SOCOMECUPS-ADICOM-MIB
64 objects
No module-level DESCRIPTION found.
Imported Objects
| RFC-1212 | OBJECT-TYPE |
| RFC-1215 | TRAP-TYPE |
| RFC1155-SMI | enterprises |
| RFC1213-MIB | DisplayString |
| SNMPv2-TC | AutonomousType TestAndIncr TimeInterval TimeStamp |
| OID | Name | Access | Status | Description |
|---|---|---|---|---|
| 1.3.6.1.4.1.4555 | NodesocomecUPS | |||
| 1.3.6.1.4.1.4555.1 | Nodesoftware | |||
| 1.3.6.1.4.1.4555.1.1 | Nodenetwork | |||
| 1.3.6.1.4.1.4555.1.1.5 | NodeadicomUps | |||
| 1.3.6.1.4.1.4555.1.1.5.1 | NodeadicomUpsObjects | |||
| 1.3.6.1.4.1.4555.1.1.5.1.1 | NodeadicomUpsIdent | |||
| 1.3.6.1.4.1.4555.1.1.5.1.1.1 | ScalaradicomUpsIdentModel | read-only | mandatory | The UPS Model designation. |
| 1.3.6.1.4.1.4555.1.1.5.1.1.2 | ScalaradicomUpsIdentSerialNumber | read-only | mandatory | The UPS serial number |
| 1.3.6.1.4.1.4555.1.1.5.1.1.3 | ScalaradicomUpsIdentFirmwareVersion | read-only | mandatory | The UPS firmware version. |
| 1.3.6.1.4.1.4555.1.1.5.1.1.4 | ScalaradicomUpsIdentAgentSoftwareVersion | read-only | mandatory | SNMP agent software version. |
| 1.3.6.1.4.1.4555.1.1.5.1.2 | NodeadicomUpsBattery | |||
| 1.3.6.1.4.1.4555.1.1.5.1.2.1 | ScalaradicomUpsBatteryStatus | read-only | mandatory | The battery status of the unit |
| 1.3.6.1.4.1.4555.1.1.5.1.2.2 | ScalaradicomUpsSecondsOnBattery | read-only | mandatory | If the unit is on battery power, the elapsed time since the unit last switched to battery power. |
| 1.3.6.1.4.1.4555.1.1.5.1.2.3 | ScalaradicomUpsEstimatedMinutesRemaining | read-only | mandatory | An estimate of the time to battery charge depletion under the present load conditions. |
| 1.3.6.1.4.1.4555.1.1.5.1.2.4 | ScalaradicomUpsEstimatedChargeRemaining | read-only | mandatory | An estimate of the battery charge remaining expressed as a percent of full charge. |
| 1.3.6.1.4.1.4555.1.1.5.1.2.5 | ScalaradicomUpsBatteryVoltage | read-only | mandatory | The battery voltage in 0.1 Volt DC. |
| 1.3.6.1.4.1.4555.1.1.5.1.2.6 | ScalaradicomUpsBatteryTemperature | read-only | mandatory | The temperature measurement inside the battery cabinet in 0.1 deg.C. |
| 1.3.6.1.4.1.4555.1.1.5.1.3 | NodeadicomUpsInput | |||
| 1.3.6.1.4.1.4555.1.1.5.1.3.1 | ScalaradicomUpsInputFrequency | read-only | mandatory | Rectifier Input frequency in 0.1 HZ. |
| 1.3.6.1.4.1.4555.1.1.5.1.3.2 | ScalaradicomUpsInputNumLines | read-only | mandatory | The number of phases |
| 1.3.6.1.4.1.4555.1.1.5.1.3.3 | TableadicomUpsInputTable | not-accessible | mandatory | A list of input table entries |
| 1.3.6.1.4.1.4555.1.1.5.1.3.3.1 | RowadicomUpsInputEntry | not-accessible | mandatory | Array of measurements |
| 1.3.6.1.4.1.4555.1.1.5.1.3.3.1.1 | ColumnadicomUpsInputLineIndex | read-only | mandatory | Rectifier input phase number. |
| 1.3.6.1.4.1.4555.1.1.5.1.3.3.1.2 | ColumnadicomUpsInputVoltage | read-only | mandatory | Rectifier input voltage in volts. |
| 1.3.6.1.4.1.4555.1.1.5.1.4 | NodeadicomUpsOutput | |||
| 1.3.6.1.4.1.4555.1.1.5.1.4.1 | ScalaradicomUpsOutputSource | read-only | mandatory | UPS load status |
| 1.3.6.1.4.1.4555.1.1.5.1.4.2 | ScalaradicomUpsOutputFrequency | read-only | mandatory | UPS Output frequency in 0.1 HZ. |
| 1.3.6.1.4.1.4555.1.1.5.1.4.3 | ScalaradicomUpsOutputLoadRate | read-only | mandatory | UPS Output Load Rate in %. |
| 1.3.6.1.4.1.4555.1.1.5.1.4.4 | ScalaradicomUpsOutputkVA | read-only | mandatory | UPS Output Power in kVA. |
| 1.3.6.1.4.1.4555.1.1.5.1.4.5 | ScalaradicomUpsOutputNumLines | read-only | mandatory | Number of phases |
| 1.3.6.1.4.1.4555.1.1.5.1.4.6 | TableadicomUpsOutputTable | not-accessible | mandatory | A list of input table entries. |
| 1.3.6.1.4.1.4555.1.1.5.1.4.6.1 | RowadicomUpsOutputEntry | not-accessible | mandatory | Array of measurements |
| 1.3.6.1.4.1.4555.1.1.5.1.4.6.1.1 | ColumnadicomUpsOutputLineIndex | read-only | mandatory | Output phase number. |
| 1.3.6.1.4.1.4555.1.1.5.1.4.6.1.2 | ColumnadicomUpsOutputVoltage | read-only | mandatory | Output voltage in volts. |
| 1.3.6.1.4.1.4555.1.1.5.1.4.6.1.3 | ColumnadicomUpsOutputCurrent | read-only | mandatory | Output current in Amps. |
| 1.3.6.1.4.1.4555.1.1.5.1.5 | NodeadicomUpsBypass | |||
| 1.3.6.1.4.1.4555.1.1.5.1.5.1 | ScalaradicomUpsBypassFrequency | read-only | mandatory | Bypass Input frequency in 0.1 HZ. |
| 1.3.6.1.4.1.4555.1.1.5.1.5.2 | ScalaradicomUpsBypassNumLines | read-only | mandatory | The number of phases |
| 1.3.6.1.4.1.4555.1.1.5.1.5.3 | TableadicomUpsBypassTable | not-accessible | mandatory | A list of bypass table entries |
| 1.3.6.1.4.1.4555.1.1.5.1.5.3.1 | RowadicomUpsBypassEntry | not-accessible | mandatory | Array of measurements |
| 1.3.6.1.4.1.4555.1.1.5.1.5.3.1.1 | ColumnadicomUpsBypassLineIndex | read-only | mandatory | Bypass input supply phase number. |
| 1.3.6.1.4.1.4555.1.1.5.1.5.3.1.2 | ColumnadicomUpsBypassVoltage | read-only | mandatory | Bypass input voltage in volts. |
| 1.3.6.1.4.1.4555.1.1.5.1.6 | NodeadicomUpsAlarm | |||
| 1.3.6.1.4.1.4555.1.1.5.1.6.1 | NodeadicomUpsWellKnownAlarms | |||
| 1.3.6.1.4.1.4555.1.1.5.1.6.1.1 | ScalaradicomUpsImminentStop | read-only | mandatory | UPS Imminent Stop |
| 1.3.6.1.4.1.4555.1.1.5.1.6.1.2 | ScalaradicomUpsOverload | read-only | mandatory | UPS in overload |
| 1.3.6.1.4.1.4555.1.1.5.1.6.1.3 | ScalaradicomUpsTransferImpossible | read-only | mandatory | Transfer Impossible |
| 1.3.6.1.4.1.4555.1.1.5.1.6.1.4 | ScalaradicomUpsInsufficientResource | read-only | mandatory | The UPS hasn't the resource to supply the load. |
| 1.3.6.1.4.1.4555.1.1.5.1.6.1.5 | ScalaradicomUpsRedundancyLoss | read-only | mandatory | The units are not any more redundant |
| 1.3.6.1.4.1.4555.1.1.5.1.6.1.6 | ScalaradicomUpsTemperatureAlarm | read-only | mandatory | The UPS or battery temperature is over the limits |
| 1.3.6.1.4.1.4555.1.1.5.1.6.1.7 | ScalaradicomUpsGeneralAlarm | read-only | mandatory | UPS general alarm |
| 1.3.6.1.4.1.4555.1.1.5.1.7 | NodeadicomUpsAgent | |||
| 1.3.6.1.4.1.4555.1.1.5.1.7.1 | ScalaradicomUpsAgentTrapString | read-only | mandatory | This OID allows traps to be sent with an octet string argument |
| 1.3.6.1.4.1.4555.1.1.5.2 | NodeadicomUpsTraps | |||
| 1.3.6.1.4.1.4555.1.1.5.2.1 | NodeadicomUpsTrapLoadOnInverter | INFORMATION: Load protected and supplied by Inverter. | ||
| 1.3.6.1.4.1.4555.1.1.5.2.2 | NodeadicomUpsTrapOnBatteryPower | WARNING: The UPS has switched to battery backup power. | ||
| 1.3.6.1.4.1.4555.1.1.5.2.3 | NodeadicomUpsTrapBatteryLow | SEVERE: Battery is near to be discharged. | ||
| 1.3.6.1.4.1.4555.1.1.5.2.4 | NodeadicomUpsTrapPowerRestored | INFORMATION: Input power has been restored. | ||
| 1.3.6.1.4.1.4555.1.1.5.2.5 | NodeadicomUpsTrapImminentStop | SEVERE: UPS Imminent Stop | ||
| 1.3.6.1.4.1.4555.1.1.5.2.6 | NodeadicomUpsTrapOverload | SEVERE: UPS in Overload | ||
| 1.3.6.1.4.1.4555.1.1.5.2.7 | NodeadicomUpsTrapOutputLoadOFF | WARNING: Load not supplied | ||
| 1.3.6.1.4.1.4555.1.1.5.2.8 | NodeadicomUpsTrapOutputOnBypass | WARNING: Load supplied by automatic bypass | ||
| 1.3.6.1.4.1.4555.1.1.5.2.9 | NodeadicomUpsTrapGeneralAlarm | WARNING: UPS general alarm | ||
| 1.3.6.1.4.1.4555.1.1.5.2.10 | NodeadicomUpsTrapAlarmCancelled | Alarm cancelled. UPS in normal situation |