SCHLEIFENBAUER-GENERIC-MIB

388 objects
The SNMP MIB structure for the Schleifenbauer Products BV enterprise. Copyright (c) 2024 by Schleifenbauer Products BV
Imported Objects
SNMPv2-CONFMODULE-COMPLIANCE NOTIFICATION-GROUP OBJECT-GROUP
SNMPv2-SMIenterprises Integer32 IpAddress MODULE-IDENTITY NOTIFICATION-TYPE OBJECT-TYPE
SNMPv2-TCDisplayString
OIDNameAccessStatusDescription
1.3.6.1.4.1.44568IdentityschleifenbauerThe SNMP MIB structure for the Schleifenbauer Products BV enterprise. Copyright (c) 2024 by Schleifenbauer Products BV
1.3.6.1.4.1.44568.1Nodeenertree
1.3.6.1.4.1.44568.1.0Nodenotifications
1.3.6.1.4.1.44568.1.0.1NotificationsystemStartedcurrentThe system has started.
1.3.6.1.4.1.44568.1.0.2NotificationsystemRebootedcurrentThe system was reset.
1.3.6.1.4.1.44568.1.0.3NotificationrestartedcurrentThe software was reset.
1.3.6.1.4.1.44568.1.0.10NotificationuserLogincurrentA user logged in.
1.3.6.1.4.1.44568.1.0.11NotificationuserLogoutcurrentA user logged out.
1.3.6.1.4.1.44568.1.0.12NotificationuserAuthenticationFailurecurrentA user authentication attempt failed.
1.3.6.1.4.1.44568.1.0.20NotificationdeviceConnectionConfiguredcurrentA new device has been added.
1.3.6.1.4.1.44568.1.0.21NotificationdeviceConnectionDeletedcurrentA new device deleted.
1.3.6.1.4.1.44568.1.0.30NotificationdeviceStartcurrentA device connects.
1.3.6.1.4.1.44568.1.0.31NotificationdeviceReconnectedcurrentA new device reconnects.
1.3.6.1.4.1.44568.1.0.32NotificationdeviceDisconnectedcurrentA device disconnects.
1.3.6.1.4.1.44568.1.0.33NotificationdeviceErrorcurrentA new device error.
1.3.6.1.4.1.44568.1.0.50NotificationwarningStartEventcurrentStart warning state.
1.3.6.1.4.1.44568.1.0.51NotificationwarningEndEventcurrentEnd warning state.
1.3.6.1.4.1.44568.1.0.60NotificationcriticalStartEventcurrentStart critical state.
1.3.6.1.4.1.44568.1.0.61NotificationcriticalEndEventcurrentEnd of critical state.
1.3.6.1.4.1.44568.1.0.62NotificationdigitalInputEventcurrentDigital state change on/off.
1.3.6.1.4.1.44568.1.1NodeenertreeObjects
1.3.6.1.4.1.44568.1.1.1NodesystemStatus
1.3.6.1.4.1.44568.1.1.1.1ScalarsystemStatusNameread-onlycurrentThe gateway name
1.3.6.1.4.1.44568.1.1.1.2ScalarsystemStatusIpread-onlycurrentThe gateway ip address
1.3.6.1.4.1.44568.1.1.1.3ScalarsystemStatusIdread-onlycurrentThe gateway shepherd ID address
1.3.6.1.4.1.44568.1.1.2NodedeviceIdentification
1.3.6.1.4.1.44568.1.1.2.1TabledeviceIdentificationTablenot-accessiblecurrentGeneral identification parameters.
1.3.6.1.4.1.44568.1.1.2.1.1RowdeviceIdentificationEntrynot-accessiblecurrentGeneral identification parameters.
1.3.6.1.4.1.44568.1.1.2.1.1.1ColumnidentificationDeviceIndexnot-accessiblecurrentA unique value for each PDU. Its value ranges between 1 and the value of pduCount.
1.3.6.1.4.1.44568.1.1.2.1.1.2ColumnidDeviceNameread-writecurrentUser configurable device name or identifier.
1.3.6.1.4.1.44568.1.1.2.1.1.3ColumnidDeviceLocationread-writecurrentUser configurable device location identifier.
1.3.6.1.4.1.44568.1.1.2.1.1.4ColumnidModuleTyperead-onlycurrentDevice category: 0 = Daisychain Module, 1 = Gateway Module, 2 = Controller Module (SF also uses -1 to meaning no module!)
1.3.6.1.4.1.44568.1.1.2.1.1.5ColumnidProductread-onlycurrentProduct id
1.3.6.1.4.1.44568.1.1.2.1.1.6ColumnidModuleFirmwareread-onlycurrentFirmware version number.
1.3.6.1.4.1.44568.1.1.2.1.1.7ColumnidMacAddressread-onlycurrentMAC address.
1.3.6.1.4.1.44568.1.1.2.1.1.8ColumnidBirthdayread-onlycurrentDate Of Manufacture (DOM)
1.3.6.1.4.1.44568.1.1.2.1.1.9ColumnidModuleSerialNumberread-onlycurrentModule serial number
1.3.6.1.4.1.44568.1.1.2.1.1.10ColumnidModulePartNoread-onlycurrentModule part number.
1.3.6.1.4.1.44568.1.1.2.1.1.11ColumnidSalesOrderNumberread-onlycurrentSales order number
1.3.6.1.4.1.44568.1.1.2.1.1.12ColumnidSerialNumberread-onlycurrentSerial number
1.3.6.1.4.1.44568.1.1.2.1.1.13ColumnidExtraTagread-writecurrentThe device extra info
1.3.6.1.4.1.44568.1.1.2.1.1.14ColumnidStateread-onlycurrentThe device state info as string
1.3.6.1.4.1.44568.1.1.2.1.1.15ColumnidVendorread-onlycurrentThe device vendor name
1.3.6.1.4.1.44568.1.1.2.1.1.16ColumnidIdread-onlycurrentThe device unique identifier
1.3.6.1.4.1.44568.1.1.2.1.1.17ColumnidIpAddrread-onlycurrentThe device IP Addr
1.3.6.1.4.1.44568.1.1.2.1.1.18ColumnidTyperead-onlycurrentThe device type. e.g. PDU, UPS, etc
1.3.6.1.4.1.44568.1.1.2.1.1.19ColumnidLastErrorread-onlycurrentThe last error message
1.3.6.1.4.1.44568.1.1.3NodedeviceConfig
1.3.6.1.4.1.44568.1.1.3.1TabledeviceConfigTablenot-accessiblecurrentA list to display device configuration.
1.3.6.1.4.1.44568.1.1.3.1.1RowdeviceConfigEntrynot-accessiblecurrentA list to display device configuration.
1.3.6.1.4.1.44568.1.1.3.1.1.1ColumnconfigDeviceIndexnot-accessiblecurrentA unique value for each PDU. Its value ranges between 1 and the value of pduCount.
1.3.6.1.4.1.44568.1.1.3.1.1.2ColumnconfigMaximumLoadread-onlycurrentMaximum rated load of the device per phase (this value is also mentioned on the PDU profile), usually either 16A, 32A or 63A.
1.3.6.1.4.1.44568.1.1.3.1.1.3ColumnconfigCustomerNameread-writecurrentCustom 64 character name field for the customer.
1.3.6.1.4.1.44568.1.1.3.1.1.4ColumnconfigFormFactorread-onlycurrentFormfactor of the device.
1.3.6.1.4.1.44568.1.1.3.1.1.5ColumnconfigLengthread-onlycurrentLength of the device in millimeter.
1.3.6.1.4.1.44568.1.1.3.1.1.6ColumnconfigNoBranchesread-onlycurrentThe number of branches available in the PDU, can be zero if no branches are available in the configuration.
1.3.6.1.4.1.44568.1.1.3.1.1.7ColumnconfigNrOutlMeasuredread-onlycurrentNumber of measured outlets available in the PDU. If numbering of outlets used is non-contiguous: the highest outlet number is assumed as amount of measured out…
1.3.6.1.4.1.44568.1.1.3.1.1.8ColumnconfigNoNeutralread-onlycurrentUse neutral current measurements if available: 0 = No neutral current measurement, 1 = Use neutral current measurement.
1.3.6.1.4.1.44568.1.1.3.1.1.9ColumnconfigNrOutletsTotalread-onlycurrentTotal number of outlets available in the PDU, including hardwired outlets without a switchmeasure module.
1.3.6.1.4.1.44568.1.1.3.1.1.10ColumnconfigNrPhasesread-onlycurrentTotal number of inputs: either zero (for no input metering), one or three for a single or three phase system.
1.3.6.1.4.1.44568.1.1.3.1.1.11ColumnconfigNrOutlSwitchedread-onlycurrentTotal number of switched outlets available. If the numbering of outlets used is non-contiguous: the highest outlet number is assumed as amount of switched outl…
1.3.6.1.4.1.44568.1.1.3.1.1.12ColumnconfigNoTotalsread-onlycurrentThe number of total calculations available in the PDU, this is usually one but can be more.
1.3.6.1.4.1.44568.1.1.3.1.1.13ColumnconfigVoltRatingread-onlycurrentVoltage rating in V for this PDU.
1.3.6.1.4.1.44568.1.1.4NodedeviceSettings
1.3.6.1.4.1.44568.1.1.4.1TabledeviceSettingsTablenot-accessiblecurrentdevice e.g. PDU settings.
1.3.6.1.4.1.44568.1.1.4.1.1RowdeviceSettingsEntrynot-accessiblecurrentdevice e.g. PDU configuration.
1.3.6.1.4.1.44568.1.1.4.1.1.1ColumnsettingsDeviceIndexnot-accessiblecurrentA unique value for each PDU. Its value ranges between 1 and the value of pduCount.
1.3.6.1.4.1.44568.1.1.4.1.1.2ColumnsetCurrentDropDetectionread-writecurrentEnable or disable current drop detection (0 = disabled, 1 = enabled)
1.3.6.1.4.1.44568.1.1.4.1.1.3ColumnsetFixedOutletDelayread-writecurrentMinimal delay between relay switch requests in milliseconds. The minimum delay is 100ms.
1.3.6.1.4.1.44568.1.1.4.1.1.4ColumnsetHighlightread-writecurrentLocate a unit. Set to '1' to switch on and to '0' to switch off this function.
1.3.6.1.4.1.44568.1.1.4.1.1.5ColumnsetLedBrightnessread-writecurrentLED brightness setting for the light ring of a PDU
1.3.6.1.4.1.44568.1.1.4.1.1.6ColumnsetDisableOutletSwitchingread-writecurrentSetting this will disable all means of switching an outlet; only the powerup modes and delays will be respected (0 = disabled, 1 = enabled).
1.3.6.1.4.1.44568.1.1.4.1.1.7ColumnsetOutletPowerupModeread-writecurrentBehaviour of outlets on power-up. 0 = off, 1 = same state as at power down use default switch delay, 2 = same state, but delayed by individual delay timer, 3 =…
1.3.6.1.4.1.44568.1.1.4.1.1.8ColumnsetSensorChangeAlertModeread-writecurrentEnables the sensor channel change detection. 0 = off (default), 1 = on
1.3.6.1.4.1.44568.1.1.4.1.1.9ColumnsetConfigUsbModeread-writecurrentUSB Mode. 0 = Disabled, 1 = Enabled
1.3.6.1.4.1.44568.1.1.5NodedeviceDaisychain
1.3.6.1.4.1.44568.1.1.5.1TabledeviceDaisychainTablenot-accessiblecurrentdevice e.g. daisychain values.
1.3.6.1.4.1.44568.1.1.5.1.1RowdeviceDaisychainEntrynot-accessiblecurrentdevice e.g. PDU configuration.
1.3.6.1.4.1.44568.1.1.5.1.1.1ColumndaisychainDeviceIndexnot-accessiblecurrentA unique value for each PDU. Its value ranges between 1 and the value of pduCount.
1.3.6.1.4.1.44568.1.1.5.1.1.2ColumndChainBreakLocationread-onlycurrentDevice index of the ring break location. Can be used to determine between which devices the ring is broken.
1.3.6.1.4.1.44568.1.1.5.1.1.3ColumndChainBusStatusread-onlycurrentSPBUS network architecture configuration. 0 = open ring network, 1 = closed ring network
1.3.6.1.4.1.44568.1.1.5.1.1.4ColumndChainNrUnitsFoundread-onlycurrentResult of scan command, denotes the number of devices on the SPBUS network.
1.3.6.1.4.1.44568.1.1.5.1.1.5ColumndChainUnitListread-onlycurrentList of unit addresses known to the device. Position ordered list of assigned unit addresses.
1.3.6.1.4.1.44568.1.1.6NodedeviceReset
1.3.6.1.4.1.44568.1.1.6.1TabledeviceResetTablenot-accessiblecurrentdevice e.g. PDU reset values.
1.3.6.1.4.1.44568.1.1.6.1.1RowdeviceResetEntrynot-accessiblecurrentdevice e.g. PDU configuration.
1.3.6.1.4.1.44568.1.1.6.1.1.1ColumnresetDeviceIndexnot-accessiblecurrentA unique value for each PDU. Its value ranges between 1 and the value of pduCount.
1.3.6.1.4.1.44568.1.1.6.1.1.2ColumnresetRestartread-writecurrentWriting '1' to this register will invoke a warm restart of the device. Note that this will have no effect on outlet status!
1.3.6.1.4.1.44568.1.1.7NodedeviceInputs
1.3.6.1.4.1.44568.1.1.7.1TabledeviceInputsTablenot-accessiblecurrentA list to display status of Input.
1.3.6.1.4.1.44568.1.1.7.1.1RowdeviceInputsEntrynot-accessiblecurrentA list to display status of Input.
1.3.6.1.4.1.44568.1.1.7.1.1.1ColumninputDeviceIndexnot-accessiblecurrentA unique value for each PDU. Its value ranges between 1 and the value of pduCount.
1.3.6.1.4.1.44568.1.1.7.1.1.2ColumninputIndexnot-accessiblecurrentIndex of inputs.
1.3.6.1.4.1.44568.1.1.7.1.1.3ColumninputNameread-writecurrentUser configurable 64 character naming of the inputs or phases.
1.3.6.1.4.1.44568.1.1.7.1.1.4ColumninputEnergyTotalread-onlycurrentEither the only phase in a single phase measurement; or one of the three phases in a multiphase measurement. This value is not resetable.
1.3.6.1.4.1.44568.1.1.7.1.1.5ColumninputEnergySubtotalread-onlycurrentkWh subtotal register of the only phase in a single phase measurement; or one of three phases in a multiphase measurement.
1.3.6.1.4.1.44568.1.1.7.1.1.6ColumninputActivePowerread-onlycurrentInput power (in W) x100, MEASURED by the device using current, voltage, and power factor measurements of a phase.
1.3.6.1.4.1.44568.1.1.7.1.1.7ColumninputApparentPowerread-onlycurrentInput VA (volt-amps, in VA) 100x, MEASURED by the device using current and voltage measurements of a phase.
1.3.6.1.4.1.44568.1.1.7.1.1.8ColumninputReactivePowerread-onlycurrentReactive power (volt-amps reactive, in VAR) 100x, MEASURED by the device.
1.3.6.1.4.1.44568.1.1.7.1.1.9ColumninputPowerFactorread-onlycurrentThe effective power factor for each input 100x.
1.3.6.1.4.1.44568.1.1.7.1.1.10ColumninputActualCurrentread-onlycurrentActual apparent, RMS current of an input 100x.
1.3.6.1.4.1.44568.1.1.7.1.1.11ColumninputActualVoltageread-onlycurrentThe actual voltage per input 100x.
1.3.6.1.4.1.44568.1.1.7.1.1.12ColumninputFrequencyread-onlycurrentFrequency in Hz per input 100x.
1.3.6.1.4.1.44568.1.1.7.1.1.13ColumninputApparentEnergyread-onlycurrentThe apparent accumulated energy VAh of each phase 100x.
1.3.6.1.4.1.44568.1.1.7.1.1.14ColumninputCrestFactorread-onlycurrentThe crest factor per input 100x. the ratio of peak values to the effective value.
1.3.6.1.4.1.44568.1.1.7.1.1.15ColumninputPeakCurrentread-onlycurrentInput peak apparent 100x, RMS current; highest value since last reset of the peaks.
1.3.6.1.4.1.44568.1.1.7.1.1.16ColumninputMaxRatedAmpsread-onlycurrentMaximum rated current in A per input.
1.3.6.1.4.1.44568.1.1.7.1.1.17ColumninputThdread-onlycurrentTotal harmonic distortion in percent per phase 100x.
1.3.6.1.4.1.44568.1.1.7.1.1.18ColumninputTyperead-onlycurrentType of input.
1.3.6.1.4.1.44568.1.1.7.1.1.19ColumninputMinVoltageread-onlycurrentRMS voltage dip; lowest value since reset of dips.
1.3.6.1.4.1.44568.1.1.7.1.1.20ColumninputMaxVoltageread-onlycurrentRMS voltage peak; highest value since reset of peaks.
1.3.6.1.4.1.44568.1.1.7.1.1.21ColumninputPhaseread-onlycurrentA mapping to which phase each input is connected to.
1.3.6.1.4.1.44568.1.1.7.1.1.22ColumninputStatusUnbalancedread-onlycurrentThe input unbalanced. 100x.
1.3.6.1.4.1.44568.1.1.8NodedeviceOutlets
1.3.6.1.4.1.44568.1.1.8.1TabledeviceOutletsTablenot-accessiblecurrentA list to display status of Outlet.
1.3.6.1.4.1.44568.1.1.8.1.1RowdeviceOutletsEntrynot-accessiblecurrentA list to display status of Outlet.
1.3.6.1.4.1.44568.1.1.8.1.1.1ColumnoutletDeviceIndexnot-accessiblecurrentA unique value for each PDU. Its value ranges between 1 and the value of pduCount.
1.3.6.1.4.1.44568.1.1.8.1.1.2ColumnoutletIndexnot-accessiblecurrentAn outlet index in pdu.
1.3.6.1.4.1.44568.1.1.8.1.1.3ColumnoutletNameread-writecurrentUser configurable naming of individual outlets.
1.3.6.1.4.1.44568.1.1.8.1.1.4ColumnoutletEnergyTotalread-onlycurrentTotal kWh of selected outlet. This value is not resetable.
1.3.6.1.4.1.44568.1.1.8.1.1.5ColumnoutletEnergySubtotalread-onlycurrentkWh subtotal register of selected output.
1.3.6.1.4.1.44568.1.1.8.1.1.6ColumnoutletActivePowerread-onlycurrentOutput power (in W), MEASURED by the device x100 using current, voltage, and power factor measurements of an outlet.
1.3.6.1.4.1.44568.1.1.8.1.1.7ColumnoutletApparentPowerread-onlycurrentOutput VA (volt-amps, in VA) 100x, MEASURED by the device using current and voltage measurements of an outlet.
1.3.6.1.4.1.44568.1.1.8.1.1.8ColumnoutletReactivePowerread-onlycurrentReactive power (volt-amps reactive, in VAR) 100x, MEASURED by the device.
1.3.6.1.4.1.44568.1.1.8.1.1.9ColumnoutletPowerFactorread-onlycurrentPower factor x100 per outlet.
1.3.6.1.4.1.44568.1.1.8.1.1.10ColumnoutletActualCurrentread-onlycurrentActual apparent 100x, RMS current per outlet.
1.3.6.1.4.1.44568.1.1.8.1.1.11ColumnoutletActualVoltageread-onlycurrentActual voltage on outlet 100x.
1.3.6.1.4.1.44568.1.1.8.1.1.12ColumnoutletTyperead-onlycurrentOutlet types: 0: Unknown, 1: BS, 2: C13, 3: C13 IEC Lock, 4: C19, 5: C19 IEC Lock, 6: CEE 16A 1 phase, 7: CEE 16A 3 phase, 8: CEE 32A 1 phase, 9: CEE 32A 3 pha…
1.3.6.1.4.1.44568.1.1.8.1.1.13ColumnoutletPhaseread-onlycurrentA mapping to which input each outlet is connected to.
1.3.6.1.4.1.44568.1.1.8.1.1.14ColumnoutletCurrentStateread-writecurrentThe state of the outlet relay(s).
1.3.6.1.4.1.44568.1.1.8.1.1.15ColumnoutletApparentEnergyread-onlycurrentThe apparent accumulated energy VAh of each outlet 100x.
1.3.6.1.4.1.44568.1.1.8.1.1.16ColumnoutletCrestFactorread-onlycurrentThe crest factor per outlet 100x. the ratio of peak values to the effective value.
1.3.6.1.4.1.44568.1.1.8.1.1.17ColumnoutletPeakCurrentread-onlycurrentPeak apparent 100x, RMS current of an outlet; highest value since last reset of the peaks.
1.3.6.1.4.1.44568.1.1.8.1.1.18ColumnoutletMaxRatedAmpsread-onlycurrentOutlet maximum rated current in A.
1.3.6.1.4.1.44568.1.1.8.1.1.19ColumnoutletThdread-onlycurrentTotal harmonic distortion per outlet 100x.
1.3.6.1.4.1.44568.1.1.8.1.1.20ColumnoutletPowerCycleread-writecurrentWriting '1' will cause the outlet to power cycle.
1.3.6.1.4.1.44568.1.1.8.1.1.21ColumnoutletPowerCycleDelayread-writecurrentOutlet individual power cycle timer. This is the amount, in seconds.
1.3.6.1.4.1.44568.1.1.8.1.1.22ColumnoutletSwitchDelayread-writecurrentDelay before an individual outlet's relay switches on at power-up, in seconds.
1.3.6.1.4.1.44568.1.1.8.1.1.23ColumnoutletBranchread-onlycurrentA mapping to which branch each outlet is connected to.
1.3.6.1.4.1.44568.1.1.9NodedeviceBranches
1.3.6.1.4.1.44568.1.1.9.1TabledeviceBranchesTablenot-accessiblecurrentA list to display status of Branch.
1.3.6.1.4.1.44568.1.1.9.1.1RowdeviceBranchesEntrynot-accessiblecurrentA list to display status of Outlet.
1.3.6.1.4.1.44568.1.1.9.1.1.1ColumnbranchDeviceIndexnot-accessiblecurrentA unique value for each PDU. Its value ranges between 1 and the value of pduCount.
1.3.6.1.4.1.44568.1.1.9.1.1.2ColumnbranchIndexnot-accessiblecurrentA branch index in pdu.
1.3.6.1.4.1.44568.1.1.9.1.1.3ColumnbranchNameread-writecurrentUser configurable naming of a branch in 64 characters per branch.
1.3.6.1.4.1.44568.1.1.9.1.1.4ColumnbranchEnergyTotalread-onlycurrentBranch energy total measurement in kWh. This value is not resetable. 24-bit little-endian integer.
1.3.6.1.4.1.44568.1.1.9.1.1.5ColumnbranchEnergySubtotalread-onlycurrentBranch energy subtotal measurement in kWh. Reset to zero with [rsbmks]. 24-bit little-endian integer.
1.3.6.1.4.1.44568.1.1.9.1.1.6ColumnbranchActivePowerread-onlycurrentBranch power (in W) x100, MEASURED by the device using current, voltage, and power factor measurements of an branch.
1.3.6.1.4.1.44568.1.1.9.1.1.7ColumnbranchApparentPowerread-onlycurrentBranch VA (volt-amps) 100x, MEASURED by the device using current and voltage measurements of an branch.
1.3.6.1.4.1.44568.1.1.9.1.1.8ColumnbranchReactivePowerread-onlycurrentReactive power (volt-amps reactive, in VAR) of a branch x100, MEASURED by the device.
1.3.6.1.4.1.44568.1.1.9.1.1.9ColumnbranchPowerFactorread-onlycurrentThe effective power factor per branch 100x.
1.3.6.1.4.1.44568.1.1.9.1.1.10ColumnbranchActualCurrentread-onlycurrentActual apparent 100x, RMS current of a branch.
1.3.6.1.4.1.44568.1.1.9.1.1.11ColumnbranchActualVoltageread-onlycurrentThe actual voltage per branch x100.
1.3.6.1.4.1.44568.1.1.9.1.1.12ColumnbranchTyperead-onlycurrentBreaker type: 0: Unknown, 1: ETA (thermal, resettable), 2: HYMA (hydraulic magnetic), 3: MCB (thermal magnetic DIN), 4: MELT (small ceramic fuse), 5: REVOLVER …
1.3.6.1.4.1.44568.1.1.9.1.1.13ColumnbranchPhaseread-onlycurrentA mapping to which phase (input) each branch is connected to.
1.3.6.1.4.1.44568.1.1.9.1.1.14ColumnbranchStateread-onlycurrentPower state of the branch, usable for determining if a branch is currently tripped. 0 = OK, 1 = Tripped.
1.3.6.1.4.1.44568.1.1.9.1.1.15ColumnbranchApparentEnergyread-onlycurrentThe apparent accumulated energy VAh of each branch. 100x
1.3.6.1.4.1.44568.1.1.9.1.1.16ColumnbranchCrestFactorread-onlycurrentThe crest factor per branch 100x. the ratio of peak values to the effective value.
1.3.6.1.4.1.44568.1.1.9.1.1.17ColumnbranchPeakCurrentread-onlycurrentBranch peak apparent 100x, RMS current; highest value since last reset of the peaks.
1.3.6.1.4.1.44568.1.1.9.1.1.18ColumnbranchMaxRatedAmpsread-onlycurrentMaximum rated current in A per branch (representing the breakerfuse value).
1.3.6.1.4.1.44568.1.1.9.1.1.19ColumnbranchThdread-onlycurrentTotal harmonic distortion in percent per branch x100.
1.3.6.1.4.1.44568.1.1.9.1.1.20ColumnbranchMinVoltageread-onlycurrentRMS voltage dip per branch; lowest value since reset of dips.
1.3.6.1.4.1.44568.1.1.9.1.1.21ColumnbranchMaxVoltageread-onlycurrentRMS voltage peak per branch; highest value since reset of peaks.
1.3.6.1.4.1.44568.1.1.9.1.1.22ColumnbranchFrequencyread-onlycurrentFrequency in Hz per branch 100x.
1.3.6.1.4.1.44568.1.1.10NodedeviceTotals
1.3.6.1.4.1.44568.1.1.10.1TabledeviceTotalsTablenot-accessiblecurrentA list to display status of totals.
1.3.6.1.4.1.44568.1.1.10.1.1RowdeviceTotalsEntrynot-accessiblecurrentA list to display status of totals.
1.3.6.1.4.1.44568.1.1.10.1.1.1ColumntotalDeviceIndexnot-accessiblecurrentA unique value for each PDU. Its value ranges between 1 and the value of pduCount.
1.3.6.1.4.1.44568.1.1.10.1.1.2ColumntotalIndexnot-accessiblecurrentA total index in pdu.
1.3.6.1.4.1.44568.1.1.10.1.1.3ColumntotalEnergyread-onlycurrentTotal energy measurement in kWh. This value is not resetable.
1.3.6.1.4.1.44568.1.1.10.1.1.4ColumntotalActivePowerread-onlycurrentTotals power (in W) 100x, sum of phases.
1.3.6.1.4.1.44568.1.1.10.1.1.5ColumntotalApparentPowerread-onlycurrentTotals VA (volt-amps, in VA) 100x, sum of phases.
1.3.6.1.4.1.44568.1.1.10.1.1.6ColumntotalReactivePowerread-onlycurrentTotals reactive power (volt-amps reactive, in VAR) 100x, sum of phases.
1.3.6.1.4.1.44568.1.1.10.1.1.7ColumntotalActualCurrentread-onlycurrentSystem total actual apparent 100x, RMS current.
1.3.6.1.4.1.44568.1.1.10.1.1.8ColumntotalApparentEnergyread-onlycurrentThe total apparent energy in VAh 100x. This value is not resetable.
1.3.6.1.4.1.44568.1.1.10.1.1.9ColumntotalPeakCurrentread-onlycurrentSystem total peak apparent 100x, RMS current; highest value since last reset of the peaks.
1.3.6.1.4.1.44568.1.1.10.1.1.10ColumntotalNeutralPeakread-onlycurrentPeak neutral current 100x.
1.3.6.1.4.1.44568.1.1.10.1.1.11ColumntotalNeutralCurrentread-onlycurrentNeutral current measurement 100x. This is the sum of the neutral measurents channels: (only in three phase configs, one channel for all except 63A, then there …
1.3.6.1.4.1.44568.1.1.10.1.1.12ColumntotalOvervoltageProtectread-onlycurrentOvervoltage protection module measurement (0 = OK, 1 = Overvoltage detected).
1.3.6.1.4.1.44568.1.1.10.1.1.13ColumntotalResidualAcCurrentread-onlycurrentAC residual current measurement 100x.
1.3.6.1.4.1.44568.1.1.10.1.1.14ColumntotalResidualPeakread-onlycurrentPeak residual current 100x.
1.3.6.1.4.1.44568.1.1.10.1.1.15ColumntotalResidualCurrentread-onlycurrentResidual current measurement 100x.
1.3.6.1.4.1.44568.1.1.10.1.1.16ColumntotalResidualDcCurrentread-onlycurrentDC residual current measurement 100x.
1.3.6.1.4.1.44568.1.1.11NodedeviceSensors
1.3.6.1.4.1.44568.1.1.11.1TabledeviceSensorsTablenot-accessiblecurrentA list to display status of Sensors.
1.3.6.1.4.1.44568.1.1.11.1.1RowdeviceSensorsEntrynot-accessiblecurrentA list to display status of Sensor.
1.3.6.1.4.1.44568.1.1.11.1.1.1ColumnsensorDeviceIndexnot-accessiblecurrentA unique value for each PDU. Its value ranges between 1 and the value of pduCount.
1.3.6.1.4.1.44568.1.1.11.1.1.2ColumnsensorIndexnot-accessiblecurrentA port index in pdu.
1.3.6.1.4.1.44568.1.1.11.1.1.3ColumnsensorNameread-writecurrentThe sensor port name.
1.3.6.1.4.1.44568.1.1.11.1.1.4ColumnsensorValueread-onlycurrentThe sensor value 10x. E.g. a temperature of 25.7 C is passed as 257.
1.3.6.1.4.1.44568.1.1.11.1.1.5ColumnsensorTyperead-onlycurrentThe sensor type string.
1.3.6.1.4.1.44568.1.1.11.1.1.6ColumnsensorSerialNumberread-onlycurrentSerial number of the sensor.
1.3.6.1.4.1.44568.1.1.11.1.1.7ColumnsensorSourceread-onlycurrentSource of the sensor.
1.3.6.1.4.1.44568.1.1.11.1.1.8ColumnsensorStateread-onlycurrentState of the sensor.
1.3.6.1.4.1.44568.1.1.11.1.1.9ColumnsensorUnitread-onlycurrentSensor measurement unit.
1.3.6.1.4.1.44568.1.1.40NodedeviceDigitalInputs
1.3.6.1.4.1.44568.1.1.40.1TabledeviceDigitalInputsTablenot-accessiblecurrentA list to display status of Digital Input.
1.3.6.1.4.1.44568.1.1.40.1.1RowdeviceDigitalInputsEntrynot-accessiblecurrentA list to display status of Digital Input.
1.3.6.1.4.1.44568.1.1.40.1.1.1ColumndigitalInputDeviceIndexnot-accessiblecurrentA unique value for each PDU. Its value ranges between 1 and the value of pduCount.
1.3.6.1.4.1.44568.1.1.40.1.1.2ColumndigitalInputIndexnot-accessiblecurrentA port index in pdu.
1.3.6.1.4.1.44568.1.1.40.1.1.3ColumndigitalInputNameread-writecurrentThe digital input name.
1.3.6.1.4.1.44568.1.1.40.1.1.6ColumndigitalInputSerialNumberread-onlycurrentSerial number of the digital input.
1.3.6.1.4.1.44568.1.1.40.1.1.7ColumndigitalInputSourceread-onlycurrentSource of the digital input.
1.3.6.1.4.1.44568.1.1.40.1.1.8ColumndigitalInputStateread-onlycurrentState of the digital input.
1.3.6.1.4.1.44568.1.1.40.1.1.9ColumndigitalInputValueread-onlycurrentThe digital input state
1.3.6.1.4.1.44568.1.1.50NodedeviceDigitalOutputs
1.3.6.1.4.1.44568.1.1.50.1TabledeviceDigitalOutputsTablenot-accessiblecurrentA list to display status of Digital Output.
1.3.6.1.4.1.44568.1.1.50.1.1RowdeviceDigitalOutputsEntrynot-accessiblecurrentA list to display status of Digital Output.
1.3.6.1.4.1.44568.1.1.50.1.1.1ColumndigitalOutputDeviceIndexnot-accessiblecurrentA unique value for each PDU. Its value ranges between 1 and the value of pduCount.
1.3.6.1.4.1.44568.1.1.50.1.1.2ColumndigitalOutputIndexnot-accessiblecurrentDigital Output index in pdu.
1.3.6.1.4.1.44568.1.1.50.1.1.3ColumndigitalOutputNameread-writecurrentThe digital output port name.
1.3.6.1.4.1.44568.1.1.50.1.1.6ColumndigitalOutputSerialNumberread-onlycurrentSerial number of the digital output.
1.3.6.1.4.1.44568.1.1.50.1.1.7ColumndigitalOutputSourceread-onlycurrentSource of the digital output.
1.3.6.1.4.1.44568.1.1.50.1.1.8ColumndigitalOutputStateread-onlycurrentState of the digital output.
1.3.6.1.4.1.44568.1.1.50.1.1.9ColumndigitalOutputValueread-writecurrentThe digital outlet switch state.
1.3.6.1.4.1.44568.1.1.100NodedcStatus
1.3.6.1.4.1.44568.1.1.100.1TabledcStatusTablenot-accessiblecurrentA list to display status of Data center.
1.3.6.1.4.1.44568.1.1.100.1.1RowdcStatusEntrynot-accessiblecurrentA list to display status of Data Center.
1.3.6.1.4.1.44568.1.1.100.1.1.1ColumndcStatusIndexnot-accessiblecurrentA unique value for each PDU. Its value ranges between 1 and the value of pduCount.
1.3.6.1.4.1.44568.1.1.100.1.1.2ColumndcStatusNameread-onlycurrentThe datacenter name
1.3.6.1.4.1.44568.1.1.100.1.1.3ColumndcStatusStateread-onlycurrentThe datacenter state .e.g normal, etc.
1.3.6.1.4.1.44568.1.1.100.1.1.4ColumndcStatusKwhTotalread-onlycurrentThe data center KWhTotal.
1.3.6.1.4.1.44568.1.1.100.1.1.5ColumndcStatusPowerWattsread-onlycurrentThe datacenter power Watt. 100x.
1.3.6.1.4.1.44568.1.1.100.1.1.6ColumndcStatusPowerVAread-onlycurrentThe daracenter power VA. 100x.
1.3.6.1.4.1.44568.1.1.100.1.1.7ColumndcStatusCurrentread-onlycurrentThe data center current. 100x.
1.3.6.1.4.1.44568.1.1.100.1.1.8ColumndcStatusVoltageread-onlycurrentThe data center Voltage. 100x.
1.3.6.1.4.1.44568.1.1.100.1.1.9ColumndcStatusTempread-onlycurrentThe temperature. 10x.
1.3.6.1.4.1.44568.1.1.100.1.1.10ColumndcStatusHumidityread-onlycurrentThe humidity. 10x.
1.3.6.1.4.1.44568.1.1.100.1.1.11ColumndcStatusRcmCurrentread-onlycurrentThe residual current in mA
1.3.6.1.4.1.44568.1.1.100.1.1.12ColumndcStatusRcmCurrentAcread-onlycurrentThe residual current AC component in mA
1.3.6.1.4.1.44568.1.1.100.1.1.13ColumndcStatusRcmCurrentDcread-onlycurrentThe residual current DC component in mA
1.3.6.1.4.1.44568.1.1.100.1.1.14ColumndcStatusL1read-onlycurrentThe data center L1current. 100x.
1.3.6.1.4.1.44568.1.1.100.1.1.15ColumndcStatusL2read-onlycurrentThe data center L2 current. 100x.
1.3.6.1.4.1.44568.1.1.100.1.1.16ColumndcStatusL3read-onlycurrentThe data center L3 current. 100x.
1.3.6.1.4.1.44568.1.1.110NoderoomStatus
1.3.6.1.4.1.44568.1.1.110.1TableroomStatusTablenot-accessiblecurrentA list to display status of rooms.
1.3.6.1.4.1.44568.1.1.110.1.1RowroomStatusEntrynot-accessiblecurrentA list to display status of a room.
1.3.6.1.4.1.44568.1.1.110.1.1.1ColumnroomStatusIndexnot-accessiblecurrentA unique value for each PDU. Its value ranges between 1 and the value of pduCount.
1.3.6.1.4.1.44568.1.1.110.1.1.2ColumnroomStatusNameread-onlycurrentThe room name
1.3.6.1.4.1.44568.1.1.110.1.1.3ColumnroomStatusStateread-onlycurrentThe room statee.g. normal, degraded
1.3.6.1.4.1.44568.1.1.110.1.1.4ColumnroomDcStatusNameread-onlycurrentThe datacenter name in which this room is
1.3.6.1.4.1.44568.1.1.110.1.1.5ColumnroomStatusKwhTotalread-onlycurrentThe room KWhTotal.
1.3.6.1.4.1.44568.1.1.110.1.1.6ColumnroomStatusPowerWattsread-onlycurrentThe room power Watt. 100x.
1.3.6.1.4.1.44568.1.1.110.1.1.7ColumnroomStatusPowerVAread-onlycurrentThe room power VA. 100x.
1.3.6.1.4.1.44568.1.1.110.1.1.8ColumnroomStatusCurrentread-onlycurrentThe room current. 100x.
1.3.6.1.4.1.44568.1.1.110.1.1.9ColumnroomStatusVoltageread-onlycurrentThe room Voltage. 100x.
1.3.6.1.4.1.44568.1.1.110.1.1.10ColumnroomStatusTempread-onlycurrentThe temperature. 10x.
1.3.6.1.4.1.44568.1.1.110.1.1.11ColumnroomStatusHumidityread-onlycurrentThe humidity. 10x.
1.3.6.1.4.1.44568.1.1.110.1.1.12ColumnroomStatusRcmCurrentread-onlycurrentThe residual current in mA
1.3.6.1.4.1.44568.1.1.110.1.1.13ColumnroomStatusRcmCurrentAcread-onlycurrentThe residual current AC component in mA
1.3.6.1.4.1.44568.1.1.110.1.1.14ColumnroomStatusRcmCurrentDcread-onlycurrentThe residual current DC component in mA
1.3.6.1.4.1.44568.1.1.110.1.1.15ColumnroomStatusL1read-onlycurrentThe room L1current. 100x.
1.3.6.1.4.1.44568.1.1.110.1.1.16ColumnroomStatusL2read-onlycurrentThe room L2 current. 100x.
1.3.6.1.4.1.44568.1.1.110.1.1.17ColumnroomStatusL3read-onlycurrentThe room L3 current. 100x.
1.3.6.1.4.1.44568.1.1.120NodeaisleStatus
1.3.6.1.4.1.44568.1.1.120.1TableaisleStatusTablenot-accessiblecurrentA list to display status of aisle.
1.3.6.1.4.1.44568.1.1.120.1.1RowaisleStatusEntrynot-accessiblecurrentA list to display status of an aisle.
1.3.6.1.4.1.44568.1.1.120.1.1.1ColumnaisleStatusIndexnot-accessiblecurrentA unique value for each PDU. Its value ranges between 1 and the value of pduCount.
1.3.6.1.4.1.44568.1.1.120.1.1.2ColumnaisleStatusNameread-onlycurrentThe aisle name
1.3.6.1.4.1.44568.1.1.120.1.1.3ColumnaisleStatusStateread-onlycurrentThe aisle statee.g. normal, degraded
1.3.6.1.4.1.44568.1.1.120.1.1.4ColumnaisleDcStatusNameread-onlycurrentThe datacenter name in which this room is
1.3.6.1.4.1.44568.1.1.120.1.1.5ColumnaisleRoomStatusNameread-onlycurrentThe room name in which this aisle is
1.3.6.1.4.1.44568.1.1.120.1.1.6ColumnaisleStatusKwhTotalread-onlycurrentThe aisle KWhTotal.
1.3.6.1.4.1.44568.1.1.120.1.1.7ColumnaisleStatusPowerWattsread-onlycurrentThe aisle power Watt. 100x.
1.3.6.1.4.1.44568.1.1.120.1.1.8ColumnaisleStatusPowerVAread-onlycurrentThe aisle power VA. 100x.
1.3.6.1.4.1.44568.1.1.120.1.1.9ColumnaisleStatusCurrentread-onlycurrentThe aisle current. 100x.
1.3.6.1.4.1.44568.1.1.120.1.1.10ColumnaisleStatusVoltageread-onlycurrentThe aisle Voltage. 100x.
1.3.6.1.4.1.44568.1.1.120.1.1.11ColumnaisleStatusTempread-onlycurrentThe aisle temperature. 10x.
1.3.6.1.4.1.44568.1.1.120.1.1.12ColumnaisleStatusHumidityread-onlycurrentThe aisle humidity. 10x.
1.3.6.1.4.1.44568.1.1.120.1.1.13ColumnaisleStatusRcmCurrentread-onlycurrentThe residual current in mA
1.3.6.1.4.1.44568.1.1.120.1.1.14ColumnaisleStatusRcmCurrentAcread-onlycurrentThe residual current AC component in mA
1.3.6.1.4.1.44568.1.1.120.1.1.15ColumnaisleStatusRcmCurrentDcread-onlycurrentThe residual current DC component in mA
1.3.6.1.4.1.44568.1.1.120.1.1.16ColumnaisleStatusL1read-onlycurrentThe aisle L1current. 100x.
1.3.6.1.4.1.44568.1.1.120.1.1.17ColumnaisleStatusL2read-onlycurrentThe aisle L2 current. 100x.
1.3.6.1.4.1.44568.1.1.120.1.1.18ColumnaisleStatusL3read-onlycurrentThe aisle L3 current. 100x.
1.3.6.1.4.1.44568.1.1.130NoderackStatus
1.3.6.1.4.1.44568.1.1.130.1TablerackStatusTablenot-accessiblecurrentA list to display status of rack.
1.3.6.1.4.1.44568.1.1.130.1.1RowrackStatusEntrynot-accessiblecurrentA list to display status of an rack.
1.3.6.1.4.1.44568.1.1.130.1.1.1ColumnrackStatusIndexnot-accessiblecurrentA unique value for each PDU. Its value ranges between 1 and the value of pduCount.
1.3.6.1.4.1.44568.1.1.130.1.1.2ColumnrackStatusNameread-onlycurrentThe rack name
1.3.6.1.4.1.44568.1.1.130.1.1.3ColumnrackStatusStateread-onlycurrentThe rack state.g. normal, degraded
1.3.6.1.4.1.44568.1.1.130.1.1.4ColumnrackDcStatusNameread-onlycurrentThe datacenter name in which this room is
1.3.6.1.4.1.44568.1.1.130.1.1.5ColumnrackRoomStatusNameread-onlycurrentThe room name in which this aisle is
1.3.6.1.4.1.44568.1.1.130.1.1.6ColumnrackAisleStatusNameread-onlycurrentThe room name in which this aisle is
1.3.6.1.4.1.44568.1.1.130.1.1.7ColumnrackStatusKwhTotalread-onlycurrentThe rack KWhTotal.
1.3.6.1.4.1.44568.1.1.130.1.1.8ColumnrackStatusPowerWattsread-onlycurrentThe rack power Watt. 100x.
1.3.6.1.4.1.44568.1.1.130.1.1.9ColumnrackStatusPowerVAread-onlycurrentThe rack power VA. 100x.
1.3.6.1.4.1.44568.1.1.130.1.1.10ColumnrackStatusCurrentread-onlycurrentThe rack current. 100x.
1.3.6.1.4.1.44568.1.1.130.1.1.11ColumnrackStatusVoltageread-onlycurrentThe rack Voltage. 100x.
1.3.6.1.4.1.44568.1.1.130.1.1.12ColumnrackStatusTempread-onlycurrentThe rack temperature. 10x.
1.3.6.1.4.1.44568.1.1.130.1.1.13ColumnrackStatusHumidityread-onlycurrentThe rack humidity. 10x.
1.3.6.1.4.1.44568.1.1.130.1.1.14ColumnrackStatusRcmCurrentread-onlycurrentThe residual current in mA
1.3.6.1.4.1.44568.1.1.130.1.1.15ColumnrackStatusRcmCurrentAcread-onlycurrentThe residual current AC component in mA
1.3.6.1.4.1.44568.1.1.130.1.1.16ColumnrackStatusRcmCurrentDcread-onlycurrentThe residual current DC component in mA
1.3.6.1.4.1.44568.1.1.130.1.1.17ColumnrackStatusL1read-onlycurrentThe rack L1current. 100x.
1.3.6.1.4.1.44568.1.1.130.1.1.18ColumnrackStatusL2read-onlycurrentThe rack L2 current. 100x.
1.3.6.1.4.1.44568.1.1.130.1.1.19ColumnrackStatusL3read-onlycurrentThe rack L3 current. 100x.
1.3.6.1.4.1.44568.1.1.140NoderackDeviceStatus
1.3.6.1.4.1.44568.1.1.140.1TablerackDeviceStatusTablenot-accessiblecurrentA list to display status of rackDevice.
1.3.6.1.4.1.44568.1.1.140.1.1RowrackDeviceStatusEntrynot-accessiblecurrentA list to display status of a rackDevice.
1.3.6.1.4.1.44568.1.1.140.1.1.1ColumnrackDeviceStatusIndexnot-accessiblecurrentA unique value for each PDU. Its value ranges between 1 and the value of pduCount.
1.3.6.1.4.1.44568.1.1.140.1.1.2ColumnrackDeviceStatusNameread-onlycurrentThe rack device name
1.3.6.1.4.1.44568.1.1.140.1.1.3ColumnrackDeviceStatusStateread-onlycurrentThe rackDevice state.g. normal, degraded
1.3.6.1.4.1.44568.1.1.140.1.1.4ColumnrackDeviceDcStatusNameread-onlycurrentThe datacenter name in which this rack Device is
1.3.6.1.4.1.44568.1.1.140.1.1.5ColumnrackDeviceRoomStatusNameread-onlycurrentThe rackDevice in tha rack inroom name in which this aisle is
1.3.6.1.4.1.44568.1.1.140.1.1.6ColumnrackDeviceAisleStatusNameread-onlycurrentThe rackDevice in tha rack inroom name in which this aisle is
1.3.6.1.4.1.44568.1.1.140.1.1.7ColumnrackDeviceRackStatusNameread-onlycurrentThe rackDevice in tha rack inroom name in which this aisle is
1.3.6.1.4.1.44568.1.1.140.1.1.8ColumnrackDeviceStatusKwhTotalread-onlycurrentThe aisle KWhTotal.
1.3.6.1.4.1.44568.1.1.140.1.1.9ColumnrackDeviceStatusPowerWattsread-onlycurrentThe aisle power Watt. 100x.
1.3.6.1.4.1.44568.1.1.140.1.1.10ColumnrackDeviceStatusPowerVAread-onlycurrentThe aisle power VA. 100x.
1.3.6.1.4.1.44568.1.1.140.1.1.11ColumnrackDeviceStatusCurrentread-onlycurrentThe aisle current. 100x.
1.3.6.1.4.1.44568.1.1.140.1.1.12ColumnrackDeviceStatusVoltageread-onlycurrentThe aisle Voltage. 100x.
1.3.6.1.4.1.44568.1.1.140.1.1.13ColumnrackDeviceStatusTempread-onlycurrentThe aisle temperature. 10x.
1.3.6.1.4.1.44568.1.1.140.1.1.14ColumnrackDeviceStatusHumidityread-onlycurrentThe aisle humidity. 10x.
1.3.6.1.4.1.44568.1.1.140.1.1.15ColumnrackDeviceStatusSwitchStateread-onlycurrentThe port switch state.
1.3.6.1.4.1.44568.1.1.140.1.1.16ColumnrackDeviceStatusRcmCurrentread-onlycurrentThe residual current in mA
1.3.6.1.4.1.44568.1.1.140.1.1.17ColumnrackDeviceStatusRcmCurrentAcread-onlycurrentThe residual current AC component in mA
1.3.6.1.4.1.44568.1.1.140.1.1.18ColumnrackDeviceStatusRcmCurrentDcread-onlycurrentThe residual current DC component in mA
1.3.6.1.4.1.44568.1.1.140.1.1.19ColumnrackDeviceStatusL1read-onlycurrentThe rack device L1 current. 100x.
1.3.6.1.4.1.44568.1.1.140.1.1.20ColumnrackDeviceStatusL2read-onlycurrentThe rack device L2 current. 100x.
1.3.6.1.4.1.44568.1.1.140.1.1.21ColumnrackDeviceStatusL3read-onlycurrentThe rack device L3 current. 100x.
1.3.6.1.4.1.44568.1.1.141NoderackDeviceConfig
1.3.6.1.4.1.44568.1.1.141.1TablerackDeviceConfigTablenot-accessiblecurrentA list to change status of RackDevice switch.
1.3.6.1.4.1.44568.1.1.141.1.1RowrackDeviceConfigEntrynot-accessiblecurrentA list to edit status of Switch.
1.3.6.1.4.1.44568.1.1.141.1.1.1ColumnrackDeviceConfigPduIndexnot-accessiblecurrentA unique value for each group.
1.3.6.1.4.1.44568.1.1.141.1.1.2ColumnrackDeviceConfigSwitchStateread-writecurrentThe rack Device switch state.
1.3.6.1.4.1.44568.1.1.200NodecustomEntityStatus
1.3.6.1.4.1.44568.1.1.500NodedeviceRuleStatus
1.3.6.1.4.1.44568.1.1.510NodelogicalRuleStatus
1.3.6.1.4.1.44568.1.1.600NodecurrentUserStatus
1.3.6.1.4.1.44568.1.1.600.1TablecurrentUserStatusTablenot-accessiblecurrentA list to display of current logged in users.
1.3.6.1.4.1.44568.1.1.600.1.1RowcurrentUserStatusEntrynot-accessiblecurrentA list to display status of Inlet.
1.3.6.1.4.1.44568.1.1.600.1.1.1ColumncurrentUserStatusIndexnot-accessiblecurrentA unique value for each PDU. Its value ranges between 1 and the value of pduCount.
1.3.6.1.4.1.44568.1.1.600.1.1.2ColumncurrentUserStatusNameread-onlycurrentThe logged in user name.
1.3.6.1.4.1.44568.1.1.600.1.1.3ColumncurrentUserStatusRoleread-onlycurrentThe role of this user
1.3.6.1.4.1.44568.1.1.700Nodewarnings
1.3.6.1.4.1.44568.1.1.700.1TablewarningsTablenot-accessiblecurrentA list to display of current warnings.
1.3.6.1.4.1.44568.1.1.700.1.1RowwarningsEntrynot-accessiblecurrentA list to display warnings.
1.3.6.1.4.1.44568.1.1.700.1.1.1ColumnwarningsIndexnot-accessiblecurrentA unique value for each warning
1.3.6.1.4.1.44568.1.1.700.1.1.2ColumnwarningsTopLevelTyperead-onlycurrentThis is a group or sensor
1.3.6.1.4.1.44568.1.1.700.1.1.3ColumnwarningsTopLevelNameread-onlycurrentThis is the group or device name
1.3.6.1.4.1.44568.1.1.700.1.1.4ColumnwarningsPortTyperead-onlycurrentThis is i, o s for device.
1.3.6.1.4.1.44568.1.1.700.1.1.5ColumnwarningsPortIndexread-onlycurrentThis is zero based port index
1.3.6.1.4.1.44568.1.1.700.1.1.6ColumnwarningsPortVariableread-onlycurrentvoltage, Current, etc.
1.3.6.1.4.1.44568.1.1.700.1.1.7ColumnwarningsValueread-onlycurrentThe value exceeding warning limit. 100x
1.3.6.1.4.1.44568.1.1.800Nodecriticals
1.3.6.1.4.1.44568.1.1.800.1TablecriticalsTablenot-accessiblecurrentA list to display of current criticals.
1.3.6.1.4.1.44568.1.1.800.1.1RowcriticalsEntrynot-accessiblecurrentA list to display warnings.
1.3.6.1.4.1.44568.1.1.800.1.1.1ColumncriticalsIndexnot-accessiblecurrentA unique value for each critical
1.3.6.1.4.1.44568.1.1.800.1.1.2ColumncriticalsTopLevelTyperead-onlycurrentThis is a group type or sensor
1.3.6.1.4.1.44568.1.1.800.1.1.3ColumncriticalsTopLevelNameread-onlycurrentThis is the group or device name
1.3.6.1.4.1.44568.1.1.800.1.1.4ColumncriticalsPortTyperead-onlycurrentThis is i, o s for device.
1.3.6.1.4.1.44568.1.1.800.1.1.5ColumncriticalsPortIndexread-onlycurrentThis is zero based port index
1.3.6.1.4.1.44568.1.1.800.1.1.6ColumncriticalsPortVariableread-onlycurrentvoltage, Current, etc.
1.3.6.1.4.1.44568.1.1.800.1.1.7ColumncriticalsValueread-onlycurrentThe value exceeding critical limit. 100x
1.3.6.1.4.1.44568.1.1.900Nodetriggers
1.3.6.1.4.1.44568.1.1.900.1ScalarnotificationTriggerValueread-onlycurrentThe notification value causing trap
1.3.6.1.4.1.44568.1.1.900.2ScalarnotificationTriggerPortTyperead-onlycurrentThe port that causes the notification value causing trap
1.3.6.1.4.1.44568.1.1.900.3ScalarnotificationTriggerPortNumberread-onlycurrentThe notification value causing trap
1.3.6.1.4.1.44568.1.1.900.4ScalarnotificationTriggerParameterread-onlycurrentVoltage, Current, etc.
1.3.6.1.4.1.44568.1.10NodegateConformance
1.3.6.1.4.1.44568.1.10.1NodegateCompliances
1.3.6.1.4.1.44568.1.10.1.1CompliancegateCompliancecurrentvalues needed for notification values, etc.
1.3.6.1.4.1.44568.1.10.2NodegateGroups
1.3.6.1.4.1.44568.1.10.2.1GroupsystemStatusGroupcurrentA collection of objects providing identification information about the pdu.
1.3.6.1.4.1.44568.1.10.2.2GroupdeviceIdentificationGroupcurrentA collection of objects providing identification information about the pdu.
1.3.6.1.4.1.44568.1.10.2.3GroupdeviceConfigGroupcurrentA collection of objects providing identification information about the pdu.
1.3.6.1.4.1.44568.1.10.2.4GroupdeviceSettingsGroupcurrentA collection of configurable values on a PDU.
1.3.6.1.4.1.44568.1.10.2.5GroupdeviceDaisychainGroupcurrentA collection of configurable values on a PDU.
1.3.6.1.4.1.44568.1.10.2.6GroupdeviceResetGroupcurrentA collection of configurable values on a PDU.
1.3.6.1.4.1.44568.1.10.2.7GroupdeviceInputsGroupcurrentA collection of objects providing identification information about the pdu.
1.3.6.1.4.1.44568.1.10.2.8GroupdeviceOutletsGroupcurrentA collection of objects providing outlet port information about the pdu.
1.3.6.1.4.1.44568.1.10.2.9GroupdeviceBranchesGroupcurrentA collection of objects providing branch information about the pdu.
1.3.6.1.4.1.44568.1.10.2.10GroupdeviceTotalsGroupcurrentA collection of objects providing total information about the pdu.
1.3.6.1.4.1.44568.1.10.2.11GroupdeviceSensorsGroupcurrentA collection of objects providing Sensor information about the pdu.
1.3.6.1.4.1.44568.1.10.2.14GroupdeviceDigitalInputsGroupcurrentA collection of objects providing Digital Input port information about the pdu.
1.3.6.1.4.1.44568.1.10.2.16GroupdeviceDigitalOutputsGroupcurrentA collection of objects providing Digital Output port information about the pdu.
1.3.6.1.4.1.44568.1.10.2.18GroupdcStatusGroupcurrentA collection of objects providing Data center information about the pdu.
1.3.6.1.4.1.44568.1.10.2.19GrouproomStatusGroupcurrentA collection of objects providing room information.
1.3.6.1.4.1.44568.1.10.2.20GroupaisleStatusGroupcurrentA collection of objects providing room information.
1.3.6.1.4.1.44568.1.10.2.21GrouprackStatusGroupcurrentA collection of objects providing rack information.
1.3.6.1.4.1.44568.1.10.2.22GrouprackDeviceStatusGroupcurrentA collection of objects providing room information.
1.3.6.1.4.1.44568.1.10.2.23GrouprackDeviceConfigGroupcurrentA switch group
1.3.6.1.4.1.44568.1.10.2.24GroupcurrentUserStatusGroupcurrentA collection of objects providing identification information about the pdu.
1.3.6.1.4.1.44568.1.10.2.25GroupwarningsGroupcurrentA collection of warning objects.
1.3.6.1.4.1.44568.1.10.2.26GroupcriticalsGroupcurrentA collection of warning objects.
1.3.6.1.4.1.44568.1.10.2.27GrouptrapsGroupcurrentA collection of traps.
1.3.6.1.4.1.44568.1.10.2.28GroupnotificationTriggerGroupcurrentA collection of objects providing extra info in notification.