MIB Viewer

SITEBOSS-420-STD-MIB

134 objects
MIB module for managing Asentria SiteBoss 420
Imported Objects
ASENTRIA-ROOT-MIBasentria
SNMPv2-SMIInteger32 IpAddress MODULE-IDENTITY NOTIFICATION-TYPE OBJECT-TYPE TimeTicks
SNMPv2-TCDisplayString
OIDNameAccessStatusDescription
1.3.6.1.4.1.3052.42Identitys420MIB module for managing Asentria SiteBoss 420
1.3.6.1.4.1.3052.42.0Nodenotification
1.3.6.1.4.1.3052.42.1Nodestatus
1.3.6.1.4.1.3052.42.1.1NodeeventSensorStatus
1.3.6.1.4.1.3052.42.1.1.1TableesPointTablenot-accessiblecurrentThis table organizes 4 basic attributes of points. A point is a particular sensor on an EventSensor (e.g., temperature, humidity, contact closure 2, relay 5, e…
1.3.6.1.4.1.3052.42.1.1.1.1RowesPointEntrynot-accessiblecurrentEntry for EventSensor point table
1.3.6.1.4.1.3052.42.1.1.1.1.1ColumnesIndexESread-onlycurrentThe part of the point index that refers to an EventSensor. The point index is a string of 3 numbers separated by periods. It contains all the information neces…
1.3.6.1.4.1.3052.42.1.1.1.1.2ColumnesIndexPCread-onlycurrentThe part of the point index that refers to point class. The point index is a string of 3 numbers separated by periods. It contains all the information necessar…
1.3.6.1.4.1.3052.42.1.1.1.1.3ColumnesIndexPointread-onlycurrentThe part of the point index that delineates which sensor on the EventSensor. So this combined with esIndexPC (Point Class or type) and esIndexES (which EventSe…
1.3.6.1.4.1.3052.42.1.1.1.1.4ColumnesPointNameread-writecurrentThe name of the point on an EventSensor. For example, 'AC temp' (in the case of the temperature sensor on an EventSensor). There can be multiple points of the …
1.3.6.1.4.1.3052.42.1.1.1.1.5ColumnesPointInEventStateread-writecurrentA number referring to the event state of a point on an EventSensor. This number can have different meanings depending on the point class. If the point class is…
1.3.6.1.4.1.3052.42.1.1.1.1.6ColumnesPointValueIntread-writecurrentA read-only number referring to the value of a point on an EventSensor. If the point class is temperature, then this object is the temperature in its configure…
1.3.6.1.4.1.3052.42.1.1.1.1.7ColumnesPointValueStrread-onlycurrentA string referring to the value of a point on an EventSensor. For contact closures this object is either 'Open' or 'Closed'. For relays this object is either '…
1.3.6.1.4.1.3052.42.2Nodeconfig
1.3.6.1.4.1.3052.42.2.2NodeeventSensorPointConfig
1.3.6.1.4.1.3052.42.2.2.1TableesPointConfigTempTablenot-accessiblecurrentThis table organizes 3 basic attributes of temperature sensor points. A point is a particular sensor on an EventSensor. The 3 point attributes organizes in thi…
1.3.6.1.4.1.3052.42.2.2.1.1RowesPointConfigTempEntrynot-accessiblecurrentEntry for EventSensor point config temperature table
1.3.6.1.4.1.3052.42.2.2.1.1.1ColumnespcTempIndexESread-onlycurrentThe part of the point index that refers to an EventSensor. The point config index is a string of 2 numbers separated by a period. It contains all the informati…
1.3.6.1.4.1.3052.42.2.2.1.1.2ColumnespcTempIndexPointread-onlycurrentThe part of the point index that delineates which sensor on the EventSensor. So this combined with espcTempIndexES (which EventSensor) uniquely defines each po…
1.3.6.1.4.1.3052.42.2.2.1.1.3ColumnespcTempEnableread-writecurrentON/OFF enable this temperature sensor
1.3.6.1.4.1.3052.42.2.2.1.1.4ColumnespcTempNameread-writecurrentThe name of this temperature sensor
1.3.6.1.4.1.3052.42.2.2.1.1.5ColumnespcTempScaleread-writecurrentScale (C/F) for this temperature sensor
1.3.6.1.4.1.3052.42.2.2.1.1.6ColumnespcTempDeadbandread-writecurrentDeadband for this temperature sensor
1.3.6.1.4.1.3052.42.2.2.1.1.7ColumnespcTempVHighTempread-writecurrentVery high temperature event threshold for this temperature sensor
1.3.6.1.4.1.3052.42.2.2.1.1.9ColumnespcTempVHighClassread-writecurrentVery high temperature event class for this temperature sensor
1.3.6.1.4.1.3052.42.2.2.1.1.10ColumnespcTempHighTempread-writecurrentHigh temperature event threshold for this temperature sensor
1.3.6.1.4.1.3052.42.2.2.1.1.13ColumnespcTempHighClassread-writecurrentHigh temperature event class for this temperature sensor
1.3.6.1.4.1.3052.42.2.2.1.1.17ColumnespcTempLowTempread-writecurrentLow temperature event threshold for this temperature sensor
1.3.6.1.4.1.3052.42.2.2.1.1.20ColumnespcTempLowClassread-writecurrentLow temperature event class for this temperature sensor
1.3.6.1.4.1.3052.42.2.2.1.1.21ColumnespcTempVLowTempread-writecurrentVery Low temperature event threshold for this temperature sensor
1.3.6.1.4.1.3052.42.2.2.1.1.24ColumnespcTempVLowClassread-writecurrentVery Low temperature event class for this temperature sensor
1.3.6.1.4.1.3052.42.2.2.1.1.25ColumnespcTempActionsread-writecurrentTemperature event Action
1.3.6.1.4.1.3052.42.2.2.2TableesPointConfigCCTablenot-accessiblecurrentThis table organizes 3 basic attributes of contact closure points. A point is a particular sensor on an EventSensor. The 3 point attributes organizes in this t…
1.3.6.1.4.1.3052.42.2.2.2.1RowesPointConfigCCEntrynot-accessiblecurrentEntry for EventSensor point config contact closure table
1.3.6.1.4.1.3052.42.2.2.2.1.1ColumnespcCCIndexESread-onlycurrentThe part of the point index that refers to an EventSensor. The point config index is a string of 2 numbers separated by a period. It contains all the informati…
1.3.6.1.4.1.3052.42.2.2.2.1.2ColumnespcCCIndexPointread-onlycurrentThe part of the point index that delineates which sensor on the EventSensor. So this combined with espcCCIndexES (which EventSensor) uniquely defines each poin…
1.3.6.1.4.1.3052.42.2.2.2.1.3ColumnespcCCEnableread-writecurrentON/OFF enable for this contact closure
1.3.6.1.4.1.3052.42.2.2.2.1.4ColumnespcCCNameread-writecurrentName for this contact closure
1.3.6.1.4.1.3052.42.2.2.2.1.5ColumnespcCCEventStateread-writecurrentEvent state for this contact closure
1.3.6.1.4.1.3052.42.2.2.2.1.6ColumnespcCCThresholdread-writecurrentThreshold (seconds) for this contact closure
1.3.6.1.4.1.3052.42.2.2.2.1.7ColumnespcCCActionsread-writecurrentEvent class for this contact closure
1.3.6.1.4.1.3052.42.2.2.2.1.9ColumnespcCCEventClassread-writecurrentEvent class for this contact closure
1.3.6.1.4.1.3052.42.2.2.2.1.12ColumnespcCCNormalClassread-writecurrentReturn-to-normal class for this contact closure
1.3.6.1.4.1.3052.42.2.2.2.1.13ColumnespcCCAlarmAliasread-writecurrentEvent alias for this contact closure
1.3.6.1.4.1.3052.42.2.2.2.1.14ColumnespcCCNormalAliasread-writecurrentReturn-to-normal alias for this contact closure
1.3.6.1.4.1.3052.42.2.2.3TableesPointConfigHumidTablenot-accessiblecurrentThis table organizes 3 basic attributes of humidity points. A point is a particular sensor on an EventSensor. The 3 point attributes organizes in this table ar…
1.3.6.1.4.1.3052.42.2.2.3.1RowesPointConfigHumidEntrynot-accessiblecurrentEntry for EventSensor point config humidity table
1.3.6.1.4.1.3052.42.2.2.3.1.1ColumnespcHumidIndexESread-onlycurrentThe part of the point index that refers to an EventSensor. The point config index is a string of 2 numbers separated by a period. It contains all the informati…
1.3.6.1.4.1.3052.42.2.2.3.1.2ColumnespcHumidIndexPointread-onlycurrentThe part of the point index that delineates which sensor on the EventSensor. So this combined with espcHumidIndexES (which EventSensor) uniquely defines each p…
1.3.6.1.4.1.3052.42.2.2.3.1.3ColumnespcHumidEnableread-writecurrentON/OFF enable for this humidity sensor
1.3.6.1.4.1.3052.42.2.2.3.1.4ColumnespcHumidNameread-writecurrentThe name for this humidity sensor
1.3.6.1.4.1.3052.42.2.2.3.1.5ColumnespcHumidDeadbandread-writecurrentDeadband for this humidity sensor
1.3.6.1.4.1.3052.42.2.2.3.1.6ColumnespcHumidVHighHumidread-writecurrentVery high event threshold for this humidity sensor
1.3.6.1.4.1.3052.42.2.2.3.1.8ColumnespcHumidVHighClassread-writecurrentVery high event class for this humidity sensor
1.3.6.1.4.1.3052.42.2.2.3.1.9ColumnespcHumidHighHumidread-writecurrentHigh event threshold for this humidity sensor
1.3.6.1.4.1.3052.42.2.2.3.1.12ColumnespcHumidHighClassread-writecurrentHigh event class for this humidity sensor
1.3.6.1.4.1.3052.42.2.2.3.1.16ColumnespcHumidLowHumidread-writecurrentLow event threshold for this humidity sensor
1.3.6.1.4.1.3052.42.2.2.3.1.19ColumnespcHumidLowClassread-writecurrentLow event class for this humidity sensor
1.3.6.1.4.1.3052.42.2.2.3.1.20ColumnespcHumidVLowHumidread-writecurrentVery low event threshold for this humidity sensor
1.3.6.1.4.1.3052.42.2.2.3.1.23ColumnespcHumidVLowClassread-writecurrentVery low event class for this humidity sensor
1.3.6.1.4.1.3052.42.2.2.3.1.24ColumnespcHumidActionsread-writecurrentHumidity event actions for this humidity sensor
1.3.6.1.4.1.3052.42.2.2.5TableesPointConfigAITablenot-accessiblecurrentThis table organizes 3 basic attributes of analog input points. A point is a particular sensor on an EventSensor. The 3 point attributes organizes in this tabl…
1.3.6.1.4.1.3052.42.2.2.5.1RowesPointConfigAIEntrynot-accessiblecurrentEntry for EventSensor point config analog input table
1.3.6.1.4.1.3052.42.2.2.5.1.1ColumnespcAIIndexESread-onlycurrentThe part of the point index that refers to an EventSensor. The point config index is a string of 2 numbers separated by a period. It contains all the informati…
1.3.6.1.4.1.3052.42.2.2.5.1.2ColumnespcAIIndexPointread-onlycurrentThe part of the point index that delineates which sensor on the EventSensor. So this combined with espcAIIndexES (which EventSensor) uniquely defines each poin…
1.3.6.1.4.1.3052.42.2.2.5.1.3ColumnespcAIEnableread-writecurrentON/OFF for this analog input sensor
1.3.6.1.4.1.3052.42.2.2.5.1.4ColumnespcAINameread-writecurrentName for this analog input sensor
1.3.6.1.4.1.3052.42.2.2.5.1.5ColumnespcAIDeadbandread-writecurrentDeadband for this analog input sensor
1.3.6.1.4.1.3052.42.2.2.5.1.6ColumnespcAIVhighValueread-writecurrentVery high event threshold (decivolts or tenths of milliamps) for this analog input sensor
1.3.6.1.4.1.3052.42.2.2.5.1.8ColumnespcAIVhighClassread-writecurrentVery high event class for this analog input sensor
1.3.6.1.4.1.3052.42.2.2.5.1.9ColumnespcAIHighValueread-writecurrentHigh event threshold (decivolts or tenths of milliamps) for this analog input sensor
1.3.6.1.4.1.3052.42.2.2.5.1.12ColumnespcAIHighClassread-writecurrentHigh event class for this analog input sensor
1.3.6.1.4.1.3052.42.2.2.5.1.16ColumnespcAILowValueread-writecurrentLow event threshold (decivolts or tenths of milliamps) for this analog input sensor
1.3.6.1.4.1.3052.42.2.2.5.1.19ColumnespcAILowClassread-writecurrentLow event class for this analog input sensor
1.3.6.1.4.1.3052.42.2.2.5.1.20ColumnespcAIVlowValueread-writecurrentVery low event threshold (decivolts or tenths of milliamps) for this analog input sensor
1.3.6.1.4.1.3052.42.2.2.5.1.23ColumnespcAIVlowClassread-writecurrentVery low event class for this analog input sensor
1.3.6.1.4.1.3052.42.2.2.5.1.24ColumnespcAIActionsread-writecurrentEvent actions for this analog input sensor
1.3.6.1.4.1.3052.42.2.2.5.1.25ColumnespcAIConvUnitNameread-writecurrentConversion unit name for this analog input sensor
1.3.6.1.4.1.3052.42.2.2.5.1.26ColumnespcAIConvLowValueread-writecurrentConversion low value for this analog input sensor
1.3.6.1.4.1.3052.42.2.2.5.1.27ColumnespcAIConvLowUnitread-writecurrentConversion low unit value for this analog input sensor
1.3.6.1.4.1.3052.42.2.2.5.1.28ColumnespcAIConvHighValueread-writecurrentConversion high value for this analog input sensor
1.3.6.1.4.1.3052.42.2.2.5.1.29ColumnespcAIConvHighUnitread-writecurrentConversion high unit value for this analog input sensor
1.3.6.1.4.1.3052.42.2.2.6TableesPointConfigRelayTablenot-accessiblecurrentThis table organizes 3 basic attributes of relay points. A point is a particular sensor on an EventSensor. The 3 point attributes organizes in this table are: …
1.3.6.1.4.1.3052.42.2.2.6.1RowesPointConfigRelayEntrynot-accessiblecurrentEntry for EventSensor point config relay table
1.3.6.1.4.1.3052.42.2.2.6.1.1ColumnespcRelayIndexESread-onlycurrentThe part of the point index that refers to an EventSensor. The point config index is a string of 2 numbers separated by a period. It contains all the informati…
1.3.6.1.4.1.3052.42.2.2.6.1.2ColumnespcRelayIndexPointread-onlycurrentThe part of the point index that delineates which sensor on the EventSensor. So this combined with espcRelayIndexES (which EventSensor) uniquely defines each p…
1.3.6.1.4.1.3052.42.2.2.6.1.3ColumnespcRelayEnableread-writecurrentON/OFF enable for this relay
1.3.6.1.4.1.3052.42.2.2.6.1.4ColumnespcRelayNameread-writecurrentName for this relay
1.3.6.1.4.1.3052.42.2.4Nodenetwork
1.3.6.1.4.1.3052.42.2.4.1Nodeethernet
1.3.6.1.4.1.3052.42.2.4.1.1ScalaripAddressread-writecurrentEthernet IP address
1.3.6.1.4.1.3052.42.2.4.1.2ScalarsubnetMaskread-writecurrentEthernet subnet mask
1.3.6.1.4.1.3052.42.2.4.1.3Scalarrouterread-writecurrentEthernet router
1.3.6.1.4.1.3052.42.2.4.8Nodesnmp
1.3.6.1.4.1.3052.42.2.4.8.2ScalarsnmpReadCommunityread-writecurrentSNMP read community
1.3.6.1.4.1.3052.42.2.4.8.3ScalarsnmpWriteCommunityread-writecurrentSNMP write community
1.3.6.1.4.1.3052.42.2.4.8.4ScalarsnmpTrapCommunityread-writecurrentSNMP trap community
1.3.6.1.4.1.3052.42.2.4.8.6TablesnmpServerTablenot-accessiblecurrentTable of network hosts to use for network-based actions
1.3.6.1.4.1.3052.42.2.4.8.6.1RowsnmpServerEntrynot-accessiblecurrentEntry for table of network hosts to use for network-based actions
1.3.6.1.4.1.3052.42.2.4.8.6.1.1ColumnsnmpServerIndexread-onlycurrentIndex for table of network hosts to use for network-based actions
1.3.6.1.4.1.3052.42.2.4.8.6.1.2ColumnsnmpServerread-writecurrentHostname/IP address used as destination for network-based action (e.g., trap)
1.3.6.1.4.1.3052.42.2.4.8.7ScalarsnmpTestTrapread-writecurrentSNMP trap community
1.3.6.1.4.1.3052.42.2.4.17Nodeemail
1.3.6.1.4.1.3052.42.2.4.17.1ScalaremailServerread-writecurrentSMTP server to which the unit sends email
1.3.6.1.4.1.3052.42.2.4.17.2ScalaremailDomainread-writecurrentDomain to use in recipient address
1.3.6.1.4.1.3052.42.2.4.17.3ScalaremailAuthEnableread-writecurrentON/OFF enable SMTP authentication
1.3.6.1.4.1.3052.42.2.4.17.4ScalaremailAuthUsernameread-writecurrentUsername for SMTP authentication
1.3.6.1.4.1.3052.42.2.4.17.5ScalaremailAuthPasswordread-writecurrentPassword for SMTP authentication
1.3.6.1.4.1.3052.42.2.4.17.6TableemailTablenot-accessiblecurrentTable of email addresses to use for email actions
1.3.6.1.4.1.3052.42.2.4.17.6.1RowemailEntrynot-accessiblecurrentEntry for table of email addresses to use for email actions
1.3.6.1.4.1.3052.42.2.4.17.6.1.1ColumnemailIndexread-onlycurrentIndex for table of email addresses to use for email actions
1.3.6.1.4.1.3052.42.2.4.17.6.1.2ColumnemailAddressread-writecurrentemail address
1.3.6.1.4.1.3052.42.2.4.17.7ScalaremailTestMailread-writecurrentPassword for SMTP authentication
1.3.6.1.4.1.3052.42.2.8NodedateTime
1.3.6.1.4.1.3052.42.2.8.1Scalardateread-writecurrentText string for date.
1.3.6.1.4.1.3052.42.2.8.2Scalartimeread-writecurrentText string for time.
1.3.6.1.4.1.3052.42.2.8.3Scalarautodstread-writecurrentON/OFF automatically adjust for Daylight Savings Time
1.3.6.1.4.1.3052.42.2.14Nodeaction
1.3.6.1.4.1.3052.42.2.14.1ScalaractionSystemAlertActionread-writecurrentSystem Alert Actions are actions that occur when the system needs to alert the user of something. The only time this occurs currently is a powerup alert.
1.3.6.1.4.1.3052.42.2.14.2ScalaractionPowerupAlertEnableread-writecurrentaction Powerup Alert Enable
1.3.6.1.4.1.3052.42.2.14.3ScalaractionRTNAlertsEnableread-writecurrentReturn to Normal Alerts Enabled
1.3.6.1.4.1.3052.42.2.14.4ScalaractionAlarmRepeatFrequencyread-writecurrentFrequency in minutes of repeats
1.3.6.1.4.1.3052.42.2.16Nodesys
1.3.6.1.4.1.3052.42.2.16.1ScalarsysSerialread-writecurrentSerial Number
1.3.6.1.4.1.3052.42.2.16.2ScalarsysVersionread-writecurrentSerial Number
1.3.6.1.4.1.3052.42.2.16.3ScalarsysBuildread-writecurrentSerial Number
1.3.6.1.4.1.3052.42.2.16.4ScalarsysSitenameread-writecurrentSerial Number
1.3.6.1.4.1.3052.42.2.16.5ScalarsysProductread-writecurrentSerial Number
1.3.6.1.4.1.3052.42.2.16.6ScalarthisTrapTextread-writecurrentA text string included in all traps
1.3.6.1.4.1.3052.42.20000Notifications420PowerUpTrapcurrentSent upon System Alert at power up.
1.3.6.1.4.1.3052.42.20001Notifications420ContactTrapcurrentSent to show a contact is in the alarm state.
1.3.6.1.4.1.3052.42.20010Notifications420TempTrapcurrentSent to show temperature exceeded threshold.
1.3.6.1.4.1.3052.42.20020Notifications420HumidTrapcurrentSent to show humidity exceeded threshold
1.3.6.1.4.1.3052.42.22000Notifications420TestTrapcurrentSent to test IP route(s) for traps.