SOCOMECUPS7-MIB
255 objects
No module-level DESCRIPTION found.
Imported Objects
| RFC-1212 | OBJECT-TYPE |
| RFC-1215 | TRAP-TYPE |
| RFC1155-SMI | enterprises |
| RFC1213-MIB | DisplayString |
| SNMPv2-TC | AutonomousType TestAndIncr TimeInterval TimeStamp |
| OID | Name | Access | Status | Description |
|---|---|---|---|---|
| 1.3.6.1.4.1.4555 | Nodesocomec | |||
| 1.3.6.1.4.1.4555.1 | Nodesoftware | |||
| 1.3.6.1.4.1.4555.1.1 | Nodenetwork | |||
| 1.3.6.1.4.1.4555.1.1.7 | Nodenetvision7 | |||
| 1.3.6.1.4.1.4555.1.1.7.1 | NodeupsObjects | |||
| 1.3.6.1.4.1.4555.1.1.7.1.1 | NodeupsIdent | |||
| 1.3.6.1.4.1.4555.1.1.7.1.1.1 | ScalarupsIdentModel | read-only | mandatory | The UPS Model designation. |
| 1.3.6.1.4.1.4555.1.1.7.1.1.2 | ScalarupsIdentSerialNumber | read-only | mandatory | The UPS Serial number. |
| 1.3.6.1.4.1.4555.1.1.7.1.1.3 | ScalarupsIdentUserRef | read-only | mandatory | The UPS Reference. |
| 1.3.6.1.4.1.4555.1.1.7.1.1.4 | ScalarupsIdentUserLocation | read-only | mandatory | The UPS Location. |
| 1.3.6.1.4.1.4555.1.1.7.1.1.5 | ScalarupsIdentAgentSoftwareVersion | read-only | mandatory | The UPS Net Vision software version. |
| 1.3.6.1.4.1.4555.1.1.7.1.1.6 | ScalarupsSystemName | read-only | mandatory | The UPS Net Vision system name. |
| 1.3.6.1.4.1.4555.1.1.7.1.1.7 | ScalarupsSystemContact | read-only | mandatory | The UPS Net Vision system contact. |
| 1.3.6.1.4.1.4555.1.1.7.1.1.8 | ScalarupsSystemLocation | read-only | mandatory | The UPS Net Vision system location. |
| 1.3.6.1.4.1.4555.1.1.7.1.2 | NodeupsBattery | |||
| 1.3.6.1.4.1.4555.1.1.7.1.2.1 | ScalarupsBatteryStatus | read-only | mandatory | The present battery status |
| 1.3.6.1.4.1.4555.1.1.7.1.2.2 | ScalarupsSecondsOnBattery | read-only | mandatory | If the unit is on battery power, the elapsed time since the UPS last switched to battery power, or the time since the network management subsystem was last res… |
| 1.3.6.1.4.1.4555.1.1.7.1.2.3 | ScalarupsEstimatedMinutesRemaining | read-only | mandatory | An estimate of the time to battery charge depletion under the present load conditions. Compute when UPS is on battery power |
| 1.3.6.1.4.1.4555.1.1.7.1.2.4 | ScalarupsEstimatedChargeRemaining | read-only | mandatory | An estimate of the battery charge remaining expressed as a percent of full charge. |
| 1.3.6.1.4.1.4555.1.1.7.1.2.5 | ScalarupsBatteryVoltage | read-only | mandatory | The magnitude of the present battery voltage in 0.1 Volt DC. |
| 1.3.6.1.4.1.4555.1.1.7.1.2.6 | ScalarupsBatteryTemperature | read-only | mandatory | The ambient temperature at or near the UPS Battery casing in 0.1 degree |
| 1.3.6.1.4.1.4555.1.1.7.1.2.7 | ScalarupsAmbientTemperature | read-only | mandatory | The ambient temperature inside the UPS in 0.1 degree |
| 1.3.6.1.4.1.4555.1.1.7.1.2.8 | ScalarupsBatteryCurrent | read-only | mandatory | The battry current in 0.1 Amp |
| 1.3.6.1.4.1.4555.1.1.7.1.2.9 | ScalarupsBatterySOC | read-only | mandatory | The battry SOC |
| 1.3.6.1.4.1.4555.1.1.7.1.3 | NodeupsInput | |||
| 1.3.6.1.4.1.4555.1.1.7.1.3.1 | ScalarupsInputNumLines | read-only | mandatory | The number of input lines utilized in this device. This variable indicates the number of rows in the input table. |
| 1.3.6.1.4.1.4555.1.1.7.1.3.2 | ScalarupsInputFrequency | read-only | mandatory | The current input frequency to the UPS system in 0.1 HZ. |
| 1.3.6.1.4.1.4555.1.1.7.1.3.3 | TableupsInputTable | not-accessible | mandatory | A list of input table entries. The number of entries is given by the value of upsInputNumLines. |
| 1.3.6.1.4.1.4555.1.1.7.1.3.3.1 | RowupsInputEntry | not-accessible | mandatory | An entry containing information applicable to a particular input line. |
| 1.3.6.1.4.1.4555.1.1.7.1.3.3.1.1 | ColumnupsInputLineIndex | read-only | mandatory | |
| 1.3.6.1.4.1.4555.1.1.7.1.3.3.1.2 | ColumnupsInputVoltage | read-only | mandatory | The input utility line voltage in 0.1 volts. |
| 1.3.6.1.4.1.4555.1.1.7.1.3.3.1.3 | ColumnupsInputCurrent | read-only | mandatory | The magnitude of the present input current in 0.1 A. |
| 1.3.6.1.4.1.4555.1.1.7.1.3.3.1.4 | ColumnupsInputVoltageMax | read-only | mandatory | The maximum utility line voltage in 0.1 VAC for last 1 minute. |
| 1.3.6.1.4.1.4555.1.1.7.1.3.3.1.5 | ColumnupsInputVoltageMin | read-only | mandatory | The minimum utility line voltage in 0.1 VAC for last 1 minute. |
| 1.3.6.1.4.1.4555.1.1.7.1.4 | NodeupsOutput | |||
| 1.3.6.1.4.1.4555.1.1.7.1.4.1 | ScalarupsOutputSource | read-only | mandatory | The present source of output power. |
| 1.3.6.1.4.1.4555.1.1.7.1.4.2 | ScalarupsOutputFrequency | read-only | mandatory | The current output frequency of the UPS system in 0.1 of HZ. |
| 1.3.6.1.4.1.4555.1.1.7.1.4.3 | ScalarupsOutputNumLines | read-only | mandatory | The number of output lines utilized in this device. This variable indicates the number of rows in the output table. |
| 1.3.6.1.4.1.4555.1.1.7.1.4.4 | TableupsOutputTable | not-accessible | mandatory | A list of output table entries. The number of entries is given by the value of upsOutputNumLines. |
| 1.3.6.1.4.1.4555.1.1.7.1.4.4.1 | RowupsOutputEntry | not-accessible | mandatory | An entry containing information applicable to a particular output line. |
| 1.3.6.1.4.1.4555.1.1.7.1.4.4.1.1 | ColumnupsOutputLineIndex | read-only | mandatory | The output line identifier. |
| 1.3.6.1.4.1.4555.1.1.7.1.4.4.1.2 | ColumnupsOutputVoltage | read-only | mandatory | The output voltage of the UPS system in 0.1 volts. |
| 1.3.6.1.4.1.4555.1.1.7.1.4.4.1.3 | ColumnupsOutputCurrent | read-only | mandatory | The output current of the UPS system in 0.1 Amps. |
| 1.3.6.1.4.1.4555.1.1.7.1.4.4.1.4 | ColumnupsOutputPercentLoad | read-only | mandatory | The percentage of the UPS power capacity presently being used on this output line |
| 1.3.6.1.4.1.4555.1.1.7.1.4.4.1.5 | ColumnupsOutputKva | read-only | mandatory | Output apparent power of the UPS in 0.1 kVA. |
| 1.3.6.1.4.1.4555.1.1.7.1.4.4.1.6 | ColumnupsOutputKw | read-only | mandatory | Output apparent power of the UPS in 0.1 kW. |
| 1.3.6.1.4.1.4555.1.1.7.1.4.5 | ScalarupsOutputGlobalkVA | read-only | mandatory | Output global apparent power of the UPS in 0.1 kVA. |
| 1.3.6.1.4.1.4555.1.1.7.1.4.6 | ScalarupsOutputGlobalkW | read-only | mandatory | Output global apparent power of the UPS in 0.1 kW. |
| 1.3.6.1.4.1.4555.1.1.7.1.4.7 | ScalarupsOutputLoadRate | read-only | mandatory | Output global Load Rate. |
| 1.3.6.1.4.1.4555.1.1.7.1.5 | NodeupsBypass | |||
| 1.3.6.1.4.1.4555.1.1.7.1.5.1 | ScalarupsBypassFrequency | read-only | mandatory | The present bypass frequency in 0.1 Hz. |
| 1.3.6.1.4.1.4555.1.1.7.1.5.2 | ScalarupsBypassNumLines | read-only | mandatory | The number of bypass lines utilized in this device. This entry indicates the number of rows in the bypass table. |
| 1.3.6.1.4.1.4555.1.1.7.1.5.3 | TableupsBypassTable | not-accessible | mandatory | A list of bypass table entries. The number of entries is given by the value of upsBypassNumLines. |
| 1.3.6.1.4.1.4555.1.1.7.1.5.3.1 | RowupsBypassEntry | not-accessible | mandatory | An entry containing information applicable to a particular bypass input. |
| 1.3.6.1.4.1.4555.1.1.7.1.5.3.1.1 | ColumnupsBypassLineIndex | read-only | mandatory | The bypass line identifier. |
| 1.3.6.1.4.1.4555.1.1.7.1.5.3.1.2 | ColumnupsBypassVoltage | read-only | mandatory | The present bypass voltage of the UPS system in 0.1 volts. |
| 1.3.6.1.4.1.4555.1.1.7.1.5.3.1.3 | ColumnupsBypassCurrent | read-only | mandatory | The present bypass current of the UPS system in 0.1 Amps. |
| 1.3.6.1.4.1.4555.1.1.7.1.6 | NodeupsAlarm | |||
| 1.3.6.1.4.1.4555.1.1.7.1.6.1 | ScalarupsAlarmsPresent | read-only | mandatory | The present number of active alarm conditions. |
| 1.3.6.1.4.1.4555.1.1.7.1.6.2 | TableupsAlarmTable | not-accessible | mandatory | A list of alarm table entries. The table contains zero, one, or many rows at any moment, depending upon the number of alarm conditions in effect. The table is … |
| 1.3.6.1.4.1.4555.1.1.7.1.6.2.1 | RowupsAlarmEntry | not-accessible | mandatory | An entry containing information applicable to a particular alarm. |
| 1.3.6.1.4.1.4555.1.1.7.1.6.2.1.1 | ColumnupsAlarmId | read-only | mandatory | A unique identifier for an alarm condition. This value must remain constant. |
| 1.3.6.1.4.1.4555.1.1.7.1.6.2.1.2 | ColumnupsAlarmDescr | read-only | mandatory | A reference to an alarm description object. The object referenced should not be accessible, but rather be used to provide a unique description of the alarm con… |
| 1.3.6.1.4.1.4555.1.1.7.1.6.2.1.3 | ColumnupsAlarmTime | read-only | mandatory | The value of sysUpTime when the alarm condition was detected. If the alarm condition was detected at the time of agent startup and presumably existed before ag… |
| 1.3.6.1.4.1.4555.1.1.7.1.6.2.1.4 | ColumnupsAlarmExtDes | read-only | mandatory | Extra description. |
| 1.3.6.1.4.1.4555.1.1.7.1.6.3 | NodeupsWellKnownAlarms | |||
| 1.3.6.1.4.1.4555.1.1.7.1.6.3.1 | ScalarupsAlarmImminentStop | read-only | mandatory | UPS in imminent stop. Load will switch off. (A000) |
| 1.3.6.1.4.1.4555.1.1.7.1.6.3.2 | ScalarupsAlarmOverload | read-only | mandatory | The output load exceeds the UPS output capacity. (A001) |
| 1.3.6.1.4.1.4555.1.1.7.1.6.3.3 | ScalarupsAlarmTemperature | read-only | mandatory | UPS temperature is out of tolerance. (A002) |
| 1.3.6.1.4.1.4555.1.1.7.1.6.3.4 | ScalarupsAlarmTransferLock | read-only | mandatory | Automatic and manual transfer are locked. (A003) |
| 1.3.6.1.4.1.4555.1.1.7.1.6.3.5 | ScalarupsAlarmAutoTransferImpossible | read-only | mandatory | Automatic transfer is disabled. Inverter and bypass sources are not synchronized (A004) |
| 1.3.6.1.4.1.4555.1.1.7.1.6.3.6 | ScalarupsAlarmInsufficientResources | read-only | mandatory | Insufficient resources alarm. The load cannot by supplied by alternate source (A005) |
| 1.3.6.1.4.1.4555.1.1.7.1.6.3.7 | ScalarupsAlarmRedundancyLost | read-only | mandatory | Redundancy lost alarm. (A006) |
| 1.3.6.1.4.1.4555.1.1.7.1.6.3.8 | ScalarupsAlarmOutputShortCircuit | read-only | mandatory | An output short-circuit has been detected by UPS. (A007) |
| 1.3.6.1.4.1.4555.1.1.7.1.6.3.9 | ScalarupsAlarmMaintenance | read-only | mandatory | The UPS requests a maintenance service check. (A012) |
| 1.3.6.1.4.1.4555.1.1.7.1.6.3.10 | ScalarupsAlarmRemoteService | read-only | mandatory | The UPS requests a remote service action. (A013) |
| 1.3.6.1.4.1.4555.1.1.7.1.6.3.11 | ScalarupsAlarmGeneralFault | read-only | mandatory | A general fault in the UPS has been detected. One of UPS alarm is present. (A015) |
| 1.3.6.1.4.1.4555.1.1.7.1.6.3.12 | ScalarupsAlarmBatteryCircuitOpen | read-only | mandatory | Battery circuit open. Battery breaker or fuse open. (A016) |
| 1.3.6.1.4.1.4555.1.1.7.1.6.3.13 | ScalarupsAlarmBatteryDischarged | read-only | mandatory | The UPS will be unable to sustain the present load when and if the utility power is lost. The Battery is discharched. (A017) |
| 1.3.6.1.4.1.4555.1.1.7.1.6.3.14 | ScalarupsAlarmLowBattery | read-only | mandatory | The remaining battery run-time is less than or equal to battery low threshold. (A018) |
| 1.3.6.1.4.1.4555.1.1.7.1.6.3.15 | ScalarupsAlarmOnBattery | read-only | mandatory | The UPS is drawing power from the batteries. (A019) |
| 1.3.6.1.4.1.4555.1.1.7.1.6.3.16 | ScalarupsAlarmBatteryTemperature | read-only | mandatory | Battery Temperature Alarm. (A020) |
| 1.3.6.1.4.1.4555.1.1.7.1.6.3.17 | ScalarupsAlarmBatteryRoom | read-only | mandatory | An external alarm has been detected in the Battery room. This alarm depends on external sensor: gaz, temperature, humidity or dry-contact. (A021) |
| 1.3.6.1.4.1.4555.1.1.7.1.6.3.18 | ScalarupsAlarmBatteryTest | read-only | mandatory | The battery has been detected as weak during the test. (A022) |
| 1.3.6.1.4.1.4555.1.1.7.1.6.3.19 | ScalarupsAlarmBatteryFault | read-only | mandatory | One or more batteries have been determined to require replacement. (A027) |
| 1.3.6.1.4.1.4555.1.1.7.1.6.3.20 | ScalarupsAlarmRectifierFault | read-only | mandatory | Rectifier Critical alarm. (A032) |
| 1.3.6.1.4.1.4555.1.1.7.1.6.3.21 | ScalarupsAlarmRectifierAlarm | read-only | mandatory | Rectifier Preventive alarm. (A033) |
| 1.3.6.1.4.1.4555.1.1.7.1.6.3.22 | ScalarupsAlarmRecInputBad | read-only | mandatory | rectifier Input power supply is out of tolerance or absent. (A035) |
| 1.3.6.1.4.1.4555.1.1.7.1.6.3.23 | ScalarupsAlarmGenSetGeneral | read-only | mandatory | Gen-set general alarm. coming from external dry-contact. (A036) |
| 1.3.6.1.4.1.4555.1.1.7.1.6.3.24 | ScalarupsAlarmBatteryChargerFault | read-only | mandatory | Battery charger Critical Alarm. (A037) |
| 1.3.6.1.4.1.4555.1.1.7.1.6.3.25 | ScalarupsAlarmBatteryChargerAlarm | read-only | mandatory | Battery charger Preventive Alarm. (A038) |
| 1.3.6.1.4.1.4555.1.1.7.1.6.3.26 | ScalarupsAlarmInverterFault | read-only | mandatory | Inverter Critical alarm. (A040) |
| 1.3.6.1.4.1.4555.1.1.7.1.6.3.27 | ScalarupsAlarmInverterAlarm | read-only | mandatory | Inverter preventive alarm. (A041) |
| 1.3.6.1.4.1.4555.1.1.7.1.6.3.28 | ScalarupsAlarmBypassFault | read-only | mandatory | Inverter Critical alarm. (A048) |
| 1.3.6.1.4.1.4555.1.1.7.1.6.3.29 | ScalarupsAlarmBypassAlarm | read-only | mandatory | Inverter preventive alarm. (A049) |
| 1.3.6.1.4.1.4555.1.1.7.1.6.3.30 | ScalarupsAlarmBypInputBad | read-only | mandatory | Bypass Input power supply is out of tolerance or absent. (A050) |
| 1.3.6.1.4.1.4555.1.1.7.1.6.3.31 | ScalarupsAlarmPhaseRotationFault | read-only | mandatory | Phase rotation fault. (A051) |
| 1.3.6.1.4.1.4555.1.1.7.1.6.3.32 | ScalarupsAlarmFansFailure | read-only | mandatory | Fans failure. (A054) |
| 1.3.6.1.4.1.4555.1.1.7.1.6.3.33 | ScalarupsAlarmMaintenanceBypass | read-only | mandatory | Maintenance bypass alarm. Output breaker and manual bypass breaker closed together. (A056) |
| 1.3.6.1.4.1.4555.1.1.7.1.6.3.34 | ScalarupsAlarmUPSPowerOffActive | read-only | mandatory | UPS power off has been activated by external device. (A059) |
| 1.3.6.1.4.1.4555.1.1.7.1.6.3.35 | ScalarupsAlarmWrongConfiguration | read-only | mandatory | Configuration data map corrupted, or wrong configuration. (A060) |
| 1.3.6.1.4.1.4555.1.1.7.1.6.3.36 | ScalarupsAlarmInternalFailure | read-only | mandatory | Internal failure, or internal communication failure. (A061) |
| 1.3.6.1.4.1.4555.1.1.7.1.6.3.37 | ScalarupsAlarmOptionalBoards | read-only | mandatory | Optional boards alarm. Board not present or wrong configuration (A062) |
| 1.3.6.1.4.1.4555.1.1.7.1.6.3.38 | ScalarupsAlarmExternalAlarm1 | read-only | mandatory | External Alarm 1. Coming from ADC Card: Input set as alarm (A064) |
| 1.3.6.1.4.1.4555.1.1.7.1.6.3.39 | ScalarupsAlarmExternalAlarm2 | read-only | mandatory | External Alarm 2. Coming from ADC Card: Input set as alarm (A065) |
| 1.3.6.1.4.1.4555.1.1.7.1.6.3.40 | ScalarupsAlarmExternalAlarm3 | read-only | mandatory | External Alarm 3. Coming from ADC Card: Input set as alarm (A066) |
| 1.3.6.1.4.1.4555.1.1.7.1.6.3.41 | ScalarupsAlarmExternalAlarm4 | read-only | mandatory | External Alarm 4. Coming from ADC Card: Input set as alarm (A067) |
| 1.3.6.1.4.1.4555.1.1.7.1.6.3.42 | ScalarupsAlarmModule1Alarm | read-only | mandatory | Unit or Module 1 in parallel general alarm. |
| 1.3.6.1.4.1.4555.1.1.7.1.6.3.43 | ScalarupsAlarmModule2Alarm | read-only | mandatory | Unit or Module 2 in parallel general alarm. |
| 1.3.6.1.4.1.4555.1.1.7.1.6.3.44 | ScalarupsAlarmModule3Alarm | read-only | mandatory | Unit or Module 3 in parallel general alarm. |
| 1.3.6.1.4.1.4555.1.1.7.1.6.3.45 | ScalarupsAlarmModule4Alarm | read-only | mandatory | Unit or Module 4 in parallel general alarm. |
| 1.3.6.1.4.1.4555.1.1.7.1.6.3.46 | ScalarupsAlarmModule5Alarm | read-only | mandatory | Unit or Module 5 in parallel general alarm. |
| 1.3.6.1.4.1.4555.1.1.7.1.6.3.47 | ScalarupsAlarmModule6Alarm | read-only | mandatory | Unit or Module 6 in parallel general alarm. |
| 1.3.6.1.4.1.4555.1.1.7.1.6.3.48 | ScalarupsAlarmModule7Alarm | read-only | mandatory | Unit or Module 7 in parallel general alarm. |
| 1.3.6.1.4.1.4555.1.1.7.1.6.3.49 | ScalarupsAlarmModule8Alarm | read-only | mandatory | Unit or Module 8 in parallel general alarm. |
| 1.3.6.1.4.1.4555.1.1.7.1.6.3.50 | ScalarupsAlarmModule9Alarm | read-only | mandatory | Unit or Module 9 in parallel general alarm. |
| 1.3.6.1.4.1.4555.1.1.7.1.6.3.51 | ScalarupsAlarmModule10Alarm | read-only | mandatory | Unit or Module 10 in parallel general alarm. |
| 1.3.6.1.4.1.4555.1.1.7.1.6.3.52 | ScalarupsAlarmModule11Alarm | read-only | mandatory | Unit or Module 11 in parallel general alarm. |
| 1.3.6.1.4.1.4555.1.1.7.1.6.3.53 | ScalarupsAlarmModule12Alarm | read-only | mandatory | Unit or Module 12 in parallel general alarm. |
| 1.3.6.1.4.1.4555.1.1.7.1.6.3.54 | ScalarupsAlarmAutoTestRunning | read-only | mandatory | The UPS has launched the auto-test. (S030) |
| 1.3.6.1.4.1.4555.1.1.7.1.6.3.55 | ScalarupsAlarmOnBypass | read-only | mandatory | Load supplied by automatic bypass. Load not protected. |
| 1.3.6.1.4.1.4555.1.1.7.1.6.3.56 | ScalarupsAlarmUpsOutputOff | read-only | mandatory | The output of the UPS is in the off state. Load OFF or UPS on standby mode. |
| 1.3.6.1.4.1.4555.1.1.7.1.6.3.57 | ScalarupsAlarmUpsSystemOff | read-only | mandatory | The UPS system is in the off state. Rectifier and Inverter are off. |
| 1.3.6.1.4.1.4555.1.1.7.1.6.3.58 | ScalarupsAlarmCommunicationLost | read-only | mandatory | The communication with UPS has been lost. |
| 1.3.6.1.4.1.4555.1.1.7.1.6.3.59 | ScalarupsAlarmShutdownPending | read-only | mandatory | The condition to shutdown servers has been detected. The shutdown delay in underway. |
| 1.3.6.1.4.1.4555.1.1.7.1.6.3.60 | ScalarupsAlarmShutdownRequestt | read-only | mandatory | The shutdown command has been sent to servers agent. |
| 1.3.6.1.4.1.4555.1.1.7.1.6.3.61 | ScalarupsAlarmShutdownImminent | read-only | mandatory | The UPS will turn OFF, according the standby schedule settings. |
| 1.3.6.1.4.1.4555.1.1.7.1.6.3.62 | ScalarupsAlarmAwaitingPower | read-only | mandatory | The UPS output is in standby, and the UPS is awaiting the return of input power. |
| 1.3.6.1.4.1.4555.1.1.7.1.7 | NodeupsControl | |||
| 1.3.6.1.4.1.4555.1.1.7.1.7.1 | ScalarupsControlStatusControl | read-write | mandatory | This object Control UPS status |
| 1.3.6.1.4.1.4555.1.1.7.1.7.2 | ScalarupsShutdownDelay | read-write | mandatory | This object set the delay time (in seconds) to turn UPS off after Net Vision broadcast shutdown request to connected clients |
| 1.3.6.1.4.1.4555.1.1.7.1.7.3 | ScalarupsTurnOffAfterShutdown | read-write | mandatory | This object enable/disable UPS turn off function after shutdown process complete |
| 1.3.6.1.4.1.4555.1.1.7.1.7.4 | TableupsControlShutdownParamTable | not-accessible | mandatory | Table which describes the parameters for shutdown process when shutdown event occurs |
| 1.3.6.1.4.1.4555.1.1.7.1.7.4.1 | RowshutdownParamEntry | not-accessible | mandatory | |
| 1.3.6.1.4.1.4555.1.1.7.1.7.4.1.1 | ColumnupsControlEventIndex | read-only | mandatory | The shutdown event identification |
| 1.3.6.1.4.1.4555.1.1.7.1.7.4.1.2 | ColumnupsControlEventStatus | read-write | mandatory | Status of the corresponding shutdown Event. When set to disable(), shutdown process will not start when corresponding event occurred. |
| 1.3.6.1.4.1.4555.1.1.7.1.7.4.1.3 | ColumnupsControlDelay | read-write | mandatory | The Delay after the occurrence of the corresponding shutdown event that Net Vision should issue shutdown request to connected clients. For WeeklyScheduledShutd… |
| 1.3.6.1.4.1.4555.1.1.7.1.7.4.1.4 | ColumnupsControlFirstWarning | read-write | mandatory | The delay after the occurrence of the corresponding shutdown event that the Net Vision will start sending the warning message to the connected clients. The val… |
| 1.3.6.1.4.1.4555.1.1.7.1.7.4.1.5 | ColumnupsControlWarningInterval | read-write | mandatory | The frequency of sending warning messages to the connected clients when the corresponding shutdown event occurs. The value is in units of seconds. |
| 1.3.6.1.4.1.4555.1.1.7.1.7.5 | TableupsControlWeeklyScheduleTable | not-accessible | mandatory | The table to schedule shutting down the ups by weekly. |
| 1.3.6.1.4.1.4555.1.1.7.1.7.5.1 | RowupsControlWeeklyScheduleEntry | not-accessible | mandatory | The entries for each day. |
| 1.3.6.1.4.1.4555.1.1.7.1.7.5.1.1 | ColumnupsControlWeeklyIndex | read-only | mandatory | The index of scheduled events. |
| 1.3.6.1.4.1.4555.1.1.7.1.7.5.1.2 | ColumnupsControlWeeklyShutdownDay | read-write | mandatory | The weekday on which the UPS should shut down. |
| 1.3.6.1.4.1.4555.1.1.7.1.7.5.1.3 | ColumnupsControlWeeklyShutdownTime | read-write | mandatory | The time that the process of shutting down the UPS will be initiated in hh:mm format. |
| 1.3.6.1.4.1.4555.1.1.7.1.7.5.1.4 | ColumnupsControlWeeklyRestartDay | read-write | mandatory | The weekday on which the UPS should restart |
| 1.3.6.1.4.1.4555.1.1.7.1.7.5.1.5 | ColumnupsControlWeeklyRestartTime | read-write | mandatory | The time the UPS will restart in hh:mm format. |
| 1.3.6.1.4.1.4555.1.1.7.1.7.6 | TableupsControlSpecialScheduleTable | not-accessible | mandatory | The table to schedule shutting down the ups. |
| 1.3.6.1.4.1.4555.1.1.7.1.7.6.1 | RowupsControlSpecialScheduleEntry | not-accessible | mandatory | The entries for each day. |
| 1.3.6.1.4.1.4555.1.1.7.1.7.6.1.1 | ColumnupsControlSpecialIndex | read-only | mandatory | The index of scheduled events. |
| 1.3.6.1.4.1.4555.1.1.7.1.7.6.1.2 | ColumnupsControlSpecialShutdownDay | read-write | mandatory | The date on which the UPS should shut down in dd/mm/yyyy format. |
| 1.3.6.1.4.1.4555.1.1.7.1.7.6.1.3 | ColumnupsControlSpecialShutdownTime | read-write | mandatory | The time that the process of shutting down the UPS will be initiated in hh:mm format |
| 1.3.6.1.4.1.4555.1.1.7.1.7.6.1.4 | ColumnupsControlSpecialRestartDay | read-write | mandatory | The date on which the UPS should restart in dd/mm/yyyy format |
| 1.3.6.1.4.1.4555.1.1.7.1.7.6.1.5 | ColumnupsControlSpecialRestartTime | read-write | mandatory | The time the UPS will restart in hh:mm format. |
| 1.3.6.1.4.1.4555.1.1.7.1.7.7 | TableupsControlEcoModeScheduleTable | not-accessible | mandatory | The table to schedule enable/disable ups eco/mode by weekly. |
| 1.3.6.1.4.1.4555.1.1.7.1.7.7.1 | RowupsControlEcoModeScheduleEntry | not-accessible | mandatory | The entries for each day. |
| 1.3.6.1.4.1.4555.1.1.7.1.7.7.1.1 | ColumnupsControlEcoModeIndex | read-only | mandatory | The index of scheduled events. |
| 1.3.6.1.4.1.4555.1.1.7.1.7.7.1.2 | ColumnupsControlEcoModeStartDay | read-write | mandatory | The weekday on which the UPS Eco/Mode should enable. |
| 1.3.6.1.4.1.4555.1.1.7.1.7.7.1.3 | ColumnupsControlEcoModeStartTime | read-write | mandatory | The time that the UPS Eco/Mode will be enabled, in hh:mm format. |
| 1.3.6.1.4.1.4555.1.1.7.1.7.7.1.4 | ColumnupsControlEcoModeEndDay | read-write | mandatory | The weekday on which the UPS Eco/Mode should disable |
| 1.3.6.1.4.1.4555.1.1.7.1.7.7.1.5 | ColumnupsControlEcoModeEndTime | read-write | mandatory | The time the UPS Eco/Mode will disabled, in hh:mm format. |
| 1.3.6.1.4.1.4555.1.1.7.1.8 | NodeupsConfig | |||
| 1.3.6.1.4.1.4555.1.1.7.1.8.1 | ScalarupsConfigNomKva | read-only | mandatory | UPS Nominal in 0.1 kVA |
| 1.3.6.1.4.1.4555.1.1.7.1.8.2 | ScalarupsConfigNbrUnit | read-only | mandatory | Number of Units installed in the system |
| 1.3.6.1.4.1.4555.1.1.7.1.8.3 | ScalarupsConfigUnitKva | read-only | mandatory | UNIT Nominal kVA |
| 1.3.6.1.4.1.4555.1.1.7.1.8.4 | ScalarupsConfigRemoteCtrl | read-only | mandatory | Set to 1 if remote controls are enabled by UPS |
| 1.3.6.1.4.1.4555.1.1.7.1.8.5 | TableupsDevicesTable | not-accessible | mandatory | The devices powered by UPS and registered to NET VISION |
| 1.3.6.1.4.1.4555.1.1.7.1.8.5.1 | RowupsDevicesEntry | not-accessible | mandatory | The devices protected by NET VISION |
| 1.3.6.1.4.1.4555.1.1.7.1.8.5.1.1 | ColumnindexOfDevice | read-only | mandatory | The index of the device that is powered from UPS. |
| 1.3.6.1.4.1.4555.1.1.7.1.8.5.1.2 | ColumnaddrOfDevice | read-only | mandatory | The ip address of the device. |
| 1.3.6.1.4.1.4555.1.1.7.1.8.5.1.3 | ColumnnameOfDevice | read-only | mandatory | The name/description of the device powered from UPS. |
| 1.3.6.1.4.1.4555.1.1.7.1.8.5.1.4 | ColumntimeOfConnection | read-only | mandatory | The device registered to NET VISION |
| 1.3.6.1.4.1.4555.1.1.7.1.8.5.1.5 | ColumnstatusOfConnection | read-only | mandatory | The device status connection |
| 1.3.6.1.4.1.4555.1.1.7.1.8.5.1.6 | ColumnseverityOfConnection | read-only | mandatory | The device severity |
| 1.3.6.1.4.1.4555.1.1.7.1.9 | NodeupsAgent | |||
| 1.3.6.1.4.1.4555.1.1.7.1.9.1 | ScalarupsAgentIpaddress | read-write | mandatory | The ip address that NMS can identify the managed device |
| 1.3.6.1.4.1.4555.1.1.7.1.9.2 | ScalarupsAgentGateway | read-write | mandatory | The default gateway that allow device managed through routers |
| 1.3.6.1.4.1.4555.1.1.7.1.9.3 | ScalarupsAgentSubnetMask | read-write | mandatory | Internet address subnet mask |
| 1.3.6.1.4.1.4555.1.1.7.1.9.4 | ScalarupsAgentDate | read-write | mandatory | The date in agent, format is (dd/mm/yyyy) |
| 1.3.6.1.4.1.4555.1.1.7.1.9.5 | ScalarupsAgentTime | read-write | mandatory | The time in agent, format is (hh:mm:ss) |
| 1.3.6.1.4.1.4555.1.1.7.1.9.6 | ScalarupsAgentNtpTimeServer | read-write | mandatory | |
| 1.3.6.1.4.1.4555.1.1.7.1.9.7 | ScalarupsAgentNtpTimeZone | read-write | mandatory | |
| 1.3.6.1.4.1.4555.1.1.7.1.9.8 | ScalarupsAgentHistoryLogFrequency | read-write | mandatory | The frequency of the updation of the history log. The value is in seconds |
| 1.3.6.1.4.1.4555.1.1.7.1.9.9 | ScalarupsAgentExtHistoryLogFrequency | read-write | mandatory | The ups parameters are sampled at the rate governed by the mconfigHistroyLogFrequency. These sampled values are further conslidated over period of time which i… |
| 1.3.6.1.4.1.4555.1.1.7.1.9.10 | ScalarupsAgentPollRate | read-write | mandatory | The frequency that proxy agent polls the connected UPS in JBUS protocol. (unit : second) |
| 1.3.6.1.4.1.4555.1.1.7.1.9.11 | ScalarupsAgentBaudRate | read-only | mandatory | The serial port communication speed. 2400,9600,19200,57600 allowed |
| 1.3.6.1.4.1.4555.1.1.7.1.9.12 | ScalarupsAgentDhcpStatue | read-write | mandatory | Enable or disable DHCP/BootP capability |
| 1.3.6.1.4.1.4555.1.1.7.1.9.13 | ScalarupsAgentTelnetStatus | read-write | mandatory | Enable or disable telnet access |
| 1.3.6.1.4.1.4555.1.1.7.1.9.14 | ScalarupsAgentTftpStatus | read-write | mandatory | Enable or disable network upgrade capability |
| 1.3.6.1.4.1.4555.1.1.7.1.9.15 | ScalarupsAgentResetToDefault | read-write | mandatory | Reset all parameters of Net Vision to default value |
| 1.3.6.1.4.1.4555.1.1.7.1.9.16 | ScalarupsAgentRestart | read-write | mandatory | Restart Net Vision |
| 1.3.6.1.4.1.4555.1.1.7.1.9.17 | ScalarupsAgentClearAgentLog | read-write | mandatory | Clear agent log data |
| 1.3.6.1.4.1.4555.1.1.7.1.9.18 | ScalarupsAgentClearEventLog | read-write | mandatory | Clear event log data |
| 1.3.6.1.4.1.4555.1.1.7.1.9.19 | ScalarupsAgentClearExtHistoryLog | read-write | mandatory | Clear extented history log data |
| 1.3.6.1.4.1.4555.1.1.7.1.9.20 | ScalarupsAgentClearHistoryLog | read-write | mandatory | Clear history log data |
| 1.3.6.1.4.1.4555.1.1.7.1.9.21 | TableupsAgentTrapsReceiversTable | not-accessible | mandatory | A list of managers to send traps to. The number of entries is given by the value of upsAgentNumTrapReceivers |
| 1.3.6.1.4.1.4555.1.1.7.1.9.21.1 | RowupsAgentTrapsReceiversEntry | not-accessible | mandatory | The managers to send traps to. |
| 1.3.6.1.4.1.4555.1.1.7.1.9.21.1.1 | ColumntrapsIndex | read-only | mandatory | The index to a trap receiver entry. |
| 1.3.6.1.4.1.4555.1.1.7.1.9.21.1.2 | ColumntrapsReceiverAddr | read-write | mandatory | The IP address of the manager to send a trap to. |
| 1.3.6.1.4.1.4555.1.1.7.1.9.21.1.3 | ColumnreceiverCommunityString | read-write | mandatory | The community name to use in the trap when sent to the manager. |
| 1.3.6.1.4.1.4555.1.1.7.1.9.21.1.4 | ColumnreceiverNmstype | read-write | mandatory | The trap group that NMS desired. |
| 1.3.6.1.4.1.4555.1.1.7.1.9.22 | TableupsAgentFirewallControlTable | not-accessible | mandatory | A list of managers which can access Net Vision with private community string. |
| 1.3.6.1.4.1.4555.1.1.7.1.9.22.1 | RowupsAgentFirewallControlEntry | not-accessible | mandatory | The managers. |
| 1.3.6.1.4.1.4555.1.1.7.1.9.22.1.1 | ColumnfirewallIndex | read-only | mandatory | The index to a firewall entry. |
| 1.3.6.1.4.1.4555.1.1.7.1.9.22.1.2 | ColumnfirewallControlAddr | read-write | mandatory | The IP address of the firewall |
| 1.3.6.1.4.1.4555.1.1.7.1.9.22.1.3 | ColumnfirewallPrefixLength | read-write | mandatory | The firewall prefix length. |
| 1.3.6.1.4.1.4555.1.1.7.1.9.22.1.4 | ColumnfirewallActionMode | read-write | mandatory | The firewall action mode |
| 1.3.6.1.4.1.4555.1.1.7.1.9.23 | ScalarupsAgentMibVersion | read-only | mandatory | The version of MIB spec. |
| 1.3.6.1.4.1.4555.1.1.7.1.10 | NodeemdStatus | |||
| 1.3.6.1.4.1.4555.1.1.7.1.10.1 | ScalaremdSatatusTemperature | read-only | mandatory | The measurement of EMD temperature, in 0.1 degree |
| 1.3.6.1.4.1.4555.1.1.7.1.10.2 | ScalaremdSatatusHumidity | read-only | mandatory | The measurement of EMD humidity, in 0.1 degree |
| 1.3.6.1.4.1.4555.1.1.7.1.10.3 | ScalaremdStatusIn1Active | read-only | mandatory | The input 1 has been detected as Active |
| 1.3.6.1.4.1.4555.1.1.7.1.10.4 | ScalaremdStatusIn2Active | read-only | mandatory | The input 2 has been detected as Active |
| 1.3.6.1.4.1.4555.1.1.7.2 | NodeupsTraps | |||
| 1.3.6.1.4.1.4555.1.1.7.2.1 | NodeupsTrapOnBattery | WARNING:The UPS is operating on battery power. This trap is persistent and is resent at one minute intervals until the UPS either turns off or is no longer run… | ||
| 1.3.6.1.4.1.4555.1.1.7.2.2 | NodeupsTrapTestCompleted | INFORMATION:This trap is sent upon completion of a UPS diagnostic test. | ||
| 1.3.6.1.4.1.4555.1.1.7.2.3 | NodeupsTrapAlarmEntryAdded | WARNING:This trap is sent each time an alarm is inserted into to the alarm table. It is sent on the insertion of all alarms except for upsAlarmOnBattery and up… | ||
| 1.3.6.1.4.1.4555.1.1.7.2.4 | NodeupsTrapAlarmEntryRemoved | INFORMATION:This trap is sent each time an alarm is removed from the alarm table. It is sent on the removal of all alarms except for upsAlarmTestInProgress. | ||
| 1.3.6.1.4.1.4555.1.1.7.2.5 | NodeupsTrapImminentStop | CRITICAL: The UPS is near to switch off the output power. | ||
| 1.3.6.1.4.1.4555.1.1.7.2.6 | NodeupsTrapOverload | WARNING: The UPS output is in overload. Output load rate more than 100% | ||
| 1.3.6.1.4.1.4555.1.1.7.2.7 | NodeupsTrapRedundancyLost | WARNING: Redundancy is lost. | ||
| 1.3.6.1.4.1.4555.1.1.7.2.8 | NodeupsTrapBatteryCircuitOpen | CRITICAL: The battery has been disconnected from UPS | ||
| 1.3.6.1.4.1.4555.1.1.7.2.9 | NodeupsTrapBatteryDischarged | CRITICAL: The battery has been detected as discharged. | ||
| 1.3.6.1.4.1.4555.1.1.7.2.10 | NodeupsTrapBatteryLow | CRITICAL: The battery is near of the end of backup time. | ||
| 1.3.6.1.4.1.4555.1.1.7.2.11 | NodeupsTrapBatteryAlarm | WARNING: The battery is in alarm. | ||
| 1.3.6.1.4.1.4555.1.1.7.2.12 | NodeupsTrapUpsCriticalAlarm | CRITICAL: A critical alarm has been detected on the UPS. | ||
| 1.3.6.1.4.1.4555.1.1.7.2.13 | NodeupsTrapLoadOFF | CRITICAL: The load has been disconnected from the UPS. LOAD OFF. | ||
| 1.3.6.1.4.1.4555.1.1.7.2.14 | NodeupsTrapCommunicationLost | CRITICAL: UPS is no more communicating with the agent. | ||
| 1.3.6.1.4.1.4555.1.1.7.2.15 | NodeupsTrapOnBatteryPower | WARNING: The UPS has switched to battery backup power. | ||
| 1.3.6.1.4.1.4555.1.1.7.2.16 | NodeupsTrapBatteryTestfailed | WARNING: The Battery test has detected a weak battery. | ||
| 1.3.6.1.4.1.4555.1.1.7.2.17 | NodeupsTrapTemperatureAlarm | WARNING: The UPS internal temperature has reached the threshold. | ||
| 1.3.6.1.4.1.4555.1.1.7.2.18 | NodeupsTrapOnBypass | WARNING: Load supplied by automatic Bypass. | ||
| 1.3.6.1.4.1.4555.1.1.7.2.19 | NodeupsTrapUpsPreventiveAlarm | WARNING: A preventive alarm has been detected by the UPS. | ||
| 1.3.6.1.4.1.4555.1.1.7.2.20 | NodeupsTrapShutdownWarning | WARNING: A warning message has be sent to shutdown agent. | ||
| 1.3.6.1.4.1.4555.1.1.7.2.21 | NodeupsTrapShutdownrequest | WARNING: A shutdown command has been sent to agent. | ||
| 1.3.6.1.4.1.4555.1.1.7.2.22 | NodeupsTrapUpsNormal | INFORMATION: The UPS status is normal. Load protected by UPS | ||
| 1.3.6.1.4.1.4555.1.1.7.2.23 | NodeupsTrapPowerRestored | INFORMATION: The Input supply has been restored | ||
| 1.3.6.1.4.1.4555.1.1.7.2.24 | NodeupsTrapAlarmCancelled | INFORMATION: Alarm cancelled. All alarms are disabled | ||
| 1.3.6.1.4.1.4555.1.1.7.2.25 | NodeupsTrapComEstablished | INFORMATION: The communication between UPS and the agent has been restored | ||
| 1.3.6.1.4.1.4555.1.1.7.2.26 | NodeupsTrapShutdwonCancelled | INFORMATION: The UPS has cancelled the shutdown procedure to agent | ||
| 1.3.6.1.4.1.4555.1.1.7.2.27 | NodeupsTrapAgentRestarting | INFORMATION: NET VISION is restarting | ||
| 1.3.6.1.4.1.4555.1.1.7.2.28 | NodeupsTrapEmdTempLow | CRITICAL: EMD Sensor detected low temperature. | ||
| 1.3.6.1.4.1.4555.1.1.7.2.29 | NodeupsTrapEmdTempNotLow | INFORMATION: EMD Sensor Not under low temperature. | ||
| 1.3.6.1.4.1.4555.1.1.7.2.30 | NodeupsTrapEmdTempHigh | CRITICAL: EMD Sensor detected high temperature. | ||
| 1.3.6.1.4.1.4555.1.1.7.2.31 | NodeupsTrapEmdTempNotHigh | INFORMATION: EMD Sensor Not over high temperature. | ||
| 1.3.6.1.4.1.4555.1.1.7.2.32 | NodeupsTrapEmdHumidityLow | CRITICAL: EMD Sensor detected low humidity. | ||
| 1.3.6.1.4.1.4555.1.1.7.2.33 | NodeupsTrapEmdHumidityNotLow | INFORMATION: EMD Sensor Not under low humidity. | ||
| 1.3.6.1.4.1.4555.1.1.7.2.34 | NodeupsTrapEmdHumidityHigh | CRITICAL: EMD Sensor detected high humidity. | ||
| 1.3.6.1.4.1.4555.1.1.7.2.35 | NodeupsTrapEmdHumidityNotHigh | INFORMATION: EMD Sensor Not over high humidity. | ||
| 1.3.6.1.4.1.4555.1.1.7.2.36 | NodeupsTrapEmdFirstInputActive | CRITICAL: The <customized string_1> input is active. | ||
| 1.3.6.1.4.1.4555.1.1.7.2.37 | NodeupsTrapEmdFirstInputRestored | INFORMATION: The <customized string_1> input is restored. | ||
| 1.3.6.1.4.1.4555.1.1.7.2.38 | NodeupsTrapEmdSecondInputActive | CRITICAL: The <customized string_2> input is active. | ||
| 1.3.6.1.4.1.4555.1.1.7.2.39 | NodeupsTrapEmdSecondInputRestored | INFORMATION: The <customized string_2> input is restored. | ||
| 1.3.6.1.4.1.4555.1.1.7.2.40 | NodeupsTrapSessionLogin | INFORMATION: New Admin or User session opened. | ||
| 1.3.6.1.4.1.4555.1.1.7.2.41 | NodeupsTrapLoginUnsuccesfulTentative | WARNING: Admin or User account locked. | ||
| 1.3.6.1.4.1.4555.1.1.7.2.42 | NodeupsTrapTest | INFORMATION: Send test trap. |