MIB Viewer

PowerNet-PDU

808 objects
No module-level DESCRIPTION found.
OIDNameAccessStatusDescription
1.3.6.1.2.1Nodemconfig
1.3.6.1.2.1.1ScalarmconfigNumTrapReceiversread-onlycurrentThe number of managers to send traps to.
1.3.6.1.2.1.2TablemconfigTrapReceiverTablenot-accessiblecurrentA list of managers to send traps to. The number of entries is given by the value of mconfigNumTrapReceivers.
1.3.6.1.2.1.2.1RowmconfigTrapReceiverEntrynot-accessiblecurrentThe managers to send traps to.
1.3.6.1.2.1.2.1.1ColumntrapIndexread-onlycurrentThe index to a trap receiver entry.
1.3.6.1.2.1.2.1.2ColumnreceiverAddrread-writecurrentThe IP address of the manager to send a trap to.
1.3.6.1.2.1.2.1.3ColumncommunityStringread-writecurrentThe community name to use in the trap when sent to the manager.
1.3.6.1.2.1.2.1.4Columnseverityread-onlyobsoleteThe severity threshold of traps to send to the manager. traps are labeled in severity as informational(1), warning(2), severe(3). Only traps of equal or greate…
1.3.6.1.2.1.2.1.5ColumnacceptThisReceiverread-writecurrentThe value of yes(1) indicates that trap generation for this manager is enabled. The value of no(2) indicates that trap generation for this manager is disabled
1.3.6.1.2.1.2.1.6ColumnreceiveTrapTyperead-onlyobsoleteType of trap.
1.3.6.1.2.1.3ScalarmconfigBOOTPEnabledread-onlycurrentThe value of yes(1) indicates the PowerNet Adapter is configured to obtain its IP configuration parameters from a BOOTP server. The value of no(2) indicates ad…
1.3.6.1.2.1.4ScalarmconfigTFTPServerIPread-writecurrentThe IP address of TFTP server. If mconfigBOOTPEnabled is yes(1), then this IP address is provided by BOOTP server and not allowed to be modified; otherwise, th…
1.3.6.1.2.1.5ScalarnewCodeAuthentViaTFTPread-onlycurrentOnce mcontrolRestartAgent is set to loadAndExecuteNewAgent (3), PowerNet adapter will start to load the remote image file, for authentication only, instead of …
1.3.6.1.2.1.6NodemconfigClock
1.3.6.1.2.1.6.1ScalarmconfigClockDateread-writecurrentThe current date in the mm/dd/yyyy format. Example: 01/01/2000.
1.3.6.1.2.1.6.2ScalarmconfigClockTimeread-writecurrentThe current time in the hh:mm:ss am/pm format. Example: 12:00:00 am.
1.3.6.1.2.2Nodemcontrol
1.3.6.1.2.2.1ScalarmcontrolRestartAgentread-writecurrentSetting this OID to restartCurrentAgent (1) will restart the same SNMP agent code currently saved in flash memory. Setting this OID to loadAndExecuteNewAgent (…
1.3.6.1.2.3Nodemtrapargs
1.3.6.1.2.3.1ScalarmtrapargsIntegerread-onlycurrentThis OID allows traps to be sent with an integer argument that my not be defined in the MIB. A get of this OID will return 0.
1.3.6.1.2.3.2ScalarmtrapargsIpAddressread-onlycurrentThis OID allows traps to be sent with an IP address argument that my not be defined in the MIB. A get of this OID will return 0.0.0.0.
1.3.6.1.2.3.3ScalarmtrapargsStringread-onlycurrentThis OID allows traps to be sent with an octet string argument that my not be defined in the MIB. A get of this OID will return a NULL string.
1.3.6.1.2.3.4ScalarmtrapargsGaugeread-onlycurrentThis OID allows traps to be sent with a Gauge argument that my not be defined in the MIB. A get of this OID will return 0.
1.3.6.1.2.3.5ScalarmtrapargsTimeTicksread-onlycurrentThis OID allows traps to be sent with a TimeTicks argument that my not be defined in the MIB. A get of this OID will return 0.
1.3.6.1.2.3.6ScalarmtrapargsInteger02read-onlycurrentThis OID allows traps to be sent with an integer argument that my not be defined in the MIB. A get of this OID will return 0.
1.3.6.1.2.3.7ScalarmtrapargsInteger03read-onlycurrentThis OID allows traps to be sent with an integer argument that my not be defined in the MIB. A get of this OID will return 0.
1.3.6.1.2.3.8ScalarmtrapargsIpAddress02read-onlycurrentThis OID allows traps to be sent with an IP address argument that my not be defined in the MIB. A get of this OID will return 0.0.0.0.
1.3.6.1.2.3.9ScalarmtrapargsIpAddress03read-onlycurrentThis OID allows traps to be sent with an IP address argument that my not be defined in the MIB. A get of this OID will return 0.0.0.0.
1.3.6.1.2.3.10ScalarmtrapargsString02read-onlycurrentThis OID allows traps to be sent with an octet string argument that my not be defined in the MIB. A get of this OID will return a NULL string.
1.3.6.1.2.3.11ScalarmtrapargsString03read-onlycurrentThis OID allows traps to be sent with an octet string argument that my not be defined in the MIB. A get of this OID will return a NULL string.
1.3.6.1.2.3.12ScalarmtrapargsGauge02read-onlycurrentThis OID allows traps to be sent with a Gauge argument that my not be defined in the MIB. A get of this OID will return 0.
1.3.6.1.2.3.13ScalarmtrapargsGauge03read-onlycurrentThis OID allows traps to be sent with a Gauge argument that my not be defined in the MIB. A get of this OID will return 0.
1.3.6.1.2.3.14ScalarmtrapargsTimeTicks02read-onlycurrentThis OID allows traps to be sent with a TimeTicks argument that my not be defined in the MIB. A get of this OID will return 0.
1.3.6.1.2.3.15ScalarmtrapargsTimeTicks03read-onlycurrentThis OID allows traps to be sent with a TimeTicks argument that my not be defined in the MIB. A get of this OID will return 0.
1.3.6.1.2.3.16ScalarmtrapargsString04read-onlycurrentThis OID allows traps to be sent with an octet string argument that my not be defined in the MIB. A get of this OID will return a NULL string.
1.3.6.1.2.3.17ScalarmtrapargsString05read-onlycurrentThis OID allows traps to be sent with an octet string argument that my not be defined in the MIB. A get of this OID will return a NULL string.
1.3.6.1.2.3.18ScalarmtrapargsInteger04read-onlycurrentThis OID allows traps to be sent with an integer argument that my not be defined in the MIB. A get of this OID will return 0.
1.3.6.1.2.3.19ScalarmtrapargsInteger05read-onlycurrentThis OID allows traps to be sent with an integer argument that my not be defined in the MIB. A get of this OID will return 0.
1.3.6.1.2.3.20ScalarmtrapargsString06read-onlycurrentThis OID allows traps to be sent with an octet string argument that my not be defined in the MIB. A get of this OID will return a NULL string.
1.3.6.1.2.3.21ScalarmtrapargsString07read-onlycurrentThis OID allows traps to be sent with an octet string argument that my not be defined in the MIB. A get of this OID will return a NULL string.
1.3.6.1.2.3.22ScalarmtrapargsString08read-onlycurrentThis OID allows traps to be sent with an octet string argument that my not be defined in the MIB. A get of this OID will return a NULL string.
1.3.6.1.2.3.23ScalarmtrapargsOctetStringread-onlycurrentThis OID allows traps to be sent with an octet string argument that my not be defined in the MIB. A get of this OID will return a NULL string.
1.3.6.1.2.3.24ScalarmtrapargsOctetString02read-onlycurrentThis OID allows traps to be sent with an octet string argument that my not be defined in the MIB. A get of this OID will return a NULL string.
1.3.6.1.2.3.25ScalarmtrapargsOctetString03read-onlycurrentThis OID allows traps to be sent with an octet string argument that my not be defined in the MIB. A get of this OID will return a NULL string.
1.3.6.1.2.3.26ScalarmtrapargsOctetString04read-onlycurrentThis OID allows traps to be sent with an octet string argument that my not be defined in the MIB. A get of this OID will return a NULL string.
1.3.6.1.2.3.27ScalarmtrapargsOctetString05read-onlycurrentThis OID allows traps to be sent with an octet string argument that my not be defined in the MIB. A get of this OID will return a NULL string.
1.3.6.1.2.3.28ScalarmtrapargsOctetString06read-onlycurrentThis OID allows traps to be sent with an octet string argument that my not be defined in the MIB. A get of this OID will return a NULL string.
1.3.6.1.2.3.29ScalarmtrapargsOctetString07read-onlycurrentThis OID allows traps to be sent with an octet string argument that my not be defined in the MIB. A get of this OID will return a NULL string.
1.3.6.1.2.3.30ScalarmtrapargsOctetString08read-onlycurrentThis OID allows traps to be sent with an octet string argument that my not be defined in the MIB. A get of this OID will return a NULL string.
1.3.6.1.2.4Nodemfiletransfer
1.3.6.1.2.4.1NodemfiletransferStatus
1.3.6.1.2.4.1.1ScalarmfiletransferStatusLastTransferResultread-onlydeprecatedThis OID has been deprecated. Once mfiletransferControlInitiateFileTransfer is set to a value other than doNotInitiateFileTransfer a file transfer of mfiletran…
1.3.6.1.2.4.2NodemfiletransferConfig
1.3.6.1.2.4.2.1NodemfiletransferConfigSettings
1.3.6.1.2.4.2.1.1ScalarmfiletransferConfigSettingsFilenameread-writedeprecatedThis OID has been deprecated. The path and name of the file to transfer using the mfiletransferControlInitiateFileTransfer OID. If the file to transfer exists …
1.3.6.1.2.4.2.2NodemfiletransferConfigTFTP
1.3.6.1.2.4.2.2.1ScalarmfiletransferConfigTFTPServerAddressread-writedeprecatedThis OID has been deprecated. The IP Address in dotted decimal notation of the TFTP server involved in the file transfer.
1.3.6.1.2.4.2.3NodemfiletransferConfigFTP
1.3.6.1.2.4.2.3.1ScalarmfiletransferConfigFTPServerAddressread-writedeprecatedThis OID has been deprecated. The IP Address in dotted decimal notation of the FTP server involved in the file transfer.
1.3.6.1.2.4.2.3.2ScalarmfiletransferConfigFTPServerUserread-writedeprecatedThis OID has been deprecated. The user identification for logging into the FTP server specified with mfiletransferConfigFTPServerAddress.
1.3.6.1.2.4.2.3.3ScalarmfiletransferConfigFTPServerPasswordread-writedeprecatedThis OID has been deprecated. The password for logging into the FTP server specified with mfiletransferConfigFTPServerAddress.
1.3.6.1.2.4.3NodemfiletransferControl
1.3.6.1.2.4.3.1ScalarmfiletransferControlInitiateFileTransferread-writedeprecatedThis OID has been deprecated. Setting this OID to doNotInitiateFileTransfer (1) will do nothing. Setting this OID to initiateFileTransferDownloadViaTFTP (2) wi…
1.3.6.1.4.1.318NodePDU
1.3.6.1.4.1.318.1Nodeproducts
1.3.6.1.4.1.318.1.1Nodehardware
1.3.6.1.4.1.318.1.1.26NoderPDU2
1.3.6.1.4.1.318.1.1.26.1ScalarrPDU2IdentTableSizeread-onlymandatoryThe total number of Rack PDUs
1.3.6.1.4.1.318.1.1.26.2TablerPDU2IdentTablenot-accessiblemandatoryA table of Rack PDU identification data
1.3.6.1.4.1.318.1.1.26.2.1RowrPDU2IdentEntrynot-accessiblemandatoryIdentification data from Rack PDU being queried
1.3.6.1.4.1.318.1.1.26.2.1.1ColumnrPDU2IdentIndexread-onlymandatoryThe index to the Rack PDU identification table entry
1.3.6.1.4.1.318.1.1.26.2.1.2ColumnrPDU2IdentModuleread-onlymandatoryThe user-defined Rack PDU numeric ID
1.3.6.1.4.1.318.1.1.26.2.1.3ColumnrPDU2IdentNameread-onlymandatoryA user-defined string identifying the Rack PDU
1.3.6.1.4.1.318.1.1.26.2.1.4ColumnrPDU2IdentLocationread-onlymandatoryA user-defined string identifying the location of the Rack PDU
1.3.6.1.4.1.318.1.1.26.2.1.5ColumnrPDU2IdentHardwareRevread-onlymandatoryThe Rack PDU hardware version
1.3.6.1.4.1.318.1.1.26.2.1.6ColumnrPDU2IdentFirmwareRevread-onlymandatoryThe Rack PDU firmware version
1.3.6.1.4.1.318.1.1.26.2.1.7ColumnrPDU2IdentDateOfManufactureread-onlymandatoryThe date the Rack PDU was manufactured in mm/dd/yyyy format
1.3.6.1.4.1.318.1.1.26.2.1.8ColumnrPDU2IdentModelNumberread-onlymandatoryThe Rack PDU model number
1.3.6.1.4.1.318.1.1.26.2.1.9ColumnrPDU2IdentSerialNumberread-onlymandatoryThe Rack PDU serial number
1.3.6.1.4.1.318.1.1.26.2.1.10ColumnrPDU2IdentContactread-onlymandatoryA user-defined string identifying the person to contact regarding the Rack PDU
1.3.6.1.4.1.318.1.1.26.2.1.11ColumnrPDU2IdentBootMonitorRevread-onlymandatoryThe Rack PDU Boot Monitor version
1.3.6.1.4.1.318.1.1.26.2.1.12ColumnrPDU2IdentLongDescriptionread-onlymandatoryThe Rack PDU Long Description name
1.3.6.1.4.1.318.1.1.26.2.1.13ColumnrPDU2IdentNMCSerialNumberread-onlymandatoryThe Rack PDU Network Management Card (NMC) serial number
1.3.6.1.4.1.318.1.1.26.3ScalarrPDU2DeviceTableSizeread-onlymandatoryThe total number of Rack PDUs
1.3.6.1.4.1.318.1.1.26.4NoderPDU2Device
1.3.6.1.4.1.318.1.1.26.4.1TablerPDU2DeviceConfigTablenot-accessiblemandatoryA table of Rack PDU configuration data
1.3.6.1.4.1.318.1.1.26.4.1.1RowrPDU2DeviceConfigEntrynot-accessiblemandatoryConfiguration data from Rack PDU being queried
1.3.6.1.4.1.318.1.1.26.4.1.1.1ColumnrPDU2DeviceConfigIndexread-onlymandatoryThe index to the Rack PDU table entry
1.3.6.1.4.1.318.1.1.26.4.1.1.2ColumnrPDU2DeviceConfigModuleread-writemandatoryThe user-defined Rack PDU numeric ID
1.3.6.1.4.1.318.1.1.26.4.1.1.3ColumnrPDU2DeviceConfigNameread-writemandatoryA user-defined string identifying the Rack PDU
1.3.6.1.4.1.318.1.1.26.4.1.1.4ColumnrPDU2DeviceConfigLocationread-writemandatoryA user-defined string identifying the location of the Rack PDU
1.3.6.1.4.1.318.1.1.26.4.1.1.5ColumnrPDU2DeviceConfigDisplayOrientationread-writemandatoryIndicates the intended physical orientation of the display. displayNormal(1) indicates normal orientation displayReverse(2) indicates upside down orientation
1.3.6.1.4.1.318.1.1.26.4.1.1.6ColumnrPDU2DeviceConfigColdstartDelayread-writemandatoryThe amount of delay, measured in seconds, between when power is provided to the Rack PDU and when the Rack PDU provides basic master power to the outlets. Allo…
1.3.6.1.4.1.318.1.1.26.4.1.1.7ColumnrPDU2DeviceConfigLowLoadPowerThresholdread-writemandatoryUser-defined low power draw alarm threshold, measured in tenths of kilowatts. Models that do not support this feature will respond to this OID with a value of …
1.3.6.1.4.1.318.1.1.26.4.1.1.8ColumnrPDU2DeviceConfigNearOverloadPowerThresholdread-writemandatoryUser-defined near power overload threshold, measured in tenths of kilowatts. Models that do not support this feature will respond to this OID with a value of -…
1.3.6.1.4.1.318.1.1.26.4.1.1.9ColumnrPDU2DeviceConfigOverloadPowerThresholdread-writemandatoryUser-defined power overload threshold, measured in tenths of kilowatts. Models that do not support this feature will respond to this OID with a value of -1.
1.3.6.1.4.1.318.1.1.26.4.1.1.10ColumnrPDU2DeviceConfigDevicePeakPowerResetread-writemandatorySetting this OID to reset (2) will cause the existing peak power value to be replaced by the current load power value. Getting this OID will do nothing and ret…
1.3.6.1.4.1.318.1.1.26.4.1.1.11ColumnrPDU2DeviceConfigDeviceEnergyResetread-writemandatorySetting this OID to reset (2) will cause the device energy meter value to be reset to zero. Getting this OID in models that support this feature will do nothin…
1.3.6.1.4.1.318.1.1.26.4.1.1.12ColumnrPDU2DeviceConfigOutletsEnergyResetread-writemandatorySetting this OID to reset (2) will cause the all outlet energy meter values to be reset to zero. Getting this OID will do nothing and return the noOperation(1)…
1.3.6.1.4.1.318.1.1.26.4.1.1.13ColumnrPDU2DeviceConfigOutletsPeakLoadResetread-writemandatorySetting this OID to reset (2) will cause the all outlet peak load values to be reset to zero. Getting this OID will do nothing and return the noOperation(1) va…
1.3.6.1.4.1.318.1.1.26.4.1.1.14ColumnrPDU2DeviceConfigContactread-writemandatoryA user-defined string identifying the person to contact regarding the Rack PDU
1.3.6.1.4.1.318.1.1.26.4.2TablerPDU2DevicePropertiesTablenot-accessiblemandatoryA table of Rack PDU properties
1.3.6.1.4.1.318.1.1.26.4.2.1RowrPDU2DevicePropertiesEntrynot-accessiblemandatoryProperties of the Rack PDU being queried
1.3.6.1.4.1.318.1.1.26.4.2.1.1ColumnrPDU2DevicePropertiesIndexread-onlymandatoryThe index to the Rack PDU properties table entry
1.3.6.1.4.1.318.1.1.26.4.2.1.2ColumnrPDU2DevicePropertiesModuleread-onlymandatoryThe user-defined Rack PDU numeric ID
1.3.6.1.4.1.318.1.1.26.4.2.1.3ColumnrPDU2DevicePropertiesNameread-onlymandatoryA user-defined string identifying the Rack PDU
1.3.6.1.4.1.318.1.1.26.4.2.1.4ColumnrPDU2DevicePropertiesNumOutletsread-onlymandatoryThe number of outlets on the Rack PDU
1.3.6.1.4.1.318.1.1.26.4.2.1.5ColumnrPDU2DevicePropertiesNumSwitchedOutletsread-onlymandatoryThe number of switched outlets on the Rack PDU
1.3.6.1.4.1.318.1.1.26.4.2.1.6ColumnrPDU2DevicePropertiesNumMeteredOutletsread-onlymandatoryThe number of metered outlets on the Rack PDU
1.3.6.1.4.1.318.1.1.26.4.2.1.7ColumnrPDU2DevicePropertiesNumPhasesread-onlymandatoryThe number of phases present in the Rack PDU
1.3.6.1.4.1.318.1.1.26.4.2.1.8ColumnrPDU2DevicePropertiesNumMeteredBanksread-onlymandatoryThe number of metered banks present in the Rack PDU
1.3.6.1.4.1.318.1.1.26.4.2.1.9ColumnrPDU2DevicePropertiesMaxCurrentRatingread-onlymandatoryThe maximum current rating, measured in Amps, for the Rack PDU
1.3.6.1.4.1.318.1.1.26.4.2.1.10ColumnrPDU2DevicePropertiesOrientationread-onlymandatoryRack PDU orientation
1.3.6.1.4.1.318.1.1.26.4.2.1.11ColumnrPDU2DevicePropertiesOutletLayoutread-onlymandatoryGetting this OID will return outlet layout for the device. seqPhaseToNeutral(1) indicates outlet layout as follows: 1:1-N,2:2-N,3:3-N,4:1-N,5:2-N,... or for si…
1.3.6.1.4.1.318.1.1.26.4.2.1.12ColumnrPDU2DevicePropertiesMaxPhaseCurrentRatingread-onlymandatoryThe maximum current rating, measured in Amps, for the Rack PDU
1.3.6.1.4.1.318.1.1.26.4.2.1.13ColumnrPDU2DevicePropertiesDevicePowerRatingread-onlymandatoryThe maximum power rating, measured in tenths of kilowatts, for the Rack PDU
1.3.6.1.4.1.318.1.1.26.4.3TablerPDU2DeviceStatusTablenot-accessiblemandatoryA table of Rack PDU status information
1.3.6.1.4.1.318.1.1.26.4.3.1RowrPDU2DeviceStatusEntrynot-accessiblemandatoryStatus information from the Rack PDU being queried
1.3.6.1.4.1.318.1.1.26.4.3.1.1ColumnrPDU2DeviceStatusIndexread-onlymandatoryThe index to the Rack PDU status table entry
1.3.6.1.4.1.318.1.1.26.4.3.1.2ColumnrPDU2DeviceStatusModuleread-onlymandatoryThe user-defined Rack PDU numeric ID
1.3.6.1.4.1.318.1.1.26.4.3.1.3ColumnrPDU2DeviceStatusNameread-onlymandatoryA user-defined string identifying the Rack PDU
1.3.6.1.4.1.318.1.1.26.4.3.1.4ColumnrPDU2DeviceStatusLoadStateread-onlymandatoryIndicates the present load status of the Rack PDU. Models that do not support this feature will respond to this OID with a value of notsupported (5).
1.3.6.1.4.1.318.1.1.26.4.3.1.5ColumnrPDU2DeviceStatusPowerread-onlymandatoryThe power consumption of the Rack PDU load in hundredths of kilowatts. Models that do not support this feature will respond to this OID with a value of -1.
1.3.6.1.4.1.318.1.1.26.4.3.1.6ColumnrPDU2DeviceStatusPeakPowerread-onlymandatoryThe peak power consumption of the Rack PDU load in hundredths of kilowatts. Models that do not support this feature will respond to this OID with a value of -1.
1.3.6.1.4.1.318.1.1.26.4.3.1.7ColumnrPDU2DeviceStatusPeakPowerTimestampread-onlymandatoryIndicates the date and time that peak power consumption occurred. Models that do not support this feature will respond to this OID with string 'notsupported'.
1.3.6.1.4.1.318.1.1.26.4.3.1.8ColumnrPDU2DeviceStatusPeakPowerStartTimeread-onlymandatoryIndicates the date and time of the last device peak power reset. Models that do not support this feature will respond to this OID with string 'notsupported'.
1.3.6.1.4.1.318.1.1.26.4.3.1.9ColumnrPDU2DeviceStatusEnergyread-onlymandatoryA user resettable energy meter measuring Rack PDU load energy consumption in tenths of kilowatt-hours. Models that do not support this feature will respond to …
1.3.6.1.4.1.318.1.1.26.4.3.1.10ColumnrPDU2DeviceStatusEnergyStartTimeread-onlymandatoryIndicates the date and time of the last device energy meter reset. Models that do not support this feature will respond to this OID with string 'notsupported'.
1.3.6.1.4.1.318.1.1.26.4.3.1.11ColumnrPDU2DeviceStatusCommandPendingread-onlymandatoryIndicates whether or not the device is processing a pending command. If the commandPendingUnknown (3) value is returned, all devices powered by the Rack PDU sh…
1.3.6.1.4.1.318.1.1.26.4.3.1.12ColumnrPDU2DeviceStatusPowerSupplyAlarmread-onlymandatoryIndicates a power supply alarm is active when value equals alarm (2)
1.3.6.1.4.1.318.1.1.26.4.3.1.13ColumnrPDU2DeviceStatusPowerSupply1Statusread-onlymandatoryIndicates whether or not an alarm is active in Power Supply 1
1.3.6.1.4.1.318.1.1.26.4.3.1.14ColumnrPDU2DeviceStatusPowerSupply2Statusread-onlymandatoryIndicates whether or not an alarm is active in Power Supply 2
1.3.6.1.4.1.318.1.1.26.4.3.1.15ColumnrPDU2DeviceStatusOutletsEnergyStartTimeread-onlymandatoryIndicates the date and time of the last outlets energy meter reset. Models that do not support this feature will respond to this OID with string 'notsupported'.
1.3.6.1.4.1.318.1.1.26.4.3.1.16ColumnrPDU2DeviceStatusApparentPowerread-onlymandatoryThe apparent power consumption of the Rack PDU load in hundredths of kiloVoltAmps (kVA). Models that do not support this feature will respond to this OID with …
1.3.6.1.4.1.318.1.1.26.4.3.1.17ColumnrPDU2DeviceStatusPowerFactorread-onlymandatoryThe power factor of the Rack PDU load in hundredths. Models that do not support this feature will respond to this OID with a value of -1.
1.3.6.1.4.1.318.1.1.26.4.3.1.18ColumnrPDU2DeviceStatusNPSTyperead-onlymandatoryThe device NPS status: notNPS (1) indicates the Rack PDU is not in an NPS group. host (2) indicates the Rack PDU has been designated as a host in an NPS group.…
1.3.6.1.4.1.318.1.1.26.4.3.1.19ColumnrPDU2DeviceStatusResidualPowerread-onlymandatoryThe measured device residual power from the PDU meters in hundredths of kiloVoltAmps.
1.3.6.1.4.1.318.1.1.26.4.3.1.20ColumnrPDU2DeviceStatusFrequencyread-onlymandatoryThe measured device frequency from the PDU meters in tenths of Hz.
1.3.6.1.4.1.318.1.1.26.4.4TablerPDU2DeviceControlTablenot-accessiblemandatoryA table of Rack PDU control data
1.3.6.1.4.1.318.1.1.26.4.4.1RowrPDU2DeviceControlEntrynot-accessiblemandatoryControl data from Rack PDU being queried
1.3.6.1.4.1.318.1.1.26.4.4.1.1ColumnrPDU2DeviceControlIndexread-onlymandatoryThe index to the Rack PDU control table entry
1.3.6.1.4.1.318.1.1.26.4.4.1.2ColumnrPDU2DeviceControlModuleread-onlymandatoryThe user-defined Rack PDU numeric ID
1.3.6.1.4.1.318.1.1.26.4.4.1.3ColumnrPDU2DeviceControlNameread-onlymandatoryA user-defined string identifying the Rack PDU
1.3.6.1.4.1.318.1.1.26.4.4.1.4ColumnrPDU2DeviceControlCommandread-writemandatorySetting this OID to immediateAllOn (1) will turn all outlets on immediately. Setting this OID to delayedAllOn (2) will turn all outlets on as defined by each o…
1.3.6.1.4.1.318.1.1.26.4.5ScalarrPDU2DeviceMapread-onlymandatoryThe Map of connected Rack PDUs
1.3.6.1.4.1.318.1.1.26.5ScalarrPDU2PhaseTableSizeread-onlymandatoryThe number of connected Rack PDU phases
1.3.6.1.4.1.318.1.1.26.6NoderPDU2Phase
1.3.6.1.4.1.318.1.1.26.6.1TablerPDU2PhaseConfigTablenot-accessiblemandatoryA table of Rack PDU phase configuration data
1.3.6.1.4.1.318.1.1.26.6.1.1RowrPDU2PhaseConfigEntrynot-accessiblemandatoryConfiguration data from currently queried Rack PDU phase
1.3.6.1.4.1.318.1.1.26.6.1.1.1ColumnrPDU2PhaseConfigIndexread-onlymandatoryThe index to the Rack PDU phase configuration table entry
1.3.6.1.4.1.318.1.1.26.6.1.1.2ColumnrPDU2PhaseConfigModuleread-onlymandatoryThe user-defined Rack PDU numeric ID
1.3.6.1.4.1.318.1.1.26.6.1.1.3ColumnrPDU2PhaseConfigNumberread-onlymandatoryThe numeric phase ID
1.3.6.1.4.1.318.1.1.26.6.1.1.4ColumnrPDU2PhaseConfigOverloadRestrictionread-writemandatoryThis OID controls the behavior of a Switched Rack PDU phase when an overload condition is possible and additional outlets are requested to be turned on. Settin…
1.3.6.1.4.1.318.1.1.26.6.1.1.5ColumnrPDU2PhaseConfigLowLoadCurrentThresholdread-writemandatoryUser-defined low load phase current threshold in Amps
1.3.6.1.4.1.318.1.1.26.6.1.1.6ColumnrPDU2PhaseConfigNearOverloadCurrentThresholdread-writemandatoryUser-defined near phase overload warning threshold in Amps
1.3.6.1.4.1.318.1.1.26.6.1.1.7ColumnrPDU2PhaseConfigOverloadCurrentThresholdread-writemandatoryUser-defined phase overload current threshold in Amps
1.3.6.1.4.1.318.1.1.26.6.1.1.8ColumnrPDU2PhaseConfigPhasePeakCurrentResetread-writemandatorySetting this OID to reset (2) will cause the existing peak current value to be replaced by the present load current value. Getting this OID will do nothing and…
1.3.6.1.4.1.318.1.1.26.6.2TablerPDU2PhasePropertiesTablenot-accessiblemandatoryA table of Rack PDU phase properties
1.3.6.1.4.1.318.1.1.26.6.2.1RowrPDU2PhasePropertiesEntrynot-accessiblemandatoryProperties of the currently queried Rack PDU phase
1.3.6.1.4.1.318.1.1.26.6.2.1.1ColumnrPDU2PhasePropertiesIndexread-onlymandatoryThe index to the Rack PDU phase properties table entry
1.3.6.1.4.1.318.1.1.26.6.2.1.2ColumnrPDU2PhasePropertiesModuleread-onlymandatoryThe user-defined Rack PDU numeric ID
1.3.6.1.4.1.318.1.1.26.6.2.1.3ColumnrPDU2PhasePropertiesNumberread-onlymandatoryThe numeric phase ID
1.3.6.1.4.1.318.1.1.26.6.3TablerPDU2PhaseStatusTablenot-accessiblemandatoryA table of Rack PDU phase status data
1.3.6.1.4.1.318.1.1.26.6.3.1RowrPDU2PhaseStatusEntrynot-accessiblemandatoryStatus data from currently queried Rack PDU phase
1.3.6.1.4.1.318.1.1.26.6.3.1.1ColumnrPDU2PhaseStatusIndexread-onlymandatoryThe index to the Rack PDU phase status table entry
1.3.6.1.4.1.318.1.1.26.6.3.1.2ColumnrPDU2PhaseStatusModuleread-onlymandatoryThe user-defined Rack PDU numeric ID
1.3.6.1.4.1.318.1.1.26.6.3.1.3ColumnrPDU2PhaseStatusNumberread-onlymandatoryThe numeric phase ID
1.3.6.1.4.1.318.1.1.26.6.3.1.4ColumnrPDU2PhaseStatusLoadStateread-onlymandatoryIndicates the present load status of the Rack PDU phase being queried
1.3.6.1.4.1.318.1.1.26.6.3.1.5ColumnrPDU2PhaseStatusCurrentread-onlymandatoryIndicates the current draw, in tenths of Amps, of the load on the Rack PDU phase being queried
1.3.6.1.4.1.318.1.1.26.6.3.1.6ColumnrPDU2PhaseStatusVoltageread-onlymandatoryIndicates the Voltage, in Volts, of the Rack PDU phase being queried. Models that do not support this feature will respond to this OID with a value of -1.
1.3.6.1.4.1.318.1.1.26.6.3.1.7ColumnrPDU2PhaseStatusPowerread-onlymandatoryIndicates the load power, in hundredths of kilowatts (kW), consumed on the Rack PDU phase being queried. Models that do not support this feature will respond t…
1.3.6.1.4.1.318.1.1.26.6.3.1.8ColumnrPDU2PhaseStatusApparentPowerread-onlymandatoryIndicates the load apparent power, in hundredths of kiloVoltAmps (kVA), consumed on the Rack PDU phase being queried. Models that do not support this feature w…
1.3.6.1.4.1.318.1.1.26.6.3.1.9ColumnrPDU2PhaseStatusPowerFactorread-onlymandatoryIndicates the load power factor, in hundredths, of the Rack PDU phase being queried. Models that do not support this feature will respond to this OID with a va…
1.3.6.1.4.1.318.1.1.26.6.3.1.10ColumnrPDU2PhaseStatusPeakCurrentread-onlymandatoryThe peak current of the Rack PDU phase load in tenths of Amps
1.3.6.1.4.1.318.1.1.26.6.3.1.11ColumnrPDU2PhaseStatusPeakCurrentTimestampread-onlymandatoryIndicates the date and time that the peak current occurred
1.3.6.1.4.1.318.1.1.26.6.3.1.12ColumnrPDU2PhaseStatusPeakCurrentStartTimeread-onlymandatoryIndicates the date and time of the last phase peak current reset
1.3.6.1.4.1.318.1.1.26.6.3.1.13ColumnrPDU2PhaseStatusEnergyread-onlymandatoryA user resettable energy meter measuring Rack PDU phase load energy consumption in tenths of kilowatt-hours. Models that do not support this feature will respo…
1.3.6.1.4.1.318.1.1.26.7ScalarrPDU2BankTableSizeread-onlymandatoryThe number of connected Rack PDU banks
1.3.6.1.4.1.318.1.1.26.8NoderPDU2Bank
1.3.6.1.4.1.318.1.1.26.8.1TablerPDU2BankConfigTablenot-accessiblemandatoryA table of Rack PDU bank configuration data
1.3.6.1.4.1.318.1.1.26.8.1.1RowrPDU2BankConfigEntrynot-accessiblemandatoryConfiguration data from currently queried Rack PDU bank
1.3.6.1.4.1.318.1.1.26.8.1.1.1ColumnrPDU2BankConfigIndexread-onlymandatoryThe index to the Rack PDU bank configuration table entry
1.3.6.1.4.1.318.1.1.26.8.1.1.2ColumnrPDU2BankConfigModuleread-onlymandatoryThe user-defined Rack PDU numeric ID
1.3.6.1.4.1.318.1.1.26.8.1.1.3ColumnrPDU2BankConfigNumberread-onlymandatoryThe numeric bank ID
1.3.6.1.4.1.318.1.1.26.8.1.1.4ColumnrPDU2BankConfigOverloadRestrictionread-writemandatoryThis OID controls the behavior of a Switched Rack PDU bank when an overload condition is possible and additional outlets are requested to be turned on. Setting…
1.3.6.1.4.1.318.1.1.26.8.1.1.5ColumnrPDU2BankConfigLowLoadCurrentThresholdread-writemandatoryUser-defined low load bank current threshold in Amps
1.3.6.1.4.1.318.1.1.26.8.1.1.6ColumnrPDU2BankConfigNearOverloadCurrentThresholdread-writemandatoryUser-defined near bank overload current warning threshold in Amps
1.3.6.1.4.1.318.1.1.26.8.1.1.7ColumnrPDU2BankConfigOverloadCurrentThresholdread-writemandatoryUser-defined bank overload current threshold in Amps
1.3.6.1.4.1.318.1.1.26.8.1.1.8ColumnrPDU2BankConfigBankPeakCurrentResetread-writemandatorySetting this OID to reset (2) will cause the existing peak current value to be replaced by the present load current value. Getting this OID will do nothing and…
1.3.6.1.4.1.318.1.1.26.8.2TablerPDU2BankPropertiesTablenot-accessiblemandatoryA table of Rack PDU bank properties
1.3.6.1.4.1.318.1.1.26.8.2.1RowrPDU2BankPropertiesEntrynot-accessiblemandatoryProperties of the currently queried Rack PDU bank
1.3.6.1.4.1.318.1.1.26.8.2.1.1ColumnrPDU2BankPropertiesIndexread-onlymandatoryThe index to the Rack PDU bank properties table entry
1.3.6.1.4.1.318.1.1.26.8.2.1.2ColumnrPDU2BankPropertiesModuleread-onlymandatoryThe user-defined Rack PDU numeric ID
1.3.6.1.4.1.318.1.1.26.8.2.1.3ColumnrPDU2BankPropertiesNumberread-onlymandatoryThe numeric bank ID
1.3.6.1.4.1.318.1.1.26.8.2.1.4ColumnrPDU2BankPropertiesPhaseLayoutread-onlymandatoryThis OID describes the outlet phase connections on the referenced bank as follows: seqPhase1ToNeutral(1) indicates that bank outlets are wired from Phase 1 to …
1.3.6.1.4.1.318.1.1.26.8.2.1.5ColumnrPDU2BankPropertiesBreakerRatingread-onlymandatoryIf bank circuit breakers are present on the device, this OID will return the rating of the breaker in Amps.
1.3.6.1.4.1.318.1.1.26.8.3TablerPDU2BankStatusTablenot-accessiblemandatoryA table of Rack PDU bank status data
1.3.6.1.4.1.318.1.1.26.8.3.1RowrPDU2BankStatusEntrynot-accessiblemandatoryStatus data from currently queried Rack PDU bank
1.3.6.1.4.1.318.1.1.26.8.3.1.1ColumnrPDU2BankStatusIndexread-onlymandatoryThe index to the Rack PDU bank status table entry
1.3.6.1.4.1.318.1.1.26.8.3.1.2ColumnrPDU2BankStatusModuleread-onlymandatoryThe user-defined Rack PDU numeric ID
1.3.6.1.4.1.318.1.1.26.8.3.1.3ColumnrPDU2BankStatusNumberread-onlymandatoryThe numeric bank ID
1.3.6.1.4.1.318.1.1.26.8.3.1.4ColumnrPDU2BankStatusLoadStateread-onlymandatoryIndicates the present load status of the Rack PDU bank being queried
1.3.6.1.4.1.318.1.1.26.8.3.1.5ColumnrPDU2BankStatusCurrentread-onlymandatoryIndicates the current draw, in tenths of Amps, of the load on the Rack PDU bank being queried
1.3.6.1.4.1.318.1.1.26.8.3.1.6ColumnrPDU2BankStatusPeakCurrentread-onlymandatoryThe peak current of the Rack PDU bank load in tenths of Amps
1.3.6.1.4.1.318.1.1.26.8.3.1.7ColumnrPDU2BankStatusPeakCurrentTimestampread-onlymandatoryIndicates the date and time the bank peak current occurred
1.3.6.1.4.1.318.1.1.26.8.3.1.8ColumnrPDU2BankStatusPeakCurrentStartTimeread-onlymandatoryIndicates the date and time of the last bank peak current reset
1.3.6.1.4.1.318.1.1.26.8.3.1.9ColumnrPDU2BankStatusVoltageread-onlymandatoryIndicates the Voltage, in Volts, of the Rack PDU bank being queried. Models that do not support this feature will respond to this OID with a value of -1.
1.3.6.1.4.1.318.1.1.26.8.3.1.10ColumnrPDU2BankStatusPowerread-onlymandatoryIndicates the load power, in hundredths of kilowatts (kW), consumed on the RackPDU phase being queried. Models that do not support this feature will respond to…
1.3.6.1.4.1.318.1.1.26.8.3.1.11ColumnrPDU2BankStatusEnergyread-onlymandatoryA user resettable energy meter measuring Rack PDU phase load energy consumption in tenths of kilowatt-hours. Models that do not support this feature will respo…
1.3.6.1.4.1.318.1.1.26.9NoderPDU2Outlet
1.3.6.1.4.1.318.1.1.26.9.1ScalarrPDU2OutletSwitchedTableSizeread-onlymandatoryThe number of switched outlets on connected Rack PDUs
1.3.6.1.4.1.318.1.1.26.9.2NoderPDU2OutletSwitched
1.3.6.1.4.1.318.1.1.26.9.2.1TablerPDU2OutletSwitchedConfigTablenot-accessiblemandatoryA table of Rack PDU switched outlet configuration data
1.3.6.1.4.1.318.1.1.26.9.2.1.1RowrPDU2OutletSwitchedConfigEntrynot-accessiblemandatoryConfiguration data from currently queried Rack PDU switched outlet
1.3.6.1.4.1.318.1.1.26.9.2.1.1.1ColumnrPDU2OutletSwitchedConfigIndexread-onlymandatoryThe index to the Rack PDU switched outlet configuration table entry
1.3.6.1.4.1.318.1.1.26.9.2.1.1.2ColumnrPDU2OutletSwitchedConfigModuleread-onlymandatoryThe user-defined Rack PDU numeric ID
1.3.6.1.4.1.318.1.1.26.9.2.1.1.3ColumnrPDU2OutletSwitchedConfigNameread-writemandatoryThe user-defined switched outlet ID string
1.3.6.1.4.1.318.1.1.26.9.2.1.1.4ColumnrPDU2OutletSwitchedConfigNumberread-onlymandatoryThe numeric switched outlet ID
1.3.6.1.4.1.318.1.1.26.9.2.1.1.5ColumnrPDU2OutletSwitchedConfigPowerOnTimeread-writemandatoryThe amount of delay, in seconds, between when power is provided to the Rack PDU and when this switched outlet starts providing power. Range -1...7200 where -1 …
1.3.6.1.4.1.318.1.1.26.9.2.1.1.6ColumnrPDU2OutletSwitchedConfigPowerOffTimeread-writemandatoryThe amount of time, in seconds, this outlet will delay powering off. Range -1...7200 where -1 = Never power off, 0 = immediate power off, and 1-7200 = seconds …
1.3.6.1.4.1.318.1.1.26.9.2.1.1.7ColumnrPDU2OutletSwitchedConfigRebootDurationread-writemandatoryAfter turning power off during a reboot sequence, the amount of time to wait before turning power to this outlet back on. Range 5-60 seconds delay.
1.3.6.1.4.1.318.1.1.26.9.2.1.1.8ColumnrPDU2OutletSwitchedConfigExternalLinkread-writemandatoryUser-defined external device web link. Possible use cases could be the IP address of the external device plugged into the outlet or its manufacturer web page f…
1.3.6.1.4.1.318.1.1.26.9.2.2TablerPDU2OutletSwitchedPropertiesTablenot-accessiblemandatoryA table of Rack PDU switched outlet properties
1.3.6.1.4.1.318.1.1.26.9.2.2.1RowrPDU2OutletSwitchedPropertiesEntrynot-accessiblemandatoryProperties of the currently queried Rack PDU switched outlet
1.3.6.1.4.1.318.1.1.26.9.2.2.1.1ColumnrPDU2OutletSwitchedPropertiesIndexread-onlymandatoryThe index to the Rack PDU switched outlet properties table entry
1.3.6.1.4.1.318.1.1.26.9.2.2.1.2ColumnrPDU2OutletSwitchedPropertiesModuleread-onlymandatoryThe user-defined Rack PDU numeric ID
1.3.6.1.4.1.318.1.1.26.9.2.2.1.3ColumnrPDU2OutletSwitchedPropertiesNameread-onlymandatoryThe user-defined switched outlet ID string
1.3.6.1.4.1.318.1.1.26.9.2.2.1.4ColumnrPDU2OutletSwitchedPropertiesNumberread-onlymandatoryThe numeric switched outlet ID
1.3.6.1.4.1.318.1.1.26.9.2.2.1.5ColumnrPDU2OutletSwitchedPropertiesPhaseLayoutread-onlymandatoryThis OID describes the phase connections of the referenced outlet as follows: seqPhase1ToNeutral(1) indicates that the outlet is wired from Phase 1 to Neutral.…
1.3.6.1.4.1.318.1.1.26.9.2.2.1.6ColumnrPDU2OutletSwitchedPropertiesBankread-onlymandatoryThe numeric bank ID
1.3.6.1.4.1.318.1.1.26.9.2.3TablerPDU2OutletSwitchedStatusTablenot-accessiblemandatoryA table of Rack PDU switched outlet status information
1.3.6.1.4.1.318.1.1.26.9.2.3.1RowrPDU2OutletSwitchedStatusEntrynot-accessiblemandatoryStatus information for currently queried Rack PDU switched outlet
1.3.6.1.4.1.318.1.1.26.9.2.3.1.1ColumnrPDU2OutletSwitchedStatusIndexread-onlymandatoryThe index to the Rack PDU switched outlet status information table entry
1.3.6.1.4.1.318.1.1.26.9.2.3.1.2ColumnrPDU2OutletSwitchedStatusModuleread-onlymandatoryThe user-defined Rack PDU numeric ID
1.3.6.1.4.1.318.1.1.26.9.2.3.1.3ColumnrPDU2OutletSwitchedStatusNameread-onlymandatoryThe user-defined switched outlet ID string
1.3.6.1.4.1.318.1.1.26.9.2.3.1.4ColumnrPDU2OutletSwitchedStatusNumberread-onlymandatoryThe numeric switched outlet ID
1.3.6.1.4.1.318.1.1.26.9.2.3.1.5ColumnrPDU2OutletSwitchedStatusStateread-onlymandatoryIndicates the present switch state of the Rack PDU switched outlet being queried
1.3.6.1.4.1.318.1.1.26.9.2.3.1.6ColumnrPDU2OutletSwitchedStatusCommandPendingread-onlymandatoryIndicates whether or not the device is processing a command for this outlet. If the commandPendingUnknown (3) value is returned, all devices powered by the Rac…
1.3.6.1.4.1.318.1.1.26.9.2.3.1.7ColumnrPDU2OutletSwitchedStatusExternalLinkread-onlymandatoryEach RPDU outlet can have its own external web URL link. This can be configured in the rPDU2OutletSwitchedConfigExternalLink OID. When this link is clicked in …
1.3.6.1.4.1.318.1.1.26.9.2.4TablerPDU2OutletSwitchedControlTablenot-accessiblemandatoryA table of Rack PDU switched outlet control data
1.3.6.1.4.1.318.1.1.26.9.2.4.1RowrPDU2OutletSwitchedControlEntrynot-accessiblemandatoryControl data for currently queried Rack PDU switched outlet
1.3.6.1.4.1.318.1.1.26.9.2.4.1.1ColumnrPDU2OutletSwitchedControlIndexread-onlymandatoryThe index to the Rack PDU switched outlet control data table entry
1.3.6.1.4.1.318.1.1.26.9.2.4.1.2ColumnrPDU2OutletSwitchedControlModuleread-onlymandatoryThe user-defined Rack PDU numeric ID
1.3.6.1.4.1.318.1.1.26.9.2.4.1.3ColumnrPDU2OutletSwitchedControlNameread-onlymandatoryThe user-defined switched outlet ID string
1.3.6.1.4.1.318.1.1.26.9.2.4.1.4ColumnrPDU2OutletSwitchedControlNumberread-onlymandatoryThe numeric switched outlet ID
1.3.6.1.4.1.318.1.1.26.9.2.4.1.5ColumnrPDU2OutletSwitchedControlCommandread-writemandatoryGetting this variable will return the outlet state. If the outlet is on, the immediateOn (1) value will be returned. If the outlet is off, the immediateOff (2)…
1.3.6.1.4.1.318.1.1.26.9.3ScalarrPDU2OutletMeteredTableSizeread-onlymandatoryThe number of metered outlets on connect Rack PDUs
1.3.6.1.4.1.318.1.1.26.9.4NoderPDU2OutletMetered
1.3.6.1.4.1.318.1.1.26.9.4.1TablerPDU2OutletMeteredConfigTablenot-accessiblemandatoryA table of Rack PDU metered outlet configuration data
1.3.6.1.4.1.318.1.1.26.9.4.1.1RowrPDU2OutletMeteredConfigEntrynot-accessiblemandatoryConfiguration data from currently queried Rack PDU metered outlet
1.3.6.1.4.1.318.1.1.26.9.4.1.1.1ColumnrPDU2OutletMeteredConfigIndexread-onlymandatoryThe index to the Rack PDU metered outlet configuration table entry
1.3.6.1.4.1.318.1.1.26.9.4.1.1.2ColumnrPDU2OutletMeteredConfigModuleread-onlymandatoryThe user-defined Rack PDU numeric ID
1.3.6.1.4.1.318.1.1.26.9.4.1.1.3ColumnrPDU2OutletMeteredConfigNameread-writemandatoryThe user-defined metered outlet ID string
1.3.6.1.4.1.318.1.1.26.9.4.1.1.4ColumnrPDU2OutletMeteredConfigNumberread-onlymandatoryThe numeric switched outlet ID
1.3.6.1.4.1.318.1.1.26.9.4.1.1.5ColumnrPDU2OutletMeteredConfigLowLoadCurrentThresholdread-writemandatoryUser-defined low load outlet current threshold in Watts
1.3.6.1.4.1.318.1.1.26.9.4.1.1.6ColumnrPDU2OutletMeteredConfigNearOverloadCurrentThresholdread-writemandatoryUser-defined near outlet overload warning threshold in Watts
1.3.6.1.4.1.318.1.1.26.9.4.1.1.7ColumnrPDU2OutletMeteredConfigOverloadCurrentThresholdread-writemandatoryUser-defined outlet overload current threshold in Watts
1.3.6.1.4.1.318.1.1.26.9.4.1.1.8ColumnrPDU2OutletMeteredConfigExternalLinkread-writemandatoryUser-defined external device web link. Possible use cases could be the IP address of the external device plugged into the outlet or its manufacturer web page f…
1.3.6.1.4.1.318.1.1.26.9.4.2TablerPDU2OutletMeteredPropertiesTablenot-accessiblemandatoryA table of Rack PDU metered outlet properties
1.3.6.1.4.1.318.1.1.26.9.4.2.1RowrPDU2OutletMeteredPropertiesEntrynot-accessiblemandatoryProperties of currently queried Rack PDU metered outlet
1.3.6.1.4.1.318.1.1.26.9.4.2.1.1ColumnrPDU2OutletMeteredPropertiesIndexread-onlymandatoryThe index to the Rack PDU metered properties table entry
1.3.6.1.4.1.318.1.1.26.9.4.2.1.2ColumnrPDU2OutletMeteredPropertiesModuleread-onlymandatoryThe user-defined Rack PDU numeric ID
1.3.6.1.4.1.318.1.1.26.9.4.2.1.3ColumnrPDU2OutletMeteredPropertiesNameread-onlymandatoryThe user-defined metered outlet ID string
1.3.6.1.4.1.318.1.1.26.9.4.2.1.4ColumnrPDU2OutletMeteredPropertiesNumberread-onlymandatoryThe numeric metered outlet ID
1.3.6.1.4.1.318.1.1.26.9.4.2.1.5ColumnrPDU2OutletMeteredPropertiesLayoutread-onlymandatoryThis OID describes the phase connections of the referenced outlet as follows: seqPhase1ToNeutral(1) indicates that the outlet is wired from Phase 1 to Neutral.…
1.3.6.1.4.1.318.1.1.26.9.4.2.1.6ColumnrPDU2OutletMeteredPropertiesPowerRatingread-onlymandatoryMaximum power rating of Rack PDU metered outlet
1.3.6.1.4.1.318.1.1.26.9.4.2.1.7ColumnrPDU2OutletMeteredPropertiesBankread-onlymandatoryThis outlet's numeric bank ID
1.3.6.1.4.1.318.1.1.26.9.4.3TablerPDU2OutletMeteredStatusTablenot-accessiblemandatoryA table of Rack PDU metered outlet status data
1.3.6.1.4.1.318.1.1.26.9.4.3.1RowrPDU2OutletMeteredStatusEntrynot-accessiblemandatoryStatus data from currently queried Rack PDU metered outlet
1.3.6.1.4.1.318.1.1.26.9.4.3.1.1ColumnrPDU2OutletMeteredStatusIndexread-onlymandatoryThe index to the Rack PDU metered status table entry
1.3.6.1.4.1.318.1.1.26.9.4.3.1.2ColumnrPDU2OutletMeteredStatusModuleread-onlymandatoryThe user-defined Rack PDU numeric ID
1.3.6.1.4.1.318.1.1.26.9.4.3.1.3ColumnrPDU2OutletMeteredStatusNameread-onlymandatoryThe user-defined metered outlet ID string
1.3.6.1.4.1.318.1.1.26.9.4.3.1.4ColumnrPDU2OutletMeteredStatusNumberread-onlymandatoryThe numeric metered outlet ID
1.3.6.1.4.1.318.1.1.26.9.4.3.1.5ColumnrPDU2OutletMeteredStatusStateread-onlymandatoryIndicates the present load status of the Rack PDU metered outlet being queried
1.3.6.1.4.1.318.1.1.26.9.4.3.1.6ColumnrPDU2OutletMeteredStatusCurrentread-onlymandatoryIndicates the current draw, in tenths of Amps, of the load on the Rack PDU outlet being queried
1.3.6.1.4.1.318.1.1.26.9.4.3.1.7ColumnrPDU2OutletMeteredStatusPowerread-onlymandatoryIndicates the power draw of the load on the Rack PDU outlet being queried
1.3.6.1.4.1.318.1.1.26.9.4.3.1.8ColumnrPDU2OutletMeteredStatusPeakPowerread-onlymandatoryIndicates the peak power load draw on the Rack PDU outlet being queried
1.3.6.1.4.1.318.1.1.26.9.4.3.1.9ColumnrPDU2OutletMeteredStatusPeakPowerTimestampread-onlymandatoryIndicates the date and time that this metered outlet's peak power consumption occurred
1.3.6.1.4.1.318.1.1.26.9.4.3.1.10ColumnrPDU2OutletMeteredStatusPeakPowerStartTimeread-onlymandatoryIndicates the start date and time that this metered outlet began recording peak power observations
1.3.6.1.4.1.318.1.1.26.9.4.3.1.11ColumnrPDU2OutletMeteredStatusEnergyread-onlymandatoryA user resettable energy meter measuring Rack PDU load energy consumption in tenths of kilowatt-hours
1.3.6.1.4.1.318.1.1.26.9.4.3.1.12ColumnrPDU2OutletMeteredStatusReceptacleTyperead-onlymandatoryIndicates receptacle type for the outlet.
1.3.6.1.4.1.318.1.1.26.9.4.3.1.13ColumnrPDU2OutletMeteredStatusExternalLinkread-onlymandatoryEach RPDU outlet can have its own external web URL link. This can be configured in the rPDU2OutletMeteredConfigExternalLink OID. When this link is clicked in t…
1.3.6.1.4.1.318.1.1.26.9.4.3.1.14ColumnrPDU2OutletMeteredStatusPowerFactorread-onlymandatoryThe power factor of the Rack PDU outlet in hundredths. Models that do not support this feature will respond to this OID with a value of -1.
1.3.6.1.4.1.318.1.1.26.10NoderPDU2Sensor
1.3.6.1.4.1.318.1.1.26.10.1ScalarrPDU2SensorTempHumidityTableSizeread-onlymandatoryThe number of connected temperature-humidity sensors
1.3.6.1.4.1.318.1.1.26.10.2NoderPDU2SensorTempHumidity
1.3.6.1.4.1.318.1.1.26.10.2.1TablerPDU2SensorTempHumidityConfigTablenot-accessiblemandatoryA table of temperature-humidity sensor configuration data
1.3.6.1.4.1.318.1.1.26.10.2.1.1RowrPDU2SensorTempHumidityConfigEntrynot-accessiblemandatoryConfiguration data from temperature-humidity sensor being queried
1.3.6.1.4.1.318.1.1.26.10.2.1.1.1ColumnrPDU2SensorTempHumidityConfigIndexread-onlymandatoryThe index to the temperature-humidity sensor configuration data table entry
1.3.6.1.4.1.318.1.1.26.10.2.1.1.2ColumnrPDU2SensorTempHumidityConfigModuleread-onlymandatoryThe user-defined Rack PDU numeric ID
1.3.6.1.4.1.318.1.1.26.10.2.1.1.3ColumnrPDU2SensorTempHumidityConfigNameread-writemandatoryThe user-defined temperature-humidity sensor ID string
1.3.6.1.4.1.318.1.1.26.10.2.1.1.4ColumnrPDU2SensorTempHumidityConfigNumberread-onlymandatoryThe temperature-humidity sensor numeric ID
1.3.6.1.4.1.318.1.1.26.10.2.1.1.5ColumnrPDU2SensorTempHumidityConfigTemperatureAlarmEnableread-writemandatorySetting this OID enables or disables generation of sensor temperature alarm. Getting this OID returns the current value of the temperature alarm enable.
1.3.6.1.4.1.318.1.1.26.10.2.1.1.6ColumnrPDU2SensorTempHumidityConfigHumidityAlarmEnableread-writemandatorySetting this OID enables or disables generation of sensor humidity alarm. Getting this OID returns the current value of the humidity alarm enable.
1.3.6.1.4.1.318.1.1.26.10.2.1.1.7ColumnrPDU2SensorTempHumidityConfigTempMaxThreshFread-writemandatorySensor maximum temperature alarm threshold in Fahrenheit. Attempting to set this OID to a value less than or equal to that of rPDU2SensorTempHumidityConfigTemp…
1.3.6.1.4.1.318.1.1.26.10.2.1.1.8ColumnrPDU2SensorTempHumidityConfigTempHighThreshFread-writemandatorySensor high temperature warning alarm threshold in Fahrenheit. Attempting to set this OID to a value greater than or equal to that of rPDU2SensorTempHumidityCo…
1.3.6.1.4.1.318.1.1.26.10.2.1.1.9ColumnrPDU2SensorTempHumidityConfigTempHysteresisFread-writemandatorySensor temperature hysteresis setting in Fahrenheit
1.3.6.1.4.1.318.1.1.26.10.2.1.1.10ColumnrPDU2SensorTempHumidityConfigTempMaxThreshCread-writemandatorySensor maximum temperature alarm threshold in Celsius. Attempting to set this OID to a value less than or equal to that of rPDU2SensorTempHumidityConfigTempHig…
1.3.6.1.4.1.318.1.1.26.10.2.1.1.11ColumnrPDU2SensorTempHumidityConfigTempHighThreshCread-writemandatorySensor high temperature warning alarm threshold in Celsius. Attempting to set this OID to a value greater than or equal to that of rPDU2SensorTempHumidityConfi…
1.3.6.1.4.1.318.1.1.26.10.2.1.1.12ColumnrPDU2SensorTempHumidityConfigTempHysteresisCread-writemandatorySensor temperature hysteresis setting in Celsius
1.3.6.1.4.1.318.1.1.26.10.2.1.1.13ColumnrPDU2SensorTempHumidityConfigHumidityLowThreshread-writemandatorySensor low humidity warning alarm threshold in percent relative humidity. Attempting to set this OID to a value less than or equal to that of rPDU2SensorTempHu…
1.3.6.1.4.1.318.1.1.26.10.2.1.1.14ColumnrPDU2SensorTempHumidityConfigHumidityMinThreshread-writemandatorySensor minimum humidity alarm threshold in percent relative humidity. Attempting to set this OID to a value greater than or equal to that of rPDU2SensorTempHum…
1.3.6.1.4.1.318.1.1.26.10.2.1.1.15ColumnrPDU2SensorTempHumidityConfigHumidityHysteresisread-writemandatorySensor humidity hysteresis setting in percent relative humidity
1.3.6.1.4.1.318.1.1.26.10.2.1.1.16ColumnrPDU2SensorTempHumidityConfigTempPeakResetread-writemandatorySetting this OID to reset (2) will cause the existing peak temperature to be replaced by the present temperature reading. Getting this OID will do nothing and …
1.3.6.1.4.1.318.1.1.26.10.2.2TablerPDU2SensorTempHumidityStatusTablenot-accessiblemandatoryA table of temperature-humidity sensor status data
1.3.6.1.4.1.318.1.1.26.10.2.2.1RowrPDU2SensorTempHumidityStatusEntrynot-accessiblemandatoryStatus information from temperature-humidity sensor being queried
1.3.6.1.4.1.318.1.1.26.10.2.2.1.1ColumnrPDU2SensorTempHumidityStatusIndexread-onlymandatoryThe index to the temperature-humidity status data table entry
1.3.6.1.4.1.318.1.1.26.10.2.2.1.2ColumnrPDU2SensorTempHumidityStatusModuleread-onlymandatoryThe user-defined Rack PDU numeric ID
1.3.6.1.4.1.318.1.1.26.10.2.2.1.3ColumnrPDU2SensorTempHumidityStatusNameread-onlymandatoryThe user-defined temperature-humidity sensor ID string
1.3.6.1.4.1.318.1.1.26.10.2.2.1.4ColumnrPDU2SensorTempHumidityStatusNumberread-onlymandatoryThe temperature-humidity sensor numeric ID
1.3.6.1.4.1.318.1.1.26.10.2.2.1.5ColumnrPDU2SensorTempHumidityStatusTyperead-onlymandatoryThe type of the sensor
1.3.6.1.4.1.318.1.1.26.10.2.2.1.6ColumnrPDU2SensorTempHumidityStatusCommStatusread-onlymandatoryThe communications status of the sensor
1.3.6.1.4.1.318.1.1.26.10.2.2.1.7ColumnrPDU2SensorTempHumidityStatusTempFread-onlymandatorySensor temperature reading in tenths of degrees Fahrenheit
1.3.6.1.4.1.318.1.1.26.10.2.2.1.8ColumnrPDU2SensorTempHumidityStatusTempCread-onlymandatorySensor temperature reading in tenths of degrees Celsius
1.3.6.1.4.1.318.1.1.26.10.2.2.1.9ColumnrPDU2SensorTempHumidityStatusTempStatusread-onlymandatoryThis OID reports the current state of the temperature probe. A notPresent (1) response indicates that no probe is attached. A belowMin (2) response indicates t…
1.3.6.1.4.1.318.1.1.26.10.2.2.1.10ColumnrPDU2SensorTempHumidityStatusRelativeHumidityread-onlymandatorySensor humidity reading in percent relative humidity
1.3.6.1.4.1.318.1.1.26.10.2.2.1.11ColumnrPDU2SensorTempHumidityStatusHumidityStatusread-onlymandatoryThis OID reports the current state of the humidity probe. A notPresent (1) response indicates that no probe is attached. A belowMin (2) response indicates that…
1.3.6.1.4.1.318.1.1.26.10.2.2.1.12ColumnrPDU2SensorTempHumidityStatusTempPeakFread-onlymandatorySensor peak temperature in tenths of degrees Fahrenheit
1.3.6.1.4.1.318.1.1.26.10.2.2.1.13ColumnrPDU2SensorTempHumidityStatusTempPeakCread-onlymandatorySensor peak temperature in tenths of degrees Celsius
1.3.6.1.4.1.318.1.1.26.10.2.2.1.14ColumnrPDU2SensorTempHumidityStatusTempPeakTimestampread-onlymandatoryIndicates the date and time that the peak temperature occurred
1.3.6.1.4.1.318.1.1.26.10.2.2.1.15ColumnrPDU2SensorTempHumidityStatusTempPeakStartTimeread-onlymandatoryIndicates the date and time of the last temperature peak reset
1.3.6.1.4.1.318.1.1.26.10.3ScalarrPDU2SensorDiscreteTableSizeread-onlymandatoryThe number of connected discrete sensors
1.3.6.1.4.1.318.1.1.26.10.4NoderPDU2SensorDiscrete
1.3.6.1.4.1.318.1.1.26.10.4.1TablerPDU2SensorDiscreteConfigTablenot-accessiblemandatoryA table of discrete sensor configuration data
1.3.6.1.4.1.318.1.1.26.10.4.1.1RowrPDU2SensorDiscreteConfigEntrynot-accessiblemandatoryConfiguration data from discreste sensor being queried
1.3.6.1.4.1.318.1.1.26.10.4.1.1.1ColumnrPDU2SensorDiscreteConfigIndexread-onlymandatoryThe index to the discrete sensor configuration data table entry
1.3.6.1.4.1.318.1.1.26.10.4.1.1.2ColumnrPDU2SensorDiscreteConfigModuleread-onlymandatoryThe user-defined Rack PDU numeric ID
1.3.6.1.4.1.318.1.1.26.10.4.1.1.3ColumnrPDU2SensorDiscreteConfigNameread-writemandatoryThe user-defined discrete sensor ID string
1.3.6.1.4.1.318.1.1.26.10.4.1.1.4ColumnrPDU2SensorDiscreteConfigNumberread-onlymandatoryThe discrete sensor numeric ID
1.3.6.1.4.1.318.1.1.26.10.4.1.1.5ColumnrPDU2SensorDiscreteConfigNormalStateread-writemandatoryIndicates the normal state of the discrete input contact
1.3.6.1.4.1.318.1.1.26.10.4.1.1.6ColumnrPDU2SensorDiscreteConfigAbnormalSeverityread-writemandatoryIndicates the severity of alarm triggered by abnormal discrete input contact state
1.3.6.1.4.1.318.1.1.26.10.4.2TablerPDU2SensorDiscreteStatusTablenot-accessiblemandatoryA table of discrete sensor status data
1.3.6.1.4.1.318.1.1.26.10.4.2.1RowrPDU2SensorDiscreteStatusEntrynot-accessiblemandatoryStatus information from discrete sensor being queried
1.3.6.1.4.1.318.1.1.26.10.4.2.1.1ColumnrPDU2SensorDiscreteStatusIndexread-onlymandatoryThe index to the discrete sensor status data table entry
1.3.6.1.4.1.318.1.1.26.10.4.2.1.2ColumnrPDU2SensorDiscreteStatusModuleread-onlymandatoryThe user-defined Rack PDU numeric ID
1.3.6.1.4.1.318.1.1.26.10.4.2.1.3ColumnrPDU2SensorDiscreteStatusNameread-onlymandatoryThe user-defined discrete sensor ID string
1.3.6.1.4.1.318.1.1.26.10.4.2.1.4ColumnrPDU2SensorDiscreteStatusNumberread-onlymandatoryThe discrete sensor numeric ID
1.3.6.1.4.1.318.1.1.26.10.4.2.1.5ColumnrPDU2SensorDiscreteStatusTyperead-onlymandatoryThe type of discrete sensor currently being queried
1.3.6.1.4.1.318.1.1.26.10.4.2.1.6ColumnrPDU2SensorDiscreteStatusCommStatusread-onlymandatoryThe communications status of the sensor
1.3.6.1.4.1.318.1.1.26.10.4.2.1.7ColumnrPDU2SensorDiscreteStatusCurrentStateread-onlymandatoryThe current open/close state of the discrete sensor
1.3.6.1.4.1.318.1.1.26.10.4.2.1.8ColumnrPDU2SensorDiscreteStatusAlarmStateread-onlymandatoryIndicates alarm status of discrete sensor input
1.3.6.1.4.1.318.1.1.26.11NoderPDU2Group
1.3.6.1.4.1.318.1.1.26.11.1ScalarrPDU2GroupNumberOfDevicesread-onlymandatoryGetting this OID will return the number of Rack PDU devices contributing to the Network Port Sharing (NPS) group power and energy values. Queries to guest unit…
1.3.6.1.4.1.318.1.1.26.11.2ScalarrPDU2GroupTotalPowerread-onlymandatoryGetting this OID will return the total power consumption of the Rack PDU Network Port Sharing (NPS) group devices in hundredths of kilowatts. Queries to guest …
1.3.6.1.4.1.318.1.1.26.11.3ScalarrPDU2GroupTotalEnergyread-onlymandatoryGetting this OID will return the total energy consumption of the Rack PDU Network Port Sharing (NPS) group devices in tenths of kilowatt-hours. To reset the en…
1.3.6.1.4.1.318.1.1.26.11.4ScalarrPDU2GroupEnergyResetread-writemandatorySetting this OID to reset (2) will cause the device energy meter value on each device in the Rack PDU Network Port Sharing (NPS) group to be reset to zero. Eac…
1.3.6.1.4.1.318.1.1.26.12ScalarrPDU2PhaseToPhaseStatusTableSizeread-onlymandatoryThe number of connected Rack PDU banks
1.3.6.1.4.1.318.1.1.26.13NoderPDU2PhaseToPhase
1.3.6.1.4.1.318.1.1.26.13.1TablerPDU2PhaseToPhaseStatusTablenot-accessiblemandatoryA table of Rack PDU phase to phase status data. This table is only applicable to SKUs that have phase to phase outputs.
1.3.6.1.4.1.318.1.1.26.13.1.1RowrPDU2PhaseToPhaseStatusEntrynot-accessiblemandatoryStatus data from currently queried Rack PDU phase to phase outputs
1.3.6.1.4.1.318.1.1.26.13.1.1.1ColumnrPDU2PhaseToPhaseStatusIndexread-onlymandatoryThe index to the Rack PDU phase to phase status table entry
1.3.6.1.4.1.318.1.1.26.13.1.1.2ColumnrPDU2PhaseToPhaseStatusModuleread-onlymandatoryThe user-defined Rack PDU numeric ID
1.3.6.1.4.1.318.1.1.26.13.1.1.3ColumnrPDU2PhaseToPhaseStatusVoltage1to2read-onlymandatoryIndicates the Voltage, in Volts, of the Rack PDU phase 1 to phase 2 output being queried
1.3.6.1.4.1.318.1.1.26.13.1.1.4ColumnrPDU2PhaseToPhaseStatusVoltage2to3read-onlymandatoryIndicates the Voltage, in Volts, of the Rack PDU phase 2 to phase 3 output being queried
1.3.6.1.4.1.318.1.1.26.13.1.1.5ColumnrPDU2PhaseToPhaseStatusVoltage3to1read-onlymandatoryIndicates the Voltage, in Volts, of the Rack PDU phase 3 to phase 2 output being queried
1.3.6.1.4.1.318.1.1.26.14ScalarrPDU2RCMTableSizeread-onlymandatoryThe number of RCM
1.3.6.1.4.1.318.1.1.26.15NoderPDU2RCM
1.3.6.1.4.1.318.1.1.26.15.1TablerPDU2RCMTablenot-accessiblemandatoryA table of Rack PDU RCM.
1.3.6.1.4.1.318.1.1.26.15.1.1RowrPDU2RCMEntrynot-accessiblemandatoryRCM data from currently queried Rack PDU
1.3.6.1.4.1.318.1.1.26.15.1.1.1ColumnrPDU2RCMIndexread-onlymandatoryThe index to the Rack PDU RCM table entry
1.3.6.1.4.1.318.1.1.26.15.1.1.2ColumnrPDU2RCMModuleread-onlymandatoryThe user-defined Rack PDU numeric ID
1.3.6.1.4.1.318.1.1.26.15.1.1.3ColumnrPDU2RCMCurrentread-onlymandatoryRCM RMS current. (mA)
1.3.6.1.4.1.318.1.1.26.15.1.1.4ColumnrPDU2RCMAlarmStatusread-writemandatoryRCM alarm status. Setting the selected variable to 1, will clear the over alarm.
1.3.6.1.4.1.318.1.1.26.15.1.1.5ColumnrPDU2RCMSelfCheckCommandread-writemandatoryGetting this variable will return the RCM self checking status, 1: featureNotAvailable(-1) 2: success(1) 3: failed(2) 4: pending(3). Setting any of the selecte…
1.3.6.1.4.1.318.1.1.26.15.1.1.6ColumnrPDU2RCMWarningThresholdread-writemandatoryOver Warning threshold of RCM current. (mA), threshold can be set in the range of 15-300mA, and must be lower or equal than Alarm threshold.
1.3.6.1.4.1.318.1.1.26.15.1.1.7ColumnrPDU2RCMAlarmThresholdread-writemandatoryOver Alarm threshold of RCM current. (mA), threshold can be set in the range of 15~300 mA, and must be higher or equal than Warning threshold.
1.3.6.1.4.1.318.1.1.26.15.1.1.8ColumnrPDU2RCMSelfCheckPeriodread-writemandatoryRCM Self-Checking Period. (day) period can be set in the range of 1~365 days, the rcm period on a single pdu is the same, setting one of the selected pdu's rcm…
1.3.6.1.4.1.318.1.2Nodesoftware
1.3.6.1.4.1.318.1.2.1NodepowerNetSubAgent
1.3.6.1.4.1.318.1.2.1.1NodepowerNetSoftwareSystem
1.3.6.1.4.1.318.1.2.1.1.1ScalarpowerNetSoftwareSystemDescriptionread-onlymandatoryA brief description of the PowerNet sub-agent.
1.3.6.1.4.1.318.1.2.1.1.2ScalarpowerNetSoftwareOidread-onlymandatoryThe object identifier of the PowerNet sub-agent.
1.3.6.1.4.1.318.1.2.1.1.3ScalarpowerNetSoftwareSystemUpTimeread-onlymandatoryThe time that the sub-agent has been running.
1.3.6.1.4.1.318.1.2.1.2NodepowerNetSoftwareConfig
1.3.6.1.4.1.318.1.2.1.2.1ScalarpowerNetSoftwareTableSizeread-onlymandatoryThe number of software modules supporting the UPS.
1.3.6.1.4.1.318.1.2.1.2.2TablepowerNetSoftwareTablenot-accessiblemandatoryA list of the software monitoring the UPS.
1.3.6.1.4.1.318.1.2.1.2.2.1RowpowerNetSoftwareEntrynot-accessiblemandatoryAn entry containing information on a software module.
1.3.6.1.4.1.318.1.2.1.2.2.1.1ColumnmoduleNumberread-onlymandatoryThe index into the Software Entry Table
1.3.6.1.4.1.318.1.2.1.2.2.1.2ColumnmoduleNameread-onlymandatoryThe name of the software module.
1.3.6.1.4.1.318.1.2.1.2.2.1.3ColumnmoduleVersionread-onlymandatoryThe version of the software module.
1.3.6.1.4.1.318.1.2.1.2.2.1.4ColumnmoduleDateread-onlymandatoryThe date of the software module represented as mm-dd-yy.
1.3.6.1.4.1.318.1.2.2NodestruxureWareOperations
1.3.6.1.4.1.318.1.2.2.1NodestruxureWareOperationsStatus
1.3.6.1.4.1.318.1.2.2.1.1ScalarserverStatusread-onlymandatoryThe status of the StruxureWare Operations server: 1: The status of the application server is unknown. Check Webmin and if the problem persists, contact Technic…
1.3.6.1.4.1.318.1.2.2.1.2ScalardatabaseStatusread-onlymandatoryThe status of the StruxureWare Operations database: 1: The status of the database is unknown. Check Webmin and if the problem persists, contact Technical Suppo…
1.3.6.1.4.1.318.1.2.2.1.3ScalarloadBalancerStatusread-onlymandatoryThe status of the StruxureWare Operations load balancer: 1: Load Balancer status is unknown. Check Webmin and if the problem persists, contact Technical Suppor…
1.3.6.1.4.1.318.1.2.2.1.4ScalaressentialServicesStatusread-onlymandatoryThe status of the StruxureWare Operations essential services: 1: Unknown status. Check Webmin and if the problem persists, contact Technical Support. 2: Essent…
1.3.6.1.4.1.318.1.2.2.1.5ScalaretlStatusread-onlymandatoryThe status of the StruxureWare Operations ETL services: 1: Unknown status. Check the network configuration and the server network settings. 2: Normal status, 3…
1.3.6.1.4.1.318.1.2.3NodepowerChuteNetworkShutdown
1.3.6.1.4.1.318.1.2.3.1NodepcnsIdent
1.3.6.1.4.1.318.1.2.3.1.1Scalarpcnshostnameread-onlymandatoryThe hostname of the PCNS instance.
1.3.6.1.4.1.318.1.2.3.1.2ScalarpcnsVersionread-onlymandatoryThe version of PCNS installed. x.x.x
1.3.6.1.4.1.318.1.2.3.1.3ScalarpcnsOSread-onlymandatoryThe version of OS PCNS is Installed on.
1.3.6.1.4.1.318.1.2.3.1.4ScalarpcnsJavaVersionread-onlymandatoryThe version of Java PCNS is running on.
1.3.6.1.4.1.318.1.2.3.2NodepcnsNetworking
1.3.6.1.4.1.318.1.2.3.2.1ScalarpcnsUIProtocolread-onlymandatoryWeb Protocol used to connect to the PCNS UI.
1.3.6.1.4.1.318.1.2.3.2.2ScalarpcnsHttpPortread-onlymandatoryPort used for PCNS http UI.
1.3.6.1.4.1.318.1.2.3.2.3ScalarpcnsHttpsPortread-onlymandatoryPort used for PCNS https UI.
1.3.6.1.4.1.318.1.2.3.2.4ScalarpcnsNetworkConfigread-onlymandatoryConfiguration of the TCP Network.
1.3.6.1.4.1.318.1.2.3.2.5ScalarpcnsVirtualInstallread-onlymandatoryVirtualization technology in use by PCNS.
1.3.6.1.4.1.318.1.2.3.3NodepcnsNMC
1.3.6.1.4.1.318.1.2.3.3.1ScalarpcnsModeread-onlymandatoryConfiguration mode of the UPS(s) which PCNS is monitoring.
1.3.6.1.4.1.318.1.2.3.3.2ScalarpcnsNMCPortread-onlymandatoryPort used to connect to all of the Network Management Card(s).
1.3.6.1.4.1.318.1.2.3.3.3ScalarpcnsNMCProtocolread-onlymandatoryWeb Protocol used to connect to all of the Network Management Card(s).
1.3.6.1.4.1.318.1.2.3.3.4TablepcnsNmcTablenot-accessiblemandatoryThe Network Management Cards in the UPS's which PCNS is monitoring to provide safe shutdown.
1.3.6.1.4.1.318.1.2.3.3.4.1RowpcnsNmcEntrynot-accessiblemandatoryDetails of the NMC.
1.3.6.1.4.1.318.1.2.3.3.4.1.1ColumnpcnsNmcIndexread-onlymandatoryIndex of the NMC within PCNS setup.
1.3.6.1.4.1.318.1.2.3.3.4.1.2ColumnpcnsNmcAddrread-onlymandatoryThe IP address of the NMC.
1.3.6.1.4.1.318.1.2.3.3.4.1.3ColumnpcnsNmcOutletread-onlymandatoryThe Outlet Group which PCNS is enrolled with on the NMC.
1.3.6.1.4.1.318.1.2.3.4NodepcnsEvents
1.3.6.1.4.1.318.1.2.3.4.1NodepcnsPowerFailed
1.3.6.1.4.1.318.1.2.3.4.1.1ScalarpcnsPowerFailedDescread-onlymandatoryThe Description of the event.
1.3.6.1.4.1.318.1.2.3.4.1.2ScalarpcnsPowerFailedEnableLoggingread-writemandatoryLog occurrences of this event in PCNS log.
1.3.6.1.4.1.318.1.2.3.4.1.3ScalarpcnsPowerFailedEnableCommandFileread-writemandatoryExecute a command file when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.1.4ScalarpcnsPowerFailedCommandFilePathread-writemandatoryPath of command file to execute when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.1.5ScalarpcnsPowerFailedCommandFileDelayread-writemandatoryHow long to wait after event occurs before executing command file (seconds).
1.3.6.1.4.1.318.1.2.3.4.1.6ScalarpcnsPowerFailedEnableShutdownread-writemandatoryPerform a graceful shutdown of the server when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.1.7ScalarpcnsPowerFailedShutdownDelayread-writemandatoryHow long to wait after event occurs before performing a graceful shutdown of the server (seconds).
1.3.6.1.4.1.318.1.2.3.4.2NodepcnsPowerRestored
1.3.6.1.4.1.318.1.2.3.4.2.1ScalarpcnsPowerRestoredDescread-onlymandatoryThe Description of the event.
1.3.6.1.4.1.318.1.2.3.4.2.2ScalarpcnsPowerRestoredEnableLoggingread-writemandatoryLog occurrences of this event in PCNS log.
1.3.6.1.4.1.318.1.2.3.4.2.3ScalarpcnsPowerRestoredEnableCommandFileread-writemandatoryExecute a command file when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.2.4ScalarpcnsPowerRestoredCommandFilePathread-writemandatoryPath of command file to execute when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.2.5ScalarpcnsPowerRestoredCommandFileDelayread-writemandatoryHow long to wait after event occurs before executing command file (seconds).
1.3.6.1.4.1.318.1.2.3.4.3NodepcnsOverload
1.3.6.1.4.1.318.1.2.3.4.3.1ScalarpcnsOverloadDescread-onlymandatoryThe Description of the event.
1.3.6.1.4.1.318.1.2.3.4.3.2ScalarpcnsOverloadEnableLoggingread-writemandatoryLog occurrences of this event in PCNS log.
1.3.6.1.4.1.318.1.2.3.4.3.3ScalarpcnsOverloadEnableCommandFileread-writemandatoryExecute a command file when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.3.4ScalarpcnsOverloadCommandFilePathread-writemandatoryPath of command file to execute when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.3.5ScalarpcnsOverloadCommandFileDelayread-writemandatoryHow long to wait after event occurs before executing command file (seconds).
1.3.6.1.4.1.318.1.2.3.4.3.6ScalarpcnsOverloadEnableShutdownread-writemandatoryPerform a graceful shutdown of the server when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.3.7ScalarpcnsOverloadShutdownDelayread-writemandatoryHow long to wait after event occurs before performing a graceful shutdown of the server (seconds).
1.3.6.1.4.1.318.1.2.3.4.4NodepcnsOverloadSolved
1.3.6.1.4.1.318.1.2.3.4.4.1ScalarpcnsOverloadSolvedDescread-onlymandatoryThe Description of the event.
1.3.6.1.4.1.318.1.2.3.4.4.2ScalarpcnsOverloadSolvedEnableLoggingread-writemandatoryLog occurrences of this event in PCNS log.
1.3.6.1.4.1.318.1.2.3.4.4.3ScalarpcnsOverloadSolvedEnableCommandFileread-writemandatoryExecute a command file when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.4.4ScalarpcnsOverloadSolvedCommandFilePathread-writemandatoryPath of command file to execute when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.4.5ScalarpcnsOverloadSolvedCommandFileDelayread-writemandatoryHow long to wait after event occurs before executing command file (seconds).
1.3.6.1.4.1.318.1.2.3.4.5NodepcnsRunTimeExceeded
1.3.6.1.4.1.318.1.2.3.4.5.1ScalarpcnsRunTimeExceededDescread-onlymandatoryThe Description of the event.
1.3.6.1.4.1.318.1.2.3.4.5.2ScalarpcnsRunTimeExceededEnableLoggingread-writemandatoryLog occurrences of this event in PCNS log.
1.3.6.1.4.1.318.1.2.3.4.5.3ScalarpcnsRunTimeExceededEnableCommandFileread-writemandatoryExecute a command file when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.5.4ScalarpcnsRunTimeExceededCommandFilePathread-writemandatoryPath of command file to execute when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.5.5ScalarpcnsRunTimeExceededCommandFileDelayread-writemandatoryHow long to wait after event occurs before executing command file (seconds).
1.3.6.1.4.1.318.1.2.3.4.5.6ScalarpcnsRunTimeExceededEnableShutdownread-writemandatoryPerform a graceful shutdown of the server when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.5.7ScalarpcnsRunTimeExceededShutdownDelayread-writemandatoryHow long to wait after event occurs before performing a graceful shutdown of the server (seconds).
1.3.6.1.4.1.318.1.2.3.4.6NodepcnsRunTimeWithinRange
1.3.6.1.4.1.318.1.2.3.4.6.1ScalarpcnsRunTimeWithinRangeDescread-onlymandatoryThe Description of the event.
1.3.6.1.4.1.318.1.2.3.4.6.2ScalarpcnsRunTimeWithinRangeEnableLoggingread-writemandatoryLog occurrences of this event in PCNS log.
1.3.6.1.4.1.318.1.2.3.4.6.3ScalarpcnsRunTimeWithinRangeEnableCommandFileread-writemandatoryExecute a command file when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.6.4ScalarpcnsRunTimeWithinRangeCommandFilePathread-writemandatoryPath of command file to execute when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.6.5ScalarpcnsRunTimeWithinRangeCommandFileDelayread-writemandatoryHow long to wait after event occurs before executing command file (seconds).
1.3.6.1.4.1.318.1.2.3.4.7NodepcnsRunTimeBelowThreshold
1.3.6.1.4.1.318.1.2.3.4.7.1ScalarpcnsRunTimeBelowThresholdDescread-onlymandatoryThe Description of the event.
1.3.6.1.4.1.318.1.2.3.4.7.2ScalarpcnspcnsRunTimeBelowThresholdEnableLoggingread-writemandatoryLog occurrences of this event in PCNS log.
1.3.6.1.4.1.318.1.2.3.4.7.3ScalarpcnsRunTimeBelowThresholdEnableCommandFileread-writemandatoryExecute a command file when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.7.4ScalarpcnsRunTimeBelowThresholdCommandFilePathread-writemandatoryPath of command file to execute when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.7.6ScalarpcnsRunTimeBelowThresholdEnableShutdownread-writemandatoryPerform a graceful shutdown of the server when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.7.8ScalarpcnsRunTimeBelowThresholdCommandFileThresholdread-writemandatoryIf the Runtime Remaining falls below this (seconds), the command file will run.
1.3.6.1.4.1.318.1.2.3.4.7.9ScalarpcnsRunTimeBelowThresholdShutdownThresholdread-writemandatoryIf the Runtime Remaining falls below this (seconds), the shutdown will begin.
1.3.6.1.4.1.318.1.2.3.4.8NodepcnsRunTimeAboveThreshold
1.3.6.1.4.1.318.1.2.3.4.8.1ScalarpcnsRunTimeAboveThresholdDescread-onlymandatoryThe Description of the event.
1.3.6.1.4.1.318.1.2.3.4.8.2ScalarpcnsRunTimeAboveThresholdEnableLoggingread-writemandatoryLog occurrences of this event in PCNS log.
1.3.6.1.4.1.318.1.2.3.4.8.3ScalarpcnsRunTimeAboveThresholdEnableCommandFileread-writemandatoryExecute a command file when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.8.4ScalarpcnsRunTimeAboveThresholdCommandFilePathread-writemandatoryPath of command file to execute when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.8.5ScalarpcnsRunTimeAboveThresholdCommandFileDelayread-writemandatoryHow long to wait after event occurs before executing command file (seconds).
1.3.6.1.4.1.318.1.2.3.4.10NodepcnsBatteryDischarged
1.3.6.1.4.1.318.1.2.3.4.10.1ScalarpcnsBatteryDischargedDescread-onlymandatoryThe Description of the event.
1.3.6.1.4.1.318.1.2.3.4.10.2ScalarpcnsBatteryDischargedEnableLoggingread-writemandatoryLog occurrences of this event in PCNS log.
1.3.6.1.4.1.318.1.2.3.4.10.3ScalarpcnsBatteryDischargedEnableCommandFileread-writemandatoryExecute a command file when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.10.4ScalarpcnsBatteryDischargedCommandFilePathread-writemandatoryPath of command file to execute when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.10.5ScalarpcnsBatteryDischargedCommandFileDelayread-writemandatoryHow long to wait after event occurs before executing command file (seconds).
1.3.6.1.4.1.318.1.2.3.4.10.6ScalarpcnsBatteryDischargedEnableShutdownread-writemandatoryPerform a graceful shutdown of the server when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.10.7ScalarpcnsBatteryDischargedShutdownDelayread-writemandatoryHow long to wait after event occurs before performing a graceful shutdown of the server (seconds).
1.3.6.1.4.1.318.1.2.3.4.11NodepcnsBatteryChargeInRange
1.3.6.1.4.1.318.1.2.3.4.11.1ScalarpcnsBatteryChargeInRangeDescread-onlymandatoryThe Description of the event.
1.3.6.1.4.1.318.1.2.3.4.11.2ScalarpcnsBatteryChargeInRangeEnableLoggingread-writemandatoryLog occurrences of this event in PCNS log.
1.3.6.1.4.1.318.1.2.3.4.11.3ScalarpcnsBatteryChargeInRangeEnableCommandFileread-writemandatoryExecute a command file when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.11.4ScalarpcnsBatteryChargeInRangeCommandFilePathread-writemandatoryPath of command file to execute when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.11.5ScalarpcnsBatteryChargeInRangeCommandFileDelayread-writemandatoryHow long to wait after event occurs before executing command file (seconds).
1.3.6.1.4.1.318.1.2.3.4.12NodepcnsFaultBypassEnabled
1.3.6.1.4.1.318.1.2.3.4.12.1ScalarpcnsFaultBypassEnabledDescread-onlymandatoryThe Description of the event.
1.3.6.1.4.1.318.1.2.3.4.12.2ScalarpcnsFaultBypassEnabledEnableLoggingread-writemandatoryLog occurrences of this event in PCNS log.
1.3.6.1.4.1.318.1.2.3.4.12.3ScalarpcnsFaultBypassEnabledEnableCommandFileread-writemandatoryExecute a command file when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.12.4ScalarpcnsFaultBypassEnabledCommandFilePathread-writemandatoryPath of command file to execute when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.12.5ScalarpcnsFaultBypassEnabledCommandFileDelayread-writemandatoryHow long to wait after event occurs before executing command file (seconds).
1.3.6.1.4.1.318.1.2.3.4.12.6ScalarpcnsFaultBypassEnabledEnableShutdownread-writemandatoryPerform a graceful shutdown of the server when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.12.7ScalarpcnsFaultBypassEnabledShutdownDelayread-writemandatoryHow long to wait after event occurs before performing a graceful shutdown of the server (seconds).
1.3.6.1.4.1.318.1.2.3.4.13NodepcnsBypassEnabled
1.3.6.1.4.1.318.1.2.3.4.13.1ScalarpcnsBypassEnabledDescread-onlymandatoryThe Description of the event.
1.3.6.1.4.1.318.1.2.3.4.13.2ScalarpcnsBypassEnabledEnableLoggingread-writemandatoryLog occurrences of this event in PCNS log.
1.3.6.1.4.1.318.1.2.3.4.13.3ScalarpcnsBypassEnabledEnableCommandFileread-writemandatoryExecute a command file when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.13.4ScalarpcnsBypassEnabledCommandFilePathread-writemandatoryPath of command file to execute when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.13.5ScalarpcnsBypassEnabledCommandFileDelayread-writemandatoryHow long to wait after event occurs before executing command file (seconds).
1.3.6.1.4.1.318.1.2.3.4.13.6ScalarpcnsBypassEnabledEnableShutdownread-writemandatoryPerform a graceful shutdown of the server when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.13.7ScalarpcnsBypassEnabledShutdownDelayread-writemandatoryHow long to wait after event occurs before performing a graceful shutdown of the server (seconds).
1.3.6.1.4.1.318.1.2.3.4.14NodepcnsBypassManualEnabled
1.3.6.1.4.1.318.1.2.3.4.14.1ScalarpcnsBypassManualEnabledDescread-onlymandatoryThe Description of the event.
1.3.6.1.4.1.318.1.2.3.4.14.2ScalarpcnsBypassManualEnabledEnableLoggingread-writemandatoryLog occurrences of this event in PCNS log.
1.3.6.1.4.1.318.1.2.3.4.14.3ScalarpcnsBypassManualEnabledEnableCommandFileread-writemandatoryExecute a command file when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.14.4ScalarpcnsBypassManualEnabledCommandFilePathread-writemandatoryPath of command file to execute when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.14.5ScalarpcnsBypassManualEnabledCommandFileDelayread-writemandatoryHow long to wait after event occurs before executing command file (seconds).
1.3.6.1.4.1.318.1.2.3.4.14.6ScalarpcnsBypassManualEnabledEnableShutdownread-writemandatoryPerform a graceful shutdown of the server when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.14.7ScalarpcnsBypassManualEnabledShutdownDelayread-writemandatoryHow long to wait after event occurs before performing a graceful shutdown of the server (seconds).
1.3.6.1.4.1.318.1.2.3.4.15NodepcnsBypassDisabled
1.3.6.1.4.1.318.1.2.3.4.15.1ScalarpcnsBypassDisabledDescread-onlymandatoryThe Description of the event.
1.3.6.1.4.1.318.1.2.3.4.15.2ScalarpcnsBypassDisabledEnableLoggingread-writemandatoryLog occurrences of this event in PCNS log.
1.3.6.1.4.1.318.1.2.3.4.15.3ScalarpcnsBypassDisabledEnableCommandFileread-writemandatoryExecute a command file when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.15.4ScalarpcnsBypassDisabledCommandFilePathread-writemandatoryPath of command file to execute when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.15.5ScalarpcnsBypassDisabledCommandFileDelayread-writemandatoryHow long to wait after event occurs before executing command file (seconds).
1.3.6.1.4.1.318.1.2.3.4.16NodepcnsBypassContactorFailed
1.3.6.1.4.1.318.1.2.3.4.16.1ScalarpcnsBypassContactorFailedDescread-onlymandatoryThe Description of the event.
1.3.6.1.4.1.318.1.2.3.4.16.2ScalarpcnsBypassContactorFailedEnableLoggingread-writemandatoryLog occurrences of this event in PCNS log.
1.3.6.1.4.1.318.1.2.3.4.16.3ScalarpcnsBypassContactorFailedEnableCommandFileread-writemandatoryExecute a command file when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.16.4ScalarpcnsBypassContactorFailedCommandFilePathread-writemandatoryPath of command file to execute when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.16.5ScalarpcnsBypassContactorFailedCommandFileDelayread-writemandatoryHow long to wait after event occurs before executing command file (seconds).
1.3.6.1.4.1.318.1.2.3.4.16.6ScalarpcnsBypassContactorFailedEnableShutdownread-writemandatoryPerform a graceful shutdown of the server when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.16.7ScalarpcnsBypassContactorFailedShutdownDelayread-writemandatoryHow long to wait after event occurs before performing a graceful shutdown of the server (seconds).
1.3.6.1.4.1.318.1.2.3.4.17NodepcnsBypassContactorOk
1.3.6.1.4.1.318.1.2.3.4.17.1ScalarpcnsBypassContactorOkDescread-onlymandatoryThe Description of the event.
1.3.6.1.4.1.318.1.2.3.4.17.2ScalarpcnsBypassContactorOkEnableLoggingread-writemandatoryLog occurrences of this event in PCNS log.
1.3.6.1.4.1.318.1.2.3.4.17.3ScalarpcnsBypassContactorOkEnableCommandFileread-writemandatoryExecute a command file when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.17.4ScalarpcnsBypassContactorOkCommandFilePathread-writemandatoryPath of command file to execute when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.17.5ScalarpcnsBypassContactorOkCommandFileDelayread-writemandatoryHow long to wait after event occurs before executing command file (seconds).
1.3.6.1.4.1.318.1.2.3.4.18NodepcnsCommunicationLostOnBattery
1.3.6.1.4.1.318.1.2.3.4.18.1ScalarpcnsCommunicationLostOnBatteryDescread-onlymandatoryThe Description of the event.
1.3.6.1.4.1.318.1.2.3.4.18.2ScalarpcnsCommunicationLostOnBatteryEnableLoggingread-writemandatoryLog occurrences of this event in PCNS log.
1.3.6.1.4.1.318.1.2.3.4.18.3ScalarpcnsCommunicationLostOnBatteryEnableCommandFileread-writemandatoryExecute a command file when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.18.4ScalarpcnsCommunicationLostOnBatteryCommandFilePathread-writemandatoryPath of command file to execute when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.18.5ScalarpcnsCommunicationLostOnBatteryCommandFileDelayread-writemandatoryHow long to wait after event occurs before executing command file (seconds).
1.3.6.1.4.1.318.1.2.3.4.18.6ScalarpcnsCommunicationLostOnBatteryEnableShutdownread-writemandatoryPerform a graceful shutdown of the server when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.18.7ScalarpcnsCommunicationLostOnBatteryShutdownDelayread-writemandatoryHow long to wait after event occurs before performing a graceful shutdown of the server (seconds).
1.3.6.1.4.1.318.1.2.3.4.19NodepcnsCommunicationLost
1.3.6.1.4.1.318.1.2.3.4.19.1ScalarpcnsCommunicationLostDescread-onlymandatoryThe Description of the event.
1.3.6.1.4.1.318.1.2.3.4.19.2ScalarpcnsCommunicationLostEnableLoggingread-writemandatoryLog occurrences of this event in PCNS log.
1.3.6.1.4.1.318.1.2.3.4.19.3ScalarpcnsCommunicationLostEnableCommandFileread-writemandatoryExecute a command file when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.19.4ScalarpcnsCommunicationLostCommandFilePathread-writemandatoryPath of command file to execute when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.19.5ScalarpcnsCommunicationLostCommandFileDelayread-writemandatoryHow long to wait after event occurs before executing command file (seconds).
1.3.6.1.4.1.318.1.2.3.4.19.6ScalarpcnsCommunicationLostEnableShutdownread-writemandatoryPerform a graceful shutdown of the server when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.19.7ScalarpcnsCommunicationLostShutdownDelayread-writemandatoryHow long to wait after event occurs before performing a graceful shutdown of the server (seconds).
1.3.6.1.4.1.318.1.2.3.4.20NodepcnsNetCommunicationLost
1.3.6.1.4.1.318.1.2.3.4.20.1ScalarpcnsNetCommunicationLostDescread-onlymandatoryThe Description of the event.
1.3.6.1.4.1.318.1.2.3.4.20.2ScalarpcnsNetCommunicationLostEnableLoggingread-writemandatoryLog occurrences of this event in PCNS log.
1.3.6.1.4.1.318.1.2.3.4.20.3ScalarpcnsNetCommunicationLostEnableCommandFileread-writemandatoryExecute a command file when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.20.4ScalarpcnsNetCommunicationLostCommandFilePathread-writemandatoryPath of command file to execute when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.20.5ScalarpcnsNetCommunicationLostCommandFileDelayread-writemandatoryHow long to wait after event occurs before executing command file (seconds).
1.3.6.1.4.1.318.1.2.3.4.20.6ScalarpcnsNetCommunicationLostEnableShutdownread-writemandatoryPerform a graceful shutdown of the server when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.20.7ScalarpcnsNetCommunicationLostShutdownDelayread-writemandatoryHow long to wait after event occurs before performing a graceful shutdown of the server (seconds).
1.3.6.1.4.1.318.1.2.3.4.21NodepcnsCommunicationEstablished
1.3.6.1.4.1.318.1.2.3.4.21.1ScalarpcnsCommunicationEstablishedDescread-onlymandatoryThe Description of the event.
1.3.6.1.4.1.318.1.2.3.4.21.2ScalarpcnsCommunicationEstablishedEnableLoggingread-writemandatoryLog occurrences of this event in PCNS log.
1.3.6.1.4.1.318.1.2.3.4.21.3ScalarpcnsCommunicationEstablishedEnableCommandFileread-writemandatoryExecute a command file when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.21.4ScalarpcnsCommunicationEstablishedCommandFilePathread-writemandatoryPath of command file to execute when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.21.5ScalarpcnsCommunicationEstablishedCommandFileDelayread-writemandatoryHow long to wait after event occurs before executing command file (seconds).
1.3.6.1.4.1.318.1.2.3.4.22NodepcnsMinRedundancyLost
1.3.6.1.4.1.318.1.2.3.4.22.1ScalarpcnsMinRedundancyLostDescread-onlymandatoryThe Description of the event.
1.3.6.1.4.1.318.1.2.3.4.22.2ScalarpcnsMinRedundancyLostEnableLoggingread-writemandatoryLog occurrences of this event in PCNS log.
1.3.6.1.4.1.318.1.2.3.4.22.3ScalarpcnsMinRedundancyLostEnableCommandFileread-writemandatoryExecute a command file when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.22.4ScalarpcnsMinRedundancyLostCommandFilePathread-writemandatoryPath of command file to execute when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.22.5ScalarpcnsMinRedundancyLostCommandFileDelayread-writemandatoryHow long to wait after event occurs before executing command file (seconds).
1.3.6.1.4.1.318.1.2.3.4.22.6ScalarpcnsMinRedundancyLostEnableShutdownread-writemandatoryPerform a graceful shutdown of the server when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.22.7ScalarpcnsMinRedundancyLostShutdownDelayread-writemandatoryHow long to wait after event occurs before performing a graceful shutdown of the server (seconds).
1.3.6.1.4.1.318.1.2.3.4.23NodepcnsMinRedundancyRegained
1.3.6.1.4.1.318.1.2.3.4.23.1ScalarpcnsMinRedundancyRegainedDescread-onlymandatoryThe Description of the event.
1.3.6.1.4.1.318.1.2.3.4.23.2ScalarpcnsMinRedundancyRegainedEnableLoggingread-writemandatoryLog occurrences of this event in PCNS log.
1.3.6.1.4.1.318.1.2.3.4.23.3ScalarpcnsMinRedundancyRegainedEnableCommandFileread-writemandatoryExecute a command file when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.23.4ScalarpcnsMinRedundancyRegainedCommandFilePathread-writemandatoryPath of command file to execute when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.23.5ScalarpcnsMinRedundancyRegainedCommandFileDelayread-writemandatoryHow long to wait after event occurs before executing command file (seconds).
1.3.6.1.4.1.318.1.2.3.4.24NodepcnsParallelRedundancyLost
1.3.6.1.4.1.318.1.2.3.4.24.1ScalarpcnsParallelRedundancyLostDescread-onlymandatoryThe Description of the event.
1.3.6.1.4.1.318.1.2.3.4.24.2ScalarpcnsParallelRedundancyLostEnableLoggingread-writemandatoryLog occurrences of this event in PCNS log.
1.3.6.1.4.1.318.1.2.3.4.24.3ScalarpcnsParallelRedundancyLostEnableCommandFileread-writemandatoryExecute a command file when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.24.4ScalarpcnsParallelRedundancyLostCommandFilePathread-writemandatoryPath of command file to execute when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.24.5ScalarpcnsParallelRedundancyLostCommandFileDelayread-writemandatoryHow long to wait after event occurs before executing command file (seconds).
1.3.6.1.4.1.318.1.2.3.4.24.6ScalarpcnsParallelRedundancyLostEnableShutdownread-writemandatoryPerform a graceful shutdown of the server when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.24.7ScalarpcnsParallelRedundancyLostShutdownDelayread-writemandatoryHow long to wait after event occurs before performing a graceful shutdown of the server (seconds).
1.3.6.1.4.1.318.1.2.3.4.25NodepcnsParallelRedundancyRegained
1.3.6.1.4.1.318.1.2.3.4.25.1ScalarpcnsParallelRedundancyRegainedDescread-onlymandatoryThe Description of the event.
1.3.6.1.4.1.318.1.2.3.4.25.2ScalarpcnsParallelRedundancyRegainedEnableLoggingread-writemandatoryLog occurrences of this event in PCNS log.
1.3.6.1.4.1.318.1.2.3.4.25.3ScalarpcnsParallelRedundancyRegainedEnableCommandFileread-writemandatoryExecute a command file when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.25.4ScalarpcnsParallelRedundancyRegainedCommandFilePathread-writemandatoryPath of command file to execute when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.25.5ScalarpcnsParallelRedundancyRegainedCommandFileDelayread-writemandatoryHow long to wait after event occurs before executing command file (seconds).
1.3.6.1.4.1.318.1.2.3.4.26NodepcnsMaxInternalTempExceeded
1.3.6.1.4.1.318.1.2.3.4.26.1ScalarpcnsMaxInternalTempExceededDescread-onlymandatoryThe Description of the event.
1.3.6.1.4.1.318.1.2.3.4.26.2ScalarpcnsMaxInternalTempExceededEnableLoggingread-writemandatoryLog occurrences of this event in PCNS log.
1.3.6.1.4.1.318.1.2.3.4.26.3ScalarpcnsMaxInternalTempExceededEnableCommandFileread-writemandatoryExecute a command file when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.26.4ScalarpcnsMaxInternalTempExceededCommandFilePathread-writemandatoryPath of command file to execute when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.26.5ScalarpcnsMaxInternalTempExceededCommandFileDelayread-writemandatoryHow long to wait after event occurs before executing command file (seconds).
1.3.6.1.4.1.318.1.2.3.4.26.6ScalarpcnsMaxInternalTempExceededEnableShutdownread-writemandatoryPerform a graceful shutdown of the server when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.26.7ScalarpcnsMaxInternalTempExceededShutdownDelayread-writemandatoryHow long to wait after event occurs before performing a graceful shutdown of the server (seconds).
1.3.6.1.4.1.318.1.2.3.4.27NodepcnsMaxInternalTempInRange
1.3.6.1.4.1.318.1.2.3.4.27.1ScalarpcnsMaxInternalTempInRangeDescread-onlymandatoryThe Description of the event.
1.3.6.1.4.1.318.1.2.3.4.27.2ScalarpcnsMaxInternalTempInRangeEnableLoggingread-writemandatoryLog occurrences of this event in PCNS log.
1.3.6.1.4.1.318.1.2.3.4.27.3ScalarpcnsMaxInternalTempInRangeEnableCommandFileread-writemandatoryExecute a command file when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.27.4ScalarpcnsMaxInternalTempInRangeCommandFilePathread-writemandatoryPath of command file to execute when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.27.5ScalarpcnsMaxInternalTempInRangeCommandFileDelayread-writemandatoryHow long to wait after event occurs before executing command file (seconds).
1.3.6.1.4.1.318.1.2.3.4.28NodepcnsMinLoadCapabilityLost
1.3.6.1.4.1.318.1.2.3.4.28.1ScalarpcnsMinLoadCapabilityLostDescread-onlymandatoryThe Description of the event.
1.3.6.1.4.1.318.1.2.3.4.28.2ScalarpcnsMinLoadCapabilityLostEnableLoggingread-writemandatoryLog occurrences of this event in PCNS log.
1.3.6.1.4.1.318.1.2.3.4.28.3ScalarpcnsMinLoadCapabilityLostEnableCommandFileread-writemandatoryExecute a command file when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.28.4ScalarpcnsMinLoadCapabilityLostCommandFilePathread-writemandatoryPath of command file to execute when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.28.5ScalarpcnsMinLoadCapabilityLostCommandFileDelayread-writemandatoryHow long to wait after event occurs before executing command file (seconds).
1.3.6.1.4.1.318.1.2.3.4.28.6ScalarpcnsMinLoadCapabilityLostEnableShutdownread-writemandatoryPerform a graceful shutdown of the server when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.28.7ScalarpcnsMinLoadCapabilityLostShutdownDelayread-writemandatoryHow long to wait after event occurs before performing a graceful shutdown of the server (seconds).
1.3.6.1.4.1.318.1.2.3.4.29NodepcnsMinLoadCapabilityRegained
1.3.6.1.4.1.318.1.2.3.4.29.1ScalarpcnsMinLoadCapabilityRegainedDescread-onlymandatoryThe Description of the event.
1.3.6.1.4.1.318.1.2.3.4.29.2ScalarpcnsMinLoadCapabilityRegainedEnableLoggingread-writemandatoryLog occurrences of this event in PCNS log.
1.3.6.1.4.1.318.1.2.3.4.29.3ScalarpcnsMinLoadCapabilityRegainedEnableCommandFileread-writemandatoryExecute a command file when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.29.4ScalarpcnsMinLoadCapabilityRegainedCommandFilePathread-writemandatoryPath of command file to execute when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.29.5ScalarpcnsMinLoadCapabilityRegainedCommandFileDelayread-writemandatoryHow long to wait after event occurs before executing command file (seconds).
1.3.6.1.4.1.318.1.2.3.4.30NodepcnsEnvironmentCommunicationEstablished
1.3.6.1.4.1.318.1.2.3.4.30.1ScalarpcnsEnvironmentCommunicationEstablishedDescread-onlymandatoryThe Description of the event.
1.3.6.1.4.1.318.1.2.3.4.30.2ScalarpcnsEnvironmentCommunicationEstablishedEnableLoggingread-writemandatoryLog occurrences of this event in PCNS log.
1.3.6.1.4.1.318.1.2.3.4.30.3ScalarpcnsEnvironmentCommunicationEstablishedEnableCommandFileread-writemandatoryExecute a command file when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.30.4ScalarpcnsEnvironmentCommunicationEstablishedCommandFilePathread-writemandatoryPath of command file to execute when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.30.5ScalarpcnsEnvironmentCommunicationEstablishedCommandFileDelayread-writemandatoryHow long to wait after event occurs before executing command file (seconds).
1.3.6.1.4.1.318.1.2.3.4.31NodepcnsEnvironmentCommunicationLost
1.3.6.1.4.1.318.1.2.3.4.31.1ScalarpcnsEnvironmentCommunicationLostDescread-onlymandatoryThe Description of the event.
1.3.6.1.4.1.318.1.2.3.4.31.2ScalarpcnsEnvironmentCommunicationLostEnableLoggingread-writemandatoryLog occurrences of this event in PCNS log.
1.3.6.1.4.1.318.1.2.3.4.31.3ScalarpcnsEnvironmentCommunicationLostEnableCommandFileread-writemandatoryExecute a command file when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.31.4ScalarpcnsEnvironmentCommunicationLostCommandFilePathread-writemandatoryPath of command file to execute when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.31.5ScalarpcnsEnvironmentCommunicationLostCommandFileDelayread-writemandatoryHow long to wait after event occurs before executing command file (seconds).
1.3.6.1.4.1.318.1.2.3.4.32NodepcnsTempInRangeProbe1
1.3.6.1.4.1.318.1.2.3.4.32.1ScalarpcnsTempInRangeProbe1Descread-onlymandatoryThe Description of the event.
1.3.6.1.4.1.318.1.2.3.4.32.2ScalarpcnsTempInRangeProbe1EnableLoggingread-writemandatoryLog occurrences of this event in PCNS log.
1.3.6.1.4.1.318.1.2.3.4.32.3ScalarpcnsTempInRangeProbe1EnableCommandFileread-writemandatoryExecute a command file when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.32.4ScalarpcnsTempInRangeProbe1CommandFilePathread-writemandatoryPath of command file to execute when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.32.5ScalarpcnsTempInRangeProbe1CommandFileDelayread-writemandatoryHow long to wait after event occurs before executing command file (seconds).
1.3.6.1.4.1.318.1.2.3.4.33NodepcnsTempOutOfRangeProbe1
1.3.6.1.4.1.318.1.2.3.4.33.1ScalarpcnsTempOutOfRangeProbe1Descread-onlymandatoryThe Description of the event.
1.3.6.1.4.1.318.1.2.3.4.33.2ScalarpcnsTempOutOfRangeProbe1EnableLoggingread-writemandatoryLog occurrences of this event in PCNS log.
1.3.6.1.4.1.318.1.2.3.4.33.3ScalarpcnsTempOutOfRangeProbe1EnableCommandFileread-writemandatoryExecute a command file when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.33.4ScalarpcnsTempOutOfRangeProbe1CommandFilePathread-writemandatoryPath of command file to execute when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.33.5ScalarpcnsTempOutOfRangeProbe1CommandFileDelayread-writemandatoryHow long to wait after event occurs before executing command file (seconds).
1.3.6.1.4.1.318.1.2.3.4.33.6ScalarpcnsTempOutOfRangeProbe1EnableShutdownread-writemandatoryPerform a graceful shutdown of the server when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.33.7ScalarpcnsTempOutOfRangeProbe1ShutdownDelayread-writemandatoryHow long to wait after event occurs before performing a graceful shutdown of the server (seconds).
1.3.6.1.4.1.318.1.2.3.4.34NodepcnsHumidityInRangeProbe1
1.3.6.1.4.1.318.1.2.3.4.34.1ScalarpcnsHumidityInRangeProbe1Descread-onlymandatoryThe Description of the event.
1.3.6.1.4.1.318.1.2.3.4.34.2ScalarpcnsHumidityInRangeProbe1EnableLoggingread-writemandatoryLog occurrences of this event in PCNS log.
1.3.6.1.4.1.318.1.2.3.4.34.3ScalarpcnsHumidityInRangeProbe1EnableCommandFileread-writemandatoryExecute a command file when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.34.4ScalarpcnsHumidityInRangeProbe1CommandFilePathread-writemandatoryPath of command file to execute when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.34.5ScalarpcnsHumidityInRangeProbe1CommandFileDelayread-writemandatoryHow long to wait after event occurs before executing command file (seconds).
1.3.6.1.4.1.318.1.2.3.4.35NodepcnsHumidityOutOfRangeProbe1
1.3.6.1.4.1.318.1.2.3.4.35.1ScalarpcnsHumidityOutOfRangeProbe1Descread-onlymandatoryThe Description of the event.
1.3.6.1.4.1.318.1.2.3.4.35.2ScalarpcnsHumidityOutOfRangeProbe1EnableLoggingread-writemandatoryLog occurrences of this event in PCNS log.
1.3.6.1.4.1.318.1.2.3.4.35.3ScalarpcnsHumidityOutOfRangeProbe1EnableCommandFileread-writemandatoryExecute a command file when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.35.4ScalarpcnsHumidityOutOfRangeProbe1CommandFilePathread-writemandatoryPath of command file to execute when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.35.5ScalarpcnsHumidityOutOfRangeProbe1CommandFileDelayread-writemandatoryHow long to wait after event occurs before executing command file (seconds).
1.3.6.1.4.1.318.1.2.3.4.35.6ScalarpcnsHumidityOutOfRangeProbe1EnableShutdownread-writemandatoryPerform a graceful shutdown of the server when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.35.7ScalarpcnsHumidityOutOfRangeProbe1ShutdownDelayread-writemandatoryHow long to wait after event occurs before performing a graceful shutdown of the server (seconds).
1.3.6.1.4.1.318.1.2.3.4.36NodepcnsTempInRangeProbe2
1.3.6.1.4.1.318.1.2.3.4.36.1ScalarpcnsTempInRangeProbe2Descread-onlymandatoryThe Description of the event.
1.3.6.1.4.1.318.1.2.3.4.36.2ScalarpcnsTempInRangeProbe2EnableLoggingread-writemandatoryLog occurrences of this event in PCNS log.
1.3.6.1.4.1.318.1.2.3.4.36.3ScalarpcnsTempInRangeProbe2EnableCommandFileread-writemandatoryExecute a command file when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.36.4ScalarpcnsTempInRangeProbe2CommandFilePathread-writemandatoryPath of command file to execute when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.36.5ScalarpcnsTempInRangeProbe2CommandFileDelayread-writemandatoryHow long to wait after event occurs before executing command file (seconds).
1.3.6.1.4.1.318.1.2.3.4.37NodepcnsTempOutOfRangeProbe2
1.3.6.1.4.1.318.1.2.3.4.37.1ScalarpcnsTempOutOfRangeProbe2Descread-onlymandatoryThe Description of the event.
1.3.6.1.4.1.318.1.2.3.4.37.2ScalarpcnsTempOutOfRangeProbe2EnableLoggingread-writemandatoryLog occurrences of this event in PCNS log.
1.3.6.1.4.1.318.1.2.3.4.37.3ScalarpcnsTempOutOfRangeProbe2EnableCommandFileread-writemandatoryExecute a command file when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.37.4ScalarpcnsTempOutOfRangeProbe2CommandFilePathread-writemandatoryPath of command file to execute when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.37.5ScalarpcnsTempOutOfRangeProbe2CommandFileDelayread-writemandatoryHow long to wait after event occurs before executing command file (seconds).
1.3.6.1.4.1.318.1.2.3.4.37.6ScalarpcnsTempOutOfRangeProbe2EnableShutdownread-writemandatoryPerform a graceful shutdown of the server when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.37.7ScalarpcnsTempOutOfRangeProbe2ShutdownDelayread-writemandatoryHow long to wait after event occurs before performing a graceful shutdown of the server (seconds).
1.3.6.1.4.1.318.1.2.3.4.38NodepcnsHumidityInRangeProbe2
1.3.6.1.4.1.318.1.2.3.4.38.1ScalarpcnsHumidityInRangeProbe2Descread-onlymandatoryThe Description of the event.
1.3.6.1.4.1.318.1.2.3.4.38.2ScalarpcnsHumidityInRangeProbe2EnableLoggingread-writemandatoryLog occurrences of this event in PCNS log.
1.3.6.1.4.1.318.1.2.3.4.38.3ScalarpcnsHumidityInRangeProbe2EnableCommandFileread-writemandatoryExecute a command file when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.38.4ScalarpcnsHumidityInRangeProbe2CommandFilePathread-writemandatoryPath of command file to execute when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.38.5ScalarpcnsHumidityInRangeProbe2CommandFileDelayread-writemandatoryHow long to wait after event occurs before executing command file (seconds).
1.3.6.1.4.1.318.1.2.3.4.39NodepcnsHumidityOutOfRangeProbe2
1.3.6.1.4.1.318.1.2.3.4.39.1ScalarpcnsHumidityOutOfRangeProbe2Descread-onlymandatoryThe Description of the event.
1.3.6.1.4.1.318.1.2.3.4.39.2ScalarpcnsHumidityOutOfRangeProbe2EnableLoggingread-writemandatoryLog occurrences of this event in PCNS log.
1.3.6.1.4.1.318.1.2.3.4.39.3ScalarpcnsHumidityOutOfRangeProbe2EnableCommandFileread-writemandatoryExecute a command file when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.39.4ScalarpcnsHumidityOutOfRangeProbe2CommandFilePathread-writemandatoryPath of command file to execute when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.39.5ScalarpcnsHumidityOutOfRangeProbe2CommandFileDelayread-writemandatoryHow long to wait after event occurs before executing command file (seconds).
1.3.6.1.4.1.318.1.2.3.4.39.6ScalarpcnsHumidityOutOfRangeProbe2EnableShutdownread-writemandatoryPerform a graceful shutdown of the server when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.39.7ScalarpcnsHumidityOutOfRangeProbe2ShutdownDelayread-writemandatoryHow long to wait after event occurs before performing a graceful shutdown of the server (seconds).
1.3.6.1.4.1.318.1.2.3.4.40NodepcnsContactFault1
1.3.6.1.4.1.318.1.2.3.4.40.1ScalarpcnsContactFault1Descread-onlymandatoryThe Description of the event.
1.3.6.1.4.1.318.1.2.3.4.40.2ScalarpcnsContactFault1EnableLoggingread-writemandatoryLog occurrences of this event in PCNS log.
1.3.6.1.4.1.318.1.2.3.4.40.3ScalarpcnsContactFault1EnableCommandFileread-writemandatoryExecute a command file when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.40.4ScalarpcnsContactFault1CommandFilePathread-writemandatoryPath of command file to execute when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.40.5ScalarpcnsContactFault1CommandFileDelayread-writemandatoryHow long to wait after event occurs before executing command file (seconds).
1.3.6.1.4.1.318.1.2.3.4.40.6ScalarpcnsContactFault1EnableShutdownread-writemandatoryPerform a graceful shutdown of the server when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.40.7ScalarpcnsContactFault1ShutdownDelayread-writemandatoryHow long to wait after event occurs before performing a graceful shutdown of the server (seconds).
1.3.6.1.4.1.318.1.2.3.4.41NodepcnsContactFault2
1.3.6.1.4.1.318.1.2.3.4.41.1ScalarpcnsContactFault2Descread-onlymandatoryThe Description of the event.
1.3.6.1.4.1.318.1.2.3.4.41.2ScalarpcnsContactFault2EnableLoggingread-writemandatoryLog occurrences of this event in PCNS log.
1.3.6.1.4.1.318.1.2.3.4.41.3ScalarpcnsContactFault2EnableCommandFileread-writemandatoryExecute a command file when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.41.4ScalarpcnsContactFault2CommandFilePathread-writemandatoryPath of command file to execute when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.41.5ScalarpcnsContactFault2CommandFileDelayread-writemandatoryHow long to wait after event occurs before executing command file (seconds).
1.3.6.1.4.1.318.1.2.3.4.41.6ScalarpcnsContactFault2EnableShutdownread-writemandatoryPerform a graceful shutdown of the server when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.41.7ScalarpcnsContactFault2ShutdownDelayread-writemandatoryHow long to wait after event occurs before performing a graceful shutdown of the server (seconds).
1.3.6.1.4.1.318.1.2.3.4.42NodepcnsContactFault3
1.3.6.1.4.1.318.1.2.3.4.42.1ScalarpcnsContactFault3Descread-onlymandatoryThe Description of the event.
1.3.6.1.4.1.318.1.2.3.4.42.2ScalarpcnsContactFault3EnableLoggingread-writemandatoryLog occurrences of this event in PCNS log.
1.3.6.1.4.1.318.1.2.3.4.42.3ScalarpcnsContactFault3EnableCommandFileread-writemandatoryExecute a command file when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.42.4ScalarpcnsContactFault3CommandFilePathread-writemandatoryPath of command file to execute when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.42.5ScalarpcnsContactFault3CommandFileDelayread-writemandatoryHow long to wait after event occurs before executing command file (seconds).
1.3.6.1.4.1.318.1.2.3.4.42.6ScalarpcnsContactFault3EnableShutdownread-writemandatoryPerform a graceful shutdown of the server when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.42.7ScalarpcnsContactFault3ShutdownDelayread-writemandatoryHow long to wait after event occurs before performing a graceful shutdown of the server (seconds).
1.3.6.1.4.1.318.1.2.3.4.43NodepcnsContactFault4
1.3.6.1.4.1.318.1.2.3.4.43.1ScalarpcnsContactFault4Descread-onlymandatoryThe Description of the event.
1.3.6.1.4.1.318.1.2.3.4.43.2ScalarpcnsContactFault4EnableLoggingread-writemandatoryLog occurrences of this event in PCNS log.
1.3.6.1.4.1.318.1.2.3.4.43.3ScalarpcnsContactFault4EnableCommandFileread-writemandatoryExecute a command file when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.43.4ScalarpcnsContactFault4CommandFilePathread-writemandatoryPath of command file to execute when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.43.5ScalarpcnsContactFault4CommandFileDelayread-writemandatoryHow long to wait after event occurs before executing command file (seconds).
1.3.6.1.4.1.318.1.2.3.4.43.6ScalarpcnsContactFault4EnableShutdownread-writemandatoryPerform a graceful shutdown of the server when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.43.7ScalarpcnsContactFault4ShutdownDelayread-writemandatoryHow long to wait after event occurs before performing a graceful shutdown of the server (seconds).
1.3.6.1.4.1.318.1.2.3.4.44NodepcnsContactNormal1
1.3.6.1.4.1.318.1.2.3.4.44.1ScalarpcnsContactNormal1Descread-onlymandatoryThe Description of the event.
1.3.6.1.4.1.318.1.2.3.4.44.2ScalarpcnsContactNormal1EnableLoggingread-writemandatoryLog occurrences of this event in PCNS log.
1.3.6.1.4.1.318.1.2.3.4.44.3ScalarpcnsContactNormal1EnableCommandFileread-writemandatoryExecute a command file when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.44.4ScalarpcnsContactNormal1CommandFilePathread-writemandatoryPath of command file to execute when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.44.5ScalarpcnsContactNormal1CommandFileDelayread-writemandatoryHow long to wait after event occurs before executing command file (seconds).
1.3.6.1.4.1.318.1.2.3.4.45NodepcnsContactNormal2
1.3.6.1.4.1.318.1.2.3.4.45.1ScalarpcnsContactNormal2Descread-onlymandatoryThe Description of the event.
1.3.6.1.4.1.318.1.2.3.4.45.2ScalarpcnsContactNormal2EnableLoggingread-writemandatoryLog occurrences of this event in PCNS log.
1.3.6.1.4.1.318.1.2.3.4.45.3ScalarpcnsContactNormal2EnableCommandFileread-writemandatoryExecute a command file when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.45.4ScalarpcnsContactNormal2CommandFilePathread-writemandatoryPath of command file to execute when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.45.5ScalarpcnsContactNormal2CommandFileDelayread-writemandatoryHow long to wait after event occurs before executing command file (seconds).
1.3.6.1.4.1.318.1.2.3.4.46NodepcnsContactNormal3
1.3.6.1.4.1.318.1.2.3.4.46.1ScalarpcnsContactNormal3Descread-onlymandatoryThe Description of the event.
1.3.6.1.4.1.318.1.2.3.4.46.2ScalarpcnsContactNormal3EnableLoggingread-writemandatoryLog occurrences of this event in PCNS log.
1.3.6.1.4.1.318.1.2.3.4.46.3ScalarpcnsContactNormal3EnableCommandFileread-writemandatoryExecute a command file when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.46.4ScalarpcnsContactNormal3CommandFilePathread-writemandatoryPath of command file to execute when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.46.5ScalarpcnsContactNormal3CommandFileDelayread-writemandatoryHow long to wait after event occurs before executing command file (seconds).
1.3.6.1.4.1.318.1.2.3.4.47NodepcnsContactNormal4
1.3.6.1.4.1.318.1.2.3.4.47.1ScalarpcnsContactNormal4Descread-onlymandatoryThe Description of the event.
1.3.6.1.4.1.318.1.2.3.4.47.2ScalarpcnsContactNormal4EnableLoggingread-writemandatoryLog occurrences of this event in PCNS log.
1.3.6.1.4.1.318.1.2.3.4.47.3ScalarpcnsContactNormal4EnableCommandFileread-writemandatoryExecute a command file when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.47.4ScalarpcnsContactNormal4CommandFilePathread-writemandatoryPath of command file to execute when this event occurs.
1.3.6.1.4.1.318.1.2.3.4.47.5ScalarpcnsContactNormal4CommandFileDelayread-writemandatoryHow long to wait after event occurs before executing command file (seconds).
1.3.6.1.4.1.318.1.2.3.5NodepcnsShutdown
1.3.6.1.4.1.318.1.2.3.5.1ScalarpcnsShutdownCommandFileEnabledread-writemandatoryRun a shutdown command file before performing graceful shutdown.
1.3.6.1.4.1.318.1.2.3.5.2ScalarpcnsShutdownCommandFileDelayread-writemandatoryHow long in seconds to wait before running a shutdown command file before graceful shutdown.
1.3.6.1.4.1.318.1.2.3.5.3ScalarpcnsShutdownCommandFileread-writemandatoryFull name of the shutdown command file to run before graceful shutdown.
1.3.6.1.4.1.318.1.2.3.5.4ScalarpcnsShutdownCommandFileDurationread-writemandatoryHow long in seconds shutdown command file takes to run.
1.3.6.1.4.1.318.1.2.3.5.5ScalarpcnsTurnOffUpsread-writemandatoryTurn off the UPS when performing a graceful shutdown.
1.3.6.1.4.1.318.1.2.3.5.6ScalarpcnsTurnOffSOGread-writemandatoryTurn off the Outlet Group on the UPS when performing a graceful shutdown.
1.3.6.1.4.1.318.1.2.3.5.7ScalarpcnsRuntimeRemainingThresholdread-writemandatoryThis defines a threshold for runtime remaining. When the UPS is running on battery power and the runtime remaining on the UPS drops below the threshold, PowerC…
1.3.6.1.4.1.318.1.2.3.5.8ScalarpcnsRuntimeRemainingCmdFileThresholdread-writemandatoryThis defines a threshold for runtime remaining. When runtime remaining drops below this threshold, PowerChute will execute the command file.
1.3.6.1.4.1.318.1.2.3.5.9TablepcnsAdvancedShutdownTablenot-accessiblemandatoryThe Network Management Cards in the UPS's which PCNS is monitoring to provide safe shutdown.
1.3.6.1.4.1.318.1.2.3.5.9.1RowpcnsAdvancedShutdownEntrynot-accessiblemandatoryDetails of the NMC.
1.3.6.1.4.1.318.1.2.3.5.9.1.1ColumnpcnsAdvancedGroupNoread-onlymandatoryIndex of the Advanced Shutdown Group.
1.3.6.1.4.1.318.1.2.3.5.9.1.2ColumnpcnsAdvancedGroupNameread-writemandatoryName of the Advanced Shutdown Group.
1.3.6.1.4.1.318.1.2.3.5.9.1.3ColumnpcnsAdvancedGroupNMCread-onlymandatoryList of NMCs in the Advanced Shutdown Group.
1.3.6.1.4.1.318.1.2.3.5.9.1.4ColumnpcnsAdvancedShutdownUPSRequiredForLoadread-writemandatoryNumber of UPS's required to power load.
1.3.6.1.4.1.318.1.2.3.5.9.1.5ColumnpcnsAdvancedShutdownCommandFileEnabledread-writemandatoryRun a shutdown command file before performing graceful shutdown.
1.3.6.1.4.1.318.1.2.3.5.9.1.6ColumnpcnsAdvancedShutdownCommandFileread-writemandatoryFull name of the shutdown command file to run before graceful shutdown.
1.3.6.1.4.1.318.1.2.3.5.9.1.7ColumnpcnsAdvancedShutdownCommandFileDurationread-writemandatoryHow long in seconds shutdown command file takes to run.
1.3.6.1.4.1.318.1.2.3.5.9.1.8ColumnpcnsAdvancedShutdownPowerchuteServerread-writemandatoryShut down PowerChute Server.
1.3.6.1.4.1.318.1.2.3.5.9.1.9ColumnpcnsAdvancedShutdownOnLostRedundancyread-writemandatoryShut down if Redundancy lost.
1.3.6.1.4.1.318.1.2.3.5.9.1.10ColumnpcnsAdvancedTurnOffUpsread-writemandatoryTurn off the UPS when performing a graceful shutdown.
1.3.6.1.4.1.318.1.2.3.5.9.1.11ColumnpcnsAdvancedTurnOffSOGread-writemandatoryTurn off the Outlet Group on the UPS when performing a graceful shutdown.
1.3.6.1.4.1.318.1.2.3.6NodepcnsAlarms
1.3.6.1.4.1.318.1.2.3.6.1ScalarpcnsCriticalFlagread-onlymandatoryPowerChute Network Shutdown has begun a safe shutdown of the host.
1.3.6.1.4.1.318.1.2.3.6.2ScalarpcnsCriticalCauseread-onlymandatoryThe reason PowerChute Network Shutdown has begun a safe shutdown.
1.3.6.1.4.1.318.1.2.3.6.3ScalarpcnsNetComsLostFlagread-onlymandatoryPowerChute cannot communicate with NMC.
1.3.6.1.4.1.318.1.2.3.6.4ScalarpcnsNMCComsLostFlagread-onlymandatoryNMC cannot communicate with UPS.
1.3.6.1.4.1.318.1.2.3.6.5ScalarpcnsUpdateAvailableFlagread-onlymandatoryPowerChute has detected that a newer version is available.
1.3.6.1.4.1.318.1.2.3.6.6ScalarpcnsUpdateDescread-onlymandatoryDetails of the newer version of PowerChute.
1.3.6.1.4.1.318.1.2.3.7ScalarpcnsLoggingLevelread-writemandatoryOverride the Root Logging level for PCNS. Possible Values: CLEAR, DEBUG
1.3.6.1.4.1.318.1.2.4NodepowerChuteBusinessEdition
1.3.6.1.4.1.318.1.2.4.1NodepcbeIdent
1.3.6.1.4.1.318.1.2.4.1.1ScalarpcbeHostnameread-onlymandatoryThe hostname of the PCBE instance.
1.3.6.1.4.1.318.1.2.4.1.2ScalarpcbeVersionread-onlymandatoryThe version of PCBE installed. x.x.x
1.3.6.1.4.1.318.1.2.4.1.3ScalarpcbeOSread-onlymandatoryThe version of OS PCBE is installed on.
1.3.6.1.4.1.318.1.2.4.1.4ScalarpcbeJavaVersionread-onlymandatoryThe version of Java PCBE is running on.
1.3.6.1.4.1.318.1.2.4.1.5ScalarpcbeUIProtocolread-onlymandatoryWeb Protocol used to connect to the PCBE UI.
1.3.6.1.4.1.318.1.2.4.1.6ScalarpcbeHttpPortread-onlymandatoryPort used for PCBE http UI.
1.3.6.1.4.1.318.1.2.4.1.7ScalarpcbeHttpsPortread-onlymandatoryPort used for PCBE https UI.
1.3.6.1.4.1.318.1.2.4.6NodepcbeAlarms
1.3.6.1.4.1.318.1.2.4.6.1ScalarpcbeCriticalFlagread-onlymandatoryPowerChute Business Edition has begun a safe shutdown of the host.
1.3.6.1.4.1.318.1.2.4.6.2ScalarpcbeCriticalCauseread-onlymandatoryThe reason PowerChute Business Edition has begun a safe shutdown.
1.3.6.1.4.1.318.1.2.4.6.3ScalarpcbeComsLostFlagread-onlymandatoryIf active (1), PowerChute cannot communicate with UPS
1.3.6.1.4.1.318.1.2.4.6.5ScalarpcbeUpdateAvailableFlagread-onlymandatoryPowerChute has detected that a newer version is available.
1.3.6.1.4.1.318.1.2.4.6.6ScalarpcbeUpdateDescread-onlymandatoryDetails of the newer version of PowerChute.
1.3.6.1.4.1.318.1.3Nodesystem
1.3.6.1.4.1.318.1.3.4NodemasterSwitch
1.3.6.1.4.1.318.1.3.4.1NodemasterSwitchV1
1.3.6.1.4.1.318.1.3.4.2NodemasterSwitchV2
1.3.6.1.4.1.318.1.3.4.3NodemasterSwitchVM
1.3.6.1.4.1.318.1.3.4.4NodemasterSwitchMSP
1.3.6.1.4.1.318.1.3.4.5NodemasterSwitchrPDU
1.3.6.1.4.1.318.1.3.4.6NodemasterSwitchrPDU2
1.3.6.1.4.1.318.1.3.4.7NodemasterSwitchsPDU
1.3.6.1.4.1.318.1.3.4.8NodemasterSwitchrPDUB
1.3.6.1.4.1.318.1.3.4.9NodemasterSwitchePDU
1.3.6.1.4.1.318.1.4Nodeexperimental
1.3.6.1.4.1.318.2Nodemgmt
1.3.6.1.4.1.318.750NoderpduCriticalConditionSEVERE: A RPDU critical condition has been detected. The first variable is the serial number. The second variable is the device name. The third variable is the…
1.3.6.1.4.1.318.751NoderpduCriticalConditionClearedINFORMATIONAL: A RPDU critical condition has been cleared. The first variable is the serial number. The second variable is the device name. The third variable …
1.3.6.1.4.1.318.752NoderpduWarningConditionWARNING: A RPDU warning condition has been detected. The first variable is the serial number. The second variable is the device name. The third variable is the…
1.3.6.1.4.1.318.753NoderpduWarningConditionClearedWARNING: A RPDU warning condition has been cleared. The first variable is the serial number. The second variable is the device name. The third variable is the …
1.3.6.1.4.1.318.754NoderpduInformationalConditionINFORMATIONAL: A RPDU informational condition has been detected. The first variable is the serial number. The second variable is the device name. The third var…
1.3.6.1.4.1.318.755NoderpduInformationalConditionClearedINFORMATIONAL: A RPDU informational condition has been cleared. The first variable is the serial number. The second variable is the device name. The third vari…
Type Definitions
NameSyntaxStatusDescription
AirIRG2RDType2IOStateINTEGER { open(1), closed(2) }
AirIRmActivityStateINTEGER { inactive(1), active(2) }
AirIRmAlarmStateINTEGER { ok(1), alarm(2) }
AirIRmControlStateINTEGER { off(1), on(2) }
AirIRmStopStateINTEGER { maybeOn(1), unitOff(2) }
AirIRSCCapacityControlTypeINTEGER { discrete(1), proportional(2) }
AirIRSCConfigTypeINTEGER { racs(1), spot(2), in-row(3) }
AirIRSCFanSpeedControlINTEGER { automatic(1), manual(2) }
AirIRSCFanSpeedPreferenceINTEGER { low(1), med-low(2), med(3), med-high(4), high(5) }
Rpdu2OutletPhaseLayoutTypeINTEGER { seqPhase1ToNeutral(1), seqPhase2ToNeutral(2), seqPhase3ToNeutral(3), seqPhase1ToPhase2(4), seqPhase2ToPhase3(5), seqPhase3ToPhase1(6) }