ROOMALERT32S-MIB

178 objects
No module-level DESCRIPTION found.
Imported Objects
RFC1155-SMIenterprises Gauge IpAddress TimeTicks
RFC1213-MIBDisplayString system
SNMPv2-SMINOTIFICATION-TYPE
OIDNameAccessStatusDescription
1.3.6.1.4.1.20916Nodeavtech
1.3.6.1.4.1.20916.1Nodeproducts
1.3.6.1.4.1.20916.1.11Noderoomalert32S
1.3.6.1.4.1.20916.1.11.1Nodesensors
1.3.6.1.4.1.20916.1.11.1.1Nodeinternal
1.3.6.1.4.1.20916.1.11.1.1.1Nodetemperature
1.3.6.1.4.1.20916.1.11.1.1.1.1Scalarinternal-tempfread-onlymandatoryThe internal temperature reading in Fahrenheit.
1.3.6.1.4.1.20916.1.11.1.1.1.2Scalarinternal-tempcread-onlymandatoryThe internal temperature reading in Celsius.
1.3.6.1.4.1.20916.1.11.1.1.2Nodehumidity
1.3.6.1.4.1.20916.1.11.1.1.2.1Scalarinternal-humidityread-onlymandatoryThe internal relative humidity reading in %RH.
1.3.6.1.4.1.20916.1.11.1.1.3Nodepower
1.3.6.1.4.1.20916.1.11.1.1.3.1Scalarinternal-powerread-onlymandatoryThe current status of the Room Alert 32S power supply. A '1' indicates the unit is running on AC/Utility power. A '0' indicates the unit is running on battery …
1.3.6.1.4.1.20916.1.11.1.1.4Nodeheat-index
1.3.6.1.4.1.20916.1.11.1.1.4.1Scalarinternal-heat-indexread-onlyoptionalThe internal heat index reading in Fahrenheit.
1.3.6.1.4.1.20916.1.11.1.1.4.2Scalarinternal-heat-indexCread-onlyoptionalThe internal heat index reading in Celsius.
1.3.6.1.4.1.20916.1.11.1.1.5Nodeanalog
1.3.6.1.4.1.20916.1.11.1.1.5.1Scalarinternal-analog1read-onlymandatoryThe current status of the Room Alert 32S analog input (0-5VDC).
1.3.6.1.4.1.20916.1.11.1.1.5.2Scalarinternal-analog2read-onlymandatoryThe current status of the Room Alert 32S analog input (0-5VDC).
1.3.6.1.4.1.20916.1.11.1.1.5.3Scalarinternal-analog-computed1read-onlymandatoryThe current computed value of the Room Alert 32S analog input.
1.3.6.1.4.1.20916.1.11.1.1.5.4Scalarinternal-analog-computed-units1read-onlymandatoryThe computed analog units for the Room Alert 32S analog input..
1.3.6.1.4.1.20916.1.11.1.1.5.5Scalarinternal-analog-computed2read-onlymandatoryThe current computed value of the Room Alert 32S analog input.
1.3.6.1.4.1.20916.1.11.1.1.5.6Scalarinternal-analog-computed-units2read-onlymandatoryThe computed analog units for the Room Alert 32S analog input..
1.3.6.1.4.1.20916.1.11.1.1.6Noderelay
1.3.6.1.4.1.20916.1.11.1.1.6.1Scalarinternal-relay1read-writemandatoryThe status of the on-board relay output
1.3.6.1.4.1.20916.1.11.1.1.6.2Scalarinternal-relay2read-writemandatoryThe status of the on-board relay output
1.3.6.1.4.1.20916.1.11.1.1.7Nodedew-point
1.3.6.1.4.1.20916.1.11.1.1.7.1Scalarinternal-dew-point-cread-onlyoptionalThe internal dew-point reading in Celsius.
1.3.6.1.4.1.20916.1.11.1.1.7.2Scalarinternal-dew-point-fread-onlyoptionalThe internal dew-point reading in Fahrenheit.
1.3.6.1.4.1.20916.1.11.1.2Nodedigital
1.3.6.1.4.1.20916.1.11.1.2.1Nodedigital-sen1
1.3.6.1.4.1.20916.1.11.1.2.1.1Scalardigital-sen1-1read-onlymandatoryThe sensor's current temperature in Celsius.
1.3.6.1.4.1.20916.1.11.1.2.1.2Scalardigital-sen1-2read-onlymandatoryThe sensor's current temperature in Fahrenheit.
1.3.6.1.4.1.20916.1.11.1.2.1.3Scalardigital-sen1-3read-onlymandatoryVaries by sensor type: current % relative humidity, voltage reading (V), power state (1=Power Detected, 0=No Power Detected), thermocouple temperature (C), air…
1.3.6.1.4.1.20916.1.11.1.2.1.4Scalardigital-sen1-4read-onlymandatoryVaries by sensor type: current heat index (F), custom analog reading, thermocouple temperature (F), air speed (f/m), or PM10 (mcg/m3).
1.3.6.1.4.1.20916.1.11.1.2.1.5Scalardigital-sen1-5read-onlymandatoryVaries by sensor type: current heat index (C), thermocouple fault code (0=No Fault), air flow (CMH), or particulate fault code (0=No Fault).
1.3.6.1.4.1.20916.1.11.1.2.1.6Scalardigital-sen1-6read-onlymandatoryVaries by sensor type: current dew point (C) or air flow (CFM).
1.3.6.1.4.1.20916.1.11.1.2.1.7Scalardigital-sen1-7read-onlymandatoryVaries by sensor type: current dew point (F).
1.3.6.1.4.1.20916.1.11.1.2.1.8Scalardigital-sen1-8read-onlymandatoryThe computed analog units for the Room Alert 32S analog input..
1.3.6.1.4.1.20916.1.11.1.2.2Nodedigital-sen2
1.3.6.1.4.1.20916.1.11.1.2.2.1Scalardigital-sen2-1read-onlymandatoryThe sensor's current temperature in Celsius.
1.3.6.1.4.1.20916.1.11.1.2.2.2Scalardigital-sen2-2read-onlymandatoryThe sensor's current temperature in Fahrenheit.
1.3.6.1.4.1.20916.1.11.1.2.2.3Scalardigital-sen2-3read-onlymandatoryVaries by sensor type: current % relative humidity, voltage reading (V), power state (1=Power Detected, 0=No Power Detected), thermocouple temperature (C), air…
1.3.6.1.4.1.20916.1.11.1.2.2.4Scalardigital-sen2-4read-onlymandatoryVaries by sensor type: current heat index (F), custom analog reading, thermocouple temperature (F), air speed (f/m), or PM10 (mcg/m3).
1.3.6.1.4.1.20916.1.11.1.2.2.5Scalardigital-sen2-5read-onlymandatoryVaries by sensor type: current heat index (C), thermocouple fault code (0=No Fault), air flow (CMH), or particulate fault code (0=No Fault).
1.3.6.1.4.1.20916.1.11.1.2.2.6Scalardigital-sen2-6read-onlymandatoryVaries by sensor type: current dew point (C) or air flow (CFM).
1.3.6.1.4.1.20916.1.11.1.2.2.7Scalardigital-sen2-7read-onlymandatoryVaries by sensor type: current dew point (F).
1.3.6.1.4.1.20916.1.11.1.2.2.8Scalardigital-sen2-8read-onlymandatoryThe computed analog units for the Room Alert 32S analog input..
1.3.6.1.4.1.20916.1.11.1.2.3Nodedigital-sen3
1.3.6.1.4.1.20916.1.11.1.2.3.1Scalardigital-sen3-1read-onlymandatoryThe sensor's current temperature in Celsius.
1.3.6.1.4.1.20916.1.11.1.2.3.2Scalardigital-sen3-2read-onlymandatoryThe sensor's current temperature in Fahrenheit.
1.3.6.1.4.1.20916.1.11.1.2.3.3Scalardigital-sen3-3read-onlymandatoryVaries by sensor type: current % relative humidity, voltage reading (V), power state (1=Power Detected, 0=No Power Detected), thermocouple temperature (C), air…
1.3.6.1.4.1.20916.1.11.1.2.3.4Scalardigital-sen3-4read-onlymandatoryVaries by sensor type: current heat index (F), custom analog reading, thermocouple temperature (F), air speed (f/m), or PM10 (mcg/m3).
1.3.6.1.4.1.20916.1.11.1.2.3.5Scalardigital-sen3-5read-onlymandatoryVaries by sensor type: current heat index (C), thermocouple fault code (0=No Fault), air flow (CMH), or particulate fault code (0=No Fault).
1.3.6.1.4.1.20916.1.11.1.2.3.6Scalardigital-sen3-6read-onlymandatoryVaries by sensor type: current dew point (C) or air flow (CFM).
1.3.6.1.4.1.20916.1.11.1.2.3.7Scalardigital-sen3-7read-onlymandatoryVaries by sensor type: current dew point (F).
1.3.6.1.4.1.20916.1.11.1.2.3.8Scalardigital-sen3-8read-onlymandatoryThe computed analog units for the Room Alert 32S analog input..
1.3.6.1.4.1.20916.1.11.1.2.4Nodedigital-sen4
1.3.6.1.4.1.20916.1.11.1.2.4.1Scalardigital-sen4-1read-onlymandatoryThe sensor's current temperature in Celsius.
1.3.6.1.4.1.20916.1.11.1.2.4.2Scalardigital-sen4-2read-onlymandatoryThe sensor's current temperature in Fahrenheit.
1.3.6.1.4.1.20916.1.11.1.2.4.3Scalardigital-sen4-3read-onlymandatoryVaries by sensor type: current % relative humidity, voltage reading (V), power state (1=Power Detected, 0=No Power Detected), thermocouple temperature (C), air…
1.3.6.1.4.1.20916.1.11.1.2.4.4Scalardigital-sen4-4read-onlymandatoryVaries by sensor type: current heat index (F), custom analog reading, thermocouple temperature (F), air speed (f/m), or PM10 (mcg/m3).
1.3.6.1.4.1.20916.1.11.1.2.4.5Scalardigital-sen4-5read-onlymandatoryVaries by sensor type: current heat index (C), thermocouple fault code (0=No Fault), air flow (CMH), or particulate fault code (0=No Fault).
1.3.6.1.4.1.20916.1.11.1.2.4.6Scalardigital-sen4-6read-onlymandatoryVaries by sensor type: current dew point (C) or air flow (CFM).
1.3.6.1.4.1.20916.1.11.1.2.4.7Scalardigital-sen4-7read-onlymandatoryVaries by sensor type: current dew point (F).
1.3.6.1.4.1.20916.1.11.1.2.4.8Scalardigital-sen4-8read-onlymandatoryThe computed analog units for the Room Alert 32S analog input..
1.3.6.1.4.1.20916.1.11.1.2.5Nodedigital-sen5
1.3.6.1.4.1.20916.1.11.1.2.5.1Scalardigital-sen5-1read-onlymandatoryThe sensor's current temperature in Celsius.
1.3.6.1.4.1.20916.1.11.1.2.5.2Scalardigital-sen5-2read-onlymandatoryThe sensor's current temperature in Fahrenheit.
1.3.6.1.4.1.20916.1.11.1.2.5.3Scalardigital-sen5-3read-onlymandatoryVaries by sensor type: current % relative humidity, voltage reading (V), power state (1=Power Detected, 0=No Power Detected), thermocouple temperature (C), air…
1.3.6.1.4.1.20916.1.11.1.2.5.4Scalardigital-sen5-4read-onlymandatoryVaries by sensor type: current heat index (F), custom analog reading, thermocouple temperature (F), air speed (f/m), or PM10 (mcg/m3).
1.3.6.1.4.1.20916.1.11.1.2.5.5Scalardigital-sen5-5read-onlymandatoryVaries by sensor type: current heat index (C), thermocouple fault code (0=No Fault), air flow (CMH), or particulate fault code (0=No Fault).
1.3.6.1.4.1.20916.1.11.1.2.5.6Scalardigital-sen5-6read-onlymandatoryVaries by sensor type: current dew point (C) or air flow (CFM).
1.3.6.1.4.1.20916.1.11.1.2.5.7Scalardigital-sen5-7read-onlymandatoryVaries by sensor type: current dew point (F).
1.3.6.1.4.1.20916.1.11.1.2.5.8Scalardigital-sen5-8read-onlymandatoryThe computed analog units for the Room Alert 32S analog input..
1.3.6.1.4.1.20916.1.11.1.2.6Nodedigital-sen6
1.3.6.1.4.1.20916.1.11.1.2.6.1Scalardigital-sen6-1read-onlymandatoryThe sensor's current temperature in Celsius.
1.3.6.1.4.1.20916.1.11.1.2.6.2Scalardigital-sen6-2read-onlymandatoryThe sensor's current temperature in Fahrenheit.
1.3.6.1.4.1.20916.1.11.1.2.6.3Scalardigital-sen6-3read-onlymandatoryVaries by sensor type: current % relative humidity, voltage reading (V), power state (1=Power Detected, 0=No Power Detected), thermocouple temperature (C), air…
1.3.6.1.4.1.20916.1.11.1.2.6.4Scalardigital-sen6-4read-onlymandatoryVaries by sensor type: current heat index (F), custom analog reading, thermocouple temperature (F), air speed (f/m), or PM10 (mcg/m3).
1.3.6.1.4.1.20916.1.11.1.2.6.5Scalardigital-sen6-5read-onlymandatoryVaries by sensor type: current heat index (C), thermocouple fault code (0=No Fault), air flow (CMH), or particulate fault code (0=No Fault).
1.3.6.1.4.1.20916.1.11.1.2.6.6Scalardigital-sen6-6read-onlymandatoryVaries by sensor type: current dew point (C) or air flow (CFM).
1.3.6.1.4.1.20916.1.11.1.2.6.7Scalardigital-sen6-7read-onlymandatoryVaries by sensor type: current dew point (F).
1.3.6.1.4.1.20916.1.11.1.2.6.8Scalardigital-sen6-8read-onlymandatoryThe computed analog units for the Room Alert 32S analog input..
1.3.6.1.4.1.20916.1.11.1.2.7Nodedigital-sen7
1.3.6.1.4.1.20916.1.11.1.2.7.1Scalardigital-sen7-1read-onlymandatoryThe sensor's current temperature in Celsius.
1.3.6.1.4.1.20916.1.11.1.2.7.2Scalardigital-sen7-2read-onlymandatoryThe sensor's current temperature in Fahrenheit.
1.3.6.1.4.1.20916.1.11.1.2.7.3Scalardigital-sen7-3read-onlymandatoryVaries by sensor type: current % relative humidity, voltage reading (V), power state (1=Power Detected, 0=No Power Detected), thermocouple temperature (C), air…
1.3.6.1.4.1.20916.1.11.1.2.7.4Scalardigital-sen7-4read-onlymandatoryVaries by sensor type: current heat index (F), custom analog reading, thermocouple temperature (F), air speed (f/m), or PM10 (mcg/m3).
1.3.6.1.4.1.20916.1.11.1.2.7.5Scalardigital-sen7-5read-onlymandatoryVaries by sensor type: current heat index (C), thermocouple fault code (0=No Fault), air flow (CMH), or particulate fault code (0=No Fault).
1.3.6.1.4.1.20916.1.11.1.2.7.6Scalardigital-sen7-6read-onlymandatoryVaries by sensor type: current dew point (C) or air flow (CFM).
1.3.6.1.4.1.20916.1.11.1.2.7.7Scalardigital-sen7-7read-onlymandatoryVaries by sensor type: current dew point (F).
1.3.6.1.4.1.20916.1.11.1.2.7.8Scalardigital-sen7-8read-onlymandatoryThe computed analog units for the Room Alert 32S analog input..
1.3.6.1.4.1.20916.1.11.1.2.8Nodedigital-sen8
1.3.6.1.4.1.20916.1.11.1.2.8.1Scalardigital-sen8-1read-onlymandatoryThe sensor's current temperature in Celsius.
1.3.6.1.4.1.20916.1.11.1.2.8.2Scalardigital-sen8-2read-onlymandatoryThe sensor's current temperature in Fahrenheit.
1.3.6.1.4.1.20916.1.11.1.2.8.3Scalardigital-sen8-3read-onlymandatoryVaries by sensor type: current % relative humidity, voltage reading (V), power state (1=Power Detected, 0=No Power Detected), thermocouple temperature (C), air…
1.3.6.1.4.1.20916.1.11.1.2.8.4Scalardigital-sen8-4read-onlymandatoryVaries by sensor type: current heat index (F), custom analog reading, thermocouple temperature (F), air speed (f/m), or PM10 (mcg/m3).
1.3.6.1.4.1.20916.1.11.1.2.8.5Scalardigital-sen8-5read-onlymandatoryVaries by sensor type: current heat index (C), thermocouple fault code (0=No Fault), air flow (CMH), or particulate fault code (0=No Fault).
1.3.6.1.4.1.20916.1.11.1.2.8.6Scalardigital-sen8-6read-onlymandatoryVaries by sensor type: current dew point (C) or air flow (CFM).
1.3.6.1.4.1.20916.1.11.1.2.8.7Scalardigital-sen8-7read-onlymandatoryVaries by sensor type: current dew point (F).
1.3.6.1.4.1.20916.1.11.1.2.8.8Scalardigital-sen8-8read-onlymandatoryThe computed analog units for the Room Alert 32S analog input..
1.3.6.1.4.1.20916.1.11.1.3Nodeswitch
1.3.6.1.4.1.20916.1.11.1.3.1Scalarswitch-sen1read-onlymandatoryThe reading for switch sensor 1 (0 = OPEN, 1 = CLOSED).
1.3.6.1.4.1.20916.1.11.1.3.2Scalarswitch-sen2read-onlymandatoryThe reading for switch sensor 2 (0 = OPEN, 1 = CLOSED).
1.3.6.1.4.1.20916.1.11.1.3.3Scalarswitch-sen3read-onlymandatoryThe reading for switch sensor 3 (0 = OPEN, 1 = CLOSED).
1.3.6.1.4.1.20916.1.11.1.3.4Scalarswitch-sen4read-onlymandatoryThe reading for switch sensor 4 (0 = OPEN, 1 = CLOSED).
1.3.6.1.4.1.20916.1.11.1.3.5Scalarswitch-sen5read-onlymandatoryThe reading for switch sensor 5 (0 = OPEN, 1 = CLOSED).
1.3.6.1.4.1.20916.1.11.1.3.6Scalarswitch-sen6read-onlymandatoryThe reading for switch sensor 6 (0 = OPEN, 1 = CLOSED).
1.3.6.1.4.1.20916.1.11.1.3.7Scalarswitch-sen7read-onlymandatoryThe reading for switch sensor 7 (0 = OPEN, 1 = CLOSED).
1.3.6.1.4.1.20916.1.11.1.3.8Scalarswitch-sen8read-onlymandatoryThe reading for switch sensor 8 (0 = OPEN, 1 = CLOSED).
1.3.6.1.4.1.20916.1.11.1.3.9Scalarswitch-sen9read-onlymandatoryThe reading for switch sensor 9 (0 = OPEN, 1 = CLOSED).
1.3.6.1.4.1.20916.1.11.1.3.10Scalarswitch-sen10read-onlymandatoryThe reading for switch sensor 10 (0 = OPEN, 1 = CLOSED).
1.3.6.1.4.1.20916.1.11.1.3.11Scalarswitch-sen11read-onlymandatoryThe reading for switch sensor 11 (0 = OPEN, 1 = CLOSED).
1.3.6.1.4.1.20916.1.11.1.3.12Scalarswitch-sen12read-onlymandatoryThe reading for switch sensor 12 (0 = OPEN, 1 = CLOSED).
1.3.6.1.4.1.20916.1.11.1.3.13Scalarswitch-sen13read-onlymandatoryThe reading for switch sensor 13 (0 = OPEN, 1 = CLOSED).
1.3.6.1.4.1.20916.1.11.1.3.14Scalarswitch-sen14read-onlymandatoryThe reading for switch sensor 14 (0 = OPEN, 1 = CLOSED).
1.3.6.1.4.1.20916.1.11.1.3.15Scalarswitch-sen15read-onlymandatoryThe reading for switch sensor 15 (0 = OPEN, 1 = CLOSED).
1.3.6.1.4.1.20916.1.11.1.3.16Scalarswitch-sen16read-onlymandatoryThe reading for switch sensor 16 (0 = OPEN, 1 = CLOSED).
1.3.6.1.4.1.20916.1.11.1.4Nodelabels
1.3.6.1.4.1.20916.1.11.1.4.1Nodeint-labels
1.3.6.1.4.1.20916.1.11.1.4.1.1Scalarlabels-internal-sen1read-onlymandatoryInternal Sensor Label
1.3.6.1.4.1.20916.1.11.1.4.1.2Scalarlabels-internal-sen2read-onlymandatoryInternal Power Sensor Label
1.3.6.1.4.1.20916.1.11.1.4.2Nodedigital-labels
1.3.6.1.4.1.20916.1.11.1.4.2.1Scalarlabels-digital-sen1read-onlymandatoryDigital Sensor Port 1 Label
1.3.6.1.4.1.20916.1.11.1.4.2.2Scalarlabels-digital-sen2read-onlymandatoryDigital Sensor Port 2 Label
1.3.6.1.4.1.20916.1.11.1.4.2.3Scalarlabels-digital-sen3read-onlymandatoryDigital Sensor Port 3 Label
1.3.6.1.4.1.20916.1.11.1.4.2.4Scalarlabels-digital-sen4read-onlymandatoryDigital Sensor Port 4 Label
1.3.6.1.4.1.20916.1.11.1.4.2.5Scalarlabels-digital-sen5read-onlymandatoryDigital Sensor Port 5 Label
1.3.6.1.4.1.20916.1.11.1.4.2.6Scalarlabels-digital-sen6read-onlymandatoryDigital Sensor Port 6 Label
1.3.6.1.4.1.20916.1.11.1.4.2.7Scalarlabels-digital-sen7read-onlymandatoryDigital Sensor Port 7 Label
1.3.6.1.4.1.20916.1.11.1.4.2.8Scalarlabels-digital-sen8read-onlymandatoryDigital Sensor Port 8 Label
1.3.6.1.4.1.20916.1.11.1.4.3Nodeswitch-labels
1.3.6.1.4.1.20916.1.11.1.4.3.1Scalarlabels-switch-sen1read-onlymandatorySwitch 1 Label
1.3.6.1.4.1.20916.1.11.1.4.3.2Scalarlabels-switch-sen2read-onlymandatorySwitch 2 Label
1.3.6.1.4.1.20916.1.11.1.4.3.3Scalarlabels-switch-sen3read-onlymandatorySwitch 3 Label
1.3.6.1.4.1.20916.1.11.1.4.3.4Scalarlabels-switch-sen4read-onlymandatorySwitch 4 Label
1.3.6.1.4.1.20916.1.11.1.4.3.5Scalarlabels-switch-sen5read-onlymandatorySwitch 5 Label
1.3.6.1.4.1.20916.1.11.1.4.3.6Scalarlabels-switch-sen6read-onlymandatorySwitch 6 Label
1.3.6.1.4.1.20916.1.11.1.4.3.7Scalarlabels-switch-sen7read-onlymandatorySwitch 7 Label
1.3.6.1.4.1.20916.1.11.1.4.3.8Scalarlabels-switch-sen8read-onlymandatorySwitch 8 Label
1.3.6.1.4.1.20916.1.11.1.4.3.9Scalarlabels-switch-sen9read-onlymandatorySwitch 9 Label
1.3.6.1.4.1.20916.1.11.1.4.3.10Scalarlabels-switch-sen10read-onlymandatorySwitch 10 Label
1.3.6.1.4.1.20916.1.11.1.4.3.11Scalarlabels-switch-sen11read-onlymandatorySwitch 11 Label
1.3.6.1.4.1.20916.1.11.1.4.3.12Scalarlabels-switch-sen12read-onlymandatorySwitch 12 Label
1.3.6.1.4.1.20916.1.11.1.4.3.13Scalarlabels-switch-sen13read-onlymandatorySwitch 13 Label
1.3.6.1.4.1.20916.1.11.1.4.3.14Scalarlabels-switch-sen14read-onlymandatorySwitch 14 Label
1.3.6.1.4.1.20916.1.11.1.4.3.15Scalarlabels-switch-sen15read-onlymandatorySwitch 15 Label
1.3.6.1.4.1.20916.1.11.1.4.3.16Scalarlabels-switch-sen16read-onlymandatorySwitch 16 Label
1.3.6.1.4.1.20916.1.11.1.4.4Nodeanalog-labels
1.3.6.1.4.1.20916.1.11.1.4.4.1Scalarlabels-analog-sen1read-onlymandatoryAnalog Sensor 1 Label
1.3.6.1.4.1.20916.1.11.1.4.4.2Scalarlabels-analog-sen2read-onlymandatoryAnalog Sensor 2 Label
1.3.6.1.4.1.20916.1.11.1.4.5Nodeinternal-relay-labels
1.3.6.1.4.1.20916.1.11.1.4.5.1Scalarinternal-relay-labels1read-onlymandatoryInternal Relay 1 Label
1.3.6.1.4.1.20916.1.11.1.4.5.2Scalarinternal-relay-labels2read-onlymandatoryInternal Relay 2 Label
1.3.6.1.4.1.20916.1.11.1.4.6Nodeexternal-relay-labels
1.3.6.1.4.1.20916.1.11.1.4.6.1Scalarexternal-relay-labels1read-onlymandatoryExternal Relay 1 Label
1.3.6.1.4.1.20916.1.11.1.4.6.2Scalarexternal-relay-labels2read-onlymandatoryExternal Relay 2 Label
1.3.6.1.4.1.20916.1.11.2Nodetraps
1.3.6.1.4.1.20916.1.11.2.1NotificationalarmmessagecurrentIndicates that an alarm condition has occurred on the sensor indicated by the alarmMessage variable.
1.3.6.1.4.1.20916.1.11.3Nodeexternalrelays
1.3.6.1.4.1.20916.1.11.3.1Nodeexternalrelay1
1.3.6.1.4.1.20916.1.11.3.1.1Scalarexternalrelay1-element-oneread-writemandatoryThe status of the first element on external relay 1.
1.3.6.1.4.1.20916.1.11.3.1.2Scalarexternalrelay1-element-tworead-writemandatoryThe status of the second element on external relay 1.
1.3.6.1.4.1.20916.1.11.3.1.3Scalarexternalrelay1-element-threeread-writemandatoryThe status of the third element on external relay 1.
1.3.6.1.4.1.20916.1.11.3.1.4Scalarexternalrelay1-element-fourread-writemandatoryThe status of the fourth element on external relay 1.
1.3.6.1.4.1.20916.1.11.3.1.5Scalarexternalrelay1-element-fiveread-writemandatoryThe status of the fifth element on external relay 1.
1.3.6.1.4.1.20916.1.11.3.1.6Scalarexternalrelay1-element-sixread-writemandatoryThe status of the sixth element on external relay 1.
1.3.6.1.4.1.20916.1.11.3.1.7Scalarexternalrelay1-element-sevenread-writemandatoryThe status of the seventh element on external relay 1.
1.3.6.1.4.1.20916.1.11.3.1.8Scalarexternalrelay1-element-eightread-writemandatoryThe status of the eighth element on external relay 1
1.3.6.1.4.1.20916.1.11.3.2Nodeexternalrelay2
1.3.6.1.4.1.20916.1.11.3.2.1Scalarexternalrelay2-element-oneread-writemandatoryThe status of the first element on external relay 2.
1.3.6.1.4.1.20916.1.11.3.2.2Scalarexternalrelay2-element-tworead-writemandatoryThe status of the second element on external relay 2.
1.3.6.1.4.1.20916.1.11.3.2.3Scalarexternalrelay2-element-threeread-writemandatoryThe status of the third element on external relay 2.
1.3.6.1.4.1.20916.1.11.3.2.4Scalarexternalrelay2-element-fourread-writemandatoryThe status of the fourth element on external relay 2.
1.3.6.1.4.1.20916.1.11.3.2.5Scalarexternalrelay2-element-fiveread-writemandatoryThe status of the fifth element on external relay 2.
1.3.6.1.4.1.20916.1.11.3.2.6Scalarexternalrelay2-element-sixread-writemandatoryThe status of the sixth element on external relay 2.
1.3.6.1.4.1.20916.1.11.3.2.7Scalarexternalrelay2-element-sevenread-writemandatoryThe status of the seventh element on external relay 2.
1.3.6.1.4.1.20916.1.11.3.2.8Scalarexternalrelay2-element-eightread-writemandatoryThe status of the eighth element on external relay 2