SCTE-HMS-PS-MIB
61 objects
No module-level DESCRIPTION found.
Imported Objects
| RFC-1212 | OBJECT-TYPE |
| RFC1213-MIB | DisplayString |
| SCTE-HMS-ROOTS | psIdent |
| OID | Name | Access | Status | Description |
|---|---|---|---|---|
| 1.3.6.1.4.1.5591.1.4.1 | ScalarpsMonitored | read-only | mandatory | Number of power supply connected to this NE. |
| 1.3.6.1.4.1.5591.1.4.2 | TablepsDeviceTable | not-accessible | mandatory | Table containing information about the individual power supplies being monitored |
| 1.3.6.1.4.1.5591.1.4.2.1 | RowpsDeviceEntry | not-accessible | mandatory | List of information about each power supply being monitored. |
| 1.3.6.1.4.1.5591.1.4.2.1.1 | ColumnpsDeviceAddress | read-only | mandatory | Index into the psDeviceTable.Address of this device on the RS-485 path |
| 1.3.6.1.4.1.5591.1.4.2.1.2 | ColumnpsProtocolVersion | read-only | mandatory | Version of the SCTE HMS protocol implemented in the monitored equipment. The 'Protocol Version' implementation will comply with the defined protocol in the SCT… |
| 1.3.6.1.4.1.5591.1.4.2.1.3 | ColumnpsSoftwareVersion | read-only | mandatory | The content of this field is vendor specific. The intent is to provide a text representation of the power supply or generator system software version. Any prin… |
| 1.3.6.1.4.1.5591.1.4.2.1.4 | ColumnpsDeviceId | read-only | mandatory | The content of this field is vendor specific. The intent is to provide manufacturer and/or product specific ASCII text information that will propagate to the m… |
| 1.3.6.1.4.1.5591.1.4.2.1.5 | ColumnpsBatteries | read-only | mandatory | Current number of batteries per battery string. |
| 1.3.6.1.4.1.5591.1.4.2.1.6 | ColumnpsBatteryStrings | read-only | mandatory | Current number of battery strings. |
| 1.3.6.1.4.1.5591.1.4.2.1.7 | ColumnpsTempSensors | read-only | mandatory | Number of Battery temperature sensors. |
| 1.3.6.1.4.1.5591.1.4.2.1.8 | ColumnpsOutputs | read-only | mandatory | Number of power supply outputs. |
| 1.3.6.1.4.1.5591.1.4.2.1.9 | ColumnpsBatteryCurrentSupport | read-only | mandatory | Bit Map that defines if battery current is measured in this installation. Bit set means this particular string supports this measurement. Bits Addresses 0 Not … |
| 1.3.6.1.4.1.5591.1.4.2.1.10 | ColumnpsFloatCurrentSupport | read-only | mandatory | Bit Map that defines if float current is measured in this installation. Bit set means this particular string supports this measurement. Bits Addresses 0 Not us… |
| 1.3.6.1.4.1.5591.1.4.2.1.11 | ColumnpsOutputVoltageSupport | read-only | mandatory | Defines if power supply supports monitoring of output voltage 1 = No support. Discard associated value in Get_Power_Supply_Data response. 2 = Field is supporte… |
| 1.3.6.1.4.1.5591.1.4.2.1.12 | ColumnpsInputVoltageSupport | read-only | mandatory | Defines if power supply supports monitoring of input or line voltage 1 = No support. Discard associated value in Get_Power_Supply_Data response. 2 = Field is s… |
| 1.3.6.1.4.1.5591.1.4.2.1.13 | ColumnpsPowerSupplyTest | read-only | mandatory | Defines if power supply supports the remote test feature: 1 = Function not supported. 2 - Function is supported. |
| 1.3.6.1.4.1.5591.1.4.2.1.14 | ColumnpsMajorAlarmSupport | read-only | mandatory | Defines if the power supply supports the major alarm indicator: 1 = No support. Discard associated value in Get_Power_Supply_Data response. 2 = Field is suppor… |
| 1.3.6.1.4.1.5591.1.4.2.1.15 | ColumnpsMinorAlarmSupport | read-only | mandatory | Defines if the power supply supports the minor alarm indicator: 1 = No support. Discard associated value in Get_Power_Supply_Data response. 2 = Field is suppor… |
| 1.3.6.1.4.1.5591.1.4.2.1.16 | ColumnpsTamperSupport | read-only | mandatory | Defines if the enclosure door switch is installed in this location: 1 = No support. Discard associated value in Get_Power_Supply_Data response. 2 = Field is su… |
| 1.3.6.1.4.1.5591.1.4.2.1.17 | ColumnpsBatteryVoltageSupport | read-only | mandatory | Defines the if batteries or string voltage are available: 1 = No battery voltage monitoring is available. 2 = Only full string battery voltage is available. 3 … |
| 1.3.6.1.4.1.5591.1.4.2.1.18 | ColumnpsOutputPowerSupport | read-only | mandatory | Defines if the output power measurement is supported 1 = No support. Discard associated value in Get_Power_Supply_Data response. 2 = Field is supported in this… |
| 1.3.6.1.4.1.5591.1.4.2.1.19 | ColumnpsOutputFrequencySupport | read-only | mandatory | Defines if the output frequency measurement is supported 1 = No support. Discard associated value in Get_Power_Supply_Data response. 2 = Field is supported in … |
| 1.3.6.1.4.1.5591.1.4.2.1.20 | ColumnpsInputCurrentSupport | read-only | mandatory | Defines if the input current measurement is supported 1 = No support. Discard associated value in Get_Power_Supply_Data response. 2 = Field is supported in thi… |
| 1.3.6.1.4.1.5591.1.4.2.1.21 | ColumnpsInputPowerSupport | read-only | mandatory | Defines if the input power measurement is supported 1 = No support. Discard associated value in Get_Power_Supply_Data response. 2 = Field is supported in this … |
| 1.3.6.1.4.1.5591.1.4.2.1.22 | ColumnpsOutputVoltage | read-only | mandatory | Power supply output voltage in 1/100 Volts units. This RMS value is common for all outputs in a multiple output system. This item requires an entry in the prop… |
| 1.3.6.1.4.1.5591.1.4.2.1.23 | ColumnpsInputVoltage | read-only | optional | Scaled representation of input 'line' or 'grid' voltage. This is an RMS value in 1/100 Volts units. This item requires an entry in the properties MIB. |
| 1.3.6.1.4.1.5591.1.4.2.1.24 | ColumnpsInverterStatus | read-only | optional | Status of power supply inverter. Enumerated value indicates current status of inverter. 1 = OFF, 2 = ON: AC Line Fail, 3 = ON: Local Test Cycle, 4 = ON: Remote… |
| 1.3.6.1.4.1.5591.1.4.2.1.25 | ColumnpsMajorAlarm | read-only | optional | Service has been dropped or a service interruption is imminent. Indicates that an immediate truck roll is appropriate. Specific alarms and alarm nomenclature v… |
| 1.3.6.1.4.1.5591.1.4.2.1.26 | ColumnpsMinorAlarm | read-only | optional | A non-service effecting condition has occurred and should be monitored. Specific alarms and alarm nomenclature varies between vendors. Vendors should disclose … |
| 1.3.6.1.4.1.5591.1.4.2.1.27 | ColumnpsTamper | read-only | optional | Indicates status of enclosure door. This notification is NOT included in the 'Major' or 'Minor' alarm fields. Individual users / installations must determine i… |
| 1.3.6.1.4.1.5591.1.4.2.1.28 | ColumnpsTotalStringVoltage | read-only | optional | Scaled representation of the full battery string in 1/100 Volts units. This item requires an entry in the properties MIB. |
| 1.3.6.1.4.1.5591.1.4.2.1.29 | ColumnpsEquipmentControl | read-write | optional | Equipment control 1 = Discontinue inverter operation, 2 = Begin inverter operation |
| 1.3.6.1.4.1.5591.1.4.2.1.30 | ColumnpsPowerOut | read-only | optional | Representation of power supply output power in 1 W. This item requires an entry in the properties MIB. |
| 1.3.6.1.4.1.5591.1.4.2.1.31 | ColumnpsFrequencyOut | read-only | optional | Scaled representation of the power supply output frequency in 1/100 Hz. This item requires an entry in the properties MIB. |
| 1.3.6.1.4.1.5591.1.4.2.1.32 | ColumnpsRMSCurrentIn | read-only | optional | Scaled representation of the power supply RMS input current in 1/100 A. This item requires an entry in the properties MIB. |
| 1.3.6.1.4.1.5591.1.4.2.1.33 | ColumnpsPowerIn | read-only | optional | Representation of the power supply input power in 1 W. This item requires an entry in the properties MIB. |
| 1.3.6.1.4.1.5591.1.4.2.1.34 | ColumnpsInputVoltagePresence | read-only | optional | Digital value indicating that line voltage is present and within tolerance or not. 1 = lost 2 = ok. This item requires entries in the discrete properties MIB. |
| 1.3.6.1.4.1.5591.1.4.2.1.35 | ColumnpsFrequencyIn | read-only | mandatory | Operational frequency for input voltage |
| 1.3.6.1.4.1.5591.1.4.3 | TablepsStringTable | not-accessible | mandatory | Table containing strings data |
| 1.3.6.1.4.1.5591.1.4.3.1 | RowpsStringEntry | not-accessible | mandatory | List of information about each string. Indexed by device and string number |
| 1.3.6.1.4.1.5591.1.4.3.1.1 | ColumnpsStringDeviceAddress | read-only | mandatory | Index into the psStringTable. Corresponds to psDeviceAddress in psDeviceTable. |
| 1.3.6.1.4.1.5591.1.4.3.1.2 | ColumnpsString | read-only | mandatory | Index into the psStringTable. |
| 1.3.6.1.4.1.5591.1.4.3.1.3 | ColumnpsStringChargeCurrent | read-only | optional | Scaled representation of battery string charge current. This is an RMS value in 1/100 Amps. When batteries being discharged, this value will = 0. This item req… |
| 1.3.6.1.4.1.5591.1.4.3.1.4 | ColumnpsStringDischargeCurrent | read-only | optional | Scaled representation of battery string discharge current. This is an RMS value in 1/100 Amps.If multiple strings are installed but only one measurement sensor… |
| 1.3.6.1.4.1.5591.1.4.3.1.5 | ColumnpsStringFloat | read-only | optional | Scaled representation of battery 'float' charge current in 1/100 Amps. This field will be '0' under conditions other than during actual float charging. When th… |
| 1.3.6.1.4.1.5591.1.4.4 | TablepsBatteryTable | not-accessible | mandatory | Table containing batteries voltages |
| 1.3.6.1.4.1.5591.1.4.4.1 | RowpsBatteryEntry | not-accessible | mandatory | List of information about each battery.Indexed by device number and string |
| 1.3.6.1.4.1.5591.1.4.4.1.1 | ColumnpsBatteryDeviceAddress | read-only | mandatory | Index into the psBatteryTable. Corresponds to psDeviceAddress in psDeviceTable. |
| 1.3.6.1.4.1.5591.1.4.4.1.2 | ColumnpsBatteryString | read-only | mandatory | Index into the psBatteryTable. Corresponds to psString in psStringTable. |
| 1.3.6.1.4.1.5591.1.4.4.1.3 | ColumnpsBattery | read-only | mandatory | Index into the psBatteryTable. |
| 1.3.6.1.4.1.5591.1.4.4.1.4 | ColumnpsBatteryVoltage | read-only | optional | Scaled representation of an individual battery voltage in 1/100 Volts. String 'A' is used if only one battery string is active. This item requires an entry in … |
| 1.3.6.1.4.1.5591.1.4.5 | TablepsOutputTable | not-accessible | mandatory | Table containing output currents |
| 1.3.6.1.4.1.5591.1.4.5.1 | RowpsOutputEntry | not-accessible | mandatory | List of information about each Output port. Indexed by device and port number |
| 1.3.6.1.4.1.5591.1.4.5.1.1 | ColumnpsOutputDeviceAddress | read-only | mandatory | Index into the psOutputTable.Corresponds to psDeviceAddress in psDeviceTable. |
| 1.3.6.1.4.1.5591.1.4.5.1.2 | ColumnpsOutput | read-only | mandatory | Index into the psOutputTable. Output number |
| 1.3.6.1.4.1.5591.1.4.5.1.3 | ColumnpsOutputCurrent | read-only | optional | Scaled representation of power supply RMS output current in 1/100 Amps. This value is the total power supply output current if only one output is active. If mu… |
| 1.3.6.1.4.1.5591.1.4.6 | TablepsTemperatureSensorTable | not-accessible | mandatory | Table containing temperature sensors information |
| 1.3.6.1.4.1.5591.1.4.6.1 | RowpsTemperatureSensorEntry | not-accessible | mandatory | List of information about each Temperature sensor. Indexed by device and Sensor number |
| 1.3.6.1.4.1.5591.1.4.6.1.1 | ColumnpsTempDeviceAddress | read-only | mandatory | Index into the psTemperatureSensorTable.Corresponds to psDeviceAddress in psDeviceTable. |
| 1.3.6.1.4.1.5591.1.4.6.1.2 | ColumnpsTemperatureSensor | read-only | mandatory | Index into the psTemperatureSensorTable. Temperature sensor number |
| 1.3.6.1.4.1.5591.1.4.6.1.3 | ColumnpsTemperature | read-only | optional | Scaled representation of temperature. in degrees C with a range of -40 to + 80 degrees C. This item requires an entry in the properties MIB. |