SOCOMECUPS-MIB-v2
489 objects
No module-level DESCRIPTION found.
Imported Objects
| RFC-1212 | OBJECT-TYPE |
| RFC-1215 | TRAP-TYPE |
| RFC1155-SMI | enterprises |
| RFC1213-MIB | DisplayString |
| OID | Name | Access | Status | Description |
|---|---|---|---|---|
| 1.3.6.1.4.1.4555 | NodesocomecSicon | |||
| 1.3.6.1.4.1.4555.1 | Nodeproduct | |||
| 1.3.6.1.4.1.4555.1.1 | NodepduAgent | |||
| 1.3.6.1.4.1.4555.1.1.20 | NodeiPDU | |||
| 1.3.6.1.4.1.4555.1.1.20.1 | NodeipduObjects | |||
| 1.3.6.1.4.1.4555.1.1.20.1.1 | NodeipduIdent | |||
| 1.3.6.1.4.1.4555.1.1.20.1.1.1 | ScalaripduIdentManufacturer | read-write | mandatory | The name of manufacturer. |
| 1.3.6.1.4.1.4555.1.1.20.1.1.2 | ScalaripduIdentModel | read-write | mandatory | The Model designation of device. |
| 1.3.6.1.4.1.4555.1.1.20.1.1.3 | ScalaripduIdentAgentSoftwareVersion | read-only | mandatory | The firmware version of the device. |
| 1.3.6.1.4.1.4555.1.1.20.1.1.4 | ScalaripduIdentName | read-write | mandatory | A description of this device. |
| 1.3.6.1.4.1.4555.1.1.20.1.2 | NodeipduAgent | |||
| 1.3.6.1.4.1.4555.1.1.20.1.2.1 | NodeipduAgentConfig | |||
| 1.3.6.1.4.1.4555.1.1.20.1.2.1.1 | ScalaripduAgentMibVersion | read-only | mandatory | The Mib Version implemented on this device. |
| 1.3.6.1.4.1.4555.1.1.20.1.2.1.4 | NodeipduAgentLog | |||
| 1.3.6.1.4.1.4555.1.1.20.1.2.1.4.1 | ScalarpduAgentDataLogInterval | read-write | mandatory | The interval of the updation of the data log. The value is in seconds |
| 1.3.6.1.4.1.4555.1.1.20.1.2.1.5 | NodeipduAgentControl | |||
| 1.3.6.1.4.1.4555.1.1.20.1.2.1.5.1 | ScalaripduAgentControlDefault | read-write | mandatory | Reset all parameters of the agent to default value. |
| 1.3.6.1.4.1.4555.1.1.20.1.2.1.5.2 | ScalaripduAgentControlRestart | read-write | mandatory | Restart the agent. |
| 1.3.6.1.4.1.4555.1.1.20.1.2.1.6 | NodeipduAgentTrap | |||
| 1.3.6.1.4.1.4555.1.1.20.1.2.1.6.1 | ScalaripduAgentTrapRetryCount | read-write | mandatory | The count of repeat traps send to NMS before trap acknowledgement received. |
| 1.3.6.1.4.1.4555.1.1.20.1.2.1.6.2 | ScalaripduAgentTrapRetryTime | read-write | mandatory | The time interval in seconds between retry traps sned to NMS. |
| 1.3.6.1.4.1.4555.1.1.20.1.2.1.6.3 | ScalaripduAgentTrapAckSignature | read-write | mandatory | The signature of trap acknowledgement. |
| 1.3.6.1.4.1.4555.1.1.20.1.2.1.7 | TableipduAgentTrapsReceiversTable | not-accessible | mandatory | A list of managers to send traps to. The number of entries is given by the value of agentConfigNumTrapReceivers |
| 1.3.6.1.4.1.4555.1.1.20.1.2.1.7.1 | RowipduAgentTrapsReceiversEntry | not-accessible | mandatory | The managers to send traps to. |
| 1.3.6.1.4.1.4555.1.1.20.1.2.1.7.1.1 | ColumntrapsIndex | read-only | mandatory | The index to a trap receiver entry. |
| 1.3.6.1.4.1.4555.1.1.20.1.2.1.7.1.2 | ColumntrapsReceiverAddr | read-write | mandatory | The IP address of the manager to send a trap to. |
| 1.3.6.1.4.1.4555.1.1.20.1.2.1.7.1.3 | ColumnreceiverCommunityString | read-write | mandatory | The community name to use in the trap when sent to the manager. |
| 1.3.6.1.4.1.4555.1.1.20.1.2.1.7.1.4 | ColumnreceiverNmsType | read-write | mandatory | The trap group that NMS desired. |
| 1.3.6.1.4.1.4555.1.1.20.1.2.1.7.1.5 | ColumnreceiverSeverityLevel | read-write | mandatory | The severity level of traps to be received by this manager. |
| 1.3.6.1.4.1.4555.1.1.20.1.2.1.7.1.6 | ColumnreceiverDescription | read-write | mandatory | Description of trap receivers |
| 1.3.6.1.4.1.4555.1.1.20.1.2.1.8 | TableipduAgentAccessControlTable | not-accessible | mandatory | A list of managers which can access the device with private community string. |
| 1.3.6.1.4.1.4555.1.1.20.1.2.1.8.1 | RowipduAgentAccessControlEntry | not-accessible | mandatory | The managers. |
| 1.3.6.1.4.1.4555.1.1.20.1.2.1.8.1.1 | ColumnaccessIndex | read-only | mandatory | The index to a access control entry. |
| 1.3.6.1.4.1.4555.1.1.20.1.2.1.8.1.2 | ColumnaccessControlAddr | read-write | mandatory | The IP address of the manager to access the device. |
| 1.3.6.1.4.1.4555.1.1.20.1.2.1.8.1.3 | ColumnaccessControlMode | read-write | mandatory | Access type, only read/Write access type can change parameter of the device. |
| 1.3.6.1.4.1.4555.1.1.20.1.2.2 | NodeipduAgentTime | |||
| 1.3.6.1.4.1.4555.1.1.20.1.2.2.1 | ScalaripduAgentTimeDate | read-write | mandatory | The date in agent, format is (dd/mm/yyyy) |
| 1.3.6.1.4.1.4555.1.1.20.1.2.2.2 | ScalaripduAgentTimeTime | read-write | mandatory | The time in agent, format is (hh:mm:ss) |
| 1.3.6.1.4.1.4555.1.1.20.1.2.2.3 | ScalaripduAgentTimerFromNtp | read-write | mandatory | Enable or disable the agent to synchronize date/time with NTP server. |
| 1.3.6.1.4.1.4555.1.1.20.1.2.2.4 | ScalaripduAgentNtpIpAddress | read-write | mandatory | The ip address of NTP server. |
| 1.3.6.1.4.1.4555.1.1.20.1.2.2.5 | ScalaripduAgentNtpTimeZone | read-write | mandatory | Time Zone to use when synchronize with NTP server. |
| 1.3.6.1.4.1.4555.1.1.20.1.2.2.6 | ScalaripduAgentDayLightSaving | read-write | mandatory | Enable/disable the Day Light Saving when synchronize with NTP server. |
| 1.3.6.1.4.1.4555.1.1.20.1.2.3 | NodeipduAgentNetwork | |||
| 1.3.6.1.4.1.4555.1.1.20.1.2.3.1 | NodeipduAgentNetworkIp | |||
| 1.3.6.1.4.1.4555.1.1.20.1.2.3.1.1 | ScalaripduAgentNetworkIpAdress | read-write | mandatory | The ip address that NMS can identify the managed device. |
| 1.3.6.1.4.1.4555.1.1.20.1.2.3.1.2 | ScalaripduAgentNetworkIpGateway | read-write | mandatory | The default gateway that allow device managed through routers. |
| 1.3.6.1.4.1.4555.1.1.20.1.2.3.1.3 | ScalaripduAgentNetworkIpSubnet | read-write | mandatory | Internet address subnet mask |
| 1.3.6.1.4.1.4555.1.1.20.1.2.3.2 | ScalaripduAgentNetworkDhcpControl | read-write | mandatory | Enable/disable DHCP protocol |
| 1.3.6.1.4.1.4555.1.1.20.1.2.3.3 | ScalaripduAgentNetworkPingControl | read-write | mandatory | Enable/disable to response to PING request. |
| 1.3.6.1.4.1.4555.1.1.20.1.2.3.4 | ScalaripduAgentNetworkTftpControl | read-write | mandatory | Enable/disable TFTP protocol |
| 1.3.6.1.4.1.4555.1.1.20.1.2.3.5 | NodeipduAgentNetworkTelnet | |||
| 1.3.6.1.4.1.4555.1.1.20.1.2.3.5.1 | ScalaripduAgentTelnetControl | read-write | mandatory | Enable/disable Telnet protocol. |
| 1.3.6.1.4.1.4555.1.1.20.1.2.3.5.2 | ScalaripduAgentTelnetPort | read-write | mandatory | The TCP port for telnet |
| 1.3.6.1.4.1.4555.1.1.20.1.2.3.6 | NodeipduAgentNetworkHttp | |||
| 1.3.6.1.4.1.4555.1.1.20.1.2.3.6.1 | ScalaripduAgentHttpControl | read-write | mandatory | Enable/disable HTTP protocol. |
| 1.3.6.1.4.1.4555.1.1.20.1.2.3.6.2 | ScalaripduAgentHttpPort | read-write | mandatory | The TCP port for HTTP. |
| 1.3.6.1.4.1.4555.1.1.20.1.2.3.7 | NodeipduAgentNetworkSnmp | |||
| 1.3.6.1.4.1.4555.1.1.20.1.2.3.7.1 | ScalaripduAgentSnmpControl | read-write | mandatory | Enable/disable SNMP protocol. |
| 1.3.6.1.4.1.4555.1.1.20.1.2.3.7.2 | ScalaripduAgentSnmpPort | read-write | mandatory | The UDP port for SNMP. |
| 1.3.6.1.4.1.4555.1.1.20.1.3 | NodeipduDevice | |||
| 1.3.6.1.4.1.4555.1.1.20.1.3.1 | NodeipduDeviceInlet | |||
| 1.3.6.1.4.1.4555.1.1.20.1.3.1.1 | ScalaripduDeviceInletNumber | read-only | mandatory | The inlet number on this device. |
| 1.3.6.1.4.1.4555.1.1.20.1.3.1.2 | TableipduDeviceInletConfigTable | not-accessible | mandatory | A list of inlet on this device. |
| 1.3.6.1.4.1.4555.1.1.20.1.3.1.2.1 | RowipduDeviceInletConfigEntry | not-accessible | mandatory | The inlet number of device. |
| 1.3.6.1.4.1.4555.1.1.20.1.3.1.2.1.1 | ColumninletConfigIndex | read-only | mandatory | The index to a access inlet configuration table. |
| 1.3.6.1.4.1.4555.1.1.20.1.3.1.2.1.2 | ColumninletConfigDesc | read-write | mandatory | A Description of inlet of device. |
| 1.3.6.1.4.1.4555.1.1.20.1.3.1.2.1.3 | ColumninletConfigVoltageHigh | read-write | mandatory | The Inlet high voltage threshold, in volts. |
| 1.3.6.1.4.1.4555.1.1.20.1.3.1.2.1.4 | ColumninletConfigVoltageHighAction | read-write | mandatory | Reaction of the device when inlet voltage higher than set point. |
| 1.3.6.1.4.1.4555.1.1.20.1.3.1.2.1.5 | ColumninletConfigVoltageLow | read-write | mandatory | The Inlet low voltage threshold, in volts. |
| 1.3.6.1.4.1.4555.1.1.20.1.3.1.2.1.6 | ColumninletConfigVoltageLowAction | read-write | mandatory | Reaction of the device when inlet voltage lower than set point. |
| 1.3.6.1.4.1.4555.1.1.20.1.3.1.2.1.7 | ColumninletConfigCurrentHigh | read-write | mandatory | The Inlet low voltage threshold, in 0.1 amps. |
| 1.3.6.1.4.1.4555.1.1.20.1.3.1.2.1.8 | ColumninletConfigCurrentHighAction | read-write | mandatory | Reaction of the device when inlet current higher than set point. |
| 1.3.6.1.4.1.4555.1.1.20.1.3.1.2.1.9 | ColumninletConfigFrequencyHigh | read-write | mandatory | The Inlet high frequency threshold, in hz. |
| 1.3.6.1.4.1.4555.1.1.20.1.3.1.2.1.10 | ColumninletConfigfrequencyHighAction | read-write | mandatory | Reaction of the device when inlet frequency higher than set point. |
| 1.3.6.1.4.1.4555.1.1.20.1.3.1.2.1.11 | ColumninletConfigFrequencyLow | read-write | mandatory | The Inlet low frequency threshold, in hz. |
| 1.3.6.1.4.1.4555.1.1.20.1.3.1.2.1.12 | ColumninletConfigfrequencyLowAction | read-write | mandatory | Reaction of the device when inlet frequency lower than set point. |
| 1.3.6.1.4.1.4555.1.1.20.1.3.1.3 | TableipduDeviceInletStatusTable | not-accessible | mandatory | A list of inlet on this device. |
| 1.3.6.1.4.1.4555.1.1.20.1.3.1.3.1 | RowipduDeviceInletStatusEntry | not-accessible | mandatory | The inlet number of device. |
| 1.3.6.1.4.1.4555.1.1.20.1.3.1.3.1.1 | ColumninletStatusIndex | read-only | mandatory | The index to a access inlet configuration table. |
| 1.3.6.1.4.1.4555.1.1.20.1.3.1.3.1.2 | ColumninletStatusVoltage | read-only | mandatory | The Inlet Voltage in 0.1 volts |
| 1.3.6.1.4.1.4555.1.1.20.1.3.1.3.1.3 | ColumninletStatusCurrent | read-only | mandatory | The Inlet Current in 0.001 Amp. |
| 1.3.6.1.4.1.4555.1.1.20.1.3.1.3.1.4 | ColumninletStatusFrequency | read-only | mandatory | The Inlet Frequency in 0.1 Hz |
| 1.3.6.1.4.1.4555.1.1.20.1.3.1.3.1.5 | ColumninletStatusKwatt | read-only | mandatory | The Inlet Kwatt in 0.1 KW/H |
| 1.3.6.1.4.1.4555.1.1.20.1.3.1.3.1.6 | ColumninletStatusWH | read-only | mandatory | The Inlet Kwatt in 0.1 W/H |
| 1.3.6.1.4.1.4555.1.1.20.1.3.1.4 | ScalarinletWattReset | read-write | mandatory | Reset inlet kw. |
| 1.3.6.1.4.1.4555.1.1.20.1.3.2 | NodeipduDeviceOutlet | |||
| 1.3.6.1.4.1.4555.1.1.20.1.3.2.1 | ScalaripduDeviceOutletNumber | read-only | mandatory | The outlet number on this device. |
| 1.3.6.1.4.1.4555.1.1.20.1.3.2.2 | TableipduDeviceOutletConfigTable | not-accessible | mandatory | A list of outlet on this device. |
| 1.3.6.1.4.1.4555.1.1.20.1.3.2.2.1 | RowipduDeviceOutletConfigEntry | not-accessible | mandatory | The inlet number of device. |
| 1.3.6.1.4.1.4555.1.1.20.1.3.2.2.1.1 | ColumnoutletConfigIndex | read-only | mandatory | The index to a access inlet configuration table. |
| 1.3.6.1.4.1.4555.1.1.20.1.3.2.2.1.2 | ColumnoutletConfigDesc | read-write | mandatory | A Description of outlet of device. |
| 1.3.6.1.4.1.4555.1.1.20.1.3.2.2.1.3 | ColumnoutletConfigLocation | read-write | mandatory | Location of device connectted to this outlet. |
| 1.3.6.1.4.1.4555.1.1.20.1.3.2.2.1.4 | ColumnoutletConfigOnDelay | read-write | mandatory | The delay time before turn on tis outlet, in seconds. |
| 1.3.6.1.4.1.4555.1.1.20.1.3.2.2.1.5 | ColumnoutletConfigOffDelay | read-write | mandatory | The delay time before turn off tis outlet, in seconds. |
| 1.3.6.1.4.1.4555.1.1.20.1.3.2.2.1.6 | ColumnoutletConfigCurrentHigh | read-write | mandatory | The outlet high current threshold, in amp. |
| 1.3.6.1.4.1.4555.1.1.20.1.3.2.2.1.7 | ColumnoutletConfigCurrentHighAction | read-write | mandatory | Reaction of the device when outlet current higher than set point. |
| 1.3.6.1.4.1.4555.1.1.20.1.3.2.3 | TableipduDeviceOutletStatusTable | not-accessible | mandatory | A list of outlet on this device. |
| 1.3.6.1.4.1.4555.1.1.20.1.3.2.3.1 | RowipduDeviceOutletStatusEntry | not-accessible | mandatory | The outlet number of device. |
| 1.3.6.1.4.1.4555.1.1.20.1.3.2.3.1.1 | ColumnoutletStatusIndex | read-only | mandatory | The index to a access outlet configuration table. |
| 1.3.6.1.4.1.4555.1.1.20.1.3.2.3.1.2 | ColumnoutletStatusStatus | read-only | mandatory | Outlet state |
| 1.3.6.1.4.1.4555.1.1.20.1.3.2.3.1.3 | ColumnoutletStatusCurrent | read-only | mandatory | The outlet Current in 0.001 Amp. |
| 1.3.6.1.4.1.4555.1.1.20.1.3.2.3.1.4 | ColumnoutletStatusKwatt | read-only | mandatory | The outlet Kwatt in 0.001 KW/H. |
| 1.3.6.1.4.1.4555.1.1.20.1.3.2.3.1.5 | ColumnoutletStatusWH | read-only | mandatory | The outlet Watt in 0.1 W/H. |
| 1.3.6.1.4.1.4555.1.1.20.1.3.2.3.1.6 | ColumnoutletStatusStateTime | read-only | mandatory | Time in seconds since the outlet changed to current state. |
| 1.3.6.1.4.1.4555.1.1.20.1.3.2.3.1.7 | ColumnoutletStatusTimeToGo | read-only | mandatory | Remain time the outlet state will be changed by agent, in seconds |
| 1.3.6.1.4.1.4555.1.1.20.1.3.2.4 | TableipduDeviceOutletControlTable | not-accessible | mandatory | A list of outlet on this device. |
| 1.3.6.1.4.1.4555.1.1.20.1.3.2.4.1 | RowipduDeviceOutletControlEntry | not-accessible | mandatory | The outlet number of device. |
| 1.3.6.1.4.1.4555.1.1.20.1.3.2.4.1.1 | ColumnoutletControlIndex | read-only | mandatory | The index to a access outlet configuration table. |
| 1.3.6.1.4.1.4555.1.1.20.1.3.2.4.1.2 | ColumnoutletControlControl | read-write | mandatory | Set to control the outlet perform action as requested. |
| 1.3.6.1.4.1.4555.1.1.20.1.3.2.5 | ScalaripduDeviceOutletControlAll | read-write | mandatory | Set to control all outlets perform action as requested. |
| 1.3.6.1.4.1.4555.1.1.20.1.3.2.6 | ScalaripduDeviceOutletWattReset | read-write | mandatory | Reset outlet kw. |
| 1.3.6.1.4.1.4555.1.1.20.1.3.3 | NodeipduDeviceCcOut | |||
| 1.3.6.1.4.1.4555.1.1.20.1.3.3.1 | ScalaripduDeviceCcOutNumber | read-only | mandatory | The contact closure output number on this device. |
| 1.3.6.1.4.1.4555.1.1.20.1.3.3.2 | TableipduDeviceCcOutConfigTable | not-accessible | mandatory | A list of contact closure output on this device. |
| 1.3.6.1.4.1.4555.1.1.20.1.3.3.2.1 | RowipduDeviceCcOutConfigEntry | not-accessible | mandatory | The CC number of device. |
| 1.3.6.1.4.1.4555.1.1.20.1.3.3.2.1.1 | ColumnccOutConfigIndex | read-only | mandatory | The index to access contact closure output configuration table. |
| 1.3.6.1.4.1.4555.1.1.20.1.3.3.2.1.2 | ColumnccOutConfigDesc | read-write | mandatory | A Description of a contact closure output of device. |
| 1.3.6.1.4.1.4555.1.1.20.1.3.3.2.1.3 | ColumnccOutConfigEventAction | read-write | mandatory | Enable/disble the contact closure output to react to events. |
| 1.3.6.1.4.1.4555.1.1.20.1.3.3.2.1.4 | ColumnccOutConfigCloseDelay | read-write | mandatory | The delay time in seconds when the contact closure output set to close. |
| 1.3.6.1.4.1.4555.1.1.20.1.3.3.2.1.5 | ColumnccOutConfigOpenDelay | read-write | mandatory | The delay time in seconds when the contact closure output set to open. |
| 1.3.6.1.4.1.4555.1.1.20.1.3.3.3 | TableipduDeviceCcOutStatusTable | not-accessible | mandatory | A list of contact closure output on this device. |
| 1.3.6.1.4.1.4555.1.1.20.1.3.3.3.1 | RowipduDeviceCcOutStatusEntry | not-accessible | mandatory | The CC number of device. |
| 1.3.6.1.4.1.4555.1.1.20.1.3.3.3.1.1 | ColumnccOutStatusIndex | read-only | mandatory | The index to access contact closure output configuration table. |
| 1.3.6.1.4.1.4555.1.1.20.1.3.3.3.1.2 | ColumnccOutStatusStatus | read-only | mandatory | State of a contact closure output of device. |
| 1.3.6.1.4.1.4555.1.1.20.1.3.3.3.1.3 | ColumnccOutStatusTimeOnState | read-only | mandatory | Time in seconds since the contact closure output changed to current state. |
| 1.3.6.1.4.1.4555.1.1.20.1.3.3.4 | TableipduDeviceCcOutControlTable | not-accessible | mandatory | A list of contact closure output on this device. |
| 1.3.6.1.4.1.4555.1.1.20.1.3.3.4.1 | RowipduDeviceCcOutControlEntry | not-accessible | mandatory | The outlet number of device. |
| 1.3.6.1.4.1.4555.1.1.20.1.3.3.4.1.1 | ColumnccOutControlIndex | read-only | mandatory | The index to a access contact closure output configuration table. |
| 1.3.6.1.4.1.4555.1.1.20.1.3.3.4.1.2 | ColumnccOutControlControl | read-write | mandatory | Set to control the contact closure output perform action as requested. |
| 1.3.6.1.4.1.4555.1.1.20.1.4 | NodeipduSlave | |||
| 1.3.6.1.4.1.4555.1.1.20.1.4.1 | NodeipduSlaveState | |||
| 1.3.6.1.4.1.4555.1.1.20.1.4.1.1 | TableipduSlaveStateTable | not-accessible | mandatory | A list of outlet on this device. |
| 1.3.6.1.4.1.4555.1.1.20.1.4.1.1.1 | RowipduSlaveStateEntry | not-accessible | mandatory | The outlet number of device. |
| 1.3.6.1.4.1.4555.1.1.20.1.4.1.1.1.1 | ColumnslaveStateIndex | read-only | mandatory | The index to a access outlet configuration table. |
| 1.3.6.1.4.1.4555.1.1.20.1.4.1.1.1.2 | ColumnslaveStateControl01 | read-only | mandatory | Set to control the outlet perform action as requested to slave outlet A |
| 1.3.6.1.4.1.4555.1.1.20.1.4.2 | NodeipduSlaveInlet | |||
| 1.3.6.1.4.1.4555.1.1.20.1.4.2.1 | NodeipduSlaveInletStatus | |||
| 1.3.6.1.4.1.4555.1.1.20.1.4.2.1.1 | TableipduDeviceSlaveInletStatusTable | not-accessible | mandatory | A list of inlet on this device. |
| 1.3.6.1.4.1.4555.1.1.20.1.4.2.1.1.1 | RowipduDeviceSlaveInletStatusEntry | not-accessible | mandatory | The inlet number of device. |
| 1.3.6.1.4.1.4555.1.1.20.1.4.2.1.1.1.1 | ColumninletSlaveStatusIndex | read-only | mandatory | The index to a access inlet configuration table. |
| 1.3.6.1.4.1.4555.1.1.20.1.4.2.1.1.1.2 | ColumninletSlaveStatusVoltage | read-only | mandatory | The Inlet Voltage in 0.1 volts |
| 1.3.6.1.4.1.4555.1.1.20.1.4.2.1.1.1.3 | ColumninletSlaveStatusCurrent | read-only | mandatory | The Inlet Current in 0.001 Amp. |
| 1.3.6.1.4.1.4555.1.1.20.1.4.2.1.1.1.4 | ColumninletSlaveStatusFrequency | read-only | mandatory | The Inlet Frequency in 0.1 Hz |
| 1.3.6.1.4.1.4555.1.1.20.1.4.2.1.1.1.5 | ColumninletSlaveStatusKwatt | read-only | mandatory | The Inlet Kwatt in 0.001 KW/H |
| 1.3.6.1.4.1.4555.1.1.20.1.4.2.1.1.1.6 | ColumninletSlaveStatusWH | read-only | mandatory | The Inlet Kwatt in 0.001 KW/H |
| 1.3.6.1.4.1.4555.1.1.20.1.4.2.1.1.1.7 | ColumninletSlaveStatusVoltage2 | read-only | mandatory | The Inlet Voltage in 0.1 volts |
| 1.3.6.1.4.1.4555.1.1.20.1.4.2.1.1.1.8 | ColumninletSlaveStatusCurrent2 | read-only | mandatory | The Inlet Current in 0.001 Amp. |
| 1.3.6.1.4.1.4555.1.1.20.1.4.2.1.1.1.9 | ColumninletSlaveStatusFrequency2 | read-only | mandatory | The Inlet Frequency in 0.1 Hz |
| 1.3.6.1.4.1.4555.1.1.20.1.4.2.1.1.1.10 | ColumninletSlaveStatusKwatt2 | read-only | mandatory | The Inlet Kwatt in 0.001 KW/H |
| 1.3.6.1.4.1.4555.1.1.20.1.4.2.1.1.1.11 | ColumninletSlaveStatusWH2 | read-only | mandatory | The Inlet Kwatt in 0.001 KW/H |
| 1.3.6.1.4.1.4555.1.1.20.1.4.2.2 | NodeipduSlaveInletConfig | |||
| 1.3.6.1.4.1.4555.1.1.20.1.4.2.2.1 | TableipduDeviceslaveInletConfigTable | not-accessible | mandatory | A list of inlet on this device. |
| 1.3.6.1.4.1.4555.1.1.20.1.4.2.2.1.1 | RowipduDeviceslaveInletConfigEntry | not-accessible | mandatory | The inlet number of device. |
| 1.3.6.1.4.1.4555.1.1.20.1.4.2.2.1.1.1 | ColumnslaveInletConfigIndex | read-only | mandatory | The index to a access inlet configuration table. |
| 1.3.6.1.4.1.4555.1.1.20.1.4.2.2.1.1.2 | ColumnslaveInletConfigVoltageHigh | read-write | mandatory | The Inlet high voltage threshold, in volts. |
| 1.3.6.1.4.1.4555.1.1.20.1.4.2.2.1.1.3 | ColumnslaveInletConfigVoltageLow | read-write | mandatory | The Inlet low voltage threshold, in volts. |
| 1.3.6.1.4.1.4555.1.1.20.1.4.2.2.1.1.4 | ColumnslaveInlet2ConfigVoltageHigh | read-write | mandatory | The Inlet 2 high voltage threshold, in volts. |
| 1.3.6.1.4.1.4555.1.1.20.1.4.2.2.1.1.5 | ColumnslaveInlet2ConfigVoltageLow | read-write | mandatory | The Inlet low voltage threshold, in volts. |
| 1.3.6.1.4.1.4555.1.1.20.1.4.3 | NodeipduSlaveOutlet | |||
| 1.3.6.1.4.1.4555.1.1.20.1.4.3.1 | NodeipduSlaveOutletConfig | |||
| 1.3.6.1.4.1.4555.1.1.20.1.4.3.1.1 | TableipduSlaveDeviceOutletNameTable | not-accessible | mandatory | A list of outlet on this device. |
| 1.3.6.1.4.1.4555.1.1.20.1.4.3.1.1.1 | RowipduSlaveDeviceOutletNameEntry | not-accessible | mandatory | The outlet number of device. |
| 1.3.6.1.4.1.4555.1.1.20.1.4.3.1.1.1.1 | ColumnslaveOutletNameIndex | read-only | mandatory | The index to a access outlet configuration table. |
| 1.3.6.1.4.1.4555.1.1.20.1.4.3.1.1.1.2 | ColumnslaveOutletName01 | read-write | mandatory | A Description of a outlet name of device. |
| 1.3.6.1.4.1.4555.1.1.20.1.4.3.1.1.1.3 | ColumnslaveOutletName02 | read-write | mandatory | A Description of a outlet name of device. |
| 1.3.6.1.4.1.4555.1.1.20.1.4.3.1.1.1.4 | ColumnslaveOutletName03 | read-write | mandatory | A Description of a outlet name of device. |
| 1.3.6.1.4.1.4555.1.1.20.1.4.3.1.1.1.5 | ColumnslaveOutletName04 | read-write | mandatory | A Description of a outlet name of device. |
| 1.3.6.1.4.1.4555.1.1.20.1.4.3.1.1.1.6 | ColumnslaveOutletName05 | read-write | mandatory | A Description of a outlet name of device. |
| 1.3.6.1.4.1.4555.1.1.20.1.4.3.1.1.1.7 | ColumnslaveOutletName06 | read-write | mandatory | A Description of a outlet name of device. |
| 1.3.6.1.4.1.4555.1.1.20.1.4.3.1.1.1.8 | ColumnslaveOutletName07 | read-write | mandatory | A Description of a outlet name of device. |
| 1.3.6.1.4.1.4555.1.1.20.1.4.3.1.1.1.9 | ColumnslaveOutletName08 | read-write | mandatory | A Description of a outlet name of device. |
| 1.3.6.1.4.1.4555.1.1.20.1.4.3.1.1.1.10 | ColumnslaveOutletName09 | read-write | mandatory | A Description of a outlet name of device. |
| 1.3.6.1.4.1.4555.1.1.20.1.4.3.1.1.1.11 | ColumnslaveOutletName10 | read-write | mandatory | A Description of a outlet name of device. |
| 1.3.6.1.4.1.4555.1.1.20.1.4.3.1.1.1.12 | ColumnslaveOutletName11 | read-write | mandatory | A Description of a outlet name of device. |
| 1.3.6.1.4.1.4555.1.1.20.1.4.3.1.1.1.13 | ColumnslaveOutletName12 | read-write | mandatory | A Description of a outlet name of device. |
| 1.3.6.1.4.1.4555.1.1.20.1.4.3.1.2 | TableipduSlaveDeviceOutletLocationTable | not-accessible | mandatory | A list of outlet on this device. |
| 1.3.6.1.4.1.4555.1.1.20.1.4.3.1.2.1 | RowipduSlaveDeviceOutletLocationEntry | not-accessible | mandatory | The outlet number of device. |
| 1.3.6.1.4.1.4555.1.1.20.1.4.3.1.2.1.1 | ColumnslaveOutletLocationIndex | read-only | mandatory | The index to a access outlet configuration table. |
| 1.3.6.1.4.1.4555.1.1.20.1.4.3.1.2.1.2 | ColumnslaveOutletLocation01 | read-write | mandatory | A Description of a outlet name of device. |
| 1.3.6.1.4.1.4555.1.1.20.1.4.3.1.2.1.3 | ColumnslaveOutletLocation02 | read-write | mandatory | A Description of a outlet name of device. |
| 1.3.6.1.4.1.4555.1.1.20.1.4.3.1.2.1.4 | ColumnslaveOutletLocation03 | read-write | mandatory | A Description of a outlet name of device. |
| 1.3.6.1.4.1.4555.1.1.20.1.4.3.1.2.1.5 | ColumnslaveOutletLocation04 | read-write | mandatory | A Description of a outlet name of device. |
| 1.3.6.1.4.1.4555.1.1.20.1.4.3.1.2.1.6 | ColumnslaveOutletLocation05 | read-write | mandatory | A Description of a outlet name of device. |
| 1.3.6.1.4.1.4555.1.1.20.1.4.3.1.2.1.7 | ColumnslaveOutletLocation06 | read-write | mandatory | A Description of a outlet name of device. |
| 1.3.6.1.4.1.4555.1.1.20.1.4.3.1.2.1.8 | ColumnslaveOutletLocation07 | read-write | mandatory | A Description of a outlet name of device. |
| 1.3.6.1.4.1.4555.1.1.20.1.4.3.1.2.1.9 | ColumnslaveOutletLocation08 | read-write | mandatory | A Description of a outlet name of device. |
| 1.3.6.1.4.1.4555.1.1.20.1.4.3.1.2.1.10 | ColumnslaveOutletLocation09 | read-write | mandatory | A Description of a outlet name of device. |
| 1.3.6.1.4.1.4555.1.1.20.1.4.3.1.2.1.11 | ColumnslaveOutletLocation10 | read-write | mandatory | A Description of a outlet name of device. |
| 1.3.6.1.4.1.4555.1.1.20.1.4.3.1.2.1.12 | ColumnslaveOutletLocation11 | read-write | mandatory | A Description of a outlet name of device. |
| 1.3.6.1.4.1.4555.1.1.20.1.4.3.1.2.1.13 | ColumnslaveOutletLocation12 | read-write | mandatory | A Description of a outlet name of device. |
| 1.3.6.1.4.1.4555.1.1.20.1.4.3.1.3 | TableipduSlaveDeviceOutletOnTimeTable | not-accessible | mandatory | A list of outlet on this device. |
| 1.3.6.1.4.1.4555.1.1.20.1.4.3.1.3.1 | RowipduSlaveDeviceOutletOnTimeEntry | not-accessible | mandatory | The outlet number of device. |
| 1.3.6.1.4.1.4555.1.1.20.1.4.3.1.3.1.1 | ColumnslaveOutletOnTimeIndex | read-only | mandatory | The index to a access outlet configuration table. |
| 1.3.6.1.4.1.4555.1.1.20.1.4.3.1.3.1.2 | ColumnslaveOutletOnTime01 | read-write | mandatory | The delay time before turn on tis outlet, in seconds. |
| 1.3.6.1.4.1.4555.1.1.20.1.4.3.1.3.1.3 | ColumnslaveOutletOnTime02 | read-write | mandatory | The delay time before turn on tis outlet, in seconds. |
| 1.3.6.1.4.1.4555.1.1.20.1.4.3.1.3.1.4 | ColumnslaveOutletOnTime03 | read-write | mandatory | The delay time before turn on tis outlet, in seconds. |
| 1.3.6.1.4.1.4555.1.1.20.1.4.3.1.3.1.5 | ColumnslaveOutletOnTime04 | read-write | mandatory | The delay time before turn on tis outlet, in seconds. |
| 1.3.6.1.4.1.4555.1.1.20.1.4.3.1.3.1.6 | ColumnslaveOutletOnTime05 | read-write | mandatory | The delay time before turn on tis outlet, in seconds. |
| 1.3.6.1.4.1.4555.1.1.20.1.4.3.1.3.1.7 | ColumnslaveOutletOnTime06 | read-write | mandatory | The delay time before turn on tis outlet, in seconds. |
| 1.3.6.1.4.1.4555.1.1.20.1.4.3.1.3.1.8 | ColumnslaveOutletOnTime07 | read-write | mandatory | The delay time before turn on tis outlet, in seconds. |
| 1.3.6.1.4.1.4555.1.1.20.1.4.3.1.3.1.9 | ColumnslaveOutletOnTime08 | read-write | mandatory | The delay time before turn on tis outlet, in seconds. |
| 1.3.6.1.4.1.4555.1.1.20.1.4.3.1.3.1.10 | ColumnslaveOutletOnTime09 | read-write | mandatory | The delay time before turn on tis outlet, in seconds. |
| 1.3.6.1.4.1.4555.1.1.20.1.4.3.1.3.1.11 | ColumnslaveOutletOnTime10 | read-write | mandatory | The delay time before turn on tis outlet, in seconds. |
| 1.3.6.1.4.1.4555.1.1.20.1.4.3.1.3.1.12 | ColumnslaveOutletOnTime11 | read-write | mandatory | The delay time before turn on tis outlet, in seconds. |
| 1.3.6.1.4.1.4555.1.1.20.1.4.3.1.3.1.13 | ColumnslaveOutletOnTime12 | read-write | mandatory | The delay time before turn on tis outlet, in seconds. |
| 1.3.6.1.4.1.4555.1.1.20.1.4.3.1.4 | TableipduSlaveDeviceOutletOffTimeTable | not-accessible | mandatory | A list of outlet on this device. |
| 1.3.6.1.4.1.4555.1.1.20.1.4.3.1.4.1 | RowipduSlaveDeviceOutletOffTimeEntry | not-accessible | mandatory | The outlet number of device. |
| 1.3.6.1.4.1.4555.1.1.20.1.4.3.1.4.1.1 | ColumnslaveOutletOffTimeIndex | read-only | mandatory | The index to a access outlet configuration table. |
| 1.3.6.1.4.1.4555.1.1.20.1.4.3.1.4.1.2 | ColumnslaveOutletOffTime01 | read-write | mandatory | The delay time before turn on tis outlet, in seconds. |
| 1.3.6.1.4.1.4555.1.1.20.1.4.3.1.4.1.3 | ColumnslaveOutletOffTime02 | read-write | mandatory | The delay time before turn on tis outlet, in seconds. |
| 1.3.6.1.4.1.4555.1.1.20.1.4.3.1.4.1.4 | ColumnslaveOutletOffTime03 | read-write | mandatory | The delay time before turn on tis outlet, in seconds. |
| 1.3.6.1.4.1.4555.1.1.20.1.4.3.1.4.1.5 | ColumnslaveOutletOffTime04 | read-write | mandatory | The delay time before turn on tis outlet, in seconds. |
| 1.3.6.1.4.1.4555.1.1.20.1.4.3.1.4.1.6 | ColumnslaveOutletOffTime05 | read-write | mandatory | The delay time before turn on tis outlet, in seconds. |
| 1.3.6.1.4.1.4555.1.1.20.1.4.3.1.4.1.7 | ColumnslaveOutletOffTime06 | read-write | mandatory | The delay time before turn on tis outlet, in seconds. |
| 1.3.6.1.4.1.4555.1.1.20.1.4.3.1.4.1.8 | ColumnslaveOutletOffTime07 | read-write | mandatory | The delay time before turn on tis outlet, in seconds. |
| 1.3.6.1.4.1.4555.1.1.20.1.4.3.1.4.1.9 | ColumnslaveOutletOffTime08 | read-write | mandatory | The delay time before turn on tis outlet, in seconds. |
| 1.3.6.1.4.1.4555.1.1.20.1.4.3.1.4.1.10 | ColumnslaveOutletOffTime09 | read-write | mandatory | The delay time before turn on tis outlet, in seconds. |
| 1.3.6.1.4.1.4555.1.1.20.1.4.3.1.4.1.11 | ColumnslaveOutletOffTime10 | read-write | mandatory | The delay time before turn on tis outlet, in seconds. |
| 1.3.6.1.4.1.4555.1.1.20.1.4.3.1.4.1.12 | ColumnslaveOutletOffTime11 | read-write | mandatory | The delay time before turn on tis outlet, in seconds. |
| 1.3.6.1.4.1.4555.1.1.20.1.4.3.1.4.1.13 | ColumnslaveOutletOffTime12 | read-write | mandatory | The delay time before turn on tis outlet, in seconds. |
| 1.3.6.1.4.1.4555.1.1.20.1.4.3.1.5 | TableipduSlaveDeviceOutletCurrThTable | not-accessible | mandatory | A list of outlet on this device. |
| 1.3.6.1.4.1.4555.1.1.20.1.4.3.1.5.1 | RowipduSlaveDeviceOutletCurrThEntry | not-accessible | mandatory | The outlet number of device. |
| 1.3.6.1.4.1.4555.1.1.20.1.4.3.1.5.1.1 | ColumnslaveOutletCurrThIndex | read-only | mandatory | The index to a access outlet configuration table. |
| 1.3.6.1.4.1.4555.1.1.20.1.4.3.1.5.1.2 | ColumnslaveOutletCurrTh01 | read-write | mandatory | The Outlet Current Threshold ,in 0.1 Amp. |
| 1.3.6.1.4.1.4555.1.1.20.1.4.3.1.5.1.3 | ColumnslaveOutletCurrTh02 | read-write | mandatory | The Outlet Current Threshold ,in 0.1 Amp. |
| 1.3.6.1.4.1.4555.1.1.20.1.4.3.1.5.1.4 | ColumnslaveOutletCurrTh03 | read-write | mandatory | The Outlet Current Threshold ,in 0.1 Amp. |
| 1.3.6.1.4.1.4555.1.1.20.1.4.3.1.5.1.5 | ColumnslaveOutletCurrTh04 | read-write | mandatory | The Outlet Current Threshold ,in 0.1 Amp. |
| 1.3.6.1.4.1.4555.1.1.20.1.4.3.1.5.1.6 | ColumnslaveOutletCurrTh05 | read-write | mandatory | The Outlet Current Threshold ,in 0.1 Amp. |
| 1.3.6.1.4.1.4555.1.1.20.1.4.3.1.5.1.7 | ColumnslaveOutletCurrTh06 | read-write | mandatory | The Outlet Current Threshold ,in 0.1 Amp. |
| 1.3.6.1.4.1.4555.1.1.20.1.4.3.1.5.1.8 | ColumnslaveOutletCurrTh07 | read-write | mandatory | The Outlet Current Threshold ,in 0.1 Amp. |
| 1.3.6.1.4.1.4555.1.1.20.1.4.3.1.5.1.9 | ColumnslaveOutletCurrTh08 | read-write | mandatory | The Outlet Current Threshold ,in 0.1 Amp. |
| 1.3.6.1.4.1.4555.1.1.20.1.4.3.1.5.1.10 | ColumnslaveOutletCurrTh09 | read-write | mandatory | The Outlet Current Threshold ,in 0.1 Amp. |
| 1.3.6.1.4.1.4555.1.1.20.1.4.3.1.5.1.11 | ColumnslaveOutletCurrTh10 | read-write | mandatory | The Outlet Current Threshold ,in 0.1 Amp. |
| 1.3.6.1.4.1.4555.1.1.20.1.4.3.1.5.1.12 | ColumnslaveOutletCurrTh11 | read-write | mandatory | The Outlet Current Threshold ,in 0.1 Amp. |
| 1.3.6.1.4.1.4555.1.1.20.1.4.3.1.5.1.13 | ColumnslaveOutletCurrTh12 | read-write | mandatory | The Outlet Current Threshold ,in 0.1 Amp. |
| 1.3.6.1.4.1.4555.1.1.20.1.4.3.2 | NodeipduSlaveOutletStatus | |||
| 1.3.6.1.4.1.4555.1.1.20.1.4.3.2.1 | TableipduSlaveDeviceOutletCurrentTable | not-accessible | mandatory | A list of outlet on this device. |
| 1.3.6.1.4.1.4555.1.1.20.1.4.3.2.1.1 | RowipduSlaveDeviceOutletCurrentEntry | not-accessible | mandatory | The outlet number of device. |
| 1.3.6.1.4.1.4555.1.1.20.1.4.3.2.1.1.1 | ColumnslaveOutletCurrentIndex | read-only | mandatory | The index to a access outlet configuration table. |
| 1.3.6.1.4.1.4555.1.1.20.1.4.3.2.1.1.2 | ColumnslaveOutletCurrent01 | read-only | mandatory | The outlet A Current in 0.001 Amp. |
| 1.3.6.1.4.1.4555.1.1.20.1.4.3.2.1.1.3 | ColumnslaveOutletCurrent02 | read-only | mandatory | The outlet B Current in 0.001 Amp. |
| 1.3.6.1.4.1.4555.1.1.20.1.4.3.2.1.1.4 | ColumnslaveOutletCurrent03 | read-only | mandatory | The outlet C Current in 0.001 Amp. |
| 1.3.6.1.4.1.4555.1.1.20.1.4.3.2.1.1.5 | ColumnslaveOutletCurrent04 | read-only | mandatory | The outlet D Current in 0.001 Amp. |
| 1.3.6.1.4.1.4555.1.1.20.1.4.3.2.1.1.6 | ColumnslaveOutletCurrent05 | read-only | mandatory | The outlet E Current in 0.001 Amp. |
| 1.3.6.1.4.1.4555.1.1.20.1.4.3.2.1.1.7 | ColumnslaveOutletCurrent06 | read-only | mandatory | The outlet F Current in 0.001 Amp. |
| 1.3.6.1.4.1.4555.1.1.20.1.4.3.2.1.1.8 | ColumnslaveOutletCurrent07 | read-only | mandatory | The outlet G Current in 0.001 Amp. |
| 1.3.6.1.4.1.4555.1.1.20.1.4.3.2.1.1.9 | ColumnslaveOutletCurrent08 | read-only | mandatory | The outlet H Current in 0.001 Amp. |
| 1.3.6.1.4.1.4555.1.1.20.1.4.3.2.1.1.10 | ColumnslaveOutletCurrent09 | read-only | mandatory | The outlet I Current in 0.001 Amp. |
| 1.3.6.1.4.1.4555.1.1.20.1.4.3.2.1.1.11 | ColumnslaveOutletCurrent10 | read-only | mandatory | The outlet J Current in 0.001 Amp. |
| 1.3.6.1.4.1.4555.1.1.20.1.4.3.2.1.1.12 | ColumnslaveOutletCurrent11 | read-only | mandatory | The outlet K Current in 0.001 Amp. |
| 1.3.6.1.4.1.4555.1.1.20.1.4.3.2.1.1.13 | ColumnslaveOutletCurrent12 | read-only | mandatory | The outlet L Current in 0.001 Amp. |
| 1.3.6.1.4.1.4555.1.1.20.1.4.3.2.2 | TableipduSlaveDeviceOutletWattTable | not-accessible | mandatory | A list of outlet on this device. |
| 1.3.6.1.4.1.4555.1.1.20.1.4.3.2.2.1 | RowipduSlaveDeviceOutletWattEntry | not-accessible | mandatory | The outlet number of device. |
| 1.3.6.1.4.1.4555.1.1.20.1.4.3.2.2.1.1 | ColumnslaveOutletWattIndex | read-only | mandatory | The index to a access outlet configuration table. |
| 1.3.6.1.4.1.4555.1.1.20.1.4.3.2.2.1.2 | ColumnslaveOutletWatt01 | read-only | mandatory | The outlet A Watt in 0.1 W/H. |
| 1.3.6.1.4.1.4555.1.1.20.1.4.3.2.2.1.3 | ColumnslaveOutletWatt02 | read-only | mandatory | The outlet B Watt in 0.1 W/H. |
| 1.3.6.1.4.1.4555.1.1.20.1.4.3.2.2.1.4 | ColumnslaveOutletWatt03 | read-only | mandatory | The outlet C Watt in 0.1 W/H. |
| 1.3.6.1.4.1.4555.1.1.20.1.4.3.2.2.1.5 | ColumnslaveOutletWatt04 | read-only | mandatory | The outlet D Watt in 0.1 W/H. |
| 1.3.6.1.4.1.4555.1.1.20.1.4.3.2.2.1.6 | ColumnslaveOutletWatt05 | read-only | mandatory | The outlet E Watt in 0.1 W/H. |
| 1.3.6.1.4.1.4555.1.1.20.1.4.3.2.2.1.7 | ColumnslaveOutletWatt06 | read-only | mandatory | The outlet F Watt in 0.1 W/H. |
| 1.3.6.1.4.1.4555.1.1.20.1.4.3.2.2.1.8 | ColumnslaveOutletWatt07 | read-only | mandatory | The outlet G Watt in 0.1 W/H. |
| 1.3.6.1.4.1.4555.1.1.20.1.4.3.2.2.1.9 | ColumnslaveOutletWatt08 | read-only | mandatory | The outlet H Watt in 0.1 W/H. |
| 1.3.6.1.4.1.4555.1.1.20.1.4.3.2.2.1.10 | ColumnslaveOutletWatt09 | read-only | mandatory | The outlet I Watt in 0.1 W/H. |
| 1.3.6.1.4.1.4555.1.1.20.1.4.3.2.2.1.11 | ColumnslaveOutletWatt10 | read-only | mandatory | The outlet J Watt in 0.1 W/H. |
| 1.3.6.1.4.1.4555.1.1.20.1.4.3.2.2.1.12 | ColumnslaveOutletWatt11 | read-only | mandatory | The outlet K Watt in 0.1 W/H. |
| 1.3.6.1.4.1.4555.1.1.20.1.4.3.2.2.1.13 | ColumnslaveOutletWatt12 | read-only | mandatory | The outlet L Watt in 0.1 W/H. |
| 1.3.6.1.4.1.4555.1.1.20.1.4.3.2.3 | TableipduSlaveDeviceOutletKwattTable | not-accessible | mandatory | A list of outlet on this device. |
| 1.3.6.1.4.1.4555.1.1.20.1.4.3.2.3.1 | RowipduSlaveDeviceOutletKwattEntry | not-accessible | mandatory | The outlet number of device. |
| 1.3.6.1.4.1.4555.1.1.20.1.4.3.2.3.1.1 | ColumnslaveOutletKwattIndex | read-only | mandatory | The index to a access outlet configuration table. |
| 1.3.6.1.4.1.4555.1.1.20.1.4.3.2.3.1.2 | ColumnslaveOutletKwatt01 | read-only | mandatory | The outlet A Kwatt in 0.001 KW/H. |
| 1.3.6.1.4.1.4555.1.1.20.1.4.3.2.3.1.3 | ColumnslaveOutletKwatt02 | read-only | mandatory | The outlet B Kwatt in 0.001 KW/H. |
| 1.3.6.1.4.1.4555.1.1.20.1.4.3.2.3.1.4 | ColumnslaveOutletKwatt03 | read-only | mandatory | The outlet C Kwatt in 0.001 KW/H. |
| 1.3.6.1.4.1.4555.1.1.20.1.4.3.2.3.1.5 | ColumnslaveOutletKwatt04 | read-only | mandatory | The outlet D Kwatt in 0.001 KW/H. |
| 1.3.6.1.4.1.4555.1.1.20.1.4.3.2.3.1.6 | ColumnslaveOutletKwatt05 | read-only | mandatory | The outlet E Kwatt in 0.001 KW/H. |
| 1.3.6.1.4.1.4555.1.1.20.1.4.3.2.3.1.7 | ColumnslaveOutletKwatt06 | read-only | mandatory | The outlet F Kwatt in 0.001 KW/H. |
| 1.3.6.1.4.1.4555.1.1.20.1.4.3.2.3.1.8 | ColumnslaveOutletKwatt07 | read-only | mandatory | The outlet G Kwatt in 0.001 KW/H. |
| 1.3.6.1.4.1.4555.1.1.20.1.4.3.2.3.1.9 | ColumnslaveOutletKwatt08 | read-only | mandatory | The outlet H Kwatt in 0.001 KW/H. |
| 1.3.6.1.4.1.4555.1.1.20.1.4.3.2.3.1.10 | ColumnslaveOutletKwatt09 | read-only | mandatory | The outlet I Kwatt in 0.001 KW/H. |
| 1.3.6.1.4.1.4555.1.1.20.1.4.3.2.3.1.11 | ColumnslaveOutletKwatt10 | read-only | mandatory | The outlet J Kwatt in 0.001 KW/H. |
| 1.3.6.1.4.1.4555.1.1.20.1.4.3.2.3.1.12 | ColumnslaveOutletKwatt11 | read-only | mandatory | The outlet K Kwatt in 0.001 KW/H. |
| 1.3.6.1.4.1.4555.1.1.20.1.4.3.2.3.1.13 | ColumnslaveOutletKwatt12 | read-only | mandatory | The outlet L Kwatt in 0.001 KW/H. |
| 1.3.6.1.4.1.4555.1.1.20.1.4.3.3 | NodeipduSlaveOutletAction | |||
| 1.3.6.1.4.1.4555.1.1.20.1.4.3.3.1 | TableipduSlaveDeviceOutletActionTable | not-accessible | mandatory | A list of outlet on this device. |
| 1.3.6.1.4.1.4555.1.1.20.1.4.3.3.1.1 | RowipduSlaveDeviceOutletActionEntry | not-accessible | mandatory | The outlet number of device. |
| 1.3.6.1.4.1.4555.1.1.20.1.4.3.3.1.1.1 | ColumnslaveOutletActionIndex | read-only | mandatory | The index to a access outlet configuration table. |
| 1.3.6.1.4.1.4555.1.1.20.1.4.3.3.1.1.2 | ColumnslaveOutletAction01 | read-write | mandatory | Set to control the outlet perform action as requested. |
| 1.3.6.1.4.1.4555.1.1.20.1.4.3.3.1.1.3 | ColumnslaveOutletAction02 | read-write | mandatory | Set to control the outlet perform action as requested. |
| 1.3.6.1.4.1.4555.1.1.20.1.4.3.3.1.1.4 | ColumnslaveOutletAction03 | read-write | mandatory | Set to control the outlet perform action as requested. |
| 1.3.6.1.4.1.4555.1.1.20.1.4.3.3.1.1.5 | ColumnslaveOutletAction04 | read-write | mandatory | Set to control the outlet perform action as requested. |
| 1.3.6.1.4.1.4555.1.1.20.1.4.3.3.1.1.6 | ColumnslaveOutletAction05 | read-write | mandatory | Set to control the outlet perform action as requested. |
| 1.3.6.1.4.1.4555.1.1.20.1.4.3.3.1.1.7 | ColumnslaveOutletAction06 | read-write | mandatory | Set to control the outlet perform action as requested. |
| 1.3.6.1.4.1.4555.1.1.20.1.4.3.3.1.1.8 | ColumnslaveOutletAction07 | read-write | mandatory | Set to control the outlet perform action as requested. |
| 1.3.6.1.4.1.4555.1.1.20.1.4.3.3.1.1.9 | ColumnslaveOutletAction08 | read-write | mandatory | Set to control the outlet perform action as requested. |
| 1.3.6.1.4.1.4555.1.1.20.1.4.3.3.1.1.10 | ColumnslaveOutletAction09 | read-write | mandatory | Set to control the outlet perform action as requested. |
| 1.3.6.1.4.1.4555.1.1.20.1.4.3.3.1.1.11 | ColumnslaveOutletAction10 | read-write | mandatory | Set to control the outlet perform action as requested. |
| 1.3.6.1.4.1.4555.1.1.20.1.4.3.3.1.1.12 | ColumnslaveOutletAction11 | read-write | mandatory | Set to control the outlet perform action as requested. |
| 1.3.6.1.4.1.4555.1.1.20.1.4.3.3.1.1.13 | ColumnslaveOutletAction12 | read-write | mandatory | Set to control the outlet perform action as requested. |
| 1.3.6.1.4.1.4555.1.1.20.1.5 | NodeipduEnv | |||
| 1.3.6.1.4.1.4555.1.1.20.1.5.1 | NodeipduEnvEmd | |||
| 1.3.6.1.4.1.4555.1.1.20.1.5.1.1 | NodeipduEnvEmdStatus | |||
| 1.3.6.1.4.1.4555.1.1.20.1.5.1.1.1 | ScalaripduEnvEmdStatusEmdType | read-only | mandatory | EMD Type. |
| 1.3.6.1.4.1.4555.1.1.20.1.5.1.1.2 | ScalaripduEnvEmdStatusTemperature | read-only | mandatory | EMD Temperature in 0.1 degree C. |
| 1.3.6.1.4.1.4555.1.1.20.1.5.1.1.3 | ScalaripduEnvEmdStatusHumidity | read-only | mandatory | EMD Humidity in 0.1%. |
| 1.3.6.1.4.1.4555.1.1.20.1.5.1.1.4 | ScalaripduEnvEmdStatusAlarm1 | read-only | mandatory | EMD Alarm-1 state. |
| 1.3.6.1.4.1.4555.1.1.20.1.5.1.1.5 | ScalaripduEnvEmdStatusAlarm2 | read-only | mandatory | EMD Alarm-2 state. |
| 1.3.6.1.4.1.4555.1.1.20.1.5.1.2 | NodeipduEnvEmdConfig | |||
| 1.3.6.1.4.1.4555.1.1.20.1.5.1.2.1 | ScalaripduEnvEmdConfigEmdPresence | read-write | mandatory | Configure the EMD presence by auto-detect or not exist (disabled). |
| 1.3.6.1.4.1.4555.1.1.20.1.5.1.2.2 | ScalaripduEnvEmdConfigEmdName | read-write | mandatory | The name of Emd. |
| 1.3.6.1.4.1.4555.1.1.20.1.5.1.2.3 | NodeipduEnvEmdConfigTemp | |||
| 1.3.6.1.4.1.4555.1.1.20.1.5.1.2.3.1 | ScalaripduEnvEmdConfigTempName | read-write | mandatory | The name of EMD Temperature sensor. |
| 1.3.6.1.4.1.4555.1.1.20.1.5.1.2.3.2 | ScalaripduEnvEmdConfigTempHighSetPoint | read-write | mandatory | EMD Temperature set point high, alarm will active when temperature over this value, in degree C. |
| 1.3.6.1.4.1.4555.1.1.20.1.5.1.2.3.3 | ScalaripduEnvEmdConfigTempHighStatus | read-write | mandatory | Enabled/disabled the high setpoint be applied or not |
| 1.3.6.1.4.1.4555.1.1.20.1.5.1.2.3.4 | ScalaripduEnvEmdConfigTempLowSetPoint | read-write | mandatory | EMD Temperature set point high, alarm will active when temperature under this value, in degree C. |
| 1.3.6.1.4.1.4555.1.1.20.1.5.1.2.3.5 | ScalaripduEnvEmdConfigTempLowStatus | read-write | mandatory | Enabled/disabled the low setpoint be applied or not |
| 1.3.6.1.4.1.4555.1.1.20.1.5.1.2.3.6 | ScalaripduEnvEmdConfigTempOffset | read-write | mandatory | Offset of temperature in degree C to adjust EMD temperature measurement. |
| 1.3.6.1.4.1.4555.1.1.20.1.5.1.2.4 | NodeipduEnvEmdConfigHumi | |||
| 1.3.6.1.4.1.4555.1.1.20.1.5.1.2.4.1 | ScalaripduEnvEmdConfigHumiName | read-write | mandatory | The name of EMD Humidity. |
| 1.3.6.1.4.1.4555.1.1.20.1.5.1.2.4.2 | ScalaripduEnvEmdConfigHumiHighSetPoint | read-write | mandatory | EMD humidity set point high, alarm will active when humidity over this value, in %. |
| 1.3.6.1.4.1.4555.1.1.20.1.5.1.2.4.3 | ScalaripduEnvEmdConfigHumiHighStatus | read-write | mandatory | Enabled/disabled the high setpoint be applied or not |
| 1.3.6.1.4.1.4555.1.1.20.1.5.1.2.4.4 | ScalaripduEnvEmdConfigHumiLowSetPoint | read-write | mandatory | EMD humidity set point low, alarm will active when humidity under this value, in %. |
| 1.3.6.1.4.1.4555.1.1.20.1.5.1.2.4.5 | ScalaripduEnvEmdConfigHumiLowStatus | read-write | mandatory | Enabled/disabled the high setpoint be applied or not |
| 1.3.6.1.4.1.4555.1.1.20.1.5.1.2.4.6 | ScalaripduEnvEmdConfigHumiOffset | read-write | mandatory | Emd Hum Offset; |
| 1.3.6.1.4.1.4555.1.1.20.1.5.1.2.5 | NodeipduEnvEmdConfigAlarm1 | |||
| 1.3.6.1.4.1.4555.1.1.20.1.5.1.2.5.1 | ScalaripduEnvEmdConfigAlarm1Name | read-write | mandatory | The name of EMD Alarm-1. |
| 1.3.6.1.4.1.4555.1.1.20.1.5.1.2.5.2 | ScalaripduEnvEmdConfigAlarm1Type | read-write | mandatory | EMD Alarm-1 type |
| 1.3.6.1.4.1.4555.1.1.20.1.5.1.2.6 | NodeipduEnvEmdConfigAlarm2 | |||
| 1.3.6.1.4.1.4555.1.1.20.1.5.1.2.6.1 | ScalaripduEnvEmdConfigAlarm2Name | read-write | mandatory | The name of EMD Alarm-2. |
| 1.3.6.1.4.1.4555.1.1.20.1.5.1.2.6.2 | ScalaripduEnvEmdConfigAlarm2Type | read-write | mandatory | EMD Alarm-2 type |
| 1.3.6.1.4.1.4555.1.1.20.2 | NodeipduTraps | |||
| 1.3.6.1.4.1.4555.1.1.20.2.1 | NodeipduInletVoltageTooHigh | CRITICAL: The input voltage over high threshold. | ||
| 1.3.6.1.4.1.4555.1.1.20.2.2 | NodeipduInletVoltageNotTooHigh | WARNING: The input voltage return from over high threshold. | ||
| 1.3.6.1.4.1.4555.1.1.20.2.3 | NodeipduInletVoltageTooLow | CRITICAL: The input voltage under low threshold. | ||
| 1.3.6.1.4.1.4555.1.1.20.2.4 | NodeipduInletVoltageNotTooLow | WARNING: The input voltage return from under low threshold. | ||
| 1.3.6.1.4.1.4555.1.1.20.2.5 | NodeipduInletCurrentTooHigh | CRITICAL: The input current over high threshold. | ||
| 1.3.6.1.4.1.4555.1.1.20.2.6 | NodeipduInletCurrentNotTooHigh | WARNING: The input current return from over high threshold. | ||
| 1.3.6.1.4.1.4555.1.1.20.2.7 | NodeipduInletFrequencyTooHigh | CRITICAL: The input frequency over high threshold. | ||
| 1.3.6.1.4.1.4555.1.1.20.2.8 | NodeipduInletFrequencyNotTooHigh | WARNING: The input frequency return from over high threshold. | ||
| 1.3.6.1.4.1.4555.1.1.20.2.9 | NodeipduInletFrequencyTooLow | CRITICAL: The input frequency under low threshold. | ||
| 1.3.6.1.4.1.4555.1.1.20.2.10 | NodeipduInletFrequencyNotTooLow | WARNING: The input frequency return from under low threshold. | ||
| 1.3.6.1.4.1.4555.1.1.20.2.11 | NodeipduInlet2VoltageTooHigh | CRITICAL: The input2 voltage over high threshold. | ||
| 1.3.6.1.4.1.4555.1.1.20.2.12 | NodeipduInlet2VoltageNotTooHigh | WARNING: The input2 voltage return from over high threshold. | ||
| 1.3.6.1.4.1.4555.1.1.20.2.13 | NodeipduInlet2VoltageTooLow | CRITICAL: The input2 voltage under low threshold. | ||
| 1.3.6.1.4.1.4555.1.1.20.2.14 | NodeipduInlet2VoltageNotTooLow | WARNING: The input2 voltage return from under low threshold. | ||
| 1.3.6.1.4.1.4555.1.1.20.2.15 | NodeipduInlet2CurrentTooHigh | CRITICAL: The input2 current over high threshold. | ||
| 1.3.6.1.4.1.4555.1.1.20.2.16 | NodeipduInlet2CurrentNotTooHigh | WARNING: The input2 current return from over high threshold. | ||
| 1.3.6.1.4.1.4555.1.1.20.2.17 | NodeipduInlet2FrequencyTooHigh | CRITICAL: The input2 frequency over high threshold. | ||
| 1.3.6.1.4.1.4555.1.1.20.2.18 | NodeipduInlet2FrequencyNotTooHigh | WARNING: The input2 frequency return from over high threshold. | ||
| 1.3.6.1.4.1.4555.1.1.20.2.19 | NodeipduInlet2FrequencyTooLow | CRITICAL: The input2 frequency under low threshold. | ||
| 1.3.6.1.4.1.4555.1.1.20.2.20 | NodeipduInlet2FrequencyNotTooLow | WARNING: The input2 frequency return from under low threshold. | ||
| 1.3.6.1.4.1.4555.1.1.20.2.21 | NodeipduOutletCurrentTooHigh | CRITICAL: The output current of outlet over high threshold. | ||
| 1.3.6.1.4.1.4555.1.1.20.2.22 | NodeipduOutletCurrentNotTooHigh | WARNING: The output current of outlet return from over high threshold. | ||
| 1.3.6.1.4.1.4555.1.1.20.2.23 | NodeipduOutletStateChanged | INFORMATION: The outlet state had changed from on to off, or from off to on. | ||
| 1.3.6.1.4.1.4555.1.1.20.2.24 | NodeipduEmdTemperatureNotHigh | INFORMATION: emd Temperature Not High. | ||
| 1.3.6.1.4.1.4555.1.1.20.2.25 | NodeipduEmdTemperatureTooHigh | WARNING: emd Temperature Too High. | ||
| 1.3.6.1.4.1.4555.1.1.20.2.26 | NodeipduEmdTemperatureNotLow | INFORMATION: emd Temperature Not Low. | ||
| 1.3.6.1.4.1.4555.1.1.20.2.27 | NodeipduEmdTemperatureTooLow | WARNING: emd Temperature Too Low. | ||
| 1.3.6.1.4.1.4555.1.1.20.2.28 | NodeipduEmdHumidityNotHigh | INFORMATION: emd Humidity Not High. | ||
| 1.3.6.1.4.1.4555.1.1.20.2.29 | NodeipduEmdHumidityTooHigh | WARNING: emd Humidity Too High. | ||
| 1.3.6.1.4.1.4555.1.1.20.2.30 | NodeipduEmdHumidityNotLow | INFORMATION: emd Humidity Not Low. | ||
| 1.3.6.1.4.1.4555.1.1.20.2.31 | NodeipduEmdHumidityTooLow | WARNING: emd Humidity Too Low. | ||
| 1.3.6.1.4.1.4555.1.1.20.2.32 | NodeipduEmdAlarm1Normal | INFORMATION: emd Alarm1 Normal. | ||
| 1.3.6.1.4.1.4555.1.1.20.2.33 | NodeipduEmdAlarm1Active | WARNING: emd Alarm1 Active. | ||
| 1.3.6.1.4.1.4555.1.1.20.2.34 | NodeipduEmdAlarm2Normal | INFORMATION: emd Alarm2 Normal. | ||
| 1.3.6.1.4.1.4555.1.1.20.2.35 | NodeipduEmdAlarm2Active | WARNING: emd Alarm2 Active. | ||
| 1.3.6.1.4.1.4555.1.1.20.2.36 | NodeipduSlave01Inlet01OverHigh | CRITICAL: The Slave01 input01 voltage over high threshold. | ||
| 1.3.6.1.4.1.4555.1.1.20.2.37 | NodeipduSlave01Inlet01NotOverHigh | CRITICAL: The Slave01 input01 voltage Not over high threshold. | ||
| 1.3.6.1.4.1.4555.1.1.20.2.38 | NodeipduSlave01Inlet02OverHigh | CRITICAL: The Slave01 input02 voltage over high threshold. | ||
| 1.3.6.1.4.1.4555.1.1.20.2.39 | NodeipduSlave01Inlet02NotOverHigh | CRITICAL: The Slave01 input02 voltage Not over high threshold. | ||
| 1.3.6.1.4.1.4555.1.1.20.2.40 | NodeipduSlave01Inlet01UnderLow | CRITICAL: The Slave01 input01 voltage under low threshold. | ||
| 1.3.6.1.4.1.4555.1.1.20.2.41 | NodeipduSlave01Inlet01NotUnderLow | CRITICAL: The Slave01 input01 voltage Not under low threshold. | ||
| 1.3.6.1.4.1.4555.1.1.20.2.42 | NodeipduSlave01Inlet02UnderLow | CRITICAL: The Slave01 input02 voltage under low threshold. | ||
| 1.3.6.1.4.1.4555.1.1.20.2.43 | NodeipduSlave01Inlet02NotUnderLow | CRITICAL: The Slave01 input02 voltage Not under low threshold. | ||
| 1.3.6.1.4.1.4555.1.1.20.2.44 | NodeipduSlave01Inlet01CurrentOverTh | CRITICAL: The Slave01 input01 current over high threshold. | ||
| 1.3.6.1.4.1.4555.1.1.20.2.45 | NodeipduSlave01Inlet01NotCurrentOverTh | CRITICAL: The Slave01 input01 current not over high threshold. | ||
| 1.3.6.1.4.1.4555.1.1.20.2.46 | NodeipduSlave01Inlet02CurrentOverTh | CRITICAL: The Slave01 input02 current over high threshold. | ||
| 1.3.6.1.4.1.4555.1.1.20.2.47 | NodeipduSlave01Inlet02NotCurrentOverTh | CRITICAL: The Slave01 input02 current not over high threshold. | ||
| 1.3.6.1.4.1.4555.1.1.20.2.48 | NodeipduSlave01EmdTemperatureNotHigh | INFORMATION: The Slave01 emd Temperature Not High. | ||
| 1.3.6.1.4.1.4555.1.1.20.2.49 | NodeipduSlave01EmdTemperatureTooHigh | WARNING: The Slave01 emd Temperature Too High. | ||
| 1.3.6.1.4.1.4555.1.1.20.2.50 | NodeipduSlave01EmdTemperatureNotLow | INFORMATION: The Slave01 emd Temperature Not Low. | ||
| 1.3.6.1.4.1.4555.1.1.20.2.51 | NodeipduSlave01EmdTemperatureTooLow | WARNING: The Slave01 emd Temperature Too Low. | ||
| 1.3.6.1.4.1.4555.1.1.20.2.52 | NodeipduSlave01EmdHumidityNotHigh | INFORMATION: The Slave01 emd Humidity Not High. | ||
| 1.3.6.1.4.1.4555.1.1.20.2.53 | NodeipduSlave01EmdHumidityTooHigh | WARNING: The Slave01 emd Humidity Too High. | ||
| 1.3.6.1.4.1.4555.1.1.20.2.54 | NodeipduSlave01EmdHumidityNotLow | INFORMATION: The Slave01 emd Humidity Not Low. | ||
| 1.3.6.1.4.1.4555.1.1.20.2.55 | NodeipduSlave01EmdHumidityTooLow | WARNING: The Slave01 emd Humidity Too Low. | ||
| 1.3.6.1.4.1.4555.1.1.20.2.56 | NodeipduSlave01EmdAlarm1Normal | INFORMATION: The Slave01 emd Alarm1 Normal. | ||
| 1.3.6.1.4.1.4555.1.1.20.2.57 | NodeipduSlave01EmdAlarm1Active | WARNING: The Slave01 emd Alarm1 Active. | ||
| 1.3.6.1.4.1.4555.1.1.20.2.58 | NodeipduSlave01EmdAlarm2Normal | INFORMATION: The Slave01 emd Alarm2 Normal. | ||
| 1.3.6.1.4.1.4555.1.1.20.2.59 | NodeipduSlave01EmdAlarm2Active | WARNING: The Slave01 emd Alarm2 Active. | ||
| 1.3.6.1.4.1.4555.1.1.20.2.60 | NodeipduSlave01OutletCurrentOverTh | WARNING: The Slave01 Outlet Current over threshold. | ||
| 1.3.6.1.4.1.4555.1.1.20.2.61 | NodeipduSlave02Inlet01OverHigh | CRITICAL: The Slave02 input01 voltage over high threshold. | ||
| 1.3.6.1.4.1.4555.1.1.20.2.62 | NodeipduSlave02Inlet01NotOverHigh | CRITICAL: The Slave02 input01 voltage Not over high threshold. | ||
| 1.3.6.1.4.1.4555.1.1.20.2.63 | NodeipduSlave02Inlet02OverHigh | CRITICAL: The Slave02 input02 voltage over high threshold. | ||
| 1.3.6.1.4.1.4555.1.1.20.2.64 | NodeipduSlave02Inlet02NotOverHigh | CRITICAL: The Slave02 input02 voltage Not over high threshold. | ||
| 1.3.6.1.4.1.4555.1.1.20.2.65 | NodeipduSlave02Inlet01UnderLow | CRITICAL: The Slave02 input01 voltage under low threshold. | ||
| 1.3.6.1.4.1.4555.1.1.20.2.66 | NodeipduSlave02Inlet01NotUnderLow | CRITICAL: The Slave02 input01 voltage Not under low threshold. | ||
| 1.3.6.1.4.1.4555.1.1.20.2.67 | NodeipduSlave02Inlet02UnderLow | CRITICAL: The Slave02 input02 voltage under low threshold. | ||
| 1.3.6.1.4.1.4555.1.1.20.2.68 | NodeipduSlave02Inlet02NotUnderLow | CRITICAL: The Slave02 input02 voltage Not under low threshold. | ||
| 1.3.6.1.4.1.4555.1.1.20.2.69 | NodeipduSlave02Inlet01CurrentOverTh | CRITICAL: The Slave02 input01 current over high threshold. | ||
| 1.3.6.1.4.1.4555.1.1.20.2.70 | NodeipduSlave02Inlet01NotCurrentOverTh | CRITICAL: The Slave02 input01 current not over high threshold. | ||
| 1.3.6.1.4.1.4555.1.1.20.2.71 | NodeipduSlave02Inlet02CurrentOverTh | CRITICAL: The Slave02 input02 current over high threshold. | ||
| 1.3.6.1.4.1.4555.1.1.20.2.72 | NodeipduSlave02Inlet02NotCurrentOverTh | CRITICAL: The Slave02 input02 current not over high threshold. | ||
| 1.3.6.1.4.1.4555.1.1.20.2.73 | NodeipduSlave02EmdTemperatureNotHigh | INFORMATION: The Slave02 emd Temperature Not High. | ||
| 1.3.6.1.4.1.4555.1.1.20.2.74 | NodeipduSlave02EmdTemperatureTooHigh | WARNING: The Slave02 emd Temperature Too High. | ||
| 1.3.6.1.4.1.4555.1.1.20.2.75 | NodeipduSlave02EmdTemperatureNotLow | INFORMATION: The Slave02 emd Temperature Not Low. | ||
| 1.3.6.1.4.1.4555.1.1.20.2.76 | NodeipduSlave02EmdTemperatureTooLow | WARNING: The Slave02 emd Temperature Too Low. | ||
| 1.3.6.1.4.1.4555.1.1.20.2.77 | NodeipduSlave02EmdHumidityNotHigh | INFORMATION: The Slave02 emd Humidity Not High. | ||
| 1.3.6.1.4.1.4555.1.1.20.2.78 | NodeipduSlave02EmdHumidityTooHigh | WARNING: The Slave02 emd Humidity Too High. | ||
| 1.3.6.1.4.1.4555.1.1.20.2.79 | NodeipduSlave02EmdHumidityNotLow | INFORMATION: The Slave02 emd Humidity Not Low. | ||
| 1.3.6.1.4.1.4555.1.1.20.2.80 | NodeipduSlave02EmdHumidityTooLow | WARNING: The Slave02 emd Humidity Too Low. | ||
| 1.3.6.1.4.1.4555.1.1.20.2.81 | NodeipduSlave02EmdAlarm1Normal | INFORMATION: The Slave02 emd Alarm1 Normal. | ||
| 1.3.6.1.4.1.4555.1.1.20.2.82 | NodeipduSlave02EmdAlarm1Active | WARNING: The Slave02 emd Alarm1 Active. | ||
| 1.3.6.1.4.1.4555.1.1.20.2.83 | NodeipduSlave02EmdAlarm2Normal | INFORMATION: The Slave02 emd Alarm2 Normal. | ||
| 1.3.6.1.4.1.4555.1.1.20.2.84 | NodeipduSlave02EmdAlarm2Active | WARNING: The Slave02 emd Alarm2 Active. | ||
| 1.3.6.1.4.1.4555.1.1.20.2.85 | NodeipduSlave02OutletCurrentOverTh | WARNING: The Slave02 Outlet Current over threshold. | ||
| 1.3.6.1.4.1.4555.1.1.20.2.86 | NodeipduSlave03Inlet01OverHigh | CRITICAL: The Slave03 input01 voltage over high threshold. | ||
| 1.3.6.1.4.1.4555.1.1.20.2.87 | NodeipduSlave03Inlet01NotOverHigh | CRITICAL: The Slave03 input01 voltage Not over high threshold. | ||
| 1.3.6.1.4.1.4555.1.1.20.2.88 | NodeipduSlave03Inlet02OverHigh | CRITICAL: The Slave03 input02 voltage over high threshold. | ||
| 1.3.6.1.4.1.4555.1.1.20.2.89 | NodeipduSlave03Inlet02NotOverHigh | CRITICAL: The Slave03 input02 voltage Not over high threshold. | ||
| 1.3.6.1.4.1.4555.1.1.20.2.90 | NodeipduSlave03Inlet01UnderLow | CRITICAL: The Slave03 input01 voltage under low threshold. | ||
| 1.3.6.1.4.1.4555.1.1.20.2.91 | NodeipduSlave03Inlet01NotUnderLow | CRITICAL: The Slave03 input01 voltage Not under low threshold. | ||
| 1.3.6.1.4.1.4555.1.1.20.2.92 | NodeipduSlave03Inlet02UnderLow | CRITICAL: The Slave03 input02 voltage under low threshold. | ||
| 1.3.6.1.4.1.4555.1.1.20.2.93 | NodeipduSlave03Inlet02NotUnderLow | CRITICAL: The Slave03 input02 voltage Not under low threshold. | ||
| 1.3.6.1.4.1.4555.1.1.20.2.94 | NodeipduSlave03Inlet01CurrentOverTh | CRITICAL: The Slave03 input01 current over high threshold. | ||
| 1.3.6.1.4.1.4555.1.1.20.2.95 | NodeipduSlave03Inlet01NotCurrentOverTh | CRITICAL: The Slave03 input01 current not over high threshold. | ||
| 1.3.6.1.4.1.4555.1.1.20.2.96 | NodeipduSlave03Inlet02CurrentOverTh | CRITICAL: The Slave03 input02 current over high threshold. | ||
| 1.3.6.1.4.1.4555.1.1.20.2.97 | NodeipduSlave03Inlet02NotCurrentOverTh | CRITICAL: The Slave03 input02 current not over high threshold. | ||
| 1.3.6.1.4.1.4555.1.1.20.2.98 | NodeipduSlave03EmdTemperatureNotHigh | INFORMATION: The Slave03 emd Temperature Not High. | ||
| 1.3.6.1.4.1.4555.1.1.20.2.99 | NodeipduSlave03EmdTemperatureTooHigh | WARNING: The Slave03 emd Temperature Too High. | ||
| 1.3.6.1.4.1.4555.1.1.20.2.100 | NodeipduSlave03EmdTemperatureNotLow | INFORMATION: The Slave03 emd Temperature Not Low. | ||
| 1.3.6.1.4.1.4555.1.1.20.2.101 | NodeipduSlave03EmdTemperatureTooLow | WARNING: The Slave03 emd Temperature Too Low. | ||
| 1.3.6.1.4.1.4555.1.1.20.2.102 | NodeipduSlave03EmdHumidityNotHigh | INFORMATION: The Slave03 emd Humidity Not High. | ||
| 1.3.6.1.4.1.4555.1.1.20.2.103 | NodeipduSlave03EmdHumidityTooHigh | WARNING: The Slave03 emd Humidity Too High. | ||
| 1.3.6.1.4.1.4555.1.1.20.2.104 | NodeipduSlave03EmdHumidityNotLow | INFORMATION: The Slave03 emd Humidity Not Low. | ||
| 1.3.6.1.4.1.4555.1.1.20.2.105 | NodeipduSlave03EmdHumidityTooLow | WARNING: The Slave03 emd Humidity Too Low. | ||
| 1.3.6.1.4.1.4555.1.1.20.2.106 | NodeipduSlave03EmdAlarm1Normal | INFORMATION: The Slave03 emd Alarm1 Normal. | ||
| 1.3.6.1.4.1.4555.1.1.20.2.107 | NodeipduSlave03EmdAlarm1Active | WARNING: The Slave03 emd Alarm1 Active. | ||
| 1.3.6.1.4.1.4555.1.1.20.2.108 | NodeipduSlave03EmdAlarm2Normal | INFORMATION: The Slave03 emd Alarm2 Normal. | ||
| 1.3.6.1.4.1.4555.1.1.20.2.109 | NodeipduSlave03EmdAlarm2Active | WARNING: The Slave03 emd Alarm2 Active. | ||
| 1.3.6.1.4.1.4555.1.1.20.2.110 | NodeipduSlave03OutletCurrentOverTh | WARNING: The Slave03 Outlet Current over threshold. | ||
| 1.3.6.1.4.1.4555.1.1.20.2.111 | NodeipduSlave04Inlet01OverHigh | CRITICAL: The Slave04 input01 voltage over high threshold. | ||
| 1.3.6.1.4.1.4555.1.1.20.2.112 | NodeipduSlave04Inlet01NotOverHigh | CRITICAL: The Slave04 input01 voltage Not over high threshold. | ||
| 1.3.6.1.4.1.4555.1.1.20.2.113 | NodeipduSlave04Inlet02OverHigh | CRITICAL: The Slave04 input02 voltage over high threshold. | ||
| 1.3.6.1.4.1.4555.1.1.20.2.114 | NodeipduSlave04Inlet02NotOverHigh | CRITICAL: The Slave04 input02 voltage Not over high threshold. | ||
| 1.3.6.1.4.1.4555.1.1.20.2.115 | NodeipduSlave04Inlet01UnderLow | CRITICAL: The Slave04 input01 voltage under low threshold. | ||
| 1.3.6.1.4.1.4555.1.1.20.2.116 | NodeipduSlave04Inlet01NotUnderLow | CRITICAL: The Slave04 input01 voltage Not under low threshold. | ||
| 1.3.6.1.4.1.4555.1.1.20.2.117 | NodeipduSlave04Inlet02UnderLow | CRITICAL: The Slave04 input02 voltage under low threshold. | ||
| 1.3.6.1.4.1.4555.1.1.20.2.118 | NodeipduSlave04Inlet02NotUnderLow | CRITICAL: The Slave04 input02 voltage Not under low threshold. | ||
| 1.3.6.1.4.1.4555.1.1.20.2.119 | NodeipduSlave04Inlet01CurrentOverTh | CRITICAL: The Slave04 input01 current over high threshold. | ||
| 1.3.6.1.4.1.4555.1.1.20.2.120 | NodeipduSlave04Inlet01NotCurrentOverTh | CRITICAL: The Slave04 input01 current not over high threshold. | ||
| 1.3.6.1.4.1.4555.1.1.20.2.121 | NodeipduSlave04Inlet02CurrentOverTh | CRITICAL: The Slave04 input02 current over high threshold. | ||
| 1.3.6.1.4.1.4555.1.1.20.2.122 | NodeipduSlave04Inlet02NotCurrentOverTh | CRITICAL: The Slave04 input02 current not over high threshold. | ||
| 1.3.6.1.4.1.4555.1.1.20.2.123 | NodeipduSlave04EmdTemperatureNotHigh | INFORMATION: The Slave04 emd Temperature Not High. | ||
| 1.3.6.1.4.1.4555.1.1.20.2.124 | NodeipduSlave04EmdTemperatureTooHigh | WARNING: The Slave04 emd Temperature Too High. | ||
| 1.3.6.1.4.1.4555.1.1.20.2.125 | NodeipduSlave04EmdTemperatureNotLow | INFORMATION: The Slave04 emd Temperature Not Low. | ||
| 1.3.6.1.4.1.4555.1.1.20.2.126 | NodeipduSlave04EmdTemperatureTooLow | WARNING: The Slave04 emd Temperature Too Low. | ||
| 1.3.6.1.4.1.4555.1.1.20.2.127 | NodeipduSlave04EmdHumidityNotHigh | INFORMATION: The Slave04 emd Humidity Not High. | ||
| 1.3.6.1.4.1.4555.1.1.20.2.128 | NodeipduSlave04EmdHumidityTooHigh | WARNING: The Slave04 emd Humidity Too High. | ||
| 1.3.6.1.4.1.4555.1.1.20.2.129 | NodeipduSlave04EmdHumidityNotLow | INFORMATION: The Slave04 emd Humidity Not Low. | ||
| 1.3.6.1.4.1.4555.1.1.20.2.130 | NodeipduSlave04EmdHumidityTooLow | WARNING: The Slave04 emd Humidity Too Low. | ||
| 1.3.6.1.4.1.4555.1.1.20.2.131 | NodeipduSlave04EmdAlarm1Normal | INFORMATION: The Slave04 emd Alarm1 Normal. | ||
| 1.3.6.1.4.1.4555.1.1.20.2.132 | NodeipduSlave04EmdAlarm1Active | WARNING: The Slave04 emd Alarm1 Active. | ||
| 1.3.6.1.4.1.4555.1.1.20.2.133 | NodeipduSlave04EmdAlarm2Normal | INFORMATION: The Slave04 emd Alarm2 Normal. | ||
| 1.3.6.1.4.1.4555.1.1.20.2.134 | NodeipduSlave04EmdAlarm2Active | WARNING: The Slave04 emd Alarm2 Active. | ||
| 1.3.6.1.4.1.4555.1.1.20.2.135 | NodeipduSlave04OutletCurrentOverTh | WARNING: The Slave04 Outlet Current over threshold. | ||
| 1.3.6.1.4.1.4555.1.1.20.2.136 | NodeipduSlave05Inlet01OverHigh | CRITICAL: The Slave05 input01 voltage over high threshold. | ||
| 1.3.6.1.4.1.4555.1.1.20.2.137 | NodeipduSlave05Inlet01NotOverHigh | CRITICAL: The Slave05 input01 voltage Not over high threshold. | ||
| 1.3.6.1.4.1.4555.1.1.20.2.138 | NodeipduSlave05Inlet02OverHigh | CRITICAL: The Slave05 input02 voltage over high threshold. | ||
| 1.3.6.1.4.1.4555.1.1.20.2.139 | NodeipduSlave05Inlet02NotOverHigh | CRITICAL: The Slave05 input02 voltage Not over high threshold. | ||
| 1.3.6.1.4.1.4555.1.1.20.2.140 | NodeipduSlave05Inlet01UnderLow | CRITICAL: The Slave05 input01 voltage under low threshold. | ||
| 1.3.6.1.4.1.4555.1.1.20.2.141 | NodeipduSlave05Inlet01NotUnderLow | CRITICAL: The Slave05 input01 voltage Not under low threshold. | ||
| 1.3.6.1.4.1.4555.1.1.20.2.142 | NodeipduSlave05Inlet02UnderLow | CRITICAL: The Slave05 input02 voltage under low threshold. | ||
| 1.3.6.1.4.1.4555.1.1.20.2.143 | NodeipduSlave05Inlet02NotUnderLow | CRITICAL: The Slave05 input02 voltage Not under low threshold. | ||
| 1.3.6.1.4.1.4555.1.1.20.2.144 | NodeipduSlave05Inlet01CurrentOverTh | CRITICAL: The Slave05 input01 current over high threshold. | ||
| 1.3.6.1.4.1.4555.1.1.20.2.145 | NodeipduSlave05Inlet01NotCurrentOverTh | CRITICAL: The Slave05 input01 current not over high threshold. | ||
| 1.3.6.1.4.1.4555.1.1.20.2.146 | NodeipduSlave05Inlet02CurrentOverTh | CRITICAL: The Slave05 input02 current over high threshold. | ||
| 1.3.6.1.4.1.4555.1.1.20.2.147 | NodeipduSlave05Inlet02NotCurrentOverTh | CRITICAL: The Slave05 input02 current not over high threshold. | ||
| 1.3.6.1.4.1.4555.1.1.20.2.148 | NodeipduSlave05EmdTemperatureNotHigh | INFORMATION: The Slave05 emd Temperature Not High. | ||
| 1.3.6.1.4.1.4555.1.1.20.2.149 | NodeipduSlave05EmdTemperatureTooHigh | WARNING: The Slave05 emd Temperature Too High. | ||
| 1.3.6.1.4.1.4555.1.1.20.2.150 | NodeipduSlave05EmdTemperatureNotLow | INFORMATION: The Slave05 emd Temperature Not Low. | ||
| 1.3.6.1.4.1.4555.1.1.20.2.151 | NodeipduSlave05EmdTemperatureTooLow | WARNING: The Slave05 emd Temperature Too Low. | ||
| 1.3.6.1.4.1.4555.1.1.20.2.152 | NodeipduSlave05EmdHumidityNotHigh | INFORMATION: The Slave05 emd Humidity Not High. | ||
| 1.3.6.1.4.1.4555.1.1.20.2.153 | NodeipduSlave05EmdHumidityTooHigh | WARNING: The Slave05 emd Humidity Too High. | ||
| 1.3.6.1.4.1.4555.1.1.20.2.154 | NodeipduSlave05EmdHumidityNotLow | INFORMATION: The Slave05 emd Humidity Not Low. | ||
| 1.3.6.1.4.1.4555.1.1.20.2.155 | NodeipduSlave05EmdHumidityTooLow | WARNING: The Slave05 emd Humidity Too Low. | ||
| 1.3.6.1.4.1.4555.1.1.20.2.156 | NodeipduSlave05EmdAlarm1Normal | INFORMATION: The Slave05 emd Alarm1 Normal. | ||
| 1.3.6.1.4.1.4555.1.1.20.2.157 | NodeipduSlave05EmdAlarm1Active | WARNING: The Slave05 emd Alarm1 Active. | ||
| 1.3.6.1.4.1.4555.1.1.20.2.158 | NodeipduSlave05EmdAlarm2Normal | INFORMATION: The Slave05 emd Alarm2 Normal. | ||
| 1.3.6.1.4.1.4555.1.1.20.2.159 | NodeipduSlave05EmdAlarm2Active | WARNING: The Slave05 emd Alarm2 Active. | ||
| 1.3.6.1.4.1.4555.1.1.20.2.160 | NodeipduSlave05OutletCurrentOverTh | WARNING: The Slave05 Outlet Current over threshold. |