MIB Viewer

SOCOMECUPS-MIB

266 objects
No module-level DESCRIPTION found.
OIDNameAccessStatusDescription
1.3.6.1.4.1.4555NodesocomecSicon
1.3.6.1.4.1.4555.1Nodesoftware
1.3.6.1.4.1.4555.1.1Nodenetwork
1.3.6.1.4.1.4555.1.1.1Nodenetvision
1.3.6.1.4.1.4555.1.1.1.1NodeupsObjects
1.3.6.1.4.1.4555.1.1.1.1.1NodeupsIdent
1.3.6.1.4.1.4555.1.1.1.1.1.1ScalarupsIdentModelread-onlymandatoryThe UPS Model designation.
1.3.6.1.4.1.4555.1.1.1.1.1.2ScalarupsIdentUPSFirmwareVersionread-onlymandatoryThe UPS firmware version.
1.3.6.1.4.1.4555.1.1.1.1.1.3ScalarupsIdentAgentSoftwareVersionread-onlymandatoryThe UPS Net Vision software version.
1.3.6.1.4.1.4555.1.1.1.1.1.4ScalarupsIdentUpsSerialNumberread-onlymandatoryThe UPS serial no.
1.3.6.1.4.1.4555.1.1.1.1.2NodeupsBattery
1.3.6.1.4.1.4555.1.1.1.1.2.1ScalarupsBatteryStatusread-onlymandatoryThe present battery status
1.3.6.1.4.1.4555.1.1.1.1.2.2ScalarupsSecondsOnBatteryread-onlymandatoryIf the unit is on battery power, the elapsed time since the UPS last switched to battery power, or the time since the network management subsystem was last res…
1.3.6.1.4.1.4555.1.1.1.1.2.3ScalarupsEstimatedMinutesRemainingread-onlymandatoryAn estimate of the time to battery charge depletion under the present load conditions if the utility power is off and remains off, or if it were to be lost and…
1.3.6.1.4.1.4555.1.1.1.1.2.4ScalarupsEstimatedChargeRemainingread-onlymandatoryAn estimate of the battery charge remaining expressed as a percent of full charge.
1.3.6.1.4.1.4555.1.1.1.1.2.5ScalarupsBatteryVoltageread-onlymandatoryThe magnitude of the present battery voltage in 0.1 Volt DC.
1.3.6.1.4.1.4555.1.1.1.1.2.6ScalarupsBatteryTemperatureread-onlymandatoryThe ambient temperature at or near the UPS Battery casing.
1.3.6.1.4.1.4555.1.1.1.1.3NodeupsInput
1.3.6.1.4.1.4555.1.1.1.1.3.1ScalarupsInputNumLinesread-onlymandatoryThe number of input lines utilized in this device. This variable indicates the number of rows in the input table.
1.3.6.1.4.1.4555.1.1.1.1.3.2ScalarupsInputFrequencyread-onlymandatoryThe current input frequency to the UPS system in 0.1 HZ.
1.3.6.1.4.1.4555.1.1.1.1.3.3TableupsInputTablenot-accessiblemandatoryA list of input table entries. The number of entries is given by the value of upsInputNumLines.
1.3.6.1.4.1.4555.1.1.1.1.3.3.1RowupsInputEntrynot-accessiblemandatoryAn entry containing information applicable to a particular input line.
1.3.6.1.4.1.4555.1.1.1.1.3.3.1.1ColumnupsInputLineIndexread-onlymandatory
1.3.6.1.4.1.4555.1.1.1.1.3.3.1.2ColumnupsInputVoltageread-onlymandatoryThe input utility line voltage in 0.1 volts.
1.3.6.1.4.1.4555.1.1.1.1.3.3.1.3ColumnupsInputCurrentread-onlymandatoryThe magnitude of the present input current in 0.1 A.
1.3.6.1.4.1.4555.1.1.1.1.3.3.1.4ColumnupsInputVoltageMaxread-onlymandatoryThe maximum utility line voltage in 0.1 VAC for last 1 minute.
1.3.6.1.4.1.4555.1.1.1.1.3.3.1.5ColumnupsInputVoltageMinread-onlymandatoryThe minimum utility line voltage in 0.1 VAC for last 1 minute.
1.3.6.1.4.1.4555.1.1.1.1.4NodeupsOutput
1.3.6.1.4.1.4555.1.1.1.1.4.1ScalarupsOutputSourceread-onlymandatoryThe present source of output power.
1.3.6.1.4.1.4555.1.1.1.1.4.2ScalarupsOutputFrequencyread-onlymandatoryThe current output frequency of the UPS system in 0.1 of HZ.
1.3.6.1.4.1.4555.1.1.1.1.4.3ScalarupsOutputNumLinesread-onlymandatoryThe number of output lines utilized in this device. This variable indicates the number of rows in the output table.
1.3.6.1.4.1.4555.1.1.1.1.4.4TableupsOutputTablenot-accessiblemandatoryA list of output table entries. The number of entries is given by the value of upsOutputNumLines.
1.3.6.1.4.1.4555.1.1.1.1.4.4.1RowupsOutputEntrynot-accessiblemandatoryAn entry containing information applicable to a particular output line.
1.3.6.1.4.1.4555.1.1.1.1.4.4.1.1ColumnupsOutputLineIndexread-onlymandatoryThe output line identifier.
1.3.6.1.4.1.4555.1.1.1.1.4.4.1.2ColumnupsOutputVoltageread-onlymandatoryThe output voltage of the UPS system in 0.1 volts.
1.3.6.1.4.1.4555.1.1.1.1.4.4.1.3ColumnupsOutputCurrentread-onlymandatoryThe output current of the UPS system in 0.1 Amps.
1.3.6.1.4.1.4555.1.1.1.1.4.4.1.4ColumnupsOutputPercentLoadread-onlymandatoryThe percentage of the UPS power capacity presently being used on this output line, i.e., the greater of the percent load of true power capacity and the percent…
1.3.6.1.4.1.4555.1.1.1.1.4.4.1.5ColumnupsOutputKvaread-onlymandatoryOutput apparent power of the UPS in kVA.
1.3.6.1.4.1.4555.1.1.1.1.5NodeupsBypass
1.3.6.1.4.1.4555.1.1.1.1.5.1ScalarupsBypassFrequencyread-onlymandatoryThe present bypass frequency.
1.3.6.1.4.1.4555.1.1.1.1.5.2ScalarupsBypassNumLinesread-onlymandatoryThe number of bypass lines utilized in this device. This entry indicates the number of rows in the bypass table.
1.3.6.1.4.1.4555.1.1.1.1.5.3TableupsBypassTablenot-accessiblemandatoryA list of bypass table entries. The number of entries is given by the value of upsBypassNumLines.
1.3.6.1.4.1.4555.1.1.1.1.5.3.1RowupsBypassEntrynot-accessiblemandatoryAn entry containing information applicable to a particular bypass input.
1.3.6.1.4.1.4555.1.1.1.1.5.3.1.1ColumnupsBypassLineIndexread-onlymandatoryThe bypass line identifier.
1.3.6.1.4.1.4555.1.1.1.1.5.3.1.2ColumnupsBypassVoltageread-onlymandatoryThe present bypass voltage of the UPS system in 0.1 volts.
1.3.6.1.4.1.4555.1.1.1.1.5.3.1.3ColumnupsBypassCurrentread-onlymandatoryThe present bypass current of the UPS system in 0.1 Amps.
1.3.6.1.4.1.4555.1.1.1.1.6NodeupsAlarm
1.3.6.1.4.1.4555.1.1.1.1.6.1ScalarupsAlarmsPresentread-onlymandatoryThe present number of active alarm conditions.
1.3.6.1.4.1.4555.1.1.1.1.6.2TableupsAlarmTablenot-accessiblemandatoryA list of alarm table entries. The table contains zero, one, or many rows at any moment, depending upon the number of alarm conditions in effect. The table is …
1.3.6.1.4.1.4555.1.1.1.1.6.2.1RowupsAlarmEntrynot-accessiblemandatoryAn entry containing information applicable to a particular alarm.
1.3.6.1.4.1.4555.1.1.1.1.6.2.1.1ColumnupsAlarmIdread-onlymandatoryA unique identifier for an alarm condition. This value must remain constant.
1.3.6.1.4.1.4555.1.1.1.1.6.2.1.2ColumnupsAlarmDescrread-onlymandatoryA reference to an alarm description object. The object referenced should not be accessible, but rather be used to provide a unique description of the alarm con…
1.3.6.1.4.1.4555.1.1.1.1.6.2.1.3ColumnupsAlarmTimeread-onlymandatoryThe value of sysUpTime when the alarm condition was detected. If the alarm condition was detected at the time of agent startup and presumably existed before ag…
1.3.6.1.4.1.4555.1.1.1.1.6.2.1.4ColumnupsAlarmExtDesread-onlymandatoryExtra description.
1.3.6.1.4.1.4555.1.1.1.1.6.3NodeupsWellKnownAlarms
1.3.6.1.4.1.4555.1.1.1.1.6.3.1ScalarupsAlarmBatteryBadread-onlymandatoryOne or more batteries have been determined to require replacement.
1.3.6.1.4.1.4555.1.1.1.1.6.3.2ScalarupsAlarmOnBatteryread-onlymandatoryThe UPS is drawing power from the batteries.
1.3.6.1.4.1.4555.1.1.1.1.6.3.3ScalarupsAlarmLowBatteryread-onlymandatoryThe remaining battery run-time is less than or equal to battery low threshold
1.3.6.1.4.1.4555.1.1.1.1.6.3.4ScalarupsAlarmDepletedBatteryread-onlymandatoryThe UPS will be unable to sustain the present load when and if the utility power is lost. The Battery is discharched.
1.3.6.1.4.1.4555.1.1.1.1.6.3.5ScalarupsAlarmTempBadread-onlymandatoryUPS temperature is out of tolerance.
1.3.6.1.4.1.4555.1.1.1.1.6.3.6ScalarupsAlarmInputBadread-onlymandatoryInput power supply is out of tolerance.
1.3.6.1.4.1.4555.1.1.1.1.6.3.7ScalarupsAlarmOutputBadread-onlymandatoryAn output condition (other than OutputOverload) is out of tolerance.
1.3.6.1.4.1.4555.1.1.1.1.6.3.8ScalarupsAlarmOutputOverloadread-onlymandatoryThe output load exceeds the UPS output capacity.
1.3.6.1.4.1.4555.1.1.1.1.6.3.9ScalarupsAlarmOnBypassread-onlymandatoryLoad supplied by bypass
1.3.6.1.4.1.4555.1.1.1.1.6.3.10ScalarupsAlarmBypassBadread-onlymandatoryBypass input supply is detected as absent.
1.3.6.1.4.1.4555.1.1.1.1.6.3.11ScalarupsAlarmOutputOffAsRequestedread-onlymandatoryThe UPS has shutdown as requested, i.e., the output is off.
1.3.6.1.4.1.4555.1.1.1.1.6.3.12ScalarupsAlarmUpsOffAsRequestedread-onlymandatoryThe entire UPS has shutdown as commanded.
1.3.6.1.4.1.4555.1.1.1.1.6.3.13ScalarupsAlarmChargerFailedread-onlymandatoryAn uncorrected problem has been detected within the UPS charger subsystem.
1.3.6.1.4.1.4555.1.1.1.1.6.3.14ScalarupsAlarmUpsOutputOffread-onlymandatoryThe output of the UPS is in the off state.
1.3.6.1.4.1.4555.1.1.1.1.6.3.15ScalarupsAlarmUpsSystemOffread-onlymandatoryThe UPS system is in the off state.
1.3.6.1.4.1.4555.1.1.1.1.6.3.16ScalarupsAlarmFanFailureread-onlymandatoryThe failure of one or more fans in the UPS has been detected.
1.3.6.1.4.1.4555.1.1.1.1.6.3.17ScalarupsAlarmFuseFailureread-onlymandatoryThe failure of one or more fuses has been detected.
1.3.6.1.4.1.4555.1.1.1.1.6.3.18ScalarupsAlarmGeneralFaultread-onlymandatoryA general fault in the UPS has been detected.
1.3.6.1.4.1.4555.1.1.1.1.6.3.19ScalarupsAlarmDiagnosticTestFailedread-onlymandatoryThe result of the last diagnostic test indicates a failure.
1.3.6.1.4.1.4555.1.1.1.1.6.3.20ScalarupsAlarmCommunicationLostread-onlymandatoryA problem has been encountered in the communications between the agent and the UPS.
1.3.6.1.4.1.4555.1.1.1.1.6.3.21ScalarupsAlarmAwaitingPowerread-onlymandatoryThe UPS output is off and the UPS is awaiting the return of input power.
1.3.6.1.4.1.4555.1.1.1.1.6.3.22ScalarupsAlarmShutdownPendingread-onlymandatoryA upsShutdownAfterDelay countdown is underway.
1.3.6.1.4.1.4555.1.1.1.1.6.3.23ScalarupsAlarmShutdownImminentread-onlymandatoryThe UPS will turn off power to the load in less than 5 seconds; this may be either a timed shutdown or a low battery shutdown.
1.3.6.1.4.1.4555.1.1.1.1.6.3.24ScalarupsAlarmTestInProgressread-onlymandatoryA test is in progress, as initiated and indicated by the Test Group. Tests initiated via other implementation-specific mechanisms can indicate the presence of …
1.3.6.1.4.1.4555.1.1.1.1.6.3.25ScalarupsAlarmPowerSupplyFaultread-onlymandatoryDigital power supply fault.
1.3.6.1.4.1.4555.1.1.1.1.6.3.26ScalarupsAlarmAuxMainFailread-onlymandatoryBypass input supply is out of tolerance.
1.3.6.1.4.1.4555.1.1.1.1.6.3.27ScalarupsAlarmManualBypassCloseread-onlymandatoryThe maintenance bypass breaker is closed
1.3.6.1.4.1.4555.1.1.1.1.6.3.28ScalarupsAlarmShortCircuitread-onlymandatoryShort Circuit on UPS output.
1.3.6.1.4.1.4555.1.1.1.1.6.3.29ScalarupsAlarmBatteryChargerFailureread-onlymandatoryBattery charger failure.
1.3.6.1.4.1.4555.1.1.1.1.6.3.30ScalarupsAlarmInverterOverCurrentread-onlymandatoryInverter Over-current.
1.3.6.1.4.1.4555.1.1.1.1.6.3.31ScalarupsAlarmInverterDistorsionread-onlymandatoryExcessive Inverter Distorsion.
1.3.6.1.4.1.4555.1.1.1.1.6.3.32ScalarupsAlarmPrechargeVoltageFailread-onlymandatoryPrecharge voltage out of tolerance.
1.3.6.1.4.1.4555.1.1.1.1.6.3.33ScalarupsAlarmBoostTooLowread-onlymandatoryBoost output voltage too low.
1.3.6.1.4.1.4555.1.1.1.1.6.3.34ScalarupsAlarmBoostTooHighread-onlymandatoryBoost output voltage too high.
1.3.6.1.4.1.4555.1.1.1.1.6.3.35ScalarupsAlarmBatteryTooHighread-onlymandatoryBattery voltage too high.
1.3.6.1.4.1.4555.1.1.1.1.6.3.36ScalarupsAlarmImproperConditionread-onlymandatoryImproper condition of use
1.3.6.1.4.1.4555.1.1.1.1.6.3.37ScalarupsAlarmOverloadTimeoutread-onlymandatoryOverload timeout blocking Inverter.
1.3.6.1.4.1.4555.1.1.1.1.6.3.38ScalarupsAlarmControlSystemFailureread-onlymandatoryMicroprocessor control system failure
1.3.6.1.4.1.4555.1.1.1.1.6.3.39ScalarupsAlarmDataCorruptedread-onlymandatoryConfiguration data map corrupted.
1.3.6.1.4.1.4555.1.1.1.1.6.3.40ScalarupsAlarmPllFaultread-onlymandatoryPll fault.
1.3.6.1.4.1.4555.1.1.1.1.6.3.41ScalarupsAlarmInputGeneralAlarmread-onlymandatoryRectifier input supply out of tolorances or absent.
1.3.6.1.4.1.4555.1.1.1.1.6.3.42ScalarupsAlarmRectifierGeneralAlarmread-onlymandatoryRectifier general alarm.
1.3.6.1.4.1.4555.1.1.1.1.6.3.43ScalarupsAlarmBoostGeneralAlarmread-onlymandatoryBoost general alarm.
1.3.6.1.4.1.4555.1.1.1.1.6.3.44ScalarupsAlarmInverterGeneralAlarmread-onlymandatoryInverter general alarm.
1.3.6.1.4.1.4555.1.1.1.1.6.3.45ScalarupsAlarmBatteryGeneralAlarmread-onlymandatoryBattery charger general alarm.
1.3.6.1.4.1.4555.1.1.1.1.6.3.46ScalarupsAlarmOutputOverread-onlymandatoryOutput voltage over limit.
1.3.6.1.4.1.4555.1.1.1.1.6.3.47ScalarupsAlarmOutputUnderread-onlymandatoryOutput voltage under limit.
1.3.6.1.4.1.4555.1.1.1.1.6.3.48ScalarupsAlarmBypassGeneralAlarmread-onlymandatoryBypass general alarm.
1.3.6.1.4.1.4555.1.1.1.1.6.3.49ScalarupsAlarmStopForOverloadread-onlymandatoryStop for overload.
1.3.6.1.4.1.4555.1.1.1.1.6.3.50ScalarupsAlarmImminentStopread-onlymandatoryUPS imminent stop
1.3.6.1.4.1.4555.1.1.1.1.6.3.51ScalarupsAlarmModule1Alarmread-onlymandatoryModule 1 in parallel general alarm.
1.3.6.1.4.1.4555.1.1.1.1.6.3.52ScalarupsAlarmModule2Alarmread-onlymandatoryModule 2 in parallel general alarm.
1.3.6.1.4.1.4555.1.1.1.1.6.3.53ScalarupsAlarmModule3Alarmread-onlymandatoryModule 3 in parallel general alarm.
1.3.6.1.4.1.4555.1.1.1.1.6.3.54ScalarupsAlarmModule4Alarmread-onlymandatoryModule 4 in parallel general alarm.
1.3.6.1.4.1.4555.1.1.1.1.6.3.55ScalarupsAlarmModule5Alarmread-onlymandatoryModule 5 in parallel general alarm.
1.3.6.1.4.1.4555.1.1.1.1.6.3.56ScalarupsAlarmModule6Alarmread-onlymandatoryModule 6 in parallel general alarm.
1.3.6.1.4.1.4555.1.1.1.1.6.3.57ScalarupsAlarmExternalAlarm1read-onlymandatoryExternal Alarm 1.
1.3.6.1.4.1.4555.1.1.1.1.6.3.58ScalarupsAlarmExternalAlarm2read-onlymandatoryExternal Alarm 2.
1.3.6.1.4.1.4555.1.1.1.1.6.3.59ScalarupsAlarmExternalAlarm3read-onlymandatoryExternal Alarm 3.
1.3.6.1.4.1.4555.1.1.1.1.6.3.60ScalarupsAlarmExternalAlarm4read-onlymandatoryExternal Alarm 4.
1.3.6.1.4.1.4555.1.1.1.1.6.3.61ScalarupsAlarmEServiceread-onlymandatoryRemote Service Alarm
1.3.6.1.4.1.4555.1.1.1.1.6.3.62ScalarupsAlarmRedundancyLostread-onlymandatoryRedundancy lost
1.3.6.1.4.1.4555.1.1.1.1.6.3.63ScalarupsAlarmPeriodicServiceCheckread-onlymandatoryPeriodic service check up.
1.3.6.1.4.1.4555.1.1.1.1.6.3.64ScalarupsAlarmAllTransferDisabledread-onlymandatoryAutomatic and manual transfer disabled
1.3.6.1.4.1.4555.1.1.1.1.6.3.65ScalarupsAlarmAutoTransferDisabledread-onlymandatoryAutomatic transfer disabled
1.3.6.1.4.1.4555.1.1.1.1.6.3.66ScalarupsAlarmBatteryRoomread-onlymandatoryBattery room alarm
1.3.6.1.4.1.4555.1.1.1.1.6.3.67ScalarupsAlarmManualBypassread-onlymandatoryMaintenance bypass alarm
1.3.6.1.4.1.4555.1.1.1.1.6.3.68ScalarupsAlarmBatteryDischargedread-onlymandatoryBattery Discharged
1.3.6.1.4.1.4555.1.1.1.1.6.3.69ScalarupsAlarmInsufficientResourcesread-onlymandatoryInsufficient resources
1.3.6.1.4.1.4555.1.1.1.1.6.3.70ScalarupsAlarmOptionalBoardsread-onlymandatoryOptional boards general alarm
1.3.6.1.4.1.4555.1.1.1.1.6.3.71ScalarupsAlarmRectifierFaultread-onlymandatoryRectifier fault
1.3.6.1.4.1.4555.1.1.1.1.6.3.72ScalarupsAlarmBoostFaultread-onlymandatoryBoost fault
1.3.6.1.4.1.4555.1.1.1.1.6.3.73ScalarupsAlarmInverterFaultread-onlymandatoryInverter fault
1.3.6.1.4.1.4555.1.1.1.1.6.3.74ScalarupsAlarmParallelModuleFaultread-onlymandatoryParallel module fault
1.3.6.1.4.1.4555.1.1.1.1.6.3.75ScalarupsAlarmGenSetGeneralread-onlymandatoryGen-set general alarm
1.3.6.1.4.1.4555.1.1.1.1.6.3.76ScalarupsAlarmGenSetFaultread-onlymandatoryGen-set fault
1.3.6.1.4.1.4555.1.1.1.1.6.3.77ScalarupsAlarmEmergencyStopActiveread-onlymandatoryUPS power off active
1.3.6.1.4.1.4555.1.1.1.1.6.3.78ScalarupsAlarmBatteryCircuitOpenread-onlymandatoryBattery circuit open
1.3.6.1.4.1.4555.1.1.1.1.6.3.79ScalarupsAlarmFansFailureread-onlymandatoryFans failure
1.3.6.1.4.1.4555.1.1.1.1.6.3.80ScalarupsAlarmPhaseRotationFaultread-onlymandatoryPhase rotation fault
1.3.6.1.4.1.4555.1.1.1.1.6.3.81ScalarupsAlarmBypassFaultread-onlymandatoryBypass fault
1.3.6.1.4.1.4555.1.1.1.1.6.3.82ScalarupsAlarmA63read-onlymandatoryA63.
1.3.6.1.4.1.4555.1.1.1.1.6.3.83ScalarupsAlarmModule7Alarmread-onlymandatoryModule 7 in parallel general alarm.
1.3.6.1.4.1.4555.1.1.1.1.6.3.84ScalarupsAlarmModule8Alarmread-onlymandatoryModule 8 in parallel general alarm.
1.3.6.1.4.1.4555.1.1.1.1.6.3.85ScalarupsAlarmBatteryTemperatureread-onlymandatoryBattery Temperature Alarm.
1.3.6.1.4.1.4555.1.1.1.1.6.3.86ScalarupsAlarmRecRedundancyread-onlymandatoryRectifier Redundancy Alarm.
1.3.6.1.4.1.4555.1.1.1.1.6.3.87ScalarupsAlarmInvRedundancyread-onlymandatoryInverter Redundancy Alarm.
1.3.6.1.4.1.4555.1.1.1.1.7NodeupsTest
1.3.6.1.4.1.4555.1.1.1.1.7.1ScalarupsTestIdread-writemandatoryThe test named by an OBJECT IDENTIFIER which allows a standard mechanism for the initiation of test, including the well known tests identified in this document…
1.3.6.1.4.1.4555.1.1.1.1.7.2ScalarupsTestSpinLockread-writemandatoryA spin lock on the test subsystem. The spinlock is used as follows. Before starting a test, a manager-station should make sure that a test is not in progress a…
1.3.6.1.4.1.4555.1.1.1.1.7.3ScalarupsTestResultsSummaryread-onlymandatoryThe results of the current or last UPS diagnostics test performed. The values for donePass(1), doneWarning(2), and doneError(3) indicate that the test complete…
1.3.6.1.4.1.4555.1.1.1.1.7.4ScalarupsTestResultsDetailread-onlymandatoryAdditional information about upsTestResultsSummary. If no additional information available, a zero length string is returned.
1.3.6.1.4.1.4555.1.1.1.1.7.5ScalarupsTestStartTimeread-onlymandatoryThe value of sysUpTime at the time the test in progress was initiated, or, if no test is in progress, the time the previous test was initiated. If the value of…
1.3.6.1.4.1.4555.1.1.1.1.7.6ScalarupsTestElapsedTimeread-onlymandatoryThe amount of time, in TimeTicks, since the test in progress was initiated, or, if no test is in progress, the previous test took to complete. If the value of …
1.3.6.1.4.1.4555.1.1.1.1.7.7NodeupsWellKnownTests
1.3.6.1.4.1.4555.1.1.1.1.7.7.1ScalarupsTestNoTestsInitiatedread-onlymandatoryNo tests have been initiated and no test is in progress.
1.3.6.1.4.1.4555.1.1.1.1.7.7.2ScalarupsTestAbortTestInProgressread-onlymandatoryThe test in progress is to be aborted / the test in progress was aborted.
1.3.6.1.4.1.4555.1.1.1.1.7.7.3ScalarupsTestGeneralSystemsTestread-onlymandatoryThe manufacturer's standard test of UPS device systems.
1.3.6.1.4.1.4555.1.1.1.1.7.7.4ScalarupsTestQuickBatteryTestread-onlymandatoryA test that is sufficient to determine if the battery needs replacement.
1.3.6.1.4.1.4555.1.1.1.1.7.7.5ScalarupsDeepBatteryCalibrationread-onlymandatoryThe system is placed on battery to a discharge level, set by the manufacturer, sufficient to determine battery replacement and battery run-time with a high deg…
1.3.6.1.4.1.4555.1.1.1.1.8NodeupsControl
1.3.6.1.4.1.4555.1.1.1.1.8.1ScalarupsControlStatusControlread-writemandatoryThis object Control UPS status
1.3.6.1.4.1.4555.1.1.1.1.8.2ScalarupsShutdownDelayread-writemandatoryThis object set the delay time (in seconds) to turn UPS off after Net Vision broadcast shutdown request to connected clients
1.3.6.1.4.1.4555.1.1.1.1.8.3ScalarupsTurnOffAfterShutdownread-writemandatoryThis object enable/disable UPS turn off function after shutdown process complete
1.3.6.1.4.1.4555.1.1.1.1.8.4TableupsControlShutdownParametersTablenot-accessiblemandatoryTable which describes the parametes for shutdown process when shutdown event occurs
1.3.6.1.4.1.4555.1.1.1.1.8.4.1RowshutdownParametersEntrynot-accessiblemandatory
1.3.6.1.4.1.4555.1.1.1.1.8.4.1.1ColumnupsControlEventDescrread-onlymandatoryThe shutdown event identification
1.3.6.1.4.1.4555.1.1.1.1.8.4.1.2ColumnupsControlEventStatusread-writemandatoryStatus of the corresponding shutdown Event. When set to disable(), shutdown process will not start when corresponding event occured.
1.3.6.1.4.1.4555.1.1.1.1.8.4.1.3ColumnupsControlDelayread-writemandatoryThe Delay after the occurance of the curresponding shutdown event that Net Vision should issue shutdown request to connected clients. For WeeklyScheduledShutdo…
1.3.6.1.4.1.4555.1.1.1.1.8.4.1.4ColumnupsControlFirstWarningread-writemandatoryThe delay after the occurance of the curresponding shutdown event that the Net Vision will start sending the warning message to the connected clients. The valu…
1.3.6.1.4.1.4555.1.1.1.1.8.4.1.5ColumnupsControlWarningIntervalread-writemandatoryThe frequency of sending warning messages to the connected clients when the curresponding shutdown event occurs. The value is in units of seconds.
1.3.6.1.4.1.4555.1.1.1.1.8.5TableupsControlWeeklyScheduleTablenot-accessiblemandatoryThe table to schedule shutting down the ups by weekly.
1.3.6.1.4.1.4555.1.1.1.1.8.5.1RowupsControlWeeklyScheduleEntrynot-accessiblemandatoryThe entries for each day.
1.3.6.1.4.1.4555.1.1.1.1.8.5.1.1ColumnupsControlWeeklyIndexread-onlymandatoryThe index of scheduled events.
1.3.6.1.4.1.4555.1.1.1.1.8.5.1.2ColumnupsControlWeeklyShutdownDayread-writemandatoryThe weekday on which the UPS should shut down.
1.3.6.1.4.1.4555.1.1.1.1.8.5.1.3ColumnupsControlWeeklyShutdownTimeread-writemandatoryThe time that the process of shutting down the UPS will be initiated in hh:mm:ss format.
1.3.6.1.4.1.4555.1.1.1.1.8.5.1.4ColumnupsControlWeeklyRestartDayread-writemandatoryThe weekday on which the UPS should restart
1.3.6.1.4.1.4555.1.1.1.1.8.5.1.5ColumnupsControlWeeklyRestartTimeread-writemandatoryThe time the UPS will restart in hh:mm:ss format.
1.3.6.1.4.1.4555.1.1.1.1.8.6TableupsControlSpecialScheduleTablenot-accessiblemandatoryThe table to schedule shutting down the ups.
1.3.6.1.4.1.4555.1.1.1.1.8.6.1RowupsControlSpecialScheduleEntrynot-accessiblemandatoryThe entries for each day.
1.3.6.1.4.1.4555.1.1.1.1.8.6.1.1ColumnupsControlSpecialIndexread-onlymandatoryThe index of scheduled events.
1.3.6.1.4.1.4555.1.1.1.1.8.6.1.2ColumnupsControlSpecialShutdownDayread-writemandatoryThe date on which the UPS should shut down in dd/mm/yyyy format.
1.3.6.1.4.1.4555.1.1.1.1.8.6.1.3ColumnupsControlSpecialShutdownTimeread-writemandatoryThe time that the process of shutting down the UPS will be initiated in hh:mm:ss format
1.3.6.1.4.1.4555.1.1.1.1.8.6.1.4ColumnupsControlSpecialRestartDayread-writemandatoryThe date on which the UPS should restart in dd/mm/yyyy format
1.3.6.1.4.1.4555.1.1.1.1.8.6.1.5ColumnupsControlSpecialRestartTimeread-writemandatoryThe time the UPS will restart in hh:mm:ss format.
1.3.6.1.4.1.4555.1.1.1.1.8.7TableupsControlEcoModeScheduleTablenot-accessiblemandatoryThe table to schedule enable/disable ups eco/mode by weekly.
1.3.6.1.4.1.4555.1.1.1.1.8.7.1RowupsControlEcoModeScheduleEntrynot-accessiblemandatoryThe entries for each day.
1.3.6.1.4.1.4555.1.1.1.1.8.7.1.1ColumnupsControlEcoModeIndexread-onlymandatoryThe index of scheduled events.
1.3.6.1.4.1.4555.1.1.1.1.8.7.1.2ColumnupsControlEcoModeStartDayread-writemandatoryThe weekday on which the UPS Eco/Mode should enable.
1.3.6.1.4.1.4555.1.1.1.1.8.7.1.3ColumnupsControlEcoModeStartTimeread-writemandatoryThe time that the UPS Eco/Mode will be enabled, in hh:mm:ss format.
1.3.6.1.4.1.4555.1.1.1.1.8.7.1.4ColumnupsControlEcoModeEndDayread-writemandatoryThe weekday on which the UPS Eco/Mode should disable
1.3.6.1.4.1.4555.1.1.1.1.8.7.1.5ColumnupsControlEcoModeEndTimeread-writemandatoryThe time the UPS Eco/Mode will disabled, in hh:mm:ss format.
1.3.6.1.4.1.4555.1.1.1.1.9NodeupsConfig
1.3.6.1.4.1.4555.1.1.1.1.9.1ScalarupsConfigInputVoltageread-onlymandatoryThe magnitude of the nominal input voltage.
1.3.6.1.4.1.4555.1.1.1.1.9.2ScalarupsConfigInputFreqread-onlymandatoryThe nominal input frequency.
1.3.6.1.4.1.4555.1.1.1.1.9.3ScalarupsConfigOutputVoltageread-onlymandatoryThe magnitude of the nominal output voltage.
1.3.6.1.4.1.4555.1.1.1.1.9.4ScalarupsConfigOutputFreqread-onlymandatoryThe nominal output frequency.
1.3.6.1.4.1.4555.1.1.1.1.9.5TableupsDevicesTablenot-accessiblemandatoryThe devices powered by UPS and registered to Net Vision
1.3.6.1.4.1.4555.1.1.1.1.9.5.1RowupsDevicesEntrynot-accessiblemandatoryThe devices protected by Net Vision
1.3.6.1.4.1.4555.1.1.1.1.9.5.1.1ColumnindexOfDeviceread-onlymandatoryThe index of the device that is plugged into the UPS.
1.3.6.1.4.1.4555.1.1.1.1.9.5.1.2ColumnaddrOfDeviceread-onlymandatoryThe ip address of the device.
1.3.6.1.4.1.4555.1.1.1.1.9.5.1.3ColumnnameOfDeviceread-onlymandatoryThe name/description of the device plugged into the UPS.
1.3.6.1.4.1.4555.1.1.1.1.9.5.1.4ColumntimeOfConnectionread-onlymandatoryThe that device registered to Net Vision
1.3.6.1.4.1.4555.1.1.1.1.9.5.1.5ColumnstatusOfConnectionread-onlymandatorystatus
1.3.6.1.4.1.4555.1.1.1.1.9.5.1.6ColumnseverityOfConnectionread-onlymandatoryseverity
1.3.6.1.4.1.4555.1.1.1.1.10NodeupsAgent
1.3.6.1.4.1.4555.1.1.1.1.10.1ScalarupsAgentIpaddressread-writemandatoryThe ip address that NMS can identify the managed device
1.3.6.1.4.1.4555.1.1.1.1.10.2ScalarupsAgentGatewayread-writemandatoryThe default gateway that allow device managed through routers
1.3.6.1.4.1.4555.1.1.1.1.10.3ScalarupsAgentSubnetMaskread-writemandatoryInternet address subnet mask
1.3.6.1.4.1.4555.1.1.1.1.10.4ScalarupsAgentDateread-writemandatoryThe date in agent, format is (dd/mm/yyyy)
1.3.6.1.4.1.4555.1.1.1.1.10.5ScalarupsAgentTimeread-writemandatoryThe time in agent, format is (hh:mm:ss)
1.3.6.1.4.1.4555.1.1.1.1.10.6ScalarupsAgentNtpTimeServerread-writemandatory
1.3.6.1.4.1.4555.1.1.1.1.10.7ScalarupsAgentNtpTimeZoneread-writemandatory
1.3.6.1.4.1.4555.1.1.1.1.10.8ScalarupsAgentHistoryLogFrequencyread-writemandatoryThe frequency of the updation of the history log. The value is in seconds
1.3.6.1.4.1.4555.1.1.1.1.10.9ScalarupsAgentExtHistoryLogFrequencyread-writemandatoryThe ups parameters are sampled at the rate governed by the mconfigHistroyLogFrequency. These sampled values are further conslidated over period of time which i…
1.3.6.1.4.1.4555.1.1.1.1.10.10ScalarupsAgentPollRateread-writemandatoryThe frequency that proxy agent polls the connected UPS in JBUS protocol. (unit : second)
1.3.6.1.4.1.4555.1.1.1.1.10.11ScalarupsAgentBaudRateread-writemandatoryThe serial port communication speed (2400/9600 allowed).
1.3.6.1.4.1.4555.1.1.1.1.10.12ScalarupsAgentDhcpStatusread-writemandatoryEnable or disable DHCP-BootP capability
1.3.6.1.4.1.4555.1.1.1.1.10.13ScalarupsAgentTelnetStatusread-writemandatoryEnable or disable telnet access
1.3.6.1.4.1.4555.1.1.1.1.10.14ScalarupsAgentTftpStatusread-writemandatoryEnable or disable network upgrade capability
1.3.6.1.4.1.4555.1.1.1.1.10.15ScalarupsAgentResetToDefaultread-writemandatoryReset all parameters of Net Vision to default value
1.3.6.1.4.1.4555.1.1.1.1.10.16ScalarupsAgentRestartread-writemandatoryRestart Net Vision
1.3.6.1.4.1.4555.1.1.1.1.10.17ScalarupsAgentClearAgentLogread-writemandatoryClear agent log data
1.3.6.1.4.1.4555.1.1.1.1.10.18ScalarupsAgentClearEventLogread-writemandatoryClear event log data
1.3.6.1.4.1.4555.1.1.1.1.10.19ScalarupsAgentClearExtHistoryLogread-writemandatoryClear extented history log data
1.3.6.1.4.1.4555.1.1.1.1.10.20ScalarupsAgentClearHistoryLogread-writemandatoryClear history log data
1.3.6.1.4.1.4555.1.1.1.1.10.21TableupsAgentTrapsReceiversTablenot-accessiblemandatoryA list of managers to send traps to. The number of entries is given by the value of upsAgentNumTrapReceivers
1.3.6.1.4.1.4555.1.1.1.1.10.21.1RowupsAgentTrapsReceiversEntrynot-accessiblemandatoryThe managers to send traps to.
1.3.6.1.4.1.4555.1.1.1.1.10.21.1.1ColumntrapsIndexread-onlymandatoryThe index to a trap receiver entry.
1.3.6.1.4.1.4555.1.1.1.1.10.21.1.2ColumntrapsReceiverAddrread-writemandatoryThe IP address of the manager to send a trap to.
1.3.6.1.4.1.4555.1.1.1.1.10.21.1.3ColumnreceiverCommunityStringread-writemandatoryThe community name to use in the trap when sent to the manager.
1.3.6.1.4.1.4555.1.1.1.1.10.21.1.4ColumnreceiverNmstyperead-writemandatoryThe trap group that NMS desired.
1.3.6.1.4.1.4555.1.1.1.1.10.22TableupsAgentAccessControlTablenot-accessiblemandatoryA list of managers which can access Net Vision with private community string.
1.3.6.1.4.1.4555.1.1.1.1.10.22.1RowupsAgentAccessControlEntrynot-accessiblemandatoryThe managers.
1.3.6.1.4.1.4555.1.1.1.1.10.22.1.1ColumnaccessIndexread-onlymandatoryThe index to a access control entry.
1.3.6.1.4.1.4555.1.1.1.1.10.22.1.2ColumnaccessControlAddrread-writemandatoryThe IP address of the manager to access Net Vision
1.3.6.1.4.1.4555.1.1.1.1.10.22.1.3ColumnaccessCommunityStringread-writemandatoryThe community name to use in the manager when access Net Vision
1.3.6.1.4.1.4555.1.1.1.1.10.22.1.4ColumnaccessControlModeread-writemandatoryAccess type, only read-Write access type can change parameter of Net Vision
1.3.6.1.4.1.4555.1.1.1.1.10.23ScalarupsAgentMibVersionread-onlymandatoryThe version of MIB spec.
1.3.6.1.4.1.4555.1.1.1.1.10.50ScalarupsAgentTrapStringread-onlymandatoryThis OID allows traps to be sent with an octet string argument that my not be defined in the. A get of this OID will return error or NULL string.
1.3.6.1.4.1.4555.1.1.1.1.11NodeemdStatus
1.3.6.1.4.1.4555.1.1.1.1.11.1ScalaremdSatatusTemperatureread-onlymandatoryThe measurement of EMD temperature, in 0.1 degree
1.3.6.1.4.1.4555.1.1.1.1.11.2ScalaremdSatatusHumidityread-onlymandatoryThe measurement of EMD humidity, in 0.1 degree
1.3.6.1.4.1.4555.1.1.1.2NodeupsTraps
1.3.6.1.4.1.4555.1.1.1.2.1NodeupsTrapOnBatteryThe UPS is operating on battery power. This trap is persistent and is resent at one minute intervals until the UPS either turns off or is no longer running on …
1.3.6.1.4.1.4555.1.1.1.2.2NodeupsTrapTestCompletedThis trap is sent upon completion of a UPS diagnostic test.
1.3.6.1.4.1.4555.1.1.1.2.3NodeupsTrapAlarmEntryAddedThis trap is sent each time an alarm is inserted into to the alarm table. It is sent on the insertion of all alarms except for upsAlarmOnBattery and upsAlarmTe…
1.3.6.1.4.1.4555.1.1.1.2.4NodeupsTrapAlarmEntryRemovedThis trap is sent each time an alarm is removed from the alarm table. It is sent on the removal of all alarms except for upsAlarmTestInProgress.
1.3.6.1.4.1.4555.1.1.1.2.5NodeupsTrapUpsNormalINFORMATION: The UPS status is normal.
1.3.6.1.4.1.4555.1.1.1.2.6NodeupsTrapUpsBattTestFailedSEVERE: UPS failed the last test of battery.
1.3.6.1.4.1.4555.1.1.1.2.7NodeupsTrapOnBatteryPowerWARNING: The UPS has switched to battery backup power.
1.3.6.1.4.1.4555.1.1.1.2.8NodeupsTrapBatteryLowSEVERE: Battery is near to be discharged.
1.3.6.1.4.1.4555.1.1.1.2.9NodeupsTrapPowerRestoredINFORMATION: Input power has been restored.
1.3.6.1.4.1.4555.1.1.1.2.10NodeupsTrapImminentStopSEVERE: The UPS is near to switch off the output power.
1.3.6.1.4.1.4555.1.1.1.2.11NodeupsTrapTurnedOffWARNING: The UPS has been turned off by the management station.
1.3.6.1.4.1.4555.1.1.1.2.12NodeupsTrapOverTemperatureSEVERE: The UPS has sensed a temperature greater than its limit.
1.3.6.1.4.1.4555.1.1.1.2.13NodeupsTrapOverloadSEVERE: The UPS has sensed a load greater than 100 percent of its rated capacity.
1.3.6.1.4.1.4555.1.1.1.2.14NodeupsTrapOnMainsSEVERE: The UPS output is on mains.
1.3.6.1.4.1.4555.1.1.1.2.15NodeupsTrapRedoundancyLostSEVERE: Redoundancy is lost.
1.3.6.1.4.1.4555.1.1.1.2.16NodeupsTrapEmdTempLowSEVERE: EMD Sensor detected low temperature.
1.3.6.1.4.1.4555.1.1.1.2.17NodeupsTrapEmdTempNotLowinformation: EMD Sensor Not under low temperature.
1.3.6.1.4.1.4555.1.1.1.2.18NodeupsTrapEmdTempHighSEVERE: EMD Sensor detected high temperature.
1.3.6.1.4.1.4555.1.1.1.2.19NodeupsTrapEmdTempNotHighinformation: EMD Sensor Not over high temperature.
1.3.6.1.4.1.4555.1.1.1.2.20NodeupsTrapEmdHumidityLowSEVERE: EMD Sensor detected low humidity.
1.3.6.1.4.1.4555.1.1.1.2.21NodeupsTrapEmdHumidityNotLowinformation: EMD Sensor Not under low humidity.
1.3.6.1.4.1.4555.1.1.1.2.22NodeupsTrapEmdHumidityHighSEVERE: EMD Sensor detected high humidity.
1.3.6.1.4.1.4555.1.1.1.2.23NodeupsTrapEmdHumidityNotHighinformation: EMD Sensor Not over high humidity.
1.3.6.1.4.1.4555.1.1.1.2.24NodeupsTrapEmdFirstInputActiveSEVERE: The <customized string_1> input is active.
1.3.6.1.4.1.4555.1.1.1.2.25NodeupsTrapEmdFirstInputRestoredINFORMATION: The <customized string_1> input is restored.
1.3.6.1.4.1.4555.1.1.1.2.26NodeupsTrapEmdSecondInputActiveSEVERE: The <customized string_2> input is active.
1.3.6.1.4.1.4555.1.1.1.2.27NodeupsTrapEmdSecondInputRestoredINFORMATION: The <customized string_2> input is restored.