SNR-ERD-4

157 objects
The MIB module for SNR-ERD-4
Imported Objects
RFC1155-SMICounter enterprises IpAddress
RFC1213-MIBDisplayString
SNMPv2-CONFNOTIFICATION-GROUP
SNMPv2-SMIMODULE-IDENTITY NOTIFICATION-TYPE OBJECT-IDENTITY OBJECT-TYPE
OIDNameAccessStatusDescription
1.3.6.1.4.1.40418Nodesnr
1.3.6.1.4.1.40418.2Nodesnr-erd
1.3.6.1.4.1.40418.2.6Identitysnr-erd-4The MIB module for SNR-ERD-4
1.3.6.1.4.1.40418.2.6.0Nodetraps
1.3.6.1.4.1.40418.2.6.0.1NotificationDI1AlarmcurrentInput 1 Alarm fires
1.3.6.1.4.1.40418.2.6.0.2NotificationDI1ReleasecurrentInput 1 Alarm released
1.3.6.1.4.1.40418.2.6.0.3NotificationDI2AlarmcurrentInput 2 Alarm fires
1.3.6.1.4.1.40418.2.6.0.4NotificationDI2ReleasecurrentInput 2 Alarm released
1.3.6.1.4.1.40418.2.6.0.5NotificationDI3AlarmcurrentInput 3 Alarm fires
1.3.6.1.4.1.40418.2.6.0.6NotificationDI3ReleasecurrentInput 3 Alarm released
1.3.6.1.4.1.40418.2.6.0.7NotificationDI4AlarmcurrentInput 4 Alarm fires
1.3.6.1.4.1.40418.2.6.0.8NotificationDI4ReleasecurrentInput 4 Alarm released
1.3.6.1.4.1.40418.2.6.0.9NotificationDI5AlarmcurrentInput 5 Alarm fires
1.3.6.1.4.1.40418.2.6.0.10NotificationDI5ReleasecurrentInput 5 Alarm released
1.3.6.1.4.1.40418.2.6.0.11NotificationuSenseAlarmcurrentSignifies that Phase sensor Alarm fires
1.3.6.1.4.1.40418.2.6.0.12NotificationuSenseReleasecurrentSignifies that Phase sensor Alarm released
1.3.6.1.4.1.40418.2.6.0.13NotificationreloutOncurrentSignifies that Rele was swithed on by Thermostat or Gigrostat mode
1.3.6.1.4.1.40418.2.6.0.14NotificationreloutOffcurrentSignifies that Rele was swithed off by Thermostat or Gigrostat mode
1.3.6.1.4.1.40418.2.6.0.15NotificationDO1OncurrentSignifies that Output 1 was swithed on by Thermostat or Gigrostat mode
1.3.6.1.4.1.40418.2.6.0.16NotificationDO1OffcurrentSignifies that Output 1 was swithed off by Thermostat or Gigrostat mode
1.3.6.1.4.1.40418.2.6.0.17NotificationDO2OncurrentSignifies that Output 2 was swithed on by Thermostat or Gigrostat mode
1.3.6.1.4.1.40418.2.6.0.18NotificationDO2OffcurrentSignifies that Output 2 was swithed off by Thermostat or Gigrostat mode
1.3.6.1.4.1.40418.2.6.0.19NotificationDO3OncurrentSignifies that Output 3 was swithed on by Thermostat or Gigrostat mode
1.3.6.1.4.1.40418.2.6.0.20NotificationDO3OffcurrentSignifies that Output 3 was swithed off by Thermostat or Gigrostat mode
1.3.6.1.4.1.40418.2.6.0.21NotificationDO4OncurrentSignifies that Output 4 was swithed on by Thermostat or Gigrostat mode
1.3.6.1.4.1.40418.2.6.0.22NotificationDO4OffcurrentSignifies that Output 4 was swithed off by Thermostat or Gigrostat mode
1.3.6.1.4.1.40418.2.6.0.23NotificationDO5OncurrentSignifies that Output 5 was swithed on by Thermostat or Gigrostat mode
1.3.6.1.4.1.40418.2.6.0.24NotificationDO5OffcurrentSignifies that Output 5 was swithed off by Thermostat or Gigrostat mode
1.3.6.1.4.1.40418.2.6.0.29NotificationtempSensorAlarmcurrentTemperature alarm
1.3.6.1.4.1.40418.2.6.0.30NotificationtempSensorReleasecurrentTemperature release
1.3.6.1.4.1.40418.2.6.0.31NotificationadcSensorAlarmcurrentVoltage sensor alarm
1.3.6.1.4.1.40418.2.6.0.32NotificationadcSensorReleasecurrentVoltage sensor release
1.3.6.1.4.1.40418.2.6.0.33NotificationhumSensorAlarmcurrentHumidity alarm
1.3.6.1.4.1.40418.2.6.0.34NotificationhumSensorReleasecurrentHumidity release
1.3.6.1.4.1.40418.2.6.0.36Notificationtask1DonecurrentTask 1 done
1.3.6.1.4.1.40418.2.6.0.37Notificationtask2DonecurrentTask 2 done
1.3.6.1.4.1.40418.2.6.0.38Notificationtask3DonecurrentTask 3 done
1.3.6.1.4.1.40418.2.6.0.39Notificationtask4DonecurrentTask 4 done
1.3.6.1.4.1.40418.2.6.0.45NotificationpingLostcurrentPing lost
1.3.6.1.4.1.40418.2.6.0.47NotificationbatteryChargeLowcurrentBattery charge is low
1.3.6.1.4.1.40418.2.6.0.50NotificationupsUtilityFailcurrentUPS utility fail
1.3.6.1.4.1.40418.2.6.0.51NotificationupsUtilityOkcurrentUPS utility OK
1.3.6.1.4.1.40418.2.6.1Nodemeasurements
1.3.6.1.4.1.40418.2.6.1.1NodeoneWire
1.3.6.1.4.1.40418.2.6.1.1.1TabledtsTablenot-accessiblecurrentA list of temperature sensors values
1.3.6.1.4.1.40418.2.6.1.1.1.1RowdtsEntrynot-accessiblecurrentAn entry (conceptual row) in the dtsTable
1.3.6.1.4.1.40418.2.6.1.1.1.1.1ColumndtsIdread-onlycurrentTemperature sensor id
1.3.6.1.4.1.40418.2.6.1.1.1.1.2ColumndtsNameread-writecurrentName (max 20)
1.3.6.1.4.1.40418.2.6.1.1.1.1.3ColumndtsTempread-onlycurrentTemperature value
1.3.6.1.4.1.40418.2.6.1.1.2TableshuntTablenot-accessiblecurrentA list of SNR-SHUNT values
1.3.6.1.4.1.40418.2.6.1.1.2.1RowshuntEntrynot-accessiblecurrentAn entry (conceptual row) in the shuntTable
1.3.6.1.4.1.40418.2.6.1.1.2.1.1ColumnshuntIdread-onlycurrentSNR-SHUNT id
1.3.6.1.4.1.40418.2.6.1.1.2.1.2ColumnshuntNameread-writecurrentName (max 20)
1.3.6.1.4.1.40418.2.6.1.1.2.1.3ColumnshuntTempread-onlycurrentTemperature value
1.3.6.1.4.1.40418.2.6.1.1.2.1.4ColumnshuntVoltread-writecurrentVoltage
1.3.6.1.4.1.40418.2.6.1.1.2.1.5ColumnshuntCurrentread-writecurrentCurrent
1.3.6.1.4.1.40418.2.6.1.1.2.1.6ColumnshuntChrgLvlread-writecurrentBattery charge level (0..100%)
1.3.6.1.4.1.40418.2.6.1.1.2.1.7ColumnshuntChrgCapread-onlycurrentCharge capacity
1.3.6.1.4.1.40418.2.6.1.1.2.1.8ColumnshuntDischCapread-onlycurrentDischarge capacity
1.3.6.1.4.1.40418.2.6.1.1.2.1.9ColumnshuntEndOfChrgread-onlycurrentEnd of charge time
1.3.6.1.4.1.40418.2.6.1.1.2.1.10ColumnshuntDiscnread-onlycurrentDisconnect time
1.3.6.1.4.1.40418.2.6.1.1.2.1.11ColumnshuntBatLiveread-onlycurrentBattery using period
1.3.6.1.4.1.40418.2.6.1.1.2.1.12ColumnshuntDischTimeread-onlycurrentTime to full discharge
1.3.6.1.4.1.40418.2.6.1.2ScalaradcSensorread-onlycurrentADC sensor value
1.3.6.1.4.1.40418.2.6.1.8ScalartemperatureDHTread-onlycurrentDHT temperature value
1.3.6.1.4.1.40418.2.6.1.9ScalarhumidityDHTread-onlycurrentDHT humidity value
1.3.6.1.4.1.40418.2.6.1.10TablerfshtpTablenot-accessiblecurrentA list of wireless sensors values
1.3.6.1.4.1.40418.2.6.1.10.1RowrfshtpEntrynot-accessiblecurrentAn entry (conceptual row) in the wrlssSensTable
1.3.6.1.4.1.40418.2.6.1.10.1.1ColumnrfshtpIdread-onlycurrentWireless sensor id
1.3.6.1.4.1.40418.2.6.1.10.1.2ColumnrfshtpNameread-writecurrentName (max 20)
1.3.6.1.4.1.40418.2.6.1.10.1.3ColumnrfshtpTempread-onlycurrentTemperature value
1.3.6.1.4.1.40418.2.6.1.10.1.4ColumnrfshtpHumread-onlycurrentHumidity value
1.3.6.1.4.1.40418.2.6.1.10.1.5ColumnrfshtpPresread-onlycurrentPressure value
1.3.6.1.4.1.40418.2.6.1.30Nodesp
1.3.6.1.4.1.40418.2.6.1.30.1TablersshtpTablenot-accessiblecurrentA list of SNR-RSsensor-H/T/P values
1.3.6.1.4.1.40418.2.6.1.30.1.1RowrsshtpEntrynot-accessiblecurrentAn entry (conceptual row) in the rsshtpTable
1.3.6.1.4.1.40418.2.6.1.30.1.1.1ColumnrsshtpIdentread-onlycurrentSNR-RSsensor-H/T/P id
1.3.6.1.4.1.40418.2.6.1.30.1.1.2ColumnrsshtpNameread-writecurrentName (max 20)
1.3.6.1.4.1.40418.2.6.1.30.1.1.3ColumnrsshtpTempread-onlycurrentTemperature value
1.3.6.1.4.1.40418.2.6.1.30.1.1.4ColumnrsshtpHumread-onlycurrentHumidity value
1.3.6.1.4.1.40418.2.6.1.30.1.1.6ColumnrsshtpPssrread-onlycurrentPressure value
1.3.6.1.4.1.40418.2.6.1.30.5TablerscounterTablenot-accessiblecurrentA list of SNR-RS-Counter
1.3.6.1.4.1.40418.2.6.1.30.5.1RowrscounterEntrynot-accessiblecurrentAn entry (conceptual row) in the rscounterTable
1.3.6.1.4.1.40418.2.6.1.30.5.1.1ColumnrscounterIdentread-onlycurrentSNR-RS-Counter id
1.3.6.1.4.1.40418.2.6.1.30.5.1.2ColumnrscounterNameread-writecurrentName (max 20)
1.3.6.1.4.1.40418.2.6.1.30.100Tablersshtp1WTablenot-accessiblecurrentA list of temperature sensors are connected to SNR-RSsensor-H/T/P
1.3.6.1.4.1.40418.2.6.1.30.100.1Rowrsshtp1WEntrynot-accessiblecurrentAn entry (conceptual row) in the rsshtp1WTable
1.3.6.1.4.1.40418.2.6.1.30.100.1.1Columnrsshtp1WIdentread-onlycurrentTemperature sensor id
1.3.6.1.4.1.40418.2.6.1.30.100.1.2Columnrsshtp1WNameread-writecurrentName (max 20)
1.3.6.1.4.1.40418.2.6.1.30.100.1.3Columnrsshtp1WTempread-onlycurrentTemperature value
1.3.6.1.4.1.40418.2.6.1.30.100.1.4Columnrsshtp1WMasterread-onlycurrentName of the SNR-RSsensor-H/T/P which this temperature sensor is connected to
1.3.6.1.4.1.40418.2.6.1.30.100.1.10ColumntempCritNotifread-writecurrentEnable notifications on the critical temperature
1.3.6.1.4.1.40418.2.6.1.30.100.1.15ColumntempCritMinread-writecurrentMinimal critical temperature. Up to -55 \B0C
1.3.6.1.4.1.40418.2.6.1.30.100.1.16ColumntempCritMaxread-writecurrentMaximum critical temperature. Up to +125\B0C
1.3.6.1.4.1.40418.2.6.1.50NodesensorsTemplate
1.3.6.1.4.1.40418.2.6.1.50.1TablesensorsTemplateTablenot-accessiblecurrentA list of sensors values
1.3.6.1.4.1.40418.2.6.1.50.1.1RowsensorsTemplateEntrynot-accessiblecurrentAn entry (conceptual row) in the rsshtp1WTable
1.3.6.1.4.1.40418.2.6.1.50.1.1.1ColumnsensorsTemplateValueread-onlycurrentCurrent value
1.3.6.1.4.1.40418.2.6.1.50.1.1.2ColumnsensorsTemplateNameread-writecurrentName
1.3.6.1.4.1.40418.2.6.1.50.2ScalarsensorsTemplateTotalConnectedread-onlycurrentTotal value of connected sensors
1.3.6.1.4.1.40418.2.6.2Nodedio
1.3.6.1.4.1.40418.2.6.2.1TablediTablenot-accessiblecurrentA list of digital inputs values
1.3.6.1.4.1.40418.2.6.2.1.1RowdiEntrynot-accessiblecurrentAn entry (conceptual row) in the diTable
1.3.6.1.4.1.40418.2.6.2.1.1.1ColumndiNameread-onlycurrentDigital input name
1.3.6.1.4.1.40418.2.6.2.1.1.2ColumndiAlarmNameread-writecurrentAlarm name
1.3.6.1.4.1.40418.2.6.2.1.1.3ColumndiStateread-onlycurrentDigital input state
1.3.6.1.4.1.40418.2.6.2.1.1.4ColumndiCntread-writecurrentDigital input impulse counter. Writable for reset only. Set 0 to reset
1.3.6.1.4.1.40418.2.6.2.2TabledoTablenot-accessiblecurrentA list of digital outputs values
1.3.6.1.4.1.40418.2.6.2.2.1RowdoEntrynot-accessiblecurrentAn entry (conceptual row) in the doTable
1.3.6.1.4.1.40418.2.6.2.2.1.1ColumndoNameread-onlycurrentDigital output name
1.3.6.1.4.1.40418.2.6.2.2.1.2ColumndoDeviceNameread-writecurrentDigital output custom name
1.3.6.1.4.1.40418.2.6.2.2.1.3ColumndoStateread-writecurrentDigital output state
1.3.6.1.4.1.40418.2.6.2.2.1.4ColumndoResetDelayread-writecurrentReload period
1.3.6.1.4.1.40418.2.6.2.3ScalaruSenseStateread-onlycurrentVoltage sensor state
1.3.6.1.4.1.40418.2.6.4Nodeserial
1.3.6.1.4.1.40418.2.6.4.1Noders485
1.3.6.1.4.1.40418.2.6.4.1.1ScalarconnectStatusRS485read-onlycurrentRS485 TCP connection status
1.3.6.1.4.1.40418.2.6.4.1.2ScalaripAddrRS485read-onlycurrentRS485 TCP connection IP address
1.3.6.1.4.1.40418.2.6.4.2Noders232
1.3.6.1.4.1.40418.2.6.4.2.1ScalarconnectStatusRS232read-onlycurrentRS232 TCP connection status
1.3.6.1.4.1.40418.2.6.4.2.2ScalaripAddrRS232read-onlycurrentRS232 TCP connection IP address
1.3.6.1.4.1.40418.2.6.5Nodemodules
1.3.6.1.4.1.40418.2.6.5.1Nodegsm
1.3.6.1.4.1.40418.2.6.5.1.1ScalargsmModuleStatusread-onlycurrentGSM module status
1.3.6.1.4.1.40418.2.6.5.1.2ScalargsmStrengthread-onlycurrentSignal level
1.3.6.1.4.1.40418.2.6.5.1.10ScalargsmReconnCountread-onlycurrentNumber of connection attempts
1.3.6.1.4.1.40418.2.6.5.2Noderf
1.3.6.1.4.1.40418.2.6.5.2.1ScalarrfModuleStatusread-onlycurrentStatus of the rf module
1.3.6.1.4.1.40418.2.6.10Nodeoptions
1.3.6.1.4.1.40418.2.6.10.1ScalardataTyperead-writecurrentValues data type
1.3.6.1.4.1.40418.2.6.10.10Nodecrit
1.3.6.1.4.1.40418.2.6.10.10.20ScalarhumCritread-writecurrentCritical humidity. From 0 to 100%
1.3.6.1.4.1.40418.2.6.10.10.30ScalaradcCritMinread-writecurrentADC IN critical min
1.3.6.1.4.1.40418.2.6.10.10.31ScalaradcCritMaxread-writecurrentADC IN critical max
1.3.6.1.4.1.40418.2.6.10.10.35ScalaradcHysteresisread-writecurrentADC IN hysteresis
1.3.6.1.4.1.40418.2.6.10.300Scalarrebootwrite-onlycurrentSend 1 to reboot
1.3.6.1.4.1.40418.2.6.11Nodediffparams
1.3.6.1.4.1.40418.2.6.11.1NodeupsStatus
1.3.6.1.4.1.40418.2.6.11.1.1ScalarstatusUPSread-onlycurrentUPS status
1.3.6.1.4.1.40418.2.6.11.1.8ScalarbeeperStatusUPSread-onlycurrentBeeper status. Megatec only
1.3.6.1.4.1.40418.2.6.11.1.10ScalarshutdownStatusUPSread-onlycurrentShutdown is active. Megatec only
1.3.6.1.4.1.40418.2.6.11.1.20ScalarlastBatteryChangeUPSread-writecurrentLast battery change date (mm/dd/yyyy). Smart only
1.3.6.1.4.1.40418.2.6.11.1.51ScalarshutdownTimeUPSread-writecurrentShutdown period, minutes for Megatec, seconds for Smart. Writeble for Megatec only
1.3.6.1.4.1.40418.2.6.11.1.52ScalarturnOnTimeUPSread-writecurrentTurn on period, minutes. Megatec only
1.3.6.1.4.1.40418.2.6.11.1.53ScalarstartShutdownTurnOnUPSwrite-onlycurrentShutdown after shutdownTimeUPS and turn on after turnOnTimeUPS for Megatec. Shutdown after shutdownTimeUPS for Smart.
1.3.6.1.4.1.40418.2.6.11.1.54ScalarstartTurnOnUPSwrite-onlycurrentTurn on immediately, send 1 to turn on. Smart only
1.3.6.1.4.1.40418.2.6.11.1.71ScalarstartLongTestUPSread-writecurrentStart specified time period test. Send period in minutes to start. Megatec only
1.3.6.1.4.1.40418.2.6.11.10Nodepid
1.3.6.1.4.1.40418.2.6.11.10.1ScalarinputPIDread-writecurrentPID SNMP input value
1.3.6.1.4.1.40418.2.6.11.10.2ScalaroutputPercentPIDread-onlycurrentPID output value. 0 to 100%
1.3.6.1.4.1.40418.2.6.11.10.3ScalaroutputRealPIDread-onlycurrentPID output value (voltage if PID runs in analog mode or time if PID runs in PWM mode)
1.3.6.1.4.1.40418.2.6.11.10.4ScalarypPIDread-onlycurrentProportional gain
1.3.6.1.4.1.40418.2.6.11.10.5ScalaryiPIDread-onlycurrentIntegral gain
1.3.6.1.4.1.40418.2.6.11.10.6ScalarydPIDread-onlycurrentDerivative gain
1.3.6.1.4.1.40418.2.6.11.10.7ScalarerrorPIDread-onlycurrentError. Difference between setpoint and input value
1.3.6.1.4.1.40418.2.6.99Grouperd4GroupcurrentNotifications
Type Definitions
NameSyntaxStatusDescription
SensorIDUnsigned32 (0..4294967295)currentThis data type is a non-negative value.