MIB Viewer

RNX-UPDU-MIB

68 objects
UPDU MIB
Imported Objects
SNMPv2-CONFMODULE-COMPLIANCE OBJECT-GROUP
SNMPv2-SMICounter64 enterprises Integer32 MODULE-IDENTITY OBJECT-TYPE
SNMPv2-TCTEXTUAL-CONVENTION
OIDNameAccessStatusDescription
1.3.6.1.4.1.55108IdentityrnxUPDU MIB
1.3.6.1.4.1.55108.1NodeupduMib
1.3.6.1.4.1.55108.1.1NodeupduInfo
1.3.6.1.4.1.55108.1.1.1ScalarupduInfoPartNumberread-onlycurrentPart number
1.3.6.1.4.1.55108.1.1.2ScalarupduInfoSerialNumberread-onlycurrentSerial number
1.3.6.1.4.1.55108.1.1.3ScalarupduInfoLotNumberread-onlycurrentLot number
1.3.6.1.4.1.55108.1.2NodeupduInventory
1.3.6.1.4.1.55108.1.2.1TableupduModuleTablenot-accessiblecurrentA list of module entries.
1.3.6.1.4.1.55108.1.2.1.1RowupduModuleEntrynot-accessiblecurrentAn entry containing information for a particular module.
1.3.6.1.4.1.55108.1.2.1.1.1ColumnupduModuleIndexnot-accessiblecurrentModule index.
1.3.6.1.4.1.55108.1.2.1.1.2ColumnupduModuleTyperead-onlycurrentModule type: tells what type of module it is.
1.3.6.1.4.1.55108.1.2.1.1.3ColumnupduModulePartNumberread-onlycurrentPart number
1.3.6.1.4.1.55108.1.2.1.1.4ColumnupduModuleSerialNumberread-onlycurrentModule serial number.
1.3.6.1.4.1.55108.1.2.1.1.5ColumnupduModuleLotNumberread-onlycurrentModule lot number.
1.3.6.1.4.1.55108.1.3NodeupduMeasurements
1.3.6.1.4.1.55108.1.3.1TableupduMeterTablenot-accessiblecurrentHolds information about each Power module.
1.3.6.1.4.1.55108.1.3.1.1RowupduMeterEntrynot-accessiblecurrentAn entry provides a power data
1.3.6.1.4.1.55108.1.3.1.1.1ColumnupduMeterIndexnot-accessiblecurrentNumber of the meter on the Module.
1.3.6.1.4.1.55108.1.3.1.1.2ColumnupduMeterNameread-onlycurrentMeter name.
1.3.6.1.4.1.55108.1.3.1.1.3ColumnupduMeterTyperead-onlycurrentMeter type: Tell if the meter is per-phase, per PDU, per module or for a single outlet or outlet group. For pduTotalCalc, phaseTotalCalc, moduleTotalCalc, the …
1.3.6.1.4.1.55108.1.3.1.1.4ColumnupduMeterEnergyPread-onlycurrentPositive active energy in watt hours.
1.3.6.1.4.1.55108.1.3.1.1.5ColumnupduMeterEnergyR1read-onlycurrentReactive energy from quadrant R1 in volt-ampere reactives hours.
1.3.6.1.4.1.55108.1.3.1.1.6ColumnupduMeterEnergyR4read-onlycurrentReactive energy from quadrant R4 in volt-ampere reactives hours.
1.3.6.1.4.1.55108.1.3.1.1.7ColumnupduMeterPowerPread-onlycurrentActive power at a given instant.
1.3.6.1.4.1.55108.1.3.1.1.8ColumnupduMeterPowerQread-onlycurrentReactive power at a given instant.
1.3.6.1.4.1.55108.1.3.1.1.9ColumnupduMeterPowerSread-onlycurrentApparent power at a given instant.
1.3.6.1.4.1.55108.1.3.1.1.10ColumnupduMeterUrmsread-onlycurrentRMS voltage at a given instant.
1.3.6.1.4.1.55108.1.3.1.1.11ColumnupduMeterIrmsread-onlycurrentRMS current at a given instant.
1.3.6.1.4.1.55108.1.3.1.1.12ColumnupduMeterSystemNameread-onlycurrentSystem-defined object name.
1.3.6.1.4.1.55108.1.3.1.1.13ColumnupduMeterCustomNameread-writecurrentUser-configured unique object name. Write access has to be explicitly enabled in the UPDU configuration (see SNMP options).
1.3.6.1.4.1.55108.1.3.1.1.14ColumnupduMeterDescriptionread-writecurrentUser-configured description. Write access has to be explicitly enabled in the UPDU configuration (see SNMP options).
1.3.6.1.4.1.55108.1.3.2TableupduSensorTablenot-accessiblecurrentHolds information about sensors connected to the PDU.
1.3.6.1.4.1.55108.1.3.2.1RowupduSensorEntrynot-accessiblecurrentHolds the information related to one specific sensor.
1.3.6.1.4.1.55108.1.3.2.1.1ColumnupduSensorPortnot-accessiblecurrentSensor port number.
1.3.6.1.4.1.55108.1.3.2.1.2ColumnupduSensorPortNameread-onlycurrentSensor port name as printed on the front plate.
1.3.6.1.4.1.55108.1.3.2.1.3ColumnupduSensorTyperead-onlycurrentSensor type.
1.3.6.1.4.1.55108.1.3.2.1.4ColumnupduSensorTemperatureCelsiusread-onlycurrentTemperature in tenth degrees.
1.3.6.1.4.1.55108.1.3.2.1.5ColumnupduSensorHumidityread-onlycurrentRelative humidity in per mil. Set to 0 for temperature only sensor.
1.3.6.1.4.1.55108.1.3.3TableupduRcmTablenot-accessiblecurrentHolds information about embedded residual current monitors.
1.3.6.1.4.1.55108.1.3.3.1RowupduRcmEntrynot-accessiblecurrentAn entry provides Residual current data
1.3.6.1.4.1.55108.1.3.3.1.1ColumnupduRcmIndexnot-accessiblecurrentRCM index.
1.3.6.1.4.1.55108.1.3.3.1.2ColumnupduRcmNameread-onlycurrentRCM name.
1.3.6.1.4.1.55108.1.3.3.1.3ColumnupduRcmCurrentRmsread-onlycurrentRMS residual current.
1.3.6.1.4.1.55108.1.3.3.1.4ColumnupduRcmCurrentDcread-onlycurrentDC residual current.
1.3.6.1.4.1.55108.1.3.3.1.5ColumnupduRcmSensorQualityread-onlycurrentRCM sensor health
1.3.6.1.4.1.55108.1.4NodeupduControl
1.3.6.1.4.1.55108.1.4.1TableupduRelayTablenot-accessiblecurrentHolds Relay state.
1.3.6.1.4.1.55108.1.4.1.1RowupduRelayEntrynot-accessiblecurrentAn entry provides the status for a relay.
1.3.6.1.4.1.55108.1.4.1.1.1ColumnupduRelayIndexnot-accessiblecurrentRelay index.
1.3.6.1.4.1.55108.1.4.1.1.2ColumnupduRelayMeterNamesread-onlycurrentComma-separated list of meter names this relay controls.
1.3.6.1.4.1.55108.1.4.1.1.3ColumnupduRelayAdminStatusread-writecurrentDefines the desired state of the relay.
1.3.6.1.4.1.55108.1.4.1.1.4ColumnupduRelayOperStatusread-onlycurrentDefines the operational state of the relay.
1.3.6.1.4.1.55108.1.4.1.1.5ColumnupduRelayConditionread-onlycurrentGives the relay condition. Ok if the desired state corresponds to the operational state, failed if it differs and unknown if the operational state is not known.
1.3.6.1.4.1.55108.1.5NodeupduConformance
1.3.6.1.4.1.55108.1.5.1NodeupduMibCompliances
1.3.6.1.4.1.55108.1.5.1.1ComplianceupduMibCompliancecurrentThe compliance statement for SNMP entities which implement the RNX-UPDU-MIB.
1.3.6.1.4.1.55108.1.5.2NodeupduMibGroups
1.3.6.1.4.1.55108.1.5.2.1GroupupduMibGroupRev1currentrev 1
Type Definitions
NameSyntaxStatusDescription
MilliAmperesInteger32currentMilli-amperes
MilliVoltsInteger32currentMilli-volts
PermilInteger32currentPer mil
TenthDegreesCelsiusInteger32currentDeci-degrees celsius
TenthMilliAmperesInteger32currentTenth of Milli-amperes
VoltAmpereReactiveHoursCounter64currentVolt-ampere reactive hours
VoltAmpereReactivesInteger32currentVolt-ampere reactives
VoltAmperesInteger32currentVolt-amperes
WattHoursCounter64currentWatt hours
WattsInteger32currentWatts