MIB Viewer

RackMonitor-MIB

175 objects
No module-level DESCRIPTION found.
Imported Objects
RFC-1212OBJECT-TYPE
RFC-1215TRAP-TYPE
RFC1155-SMIenterprises
RFC1213-MIBDisplayString
OIDNameAccessStatusDescription
1.3.6.1.4.1.534Nodepowerware
1.3.6.1.4.1.534.6Nodeproduct
1.3.6.1.4.1.534.6.7NodedataCenter
1.3.6.1.4.1.534.6.7.1NodeenvironmentalMonitor
1.3.6.1.4.1.534.6.7.1.1NodeinsObjects
1.3.6.1.4.1.534.6.7.1.1.1NodermIdent
1.3.6.1.4.1.534.6.7.1.1.1.1ScalarinsIdentManufacturerread-onlymandatoryThe name of the RackMonitor manufacturer.
1.3.6.1.4.1.534.6.7.1.1.1.2ScalarinsIdentModelread-onlymandatoryThe RackMonitor Model designation.
1.3.6.1.4.1.534.6.7.1.1.1.3ScalarinsIdentAgentSoftwareVersionread-onlymandatoryThe RackMonitor software/firmware version. This variable may or may not have the same value as upsIdentUPSSoftwareVersion in some implementations.
1.3.6.1.4.1.534.6.7.1.1.1.4ScalarinsIdentNameread-writemandatoryA string identifying the RackMonitor. This object should be set by the administrator.
1.3.6.1.4.1.534.6.7.1.1.2NodermConfig
1.3.6.1.4.1.534.6.7.1.1.2.1ScalarrmConfigMibVersionread-onlymandatoryThe version of MIB spec.
1.3.6.1.4.1.534.6.7.1.1.2.2NodermConfigNetwork
1.3.6.1.4.1.534.6.7.1.1.2.2.1ScalarrmConfigIpAddressread-writemandatoryThe ip address that NMS can identify the managed device
1.3.6.1.4.1.534.6.7.1.1.2.2.2ScalarrmConfigGatewayread-writemandatoryThe default gateway that allow device managed through routers
1.3.6.1.4.1.534.6.7.1.1.2.2.3ScalarrmConfigSubnetMaskread-writemandatoryInternet address subnet mask
1.3.6.1.4.1.534.6.7.1.1.2.3NodermConfigDateTime
1.3.6.1.4.1.534.6.7.1.1.2.3.1ScalarrmConfigDateread-writemandatoryThe date in Environmental Rack Monitor, format is (dd/mm/yyyy)
1.3.6.1.4.1.534.6.7.1.1.2.3.2ScalarrmConfigTimeread-writemandatoryThe time in Environmental Rack Monitor, format is (hh:mm:ss)
1.3.6.1.4.1.534.6.7.1.1.2.3.3ScalarrmConfigTimeFromNtpread-writemandatoryEnable/disable update of the date and time from the NTP server.
1.3.6.1.4.1.534.6.7.1.1.2.3.4ScalarrmConfigNtpIpAddressread-writemandatoryNTP IP address.
1.3.6.1.4.1.534.6.7.1.1.2.3.5ScalarrmConfigNtpTimeZoneread-writemandatoryEnable/disable update of the date and time from the NTP server.
1.3.6.1.4.1.534.6.7.1.1.2.3.6ScalarrmConfigDayLightSavingread-writemandatoryEnable/disable daylight saving for NTP time, if enabled, the time obtained from the NTP will be set one hour in advance to reflect daylight saving status.
1.3.6.1.4.1.534.6.7.1.1.2.4NodermConfigLog
1.3.6.1.4.1.534.6.7.1.1.2.4.1ScalarrmConfigHistoryLogFrequencyread-writemandatoryThe frequency of the history log update. The value is in seconds
1.3.6.1.4.1.534.6.7.1.1.2.4.2ScalarrmConfigExtHistoryLogFrequencyread-writemandatoryThe frequency of the extended history log update. The value is in seconds
1.3.6.1.4.1.534.6.7.1.1.2.4.3ScalarrmConfigConfigurationLogread-writemandatoryEnable/Disable Environmental Rack Monitor parameters change logging.
1.3.6.1.4.1.534.6.7.1.1.2.5ScalarrmConfigDhcpStatueread-writemandatoryEnable or Disable DHCP/BootP capability
1.3.6.1.4.1.534.6.7.1.1.2.6ScalarrmConfigPingStatueread-writemandatoryEnable or Disable Ping Echo capability
1.3.6.1.4.1.534.6.7.1.1.2.7ScalarrmConfigTftpStatueread-writemandatoryEnable or Disable TFTP network upgrade capability
1.3.6.1.4.1.534.6.7.1.1.2.8NodermConfigTelnet
1.3.6.1.4.1.534.6.7.1.1.2.8.1ScalarrmConfigTelnetStatueread-writemandatoryEnable or Disable telnet access
1.3.6.1.4.1.534.6.7.1.1.2.8.2ScalarrmConfigTelnetPortNumberread-writemandatorySetting the server port for telnet.
1.3.6.1.4.1.534.6.7.1.1.2.9NodermConfigHttp
1.3.6.1.4.1.534.6.7.1.1.2.9.1ScalarrmConfigHttpStatueread-writemandatoryEnable or Disable HTTP access
1.3.6.1.4.1.534.6.7.1.1.2.9.2ScalarrmConfigHttpPortNumberread-writemandatorySetting the server port of HTTP.
1.3.6.1.4.1.534.6.7.1.1.2.9.3ScalarrmConfigHttpSecurityread-writemandatoryEnable/Disable HTTP access for read-only users
1.3.6.1.4.1.534.6.7.1.1.2.10NodermConfigSnmp
1.3.6.1.4.1.534.6.7.1.1.2.10.1ScalarrmConfigSnmpStatueread-writemandatoryEnable or Disable SNMP access
1.3.6.1.4.1.534.6.7.1.1.2.10.2ScalarrmConfigSnmpPortNumberread-writemandatorySetting the server port for SNMP.
1.3.6.1.4.1.534.6.7.1.1.2.11NodermConfigControl
1.3.6.1.4.1.534.6.7.1.1.2.11.1ScalarrmConfigResetToDefaultread-writemandatoryReset all parameters of Environmental Rack Monitor to default values
1.3.6.1.4.1.534.6.7.1.1.2.11.2ScalarrmConfigRestartread-writemandatoryRestart rm
1.3.6.1.4.1.534.6.7.1.1.2.12NodermConfigTrap
1.3.6.1.4.1.534.6.7.1.1.2.12.1ScalarrmConfigTrapRetryCountread-writemandatoryThe count of repeat traps to send to NMS before trap acknowledge received.
1.3.6.1.4.1.534.6.7.1.1.2.12.2ScalarrmConfigTrapRetryTimeread-writemandatoryThe time between retry traps sent to NMS.
1.3.6.1.4.1.534.6.7.1.1.2.12.3ScalarrmConfigTrapAckSignatureread-writemandatoryThe signature of trap acknowledge.
1.3.6.1.4.1.534.6.7.1.1.2.13ScalarrmConfigPollRateread-writemandatoryThe frequency that the Rack Monitor will read from sensors (unit : second).
1.3.6.1.4.1.534.6.7.1.1.2.14TablermConfigTrapsReceiversTablenot-accessiblemandatoryA list of managers to send traps to. The number of entries is given by the value of rmConfigNumTrapReceivers
1.3.6.1.4.1.534.6.7.1.1.2.14.1RowrmConfigTrapsReceiversEntrynot-accessiblemandatoryThe managers to send traps to.
1.3.6.1.4.1.534.6.7.1.1.2.14.1.1ColumntrapsIndexread-onlymandatoryThe index to a trap receiver entry.
1.3.6.1.4.1.534.6.7.1.1.2.14.1.2ColumntrapsReceiverAddrread-writemandatoryThe IP address of the manager to send a trap to.
1.3.6.1.4.1.534.6.7.1.1.2.14.1.3ColumnreceiverCommunityStringread-writemandatoryThe community name to use in the trap when sent to the manager.
1.3.6.1.4.1.534.6.7.1.1.2.14.1.4ColumnreceiverSeverityLevelread-writemandatoryThe severity level of traps to be received by this manager.
1.3.6.1.4.1.534.6.7.1.1.2.14.1.5ColumnreceiverDescriptionread-writemandatoryDescription of trap receivers
1.3.6.1.4.1.534.6.7.1.1.2.15TablermConfigAccessControlTablenot-accessiblemandatoryA list of managers which can access rm with private community string.
1.3.6.1.4.1.534.6.7.1.1.2.15.1RowrmConfigAccessControlEntrynot-accessiblemandatoryThe managers.
1.3.6.1.4.1.534.6.7.1.1.2.15.1.1ColumnaccessIndexread-onlymandatoryThe index to a access control entry.
1.3.6.1.4.1.534.6.7.1.1.2.15.1.2ColumnaccessControlAddrread-writemandatoryThe IP address of the manager to access RackMonitor
1.3.6.1.4.1.534.6.7.1.1.2.15.1.3ColumnaccessCommunityStringread-writemandatoryThe community name to use in the manager when access RackMonitor
1.3.6.1.4.1.534.6.7.1.1.2.15.1.4ColumnaccessControlModeread-writemandatoryAccess type, only read/Write access type can change parameter of RackMonitor
1.3.6.1.4.1.534.6.7.1.1.2.16ScalarrmConfigTemperatureUnitread-writemandatoryThe temperature unit of the system, can be Celsius or Fahrenheit
1.3.6.1.4.1.534.6.7.1.1.2.17ScalarrmConfigDateFormatread-writemandatoryThe date format of the system, can be dd/mm/yyyy or mm/dd/yyyy
1.3.6.1.4.1.534.6.7.1.1.3NodesensorMonitor
1.3.6.1.4.1.534.6.7.1.1.3.1ScalarsmSensorNumberread-onlymandatoryThe number of sensors that can be monitored.
1.3.6.1.4.1.534.6.7.1.1.3.2TablesmSensorTablenot-accessiblemandatoryA list of sensor devices to be monitored.
1.3.6.1.4.1.534.6.7.1.1.3.2.1RowsmSensorEntrynot-accessiblemandatoryThe sensor device.
1.3.6.1.4.1.534.6.7.1.1.3.2.1.1ColumnsmDeviceIndexread-onlymandatoryThe index to a sensor device entry.
1.3.6.1.4.1.534.6.7.1.1.3.2.1.2ColumnsmDeviceStatusread-onlymandatoryThe device type plugged into RackMonitor.
1.3.6.1.4.1.534.6.7.1.1.3.2.1.3ColumnsmDeviceTemperatureread-onlymandatoryThe temperature of sensor on device RackMonitor, the unit is 0.1 degree.
1.3.6.1.4.1.534.6.7.1.1.3.2.1.4ColumnsmDeviceTemperatureAlarmread-onlymandatoryThe status of temperature sensor on device RackMonitor.
1.3.6.1.4.1.534.6.7.1.1.3.2.1.5ColumnsmDeviceHumidityread-onlymandatoryThe humidity of sensor on device RackMonitor, the unit is 0.1%.
1.3.6.1.4.1.534.6.7.1.1.3.2.1.6ColumnsmDeviceHumidityAlarmread-onlymandatoryThe device type plugged into RackMonitor.
1.3.6.1.4.1.534.6.7.1.1.3.2.1.7ColumnsmAlarm1read-onlymandatoryThe device type plugged into RackMonitor.
1.3.6.1.4.1.534.6.7.1.1.3.2.1.8ColumnsmAlarm2read-onlymandatoryThe device type plugged into RackMonitor.
1.3.6.1.4.1.534.6.7.1.1.4NodesensorConfig
1.3.6.1.4.1.534.6.7.1.1.4.1ScalarscSensorNumberread-onlymandatoryThe number of sensors that can be plugged into RackMonitor.
1.3.6.1.4.1.534.6.7.1.1.4.2TablescSensorTablenot-accessiblemandatoryA list of sensor devices to be configured.
1.3.6.1.4.1.534.6.7.1.1.4.2.1RowscSensorEntrynot-accessiblemandatoryThe sensor device.
1.3.6.1.4.1.534.6.7.1.1.4.2.1.1ColumnscDeviceIndexread-onlymandatoryThe index to a sensor device entry.
1.3.6.1.4.1.534.6.7.1.1.4.2.1.2ColumnscDeviceNameread-writemandatoryThe name of the sensor device for identification.
1.3.6.1.4.1.534.6.7.1.1.4.2.1.3ColumnscDeviceStateread-writemandatoryThe setup of sensor device type.
1.3.6.1.4.1.534.6.7.1.1.4.3NodescSensor1
1.3.6.1.4.1.534.6.7.1.1.4.3.1ScalarscSensor1DeviceNameread-writemandatoryThe name of sensor device.
1.3.6.1.4.1.534.6.7.1.1.4.3.2ScalarscSensor1DeviceStateread-writemandatoryThe setup of sensor device type.
1.3.6.1.4.1.534.6.7.1.1.4.3.3NodescSensor1Temperature
1.3.6.1.4.1.534.6.7.1.1.4.3.3.1ScalarscSensor1TemperatureNameread-writemandatoryThe temperature sensor name.
1.3.6.1.4.1.534.6.7.1.1.4.3.3.2ScalarscSensor1TemperatureLowWarningread-writemandatoryThe set point to trigger low warning alarm.
1.3.6.1.4.1.534.6.7.1.1.4.3.3.3ScalarscSensor1TemperatureLowCriticalread-writemandatoryThe threshold to trigger low critical alarm.
1.3.6.1.4.1.534.6.7.1.1.4.3.3.4ScalarscSensor1TemperatureHighWarningread-writemandatoryThe threshold to trigger high warning alarm.
1.3.6.1.4.1.534.6.7.1.1.4.3.3.5ScalarscSensor1TemperatureHighCriticalread-writemandatoryThe threshold to trigger high critical alarm.
1.3.6.1.4.1.534.6.7.1.1.4.3.3.6ScalarscSensor1TemperatureHysteresisread-writemandatoryThe set value to prevent too many alarms when temperature is hovering around the set threshold.
1.3.6.1.4.1.534.6.7.1.1.4.3.3.7ScalarscSensor1TemperatureCalibrationread-writemandatoryThe set value to get the correct temperature according to the reference temperature.
1.3.6.1.4.1.534.6.7.1.1.4.3.3.8ScalarscSensor1TemperatureLowWarningStatusread-writemandatoryEnable/Disable the set point to trigger low warning alarm.
1.3.6.1.4.1.534.6.7.1.1.4.3.3.9ScalarscSensor1TemperatureLowCriticalStatusread-writemandatoryEnable/Disable the set point to trigger low critical alarm.
1.3.6.1.4.1.534.6.7.1.1.4.3.3.10ScalarscSensor1TemperatureHighWarningStatusread-writemandatoryEnable/Disable the set point to trigger high warning alarm.
1.3.6.1.4.1.534.6.7.1.1.4.3.3.11ScalarscSensor1TemperatureHighCriticalStatusread-writemandatoryEnable/disable the set point to trigger high critical alarm.
1.3.6.1.4.1.534.6.7.1.1.4.3.4NodescSensor1Humidity
1.3.6.1.4.1.534.6.7.1.1.4.3.4.1ScalarscSensor1HumdityNameread-writemandatoryThe humidity sensor name.
1.3.6.1.4.1.534.6.7.1.1.4.3.4.2ScalarscSensor1HumidityLowWarningread-writemandatoryThe set point to trigger low warning alarm.
1.3.6.1.4.1.534.6.7.1.1.4.3.4.3ScalarscSensor1HumidityLowCriticalread-writemandatoryThe threshold to trigger low critical alarm.
1.3.6.1.4.1.534.6.7.1.1.4.3.4.4ScalarscSensor1HumidityHighWarningread-writemandatoryThe threshold to trigger high warning alarm.
1.3.6.1.4.1.534.6.7.1.1.4.3.4.5ScalarscSensor1HumidityHighCriticalread-writemandatoryThe threshold to trigger high critical alarm.
1.3.6.1.4.1.534.6.7.1.1.4.3.4.6ScalarscSensor1HumidityHysteresisread-writemandatoryThe set value to prevent too many alarms when Humidity is hovering around the set threshold.
1.3.6.1.4.1.534.6.7.1.1.4.3.4.7ScalarscSensor1HumidityCalibrationread-writemandatoryThe set value to get the correct temperature according to your reference temperature.
1.3.6.1.4.1.534.6.7.1.1.4.3.4.8ScalarscSensor1HumidityLowWarningStatusread-writemandatoryEnable/Disable the set point to trigger low warning alarm.
1.3.6.1.4.1.534.6.7.1.1.4.3.4.9ScalarscSensor1HumidityLowCriticalStatusread-writemandatoryEnable/Disable the set point to trigger low critical alarm.
1.3.6.1.4.1.534.6.7.1.1.4.3.4.10ScalarscSensor1HumidityHighWarningStatusread-writemandatoryEnable/Disable the set point to trigger high warning alarm.
1.3.6.1.4.1.534.6.7.1.1.4.3.4.11ScalarscSensor1HumidityHighCriticalStatusread-writemandatoryEnable/Disable the set point to trigger high critical alarm.
1.3.6.1.4.1.534.6.7.1.1.4.3.5NodescSensor1Alarm1
1.3.6.1.4.1.534.6.7.1.1.4.3.5.1ScalarscSensor1Alarm1Nameread-writemandatoryThe name of alarm-1.
1.3.6.1.4.1.534.6.7.1.1.4.3.5.2ScalarscSensor1Alarm1Stateread-writemandatorySetup the signal type to trigger alarm.
1.3.6.1.4.1.534.6.7.1.1.4.3.5.3ScalarscSensor1Alarm1Hysteresisread-writemandatoryThe set value to delay the alarm triggered when event occurs.
1.3.6.1.4.1.534.6.7.1.1.4.3.6NodescSensor1Alarm2
1.3.6.1.4.1.534.6.7.1.1.4.3.6.1ScalarscSensor1Alarm2Nameread-writemandatoryThe name of alarm-1.
1.3.6.1.4.1.534.6.7.1.1.4.3.6.2ScalarscSensor1Alarm2Stateread-writemandatorySetup the signal type to trigger alarm.
1.3.6.1.4.1.534.6.7.1.1.4.3.6.3ScalarscSensor1Alarm2Hysteresisread-writemandatoryThe set value to delay the alarm triggered when event occurs.
1.3.6.1.4.1.534.6.7.1.1.4.4NodescSensor2
1.3.6.1.4.1.534.6.7.1.1.4.4.1ScalarscSensor2DeviceNameread-writemandatoryThe name of sensor device.
1.3.6.1.4.1.534.6.7.1.1.4.4.2ScalarscSensor2DeviceStateread-writemandatoryThe setup of sensor device type.
1.3.6.1.4.1.534.6.7.1.1.4.4.3NodescSensor2Temperature
1.3.6.1.4.1.534.6.7.1.1.4.4.3.1ScalarscSensor2TemperatureNameread-writemandatoryThe temperature sensor name.
1.3.6.1.4.1.534.6.7.1.1.4.4.3.2ScalarscSensor2TemperatureLowWarningread-writemandatoryThe set point to trigger low warning alarm.
1.3.6.1.4.1.534.6.7.1.1.4.4.3.3ScalarscSensor2TemperatureLowCriticalread-writemandatoryThe threshold to trigger low critical alarm.
1.3.6.1.4.1.534.6.7.1.1.4.4.3.4ScalarscSensor2TemperatureHighWarningread-writemandatoryThe threshold to trigger high warning alarm.
1.3.6.1.4.1.534.6.7.1.1.4.4.3.5ScalarscSensor2TemperatureHighCriticalread-writemandatoryThe threshold to trigger high critical alarm.
1.3.6.1.4.1.534.6.7.1.1.4.4.3.6ScalarscSensor2TemperatureHysteresisread-writemandatoryThe set value to prevent too many alarms when temperature is hovering around the set threshold.
1.3.6.1.4.1.534.6.7.1.1.4.4.3.7ScalarscSensor2TemperatureCalibrationread-writemandatoryThe set value to get the correct temperature according to your reference temperature.
1.3.6.1.4.1.534.6.7.1.1.4.4.3.8ScalarscSensor2TemperatureLowWarningStatusread-writemandatoryEnable/Disable the set point to trigger low warning alarm.
1.3.6.1.4.1.534.6.7.1.1.4.4.3.9ScalarscSensor2TemperatureLowCriticalStatusread-writemandatoryEnable/Disable the set point to trigger low critical alarm.
1.3.6.1.4.1.534.6.7.1.1.4.4.3.10ScalarscSensor2TemperatureHighWarningStatusread-writemandatoryEnable/Disable the set point to trigger high warning alarm.
1.3.6.1.4.1.534.6.7.1.1.4.4.3.11ScalarscSensor2TemperatureHighCriticalStatusread-writemandatoryEnable/Disable the set point to trigger high critical alarm.
1.3.6.1.4.1.534.6.7.1.1.4.4.4NodescSensor2Humidity
1.3.6.1.4.1.534.6.7.1.1.4.4.4.1ScalarscSensor2HumdityNameread-writemandatoryThe humidity sensor name.
1.3.6.1.4.1.534.6.7.1.1.4.4.4.2ScalarscSensor2HumidityLowWarningread-writemandatoryThe set point to trigger low warning alarm.
1.3.6.1.4.1.534.6.7.1.1.4.4.4.3ScalarscSensor2HumidityLowCriticalread-writemandatoryThe threshold to trigger low critical alarm.
1.3.6.1.4.1.534.6.7.1.1.4.4.4.4ScalarscSensor2HumidityHighWarningread-writemandatoryThe threshold to trigger high warning alarm.
1.3.6.1.4.1.534.6.7.1.1.4.4.4.5ScalarscSensor2HumidityHighCriticalread-writemandatoryThe threshold to trigger high critical alarm.
1.3.6.1.4.1.534.6.7.1.1.4.4.4.6ScalarscSensor2HumidityHysteresisread-writemandatoryThe set value to prevent too many alarms when Humidity is hovering around the set threshold.
1.3.6.1.4.1.534.6.7.1.1.4.4.4.7ScalarscSensor2HumidityCalibrationread-writemandatoryThe set value to get the correct temperature according to the reference temperature.
1.3.6.1.4.1.534.6.7.1.1.4.4.4.8ScalarscSensor2HumidityLowWarningStatusread-writemandatoryEnable/Disable the set point to trigger low warning alarm.
1.3.6.1.4.1.534.6.7.1.1.4.4.4.9ScalarscSensor2HumidityLowCriticalStatusread-writemandatoryEnable/Disable the set point to trigger low critical alarm.
1.3.6.1.4.1.534.6.7.1.1.4.4.4.10ScalarscSensor2HumidityHighWarningStatusread-writemandatoryEnable/Disable the set point to trigger high warning alarm.
1.3.6.1.4.1.534.6.7.1.1.4.4.4.11ScalarscSensor2HumidityHighCriticalStatusread-writemandatoryEnable/Disable the set point to trigger high critical alarm.
1.3.6.1.4.1.534.6.7.1.1.4.4.5NodescSensor2Alarm1
1.3.6.1.4.1.534.6.7.1.1.4.4.5.1ScalarscSensor2Alarm1Nameread-writemandatoryThe name of alarm-1.
1.3.6.1.4.1.534.6.7.1.1.4.4.5.2ScalarscSensor2Alarm1Stateread-writemandatorySetup the signal type to trigger alarm.
1.3.6.1.4.1.534.6.7.1.1.4.4.5.3ScalarscSensor2Alarm1Hysteresisread-writemandatoryThe set value to delay the alarm triggered when event occurs.
1.3.6.1.4.1.534.6.7.1.1.4.4.6NodescSensor2Alarm2
1.3.6.1.4.1.534.6.7.1.1.4.4.6.1ScalarscSensor2Alarm2Nameread-writemandatoryThe name of alarm-1.
1.3.6.1.4.1.534.6.7.1.1.4.4.6.2ScalarscSensor2Alarm2Stateread-writemandatorySetup the signal type to trigger alarm.
1.3.6.1.4.1.534.6.7.1.1.4.4.6.3ScalarscSensor2Alarm2Hysteresisread-writemandatoryThe set value to delay the alarm triggered when event occurs.
1.3.6.1.4.1.534.6.7.1.2NodermTraps
1.3.6.1.4.1.534.6.7.1.2.1NodermCommunicationRestoredINFORMATION: Communication between RackMonitor and sensor had established.
1.3.6.1.4.1.534.6.7.1.2.2NodermCommunicationLostWARNING: Communication between RackMonitor and sensor had lost.
1.3.6.1.4.1.534.6.7.1.2.3NodermAlarm1InactiveINFORMATION: Alarm1 of sensor had return from active state.
1.3.6.1.4.1.534.6.7.1.2.4NodermAlarm1ActiveWARNING: Alarm1 has become active.
1.3.6.1.4.1.534.6.7.1.2.5NodermAlarm2InactiveINFORMATION: Alarm2 of sensor has returned to normal state.
1.3.6.1.4.1.534.6.7.1.2.6NodermAlarm2ActiveWARNING: Alarm2 had became active.
1.3.6.1.4.1.534.6.7.1.2.7NodermTemperatureNotHighWarningINFORMATION: The temperature of sensor had return from High warning to normal.
1.3.6.1.4.1.534.6.7.1.2.8NodermTemperatureHighWarningWARNING: The temperature of sensor was higher than High warning set point.
1.3.6.1.4.1.534.6.7.1.2.9NodermTemperatureNotLowWarningINFORMATION: The temperature of sensor had return from low warning to normal.
1.3.6.1.4.1.534.6.7.1.2.10NodermTemperatureLowWarningWARNING: The temperature of sensor was lower than low warning set point.
1.3.6.1.4.1.534.6.7.1.2.11NodermTemperatureNotHighCriticalINFORMATION: The temperature of sensor lower than high critical set point.
1.3.6.1.4.1.534.6.7.1.2.12NodermTemperatureHighCriticalCRITICAL: The temperature of sensor was higher than high critical set point.
1.3.6.1.4.1.534.6.7.1.2.13NodermTemperatureNotLowCriticalINFORMATION: The temperature of sensor was higher than low critical set point.
1.3.6.1.4.1.534.6.7.1.2.14NodermTemperatureLowCriticalCRITICAL: The temperature of sensor was lower than low critical set point.
1.3.6.1.4.1.534.6.7.1.2.15NodermHumidityNotHighWarningINFORMATION: The humidity of sensor had return from High warning to normal.
1.3.6.1.4.1.534.6.7.1.2.16NodermHumidityHighWarningWARNING: The humidity of sensor was higher than High warning set point.
1.3.6.1.4.1.534.6.7.1.2.17NodermHumidityNotLowWarningINFORMATION: The humidity of sensor had return from low warning to normal.
1.3.6.1.4.1.534.6.7.1.2.18NodermHumidityLowWarningWARNING: The humidity of sensor was lower than low warning set point.
1.3.6.1.4.1.534.6.7.1.2.19NodermHumidityNotHighCriticalINFORMATION: The humidity of sensor lower than high critical set point.
1.3.6.1.4.1.534.6.7.1.2.20NodermHumidityHighCriticalCRITICAL: The humidity of sensor was higher than high critical set point.
1.3.6.1.4.1.534.6.7.1.2.21NodermHumidityNotLowCriticalINFORMATION: The humidity of sensor was higher than low critical set point.
1.3.6.1.4.1.534.6.7.1.2.22NodermHumidityLowCriticalCRITICAL: The humidity of sensor was lower than low critical set point.