RMS-MIB
181 objects
No module-level DESCRIPTION found.
Imported Objects
| RFC1155-SMI | Counter enterprises Gauge IpAddress OBJECT-TYPE TimeTicks |
| OID | Name | Access | Status | Description |
|---|---|---|---|---|
| 1.3.6.1.4.1.2769 | NodeKnuerr | |||
| 1.3.6.1.4.1.2769.10 | Noderms | |||
| 1.3.6.1.4.1.2769.10.1 | NodermsFilterTrap | A rmsFilterTrap signals that a filter became true. The index of the filter and its description are transmitted to all registered trap destinations. | ||
| 1.3.6.1.4.1.2769.10.1 | Nodermssystem | |||
| 1.3.6.1.4.1.2769.10.1.1 | ScalarsystemVersion | read-only | mandatory | The systemVersion shows the current installed software version. |
| 1.3.6.1.4.1.2769.10.1.2 | ScalarsystemSNMPsave | read-write | mandatory | systemSNMPsave is used to write all changes made via SNMP into the flash disk. If set to 2 the save operation is triggered. After successfull write it is reset… |
| 1.3.6.1.4.1.2769.10.1.3 | ScalarsystemMsgToSyslog | read-write | mandatory | If systemMsgToSyslog is set to 2, all messages are additionally logged to all syslog destinations. |
| 1.3.6.1.4.1.2769.10.1.4 | ScalarsystemReset | read-write | mandatory | Writing 2 into systemReset forces the RMS to reboot. Reading allways gives back 1 (default value). |
| 1.3.6.1.4.1.2769.10.1.5 | ScalarsystemSNMPaccess | read-only | mandatory | systemSNMPaccess displays the current access right for SNMP access. If 1, variables only can be read, if 2, full SNMP access with SET operaions is allowed. Thi… |
| 1.3.6.1.4.1.2769.10.2 | Nodeinput | |||
| 1.3.6.1.4.1.2769.10.2.1 | TabledigitalInTable | not-accessible | mandatory | The digitalInTable contains all information about physical inputs Digital In 1-8. |
| 1.3.6.1.4.1.2769.10.2.1.1 | RowdigitalInEntry | not-accessible | mandatory | Each entry contains information for each input |
| 1.3.6.1.4.1.2769.10.2.1.1.1 | ColumndigitalInIndex | read-only | mandatory | Index of Digital Input |
| 1.3.6.1.4.1.2769.10.2.1.1.2 | ColumndigitalInDescr | read-write | mandatory | Descriptive name of Digital Input |
| 1.3.6.1.4.1.2769.10.2.1.1.3 | ColumndigitalInState | read-only | mandatory | Current state of Digital Input |
| 1.3.6.1.4.1.2769.10.2.1.1.4 | ColumndigitalInLastChange | read-only | mandatory | Timestamp of last change |
| 1.3.6.1.4.1.2769.10.2.1.1.5 | ColumndigitalInChanges | read-only | mandatory | How many times the input changed since system startup |
| 1.3.6.1.4.1.2769.10.2.2 | TablealertInTable | not-accessible | mandatory | The alertInTable contains all information about physical inputs Alert In 1-4. |
| 1.3.6.1.4.1.2769.10.2.2.1 | RowalertInEntry | not-accessible | mandatory | Each entry contains the values for an alert input |
| 1.3.6.1.4.1.2769.10.2.2.1.1 | ColumnalertInIndex | read-only | mandatory | Index of Alert Input |
| 1.3.6.1.4.1.2769.10.2.2.1.2 | ColumnalertInDescr | read-write | mandatory | Descriptive name of Alert Input |
| 1.3.6.1.4.1.2769.10.2.2.1.3 | ColumnalertInState | read-only | mandatory | Current state of Alert Input |
| 1.3.6.1.4.1.2769.10.2.2.1.4 | ColumnalertInLastChange | read-only | mandatory | Timestamp of last change |
| 1.3.6.1.4.1.2769.10.2.2.1.5 | ColumnalertInChanges | read-only | mandatory | How many times the input changed since system startup |
| 1.3.6.1.4.1.2769.10.2.2.1.6 | ColumnalertInReset | read-write | mandatory | Reset an Alert In by writing 2 in here. Most sensors use to store an alarm, which only can be deleted by resetting the sensor respectively the whole signalling… |
| 1.3.6.1.4.1.2769.10.2.3 | TableupsInTable | not-accessible | mandatory | The upsInputTable contains all information about physical inputs UPS In 1-2. |
| 1.3.6.1.4.1.2769.10.2.3.1 | RowupsInEntry | not-accessible | mandatory | Each entry contains the values for an UPS input |
| 1.3.6.1.4.1.2769.10.2.3.1.1 | ColumnupsInIndex | read-only | mandatory | Index of UPS Input |
| 1.3.6.1.4.1.2769.10.2.3.1.2 | ColumnupsInDescr | read-write | mandatory | Name of UPS Input |
| 1.3.6.1.4.1.2769.10.2.3.1.3 | ColumnupsInState | read-only | mandatory | Current state of UPS Input |
| 1.3.6.1.4.1.2769.10.2.3.1.4 | ColumnupsInLastChange | read-only | mandatory | Timestamp of last change |
| 1.3.6.1.4.1.2769.10.2.3.1.5 | ColumnupsInChanges | read-only | mandatory | How many times the input changed since system startup |
| 1.3.6.1.4.1.2769.10.3 | Nodeoutput | |||
| 1.3.6.1.4.1.2769.10.3.1 | TableoutputTable | not-accessible | mandatory | The table used for describing the digital outputs |
| 1.3.6.1.4.1.2769.10.3.1.1 | RowoutputEntry | not-accessible | mandatory | Each entry contains the description of an digital output |
| 1.3.6.1.4.1.2769.10.3.1.1.1 | ColumnoutputIndex | read-only | mandatory | Index of digital output |
| 1.3.6.1.4.1.2769.10.3.1.1.2 | ColumnoutputDescr | read-write | mandatory | Descriptive Name of one digital output |
| 1.3.6.1.4.1.2769.10.3.1.1.3 | ColumnoutputEffect | read-write | mandatory | Determines the way the physical digital output is influenced by one or more filter results. For this the result of the logical output block can be passed thru … |
| 1.3.6.1.4.1.2769.10.3.1.1.4 | ColumnoutputLastChange | read-only | mandatory | Timestamp of last change |
| 1.3.6.1.4.1.2769.10.3.1.1.5 | ColumnoutputChanges | read-only | mandatory | How many times an output changed since system startup |
| 1.3.6.1.4.1.2769.10.3.1.1.6 | ColumnoutputLogic | read-write | mandatory | Each output can be controlled by a couple of filters, which are combined in a boolean operation. The logic operation (and/or) can be set up with this entry. |
| 1.3.6.1.4.1.2769.10.3.1.1.7 | ColumnoutputState | read-only | mandatory | Current state of digital output |
| 1.3.6.1.4.1.2769.10.3.2 | TableoutputLogicTable | not-accessible | mandatory | The table used for describing the list of filters, which effect an output. |
| 1.3.6.1.4.1.2769.10.3.2.1 | RowoutputLogicEntry | not-accessible | mandatory | Each entry contains the description of one logic and/or element |
| 1.3.6.1.4.1.2769.10.3.2.1.1 | ColumnoutputLogicOutputIndex | read-only | mandatory | Index of the output |
| 1.3.6.1.4.1.2769.10.3.2.1.2 | ColumnoutputLogicFilterIndex | read-only | mandatory | Index of the filter |
| 1.3.6.1.4.1.2769.10.3.2.1.3 | ColumnoutputLogicFilter | read-write | mandatory | Determines, if this filter works on the logical and/or element. Default is off. |
| 1.3.6.1.4.1.2769.10.4 | Nodetemp | |||
| 1.3.6.1.4.1.2769.10.4.1 | TabletempTable | not-accessible | mandatory | Table to hold the information about temperature inputs |
| 1.3.6.1.4.1.2769.10.4.1.1 | RowtempEntry | not-accessible | mandatory | Each entry contains information about one temperature input |
| 1.3.6.1.4.1.2769.10.4.1.1.1 | ColumntempIndex | read-only | mandatory | Index of temperature input |
| 1.3.6.1.4.1.2769.10.4.1.1.2 | ColumntempDescr | read-write | mandatory | Descriptive name of temperature input |
| 1.3.6.1.4.1.2769.10.4.1.1.3 | ColumntempValue | read-only | mandatory | Current temperature in degree celsius. If 655 no sensor is connected. |
| 1.3.6.1.4.1.2769.10.5 | Nodehumid | |||
| 1.3.6.1.4.1.2769.10.5.1 | TablehumidTable | not-accessible | mandatory | Table to hold the information about humidity inputs |
| 1.3.6.1.4.1.2769.10.5.1.1 | RowhumidEntry | not-accessible | mandatory | Each entry contains information about one humidity input |
| 1.3.6.1.4.1.2769.10.5.1.1.1 | ColumnhumidIndex | read-only | mandatory | Index of humidity input |
| 1.3.6.1.4.1.2769.10.5.1.1.2 | ColumnhumidDescr | read-write | mandatory | Descriptive name of the humidity input |
| 1.3.6.1.4.1.2769.10.5.1.1.3 | ColumnhumidValue | read-only | mandatory | Current humidity in percent rel. humidity. If 255 no sensor is connected. |
| 1.3.6.1.4.1.2769.10.6 | Nodemains | |||
| 1.3.6.1.4.1.2769.10.6.1 | TablemainsTable | not-accessible | mandatory | Table to hold the information about the mains inputs |
| 1.3.6.1.4.1.2769.10.6.1.1 | RowmainsEntry | not-accessible | mandatory | Each entry contains information about one mains input |
| 1.3.6.1.4.1.2769.10.6.1.1.1 | ColumnmainsIndex | read-only | mandatory | Index of mains input |
| 1.3.6.1.4.1.2769.10.6.1.1.2 | ColumnmainsDescr | read-write | mandatory | Descriptive name of the mains input |
| 1.3.6.1.4.1.2769.10.6.1.1.3 | ColumnmainsValue | read-only | mandatory | Current voltage of mains input in volt. If 13 or 255 no voltage is detected. |
| 1.3.6.1.4.1.2769.10.7 | Nodefilter | |||
| 1.3.6.1.4.1.2769.10.7.1 | TablefilterTable | not-accessible | mandatory | Table containing all information about the defined filters |
| 1.3.6.1.4.1.2769.10.7.1.1 | RowfilterEntry | not-accessible | mandatory | Each entry contains the description of one filter |
| 1.3.6.1.4.1.2769.10.7.1.1.1 | ColumnfilterIndex | read-only | mandatory | Index of the filter entry |
| 1.3.6.1.4.1.2769.10.7.1.1.2 | ColumnfilterDescr | read-write | mandatory | Descriptive name of filter |
| 1.3.6.1.4.1.2769.10.7.1.1.3 | ColumnfilterResult | read-only | mandatory | Current filter result, i.e. result of all 'or'ed inputs - see block diagram |
| 1.3.6.1.4.1.2769.10.7.1.1.4 | ColumnfilterEffect | read-write | mandatory | Determines the way the filter is used for further operation Can be switched off, passed thru or inverted. |
| 1.3.6.1.4.1.2769.10.7.1.1.5 | ColumnfilterTrap | read-write | mandatory | Determines the way of trap notification to management station(s) in case of filter events. Traps can be off, sent once (when filter becomes true) or sent repea… |
| 1.3.6.1.4.1.2769.10.7.1.1.6 | ColumnfilterLED | read-write | mandatory | When set to yes(2) a filter event will be signalled by the warning LED on front of RMS |
| 1.3.6.1.4.1.2769.10.7.1.1.7 | ColumnfilterBuzzer | read-write | mandatory | When set to yes(2) a filter event will be signalled by the build-in buzzer |
| 1.3.6.1.4.1.2769.10.7.1.1.8 | ColumnfilterMessagePriority | read-write | mandatory | If set to priority-warning(2) or priority-critical(3), a filter event will be logged in the message log an on all defined log server(s) with the corresponding … |
| 1.3.6.1.4.1.2769.10.7.1.1.9 | ColumnfilterConfirmation | read-write | mandatory | If set to enabled(1), it is possible to confirme a true filter. This can be done on front panel of RMS, via telnet or via SNMP (see also variable filterConfirm… |
| 1.3.6.1.4.1.2769.10.7.1.1.10 | ColumnfilterReactivationTime | read-write | mandatory | Time after which a confirmed filter will be reactivated automatically |
| 1.3.6.1.4.1.2769.10.7.1.1.11 | ColumnfilterConfirm | read-write | mandatory | A true filter can be confimed by writing confirmed(2) in here (provided filter confirmation is enabled - see variable filterConfirmation). By doing this the ef… |
| 1.3.6.1.4.1.2769.10.7.2 | TablefilterDigitalInTable | not-accessible | mandatory | Table containing all information about the filter inputs Digital 1-8 of each filter |
| 1.3.6.1.4.1.2769.10.7.2.1 | RowfilterDigitalInEntry | not-accessible | mandatory | Each entry contains the description of one digital input |
| 1.3.6.1.4.1.2769.10.7.2.1.1 | ColumnfilterDigitalInIndex | read-only | mandatory | Index of the filter |
| 1.3.6.1.4.1.2769.10.7.2.1.2 | ColumnfilterDigitalInPort | read-only | mandatory | Index of the digital input |
| 1.3.6.1.4.1.2769.10.7.2.1.3 | ColumnfilterDigitalInEffect | read-write | mandatory | Determines the way the digital input effects the filter. Can be switched off(1), inverted(3) or passed thru(2). |
| 1.3.6.1.4.1.2769.10.7.3 | TablefilterAlertInTable | not-accessible | mandatory | Table containing all information about the filter inputs Alert In 1-4 of each filter |
| 1.3.6.1.4.1.2769.10.7.3.1 | RowfilterAlertInEntry | not-accessible | mandatory | Each entry contains information of one alert input |
| 1.3.6.1.4.1.2769.10.7.3.1.1 | ColumnfilterAlertInIndex | read-only | mandatory | Index of the filter |
| 1.3.6.1.4.1.2769.10.7.3.1.2 | ColumnfilterAlertInPort | read-only | mandatory | Index of the alert input |
| 1.3.6.1.4.1.2769.10.7.3.1.3 | ColumnfilterAlertInEffect | read-write | mandatory | Determines the way the alert input effects the filter. Can be switched off(1), inverted(3) or passed thru(2). |
| 1.3.6.1.4.1.2769.10.7.4 | TablefilterUPSInTable | not-accessible | mandatory | Table containing all information about the filter inputs UPS In 1-2 of each filter |
| 1.3.6.1.4.1.2769.10.7.4.1 | RowfilterUPSInEntry | not-accessible | mandatory | Each entry contains the description of one ups input |
| 1.3.6.1.4.1.2769.10.7.4.1.1 | ColumnfilterUPSInIndex | read-only | mandatory | Index of the filter |
| 1.3.6.1.4.1.2769.10.7.4.1.2 | ColumnfilterUPSInPort | read-only | mandatory | Index of the UPS input |
| 1.3.6.1.4.1.2769.10.7.4.1.3 | ColumnfilterUPSInEffect | read-write | mandatory | Determines the way the UPS input effects the filter. Can be switched off(1), inverted(3) or passed thru(2). |
| 1.3.6.1.4.1.2769.10.7.5 | TablefilterTempTable | not-accessible | mandatory | Table containing information about temperature inputs of each filter, i.e. thresholds and compare operations |
| 1.3.6.1.4.1.2769.10.7.5.1 | RowfilterTempEntry | not-accessible | mandatory | Each entry contains the description of one filter temp input |
| 1.3.6.1.4.1.2769.10.7.5.1.1 | ColumnfilterTempIndex | read-only | mandatory | Index of the filter |
| 1.3.6.1.4.1.2769.10.7.5.1.2 | ColumnfilterTempSensor | read-only | mandatory | Index of the temp input |
| 1.3.6.1.4.1.2769.10.7.5.1.3 | ColumnfilterTempEffect | read-write | mandatory | Determines the way the result of temp input comparison effects on the filter. Can be switched off(1), inverted (3) or passed thru(3). |
| 1.3.6.1.4.1.2769.10.7.5.1.4 | ColumnfilterTempAThres | read-write | mandatory | Threshold of temp input part A |
| 1.3.6.1.4.1.2769.10.7.5.1.5 | ColumnfilterTempAMode | read-write | mandatory | Determines the operating mode of comparison operation A. Can be set to greater(2) ' >', less(3) '<' or turned off(1), if not needed |
| 1.3.6.1.4.1.2769.10.7.5.1.6 | ColumnfilterTempBThres | read-write | mandatory | Threshold of temp input part B |
| 1.3.6.1.4.1.2769.10.7.5.1.7 | ColumnfilterTempBMode | read-write | mandatory | Determines the operating mode of comparison operation B. Can be set to greater(2) ' >', less(3) '<' or turned off(1), if not needed |
| 1.3.6.1.4.1.2769.10.7.6 | TablefilterHumidityTable | not-accessible | mandatory | Table containing information about humidity inputs of each filter, i.e. thresholds and compare operations |
| 1.3.6.1.4.1.2769.10.7.6.1 | RowfilterHumidityEntry | not-accessible | mandatory | Each entry contains the description of one filter |
| 1.3.6.1.4.1.2769.10.7.6.1.1 | ColumnfilterHumidityIndex | read-only | mandatory | Index of the filter |
| 1.3.6.1.4.1.2769.10.7.6.1.2 | ColumnfilterHumiditySensor | read-only | mandatory | Index of the humidity input |
| 1.3.6.1.4.1.2769.10.7.6.1.3 | ColumnfilterHumidityEffect | read-write | mandatory | Determines the way the result of humidity input comparison effects the filter. Can be switched off(1), inverted(3) or passed thru(2), if not needed. |
| 1.3.6.1.4.1.2769.10.7.6.1.4 | ColumnfilterHumidityAThres | read-write | mandatory | Threshold of humidity input part A |
| 1.3.6.1.4.1.2769.10.7.6.1.5 | ColumnfilterHumidityAMode | read-write | mandatory | Determines the operating mode of comparison operation A. Can be set to greater(2) ' >', less(3) '<' or turned off(1), if not needed |
| 1.3.6.1.4.1.2769.10.7.6.1.6 | ColumnfilterHumidityBThres | read-write | mandatory | Threshold of humidity input part B |
| 1.3.6.1.4.1.2769.10.7.6.1.7 | ColumnfilterHumidityBMode | read-write | mandatory | Determines the operating mode of comparison operation B. Can be set to greater(2) ' >', less(3) '<' or turned off(1), if not needed |
| 1.3.6.1.4.1.2769.10.7.7 | TablefilterMainsTable | not-accessible | mandatory | Table containing information about mains inputs of each filter, i.e. thresholds and compare operations |
| 1.3.6.1.4.1.2769.10.7.7.1 | RowfilterMainsEntry | not-accessible | mandatory | Each entry contains the description of one filter |
| 1.3.6.1.4.1.2769.10.7.7.1.1 | ColumnfilterMainsIndex | read-only | mandatory | Index of the filter |
| 1.3.6.1.4.1.2769.10.7.7.1.2 | ColumnfilterMainsSensor | read-only | mandatory | Index of the mains sensor |
| 1.3.6.1.4.1.2769.10.7.7.1.3 | ColumnfilterMainsEffect | read-write | mandatory | Determines the way the result of mains input comparison effects on the filter. Can be switched off(1), inverted(3) or passed thru (2). |
| 1.3.6.1.4.1.2769.10.7.7.1.4 | ColumnfilterMainsAThres | read-write | mandatory | Threshold of mains input part B |
| 1.3.6.1.4.1.2769.10.7.7.1.5 | ColumnfilterMainsAMode | read-write | mandatory | Determines the operating mode of comparison operation A. Can be set to greater(2) ' >', less(3) '<' or turned off(1), if not needed |
| 1.3.6.1.4.1.2769.10.7.7.1.6 | ColumnfilterMainsBThres | read-write | mandatory | Threshold of mains input part B |
| 1.3.6.1.4.1.2769.10.7.7.1.7 | ColumnfilterMainsBMode | read-write | mandatory | Determines the operating mode of comparison operation B. Can be set to greater(2) ' >', less(3) '<' or turned off(1), if not needed |
| 1.3.6.1.4.1.2769.10.7.8 | TablefilterFeedbackTable | not-accessible | mandatory | Table containing information about feedback inputs |
| 1.3.6.1.4.1.2769.10.7.8.1 | RowfilterFeedbackEntry | not-accessible | mandatory | Each entry contains the description of one filter |
| 1.3.6.1.4.1.2769.10.7.8.1.1 | ColumnfilterFeedbackIndex | read-only | mandatory | Index of the filter |
| 1.3.6.1.4.1.2769.10.7.8.1.2 | ColumnfilterFeedbackInput | read-only | mandatory | Index of the feedback input |
| 1.3.6.1.4.1.2769.10.7.8.1.3 | ColumnfilterFeedbackInFilter | read-write | mandatory | Number of the filter which is connected to this feedback input |
| 1.3.6.1.4.1.2769.10.7.8.1.4 | ColumnfilterFeedbackDelay | read-write | mandatory | Delay time to wait until signal is forwarded |
| 1.3.6.1.4.1.2769.10.7.8.1.5 | ColumnfilterFeedbackPassCondition | read-write | mandatory | Determines the way an incoming signal is forwarded to the filter structure. If set to thru(1), all incoming signals are straight forwarded. If set to condition… |
| 1.3.6.1.4.1.2769.10.7.8.1.6 | ColumnfilterFeedbackHold | read-write | mandatory | Determines the time the passed signal will be held up, after the falling edge of the original trigger signal. See timing diagram in manual for further details. |
| 1.3.6.1.4.1.2769.10.7.8.1.7 | ColumnfilterFeedbackEffect | read-write | mandatory | Determines the way the result of feedback input effects the filter. Can be switched off(1), inverted(3) or passed thru (2). |
| 1.3.6.1.4.1.2769.10.8 | Nodemessage | |||
| 1.3.6.1.4.1.2769.10.8.1 | TablemessageTable | not-accessible | mandatory | The message table contains the logged filter events |
| 1.3.6.1.4.1.2769.10.8.1.1 | RowmessageEntry | not-accessible | mandatory | Each entry contains information of one message |
| 1.3.6.1.4.1.2769.10.8.1.1.1 | ColumnmessageIndex | read-only | mandatory | Index of message line |
| 1.3.6.1.4.1.2769.10.8.1.1.2 | ColumnmessageFilter | read-only | mandatory | Number of filter which caused the message |
| 1.3.6.1.4.1.2769.10.8.1.1.3 | ColumnmessageFilterDescr | read-only | mandatory | Name of the filter which caused the message |
| 1.3.6.1.4.1.2769.10.8.1.1.4 | ColumnmessageTime | read-only | mandatory | Timestamp of event |
| 1.3.6.1.4.1.2769.10.8.1.1.5 | ColumnmessagePriority | read-only | mandatory | Priority of the message. If set to no-priority(1) no message will be logged. The Priority has only informational character and doesn't affect the way it is han… |
| 1.3.6.1.4.1.2769.10.8.1.1.6 | ColumnmessageAcknoledged | read-write | mandatory | Displays, if event was acknoledged already. Has only informational character for operator |
| 1.3.6.1.4.1.2769.10.9 | Nodeuser | |||
| 1.3.6.1.4.1.2769.10.9.1 | TableuserTable | not-accessible | mandatory | Some infos about all registered users, e.g. name, right and chipcard key (if reader installed) |
| 1.3.6.1.4.1.2769.10.9.1.1 | RowuserEntry | not-accessible | mandatory | Each entry contains information about one user |
| 1.3.6.1.4.1.2769.10.9.1.1.1 | ColumnuserIndex | read-only | mandatory | Index of user. Is dynamically filled from 1..n |
| 1.3.6.1.4.1.2769.10.9.1.1.2 | ColumnuserName | read-only | mandatory | name of one user |
| 1.3.6.1.4.1.2769.10.9.1.1.3 | ColumnuserRight | read-only | mandatory | Access right of one user |
| 1.3.6.1.4.1.2769.10.9.1.1.4 | ColumnuserChipcardKey | read-only | mandatory | Displays the chipcard key of this user - only available, if optional chipcard reader installed. |
| 1.3.6.1.4.1.2769.10.9.1.1.5 | ColumnuserChipcardAccess | read-only | mandatory | Holds the status of the last access try via chipcard reader. In case of failure a rmsChipcardTrap will be sent. |
| 1.3.6.1.4.1.2769.10.20 | Nodeaux | |||
| 1.3.6.1.4.1.2769.10.20.1 | ScalarauxDevice | read-only | mandatory | AUX device number - currently supported numbers are 1 - <no device> 2 - Chipcard Reader The set of supported devices will grow. Check the support server from t… |
| 1.3.6.1.4.1.2769.10.20.2 | ScalarauxDeviceName | read-only | mandatory | Name of the device connected to the AUX port or <no device>. |
| 1.3.6.1.4.1.2769.10.21 | Nodeicc | |||
| 1.3.6.1.4.1.2769.10.21.1 | ScalarreaderConnected | read-only | mandatory | Shows if chipcard reader is connected to the RMS |
| 1.3.6.1.4.1.2769.10.21.2 | ScalarreaderCardInside | read-only | mandatory | Shows if reader contains a chipcard |
| 1.3.6.1.4.1.2769.10.21.3 | ScalarreaderCardKey | read-only | mandatory | Shows key of chipcard in Chipcard Reader |
| 1.3.6.1.4.1.2769.10.21.4 | ScalarreaderLEDcolor | read-only | mandatory | Shows if reader contains a chipcard |
| 1.3.6.1.4.1.2769.10.21.5 | ScalaropenerLogic | read-only | mandatory | Logic of door opener connected to chipcard reader. If make(1) Digital Out 4 will get short in case of successfull access attempt, and open else. If break(2) Di… |
| 1.3.6.1.4.1.2769.10.21.6 | ScalaropenerOpenTime | read-only | mandatory | How long the door opener (e.g. Digital Out 4) will get open/short in case of successfull access attempt (in secs). |
| 1.3.6.1.4.1.2769.10.21.7 | ScalaropenerState | read-only | mandatory | Current state of the door opener. |
| 1.3.6.1.4.1.2769.10.22 | Nodeups | |||
| 1.3.6.1.4.1.2769.10.22.1 | ScalarupsConnected | read-only | mandatory | Shows if ups is connected to AUX on the RMS |
| 1.3.6.1.4.1.2769.10.22.2 | ScalarupsManufacturer | read-only | current | The name of the UPS manufacturer. |
| 1.3.6.1.4.1.2769.10.22.3 | ScalarupsModel | read-only | current | The UPS Model designation. |
| 1.3.6.1.4.1.2769.10.22.4 | ScalarupsFirmwareVersion | read-only | current | The UPS firmware/software version(s). This variable may or may not have the same value as upsIdentAgentSoftwareVersion in some implementations. |
| 1.3.6.1.4.1.2769.10.22.5 | ScalarupsSoftwareVersion | read-only | current | The UPS agent software version. This variable may or may not have the same value as upsIdentUPSSoftwareVersion in some implementations. |
| 1.3.6.1.4.1.2769.10.22.6 | ScalarupsID | read-write | current | The UPS Serial Number |
| 1.3.6.1.4.1.2769.10.22.7 | ScalarupsBatteryLastReplaced | not-accessible | current | |
| 1.3.6.1.4.1.2769.10.22.8 | ScalarupsTimeOnBattery | read-only | current | If the unit is on battery power, the elapsed time since the UPS last switched to battery power, or the time since the network management subsystem was last res… |
| 1.3.6.1.4.1.2769.10.22.9 | ScalarupsTimeRemaining | read-only | current | An estimate of the time to battery charge depletion under the present load conditions if the utility power is off and remains off, or if it were to be lost and… |
| 1.3.6.1.4.1.2769.10.22.10 | ScalarupsBatteryVoltage | read-only | current | The magnitude of the present battery voltage. |
| 1.3.6.1.4.1.2769.10.22.11 | ScalarupsBatteryCurrent | read-only | current | The present battery current. |
| 1.3.6.1.4.1.2769.10.22.12 | ScalarupsBatteryTemp | read-only | current | The ambient temperature at or near the UPS Battery casing. |
| 1.3.6.1.4.1.2769.10.22.13 | ScalarupsBatteryStatus | read-only | current | The indication of the capacity remaining in the UPS system's batteries. A value of batteryNormal indicates that the remaining run-time is greater than upsConfi… |
| 1.3.6.1.4.1.2769.10.22.14 | ScalarupsLineFrequency | read-only | current | The present input frequency. |
| 1.3.6.1.4.1.2769.10.22.15 | ScalarupsLineVoltage | read-only | current | The magnitude of the present input voltage. |
| 1.3.6.1.4.1.2769.10.22.16 | ScalarupsOutputVoltage | read-only | current | The present output voltage. |
| 1.3.6.1.4.1.2769.10.22.17 | ScalarupsNominalOutputVoltage | read-write | current | The magnitude of the nominal output voltage. On those systems which support read-write access to this object, if there is an attempt to set this variable to a … |
| 1.3.6.1.4.1.2769.10.22.18 | ScalarupsOnline | not-accessible | current | |
| 1.3.6.1.4.1.2769.10.22.19 | ScalarupsCalibrating | not-accessible | current | |
| 1.3.6.1.4.1.2769.10.22.20 | ScalarupsSleeping | not-accessible | current | |
| 1.3.6.1.4.1.2769.10.22.21 | ScalarupsLoad | not-accessible | current | |
| 1.3.6.1.4.1.2769.10.50 | NodermsChipcardTrap | A rmsChipcardTrap signals any access by use of the (optional) chipcard reader. In any case all informations are transmitted. |