ROOMALERT24E-MIB
97 objects
No module-level DESCRIPTION found.
Imported Objects
| RFC-1212 | OBJECT-TYPE |
| RFC-1215 | TRAP-TYPE |
| RFC1155-SMI | Counter enterprises IpAddress TimeTicks |
| OID | Name | Access | Status | Description |
|---|---|---|---|---|
| 1.3.6.1.4.1.20916 | Nodeavtech | |||
| 1.3.6.1.4.1.20916.1 | Nodeproducts | |||
| 1.3.6.1.4.1.20916.1.5 | Noderoomalert24e | |||
| 1.3.6.1.4.1.20916.1.5.1 | Nodesensors | |||
| 1.3.6.1.4.1.20916.1.5.1 | Nodetempalarm1-24e | A tempalarm1 trap signifies that the current temperature on external sensor 1 is outside the defined high or low threshold. | ||
| 1.3.6.1.4.1.20916.1.5.1.1 | Nodeinternal | |||
| 1.3.6.1.4.1.20916.1.5.1.1.1 | Nodetemperature | |||
| 1.3.6.1.4.1.20916.1.5.1.1.1.1 | Scalarinternal-tempf | read-only | mandatory | The internal temperature reading in Fahrenheit. Because the SNMP Protocol does not support floating point numbers, values are scaled by 100 and should be divid… |
| 1.3.6.1.4.1.20916.1.5.1.1.1.2 | Scalarinternal-tempc | read-only | mandatory | The internal temperature reading in Celsius. Because the SNMP Protocol does not support floating point numbers, values are scaled by 100 and should be divided … |
| 1.3.6.1.4.1.20916.1.5.1.1.2 | Nodehumidity | |||
| 1.3.6.1.4.1.20916.1.5.1.1.2.1 | Scalarinternal-humidity | read-only | mandatory | The internal relative humidity reading in %RH. Because the SNMP Protocol does not support floating point numbers, values are scaled by 100 and should be divide… |
| 1.3.6.1.4.1.20916.1.5.1.1.3 | Nodeheat-index | |||
| 1.3.6.1.4.1.20916.1.5.1.1.3.1 | Scalarinternal-heat-index | read-only | mandatory | The internal heat index reading in Fahrenheit. Because the SNMP Protocol does not support floating point numbers, values are scaled by 100 and should be divide… |
| 1.3.6.1.4.1.20916.1.5.1.1.3.2 | Scalarinternal-heat-indexc | read-only | mandatory | The internal heat index reading in Celsius. Because the SNMP Protocol does not support floating point numbers, values are scaled by 100 and should be divided b… |
| 1.3.6.1.4.1.20916.1.5.1.2 | Nodedigital | |||
| 1.3.6.1.4.1.20916.1.5.1.2.1 | Nodedigital-sen1 | |||
| 1.3.6.1.4.1.20916.1.5.1.2.1.1 | Scalardigital-sen1-1 | read-only | mandatory | If this sensor is a Temperature or Temp/Humidity sensor, this value represents the current temperature in Celsius. If this sensor is a Digital Power Sensor, th… |
| 1.3.6.1.4.1.20916.1.5.1.2.1.2 | Scalardigital-sen1-2 | read-only | mandatory | If this sensor is a Temperature or Temp/Humidity sensor, this value represents the current temperature in Fahrenheit. If this sensor is a Digital Power Sensor,… |
| 1.3.6.1.4.1.20916.1.5.1.2.1.3 | Scalardigital-sen1-3 | read-only | mandatory | If this sensor is a Temp/Humidity sensor, this value represents the current relative humidity in % Relative Humidity. If this sensor is a Digital Power Sensor,… |
| 1.3.6.1.4.1.20916.1.5.1.2.1.4 | Scalardigital-sen1-4 | read-only | mandatory | If this sensor is a Temp/Humidity sensor, this value represents the current heat index in Fahrenheit. If this sensor is a Digital Power Sensor, this value repr… |
| 1.3.6.1.4.1.20916.1.5.1.2.1.5 | Scalardigital-sen1-5 | read-only | mandatory | If this sensor is a Temp/Humidity sensor, this value represents the current heat index in Celsius. |
| 1.3.6.1.4.1.20916.1.5.1.2.2 | Nodedigital-sen2 | |||
| 1.3.6.1.4.1.20916.1.5.1.2.2.1 | Scalardigital-sen2-1 | read-only | mandatory | If this sensor is a Temperature or Temp/Humidity sensor, this value represents the current temperature in Celsius. If this sensor is a Digital Power Sensor, th… |
| 1.3.6.1.4.1.20916.1.5.1.2.2.2 | Scalardigital-sen2-2 | read-only | mandatory | If this sensor is a Temperature or Temp/Humidity sensor, this value represents the current temperature in Fahrenheit. If this sensor is a Digital Power Sensor,… |
| 1.3.6.1.4.1.20916.1.5.1.2.2.3 | Scalardigital-sen2-3 | read-only | mandatory | If this sensor is a Temp/Humidity sensor, this value represents the current relative humidity in % Relative Humidity. If this sensor is a Digital Power Sensor,… |
| 1.3.6.1.4.1.20916.1.5.1.2.2.4 | Scalardigital-sen2-4 | read-only | mandatory | If this sensor is a Temp/Humidity sensor, this value represents the current heat index in Fahrenheit. If this sensor is a Digital Power Sensor, this value repr… |
| 1.3.6.1.4.1.20916.1.5.1.2.2.5 | Scalardigital-sen2-5 | read-only | mandatory | If this sensor is a Temp/Humidity sensor, this value represents the current heat index in Celsius. |
| 1.3.6.1.4.1.20916.1.5.1.2.3 | Nodedigital-sen3 | |||
| 1.3.6.1.4.1.20916.1.5.1.2.3.1 | Scalardigital-sen3-1 | read-only | mandatory | If this sensor is a Temperature or Temp/Humidity sensor, this value represents the current temperature in Celsius. If this sensor is a Digital Power Sensor, th… |
| 1.3.6.1.4.1.20916.1.5.1.2.3.2 | Scalardigital-sen3-2 | read-only | mandatory | If this sensor is a Temperature or Temp/Humidity sensor, this value represents the current temperature in Fahrenheit. If this sensor is a Digital Power Sensor,… |
| 1.3.6.1.4.1.20916.1.5.1.2.3.3 | Scalardigital-sen3-3 | read-only | mandatory | If this sensor is a Temp/Humidity sensor, this value represents the current relative humidity in % Relative Humidity. If this sensor is a Digital Power Sensor,… |
| 1.3.6.1.4.1.20916.1.5.1.2.3.4 | Scalardigital-sen3-4 | read-only | mandatory | If this sensor is a Temp/Humidity sensor, this value represents the current heat index in Fahrenheit. If this sensor is a Digital Power Sensor, this value repr… |
| 1.3.6.1.4.1.20916.1.5.1.2.3.5 | Scalardigital-sen3-5 | read-only | mandatory | If this sensor is a Temp/Humidity sensor, this value represents the current heat index in Celsius. |
| 1.3.6.1.4.1.20916.1.5.1.2.4 | Nodedigital-sen4 | |||
| 1.3.6.1.4.1.20916.1.5.1.2.4.1 | Scalardigital-sen4-1 | read-only | mandatory | If this sensor is a Temperature or Temp/Humidity sensor, this value represents the current temperature in Celsius. If this sensor is a Digital Power Sensor, th… |
| 1.3.6.1.4.1.20916.1.5.1.2.4.2 | Scalardigital-sen4-2 | read-only | mandatory | If this sensor is a Temperature or Temp/Humidity sensor, this value represents the current temperature in Fahrenheit. If this sensor is a Digital Power Sensor,… |
| 1.3.6.1.4.1.20916.1.5.1.2.4.3 | Scalardigital-sen4-3 | read-only | mandatory | If this sensor is a Temp/Humidity sensor, this value represents the current relative humidity in % Relative Humidity. If this sensor is a Digital Power Sensor,… |
| 1.3.6.1.4.1.20916.1.5.1.2.4.4 | Scalardigital-sen4-4 | read-only | mandatory | If this sensor is a Temp/Humidity sensor, this value represents the current heat index in Fahrenheit. If this sensor is a Digital Power Sensor, this value repr… |
| 1.3.6.1.4.1.20916.1.5.1.2.4.5 | Scalardigital-sen4-5 | read-only | mandatory | If this sensor is a Temp/Humidity sensor, this value represents the current heat index in Celsius. |
| 1.3.6.1.4.1.20916.1.5.1.2.5 | Nodedigital-sen5 | |||
| 1.3.6.1.4.1.20916.1.5.1.2.5.1 | Scalardigital-sen5-1 | read-only | mandatory | If this sensor is a Temperature or Temp/Humidity sensor, this value represents the current temperature in Celsius. If this sensor is a Digital Power Sensor, th… |
| 1.3.6.1.4.1.20916.1.5.1.2.5.2 | Scalardigital-sen5-2 | read-only | mandatory | If this sensor is a Temperature or Temp/Humidity sensor, this value represents the current temperature in Fahrenheit. If this sensor is a Digital Power Sensor,… |
| 1.3.6.1.4.1.20916.1.5.1.2.5.3 | Scalardigital-sen5-3 | read-only | mandatory | If this sensor is a Temp/Humidity sensor, this value represents the current relative humidity in % Relative Humidity. If this sensor is a Digital Power Sensor,… |
| 1.3.6.1.4.1.20916.1.5.1.2.5.4 | Scalardigital-sen5-4 | read-only | mandatory | If this sensor is a Temp/Humidity sensor, this value represents the current heat index in Fahrenheit. If this sensor is a Digital Power Sensor, this value repr… |
| 1.3.6.1.4.1.20916.1.5.1.2.5.5 | Scalardigital-sen5-5 | read-only | mandatory | If this sensor is a Temp/Humidity sensor, this value represents the current heat index in Celsius. |
| 1.3.6.1.4.1.20916.1.5.1.2.6 | Nodedigital-sen6 | |||
| 1.3.6.1.4.1.20916.1.5.1.2.6.1 | Scalardigital-sen6-1 | read-only | mandatory | If this sensor is a Temperature or Temp/Humidity sensor, this value represents the current temperature in Celsius. If this sensor is a Digital Power Sensor, th… |
| 1.3.6.1.4.1.20916.1.5.1.2.6.2 | Scalardigital-sen6-2 | read-only | mandatory | If this sensor is a Temperature or Temp/Humidity sensor, this value represents the current temperature in Fahrenheit. If this sensor is a Digital Power Sensor,… |
| 1.3.6.1.4.1.20916.1.5.1.2.6.3 | Scalardigital-sen6-3 | read-only | mandatory | If this sensor is a Temp/Humidity sensor, this value represents the current relative humidity in % Relative Humidity. If this sensor is a Digital Power Sensor,… |
| 1.3.6.1.4.1.20916.1.5.1.2.6.4 | Scalardigital-sen6-4 | read-only | mandatory | If this sensor is a Temp/Humidity sensor, this value represents the current heat index in Fahrenheit. If this sensor is a Digital Power Sensor, this value repr… |
| 1.3.6.1.4.1.20916.1.5.1.2.6.5 | Scalardigital-sen6-5 | read-only | mandatory | If this sensor is a Temp/Humidity sensor, this value represents the current heat index in Celsius. |
| 1.3.6.1.4.1.20916.1.5.1.3 | Nodeswitch | |||
| 1.3.6.1.4.1.20916.1.5.1.3.1 | Scalarswitch-sen1 | read-only | mandatory | The reading for switch sensor 1 (0 = OPEN, 1 = CLOSED). |
| 1.3.6.1.4.1.20916.1.5.1.3.2 | Scalarswitch-sen2 | read-only | mandatory | The reading for switch sensor 2 (0 = OPEN, 1 = CLOSED). |
| 1.3.6.1.4.1.20916.1.5.1.3.3 | Scalarswitch-sen3 | read-only | mandatory | The reading for switch sensor 3 (0 = OPEN, 1 = CLOSED). |
| 1.3.6.1.4.1.20916.1.5.1.3.4 | Scalarswitch-sen4 | read-only | mandatory | The reading for switch sensor 4 (0 = OPEN, 1 = CLOSED). |
| 1.3.6.1.4.1.20916.1.5.1.3.5 | Scalarswitch-sen5 | read-only | mandatory | The reading for switch sensor 5 (0 = OPEN, 1 = CLOSED). |
| 1.3.6.1.4.1.20916.1.5.1.3.6 | Scalarswitch-sen6 | read-only | mandatory | The reading for switch sensor 6 (0 = OPEN, 1 = CLOSED). |
| 1.3.6.1.4.1.20916.1.5.1.3.7 | Scalarswitch-sen7 | read-only | mandatory | The reading for switch sensor 7 (0 = OPEN, 1 = CLOSED). |
| 1.3.6.1.4.1.20916.1.5.1.3.8 | Scalarswitch-sen8 | read-only | mandatory | The reading for switch sensor 8 (0 = OPEN, 1 = CLOSED). |
| 1.3.6.1.4.1.20916.1.5.1.3.9 | Scalarswitch-sen9 | read-only | mandatory | The reading for switch sensor 9 (0 = OPEN, 1 = CLOSED). |
| 1.3.6.1.4.1.20916.1.5.1.3.10 | Scalarswitch-sen10 | read-only | mandatory | The reading for switch sensor 10 (0 = OPEN, 1 = CLOSED). |
| 1.3.6.1.4.1.20916.1.5.1.3.11 | Scalarswitch-sen11 | read-only | mandatory | The reading for switch sensor 11 (0 = OPEN, 1 = CLOSED). |
| 1.3.6.1.4.1.20916.1.5.1.3.12 | Scalarswitch-sen12 | read-only | mandatory | The reading for switch sensor 12 (0 = OPEN, 1 = CLOSED). |
| 1.3.6.1.4.1.20916.1.5.1.3.13 | Scalarswitch-sen13 | read-only | mandatory | The reading for switch sensor 13 (0 = OPEN, 1 = CLOSED). |
| 1.3.6.1.4.1.20916.1.5.1.3.14 | Scalarswitch-sen14 | read-only | mandatory | The reading for switch sensor 14 (0 = OPEN, 1 = CLOSED). |
| 1.3.6.1.4.1.20916.1.5.1.3.15 | Scalarswitch-sen15 | read-only | mandatory | The reading for switch sensor 15 (0 = OPEN, 1 = CLOSED). |
| 1.3.6.1.4.1.20916.1.5.1.3.16 | Scalarswitch-sen16 | read-only | mandatory | The reading for switch sensor 16 (0 = OPEN, 1 = CLOSED). |
| 1.3.6.1.4.1.20916.1.5.2 | Noderoom-alert-24e-snmp-trap | A room-alert-24e-snmp-trap indicates that an alarm condition has occurred on the sensor indicated by the alarmmessage variable. | ||
| 1.3.6.1.4.1.20916.1.5.2 | Nodetraps | |||
| 1.3.6.1.4.1.20916.1.5.2.1 | Scalaralarmmessage | read-only | mandatory | Last Alarm Message |
| 1.3.6.1.4.1.20916.1.5.3 | Nodetempalarm2-24e | A tempalarm2 trap signifies that the current temperature on external sensor 2 is outside the defined high or low threshold. | ||
| 1.3.6.1.4.1.20916.1.5.4 | Nodetempclear2-24e | A tempclear2 trap signifies that the current temperature on external sensor 2 has returned to a normal condition and is within the defined high or low threshol… | ||
| 1.3.6.1.4.1.20916.1.5.5 | Nodetempalarm3-24e | A tempalarm3 trap signifies that the current temperature on external sensor 3 is outside the defined high or low threshold. | ||
| 1.3.6.1.4.1.20916.1.5.6 | Nodetempclear3-24e | A tempclear3 trap signifies that the current temperature on external sensor 3 has returned to a normal condition and is within the defined high or low threshol… | ||
| 1.3.6.1.4.1.20916.1.5.7 | Nodehumidityalarm1-24e | A humidityalarm1 trap signifies that the current humidity on external sensor 1 is outside the defined high or low threshold. | ||
| 1.3.6.1.4.1.20916.1.5.8 | Nodehumidityclear1-24e | A humidityclear1 trap signifies that the current humidity on external sensor 1 has returned to a normal condition and is within the defined high or low thresho… | ||
| 1.3.6.1.4.1.20916.1.5.9 | Nodehumidityalarm2-24e | A humidityalarm2 trap signifies that the current humidity on external sensor 2 is outside the defined high or low threshold. | ||
| 1.3.6.1.4.1.20916.1.5.10 | Nodehumidityclear2-24e | A humidityclear2 trap signifies that the current humidity on external sensor 2 has returned to a normal condition and is within the defined high or low thresho… | ||
| 1.3.6.1.4.1.20916.1.5.11 | Nodehumidityalarm3-24e | A humidityalarm3 trap signifies that the current humidity on external sensor 3 is outside the defined high or low threshold. | ||
| 1.3.6.1.4.1.20916.1.5.12 | Nodehumidityclear3-24e | A humidityclear3 trap signifies that the current humidity on external sensor 3 has returned to a normal condition and is within the defined high or low thresho… | ||
| 1.3.6.1.4.1.20916.1.5.13 | Nodeswitchalarm1-24e | A switchalarm1 trap signifies that switch sensor 1 is in an alarm state. | ||
| 1.3.6.1.4.1.20916.1.5.14 | Nodeswitchclear1-24e | A switchclear1 trap signifies that the switch sensor 1 has returned to a normal state. | ||
| 1.3.6.1.4.1.20916.1.5.15 | Nodeswitchalarm2-24e | A switchalarm2 trap signifies that switch sensor 2 is in an alarm state. | ||
| 1.3.6.1.4.1.20916.1.5.16 | Nodeswitchclear2-24e | A switchclear2 trap signifies that the switch sensor 2 has returned to a normal state. | ||
| 1.3.6.1.4.1.20916.1.5.17 | Nodeswitchalarm3-24e | A switchalarm1 trap signifies that switch sensor 1 is in an alarm state. | ||
| 1.3.6.1.4.1.20916.1.5.18 | Nodeswitchclear3-24e | A switchclear3 trap signifies that the switch sensor 3 has returned to a normal state. | ||
| 1.3.6.1.4.1.20916.1.5.19 | Nodeswitchalarm4-24e | A switchalarm4 trap signifies that switch sensor 4 is in an alarm state. | ||
| 1.3.6.1.4.1.20916.1.5.20 | Nodeswitchclear4-24e | A switchclear4 trap signifies that the switch sensor 4 has returned to a normal state. | ||
| 1.3.6.1.4.1.20916.1.5.21 | Nodeswitchalarm5-24e | A switchalarm5 trap signifies that switch sensor 5 is in an alarm state. | ||
| 1.3.6.1.4.1.20916.1.5.22 | Nodeswitchclear5-24e | A switchclear5 trap signifies that the switch sensor 5 has returned to a normal state. | ||
| 1.3.6.1.4.1.20916.1.5.23 | Nodeswitchalarm6-24e | A switchalarm6 trap signifies that switch sensor 6 is in an alarm state. | ||
| 1.3.6.1.4.1.20916.1.5.24 | Nodeswitchclear6-24e | A switchclear6 trap signifies that the switch sensor 6 has returned to a normal state. | ||
| 1.3.6.1.4.1.20916.1.5.25 | Nodeswitchalarm7-24e | A switchalarm7 trap signifies that switch sensor 7 is in an alarm state. | ||
| 1.3.6.1.4.1.20916.1.5.26 | Nodeswitchclear7-24e | A switchclear7 trap signifies that the switch sensor 7 has returned to a normal state. | ||
| 1.3.6.1.4.1.20916.1.5.27 | Nodeswitchalarm8-24e | A switchalarm8 trap signifies that switch sensor 8 is in an alarm state. | ||
| 1.3.6.1.4.1.20916.1.5.28 | Nodeswitchclear8-24e | A switchclear8 trap signifies that the switch sensor 8 has returned to a normal state. |