MIB Viewer

RMS-MIB

181 objects
No module-level DESCRIPTION found.
OIDNameAccessStatusDescription
1.3.6.1.4.1.2769NodeKnuerr
1.3.6.1.4.1.2769.10Noderms
1.3.6.1.4.1.2769.10.1NodermsFilterTrapA rmsFilterTrap signals that a filter became true. The index of the filter and its description are transmitted to all registered trap destinations.
1.3.6.1.4.1.2769.10.1Nodermssystem
1.3.6.1.4.1.2769.10.1.1ScalarsystemVersionread-onlymandatoryThe systemVersion shows the current installed software version.
1.3.6.1.4.1.2769.10.1.2ScalarsystemSNMPsaveread-writemandatorysystemSNMPsave is used to write all changes made via SNMP into the flash disk. If set to 2 the save operation is triggered. After successfull write it is reset…
1.3.6.1.4.1.2769.10.1.3ScalarsystemMsgToSyslogread-writemandatoryIf systemMsgToSyslog is set to 2, all messages are additionally logged to all syslog destinations.
1.3.6.1.4.1.2769.10.1.4ScalarsystemResetread-writemandatoryWriting 2 into systemReset forces the RMS to reboot. Reading allways gives back 1 (default value).
1.3.6.1.4.1.2769.10.1.5ScalarsystemSNMPaccessread-onlymandatorysystemSNMPaccess displays the current access right for SNMP access. If 1, variables only can be read, if 2, full SNMP access with SET operaions is allowed. Thi…
1.3.6.1.4.1.2769.10.2Nodeinput
1.3.6.1.4.1.2769.10.2.1TabledigitalInTablenot-accessiblemandatoryThe digitalInTable contains all information about physical inputs Digital In 1-8.
1.3.6.1.4.1.2769.10.2.1.1RowdigitalInEntrynot-accessiblemandatoryEach entry contains information for each input
1.3.6.1.4.1.2769.10.2.1.1.1ColumndigitalInIndexread-onlymandatoryIndex of Digital Input
1.3.6.1.4.1.2769.10.2.1.1.2ColumndigitalInDescrread-writemandatoryDescriptive name of Digital Input
1.3.6.1.4.1.2769.10.2.1.1.3ColumndigitalInStateread-onlymandatoryCurrent state of Digital Input
1.3.6.1.4.1.2769.10.2.1.1.4ColumndigitalInLastChangeread-onlymandatoryTimestamp of last change
1.3.6.1.4.1.2769.10.2.1.1.5ColumndigitalInChangesread-onlymandatoryHow many times the input changed since system startup
1.3.6.1.4.1.2769.10.2.2TablealertInTablenot-accessiblemandatoryThe alertInTable contains all information about physical inputs Alert In 1-4.
1.3.6.1.4.1.2769.10.2.2.1RowalertInEntrynot-accessiblemandatoryEach entry contains the values for an alert input
1.3.6.1.4.1.2769.10.2.2.1.1ColumnalertInIndexread-onlymandatoryIndex of Alert Input
1.3.6.1.4.1.2769.10.2.2.1.2ColumnalertInDescrread-writemandatoryDescriptive name of Alert Input
1.3.6.1.4.1.2769.10.2.2.1.3ColumnalertInStateread-onlymandatoryCurrent state of Alert Input
1.3.6.1.4.1.2769.10.2.2.1.4ColumnalertInLastChangeread-onlymandatoryTimestamp of last change
1.3.6.1.4.1.2769.10.2.2.1.5ColumnalertInChangesread-onlymandatoryHow many times the input changed since system startup
1.3.6.1.4.1.2769.10.2.2.1.6ColumnalertInResetread-writemandatoryReset an Alert In by writing 2 in here. Most sensors use to store an alarm, which only can be deleted by resetting the sensor respectively the whole signalling…
1.3.6.1.4.1.2769.10.2.3TableupsInTablenot-accessiblemandatoryThe upsInputTable contains all information about physical inputs UPS In 1-2.
1.3.6.1.4.1.2769.10.2.3.1RowupsInEntrynot-accessiblemandatoryEach entry contains the values for an UPS input
1.3.6.1.4.1.2769.10.2.3.1.1ColumnupsInIndexread-onlymandatoryIndex of UPS Input
1.3.6.1.4.1.2769.10.2.3.1.2ColumnupsInDescrread-writemandatoryName of UPS Input
1.3.6.1.4.1.2769.10.2.3.1.3ColumnupsInStateread-onlymandatoryCurrent state of UPS Input
1.3.6.1.4.1.2769.10.2.3.1.4ColumnupsInLastChangeread-onlymandatoryTimestamp of last change
1.3.6.1.4.1.2769.10.2.3.1.5ColumnupsInChangesread-onlymandatoryHow many times the input changed since system startup
1.3.6.1.4.1.2769.10.3Nodeoutput
1.3.6.1.4.1.2769.10.3.1TableoutputTablenot-accessiblemandatoryThe table used for describing the digital outputs
1.3.6.1.4.1.2769.10.3.1.1RowoutputEntrynot-accessiblemandatoryEach entry contains the description of an digital output
1.3.6.1.4.1.2769.10.3.1.1.1ColumnoutputIndexread-onlymandatoryIndex of digital output
1.3.6.1.4.1.2769.10.3.1.1.2ColumnoutputDescrread-writemandatoryDescriptive Name of one digital output
1.3.6.1.4.1.2769.10.3.1.1.3ColumnoutputEffectread-writemandatoryDetermines the way the physical digital output is influenced by one or more filter results. For this the result of the logical output block can be passed thru …
1.3.6.1.4.1.2769.10.3.1.1.4ColumnoutputLastChangeread-onlymandatoryTimestamp of last change
1.3.6.1.4.1.2769.10.3.1.1.5ColumnoutputChangesread-onlymandatoryHow many times an output changed since system startup
1.3.6.1.4.1.2769.10.3.1.1.6ColumnoutputLogicread-writemandatoryEach output can be controlled by a couple of filters, which are combined in a boolean operation. The logic operation (and/or) can be set up with this entry.
1.3.6.1.4.1.2769.10.3.1.1.7ColumnoutputStateread-onlymandatoryCurrent state of digital output
1.3.6.1.4.1.2769.10.3.2TableoutputLogicTablenot-accessiblemandatoryThe table used for describing the list of filters, which effect an output.
1.3.6.1.4.1.2769.10.3.2.1RowoutputLogicEntrynot-accessiblemandatoryEach entry contains the description of one logic and/or element
1.3.6.1.4.1.2769.10.3.2.1.1ColumnoutputLogicOutputIndexread-onlymandatoryIndex of the output
1.3.6.1.4.1.2769.10.3.2.1.2ColumnoutputLogicFilterIndexread-onlymandatoryIndex of the filter
1.3.6.1.4.1.2769.10.3.2.1.3ColumnoutputLogicFilterread-writemandatoryDetermines, if this filter works on the logical and/or element. Default is off.
1.3.6.1.4.1.2769.10.4Nodetemp
1.3.6.1.4.1.2769.10.4.1TabletempTablenot-accessiblemandatoryTable to hold the information about temperature inputs
1.3.6.1.4.1.2769.10.4.1.1RowtempEntrynot-accessiblemandatoryEach entry contains information about one temperature input
1.3.6.1.4.1.2769.10.4.1.1.1ColumntempIndexread-onlymandatoryIndex of temperature input
1.3.6.1.4.1.2769.10.4.1.1.2ColumntempDescrread-writemandatoryDescriptive name of temperature input
1.3.6.1.4.1.2769.10.4.1.1.3ColumntempValueread-onlymandatoryCurrent temperature in degree celsius. If 655 no sensor is connected.
1.3.6.1.4.1.2769.10.5Nodehumid
1.3.6.1.4.1.2769.10.5.1TablehumidTablenot-accessiblemandatoryTable to hold the information about humidity inputs
1.3.6.1.4.1.2769.10.5.1.1RowhumidEntrynot-accessiblemandatoryEach entry contains information about one humidity input
1.3.6.1.4.1.2769.10.5.1.1.1ColumnhumidIndexread-onlymandatoryIndex of humidity input
1.3.6.1.4.1.2769.10.5.1.1.2ColumnhumidDescrread-writemandatoryDescriptive name of the humidity input
1.3.6.1.4.1.2769.10.5.1.1.3ColumnhumidValueread-onlymandatoryCurrent humidity in percent rel. humidity. If 255 no sensor is connected.
1.3.6.1.4.1.2769.10.6Nodemains
1.3.6.1.4.1.2769.10.6.1TablemainsTablenot-accessiblemandatoryTable to hold the information about the mains inputs
1.3.6.1.4.1.2769.10.6.1.1RowmainsEntrynot-accessiblemandatoryEach entry contains information about one mains input
1.3.6.1.4.1.2769.10.6.1.1.1ColumnmainsIndexread-onlymandatoryIndex of mains input
1.3.6.1.4.1.2769.10.6.1.1.2ColumnmainsDescrread-writemandatoryDescriptive name of the mains input
1.3.6.1.4.1.2769.10.6.1.1.3ColumnmainsValueread-onlymandatoryCurrent voltage of mains input in volt. If 13 or 255 no voltage is detected.
1.3.6.1.4.1.2769.10.7Nodefilter
1.3.6.1.4.1.2769.10.7.1TablefilterTablenot-accessiblemandatoryTable containing all information about the defined filters
1.3.6.1.4.1.2769.10.7.1.1RowfilterEntrynot-accessiblemandatoryEach entry contains the description of one filter
1.3.6.1.4.1.2769.10.7.1.1.1ColumnfilterIndexread-onlymandatoryIndex of the filter entry
1.3.6.1.4.1.2769.10.7.1.1.2ColumnfilterDescrread-writemandatoryDescriptive name of filter
1.3.6.1.4.1.2769.10.7.1.1.3ColumnfilterResultread-onlymandatoryCurrent filter result, i.e. result of all 'or'ed inputs - see block diagram
1.3.6.1.4.1.2769.10.7.1.1.4ColumnfilterEffectread-writemandatoryDetermines the way the filter is used for further operation Can be switched off, passed thru or inverted.
1.3.6.1.4.1.2769.10.7.1.1.5ColumnfilterTrapread-writemandatoryDetermines the way of trap notification to management station(s) in case of filter events. Traps can be off, sent once (when filter becomes true) or sent repea…
1.3.6.1.4.1.2769.10.7.1.1.6ColumnfilterLEDread-writemandatoryWhen set to yes(2) a filter event will be signalled by the warning LED on front of RMS
1.3.6.1.4.1.2769.10.7.1.1.7ColumnfilterBuzzerread-writemandatoryWhen set to yes(2) a filter event will be signalled by the build-in buzzer
1.3.6.1.4.1.2769.10.7.1.1.8ColumnfilterMessagePriorityread-writemandatoryIf set to priority-warning(2) or priority-critical(3), a filter event will be logged in the message log an on all defined log server(s) with the corresponding …
1.3.6.1.4.1.2769.10.7.1.1.9ColumnfilterConfirmationread-writemandatoryIf set to enabled(1), it is possible to confirme a true filter. This can be done on front panel of RMS, via telnet or via SNMP (see also variable filterConfirm…
1.3.6.1.4.1.2769.10.7.1.1.10ColumnfilterReactivationTimeread-writemandatoryTime after which a confirmed filter will be reactivated automatically
1.3.6.1.4.1.2769.10.7.1.1.11ColumnfilterConfirmread-writemandatoryA true filter can be confimed by writing confirmed(2) in here (provided filter confirmation is enabled - see variable filterConfirmation). By doing this the ef…
1.3.6.1.4.1.2769.10.7.2TablefilterDigitalInTablenot-accessiblemandatoryTable containing all information about the filter inputs Digital 1-8 of each filter
1.3.6.1.4.1.2769.10.7.2.1RowfilterDigitalInEntrynot-accessiblemandatoryEach entry contains the description of one digital input
1.3.6.1.4.1.2769.10.7.2.1.1ColumnfilterDigitalInIndexread-onlymandatoryIndex of the filter
1.3.6.1.4.1.2769.10.7.2.1.2ColumnfilterDigitalInPortread-onlymandatoryIndex of the digital input
1.3.6.1.4.1.2769.10.7.2.1.3ColumnfilterDigitalInEffectread-writemandatoryDetermines the way the digital input effects the filter. Can be switched off(1), inverted(3) or passed thru(2).
1.3.6.1.4.1.2769.10.7.3TablefilterAlertInTablenot-accessiblemandatoryTable containing all information about the filter inputs Alert In 1-4 of each filter
1.3.6.1.4.1.2769.10.7.3.1RowfilterAlertInEntrynot-accessiblemandatoryEach entry contains information of one alert input
1.3.6.1.4.1.2769.10.7.3.1.1ColumnfilterAlertInIndexread-onlymandatoryIndex of the filter
1.3.6.1.4.1.2769.10.7.3.1.2ColumnfilterAlertInPortread-onlymandatoryIndex of the alert input
1.3.6.1.4.1.2769.10.7.3.1.3ColumnfilterAlertInEffectread-writemandatoryDetermines the way the alert input effects the filter. Can be switched off(1), inverted(3) or passed thru(2).
1.3.6.1.4.1.2769.10.7.4TablefilterUPSInTablenot-accessiblemandatoryTable containing all information about the filter inputs UPS In 1-2 of each filter
1.3.6.1.4.1.2769.10.7.4.1RowfilterUPSInEntrynot-accessiblemandatoryEach entry contains the description of one ups input
1.3.6.1.4.1.2769.10.7.4.1.1ColumnfilterUPSInIndexread-onlymandatoryIndex of the filter
1.3.6.1.4.1.2769.10.7.4.1.2ColumnfilterUPSInPortread-onlymandatoryIndex of the UPS input
1.3.6.1.4.1.2769.10.7.4.1.3ColumnfilterUPSInEffectread-writemandatoryDetermines the way the UPS input effects the filter. Can be switched off(1), inverted(3) or passed thru(2).
1.3.6.1.4.1.2769.10.7.5TablefilterTempTablenot-accessiblemandatoryTable containing information about temperature inputs of each filter, i.e. thresholds and compare operations
1.3.6.1.4.1.2769.10.7.5.1RowfilterTempEntrynot-accessiblemandatoryEach entry contains the description of one filter temp input
1.3.6.1.4.1.2769.10.7.5.1.1ColumnfilterTempIndexread-onlymandatoryIndex of the filter
1.3.6.1.4.1.2769.10.7.5.1.2ColumnfilterTempSensorread-onlymandatoryIndex of the temp input
1.3.6.1.4.1.2769.10.7.5.1.3ColumnfilterTempEffectread-writemandatoryDetermines the way the result of temp input comparison effects on the filter. Can be switched off(1), inverted (3) or passed thru(3).
1.3.6.1.4.1.2769.10.7.5.1.4ColumnfilterTempAThresread-writemandatoryThreshold of temp input part A
1.3.6.1.4.1.2769.10.7.5.1.5ColumnfilterTempAModeread-writemandatoryDetermines the operating mode of comparison operation A. Can be set to greater(2) ' >', less(3) '<' or turned off(1), if not needed
1.3.6.1.4.1.2769.10.7.5.1.6ColumnfilterTempBThresread-writemandatoryThreshold of temp input part B
1.3.6.1.4.1.2769.10.7.5.1.7ColumnfilterTempBModeread-writemandatoryDetermines the operating mode of comparison operation B. Can be set to greater(2) ' >', less(3) '<' or turned off(1), if not needed
1.3.6.1.4.1.2769.10.7.6TablefilterHumidityTablenot-accessiblemandatoryTable containing information about humidity inputs of each filter, i.e. thresholds and compare operations
1.3.6.1.4.1.2769.10.7.6.1RowfilterHumidityEntrynot-accessiblemandatoryEach entry contains the description of one filter
1.3.6.1.4.1.2769.10.7.6.1.1ColumnfilterHumidityIndexread-onlymandatoryIndex of the filter
1.3.6.1.4.1.2769.10.7.6.1.2ColumnfilterHumiditySensorread-onlymandatoryIndex of the humidity input
1.3.6.1.4.1.2769.10.7.6.1.3ColumnfilterHumidityEffectread-writemandatoryDetermines the way the result of humidity input comparison effects the filter. Can be switched off(1), inverted(3) or passed thru(2), if not needed.
1.3.6.1.4.1.2769.10.7.6.1.4ColumnfilterHumidityAThresread-writemandatoryThreshold of humidity input part A
1.3.6.1.4.1.2769.10.7.6.1.5ColumnfilterHumidityAModeread-writemandatoryDetermines the operating mode of comparison operation A. Can be set to greater(2) ' >', less(3) '<' or turned off(1), if not needed
1.3.6.1.4.1.2769.10.7.6.1.6ColumnfilterHumidityBThresread-writemandatoryThreshold of humidity input part B
1.3.6.1.4.1.2769.10.7.6.1.7ColumnfilterHumidityBModeread-writemandatoryDetermines the operating mode of comparison operation B. Can be set to greater(2) ' >', less(3) '<' or turned off(1), if not needed
1.3.6.1.4.1.2769.10.7.7TablefilterMainsTablenot-accessiblemandatoryTable containing information about mains inputs of each filter, i.e. thresholds and compare operations
1.3.6.1.4.1.2769.10.7.7.1RowfilterMainsEntrynot-accessiblemandatoryEach entry contains the description of one filter
1.3.6.1.4.1.2769.10.7.7.1.1ColumnfilterMainsIndexread-onlymandatoryIndex of the filter
1.3.6.1.4.1.2769.10.7.7.1.2ColumnfilterMainsSensorread-onlymandatoryIndex of the mains sensor
1.3.6.1.4.1.2769.10.7.7.1.3ColumnfilterMainsEffectread-writemandatoryDetermines the way the result of mains input comparison effects on the filter. Can be switched off(1), inverted(3) or passed thru (2).
1.3.6.1.4.1.2769.10.7.7.1.4ColumnfilterMainsAThresread-writemandatoryThreshold of mains input part B
1.3.6.1.4.1.2769.10.7.7.1.5ColumnfilterMainsAModeread-writemandatoryDetermines the operating mode of comparison operation A. Can be set to greater(2) ' >', less(3) '<' or turned off(1), if not needed
1.3.6.1.4.1.2769.10.7.7.1.6ColumnfilterMainsBThresread-writemandatoryThreshold of mains input part B
1.3.6.1.4.1.2769.10.7.7.1.7ColumnfilterMainsBModeread-writemandatoryDetermines the operating mode of comparison operation B. Can be set to greater(2) ' >', less(3) '<' or turned off(1), if not needed
1.3.6.1.4.1.2769.10.7.8TablefilterFeedbackTablenot-accessiblemandatoryTable containing information about feedback inputs
1.3.6.1.4.1.2769.10.7.8.1RowfilterFeedbackEntrynot-accessiblemandatoryEach entry contains the description of one filter
1.3.6.1.4.1.2769.10.7.8.1.1ColumnfilterFeedbackIndexread-onlymandatoryIndex of the filter
1.3.6.1.4.1.2769.10.7.8.1.2ColumnfilterFeedbackInputread-onlymandatoryIndex of the feedback input
1.3.6.1.4.1.2769.10.7.8.1.3ColumnfilterFeedbackInFilterread-writemandatoryNumber of the filter which is connected to this feedback input
1.3.6.1.4.1.2769.10.7.8.1.4ColumnfilterFeedbackDelayread-writemandatoryDelay time to wait until signal is forwarded
1.3.6.1.4.1.2769.10.7.8.1.5ColumnfilterFeedbackPassConditionread-writemandatoryDetermines the way an incoming signal is forwarded to the filter structure. If set to thru(1), all incoming signals are straight forwarded. If set to condition…
1.3.6.1.4.1.2769.10.7.8.1.6ColumnfilterFeedbackHoldread-writemandatoryDetermines the time the passed signal will be held up, after the falling edge of the original trigger signal. See timing diagram in manual for further details.
1.3.6.1.4.1.2769.10.7.8.1.7ColumnfilterFeedbackEffectread-writemandatoryDetermines the way the result of feedback input effects the filter. Can be switched off(1), inverted(3) or passed thru (2).
1.3.6.1.4.1.2769.10.8Nodemessage
1.3.6.1.4.1.2769.10.8.1TablemessageTablenot-accessiblemandatoryThe message table contains the logged filter events
1.3.6.1.4.1.2769.10.8.1.1RowmessageEntrynot-accessiblemandatoryEach entry contains information of one message
1.3.6.1.4.1.2769.10.8.1.1.1ColumnmessageIndexread-onlymandatoryIndex of message line
1.3.6.1.4.1.2769.10.8.1.1.2ColumnmessageFilterread-onlymandatoryNumber of filter which caused the message
1.3.6.1.4.1.2769.10.8.1.1.3ColumnmessageFilterDescrread-onlymandatoryName of the filter which caused the message
1.3.6.1.4.1.2769.10.8.1.1.4ColumnmessageTimeread-onlymandatoryTimestamp of event
1.3.6.1.4.1.2769.10.8.1.1.5ColumnmessagePriorityread-onlymandatoryPriority of the message. If set to no-priority(1) no message will be logged. The Priority has only informational character and doesn't affect the way it is han…
1.3.6.1.4.1.2769.10.8.1.1.6ColumnmessageAcknoledgedread-writemandatoryDisplays, if event was acknoledged already. Has only informational character for operator
1.3.6.1.4.1.2769.10.9Nodeuser
1.3.6.1.4.1.2769.10.9.1TableuserTablenot-accessiblemandatorySome infos about all registered users, e.g. name, right and chipcard key (if reader installed)
1.3.6.1.4.1.2769.10.9.1.1RowuserEntrynot-accessiblemandatoryEach entry contains information about one user
1.3.6.1.4.1.2769.10.9.1.1.1ColumnuserIndexread-onlymandatoryIndex of user. Is dynamically filled from 1..n
1.3.6.1.4.1.2769.10.9.1.1.2ColumnuserNameread-onlymandatoryname of one user
1.3.6.1.4.1.2769.10.9.1.1.3ColumnuserRightread-onlymandatoryAccess right of one user
1.3.6.1.4.1.2769.10.9.1.1.4ColumnuserChipcardKeyread-onlymandatoryDisplays the chipcard key of this user - only available, if optional chipcard reader installed.
1.3.6.1.4.1.2769.10.9.1.1.5ColumnuserChipcardAccessread-onlymandatoryHolds the status of the last access try via chipcard reader. In case of failure a rmsChipcardTrap will be sent.
1.3.6.1.4.1.2769.10.20Nodeaux
1.3.6.1.4.1.2769.10.20.1ScalarauxDeviceread-onlymandatoryAUX device number - currently supported numbers are 1 - <no device> 2 - Chipcard Reader The set of supported devices will grow. Check the support server from t…
1.3.6.1.4.1.2769.10.20.2ScalarauxDeviceNameread-onlymandatoryName of the device connected to the AUX port or <no device>.
1.3.6.1.4.1.2769.10.21Nodeicc
1.3.6.1.4.1.2769.10.21.1ScalarreaderConnectedread-onlymandatoryShows if chipcard reader is connected to the RMS
1.3.6.1.4.1.2769.10.21.2ScalarreaderCardInsideread-onlymandatoryShows if reader contains a chipcard
1.3.6.1.4.1.2769.10.21.3ScalarreaderCardKeyread-onlymandatoryShows key of chipcard in Chipcard Reader
1.3.6.1.4.1.2769.10.21.4ScalarreaderLEDcolorread-onlymandatoryShows if reader contains a chipcard
1.3.6.1.4.1.2769.10.21.5ScalaropenerLogicread-onlymandatoryLogic of door opener connected to chipcard reader. If make(1) Digital Out 4 will get short in case of successfull access attempt, and open else. If break(2) Di…
1.3.6.1.4.1.2769.10.21.6ScalaropenerOpenTimeread-onlymandatoryHow long the door opener (e.g. Digital Out 4) will get open/short in case of successfull access attempt (in secs).
1.3.6.1.4.1.2769.10.21.7ScalaropenerStateread-onlymandatoryCurrent state of the door opener.
1.3.6.1.4.1.2769.10.22Nodeups
1.3.6.1.4.1.2769.10.22.1ScalarupsConnectedread-onlymandatoryShows if ups is connected to AUX on the RMS
1.3.6.1.4.1.2769.10.22.2ScalarupsManufacturerread-onlycurrentThe name of the UPS manufacturer.
1.3.6.1.4.1.2769.10.22.3ScalarupsModelread-onlycurrentThe UPS Model designation.
1.3.6.1.4.1.2769.10.22.4ScalarupsFirmwareVersionread-onlycurrentThe UPS firmware/software version(s). This variable may or may not have the same value as upsIdentAgentSoftwareVersion in some implementations.
1.3.6.1.4.1.2769.10.22.5ScalarupsSoftwareVersionread-onlycurrentThe UPS agent software version. This variable may or may not have the same value as upsIdentUPSSoftwareVersion in some implementations.
1.3.6.1.4.1.2769.10.22.6ScalarupsIDread-writecurrentThe UPS Serial Number
1.3.6.1.4.1.2769.10.22.7ScalarupsBatteryLastReplacednot-accessiblecurrent
1.3.6.1.4.1.2769.10.22.8ScalarupsTimeOnBatteryread-onlycurrentIf the unit is on battery power, the elapsed time since the UPS last switched to battery power, or the time since the network management subsystem was last res…
1.3.6.1.4.1.2769.10.22.9ScalarupsTimeRemainingread-onlycurrentAn estimate of the time to battery charge depletion under the present load conditions if the utility power is off and remains off, or if it were to be lost and…
1.3.6.1.4.1.2769.10.22.10ScalarupsBatteryVoltageread-onlycurrentThe magnitude of the present battery voltage.
1.3.6.1.4.1.2769.10.22.11ScalarupsBatteryCurrentread-onlycurrentThe present battery current.
1.3.6.1.4.1.2769.10.22.12ScalarupsBatteryTempread-onlycurrentThe ambient temperature at or near the UPS Battery casing.
1.3.6.1.4.1.2769.10.22.13ScalarupsBatteryStatusread-onlycurrentThe indication of the capacity remaining in the UPS system's batteries. A value of batteryNormal indicates that the remaining run-time is greater than upsConfi…
1.3.6.1.4.1.2769.10.22.14ScalarupsLineFrequencyread-onlycurrentThe present input frequency.
1.3.6.1.4.1.2769.10.22.15ScalarupsLineVoltageread-onlycurrentThe magnitude of the present input voltage.
1.3.6.1.4.1.2769.10.22.16ScalarupsOutputVoltageread-onlycurrentThe present output voltage.
1.3.6.1.4.1.2769.10.22.17ScalarupsNominalOutputVoltageread-writecurrentThe magnitude of the nominal output voltage. On those systems which support read-write access to this object, if there is an attempt to set this variable to a …
1.3.6.1.4.1.2769.10.22.18ScalarupsOnlinenot-accessiblecurrent
1.3.6.1.4.1.2769.10.22.19ScalarupsCalibratingnot-accessiblecurrent
1.3.6.1.4.1.2769.10.22.20ScalarupsSleepingnot-accessiblecurrent
1.3.6.1.4.1.2769.10.22.21ScalarupsLoadnot-accessiblecurrent
1.3.6.1.4.1.2769.10.50NodermsChipcardTrapA rmsChipcardTrap signals any access by use of the (optional) chipcard reader. In any case all informations are transmitted.