RackMonitor-MIB
175 objects
No module-level DESCRIPTION found.
Imported Objects
| RFC-1212 | OBJECT-TYPE |
| RFC-1215 | TRAP-TYPE |
| RFC1155-SMI | enterprises |
| RFC1213-MIB | DisplayString |
| OID | Name | Access | Status | Description |
|---|---|---|---|---|
| 1.3.6.1.4.1.534 | Nodepowerware | |||
| 1.3.6.1.4.1.534.6 | Nodeproduct | |||
| 1.3.6.1.4.1.534.6.7 | NodedataCenter | |||
| 1.3.6.1.4.1.534.6.7.1 | NodeenvironmentalMonitor | |||
| 1.3.6.1.4.1.534.6.7.1.1 | NodeinsObjects | |||
| 1.3.6.1.4.1.534.6.7.1.1.1 | NodermIdent | |||
| 1.3.6.1.4.1.534.6.7.1.1.1.1 | ScalarinsIdentManufacturer | read-only | mandatory | The name of the RackMonitor manufacturer. |
| 1.3.6.1.4.1.534.6.7.1.1.1.2 | ScalarinsIdentModel | read-only | mandatory | The RackMonitor Model designation. |
| 1.3.6.1.4.1.534.6.7.1.1.1.3 | ScalarinsIdentAgentSoftwareVersion | read-only | mandatory | The RackMonitor software/firmware version. This variable may or may not have the same value as upsIdentUPSSoftwareVersion in some implementations. |
| 1.3.6.1.4.1.534.6.7.1.1.1.4 | ScalarinsIdentName | read-write | mandatory | A string identifying the RackMonitor. This object should be set by the administrator. |
| 1.3.6.1.4.1.534.6.7.1.1.2 | NodermConfig | |||
| 1.3.6.1.4.1.534.6.7.1.1.2.1 | ScalarrmConfigMibVersion | read-only | mandatory | The version of MIB spec. |
| 1.3.6.1.4.1.534.6.7.1.1.2.2 | NodermConfigNetwork | |||
| 1.3.6.1.4.1.534.6.7.1.1.2.2.1 | ScalarrmConfigIpAddress | read-write | mandatory | The ip address that NMS can identify the managed device |
| 1.3.6.1.4.1.534.6.7.1.1.2.2.2 | ScalarrmConfigGateway | read-write | mandatory | The default gateway that allow device managed through routers |
| 1.3.6.1.4.1.534.6.7.1.1.2.2.3 | ScalarrmConfigSubnetMask | read-write | mandatory | Internet address subnet mask |
| 1.3.6.1.4.1.534.6.7.1.1.2.3 | NodermConfigDateTime | |||
| 1.3.6.1.4.1.534.6.7.1.1.2.3.1 | ScalarrmConfigDate | read-write | mandatory | The date in Environmental Rack Monitor, format is (dd/mm/yyyy) |
| 1.3.6.1.4.1.534.6.7.1.1.2.3.2 | ScalarrmConfigTime | read-write | mandatory | The time in Environmental Rack Monitor, format is (hh:mm:ss) |
| 1.3.6.1.4.1.534.6.7.1.1.2.3.3 | ScalarrmConfigTimeFromNtp | read-write | mandatory | Enable/disable update of the date and time from the NTP server. |
| 1.3.6.1.4.1.534.6.7.1.1.2.3.4 | ScalarrmConfigNtpIpAddress | read-write | mandatory | NTP IP address. |
| 1.3.6.1.4.1.534.6.7.1.1.2.3.5 | ScalarrmConfigNtpTimeZone | read-write | mandatory | Enable/disable update of the date and time from the NTP server. |
| 1.3.6.1.4.1.534.6.7.1.1.2.3.6 | ScalarrmConfigDayLightSaving | read-write | mandatory | Enable/disable daylight saving for NTP time, if enabled, the time obtained from the NTP will be set one hour in advance to reflect daylight saving status. |
| 1.3.6.1.4.1.534.6.7.1.1.2.4 | NodermConfigLog | |||
| 1.3.6.1.4.1.534.6.7.1.1.2.4.1 | ScalarrmConfigHistoryLogFrequency | read-write | mandatory | The frequency of the history log update. The value is in seconds |
| 1.3.6.1.4.1.534.6.7.1.1.2.4.2 | ScalarrmConfigExtHistoryLogFrequency | read-write | mandatory | The frequency of the extended history log update. The value is in seconds |
| 1.3.6.1.4.1.534.6.7.1.1.2.4.3 | ScalarrmConfigConfigurationLog | read-write | mandatory | Enable/Disable Environmental Rack Monitor parameters change logging. |
| 1.3.6.1.4.1.534.6.7.1.1.2.5 | ScalarrmConfigDhcpStatue | read-write | mandatory | Enable or Disable DHCP/BootP capability |
| 1.3.6.1.4.1.534.6.7.1.1.2.6 | ScalarrmConfigPingStatue | read-write | mandatory | Enable or Disable Ping Echo capability |
| 1.3.6.1.4.1.534.6.7.1.1.2.7 | ScalarrmConfigTftpStatue | read-write | mandatory | Enable or Disable TFTP network upgrade capability |
| 1.3.6.1.4.1.534.6.7.1.1.2.8 | NodermConfigTelnet | |||
| 1.3.6.1.4.1.534.6.7.1.1.2.8.1 | ScalarrmConfigTelnetStatue | read-write | mandatory | Enable or Disable telnet access |
| 1.3.6.1.4.1.534.6.7.1.1.2.8.2 | ScalarrmConfigTelnetPortNumber | read-write | mandatory | Setting the server port for telnet. |
| 1.3.6.1.4.1.534.6.7.1.1.2.9 | NodermConfigHttp | |||
| 1.3.6.1.4.1.534.6.7.1.1.2.9.1 | ScalarrmConfigHttpStatue | read-write | mandatory | Enable or Disable HTTP access |
| 1.3.6.1.4.1.534.6.7.1.1.2.9.2 | ScalarrmConfigHttpPortNumber | read-write | mandatory | Setting the server port of HTTP. |
| 1.3.6.1.4.1.534.6.7.1.1.2.9.3 | ScalarrmConfigHttpSecurity | read-write | mandatory | Enable/Disable HTTP access for read-only users |
| 1.3.6.1.4.1.534.6.7.1.1.2.10 | NodermConfigSnmp | |||
| 1.3.6.1.4.1.534.6.7.1.1.2.10.1 | ScalarrmConfigSnmpStatue | read-write | mandatory | Enable or Disable SNMP access |
| 1.3.6.1.4.1.534.6.7.1.1.2.10.2 | ScalarrmConfigSnmpPortNumber | read-write | mandatory | Setting the server port for SNMP. |
| 1.3.6.1.4.1.534.6.7.1.1.2.11 | NodermConfigControl | |||
| 1.3.6.1.4.1.534.6.7.1.1.2.11.1 | ScalarrmConfigResetToDefault | read-write | mandatory | Reset all parameters of Environmental Rack Monitor to default values |
| 1.3.6.1.4.1.534.6.7.1.1.2.11.2 | ScalarrmConfigRestart | read-write | mandatory | Restart rm |
| 1.3.6.1.4.1.534.6.7.1.1.2.12 | NodermConfigTrap | |||
| 1.3.6.1.4.1.534.6.7.1.1.2.12.1 | ScalarrmConfigTrapRetryCount | read-write | mandatory | The count of repeat traps to send to NMS before trap acknowledge received. |
| 1.3.6.1.4.1.534.6.7.1.1.2.12.2 | ScalarrmConfigTrapRetryTime | read-write | mandatory | The time between retry traps sent to NMS. |
| 1.3.6.1.4.1.534.6.7.1.1.2.12.3 | ScalarrmConfigTrapAckSignature | read-write | mandatory | The signature of trap acknowledge. |
| 1.3.6.1.4.1.534.6.7.1.1.2.13 | ScalarrmConfigPollRate | read-write | mandatory | The frequency that the Rack Monitor will read from sensors (unit : second). |
| 1.3.6.1.4.1.534.6.7.1.1.2.14 | TablermConfigTrapsReceiversTable | not-accessible | mandatory | A list of managers to send traps to. The number of entries is given by the value of rmConfigNumTrapReceivers |
| 1.3.6.1.4.1.534.6.7.1.1.2.14.1 | RowrmConfigTrapsReceiversEntry | not-accessible | mandatory | The managers to send traps to. |
| 1.3.6.1.4.1.534.6.7.1.1.2.14.1.1 | ColumntrapsIndex | read-only | mandatory | The index to a trap receiver entry. |
| 1.3.6.1.4.1.534.6.7.1.1.2.14.1.2 | ColumntrapsReceiverAddr | read-write | mandatory | The IP address of the manager to send a trap to. |
| 1.3.6.1.4.1.534.6.7.1.1.2.14.1.3 | ColumnreceiverCommunityString | read-write | mandatory | The community name to use in the trap when sent to the manager. |
| 1.3.6.1.4.1.534.6.7.1.1.2.14.1.4 | ColumnreceiverSeverityLevel | read-write | mandatory | The severity level of traps to be received by this manager. |
| 1.3.6.1.4.1.534.6.7.1.1.2.14.1.5 | ColumnreceiverDescription | read-write | mandatory | Description of trap receivers |
| 1.3.6.1.4.1.534.6.7.1.1.2.15 | TablermConfigAccessControlTable | not-accessible | mandatory | A list of managers which can access rm with private community string. |
| 1.3.6.1.4.1.534.6.7.1.1.2.15.1 | RowrmConfigAccessControlEntry | not-accessible | mandatory | The managers. |
| 1.3.6.1.4.1.534.6.7.1.1.2.15.1.1 | ColumnaccessIndex | read-only | mandatory | The index to a access control entry. |
| 1.3.6.1.4.1.534.6.7.1.1.2.15.1.2 | ColumnaccessControlAddr | read-write | mandatory | The IP address of the manager to access RackMonitor |
| 1.3.6.1.4.1.534.6.7.1.1.2.15.1.3 | ColumnaccessCommunityString | read-write | mandatory | The community name to use in the manager when access RackMonitor |
| 1.3.6.1.4.1.534.6.7.1.1.2.15.1.4 | ColumnaccessControlMode | read-write | mandatory | Access type, only read/Write access type can change parameter of RackMonitor |
| 1.3.6.1.4.1.534.6.7.1.1.2.16 | ScalarrmConfigTemperatureUnit | read-write | mandatory | The temperature unit of the system, can be Celsius or Fahrenheit |
| 1.3.6.1.4.1.534.6.7.1.1.2.17 | ScalarrmConfigDateFormat | read-write | mandatory | The date format of the system, can be dd/mm/yyyy or mm/dd/yyyy |
| 1.3.6.1.4.1.534.6.7.1.1.3 | NodesensorMonitor | |||
| 1.3.6.1.4.1.534.6.7.1.1.3.1 | ScalarsmSensorNumber | read-only | mandatory | The number of sensors that can be monitored. |
| 1.3.6.1.4.1.534.6.7.1.1.3.2 | TablesmSensorTable | not-accessible | mandatory | A list of sensor devices to be monitored. |
| 1.3.6.1.4.1.534.6.7.1.1.3.2.1 | RowsmSensorEntry | not-accessible | mandatory | The sensor device. |
| 1.3.6.1.4.1.534.6.7.1.1.3.2.1.1 | ColumnsmDeviceIndex | read-only | mandatory | The index to a sensor device entry. |
| 1.3.6.1.4.1.534.6.7.1.1.3.2.1.2 | ColumnsmDeviceStatus | read-only | mandatory | The device type plugged into RackMonitor. |
| 1.3.6.1.4.1.534.6.7.1.1.3.2.1.3 | ColumnsmDeviceTemperature | read-only | mandatory | The temperature of sensor on device RackMonitor, the unit is 0.1 degree. |
| 1.3.6.1.4.1.534.6.7.1.1.3.2.1.4 | ColumnsmDeviceTemperatureAlarm | read-only | mandatory | The status of temperature sensor on device RackMonitor. |
| 1.3.6.1.4.1.534.6.7.1.1.3.2.1.5 | ColumnsmDeviceHumidity | read-only | mandatory | The humidity of sensor on device RackMonitor, the unit is 0.1%. |
| 1.3.6.1.4.1.534.6.7.1.1.3.2.1.6 | ColumnsmDeviceHumidityAlarm | read-only | mandatory | The device type plugged into RackMonitor. |
| 1.3.6.1.4.1.534.6.7.1.1.3.2.1.7 | ColumnsmAlarm1 | read-only | mandatory | The device type plugged into RackMonitor. |
| 1.3.6.1.4.1.534.6.7.1.1.3.2.1.8 | ColumnsmAlarm2 | read-only | mandatory | The device type plugged into RackMonitor. |
| 1.3.6.1.4.1.534.6.7.1.1.4 | NodesensorConfig | |||
| 1.3.6.1.4.1.534.6.7.1.1.4.1 | ScalarscSensorNumber | read-only | mandatory | The number of sensors that can be plugged into RackMonitor. |
| 1.3.6.1.4.1.534.6.7.1.1.4.2 | TablescSensorTable | not-accessible | mandatory | A list of sensor devices to be configured. |
| 1.3.6.1.4.1.534.6.7.1.1.4.2.1 | RowscSensorEntry | not-accessible | mandatory | The sensor device. |
| 1.3.6.1.4.1.534.6.7.1.1.4.2.1.1 | ColumnscDeviceIndex | read-only | mandatory | The index to a sensor device entry. |
| 1.3.6.1.4.1.534.6.7.1.1.4.2.1.2 | ColumnscDeviceName | read-write | mandatory | The name of the sensor device for identification. |
| 1.3.6.1.4.1.534.6.7.1.1.4.2.1.3 | ColumnscDeviceState | read-write | mandatory | The setup of sensor device type. |
| 1.3.6.1.4.1.534.6.7.1.1.4.3 | NodescSensor1 | |||
| 1.3.6.1.4.1.534.6.7.1.1.4.3.1 | ScalarscSensor1DeviceName | read-write | mandatory | The name of sensor device. |
| 1.3.6.1.4.1.534.6.7.1.1.4.3.2 | ScalarscSensor1DeviceState | read-write | mandatory | The setup of sensor device type. |
| 1.3.6.1.4.1.534.6.7.1.1.4.3.3 | NodescSensor1Temperature | |||
| 1.3.6.1.4.1.534.6.7.1.1.4.3.3.1 | ScalarscSensor1TemperatureName | read-write | mandatory | The temperature sensor name. |
| 1.3.6.1.4.1.534.6.7.1.1.4.3.3.2 | ScalarscSensor1TemperatureLowWarning | read-write | mandatory | The set point to trigger low warning alarm. |
| 1.3.6.1.4.1.534.6.7.1.1.4.3.3.3 | ScalarscSensor1TemperatureLowCritical | read-write | mandatory | The threshold to trigger low critical alarm. |
| 1.3.6.1.4.1.534.6.7.1.1.4.3.3.4 | ScalarscSensor1TemperatureHighWarning | read-write | mandatory | The threshold to trigger high warning alarm. |
| 1.3.6.1.4.1.534.6.7.1.1.4.3.3.5 | ScalarscSensor1TemperatureHighCritical | read-write | mandatory | The threshold to trigger high critical alarm. |
| 1.3.6.1.4.1.534.6.7.1.1.4.3.3.6 | ScalarscSensor1TemperatureHysteresis | read-write | mandatory | The set value to prevent too many alarms when temperature is hovering around the set threshold. |
| 1.3.6.1.4.1.534.6.7.1.1.4.3.3.7 | ScalarscSensor1TemperatureCalibration | read-write | mandatory | The set value to get the correct temperature according to the reference temperature. |
| 1.3.6.1.4.1.534.6.7.1.1.4.3.3.8 | ScalarscSensor1TemperatureLowWarningStatus | read-write | mandatory | Enable/Disable the set point to trigger low warning alarm. |
| 1.3.6.1.4.1.534.6.7.1.1.4.3.3.9 | ScalarscSensor1TemperatureLowCriticalStatus | read-write | mandatory | Enable/Disable the set point to trigger low critical alarm. |
| 1.3.6.1.4.1.534.6.7.1.1.4.3.3.10 | ScalarscSensor1TemperatureHighWarningStatus | read-write | mandatory | Enable/Disable the set point to trigger high warning alarm. |
| 1.3.6.1.4.1.534.6.7.1.1.4.3.3.11 | ScalarscSensor1TemperatureHighCriticalStatus | read-write | mandatory | Enable/disable the set point to trigger high critical alarm. |
| 1.3.6.1.4.1.534.6.7.1.1.4.3.4 | NodescSensor1Humidity | |||
| 1.3.6.1.4.1.534.6.7.1.1.4.3.4.1 | ScalarscSensor1HumdityName | read-write | mandatory | The humidity sensor name. |
| 1.3.6.1.4.1.534.6.7.1.1.4.3.4.2 | ScalarscSensor1HumidityLowWarning | read-write | mandatory | The set point to trigger low warning alarm. |
| 1.3.6.1.4.1.534.6.7.1.1.4.3.4.3 | ScalarscSensor1HumidityLowCritical | read-write | mandatory | The threshold to trigger low critical alarm. |
| 1.3.6.1.4.1.534.6.7.1.1.4.3.4.4 | ScalarscSensor1HumidityHighWarning | read-write | mandatory | The threshold to trigger high warning alarm. |
| 1.3.6.1.4.1.534.6.7.1.1.4.3.4.5 | ScalarscSensor1HumidityHighCritical | read-write | mandatory | The threshold to trigger high critical alarm. |
| 1.3.6.1.4.1.534.6.7.1.1.4.3.4.6 | ScalarscSensor1HumidityHysteresis | read-write | mandatory | The set value to prevent too many alarms when Humidity is hovering around the set threshold. |
| 1.3.6.1.4.1.534.6.7.1.1.4.3.4.7 | ScalarscSensor1HumidityCalibration | read-write | mandatory | The set value to get the correct temperature according to your reference temperature. |
| 1.3.6.1.4.1.534.6.7.1.1.4.3.4.8 | ScalarscSensor1HumidityLowWarningStatus | read-write | mandatory | Enable/Disable the set point to trigger low warning alarm. |
| 1.3.6.1.4.1.534.6.7.1.1.4.3.4.9 | ScalarscSensor1HumidityLowCriticalStatus | read-write | mandatory | Enable/Disable the set point to trigger low critical alarm. |
| 1.3.6.1.4.1.534.6.7.1.1.4.3.4.10 | ScalarscSensor1HumidityHighWarningStatus | read-write | mandatory | Enable/Disable the set point to trigger high warning alarm. |
| 1.3.6.1.4.1.534.6.7.1.1.4.3.4.11 | ScalarscSensor1HumidityHighCriticalStatus | read-write | mandatory | Enable/Disable the set point to trigger high critical alarm. |
| 1.3.6.1.4.1.534.6.7.1.1.4.3.5 | NodescSensor1Alarm1 | |||
| 1.3.6.1.4.1.534.6.7.1.1.4.3.5.1 | ScalarscSensor1Alarm1Name | read-write | mandatory | The name of alarm-1. |
| 1.3.6.1.4.1.534.6.7.1.1.4.3.5.2 | ScalarscSensor1Alarm1State | read-write | mandatory | Setup the signal type to trigger alarm. |
| 1.3.6.1.4.1.534.6.7.1.1.4.3.5.3 | ScalarscSensor1Alarm1Hysteresis | read-write | mandatory | The set value to delay the alarm triggered when event occurs. |
| 1.3.6.1.4.1.534.6.7.1.1.4.3.6 | NodescSensor1Alarm2 | |||
| 1.3.6.1.4.1.534.6.7.1.1.4.3.6.1 | ScalarscSensor1Alarm2Name | read-write | mandatory | The name of alarm-1. |
| 1.3.6.1.4.1.534.6.7.1.1.4.3.6.2 | ScalarscSensor1Alarm2State | read-write | mandatory | Setup the signal type to trigger alarm. |
| 1.3.6.1.4.1.534.6.7.1.1.4.3.6.3 | ScalarscSensor1Alarm2Hysteresis | read-write | mandatory | The set value to delay the alarm triggered when event occurs. |
| 1.3.6.1.4.1.534.6.7.1.1.4.4 | NodescSensor2 | |||
| 1.3.6.1.4.1.534.6.7.1.1.4.4.1 | ScalarscSensor2DeviceName | read-write | mandatory | The name of sensor device. |
| 1.3.6.1.4.1.534.6.7.1.1.4.4.2 | ScalarscSensor2DeviceState | read-write | mandatory | The setup of sensor device type. |
| 1.3.6.1.4.1.534.6.7.1.1.4.4.3 | NodescSensor2Temperature | |||
| 1.3.6.1.4.1.534.6.7.1.1.4.4.3.1 | ScalarscSensor2TemperatureName | read-write | mandatory | The temperature sensor name. |
| 1.3.6.1.4.1.534.6.7.1.1.4.4.3.2 | ScalarscSensor2TemperatureLowWarning | read-write | mandatory | The set point to trigger low warning alarm. |
| 1.3.6.1.4.1.534.6.7.1.1.4.4.3.3 | ScalarscSensor2TemperatureLowCritical | read-write | mandatory | The threshold to trigger low critical alarm. |
| 1.3.6.1.4.1.534.6.7.1.1.4.4.3.4 | ScalarscSensor2TemperatureHighWarning | read-write | mandatory | The threshold to trigger high warning alarm. |
| 1.3.6.1.4.1.534.6.7.1.1.4.4.3.5 | ScalarscSensor2TemperatureHighCritical | read-write | mandatory | The threshold to trigger high critical alarm. |
| 1.3.6.1.4.1.534.6.7.1.1.4.4.3.6 | ScalarscSensor2TemperatureHysteresis | read-write | mandatory | The set value to prevent too many alarms when temperature is hovering around the set threshold. |
| 1.3.6.1.4.1.534.6.7.1.1.4.4.3.7 | ScalarscSensor2TemperatureCalibration | read-write | mandatory | The set value to get the correct temperature according to your reference temperature. |
| 1.3.6.1.4.1.534.6.7.1.1.4.4.3.8 | ScalarscSensor2TemperatureLowWarningStatus | read-write | mandatory | Enable/Disable the set point to trigger low warning alarm. |
| 1.3.6.1.4.1.534.6.7.1.1.4.4.3.9 | ScalarscSensor2TemperatureLowCriticalStatus | read-write | mandatory | Enable/Disable the set point to trigger low critical alarm. |
| 1.3.6.1.4.1.534.6.7.1.1.4.4.3.10 | ScalarscSensor2TemperatureHighWarningStatus | read-write | mandatory | Enable/Disable the set point to trigger high warning alarm. |
| 1.3.6.1.4.1.534.6.7.1.1.4.4.3.11 | ScalarscSensor2TemperatureHighCriticalStatus | read-write | mandatory | Enable/Disable the set point to trigger high critical alarm. |
| 1.3.6.1.4.1.534.6.7.1.1.4.4.4 | NodescSensor2Humidity | |||
| 1.3.6.1.4.1.534.6.7.1.1.4.4.4.1 | ScalarscSensor2HumdityName | read-write | mandatory | The humidity sensor name. |
| 1.3.6.1.4.1.534.6.7.1.1.4.4.4.2 | ScalarscSensor2HumidityLowWarning | read-write | mandatory | The set point to trigger low warning alarm. |
| 1.3.6.1.4.1.534.6.7.1.1.4.4.4.3 | ScalarscSensor2HumidityLowCritical | read-write | mandatory | The threshold to trigger low critical alarm. |
| 1.3.6.1.4.1.534.6.7.1.1.4.4.4.4 | ScalarscSensor2HumidityHighWarning | read-write | mandatory | The threshold to trigger high warning alarm. |
| 1.3.6.1.4.1.534.6.7.1.1.4.4.4.5 | ScalarscSensor2HumidityHighCritical | read-write | mandatory | The threshold to trigger high critical alarm. |
| 1.3.6.1.4.1.534.6.7.1.1.4.4.4.6 | ScalarscSensor2HumidityHysteresis | read-write | mandatory | The set value to prevent too many alarms when Humidity is hovering around the set threshold. |
| 1.3.6.1.4.1.534.6.7.1.1.4.4.4.7 | ScalarscSensor2HumidityCalibration | read-write | mandatory | The set value to get the correct temperature according to the reference temperature. |
| 1.3.6.1.4.1.534.6.7.1.1.4.4.4.8 | ScalarscSensor2HumidityLowWarningStatus | read-write | mandatory | Enable/Disable the set point to trigger low warning alarm. |
| 1.3.6.1.4.1.534.6.7.1.1.4.4.4.9 | ScalarscSensor2HumidityLowCriticalStatus | read-write | mandatory | Enable/Disable the set point to trigger low critical alarm. |
| 1.3.6.1.4.1.534.6.7.1.1.4.4.4.10 | ScalarscSensor2HumidityHighWarningStatus | read-write | mandatory | Enable/Disable the set point to trigger high warning alarm. |
| 1.3.6.1.4.1.534.6.7.1.1.4.4.4.11 | ScalarscSensor2HumidityHighCriticalStatus | read-write | mandatory | Enable/Disable the set point to trigger high critical alarm. |
| 1.3.6.1.4.1.534.6.7.1.1.4.4.5 | NodescSensor2Alarm1 | |||
| 1.3.6.1.4.1.534.6.7.1.1.4.4.5.1 | ScalarscSensor2Alarm1Name | read-write | mandatory | The name of alarm-1. |
| 1.3.6.1.4.1.534.6.7.1.1.4.4.5.2 | ScalarscSensor2Alarm1State | read-write | mandatory | Setup the signal type to trigger alarm. |
| 1.3.6.1.4.1.534.6.7.1.1.4.4.5.3 | ScalarscSensor2Alarm1Hysteresis | read-write | mandatory | The set value to delay the alarm triggered when event occurs. |
| 1.3.6.1.4.1.534.6.7.1.1.4.4.6 | NodescSensor2Alarm2 | |||
| 1.3.6.1.4.1.534.6.7.1.1.4.4.6.1 | ScalarscSensor2Alarm2Name | read-write | mandatory | The name of alarm-1. |
| 1.3.6.1.4.1.534.6.7.1.1.4.4.6.2 | ScalarscSensor2Alarm2State | read-write | mandatory | Setup the signal type to trigger alarm. |
| 1.3.6.1.4.1.534.6.7.1.1.4.4.6.3 | ScalarscSensor2Alarm2Hysteresis | read-write | mandatory | The set value to delay the alarm triggered when event occurs. |
| 1.3.6.1.4.1.534.6.7.1.2 | NodermTraps | |||
| 1.3.6.1.4.1.534.6.7.1.2.1 | NodermCommunicationRestored | INFORMATION: Communication between RackMonitor and sensor had established. | ||
| 1.3.6.1.4.1.534.6.7.1.2.2 | NodermCommunicationLost | WARNING: Communication between RackMonitor and sensor had lost. | ||
| 1.3.6.1.4.1.534.6.7.1.2.3 | NodermAlarm1Inactive | INFORMATION: Alarm1 of sensor had return from active state. | ||
| 1.3.6.1.4.1.534.6.7.1.2.4 | NodermAlarm1Active | WARNING: Alarm1 has become active. | ||
| 1.3.6.1.4.1.534.6.7.1.2.5 | NodermAlarm2Inactive | INFORMATION: Alarm2 of sensor has returned to normal state. | ||
| 1.3.6.1.4.1.534.6.7.1.2.6 | NodermAlarm2Active | WARNING: Alarm2 had became active. | ||
| 1.3.6.1.4.1.534.6.7.1.2.7 | NodermTemperatureNotHighWarning | INFORMATION: The temperature of sensor had return from High warning to normal. | ||
| 1.3.6.1.4.1.534.6.7.1.2.8 | NodermTemperatureHighWarning | WARNING: The temperature of sensor was higher than High warning set point. | ||
| 1.3.6.1.4.1.534.6.7.1.2.9 | NodermTemperatureNotLowWarning | INFORMATION: The temperature of sensor had return from low warning to normal. | ||
| 1.3.6.1.4.1.534.6.7.1.2.10 | NodermTemperatureLowWarning | WARNING: The temperature of sensor was lower than low warning set point. | ||
| 1.3.6.1.4.1.534.6.7.1.2.11 | NodermTemperatureNotHighCritical | INFORMATION: The temperature of sensor lower than high critical set point. | ||
| 1.3.6.1.4.1.534.6.7.1.2.12 | NodermTemperatureHighCritical | CRITICAL: The temperature of sensor was higher than high critical set point. | ||
| 1.3.6.1.4.1.534.6.7.1.2.13 | NodermTemperatureNotLowCritical | INFORMATION: The temperature of sensor was higher than low critical set point. | ||
| 1.3.6.1.4.1.534.6.7.1.2.14 | NodermTemperatureLowCritical | CRITICAL: The temperature of sensor was lower than low critical set point. | ||
| 1.3.6.1.4.1.534.6.7.1.2.15 | NodermHumidityNotHighWarning | INFORMATION: The humidity of sensor had return from High warning to normal. | ||
| 1.3.6.1.4.1.534.6.7.1.2.16 | NodermHumidityHighWarning | WARNING: The humidity of sensor was higher than High warning set point. | ||
| 1.3.6.1.4.1.534.6.7.1.2.17 | NodermHumidityNotLowWarning | INFORMATION: The humidity of sensor had return from low warning to normal. | ||
| 1.3.6.1.4.1.534.6.7.1.2.18 | NodermHumidityLowWarning | WARNING: The humidity of sensor was lower than low warning set point. | ||
| 1.3.6.1.4.1.534.6.7.1.2.19 | NodermHumidityNotHighCritical | INFORMATION: The humidity of sensor lower than high critical set point. | ||
| 1.3.6.1.4.1.534.6.7.1.2.20 | NodermHumidityHighCritical | CRITICAL: The humidity of sensor was higher than high critical set point. | ||
| 1.3.6.1.4.1.534.6.7.1.2.21 | NodermHumidityNotLowCritical | INFORMATION: The humidity of sensor was higher than low critical set point. | ||
| 1.3.6.1.4.1.534.6.7.1.2.22 | NodermHumidityLowCritical | CRITICAL: The humidity of sensor was lower than low critical set point. |