RIELLOUPS-MIB
165 objects
No module-level DESCRIPTION found.
Imported Objects
| RFC-1212 | OBJECT-TYPE |
| RFC-1215 | TRAP-TYPE |
| RFC1155-SMI | Counter Gauge |
| RIELLO-MIB | rielloMIB |
| SNMPv2-CONF | MODULE-COMPLIANCE OBJECT-GROUP |
| SNMPv2-SMI | Counter32 Gauge32 Integer32 MODULE-IDENTITY NOTIFICATION-TYPE OBJECT-IDENTITY |
| SNMPv2-TC | AutonomousType DisplayString TestAndIncr TEXTUAL-CONVENTION TimeInterval TimeStamp |
| OID | Name | Access | Status | Description |
|---|---|---|---|---|
| 1.3.6.1.4.1.5491.10 | NoderupsMIB | |||
| 1.3.6.1.4.1.5491.10.1 | NoderupsObjects | |||
| 1.3.6.1.4.1.5491.10.1.1 | NoderupsIdent | |||
| 1.3.6.1.4.1.5491.10.1.1.1 | ScalarrupsIdentManufacturer | read-only | mandatory | The name of the UPS manufacturer. |
| 1.3.6.1.4.1.5491.10.1.1.2 | ScalarrupsIdentModel | read-only | mandatory | The UPS Model designation. |
| 1.3.6.1.4.1.5491.10.1.1.3 | ScalarrupsIdentUPSSoftwareVersion | read-only | mandatory | The UPS firmware/software version(s). This variable may or may not have the same value as upsIdentAgentSoftwareVersion in some implementations. |
| 1.3.6.1.4.1.5491.10.1.1.4 | ScalarrupsIdentAgentSoftwareVersion | read-only | mandatory | The UPS agent software version. This variable may or may not have the same value as upsIdentUPSSoftwareVersion in some implementations. |
| 1.3.6.1.4.1.5491.10.1.1.5 | ScalarrupsIdentName | read-write | mandatory | A string identifying the UPS. This object should be set by the administrator. |
| 1.3.6.1.4.1.5491.10.1.1.6 | ScalarrupsIdentAttachedDevices | read-write | mandatory | A string identifying the devices attached to the output(s) of the UPS. This object should be set by the administrator. |
| 1.3.6.1.4.1.5491.10.1.1.7 | ScalarrupsIdentIOConfiguration | read-only | mandatory | The UPS IO configuration. |
| 1.3.6.1.4.1.5491.10.1.1.8 | ScalarrupsIdentUpsType | read-only | mandatory | The UPS type. |
| 1.3.6.1.4.1.5491.10.1.1.9 | ScalarrupsIdentNominalPowerVA | read-only | mandatory | The UPS nominal power VA. |
| 1.3.6.1.4.1.5491.10.1.1.10 | ScalarrupsIdentNominalPowerW | read-only | mandatory | The UPS nominal power W. |
| 1.3.6.1.4.1.5491.10.1.1.11 | ScalarrupsIdentBatteryVoltage | read-only | mandatory | The UPS nominal battery voltage. |
| 1.3.6.1.4.1.5491.10.1.1.12 | ScalarrupsIdentBatteryCapacity | read-only | mandatory | The UPS nominal battery capacity. |
| 1.3.6.1.4.1.5491.10.1.1.13 | ScalarrupsIdentOutputVoltage | read-only | mandatory | The UPS nominal output voltage. |
| 1.3.6.1.4.1.5491.10.1.1.14 | ScalarrupsIdentOutputFrequency | read-only | mandatory | The UPS nominal output frequency. |
| 1.3.6.1.4.1.5491.10.1.2 | NoderupsBattery | |||
| 1.3.6.1.4.1.5491.10.1.2.1 | ScalarrupsBatteryStatus | read-only | mandatory | The indication of the capacity remaining in the UPS system's batteries. A value of batteryNormal indicates that the remaining run-time is greater than rupsConf… |
| 1.3.6.1.4.1.5491.10.1.2.2 | ScalarrupsSecondsOnBattery | read-only | mandatory | If the unit is on battery power, the elapsed time since the UPS last switched to battery power, or the time since the network management subsystem was last res… |
| 1.3.6.1.4.1.5491.10.1.2.3 | ScalarrupsEstimatedMinutesRemaining | read-only | mandatory | An estimate of the time to battery charge depletion under the present load conditions if the utility power is off and remains off, or if it were to be lost and… |
| 1.3.6.1.4.1.5491.10.1.2.4 | ScalarrupsEstimatedChargeRemaining | read-only | mandatory | An estimate of the battery charge remaining expressed as a percent of full charge. |
| 1.3.6.1.4.1.5491.10.1.2.5 | ScalarrupsBatteryVoltage | read-only | mandatory | The magnitude of the present battery voltage. |
| 1.3.6.1.4.1.5491.10.1.2.6 | ScalarrupsBatteryCurrent | read-only | mandatory | The present battery current. |
| 1.3.6.1.4.1.5491.10.1.2.7 | ScalarrupsBatteryTemperature | read-only | mandatory | The ambient temperature at or near the UPS Battery casing. |
| 1.3.6.1.4.1.5491.10.1.2.8 | ScalarrupsBatteryPositiveVoltage | read-only | mandatory | The UPS Battery positive voltage. |
| 1.3.6.1.4.1.5491.10.1.2.9 | ScalarrupsBatteryNegativeVoltage | read-only | mandatory | The UPS Battery negative voltage. |
| 1.3.6.1.4.1.5491.10.1.2.10 | ScalarrupsBatteryPositiveCurrent | read-only | mandatory | The UPS Battery positive current. |
| 1.3.6.1.4.1.5491.10.1.2.11 | ScalarrupsBatteryNegativeCurrent | read-only | mandatory | The UPS Battery positive current. |
| 1.3.6.1.4.1.5491.10.1.2.12 | ScalarrupsIsCharging | read-only | mandatory | The charging/discharging status of the battery |
| 1.3.6.1.4.1.5491.10.1.3 | NoderupsInput | |||
| 1.3.6.1.4.1.5491.10.1.3.1 | ScalarrupsInputLineBads | read-only | mandatory | A count of the number of times the input entered an out-of-tolerance condition as defined by the manufacturer. This count is incremented by one each time the i… |
| 1.3.6.1.4.1.5491.10.1.3.2 | ScalarrupsInputNumLines | read-only | mandatory | The number of input lines utilized in this device. This variable indicates the number of rows in the input table. |
| 1.3.6.1.4.1.5491.10.1.3.3 | TablerupsInputTable | not-accessible | mandatory | A list of input table entries. The number of entries is given by the value of upsInputNumLines. |
| 1.3.6.1.4.1.5491.10.1.3.3.1 | RowrupsInputEntry | not-accessible | mandatory | An entry containing information applicable to a particular input line. |
| 1.3.6.1.4.1.5491.10.1.3.3.1.1 | ColumnrupsInputLineIndex | not-accessible | mandatory | The input line identifier. |
| 1.3.6.1.4.1.5491.10.1.3.3.1.2 | ColumnrupsInputFrequency | read-only | mandatory | The present input frequency. |
| 1.3.6.1.4.1.5491.10.1.3.3.1.3 | ColumnrupsInputVoltage | read-only | mandatory | The magnitude of the present input voltage. |
| 1.3.6.1.4.1.5491.10.1.3.3.1.4 | ColumnrupsInputCurrent | read-only | mandatory | The magnitude of the present input current. |
| 1.3.6.1.4.1.5491.10.1.3.3.1.5 | ColumnrupsInputTruePower | read-only | mandatory | The magnitude of the present input true power. |
| 1.3.6.1.4.1.5491.10.1.4 | NoderupsOutput | |||
| 1.3.6.1.4.1.5491.10.1.4.1 | ScalarrupsOutputSource | read-only | mandatory | The present source of output power. The enumeration none(2) indicates that there is no source of output power (and therefore no output power), for example, the… |
| 1.3.6.1.4.1.5491.10.1.4.2 | ScalarrupsOutputFrequency | read-only | mandatory | The present output frequency. |
| 1.3.6.1.4.1.5491.10.1.4.3 | ScalarrupsOutputNumLines | read-only | mandatory | The number of output lines utilized in this device. This variable indicates the number of rows in the output table. |
| 1.3.6.1.4.1.5491.10.1.4.4 | TablerupsOutputTable | not-accessible | mandatory | A list of output table entries. The number of entries is given by the value of rupsOutputNumLines. |
| 1.3.6.1.4.1.5491.10.1.4.4.1 | RowrupsOutputEntry | not-accessible | mandatory | An entry containing information applicable to a particular output line. |
| 1.3.6.1.4.1.5491.10.1.4.4.1.1 | ColumnrupsOutputLineIndex | not-accessible | mandatory | The output line identifier. |
| 1.3.6.1.4.1.5491.10.1.4.4.1.2 | ColumnrupsOutputVoltage | read-only | mandatory | The present output voltage. |
| 1.3.6.1.4.1.5491.10.1.4.4.1.3 | ColumnrupsOutputCurrent | read-only | mandatory | The present output current. |
| 1.3.6.1.4.1.5491.10.1.4.4.1.4 | ColumnrupsOutputPower | read-only | mandatory | The present output true power. |
| 1.3.6.1.4.1.5491.10.1.4.4.1.5 | ColumnrupsOutputPercentLoad | read-only | mandatory | The percentage of the UPS power capacity presently being used on this output line, i.e., the greater of the percent load of true power capacity and the percent… |
| 1.3.6.1.4.1.5491.10.1.4.4.1.6 | ColumnrupsOutputPeakCurrent | read-only | mandatory | The present output peak current. |
| 1.3.6.1.4.1.5491.10.1.5 | NoderupsBypass | |||
| 1.3.6.1.4.1.5491.10.1.5.1 | ScalarrupsBypassFrequency | read-only | mandatory | The present bypass frequency. |
| 1.3.6.1.4.1.5491.10.1.5.2 | ScalarrupsBypassNumLines | read-only | mandatory | The number of bypass lines utilized in this device. This entry indicates the number of rows in the bypass table. |
| 1.3.6.1.4.1.5491.10.1.5.3 | TablerupsBypassTable | not-accessible | mandatory | A list of bypass table entries. The number of entries is given by the value of rupsBypassNumLines. |
| 1.3.6.1.4.1.5491.10.1.5.3.1 | RowrupsBypassEntry | not-accessible | mandatory | An entry containing information applicable to a particular bypass input. |
| 1.3.6.1.4.1.5491.10.1.5.3.1.1 | ColumnrupsBypassLineIndex | not-accessible | mandatory | The bypass line identifier. |
| 1.3.6.1.4.1.5491.10.1.5.3.1.2 | ColumnrupsBypassVoltage | read-only | mandatory | The present bypass voltage. |
| 1.3.6.1.4.1.5491.10.1.5.3.1.3 | ColumnrupsBypassCurrent | read-only | mandatory | The present bypass current. |
| 1.3.6.1.4.1.5491.10.1.5.3.1.4 | ColumnrupsBypassPower | read-only | mandatory | The present true power conveyed by the bypass. |
| 1.3.6.1.4.1.5491.10.1.6 | NoderupsAlarm | |||
| 1.3.6.1.4.1.5491.10.1.6.1 | ScalarrupsAlarmsPresent | read-only | mandatory | The present number of active alarm conditions. |
| 1.3.6.1.4.1.5491.10.1.6.2 | TablerupsAlarmTable | not-accessible | mandatory | A list of alarm table entries. The table contains zero, one, or many rows at any moment, depending upon the number of alarm conditions in effect. The table is … |
| 1.3.6.1.4.1.5491.10.1.6.2.1 | RowrupsAlarmEntry | not-accessible | mandatory | An entry containing information applicable to a particular alarm. |
| 1.3.6.1.4.1.5491.10.1.6.2.1.1 | ColumnrupsAlarmId | not-accessible | mandatory | A unique identifier for an alarm condition. This value must remain constant. |
| 1.3.6.1.4.1.5491.10.1.6.2.1.2 | ColumnrupsAlarmDescr | read-only | mandatory | A reference to an alarm description object. The object referenced should not be accessible, but rather be used to provide a unique description of the alarm con… |
| 1.3.6.1.4.1.5491.10.1.6.2.1.3 | ColumnrupsAlarmTime | read-only | mandatory | The value of sysUpTime when the alarm condition was detected. If the alarm condition was detected at the time of agent startup and presumably existed before ag… |
| 1.3.6.1.4.1.5491.10.1.6.3 | NoderupsWellKnownAlarms | |||
| 1.3.6.1.4.1.5491.10.1.6.3.1 | NoderupsAlarmBatteryBad | |||
| 1.3.6.1.4.1.5491.10.1.6.3.2 | NoderupsAlarmOnBattery | |||
| 1.3.6.1.4.1.5491.10.1.6.3.3 | NoderupsAlarmLowBattery | |||
| 1.3.6.1.4.1.5491.10.1.6.3.4 | NoderupsAlarmShutdownImminent | |||
| 1.3.6.1.4.1.5491.10.1.6.3.5 | NoderupsAlarmTempBad | |||
| 1.3.6.1.4.1.5491.10.1.6.3.6 | NoderupsAlarmFault | |||
| 1.3.6.1.4.1.5491.10.1.6.3.7 | NoderupsAlarmInternal | |||
| 1.3.6.1.4.1.5491.10.1.6.3.8 | NoderupsAlarmOutputOverload | |||
| 1.3.6.1.4.1.5491.10.1.6.3.9 | NoderupsAlarmOnBypass | |||
| 1.3.6.1.4.1.5491.10.1.6.3.10 | NoderupsAlarmBypassBad | |||
| 1.3.6.1.4.1.5491.10.1.7 | NoderupsTest | |||
| 1.3.6.1.4.1.5491.10.1.7.1 | ScalarrupsTestId | read-write | optional | The test is named by an OBJECT IDENTIFIER which allows a standard mechanism for the initiation of tests, including the well known tests identified in this docu… |
| 1.3.6.1.4.1.5491.10.1.7.2 | ScalarrupsTestSpinLock | read-write | optional | A spin lock on the test subsystem. The spinlock is used as follows. Before starting a test, a manager-station should make sure that a test is not in progress a… |
| 1.3.6.1.4.1.5491.10.1.7.3 | ScalarrupsTestResultsSummary | read-only | optional | The results of the current or last UPS diagnostics test performed. The values for donePass(1), doneWarning(2), and doneError(3) indicate that the test complete… |
| 1.3.6.1.4.1.5491.10.1.7.4 | ScalarrupsTestResultsDetail | read-only | optional | Additional information about upsTestResultsSummary. If no additional information available, a zero length string is returned. |
| 1.3.6.1.4.1.5491.10.1.7.5 | ScalarrupsTestStartTime | read-only | optional | The value of sysUpTime at the time the test in progress was initiated, or, if no test is in progress, the time the previous test was initiated. If the value of… |
| 1.3.6.1.4.1.5491.10.1.7.6 | ScalarrupsTestElapsedTime | read-only | optional | The amount of time, in TimeTicks, since the test in progress was initiated, or, if no test is in progress, the previous test took to complete. If the value of … |
| 1.3.6.1.4.1.5491.10.1.7.7 | NoderupsWellKnownTests | |||
| 1.3.6.1.4.1.5491.10.1.7.7.1 | NoderupsTestNoTestsInitiated | |||
| 1.3.6.1.4.1.5491.10.1.7.7.2 | NoderupsTestAbortTestInProgress | |||
| 1.3.6.1.4.1.5491.10.1.7.7.3 | NoderupsTestGeneralSystemsTest | |||
| 1.3.6.1.4.1.5491.10.1.7.7.4 | NoderupsTestQuickBatteryTest | |||
| 1.3.6.1.4.1.5491.10.1.7.7.5 | NoderupsTestDeepBatteryCalibration | |||
| 1.3.6.1.4.1.5491.10.1.8 | NoderupsControl | |||
| 1.3.6.1.4.1.5491.10.1.8.1 | ScalarrupsShutdownType | read-write | mandatory | This object determines the nature of the action to be taken at the time when the countdown of the upsShutdownAfterDelay and upsRebootWithDuration objects reach… |
| 1.3.6.1.4.1.5491.10.1.8.2 | ScalarrupsShutdownAfterDelay | read-write | mandatory | Setting this object will shutdown (i.e., turn off) either the UPS output or the UPS system (as determined by the value of upsShutdownType at the time of shutdo… |
| 1.3.6.1.4.1.5491.10.1.8.3 | ScalarrupsStartupAfterDelay | read-write | mandatory | Setting this object will start the output after the indicated number of seconds, including starting the UPS, if necessary. Setting this object to 0 will cause … |
| 1.3.6.1.4.1.5491.10.1.8.4 | ScalarrupsRebootWithDuration | read-write | mandatory | Setting this object will immediately shutdown (i.e., turn off) either the UPS output or the UPS system (as determined by the value of upsShutdownType at the ti… |
| 1.3.6.1.4.1.5491.10.1.8.5 | ScalarrupsAutoRestart | read-write | mandatory | Setting this object to 'on' will cause the UPS system to restart after a shutdown if the shutdown occurred during a power loss as a result of either a upsShutd… |
| 1.3.6.1.4.1.5491.10.1.10 | NoderupsTemperature | |||
| 1.3.6.1.4.1.5491.10.1.10.1 | ScalarrupsSystemTemperature | read-only | mandatory | The present temperature. |
| 1.3.6.1.4.1.5491.10.1.10.2 | ScalarrupsPowerTemperature1 | read-only | mandatory | The present temperature. |
| 1.3.6.1.4.1.5491.10.1.10.3 | ScalarrupsPowerTemperature2 | read-only | mandatory | The present temperature. |
| 1.3.6.1.4.1.5491.10.1.10.4 | ScalarrupsPowerTemperature3 | read-only | mandatory | The present temperature. |
| 1.3.6.1.4.1.5491.10.1.10.5 | ScalarrupsChargerTemperature | read-only | mandatory | The present temperature. |
| 1.3.6.1.4.1.5491.10.1.10.6 | ScalarrupsBatteryPositiveTemperature | read-only | mandatory | The present temperature. |
| 1.3.6.1.4.1.5491.10.1.10.7 | ScalarrupsBatteryNegativeTemperature | read-only | mandatory | The present temperature. |
| 1.3.6.1.4.1.5491.10.1.10.8 | ScalarrupsBatteryExternalTemperature | read-only | mandatory | The present temperature. |
| 1.3.6.1.4.1.5491.10.1.20 | NoderupsMPS | |||
| 1.3.6.1.4.1.5491.10.1.20.1 | ScalarmpsAlarmGroupS | read-only | mandatory | The alarm group s. |
| 1.3.6.1.4.1.5491.10.1.20.2 | ScalarmpsAlarmGroupC | read-only | mandatory | The alarm group c. |
| 1.3.6.1.4.1.5491.10.1.20.3 | ScalarmpsAlarmGroupB | read-only | mandatory | The alarm group b. |
| 1.3.6.1.4.1.5491.10.1.20.4 | ScalarmpsAlarmGroupR | read-only | mandatory | The alarm group r. |
| 1.3.6.1.4.1.5491.10.1.20.5 | ScalarmpsAlarmGroupRI | read-only | mandatory | The alarm group RI. |
| 1.3.6.1.4.1.5491.10.1.20.6 | ScalarmpsAlarmGroupI | read-only | mandatory | The alarm group I. |
| 1.3.6.1.4.1.5491.10.1.20.7 | ScalarmpsAlarmGroupA0 | read-only | mandatory | The alarm group A0. |
| 1.3.6.1.4.1.5491.10.1.20.8 | ScalarmpsAlarmGroupA1 | read-only | mandatory | The alarm group A1. |
| 1.3.6.1.4.1.5491.10.1.20.9 | ScalarmpsAlarmGroupA2 | read-only | mandatory | The alarm group A2. |
| 1.3.6.1.4.1.5491.10.1.20.10 | ScalarmpsAlarmGroupA3 | read-only | mandatory | The alarm group A3. |
| 1.3.6.1.4.1.5491.10.1.20.11 | ScalarmpsAlarmGroupA4 | read-only | mandatory | The alarm group A4. |
| 1.3.6.1.4.1.5491.10.1.20.12 | ScalarmpsAlarmGroupA5 | read-only | mandatory | The alarm group A5. |
| 1.3.6.1.4.1.5491.10.1.21 | NoderupsMST | |||
| 1.3.6.1.4.1.5491.10.1.21.1 | ScalarmstWarningGroupW0W1 | read-only | mandatory | The anomaly group W0W1. |
| 1.3.6.1.4.1.5491.10.1.21.2 | ScalarmstAnomalyGroupA0A1 | read-only | mandatory | The anomaly group A0A1. |
| 1.3.6.1.4.1.5491.10.1.21.3 | ScalarmstAnomalyGroupA2A3 | read-only | mandatory | The anomaly group A2A3. |
| 1.3.6.1.4.1.5491.10.1.21.4 | ScalarmstAnomalyGroupA4A5 | read-only | mandatory | The anomaly group A4A5. |
| 1.3.6.1.4.1.5491.10.1.21.5 | ScalarmstFaultGroupF0F1 | read-only | mandatory | The fault group F0F1. |
| 1.3.6.1.4.1.5491.10.1.21.6 | ScalarmstFaultGroupF2F3 | read-only | mandatory | The fault group F2F3. |
| 1.3.6.1.4.1.5491.10.1.21.7 | ScalarmstFaultGroupF4F5 | read-only | mandatory | The fault group F4F5. |
| 1.3.6.1.4.1.5491.10.1.21.8 | ScalarmstLockGroupL0L1 | read-only | mandatory | The lock group L0L1. |
| 1.3.6.1.4.1.5491.10.1.21.9 | ScalarmstLockGroupL2L3 | read-only | mandatory | The lock group L2L3. |
| 1.3.6.1.4.1.5491.10.1.21.10 | ScalarmstLockGroupL4L5 | read-only | mandatory | The lock group L4L5. |
| 1.3.6.1.4.1.5491.10.1.21.11 | ScalarmstEventGroupE0E1 | read-only | mandatory | The event group E0E1. |
| 1.3.6.1.4.1.5491.10.1.22 | NoderupsMPW | |||
| 1.3.6.1.4.1.5491.10.1.22.1 | ScalarmpwSystemStatusGroup1 | read-only | mandatory | The system status group 1. |
| 1.3.6.1.4.1.5491.10.1.22.2 | ScalarmpwSystemStatusGroup2 | read-only | mandatory | The system status group 2. |
| 1.3.6.1.4.1.5491.10.1.22.3 | ScalarmpwSystemStatusGroup3 | read-only | mandatory | The system status group 3. |
| 1.3.6.1.4.1.5491.10.1.22.4 | ScalarmpwBypassModuleAlarmGroup | read-only | mandatory | The bypass module alarm group. |
| 1.3.6.1.4.1.5491.10.1.22.5 | ScalarmpwPowerModule1AlarmGroup | read-only | mandatory | The power module 1 alarm group. |
| 1.3.6.1.4.1.5491.10.1.22.6 | ScalarmpwPowerModule2AlarmGroup | read-only | mandatory | The power module 2 alarm group. |
| 1.3.6.1.4.1.5491.10.1.22.7 | ScalarmpwPowerModule3AlarmGroup | read-only | mandatory | The power module 3 alarm group. |
| 1.3.6.1.4.1.5491.10.1.22.8 | ScalarmpwPowerModule4AlarmGroup | read-only | mandatory | The power module 4 alarm group. |
| 1.3.6.1.4.1.5491.10.1.22.9 | ScalarmpwPowerModule5AlarmGroup | read-only | mandatory | The power module 5 alarm group. |
| 1.3.6.1.4.1.5491.10.1.22.10 | ScalarmpwPowerModule6AlarmGroup | read-only | mandatory | The power module 6 alarm group. |
| 1.3.6.1.4.1.5491.10.1.22.11 | ScalarmpwPowerModule7AlarmGroup | read-only | mandatory | The power module 7 alarm group. |
| 1.3.6.1.4.1.5491.10.1.22.12 | ScalarmpwBypassModuleStatus | read-only | mandatory | The bypass module status. |
| 1.3.6.1.4.1.5491.10.1.22.13 | ScalarmpwPowerModule1Status | read-only | mandatory | The status of power module 1. |
| 1.3.6.1.4.1.5491.10.1.22.14 | ScalarmpwPowerModule2Status | read-only | mandatory | The status of power module 2. |
| 1.3.6.1.4.1.5491.10.1.22.15 | ScalarmpwPowerModule3Status | read-only | mandatory | The status of power module 3. |
| 1.3.6.1.4.1.5491.10.1.22.16 | ScalarmpwPowerModule4Status | read-only | mandatory | The status of power module 4. |
| 1.3.6.1.4.1.5491.10.1.22.17 | ScalarmpwPowerModule5Status | read-only | mandatory | The status of power module 5. |
| 1.3.6.1.4.1.5491.10.1.22.18 | ScalarmpwPowerModule6Status | read-only | mandatory | The status of power module 6. |
| 1.3.6.1.4.1.5491.10.1.22.19 | ScalarmpwPowerModule7Status | read-only | mandatory | The status of power module 7. |
| 1.3.6.1.4.1.5491.10.1.22.20 | NodempwControl | |||
| 1.3.6.1.4.1.5491.10.1.22.20.1 | ScalarmpwCommandCode | read-write | mandatory | Command code. |
| 1.3.6.1.4.1.5491.10.1.22.20.2 | ScalarmpwShutdownDelay | read-write | mandatory | Shutdown delay. |
| 1.3.6.1.4.1.5491.10.1.22.20.3 | ScalarmpwRestoreDelay | read-write | mandatory | Restore delay. |
| 1.3.6.1.4.1.5491.10.1.22.20.4 | ScalarmpwModuleApplyCommand | read-write | mandatory | Module apply command |
| 1.3.6.1.4.1.5491.10.1.22.20.5 | ScalarmpwCommandResult | read-only | mandatory | Result of command. |
| 1.3.6.1.4.1.5491.10.2 | NoderupsTraps | |||
| 1.3.6.1.4.1.5491.10.2.1 | NoderupsTrapOnBattery | The UPS is operating on battery power. This trap is persistent and is resent at one minute intervals until the UPS either turns off or is no longer running on … | ||
| 1.3.6.1.4.1.5491.10.2.2 | NoderupsTrapTestCompleted | This trap is sent upon completion of a UPS diagnostic test. | ||
| 1.3.6.1.4.1.5491.10.2.3 | NoderupsTrapAlarmEntryAdded | This trap is sent each time an alarm is inserted into to the alarm table. It is sent on the insertion of all alarms except for rupsAlarmOnBattery and rupsAlarm… | ||
| 1.3.6.1.4.1.5491.10.2.4 | NoderupsTrapAlarmEntryRemoved | This trap is sent each time an alarm is removed from the alarm table. It is sent on the removal of all alarms except for rupsAlarmTestInProgress. |
Type Definitions
| Name | Syntax | Status | Description |
|---|---|---|---|
| NonNegativeInteger | INTEGER (0..2147483647) | current | This data type is a non-negative value. |
| PositiveInteger | INTEGER (1..2147483647) | current | This data type is a non-zero and non-negative value. |