RITTAL-CMC-TC-MIB

270 objects
No module-level DESCRIPTION found.
OIDNameAccessStatusDescription
1.3.6.1.4.1.2606Noderittal
1.3.6.1.4.1.2606.4NodecmcTc
1.3.6.1.4.1.2606.4.1NodealarmSensorUnit1Alarm of sensor unit 1
1.3.6.1.4.1.2606.4.1NodecmcTcMibRev
1.3.6.1.4.1.2606.4.1.1ScalarcmcTcMibMajRevread-onlymandatoryThe Major Revision level. A change in the major revision level represents a major change in the architecture of the MIB. A change in the major revision level m…
1.3.6.1.4.1.2606.4.1.2ScalarcmcTcMibMinRevread-onlymandatoryThe Minor Revision level. A change in the minor revision level may represent some minor additional support, no changes to any pre-existing information has occu…
1.3.6.1.4.1.2606.4.1.3ScalarcmcTcMibConditionread-onlymandatoryThe overall condition (status) of the system represented by this MIB. (2) OK (3) a minor problem, warning condition (yellow LED on CMC) (4) a major problem (re…
1.3.6.1.4.1.2606.4.2NodealarmSensorUnit2Alarm of sensor unit 2
1.3.6.1.4.1.2606.4.2NodecmcTcStatus
1.3.6.1.4.1.2606.4.2.1ScalarcmcTcStatusDeviceCMCread-onlymandatoryGeneral Status of CMC-TC unit itself (1) failed (2) OK
1.3.6.1.4.1.2606.4.2.2ScalarcmcTcUnitsConnectedread-onlymandatoryNumber of sensor units connected to the CMC, Port 1 to 4
1.3.6.1.4.1.2606.4.2.3NodecmcTcStatusSensorUnit1
1.3.6.1.4.1.2606.4.2.3.1ScalarcmcTcUnit1TypeOfDeviceread-onlymandatoryType of sensor unit connected to port 1
1.3.6.1.4.1.2606.4.2.3.2ScalarcmcTcUnit1Textread-writemandatoryDescriptional text for sensor unit connected to port 1
1.3.6.1.4.1.2606.4.2.3.3ScalarcmcTcUnit1Serialread-onlymandatorySerialnumber of sensor unit connected to port 1
1.3.6.1.4.1.2606.4.2.3.4ScalarcmcTcUnit1Statusread-onlymandatoryGeneral Status sensor unit connected to port 1 (1) OK (2) error, e. g. value overflow (3) configuration of sensor unit has changed, confirmation required (4) Q…
1.3.6.1.4.1.2606.4.2.3.5NodecmcTcStatusUnit1Sensors
1.3.6.1.4.1.2606.4.2.3.5.1ScalarcmcTcUnit1NumberOfSensorsread-onlymandatoryNumber of sensors connected to sensor unit 1
1.3.6.1.4.1.2606.4.2.3.5.2TablecmcTcUnit1SensorTablenot-accessiblemandatoryHeadline of sensor table
1.3.6.1.4.1.2606.4.2.3.5.2.1RowcmcTcUnit1SensorEntrynot-accessiblemandatoryEntries of sensor table
1.3.6.1.4.1.2606.4.2.3.5.2.1.1Columnunit1SensorIndexread-onlymandatoryIndex for the list of value entries. Its value ranges between 1 and the value of cmcTcUnit1NumberOfSensors.
1.3.6.1.4.1.2606.4.2.3.5.2.1.2Columnunit1SensorTyperead-onlymandatoryType of sensor which is connected to sensor unit 1 to sensor[unit1SensorIndex] 1: no sensor connected 2: sensor failure 3: value overflow 4: sensor type 1, acc…
1.3.6.1.4.1.2606.4.2.3.5.2.1.3Columnunit1SensorTextread-writemandatoryDescriptional text for each sensor (entry in the table)
1.3.6.1.4.1.2606.4.2.3.5.2.1.4Columnunit1SensorStatusread-onlymandatoryActual status of the sensor
1.3.6.1.4.1.2606.4.2.3.5.2.1.5Columnunit1SensorValueread-onlymandatoryValue of sensor
1.3.6.1.4.1.2606.4.2.3.5.2.1.6Columnunit1SensorSetHighread-writemandatoryValue for high setpoint of sensor
1.3.6.1.4.1.2606.4.2.3.5.2.1.7Columnunit1SensorSetLowread-writemandatoryValue for low setpoint of sensor, also used as alarm delay
1.3.6.1.4.1.2606.4.2.3.5.2.1.8Columnunit1SensorSetWarnread-writemandatoryValue for warning setpoint of sensor, also used as fan threshold
1.3.6.1.4.1.2606.4.2.3.5.2.1.9Columnunit1SensorHysteresisread-writemandatory% -Value for hysteresis for High, Low and Warning, input in % from actual setpoint
1.3.6.1.4.1.2606.4.2.3.5.2.1.10Columnunit1SensorDisplayFactorread-onlymandatoryFactor of sensor value and setpoints, devide actual value with this value, e. g. factor = 10: sensor value = 100, actual value = 10.0
1.3.6.1.4.1.2606.4.2.3.5.2.1.11Columnunit1SensorScaleStartread-writemandatoryValue for start value for scaling of 0..100% (4..20mA) sensor, example: acutal range of value of 4..20mA sensor is from 10 to 60A, then this variable is set to…
1.3.6.1.4.1.2606.4.2.3.5.2.1.12Columnunit1SensorScaleEndread-writemandatoryValue for end value for scaling of 0..100% (4..20mA) sensor, example: acutal range of value of 4..20mA sensor is from 10 to 60A, then this variable is set to 6…
1.3.6.1.4.1.2606.4.2.3.5.2.1.13Columnunit1SensorUnitread-writemandatoryUnit for 0..100% (4..20mA) sensor, example: acutal range of value of 4..20mA sensor is from 10 to 60A, then this variable is set to 'A'
1.3.6.1.4.1.2606.4.2.3.5.2.1.14Columnunit1SensorInforead-onlymandatoryAdditional information to the sensor, e. g. Serialnumber, Signal Quality..
1.3.6.1.4.1.2606.4.2.3.6NodecmcTcStatusUnit1Outputs
1.3.6.1.4.1.2606.4.2.3.6.1ScalarcmcTcUnit1NumberOfOutputsread-onlymandatoryNumber of outputs available on sensor unit 1
1.3.6.1.4.1.2606.4.2.3.6.2TablecmcTcUnit1OutputTablenot-accessiblemandatoryHeadline of output table
1.3.6.1.4.1.2606.4.2.3.6.2.1RowcmcTcUnit1OutputEntrynot-accessiblemandatoryEntries of output table
1.3.6.1.4.1.2606.4.2.3.6.2.1.1Columnunit1OutputIndexread-onlymandatoryIndex for the list of output entries. Its value ranges between 1 and the value of cmcTcUnit1NumberOfOutputs.
1.3.6.1.4.1.2606.4.2.3.6.2.1.2Columnunit1OutputTyperead-onlymandatoryType of output which is connected to sensor unit 1 to output[unit1OutputIndex] 1: no output connected 2: output failure 3: value overflow 4: output type 1, doo…
1.3.6.1.4.1.2606.4.2.3.6.2.1.3Columnunit1OutputTextread-writemandatoryDescriptional text for each output (entry in the table)
1.3.6.1.4.1.2606.4.2.3.6.2.1.4Columnunit1OutputStatusread-writemandatoryActual status of the output
1.3.6.1.4.1.2606.4.2.3.6.2.1.5Columnunit1OutputValueread-writemandatoryValue for output
1.3.6.1.4.1.2606.4.2.3.6.2.1.6Columnunit1OutputSetread-writemandatoryCommand for output
1.3.6.1.4.1.2606.4.2.3.6.2.1.7Columnunit1OutputConfigread-writemandatoryConfiguration for output 1: disable remote control (e.g. keypad) 2: enable remote control
1.3.6.1.4.1.2606.4.2.3.6.2.1.8Columnunit1OutputDelayread-writemandatoryUnsigned Value for delay, after this time the output will fall into the previous state
1.3.6.1.4.1.2606.4.2.3.6.2.1.9Columnunit1OutputTimeoutActionread-writemandatoryState for output if timeout (RS422) occurs
1.3.6.1.4.1.2606.4.2.3.7NodecmcTcStatusUnit1Msg
1.3.6.1.4.1.2606.4.2.3.7.1ScalarcmcTcUnit1NumberOfMsgsread-onlymandatoryNumber of messages that can be created with sensor unit 1
1.3.6.1.4.1.2606.4.2.3.7.2TablecmcTcUnit1MsgTablenot-accessiblemandatoryHeadline of message table
1.3.6.1.4.1.2606.4.2.3.7.2.1RowcmcTcUnit1MsgEntrynot-accessiblemandatoryEntries of message table
1.3.6.1.4.1.2606.4.2.3.7.2.1.1Columnunit1MsgIndexread-onlymandatoryIndex for the list of message entries. Its value ranges between 1 and the value of cmcTcUnit1NumberOfMsgs.
1.3.6.1.4.1.2606.4.2.3.7.2.1.2Columnunit1MsgTextread-writemandatoryDescriptional text for each message (entry in the table)
1.3.6.1.4.1.2606.4.2.3.7.2.1.3Columnunit1MsgStatusread-onlymandatoryActual message status 1: not available 2: configuration has changed (sensor new, changed, lost) 3: error 4: OK 5: alarm, e.g. smoke, vibration... 6: warning of…
1.3.6.1.4.1.2606.4.2.3.7.2.1.4Columnunit1MsgRelayread-writemandatorySetup of Alarm relay for this message/alarm 1: no switching of alarm relay 2: switching of alarm relay
1.3.6.1.4.1.2606.4.2.3.7.2.1.5Columnunit1MsgBeeperread-writemandatorySetup of Alarm beeper for this alarm 1: no audible alarm 2: audible alarm
1.3.6.1.4.1.2606.4.2.3.7.2.1.6Columnunit1MsgTrap1read-writemandatoryTrap receiver 1 activated
1.3.6.1.4.1.2606.4.2.3.7.2.1.7Columnunit1MsgTrap2read-writemandatoryTrap receiver 2 activated
1.3.6.1.4.1.2606.4.2.3.7.2.1.8Columnunit1MsgTrap3read-writemandatoryTrap receiver 3 activated
1.3.6.1.4.1.2606.4.2.3.7.2.1.9Columnunit1MsgTrap4read-writemandatoryTrap receiver 4 and Event Logging activated
1.3.6.1.4.1.2606.4.2.3.7.2.1.10Columnunit1MsgQuitread-writemandatoryReset of this alarm 1: auto 2: manual, alarm needs confirmation, e. g. with 'C' key
1.3.6.1.4.1.2606.4.2.3.7.2.1.11Columnunit1MsgDelayread-writemandatoryDelay of alarm condition
1.3.6.1.4.1.2606.4.2.4NodecmcTcStatusSensorUnit2
1.3.6.1.4.1.2606.4.2.4.1ScalarcmcTcUnit2TypeOfDeviceread-onlymandatoryType of sensor unit connected to port 2
1.3.6.1.4.1.2606.4.2.4.2ScalarcmcTcUnit2Textread-writemandatoryDescriptional text for sensor unit connected to port 2
1.3.6.1.4.1.2606.4.2.4.3ScalarcmcTcUnit2Serialread-onlymandatorySerialnumber of sensor unit connected to port 2
1.3.6.1.4.1.2606.4.2.4.4ScalarcmcTcUnit2Statusread-onlymandatoryGeneral Status sensor unit connected to port 2 (1) OK (2) error (3) configuration of sensor unit has changed, confirmation required (4) Quit from sensor unit t…
1.3.6.1.4.1.2606.4.2.4.5NodecmcTcStatusUnit2Sensors
1.3.6.1.4.1.2606.4.2.4.5.1ScalarcmcTcUnit2NumberOfSensorsread-onlymandatoryNumber of sensors connected to sensor unit 2
1.3.6.1.4.1.2606.4.2.4.5.2TablecmcTcUnit2SensorTablenot-accessiblemandatoryHeadline of sensor table
1.3.6.1.4.1.2606.4.2.4.5.2.1RowcmcTcUnit2SensorEntrynot-accessiblemandatoryEntries of sensor table
1.3.6.1.4.1.2606.4.2.4.5.2.1.1Columnunit2SensorIndexread-onlymandatoryIndex for the list of value entries. Its value ranges between 1 and the value of cmcTcUnit2NumberOfSensors.
1.3.6.1.4.1.2606.4.2.4.5.2.1.2Columnunit2SensorTyperead-onlymandatoryType of sensor which is connected to sensor unit 2 to sensor[unit2SensorIndex] 1: no sensor connected 2: sensor failure 3: value overflow 4: sensor type 1, acc…
1.3.6.1.4.1.2606.4.2.4.5.2.1.3Columnunit2SensorTextread-writemandatoryDescriptional text for each sensor (entry in the table)
1.3.6.1.4.1.2606.4.2.4.5.2.1.4Columnunit2SensorStatusread-onlymandatoryActual status of the sensor
1.3.6.1.4.1.2606.4.2.4.5.2.1.5Columnunit2SensorValueread-onlymandatoryValue of sensor
1.3.6.1.4.1.2606.4.2.4.5.2.1.6Columnunit2SensorSetHighread-writemandatoryValue for high setpoint of sensor
1.3.6.1.4.1.2606.4.2.4.5.2.1.7Columnunit2SensorSetLowread-writemandatoryValue for low setpoint of sensor, also used as alarm delay
1.3.6.1.4.1.2606.4.2.4.5.2.1.8Columnunit2SensorSetWarnread-writemandatoryValue for warning setpoint of sensor, also used as fan threshold
1.3.6.1.4.1.2606.4.2.4.5.2.1.9Columnunit2SensorHysteresisread-writemandatory% -Value for hysteresis for High, Low and Warning, input in % from actual setpoint
1.3.6.1.4.1.2606.4.2.4.5.2.1.10Columnunit2SensorDisplayFactorread-onlymandatoryFactor of sensor value and setpoints, devide actual value with this value, e. g. factor = 10: sensor value = 100, actual value = 10.0
1.3.6.1.4.1.2606.4.2.4.5.2.1.11Columnunit2SensorScaleStartread-writemandatoryValue for start value for scaling of 0..100% (4..20mA) sensor, example: acutal range of value of 4..20mA sensor is from 10 to 60A, then this variable is set to…
1.3.6.1.4.1.2606.4.2.4.5.2.1.12Columnunit2SensorScaleEndread-writemandatoryValue for end value for scaling of 0..100% (4..20mA) sensor, example: acutal range of value of 4..20mA sensor is from 10 to 60A, then this variable is set to 6…
1.3.6.1.4.1.2606.4.2.4.5.2.1.13Columnunit2SensorUnitread-writemandatoryUnit for 0..100% (4..20mA) sensor, example: acutal range of value of 4..20mA sensor is from 10 to 60A, then this variable is set to 'A'
1.3.6.1.4.1.2606.4.2.4.5.2.1.14Columnunit2SensorInforead-onlymandatoryAdditional information to the sensor, e. g. Serialnumber, Signal Quality..
1.3.6.1.4.1.2606.4.2.4.6NodecmcTcStatusUnit2Outputs
1.3.6.1.4.1.2606.4.2.4.6.1ScalarcmcTcUnit2NumberOfOutputsread-onlymandatoryNumber of outputs available on sensor unit 2
1.3.6.1.4.1.2606.4.2.4.6.2TablecmcTcUnit2OutputTablenot-accessiblemandatoryHeadline of output table
1.3.6.1.4.1.2606.4.2.4.6.2.1RowcmcTcUnit2OutputEntrynot-accessiblemandatoryEntries of output table
1.3.6.1.4.1.2606.4.2.4.6.2.1.1Columnunit2OutputIndexread-onlymandatoryIndex for the list of output entries. Its value ranges between 1 and the value of cmcTcUnit2NumberOfOutputs.
1.3.6.1.4.1.2606.4.2.4.6.2.1.2Columnunit2OutputTyperead-onlymandatoryType of output which is connected to sensor unit 2 to output[unit2OutputIndex] 1: no output connected 2: output failure 3: value overflow 4: output type 1, doo…
1.3.6.1.4.1.2606.4.2.4.6.2.1.3Columnunit2OutputTextread-writemandatoryDescriptional text for each output (entry in the table)
1.3.6.1.4.1.2606.4.2.4.6.2.1.4Columnunit2OutputStatusread-writemandatoryActual status of the output
1.3.6.1.4.1.2606.4.2.4.6.2.1.5Columnunit2OutputValueread-writemandatorySigned value for output
1.3.6.1.4.1.2606.4.2.4.6.2.1.6Columnunit2OutputSetread-writemandatoryCommand for output
1.3.6.1.4.1.2606.4.2.4.6.2.1.7Columnunit2OutputConfigread-writemandatoryConfiguration for output 1: disable remote control (e.g. keypad) 2: enable remote control
1.3.6.1.4.1.2606.4.2.4.6.2.1.8Columnunit2OutputDelayread-writemandatoryUnsigned Value for delay, after this time the output will fall into the previous state
1.3.6.1.4.1.2606.4.2.4.6.2.1.9Columnunit2OutputTimeoutActionread-writemandatoryState for output if timeout (RS422) occurs
1.3.6.1.4.1.2606.4.2.4.7NodecmcTcStatusUnit2Msg
1.3.6.1.4.1.2606.4.2.4.7.1ScalarcmcTcUnit2NumberOfMsgsread-onlymandatoryNumber of alarms that can be created with sensor unit 2
1.3.6.1.4.1.2606.4.2.4.7.2TablecmcTcUnit2MsgTablenot-accessiblemandatoryHeadline of message table
1.3.6.1.4.1.2606.4.2.4.7.2.1RowcmcTcUnit2MsgEntrynot-accessiblemandatoryEntries of message table
1.3.6.1.4.1.2606.4.2.4.7.2.1.1Columnunit2MsgIndexread-onlymandatoryIndex for the list of alarm entries. Its value ranges between 1 and the value of cmcTcUnit2NumberOfMsgs.
1.3.6.1.4.1.2606.4.2.4.7.2.1.2Columnunit2MsgTextread-writemandatoryDescriptional text for each message (entry in the table)
1.3.6.1.4.1.2606.4.2.4.7.2.1.3Columnunit2MsgStatusread-onlymandatoryActual message status 1: not available 2: configuration has changed (sensor new, changed, lost) 3: error 4: OK 5: alarm, e.g. smoke, vibration... 6: warning of…
1.3.6.1.4.1.2606.4.2.4.7.2.1.4Columnunit2MsgRelayread-writemandatorySetup of Alarm relay for this alarm 2: no switching of alarm relay 1: switching of alarm relay
1.3.6.1.4.1.2606.4.2.4.7.2.1.5Columnunit2MsgBeeperread-writemandatorySetup of Alarm beeper for this alarm 2: no audible alarm 1: audible alarm
1.3.6.1.4.1.2606.4.2.4.7.2.1.6Columnunit2MsgTrap1read-writemandatoryTrap receiver 1 activated
1.3.6.1.4.1.2606.4.2.4.7.2.1.7Columnunit2MsgTrap2read-writemandatoryTrap receiver 2 activated
1.3.6.1.4.1.2606.4.2.4.7.2.1.8Columnunit2MsgTrap3read-writemandatoryTrap receiver 3 activated
1.3.6.1.4.1.2606.4.2.4.7.2.1.9Columnunit2MsgTrap4read-writemandatoryTrap receiver 4 and Event Logging activated
1.3.6.1.4.1.2606.4.2.4.7.2.1.10Columnunit2MsgQuitread-writemandatoryReset of this alarm 1: auto 2: manual, alarm needs confirmation, e. g. with 'C' key
1.3.6.1.4.1.2606.4.2.4.7.2.1.11Columnunit2MsgDelayread-writemandatoryDelay of alarm condition
1.3.6.1.4.1.2606.4.2.5NodecmcTcStatusSensorUnit3
1.3.6.1.4.1.2606.4.2.5.1ScalarcmcTcUnit3TypeOfDeviceread-onlymandatoryType of sensor unit connected to port 3
1.3.6.1.4.1.2606.4.2.5.2ScalarcmcTcUnit3Textread-writemandatoryDescriptional text for sensor unit connected to port 3
1.3.6.1.4.1.2606.4.2.5.3ScalarcmcTcUnit3Serialread-onlymandatorySerialnumber of sensor unit connected to port 3
1.3.6.1.4.1.2606.4.2.5.4ScalarcmcTcUnit3Statusread-onlymandatoryGeneral Status sensor unit connected to port 3 (1) OK (2) error, e. g. value overflow (3) configuration of sensor unit has changed, confirmation required (4) Q…
1.3.6.1.4.1.2606.4.2.5.5NodecmcTcStatusUnit3Sensors
1.3.6.1.4.1.2606.4.2.5.5.1ScalarcmcTcUnit3NumberOfSensorsread-onlymandatoryNumber of sensors connected to sensor unit 3
1.3.6.1.4.1.2606.4.2.5.5.2TablecmcTcUnit3SensorTablenot-accessiblemandatoryHeadline of sensor table
1.3.6.1.4.1.2606.4.2.5.5.2.1RowcmcTcUnit3SensorEntrynot-accessiblemandatoryEntries of sensor table
1.3.6.1.4.1.2606.4.2.5.5.2.1.1Columnunit3SensorIndexread-onlymandatoryIndex for the list of value entries. Its value ranges between 1 and the value of cmcTcUnit3NumberOfSensors.
1.3.6.1.4.1.2606.4.2.5.5.2.1.2Columnunit3SensorTyperead-onlymandatoryType of sensor which is connected to sensor unit 3 to sensor[unit3SensorIndex] 1: no sensor connected 2: sensor failure 3: value overflow 4: sensor type 1, acc…
1.3.6.1.4.1.2606.4.2.5.5.2.1.3Columnunit3SensorTextread-writemandatoryDescriptional text for each sensor (entry in the table)
1.3.6.1.4.1.2606.4.2.5.5.2.1.4Columnunit3SensorStatusread-onlymandatoryActual status of the sensor
1.3.6.1.4.1.2606.4.2.5.5.2.1.5Columnunit3SensorValueread-onlymandatoryValue of sensor
1.3.6.1.4.1.2606.4.2.5.5.2.1.6Columnunit3SensorSetHighread-writemandatoryValue for high setpoint of sensor
1.3.6.1.4.1.2606.4.2.5.5.2.1.7Columnunit3SensorSetLowread-writemandatoryValue for low setpoint of sensor
1.3.6.1.4.1.2606.4.2.5.5.2.1.8Columnunit3SensorSetWarnread-writemandatoryValue for warning setpoint of sensor, also used as fan threshold
1.3.6.1.4.1.2606.4.2.5.5.2.1.9Columnunit3SensorHysteresisread-writemandatory% -Value for hysteresis for High, Low and Warning, input in % from actual setpoint
1.3.6.1.4.1.2606.4.2.5.5.2.1.10Columnunit3SensorDisplayFactorread-onlymandatoryFactor of sensor value and setpoints, devide actual value with this value, e. g. factor = 10: sensor value = 100, actual value = 10.0
1.3.6.1.4.1.2606.4.2.5.5.2.1.11Columnunit3SensorScaleStartread-writemandatoryValue for start value for scaling of 0..100% (4..20mA) sensor, example: acutal range of value of 4..20mA sensor is from 10 to 60A, then this variable is set to…
1.3.6.1.4.1.2606.4.2.5.5.2.1.12Columnunit3SensorScaleEndread-writemandatoryValue for end value for scaling of 0..100% (4..20mA) sensor, example: acutal range of value of 4..20mA sensor is from 10 to 60A, then this variable is set to 6…
1.3.6.1.4.1.2606.4.2.5.5.2.1.13Columnunit3SensorUnitread-writemandatoryUnit for 0..100% (4..20mA) sensor, example: acutal range of value of 4..20mA sensor is from 10 to 60A, then this variable is set to 'A'
1.3.6.1.4.1.2606.4.2.5.5.2.1.14Columnunit3SensorInforead-onlymandatoryAdditional information to the sensor, e. g. Serialnumber, Signal Quality..
1.3.6.1.4.1.2606.4.2.5.6NodecmcTcStatusUnit3Outputs
1.3.6.1.4.1.2606.4.2.5.6.1ScalarcmcTcUnit3NumberOfOutputsread-onlymandatoryNumber of outputs available on sensor unit 3
1.3.6.1.4.1.2606.4.2.5.6.2TablecmcTcUnit3OutputTablenot-accessiblemandatoryHeadline of output table
1.3.6.1.4.1.2606.4.2.5.6.2.1RowcmcTcUnit3OutputEntrynot-accessiblemandatoryEntries of output table
1.3.6.1.4.1.2606.4.2.5.6.2.1.1Columnunit3OutputIndexread-onlymandatoryIndex for the list of output entries. Its value ranges between 1 and the value of cmcTcUnit3NumberOfOutputs.
1.3.6.1.4.1.2606.4.2.5.6.2.1.2Columnunit3OutputTyperead-onlymandatoryType of output which is connected to sensor unit 3 to output[unit3OutputIndex] 1: no output connected 2: output failure 3: value overflow 4: output type 1, doo…
1.3.6.1.4.1.2606.4.2.5.6.2.1.3Columnunit3OutputTextread-writemandatoryDescriptional text for each output (entry in the table)
1.3.6.1.4.1.2606.4.2.5.6.2.1.4Columnunit3OutputStatusread-writemandatoryActual status of the output
1.3.6.1.4.1.2606.4.2.5.6.2.1.5Columnunit3OutputValueread-writemandatoryValue for output
1.3.6.1.4.1.2606.4.2.5.6.2.1.6Columnunit3OutputSetread-writemandatoryCommand for output
1.3.6.1.4.1.2606.4.2.5.6.2.1.7Columnunit3OutputConfigread-writemandatoryConfiguration for output 1: disable remote control (e.g. keypad) 2: enable remote control
1.3.6.1.4.1.2606.4.2.5.6.2.1.8Columnunit3OutputDelayread-writemandatoryUnsigned Value for delay, after this time the output will fall into the previous state
1.3.6.1.4.1.2606.4.2.5.6.2.1.9Columnunit3OutputTimeoutActionread-writemandatoryState for output if timeout (RS422) occurs
1.3.6.1.4.1.2606.4.2.5.7NodecmcTcStatusUnit3Msg
1.3.6.1.4.1.2606.4.2.5.7.1ScalarcmcTcUnit3NumberOfMsgsread-onlymandatoryNumber of alarms that can be created with sensor unit 3
1.3.6.1.4.1.2606.4.2.5.7.2TablecmcTcUnit3MsgTablenot-accessiblemandatoryHeadline of message table
1.3.6.1.4.1.2606.4.2.5.7.2.1RowcmcTcUnit3MsgEntrynot-accessiblemandatoryEntries of message table
1.3.6.1.4.1.2606.4.2.5.7.2.1.1Columnunit3MsgIndexread-onlymandatoryIndex for the list of alarm entries. Its value ranges between 1 and the value of cmcTcUnit3NumberOfMsgs.
1.3.6.1.4.1.2606.4.2.5.7.2.1.2Columnunit3MsgTextread-writemandatoryDescriptional text for each message (entry in the table)
1.3.6.1.4.1.2606.4.2.5.7.2.1.3Columnunit3MsgStatusread-onlymandatoryActual message status 1: not available 2: configuration has changed (sensor new, changed, lost) 3: error 4: OK 5: alarm, e.g. smoke, vibration... 6: warning of…
1.3.6.1.4.1.2606.4.2.5.7.2.1.4Columnunit3MsgRelayread-writemandatorySetup of Alarm relay for this alarm 1: no switching of alarm relay 2: switching of alarm relay
1.3.6.1.4.1.2606.4.2.5.7.2.1.5Columnunit3MsgBeeperread-writemandatorySetup of Alarm beeper for this alarm 1: no audible alarm 2: audible alarm
1.3.6.1.4.1.2606.4.2.5.7.2.1.6Columnunit3MsgTrap1read-writemandatoryTrap receiver 1 activated
1.3.6.1.4.1.2606.4.2.5.7.2.1.7Columnunit3MsgTrap2read-writemandatoryTrap receiver 2 activated
1.3.6.1.4.1.2606.4.2.5.7.2.1.8Columnunit3MsgTrap3read-writemandatoryTrap receiver 3 activated
1.3.6.1.4.1.2606.4.2.5.7.2.1.9Columnunit3MsgTrap4read-writemandatoryTrap receiver 4 and Event Logging activated
1.3.6.1.4.1.2606.4.2.5.7.2.1.10Columnunit3MsgQuitread-writemandatoryReset of this alarm 1: auto 2: manual, alarm needs confirmation, e. g. with 'C' key
1.3.6.1.4.1.2606.4.2.5.7.2.1.11Columnunit3MsgDelayread-writemandatoryDelay of alarm condition
1.3.6.1.4.1.2606.4.2.6NodecmcTcStatusSensorUnit4
1.3.6.1.4.1.2606.4.2.6.1ScalarcmcTcUnit4TypeOfDeviceread-onlymandatoryType of sensor unit connected to port 4
1.3.6.1.4.1.2606.4.2.6.2ScalarcmcTcUnit4Textread-writemandatoryDescriptional text for sensor unit connected to port 4
1.3.6.1.4.1.2606.4.2.6.3ScalarcmcTcUnit4Serialread-onlymandatorySerialnumber of sensor unit connected to port 4
1.3.6.1.4.1.2606.4.2.6.4ScalarcmcTcUnit4Statusread-onlymandatoryGeneral Status sensor unit connected to port 4 (1) OK (2) error, e. g. value overflow (3) configuration of sensor unit has changed, confirmation required (4) Q…
1.3.6.1.4.1.2606.4.2.6.5NodecmcTcStatusUnit4Sensors
1.3.6.1.4.1.2606.4.2.6.5.1ScalarcmcTcUnit4NumberOfSensorsread-onlymandatoryNumber of sensors connected to sensor unit 4
1.3.6.1.4.1.2606.4.2.6.5.2TablecmcTcUnit4SensorTablenot-accessiblemandatoryHeadline of sensor table
1.3.6.1.4.1.2606.4.2.6.5.2.1RowcmcTcUnit4SensorEntrynot-accessiblemandatoryEntries of sensor table
1.3.6.1.4.1.2606.4.2.6.5.2.1.1Columnunit4SensorIndexread-onlymandatoryIndex for the list of value entries. Its value ranges between 1 and the value of cmcTcUnit4NumberOfSensors.
1.3.6.1.4.1.2606.4.2.6.5.2.1.2Columnunit4SensorTyperead-onlymandatoryType of sensor which is connected to sensor unit 4 to sensor[unit4SensorIndex] 1: no sensor connected 2: sensor failure 3: value overflow 4: sensor type 1, acc…
1.3.6.1.4.1.2606.4.2.6.5.2.1.3Columnunit4SensorTextread-writemandatoryDescriptional text for each sensor (entry in the table)
1.3.6.1.4.1.2606.4.2.6.5.2.1.4Columnunit4SensorStatusread-onlymandatoryActual status of the sensor
1.3.6.1.4.1.2606.4.2.6.5.2.1.5Columnunit4SensorValueread-onlymandatoryValue of sensor
1.3.6.1.4.1.2606.4.2.6.5.2.1.6Columnunit4SensorSetHighread-writemandatoryValue for high setpoint of sensor
1.3.6.1.4.1.2606.4.2.6.5.2.1.7Columnunit4SensorSetLowread-writemandatoryValue for low setpoint of sensor
1.3.6.1.4.1.2606.4.2.6.5.2.1.8Columnunit4SensorSetWarnread-writemandatoryValue for warning setpoint of sensor, also used as fan threshold
1.3.6.1.4.1.2606.4.2.6.5.2.1.9Columnunit4SensorHysteresisread-writemandatory% -Value for hysteresis for High, Low and Warning, input in % from actual setpoint
1.3.6.1.4.1.2606.4.2.6.5.2.1.10Columnunit4SensorDisplayFactorread-onlymandatoryFactor of sensor value and setpoints, devide actual value with this value, e. g. factor = 10: sensor value = 100, actual value = 10.0
1.3.6.1.4.1.2606.4.2.6.5.2.1.11Columnunit4SensorScaleStartread-writemandatoryValue for start value for scaling of 0..100% (4..20mA) sensor, example: acutal range of value of 4..20mA sensor is from 10 to 60A, then this variable is set to…
1.3.6.1.4.1.2606.4.2.6.5.2.1.12Columnunit4SensorScaleEndread-writemandatoryValue for end value for scaling of 0..100% (4..20mA) sensor, example: acutal range of value of 4..20mA sensor is from 10 to 60A, then this variable is set to 6…
1.3.6.1.4.1.2606.4.2.6.5.2.1.13Columnunit4SensorUnitread-writemandatoryUnit for 0..100% (4..20mA) sensor, example: acutal range of value of 4..20mA sensor is from 10 to 60A, then this variable is set to 'A'
1.3.6.1.4.1.2606.4.2.6.5.2.1.14Columnunit4SensorInforead-onlymandatoryAdditional information to the sensor, e. g. Serialnumber, Signal Quality..
1.3.6.1.4.1.2606.4.2.6.6NodecmcTcStatusUnit4Outputs
1.3.6.1.4.1.2606.4.2.6.6.1ScalarcmcTcUnit4NumberOfOutputsread-onlymandatoryNumber of outputs available on sensor unit 4
1.3.6.1.4.1.2606.4.2.6.6.2TablecmcTcUnit4OutputTablenot-accessiblemandatoryHeadline of output table
1.3.6.1.4.1.2606.4.2.6.6.2.1RowcmcTcUnit4OutputEntrynot-accessiblemandatoryEntries of output table
1.3.6.1.4.1.2606.4.2.6.6.2.1.1Columnunit4OutputIndexread-onlymandatoryIndex for the list of output entries. Its value ranges between 1 and the value of cmcTcUnit4NumberOfOutputs.
1.3.6.1.4.1.2606.4.2.6.6.2.1.2Columnunit4OutputTyperead-onlymandatoryType of output which is connected to sensor unit 4 to output[unit4OutputIndex] 1: no output connected 2: output failure 3: value overflow 4: output type 1, doo…
1.3.6.1.4.1.2606.4.2.6.6.2.1.3Columnunit4OutputTextread-writemandatoryDescriptional text for each output (entry in the table)
1.3.6.1.4.1.2606.4.2.6.6.2.1.4Columnunit4OutputStatusread-writemandatoryActual status of the output
1.3.6.1.4.1.2606.4.2.6.6.2.1.5Columnunit4OutputValueread-writemandatoryValue for output
1.3.6.1.4.1.2606.4.2.6.6.2.1.6Columnunit4OutputSetread-writemandatoryCommand for output
1.3.6.1.4.1.2606.4.2.6.6.2.1.7Columnunit4OutputConfigread-writemandatoryConfiguration for output 1: disable remote control (e.g. keypad) 2: enable remote control
1.3.6.1.4.1.2606.4.2.6.6.2.1.8Columnunit4OutputDelayread-writemandatoryUnsigned Value for delay, after this time the output will fall into the previous state
1.3.6.1.4.1.2606.4.2.6.6.2.1.9Columnunit4OutputTimeoutActionread-writemandatoryState for output if timeout (RS422) occurs
1.3.6.1.4.1.2606.4.2.6.7NodecmcTcStatusUnit4Msg
1.3.6.1.4.1.2606.4.2.6.7.1ScalarcmcTcUnit4NumberOfMsgsread-onlymandatoryNumber of alarms that can be created with sensor unit 4
1.3.6.1.4.1.2606.4.2.6.7.2TablecmcTcUnit4MsgTablenot-accessiblemandatoryHeadline of message table
1.3.6.1.4.1.2606.4.2.6.7.2.1RowcmcTcUnit4MsgEntrynot-accessiblemandatoryEntries of message table
1.3.6.1.4.1.2606.4.2.6.7.2.1.1Columnunit4MsgIndexread-onlymandatoryIndex for the list of alarm entries. Its value ranges between 1 and the value of cmcTcUnit4NumberOfMsgs.
1.3.6.1.4.1.2606.4.2.6.7.2.1.2Columnunit4MsgTextread-writemandatoryDescriptional text for each message (entry in the table)
1.3.6.1.4.1.2606.4.2.6.7.2.1.3Columnunit4MsgStatusread-onlymandatoryActual message status 1: not available 2: configuration has changed (sensor new, changed, lost) 3: error 4: OK 5: alarm, e.g. smoke, vibration... 6: warning of…
1.3.6.1.4.1.2606.4.2.6.7.2.1.4Columnunit4MsgRelayread-writemandatorySetup of Alarm relay for this alarm 1: no switching of alarm relay 2: switching of alarm relay
1.3.6.1.4.1.2606.4.2.6.7.2.1.5Columnunit4MsgBeeperread-writemandatorySetup of Alarm beeper for this alarm 1: no audible alarm 2: audible alarm
1.3.6.1.4.1.2606.4.2.6.7.2.1.6Columnunit4MsgTrap1read-writemandatoryTrap receiver 1 activated
1.3.6.1.4.1.2606.4.2.6.7.2.1.7Columnunit4MsgTrap2read-writemandatoryTrap receiver 2 activated
1.3.6.1.4.1.2606.4.2.6.7.2.1.8Columnunit4MsgTrap3read-writemandatoryTrap receiver 3 activated
1.3.6.1.4.1.2606.4.2.6.7.2.1.9Columnunit4MsgTrap4read-writemandatoryTrap receiver 4 and Event Logging activated
1.3.6.1.4.1.2606.4.2.6.7.2.1.10Columnunit4MsgQuitread-writemandatoryReset of this alarm 1: auto 2: manual, alarm needs confirmation, e. g. with 'C' key
1.3.6.1.4.1.2606.4.2.6.7.2.1.11Columnunit4MsgDelayread-writemandatoryDelay of alarm condition
1.3.6.1.4.1.2606.4.2.7NodecmcTcStatusExtUnit
1.3.6.1.4.1.2606.4.2.7.1ScalarcmcTcValuesRelayread-writemandatorySetup of Alarm relay for alarm ext. unit(s) 1: no switching of alarm relay 2: switching of alarm relay
1.3.6.1.4.1.2606.4.2.7.2ScalarcmcTcValuesBeeperread-writemandatorySetup of Alarm beeper for alarm ext. unit(s) 1: no audible alarm 2: audible alarm
1.3.6.1.4.1.2606.4.2.7.3ScalarcmcTcValuesTrap1read-writemandatoryTrap receiver 1 activated
1.3.6.1.4.1.2606.4.2.7.4ScalarcmcTcValuesTrap2read-writemandatoryTrap receiver 2 activated
1.3.6.1.4.1.2606.4.2.7.5ScalarcmcTcValuesTrap3read-writemandatoryTrap receiver 3 activated
1.3.6.1.4.1.2606.4.2.7.6ScalarcmcTcValuesTrap4read-writemandatoryTrap receiver 4 and Event Logging activated
1.3.6.1.4.1.2606.4.2.7.7ScalarcmcTcNumberOfValuesread-onlymandatoryNumber of values availabel on extension units connected to the CMC
1.3.6.1.4.1.2606.4.2.7.8TablecmcTcValuesTablenot-accessiblemandatoryHeadline of values-table
1.3.6.1.4.1.2606.4.2.7.8.1RowcmcTcValuesEntrynot-accessiblemandatoryEntries of values-table
1.3.6.1.4.1.2606.4.2.7.8.1.1ColumnvaluesIndexread-onlymandatoryIndex for the list of value entries. Its value ranges between 1 and the value of cmcTcNumberOfValues.
1.3.6.1.4.1.2606.4.2.7.8.1.2ColumnvaluesTextread-writemandatoryDescriptional text for each value (entry in the table) of the extension card
1.3.6.1.4.1.2606.4.2.7.8.1.3ColumnvaluesStatusread-onlymandatoryActual status of the value of the extension card
1.3.6.1.4.1.2606.4.2.7.8.1.4ColumnvaluesValueread-onlymandatoryValue of sensor
1.3.6.1.4.1.2606.4.2.7.8.1.5ColumnvaluesSetHighread-writemandatoryValue for high setpoint of sensor
1.3.6.1.4.1.2606.4.2.7.8.1.6ColumnvaluesSetLowread-writemandatoryValue for low setpoint of sensor
1.3.6.1.4.1.2606.4.2.7.8.1.7ColumnvaluesHysteresisread-writemandatory% -Value for hysteresis for High and Low setpoints, input in % from actual setpoint
1.3.6.1.4.1.2606.4.3NodealarmSensorUnit3Alarm of sensor unit 3
1.3.6.1.4.1.2606.4.3NodecmcTcSetup
1.3.6.1.4.1.2606.4.3.1NodecmcTcSetupGeneral
1.3.6.1.4.1.2606.4.3.1.1ScalarcmcTcSetTempUnitread-writemandatoryUnit of all temperature values and setpoints, Celsius or Fahrenheit
1.3.6.1.4.1.2606.4.3.1.2ScalarcmcTcSetBeeperread-writemandatoryAudible alarm in CMC-TC unit: (2): beeper is on (1): beeper is off (general)
1.3.6.1.4.1.2606.4.3.1.3ScalarcmcTcQuitRelayread-writemandatoryEnable or disable acknowledging currently active alarm relay (with 'C' on CMC-TC).
1.3.6.1.4.1.2606.4.3.1.4ScalarcmcTcLogicRelayread-writemandatoryLogic of alarm relay: (1) Relay will pick up in case of an alarm (2) Relay will release in case of an alarm (3) Relay off (general)
1.3.6.1.4.1.2606.4.3.1.5ScalarcmcTcWebAccessread-writemandatoryWeb access via HTTP: (1) view only (2) full Access, read and set (3) Web disabled (general)
1.3.6.1.4.1.2606.4.3.1.6ScalarcmcTcSetupDateread-writemandatoryactual Date in format DD.MM.YYYY
1.3.6.1.4.1.2606.4.3.1.7ScalarcmcTcSetupTimeread-writemandatoryactual Time in format HH:MM:SS, HH (0-23), MM (0-59), SS (0-59)
1.3.6.1.4.1.2606.4.3.1.8NodecmcTcTimerTable1
1.3.6.1.4.1.2606.4.3.1.8.1ScalarcmcTcTimerNumberread-onlymandatoryNumber of value-table entries=number of outlets available on this unit
1.3.6.1.4.1.2606.4.3.1.8.2TablecmcTcTimerTablenot-accessiblemandatoryHeadline of status-table
1.3.6.1.4.1.2606.4.3.1.8.2.1RowcmcTcTimerEntrynot-accessiblemandatoryEntries of timer-table
1.3.6.1.4.1.2606.4.3.1.8.2.1.1ColumncmcTcTimerIndexread-onlymandatoryIndex for the list of timer entries. Its value ranges between 1 and the value of cmcTcTimerNumber.
1.3.6.1.4.1.2606.4.3.1.8.2.1.2ColumncmcTcTimerStatusread-onlymandatoryActual status of the timer
1.3.6.1.4.1.2606.4.3.1.8.2.1.3ColumncmcTcTimerDayOfWeekread-writemandatorySelection of day of week for timer to switch
1.3.6.1.4.1.2606.4.3.1.8.2.1.4ColumncmcTcTimeOnread-writemandatoryTime to switch on current function, Format: HH:MM
1.3.6.1.4.1.2606.4.3.1.8.2.1.5ColumncmcTcTimeOffread-writemandatoryTime to switch off current function, Format: HH:MM
1.3.6.1.4.1.2606.4.3.1.8.2.1.6ColumncmcTcTimeControlread-writemandatoryControl via RTC
1.3.6.1.4.1.2606.4.3.1.8.2.1.7ColumncmcTcTimerFunctionread-writemandatoryFunction which is controlled via timer 1: unlock via keypad 1 on unit 1 or remote input lock 1 is disabled 2: unlock via keypad 2 on unit 1 or remote input loc…
1.3.6.1.4.1.2606.4.4NodealarmSensorUnit4Alarm of sensor unit 4
1.3.6.1.4.1.2606.4.4NodecmcTcTrapControl
1.3.6.1.4.1.2606.4.4.7NodecmcTcTraps
1.3.6.1.4.1.2606.4.4.7.1ScalarcmcTcTraptableNumberread-onlymandatoryNumber of trapTable entries. The number of trap-receiver
1.3.6.1.4.1.2606.4.4.7.2TablecmcTcTrapTableTablenot-accessiblemandatoryA list of trap-receiver entries
1.3.6.1.4.1.2606.4.4.7.2.1RowcmcTcTrapTableEntrynot-accessiblemandatoryEntries of trapTable
1.3.6.1.4.1.2606.4.4.7.2.1.1ColumntrapIndexread-onlymandatoryIndex for the trap-receiver-table. Its value ranges between 1 and the value of traptableNumber
1.3.6.1.4.1.2606.4.4.7.2.1.2ColumntrapStatusread-writemandatoryEnable or disable trap receiver
1.3.6.1.4.1.2606.4.4.7.2.1.3ColumntrapIPaddressread-writemandatoryIP-address of trap-receiver
1.3.6.1.4.1.2606.4.5NodealarmUnit1Alarm of unit 1
1.3.6.1.4.1.2606.4.5NodecmcTcControl
1.3.6.1.4.1.2606.4.5.1ScalarcmcTcQuitUnitread-writemandatoryCommand to quit (acknowledge) alarms of CMC-TC unit. Setting to 'quit' (2) will have same result as pressing 'C' on Units. Variable is automatically set back t…
1.3.6.1.4.1.2606.4.6NodealarmUnit2Alarm of unit 2
1.3.6.1.4.1.2606.4.7NodealarmUnit3Alarm of unit 3
1.3.6.1.4.1.2606.4.8NodealarmUnit4Alarm of unit 4
1.3.6.1.4.1.2606.4.9NodealarmValuesAlarm of values measured by external card
1.3.6.1.4.1.2606.4.10NodeconfigChangedThe configuration of the cmc has changed, this trap is send if new setup is saved. Configuration can be changed by Terminal, Telnet, Web or SNMP *** NOT IMPLEM…