PowerNet-PDU
808 objects
No module-level DESCRIPTION found.
Imported Objects
| RFC-1212 | OBJECT-TYPE |
| RFC-1215 | TRAP-TYPE |
| RFC1155-SMI | enterprises Gauge IpAddress Opaque TimeTicks |
| RFC1213-MIB | DisplayString |
| OID | Name | Access | Status | Description |
|---|---|---|---|---|
| 1.3.6.1.2.1 | Nodemconfig | |||
| 1.3.6.1.2.1.1 | ScalarmconfigNumTrapReceivers | read-only | current | The number of managers to send traps to. |
| 1.3.6.1.2.1.2 | TablemconfigTrapReceiverTable | not-accessible | current | A list of managers to send traps to. The number of entries is given by the value of mconfigNumTrapReceivers. |
| 1.3.6.1.2.1.2.1 | RowmconfigTrapReceiverEntry | not-accessible | current | The managers to send traps to. |
| 1.3.6.1.2.1.2.1.1 | ColumntrapIndex | read-only | current | The index to a trap receiver entry. |
| 1.3.6.1.2.1.2.1.2 | ColumnreceiverAddr | read-write | current | The IP address of the manager to send a trap to. |
| 1.3.6.1.2.1.2.1.3 | ColumncommunityString | read-write | current | The community name to use in the trap when sent to the manager. |
| 1.3.6.1.2.1.2.1.4 | Columnseverity | read-only | obsolete | The severity threshold of traps to send to the manager. traps are labeled in severity as informational(1), warning(2), severe(3). Only traps of equal or greate… |
| 1.3.6.1.2.1.2.1.5 | ColumnacceptThisReceiver | read-write | current | The value of yes(1) indicates that trap generation for this manager is enabled. The value of no(2) indicates that trap generation for this manager is disabled |
| 1.3.6.1.2.1.2.1.6 | ColumnreceiveTrapType | read-only | obsolete | Type of trap. |
| 1.3.6.1.2.1.3 | ScalarmconfigBOOTPEnabled | read-only | current | The value of yes(1) indicates the PowerNet Adapter is configured to obtain its IP configuration parameters from a BOOTP server. The value of no(2) indicates ad… |
| 1.3.6.1.2.1.4 | ScalarmconfigTFTPServerIP | read-write | current | The IP address of TFTP server. If mconfigBOOTPEnabled is yes(1), then this IP address is provided by BOOTP server and not allowed to be modified; otherwise, th… |
| 1.3.6.1.2.1.5 | ScalarnewCodeAuthentViaTFTP | read-only | current | Once mcontrolRestartAgent is set to loadAndExecuteNewAgent (3), PowerNet adapter will start to load the remote image file, for authentication only, instead of … |
| 1.3.6.1.2.1.6 | NodemconfigClock | |||
| 1.3.6.1.2.1.6.1 | ScalarmconfigClockDate | read-write | current | The current date in the mm/dd/yyyy format. Example: 01/01/2000. |
| 1.3.6.1.2.1.6.2 | ScalarmconfigClockTime | read-write | current | The current time in the hh:mm:ss am/pm format. Example: 12:00:00 am. |
| 1.3.6.1.2.2 | Nodemcontrol | |||
| 1.3.6.1.2.2.1 | ScalarmcontrolRestartAgent | read-write | current | Setting this OID to restartCurrentAgent (1) will restart the same SNMP agent code currently saved in flash memory. Setting this OID to loadAndExecuteNewAgent (… |
| 1.3.6.1.2.3 | Nodemtrapargs | |||
| 1.3.6.1.2.3.1 | ScalarmtrapargsInteger | read-only | current | This OID allows traps to be sent with an integer argument that my not be defined in the MIB. A get of this OID will return 0. |
| 1.3.6.1.2.3.2 | ScalarmtrapargsIpAddress | read-only | current | This OID allows traps to be sent with an IP address argument that my not be defined in the MIB. A get of this OID will return 0.0.0.0. |
| 1.3.6.1.2.3.3 | ScalarmtrapargsString | read-only | current | This OID allows traps to be sent with an octet string argument that my not be defined in the MIB. A get of this OID will return a NULL string. |
| 1.3.6.1.2.3.4 | ScalarmtrapargsGauge | read-only | current | This OID allows traps to be sent with a Gauge argument that my not be defined in the MIB. A get of this OID will return 0. |
| 1.3.6.1.2.3.5 | ScalarmtrapargsTimeTicks | read-only | current | This OID allows traps to be sent with a TimeTicks argument that my not be defined in the MIB. A get of this OID will return 0. |
| 1.3.6.1.2.3.6 | ScalarmtrapargsInteger02 | read-only | current | This OID allows traps to be sent with an integer argument that my not be defined in the MIB. A get of this OID will return 0. |
| 1.3.6.1.2.3.7 | ScalarmtrapargsInteger03 | read-only | current | This OID allows traps to be sent with an integer argument that my not be defined in the MIB. A get of this OID will return 0. |
| 1.3.6.1.2.3.8 | ScalarmtrapargsIpAddress02 | read-only | current | This OID allows traps to be sent with an IP address argument that my not be defined in the MIB. A get of this OID will return 0.0.0.0. |
| 1.3.6.1.2.3.9 | ScalarmtrapargsIpAddress03 | read-only | current | This OID allows traps to be sent with an IP address argument that my not be defined in the MIB. A get of this OID will return 0.0.0.0. |
| 1.3.6.1.2.3.10 | ScalarmtrapargsString02 | read-only | current | This OID allows traps to be sent with an octet string argument that my not be defined in the MIB. A get of this OID will return a NULL string. |
| 1.3.6.1.2.3.11 | ScalarmtrapargsString03 | read-only | current | This OID allows traps to be sent with an octet string argument that my not be defined in the MIB. A get of this OID will return a NULL string. |
| 1.3.6.1.2.3.12 | ScalarmtrapargsGauge02 | read-only | current | This OID allows traps to be sent with a Gauge argument that my not be defined in the MIB. A get of this OID will return 0. |
| 1.3.6.1.2.3.13 | ScalarmtrapargsGauge03 | read-only | current | This OID allows traps to be sent with a Gauge argument that my not be defined in the MIB. A get of this OID will return 0. |
| 1.3.6.1.2.3.14 | ScalarmtrapargsTimeTicks02 | read-only | current | This OID allows traps to be sent with a TimeTicks argument that my not be defined in the MIB. A get of this OID will return 0. |
| 1.3.6.1.2.3.15 | ScalarmtrapargsTimeTicks03 | read-only | current | This OID allows traps to be sent with a TimeTicks argument that my not be defined in the MIB. A get of this OID will return 0. |
| 1.3.6.1.2.3.16 | ScalarmtrapargsString04 | read-only | current | This OID allows traps to be sent with an octet string argument that my not be defined in the MIB. A get of this OID will return a NULL string. |
| 1.3.6.1.2.3.17 | ScalarmtrapargsString05 | read-only | current | This OID allows traps to be sent with an octet string argument that my not be defined in the MIB. A get of this OID will return a NULL string. |
| 1.3.6.1.2.3.18 | ScalarmtrapargsInteger04 | read-only | current | This OID allows traps to be sent with an integer argument that my not be defined in the MIB. A get of this OID will return 0. |
| 1.3.6.1.2.3.19 | ScalarmtrapargsInteger05 | read-only | current | This OID allows traps to be sent with an integer argument that my not be defined in the MIB. A get of this OID will return 0. |
| 1.3.6.1.2.3.20 | ScalarmtrapargsString06 | read-only | current | This OID allows traps to be sent with an octet string argument that my not be defined in the MIB. A get of this OID will return a NULL string. |
| 1.3.6.1.2.3.21 | ScalarmtrapargsString07 | read-only | current | This OID allows traps to be sent with an octet string argument that my not be defined in the MIB. A get of this OID will return a NULL string. |
| 1.3.6.1.2.3.22 | ScalarmtrapargsString08 | read-only | current | This OID allows traps to be sent with an octet string argument that my not be defined in the MIB. A get of this OID will return a NULL string. |
| 1.3.6.1.2.3.23 | ScalarmtrapargsOctetString | read-only | current | This OID allows traps to be sent with an octet string argument that my not be defined in the MIB. A get of this OID will return a NULL string. |
| 1.3.6.1.2.3.24 | ScalarmtrapargsOctetString02 | read-only | current | This OID allows traps to be sent with an octet string argument that my not be defined in the MIB. A get of this OID will return a NULL string. |
| 1.3.6.1.2.3.25 | ScalarmtrapargsOctetString03 | read-only | current | This OID allows traps to be sent with an octet string argument that my not be defined in the MIB. A get of this OID will return a NULL string. |
| 1.3.6.1.2.3.26 | ScalarmtrapargsOctetString04 | read-only | current | This OID allows traps to be sent with an octet string argument that my not be defined in the MIB. A get of this OID will return a NULL string. |
| 1.3.6.1.2.3.27 | ScalarmtrapargsOctetString05 | read-only | current | This OID allows traps to be sent with an octet string argument that my not be defined in the MIB. A get of this OID will return a NULL string. |
| 1.3.6.1.2.3.28 | ScalarmtrapargsOctetString06 | read-only | current | This OID allows traps to be sent with an octet string argument that my not be defined in the MIB. A get of this OID will return a NULL string. |
| 1.3.6.1.2.3.29 | ScalarmtrapargsOctetString07 | read-only | current | This OID allows traps to be sent with an octet string argument that my not be defined in the MIB. A get of this OID will return a NULL string. |
| 1.3.6.1.2.3.30 | ScalarmtrapargsOctetString08 | read-only | current | This OID allows traps to be sent with an octet string argument that my not be defined in the MIB. A get of this OID will return a NULL string. |
| 1.3.6.1.2.4 | Nodemfiletransfer | |||
| 1.3.6.1.2.4.1 | NodemfiletransferStatus | |||
| 1.3.6.1.2.4.1.1 | ScalarmfiletransferStatusLastTransferResult | read-only | deprecated | This OID has been deprecated. Once mfiletransferControlInitiateFileTransfer is set to a value other than doNotInitiateFileTransfer a file transfer of mfiletran… |
| 1.3.6.1.2.4.2 | NodemfiletransferConfig | |||
| 1.3.6.1.2.4.2.1 | NodemfiletransferConfigSettings | |||
| 1.3.6.1.2.4.2.1.1 | ScalarmfiletransferConfigSettingsFilename | read-write | deprecated | This OID has been deprecated. The path and name of the file to transfer using the mfiletransferControlInitiateFileTransfer OID. If the file to transfer exists … |
| 1.3.6.1.2.4.2.2 | NodemfiletransferConfigTFTP | |||
| 1.3.6.1.2.4.2.2.1 | ScalarmfiletransferConfigTFTPServerAddress | read-write | deprecated | This OID has been deprecated. The IP Address in dotted decimal notation of the TFTP server involved in the file transfer. |
| 1.3.6.1.2.4.2.3 | NodemfiletransferConfigFTP | |||
| 1.3.6.1.2.4.2.3.1 | ScalarmfiletransferConfigFTPServerAddress | read-write | deprecated | This OID has been deprecated. The IP Address in dotted decimal notation of the FTP server involved in the file transfer. |
| 1.3.6.1.2.4.2.3.2 | ScalarmfiletransferConfigFTPServerUser | read-write | deprecated | This OID has been deprecated. The user identification for logging into the FTP server specified with mfiletransferConfigFTPServerAddress. |
| 1.3.6.1.2.4.2.3.3 | ScalarmfiletransferConfigFTPServerPassword | read-write | deprecated | This OID has been deprecated. The password for logging into the FTP server specified with mfiletransferConfigFTPServerAddress. |
| 1.3.6.1.2.4.3 | NodemfiletransferControl | |||
| 1.3.6.1.2.4.3.1 | ScalarmfiletransferControlInitiateFileTransfer | read-write | deprecated | This OID has been deprecated. Setting this OID to doNotInitiateFileTransfer (1) will do nothing. Setting this OID to initiateFileTransferDownloadViaTFTP (2) wi… |
| 1.3.6.1.4.1.318 | NodePDU | |||
| 1.3.6.1.4.1.318.1 | Nodeproducts | |||
| 1.3.6.1.4.1.318.1.1 | Nodehardware | |||
| 1.3.6.1.4.1.318.1.1.26 | NoderPDU2 | |||
| 1.3.6.1.4.1.318.1.1.26.1 | ScalarrPDU2IdentTableSize | read-only | mandatory | The total number of Rack PDUs |
| 1.3.6.1.4.1.318.1.1.26.2 | TablerPDU2IdentTable | not-accessible | mandatory | A table of Rack PDU identification data |
| 1.3.6.1.4.1.318.1.1.26.2.1 | RowrPDU2IdentEntry | not-accessible | mandatory | Identification data from Rack PDU being queried |
| 1.3.6.1.4.1.318.1.1.26.2.1.1 | ColumnrPDU2IdentIndex | read-only | mandatory | The index to the Rack PDU identification table entry |
| 1.3.6.1.4.1.318.1.1.26.2.1.2 | ColumnrPDU2IdentModule | read-only | mandatory | The user-defined Rack PDU numeric ID |
| 1.3.6.1.4.1.318.1.1.26.2.1.3 | ColumnrPDU2IdentName | read-only | mandatory | A user-defined string identifying the Rack PDU |
| 1.3.6.1.4.1.318.1.1.26.2.1.4 | ColumnrPDU2IdentLocation | read-only | mandatory | A user-defined string identifying the location of the Rack PDU |
| 1.3.6.1.4.1.318.1.1.26.2.1.5 | ColumnrPDU2IdentHardwareRev | read-only | mandatory | The Rack PDU hardware version |
| 1.3.6.1.4.1.318.1.1.26.2.1.6 | ColumnrPDU2IdentFirmwareRev | read-only | mandatory | The Rack PDU firmware version |
| 1.3.6.1.4.1.318.1.1.26.2.1.7 | ColumnrPDU2IdentDateOfManufacture | read-only | mandatory | The date the Rack PDU was manufactured in mm/dd/yyyy format |
| 1.3.6.1.4.1.318.1.1.26.2.1.8 | ColumnrPDU2IdentModelNumber | read-only | mandatory | The Rack PDU model number |
| 1.3.6.1.4.1.318.1.1.26.2.1.9 | ColumnrPDU2IdentSerialNumber | read-only | mandatory | The Rack PDU serial number |
| 1.3.6.1.4.1.318.1.1.26.2.1.10 | ColumnrPDU2IdentContact | read-only | mandatory | A user-defined string identifying the person to contact regarding the Rack PDU |
| 1.3.6.1.4.1.318.1.1.26.2.1.11 | ColumnrPDU2IdentBootMonitorRev | read-only | mandatory | The Rack PDU Boot Monitor version |
| 1.3.6.1.4.1.318.1.1.26.2.1.12 | ColumnrPDU2IdentLongDescription | read-only | mandatory | The Rack PDU Long Description name |
| 1.3.6.1.4.1.318.1.1.26.2.1.13 | ColumnrPDU2IdentNMCSerialNumber | read-only | mandatory | The Rack PDU Network Management Card (NMC) serial number |
| 1.3.6.1.4.1.318.1.1.26.3 | ScalarrPDU2DeviceTableSize | read-only | mandatory | The total number of Rack PDUs |
| 1.3.6.1.4.1.318.1.1.26.4 | NoderPDU2Device | |||
| 1.3.6.1.4.1.318.1.1.26.4.1 | TablerPDU2DeviceConfigTable | not-accessible | mandatory | A table of Rack PDU configuration data |
| 1.3.6.1.4.1.318.1.1.26.4.1.1 | RowrPDU2DeviceConfigEntry | not-accessible | mandatory | Configuration data from Rack PDU being queried |
| 1.3.6.1.4.1.318.1.1.26.4.1.1.1 | ColumnrPDU2DeviceConfigIndex | read-only | mandatory | The index to the Rack PDU table entry |
| 1.3.6.1.4.1.318.1.1.26.4.1.1.2 | ColumnrPDU2DeviceConfigModule | read-write | mandatory | The user-defined Rack PDU numeric ID |
| 1.3.6.1.4.1.318.1.1.26.4.1.1.3 | ColumnrPDU2DeviceConfigName | read-write | mandatory | A user-defined string identifying the Rack PDU |
| 1.3.6.1.4.1.318.1.1.26.4.1.1.4 | ColumnrPDU2DeviceConfigLocation | read-write | mandatory | A user-defined string identifying the location of the Rack PDU |
| 1.3.6.1.4.1.318.1.1.26.4.1.1.5 | ColumnrPDU2DeviceConfigDisplayOrientation | read-write | mandatory | Indicates the intended physical orientation of the display. displayNormal(1) indicates normal orientation displayReverse(2) indicates upside down orientation |
| 1.3.6.1.4.1.318.1.1.26.4.1.1.6 | ColumnrPDU2DeviceConfigColdstartDelay | read-write | mandatory | The amount of delay, measured in seconds, between when power is provided to the Rack PDU and when the Rack PDU provides basic master power to the outlets. Allo… |
| 1.3.6.1.4.1.318.1.1.26.4.1.1.7 | ColumnrPDU2DeviceConfigLowLoadPowerThreshold | read-write | mandatory | User-defined low power draw alarm threshold, measured in tenths of kilowatts. Models that do not support this feature will respond to this OID with a value of … |
| 1.3.6.1.4.1.318.1.1.26.4.1.1.8 | ColumnrPDU2DeviceConfigNearOverloadPowerThreshold | read-write | mandatory | User-defined near power overload threshold, measured in tenths of kilowatts. Models that do not support this feature will respond to this OID with a value of -… |
| 1.3.6.1.4.1.318.1.1.26.4.1.1.9 | ColumnrPDU2DeviceConfigOverloadPowerThreshold | read-write | mandatory | User-defined power overload threshold, measured in tenths of kilowatts. Models that do not support this feature will respond to this OID with a value of -1. |
| 1.3.6.1.4.1.318.1.1.26.4.1.1.10 | ColumnrPDU2DeviceConfigDevicePeakPowerReset | read-write | mandatory | Setting this OID to reset (2) will cause the existing peak power value to be replaced by the current load power value. Getting this OID will do nothing and ret… |
| 1.3.6.1.4.1.318.1.1.26.4.1.1.11 | ColumnrPDU2DeviceConfigDeviceEnergyReset | read-write | mandatory | Setting this OID to reset (2) will cause the device energy meter value to be reset to zero. Getting this OID in models that support this feature will do nothin… |
| 1.3.6.1.4.1.318.1.1.26.4.1.1.12 | ColumnrPDU2DeviceConfigOutletsEnergyReset | read-write | mandatory | Setting this OID to reset (2) will cause the all outlet energy meter values to be reset to zero. Getting this OID will do nothing and return the noOperation(1)… |
| 1.3.6.1.4.1.318.1.1.26.4.1.1.13 | ColumnrPDU2DeviceConfigOutletsPeakLoadReset | read-write | mandatory | Setting this OID to reset (2) will cause the all outlet peak load values to be reset to zero. Getting this OID will do nothing and return the noOperation(1) va… |
| 1.3.6.1.4.1.318.1.1.26.4.1.1.14 | ColumnrPDU2DeviceConfigContact | read-write | mandatory | A user-defined string identifying the person to contact regarding the Rack PDU |
| 1.3.6.1.4.1.318.1.1.26.4.2 | TablerPDU2DevicePropertiesTable | not-accessible | mandatory | A table of Rack PDU properties |
| 1.3.6.1.4.1.318.1.1.26.4.2.1 | RowrPDU2DevicePropertiesEntry | not-accessible | mandatory | Properties of the Rack PDU being queried |
| 1.3.6.1.4.1.318.1.1.26.4.2.1.1 | ColumnrPDU2DevicePropertiesIndex | read-only | mandatory | The index to the Rack PDU properties table entry |
| 1.3.6.1.4.1.318.1.1.26.4.2.1.2 | ColumnrPDU2DevicePropertiesModule | read-only | mandatory | The user-defined Rack PDU numeric ID |
| 1.3.6.1.4.1.318.1.1.26.4.2.1.3 | ColumnrPDU2DevicePropertiesName | read-only | mandatory | A user-defined string identifying the Rack PDU |
| 1.3.6.1.4.1.318.1.1.26.4.2.1.4 | ColumnrPDU2DevicePropertiesNumOutlets | read-only | mandatory | The number of outlets on the Rack PDU |
| 1.3.6.1.4.1.318.1.1.26.4.2.1.5 | ColumnrPDU2DevicePropertiesNumSwitchedOutlets | read-only | mandatory | The number of switched outlets on the Rack PDU |
| 1.3.6.1.4.1.318.1.1.26.4.2.1.6 | ColumnrPDU2DevicePropertiesNumMeteredOutlets | read-only | mandatory | The number of metered outlets on the Rack PDU |
| 1.3.6.1.4.1.318.1.1.26.4.2.1.7 | ColumnrPDU2DevicePropertiesNumPhases | read-only | mandatory | The number of phases present in the Rack PDU |
| 1.3.6.1.4.1.318.1.1.26.4.2.1.8 | ColumnrPDU2DevicePropertiesNumMeteredBanks | read-only | mandatory | The number of metered banks present in the Rack PDU |
| 1.3.6.1.4.1.318.1.1.26.4.2.1.9 | ColumnrPDU2DevicePropertiesMaxCurrentRating | read-only | mandatory | The maximum current rating, measured in Amps, for the Rack PDU |
| 1.3.6.1.4.1.318.1.1.26.4.2.1.10 | ColumnrPDU2DevicePropertiesOrientation | read-only | mandatory | Rack PDU orientation |
| 1.3.6.1.4.1.318.1.1.26.4.2.1.11 | ColumnrPDU2DevicePropertiesOutletLayout | read-only | mandatory | Getting this OID will return outlet layout for the device. seqPhaseToNeutral(1) indicates outlet layout as follows: 1:1-N,2:2-N,3:3-N,4:1-N,5:2-N,... or for si… |
| 1.3.6.1.4.1.318.1.1.26.4.2.1.12 | ColumnrPDU2DevicePropertiesMaxPhaseCurrentRating | read-only | mandatory | The maximum current rating, measured in Amps, for the Rack PDU |
| 1.3.6.1.4.1.318.1.1.26.4.2.1.13 | ColumnrPDU2DevicePropertiesDevicePowerRating | read-only | mandatory | The maximum power rating, measured in tenths of kilowatts, for the Rack PDU |
| 1.3.6.1.4.1.318.1.1.26.4.3 | TablerPDU2DeviceStatusTable | not-accessible | mandatory | A table of Rack PDU status information |
| 1.3.6.1.4.1.318.1.1.26.4.3.1 | RowrPDU2DeviceStatusEntry | not-accessible | mandatory | Status information from the Rack PDU being queried |
| 1.3.6.1.4.1.318.1.1.26.4.3.1.1 | ColumnrPDU2DeviceStatusIndex | read-only | mandatory | The index to the Rack PDU status table entry |
| 1.3.6.1.4.1.318.1.1.26.4.3.1.2 | ColumnrPDU2DeviceStatusModule | read-only | mandatory | The user-defined Rack PDU numeric ID |
| 1.3.6.1.4.1.318.1.1.26.4.3.1.3 | ColumnrPDU2DeviceStatusName | read-only | mandatory | A user-defined string identifying the Rack PDU |
| 1.3.6.1.4.1.318.1.1.26.4.3.1.4 | ColumnrPDU2DeviceStatusLoadState | read-only | mandatory | Indicates the present load status of the Rack PDU. Models that do not support this feature will respond to this OID with a value of notsupported (5). |
| 1.3.6.1.4.1.318.1.1.26.4.3.1.5 | ColumnrPDU2DeviceStatusPower | read-only | mandatory | The power consumption of the Rack PDU load in hundredths of kilowatts. Models that do not support this feature will respond to this OID with a value of -1. |
| 1.3.6.1.4.1.318.1.1.26.4.3.1.6 | ColumnrPDU2DeviceStatusPeakPower | read-only | mandatory | The peak power consumption of the Rack PDU load in hundredths of kilowatts. Models that do not support this feature will respond to this OID with a value of -1. |
| 1.3.6.1.4.1.318.1.1.26.4.3.1.7 | ColumnrPDU2DeviceStatusPeakPowerTimestamp | read-only | mandatory | Indicates the date and time that peak power consumption occurred. Models that do not support this feature will respond to this OID with string 'notsupported'. |
| 1.3.6.1.4.1.318.1.1.26.4.3.1.8 | ColumnrPDU2DeviceStatusPeakPowerStartTime | read-only | mandatory | Indicates the date and time of the last device peak power reset. Models that do not support this feature will respond to this OID with string 'notsupported'. |
| 1.3.6.1.4.1.318.1.1.26.4.3.1.9 | ColumnrPDU2DeviceStatusEnergy | read-only | mandatory | A user resettable energy meter measuring Rack PDU load energy consumption in tenths of kilowatt-hours. Models that do not support this feature will respond to … |
| 1.3.6.1.4.1.318.1.1.26.4.3.1.10 | ColumnrPDU2DeviceStatusEnergyStartTime | read-only | mandatory | Indicates the date and time of the last device energy meter reset. Models that do not support this feature will respond to this OID with string 'notsupported'. |
| 1.3.6.1.4.1.318.1.1.26.4.3.1.11 | ColumnrPDU2DeviceStatusCommandPending | read-only | mandatory | Indicates whether or not the device is processing a pending command. If the commandPendingUnknown (3) value is returned, all devices powered by the Rack PDU sh… |
| 1.3.6.1.4.1.318.1.1.26.4.3.1.12 | ColumnrPDU2DeviceStatusPowerSupplyAlarm | read-only | mandatory | Indicates a power supply alarm is active when value equals alarm (2) |
| 1.3.6.1.4.1.318.1.1.26.4.3.1.13 | ColumnrPDU2DeviceStatusPowerSupply1Status | read-only | mandatory | Indicates whether or not an alarm is active in Power Supply 1 |
| 1.3.6.1.4.1.318.1.1.26.4.3.1.14 | ColumnrPDU2DeviceStatusPowerSupply2Status | read-only | mandatory | Indicates whether or not an alarm is active in Power Supply 2 |
| 1.3.6.1.4.1.318.1.1.26.4.3.1.15 | ColumnrPDU2DeviceStatusOutletsEnergyStartTime | read-only | mandatory | Indicates the date and time of the last outlets energy meter reset. Models that do not support this feature will respond to this OID with string 'notsupported'. |
| 1.3.6.1.4.1.318.1.1.26.4.3.1.16 | ColumnrPDU2DeviceStatusApparentPower | read-only | mandatory | The apparent power consumption of the Rack PDU load in hundredths of kiloVoltAmps (kVA). Models that do not support this feature will respond to this OID with … |
| 1.3.6.1.4.1.318.1.1.26.4.3.1.17 | ColumnrPDU2DeviceStatusPowerFactor | read-only | mandatory | The power factor of the Rack PDU load in hundredths. Models that do not support this feature will respond to this OID with a value of -1. |
| 1.3.6.1.4.1.318.1.1.26.4.3.1.18 | ColumnrPDU2DeviceStatusNPSType | read-only | mandatory | The device NPS status: notNPS (1) indicates the Rack PDU is not in an NPS group. host (2) indicates the Rack PDU has been designated as a host in an NPS group.… |
| 1.3.6.1.4.1.318.1.1.26.4.3.1.19 | ColumnrPDU2DeviceStatusResidualPower | read-only | mandatory | The measured device residual power from the PDU meters in hundredths of kiloVoltAmps. |
| 1.3.6.1.4.1.318.1.1.26.4.3.1.20 | ColumnrPDU2DeviceStatusFrequency | read-only | mandatory | The measured device frequency from the PDU meters in tenths of Hz. |
| 1.3.6.1.4.1.318.1.1.26.4.4 | TablerPDU2DeviceControlTable | not-accessible | mandatory | A table of Rack PDU control data |
| 1.3.6.1.4.1.318.1.1.26.4.4.1 | RowrPDU2DeviceControlEntry | not-accessible | mandatory | Control data from Rack PDU being queried |
| 1.3.6.1.4.1.318.1.1.26.4.4.1.1 | ColumnrPDU2DeviceControlIndex | read-only | mandatory | The index to the Rack PDU control table entry |
| 1.3.6.1.4.1.318.1.1.26.4.4.1.2 | ColumnrPDU2DeviceControlModule | read-only | mandatory | The user-defined Rack PDU numeric ID |
| 1.3.6.1.4.1.318.1.1.26.4.4.1.3 | ColumnrPDU2DeviceControlName | read-only | mandatory | A user-defined string identifying the Rack PDU |
| 1.3.6.1.4.1.318.1.1.26.4.4.1.4 | ColumnrPDU2DeviceControlCommand | read-write | mandatory | Setting this OID to immediateAllOn (1) will turn all outlets on immediately. Setting this OID to delayedAllOn (2) will turn all outlets on as defined by each o… |
| 1.3.6.1.4.1.318.1.1.26.4.5 | ScalarrPDU2DeviceMap | read-only | mandatory | The Map of connected Rack PDUs |
| 1.3.6.1.4.1.318.1.1.26.5 | ScalarrPDU2PhaseTableSize | read-only | mandatory | The number of connected Rack PDU phases |
| 1.3.6.1.4.1.318.1.1.26.6 | NoderPDU2Phase | |||
| 1.3.6.1.4.1.318.1.1.26.6.1 | TablerPDU2PhaseConfigTable | not-accessible | mandatory | A table of Rack PDU phase configuration data |
| 1.3.6.1.4.1.318.1.1.26.6.1.1 | RowrPDU2PhaseConfigEntry | not-accessible | mandatory | Configuration data from currently queried Rack PDU phase |
| 1.3.6.1.4.1.318.1.1.26.6.1.1.1 | ColumnrPDU2PhaseConfigIndex | read-only | mandatory | The index to the Rack PDU phase configuration table entry |
| 1.3.6.1.4.1.318.1.1.26.6.1.1.2 | ColumnrPDU2PhaseConfigModule | read-only | mandatory | The user-defined Rack PDU numeric ID |
| 1.3.6.1.4.1.318.1.1.26.6.1.1.3 | ColumnrPDU2PhaseConfigNumber | read-only | mandatory | The numeric phase ID |
| 1.3.6.1.4.1.318.1.1.26.6.1.1.4 | ColumnrPDU2PhaseConfigOverloadRestriction | read-write | mandatory | This OID controls the behavior of a Switched Rack PDU phase when an overload condition is possible and additional outlets are requested to be turned on. Settin… |
| 1.3.6.1.4.1.318.1.1.26.6.1.1.5 | ColumnrPDU2PhaseConfigLowLoadCurrentThreshold | read-write | mandatory | User-defined low load phase current threshold in Amps |
| 1.3.6.1.4.1.318.1.1.26.6.1.1.6 | ColumnrPDU2PhaseConfigNearOverloadCurrentThreshold | read-write | mandatory | User-defined near phase overload warning threshold in Amps |
| 1.3.6.1.4.1.318.1.1.26.6.1.1.7 | ColumnrPDU2PhaseConfigOverloadCurrentThreshold | read-write | mandatory | User-defined phase overload current threshold in Amps |
| 1.3.6.1.4.1.318.1.1.26.6.1.1.8 | ColumnrPDU2PhaseConfigPhasePeakCurrentReset | read-write | mandatory | Setting this OID to reset (2) will cause the existing peak current value to be replaced by the present load current value. Getting this OID will do nothing and… |
| 1.3.6.1.4.1.318.1.1.26.6.2 | TablerPDU2PhasePropertiesTable | not-accessible | mandatory | A table of Rack PDU phase properties |
| 1.3.6.1.4.1.318.1.1.26.6.2.1 | RowrPDU2PhasePropertiesEntry | not-accessible | mandatory | Properties of the currently queried Rack PDU phase |
| 1.3.6.1.4.1.318.1.1.26.6.2.1.1 | ColumnrPDU2PhasePropertiesIndex | read-only | mandatory | The index to the Rack PDU phase properties table entry |
| 1.3.6.1.4.1.318.1.1.26.6.2.1.2 | ColumnrPDU2PhasePropertiesModule | read-only | mandatory | The user-defined Rack PDU numeric ID |
| 1.3.6.1.4.1.318.1.1.26.6.2.1.3 | ColumnrPDU2PhasePropertiesNumber | read-only | mandatory | The numeric phase ID |
| 1.3.6.1.4.1.318.1.1.26.6.3 | TablerPDU2PhaseStatusTable | not-accessible | mandatory | A table of Rack PDU phase status data |
| 1.3.6.1.4.1.318.1.1.26.6.3.1 | RowrPDU2PhaseStatusEntry | not-accessible | mandatory | Status data from currently queried Rack PDU phase |
| 1.3.6.1.4.1.318.1.1.26.6.3.1.1 | ColumnrPDU2PhaseStatusIndex | read-only | mandatory | The index to the Rack PDU phase status table entry |
| 1.3.6.1.4.1.318.1.1.26.6.3.1.2 | ColumnrPDU2PhaseStatusModule | read-only | mandatory | The user-defined Rack PDU numeric ID |
| 1.3.6.1.4.1.318.1.1.26.6.3.1.3 | ColumnrPDU2PhaseStatusNumber | read-only | mandatory | The numeric phase ID |
| 1.3.6.1.4.1.318.1.1.26.6.3.1.4 | ColumnrPDU2PhaseStatusLoadState | read-only | mandatory | Indicates the present load status of the Rack PDU phase being queried |
| 1.3.6.1.4.1.318.1.1.26.6.3.1.5 | ColumnrPDU2PhaseStatusCurrent | read-only | mandatory | Indicates the current draw, in tenths of Amps, of the load on the Rack PDU phase being queried |
| 1.3.6.1.4.1.318.1.1.26.6.3.1.6 | ColumnrPDU2PhaseStatusVoltage | read-only | mandatory | Indicates the Voltage, in Volts, of the Rack PDU phase being queried. Models that do not support this feature will respond to this OID with a value of -1. |
| 1.3.6.1.4.1.318.1.1.26.6.3.1.7 | ColumnrPDU2PhaseStatusPower | read-only | mandatory | Indicates the load power, in hundredths of kilowatts (kW), consumed on the Rack PDU phase being queried. Models that do not support this feature will respond t… |
| 1.3.6.1.4.1.318.1.1.26.6.3.1.8 | ColumnrPDU2PhaseStatusApparentPower | read-only | mandatory | Indicates the load apparent power, in hundredths of kiloVoltAmps (kVA), consumed on the Rack PDU phase being queried. Models that do not support this feature w… |
| 1.3.6.1.4.1.318.1.1.26.6.3.1.9 | ColumnrPDU2PhaseStatusPowerFactor | read-only | mandatory | Indicates the load power factor, in hundredths, of the Rack PDU phase being queried. Models that do not support this feature will respond to this OID with a va… |
| 1.3.6.1.4.1.318.1.1.26.6.3.1.10 | ColumnrPDU2PhaseStatusPeakCurrent | read-only | mandatory | The peak current of the Rack PDU phase load in tenths of Amps |
| 1.3.6.1.4.1.318.1.1.26.6.3.1.11 | ColumnrPDU2PhaseStatusPeakCurrentTimestamp | read-only | mandatory | Indicates the date and time that the peak current occurred |
| 1.3.6.1.4.1.318.1.1.26.6.3.1.12 | ColumnrPDU2PhaseStatusPeakCurrentStartTime | read-only | mandatory | Indicates the date and time of the last phase peak current reset |
| 1.3.6.1.4.1.318.1.1.26.6.3.1.13 | ColumnrPDU2PhaseStatusEnergy | read-only | mandatory | A user resettable energy meter measuring Rack PDU phase load energy consumption in tenths of kilowatt-hours. Models that do not support this feature will respo… |
| 1.3.6.1.4.1.318.1.1.26.7 | ScalarrPDU2BankTableSize | read-only | mandatory | The number of connected Rack PDU banks |
| 1.3.6.1.4.1.318.1.1.26.8 | NoderPDU2Bank | |||
| 1.3.6.1.4.1.318.1.1.26.8.1 | TablerPDU2BankConfigTable | not-accessible | mandatory | A table of Rack PDU bank configuration data |
| 1.3.6.1.4.1.318.1.1.26.8.1.1 | RowrPDU2BankConfigEntry | not-accessible | mandatory | Configuration data from currently queried Rack PDU bank |
| 1.3.6.1.4.1.318.1.1.26.8.1.1.1 | ColumnrPDU2BankConfigIndex | read-only | mandatory | The index to the Rack PDU bank configuration table entry |
| 1.3.6.1.4.1.318.1.1.26.8.1.1.2 | ColumnrPDU2BankConfigModule | read-only | mandatory | The user-defined Rack PDU numeric ID |
| 1.3.6.1.4.1.318.1.1.26.8.1.1.3 | ColumnrPDU2BankConfigNumber | read-only | mandatory | The numeric bank ID |
| 1.3.6.1.4.1.318.1.1.26.8.1.1.4 | ColumnrPDU2BankConfigOverloadRestriction | read-write | mandatory | This OID controls the behavior of a Switched Rack PDU bank when an overload condition is possible and additional outlets are requested to be turned on. Setting… |
| 1.3.6.1.4.1.318.1.1.26.8.1.1.5 | ColumnrPDU2BankConfigLowLoadCurrentThreshold | read-write | mandatory | User-defined low load bank current threshold in Amps |
| 1.3.6.1.4.1.318.1.1.26.8.1.1.6 | ColumnrPDU2BankConfigNearOverloadCurrentThreshold | read-write | mandatory | User-defined near bank overload current warning threshold in Amps |
| 1.3.6.1.4.1.318.1.1.26.8.1.1.7 | ColumnrPDU2BankConfigOverloadCurrentThreshold | read-write | mandatory | User-defined bank overload current threshold in Amps |
| 1.3.6.1.4.1.318.1.1.26.8.1.1.8 | ColumnrPDU2BankConfigBankPeakCurrentReset | read-write | mandatory | Setting this OID to reset (2) will cause the existing peak current value to be replaced by the present load current value. Getting this OID will do nothing and… |
| 1.3.6.1.4.1.318.1.1.26.8.2 | TablerPDU2BankPropertiesTable | not-accessible | mandatory | A table of Rack PDU bank properties |
| 1.3.6.1.4.1.318.1.1.26.8.2.1 | RowrPDU2BankPropertiesEntry | not-accessible | mandatory | Properties of the currently queried Rack PDU bank |
| 1.3.6.1.4.1.318.1.1.26.8.2.1.1 | ColumnrPDU2BankPropertiesIndex | read-only | mandatory | The index to the Rack PDU bank properties table entry |
| 1.3.6.1.4.1.318.1.1.26.8.2.1.2 | ColumnrPDU2BankPropertiesModule | read-only | mandatory | The user-defined Rack PDU numeric ID |
| 1.3.6.1.4.1.318.1.1.26.8.2.1.3 | ColumnrPDU2BankPropertiesNumber | read-only | mandatory | The numeric bank ID |
| 1.3.6.1.4.1.318.1.1.26.8.2.1.4 | ColumnrPDU2BankPropertiesPhaseLayout | read-only | mandatory | This OID describes the outlet phase connections on the referenced bank as follows: seqPhase1ToNeutral(1) indicates that bank outlets are wired from Phase 1 to … |
| 1.3.6.1.4.1.318.1.1.26.8.2.1.5 | ColumnrPDU2BankPropertiesBreakerRating | read-only | mandatory | If bank circuit breakers are present on the device, this OID will return the rating of the breaker in Amps. |
| 1.3.6.1.4.1.318.1.1.26.8.3 | TablerPDU2BankStatusTable | not-accessible | mandatory | A table of Rack PDU bank status data |
| 1.3.6.1.4.1.318.1.1.26.8.3.1 | RowrPDU2BankStatusEntry | not-accessible | mandatory | Status data from currently queried Rack PDU bank |
| 1.3.6.1.4.1.318.1.1.26.8.3.1.1 | ColumnrPDU2BankStatusIndex | read-only | mandatory | The index to the Rack PDU bank status table entry |
| 1.3.6.1.4.1.318.1.1.26.8.3.1.2 | ColumnrPDU2BankStatusModule | read-only | mandatory | The user-defined Rack PDU numeric ID |
| 1.3.6.1.4.1.318.1.1.26.8.3.1.3 | ColumnrPDU2BankStatusNumber | read-only | mandatory | The numeric bank ID |
| 1.3.6.1.4.1.318.1.1.26.8.3.1.4 | ColumnrPDU2BankStatusLoadState | read-only | mandatory | Indicates the present load status of the Rack PDU bank being queried |
| 1.3.6.1.4.1.318.1.1.26.8.3.1.5 | ColumnrPDU2BankStatusCurrent | read-only | mandatory | Indicates the current draw, in tenths of Amps, of the load on the Rack PDU bank being queried |
| 1.3.6.1.4.1.318.1.1.26.8.3.1.6 | ColumnrPDU2BankStatusPeakCurrent | read-only | mandatory | The peak current of the Rack PDU bank load in tenths of Amps |
| 1.3.6.1.4.1.318.1.1.26.8.3.1.7 | ColumnrPDU2BankStatusPeakCurrentTimestamp | read-only | mandatory | Indicates the date and time the bank peak current occurred |
| 1.3.6.1.4.1.318.1.1.26.8.3.1.8 | ColumnrPDU2BankStatusPeakCurrentStartTime | read-only | mandatory | Indicates the date and time of the last bank peak current reset |
| 1.3.6.1.4.1.318.1.1.26.8.3.1.9 | ColumnrPDU2BankStatusVoltage | read-only | mandatory | Indicates the Voltage, in Volts, of the Rack PDU bank being queried. Models that do not support this feature will respond to this OID with a value of -1. |
| 1.3.6.1.4.1.318.1.1.26.8.3.1.10 | ColumnrPDU2BankStatusPower | read-only | mandatory | Indicates the load power, in hundredths of kilowatts (kW), consumed on the RackPDU phase being queried. Models that do not support this feature will respond to… |
| 1.3.6.1.4.1.318.1.1.26.8.3.1.11 | ColumnrPDU2BankStatusEnergy | read-only | mandatory | A user resettable energy meter measuring Rack PDU phase load energy consumption in tenths of kilowatt-hours. Models that do not support this feature will respo… |
| 1.3.6.1.4.1.318.1.1.26.9 | NoderPDU2Outlet | |||
| 1.3.6.1.4.1.318.1.1.26.9.1 | ScalarrPDU2OutletSwitchedTableSize | read-only | mandatory | The number of switched outlets on connected Rack PDUs |
| 1.3.6.1.4.1.318.1.1.26.9.2 | NoderPDU2OutletSwitched | |||
| 1.3.6.1.4.1.318.1.1.26.9.2.1 | TablerPDU2OutletSwitchedConfigTable | not-accessible | mandatory | A table of Rack PDU switched outlet configuration data |
| 1.3.6.1.4.1.318.1.1.26.9.2.1.1 | RowrPDU2OutletSwitchedConfigEntry | not-accessible | mandatory | Configuration data from currently queried Rack PDU switched outlet |
| 1.3.6.1.4.1.318.1.1.26.9.2.1.1.1 | ColumnrPDU2OutletSwitchedConfigIndex | read-only | mandatory | The index to the Rack PDU switched outlet configuration table entry |
| 1.3.6.1.4.1.318.1.1.26.9.2.1.1.2 | ColumnrPDU2OutletSwitchedConfigModule | read-only | mandatory | The user-defined Rack PDU numeric ID |
| 1.3.6.1.4.1.318.1.1.26.9.2.1.1.3 | ColumnrPDU2OutletSwitchedConfigName | read-write | mandatory | The user-defined switched outlet ID string |
| 1.3.6.1.4.1.318.1.1.26.9.2.1.1.4 | ColumnrPDU2OutletSwitchedConfigNumber | read-only | mandatory | The numeric switched outlet ID |
| 1.3.6.1.4.1.318.1.1.26.9.2.1.1.5 | ColumnrPDU2OutletSwitchedConfigPowerOnTime | read-write | mandatory | The amount of delay, in seconds, between when power is provided to the Rack PDU and when this switched outlet starts providing power. Range -1...7200 where -1 … |
| 1.3.6.1.4.1.318.1.1.26.9.2.1.1.6 | ColumnrPDU2OutletSwitchedConfigPowerOffTime | read-write | mandatory | The amount of time, in seconds, this outlet will delay powering off. Range -1...7200 where -1 = Never power off, 0 = immediate power off, and 1-7200 = seconds … |
| 1.3.6.1.4.1.318.1.1.26.9.2.1.1.7 | ColumnrPDU2OutletSwitchedConfigRebootDuration | read-write | mandatory | After turning power off during a reboot sequence, the amount of time to wait before turning power to this outlet back on. Range 5-60 seconds delay. |
| 1.3.6.1.4.1.318.1.1.26.9.2.1.1.8 | ColumnrPDU2OutletSwitchedConfigExternalLink | read-write | mandatory | User-defined external device web link. Possible use cases could be the IP address of the external device plugged into the outlet or its manufacturer web page f… |
| 1.3.6.1.4.1.318.1.1.26.9.2.2 | TablerPDU2OutletSwitchedPropertiesTable | not-accessible | mandatory | A table of Rack PDU switched outlet properties |
| 1.3.6.1.4.1.318.1.1.26.9.2.2.1 | RowrPDU2OutletSwitchedPropertiesEntry | not-accessible | mandatory | Properties of the currently queried Rack PDU switched outlet |
| 1.3.6.1.4.1.318.1.1.26.9.2.2.1.1 | ColumnrPDU2OutletSwitchedPropertiesIndex | read-only | mandatory | The index to the Rack PDU switched outlet properties table entry |
| 1.3.6.1.4.1.318.1.1.26.9.2.2.1.2 | ColumnrPDU2OutletSwitchedPropertiesModule | read-only | mandatory | The user-defined Rack PDU numeric ID |
| 1.3.6.1.4.1.318.1.1.26.9.2.2.1.3 | ColumnrPDU2OutletSwitchedPropertiesName | read-only | mandatory | The user-defined switched outlet ID string |
| 1.3.6.1.4.1.318.1.1.26.9.2.2.1.4 | ColumnrPDU2OutletSwitchedPropertiesNumber | read-only | mandatory | The numeric switched outlet ID |
| 1.3.6.1.4.1.318.1.1.26.9.2.2.1.5 | ColumnrPDU2OutletSwitchedPropertiesPhaseLayout | read-only | mandatory | This OID describes the phase connections of the referenced outlet as follows: seqPhase1ToNeutral(1) indicates that the outlet is wired from Phase 1 to Neutral.… |
| 1.3.6.1.4.1.318.1.1.26.9.2.2.1.6 | ColumnrPDU2OutletSwitchedPropertiesBank | read-only | mandatory | The numeric bank ID |
| 1.3.6.1.4.1.318.1.1.26.9.2.3 | TablerPDU2OutletSwitchedStatusTable | not-accessible | mandatory | A table of Rack PDU switched outlet status information |
| 1.3.6.1.4.1.318.1.1.26.9.2.3.1 | RowrPDU2OutletSwitchedStatusEntry | not-accessible | mandatory | Status information for currently queried Rack PDU switched outlet |
| 1.3.6.1.4.1.318.1.1.26.9.2.3.1.1 | ColumnrPDU2OutletSwitchedStatusIndex | read-only | mandatory | The index to the Rack PDU switched outlet status information table entry |
| 1.3.6.1.4.1.318.1.1.26.9.2.3.1.2 | ColumnrPDU2OutletSwitchedStatusModule | read-only | mandatory | The user-defined Rack PDU numeric ID |
| 1.3.6.1.4.1.318.1.1.26.9.2.3.1.3 | ColumnrPDU2OutletSwitchedStatusName | read-only | mandatory | The user-defined switched outlet ID string |
| 1.3.6.1.4.1.318.1.1.26.9.2.3.1.4 | ColumnrPDU2OutletSwitchedStatusNumber | read-only | mandatory | The numeric switched outlet ID |
| 1.3.6.1.4.1.318.1.1.26.9.2.3.1.5 | ColumnrPDU2OutletSwitchedStatusState | read-only | mandatory | Indicates the present switch state of the Rack PDU switched outlet being queried |
| 1.3.6.1.4.1.318.1.1.26.9.2.3.1.6 | ColumnrPDU2OutletSwitchedStatusCommandPending | read-only | mandatory | Indicates whether or not the device is processing a command for this outlet. If the commandPendingUnknown (3) value is returned, all devices powered by the Rac… |
| 1.3.6.1.4.1.318.1.1.26.9.2.3.1.7 | ColumnrPDU2OutletSwitchedStatusExternalLink | read-only | mandatory | Each RPDU outlet can have its own external web URL link. This can be configured in the rPDU2OutletSwitchedConfigExternalLink OID. When this link is clicked in … |
| 1.3.6.1.4.1.318.1.1.26.9.2.4 | TablerPDU2OutletSwitchedControlTable | not-accessible | mandatory | A table of Rack PDU switched outlet control data |
| 1.3.6.1.4.1.318.1.1.26.9.2.4.1 | RowrPDU2OutletSwitchedControlEntry | not-accessible | mandatory | Control data for currently queried Rack PDU switched outlet |
| 1.3.6.1.4.1.318.1.1.26.9.2.4.1.1 | ColumnrPDU2OutletSwitchedControlIndex | read-only | mandatory | The index to the Rack PDU switched outlet control data table entry |
| 1.3.6.1.4.1.318.1.1.26.9.2.4.1.2 | ColumnrPDU2OutletSwitchedControlModule | read-only | mandatory | The user-defined Rack PDU numeric ID |
| 1.3.6.1.4.1.318.1.1.26.9.2.4.1.3 | ColumnrPDU2OutletSwitchedControlName | read-only | mandatory | The user-defined switched outlet ID string |
| 1.3.6.1.4.1.318.1.1.26.9.2.4.1.4 | ColumnrPDU2OutletSwitchedControlNumber | read-only | mandatory | The numeric switched outlet ID |
| 1.3.6.1.4.1.318.1.1.26.9.2.4.1.5 | ColumnrPDU2OutletSwitchedControlCommand | read-write | mandatory | Getting this variable will return the outlet state. If the outlet is on, the immediateOn (1) value will be returned. If the outlet is off, the immediateOff (2)… |
| 1.3.6.1.4.1.318.1.1.26.9.3 | ScalarrPDU2OutletMeteredTableSize | read-only | mandatory | The number of metered outlets on connect Rack PDUs |
| 1.3.6.1.4.1.318.1.1.26.9.4 | NoderPDU2OutletMetered | |||
| 1.3.6.1.4.1.318.1.1.26.9.4.1 | TablerPDU2OutletMeteredConfigTable | not-accessible | mandatory | A table of Rack PDU metered outlet configuration data |
| 1.3.6.1.4.1.318.1.1.26.9.4.1.1 | RowrPDU2OutletMeteredConfigEntry | not-accessible | mandatory | Configuration data from currently queried Rack PDU metered outlet |
| 1.3.6.1.4.1.318.1.1.26.9.4.1.1.1 | ColumnrPDU2OutletMeteredConfigIndex | read-only | mandatory | The index to the Rack PDU metered outlet configuration table entry |
| 1.3.6.1.4.1.318.1.1.26.9.4.1.1.2 | ColumnrPDU2OutletMeteredConfigModule | read-only | mandatory | The user-defined Rack PDU numeric ID |
| 1.3.6.1.4.1.318.1.1.26.9.4.1.1.3 | ColumnrPDU2OutletMeteredConfigName | read-write | mandatory | The user-defined metered outlet ID string |
| 1.3.6.1.4.1.318.1.1.26.9.4.1.1.4 | ColumnrPDU2OutletMeteredConfigNumber | read-only | mandatory | The numeric switched outlet ID |
| 1.3.6.1.4.1.318.1.1.26.9.4.1.1.5 | ColumnrPDU2OutletMeteredConfigLowLoadCurrentThreshold | read-write | mandatory | User-defined low load outlet current threshold in Watts |
| 1.3.6.1.4.1.318.1.1.26.9.4.1.1.6 | ColumnrPDU2OutletMeteredConfigNearOverloadCurrentThreshold | read-write | mandatory | User-defined near outlet overload warning threshold in Watts |
| 1.3.6.1.4.1.318.1.1.26.9.4.1.1.7 | ColumnrPDU2OutletMeteredConfigOverloadCurrentThreshold | read-write | mandatory | User-defined outlet overload current threshold in Watts |
| 1.3.6.1.4.1.318.1.1.26.9.4.1.1.8 | ColumnrPDU2OutletMeteredConfigExternalLink | read-write | mandatory | User-defined external device web link. Possible use cases could be the IP address of the external device plugged into the outlet or its manufacturer web page f… |
| 1.3.6.1.4.1.318.1.1.26.9.4.2 | TablerPDU2OutletMeteredPropertiesTable | not-accessible | mandatory | A table of Rack PDU metered outlet properties |
| 1.3.6.1.4.1.318.1.1.26.9.4.2.1 | RowrPDU2OutletMeteredPropertiesEntry | not-accessible | mandatory | Properties of currently queried Rack PDU metered outlet |
| 1.3.6.1.4.1.318.1.1.26.9.4.2.1.1 | ColumnrPDU2OutletMeteredPropertiesIndex | read-only | mandatory | The index to the Rack PDU metered properties table entry |
| 1.3.6.1.4.1.318.1.1.26.9.4.2.1.2 | ColumnrPDU2OutletMeteredPropertiesModule | read-only | mandatory | The user-defined Rack PDU numeric ID |
| 1.3.6.1.4.1.318.1.1.26.9.4.2.1.3 | ColumnrPDU2OutletMeteredPropertiesName | read-only | mandatory | The user-defined metered outlet ID string |
| 1.3.6.1.4.1.318.1.1.26.9.4.2.1.4 | ColumnrPDU2OutletMeteredPropertiesNumber | read-only | mandatory | The numeric metered outlet ID |
| 1.3.6.1.4.1.318.1.1.26.9.4.2.1.5 | ColumnrPDU2OutletMeteredPropertiesLayout | read-only | mandatory | This OID describes the phase connections of the referenced outlet as follows: seqPhase1ToNeutral(1) indicates that the outlet is wired from Phase 1 to Neutral.… |
| 1.3.6.1.4.1.318.1.1.26.9.4.2.1.6 | ColumnrPDU2OutletMeteredPropertiesPowerRating | read-only | mandatory | Maximum power rating of Rack PDU metered outlet |
| 1.3.6.1.4.1.318.1.1.26.9.4.2.1.7 | ColumnrPDU2OutletMeteredPropertiesBank | read-only | mandatory | This outlet's numeric bank ID |
| 1.3.6.1.4.1.318.1.1.26.9.4.3 | TablerPDU2OutletMeteredStatusTable | not-accessible | mandatory | A table of Rack PDU metered outlet status data |
| 1.3.6.1.4.1.318.1.1.26.9.4.3.1 | RowrPDU2OutletMeteredStatusEntry | not-accessible | mandatory | Status data from currently queried Rack PDU metered outlet |
| 1.3.6.1.4.1.318.1.1.26.9.4.3.1.1 | ColumnrPDU2OutletMeteredStatusIndex | read-only | mandatory | The index to the Rack PDU metered status table entry |
| 1.3.6.1.4.1.318.1.1.26.9.4.3.1.2 | ColumnrPDU2OutletMeteredStatusModule | read-only | mandatory | The user-defined Rack PDU numeric ID |
| 1.3.6.1.4.1.318.1.1.26.9.4.3.1.3 | ColumnrPDU2OutletMeteredStatusName | read-only | mandatory | The user-defined metered outlet ID string |
| 1.3.6.1.4.1.318.1.1.26.9.4.3.1.4 | ColumnrPDU2OutletMeteredStatusNumber | read-only | mandatory | The numeric metered outlet ID |
| 1.3.6.1.4.1.318.1.1.26.9.4.3.1.5 | ColumnrPDU2OutletMeteredStatusState | read-only | mandatory | Indicates the present load status of the Rack PDU metered outlet being queried |
| 1.3.6.1.4.1.318.1.1.26.9.4.3.1.6 | ColumnrPDU2OutletMeteredStatusCurrent | read-only | mandatory | Indicates the current draw, in tenths of Amps, of the load on the Rack PDU outlet being queried |
| 1.3.6.1.4.1.318.1.1.26.9.4.3.1.7 | ColumnrPDU2OutletMeteredStatusPower | read-only | mandatory | Indicates the power draw of the load on the Rack PDU outlet being queried |
| 1.3.6.1.4.1.318.1.1.26.9.4.3.1.8 | ColumnrPDU2OutletMeteredStatusPeakPower | read-only | mandatory | Indicates the peak power load draw on the Rack PDU outlet being queried |
| 1.3.6.1.4.1.318.1.1.26.9.4.3.1.9 | ColumnrPDU2OutletMeteredStatusPeakPowerTimestamp | read-only | mandatory | Indicates the date and time that this metered outlet's peak power consumption occurred |
| 1.3.6.1.4.1.318.1.1.26.9.4.3.1.10 | ColumnrPDU2OutletMeteredStatusPeakPowerStartTime | read-only | mandatory | Indicates the start date and time that this metered outlet began recording peak power observations |
| 1.3.6.1.4.1.318.1.1.26.9.4.3.1.11 | ColumnrPDU2OutletMeteredStatusEnergy | read-only | mandatory | A user resettable energy meter measuring Rack PDU load energy consumption in tenths of kilowatt-hours |
| 1.3.6.1.4.1.318.1.1.26.9.4.3.1.12 | ColumnrPDU2OutletMeteredStatusReceptacleType | read-only | mandatory | Indicates receptacle type for the outlet. |
| 1.3.6.1.4.1.318.1.1.26.9.4.3.1.13 | ColumnrPDU2OutletMeteredStatusExternalLink | read-only | mandatory | Each RPDU outlet can have its own external web URL link. This can be configured in the rPDU2OutletMeteredConfigExternalLink OID. When this link is clicked in t… |
| 1.3.6.1.4.1.318.1.1.26.9.4.3.1.14 | ColumnrPDU2OutletMeteredStatusPowerFactor | read-only | mandatory | The power factor of the Rack PDU outlet in hundredths. Models that do not support this feature will respond to this OID with a value of -1. |
| 1.3.6.1.4.1.318.1.1.26.10 | NoderPDU2Sensor | |||
| 1.3.6.1.4.1.318.1.1.26.10.1 | ScalarrPDU2SensorTempHumidityTableSize | read-only | mandatory | The number of connected temperature-humidity sensors |
| 1.3.6.1.4.1.318.1.1.26.10.2 | NoderPDU2SensorTempHumidity | |||
| 1.3.6.1.4.1.318.1.1.26.10.2.1 | TablerPDU2SensorTempHumidityConfigTable | not-accessible | mandatory | A table of temperature-humidity sensor configuration data |
| 1.3.6.1.4.1.318.1.1.26.10.2.1.1 | RowrPDU2SensorTempHumidityConfigEntry | not-accessible | mandatory | Configuration data from temperature-humidity sensor being queried |
| 1.3.6.1.4.1.318.1.1.26.10.2.1.1.1 | ColumnrPDU2SensorTempHumidityConfigIndex | read-only | mandatory | The index to the temperature-humidity sensor configuration data table entry |
| 1.3.6.1.4.1.318.1.1.26.10.2.1.1.2 | ColumnrPDU2SensorTempHumidityConfigModule | read-only | mandatory | The user-defined Rack PDU numeric ID |
| 1.3.6.1.4.1.318.1.1.26.10.2.1.1.3 | ColumnrPDU2SensorTempHumidityConfigName | read-write | mandatory | The user-defined temperature-humidity sensor ID string |
| 1.3.6.1.4.1.318.1.1.26.10.2.1.1.4 | ColumnrPDU2SensorTempHumidityConfigNumber | read-only | mandatory | The temperature-humidity sensor numeric ID |
| 1.3.6.1.4.1.318.1.1.26.10.2.1.1.5 | ColumnrPDU2SensorTempHumidityConfigTemperatureAlarmEnable | read-write | mandatory | Setting this OID enables or disables generation of sensor temperature alarm. Getting this OID returns the current value of the temperature alarm enable. |
| 1.3.6.1.4.1.318.1.1.26.10.2.1.1.6 | ColumnrPDU2SensorTempHumidityConfigHumidityAlarmEnable | read-write | mandatory | Setting this OID enables or disables generation of sensor humidity alarm. Getting this OID returns the current value of the humidity alarm enable. |
| 1.3.6.1.4.1.318.1.1.26.10.2.1.1.7 | ColumnrPDU2SensorTempHumidityConfigTempMaxThreshF | read-write | mandatory | Sensor maximum temperature alarm threshold in Fahrenheit. Attempting to set this OID to a value less than or equal to that of rPDU2SensorTempHumidityConfigTemp… |
| 1.3.6.1.4.1.318.1.1.26.10.2.1.1.8 | ColumnrPDU2SensorTempHumidityConfigTempHighThreshF | read-write | mandatory | Sensor high temperature warning alarm threshold in Fahrenheit. Attempting to set this OID to a value greater than or equal to that of rPDU2SensorTempHumidityCo… |
| 1.3.6.1.4.1.318.1.1.26.10.2.1.1.9 | ColumnrPDU2SensorTempHumidityConfigTempHysteresisF | read-write | mandatory | Sensor temperature hysteresis setting in Fahrenheit |
| 1.3.6.1.4.1.318.1.1.26.10.2.1.1.10 | ColumnrPDU2SensorTempHumidityConfigTempMaxThreshC | read-write | mandatory | Sensor maximum temperature alarm threshold in Celsius. Attempting to set this OID to a value less than or equal to that of rPDU2SensorTempHumidityConfigTempHig… |
| 1.3.6.1.4.1.318.1.1.26.10.2.1.1.11 | ColumnrPDU2SensorTempHumidityConfigTempHighThreshC | read-write | mandatory | Sensor high temperature warning alarm threshold in Celsius. Attempting to set this OID to a value greater than or equal to that of rPDU2SensorTempHumidityConfi… |
| 1.3.6.1.4.1.318.1.1.26.10.2.1.1.12 | ColumnrPDU2SensorTempHumidityConfigTempHysteresisC | read-write | mandatory | Sensor temperature hysteresis setting in Celsius |
| 1.3.6.1.4.1.318.1.1.26.10.2.1.1.13 | ColumnrPDU2SensorTempHumidityConfigHumidityLowThresh | read-write | mandatory | Sensor low humidity warning alarm threshold in percent relative humidity. Attempting to set this OID to a value less than or equal to that of rPDU2SensorTempHu… |
| 1.3.6.1.4.1.318.1.1.26.10.2.1.1.14 | ColumnrPDU2SensorTempHumidityConfigHumidityMinThresh | read-write | mandatory | Sensor minimum humidity alarm threshold in percent relative humidity. Attempting to set this OID to a value greater than or equal to that of rPDU2SensorTempHum… |
| 1.3.6.1.4.1.318.1.1.26.10.2.1.1.15 | ColumnrPDU2SensorTempHumidityConfigHumidityHysteresis | read-write | mandatory | Sensor humidity hysteresis setting in percent relative humidity |
| 1.3.6.1.4.1.318.1.1.26.10.2.1.1.16 | ColumnrPDU2SensorTempHumidityConfigTempPeakReset | read-write | mandatory | Setting this OID to reset (2) will cause the existing peak temperature to be replaced by the present temperature reading. Getting this OID will do nothing and … |
| 1.3.6.1.4.1.318.1.1.26.10.2.2 | TablerPDU2SensorTempHumidityStatusTable | not-accessible | mandatory | A table of temperature-humidity sensor status data |
| 1.3.6.1.4.1.318.1.1.26.10.2.2.1 | RowrPDU2SensorTempHumidityStatusEntry | not-accessible | mandatory | Status information from temperature-humidity sensor being queried |
| 1.3.6.1.4.1.318.1.1.26.10.2.2.1.1 | ColumnrPDU2SensorTempHumidityStatusIndex | read-only | mandatory | The index to the temperature-humidity status data table entry |
| 1.3.6.1.4.1.318.1.1.26.10.2.2.1.2 | ColumnrPDU2SensorTempHumidityStatusModule | read-only | mandatory | The user-defined Rack PDU numeric ID |
| 1.3.6.1.4.1.318.1.1.26.10.2.2.1.3 | ColumnrPDU2SensorTempHumidityStatusName | read-only | mandatory | The user-defined temperature-humidity sensor ID string |
| 1.3.6.1.4.1.318.1.1.26.10.2.2.1.4 | ColumnrPDU2SensorTempHumidityStatusNumber | read-only | mandatory | The temperature-humidity sensor numeric ID |
| 1.3.6.1.4.1.318.1.1.26.10.2.2.1.5 | ColumnrPDU2SensorTempHumidityStatusType | read-only | mandatory | The type of the sensor |
| 1.3.6.1.4.1.318.1.1.26.10.2.2.1.6 | ColumnrPDU2SensorTempHumidityStatusCommStatus | read-only | mandatory | The communications status of the sensor |
| 1.3.6.1.4.1.318.1.1.26.10.2.2.1.7 | ColumnrPDU2SensorTempHumidityStatusTempF | read-only | mandatory | Sensor temperature reading in tenths of degrees Fahrenheit |
| 1.3.6.1.4.1.318.1.1.26.10.2.2.1.8 | ColumnrPDU2SensorTempHumidityStatusTempC | read-only | mandatory | Sensor temperature reading in tenths of degrees Celsius |
| 1.3.6.1.4.1.318.1.1.26.10.2.2.1.9 | ColumnrPDU2SensorTempHumidityStatusTempStatus | read-only | mandatory | This OID reports the current state of the temperature probe. A notPresent (1) response indicates that no probe is attached. A belowMin (2) response indicates t… |
| 1.3.6.1.4.1.318.1.1.26.10.2.2.1.10 | ColumnrPDU2SensorTempHumidityStatusRelativeHumidity | read-only | mandatory | Sensor humidity reading in percent relative humidity |
| 1.3.6.1.4.1.318.1.1.26.10.2.2.1.11 | ColumnrPDU2SensorTempHumidityStatusHumidityStatus | read-only | mandatory | This OID reports the current state of the humidity probe. A notPresent (1) response indicates that no probe is attached. A belowMin (2) response indicates that… |
| 1.3.6.1.4.1.318.1.1.26.10.2.2.1.12 | ColumnrPDU2SensorTempHumidityStatusTempPeakF | read-only | mandatory | Sensor peak temperature in tenths of degrees Fahrenheit |
| 1.3.6.1.4.1.318.1.1.26.10.2.2.1.13 | ColumnrPDU2SensorTempHumidityStatusTempPeakC | read-only | mandatory | Sensor peak temperature in tenths of degrees Celsius |
| 1.3.6.1.4.1.318.1.1.26.10.2.2.1.14 | ColumnrPDU2SensorTempHumidityStatusTempPeakTimestamp | read-only | mandatory | Indicates the date and time that the peak temperature occurred |
| 1.3.6.1.4.1.318.1.1.26.10.2.2.1.15 | ColumnrPDU2SensorTempHumidityStatusTempPeakStartTime | read-only | mandatory | Indicates the date and time of the last temperature peak reset |
| 1.3.6.1.4.1.318.1.1.26.10.3 | ScalarrPDU2SensorDiscreteTableSize | read-only | mandatory | The number of connected discrete sensors |
| 1.3.6.1.4.1.318.1.1.26.10.4 | NoderPDU2SensorDiscrete | |||
| 1.3.6.1.4.1.318.1.1.26.10.4.1 | TablerPDU2SensorDiscreteConfigTable | not-accessible | mandatory | A table of discrete sensor configuration data |
| 1.3.6.1.4.1.318.1.1.26.10.4.1.1 | RowrPDU2SensorDiscreteConfigEntry | not-accessible | mandatory | Configuration data from discreste sensor being queried |
| 1.3.6.1.4.1.318.1.1.26.10.4.1.1.1 | ColumnrPDU2SensorDiscreteConfigIndex | read-only | mandatory | The index to the discrete sensor configuration data table entry |
| 1.3.6.1.4.1.318.1.1.26.10.4.1.1.2 | ColumnrPDU2SensorDiscreteConfigModule | read-only | mandatory | The user-defined Rack PDU numeric ID |
| 1.3.6.1.4.1.318.1.1.26.10.4.1.1.3 | ColumnrPDU2SensorDiscreteConfigName | read-write | mandatory | The user-defined discrete sensor ID string |
| 1.3.6.1.4.1.318.1.1.26.10.4.1.1.4 | ColumnrPDU2SensorDiscreteConfigNumber | read-only | mandatory | The discrete sensor numeric ID |
| 1.3.6.1.4.1.318.1.1.26.10.4.1.1.5 | ColumnrPDU2SensorDiscreteConfigNormalState | read-write | mandatory | Indicates the normal state of the discrete input contact |
| 1.3.6.1.4.1.318.1.1.26.10.4.1.1.6 | ColumnrPDU2SensorDiscreteConfigAbnormalSeverity | read-write | mandatory | Indicates the severity of alarm triggered by abnormal discrete input contact state |
| 1.3.6.1.4.1.318.1.1.26.10.4.2 | TablerPDU2SensorDiscreteStatusTable | not-accessible | mandatory | A table of discrete sensor status data |
| 1.3.6.1.4.1.318.1.1.26.10.4.2.1 | RowrPDU2SensorDiscreteStatusEntry | not-accessible | mandatory | Status information from discrete sensor being queried |
| 1.3.6.1.4.1.318.1.1.26.10.4.2.1.1 | ColumnrPDU2SensorDiscreteStatusIndex | read-only | mandatory | The index to the discrete sensor status data table entry |
| 1.3.6.1.4.1.318.1.1.26.10.4.2.1.2 | ColumnrPDU2SensorDiscreteStatusModule | read-only | mandatory | The user-defined Rack PDU numeric ID |
| 1.3.6.1.4.1.318.1.1.26.10.4.2.1.3 | ColumnrPDU2SensorDiscreteStatusName | read-only | mandatory | The user-defined discrete sensor ID string |
| 1.3.6.1.4.1.318.1.1.26.10.4.2.1.4 | ColumnrPDU2SensorDiscreteStatusNumber | read-only | mandatory | The discrete sensor numeric ID |
| 1.3.6.1.4.1.318.1.1.26.10.4.2.1.5 | ColumnrPDU2SensorDiscreteStatusType | read-only | mandatory | The type of discrete sensor currently being queried |
| 1.3.6.1.4.1.318.1.1.26.10.4.2.1.6 | ColumnrPDU2SensorDiscreteStatusCommStatus | read-only | mandatory | The communications status of the sensor |
| 1.3.6.1.4.1.318.1.1.26.10.4.2.1.7 | ColumnrPDU2SensorDiscreteStatusCurrentState | read-only | mandatory | The current open/close state of the discrete sensor |
| 1.3.6.1.4.1.318.1.1.26.10.4.2.1.8 | ColumnrPDU2SensorDiscreteStatusAlarmState | read-only | mandatory | Indicates alarm status of discrete sensor input |
| 1.3.6.1.4.1.318.1.1.26.11 | NoderPDU2Group | |||
| 1.3.6.1.4.1.318.1.1.26.11.1 | ScalarrPDU2GroupNumberOfDevices | read-only | mandatory | Getting this OID will return the number of Rack PDU devices contributing to the Network Port Sharing (NPS) group power and energy values. Queries to guest unit… |
| 1.3.6.1.4.1.318.1.1.26.11.2 | ScalarrPDU2GroupTotalPower | read-only | mandatory | Getting this OID will return the total power consumption of the Rack PDU Network Port Sharing (NPS) group devices in hundredths of kilowatts. Queries to guest … |
| 1.3.6.1.4.1.318.1.1.26.11.3 | ScalarrPDU2GroupTotalEnergy | read-only | mandatory | Getting this OID will return the total energy consumption of the Rack PDU Network Port Sharing (NPS) group devices in tenths of kilowatt-hours. To reset the en… |
| 1.3.6.1.4.1.318.1.1.26.11.4 | ScalarrPDU2GroupEnergyReset | read-write | mandatory | Setting this OID to reset (2) will cause the device energy meter value on each device in the Rack PDU Network Port Sharing (NPS) group to be reset to zero. Eac… |
| 1.3.6.1.4.1.318.1.1.26.12 | ScalarrPDU2PhaseToPhaseStatusTableSize | read-only | mandatory | The number of connected Rack PDU banks |
| 1.3.6.1.4.1.318.1.1.26.13 | NoderPDU2PhaseToPhase | |||
| 1.3.6.1.4.1.318.1.1.26.13.1 | TablerPDU2PhaseToPhaseStatusTable | not-accessible | mandatory | A table of Rack PDU phase to phase status data. This table is only applicable to SKUs that have phase to phase outputs. |
| 1.3.6.1.4.1.318.1.1.26.13.1.1 | RowrPDU2PhaseToPhaseStatusEntry | not-accessible | mandatory | Status data from currently queried Rack PDU phase to phase outputs |
| 1.3.6.1.4.1.318.1.1.26.13.1.1.1 | ColumnrPDU2PhaseToPhaseStatusIndex | read-only | mandatory | The index to the Rack PDU phase to phase status table entry |
| 1.3.6.1.4.1.318.1.1.26.13.1.1.2 | ColumnrPDU2PhaseToPhaseStatusModule | read-only | mandatory | The user-defined Rack PDU numeric ID |
| 1.3.6.1.4.1.318.1.1.26.13.1.1.3 | ColumnrPDU2PhaseToPhaseStatusVoltage1to2 | read-only | mandatory | Indicates the Voltage, in Volts, of the Rack PDU phase 1 to phase 2 output being queried |
| 1.3.6.1.4.1.318.1.1.26.13.1.1.4 | ColumnrPDU2PhaseToPhaseStatusVoltage2to3 | read-only | mandatory | Indicates the Voltage, in Volts, of the Rack PDU phase 2 to phase 3 output being queried |
| 1.3.6.1.4.1.318.1.1.26.13.1.1.5 | ColumnrPDU2PhaseToPhaseStatusVoltage3to1 | read-only | mandatory | Indicates the Voltage, in Volts, of the Rack PDU phase 3 to phase 2 output being queried |
| 1.3.6.1.4.1.318.1.1.26.14 | ScalarrPDU2RCMTableSize | read-only | mandatory | The number of RCM |
| 1.3.6.1.4.1.318.1.1.26.15 | NoderPDU2RCM | |||
| 1.3.6.1.4.1.318.1.1.26.15.1 | TablerPDU2RCMTable | not-accessible | mandatory | A table of Rack PDU RCM. |
| 1.3.6.1.4.1.318.1.1.26.15.1.1 | RowrPDU2RCMEntry | not-accessible | mandatory | RCM data from currently queried Rack PDU |
| 1.3.6.1.4.1.318.1.1.26.15.1.1.1 | ColumnrPDU2RCMIndex | read-only | mandatory | The index to the Rack PDU RCM table entry |
| 1.3.6.1.4.1.318.1.1.26.15.1.1.2 | ColumnrPDU2RCMModule | read-only | mandatory | The user-defined Rack PDU numeric ID |
| 1.3.6.1.4.1.318.1.1.26.15.1.1.3 | ColumnrPDU2RCMCurrent | read-only | mandatory | RCM RMS current. (mA) |
| 1.3.6.1.4.1.318.1.1.26.15.1.1.4 | ColumnrPDU2RCMAlarmStatus | read-write | mandatory | RCM alarm status. Setting the selected variable to 1, will clear the over alarm. |
| 1.3.6.1.4.1.318.1.1.26.15.1.1.5 | ColumnrPDU2RCMSelfCheckCommand | read-write | mandatory | Getting this variable will return the RCM self checking status, 1: featureNotAvailable(-1) 2: success(1) 3: failed(2) 4: pending(3). Setting any of the selecte… |
| 1.3.6.1.4.1.318.1.1.26.15.1.1.6 | ColumnrPDU2RCMWarningThreshold | read-write | mandatory | Over Warning threshold of RCM current. (mA), threshold can be set in the range of 15-300mA, and must be lower or equal than Alarm threshold. |
| 1.3.6.1.4.1.318.1.1.26.15.1.1.7 | ColumnrPDU2RCMAlarmThreshold | read-write | mandatory | Over Alarm threshold of RCM current. (mA), threshold can be set in the range of 15~300 mA, and must be higher or equal than Warning threshold. |
| 1.3.6.1.4.1.318.1.1.26.15.1.1.8 | ColumnrPDU2RCMSelfCheckPeriod | read-write | mandatory | RCM Self-Checking Period. (day) period can be set in the range of 1~365 days, the rcm period on a single pdu is the same, setting one of the selected pdu's rcm… |
| 1.3.6.1.4.1.318.1.2 | Nodesoftware | |||
| 1.3.6.1.4.1.318.1.2.1 | NodepowerNetSubAgent | |||
| 1.3.6.1.4.1.318.1.2.1.1 | NodepowerNetSoftwareSystem | |||
| 1.3.6.1.4.1.318.1.2.1.1.1 | ScalarpowerNetSoftwareSystemDescription | read-only | mandatory | A brief description of the PowerNet sub-agent. |
| 1.3.6.1.4.1.318.1.2.1.1.2 | ScalarpowerNetSoftwareOid | read-only | mandatory | The object identifier of the PowerNet sub-agent. |
| 1.3.6.1.4.1.318.1.2.1.1.3 | ScalarpowerNetSoftwareSystemUpTime | read-only | mandatory | The time that the sub-agent has been running. |
| 1.3.6.1.4.1.318.1.2.1.2 | NodepowerNetSoftwareConfig | |||
| 1.3.6.1.4.1.318.1.2.1.2.1 | ScalarpowerNetSoftwareTableSize | read-only | mandatory | The number of software modules supporting the UPS. |
| 1.3.6.1.4.1.318.1.2.1.2.2 | TablepowerNetSoftwareTable | not-accessible | mandatory | A list of the software monitoring the UPS. |
| 1.3.6.1.4.1.318.1.2.1.2.2.1 | RowpowerNetSoftwareEntry | not-accessible | mandatory | An entry containing information on a software module. |
| 1.3.6.1.4.1.318.1.2.1.2.2.1.1 | ColumnmoduleNumber | read-only | mandatory | The index into the Software Entry Table |
| 1.3.6.1.4.1.318.1.2.1.2.2.1.2 | ColumnmoduleName | read-only | mandatory | The name of the software module. |
| 1.3.6.1.4.1.318.1.2.1.2.2.1.3 | ColumnmoduleVersion | read-only | mandatory | The version of the software module. |
| 1.3.6.1.4.1.318.1.2.1.2.2.1.4 | ColumnmoduleDate | read-only | mandatory | The date of the software module represented as mm-dd-yy. |
| 1.3.6.1.4.1.318.1.2.2 | NodestruxureWareOperations | |||
| 1.3.6.1.4.1.318.1.2.2.1 | NodestruxureWareOperationsStatus | |||
| 1.3.6.1.4.1.318.1.2.2.1.1 | ScalarserverStatus | read-only | mandatory | The status of the StruxureWare Operations server: 1: The status of the application server is unknown. Check Webmin and if the problem persists, contact Technic… |
| 1.3.6.1.4.1.318.1.2.2.1.2 | ScalardatabaseStatus | read-only | mandatory | The status of the StruxureWare Operations database: 1: The status of the database is unknown. Check Webmin and if the problem persists, contact Technical Suppo… |
| 1.3.6.1.4.1.318.1.2.2.1.3 | ScalarloadBalancerStatus | read-only | mandatory | The status of the StruxureWare Operations load balancer: 1: Load Balancer status is unknown. Check Webmin and if the problem persists, contact Technical Suppor… |
| 1.3.6.1.4.1.318.1.2.2.1.4 | ScalaressentialServicesStatus | read-only | mandatory | The status of the StruxureWare Operations essential services: 1: Unknown status. Check Webmin and if the problem persists, contact Technical Support. 2: Essent… |
| 1.3.6.1.4.1.318.1.2.2.1.5 | ScalaretlStatus | read-only | mandatory | The status of the StruxureWare Operations ETL services: 1: Unknown status. Check the network configuration and the server network settings. 2: Normal status, 3… |
| 1.3.6.1.4.1.318.1.2.3 | NodepowerChuteNetworkShutdown | |||
| 1.3.6.1.4.1.318.1.2.3.1 | NodepcnsIdent | |||
| 1.3.6.1.4.1.318.1.2.3.1.1 | Scalarpcnshostname | read-only | mandatory | The hostname of the PCNS instance. |
| 1.3.6.1.4.1.318.1.2.3.1.2 | ScalarpcnsVersion | read-only | mandatory | The version of PCNS installed. x.x.x |
| 1.3.6.1.4.1.318.1.2.3.1.3 | ScalarpcnsOS | read-only | mandatory | The version of OS PCNS is Installed on. |
| 1.3.6.1.4.1.318.1.2.3.1.4 | ScalarpcnsJavaVersion | read-only | mandatory | The version of Java PCNS is running on. |
| 1.3.6.1.4.1.318.1.2.3.2 | NodepcnsNetworking | |||
| 1.3.6.1.4.1.318.1.2.3.2.1 | ScalarpcnsUIProtocol | read-only | mandatory | Web Protocol used to connect to the PCNS UI. |
| 1.3.6.1.4.1.318.1.2.3.2.2 | ScalarpcnsHttpPort | read-only | mandatory | Port used for PCNS http UI. |
| 1.3.6.1.4.1.318.1.2.3.2.3 | ScalarpcnsHttpsPort | read-only | mandatory | Port used for PCNS https UI. |
| 1.3.6.1.4.1.318.1.2.3.2.4 | ScalarpcnsNetworkConfig | read-only | mandatory | Configuration of the TCP Network. |
| 1.3.6.1.4.1.318.1.2.3.2.5 | ScalarpcnsVirtualInstall | read-only | mandatory | Virtualization technology in use by PCNS. |
| 1.3.6.1.4.1.318.1.2.3.3 | NodepcnsNMC | |||
| 1.3.6.1.4.1.318.1.2.3.3.1 | ScalarpcnsMode | read-only | mandatory | Configuration mode of the UPS(s) which PCNS is monitoring. |
| 1.3.6.1.4.1.318.1.2.3.3.2 | ScalarpcnsNMCPort | read-only | mandatory | Port used to connect to all of the Network Management Card(s). |
| 1.3.6.1.4.1.318.1.2.3.3.3 | ScalarpcnsNMCProtocol | read-only | mandatory | Web Protocol used to connect to all of the Network Management Card(s). |
| 1.3.6.1.4.1.318.1.2.3.3.4 | TablepcnsNmcTable | not-accessible | mandatory | The Network Management Cards in the UPS's which PCNS is monitoring to provide safe shutdown. |
| 1.3.6.1.4.1.318.1.2.3.3.4.1 | RowpcnsNmcEntry | not-accessible | mandatory | Details of the NMC. |
| 1.3.6.1.4.1.318.1.2.3.3.4.1.1 | ColumnpcnsNmcIndex | read-only | mandatory | Index of the NMC within PCNS setup. |
| 1.3.6.1.4.1.318.1.2.3.3.4.1.2 | ColumnpcnsNmcAddr | read-only | mandatory | The IP address of the NMC. |
| 1.3.6.1.4.1.318.1.2.3.3.4.1.3 | ColumnpcnsNmcOutlet | read-only | mandatory | The Outlet Group which PCNS is enrolled with on the NMC. |
| 1.3.6.1.4.1.318.1.2.3.4 | NodepcnsEvents | |||
| 1.3.6.1.4.1.318.1.2.3.4.1 | NodepcnsPowerFailed | |||
| 1.3.6.1.4.1.318.1.2.3.4.1.1 | ScalarpcnsPowerFailedDesc | read-only | mandatory | The Description of the event. |
| 1.3.6.1.4.1.318.1.2.3.4.1.2 | ScalarpcnsPowerFailedEnableLogging | read-write | mandatory | Log occurrences of this event in PCNS log. |
| 1.3.6.1.4.1.318.1.2.3.4.1.3 | ScalarpcnsPowerFailedEnableCommandFile | read-write | mandatory | Execute a command file when this event occurs. |
| 1.3.6.1.4.1.318.1.2.3.4.1.4 | ScalarpcnsPowerFailedCommandFilePath | read-write | mandatory | Path of command file to execute when this event occurs. |
| 1.3.6.1.4.1.318.1.2.3.4.1.5 | ScalarpcnsPowerFailedCommandFileDelay | read-write | mandatory | How long to wait after event occurs before executing command file (seconds). |
| 1.3.6.1.4.1.318.1.2.3.4.1.6 | ScalarpcnsPowerFailedEnableShutdown | read-write | mandatory | Perform a graceful shutdown of the server when this event occurs. |
| 1.3.6.1.4.1.318.1.2.3.4.1.7 | ScalarpcnsPowerFailedShutdownDelay | read-write | mandatory | How long to wait after event occurs before performing a graceful shutdown of the server (seconds). |
| 1.3.6.1.4.1.318.1.2.3.4.2 | NodepcnsPowerRestored | |||
| 1.3.6.1.4.1.318.1.2.3.4.2.1 | ScalarpcnsPowerRestoredDesc | read-only | mandatory | The Description of the event. |
| 1.3.6.1.4.1.318.1.2.3.4.2.2 | ScalarpcnsPowerRestoredEnableLogging | read-write | mandatory | Log occurrences of this event in PCNS log. |
| 1.3.6.1.4.1.318.1.2.3.4.2.3 | ScalarpcnsPowerRestoredEnableCommandFile | read-write | mandatory | Execute a command file when this event occurs. |
| 1.3.6.1.4.1.318.1.2.3.4.2.4 | ScalarpcnsPowerRestoredCommandFilePath | read-write | mandatory | Path of command file to execute when this event occurs. |
| 1.3.6.1.4.1.318.1.2.3.4.2.5 | ScalarpcnsPowerRestoredCommandFileDelay | read-write | mandatory | How long to wait after event occurs before executing command file (seconds). |
| 1.3.6.1.4.1.318.1.2.3.4.3 | NodepcnsOverload | |||
| 1.3.6.1.4.1.318.1.2.3.4.3.1 | ScalarpcnsOverloadDesc | read-only | mandatory | The Description of the event. |
| 1.3.6.1.4.1.318.1.2.3.4.3.2 | ScalarpcnsOverloadEnableLogging | read-write | mandatory | Log occurrences of this event in PCNS log. |
| 1.3.6.1.4.1.318.1.2.3.4.3.3 | ScalarpcnsOverloadEnableCommandFile | read-write | mandatory | Execute a command file when this event occurs. |
| 1.3.6.1.4.1.318.1.2.3.4.3.4 | ScalarpcnsOverloadCommandFilePath | read-write | mandatory | Path of command file to execute when this event occurs. |
| 1.3.6.1.4.1.318.1.2.3.4.3.5 | ScalarpcnsOverloadCommandFileDelay | read-write | mandatory | How long to wait after event occurs before executing command file (seconds). |
| 1.3.6.1.4.1.318.1.2.3.4.3.6 | ScalarpcnsOverloadEnableShutdown | read-write | mandatory | Perform a graceful shutdown of the server when this event occurs. |
| 1.3.6.1.4.1.318.1.2.3.4.3.7 | ScalarpcnsOverloadShutdownDelay | read-write | mandatory | How long to wait after event occurs before performing a graceful shutdown of the server (seconds). |
| 1.3.6.1.4.1.318.1.2.3.4.4 | NodepcnsOverloadSolved | |||
| 1.3.6.1.4.1.318.1.2.3.4.4.1 | ScalarpcnsOverloadSolvedDesc | read-only | mandatory | The Description of the event. |
| 1.3.6.1.4.1.318.1.2.3.4.4.2 | ScalarpcnsOverloadSolvedEnableLogging | read-write | mandatory | Log occurrences of this event in PCNS log. |
| 1.3.6.1.4.1.318.1.2.3.4.4.3 | ScalarpcnsOverloadSolvedEnableCommandFile | read-write | mandatory | Execute a command file when this event occurs. |
| 1.3.6.1.4.1.318.1.2.3.4.4.4 | ScalarpcnsOverloadSolvedCommandFilePath | read-write | mandatory | Path of command file to execute when this event occurs. |
| 1.3.6.1.4.1.318.1.2.3.4.4.5 | ScalarpcnsOverloadSolvedCommandFileDelay | read-write | mandatory | How long to wait after event occurs before executing command file (seconds). |
| 1.3.6.1.4.1.318.1.2.3.4.5 | NodepcnsRunTimeExceeded | |||
| 1.3.6.1.4.1.318.1.2.3.4.5.1 | ScalarpcnsRunTimeExceededDesc | read-only | mandatory | The Description of the event. |
| 1.3.6.1.4.1.318.1.2.3.4.5.2 | ScalarpcnsRunTimeExceededEnableLogging | read-write | mandatory | Log occurrences of this event in PCNS log. |
| 1.3.6.1.4.1.318.1.2.3.4.5.3 | ScalarpcnsRunTimeExceededEnableCommandFile | read-write | mandatory | Execute a command file when this event occurs. |
| 1.3.6.1.4.1.318.1.2.3.4.5.4 | ScalarpcnsRunTimeExceededCommandFilePath | read-write | mandatory | Path of command file to execute when this event occurs. |
| 1.3.6.1.4.1.318.1.2.3.4.5.5 | ScalarpcnsRunTimeExceededCommandFileDelay | read-write | mandatory | How long to wait after event occurs before executing command file (seconds). |
| 1.3.6.1.4.1.318.1.2.3.4.5.6 | ScalarpcnsRunTimeExceededEnableShutdown | read-write | mandatory | Perform a graceful shutdown of the server when this event occurs. |
| 1.3.6.1.4.1.318.1.2.3.4.5.7 | ScalarpcnsRunTimeExceededShutdownDelay | read-write | mandatory | How long to wait after event occurs before performing a graceful shutdown of the server (seconds). |
| 1.3.6.1.4.1.318.1.2.3.4.6 | NodepcnsRunTimeWithinRange | |||
| 1.3.6.1.4.1.318.1.2.3.4.6.1 | ScalarpcnsRunTimeWithinRangeDesc | read-only | mandatory | The Description of the event. |
| 1.3.6.1.4.1.318.1.2.3.4.6.2 | ScalarpcnsRunTimeWithinRangeEnableLogging | read-write | mandatory | Log occurrences of this event in PCNS log. |
| 1.3.6.1.4.1.318.1.2.3.4.6.3 | ScalarpcnsRunTimeWithinRangeEnableCommandFile | read-write | mandatory | Execute a command file when this event occurs. |
| 1.3.6.1.4.1.318.1.2.3.4.6.4 | ScalarpcnsRunTimeWithinRangeCommandFilePath | read-write | mandatory | Path of command file to execute when this event occurs. |
| 1.3.6.1.4.1.318.1.2.3.4.6.5 | ScalarpcnsRunTimeWithinRangeCommandFileDelay | read-write | mandatory | How long to wait after event occurs before executing command file (seconds). |
| 1.3.6.1.4.1.318.1.2.3.4.7 | NodepcnsRunTimeBelowThreshold | |||
| 1.3.6.1.4.1.318.1.2.3.4.7.1 | ScalarpcnsRunTimeBelowThresholdDesc | read-only | mandatory | The Description of the event. |
| 1.3.6.1.4.1.318.1.2.3.4.7.2 | ScalarpcnspcnsRunTimeBelowThresholdEnableLogging | read-write | mandatory | Log occurrences of this event in PCNS log. |
| 1.3.6.1.4.1.318.1.2.3.4.7.3 | ScalarpcnsRunTimeBelowThresholdEnableCommandFile | read-write | mandatory | Execute a command file when this event occurs. |
| 1.3.6.1.4.1.318.1.2.3.4.7.4 | ScalarpcnsRunTimeBelowThresholdCommandFilePath | read-write | mandatory | Path of command file to execute when this event occurs. |
| 1.3.6.1.4.1.318.1.2.3.4.7.6 | ScalarpcnsRunTimeBelowThresholdEnableShutdown | read-write | mandatory | Perform a graceful shutdown of the server when this event occurs. |
| 1.3.6.1.4.1.318.1.2.3.4.7.8 | ScalarpcnsRunTimeBelowThresholdCommandFileThreshold | read-write | mandatory | If the Runtime Remaining falls below this (seconds), the command file will run. |
| 1.3.6.1.4.1.318.1.2.3.4.7.9 | ScalarpcnsRunTimeBelowThresholdShutdownThreshold | read-write | mandatory | If the Runtime Remaining falls below this (seconds), the shutdown will begin. |
| 1.3.6.1.4.1.318.1.2.3.4.8 | NodepcnsRunTimeAboveThreshold | |||
| 1.3.6.1.4.1.318.1.2.3.4.8.1 | ScalarpcnsRunTimeAboveThresholdDesc | read-only | mandatory | The Description of the event. |
| 1.3.6.1.4.1.318.1.2.3.4.8.2 | ScalarpcnsRunTimeAboveThresholdEnableLogging | read-write | mandatory | Log occurrences of this event in PCNS log. |
| 1.3.6.1.4.1.318.1.2.3.4.8.3 | ScalarpcnsRunTimeAboveThresholdEnableCommandFile | read-write | mandatory | Execute a command file when this event occurs. |
| 1.3.6.1.4.1.318.1.2.3.4.8.4 | ScalarpcnsRunTimeAboveThresholdCommandFilePath | read-write | mandatory | Path of command file to execute when this event occurs. |
| 1.3.6.1.4.1.318.1.2.3.4.8.5 | ScalarpcnsRunTimeAboveThresholdCommandFileDelay | read-write | mandatory | How long to wait after event occurs before executing command file (seconds). |
| 1.3.6.1.4.1.318.1.2.3.4.10 | NodepcnsBatteryDischarged | |||
| 1.3.6.1.4.1.318.1.2.3.4.10.1 | ScalarpcnsBatteryDischargedDesc | read-only | mandatory | The Description of the event. |
| 1.3.6.1.4.1.318.1.2.3.4.10.2 | ScalarpcnsBatteryDischargedEnableLogging | read-write | mandatory | Log occurrences of this event in PCNS log. |
| 1.3.6.1.4.1.318.1.2.3.4.10.3 | ScalarpcnsBatteryDischargedEnableCommandFile | read-write | mandatory | Execute a command file when this event occurs. |
| 1.3.6.1.4.1.318.1.2.3.4.10.4 | ScalarpcnsBatteryDischargedCommandFilePath | read-write | mandatory | Path of command file to execute when this event occurs. |
| 1.3.6.1.4.1.318.1.2.3.4.10.5 | ScalarpcnsBatteryDischargedCommandFileDelay | read-write | mandatory | How long to wait after event occurs before executing command file (seconds). |
| 1.3.6.1.4.1.318.1.2.3.4.10.6 | ScalarpcnsBatteryDischargedEnableShutdown | read-write | mandatory | Perform a graceful shutdown of the server when this event occurs. |
| 1.3.6.1.4.1.318.1.2.3.4.10.7 | ScalarpcnsBatteryDischargedShutdownDelay | read-write | mandatory | How long to wait after event occurs before performing a graceful shutdown of the server (seconds). |
| 1.3.6.1.4.1.318.1.2.3.4.11 | NodepcnsBatteryChargeInRange | |||
| 1.3.6.1.4.1.318.1.2.3.4.11.1 | ScalarpcnsBatteryChargeInRangeDesc | read-only | mandatory | The Description of the event. |
| 1.3.6.1.4.1.318.1.2.3.4.11.2 | ScalarpcnsBatteryChargeInRangeEnableLogging | read-write | mandatory | Log occurrences of this event in PCNS log. |
| 1.3.6.1.4.1.318.1.2.3.4.11.3 | ScalarpcnsBatteryChargeInRangeEnableCommandFile | read-write | mandatory | Execute a command file when this event occurs. |
| 1.3.6.1.4.1.318.1.2.3.4.11.4 | ScalarpcnsBatteryChargeInRangeCommandFilePath | read-write | mandatory | Path of command file to execute when this event occurs. |
| 1.3.6.1.4.1.318.1.2.3.4.11.5 | ScalarpcnsBatteryChargeInRangeCommandFileDelay | read-write | mandatory | How long to wait after event occurs before executing command file (seconds). |
| 1.3.6.1.4.1.318.1.2.3.4.12 | NodepcnsFaultBypassEnabled | |||
| 1.3.6.1.4.1.318.1.2.3.4.12.1 | ScalarpcnsFaultBypassEnabledDesc | read-only | mandatory | The Description of the event. |
| 1.3.6.1.4.1.318.1.2.3.4.12.2 | ScalarpcnsFaultBypassEnabledEnableLogging | read-write | mandatory | Log occurrences of this event in PCNS log. |
| 1.3.6.1.4.1.318.1.2.3.4.12.3 | ScalarpcnsFaultBypassEnabledEnableCommandFile | read-write | mandatory | Execute a command file when this event occurs. |
| 1.3.6.1.4.1.318.1.2.3.4.12.4 | ScalarpcnsFaultBypassEnabledCommandFilePath | read-write | mandatory | Path of command file to execute when this event occurs. |
| 1.3.6.1.4.1.318.1.2.3.4.12.5 | ScalarpcnsFaultBypassEnabledCommandFileDelay | read-write | mandatory | How long to wait after event occurs before executing command file (seconds). |
| 1.3.6.1.4.1.318.1.2.3.4.12.6 | ScalarpcnsFaultBypassEnabledEnableShutdown | read-write | mandatory | Perform a graceful shutdown of the server when this event occurs. |
| 1.3.6.1.4.1.318.1.2.3.4.12.7 | ScalarpcnsFaultBypassEnabledShutdownDelay | read-write | mandatory | How long to wait after event occurs before performing a graceful shutdown of the server (seconds). |
| 1.3.6.1.4.1.318.1.2.3.4.13 | NodepcnsBypassEnabled | |||
| 1.3.6.1.4.1.318.1.2.3.4.13.1 | ScalarpcnsBypassEnabledDesc | read-only | mandatory | The Description of the event. |
| 1.3.6.1.4.1.318.1.2.3.4.13.2 | ScalarpcnsBypassEnabledEnableLogging | read-write | mandatory | Log occurrences of this event in PCNS log. |
| 1.3.6.1.4.1.318.1.2.3.4.13.3 | ScalarpcnsBypassEnabledEnableCommandFile | read-write | mandatory | Execute a command file when this event occurs. |
| 1.3.6.1.4.1.318.1.2.3.4.13.4 | ScalarpcnsBypassEnabledCommandFilePath | read-write | mandatory | Path of command file to execute when this event occurs. |
| 1.3.6.1.4.1.318.1.2.3.4.13.5 | ScalarpcnsBypassEnabledCommandFileDelay | read-write | mandatory | How long to wait after event occurs before executing command file (seconds). |
| 1.3.6.1.4.1.318.1.2.3.4.13.6 | ScalarpcnsBypassEnabledEnableShutdown | read-write | mandatory | Perform a graceful shutdown of the server when this event occurs. |
| 1.3.6.1.4.1.318.1.2.3.4.13.7 | ScalarpcnsBypassEnabledShutdownDelay | read-write | mandatory | How long to wait after event occurs before performing a graceful shutdown of the server (seconds). |
| 1.3.6.1.4.1.318.1.2.3.4.14 | NodepcnsBypassManualEnabled | |||
| 1.3.6.1.4.1.318.1.2.3.4.14.1 | ScalarpcnsBypassManualEnabledDesc | read-only | mandatory | The Description of the event. |
| 1.3.6.1.4.1.318.1.2.3.4.14.2 | ScalarpcnsBypassManualEnabledEnableLogging | read-write | mandatory | Log occurrences of this event in PCNS log. |
| 1.3.6.1.4.1.318.1.2.3.4.14.3 | ScalarpcnsBypassManualEnabledEnableCommandFile | read-write | mandatory | Execute a command file when this event occurs. |
| 1.3.6.1.4.1.318.1.2.3.4.14.4 | ScalarpcnsBypassManualEnabledCommandFilePath | read-write | mandatory | Path of command file to execute when this event occurs. |
| 1.3.6.1.4.1.318.1.2.3.4.14.5 | ScalarpcnsBypassManualEnabledCommandFileDelay | read-write | mandatory | How long to wait after event occurs before executing command file (seconds). |
| 1.3.6.1.4.1.318.1.2.3.4.14.6 | ScalarpcnsBypassManualEnabledEnableShutdown | read-write | mandatory | Perform a graceful shutdown of the server when this event occurs. |
| 1.3.6.1.4.1.318.1.2.3.4.14.7 | ScalarpcnsBypassManualEnabledShutdownDelay | read-write | mandatory | How long to wait after event occurs before performing a graceful shutdown of the server (seconds). |
| 1.3.6.1.4.1.318.1.2.3.4.15 | NodepcnsBypassDisabled | |||
| 1.3.6.1.4.1.318.1.2.3.4.15.1 | ScalarpcnsBypassDisabledDesc | read-only | mandatory | The Description of the event. |
| 1.3.6.1.4.1.318.1.2.3.4.15.2 | ScalarpcnsBypassDisabledEnableLogging | read-write | mandatory | Log occurrences of this event in PCNS log. |
| 1.3.6.1.4.1.318.1.2.3.4.15.3 | ScalarpcnsBypassDisabledEnableCommandFile | read-write | mandatory | Execute a command file when this event occurs. |
| 1.3.6.1.4.1.318.1.2.3.4.15.4 | ScalarpcnsBypassDisabledCommandFilePath | read-write | mandatory | Path of command file to execute when this event occurs. |
| 1.3.6.1.4.1.318.1.2.3.4.15.5 | ScalarpcnsBypassDisabledCommandFileDelay | read-write | mandatory | How long to wait after event occurs before executing command file (seconds). |
| 1.3.6.1.4.1.318.1.2.3.4.16 | NodepcnsBypassContactorFailed | |||
| 1.3.6.1.4.1.318.1.2.3.4.16.1 | ScalarpcnsBypassContactorFailedDesc | read-only | mandatory | The Description of the event. |
| 1.3.6.1.4.1.318.1.2.3.4.16.2 | ScalarpcnsBypassContactorFailedEnableLogging | read-write | mandatory | Log occurrences of this event in PCNS log. |
| 1.3.6.1.4.1.318.1.2.3.4.16.3 | ScalarpcnsBypassContactorFailedEnableCommandFile | read-write | mandatory | Execute a command file when this event occurs. |
| 1.3.6.1.4.1.318.1.2.3.4.16.4 | ScalarpcnsBypassContactorFailedCommandFilePath | read-write | mandatory | Path of command file to execute when this event occurs. |
| 1.3.6.1.4.1.318.1.2.3.4.16.5 | ScalarpcnsBypassContactorFailedCommandFileDelay | read-write | mandatory | How long to wait after event occurs before executing command file (seconds). |
| 1.3.6.1.4.1.318.1.2.3.4.16.6 | ScalarpcnsBypassContactorFailedEnableShutdown | read-write | mandatory | Perform a graceful shutdown of the server when this event occurs. |
| 1.3.6.1.4.1.318.1.2.3.4.16.7 | ScalarpcnsBypassContactorFailedShutdownDelay | read-write | mandatory | How long to wait after event occurs before performing a graceful shutdown of the server (seconds). |
| 1.3.6.1.4.1.318.1.2.3.4.17 | NodepcnsBypassContactorOk | |||
| 1.3.6.1.4.1.318.1.2.3.4.17.1 | ScalarpcnsBypassContactorOkDesc | read-only | mandatory | The Description of the event. |
| 1.3.6.1.4.1.318.1.2.3.4.17.2 | ScalarpcnsBypassContactorOkEnableLogging | read-write | mandatory | Log occurrences of this event in PCNS log. |
| 1.3.6.1.4.1.318.1.2.3.4.17.3 | ScalarpcnsBypassContactorOkEnableCommandFile | read-write | mandatory | Execute a command file when this event occurs. |
| 1.3.6.1.4.1.318.1.2.3.4.17.4 | ScalarpcnsBypassContactorOkCommandFilePath | read-write | mandatory | Path of command file to execute when this event occurs. |
| 1.3.6.1.4.1.318.1.2.3.4.17.5 | ScalarpcnsBypassContactorOkCommandFileDelay | read-write | mandatory | How long to wait after event occurs before executing command file (seconds). |
| 1.3.6.1.4.1.318.1.2.3.4.18 | NodepcnsCommunicationLostOnBattery | |||
| 1.3.6.1.4.1.318.1.2.3.4.18.1 | ScalarpcnsCommunicationLostOnBatteryDesc | read-only | mandatory | The Description of the event. |
| 1.3.6.1.4.1.318.1.2.3.4.18.2 | ScalarpcnsCommunicationLostOnBatteryEnableLogging | read-write | mandatory | Log occurrences of this event in PCNS log. |
| 1.3.6.1.4.1.318.1.2.3.4.18.3 | ScalarpcnsCommunicationLostOnBatteryEnableCommandFile | read-write | mandatory | Execute a command file when this event occurs. |
| 1.3.6.1.4.1.318.1.2.3.4.18.4 | ScalarpcnsCommunicationLostOnBatteryCommandFilePath | read-write | mandatory | Path of command file to execute when this event occurs. |
| 1.3.6.1.4.1.318.1.2.3.4.18.5 | ScalarpcnsCommunicationLostOnBatteryCommandFileDelay | read-write | mandatory | How long to wait after event occurs before executing command file (seconds). |
| 1.3.6.1.4.1.318.1.2.3.4.18.6 | ScalarpcnsCommunicationLostOnBatteryEnableShutdown | read-write | mandatory | Perform a graceful shutdown of the server when this event occurs. |
| 1.3.6.1.4.1.318.1.2.3.4.18.7 | ScalarpcnsCommunicationLostOnBatteryShutdownDelay | read-write | mandatory | How long to wait after event occurs before performing a graceful shutdown of the server (seconds). |
| 1.3.6.1.4.1.318.1.2.3.4.19 | NodepcnsCommunicationLost | |||
| 1.3.6.1.4.1.318.1.2.3.4.19.1 | ScalarpcnsCommunicationLostDesc | read-only | mandatory | The Description of the event. |
| 1.3.6.1.4.1.318.1.2.3.4.19.2 | ScalarpcnsCommunicationLostEnableLogging | read-write | mandatory | Log occurrences of this event in PCNS log. |
| 1.3.6.1.4.1.318.1.2.3.4.19.3 | ScalarpcnsCommunicationLostEnableCommandFile | read-write | mandatory | Execute a command file when this event occurs. |
| 1.3.6.1.4.1.318.1.2.3.4.19.4 | ScalarpcnsCommunicationLostCommandFilePath | read-write | mandatory | Path of command file to execute when this event occurs. |
| 1.3.6.1.4.1.318.1.2.3.4.19.5 | ScalarpcnsCommunicationLostCommandFileDelay | read-write | mandatory | How long to wait after event occurs before executing command file (seconds). |
| 1.3.6.1.4.1.318.1.2.3.4.19.6 | ScalarpcnsCommunicationLostEnableShutdown | read-write | mandatory | Perform a graceful shutdown of the server when this event occurs. |
| 1.3.6.1.4.1.318.1.2.3.4.19.7 | ScalarpcnsCommunicationLostShutdownDelay | read-write | mandatory | How long to wait after event occurs before performing a graceful shutdown of the server (seconds). |
| 1.3.6.1.4.1.318.1.2.3.4.20 | NodepcnsNetCommunicationLost | |||
| 1.3.6.1.4.1.318.1.2.3.4.20.1 | ScalarpcnsNetCommunicationLostDesc | read-only | mandatory | The Description of the event. |
| 1.3.6.1.4.1.318.1.2.3.4.20.2 | ScalarpcnsNetCommunicationLostEnableLogging | read-write | mandatory | Log occurrences of this event in PCNS log. |
| 1.3.6.1.4.1.318.1.2.3.4.20.3 | ScalarpcnsNetCommunicationLostEnableCommandFile | read-write | mandatory | Execute a command file when this event occurs. |
| 1.3.6.1.4.1.318.1.2.3.4.20.4 | ScalarpcnsNetCommunicationLostCommandFilePath | read-write | mandatory | Path of command file to execute when this event occurs. |
| 1.3.6.1.4.1.318.1.2.3.4.20.5 | ScalarpcnsNetCommunicationLostCommandFileDelay | read-write | mandatory | How long to wait after event occurs before executing command file (seconds). |
| 1.3.6.1.4.1.318.1.2.3.4.20.6 | ScalarpcnsNetCommunicationLostEnableShutdown | read-write | mandatory | Perform a graceful shutdown of the server when this event occurs. |
| 1.3.6.1.4.1.318.1.2.3.4.20.7 | ScalarpcnsNetCommunicationLostShutdownDelay | read-write | mandatory | How long to wait after event occurs before performing a graceful shutdown of the server (seconds). |
| 1.3.6.1.4.1.318.1.2.3.4.21 | NodepcnsCommunicationEstablished | |||
| 1.3.6.1.4.1.318.1.2.3.4.21.1 | ScalarpcnsCommunicationEstablishedDesc | read-only | mandatory | The Description of the event. |
| 1.3.6.1.4.1.318.1.2.3.4.21.2 | ScalarpcnsCommunicationEstablishedEnableLogging | read-write | mandatory | Log occurrences of this event in PCNS log. |
| 1.3.6.1.4.1.318.1.2.3.4.21.3 | ScalarpcnsCommunicationEstablishedEnableCommandFile | read-write | mandatory | Execute a command file when this event occurs. |
| 1.3.6.1.4.1.318.1.2.3.4.21.4 | ScalarpcnsCommunicationEstablishedCommandFilePath | read-write | mandatory | Path of command file to execute when this event occurs. |
| 1.3.6.1.4.1.318.1.2.3.4.21.5 | ScalarpcnsCommunicationEstablishedCommandFileDelay | read-write | mandatory | How long to wait after event occurs before executing command file (seconds). |
| 1.3.6.1.4.1.318.1.2.3.4.22 | NodepcnsMinRedundancyLost | |||
| 1.3.6.1.4.1.318.1.2.3.4.22.1 | ScalarpcnsMinRedundancyLostDesc | read-only | mandatory | The Description of the event. |
| 1.3.6.1.4.1.318.1.2.3.4.22.2 | ScalarpcnsMinRedundancyLostEnableLogging | read-write | mandatory | Log occurrences of this event in PCNS log. |
| 1.3.6.1.4.1.318.1.2.3.4.22.3 | ScalarpcnsMinRedundancyLostEnableCommandFile | read-write | mandatory | Execute a command file when this event occurs. |
| 1.3.6.1.4.1.318.1.2.3.4.22.4 | ScalarpcnsMinRedundancyLostCommandFilePath | read-write | mandatory | Path of command file to execute when this event occurs. |
| 1.3.6.1.4.1.318.1.2.3.4.22.5 | ScalarpcnsMinRedundancyLostCommandFileDelay | read-write | mandatory | How long to wait after event occurs before executing command file (seconds). |
| 1.3.6.1.4.1.318.1.2.3.4.22.6 | ScalarpcnsMinRedundancyLostEnableShutdown | read-write | mandatory | Perform a graceful shutdown of the server when this event occurs. |
| 1.3.6.1.4.1.318.1.2.3.4.22.7 | ScalarpcnsMinRedundancyLostShutdownDelay | read-write | mandatory | How long to wait after event occurs before performing a graceful shutdown of the server (seconds). |
| 1.3.6.1.4.1.318.1.2.3.4.23 | NodepcnsMinRedundancyRegained | |||
| 1.3.6.1.4.1.318.1.2.3.4.23.1 | ScalarpcnsMinRedundancyRegainedDesc | read-only | mandatory | The Description of the event. |
| 1.3.6.1.4.1.318.1.2.3.4.23.2 | ScalarpcnsMinRedundancyRegainedEnableLogging | read-write | mandatory | Log occurrences of this event in PCNS log. |
| 1.3.6.1.4.1.318.1.2.3.4.23.3 | ScalarpcnsMinRedundancyRegainedEnableCommandFile | read-write | mandatory | Execute a command file when this event occurs. |
| 1.3.6.1.4.1.318.1.2.3.4.23.4 | ScalarpcnsMinRedundancyRegainedCommandFilePath | read-write | mandatory | Path of command file to execute when this event occurs. |
| 1.3.6.1.4.1.318.1.2.3.4.23.5 | ScalarpcnsMinRedundancyRegainedCommandFileDelay | read-write | mandatory | How long to wait after event occurs before executing command file (seconds). |
| 1.3.6.1.4.1.318.1.2.3.4.24 | NodepcnsParallelRedundancyLost | |||
| 1.3.6.1.4.1.318.1.2.3.4.24.1 | ScalarpcnsParallelRedundancyLostDesc | read-only | mandatory | The Description of the event. |
| 1.3.6.1.4.1.318.1.2.3.4.24.2 | ScalarpcnsParallelRedundancyLostEnableLogging | read-write | mandatory | Log occurrences of this event in PCNS log. |
| 1.3.6.1.4.1.318.1.2.3.4.24.3 | ScalarpcnsParallelRedundancyLostEnableCommandFile | read-write | mandatory | Execute a command file when this event occurs. |
| 1.3.6.1.4.1.318.1.2.3.4.24.4 | ScalarpcnsParallelRedundancyLostCommandFilePath | read-write | mandatory | Path of command file to execute when this event occurs. |
| 1.3.6.1.4.1.318.1.2.3.4.24.5 | ScalarpcnsParallelRedundancyLostCommandFileDelay | read-write | mandatory | How long to wait after event occurs before executing command file (seconds). |
| 1.3.6.1.4.1.318.1.2.3.4.24.6 | ScalarpcnsParallelRedundancyLostEnableShutdown | read-write | mandatory | Perform a graceful shutdown of the server when this event occurs. |
| 1.3.6.1.4.1.318.1.2.3.4.24.7 | ScalarpcnsParallelRedundancyLostShutdownDelay | read-write | mandatory | How long to wait after event occurs before performing a graceful shutdown of the server (seconds). |
| 1.3.6.1.4.1.318.1.2.3.4.25 | NodepcnsParallelRedundancyRegained | |||
| 1.3.6.1.4.1.318.1.2.3.4.25.1 | ScalarpcnsParallelRedundancyRegainedDesc | read-only | mandatory | The Description of the event. |
| 1.3.6.1.4.1.318.1.2.3.4.25.2 | ScalarpcnsParallelRedundancyRegainedEnableLogging | read-write | mandatory | Log occurrences of this event in PCNS log. |
| 1.3.6.1.4.1.318.1.2.3.4.25.3 | ScalarpcnsParallelRedundancyRegainedEnableCommandFile | read-write | mandatory | Execute a command file when this event occurs. |
| 1.3.6.1.4.1.318.1.2.3.4.25.4 | ScalarpcnsParallelRedundancyRegainedCommandFilePath | read-write | mandatory | Path of command file to execute when this event occurs. |
| 1.3.6.1.4.1.318.1.2.3.4.25.5 | ScalarpcnsParallelRedundancyRegainedCommandFileDelay | read-write | mandatory | How long to wait after event occurs before executing command file (seconds). |
| 1.3.6.1.4.1.318.1.2.3.4.26 | NodepcnsMaxInternalTempExceeded | |||
| 1.3.6.1.4.1.318.1.2.3.4.26.1 | ScalarpcnsMaxInternalTempExceededDesc | read-only | mandatory | The Description of the event. |
| 1.3.6.1.4.1.318.1.2.3.4.26.2 | ScalarpcnsMaxInternalTempExceededEnableLogging | read-write | mandatory | Log occurrences of this event in PCNS log. |
| 1.3.6.1.4.1.318.1.2.3.4.26.3 | ScalarpcnsMaxInternalTempExceededEnableCommandFile | read-write | mandatory | Execute a command file when this event occurs. |
| 1.3.6.1.4.1.318.1.2.3.4.26.4 | ScalarpcnsMaxInternalTempExceededCommandFilePath | read-write | mandatory | Path of command file to execute when this event occurs. |
| 1.3.6.1.4.1.318.1.2.3.4.26.5 | ScalarpcnsMaxInternalTempExceededCommandFileDelay | read-write | mandatory | How long to wait after event occurs before executing command file (seconds). |
| 1.3.6.1.4.1.318.1.2.3.4.26.6 | ScalarpcnsMaxInternalTempExceededEnableShutdown | read-write | mandatory | Perform a graceful shutdown of the server when this event occurs. |
| 1.3.6.1.4.1.318.1.2.3.4.26.7 | ScalarpcnsMaxInternalTempExceededShutdownDelay | read-write | mandatory | How long to wait after event occurs before performing a graceful shutdown of the server (seconds). |
| 1.3.6.1.4.1.318.1.2.3.4.27 | NodepcnsMaxInternalTempInRange | |||
| 1.3.6.1.4.1.318.1.2.3.4.27.1 | ScalarpcnsMaxInternalTempInRangeDesc | read-only | mandatory | The Description of the event. |
| 1.3.6.1.4.1.318.1.2.3.4.27.2 | ScalarpcnsMaxInternalTempInRangeEnableLogging | read-write | mandatory | Log occurrences of this event in PCNS log. |
| 1.3.6.1.4.1.318.1.2.3.4.27.3 | ScalarpcnsMaxInternalTempInRangeEnableCommandFile | read-write | mandatory | Execute a command file when this event occurs. |
| 1.3.6.1.4.1.318.1.2.3.4.27.4 | ScalarpcnsMaxInternalTempInRangeCommandFilePath | read-write | mandatory | Path of command file to execute when this event occurs. |
| 1.3.6.1.4.1.318.1.2.3.4.27.5 | ScalarpcnsMaxInternalTempInRangeCommandFileDelay | read-write | mandatory | How long to wait after event occurs before executing command file (seconds). |
| 1.3.6.1.4.1.318.1.2.3.4.28 | NodepcnsMinLoadCapabilityLost | |||
| 1.3.6.1.4.1.318.1.2.3.4.28.1 | ScalarpcnsMinLoadCapabilityLostDesc | read-only | mandatory | The Description of the event. |
| 1.3.6.1.4.1.318.1.2.3.4.28.2 | ScalarpcnsMinLoadCapabilityLostEnableLogging | read-write | mandatory | Log occurrences of this event in PCNS log. |
| 1.3.6.1.4.1.318.1.2.3.4.28.3 | ScalarpcnsMinLoadCapabilityLostEnableCommandFile | read-write | mandatory | Execute a command file when this event occurs. |
| 1.3.6.1.4.1.318.1.2.3.4.28.4 | ScalarpcnsMinLoadCapabilityLostCommandFilePath | read-write | mandatory | Path of command file to execute when this event occurs. |
| 1.3.6.1.4.1.318.1.2.3.4.28.5 | ScalarpcnsMinLoadCapabilityLostCommandFileDelay | read-write | mandatory | How long to wait after event occurs before executing command file (seconds). |
| 1.3.6.1.4.1.318.1.2.3.4.28.6 | ScalarpcnsMinLoadCapabilityLostEnableShutdown | read-write | mandatory | Perform a graceful shutdown of the server when this event occurs. |
| 1.3.6.1.4.1.318.1.2.3.4.28.7 | ScalarpcnsMinLoadCapabilityLostShutdownDelay | read-write | mandatory | How long to wait after event occurs before performing a graceful shutdown of the server (seconds). |
| 1.3.6.1.4.1.318.1.2.3.4.29 | NodepcnsMinLoadCapabilityRegained | |||
| 1.3.6.1.4.1.318.1.2.3.4.29.1 | ScalarpcnsMinLoadCapabilityRegainedDesc | read-only | mandatory | The Description of the event. |
| 1.3.6.1.4.1.318.1.2.3.4.29.2 | ScalarpcnsMinLoadCapabilityRegainedEnableLogging | read-write | mandatory | Log occurrences of this event in PCNS log. |
| 1.3.6.1.4.1.318.1.2.3.4.29.3 | ScalarpcnsMinLoadCapabilityRegainedEnableCommandFile | read-write | mandatory | Execute a command file when this event occurs. |
| 1.3.6.1.4.1.318.1.2.3.4.29.4 | ScalarpcnsMinLoadCapabilityRegainedCommandFilePath | read-write | mandatory | Path of command file to execute when this event occurs. |
| 1.3.6.1.4.1.318.1.2.3.4.29.5 | ScalarpcnsMinLoadCapabilityRegainedCommandFileDelay | read-write | mandatory | How long to wait after event occurs before executing command file (seconds). |
| 1.3.6.1.4.1.318.1.2.3.4.30 | NodepcnsEnvironmentCommunicationEstablished | |||
| 1.3.6.1.4.1.318.1.2.3.4.30.1 | ScalarpcnsEnvironmentCommunicationEstablishedDesc | read-only | mandatory | The Description of the event. |
| 1.3.6.1.4.1.318.1.2.3.4.30.2 | ScalarpcnsEnvironmentCommunicationEstablishedEnableLogging | read-write | mandatory | Log occurrences of this event in PCNS log. |
| 1.3.6.1.4.1.318.1.2.3.4.30.3 | ScalarpcnsEnvironmentCommunicationEstablishedEnableCommandFile | read-write | mandatory | Execute a command file when this event occurs. |
| 1.3.6.1.4.1.318.1.2.3.4.30.4 | ScalarpcnsEnvironmentCommunicationEstablishedCommandFilePath | read-write | mandatory | Path of command file to execute when this event occurs. |
| 1.3.6.1.4.1.318.1.2.3.4.30.5 | ScalarpcnsEnvironmentCommunicationEstablishedCommandFileDelay | read-write | mandatory | How long to wait after event occurs before executing command file (seconds). |
| 1.3.6.1.4.1.318.1.2.3.4.31 | NodepcnsEnvironmentCommunicationLost | |||
| 1.3.6.1.4.1.318.1.2.3.4.31.1 | ScalarpcnsEnvironmentCommunicationLostDesc | read-only | mandatory | The Description of the event. |
| 1.3.6.1.4.1.318.1.2.3.4.31.2 | ScalarpcnsEnvironmentCommunicationLostEnableLogging | read-write | mandatory | Log occurrences of this event in PCNS log. |
| 1.3.6.1.4.1.318.1.2.3.4.31.3 | ScalarpcnsEnvironmentCommunicationLostEnableCommandFile | read-write | mandatory | Execute a command file when this event occurs. |
| 1.3.6.1.4.1.318.1.2.3.4.31.4 | ScalarpcnsEnvironmentCommunicationLostCommandFilePath | read-write | mandatory | Path of command file to execute when this event occurs. |
| 1.3.6.1.4.1.318.1.2.3.4.31.5 | ScalarpcnsEnvironmentCommunicationLostCommandFileDelay | read-write | mandatory | How long to wait after event occurs before executing command file (seconds). |
| 1.3.6.1.4.1.318.1.2.3.4.32 | NodepcnsTempInRangeProbe1 | |||
| 1.3.6.1.4.1.318.1.2.3.4.32.1 | ScalarpcnsTempInRangeProbe1Desc | read-only | mandatory | The Description of the event. |
| 1.3.6.1.4.1.318.1.2.3.4.32.2 | ScalarpcnsTempInRangeProbe1EnableLogging | read-write | mandatory | Log occurrences of this event in PCNS log. |
| 1.3.6.1.4.1.318.1.2.3.4.32.3 | ScalarpcnsTempInRangeProbe1EnableCommandFile | read-write | mandatory | Execute a command file when this event occurs. |
| 1.3.6.1.4.1.318.1.2.3.4.32.4 | ScalarpcnsTempInRangeProbe1CommandFilePath | read-write | mandatory | Path of command file to execute when this event occurs. |
| 1.3.6.1.4.1.318.1.2.3.4.32.5 | ScalarpcnsTempInRangeProbe1CommandFileDelay | read-write | mandatory | How long to wait after event occurs before executing command file (seconds). |
| 1.3.6.1.4.1.318.1.2.3.4.33 | NodepcnsTempOutOfRangeProbe1 | |||
| 1.3.6.1.4.1.318.1.2.3.4.33.1 | ScalarpcnsTempOutOfRangeProbe1Desc | read-only | mandatory | The Description of the event. |
| 1.3.6.1.4.1.318.1.2.3.4.33.2 | ScalarpcnsTempOutOfRangeProbe1EnableLogging | read-write | mandatory | Log occurrences of this event in PCNS log. |
| 1.3.6.1.4.1.318.1.2.3.4.33.3 | ScalarpcnsTempOutOfRangeProbe1EnableCommandFile | read-write | mandatory | Execute a command file when this event occurs. |
| 1.3.6.1.4.1.318.1.2.3.4.33.4 | ScalarpcnsTempOutOfRangeProbe1CommandFilePath | read-write | mandatory | Path of command file to execute when this event occurs. |
| 1.3.6.1.4.1.318.1.2.3.4.33.5 | ScalarpcnsTempOutOfRangeProbe1CommandFileDelay | read-write | mandatory | How long to wait after event occurs before executing command file (seconds). |
| 1.3.6.1.4.1.318.1.2.3.4.33.6 | ScalarpcnsTempOutOfRangeProbe1EnableShutdown | read-write | mandatory | Perform a graceful shutdown of the server when this event occurs. |
| 1.3.6.1.4.1.318.1.2.3.4.33.7 | ScalarpcnsTempOutOfRangeProbe1ShutdownDelay | read-write | mandatory | How long to wait after event occurs before performing a graceful shutdown of the server (seconds). |
| 1.3.6.1.4.1.318.1.2.3.4.34 | NodepcnsHumidityInRangeProbe1 | |||
| 1.3.6.1.4.1.318.1.2.3.4.34.1 | ScalarpcnsHumidityInRangeProbe1Desc | read-only | mandatory | The Description of the event. |
| 1.3.6.1.4.1.318.1.2.3.4.34.2 | ScalarpcnsHumidityInRangeProbe1EnableLogging | read-write | mandatory | Log occurrences of this event in PCNS log. |
| 1.3.6.1.4.1.318.1.2.3.4.34.3 | ScalarpcnsHumidityInRangeProbe1EnableCommandFile | read-write | mandatory | Execute a command file when this event occurs. |
| 1.3.6.1.4.1.318.1.2.3.4.34.4 | ScalarpcnsHumidityInRangeProbe1CommandFilePath | read-write | mandatory | Path of command file to execute when this event occurs. |
| 1.3.6.1.4.1.318.1.2.3.4.34.5 | ScalarpcnsHumidityInRangeProbe1CommandFileDelay | read-write | mandatory | How long to wait after event occurs before executing command file (seconds). |
| 1.3.6.1.4.1.318.1.2.3.4.35 | NodepcnsHumidityOutOfRangeProbe1 | |||
| 1.3.6.1.4.1.318.1.2.3.4.35.1 | ScalarpcnsHumidityOutOfRangeProbe1Desc | read-only | mandatory | The Description of the event. |
| 1.3.6.1.4.1.318.1.2.3.4.35.2 | ScalarpcnsHumidityOutOfRangeProbe1EnableLogging | read-write | mandatory | Log occurrences of this event in PCNS log. |
| 1.3.6.1.4.1.318.1.2.3.4.35.3 | ScalarpcnsHumidityOutOfRangeProbe1EnableCommandFile | read-write | mandatory | Execute a command file when this event occurs. |
| 1.3.6.1.4.1.318.1.2.3.4.35.4 | ScalarpcnsHumidityOutOfRangeProbe1CommandFilePath | read-write | mandatory | Path of command file to execute when this event occurs. |
| 1.3.6.1.4.1.318.1.2.3.4.35.5 | ScalarpcnsHumidityOutOfRangeProbe1CommandFileDelay | read-write | mandatory | How long to wait after event occurs before executing command file (seconds). |
| 1.3.6.1.4.1.318.1.2.3.4.35.6 | ScalarpcnsHumidityOutOfRangeProbe1EnableShutdown | read-write | mandatory | Perform a graceful shutdown of the server when this event occurs. |
| 1.3.6.1.4.1.318.1.2.3.4.35.7 | ScalarpcnsHumidityOutOfRangeProbe1ShutdownDelay | read-write | mandatory | How long to wait after event occurs before performing a graceful shutdown of the server (seconds). |
| 1.3.6.1.4.1.318.1.2.3.4.36 | NodepcnsTempInRangeProbe2 | |||
| 1.3.6.1.4.1.318.1.2.3.4.36.1 | ScalarpcnsTempInRangeProbe2Desc | read-only | mandatory | The Description of the event. |
| 1.3.6.1.4.1.318.1.2.3.4.36.2 | ScalarpcnsTempInRangeProbe2EnableLogging | read-write | mandatory | Log occurrences of this event in PCNS log. |
| 1.3.6.1.4.1.318.1.2.3.4.36.3 | ScalarpcnsTempInRangeProbe2EnableCommandFile | read-write | mandatory | Execute a command file when this event occurs. |
| 1.3.6.1.4.1.318.1.2.3.4.36.4 | ScalarpcnsTempInRangeProbe2CommandFilePath | read-write | mandatory | Path of command file to execute when this event occurs. |
| 1.3.6.1.4.1.318.1.2.3.4.36.5 | ScalarpcnsTempInRangeProbe2CommandFileDelay | read-write | mandatory | How long to wait after event occurs before executing command file (seconds). |
| 1.3.6.1.4.1.318.1.2.3.4.37 | NodepcnsTempOutOfRangeProbe2 | |||
| 1.3.6.1.4.1.318.1.2.3.4.37.1 | ScalarpcnsTempOutOfRangeProbe2Desc | read-only | mandatory | The Description of the event. |
| 1.3.6.1.4.1.318.1.2.3.4.37.2 | ScalarpcnsTempOutOfRangeProbe2EnableLogging | read-write | mandatory | Log occurrences of this event in PCNS log. |
| 1.3.6.1.4.1.318.1.2.3.4.37.3 | ScalarpcnsTempOutOfRangeProbe2EnableCommandFile | read-write | mandatory | Execute a command file when this event occurs. |
| 1.3.6.1.4.1.318.1.2.3.4.37.4 | ScalarpcnsTempOutOfRangeProbe2CommandFilePath | read-write | mandatory | Path of command file to execute when this event occurs. |
| 1.3.6.1.4.1.318.1.2.3.4.37.5 | ScalarpcnsTempOutOfRangeProbe2CommandFileDelay | read-write | mandatory | How long to wait after event occurs before executing command file (seconds). |
| 1.3.6.1.4.1.318.1.2.3.4.37.6 | ScalarpcnsTempOutOfRangeProbe2EnableShutdown | read-write | mandatory | Perform a graceful shutdown of the server when this event occurs. |
| 1.3.6.1.4.1.318.1.2.3.4.37.7 | ScalarpcnsTempOutOfRangeProbe2ShutdownDelay | read-write | mandatory | How long to wait after event occurs before performing a graceful shutdown of the server (seconds). |
| 1.3.6.1.4.1.318.1.2.3.4.38 | NodepcnsHumidityInRangeProbe2 | |||
| 1.3.6.1.4.1.318.1.2.3.4.38.1 | ScalarpcnsHumidityInRangeProbe2Desc | read-only | mandatory | The Description of the event. |
| 1.3.6.1.4.1.318.1.2.3.4.38.2 | ScalarpcnsHumidityInRangeProbe2EnableLogging | read-write | mandatory | Log occurrences of this event in PCNS log. |
| 1.3.6.1.4.1.318.1.2.3.4.38.3 | ScalarpcnsHumidityInRangeProbe2EnableCommandFile | read-write | mandatory | Execute a command file when this event occurs. |
| 1.3.6.1.4.1.318.1.2.3.4.38.4 | ScalarpcnsHumidityInRangeProbe2CommandFilePath | read-write | mandatory | Path of command file to execute when this event occurs. |
| 1.3.6.1.4.1.318.1.2.3.4.38.5 | ScalarpcnsHumidityInRangeProbe2CommandFileDelay | read-write | mandatory | How long to wait after event occurs before executing command file (seconds). |
| 1.3.6.1.4.1.318.1.2.3.4.39 | NodepcnsHumidityOutOfRangeProbe2 | |||
| 1.3.6.1.4.1.318.1.2.3.4.39.1 | ScalarpcnsHumidityOutOfRangeProbe2Desc | read-only | mandatory | The Description of the event. |
| 1.3.6.1.4.1.318.1.2.3.4.39.2 | ScalarpcnsHumidityOutOfRangeProbe2EnableLogging | read-write | mandatory | Log occurrences of this event in PCNS log. |
| 1.3.6.1.4.1.318.1.2.3.4.39.3 | ScalarpcnsHumidityOutOfRangeProbe2EnableCommandFile | read-write | mandatory | Execute a command file when this event occurs. |
| 1.3.6.1.4.1.318.1.2.3.4.39.4 | ScalarpcnsHumidityOutOfRangeProbe2CommandFilePath | read-write | mandatory | Path of command file to execute when this event occurs. |
| 1.3.6.1.4.1.318.1.2.3.4.39.5 | ScalarpcnsHumidityOutOfRangeProbe2CommandFileDelay | read-write | mandatory | How long to wait after event occurs before executing command file (seconds). |
| 1.3.6.1.4.1.318.1.2.3.4.39.6 | ScalarpcnsHumidityOutOfRangeProbe2EnableShutdown | read-write | mandatory | Perform a graceful shutdown of the server when this event occurs. |
| 1.3.6.1.4.1.318.1.2.3.4.39.7 | ScalarpcnsHumidityOutOfRangeProbe2ShutdownDelay | read-write | mandatory | How long to wait after event occurs before performing a graceful shutdown of the server (seconds). |
| 1.3.6.1.4.1.318.1.2.3.4.40 | NodepcnsContactFault1 | |||
| 1.3.6.1.4.1.318.1.2.3.4.40.1 | ScalarpcnsContactFault1Desc | read-only | mandatory | The Description of the event. |
| 1.3.6.1.4.1.318.1.2.3.4.40.2 | ScalarpcnsContactFault1EnableLogging | read-write | mandatory | Log occurrences of this event in PCNS log. |
| 1.3.6.1.4.1.318.1.2.3.4.40.3 | ScalarpcnsContactFault1EnableCommandFile | read-write | mandatory | Execute a command file when this event occurs. |
| 1.3.6.1.4.1.318.1.2.3.4.40.4 | ScalarpcnsContactFault1CommandFilePath | read-write | mandatory | Path of command file to execute when this event occurs. |
| 1.3.6.1.4.1.318.1.2.3.4.40.5 | ScalarpcnsContactFault1CommandFileDelay | read-write | mandatory | How long to wait after event occurs before executing command file (seconds). |
| 1.3.6.1.4.1.318.1.2.3.4.40.6 | ScalarpcnsContactFault1EnableShutdown | read-write | mandatory | Perform a graceful shutdown of the server when this event occurs. |
| 1.3.6.1.4.1.318.1.2.3.4.40.7 | ScalarpcnsContactFault1ShutdownDelay | read-write | mandatory | How long to wait after event occurs before performing a graceful shutdown of the server (seconds). |
| 1.3.6.1.4.1.318.1.2.3.4.41 | NodepcnsContactFault2 | |||
| 1.3.6.1.4.1.318.1.2.3.4.41.1 | ScalarpcnsContactFault2Desc | read-only | mandatory | The Description of the event. |
| 1.3.6.1.4.1.318.1.2.3.4.41.2 | ScalarpcnsContactFault2EnableLogging | read-write | mandatory | Log occurrences of this event in PCNS log. |
| 1.3.6.1.4.1.318.1.2.3.4.41.3 | ScalarpcnsContactFault2EnableCommandFile | read-write | mandatory | Execute a command file when this event occurs. |
| 1.3.6.1.4.1.318.1.2.3.4.41.4 | ScalarpcnsContactFault2CommandFilePath | read-write | mandatory | Path of command file to execute when this event occurs. |
| 1.3.6.1.4.1.318.1.2.3.4.41.5 | ScalarpcnsContactFault2CommandFileDelay | read-write | mandatory | How long to wait after event occurs before executing command file (seconds). |
| 1.3.6.1.4.1.318.1.2.3.4.41.6 | ScalarpcnsContactFault2EnableShutdown | read-write | mandatory | Perform a graceful shutdown of the server when this event occurs. |
| 1.3.6.1.4.1.318.1.2.3.4.41.7 | ScalarpcnsContactFault2ShutdownDelay | read-write | mandatory | How long to wait after event occurs before performing a graceful shutdown of the server (seconds). |
| 1.3.6.1.4.1.318.1.2.3.4.42 | NodepcnsContactFault3 | |||
| 1.3.6.1.4.1.318.1.2.3.4.42.1 | ScalarpcnsContactFault3Desc | read-only | mandatory | The Description of the event. |
| 1.3.6.1.4.1.318.1.2.3.4.42.2 | ScalarpcnsContactFault3EnableLogging | read-write | mandatory | Log occurrences of this event in PCNS log. |
| 1.3.6.1.4.1.318.1.2.3.4.42.3 | ScalarpcnsContactFault3EnableCommandFile | read-write | mandatory | Execute a command file when this event occurs. |
| 1.3.6.1.4.1.318.1.2.3.4.42.4 | ScalarpcnsContactFault3CommandFilePath | read-write | mandatory | Path of command file to execute when this event occurs. |
| 1.3.6.1.4.1.318.1.2.3.4.42.5 | ScalarpcnsContactFault3CommandFileDelay | read-write | mandatory | How long to wait after event occurs before executing command file (seconds). |
| 1.3.6.1.4.1.318.1.2.3.4.42.6 | ScalarpcnsContactFault3EnableShutdown | read-write | mandatory | Perform a graceful shutdown of the server when this event occurs. |
| 1.3.6.1.4.1.318.1.2.3.4.42.7 | ScalarpcnsContactFault3ShutdownDelay | read-write | mandatory | How long to wait after event occurs before performing a graceful shutdown of the server (seconds). |
| 1.3.6.1.4.1.318.1.2.3.4.43 | NodepcnsContactFault4 | |||
| 1.3.6.1.4.1.318.1.2.3.4.43.1 | ScalarpcnsContactFault4Desc | read-only | mandatory | The Description of the event. |
| 1.3.6.1.4.1.318.1.2.3.4.43.2 | ScalarpcnsContactFault4EnableLogging | read-write | mandatory | Log occurrences of this event in PCNS log. |
| 1.3.6.1.4.1.318.1.2.3.4.43.3 | ScalarpcnsContactFault4EnableCommandFile | read-write | mandatory | Execute a command file when this event occurs. |
| 1.3.6.1.4.1.318.1.2.3.4.43.4 | ScalarpcnsContactFault4CommandFilePath | read-write | mandatory | Path of command file to execute when this event occurs. |
| 1.3.6.1.4.1.318.1.2.3.4.43.5 | ScalarpcnsContactFault4CommandFileDelay | read-write | mandatory | How long to wait after event occurs before executing command file (seconds). |
| 1.3.6.1.4.1.318.1.2.3.4.43.6 | ScalarpcnsContactFault4EnableShutdown | read-write | mandatory | Perform a graceful shutdown of the server when this event occurs. |
| 1.3.6.1.4.1.318.1.2.3.4.43.7 | ScalarpcnsContactFault4ShutdownDelay | read-write | mandatory | How long to wait after event occurs before performing a graceful shutdown of the server (seconds). |
| 1.3.6.1.4.1.318.1.2.3.4.44 | NodepcnsContactNormal1 | |||
| 1.3.6.1.4.1.318.1.2.3.4.44.1 | ScalarpcnsContactNormal1Desc | read-only | mandatory | The Description of the event. |
| 1.3.6.1.4.1.318.1.2.3.4.44.2 | ScalarpcnsContactNormal1EnableLogging | read-write | mandatory | Log occurrences of this event in PCNS log. |
| 1.3.6.1.4.1.318.1.2.3.4.44.3 | ScalarpcnsContactNormal1EnableCommandFile | read-write | mandatory | Execute a command file when this event occurs. |
| 1.3.6.1.4.1.318.1.2.3.4.44.4 | ScalarpcnsContactNormal1CommandFilePath | read-write | mandatory | Path of command file to execute when this event occurs. |
| 1.3.6.1.4.1.318.1.2.3.4.44.5 | ScalarpcnsContactNormal1CommandFileDelay | read-write | mandatory | How long to wait after event occurs before executing command file (seconds). |
| 1.3.6.1.4.1.318.1.2.3.4.45 | NodepcnsContactNormal2 | |||
| 1.3.6.1.4.1.318.1.2.3.4.45.1 | ScalarpcnsContactNormal2Desc | read-only | mandatory | The Description of the event. |
| 1.3.6.1.4.1.318.1.2.3.4.45.2 | ScalarpcnsContactNormal2EnableLogging | read-write | mandatory | Log occurrences of this event in PCNS log. |
| 1.3.6.1.4.1.318.1.2.3.4.45.3 | ScalarpcnsContactNormal2EnableCommandFile | read-write | mandatory | Execute a command file when this event occurs. |
| 1.3.6.1.4.1.318.1.2.3.4.45.4 | ScalarpcnsContactNormal2CommandFilePath | read-write | mandatory | Path of command file to execute when this event occurs. |
| 1.3.6.1.4.1.318.1.2.3.4.45.5 | ScalarpcnsContactNormal2CommandFileDelay | read-write | mandatory | How long to wait after event occurs before executing command file (seconds). |
| 1.3.6.1.4.1.318.1.2.3.4.46 | NodepcnsContactNormal3 | |||
| 1.3.6.1.4.1.318.1.2.3.4.46.1 | ScalarpcnsContactNormal3Desc | read-only | mandatory | The Description of the event. |
| 1.3.6.1.4.1.318.1.2.3.4.46.2 | ScalarpcnsContactNormal3EnableLogging | read-write | mandatory | Log occurrences of this event in PCNS log. |
| 1.3.6.1.4.1.318.1.2.3.4.46.3 | ScalarpcnsContactNormal3EnableCommandFile | read-write | mandatory | Execute a command file when this event occurs. |
| 1.3.6.1.4.1.318.1.2.3.4.46.4 | ScalarpcnsContactNormal3CommandFilePath | read-write | mandatory | Path of command file to execute when this event occurs. |
| 1.3.6.1.4.1.318.1.2.3.4.46.5 | ScalarpcnsContactNormal3CommandFileDelay | read-write | mandatory | How long to wait after event occurs before executing command file (seconds). |
| 1.3.6.1.4.1.318.1.2.3.4.47 | NodepcnsContactNormal4 | |||
| 1.3.6.1.4.1.318.1.2.3.4.47.1 | ScalarpcnsContactNormal4Desc | read-only | mandatory | The Description of the event. |
| 1.3.6.1.4.1.318.1.2.3.4.47.2 | ScalarpcnsContactNormal4EnableLogging | read-write | mandatory | Log occurrences of this event in PCNS log. |
| 1.3.6.1.4.1.318.1.2.3.4.47.3 | ScalarpcnsContactNormal4EnableCommandFile | read-write | mandatory | Execute a command file when this event occurs. |
| 1.3.6.1.4.1.318.1.2.3.4.47.4 | ScalarpcnsContactNormal4CommandFilePath | read-write | mandatory | Path of command file to execute when this event occurs. |
| 1.3.6.1.4.1.318.1.2.3.4.47.5 | ScalarpcnsContactNormal4CommandFileDelay | read-write | mandatory | How long to wait after event occurs before executing command file (seconds). |
| 1.3.6.1.4.1.318.1.2.3.5 | NodepcnsShutdown | |||
| 1.3.6.1.4.1.318.1.2.3.5.1 | ScalarpcnsShutdownCommandFileEnabled | read-write | mandatory | Run a shutdown command file before performing graceful shutdown. |
| 1.3.6.1.4.1.318.1.2.3.5.2 | ScalarpcnsShutdownCommandFileDelay | read-write | mandatory | How long in seconds to wait before running a shutdown command file before graceful shutdown. |
| 1.3.6.1.4.1.318.1.2.3.5.3 | ScalarpcnsShutdownCommandFile | read-write | mandatory | Full name of the shutdown command file to run before graceful shutdown. |
| 1.3.6.1.4.1.318.1.2.3.5.4 | ScalarpcnsShutdownCommandFileDuration | read-write | mandatory | How long in seconds shutdown command file takes to run. |
| 1.3.6.1.4.1.318.1.2.3.5.5 | ScalarpcnsTurnOffUps | read-write | mandatory | Turn off the UPS when performing a graceful shutdown. |
| 1.3.6.1.4.1.318.1.2.3.5.6 | ScalarpcnsTurnOffSOG | read-write | mandatory | Turn off the Outlet Group on the UPS when performing a graceful shutdown. |
| 1.3.6.1.4.1.318.1.2.3.5.7 | ScalarpcnsRuntimeRemainingThreshold | read-write | mandatory | This defines a threshold for runtime remaining. When the UPS is running on battery power and the runtime remaining on the UPS drops below the threshold, PowerC… |
| 1.3.6.1.4.1.318.1.2.3.5.8 | ScalarpcnsRuntimeRemainingCmdFileThreshold | read-write | mandatory | This defines a threshold for runtime remaining. When runtime remaining drops below this threshold, PowerChute will execute the command file. |
| 1.3.6.1.4.1.318.1.2.3.5.9 | TablepcnsAdvancedShutdownTable | not-accessible | mandatory | The Network Management Cards in the UPS's which PCNS is monitoring to provide safe shutdown. |
| 1.3.6.1.4.1.318.1.2.3.5.9.1 | RowpcnsAdvancedShutdownEntry | not-accessible | mandatory | Details of the NMC. |
| 1.3.6.1.4.1.318.1.2.3.5.9.1.1 | ColumnpcnsAdvancedGroupNo | read-only | mandatory | Index of the Advanced Shutdown Group. |
| 1.3.6.1.4.1.318.1.2.3.5.9.1.2 | ColumnpcnsAdvancedGroupName | read-write | mandatory | Name of the Advanced Shutdown Group. |
| 1.3.6.1.4.1.318.1.2.3.5.9.1.3 | ColumnpcnsAdvancedGroupNMC | read-only | mandatory | List of NMCs in the Advanced Shutdown Group. |
| 1.3.6.1.4.1.318.1.2.3.5.9.1.4 | ColumnpcnsAdvancedShutdownUPSRequiredForLoad | read-write | mandatory | Number of UPS's required to power load. |
| 1.3.6.1.4.1.318.1.2.3.5.9.1.5 | ColumnpcnsAdvancedShutdownCommandFileEnabled | read-write | mandatory | Run a shutdown command file before performing graceful shutdown. |
| 1.3.6.1.4.1.318.1.2.3.5.9.1.6 | ColumnpcnsAdvancedShutdownCommandFile | read-write | mandatory | Full name of the shutdown command file to run before graceful shutdown. |
| 1.3.6.1.4.1.318.1.2.3.5.9.1.7 | ColumnpcnsAdvancedShutdownCommandFileDuration | read-write | mandatory | How long in seconds shutdown command file takes to run. |
| 1.3.6.1.4.1.318.1.2.3.5.9.1.8 | ColumnpcnsAdvancedShutdownPowerchuteServer | read-write | mandatory | Shut down PowerChute Server. |
| 1.3.6.1.4.1.318.1.2.3.5.9.1.9 | ColumnpcnsAdvancedShutdownOnLostRedundancy | read-write | mandatory | Shut down if Redundancy lost. |
| 1.3.6.1.4.1.318.1.2.3.5.9.1.10 | ColumnpcnsAdvancedTurnOffUps | read-write | mandatory | Turn off the UPS when performing a graceful shutdown. |
| 1.3.6.1.4.1.318.1.2.3.5.9.1.11 | ColumnpcnsAdvancedTurnOffSOG | read-write | mandatory | Turn off the Outlet Group on the UPS when performing a graceful shutdown. |
| 1.3.6.1.4.1.318.1.2.3.6 | NodepcnsAlarms | |||
| 1.3.6.1.4.1.318.1.2.3.6.1 | ScalarpcnsCriticalFlag | read-only | mandatory | PowerChute Network Shutdown has begun a safe shutdown of the host. |
| 1.3.6.1.4.1.318.1.2.3.6.2 | ScalarpcnsCriticalCause | read-only | mandatory | The reason PowerChute Network Shutdown has begun a safe shutdown. |
| 1.3.6.1.4.1.318.1.2.3.6.3 | ScalarpcnsNetComsLostFlag | read-only | mandatory | PowerChute cannot communicate with NMC. |
| 1.3.6.1.4.1.318.1.2.3.6.4 | ScalarpcnsNMCComsLostFlag | read-only | mandatory | NMC cannot communicate with UPS. |
| 1.3.6.1.4.1.318.1.2.3.6.5 | ScalarpcnsUpdateAvailableFlag | read-only | mandatory | PowerChute has detected that a newer version is available. |
| 1.3.6.1.4.1.318.1.2.3.6.6 | ScalarpcnsUpdateDesc | read-only | mandatory | Details of the newer version of PowerChute. |
| 1.3.6.1.4.1.318.1.2.3.7 | ScalarpcnsLoggingLevel | read-write | mandatory | Override the Root Logging level for PCNS. Possible Values: CLEAR, DEBUG |
| 1.3.6.1.4.1.318.1.2.4 | NodepowerChuteBusinessEdition | |||
| 1.3.6.1.4.1.318.1.2.4.1 | NodepcbeIdent | |||
| 1.3.6.1.4.1.318.1.2.4.1.1 | ScalarpcbeHostname | read-only | mandatory | The hostname of the PCBE instance. |
| 1.3.6.1.4.1.318.1.2.4.1.2 | ScalarpcbeVersion | read-only | mandatory | The version of PCBE installed. x.x.x |
| 1.3.6.1.4.1.318.1.2.4.1.3 | ScalarpcbeOS | read-only | mandatory | The version of OS PCBE is installed on. |
| 1.3.6.1.4.1.318.1.2.4.1.4 | ScalarpcbeJavaVersion | read-only | mandatory | The version of Java PCBE is running on. |
| 1.3.6.1.4.1.318.1.2.4.1.5 | ScalarpcbeUIProtocol | read-only | mandatory | Web Protocol used to connect to the PCBE UI. |
| 1.3.6.1.4.1.318.1.2.4.1.6 | ScalarpcbeHttpPort | read-only | mandatory | Port used for PCBE http UI. |
| 1.3.6.1.4.1.318.1.2.4.1.7 | ScalarpcbeHttpsPort | read-only | mandatory | Port used for PCBE https UI. |
| 1.3.6.1.4.1.318.1.2.4.6 | NodepcbeAlarms | |||
| 1.3.6.1.4.1.318.1.2.4.6.1 | ScalarpcbeCriticalFlag | read-only | mandatory | PowerChute Business Edition has begun a safe shutdown of the host. |
| 1.3.6.1.4.1.318.1.2.4.6.2 | ScalarpcbeCriticalCause | read-only | mandatory | The reason PowerChute Business Edition has begun a safe shutdown. |
| 1.3.6.1.4.1.318.1.2.4.6.3 | ScalarpcbeComsLostFlag | read-only | mandatory | If active (1), PowerChute cannot communicate with UPS |
| 1.3.6.1.4.1.318.1.2.4.6.5 | ScalarpcbeUpdateAvailableFlag | read-only | mandatory | PowerChute has detected that a newer version is available. |
| 1.3.6.1.4.1.318.1.2.4.6.6 | ScalarpcbeUpdateDesc | read-only | mandatory | Details of the newer version of PowerChute. |
| 1.3.6.1.4.1.318.1.3 | Nodesystem | |||
| 1.3.6.1.4.1.318.1.3.4 | NodemasterSwitch | |||
| 1.3.6.1.4.1.318.1.3.4.1 | NodemasterSwitchV1 | |||
| 1.3.6.1.4.1.318.1.3.4.2 | NodemasterSwitchV2 | |||
| 1.3.6.1.4.1.318.1.3.4.3 | NodemasterSwitchVM | |||
| 1.3.6.1.4.1.318.1.3.4.4 | NodemasterSwitchMSP | |||
| 1.3.6.1.4.1.318.1.3.4.5 | NodemasterSwitchrPDU | |||
| 1.3.6.1.4.1.318.1.3.4.6 | NodemasterSwitchrPDU2 | |||
| 1.3.6.1.4.1.318.1.3.4.7 | NodemasterSwitchsPDU | |||
| 1.3.6.1.4.1.318.1.3.4.8 | NodemasterSwitchrPDUB | |||
| 1.3.6.1.4.1.318.1.3.4.9 | NodemasterSwitchePDU | |||
| 1.3.6.1.4.1.318.1.4 | Nodeexperimental | |||
| 1.3.6.1.4.1.318.2 | Nodemgmt | |||
| 1.3.6.1.4.1.318.750 | NoderpduCriticalCondition | SEVERE: A RPDU critical condition has been detected. The first variable is the serial number. The second variable is the device name. The third variable is the… | ||
| 1.3.6.1.4.1.318.751 | NoderpduCriticalConditionCleared | INFORMATIONAL: A RPDU critical condition has been cleared. The first variable is the serial number. The second variable is the device name. The third variable … | ||
| 1.3.6.1.4.1.318.752 | NoderpduWarningCondition | WARNING: A RPDU warning condition has been detected. The first variable is the serial number. The second variable is the device name. The third variable is the… | ||
| 1.3.6.1.4.1.318.753 | NoderpduWarningConditionCleared | WARNING: A RPDU warning condition has been cleared. The first variable is the serial number. The second variable is the device name. The third variable is the … | ||
| 1.3.6.1.4.1.318.754 | NoderpduInformationalCondition | INFORMATIONAL: A RPDU informational condition has been detected. The first variable is the serial number. The second variable is the device name. The third var… | ||
| 1.3.6.1.4.1.318.755 | NoderpduInformationalConditionCleared | INFORMATIONAL: A RPDU informational condition has been cleared. The first variable is the serial number. The second variable is the device name. The third vari… |
Type Definitions
| Name | Syntax | Status | Description |
|---|---|---|---|
| AirIRG2RDType2IOState | INTEGER { open(1), closed(2) } | ||
| AirIRmActivityState | INTEGER { inactive(1), active(2) } | ||
| AirIRmAlarmState | INTEGER { ok(1), alarm(2) } | ||
| AirIRmControlState | INTEGER { off(1), on(2) } | ||
| AirIRmStopState | INTEGER { maybeOn(1), unitOff(2) } | ||
| AirIRSCCapacityControlType | INTEGER { discrete(1), proportional(2) } | ||
| AirIRSCConfigType | INTEGER { racs(1), spot(2), in-row(3) } | ||
| AirIRSCFanSpeedControl | INTEGER { automatic(1), manual(2) } | ||
| AirIRSCFanSpeedPreference | INTEGER { low(1), med-low(2), med(3), med-high(4), high(5) } | ||
| Rpdu2OutletPhaseLayoutType | INTEGER { seqPhase1ToNeutral(1), seqPhase2ToNeutral(2), seqPhase3ToNeutral(3), seqPhase1ToPhase2(4), seqPhase2ToPhase3(5), seqPhase3ToPhase1(6) } |