MIB Viewer

SCHLEIFENBAUER-DATABUS-MIB

238 objects
This MIB describes the SNMP functions of network enabled databus devices. Copyright (c) 2021 by Schleifenbauer Holding BV
Imported Objects
SCHLEIFENBAUER-SMIschleifenbauerMgmt
SNMPv2-CONFMODULE-COMPLIANCE NOTIFICATION-GROUP OBJECT-GROUP
SNMPv2-SMIInteger32 MODULE-IDENTITY NOTIFICATION-TYPE OBJECT-TYPE Unsigned32
SNMPv2-TCDisplayString TEXTUAL-CONVENTION
OIDNameAccessStatusDescription
1.3.6.1.4.1.31034.12.1IdentityschleifenbauerDatabusMIBThis MIB describes the SNMP functions of network enabled databus devices. Copyright (c) 2021 by Schleifenbauer Holding BV
1.3.6.1.4.1.31034.12.1.0NodesdbMIBNotifications
1.3.6.1.4.1.31034.12.1.0.1NotificationsdbDevSsDeviceStatusCodeChangedcurrentDevice status code changed. OBJECTS { sdbDevSsDeviceStatusCode }
1.3.6.1.4.1.31034.12.1.0.2NotificationsdbDevSsTemperatureAlertDetectedcurrentTemperature alert detected. Internal temperature alert: OBJECTS { sdbDevSsTemperatureAlert, sdbDevMsIntTemperature, sdbDevMsIntTemperaturePeak } External analo…
1.3.6.1.4.1.31034.12.1.0.3NotificationsdbDevSsInputCurrentAlertDetectedcurrentInput current alert detected. OBJECTS { sdbDevSsInputCurrentAlert, sdbDevInActualCurrent }
1.3.6.1.4.1.31034.12.1.0.4NotificationsdbDevSsOutletCurrentAlertDetectedcurrentOutlet current alert detected. OBJECTS { sdbDevSsOutletCurrentAlert, sdbDevOutMtActualCurrent }
1.3.6.1.4.1.31034.12.1.0.5NotificationsdbDevSsInputVoltageAlertDetectedcurrentInput voltage alert detected. OBJECTS { sdbDevSsInputVoltageAlert, sdbDevInActualVoltage }
1.3.6.1.4.1.31034.12.1.0.6NotificationsdbDevSsOutletCurrentDropAlertDetectedcurrentOutlet current drop alert detected. OBJECTS { sdbDevSsOutletCurrentDropAlert, sdbDevOutMtActualCurrent }
1.3.6.1.4.1.31034.12.1.0.7NotificationsdbDevSsInputCurrentDropAlertDetectedcurrentInput current drop alert detected. OBJECTS { sdbDevSsInputCurrentDropAlert, sdbDevInActualCurrent }
1.3.6.1.4.1.31034.12.1.0.8NotificationsdbDevSsSensorChangeAlertDetectedcurrentSensor channel change alert detected. OBJECTS { sdbDevSsSensorChangeAlert }
1.3.6.1.4.1.31034.12.1.0.9NotificationsdbMgmtStsRingStateChangedcurrentRing state changed. Ring state changded to open: OBJECTS { sdbMgmtStsRingState, sdbMgmtStsRingBreachIndex } Ring state changded to closed: OBJECTS { sdbMgmtSts…
1.3.6.1.4.1.31034.12.1.0.10NotificationsdbDevSsOutletVoltageDropAlertDetectedcurrentOutlet voltage drop alert detected. OBJECTS { sdbDevSsOutletVoltageDropAlert, sdbDevOutMtActualVoltage }
1.3.6.1.4.1.31034.12.1.0.11NotificationsdbDevSsBranchCurrentAlertDetectedcurrentBranch current alert detected. OBJECTS { sdbDevSsBranchCurrentAlert, sdbDevBranchActualCurrent }
1.3.6.1.4.1.31034.12.1.0.12NotificationsdbDevSsBranchVoltageAlertDetectedcurrentBranch current alert detected. OBJECTS { sdbDevSsBranchVoltageAlert, sdbDevBranchActualVoltage }
1.3.6.1.4.1.31034.12.1.0.13NotificationsdbDevSsNeutralCurrentAlertDetectedcurrentInput current alert detected. OBJECTS { sdbDevSsNeutralCurrentAlert, sdbDevTotalsNeutralCurrent }
1.3.6.1.4.1.31034.12.1.0.14NotificationsdbDevSsResidualCurrentAlertDetectedcurrentResidual current alert detected. OBJECTS { sdbDevSsResidualCurrentAlert, sdbDevMsResidualCurrent, sdbDevMsResidualPeak }
1.3.6.1.4.1.31034.12.1.0.15NotificationsdbDevSsHardwareAlertDetectedcurrentHardware alert detected. OBJECTS { sdbDevSsHardwareAlert }
1.3.6.1.4.1.31034.12.1.1NodesdbMIBObjects
1.3.6.1.4.1.31034.12.1.1.1NodesdbMgmt
1.3.6.1.4.1.31034.12.1.1.1.1NodesdbMgmtStatus
1.3.6.1.4.1.31034.12.1.1.1.1.1ScalarsdbMgmtStsDevicesread-onlycurrentThe number of devices on the databus.
1.3.6.1.4.1.31034.12.1.1.1.1.2ScalarsdbMgmtStsAddressableDevicesread-onlycurrentThe number of devices on the databus addressable by snmp.
1.3.6.1.4.1.31034.12.1.1.1.1.3ScalarsdbMgmtStsNewDevicesread-onlycurrentThe number of new devices on the databus.
1.3.6.1.4.1.31034.12.1.1.1.1.4ScalarsdbMgmtStsDuplicateDevicesread-onlycurrentThe number of duplicate devices on the databus.
1.3.6.1.4.1.31034.12.1.1.1.1.5ScalarsdbMgmtStsRingStateread-onlycurrentIf the device is in a bridge-like mode, this will indicate the actual state of the databus.
1.3.6.1.4.1.31034.12.1.1.1.1.6ScalarsdbMgmtStsRingBreachIndexread-onlycurrentIndicates the breach index if the current state of the data bus is open. If the data bus is closed this has no meaning.
1.3.6.1.4.1.31034.12.1.1.1.2NodesdbMgmtControl
1.3.6.1.4.1.31034.12.1.1.1.2.1ScalarsdbMgmtCtrlScanread-writecurrentPerform a bus scan. To verify if scanning is completed the value of this object can be read. During the bus scan the value remains 1. When the bus scan complet…
1.3.6.1.4.1.31034.12.1.1.1.2.2ScalarsdbMgmtCtrlRenumberAllFromNread-writecurrentRenumber all devices on the databus. If set to 0 all units will be set to 0. If set to another value, all units will be numbered in sequence starting from the …
1.3.6.1.4.1.31034.12.1.1.1.2.3ScalarsdbMgmtCtrlRenumberZerosread-writecurrentRenumber all devices on the databus having address 0. Renumbering will be done in sequence. The sequence starts with the highest address found on the databus.
1.3.6.1.4.1.31034.12.1.1.1.2.4TablesdbMgmtCtrlDevicesTablenot-accessiblecurrentA table containing information of devices connected to the databus. The number of entries is given by the value of sdbMgmtStsDevices.
1.3.6.1.4.1.31034.12.1.1.1.2.4.1RowsdbMgmtCtrlDevicesEntrynot-accessiblecurrentInformation entry containing objects of a particular databus device.
1.3.6.1.4.1.31034.12.1.1.1.2.4.1.1ColumnsdbMgmtCtrlDevIndexnot-accessiblecurrentA unique value for each device. Its value ranges between 1 and the value of sdbMgmtStsDevices with a maximum of 255. The value for each device will remain cons…
1.3.6.1.4.1.31034.12.1.1.1.2.4.1.2ColumnsdbMgmtCtrlDevUnitAddressread-writecurrentUser defined address. This will be used for addressing the device on the databus.
1.3.6.1.4.1.31034.12.1.1.1.2.4.1.3ColumnsdbMgmtCtrlDevHardwareAddressread-onlycurrentHardware serial number. This cannot be changed. It can be used as backup unit address. format as 3 unsigned ints separated by dashes: int - int - int
1.3.6.1.4.1.31034.12.1.1.1.2.4.1.4ColumnsdbMgmtCtrlDevIsNewread-onlycurrentIndication if the device is new on the databus.
1.3.6.1.4.1.31034.12.1.1.1.2.4.1.5ColumnsdbMgmtCtrlDevIsDuplicateread-onlycurrentIndication if the device is conflicting with another device on the databus.
1.3.6.1.4.1.31034.12.1.1.2NodesdbDevice
1.3.6.1.4.1.31034.12.1.1.2.1NodesdbDevIdentification
1.3.6.1.4.1.31034.12.1.1.2.1.1TablesdbDevIdTablenot-accessiblecurrentA table containing identification information of devices connected to the databus. The number of entries is given by the value of sdbMgmtStsAddressableDevices.
1.3.6.1.4.1.31034.12.1.1.2.1.1.1RowsdbDevIdEntrynot-accessiblecurrentInformation entry containing information objects of a particular databus device.
1.3.6.1.4.1.31034.12.1.1.2.1.1.1.1ColumnsdbDevIdSPDMVersionread-onlycurrentData model version.
1.3.6.1.4.1.31034.12.1.1.2.1.1.1.2ColumnsdbDevIdFirmwareVersionread-onlycurrentThe firmware revision number.
1.3.6.1.4.1.31034.12.1.1.2.1.1.1.3ColumnsdbDevIdBuildNumberread-onlycurrentDate and time the firmware was built.
1.3.6.1.4.1.31034.12.1.1.2.1.1.1.4ColumnsdbDevIdSalesOrderNumberread-onlycurrentSP sales order number.
1.3.6.1.4.1.31034.12.1.1.2.1.1.1.5ColumnsdbDevIdProductIdread-onlycurrentSP product id.
1.3.6.1.4.1.31034.12.1.1.2.1.1.1.6ColumnsdbDevIdSerialNumberread-onlycurrentSP serial number.
1.3.6.1.4.1.31034.12.1.1.2.1.1.1.7ColumnsdbDevIdHardwareAddressread-onlycurrentHardware serial number. This can not be changed. It can be used as backup unit address. Format as 3 unsigned ints separated by dashes (-) e.g. 12345-54321-00000
1.3.6.1.4.1.31034.12.1.1.2.1.1.1.8ColumnsdbDevIdMacAddressread-onlycurrentThe MAC address. This can not be changed. It represents an 802 MAC address as if it were transmitted least significant bit first. Format as six groups of 2 hex…
1.3.6.1.4.1.31034.12.1.1.2.1.1.1.9ColumnsdbDevIdUnitAddressread-writecurrentUser defined address. This will be used for addressing the device on the databus.
1.3.6.1.4.1.31034.12.1.1.2.1.1.1.10ColumnsdbDevIdNameread-writecurrentUser configurable device name or identifier.
1.3.6.1.4.1.31034.12.1.1.2.1.1.1.11ColumnsdbDevIdLocationread-writecurrentUser configurable device location identifier.
1.3.6.1.4.1.31034.12.1.1.2.1.1.1.12ColumnsdbDevIdVanityTagread-writecurrentCharacters to be displayed as vanity text in display.
1.3.6.1.4.1.31034.12.1.1.2.1.1.1.13ColumnsdbDevIdIndexnot-accessiblecurrentA unique value for each device. Its value represents the unit address of the device and is used to address individual devices in the tree. The value for each d…
1.3.6.1.4.1.31034.12.1.1.2.1.1.1.14ColumnsdbDevIdDeviceTyperead-onlycurrentA unique value for each device group. Its value represents the device type of the device. Refer to manual for more information.
1.3.6.1.4.1.31034.12.1.1.2.1.1.1.15ColumnsdbDevIdLocateUnitread-writecurrentThe LCD-backlight flashes in a heartbeat rhythm to locate the unit.
1.3.6.1.4.1.31034.12.1.1.2.1.1.1.16ColumnsdbDevIdConfigTyperead-onlycurrentWiring configuration type used.
1.3.6.1.4.1.31034.12.1.1.2.2NodesdbDevConfiguration
1.3.6.1.4.1.31034.12.1.1.2.2.1TablesdbDevCfTablenot-accessiblecurrentA table containing configuration information of devices connected to the databus. The number of entries is given by the value of sdbMgmtStsAddressableDevices.
1.3.6.1.4.1.31034.12.1.1.2.2.1.1RowsdbDevCfEntrynot-accessiblecurrentConfiguration entry containing configuration objects of a particular databus device.
1.3.6.1.4.1.31034.12.1.1.2.2.1.1.1ColumnsdbDevCfPhasesread-onlycurrentNumber of phases for input metering.
1.3.6.1.4.1.31034.12.1.1.2.2.1.1.2ColumnsdbDevCfOutletsTotalread-onlycurrentTotal number of outlets including hardwired without switch/metered modules.
1.3.6.1.4.1.31034.12.1.1.2.2.1.1.3ColumnsdbDevCfOutletsSwitchedread-onlycurrentNumber of switched outlets. If outlet numbering is non-contiguous its the highest outlet number.
1.3.6.1.4.1.31034.12.1.1.2.2.1.1.4ColumnsdbDevCfOutletsMeteredread-onlycurrentNumber of metered outlets. If outlet numbering is non-contiguous its the highest outlet number.
1.3.6.1.4.1.31034.12.1.1.2.2.1.1.5ColumnsdbDevCfSensorsread-onlycurrentThe number sensors.
1.3.6.1.4.1.31034.12.1.1.2.2.1.1.6ColumnsdbDevCfMaximumLoadread-onlycurrentMaximum rated load of device per phase
1.3.6.1.4.1.31034.12.1.1.2.2.1.1.7ColumnsdbDevCfBranchesread-onlycurrentNumber of branches for input metering.
1.3.6.1.4.1.31034.12.1.1.2.2.1.1.8ColumnsdbDevCfNeutralread-onlycurrentNuetral current measurement.
1.3.6.1.4.1.31034.12.1.1.2.2.1.1.9ColumnsdbDevCfTempSensorsread-onlycurrentNumber of temperature sensors present in the system.
1.3.6.1.4.1.31034.12.1.1.2.2.1.1.10ColumnsdbDevCfTotalsread-onlycurrentThe number of totals rows for the configuration.
1.3.6.1.4.1.31034.12.1.1.2.3NodesdbDevSystemStatus
1.3.6.1.4.1.31034.12.1.1.2.3.1TablesdbDevSsTablenot-accessiblecurrentA table containing system status information of devices connected to the databus. The number of entries is given by the value of sdbMgmtStsAddressableDevices.
1.3.6.1.4.1.31034.12.1.1.2.3.1.1RowsdbDevSsEntrynot-accessiblecurrentSystem status entry containing system status objects of a particular databus device.
1.3.6.1.4.1.31034.12.1.1.2.3.1.1.1ColumnsdbDevSsDeviceStatusCoderead-onlycurrentReturns an internal status or error code. A value of 0 means OK. If not 0 it can be any of the following codes. Multiple status codes can be active at the same…
1.3.6.1.4.1.31034.12.1.1.2.3.1.1.2ColumnsdbDevSsTemperatureAlertread-onlycurrentAn alert has been raised due to temperature exceeding treshhold. 0 = no alert 1 = internal temperature sensor 2 = external temperature sensor
1.3.6.1.4.1.31034.12.1.1.2.3.1.1.3ColumnsdbDevSsInputCurrentAlertread-onlycurrentAn alert has been raised due to current exceeding treshhold. The value indicates the exceeding phase. 0 = no alert.
1.3.6.1.4.1.31034.12.1.1.2.3.1.1.4ColumnsdbDevSsOutletCurrentAlertread-onlycurrentAn alert has been raised due to current exceeding treshhold. The value indicates the exceeding outlet. 0 = no alert.
1.3.6.1.4.1.31034.12.1.1.2.3.1.1.5ColumnsdbDevSsInputVoltageAlertread-onlycurrentAn alert has been raised due to a voltage dip. The value indicates the dipped phase. 0 = no alert.
1.3.6.1.4.1.31034.12.1.1.2.3.1.1.6ColumnsdbDevSsOutletCurrentDropAlertread-onlycurrentAn alert has been raised due to the current of a metered outlet suddenly dropping to near zero, possibly indicating a blown fuse. The value indicates the dropp…
1.3.6.1.4.1.31034.12.1.1.2.3.1.1.7ColumnsdbDevSsInputCurrentDropAlertread-onlycurrentAn alert has been raised due to the current of a metered input suddenly dropping to near zero, possibly indicating a blown fuse. The value indicates the droppe…
1.3.6.1.4.1.31034.12.1.1.2.3.1.1.8ColumnsdbDevSsSensorChangeAlertread-onlycurrentAn alert has been raised due to a change in the number of sensors. The value indicates the previous amount of sensors.
1.3.6.1.4.1.31034.12.1.1.2.3.1.1.9ColumnsdbDevSsOutletVoltageDropAlertread-onlycurrentAn alert has been raised due to voltage drop on this outlet. The value indicates the first failed outlet.
1.3.6.1.4.1.31034.12.1.1.2.3.1.1.10ColumnsdbDevSsBranchCurrentAlertread-onlycurrentAn alert has been raised due to current exceeding treshhold. The value indicates the exceeding branch. 0 = no alert.
1.3.6.1.4.1.31034.12.1.1.2.3.1.1.11ColumnsdbDevSsBranchVoltageAlertread-onlycurrentAn alert has been raised due to a voltage dip. The value indicates the dipped branch. 0 = no alert.
1.3.6.1.4.1.31034.12.1.1.2.3.1.1.12ColumnsdbDevSsNeutralCurrentAlertread-onlycurrentAn alert has been raised due to current exceeding treshhold. 0 = no alert 1 = current alert
1.3.6.1.4.1.31034.12.1.1.2.3.1.1.13ColumnsdbDevSsResidualCurrentAlertread-onlycurrentA residual current alert has been raised. 0 = no alert 1 = current exceeding treshhold alert 2 = sensor error
1.3.6.1.4.1.31034.12.1.1.2.3.1.1.14ColumnsdbDevSsHardwareAlertread-onlycurrent0 = no alarm >0 = or slave number for alert
1.3.6.1.4.1.31034.12.1.1.2.4NodesdbDevReset
1.3.6.1.4.1.31034.12.1.1.2.4.1TablesdbDevRsTablenot-accessiblecurrentA table providing reset capabilities to devices connected to the databus. The number of entries is given by the value of sdbMgmtStsAddressableDevices.
1.3.6.1.4.1.31034.12.1.1.2.4.1.1RowsdbDevRsEntrynot-accessiblecurrentReset entry providing reset objects of a particular databus device.
1.3.6.1.4.1.31034.12.1.1.2.4.1.1.1ColumnsdbDevRsRebootread-writecurrentWarm reboot/reset of device controller. NOTE: this will have NO effect on outlet status!
1.3.6.1.4.1.31034.12.1.1.2.4.1.1.2ColumnsdbDevRsResetAlertsread-writecurrentReset all alert signals and device status code.
1.3.6.1.4.1.31034.12.1.1.2.4.1.1.3ColumnsdbDevRsZeroInputKWhSubtotalread-writecurrentReset of all input kWh subtotal counters to zero.
1.3.6.1.4.1.31034.12.1.1.2.4.1.1.4ColumnsdbDevRsZeroOutletKWhSubtotalread-writecurrentReset of all outlet kWh subtotal counter to zero.
1.3.6.1.4.1.31034.12.1.1.2.4.1.1.5ColumnsdbDevRsResetPeaksAndDipsread-writecurrentReset all peak and dip values to zero.
1.3.6.1.4.1.31034.12.1.1.2.5NodesdbDevSettings
1.3.6.1.4.1.31034.12.1.1.2.5.1TablesdbDevStTablenot-accessiblecurrentA table containing setting information of devices connected to the databus. The number of entries is given by the value of sdbMgmtStsAddressableDevices.
1.3.6.1.4.1.31034.12.1.1.2.5.1.1RowsdbDevStEntrynot-accessiblecurrentSetting entry containing settings objects of a particular databus device.
1.3.6.1.4.1.31034.12.1.1.2.5.1.1.2ColumnsdbDevStAutoResetAlertsread-writecurrentAuto reset alerts configuration. If set to 0 the auto reset alerts feature is disabled. If set to a value greater then 0, the auto reset alerts feature is enab…
1.3.6.1.4.1.31034.12.1.1.2.5.1.1.3ColumnsdbDevStExtendedNamesread-writecurrentUse original or longer names for inputs, outlets and sensors.
1.3.6.1.4.1.31034.12.1.1.2.5.1.1.4ColumnsdbDevStPeakDurationread-writecurrentAmount of ms a current peak should last before an alert is raised.
1.3.6.1.4.1.31034.12.1.1.2.5.1.1.5ColumnsdbDevStFixedOutletDelayread-writecurrentMinimal delay between two successive relay switches in milliseconds. Minimal delay is 100 ms. Will always be respected!
1.3.6.1.4.1.31034.12.1.1.2.5.1.1.6ColumnsdbDevStPowerSaverModeread-writecurrentSet backlight on time in seconds. 0 keeps display always on. Note that keeping the backlight on may decrease luminosity over time.
1.3.6.1.4.1.31034.12.1.1.2.5.1.1.7ColumnsdbDevStOutletPowerUpModeread-writecurrentBehaviour of outlets on power-up.
1.3.6.1.4.1.31034.12.1.1.2.5.1.1.8ColumnsdbDevStMaximumTemperatureread-writecurrentMaximum temperature threshold An alert will be generated whenever the temperature is above this value. Zero means disabled.
1.3.6.1.4.1.31034.12.1.1.2.5.1.1.9ColumnsdbDevStDisplayOrientationread-writecurrentDisplay orientation.
1.3.6.1.4.1.31034.12.1.1.2.5.1.1.10ColumnsdbDevStLocalAlertResetread-writecurrentAllow alerts to be reset locally on device by pushing one of the buttons.
1.3.6.1.4.1.31034.12.1.1.2.5.1.1.11ColumnsdbDevStCurrentDropDetectionread-writecurrentEnables the current drop detection function.
1.3.6.1.4.1.31034.12.1.1.2.5.1.1.13ColumnsdbDevStUsbModeread-writecurrentAllow the USB port to be used for specific tasks
1.3.6.1.4.1.31034.12.1.1.2.5.1.1.14ColumnsdbDevStSensorChangeAlertModeread-writecurrentEnable sensoe change alerts
1.3.6.1.4.1.31034.12.1.1.2.5.1.1.15ColumnsdbDevStOutletUnlockOverrideread-writecurrentOverrides the timeout. If this is set to 1 then the timeout will be ignored, otherwise the timeout will be taken into account.
1.3.6.1.4.1.31034.12.1.1.2.6NodesdbDevInput
1.3.6.1.4.1.31034.12.1.1.2.6.1TablesdbDevInTablenot-accessiblecurrentA table containing information of inputs of devices connected to the databus.
1.3.6.1.4.1.31034.12.1.1.2.6.1.1RowsdbDevInEntrynot-accessiblecurrentInputs entry containing objects of an input of a particular databus device. Note that this table has two indexes. sdbDevIdIndex to identify a particular device…
1.3.6.1.4.1.31034.12.1.1.2.6.1.1.1ColumnsdbDevInIndexnot-accessiblecurrentA unique value for each input. Its value ranges between 1 and the value of sdbDevCfPhases.
1.3.6.1.4.1.31034.12.1.1.2.6.1.1.2ColumnsdbDevInKWhTotalread-onlycurrentTotal kWh value of an input. This value can not be reset.
1.3.6.1.4.1.31034.12.1.1.2.6.1.1.3ColumnsdbDevInKWhSubtotalread-onlycurrentSubtotal kWh value of an input. This value can be reset.
1.3.6.1.4.1.31034.12.1.1.2.6.1.1.4ColumnsdbDevInPowerFactorread-onlycurrentPower factor of input. The power factor of an AC power system is defined as the ratio of the real or active power to the apparent power and is a number between…
1.3.6.1.4.1.31034.12.1.1.2.6.1.1.5ColumnsdbDevInActualCurrentread-onlycurrentActual apparent, RMS current.
1.3.6.1.4.1.31034.12.1.1.2.6.1.1.6ColumnsdbDevInPeakCurrentread-onlycurrentPeak apparent, RMS current. Highest value since last reset of the alerts.
1.3.6.1.4.1.31034.12.1.1.2.6.1.1.7ColumnsdbDevInActualVoltageread-onlycurrentThe actual voltage.
1.3.6.1.4.1.31034.12.1.1.2.6.1.1.8ColumnsdbDevInMinVoltageread-onlycurrentRMS voltage dip. Lowest value since reset of alerts.
1.3.6.1.4.1.31034.12.1.1.2.6.1.1.9ColumnsdbDevInPowerVoltAmpereread-onlycurrentCalculated apparent power.
1.3.6.1.4.1.31034.12.1.1.2.6.1.1.10ColumnsdbDevInPowerWattread-onlycurrentCalculated real power.
1.3.6.1.4.1.31034.12.1.1.2.6.1.1.11ColumnsdbDevInMaxAmpsread-writecurrentMaximum current per input phase. Should last at least sdbDevStPeakDuration ms before triggering an alert.
1.3.6.1.4.1.31034.12.1.1.2.6.1.1.12ColumnsdbDevInCTRatioread-writecurrentThe multiplier to use for the input CTs.
1.3.6.1.4.1.31034.12.1.1.2.6.1.1.13ColumnsdbDevInNameread-writecurrentUser configurable naming of inputs or phases.
1.3.6.1.4.1.31034.12.1.1.2.6.1.1.14ColumnsdbDevInZeroKWhSubtotalread-writecurrentReset input kWh subtotal counter of a single input to zero.
1.3.6.1.4.1.31034.12.1.1.2.7NodesdbDevOutlet
1.3.6.1.4.1.31034.12.1.1.2.7.1TablesdbDevOutTablenot-accessiblecurrentA table containing information of outlets of devices connected to the databus.
1.3.6.1.4.1.31034.12.1.1.2.7.1.1RowsdbDevOutEntrynot-accessiblecurrentOutlets entry containing objects of an outlet of a particular databus device. Note that this table has two indexes. sdbDevIdIndex to identify a particular devi…
1.3.6.1.4.1.31034.12.1.1.2.7.1.1.1ColumnsdbDevOutIndexnot-accessiblecurrentA unique value for each outlet. Its value ranges between 1 and the value of sdbDevCfOutletsTotal.
1.3.6.1.4.1.31034.12.1.1.2.7.1.1.2ColumnsdbDevOutNameread-writecurrentUser configurable naming of individual outlets.
1.3.6.1.4.1.31034.12.1.1.2.7.2TablesdbDevOutMtTablenot-accessiblecurrentA table containing information of metered outlets of devices connected to the databus.
1.3.6.1.4.1.31034.12.1.1.2.7.2.1RowsdbDevOutMtEntrynot-accessiblecurrentMetered outlets entry containing objects of a metered outlet of a particular databus device. Note that this table has two indexes. sdbDevIdIndex to identify a …
1.3.6.1.4.1.31034.12.1.1.2.7.2.1.1ColumnsdbDevOutMtIndexnot-accessiblecurrentA unique value for each outlet. Its value ranges between 1 and the value of sdbDevCfOutletsMetered.
1.3.6.1.4.1.31034.12.1.1.2.7.2.1.2ColumnsdbDevOutMtKWhTotalread-onlycurrentTotal kWh value of an outlet. This value can not be reset.
1.3.6.1.4.1.31034.12.1.1.2.7.2.1.3ColumnsdbDevOutMtKWhSubtotalread-onlycurrentSubotal kWh value of an outlet. This value can be reset.
1.3.6.1.4.1.31034.12.1.1.2.7.2.1.4ColumnsdbDevOutMtPowerFactorread-onlycurrentPower factor of outlet. The power factor of an AC power system is defined as the ratio of the real or active power to the apparent power and is a number betwee…
1.3.6.1.4.1.31034.12.1.1.2.7.2.1.5ColumnsdbDevOutMtActualCurrentread-onlycurrentActual apparent, RMS current.
1.3.6.1.4.1.31034.12.1.1.2.7.2.1.6ColumnsdbDevOutMtPeakCurrentread-onlycurrentPeak apparent, RMS current. Highest value since last reset of the alerts.
1.3.6.1.4.1.31034.12.1.1.2.7.2.1.7ColumnsdbDevOutMtActualVoltageread-onlycurrentActual voltage on outlet.
1.3.6.1.4.1.31034.12.1.1.2.7.2.1.8ColumnsdbDevOutMtMaxAmpsread-writecurrentMaximum current per outlet. Should last at least sdbDevStPeakDuration ms before triggering an alert.
1.3.6.1.4.1.31034.12.1.1.2.7.2.1.9ColumnsdbDevOutMtCTRatioread-writecurrentThe multiplier to use for the outlet CTs.
1.3.6.1.4.1.31034.12.1.1.2.7.2.1.10ColumnsdbDevOutMtPowerVoltAmpereread-onlycurrentCalculated apparent power.
1.3.6.1.4.1.31034.12.1.1.2.7.2.1.11ColumnsdbDevOutMtPowerWattread-onlycurrentCalculated real power.
1.3.6.1.4.1.31034.12.1.1.2.7.3TablesdbDevOutSwTablenot-accessiblecurrentA table containing information of switched outlets of devices connected to the databus.
1.3.6.1.4.1.31034.12.1.1.2.7.3.1RowsdbDevOutSwEntrynot-accessiblecurrentSwitched outlets entry containing objects of a switched outlet of a particular databus device. Note that this table has two indexes. sdbDevIdIndex to identify …
1.3.6.1.4.1.31034.12.1.1.2.7.3.1.1ColumnsdbDevOutSwIndexnot-accessiblecurrentA unique value for each outlet. Its value ranges between 1 and the value of sdbDevCfOutletsSwitched.
1.3.6.1.4.1.31034.12.1.1.2.7.3.1.2ColumnsdbDevOutSwCurrentStateread-writecurrentThe actual state of the outlet relay. Note that Writing is only effective after setting sdbDevOutSwUnlock.
1.3.6.1.4.1.31034.12.1.1.2.7.3.1.3ColumnsdbDevOutSwScheduledread-onlycurrentA one indicates pending activity; the switch delay has not yet expired.
1.3.6.1.4.1.31034.12.1.1.2.7.3.1.4ColumnsdbDevOutSwUnlockread-writecurrentSwitching and rebooting is unlocked for 10 seconds by writing a 1.
1.3.6.1.4.1.31034.12.1.1.2.7.3.1.5ColumnsdbDevOutSwIndividualOutletDelayread-writecurrentDelay before an individual outlet switches on at power-up.
1.3.6.1.4.1.31034.12.1.1.2.7.3.1.6ColumnsdbDevOutSwRebootread-writecurrentReboot outlet relay if current state is on and outlet is unlocked; The outlet will be turned on after 10 seconds.
1.3.6.1.4.1.31034.12.1.1.2.8NodesdbDevSensor
1.3.6.1.4.1.31034.12.1.1.2.8.1TablesdbDevMeasuresTablenot-accessiblecurrentA table containing information of temperatures of devices connected to the databus.
1.3.6.1.4.1.31034.12.1.1.2.8.1.1RowsdbDevMeasuresEntrynot-accessiblecurrentDevice measures entry containing temperature information objects of a particular databus device.
1.3.6.1.4.1.31034.12.1.1.2.8.1.1.1ColumnsdbDevMsIntTemperatureread-onlycurrentActual internal device temperature in deg C
1.3.6.1.4.1.31034.12.1.1.2.8.1.1.2ColumnsdbDevMsExtTemperatureread-onlycurrentActual external device temperature sensor in deg C.
1.3.6.1.4.1.31034.12.1.1.2.8.1.1.3ColumnsdbDevMsIntTemperaturePeakread-onlycurrentPeak internal device temperature since last reset of alerts.
1.3.6.1.4.1.31034.12.1.1.2.8.1.1.4ColumnsdbDevMsExtTemperaturePeakread-onlycurrentPeak external device temperature since last reset of alerts.
1.3.6.1.4.1.31034.12.1.1.2.8.1.1.5ColumnsdbDevMsResidualCurrentread-onlycurrentResidual current.
1.3.6.1.4.1.31034.12.1.1.2.8.1.1.6ColumnsdbDevMsResidualPeakread-onlycurrentPeak residual current.
1.3.6.1.4.1.31034.12.1.1.2.8.2TablesdbDevSnsTablenot-accessiblecurrentA table containing information of sensors of devices connected to the databus.
1.3.6.1.4.1.31034.12.1.1.2.8.2.1RowsdbDevSnsEntrynot-accessiblecurrentSensors entry containing objects of a sensor of a particular databus device. Note that this table has two indexes. sdbDevIdIndex to identify a particular devic…
1.3.6.1.4.1.31034.12.1.1.2.8.2.1.1ColumnsdbDevSnsIndexnot-accessiblecurrentA unique value for each sensor. Its value ranges between 1 and the value of sdbDevCfSensors.
1.3.6.1.4.1.31034.12.1.1.2.8.2.1.2ColumnsdbDevSnsTyperead-onlycurrentType of connected sensor. T = Temperature (C) H = Humidity (%) I = dry switch contact
1.3.6.1.4.1.31034.12.1.1.2.8.2.1.3ColumnsdbDevSnsValueread-onlycurrentValue of connected sensor
1.3.6.1.4.1.31034.12.1.1.2.8.2.1.4ColumnsdbDevSnsNameread-writecurrentUser definable name for sensors.
1.3.6.1.4.1.31034.12.1.1.2.9NodesdbDevPerformance
1.3.6.1.4.1.31034.12.1.1.2.9.1TablesdbDevPerformanceTablenot-accessiblecurrentA table containing information of sensors of devices connected to the databus.
1.3.6.1.4.1.31034.12.1.1.2.9.1.1RowsdbDevPerformanceEntrynot-accessiblecurrentPerformance counters of a particular databus device. Note that this table has two indexes. sdbDevIdIndex to identify a particular device and sdbDevPerformanceI…
1.3.6.1.4.1.31034.12.1.1.2.9.1.1.1ColumnsdbDevPerformanceIndexnot-accessiblecurrentA unique value for each counter. Its value ranges between 1 and 16.
1.3.6.1.4.1.31034.12.1.1.2.9.1.1.2ColumnsdbDevPerformanceValueread-onlycurrentValue of counter
1.3.6.1.4.1.31034.12.1.1.2.9.1.1.3ColumnsdbDevPerformanceMaxread-onlycurrentMax of counter
1.3.6.1.4.1.31034.12.1.1.2.9.1.1.4ColumnsdbDevPerformanceLimitread-onlycurrentLimit of counter
1.3.6.1.4.1.31034.12.1.1.2.9.1.1.5ColumnsdbDevPerformanceNameread-writecurrentUser definable name for counter.
1.3.6.1.4.1.31034.12.1.1.2.9.2TablesdbDevPerformanceResetTablenot-accessiblecurrentA table containing the last reset reason of the device
1.3.6.1.4.1.31034.12.1.1.2.9.2.1RowsdbDevPerformanceResetEntrynot-accessiblecurrentSetting entry containing settings objects of a particular databus device.
1.3.6.1.4.1.31034.12.1.1.2.9.2.1.1ColumnsdbDevPerformanceResetReasonread-writecurrentLast reset reason.
1.3.6.1.4.1.31034.12.1.1.2.9.2.1.2ColumnsdbDevResetUptimeread-onlycurrentUptime before last reset
1.3.6.1.4.1.31034.12.1.1.2.10NodesdbDevBranches
1.3.6.1.4.1.31034.12.1.1.2.10.1TablesdbDevBranchTablenot-accessiblecurrentA table containing information of inputs of devices connected to the databus.
1.3.6.1.4.1.31034.12.1.1.2.10.1.1RowsdbDevBranchEntrynot-accessiblecurrentInputs entry containing objects of an input of a particular databus device. Note that this table has two indexes. sdbDevIdIndex to identify a particular device…
1.3.6.1.4.1.31034.12.1.1.2.10.1.1.1ColumnsdbDevBranchIndexnot-accessiblecurrentA unique value for each input. Its value ranges between 1 and the value of sdbDevCfPhases.
1.3.6.1.4.1.31034.12.1.1.2.10.1.1.2ColumnsdbDevBranchKWhTotalread-onlycurrentTotal kWh value of an input. This value can not be reset.
1.3.6.1.4.1.31034.12.1.1.2.10.1.1.3ColumnsdbDevBranchKWhSubtotalread-onlycurrentSubtotal kWh value of an input. This value can be reset.
1.3.6.1.4.1.31034.12.1.1.2.10.1.1.4ColumnsdbDevBranchPowerFactorread-onlycurrentPower factor of input. The power factor of an AC power system is defined as the ratio of the real or active power to the apparent power and is a number between…
1.3.6.1.4.1.31034.12.1.1.2.10.1.1.5ColumnsdbDevBranchActualCurrentread-onlycurrentActual apparent, RMS current.
1.3.6.1.4.1.31034.12.1.1.2.10.1.1.6ColumnsdbDevBranchPeakCurrentread-onlycurrentPeak apparent, RMS current. Highest value since last reset of the alerts.
1.3.6.1.4.1.31034.12.1.1.2.10.1.1.7ColumnsdbDevBranchActualVoltageread-onlycurrentThe actual voltage.
1.3.6.1.4.1.31034.12.1.1.2.10.1.1.8ColumnsdbDevBranchMinVoltageread-onlycurrentRMS voltage dip. Lowest value since reset of alerts.
1.3.6.1.4.1.31034.12.1.1.2.10.1.1.9ColumnsdbDevBranchPowerVoltAmpereread-onlycurrentCalculated apparent power.
1.3.6.1.4.1.31034.12.1.1.2.10.1.1.10ColumnsdbDevBranchPowerWattread-onlycurrentCalculated real power.
1.3.6.1.4.1.31034.12.1.1.2.10.1.1.11ColumnsdbDevBranchMaxAmpsread-writecurrentMaximum current per input phase. Should last at least sdbDevStPeakDuration ms before triggering an alert.
1.3.6.1.4.1.31034.12.1.1.2.10.1.1.12ColumnsdbDevBranchCTRatioread-writecurrentThe multiplier to use for the input CTs.
1.3.6.1.4.1.31034.12.1.1.2.10.1.1.13ColumnsdbDevBranchNameread-writecurrentUser configurable naming of branches.
1.3.6.1.4.1.31034.12.1.1.2.10.1.1.14ColumnsdbDevBranchZeroKWhSubtotalread-writecurrentReset input kWh subtotal counter of a single input to zero.
1.3.6.1.4.1.31034.12.1.1.2.11NodesdbDevTotals
1.3.6.1.4.1.31034.12.1.1.2.11.1TablesdbDevTotalsTablenot-accessiblecurrentA table containing information of inputs of devices connected to the databus.
1.3.6.1.4.1.31034.12.1.1.2.11.1.1RowsdbDevTotalsEntrynot-accessiblecurrentInputs entry containing objects of an input of a particular databus device. Note that this table has two indexes. sdbDevIdIndex to identify a particular device…
1.3.6.1.4.1.31034.12.1.1.2.11.1.1.1ColumnsdbDevTotalsIndexnot-accessiblecurrentA unique value for each input. Its value ranges between 1 and the value of sdbDevCfPhases.
1.3.6.1.4.1.31034.12.1.1.2.11.1.1.2ColumnsdbDevTotalsKWhTotalread-onlycurrentTotal kWh value of an input. This value can not be reset.
1.3.6.1.4.1.31034.12.1.1.2.11.1.1.3ColumnsdbDevTotalsPowerFactorread-onlycurrentPower factor of input. The power factor of an AC power system is defined as the ratio of the real or active power to the apparent power and is a number between…
1.3.6.1.4.1.31034.12.1.1.2.11.1.1.4ColumnsdbDevTotalsActualCurrentread-onlycurrentActual apparent, RMS current.
1.3.6.1.4.1.31034.12.1.1.2.11.1.1.5ColumnsdbDevTotalsPeakCurrentread-onlycurrentPeak apparent, RMS current. Highest value since last reset of the alerts.
1.3.6.1.4.1.31034.12.1.1.2.11.1.1.6ColumnsdbDevTotalsPowerVoltAmpereread-onlycurrentCalculated apparent power.
1.3.6.1.4.1.31034.12.1.1.2.11.1.1.7ColumnsdbDevTotalsPowerWattread-onlycurrentCalculated real power.
1.3.6.1.4.1.31034.12.1.1.2.11.1.1.8ColumnsdbDevTotalsNeutralCurrentread-onlycurrentNeutral current of phases.
1.3.6.1.4.1.31034.12.1.1.2.11.1.1.9ColumnsdbDevTotalsNeutralPeakread-onlycurrentPeak neutral current of phases.
1.3.6.1.4.1.31034.12.1.1.2.11.1.1.10ColumnsdbDevTotalsNeutralMaxAmpsread-writecurrentMaximum neutral current. Should last at least sdbDevStPeakDuration ms before triggering an alert.
1.3.6.1.4.1.31034.12.1.1.2.11.1.1.11ColumnsdbDevTotalsResidualMaxAmpsread-writecurrentMaximum residual current. Should last at least sdbDevStPeakDuration ms before triggering an alert.
1.3.6.1.4.1.31034.12.1.2NodesdbMIBConformance
1.3.6.1.4.1.31034.12.1.2.1NodesdbMIBCompliances
1.3.6.1.4.1.31034.12.1.2.1.1CompliancesdbMIBCompliancecurrentThe requirements for conformance to the SCHLEIFENBAUER-DATABUS-MIB.
1.3.6.1.4.1.31034.12.1.2.2NodesdbMIBGroups
1.3.6.1.4.1.31034.12.1.2.2.1GroupsdbMIBNotificationGroupcurrentA collection of notifications.
1.3.6.1.4.1.31034.12.1.2.2.3GroupsdbMIBDevIdGroupcurrentA collection of objects providing identification information about the device.
1.3.6.1.4.1.31034.12.1.2.2.4GroupsdbMIBDevCfGroupcurrentA collection of objects providing configuration information about the device.
1.3.6.1.4.1.31034.12.1.2.2.5GroupsdbMIBDevSsGroupcurrentA collection of objects providing status information about the device.
1.3.6.1.4.1.31034.12.1.2.2.6GroupsdbMIBDevRsGroupcurrentGroups resettable attributes op the device.
1.3.6.1.4.1.31034.12.1.2.2.7GroupsdbMIBDevStGroupcurrentA collection of objects providing the actual settings about the device.
1.3.6.1.4.1.31034.12.1.2.2.8GroupsdbMIBDevInGroupcurrentA collection of objects providing the actual input measurements of the device.
1.3.6.1.4.1.31034.12.1.2.2.9GroupsdbMIBDevOutGroupcurrentA collection of objects providing the actual outlet measurements of the device.
1.3.6.1.4.1.31034.12.1.2.2.10GroupsdbMIBDevOutMtGroupcurrentA collection of objects providing the actual outlet measurements of the device.
1.3.6.1.4.1.31034.12.1.2.2.11GroupsdbMIBDevOutSwGroupcurrentA collection of objects providing the actual outlet measurements of the device.
1.3.6.1.4.1.31034.12.1.2.2.12GroupsdbMIBDevSensorGroupcurrentA collection of objects providing the actual environmental measurements of the device.
1.3.6.1.4.1.31034.12.1.2.2.13GroupsdbMIBMgmtStatusGroupcurrentA collection of objects providing management status information about the databus.
1.3.6.1.4.1.31034.12.1.2.2.14GroupsdbMIBMgmtControlGroupcurrentA collection of objects providing management control information about the databus.
1.3.6.1.4.1.31034.12.1.2.2.15GroupsdbMIBDevPerformanceGroupcurrentA collection of objects providing performance information about the MCU
Type Definitions
NameSyntaxStatusDescription
CentiAmpereInteger32 (0..327680)currentData type for reporting measurements and thresholds associated with current sensors. If the underlying hardware sensor indicates 1.1 A, then the SNMP agent will report a value of 110 CentiAmpere.
CentiCelsiusInteger32 (0..9900)currentData type for reporting sensor readings associated with temperature sensors. If the underlying hardware sensor indicates 20.1 degrees Celsius, then the SNMP agent will report a value of 2010 CentiCelsius.
CentiPercentInteger32 (0..10000)currentData type for reporting calculated percentages. If the calculated percentage is 98.3%, then the SNMP agent will report a value of 9830 CentiPercent.
CentiValueInteger32 (0..327680)currentData type for reporting generic measurements associated with environmental sensors. If the underlying hardware sensor indicates 21.1 degrees Celsius, then the SNMP agent will report a value of 2110 CentiValue.
CentiVoltInteger32 (0..327680)currentData type for reporting measurements and thresholds associated with voltage sensors. If the underlying hardware sensor indicates 231.1 V, then the SNMP agent will report a value of 23110 CentiVolt.
KiloWattHourInteger32 (0..16777215)currentData type for reporting measurements associated with energy accumulation sensors. If the underlying hardware sensor indicates 1 kWh, then the SNMP agent will report a value of 1 kWh.
MilliSecondInteger32currentDuration in milliseconds
SecondInteger32currentDuration in seconds.