SOCOMECPDU-MIB
104 objects
No module-level DESCRIPTION found.
Imported Objects
| RFC-1212 | OBJECT-TYPE |
| RFC-1215 | TRAP-TYPE |
| RFC1155-SMI | enterprises IpAddress |
| RFC1213-MIB | DisplayString |
| OID | Name | Access | Status | Description |
|---|---|---|---|---|
| 1.3.6.1.4.1.4555 | Nodesocomec | |||
| 1.3.6.1.4.1.4555.2 | Nodeups | |||
| 1.3.6.1.4.1.4555.2.30 | Nodepdu | |||
| 1.3.6.1.4.1.4555.2.30.1 | NodedpduIdent | |||
| 1.3.6.1.4.1.4555.2.30.1.1 | ScalardpduIdentManufacturer | read-only | mandatory | The EnviroStation Vendor. |
| 1.3.6.1.4.1.4555.2.30.1.2 | ScalardpduIdentModel | read-only | mandatory | The PDU Model designation. |
| 1.3.6.1.4.1.4555.2.30.1.3 | ScalardpduIdentSerialNumber | read-only | mandatory | The PDU serial number |
| 1.3.6.1.4.1.4555.2.30.1.4 | ScalardpduIdentPDUFirmwareVersion | read-only | mandatory | The PDU firmware version |
| 1.3.6.1.4.1.4555.2.30.1.5 | ScalardpduIdentAgentSoftwareVersion | read-only | mandatory | The PDU NMC software version |
| 1.3.6.1.4.1.4555.2.30.1.6 | ScalardpduIdentName | read-write | mandatory | A string identifying the PDU. This object should be set by the administrator. |
| 1.3.6.1.4.1.4555.2.30.1.7 | ScalardpduAttachedDevices | read-write | mandatory | A string identifying the devices attached to the output(s) of the PDU. This object should be set by the administrator. |
| 1.3.6.1.4.1.4555.2.30.2 | NodedpduOutput | |||
| 1.3.6.1.4.1.4555.2.30.2.1 | ScalardpduOutputFrequency | read-only | mandatory | The present output frequency in 1/10 Hz. |
| 1.3.6.1.4.1.4555.2.30.2.2 | ScalardpduOutputVoltage1 | read-only | mandatory | The Output line 1 voltage of the PDU system in 1/10 V. |
| 1.3.6.1.4.1.4555.2.30.2.3 | ScalardpduOutputCurrent1 | read-only | mandatory | The Output line 1 current of the PDU system in 1/10 A. |
| 1.3.6.1.4.1.4555.2.30.2.4 | ScalardpduOutputVoltage2 | read-only | mandatory | The Output line 2 voltage of the PDU system in 1/10 V. |
| 1.3.6.1.4.1.4555.2.30.2.5 | ScalardpduOutputCurrent2 | read-only | mandatory | The Output line 2 current of the PDU system in 1/10 A. |
| 1.3.6.1.4.1.4555.2.30.2.6 | ScalardpduOutputVoltage3 | read-only | mandatory | The Output line 3 voltage of the PDU system in 1/10 V. |
| 1.3.6.1.4.1.4555.2.30.2.7 | ScalardpduOutputCurrent3 | read-only | mandatory | The Output line 3 current of the PDU system in 1/10 A. |
| 1.3.6.1.4.1.4555.2.30.3 | NodedpduAlarm | |||
| 1.3.6.1.4.1.4555.2.30.3.1 | ScalardpduAlarmDisconnect | read-only | mandatory | Does the PDU disconnect? |
| 1.3.6.1.4.1.4555.2.30.3.2 | ScalardpduAlarmL1LoadMajor | read-only | mandatory | L1 load major alarm |
| 1.3.6.1.4.1.4555.2.30.3.3 | ScalardpduAlarmL1LoadMinor | read-only | mandatory | L1 load minor alarm |
| 1.3.6.1.4.1.4555.2.30.3.4 | ScalardpduAlarmL1OutVoltMajor | read-only | mandatory | L1 output votage major alarm |
| 1.3.6.1.4.1.4555.2.30.3.5 | ScalardpduAlarmL1OutVoltMinor | read-only | mandatory | L1 output voltage minor alarm |
| 1.3.6.1.4.1.4555.2.30.3.6 | ScalardpduAlarmL2LoadMajor | read-only | mandatory | L2 load major alarm |
| 1.3.6.1.4.1.4555.2.30.3.7 | ScalardpduAlarmL2LoadMinor | read-only | mandatory | L2 load minor alarm |
| 1.3.6.1.4.1.4555.2.30.3.8 | ScalardpduAlarmL2OutVoltMajor | read-only | mandatory | L2 output votage major alarm |
| 1.3.6.1.4.1.4555.2.30.3.9 | ScalardpduAlarmL2OutVoltMinor | read-only | mandatory | L2 output voltage minor alarm |
| 1.3.6.1.4.1.4555.2.30.3.10 | ScalardpduAlarmL3LoadMajor | read-only | mandatory | L3 load major alarm |
| 1.3.6.1.4.1.4555.2.30.3.11 | ScalardpduAlarmL3LoadMinor | read-only | mandatory | L3 load minor alarm |
| 1.3.6.1.4.1.4555.2.30.3.12 | ScalardpduAlarmL3OutVoltMajor | read-only | mandatory | L3 output votage major alarm |
| 1.3.6.1.4.1.4555.2.30.3.13 | ScalardpduAlarmL3OutVoltMinor | read-only | mandatory | L3 output voltage minor alarm |
| 1.3.6.1.4.1.4555.2.30.3.14 | ScalardpduAlarmL12LoadMajor | read-only | mandatory | L1, L2 load major alarm |
| 1.3.6.1.4.1.4555.2.30.3.15 | ScalardpduAlarmL12LoadMinor | read-only | mandatory | L1, L2 load minor alarm |
| 1.3.6.1.4.1.4555.2.30.4 | NodedpduEnvironment | |||
| 1.3.6.1.4.1.4555.2.30.4.1 | ScalardpduEnvTemperature | read-only | mandatory | The ambient environmental temperature. |
| 1.3.6.1.4.1.4555.2.30.4.2 | ScalardpduEnvHumidity | read-only | mandatory | The environmental humidity. |
| 1.3.6.1.4.1.4555.2.30.4.3 | ScalardpduEnvSetTemperatureWarnLimit | read-write | mandatory | Alarm dpduEnvOverWarnTemperature on when the environmental temperature over the value. |
| 1.3.6.1.4.1.4555.2.30.4.4 | ScalardpduEnvSetTemperatureAlarmLimit | read-write | mandatory | Alarm dpduEnvOverAlarmTemperature on when the environmental temperature over the value. |
| 1.3.6.1.4.1.4555.2.30.4.5 | ScalardpduEnvSetHumidityWarnLimit | read-write | mandatory | Alarm dpduEnvOverWarnHumidity on when the environmental humidity over the value. |
| 1.3.6.1.4.1.4555.2.30.4.6 | ScalardpduEnvSetHumidityAlarmLimit | read-write | mandatory | Alarm dpduEnvOverAlarmHumidity on when the environmental humidity over the value. |
| 1.3.6.1.4.1.4555.2.30.4.7 | ScalardpduEnvSetEnvRelay1 | read-write | mandatory | |
| 1.3.6.1.4.1.4555.2.30.4.8 | ScalardpduEnvSetEnvRelay2 | read-write | mandatory | |
| 1.3.6.1.4.1.4555.2.30.4.9 | ScalardpduEnvSetEnvRelay3 | read-write | mandatory | |
| 1.3.6.1.4.1.4555.2.30.4.10 | ScalardpduEnvSetEnvRelay4 | read-write | mandatory | |
| 1.3.6.1.4.1.4555.2.30.4.11 | ScalardpduWarnOverEnvTemperature | read-only | mandatory | Does the environment over warning temperature? |
| 1.3.6.1.4.1.4555.2.30.4.12 | ScalardpduAlarmOverEnvTemperature | read-only | mandatory | Does the environment over alarm temperature? |
| 1.3.6.1.4.1.4555.2.30.4.13 | ScalardpduWarnmOverEnvHumidity | read-only | mandatory | Does the environment over warn humidity? |
| 1.3.6.1.4.1.4555.2.30.4.14 | ScalardpduAlarmOverEnvHumidity | read-only | mandatory | Does the environment over alarm humidity? |
| 1.3.6.1.4.1.4555.2.30.4.15 | ScalardpduAlarmEnvRelay1 | read-only | mandatory | The alarm status of relay1. |
| 1.3.6.1.4.1.4555.2.30.4.16 | ScalardpduAlarmEnvRelay2 | read-only | mandatory | The alarm status of relay2. |
| 1.3.6.1.4.1.4555.2.30.4.17 | ScalardpduAlarmEnvRelay3 | read-only | mandatory | The alarm status of relay3. |
| 1.3.6.1.4.1.4555.2.30.4.18 | ScalardpduAlarmEnvRelay4 | read-only | mandatory | The alarm status of relay4. |
| 1.3.6.1.4.1.4555.2.30.4.19 | ScalardpduAlarmEnvDisconnect | read-only | mandatory | To indicate the communication status of EnviroProbe. |
| 1.3.6.1.4.1.4555.2.30.20 | NodedpduTraps | |||
| 1.3.6.1.4.1.4555.2.30.20.1 | NodedpduCommunicationLost | Communication with the PDU failed. | ||
| 1.3.6.1.4.1.4555.2.30.20.2 | NodedpduCommunicationEstablished | Communication with the PDU reestablished. | ||
| 1.3.6.1.4.1.4555.2.30.20.3 | NodedpduL1LoadMajorAlarm | L1 load major alarm. | ||
| 1.3.6.1.4.1.4555.2.30.20.4 | NodedpduL1LoadMajorAlarmRecover | Recover from L1 load major alarm. | ||
| 1.3.6.1.4.1.4555.2.30.20.5 | NodedpduL1LoadMinorAlarm | L1 load minor alarm. | ||
| 1.3.6.1.4.1.4555.2.30.20.6 | NodedpduL1LoadMinorAlarmRecover | Recover from L1 load minor alarm. | ||
| 1.3.6.1.4.1.4555.2.30.20.7 | NodedpduL1OutVoltMajorAlarm | L1 output voltage major alarm. | ||
| 1.3.6.1.4.1.4555.2.30.20.8 | NodedpduL1OutVoltMajorAlarmRecover | Recover from L1 output voltage major alarm. | ||
| 1.3.6.1.4.1.4555.2.30.20.9 | NodedpduL1OutVoltMinorAlarm | L1 output voltage minor alarm. | ||
| 1.3.6.1.4.1.4555.2.30.20.10 | NodedpduL1OutVoltMinorAlarmRecover | Recover from L1 output voltage minor alarm. | ||
| 1.3.6.1.4.1.4555.2.30.20.11 | NodedpduL2LoadMajorAlarm | L2 load major alarm. | ||
| 1.3.6.1.4.1.4555.2.30.20.12 | NodedpduL2LoadMajorAlarmRecover | Recover from L2 load major alarm. | ||
| 1.3.6.1.4.1.4555.2.30.20.13 | NodedpduL2LoadMinorAlarm | L2 load minor alarm. | ||
| 1.3.6.1.4.1.4555.2.30.20.14 | NodedpduL2LoadMinorAlarmRecover | Recover from L2 load minor alarm. | ||
| 1.3.6.1.4.1.4555.2.30.20.15 | NodedpduL2OutVoltMajorAlarm | L2 output voltage major alarm. | ||
| 1.3.6.1.4.1.4555.2.30.20.16 | NodedpduL2OutVoltMajorAlarmRecover | Recover from L2 output voltage major alarm. | ||
| 1.3.6.1.4.1.4555.2.30.20.17 | NodedpduL2OutVoltMinorAlarm | L2 output voltage minor alarm. | ||
| 1.3.6.1.4.1.4555.2.30.20.18 | NodedpduL2OutVoltMinorAlarmRecover | Recover from L2 output voltage minor alarm. | ||
| 1.3.6.1.4.1.4555.2.30.20.19 | NodedpduL3LoadMajorAlarm | L3 load major alarm. | ||
| 1.3.6.1.4.1.4555.2.30.20.20 | NodedpduL3LoadMajorAlarmRecover | Recover from L3 load major alarm. | ||
| 1.3.6.1.4.1.4555.2.30.20.21 | NodedpduL3LoadMinorAlarm | L3 load minor alarm. | ||
| 1.3.6.1.4.1.4555.2.30.20.22 | NodedpduL3LoadMinorAlarmRecover | Recover from L3 load minor alarm. | ||
| 1.3.6.1.4.1.4555.2.30.20.23 | NodedpduL3OutVoltMajorAlarm | L3 output voltage major alarm. | ||
| 1.3.6.1.4.1.4555.2.30.20.24 | NodedpduL3OutVoltMajorAlarmRecover | Recover from L3 output voltage major alarm. | ||
| 1.3.6.1.4.1.4555.2.30.20.25 | NodedpduL3OutVoltMinorAlarm | L3 output voltage minor alarm. | ||
| 1.3.6.1.4.1.4555.2.30.20.26 | NodedpduL3OutVoltMinorAlarmRecover | Recover from L3 output voltage minor alarm. | ||
| 1.3.6.1.4.1.4555.2.30.20.27 | NodedpduL12LoadMajorAlarm | L1 L2 load major alarm. | ||
| 1.3.6.1.4.1.4555.2.30.20.28 | NodedpduL12LoadMajorAlarmRecover | Recover from L1 L2 load major alarm. | ||
| 1.3.6.1.4.1.4555.2.30.20.29 | NodedpduL12LoadMinorAlarm | L1 L2 load minor alarm. | ||
| 1.3.6.1.4.1.4555.2.30.20.30 | NodedpduL12LoadMinorAlarmRecover | Recover from L1 L2 load minor alarm. | ||
| 1.3.6.1.4.1.4555.2.30.20.31 | NodedpduEnvCommunicationLost | Communication with the environmental sensor failed. | ||
| 1.3.6.1.4.1.4555.2.30.20.32 | NodedpduEnvCommunicationEstablished | Communication with the environmental sensor reestablished. | ||
| 1.3.6.1.4.1.4555.2.30.20.33 | NodedpduEnvOverWarnTemperature | The environment over warning temperature. | ||
| 1.3.6.1.4.1.4555.2.30.20.34 | NodedpduNoLongerEnvOverWarnTemperature | The environment recovered from over warning temperature. | ||
| 1.3.6.1.4.1.4555.2.30.20.35 | NodedpduEnvOverWarnHumidity | The environment over warning humidity. | ||
| 1.3.6.1.4.1.4555.2.30.20.36 | NodedpduNoLongerEnvOverWarnHumidity | The environment recovered from over warning humidity. | ||
| 1.3.6.1.4.1.4555.2.30.20.37 | NodedpduEnvOverAlarmTemperature | The environment over alarm temperature. | ||
| 1.3.6.1.4.1.4555.2.30.20.38 | NodedpduNoLongerEnvOverAlarmTemperature | The environment recovered from over alarm temperature. | ||
| 1.3.6.1.4.1.4555.2.30.20.39 | NodedpduEnvOverAlarmHumidity | The environment over alarm humidity. | ||
| 1.3.6.1.4.1.4555.2.30.20.40 | NodedpduNoLongerEnvOverAlarmHumidity | The environment recovered from over alarm humidity. | ||
| 1.3.6.1.4.1.4555.2.30.20.41 | NodedpduEnvRelay1Alarm | The environment relay1 is not in normal state. | ||
| 1.3.6.1.4.1.4555.2.30.20.42 | NodedpduEnvRelay1Normal | The environment relay1 is in normal state. | ||
| 1.3.6.1.4.1.4555.2.30.20.43 | NodedpduEnvRelay2Alarm | The environment relay2 is not in normal state. | ||
| 1.3.6.1.4.1.4555.2.30.20.44 | NodedpduEnvRelay2Normal | The environment relay2 is in normal state. | ||
| 1.3.6.1.4.1.4555.2.30.20.45 | NodedpduEnvRelay3Alarm | The environment relay3 is not in normal state. | ||
| 1.3.6.1.4.1.4555.2.30.20.46 | NodedpduEnvRelay3Normal | The environment relay3 is in normal state. | ||
| 1.3.6.1.4.1.4555.2.30.20.47 | NodedpduEnvRelay4Alarm | The environment relay4 is not in normal state. | ||
| 1.3.6.1.4.1.4555.2.30.20.48 | NodedpduEnvRelay4Normal | The environment relay4 is in normal state. |