ROOMALERT11E-MIB

105 objects
No module-level DESCRIPTION found.
OIDNameAccessStatusDescription
1.3.6.1.4.1.20916Nodeavtech
1.3.6.1.4.1.20916.1Nodeproducts
1.3.6.1.4.1.20916.1.3Noderoomalert11E
1.3.6.1.4.1.20916.1.3.1Nodesensors
1.3.6.1.4.1.20916.1.3.1NodetempAlarm1-11eA tempAlarm1 trap signifies that the current temperature on external sensor 1 is outside the defined high or low threshold.
1.3.6.1.4.1.20916.1.3.1.1Nodechannel1
1.3.6.1.4.1.20916.1.3.1.1.1Scalarsensor1-1read-onlymandatoryThe reading for internal switch sensor 1 (0 = OPEN, 1 = CLOSED).
1.3.6.1.4.1.20916.1.3.1.1.2Scalarsensor1-2read-onlymandatoryThe reading for internal switch sensor 2 (0 = OPEN, 1 = CLOSED).
1.3.6.1.4.1.20916.1.3.1.1.3Scalarsensor1-3read-onlymandatoryThe reading for internal switch sensor 3 (0 = OPEN, 1 = CLOSED).
1.3.6.1.4.1.20916.1.3.1.1.4Scalarsensor1-4read-onlymandatoryThe reading for internal switch sensor 4 (0 = OPEN, 1 = CLOSED).
1.3.6.1.4.1.20916.1.3.1.1.5Scalarsensor1-5read-onlymandatoryThe reading for internal switch sensor 5 (0 = OPEN, 1 = CLOSED).
1.3.6.1.4.1.20916.1.3.1.1.6Scalarsensor1-6read-onlymandatoryThe reading for internal switch sensor 6 (0 = OPEN, 1 = CLOSED).
1.3.6.1.4.1.20916.1.3.1.1.7Scalarsensor1-7read-onlymandatoryThe reading for internal switch sensor 7 (0 = OPEN, 1 = CLOSED).
1.3.6.1.4.1.20916.1.3.1.1.8Scalarsensor1-8read-onlymandatoryThe reading for internal switch sensor 8 (0 = OPEN, 1 = CLOSED).
1.3.6.1.4.1.20916.1.3.1.1.9Scalarswitch-label-1read-onlymandatoryThe label for switch sensor 1
1.3.6.1.4.1.20916.1.3.1.1.10Scalarswitch-label-2read-onlymandatoryThe label for switch sensor 2
1.3.6.1.4.1.20916.1.3.1.1.11Scalarswitch-label-3read-onlymandatoryThe label for switch sensor 3
1.3.6.1.4.1.20916.1.3.1.1.12Scalarswitch-label-4read-onlymandatoryThe label for switch sensor 4
1.3.6.1.4.1.20916.1.3.1.1.13Scalarswitch-label-5read-onlymandatoryThe label for switch sensor 5
1.3.6.1.4.1.20916.1.3.1.1.14Scalarswitch-label-6read-onlymandatoryThe label for switch sensor 6
1.3.6.1.4.1.20916.1.3.1.1.15Scalarswitch-label-7read-onlymandatoryThe label for switch sensor 7
1.3.6.1.4.1.20916.1.3.1.1.16Scalarswitch-label-8read-onlymandatoryThe label for switch sensor 8
1.3.6.1.4.1.20916.1.3.1.2Nodechannel2
1.3.6.1.4.1.20916.1.3.1.2.1Scalarsensor2-1read-onlymandatoryThe reading for sensor 2-1. If a temp or temp/humidity sensor is connected, value will be current temperature in Celsius.
1.3.6.1.4.1.20916.1.3.1.2.2Scalarsensor2-2read-onlymandatoryThe reading for sensor 2-2. If a temp or temp/humidity sensor is connected, value will be current temperature in Fahrenheit.
1.3.6.1.4.1.20916.1.3.1.2.3Scalarsensor2-3read-onlymandatoryThe reading for sensor 2-3. If temp/humidity sensor is connected, value will be current %RH.
1.3.6.1.4.1.20916.1.3.1.2.4Scalarsensor2-4read-onlymandatoryThe reading for sensor 2-4. If temp/humidity sensor is connected, value will be current Heat Index in Fahrenheit.
1.3.6.1.4.1.20916.1.3.1.2.5Scalarsensor2-5read-onlymandatoryThe reading for sensor 2-5. If temp/humidity sensor is connected, value will be current Heat Index in Celsius.
1.3.6.1.4.1.20916.1.3.1.2.6Scalarsensor2-6-labelread-onlymandatoryThe label of this sensor
1.3.6.1.4.1.20916.1.3.1.3Nodechannel3
1.3.6.1.4.1.20916.1.3.1.3.1Scalarsensor3-1read-onlymandatoryThe reading for sensor 3-1. If a temp or temp/humidity sensor is connected, value will be current temperature in Celsius.
1.3.6.1.4.1.20916.1.3.1.3.2Scalarsensor3-2read-onlymandatoryThe reading for sensor 3-2. If a temp or temp/humidity sensor is connected, value will be current temperature in Fahrenheit.
1.3.6.1.4.1.20916.1.3.1.3.3Scalarsensor3-3read-onlymandatoryThe reading for sensor 3-3. If temp/humidity sensor is connected, value will be current %RH.
1.3.6.1.4.1.20916.1.3.1.3.4Scalarsensor3-4read-onlymandatoryThe reading for sensor 3-4. If temp/humidity sensor is connected, value will be current Heat Index in Fahrenheit.
1.3.6.1.4.1.20916.1.3.1.3.5Scalarsensor3-5read-onlymandatoryThe reading for sensor 3-5. If temp/humidity sensor is connected, value will be current Heat Index in Celsius.
1.3.6.1.4.1.20916.1.3.1.3.6Scalarsensor3-6-labelread-onlymandatoryThe label of this sensor
1.3.6.1.4.1.20916.1.3.1.4Nodechannel4
1.3.6.1.4.1.20916.1.3.1.4.1Scalarsensor4-1read-onlymandatoryThe reading for sensor 4-1. If a temp or temp/humidity sensor is connected, value will be current temperature in Celsius.
1.3.6.1.4.1.20916.1.3.1.4.2Scalarsensor4-2read-onlymandatoryThe reading for sensor 4-2. If a temp or temp/humidity sensor is connected, value will be current temperature in Fahrenheit.
1.3.6.1.4.1.20916.1.3.1.4.3Scalarsensor4-3read-onlymandatoryThe reading for sensor 4-3. If temp/humidity sensor is connected, value will be current %RH.
1.3.6.1.4.1.20916.1.3.1.4.4Scalarsensor4-4read-onlymandatoryThe reading for sensor 4-4. If temp/humidity sensor is connected, value will be current Heat Index in Fahrenheit.
1.3.6.1.4.1.20916.1.3.1.4.5Scalarsensor4-5read-onlymandatoryThe reading for sensor 4-5. If temp/humidity sensor is connected, value will be current Heat Index in Celsius.
1.3.6.1.4.1.20916.1.3.1.4.6Scalarsensor4-6-labelread-onlymandatoryThe label of this sensor
1.3.6.1.4.1.20916.1.3.2Noderoom-alert-11E-SNMP-trapA Room Alert 11E SNMP Trap indicates that an alarm condition has occurred on the sensor inidcated by the alarmMessage variable.
1.3.6.1.4.1.20916.1.3.2Nodetraps
1.3.6.1.4.1.20916.1.3.2.1Scalaralarm1read-onlymandatoryAlarm for sensor channel 1. The binary equivalent of the decimal number displayed will indicate which switch sensors are currently in an alarm state (0 = senso…
1.3.6.1.4.1.20916.1.3.2.2Scalaralarm2read-onlymandatoryAlarm for sensor channel 2. If a digital temperature/humidity or digital temperature sensor is connected to this channel, 0 = sensor ok, 1 = high temp alarm, 2…
1.3.6.1.4.1.20916.1.3.2.3Scalaralarm3read-onlymandatoryAlarm for sensor channel 3. If a digital temperature/humidity or digital temperature sensor is connected to this channel, 0 = sensor ok, 1 = high temp alarm, 2…
1.3.6.1.4.1.20916.1.3.2.4Scalaralarm4read-onlymandatoryAlarm for sensor channel 4. If a digital temperature/humidity or digital temperature sensor is connected to this channel, 0 = sensor ok, 1 = high temp alarm, 2…
1.3.6.1.4.1.20916.1.3.2.5ScalaralarmMessage1read-onlymandatoryAlarm Message from sensor channel 1 (Internal)
1.3.6.1.4.1.20916.1.3.2.6ScalaralarmMessage2read-onlymandatoryAlarm Message from sensor channel 2 (External)
1.3.6.1.4.1.20916.1.3.2.7ScalaralarmMessage3read-onlymandatoryAlarm Message from sensor channel 3 (External)
1.3.6.1.4.1.20916.1.3.2.8ScalaralarmMessage4read-onlymandatoryAlarm Message from sensor channel 4 (External)
1.3.6.1.4.1.20916.1.3.3NodetempAlarm2-11eA tempAlarm2 trap signifies that the current temperature on external sensor 2 is outside the defined high or low threshold.
1.3.6.1.4.1.20916.1.3.3Nodethresholds
1.3.6.1.4.1.20916.1.3.3.1Nodechannels
1.3.6.1.4.1.20916.1.3.3.1.1Nodechannels1
1.3.6.1.4.1.20916.1.3.3.1.1.1Scalarthreshold1-1read-onlymandatoryThreshold 1 defined for Channel 1
1.3.6.1.4.1.20916.1.3.3.1.1.2Scalarthreshold1-2read-onlymandatoryThreshold 2 defined for Channel 1
1.3.6.1.4.1.20916.1.3.3.1.1.3Scalarthreshold1-3read-onlymandatoryThreshold 3 defined for Channel 1
1.3.6.1.4.1.20916.1.3.3.1.1.4Scalarthreshold1-4read-onlymandatoryThreshold 4 defined for Channel 1
1.3.6.1.4.1.20916.1.3.3.1.1.5Scalarthreshold1-5read-onlymandatoryThreshold 5 defined for Channel 1
1.3.6.1.4.1.20916.1.3.3.1.1.6Scalarthreshold1-6read-onlymandatoryThreshold 6 defined for Channel 1
1.3.6.1.4.1.20916.1.3.3.1.1.7Scalarthreshold1-7read-onlymandatoryThreshold 7 defined for Channel 1
1.3.6.1.4.1.20916.1.3.3.1.1.8Scalarthreshold1-8read-onlymandatoryThreshold 8 defined for Channel 1
1.3.6.1.4.1.20916.1.3.3.1.2Nodechannels2
1.3.6.1.4.1.20916.1.3.3.1.2.1Scalarthreshold2-1read-onlymandatoryThreshold 1 defined for Channel 2
1.3.6.1.4.1.20916.1.3.3.1.2.2Scalarthreshold2-2read-onlymandatoryThreshold 2 defined for Channel 2
1.3.6.1.4.1.20916.1.3.3.1.2.3Scalarthreshold2-3read-onlymandatoryThreshold 3 defined for Channel 2
1.3.6.1.4.1.20916.1.3.3.1.2.4Scalarthreshold2-4read-onlymandatoryThreshold 4 defined for Channel 2
1.3.6.1.4.1.20916.1.3.3.1.3Nodechannels3
1.3.6.1.4.1.20916.1.3.3.1.3.1Scalarthreshold3-1read-onlymandatoryThreshold 1 defined for Channel 3
1.3.6.1.4.1.20916.1.3.3.1.3.2Scalarthreshold3-2read-onlymandatoryThreshold 2 defined for Channel 3
1.3.6.1.4.1.20916.1.3.3.1.3.3Scalarthreshold3-3read-onlymandatoryThreshold 3 defined for Channel 3
1.3.6.1.4.1.20916.1.3.3.1.3.4Scalarthreshold3-4read-onlymandatoryThreshold 4 defined for Channel 3
1.3.6.1.4.1.20916.1.3.3.1.4Nodechannels4
1.3.6.1.4.1.20916.1.3.3.1.4.1Scalarthreshold4-1read-onlymandatoryThreshold 1 defined for Channel 4
1.3.6.1.4.1.20916.1.3.3.1.4.2Scalarthreshold4-2read-onlymandatoryThreshold 2 defined for Channel 4
1.3.6.1.4.1.20916.1.3.3.1.4.3Scalarthreshold4-3read-onlymandatoryThreshold 3 defined for Channel 4
1.3.6.1.4.1.20916.1.3.3.1.4.4Scalarthreshold4-4read-onlymandatoryThreshold 4 defined for Channel 4
1.3.6.1.4.1.20916.1.3.4NodetempClear2-11eA tempClear2 trap signifies that the current temperature on external sensor 2 has returned to a normal condition and is within the defined high or low threshol…
1.3.6.1.4.1.20916.1.3.5NodetempAlarm3-11eA tempAlarm3 trap signifies that the current temperature on external sensor 3 is outside the defined high or low threshold.
1.3.6.1.4.1.20916.1.3.6NodetempClear3-11eA tempClear3 trap signifies that the current temperature on external sensor 3 has returned to a normal condition and is within the defined high or low threshol…
1.3.6.1.4.1.20916.1.3.7NodehumidityAlarm1-11eA humidityAlarm1 trap signifies that the current humidity on external sensor 1 is outside the defined high or low threshold.
1.3.6.1.4.1.20916.1.3.8NodehumidityClear1-11eA humidityClear1 trap signifies that the current humidity on external sensor 1 has returned to a normal condition and is within the defined high or low thresho…
1.3.6.1.4.1.20916.1.3.9NodehumidityAlarm2-11eA humidityAlarm2 trap signifies that the current humidity on external sensor 2 is outside the defined high or low threshold.
1.3.6.1.4.1.20916.1.3.10NodehumidityClear2-11eA humidityClear2 trap signifies that the current humidity on external sensor 2 has returned to a normal condition and is within the defined high or low thresho…
1.3.6.1.4.1.20916.1.3.11NodehumidityAlarm3-11eA humidityAlarm3 trap signifies that the current humidity on external sensor 3 is outside the defined high or low threshold.
1.3.6.1.4.1.20916.1.3.12NodehumidityClear3-11eA humidityClear3 trap signifies that the current humidity on external sensor 3 has returned to a normal condition and is within the defined high or low thresho…
1.3.6.1.4.1.20916.1.3.13NodeswitchAlarm1-11eA switchAlarm1 trap signifies that switch sensor 1 is in an alarm state.
1.3.6.1.4.1.20916.1.3.14NodeswitchClear1-11eA switchClear1 trap signifies that the switch sensor 1 has returned to a normal state.
1.3.6.1.4.1.20916.1.3.15NodeswitchAlarm2-11eA switchAlarm2 trap signifies that switch sensor 2 is in an alarm state.
1.3.6.1.4.1.20916.1.3.16NodeswitchClear2-11eA switchClear2 trap signifies that the switch sensor 2 has returned to a normal state.
1.3.6.1.4.1.20916.1.3.17NodeswitchAlarm3-11eA switchAlarm1 trap signifies that switch sensor 1 is in an alarm state.
1.3.6.1.4.1.20916.1.3.18NodeswitchClear3-11eA switchClear3 trap signifies that the switch sensor 3 has returned to a normal state.
1.3.6.1.4.1.20916.1.3.19NodeswitchAlarm4-11eA switchAlarm4 trap signifies that switch sensor 4 is in an alarm state.
1.3.6.1.4.1.20916.1.3.20NodeswitchClear4-11eA switchClear4 trap signifies that the switch sensor 4 has returned to a normal state.
1.3.6.1.4.1.20916.1.3.21NodeswitchAlarm5-11eA switchAlarm5 trap signifies that switch sensor 5 is in an alarm state.
1.3.6.1.4.1.20916.1.3.22NodeswitchClear5-11eA switchClear5 trap signifies that the switch sensor 5 has returned to a normal state.
1.3.6.1.4.1.20916.1.3.23NodeswitchAlarm6-11eA switchAlarm6 trap signifies that switch sensor 6 is in an alarm state.
1.3.6.1.4.1.20916.1.3.24NodeswitchClear6-11eA switchClear6 trap signifies that the switch sensor 6 has returned to a normal state.
1.3.6.1.4.1.20916.1.3.25NodeswitchAlarm7-11eA switchAlarm7 trap signifies that switch sensor 7 is in an alarm state.
1.3.6.1.4.1.20916.1.3.26NodeswitchClear7-11eA switchClear7 trap signifies that the switch sensor 7 has returned to a normal state.
1.3.6.1.4.1.20916.1.3.27NodeswitchAlarm8-11eA switchAlarm8 trap signifies that switch sensor 8 is in an alarm state.
1.3.6.1.4.1.20916.1.3.28NodeswitchClear8-11eA switchClear8 trap signifies that the switch sensor 8 has returned to a normal state.