MIB Viewer

RIELLOMDU-MIB

42 objects
No module-level DESCRIPTION found.
Imported Objects
RFC-1212OBJECT-TYPE
RFC-1215TRAP-TYPE
RFC1213-MIBDisplayString
RIELLO-MIBrielloMIB
OIDNameAccessStatusDescription
1.3.6.1.4.1.5491.11NodemduMIB
1.3.6.1.4.1.5491.11.1NodemduIdent
1.3.6.1.4.1.5491.11.1.1ScalarmduIdentManufacturerread-onlymandatoryThe name of the mdu manufacturer.
1.3.6.1.4.1.5491.11.1.2ScalarmduIdentModelread-onlymandatoryThe mdu Model designation.
1.3.6.1.4.1.5491.11.1.3ScalarmduIdentSoftwareVersionread-onlymandatoryThe mdu Software version.
1.3.6.1.4.1.5491.11.1.4ScalarmduIdentIOConfigurationread-onlymandatoryThe mdu input/output configuration (1 for Mono/mono, 4 for Tri/tri).
1.3.6.1.4.1.5491.11.1.5ScalarmduIdentInputSocketsread-onlymandatoryThe number of mdu input sockets.
1.3.6.1.4.1.5491.11.1.6ScalarmduIdentOutputSocketsread-onlymandatoryThe number of mdu output sockets.
1.3.6.1.4.1.5491.11.1.7ScalarmduIdentNominalCurrentread-onlymandatoryThe mdu nominal current (A).
1.3.6.1.4.1.5491.11.1.8ScalarmduIdentNominalVoltageread-onlymandatoryThe mdu nominal voltage (V).
1.3.6.1.4.1.5491.11.1.9ScalarmduIdentNominalFrequencyread-onlymandatoryThe mdu nominal frequency (0.1 Hz).
1.3.6.1.4.1.5491.11.2NodemduStatus
1.3.6.1.4.1.5491.11.2.1ScalarmduLineAFrequencyread-onlymandatoryThe frequency of source A (0.1 Hz).
1.3.6.1.4.1.5491.11.2.2ScalarmduLineAVoltageread-onlymandatoryThe voltage of source 1 (V).
1.3.6.1.4.1.5491.11.2.3ScalarmduLineACurrentread-onlymandatoryThe current of line A (0.1 A).
1.3.6.1.4.1.5491.11.2.4TablemduOutputnot-accessiblemandatoryA list of output table entries.
1.3.6.1.4.1.5491.11.2.4.1RowmduOutputSocketsnot-accessiblemandatoryAn entry containing information applicable to a particular output line.
1.3.6.1.4.1.5491.11.2.4.1.1ColumnmduOutputLineIndexnot-accessiblemandatoryThe line identifier.
1.3.6.1.4.1.5491.11.2.4.1.2ColumnmduOutputCurrentread-onlymandatoryOutput current (0.1 A)
1.3.6.1.4.1.5491.11.2.4.1.3ColumnmduOutputDisabledread-onlymandatory1->line active, 2->line deactivated
1.3.6.1.4.1.5491.11.2.4.1.4ColumnmduOutputOverloadread-onlymandatory1->line ok, 2->line deactivated for overload
1.3.6.1.4.1.5491.11.2.4.1.5ColumnmduOutputStatusread-onlymandatory0=OFF 1=ON 2= Shutdown active (when a CS or a CR command is received but shutdown is not yet been executed and the
1.3.6.1.4.1.5491.11.2.5ScalarmduLowInputVoltageread-onlymandatory1= yes, 0= no.
1.3.6.1.4.1.5491.11.2.6ScalarmduHighInputVoltageread-onlymandatory1= yes, 0= no.
1.3.6.1.4.1.5491.11.2.7ScalarmduLowInputCurrentread-onlymandatory1= yes, 0= no.
1.3.6.1.4.1.5491.11.2.8ScalarmduHighInputCurrentread-onlymandatory1= yes, 0= no.
1.3.6.1.4.1.5491.11.2.9ScalarmduPowerFailAux1read-onlymandatory1= yes, 0= no.
1.3.6.1.4.1.5491.11.2.10ScalarmduPowerFailAux2read-onlymandatory1= yes, 0= no.
1.3.6.1.4.1.5491.11.2.11ScalarmduManualBypassread-onlymandatory1= on manual bypass, 0= no.
1.3.6.1.4.1.5491.11.2.12ScalarmduTemperatureread-onlymandatoryThe temperature (°C).
1.3.6.1.4.1.5491.11.3NodemduCommand
1.3.6.1.4.1.5491.11.3.1ScalarmduCommandCoderead-writemandatoryThis object determines the nature of the action to be taken at the time when the countdown of the mduShutdownDelay and mduRestoreDelay objects reaches zero. Se…
1.3.6.1.4.1.5491.11.3.2ScalarmduShutdownDelayread-writemandatorySetting this object will shutdown (i.e., turn off) either the MDU output socket by the value of mduCommandCode at the time of shutdown after the indicated numb…
1.3.6.1.4.1.5491.11.3.3ScalarmduRestoreDelayread-writemandatoryThe restore delay.
1.3.6.1.4.1.5491.11.3.4ScalarmduOutputSocketApplyCommandread-writemandatorySpecify the socket to apply the command, the value 0 apply to all sockets.
1.3.6.1.4.1.5491.11.3.5ScalarmduCommandResultread-onlymandatoryThe command result, refer to the follow codes: 0+mduCommandCode Command in progress 256+mduCommandCode Wrong Command code 512+mduCommandCode Command is not han…
1.3.6.1.4.1.5491.11.4NodemduTraps
1.3.6.1.4.1.5491.11.4.1NodemduNormalThis trap is sent when MDU is on normal status
1.3.6.1.4.1.5491.11.4.2NodemduAnomalyThis trap is sent when MDU is has some anomaly and is resent every minute
1.3.6.1.4.1.5491.11.4.3NodemduFaultThis trap is sent when MDU is has some fault and is resent every minute
1.3.6.1.4.1.5491.11.4.4NodemduLockThis trap is sent when MDU is locked and is resent every minute
1.3.6.1.4.1.5491.11.4.5NodemduManualBypassEnabledThis trap is sent when MDU is on manual bypass and is resent every minute