RNX-UPDU-MIB
68 objects
UPDU MIB
Imported Objects
| SNMPv2-CONF | MODULE-COMPLIANCE OBJECT-GROUP |
| SNMPv2-SMI | Counter64 enterprises Integer32 MODULE-IDENTITY OBJECT-TYPE |
| SNMPv2-TC | TEXTUAL-CONVENTION |
| OID | Name | Access | Status | Description |
|---|---|---|---|---|
| 1.3.6.1.4.1.55108 | Identityrnx | UPDU MIB | ||
| 1.3.6.1.4.1.55108.1 | NodeupduMib | |||
| 1.3.6.1.4.1.55108.1.1 | NodeupduInfo | |||
| 1.3.6.1.4.1.55108.1.1.1 | ScalarupduInfoPartNumber | read-only | current | Part number |
| 1.3.6.1.4.1.55108.1.1.2 | ScalarupduInfoSerialNumber | read-only | current | Serial number |
| 1.3.6.1.4.1.55108.1.1.3 | ScalarupduInfoLotNumber | read-only | current | Lot number |
| 1.3.6.1.4.1.55108.1.2 | NodeupduInventory | |||
| 1.3.6.1.4.1.55108.1.2.1 | TableupduModuleTable | not-accessible | current | A list of module entries. |
| 1.3.6.1.4.1.55108.1.2.1.1 | RowupduModuleEntry | not-accessible | current | An entry containing information for a particular module. |
| 1.3.6.1.4.1.55108.1.2.1.1.1 | ColumnupduModuleIndex | not-accessible | current | Module index. |
| 1.3.6.1.4.1.55108.1.2.1.1.2 | ColumnupduModuleType | read-only | current | Module type: tells what type of module it is. |
| 1.3.6.1.4.1.55108.1.2.1.1.3 | ColumnupduModulePartNumber | read-only | current | Part number |
| 1.3.6.1.4.1.55108.1.2.1.1.4 | ColumnupduModuleSerialNumber | read-only | current | Module serial number. |
| 1.3.6.1.4.1.55108.1.2.1.1.5 | ColumnupduModuleLotNumber | read-only | current | Module lot number. |
| 1.3.6.1.4.1.55108.1.3 | NodeupduMeasurements | |||
| 1.3.6.1.4.1.55108.1.3.1 | TableupduMeterTable | not-accessible | current | Holds information about each Power module. |
| 1.3.6.1.4.1.55108.1.3.1.1 | RowupduMeterEntry | not-accessible | current | An entry provides a power data |
| 1.3.6.1.4.1.55108.1.3.1.1.1 | ColumnupduMeterIndex | not-accessible | current | Number of the meter on the Module. |
| 1.3.6.1.4.1.55108.1.3.1.1.2 | ColumnupduMeterName | read-only | current | Meter name. |
| 1.3.6.1.4.1.55108.1.3.1.1.3 | ColumnupduMeterType | read-only | current | Meter type: Tell if the meter is per-phase, per PDU, per module or for a single outlet or outlet group. For pduTotalCalc, phaseTotalCalc, moduleTotalCalc, the … |
| 1.3.6.1.4.1.55108.1.3.1.1.4 | ColumnupduMeterEnergyP | read-only | current | Positive active energy in watt hours. |
| 1.3.6.1.4.1.55108.1.3.1.1.5 | ColumnupduMeterEnergyR1 | read-only | current | Reactive energy from quadrant R1 in volt-ampere reactives hours. |
| 1.3.6.1.4.1.55108.1.3.1.1.6 | ColumnupduMeterEnergyR4 | read-only | current | Reactive energy from quadrant R4 in volt-ampere reactives hours. |
| 1.3.6.1.4.1.55108.1.3.1.1.7 | ColumnupduMeterPowerP | read-only | current | Active power at a given instant. |
| 1.3.6.1.4.1.55108.1.3.1.1.8 | ColumnupduMeterPowerQ | read-only | current | Reactive power at a given instant. |
| 1.3.6.1.4.1.55108.1.3.1.1.9 | ColumnupduMeterPowerS | read-only | current | Apparent power at a given instant. |
| 1.3.6.1.4.1.55108.1.3.1.1.10 | ColumnupduMeterUrms | read-only | current | RMS voltage at a given instant. |
| 1.3.6.1.4.1.55108.1.3.1.1.11 | ColumnupduMeterIrms | read-only | current | RMS current at a given instant. |
| 1.3.6.1.4.1.55108.1.3.1.1.12 | ColumnupduMeterSystemName | read-only | current | System-defined object name. |
| 1.3.6.1.4.1.55108.1.3.1.1.13 | ColumnupduMeterCustomName | read-write | current | User-configured unique object name. Write access has to be explicitly enabled in the UPDU configuration (see SNMP options). |
| 1.3.6.1.4.1.55108.1.3.1.1.14 | ColumnupduMeterDescription | read-write | current | User-configured description. Write access has to be explicitly enabled in the UPDU configuration (see SNMP options). |
| 1.3.6.1.4.1.55108.1.3.2 | TableupduSensorTable | not-accessible | current | Holds information about sensors connected to the PDU. |
| 1.3.6.1.4.1.55108.1.3.2.1 | RowupduSensorEntry | not-accessible | current | Holds the information related to one specific sensor. |
| 1.3.6.1.4.1.55108.1.3.2.1.1 | ColumnupduSensorPort | not-accessible | current | Sensor port number. |
| 1.3.6.1.4.1.55108.1.3.2.1.2 | ColumnupduSensorPortName | read-only | current | Sensor port name as printed on the front plate. |
| 1.3.6.1.4.1.55108.1.3.2.1.3 | ColumnupduSensorType | read-only | current | Sensor type. |
| 1.3.6.1.4.1.55108.1.3.2.1.4 | ColumnupduSensorTemperatureCelsius | read-only | current | Temperature in tenth degrees. |
| 1.3.6.1.4.1.55108.1.3.2.1.5 | ColumnupduSensorHumidity | read-only | current | Relative humidity in per mil. Set to 0 for temperature only sensor. |
| 1.3.6.1.4.1.55108.1.3.3 | TableupduRcmTable | not-accessible | current | Holds information about embedded residual current monitors. |
| 1.3.6.1.4.1.55108.1.3.3.1 | RowupduRcmEntry | not-accessible | current | An entry provides Residual current data |
| 1.3.6.1.4.1.55108.1.3.3.1.1 | ColumnupduRcmIndex | not-accessible | current | RCM index. |
| 1.3.6.1.4.1.55108.1.3.3.1.2 | ColumnupduRcmName | read-only | current | RCM name. |
| 1.3.6.1.4.1.55108.1.3.3.1.3 | ColumnupduRcmCurrentRms | read-only | current | RMS residual current. |
| 1.3.6.1.4.1.55108.1.3.3.1.4 | ColumnupduRcmCurrentDc | read-only | current | DC residual current. |
| 1.3.6.1.4.1.55108.1.3.3.1.5 | ColumnupduRcmSensorQuality | read-only | current | RCM sensor health |
| 1.3.6.1.4.1.55108.1.4 | NodeupduControl | |||
| 1.3.6.1.4.1.55108.1.4.1 | TableupduRelayTable | not-accessible | current | Holds Relay state. |
| 1.3.6.1.4.1.55108.1.4.1.1 | RowupduRelayEntry | not-accessible | current | An entry provides the status for a relay. |
| 1.3.6.1.4.1.55108.1.4.1.1.1 | ColumnupduRelayIndex | not-accessible | current | Relay index. |
| 1.3.6.1.4.1.55108.1.4.1.1.2 | ColumnupduRelayMeterNames | read-only | current | Comma-separated list of meter names this relay controls. |
| 1.3.6.1.4.1.55108.1.4.1.1.3 | ColumnupduRelayAdminStatus | read-write | current | Defines the desired state of the relay. |
| 1.3.6.1.4.1.55108.1.4.1.1.4 | ColumnupduRelayOperStatus | read-only | current | Defines the operational state of the relay. |
| 1.3.6.1.4.1.55108.1.4.1.1.5 | ColumnupduRelayCondition | read-only | current | Gives the relay condition. Ok if the desired state corresponds to the operational state, failed if it differs and unknown if the operational state is not known. |
| 1.3.6.1.4.1.55108.1.5 | NodeupduConformance | |||
| 1.3.6.1.4.1.55108.1.5.1 | NodeupduMibCompliances | |||
| 1.3.6.1.4.1.55108.1.5.1.1 | ComplianceupduMibCompliance | current | The compliance statement for SNMP entities which implement the RNX-UPDU-MIB. | |
| 1.3.6.1.4.1.55108.1.5.2 | NodeupduMibGroups | |||
| 1.3.6.1.4.1.55108.1.5.2.1 | GroupupduMibGroupRev1 | current | rev 1 |
Type Definitions
| Name | Syntax | Status | Description |
|---|---|---|---|
| MilliAmperes | Integer32 | current | Milli-amperes |
| MilliVolts | Integer32 | current | Milli-volts |
| Permil | Integer32 | current | Per mil |
| TenthDegreesCelsius | Integer32 | current | Deci-degrees celsius |
| TenthMilliAmperes | Integer32 | current | Tenth of Milli-amperes |
| VoltAmpereReactiveHours | Counter64 | current | Volt-ampere reactive hours |
| VoltAmpereReactives | Integer32 | current | Volt-ampere reactives |
| VoltAmperes | Integer32 | current | Volt-amperes |
| WattHours | Counter64 | current | Watt hours |
| Watts | Integer32 | current | Watts |