SMART-PDUATS-MIB
173 objects
MIB file for the PDU (Power Distribution Unit) equipments.
Imported Objects
| SNMPv2-SMI | enterprises Integer32 IpAddress MODULE-IDENTITY NOTIFICATION-TYPE OBJECT-TYPE |
| SNMPv2-TC | DisplayString TruthValue |
| OID | Name | Access | Status | Description |
|---|---|---|---|---|
| 1.3.6.1.4.1.55508 | Identitysmart-PDU | MIB file for the PDU (Power Distribution Unit) equipments. | ||
| 1.3.6.1.4.1.55508.1 | NodepduAts | |||
| 1.3.6.1.4.1.55508.1.1 | Nodesystem | |||
| 1.3.6.1.4.1.55508.1.1.1 | NodeeventInfo | |||
| 1.3.6.1.4.1.55508.1.1.1.1 | ScalarsourceID | read-only | current | The ID (address code) of sources(PDU/ATS/SENSOR). The OID is bound in a trap message. |
| 1.3.6.1.4.1.55508.1.1.1.2 | ScalarpowerDescr | read-only | current | The description to source PDU/ATS. The OID is bound in a trap message. |
| 1.3.6.1.4.1.55508.1.1.1.3 | ScalareventSource | read-only | current | The event sources: PDU(fuse/load), ATS(switching/voltage), SENSOR(temp./humid./wind/environment). The OID is bound in a trap message. |
| 1.3.6.1.4.1.55508.1.1.1.4 | ScalarsensorDescr | read-only | current | The description to source SENSOR. The OID is bound in a trap message. |
| 1.3.6.1.4.1.55508.1.1.1.5 | ScalareventType | read-only | current | The type of the event (trap). The value would be 'recovery' or 'alarm' or 'notify'. 'recovery': An alarm is recovery. 'alarm': An alarm is issued or repeated. … |
| 1.3.6.1.4.1.55508.1.1.1.6 | ScalareventDateTime | read-only | current | Alert time. The OID is bound in a trap message. |
| 1.3.6.1.4.1.55508.1.1.1.7 | ScalarloadValue | read-only | current | The load value of OUTLET/TOTAL. A non-negative value indicates the measured load in tenth of amperes. A negative value indicates that a load value was not avai… |
| 1.3.6.1.4.1.55508.1.1.1.8 | ScalarloadLowValue | read-only | current | The setting of low limit of load of OUTLET/TOTAL. A non-negative value indicates the measured load in tenth of amperes. A negative value indicates that a load … |
| 1.3.6.1.4.1.55508.1.1.1.9 | ScalarloadHighValue | read-only | current | The setting of high limit of load of OUTLET/TOTAL. A non-negative value indicates the measured load in tenth of amperes. A negative value indicates that a load… |
| 1.3.6.1.4.1.55508.1.1.1.10 | ScalarvoltageValue | read-only | current | The voltage value of input. A non-negative value indicates the measured value in volts. A negative value indicates that a value was not available. The OID is b… |
| 1.3.6.1.4.1.55508.1.1.1.11 | ScalarvoltageLowValue | read-only | current | The setting of low limit of voltage of input. A non-negative value indicates the measured value in volts. A negative value indicates that a value was not avail… |
| 1.3.6.1.4.1.55508.1.1.1.12 | ScalarvoltageHighValue | read-only | current | The setting of high limit of voltage of input. A non-negative value indicates the measured value in volts. A negative value indicates that a value was not avai… |
| 1.3.6.1.4.1.55508.1.1.2 | NodesysNetwork | |||
| 1.3.6.1.4.1.55508.1.1.2.1 | ScalaripAddress | read-write | current | The IP address of this management node where this SNMP agent is running(Default value: 192.168.0.254). NOTATION: When ipAddress is changed, the IP address of t… |
| 1.3.6.1.4.1.55508.1.1.2.2 | ScalarmaskIpAddress | read-write | current | The mask IP address,default value: 255.255.255.0 NOTATION: When changed, this equipment should be reboot to take effect. |
| 1.3.6.1.4.1.55508.1.1.2.3 | ScalargatewayIpAddress | read-write | current | The gateway IP address,default value: 0.0.0.0 NOTATION: When changed, this equipment should be reboot to take effect. |
| 1.3.6.1.4.1.55508.1.1.2.4 | ScalardnsIpAddress1 | read-write | current | The DNS#1 IP address,default value: 0.0.0.0 NOTATION: When changed, this equipment should be reboot to take effect. |
| 1.3.6.1.4.1.55508.1.1.2.5 | ScalardnsIpAddress2 | read-write | current | The DNS#2 IP address,default value: 0.0.0.0 NOTATION: When changed, this equipment should be reboot to take effect. |
| 1.3.6.1.4.1.55508.1.1.2.6 | ScalarrebootSystem | read-write | current | Set value 1 to the OID to reboot the system. set value 0 would not be allowed. WARNING: TAKE CARE BEFORE SET! |
| 1.3.6.1.4.1.55508.1.1.2.7 | ScalartrapDestIP1 | read-write | current | The trap destination IP address #1,default value: 0.0.0.0 |
| 1.3.6.1.4.1.55508.1.1.2.8 | ScalartrapDestIP2 | read-write | current | The trap destination IP address #2,default value: 0.0.0.0 |
| 1.3.6.1.4.1.55508.1.1.2.9 | ScalartrapDestIP3 | read-write | current | The trap destination IP address #3,default value: 0.0.0.0 |
| 1.3.6.1.4.1.55508.1.1.2.10 | ScalartrapDestIP4 | read-write | current | The trap destination IP address #2,default value: 0.0.0.0 |
| 1.3.6.1.4.1.55508.1.2 | NodepowerTables | |||
| 1.3.6.1.4.1.55508.1.2.1 | Tablepower1OutletTable | not-accessible | current | A table list the status of all outlets. |
| 1.3.6.1.4.1.55508.1.2.1.1 | Rowpower1OutletEntry | not-accessible | current | Row definition for the status list. |
| 1.3.6.1.4.1.55508.1.2.1.1.1 | Columnp1OutletSeq | read-only | current | Sequence of table. |
| 1.3.6.1.4.1.55508.1.2.1.1.2 | Columnp1OutletNo | read-only | current | Outlet's No. |
| 1.3.6.1.4.1.55508.1.2.1.1.3 | Columnp1OutletDesc | read-write | current | Outlet's description. |
| 1.3.6.1.4.1.55508.1.2.1.1.4 | Columnp1OutletSocket | read-only | current | Outlet's socket standard description. |
| 1.3.6.1.4.1.55508.1.2.1.1.5 | Columnp1OutletFuse | read-only | current | Outlet's fuse status. Normal or Alarm. |
| 1.3.6.1.4.1.55508.1.2.1.1.6 | Columnp1OutletOnOff | read-write | current | Outlet's ON/OFF status. |
| 1.3.6.1.4.1.55508.1.2.1.1.7 | Columnp1OutletLoad | read-only | current | Outlet's load amperes. A non-negative value indicates the measured load in tenth of amperes. A negative value indicates that a load value was not available. |
| 1.3.6.1.4.1.55508.1.2.1.1.8 | Columnp1OutletLoadLowLimit | read-write | current | Outlet's load low-limit in amperes. A non-negative value indicates the measured load in tenth of amperes. A negative value indicates that a load value was not … |
| 1.3.6.1.4.1.55508.1.2.1.1.9 | Columnp1OutletLoadHighLimit | read-write | current | Outlet's load high-limit in amperes. A non-negative value indicates the measured load in tenth of amperes. A negative value indicates that a load value was not… |
| 1.3.6.1.4.1.55508.1.2.1.1.10 | Columnp1OutletEnergy | read-only | current | Outlet's energy (unit in 0.01kWh). A non-negative value indicates the measured energy hundredth of kWh. A negative value indicates that the energy value was no… |
| 1.3.6.1.4.1.55508.1.2.1.1.11 | Columnp1Power | read-only | current | Outlet's active power (unit in 0.01W). A non-negative value indicates the measured active power hundredth of W. A negative value indicates that the active powe… |
| 1.3.6.1.4.1.55508.1.2.1.1.12 | Columnp1PowerFactor | read-only | current | Outlet's power factor (unit in 0.01). A non-negative value indicates the measured power factor hundredth. A negative value indicates that the power factor valu… |
| 1.3.6.1.4.1.55508.1.2.2 | Tablepower2OutletTable | not-accessible | current | A table list the status of all outlets. |
| 1.3.6.1.4.1.55508.1.2.2.1 | Rowpower2OutletEntry | not-accessible | current | Row definition for the status list. |
| 1.3.6.1.4.1.55508.1.2.2.1.1 | Columnp2OutletSeq | read-only | current | Sequence of table. |
| 1.3.6.1.4.1.55508.1.2.2.1.2 | Columnp2OutletNo | read-only | current | Outlet's No. |
| 1.3.6.1.4.1.55508.1.2.2.1.3 | Columnp2OutletDesc | read-write | current | Outlet's description. |
| 1.3.6.1.4.1.55508.1.2.2.1.4 | Columnp2OutletSocket | read-only | current | Outlet's socket standard description. |
| 1.3.6.1.4.1.55508.1.2.2.1.5 | Columnp2OutletFuse | read-only | current | Outlet's fuse status. Normal or Alarm. |
| 1.3.6.1.4.1.55508.1.2.2.1.6 | Columnp2OutletOnOff | read-write | current | Outlet's ON/OFF status. |
| 1.3.6.1.4.1.55508.1.2.2.1.7 | Columnp2OutletLoad | read-only | current | Outlet's load amperes. A non-negative value indicates the measured load in tenth of amperes. A negative value indicates that a load value was not available. |
| 1.3.6.1.4.1.55508.1.2.2.1.8 | Columnp2OutletLoadLowLimit | read-write | current | Outlet's load low-limit in amperes. A non-negative value indicates the measured load in tenth of amperes. A negative value indicates that a load value was not … |
| 1.3.6.1.4.1.55508.1.2.2.1.9 | Columnp2OutletLoadHighLimit | read-write | current | Outlet's load high-limit in amperes. A non-negative value indicates the measured load in tenth of amperes. A negative value indicates that a load value was not… |
| 1.3.6.1.4.1.55508.1.2.2.1.10 | Columnp2OutletEnergy | read-only | current | Outlet's energy (unit in 0.01kWh). A non-negative value indicates the measured energy hundredth of kWh. A negative value indicates that the energy value was no… |
| 1.3.6.1.4.1.55508.1.2.2.1.11 | Columnp2Power | read-only | current | Outlet's active power (unit in 0.01W). A non-negative value indicates the measured active power hundredth of W. A negative value indicates that the active powe… |
| 1.3.6.1.4.1.55508.1.2.2.1.12 | Columnp2PowerFactor | read-only | current | Outlet's power factor (unit in 0.01). A non-negative value indicates the measured power factor hundredth. A negative value indicates that the power factor valu… |
| 1.3.6.1.4.1.55508.1.2.3 | Tablepower3OutletTable | not-accessible | current | A table list the status of all outlets. |
| 1.3.6.1.4.1.55508.1.2.3.1 | Rowpower3OutletEntry | not-accessible | current | Row definition for the status list. |
| 1.3.6.1.4.1.55508.1.2.3.1.1 | Columnp3OutletSeq | read-only | current | Sequence of table. |
| 1.3.6.1.4.1.55508.1.2.3.1.2 | Columnp3OutletNo | read-only | current | Outlet's No. |
| 1.3.6.1.4.1.55508.1.2.3.1.3 | Columnp3OutletDesc | read-write | current | Outlet's description. |
| 1.3.6.1.4.1.55508.1.2.3.1.4 | Columnp3OutletSocket | read-only | current | Outlet's socket standard description. |
| 1.3.6.1.4.1.55508.1.2.3.1.5 | Columnp3OutletFuse | read-only | current | Outlet's fuse status. Normal or Alarm. |
| 1.3.6.1.4.1.55508.1.2.3.1.6 | Columnp3OutletOnOff | read-write | current | Outlet's ON/OFF status. |
| 1.3.6.1.4.1.55508.1.2.3.1.7 | Columnp3OutletLoad | read-only | current | Outlet's load amperes. A non-negative value indicates the measured load in tenth of amperes. A negative value indicates that a load value was not available. |
| 1.3.6.1.4.1.55508.1.2.3.1.8 | Columnp3OutletLoadLowLimit | read-write | current | Outlet's load low-limit in amperes. A non-negative value indicates the measured load in tenth of amperes. A negative value indicates that a load value was not … |
| 1.3.6.1.4.1.55508.1.2.3.1.9 | Columnp3OutletLoadHighLimit | read-write | current | Outlet's load high-limit in amperes. A non-negative value indicates the measured load in tenth of amperes. A negative value indicates that a load value was not… |
| 1.3.6.1.4.1.55508.1.2.3.1.10 | Columnp3OutletEnergy | read-only | current | Outlet's energy (unit in 0.01kWh). A non-negative value indicates the measured energy hundredth of kWh. A negative value indicates that the energy value was no… |
| 1.3.6.1.4.1.55508.1.2.3.1.11 | Columnp3Power | read-only | current | Outlet's active power (unit in 0.01W). A non-negative value indicates the measured active power hundredth of W. A negative value indicates that the active powe… |
| 1.3.6.1.4.1.55508.1.2.3.1.12 | Columnp3PowerFactor | read-only | current | Outlet's power factor (unit in 0.01). A non-negative value indicates the measured power factor hundredth. A negative value indicates that the power factor valu… |
| 1.3.6.1.4.1.55508.1.2.4 | TablepowerBranchTable | not-accessible | current | A table list the status of all branchs. |
| 1.3.6.1.4.1.55508.1.2.4.1 | RowpowerBranchEntry | not-accessible | current | Row definition for the status list. |
| 1.3.6.1.4.1.55508.1.2.4.1.1 | ColumnbranchSeq | read-only | current | Sequence of table. |
| 1.3.6.1.4.1.55508.1.2.4.1.2 | ColumnbranchRate | read-only | current | Branch rated current (unit in 0.01A). A non-negative value indicates the measured load in hundredth of amperes. A negative value indicates that a load value wa… |
| 1.3.6.1.4.1.55508.1.2.4.1.3 | ColumnbranchVoltage | read-only | current | The voltage of branch (unit in 0.1V). A non-negative value indicates the measured voltage in tenth of volts. A negative value indicates that a voltage value wa… |
| 1.3.6.1.4.1.55508.1.2.4.1.4 | ColumnbranchEnergy | read-only | current | The energy of branch (unit in 0.1kWh). A non-negative value indicates the measured energy tenth of kWh. A negative value indicates that the energy value was no… |
| 1.3.6.1.4.1.55508.1.2.4.1.5 | ColumnbranchPower | read-only | current | The active power of branch (unit in W). A non-negative value indicates the measured active power. A negative value indicates that the active power value was no… |
| 1.3.6.1.4.1.55508.1.2.4.1.6 | ColumnbranchPowerFactor | read-only | current | The power factor of branch (unit in 0.01). A non-negative value indicates the measured power factor hundredth. A negative value indicates that the power factor… |
| 1.3.6.1.4.1.55508.1.2.4.1.7 | ColumnbranchLoad | read-only | current | The load of branch (unit in 0.01A). A non-negative value indicates the measured load in hundredth of amperes. A negative value indicates that a load value was … |
| 1.3.6.1.4.1.55508.1.2.4.1.8 | ColumnbranchLoadHighLimit | read-write | current | Branch's load high-limit in amperes. A non-negative value indicates the measured load in hundredth of amperes. A negative value indicates that a load value was… |
| 1.3.6.1.4.1.55508.1.2.4.1.9 | ColumnbranchNo | read-only | current | Branch's No. |
| 1.3.6.1.4.1.55508.1.2.4.1.10 | ColumnbranchBreaker | read-only | current | Breaker's status. |
| 1.3.6.1.4.1.55508.1.2.5 | TablepowerSummaryTable | not-accessible | current | A table list the summary status information for PDU. |
| 1.3.6.1.4.1.55508.1.2.5.1 | RowpowerSummaryEntry | not-accessible | current | Row definition for the status list. |
| 1.3.6.1.4.1.55508.1.2.5.1.1 | ColumnpowerSeq | read-only | current | Sequence of table. |
| 1.3.6.1.4.1.55508.1.2.5.1.2 | ColumnpowerID | read-only | current | Outlet's No. |
| 1.3.6.1.4.1.55508.1.2.5.1.3 | ColumnpowerName | read-write | current | The PDU description. |
| 1.3.6.1.4.1.55508.1.2.5.1.4 | ColumnpowerType | read-only | current | The PDU type. |
| 1.3.6.1.4.1.55508.1.2.5.1.5 | ColumnpowerModel | read-only | current | The PDU type. |
| 1.3.6.1.4.1.55508.1.2.5.1.6 | ColumnpowerOnGap | read-write | current | The interval of outlets' of the PDU when power on. |
| 1.3.6.1.4.1.55508.1.2.5.1.7 | ColumntotalLoadA | read-only | current | The A total load of the PDU when it is Three-phase input, or the total load of the PDU when it is Single-phase input. A non-negative value indicates the measur… |
| 1.3.6.1.4.1.55508.1.2.5.1.8 | ColumntotalLoadALowLimit | read-write | current | The A total load low limit of the PDU when it is Three-phase input, or the total load of the PDU when it is Single-phase input. A non-negative value indicates … |
| 1.3.6.1.4.1.55508.1.2.5.1.9 | ColumntotalLoadAHighLimit | read-write | current | The A total load high limit of the PDU when it is Three-phase input, or the total load of the PDU when it is Single-phase input. A non-negative value indicates… |
| 1.3.6.1.4.1.55508.1.2.5.1.10 | ColumntotalLoadB | read-only | current | The B total load of the PDU when it is Three-phase input. A non-negative value indicates the measured load in tenth of amperes. A negative value indicates that… |
| 1.3.6.1.4.1.55508.1.2.5.1.11 | ColumntotalLoadBLowLimit | read-write | current | The B total load low limit of the PDU when it is Three-phase input, A non-negative value indicates the measured load in tenth of amperes. A negative value indi… |
| 1.3.6.1.4.1.55508.1.2.5.1.12 | ColumntotalLoadBHighLimit | read-write | current | The B total load high limit of the PDU when it is Three-phase input, A non-negative value indicates the measured load in tenth of amperes. A negative value ind… |
| 1.3.6.1.4.1.55508.1.2.5.1.13 | ColumntotalLoadC | read-only | current | The C total load of the PDU when it is Three-phase input, A non-negative value indicates the measured load in tenth of amperes. A negative value indicates that… |
| 1.3.6.1.4.1.55508.1.2.5.1.14 | ColumntotalLoadCLowLimit | read-write | current | The C total load low limit of the PDU when it is Three-phase input, A non-negative value indicates the measured load in tenth of amperes. A negative value indi… |
| 1.3.6.1.4.1.55508.1.2.5.1.15 | ColumntotalLoadCHighLimit | read-write | current | The C total load high limit of the PDU when it is Three-phase input, A non-negative value indicates the measured load in tenth of amperes. A negative value ind… |
| 1.3.6.1.4.1.55508.1.2.5.1.16 | ColumnvoltageA | read-only | current | The A voltage of the PDU when it is Three-phase input, or the voltage of the PDU when it is Single-phase input, A non-negative value indicates the measured val… |
| 1.3.6.1.4.1.55508.1.2.5.1.17 | ColumnvoltageB | read-only | current | The B voltage of the PDU when it is Three-phase input, A non-negative value indicates the measured value in volts. A negative value indicates that a value was … |
| 1.3.6.1.4.1.55508.1.2.5.1.18 | ColumnvoltageC | read-only | current | The C voltage of the PDU when it is Three-phase input, A non-negative value indicates the measured value in volts. A negative value indicates that a value was … |
| 1.3.6.1.4.1.55508.1.2.5.1.19 | ColumnpowerEnergy | read-only | current | The ACC. energy of the PDU, A non-negative value indicates the measured value in tenth of kWh. A negative value indicates that a value was not available. |
| 1.3.6.1.4.1.55508.1.2.5.1.20 | ColumnactivePowerA | read-only | current | The active power of the input power A. A non-negative value indicates the measured value in tenth of watts. A negative value indicates that a value was not ava… |
| 1.3.6.1.4.1.55508.1.2.5.1.21 | ColumnratedPowerA | read-only | current | The rated power of the input power B. A non-negative value indicates the measured value in tenth of watts. A negative value indicates that a value was not avai… |
| 1.3.6.1.4.1.55508.1.2.5.1.22 | ColumnremainPowerA | read-only | current | The remain power of the input power A. A non-negative value indicates the measured value in tenth of watts. A negative value indicates that a value was not ava… |
| 1.3.6.1.4.1.55508.1.2.5.1.23 | ColumnapparentPowerA | read-only | current | The apparent power of the input power A. A non-negative value indicates the measured value in tenth of W. A negative value indicates that a value was not avail… |
| 1.3.6.1.4.1.55508.1.2.5.1.24 | ColumnpowerFactorA | read-only | current | The power factor of the input power A. A non-negative value indicates the power factor in hundredth. A negative value indicates that the power factor was not a… |
| 1.3.6.1.4.1.55508.1.2.5.1.25 | ColumnactivePowerB | read-only | current | The active power of the input power B. A non-negative value indicates the measured value in tenth of watts. A negative value indicates that a value was not ava… |
| 1.3.6.1.4.1.55508.1.2.5.1.26 | ColumnratedPowerB | read-only | current | The rated power of the input power B. A non-negative value indicates the measured value in tenth of watts. A negative value indicates that a value was not avai… |
| 1.3.6.1.4.1.55508.1.2.5.1.27 | ColumnremainPowerB | read-only | current | The remain power of the input power B. A non-negative value indicates the measured value in tenth of watts. A negative value indicates that a value was not ava… |
| 1.3.6.1.4.1.55508.1.2.5.1.28 | ColumnapparentPowerB | read-only | current | The apparent power of the input power B. A non-negative value indicates the measured value in tenth of W. A negative value indicates that a value was not avail… |
| 1.3.6.1.4.1.55508.1.2.5.1.29 | ColumnpowerFactorB | read-only | current | The power factor of the input power B. A non-negative value indicates the power factor in hundredth. A negative value indicates that the power factor was not a… |
| 1.3.6.1.4.1.55508.1.2.5.1.30 | ColumnactivePowerC | read-only | current | The active power of the input power C. A non-negative value indicates the measured value in tenth of watts. A negative value indicates that a value was not ava… |
| 1.3.6.1.4.1.55508.1.2.5.1.31 | ColumnratedPowerC | read-only | current | The rated power of the input power C. A non-negative value indicates the measured value in tenth of watts. A negative value indicates that a value was not avai… |
| 1.3.6.1.4.1.55508.1.2.5.1.32 | ColumnremainPowerC | read-only | current | The remain power of the input powerC. A non-negative value indicates the measured value in tenth of watts. A negative value indicates that a value was not avai… |
| 1.3.6.1.4.1.55508.1.2.5.1.33 | ColumnapparentPowerC | read-only | current | The apparent power of the input power C. A non-negative value indicates the measured value in tenth of W. A negative value indicates that a value was not avail… |
| 1.3.6.1.4.1.55508.1.2.5.1.34 | ColumnpowerFactorC | read-only | current | The power factor of the input power C. A non-negative value indicates the power factor in hundredth. A negative value indicates that the power factor was not a… |
| 1.3.6.1.4.1.55508.1.2.5.1.35 | ColumnatsInput | read-only | current | The power input of ATS, which would be A or B. |
| 1.3.6.1.4.1.55508.1.2.5.1.36 | ColumnatsPriority | read-write | current | The priority input of ATS. |
| 1.3.6.1.4.1.55508.1.2.5.1.37 | ColumnatsAVoltage | read-only | current | The A voltage of ATS, A non-negative value indicates the measured value in volts. A negative value indicates that a value was not available. |
| 1.3.6.1.4.1.55508.1.2.5.1.38 | ColumnatsBVoltage | read-only | current | The B voltage of ATS, A non-negative value indicates the measured value in volts. A negative value indicates that a value was not available. |
| 1.3.6.1.4.1.55508.1.2.5.1.39 | ColumnatsAEnergy | read-only | current | The A energy of ATS, A non-negative value indicates the measured value in tenth of kWh. A negative value indicates that a value was not available. |
| 1.3.6.1.4.1.55508.1.2.5.1.40 | ColumnatsBEnergy | read-only | current | The B energy of ATS, A non-negative value indicates the measured value in tenth of kWh. A negative value indicates that a value was not available. |
| 1.3.6.1.4.1.55508.1.2.5.1.41 | ColumnatsSwitchLow | read-write | current | The switch voltage low-limit of ATS, A non-negative value indicates the measured value in volts. A negative value indicates that a value was not available. |
| 1.3.6.1.4.1.55508.1.2.5.1.42 | ColumnatsSwitchHigh | read-write | current | The switch voltage high-limit of ATS, A non-negative value indicates the measured value in volts. A negative value indicates that a value was not available. |
| 1.3.6.1.4.1.55508.1.2.5.1.43 | ColumnatsSwitchTime | read-write | current | The switch time of ATS. A non-negative value indicates the measured load in minutes. A negative value indicates that a time value was not available. |
| 1.3.6.1.4.1.55508.1.2.5.1.44 | ColumnatsSwitchLock | read-write | current | The switch lock status of ATS. |
| 1.3.6.1.4.1.55508.1.2.5.1.45 | ColumnatsMonitor | read-write | current | The stability monitor status of ATS. |
| 1.3.6.1.4.1.55508.1.2.5.1.46 | ColumnallOutletsSwitch | read-write | current | To set the switches of all outlets belong to this Power(PDU). A negative value none(-1) would be returned for GET command. Nothing to do when SET with the valu… |
| 1.3.6.1.4.1.55508.1.2.5.1.47 | Columnfrequency | read-only | current | The frequency value of the input. A non-negative value indicates the measured value in hertz. |
| 1.3.6.1.4.1.55508.1.2.5.1.48 | ColumnvoltageALowLimit | read-write | current | The A voltage low limit of the PDU when it is Three-phase input, or the voltage low limit of the PDU when it is Single-phase input. A non-negative value indica… |
| 1.3.6.1.4.1.55508.1.2.5.1.49 | ColumnvoltageAHighLimit | read-write | current | The A voltage high limit of the PDU when it is Three-phase input, or the voltage high limit of the PDU when it is Single-phase input. A non-negative value indi… |
| 1.3.6.1.4.1.55508.1.2.5.1.50 | ColumnvoltageBLowLimit | read-write | current | The B voltage low limit of the PDU when it is Three-phase input. A non-negative value indicates the measured value in volts. A negative value indicates that a … |
| 1.3.6.1.4.1.55508.1.2.5.1.51 | ColumnvoltageBHighLimit | read-write | current | The B voltage high limit of the PDU when it is Three-phase input. A non-negative value indicates the measured value in volts. A negative value indicates that a… |
| 1.3.6.1.4.1.55508.1.2.5.1.52 | ColumnvoltageCLowLimit | read-write | current | The C voltage low limit of the PDU when it is Three-phase input. A non-negative value indicates the measured value in volts. A negative value indicates that a … |
| 1.3.6.1.4.1.55508.1.2.5.1.53 | ColumnvoltageCHighLimit | read-write | current | The C voltage high limit of the PDU when it is Three-phase input. A non-negative value indicates the measured value in volts. A negative value indicates that a… |
| 1.3.6.1.4.1.55508.1.3 | NodeenvironmentTable | |||
| 1.3.6.1.4.1.55508.1.3.1 | TablesensorTable | not-accessible | current | A table list the status of all external sensors. |
| 1.3.6.1.4.1.55508.1.3.1.1 | RowsensorEntry | not-accessible | current | Row definition for the status list. |
| 1.3.6.1.4.1.55508.1.3.1.1.1 | ColumnsensorSeq | read-only | current | Sequence of table. |
| 1.3.6.1.4.1.55508.1.3.1.1.2 | ColumnsensorNo | read-only | current | Sensor's No. |
| 1.3.6.1.4.1.55508.1.3.1.1.3 | ColumnsensorType | read-only | current | Sensor's Type. |
| 1.3.6.1.4.1.55508.1.3.1.1.4 | ColumnsensorID | read-only | current | Sensor's ID. |
| 1.3.6.1.4.1.55508.1.3.1.1.5 | ColumnsensorLocation | read-write | current | Sensor's location. |
| 1.3.6.1.4.1.55508.1.3.1.1.6 | ColumnsensorValue | read-only | current | Sensor's value of smog/door/water. |
| 1.3.6.1.4.1.55508.1.3.1.1.8 | ColumntemperatureLowLimit | read-write | current | Temperature low limit. NOTE: the UNIT is Deg.C or Deg.F which is select from the setting WEB page. |
| 1.3.6.1.4.1.55508.1.3.1.1.10 | ColumnhumidityValue | read-only | current | The humidity measured by the sensor. A non-negative value indicates the measured humidity in percentage relative humidity. A negative value indicates that a hu… |
| 1.3.6.1.4.1.55508.1.3.1.1.11 | ColumnhumidityLowLimit | read-write | current | Humidity low limit. |
| 1.3.6.1.4.1.55508.1.3.1.1.12 | ColumnhumidityHighLimit | read-write | current | Humidity high limit. |
| 1.3.6.1.4.1.55508.1.3.1.1.13 | ColumnwindValue | read-only | current | The wind speed is measured by the sensor. A non-negative value indicates the measured wind speed. A negative value indicates that a wind speed value was not av… |
| 1.3.6.1.4.1.55508.1.3.1.1.14 | ColumnwindLowLimit | read-write | current | Wind speed low limit. see windValue for more detail. |
| 1.3.6.1.4.1.55508.1.3.1.1.15 | ColumnwindHighLimit | read-write | current | Wind speed high limit. see windValue for more detail. |
| 1.3.6.1.4.1.55508.1.3.2 | TableinternalSensorTable | not-accessible | current | A table list the status of internal sensors. |
| 1.3.6.1.4.1.55508.1.3.2.1 | RowinternalSensorEntry | not-accessible | current | Row definition for the status list. |
| 1.3.6.1.4.1.55508.1.3.2.1.1 | ColumninternalSensorSeq | read-only | current | Sequence of table. |
| 1.3.6.1.4.1.55508.1.3.2.1.2 | ColumnfanStatus | read-only | current | Fan's status. Normal or Alarm. |
| 1.3.6.1.4.1.55508.1.3.2.1.3 | ColumntemperatureValue | read-only | current | Internal temperature Value. The UNIT is Deg.C. |
| 1.3.6.1.4.1.55508.1.3.2.1.4 | ColumntemperatureHighLimit | read-write | current | Internal temperature high limit. The UNIT is Deg.C. |
| 1.3.6.1.4.1.55508.1.3.2.1.5 | ColumntemperatureStatus | read-only | current | Temperature's status. Normal or Alarm. |
| 1.3.6.1.4.1.55508.1.100 | NodenetPowerTraps | |||
| 1.3.6.1.4.1.55508.1.100.1 | NodenetPowerPduAtsEvents | |||
| 1.3.6.1.4.1.55508.1.100.1.1 | NotificationfuseEvent | current | Fuse event for the PDU outlets. The event would occurred when the fuse is burned/repaired. NMS can check the bound OID 'eventType' for handling the trap. | |
| 1.3.6.1.4.1.55508.1.100.1.2 | NotificationloadEvent | current | Load event for the PDU outlets and total power. The event would occurred when load is lower/higher than the limit setting or recovery to normal. NMS can check … | |
| 1.3.6.1.4.1.55508.1.100.1.3 | NotificationtemperatureSensorEvent | current | Temperature sensor event. The event would occurred when temperature value is lower/higher than the limit setting or recovery to normal. NMS can check the bound… | |
| 1.3.6.1.4.1.55508.1.100.1.4 | NotificationhumiditySensorEvent | current | Humidity sensor event.The event would occurred when humidity value is lower/higher than the limit setting or recovery to normal. NMS can check the bound OID 'e… | |
| 1.3.6.1.4.1.55508.1.100.1.5 | NotificationwindSensorEvent | current | Wind sensor event.The event would occurred when wind speed value is lower/higher than the limit setting or recovery to normal. NMS can check the bound OID 'eve… | |
| 1.3.6.1.4.1.55508.1.100.1.6 | NotificationenvironmentSensorEvent | current | Environment sensor event, including smog, water, door and so on. The event would occurred when the sensor detects an alarm or recovery. NMS can check the bound… | |
| 1.3.6.1.4.1.55508.1.100.1.7 | NotificationatsSwitchingEvent | current | ATS switch event. The event would occurred when ATS switched the input power A to B, or B to A. NMS can check the bound OID 'eventType' for handling the trap. | |
| 1.3.6.1.4.1.55508.1.100.1.8 | NotificationatsVoltageEvent | current | ATS voltage event. The event would occurred when voltage is lower/higher than the limit setting or recovery to normal. NMS can check the bound OID 'eventType' … | |
| 1.3.6.1.4.1.55508.1.100.1.9 | NotificationsnmpQueryTimeoutEvent | current | Snmp Query Timeout event for the PDU snmp connection. The event would occurred when no any query until timeout is come. NMS can check the bound OID 'eventType'… | |
| 1.3.6.1.4.1.55508.1.100.1.10 | NotificationvoltageEvent | current | Voltage event for the PDU input. The event would occurred when voltage is lower/higher than the limit setting or recovery to normal. NMS can check the bound OI… | |
| 1.3.6.1.4.1.55508.1.100.1.11 | NotificationconnectEvent | current | Connect event for the PDU failure. The event would occurred when the power module or outlets module is disconnect/repaired. NMS can check the bound OID 'eventT… |