SCHLEIFENBAUER-DATABUS-MIB
238 objects
This MIB describes the SNMP functions of network enabled databus devices. Copyright (c) 2021 by Schleifenbauer Holding BV
Imported Objects
| SCHLEIFENBAUER-SMI | schleifenbauerMgmt |
| SNMPv2-CONF | MODULE-COMPLIANCE NOTIFICATION-GROUP OBJECT-GROUP |
| SNMPv2-SMI | Integer32 MODULE-IDENTITY NOTIFICATION-TYPE OBJECT-TYPE Unsigned32 |
| SNMPv2-TC | DisplayString TEXTUAL-CONVENTION |
| OID | Name | Access | Status | Description |
|---|---|---|---|---|
| 1.3.6.1.4.1.31034.12.1 | IdentityschleifenbauerDatabusMIB | This MIB describes the SNMP functions of network enabled databus devices. Copyright (c) 2021 by Schleifenbauer Holding BV | ||
| 1.3.6.1.4.1.31034.12.1.0 | NodesdbMIBNotifications | |||
| 1.3.6.1.4.1.31034.12.1.0.1 | NotificationsdbDevSsDeviceStatusCodeChanged | current | Device status code changed. OBJECTS { sdbDevSsDeviceStatusCode } | |
| 1.3.6.1.4.1.31034.12.1.0.2 | NotificationsdbDevSsTemperatureAlertDetected | current | Temperature alert detected. Internal temperature alert: OBJECTS { sdbDevSsTemperatureAlert, sdbDevMsIntTemperature, sdbDevMsIntTemperaturePeak } External analo… | |
| 1.3.6.1.4.1.31034.12.1.0.3 | NotificationsdbDevSsInputCurrentAlertDetected | current | Input current alert detected. OBJECTS { sdbDevSsInputCurrentAlert, sdbDevInActualCurrent } | |
| 1.3.6.1.4.1.31034.12.1.0.4 | NotificationsdbDevSsOutletCurrentAlertDetected | current | Outlet current alert detected. OBJECTS { sdbDevSsOutletCurrentAlert, sdbDevOutMtActualCurrent } | |
| 1.3.6.1.4.1.31034.12.1.0.5 | NotificationsdbDevSsInputVoltageAlertDetected | current | Input voltage alert detected. OBJECTS { sdbDevSsInputVoltageAlert, sdbDevInActualVoltage } | |
| 1.3.6.1.4.1.31034.12.1.0.6 | NotificationsdbDevSsOutletCurrentDropAlertDetected | current | Outlet current drop alert detected. OBJECTS { sdbDevSsOutletCurrentDropAlert, sdbDevOutMtActualCurrent } | |
| 1.3.6.1.4.1.31034.12.1.0.7 | NotificationsdbDevSsInputCurrentDropAlertDetected | current | Input current drop alert detected. OBJECTS { sdbDevSsInputCurrentDropAlert, sdbDevInActualCurrent } | |
| 1.3.6.1.4.1.31034.12.1.0.8 | NotificationsdbDevSsSensorChangeAlertDetected | current | Sensor channel change alert detected. OBJECTS { sdbDevSsSensorChangeAlert } | |
| 1.3.6.1.4.1.31034.12.1.0.9 | NotificationsdbMgmtStsRingStateChanged | current | Ring state changed. Ring state changded to open: OBJECTS { sdbMgmtStsRingState, sdbMgmtStsRingBreachIndex } Ring state changded to closed: OBJECTS { sdbMgmtSts… | |
| 1.3.6.1.4.1.31034.12.1.0.10 | NotificationsdbDevSsOutletVoltageDropAlertDetected | current | Outlet voltage drop alert detected. OBJECTS { sdbDevSsOutletVoltageDropAlert, sdbDevOutMtActualVoltage } | |
| 1.3.6.1.4.1.31034.12.1.0.11 | NotificationsdbDevSsBranchCurrentAlertDetected | current | Branch current alert detected. OBJECTS { sdbDevSsBranchCurrentAlert, sdbDevBranchActualCurrent } | |
| 1.3.6.1.4.1.31034.12.1.0.12 | NotificationsdbDevSsBranchVoltageAlertDetected | current | Branch current alert detected. OBJECTS { sdbDevSsBranchVoltageAlert, sdbDevBranchActualVoltage } | |
| 1.3.6.1.4.1.31034.12.1.0.13 | NotificationsdbDevSsNeutralCurrentAlertDetected | current | Input current alert detected. OBJECTS { sdbDevSsNeutralCurrentAlert, sdbDevTotalsNeutralCurrent } | |
| 1.3.6.1.4.1.31034.12.1.0.14 | NotificationsdbDevSsResidualCurrentAlertDetected | current | Residual current alert detected. OBJECTS { sdbDevSsResidualCurrentAlert, sdbDevMsResidualCurrent, sdbDevMsResidualPeak } | |
| 1.3.6.1.4.1.31034.12.1.0.15 | NotificationsdbDevSsHardwareAlertDetected | current | Hardware alert detected. OBJECTS { sdbDevSsHardwareAlert } | |
| 1.3.6.1.4.1.31034.12.1.1 | NodesdbMIBObjects | |||
| 1.3.6.1.4.1.31034.12.1.1.1 | NodesdbMgmt | |||
| 1.3.6.1.4.1.31034.12.1.1.1.1 | NodesdbMgmtStatus | |||
| 1.3.6.1.4.1.31034.12.1.1.1.1.1 | ScalarsdbMgmtStsDevices | read-only | current | The number of devices on the databus. |
| 1.3.6.1.4.1.31034.12.1.1.1.1.2 | ScalarsdbMgmtStsAddressableDevices | read-only | current | The number of devices on the databus addressable by snmp. |
| 1.3.6.1.4.1.31034.12.1.1.1.1.3 | ScalarsdbMgmtStsNewDevices | read-only | current | The number of new devices on the databus. |
| 1.3.6.1.4.1.31034.12.1.1.1.1.4 | ScalarsdbMgmtStsDuplicateDevices | read-only | current | The number of duplicate devices on the databus. |
| 1.3.6.1.4.1.31034.12.1.1.1.1.5 | ScalarsdbMgmtStsRingState | read-only | current | If the device is in a bridge-like mode, this will indicate the actual state of the databus. |
| 1.3.6.1.4.1.31034.12.1.1.1.1.6 | ScalarsdbMgmtStsRingBreachIndex | read-only | current | Indicates the breach index if the current state of the data bus is open. If the data bus is closed this has no meaning. |
| 1.3.6.1.4.1.31034.12.1.1.1.2 | NodesdbMgmtControl | |||
| 1.3.6.1.4.1.31034.12.1.1.1.2.1 | ScalarsdbMgmtCtrlScan | read-write | current | Perform a bus scan. To verify if scanning is completed the value of this object can be read. During the bus scan the value remains 1. When the bus scan complet… |
| 1.3.6.1.4.1.31034.12.1.1.1.2.2 | ScalarsdbMgmtCtrlRenumberAllFromN | read-write | current | Renumber all devices on the databus. If set to 0 all units will be set to 0. If set to another value, all units will be numbered in sequence starting from the … |
| 1.3.6.1.4.1.31034.12.1.1.1.2.3 | ScalarsdbMgmtCtrlRenumberZeros | read-write | current | Renumber all devices on the databus having address 0. Renumbering will be done in sequence. The sequence starts with the highest address found on the databus. |
| 1.3.6.1.4.1.31034.12.1.1.1.2.4 | TablesdbMgmtCtrlDevicesTable | not-accessible | current | A table containing information of devices connected to the databus. The number of entries is given by the value of sdbMgmtStsDevices. |
| 1.3.6.1.4.1.31034.12.1.1.1.2.4.1 | RowsdbMgmtCtrlDevicesEntry | not-accessible | current | Information entry containing objects of a particular databus device. |
| 1.3.6.1.4.1.31034.12.1.1.1.2.4.1.1 | ColumnsdbMgmtCtrlDevIndex | not-accessible | current | A unique value for each device. Its value ranges between 1 and the value of sdbMgmtStsDevices with a maximum of 255. The value for each device will remain cons… |
| 1.3.6.1.4.1.31034.12.1.1.1.2.4.1.2 | ColumnsdbMgmtCtrlDevUnitAddress | read-write | current | User defined address. This will be used for addressing the device on the databus. |
| 1.3.6.1.4.1.31034.12.1.1.1.2.4.1.3 | ColumnsdbMgmtCtrlDevHardwareAddress | read-only | current | Hardware serial number. This cannot be changed. It can be used as backup unit address. format as 3 unsigned ints separated by dashes: int - int - int |
| 1.3.6.1.4.1.31034.12.1.1.1.2.4.1.4 | ColumnsdbMgmtCtrlDevIsNew | read-only | current | Indication if the device is new on the databus. |
| 1.3.6.1.4.1.31034.12.1.1.1.2.4.1.5 | ColumnsdbMgmtCtrlDevIsDuplicate | read-only | current | Indication if the device is conflicting with another device on the databus. |
| 1.3.6.1.4.1.31034.12.1.1.2 | NodesdbDevice | |||
| 1.3.6.1.4.1.31034.12.1.1.2.1 | NodesdbDevIdentification | |||
| 1.3.6.1.4.1.31034.12.1.1.2.1.1 | TablesdbDevIdTable | not-accessible | current | A table containing identification information of devices connected to the databus. The number of entries is given by the value of sdbMgmtStsAddressableDevices. |
| 1.3.6.1.4.1.31034.12.1.1.2.1.1.1 | RowsdbDevIdEntry | not-accessible | current | Information entry containing information objects of a particular databus device. |
| 1.3.6.1.4.1.31034.12.1.1.2.1.1.1.1 | ColumnsdbDevIdSPDMVersion | read-only | current | Data model version. |
| 1.3.6.1.4.1.31034.12.1.1.2.1.1.1.2 | ColumnsdbDevIdFirmwareVersion | read-only | current | The firmware revision number. |
| 1.3.6.1.4.1.31034.12.1.1.2.1.1.1.3 | ColumnsdbDevIdBuildNumber | read-only | current | Date and time the firmware was built. |
| 1.3.6.1.4.1.31034.12.1.1.2.1.1.1.4 | ColumnsdbDevIdSalesOrderNumber | read-only | current | SP sales order number. |
| 1.3.6.1.4.1.31034.12.1.1.2.1.1.1.5 | ColumnsdbDevIdProductId | read-only | current | SP product id. |
| 1.3.6.1.4.1.31034.12.1.1.2.1.1.1.6 | ColumnsdbDevIdSerialNumber | read-only | current | SP serial number. |
| 1.3.6.1.4.1.31034.12.1.1.2.1.1.1.7 | ColumnsdbDevIdHardwareAddress | read-only | current | Hardware serial number. This can not be changed. It can be used as backup unit address. Format as 3 unsigned ints separated by dashes (-) e.g. 12345-54321-00000 |
| 1.3.6.1.4.1.31034.12.1.1.2.1.1.1.8 | ColumnsdbDevIdMacAddress | read-only | current | The MAC address. This can not be changed. It represents an 802 MAC address as if it were transmitted least significant bit first. Format as six groups of 2 hex… |
| 1.3.6.1.4.1.31034.12.1.1.2.1.1.1.9 | ColumnsdbDevIdUnitAddress | read-write | current | User defined address. This will be used for addressing the device on the databus. |
| 1.3.6.1.4.1.31034.12.1.1.2.1.1.1.10 | ColumnsdbDevIdName | read-write | current | User configurable device name or identifier. |
| 1.3.6.1.4.1.31034.12.1.1.2.1.1.1.11 | ColumnsdbDevIdLocation | read-write | current | User configurable device location identifier. |
| 1.3.6.1.4.1.31034.12.1.1.2.1.1.1.12 | ColumnsdbDevIdVanityTag | read-write | current | Characters to be displayed as vanity text in display. |
| 1.3.6.1.4.1.31034.12.1.1.2.1.1.1.13 | ColumnsdbDevIdIndex | not-accessible | current | A unique value for each device. Its value represents the unit address of the device and is used to address individual devices in the tree. The value for each d… |
| 1.3.6.1.4.1.31034.12.1.1.2.1.1.1.14 | ColumnsdbDevIdDeviceType | read-only | current | A unique value for each device group. Its value represents the device type of the device. Refer to manual for more information. |
| 1.3.6.1.4.1.31034.12.1.1.2.1.1.1.15 | ColumnsdbDevIdLocateUnit | read-write | current | The LCD-backlight flashes in a heartbeat rhythm to locate the unit. |
| 1.3.6.1.4.1.31034.12.1.1.2.1.1.1.16 | ColumnsdbDevIdConfigType | read-only | current | Wiring configuration type used. |
| 1.3.6.1.4.1.31034.12.1.1.2.2 | NodesdbDevConfiguration | |||
| 1.3.6.1.4.1.31034.12.1.1.2.2.1 | TablesdbDevCfTable | not-accessible | current | A table containing configuration information of devices connected to the databus. The number of entries is given by the value of sdbMgmtStsAddressableDevices. |
| 1.3.6.1.4.1.31034.12.1.1.2.2.1.1 | RowsdbDevCfEntry | not-accessible | current | Configuration entry containing configuration objects of a particular databus device. |
| 1.3.6.1.4.1.31034.12.1.1.2.2.1.1.1 | ColumnsdbDevCfPhases | read-only | current | Number of phases for input metering. |
| 1.3.6.1.4.1.31034.12.1.1.2.2.1.1.2 | ColumnsdbDevCfOutletsTotal | read-only | current | Total number of outlets including hardwired without switch/metered modules. |
| 1.3.6.1.4.1.31034.12.1.1.2.2.1.1.3 | ColumnsdbDevCfOutletsSwitched | read-only | current | Number of switched outlets. If outlet numbering is non-contiguous its the highest outlet number. |
| 1.3.6.1.4.1.31034.12.1.1.2.2.1.1.4 | ColumnsdbDevCfOutletsMetered | read-only | current | Number of metered outlets. If outlet numbering is non-contiguous its the highest outlet number. |
| 1.3.6.1.4.1.31034.12.1.1.2.2.1.1.5 | ColumnsdbDevCfSensors | read-only | current | The number sensors. |
| 1.3.6.1.4.1.31034.12.1.1.2.2.1.1.6 | ColumnsdbDevCfMaximumLoad | read-only | current | Maximum rated load of device per phase |
| 1.3.6.1.4.1.31034.12.1.1.2.2.1.1.7 | ColumnsdbDevCfBranches | read-only | current | Number of branches for input metering. |
| 1.3.6.1.4.1.31034.12.1.1.2.2.1.1.8 | ColumnsdbDevCfNeutral | read-only | current | Nuetral current measurement. |
| 1.3.6.1.4.1.31034.12.1.1.2.2.1.1.9 | ColumnsdbDevCfTempSensors | read-only | current | Number of temperature sensors present in the system. |
| 1.3.6.1.4.1.31034.12.1.1.2.2.1.1.10 | ColumnsdbDevCfTotals | read-only | current | The number of totals rows for the configuration. |
| 1.3.6.1.4.1.31034.12.1.1.2.3 | NodesdbDevSystemStatus | |||
| 1.3.6.1.4.1.31034.12.1.1.2.3.1 | TablesdbDevSsTable | not-accessible | current | A table containing system status information of devices connected to the databus. The number of entries is given by the value of sdbMgmtStsAddressableDevices. |
| 1.3.6.1.4.1.31034.12.1.1.2.3.1.1 | RowsdbDevSsEntry | not-accessible | current | System status entry containing system status objects of a particular databus device. |
| 1.3.6.1.4.1.31034.12.1.1.2.3.1.1.1 | ColumnsdbDevSsDeviceStatusCode | read-only | current | Returns an internal status or error code. A value of 0 means OK. If not 0 it can be any of the following codes. Multiple status codes can be active at the same… |
| 1.3.6.1.4.1.31034.12.1.1.2.3.1.1.2 | ColumnsdbDevSsTemperatureAlert | read-only | current | An alert has been raised due to temperature exceeding treshhold. 0 = no alert 1 = internal temperature sensor 2 = external temperature sensor |
| 1.3.6.1.4.1.31034.12.1.1.2.3.1.1.3 | ColumnsdbDevSsInputCurrentAlert | read-only | current | An alert has been raised due to current exceeding treshhold. The value indicates the exceeding phase. 0 = no alert. |
| 1.3.6.1.4.1.31034.12.1.1.2.3.1.1.4 | ColumnsdbDevSsOutletCurrentAlert | read-only | current | An alert has been raised due to current exceeding treshhold. The value indicates the exceeding outlet. 0 = no alert. |
| 1.3.6.1.4.1.31034.12.1.1.2.3.1.1.5 | ColumnsdbDevSsInputVoltageAlert | read-only | current | An alert has been raised due to a voltage dip. The value indicates the dipped phase. 0 = no alert. |
| 1.3.6.1.4.1.31034.12.1.1.2.3.1.1.6 | ColumnsdbDevSsOutletCurrentDropAlert | read-only | current | An alert has been raised due to the current of a metered outlet suddenly dropping to near zero, possibly indicating a blown fuse. The value indicates the dropp… |
| 1.3.6.1.4.1.31034.12.1.1.2.3.1.1.7 | ColumnsdbDevSsInputCurrentDropAlert | read-only | current | An alert has been raised due to the current of a metered input suddenly dropping to near zero, possibly indicating a blown fuse. The value indicates the droppe… |
| 1.3.6.1.4.1.31034.12.1.1.2.3.1.1.8 | ColumnsdbDevSsSensorChangeAlert | read-only | current | An alert has been raised due to a change in the number of sensors. The value indicates the previous amount of sensors. |
| 1.3.6.1.4.1.31034.12.1.1.2.3.1.1.9 | ColumnsdbDevSsOutletVoltageDropAlert | read-only | current | An alert has been raised due to voltage drop on this outlet. The value indicates the first failed outlet. |
| 1.3.6.1.4.1.31034.12.1.1.2.3.1.1.10 | ColumnsdbDevSsBranchCurrentAlert | read-only | current | An alert has been raised due to current exceeding treshhold. The value indicates the exceeding branch. 0 = no alert. |
| 1.3.6.1.4.1.31034.12.1.1.2.3.1.1.11 | ColumnsdbDevSsBranchVoltageAlert | read-only | current | An alert has been raised due to a voltage dip. The value indicates the dipped branch. 0 = no alert. |
| 1.3.6.1.4.1.31034.12.1.1.2.3.1.1.12 | ColumnsdbDevSsNeutralCurrentAlert | read-only | current | An alert has been raised due to current exceeding treshhold. 0 = no alert 1 = current alert |
| 1.3.6.1.4.1.31034.12.1.1.2.3.1.1.13 | ColumnsdbDevSsResidualCurrentAlert | read-only | current | A residual current alert has been raised. 0 = no alert 1 = current exceeding treshhold alert 2 = sensor error |
| 1.3.6.1.4.1.31034.12.1.1.2.3.1.1.14 | ColumnsdbDevSsHardwareAlert | read-only | current | 0 = no alarm >0 = or slave number for alert |
| 1.3.6.1.4.1.31034.12.1.1.2.4 | NodesdbDevReset | |||
| 1.3.6.1.4.1.31034.12.1.1.2.4.1 | TablesdbDevRsTable | not-accessible | current | A table providing reset capabilities to devices connected to the databus. The number of entries is given by the value of sdbMgmtStsAddressableDevices. |
| 1.3.6.1.4.1.31034.12.1.1.2.4.1.1 | RowsdbDevRsEntry | not-accessible | current | Reset entry providing reset objects of a particular databus device. |
| 1.3.6.1.4.1.31034.12.1.1.2.4.1.1.1 | ColumnsdbDevRsReboot | read-write | current | Warm reboot/reset of device controller. NOTE: this will have NO effect on outlet status! |
| 1.3.6.1.4.1.31034.12.1.1.2.4.1.1.2 | ColumnsdbDevRsResetAlerts | read-write | current | Reset all alert signals and device status code. |
| 1.3.6.1.4.1.31034.12.1.1.2.4.1.1.3 | ColumnsdbDevRsZeroInputKWhSubtotal | read-write | current | Reset of all input kWh subtotal counters to zero. |
| 1.3.6.1.4.1.31034.12.1.1.2.4.1.1.4 | ColumnsdbDevRsZeroOutletKWhSubtotal | read-write | current | Reset of all outlet kWh subtotal counter to zero. |
| 1.3.6.1.4.1.31034.12.1.1.2.4.1.1.5 | ColumnsdbDevRsResetPeaksAndDips | read-write | current | Reset all peak and dip values to zero. |
| 1.3.6.1.4.1.31034.12.1.1.2.5 | NodesdbDevSettings | |||
| 1.3.6.1.4.1.31034.12.1.1.2.5.1 | TablesdbDevStTable | not-accessible | current | A table containing setting information of devices connected to the databus. The number of entries is given by the value of sdbMgmtStsAddressableDevices. |
| 1.3.6.1.4.1.31034.12.1.1.2.5.1.1 | RowsdbDevStEntry | not-accessible | current | Setting entry containing settings objects of a particular databus device. |
| 1.3.6.1.4.1.31034.12.1.1.2.5.1.1.2 | ColumnsdbDevStAutoResetAlerts | read-write | current | Auto reset alerts configuration. If set to 0 the auto reset alerts feature is disabled. If set to a value greater then 0, the auto reset alerts feature is enab… |
| 1.3.6.1.4.1.31034.12.1.1.2.5.1.1.3 | ColumnsdbDevStExtendedNames | read-write | current | Use original or longer names for inputs, outlets and sensors. |
| 1.3.6.1.4.1.31034.12.1.1.2.5.1.1.4 | ColumnsdbDevStPeakDuration | read-write | current | Amount of ms a current peak should last before an alert is raised. |
| 1.3.6.1.4.1.31034.12.1.1.2.5.1.1.5 | ColumnsdbDevStFixedOutletDelay | read-write | current | Minimal delay between two successive relay switches in milliseconds. Minimal delay is 100 ms. Will always be respected! |
| 1.3.6.1.4.1.31034.12.1.1.2.5.1.1.6 | ColumnsdbDevStPowerSaverMode | read-write | current | Set backlight on time in seconds. 0 keeps display always on. Note that keeping the backlight on may decrease luminosity over time. |
| 1.3.6.1.4.1.31034.12.1.1.2.5.1.1.7 | ColumnsdbDevStOutletPowerUpMode | read-write | current | Behaviour of outlets on power-up. |
| 1.3.6.1.4.1.31034.12.1.1.2.5.1.1.8 | ColumnsdbDevStMaximumTemperature | read-write | current | Maximum temperature threshold An alert will be generated whenever the temperature is above this value. Zero means disabled. |
| 1.3.6.1.4.1.31034.12.1.1.2.5.1.1.9 | ColumnsdbDevStDisplayOrientation | read-write | current | Display orientation. |
| 1.3.6.1.4.1.31034.12.1.1.2.5.1.1.10 | ColumnsdbDevStLocalAlertReset | read-write | current | Allow alerts to be reset locally on device by pushing one of the buttons. |
| 1.3.6.1.4.1.31034.12.1.1.2.5.1.1.11 | ColumnsdbDevStCurrentDropDetection | read-write | current | Enables the current drop detection function. |
| 1.3.6.1.4.1.31034.12.1.1.2.5.1.1.13 | ColumnsdbDevStUsbMode | read-write | current | Allow the USB port to be used for specific tasks |
| 1.3.6.1.4.1.31034.12.1.1.2.5.1.1.14 | ColumnsdbDevStSensorChangeAlertMode | read-write | current | Enable sensoe change alerts |
| 1.3.6.1.4.1.31034.12.1.1.2.5.1.1.15 | ColumnsdbDevStOutletUnlockOverride | read-write | current | Overrides the timeout. If this is set to 1 then the timeout will be ignored, otherwise the timeout will be taken into account. |
| 1.3.6.1.4.1.31034.12.1.1.2.6 | NodesdbDevInput | |||
| 1.3.6.1.4.1.31034.12.1.1.2.6.1 | TablesdbDevInTable | not-accessible | current | A table containing information of inputs of devices connected to the databus. |
| 1.3.6.1.4.1.31034.12.1.1.2.6.1.1 | RowsdbDevInEntry | not-accessible | current | Inputs entry containing objects of an input of a particular databus device. Note that this table has two indexes. sdbDevIdIndex to identify a particular device… |
| 1.3.6.1.4.1.31034.12.1.1.2.6.1.1.1 | ColumnsdbDevInIndex | not-accessible | current | A unique value for each input. Its value ranges between 1 and the value of sdbDevCfPhases. |
| 1.3.6.1.4.1.31034.12.1.1.2.6.1.1.2 | ColumnsdbDevInKWhTotal | read-only | current | Total kWh value of an input. This value can not be reset. |
| 1.3.6.1.4.1.31034.12.1.1.2.6.1.1.3 | ColumnsdbDevInKWhSubtotal | read-only | current | Subtotal kWh value of an input. This value can be reset. |
| 1.3.6.1.4.1.31034.12.1.1.2.6.1.1.4 | ColumnsdbDevInPowerFactor | read-only | current | Power factor of input. The power factor of an AC power system is defined as the ratio of the real or active power to the apparent power and is a number between… |
| 1.3.6.1.4.1.31034.12.1.1.2.6.1.1.5 | ColumnsdbDevInActualCurrent | read-only | current | Actual apparent, RMS current. |
| 1.3.6.1.4.1.31034.12.1.1.2.6.1.1.6 | ColumnsdbDevInPeakCurrent | read-only | current | Peak apparent, RMS current. Highest value since last reset of the alerts. |
| 1.3.6.1.4.1.31034.12.1.1.2.6.1.1.7 | ColumnsdbDevInActualVoltage | read-only | current | The actual voltage. |
| 1.3.6.1.4.1.31034.12.1.1.2.6.1.1.8 | ColumnsdbDevInMinVoltage | read-only | current | RMS voltage dip. Lowest value since reset of alerts. |
| 1.3.6.1.4.1.31034.12.1.1.2.6.1.1.9 | ColumnsdbDevInPowerVoltAmpere | read-only | current | Calculated apparent power. |
| 1.3.6.1.4.1.31034.12.1.1.2.6.1.1.10 | ColumnsdbDevInPowerWatt | read-only | current | Calculated real power. |
| 1.3.6.1.4.1.31034.12.1.1.2.6.1.1.11 | ColumnsdbDevInMaxAmps | read-write | current | Maximum current per input phase. Should last at least sdbDevStPeakDuration ms before triggering an alert. |
| 1.3.6.1.4.1.31034.12.1.1.2.6.1.1.12 | ColumnsdbDevInCTRatio | read-write | current | The multiplier to use for the input CTs. |
| 1.3.6.1.4.1.31034.12.1.1.2.6.1.1.13 | ColumnsdbDevInName | read-write | current | User configurable naming of inputs or phases. |
| 1.3.6.1.4.1.31034.12.1.1.2.6.1.1.14 | ColumnsdbDevInZeroKWhSubtotal | read-write | current | Reset input kWh subtotal counter of a single input to zero. |
| 1.3.6.1.4.1.31034.12.1.1.2.7 | NodesdbDevOutlet | |||
| 1.3.6.1.4.1.31034.12.1.1.2.7.1 | TablesdbDevOutTable | not-accessible | current | A table containing information of outlets of devices connected to the databus. |
| 1.3.6.1.4.1.31034.12.1.1.2.7.1.1 | RowsdbDevOutEntry | not-accessible | current | Outlets entry containing objects of an outlet of a particular databus device. Note that this table has two indexes. sdbDevIdIndex to identify a particular devi… |
| 1.3.6.1.4.1.31034.12.1.1.2.7.1.1.1 | ColumnsdbDevOutIndex | not-accessible | current | A unique value for each outlet. Its value ranges between 1 and the value of sdbDevCfOutletsTotal. |
| 1.3.6.1.4.1.31034.12.1.1.2.7.1.1.2 | ColumnsdbDevOutName | read-write | current | User configurable naming of individual outlets. |
| 1.3.6.1.4.1.31034.12.1.1.2.7.2 | TablesdbDevOutMtTable | not-accessible | current | A table containing information of metered outlets of devices connected to the databus. |
| 1.3.6.1.4.1.31034.12.1.1.2.7.2.1 | RowsdbDevOutMtEntry | not-accessible | current | Metered outlets entry containing objects of a metered outlet of a particular databus device. Note that this table has two indexes. sdbDevIdIndex to identify a … |
| 1.3.6.1.4.1.31034.12.1.1.2.7.2.1.1 | ColumnsdbDevOutMtIndex | not-accessible | current | A unique value for each outlet. Its value ranges between 1 and the value of sdbDevCfOutletsMetered. |
| 1.3.6.1.4.1.31034.12.1.1.2.7.2.1.2 | ColumnsdbDevOutMtKWhTotal | read-only | current | Total kWh value of an outlet. This value can not be reset. |
| 1.3.6.1.4.1.31034.12.1.1.2.7.2.1.3 | ColumnsdbDevOutMtKWhSubtotal | read-only | current | Subotal kWh value of an outlet. This value can be reset. |
| 1.3.6.1.4.1.31034.12.1.1.2.7.2.1.4 | ColumnsdbDevOutMtPowerFactor | read-only | current | Power factor of outlet. The power factor of an AC power system is defined as the ratio of the real or active power to the apparent power and is a number betwee… |
| 1.3.6.1.4.1.31034.12.1.1.2.7.2.1.5 | ColumnsdbDevOutMtActualCurrent | read-only | current | Actual apparent, RMS current. |
| 1.3.6.1.4.1.31034.12.1.1.2.7.2.1.6 | ColumnsdbDevOutMtPeakCurrent | read-only | current | Peak apparent, RMS current. Highest value since last reset of the alerts. |
| 1.3.6.1.4.1.31034.12.1.1.2.7.2.1.7 | ColumnsdbDevOutMtActualVoltage | read-only | current | Actual voltage on outlet. |
| 1.3.6.1.4.1.31034.12.1.1.2.7.2.1.8 | ColumnsdbDevOutMtMaxAmps | read-write | current | Maximum current per outlet. Should last at least sdbDevStPeakDuration ms before triggering an alert. |
| 1.3.6.1.4.1.31034.12.1.1.2.7.2.1.9 | ColumnsdbDevOutMtCTRatio | read-write | current | The multiplier to use for the outlet CTs. |
| 1.3.6.1.4.1.31034.12.1.1.2.7.2.1.10 | ColumnsdbDevOutMtPowerVoltAmpere | read-only | current | Calculated apparent power. |
| 1.3.6.1.4.1.31034.12.1.1.2.7.2.1.11 | ColumnsdbDevOutMtPowerWatt | read-only | current | Calculated real power. |
| 1.3.6.1.4.1.31034.12.1.1.2.7.3 | TablesdbDevOutSwTable | not-accessible | current | A table containing information of switched outlets of devices connected to the databus. |
| 1.3.6.1.4.1.31034.12.1.1.2.7.3.1 | RowsdbDevOutSwEntry | not-accessible | current | Switched outlets entry containing objects of a switched outlet of a particular databus device. Note that this table has two indexes. sdbDevIdIndex to identify … |
| 1.3.6.1.4.1.31034.12.1.1.2.7.3.1.1 | ColumnsdbDevOutSwIndex | not-accessible | current | A unique value for each outlet. Its value ranges between 1 and the value of sdbDevCfOutletsSwitched. |
| 1.3.6.1.4.1.31034.12.1.1.2.7.3.1.2 | ColumnsdbDevOutSwCurrentState | read-write | current | The actual state of the outlet relay. Note that Writing is only effective after setting sdbDevOutSwUnlock. |
| 1.3.6.1.4.1.31034.12.1.1.2.7.3.1.3 | ColumnsdbDevOutSwScheduled | read-only | current | A one indicates pending activity; the switch delay has not yet expired. |
| 1.3.6.1.4.1.31034.12.1.1.2.7.3.1.4 | ColumnsdbDevOutSwUnlock | read-write | current | Switching and rebooting is unlocked for 10 seconds by writing a 1. |
| 1.3.6.1.4.1.31034.12.1.1.2.7.3.1.5 | ColumnsdbDevOutSwIndividualOutletDelay | read-write | current | Delay before an individual outlet switches on at power-up. |
| 1.3.6.1.4.1.31034.12.1.1.2.7.3.1.6 | ColumnsdbDevOutSwReboot | read-write | current | Reboot outlet relay if current state is on and outlet is unlocked; The outlet will be turned on after 10 seconds. |
| 1.3.6.1.4.1.31034.12.1.1.2.8 | NodesdbDevSensor | |||
| 1.3.6.1.4.1.31034.12.1.1.2.8.1 | TablesdbDevMeasuresTable | not-accessible | current | A table containing information of temperatures of devices connected to the databus. |
| 1.3.6.1.4.1.31034.12.1.1.2.8.1.1 | RowsdbDevMeasuresEntry | not-accessible | current | Device measures entry containing temperature information objects of a particular databus device. |
| 1.3.6.1.4.1.31034.12.1.1.2.8.1.1.1 | ColumnsdbDevMsIntTemperature | read-only | current | Actual internal device temperature in deg C |
| 1.3.6.1.4.1.31034.12.1.1.2.8.1.1.2 | ColumnsdbDevMsExtTemperature | read-only | current | Actual external device temperature sensor in deg C. |
| 1.3.6.1.4.1.31034.12.1.1.2.8.1.1.3 | ColumnsdbDevMsIntTemperaturePeak | read-only | current | Peak internal device temperature since last reset of alerts. |
| 1.3.6.1.4.1.31034.12.1.1.2.8.1.1.4 | ColumnsdbDevMsExtTemperaturePeak | read-only | current | Peak external device temperature since last reset of alerts. |
| 1.3.6.1.4.1.31034.12.1.1.2.8.1.1.5 | ColumnsdbDevMsResidualCurrent | read-only | current | Residual current. |
| 1.3.6.1.4.1.31034.12.1.1.2.8.1.1.6 | ColumnsdbDevMsResidualPeak | read-only | current | Peak residual current. |
| 1.3.6.1.4.1.31034.12.1.1.2.8.2 | TablesdbDevSnsTable | not-accessible | current | A table containing information of sensors of devices connected to the databus. |
| 1.3.6.1.4.1.31034.12.1.1.2.8.2.1 | RowsdbDevSnsEntry | not-accessible | current | Sensors entry containing objects of a sensor of a particular databus device. Note that this table has two indexes. sdbDevIdIndex to identify a particular devic… |
| 1.3.6.1.4.1.31034.12.1.1.2.8.2.1.1 | ColumnsdbDevSnsIndex | not-accessible | current | A unique value for each sensor. Its value ranges between 1 and the value of sdbDevCfSensors. |
| 1.3.6.1.4.1.31034.12.1.1.2.8.2.1.2 | ColumnsdbDevSnsType | read-only | current | Type of connected sensor. T = Temperature (C) H = Humidity (%) I = dry switch contact |
| 1.3.6.1.4.1.31034.12.1.1.2.8.2.1.3 | ColumnsdbDevSnsValue | read-only | current | Value of connected sensor |
| 1.3.6.1.4.1.31034.12.1.1.2.8.2.1.4 | ColumnsdbDevSnsName | read-write | current | User definable name for sensors. |
| 1.3.6.1.4.1.31034.12.1.1.2.9 | NodesdbDevPerformance | |||
| 1.3.6.1.4.1.31034.12.1.1.2.9.1 | TablesdbDevPerformanceTable | not-accessible | current | A table containing information of sensors of devices connected to the databus. |
| 1.3.6.1.4.1.31034.12.1.1.2.9.1.1 | RowsdbDevPerformanceEntry | not-accessible | current | Performance counters of a particular databus device. Note that this table has two indexes. sdbDevIdIndex to identify a particular device and sdbDevPerformanceI… |
| 1.3.6.1.4.1.31034.12.1.1.2.9.1.1.1 | ColumnsdbDevPerformanceIndex | not-accessible | current | A unique value for each counter. Its value ranges between 1 and 16. |
| 1.3.6.1.4.1.31034.12.1.1.2.9.1.1.2 | ColumnsdbDevPerformanceValue | read-only | current | Value of counter |
| 1.3.6.1.4.1.31034.12.1.1.2.9.1.1.3 | ColumnsdbDevPerformanceMax | read-only | current | Max of counter |
| 1.3.6.1.4.1.31034.12.1.1.2.9.1.1.4 | ColumnsdbDevPerformanceLimit | read-only | current | Limit of counter |
| 1.3.6.1.4.1.31034.12.1.1.2.9.1.1.5 | ColumnsdbDevPerformanceName | read-write | current | User definable name for counter. |
| 1.3.6.1.4.1.31034.12.1.1.2.9.2 | TablesdbDevPerformanceResetTable | not-accessible | current | A table containing the last reset reason of the device |
| 1.3.6.1.4.1.31034.12.1.1.2.9.2.1 | RowsdbDevPerformanceResetEntry | not-accessible | current | Setting entry containing settings objects of a particular databus device. |
| 1.3.6.1.4.1.31034.12.1.1.2.9.2.1.1 | ColumnsdbDevPerformanceResetReason | read-write | current | Last reset reason. |
| 1.3.6.1.4.1.31034.12.1.1.2.9.2.1.2 | ColumnsdbDevResetUptime | read-only | current | Uptime before last reset |
| 1.3.6.1.4.1.31034.12.1.1.2.10 | NodesdbDevBranches | |||
| 1.3.6.1.4.1.31034.12.1.1.2.10.1 | TablesdbDevBranchTable | not-accessible | current | A table containing information of inputs of devices connected to the databus. |
| 1.3.6.1.4.1.31034.12.1.1.2.10.1.1 | RowsdbDevBranchEntry | not-accessible | current | Inputs entry containing objects of an input of a particular databus device. Note that this table has two indexes. sdbDevIdIndex to identify a particular device… |
| 1.3.6.1.4.1.31034.12.1.1.2.10.1.1.1 | ColumnsdbDevBranchIndex | not-accessible | current | A unique value for each input. Its value ranges between 1 and the value of sdbDevCfPhases. |
| 1.3.6.1.4.1.31034.12.1.1.2.10.1.1.2 | ColumnsdbDevBranchKWhTotal | read-only | current | Total kWh value of an input. This value can not be reset. |
| 1.3.6.1.4.1.31034.12.1.1.2.10.1.1.3 | ColumnsdbDevBranchKWhSubtotal | read-only | current | Subtotal kWh value of an input. This value can be reset. |
| 1.3.6.1.4.1.31034.12.1.1.2.10.1.1.4 | ColumnsdbDevBranchPowerFactor | read-only | current | Power factor of input. The power factor of an AC power system is defined as the ratio of the real or active power to the apparent power and is a number between… |
| 1.3.6.1.4.1.31034.12.1.1.2.10.1.1.5 | ColumnsdbDevBranchActualCurrent | read-only | current | Actual apparent, RMS current. |
| 1.3.6.1.4.1.31034.12.1.1.2.10.1.1.6 | ColumnsdbDevBranchPeakCurrent | read-only | current | Peak apparent, RMS current. Highest value since last reset of the alerts. |
| 1.3.6.1.4.1.31034.12.1.1.2.10.1.1.7 | ColumnsdbDevBranchActualVoltage | read-only | current | The actual voltage. |
| 1.3.6.1.4.1.31034.12.1.1.2.10.1.1.8 | ColumnsdbDevBranchMinVoltage | read-only | current | RMS voltage dip. Lowest value since reset of alerts. |
| 1.3.6.1.4.1.31034.12.1.1.2.10.1.1.9 | ColumnsdbDevBranchPowerVoltAmpere | read-only | current | Calculated apparent power. |
| 1.3.6.1.4.1.31034.12.1.1.2.10.1.1.10 | ColumnsdbDevBranchPowerWatt | read-only | current | Calculated real power. |
| 1.3.6.1.4.1.31034.12.1.1.2.10.1.1.11 | ColumnsdbDevBranchMaxAmps | read-write | current | Maximum current per input phase. Should last at least sdbDevStPeakDuration ms before triggering an alert. |
| 1.3.6.1.4.1.31034.12.1.1.2.10.1.1.12 | ColumnsdbDevBranchCTRatio | read-write | current | The multiplier to use for the input CTs. |
| 1.3.6.1.4.1.31034.12.1.1.2.10.1.1.13 | ColumnsdbDevBranchName | read-write | current | User configurable naming of branches. |
| 1.3.6.1.4.1.31034.12.1.1.2.10.1.1.14 | ColumnsdbDevBranchZeroKWhSubtotal | read-write | current | Reset input kWh subtotal counter of a single input to zero. |
| 1.3.6.1.4.1.31034.12.1.1.2.11 | NodesdbDevTotals | |||
| 1.3.6.1.4.1.31034.12.1.1.2.11.1 | TablesdbDevTotalsTable | not-accessible | current | A table containing information of inputs of devices connected to the databus. |
| 1.3.6.1.4.1.31034.12.1.1.2.11.1.1 | RowsdbDevTotalsEntry | not-accessible | current | Inputs entry containing objects of an input of a particular databus device. Note that this table has two indexes. sdbDevIdIndex to identify a particular device… |
| 1.3.6.1.4.1.31034.12.1.1.2.11.1.1.1 | ColumnsdbDevTotalsIndex | not-accessible | current | A unique value for each input. Its value ranges between 1 and the value of sdbDevCfPhases. |
| 1.3.6.1.4.1.31034.12.1.1.2.11.1.1.2 | ColumnsdbDevTotalsKWhTotal | read-only | current | Total kWh value of an input. This value can not be reset. |
| 1.3.6.1.4.1.31034.12.1.1.2.11.1.1.3 | ColumnsdbDevTotalsPowerFactor | read-only | current | Power factor of input. The power factor of an AC power system is defined as the ratio of the real or active power to the apparent power and is a number between… |
| 1.3.6.1.4.1.31034.12.1.1.2.11.1.1.4 | ColumnsdbDevTotalsActualCurrent | read-only | current | Actual apparent, RMS current. |
| 1.3.6.1.4.1.31034.12.1.1.2.11.1.1.5 | ColumnsdbDevTotalsPeakCurrent | read-only | current | Peak apparent, RMS current. Highest value since last reset of the alerts. |
| 1.3.6.1.4.1.31034.12.1.1.2.11.1.1.6 | ColumnsdbDevTotalsPowerVoltAmpere | read-only | current | Calculated apparent power. |
| 1.3.6.1.4.1.31034.12.1.1.2.11.1.1.7 | ColumnsdbDevTotalsPowerWatt | read-only | current | Calculated real power. |
| 1.3.6.1.4.1.31034.12.1.1.2.11.1.1.8 | ColumnsdbDevTotalsNeutralCurrent | read-only | current | Neutral current of phases. |
| 1.3.6.1.4.1.31034.12.1.1.2.11.1.1.9 | ColumnsdbDevTotalsNeutralPeak | read-only | current | Peak neutral current of phases. |
| 1.3.6.1.4.1.31034.12.1.1.2.11.1.1.10 | ColumnsdbDevTotalsNeutralMaxAmps | read-write | current | Maximum neutral current. Should last at least sdbDevStPeakDuration ms before triggering an alert. |
| 1.3.6.1.4.1.31034.12.1.1.2.11.1.1.11 | ColumnsdbDevTotalsResidualMaxAmps | read-write | current | Maximum residual current. Should last at least sdbDevStPeakDuration ms before triggering an alert. |
| 1.3.6.1.4.1.31034.12.1.2 | NodesdbMIBConformance | |||
| 1.3.6.1.4.1.31034.12.1.2.1 | NodesdbMIBCompliances | |||
| 1.3.6.1.4.1.31034.12.1.2.1.1 | CompliancesdbMIBCompliance | current | The requirements for conformance to the SCHLEIFENBAUER-DATABUS-MIB. | |
| 1.3.6.1.4.1.31034.12.1.2.2 | NodesdbMIBGroups | |||
| 1.3.6.1.4.1.31034.12.1.2.2.1 | GroupsdbMIBNotificationGroup | current | A collection of notifications. | |
| 1.3.6.1.4.1.31034.12.1.2.2.3 | GroupsdbMIBDevIdGroup | current | A collection of objects providing identification information about the device. | |
| 1.3.6.1.4.1.31034.12.1.2.2.4 | GroupsdbMIBDevCfGroup | current | A collection of objects providing configuration information about the device. | |
| 1.3.6.1.4.1.31034.12.1.2.2.5 | GroupsdbMIBDevSsGroup | current | A collection of objects providing status information about the device. | |
| 1.3.6.1.4.1.31034.12.1.2.2.6 | GroupsdbMIBDevRsGroup | current | Groups resettable attributes op the device. | |
| 1.3.6.1.4.1.31034.12.1.2.2.7 | GroupsdbMIBDevStGroup | current | A collection of objects providing the actual settings about the device. | |
| 1.3.6.1.4.1.31034.12.1.2.2.8 | GroupsdbMIBDevInGroup | current | A collection of objects providing the actual input measurements of the device. | |
| 1.3.6.1.4.1.31034.12.1.2.2.9 | GroupsdbMIBDevOutGroup | current | A collection of objects providing the actual outlet measurements of the device. | |
| 1.3.6.1.4.1.31034.12.1.2.2.10 | GroupsdbMIBDevOutMtGroup | current | A collection of objects providing the actual outlet measurements of the device. | |
| 1.3.6.1.4.1.31034.12.1.2.2.11 | GroupsdbMIBDevOutSwGroup | current | A collection of objects providing the actual outlet measurements of the device. | |
| 1.3.6.1.4.1.31034.12.1.2.2.12 | GroupsdbMIBDevSensorGroup | current | A collection of objects providing the actual environmental measurements of the device. | |
| 1.3.6.1.4.1.31034.12.1.2.2.13 | GroupsdbMIBMgmtStatusGroup | current | A collection of objects providing management status information about the databus. | |
| 1.3.6.1.4.1.31034.12.1.2.2.14 | GroupsdbMIBMgmtControlGroup | current | A collection of objects providing management control information about the databus. | |
| 1.3.6.1.4.1.31034.12.1.2.2.15 | GroupsdbMIBDevPerformanceGroup | current | A collection of objects providing performance information about the MCU |
Type Definitions
| Name | Syntax | Status | Description |
|---|---|---|---|
| CentiAmpere | Integer32 (0..327680) | current | Data type for reporting measurements and thresholds associated with current sensors. If the underlying hardware sensor indicates 1.1 A, then the SNMP agent will report a value of 110 CentiAmpere. |
| CentiCelsius | Integer32 (0..9900) | current | Data type for reporting sensor readings associated with temperature sensors. If the underlying hardware sensor indicates 20.1 degrees Celsius, then the SNMP agent will report a value of 2010 CentiCelsius. |
| CentiPercent | Integer32 (0..10000) | current | Data type for reporting calculated percentages. If the calculated percentage is 98.3%, then the SNMP agent will report a value of 9830 CentiPercent. |
| CentiValue | Integer32 (0..327680) | current | Data type for reporting generic measurements associated with environmental sensors. If the underlying hardware sensor indicates 21.1 degrees Celsius, then the SNMP agent will report a value of 2110 CentiValue. |
| CentiVolt | Integer32 (0..327680) | current | Data type for reporting measurements and thresholds associated with voltage sensors. If the underlying hardware sensor indicates 231.1 V, then the SNMP agent will report a value of 23110 CentiVolt. |
| KiloWattHour | Integer32 (0..16777215) | current | Data type for reporting measurements associated with energy accumulation sensors. If the underlying hardware sensor indicates 1 kWh, then the SNMP agent will report a value of 1 kWh. |
| MilliSecond | Integer32 | current | Duration in milliseconds |
| Second | Integer32 | current | Duration in seconds. |