entries in the battManString1OhmicValueTable.
1.3.6.1.4.1.318.1.1.16.13.3TablebattManString1OhmicValueTablenot-accessiblemandatoryAllows for getting ohmic value information from each battery in String 1.
1.3.6.1.4.1.318.1.1.16.13.3.1RowbattManString1OhmicValueEntrynot-accessiblemandatoryThe string to get data from.
1.3.6.1.4.1.318.1.1.16.13.3.1.1ColumnbattManString1OhmicValueIndexread-onlymandatoryThe battery number.
1.3.6.1.4.1.318.1.1.16.13.3.1.2ColumnbattManString1OhmicValueDataread-onlymandatoryThe battery inter-tier ohmic value in ohms. Note: Zero or negative values are invalid and may indicate faulty calibration of ohmic value correction factors.
1.3.6.1.4.1.318.1.1.16.13.4ScalarbattManString1ResponseTestChangeTableSizeread-onlymandatoryThe number of entries in the battManString1ResponseTestChangeTable.
1.3.6.1.4.1.318.1.1.16.13.5TablebattManString1ResponseTestChangeTablenot-accessiblemandatoryAllows for getting response test change information from each battery in String 1.
1.3.6.1.4.1.318.1.1.16.13.5.1RowbattManString1ResponseTestChangeEntrynot-accessiblemandatoryThe string to get data from.
1.3.6.1.4.1.318.1.1.16.13.5.1.1ColumnbattManString1ResponseTestChangeIndexread-onlymandatoryIndex of the entries in the table.
1.3.6.1.4.1.318.1.1.16.13.5.1.2ColumnbattManString1ResponseTestChangeDataread-onlymandatoryThe battery response test change in percent.
1.3.6.1.4.1.318.1.1.16.13.6ScalarbattManString2OhmicValueLastDischargeInforead-onlymandatoryInformational text showing the date/time, load, and pilot temperature for the string during the last discharge when ohmic values were recorded.
1.3.6.1.4.1.318.1.1.16.13.7ScalarbattManString2OhmicValueTableSizeread-onlymandatoryThe number of entries in the battManString2OhmicValueTable.
1.3.6.1.4.1.318.1.1.16.13.8TablebattManString2OhmicValueTablenot-accessiblemandatoryAllows for getting ohmic value information from each battery in String 2.
1.3.6.1.4.1.318.1.1.16.13.8.1RowbattManString2OhmicValueEntrynot-accessiblemandatoryThe string to get data from.
1.3.6.1.4.1.318.1.1.16.13.8.1.1ColumnbattManString2OhmicValueIndexread-onlymandatoryIndex of battery calibration entries in the table.
1.3.6.1.4.1.318.1.1.16.13.8.1.2ColumnbattManString2OhmicValueDataread-onlymandatoryThe battery inter-tier ohmic value in ohms. Note: Zero or negative values are invalid and may indicate faulty calibration of ohmic value correction factors.
1.3.6.1.4.1.318.1.1.16.13.9ScalarbattManString2ResponseTestChangeTableSizeread-onlymandatoryThe number of entries in the battManString2ResponseTestChangeTable.
1.3.6.1.4.1.318.1.1.16.13.10TablebattManString2ResponseTestChangeTablenot-accessiblemandatoryAllows for getting response test change information from each battery in String 2.
1.3.6.1.4.1.318.1.1.16.13.10.1RowbattManString2ResponseTestChangeEntrynot-accessiblemandatoryThe string to get data from.
1.3.6.1.4.1.318.1.1.16.13.10.1.1ColumnbattManString2ResponseTestChangeIndexread-onlymandatoryIndex of the entries in the table.
1.3.6.1.4.1.318.1.1.16.13.10.1.2ColumnbattManString2ResponseTestChangeDataread-onlymandatoryThe battery response test change in percent.
1.3.6.1.4.1.318.1.1.16.13.11ScalarbattManString1ResponseTestCurrentTableSizeread-onlymandatoryThe number of entries in the battManString1ResponseTestCurrentTable.
1.3.6.1.4.1.318.1.1.16.13.12TablebattManString1ResponseTestCurrentTablenot-accessiblemandatoryAllows for getting response test current information from each battery in String 1.
1.3.6.1.4.1.318.1.1.16.13.12.1RowbattManString1ResponseTestCurrentEntrynot-accessiblemandatoryThe string to get data from.
1.3.6.1.4.1.318.1.1.16.13.12.1.1ColumnbattManString1ResponseTestCurrentIndexread-onlymandatoryIndex of the entries in the table.
1.3.6.1.4.1.318.1.1.16.13.12.1.2ColumnbattManString1ResponseTestCurrentDataread-onlymandatoryThe battery response test current in milliamps.
1.3.6.1.4.1.318.1.1.16.13.13ScalarbattManString2ResponseTestCurrentTableSizeread-onlymandatoryThe number of entries in the battManString2ResponseTestCurrentTable.
1.3.6.1.4.1.318.1.1.16.13.14TablebattManString2ResponseTestCurrentTablenot-accessiblemandatoryAllows for getting response test current information from each battery in String 2.
1.3.6.1.4.1.318.1.1.16.13.14.1RowbattManString2ResponseTestCurrentEntrynot-accessiblemandatoryThe string to get data from.
1.3.6.1.4.1.318.1.1.16.13.14.1.1ColumnbattManString2ResponseTestCurrentIndexread-onlymandatoryIndex of the entries in the table.
1.3.6.1.4.1.318.1.1.16.13.14.1.2ColumnbattManString2ResponseTestCurrentDataread-onlymandatoryThe battery response test current in milliamps.
1.3.6.1.4.1.318.1.1.16.13.15ScalarbattManString1ResponseTestCurrentBenchmarkTableSizeread-onlymandatoryThe number of entries in the battManString1ResponseTestCurrentBenchmarkTable.
1.3.6.1.4.1.318.1.1.16.13.16TablebattManString1ResponseTestCurrentBenchmarkTablenot-accessiblemandatoryAllows for getting response test current benchmark information from each battery in String 1.
1.3.6.1.4.1.318.1.1.16.13.16.1RowbattManString1ResponseTestCurrentBenchmarkEntrynot-accessiblemandatoryThe string to get data from.
1.3.6.1.4.1.318.1.1.16.13.16.1.1ColumnbattManString1ResponseTestCurrentBenchmarkIndexread-onlymandatoryIndex of the entries in the table.
1.3.6.1.4.1.318.1.1.16.13.16.1.2ColumnbattManString1ResponseTestCurrentBenchmarkDataread-onlymandatoryThe battery response test current benchmark in milliamps.
1.3.6.1.4.1.318.1.1.16.13.17ScalarbattManString2ResponseTestCurrentBenchmarkTableSizeread-onlymandatoryThe number of entries in the battManString2ResponseTestCurrentBenchmarkTable.
1.3.6.1.4.1.318.1.1.16.13.18TablebattManString2ResponseTestCurrentBenchmarkTablenot-accessiblemandatoryAllows for getting response test current benchmark information from each battery in String 2.
1.3.6.1.4.1.318.1.1.16.13.18.1RowbattManString2ResponseTestCurrentBenchmarkEntrynot-accessiblemandatoryThe string to get data from.
1.3.6.1.4.1.318.1.1.16.13.18.1.1ColumnbattManString2ResponseTestCurrentBenchmarkIndexread-onlymandatoryIndex of the entries in the table.
1.3.6.1.4.1.318.1.1.16.13.18.1.2ColumnbattManString2ResponseTestCurrentBenchmarkDataread-onlymandatoryThe battery response test current benchmark in milliamps.
1.3.6.1.4.1.318.1.1.16.14NodebattManUnitStatus
1.3.6.1.4.1.318.1.1.16.14.1ScalarbattManUnitStatusTableSizeread-onlymandatoryThe number of entries in the battManUnitStatusTable.
1.3.6.1.4.1.318.1.1.16.14.2TablebattManUnitStatusTablenot-accessiblemandatoryAllows for getting status information from each unit in the system.
1.3.6.1.4.1.318.1.1.16.14.2.1RowbattManUnitStatusEntrynot-accessiblemandatoryThe unit to get data from.
1.3.6.1.4.1.318.1.1.16.14.2.1.1ColumnbattManUnitStatusIndexread-onlymandatoryIndex of unit status entries in the table.
1.3.6.1.4.1.318.1.1.16.14.2.1.2ColumnbattManUnitStatusSerialNumberread-onlymandatoryThe battery manager unit serial number character string. This value is set at the factory.
1.3.6.1.4.1.318.1.1.16.14.2.1.3ColumnbattManUnitHardwareRevread-onlymandatoryThe battery manager unit hardware revision. This value is set at the factory.
1.3.6.1.4.1.318.1.1.16.14.2.1.4ColumnbattManUnitFirmwareRevread-onlymandatoryThe battery manager unit firmware revision. This value is set at the factory and can change with firmware update.
1.3.6.1.4.1.318.1.1.16.14.2.1.5ColumnbattManUnitCommLossread-onlymandatoryWhen set to alarm(2), indicates the system has lost communication with the unit.
1.3.6.1.4.1.318.1.1.16.14.2.1.6ColumnbattManUnitRelayStuckread-onlymandatoryWhen set to alarm(2), indicates the unit monitor relay is stuck.
1.3.6.1.4.1.318.1.1.17NodexATS
1.3.6.1.4.1.318.1.1.17.1NodexATSIdent
1.3.6.1.4.1.318.1.1.17.1.1ScalarxATSIdentProductNameread-writemandatoryThe name of the transfer switch unit.
1.3.6.1.4.1.318.1.1.17.1.2ScalarxATSIdentHardwareRevread-onlymandatoryThe hardware revision of the transfer switch. This value is set at the factory.
1.3.6.1.4.1.318.1.1.17.1.3ScalarxATSIdentFirmwareAppRevread-onlymandatoryAn ID string identifying the application firmware revision of the transfer switch.
1.3.6.1.4.1.318.1.1.17.1.4ScalarxATSIdentFirmwareAppOSRevread-onlymandatoryAn ID string identifying the application operating system firmware revision of the transfer switch.
1.3.6.1.4.1.318.1.1.17.1.5ScalarxATSIdentFirmwareControllerRevread-onlymandatoryAn ID string identifying the transfer switch controller firmware revision.
1.3.6.1.4.1.318.1.1.17.1.6ScalarxATSIdentDateOfManufactureread-onlymandatoryThe date when the transfer switch was manufactured in mm/dd/yyyy format. This value is set at the factory.
1.3.6.1.4.1.318.1.1.17.1.7ScalarxATSIdentModelNumberread-onlymandatoryA character string identifying the model number of the transfer switch. This value is set at the factory.
1.3.6.1.4.1.318.1.1.17.1.8ScalarxATSIdentSerialNumberread-onlymandatoryA character string identifying the serial number of the transfer switch. This value is set at the factory.
1.3.6.1.4.1.318.1.1.17.2NodexATSDevice
1.3.6.1.4.1.318.1.1.17.2.1ScalarxATSDeviceServiceTyperead-onlymandatoryThe type of utility input to the transfer switch. Either 3 wires (delta), or 4 wires (wye).
1.3.6.1.4.1.318.1.1.17.2.2ScalarxATSDeviceNominalVoltageread-onlymandatoryThe nominal line-to-neutral system voltage. Measured in Volts, line-to-line for a 3-wire service or line-to-neutral for a 4-wire service. -1 if not available.
1.3.6.1.4.1.318.1.1.17.2.3ScalarxATSDeviceNominalFrequencyread-onlymandatoryThe nominal system frequency. Measured in tenths of Hertz. -1 if not available.
1.3.6.1.4.1.318.1.1.17.2.4ScalarxATSDeviceTransferSwitchRatingread-onlymandatoryThe rating of the transfer switch. Measured in Amps.
1.3.6.1.4.1.318.1.1.17.2.5ScalarxATSDeviceDCBackUpPresentread-writemandatoryIndicates if a DC backup is present or not.
1.3.6.1.4.1.318.1.1.17.3NodexATSSwitch
1.3.6.1.4.1.318.1.1.17.3.1NodexATSSwitchStatus
1.3.6.1.4.1.318.1.1.17.3.1.1ScalarxATSSwitchStatusSelectedSourceread-onlymandatoryThe source which is currently selected, i.e. supplying power to the load.
1.3.6.1.4.1.318.1.1.17.3.1.2ScalarxATSSwitchStatusOperationalModeread-onlymandatoryThe current operating mode of the transfer switch. When the ATS is in automatic mode, generator starting and ATS transferring is all done automatically as need…
1.3.6.1.4.1.318.1.1.17.3.1.3ScalarxATSSwitchStatusAutomaticOperationSwitchread-onlymandatoryThe position of the automatic operation switch on the front of the transfer switch.
1.3.6.1.4.1.318.1.1.17.3.1.4ScalarxATSSwitchStatusEngineStartSignalread-onlymandatoryThe position of the Start/Stop contact which signals the generator engine to start/run. When the ATS is in automatic mode, generator starting/stopping is under…
1.3.6.1.4.1.318.1.1.17.3.2NodexATSSwitchSettings
1.3.6.1.4.1.318.1.1.17.3.2.1ScalarxATSSwitchSettingsLowVoltageTransferPointread-writemandatoryThe lowest acceptable voltage condition at source 1. When any phase of source 1 is lower than this voltage, source quality is considered bad and the generator …
1.3.6.1.4.1.318.1.1.17.3.2.2ScalarxATSSwitchSettingsHighVoltageTransferPointread-writemandatoryThe highest acceptable voltage condition at source 1. When any phase of source 1 is greater than this voltage, source quality is considered bad and the generat…
1.3.6.1.4.1.318.1.1.17.3.2.3ScalarxATSSwitchSettingsMaxFrequencyDeviationread-writemandatoryThe maximum acceptable frequency deviation condition from nominal at source 1. When source 1 frequency is outside the specified range, source quality is consid…
1.3.6.1.4.1.318.1.1.17.3.2.4ScalarxATSSwitchSettingsMinPhaseBalanceread-writemandatoryThe minimum required phase balance at source 1. When the percentage difference between the minimum and maximum phase voltage measurements at source 1 is greate…
1.3.6.1.4.1.318.1.1.17.3.2.5ScalarxATSSwitchSettingsNominalRotationread-writemandatoryThe nominal phase rotation (or phase sequence) required by the load. For certain types of equipment, such as rotating machinery, phase rotation is critical for…
1.3.6.1.4.1.318.1.1.17.3.2.6ScalarxATSSwitchSettingsAllowClosedTransferread-writemandatoryThis setting enables seamless (closed) transfers between sources. When possible, both source 1 and source 2 are closed to the output for a brief time. If close…
1.3.6.1.4.1.318.1.1.17.3.2.7ScalarxATSSwitchSettingsMaxSyncTimeread-writemandatoryWhen attempting/seeking to perform a closed transfer, this setting defines the maximum time allowed before the transfer switch will give up and perform an open…
1.3.6.1.4.1.318.1.1.17.3.2.8ScalarxATSSwitchSettingsNeutralTransferTimeread-writemandatoryThis setting defines how long both source 1 and source 2 will be disconnected from the output, during an open transfer. Specified in seconds. -1 if not availab…
1.3.6.1.4.1.318.1.1.17.3.2.9ScalarxATSSwitchSettingsClearLatchedAlarmsread-writemandatoryClears any latched alarm conditions.
1.3.6.1.4.1.318.1.1.17.3.2.10ScalarxATSSwitchSettingsSetToFactoryDefaultsread-writemandatorySets all transfer switch settings to factory default values.
1.3.6.1.4.1.318.1.1.17.3.3NodexATSSwitchTimers
1.3.6.1.4.1.318.1.1.17.3.3.1ScalarxATSSwitchTimersTableSizeread-onlymandatoryThe number of transfer switch timer entries.
1.3.6.1.4.1.318.1.1.17.3.3.2TablexATSSwitchTimersTablenot-accessiblemandatoryA list of timers supported by ATS. The number of entries is contained in the xATSSwitchTimersTableSize OID.
1.3.6.1.4.1.318.1.1.17.3.3.2.1RowxATSSwitchTimersEntrynot-accessiblemandatoryAn entry containing information about an individual ATS timer.
1.3.6.1.4.1.318.1.1.17.3.3.2.1.1ColumnxATSSwitchTimersIndexread-onlymandatoryIndex of timer entries in the table.
1.3.6.1.4.1.318.1.1.17.3.3.2.1.2ColumnxATSSwitchTimersNameread-onlymandatoryName of the individual timer.Refer to ATS operation manual, or on-line help, for detailed descriptions of ATS timers.
1.3.6.1.4.1.318.1.1.17.3.3.2.1.3ColumnxATSSwitchTimersAbortread-writemandatoryThis aborts the individual timer.
1.3.6.1.4.1.318.1.1.17.3.3.2.1.4ColumnxATSSwitchTimersStatusread-onlymandatoryThe status of the individual timer. Designates whether this timer entry is currently running or inactive.
1.3.6.1.4.1.318.1.1.17.3.3.2.1.5ColumnxATSSwitchTimersRemainingTimeread-onlymandatoryThe time remaining for this timer entry. Specified in seconds.
1.3.6.1.4.1.318.1.1.17.3.3.2.1.6ColumnxATSSwitchTimersDelaySettingread-writemandatoryThe delay settings associated with this timer entry. When this timer entry is active, the timer value must exceed this setting before the ATS behavior associat…
1.3.6.1.4.1.318.1.1.17.3.4NodexATSSwitchBlockMap
1.3.6.1.4.1.318.1.1.17.3.4.1ScalarxATSSwitchBlockMapTableSizeread-onlymandatoryThe number of blocking map entries, or how many ATS actions can be blocked.
1.3.6.1.4.1.318.1.1.17.3.4.2TablexATSSwitchBlockMapTablenot-accessiblemandatoryA list of blocking maps supported by the ATS. The number of entries is contained in the xATSSwitchBlockMapTableSize OID.
1.3.6.1.4.1.318.1.1.17.3.4.2.1RowxATSSwitchBlockMapEntrynot-accessiblemandatoryAn entry containing information about a specific ATS blocking map.
1.3.6.1.4.1.318.1.1.17.3.4.2.1.1ColumnxATSSwitchBlockMapIndexread-onlymandatoryIndex of blocking map entries in the table.
1.3.6.1.4.1.318.1.1.17.3.4.2.1.2ColumnxATSSwitchBlockMapNameread-onlymandatoryA string describing the ATS action to be blocked.
1.3.6.1.4.1.318.1.1.17.3.4.2.1.3ColumnxATSSwitchBlockMapStatusread-onlymandatoryRepresents the status of this blocking map entry, in bit-mapped format. A non-zero value indicates that this entry's ATS action is currently being blocked. The…
1.3.6.1.4.1.318.1.1.17.3.4.2.1.4ColumnxATSSwitchBlockMapSettingread-writemandatoryThis setting designates the inputs that block the ATS action The mapping is specified as a bit-field, where each bit set indicates the input that blocks the AT…
1.3.6.1.4.1.318.1.1.17.3.5NodexATSSwitchStatistics
1.3.6.1.4.1.318.1.1.17.3.5.1ScalarxATSSwitchStatisticsTableSizeread-onlymandatoryThe number of transfer switch statistics entries.
1.3.6.1.4.1.318.1.1.17.3.5.2TablexATSSwitchStatisticsTablenot-accessiblemandatoryA list of statistics supported by ATS. The number of entries is contained in the xATSSwitchStatisticsTableSize OID.
1.3.6.1.4.1.318.1.1.17.3.5.2.1RowxATSSwitchStatisticsEntrynot-accessiblemandatoryAn entry containing information about an individual ATS statistic.
1.3.6.1.4.1.318.1.1.17.3.5.2.1.1ColumnxATSSwitchStatisticsIndexread-onlymandatoryIndex of ATS statistics entries in the table.
1.3.6.1.4.1.318.1.1.17.3.5.2.1.2ColumnxATSSwitchStatisticsNameread-onlymandatoryThis is the name of the ATS statistic associated with this entry.
1.3.6.1.4.1.318.1.1.17.3.5.2.1.3ColumnxATSSwitchStatisticsValueread-onlymandatoryThis is the value of the ATS statistic associated with this entry.
1.3.6.1.4.1.318.1.1.17.3.5.2.1.4ColumnxATSSwitchStatisticsResetread-writemandatoryThis will reset the individual ATS statistic associated with this entry.
1.3.6.1.4.1.318.1.1.17.4NodexATSACMonitoringPoint
1.3.6.1.4.1.318.1.1.17.4.1NodexATSSource1
1.3.6.1.4.1.318.1.1.17.4.1.1ScalarxATSSource1Nameread-writemandatoryString used to identify source 1.
1.3.6.1.4.1.318.1.1.17.4.1.2ScalarxATSSource1Positionread-onlymandatoryThe current position of the switch at source 1.
1.3.6.1.4.1.318.1.1.17.4.1.3ScalarxATSSource1Frequencyread-onlymandatoryThe frequency at source 1 in tenths of Hertz. -1 if unavailable.
1.3.6.1.4.1.318.1.1.17.4.1.4ScalarxATSSource1Qualityread-onlymandatoryThe current line quality of source 1.
1.3.6.1.4.1.318.1.1.17.4.1.5ScalarxATSSource1Rotationread-onlymandatoryThe phase rotation measured at the source 1 input of the ATS. The sequence is a reference to the order in which the three phases pass the zero-crossing boundar…
1.3.6.1.4.1.318.1.1.17.4.1.6ScalarxATSSource1TableSizeread-onlymandatoryThe number of input voltage entries at the source 1 input of the ATS.
1.3.6.1.4.1.318.1.1.17.4.1.7TablexATSSource1PhaseTablenot-accessiblemandatoryA list of voltage table entries for source 1. The number of entries are the phase entries. The number of entries is contained in the xATSSource1TableSize OID.
1.3.6.1.4.1.318.1.1.17.4.1.7.1RowxATSSource1PhaseEntrynot-accessiblemandatoryAn entry containing information applicable to a particular input voltage phase at the source 1 input of the ATS.
1.3.6.1.4.1.318.1.1.17.4.1.7.1.1ColumnxATSSource1Indexread-onlymandatoryDescription of each phase utilized at source 1.
1.3.6.1.4.1.318.1.1.17.4.1.7.1.2ColumnxATSSource1VoltageLtoLread-onlymandatorySource 1 line-to-line input voltage. Measured in tenths of Volts.
1.3.6.1.4.1.318.1.1.17.4.1.7.1.3ColumnxATSSource1VoltageLtoNread-onlymandatorySource 1 line-to-neutral input voltage. Measured in tenths of Volts. -1 for a 3-wire service type.
1.3.6.1.4.1.318.1.1.17.4.2NodexATSSource2
1.3.6.1.4.1.318.1.1.17.4.2.1ScalarxATSSource2Nameread-writemandatoryString used to identify source 2.
1.3.6.1.4.1.318.1.1.17.4.2.2ScalarxATSSource2Positionread-onlymandatoryThe current position of the switch at source 2.
1.3.6.1.4.1.318.1.1.17.4.2.3ScalarxATSSource2Frequencyread-onlymandatoryThe frequency at source 2 in tenths of Hertz. -1 if not available.
1.3.6.1.4.1.318.1.1.17.4.2.4ScalarxATSSource2Qualityread-onlymandatoryThe current line quality of source 2.
1.3.6.1.4.1.318.1.1.17.4.2.5ScalarxATSSource2Rotationread-onlymandatoryThe phase rotation measured at the source 2 input of the ATS. -1 if not available.
1.3.6.1.4.1.318.1.1.17.4.2.6ScalarxATSSource2TableSizeread-onlymandatoryThe number of input voltage entries at the source 2 input of the ATS.
1.3.6.1.4.1.318.1.1.17.4.2.7TablexATSSource2PhaseTablenot-accessiblemandatoryA list of voltage table entries for the source 2. The number of entries are the phase entries. The number of entries is contained in the xATSSource2TableSize O…
1.3.6.1.4.1.318.1.1.17.4.2.7.1RowxATSSource2PhaseEntrynot-accessiblemandatoryAn entry containing information applicable to a particular input voltage phase at the source 2 input of the ATS.
1.3.6.1.4.1.318.1.1.17.4.2.7.1.1ColumnxATSSource2Indexread-onlymandatoryDescription of each phase utilized at the source 2.
1.3.6.1.4.1.318.1.1.17.4.2.7.1.2ColumnxATSSource2VoltageLtoLread-onlymandatorySource 2 line-to-line input voltage. Measured in tenths of Volts.
1.3.6.1.4.1.318.1.1.17.4.2.7.1.3ColumnxATSSource2VoltageLtoNread-onlymandatorySource 2 line-to-neutral input voltage. Measured in tenths of Volts. -1 for a 3-wire service type.
1.3.6.1.4.1.318.1.1.17.4.3NodexATSSystemOutput
1.3.6.1.4.1.318.1.1.17.4.3.1ScalarxATSSystemOutputFrequencyread-onlymandatoryThe system output frequency in tenths of Hertz.
1.3.6.1.4.1.318.1.1.17.4.3.2ScalarxATSSystemOutputTotalPowerread-onlymandatoryShows the total system output power in tenths of kW.
1.3.6.1.4.1.318.1.1.17.4.3.3ScalarxATSSystemOutputTotalApparentPowerread-onlymandatoryShows the total system output power in tenths of kVA.
1.3.6.1.4.1.318.1.1.17.4.3.4ScalarxATSSystemOutputTotalPowerFactorread-onlymandatoryIndicates the total power factor of the system output. A value of 100 representing a unity power factor (1.00) Specified in hundredths.
1.3.6.1.4.1.318.1.1.17.4.3.5ScalarxATSSystemOutputFrequencyToleranceread-writemandatoryShows the panel output frequency tolerance in +/- Hertz.
1.3.6.1.4.1.318.1.1.17.4.3.6ScalarxATSSystemOutputOverVoltThresholdread-writemandatoryThreshold above which an output over voltage condition will be generated. Specified as tenths of percent deviation from nominal. A value of zero indicates that…
1.3.6.1.4.1.318.1.1.17.4.3.7ScalarxATSSystemOutputUnderVoltThresholdread-writemandatoryThreshold below which an output under voltage condition will be generated. Specified as tenths of percent deviation from nominal. A value of zero indicates tha…
1.3.6.1.4.1.318.1.1.17.4.3.8ScalarxATSSystemOutputOverCurrentThresholdread-writemandatoryThreshold above which an over current condition will be generated. Specified as a percent of the transfer switch rating (xATSDeviceTransferSwitchRating OID). A…
1.3.6.1.4.1.318.1.1.17.4.3.9ScalarxATSSystemOutputUnderCurrentThresholdread-writemandatoryThreshold below which an under current condition will be generated. Specified as a percent of the transfer switch rating (xATSDeviceTransferSwitchRating OID). …
1.3.6.1.4.1.318.1.1.17.4.3.10ScalarxATSSystemOutputAlarmDelayThresholdread-writemandatoryDelay the generation of an output alarm. Specified in seconds.
1.3.6.1.4.1.318.1.1.17.4.3.11ScalarxATSSystemOutputTableSizeread-onlymandatoryThe number of system output phase entries.
1.3.6.1.4.1.318.1.1.17.4.3.12TablexATSSystemOutputPhaseTablenot-accessiblemandatoryA list of system output table entries. The number of entries is contained in the xATSSystemOutputTableSize OID.
1.3.6.1.4.1.318.1.1.17.4.3.12.1RowxATSSystemOutputPhaseEntrynot-accessiblemandatoryAn entry containing information applicable to a particular system output phase.
1.3.6.1.4.1.318.1.1.17.4.3.12.1.1ColumnxATSSystemOutputPhaseIndexread-onlymandatoryDescription of each system output phase utilized in this device.
1.3.6.1.4.1.318.1.1.17.4.3.12.1.2ColumnxATSSystemOutputVoltageLtoLread-onlymandatoryLine-to-line system output voltage available at the circuit panel. Measured in tenths of Volts. -1 if not available.
1.3.6.1.4.1.318.1.1.17.4.3.12.1.3ColumnxATSSystemOutputVoltageLtoNread-onlymandatoryLine-to-neutral system output voltage available at the circuit panel. Measured in tenths of Volts. -1 for a 3-wire service type or if not available.
1.3.6.1.4.1.318.1.1.17.4.3.12.1.4ColumnxATSSystemOutputPhaseCurrentread-onlymandatorySystem load current per phase. Measured in Amps. -1 if not available.
1.3.6.1.4.1.318.1.1.17.4.3.12.1.5ColumnxATSSystemOutputPowerread-onlymandatorySystem output power per phase. Measured in tenths of kW.
1.3.6.1.4.1.318.1.1.17.4.3.12.1.6ColumnxATSSystemOutputApparentPowerread-onlymandatorysystem output power per phase. Measured in tenths of kVA.
1.3.6.1.4.1.318.1.1.17.4.3.12.1.7ColumnxATSSystemOutputPowerFactorread-onlymandatoryindicates the power factor of the system output per phase. A value of 100 representing a unity power factor (1.00). Measured in hundredths.
1.3.6.1.4.1.318.1.1.17.5NodexATSTesting
1.3.6.1.4.1.318.1.1.17.5.1NodexATSTestingStatus
1.3.6.1.4.1.318.1.1.17.5.1.1ScalarxATSTestingStatusSelectTestProcessread-writemandatoryType of tests that can be selected when no test has been scheduled. engineStartTest and systemLoadTest may be selected when no tests are running. Tests that ar…
1.3.6.1.4.1.318.1.1.17.5.1.2ScalarxATSTestingStatusTestStatusread-onlymandatoryThe present system test status/state.
1.3.6.1.4.1.318.1.1.17.5.1.3ScalarxATSTestingStatusProfileWarmupTimeread-writemandatoryThe amount of time that the generator will warm up during a test. This is portion of the test when the xATSTestingStatusTestStatus OID returns the value engine…
1.3.6.1.4.1.318.1.1.17.5.1.4ScalarxATSTestingStatusProfileLoadedTimeread-writemandatoryThe amount of time that ATS will apply the system load to the generator during a system load test. This is portion of the test when the xATSTestingStatusTestSt…
1.3.6.1.4.1.318.1.1.17.5.1.5ScalarxATSTestingStatusProfileUnloadedTimeread-writemandatoryThe amount of time that the generator will run following the warm up portion of a start test, or the loaded portion of a load test. This is portion of the test…
1.3.6.1.4.1.318.1.1.17.5.2NodexATSTestingResults
1.3.6.1.4.1.318.1.1.17.5.2.1ScalarxATSTestingResultsLastDateOfTestread-onlymandatoryDate of the last test that was performed, either scheduled or manual. Test results are available in the xATSTestingResultsLastResult OID. Specified in the dd/m…
1.3.6.1.4.1.318.1.1.17.5.2.2ScalarxATSTestingResultsLastResultread-onlymandatoryThe result of the last ATS/generator system test.
1.3.6.1.4.1.318.1.1.17.5.2.3ScalarxATSTestingResultsTestLastTestTimeread-onlymandatoryTime of day at which the last test was performed, either scheduled or manual. Test results are available in the xATSTestingResultsLastResult OID. Specified in …
1.3.6.1.4.1.318.1.1.17.5.2.4ScalarxATSTestingResultsLastCrankDurationread-onlymandatoryThe time spent cranking the generator before it started during the last test. Specified in seconds, or -1 if not available.
1.3.6.1.4.1.318.1.1.17.5.2.5ScalarxATSTestingResultsLastWarmupDurationread-onlymandatoryThe time spent in the engineWarmingUp state during the last system test. Specified in seconds, or -1 if not available.
1.3.6.1.4.1.318.1.1.17.5.2.6ScalarxATSTestingResultsLastLoadedDurationread-onlymandatoryThe time spent in the testingWithLoad state during the last system test. Specified in seconds, or -1 if not available.
1.3.6.1.4.1.318.1.1.17.5.2.7ScalarxATSTestingResultsLastUnloadedDurationread-onlymandatoryThe time spent in the testingWithoutLoad state during the last system test. Specified in seconds, or -1 if not available.
1.3.6.1.4.1.318.1.1.17.5.3NodexATSTestingSchedule
1.3.6.1.4.1.318.1.1.17.5.3.1ScalarxATSTestingScheduleFrequencyread-writemandatoryThe frequency of running scheduled tests.
1.3.6.1.4.1.318.1.1.17.5.3.2ScalarxATSTestingScheduleTestDayread-writemandatoryThe desired day for the scheduled test. This object applies only when the xATSTestingScheduleFrequency OID is set to weekly or monthly. For weekly test frequen…
1.3.6.1.4.1.318.1.1.17.5.3.3ScalarxATSTestingScheduleTestTimeread-writemandatoryThe time of day that the scheduled test will occur. Specified in the format hh:mm.
1.3.6.1.4.1.318.1.1.17.5.3.4ScalarxATSTestingScheduleTestWithLoadIntervalread-writemandatoryThis setting specifies which system tests should include applying the load to the generator. The applyLoadMonthlyDetailed entry in the list will apply load onc…
1.3.6.1.4.1.318.1.1.17.5.3.5ScalarxATSTestingScheduleTestWithLoadSelectMonthread-writemandatoryThe detailed selection for testing with load on a month-by-month basis. This object is applicable when the xATSTestingScheduleTestWithLoadInterval is set to ap…
1.3.6.1.4.1.318.1.1.17.5.3.6ScalarxATSTestingScheduleNextTestDateread-onlymandatoryThe date of the next scheduled test, in the format dd-mmm-yyyy.
1.3.6.1.4.1.318.1.1.17.5.4NodexATSTestingSimulatePowerFail
1.3.6.1.4.1.318.1.1.17.5.4.1ScalarxATSTestingSimulatePowerFailTestread-writemandatoryThis object executes a simulated power failure for the duration indicated. Simulation can be aborted by selecting cancelSimulation.
1.3.6.1.4.1.318.1.1.17.5.4.2ScalarxATSTestingSimulatePowerFailTimeRemainingread-onlymandatoryIndicates the time remaining in seconds, for a simulated power failure. a value of zero indicates that simulated power failure is not active.
1.3.6.1.4.1.318.1.1.17.6NodexATSInputContacts
1.3.6.1.4.1.318.1.1.17.6.1ScalarxATSInputContactNumContactsread-onlymandatoryThe number of contacts supported by the ATS.
1.3.6.1.4.1.318.1.1.17.6.2ScalarxATSInputContactTableSizeread-onlymandatoryThe number of input contact entries.
1.3.6.1.4.1.318.1.1.17.6.3TablexATSInputContactTablenot-accessiblemandatoryA list of contacts supported by the ATS. The number of entries is contained in the xATSInputContactTableSize OID.
1.3.6.1.4.1.318.1.1.17.6.3.1RowxATSInputContactEntrynot-accessiblemandatoryA contact entry containing information for a given contact.
1.3.6.1.4.1.318.1.1.17.6.3.1.1ColumnxATSInputContactNumberread-onlymandatoryAn index identifying the contact on the ATS.
1.3.6.1.4.1.318.1.1.17.6.3.1.2ColumnxATSInputContactNameread-writemandatoryThe description of the purpose/use of the contact.
1.3.6.1.4.1.318.1.1.17.6.3.1.3ColumnxATSInputContactNormalStateread-writemandatoryThe normal operating position of the contact.
1.3.6.1.4.1.318.1.1.17.6.3.1.4ColumnxATSInputContactCurrentStateread-onlymandatoryThis value indicates the current state of the contact.
1.3.6.1.4.1.318.1.1.17.7NodexATSOutputRelays
1.3.6.1.4.1.318.1.1.17.7.1ScalarxATSOutputRelayNumRelaysread-onlymandatoryThe number of output relays supported by the ATS.
1.3.6.1.4.1.318.1.1.17.7.2ScalarxATSOutputRelayTableSizeread-onlymandatoryThe number of output relay entries.
1.3.6.1.4.1.318.1.1.17.7.3TablexATSOutputRelayTablenot-accessiblemandatoryA list of output relays supported by the ATS. The number of entries is contained in the xATSOutputRelayTableSize OID.
1.3.6.1.4.1.318.1.1.17.7.3.1RowxATSOutputRelayEntrynot-accessiblemandatoryA output relay entry containing information for a given contact.
1.3.6.1.4.1.318.1.1.17.7.3.1.1ColumnxATSOutputRelayNumberread-onlymandatoryAn index identifying the output relay on the ATS.
1.3.6.1.4.1.318.1.1.17.7.3.1.2ColumnxATSOutputRelayNameread-writemandatoryThe description of the purpose/use of the output relay.
1.3.6.1.4.1.318.1.1.17.7.3.1.3ColumnxATSOutputRelayNormalStateread-writemandatoryThe normal operating position of the output relay.
1.3.6.1.4.1.318.1.1.17.7.3.1.4ColumnxATSOutputRelayCurrentStateread-onlymandatoryThis value indicates the current state of the output relay.
1.3.6.1.4.1.318.1.1.17.8NodexATSMisc
1.3.6.1.4.1.318.1.1.18Nodegenerator
1.3.6.1.4.1.318.1.1.18.1NodexATSGenerator
1.3.6.1.4.1.318.1.1.18.1.1NodexATSGeneratorIdent
1.3.6.1.4.1.318.1.1.18.1.1.1ScalarxATSGeneratorIdentModelNumberread-onlymandatoryA character string identifying the model number of the generator. This value is set at the factory.
1.3.6.1.4.1.318.1.1.18.1.1.2ScalarxATSGeneratorIdentSerialNumberread-onlymandatoryA character string identifying the serial number of the generator. This value is set at the factory.
1.3.6.1.4.1.318.1.1.18.1.1.3ScalarxATSGeneratorIdentDateofManufactureread-onlymandatoryA character string identifying when the generator was manufactured in mm/dd/yyyy format. This value is set at the factory.
1.3.6.1.4.1.318.1.1.18.1.1.4ScalarxATSGeneratorIdentVoltageConfigurationread-onlymandatoryThe voltage for which the generator's alternator is designed. Specified in Volts line-to-line.
1.3.6.1.4.1.318.1.1.18.1.1.5ScalarxATSGeneratorIdentMaxPowerRatingread-onlymandatoryThe max power rating of the generator. Specified in kW.
1.3.6.1.4.1.318.1.1.18.1.1.6ScalarxATSGeneratorIdentAlternatorFrequencyread-onlymandatoryThe frequency for which the generator's alternator is designed. Specified in Hertz.
1.3.6.1.4.1.318.1.1.18.1.2NodexATSGeneratorStatus
1.3.6.1.4.1.318.1.1.18.1.2.1ScalarxATSGeneratorStatusGeneratorNameread-writemandatoryThe name or label for the generator connected to the source 2 of the ATS.
1.3.6.1.4.1.318.1.1.18.1.2.2ScalarxATSGeneratorStatusOperationalread-onlymandatoryThe operational status of the generator. unavailable when unrecognized status is received.
1.3.6.1.4.1.318.1.1.18.1.2.3ScalarxATSGeneratorStatusModeSwitchPositionread-onlymandatoryThe position of the generator's auto-mode switch. In automatic mode, the generator is started and stopped via the remote start contact, which has state indicat…
1.3.6.1.4.1.318.1.1.18.1.2.4ScalarxATSGeneratorStatusRemoteStartread-onlymandatoryThe status of the generator's remote start contact, which is provided as an output from the transfer switch to start/stop the generator when in automatic mode.
1.3.6.1.4.1.318.1.1.18.1.3NodexATSGeneratorAdvStatus
1.3.6.1.4.1.318.1.1.18.1.3.1ScalarxATSGeneratorAdvStatusBatteryVoltageread-onlymandatoryThe voltage of the generator's starting battery. Measured in tenths of VDC, or -1 if not available.
1.3.6.1.4.1.318.1.1.18.1.3.2ScalarxATSGeneratorAdvStatusOilPressureread-onlymandatoryThe generator's engine oil pressure. Measured in tenths of Psi or kPa, based on the value of the xATSGeneratorSettingsMetricUnit OID, or -1 if not available.
1.3.6.1.4.1.318.1.1.18.1.3.3ScalarxATSGeneratorAdvStatusCoolantTemperatureread-onlymandatoryCurrent coolant temperature in the generator. Measured in degrees Celsius or Fahrenheit, based on the value of the xATSGeneratorSettingsMetricUnit OID, or -1 i…
1.3.6.1.4.1.318.1.1.18.1.3.4ScalarxATSGeneratorAdvStatusEngineRPMread-onlymandatoryCurrent engine speed of the generator. Measured in RPM, or -1 if not available.
1.3.6.1.4.1.318.1.1.18.1.3.5ScalarxATSGeneratorAdvStatusOilLevelread-onlymandatoryIndicates adequate oil level in the generator.
1.3.6.1.4.1.318.1.1.18.1.3.6ScalarxATSGeneratorAdvStatusCoolantLevelread-onlymandatoryIndicates adequate coolant level in the generator.
1.3.6.1.4.1.318.1.1.18.1.4NodexATSGeneratorOutput
1.3.6.1.4.1.318.1.1.18.1.4.1ScalarxATSGeneratorOutputFrequencyread-onlymandatoryThe output frequency of the generator. Measured in tenths of Hertz, or -1 if not available.
1.3.6.1.4.1.318.1.1.18.1.4.2ScalarxATSGeneratorOutputTotalPowerread-onlymandatoryThe total output power of the generator. Measured in tenths of tenths of kW, or -1 if not available.
1.3.6.1.4.1.318.1.1.18.1.4.3ScalarxATSGeneratorOutputTotalApparentPowerread-onlymandatoryThe total output power of the generator. Measured in tenths of kVA, or -1 if not available.
1.3.6.1.4.1.318.1.1.18.1.4.4ScalarxATSGeneratorOutputTotalPowerFactorread-onlymandatoryIndicates the total load power factor of the generator. A value of 100 representing a unity power factor (1.00), or -1 when if not available.
1.3.6.1.4.1.318.1.1.18.1.4.5ScalarxATSGeneratorOutputTableSizeread-onlymandatoryThe number of generator output phase entries.
1.3.6.1.4.1.318.1.1.18.1.4.6TablexATSGeneratorOutputPhaseTablenot-accessiblemandatoryA list of generator output table entries. The number of entries is contained in the xATSGeneratorOutputTableSize OID.
1.3.6.1.4.1.318.1.1.18.1.4.6.1RowxATSGeneratorOutputPhaseEntrynot-accessiblemandatoryAn entry containing information applicable to a particular generator output phase.
1.3.6.1.4.1.318.1.1.18.1.4.6.1.1ColumnxATSGeneratorOutputPhaseIndexread-onlymandatoryDescription of each generator output phase utilized in this device.
1.3.6.1.4.1.318.1.1.18.1.4.6.1.2ColumnxATSGeneratorOutputVoltageLtoLread-onlymandatoryLine-to-line generator output voltage. Measured in Volts, or -1 if not available.
1.3.6.1.4.1.318.1.1.18.1.4.6.1.3ColumnxATSGeneratorOutputVoltageLtoNread-onlymandatoryLine-to-neutral generator output voltage. Measured in volts, or -1 if not available.
1.3.6.1.4.1.318.1.1.18.1.4.6.1.4ColumnxATSGeneratorOutputPhaseCurrentread-onlymandatoryGenerator load current per phase. Measured in Amps, or -1 if not available.
1.3.6.1.4.1.318.1.1.18.1.4.6.1.5ColumnxATSGeneratorOutputPowerread-onlymandatoryGenerator output power per phase. Measured in tenths of kW, or -1 if not available.
1.3.6.1.4.1.318.1.1.18.1.4.6.1.6ColumnxATSGeneratorOutputApparentPowerread-onlymandatoryGenerator output power per phase. Measured in tenths of kVA, or -1 if not available.
1.3.6.1.4.1.318.1.1.18.1.4.6.1.7ColumnxATSGeneratorOutputPowerFactorread-onlymandatoryIndicates the load power factor of the generator output per phase. A value of 100 representing a unity power factor (1.00), or -1 if not available.
1.3.6.1.4.1.318.1.1.18.1.5NodexATSGeneratorSettings
1.3.6.1.4.1.318.1.1.18.1.5.1ScalarxATSGeneratorSettingsVoltageAdjustread-onlymandatoryThe voltage adjust of the generator. Specified in volts line-to-line, or -1 if not available.
1.3.6.1.4.1.318.1.1.18.1.5.2ScalarxATSGeneratorSettingsFrequencyAdjustread-onlymandatoryThe frequency adjust of the generator. Specified in tenths of Hertz.
1.3.6.1.4.1.318.1.1.18.1.5.3ScalarxATSGeneratorSettingsStartDelayread-onlymandatoryThe delay, in seconds, after the remote run signal is activated before the generator's engine will be cranked to start, or -1 if not available.
1.3.6.1.4.1.318.1.1.18.1.5.4ScalarxATSGeneratorSettingsStopDelayread-onlymandatoryThe delay, in seconds, before the generator will stop after the remote run signal is deactivated, or -1 if not available.
1.3.6.1.4.1.318.1.1.18.1.5.5ScalarxATSGeneratorSettingsCrankCycleEnableread-onlymandatoryWhen Crank Cycle is enabled, the engine will be cranked up to the time specified by the xATSGeneratorSettingsCrankTime OID. If the generator's engine does not …
1.3.6.1.4.1.318.1.1.18.1.5.6ScalarxATSGeneratorSettingsCrankTimeread-onlymandatoryThe duration of engine cranking, in seconds, when starting the generator. Applicable when the xATSGeneratorSettingsCrankCycleEnable OID is enabled. -1 if not a…
1.3.6.1.4.1.318.1.1.18.1.5.7ScalarxATSGeneratorSettingsCrankRestTimeread-onlymandatoryThe pause duration, in seconds, following an unsuccessful attempt to start the generator. Applicable when the xATSGeneratorSettingsCrankCycleEnable OID is enab…
1.3.6.1.4.1.318.1.1.18.1.5.8ScalarxATSGeneratorSettingsNumberCrankread-onlymandatoryThe number of failed crank attempts before giving up on starting the generator. Applicable when the xATSGeneratorSettingsCrankCycleEnable OID is enabled. -1 if…
1.3.6.1.4.1.318.1.1.18.1.5.9ScalarxATSGeneratorSettingsMetricUnitread-writemandatorySpecifies the use of metric units in generator related OIDs, as well as on all other interfaces including the generator's local interface.
1.3.6.1.4.1.318.1.1.18.1.6NodexATSGeneratorService
1.3.6.1.4.1.318.1.1.18.1.6.1ScalarxATSGeneratorServiceTotalRunHoursLifetimeread-onlymandatoryTotal time that the generator engine has been run, over the life of the generator. Measured in hours. -1 if not available.
1.3.6.1.4.1.318.1.1.18.1.6.2ScalarxATSGeneratorServiceEngineStartsLifetimeread-onlymandatoryNumber of engine starts over the life of the generator. -1 if not available.
1.3.6.1.4.1.318.1.1.18.1.6.3ScalarxATSGeneratorServiceTotalkWhLifetimeread-onlymandatoryTotal kWh of operation over the life of the generator. -1 if not available.
1.3.6.1.4.1.318.1.1.18.1.6.4ScalarxATSGeneratorServiceTotalRunHoursSinceMaintenanceread-onlymandatoryTotal time that the generator engine has been run, since last service maintenance. Measured in tenths of hours. -1 if not available.
1.3.6.1.4.1.318.1.1.18.1.6.5ScalarxATSGeneratorServiceEngineStartsSinceMaintenanceread-onlymandatoryNumber of engine starts since last service maintenance. -1 if not available.
1.3.6.1.4.1.318.1.1.18.1.6.6ScalarxATSGeneratorServiceTotalkWhMaintenanceread-onlymandatoryTotal kWh of operation since last service maintenance. -1 if not available.
1.3.6.1.4.1.318.1.1.18.1.6.7ScalarxATSGeneratorServiceResetRecordread-writemandatoryResets the engine start counter, engine run-hours, and kWh values that have accumulated in the generator since last maintenance. Also, the last service date wi…
1.3.6.1.4.1.318.1.1.18.1.6.8ScalarxATSGeneratorServiceRecordResetDateread-onlymandatoryDate at which the generator's service record was reset, in dd-mmm-yyyy format.
1.3.6.1.4.1.318.1.1.18.1.6.9ScalarxATSGeneratorServiceNextServiceDateread-onlymandatoryDate at which the next generator service is due in dd-mmm-yyyy format. Based on the xATSGeneratorServiceCalendarIntervalThreshold OID or '' if the calendar-bas…
1.3.6.1.4.1.318.1.1.18.1.6.10ScalarxATSGeneratorServiceRunHoursUntilServiceDateread-onlymandatoryRun hours until the next generator service is due, in hours. Based on the xATSGeneratorServiceRunHoursThreshold OID or -1 if the run hour-based threshold is se…
1.3.6.1.4.1.318.1.1.18.1.6.11ScalarxATSGeneratorServiceRunHoursThresholdread-writemandatoryRun hour-based service interval. When the run-hours since service surpasses this threshold, generator service is due.
1.3.6.1.4.1.318.1.1.18.1.6.12ScalarxATSGeneratorServiceCalendarIntervalThresholdread-writemandatoryCalendar-based service interval. When the next service date, as indicated by the xATSGeneratorServiceNextServiceDate OID is in the past, generator is due for s…
1.3.6.1.4.1.318.1.1.18.1.7NodexATSGeneratorFuelSystem
1.3.6.1.4.1.318.1.1.18.1.7.1ScalarxATSGeneratorFuelSystemTyperead-onlymandatoryThe type of fuel used by the generator.
1.3.6.1.4.1.318.1.1.18.1.7.2ScalarxATSGeneratorFuelSystemTankSizeread-onlymandatorySize of the generator's fuel tank. Specified in gallons or liters, based on the value of the xATSGeneratorSettingsMetricUnit OID, or -1 if not available.
1.3.6.1.4.1.318.1.1.18.1.7.3ScalarxATSGeneratorFuelSystemFuelLevelread-onlymandatoryFuel remaining in the generator tank. Measured in percent of tank fill, or -1 if not available.
1.3.6.1.4.1.318.1.1.18.1.7.4ScalarxATSGeneratorFuelSystemRuntimePowerread-onlymandatoryThe power value used in the runtime remaining calculation. Measured in tenths of kW, or -1 if not available.
1.3.6.1.4.1.318.1.1.18.1.7.5ScalarxATSGeneratorFuelSystemEstimatedRunTimeread-onlymandatoryAn estimate of available runtime for the generator, based on available fuel as specified in the xATSGeneratorFuelSystemFuelLevel OID and kW load as specified i…
1.3.6.1.4.1.318.1.1.18.1.7.6ScalarxATSGeneratorFuelSystemLowRunTimeThresholdread-writemandatoryThreshold below which a low runtime alarm will exist.
1.3.6.1.4.1.318.1.1.18.1.7.7ScalarxATSGeneratorFuelSystemVeryLowRunTimeThresholdread-writemandatoryThreshold below which a very low runtime alarm will exist.
1.3.6.1.4.1.318.1.1.18.1.7.8ScalarxATSGeneratorFuelSystemLowFuelLevelThresholdread-writemandatoryThreshold below which a low fuel alarm will exist, with a value of 0 indicating disabled. Specified as percent of tank fill.
1.3.6.1.4.1.318.1.1.18.1.7.9ScalarxATSGeneratorFuelSystemVeryLowFuelLevelThresholdread-writemandatoryThreshold below which a very low fuel alarm will exist, with a value of 0 indicating disabled. Specified as percent of tank fill.
1.3.6.1.4.1.318.1.1.19NodeconsolePortServer
1.3.6.1.4.1.318.1.1.19.1NodecpsAP930x
1.3.6.1.4.1.318.1.1.19.1.1NodecpsAP930xSys
1.3.6.1.4.1.318.1.1.19.1.1.1ScalarapCPSpnameread-onlymandatoryThe product's name.
1.3.6.1.4.1.318.1.1.19.1.1.2ScalarapCPSversionread-onlymandatoryThe firmware's version.
1.3.6.1.4.1.318.1.1.19.1.1.3NodeapCPSPower
1.3.6.1.4.1.318.1.1.19.1.1.3.1ScalarapCPSPwNumread-onlymandatoryThe number of the power supplies.
1.3.6.1.4.1.318.1.1.19.1.1.3.2ScalarapCPSPw1read-onlymandatoryState of the first power supply. 0 will indicate not installed, 1 will indicate power ON, 2 will indicate power OFF.
1.3.6.1.4.1.318.1.1.19.1.1.3.3ScalarapCPSPw2read-onlymandatoryState of the second power supply. 0 will indicate not installed, 1 will indicate power ON, 2 will indicate power OFF.
1.3.6.1.4.1.318.1.1.19.1.1.4NodeapCPSPcmcia
1.3.6.1.4.1.318.1.1.19.1.1.4.1ScalarapCPSNPcmciaread-onlymandatoryNumber of PCMCIA cards available.
1.3.6.1.4.1.318.1.1.19.1.1.4.2TablecpsCardIdentTablenot-accessiblemandatoryA table of PCMCIA card identifications.
1.3.6.1.4.1.318.1.1.19.1.1.4.2.1RowcpsCardIdentEntrynot-accessiblemandatoryIdentification information for a PCMCIA card.
1.3.6.1.4.1.318.1.1.19.1.1.4.2.1.1ColumncpsCardIdentIndexread-onlymandatoryNumber to identify the socket Card.
1.3.6.1.4.1.318.1.1.19.1.1.4.2.1.2ColumncpsCardIdentProdread-onlymandatoryProduct identification string.
1.3.6.1.4.1.318.1.1.19.1.1.4.2.1.3ColumncpsCardIdentManread-onlymandatoryManufacturer ID code.
1.3.6.1.4.1.318.1.1.19.1.1.4.2.1.4ColumncpsCardIdentFuncread-onlymandatoryFunction ID code.
1.3.6.1.4.1.318.1.1.19.1.1.4.2.1.5ColumncpsCardIdentPCIread-onlymandatoryPCI ID
1.3.6.1.4.1.318.1.1.19.1.1.4.3TablecpsCardConfTablenot-accessiblemandatoryA table of socket configuration information.
1.3.6.1.4.1.318.1.1.19.1.1.4.3.1RowcpsCardConfEntrynot-accessiblemandatoryConfiguration information for a socket.
1.3.6.1.4.1.318.1.1.19.1.1.4.3.1.1ColumncpsCardConfIndexread-onlymandatoryNumber to identify the socket PCMCIA.
1.3.6.1.4.1.318.1.1.19.1.1.4.3.1.2ColumncpsCardConfPowerread-onlymandatoryPower Settings.
1.3.6.1.4.1.318.1.1.19.1.1.4.3.1.3ColumncpsCardConfTyperead-onlymandatoryInterface Type.
1.3.6.1.4.1.318.1.1.19.1.1.4.3.1.4ColumncpsCardConfInterread-onlymandatoryInterrupt number.
1.3.6.1.4.1.318.1.1.19.1.1.4.3.1.5ColumncpsCardConfFuncread-onlymandatoryFunction.
1.3.6.1.4.1.318.1.1.19.1.1.4.3.1.6ColumncpsCardConfCardvread-onlymandatoryCard values.
1.3.6.1.4.1.318.1.1.19.1.1.4.3.1.7ColumncpsCardConfPort1read-onlymandatoryI/O Port 1.
1.3.6.1.4.1.318.1.1.19.1.1.4.3.1.8ColumncpsCardConfPort2read-onlymandatoryI/O Port 2.
1.3.6.1.4.1.318.1.1.19.1.1.4.4TablecpsCardStatusTablenot-accessiblemandatoryA table of current socket status information.
1.3.6.1.4.1.318.1.1.19.1.1.4.4.1RowcpsCardStatusEntrynot-accessiblemandatoryCurrent status information for a socket.
1.3.6.1.4.1.318.1.1.19.1.1.4.4.1.1ColumncpsCardStatusIndexread-onlymandatoryNumber to identify the socket PCMCIA.
1.3.6.1.4.1.318.1.1.19.1.1.4.4.1.2ColumncpsCardStatusCardread-onlymandatoryCurrent Card State.
1.3.6.1.4.1.318.1.1.19.1.1.4.4.1.3ColumncpsCardStatusFuncread-onlymandatoryCurrent Function.
1.3.6.1.4.1.318.1.1.19.1.1.5ScalarapCPSFlashSizeread-onlymandatoryTotal amount of flash memory in Mbytes.
1.3.6.1.4.1.318.1.1.19.1.1.6ScalarapCPSRAMSizeread-onlymandatoryTotal amount of RAM in Mbytes.
1.3.6.1.4.1.318.1.1.19.1.1.7ScalarapCPSCPUfreqread-onlymandatoryCPU clock in MHz.
1.3.6.1.4.1.318.1.1.19.1.1.8ScalarapCPSDevIdread-onlymandatoryThe product's identifier.
1.3.6.1.4.1.318.1.1.19.1.2NodecpsAP930xConf
1.3.6.1.4.1.318.1.1.19.1.2.1ScalarcpsHostNameread-writemandatoryThe Host Name.
1.3.6.1.4.1.318.1.1.19.1.2.2ScalarcpsConsoleBannerread-writemandatoryThe console banner.
1.3.6.1.4.1.318.1.1.19.1.2.3ScalarcpsMotdread-writemandatoryThe motd message.
1.3.6.1.4.1.318.1.1.19.1.2.4NodecpsEthItf
1.3.6.1.4.1.318.1.1.19.1.2.4.1ScalarcpsEthDhcpcread-writemandatory0 will indicate DHCP inactive, 1 will indicate DHCP active, 2 will indicate DHCP active and the last parameter is saved.
1.3.6.1.4.1.318.1.1.19.1.2.4.2ScalarcpsEthIPaddrread-writemandatoryThis is the IP address of the Ethernet Interface.
1.3.6.1.4.1.318.1.1.19.1.2.4.3ScalarcpsEthIPmaskread-writemandatoryThe mask for the Ethernet network.
1.3.6.1.4.1.318.1.1.19.1.2.4.4ScalarcpsEthMTUread-writemandatoryThe Maximum Transmission Unit size, which determines whether packets should be broken up.
1.3.6.1.4.1.318.1.1.19.1.2.4.5ScalarcpsEthIPaddr2read-writemandatoryThe Ethernet secondary IP address.
1.3.6.1.4.1.318.1.1.19.1.2.4.6ScalarcpsEthIPmask2read-writemandatoryThe Ethernet secondary IP mask.
1.3.6.1.4.1.318.1.1.19.1.2.5NodecpsNameService
1.3.6.1.4.1.318.1.1.19.1.2.5.1ScalarcpsResolverOrderread-writemandatorySpecifies how host lookups are to be performed. Valid values : empty, 'hosts', 'bind', 'hosts, bind', 'bind, hosts'
1.3.6.1.4.1.318.1.1.19.1.2.5.2ScalarcpsMultipleIPread-writemandatoryValid values are ON or OFF. If set to ON, the resolve library will return all valid addresses for a host that appears in the /etc/hosts file, instead of only t…
1.3.6.1.4.1.318.1.1.19.1.2.5.3NodecpsDNSserv
1.3.6.1.4.1.318.1.1.19.1.2.5.3.1ScalarcpsDNSpriservread-writemandatoryInternet Address (in dot notation) of primary name server that the resolver should query.
1.3.6.1.4.1.318.1.1.19.1.2.5.3.2ScalarcpsDNSsecservread-writemandatoryInternet Address (in dot notation) of secondary name server that the resolver should query.
1.3.6.1.4.1.318.1.1.19.1.2.5.3.3ScalarcpsDNSdomainread-writemandatoryLocal domain name.
1.3.6.1.4.1.318.1.1.19.1.2.6NodecpsSerialPortConf
1.3.6.1.4.1.318.1.1.19.1.2.6.1NodecpsSerialGlobal
1.3.6.1.4.1.318.1.1.19.1.2.6.1.1ScalarcpsSerialIncluderead-writemandatoryFile used in centralized management.
1.3.6.1.4.1.318.1.1.19.1.2.6.1.2ScalarcpsSerialNFSread-writemandatoryRemote Network File System where data buffering will be written instead of the default directory '/var/run/DB'.
1.3.6.1.4.1.318.1.1.19.1.2.6.1.3ScalarcpsSerialLockDirread-writemandatoryThe lock directory.
1.3.6.1.4.1.318.1.1.19.1.2.6.1.4ScalarcpsSerialRloginread-writemandatoryLocation of the rlogin binary that accepts the -i flag.
1.3.6.1.4.1.318.1.1.19.1.2.6.1.5ScalarcpsSerialPppdread-writemandatoryLocation of the pppd binary.
1.3.6.1.4.1.318.1.1.19.1.2.6.1.6ScalarcpsSerialTelnetread-writemandatoryLocation of the telnet application.
1.3.6.1.4.1.318.1.1.19.1.2.6.1.7ScalarcpsSerialSshread-writemandatoryLocation of the ssh application.
1.3.6.1.4.1.318.1.1.19.1.2.6.1.8ScalarcpsSerialLocalLoginsread-writemandatoryThis parameter is only necessary when authentication is being performed for a port. This is useful if the Radius authentication server is down. 0 indicates OFF…
1.3.6.1.4.1.318.1.1.19.1.2.6.1.9ScalarcpsSerialFacilityread-writemandatoryThis value (0-7) is the Local facility sent to the syslog daemon.
1.3.6.1.4.1.318.1.1.19.1.2.6.1.10ScalarcpsSerialDBFacilityread-writemandatoryThis value (0-7) is the Local facility sent to the syslog daemon.
1.3.6.1.4.1.318.1.1.19.1.2.6.1.11TablecpsSerialGroupTablenot-accessiblemandatory
1.3.6.1.4.1.318.1.1.19.1.2.6.1.11.1RowcpsSerialGroupEntrynot-accessiblemandatory
1.3.6.1.4.1.318.1.1.19.1.2.6.1.11.1.1ColumncpsSerialGroupIndexread-onlymandatoryNumber to identify the group.
1.3.6.1.4.1.318.1.1.19.1.2.6.1.11.1.2ColumncpsSerialGroupNameread-writemandatoryThe group name.
1.3.6.1.4.1.318.1.1.19.1.2.6.1.11.1.3ColumncpsSerialGroupUsersread-writemandatoryThe user's names.
1.3.6.1.4.1.318.1.1.19.1.2.6.2NodecpsSerialSpec
1.3.6.1.4.1.318.1.1.19.1.2.6.2.1TablecpsSerialPortTablenot-accessiblemandatoryThis is the specific configuration per serial port.
1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1RowcpsSerialPortEntrynot-accessiblemandatoryOne particular serial port configuration.
1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.1ColumncpsSerialPortNumberread-onlymandatoryNumber to identify the serial port. Value 0 is ALL.
1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.2ColumncpsSerialPortTtyread-writemandatoryThe device name for the serial port.
1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.3ColumncpsSerialPortNameread-writemandatoryAlias name given to the server connected to the serial port.
1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.4ColumncpsSerialPortSpeedread-writemandatoryThe speed of the serial port. Supported values are: 50, 75, 110, 134, 150, 200, 300, 600, 1200, 1800, 2400, 4800, 9600, 14400, 19200, 28800, 38400, 57600, 1152…
1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.5ColumncpsSerialPortDataSizeread-writemandatoryThe data size for the serial port.
1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.6ColumncpsSerialPortStopBitsread-writemandatoryThe number of stop bits for the serial port.
1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.7ColumncpsSerialPortParityread-writemandatoryThe parity for the serial port.
1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.8ColumncpsSerialPortFlowCtrlread-writemandatoryThe flow control for the serial port.
1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.9ColumncpsSerialPortDTRdelayread-writemandatoryThis specifies how long (in milliseconds) a DTR signal will be turned off before it is turned on again.
1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.10ColumncpsSerialPortDCDCtrlread-writemandatoryDCD signal controls the connection request. 0 will indicate nocontrol, 1 will indicate control.
1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.11ColumncpsSerialPortLogUtmpread-writemandatoryUpdate the login records in /var/run/utmp file. 0 will indicate inactive, 1 will indicate active.
1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.12ColumncpsSerialPortLogWtmpread-writemandatoryUpdate the login records in /var/run/wtmp file. 0 will indicate inactive, 1 will indicate active.
1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.13ColumncpsSerialPortLogformread-writemandatoryThis is the format to write the login record.
1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.14ColumncpsSerialPortAuthtyperead-writemandatoryAuthentication type.
1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.15ColumncpsSerialPortAuthSrv1read-writemandatoryIP address of the primary authentication server.
1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.16ColumncpsSerialPortAccSrv1read-writemandatoryIP address of the primary accounting server.
1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.17ColumncpsSerialPortAuthTmoread-writemandatoryThis is the timeout (in seconds) for the authentication query to be answered.
1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.18ColumncpsSerialPortAuthRetrread-writemandatoryThis defines the number of times each server is tried before another is contacted.
1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.19ColumncpsSerialPortAuthSrv2read-writemandatoryIP address of the secondary authentication server.
1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.20ColumncpsSerialPortAccSrv2read-writemandatoryIP address of the secondary accounting server.
1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.21ColumncpsSerialPortAuthSecretread-writemandatoryThis is the shared secret with authentication servers.
1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.22ColumncpsSerialPortAuthRadPread-writemandatoryRadius state. 0 will indicate inactive, 1 will indicate active.
1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.23ColumncpsSerialPortAuthAccread-writemandatoryAccess restriction.
1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.24ColumncpsSerialPortProtocolread-writemandatoryDefines the serial port's protocol.
1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.25ColumncpsSerialPortRemoteIPread-writemandatoryThis is the default IP address of the serial port.
1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.26ColumncpsSerialPortSocketPortread-writemandatoryThis defines an alternative labeling system for the serial port.
1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.27ColumncpsSerialPortRemHostread-writemandatoryThe IP address of the host to which the serial port will connect.
1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.28ColumncpsSerialPortBannerread-writemandatoryThis defines the banner.
1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.29ColumncpsSerialPortPromptread-writemandatoryThis defines the login prompt to the serial port.
1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.30ColumncpsSerialPortTermTyperead-writemandatoryThis defines the terminal type.
1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.31ColumncpsSerialPortAutomUsrread-writemandatoryThis defines the automatic user.
1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.32ColumncpsSerialPortNetMaskread-writemandatoryThe network mask used in dial in connection.
1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.33ColumncpsSerialPortPppMturead-writemandatoryThe PPP MTU - dial in connection.
1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.34ColumncpsSerialPortPppMruread-writemandatoryThe PPP MRU - dial in connection.
1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.35ColumncpsSerialPortPppOptionsread-writemandatoryThe PPP options when the PPP session is autodetected.
1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.36ColumncpsSerialPortPppFoptionread-writemandatoryThe PPP forced options when the user has already been authenticated.
1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.37ColumncpsSerialPortModemChatread-writemandatoryThe initchat send to modem connected.
1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.38ColumncpsSerialPortSttyCmdread-writemandatoryThe tty settings after socket connection is established.
1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.39ColumncpsSerialPortSockTxread-writemandatoryDefines the delay (in milliseconds) before transmission to the Ethernet of data received through a serial port.
1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.40ColumncpsSerialPortSockPollread-writemandatoryKeep-alive timer (milliseconds) for the TCP connection.
1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.41ColumncpsSerialPortSockIdleread-writemandatoryThe idle timeout in seconds.
1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.42ColumncpsSerialPortDBsizeread-writemandatoryMaximum size of the data buffering file.
1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.43ColumncpsSerialPortDBtimeread-writemandatoryTimestamp in data buffering. 0 will indicate inactive, 1 will indicate active.
1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.44ColumncpsSerialPortDBmoderead-writemandatoryData buffering mode : circ or line.
1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.45ColumncpsSerialPortDBsyslogread-writemandatorySize of the data buffer sent to syslog.
1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.46ColumncpsSerialPortDBmenuread-writemandatoryMenu type for data buffering. 0 will indicate display Menu, 1 will indicate inactive, 2 will indicate DB, 3 will indicate Parc.
1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.47ColumncpsSerialPortDBalarmread-writemandatoryAlarm generation status. 0 will indicate inactive, 1 will indicate active.
1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.48ColumncpsSerialPortSSHbreakread-writemandatoryBreak sequence - ssh session.
1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.49ColumncpsSerialPortSniffSessread-writemandatorySniff session type.
1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.50ColumncpsSerialPortSniffAdmread-writemandatoryList of admin users allowed to sniff session.
1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.51ColumncpsSerialPortSniffEscread-writemandatoryEscape sequence used in sniff session.
1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.52ColumncpsSerialPortSniffMsessread-writemandatory
1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.53ColumncpsSerialPortTelnetModeread-writemandatoryMode negotiated by client telnet with the server. 0 will indicate text, 1 will indicate binary.
1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.54ColumncpsSerialPortSysBufSessread-writemandatorySyslog Buffering at all times. 0 will indicate yes, 1 will indicate no.
1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.55ColumncpsSerialPortLFSuppressread-writemandatoryLF suppression in socket_server session. 0 will indicate inactive, 1 will indicate active.
1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.56ColumncpsSerialPortAutoInputread-writemandatoryInput string used for auto answer.
1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.57ColumncpsSerialPortAutoOutputread-writemandatoryOutput string used for auto answer.
1.3.6.1.4.1.318.1.1.19.1.2.6.2.1.1.58ColumncpsSerialPortBreakIntervalread-writemandatoryThe break interval in milliseconds.
1.3.6.1.4.1.318.1.1.19.1.3NodecpsAP930xInfo
1.3.6.1.4.1.318.1.1.19.1.3.1TablecpsInfoSerialPortTablenot-accessiblemandatoryThis is the information of the specific serial port.
1.3.6.1.4.1.318.1.1.19.1.3.1.1RowcpsInfoSerialPortEntrynot-accessiblemandatoryOne particular serial port.
1.3.6.1.4.1.318.1.1.19.1.3.1.1.1ColumncpsInfoSerialPortNumberread-onlymandatoryNumber to identify the serial port.
1.3.6.1.4.1.318.1.1.19.1.3.1.1.2ColumncpsInfoSerialPortTtyread-onlymandatoryThe device name for the serial port.
1.3.6.1.4.1.318.1.1.19.1.3.1.1.3ColumncpsInfoSerialPortNameread-onlymandatoryAlias name given to the server connected to the serial port.
1.3.6.1.4.1.318.1.1.19.1.3.1.1.4ColumncpsInfoSerialPortSpeedread-onlymandatoryThe speed for serial port.
1.3.6.1.4.1.318.1.1.19.1.3.1.1.5ColumncpsInfoSerialPortTxBytesread-onlymandatoryThe number of transmitted bytes by the serial port.
1.3.6.1.4.1.318.1.1.19.1.3.1.1.6ColumncpsInfoSerialPortRXBytesread-onlymandatoryThe number of received bytes by the serial port.
1.3.6.1.4.1.318.1.1.19.1.3.1.1.7ColumncpsInfoSerialPortErrFrameread-onlymandatoryThe number of frame errors.
1.3.6.1.4.1.318.1.1.19.1.3.1.1.8ColumncpsInfoSerialPortErrParityread-onlymandatoryThe number of parity errors.
1.3.6.1.4.1.318.1.1.19.1.3.1.1.9ColumncpsInfoSerialPortErrBreaksread-onlymandatoryThe number of breaks errors.
1.3.6.1.4.1.318.1.1.19.1.3.1.1.10ColumncpsInfoSerialPortErrOverrunread-onlymandatoryThe number of overrun errors.
1.3.6.1.4.1.318.1.1.19.1.3.1.1.11ColumncpsInfoSerialPortSigDTRread-onlymandatoryThe state of the DTR signal. 0 will indicate down, 1 will indicate up.
1.3.6.1.4.1.318.1.1.19.1.3.1.1.12ColumncpsInfoSerialPortSigCDread-onlymandatoryThe state of the DCD signal. 0 will indicate down, 1 will indicate up.
1.3.6.1.4.1.318.1.1.19.1.3.1.1.13ColumncpsInfoSerialPortSigDSRread-onlymandatoryThe state of the DSR signal. 0 will indicate down, 1 will indicate up.
1.3.6.1.4.1.318.1.1.19.1.3.1.1.14ColumncpsInfoSerialPortSigRTSread-onlymandatoryThe state of the RTS signal. 0 will indicate down, 1 will indicate up.
1.3.6.1.4.1.318.1.1.19.1.3.1.1.15ColumncpsInfoSerialPortSigCTSread-onlymandatoryThe state of the CTS signal. 0 will indicate down, 1 will indicate up.
1.3.6.1.4.1.318.1.1.19.1.3.1.1.16ColumncpsInfoSerialPortSigRIread-onlymandatoryThe state of the RI signal. 0 will indicate down, 1 will indicate up.
1.3.6.1.4.1.318.1.1.19.1.4NodecpsAP930xAdm
1.3.6.1.4.1.318.1.1.19.1.4.1ScalarapCPSSaveread-writemandatoryExec saveconf command. 0 will indicate don't save, 1 will indicate save.
1.3.6.1.4.1.318.1.1.19.1.4.2ScalarapCPSSerialHUPread-writemandatoryExec signal_ras hup command. 0 will indicate no restart, 1 will indicate restart.
1.3.6.1.4.1.318.1.1.20NodeaccessControl
1.3.6.1.4.1.318.1.1.20.1NodeaccessPX
1.3.6.1.4.1.318.1.1.20.1.1NodeaccessPXIdent
1.3.6.1.4.1.318.1.1.20.1.1.1ScalaraccessPXIdentAlarmStatusread-onlymandatoryAccess PX alarm status 1 = Normal 2 = Warning 3 = Critical.
1.3.6.1.4.1.318.1.1.20.1.1.2ScalaraccessPXIdentProductNumberread-onlymandatoryThe product number of the Access PX.
1.3.6.1.4.1.318.1.1.20.1.1.3ScalaraccessPXIdentHardwareRevread-onlymandatoryThe hardware revision number of the Access PX.
1.3.6.1.4.1.318.1.1.20.1.1.4ScalaraccessPXIdentDateOfManufactureread-onlymandatoryThe date of manufacture of the Access PX.
1.3.6.1.4.1.318.1.1.20.1.1.5ScalaraccessPXIdentSerialNumberread-onlymandatoryThe serial number of the Access PX.
1.3.6.1.4.1.318.1.1.20.1.2NodeaccessPXConfig
1.3.6.1.4.1.318.1.1.20.1.2.1ScalaraccessPXConfigCardReaderEnableDisableActionread-writemandatoryAction to disable/enable the card reader.
1.3.6.1.4.1.318.1.1.20.1.2.2ScalaraccessPXConfigAutoRelockTimeread-writemandatoryTime (10 - 60) in seconds when the door will automatically relock after it has been unlocked and the handle has not been opened.
1.3.6.1.4.1.318.1.1.20.1.2.3ScalaraccessPXConfigCardFormatread-writemandatoryIndicates and controls the various card format.
1.3.6.1.4.1.318.1.1.20.1.3NodeaccessPXConfigFront
1.3.6.1.4.1.318.1.1.20.1.3.1ScalaraccessPXConfigFrontDoorLockControlread-writemandatoryControl action (unlock, lock) for the front door. Setting this OID will unlock or lock the front door. Getting this OID will respond with the current state of …
1.3.6.1.4.1.318.1.1.20.1.3.2ScalaraccessPXConfigFrontDoorMaxOpenTimeread-writemandatoryTime in minutes, (1 - 120), that the front door can be allowed to remain open without generating an alarm condition.
1.3.6.1.4.1.318.1.1.20.1.4NodeaccessPXStatusFront
1.3.6.1.4.1.318.1.1.20.1.4.1ScalaraccessPXStatusFrontDoorLockread-onlymandatoryPresent state of the front door lock: unlocked, locked, not installed, or disconnected.
1.3.6.1.4.1.318.1.1.20.1.4.2ScalaraccessPXStatusFrontDoorread-onlymandatoryPresent state of the front door: open, closed, not installed, or disconnected.
1.3.6.1.4.1.318.1.1.20.1.4.3ScalaraccessPXStatusFrontDoorHandleread-onlymandatoryPresent state of the front door handle: open, closed, not installed, or disconnected.
1.3.6.1.4.1.318.1.1.20.1.4.4ScalaraccessPXStatusFrontDoorMaxOpenTimeread-onlymandatoryTime in minutes, (1 - 120), that the front door can be allowed to remain open without generating an alarm condition.
1.3.6.1.4.1.318.1.1.20.1.4.5ScalaraccessPXStatusFrontDoorAlarmStatusread-onlymandatoryFront door alarm status 1 = Normal 2 = Warning 3 = Critical 4 = Front door not installed.
1.3.6.1.4.1.318.1.1.20.1.5NodeaccessPXConfigRear
1.3.6.1.4.1.318.1.1.20.1.5.1ScalaraccessPXConfigRearDoorLockControlread-writemandatoryControl action (unlock, lock) for the rear door. Setting this OID will unlock or lock the rear door. Getting this OID will respond with the current state of th…
1.3.6.1.4.1.318.1.1.20.1.5.2ScalaraccessPXConfigRearDoorMaxOpenTimeread-writemandatoryTime in minutes, (1 - 120), that the rear door can be allowed to remain open without generating an alarm condition.
1.3.6.1.4.1.318.1.1.20.1.6NodeaccessPXStatusRear
1.3.6.1.4.1.318.1.1.20.1.6.1ScalaraccessPXStatusRearDoorLockread-onlymandatoryPresent state of the rear door lock: unlocked, locked, not installed, or disconnected.
1.3.6.1.4.1.318.1.1.20.1.6.2ScalaraccessPXStatusRearDoorread-onlymandatoryPresent state of the rear door: open, closed, not installed, or disconnected.
1.3.6.1.4.1.318.1.1.20.1.6.3ScalaraccessPXStatusRearDoorHandleread-onlymandatoryPresent state of the rear door handle: open, closed, not installed, or disconnected.
1.3.6.1.4.1.318.1.1.20.1.6.4ScalaraccessPXStatusRearDoorMaxOpenTimeread-onlymandatoryTime in minutes, (1 - 120), that the rear door can be allowed to remain open without generating an alarm condition.
1.3.6.1.4.1.318.1.1.20.1.6.5ScalaraccessPXStatusRearDoorAlarmStatusread-onlymandatoryRear door alarm status 1 = Normal 2 = Warning 3 = Critical 4 = Rear door not installed.
1.3.6.1.4.1.318.1.1.20.1.7NodeaccessPXConfigBeacon
1.3.6.1.4.1.318.1.1.20.1.7.1ScalaraccessPXConfigBeaconNameread-writemandatoryA descriptive name for the Beacon.
1.3.6.1.4.1.318.1.1.20.1.7.2ScalaraccessPXConfigBeaconLocationread-writemandatoryA descriptive name for the location of the Beacon.
1.3.6.1.4.1.318.1.1.20.1.7.3ScalaraccessPXConfigBeaconActionread-writemandatoryControl action (turnOff, turnOn) for the beacon. Setting this OID will turn the beacon off or on. Getting this OID will respond with the current state which co…
1.3.6.1.4.1.318.1.1.20.1.8NodeaccessPXStatusBeacon
1.3.6.1.4.1.318.1.1.20.1.8.1ScalaraccessPXStatusBeaconNameread-onlymandatoryThe name of the beacon.
1.3.6.1.4.1.318.1.1.20.1.8.2ScalaraccessPXStatusBeaconLocationread-onlymandatoryThe name of the location of the beacon.
1.3.6.1.4.1.318.1.1.20.1.8.3ScalaraccessPXStatusBeaconCurrentStateread-onlymandatoryThe current state of the beacon: off, on, not installed, or disconnected.
1.3.6.1.4.1.318.1.1.21NodeapcLocalDisplay
1.3.6.1.4.1.318.1.1.21.1NodeapcLocalDisplayIdent
1.3.6.1.4.1.318.1.1.21.1.1ScalarapcLocalDisplayIdentDisplayTyperead-onlymandatoryNumeric value used to identify the type of display in use.
1.3.6.1.4.1.318.1.1.21.1.2ScalarapcLocalDisplayIdentModelNumberread-onlymandatoryThe model number of the local display.
1.3.6.1.4.1.318.1.1.21.1.3ScalarapcLocalDisplayIdentFirmwareRevread-onlymandatoryThe firmware revision number of the local display.
1.3.6.1.4.1.318.1.1.21.1.4ScalarapcLocalDisplayIdentOptionsread-onlymandatoryA display-specific string identifying options in the local display.
1.3.6.1.4.1.318.1.1.21.1.5ScalarapcLocalDisplayIdentDateOfManufactureread-onlymandatoryThe date of manufacture of the local display, if available.
1.3.6.1.4.1.318.1.1.21.1.6ScalarapcLocalDisplayIdentSerialNumberread-onlymandatoryThe serial number of the local display, if available.
1.3.6.1.4.1.318.1.1.21.2NodeapcLocalDisplayConfig
1.3.6.1.4.1.318.1.1.21.2.1ScalarapcLocalDisplayConfigAlarmBeeperread-writemandatoryThe alarm beeper setting for the local display. When enabled, the alarm beeper will begin to sound whenever there a new alarm becomes active. The alarm beeper …
1.3.6.1.4.1.318.1.1.21.2.2ScalarapcLocalDisplayConfigBeeperVolumeread-writemandatoryThe volume setting of the beeper on the local display.
1.3.6.1.4.1.318.1.1.21.2.3ScalarapcLocalDisplayConfigCheckLogIndicatorread-writemandatoryThe minimum level event severity level required to illuminate the check log light on the local display. notPresent (1) indicates that the display does not have…
1.3.6.1.4.1.318.1.1.21.2.4ScalarapcLocalDisplayConfigKeyClickread-writemandatoryThe key click setting of the local display.
1.3.6.1.4.1.318.1.1.21.2.5ScalarapcLocalDisplayConfigContrastread-writemandatoryThe contrast level of the local display.
1.3.6.1.4.1.318.1.1.22NodeisxModularDistribution
1.3.6.1.4.1.318.1.1.22.1NodeisxModularDistInfo
1.3.6.1.4.1.318.1.1.22.1.1ScalarisxModularDistInfoTableSizeread-onlymandatoryThe number of entries in the isxModularDistInfoTable.
1.3.6.1.4.1.318.1.1.22.1.2TableisxModularDistInfoTablenot-accessiblemandatoryAllows for getting information about the modular distribution metering equipment.
1.3.6.1.4.1.318.1.1.22.1.2.1RowisxModularDistInfoEntrynot-accessiblemandatoryAn entry containing information about an individual metering segment.
1.3.6.1.4.1.318.1.1.22.1.2.1.1ColumnisxModularDistInfoSegmentIndexread-onlymandatoryThe index of the metering segment.
1.3.6.1.4.1.318.1.1.22.1.2.1.2ColumnisxModularDistInfoMeterModelNumberread-onlymandatoryThe model number of the metering board for this segment.
1.3.6.1.4.1.318.1.1.22.1.2.1.3ColumnisxModularDistInfoMeterSerialNumberread-onlymandatoryThe serial number of the metering board for this segment.
1.3.6.1.4.1.318.1.1.22.1.2.1.4ColumnisxModularDistInfoMeterDateOfManufactureread-onlymandatoryThe date of manufacture for the metering board for this segment, in the format mm/dd/yyyy.
1.3.6.1.4.1.318.1.1.22.1.2.1.5ColumnisxModularDistInfoMeterFirmwareRevread-onlymandatoryThe firmware revision number of the metering board for this segment.
1.3.6.1.4.1.318.1.1.22.1.2.1.6ColumnisxModularDistInfoMeterHardwareRevread-onlymandatoryThe hardware revision number of the metering board for this segment.
1.3.6.1.4.1.318.1.1.22.2NodeisxModularDistModules
1.3.6.1.4.1.318.1.1.22.2.1ScalarisxModularDistModuleInfoTableSizeread-onlymandatoryThe number of entries in the isxModularDistModuleInfoTable.
1.3.6.1.4.1.318.1.1.22.2.2TableisxModularDistModuleInfoTablenot-accessiblemandatoryAllows for getting basic information about the distribution modules installed in the system.
1.3.6.1.4.1.318.1.1.22.2.2.1RowisxModularDistModuleInfoEntrynot-accessiblemandatoryAn entry containing information about a specific distribution module.
1.3.6.1.4.1.318.1.1.22.2.2.1.1ColumnisxModularDistModuleInfoModIndexread-onlymandatoryThe number of the distribution module.
1.3.6.1.4.1.318.1.1.22.2.2.1.2ColumnisxModularDistModuleInfoAlarmStatusread-onlymandatoryThe status of this module. This reflects the indicator lamp(s) on the front of the module. A value of notPresent indicates that the module is not installed. A …
1.3.6.1.4.1.318.1.1.22.2.2.1.3ColumnisxModularDistModuleInfoModelNumberread-onlymandatoryThe model number of the distribution module.
1.3.6.1.4.1.318.1.1.22.2.2.1.4ColumnisxModularDistModuleInfoSerialNumberread-onlymandatoryThe serial number of the distribution module.
1.3.6.1.4.1.318.1.1.22.2.2.1.5ColumnisxModularDistModuleInfoDateOfManufactureread-onlymandatoryThe date that the distribution module was manufactured.
1.3.6.1.4.1.318.1.1.22.2.2.1.6ColumnisxModularDistModuleInfoNumCablesread-onlymandatoryThe number of cables provided by this distribution module.
1.3.6.1.4.1.318.1.1.22.2.3ScalarisxModularDistModuleBreakerTableSizeread-onlymandatoryThe number of entries in the isxModularDistModuleBreakerTable.
1.3.6.1.4.1.318.1.1.22.2.4TableisxModularDistModuleBreakerTablenot-accessiblemandatoryAllows for getting operational information about the distribution modules.
1.3.6.1.4.1.318.1.1.22.2.4.1RowisxModularDistModuleBreakerEntrynot-accessiblemandatoryAn entry containing information about a specific distribution modules and circuit breakers.
1.3.6.1.4.1.318.1.1.22.2.4.1.1ColumnisxModularDistModuleBreakerModIndexread-onlymandatoryThe distribution module number.
1.3.6.1.4.1.318.1.1.22.2.4.1.2ColumnisxModularDistModuleBreakerPhaseIndexread-onlymandatoryThe index to an individual breaker in the distribution module. The index also corresponds to the system phase to which the breaker is attached.
1.3.6.1.4.1.318.1.1.22.2.4.1.3ColumnisxModularDistModuleBreakerAlarmStatusread-onlymandatoryThis is a bit map representing the active alarms for this breaker: b0 - Minimum current threshold exceeded (critical) b1 - Low current threshold exceeded (warn…
1.3.6.1.4.1.318.1.1.22.2.4.1.4ColumnisxModularDistModuleBreakerRatingread-onlymandatoryThe current rating of the breaker.
1.3.6.1.4.1.318.1.1.22.2.4.1.5ColumnisxModularDistModuleBreakerPhysicalGroupread-onlymandatoryNumeric value used to indicate that a breaker is a part of a multi-pole breaker. Breakers within a distribution module, with equivalent physical group numbers,…
1.3.6.1.4.1.318.1.1.22.2.4.1.6ColumnisxModularDistModuleBreakerCableNumread-onlymandatoryNumeric value used to indicate the distribution cable to which this breaker is connected. These distribution cables are described in the table isxModularDistMo…
1.3.6.1.4.1.318.1.1.22.2.4.1.7ColumnisxModularDistModuleBreakerPositionread-onlymandatoryThe physical status of this breaker pole, either closed or open (including tripped).
1.3.6.1.4.1.318.1.1.22.2.4.1.8ColumnisxModularDistModuleBreakerPositionAlarmsread-writemandatoryEnable or disable breaker position alarms for this circuit breaker.
1.3.6.1.4.1.318.1.1.22.2.4.1.9ColumnisxModularDistModuleBreakerCurrentread-onlymandatoryThe current flowing though this breaker. Measured in tenths of amps.
1.3.6.1.4.1.318.1.1.22.2.4.1.10ColumnisxModularDistModuleBreakerPercentread-onlymandatoryThe loading on this breaker as a percentage of the breaker's current rating. Expressed in tenths of percent.
1.3.6.1.4.1.318.1.1.22.2.4.1.11ColumnisxModularDistModuleBreakerPowerread-onlymandatoryThe power being supplied through this breaker. Measured in tenths of kW.
1.3.6.1.4.1.318.1.1.22.2.5ScalarisxModularDistModuleOutputsTableSizeread-onlymandatoryThe number of entries in the isxModularDistModuleOutputTable.
1.3.6.1.4.1.318.1.1.22.2.6TableisxModularDistModuleOutputTablenot-accessiblemandatoryAllows for getting and setting information related to the load equipment being fed by the distribution modules in the ISX Modular Distribution System.
1.3.6.1.4.1.318.1.1.22.2.6.1RowisxModularDistModuleOutputEntrynot-accessiblemandatoryAn entry containing information about a specific distribution module and its output distribution cables.
1.3.6.1.4.1.318.1.1.22.2.6.1.1ColumnisxModularDistModuleOutputModIndexread-onlymandatoryThe number of the distribution module supplying power to the load equipment.
1.3.6.1.4.1.318.1.1.22.2.6.1.2ColumnisxModularDistModuleOutputNumCablesread-onlymandatoryThe number of distribution cables provided by this module.
1.3.6.1.4.1.318.1.1.22.2.6.1.3ColumnisxModularDistModuleOutputCordIndexread-onlymandatoryThe index of an individual distribution cable supplied by this module.
1.3.6.1.4.1.318.1.1.22.2.6.1.4ColumnisxModularDistModuleOutputNameread-writemandatoryA string describing the load equipment being supplied by this distribution cable.
1.3.6.1.4.1.318.1.1.22.2.6.1.5ColumnisxModularDistModuleOutputLocationread-writemandatoryA string describing the location of equipment being supplied by distribution cable.
1.3.6.1.4.1.318.1.1.22.2.6.1.6ColumnisxModularDistModuleOutputStatusread-onlymandatoryThis reflects the worse case severity for alarms associated with this distribution cable. A value of notPresent indicates that the cable does not exist for thi…
1.3.6.1.4.1.318.1.1.22.2.6.1.7ColumnisxModularDistModuleOutputAlarmGenerationread-writemandatoryEnable or disable all alarm generation related to this distribution cable.
1.3.6.1.4.1.318.1.1.22.2.6.1.8ColumnisxModularDistModuleOutputBreakerMapread-onlymandatoryThis is a bit map representing the breaker poles within the module that are associated with this distribution cable. The following 3 bits are used to indicate …
1.3.6.1.4.1.318.1.1.22.2.6.1.9ColumnisxModularDistModuleOutputThresholdMinread-writemandatoryWhen the current drops below this value a critical alarm will exist.
1.3.6.1.4.1.318.1.1.22.2.6.1.10ColumnisxModularDistModuleOutputThresholdLowread-writemandatoryWhen the current drops below this value a warning alarm will exist.
1.3.6.1.4.1.318.1.1.22.2.6.1.11ColumnisxModularDistModuleOutputThresholdHighread-writemandatoryWhen the current exceeds this value a warning alarm will exist.
1.3.6.1.4.1.318.1.1.22.2.6.1.12ColumnisxModularDistModuleOutputThresholdMaxread-writemandatoryWhen the current exceeds this value a critical alarm will exist.
1.3.6.1.4.1.318.1.1.22.2.6.1.13ColumnisxModularDistModuleOutputAlarmMinEnableread-writemandatoryEnable or disable minimum current alarm generation for this distribution cable.
1.3.6.1.4.1.318.1.1.22.2.6.1.14ColumnisxModularDistModuleOutputAlarmLowEnableread-writemandatoryEnable or disable low current alarm generation for this distribution cable.
1.3.6.1.4.1.318.1.1.22.2.6.1.15ColumnisxModularDistModuleOutputAlarmHighEnableread-writemandatoryEnable or disable high current alarm generation for this distribution cable.
1.3.6.1.4.1.318.1.1.22.2.6.1.16ColumnisxModularDistModuleOutputAlarmMaxEnableread-writemandatoryEnable or disable maximum current alarm generation for this distribution cable.
1.3.6.1.4.1.318.1.1.22.2.6.1.17ColumnisxModularDistModuleOutputCableLengthread-onlymandatoryThe length of this distribution cable. Specified in tenths of meters.
1.3.6.1.4.1.318.1.1.22.2.6.1.18ColumnisxModularDistModuleOutputConnectorTyperead-onlymandatoryA string describing the connector on the end of this distribution cable.
1.3.6.1.4.1.318.1.1.22.2.6.1.19ColumnisxModularDistModuleOutputAvailableVoltagesread-onlymandatoryThis is a bit map representing the voltages that are available at the connector. 6 bits are used to indicate the following: b0 - L1 b1 - L2 b2 - L3 b3 - L1-2 b…
1.3.6.1.4.1.318.1.1.22.2.6.1.20ColumnisxModularDistModuleOutputTotalPowerread-onlymandatoryThe total power being consumed by the load equipment supplied by this distribution cable. Measured in tenths of kW.
1.3.6.1.4.1.318.1.1.22.2.6.1.21ColumnisxModularDistModuleOutputKwhUsageread-onlymandatoryThe total energy consumed by the load equipment fed by this distribution cable. This is the total since the date specified in the isxModularDistModuleOutputKwh…
1.3.6.1.4.1.318.1.1.22.2.6.1.22ColumnisxModularDistModuleOutputKwhResetread-writemandatoryWriting yes to this OID will reset the total kWh usage shown in the isxModularDistModuleOutputKwhUsage OID.
1.3.6.1.4.1.318.1.1.22.2.6.1.23ColumnisxModularDistModuleOutputKwhResetDateread-onlymandatoryThe date that the kWh usage was reset, in the format mm/dd/yyyy. Example: 01/01/2000.
1.3.6.1.4.1.318.1.1.22.3NodeisxModularDistSubFeeds
1.3.6.1.4.1.318.1.1.22.3.1ScalarisxModularDistSubFeedInfoTableSizeread-onlymandatoryThe number of entries in the isxModularDistSubFeedInfoTable.
1.3.6.1.4.1.318.1.1.22.3.2TableisxModularDistSubFeedInfoTablenot-accessiblemandatoryAllows for getting information about distribution subfeed breakers.
1.3.6.1.4.1.318.1.1.22.3.2.1RowisxModularDistSubFeedInfoEntrynot-accessiblemandatoryAn entry containing information about a specific distribution subfeed.
1.3.6.1.4.1.318.1.1.22.3.2.1.1ColumnisxModularDistSubFeedInfoSubIndexread-onlymandatoryThe index of an individual subfeed.
1.3.6.1.4.1.318.1.1.22.3.2.1.2ColumnisxModularDistSubFeedInfoNameread-writemandatoryA string describing the load equipment being supplied by this subfeed.
1.3.6.1.4.1.318.1.1.22.3.2.1.3ColumnisxModularDistSubFeedInfoLocationread-writemandatoryA string describing the location of the equipment being supplied by this subfeed.
1.3.6.1.4.1.318.1.1.22.3.2.1.4ColumnisxModularDistSubFeedInfoBreakerRatingread-onlymandatoryThe current rating of this subfeed breaker.
1.3.6.1.4.1.318.1.1.22.3.2.1.5ColumnisxModularDistSubFeedInfoBreakerPositionread-onlymandatoryThe operational status of this breaker, either closed or open (including tripped).
1.3.6.1.4.1.318.1.1.22.3.2.1.6ColumnisxModularDistSubFeedInfoAlarmStatusread-onlymandatoryThe worst case alarm status for this subfeed.
1.3.6.1.4.1.318.1.1.22.3.2.1.7ColumnisxModularDistSubFeedInfoAlarmGenerationread-writemandatoryEnable or disable all alarm generation related to this subfeed.
1.3.6.1.4.1.318.1.1.22.3.2.1.8ColumnisxModularDistSubFeedInfoThresholdMinread-writemandatoryWhen the current drops below this value a critical alarm will exist.
1.3.6.1.4.1.318.1.1.22.3.2.1.9ColumnisxModularDistSubFeedInfoThresholdLowread-writemandatoryWhen the current drops below this value a warning alarm will exist.
1.3.6.1.4.1.318.1.1.22.3.2.1.10ColumnisxModularDistSubFeedInfoThresholdHighread-writemandatoryWhen the current exceeds this value a warning alarm will exist.
1.3.6.1.4.1.318.1.1.22.3.2.1.11ColumnisxModularDistSubFeedInfoThresholdMaxread-writemandatoryWhen the current exceeds this value a critical alarm will exist.
1.3.6.1.4.1.318.1.1.22.3.2.1.12ColumnisxModularDistSubFeedInfoAlarmMinEnableread-writemandatoryEnable or disable minimum current alarm generation for this subfeed.
1.3.6.1.4.1.318.1.1.22.3.2.1.13ColumnisxModularDistSubFeedInfoAlarmLowEnableread-writemandatoryEnable or disable low current alarm generation for this subfeed.
1.3.6.1.4.1.318.1.1.22.3.2.1.14ColumnisxModularDistSubFeedInfoAlarmHighEnableread-writemandatoryEnable or disable high current alarm generation for this subfeed.
1.3.6.1.4.1.318.1.1.22.3.2.1.15ColumnisxModularDistSubFeedInfoAlarmMaxEnableread-writemandatoryEnable or disable maximum current alarm generation for this subfeed.
1.3.6.1.4.1.318.1.1.22.3.2.1.16ColumnisxModularDistSubFeedInfoBreakerAlarmEnableread-writemandatoryEnable or disable breaker position alarms for this subfeed.
1.3.6.1.4.1.318.1.1.22.3.2.1.17ColumnisxModularDistSubFeedInfoTotalPowerread-onlymandatoryThe total power being supplied by this subfeed. Measured in tenths of kW.
1.3.6.1.4.1.318.1.1.22.3.2.1.18ColumnisxModularDistSubFeedInfoKwhUsageread-onlymandatoryThe total energy consumed by the load equipment fed by this subfeed. This is the total since the date specified in the isxModularDistSubFeedInfoKwhResetDate OI…
1.3.6.1.4.1.318.1.1.22.3.2.1.19ColumnisxModularDistSubFeedInfoKwhResetread-writemandatoryWriting yes to this OID will reset the total kWh usage shown in the isxModularDistSubFeedInfoKwhUsage OID.
1.3.6.1.4.1.318.1.1.22.3.2.1.20ColumnisxModularDistSubFeedInfoKwhResetDateread-onlymandatoryThe date that the kWh usage was reset, in the format mm/dd/yyyy. Example: 01/01/2000.
1.3.6.1.4.1.318.1.1.22.3.3ScalarisxModularDistSubFeedLoadingTableSizeread-onlymandatoryThe number of entries in the isxModularDistSubFeedLoadingTable.
1.3.6.1.4.1.318.1.1.22.3.4TableisxModularDistSubFeedLoadingTablenot-accessiblemandatoryAllows for getting subfeed phase loading information.
1.3.6.1.4.1.318.1.1.22.3.4.1RowisxModularDistSubFeedLoadingEntrynot-accessiblemandatoryAn entry containing data for an individual subfeed.
1.3.6.1.4.1.318.1.1.22.3.4.1.1ColumnisxModularDistSubFeedLoadingSubIndexread-onlymandatoryThe index of an individual subfeed.
1.3.6.1.4.1.318.1.1.22.3.4.1.2ColumnisxModularDistSubFeedLoadingPhaseIndexread-onlymandatoryDescription of each input phase entry in the table.
1.3.6.1.4.1.318.1.1.22.3.4.1.3ColumnisxModularDistSubFeedLoadingAlarmStatusread-onlymandatoryThis is a bit map representing the active alarms for this subfeed: b0 - Minimum current threshold exceeded (critical) b1 - Low current threshold exceeded (warn…
1.3.6.1.4.1.318.1.1.22.3.4.1.4ColumnisxModularDistSubFeedLoadingCurrentread-onlymandatoryThe current flowing though this subfeed phase. Measured in tenths of amps.
1.3.6.1.4.1.318.1.1.22.3.4.1.5ColumnisxModularDistSubFeedLoadingPercentread-onlymandatoryThe loading on this subfeed phase as a percentage of the subfeed's current rating. Expressed in tenths of percent.
1.3.6.1.4.1.318.1.1.22.3.4.1.6ColumnisxModularDistSubFeedLoadingPowerread-onlymandatoryThe power being supplied by this subfeed phase. Measured in tenths of kW.
1.3.6.1.4.1.318.1.1.22.4NodeisxModularDistTotals
1.3.6.1.4.1.318.1.1.22.4.1NodeisxModularDistSysVoltage
1.3.6.1.4.1.318.1.1.22.4.1.1ScalarisxModularDistSysOutputVoltageNominalLineToNeutralread-onlymandatoryThe nominal line-to-neutral voltage available at the distribution panel.
1.3.6.1.4.1.318.1.1.22.4.1.2ScalarisxModularDistSysOutputVoltageNominalLineToLineread-onlymandatoryThe nominal line-to-line voltage available at the distribution panel.
1.3.6.1.4.1.318.1.1.22.4.1.3ScalarisxModularDistSysOutputNominalFrequencyread-onlymandatoryThe nominal system output frequency. Measured in tenths of Hertz.
1.3.6.1.4.1.318.1.1.22.4.1.4ScalarisxModularDistSysOutputFrequencyread-onlymandatoryThe system output frequency in tenths of Hertz. -1 if not available.
1.3.6.1.4.1.318.1.1.22.4.1.5ScalarisxModularDistSysOutputVoltageMonitoringread-onlymandatoryIndicates whether or not output voltage alarm generation is present.
1.3.6.1.4.1.318.1.1.22.4.1.6ScalarisxModularDistSysOutputVoltageThresholdMinread-writemandatoryWhen the line-to-neutral voltage of any phase drops below this value a critical alarm will exist. Specified as a percent of the nominal voltage, isxModularDist…
1.3.6.1.4.1.318.1.1.22.4.1.7ScalarisxModularDistSysOutputVoltageThresholdLowread-writemandatoryWhen the line-to-neutral voltage of any phase drops below this value a warning alarm will exist. Specified as a percent of the nominal voltage, isxModularDistS…
1.3.6.1.4.1.318.1.1.22.4.1.8ScalarisxModularDistSysOutputVoltageThresholdHighread-writemandatoryWhen the line-to-neutral voltage of any phase exceeds this value a warning alarm will exist. Specified as a percent of the nominal voltage, isxModularDistSysOu…
1.3.6.1.4.1.318.1.1.22.4.1.9ScalarisxModularDistSysOutputVoltageThresholdMaxread-writemandatoryWhen the line-to-neutral voltage of any phase exceeds this value a critical alarm will exist. Specified as a percent of the nominal voltage, isxModularDistSysO…
1.3.6.1.4.1.318.1.1.22.4.1.10ScalarisxModularDistSysOutputVoltageAlarmMinEnableread-writemandatoryEnable or disable minimum voltage alarm generation for the distribution panel.
1.3.6.1.4.1.318.1.1.22.4.1.11ScalarisxModularDistSysOutputVoltageAlarmLowEnableread-writemandatoryEnable or disable low voltage alarm generation for the distribution panel.
1.3.6.1.4.1.318.1.1.22.4.1.12ScalarisxModularDistSysOutputVoltageAlarmHighEnableread-writemandatoryEnable or disable high voltage alarm generation for the distribution panel.
1.3.6.1.4.1.318.1.1.22.4.1.13ScalarisxModularDistSysOutputVoltageAlarmMaxEnableread-writemandatoryEnable or disable maximum voltage alarm generation for the distribution panel.
1.3.6.1.4.1.318.1.1.22.4.1.14ScalarisxModularDistSysOutputVoltageFrequencyToleranceread-writemandatoryThe circuit panel output frequency tolerance in Hertz. When the system output frequency deviates from the nominal by more than this range, a critical alarm wil…
1.3.6.1.4.1.318.1.1.22.4.1.15TableisxModularDistSysVoltageTablenot-accessiblemandatoryAllows for getting the system output voltage information.
1.3.6.1.4.1.318.1.1.22.4.1.15.1RowisxModularDistSysVoltageEntrynot-accessiblemandatoryAn entry containing data for an individual system output phase.
1.3.6.1.4.1.318.1.1.22.4.1.15.1.1ColumnisxModularDistSysVoltagePhaseIndexread-onlymandatoryDescription of each phase entry in the table.
1.3.6.1.4.1.318.1.1.22.4.1.15.1.2ColumnisxModularDistSysVoltageAlarmStatusread-onlymandatoryThis is a bit map representing the active alarms for this output phase: b0 - Minimum voltage threshold exceeded (critical) b1 - Low voltage threshold exceeded …
1.3.6.1.4.1.318.1.1.22.4.1.15.1.3ColumnisxModularDistSysVoltageLtoNread-onlymandatoryLine-to-neutral system output voltage available at the distribution panel. Measured in tenths of Volts.
1.3.6.1.4.1.318.1.1.22.4.1.15.1.4ColumnisxModularDistSysVoltageLtoLread-onlymandatoryLine-to-line system output voltage available at the distribution panel. Measured in tenths of Volts.
1.3.6.1.4.1.318.1.1.22.4.2NodeisxModularDistSysCurrent
1.3.6.1.4.1.318.1.1.22.4.2.1ScalarisxModularDistSysCurrentRatingread-onlymandatoryThe 100 percent current rating of the distribution panel.
1.3.6.1.4.1.318.1.1.22.4.2.2ScalarisxModularDistSysCurrentMonitoringread-onlymandatoryIndicates whether or not total output current measurements and alarm generation are present.
1.3.6.1.4.1.318.1.1.22.4.2.3ScalarisxModularDistSysCurrentThresholdMinread-writemandatoryWhen total system current in any phase drops below this value a critical alarm will exist. Specified as a percent of the panel rating, isxModularDistSysCurrent…
1.3.6.1.4.1.318.1.1.22.4.2.4ScalarisxModularDistSysCurrentThresholdLowread-writemandatoryWhen total system current in any phase drops below this value a warning alarm will exist. Specified as a percent of the panel rating, isxModularDistSysCurrentR…
1.3.6.1.4.1.318.1.1.22.4.2.5ScalarisxModularDistSysCurrentThresholdHighread-writemandatoryWhen total system current in any phase exceeds this value a warning alarm will exist. Specified as a percent of the panel rating, isxModularDistSysCurrentRatin…
1.3.6.1.4.1.318.1.1.22.4.2.6ScalarisxModularDistSysCurrentThresholdMaxread-writemandatoryWhen total system current in any phase exceeds this value a critical alarm will exist. Specified as a percent of the panel rating, isxModularDistSysCurrentRati…
1.3.6.1.4.1.318.1.1.22.4.2.7ScalarisxModularDistSysCurrentAlarmMinEnableread-writemandatoryEnable or disable minimum total output current alarm generation.
1.3.6.1.4.1.318.1.1.22.4.2.8ScalarisxModularDistSysCurrentAlarmLowEnableread-writemandatoryEnable or disable low total output current alarm generation.
1.3.6.1.4.1.318.1.1.22.4.2.9ScalarisxModularDistSysCurrentAlarmHighEnableread-writemandatoryEnable or disable high total output current alarm generation.
1.3.6.1.4.1.318.1.1.22.4.2.10ScalarisxModularDistSysCurrentAlarmMaxEnableread-writemandatoryEnable or disable maximum total output current alarm generation.
1.3.6.1.4.1.318.1.1.22.4.2.11TableisxModularDistSysCurrentTablenot-accessiblemandatoryAllows for getting the total system phase current information.
1.3.6.1.4.1.318.1.1.22.4.2.11.1RowisxModularDistSysCurrentEntrynot-accessiblemandatoryAn entry containing data for an individual system output phase.
1.3.6.1.4.1.318.1.1.22.4.2.11.1.1ColumnisxModularDistSysCurrentPhaseIndexread-onlymandatoryDescription of each phase entry in the table.
1.3.6.1.4.1.318.1.1.22.4.2.11.1.2ColumnisxModularDistSysCurrentAlarmStatusread-onlymandatoryThis is a bit map representing the active alarms for this output phase: b0 - Minimum current threshold exceeded (critical) b1 - Low current threshold exceeded …
1.3.6.1.4.1.318.1.1.22.4.2.11.1.3ColumnisxModularDistSysCurrentAmpsread-onlymandatoryThe current flowing though this system output phase. Measured in tenths of amps.
1.3.6.1.4.1.318.1.1.22.4.2.11.1.4ColumnisxModularDistSysCurrentPercentread-onlymandatoryThe loading on this system output phase as a percentage of the panel current rating. Expressed in tenths of percent.
1.3.6.1.4.1.318.1.1.22.4.3NodeisxModularDistSysPower
1.3.6.1.4.1.318.1.1.22.4.3.1ScalarisxModularDistSysPowerTotalread-onlymandatoryThe total system power being supplied. Measured in tenths of kW.
1.3.6.1.4.1.318.1.1.22.4.3.2ScalarisxModularDistSysPowerKwhUsageread-onlymandatoryThe total system energy consumed by the load equipment. This is the total since the date specified in the isxModularDistSysOutputKwhResetDate OID, and may be c…
1.3.6.1.4.1.318.1.1.22.4.3.3ScalarisxModularDistSysPowerKwhResetread-writemandatoryWriting yes to this OID will reset the total kWh usage shown in the isxModularDistSysPowerKwhUsage OID.
1.3.6.1.4.1.318.1.1.22.4.3.4ScalarisxModularDistSysPowerKwhResetDateread-onlymandatoryThe date that the kWh usage was reset, in the format mm/dd/yyyy. Example: 01/01/2000.
1.3.6.1.4.1.318.1.1.22.4.3.5TableisxModularDistSysPowerTablenot-accessiblemandatoryAllows for getting the total system phase power loading information.
1.3.6.1.4.1.318.1.1.22.4.3.5.1RowisxModularDistSysPowerEntrynot-accessiblemandatoryAn entry containing data for an individual system output phase.
1.3.6.1.4.1.318.1.1.22.4.3.5.1.1ColumnisxModularDistSysPowerPhaseIndexread-onlymandatoryDescription of each phase entry in the table.
1.3.6.1.4.1.318.1.1.22.4.3.5.1.2ColumnisxModularDistSysPowerKwread-onlymandatoryThe power being supplied by this system output phase. Measured in tenths of kW.
1.3.6.1.4.1.318.1.1.22.4.3.5.1.3ColumnisxModularDistSysPowerKwhPhaseUsageread-onlymandatoryThe energy consumed by the load equipment on this system output phase. This is the total since the date specified in the isxModularDistSysPowerKwhResetDate OID…
1.3.6.1.4.1.318.1.1.23NodeisxModularPdu
1.3.6.1.4.1.318.1.1.23.1NodeisxModularPduIdent
1.3.6.1.4.1.318.1.1.23.1.1ScalarisxModularPduIdentModelNumberread-onlymandatoryA character string identifying the model number of the PDU. This value is set at the factory.
1.3.6.1.4.1.318.1.1.23.1.2ScalarisxModularPduIdentSerialNumberread-onlymandatoryA character string identifying the serial number of the PDU. This value is set at the factory.
1.3.6.1.4.1.318.1.1.23.1.3ScalarisxModularPduIdentDateOfManufactureread-onlymandatoryThe date when the PDU was manufactured in mm/dd/yyyy format. This value is set at the factory.
1.3.6.1.4.1.318.1.1.23.1.4ScalarisxModularPduIdentMonitorCardSerialNumberread-onlymandatoryA character string identifying the serial number of the PDU monitor card. This value is set at the factory.
1.3.6.1.4.1.318.1.1.23.1.5ScalarisxModularPduIdentMonitorCardHardwareRevread-onlymandatoryThe hardware revision of the PDU monitor card. This value is set at the factory.
1.3.6.1.4.1.318.1.1.23.1.6ScalarisxModularPduIdentMonitorCardFirmwareAppRevread-onlymandatoryAn ID string identifying the application firmware revision of the PDU monitor card.
1.3.6.1.4.1.318.1.1.23.1.7ScalarisxModularPduIdentMonitorCardFirmwareAppOSRevread-onlymandatoryAn ID string identifying the application operating system firmware revision of the PDU monitor card.
1.3.6.1.4.1.318.1.1.23.2NodeisxModularPduDevice
1.3.6.1.4.1.318.1.1.23.2.1ScalarisxModularPduDeviceTransformerPresentread-onlymandatoryIndicates the type of transformer present in this PDU.
1.3.6.1.4.1.318.1.1.23.2.2ScalarisxModularPduDeviceServiceTyperead-onlymandatoryThe type of utility input to the PDU. Either 3 wires (delta), or 4 wires (wye).
1.3.6.1.4.1.318.1.1.23.2.3ScalarisxModularPduDeviceFansPresentread-onlymandatoryIndicates whether or not cooling fans are installed in the PDU.
1.3.6.1.4.1.318.1.1.23.2.4ScalarisxModularPduDeviceNominalMainInputVoltageread-onlymandatoryThe nominal main input voltage to the system. Measured in Volts, line-to-line for a 3-wire (delta) service or line-to-neutral for a 4-wire (wye) service. -1 if…
1.3.6.1.4.1.318.1.1.23.3NodeisxModularPduStatus
1.3.6.1.4.1.318.1.1.23.3.1ScalarisxModularPduAlarmStatusread-onlymandatoryThe overall status (worst case) of this PDU.
1.3.6.1.4.1.318.1.1.23.3.2ScalarisxModularPduTransformerTempStatusread-onlymandatoryIndicates if the PDU isolation transformer is over temperature.
1.3.6.1.4.1.318.1.1.23.3.3ScalarisxModularPduFanStatusread-onlymandatoryIndicates if one or more of the PDU's cooling fans have failed.
1.3.6.1.4.1.318.1.1.25NodeuniversalInputOutput
1.3.6.1.4.1.318.1.1.25.1NodeuioSensor
1.3.6.1.4.1.318.1.1.25.1.1ScalaruioSensorStatusTableSizeread-onlymandatoryThe number of entries in the uioSensorStatusTable.
1.3.6.1.4.1.318.1.1.25.1.2TableuioSensorStatusTablenot-accessiblemandatoryAllows for getting sensor status information.
1.3.6.1.4.1.318.1.1.25.1.2.1RowuioSensorStatusEntrynot-accessiblemandatoryThe unit from which to get data.
1.3.6.1.4.1.318.1.1.25.1.2.1.1ColumnuioSensorStatusPortIDread-onlymandatoryThe ID of the port to which the sensor is attached.
1.3.6.1.4.1.318.1.1.25.1.2.1.2ColumnuioSensorStatusSensorIDread-onlymandatoryThe ID of the sensor.
1.3.6.1.4.1.318.1.1.25.1.2.1.3ColumnuioSensorStatusSensorNameread-onlymandatoryThe sensor name.
1.3.6.1.4.1.318.1.1.25.1.2.1.4ColumnuioSensorStatusSensorLocationread-onlymandatoryThe location of the sensor.
1.3.6.1.4.1.318.1.1.25.1.2.1.5ColumnuioSensorStatusTemperatureDegFread-onlymandatoryThe sensor's current temperature reading in degrees Fahrenheit. -1 indicates an invalid reading due to lost communications.
1.3.6.1.4.1.318.1.1.25.1.2.1.6ColumnuioSensorStatusTemperatureDegCread-onlymandatoryThe sensor's current temperature reading in degrees Celsius. -1 indicates an invalid reading due to lost communications.
1.3.6.1.4.1.318.1.1.25.1.2.1.7ColumnuioSensorStatusHumidityread-onlymandatoryThe sensor's current humidity reading in percent relative humidity. -1 indicates an invalid reading due to either a sensor that doesn't read humidity or lost c…
1.3.6.1.4.1.318.1.1.25.1.2.1.8ColumnuioSensorStatusViolationStatusread-onlymandatoryThe violation status of the sensor. This integer should be interpreted as a bit map, with each bit representing the presence or absence of the specific alarm c…
1.3.6.1.4.1.318.1.1.25.1.2.1.9ColumnuioSensorStatusAlarmStatusread-onlymandatoryThe alarm status of the sensor.
1.3.6.1.4.1.318.1.1.25.1.2.1.10ColumnuioSensorStatusCommStatusread-onlymandatoryThe communications status of the sensor.
1.3.6.1.4.1.318.1.1.25.1.3ScalaruioSensorConfigTableSizeread-onlymandatoryThe number of entries in the uioSensorConfigTable.
1.3.6.1.4.1.318.1.1.25.1.4TableuioSensorConfigTablenot-accessiblemandatoryAllows for configuring the sensor.
1.3.6.1.4.1.318.1.1.25.1.4.1RowuioSensorConfigEntrynot-accessiblemandatoryThe sensor from which to get configuration.
1.3.6.1.4.1.318.1.1.25.1.4.1.1ColumnuioSensorConfigPortIDread-onlymandatoryThe ID of the port to which the sensor is attached.
1.3.6.1.4.1.318.1.1.25.1.4.1.2ColumnuioSensorConfigSensorIDread-onlymandatoryThe ID of the sensor.
1.3.6.1.4.1.318.1.1.25.1.4.1.3ColumnuioSensorConfigSensorNameread-writemandatoryThe sensor name.
1.3.6.1.4.1.318.1.1.25.1.4.1.4ColumnuioSensorConfigSensorLocationread-writemandatoryThe location of the sensor.
1.3.6.1.4.1.318.1.1.25.1.4.1.5ColumnuioSensorConfigMinTemperatureThresholdread-writemandatoryThe minimum (critical) temperature alarm threshold for the probe in degrees C. Must be lower than the low threshold to ensure proper sensor alarm behavior.
1.3.6.1.4.1.318.1.1.25.1.4.1.6ColumnuioSensorConfigLowTemperatureThresholdread-writemandatoryThe low (warning) temperature alarm threshold for the probe in degrees C. Must be higher than the minimum threshold and lower than the high threshold to ensure…
1.3.6.1.4.1.318.1.1.25.1.4.1.7ColumnuioSensorConfigHighTemperatureThresholdread-writemandatoryThe high (warning) temperature alarm threshold for the probe in degrees C. Must be lower than the maximum threshold and higher than the low threshold to ensure…
1.3.6.1.4.1.318.1.1.25.1.4.1.8ColumnuioSensorConfigMaxTemperatureThresholdread-writemandatoryThe maximum (critical) temperature alarm threshold for the probe in degrees C. Must be higher than the high threshold to ensure proper sensor alarm behavior.
1.3.6.1.4.1.318.1.1.25.1.4.1.9ColumnuioSensorConfigTemperatureHysteresisread-writemandatoryThe number of degrees C beyond the temperature thresholds at which an active temperature alarm will be cleared. This value applies to all temperature threshold…
1.3.6.1.4.1.318.1.1.25.1.4.1.10ColumnuioSensorConfigMinTemperatureEnableread-writemandatoryThe minimum temperature alarm enable/disable for the sensor. 1 - disabled 2 - enabled
1.3.6.1.4.1.318.1.1.25.1.4.1.11ColumnuioSensorConfigLowTemperatureEnableread-writemandatoryThe low temperature alarm enable/disable for the sensor. 1 - disabled 2 - enabled
1.3.6.1.4.1.318.1.1.25.1.4.1.12ColumnuioSensorConfigHighTemperatureEnableread-writemandatoryThe high temperature alarm enable/disable for the sensor. 1 - disabled 2 - enabled
1.3.6.1.4.1.318.1.1.25.1.4.1.13ColumnuioSensorConfigMaxTemperatureEnableread-writemandatoryThe maximum temperature alarm enable/disable for the sensor. 1 - disabled 2 - enabled
1.3.6.1.4.1.318.1.1.25.1.4.1.14ColumnuioSensorConfigMinHumidityThresholdread-writemandatoryThe minimum (critical) humidity alarm threshold for the probe in percent relative humidity. Must be lower than the low threshold to ensure proper sensor alarm …
1.3.6.1.4.1.318.1.1.25.1.4.1.15ColumnuioSensorConfigLowHumidityThresholdread-writemandatoryThe low (warning) humidity alarm threshold for the probe in percent relative humidity. Must be higher than the minimum threshold and lower than the high thresh…
1.3.6.1.4.1.318.1.1.25.1.4.1.16ColumnuioSensorConfigHighHumidityThresholdread-writemandatoryThe high (warning) humidity alarm threshold for the probe in percent relative humidity. Must be lower than the maximum threshold and higher than the low thresh…
1.3.6.1.4.1.318.1.1.25.1.4.1.17ColumnuioSensorConfigMaxHumidityThresholdread-writemandatoryThe maximum (critical) humidity alarm threshold for the probe in percent relative humidity. Must be higher than the high threshold to ensure proper sensor alar…
1.3.6.1.4.1.318.1.1.25.1.4.1.18ColumnuioSensorConfigHumidityHysteresisread-writemandatoryThe number of percent relative humidity beyond the humidity thresholds at which an active humidity alarm will be cleared. This value applies to all humidity th…
1.3.6.1.4.1.318.1.1.25.1.4.1.19ColumnuioSensorConfigMinHumidityEnableread-writemandatoryThe minimum humidity alarm enable/disable for the sensor. 1 - disabled (always set if the sensor doesn't read humidity) 2 - enabled
1.3.6.1.4.1.318.1.1.25.1.4.1.20ColumnuioSensorConfigLowHumidityEnableread-writemandatoryThe low humidity alarm enable/disable for the sensor. 1 - disabled (always set if the sensor doesn't read humidity) 2 - enabled
1.3.6.1.4.1.318.1.1.25.1.4.1.21ColumnuioSensorConfigHighHumidityEnableread-writemandatoryThe high humidity alarm enable/disable for the sensor. 1 - disabled (always set if the sensor doesn't read humidity) 2 - enabled
1.3.6.1.4.1.318.1.1.25.1.4.1.22ColumnuioSensorConfigMaxHumidityEnableread-writemandatoryThe maximum humidity alarm enable/disable for the sensor. 1 - disabled (always set if the sensor doesn't read humidity) 2 - enabled
1.3.6.1.4.1.318.1.1.25.2NodeuioInputContact
1.3.6.1.4.1.318.1.1.25.2.1ScalaruioInputContactStatusTableSizeread-onlymandatoryThe number of entries in the uioInputContactStatusTable.
1.3.6.1.4.1.318.1.1.25.2.2TableuioInputContactStatusTablenot-accessiblemandatoryAllows for getting input contact status information.
1.3.6.1.4.1.318.1.1.25.2.2.1RowuioInputContactStatusEntrynot-accessiblemandatoryThe input contact from which to get data.
1.3.6.1.4.1.318.1.1.25.2.2.1.1ColumnuioInputContactStatusPortIDread-onlymandatoryThe ID of the port to which the input contact is attached.
1.3.6.1.4.1.318.1.1.25.2.2.1.2ColumnuioInputContactStatusContactIDread-onlymandatoryThe ID of the input contact on the module.
1.3.6.1.4.1.318.1.1.25.2.2.1.3ColumnuioInputContactStatusContactNameread-onlymandatoryThe input contact name.
1.3.6.1.4.1.318.1.1.25.2.2.1.4ColumnuioInputContactStatusContactLocationread-onlymandatoryThe location of the input contact.
1.3.6.1.4.1.318.1.1.25.2.2.1.5ColumnuioInputContactStatusCurrentStateread-onlymandatoryThe current state of the input contact.
1.3.6.1.4.1.318.1.1.25.2.2.1.6ColumnuioInputContactStatusAlarmStatusread-onlymandatoryThe alarm status of the input contact.
1.3.6.1.4.1.318.1.1.25.2.2.1.7ColumnuioInputContactStatusCommStatusread-onlymandatoryThe communications status of the input contact.
1.3.6.1.4.1.318.1.1.25.2.3ScalaruioInputContactConfigTableSizeread-onlymandatoryThe number of entries in the uioInputContactConfigTable.
1.3.6.1.4.1.318.1.1.25.2.4TableuioInputContactConfigTablenot-accessiblemandatoryAllows for configuring the input contacts.
1.3.6.1.4.1.318.1.1.25.2.4.1RowuioInputContactConfigEntrynot-accessiblemandatoryThe input contact from which to get configuration.
1.3.6.1.4.1.318.1.1.25.2.4.1.1ColumnuioInputContactConfigPortIDread-onlymandatoryThe ID of the port to which the input contact is attached.
1.3.6.1.4.1.318.1.1.25.2.4.1.2ColumnuioInputContactConfigContactIDread-onlymandatoryThe ID of the input contact on the module.
1.3.6.1.4.1.318.1.1.25.2.4.1.3ColumnuioInputContactConfigContactNameread-writemandatoryThe input contact name.
1.3.6.1.4.1.318.1.1.25.2.4.1.4ColumnuioInputContactConfigContactLocationread-writemandatoryThe location of the input contact.
1.3.6.1.4.1.318.1.1.25.2.4.1.5ColumnuioInputContactConfigEnableread-writemandatoryEnable or disable this input contact. 1 - disabled 2 - enabled
1.3.6.1.4.1.318.1.1.25.2.4.1.6ColumnuioInputContactConfigNormalStateread-writemandatoryThe normal (non-alarm) state of the input contact. 1 - normally open 2 - normally closed
1.3.6.1.4.1.318.1.1.25.2.4.1.7ColumnuioInputContactConfigSeverityread-writemandatoryThe severity of the alarm that this input contact will generate in the abnormal state. 1 - critical severity 2 - warning severity
1.3.6.1.4.1.318.1.1.25.3NodeuioOutputRelay
1.3.6.1.4.1.318.1.1.25.3.1ScalaruioOutputRelayStatusTableSizeread-onlymandatoryThe number of entries in the uioOutputRelayStatusTable.
1.3.6.1.4.1.318.1.1.25.3.2TableuioOutputRelayStatusTablenot-accessiblemandatoryAllows for getting output relay status information.
1.3.6.1.4.1.318.1.1.25.3.2.1RowuioOutputRelayStatusEntrynot-accessiblemandatoryThe unit from which to get data.
1.3.6.1.4.1.318.1.1.25.3.2.1.1ColumnuioOutputRelayStatusPortIDread-onlymandatoryThe ID of the port to which the output relay is attached.
1.3.6.1.4.1.318.1.1.25.3.2.1.2ColumnuioOutputRelayStatusRelayIDread-onlymandatoryThe ID of the output relay on the module.
1.3.6.1.4.1.318.1.1.25.3.2.1.3ColumnuioOutputRelayStatusRelayNameread-onlymandatoryThe output relay name.
1.3.6.1.4.1.318.1.1.25.3.2.1.4ColumnuioOutputRelayStatusRelayLocationread-onlymandatoryThe location of the output relay.
1.3.6.1.4.1.318.1.1.25.3.2.1.5ColumnuioOutputRelayStatusCurrentStateread-onlymandatoryThe current state of the output relay.
1.3.6.1.4.1.318.1.1.25.3.2.1.6ColumnuioOutputRelayStatusAlarmStatusread-onlymandatoryThe alarm status of the output relay.
1.3.6.1.4.1.318.1.1.25.3.2.1.7ColumnuioOutputRelayStatusCommStatusread-onlymandatoryThe communications status of the output relay.
1.3.6.1.4.1.318.1.1.25.3.3ScalaruioOutputRelayConfigTableSizeread-onlymandatoryThe number of entries in the uioOutputRelayConfigTable.
1.3.6.1.4.1.318.1.1.25.3.4TableuioOutputRelayConfigTablenot-accessiblemandatoryAllows for configuring the output relay.
1.3.6.1.4.1.318.1.1.25.3.4.1RowuioOutputRelayConfigEntrynot-accessiblemandatoryThe unit from which to get configuration.
1.3.6.1.4.1.318.1.1.25.3.4.1.1ColumnuioOutputRelayConfigPortIDread-onlymandatoryThe ID of the port to which the output relay is attached.
1.3.6.1.4.1.318.1.1.25.3.4.1.2ColumnuioOutputRelayConfigRelayIDread-onlymandatoryThe ID of the output relay on the module.
1.3.6.1.4.1.318.1.1.25.3.4.1.3ColumnuioOutputRelayConfigRelayNameread-writemandatoryThe output relay name.
1.3.6.1.4.1.318.1.1.25.3.4.1.4ColumnuioOutputRelayConfigRelayLocationread-writemandatoryThe location of the output relay.
1.3.6.1.4.1.318.1.1.25.3.4.1.5ColumnuioOutputRelayConfigNormalStateread-writemandatoryThe normal state of the output relay. 1 - normally open 2 - normally closed
1.3.6.1.4.1.318.1.1.25.3.4.1.6ColumnuioOutputRelayConfigControlStateread-writemandatoryClose or open the output relay for testing purposes. Always returns 1 when read. 1 - close output relay 2 - open output relay
1.3.6.1.4.1.318.1.1.25.3.4.1.7ColumnuioOutputRelayConfigDelayread-writemandatoryThe time a selected alarm condition must exist before the output relay is activated. Valid values are whole seconds from 0 to 65535.
1.3.6.1.4.1.318.1.1.25.3.4.1.8ColumnuioOutputRelayConfigHoldread-writemandatoryThe minimum time the output relay remains activated after the alarm occurs. Valid values are whole seconds from 0 to 65535.
1.3.6.1.4.1.318.1.1.26NoderPDU2
1.3.6.1.4.1.318.1.1.26.1ScalarrPDU2IdentTableSizeread-onlymandatoryThe total number of Rack PDUs
1.3.6.1.4.1.318.1.1.26.2TablerPDU2IdentTablenot-accessiblemandatoryA table of Rack PDU identification data
1.3.6.1.4.1.318.1.1.26.2.1RowrPDU2IdentEntrynot-accessiblemandatoryIdentification data from Rack PDU being queried
1.3.6.1.4.1.318.1.1.26.2.1.1ColumnrPDU2IdentIndexread-onlymandatoryThe index to the Rack PDU identification table entry
1.3.6.1.4.1.318.1.1.26.2.1.2ColumnrPDU2IdentModuleread-onlymandatoryThe user-defined Rack PDU numeric ID
1.3.6.1.4.1.318.1.1.26.2.1.3ColumnrPDU2IdentNameread-onlymandatoryA user-defined string identifying the Rack PDU
1.3.6.1.4.1.318.1.1.26.2.1.4ColumnrPDU2IdentLocationread-onlymandatoryA user-defined string identifying the location of the Rack PDU
1.3.6.1.4.1.318.1.1.26.2.1.5ColumnrPDU2IdentHardwareRevread-onlymandatoryThe Rack PDU hardware version
1.3.6.1.4.1.318.1.1.26.2.1.6ColumnrPDU2IdentFirmwareRevread-onlymandatoryThe Rack PDU firmware version
1.3.6.1.4.1.318.1.1.26.2.1.7ColumnrPDU2IdentDateOfManufactureread-onlymandatoryThe date the Rack PDU was manufactured in mm/dd/yyyy format
1.3.6.1.4.1.318.1.1.26.2.1.8ColumnrPDU2IdentModelNumberread-onlymandatoryThe Rack PDU model number
1.3.6.1.4.1.318.1.1.26.2.1.9ColumnrPDU2IdentSerialNumberread-onlymandatoryThe Rack PDU serial number
1.3.6.1.4.1.318.1.1.26.2.1.10ColumnrPDU2IdentContactread-onlymandatoryA user-defined string identifying the person to contact regarding the Rack PDU
1.3.6.1.4.1.318.1.1.26.2.1.11ColumnrPDU2IdentBootMonitorRevread-onlymandatoryThe Rack PDU Boot Monitor version
1.3.6.1.4.1.318.1.1.26.2.1.12ColumnrPDU2IdentLongDescriptionread-onlymandatoryThe Rack PDU Long Description name
1.3.6.1.4.1.318.1.1.26.2.1.13ColumnrPDU2IdentNMCSerialNumberread-onlymandatoryThe Rack PDU Network Management Card (NMC) serial number
1.3.6.1.4.1.318.1.1.26.3ScalarrPDU2DeviceTableSizeread-onlymandatoryThe total number of Rack PDUs
1.3.6.1.4.1.318.1.1.26.4NoderPDU2Device
1.3.6.1.4.1.318.1.1.26.4.1TablerPDU2DeviceConfigTablenot-accessiblemandatoryA table of Rack PDU configuration data
1.3.6.1.4.1.318.1.1.26.4.1.1RowrPDU2DeviceConfigEntrynot-accessiblemandatoryConfiguration data from Rack PDU being queried
1.3.6.1.4.1.318.1.1.26.4.1.1.1ColumnrPDU2DeviceConfigIndexread-onlymandatoryThe index to the Rack PDU table entry
1.3.6.1.4.1.318.1.1.26.4.1.1.2ColumnrPDU2DeviceConfigModuleread-writemandatoryThe user-defined Rack PDU numeric ID
1.3.6.1.4.1.318.1.1.26.4.1.1.3ColumnrPDU2DeviceConfigNameread-writemandatoryA user-defined string identifying the Rack PDU
1.3.6.1.4.1.318.1.1.26.4.1.1.4ColumnrPDU2DeviceConfigLocationread-writemandatoryA user-defined string identifying the location of the Rack PDU
1.3.6.1.4.1.318.1.1.26.4.1.1.5ColumnrPDU2DeviceConfigDisplayOrientationread-writemandatoryIndicates the intended physical orientation of the display. displayNormal(1) indicates normal orientation displayReverse(2) indicates upside down orientation
1.3.6.1.4.1.318.1.1.26.4.1.1.6ColumnrPDU2DeviceConfigColdstartDelayread-writemandatoryThe amount of delay, measured in seconds, between when power is provided to the Rack PDU and when the Rack PDU provides basic master power to the outlets. Allo…
1.3.6.1.4.1.318.1.1.26.4.1.1.7ColumnrPDU2DeviceConfigLowLoadPowerThresholdread-writemandatoryUser-defined low power draw alarm threshold, measured in tenths of kilowatts. Models that do not support this feature will respond to this OID with a value of …
1.3.6.1.4.1.318.1.1.26.4.1.1.8ColumnrPDU2DeviceConfigNearOverloadPowerThresholdread-writemandatoryUser-defined near power overload threshold, measured in tenths of kilowatts. Models that do not support this feature will respond to this OID with a value of -…
1.3.6.1.4.1.318.1.1.26.4.1.1.9ColumnrPDU2DeviceConfigOverloadPowerThresholdread-writemandatoryUser-defined power overload threshold, measured in tenths of kilowatts. Models that do not support this feature will respond to this OID with a value of -1.
1.3.6.1.4.1.318.1.1.26.4.1.1.10ColumnrPDU2DeviceConfigDevicePeakPowerResetread-writemandatorySetting this OID to reset (2) will cause the existing peak power value to be replaced by the current load power value. Getting this OID will do nothing and ret…
1.3.6.1.4.1.318.1.1.26.4.1.1.11ColumnrPDU2DeviceConfigDeviceEnergyResetread-writemandatorySetting this OID to reset (2) will cause the device energy meter value to be reset to zero. Getting this OID in models that support this feature will do nothin…
1.3.6.1.4.1.318.1.1.26.4.1.1.12ColumnrPDU2DeviceConfigOutletsEnergyResetread-writemandatorySetting this OID to reset (2) will cause the all outlet energy meter values to be reset to zero. Getting this OID will do nothing and return the noOperation(1)…
1.3.6.1.4.1.318.1.1.26.4.1.1.13ColumnrPDU2DeviceConfigOutletsPeakLoadResetread-writemandatorySetting this OID to reset (2) will cause the all outlet peak load values to be reset to zero. Getting this OID will do nothing and return the noOperation(1) va…
1.3.6.1.4.1.318.1.1.26.4.1.1.14ColumnrPDU2DeviceConfigContactread-writemandatoryA user-defined string identifying the person to contact regarding the Rack PDU
1.3.6.1.4.1.318.1.1.26.4.2TablerPDU2DevicePropertiesTablenot-accessiblemandatoryA table of Rack PDU properties
1.3.6.1.4.1.318.1.1.26.4.2.1RowrPDU2DevicePropertiesEntrynot-accessiblemandatoryProperties of the Rack PDU being queried
1.3.6.1.4.1.318.1.1.26.4.2.1.1ColumnrPDU2DevicePropertiesIndexread-onlymandatoryThe index to the Rack PDU properties table entry
1.3.6.1.4.1.318.1.1.26.4.2.1.2ColumnrPDU2DevicePropertiesModuleread-onlymandatoryThe user-defined Rack PDU numeric ID
1.3.6.1.4.1.318.1.1.26.4.2.1.3ColumnrPDU2DevicePropertiesNameread-onlymandatoryA user-defined string identifying the Rack PDU
1.3.6.1.4.1.318.1.1.26.4.2.1.4ColumnrPDU2DevicePropertiesNumOutletsread-onlymandatoryThe number of outlets on the Rack PDU
1.3.6.1.4.1.318.1.1.26.4.2.1.5ColumnrPDU2DevicePropertiesNumSwitchedOutletsread-onlymandatoryThe number of switched outlets on the Rack PDU
1.3.6.1.4.1.318.1.1.26.4.2.1.6ColumnrPDU2DevicePropertiesNumMeteredOutletsread-onlymandatoryThe number of metered outlets on the Rack PDU
1.3.6.1.4.1.318.1.1.26.4.2.1.7ColumnrPDU2DevicePropertiesNumPhasesread-onlymandatoryThe number of phases present in the Rack PDU
1.3.6.1.4.1.318.1.1.26.4.2.1.8ColumnrPDU2DevicePropertiesNumMeteredBanksread-onlymandatoryThe number of metered banks present in the Rack PDU
1.3.6.1.4.1.318.1.1.26.4.2.1.9ColumnrPDU2DevicePropertiesMaxCurrentRatingread-onlymandatoryThe maximum current rating, measured in Amps, for the Rack PDU
1.3.6.1.4.1.318.1.1.26.4.2.1.10ColumnrPDU2DevicePropertiesOrientationread-onlymandatoryRack PDU orientation
1.3.6.1.4.1.318.1.1.26.4.2.1.11ColumnrPDU2DevicePropertiesOutletLayoutread-onlymandatoryGetting this OID will return outlet layout for the device. seqPhaseToNeutral(1) indicates outlet layout as follows: 1:1-N,2:2-N,3:3-N,4:1-N,5:2-N,... or for si…
1.3.6.1.4.1.318.1.1.26.4.2.1.12ColumnrPDU2DevicePropertiesMaxPhaseCurrentRatingread-onlymandatoryThe maximum current rating, measured in Amps, for the Rack PDU
1.3.6.1.4.1.318.1.1.26.4.2.1.13ColumnrPDU2DevicePropertiesDevicePowerRatingread-onlymandatoryThe maximum power rating, measured in Watts, for the Rack PDU
1.3.6.1.4.1.318.1.1.26.4.3TablerPDU2DeviceStatusTablenot-accessiblemandatoryA table of Rack PDU status information
1.3.6.1.4.1.318.1.1.26.4.3.1RowrPDU2DeviceStatusEntrynot-accessiblemandatoryStatus information from the Rack PDU being queried
1.3.6.1.4.1.318.1.1.26.4.3.1.1ColumnrPDU2DeviceStatusIndexread-onlymandatoryThe index to the Rack PDU status table entry
1.3.6.1.4.1.318.1.1.26.4.3.1.2ColumnrPDU2DeviceStatusModuleread-onlymandatoryThe user-defined Rack PDU numeric ID
1.3.6.1.4.1.318.1.1.26.4.3.1.3ColumnrPDU2DeviceStatusNameread-onlymandatoryA user-defined string identifying the Rack PDU
1.3.6.1.4.1.318.1.1.26.4.3.1.4ColumnrPDU2DeviceStatusLoadStateread-onlymandatoryIndicates the present load status of the Rack PDU. Models that do not support this feature will respond to this OID with a value of notsupported (5).
1.3.6.1.4.1.318.1.1.26.4.3.1.5ColumnrPDU2DeviceStatusPowerread-onlymandatoryThe power consumption of the Rack PDU load in hundredths of kilowatts. Models that do not support this feature will respond to this OID with a value of -1.
1.3.6.1.4.1.318.1.1.26.4.3.1.6ColumnrPDU2DeviceStatusPeakPowerread-onlymandatoryThe peak power consumption of the Rack PDU load in hundredths of kilowatts. Models that do not support this feature will respond to this OID with a value of -1.
1.3.6.1.4.1.318.1.1.26.4.3.1.7ColumnrPDU2DeviceStatusPeakPowerTimestampread-onlymandatoryIndicates the date and time that peak power consumption occurred. Models that do not support this feature will respond to this OID with string 'notsupported'.
1.3.6.1.4.1.318.1.1.26.4.3.1.8ColumnrPDU2DeviceStatusPeakPowerStartTimeread-onlymandatoryIndicates the date and time of the last device peak power reset. Models that do not support this feature will respond to this OID with string 'notsupported'.
1.3.6.1.4.1.318.1.1.26.4.3.1.9ColumnrPDU2DeviceStatusEnergyread-onlymandatoryA user resettable energy meter measuring Rack PDU load energy consumption in tenths of kilowatt-hours. Models that do not support this feature will respond to …
1.3.6.1.4.1.318.1.1.26.4.3.1.10ColumnrPDU2DeviceStatusEnergyStartTimeread-onlymandatoryIndicates the date and time of the last device energy meter reset. Models that do not support this feature will respond to this OID with string 'notsupported'.
1.3.6.1.4.1.318.1.1.26.4.3.1.11ColumnrPDU2DeviceStatusCommandPendingread-onlymandatoryIndicates whether or not the device is processing a pending command. If the commandPendingUnknown (3) value is returned, all devices powered by the Rack PDU sh…
1.3.6.1.4.1.318.1.1.26.4.3.1.12ColumnrPDU2DeviceStatusPowerSupplyAlarmread-onlymandatoryIndicates a power supply alarm is active when value equals alarm (2)
1.3.6.1.4.1.318.1.1.26.4.3.1.13ColumnrPDU2DeviceStatusPowerSupply1Statusread-onlymandatoryIndicates whether or not an alarm is active in Power Supply 1
1.3.6.1.4.1.318.1.1.26.4.3.1.14ColumnrPDU2DeviceStatusPowerSupply2Statusread-onlymandatoryIndicates whether or not an alarm is active in Power Supply 2
1.3.6.1.4.1.318.1.1.26.4.3.1.15ColumnrPDU2DeviceStatusOutletsEnergyStartTimeread-onlymandatoryIndicates the date and time of the last outlets energy meter reset. Models that do not support this feature will respond to this OID with string 'notsupported'.
1.3.6.1.4.1.318.1.1.26.4.3.1.16ColumnrPDU2DeviceStatusApparentPowerread-onlymandatoryThe apparent power consumption of the Rack PDU load in hundredths of kiloVoltAmps (kVA). Models that do not support this feature will respond to this OID with …
1.3.6.1.4.1.318.1.1.26.4.3.1.17ColumnrPDU2DeviceStatusPowerFactorread-onlymandatoryThe power factor of the Rack PDU load in hundredths. Models that do not support this feature will respond to this OID with a value of -1.
1.3.6.1.4.1.318.1.1.26.4.3.1.18ColumnrPDU2DeviceStatusNPSTyperead-onlymandatoryThe device NPS status: notNPS (1) indicates the Rack PDU is not in an NPS group. host (2) indicates the Rack PDU has been designated as a host in an NPS group.…
1.3.6.1.4.1.318.1.1.26.4.4TablerPDU2DeviceControlTablenot-accessiblemandatoryA table of Rack PDU control data
1.3.6.1.4.1.318.1.1.26.4.4.1RowrPDU2DeviceControlEntrynot-accessiblemandatoryControl data from Rack PDU being queried
1.3.6.1.4.1.318.1.1.26.4.4.1.1ColumnrPDU2DeviceControlIndexread-onlymandatoryThe index to the Rack PDU control table entry
1.3.6.1.4.1.318.1.1.26.4.4.1.2ColumnrPDU2DeviceControlModuleread-onlymandatoryThe user-defined Rack PDU numeric ID
1.3.6.1.4.1.318.1.1.26.4.4.1.3ColumnrPDU2DeviceControlNameread-onlymandatoryA user-defined string identifying the Rack PDU
1.3.6.1.4.1.318.1.1.26.4.4.1.4ColumnrPDU2DeviceControlCommandread-writemandatorySetting this OID to immediateAllOn (1) will turn all outlets on immediately. Setting this OID to delayedAllOn (2) will turn all outlets on as defined by each o…
1.3.6.1.4.1.318.1.1.26.5ScalarrPDU2PhaseTableSizeread-onlymandatoryThe number of connected Rack PDU phases
1.3.6.1.4.1.318.1.1.26.6NoderPDU2Phase
1.3.6.1.4.1.318.1.1.26.6.1TablerPDU2PhaseConfigTablenot-accessiblemandatoryA table of Rack PDU phase configuration data
1.3.6.1.4.1.318.1.1.26.6.1.1RowrPDU2PhaseConfigEntrynot-accessiblemandatoryConfiguration data from currently queried Rack PDU phase
1.3.6.1.4.1.318.1.1.26.6.1.1.1ColumnrPDU2PhaseConfigIndexread-onlymandatoryThe index to the Rack PDU phase configuration table entry
1.3.6.1.4.1.318.1.1.26.6.1.1.2ColumnrPDU2PhaseConfigModuleread-onlymandatoryThe user-defined Rack PDU numeric ID
1.3.6.1.4.1.318.1.1.26.6.1.1.3ColumnrPDU2PhaseConfigNumberread-onlymandatoryThe numeric phase ID
1.3.6.1.4.1.318.1.1.26.6.1.1.4ColumnrPDU2PhaseConfigOverloadRestrictionread-writemandatoryThis OID controls the behavior of a Switched Rack PDU phase when an overload condition is possible and additional outlets are requested to be turned on. Settin…
1.3.6.1.4.1.318.1.1.26.6.1.1.5ColumnrPDU2PhaseConfigLowLoadCurrentThresholdread-writemandatoryUser-defined low load phase current threshold in Amps
1.3.6.1.4.1.318.1.1.26.6.1.1.6ColumnrPDU2PhaseConfigNearOverloadCurrentThresholdread-writemandatoryUser-defined near phase overload warning threshold in Amps
1.3.6.1.4.1.318.1.1.26.6.1.1.7ColumnrPDU2PhaseConfigOverloadCurrentThresholdread-writemandatoryUser-defined phase overload current threshold in Amps
1.3.6.1.4.1.318.1.1.26.6.1.1.8ColumnrPDU2PhaseConfigPhasePeakCurrentResetread-writemandatorySetting this OID to reset (2) will cause the existing peak current value to be replaced by the present load current value. Getting this OID will do nothing and…
1.3.6.1.4.1.318.1.1.26.6.2TablerPDU2PhasePropertiesTablenot-accessiblemandatoryA table of Rack PDU phase properties
1.3.6.1.4.1.318.1.1.26.6.2.1RowrPDU2PhasePropertiesEntrynot-accessiblemandatoryProperties of the currently queried Rack PDU phase
1.3.6.1.4.1.318.1.1.26.6.2.1.1ColumnrPDU2PhasePropertiesIndexread-onlymandatoryThe index to the Rack PDU phase properties table entry
1.3.6.1.4.1.318.1.1.26.6.2.1.2ColumnrPDU2PhasePropertiesModuleread-onlymandatoryThe user-defined Rack PDU numeric ID
1.3.6.1.4.1.318.1.1.26.6.2.1.3ColumnrPDU2PhasePropertiesNumberread-onlymandatoryThe numeric phase ID
1.3.6.1.4.1.318.1.1.26.6.3TablerPDU2PhaseStatusTablenot-accessiblemandatoryA table of Rack PDU phase status data
1.3.6.1.4.1.318.1.1.26.6.3.1RowrPDU2PhaseStatusEntrynot-accessiblemandatoryStatus data from currently queried Rack PDU phase
1.3.6.1.4.1.318.1.1.26.6.3.1.1ColumnrPDU2PhaseStatusIndexread-onlymandatoryThe index to the Rack PDU phase status table entry
1.3.6.1.4.1.318.1.1.26.6.3.1.2ColumnrPDU2PhaseStatusModuleread-onlymandatoryThe user-defined Rack PDU numeric ID
1.3.6.1.4.1.318.1.1.26.6.3.1.3ColumnrPDU2PhaseStatusNumberread-onlymandatoryThe numeric phase ID
1.3.6.1.4.1.318.1.1.26.6.3.1.4ColumnrPDU2PhaseStatusLoadStateread-onlymandatoryIndicates the present load status of the Rack PDU phase being queried
1.3.6.1.4.1.318.1.1.26.6.3.1.5ColumnrPDU2PhaseStatusCurrentread-onlymandatoryIndicates the current draw, in tenths of Amps, of the load on the Rack PDU phase being queried
1.3.6.1.4.1.318.1.1.26.6.3.1.6ColumnrPDU2PhaseStatusVoltageread-onlymandatoryIndicates the Voltage, in Volts, of the Rack PDU phase being queried. Models that do not support this feature will respond to this OID with a value of -1.
1.3.6.1.4.1.318.1.1.26.6.3.1.7ColumnrPDU2PhaseStatusPowerread-onlymandatoryIndicates the load power, in hundredths of kilowatts (kW), consumed on the Rack PDU phase being queried. Models that do not support this feature will respond t…
1.3.6.1.4.1.318.1.1.26.6.3.1.8ColumnrPDU2PhaseStatusApparentPowerread-onlymandatoryIndicates the load apparent power, in hundredths of kiloVoltAmps (kVA), consumed on the Rack PDU phase being queried. Models that do not support this feature w…
1.3.6.1.4.1.318.1.1.26.6.3.1.9ColumnrPDU2PhaseStatusPowerFactorread-onlymandatoryIndicates the load power factor, in hundredths, of the Rack PDU phase being queried. Models that do not support this feature will respond to this OID with a va…
1.3.6.1.4.1.318.1.1.26.6.3.1.10ColumnrPDU2PhaseStatusPeakCurrentread-onlymandatoryThe peak current of the Rack PDU phase load in tenths of Amps
1.3.6.1.4.1.318.1.1.26.6.3.1.11ColumnrPDU2PhaseStatusPeakCurrentTimestampread-onlymandatoryIndicates the date and time that the peak current occurred
1.3.6.1.4.1.318.1.1.26.6.3.1.12ColumnrPDU2PhaseStatusPeakCurrentStartTimeread-onlymandatoryIndicates the date and time of the last phase peak current reset
1.3.6.1.4.1.318.1.1.26.7ScalarrPDU2BankTableSizeread-onlymandatoryThe number of connected Rack PDU banks
1.3.6.1.4.1.318.1.1.26.8NoderPDU2Bank
1.3.6.1.4.1.318.1.1.26.8.1TablerPDU2BankConfigTablenot-accessiblemandatoryA table of Rack PDU bank configuration data
1.3.6.1.4.1.318.1.1.26.8.1.1RowrPDU2BankConfigEntrynot-accessiblemandatoryConfiguration data from currently queried Rack PDU bank
1.3.6.1.4.1.318.1.1.26.8.1.1.1ColumnrPDU2BankConfigIndexread-onlymandatoryThe index to the Rack PDU bank configuration table entry
1.3.6.1.4.1.318.1.1.26.8.1.1.2ColumnrPDU2BankConfigModuleread-onlymandatoryThe user-defined Rack PDU numeric ID
1.3.6.1.4.1.318.1.1.26.8.1.1.3ColumnrPDU2BankConfigNumberread-onlymandatoryThe numeric bank ID
1.3.6.1.4.1.318.1.1.26.8.1.1.4ColumnrPDU2BankConfigOverloadRestrictionread-writemandatoryThis OID controls the behavior of a Switched Rack PDU bank when an overload condition is possible and additional outlets are requested to be turned on. Setting…
1.3.6.1.4.1.318.1.1.26.8.1.1.5ColumnrPDU2BankConfigLowLoadCurrentThresholdread-writemandatoryUser-defined low load bank current threshold in Amps
1.3.6.1.4.1.318.1.1.26.8.1.1.6ColumnrPDU2BankConfigNearOverloadCurrentThresholdread-writemandatoryUser-defined near bank overload current warning threshold in Amps
1.3.6.1.4.1.318.1.1.26.8.1.1.7ColumnrPDU2BankConfigOverloadCurrentThresholdread-writemandatoryUser-defined bank overload current threshold in Amps
1.3.6.1.4.1.318.1.1.26.8.1.1.8ColumnrPDU2BankConfigBankPeakCurrentResetread-writemandatorySetting this OID to reset (2) will cause the existing peak current value to be replaced by the present load current value. Getting this OID will do nothing and…
1.3.6.1.4.1.318.1.1.26.8.2TablerPDU2BankPropertiesTablenot-accessiblemandatoryA table of Rack PDU bank properties
1.3.6.1.4.1.318.1.1.26.8.2.1RowrPDU2BankPropertiesEntrynot-accessiblemandatoryProperties of the currently queried Rack PDU bank
1.3.6.1.4.1.318.1.1.26.8.2.1.1ColumnrPDU2BankPropertiesIndexread-onlymandatoryThe index to the Rack PDU bank properties table entry
1.3.6.1.4.1.318.1.1.26.8.2.1.2ColumnrPDU2BankPropertiesModuleread-onlymandatoryThe user-defined Rack PDU numeric ID
1.3.6.1.4.1.318.1.1.26.8.2.1.3ColumnrPDU2BankPropertiesNumberread-onlymandatoryThe numeric bank ID
1.3.6.1.4.1.318.1.1.26.8.2.1.4ColumnrPDU2BankPropertiesPhaseLayoutread-onlymandatoryThis OID describes the outlet phase connections on the referenced bank as follows: seqPhase1ToNeutral(1) indicates that bank outlets are wired from Phase 1 to …
1.3.6.1.4.1.318.1.1.26.8.2.1.5ColumnrPDU2BankPropertiesBreakerRatingread-onlymandatoryIf bank circuit breakers are present on the device, this OID will return the rating of the breaker in Amps.
1.3.6.1.4.1.318.1.1.26.8.3TablerPDU2BankStatusTablenot-accessiblemandatoryA table of Rack PDU bank status data
1.3.6.1.4.1.318.1.1.26.8.3.1RowrPDU2BankStatusEntrynot-accessiblemandatoryStatus data from currently queried Rack PDU bank
1.3.6.1.4.1.318.1.1.26.8.3.1.1ColumnrPDU2BankStatusIndexread-onlymandatoryThe index to the Rack PDU bank status table entry
1.3.6.1.4.1.318.1.1.26.8.3.1.2ColumnrPDU2BankStatusModuleread-onlymandatoryThe user-defined Rack PDU numeric ID
1.3.6.1.4.1.318.1.1.26.8.3.1.3ColumnrPDU2BankStatusNumberread-onlymandatoryThe numeric bank ID
1.3.6.1.4.1.318.1.1.26.8.3.1.4ColumnrPDU2BankStatusLoadStateread-onlymandatoryIndicates the present load status of the Rack PDU bank being queried
1.3.6.1.4.1.318.1.1.26.8.3.1.5ColumnrPDU2BankStatusCurrentread-onlymandatoryIndicates the current draw, in tenths of Amps, of the load on the Rack PDU bank being queried
1.3.6.1.4.1.318.1.1.26.8.3.1.6ColumnrPDU2BankStatusPeakCurrentread-onlymandatoryThe peak current of the Rack PDU bank load in tenths of Amps
1.3.6.1.4.1.318.1.1.26.8.3.1.7ColumnrPDU2BankStatusPeakCurrentTimestampread-onlymandatoryIndicates the date and time the bank peak current occurred
1.3.6.1.4.1.318.1.1.26.8.3.1.8ColumnrPDU2BankStatusPeakCurrentStartTimeread-onlymandatoryIndicates the date and time of the last bank peak current reset
1.3.6.1.4.1.318.1.1.26.9NoderPDU2Outlet
1.3.6.1.4.1.318.1.1.26.9.1ScalarrPDU2OutletSwitchedTableSizeread-onlymandatoryThe number of switched outlets on connected Rack PDUs
1.3.6.1.4.1.318.1.1.26.9.2NoderPDU2OutletSwitched
1.3.6.1.4.1.318.1.1.26.9.2.1TablerPDU2OutletSwitchedConfigTablenot-accessiblemandatoryA table of Rack PDU switched outlet configuration data
1.3.6.1.4.1.318.1.1.26.9.2.1.1RowrPDU2OutletSwitchedConfigEntrynot-accessiblemandatoryConfiguration data from currently queried Rack PDU switched outlet
1.3.6.1.4.1.318.1.1.26.9.2.1.1.1ColumnrPDU2OutletSwitchedConfigIndexread-onlymandatoryThe index to the Rack PDU switched outlet configuration table entry
1.3.6.1.4.1.318.1.1.26.9.2.1.1.2ColumnrPDU2OutletSwitchedConfigModuleread-onlymandatoryThe user-defined Rack PDU numeric ID
1.3.6.1.4.1.318.1.1.26.9.2.1.1.3ColumnrPDU2OutletSwitchedConfigNameread-writemandatoryThe user-defined switched outlet ID string
1.3.6.1.4.1.318.1.1.26.9.2.1.1.4ColumnrPDU2OutletSwitchedConfigNumberread-onlymandatoryThe numeric switched outlet ID
1.3.6.1.4.1.318.1.1.26.9.2.1.1.5ColumnrPDU2OutletSwitchedConfigPowerOnTimeread-writemandatoryThe amount of delay, in seconds, between when power is provided to the Rack PDU and when this switched outlet starts providing power. Range -1...300 where -1 =…
1.3.6.1.4.1.318.1.1.26.9.2.1.1.6ColumnrPDU2OutletSwitchedConfigPowerOffTimeread-writemandatoryThe amount of time, in seconds, this outlet will delay powering off. Range -1...300 where -1 = Never power off, 0 = immediate power off, and 1-300 = seconds to…
1.3.6.1.4.1.318.1.1.26.9.2.1.1.7ColumnrPDU2OutletSwitchedConfigRebootDurationread-writemandatoryAfter turning power off during a reboot sequence, the amount of time to wait before turning power to this outlet back on. Range 5-60 seconds delay.
1.3.6.1.4.1.318.1.1.26.9.2.1.1.8ColumnrPDU2OutletSwitchedConfigExternalLinkread-writemandatoryUser-defined external device web link. Possible use cases could be the IP address of the external device plugged into the outlet or its manufacturer web page f…
1.3.6.1.4.1.318.1.1.26.9.2.2TablerPDU2OutletSwitchedPropertiesTablenot-accessiblemandatoryA table of Rack PDU switched outlet properties
1.3.6.1.4.1.318.1.1.26.9.2.2.1RowrPDU2OutletSwitchedPropertiesEntrynot-accessiblemandatoryProperties of the currently queried Rack PDU switched outlet
1.3.6.1.4.1.318.1.1.26.9.2.2.1.1ColumnrPDU2OutletSwitchedPropertiesIndexread-onlymandatoryThe index to the Rack PDU switched outlet properties table entry
1.3.6.1.4.1.318.1.1.26.9.2.2.1.2ColumnrPDU2OutletSwitchedPropertiesModuleread-onlymandatoryThe user-defined Rack PDU numeric ID
1.3.6.1.4.1.318.1.1.26.9.2.2.1.3ColumnrPDU2OutletSwitchedPropertiesNameread-onlymandatoryThe user-defined switched outlet ID string
1.3.6.1.4.1.318.1.1.26.9.2.2.1.4ColumnrPDU2OutletSwitchedPropertiesNumberread-onlymandatoryThe numeric switched outlet ID
1.3.6.1.4.1.318.1.1.26.9.2.2.1.5ColumnrPDU2OutletSwitchedPropertiesPhaseLayoutread-onlymandatoryThis OID describes the phase connections of the referenced outlet as follows: seqPhase1ToNeutral(1) indicates that the outlet is wired from Phase 1 to Neutral.…
1.3.6.1.4.1.318.1.1.26.9.2.2.1.6ColumnrPDU2OutletSwitchedPropertiesBankread-onlymandatoryThe numeric bank ID
1.3.6.1.4.1.318.1.1.26.9.2.3TablerPDU2OutletSwitchedStatusTablenot-accessiblemandatoryA table of Rack PDU switched outlet status information
1.3.6.1.4.1.318.1.1.26.9.2.3.1RowrPDU2OutletSwitchedStatusEntrynot-accessiblemandatoryStatus information for currently queried Rack PDU switched outlet
1.3.6.1.4.1.318.1.1.26.9.2.3.1.1ColumnrPDU2OutletSwitchedStatusIndexread-onlymandatoryThe index to the Rack PDU switched outlet status information table entry
1.3.6.1.4.1.318.1.1.26.9.2.3.1.2ColumnrPDU2OutletSwitchedStatusModuleread-onlymandatoryThe user-defined Rack PDU numeric ID
1.3.6.1.4.1.318.1.1.26.9.2.3.1.3ColumnrPDU2OutletSwitchedStatusNameread-onlymandatoryThe user-defined switched outlet ID string
1.3.6.1.4.1.318.1.1.26.9.2.3.1.4ColumnrPDU2OutletSwitchedStatusNumberread-onlymandatoryThe numeric switched outlet ID
1.3.6.1.4.1.318.1.1.26.9.2.3.1.5ColumnrPDU2OutletSwitchedStatusStateread-onlymandatoryIndicates the present switch state of the Rack PDU switched outlet being queried
1.3.6.1.4.1.318.1.1.26.9.2.3.1.6ColumnrPDU2OutletSwitchedStatusCommandPendingread-onlymandatoryIndicates whether or not the device is processing a command for this outlet. If the commandPendingUnknown (3) value is returned, all devices powered by the Rac…
1.3.6.1.4.1.318.1.1.26.9.2.3.1.7ColumnrPDU2OutletSwitchedStatusExternalLinkread-onlymandatoryEach RPDU outlet can have its own external web URL link. This can be configured in the rPDU2OutletSwitchedConfigExternalLink OID. When this link is clicked in …
1.3.6.1.4.1.318.1.1.26.9.2.4TablerPDU2OutletSwitchedControlTablenot-accessiblemandatoryA table of Rack PDU switched outlet control data
1.3.6.1.4.1.318.1.1.26.9.2.4.1RowrPDU2OutletSwitchedControlEntrynot-accessiblemandatoryControl data for currently queried Rack PDU switched outlet
1.3.6.1.4.1.318.1.1.26.9.2.4.1.1ColumnrPDU2OutletSwitchedControlIndexread-onlymandatoryThe index to the Rack PDU switched outlet control data table entry
1.3.6.1.4.1.318.1.1.26.9.2.4.1.2ColumnrPDU2OutletSwitchedControlModuleread-onlymandatoryThe user-defined Rack PDU numeric ID
1.3.6.1.4.1.318.1.1.26.9.2.4.1.3ColumnrPDU2OutletSwitchedControlNameread-onlymandatoryThe user-defined switched outlet ID string
1.3.6.1.4.1.318.1.1.26.9.2.4.1.4ColumnrPDU2OutletSwitchedControlNumberread-onlymandatoryThe numeric switched outlet ID
1.3.6.1.4.1.318.1.1.26.9.2.4.1.5ColumnrPDU2OutletSwitchedControlCommandread-writemandatoryGetting this variable will return the outlet state. If the outlet is on, the immediateOn (1) value will be returned. If the outlet is off, the immediateOff (2)…
1.3.6.1.4.1.318.1.1.26.9.3ScalarrPDU2OutletMeteredTableSizeread-onlymandatoryThe number of metered outlets on connect Rack PDUs
1.3.6.1.4.1.318.1.1.26.9.4NoderPDU2OutletMetered
1.3.6.1.4.1.318.1.1.26.9.4.1TablerPDU2OutletMeteredConfigTablenot-accessiblemandatoryA table of Rack PDU metered outlet configuration data
1.3.6.1.4.1.318.1.1.26.9.4.1.1RowrPDU2OutletMeteredConfigEntrynot-accessiblemandatoryConfiguration data from currently queried Rack PDU metered outlet
1.3.6.1.4.1.318.1.1.26.9.4.1.1.1ColumnrPDU2OutletMeteredConfigIndexread-onlymandatoryThe index to the Rack PDU metered outlet configuration table entry
1.3.6.1.4.1.318.1.1.26.9.4.1.1.2ColumnrPDU2OutletMeteredConfigModuleread-onlymandatoryThe user-defined Rack PDU numeric ID
1.3.6.1.4.1.318.1.1.26.9.4.1.1.3ColumnrPDU2OutletMeteredConfigNameread-writemandatoryThe user-defined metered outlet ID string
1.3.6.1.4.1.318.1.1.26.9.4.1.1.4ColumnrPDU2OutletMeteredConfigNumberread-onlymandatoryThe numeric switched outlet ID
1.3.6.1.4.1.318.1.1.26.9.4.1.1.5ColumnrPDU2OutletMeteredConfigLowLoadCurrentThresholdread-writemandatoryUser-defined low load outlet current threshold in Watts
1.3.6.1.4.1.318.1.1.26.9.4.1.1.6ColumnrPDU2OutletMeteredConfigNearOverloadCurrentThresholdread-writemandatoryUser-defined near outlet overload warning threshold in Watts
1.3.6.1.4.1.318.1.1.26.9.4.1.1.7ColumnrPDU2OutletMeteredConfigOverloadCurrentThresholdread-writemandatoryUser-defined outlet overload current threshold in Watts
1.3.6.1.4.1.318.1.1.26.9.4.1.1.8ColumnrPDU2OutletMeteredConfigExternalLinkread-writemandatoryUser-defined external device web link. Possible use cases could be the IP address of the external device plugged into the outlet or its manufacturer web page f…
1.3.6.1.4.1.318.1.1.26.9.4.2TablerPDU2OutletMeteredPropertiesTablenot-accessiblemandatoryA table of Rack PDU metered outlet properties
1.3.6.1.4.1.318.1.1.26.9.4.2.1RowrPDU2OutletMeteredPropertiesEntrynot-accessiblemandatoryProperties of currently queried Rack PDU metered outlet
1.3.6.1.4.1.318.1.1.26.9.4.2.1.1ColumnrPDU2OutletMeteredPropertiesIndexread-onlymandatoryThe index to the Rack PDU metered properties table entry
1.3.6.1.4.1.318.1.1.26.9.4.2.1.2ColumnrPDU2OutletMeteredPropertiesModuleread-onlymandatoryThe user-defined Rack PDU numeric ID
1.3.6.1.4.1.318.1.1.26.9.4.2.1.3ColumnrPDU2OutletMeteredPropertiesNameread-onlymandatoryThe user-defined metered outlet ID string
1.3.6.1.4.1.318.1.1.26.9.4.2.1.4ColumnrPDU2OutletMeteredPropertiesNumberread-onlymandatoryThe numeric metered outlet ID
1.3.6.1.4.1.318.1.1.26.9.4.2.1.5ColumnrPDU2OutletMeteredPropertiesLayoutread-onlymandatoryThis OID describes the phase connections of the referenced outlet as follows: seqPhase1ToNeutral(1) indicates that the outlet is wired from Phase 1 to Neutral.…
1.3.6.1.4.1.318.1.1.26.9.4.2.1.6ColumnrPDU2OutletMeteredPropertiesPowerRatingread-onlymandatoryMaximum power rating of Rack PDU metered outlet
1.3.6.1.4.1.318.1.1.26.9.4.2.1.7ColumnrPDU2OutletMeteredPropertiesBankread-onlymandatoryThis outlet's numeric bank ID
1.3.6.1.4.1.318.1.1.26.9.4.3TablerPDU2OutletMeteredStatusTablenot-accessiblemandatoryA table of Rack PDU metered outlet status data
1.3.6.1.4.1.318.1.1.26.9.4.3.1RowrPDU2OutletMeteredStatusEntrynot-accessiblemandatoryStatus data from currently queried Rack PDU metered outlet
1.3.6.1.4.1.318.1.1.26.9.4.3.1.1ColumnrPDU2OutletMeteredStatusIndexread-onlymandatoryThe index to the Rack PDU metered status table entry
1.3.6.1.4.1.318.1.1.26.9.4.3.1.2ColumnrPDU2OutletMeteredStatusModuleread-onlymandatoryThe user-defined Rack PDU numeric ID
1.3.6.1.4.1.318.1.1.26.9.4.3.1.3ColumnrPDU2OutletMeteredStatusNameread-onlymandatoryThe user-defined metered outlet ID string
1.3.6.1.4.1.318.1.1.26.9.4.3.1.4ColumnrPDU2OutletMeteredStatusNumberread-onlymandatoryThe numeric metered outlet ID
1.3.6.1.4.1.318.1.1.26.9.4.3.1.5ColumnrPDU2OutletMeteredStatusStateread-onlymandatoryIndicates the present load status of the Rack PDU metered outlet being queried
1.3.6.1.4.1.318.1.1.26.9.4.3.1.6ColumnrPDU2OutletMeteredStatusCurrentread-onlymandatoryIndicates the current draw, in tenths of Amps, of the load on the Rack PDU outlet being queried
1.3.6.1.4.1.318.1.1.26.9.4.3.1.7ColumnrPDU2OutletMeteredStatusPowerread-onlymandatoryIndicates the power draw of the load on the Rack PDU outlet being queried
1.3.6.1.4.1.318.1.1.26.9.4.3.1.8ColumnrPDU2OutletMeteredStatusPeakPowerread-onlymandatoryIndicates the peak power load draw on the Rack PDU outlet being queried
1.3.6.1.4.1.318.1.1.26.9.4.3.1.9ColumnrPDU2OutletMeteredStatusPeakPowerTimestampread-onlymandatoryIndicates the date and time that this metered outlet's peak power consumption occurred
1.3.6.1.4.1.318.1.1.26.9.4.3.1.10ColumnrPDU2OutletMeteredStatusPeakPowerStartTimeread-onlymandatoryIndicates the start date and time that this metered outlet began recording peak power observations
1.3.6.1.4.1.318.1.1.26.9.4.3.1.11ColumnrPDU2OutletMeteredStatusEnergyread-onlymandatoryA user resettable energy meter measuring Rack PDU load energy consumption in tenths of kilowatt-hours
1.3.6.1.4.1.318.1.1.26.9.4.3.1.12ColumnrPDU2OutletMeteredStatusReceptacleTyperead-onlymandatoryIndicates receptacle type for the outlet.
1.3.6.1.4.1.318.1.1.26.9.4.3.1.13ColumnrPDU2OutletMeteredStatusExternalLinkread-onlymandatoryEach RPDU outlet can have its own external web URL link. This can be configured in the rPDU2OutletMeteredConfigExternalLink OID. When this link is clicked in t…
1.3.6.1.4.1.318.1.1.26.10NoderPDU2Sensor
1.3.6.1.4.1.318.1.1.26.10.1ScalarrPDU2SensorTempHumidityTableSizeread-onlymandatoryThe number of connected temperature-humidity sensors
1.3.6.1.4.1.318.1.1.26.10.2NoderPDU2SensorTempHumidity
1.3.6.1.4.1.318.1.1.26.10.2.1TablerPDU2SensorTempHumidityConfigTablenot-accessiblemandatoryA table of temperature-humidity sensor configuration data
1.3.6.1.4.1.318.1.1.26.10.2.1.1RowrPDU2SensorTempHumidityConfigEntrynot-accessiblemandatoryConfiguration data from temperature-humidity sensor being queried
1.3.6.1.4.1.318.1.1.26.10.2.1.1.1ColumnrPDU2SensorTempHumidityConfigIndexread-onlymandatoryThe index to the temperature-humidity sensor configuration data table entry
1.3.6.1.4.1.318.1.1.26.10.2.1.1.2ColumnrPDU2SensorTempHumidityConfigModuleread-onlymandatoryThe user-defined Rack PDU numeric ID
1.3.6.1.4.1.318.1.1.26.10.2.1.1.3ColumnrPDU2SensorTempHumidityConfigNameread-writemandatoryThe user-defined temperature-humidity sensor ID string
1.3.6.1.4.1.318.1.1.26.10.2.1.1.4ColumnrPDU2SensorTempHumidityConfigNumberread-onlymandatoryThe temperature-humidity sensor numeric ID
1.3.6.1.4.1.318.1.1.26.10.2.1.1.5ColumnrPDU2SensorTempHumidityConfigTemperatureAlarmEnableread-writemandatorySetting this OID enables or disables generation of sensor temperature alarm. Getting this OID returns the current value of the temperature alarm enable.
1.3.6.1.4.1.318.1.1.26.10.2.1.1.6ColumnrPDU2SensorTempHumidityConfigHumidityAlarmEnableread-writemandatorySetting this OID enables or disables generation of sensor humidity alarm. Getting this OID returns the current value of the humidity alarm enable.
1.3.6.1.4.1.318.1.1.26.10.2.1.1.7ColumnrPDU2SensorTempHumidityConfigTempMaxThreshFread-writemandatorySensor maximum temperature alarm threshold in Fahrenheit. Attempting to set this OID to a value less than or equal to that of rPDU2SensorTempHumidityConfigTemp…
1.3.6.1.4.1.318.1.1.26.10.2.1.1.8ColumnrPDU2SensorTempHumidityConfigTempHighThreshFread-writemandatorySensor high temperature warning alarm threshold in Fahrenheit. Attempting to set this OID to a value greater than or equal to that of rPDU2SensorTempHumidityCo…
1.3.6.1.4.1.318.1.1.26.10.2.1.1.9ColumnrPDU2SensorTempHumidityConfigTempHysteresisFread-writemandatorySensor temperature hysteresis setting in Fahrenheit
1.3.6.1.4.1.318.1.1.26.10.2.1.1.10ColumnrPDU2SensorTempHumidityConfigTempMaxThreshCread-writemandatorySensor maximum temperature alarm threshold in Celsius. Attempting to set this OID to a value less than or equal to that of rPDU2SensorTempHumidityConfigTempHig…
1.3.6.1.4.1.318.1.1.26.10.2.1.1.11ColumnrPDU2SensorTempHumidityConfigTempHighThreshCread-writemandatorySensor high temperature warning alarm threshold in Celsius. Attempting to set this OID to a value greater than or equal to that of rPDU2SensorTempHumidityConfi…
1.3.6.1.4.1.318.1.1.26.10.2.1.1.12ColumnrPDU2SensorTempHumidityConfigTempHysteresisCread-writemandatorySensor temperature hysteresis setting in Celsius
1.3.6.1.4.1.318.1.1.26.10.2.1.1.13ColumnrPDU2SensorTempHumidityConfigHumidityLowThreshread-writemandatorySensor low humidity warning alarm threshold in percent relative humidity. Attempting to set this OID to a value less than or equal to that of rPDU2SensorTempHu…
1.3.6.1.4.1.318.1.1.26.10.2.1.1.14ColumnrPDU2SensorTempHumidityConfigHumidityMinThreshread-writemandatorySensor minimum humidity alarm threshold in percent relative humidity. Attempting to set this OID to a value greater than or equal to that of rPDU2SensorTempHum…
1.3.6.1.4.1.318.1.1.26.10.2.1.1.15ColumnrPDU2SensorTempHumidityConfigHumidityHysteresisread-writemandatorySensor humidity hysteresis setting in percent relative humidity
1.3.6.1.4.1.318.1.1.26.10.2.1.1.16ColumnrPDU2SensorTempHumidityConfigTempPeakResetread-writemandatorySetting this OID to reset (2) will cause the existing peak temperature to be replaced by the present temperature reading. Getting this OID will do nothing and …
1.3.6.1.4.1.318.1.1.26.10.2.2TablerPDU2SensorTempHumidityStatusTablenot-accessiblemandatoryA table of temperature-humidity sensor status data
1.3.6.1.4.1.318.1.1.26.10.2.2.1RowrPDU2SensorTempHumidityStatusEntrynot-accessiblemandatoryStatus information from temperature-humidity sensor being queried
1.3.6.1.4.1.318.1.1.26.10.2.2.1.1ColumnrPDU2SensorTempHumidityStatusIndexread-onlymandatoryThe index to the temperature-humidity status data table entry
1.3.6.1.4.1.318.1.1.26.10.2.2.1.2ColumnrPDU2SensorTempHumidityStatusModuleread-onlymandatoryThe user-defined Rack PDU numeric ID
1.3.6.1.4.1.318.1.1.26.10.2.2.1.3ColumnrPDU2SensorTempHumidityStatusNameread-onlymandatoryThe user-defined temperature-humidity sensor ID string
1.3.6.1.4.1.318.1.1.26.10.2.2.1.4ColumnrPDU2SensorTempHumidityStatusNumberread-onlymandatoryThe temperature-humidity sensor numeric ID
1.3.6.1.4.1.318.1.1.26.10.2.2.1.5ColumnrPDU2SensorTempHumidityStatusTyperead-onlymandatoryThe type of the sensor
1.3.6.1.4.1.318.1.1.26.10.2.2.1.6ColumnrPDU2SensorTempHumidityStatusCommStatusread-onlymandatoryThe communications status of the sensor
1.3.6.1.4.1.318.1.1.26.10.2.2.1.7ColumnrPDU2SensorTempHumidityStatusTempFread-onlymandatorySensor temperature reading in tenths of degrees Fahrenheit
1.3.6.1.4.1.318.1.1.26.10.2.2.1.8ColumnrPDU2SensorTempHumidityStatusTempCread-onlymandatorySensor temperature reading in tenths of degrees Celsius
1.3.6.1.4.1.318.1.1.26.10.2.2.1.9ColumnrPDU2SensorTempHumidityStatusTempStatusread-onlymandatoryThis OID reports the current state of the temperature probe. A notPresent (1) response indicates that no probe is attached. A belowMin (2) response indicates t…
1.3.6.1.4.1.318.1.1.26.10.2.2.1.10ColumnrPDU2SensorTempHumidityStatusRelativeHumidityread-onlymandatorySensor humidity reading in percent relative humidity
1.3.6.1.4.1.318.1.1.26.10.2.2.1.11ColumnrPDU2SensorTempHumidityStatusHumidityStatusread-onlymandatoryThis OID reports the current state of the humidity probe. A notPresent (1) response indicates that no probe is attached. A belowMin (2) response indicates that…
1.3.6.1.4.1.318.1.1.26.10.2.2.1.12ColumnrPDU2SensorTempHumidityStatusTempPeakFread-onlymandatorySensor peak temperature in tenths of degrees Fahrenheit
1.3.6.1.4.1.318.1.1.26.10.2.2.1.13ColumnrPDU2SensorTempHumidityStatusTempPeakCread-onlymandatorySensor peak temperature in tenths of degrees Celsius
1.3.6.1.4.1.318.1.1.26.10.2.2.1.14ColumnrPDU2SensorTempHumidityStatusTempPeakTimestampread-onlymandatoryIndicates the date and time that the peak temperature occurred
1.3.6.1.4.1.318.1.1.26.10.2.2.1.15ColumnrPDU2SensorTempHumidityStatusTempPeakStartTimeread-onlymandatoryIndicates the date and time of the last temperature peak reset
1.3.6.1.4.1.318.1.1.26.10.3ScalarrPDU2SensorDiscreteTableSizeread-onlymandatoryThe number of connected discrete sensors
1.3.6.1.4.1.318.1.1.26.10.4NoderPDU2SensorDiscrete
1.3.6.1.4.1.318.1.1.26.10.4.1TablerPDU2SensorDiscreteConfigTablenot-accessiblemandatoryA table of discrete sensor configuration data
1.3.6.1.4.1.318.1.1.26.10.4.1.1RowrPDU2SensorDiscreteConfigEntrynot-accessiblemandatoryConfiguration data from discreste sensor being queried
1.3.6.1.4.1.318.1.1.26.10.4.1.1.1ColumnrPDU2SensorDiscreteConfigIndexread-onlymandatoryThe index to the discrete sensor configuration data table entry
1.3.6.1.4.1.318.1.1.26.10.4.1.1.2ColumnrPDU2SensorDiscreteConfigModuleread-onlymandatoryThe user-defined Rack PDU numeric ID
1.3.6.1.4.1.318.1.1.26.10.4.1.1.3ColumnrPDU2SensorDiscreteConfigNameread-writemandatoryThe user-defined discrete sensor ID string
1.3.6.1.4.1.318.1.1.26.10.4.1.1.4ColumnrPDU2SensorDiscreteConfigNumberread-onlymandatoryThe discrete sensor numeric ID
1.3.6.1.4.1.318.1.1.26.10.4.1.1.5ColumnrPDU2SensorDiscreteConfigNormalStateread-writemandatoryIndicates the normal state of the discrete input contact
1.3.6.1.4.1.318.1.1.26.10.4.1.1.6ColumnrPDU2SensorDiscreteConfigAbnormalSeverityread-writemandatoryIndicates the severity of alarm triggered by abnormal discrete input contact state
1.3.6.1.4.1.318.1.1.26.10.4.2TablerPDU2SensorDiscreteStatusTablenot-accessiblemandatoryA table of discrete sensor status data
1.3.6.1.4.1.318.1.1.26.10.4.2.1RowrPDU2SensorDiscreteStatusEntrynot-accessiblemandatoryStatus information from discrete sensor being queried
1.3.6.1.4.1.318.1.1.26.10.4.2.1.1ColumnrPDU2SensorDiscreteStatusIndexread-onlymandatoryThe index to the discrete sensor status data table entry
1.3.6.1.4.1.318.1.1.26.10.4.2.1.2ColumnrPDU2SensorDiscreteStatusModuleread-onlymandatoryThe user-defined Rack PDU numeric ID
1.3.6.1.4.1.318.1.1.26.10.4.2.1.3ColumnrPDU2SensorDiscreteStatusNameread-onlymandatoryThe user-defined discrete sensor ID string
1.3.6.1.4.1.318.1.1.26.10.4.2.1.4ColumnrPDU2SensorDiscreteStatusNumberread-onlymandatoryThe discrete sensor numeric ID
1.3.6.1.4.1.318.1.1.26.10.4.2.1.5ColumnrPDU2SensorDiscreteStatusTyperead-onlymandatoryThe type of discrete sensor currently being queried
1.3.6.1.4.1.318.1.1.26.10.4.2.1.6ColumnrPDU2SensorDiscreteStatusCommStatusread-onlymandatoryThe communications status of the sensor
1.3.6.1.4.1.318.1.1.26.10.4.2.1.7ColumnrPDU2SensorDiscreteStatusCurrentStateread-onlymandatoryThe current open/close state of the discrete sensor
1.3.6.1.4.1.318.1.1.26.10.4.2.1.8ColumnrPDU2SensorDiscreteStatusAlarmStateread-onlymandatoryIndicates alarm status of discrete sensor input
1.3.6.1.4.1.318.1.1.26.11NoderPDU2Group
1.3.6.1.4.1.318.1.1.26.11.1ScalarrPDU2GroupNumberOfDevicesread-onlymandatoryGetting this OID will return the number of Rack PDU devices contributing to the Network Port Sharing (NPS) group power and energy values. Queries to guest unit…
1.3.6.1.4.1.318.1.1.26.11.2ScalarrPDU2GroupTotalPowerread-onlymandatoryGetting this OID will return the total power consumption of the Rack PDU Network Port Sharing (NPS) group devices in hundredths of kilowatts. Queries to guest …
1.3.6.1.4.1.318.1.1.26.11.3ScalarrPDU2GroupTotalEnergyread-onlymandatoryGetting this OID will return the total energy consumption of the Rack PDU Network Port Sharing (NPS) group devices in tenths of kilowatt-hours. To reset the en…
1.3.6.1.4.1.318.1.1.26.11.4ScalarrPDU2GroupEnergyResetread-writemandatorySetting this OID to reset (2) will cause the device energy meter value on each device in the Rack PDU Network Port Sharing (NPS) group to be reset to zero. Eac…
1.3.6.1.4.1.318.1.1.26.12ScalarrPDU2PhaseToPhaseStatusTableSizeread-onlymandatoryThe number of connected Rack PDU banks
1.3.6.1.4.1.318.1.1.26.13NoderPDU2PhaseToPhase
1.3.6.1.4.1.318.1.1.26.13.1TablerPDU2PhaseToPhaseStatusTablenot-accessiblemandatoryA table of Rack PDU phase to phase status data. This table is only applicable to SKUs that have phase to phase outputs.
1.3.6.1.4.1.318.1.1.26.13.1.1RowrPDU2PhaseToPhaseStatusEntrynot-accessiblemandatoryStatus data from currently queried Rack PDU phase to phase outputs
1.3.6.1.4.1.318.1.1.26.13.1.1.1ColumnrPDU2PhaseToPhaseStatusIndexread-onlymandatoryThe index to the Rack PDU phase to phase status table entry
1.3.6.1.4.1.318.1.1.26.13.1.1.2ColumnrPDU2PhaseToPhaseStatusModuleread-onlymandatoryThe user-defined Rack PDU numeric ID
1.3.6.1.4.1.318.1.1.26.13.1.1.3ColumnrPDU2PhaseToPhaseStatusVoltage1to2read-onlymandatoryIndicates the Voltage, in Volts, of the Rack PDU phase 1 to phase 2 output being queried
1.3.6.1.4.1.318.1.1.26.13.1.1.4ColumnrPDU2PhaseToPhaseStatusVoltage2to3read-onlymandatoryIndicates the Voltage, in Volts, of the Rack PDU phase 2 to phase 3 output being queried
1.3.6.1.4.1.318.1.1.26.13.1.1.5ColumnrPDU2PhaseToPhaseStatusVoltage3to1read-onlymandatoryIndicates the Voltage, in Volts, of the Rack PDU phase 3 to phase 2 output being queried
1.3.6.1.4.1.318.1.1.27Nodecooling
1.3.6.1.4.1.318.1.1.27.1NodecoolingUnit
1.3.6.1.4.1.318.1.1.27.1.1ScalarcoolingUnitTableSizeread-onlymandatoryThe number of cooling units accessible via this agent.
1.3.6.1.4.1.318.1.1.27.1.2TablecoolingUnitTablenot-accessiblemandatoryA table of cooling unit level data.
1.3.6.1.4.1.318.1.1.27.1.2.1RowcoolingUnitEntrynot-accessiblemandatoryAn element of coolingUnitTable.
1.3.6.1.4.1.318.1.1.27.1.2.1.1ColumncoolingUnitTableIndexnot-accessiblemandatoryThe unit reference identifier for this table and all other table entries subordinate to coolingUnits.
1.3.6.1.4.1.318.1.1.27.1.3NodecoolingUnitAbout
1.3.6.1.4.1.318.1.1.27.1.3.1ScalarcoolingUnitAboutTableSizeread-onlymandatoryThe potential number of entries available in coolingUnitAboutTable.
1.3.6.1.4.1.318.1.1.27.1.3.2TablecoolingUnitAboutTablenot-accessiblemandatoryA table of unit reference information.
1.3.6.1.4.1.318.1.1.27.1.3.2.1RowcoolingUnitAboutEntrynot-accessiblemandatoryAn element of coolingUnitAboutTable.
1.3.6.1.4.1.318.1.1.27.1.3.2.1.1ColumncoolingUnitAboutTableIndexnot-accessiblemandatoryThe static reference identifier for each table entry.
1.3.6.1.4.1.318.1.1.27.1.3.2.1.2ColumncoolingUnitAboutDescriptionread-onlymandatoryA text description of the information presented in coolingUnitAboutValue.
1.3.6.1.4.1.318.1.1.27.1.3.2.1.3ColumncoolingUnitAboutValueread-onlymandatoryThe actual value of the current table entry.
1.3.6.1.4.1.318.1.1.27.1.4NodecoolingUnitStatus
1.3.6.1.4.1.318.1.1.27.1.4.1NodecoolingUnitStatusAnalog
1.3.6.1.4.1.318.1.1.27.1.4.1.1ScalarcoolingUnitStatusAnalogTableSizeread-onlymandatoryThe potential number of entries available in coolingUnitStatusAnalogTable.
1.3.6.1.4.1.318.1.1.27.1.4.1.2TablecoolingUnitStatusAnalogTablenot-accessiblemandatoryA table of analog unit status data.
1.3.6.1.4.1.318.1.1.27.1.4.1.2.1RowcoolingUnitStatusAnalogEntrynot-accessiblemandatoryAn element of coolingUnitStatusAnalogTable.
1.3.6.1.4.1.318.1.1.27.1.4.1.2.1.1ColumncoolingUnitStatusAnalogTableIndexnot-accessiblemandatoryThe static reference identifier for each table entry.
1.3.6.1.4.1.318.1.1.27.1.4.1.2.1.2ColumncoolingUnitStatusAnalogDescriptionread-onlymandatoryA text description of the information presented in coolingUnitStatusAnalogValue.
1.3.6.1.4.1.318.1.1.27.1.4.1.2.1.3ColumncoolingUnitStatusAnalogValueread-onlymandatoryThe scaled value of the current table entry (multiplied by coolingUnitStatusAnalogScale for integer presentation).
1.3.6.1.4.1.318.1.1.27.1.4.1.2.1.4ColumncoolingUnitStatusAnalogUnitsread-onlymandatoryThe unit of measure by which coolingUnitStatusAnalogValue is expressed.
1.3.6.1.4.1.318.1.1.27.1.4.1.2.1.5ColumncoolingUnitStatusAnalogScaleread-onlymandatoryThe factor by which coolingUnitStatusAnalogValue is expressed.
1.3.6.1.4.1.318.1.1.27.1.4.2NodecoolingUnitStatusDiscrete
1.3.6.1.4.1.318.1.1.27.1.4.2.1ScalarcoolingUnitStatusDiscreteTableSizeread-onlymandatoryThe potential number of entries available in coolingUnitStatusDiscreteTable.
1.3.6.1.4.1.318.1.1.27.1.4.2.2TablecoolingUnitStatusDiscreteTablenot-accessiblemandatoryA table of discrete unit status data.
1.3.6.1.4.1.318.1.1.27.1.4.2.2.1RowcoolingUnitStatusDiscreteEntrynot-accessiblemandatoryAn element of coolingUnitStatusDiscreteTable.
1.3.6.1.4.1.318.1.1.27.1.4.2.2.1.1ColumncoolingUnitStatusDiscreteTableIndexnot-accessiblemandatoryThe static reference identifier for each table entry.
1.3.6.1.4.1.318.1.1.27.1.4.2.2.1.2ColumncoolingUnitStatusDiscreteDescriptionread-onlymandatoryA text description of the information presented in this table's 'value' OIDs.
1.3.6.1.4.1.318.1.1.27.1.4.2.2.1.3ColumncoolingUnitStatusDiscreteValueAsStringread-onlymandatoryThe actual value of the current table entry expressed as a string.
1.3.6.1.4.1.318.1.1.27.1.4.2.2.1.4ColumncoolingUnitStatusDiscreteValueAsIntegerread-onlymandatoryThe actual value of the current table entry expressed as an integer value.
1.3.6.1.4.1.318.1.1.27.1.4.2.2.1.5ColumncoolingUnitStatusDiscreteIntegerReferenceKeyread-onlymandatoryA complete listing of all possible coolingUnitStatusDiscreteValueAsInteger values paired with their identifying strings.
1.3.6.1.4.1.318.1.1.27.1.5NodecoolingUnitConfiguration
1.3.6.1.4.1.318.1.1.27.1.5.1NodecoolingUnitConfigurationAnalog
1.3.6.1.4.1.318.1.1.27.1.5.1.1ScalarcoolingUnitConfigurationAnalogTableSizeread-onlymandatoryThe potential number of entries available in coolingUnitConfigurationAnalogTable.
1.3.6.1.4.1.318.1.1.27.1.5.1.2TablecoolingUnitConfigurationAnalogTablenot-accessiblemandatoryA table of analog unit configuration data.
1.3.6.1.4.1.318.1.1.27.1.5.1.2.1RowcoolingUnitConfigurationAnalogEntrynot-accessiblemandatoryAn element of coolingUnitConfigurationAnalogTable.
1.3.6.1.4.1.318.1.1.27.1.5.1.2.1.1ColumncoolingUnitConfigurationAnalogTableIndexnot-accessiblemandatoryThe static reference identifier for each table entry.
1.3.6.1.4.1.318.1.1.27.1.5.1.2.1.2ColumncoolingUnitConfigurationAnalogDescriptionread-onlymandatoryA text description of the information presented in coolingUnitConfigurationAnalogValue.
1.3.6.1.4.1.318.1.1.27.1.5.1.2.1.3ColumncoolingUnitConfigurationAnalogValueread-writemandatoryThe scaled value of the current table entry (multiplied by coolingUnitConfigurationAnalogScale for integer presentation).
1.3.6.1.4.1.318.1.1.27.1.5.1.2.1.4ColumncoolingUnitConfigurationAnalogUnitsread-onlymandatoryThe unit of measure by which coolingUnitConfigurationAnalogValue is expressed.
1.3.6.1.4.1.318.1.1.27.1.5.1.2.1.5ColumncoolingUnitConfigurationAnalogScaleread-onlymandatoryThe factor by which coolingUnitConfigurationAnalogValue is expressed.
1.3.6.1.4.1.318.1.1.27.1.5.1.2.1.6ColumncoolingUnitConfigurationAnalogAccessread-onlymandatoryA description of available access to coolingUnitConfigurationAnalogValue via SNMP client.
1.3.6.1.4.1.318.1.1.27.1.5.1.2.1.7ColumncoolingUnitConfigurationAnalogMinimumread-onlymandatoryThe minimum possible value of coolingUnitConfigurationAnalogValue.
1.3.6.1.4.1.318.1.1.27.1.5.1.2.1.8ColumncoolingUnitConfigurationAnalogMaximumread-onlymandatoryThe maximum possible value of coolingUnitConfigurationAnalogValue.
1.3.6.1.4.1.318.1.1.27.1.5.2NodecoolingUnitConfigurationDiscrete
1.3.6.1.4.1.318.1.1.27.1.5.2.1ScalarcoolingUnitConfigurationDiscreteTableSizeread-onlymandatoryThe potential number of entries available in coolingUnitConfigurationDiscreteTable.
1.3.6.1.4.1.318.1.1.27.1.5.2.2TablecoolingUnitConfigurationDiscreteTablenot-accessiblemandatoryA table of discrete unit configuration data.
1.3.6.1.4.1.318.1.1.27.1.5.2.2.1RowcoolingUnitConfigurationDiscreteEntrynot-accessiblemandatoryAn element of coolingUnitConfigurationDiscreteTable.
1.3.6.1.4.1.318.1.1.27.1.5.2.2.1.1ColumncoolingUnitConfigurationDiscreteTableIndexnot-accessiblemandatoryThe static reference identifier for each table entry.
1.3.6.1.4.1.318.1.1.27.1.5.2.2.1.2ColumncoolingUnitConfigurationDiscreteDescriptionread-onlymandatoryA text description of the information presented in this table's 'value' OIDs.
1.3.6.1.4.1.318.1.1.27.1.5.2.2.1.3ColumncoolingUnitConfigurationDiscreteValueAsStringread-onlymandatoryThe actual value of the current table entry expressed as a string.
1.3.6.1.4.1.318.1.1.27.1.5.2.2.1.4ColumncoolingUnitConfigurationDiscreteValueAsIntegerread-writemandatoryThe actual value of the current table entry expressed as an integer value.
1.3.6.1.4.1.318.1.1.27.1.5.2.2.1.5ColumncoolingUnitConfigurationDiscreteIntegerReferenceKeyread-onlymandatoryA complete listing of all possible coolingUnitConfigurationDiscreteValueAsInteger values paired with their identifying strings.
1.3.6.1.4.1.318.1.1.27.1.5.2.2.1.6ColumncoolingUnitConfigurationDiscreteAccessread-onlymandatoryA description of available access to coolingUnitConfigurationDiscreteValueAsInteger via SNMP client.
1.3.6.1.4.1.318.1.1.27.1.5.3NodecoolingUnitConfigurationString
1.3.6.1.4.1.318.1.1.27.1.5.3.1ScalarcoolingUnitConfigurationStringTableSizeread-onlymandatoryThe potential number of entries available in coolingUnitConfigurationStringTable.
1.3.6.1.4.1.318.1.1.27.1.5.3.2TablecoolingUnitConfigurationStringTablenot-accessiblemandatoryA table of unit configuration strings.
1.3.6.1.4.1.318.1.1.27.1.5.3.2.1RowcoolingUnitConfigurationStringEntrynot-accessiblemandatoryAn element of coolingUnitConfigurationStringTable.
1.3.6.1.4.1.318.1.1.27.1.5.3.2.1.1ColumncoolingUnitConfigurationStringTableIndexnot-accessiblemandatoryThe static reference identifier for each table entry.
1.3.6.1.4.1.318.1.1.27.1.5.3.2.1.2ColumncoolingUnitConfigurationStringDescriptionread-onlymandatoryA text description of the information presented in coolingUnitConfigurationStringValue.
1.3.6.1.4.1.318.1.1.27.1.5.3.2.1.3ColumncoolingUnitConfigurationStringValueread-writemandatoryThe actual value of the current table entry.
1.3.6.1.4.1.318.1.1.27.1.5.3.2.1.4ColumncoolingUnitConfigurationStringMaxLengthread-onlymandatoryThe maximum string length supported by coolingUnitConfigurationStringValue.
1.3.6.1.4.1.318.1.1.27.1.5.3.2.1.5ColumncoolingUnitConfigurationStringAccessread-onlymandatoryA description of available access to coolingUnitConfigurationStringValue via SNMP client.
1.3.6.1.4.1.318.1.1.27.1.6NodecoolingUnitExtended
1.3.6.1.4.1.318.1.1.27.1.6.1NodecoolingUnitExtendedAnalog
1.3.6.1.4.1.318.1.1.27.1.6.1.1ScalarcoolingUnitExtendedAnalogTableSizeread-onlymandatoryThe potential number of entries available in coolingUnitExtendedAnalogTable.
1.3.6.1.4.1.318.1.1.27.1.6.1.2TablecoolingUnitExtendedAnalogTablenot-accessiblemandatoryA table of secondary analog data for the cooling unit or one of its components.
1.3.6.1.4.1.318.1.1.27.1.6.1.2.1RowcoolingUnitExtendedAnalogEntrynot-accessiblemandatoryAn element of coolingUnitExtendedAnalogTable.
1.3.6.1.4.1.318.1.1.27.1.6.1.2.1.1ColumncoolingUnitExtendedAnalogTableIndexnot-accessiblemandatoryThe static reference identifier for each table entry. This identifier may reference different table entries in different unit models.
1.3.6.1.4.1.318.1.1.27.1.6.1.2.1.2ColumncoolingUnitExtendedAnalogDescriptionread-onlymandatoryA text description of the information presented in coolingUnitExtendedAnalogValue.
1.3.6.1.4.1.318.1.1.27.1.6.1.2.1.3ColumncoolingUnitExtendedAnalogValueread-onlymandatoryThe scaled value of the current table entry (multiplied by coolingUnitExtendedAnalogScale for integer presentation).
1.3.6.1.4.1.318.1.1.27.1.6.1.2.1.4ColumncoolingUnitExtendedAnalogUnitsread-onlymandatoryThe unit of measure by which coolingUnitExtendedAnalogValue is expressed.
1.3.6.1.4.1.318.1.1.27.1.6.1.2.1.5ColumncoolingUnitExtendedAnalogScaleread-onlymandatoryThe factor by which coolingUnitExtendedAnalogValue is expressed.
1.3.6.1.4.1.318.1.1.27.1.6.2NodecoolingUnitExtendedDiscrete
1.3.6.1.4.1.318.1.1.27.1.6.2.1ScalarcoolingUnitExtendedDiscreteTableSizeread-onlymandatoryThe potential number of entries available in coolingUnitExtendedDiscreteTable.
1.3.6.1.4.1.318.1.1.27.1.6.2.2TablecoolingUnitExtendedDiscreteTablenot-accessiblemandatoryA table of secondary discrete cooling unit data.
1.3.6.1.4.1.318.1.1.27.1.6.2.2.1RowcoolingUnitExtendedDiscreteEntrynot-accessiblemandatoryAn element of coolingUnitExtendedDiscreteTable.
1.3.6.1.4.1.318.1.1.27.1.6.2.2.1.1ColumncoolingUnitExtendedDiscreteTableIndexnot-accessiblemandatoryThe static reference identifier for each table entry. This identifier may reference different table entries in different unit models.
1.3.6.1.4.1.318.1.1.27.1.6.2.2.1.2ColumncoolingUnitExtendedDiscreteDescriptionread-onlymandatoryA text description of the information presented in this table's 'value' OIDs.
1.3.6.1.4.1.318.1.1.27.1.6.2.2.1.3ColumncoolingUnitExtendedDiscreteValueAsStringread-onlymandatoryThe actual value of the current table entry expressed as a string.
1.3.6.1.4.1.318.1.1.27.1.6.2.2.1.4ColumncoolingUnitExtendedDiscreteValueAsIntegerread-onlymandatoryThe actual value of the current table entry expressed as an integer value.
1.3.6.1.4.1.318.1.1.27.1.6.2.2.1.5ColumncoolingUnitExtendedDiscreteIntegerReferenceKeyread-onlymandatoryA complete listing of all possible coolingUnitExtendedDiscreteValueAsInteger values paired with their identifying strings.
1.3.6.1.4.1.318.1.1.27.1.6.3NodecoolingUnitExtendedString
1.3.6.1.4.1.318.1.1.27.1.6.3.1ScalarcoolingUnitExtendedStringTableSizeread-onlymandatoryThe potential number of entries available in coolingUnitExtendedStringTable.
1.3.6.1.4.1.318.1.1.27.1.6.3.2TablecoolingUnitExtendedStringTablenot-accessiblemandatoryA table of secondary unit reference data.
1.3.6.1.4.1.318.1.1.27.1.6.3.2.1RowcoolingUnitExtendedStringEntrynot-accessiblemandatoryAn element of coolingUnitExtendedStringTable.
1.3.6.1.4.1.318.1.1.27.1.6.3.2.1.1ColumncoolingUnitExtendedStringTableIndexnot-accessiblemandatoryThe static reference identifier for each table entry. This identifier may reference different table entries in different unit models.
1.3.6.1.4.1.318.1.1.27.1.6.3.2.1.2ColumncoolingUnitExtendedStringDescriptionread-onlymandatoryA text description of the information presented in coolingUnitExtendedStringValue.
1.3.6.1.4.1.318.1.1.27.1.6.3.2.1.3ColumncoolingUnitExtendedStringValueread-onlymandatoryThe actual value of the current table entry.
1.3.6.1.4.1.318.1.1.28NodepowerManagementModule
1.3.6.1.4.1.318.1.1.28.1NodepmmIdent
1.3.6.1.4.1.318.1.1.28.1.1ScalarpmmIdentModelNumberread-onlymandatoryA character string identifying the model number of the PMM. This value is set at the factory.
1.3.6.1.4.1.318.1.1.28.1.2ScalarpmmIdentSerialNumberread-onlymandatoryA character string identifying the serial number of the PMM. This value is set at the factory.
1.3.6.1.4.1.318.1.1.28.1.3ScalarpmmIdentDateOfManufactureread-onlymandatoryThe date when the PMM was manufactured in mm/dd/yyyy format. This value is set at the factory.
1.3.6.1.4.1.318.1.1.28.1.4ScalarpmmIdentHMISerialNumberread-onlymandatoryA character string identifying the serial number of the HMI. This value is set at the factory.
1.3.6.1.4.1.318.1.1.28.1.5ScalarpmmIdentHMIHardwareRevread-onlymandatoryThe hardware revision of the HMI. This value is set at the factory.
1.3.6.1.4.1.318.1.1.28.1.6ScalarpmmIdentHMIFirmwareAppRevread-onlymandatoryAn ID string identifying the application firmware revision of the HMI.
1.3.6.1.4.1.318.1.1.28.1.7ScalarpmmIdentHMIFirmwareAppOSRevread-onlymandatoryAn ID string identifying the application operating system firmware revision of the HMI.
1.3.6.1.4.1.318.1.1.28.2NodepmmDevice
1.3.6.1.4.1.318.1.1.28.2.1ScalarpmmDeviceNominalInputVoltageread-onlymandatoryThe nominal input voltage to the PMM. Measured in Volts, line-to-line for a 3-wire (delta) service or line-to-neutral for a 4-wire (wye) service.
1.3.6.1.4.1.318.1.1.28.2.2ScalarpmmDeviceServiceTyperead-onlymandatoryThe type of utility input to the PMM. Either 3 wires (delta), or 4 wires (wye).
1.3.6.1.4.1.318.1.1.28.2.3ScalarpmmDeviceNominalOutputVoltageread-onlymandatoryThe nominal line-to-neutral output voltage to the load measured in Volts.
1.3.6.1.4.1.318.1.1.28.3NodepmmMonitoring
1.3.6.1.4.1.318.1.1.28.3.1NodepmmInput
1.3.6.1.4.1.318.1.1.28.3.1.1ScalarpmmInputMeterTableSizeread-onlymandatoryThe number of input meters attached to the system.
1.3.6.1.4.1.318.1.1.28.3.1.2TablepmmInputTablenot-accessiblemandatoryA list of input meter entries.
1.3.6.1.4.1.318.1.1.28.3.1.2.1RowpmmInputEntrynot-accessiblemandatoryAn entry containing information applicable to a particular input meter.
1.3.6.1.4.1.318.1.1.28.3.1.2.1.1ColumnpmmInputMeterIndexread-onlymandatoryThe input meter identifier.
1.3.6.1.4.1.318.1.1.28.3.1.2.1.2ColumnpmmInputFrequencyread-onlymandatoryThe input frequency in tenths of Hertz.
1.3.6.1.4.1.318.1.1.28.3.1.2.1.3ColumnpmmInputTotalActivePowerread-onlymandatoryShows the total input active power in tenths of kW.
1.3.6.1.4.1.318.1.1.28.3.1.2.1.4ColumnpmmInputTotalApparentPowerread-onlymandatoryShows the total input apparent power in tenths of kVA.
1.3.6.1.4.1.318.1.1.28.3.1.2.1.5ColumnpmmInputTotalPowerFactorread-onlymandatoryIndicates the total power factor. A value of 100 representing a unity power factor (1.00). Specified in hundredths.
1.3.6.1.4.1.318.1.1.28.3.1.2.1.6ColumnpmmInputActiveEnergyDeliveredread-onlymandatoryShows the input active energy delivered in tenths of kWh.
1.3.6.1.4.1.318.1.1.28.3.1.2.1.7ColumnpmmInputActiveEnergyReceivedread-onlymandatoryShows the input active energy received in tenths of kWh.
1.3.6.1.4.1.318.1.1.28.3.1.2.1.8ColumnpmmInputApparentEnergyDeliveredread-onlymandatoryShows the input apparent energy delivered in tenths of kVAh.
1.3.6.1.4.1.318.1.1.28.3.1.2.1.9ColumnpmmInputApparentEnergyReceivedread-onlymandatoryShows the input apparent energy received in tenths of kVAh.
1.3.6.1.4.1.318.1.1.28.3.1.2.1.10ColumnpmmInputFrequencyDeviationread-writemandatoryShows the input frequency deviation in Hertz.
1.3.6.1.4.1.318.1.1.28.3.1.2.1.11ColumnpmmInputPowerFactorDeviationread-writemandatoryShows the input power factor deviation. Specified in tenths. A value of zero indicates that the threshold is disabled.
1.3.6.1.4.1.318.1.1.28.3.1.2.1.12ColumnpmmInputMinVoltThresholdread-writemandatoryThreshold below which an input minimum voltage condition will be generated. Specified as percent deviation from nominal voltage represented in the OID pmmDevic…
1.3.6.1.4.1.318.1.1.28.3.1.2.1.13ColumnpmmInputLowVoltThresholdread-writemandatoryThreshold below which an input low voltage condition will be generated. Specified as percent deviation from nominal voltage represented in the OID pmmDeviceNom…
1.3.6.1.4.1.318.1.1.28.3.1.2.1.14ColumnpmmInputHighVoltThresholdread-writemandatoryThreshold above which an input high voltage condition will be generated. Specified as percent deviation from nominal voltage represented in the OID pmmDeviceNo…
1.3.6.1.4.1.318.1.1.28.3.1.2.1.15ColumnpmmInputMaxVoltThresholdread-writemandatoryThreshold above which an input maximum voltage condition will be generated. Specified as percent deviation from nominal voltage represented in the OID pmmDevic…
1.3.6.1.4.1.318.1.1.28.3.1.2.1.16ColumnpmmInputMinCurrentThresholdread-writemandatoryThreshold below which an input minimum current condition will be generated. Specified as a percent of the panel breaker rating. A value of zero indicates that …
1.3.6.1.4.1.318.1.1.28.3.1.2.1.17ColumnpmmInputLowCurrentThresholdread-writemandatoryThreshold below which an input low current condition will be generated. Specified as a percent of the panel breaker rating. A value of zero indicates that the …
1.3.6.1.4.1.318.1.1.28.3.1.2.1.18ColumnpmmInputHighCurrentThresholdread-writemandatoryThreshold above which an input high current condition will be generated. Specified as a percent of the panel breaker rating. A value of zero indicates that the…
1.3.6.1.4.1.318.1.1.28.3.1.2.1.19ColumnpmmInputMaxCurrentThresholdread-writemandatoryThreshold above which an input maximum current condition will be generated. Specified as a percent of the panel breaker rating. A value of zero indicates that …
1.3.6.1.4.1.318.1.1.28.3.1.2.1.20ColumnpmmInputMinApparentPowerThresholdread-writemandatoryThreshold below which an input minimum apparent power condition will be generated. Specified as a percent deviation from nominal power rating. A value of zero …
1.3.6.1.4.1.318.1.1.28.3.1.2.1.21ColumnpmmInputMaxApparentPowerThresholdread-writemandatoryThreshold above which an input maximum apparent power condition will be generated. Specified as a percent deviation from nominal power rating. A value of zero …
1.3.6.1.4.1.318.1.1.28.3.1.2.1.22ColumnpmmInputOverActivePowerThresholdread-writemandatoryThreshold above which an input over active power condition will be generated. Specified as a percent deviation from nominal power rating. A value of zero indic…
1.3.6.1.4.1.318.1.1.28.3.1.2.1.23ColumnpmmInputBreakerStateread-onlymandatoryThis value indicates the current state of input breaker. 1 will indicate open, 2 will indicate closed, 3 will indicate unknown.
1.3.6.1.4.1.318.1.1.28.3.1.2.1.24ColumnpmmInputBreakerOpenAlarmread-writemandatoryBreaker open alarm status. 1 will indicate enabled, 2 will indicate disabled, 3 will indicate unknown.
1.3.6.1.4.1.318.1.1.28.3.1.3TablepmmInputPhaseTablenot-accessiblemandatoryA list of input table entries. The number of entries is given by the value of pmmInputMeterTableSize OID.
1.3.6.1.4.1.318.1.1.28.3.1.3.1RowpmmInputPhaseEntrynot-accessiblemandatoryAn entry containing information applicable to a particular input phase.
1.3.6.1.4.1.318.1.1.28.3.1.3.1.1ColumnpmmInputMeterNumread-onlymandatoryThe input meter identifier.
1.3.6.1.4.1.318.1.1.28.3.1.3.1.2ColumnpmmInputPhaseread-onlymandatoryInput phase index.
1.3.6.1.4.1.318.1.1.28.3.1.3.1.3ColumnpmmInputVoltageLtoLread-onlymandatoryLine-to-line input voltage available. Measured in tenths of Volts.
1.3.6.1.4.1.318.1.1.28.3.1.3.1.4ColumnpmmInputVoltageLtoNread-onlymandatoryLine-to-neutral input voltage available. Measured in tenths of Volts.
1.3.6.1.4.1.318.1.1.28.3.1.3.1.5ColumnpmmInputPhaseCurrentread-onlymandatoryInput current per phase. Measured in tenths of Amps.
1.3.6.1.4.1.318.1.1.28.3.1.3.1.6ColumnpmmInputActivePowerread-onlymandatoryInput power per phase. Measured in tenths of kW.
1.3.6.1.4.1.318.1.1.28.3.1.3.1.7ColumnpmmInputApparentPowerread-onlymandatoryInput power per phase. Measured in tenths of kVA.
1.3.6.1.4.1.318.1.1.28.3.1.3.1.8ColumnpmmInputPowerFactorread-onlymandatoryIndicates the power factor of the input per phase. A value of 100 representing a unity power factor (1.00). Specified in hundredths.
1.3.6.1.4.1.318.1.1.28.3.2NodepmmOutput
1.3.6.1.4.1.318.1.1.28.3.2.1ScalarpmmOutputMeterTableSizeread-onlymandatoryThe number of output meters attached to the system.
1.3.6.1.4.1.318.1.1.28.3.2.2TablepmmOutputTablenot-accessiblemandatoryA list of output meter entries.
1.3.6.1.4.1.318.1.1.28.3.2.2.1RowpmmOutputEntrynot-accessiblemandatoryAn entry containing information applicable to a particular output meter.
1.3.6.1.4.1.318.1.1.28.3.2.2.1.1ColumnpmmOutputMeterIndexread-onlymandatoryThe output meter identifier.
1.3.6.1.4.1.318.1.1.28.3.2.2.1.2ColumnpmmOutputFrequencyread-onlymandatoryThe output frequency in tenths of Hertz.
1.3.6.1.4.1.318.1.1.28.3.2.2.1.3ColumnpmmOutputTotalActivePowerread-onlymandatoryShows the total output active power in tenths of kW.
1.3.6.1.4.1.318.1.1.28.3.2.2.1.4ColumnpmmOutputTotalApparentPowerread-onlymandatoryShows the total output apparent power in tenths of kVA.
1.3.6.1.4.1.318.1.1.28.3.2.2.1.5ColumnpmmOutputTotalPowerFactorread-onlymandatoryIndicates the total power factor. A value of 100 representing a unity power factor (1.00). Specified in hundredths.
1.3.6.1.4.1.318.1.1.28.3.2.2.1.6ColumnpmmOutputActiveEnergyDeliveredread-onlymandatoryShows the output active energy delivered in tenths of kWh.
1.3.6.1.4.1.318.1.1.28.3.2.2.1.7ColumnpmmOutputActiveEnergyReceivedread-onlymandatoryShows the output active energy received in tenths of kWh.
1.3.6.1.4.1.318.1.1.28.3.2.2.1.8ColumnpmmOutputApparentEnergyDeliveredread-onlymandatoryShows the output apparent energy delivered in tenths of kVAh.
1.3.6.1.4.1.318.1.1.28.3.2.2.1.9ColumnpmmOutputApparentEnergyReceivedread-onlymandatoryShows the output apparent energy received in tenths of kVAh.
1.3.6.1.4.1.318.1.1.28.3.2.2.1.10ColumnpmmOutputFrequencyDeviationread-writemandatoryShows the output frequency deviation in Hertz.
1.3.6.1.4.1.318.1.1.28.3.2.2.1.11ColumnpmmOutputPowerFactorDeviationread-writemandatoryShows the output power factor deviation. Specified in tenths. A value of zero indicates that the threshold is disabled.
1.3.6.1.4.1.318.1.1.28.3.2.2.1.12ColumnpmmOutputMinVoltThresholdread-writemandatoryThreshold below which an output minimum voltage condition will be generated. Specified as percent deviation from nominal voltage represented in the OID pmmDevi…
1.3.6.1.4.1.318.1.1.28.3.2.2.1.13ColumnpmmOutputLowVoltThresholdread-writemandatoryThreshold below which an output low voltage condition will be generated. Specified as percent deviation from nominal voltage represented in the OID pmmDeviceNo…
1.3.6.1.4.1.318.1.1.28.3.2.2.1.14ColumnpmmOutputHighVoltThresholdread-writemandatoryThreshold above which an output high voltage condition will be generated. Specified as percent deviation from nominal voltage represented in the OID pmmDeviceN…
1.3.6.1.4.1.318.1.1.28.3.2.2.1.15ColumnpmmOutputMaxVoltThresholdread-writemandatoryThreshold above which an output maximum voltage condition will be generated. Specified as percent deviation from nominal voltage represented in the OID pmmDevi…
1.3.6.1.4.1.318.1.1.28.3.2.2.1.16ColumnpmmOutputMinCurrentThresholdread-writemandatoryThreshold below which an output minimum current condition will be generated. Specified as a percent of the panel breaker rating. A value of zero indicates that…
1.3.6.1.4.1.318.1.1.28.3.2.2.1.17ColumnpmmOutputLowCurrentThresholdread-writemandatoryThreshold below which an output low current condition will be generated. Specified as a percent of the panel breaker rating. A value of zero indicates that the…
1.3.6.1.4.1.318.1.1.28.3.2.2.1.18ColumnpmmOutputHighCurrentThresholdread-writemandatoryThreshold above which an output high current condition will be generated. Specified as a percent of the panel breaker rating. A value of zero indicates that th…
1.3.6.1.4.1.318.1.1.28.3.2.2.1.19ColumnpmmOutputMaxCurrentThresholdread-writemandatoryThreshold above which an output maximum current condition will be generated. Specified as a percent of the panel breaker rating. A value of zero indicates that…
1.3.6.1.4.1.318.1.1.28.3.2.2.1.20ColumnpmmOutputMinApparentPowerThresholdread-writemandatoryThreshold below which an output minimum apparent power condition will be generated. Specified as a percent deviation from nominal power rating. A value of zero…
1.3.6.1.4.1.318.1.1.28.3.2.2.1.21ColumnpmmOutputMaxApparentPowerThresholdread-writemandatoryThreshold above which an output maximum apparent power condition will be generated. Specified as a percent deviation from nominal power rating. A value of zero…
1.3.6.1.4.1.318.1.1.28.3.2.2.1.22ColumnpmmOutputOverActivePowerThresholdread-writemandatoryThreshold above which an output over active power condition will be generated. Specified as a percent deviation from nominal power rating. A value of zero indi…
1.3.6.1.4.1.318.1.1.28.3.2.2.1.23ColumnpmmOutputPhaseLossThresholdread-writemandatoryThreshold below which an output phase loss condition will be generated. Specified as a percent deviation from nominal voltage represented in the OID pmmDeviceN…
1.3.6.1.4.1.318.1.1.28.3.2.2.1.24ColumnpmmOutputBreakerStateread-onlymandatoryThis value indicates the current state of output breaker. 1 will indicate open, 2 will indicate closed, 3 will indicate unknown.
1.3.6.1.4.1.318.1.1.28.3.2.2.1.25ColumnpmmOutputBreakerOpenAlarmread-writemandatoryBreaker open alarm status. 1 will indicate enabled, 2 will indicate disabled, 3 will indicate unknown.
1.3.6.1.4.1.318.1.1.28.3.2.3TablepmmOutputPhaseTablenot-accessiblemandatoryA list of output table entries. The number of entries is given by the value of pmmOutputMeterTableSize OID.
1.3.6.1.4.1.318.1.1.28.3.2.3.1RowpmmOutputPhaseEntrynot-accessiblemandatoryAn entry containing information applicable to a particular output phase.
1.3.6.1.4.1.318.1.1.28.3.2.3.1.1ColumnpmmOutputMeterNumread-onlymandatoryThe output meter identifier.
1.3.6.1.4.1.318.1.1.28.3.2.3.1.2ColumnpmmOutputPhaseread-onlymandatoryOutput phase index.
1.3.6.1.4.1.318.1.1.28.3.2.3.1.3ColumnpmmOutputVoltageLtoLread-onlymandatoryLine-to-line output voltage available. Measured in tenths of Volts.
1.3.6.1.4.1.318.1.1.28.3.2.3.1.4ColumnpmmOutputVoltageLtoNread-onlymandatoryLine-to-neutral output voltage available. Measured in tenths of Volts.
1.3.6.1.4.1.318.1.1.28.3.2.3.1.5ColumnpmmOutputPhaseCurrentread-onlymandatoryLoad current per phase. Measured in tenths of Amps.
1.3.6.1.4.1.318.1.1.28.3.2.3.1.6ColumnpmmOutputActivePowerread-onlymandatoryOutput power per phase. Measured in tenths of kW.
1.3.6.1.4.1.318.1.1.28.3.2.3.1.7ColumnpmmOutputApparentPowerread-onlymandatoryOutput power per phase. Measured in tenths of kVA.
1.3.6.1.4.1.318.1.1.28.3.2.3.1.8ColumnpmmOutputPowerFactorread-onlymandatoryIndicates the power factor of the output per phase. A value of 100 representing a unity power factor (1.00). Specified in hundredths.
1.3.6.1.4.1.318.1.1.28.3.3NodepmmBranch
1.3.6.1.4.1.318.1.1.28.3.3.1ScalarpmmnumofBranchMetersread-onlymandatoryThe number of branch meters attached to the system.
1.3.6.1.4.1.318.1.1.28.3.3.2ScalarpmmBranchBreakerTableSizeread-onlymandatoryThe number of branch breaker entries.
1.3.6.1.4.1.318.1.1.28.3.3.3TablepmmBranchBreakerTablenot-accessiblemandatoryA list of branch breaker table entries. The number of entries is contained in the pmmBranchBreakerTableSize OID.
1.3.6.1.4.1.318.1.1.28.3.3.3.1RowpmmBranchBreakerEntrynot-accessiblemandatoryAn entry containing information applicable to a particular branch breaker (panel/circuit position).
1.3.6.1.4.1.318.1.1.28.3.3.3.1.1ColumnpmmBranchCircuitMeterIndexread-onlymandatoryIndex of branch circuit meter in the table.
1.3.6.1.4.1.318.1.1.28.3.3.3.1.2ColumnpmmBranchCircuitIndexread-onlymandatoryThe branch circuit index.
1.3.6.1.4.1.318.1.1.28.3.3.3.1.3ColumnpmmBranchCircuitNumberOfPolesread-onlymandatoryThe number of poles.
1.3.6.1.4.1.318.1.1.28.3.3.3.1.4ColumnpmmBranchCircuitPhaseread-onlymandatoryThe phase associated with branch circuit.
1.3.6.1.4.1.318.1.1.28.3.3.3.1.5ColumnpmmBranchCircuitBreakerIdentifierread-onlymandatoryThe branch circuit identifier.
1.3.6.1.4.1.318.1.1.28.3.3.3.1.6ColumnpmmBranchCircuitLoadIdentifierread-onlymandatoryIdentifies the name or location of the branch circuit load.
1.3.6.1.4.1.318.1.1.28.3.3.3.1.7ColumnpmmBranchCircuitCurrentread-onlymandatoryThe branch circuit current Measured in tenths of Amps.
1.3.6.1.4.1.318.1.1.28.3.3.3.1.8ColumnpmmBranchCircuitBreakerRatingread-onlymandatoryThe rating of the branch circuit breaker in Amps.
1.3.6.1.4.1.318.1.1.28.3.3.3.1.9ColumnpmmBranchCircuitTotalActivePowerread-onlymandatoryBranch circuit total power. Measured in tenths of kW.
1.3.6.1.4.1.318.1.1.28.3.3.3.1.10ColumnpmmBranchCircuitTotalApparentPowerread-onlymandatoryBranch circuit total apparent power. Measured in tenths of kVA.
1.3.6.1.4.1.318.1.1.28.3.3.3.1.11ColumnpmmBranchCircuitEnergyUsageread-onlymandatoryIndicates the energy usage in tenths of kWh or -1 when not available.
1.3.6.1.4.1.318.1.1.28.3.3.3.1.12ColumnpmmBranchCircuitEnergyUsageResetDateread-onlymandatoryThe date that the kWh usage was reset, in the format mm/dd/yyyy.
1.3.6.1.4.1.318.1.1.28.3.3.3.1.13ColumnpmmBranchCircuitTotalPowerFactorread-onlymandatoryIndicates the total power factor of the branch circuit output. A value of 100 representing a unity power factor (1.00) Specified in hundredths.
1.3.6.1.4.1.318.1.1.28.3.3.3.1.14ColumnpmmBranchCircuitBreakerStateread-onlymandatoryThis value indicates the current state of branch circuit breaker. 1 will indicate open, 2 will indicate closed, 3 will indicate unknown.
1.3.6.1.4.1.318.1.1.28.3.3.3.1.15ColumnpmmBranchCircuitMinCurrentThresholdread-writemandatoryThreshold below which a branch circuit minimum current condition will be generated. Specified as a percent of the branch breaker rating represented in the OID …
1.3.6.1.4.1.318.1.1.28.3.3.3.1.16ColumnpmmBranchCircuitLowCurrentThresholdread-writemandatoryThreshold below which a branch circuit low current condition will be generated. Specified as a percent of the branch breaker rating represented in the OID pmmB…
1.3.6.1.4.1.318.1.1.28.3.3.3.1.17ColumnpmmBranchCircuitHighCurrentThresholdread-writemandatoryThreshold below which a branch circuit high current condition will be generated. Specified as a percent of the branch breaker rating represented in the OID pmm…
1.3.6.1.4.1.318.1.1.28.3.3.3.1.18ColumnpmmBranchCircuitMaxCurrentThresholdread-writemandatoryThreshold below which a branch circuit maximum current condition will be generated. Specified as a percent of the branch breaker rating represented in the OID …
1.3.6.1.4.1.318.1.1.28.3.3.3.1.19ColumnpmmBranchCircuitMinApparentPowerThresholdread-writemandatoryThreshold below which a branch circuit minimum apparent power condition will be generated. Specified as a percent of the branch breaker apparent power rating. …
1.3.6.1.4.1.318.1.1.28.3.3.3.1.20ColumnpmmBranchCircuitMaxApparentPowerThresholdread-writemandatoryThreshold below which a branch circuit maximum apparent power condition will be generated. Specified as a percent of the branch breaker apparent power rating. …
1.3.6.1.4.1.318.1.1.28.3.3.3.1.21ColumnpmmBranchCircuitAlaramGenerationread-onlymandatoryAlarm generation status. 1 will indicate enabled, 2 will indicate disabled, 3 will indicate unknown.
1.3.6.1.4.1.318.1.1.28.3.3.3.1.22ColumnpmmBranchCircuitBreakerOpenAlarmread-writemandatoryBreaker open alarm status. 1 will indicate enabled, 2 will indicate disabled, 3 will indicate unknown.
1.3.6.1.4.1.318.1.2Nodesoftware
1.3.6.1.4.1.318.1.2.1NodepowerNetSubAgent
1.3.6.1.4.1.318.1.2.1.1NodepowerNetSoftwareSystem
1.3.6.1.4.1.318.1.2.1.1.1ScalarpowerNetSoftwareSystemDescriptionread-onlymandatoryA brief description of the PowerNet sub-agent.
1.3.6.1.4.1.318.1.2.1.1.2ScalarpowerNetSoftwareOidread-onlymandatoryThe object identifier of the PowerNet sub-agent.
1.3.6.1.4.1.318.1.2.1.1.3ScalarpowerNetSoftwareSystemUpTimeread-onlymandatoryThe time that the sub-agent has been running.
1.3.6.1.4.1.318.1.2.1.2NodepowerNetSoftwareConfig
1.3.6.1.4.1.318.1.2.1.2.1ScalarpowerNetSoftwareTableSizeread-onlymandatoryThe number of software modules supporting the UPS.
1.3.6.1.4.1.318.1.2.1.2.2TablepowerNetSoftwareTablenot-accessiblemandatoryA list of the software monitoring the UPS.
1.3.6.1.4.1.318.1.2.1.2.2.1RowpowerNetSoftwareEntrynot-accessiblemandatoryAn entry containing information on a software module.
1.3.6.1.4.1.318.1.2.1.2.2.1.1ColumnmoduleNumberread-onlymandatoryThe index into the Software Entry Table
1.3.6.1.4.1.318.1.2.1.2.2.1.2ColumnmoduleNameread-onlymandatoryThe name of the software module.
1.3.6.1.4.1.318.1.2.1.2.2.1.3ColumnmoduleVersionread-onlymandatoryThe version of the software module.
1.3.6.1.4.1.318.1.2.1.2.2.1.4ColumnmoduleDateread-onlymandatoryThe date of the software module represented as mm-dd-yy.
1.3.6.1.4.1.318.1.2.2NodestruxureWareOperations
1.3.6.1.4.1.318.1.2.2.1NodestruxureWareOperationsStatus
1.3.6.1.4.1.318.1.2.2.1.1ScalarserverStatusread-onlymandatoryThe status of the StruxureWare Operations server: 1: The status of the application server is unknown. Check Webmin and if the problem persists, contact Technic…
1.3.6.1.4.1.318.1.2.2.1.2ScalardatabaseStatusread-onlymandatoryThe status of the StruxureWare Operations database: 1: The status of the database is unknown. Check Webmin and if the problem persists, contact Technical Suppo…
1.3.6.1.4.1.318.1.2.2.1.3ScalarloadBalancerStatusread-onlymandatoryThe status of the StruxureWare Operations load balancer: 1: Load Balancer status is unknown. Check Webmin and if the problem persists, contact Technical Suppor…
1.3.6.1.4.1.318.1.2.2.1.4ScalaressentialServicesStatusread-onlymandatoryThe status of the StruxureWare Operations essential services: 1: Unknown status. Check Webmin and if the problem persists, contact Technical Support. 2: Essent…
1.3.6.1.4.1.318.1.2.2.1.5ScalaretlStatusread-onlymandatoryThe status of the StruxureWare Operations ETL services: 1: Unknown status. Check the network configuration and the server network settings. If the problem pers…
1.3.6.1.4.1.318.1.2.3NodepowerChuteNetworkShutdown
1.3.6.1.4.1.318.1.2.3.1NodepcnsIdent
1.3.6.1.4.1.318.1.2.3.1.1Scalarpcnshostnameread-onlymandatoryThe hostname of the PCNS instance.
1.3.6.1.4.1.318.1.2.3.1.2ScalarpcnsVersionread-onlymandatoryThe version of PCNS installed. x.x.x
1.3.6.1.4.1.318.1.2.3.1.3ScalarpcnsOSread-onlymandatoryThe version of OS PCNS is Installed on.
1.3.6.1.4.1.318.1.2.3.1.4ScalarpcnsJavaVersionread-onlymandatoryThe version of Java PCNS is running on.
1.3.6.1.4.1.318.1.2.3.2NodepcnsNetworking
1.3.6.1.4.1.318.1.2.3.2.1ScalarpcnsUIProtocolread-onlymandatoryWeb Protocol used to connect to the PCNS UI.
1.3.6.1.4.1.318.1.2.3.2.2ScalarpcnsHttpPortread-onlymandatoryPort used for PCNS http UI.
1.3.6.1.4.1.318.1.2.3.2.3ScalarpcnsHttpsPortread-onlymandatoryPort used for PCNS https UI.
1.3.6.1.4.1.318.1.2.3.2.4ScalarpcnsNetworkConfigread-onlymandatoryConfiguration of the TCP Network.
1.3.6.1.4.1.318.1.2.3.2.5ScalarpcnsVirtualInstallread-onlymandatoryVirtualization technology in use by PCNS.
1.3.6.1.4.1.318.1.2.3.3NodepcnsNMC
1.3.6.1.4.1.318.1.2.3.3.1ScalarpcnsModeread-onlymandatoryConfiguration mode of the UPS(s) which PCNS is monitoring.
1.3.6.1.4.1.318.1.2.3.3.2ScalarpcnsNMCPortread-onlymandatoryPort used to connect to all of the Network Management Card(s).
1.3.6.1.4.1.318.1.2.3.3.3ScalarpcnsNMCProtocolread-onlymandatoryWeb Protocol used to connect to all of the Network Management Card(s).
1.3.6.1.4.1.318.1.2.3.3.4TablepcnsNmcTablenot-accessiblemandatoryThe Network Management Cards in the UPS's which PCNS is monitoring to provide safe shutdown.
1.3.6.1.4.1.318.1.2.3.3.4.1RowpcnsNmcEntrynot-accessiblemandatoryDetails of the NMC.
1.3.6.1.4.1.318.1.2.3.3.4.1.1ColumnpcnsNmcIndexread-onlymandatoryIndex of the NMC within PCNS setup.
1.3.6.1.4.1.318.1.2.3.3.4.1.2ColumnpcnsNmcAddrread-onlymandatoryThe IP address of the NMC.
1.3.6.1.4.1.318.1.2.3.3.4.1.3ColumnpcnsNmcOutletread-onlymandatoryThe Outlet Group which PCNS is enrolled with on the NMC.
1.3.6.1.4.1.318.1.2.3.4NodepcnsEvents
1.3.6.1.4.1.318.1.2.3.4.1NodepcnsPowerFailed
1.3.6.1.4.1.318.1.2.3.4.1.1ScalarpcnsPowerFailedDescread-onlymandatoryThe Description of the event.
1.3.6.1.4.1.318.1.2.3.4.1.2ScalarpcnsPowerFailedEnableLoggingread-writemandatoryLog occurrences of this event in PCNS log.
1.3.6.1.4.1.318.1.2.3.4.1.3ScalarpcnsPowerFailedEnableCommandFileread-writemandatoryExecute a command file when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.1.4ScalarpcnsPowerFailedCommandFilePathread-writemandatoryPath of command file to execute when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.1.5ScalarpcnsPowerFailedCommandFileDelayread-writemandatoryHow long to wait after event occurs before executing command file (seconds).
1.3.6.1.4.1.318.1.2.3.4.1.6ScalarpcnsPowerFailedEnableShutdownread-writemandatoryPerform a graceful shutdown of the server when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.1.7ScalarpcnsPowerFailedShutdownDelayread-writemandatoryHow long to wait after event occurs before performing a graceful shutdown of the server (seconds).
1.3.6.1.4.1.318.1.2.3.4.2NodepcnsPowerRestored
1.3.6.1.4.1.318.1.2.3.4.2.1ScalarpcnsPowerRestoredDescread-onlymandatoryThe Description of the event.
1.3.6.1.4.1.318.1.2.3.4.2.2ScalarpcnsPowerRestoredEnableLoggingread-writemandatoryLog occurrences of this event in PCNS log.
1.3.6.1.4.1.318.1.2.3.4.2.3ScalarpcnsPowerRestoredEnableCommandFileread-writemandatoryExecute a command file when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.2.4ScalarpcnsPowerRestoredCommandFilePathread-writemandatoryPath of command file to execute when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.2.5ScalarpcnsPowerRestoredCommandFileDelayread-writemandatoryHow long to wait after event occurs before executing command file (seconds).
1.3.6.1.4.1.318.1.2.3.4.3NodepcnsOverload
1.3.6.1.4.1.318.1.2.3.4.3.1ScalarpcnsOverloadDescread-onlymandatoryThe Description of the event.
1.3.6.1.4.1.318.1.2.3.4.3.2ScalarpcnsOverloadEnableLoggingread-writemandatoryLog occurrences of this event in PCNS log.
1.3.6.1.4.1.318.1.2.3.4.3.3ScalarpcnsOverloadEnableCommandFileread-writemandatoryExecute a command file when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.3.4ScalarpcnsOverloadCommandFilePathread-writemandatoryPath of command file to execute when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.3.5ScalarpcnsOverloadCommandFileDelayread-writemandatoryHow long to wait after event occurs before executing command file (seconds).
1.3.6.1.4.1.318.1.2.3.4.3.6ScalarpcnsOverloadEnableShutdownread-writemandatoryPerform a graceful shutdown of the server when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.3.7ScalarpcnsOverloadShutdownDelayread-writemandatoryHow long to wait after event occurs before performing a graceful shutdown of the server (seconds).
1.3.6.1.4.1.318.1.2.3.4.4NodepcnsOverloadSolved
1.3.6.1.4.1.318.1.2.3.4.4.1ScalarpcnsOverloadSolvedDescread-onlymandatoryThe Description of the event.
1.3.6.1.4.1.318.1.2.3.4.4.2ScalarpcnsOverloadSolvedEnableLoggingread-writemandatoryLog occurrences of this event in PCNS log.
1.3.6.1.4.1.318.1.2.3.4.4.3ScalarpcnsOverloadSolvedEnableCommandFileread-writemandatoryExecute a command file when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.4.4ScalarpcnsOverloadSolvedCommandFilePathread-writemandatoryPath of command file to execute when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.4.5ScalarpcnsOverloadSolvedCommandFileDelayread-writemandatoryHow long to wait after event occurs before executing command file (seconds).
1.3.6.1.4.1.318.1.2.3.4.5NodepcnsRunTimeExceeded
1.3.6.1.4.1.318.1.2.3.4.5.1ScalarpcnsRunTimeExceededDescread-onlymandatoryThe Description of the event.
1.3.6.1.4.1.318.1.2.3.4.5.2ScalarpcnsRunTimeExceededEnableLoggingread-writemandatoryLog occurrences of this event in PCNS log.
1.3.6.1.4.1.318.1.2.3.4.5.3ScalarpcnsRunTimeExceededEnableCommandFileread-writemandatoryExecute a command file when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.5.4ScalarpcnsRunTimeExceededCommandFilePathread-writemandatoryPath of command file to execute when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.5.5ScalarpcnsRunTimeExceededCommandFileDelayread-writemandatoryHow long to wait after event occurs before executing command file (seconds).
1.3.6.1.4.1.318.1.2.3.4.5.6ScalarpcnsRunTimeExceededEnableShutdownread-writemandatoryPerform a graceful shutdown of the server when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.5.7ScalarpcnsRunTimeExceededShutdownDelayread-writemandatoryHow long to wait after event occurs before performing a graceful shutdown of the server (seconds).
1.3.6.1.4.1.318.1.2.3.4.6NodepcnsRunTimeWithinRange
1.3.6.1.4.1.318.1.2.3.4.6.1ScalarpcnsRunTimeWithinRangeDescread-onlymandatoryThe Description of the event.
1.3.6.1.4.1.318.1.2.3.4.6.2ScalarpcnsRunTimeWithinRangeEnableLoggingread-writemandatoryLog occurrences of this event in PCNS log.
1.3.6.1.4.1.318.1.2.3.4.6.3ScalarpcnsRunTimeWithinRangeEnableCommandFileread-writemandatoryExecute a command file when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.6.4ScalarpcnsRunTimeWithinRangeCommandFilePathread-writemandatoryPath of command file to execute when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.6.5ScalarpcnsRunTimeWithinRangeCommandFileDelayread-writemandatoryHow long to wait after event occurs before executing command file (seconds).
1.3.6.1.4.1.318.1.2.3.4.7NodepcnsRunTimeBelowThreshold
1.3.6.1.4.1.318.1.2.3.4.7.1ScalarpcnsRunTimeBelowThresholdDescread-onlymandatoryThe Description of the event.
1.3.6.1.4.1.318.1.2.3.4.7.2ScalarpcnspcnsRunTimeBelowThresholdEnableLoggingread-writemandatoryLog occurrences of this event in PCNS log.
1.3.6.1.4.1.318.1.2.3.4.7.3ScalarpcnsRunTimeBelowThresholdEnableCommandFileread-writemandatoryExecute a command file when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.7.4ScalarpcnsRunTimeBelowThresholdCommandFilePathread-writemandatoryPath of command file to execute when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.7.6ScalarpcnsRunTimeBelowThresholdEnableShutdownread-writemandatoryPerform a graceful shutdown of the server when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.7.8ScalarpcnsRunTimeBelowThresholdCommandFileThresholdread-writemandatoryIf the Runtime Remaining falls below this (seconds), the command file will run.
1.3.6.1.4.1.318.1.2.3.4.7.9ScalarpcnsRunTimeBelowThresholdShutdownThresholdread-writemandatoryIf the Runtime Remaining falls below this (seconds), the shutdown will begin.
1.3.6.1.4.1.318.1.2.3.4.8NodepcnsRunTimeAboveThreshold
1.3.6.1.4.1.318.1.2.3.4.8.1ScalarpcnsRunTimeAboveThresholdDescread-onlymandatoryThe Description of the event.
1.3.6.1.4.1.318.1.2.3.4.8.2ScalarpcnsRunTimeAboveThresholdEnableLoggingread-writemandatoryLog occurrences of this event in PCNS log.
1.3.6.1.4.1.318.1.2.3.4.8.3ScalarpcnsRunTimeAboveThresholdEnableCommandFileread-writemandatoryExecute a command file when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.8.4ScalarpcnsRunTimeAboveThresholdCommandFilePathread-writemandatoryPath of command file to execute when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.8.5ScalarpcnsRunTimeAboveThresholdCommandFileDelayread-writemandatoryHow long to wait after event occurs before executing command file (seconds).
1.3.6.1.4.1.318.1.2.3.4.10NodepcnsBatteryDischarged
1.3.6.1.4.1.318.1.2.3.4.10.1ScalarpcnsBatteryDischargedDescread-onlymandatoryThe Description of the event.
1.3.6.1.4.1.318.1.2.3.4.10.2ScalarpcnsBatteryDischargedEnableLoggingread-writemandatoryLog occurrences of this event in PCNS log.
1.3.6.1.4.1.318.1.2.3.4.10.3ScalarpcnsBatteryDischargedEnableCommandFileread-writemandatoryExecute a command file when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.10.4ScalarpcnsBatteryDischargedCommandFilePathread-writemandatoryPath of command file to execute when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.10.5ScalarpcnsBatteryDischargedCommandFileDelayread-writemandatoryHow long to wait after event occurs before executing command file (seconds).
1.3.6.1.4.1.318.1.2.3.4.10.6ScalarpcnsBatteryDischargedEnableShutdownread-writemandatoryPerform a graceful shutdown of the server when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.10.7ScalarpcnsBatteryDischargedShutdownDelayread-writemandatoryHow long to wait after event occurs before performing a graceful shutdown of the server (seconds).
1.3.6.1.4.1.318.1.2.3.4.11NodepcnsBatteryChargeInRange
1.3.6.1.4.1.318.1.2.3.4.11.1ScalarpcnsBatteryChargeInRangeDescread-onlymandatoryThe Description of the event.
1.3.6.1.4.1.318.1.2.3.4.11.2ScalarpcnsBatteryChargeInRangeEnableLoggingread-writemandatoryLog occurrences of this event in PCNS log.
1.3.6.1.4.1.318.1.2.3.4.11.3ScalarpcnsBatteryChargeInRangeEnableCommandFileread-writemandatoryExecute a command file when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.11.4ScalarpcnsBatteryChargeInRangeCommandFilePathread-writemandatoryPath of command file to execute when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.11.5ScalarpcnsBatteryChargeInRangeCommandFileDelayread-writemandatoryHow long to wait after event occurs before executing command file (seconds).
1.3.6.1.4.1.318.1.2.3.4.12NodepcnsFaultBypassEnabled
1.3.6.1.4.1.318.1.2.3.4.12.1ScalarpcnsFaultBypassEnabledDescread-onlymandatoryThe Description of the event.
1.3.6.1.4.1.318.1.2.3.4.12.2ScalarpcnsFaultBypassEnabledEnableLoggingread-writemandatoryLog occurrences of this event in PCNS log.
1.3.6.1.4.1.318.1.2.3.4.12.3ScalarpcnsFaultBypassEnabledEnableCommandFileread-writemandatoryExecute a command file when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.12.4ScalarpcnsFaultBypassEnabledCommandFilePathread-writemandatoryPath of command file to execute when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.12.5ScalarpcnsFaultBypassEnabledCommandFileDelayread-writemandatoryHow long to wait after event occurs before executing command file (seconds).
1.3.6.1.4.1.318.1.2.3.4.12.6ScalarpcnsFaultBypassEnabledEnableShutdownread-writemandatoryPerform a graceful shutdown of the server when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.12.7ScalarpcnsFaultBypassEnabledShutdownDelayread-writemandatoryHow long to wait after event occurs before performing a graceful shutdown of the server (seconds).
1.3.6.1.4.1.318.1.2.3.4.13NodepcnsBypassEnabled
1.3.6.1.4.1.318.1.2.3.4.13.1ScalarpcnsBypassEnabledDescread-onlymandatoryThe Description of the event.
1.3.6.1.4.1.318.1.2.3.4.13.2ScalarpcnsBypassEnabledEnableLoggingread-writemandatoryLog occurrences of this event in PCNS log.
1.3.6.1.4.1.318.1.2.3.4.13.3ScalarpcnsBypassEnabledEnableCommandFileread-writemandatoryExecute a command file when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.13.4ScalarpcnsBypassEnabledCommandFilePathread-writemandatoryPath of command file to execute when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.13.5ScalarpcnsBypassEnabledCommandFileDelayread-writemandatoryHow long to wait after event occurs before executing command file (seconds).
1.3.6.1.4.1.318.1.2.3.4.13.6ScalarpcnsBypassEnabledEnableShutdownread-writemandatoryPerform a graceful shutdown of the server when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.13.7ScalarpcnsBypassEnabledShutdownDelayread-writemandatoryHow long to wait after event occurs before performing a graceful shutdown of the server (seconds).
1.3.6.1.4.1.318.1.2.3.4.14NodepcnsBypassManualEnabled
1.3.6.1.4.1.318.1.2.3.4.14.1ScalarpcnsBypassManualEnabledDescread-onlymandatoryThe Description of the event.
1.3.6.1.4.1.318.1.2.3.4.14.2ScalarpcnsBypassManualEnabledEnableLoggingread-writemandatoryLog occurrences of this event in PCNS log.
1.3.6.1.4.1.318.1.2.3.4.14.3ScalarpcnsBypassManualEnabledEnableCommandFileread-writemandatoryExecute a command file when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.14.4ScalarpcnsBypassManualEnabledCommandFilePathread-writemandatoryPath of command file to execute when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.14.5ScalarpcnsBypassManualEnabledCommandFileDelayread-writemandatoryHow long to wait after event occurs before executing command file (seconds).
1.3.6.1.4.1.318.1.2.3.4.14.6ScalarpcnsBypassManualEnabledEnableShutdownread-writemandatoryPerform a graceful shutdown of the server when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.14.7ScalarpcnsBypassManualEnabledShutdownDelayread-writemandatoryHow long to wait after event occurs before performing a graceful shutdown of the server (seconds).
1.3.6.1.4.1.318.1.2.3.4.15NodepcnsBypassDisabled
1.3.6.1.4.1.318.1.2.3.4.15.1ScalarpcnsBypassDisabledDescread-onlymandatoryThe Description of the event.
1.3.6.1.4.1.318.1.2.3.4.15.2ScalarpcnsBypassDisabledEnableLoggingread-writemandatoryLog occurrences of this event in PCNS log.
1.3.6.1.4.1.318.1.2.3.4.15.3ScalarpcnsBypassDisabledEnableCommandFileread-writemandatoryExecute a command file when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.15.4ScalarpcnsBypassDisabledCommandFilePathread-writemandatoryPath of command file to execute when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.15.5ScalarpcnsBypassDisabledCommandFileDelayread-writemandatoryHow long to wait after event occurs before executing command file (seconds).
1.3.6.1.4.1.318.1.2.3.4.16NodepcnsBypassContactorFailed
1.3.6.1.4.1.318.1.2.3.4.16.1ScalarpcnsBypassContactorFailedDescread-onlymandatoryThe Description of the event.
1.3.6.1.4.1.318.1.2.3.4.16.2ScalarpcnsBypassContactorFailedEnableLoggingread-writemandatoryLog occurrences of this event in PCNS log.
1.3.6.1.4.1.318.1.2.3.4.16.3ScalarpcnsBypassContactorFailedEnableCommandFileread-writemandatoryExecute a command file when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.16.4ScalarpcnsBypassContactorFailedCommandFilePathread-writemandatoryPath of command file to execute when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.16.5ScalarpcnsBypassContactorFailedCommandFileDelayread-writemandatoryHow long to wait after event occurs before executing command file (seconds).
1.3.6.1.4.1.318.1.2.3.4.16.6ScalarpcnsBypassContactorFailedEnableShutdownread-writemandatoryPerform a graceful shutdown of the server when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.16.7ScalarpcnsBypassContactorFailedShutdownDelayread-writemandatoryHow long to wait after event occurs before performing a graceful shutdown of the server (seconds).
1.3.6.1.4.1.318.1.2.3.4.17NodepcnsBypassContactorOk
1.3.6.1.4.1.318.1.2.3.4.17.1ScalarpcnsBypassContactorOkDescread-onlymandatoryThe Description of the event.
1.3.6.1.4.1.318.1.2.3.4.17.2ScalarpcnsBypassContactorOkEnableLoggingread-writemandatoryLog occurrences of this event in PCNS log.
1.3.6.1.4.1.318.1.2.3.4.17.3ScalarpcnsBypassContactorOkEnableCommandFileread-writemandatoryExecute a command file when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.17.4ScalarpcnsBypassContactorOkCommandFilePathread-writemandatoryPath of command file to execute when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.17.5ScalarpcnsBypassContactorOkCommandFileDelayread-writemandatoryHow long to wait after event occurs before executing command file (seconds).
1.3.6.1.4.1.318.1.2.3.4.18NodepcnsCommunicationLostOnBattery
1.3.6.1.4.1.318.1.2.3.4.18.1ScalarpcnsCommunicationLostOnBatteryDescread-onlymandatoryThe Description of the event.
1.3.6.1.4.1.318.1.2.3.4.18.2ScalarpcnsCommunicationLostOnBatteryEnableLoggingread-writemandatoryLog occurrences of this event in PCNS log.
1.3.6.1.4.1.318.1.2.3.4.18.3ScalarpcnsCommunicationLostOnBatteryEnableCommandFileread-writemandatoryExecute a command file when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.18.4ScalarpcnsCommunicationLostOnBatteryCommandFilePathread-writemandatoryPath of command file to execute when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.18.5ScalarpcnsCommunicationLostOnBatteryCommandFileDelayread-writemandatoryHow long to wait after event occurs before executing command file (seconds).
1.3.6.1.4.1.318.1.2.3.4.18.6ScalarpcnsCommunicationLostOnBatteryEnableShutdownread-writemandatoryPerform a graceful shutdown of the server when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.18.7ScalarpcnsCommunicationLostOnBatteryShutdownDelayread-writemandatoryHow long to wait after event occurs before performing a graceful shutdown of the server (seconds).
1.3.6.1.4.1.318.1.2.3.4.19NodepcnsCommunicationLost
1.3.6.1.4.1.318.1.2.3.4.19.1ScalarpcnsCommunicationLostDescread-onlymandatoryThe Description of the event.
1.3.6.1.4.1.318.1.2.3.4.19.2ScalarpcnsCommunicationLostEnableLoggingread-writemandatoryLog occurrences of this event in PCNS log.
1.3.6.1.4.1.318.1.2.3.4.19.3ScalarpcnsCommunicationLostEnableCommandFileread-writemandatoryExecute a command file when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.19.4ScalarpcnsCommunicationLostCommandFilePathread-writemandatoryPath of command file to execute when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.19.5ScalarpcnsCommunicationLostCommandFileDelayread-writemandatoryHow long to wait after event occurs before executing command file (seconds).
1.3.6.1.4.1.318.1.2.3.4.19.6ScalarpcnsCommunicationLostEnableShutdownread-writemandatoryPerform a graceful shutdown of the server when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.19.7ScalarpcnsCommunicationLostShutdownDelayread-writemandatoryHow long to wait after event occurs before performing a graceful shutdown of the server (seconds).
1.3.6.1.4.1.318.1.2.3.4.20NodepcnsNetCommunicationLost
1.3.6.1.4.1.318.1.2.3.4.20.1ScalarpcnsNetCommunicationLostDescread-onlymandatoryThe Description of the event.
1.3.6.1.4.1.318.1.2.3.4.20.2ScalarpcnsNetCommunicationLostEnableLoggingread-writemandatoryLog occurrences of this event in PCNS log.
1.3.6.1.4.1.318.1.2.3.4.20.3ScalarpcnsNetCommunicationLostEnableCommandFileread-writemandatoryExecute a command file when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.20.4ScalarpcnsNetCommunicationLostCommandFilePathread-writemandatoryPath of command file to execute when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.20.5ScalarpcnsNetCommunicationLostCommandFileDelayread-writemandatoryHow long to wait after event occurs before executing command file (seconds).
1.3.6.1.4.1.318.1.2.3.4.20.6ScalarpcnsNetCommunicationLostEnableShutdownread-writemandatoryPerform a graceful shutdown of the server when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.20.7ScalarpcnsNetCommunicationLostShutdownDelayread-writemandatoryHow long to wait after event occurs before performing a graceful shutdown of the server (seconds).
1.3.6.1.4.1.318.1.2.3.4.21NodepcnsCommunicationEstablished
1.3.6.1.4.1.318.1.2.3.4.21.1ScalarpcnsCommunicationEstablishedDescread-onlymandatoryThe Description of the event.
1.3.6.1.4.1.318.1.2.3.4.21.2ScalarpcnsCommunicationEstablishedEnableLoggingread-writemandatoryLog occurrences of this event in PCNS log.
1.3.6.1.4.1.318.1.2.3.4.21.3ScalarpcnsCommunicationEstablishedEnableCommandFileread-writemandatoryExecute a command file when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.21.4ScalarpcnsCommunicationEstablishedCommandFilePathread-writemandatoryPath of command file to execute when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.21.5ScalarpcnsCommunicationEstablishedCommandFileDelayread-writemandatoryHow long to wait after event occurs before executing command file (seconds).
1.3.6.1.4.1.318.1.2.3.4.22NodepcnsMinRedundancyLost
1.3.6.1.4.1.318.1.2.3.4.22.1ScalarpcnsMinRedundancyLostDescread-onlymandatoryThe Description of the event.
1.3.6.1.4.1.318.1.2.3.4.22.2ScalarpcnsMinRedundancyLostEnableLoggingread-writemandatoryLog occurrences of this event in PCNS log.
1.3.6.1.4.1.318.1.2.3.4.22.3ScalarpcnsMinRedundancyLostEnableCommandFileread-writemandatoryExecute a command file when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.22.4ScalarpcnsMinRedundancyLostCommandFilePathread-writemandatoryPath of command file to execute when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.22.5ScalarpcnsMinRedundancyLostCommandFileDelayread-writemandatoryHow long to wait after event occurs before executing command file (seconds).
1.3.6.1.4.1.318.1.2.3.4.22.6ScalarpcnsMinRedundancyLostEnableShutdownread-writemandatoryPerform a graceful shutdown of the server when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.22.7ScalarpcnsMinRedundancyLostShutdownDelayread-writemandatoryHow long to wait after event occurs before performing a graceful shutdown of the server (seconds).
1.3.6.1.4.1.318.1.2.3.4.23NodepcnsMinRedundancyRegained
1.3.6.1.4.1.318.1.2.3.4.23.1ScalarpcnsMinRedundancyRegainedDescread-onlymandatoryThe Description of the event.
1.3.6.1.4.1.318.1.2.3.4.23.2ScalarpcnsMinRedundancyRegainedEnableLoggingread-writemandatoryLog occurrences of this event in PCNS log.
1.3.6.1.4.1.318.1.2.3.4.23.3ScalarpcnsMinRedundancyRegainedEnableCommandFileread-writemandatoryExecute a command file when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.23.4ScalarpcnsMinRedundancyRegainedCommandFilePathread-writemandatoryPath of command file to execute when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.23.5ScalarpcnsMinRedundancyRegainedCommandFileDelayread-writemandatoryHow long to wait after event occurs before executing command file (seconds).
1.3.6.1.4.1.318.1.2.3.4.24NodepcnsParallelRedundancyLost
1.3.6.1.4.1.318.1.2.3.4.24.1ScalarpcnsParallelRedundancyLostDescread-onlymandatoryThe Description of the event.
1.3.6.1.4.1.318.1.2.3.4.24.2ScalarpcnsParallelRedundancyLostEnableLoggingread-writemandatoryLog occurrences of this event in PCNS log.
1.3.6.1.4.1.318.1.2.3.4.24.3ScalarpcnsParallelRedundancyLostEnableCommandFileread-writemandatoryExecute a command file when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.24.4ScalarpcnsParallelRedundancyLostCommandFilePathread-writemandatoryPath of command file to execute when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.24.5ScalarpcnsParallelRedundancyLostCommandFileDelayread-writemandatoryHow long to wait after event occurs before executing command file (seconds).
1.3.6.1.4.1.318.1.2.3.4.24.6ScalarpcnsParallelRedundancyLostEnableShutdownread-writemandatoryPerform a graceful shutdown of the server when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.24.7ScalarpcnsParallelRedundancyLostShutdownDelayread-writemandatoryHow long to wait after event occurs before performing a graceful shutdown of the server (seconds).
1.3.6.1.4.1.318.1.2.3.4.25NodepcnsParallelRedundancyRegained
1.3.6.1.4.1.318.1.2.3.4.25.1ScalarpcnsParallelRedundancyRegainedDescread-onlymandatoryThe Description of the event.
1.3.6.1.4.1.318.1.2.3.4.25.2ScalarpcnsParallelRedundancyRegainedEnableLoggingread-writemandatoryLog occurrences of this event in PCNS log.
1.3.6.1.4.1.318.1.2.3.4.25.3ScalarpcnsParallelRedundancyRegainedEnableCommandFileread-writemandatoryExecute a command file when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.25.4ScalarpcnsParallelRedundancyRegainedCommandFilePathread-writemandatoryPath of command file to execute when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.25.5ScalarpcnsParallelRedundancyRegainedCommandFileDelayread-writemandatoryHow long to wait after event occurs before executing command file (seconds).
1.3.6.1.4.1.318.1.2.3.4.26NodepcnsMaxInternalTempExceeded
1.3.6.1.4.1.318.1.2.3.4.26.1ScalarpcnsMaxInternalTempExceededDescread-onlymandatoryThe Description of the event.
1.3.6.1.4.1.318.1.2.3.4.26.2ScalarpcnsMaxInternalTempExceededEnableLoggingread-writemandatoryLog occurrences of this event in PCNS log.
1.3.6.1.4.1.318.1.2.3.4.26.3ScalarpcnsMaxInternalTempExceededEnableCommandFileread-writemandatoryExecute a command file when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.26.4ScalarpcnsMaxInternalTempExceededCommandFilePathread-writemandatoryPath of command file to execute when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.26.5ScalarpcnsMaxInternalTempExceededCommandFileDelayread-writemandatoryHow long to wait after event occurs before executing command file (seconds).
1.3.6.1.4.1.318.1.2.3.4.26.6ScalarpcnsMaxInternalTempExceededEnableShutdownread-writemandatoryPerform a graceful shutdown of the server when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.26.7ScalarpcnsMaxInternalTempExceededShutdownDelayread-writemandatoryHow long to wait after event occurs before performing a graceful shutdown of the server (seconds).
1.3.6.1.4.1.318.1.2.3.4.27NodepcnsMaxInternalTempInRange
1.3.6.1.4.1.318.1.2.3.4.27.1ScalarpcnsMaxInternalTempInRangeDescread-onlymandatoryThe Description of the event.
1.3.6.1.4.1.318.1.2.3.4.27.2ScalarpcnsMaxInternalTempInRangeEnableLoggingread-writemandatoryLog occurrences of this event in PCNS log.
1.3.6.1.4.1.318.1.2.3.4.27.3ScalarpcnsMaxInternalTempInRangeEnableCommandFileread-writemandatoryExecute a command file when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.27.4ScalarpcnsMaxInternalTempInRangeCommandFilePathread-writemandatoryPath of command file to execute when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.27.5ScalarpcnsMaxInternalTempInRangeCommandFileDelayread-writemandatoryHow long to wait after event occurs before executing command file (seconds).
1.3.6.1.4.1.318.1.2.3.4.28NodepcnsMinLoadCapabilityLost
1.3.6.1.4.1.318.1.2.3.4.28.1ScalarpcnsMinLoadCapabilityLostDescread-onlymandatoryThe Description of the event.
1.3.6.1.4.1.318.1.2.3.4.28.2ScalarpcnsMinLoadCapabilityLostEnableLoggingread-writemandatoryLog occurrences of this event in PCNS log.
1.3.6.1.4.1.318.1.2.3.4.28.3ScalarpcnsMinLoadCapabilityLostEnableCommandFileread-writemandatoryExecute a command file when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.28.4ScalarpcnsMinLoadCapabilityLostCommandFilePathread-writemandatoryPath of command file to execute when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.28.5ScalarpcnsMinLoadCapabilityLostCommandFileDelayread-writemandatoryHow long to wait after event occurs before executing command file (seconds).
1.3.6.1.4.1.318.1.2.3.4.28.6ScalarpcnsMinLoadCapabilityLostEnableShutdownread-writemandatoryPerform a graceful shutdown of the server when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.28.7ScalarpcnsMinLoadCapabilityLostShutdownDelayread-writemandatoryHow long to wait after event occurs before performing a graceful shutdown of the server (seconds).
1.3.6.1.4.1.318.1.2.3.4.29NodepcnsMinLoadCapabilityRegained
1.3.6.1.4.1.318.1.2.3.4.29.1ScalarpcnsMinLoadCapabilityRegainedDescread-onlymandatoryThe Description of the event.
1.3.6.1.4.1.318.1.2.3.4.29.2ScalarpcnsMinLoadCapabilityRegainedEnableLoggingread-writemandatoryLog occurrences of this event in PCNS log.
1.3.6.1.4.1.318.1.2.3.4.29.3ScalarpcnsMinLoadCapabilityRegainedEnableCommandFileread-writemandatoryExecute a command file when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.29.4ScalarpcnsMinLoadCapabilityRegainedCommandFilePathread-writemandatoryPath of command file to execute when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.29.5ScalarpcnsMinLoadCapabilityRegainedCommandFileDelayread-writemandatoryHow long to wait after event occurs before executing command file (seconds).
1.3.6.1.4.1.318.1.2.3.4.30NodepcnsEnvironmentCommunicationEstablished
1.3.6.1.4.1.318.1.2.3.4.30.1ScalarpcnsEnvironmentCommunicationEstablishedDescread-onlymandatoryThe Description of the event.
1.3.6.1.4.1.318.1.2.3.4.30.2ScalarpcnsEnvironmentCommunicationEstablishedEnableLoggingread-writemandatoryLog occurrences of this event in PCNS log.
1.3.6.1.4.1.318.1.2.3.4.30.3ScalarpcnsEnvironmentCommunicationEstablishedEnableCommandFileread-writemandatoryExecute a command file when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.30.4ScalarpcnsEnvironmentCommunicationEstablishedCommandFilePathread-writemandatoryPath of command file to execute when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.30.5ScalarpcnsEnvironmentCommunicationEstablishedCommandFileDelayread-writemandatoryHow long to wait after event occurs before executing command file (seconds).
1.3.6.1.4.1.318.1.2.3.4.31NodepcnsEnvironmentCommunicationLost
1.3.6.1.4.1.318.1.2.3.4.31.1ScalarpcnsEnvironmentCommunicationLostDescread-onlymandatoryThe Description of the event.
1.3.6.1.4.1.318.1.2.3.4.31.2ScalarpcnsEnvironmentCommunicationLostEnableLoggingread-writemandatoryLog occurrences of this event in PCNS log.
1.3.6.1.4.1.318.1.2.3.4.31.3ScalarpcnsEnvironmentCommunicationLostEnableCommandFileread-writemandatoryExecute a command file when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.31.4ScalarpcnsEnvironmentCommunicationLostCommandFilePathread-writemandatoryPath of command file to execute when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.31.5ScalarpcnsEnvironmentCommunicationLostCommandFileDelayread-writemandatoryHow long to wait after event occurs before executing command file (seconds).
1.3.6.1.4.1.318.1.2.3.4.32NodepcnsTempInRangeProbe1
1.3.6.1.4.1.318.1.2.3.4.32.1ScalarpcnsTempInRangeProbe1Descread-onlymandatoryThe Description of the event.
1.3.6.1.4.1.318.1.2.3.4.32.2ScalarpcnsTempInRangeProbe1EnableLoggingread-writemandatoryLog occurrences of this event in PCNS log.
1.3.6.1.4.1.318.1.2.3.4.32.3ScalarpcnsTempInRangeProbe1EnableCommandFileread-writemandatoryExecute a command file when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.32.4ScalarpcnsTempInRangeProbe1CommandFilePathread-writemandatoryPath of command file to execute when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.32.5ScalarpcnsTempInRangeProbe1CommandFileDelayread-writemandatoryHow long to wait after event occurs before executing command file (seconds).
1.3.6.1.4.1.318.1.2.3.4.33NodepcnsTempOutOfRangeProbe1
1.3.6.1.4.1.318.1.2.3.4.33.1ScalarpcnsTempOutOfRangeProbe1Descread-onlymandatoryThe Description of the event.
1.3.6.1.4.1.318.1.2.3.4.33.2ScalarpcnsTempOutOfRangeProbe1EnableLoggingread-writemandatoryLog occurrences of this event in PCNS log.
1.3.6.1.4.1.318.1.2.3.4.33.3ScalarpcnsTempOutOfRangeProbe1EnableCommandFileread-writemandatoryExecute a command file when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.33.4ScalarpcnsTempOutOfRangeProbe1CommandFilePathread-writemandatoryPath of command file to execute when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.33.5ScalarpcnsTempOutOfRangeProbe1CommandFileDelayread-writemandatoryHow long to wait after event occurs before executing command file (seconds).
1.3.6.1.4.1.318.1.2.3.4.33.6ScalarpcnsTempOutOfRangeProbe1EnableShutdownread-writemandatoryPerform a graceful shutdown of the server when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.33.7ScalarpcnsTempOutOfRangeProbe1ShutdownDelayread-writemandatoryHow long to wait after event occurs before performing a graceful shutdown of the server (seconds).
1.3.6.1.4.1.318.1.2.3.4.34NodepcnsHumidityInRangeProbe1
1.3.6.1.4.1.318.1.2.3.4.34.1ScalarpcnsHumidityInRangeProbe1Descread-onlymandatoryThe Description of the event.
1.3.6.1.4.1.318.1.2.3.4.34.2ScalarpcnsHumidityInRangeProbe1EnableLoggingread-writemandatoryLog occurrences of this event in PCNS log.
1.3.6.1.4.1.318.1.2.3.4.34.3ScalarpcnsHumidityInRangeProbe1EnableCommandFileread-writemandatoryExecute a command file when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.34.4ScalarpcnsHumidityInRangeProbe1CommandFilePathread-writemandatoryPath of command file to execute when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.34.5ScalarpcnsHumidityInRangeProbe1CommandFileDelayread-writemandatoryHow long to wait after event occurs before executing command file (seconds).
1.3.6.1.4.1.318.1.2.3.4.35NodepcnsHumidityOutOfRangeProbe1
1.3.6.1.4.1.318.1.2.3.4.35.1ScalarpcnsHumidityOutOfRangeProbe1Descread-onlymandatoryThe Description of the event.
1.3.6.1.4.1.318.1.2.3.4.35.2ScalarpcnsHumidityOutOfRangeProbe1EnableLoggingread-writemandatoryLog occurrences of this event in PCNS log.
1.3.6.1.4.1.318.1.2.3.4.35.3ScalarpcnsHumidityOutOfRangeProbe1EnableCommandFileread-writemandatoryExecute a command file when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.35.4ScalarpcnsHumidityOutOfRangeProbe1CommandFilePathread-writemandatoryPath of command file to execute when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.35.5ScalarpcnsHumidityOutOfRangeProbe1CommandFileDelayread-writemandatoryHow long to wait after event occurs before executing command file (seconds).
1.3.6.1.4.1.318.1.2.3.4.35.6ScalarpcnsHumidityOutOfRangeProbe1EnableShutdownread-writemandatoryPerform a graceful shutdown of the server when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.35.7ScalarpcnsHumidityOutOfRangeProbe1ShutdownDelayread-writemandatoryHow long to wait after event occurs before performing a graceful shutdown of the server (seconds).
1.3.6.1.4.1.318.1.2.3.4.36NodepcnsTempInRangeProbe2
1.3.6.1.4.1.318.1.2.3.4.36.1ScalarpcnsTempInRangeProbe2Descread-onlymandatoryThe Description of the event.
1.3.6.1.4.1.318.1.2.3.4.36.2ScalarpcnsTempInRangeProbe2EnableLoggingread-writemandatoryLog occurrences of this event in PCNS log.
1.3.6.1.4.1.318.1.2.3.4.36.3ScalarpcnsTempInRangeProbe2EnableCommandFileread-writemandatoryExecute a command file when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.36.4ScalarpcnsTempInRangeProbe2CommandFilePathread-writemandatoryPath of command file to execute when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.36.5ScalarpcnsTempInRangeProbe2CommandFileDelayread-writemandatoryHow long to wait after event occurs before executing command file (seconds).
1.3.6.1.4.1.318.1.2.3.4.37NodepcnsTempOutOfRangeProbe2
1.3.6.1.4.1.318.1.2.3.4.37.1ScalarpcnsTempOutOfRangeProbe2Descread-onlymandatoryThe Description of the event.
1.3.6.1.4.1.318.1.2.3.4.37.2ScalarpcnsTempOutOfRangeProbe2EnableLoggingread-writemandatoryLog occurrences of this event in PCNS log.
1.3.6.1.4.1.318.1.2.3.4.37.3ScalarpcnsTempOutOfRangeProbe2EnableCommandFileread-writemandatoryExecute a command file when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.37.4ScalarpcnsTempOutOfRangeProbe2CommandFilePathread-writemandatoryPath of command file to execute when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.37.5ScalarpcnsTempOutOfRangeProbe2CommandFileDelayread-writemandatoryHow long to wait after event occurs before executing command file (seconds).
1.3.6.1.4.1.318.1.2.3.4.37.6ScalarpcnsTempOutOfRangeProbe2EnableShutdownread-writemandatoryPerform a graceful shutdown of the server when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.37.7ScalarpcnsTempOutOfRangeProbe2ShutdownDelayread-writemandatoryHow long to wait after event occurs before performing a graceful shutdown of the server (seconds).
1.3.6.1.4.1.318.1.2.3.4.38NodepcnsHumidityInRangeProbe2
1.3.6.1.4.1.318.1.2.3.4.38.1ScalarpcnsHumidityInRangeProbe2Descread-onlymandatoryThe Description of the event.
1.3.6.1.4.1.318.1.2.3.4.38.2ScalarpcnsHumidityInRangeProbe2EnableLoggingread-writemandatoryLog occurrences of this event in PCNS log.
1.3.6.1.4.1.318.1.2.3.4.38.3ScalarpcnsHumidityInRangeProbe2EnableCommandFileread-writemandatoryExecute a command file when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.38.4ScalarpcnsHumidityInRangeProbe2CommandFilePathread-writemandatoryPath of command file to execute when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.38.5ScalarpcnsHumidityInRangeProbe2CommandFileDelayread-writemandatoryHow long to wait after event occurs before executing command file (seconds).
1.3.6.1.4.1.318.1.2.3.4.39NodepcnsHumidityOutOfRangeProbe2
1.3.6.1.4.1.318.1.2.3.4.39.1ScalarpcnsHumidityOutOfRangeProbe2Descread-onlymandatoryThe Description of the event.
1.3.6.1.4.1.318.1.2.3.4.39.2ScalarpcnsHumidityOutOfRangeProbe2EnableLoggingread-writemandatoryLog occurrences of this event in PCNS log.
1.3.6.1.4.1.318.1.2.3.4.39.3ScalarpcnsHumidityOutOfRangeProbe2EnableCommandFileread-writemandatoryExecute a command file when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.39.4ScalarpcnsHumidityOutOfRangeProbe2CommandFilePathread-writemandatoryPath of command file to execute when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.39.5ScalarpcnsHumidityOutOfRangeProbe2CommandFileDelayread-writemandatoryHow long to wait after event occurs before executing command file (seconds).
1.3.6.1.4.1.318.1.2.3.4.39.6ScalarpcnsHumidityOutOfRangeProbe2EnableShutdownread-writemandatoryPerform a graceful shutdown of the server when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.39.7ScalarpcnsHumidityOutOfRangeProbe2ShutdownDelayread-writemandatoryHow long to wait after event occurs before performing a graceful shutdown of the server (seconds).
1.3.6.1.4.1.318.1.2.3.4.40NodepcnsContactFault1
1.3.6.1.4.1.318.1.2.3.4.40.1ScalarpcnsContactFault1Descread-onlymandatoryThe Description of the event.
1.3.6.1.4.1.318.1.2.3.4.40.2ScalarpcnsContactFault1EnableLoggingread-writemandatoryLog occurrences of this event in PCNS log.
1.3.6.1.4.1.318.1.2.3.4.40.3ScalarpcnsContactFault1EnableCommandFileread-writemandatoryExecute a command file when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.40.4ScalarpcnsContactFault1CommandFilePathread-writemandatoryPath of command file to execute when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.40.5ScalarpcnsContactFault1CommandFileDelayread-writemandatoryHow long to wait after event occurs before executing command file (seconds).
1.3.6.1.4.1.318.1.2.3.4.40.6ScalarpcnsContactFault1EnableShutdownread-writemandatoryPerform a graceful shutdown of the server when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.40.7ScalarpcnsContactFault1ShutdownDelayread-writemandatoryHow long to wait after event occurs before performing a graceful shutdown of the server (seconds).
1.3.6.1.4.1.318.1.2.3.4.41NodepcnsContactFault2
1.3.6.1.4.1.318.1.2.3.4.41.1ScalarpcnsContactFault2Descread-onlymandatoryThe Description of the event.
1.3.6.1.4.1.318.1.2.3.4.41.2ScalarpcnsContactFault2EnableLoggingread-writemandatoryLog occurrences of this event in PCNS log.
1.3.6.1.4.1.318.1.2.3.4.41.3ScalarpcnsContactFault2EnableCommandFileread-writemandatoryExecute a command file when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.41.4ScalarpcnsContactFault2CommandFilePathread-writemandatoryPath of command file to execute when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.41.5ScalarpcnsContactFault2CommandFileDelayread-writemandatoryHow long to wait after event occurs before executing command file (seconds).
1.3.6.1.4.1.318.1.2.3.4.41.6ScalarpcnsContactFault2EnableShutdownread-writemandatoryPerform a graceful shutdown of the server when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.41.7ScalarpcnsContactFault2ShutdownDelayread-writemandatoryHow long to wait after event occurs before performing a graceful shutdown of the server (seconds).
1.3.6.1.4.1.318.1.2.3.4.42NodepcnsContactFault3
1.3.6.1.4.1.318.1.2.3.4.42.1ScalarpcnsContactFault3Descread-onlymandatoryThe Description of the event.
1.3.6.1.4.1.318.1.2.3.4.42.2ScalarpcnsContactFault3EnableLoggingread-writemandatoryLog occurrences of this event in PCNS log.
1.3.6.1.4.1.318.1.2.3.4.42.3ScalarpcnsContactFault3EnableCommandFileread-writemandatoryExecute a command file when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.42.4ScalarpcnsContactFault3CommandFilePathread-writemandatoryPath of command file to execute when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.42.5ScalarpcnsContactFault3CommandFileDelayread-writemandatoryHow long to wait after event occurs before executing command file (seconds).
1.3.6.1.4.1.318.1.2.3.4.42.6ScalarpcnsContactFault3EnableShutdownread-writemandatoryPerform a graceful shutdown of the server when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.42.7ScalarpcnsContactFault3ShutdownDelayread-writemandatoryHow long to wait after event occurs before performing a graceful shutdown of the server (seconds).
1.3.6.1.4.1.318.1.2.3.4.43NodepcnsContactFault4
1.3.6.1.4.1.318.1.2.3.4.43.1ScalarpcnsContactFault4Descread-onlymandatoryThe Description of the event.
1.3.6.1.4.1.318.1.2.3.4.43.2ScalarpcnsContactFault4EnableLoggingread-writemandatoryLog occurrences of this event in PCNS log.
1.3.6.1.4.1.318.1.2.3.4.43.3ScalarpcnsContactFault4EnableCommandFileread-writemandatoryExecute a command file when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.43.4ScalarpcnsContactFault4CommandFilePathread-writemandatoryPath of command file to execute when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.43.5ScalarpcnsContactFault4CommandFileDelayread-writemandatoryHow long to wait after event occurs before executing command file (seconds).
1.3.6.1.4.1.318.1.2.3.4.43.6ScalarpcnsContactFault4EnableShutdownread-writemandatoryPerform a graceful shutdown of the server when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.43.7ScalarpcnsContactFault4ShutdownDelayread-writemandatoryHow long to wait after event occurs before performing a graceful shutdown of the server (seconds).
1.3.6.1.4.1.318.1.2.3.4.44NodepcnsContactNormal1
1.3.6.1.4.1.318.1.2.3.4.44.1ScalarpcnsContactNormal1Descread-onlymandatoryThe Description of the event.
1.3.6.1.4.1.318.1.2.3.4.44.2ScalarpcnsContactNormal1EnableLoggingread-writemandatoryLog occurrences of this event in PCNS log.
1.3.6.1.4.1.318.1.2.3.4.44.3ScalarpcnsContactNormal1EnableCommandFileread-writemandatoryExecute a command file when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.44.4ScalarpcnsContactNormal1CommandFilePathread-writemandatoryPath of command file to execute when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.44.5ScalarpcnsContactNormal1CommandFileDelayread-writemandatoryHow long to wait after event occurs before executing command file (seconds).
1.3.6.1.4.1.318.1.2.3.4.45NodepcnsContactNormal2
1.3.6.1.4.1.318.1.2.3.4.45.1ScalarpcnsContactNormal2Descread-onlymandatoryThe Description of the event.
1.3.6.1.4.1.318.1.2.3.4.45.2ScalarpcnsContactNormal2EnableLoggingread-writemandatoryLog occurrences of this event in PCNS log.
1.3.6.1.4.1.318.1.2.3.4.45.3ScalarpcnsContactNormal2EnableCommandFileread-writemandatoryExecute a command file when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.45.4ScalarpcnsContactNormal2CommandFilePathread-writemandatoryPath of command file to execute when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.45.5ScalarpcnsContactNormal2CommandFileDelayread-writemandatoryHow long to wait after event occurs before executing command file (seconds).
1.3.6.1.4.1.318.1.2.3.4.46NodepcnsContactNormal3
1.3.6.1.4.1.318.1.2.3.4.46.1ScalarpcnsContactNormal3Descread-onlymandatoryThe Description of the event.
1.3.6.1.4.1.318.1.2.3.4.46.2ScalarpcnsContactNormal3EnableLoggingread-writemandatoryLog occurrences of this event in PCNS log.
1.3.6.1.4.1.318.1.2.3.4.46.3ScalarpcnsContactNormal3EnableCommandFileread-writemandatoryExecute a command file when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.46.4ScalarpcnsContactNormal3CommandFilePathread-writemandatoryPath of command file to execute when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.46.5ScalarpcnsContactNormal3CommandFileDelayread-writemandatoryHow long to wait after event occurs before executing command file (seconds).
1.3.6.1.4.1.318.1.2.3.4.47NodepcnsContactNormal4
1.3.6.1.4.1.318.1.2.3.4.47.1ScalarpcnsContactNormal4Descread-onlymandatoryThe Description of the event.
1.3.6.1.4.1.318.1.2.3.4.47.2ScalarpcnsContactNormal4EnableLoggingread-writemandatoryLog occurrences of this event in PCNS log.
1.3.6.1.4.1.318.1.2.3.4.47.3ScalarpcnsContactNormal4EnableCommandFileread-writemandatoryExecute a command file when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.47.4ScalarpcnsContactNormal4CommandFilePathread-writemandatoryPath of command file to execute when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.47.5ScalarpcnsContactNormal4CommandFileDelayread-writemandatoryHow long to wait after event occurs before executing command file (seconds).
1.3.6.1.4.1.318.1.2.3.5NodepcnsShutdown
1.3.6.1.4.1.318.1.2.3.5.1ScalarpcnsShutdownCommandFileEnabledread-writemandatoryRun a shutdown command file before performing graceful shutdown.
1.3.6.1.4.1.318.1.2.3.5.2ScalarpcnsShutdownCommandFileDelayread-writemandatoryHow long in seconds to wait before running a shutdown command file before graceful shutdown.
1.3.6.1.4.1.318.1.2.3.5.3ScalarpcnsShutdownCommandFileread-writemandatoryFull name of the shutdown command file to run before graceful shutdown.
1.3.6.1.4.1.318.1.2.3.5.4ScalarpcnsShutdownCommandFileDurationread-writemandatoryHow long in seconds shutdown command file takes to run.
1.3.6.1.4.1.318.1.2.3.5.5ScalarpcnsTurnOffUpsread-writemandatoryTurn off the UPS when performing a graceful shutdown.
1.3.6.1.4.1.318.1.2.3.5.6ScalarpcnsTurnOffSOGread-writemandatoryTurn off the Outlet Group on the UPS when performing a graceful shutdown.
1.3.6.1.4.1.318.1.2.3.5.7ScalarpcnsRuntimeRemainingThresholdread-writemandatoryThis defines a threshold for runtime remaining. When the UPS is running on battery power and the runtime remaining on the UPS drops below the threshold, PowerC…
1.3.6.1.4.1.318.1.2.3.5.8ScalarpcnsRuntimeRemainingCmdFileThresholdread-writemandatoryThis defines a threshold for runtime remaining. When runtime remaining drops below this threshold, PowerChute will execute the command file.
1.3.6.1.4.1.318.1.2.3.5.9TablepcnsAdvancedShutdownTablenot-accessiblemandatoryThe Network Management Cards in the UPS's which PCNS is monitoring to provide safe shutdown.
1.3.6.1.4.1.318.1.2.3.5.9.1RowpcnsAdvancedShutdownEntrynot-accessiblemandatoryDetails of the NMC.
1.3.6.1.4.1.318.1.2.3.5.9.1.1ColumnpcnsAdvancedGroupNoread-onlymandatoryIndex of the Advanced Shutdown Group.
1.3.6.1.4.1.318.1.2.3.5.9.1.2ColumnpcnsAdvancedGroupNameread-writemandatoryName of the Advanced Shutdown Group.
1.3.6.1.4.1.318.1.2.3.5.9.1.3ColumnpcnsAdvancedGroupNMCread-onlymandatoryList of NMCs in the Advanced Shutdown Group.
1.3.6.1.4.1.318.1.2.3.5.9.1.4ColumnpcnsAdvancedShutdownUPSRequiredForLoadread-writemandatoryNumber of UPS's required to power load.
1.3.6.1.4.1.318.1.2.3.5.9.1.5ColumnpcnsAdvancedShutdownCommandFileEnabledread-writemandatoryRun a shutdown command file before performing graceful shutdown.
1.3.6.1.4.1.318.1.2.3.5.9.1.6ColumnpcnsAdvancedShutdownCommandFileread-writemandatoryFull name of the shutdown command file to run before graceful shutdown.
1.3.6.1.4.1.318.1.2.3.5.9.1.7ColumnpcnsAdvancedShutdownCommandFileDurationread-writemandatoryHow long in seconds shutdown command file takes to run.
1.3.6.1.4.1.318.1.2.3.5.9.1.8ColumnpcnsAdvancedShutdownPowerchuteServerread-writemandatoryShut down PowerChute Server.
1.3.6.1.4.1.318.1.2.3.5.9.1.9ColumnpcnsAdvancedShutdownOnLostRedundancyread-writemandatoryShut down if Redundancy lost.
1.3.6.1.4.1.318.1.2.3.5.9.1.10ColumnpcnsAdvancedTurnOffUpsread-writemandatoryTurn off the UPS when performing a graceful shutdown.
1.3.6.1.4.1.318.1.2.3.5.9.1.11ColumnpcnsAdvancedTurnOffSOGread-writemandatoryTurn off the Outlet Group on the UPS when performing a graceful shutdown.
1.3.6.1.4.1.318.1.2.3.6NodepcnsAlarms
1.3.6.1.4.1.318.1.2.3.6.1ScalarpcnsCriticalFlagread-onlymandatoryPowerChute Network Shutdown has begun a safe shutdown of the host.
1.3.6.1.4.1.318.1.2.3.6.2ScalarpcnsCriticalCauseread-onlymandatoryThe reason PowerChute Network Shutdown has begun a safe shutdown.
1.3.6.1.4.1.318.1.2.3.6.3ScalarpcnsNetComsLostFlagread-onlymandatoryPowerChute cannot communicate with NMC.
1.3.6.1.4.1.318.1.2.3.6.4ScalarpcnsNMCComsLostFlagread-onlymandatoryNMC cannot communicate with UPS.
1.3.6.1.4.1.318.1.2.3.6.5ScalarpcnsUpdateAvailableFlagread-onlymandatoryPowerChute has detected that a newer version is available.
1.3.6.1.4.1.318.1.2.3.6.6ScalarpcnsUpdateDescread-onlymandatoryDetails of the newer version of PowerChute.
1.3.6.1.4.1.318.1.2.3.7ScalarpcnsLoggingLevelread-writemandatoryOverride the Root Logging level for PCNS. Possible Values: CLEAR, DEBUG
1.3.6.1.4.1.318.1.2.4NodepowerChuteBusinessEdition
1.3.6.1.4.1.318.1.2.4.1NodepcbeIdent
1.3.6.1.4.1.318.1.2.4.1.1ScalarpcbeHostnameread-onlymandatoryThe hostname of the PCBE instance.
1.3.6.1.4.1.318.1.2.4.1.2ScalarpcbeVersionread-onlymandatoryThe version of PCBE installed. x.x.x
1.3.6.1.4.1.318.1.2.4.1.3ScalarpcbeOSread-onlymandatoryThe version of OS PCBE is installed on.
1.3.6.1.4.1.318.1.2.4.1.4ScalarpcbeJavaVersionread-onlymandatoryThe version of Java PCBE is running on.
1.3.6.1.4.1.318.1.2.4.1.5ScalarpcbeUIProtocolread-onlymandatoryWeb Protocol used to connect to the PCBE UI.
1.3.6.1.4.1.318.1.2.4.1.6ScalarpcbeHttpPortread-onlymandatoryPort used for PCBE http UI.
1.3.6.1.4.1.318.1.2.4.1.7ScalarpcbeHttpsPortread-onlymandatoryPort used for PCBE https UI.
1.3.6.1.4.1.318.1.2.4.6NodepcbeAlarms
1.3.6.1.4.1.318.1.2.4.6.1ScalarpcbeCriticalFlagread-onlymandatoryPowerChute Business Edition has begun a safe shutdown of the host.
1.3.6.1.4.1.318.1.2.4.6.2ScalarpcbeCriticalCauseread-onlymandatoryThe reason PowerChute Business Edition has begun a safe shutdown.
1.3.6.1.4.1.318.1.2.4.6.3ScalarpcbeComsLostFlagread-onlymandatoryIf active (1), PowerChute cannot communicate with UPS
1.3.6.1.4.1.318.1.2.4.6.5ScalarpcbeUpdateAvailableFlagread-onlymandatoryPowerChute has detected that a newer version is available.
1.3.6.1.4.1.318.1.2.4.6.6ScalarpcbeUpdateDescread-onlymandatoryDetails of the newer version of PowerChute.
1.3.6.1.4.1.318.1.3Nodesystem
1.3.6.1.4.1.318.1.3.1NodebackUPS
1.3.6.1.4.1.318.1.3.2NodesmartUPS
1.3.6.1.4.1.318.1.3.2.1NodesmartUPS250
1.3.6.1.4.1.318.1.3.2.2NodesmartUPS400
1.3.6.1.4.1.318.1.3.2.3NodesmartUPS600
1.3.6.1.4.1.318.1.3.2.4NodesmartUPS900
1.3.6.1.4.1.318.1.3.2.5NodesmartUPS1250
1.3.6.1.4.1.318.1.3.2.6NodesmartUPS2000
1.3.6.1.4.1.318.1.3.2.7NodesmartUPS450
1.3.6.1.4.1.318.1.3.2.8NodesmartUPS700
1.3.6.1.4.1.318.1.3.2.9NodesmartUPS1000
1.3.6.1.4.1.318.1.3.2.10NodesmartUPS1400
1.3.6.1.4.1.318.1.3.2.11NodesmartUPS2200
1.3.6.1.4.1.318.1.3.2.12NodesmartUPS3000
1.3.6.1.4.1.318.1.3.2.13NodesmartUPS5000
1.3.6.1.4.1.318.1.3.2.14NodesmartUPS7500
1.3.6.1.4.1.318.1.3.2.15NodesmartUPS10000
1.3.6.1.4.1.318.1.3.2.16NodesmartUPS1500
1.3.6.1.4.1.318.1.3.2.17NodesmartUPS3000DSP
1.3.6.1.4.1.318.1.3.2.18NodesmartUPS5000DSP
1.3.6.1.4.1.318.1.3.2.19NodesmartUPS8000
1.3.6.1.4.1.318.1.3.3NodematrixUPS
1.3.6.1.4.1.318.1.3.3.1NodematrixUPS3000
1.3.6.1.4.1.318.1.3.3.2NodematrixUPS5000
1.3.6.1.4.1.318.1.3.4NodemasterSwitch
1.3.6.1.4.1.318.1.3.4.1NodemasterSwitchV1
1.3.6.1.4.1.318.1.3.4.2NodemasterSwitchV2
1.3.6.1.4.1.318.1.3.4.3NodemasterSwitchVM
1.3.6.1.4.1.318.1.3.4.4NodemasterSwitchMSP
1.3.6.1.4.1.318.1.3.4.5NodemasterSwitchrPDU
1.3.6.1.4.1.318.1.3.4.6NodemasterSwitchrPDU2
1.3.6.1.4.1.318.1.3.4.7NodemasterSwitchsPDU
1.3.6.1.4.1.318.1.3.4.8NodemasterSwitchrPDUB
1.3.6.1.4.1.318.1.3.5NodesymmetraUPS
1.3.6.1.4.1.318.1.3.5.1NodesymmetraUPS4kVA
1.3.6.1.4.1.318.1.3.5.2NodesymmetraUPS8kVA
1.3.6.1.4.1.318.1.3.5.3NodesymmetraUPS12kVA
1.3.6.1.4.1.318.1.3.5.4NodesymmetraUPS16kVA
1.3.6.1.4.1.318.1.3.6Nodedp100E
1.3.6.1.4.1.318.1.3.7Nodedp300E
1.3.6.1.4.1.318.1.3.8Nodemonitors
1.3.6.1.4.1.318.1.3.8.1Nodeenvironmental
1.3.6.1.4.1.318.1.3.8.2NodeenvironmentalMgtSystem
1.3.6.1.4.1.318.1.3.8.3Nodeemu2
1.3.6.1.4.1.318.1.3.8.4Nodemem
1.3.6.1.4.1.318.1.3.9NoderedundantSwitch
1.3.6.1.4.1.318.1.3.10NodedcPower
1.3.6.1.4.1.318.1.3.10.1Nodedm3
1.3.6.1.4.1.318.1.3.10.2Nodedcmim2
1.3.6.1.4.1.318.1.3.11NodeautomaticXferSwitch
1.3.6.1.4.1.318.1.3.12NodenetLock
1.3.6.1.4.1.318.1.3.13Nodesymmetra3PhaseUPS
1.3.6.1.4.1.318.1.3.13.1Nodesymmetra3PhaseUPS40kVA
1.3.6.1.4.1.318.1.3.13.2Nodesymmetra3PhaseUPS60kVA
1.3.6.1.4.1.318.1.3.13.3Nodesymmetra3PhaseUPS80kVA
1.3.6.1.4.1.318.1.3.13.4Nodesymmetra3PhaseUPS20kVA
1.3.6.1.4.1.318.1.3.14NodenetworkAir
1.3.6.1.4.1.318.1.3.14.1NodeairFMSeries
1.3.6.1.4.1.318.1.3.14.2NoderackAirRemovalUnit
1.3.6.1.4.1.318.1.3.14.3NodeairPASeries
1.3.6.1.4.1.318.1.3.14.4NodeairIRSC100Series
1.3.6.1.4.1.318.1.3.14.5NodeairIRRC100Series
1.3.6.1.4.1.318.1.3.14.6NodeairIRRP100Series
1.3.6.1.4.1.318.1.3.14.7NodeairIRRP500Series
1.3.6.1.4.1.318.1.3.14.8NodeairIRRD100Series
1.3.6.1.4.1.318.1.3.14.9NodeairInRoomPerimeter
1.3.6.1.4.1.318.1.3.14.10NodeairACRC300Series
1.3.6.1.4.1.318.1.3.14.11NodeairLESeries
1.3.6.1.4.1.318.1.3.14.12NodeairIRRDU
1.3.6.1.4.1.318.1.3.14.13NodeairEcoBreeze
1.3.6.1.4.1.318.1.3.14.14NodeairLELSeries
1.3.6.1.4.1.318.1.3.14.15NodeairACRC600Series
1.3.6.1.4.1.318.1.3.14.16NodeairACRD600Series
1.3.6.1.4.1.318.1.3.14.17NodeairEconomizer
1.3.6.1.4.1.318.1.3.14.18NodeairTSAChillers
1.3.6.1.4.1.318.1.3.14.19NodeairLEG2Series
1.3.6.1.4.1.318.1.3.14.20NodeairAmico
1.3.6.1.4.1.318.1.3.14.21NodeairUniflarSP
1.3.6.1.4.1.318.1.3.14.22NodeairTrimChiller
1.3.6.1.4.1.318.1.3.14.23NodeairACRD300Series
1.3.6.1.4.1.318.1.3.15NodeinfraStruXurePDU
1.3.6.1.4.1.318.1.3.16Nodeais5000UPS
1.3.6.1.4.1.318.1.3.16.1Nodeais5000UPS10kVA
1.3.6.1.4.1.318.1.3.16.2Nodeais5000UPS20kVA
1.3.6.1.4.1.318.1.3.16.3Nodeais5000UPS30kVA
1.3.6.1.4.1.318.1.3.16.4Nodeais5000UPS40kVA
1.3.6.1.4.1.318.1.3.16.5Nodeais5000UPS60kVA
1.3.6.1.4.1.318.1.3.16.6Nodeais5000UPS80kVA
1.3.6.1.4.1.318.1.3.16.7Nodeais5000UPS100kVA
1.3.6.1.4.1.318.1.3.17NodesmartUPS3Phase
1.3.6.1.4.1.318.1.3.17.1NodesmartUPS3Phase10kVA
1.3.6.1.4.1.318.1.3.17.2NodesmartUPS3Phase15kVA
1.3.6.1.4.1.318.1.3.17.3NodesmartUPS3Phase20kVA
1.3.6.1.4.1.318.1.3.17.4NodesmartUPS3Phase30kVA
1.3.6.1.4.1.318.1.3.17.5NodesmartUPS3Phase40kVA
1.3.6.1.4.1.318.1.3.18NodebattManager
1.3.6.1.4.1.318.1.3.19NodeinfraStruXureATS
1.3.6.1.4.1.318.1.3.20NodeconPortServ
1.3.6.1.4.1.318.1.3.20.1NodeconPortServAP930x
1.3.6.1.4.1.318.1.3.21Nodegutor
1.3.6.1.4.1.318.1.3.21.1NodegutorPEW
1.3.6.1.4.1.318.1.3.21.2NodegutorPDW
1.3.6.1.4.1.318.1.3.21.3NodegutorWEW
1.3.6.1.4.1.318.1.3.21.4NodegutorWDW
1.3.6.1.4.1.318.1.3.21.5NodegutorSDC
1.3.6.1.4.1.318.1.3.21.6NodegutorPXP
1.3.6.1.4.1.318.1.3.21.7NodegutorPXC
1.3.6.1.4.1.318.1.3.22NodeaccControl
1.3.6.1.4.1.318.1.3.22.1NodeaccPX
1.3.6.1.4.1.318.1.3.23NodesymmetraPX
1.3.6.1.4.1.318.1.3.23.1NodesymmetraPx48kVA
1.3.6.1.4.1.318.1.3.23.2NodesymmetraPx160kVA
1.3.6.1.4.1.318.1.3.23.3NodesymmetraPx250kVA
1.3.6.1.4.1.318.1.3.23.4NodesymmetraPx500kVA
1.3.6.1.4.1.318.1.3.23.5NodesymmetraPx100kVA
1.3.6.1.4.1.318.1.3.23.6NodesymmetraPxDisplay
1.3.6.1.4.1.318.1.3.24NodeisxModDistribution
1.3.6.1.4.1.318.1.3.24.1Nodeisx24ModuleHalfRackPdu
1.3.6.1.4.1.318.1.3.24.2Nodeisx6ModuleRackPdu
1.3.6.1.4.1.318.1.3.25NodeisxServers
1.3.6.1.4.1.318.1.3.25.1NodeisxcBasic
1.3.6.1.4.1.318.1.3.25.2NodeisxcStandard
1.3.6.1.4.1.318.1.3.25.3NodeisxcEnterprise
1.3.6.1.4.1.318.1.3.25.4NodeisxcVirtual
1.3.6.1.4.1.318.1.3.27NodesmartUPS2
1.3.6.1.4.1.318.1.3.28Nodegalaxy
1.3.6.1.4.1.318.1.3.28.1Nodegalaxy7000UPS200kVA
1.3.6.1.4.1.318.1.3.28.2Nodegalaxy7000UPS250kVA
1.3.6.1.4.1.318.1.3.28.3Nodegalaxy7000UPS300kVA
1.3.6.1.4.1.318.1.3.28.4Nodegalaxy7000UPS400kVA
1.3.6.1.4.1.318.1.3.28.5Nodegalaxy7000UPS500kVA
1.3.6.1.4.1.318.1.3.28.6Nodegalaxy7000SSC800kVA
1.3.6.1.4.1.318.1.3.28.7Nodegalaxy7000SSC1200kVA
1.3.6.1.4.1.318.1.3.28.8Nodegalaxy7000SSC2000kVA
1.3.6.1.4.1.318.1.3.28.9Nodegalaxy300UPS10kVA33
1.3.6.1.4.1.318.1.3.28.10Nodegalaxy300UPS15kVA33
1.3.6.1.4.1.318.1.3.28.11Nodegalaxy300UPS20kVA33
1.3.6.1.4.1.318.1.3.28.12Nodegalaxy300UPS30kVA33
1.3.6.1.4.1.318.1.3.28.13Nodegalaxy300UPS40kVA33
1.3.6.1.4.1.318.1.3.28.14Nodegalaxy300UPS10kVA31
1.3.6.1.4.1.318.1.3.28.15Nodegalaxy300UPS15kVA31
1.3.6.1.4.1.318.1.3.28.16Nodegalaxy300UPS20kVA31
1.3.6.1.4.1.318.1.3.28.17Nodegalaxy300UPS30kVA31
1.3.6.1.4.1.318.1.3.28.18Nodegalaxy5000UPS20KVA
1.3.6.1.4.1.318.1.3.28.19Nodegalaxy5000UPS30KVA
1.3.6.1.4.1.318.1.3.28.20Nodegalaxy5000UPS40KVA
1.3.6.1.4.1.318.1.3.28.21Nodegalaxy5000UPS50KVA
1.3.6.1.4.1.318.1.3.28.22Nodegalaxy5000UPS60KVA
1.3.6.1.4.1.318.1.3.28.23Nodegalaxy5000UPS80KVA
1.3.6.1.4.1.318.1.3.28.24Nodegalaxy5000UPS100KVA
1.3.6.1.4.1.318.1.3.28.25Nodegalaxy5000UPS120KVA
1.3.6.1.4.1.318.1.3.28.26Nodegalaxy5000UPS130KVA
1.3.6.1.4.1.318.1.3.28.27Nodegalaxy5500UPS20KVA
1.3.6.1.4.1.318.1.3.28.28Nodegalaxy5500UPS30KVA
1.3.6.1.4.1.318.1.3.28.29Nodegalaxy5500UPS40KVA
1.3.6.1.4.1.318.1.3.28.30Nodegalaxy5500UPS50KVA
1.3.6.1.4.1.318.1.3.28.31Nodegalaxy5500UPS60KVA
1.3.6.1.4.1.318.1.3.28.32Nodegalaxy5500UPS80KVA
1.3.6.1.4.1.318.1.3.28.33Nodegalaxy5500UPS100KVA
1.3.6.1.4.1.318.1.3.28.34Nodegalaxy5500UPS120KVA
1.3.6.1.4.1.318.1.3.28.35Nodegalaxy5500UPS130KVA
1.3.6.1.4.1.318.1.3.28.36NodegalaxyVMUPS50kVA
1.3.6.1.4.1.318.1.3.28.37NodegalaxyVMUPS60kVA
1.3.6.1.4.1.318.1.3.28.38NodegalaxyVMUPS80kVA
1.3.6.1.4.1.318.1.3.28.39NodegalaxyVMUPS90kVA
1.3.6.1.4.1.318.1.3.28.40NodegalaxyVMUPS100kVA
1.3.6.1.4.1.318.1.3.28.41NodegalaxyVMUPS110kVA
1.3.6.1.4.1.318.1.3.28.42NodegalaxyVMUPS120kVA
1.3.6.1.4.1.318.1.3.28.43NodegalaxyVMUPS130kVA
1.3.6.1.4.1.318.1.3.28.44NodegalaxyVMUPS160kVA
1.3.6.1.4.1.318.1.3.28.45NodegalaxyVMUPS180kVA
1.3.6.1.4.1.318.1.3.28.46NodegalaxyVMUPS200kVA
1.3.6.1.4.1.318.1.3.28.47NodegalaxyVMUPS225kVA
1.3.6.1.4.1.318.1.3.28.48Nodegalaxy9000UPS
1.3.6.1.4.1.318.1.3.28.49Nodegalaxy9000SSC
1.3.6.1.4.1.318.1.3.28.50Nodegalaxy9000UPSWithSSC
1.3.6.1.4.1.318.1.3.28.51Nodegalaxy9000FreqConverter
1.3.6.1.4.1.318.1.3.28.56NodegalaxyVXUPS625kVA
1.3.6.1.4.1.318.1.3.28.57NodegalaxyVXUPS750kVA
1.3.6.1.4.1.318.1.3.28.58NodegalaxyVXUPS1000kVA
1.3.6.1.4.1.318.1.3.28.59NodegalaxyVXUPS1250kVA
1.3.6.1.4.1.318.1.3.28.60NodegalaxyVXUPS1500kVA
1.3.6.1.4.1.318.1.3.28.61Nodegalaxy300UPS60kVA33
1.3.6.1.4.1.318.1.3.28.62Nodegalaxy300UPS80kVA33
1.3.6.1.4.1.318.1.3.28.63NodegalaxyVXUPS500kVA
1.3.6.1.4.1.318.1.3.28.64NodegalaxyVXUPS250kVA
1.3.6.1.4.1.318.1.3.28.65NodegalaxyVXUPS400kVA
1.3.6.1.4.1.318.1.3.28.66NodegalaxyVSUPS100kW
1.3.6.1.4.1.318.1.3.28.67Nodegalaxy7000UPS160kVA
1.3.6.1.4.1.318.1.3.28.68NodegalaxyVXUPS300kVA
1.3.6.1.4.1.318.1.3.28.69NodegalaxyVXUPS1100kVA
1.3.6.1.4.1.318.1.3.30Nodeeps
1.3.6.1.4.1.318.1.3.30.1Nodeeps6000UPS
1.3.6.1.4.1.318.1.3.30.2Nodeeps6000SSC
1.3.6.1.4.1.318.1.3.30.3Nodeeps6000UPSWithSSC
1.3.6.1.4.1.318.1.3.30.4Nodeeps6000FreqConverter
1.3.6.1.4.1.318.1.3.30.5Nodeeps7000UPS
1.3.6.1.4.1.318.1.3.30.6Nodeeps7000SSC
1.3.6.1.4.1.318.1.3.30.7Nodeeps7000UPSWithSSC
1.3.6.1.4.1.318.1.3.30.8Nodeeps7000FreqConverter
1.3.6.1.4.1.318.1.3.30.9Nodeeps8000UPS
1.3.6.1.4.1.318.1.3.30.10Nodeeps8000SSC
1.3.6.1.4.1.318.1.3.30.11Nodeeps8000UPSWithSSC
1.3.6.1.4.1.318.1.3.30.12Nodeeps8000FreqConverter
1.3.6.1.4.1.318.1.3.31Nodepcns
1.3.6.1.4.1.318.1.3.31.1Nodepcns4
1.3.6.1.4.1.318.1.3.33Nodepcbe
1.3.6.1.4.1.318.1.3.33.1Nodepcbe9
1.3.6.1.4.1.318.1.3.34Nodepmm
1.3.6.1.4.1.318.1.3.34.1Nodepmm400kVA
1.3.6.1.4.1.318.1.3.34.2Nodepmm500kVA
1.3.6.1.4.1.318.2Nodeapcmgmt
1.3.6.1.4.1.318.2NodeupsOverloadSEVERE: The UPS has sensed a load greater than 100 percent of its rated capacity.
1.3.6.1.4.1.318.2.1Nodemconfig
1.3.6.1.4.1.318.2.1.1ScalarmconfigNumTrapReceiversread-onlymandatoryThe number of managers to send traps to.
1.3.6.1.4.1.318.2.1.2TablemconfigTrapReceiverTablenot-accessiblemandatoryA list of managers to send traps to. The number of entries is given by the value of mconfigNumTrapReceivers.
1.3.6.1.4.1.318.2.1.2.1RowmconfigTrapReceiverEntrynot-accessiblemandatoryThe managers to send traps to.
1.3.6.1.4.1.318.2.1.2.1.1ColumntrapIndexread-onlymandatoryThe index to a trap receiver entry.
1.3.6.1.4.1.318.2.1.2.1.2ColumnreceiverAddrread-writemandatoryThe IP address of the manager to send a trap to.
1.3.6.1.4.1.318.2.1.2.1.3ColumncommunityStringread-writemandatoryThe community name to use in the trap when sent to the manager.
1.3.6.1.4.1.318.2.1.2.1.4Columnseverityread-onlyobsoleteThe severity threshold of traps to send to the manager. traps are labeled in severity as informational(1), warning(2), severe(3). Only traps of equal or greate…
1.3.6.1.4.1.318.2.1.2.1.5ColumnacceptThisReceiverread-writemandatoryThe value of yes(1) indicates that trap generation for this manager is enabled. The value of no(2) indicates that trap generation for this manager is disabled
1.3.6.1.4.1.318.2.1.2.1.6ColumnreceiveTrapTyperead-onlyobsoleteType of trap.
1.3.6.1.4.1.318.2.1.3ScalarmconfigBOOTPEnabledread-onlymandatoryThe value of yes(1) indicates the PowerNet Adapter is configured to obtain its IP configuration parameters from a BOOTP server. The value of no(2) indicates ad…
1.3.6.1.4.1.318.2.1.4ScalarmconfigTFTPServerIPread-writemandatoryThe IP address of TFTP server. If mconfigBOOTPEnabled is yes(1), then this IP address is provided by BOOTP server and not allowed to be modified; otherwise, th…
1.3.6.1.4.1.318.2.1.5ScalarnewCodeAuthentViaTFTPread-onlymandatoryOnce mcontrolRestartAgent is set to loadAndExecuteNewAgent (3), PowerNet adapter will start to load the remote image file, for authentication only, instead of …
1.3.6.1.4.1.318.2.1.6NodemconfigClock
1.3.6.1.4.1.318.2.1.6.1ScalarmconfigClockDateread-writemandatoryThe current date in the mm/dd/yyyy format. Example: 01/01/2000.
1.3.6.1.4.1.318.2.1.6.2ScalarmconfigClockTimeread-writemandatoryThe current time in the hh:mm:ss am/pm format. Example: 12:00:00 am.
1.3.6.1.4.1.318.2.2Nodemcontrol
1.3.6.1.4.1.318.2.2.1ScalarmcontrolRestartAgentread-writemandatorySetting this OID to restartCurrentAgent (1) will restart the same SNMP agent code currently saved in flash memory. Setting this OID to loadAndExecuteNewAgent (…
1.3.6.1.4.1.318.2.3Nodemtrapargs
1.3.6.1.4.1.318.2.3.1ScalarmtrapargsIntegerread-onlymandatoryThis OID allows APC traps to be sent with an integer argument that my not be defined in the APC MIB. A get of this OID will return 0.
1.3.6.1.4.1.318.2.3.2ScalarmtrapargsIpAddressread-onlymandatoryThis OID allows APC traps to be sent with an IP address argument that my not be defined in the APC MIB. A get of this OID will return 0.0.0.0.
1.3.6.1.4.1.318.2.3.3ScalarmtrapargsStringread-onlymandatoryThis OID allows APC traps to be sent with an octet string argument that my not be defined in the APC MIB. A get of this OID will return a NULL string.
1.3.6.1.4.1.318.2.3.4ScalarmtrapargsGaugeread-onlymandatoryThis OID allows APC traps to be sent with a Gauge argument that my not be defined in the APC MIB. A get of this OID will return 0.
1.3.6.1.4.1.318.2.3.5ScalarmtrapargsTimeTicksread-onlymandatoryThis OID allows APC traps to be sent with a TimeTicks argument that my not be defined in the APC MIB. A get of this OID will return 0.
1.3.6.1.4.1.318.2.3.6ScalarmtrapargsInteger02read-onlymandatoryThis OID allows APC traps to be sent with an integer argument that my not be defined in the APC MIB. A get of this OID will return 0.
1.3.6.1.4.1.318.2.3.7ScalarmtrapargsInteger03read-onlymandatoryThis OID allows APC traps to be sent with an integer argument that my not be defined in the APC MIB. A get of this OID will return 0.
1.3.6.1.4.1.318.2.3.8ScalarmtrapargsIpAddress02read-onlymandatoryThis OID allows APC traps to be sent with an IP address argument that my not be defined in the APC MIB. A get of this OID will return 0.0.0.0.
1.3.6.1.4.1.318.2.3.9ScalarmtrapargsIpAddress03read-onlymandatoryThis OID allows APC traps to be sent with an IP address argument that my not be defined in the APC MIB. A get of this OID will return 0.0.0.0.
1.3.6.1.4.1.318.2.3.10ScalarmtrapargsString02read-onlymandatoryThis OID allows APC traps to be sent with an octet string argument that my not be defined in the APC MIB. A get of this OID will return a NULL string.
1.3.6.1.4.1.318.2.3.11ScalarmtrapargsString03read-onlymandatoryThis OID allows APC traps to be sent with an octet string argument that my not be defined in the APC MIB. A get of this OID will return a NULL string.
1.3.6.1.4.1.318.2.3.12ScalarmtrapargsGauge02read-onlymandatoryThis OID allows APC traps to be sent with a Gauge argument that my not be defined in the APC MIB. A get of this OID will return 0.
1.3.6.1.4.1.318.2.3.13ScalarmtrapargsGauge03read-onlymandatoryThis OID allows APC traps to be sent with a Gauge argument that my not be defined in the APC MIB. A get of this OID will return 0.
1.3.6.1.4.1.318.2.3.14ScalarmtrapargsTimeTicks02read-onlymandatoryThis OID allows APC traps to be sent with a TimeTicks argument that my not be defined in the APC MIB. A get of this OID will return 0.
1.3.6.1.4.1.318.2.3.15ScalarmtrapargsTimeTicks03read-onlymandatoryThis OID allows APC traps to be sent with a TimeTicks argument that my not be defined in the APC MIB. A get of this OID will return 0.
1.3.6.1.4.1.318.2.3.16ScalarmtrapargsString04read-onlymandatoryThis OID allows APC traps to be sent with an octet string argument that my not be defined in the APC MIB. A get of this OID will return a NULL string.
1.3.6.1.4.1.318.2.3.17ScalarmtrapargsString05read-onlymandatoryThis OID allows APC traps to be sent with an octet string argument that my not be defined in the APC MIB. A get of this OID will return a NULL string.
1.3.6.1.4.1.318.2.3.18ScalarmtrapargsInteger04read-onlymandatoryThis OID allows APC traps to be sent with an integer argument that my not be defined in the APC MIB. A get of this OID will return 0.
1.3.6.1.4.1.318.2.3.19ScalarmtrapargsInteger05read-onlymandatoryThis OID allows APC traps to be sent with an integer argument that my not be defined in the APC MIB. A get of this OID will return 0.
1.3.6.1.4.1.318.2.3.20ScalarmtrapargsString06read-onlymandatoryThis OID allows APC traps to be sent with an octet string argument that my not be defined in the APC MIB. A get of this OID will return a NULL string.
1.3.6.1.4.1.318.2.3.21ScalarmtrapargsString07read-onlymandatoryThis OID allows APC traps to be sent with an octet string argument that my not be defined in the APC MIB. A get of this OID will return a NULL string.
1.3.6.1.4.1.318.2.3.22ScalarmtrapargsString08read-onlymandatoryThis OID allows APC traps to be sent with an octet string argument that my not be defined in the APC MIB. A get of this OID will return a NULL string.
1.3.6.1.4.1.318.2.3.23ScalarmtrapargsOctetStringread-onlymandatoryThis OID allows APC traps to be sent with an octet string argument that my not be defined in the APC MIB. A get of this OID will return a NULL string.
1.3.6.1.4.1.318.2.3.24ScalarmtrapargsOctetString02read-onlymandatoryThis OID allows APC traps to be sent with an octet string argument that my not be defined in the APC MIB. A get of this OID will return a NULL string.
1.3.6.1.4.1.318.2.3.25ScalarmtrapargsOctetString03read-onlymandatoryThis OID allows APC traps to be sent with an octet string argument that my not be defined in the APC MIB. A get of this OID will return a NULL string.
1.3.6.1.4.1.318.2.3.26ScalarmtrapargsOctetString04read-onlymandatoryThis OID allows APC traps to be sent with an octet string argument that my not be defined in the APC MIB. A get of this OID will return a NULL string.
1.3.6.1.4.1.318.2.3.27ScalarmtrapargsOctetString05read-onlymandatoryThis OID allows APC traps to be sent with an octet string argument that my not be defined in the APC MIB. A get of this OID will return a NULL string.
1.3.6.1.4.1.318.2.3.28ScalarmtrapargsOctetString06read-onlymandatoryThis OID allows APC traps to be sent with an octet string argument that my not be defined in the APC MIB. A get of this OID will return a NULL string.
1.3.6.1.4.1.318.2.3.29ScalarmtrapargsOctetString07read-onlymandatoryThis OID allows APC traps to be sent with an octet string argument that my not be defined in the APC MIB. A get of this OID will return a NULL string.
1.3.6.1.4.1.318.2.3.30ScalarmtrapargsOctetString08read-onlymandatoryThis OID allows APC traps to be sent with an octet string argument that my not be defined in the APC MIB. A get of this OID will return a NULL string.
1.3.6.1.4.1.318.2.4Nodemfiletransfer
1.3.6.1.4.1.318.2.4.1NodemfiletransferStatus
1.3.6.1.4.1.318.2.4.1.1ScalarmfiletransferStatusLastTransferResultread-onlydeprecatedThis OID has been deprecated. Once mfiletransferControlInitiateFileTransfer is set to a value other than doNotInitiateFileTransfer a file transfer of mfiletran…
1.3.6.1.4.1.318.2.4.2NodemfiletransferConfig
1.3.6.1.4.1.318.2.4.2.1NodemfiletransferConfigSettings
1.3.6.1.4.1.318.2.4.2.1.1ScalarmfiletransferConfigSettingsFilenameread-writedeprecatedThis OID has been deprecated. The path and name of the file to transfer using the mfiletransferControlInitiateFileTransfer OID. If the file to transfer exists …
1.3.6.1.4.1.318.2.4.2.2NodemfiletransferConfigTFTP
1.3.6.1.4.1.318.2.4.2.2.1ScalarmfiletransferConfigTFTPServerAddressread-writedeprecatedThis OID has been deprecated. The IP Address in dotted decimal notation of the TFTP server involved in the file transfer.
1.3.6.1.4.1.318.2.4.2.3NodemfiletransferConfigFTP
1.3.6.1.4.1.318.2.4.2.3.1ScalarmfiletransferConfigFTPServerAddressread-writedeprecatedThis OID has been deprecated. The IP Address in dotted decimal notation of the FTP server involved in the file transfer.
1.3.6.1.4.1.318.2.4.2.3.2ScalarmfiletransferConfigFTPServerUserread-writedeprecatedThis OID has been deprecated. The user identification for logging into the FTP server specified with mfiletransferConfigFTPServerAddress.
1.3.6.1.4.1.318.2.4.2.3.3ScalarmfiletransferConfigFTPServerPasswordread-writedeprecatedThis OID has been deprecated. The password for logging into the FTP server specified with mfiletransferConfigFTPServerAddress.
1.3.6.1.4.1.318.2.4.3NodemfiletransferControl
1.3.6.1.4.1.318.2.4.3.1ScalarmfiletransferControlInitiateFileTransferread-writedeprecatedThis OID has been deprecated. Setting this OID to doNotInitiateFileTransfer (1) will do nothing. Setting this OID to initiateFileTransferDownloadViaTFTP (2) wi…
1.3.6.1.4.1.318.3NodeupsDiagnosticsFailedSEVERE: The UPS failed its internal diagnostic self-test.
1.3.6.1.4.1.318.4NodeupsDischargedSEVERE: The UPS batteries are discharged; if utility power fails an immediate low battery condition will exist. Sufficient runtime for necessary action cannot …
1.3.6.1.4.1.318.5NodeupsOnBatteryWARNING: The UPS has switched to battery backup power.
1.3.6.1.4.1.318.6NodesmartBoostOnWARNING: The UPS has enabled SmartBoost(TM).
1.3.6.1.4.1.318.7NodelowBatterySEVERE: The UPS batteries are low and will soon be exhausted. If utility power is not restored the UPS will put itself to 'sleep' and immediately cut power to …
1.3.6.1.4.1.318.8NodecommunicationEstablishedINFORMATIONAL: Communication with the UPS has been established.
1.3.6.1.4.1.318.9NodepowerRestoredINFORMATIONAL: Utility power has been restored.
1.3.6.1.4.1.318.10NodeupsDiagnosticsPassedINFORMATIONAL: The UPS passed its internal self-test.
1.3.6.1.4.1.318.11NodereturnFromLowBatteryINFORMATIONAL: The UPS has returned from a low battery condition.
1.3.6.1.4.1.318.12NodeupsTurnedOffWARNING: The UPS has been turned 'off' by the management station.
1.3.6.1.4.1.318.13NodeupsSleepingWARNING: The UPS is entering 'sleep' mode. Power to the load will be cut off.
1.3.6.1.4.1.318.14NodeupsWokeUpINFORMATION: The UPS has returned from 'sleep' mode. Power to the load has been restored.
1.3.6.1.4.1.318.15NodeupsRebootStartedWARNING: The UPS has started its reboot sequence. The UPS will reboot itself at this time.
1.3.6.1.4.1.318.16NodeupsDipSwitchChangedWARNING: The dip switch settings on the UPS have been changed, possibly altering UPS performance.
1.3.6.1.4.1.318.17NodeupsBatteryNeedsReplacementSEVERE: The batteries of the UPS need immediate replacement.
1.3.6.1.4.1.318.18NodecontactFaultSEVERE: One of the contacts on the Environmental Monitor has changed from its default position. The first variable is the contact number that is faulted.
1.3.6.1.4.1.318.19NodecontactFaultResolvedINFORMATIONAL: A fault on one of the Environmental Monitor contacts has been resolved. The first variable is the contact number that has been resolved.
1.3.6.1.4.1.318.20NodehardwareFailureBypassSEVERE: UPS on bypass due to internal fault
1.3.6.1.4.1.318.21NodesoftwareBypassWARNING: UPS on bypass - user set via software or panel
1.3.6.1.4.1.318.22NodeswitchedBypassWARNING: UPS on bypass - initiated by user
1.3.6.1.4.1.318.23NodereturnFromBypassINFORMATIONAL: UPS has returned from bypass
1.3.6.1.4.1.318.24NodebypassPowerSupplyFailureSEVERE: Base module bypass power supply needs repair
1.3.6.1.4.1.318.25NodebaseFanFailureSEVERE: Base module fan needs repair
1.3.6.1.4.1.318.26NodebatteryPackCommLostSEVERE: Check installation of external battery packs signal cable
1.3.6.1.4.1.318.27NodebatteryPackCommEstablishedINFORMATIONAL: UPS is communicating with the external battery packs.
1.3.6.1.4.1.318.28NodecalibrationStartINFORMATIONAL: A battery calibration test has been initiated on the UPS.
1.3.6.1.4.1.318.29NoderestartAgentINFORMATIONAL: Agent restarting as commanded by manager.
1.3.6.1.4.1.318.30NodeupsTurnedOnINFORMATIONAL: A UPS is turned on.
1.3.6.1.4.1.318.31NodesmartAvrReducingWARNING: The UPS is reducing the line voltage via SmartTrim(TM).
1.3.6.1.4.1.318.32NodecodeAuthenticationDoneINFORMATIONAL: Authentication on agent code image is done.
1.3.6.1.4.1.318.33NodeupsOverloadClearedINFORMATIONAL: The overload condition has been cleared.
1.3.6.1.4.1.318.34NodesmartBoostOffINFORMATIONAL: The UPS has returned from SmartBoost(TM).
1.3.6.1.4.1.318.35NodesmartAvrReducingOffINFORMATIONAL: The UPS has returned from SmartTrim(TM).
1.3.6.1.4.1.318.36NodeupsBatteryReplacedINFORMATIONAL: A bad battery fault has been cleared.
1.3.6.1.4.1.318.37NodecalibrationEndINFORMATIONAL: The UPS has finished calibrating.
1.3.6.1.4.1.318.38NodedischargeClearedINFORMATIONAL: A UPS discharge condition has been cleared.
1.3.6.1.4.1.318.39NodegracefulShutdownINFORMATIONAL: A graceful shutdown has been initiated.
1.3.6.1.4.1.318.41NodeoutletOnWARNING: The specified PDU outlet has turned on. If sPDUOutletControlIndex equals zero, then all outlets have turned on.
1.3.6.1.4.1.318.42NodeoutletOffWARNING: The specified PDU outlet has turned off. If sPDUOutletControlIndex equals zero, then all outlets have turned off.
1.3.6.1.4.1.318.43NodeoutletRebootWARNING: The specified PDU outlet has rebooted. If sPDUOutletControlIndex equals zero, then all outlets have rebooted.
1.3.6.1.4.1.318.44NodeconfigChangeSNMPWARNING: The SNMP configuration has been changed.
1.3.6.1.4.1.318.45NodeconfigChangeOutletWARNING: The specified PDU outlet has changed configuration. If sPDUOutletConfigIndex equals zero, then the Master outlet has changed configuration.
1.3.6.1.4.1.318.46NodeaccessViolationConsoleWARNING: Someone has attempted to login via the console with the incorrect password.
1.3.6.1.4.1.318.47NodeaccessViolationHTTPWARNING: Someone has attempted to login via HTTP with the incorrect password.
1.3.6.1.4.1.318.48NodepasswordChangeWARNING: The password for the device has been changed.
1.3.6.1.4.1.318.49NodebadVoltageWARNING: The output voltage is not within acceptable range.
1.3.6.1.4.1.318.50NodebadVoltageClearedINFORMATIONAL: The output voltage has returned to an acceptable level.
1.3.6.1.4.1.318.51NodechargerFailureWARNING: The battery charger has failed.
1.3.6.1.4.1.318.52NodechargerFailureClearedINFORMATIONAL: The battery charger failure condition has been cleared.
1.3.6.1.4.1.318.53NodebatteryOverTemperatureWARNING: The battery temperature threshold has been violated.
1.3.6.1.4.1.318.54NodebatteryOverTemperatureClearedINFORMATIONAL: The battery over temperature has been cleared.
1.3.6.1.4.1.318.55NodesmartRelayFaultWARNING: SmartBoost(TM) or SmartTrim(TM) relay fault.
1.3.6.1.4.1.318.56NodesmartRelayFaultClearedINFORMATIONAL: SmartBoost(TM) or SmartTrim(TM) relay fault has been cleared.
1.3.6.1.4.1.318.57NodehumidityThresholdViolation1SEVERE: Probe 1 humidity threshold violated. The first variable is the current humidity.
1.3.6.1.4.1.318.58NodehumidityThresholdViolationCleared1INFORMATIONAL: An Environmental Monitor humidity threshold violation has been cleared on probe 1.
1.3.6.1.4.1.318.59NodetemperatureThresholdViolation1SEVERE: An Environmental Monitor temperature threshold has been violated on probe 1. The first variable is the current temperature.
1.3.6.1.4.1.318.60NodetemperatureThresholdViolationCleared1INFORMATIONAL: An Environmental Monitor temperature threshold violation has been cleared on probe 1.
1.3.6.1.4.1.318.61NodehumidityThresholdViolation2SEVERE: An Environmental Monitor humidity threshold has been violated on probe 2. The first variable is the current humidity.
1.3.6.1.4.1.318.62NodehumidityThresholdViolationCleared2INFORMATIONAL: An Environmental Monitor humidity threshold violation has been cleared on probe 2.
1.3.6.1.4.1.318.63NodetemperatureThresholdViolation2SEVERE: An Environmental Monitor temperature threshold has been violated on probe 2. The first variable is the current temperature.
1.3.6.1.4.1.318.64NodetemperatureThresholdViolationCleared2INFORMATIONAL: An Environmental Monitor temperature threshold violation has been cleared on probe 2.
1.3.6.1.4.1.318.65NodemupsCommunicationEstablishedINFORMATIONAL: Communication with the Environmental Monitor has been established.
1.3.6.1.4.1.318.66NodemupsCommunicationLostSEVERE: Communication to the Environmental Monitor has been lost. Steps to reestablish communication are in progress.
1.3.6.1.4.1.318.67NodebatteryIncreaseINFORMATIONAL: The number of batteries has increased.
1.3.6.1.4.1.318.68NodebatteryDecreaseINFORMATIONAL: The number of batteries has decreased.
1.3.6.1.4.1.318.69NodepowerModuleIncreaseINFORMATIONAL: The number of power modules has increased.
1.3.6.1.4.1.318.70NodepowerModuleDecreaseINFORMATIONAL: The number of power modules has decreased.
1.3.6.1.4.1.318.71NodeintelligenceModuleInsertedINFORMATIONAL: An intelligence module has been inserted.
1.3.6.1.4.1.318.72NodeintelligenceModuleRemovedINFORMATIONAL: An intelligence module has been removed.
1.3.6.1.4.1.318.73NoderintelligenceModuleInsertedINFORMATIONAL: A redundant intelligence module has been inserted.
1.3.6.1.4.1.318.74NoderintelligenceModuleRemovedINFORMATIONAL: A redundant intelligence module has been removed.
1.3.6.1.4.1.318.75NodeextBatteryFrameInceaseINFORMATIONAL: An external battery frame has been added.
1.3.6.1.4.1.318.76NodeextBatteryFrameDecreaseINFORMATIONAL: An external battery frame has been removed.
1.3.6.1.4.1.318.77NodeabnormalConditionSEVERE: An abnormal condition has been detected. The first variable is the fault condition.
1.3.6.1.4.1.318.78NodeabnormalConditionClearedINFORMATIONAL: An abnormal condition has been cleared. The first variable is the fault condition.
1.3.6.1.4.1.318.79NodedeviceStatusChangeINFORMATIONAL: The status of the device being monitored has changed.
1.3.6.1.4.1.318.80NodenoBatteriesWARNING: The UPS has no batteries attached.
1.3.6.1.4.1.318.81NodenoBatteriesClearedINFORMATIONAL: The UPS's batteries have been attached.
1.3.6.1.4.1.318.82NodeuserAddedINFORMATIONAL: A new user has been added.
1.3.6.1.4.1.318.83NodeuserDeletedINFORMATIONAL: A user has been deleted.
1.3.6.1.4.1.318.84NodeuserModifiedINFORMATIONAL: A user has been modified.
1.3.6.1.4.1.318.85NodemsvmCommunicationEstablishedINFORMATIONAL: Communications with the MasterSwitch VM has been established.
1.3.6.1.4.1.318.86NodemsvmCommunicationLostSEVERE: Communications with the MasterSwitch VM has been lost.
1.3.6.1.4.1.318.87NodemsvmOverloadSEVERE: The MasterSwitch VM in an overload condition.
1.3.6.1.4.1.318.88NodemsvmOverloadClearedINFORMATIONAL: The overload condition on the MasterSwitch VM has been cleared.
1.3.6.1.4.1.318.89NodemsvmOutletOnINFORMATIONAL: An outlet on the MasterSwitch VM has turned on.
1.3.6.1.4.1.318.90NodemsvmOutletOffINFORMATIONAL: An outlet on the MasterSwitch VM has turned off.
1.3.6.1.4.1.318.91NodemsvmDeviceConfigChangeINFORMATIONAL: A device configuration change has been made on a MasterSwitch VM.
1.3.6.1.4.1.318.92NodemsvmOutletConfigChangeINFORMATIONAL: An outlet configuration change has been made on a MasterSwitch VM.
1.3.6.1.4.1.318.93NodemsvmLowLoadINFORMATIONAL: The MasterSwitch VM has violated the low load threshold.
1.3.6.1.4.1.318.94NodemsvmLowLoadClearedINFORMATIONAL: The low load condition on the MasterSwitch VM has been cleared.
1.3.6.1.4.1.318.95NodemsvmNearOverloadSEVERE: The MasterSwitch VM is approaching an overload condition.
1.3.6.1.4.1.318.96NodemsvmNearOverloadClearedINFORMATIONAL: The near overload condition on the MasterSwitch VM has been cleared.
1.3.6.1.4.1.318.97NodemsvmPowerSupplyStatusChangeWARNING: The power supply status of the MasterSwitch VM has changed.
1.3.6.1.4.1.318.98NodemspCommunicationEstablishedINFORMATIONAL: Communications with the MasterSwitch plus has been established.
1.3.6.1.4.1.318.99NodemspCommunicationLostSEVERE: Communications with the MasterSwitch plus has been lost.
1.3.6.1.4.1.318.100NodemspOutletOnINFORMATIONAL: An outlet on the MasterSwitch plus has turned on.
1.3.6.1.4.1.318.101NodemspOutletOffINFORMATIONAL: An outlet on the MasterSwitch plus has turned off.
1.3.6.1.4.1.318.102NodemspDeviceConfigChangeINFORMATIONAL: A device configuration change has been made on a MasterSwitch plus.
1.3.6.1.4.1.318.103NodemspOutletConfigChangeINFORMATIONAL: An outlet configuration change has been made on a MasterSwitch plus.
1.3.6.1.4.1.318.104NodersSourceSwitchedINFORMATIONAL: The Redundant Switch has switched source. The first variable is an integer representing the current source: 0=A, 1=B. The second variable is the…
1.3.6.1.4.1.318.105NodersLostRedundancySEVERE: The Redundant Switch has lost redundancy. The first variable is an integer representing the source which is no longer available: 0=A, 1=B. The second v…
1.3.6.1.4.1.318.106NodersRedundancyRestoredINFORMATIONAL: Redundancy has been restored to the Redundant Switch . The first variable is an integer representing the source which has been restored: 0=A, 1=…
1.3.6.1.4.1.318.107NodersConfigChangeINFORMATIONAL: A configuration change has been made on a Redundant Switch.
1.3.6.1.4.1.318.108NodersCommunicationEstablishedINFORMATIONAL: Communications with the Redundant Switch has been established.
1.3.6.1.4.1.318.109NodersCommunicationLostSEVERE: Communications with the Redundant Switch has been lost.
1.3.6.1.4.1.318.110NodedcCommunicationEstablishedINFORMATIONAL: Communications with the DC power plant has been established.
1.3.6.1.4.1.318.111NodedcCommunicationLostSEVERE: Communications with the DC power plant has been lost.
1.3.6.1.4.1.318.112NodedcPINChangedINFORMATIONAL: The active PIN on the DC controller has been changed.
1.3.6.1.4.1.318.113NodedcMajorAlarmSEVERE: A Major alarm is active in the DC power plant.
1.3.6.1.4.1.318.114NodedcMajorAlarmClearedINFORMATIONAL: A Major alarm is no longer active in the DC power plant.
1.3.6.1.4.1.318.115NodedcMinorAlarmWARNING: A Minor alarm is active in the DC power plant.
1.3.6.1.4.1.318.116NodedcMinorAlarmClearedINFORMATIONAL: A Minor alarm is no longer active in the DC power plant.
1.3.6.1.4.1.318.117NodedcOutputRelayOnWARNING: An output relay for the powerplant has been activated (state changed to on). The first variable is an integer representing the output relay number tha…
1.3.6.1.4.1.318.118NodedcOutputRelayOffINFORMATIONAL: An output relay for the powerplant has been deactivated (state changed to off). The first variable is an integer representing the output relay n…
1.3.6.1.4.1.318.119NodedcInputRelayOnWARNING: An input relay for the powerplant has been activated (state changed to on). The first variable is an integer representing the input relay number that …
1.3.6.1.4.1.318.120NodedcInputRelayOffINFORMATIONAL: An input relay for the powerplant has been deactivated (state changed to off). The first variable is an integer representing the input relay num…
1.3.6.1.4.1.318.121NodelogicPowerSuppliesIncreasedINFORMATIONAL: The number of system power supplies has increased.
1.3.6.1.4.1.318.122NodelogicPowerSuppliesDecreasedINFORMATIONAL: The number of system power supplies has decreased.
1.3.6.1.4.1.318.123NodeexternalSwitchGearClosedINFORMATIONAL: External Switch Gear closed.
1.3.6.1.4.1.318.124NodeexternalSwitchGearOpenedINFORMATIONAL: External Switch Gear opened.
1.3.6.1.4.1.318.125NodegeneralDeviceEventINFORMATIONAL: APC Device event.
1.3.6.1.4.1.318.126NodeatsSourceSwitchedINFORMATIONAL: The Automatic Transfer Switch has switched source. The first variable is an integer representing the current source: 0=A, 1=B. The second variab…
1.3.6.1.4.1.318.127NodeatsLostRedundancySEVERE: The Automatic Transfer Switch has lost redundancy. The first variable is an integer representing the source which is no longer available: 0=A, 1=B. The…
1.3.6.1.4.1.318.128NodeatsRedundancyRestoredINFORMATIONAL: Redundancy has been restored to the Automatic Transfer Switch . The first variable is an integer representing the source which has been restored…
1.3.6.1.4.1.318.129NodeatsConfigChangeINFORMATIONAL: A configuration change has been made on the Automatic Transfer Switch. The first variable is an integer representing the configuration setting w…
1.3.6.1.4.1.318.130NodeatsCommunicationEstablishedINFORMATIONAL: Communications with the Automatic Transfer Switch has been established.
1.3.6.1.4.1.318.131NodeatsCommunicationLostSEVERE: Communications with the Automatic Transfer Switch has been lost.
1.3.6.1.4.1.318.132NodeatsOverCurrentSEVERE: Output Current has exceeded threshold. This is same as atsOverload Trap for phase or total in case banked units
1.3.6.1.4.1.318.133NodeatsOverCurrentClearedINFORMATIONAL: Output Current has returned below threshold.This is same as atsOverloadCleared Trap for phase or total in case banked units
1.3.6.1.4.1.318.134NodeatsPowerSupplyFailureSEVERE: The Automatic Transfer Switch Power Supply has failed. The first variable is an integer representing the Power Supply which has failed: 0 = Source A 24…
1.3.6.1.4.1.318.135NodeatsPowerSupplyFailureClearedINFORMATIONAL: The Automatic Transfer Power Supply Failure Cleared. The first variable is an integer representing the Power Supply which has cleared: 0 = Sourc…
1.3.6.1.4.1.318.136NodedcMainsFailAlarmWARNING: A Mains Fail alarm is active in the DC power plant.
1.3.6.1.4.1.318.137NodedcMainsFailAlarmClearedINFORMATIONAL: Mains Fail alarm is no longer active in the DC power plant.
1.3.6.1.4.1.318.138NodedcFanFailAlarmWARNING: A Fan Fail alarm is active in the DC power plant.
1.3.6.1.4.1.318.139NodedcFanFailAlarmClearedINFORMATIONAL: A Fan Fail alarm is no longer active in the DC power plant.
1.3.6.1.4.1.318.140NodedcRectifierOvertempAlarmWARNING: Rect. Overtemp alarm is active in the power plant.
1.3.6.1.4.1.318.141NodedcRectifierOvertempAlarmClearedINFORMATIONAL: Rect. Overtemp alarm is no longer active in the power plant.
1.3.6.1.4.1.318.142NodedcCurrentLimitAlarmWARNING: A Current Limit alarm is active in the power plant.
1.3.6.1.4.1.318.143NodedcCurrentLimitAlarmClearedINFORMATIONAL: Current Limit alarm is no longer active in the power plant.
1.3.6.1.4.1.318.144NodedcRectifierFailAlarmWARNING: A Rect. Fail alarm is active in the power plant.
1.3.6.1.4.1.318.145NodedcRectifierFailAlarmClearedINFORMATIONAL: Rect. Fail alarm is no longer active in the power plant.
1.3.6.1.4.1.318.146NodedcMultRectFailAlarmWARNING: Multiple Rect. Fail alarm is active in the powerplant.
1.3.6.1.4.1.318.147NodedcMultRectFailAlarmClearedINFORMATIONAL: Multiple Rect Fail alarm is no longer active in the powerplant.
1.3.6.1.4.1.318.148NodedcBatteryBreakerAlarmWARNING: Batt. Breaker alarm is active in the power plant.
1.3.6.1.4.1.318.149NodedcBatteryBreakerAlarmClearedINFORMATIONAL: Batt. Breaker alarm is no longer active in the power plant.
1.3.6.1.4.1.318.150NodedcRectifierOVPAlarmWARNING: A Rect. OVP alarm is active in the power plant.
1.3.6.1.4.1.318.151NodedcRectifierOVPAlarmClearedINFORMATIONAL: A Rect. OVP alarm is no longer active in the power plant.
1.3.6.1.4.1.318.152NodedcLVDImminentAlarmWARNING: A LVD Imminent alarm is active in the powerplant.
1.3.6.1.4.1.318.153NodedcLVDImminentAlarmClearedINFORMATIONAL: A LVD Imminent alarm is no longer active in the powerplant.
1.3.6.1.4.1.318.154NodedcFuseCBAlarmWARNING: A Fuse/CB alarm is active in the DC power plant.
1.3.6.1.4.1.318.155NodedcFuseCBAlarmClearedINFORMATIONAL: A Fuse/CB alarm is no longer active in the DC power plant.
1.3.6.1.4.1.318.156NodedcBatteryTestFailWARNING: A Battery Test failed in the DC power plant.
1.3.6.1.4.1.318.157NodedcTemperatureAlarmWARNING: A Temperature is active in the power plant.
1.3.6.1.4.1.318.158NodedcTemperatureAlarmClearedINFORMATIONAL: A Temperature alarm is no longer active in the power plant.
1.3.6.1.4.1.318.159NodedcHumidityAlarmWARNING: A Humidity alarm is active in the DC power plant.
1.3.6.1.4.1.318.160NodedcHumidityAlarmClearedINFORMATIONAL: A Humidity alarm is no longer active in the DC power plant.
1.3.6.1.4.1.318.161NodedcBBCommunicationEstablishedINFORMATIONAL: Power plant bridging board communications established.
1.3.6.1.4.1.318.162NodedcBBCommunicationLostSEVERE: Power plant bridging board communications lost.
1.3.6.1.4.1.318.163NodeiemHighTempThresholdViolationSEVERE: High temperature threshold violated on Integrated Environmental Monitor probe. The first variable is the current temperature. The second variable is th…
1.3.6.1.4.1.318.164NodeiemHighTempThresholdViolationClearedINFORMATIONAL: High temperature threshold violated on Integrated Environmental Monitor probe has been cleared. The first variable is the probe number. The seco…
1.3.6.1.4.1.318.165NodeiemLowTempThresholdViolationSEVERE: Low temperature threshold violated on integrated probe. The first variable is the current temperature. The second variable is the temperature scale. Th…
1.3.6.1.4.1.318.166NodeiemLowTempThresholdViolationClearedINFORMATIONAL: Low temperature threshold violated on integrated probe has been cleared. The first variable is the probe number. The second variable is the prob…
1.3.6.1.4.1.318.167NodeiemHighHumidThresholdViolationSEVERE: High humidity threshold violated on integrated probe. The first variable is the current humidity. The second variable is the probe number. The third va…
1.3.6.1.4.1.318.168NodeiemHighHumidThresholdViolationClearedINFORMATIONAL: High humidity threshold violated on integrated probe cleared. The first variable is the probe number. The second variable is the probe name.
1.3.6.1.4.1.318.169NodeiemLowHumidThresholdViolationSEVERE: Low humidity threshold violated on integrated probe. The first variable is the current humidity. The second variable is the probe number. The third var…
1.3.6.1.4.1.318.170NodeiemLowHumidThresholdViolationClearedINFORMATIONAL: Low humidity threshold violated on integrated probe cleared. The first variable is the probe number. The second variable is the probe name.
1.3.6.1.4.1.318.171NodeiemProbeDisconnectedWARNING: The temperature/humidity probe on the Integrated Environmental Monitor has been disconnected. This trap is generated when a probe that has been in com…
1.3.6.1.4.1.318.172NodeiemProbeConnectedINFORMATIONAL: The temperature/humidity probe on the Integrated Environmental Monitor has been connected. This trap is generated when the Environmental Monitor…
1.3.6.1.4.1.318.173NodeiemContactFaultSEVERE: There is a contact fault on the Integrated Environmental Monitor. The first argument is the number of the contact. The second argument is the name of t…
1.3.6.1.4.1.318.174NodeiemContactFaultClearedINFORMATIONAL: The contact fault on the Integrated Environmental Monitor has been cleared. The first argument is the number of the contact. The second argument…
1.3.6.1.4.1.318.175NodeiemRelayFaultSEVERE: The output relay on the Integrated Environmental Monitor has switched to the fault state. The first argument is the number of the output relay. The sec…
1.3.6.1.4.1.318.176NodeiemRelayFaultClearedINFORMATIONAL: The fault condition on the output relay on the Integrated Environmental Monitor has cleared. The first argument is the number of the output rela…
1.3.6.1.4.1.318.177NodebmBatManCommEstabINFORMATIONAL: Serial Communications Established with Battery Manager.
1.3.6.1.4.1.318.178NodebmBatManCommLostSEVERE: Serial Communications Lost with Battery Manager.
1.3.6.1.4.1.318.179NodebmBatManKneeAlarmSEVERE: Battery Voltage Knee Threshold Alarm Detected.
1.3.6.1.4.1.318.180NodebmBatManKneeAlarmClearedINFORMATIONAL: Battery Voltage Knee Threshold Alarm Cleared.
1.3.6.1.4.1.318.181NodebmBatManChargerAlarmWARNING: Charger Alarm Detected.
1.3.6.1.4.1.318.182NodebmBatManChargerAlarmClearedINFORMATIONAL: Charger Alarm Cleared.
1.3.6.1.4.1.318.183NodebmBatManBatteryAlarmWARNING: Battery Alarm Detected.
1.3.6.1.4.1.318.184NodebmBatManBatteryAlarmClearedINFORMATIONAL: Battery Alarm Cleared.
1.3.6.1.4.1.318.185NodebmBatManEnvironmentAlarmWARNING: Environment Alarm Detected.
1.3.6.1.4.1.318.186NodebmBatManEnvironmentAlarmClearedINFORMATIONAL: Environment Alarm Cleared.
1.3.6.1.4.1.318.187NodebmBatManMaintenanceAlarmINFORMATIONAL: Maintenance Alarm Detected.
1.3.6.1.4.1.318.188NodebmBatManMaintenanceAlarmClearedINFORMATIONAL: Maintenance Alarm Cleared.
1.3.6.1.4.1.318.189NodepduCommunicationEstablishedINFORMATIONAL: Communication Established. The first argument is the serial number. The second argument is the device name.
1.3.6.1.4.1.318.190NodepduCommunicationLostSEVERE: Communication Lost. The first argument is the serial number. The second argument is the device name.
1.3.6.1.4.1.318.191NodepduUtilityLineUndervoltageSEVERE: Utility Line Undervoltage. The first argument is the serial number. The second argument is the device name. The third argument is the phase number.
1.3.6.1.4.1.318.192NodepduUtilityLineUndervoltageClearedINFORMATIONAL: Utility Line Undervoltage Cleared. The first argument is the serial number. The second argument is the device name. The third argument is the ph…
1.3.6.1.4.1.318.193NodepduUtilityLineOvervoltageSEVERE: Utility Line Overvoltage. The first argument is the serial number. The second argument is the device name. The third argument is the phase number.
1.3.6.1.4.1.318.194NodepduUtilityLineOvervoltageClearedINFORMATIONAL: Utility Line Overvoltage Cleared. The first argument is the serial number. The second argument is the device name. The third argument is the pha…
1.3.6.1.4.1.318.195NodepduGroundOvercurrentSEVERE: Ground Overcurrent. The first argument is the serial number. The second argument is the device name.
1.3.6.1.4.1.318.196NodepduGroundOvercurrentClearedINFORMATIONAL: Ground Overcurrent Cleared. The first argument is the serial number. The second argument is the device name.
1.3.6.1.4.1.318.197NodepduCircuitPanelInputUndervoltageSEVERE: Circuit Panel Input Undervoltage. The first argument is the serial number. The second argument is the device name. The third argument is the phase numb…
1.3.6.1.4.1.318.198NodepduCircuitPanelInputUndervoltageClearedINFORMATIONAL: Circuit Panel Input Undervoltage Cleared. The first argument is the serial number. The second argument is the device name. The third argument is…
1.3.6.1.4.1.318.199NodepduCircuitPanelInputOvervoltageSEVERE: Circuit Panel Input Overvoltage. The first argument is the serial number. The second argument is the device name. The third argument is the phase numbe…
1.3.6.1.4.1.318.200NodepduCircuitPanelInputOvervoltageClearedINFORMATIONAL: Circuit Panel Input Overvoltage Cleared. The first argument is the serial number. The second argument is the device name. The third argument is …
1.3.6.1.4.1.318.201NodepduCircuitPanelInputUndercurrentSEVERE: Circuit Panel Input Undercurrent. The first argument is the serial number. The second argument is the device name. The third argument is the phase numb…
1.3.6.1.4.1.318.202NodepduCircuitPanelInputUndercurrentClearedINFORMATIONAL: Circuit Panel Input Undercurrent Cleared. The first argument is the serial number. The second argument is the device name. The third argument is…
1.3.6.1.4.1.318.203NodepduCircuitPanelInputOvercurrentSEVERE: Circuit Panel Input Overcurrent. The first argument is the serial number. The second argument is the device name. The third argument is the phase numbe…
1.3.6.1.4.1.318.204NodepduCircuitPanelInputOvercurrentClearedINFORMATIONAL: Circuit Panel Input Overcurrent Cleared. The first argument is the serial number. The second argument is the device name. The third argument is …
1.3.6.1.4.1.318.205NodepduCircuitPanelFrequencyOutOfRangeSEVERE: Circuit Panel Input Frequency Out Of Range. The first argument is the serial number. The second argument is the device name.
1.3.6.1.4.1.318.206NodepduCircuitPanelFrequencyOutofRangeClearedINFORMATIONAL: Circuit Panel Input Frequency No Longer Out Of Range. The first argument is the serial number. The second argument is the device name.
1.3.6.1.4.1.318.207NodepduCircuitPanelNeutralOvercurrentSEVERE: Circuit Panel Input Neutral Overcurrent. The first argument is the serial number. The second argument is the device name.
1.3.6.1.4.1.318.208NodepduCircuitPanelNeutralOvercurrentClearedINFORMATIONAL: Circuit Panel Input Neutral Overcurrent Cleared. The first argument is the serial number. The second argument is the device name.
1.3.6.1.4.1.318.209NodepduSystemOffSEVERE: PDU System Off. The first argument is the serial number. The second argument is the device name.
1.3.6.1.4.1.318.210NodepduOnBatteryModeSEVERE: PDU is in On Battery Mode. The first argument is the serial number. The second argument is the device name.
1.3.6.1.4.1.318.211NodepduMaintenanceBypassModeINFORMATIONAL: PDU is in Maintenance Bypass Mode. The first argument is the serial number. The second argument is the device name.
1.3.6.1.4.1.318.212NodepduAtypicalBypassModeWARNING: PDU is in Atypical Bypass Mode. The first argument is the serial number. The second argument is the device name.
1.3.6.1.4.1.318.213NodepduNoPanelFeedModeSEVERE: PDU is in No Panel Feed Mode. The first argument is the serial number. The second argument is the device name.
1.3.6.1.4.1.318.214NodepduUpsOperationModeINFORMATIONAL: PDU is in Ups Operation Mode. The first argument is the serial number. The second argument is the device name.
1.3.6.1.4.1.318.215NodepduForcedBypassModeWARNING: PDU is in Forced Bypass Mode. The first argument is the serial number. The second argument is the device name.
1.3.6.1.4.1.318.216NodepduInputTransformerOverTemperatureSEVERE: Input Transformer Over Temperature. The first argument is the serial number. The second argument is the device name.
1.3.6.1.4.1.318.217NodepduInputTransformerOverTemperatureClearedINFORMATIONAL: Input Transformer Over Temperature Cleared. The first argument is the serial number. The second argument is the device name.
1.3.6.1.4.1.318.218NodepduUPSInputVoltageLostSEVERE: UPS Input Voltage phase-N Lost. The first argument is the serial number. The second argument is the device name. The third argument is the phase number.
1.3.6.1.4.1.318.219NodepduUPSInputVoltageRestoredINFORMATIONAL: UPS Input Voltage phase-N Restored. The first argument is the serial number. The second argument is the device name. The third argument is the p…
1.3.6.1.4.1.318.220NodepduContactFaultSEVERE: A contact closure in the PDU is in an abnormal position. The first argument is the serial number. The second argument is the device name. The third arg…
1.3.6.1.4.1.318.221NodepduContactFaultClearedINFORMATIONAL: A contact closure in the PDU is in a normal position. The first argument is the serial number. The second argument is the device name. The third…
1.3.6.1.4.1.318.222NoderPDUBankPhaseLowLoadWARNING: A bank or phase on the Rack PDU has violated the low load threshold. The first argument is the serial number. The second argument is the device name. …
1.3.6.1.4.1.318.223NoderPDUBankPhaseLowLoadClearedINFORMATIONAL: The bank or phase low load condition on a Rack PDU has been cleared. The first argument is the serial number. The second argument is the device …
1.3.6.1.4.1.318.224NoderPDUBankPhaseNearOverloadWARNING: A bank or phase of the Rack PDU is near an overload condition. The first argument is the serial number. The second argument is the device name. The th…
1.3.6.1.4.1.318.225NoderPDUBankPhaseNearOverloadClearedINFORMATIONAL: The bank or phase near overload condition on a Rack PDU has been cleared. The first argument is the serial number. The second argument is the de…
1.3.6.1.4.1.318.226NoderPDUBankPhaseOverloadSEVERE: A bank or phase of the Rack PDU is in an overload condition. The first argument is the serial number. The second argument is the device name. The third…
1.3.6.1.4.1.318.227NoderPDUBankPhaseOverloadClearedINFORMATIONAL: The bank or phase overload condition on a Rack PDU has been cleared. The first argument is the serial number. The second argument is the device …
1.3.6.1.4.1.318.228NodearuDeviceConfigChangeINFORMATIONAL: Remote ARU Device Configuration change. The first argument is the host device serial number. The second argument is the host device name. The th…
1.3.6.1.4.1.318.229NodermPDUCommunicationLostSEVERE: Communication Lost. The first argument is the serial number. The second argument is the device name.
1.3.6.1.4.1.318.230NodeemsCommunicationEstablishedINFORMATIONAL: Communication Established. The first argument is the serial number. The second argument is the device name.
1.3.6.1.4.1.318.231NodeemsCommunicationLostSEVERE: Communication Lost. The first argument is the serial number. The second argument is the device name.
1.3.6.1.4.1.318.232NodeemsProbeConnectedINFORMATIONAL: A probe has been connected to the EMS. The first argument is the host device serial number. The second argument is the host device name. The thi…
1.3.6.1.4.1.318.233NodeemsProbeDisconnectedSEVERE: A probe has been disconnected from the EMS. The first argument is the host device serial number. The second argument is the host device name. The third…
1.3.6.1.4.1.318.234NodeemsSensorConnectedINFORMATIONAL: A sensor has been connected to the EMS. The first argument is the host device serial number. The second argument is the host device name. The th…
1.3.6.1.4.1.318.235NodeemsSensorDisconnectedSEVERE: A sensor has been disconnected from the EMS. The first argument is the host device serial number. The second argument is the host device name. The thir…
1.3.6.1.4.1.318.236NodeemsSensorFaultSEVERE: A EMS sensor is in the fault condition. The first argument is the host device serial number. The second argument is the host device name. The third arg…
1.3.6.1.4.1.318.237NodeemsSensorFaultClearedINFORMATIONAL: A EMS sensor fault condition has cleared. The first argument is the host device serial number. The second argument is the host device name. The …
1.3.6.1.4.1.318.238NodeemsBeaconConnectedINFORMATIONAL: A beacon has been connected to the EMS. The first argument is the host device serial number. The second argument is the host device name.
1.3.6.1.4.1.318.239NodeemsBeaconDisconnectedSEVERE: A beacon has been disconnected from the EMS. The first argument is the host device serial number. The second argument is the host device name.
1.3.6.1.4.1.318.240NodeemsBeaconOnINFORMATIONAL: A EMS beacon has gone on. The first argument is the host device serial number. The second argument is the host device name.
1.3.6.1.4.1.318.241NodeemsBeaconOffINFORMATIONAL: A EMS beacon has gone off. The first argument is the host device serial number. The second argument is the host device name.
1.3.6.1.4.1.318.242NodeemsMajorAlarmSEVERE: A Major Alarm is present in the EMS. The first argument is the EMS serial number. The second argument is the EMS name.
1.3.6.1.4.1.318.243NodeemsMajorAlarmClearedINFORMATIONAL: A Major Alarm condition has been cleared in the EMS. The first argument is the EMS serial number. The second argument is the EMS name.
1.3.6.1.4.1.318.244NodeemsMinorAlarmSEVERE: A Minor Alarm is present in the EMS. The first argument is the EMS serial number. The second argument is the EMS name.
1.3.6.1.4.1.318.245NodeemsMinorAlarmClearedINFORMATIONAL: A Minor Alarm condition has been cleared in the EMS. The first argument is the EMS serial number. The second argument is the EMS name.
1.3.6.1.4.1.318.246NodeemsOutletStateAbnormalWARNING: An outlet on the EMS has changed to its abnormal state. The first argument is the host device serial number. The second argument is the host device na…
1.3.6.1.4.1.318.247NodeemsOutletStateNormalINFORMATIONAL: An outlet on the EMS has changed to its normal state. The first argument is the host device serial number. The second argument is the host devic…
1.3.6.1.4.1.318.248NodeemsInputContactStateAbnormalWARNING: An input contact on the EMS has changed to its abnormal state. The first argument is the host device serial number. The second argument is the host de…
1.3.6.1.4.1.318.249NodeemsInputContactStateNormalINFORMATIONAL: An input contact on the EMS has changed to its normal state. The first argument is the host device serial number. The second argument is the hos…
1.3.6.1.4.1.318.250NodeemsOutputRelayStateAbnormalWARNING: An output relay on the EMS has changed to its abnormal state. The first argument is the host device serial number. The second argument is the host dev…
1.3.6.1.4.1.318.251NodeemsOutputRelayStateNormalINFORMATIONAL: An output relay on the EMS has changed to its normal state. The first argument is the host device serial number. The second argument is the host…
1.3.6.1.4.1.318.252NodeemsDeviceConfigChangeINFORMATIONAL: A device configuration change has been made on the EMS. The first argument is the EMS serial number. The second argument is the EMS name.
1.3.6.1.4.1.318.253NodeenvHighTempThresholdViolationSEVERE: High temperature threshold violated on the probe. The first argument is the host device serial number. The second argument is the host device name. The…
1.3.6.1.4.1.318.254NodeenvHighTempThresholdViolationClearedINFORMATIONAL: High temperature threshold violation cleared on the probe. The first argument is the host device serial number. The second argument is the host …
1.3.6.1.4.1.318.255NodeenvLowTempThresholdViolationSEVERE: Low temperature threshold violated on the probe. The first argument is the host device serial number. The second argument is the host device name. The …
1.3.6.1.4.1.318.256NodeenvLowTempThresholdViolationClearedINFORMATIONAL: Low temperature threshold violation cleared on the probe. The first argument is the host device serial number. The second argument is the host d…
1.3.6.1.4.1.318.257NodeenvHighHumidityThresholdViolationSEVERE: High humidity threshold violated on the probe. The first argument is the host device serial number. The second argument is the host device name. The th…
1.3.6.1.4.1.318.258NodeenvHighHumidityThresholdViolationClearedINFORMATIONAL: High humidity threshold violation cleared on the probe. The first argument is the host device serial number. The second argument is the host dev…
1.3.6.1.4.1.318.259NodeenvLowHumidityThresholdViolationSEVERE: Low humidity threshold violated on the probe. The first argument is the host device serial number. The second argument is the host device name. The thi…
1.3.6.1.4.1.318.260NodeenvLowHumidityThresholdViolationClearedINFORMATIONAL: Low humidity threshold violation cleared on the probe. The first argument is the host device serial number. The second argument is the host devi…
1.3.6.1.4.1.318.266NoderPDUCommunicationEstablishedINFORMATIONAL: Communication with a Rack PDU has been established. The first argument is the serial number. The second argument is the device name.
1.3.6.1.4.1.318.267NoderPDUCommunicationLostSEVERE: Communication with a Rack PDU has been lost. The first argument is the serial number. The second argument is the device name.
1.3.6.1.4.1.318.268NoderPDUOutletOnINFORMATIONAL: An outlet on a Switched Rack PDU has turned on. The first argument is the serial number. The second argument is the device name. The third argum…
1.3.6.1.4.1.318.269NoderPDUOutletOffINFORMATIONAL: An outlet on a Switched Rack PDU has turned off. The first argument is the serial number. The second argument is the device name. The third argu…
1.3.6.1.4.1.318.270NoderPDUDeviceConfigChangeINFORMATIONAL: A device configuration change has been made on a Rack PDU. The first argument is the serial number. The second argument is the device name.
1.3.6.1.4.1.318.271NoderPDUOutletConfigChangeINFORMATIONAL: An outlet configuration change has been made on a Switched Rack PDU. The first argument is the serial number. The second argument is the device …
1.3.6.1.4.1.318.272NoderPDULowLoadWARNING: A Rack PDU has violated the low load threshold. The first argument is the serial number. The second argument is the device name. The third argument is…
1.3.6.1.4.1.318.273NoderPDULowLoadClearedINFORMATIONAL: The low load condition on a Rack PDU has been cleared. The first argument is the serial number. The second argument is the device name. The thir…
1.3.6.1.4.1.318.274NoderPDUNearOverloadWARNING: A Rack PDU is near an overload condition. The first argument is the serial number. The second argument is the device name. The third argument is the p…
1.3.6.1.4.1.318.275NoderPDUNearOverloadClearedINFORMATIONAL: The near overload condition on a Rack PDU has been cleared. The first argument is the serial number. The second argument is the device name. The…
1.3.6.1.4.1.318.276NoderPDUOverloadSEVERE: A Rack PDU is in an overload condition. The first argument is the serial number. The second argument is the device name. The third argument is the phas…
1.3.6.1.4.1.318.277NoderPDUOverloadClearedINFORMATIONAL: The overload condition on a Rack PDU has been cleared. The first argument is the serial number. The second argument is the device name. The thir…
1.3.6.1.4.1.318.278NoderPDUPowerSupply1FailSEVERE: Power Supply 1 on Rack PDU is in FAIL state. The first argument is the serial number. The second argument is the device name.
1.3.6.1.4.1.318.279NoderPDUPowerSupply1OkINFORMATIONAL: Power Supply 1 on Rack PDU is operating normally. The first argument is the serial number. The second argument is the device name.
1.3.6.1.4.1.318.280NoderPDUPowerSupply2FailSEVERE: Power Supply 2 on Rack PDU is in FAIL state. The first argument is the serial number. The second argument is the device name.
1.3.6.1.4.1.318.281NoderPDUPowerSupply2OkINFORMATIONAL: Power Supply 2 on Rack PDU is operating normally. The first argument is the serial number. The second argument is the device name.
1.3.6.1.4.1.318.282NoderPDUPhaseConfigChangeINFORMATIONAL: A phase configuration change has been made on a Rack PDU. The first argument is the serial number. The second argument is the device name. The t…
1.3.6.1.4.1.318.283NoderPDUCancelPendingCommandINFORMATIONAL: A cancel pending command has been made on a Switched Rack PDU. The first argument is the serial number. The second argument is the device name. …
1.3.6.1.4.1.318.284NodearuAlinkCommunicationEstablishedINFORMATIONAL: Remote ARU Communication Established. The first argument is the host device serial number. The second argument is the host device name. The thir…
1.3.6.1.4.1.318.285NodearuAlinkCommunicationLostSEVERE: Remote ARU Communication Lost. The first argument is the host device serial number. The second argument is the host device name. The third argument is …
1.3.6.1.4.1.318.286NodearuFanFailSEVERE: Remote ARU Fan Fail. The first argument is the host device serial number. The second argument is the host device name. The third argument is the ARU nu…
1.3.6.1.4.1.318.287NodearuFanFailClearedINFORMATIONAL: Remote ARU Fan Fail Cleared. The first argument is the host device serial number. The second argument is the host device name. The third argumen…
1.3.6.1.4.1.318.288NodearuSmokeAlarmSEVERE: Remote ARU Smoke Alarm. The first argument is the host device serial number. The second argument is the host device name. The third argument is the ARU…
1.3.6.1.4.1.318.289NodearuSmokeAlarmClearedINFORMATIONAL: Remote ARU Smoke Alarm Cleared. The first argument is the host device serial number. The second argument is the host device name. The third argu…
1.3.6.1.4.1.318.290NodearuHighTemperatureAlarmWARNING: ARU Exhaust temperature has exceeded the override threshold and the ARU has increased fan speed to maintain a safe environment in the rack. The first …
1.3.6.1.4.1.318.291NodearuHighTemperatureAlarmClearedINFORMATIONAL: ARU temperature override state has been cleared. The first argument is the host device serial number. The second argument is the host device nam…
1.3.6.1.4.1.318.292NodearuExhaustTemperatureAlarmSEVERE: ARU Extreme Exhaust Temperature Alarm. The ARU is unable to control the temperature within the rack The first argument is the host device serial number…
1.3.6.1.4.1.318.293NodearuExhaustTemperatureAlarmClearedINFORMATIONAL: Remote ARU Exhaust Temperature Alarm Cleared. The first argument is the host device serial number. The second argument is the host device name. …
1.3.6.1.4.1.318.294NodeenvAlinkCommunicationEstablishedINFORMATIONAL: Remote Probe Communication Established. The first argument is the host device serial number. The second argument is the host device name. The th…
1.3.6.1.4.1.318.295NodeenvAlinkCommunicationLostSEVERE: Remote Probe Communication Lost. The first argument is the host device serial number. The second argument is the host device name. The third argument i…
1.3.6.1.4.1.318.296NodeemsAlinkPowerOverloadSEVERE: Alink Power Overload. The first argument is the host device serial number. The second argument is the host device name.
1.3.6.1.4.1.318.297NodeemsAlinkPowerOverloadClearedINFORMATIONAL: Alink Power Overload Cleared. The first argument is the host device serial number. The second argument is the host device name.
1.3.6.1.4.1.318.298NodeupsOutletGroupTurnedOnINFORMATIONAL: The specified Outlet Group turned on.
1.3.6.1.4.1.318.299NodeupsOutletGroupTurnedOffWARNING: The specified Outlet Group turned off.
1.3.6.1.4.1.318.300NodesmwCriticalConditionSEVERE: A Symmetra MW UPS critical condition has been detected. The first variable is the fault condition.
1.3.6.1.4.1.318.301NodesmwCriticalConditionClearedINFORMATIONAL: A Symmetra MW UPS critical condition has been cleared. The first variable is the fault condition.
1.3.6.1.4.1.318.302NodesmwWarningConditionWARNING: A Symmetra MW UPS warning condition has been detected. The first variable is the fault condition.
1.3.6.1.4.1.318.303NodesmwWarningConditionClearedWARNING: A Symmetra MW UPS warning condition has been cleared. The first variable is the fault condition.
1.3.6.1.4.1.318.304NodesmwInformationalConditionINFORMATIONAL: A Symmetra MW UPS informational condition has been detected. The first variable is the fault condition.
1.3.6.1.4.1.318.305NodesmwInformationalConditionClearedINFORMATIONAL: A Symmetra MW UPS informational condition has been cleared. The first variable is the fault condition.
1.3.6.1.4.1.318.306NodeairCriticalConditionSEVERE: An Air critical condition was detected. The first variable is the error condition text message. The second variable is the error number.
1.3.6.1.4.1.318.307NodeairCriticalConditionClearedINFORMATIONAL: An Air critical condition was cleared. The first variable is the error condition text message. The second variable is the error number.
1.3.6.1.4.1.318.308NodeairWarningConditionWARNING: An Air warning condition was detected. The first variable is the error condition text message. The second variable is the error number.
1.3.6.1.4.1.318.309NodeairWarningConditionClearedWARNING: An Air warning condition was cleared. The first variable is the error condition text message. The second variable is the error number.
1.3.6.1.4.1.318.310NodeairInformationalConditionINFORMATIONAL: An Air informational condition was detected. The first variable is the error condition text message. The second variable is the error number.
1.3.6.1.4.1.318.311NodeairInformationalConditionClearedINFORMATIONAL: An Air informational condition was cleared. The first variable is the error condition text message. The second variable is the error number.
1.3.6.1.4.1.318.312NodexPDUInputVoltageLowAlarmSEVERE: Three-phase input voltage to the device is outside the specified limits. The first argument is the host device serial number. The second argument is th…
1.3.6.1.4.1.318.313NodexPDUInputVoltageLowAlarmClearedINFORMATIONAL: Three-phase input voltage to the device is back within the specified limits. The first argument is the host device serial number. The second arg…
1.3.6.1.4.1.318.314NodexPDUInputVoltageHighAlarmSEVERE: Three-phase input voltage to the device is outside the specified limits. The first argument is the host device serial number. The second argument is th…
1.3.6.1.4.1.318.315NodexPDUInputVoltageHighAlarmClearedINFORMATIONAL: Three-phase input voltage to the device is back within the specified limits. The first argument is the host device serial number. The second arg…
1.3.6.1.4.1.318.316NodexPDUBypassVoltageLowAlarmSEVERE: Three-phase bypass input voltage to the device is outside the specified limits. The first argument is the host device serial number. The second argumen…
1.3.6.1.4.1.318.317NodexPDUBypassVoltageLowAlarmClearedINFORMATIONAL: Three-phase bypass input voltage to the device is back within the specified limits. The first argument is the host device serial number. The sec…
1.3.6.1.4.1.318.318NodexPDUBypassVoltageHighAlarmSEVERE: Three-phase bypass input voltage to the device is outside the specified limits. The first argument is the host device serial number. The second argumen…
1.3.6.1.4.1.318.319NodexPDUBypassVoltageHighAlarmClearedINFORMATIONAL: Three-phase bypass input voltage to the device is back within the specified limits. The first argument is the host device serial number. The sec…
1.3.6.1.4.1.318.320NodexPDUOutputVoltageLowAlarmSEVERE: The three-phase output voltage of the device is outside the specified limits. The first argument is the host device serial number. The second argument …
1.3.6.1.4.1.318.321NodexPDUOutputVoltageLowAlarmClearedINFORMATIONAL: The three-phase output voltage of the device is back within the specified limits. The first argument is the host device serial number. The secon…
1.3.6.1.4.1.318.322NodexPDUOutputVoltageHighAlarmSEVERE: The three-phase output voltage of the device is outside the specified limits. The first argument is the host device serial number. The second argument …
1.3.6.1.4.1.318.323NodexPDUOutputVoltageHighAlarmClearedINFORMATIONAL: The three-phase output voltage of the device is back within the specified limits. The first argument is the host device serial number. The secon…
1.3.6.1.4.1.318.324NodexPDUOutputCurrentLowAlarmSEVERE: The three-phase output load current of the device is outside the specified limits. The first argument is the host device serial number. The second argu…
1.3.6.1.4.1.318.325NodexPDUOutputCurrentLowAlarmClearedINFORMATIONAL: The three-phase output load current of the device is back within the specified limits. The first argument is the host device serial number. The …
1.3.6.1.4.1.318.326NodexPDUOutputCurrentHighAlarmSEVERE: The three-phase load current of the device is outside the specified limits. The first argument is the host device serial number. The second argument is…
1.3.6.1.4.1.318.327NodexPDUOutputCurrentHighAlarmClearedINFORMATIONAL: The three-phase output current of the device is back within the specified limits. The first argument is the host device serial number. The secon…
1.3.6.1.4.1.318.328NodexPDUOutputFrequencyAlarmSEVERE: The devices output frequency is outside the specified limits. The first argument is the host device serial number. The second argument is the host devi…
1.3.6.1.4.1.318.329NodexPDUOutputFrequencyAlarmClearedINFORMATIONAL: The devices output frequency is back within the specified limits. The first argument is the host device serial number. The second argument is th…
1.3.6.1.4.1.318.330NodexPDUSystemGroundCurrentAlarmSEVERE: The earth ground current of the device is over the specified limits. The first argument is the host device serial number. The second argument is the ho…
1.3.6.1.4.1.318.331NodexPDUSystemGroundCurrentAlarmClearedINFORMATIONAL: The earth ground current of the device is back within the specified limits. The first argument is the host device serial number. The second argu…
1.3.6.1.4.1.318.332NodexPDUInputContactStateAbnormalSEVERE: A user input contact on the device has changed to its abnormal state. The first argument is the host device serial number. The second argument is the h…
1.3.6.1.4.1.318.333NodexPDUInputContactStateNormalINFORMATIONAL: A user input contact on the device has changed to its normal state. The first argument is the host device serial number. The second argument is …
1.3.6.1.4.1.318.334NodexPDUOutputNeutralCurrentHighAlarmWARNING: The three-phase neutral current of the device is outside the specified limits. The first argument is the host device serial number. The second argumen…
1.3.6.1.4.1.318.335NodexPDUOutputNeutralCurrentHighAlarmClearedINFORMATIONAL: The output neutral current of the device is back within the specified limits. The first argument is the host device serial number. The second ar…
1.3.6.1.4.1.318.336NodexPDUCoolingFanAlarmSEVERE: The device's internal cooling fans have failed. The first argument is the host device serial number. The second argument is the host device name.
1.3.6.1.4.1.318.337NodexPDUCoolingFanAlarmClearedINFORMATIONAL: The device's cooling fans are now functioning properly. The first argument is the host device serial number. The second argument is the host dev…
1.3.6.1.4.1.318.338NodexPDUTransformerTempAlarmSEVERE: The device's isolation transformer is over temperature. The first argument is the host device serial number. The second argument is the host device nam…
1.3.6.1.4.1.318.339NodexPDUTransformerTempAlarmClearedINFORMATIONAL: The device's isolation transformer is no longer over temperature. The first argument is the host device serial number. The second argument is th…
1.3.6.1.4.1.318.340NodexPDUBranchCurrentLowAlarmWARNING: The current in a branch circuit is outside the limits specified for that branch circuit. The first argument is the host device serial number. The seco…
1.3.6.1.4.1.318.341NodexPDUBranchCurrentLowAlarmClearedINFORMATIONAL: The current in a branch circuit is back within the limits specified for that branch circuit. The first argument is the host device serial number…
1.3.6.1.4.1.318.342NodexPDUBranchCurrentHighAlarmWARNING: The current in a branch circuit is outside the limits specified for that branch circuit. The first argument is the host device serial number. The seco…
1.3.6.1.4.1.318.343NodexPDUBranchCurrentHighAlarmClearedINFORMATIONAL: The current in a branch circuit is back within the limits specified for that branch circuit. The first argument is the host device serial number…
1.3.6.1.4.1.318.344NodexPDUInternalCommErrorSEVERE: There is an internal communication error in the device. The first argument is the host device serial number. The second argument is the host device nam…
1.3.6.1.4.1.318.345NodeemsHardwareStateAbnormalSEVERE: The device's hardware is improperly configured and operating outside normal bounds for the hardware. This can be caused by improper devices being conne…
1.3.6.1.4.1.318.346NodeemsHardwareStateNormalINFORMATIONAL: The device's hardware is in its normal operational state. The first argument is the host device serial number.
1.3.6.1.4.1.318.347NodeceSevereConditionSEVERE: A Custom Event severe condition was detected. The first variable is the custom event text message. The second variable is the custom event number.
1.3.6.1.4.1.318.348NodeceSevereConditionClearedINFORMATIONAL: A Custom Event severe condition was cleared. The first variable is the custom event text message. The second variable is the custom event number.
1.3.6.1.4.1.318.349NodeceWarningConditionWARNING: A Custom Event warning condition was detected. The first variable is the custom event text message. The second variable is the custom event number.
1.3.6.1.4.1.318.350NodeceWarningConditionClearedINFORMATIONAL: A Custom Event warning condition was cleared. The first variable is the custom event text message. The second variable is the custom event numbe…
1.3.6.1.4.1.318.351NodeceInformationalConditionINFORMATIONAL: A Custom Event informational condition was detected. The first variable is the custom event text message. The second variable is the custom even…
1.3.6.1.4.1.318.352NodeceInformationalConditionClearedINFORMATIONAL: A Custom Event informational condition was cleared. The first variable is the custom event text message. The second variable is the custom event…
1.3.6.1.4.1.318.353NodeupsInternalOverTemperatureWARNING: The internal over temperature condition exists.
1.3.6.1.4.1.318.354NodeupsInternalOverTemperatureClearedINFORMATIONAL: The internal over temperature condition cleared.
1.3.6.1.4.1.318.355NodeupsMpuResetINFORMATIONAL: The MPU has been reset.
1.3.6.1.4.1.318.356NodeupsOutputSwitchClosedINFORMATIONAL: The Output Switch is closed.
1.3.6.1.4.1.318.357NodeupsOutputSwitchOpenedINFORMATIONAL: The Output Switch is open.
1.3.6.1.4.1.318.358NodeupsCalibrationStackChangedINFORMATIONAL: A calibration value in the stack was changed.
1.3.6.1.4.1.318.359NodeenvMaxTempThresholdViolationSEVERE: Max temperature threshold violated on the probe. The first argument is the host device serial number. The second argument is the host device name. The …
1.3.6.1.4.1.318.360NodeenvMaxTempThresholdViolationClearedINFORMATIONAL: Max temperature threshold violation cleared on the probe. The first argument is the host device serial number. The second argument is the host d…
1.3.6.1.4.1.318.361NodeenvMinTempThresholdViolationSEVERE: Min temperature threshold violated on the probe. The first argument is the host device serial number. The second argument is the host device name. The …
1.3.6.1.4.1.318.362NodeenvMinTempThresholdViolationClearedINFORMATIONAL: Min temperature threshold violation cleared on the probe. The first argument is the host device serial number. The second argument is the host d…
1.3.6.1.4.1.318.363NodeenvMaxHumidityThresholdViolationSEVERE: Max humidity threshold violated on the probe. The first argument is the host device serial number. The second argument is the host device name. The thi…
1.3.6.1.4.1.318.364NodeenvMaxHumidityThresholdViolationClearedINFORMATIONAL: Max humidity threshold violation cleared on the probe. The first argument is the host device serial number. The second argument is the host devi…
1.3.6.1.4.1.318.365NodeenvMinHumidityThresholdViolationSEVERE: Min humidity threshold violated on the probe. The first argument is the host device serial number. The second argument is the host device name. The thi…
1.3.6.1.4.1.318.366NodeenvMinHumidityThresholdViolationClearedINFORMATIONAL: Min humidity threshold violation cleared on the probe. The first argument is the host device serial number. The second argument is the host devi…
1.3.6.1.4.1.318.367NodeenvSTIncTempRateViolationSEVERE: Short-term increasing temperature rate violated on the probe. The first argument is the host device serial number. The second argument is the host devi…
1.3.6.1.4.1.318.368NodeenvSTIncTempRateViolationClearedINFORMATIONAL: Short-term increasing temperature rate cleared on the probe. The first argument is the host device serial number. The second argument is the hos…
1.3.6.1.4.1.318.369NodeenvSTDecTempRateViolationSEVERE: Short-term decreasing temperature rate violated on the probe. The first argument is the host device serial number. The second argument is the host devi…
1.3.6.1.4.1.318.370NodeenvSTDecTempRateViolationClearedINFORMATIONAL: Short-term decreasing temperature rate cleared on the probe. The first argument is the host device serial number. The second argument is the hos…
1.3.6.1.4.1.318.371NodeenvLTIncTempRateViolationSEVERE: Long-term increasing temperature rate violated on the probe. The first argument is the host device serial number. The second argument is the host devic…
1.3.6.1.4.1.318.372NodeenvLTIncTempRateViolationClearedINFORMATIONAL: Long-term increasing temperature rate cleared on the probe. The first argument is the host device serial number. The second argument is the host…
1.3.6.1.4.1.318.373NodeenvLTDecTempRateViolationSEVERE: Long-term decreasing temperature rate violated on the probe. The first argument is the host device serial number. The second argument is the host devic…
1.3.6.1.4.1.318.374NodeenvLTDecTempRateViolationClearedINFORMATIONAL: Long-term decreasing temperature rate cleared on the probe. The first argument is the host device serial number. The second argument is the host…
1.3.6.1.4.1.318.375NodebmsCriticalConditionSEVERE: A Battery Management System critical condition was detected. The first variable is the error condition text message. The second variable is the error n…
1.3.6.1.4.1.318.376NodebmsCriticalConditionClearedINFORMATIONAL: A Battery Management System critical condition was cleared. The first variable is the error condition text message. The second variable is the e…
1.3.6.1.4.1.318.377NodebmsWarningConditionWARNING: A Battery Management System warning condition was detected. The first variable is the error condition text message. The second variable is the error n…
1.3.6.1.4.1.318.378NodebmsWarningConditionClearedWARNING: A Battery Management System warning condition was cleared. The first variable is the error condition text message. The second variable is the error nu…
1.3.6.1.4.1.318.379NodebmsInformationalConditionINFORMATIONAL: A Battery Management System informational condition was detected. The first variable is the error condition text message. The second variable is…
1.3.6.1.4.1.318.380NodebmsInformationalConditionClearedINFORMATIONAL: A Battery Management System informational condition was cleared. The first variable is the error condition text message. The second variable is …
1.3.6.1.4.1.318.381NodexATSOutputVoltageLowAlarmSEVERE: The device three-phase output voltage of the device is outside the specified limits. The first argument is the host device serial number. The second ar…
1.3.6.1.4.1.318.382NodexATSOutputVoltageLowAlarmClearedINFORMATIONAL: The devices three-phase output voltage is back within the specified limits. The first argument is the host device serial number. The second argu…
1.3.6.1.4.1.318.383NodexATSOutputVoltageHighAlarmSEVERE: The device three-phase output voltage of the device is outside the specified limits. The first argument is the host device serial number. The second ar…
1.3.6.1.4.1.318.384NodexATSOutputVoltageHighAlarmClearedINFORMATIONAL: The devices three-phase output voltage is back within the specified limits. The first argument is the host device serial number. The second argu…
1.3.6.1.4.1.318.385NodexATSOutputCurrentLowAlarmSEVERE: The three-phase load current of the device is outside the specified limits. The first argument is the host device serial number. The second argument is…
1.3.6.1.4.1.318.386NodexATSOutputCurrentLowAlarmClearedINFORMATIONAL: The three-phase load current of the device is back within the specified limits. The first argument is the host device serial number. The second …
1.3.6.1.4.1.318.387NodexATSOutputCurrentHighAlarmSEVERE: The three-phase output load current of the device is outside the specified limits. The first argument is the host device serial number. The second argu…
1.3.6.1.4.1.318.388NodexATSOutputCurrentHighAlarmClearedINFORMATIONAL: The three-phase output load current of the device is back within the specified limits. The first argument is the host device serial number. The …
1.3.6.1.4.1.318.389NodexATSOutputFrequencyAlarmSEVERE: The devices output frequency is outside the specified limits. The first argument is the host device serial number. The second argument is the host devi…
1.3.6.1.4.1.318.390NodexATSOutputFrequencyAlarmClearedINFORMATIONAL: The devices output frequency is back within the specified limits. The first argument is the host device serial number. The second argument is th…
1.3.6.1.4.1.318.391NodexATSInternalCommErrorSEVERE: There is an internal communication error in the device. The first argument is the host device serial number. The second argument is the host device nam…
1.3.6.1.4.1.318.392NodexATSInternalCommErrorClearedINFORMATIONAL: Internal communication has been restored. The first argument is the host device serial number. The second argument is the host device name.
1.3.6.1.4.1.318.393NodexATSDataCommMismatchErrorSEVERE: A data incompatibility exists within the device. This is typically the result of mismatches between firmware revisions of the transfer switch controlle…
1.3.6.1.4.1.318.394NodexATSDataCommMismatchErrorClearedINFORMATIONAL: The internal data incompatibility has been resolved. The first argument is the host device serial number. The second argument is the host device…
1.3.6.1.4.1.318.395NodexATSGenCommLostWARNING: The XATS cannot communicate with the generator. This will make unavailable all the xATSGenerator OIDs. The first argument is the host device serial nu…
1.3.6.1.4.1.318.396NodexATSGenCommEstablishedINFORMATIONAL: The XATS has established communication with the generator. The first argument is the host device serial number. The second argument is the host …
1.3.6.1.4.1.318.397NodexATSNeutralPositionWARNING: XATS has transferred to neutral position. In this position neither Source 1 nor Source 2 is selected, and the XATS will have no output voltage. The fi…
1.3.6.1.4.1.318.398NodexATSSwitchTransferEventINFORMATIONAL: XATS has transferred from one source to the other. The first argument is the host device serial number. The second argument is the host device n…
1.3.6.1.4.1.318.399NodexATSInternalATSFaultSEVERE: An internal XATS fault has been detected. The XATS may have forced itself to not-in-auto mode (abnormal condition), as indicated by the xATSSwitchStatu…
1.3.6.1.4.1.318.400NodexATSInternalATSFaultClearedINFORMATIONAL: The detected internal XATS fault has been cleared. The first argument is the host device serial number. The second argument is the host device n…
1.3.6.1.4.1.318.401NodexATSEngineStartAssertedINFORMATIONAL: The XATS has asserted the Engine Start contact. This should result in the generator producing output voltage. The first argument is the host dev…
1.3.6.1.4.1.318.402NodexATSEngineStopAssertedINFORMATIONAL: The XATS has de-asserted the Engine Start contact. This should result in the generator shutting down, and producing no output voltage. The first…
1.3.6.1.4.1.318.403NodexATSStartFailureSEVERE: The generator failed to start. After assertion of the Engine Start signal, the quality of Source 2 was not seen as good. This alarm can be cleared usin…
1.3.6.1.4.1.318.404NodexATSStopFailureWARNING: The generator failed to stop. After de-assertion of the Engine Start signal, the quality of Source 2 continued to be seen as good. This alarm can be c…
1.3.6.1.4.1.318.405NodexATSNotInAutomaticModeSEVERE: Automatic Transfer Switch is not in automatic mode. The first argument is the host device serial number. The second argument is the host device name. T…
1.3.6.1.4.1.318.406NodexATSNotInAutomaticModeClearedINFORMATIONAL: Automatic Transfer Switch is in automatic mode. The first argument is the host device serial number. The second argument is the host device name.
1.3.6.1.4.1.318.407NodexATSEpoTrippedSEVERE: The device's Emergency Power Off (EPO) circuit is tripped. The first argument is the host device serial number. The second argument is the host device …
1.3.6.1.4.1.318.408NodexATSEpoResetINFORMATIONAL: The device's Emergency Power Off (EPO) circuit has been reset to the armed position. The first argument is the host device serial number. The se…
1.3.6.1.4.1.318.409NodexATSEpoTestModeWARNING: The device's Emergency Power Off (EPO) circuit has been switched back to the test position. The first argument is the host device serial number. The s…
1.3.6.1.4.1.318.410NodexATSEpoArmedINFORMATIONAL: The device's Emergency Power Off (EPO) circuit has been switched back to the armed position. The first argument is the host device serial number…
1.3.6.1.4.1.318.411NodexATSTestInitiatedINFORMATIONAL: A scheduled test has been initiated. The first argument is the host device serial number. The second argument is the host device name. The third…
1.3.6.1.4.1.318.412NodexATSTestCanceledINFORMATIONAL: The scheduled test has been canceled The first argument is the host device serial number. The second argument is the host device name. The third…
1.3.6.1.4.1.318.413NodexATSTestFailedSEVERE: The initiated test has failed. This alarm can be cleared using the xATSSwitchStatusClearLatchedAlarms OID. The first argument is the host device serial…
1.3.6.1.4.1.318.414NodexATSTestPassedINFORMATIONAL: The initiated test has passed switched back to the armed position. The first argument is the host device serial number. The second argument is t…
1.3.6.1.4.1.318.415NodexATSInputContactStateAbnormalSEVERE: A user input contact on the device has changed to its abnormal state. The first argument is the host device serial number. The second argument is the h…
1.3.6.1.4.1.318.416NodexATSInputContactStateNormalINFORMATIONAL: A user input contact on the device has changed to its normal state. The first argument is the host device serial number. The second argument is …
1.3.6.1.4.1.318.417NodexATSRemoteStartContactMismatchSEVERE: The state of the generator's Remote Start input and the ATS's Engine Start output do not match. This indicates something wrong in the Engine Start wiri…
1.3.6.1.4.1.318.418NodexATSRemoteStartContactMismatchClearedINFORMATIONAL: Mismatch in the state of the generator's Remote Start input and the ATS's Engine Start output as been resolved. This indicates something wrong i…
1.3.6.1.4.1.318.419NodexATSDoorOpenAlarmWARNING: The XATS exterior panel door is open. The first argument is the host device serial number. The second argument is the host device name.
1.3.6.1.4.1.318.420NodexATSDoorOpenAlarmClearedINFORMATIONAL: The external door to the device is closed. The first argument is the host device serial number. The second argument is the host device name.
1.3.6.1.4.1.318.421NodexATSDCBackupAlarmWARNING: The XATS's DC backup has been lost. The XATS will lose power on Source 1 failure, causing the Engine Start signal to be asserted. The XATS will then r…
1.3.6.1.4.1.318.422NodexATSDCBackupAlarmClearedINFORMATIONAL: DC backup alarm has been cleared in the device. The first argument is the host device serial number. The second argument is the host device name.
1.3.6.1.4.1.318.423NodexATSGeneratorLowCoolantLevelAlarmSEVERE: Low coolant level has been detected in the generator. The first argument is the host device serial number. The second argument is the host device name.…
1.3.6.1.4.1.318.424NodexATSGeneratorLowCoolantLevelAlarmClearedINFORMATIONAL: The detected low coolant level has been cleared in the generator. The first argument is the host device serial number. The second argument is th…
1.3.6.1.4.1.318.425NodexATSGeneratorVeryLowCoolantLevelAlarmSEVERE: Very low coolant level has been detected in the generator. The first argument is the host device serial number. The second argument is the host device …
1.3.6.1.4.1.318.426NodexATSGeneratorVeryLowCoolantLevelAlarmClearedINFORMATIONAL: The detected Very low coolant level has been cleared in the generator. The first argument is the host device serial number. The second argument …
1.3.6.1.4.1.318.427NodexATSGeneratorHighCoolantTempAlarmSEVERE: High coolant temperature has been detected in the generator. The first argument is the host device serial number. The second argument is the host devic…
1.3.6.1.4.1.318.428NodexATSGeneratorHighCoolantTempAlarmClearedINFORMATIONAL: The detected high coolant temperature has been cleared in the generator. The first argument is the host device serial number. The second argumen…
1.3.6.1.4.1.318.429NodexATSGeneratorVeryHighCoolantTempAlarmSEVERE: Very high coolant temperature has been detected in the generator. The first argument is the host device serial number. The second argument is the host …
1.3.6.1.4.1.318.430NodexATSGeneratorVeryHighCoolantTempAlarmClearedINFORMATIONAL: The Very high coolant temperature condition has been cleared in the generator. The first argument is the host device serial number. The second a…
1.3.6.1.4.1.318.431NodexATSGeneratorLowCoolantTempAlarmWARNING: Low coolant temperature has been detected in the generator. The first argument is the host device serial number. The second argument is the host devic…
1.3.6.1.4.1.318.432NodexATSGeneratorLowCoolantTempAlarmClearedINFORMATIONAL: The low coolant temperature condition has been cleared in the generator. The first argument is the host device serial number. The second argumen…
1.3.6.1.4.1.318.433NodexATSGeneratorLowOilLevelAlarmSEVERE: Low oil level has been detected in the generator. The first argument is the host device serial number. The second argument is the host device name. The…
1.3.6.1.4.1.318.434NodexATSGeneratorLowOilLevelAlarmClearedINFORMATIONAL: Low oil level alarm has been cleared in the generator. The first argument is the host device serial number. The second argument is the host devi…
1.3.6.1.4.1.318.435NodexATSGeneratorLowBatteryVoltDuringCrankAlarmSEVERE: The generator's battery voltage has been detected as low while cranking the engine. The first argument is the host device serial number. The second arg…
1.3.6.1.4.1.318.436NodexATSGeneratorLowBatteryVoltDuringCrankAlarmClearedINFORMATIONAL: The generator's low battery voltage while cranking condition has been cleared. The second argument is the host device name. The third argument i…
1.3.6.1.4.1.318.437NodexATSGeneratorVeryLowBatteryVoltDuringCrankAlarmSEVERE: The generator's battery voltage has been detected as very low while cranking the engine. The first argument is the host device serial number. The secon…
1.3.6.1.4.1.318.438NodexATSGeneratorVeryLowBatteryVoltDuringCrankAlarmClearedINFORMATIONAL: The generator's high battery voltage while cranking condition has been cleared. The first argument is the host device serial number. The second …
1.3.6.1.4.1.318.439NodexATSGeneratorEStopSEVERE: The generator's emergency stop input has been activated. After the emergency stop signal has been removed, the E-Stop condition must be cleared before …
1.3.6.1.4.1.318.440NodexATSGeneratorEStopClearedINFORMATIONAL: The generator's emergency stop condition has been cleared. The first argument is the host device serial number. The second argument is the host …
1.3.6.1.4.1.318.441NodexATSGeneratorHighBatteryVoltWARNING: The generator's battery voltage has been detected as high. The first argument is the host device serial number. The second argument is the host device…
1.3.6.1.4.1.318.442NodexATSGeneratorHighBatteryVoltClearedINFORMATIONAL: The detected high battery voltage has been cleared, on the generator. The first argument is the host device serial number. The second argument i…
1.3.6.1.4.1.318.443NodexATSGeneratorLowBatteryVoltSEVERE: The generator's battery voltage has been detected as low. The first argument is the host device serial number. The second argument is the host device n…
1.3.6.1.4.1.318.444NodexATSGeneratorLowBatteryVoltClearedINFORMATIONAL: The detected low battery voltage has been cleared, on the generator. The first argument is the host device serial number. The second argument is…
1.3.6.1.4.1.318.445NodexATSGeneratorControlSwitchNotAutoSEVERE: The control switch on the generator is not in auto position. The first argument is the host device serial number. The second argument is the host devic…
1.3.6.1.4.1.318.446NodexATSGeneratorControlSwitchNotAutoClearedINFORMATIONAL: The control switch on the generator is in auto position. The first argument is the host device serial number. The second argument is the host de…
1.3.6.1.4.1.318.447NodexATSGeneratorLowOilPressureSEVERE: The generator's oil pressure has been detected as low. The first argument is the host device serial number. The second argument is the host device name…
1.3.6.1.4.1.318.448NodexATSGeneratorLowOilPressureClearedINFORMATIONAL: The detected low oil pressure has been cleared, on the generator. The first argument is the host device serial number. The second argument is th…
1.3.6.1.4.1.318.449NodexATSGeneratorVeryLowOilPressureSEVERE: The generator's oil pressure has been detected as very low. The first argument is the host device serial number. The second argument is the host device…
1.3.6.1.4.1.318.450NodexATSGeneratorVeryLowOilPressureClearedINFORMATIONAL: The detected v.low oil pressure has been cleared, on the generator. The first argument is the host device serial number. The second argument is …
1.3.6.1.4.1.318.451NodexATSGeneratorOverloadSEVERE: The generator is overloaded. The first argument is the host device serial number. The second argument is the host device name. The third argument is th…
1.3.6.1.4.1.318.452NodexATSGeneratorOverloadClearedINFORMATIONAL: The generator is running within loading limits. The first argument is the host device serial number. The second argument is the host device name…
1.3.6.1.4.1.318.453NodexATSGeneratorLowACVEventSEVERE: The generator AC voltage is outside the acceptable bounds. The first argument is the host device serial number. The second argument is the host device …
1.3.6.1.4.1.318.454NodexATSGeneratorLowACVEventClearedINFORMATIONAL: The generator AC voltage is within normal bounds. The first argument is the host device serial number. The second argument is the host device na…
1.3.6.1.4.1.318.455NodexATSGeneratorHighACVEventSEVERE: The generator AC voltage is outside the acceptable bounds. The first argument is the host device serial number. The second argument is the host device …
1.3.6.1.4.1.318.456NodexATSGeneratorHighACVEventClearedINFORMATIONAL: The generator AC voltage is within normal bounds. The first argument is the host device serial number. The second argument is the host device na…
1.3.6.1.4.1.318.457NodexATSGeneratorOverspeedSEVERE: The generator is running over the acceptable RPM. The first argument is the host device serial number. The second argument is the host device name. The…
1.3.6.1.4.1.318.458NodexATSGeneratorOverspeedClearedINFORMATIONAL: The generator overspeed shutdown has been cleared. The first argument is the host device serial number. The second argument is the host device n…
1.3.6.1.4.1.318.459NodexATSGeneratorEngineColdSEVERE: The generator engine is cold, may not start. The first argument is the host device serial number. The second argument is the host device name. The thir…
1.3.6.1.4.1.318.460NodexATSGeneratorEngineColdClearedINFORMATIONAL: The engine is not cold to start. The first argument is the host device serial number. The second argument is the host device name. The third arg…
1.3.6.1.4.1.318.461NodexATSGeneratorOutputBreakerOpenSEVERE: The generators output breaker has been detected as open. The first argument is the host device serial number. The second argument is the host device na…
1.3.6.1.4.1.318.462NodexATSGeneratorOutputBreakerOpenClearedINFORMATIONAL: The engine is not cold to start. The first argument is the host device serial number. The second argument is the host device name. The third arg…
1.3.6.1.4.1.318.463NodexATSGeneratorLowFuelLevelAlarmWARNING: The tank fuel level is below the limits specified in the xATSGeneratorFuelSystemLowFuelLevelThreshold OID. The first argument is the host device seria…
1.3.6.1.4.1.318.464NodexATSGeneratorLowFuelLevelAlarmClearedINFORMATIONAL: The tank fuel level is back above the specified limit. The first argument is the host device serial number. The second argument is the host devi…
1.3.6.1.4.1.318.465NodexATSGeneratorVeryLowFuelLevelAlarmSEVERE: The tank fuel level is below the low threshold limits. The first argument is the host device serial number. The second argument is the host device name…
1.3.6.1.4.1.318.466NodexATSGeneratorVeryLowFuelLevelAlarmClearedINFORMATIONAL: The detected low tank level has been cleared in the device. The first argument is the host device serial number. The second argument is the host…
1.3.6.1.4.1.318.467NodexATSGeneratorLowRunTimeAlarmWARNING: The estimated runtime is below the limits specified. The first argument is the host device serial number. The second argument is the host device name.…
1.3.6.1.4.1.318.468NodexATSGeneratorLowRunTimeAlarmClearedINFORMATIONAL: The detected low runtime has been cleared in the device. The first argument is the host device serial number. The second argument is the host de…
1.3.6.1.4.1.318.469NodexATSGeneratorVeryLowRunTimeAlarmSEVERE: The estimated runtime is below the limits specified in the xATSGeneratorFuelSystemVeryLowRunTimeThreshold OID. The first argument is the host device se…
1.3.6.1.4.1.318.470NodexATSGeneratorVeryLowRunTimeAlarmClearedINFORMATIONAL: The detected low runtime has been cleared in the device. The first argument is the host device serial number. The second argument is the host de…
1.3.6.1.4.1.318.471NodexATSGeneratorServiceDueAlarmWARNING: The generator is due for scheduled service. Generation of this alarm is based on calendar days since and/or actual generator run-hours since last serv…
1.3.6.1.4.1.318.472NodexATSGeneratorServiceDueAlarmClearedINFORMATIONAL: The generator's service registers have been reset. The first argument is the host device serial number. The second argument is the host device n…
1.3.6.1.4.1.318.473NodexATSGeneratorShutdownSEVERE: The generator is shutdown. The first argument is the host device serial number. The second argument is the host device name. The third argument is the …
1.3.6.1.4.1.318.474NodexATSGeneratorShutdownClearedINFORMATIONAL: The generator shutdown alarm is cleared. The first argument is the host device serial number. The second argument is the host device name. The t…
1.3.6.1.4.1.318.475NodexATSGeneratorBatteryChargerSEVERE: The generator battery charger is nonfunctional. The first argument is the host device serial number. The second argument is the host device name. The t…
1.3.6.1.4.1.318.476NodexATSGeneratorBatteryChargerClearedINFORMATIONAL: Fault in the generator battery charger is cleared. The first argument is the host device serial number. The second argument is the host device n…
1.3.6.1.4.1.318.477NodexATSGeneratorGenericEventWARNING: Any generic generator event. The first argument is the host device serial number. The second argument is the host device name. The third argument is t…
1.3.6.1.4.1.318.478NodexATSGeneratorGenericEventClearedINFORMATIONAL: Generated generic generator event is cleared. The first argument is the host device serial number. The second argument is the host device name. …
1.3.6.1.4.1.318.479NodexPDUInternalCommErrorClearedINFORMATIONAL: Internal communication has been restored. The first argument is the host device serial number. The second argument is the host device name.
1.3.6.1.4.1.318.480NodexPDUSystemStateAlarmSEVERE: The PDU's breakers (Q1, Q2 & Q3) are in a configuration that might lead to system unavailability. it may signify a temporary condition, when the breake…
1.3.6.1.4.1.318.481NodexPDUSystemStateAlarmClearedINFORMATIONAL: The PDU's breakers (Q1, Q2 & Q3) are set in a configuration that is a non-alarm state. The first argument is the host device serial number. The …
1.3.6.1.4.1.318.482NodexPDUEpoTestModeWARNING: The device's Emergency Power Off (EPO) circuit has been switched back to the test position. The first argument is the host device serial number. The s…
1.3.6.1.4.1.318.483NodexPDUEpoArmedINFORMATIONAL: The device's Emergency Power Off (EPO) circuit has been switched back to the armed position. The first argument is the host device serial number…
1.3.6.1.4.1.318.484NodexPDUFuseBlownAlarmSEVERE: One or more fuses in this PDU have been detected as open. These fuses are in the feed to the UPS associated with this PDU. The first argument is the ho…
1.3.6.1.4.1.318.485NodexPDUFuseBlownAlarmClearedINFORMATIONAL: A previous check fuse alarm in this PDU has cleared. These fuses are in the feed to the UPS associated with this PDU. The first argument is the …
1.3.6.1.4.1.318.486NodexPDUBreakerPositionAlarmSEVERE: A PDU breaker is in a state that compromises system availability. The first argument is the host device serial number. The second argument is the host …
1.3.6.1.4.1.318.487NodexPDUBreakerPositionAlarmClearedINFORMATIONAL: A PDU breaker is no longer in a state that compromises system availability. The first argument is the host device serial number. The second argu…
1.3.6.1.4.1.318.488NodexPDUBreakerChangeEventINFORMATIONAL: A system breaker or switch within the device has changed state. They are generated when any of the Q1, Q2 or Q3 breakers have changed states. Th…
1.3.6.1.4.1.318.489NodexPDUDataCommMismatchErrorSEVERE: A data incompatibility exists within the device. This is typically the result of mismatches between firmware revisions of the transfer switch controlle…
1.3.6.1.4.1.318.490NodexPDUDataCommMismatchErrorClearedINFORMATIONAL: The internal data incompatibility has been resolved. The first argument is the host device serial number. The second argument is the host device…
1.3.6.1.4.1.318.491NodexPDUSystemInMaintenanceBypassModeWARNING: The PDU state has changed to maintenance bypass mode. The first argument is the host device serial number. The second argument is the host device name.
1.3.6.1.4.1.318.492NodexPDUSystemInUPSOperationalModeINFORMATIONAL: The PDU state has changed to UPS operational mode. The first argument is the host device serial number. The second argument is the host device n…
1.3.6.1.4.1.318.493NodexATSGeneratorFuelTankRuptureAlarmWARNING: Detected a rupture in the inner wall of the generator fuel tank. The first argument is the host device serial number. The second argument is the host …
1.3.6.1.4.1.318.494NodexATSGeneratorFuelTankRuptureAlarmClearedINFORMATIONAL: The rupture in the inner wall of the generator is not detected. The first argument is the host device serial number. The second argument is the …
1.3.6.1.4.1.318.495NodexATSGeneratorGroundFaultAlarmSEVERE: Generator ground fault alarm. The first argument is the host device serial number. The second argument is the host device name. The third argument is t…
1.3.6.1.4.1.318.496NodexATSGeneratorGroundFaultAlarmClearedINFORMATIONAL: Generator ground fault alarm cleared. The first argument is the host device serial number. The second argument is the host device name. The thir…
1.3.6.1.4.1.318.497NodexATSOutputLoadPoweredByGeneratorAlarmWARNING: The system load on the output of the ATS is being powered by source 2 (generator). The first argument is the host device serial number. The second arg…
1.3.6.1.4.1.318.498NodexATSOutputLoadPoweredByGeneratorAlarmClearedINFORMATIONAL: The system load on the output of the ATS is no longer being powered by source 2 (generator). The first argument is the host device serial number…
1.3.6.1.4.1.318.499NodexAPCControllerFirmwareUpdateTransferStartINFORMATIONAL: Start controller firmware transfer in the device. The first argument is the host device serial number. The second argument is the host model nam…
1.3.6.1.4.1.318.500NodexAPCControllerFirmwareUpdateTransferCompleteINFORMATIONAL: Transfer of controller firmware was completed in the device. The first argument is the host device serial number. The second argument is the hos…
1.3.6.1.4.1.318.501NodexAPCControllerFirmwareUpdateTransferFailedSEVERE: Transfer of controller firmware failed. The first argument is the host device serial number. The second argument is the host device model name that fai…
1.3.6.1.4.1.318.502NodeupsPfcInputRelayFailureWARNING: The PFC (Power Factor Correction) input relay failure exists.
1.3.6.1.4.1.318.503NodeupsPfcInputRelayFailureClearedINFORMATIONAL: The PFC (Power Factor Correction) input relay failure cleared.
1.3.6.1.4.1.318.504NodeupsInverterOverTemperatureWARNING: The inverter over temperature condition exists.
1.3.6.1.4.1.318.505NodeupsInverterOverTemperatureClearedINFORMATIONAL: The inverter over temperature condition cleared.
1.3.6.1.4.1.318.506NodeupsBatteryOverVoltageWARNING: The battery over voltage condition exists.
1.3.6.1.4.1.318.507NodeupsBatteryOverVoltageClearedINFORMATIONAL: The battery over voltage condition cleared.
1.3.6.1.4.1.318.508NodeupsEepromFaultWARNING: The EEPROM fault exists.
1.3.6.1.4.1.318.509NodeupsEepromFaultClearedINFORMATIONAL: The EEPROM fault cleared.
1.3.6.1.4.1.318.510NodearuFanRuntimeAlarmWARNING: The total running hours for a fan has exceeded the run hour threshold. The first argument is the host device serial number. The second argument is the…
1.3.6.1.4.1.318.511NodearuFanRuntimeAlarmClearedINFORMATIONAL: The total running hours for a fan is no longer above the fan runhour threshold. The first argument is the host device serial number. The second …
1.3.6.1.4.1.318.512NodearuFanPoorPerformanceAlarmWARNING: Poor fan performance has been detected in the ARU, indicating that the fan may be close to failing. The first argument is the host device serial numbe…
1.3.6.1.4.1.318.513NodearuFanPoorPerformanceAlarmClearedINFORMATIONAL: Fan performance is no longer degraded. The first argument is the host device serial number. The second argument is the host device name. The thi…
1.3.6.1.4.1.318.514NodearuRedundantPowerLostAlarmWARNING: One of the redundant line cords on the ARU is no longer receiving AC power. The first argument is the host device serial number. The second argument i…
1.3.6.1.4.1.318.515NodearuRedundantPowerLostAlarmClearedINFORMATIONAL: Line-cord redundancy has been restored to the ARU. The first argument is the host device serial number. The second argument is the host device n…
1.3.6.1.4.1.318.516NodeapcDeviceConfigChangeINFORMATIONAL: A device configuration change has been made on the device. The first argument is the device serial number. The second argument is the device nam…
1.3.6.1.4.1.318.517NodeapcEnvSensorConnectedINFORMATIONAL: A sensor has been connected to the host device. The first argument is the host device serial number. The second argument is the host device name…
1.3.6.1.4.1.318.518NodeapcEnvSensorDisconnectedSEVERE: A sensor has been disconnected from the device. The first argument is the host device serial number. The second argument is the host device name. The t…
1.3.6.1.4.1.318.519NodeapcEnvMaxTempThresholdViolationSEVERE: Max temperature threshold violated on the sensor. The first argument is the host device serial number. The second argument is the host device name. The…
1.3.6.1.4.1.318.520NodeapcEnvMaxTempThresholdViolationClearedINFORMATIONAL: Max temperature threshold violation cleared on the sensor. The first argument is the host device serial number. The second argument is the host …
1.3.6.1.4.1.318.521NodeapcEnvHighTempThresholdViolationWARNING: High temperature threshold violated on the sensor. The first argument is the host device serial number. The second argument is the host device name. T…
1.3.6.1.4.1.318.522NodeapcEnvHighTempThresholdViolationClearedINFORMATIONAL: High temperature threshold violation cleared on the sensor. The first argument is the host device serial number. The second argument is the host…
1.3.6.1.4.1.318.523NodeapcEnvLowTempThresholdViolationWARNING: Low temperature threshold violated on the sensor. The first argument is the host device serial number. The second argument is the host device name. Th…
1.3.6.1.4.1.318.524NodeapcEnvLowTempThresholdViolationClearedINFORMATIONAL: Low temperature threshold violation cleared on the sensor. The first argument is the host device serial number. The second argument is the host …
1.3.6.1.4.1.318.525NodeapcEnvMinTempThresholdViolationSEVERE: Min temperature threshold violated on the sensor. The first argument is the host device serial number. The second argument is the host device name. The…
1.3.6.1.4.1.318.526NodeapcEnvMinTempThresholdViolationClearedINFORMATIONAL: Min temperature threshold violation cleared on the sensor. The first argument is the host device serial number. The second argument is the host …
1.3.6.1.4.1.318.527NodeapcEnvSTIncTempRateViolationSEVERE: Short-term increasing temperature rate violated on the sensor. The first argument is the host device serial number. The second argument is the host dev…
1.3.6.1.4.1.318.528NodeapcEnvSTIncTempRateViolationClearedINFORMATIONAL: Short-term increasing temperature rate cleared on the sensor. The first argument is the host device serial number. The second argument is the ho…
1.3.6.1.4.1.318.529NodeapcEnvSTDecTempRateViolationSEVERE: Short-term decreasing temperature rate violated on the sensor. The first argument is the host device serial number. The second argument is the host dev…
1.3.6.1.4.1.318.530NodeapcEnvSTDecTempRateViolationClearedINFORMATIONAL: Short-term decreasing temperature rate cleared on the sensor. The first argument is the host device serial number. The second argument is the ho…
1.3.6.1.4.1.318.531NodeapcEnvLTIncTempRateViolationSEVERE: Long-term increasing temperature rate violated on the sensor. The first argument is the host device serial number. The second argument is the host devi…
1.3.6.1.4.1.318.532NodeapcEnvLTIncTempRateViolationClearedINFORMATIONAL: Long-term increasing temperature rate cleared on the sensor. The first argument is the host device serial number. The second argument is the hos…
1.3.6.1.4.1.318.533NodeapcEnvLTDecTempRateViolationSEVERE: Long-term decreasing temperature rate violated on the sensor. The first argument is the host device serial number. The second argument is the host devi…
1.3.6.1.4.1.318.534NodeapcEnvLTDecTempRateViolationClearedINFORMATIONAL: Long-term decreasing temperature rate cleared on the sensor. The first argument is the host device serial number. The second argument is the hos…
1.3.6.1.4.1.318.535NodeapcEnvMaxHumidityThresholdViolationSEVERE: Max humidity threshold violated on the sensor. The first argument is the host device serial number. The second argument is the host device name. The th…
1.3.6.1.4.1.318.536NodeapcEnvMaxHumidityThresholdViolationClearedINFORMATIONAL: Max humidity threshold violation cleared on the sensor. The first argument is the host device serial number. The second argument is the host dev…
1.3.6.1.4.1.318.537NodeapcEnvHighHumidityThresholdViolationWARNING: High humidity threshold violated on the sensor. The first argument is the host device serial number. The second argument is the host device name. The …
1.3.6.1.4.1.318.538NodeapcEnvHighHumidityThresholdViolationClearedINFORMATIONAL: High humidity threshold violation cleared on the sensor. The first argument is the host device serial number. The second argument is the host de…
1.3.6.1.4.1.318.539NodeapcEnvLowHumidityThresholdViolationWARNING: Low humidity threshold violated on the sensor. The first argument is the host device serial number. The second argument is the host device name. The t…
1.3.6.1.4.1.318.540NodeapcEnvLowHumidityThresholdViolationClearedINFORMATIONAL: Low humidity threshold violation cleared on the sensor. The first argument is the host device serial number. The second argument is the host dev…
1.3.6.1.4.1.318.541NodeapcEnvMinHumidityThresholdViolationSEVERE: Min humidity threshold violated on the sensor. The first argument is the host device serial number. The second argument is the host device name. The th…
1.3.6.1.4.1.318.542NodeapcEnvMinHumidityThresholdViolationClearedINFORMATIONAL: Min humidity threshold violation cleared on the sensor. The first argument is the host device serial number. The second argument is the host dev…
1.3.6.1.4.1.318.543NodeapcBeaconConnectedINFORMATIONAL: A beacon has been connected to the device. The first argument is the host device serial number. The second argument is the host device name. The…
1.3.6.1.4.1.318.544NodeapcBeaconDisconnectedSEVERE: A beacon has been disconnected from the device. The first argument is the host device serial number. The second argument is the host device name. The t…
1.3.6.1.4.1.318.545NodeapcBeaconOnINFORMATIONAL: A beacon has gone on (activated). The first argument is the host device serial number. The second argument is the host device name. The third ar…
1.3.6.1.4.1.318.546NodeapcBeaconOffINFORMATIONAL: A beacon has gone off (deactivated). The first argument is the host device serial number. The second argument is the host device name. The third…
1.3.6.1.4.1.318.547NodeapcOutletStateAbnormalWARNING: An outlet on the device has changed to its abnormal state. The first argument is the host device serial number. The second argument is the host device…
1.3.6.1.4.1.318.548NodeapcOutletStateNormalINFORMATIONAL: An outlet on the device has changed to its normal state. The first argument is the host device serial number. The second argument is the host de…
1.3.6.1.4.1.318.549NodeapcOutputRelayStateAbnormalWARNING: An output relay on the device has changed to its abnormal state. The first argument is the host device serial number. The second argument is the host …
1.3.6.1.4.1.318.550NodeapcOutputRelayStateNormalINFORMATIONAL: An output relay on the device has changed to its normal state. The first argument is the host device serial number. The second argument is the h…
1.3.6.1.4.1.318.551NodeapcHardwareStateAbnormalSEVERE: The device's hardware is improperly configured and operating outside normal bounds for the hardware. This can be caused by improper devices being conne…
1.3.6.1.4.1.318.552NodeapcHardwareStateNormalINFORMATIONAL: The device's hardware is in its normal operational state. The first argument is the host device serial number. The second argument is the host d…
1.3.6.1.4.1.318.553NodeapcCriticalDiscreteInputContactStateAbnormalSEVERE: A discrete input contact on the device has changed to its abnormal state. The first argument is the host device serial number. The second argument is t…
1.3.6.1.4.1.318.554NodeapcCriticalDiscreteInputContactStateNormalINFORMATIONAL: A discrete input contact on the device has changed to its normal state. The first argument is the host device serial number. The second argument…
1.3.6.1.4.1.318.555NodeapcWarningDiscreteInputContactStateAbnormalWARNING: A discrete input contact on the device has changed to its abnormal state. The first argument is the host device serial number. The second argument is …
1.3.6.1.4.1.318.556NodeapcWarningDiscreteInputContactStateNormalINFORMATIONAL: A discrete input contact on the device has changed to its normal state. The first argument is the host device serial number. The second argument…
1.3.6.1.4.1.318.557NodeapcInformationalDiscreteInputContactStateAbnormalINFORMATIONAL: A discrete input contact on the device has changed to its abnormal state. The first argument is the host device serial number. The second argume…
1.3.6.1.4.1.318.558NodeapcInformationalDiscreteInputContactStateNormalINFORMATIONAL: A discrete input contact on the device has changed to its normal state. The first argument is the host device serial number. The second argument…
1.3.6.1.4.1.318.559NodeapcAnalogInputMaxThresholdViolationSEVERE: Maximum threshold violated on an analog input. The first argument is the host device serial number. The second argument is the host device name. The th…
1.3.6.1.4.1.318.560NodeapcAnalogInputMaxThresholdViolationClearedINFORMATIONAL: Maximum threshold violation cleared on the analog input. The first argument is the host device serial number. The second argument is the host de…
1.3.6.1.4.1.318.561NodeapcAnalogInputHighThresholdViolationWARNING: High threshold violated on an analog input. The first argument is the host device serial number. The second argument is the host device name. The thir…
1.3.6.1.4.1.318.562NodeapcAnalogInputHighThresholdViolationClearedINFORMATIONAL: High threshold violation cleared on the analog input. The first argument is the host device serial number. The second argument is the host devic…
1.3.6.1.4.1.318.563NodeapcAnalogInputLowThresholdViolationWARNING: Low threshold violated on an analog input. The first argument is the host device serial number. The second argument is the host device name. The third…
1.3.6.1.4.1.318.564NodeapcAnalogInputLowThresholdViolationClearedINFORMATIONAL: Low threshold violation cleared on the analog input. The first argument is the host device serial number. The second argument is the host device…
1.3.6.1.4.1.318.565NodeapcAnalogInputMinThresholdViolationSEVERE: Minimum threshold violated on an analog input. The first argument is the host device serial number. The second argument is the host device name. The th…
1.3.6.1.4.1.318.566NodeapcAnalogInputMinThresholdViolationClearedINFORMATIONAL: Minimum threshold violation cleared on the analog input. The first argument is the host device serial number. The second argument is the host de…
1.3.6.1.4.1.318.567NodeapcDeviceClearLostCommsINFORMATIONAL: Lost communications reset command has been issued. The first argument is the device serial number. The second argument is the device name. The t…
1.3.6.1.4.1.318.568NodeapcDeviceConnectedINFORMATIONAL: A device has been connected to the host. The first argument is the host serial number. The second argument is the host name. The third argument …
1.3.6.1.4.1.318.569NodeapcDeviceDisconnectedSEVERE: A device has been disconnected from the host. The first argument is the host serial number. The second argument is the host name. The third argument is…
1.3.6.1.4.1.318.570NodeapcUnregisteredUserAccessDeniedINFORMATIONAL: An unregistered user has tried to access the device. The first argument is the host device serial number. The second argument is the host device…
1.3.6.1.4.1.318.571NodeapcRegisteredUserAccessDeniedINFORMATIONAL: A registered user has been denied access to the device. The first argument is the host device serial number. The second argument is the host dev…
1.3.6.1.4.1.318.572NodeapcRegisteredUserConfigChangeINFORMATIONAL: Registered user configuration change. The first argument is the host device serial number. The second argument is the host device name. The thir…
1.3.6.1.4.1.318.573NodeapcDoorUnlockedINFORMATIONAL: A door has been unlocked. The first argument is the host device serial number. The second argument is the host device name. The third argument i…
1.3.6.1.4.1.318.574NodeapcDoorLockedINFORMATIONAL: A door has been locked. The first argument is the host device serial number. The second argument is the host device name. The third argument is …
1.3.6.1.4.1.318.575NodeapcHandleOpenedINFORMATIONAL: A door handle has been opened. The first argument is the host device serial number. The second argument is the host device name. The third argum…
1.3.6.1.4.1.318.576NodeapcHandleClosedINFORMATIONAL: A door handle has been closed. The first argument is the host device serial number. The second argument is the host device name. The third argum…
1.3.6.1.4.1.318.577NodeapcDoorOpenedINFORMATIONAL: A door has been opened. The first argument is the host device serial number. The second argument is the host device name. The third argument is …
1.3.6.1.4.1.318.578NodeapcDoorClosedINFORMATIONAL: A door has been closed. The first argument is the host device serial number. The second argument is the host device name. The third argument is …
1.3.6.1.4.1.318.580NodeapcKeyOverrideUnlockedSEVERE: Key override unlock has occurred. The first argument is the host device serial number. The second argument is the host device name. The third argument …
1.3.6.1.4.1.318.581NodeapcKeyOverrideLockedINFORMATIONAL: Key override lock has occurred. The first argument is the host device serial number. The second argument is the host device name. The third argu…
1.3.6.1.4.1.318.582NodeapcForcedEntrySEVERE: A forced entry condition has occurred. The first argument is the host device serial number. The second argument is the host device name. The third argu…
1.3.6.1.4.1.318.583NodeapcForcedEntryClearedINFORMATIONAL: A forced entry condition has been cleared. The first argument is the host device serial number. The second argument is the host device name. The…
1.3.6.1.4.1.318.584NodeapcRelockTimeoutSEVERE: A relock timout has occurred. The first argument is the host device serial number. The second argument is the host device name. The third argument is t…
1.3.6.1.4.1.318.585NodeapcRelockTimeoutClearedINFORMATIONAL: A relock timout has been cleared. The first argument is the host device serial number. The second argument is the host device name. The third ar…
1.3.6.1.4.1.318.586NodeapcDoorSenseDisconnectedSEVERE: A door sensor was disconnected. The first argument is the host device serial number. The second argument is the host device name. The third argument is…
1.3.6.1.4.1.318.587NodeapcDoorSenseConnectedINFORMATIONAL: A forced entry condition has been cleared. The first argument is the host device serial number. The second argument is the host device name. The…
1.3.6.1.4.1.318.588NodeapcDoorLostCommsSEVERE: Communications have been lost with the door. The first argument is the host device serial number. The second argument is the host device name. The thir…
1.3.6.1.4.1.318.589NodeapcDoorEstablishedCommsINFORMATIONAL: Communications have been established with the door. The first argument is the host device serial number. The second argument is the host device …
1.3.6.1.4.1.318.590NodeapcRegisteredUserAccessChangeINFORMATIONAL: Registered user access changed. The first argument is the host device serial number. The second argument is the host device name. The third argu…
1.3.6.1.4.1.318.591NodeapcUnregisteredUserStatusChangeINFORMATIONAL: Unregistered user status changed. The first argument is the host device serial number. The second argument is the host device name. The third ar…
1.3.6.1.4.1.318.592NodeapcDeviceClearUserConfigsINFORMATIONAL: User configurations reset command has been issued. The first argument is the device serial number. The second argument is the device name. The t…
1.3.6.1.4.1.318.600NodeupsBatteryTempSensorFaultWARNING: The battery temperature sensor fault exists.
1.3.6.1.4.1.318.601NodeupsBatteryTempSensorFaultClearedINFORMATIONAL: The battery temperature sensor fault cleared.
1.3.6.1.4.1.318.602NodeupsBatterySoftBusStartFaultWARNING: A battery bus soft start fault exists.
1.3.6.1.4.1.318.603NodeupsBatterySoftBusStartFaultClearedINFORMATIONAL: A battery bus soft start fault exists cleared.
1.3.6.1.4.1.318.604NodeapcOutputShortCircuitWARNING: An output short circuit condition exists.
1.3.6.1.4.1.318.605NodeapcOutputShortCircuitClearedINFORMATIONAL: An output short circuit condition cleared.
1.3.6.1.4.1.318.606NodeapcOutputRelayFaultWARNING: An output relay (or its driver) fault exists.
1.3.6.1.4.1.318.607NodeapcOutputRelayFaultClearedINFORMATIONAL: An output relay (or its driver) fault cleared.
1.3.6.1.4.1.318.608NodeupsPfcFaultWARNING: A PFC fault exists.
1.3.6.1.4.1.318.609NodeupsPfcFaultClearedINFORMATIONAL: The PFC fault cleared.
1.3.6.1.4.1.318.610NodeapcDcBusOverVoltageWARNING: The DC bus voltage is too high.
1.3.6.1.4.1.318.611NodeapcDcBusOverVoltageClearedINFORMATIONAL: The DC bus voltage is too high cleared.
1.3.6.1.4.1.318.612NodeupsInverterFaultWARNING: The inverter fault exists.
1.3.6.1.4.1.318.613NodeupsInverterFaultClearedINFORMATIONAL: The inverter fault cleared.
1.3.6.1.4.1.318.614NodeapcAdConverterFaultWARNING: The A/D converter fault exists.
1.3.6.1.4.1.318.615NodeapcAdConverterFaultClearedINFORMATIONAL: The A/D converter fault cleared.
1.3.6.1.4.1.318.616NodeapcLogicPowerSupplyFaultWARNING: A logic power supply fault exists.
1.3.6.1.4.1.318.617NodeapcLogicPowerSupplyFaultClearedINFORMATIONAL: A logic power supply fault cleared.
1.3.6.1.4.1.318.618NodeapcTransformerDCImbalanceFaultWARNING: The DC component of the transformer's current is too high.
1.3.6.1.4.1.318.619NodeapcTransformerDCImbalanceFaultClearedWARNING: The DC component of the transformer's current is normal.
1.3.6.1.4.1.318.620NodeupsBackfeedRelayFaultWARNING: The backfeed relay (or its driver) has a fault.
1.3.6.1.4.1.318.621NodeupsBackfeedRelayFaultClearedWARNING: The backfeed relay (or its driver) has a fault cleared.
1.3.6.1.4.1.318.622NodeupsBypassRelayFaultWARNING: A bypass relay (or its driver) has a fault.
1.3.6.1.4.1.318.623NodeupsBypassRelayFaultClearedWARNING: A bypass relay (or its driver) has a fault cleared.
1.3.6.1.4.1.318.626NodexPDUBranchCurrentMinAlarmSEVERE: The current in a branch circuit is outside the limits specified for that branch circuit. The first argument is the host device serial number. The secon…
1.3.6.1.4.1.318.627NodexPDUBranchCurrentMinAlarmClearedINFORMATIONAL: The current in a branch circuit is back within the limits specified for that branch circuit. The first argument is the host device serial number…
1.3.6.1.4.1.318.628NodexPDUBranchCurrentMaxAlarmSEVERE: The current in a branch circuit is outside the limits specified for that branch circuit. The first argument is the host device serial number. The secon…
1.3.6.1.4.1.318.629NodexPDUBranchCurrentMaxAlarmClearedINFORMATIONAL: The current in a branch circuit is back within the limits specified for that branch circuit. The first argument is the host device serial number…
1.3.6.1.4.1.318.630NoderPDUOutletLowLoadWARNING: A Rack PDU has violated the outlet low load threshold. The first argument is the serial number. The second argument is the device name. The third argu…
1.3.6.1.4.1.318.631NoderPDUOutletLowLoadClearedINFORMATIONAL: The outlet low load condition on a Rack PDU has been cleared. The first argument is the serial number. The second argument is the device name. T…
1.3.6.1.4.1.318.632NoderPDUOutletNearOverloadWARNING: A Rack PDU is near an outlet overload condition. The first argument is the serial number. The second argument is the device name. The third argument i…
1.3.6.1.4.1.318.633NoderPDUOutletNearOverloadClearedINFORMATIONAL: The outlet near overload condition on a Rack PDU has been cleared. The first argument is the serial number. The second argument is the device na…
1.3.6.1.4.1.318.634NoderPDUOutletOverloadSEVERE: A Rack PDU is in an overload condition. The first argument is the serial number. The second argument is the device name. The third argument is the outl…
1.3.6.1.4.1.318.635NoderPDUOutletOverloadClearedINFORMATIONAL: The outlet overload condition on a Rack PDU has been cleared. The first argument is the serial number. The second argument is the device name. T…
1.3.6.1.4.1.318.636NodeapcTestTrapINFORMATIONAL: Trap used to test SNMP trap functionality. The first argument is a place holder for test variables.
1.3.6.1.4.1.318.637NodebaseFanFailureClearedINFORMATIONAL: Base module fan has been repaired
1.3.6.1.4.1.318.638NodeatsLowLoadWARNING: ATS has violated the bank or phase low load threshold. The first argument is the serial number. The second argument is the product name. The third arg…
1.3.6.1.4.1.318.639NodeatsLowLoadClearedINFORMATIONAL: The bank or phase low load condition on an ATS has been cleared. The first argument is the serial number. The second argument is the product nam…
1.3.6.1.4.1.318.640NodeatsNearOverloadWARNING: ATS has violated the bank or phase near overload threshold. The first argument is the serial number. The second argument is the product name. The thir…
1.3.6.1.4.1.318.641NodeatsNearOverloadClearedINFORMATIONAL: The bank or phase near overload condition on an ATS has been cleared. The first argument is the serial number. The second argument is the produc…
1.3.6.1.4.1.318.642NodeatsOverloadSEVERE: ATS is in an overload condition. The first argument is the serial number. The second argument is the product name. The third argument is the phase numb…
1.3.6.1.4.1.318.643NodeatsOverloadClearedINFORMATIONAL: The bank or phase overload condition on an ATS has been cleared. The first argument is the serial number. The second argument is the product nam…
1.3.6.1.4.1.318.644NodeatsRMSOverVoltageSEVERE: Overvoltage condition violated. The first argument is the serial number. The second argument is the product name. The third argument is an integer repr…
1.3.6.1.4.1.318.645NodeatsRMSOverVoltageClearedINFORMATIONAL: Overvoltage condition cleared. The first argument is the serial number. The second argument is the product name. The third argument is an intege…
1.3.6.1.4.1.318.646NodeatsRMSUnderVoltageSEVERE: Undervoltage condition violated. The first argument is the serial number. The second argument is the product name. The third argument is an integer rep…
1.3.6.1.4.1.318.647NodeatsRMSUnderVoltageClearedINFORMATIONAL: Undervoltage condition cleared. The first argument is the serial number. The second argument is the product name. The third argument is an integ…
1.3.6.1.4.1.318.648NodeatsRMSOverFrequencySEVERE: OverFrequency condition violated. The first argument is the serial number. The second argument is the product name. The third argument is an integer re…
1.3.6.1.4.1.318.649NodeatsRMSOverFrequencyClearedINFORMATIONAL: OverFrequency condition cleared. The first argument is the serial number. The second argument is the product name. The third argument is an inte…
1.3.6.1.4.1.318.650NodeatsRMSUnderFrequencySEVERE: UnderFrequency condition violated. The first argument is the serial number. The second argument is the product name. The third argument is an integer r…
1.3.6.1.4.1.318.651NodeatsRMSUnderFrequencyClearedINFORMATIONAL: UnderFrequency condition cleared. The first argument is the serial number. The second argument is the product name. The third argument is an int…
1.3.6.1.4.1.318.652NodeisxModularDistributionCommLostSEVERE: Communication with a metering segment of the modular distribution system has been lost. The first argument is the host device serial number. The second…
1.3.6.1.4.1.318.653NodeisxModularDistributionCommEstablishedINFORMATIONAL: Communication with a metering segment of the modular distribution system has been restored. The first argument is the host device serial number.…
1.3.6.1.4.1.318.654NodeisxModularDistributionModuleInsertedINFORMATIONAL: A distribution module has been inserted into the system. The first argument is the host device serial number. The second argument is the host de…
1.3.6.1.4.1.318.655NodeisxModularDistributionModuleRemovedINFORMATIONAL: A distribution module has been removed from the system. The first argument is the host device serial number. The second argument is the host dev…
1.3.6.1.4.1.318.656NodeisxModularBreakerOpenAlarmSEVERE: A distribution module breaker is open and in an alarm condition. The first argument is the host device serial number. The second argument is the host d…
1.3.6.1.4.1.318.657NodeisxModularBreakerOpenAlarmClearedINFORMATIONAL: An alarm caused by a distribution breaker being open has been cleared. The first argument is the host device serial number. The second argument …
1.3.6.1.4.1.318.658NodeisxModularMinCurrentThresholdViolationSEVERE: The current in a distribution module is below the minimum/critical limit specified for the circuit/cable. The first argument is the host device serial …
1.3.6.1.4.1.318.659NodeisxModularMinCurrentThresholdViolationClearedINFORMATIONAL: The current in a distribution module is no longer below the minimum/critical limit specified for the circuit/cable. The first argument is the ho…
1.3.6.1.4.1.318.660NodeisxModularLowCurrentThresholdViolationWARNING: The current in a distribution module is below the low/warning limit specified for the circuit/cable. The first argument is the host device serial numb…
1.3.6.1.4.1.318.661NodeisxModularLowCurrentThresholdViolationClearedINFORMATIONAL: The current in a distribution module is no longer below the low/warning limit specified for the circuit/cable. The first argument is the host de…
1.3.6.1.4.1.318.662NodeisxModularHighCurrentThresholdViolationWARNING: The current in a distribution module is above the high/warning limit specified for the circuit/cable. The first argument is the host device serial num…
1.3.6.1.4.1.318.663NodeisxModularHighCurrentThresholdViolationClearedINFORMATIONAL: The current in a distribution module is no longer above the high/warning limit specified for the circuit/cable. The first argument is the host d…
1.3.6.1.4.1.318.664NodeisxModularMaxCurrentThresholdViolationSEVERE: The current in a distribution module is above the maximum/critical limit specified for the circuit/cable. The first argument is the host device serial …
1.3.6.1.4.1.318.665NodeisxModularMaxCurrentThresholdViolationClearedINFORMATIONAL: The current in a distribution module is no longer above the maximum/critical limit specified for the circuit/cable. The first argument is the ho…
1.3.6.1.4.1.318.666NodeisxModularSubfeedBreakerOpenAlarmSEVERE: A distribution subfeed breaker is open and in an alarm condition. The first argument is the host device serial number. The second argument is the host …
1.3.6.1.4.1.318.667NodeisxModularSubfeedBreakerOpenAlarmClearedINFORMATIONAL: An alarm caused by a distribution subfeed breaker being open has been cleared. The first argument is the host device serial number. The second a…
1.3.6.1.4.1.318.668NodeisxModularSubfeedMinCurrentThresholdViolationSEVERE: The current in a distribution subfeed is below the minimum/critical limit specified. The first argument is the host device serial number. The second ar…
1.3.6.1.4.1.318.669NodeisxModularSubfeedMinCurrentThresholdViolationClearedINFORMATIONAL: The current in a distribution subfeed is no longer below the minimum/critical limit specified. The first argument is the host device serial numb…
1.3.6.1.4.1.318.670NodeisxModularSubfeedLowCurrentThresholdViolationWARNING: The current in a distribution subfeed is below the low/warning limit specified. The first argument is the host device serial number. The second argume…
1.3.6.1.4.1.318.671NodeisxModularSubfeedLowCurrentThresholdViolationClearedINFORMATIONAL: The current in a distribution subfeed is no longer below the low/warning limit specified. The first argument is the host device serial number. T…
1.3.6.1.4.1.318.672NodeisxModularSubfeedHighCurrentThresholdViolationWARNING: The current in a distribution subfeed is above the high/warning limit specified. The first argument is the host device serial number. The second argum…
1.3.6.1.4.1.318.673NodeisxModularSubfeedHighCurrentThresholdViolationClearedINFORMATIONAL: The current in a distribution subfeed is no longer above the high/warning limit specified. The first argument is the host device serial number. …
1.3.6.1.4.1.318.674NodeisxModularSubfeedMaxCurrentThresholdViolationSEVERE: The current in a distribution subfeed is above the maximum/critical limit specified. The first argument is the host device serial number. The second ar…
1.3.6.1.4.1.318.675NodeisxModularSubfeedMaxCurrentThresholdViolationClearedINFORMATIONAL: The current in a distribution subfeed is no longer above the maximum/critical limit specified. The first argument is the host device serial numb…
1.3.6.1.4.1.318.676NodeisxModularTotalOutputCurrentMinThresholdViolationSEVERE: The total output current of the distribution is below the minimum/critical limit specified. The first argument is the host device serial number. The se…
1.3.6.1.4.1.318.677NodeisxModularTotalOutputCurrentMinThresholdViolationClearedINFORMATIONAL: The total output current of the distribution is no longer below the minimum/critical limit specified. The first argument is the host device seri…
1.3.6.1.4.1.318.678NodeisxModularTotalOutputCurrentLowThresholdViolationWARNING: The total output current of the distribution is below the low/warning limit specified. The first argument is the host device serial number. The second…
1.3.6.1.4.1.318.679NodeisxModularTotalOutputCurrentLowThresholdViolationClearedINFORMATIONAL: The total output current of the distribution is no longer below the low/warning limit specified. The first argument is the host device serial nu…
1.3.6.1.4.1.318.680NodeisxModularTotalOutputCurrentHighThresholdViolationWARNING: The total output current of the distribution is above the high/warning limit specified. The first argument is the host device serial number. The secon…
1.3.6.1.4.1.318.681NodeisxModularTotalOutputCurrentHighThresholdViolationClearedINFORMATIONAL: The total output current of the distribution is no longer above the high/warning limit specified. The first argument is the host device serial n…
1.3.6.1.4.1.318.682NodeisxModularTotalOutputCurrentMaxThresholdViolationSEVERE: The total output current of the distribution is above the maximum/critical limit specified. The first argument is the host device serial number. The se…
1.3.6.1.4.1.318.683NodeisxModularTotalOutputCurrentMaxThresholdViolationClearedINFORMATIONAL: The total output current of the distribution is no longer above the maximum/critical limit specified. The first argument is the host device seri…
1.3.6.1.4.1.318.684NodeisxModularOutputVoltageMinThresholdViolationSEVERE: The distribution output voltage is below the minimum/critical limit specified. The first argument is the host device serial number. The second argument…
1.3.6.1.4.1.318.685NodeisxModularOutputVoltageMinThresholdViolationClearedINFORMATIONAL: The distribution output voltage is no longer below the minimum/critical limit specified. The first argument is the host device serial number. Th…
1.3.6.1.4.1.318.686NodeisxModularOutputVoltageLowThresholdViolationWARNING: The distribution output voltage is below the low/warning limit specified. The first argument is the host device serial number. The second argument is …
1.3.6.1.4.1.318.687NodeisxModularOutputVoltageLowThresholdViolationClearedINFORMATIONAL: The distribution output voltage is no longer below the low/warning limit specified. The first argument is the host device serial number. The sec…
1.3.6.1.4.1.318.688NodeisxModularOutputVoltageHighThresholdViolationWARNING: The distribution output voltage is above the high/warning limit specified. The first argument is the host device serial number. The second argument is…
1.3.6.1.4.1.318.689NodeisxModularOutputVoltageHighThresholdViolationClearedINFORMATIONAL: The distribution output voltage is no longer above the high/warning limit specified. The first argument is the host device serial number. The se…
1.3.6.1.4.1.318.690NodeisxModularOutputVoltageMaxThresholdViolationSEVERE: The distribution output voltage is above the maximum/critical limit specified. The first argument is the host device serial number. The second argument…
1.3.6.1.4.1.318.691NodeisxModularOutputVoltageMaxThresholdViolationClearedINFORMATIONAL: The distribution output voltage is no longer above the maximum/critical limit specified. The first argument is the host device serial number. Th…
1.3.6.1.4.1.318.692NodeapcDoorClosedImproperlySEVERE: A door has been closed improperly. The first argument is the host device serial number. The second argument is the host device name. The third argument…
1.3.6.1.4.1.318.693NodeapcDoorClosedImproperlyClearedINFORMATIONAL: A door is no longer closed improperly. The first argument is the host device serial number. The second argument is the host device name. The thi…
1.3.6.1.4.1.318.694NodeapcUserScheduleViolationSEVERE: A user has had a door opened past the scheduled access period. The first argument is the host device serial number. The second argument is the host dev…
1.3.6.1.4.1.318.695NodeapcUserScheduleViolationClearedINFORMATIONAL: User schedule violation has been cleared. The first argument is the host device serial number. The second argument is the host device name. The …
1.3.6.1.4.1.318.696NodeisxModularOutputFrequencyThresholdViolationSEVERE: The distribution output frequency is outside of the operating range specified. The first argument is the host device serial number. The second argument…
1.3.6.1.4.1.318.697NodeisxModularOutputFrequencyViolationClearedINFORMATIONAL: The distribution output frequency is no longer out of range. The first argument is the host device serial number. The second argument is the hos…
1.3.6.1.4.1.318.698NodeatsSourceStatusFailSEVERE: ATS Source failed. The first argument is the serial number. The second argument is the product name. The third argument is an integer representing the …
1.3.6.1.4.1.318.699NodeatsSourceStatusOkINFORMATIONAL: ATS Source OK. The first argument is the serial number. The second argument is the product name. The third argument is an integer representing t…
1.3.6.1.4.1.318.700NodeatsHardwareStatusFailSEVERE: ATS display board hardware failed. The first argument is the serial number. The second argument is the product name. The third argument is an integer r…
1.3.6.1.4.1.318.701NodeatsHardwareStatusOkINFORMATIONAL: ATS display board hardware ok. The first argument is the serial number. The second argument is the product name. The third argument is an intege…
1.3.6.1.4.1.318.702NodeatsControllerRestartINFORMATIONAL: ATS Controller restarted.
1.3.6.1.4.1.318.703NodeinputWarningErrorWARNING: Input warning error has been detected. The first variable is the fault condition.
1.3.6.1.4.1.318.704NodeinputOKINFORMATIONAL: Input warning error has been cleared. The first variable is the fault condition.
1.3.6.1.4.1.318.705NodebypassWarningErrorWARNING: Bypass warning error has been detected. The first variable is the fault condition.
1.3.6.1.4.1.318.706NodebypassOKINFORMATIONAL: Bypass warning error has been cleared. The first variable is the fault condition.
1.3.6.1.4.1.318.707NodecommunicationWarningErrorWARNING: Communication warning error has been detected. The first variable is the fault condition.
1.3.6.1.4.1.318.708NodecommunicationOKINFORMATIONAL: Communication warning error has been cleared. The first variable is the fault condition.
1.3.6.1.4.1.318.709NodepowerModuleSevereErrorSEVERE: Power module severe error has been detected. The first variable is the fault condition.
1.3.6.1.4.1.318.710NodepowerModuleOKINFORMATIONAL: Power module severe error has been cleared. The first variable is the fault condition.
1.3.6.1.4.1.318.711NodeoutputVoltageWaveformErrorSEVERE: Output voltage waveform error has been detected.
1.3.6.1.4.1.318.712NodeoutputVoltageWaveformOKINFORMATIONAL: Output voltage waveform is OK.
1.3.6.1.4.1.318.713NodebypassStaticSwitchOverloadSEVERE: Overload on bypass static switch has been detected.
1.3.6.1.4.1.318.714NodenoOverloadOnBypassStaticSwitchINFORMATIONAL: Overload on static bypass switch no longer present.
1.3.6.1.4.1.318.715NodebatteryVoltageCollapseSEVERE: Battery voltage collapse has been detected.
1.3.6.1.4.1.318.716NodebatteryVoltageOKINFORMATIONAL: Battery voltage OK.
1.3.6.1.4.1.318.717NodeoverloadOnInstallationSEVERE: Overload on installation has been detected.
1.3.6.1.4.1.318.718NodenoOverloadOnInstallationINFORMATIONAL: Overload on installation no longer present.
1.3.6.1.4.1.318.719NodebypassStaticSwitchErrorSEVERE: Bypass static switch error, module has critical error.
1.3.6.1.4.1.318.720NodebypassStaticSwitchOKINFORMATIONAL: Bypass static switch OK.
1.3.6.1.4.1.318.721NodeforcedBypassSwitchActivatedSEVERE: Forced bypass switch has been activated.
1.3.6.1.4.1.318.722NodeforcedBypassSwitchReleasedINFORMATIONAL: Forced bypass switch has been released.
1.3.6.1.4.1.318.723NodeepoActivatedSEVERE: Emergency Power Off (EPO) switch has been activated.
1.3.6.1.4.1.318.724NodexATSS1BadPhaseRotationSEVERE: The device's source 1 phase rotation is bad. The first argument is the host device serial number. The second argument is the host device name.
1.3.6.1.4.1.318.725NodexATSS1BadPhaseRotationClearedINFORMATIONAL: The device's source 1 phase rotation is back to normal. The first argument is the host device serial number. The second argument is the host dev…
1.3.6.1.4.1.318.726NodexATSS1BadPhaseBalanceSEVERE: The device's source 1 phase balance is out of bounds. The first argument is the host device serial number. The second argument is the host device name.…
1.3.6.1.4.1.318.727NodexATSS1BadPhaseBalanceClearedINFORMATIONAL: The device's source 1 phase balance is back to normal. The first argument is the host device serial number. The second argument is the host devi…
1.3.6.1.4.1.318.728NodeisxModularTransformerOverheatingSEVERE: The distribution transformer temperature is too hot. The first argument is the host device serial number. The second argument is the host device name.
1.3.6.1.4.1.318.729NodeisxModularTransformerOverheatingClearedINFORMATIONAL: The distribution transformer temperature has returned to normal. The first argument is the host device serial number. The second argument is the…
1.3.6.1.4.1.318.730NodeapcInternalCommunicationFaultSEVERE: An internal UPS communication fault exists.
1.3.6.1.4.1.318.731NodeapcInternalCommunicationFaultClearedINFORMATIONAL: An internal UPS communication fault no longer exists.
1.3.6.1.4.1.318.732NodeupsOutletGroupCommandWARNING: The specified Outlet Group command has been issued.
1.3.6.1.4.1.318.733NodeonbatterycommunicationLostSEVERE: Communication to the UPS when the UPS is on Battery. Steps to reestablish communication are in progress.
1.3.6.1.4.1.318.734NodeupsCriticalConditionSEVERE: A UPS critical condition was detected. The first variable is the error condition text message. The second variable is the error number.
1.3.6.1.4.1.318.735NodeupsCriticalConditionClearedINFORMATIONAL: A UPS critical condition has been cleared. The first variable is the fault condition.
1.3.6.1.4.1.318.736NodeupsWarningConditionWARNING: A UPS warning condition has been detected. The first variable is the fault condition.
1.3.6.1.4.1.318.737NodeupsWarningConditionClearedWARNING: A UPS warning condition has been cleared. The first variable is the fault condition.
1.3.6.1.4.1.318.738NodeupsInformationalConditionINFORMATIONAL: A UPS informational condition has been detected. The first variable is the fault condition.
1.3.6.1.4.1.318.739NodeupsInformationalConditionClearedINFORMATIONAL: A UPS informational condition has been cleared. The first variable is the fault condition.
1.3.6.1.4.1.318.740NodeisxcInformationalAlarmINFORMATIONAL: An ISXC Alarm exists. The first argument is the unique ISXC alarm ID. The second argument is the ISXC alarm label as a UTF8 string. The third ar…
1.3.6.1.4.1.318.741NodeisxcInformationalAlarmClearedINFORMATIONAL: An ISXC Alarm has been cleared. The first argument is the unique ISXC alarm ID. The second argument is the ISXC alarm label as a UTF8 string. Th…
1.3.6.1.4.1.318.742NodeisxcWarningAlarmWARNING: An ISXC Alarm exists. The first argument is the unique ISXC alarm ID. The second argument is the ISXC alarm label as a UTF8 string. The third argument…
1.3.6.1.4.1.318.743NodeisxcWarningAlarmClearedWARNING: An ISXC Alarm has been cleared. The first argument is the unique ISXC alarm ID. The second argument is the ISXC alarm label as a UTF8 string. The thir…
1.3.6.1.4.1.318.744NodeisxcErrorAlarmERROR: An ISXC Alarm exists. The first argument is the unique ISXC alarm ID. The second argument is the ISXC alarm label as a UTF8 string. The third argument i…
1.3.6.1.4.1.318.745NodeisxcErrorAlarmClearedERROR: An ISXC Alarm has been cleared. The first argument is the unique ISXC alarm ID. The second argument is the ISXC alarm label as a UTF8 string. The third …
1.3.6.1.4.1.318.746NodeisxcCriticalAlarmCRITICAL: An ISXC Alarm exists. The first argument is the unique ISXC alarm ID. The second argument is the ISXC alarm label as a UTF8 string. The third argumen…
1.3.6.1.4.1.318.747NodeisxcCriticalAlarmClearedCRITICAL: An ISXC Alarm has been cleared. The first argument is the unique ISXC alarm ID. The second argument is the ISXC alarm label as a UTF8 string. The thi…
1.3.6.1.4.1.318.748NodeisxcFailureAlarmFAILURE: An ISXC Alarm exists. The first argument is the unique ISXC alarm ID. The second argument is the ISXC alarm label as a UTF8 string. The third argument…
1.3.6.1.4.1.318.749NodeisxcFailureAlarmClearedFAILURE: An ISXC Alarm has been cleared. The first argument is the unique ISXC alarm ID. The second argument is the ISXC alarm label as a UTF8 string. The thir…
1.3.6.1.4.1.318.750NoderpduCriticalConditionSEVERE: A RPDU critical condition has been detected. The first variable is the serial number. The second variable is the device name. The third variable is the…
1.3.6.1.4.1.318.751NoderpduCriticalConditionClearedINFORMATIONAL: A RPDU critical condition has been cleared. The first variable is the serial number. The second variable is the device name. The third variable …
1.3.6.1.4.1.318.752NoderpduWarningConditionWARNING: A RPDU warning condition has been detected. The first variable is the serial number. The second variable is the device name. The third variable is the…
1.3.6.1.4.1.318.753NoderpduWarningConditionClearedWARNING: A RPDU warning condition has been cleared. The first variable is the serial number. The second variable is the device name. The third variable is the …
1.3.6.1.4.1.318.754NoderpduInformationalConditionINFORMATIONAL: A RPDU informational condition has been detected. The first variable is the serial number. The second variable is the device name. The third var…
1.3.6.1.4.1.318.755NoderpduInformationalConditionClearedINFORMATIONAL: A RPDU informational condition has been cleared. The first variable is the serial number. The second variable is the device name. The third vari…
1.3.6.1.4.1.318.756NodeisxModularCoolingFanAlarmSEVERE: The device's internal cooling fans have failed. The first argument is the host device serial number. The second argument is the host device name.
1.3.6.1.4.1.318.757NodeisxModularCoolingFanAlarmClearedINFORMATIONAL: The device's internal cooling fans are now functioning properly. The first argument is the host device serial number. The second argument is the…
1.3.6.1.4.1.318.758NodeupsFirmwareUpdateStartedWARNING: Updating UPS firmware.
1.3.6.1.4.1.318.759NodeupsFirmwareUpdateFinishedINFORMATIONAL: Finished updating UPS firmware.
1.3.6.1.4.1.318.760NodeupsFirmwareUpdateSucceededINFORMATIONAL: UPS firmware update succeeded.
1.3.6.1.4.1.318.761NodeupsFirmwareUpdateFailedWARNING: UPS firmware update failed.
1.3.6.1.4.1.318.762NodeupsHasNoValidFirmwareSEVERE: UPS has no valid firmware.
1.3.6.1.4.1.318.763NodeupsHasNoValidFirmwareClearedINFORMATIONAL: UPS now has a valid firmware.
1.3.6.1.4.1.318.767NodeupsLocalDisplayButtonFaultWARNING: A local display button fault exists.
1.3.6.1.4.1.318.768NodeupsLocalDisplayButtonFaultClearedINFORMATIONAL: A local display button fault no longer exists.
1.3.6.1.4.1.318.769NodeupsNeedsFactorySetupFaultSEVERE: UPS needs factory setup.
1.3.6.1.4.1.318.770NodeupsNeedsFactorySetupFaultClearedINFORMATIONAL: UPS no longer needs factory setup.
1.3.6.1.4.1.318.771NodeupsEPOActiveSEVERE: Emergency Power Off (EPO) active.
1.3.6.1.4.1.318.772NodeupsEPOActiveClearedINFORMATIONAL: Emergency Power Off (EPO) now inactive.
1.3.6.1.4.1.318.773NodeupsFirmwareMismatchSEVERE: A firmware mismatch error exists.
1.3.6.1.4.1.318.774NodeupsFirmwareMismatchClearedINFORMATIONAL: A firmware mismatch error no longer exists.
1.3.6.1.4.1.318.775NodeupsOscillatorFailedSEVERE: An oscillator error exists.
1.3.6.1.4.1.318.776NodeupsOscillatorFailedClearedINFORMATIONAL: An oscillator error no longer exists.
1.3.6.1.4.1.318.777NodeupsOnBatteryDueToFaultSEVERE: The UPS is on battery due to an error. Symmetra UPSes: Intelligence module has reported being in self-test for too long. When this happens, the UPS is …
1.3.6.1.4.1.318.778NodeupsOnBatteryDueToFaultClearedINFORMATIONAL: The UPS is no longer on battery due to an error.
1.3.6.1.4.1.318.779NodepcnsCriticalEventActiveSEVERE: PowerChute Network Shutdown has begun a safe shutdown of the host.
1.3.6.1.4.1.318.780NodepcnsCriticalEventResolvedINFORMATIONAL: PowerChute Network Shutdown critical event resolved. Safe shutdown will continue.
1.3.6.1.4.1.318.781NodepcnsNetworkComsLostSEVERE: PowerChute cannot communicate with NMC
1.3.6.1.4.1.318.782NodepcnsNetworkComsLostResolvedINFORMATIONAL: PowerChute can communicate with NMC again.
1.3.6.1.4.1.318.783NodepcnsNMCComsLostSEVERE: NMC cannot communicate with UPS.
1.3.6.1.4.1.318.784NodepcnsNMCComsLostResolvedINFORMATIONAL: NMC can communicate with UPS again.
1.3.6.1.4.1.318.785NodepcnsTestINFORMATIONAL: PowerChute has sent a test trap.
1.3.6.1.4.1.318.786NodepcnsUpdateAvailableINFORMATIONAL: PowerChute has detected that a newer version is available.
1.3.6.1.4.1.318.787NodetemporaryBypassWARNING: UPS on temporary bypass
1.3.6.1.4.1.318.790NodepcbeCriticalEventActiveSEVERE: PowerChute Business Edition has begun a safe shutdown of the host.
1.3.6.1.4.1.318.791NodepcbeCriticalEventResolvedINFORMATIONAL: PowerChute Business Edition critical event resolved. Safe shutdown will continue.
1.3.6.1.4.1.318.792NodepcbeComsLostSEVERE: PowerChute cannot communicate with UPS
1.3.6.1.4.1.318.793NodepcbeComsLostResolvedINFORMATIONAL: PowerChute can communicate with UPS again.
1.3.6.1.4.1.318.794NodepcbeTestINFORMATIONAL: PowerChute has sent a test trap.
1.3.6.1.4.1.318.795NodepcbeUpdateAvailableINFORMATIONAL: PowerChute has detected that a newer version is available.
1.3.6.1.4.1.318.796NodepmmCriticalConditionSEVERE: A PMM critical condition has been detected. The first variable is the serial number. The second variable is the device name. The third variable is the …
1.3.6.1.4.1.318.797NodepmmCriticalConditionClearedINFORMATIONAL: A PMM critical condition has been cleared. The first variable is the serial number. The second variable is the device name. The third variable i…
1.3.6.1.4.1.318.798NodepmmWarningConditionWARNING: A PMM warning condition has been detected. The first variable is the serial number. The second variable is the device name. The third variable is the …
1.3.6.1.4.1.318.799NodepmmWarningConditionClearedWARNING: A PMM warning condition has been cleared. The first variable is the serial number. The second variable is the device name. The third variable is the e…
1.3.6.1.4.1.318.800NodepmmInformationalConditionINFORMATIONAL: A PMM informational condition has been detected. The first variable is the serial number. The second variable is the device name. The third vari…
1.3.6.1.4.1.318.801NodepmmInformationalConditionClearedINFORMATIONAL: A PMM informational condition has been cleared. The first variable is the serial number. The second variable is the device name. The third varia…