MIB Viewer

SDEVICE-MIB

111 objects
This MIB describes the functions of the Schleifenbauer device family.
Imported Objects
SNMPv2-CONFMODULE-COMPLIANCE NOTIFICATION-GROUP OBJECT-GROUP
SNMPv2-SMIenterprises Integer32 IpAddress MODULE-IDENTITY NOTIFICATION-TYPE OBJECT-IDENTITY OBJECT-TYPE
SNMPv2-TCDisplayString MacAddress TEXTUAL-CONVENTION
OIDNameAccessStatusDescription
1.3.6.1.4.1.31034IdentityschleifenbauerThis MIB describes the functions of the Schleifenbauer device family.
1.3.6.1.4.1.31034.2Nodedevice0
1.3.6.1.4.1.31034.2.3Nodeidentification
1.3.6.1.4.1.31034.2.3.1ScalarspdmVersionread-onlycurrentData model version, currently 1.10
1.3.6.1.4.1.31034.2.3.2ScalarfirmwareVersionread-onlycurrentThe units firmware revision number.
1.3.6.1.4.1.31034.2.3.3ScalarbuildNumberread-onlycurrentDate and time of latest build of the firmware.
1.3.6.1.4.1.31034.2.3.4ScalarsalesOrderNumberread-onlycurrentSP sales order number.
1.3.6.1.4.1.31034.2.3.5ScalarproductIdread-onlycurrentSP product id.
1.3.6.1.4.1.31034.2.3.6ScalarserialNumberread-onlycurrentSP serial number.
1.3.6.1.4.1.31034.2.3.7ScalarhardwareAddressread-onlycurrentHardware serial number; cannot be changed. Can be used as backup unit address. format as 3 unsigned ints separated by dashes: int - int - int
1.3.6.1.4.1.31034.2.3.8ScalarmacAddressread-onlycurrentThe ethernet interfaces unique hardware address.
1.3.6.1.4.1.31034.2.3.9ScalarunitAddressread-writecurrentUser defined address; this will be used for addressing the unit.
1.3.6.1.4.1.31034.2.3.10ScalardeviceNameread-writecurrentUser configurable device name or identifier.
1.3.6.1.4.1.31034.2.3.11ScalardeviceLocationread-writecurrentUser configurable device location identifier.
1.3.6.1.4.1.31034.2.3.12ScalarvanityTagread-writecurrentCharacters to be displayed as vanity tekst in display.
1.3.6.1.4.1.31034.2.4Nodeconfiguration
1.3.6.1.4.1.31034.2.4.1ScalarnoPhasesread-onlycurrentEither zero, one or three for no input metering, single or three phase system
1.3.6.1.4.1.31034.2.4.2ScalarnoOutletsTotalread-onlycurrentTotal number of outlets, even hardwired without switch/measure modules.
1.3.6.1.4.1.31034.2.4.3ScalarnoSwitchedOutletsread-onlycurrentNumber of switched outlets. If outlet numbering is non-contiguous: the highest outlet number.
1.3.6.1.4.1.31034.2.4.4ScalarnoMeasuredOutletsread-onlycurrentNumber of measured outlets. If outlet numbering is non-contiguous: the highest outlet number.
1.3.6.1.4.1.31034.2.4.5ScalarnoSensorsread-onlycurrentThe number of external, digital environmental sensors: 0 for none, 1 to 16 depending on number of reported sensors
1.3.6.1.4.1.31034.2.4.6ScalarmaximumLoadread-onlycurrentMaximum rated load of device per phase, usually either 16 or 32 A.
1.3.6.1.4.1.31034.2.5Nodesystemstatus
1.3.6.1.4.1.31034.2.5.1ScalardeviceStatusCoderead-onlycurrentReturns an internal status or error code. 0 = OK, 16 = watchdog timer caused reset, 128 = slave module was reset, 144 = both previous.
1.3.6.1.4.1.31034.2.5.2ScalartemperatureAlertread-onlycurrentAn alert has been raised due to temperature exceeding treshhold; 0= no alert; 1= internal unit temp, 2= external sensor.
1.3.6.1.4.1.31034.2.5.3ScalarinputCurrentAlertread-onlycurrentAn alert has been raised due to current exceeding treshhold; 0=no alert; 1-3 for input phase.
1.3.6.1.4.1.31034.2.5.4ScalaroutputCurrentAlertread-onlycurrentAn alert has been raised due to current exceeding treshhold; 0=no alert; 1-48 for outlet.
1.3.6.1.4.1.31034.2.5.5ScalarinputVoltageAlertread-onlycurrentAn alert has been raised due to a voltage dip; 0=no alert; 1-3 for input phase.
1.3.6.1.4.1.31034.2.5.6ScalaroCurrentDropAlertread-onlycurrentAn alert has been raised due to the current of a measured outlet suddenly dropping to near zero, possibly indicating a blown fuse; 0=no alert; 1-48 for outlet.
1.3.6.1.4.1.31034.2.5.7ScalariCurrentDropAlertread-onlycurrentAn alert has been raised due to the current of a measured input suddenly dropping to near zero, possibly indicating a blown fuse; 0=no alert; 1-3 for phase.
1.3.6.1.4.1.31034.2.6Nodereset
1.3.6.1.4.1.31034.2.6.1ScalarrebootDeviceread-writecurrentWarm reboot/reset of device; note: this will have no effect on outlet status!
1.3.6.1.4.1.31034.2.6.2ScalarresetAlertsread-writecurrentReset all alert signals.
1.3.6.1.4.1.31034.2.6.3ScalarzeroInputKWhSubtotalread-writecurrentReset of input kWh subtotal counters to zero.
1.3.6.1.4.1.31034.2.6.4ScalarzeroOutKWhSubtotalread-writecurrentReset of outlet kWh subtotal counter to zero.
1.3.6.1.4.1.31034.2.6.5ScalarresetPeakValuesread-writecurrentReset all peak values to zero, as well input as output metering, voltages dips, current peaks and temperatures.
1.3.6.1.4.1.31034.2.7Nodesettings
1.3.6.1.4.1.31034.2.7.1Nodegeneral
1.3.6.1.4.1.31034.2.7.1.4ScalarpeakDurationread-writecurrentA current peak should last at least [stpkdr] MilliSeconds before an alert is raised; max about a minute.
1.3.6.1.4.1.31034.2.7.1.5ScalarfixedOutletDelayread-writecurrentMinimal delay between two successive relay switches in milliseconds. Minimal delay is 100 ms. Will always be respected!
1.3.6.1.4.1.31034.2.7.1.6ScalarpowerSaverModeread-writecurrentSet backlight on time in seconds; 0 keeps display always on. Note that keeping the backlight on may decrease luminosity over time. Setting this to other values…
1.3.6.1.4.1.31034.2.7.1.7ScalaroutletPowerupModeread-writecurrentBehaviour of outlet on power-up: 0=off; 1=same state as at power down; 2=same state, but delayed by individual delay timer.
1.3.6.1.4.1.31034.2.7.1.8ScalarmaximumTemperatureread-writecurrentAn alert should be generated whenever the temperature of the first connected T sensor is above this value. Zero means disabled.
1.3.6.1.4.1.31034.2.7.1.9ScalardisplayOrientationread-writecurrent0 no display; display off; 1 vertical, display on top; 2 vertical, upside down; 3 horizontal, display at left; 4 horizontal, display at right
1.3.6.1.4.1.31034.2.7.1.10ScalarlocalAlertResetread-writecurrentAllow alerts to be reset locally on device by pushing one of the buttons. [replaces dipDuration]
1.3.6.1.4.1.31034.2.7.1.11ScalarcurrentDropDetectionread-writecurrentEnables the current drop detection function. 0 = always off (default), 1 = input (s) only, 2 = output(s) only, 3 = both inputs and outputs.
1.3.6.1.4.1.31034.2.7.1.12ScalarwirelessDisplayPowerread-writecurrentControls the transit power of the wireless display transciever (if installed). Set to zero to completely disable the module.
1.3.6.1.4.1.31034.2.8TableinputmeasuresTablenot-accessiblecurrentThis table contains all measures related to the measured inputs of the DEVICE. Note: either 1 or 3 channels, depending on number of phases measured.
1.3.6.1.4.1.31034.2.8.1RowinputmeasuresEntrynot-accessiblecurrentThe record containing the registers for the channel selected by channelIndex.
1.3.6.1.4.1.31034.2.8.1.1ColumnchannelIndex6not-accessiblecurrentThe channel. Its value ranges between 1 and 48, depending on the number of channels, usually 1.
1.3.6.1.4.1.31034.2.8.1.2ColumnkWhTotalIread-onlycurrentEither the only phase in a single phase measurement; or one of the three phases in a multiphase measurement.
1.3.6.1.4.1.31034.2.8.1.3ColumnkWhSubtotalIread-onlycurrentkWh subtotal register of the only phase in a single phase measurement; or one of three phases in a multiphase measurement. Reset to zero with [rsimks].
1.3.6.1.4.1.31034.2.8.1.4ColumnpowerFactorIread-onlycurrentThe effective power factor in percent.
1.3.6.1.4.1.31034.2.8.1.5ColumnactualCurrentIread-onlycurrentActual apparent, RMS current.
1.3.6.1.4.1.31034.2.8.1.6ColumnpeakCurrentIread-onlycurrentPeak apparent, RMS current; highest value since last reset of the alerts.
1.3.6.1.4.1.31034.2.8.1.7ColumnactualVoltageIread-onlycurrentThe actual voltage.
1.3.6.1.4.1.31034.2.8.1.8ColumnminVoltageIread-onlycurrentRMS voltage dip; lowest value since reset of alerts.
1.3.6.1.4.1.31034.2.8.1.9ColumnpowerVAIread-onlycurrentPower value calculated, not in data model of device.
1.3.6.1.4.1.31034.2.8.1.10ColumnpowerWattIread-onlycurrentPower value calculated by the gateway, not in data model of device.
1.3.6.1.4.1.31034.2.8.1.11ColumnmaxInletAmpsread-writecurrentMaximum current per input phase in A; should last at least [stpkdr] MilliSeconds before triggering an alert.
1.3.6.1.4.1.31034.2.8.1.12ColumninputCTratioread-writecurrentThe multiplier to use in case of use of /5 current transformers. Defaults to 1.
1.3.6.1.4.1.31034.2.8.1.13ColumninputNameread-writecurrentUser configurable naming of inputs or phases. Useful if channels are used to measure branches..
1.3.6.1.4.1.31034.2.9TableoutletsTablenot-accessiblecurrentThis table contains the customer specific settings, determining toutlestablehe behaviour of the DEVICE.
1.3.6.1.4.1.31034.2.9.1RowoutletsEntrynot-accessiblecurrentThe record containing the registers forthe channel selected by channelIndex.
1.3.6.1.4.1.31034.2.9.1.1ColumnchannelIndex4not-accessiblecurrentThe channel. Its value ranges between 1 and 48, depending on the number of channels, usually 1.
1.3.6.1.4.1.31034.2.9.1.2ColumnoutletNameread-onlycurrentUser configurable naming of individual outlets. Useful to distinguish outlets based on customer or device name.
1.3.6.1.4.1.31034.2.10TableoutputmeasuresTablenot-accessiblecurrentThis table contains all measures related to the measured outputs of the DEVICE. Note: up to 48 channels, depending on number of measured outlets.
1.3.6.1.4.1.31034.2.10.1RowoutputmeasuresEntrynot-accessiblecurrentThe record containing the registers for the channel selected by channelIndex.
1.3.6.1.4.1.31034.2.10.1.1ColumnchannelIndex7not-accessiblecurrentThe channel. Its value ranges between 1 and 48, depending on the number of channels, usually 1.
1.3.6.1.4.1.31034.2.10.1.2ColumnkWhTotalOread-onlycurrentTotal kWh of selected output.
1.3.6.1.4.1.31034.2.10.1.3ColumnkWhSubtotalOread-onlycurrentkWh subtotal register of selected output. Reset to zero with [rsomks].
1.3.6.1.4.1.31034.2.10.1.4ColumnpowerFactorOread-onlycurrentPower factor of output.
1.3.6.1.4.1.31034.2.10.1.5ColumnactualCurrentOread-onlycurrentActual apparent, RMS current.
1.3.6.1.4.1.31034.2.10.1.6ColumnpeakCurrentOread-onlycurrentPeak apparent, RMS current; highest value since last reset of alerts.
1.3.6.1.4.1.31034.2.10.1.7ColumnactualVoltageOread-onlycurrentActual voltage on output.
1.3.6.1.4.1.31034.2.10.1.8ColumnmaxOutletAmpsread-writecurrentMaximum current per outlet in A; should last at least [stpkdr] MilliSeconds before triggering an alert.
1.3.6.1.4.1.31034.2.10.1.9ColumnoutputCTratioread-writecurrentThe multiplier to use in case of use of /5 current transformers. Defaults to 1.
1.3.6.1.4.1.31034.2.11TableswitchedoutletsTablenot-accessiblecurrentThis table contains the current status of switchable DEVICE's.
1.3.6.1.4.1.31034.2.11.1RowswitchedoutletsEntrynot-accessiblecurrentThe record containing the registers for the channel selected by channelIndex.
1.3.6.1.4.1.31034.2.11.1.1ColumnchannelIndex5not-accessiblecurrentThe channel. Its value ranges between 1 and 48, depending on the number of channels, usually 1.
1.3.6.1.4.1.31034.2.11.1.2ColumncurrentStateread-writecurrentThe actual state of the outlet relays. The hardware will contain max 48 outlets. Writing is only effective after setting [swounl].
1.3.6.1.4.1.31034.2.11.1.3Columnscheduledread-onlycurrentA one indicates pending activity; the switch delay has not yet expired.
1.3.6.1.4.1.31034.2.11.1.4Columnunlockread-writecurrentSetting the value to one will release the safety for this outlet for a couple seconds; switching and rebooting are then temporarily enabled.
1.3.6.1.4.1.31034.2.11.1.5ColumnindividualOutletDelayread-writecurrentDelay before an individual outlet switches on at power-up in Seconds.
1.3.6.1.4.1.31034.2.12TablesensorTablenot-accessiblecurrentThis table contains the environmental measurements. As well internal temperature as external temperature probes.
1.3.6.1.4.1.31034.2.12.1RowsensorEntrynot-accessiblecurrentThe record containing the registers for the channel selected by channelIndex.
1.3.6.1.4.1.31034.2.12.1.1ColumnchannelIndex8not-accessiblecurrentThe channel. Its value ranges between 1 and 48, depending on the number of channels, usually 1.
1.3.6.1.4.1.31034.2.12.1.2ColumnsensorTyperead-onlycurrentType of connected sensor, either T, H or I for respectively Temperature (C), Humidity (%) or dry switch contact
1.3.6.1.4.1.31034.2.12.1.3ColumnsensorValueread-onlycurrentValue of connected sensor
1.3.6.1.4.1.31034.2.12.1.4ColumnsensorNameread-writecurrentUser definable name for sensors.
1.3.6.1.4.1.31034.99Nodeconformance
1.3.6.1.4.1.31034.99.1Nodecompliances
1.3.6.1.4.1.31034.99.1.1CompliancecompliancecurrentThe requirements for conformance to the SPGW-MIB.
1.3.6.1.4.1.31034.99.2Nodegroups
1.3.6.1.4.1.31034.99.2.1GroupidentificationGroupcurrentA collection of objects providing identification information about the device.
1.3.6.1.4.1.31034.99.2.2GroupconfigurationGroupcurrentA collection of objects providing configuration information about the device.
1.3.6.1.4.1.31034.99.2.3GroupsystemStatusGroupcurrentA collection of objects providing status information about the device.
1.3.6.1.4.1.31034.99.2.4GroupresetGroupcurrentGroups resettable attributes op the device.
1.3.6.1.4.1.31034.99.2.5GroupsettingsGroupcurrentA collection of objects providing the actual settings about the device.
1.3.6.1.4.1.31034.99.2.6GroupswitchedOutletsGroupcurrentA collection of objects providing the actual outlet status of the device.
1.3.6.1.4.1.31034.99.2.7GroupinputMeasuresGroupcurrentA collection of objects providing the actual input measurements of the device.
1.3.6.1.4.1.31034.99.2.8GroupoutputMeasuresGroupcurrentA collection of objects providing the actual output measurements of the device.
1.3.6.1.4.1.31034.99.2.9GroupsensorsGroupcurrentA collection of objects providing the actual environmental measurements of the device.
Type Definitions
NameSyntaxStatusDescription
DeciAmpsInteger32currentData type for reporting measurements and thresholds associated with current sensors. If the underlying hardware sensor indicates 1.1 amp, then the SNMP agent will report a value of 11 DeciAmps. The value is scaled in th…
DeciCelsiusInteger32currentData type for reporting sensor readings associated with temperature sensors. If the underlying hardware sensor indicates 20.1 degree Celsius, then the SNMP agent will report a value of 201 tenth degrees Celsius. The val…
DeciPowerFactorInteger32currentData type for reporting measurements associated with power factor calculation. The power factor of an AC power system is defined as the ratio of the real or active power to the apparent power and is a number between 0 a…
DeciValueInteger32currentData type for reporting generic measurements associated with environmental sensors. If the underlying hardware sensor indicates 21.1 degree, then the SNMP agent will report a value of 211 DeciValue. The value is scaled …
DeciVoltsInteger32 IdentificationEntry ::= SEQUENCE { channelIndex1 Integer32, spdmVersion Integer32, firmwareVersion Integer32, salesOrderNumber DisplayString, productId DisplayString, serialNumber DisplayString, hardwareAddress DisplayString, unitAddress Integer32, busPosition Integer32 }currentData type for reporting measurements and thresholds associated with voltage sensors. If the underlying hardware sensor indicates 231.1 volts, then the SNMP agent will report a value of 2311 DeciVolts. The value is scale…
KiloWattHourInteger32currentData type for reporting measurements associated with energy accumulation sensors. If the underlying hardware sensor indicates 1 kWh, then the SNMP agent will report a value of 1 kWh. No scaling is performed for this typ…
MilliSecondsInteger32currentThe unit of duration for some settings
SecondsInteger32 SystemstatusEntry ::= SEQUENCE { channelIndex3 Integer32, deviceStatusCode Integer32, temperatureAlert Integer32, inputCurrentAlert Integer32, outputCurrentAlert Integer32, inputVoltageAlert Integer32, oCurrentDropAlert Integer32, iCurrentDropAlert Integer32 }currentThe unit of duration for some settings