MIB Viewer

ROOMALERT12S-MIB

77 objects
No module-level DESCRIPTION found.
Imported Objects
RFC1155-SMIenterprises Gauge IpAddress TimeTicks
RFC1213-MIBDisplayString system
SNMPv2-SMINOTIFICATION-TYPE
OIDNameAccessStatusDescription
1.3.6.1.4.1.20916Nodeavtech
1.3.6.1.4.1.20916.1Nodeproducts
1.3.6.1.4.1.20916.1.12Noderoomalert12S
1.3.6.1.4.1.20916.1.12.1Nodesensors
1.3.6.1.4.1.20916.1.12.1.1Nodeinternal
1.3.6.1.4.1.20916.1.12.1.1.1Nodetemperature
1.3.6.1.4.1.20916.1.12.1.1.1.1Scalarinternal-tempfread-onlymandatoryThe internal temperature reading in Fahrenheit.
1.3.6.1.4.1.20916.1.12.1.1.1.2Scalarinternal-tempcread-onlymandatoryThe internal temperature reading in Celsius.
1.3.6.1.4.1.20916.1.12.1.1.2Nodeanalog
1.3.6.1.4.1.20916.1.12.1.1.2.1Scalarinternal-analog1read-onlymandatoryThe current status of the Room Alert 12S analog input (0-5VDC).
1.3.6.1.4.1.20916.1.12.1.1.2.2Scalarinternal-analog-computed1read-onlymandatoryThe current computed value of the Room Alert 12S analog input.
1.3.6.1.4.1.20916.1.12.1.1.2.3Scalarinternal-analog-computed-units1read-onlymandatoryThe computed analog units for the Room Alert 12S analog input..
1.3.6.1.4.1.20916.1.12.1.1.3Noderelay
1.3.6.1.4.1.20916.1.12.1.1.3.1Scalarinternal-relay1read-writemandatoryThe status of the on-board relay output
1.3.6.1.4.1.20916.1.12.1.2Nodedigital
1.3.6.1.4.1.20916.1.12.1.2.1Nodedigital-sen1
1.3.6.1.4.1.20916.1.12.1.2.1.1Scalardigital-sen1-1read-onlymandatoryThe sensor's current temperature in Celsius.
1.3.6.1.4.1.20916.1.12.1.2.1.2Scalardigital-sen1-2read-onlymandatoryThe sensor's current temperature in Fahrenheit.
1.3.6.1.4.1.20916.1.12.1.2.1.3Scalardigital-sen1-3read-onlymandatoryVaries by sensor type: current % relative humidity, voltage reading (V), power state (1=Power Detected, 0=No Power Detected), thermocouple temperature (C), or …
1.3.6.1.4.1.20916.1.12.1.2.1.4Scalardigital-sen1-4read-onlymandatoryVaries by sensor type: current heat index (F), custom analog reading, thermocouple temperature (F), or air speed (f/m).
1.3.6.1.4.1.20916.1.12.1.2.1.5Scalardigital-sen1-5read-onlymandatoryVaries by sensor type: current heat index (C), thermocouple fault code (0=No Fault), or air flow (CMH).
1.3.6.1.4.1.20916.1.12.1.2.1.6Scalardigital-sen1-6read-onlymandatoryVaries by sensor type: current dew point (C) or air flow (CFM).
1.3.6.1.4.1.20916.1.12.1.2.1.7Scalardigital-sen1-7read-onlymandatoryVaries by sensor type: current dew point (F).
1.3.6.1.4.1.20916.1.12.1.2.1.8Scalardigital-sen1-8read-onlymandatoryThe computed analog units for the Room Alert 32S analog input..
1.3.6.1.4.1.20916.1.12.1.2.2Nodedigital-sen2
1.3.6.1.4.1.20916.1.12.1.2.2.1Scalardigital-sen2-1read-onlymandatoryThe sensor's current temperature in Celsius.
1.3.6.1.4.1.20916.1.12.1.2.2.2Scalardigital-sen2-2read-onlymandatoryThe sensor's current temperature in Fahrenheit.
1.3.6.1.4.1.20916.1.12.1.2.2.3Scalardigital-sen2-3read-onlymandatoryVaries by sensor type: current % relative humidity, voltage reading (V), power state (1=Power Detected, 0=No Power Detected), thermocouple temperature (C), or …
1.3.6.1.4.1.20916.1.12.1.2.2.4Scalardigital-sen2-4read-onlymandatoryVaries by sensor type: current heat index (F), custom analog reading, thermocouple temperature (F), or air speed (f/m).
1.3.6.1.4.1.20916.1.12.1.2.2.5Scalardigital-sen2-5read-onlymandatoryVaries by sensor type: current heat index (C), thermocouple fault code (0=No Fault), or air flow (CMH).
1.3.6.1.4.1.20916.1.12.1.2.2.6Scalardigital-sen2-6read-onlymandatoryVaries by sensor type: current dew point (C) or air flow (CFM).
1.3.6.1.4.1.20916.1.12.1.2.2.7Scalardigital-sen2-7read-onlymandatoryVaries by sensor type: current dew point (F).
1.3.6.1.4.1.20916.1.12.1.2.2.8Scalardigital-sen2-8read-onlymandatoryThe computed analog units for the Room Alert 32S analog input..
1.3.6.1.4.1.20916.1.12.1.2.3Nodedigital-sen3
1.3.6.1.4.1.20916.1.12.1.2.3.1Scalardigital-sen3-1read-onlymandatoryThe sensor's current temperature in Celsius.
1.3.6.1.4.1.20916.1.12.1.2.3.2Scalardigital-sen3-2read-onlymandatoryThe sensor's current temperature in Fahrenheit.
1.3.6.1.4.1.20916.1.12.1.2.3.3Scalardigital-sen3-3read-onlymandatoryVaries by sensor type: current % relative humidity, voltage reading (V), power state (1=Power Detected, 0=No Power Detected), thermocouple temperature (C), or …
1.3.6.1.4.1.20916.1.12.1.2.3.4Scalardigital-sen3-4read-onlymandatoryVaries by sensor type: current heat index (F), custom analog reading, thermocouple temperature (F), or air speed (f/m).
1.3.6.1.4.1.20916.1.12.1.2.3.5Scalardigital-sen3-5read-onlymandatoryVaries by sensor type: current heat index (C), thermocouple fault code (0=No Fault), or air flow (CMH).
1.3.6.1.4.1.20916.1.12.1.2.3.6Scalardigital-sen3-6read-onlymandatoryVaries by sensor type: current dew point (C) or air flow (CFM).
1.3.6.1.4.1.20916.1.12.1.2.3.7Scalardigital-sen3-7read-onlymandatoryVaries by sensor type: current dew point (F).
1.3.6.1.4.1.20916.1.12.1.2.3.8Scalardigital-sen3-8read-onlymandatoryThe computed analog units for the Room Alert 32S analog input..
1.3.6.1.4.1.20916.1.12.1.3Nodeswitch
1.3.6.1.4.1.20916.1.12.1.3.1Scalarswitch-sen1read-onlymandatoryThe reading for switch sensor 1 (0 = OPEN, 1 = CLOSED).
1.3.6.1.4.1.20916.1.12.1.3.2Scalarswitch-sen2read-onlymandatoryThe reading for switch sensor 2 (0 = OPEN, 1 = CLOSED).
1.3.6.1.4.1.20916.1.12.1.3.3Scalarswitch-sen3read-onlymandatoryThe reading for switch sensor 3 (0 = OPEN, 1 = CLOSED).
1.3.6.1.4.1.20916.1.12.1.3.4Scalarswitch-sen4read-onlymandatoryThe reading for switch sensor 4 (0 = OPEN, 1 = CLOSED).
1.3.6.1.4.1.20916.1.12.1.4Nodelabels
1.3.6.1.4.1.20916.1.12.1.4.1Nodeint-labels
1.3.6.1.4.1.20916.1.12.1.4.1.1Scalarlabels-internal-sen1read-onlymandatoryInternal Sensor Label
1.3.6.1.4.1.20916.1.12.1.4.2Nodedigital-labels
1.3.6.1.4.1.20916.1.12.1.4.2.1Scalarlabels-digital-sen1read-onlymandatoryDigital Sensor Port 1 Label
1.3.6.1.4.1.20916.1.12.1.4.2.2Scalarlabels-digital-sen2read-onlymandatoryDigital Sensor Port 2 Label
1.3.6.1.4.1.20916.1.12.1.4.2.3Scalarlabels-digital-sen3read-onlymandatoryDigital Sensor Port 3 Label
1.3.6.1.4.1.20916.1.12.1.4.3Nodeswitch-labels
1.3.6.1.4.1.20916.1.12.1.4.3.1Scalarlabels-switch-sen1read-onlymandatorySwitch 1 Label
1.3.6.1.4.1.20916.1.12.1.4.3.2Scalarlabels-switch-sen2read-onlymandatorySwitch 2 Label
1.3.6.1.4.1.20916.1.12.1.4.3.3Scalarlabels-switch-sen3read-onlymandatorySwitch 3 Label
1.3.6.1.4.1.20916.1.12.1.4.3.4Scalarlabels-switch-sen4read-onlymandatorySwitch 4 Label
1.3.6.1.4.1.20916.1.12.1.4.4Nodeanalog-labels
1.3.6.1.4.1.20916.1.12.1.4.4.1Scalarlabels-analog-sen1read-onlymandatoryAnalog Sensor 1 Label
1.3.6.1.4.1.20916.1.12.1.4.5Nodeinternal-relay-labels
1.3.6.1.4.1.20916.1.12.1.4.5.1Scalarinternal-relay-labels1read-onlymandatoryInternal Relay 1 Label
1.3.6.1.4.1.20916.1.12.1.4.6Nodeexternal-relay-labels
1.3.6.1.4.1.20916.1.12.1.4.6.1Scalarexternal-relay-labels1read-onlymandatoryExternal Relay 1 Label
1.3.6.1.4.1.20916.1.12.2Nodetraps
1.3.6.1.4.1.20916.1.12.2.1NotificationalarmmessagecurrentIndicates that an alarm condition has occurred on the sensor indicated by the alarmMessage variable.
1.3.6.1.4.1.20916.1.12.3Nodeexternalrelays
1.3.6.1.4.1.20916.1.12.3.1Nodeexternalrelay1
1.3.6.1.4.1.20916.1.12.3.1.1Scalarexternalrelay1-element-oneread-writemandatoryThe status of the first element on external relay 1.
1.3.6.1.4.1.20916.1.12.3.1.2Scalarexternalrelay1-element-tworead-writemandatoryThe status of the second element on external relay 1.
1.3.6.1.4.1.20916.1.12.3.1.3Scalarexternalrelay1-element-threeread-writemandatoryThe status of the third element on external relay 1.
1.3.6.1.4.1.20916.1.12.3.1.4Scalarexternalrelay1-element-fourread-writemandatoryThe status of the fourth element on external relay 1.
1.3.6.1.4.1.20916.1.12.3.1.5Scalarexternalrelay1-element-fiveread-writemandatoryThe status of the fifth element on external relay 1.
1.3.6.1.4.1.20916.1.12.3.1.6Scalarexternalrelay1-element-sixread-writemandatoryThe status of the sixth element on external relay 1.
1.3.6.1.4.1.20916.1.12.3.1.7Scalarexternalrelay1-element-sevenread-writemandatoryThe status of the seventh element on external relay 1.
1.3.6.1.4.1.20916.1.12.3.1.8Scalarexternalrelay1-element-eightread-writemandatoryThe status of the eighth element on external relay 1