MIB Viewer

SP2-MIB

1867 objects
An ongoing effort toward a generic MIB for all ELTEK products. Branch overview: Aeongold branch will be 1 AL175 branch will be 2 AL6000 branch will be 3 Internal used branch will be 4 Internal used branch will be 5 OEM Smartpack branch will be 6 ELTEK Common branch will be 7 (SmartPack, MCU, AEON w/WebPower sw V2.x) ELTEK Distributed branch will be 8 (SmartPack w/WebPower sw V3.x) ELTEK Distributed V2 branch will be 9 (SmartPack w/WebPower sw V4.0) ELTEK Distributed V3 branch will be 9 (SmartPack w/WebPower sw V4.1) ELTEK Distributed V4 branch will be 9 (SmartPack w/WebPower sw V4.1, V4.2, V4.3, V4.5 and compack V1.0, V1.01, V1.02, V1.03) ELTEK Distributed V5 branch will be 9 (SmartPack w/WebPower sw V4.1, V4.2, V4.3, V4.5, V4.6) ELTEK Distributed V6 branch will be 9 (SmartPack2 sw V1.1, V1.2, V1.3) ELTEK Distributed V7 branch will be 9 (SmartPack w/WebPower sw V4.1, V4.2, V4.3, V4.5, V4.6, V4.7 and compack V1.04, V1.05) ELTEK eNexus MIB branch will be 10 (SmartPack2 Touch V2.x, Smartpack R V2.x, SmartPack2 V2.x, SmartPack S V2.x and Compack V2.x) ELTEK Brasil office will have branch 11 ELTEK BMS-EM MIB will have branch 12 ELTEK TELMEX MIB will have branch 13 ELTEK MSM MIB will have branch 14
Imported Objects
SNMPv2-CONFNOTIFICATION-GROUP
SNMPv2-SMICounter32 enterprises Integer32 MODULE-IDENTITY NOTIFICATION-TYPE OBJECT-TYPE Unsigned32
SNMPv2-TCDateAndTime DisplayString
OIDNameAccessStatusDescription
1.3.6.1.4.1.12148IdentityeltekAn ongoing effort toward a generic MIB for all ELTEK products. Branch overview: Aeongold branch will be 1 AL175 branch will be 2 AL6000 branch will be 3 Intern…
1.3.6.1.4.1.12148.10NodeeNexus
1.3.6.1.4.1.12148.10.1NodeeltekTraps
1.3.6.1.4.1.12148.10.1.1NodepowerAlarmVars
1.3.6.1.4.1.12148.10.1.1.1ScalaralarmSubsysSourceDescraccessible-for-notifycurrentA description of the source generating the trap for the Alarm Condition. Used in alarmSubSystemTrap to describe the alarm source. Example: 'batteryVoltageDescr…
1.3.6.1.4.1.12148.10.1.1.2ScalaralarmSubsysStatusOidaccessible-for-notifycurrentThe OID (name) of the object indicating the alarm-status for which the alarm is generated. The Status must be an INTEGER type. Example: SP2-MIB::batteryVoltage…
1.3.6.1.4.1.12148.10.1.1.3ScalaralarmSubsysStatusValueaccessible-for-notifycurrentThe value of the Status object of the subsystem for which the alarm-status is generated. The OID (name) of this object is indicated by alarmSubsysStatusOid abo…
1.3.6.1.4.1.12148.10.1.1.4ScalaralarmSubsysStatusOnOffaccessible-for-notifycurrentThis indicates if the abnormal condition is on or goes off.
1.3.6.1.4.1.12148.10.1.1.5ScalaralarmMeasuredVarOidaccessible-for-notifycurrentThe OID (name) of the measured-object indicating some measurement (e.g voltage) for which the alarm is generated. Example: SP2-MIB::batteryVoltage.batteryVolta…
1.3.6.1.4.1.12148.10.1.1.6ScalaralarmMeasuredVarValueaccessible-for-notifycurrentThe value of the measured-object for which the alarm-status is generated, for example 13 volt. The actual value is in units defined by the actual variable (e.g…
1.3.6.1.4.1.12148.10.1.1.7ScalaralarmTrapCounterVarValueaccessible-for-notifycurrent
1.3.6.1.4.1.12148.10.1.1.8ScalaralarmTrapTimeaccessible-for-notifycurrentTime stemp of trap
1.3.6.1.4.1.12148.10.1.2NodepowerSystemTraps
1.3.6.1.4.1.12148.10.1.2.1NotificationalarmPowerSystemTrapcurrentThis Trap is sent when an alarm condition occurs in the power system.
1.3.6.1.4.1.12148.10.1.2.2NotificationalarmBatteryTrapcurrentThis Trap is sent when an alarm condition occurs in the battery subsystem.
1.3.6.1.4.1.12148.10.1.2.3NotificationalarmLoadGroupTrapcurrentThis Trap is sent when an alarm condition occurs in the Load subsystem.
1.3.6.1.4.1.12148.10.1.2.4NotificationalarmMainsTrapcurrentThis Trap is sent when an alarm condition occurs in the Mains subsystem.
1.3.6.1.4.1.12148.10.1.2.5NotificationalarmRectifierTrapcurrentThis Trap is sent when an alarm condition occurs in the Rectifier subsystem.
1.3.6.1.4.1.12148.10.1.2.6NotificationalarmControlSystemTrapcurrentThis Trap is sent when an alarm condition occurs in the Control-system subsystem.
1.3.6.1.4.1.12148.10.1.2.7NotificationalarmDcDcTrapcurrentThis Trap is sent when an alarm condition occurs in the DCDC converter subsystem.
1.3.6.1.4.1.12148.10.1.2.8NotificationalarmInputsTrapcurrentThis Trap is sent when an alarm condition occurs in the Inputs subsystem.
1.3.6.1.4.1.12148.10.1.2.9NotificationalarmOutputsTrapcurrentThis Trap is sent when an alarm condition occurs in the Outputs subsystem.
1.3.6.1.4.1.12148.10.1.2.10NotificationalarmGeneratorTrapcurrentThis Trap is sent when an alarm condition occurs in the Generator subsystem.
1.3.6.1.4.1.12148.10.1.2.11NotificationalarmSolarChargerTrapcurrentThis Trap is sent when an alarm condition occurs in the SolarCharger subsystem.
1.3.6.1.4.1.12148.10.1.2.12NotificationalarmWindChargerTrapcurrentThis Trap is sent when an alarm condition occurs in the WindCharger subsystem.
1.3.6.1.4.1.12148.10.1.2.13NotificationinfoHeartBeatTrapcurrentWhen enabled, this trap will be transmitted at regular inervals. This trap is not intended to be an alarm but more like some information that the system is ali…
1.3.6.1.4.1.12148.10.1.2.14NotificationalarmInverterTrapcurrentThis Trap is sent when an alarm condition occurs in the Inverter subsystem.
1.3.6.1.4.1.12148.10.1.2.15NotificationalarmGridInverterTrapObsoletecurrentThis Trap is sent when an alarm condition occurs in the Grid Inverter subsystem.
1.3.6.1.4.1.12148.10.1.2.16NotificationalarmRectiverterTrapcurrentThis Trap is sent when an alarm condition occurs in the Rectiverter subsystem.
1.3.6.1.4.1.12148.10.1.2.17NotificationinfoBatteryTestTrapcurrentThis Trap is sent when battery test is performed in the power system:
1.3.6.1.4.1.12148.10.1.2.18NotificationalarmFuelCellTrapcurrentThis Trap is sent when an alarm condition occurs in the fuel cell subsystem.
1.3.6.1.4.1.12148.10.1.3GrouppowerSystemTrapsGroupcurrentThe powerSystem Trap goup. Entry point for the trap list.
1.3.6.1.4.1.12148.10.2NodepowerSystem
1.3.6.1.4.1.12148.10.2.1ScalarpowerSystemStatusread-onlycurrentA status value showing the overall condition of the power system.
1.3.6.1.4.1.12148.10.2.2ScalarpowerSystemTyperead-onlycurrentA value showing the type of the power system, which is named after the main controller.
1.3.6.1.4.1.12148.10.2.3ScalarpowerSystemModeread-onlycurrentA summary status showing if the system is in test, boost, float, equalize, emergency or start-up delay mode
1.3.6.1.4.1.12148.10.2.4ScalarpowerSystemCompanyread-writecurrentThe Copmany name (as stored in the Control Unit).
1.3.6.1.4.1.12148.10.2.5ScalarpowerSystemSiteread-writecurrentThe system/site Location details (as stored in the Control Unit).
1.3.6.1.4.1.12148.10.2.6ScalarpowerSystemModelread-onlycurrentThe model/part number of the power system (as stored in the Control Unit).
1.3.6.1.4.1.12148.10.2.7ScalarpowerSystemSerialNumberread-writecurrentThe serial number for the complete system.
1.3.6.1.4.1.12148.10.2.8ScalarpowerSystemInstallDateread-writecurrentThe system's Installation date (as stored in the Control Unit).
1.3.6.1.4.1.12148.10.2.9ScalarpowerSystemNominalVoltageread-onlycurrentThe nominal voltage rating. 12V/24V/48V/60V/110V/220V/380V etc. systems.
1.3.6.1.4.1.12148.10.2.10ScalarpowerSystemLongituderead-writecurrentA part of the systems global positioning data. The range +-180degrees Longitude lines are imaginary lines running from the north pole to the south pole. Longit…
1.3.6.1.4.1.12148.10.2.11ScalarpowerSystemLongitudeDecimalread-writecurrentThe decimal part of dcSystemLatitude contains up to 7digits. This number is in 1/1000000 degree fractions or 0,0000001 degree. A part of the systems global pos…
1.3.6.1.4.1.12148.10.2.12ScalarpowerSystemLatituderead-writecurrentA part of the systems global positioning data. The latitude gives the location of a place on Earth (or other planetary body) north or south of the equator. Lin…
1.3.6.1.4.1.12148.10.2.13ScalarpowerSystemLatitudeDecimalread-writecurrentThe decimal part of dcSystemLatitude contains up to 7digits. This number is in 1/1000000 degree fractions or 0,0000001 degree. A part of the systems global pos…
1.3.6.1.4.1.12148.10.2.14ScalarpowerSystemElevationread-writecurrentA part of the systems global positioning data. This is the sites height above sealevel in Meters. The Elevation together with Latituse and Longitude is used fo…
1.3.6.1.4.1.12148.10.2.15ScalarpowerSystemCurrentDecimalSettingread-writecurrentA global flag telling if the current values in the system is Amperes or DeciAmpres
1.3.6.1.4.1.12148.10.2.16ScalarpowerSystemTemperatureScaleread-writecurrentA flag telling if the temperatures values in the system is of Celcius or Fahrenheit type
1.3.6.1.4.1.12148.10.2.17ScalarpowerSystemCapacityScaleread-writecurrentA flag telling if the system's battery capacity value is a percentage of a fully charged battery, or in AmpereHours
1.3.6.1.4.1.12148.10.2.18ScalarpowerSystemEnergySourceread-onlycurrentShow the energy source that currently powering the system.
1.3.6.1.4.1.12148.10.3Nodemains
1.3.6.1.4.1.12148.10.3.1ScalarmainsStatusread-onlycurrentThe overall status of mains/AC feed subsystem.
1.3.6.1.4.1.12148.10.3.2NodemainsMainsFailure
1.3.6.1.4.1.12148.10.3.2.1ScalarmainsMainsFailureStatusread-onlycurrentThis status value shows if the number of failed phases is higher than the defined alarm level.
1.3.6.1.4.1.12148.10.3.2.2ScalarmainsMainsFailureDescriptionread-writecurrentA textual description of the mains phase failure monitor. This is stored in the system controller and can be changed by the user.
1.3.6.1.4.1.12148.10.3.2.3ScalarmainsMainsFailureTrapRepeatCounteraccessible-for-notifycurrentThe number of consecutive times this alam condition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this tr…
1.3.6.1.4.1.12148.10.3.2.4ScalarmainsMainsFailureAlarmEnableread-writecurrentThis value once enabled, the alarm condition of the monitor will be reported.
1.3.6.1.4.1.12148.10.3.2.5ScalarmainsMainsFailureValueread-onlycurrentThe detected number of failed phases.
1.3.6.1.4.1.12148.10.3.2.6ScalarmainsMainsFailureMajorAlarmLevelread-writecurrentThe major alarm limit
1.3.6.1.4.1.12148.10.3.2.7ScalarmainsMainsFailureMinorAlarmLevelread-writecurrentThe minor alarm limit
1.3.6.1.4.1.12148.10.3.3ScalarmainsNumberOfPhasesread-writecurrentThis value showing the number of phases of the mains subsystem.
1.3.6.1.4.1.12148.10.3.4TablemainsVoltageTablenot-accessiblecurrentThis table contains information about mains voltage monitor
1.3.6.1.4.1.12148.10.3.4.1RowmainsVoltageEntrynot-accessiblecurrent
1.3.6.1.4.1.12148.10.3.4.1.1ColumnmainsVoltageIndexnot-accessiblecurrentIndex used for navigating the rows 1..12 of mainsVoltageTable
1.3.6.1.4.1.12148.10.3.4.1.2ColumnmainsVoltageStatusread-onlycurrentThe status of the measured mains voltage.
1.3.6.1.4.1.12148.10.3.4.1.3ColumnmainsVoltageDescriptionread-writecurrentA textual description of the mains voltage monitor. This is stored in the system controller and can be changed by the user.
1.3.6.1.4.1.12148.10.3.4.1.4ColumnmainsVoltageTrapRepeatCounteraccessible-for-notifycurrentThe number of consecutive times this alamcondition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this tra…
1.3.6.1.4.1.12148.10.3.4.1.5ColumnmainsVoltageAlarmEnableread-writecurrentThis value once enabled, the alarm condition of the monitor will be reported.
1.3.6.1.4.1.12148.10.3.4.1.6ColumnmainsVoltageValueread-onlycurrentThe value of the measured mains voltage.
1.3.6.1.4.1.12148.10.3.4.1.7ColumnmainsVoltageMajorHighLevelread-writecurrentThe major high alarm limit
1.3.6.1.4.1.12148.10.3.4.1.8ColumnmainsVoltageMinorHighLevelread-writecurrentThe minor high alarm limit
1.3.6.1.4.1.12148.10.3.4.1.9ColumnmainsVoltageMinorLowLevelread-writecurrentThe minor low alarm limit
1.3.6.1.4.1.12148.10.3.4.1.10ColumnmainsVoltageMajorLowLevelread-writecurrentThe major low alarm limit
1.3.6.1.4.1.12148.10.3.5NodemainsMonitors
1.3.6.1.4.1.12148.10.3.5.1ScalarmainsMonitorsNumberOfUnitsread-writecurrentThis is the number of AC Mains Monitor CAN Nodes installed in the system.
1.3.6.1.4.1.12148.10.3.5.2TablemainsMonitorsTablenot-accessiblecurrentThis table contains the number of voltage, current and frequency measurements in each AC Mains Monitor
1.3.6.1.4.1.12148.10.3.5.2.1RowmainsMonitorsEntrynot-accessiblecurrent
1.3.6.1.4.1.12148.10.3.5.2.1.1ColumnmainsMonitorIndexnot-accessiblecurrentIndex used for navigating the rows of mainsMonitorsTable The size of the table is defined by the system
1.3.6.1.4.1.12148.10.3.5.2.1.2ColumnmainsMonitorNumberOfVoltagesread-onlycurrentThe number of voltage measurements in the AC Mains Monitor
1.3.6.1.4.1.12148.10.3.5.2.1.3ColumnmainsMonitorNumberOfCurrentsread-onlycurrentThe number of current measurements in the AC Mains Monitor
1.3.6.1.4.1.12148.10.3.5.2.1.4ColumnmainsMonitorNumberOfFrequenciesread-onlycurrentThe number of frequency measurements in the AC Mains Monitor
1.3.6.1.4.1.12148.10.3.5.3TablemainsMonitorVoltageTablenot-accessiblecurrentThis table contains information about mains voltage in AC Mains Monitor
1.3.6.1.4.1.12148.10.3.5.3.1RowmainsMonitorVoltageEntrynot-accessiblecurrent
1.3.6.1.4.1.12148.10.3.5.3.1.1ColumnmainsMonitorPhaseIndexnot-accessiblecurrentIndex used for navigating the rows 1..3 of mainsMonitorVolatgeTable
1.3.6.1.4.1.12148.10.3.5.3.1.2ColumnmainsMonitorVoltageStatusread-onlycurrentThe status of the measured mains voltage in AC Mains Monitor.
1.3.6.1.4.1.12148.10.3.5.3.1.3ColumnmainsMonitorVoltageDescriptionread-writecurrentA textual description of the mains voltage in AC Mains Monitor. This is stored in the system controller and can be changed by the user.
1.3.6.1.4.1.12148.10.3.5.3.1.4ColumnmainsMonitorVoltageTrapRepeatCounteraccessible-for-notifycurrentThe number of consecutive times this alamcondition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this tra…
1.3.6.1.4.1.12148.10.3.5.3.1.5ColumnmainsMonitorVoltageAlarmEnableread-writecurrentThis value once enabled, the alarm condition of the monitor will be reported.
1.3.6.1.4.1.12148.10.3.5.3.1.6ColumnmainsMonitorVoltageValueread-onlycurrentThe value of the measured mains voltage in AC Mains Monitor.
1.3.6.1.4.1.12148.10.3.5.3.1.7ColumnmainsMonitorVoltageMajorHighLevelread-writecurrentThe major high alarm limit
1.3.6.1.4.1.12148.10.3.5.3.1.8ColumnmainsMonitorVoltageMinorHighLevelread-writecurrentThe minor high alarm limit
1.3.6.1.4.1.12148.10.3.5.3.1.9ColumnmainsMonitorVoltageMinorLowLevelread-writecurrentThe minor low alarm limit
1.3.6.1.4.1.12148.10.3.5.3.1.10ColumnmainsMonitorVoltageMajorLowLevelread-writecurrentThe major low alarm limit
1.3.6.1.4.1.12148.10.3.5.4TablemainsMonitorCurrentTablenot-accessiblecurrentThis table contains information about mains current in AC Mains Monitor
1.3.6.1.4.1.12148.10.3.5.4.1RowmainsMonitorCurrentEntrynot-accessiblecurrent
1.3.6.1.4.1.12148.10.3.5.4.1.1ColumnmainsMonitorCurrentStatusread-onlycurrentThe status of the measured mains current in AC Mains Monitor.
1.3.6.1.4.1.12148.10.3.5.4.1.2ColumnmainsMonitorCurrentDescriptionread-writecurrentA textual description of the mains current in AC Mains Monitor. This is stored in the system controller and can be changed by the user.
1.3.6.1.4.1.12148.10.3.5.4.1.3ColumnmainsMonitorCurrentTrapRepeatCounteraccessible-for-notifycurrentThe number of consecutive times this alamcondition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this tra…
1.3.6.1.4.1.12148.10.3.5.4.1.4ColumnmainsMonitorCurrentAlarmEnableread-writecurrentThis value once enabled, the alarm condition of the monitor will be reported.
1.3.6.1.4.1.12148.10.3.5.4.1.5ColumnmainsMonitorCurrentValueread-onlycurrentThe value of the measured mains current in AC Mains Monitor.
1.3.6.1.4.1.12148.10.3.5.4.1.6ColumnmainsMonitorCurrentMajorHighLevelread-writecurrentThe major high alarm limit
1.3.6.1.4.1.12148.10.3.5.4.1.7ColumnmainsMonitorCurrentMinorHighLevelread-writecurrentThe minor high alarm limit
1.3.6.1.4.1.12148.10.3.5.5TablemainsMonitorFrequencyTablenot-accessiblecurrentThis table contains information about mains frequency in AC Mains Monitor
1.3.6.1.4.1.12148.10.3.5.5.1RowmainsMonitorFrequencyEntrynot-accessiblecurrent
1.3.6.1.4.1.12148.10.3.5.5.1.1ColumnmainsMonitorFrequencyStatusread-onlycurrentThe status of the measured mains frequency in AC Mains Monitor.
1.3.6.1.4.1.12148.10.3.5.5.1.2ColumnmainsMonitorFrequencyDescriptionread-writecurrentA textual description of the mains frequency in AC Mains Monitor. This is stored in the system controller and can be changed by the user.
1.3.6.1.4.1.12148.10.3.5.5.1.3ColumnmainsMonitorFrequencyTrapRepeatCounteraccessible-for-notifycurrentThe number of consecutive times this alamcondition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this tra…
1.3.6.1.4.1.12148.10.3.5.5.1.4ColumnmainsMonitorFrequencyAlarmEnableread-writecurrentThis value once enabled, the alarm condition of the monitor will be reported.
1.3.6.1.4.1.12148.10.3.5.5.1.5ColumnmainsMonitorFrequencyValueread-onlycurrentThe value of the measured mains frequency in AC Mains Monitor.
1.3.6.1.4.1.12148.10.3.5.5.1.6ColumnmainsMonitorFrequencyMajorHighLevelread-writecurrentThe major high alarm limit
1.3.6.1.4.1.12148.10.3.5.5.1.7ColumnmainsMonitorFrequencyMinorHighLevelread-writecurrentThe minor high alarm limit
1.3.6.1.4.1.12148.10.3.5.5.1.8ColumnmainsMonitorFrequencyMinorLowLevelread-writecurrentThe minor low alarm limit
1.3.6.1.4.1.12148.10.3.5.5.1.9ColumnmainsMonitorFrequencyMajorLowLevelread-writecurrentThe major low alarm limit
1.3.6.1.4.1.12148.10.3.5.6TablemainsMonitorEnergyLogAccumulatedTablenot-accessiblecurrentThis table contains the accumulated energy consumption measured in AC Mains Monitor
1.3.6.1.4.1.12148.10.3.5.6.1RowmainsMonitorEnergyLogAccumulatedEntrynot-accessiblecurrent
1.3.6.1.4.1.12148.10.3.5.6.1.1ColumnmainsMonitorEnergyLogAccumulatedread-onlycurrentThe accumulated energy consumption value
1.3.6.1.4.1.12148.10.3.5.7ScalarmainsMonitorEnergyLogLastHoursNumberOfEntriesread-onlycurrentThis is the maximal number of entries stored in hourly energy log
1.3.6.1.4.1.12148.10.3.5.8TablemainsMonitorEnergyLogLastHoursTablenot-accessiblecurrentThis table contains energy consumption values logged every hour in AC Mains Monitor.
1.3.6.1.4.1.12148.10.3.5.8.1RowmainsMonitorEnergyLogLastHoursEntrynot-accessiblecurrent
1.3.6.1.4.1.12148.10.3.5.8.1.1ColumnmainsMonitorEnergyLogLastHoursIndexnot-accessiblecurrentIndex used for navigating the rows 1..52 of mainsMonitorEnergyLogLastHoursTable
1.3.6.1.4.1.12148.10.3.5.8.1.2ColumnmainsMonitorEnergyLogLastHoursValueread-onlycurrentEnergy consumption value logged every hour in AC Mains Monitor.
1.3.6.1.4.1.12148.10.3.5.9ScalarmainsMonitorEnergyLogLastDaysNumberOfEntriesread-onlycurrentThis is the maximal number of entries stored in daily energy log
1.3.6.1.4.1.12148.10.3.5.10TablemainsMonitorEnergyLogLastDaysTablenot-accessiblecurrentThis table contains energy consumption values logged every day in AC Mains Monitor.
1.3.6.1.4.1.12148.10.3.5.10.1RowmainsMonitorEnergyLogLastDaysEntrynot-accessiblecurrent
1.3.6.1.4.1.12148.10.3.5.10.1.1ColumnmainsMonitorEnergyLogLastDaysIndexnot-accessiblecurrentIndex used for navigating the rows 1..52 of mainsMonitorEnergyLogLastDaysTable
1.3.6.1.4.1.12148.10.3.5.10.1.2ColumnmainsMonitorEnergyLogLastDaysValueread-onlycurrentEnergy consumption value logged every day in AC Mains Monitor.
1.3.6.1.4.1.12148.10.3.5.11ScalarmainsMonitorEnergyLogLastWeeksNumberOfEntriesread-onlycurrentThis is the maximal number of entries stored in weekly energy log
1.3.6.1.4.1.12148.10.3.5.12TablemainsMonitorEnergyLogLastWeeksTablenot-accessiblecurrentThis table contains energy consumption values logged every week in AC Mains Monitor.
1.3.6.1.4.1.12148.10.3.5.12.1RowmainsMonitorEnergyLogLastWeeksEntrynot-accessiblecurrent
1.3.6.1.4.1.12148.10.3.5.12.1.1ColumnmainsMonitorEnergyLogLastWeeksIndexnot-accessiblecurrentIndex used for navigating the rows 1..52 of mainsMonitorEnergyLogLastWeeksTable
1.3.6.1.4.1.12148.10.3.5.12.1.2ColumnmainsMonitorEnergyLogLastWeeksValueread-onlycurrentEnergy consumption value logged every week in AC Mains Monitor.
1.3.6.1.4.1.12148.10.3.5.13TablemainsMonitorActivePowerTablenot-accessiblecurrentThis table contains information about mains active power in AC Mains Monitor
1.3.6.1.4.1.12148.10.3.5.13.1RowmainsMonitorActivePowerEntrynot-accessiblecurrent
1.3.6.1.4.1.12148.10.3.5.13.1.1ColumnmainsMonitorActivePowerStatusread-onlycurrentThe status of the measured mains active power in AC Mains Monitor.
1.3.6.1.4.1.12148.10.3.5.13.1.2ColumnmainsMonitorActivePowerDescriptionread-writecurrentA textual description of the mains active power in AC Mains Monitor. This is stored in the system controller and can be changed by the user.
1.3.6.1.4.1.12148.10.3.5.13.1.3ColumnmainsMonitorActivePowerTrapRepeatCounteraccessible-for-notifycurrentThe number of consecutive times this alamcondition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this tra…
1.3.6.1.4.1.12148.10.3.5.13.1.4ColumnmainsMonitorActivePowerAlarmEnableread-writecurrentThis value once enabled, the alarm condition of the monitor will be reported.
1.3.6.1.4.1.12148.10.3.5.13.1.5ColumnmainsMonitorActivePowerValueread-onlycurrentThe value of the measured mains active power in AC Mains Monitor.
1.3.6.1.4.1.12148.10.3.5.13.1.6ColumnmainsMonitorActivePowerMajorHighLevelread-writecurrentThe major high alarm limit
1.3.6.1.4.1.12148.10.3.5.13.1.7ColumnmainsMonitorActivePowerMinorHighLevelread-writecurrentThe minor high alarm limit
1.3.6.1.4.1.12148.10.3.5.14TablemainsMonitorReactivePowerTablenot-accessiblecurrentThis table contains information about mains reactive power in AC Mains Monitor
1.3.6.1.4.1.12148.10.3.5.14.1RowmainsMonitorReactivePowerEntrynot-accessiblecurrent
1.3.6.1.4.1.12148.10.3.5.14.1.1ColumnmainsMonitorReactivePowerStatusread-onlycurrentThe status of the measured mains reactive power in AC Mains Monitor.
1.3.6.1.4.1.12148.10.3.5.14.1.2ColumnmainsMonitorReactivePowerDescriptionread-writecurrentA textual description of the mains reactive power in AC Mains Monitor. This is stored in the system controller and can be changed by the user.
1.3.6.1.4.1.12148.10.3.5.14.1.3ColumnmainsMonitorReactivePowerTrapRepeatCounteraccessible-for-notifycurrentThe number of consecutive times this alamcondition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this tra…
1.3.6.1.4.1.12148.10.3.5.14.1.4ColumnmainsMonitorReactivePowerAlarmEnableread-writecurrentThis value once enabled, the alarm condition of the monitor will be reported.
1.3.6.1.4.1.12148.10.3.5.14.1.5ColumnmainsMonitorReactivePowerValueread-onlycurrentThe value of the measured mains reactive power in AC Mains Monitor.
1.3.6.1.4.1.12148.10.3.5.14.1.6ColumnmainsMonitorReactivePowerMajorHighLevelread-writecurrentThe major high alarm limit
1.3.6.1.4.1.12148.10.3.5.14.1.7ColumnmainsMonitorReactivePowerMinorHighLevelread-writecurrentThe minor high alarm limit
1.3.6.1.4.1.12148.10.3.5.15TablemainsMonitorApparentPowerTablenot-accessiblecurrentThis table contains information about mains apparent power in AC Mains Monitor
1.3.6.1.4.1.12148.10.3.5.15.1RowmainsMonitorApparentPowerEntrynot-accessiblecurrent
1.3.6.1.4.1.12148.10.3.5.15.1.1ColumnmainsMonitorApparentPowerStatusread-onlycurrentThe status of the measured mains apparent power in AC Mains Monitor.
1.3.6.1.4.1.12148.10.3.5.15.1.2ColumnmainsMonitorApparentPowerDescriptionread-writecurrentA textual description of the mains apparent power in AC Mains Monitor. This is stored in the system controller and can be changed by the user.
1.3.6.1.4.1.12148.10.3.5.15.1.3ColumnmainsMonitorApparentPowerTrapRepeatCounteraccessible-for-notifycurrentThe number of consecutive times this alamcondition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this tra…
1.3.6.1.4.1.12148.10.3.5.15.1.4ColumnmainsMonitorApparentPowerAlarmEnableread-writecurrentThis value once enabled, the alarm condition of the monitor will be reported.
1.3.6.1.4.1.12148.10.3.5.15.1.5ColumnmainsMonitorApparentPowerValueread-onlycurrentThe value of the measured mains apparent power in AC Mains Monitor.
1.3.6.1.4.1.12148.10.3.5.15.1.6ColumnmainsMonitorApparentPowerMajorHighLevelread-writecurrentThe major high alarm limit
1.3.6.1.4.1.12148.10.3.5.15.1.7ColumnmainsMonitorApparentPowerMinorHighLevelread-writecurrentThe minor high alarm limit
1.3.6.1.4.1.12148.10.3.6NodemainsOutageLog
1.3.6.1.4.1.12148.10.3.6.1ScalarmainsOutageTotalread-onlycurrentThis is the total mains outage time measured in hours. Note that the value of this OID does not changed when the 'mainsLogMode' OID is set to 'runningTime'. Th…
1.3.6.1.4.1.12148.10.3.6.2ScalarmainsOutageLogDaysNumberOfEntriesread-onlycurrentThis is the maximal number of entries stored in daily mains outage/running time log.
1.3.6.1.4.1.12148.10.3.6.3TablemainsOutageLogDaysTablenot-accessiblecurrentThis table contains daily mains outage or running time log depending on the log mode.
1.3.6.1.4.1.12148.10.3.6.3.1RowmainsOutageLogDaysEntrynot-accessiblecurrent
1.3.6.1.4.1.12148.10.3.6.3.1.1ColumnmainsOutageLogDaysIndexnot-accessiblecurrentIndex used for navigating the rows 1..52 of mainsOutageLogDaysTable
1.3.6.1.4.1.12148.10.3.6.3.1.2ColumnmainsOutageLogDaysValueread-onlycurrentMains outage or running time value in minutes, logged every day.
1.3.6.1.4.1.12148.10.3.6.4ScalarmainsOutageLogWeeksNumberOfEntriesread-onlycurrentThis is the maximal number of entries stored in weekly mains outage/running time log.
1.3.6.1.4.1.12148.10.3.6.5TablemainsOutageLogWeeksTablenot-accessiblecurrentThis table contains weekly mains outage or running time log depending on the log mode.
1.3.6.1.4.1.12148.10.3.6.5.1RowmainsOutageLogWeeksEntrynot-accessiblecurrent
1.3.6.1.4.1.12148.10.3.6.5.1.1ColumnmainsOutageLogWeeksIndexnot-accessiblecurrentIndex used for navigating the rows 1..52 of mainsOutageLogWeeksTable
1.3.6.1.4.1.12148.10.3.6.5.1.2ColumnmainsOutageLogWeeksValueread-onlycurrentMains outage or running time value in hours, logged every week.
1.3.6.1.4.1.12148.10.3.6.6ScalarmainsOutageLogMonthsNumberOfEntriesread-onlycurrentThis is the maximal number of entries stored in monthly mains outage/running time log.
1.3.6.1.4.1.12148.10.3.6.7TablemainsOutageLogMonthsTablenot-accessiblecurrentThis table contains monthly mains outage or running time log depending on the log mode.
1.3.6.1.4.1.12148.10.3.6.7.1RowmainsOutageLogMonthsEntrynot-accessiblecurrent
1.3.6.1.4.1.12148.10.3.6.7.1.1ColumnmainsOutageLogMonthsIndexnot-accessiblecurrentIndex used for navigating the rows 1..52 of mainsOutageLogMonthsTable
1.3.6.1.4.1.12148.10.3.6.7.1.2ColumnmainsOutageLogMonthsValueread-onlycurrentMains outage or running time value in hours, logged every month.
1.3.6.1.4.1.12148.10.3.6.8ScalarmainsLogModeread-writecurrentThis value determines if the mains outage time or running time should be logged.
1.3.6.1.4.1.12148.10.3.7ScalarmainsNumberOfGroupsread-onlycurrentThis value showing the number of groups of the mains subsystem.
1.3.6.1.4.1.12148.10.3.8TablemainsGroupsTablenot-accessiblecurrentThis table contains the status of mains group and number of phases in each group.
1.3.6.1.4.1.12148.10.3.8.1RowmainsGroupsEntrynot-accessiblecurrent
1.3.6.1.4.1.12148.10.3.8.1.1ColumnmainsGroupIndexnot-accessiblecurrentIndex used for navigating the rows 1..10 of mainsGroupTable
1.3.6.1.4.1.12148.10.3.8.1.2ColumnmainsGroupStatusread-onlycurrentThe status of mains group.
1.3.6.1.4.1.12148.10.3.8.1.3ColumnmainsGroupNumberOfPhasesread-writecurrentThis value showing the number of phases of the mains group subsystem.
1.3.6.1.4.1.12148.10.3.9TablemainsGroupMainsFailureTablenot-accessiblecurrentThis table contains information about mains failure monitor of mains group
1.3.6.1.4.1.12148.10.3.9.1RowmainsGroupMainsFailureEntrynot-accessiblecurrent
1.3.6.1.4.1.12148.10.3.9.1.1ColumnmainsGroupMainsFailureStatusread-onlycurrentThis status value shows if the number of failed phases is higher than the defined alarm level for the mains group
1.3.6.1.4.1.12148.10.3.9.1.2ColumnmainsGroupMainsFailureDescriptionread-writecurrentA textual description of the mains group phase failure monitor. This is stored in the system controller and can be changed by the user.
1.3.6.1.4.1.12148.10.3.9.1.3ColumnmainsGroupMainsFailureTrapRepeatCounteraccessible-for-notifycurrentThe number of consecutive times this alam condition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this tr…
1.3.6.1.4.1.12148.10.3.9.1.4ColumnmainsGroupMainsFailureAlarmEnableread-writecurrentThis value once enabled, the alarm condition of the monitor will be reported.
1.3.6.1.4.1.12148.10.3.9.1.5ColumnmainsGroupMainsFailureValueread-onlycurrentThe detected number of failed phases in the mains group.
1.3.6.1.4.1.12148.10.3.9.1.6ColumnmainsGroupMainsFailureMajorAlarmLevelread-writecurrentThe major alarm limit
1.3.6.1.4.1.12148.10.3.9.1.7ColumnmainsGroupMainsFailureMinorAlarmLevelread-writecurrentThe minor alarm limit
1.3.6.1.4.1.12148.10.3.10TablemainsGroupVoltageTablenot-accessiblecurrentThis table contains information about mains voltage monitors for mains group
1.3.6.1.4.1.12148.10.3.10.1RowmainsGroupVoltageEntrynot-accessiblecurrent
1.3.6.1.4.1.12148.10.3.10.1.1ColumnmainsGroupVoltageIndexnot-accessiblecurrentIndex used for navigating the rows 1..12 of mainsGroupVoltageTable
1.3.6.1.4.1.12148.10.3.10.1.2ColumnmainsGroupVoltageStatusread-onlycurrentThe status of the measured mains voltage of the mains group.
1.3.6.1.4.1.12148.10.3.10.1.3ColumnmainsGroupVoltageDescriptionread-writecurrentA textual description of the mains voltage monitor of the mains group. This is stored in the system controller and can be changed by the user.
1.3.6.1.4.1.12148.10.3.10.1.4ColumnmainsGroupVoltageTrapRepeatCounteraccessible-for-notifycurrentThe number of consecutive times this alamcondition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this tra…
1.3.6.1.4.1.12148.10.3.10.1.5ColumnmainsGroupVoltageAlarmEnableread-writecurrentThis value once enabled, the alarm condition of the monitor will be reported.
1.3.6.1.4.1.12148.10.3.10.1.6ColumnmainsGroupVoltageValueread-onlycurrentThe value of the measured mains voltage in the mains group.
1.3.6.1.4.1.12148.10.3.10.1.7ColumnmainsGroupVoltageMajorHighLevelread-writecurrentThe major high alarm limit
1.3.6.1.4.1.12148.10.3.10.1.8ColumnmainsGroupVoltageMinorHighLevelread-writecurrentThe minor high alarm limit
1.3.6.1.4.1.12148.10.3.10.1.9ColumnmainsGroupVoltageMinorLowLevelread-writecurrentThe minor low alarm limit
1.3.6.1.4.1.12148.10.3.10.1.10ColumnmainsGroupVoltageMajorLowLevelread-writecurrentThe major low alarm limit
1.3.6.1.4.1.12148.10.3.11TablemainsGroupOutageLogTablenot-accessiblecurrentThis table contains total mains outage of the mains group and number of entries in each log table.
1.3.6.1.4.1.12148.10.3.11.1RowmainsGroupOutageLogEntrynot-accessiblecurrent
1.3.6.1.4.1.12148.10.3.11.1.1ColumnmainsGroupOutageTotalread-onlycurrentThis is the total mains outage time measured in hours in the mains group.
1.3.6.1.4.1.12148.10.3.11.1.2ColumnmainsGroupOutageLogDaysNumberOfEntriesread-onlycurrentThis is the maximal number of entries stored in daily mains outage log.
1.3.6.1.4.1.12148.10.3.11.1.3ColumnmainsGroupOutageLogWeeksNumberOfEntriesread-onlycurrentThis is the maximal number of entries stored in weekly mains outage time log.
1.3.6.1.4.1.12148.10.3.11.1.4ColumnmainsGroupOutageLogMonthsNumberOfEntriesread-onlycurrentThis is the maximal number of entries stored in monthly mains outage time log.
1.3.6.1.4.1.12148.10.3.12TablemainsGroupOutageLogDaysTablenot-accessiblecurrentThis table contains daily mains outage time log of mains group.
1.3.6.1.4.1.12148.10.3.12.1RowmainsGroupOutageLogDaysEntrynot-accessiblecurrent
1.3.6.1.4.1.12148.10.3.12.1.1ColumnmainsGroupOutageLogDaysIndexnot-accessiblecurrentIndex used for navigating the rows 1..52 of mainsGroupOutageLogDaysTable
1.3.6.1.4.1.12148.10.3.12.1.2ColumnmainsGroupOutageLogDaysValueread-onlycurrentMains outage time value in minutes of each mains group, logged every day.
1.3.6.1.4.1.12148.10.3.13TablemainsGroupOutageLogWeeksTablenot-accessiblecurrentThis table contains weekly mains outage time log of mains group.
1.3.6.1.4.1.12148.10.3.13.1RowmainsGroupOutageLogWeeksEntrynot-accessiblecurrent
1.3.6.1.4.1.12148.10.3.13.1.1ColumnmainsGroupOutageLogWeeksIndexnot-accessiblecurrentIndex used for navigating the rows 1..52 of mainsGroupOutageLogWeeksTable
1.3.6.1.4.1.12148.10.3.13.1.2ColumnmainsGroupOutageLogWeeksValueread-onlycurrentMains outage time value in hours of each mains group, logged every week.
1.3.6.1.4.1.12148.10.3.14TablemainsGroupOutageLogMonthsTablenot-accessiblecurrentThis table contains monthly mains outage time log of mains group.
1.3.6.1.4.1.12148.10.3.14.1RowmainsGroupOutageLogMonthsEntrynot-accessiblecurrent
1.3.6.1.4.1.12148.10.3.14.1.1ColumnmainsGroupOutageLogMonthsIndexnot-accessiblecurrentIndex used for navigating the rows 1..52 of mainsGroupOutageLogMonthsTable
1.3.6.1.4.1.12148.10.3.14.1.2ColumnmainsGroupOutageLogMonthsValueread-onlycurrentMains outage time value in hours of each mains group, logged every month.
1.3.6.1.4.1.12148.10.3.15ScalarmainsRunningHoursread-onlycurrentThis is the total mains running time measured in hours. The total outage time is available at OID 1.3.6.1.4.1.12148.10.3.6.1
1.3.6.1.4.1.12148.10.4Nodegenerator
1.3.6.1.4.1.12148.10.4.1ScalargeneratorStatusread-onlycurrentThe overall status of generator subsystem.
1.3.6.1.4.1.12148.10.4.2ScalargeneratorFailStatusread-onlycurrentThe status of generator failure monitor.
1.3.6.1.4.1.12148.10.4.3ScalargeneratorActivationread-onlycurrentIndicate if the generator run output signal is activated.
1.3.6.1.4.1.12148.10.4.4ScalargeneratorDischargeValueread-onlycurrentThis is the present discharge value in percentage of total capacity.
1.3.6.1.4.1.12148.10.4.5ScalargeneratorMainsDelayread-onlycurrentElapsing time of mains failure.
1.3.6.1.4.1.12148.10.4.6ScalargeneratorChargeTimeread-onlycurrentElapsing time of charging with generator running.
1.3.6.1.4.1.12148.10.4.7ScalargeneratorCapacityControlledStartStopEnableread-writecurrentBattery charge/discharge level control of starting and stopping of generator
1.3.6.1.4.1.12148.10.4.8ScalargeneratorCapacityStartOnDischargeLimitread-writecurrentWhen the generatorCapacityControlled is enabled, the generator is started when the remaining battery capacity drops below this limit in percentage of the total…
1.3.6.1.4.1.12148.10.4.9ScalargeneratorCapacityStopOnChargeLimitread-writecurrentWhen the generatorCapacityControlled is enabled, the generator is stopped when the remaining battery capacity is greater than this limit in percentage of the t…
1.3.6.1.4.1.12148.10.4.10ScalargeneratorCurrentLimitControlledStopEnableread-writecurrentEnables the generator to stop when the charge current drops below generatorCurrentLimitControlledStopValue.
1.3.6.1.4.1.12148.10.4.11ScalargeneratorCurrentLimitControlledStopValueread-writecurrentGenerator stops when the charge current drop drops below this level.
1.3.6.1.4.1.12148.10.4.12ScalargeneratorVoltageControlledStartEnableread-writecurrentEnable/disable voltage controlled generator activation.
1.3.6.1.4.1.12148.10.4.13ScalargeneratorVoltageControlStartVoltageread-writecurrentThe voltage limit to start generator.
1.3.6.1.4.1.12148.10.4.14ScalargeneratorVoltageControlStopAfterread-writecurrentA time delay for stopping generator when generator is activated by voltage.
1.3.6.1.4.1.12148.10.4.15ScalargeneratorDailyRunEnableread-writecurrentEnable/disable generator daily run function.
1.3.6.1.4.1.12148.10.4.16TablegeneratorDailyRunSetupTablenot-accessiblecurrentThis table contains configurations of generator daily run.
1.3.6.1.4.1.12148.10.4.16.1RowgeneratorDailyRunSetupEntrynot-accessiblecurrent
1.3.6.1.4.1.12148.10.4.16.1.1ColumngeneratorDailyRunDayIndexnot-accessiblecurrentIndex used for navigating the rows 1..7 of generatorDailyRunSetupTable
1.3.6.1.4.1.12148.10.4.16.1.2ColumngeneratorDailyRunStartHourread-writecurrentGenerator daily starting time.
1.3.6.1.4.1.12148.10.4.16.1.3ColumngeneratorDailyRunStopHourread-writecurrentGenerator daily stopping time.
1.3.6.1.4.1.12148.10.4.17ScalargeneratorMonthlyRunEnableread-writecurrentEnable/disable generator monthly run function.
1.3.6.1.4.1.12148.10.4.18ScalargeneratorMonthlyRunStartTimeread-writecurrentGenerator monthly run starting time.
1.3.6.1.4.1.12148.10.4.19ScalargeneratorMonthlyRunStartDayinMonth1read-writecurrentGenerator monthly run starting day #1.
1.3.6.1.4.1.12148.10.4.20ScalargeneratorMonthlyRunStartDayinMonth2read-writecurrentGenerator monthly run starting day #2.
1.3.6.1.4.1.12148.10.4.21ScalargeneratorTankNumberOfTanksread-onlycurrentNumber of fuel tanks.
1.3.6.1.4.1.12148.10.4.22TablegeneratorTankTablenot-accessiblecurrentThis table contains information about generator fuel tanks.
1.3.6.1.4.1.12148.10.4.22.1RowgeneratorTankEntrynot-accessiblecurrent
1.3.6.1.4.1.12148.10.4.22.1.1ColumngeneratorTankIndexnot-accessiblecurrentIndex used for navigating the rows 1..2 of generatorTankTable
1.3.6.1.4.1.12148.10.4.22.1.2ColumngeneratorTankStatusread-onlycurrentThe status of the measured fuel level in tank.
1.3.6.1.4.1.12148.10.4.22.1.3ColumngeneratorTankDescriptionread-writecurrentA textual description of the fuel level monitor. This is stored in the system controller and can be changed by the user.
1.3.6.1.4.1.12148.10.4.22.1.4ColumngeneratorTankTrapRepeatCounteraccessible-for-notifycurrentThe number of consecutive times this alamcondition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this tra…
1.3.6.1.4.1.12148.10.4.22.1.5ColumngeneratorTankEnableread-writecurrentThis value once enabled, the alarm condition of the monitor will be reported.
1.3.6.1.4.1.12148.10.4.22.1.6ColumngeneratorTankValueread-onlycurrentThe value of the measured fuel level.
1.3.6.1.4.1.12148.10.4.22.1.7ColumngeneratorTankMajorHighLevelread-writecurrentThe major high alarm limit
1.3.6.1.4.1.12148.10.4.22.1.8ColumngeneratorTankMinorHighLevelread-writecurrentThe minor high alarm limit
1.3.6.1.4.1.12148.10.4.22.1.9ColumngeneratorTankMinorLowLevelread-writecurrentThe minor low alarm limit
1.3.6.1.4.1.12148.10.4.22.1.10ColumngeneratorTankMajorLowLevelread-writecurrentThe major low alarm limit
1.3.6.1.4.1.12148.10.4.23NodegeneratorEnergyLog
1.3.6.1.4.1.12148.10.4.23.1ScalargeneratorEnergyLogAccumulatedread-onlycurrentThis is the accumulated energy delivered through rectifiers from generator.
1.3.6.1.4.1.12148.10.4.23.2ScalargeneratorEnergyLogLastHoursNumberOfEntriesread-onlycurrentThis is the maximal number of entries stored in generator hourly energy log.
1.3.6.1.4.1.12148.10.4.23.3TablegeneratorEnergyLogLastHoursTablenot-accessiblecurrentThis table contains hourly energy log of generator.
1.3.6.1.4.1.12148.10.4.23.3.1RowgeneratorEnergyLogLastHoursEntrynot-accessiblecurrent
1.3.6.1.4.1.12148.10.4.23.3.1.1ColumngeneratorEnergyLogLastHoursIndexnot-accessiblecurrentIndex used for navigating the rows 1..52 of generatorEnergyLogLastHoursTable
1.3.6.1.4.1.12148.10.4.23.3.1.2ColumngeneratorEnergyLogLastHoursValueread-onlycurrentEnergy value logged every hour.
1.3.6.1.4.1.12148.10.4.23.4ScalargeneratorEnergyLogLastDaysNumberOfEntriesread-onlycurrentThis is the maximal number of entries stored in generator daily energy log.
1.3.6.1.4.1.12148.10.4.23.5TablegeneratorEnergyLogLastDaysTablenot-accessiblecurrentThis table contains daily energy log of generator.
1.3.6.1.4.1.12148.10.4.23.5.1RowgeneratorEnergyLogLastDaysEntrynot-accessiblecurrent
1.3.6.1.4.1.12148.10.4.23.5.1.1ColumngeneratorEnergyLogLastDaysIndexnot-accessiblecurrentIndex used for navigating the rows 1..52 of generatorEnergyLogLastDaysTable
1.3.6.1.4.1.12148.10.4.23.5.1.2ColumngeneratorEnergyLogLastDaysValueread-onlycurrentEnergy value logged every day
1.3.6.1.4.1.12148.10.4.23.6ScalargeneratorEnergyLogLastWeeksNumberOfEntriesread-onlycurrentThis is the maximal number of entries stored in generator weekly energy log.
1.3.6.1.4.1.12148.10.4.23.7TablegeneratorEnergyLogLastWeeksTablenot-accessiblecurrentThis table contains weekly energy log of generator.
1.3.6.1.4.1.12148.10.4.23.7.1RowgeneratorEnergyLogLastWeeksEntrynot-accessiblecurrent
1.3.6.1.4.1.12148.10.4.23.7.1.1ColumngeneratorEnergyLogLastWeeksIndexnot-accessiblecurrentIndex used for navigating the rows 1..52 of generatorEnergyLogLastWeeksTable
1.3.6.1.4.1.12148.10.4.23.7.1.2ColumngeneratorEnergyLogLastWeeksValueread-onlycurrentEnergy value logged every week.
1.3.6.1.4.1.12148.10.4.24NodegeneratorRunHoursLog
1.3.6.1.4.1.12148.10.4.24.1ScalargeneratorRunHoursTotalHoursread-onlycurrentThis is the total generator running hours.
1.3.6.1.4.1.12148.10.4.24.2ScalargeneratorRunHoursLogLastDaysNumberOfEntriesread-onlycurrentThis is the maximal number of entries stored in generator daily running hours log.
1.3.6.1.4.1.12148.10.4.24.3TablegeneratorRunHoursLogLastDaysTablenot-accessiblecurrentgenerator running time in minutes
1.3.6.1.4.1.12148.10.4.24.3.1RowgeneratorRunHoursLogLastDaysEntrynot-accessiblecurrent
1.3.6.1.4.1.12148.10.4.24.3.1.1ColumngeneratorRunHoursLogLastDaysIndexnot-accessiblecurrentIndex used for navigating the rows 1..52 of generatorRunHoursLogLastDaysTable
1.3.6.1.4.1.12148.10.4.24.3.1.2ColumngeneratorRunHoursLogLastDaysValueread-onlycurrentGenerator running time in minutes, logged every day.
1.3.6.1.4.1.12148.10.4.24.4ScalargeneratorRunHoursLogLastWeeksNumberOfEntriesread-onlycurrentThis is the maximal number of entries stored in generator weekly running hours log.
1.3.6.1.4.1.12148.10.4.24.5TablegeneratorRunHoursLogLastWeeksTablenot-accessiblecurrentgenerator running time in hours
1.3.6.1.4.1.12148.10.4.24.5.1RowgeneratorRunHoursLogLastWeeksEntrynot-accessiblecurrent
1.3.6.1.4.1.12148.10.4.24.5.1.1ColumngeneratorRunHoursLogLastWeeksIndexnot-accessiblecurrentIndex used for navigating the rows 1..52 of generatorRunHoursLogLastWeeksTable
1.3.6.1.4.1.12148.10.4.24.5.1.2ColumngeneratorRunHoursLogLastWeeksValueread-onlycurrentGenerator running time in hours, logged every week.
1.3.6.1.4.1.12148.10.4.24.6ScalargeneratorRunHoursLogLastMonthsNumberOfEntriesread-onlycurrentThis is the maximal number of entries stored in generator monthly running hours log.
1.3.6.1.4.1.12148.10.4.24.7TablegeneratorRunHoursLogLastMonthsTablenot-accessiblecurrentgenerator running time in hours
1.3.6.1.4.1.12148.10.4.24.7.1RowgeneratorRunHoursLogLastMonthsEntrynot-accessiblecurrent
1.3.6.1.4.1.12148.10.4.24.7.1.1ColumngeneratorRunHoursLogLastMonthsIndexnot-accessiblecurrentIndex used for navigating the rows 1..52 of generatorRunHoursLogLastMonthsTable
1.3.6.1.4.1.12148.10.4.24.7.1.2ColumngeneratorRunHoursLogLastMonthsValueread-onlycurrentGenerator running time in hours, logged every month.
1.3.6.1.4.1.12148.10.4.25NodegeneratorFuelConsumptionLog
1.3.6.1.4.1.12148.10.4.25.1TablegeneratorFuelConsumptionTotalUsedTablenot-accessiblecurrentThis table contains total fuel consumption for each tank.
1.3.6.1.4.1.12148.10.4.25.1.1RowgeneratorFuelConsumptionTotalUsedEntrynot-accessiblecurrent
1.3.6.1.4.1.12148.10.4.25.1.1.1ColumngeneratorFuelConsumptionTotalUsedread-onlycurrentTotal fuel consumption value.
1.3.6.1.4.1.12148.10.4.25.2ScalargeneratorFuelConsumptionLogLastDaysNoOfEntriesread-onlycurrentThis is the maximal number of entries stored in generator daily fuel consumption log.
1.3.6.1.4.1.12148.10.4.25.3TablegeneratorFuelConsumptionLogLastDaysTablenot-accessiblecurrentThis table contains generator daily fuel consumption log.
1.3.6.1.4.1.12148.10.4.25.3.1RowgeneratorFuelConsumptionLogLastDaysEntrynot-accessiblecurrent
1.3.6.1.4.1.12148.10.4.25.3.1.1ColumngeneratorFuelConsumptionLogLastDaysIndexnot-accessiblecurrentIndex used for navigating the rows 1..52 of generatorFuelConsumptionLogLastDaysTable
1.3.6.1.4.1.12148.10.4.25.3.1.2ColumngeneratorFuelConsumptionLogLastDaysValueread-onlycurrentGenerator fuel consumption value, logged every day.
1.3.6.1.4.1.12148.10.4.25.4ScalargeneratorFuelConsumptionLogLastWeeksNoOfEntriesread-onlycurrentThis is the maximal number of entries stored in generator weekly fuel consumption log.
1.3.6.1.4.1.12148.10.4.25.5TablegeneratorFuelConsumptionLogLastWeeksTablenot-accessiblecurrentThis table contains generator weekly fuel consumption log.
1.3.6.1.4.1.12148.10.4.25.5.1RowgeneratorFuelConsumptionLogLastWeeksEntrynot-accessiblecurrent
1.3.6.1.4.1.12148.10.4.25.5.1.1ColumngeneratorFuelConsumptionLogLastWeeksIndexnot-accessiblecurrentIndex used for navigating the rows 1..52 of generatorFuelConsumptionLogLastWeeksTable
1.3.6.1.4.1.12148.10.4.25.5.1.2ColumngeneratorFuelConsumptionLogLastWeeksValueread-onlycurrentGenerator fuel consumption value, logged every week.
1.3.6.1.4.1.12148.10.4.25.6ScalargeneratorFuelConsumptionLogLastMonthsNoOfEntriesread-onlycurrentThis is the maximal number of entries stored in generator hourly fuel consumption log.
1.3.6.1.4.1.12148.10.4.25.7TablegeneratorFuelConsumptionLogLastMonthsTablenot-accessiblecurrentThis table contains generator hourly fuel consumption log.
1.3.6.1.4.1.12148.10.4.25.7.1RowgeneratorFuelConsumptionLogLastMonthsEntrynot-accessiblecurrent
1.3.6.1.4.1.12148.10.4.25.7.1.1ColumngeneratorFuelConsumptionLogLastMonthsIndexnot-accessiblecurrentIndex used for navigating the rows 1..52 of generatorFuelConsumptionLogLastHoursTable
1.3.6.1.4.1.12148.10.4.25.7.1.2ColumngeneratorFuelConsumptionLogLastMonthsValueread-onlycurrentGenerator fuel consumption value, logged every hour.
1.3.6.1.4.1.12148.10.4.26NodegseGenerator
1.3.6.1.4.1.12148.10.4.26.1ScalargseGeneratorOilPressureread-onlycurrentOil pressure in kpa
1.3.6.1.4.1.12148.10.4.26.2ScalargseGeneratorCoolantTemperatureread-onlycurrentCoolant temperature
1.3.6.1.4.1.12148.10.4.26.3ScalargseGeneratorFuelLevelread-onlycurrentFuel level in percentage
1.3.6.1.4.1.12148.10.4.26.4ScalargseGeneratorEngineBatteryVoltageread-onlycurrentEngine Battery voltage
1.3.6.1.4.1.12148.10.4.26.5ScalargseGeneratorEngineSpeedread-onlycurrentEngine speed in RPM
1.3.6.1.4.1.12148.10.4.26.6ScalargseGeneratorFrequencyread-onlycurrentGenerator frequency in Hz
1.3.6.1.4.1.12148.10.4.26.7ScalargseGeneratorEngineRunTimeread-onlycurrentEngine run time in seconds
1.3.6.1.4.1.12148.10.4.26.8ScalargseGeneratorModeread-onlycurrentGenerator Auto/manual mode
1.3.6.1.4.1.12148.10.4.26.9ScalargseGeneratorRunningread-onlycurrentgenerator operating state
1.3.6.1.4.1.12148.10.4.26.10ScalargseGeneratorHighTemperatureread-onlycurrent
1.3.6.1.4.1.12148.10.4.26.11ScalargseGeneratorLowOilPressureread-onlycurrent
1.3.6.1.4.1.12148.10.4.26.12ScalargseGeneratorFuelProbeFailread-onlycurrent
1.3.6.1.4.1.12148.10.4.26.13ScalargseGeneratorFuelTankLevelLowread-onlycurrent
1.3.6.1.4.1.12148.10.4.26.14ScalargseGeneratorFuelTankLossread-onlycurrent
1.3.6.1.4.1.12148.10.4.26.15ScalargseGeneratorRMSCommunicationFailureread-onlycurrent
1.3.6.1.4.1.12148.10.4.26.16ScalargseGeneratorOtherAlarmsread-onlycurrent
1.3.6.1.4.1.12148.10.4.27NodegeneratorFailure
1.3.6.1.4.1.12148.10.4.27.1ScalargeneratorFailureStatusread-onlycurrentThis status value shows if the number of failed phases is higher than the defined alarm level.
1.3.6.1.4.1.12148.10.4.27.2ScalargeneratorFailureDescriptionread-writecurrentA textual description of the generator failure monitor. This is stored in the system controller and can be changed by the user.
1.3.6.1.4.1.12148.10.4.27.3ScalargeneratorFailureTrapRepeatCounteraccessible-for-notifycurrentThe number of consecutive times this alam condition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this tr…
1.3.6.1.4.1.12148.10.4.27.4ScalargeneratorFailureAlarmEnableread-writecurrentThis value once enabled, the alarm condition of the monitor will be reported.
1.3.6.1.4.1.12148.10.4.27.5ScalargeneratorFailureValueread-onlycurrentThe value of the monitor.
1.3.6.1.4.1.12148.10.5Noderectifiers
1.3.6.1.4.1.12148.10.5.1ScalarrectifiersStatusread-onlycurrentThe overall status of rectifier subsystem.
1.3.6.1.4.1.12148.10.5.2NoderectifiersCurrent
1.3.6.1.4.1.12148.10.5.2.1ScalarrectifiersCurrentStatusread-onlycurrentThe status of the measured total rectifier current.
1.3.6.1.4.1.12148.10.5.2.2ScalarrectifiersCurrentDescriptionread-writecurrentA textual description of the total rectifier current monitor. This is stored in the system controller and can be changed by the user
1.3.6.1.4.1.12148.10.5.2.3ScalarrectifiersCurrentTrapRepeatCounteraccessible-for-notifycurrentThe number of consecutive times this alamcondition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this tra…
1.3.6.1.4.1.12148.10.5.2.4ScalarrectifiersCurrentAlarmEnableread-writecurrentThis value once enabled, the alarm condition of the monitor will be reported.
1.3.6.1.4.1.12148.10.5.2.5ScalarrectifiersCurrentValueread-onlycurrentThe value of the measured total rectifier current.
1.3.6.1.4.1.12148.10.5.2.6ScalarrectifiersCurrentMajorAlarmLevelread-writecurrentThe major alarm limit
1.3.6.1.4.1.12148.10.5.2.7ScalarrectifiersCurrentMinorAlarmLevelread-writecurrentThe minor alarm limit
1.3.6.1.4.1.12148.10.5.3NoderectifiersCapacity
1.3.6.1.4.1.12148.10.5.3.1ScalarrectifiersCapacityStatusread-onlycurrentThe status of the measured used rectifier capacity.
1.3.6.1.4.1.12148.10.5.3.2ScalarrectifiersCapacityDescriptionread-writecurrentA textual description of the used rectifier capacity monitor. This is stored in the system controller and can be changed by the user
1.3.6.1.4.1.12148.10.5.3.3ScalarrectifiersCapacityTrapRepeatCounteraccessible-for-notifycurrentThe number of consecutive times this alamcondition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this tra…
1.3.6.1.4.1.12148.10.5.3.4ScalarrectifiersCapacityAlarmEnableread-writecurrentThis value once enabled, the alarm condition of the monitor will be reported.
1.3.6.1.4.1.12148.10.5.3.5ScalarrectifiersCapacityValueread-onlycurrentThe used rectifier capacity value presented in percentage of the total installed rectifier capacity.
1.3.6.1.4.1.12148.10.5.3.6ScalarrectifiersCapacityMajorAlarmLevelread-writecurrentThe major alarm limit
1.3.6.1.4.1.12148.10.5.3.7ScalarrectifiersCapacityMinorAlarmLevelread-writecurrentThe minor alarm limit
1.3.6.1.4.1.12148.10.5.4NoderectifiersError
1.3.6.1.4.1.12148.10.5.4.1ScalarrectifiersErrorStatusread-onlycurrentThis status value shows if the number of failed units is higher than the defined alarm level.
1.3.6.1.4.1.12148.10.5.4.2ScalarrectifiersErrorDescriptionread-writecurrentA textual description of the rectifier error monitor. This is stored in the system controller and can be changed by the user
1.3.6.1.4.1.12148.10.5.4.3ScalarrectifiersErrorTrapRepeatCounteraccessible-for-notifycurrentThe number of consecutive times this alamcondition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this tra…
1.3.6.1.4.1.12148.10.5.4.4ScalarrectifiersErrorEnableread-writecurrentThis value once enabled, the alarm condition of the monitor will be reported.
1.3.6.1.4.1.12148.10.5.4.5ScalarrectifiersErrorValueread-onlycurrentThe number of failed rectifiers.
1.3.6.1.4.1.12148.10.5.4.6ScalarrectifiersErrorMajorAlarmLevelread-writecurrentThe major alarm limit
1.3.6.1.4.1.12148.10.5.4.7ScalarrectifiersErrorMinorAlarmLevelread-writecurrentThe minor alarm limit
1.3.6.1.4.1.12148.10.5.5ScalarrectifiersNumberOfRectifiersread-writecurrentNumber of installed rectifiers.
1.3.6.1.4.1.12148.10.5.6TablerectifierTablenot-accessiblecurrentThis table shows the information of each rectifier installed in the system.
1.3.6.1.4.1.12148.10.5.6.1RowrectifierEntrynot-accessiblecurrent
1.3.6.1.4.1.12148.10.5.6.1.1ColumnrectifierIndexnot-accessiblecurrentIndex used for navigating the rows 1..100 of rectifierTable
1.3.6.1.4.1.12148.10.5.6.1.2ColumnrectifierStatusread-onlycurrentThe overall status of rectifier.
1.3.6.1.4.1.12148.10.5.6.1.3ColumnrectifierOutputCurrentValueread-onlycurrentThe output current value of rectifier.
1.3.6.1.4.1.12148.10.5.6.1.4ColumnrectifierInputVoltageValueread-onlycurrentThe input voltage value of rectifier.
1.3.6.1.4.1.12148.10.5.6.1.5ColumnrectifierTyperead-onlycurrentType of rectifier
1.3.6.1.4.1.12148.10.5.6.1.6ColumnrectifierHwPartNumberread-onlycurrentHardware part number of rectifier
1.3.6.1.4.1.12148.10.5.6.1.7ColumnrectifierHwVersionread-onlycurrentHardware version number of rectifier
1.3.6.1.4.1.12148.10.5.6.1.8ColumnrectifierSwPartNumberread-onlycurrentPart number of secondary software in rectifier
1.3.6.1.4.1.12148.10.5.6.1.9ColumnrectifierSwVersionread-onlycurrentVersion number of secondary software in rectifier
1.3.6.1.4.1.12148.10.5.6.1.10ColumnrectifierSerialNumberread-onlycurrentSerial number of rectifier
1.3.6.1.4.1.12148.10.5.7NoderectifiersEnergyLog
1.3.6.1.4.1.12148.10.5.7.1ScalarrectifiersEnergyLogAccumulatedread-onlycurrentThis is the accumulated energy delivered from rectifiers.
1.3.6.1.4.1.12148.10.5.7.2ScalarrectifiersEnergyLogLastHoursNumberOfEntriesread-onlycurrentThis is the maximal number of entries stored in rectifier hourly energy log.
1.3.6.1.4.1.12148.10.5.7.3TablerectifiersEnergyLogLastHoursTablenot-accessiblecurrentThis table contains hourly energy log of rectifiers.
1.3.6.1.4.1.12148.10.5.7.3.1RowrectifiersEnergyLogLastHoursEntrynot-accessiblecurrent
1.3.6.1.4.1.12148.10.5.7.3.1.1ColumnrectifiersEnergyLogLastHoursIndexnot-accessiblecurrentIndex used for navigating the rows 1..52 of rectifiersEnergyLogLastHoursTable
1.3.6.1.4.1.12148.10.5.7.3.1.2ColumnrectifiersEnergyLogLastHoursValueread-onlycurrentEnergy value logged every hour.
1.3.6.1.4.1.12148.10.5.7.4ScalarrectifiersEnergyLogLastDaysNumberOfEntriesread-onlycurrentThis is the maximal number of entries stored in rectifier daily energy log.
1.3.6.1.4.1.12148.10.5.7.5TablerectifiersEnergyLogLastDaysTablenot-accessiblecurrentThis table contains daily energy log of rectifiers.
1.3.6.1.4.1.12148.10.5.7.5.1RowrectifiersEnergyLogLastDaysEntrynot-accessiblecurrent
1.3.6.1.4.1.12148.10.5.7.5.1.1ColumnrectifiersEnergyLogLastDaysIndexnot-accessiblecurrentIndex used for navigating the rows 1..52 of rectifiersEnergyLogLastDaysTable
1.3.6.1.4.1.12148.10.5.7.5.1.2ColumnrectifiersEnergyLogLastDaysValueread-onlycurrentEnergy value logged every day.
1.3.6.1.4.1.12148.10.5.7.6ScalarrectifiersEnergyLogLastWeeksNumberOfEntriesread-onlycurrentThis is the maximal number of entries stored in rectifier weekly energy log.
1.3.6.1.4.1.12148.10.5.7.7TablerectifiersEnergyLogLastWeeksTablenot-accessiblecurrentThis table contains weekly energy log of rectifiers.
1.3.6.1.4.1.12148.10.5.7.7.1RowrectifiersEnergyLogLastWeeksEntrynot-accessiblecurrent
1.3.6.1.4.1.12148.10.5.7.7.1.1ColumnrectifiersEnergyLogLastWeeksIndexnot-accessiblecurrentIndex used for navigating the rows 1..52 of rectifiersEnergyLogLastWeekTable
1.3.6.1.4.1.12148.10.5.7.7.1.2ColumnrectifiersEnergyLogLastWeeksValueread-onlycurrentEnergy value logged every week.
1.3.6.1.4.1.12148.10.5.8ScalarrectifiersNumberOfGroupsread-onlycurrentNumber of rectifier groups
1.3.6.1.4.1.12148.10.5.9TablerectifierGroupsTablenot-accessiblecurrentThis table contains status and the number of installed rectifiers of each rectifier groups.
1.3.6.1.4.1.12148.10.5.9.1RowrectifierGroupsEntrynot-accessiblecurrent
1.3.6.1.4.1.12148.10.5.9.1.1ColumnrectifierGroupIndexnot-accessiblecurrentIndex used for navigating the rows 1..10 of rectifierGroupsTable
1.3.6.1.4.1.12148.10.5.9.1.2ColumnrectifierGroupStatusread-onlycurrentThe status of each rectifier group.
1.3.6.1.4.1.12148.10.5.9.1.3ColumnrectifierGroupNumberOfRectifiersread-writecurrentNumber of installed rectifiers in each rectifier groups
1.3.6.1.4.1.12148.10.5.10TablerectifierGroupCurrentTablenot-accessiblecurrentThis table contains information about the total rectifier current of each rectifier groups, which is calculated by summing up current from each rectifier in a …
1.3.6.1.4.1.12148.10.5.10.1RowrectifierGroupCurrentEntrynot-accessiblecurrent
1.3.6.1.4.1.12148.10.5.10.1.1ColumnrectifierGroupCurrentStatusread-onlycurrentThe status of the measured total rectifier current of the rectifier group
1.3.6.1.4.1.12148.10.5.10.1.2ColumnrectifierGroupCurrentDescriptionread-writecurrentA textual description of the total rectifier current monitor of a rectifier group. This is stored in the system controller and can be changed by the user
1.3.6.1.4.1.12148.10.5.10.1.3ColumnrectifierGroupCurrentTrapRepeatCounteraccessible-for-notifycurrentThe number of consecutive times this alamcondition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this tra…
1.3.6.1.4.1.12148.10.5.10.1.4ColumnrectifierGroupCurrentAlarmEnableread-writecurrentThis value once enabled, the alarm condition of the monitor will be reported.
1.3.6.1.4.1.12148.10.5.10.1.5ColumnrectifierGroupCurrentValueread-onlycurrentThe value of the measured total rectifier current of each rectifier group.
1.3.6.1.4.1.12148.10.5.10.1.6ColumnrectifierGroupCurrentMajorAlarmLevelread-writecurrentThe major alarm limit
1.3.6.1.4.1.12148.10.5.10.1.7ColumnrectifierGroupCurrentMinorAlarmLevelread-writecurrentThe minor alarm limit
1.3.6.1.4.1.12148.10.5.11TablerectifierGroupCapacityTablenot-accessiblecurrentThis table contains information about the used rectifier capacity of each rectifier group.
1.3.6.1.4.1.12148.10.5.11.1RowrectifierGroupCapacityEntrynot-accessiblecurrent
1.3.6.1.4.1.12148.10.5.11.1.1ColumnrectifierGroupCapacityStatusread-onlycurrentThe status of the measured used rectifier capacity of each rectifier group
1.3.6.1.4.1.12148.10.5.11.1.2ColumnrectifierGroupCapacityDescriptionread-writecurrentA textual description of the used rectifier capacity monitor of each rectifier group. This is stored in the system controller and can be changed by the user
1.3.6.1.4.1.12148.10.5.11.1.3ColumnrectifierGroupCapacityTrapRepeatCounteraccessible-for-notifycurrentThe number of consecutive times this alamcondition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this tra…
1.3.6.1.4.1.12148.10.5.11.1.4ColumnrectifierGroupCapacityAlarmEnableread-writecurrentThis value once enabled, the alarm condition of the monitor will be reported.
1.3.6.1.4.1.12148.10.5.11.1.5ColumnrectifierGroupCapacityValueread-onlycurrentThe used rectifier capacity value presented in percentage of the total installed rectifier capacity of each rectifier group.
1.3.6.1.4.1.12148.10.5.11.1.6ColumnrectifierGroupCapacityMajorAlarmLevelread-writecurrentThe major alarm limit
1.3.6.1.4.1.12148.10.5.11.1.7ColumnrectifierGroupCapacityMinorAlarmLevelread-writecurrentThe minor alarm limit
1.3.6.1.4.1.12148.10.5.12TablerectifierGroupErrorTablenot-accessiblecurrentThis table contains information about the rectifier error monitor of each rectifier group.
1.3.6.1.4.1.12148.10.5.12.1RowrectifierGroupErrorEntrynot-accessiblecurrent
1.3.6.1.4.1.12148.10.5.12.1.1ColumnrectifierGroupErrorStatusread-onlycurrentThis status value shows if the number of failed units is higher than the defined alarm level.
1.3.6.1.4.1.12148.10.5.12.1.2ColumnrectifierGroupErrorDescriptionread-writecurrentA textual description of the rectifier error monitor of each rectifier group. This is stored in the system controller and can be changed by the user
1.3.6.1.4.1.12148.10.5.12.1.3ColumnrectifierGroupErrorTrapRepeatCounteraccessible-for-notifycurrentThe number of consecutive times this alamcondition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this tra…
1.3.6.1.4.1.12148.10.5.12.1.4ColumnrectifierGroupErrorAlarmEnableread-writecurrentThis value once enabled, the alarm condition of the monitor will be reported.
1.3.6.1.4.1.12148.10.5.12.1.5ColumnrectifierGroupErrorValueread-onlycurrentThe number of failed rectifiers of each rectifier group.
1.3.6.1.4.1.12148.10.5.12.1.6ColumnrectifierGroupErrorMajorAlarmLevelread-writecurrentThe major alarm limit
1.3.6.1.4.1.12148.10.5.12.1.7ColumnrectifierGroupErrorMinorAlarmLevelread-writecurrentThe minor alarm limit
1.3.6.1.4.1.12148.10.5.13TablerectifierGroupRectifierTablenot-accessiblecurrentThis table shows the information of each rectifier installed in each of the rectifier group in the system.
1.3.6.1.4.1.12148.10.5.13.1RowrectifierGroupRectifierEntrynot-accessiblecurrent
1.3.6.1.4.1.12148.10.5.13.1.1ColumnrectifierGroupRectifierIndexnot-accessiblecurrentIndex used for navigating the rows 1..100 of rectifierGroupRectifierTable
1.3.6.1.4.1.12148.10.5.13.1.2ColumnrectifierGroupRectifierStatusread-onlycurrentThe overall status of rectifier.
1.3.6.1.4.1.12148.10.5.13.1.3ColumnrectifierGroupRectifierOutputCurrentValueread-onlycurrentThe output current value of rectifier.
1.3.6.1.4.1.12148.10.5.13.1.4ColumnrectifierGroupRectifierInputVoltageValueread-onlycurrentThe input voltage value of rectifier.
1.3.6.1.4.1.12148.10.5.13.1.5ColumnrectifierGroupRectifierTyperead-onlycurrentType of rectifier
1.3.6.1.4.1.12148.10.5.13.1.6ColumnrectifierGroupRectifierHwPartNumberread-onlycurrentHardware part number of rectifier
1.3.6.1.4.1.12148.10.5.13.1.7ColumnrectifierGroupRectifierHwVersionread-onlycurrentHardware version number of rectifier
1.3.6.1.4.1.12148.10.5.13.1.8ColumnrectifierGroupRectifierSwPartNumberread-onlycurrentPart number of secondary software in rectifier
1.3.6.1.4.1.12148.10.5.13.1.9ColumnrectifierGroupRectifierSwVersionread-onlycurrentVersion number of secondary software in rectifier
1.3.6.1.4.1.12148.10.5.14TablerectifierGroupEnergyLogTablenot-accessiblecurrentThis branch contains information about rectifiers' energy logs of each rectifier group.
1.3.6.1.4.1.12148.10.5.14.1RowrectifierGroupEnergyLogEntrynot-accessiblecurrent
1.3.6.1.4.1.12148.10.5.14.1.1ColumnrectifierGroupEnergyLogAccumulatedread-onlycurrentThis is the accumulated energy delivered from rectifiers of each rectifier group.
1.3.6.1.4.1.12148.10.5.14.1.2ColumnrectifierGroupEnergyLogLastHoursNumberOfEntriesread-onlycurrentThis is the maximal number of entries stored in rectifier group hourly energy log.
1.3.6.1.4.1.12148.10.5.14.1.3ColumnrectifierGroupEnergyLogLastDaysNumberOfEntriesread-onlycurrentThis is the maximal number of entries stored in rectifier group daily energy log.
1.3.6.1.4.1.12148.10.5.14.1.4ColumnrectifierGroupEnergyLogLastWeeksNumberOfEntriesread-onlycurrentThis is the maximal number of entries stored in rectifier group weekly energy log.
1.3.6.1.4.1.12148.10.5.15TablerectifierGroupEnergyLogLastHoursTablenot-accessiblecurrentThis table contains hourly energy log of each rectifier group
1.3.6.1.4.1.12148.10.5.15.1RowrectifierGroupEnergyLogLastHoursEntrynot-accessiblecurrent
1.3.6.1.4.1.12148.10.5.15.1.1ColumnrectifierGroupEnergyLogLastHoursIndexnot-accessiblecurrentIndex used for navigating the rows 1..52 of rectifierGroupEnergyLogLastHoursTable
1.3.6.1.4.1.12148.10.5.15.1.2ColumnrectifierGroupEnergyLogLastHoursValueread-onlycurrentEnergy value logged every hour.
1.3.6.1.4.1.12148.10.5.16TablerectifierGroupEnergyLogLastDaysTablenot-accessiblecurrentThis table contains daily energy log of each rectifier group
1.3.6.1.4.1.12148.10.5.16.1RowrectifierGroupEnergyLogLastDaysEntrynot-accessiblecurrent
1.3.6.1.4.1.12148.10.5.16.1.1ColumnrectifierGroupEnergyLogLastDaysIndexnot-accessiblecurrentIndex used for navigating the rows 1..52 of rectifierGroupEnergyLogLasDaysTable
1.3.6.1.4.1.12148.10.5.16.1.2ColumnrectifierGroupEnergyLogLastDaysValueread-onlycurrentEnergy value logged every day.
1.3.6.1.4.1.12148.10.5.17TablerectifierGroupEnergyLogLastWeeksTablenot-accessiblecurrentThis table contains weekly energy log of each rectifier group
1.3.6.1.4.1.12148.10.5.17.1RowrectifierGroupEnergyLogLastWeeksEntrynot-accessiblecurrent
1.3.6.1.4.1.12148.10.5.17.1.1ColumnrectifierGroupEnergyLogLastWeeksIndexnot-accessiblecurrentIndex used for navigating the rows 1..52 of rectifierGroupEnergyLogLastWeeksTable
1.3.6.1.4.1.12148.10.5.17.1.2ColumnrectifierGroupEnergyLogLastWeeksValueread-onlycurrentEnergy value logged every week.
1.3.6.1.4.1.12148.10.5.18NoderectifiersTemperature
1.3.6.1.4.1.12148.10.5.18.1ScalarrectifiersTemperatureStatusread-onlycurrentThe state of the rectifier temperature can be either one of the defined enumerated values
1.3.6.1.4.1.12148.10.5.18.2ScalarrectifiersTemperatureDescriptionread-writecurrentA textual description of the rectifier temperature monitor. This is stored in the system controller and can be changed by the user.
1.3.6.1.4.1.12148.10.5.18.3ScalarrectifiersTemperatureTrapRepeatCounteraccessible-for-notifycurrentThe number of consecutive times this alamcondition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this tra…
1.3.6.1.4.1.12148.10.5.18.4ScalarrectifiersTemperatureAlarmEnableread-writecurrentThis value once enabled, the alarm condition of the monitor will be reported.
1.3.6.1.4.1.12148.10.5.18.5ScalarrectifiersTemperatureValueread-onlycurrentThe highest value of the rectifier temperature measurements. Depending on the global setting in the Control unit, this value will be presented in Celsius or Fa…
1.3.6.1.4.1.12148.10.5.18.6ScalarrectifiersTemperatureMajorHighLevelread-writecurrentThe major high alarm limit
1.3.6.1.4.1.12148.10.5.18.7ScalarrectifiersTemperatureMinorHighLevelread-writecurrentThe minor high alarm limit
1.3.6.1.4.1.12148.10.5.18.8ScalarrectifiersTemperatureMinorLowLevelread-writecurrentThe minor low alarm limit
1.3.6.1.4.1.12148.10.5.18.9ScalarrectifiersTemperatureMajorLowLevelread-writecurrentThe major low alarm limit
1.3.6.1.4.1.12148.10.5.19TablerectifierGroupTemperatureTablenot-accessiblecurrentThis table contains information about the highest rectifier temperature of each rectifier groups, which is calculated by summing up current from each rectifier…
1.3.6.1.4.1.12148.10.5.19.1RowrectifierGroupTemperatureEntrynot-accessiblecurrent
1.3.6.1.4.1.12148.10.5.19.1.1ColumnrectifierGroupTemperatureStatusread-onlycurrentThe status of the measured highest rectifier temperature of the rectifier group
1.3.6.1.4.1.12148.10.5.19.1.2ColumnrectifierGroupTemperatureDescriptionread-writecurrentA textual description of the highest rectifier temperature monitor of a rectifier group. This is stored in the system controller and can be changed by the user
1.3.6.1.4.1.12148.10.5.19.1.3ColumnrectifierGroupTemperatureTrapRepeatCounteraccessible-for-notifycurrentThe number of consecutive times this alamcondition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this tra…
1.3.6.1.4.1.12148.10.5.19.1.4ColumnrectifierGroupTemperatureAlarmEnableread-writecurrentThis value once enabled, the alarm condition of the monitor will be reported.
1.3.6.1.4.1.12148.10.5.19.1.5ColumnrectifierGroupTemperatureValueread-onlycurrentThe value of the measured highest rectifier temperature of each rectifier group.
1.3.6.1.4.1.12148.10.5.19.1.6ColumnrectifierGroupTemperatureMajorHighLevelread-writecurrentThe major high alarm limit
1.3.6.1.4.1.12148.10.5.19.1.7ColumnrectifierGroupTemperatureMinorHighLevelread-writecurrentThe minor high alarm limit
1.3.6.1.4.1.12148.10.5.19.1.8ColumnrectifierGroupTemperatureMinorLowLevelread-writecurrentThe minor low alarm limit
1.3.6.1.4.1.12148.10.5.19.1.9ColumnrectifierGroupTemperatureMajorLowLevelread-writecurrentThe major low alarm limit
1.3.6.1.4.1.12148.10.5.20ScalarrectifiersCurrentLimitEnableread-writecurrentEnable/disable current limit
1.3.6.1.4.1.12148.10.5.21ScalarrectifiersCurrentLimitValueread-writecurrentCurrent limit value
1.3.6.1.4.1.12148.10.6Nodedcdc
1.3.6.1.4.1.12148.10.6.1ScalardcdcNumberOfGroupsread-onlycurrentNumber of dcdc groups
1.3.6.1.4.1.12148.10.6.2TabledcdcGroupsTablenot-accessiblecurrentThis table contains information about dcdc groups.
1.3.6.1.4.1.12148.10.6.2.1RowdcdcGroupsEntrynot-accessiblecurrent
1.3.6.1.4.1.12148.10.6.2.1.1ColumndcdcGroupIndexnot-accessiblecurrent
1.3.6.1.4.1.12148.10.6.2.1.2ColumndcdcGroupStatusread-onlycurrentThe overall status of dcdc group.
1.3.6.1.4.1.12148.10.6.2.1.3ColumndcdcGroupNumberOfDcdcConvertersread-writecurrentNumber of installed dcdc converters.
1.3.6.1.4.1.12148.10.6.2.1.4ColumndcdcGroupOutputVoltageread-writecurrentOutput voltage of dcdc converters
1.3.6.1.4.1.12148.10.6.2.1.5ColumndcdcNumberOfCurrentsread-onlycurrentNumber of dcdc currents
1.3.6.1.4.1.12148.10.6.2.1.6ColumndcdcNumberOfCapacitiesread-onlycurrentNumber of dcdc capacities
1.3.6.1.4.1.12148.10.6.2.1.7ColumndcdcNumberOfAlarmsread-onlycurrentNumber of dcdc alarms
1.3.6.1.4.1.12148.10.6.3TabledcdcCurrentTablenot-accessiblecurrentThis table contains information about the total dcdc current.
1.3.6.1.4.1.12148.10.6.3.1RowdcdcCurrentEntrynot-accessiblecurrent
1.3.6.1.4.1.12148.10.6.3.1.1ColumndcdcCurrentStatusread-onlycurrentThe status of the measured total dcdc current.
1.3.6.1.4.1.12148.10.6.3.1.2ColumndcdcCurrentDescriptionread-writecurrentA textual description of the total dcdc current monitor. This is stored in the system controller and can be changed by the user
1.3.6.1.4.1.12148.10.6.3.1.3ColumndcdcCurrentTrapRepeatCounteraccessible-for-notifycurrentThe number of consecutive times this alamcondition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this tra…
1.3.6.1.4.1.12148.10.6.3.1.4ColumndcdcCurrentAlarmEnableread-writecurrentThis value once enabled, the alarm condition of the monitor will be reported.
1.3.6.1.4.1.12148.10.6.3.1.5ColumndcdcCurrentValueread-onlycurrentThe value of the measured total dcdc current.
1.3.6.1.4.1.12148.10.6.3.1.6ColumndcdcCurrentMajorAlarmLevelread-writecurrentThe major alarm limit
1.3.6.1.4.1.12148.10.6.3.1.7ColumndcdcCurrentMinorAlarmLevelread-writecurrentThe minor alarm limit
1.3.6.1.4.1.12148.10.6.4TabledcdcCapacityTablenot-accessiblecurrentThis table contains information about the used dcdc capacity.
1.3.6.1.4.1.12148.10.6.4.1RowdcdcCapacityEntrynot-accessiblecurrent
1.3.6.1.4.1.12148.10.6.4.1.1ColumndcdcCapacityStatusread-onlycurrentThe status of the measured used dcdc capacity.
1.3.6.1.4.1.12148.10.6.4.1.2ColumndcdcCapacityDescriptionread-writecurrentA textual description of the used dcdc capacity monitor. This is stored in the system controller and can be changed by the user
1.3.6.1.4.1.12148.10.6.4.1.3ColumndcdcCapacityTrapRepeatCounteraccessible-for-notifycurrentThe number of consecutive times this alamcondition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this tra…
1.3.6.1.4.1.12148.10.6.4.1.4ColumndcdcCapacityAlarmEnableread-writecurrentThis value once enabled, the alarm condition of the monitor will be reported.
1.3.6.1.4.1.12148.10.6.4.1.5ColumndcdcCapacityValueread-onlycurrentThe used dcdc capacity value presented in percentage of the total installed dcdc capacity.
1.3.6.1.4.1.12148.10.6.4.1.6ColumndcdcCapacityMajorAlarmLevelread-writecurrentThe major alarm limit
1.3.6.1.4.1.12148.10.6.4.1.7ColumndcdcCapacityMinorAlarmLevelread-writecurrentThe minor alarm limit
1.3.6.1.4.1.12148.10.6.5TabledcdcTablenot-accessiblecurrentThis table shows the information of each dcdc converter installed in the system.
1.3.6.1.4.1.12148.10.6.5.1RowdcdcEntrynot-accessiblecurrent
1.3.6.1.4.1.12148.10.6.5.1.1ColumndcdcIndexnot-accessiblecurrentIndex used for navigating the rows 1..100 of dcdcTable
1.3.6.1.4.1.12148.10.6.5.1.2ColumndcdcStatusread-onlycurrentThe overall status of dcdc converter
1.3.6.1.4.1.12148.10.6.5.1.3ColumndcdcOutputCurrentValueread-onlycurrentThe output current value of dcdc.
1.3.6.1.4.1.12148.10.6.5.1.4ColumndcdcInputVoltageValueread-onlycurrentThe input voltage value of dcdc.
1.3.6.1.4.1.12148.10.6.5.1.5ColumndcdcTyperead-onlycurrentType of dcdc converter
1.3.6.1.4.1.12148.10.6.5.1.6ColumndcdcHwPartNumberread-onlycurrentHardware part number of dcdc converter
1.3.6.1.4.1.12148.10.6.5.1.7ColumndcdcHwVersionread-onlycurrentHardware version number of dcdc converter
1.3.6.1.4.1.12148.10.6.5.1.8ColumndcdcSwPartNumberread-onlycurrentPart number of secondary software in dcdc converter
1.3.6.1.4.1.12148.10.6.5.1.9ColumndcdcSwVersionread-onlycurrentVersion number of secondary software in dcdc converter
1.3.6.1.4.1.12148.10.6.6TabledcdcErrorTablenot-accessiblecurrentThis table contains information about the dcdc error monitor.
1.3.6.1.4.1.12148.10.6.6.1RowdcdcErrorEntrynot-accessiblecurrent
1.3.6.1.4.1.12148.10.6.6.1.1ColumndcdcErrorStatusread-onlycurrentThis status value shows if the number of failed units is higher than the defined alarm level.
1.3.6.1.4.1.12148.10.6.6.1.2ColumndcdcErrorDescriptionread-writecurrentA textual description of the dcdc error monitor. This is stored in the system controller and can be changed by the user
1.3.6.1.4.1.12148.10.6.6.1.3ColumndcdcErrorTrapRepeatCounteraccessible-for-notifycurrentThe number of consecutive times this alamcondition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this tra…
1.3.6.1.4.1.12148.10.6.6.1.4ColumndcdcErrorEnableread-writecurrentThis value once enabled, the alarm condition of the monitor will be reported.
1.3.6.1.4.1.12148.10.6.6.1.5ColumndcdcErrorValueread-onlycurrentThe number of failed dcdc converters.
1.3.6.1.4.1.12148.10.6.6.1.6ColumndcdcErrorMajorAlarmLevelread-writecurrentThe major alarm limit
1.3.6.1.4.1.12148.10.6.6.1.7ColumndcdcErrorMinorAlarmLevelread-writecurrentThe minor alarm limit
1.3.6.1.4.1.12148.10.6.7NodedcdcObsolete
1.3.6.1.4.1.12148.10.7NodesolarChargers
1.3.6.1.4.1.12148.10.7.1ScalarsolarChargersStatusread-onlycurrentThe overall status of solar charger subsystem.
1.3.6.1.4.1.12148.10.7.2NodesolarChargersCurrent
1.3.6.1.4.1.12148.10.7.2.1ScalarsolarChargersCurrentStatusread-onlycurrentThe status of the measured total solar current.
1.3.6.1.4.1.12148.10.7.2.2ScalarsolarChargersCurrentDescriptionread-writecurrentA textual description of the total solar current monitor. This is stored in the system controller and can be changed by the user
1.3.6.1.4.1.12148.10.7.2.3ScalarsolarChargersCurrentTrapRepeatCounteraccessible-for-notifycurrentThe number of consecutive times this alamcondition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this tra…
1.3.6.1.4.1.12148.10.7.2.4ScalarsolarChargersCurrentAlarmEnableread-writecurrentThis value once enabled, the alarm condition of the monitor will be reported.
1.3.6.1.4.1.12148.10.7.2.5ScalarsolarChargersCurrentValueread-onlycurrentThe value of the measured total solar current.
1.3.6.1.4.1.12148.10.7.2.6ScalarsolarChargersCurrentMajorAlarmLevelread-writecurrentThe major alarm limit
1.3.6.1.4.1.12148.10.7.2.7ScalarsolarChargersCurrentMinorAlarmLevelread-writecurrentThe minor alarm limit
1.3.6.1.4.1.12148.10.7.3NodesolarChargersObsolete
1.3.6.1.4.1.12148.10.7.4NodesolarChargersError
1.3.6.1.4.1.12148.10.7.4.1ScalarsolarChargersErrorStatusread-onlycurrentThis status value shows if the number of failed units is higher than the defined alarm level.
1.3.6.1.4.1.12148.10.7.4.2ScalarsolarChargersErrorDescriptionread-writecurrentA textual description of the solar error monitor. This is stored in the system controller and can be changed by the user
1.3.6.1.4.1.12148.10.7.4.3ScalarsolarChargersErrorTrapRepeatCounteraccessible-for-notifycurrentThe number of consecutive times this alamcondition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this tra…
1.3.6.1.4.1.12148.10.7.4.4ScalarsolarChargersErrorEnableread-writecurrentThis value once enabled, the alarm condition of the monitor will be reported.
1.3.6.1.4.1.12148.10.7.4.5ScalarsolarChargersErrorValueread-onlycurrentThe number of failed solar chargers.
1.3.6.1.4.1.12148.10.7.4.6ScalarsolarChargersErrorMajorAlarmLevelread-writecurrentThe major alarm limit
1.3.6.1.4.1.12148.10.7.4.7ScalarsolarChargersErrorMinorAlarmLevelread-writecurrentThe minor alarm limit
1.3.6.1.4.1.12148.10.7.5ScalarsolarChargersNumberOfSolarChargersread-writecurrentNumber of installed solar chargers.
1.3.6.1.4.1.12148.10.7.6TablesolarChargerTablenot-accessiblecurrentThis table shows the information of each solar charger installed in the system.
1.3.6.1.4.1.12148.10.7.6.1RowsolarChargerEntrynot-accessiblecurrent
1.3.6.1.4.1.12148.10.7.6.1.1ColumnsolarChargerIndexnot-accessiblecurrentIndex used for navigating the rows 1..100 of solarChargerTable
1.3.6.1.4.1.12148.10.7.6.1.2ColumnsolarChargerStatusread-onlycurrentThe overall status of solar charger.
1.3.6.1.4.1.12148.10.7.6.1.3ColumnsolarChargerOutputCurrentValueread-onlycurrentThe output current value of solar charger.
1.3.6.1.4.1.12148.10.7.6.1.4ColumnsolarChargerInputVoltageValueread-onlycurrentThe input voltage value of solar charger.
1.3.6.1.4.1.12148.10.7.6.1.5ColumnsolarChargerTyperead-onlycurrentType of solar charger
1.3.6.1.4.1.12148.10.7.6.1.6ColumnsolarChargerHwPartNumberread-onlycurrentHardware part number of solar charger
1.3.6.1.4.1.12148.10.7.6.1.7ColumnsolarChargerHwVersionread-onlycurrentHardware version number of solar charger
1.3.6.1.4.1.12148.10.7.6.1.8ColumnsolarChargerSwPartNumberread-onlycurrentPart number of secondary software in solar charger
1.3.6.1.4.1.12148.10.7.6.1.9ColumnsolarChargerSwVersionread-onlycurrentVersion number of secondary software in solar charger
1.3.6.1.4.1.12148.10.7.7NodesolarChargersEnergyLog
1.3.6.1.4.1.12148.10.7.7.1ScalarsolarChargersEnergyLogAccumulatedread-onlycurrentThis is the accumulated energy delivered from solar chargers.
1.3.6.1.4.1.12148.10.7.7.2ScalarsolarChargersEnergyLogLastHoursNumberOfEntriesread-onlycurrentThis is the maximal number of entries stored in solar charger hourly energy log.
1.3.6.1.4.1.12148.10.7.7.3TablesolarChargersEnergyLogLastHoursTablenot-accessiblecurrentThis table contains hourly energy log of solar chargers.
1.3.6.1.4.1.12148.10.7.7.3.1RowsolarChargersEnergyLogLastHoursEntrynot-accessiblecurrent
1.3.6.1.4.1.12148.10.7.7.3.1.1ColumnsolarChargersEnergyLogLastHoursIndexnot-accessiblecurrentIndex used for navigating the rows 1..52 of solarChargersEnergyLogLastHoursTable
1.3.6.1.4.1.12148.10.7.7.3.1.2ColumnsolarChargersEnergyLogLastHoursValueread-onlycurrentEnergy value logged every hour.
1.3.6.1.4.1.12148.10.7.7.4ScalarsolarChargersEnergyLogLastDaysNumberOfEntriesread-onlycurrentThis is the maximal number of entries stored in solar charger daily energy log.
1.3.6.1.4.1.12148.10.7.7.5TablesolarChargersEnergyLogLastDaysTablenot-accessiblecurrentThis table contains daily energy log of solar chargers.
1.3.6.1.4.1.12148.10.7.7.5.1RowsolarChargersEnergyLogLastDaysEntrynot-accessiblecurrent
1.3.6.1.4.1.12148.10.7.7.5.1.1ColumnsolarChargersEnergyLogLastDaysIndexnot-accessiblecurrentIndex used for navigating the rows 1..52 of solarChargersEnergyLogLastDaysTable
1.3.6.1.4.1.12148.10.7.7.5.1.2ColumnsolarChargersEnergyLogLastDaysValueread-onlycurrentEnergy value logged every day.
1.3.6.1.4.1.12148.10.7.7.6ScalarsolarChargersEnergyLogLastWeeksNumberOfEntriesread-onlycurrentThis is the maximal number of entries stored in solar charger weekly energy log.
1.3.6.1.4.1.12148.10.7.7.7TablesolarChargersEnergyLogLastWeeksTablenot-accessiblecurrentThis table contains weekly energy log of solar chargers.
1.3.6.1.4.1.12148.10.7.7.7.1RowsolarChargersEnergyLogLastWeeksEntrynot-accessiblecurrent
1.3.6.1.4.1.12148.10.7.7.7.1.1ColumnsolarChargersEnergyLogLastWeeksIndexnot-accessiblecurrentIndex used for navigating the rows 1..52 of solarChargersEnergyLogLastWeekTable
1.3.6.1.4.1.12148.10.7.7.7.1.2ColumnsolarChargersEnergyLogLastWeeksValueread-onlycurrentEnergy value logged every week.
1.3.6.1.4.1.12148.10.7.8ScalarsolarChargersEarthFaultStatusread-onlycurrentThe status of solar charger's Earth Fault monitor
1.3.6.1.4.1.12148.10.8NodewindChargers
1.3.6.1.4.1.12148.10.8.1ScalarwindChargersStatusread-onlycurrentThe overall status of wind charger subsystem.
1.3.6.1.4.1.12148.10.8.2NodewindChargersCurrent
1.3.6.1.4.1.12148.10.8.2.1ScalarwindChargersCurrentStatusread-onlycurrentThe status of the measured total wind current.
1.3.6.1.4.1.12148.10.8.2.2ScalarwindChargersCurrentDescriptionread-writecurrentA textual description of the total wind current monitor. This is stored in the system controller and can be changed by the user
1.3.6.1.4.1.12148.10.8.2.3ScalarwindChargersCurrentTrapRepeatCounteraccessible-for-notifycurrentThe number of consecutive times this alamcondition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this tra…
1.3.6.1.4.1.12148.10.8.2.4ScalarwindChargersCurrentAlarmEnableread-writecurrentThis value once enabled, the alarm condition of the monitor will be reported.
1.3.6.1.4.1.12148.10.8.2.5ScalarwindChargersCurrentValueread-onlycurrentThe value of the measured total wind current.
1.3.6.1.4.1.12148.10.8.2.6ScalarwindChargersCurrentMajorAlarmLevelread-writecurrentThe major alarm limit
1.3.6.1.4.1.12148.10.8.2.7ScalarwindChargersCurrentMinorAlarmLevelread-writecurrentThe minor alarm limit
1.3.6.1.4.1.12148.10.8.3NodewindChargersObsolete
1.3.6.1.4.1.12148.10.8.4NodewindChargersError
1.3.6.1.4.1.12148.10.8.4.1ScalarwindChargersErrorStatusread-onlycurrentThis status value shows if the number of failed units is higher than the defined alarm level.
1.3.6.1.4.1.12148.10.8.4.2ScalarwindChargersErrorDescriptionread-writecurrentA textual description of the wind error monitor. This is stored in the system controller and can be changed by the user
1.3.6.1.4.1.12148.10.8.4.3ScalarwindChargersErrorTrapRepeatCounteraccessible-for-notifycurrentThe number of consecutive times this alamcondition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this tra…
1.3.6.1.4.1.12148.10.8.4.4ScalarwindChargersErrorEnableread-writecurrentThis value once enabled, the alarm condition of the monitor will be reported.
1.3.6.1.4.1.12148.10.8.4.5ScalarwindChargersErrorValueread-onlycurrentThe number of failed wind chargers.
1.3.6.1.4.1.12148.10.8.4.6ScalarwindChargersErrorMajorAlarmLevelread-writecurrentThe major alarm limit
1.3.6.1.4.1.12148.10.8.4.7ScalarwindChargersErrorMinorAlarmLevelread-writecurrentThe minor alarm limit
1.3.6.1.4.1.12148.10.8.5ScalarwindChargersNumberOfWindChargersread-writecurrentNumber of installed wind chargers.
1.3.6.1.4.1.12148.10.8.6TablewindChargerTablenot-accessiblecurrentThis table shows the information of each wind charger installed in the system.
1.3.6.1.4.1.12148.10.8.6.1RowwindChargerEntrynot-accessiblecurrent
1.3.6.1.4.1.12148.10.8.6.1.1ColumnwindChargerIndexnot-accessiblecurrentIndex used for navigating the rows 1..100 of windChargerTable
1.3.6.1.4.1.12148.10.8.6.1.2ColumnwindChargerStatusread-onlycurrentThe overall status of wind charger.
1.3.6.1.4.1.12148.10.8.6.1.3ColumnwindChargerOutputCurrentValueread-onlycurrentThe output current value of wind charger.
1.3.6.1.4.1.12148.10.8.6.1.4ColumnwindChargerInputVoltageValueread-onlycurrentThe input voltage value of wind charger.
1.3.6.1.4.1.12148.10.8.6.1.5ColumnwindChargerTyperead-onlycurrentType of wind charger
1.3.6.1.4.1.12148.10.8.6.1.6ColumnwindChargerHwPartNumberread-onlycurrentHardware part number of wind charger
1.3.6.1.4.1.12148.10.8.6.1.7ColumnwindChargerHwVersionread-onlycurrentHardware version number of wind charger
1.3.6.1.4.1.12148.10.8.6.1.8ColumnwindChargerSwPartNumberread-onlycurrentPart number of secondary software in wind charger
1.3.6.1.4.1.12148.10.8.6.1.9ColumnwindChargerSwVersionread-onlycurrentVersion number of secondary software in wind charger
1.3.6.1.4.1.12148.10.8.7NodewindChargersEnergyLog
1.3.6.1.4.1.12148.10.8.7.1ScalarwindChargersEnergyLogAccumulatedread-onlycurrentThis is the accumulated energy delivered to/from wind chargers.
1.3.6.1.4.1.12148.10.8.7.2ScalarwindChargersEnergyLogLastHoursNumberOfEntriesread-onlycurrentThis is the maximal number of entries stored in wind charger hourly energy log.
1.3.6.1.4.1.12148.10.8.7.3TablewindChargersEnergyLogLastHoursTablenot-accessiblecurrentThis table contains hourly energy log of wind chargers.
1.3.6.1.4.1.12148.10.8.7.3.1RowwindChargersEnergyLogLastHoursEntrynot-accessiblecurrent
1.3.6.1.4.1.12148.10.8.7.3.1.1ColumnwindChargersEnergyLogLastHoursIndexnot-accessiblecurrentIndex used for navigating the rows 1..52 of windChargersEnergyLogLastHoursTable
1.3.6.1.4.1.12148.10.8.7.3.1.2ColumnwindChargersEnergyLogLastHoursValueread-onlycurrentEnergy value logged every hour.
1.3.6.1.4.1.12148.10.8.7.4ScalarwindChargersEnergyLogLastDaysNumberOfEntriesread-onlycurrentThis is the maximal number of entries stored in wind charger daily energy log.
1.3.6.1.4.1.12148.10.8.7.5TablewindChargersEnergyLogLastDaysTablenot-accessiblecurrentThis table contains daily energy log of wind chargers.
1.3.6.1.4.1.12148.10.8.7.5.1RowwindChargersEnergyLogLastDaysEntrynot-accessiblecurrent
1.3.6.1.4.1.12148.10.8.7.5.1.1ColumnwindChargersEnergyLogLastDaysIndexnot-accessiblecurrentIndex used for navigating the rows 1..52 of windChargersEnergyLogLastDaysTable
1.3.6.1.4.1.12148.10.8.7.5.1.2ColumnwindChargersEnergyLogLastDaysValueread-onlycurrentEnergy value logged every day.
1.3.6.1.4.1.12148.10.8.7.6ScalarwindChargersEnergyLogLastWeeksNumberOfEntriesread-onlycurrentThis is the maximal number of entries stored in wind charger weekly energy log.
1.3.6.1.4.1.12148.10.8.7.7TablewindChargersEnergyLogLastWeeksTablenot-accessiblecurrentThis table contains weekly energy log of wind chargers.
1.3.6.1.4.1.12148.10.8.7.7.1RowwindChargersEnergyLogLastWeeksEntrynot-accessiblecurrent
1.3.6.1.4.1.12148.10.8.7.7.1.1ColumnwindChargersEnergyLogLastWeeksIndexnot-accessiblecurrentIndex used for navigating the rows 1..52 of windChargersEnergyLogLastWeekTable
1.3.6.1.4.1.12148.10.8.7.7.1.2ColumnwindChargersEnergyLogLastWeeksValueread-onlycurrentEnergy value logged every week.
1.3.6.1.4.1.12148.10.9Nodeload
1.3.6.1.4.1.12148.10.9.1ScalarloadStatusread-onlycurrentThe overall status of load subsystem.
1.3.6.1.4.1.12148.10.9.2NodeloadCurrent
1.3.6.1.4.1.12148.10.9.2.1ScalarloadCurrentStatusread-onlycurrentThe status of the measured load current.
1.3.6.1.4.1.12148.10.9.2.2ScalarloadCurrentDescriptionread-writecurrentA textual description of the load current monitor. This is stored in the system controller and can be changed by the user.
1.3.6.1.4.1.12148.10.9.2.3ScalarloadCurrentTrapRepeatCounteraccessible-for-notifycurrentThe number of consecutive times this alamcondition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this tra…
1.3.6.1.4.1.12148.10.9.2.4ScalarloadCurrentAlarmEnableread-writecurrentThis value once enabled, the alarm condition of the monitor will be reported.
1.3.6.1.4.1.12148.10.9.2.5ScalarloadCurrentValueread-onlycurrentThe value of the measured load current.
1.3.6.1.4.1.12148.10.9.2.6ScalarloadCurrentMajorHighLevelread-writecurrentThe major high alarm limit
1.3.6.1.4.1.12148.10.9.2.7ScalarloadCurrentMinorHighLevelread-writecurrentThe minor high alarm limit
1.3.6.1.4.1.12148.10.9.3ScalarloadFusesStatusread-onlycurrentThe overall status of the load fuses.
1.3.6.1.4.1.12148.10.9.4ScalarloadNumberOfGroupsread-writecurrentNumber of load groups
1.3.6.1.4.1.12148.10.9.5TableloadGroupTablenot-accessiblecurrentThis table contains information about load groups.
1.3.6.1.4.1.12148.10.9.5.1RowloadGroupEntrynot-accessiblecurrent
1.3.6.1.4.1.12148.10.9.5.1.1ColumnloadGroupIndexnot-accessiblecurrentIndex used for navigating the rows 1..8 of loadGroupTable
1.3.6.1.4.1.12148.10.9.5.1.2ColumnloadGroupStatusread-onlycurrentThe status of load group
1.3.6.1.4.1.12148.10.9.5.1.3ColumnloadNumberOfLVLDsread-onlycurrentNumber of LVLDs installed in load group
1.3.6.1.4.1.12148.10.9.5.1.4ColumnloadNumberOfVoltagesread-onlycurrentNumber of voltages in load group
1.3.6.1.4.1.12148.10.9.6TableloadLVLDTablenot-accessiblecurrentThis table contains information about LVLDs
1.3.6.1.4.1.12148.10.9.6.1RowloadLVLDEntrynot-accessiblecurrent
1.3.6.1.4.1.12148.10.9.6.1.1ColumnloadLVLDIndexnot-accessiblecurrentIndex used for navigating the rows 1..8 of loadLVLDTable
1.3.6.1.4.1.12148.10.9.6.1.2ColumnloadLVLDStatusread-onlycurrentThe status of LVLD
1.3.6.1.4.1.12148.10.9.6.1.3ColumnloadLVLDDescriptionread-writecurrentA textual description of the LVLD. This is stored in the system controller and can be changed by the user.
1.3.6.1.4.1.12148.10.9.6.1.4ColumnloadLVLDTrapRepeatCounteraccessible-for-notifycurrentThe number of consecutive times this alamcondition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this tra…
1.3.6.1.4.1.12148.10.9.6.1.5ColumnloadLVLDEnableread-writecurrentThis value once enabled, the alarm condition of the LVLD will be reported.
1.3.6.1.4.1.12148.10.9.6.1.6ColumnloadLVLDValueread-onlycurrentThe measured value of the LVLD.
1.3.6.1.4.1.12148.10.9.6.1.7ColumnloadLVLDConnectVoltageread-writecurrentThe load Contactor's Reconnect Voltage
1.3.6.1.4.1.12148.10.9.6.1.8ColumnloadLVLDDisconnectVoltageread-writecurrentThe load Contactor's Disconnect Voltage
1.3.6.1.4.1.12148.10.9.6.1.9ColumnloadLVLDDisconnectDelayEnableread-writecurrentEnable/disable LVLD disconnect delay.
1.3.6.1.4.1.12148.10.9.6.1.10ColumnloadLVLDDisconnectDelayTimeread-writecurrentLVLD disconnect delay time in minutes.
1.3.6.1.4.1.12148.10.9.7TableloadFuseTablenot-accessiblecurrentThis table contains information about load fuse
1.3.6.1.4.1.12148.10.9.7.1RowloadFuseEntrynot-accessiblecurrent
1.3.6.1.4.1.12148.10.9.7.1.1ColumnloadFuseStatusread-onlycurrentThe status of load fuse
1.3.6.1.4.1.12148.10.9.7.1.2ColumnloadFuseDescriptionread-writecurrentA textual description of the load fuse monitor. This is stored in the system controller and can be changed by the user.
1.3.6.1.4.1.12148.10.9.7.1.3ColumnloadFuseTrapRepeatCounteraccessible-for-notifycurrentThe number of consecutive times this alamcondition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this tra…
1.3.6.1.4.1.12148.10.9.7.1.4ColumnloadFuseAlarmEnableread-writecurrentThis value once enabled, the alarm condition of the monitor will be reported.
1.3.6.1.4.1.12148.10.9.7.1.5ColumnloadFuseValueread-writecurrentThe measured value of the load fuse.
1.3.6.1.4.1.12148.10.9.8NodeloadEnergyLog
1.3.6.1.4.1.12148.10.9.8.1ScalarloadEnergyLogAccumulatedread-onlycurrentThis is the accumulated energy delivered to load.
1.3.6.1.4.1.12148.10.9.8.2ScalarloadEnergyLogLastHoursNumberOfEntriesread-onlycurrentThis is the maximal number of entries stored in load hourly energy log.
1.3.6.1.4.1.12148.10.9.8.3TableloadEnergyLogLastHoursTablenot-accessiblecurrent
1.3.6.1.4.1.12148.10.9.8.3.1RowloadEnergyLogLastHoursEntrynot-accessiblecurrent
1.3.6.1.4.1.12148.10.9.8.3.1.1ColumnloadEnergyLogLastHoursIndexnot-accessiblecurrentIndex used for navigating the rows 1..52 of loadEnergyLogLastHoursTable
1.3.6.1.4.1.12148.10.9.8.3.1.2ColumnloadEnergyLogLastHoursValueread-onlycurrentEnergy value logged every hour.
1.3.6.1.4.1.12148.10.9.8.4ScalarloadEnergyLogLastDaysNumberOfEntriesread-onlycurrentThis is the maximal number of entries stored in load daily energy log.
1.3.6.1.4.1.12148.10.9.8.5TableloadEnergyLogLastDaysTablenot-accessiblecurrent
1.3.6.1.4.1.12148.10.9.8.5.1RowloadEnergyLogLastDaysEntrynot-accessiblecurrent
1.3.6.1.4.1.12148.10.9.8.5.1.1ColumnloadEnergyLogLastDaysIndexnot-accessiblecurrentIndex used for navigating the rows 1..52 of loadEnergyLogLastDaysTable
1.3.6.1.4.1.12148.10.9.8.5.1.2ColumnloadEnergyLogLastDaysValueread-onlycurrentEnergy value logged every day.
1.3.6.1.4.1.12148.10.9.8.6ScalarloadEnergyLogLastWeeksNumberOfEntriesread-onlycurrentThis is the maximal number of entries stored in load weekly energy log.
1.3.6.1.4.1.12148.10.9.8.7TableloadEnergyLogLastWeeksTablenot-accessiblecurrent
1.3.6.1.4.1.12148.10.9.8.7.1RowloadEnergyLogLastWeeksEntrynot-accessiblecurrent
1.3.6.1.4.1.12148.10.9.8.7.1.1ColumnloadEnergyLogLastWeeksIndexnot-accessiblecurrentIndex used for navigating the rows 1..52 of loadEnergyLogLastWeekTable
1.3.6.1.4.1.12148.10.9.8.7.1.2ColumnloadEnergyLogLastWeeksValueread-onlycurrentEnergy value logged every week.
1.3.6.1.4.1.12148.10.9.9TableloadVoltageTablenot-accessiblecurrentThis table contains information about voltages
1.3.6.1.4.1.12148.10.9.9.1RowloadVoltageEntrynot-accessiblecurrent
1.3.6.1.4.1.12148.10.9.9.1.1ColumnloadVoltageIndexnot-accessiblecurrentIndex used for navigating the rows 1..3 of loadVoltageTable
1.3.6.1.4.1.12148.10.9.9.1.2ColumnloadVoltageStatusread-onlycurrentThe status of voltage
1.3.6.1.4.1.12148.10.9.9.1.3ColumnloadVoltageDescriptionread-writecurrentA textual description of the voltage. This is stored in the system controller and can be changed by the user.
1.3.6.1.4.1.12148.10.9.9.1.4ColumnloadVoltageTrapRepeatCounteraccessible-for-notifycurrentThe number of consecutive times this alamcondition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this tra…
1.3.6.1.4.1.12148.10.9.9.1.5ColumnloadVoltageEnableread-writecurrentThis value once enabled, the alarm condition of the LVLD will be reported.
1.3.6.1.4.1.12148.10.9.9.1.6ColumnloadVoltageValueread-onlycurrentThe measured value of the voltage.
1.3.6.1.4.1.12148.10.10Nodebattery
1.3.6.1.4.1.12148.10.10.1ScalarbatteryStatusread-onlycurrentA toplevel status for the battery subsystem. The state of this reflects the status of all underlying statuses for the battery. Any change in one of the 'data m…
1.3.6.1.4.1.12148.10.10.2ScalarbatteryDescriptionread-writecurrentA descriptive name of the battery installed in the system.
1.3.6.1.4.1.12148.10.10.3ScalarbatteryReferenceVoltageread-writecurrentThe Voltage at which the DC System float charges. Acts as reference voltage when running temperature compensated charging.
1.3.6.1.4.1.12148.10.10.4ScalarbatteryFusesStatusread-onlycurrentThe state of the battery fuses/breakers can mainly be normal(1) or majorAlarm(3) and some other rarely used values .
1.3.6.1.4.1.12148.10.10.5NodebatteryVoltage
1.3.6.1.4.1.12148.10.10.5.1ScalarbatteryVoltageStatusread-onlycurrentThe status of the measured battery voltage.
1.3.6.1.4.1.12148.10.10.5.2ScalarbatteryVoltageDescriptionread-writecurrentA textual description of the battery voltage monitor. This is stored in the system controller and can be changed by the user.
1.3.6.1.4.1.12148.10.10.5.3ScalarbatteryVoltageTrapRepeatCounteraccessible-for-notifycurrentThe number of consecutive times this alamcondition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this tra…
1.3.6.1.4.1.12148.10.10.5.4ScalarbatteryVoltageAlarmEnableread-writecurrentThe measured battery voltage alarm enable/disable control
1.3.6.1.4.1.12148.10.10.5.5ScalarbatteryVoltageValueread-onlycurrentThe value of the measured battery voltage. Scale is 0.01v.
1.3.6.1.4.1.12148.10.10.5.6ScalarbatteryVoltageMajorHighLevelread-writecurrentThe Major High Battery Voltage alarm limit set voltage.Scale is 0.01v.
1.3.6.1.4.1.12148.10.10.5.7ScalarbatteryVoltageMinorHighLevelread-writecurrentThe Minor High Battery Voltage alarm limit set voltage.Scale is 0.01v.
1.3.6.1.4.1.12148.10.10.5.8ScalarbatteryVoltageMinorLowLevelread-writecurrentThe Minor Low Battery Voltage alarm limit set voltage.Scale is 0.01v.
1.3.6.1.4.1.12148.10.10.5.9ScalarbatteryVoltageMajorLowLevelread-writecurrentThe Major Low Battery Voltage alarm limit set voltage.Scale is 0.01v.
1.3.6.1.4.1.12148.10.10.6NodebatteryCurrents
1.3.6.1.4.1.12148.10.10.6.1ScalarbatteryCurrentsStatusread-onlycurrentThe status of the measured battery current
1.3.6.1.4.1.12148.10.10.6.2ScalarbatteryCurrentsDescriptionread-writecurrentA textual description of the battery current monitor. This is stored in the system controller and can be changed by the user.
1.3.6.1.4.1.12148.10.10.6.3ScalarbatteryCurrentsTrapRepeatCounteraccessible-for-notifycurrentThe number of consecutive times this alam condition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this tr…
1.3.6.1.4.1.12148.10.10.6.4ScalarbatteryCurrentsAlarmEnableread-writecurrentThis value once enabled, the alarm condition of the monitor will be reported.
1.3.6.1.4.1.12148.10.10.6.5ScalarbatteryCurrentsValueread-onlycurrentThe measured total battery current. This is the sum of all the enabled shunt measurements in the system. Negative battery current indicates discharging of the …
1.3.6.1.4.1.12148.10.10.6.6ScalarbatteryCurrentsMajorHighLevelread-writecurrentThe major high alarm limit
1.3.6.1.4.1.12148.10.10.6.7ScalarbatteryCurrentsMinorHighLevelread-writecurrentThe minor high alarm limit
1.3.6.1.4.1.12148.10.10.6.8ScalarbatteryCurrentsMinorLowLevelread-writecurrentThe minor low alarm limit
1.3.6.1.4.1.12148.10.10.6.9ScalarbatteryCurrentsMajorLowLevelread-writecurrentThe major low alarm limit
1.3.6.1.4.1.12148.10.10.7NodebatteryTemperatures
1.3.6.1.4.1.12148.10.10.7.1ScalarbatteryTemperaturesStatusread-onlycurrentThe state of the battery fuses/breakers can be either one of the defined enumerated values
1.3.6.1.4.1.12148.10.10.7.2ScalarbatteryTemperaturesDescriptionread-writecurrentA textual description of the battery temperature monitor. This is stored in the system controller and can be changed by the user.
1.3.6.1.4.1.12148.10.10.7.3ScalarbatteryTemperaturesTrapRepeatCounteraccessible-for-notifycurrentThe number of consecutive times this alamcondition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this tra…
1.3.6.1.4.1.12148.10.10.7.4ScalarbatteryTemperaturesAlarmEnableread-writecurrentThis value once enabled, the alarm condition of the monitor will be reported.
1.3.6.1.4.1.12148.10.10.7.5ScalarbatteryTemperaturesValueread-onlycurrentThe highest value of the enabled battery temperature measurements. Depending on the global setting in the Control unit, this value will be presented in Celsius…
1.3.6.1.4.1.12148.10.10.7.6ScalarbatteryTemperaturesMajorHighLevelread-writecurrentThe major high alarm limit
1.3.6.1.4.1.12148.10.10.7.7ScalarbatteryTemperaturesMinorHighLevelread-writecurrentThe minor high alarm limit
1.3.6.1.4.1.12148.10.10.7.8ScalarbatteryTemperaturesMinorLowLevelread-writecurrentThe minor low alarm limit
1.3.6.1.4.1.12148.10.10.7.9ScalarbatteryTemperaturesMajorLowLevelread-writecurrentThe major low alarm limit
1.3.6.1.4.1.12148.10.10.8NodebatteryTimeLeft
1.3.6.1.4.1.12148.10.10.8.1ScalarbatteryTimeLeftStatusread-onlycurrentThe status of the estimated battery remaining backup time.
1.3.6.1.4.1.12148.10.10.8.2ScalarbatteryTimeLeftDescriptionread-writecurrentA textual description of the battery discharge time monitor. This is stored in the system controller and can be changed by the user.
1.3.6.1.4.1.12148.10.10.8.3ScalarbatteryTimeLeftTrapRepeatCounteraccessible-for-notifycurrentThe number of consecutive times this alam condition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this tr…
1.3.6.1.4.1.12148.10.10.8.4ScalarbatteryTimeLeftAlarmEnableread-writecurrentThis value once enabled, the alarm condition of the monitor will be reported.
1.3.6.1.4.1.12148.10.10.8.5ScalarbatteryTimeLeftValueread-onlycurrentThe estimated value of battery remaining backup time.
1.3.6.1.4.1.12148.10.10.8.6ScalarbatteryTimeLeftMinorAlarmLevelread-writecurrentThe minor alarm limit
1.3.6.1.4.1.12148.10.10.8.7ScalarbatteryTimeLeftMajorAlarmLevelread-writecurrentThe major alarm limit
1.3.6.1.4.1.12148.10.10.9NodebatteryRemainingCapacity
1.3.6.1.4.1.12148.10.10.9.1ScalarbatteryRemainingCapacityStatusread-onlycurrentThe status of the battery remaining capacity monitor.
1.3.6.1.4.1.12148.10.10.9.2ScalarbatteryRemainingCapacityDescriptionread-writecurrentA textual description of the battery remaining capacity monitor. This is stored in the system controller and can be changed by the user.
1.3.6.1.4.1.12148.10.10.9.3ScalarbatteryRemainingCapacityTrapRepeatCounteraccessible-for-notifycurrentThe number of consecutive times this alam condition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this tr…
1.3.6.1.4.1.12148.10.10.9.4ScalarbatteryRemainingCapacityAlarmEnableread-writecurrentThis value once enabled, the alarm condition of the monitor will be reported.
1.3.6.1.4.1.12148.10.10.9.5ScalarbatteryRemainingCapacityValueread-onlycurrentBattery remaining capacity (SOC) value estimated from the latest battery test result.
1.3.6.1.4.1.12148.10.10.9.6ScalarbatteryRemainingCapacityMinorLowLevelread-writecurrentThe minor low alarm limit
1.3.6.1.4.1.12148.10.10.9.7ScalarbatteryRemainingCapacityMajorLowLevelread-writecurrentThe major low alarm limit
1.3.6.1.4.1.12148.10.10.10NodebatteryUsedCapacity
1.3.6.1.4.1.12148.10.10.10.1ScalarbatteryUsedCapacityStatusread-onlycurrentThe status of the battery used capacity (DoD) monitor
1.3.6.1.4.1.12148.10.10.10.2ScalarbatteryUsedCapacityDescriptionread-writecurrentA textual description of the battery used capacity (DoD) monitor. This is stored in the system controller and can be changed by the user.
1.3.6.1.4.1.12148.10.10.10.3ScalarbatteryUsedCapacityTrapRepeatCounteraccessible-for-notifycurrentThe number of consecutive times this alam condition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this tr…
1.3.6.1.4.1.12148.10.10.10.4ScalarbatteryUsedCapacityAlarmEnableread-writecurrentThis value once enabled, the alarm condition of the monitor will be reported.
1.3.6.1.4.1.12148.10.10.10.5ScalarbatteryUsedCapacityValueread-onlycurrentThis is the estimated battery used capacity (DoD).
1.3.6.1.4.1.12148.10.10.10.6ScalarbatteryUsedCapacityMajorAlarmLevelread-writecurrentThe major alarm limit
1.3.6.1.4.1.12148.10.10.10.7ScalarbatteryUsedCapacityMinorAlarmLevelread-writecurrentThe minor alarm limit
1.3.6.1.4.1.12148.10.10.11NodebatteryTotalCapacity
1.3.6.1.4.1.12148.10.10.11.1ScalarbatteryTotalCapacityStatusread-onlycurrentThe status of the total capacity monitor.
1.3.6.1.4.1.12148.10.10.11.2ScalarbatteryTotalCapacityDescriptionread-writecurrentA textual description of the battery total capacity monitor. This is stored in the system controller and can be changed by the user
1.3.6.1.4.1.12148.10.10.11.3ScalarbatteryTotalCapacityTrapRepeatCounteraccessible-for-notifycurrentThe number of consecutive times this alam condition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this tr…
1.3.6.1.4.1.12148.10.10.11.4ScalarbatteryTotalCapacityAlarmEnableread-writecurrentThis value once enabled, the alarm condition of the monitor will be reported.
1.3.6.1.4.1.12148.10.10.11.5ScalarbatteryTotalCapacityValueread-onlycurrentThis is the estimated total battery capacity (installed Ah - SoH) value.
1.3.6.1.4.1.12148.10.10.11.6ScalarbatteryTotalCapacityMinorLowLevelread-writecurrentThe minor low alarm limit
1.3.6.1.4.1.12148.10.10.11.7ScalarbatteryTotalCapacityMajorLowLevelread-writecurrentThe major low alarm limit
1.3.6.1.4.1.12148.10.10.12NodebatteryQuality
1.3.6.1.4.1.12148.10.10.12.1ScalarbatteryQualityStatusread-onlycurrentThe status of the battery quality (SoH) monitor.
1.3.6.1.4.1.12148.10.10.12.2ScalarbatteryQualityDescriptionread-writecurrentA textual description of the battery quality (SoH) monitor. This is stored in the system controller and can be changed by the user
1.3.6.1.4.1.12148.10.10.12.3ScalarbatteryQualityTrapRepeatCounteraccessible-for-notifycurrentThe number of consecutive times this alamcondition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this tra…
1.3.6.1.4.1.12148.10.10.12.4ScalarbatteryQualityAlarmEnableread-writecurrentThis value once enabled, the alarm condition of the monitor will be reported.
1.3.6.1.4.1.12148.10.10.12.5ScalarbatteryQualityValueread-onlycurrentThe calculated battery quality (SoH) based on the latest battery test
1.3.6.1.4.1.12148.10.10.12.6ScalarbatteryQualityMinorAlarmLevelread-writecurrentThe minor alarm limit
1.3.6.1.4.1.12148.10.10.12.7ScalarbatteryQualityMajorAlarmLevelread-writecurrentThe major alarm limit
1.3.6.1.4.1.12148.10.10.13NodebatteryLVBD
1.3.6.1.4.1.12148.10.10.13.1ScalarbatteryLVBDStatusread-onlycurrentThe Battery Contactor is connected, disconnected, disabled or in any other alarm condition
1.3.6.1.4.1.12148.10.10.13.2ScalarbatteryLVBDDescriptionread-writecurrentA textual description of the battery LVBD monitor. This is stored in the system controller and can be changed by the user.
1.3.6.1.4.1.12148.10.10.13.3ScalarbatteryLVBDTrapRepeatCounteraccessible-for-notifycurrentThe number of consecutive times this alam condition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this tr…
1.3.6.1.4.1.12148.10.10.13.4ScalarbatteryLVBDEnableread-writecurrentThis value once enabled, the alarm condition of the LVBD will be reported.
1.3.6.1.4.1.12148.10.10.13.5ScalarbatteryLVBDValueread-onlycurrentThe measured value of the LVBD.
1.3.6.1.4.1.12148.10.10.13.6ScalarbatteryLVBDConnectVoltageread-writecurrentThe Battery Contactor's Reconnect Voltage
1.3.6.1.4.1.12148.10.10.13.7ScalarbatteryLVBDDisconnectVoltageread-writecurrentThe Battery Contactor's Disconnect Voltage
1.3.6.1.4.1.12148.10.10.14NodebatteryChargeCurrentLimit
1.3.6.1.4.1.12148.10.10.14.1ScalarbatteryChargeCurrentLimitEnableread-writecurrentEnable/disable of the battery charge current limitation feature; 0=disable, 1=enable.
1.3.6.1.4.1.12148.10.10.14.2ScalarbatteryChargeCurrentLimitValueread-writecurrentBattery charging current limit value. Used only when AC source is mains feed. Note that the units measured may be i Amperes or in Deciamperes depending on glob…
1.3.6.1.4.1.12148.10.10.15NodebatteryBoost
1.3.6.1.4.1.12148.10.10.15.1ScalarbatteryBoostVoltageread-writecurrentThe Voltage at which the DC System boost charges the batteries.
1.3.6.1.4.1.12148.10.10.15.2ScalarbatteryBoostCommandread-writecurrentThis pushbutton will start or stop a manual battery boost if the system allows it.
1.3.6.1.4.1.12148.10.10.15.3ScalarbatteryBoostCurrentThresholdread-writecurrentThe boosting will terminate when the charge current drops below the BoostCurrentThreshold limit.
1.3.6.1.4.1.12148.10.10.15.4ScalarbatteryBoostManualMaxDurationread-writecurrentA protection against overcharging. When running manual boost, the boosting will always terminate at this point.
1.3.6.1.4.1.12148.10.10.16NodebatteryTest
1.3.6.1.4.1.12148.10.10.16.1ScalarbatteryTestVoltageread-writecurrentThis is the simplified battery test end voltage. The battery test will be terminated when the voltage drops below the end voltage.
1.3.6.1.4.1.12148.10.10.16.2ScalarbatteryTestCommandread-writecurrentThis pushbutton will start or stop a manual battery test if the system allows it.
1.3.6.1.4.1.12148.10.10.16.3ScalarbatteryTestNumberOfResultsread-onlycurrentThis is the number of valid battery test results stored in controller.
1.3.6.1.4.1.12148.10.10.16.4TablebatteryTestResultTablenot-accessiblecurrentThis table contains the battery test results stored in controller.
1.3.6.1.4.1.12148.10.10.16.4.1RowbatteryTestResultEntrynot-accessiblecurrent
1.3.6.1.4.1.12148.10.10.16.4.1.1ColumnbatteryTestResultIndexnot-accessiblecurrentA index pointing to one of ten possible battery test results
1.3.6.1.4.1.12148.10.10.16.4.1.2ColumnbatteryTestResultStartDateTimeread-onlycurrentThis is the time and date when the test started.
1.3.6.1.4.1.12148.10.10.16.4.1.3ColumnbatteryTestResultDurationread-onlycurrentThis is the test duration in minutes.
1.3.6.1.4.1.12148.10.10.16.4.1.4ColumnbatteryTestResultDischargedread-onlycurrentThis is the discharged Ah during test.
1.3.6.1.4.1.12148.10.10.16.4.1.5ColumnbatteryTestResultQualityread-onlycurrentThis is the calculated battery quality (SoH)in percentage.
1.3.6.1.4.1.12148.10.10.16.4.1.6ColumnbatteryTestResultEndVoltageread-onlycurrentThis is the test end voltage in volt.
1.3.6.1.4.1.12148.10.10.16.4.1.7ColumnbatteryTestResultTestResultread-onlycurrentThis is the test result.
1.3.6.1.4.1.12148.10.10.16.4.1.8ColumnbatteryTestResultTerminationCriteriaread-onlycurrentThis is the test Termination Criteria.
1.3.6.1.4.1.12148.10.10.16.4.1.9ColumnbatteryTestResultBatteryTemperatureread-onlycurrentThis is the battery temperature
1.3.6.1.4.1.12148.10.10.16.5ScalarbatteryTestDurationread-writecurrentThis is the battery test max duration.
1.3.6.1.4.1.12148.10.10.16.6ScalarbatteryTestCfgTestTyperead-writecurrentThis is to configurate normal or simplified battery test.
1.3.6.1.4.1.12148.10.10.16.7ScalarbatteryTestEnableMaxDurationread-writecurrentThis is to enable/disable battery test max duration.
1.3.6.1.4.1.12148.10.10.17NodebatteryTempComp
1.3.6.1.4.1.12148.10.10.17.1ScalarbatteryTempCompEnableread-writecurrentEnable (1) or Disable (0) of Battery Temperature Compensated output regulation mode
1.3.6.1.4.1.12148.10.10.18NodebatteryBank
1.3.6.1.4.1.12148.10.10.18.1ScalarbatteryBankNumberOfBanksread-writecurrentNumber of battery banks installed in system.
1.3.6.1.4.1.12148.10.10.18.2TablebatteryBankTablenot-accessiblecurrent
1.3.6.1.4.1.12148.10.10.18.2.1RowbatteryBankEntrynot-accessiblecurrent
1.3.6.1.4.1.12148.10.10.18.2.1.1ColumnbatteryBankIndexnot-accessiblecurrentIndex used for navigating the rows 1..8 of batteryBankTable
1.3.6.1.4.1.12148.10.10.18.2.1.2ColumnbatteryBankStatusread-onlycurrentThe overall status of battery bank
1.3.6.1.4.1.12148.10.10.18.2.1.3ColumnbatteryBankNumberOfTemperaturesread-onlycurrentNumber of temperature measurements in battery bank.
1.3.6.1.4.1.12148.10.10.18.2.1.4ColumnbatteryBankNumberOfCurrentsread-onlycurrentNumber of current measurements in battery bank.
1.3.6.1.4.1.12148.10.10.18.2.1.5ColumnbatteryBankNumberOfFusesread-onlycurrentNumber of fuses installed in battery bank.
1.3.6.1.4.1.12148.10.10.18.2.1.6ColumnbatteryBankNumberOfSymmetriesread-onlycurrentNumber of symmetry measurements available in battery bank.
1.3.6.1.4.1.12148.10.10.18.3TablebatteryBankTemperatureTablenot-accessiblecurrent
1.3.6.1.4.1.12148.10.10.18.3.1RowbatteryBankTemperatureEntrynot-accessiblecurrent
1.3.6.1.4.1.12148.10.10.18.3.1.1ColumnbatteryTemperatureIndexnot-accessiblecurrentThis index denotes which row in the temperature input table. The size of the table is defined by the batteryBankNumberOfTemp
1.3.6.1.4.1.12148.10.10.18.3.1.2ColumnbatteryTemperatureStatusread-onlycurrentThe status of battery temperature monitor
1.3.6.1.4.1.12148.10.10.18.3.1.3ColumnbatteryTemperatureDescriptionread-writecurrentA textual description of the battery temperature monitor. This is stored in the system controller and can be changed by the user.
1.3.6.1.4.1.12148.10.10.18.3.1.4ColumnbatteryTemperatureTrapRepeatCounteraccessible-for-notifycurrentThe number of consecutive times this alam condition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this tr…
1.3.6.1.4.1.12148.10.10.18.3.1.5ColumnbatteryTemperatureAlarmEnableread-writecurrentThis value once enabled, the alarm condition of the monitor will be reported.
1.3.6.1.4.1.12148.10.10.18.3.1.6ColumnbatteryTemperatureValueread-onlycurrentThe measured battery temperature.
1.3.6.1.4.1.12148.10.10.18.3.1.7ColumnbatteryTemperatureMajorHighLevelread-writecurrentThe major high alarm limit
1.3.6.1.4.1.12148.10.10.18.3.1.8ColumnbatteryTemperatureMinorHighLevelread-writecurrentThe minor high alarm limit
1.3.6.1.4.1.12148.10.10.18.3.1.9ColumnbatteryTemperatureMinorLowLevelread-writecurrentThe minor low alarm limit
1.3.6.1.4.1.12148.10.10.18.3.1.10ColumnbatteryTemperatureMajorLowLevelread-writecurrentThe major low alarm limit
1.3.6.1.4.1.12148.10.10.18.4TablebatteryBankCurrentTablenot-accessiblecurrent
1.3.6.1.4.1.12148.10.10.18.4.1RowbatteryBankCurrentEntrynot-accessiblecurrent
1.3.6.1.4.1.12148.10.10.18.4.1.1ColumnbatteryCurrentIndexnot-accessiblecurrentThis index denotes which row in the current input table. The size of the table is defined by the system
1.3.6.1.4.1.12148.10.10.18.4.1.2ColumnbatteryCurrentStatusread-onlycurrentThe status of battery current monitor
1.3.6.1.4.1.12148.10.10.18.4.1.3ColumnbatteryCurrentDescriptionread-writecurrentA textual description of the battery current monitor. This is stored in the system controller and can be changed by the user.
1.3.6.1.4.1.12148.10.10.18.4.1.4ColumnbatteryCurrentTrapRepeatCounteraccessible-for-notifycurrentThe number of consecutive times this alam condition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this tr…
1.3.6.1.4.1.12148.10.10.18.4.1.5ColumnbatteryCurrentAlarmEnableread-writecurrentThis value once enabled, the alarm condition of the monitor will be reported.
1.3.6.1.4.1.12148.10.10.18.4.1.6ColumnbatteryCurrentValueread-onlycurrentThe measured battery current
1.3.6.1.4.1.12148.10.10.18.4.1.7ColumnbatteryCurrentMajorHighLevelread-writecurrentThe major high alarm limit
1.3.6.1.4.1.12148.10.10.18.4.1.8ColumnbatteryCurrentMinorHighLevelread-writecurrentThe minor high alarm limit
1.3.6.1.4.1.12148.10.10.18.4.1.9ColumnbatteryCurrentMinorLowLevelread-writecurrentThe minor low alarm limit
1.3.6.1.4.1.12148.10.10.18.4.1.10ColumnbatteryCurrentMajorLowLevelread-writecurrentThe major low alarm limit
1.3.6.1.4.1.12148.10.10.18.5TablebatteryBankFuseTablenot-accessiblecurrent
1.3.6.1.4.1.12148.10.10.18.5.1RowbatteryBankFuseEntrynot-accessiblecurrent
1.3.6.1.4.1.12148.10.10.18.5.1.1ColumnbatteryFuseIndexnot-accessiblecurrentThis index denotes which row in the fuse table. The size of the table is defined by the system
1.3.6.1.4.1.12148.10.10.18.5.1.2ColumnbatteryFuseStatusread-onlycurrentThe status of battery fuse monitor
1.3.6.1.4.1.12148.10.10.18.5.1.3ColumnbatteryFuseDescriptionread-writecurrentA textual description of the battery fuse monitor. This is stored in the system controller and can be changed by the user.
1.3.6.1.4.1.12148.10.10.18.5.1.4ColumnbatteryFuseTrapRepeatCounteraccessible-for-notifycurrentThe number of consecutive times this alam condition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this tr…
1.3.6.1.4.1.12148.10.10.18.5.1.5ColumnbatteryFuseAlarmEnableread-writecurrentThis value once enabled, the alarm condition of the monitor will be reported.
1.3.6.1.4.1.12148.10.10.18.5.1.6ColumnbatteryFuseValueread-onlycurrentThe measured value of battery fuse input.
1.3.6.1.4.1.12148.10.10.18.6TablebatteryBankSymmetryTablenot-accessiblecurrent
1.3.6.1.4.1.12148.10.10.18.6.1RowbatteryBankSymmetryEntrynot-accessiblecurrent
1.3.6.1.4.1.12148.10.10.18.6.1.1ColumnbatteryBankSymmetryIndexnot-accessiblecurrentThis index denotes which row in the symmetry input table. The size of the table is defined by the batteryMonitorNumberOfSymmetries
1.3.6.1.4.1.12148.10.10.18.6.1.2ColumnbatteryBankSymmetryStatusread-onlycurrentThe status of battery symmetry monitor
1.3.6.1.4.1.12148.10.10.18.6.1.3ColumnbatteryBankSymmetryDescriptionread-writecurrentA textual description of the battery monitor symmetry. This is stored in the system controller and can be changed by the user.
1.3.6.1.4.1.12148.10.10.18.6.1.4ColumnbatteryBankSymmetryTrapRepeatCounteraccessible-for-notifycurrentThe number of consecutive times this alam condition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this tr…
1.3.6.1.4.1.12148.10.10.18.6.1.5ColumnbatteryBankSymmetryAlarmEnableread-writecurrentThis value once enabled, the alarm condition of the monitor will be reported.
1.3.6.1.4.1.12148.10.10.18.6.1.6ColumnbatteryBankSymmetryMeasureValueread-onlycurrentThe measured battery symmetry voltage in battery monitor.
1.3.6.1.4.1.12148.10.10.18.6.1.7ColumnbatteryBankSymmetryDeltaValueread-onlycurrentThe measured battery symmetry delta voltage in battery monitor.
1.3.6.1.4.1.12148.10.10.18.6.1.8ColumnbatteryBankSymmetryMajorAlarmLevelread-writecurrentThe major alarm limit
1.3.6.1.4.1.12148.10.10.18.6.1.9ColumnbatteryBankSymmetryMinorAlarmLevelread-writecurrentThe minor alarm limit
1.3.6.1.4.1.12148.10.10.19NodebatteryMonitors
1.3.6.1.4.1.12148.10.10.19.1ScalarbatteryMonitorsNumberOfUnitsread-writecurrentThe number of battery monitor installed in system.
1.3.6.1.4.1.12148.10.10.19.2TablebatteryMonitorsTablenot-accessiblecurrent
1.3.6.1.4.1.12148.10.10.19.2.1RowbatteryMonitorsEntrynot-accessiblecurrent
1.3.6.1.4.1.12148.10.10.19.2.1.1ColumnbatteryMonitorIndexnot-accessiblecurrentIndex used for navigating the rows 1..8 of batteryMonitorsTable
1.3.6.1.4.1.12148.10.10.19.2.1.2ColumnbatteryMonitorNumberOfTemperaturesread-onlycurrentThe number of temperature measurements in battery monitor.
1.3.6.1.4.1.12148.10.10.19.2.1.3ColumnbatteryMonitorNumberOfCurrentsread-onlycurrentThe number of current measurements in battery monitor.
1.3.6.1.4.1.12148.10.10.19.2.1.4ColumnbatteryMonitorNumberOfFusesread-onlycurrentThe number of fuse measurements in battery monitor.
1.3.6.1.4.1.12148.10.10.19.2.1.5ColumnbatteryMonitorNumberOfSymmetriesread-onlycurrentThe number of symmetry measurements in battery monitor.
1.3.6.1.4.1.12148.10.10.19.3TablebatteryMonitorTemperatureTablenot-accessiblecurrent
1.3.6.1.4.1.12148.10.10.19.3.1RowbatteryMonitorTemperatureEntrynot-accessiblecurrent
1.3.6.1.4.1.12148.10.10.19.3.1.1ColumnbatteryMonitorTemperatureIndexnot-accessiblecurrentThis index denotes which row in the temperature input table. The size of the table is defined by the batteryMonitorNumberOfTemperatures
1.3.6.1.4.1.12148.10.10.19.3.1.2ColumnbatteryMonitorTemperatureStatusread-onlycurrentThe status of battery temperature monitor
1.3.6.1.4.1.12148.10.10.19.3.1.3ColumnbatteryMonitorTemperatureDescriptionread-writecurrentA textual description of the battery monitor temperature. This is stored in the system controller and can be changed by the user.
1.3.6.1.4.1.12148.10.10.19.3.1.4ColumnbatteryMonitorTemperatureTrapRepeatCounteraccessible-for-notifycurrentThe number of consecutive times this alam condition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this tr…
1.3.6.1.4.1.12148.10.10.19.3.1.5ColumnbatteryMonitorTemperatureAlarmEnableread-writecurrentThis value once enabled, the alarm condition of the monitor will be reported.
1.3.6.1.4.1.12148.10.10.19.3.1.6ColumnbatteryMonitorTemperatureValueread-onlycurrentThe measured battery temperature in battery monitor.
1.3.6.1.4.1.12148.10.10.19.3.1.7ColumnbatteryMonitorTemperatureMajorHighLevelread-writecurrentThe major high alarm limit
1.3.6.1.4.1.12148.10.10.19.3.1.8ColumnbatteryMonitorTemperatureMinorHighLevelread-writecurrentThe minor high alarm limit
1.3.6.1.4.1.12148.10.10.19.3.1.9ColumnbatteryMonitorTemperatureMinorLowLevelread-writecurrentThe minor low alarm limit
1.3.6.1.4.1.12148.10.10.19.3.1.10ColumnbatteryMonitorTemperatureMajorLowLevelread-writecurrentThe major low alarm limit
1.3.6.1.4.1.12148.10.10.19.4TablebatteryMonitorCurrentTablenot-accessiblecurrent
1.3.6.1.4.1.12148.10.10.19.4.1RowbatteryMonitorCurrentEntrynot-accessiblecurrent
1.3.6.1.4.1.12148.10.10.19.4.1.1ColumnbatteryMonitorCurrentIndexnot-accessiblecurrentThis index denotes which row in the current input table. The size of the table is defined by the batteryMonitorNumberOfCurrents
1.3.6.1.4.1.12148.10.10.19.4.1.2ColumnbatteryMonitorCurrentStatusread-onlycurrentThe status of battery current monitor
1.3.6.1.4.1.12148.10.10.19.4.1.3ColumnbatteryMonitorCurrentDescriptionread-writecurrentA textual description of the battery monitor current. This is stored in the system controller and can be changed by the user.
1.3.6.1.4.1.12148.10.10.19.4.1.4ColumnbatteryMonitorCurrentTrapRepeatCounteraccessible-for-notifycurrentThe number of consecutive times this alam condition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this tr…
1.3.6.1.4.1.12148.10.10.19.4.1.5ColumnbatteryMonitorCurrentAlarmEnableread-writecurrentThis value once enabled, the alarm condition of the monitor will be reported.
1.3.6.1.4.1.12148.10.10.19.4.1.6ColumnbatteryMonitorCurrentValueread-onlycurrentThe measured battery current in battery monitor.
1.3.6.1.4.1.12148.10.10.19.4.1.7ColumnbatteryMonitorCurrentMajorHighLevelread-writecurrentThe major high alarm limit
1.3.6.1.4.1.12148.10.10.19.4.1.8ColumnbatteryMonitorCurrentMinorHighLevelread-writecurrentThe minor high alarm limit
1.3.6.1.4.1.12148.10.10.19.4.1.9ColumnbatteryMonitorCurrentMinorLowLevelread-writecurrentThe minor low alarm limit
1.3.6.1.4.1.12148.10.10.19.4.1.10ColumnbatteryMonitorCurrentMajorLowLevelread-writecurrentThe major low alarm limit
1.3.6.1.4.1.12148.10.10.19.5TablebatteryMonitorFuseTablenot-accessiblecurrent
1.3.6.1.4.1.12148.10.10.19.5.1RowbatteryMonitorFuseEntrynot-accessiblecurrent
1.3.6.1.4.1.12148.10.10.19.5.1.1ColumnbatteryMonitorFuseIndexnot-accessiblecurrentThis index denotes which row in the fuse table. The size of the table is defined by the batteryMonitorNumberOfFuses
1.3.6.1.4.1.12148.10.10.19.5.1.2ColumnbatteryMonitorFuseStatusread-onlycurrentThe status of battery fuse monitor
1.3.6.1.4.1.12148.10.10.19.5.1.3ColumnbatteryMonitorFuseDescriptionread-writecurrentA textual description of the battery monitor fuse. This is stored in the system controller and can be changed by the user.
1.3.6.1.4.1.12148.10.10.19.5.1.4ColumnbatteryMonitorFuseTrapRepeatCounteraccessible-for-notifycurrentThe number of consecutive times this alam condition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this tr…
1.3.6.1.4.1.12148.10.10.19.5.1.5ColumnbatteryMonitorFuseAlarmEnableread-writecurrentThis value once enabled, the alarm condition of the monitor will be reported.
1.3.6.1.4.1.12148.10.10.19.5.1.6ColumnbatteryMonitorFuseValueread-onlycurrentThe measured value of battery fuse in battery monitor.
1.3.6.1.4.1.12148.10.10.19.6TablebatteryMonitorSymmetryTablenot-accessiblecurrent
1.3.6.1.4.1.12148.10.10.19.6.1RowbatteryMonitorSymmetryEntrynot-accessiblecurrent
1.3.6.1.4.1.12148.10.10.19.6.1.1ColumnbatteryMonitorSymmetryIndexnot-accessiblecurrentThis index denotes which row in the symmetry input table. The size of the table is defined by the batteryMonitorNumberOfSymmetries
1.3.6.1.4.1.12148.10.10.19.6.1.2ColumnbatteryMonitorSymmetryStatusread-onlycurrentThe status of battery symmetry monitor
1.3.6.1.4.1.12148.10.10.19.6.1.3ColumnbatteryMonitorSymmetryDescriptionread-writecurrentA textual description of the battery monitor symmetry. This is stored in the system controller and can be changed by the user.
1.3.6.1.4.1.12148.10.10.19.6.1.4ColumnbatteryMonitorSymmetryTrapRepeatCounteraccessible-for-notifycurrentThe number of consecutive times this alam condition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this tr…
1.3.6.1.4.1.12148.10.10.19.6.1.5ColumnbatteryMonitorSymmetryAlarmEnableread-writecurrentThis value once enabled, the alarm condition of the monitor will be reported.
1.3.6.1.4.1.12148.10.10.19.6.1.6ColumnbatteryMonitorSymmetryMeasureValueread-onlycurrentThe measured battery symmetry voltage in battery monitor.
1.3.6.1.4.1.12148.10.10.19.6.1.7ColumnbatteryMonitorSymmetryDeltaValueread-onlycurrentThe measured battery symmetry delta voltage in battery monitor.
1.3.6.1.4.1.12148.10.10.19.6.1.8ColumnbatteryMonitorSymmetryMajorAlarmLevelread-writecurrentThe major alarm limit
1.3.6.1.4.1.12148.10.10.19.6.1.9ColumnbatteryMonitorSymmetryMinorAlarmLevelread-writecurrentThe minor alarm limit
1.3.6.1.4.1.12148.10.10.20NodebatteryEnergyLog
1.3.6.1.4.1.12148.10.10.20.1ScalarbatteryEnergyLogAccumulatedread-onlycurrentThis is the accumulated energy delivered to/from battery.
1.3.6.1.4.1.12148.10.10.20.2ScalarbatteryEnergyLogLastHoursNumberOfEntriesread-onlycurrentThis is the maximal number of entries stored in battery hourly energy log.
1.3.6.1.4.1.12148.10.10.20.3TablebatteryEnergyLogLastHoursTablenot-accessiblecurrentThis table contains hourly energy log of battery.
1.3.6.1.4.1.12148.10.10.20.3.1RowbatteryEnergyLogLastHoursEntrynot-accessiblecurrent
1.3.6.1.4.1.12148.10.10.20.3.1.1ColumnbatteryEnergyLogLastHoursIndexnot-accessiblecurrentIndex used for navigating the rows 1..52 of batteryEnergyLogLastHoursTable
1.3.6.1.4.1.12148.10.10.20.3.1.2ColumnbatteryEnergyLogLastHoursValueread-onlycurrentEnergy value logged every hour.
1.3.6.1.4.1.12148.10.10.20.4ScalarbatteryEnergyLogLastDaysNumberOfEntriesread-onlycurrentThis is the maximal number of entries stored in battery daily energy log.
1.3.6.1.4.1.12148.10.10.20.5TablebatteryEnergyLogLastDaysTablenot-accessiblecurrentThis table contains daily energy log of battery.
1.3.6.1.4.1.12148.10.10.20.5.1RowbatteryEnergyLogLastDaysEntrynot-accessiblecurrent
1.3.6.1.4.1.12148.10.10.20.5.1.1ColumnbatteryEnergyLogLastDaysIndexnot-accessiblecurrentIndex used for navigating the rows 1..52 of batteryEnergyLogLastDaysTable
1.3.6.1.4.1.12148.10.10.20.5.1.2ColumnbatteryEnergyLogLastDaysValueread-onlycurrentEnergy value logged every day.
1.3.6.1.4.1.12148.10.10.20.6ScalarbatteryEnergyLogLastWeeksNumberOfEntriesread-onlycurrentThis is the maximal number of entries stored in battery weekly energy log.
1.3.6.1.4.1.12148.10.10.20.7TablebatteryEnergyLogLastWeeksTablenot-accessiblecurrentThis table contains weekly energy log of battery.
1.3.6.1.4.1.12148.10.10.20.7.1RowbatteryEnergyLogLastWeeksEntrynot-accessiblecurrent
1.3.6.1.4.1.12148.10.10.20.7.1.1ColumnbatteryEnergyLogLastWeeksIndexnot-accessiblecurrentIndex used for navigating the rows 1..52 of batteryEnergyLogLastWeekTable
1.3.6.1.4.1.12148.10.10.20.7.1.2ColumnbatteryEnergyLogLastWeeksValueread-onlycurrentEnergy value logged every week.
1.3.6.1.4.1.12148.10.10.21NodebatteryCycleLog
1.3.6.1.4.1.12148.10.10.21.1ScalarbatteryCycleLogTotalCyclesread-onlycurrentThis is the total number of battery discharge cycles.
1.3.6.1.4.1.12148.10.10.21.2ScalarbatteryCycleLogDaysNumberOfEntriesread-onlycurrentThis is the maximal number of entries stored in daily battery discharge cycle log.
1.3.6.1.4.1.12148.10.10.21.3TablebatteryCycleLogDaysTablenot-accessiblecurrentThis table contains daily battery discharge cycle log.
1.3.6.1.4.1.12148.10.10.21.3.1RowbatteryCycleLogDaysEntrynot-accessiblecurrent
1.3.6.1.4.1.12148.10.10.21.3.1.1ColumnbatteryCycleLogDaysIndexnot-accessiblecurrentIndex used for navigating the rows 1..52 of batteryCycleLogLastDaysTable
1.3.6.1.4.1.12148.10.10.21.3.1.2ColumnbatteryCycleLogDaysValueread-onlycurrentNumber of discharge cycles logged every day.
1.3.6.1.4.1.12148.10.10.21.4ScalarbatteryCycleLogWeeksNumberOfEntriesread-onlycurrentThis is the maximal number of entries stored in weeky battery discharge cycle log.
1.3.6.1.4.1.12148.10.10.21.5TablebatteryCycleLogWeeksTablenot-accessiblecurrentThis table contains weekly battery discharge cycle log.
1.3.6.1.4.1.12148.10.10.21.5.1RowbatteryCycleLogWeeksEntrynot-accessiblecurrent
1.3.6.1.4.1.12148.10.10.21.5.1.1ColumnbatteryCycleLogWeeksIndexnot-accessiblecurrentIndex used for navigating the rows 1..52 of batteryCycleLogLastWeeksTable
1.3.6.1.4.1.12148.10.10.21.5.1.2ColumnbatteryCycleLogWeeksValueread-onlycurrentNumber of discharge cycles logged every week.
1.3.6.1.4.1.12148.10.10.21.6ScalarbatteryCycleLogMonthsNumberOfEntriesread-onlycurrentThis is the maximal number of entries stored in monthly battery discharge cycle log.
1.3.6.1.4.1.12148.10.10.21.7TablebatteryCycleLogMonthsTablenot-accessiblecurrentThis table contains monthly battery discharge cycle log.
1.3.6.1.4.1.12148.10.10.21.7.1RowbatteryCycleLogMonthsEntrynot-accessiblecurrent
1.3.6.1.4.1.12148.10.10.21.7.1.1ColumnbatteryCycleLogMonthsIndexnot-accessiblecurrentIndex used for navigating the rows 1..52 of batteryCycleLogLastMonthTable
1.3.6.1.4.1.12148.10.10.21.7.1.2ColumnbatteryCycleLogMonthsValueread-onlycurrentNumber of discharge cycles logged every month.
1.3.6.1.4.1.12148.10.10.22NodebatteryEqualize
1.3.6.1.4.1.12148.10.10.22.1ScalarbatteryEqualizeVoltageread-writecurrentThe Voltage at which the DC System equalize charges the batteries.
1.3.6.1.4.1.12148.10.10.22.2ScalarbatteryEqualizeCommandread-writecurrentThis pushbutton will start or stop a manual battery equalize if the system allows it.
1.3.6.1.4.1.12148.10.10.22.3ScalarbatteryEqualizeCurrentThresholdread-writecurrentThe equalizing will terminate when the charge current drops below the EqualizeCurrentThreshold limit.
1.3.6.1.4.1.12148.10.10.22.4ScalarbatteryEqualizeManualMaxDurationread-writecurrentA protection against overcharging. When running manual equalize, the boosting will always terminate at this point.
1.3.6.1.4.1.12148.10.10.23NodebatteryAhCharged
1.3.6.1.4.1.12148.10.10.23.1ScalarbatteryAhChargedStatusread-onlycurrentThe status of the battery ah charged monitor.
1.3.6.1.4.1.12148.10.10.23.2ScalarbatteryAhChargedDescriptionread-writecurrentA textual description of the battery ah charged monitor. This is stored in the system controller and can be changed by the user
1.3.6.1.4.1.12148.10.10.23.3ScalarbatteryAhChargedTrapRepeatCounteraccessible-for-notifycurrentThe number of consecutive times this alamcondition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this tra…
1.3.6.1.4.1.12148.10.10.23.4ScalarbatteryAhChargedAlarmEnableread-writecurrentThis value once enabled, the alarm condition of the monitor will be reported.
1.3.6.1.4.1.12148.10.10.23.5ScalarbatteryAhChargedValueread-onlycurrentThe calculated battery ah (x100) charged value.
1.3.6.1.4.1.12148.10.10.23.6ScalarbatteryAhChargedMinorHighLevelread-writecurrentThe minor high alarm limit
1.3.6.1.4.1.12148.10.10.23.7ScalarbatteryAhChargedMajorHighLevelread-writecurrentThe major high alarm limit
1.3.6.1.4.1.12148.10.10.24NodebatteryAhDischarged
1.3.6.1.4.1.12148.10.10.24.1ScalarbatteryAhDischargedStatusread-onlycurrentThe status of the battery ah discharged monitor.
1.3.6.1.4.1.12148.10.10.24.2ScalarbatteryAhDischargedDescriptionread-writecurrentA textual description of the battery ah discharged monitor. This is stored in the system controller and can be changed by the user
1.3.6.1.4.1.12148.10.10.24.3ScalarbatteryAhDischargedTrapRepeatCounteraccessible-for-notifycurrentThe number of consecutive times this alamcondition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this tra…
1.3.6.1.4.1.12148.10.10.24.4ScalarbatteryAhDischargedAlarmEnableread-writecurrentThis value once enabled, the alarm condition of the monitor will be reported.
1.3.6.1.4.1.12148.10.10.24.5ScalarbatteryAhDischargedValueread-onlycurrentThe calculated battery ah (x100) discharged value.
1.3.6.1.4.1.12148.10.10.24.6ScalarbatteryAhDischargedMinorHighLevelread-writecurrentThe minor high alarm limit
1.3.6.1.4.1.12148.10.10.24.7ScalarbatteryAhDischargedMajorHighLevelread-writecurrentThe major high alarm limit
1.3.6.1.4.1.12148.10.10.25NodebatteryRunTimeLog
1.3.6.1.4.1.12148.10.10.25.1ScalarbatteryRunTimeAccumulatedread-onlycurrentThis is the accumulated running time of battery in hours.
1.3.6.1.4.1.12148.10.10.25.2ScalarbatteryRunTimeLogDaysNumberOfEntriesread-onlycurrentThis is the maximal number of entries stored in daily battery run time log.
1.3.6.1.4.1.12148.10.10.25.3TablebatteryRunTimeLogDaysTablenot-accessiblecurrentThis table contains daily battery run time log.
1.3.6.1.4.1.12148.10.10.25.3.1RowbatteryRunTimeLogDaysEntrynot-accessiblecurrent
1.3.6.1.4.1.12148.10.10.25.3.1.1ColumnbatteryRunTimeLogDaysIndexnot-accessiblecurrentIndex used for navigating the rows 1..52 of batteryRunTimeLogDaysTable
1.3.6.1.4.1.12148.10.10.25.3.1.2ColumnbatteryRunTimeLogDaysValueread-onlycurrentBattery running minutes logged every day.
1.3.6.1.4.1.12148.10.10.25.4ScalarbatteryRunTimeLogWeeksNumberOfEntriesread-onlycurrentThis is the maximal number of entries stored in weeky battery run time log.
1.3.6.1.4.1.12148.10.10.25.5TablebatteryRunTimeLogWeeksTablenot-accessiblecurrentThis table contains weekly battery run time log.
1.3.6.1.4.1.12148.10.10.25.5.1RowbatteryRunTimeLogWeeksEntrynot-accessiblecurrent
1.3.6.1.4.1.12148.10.10.25.5.1.1ColumnbatteryRunTimeLogWeeksIndexnot-accessiblecurrentIndex used for navigating the rows 1..52 of batteryRunTimeLogWeeksTable
1.3.6.1.4.1.12148.10.10.25.5.1.2ColumnbatteryRunTimeLogWeeksValueread-onlycurrentBattery running hours logged every week.
1.3.6.1.4.1.12148.10.10.25.6ScalarbatteryRunTimeLogMonthsNumberOfEntriesread-onlycurrentThis is the maximal number of entries stored in monthly battery run time log.
1.3.6.1.4.1.12148.10.10.25.7TablebatteryRunTimeLogMonthsTablenot-accessiblecurrentThis table contains monthly battery run time log.
1.3.6.1.4.1.12148.10.10.25.7.1RowbatteryRunTimeLogMonthsEntrynot-accessiblecurrent
1.3.6.1.4.1.12148.10.10.25.7.1.1ColumnbatteryRunTimeLogMonthsIndexnot-accessiblecurrentIndex used for navigating the rows 1..52 of batteryRunTimeLogMonthsTable
1.3.6.1.4.1.12148.10.10.25.7.1.2ColumnbatteryRunTimeLogMonthsValueread-onlycurrentBattery running hours logged every month.
1.3.6.1.4.1.12148.10.10.26NodebatteryModule
1.3.6.1.4.1.12148.10.10.26.1ScalarbatteryModuleNoOfBatteryModulesread-onlycurrentThe number of battery modules installed
1.3.6.1.4.1.12148.10.10.26.2NodebatteryModuleError
1.3.6.1.4.1.12148.10.10.26.2.1ScalarbatteryModuleErrorStatusread-onlycurrentThis status value shows if the number of failed units is higher than the defined alarm level.
1.3.6.1.4.1.12148.10.10.26.2.2ScalarbatteryModuleErrorDescriptionread-writecurrentA textual description of the battery error monitor. This is stored in the system controller and can be changed by the user
1.3.6.1.4.1.12148.10.10.26.2.3ScalarbatteryModuleErrorTrapRepeatCounteraccessible-for-notifycurrentThe number of consecutive times this alamcondition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this tra…
1.3.6.1.4.1.12148.10.10.26.2.4ScalarbatteryModuleErrorEnableread-writecurrentThis value once enabled, the alarm condition of the monitor will be reported.
1.3.6.1.4.1.12148.10.10.26.2.5ScalarbatteryModuleErrorValueread-onlycurrentThe number of failed batteries.
1.3.6.1.4.1.12148.10.10.26.2.6ScalarbatteryModuleErrorMajorAlarmLevelread-writecurrentThe major alarm limit
1.3.6.1.4.1.12148.10.10.26.2.7ScalarbatteryModuleErrorMinorAlarmLevelread-writecurrentThe minor alarm limit
1.3.6.1.4.1.12148.10.10.26.3NodebatteryModuleCommError
1.3.6.1.4.1.12148.10.10.26.3.1ScalarbatteryModuleCommErrorStatusread-onlycurrentThis status value shows if the number of failed units is higher than the defined alarm level.
1.3.6.1.4.1.12148.10.10.26.3.2ScalarbatteryModuleCommErrorDescriptionread-writecurrentA textual description of the battery comm error monitor. This is stored in the system controller and can be changed by the user
1.3.6.1.4.1.12148.10.10.26.3.3ScalarbatteryModuleCommErrorTrapRepeatCounteraccessible-for-notifycurrentThe number of consecutive times this alamcondition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this tra…
1.3.6.1.4.1.12148.10.10.26.3.4ScalarbatteryModuleCommErrorEnableread-writecurrentThis value once enabled, the alarm condition of the monitor will be reported.
1.3.6.1.4.1.12148.10.10.26.3.5ScalarbatteryModuleCommErrorValueread-onlycurrentThe number of batteries in comm error.
1.3.6.1.4.1.12148.10.10.26.3.6ScalarbatteryModuleCommErrorMajorAlarmLevelread-writecurrentThe major alarm limit
1.3.6.1.4.1.12148.10.10.26.3.7ScalarbatteryModuleCommErrorMinorAlarmLevelread-writecurrentThe minor alarm limit
1.3.6.1.4.1.12148.10.10.26.4TablebatteryModuleTablenot-accessiblecurrentInformation of individule battery module
1.3.6.1.4.1.12148.10.10.26.4.1RowbatteryModuleEntrynot-accessiblecurrent
1.3.6.1.4.1.12148.10.10.26.4.1.1ColumnbatteryModuleIndexnot-accessiblecurrentIndex used for navigating the rows 1..100 of batteryModuleTable
1.3.6.1.4.1.12148.10.10.26.4.1.2ColumnbatteryModuleStatusread-onlycurrentThe status value for the battery module
1.3.6.1.4.1.12148.10.10.26.4.1.3ColumnbatteryModuleBatteryVoltageread-onlycurrentBattery voltage value
1.3.6.1.4.1.12148.10.10.26.4.1.4ColumnbatteryModuleBatteryCurrentread-onlycurrentBattery current value
1.3.6.1.4.1.12148.10.10.26.4.1.5ColumnbatteryModuleBatteryRemCapread-onlycurrentBattery remaining capacity value
1.3.6.1.4.1.12148.10.10.26.4.1.6ColumnbatteryModuleBatteryTemperatureread-onlycurrentBattery temperature value
1.3.6.1.4.1.12148.10.10.26.4.1.7ColumnbatteryModuleBatteryQualityread-onlycurrentBattery quality value
1.3.6.1.4.1.12148.10.10.26.4.1.8ColumnbatteryModuleMaxChargeCurrentread-onlycurrentMaximal charging current in Amp
1.3.6.1.4.1.12148.10.10.26.4.1.9ColumnbatteryModuleMaxDischargeCurrentread-onlycurrentMaximal discharge current in Amp
1.3.6.1.4.1.12148.10.10.26.4.1.10ColumnbatteryModuleBatteryModeread-onlycurrentBattery mode
1.3.6.1.4.1.12148.10.10.26.4.1.11ColumnbatteryModuleChargeModeread-onlycurrentCharge mode
1.3.6.1.4.1.12148.10.10.26.4.1.12ColumnbatteryModuleManufacturerread-onlycurrentBattery manufaturer
1.3.6.1.4.1.12148.10.10.26.4.1.13ColumnbatteryModulePartNumberread-onlycurrentPart number
1.3.6.1.4.1.12148.10.10.26.4.1.14ColumnbatteryModuleSerialNumberread-onlycurrentSerial number
1.3.6.1.4.1.12148.10.10.26.4.1.15ColumnbatteryModuleSoftwareVersionread-onlycurrentSoftware version
1.3.6.1.4.1.12148.10.10.26.4.1.16ColumnbatteryModuleProductionDateread-onlycurrentDate of production
1.3.6.1.4.1.12148.10.10.26.4.1.17ColumnbatteryModuleAccumulatedAhChargedread-onlycurrentAccumulated Ah charged
1.3.6.1.4.1.12148.10.10.26.4.1.18ColumnbatteryModuleAccumulatedAhDischargedread-onlycurrentAccumulated Ah discharged
1.3.6.1.4.1.12148.10.10.26.4.1.19ColumnbatteryModuleNoOfChargeCyclesread-onlycurrentNumber of charge cycles
1.3.6.1.4.1.12148.10.10.26.4.1.20ColumnbatteryModuleNoOfDischargeCyclesread-onlycurrentNumber of discharge cycles
1.3.6.1.4.1.12148.10.11Nodeinputs
1.3.6.1.4.1.12148.10.11.1TableinputControlUnitsTablenot-accessiblecurrent
1.3.6.1.4.1.12148.10.11.1.1RowinputControlUnitsEntrynot-accessiblecurrent
1.3.6.1.4.1.12148.10.11.1.1.1ColumninputControlUnitIndexnot-accessiblecurrentIndex used for navigating the rows of inputControlUnitTable The size of the table is defined by the system
1.3.6.1.4.1.12148.10.11.1.1.2ColumninputControlUnitNumberOfInputsread-onlycurrentNumber of programmable inputs available in controller.
1.3.6.1.4.1.12148.10.11.2TableinputControlUnitInputTablenot-accessiblecurrentThis table contains the status of the programmable inputs for Control Units.
1.3.6.1.4.1.12148.10.11.2.1RowinputControlUnitInputEntrynot-accessiblecurrent
1.3.6.1.4.1.12148.10.11.2.1.1ColumninputControlUnitInputIndexnot-accessiblecurrentIndex used for navigating the rows of inputControlUnitInputTable The size of the table is defined by the inputControlUnitNumberOfInputs
1.3.6.1.4.1.12148.10.11.2.1.2ColumninputControlUnitInputStatusread-onlycurrentProgrammable input status.
1.3.6.1.4.1.12148.10.11.2.1.3ColumninputControlUnitInputDescriptionread-writecurrentA textual description of the programmable input. This is stored in the system controller and can be changed by the user.
1.3.6.1.4.1.12148.10.11.2.1.4ColumninputControlUnitInputTrapRepeatCounteraccessible-for-notifycurrentThe number of consecutive times this alamcondition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this tra…
1.3.6.1.4.1.12148.10.11.2.1.5ColumninputControlUnitInputAlarmEnableread-writecurrentThis will enable or disable this inputs Alarm functionality. Setting 'disabled' here will turn off lock the status to 'disabled' state
1.3.6.1.4.1.12148.10.11.2.1.6ColumninputControlUnitInputValueread-writecurrentThe inputs measured Value. Depending on the type of input, this may represent a Voltage, a Temperature, a Current or a Boolean value. Note: This value can only…
1.3.6.1.4.1.12148.10.11.2.1.7ColumninputControlUnitInputConfigurationread-writecurrentConfiguration of the input type. Configurations available for different controllers are as follows: SP2 Basic(normally open, normally closed); SP2 BasicInd(nor…
1.3.6.1.4.1.12148.10.11.3TableinputIoUnitsTablenot-accessiblecurrent
1.3.6.1.4.1.12148.10.11.3.1RowinputIoUnitsEntrynot-accessiblecurrent
1.3.6.1.4.1.12148.10.11.3.1.1ColumninputIoUnitIndexnot-accessiblecurrentIndex used for navigating the rows of inputIoUnitsTable The size of the table is defined by the system
1.3.6.1.4.1.12148.10.11.3.1.2ColumninputIoUnitNumberOfInputsread-onlycurrentNumber of programmable inputs available in IO unit.
1.3.6.1.4.1.12148.10.11.4TableinputIoUnitProgInputTablenot-accessiblecurrentThis table contains the status of the programmable inputs for I/O monitor units. .
1.3.6.1.4.1.12148.10.11.4.1RowinputIoUnitProgInputEntrynot-accessiblecurrent
1.3.6.1.4.1.12148.10.11.4.1.1ColumninputIoUnitProgInputIndexnot-accessiblecurrentThe Index to the Input of the selected I/O monitor unit. Or the input number if you like.
1.3.6.1.4.1.12148.10.11.4.1.2ColumninputIoUnitProgInputStatusread-onlycurrentProgrammable input status.
1.3.6.1.4.1.12148.10.11.4.1.3ColumninputIoUnitProgInputDescriptionread-writecurrentA textual description of the programmable input in IO unit. This is stored in the system controller and can be changed by the user.
1.3.6.1.4.1.12148.10.11.4.1.4ColumninputIoUnitProgInputTrapRepeatCounteraccessible-for-notifycurrentThe number of consecutive times this alamcondition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this tra…
1.3.6.1.4.1.12148.10.11.4.1.5ColumninputIoUnitProgInputAlarmEnableread-writecurrentThis will enable or disable this inputs Alarm functionality. Setting 'disabled' here will turn off lock the status to 'disabled' state
1.3.6.1.4.1.12148.10.11.4.1.6ColumninputIoUnitProgInputValueread-onlycurrentThe inputs measured Value. Depending on the type of input, this may represent a Voltage, a Temperature, a Current or a Boolean value.
1.3.6.1.4.1.12148.10.11.4.1.7ColumninputIoUnitProgInputConfigurationread-writecurrentConfiguration of the input type. Configurations available for IO unit are normally open, normally closed, diode matrix, voltage and clock. Note: If an input is…
1.3.6.1.4.1.12148.10.12Nodeoutputs
1.3.6.1.4.1.12148.10.12.1TableoutputControlUnitTablenot-accessiblecurrent
1.3.6.1.4.1.12148.10.12.1.1RowoutputControlUnitEntrynot-accessiblecurrent
1.3.6.1.4.1.12148.10.12.1.1.1ColumnoutputControlUnitIndexnot-accessiblecurrentIndex used for navigating the rows of outputControlUnitTable The size of the table is defined by the system
1.3.6.1.4.1.12148.10.12.1.1.2ColumnoutputControlUnitNumberOfOutputsread-onlycurrentNumber of outputs available in controller.
1.3.6.1.4.1.12148.10.12.2TableoutputControlUnitOutputTablenot-accessiblecurrentThis table contains the status of the outputs for Control Units.
1.3.6.1.4.1.12148.10.12.2.1RowoutputControlUnitOutputEntrynot-accessiblecurrent
1.3.6.1.4.1.12148.10.12.2.1.1ColumnoutputControlUnitOutputIndexnot-accessiblecurrentIndex used for navigating the rows of outputControlUnitoutputTable The size of the table is defined by the outputControlUnitNumberOfOutputs
1.3.6.1.4.1.12148.10.12.2.1.2ColumnoutputControlUnitOutputStatusread-onlycurrentGeneral output relays may be 'energized' or 'not energized'. 'energized' and 'not energized' correspond to normal and alarm condition respectively for normally…
1.3.6.1.4.1.12148.10.12.2.1.3ColumnoutputControlUnitOutputDescriptionread-writecurrentA textual description of the output. This is stored in the system controller and can be changed by the user.
1.3.6.1.4.1.12148.10.12.3TableoutputIoUnitTablenot-accessiblecurrent
1.3.6.1.4.1.12148.10.12.3.1RowoutputIoUnitEntrynot-accessiblecurrent
1.3.6.1.4.1.12148.10.12.3.1.1ColumnoutputIoUnitIndexnot-accessiblecurrentIndex used for navigating the rows of outputIoUnitTable The size of the table is defined by the system
1.3.6.1.4.1.12148.10.12.3.1.2ColumnoutputIoUnitNumberOfOutputsread-onlycurrentNumber of outputs available in IO unit.
1.3.6.1.4.1.12148.10.12.4TableoutputIoUnitOutputTablenot-accessiblecurrentThis table contains the status of the outputs for IO Units.
1.3.6.1.4.1.12148.10.12.4.1RowoutputIoUnitOutputEntrynot-accessiblecurrent
1.3.6.1.4.1.12148.10.12.4.1.1ColumnoutputIoUnitOutputIndexnot-accessiblecurrentIndex used for navigating the rows of outputIOUnitOutputTable The size of the table is defined by the outputIOUnitNumberOfOutputs
1.3.6.1.4.1.12148.10.12.4.1.2ColumnoutputIoUnitOutputStatusread-onlycurrentGeneral output relays may be 'energized' or 'not energized'. Latched contactors may have values 'disconnected' or 'connected'
1.3.6.1.4.1.12148.10.12.4.1.3ColumnoutputIoUnitOutputDescriptionread-writecurrentA textual description of the output in IO unit. This is stored in the system controller and can be changed by the user.
1.3.6.1.4.1.12148.10.13NodecontrolSystem
1.3.6.1.4.1.12148.10.13.1ScalarcontrolSystemStatusread-onlycurrentThe overall status of control system subsystem
1.3.6.1.4.1.12148.10.13.2ScalarcontrolSystemClockread-writecurrentThis is the system time.
1.3.6.1.4.1.12148.10.13.3ScalarcontrolSystemNumberOfControlUnitsread-writecurrentTotal number of main controllers (SP2 Master, SP2 Basic Ind, SP2 Basic, Compack, Smartpack S, Smartpack)
1.3.6.1.4.1.12148.10.13.4Nodesnmp
1.3.6.1.4.1.12148.10.13.4.1ScalarsnmpSendOffTrapsread-writecurrentWhen this is enabled, a trap is sent when a alarm condition goes off .
1.3.6.1.4.1.12148.10.13.4.2ScalarsnmpTrapRepeatRateread-writecurrentThe time between every repeated trap when an alarm condition is on. To turn repetetive traps off, set to zero. Can be 0 to 1440 minutes i.e 24 hours.
1.3.6.1.4.1.12148.10.13.4.3ScalarsnmpHeartBeatTrapRepeatRateread-writecurrentThe time between every heartbeat trap when an alarm condition is on. To turn heartbeat traps off, set to zero. Can be 0 to 1440 minutes i.e 24 hours.
1.3.6.1.4.1.12148.10.13.4.4ScalarsnmpInhibitTrapsread-writecurrentWhen this is enabled, no trap is sent regardless of alarm conditions.
1.3.6.1.4.1.12148.10.13.4.5ScalarsnmpResendTrapsread-writecurrentResend traps once for all active alarms
1.3.6.1.4.1.12148.10.13.4.6TablesnmpTrapsTargetAddressTablenot-accessiblecurrentThis table shows the trap target address. Note that it is NOT allowed to change or create SNMP v3 trap target address IPs.
1.3.6.1.4.1.12148.10.13.4.6.1RowsnmpTrapsTargetAddressEntrynot-accessiblecurrent
1.3.6.1.4.1.12148.10.13.4.6.1.1ColumnsnmpTrapsTargetAddressIndexnot-accessiblecurrent
1.3.6.1.4.1.12148.10.13.4.6.1.2ColumnsnmpTrapsTargetAddressIPread-writecurrentNote that it is only allowed to change or create SNMP v2c trap target address IPs.
1.3.6.1.4.1.12148.10.13.4.6.1.3ColumnsnmpTrapsTargetAddressPortread-onlycurrent
1.3.6.1.4.1.12148.10.13.4.6.1.4ColumnsnmpTrapsTargetAddressVersionread-onlycurrent
1.3.6.1.4.1.12148.10.13.5ScalarcontrolSystemResetManualAlarmsread-writecurrentReset manual alarms and put buzzer into silence.
1.3.6.1.4.1.12148.10.13.6ScalarcontrolSystemResetNumberOfModulesread-writecurrentIf set to '1', the number of modules (rectifier, solar charger, wind charger, control units, etc.) will be reset, and only those modules communicating are coun…
1.3.6.1.4.1.12148.10.13.7NodecontrolSystemIoUnits
1.3.6.1.4.1.12148.10.13.7.1ScalarcontrolSystemIoUnitsNumberOfUnitsread-writecurrentThis is the number of IO units installed in the system.
1.3.6.1.4.1.12148.10.13.7.2TablecontrolSystemIoUnitsTablenot-accessiblecurrent
1.3.6.1.4.1.12148.10.13.7.2.1RowcontrolSystemIoUnitsEntrynot-accessiblecurrent
1.3.6.1.4.1.12148.10.13.7.2.1.1ColumncontrolSystemIoUnitIndexnot-accessiblecurrentIndex used for navigating the rows of controlSystemIoUnitTable The size of the table is defined by the system
1.3.6.1.4.1.12148.10.13.7.2.1.2ColumncontrolSystemIoUnitNumberOfTemperaturesread-onlycurrentNumber of temperature measurements available in IO unit
1.3.6.1.4.1.12148.10.13.7.2.1.3ColumncontrolSystemIoUnitNumberOfFansread-onlycurrentNumber of fan measurements available in IO unit
1.3.6.1.4.1.12148.10.13.7.3TablecontrolSystemIoUnitTemperatureTablenot-accessiblecurrent
1.3.6.1.4.1.12148.10.13.7.3.1RowcontrolSystemIoUnitTemperatureEntrynot-accessiblecurrent
1.3.6.1.4.1.12148.10.13.7.3.1.1ColumncontrolSystemIoUnitTemperatureIndexnot-accessiblecurrentIndex used for navigating the rows of controlSystemIoUnitTemperatureTable The size of the table is defined by the controlSystemIoUnitNumberOfTemperatures
1.3.6.1.4.1.12148.10.13.7.3.1.2ColumncontrolSystemIoUnitTemperatureStatusread-onlycurrentThe status of temperature monitor
1.3.6.1.4.1.12148.10.13.7.3.1.3ColumncontrolSystemIoUnitTemperatureDescriptionread-writecurrentA textual description of the temperature monitor in control system. This is stored in the system controller and can be changed by the user.
1.3.6.1.4.1.12148.10.13.7.3.1.4ColumncontrolSystemIoUnitTemperatureTrapRepeatCounteraccessible-for-notifycurrentThe number of consecutive times this alamcondition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this tra…
1.3.6.1.4.1.12148.10.13.7.3.1.5ColumncontrolSystemIoUnitTemperatureAlarmEnableread-writecurrentThis value once enabled, the alarm condition of the monitor will be reported.
1.3.6.1.4.1.12148.10.13.7.3.1.6ColumncontrolSystemIoUnitTemperatureValueread-onlycurrentThe measured temperature value.
1.3.6.1.4.1.12148.10.13.7.3.1.7ColumncontrolSystemIoUnitTemperatureMajorHighLevelread-writecurrentThe major high alarm limit
1.3.6.1.4.1.12148.10.13.7.3.1.8ColumncontrolSystemIoUnitTemperatureMinorHighLevelread-writecurrentThe minor high alarm limit
1.3.6.1.4.1.12148.10.13.7.3.1.9ColumncontrolSystemIoUnitTemperatureMinorLowLevelread-writecurrentThe minor low alarm limit
1.3.6.1.4.1.12148.10.13.7.3.1.10ColumncontrolSystemIoUnitTemperatureMajorLowLevelread-writecurrentThe major low alarm limit
1.3.6.1.4.1.12148.10.13.7.4TablecontrolSystemIoUnitFanTablenot-accessiblecurrent
1.3.6.1.4.1.12148.10.13.7.4.1RowcontrolSystemIoUnitFanEntrynot-accessiblecurrent
1.3.6.1.4.1.12148.10.13.7.4.1.1ColumncontrolSystemIoUnitFanIndexnot-accessiblecurrentIndex used for navigating the rows 1..2 of ioUnitFan Table
1.3.6.1.4.1.12148.10.13.7.4.1.2ColumncontrolSystemIoUnitFanSpeedValueread-onlycurrentThe measured fan speed
1.3.6.1.4.1.12148.10.13.7.4.1.3ColumncontrolSystemIoUnitFanSpeedDeviationread-onlycurrentThe measured fan speed deviation
1.3.6.1.4.1.12148.10.13.7.4.1.4ColumncontrolSystemIoUnitFanControlread-onlycurrentFan speed control value in percentage
1.3.6.1.4.1.12148.10.13.8NodecontrolSystemInventory
1.3.6.1.4.1.12148.10.13.8.1ScalarcontrolUnitNumberOfUnitsread-onlycurrentTotal number of control units installed in system.
1.3.6.1.4.1.12148.10.13.8.2TablecontrolUnitTablenot-accessiblecurrentA table containing an inventory listing. Each row represent one of the system hardware unit that is connected to the can bus. These units are system controller…
1.3.6.1.4.1.12148.10.13.8.2.1RowcontrolUnitEntrynot-accessiblecurrentOne row in the table containing all hardware units connected to the canbus.
1.3.6.1.4.1.12148.10.13.8.2.1.1ColumncontrolUnitIndexnot-accessiblecurrentIndex used for navigating the rows of controlUnitTable The size of the table is defined by the controlUnitNumberOfUnits
1.3.6.1.4.1.12148.10.13.8.2.1.2ColumncontrolUnitDescriptionread-onlycurrentA textual description of the control unit
1.3.6.1.4.1.12148.10.13.8.2.1.3ColumncontrolUnitStatusread-onlycurrentThe overall status of the control unit.
1.3.6.1.4.1.12148.10.13.8.2.1.4ColumncontrolUnitSerialNumberread-onlycurrentSerial number of the control unit.
1.3.6.1.4.1.12148.10.13.8.2.1.5ColumncontrolUnitHwPartNumberread-onlycurrentHardware part number of the control unit.
1.3.6.1.4.1.12148.10.13.8.2.1.6ColumncontrolUnitHwVersionread-onlycurrentHardware version of the control unit.
1.3.6.1.4.1.12148.10.13.8.2.1.7ColumncontrolUnitSwPartNumberread-onlycurrentSoftware part number of the control unit.
1.3.6.1.4.1.12148.10.13.8.2.1.8ColumncontrolUnitSwVersionread-onlycurrentSoftware version of the control unit.
1.3.6.1.4.1.12148.10.13.9NodecurrentMonitors
1.3.6.1.4.1.12148.10.13.9.1ScalarcurrentMonitorsNumberOfUnitsread-writecurrentThis is the number of current monitors installed in the system.
1.3.6.1.4.1.12148.10.13.9.2TablecurrentMonitorsTablenot-accessiblecurrent
1.3.6.1.4.1.12148.10.13.9.2.1RowcurrentMonitorsEntrynot-accessiblecurrent
1.3.6.1.4.1.12148.10.13.9.2.1.1ColumncurrentMonitorIndexnot-accessiblecurrentIndex used for navigating the rows of currentMonitorsTable The size of the table is defined by the system
1.3.6.1.4.1.12148.10.13.9.2.1.2ColumncurrentMonitorTyperead-onlycurrentThis shows if the current monitor is configured as standard load monitor (1), load current monitor (2), rectifier current monitor (3), dcdc current monitor (4)…
1.3.6.1.4.1.12148.10.13.9.2.1.3ColumncurrentMonitorIdread-onlycurrentThis is the unit index for each current monitor type.
1.3.6.1.4.1.12148.10.13.9.2.1.4ColumncurrentMonitorNumberOfFusesread-onlycurrentNumber of fuse measurements in current monitor.
1.3.6.1.4.1.12148.10.13.9.2.1.5ColumncurrentMonitorNumberOfCurrentsread-onlycurrentNumber of current measurements in current monitor.
1.3.6.1.4.1.12148.10.13.9.3TablecurrentMonitorFuseTablenot-accessiblecurrent
1.3.6.1.4.1.12148.10.13.9.3.1RowcurrentMonitorFuseEntrynot-accessiblecurrent
1.3.6.1.4.1.12148.10.13.9.3.1.1ColumncurrentMonitorFuseIndexnot-accessiblecurrentIndex used for navigating the rows of currentMonitorFuseTable The size of the table is defined by the currentMonitorNumberOfFuses
1.3.6.1.4.1.12148.10.13.9.3.1.2ColumncurrentMonitorFuseStatusread-onlycurrentThe status of fuse in current monitor
1.3.6.1.4.1.12148.10.13.9.3.1.3ColumncurrentMonitorFuseDescriptionread-writecurrentA textual description of the fuse monitor. This is stored in the system controller and can be changed by the user.
1.3.6.1.4.1.12148.10.13.9.3.1.4ColumncurrentMonitorFuseTrapRepeatCounteraccessible-for-notifycurrentThe number of consecutive times this alamcondition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this tra…
1.3.6.1.4.1.12148.10.13.9.3.1.5ColumncurrentMonitorFuseAlarmEnableread-writecurrentThis value once enabled, the alarm condition of the monitor will be reported.
1.3.6.1.4.1.12148.10.13.9.3.1.6ColumncurrentMonitorFuseValueread-onlycurrentThe measured fuse value.
1.3.6.1.4.1.12148.10.13.9.4TablecurrentMonitorCurrentTablenot-accessiblecurrent
1.3.6.1.4.1.12148.10.13.9.4.1RowcurrentMonitorCurrentEntrynot-accessiblecurrent
1.3.6.1.4.1.12148.10.13.9.4.1.1ColumncurrentMonitorCurrentIndexnot-accessiblecurrentIndex used for navigating the rows of currentMonitorCurrentTable The size of the table is defined by the currentMonitorNumberOfCurrents
1.3.6.1.4.1.12148.10.13.9.4.1.2ColumncurrentMonitorCurrentStatusread-onlycurrentThe status of current in current monitor
1.3.6.1.4.1.12148.10.13.9.4.1.3ColumncurrentMonitorCurrentDescriptionread-writecurrentA textual description of the current monitor. This is stored in the system controller and can be changed by the user.
1.3.6.1.4.1.12148.10.13.9.4.1.4ColumncurrentMonitorCurrentTrapRepeatCounteraccessible-for-notifycurrentThe number of consecutive times this alamcondition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this tra…
1.3.6.1.4.1.12148.10.13.9.4.1.5ColumncurrentMonitorCurrentAlarmEnableread-writecurrentThis value once enabled, the alarm condition of the monitor will be reported.
1.3.6.1.4.1.12148.10.13.9.4.1.6ColumncurrentMonitorCurrentValueread-onlycurrentThe measured current value.
1.3.6.1.4.1.12148.10.13.9.4.1.7ColumncurrentMonitorCurrentMajorAlarmLevelread-writecurrentThe major alarm limit
1.3.6.1.4.1.12148.10.13.9.4.1.8ColumncurrentMonitorCurrentMinorAlarmLevelread-writecurrentThe minor alarm limit
1.3.6.1.4.1.12148.10.13.9.5TablecurrentMonitorEnergyLogAccumulatedTablenot-accessiblecurrentThis table contains the accumulated energy consumption measured in current monitor
1.3.6.1.4.1.12148.10.13.9.5.1RowcurrentMonitorEnergyLogAccumulatedEntrynot-accessiblecurrent
1.3.6.1.4.1.12148.10.13.9.5.1.1ColumncurrentMonitorEnergyLogAccumulatedread-onlycurrentThe accumulated energy consumption value
1.3.6.1.4.1.12148.10.13.9.6ScalarcurrentMonitorEnergyLogLastHoursNumberOfEntriesread-onlycurrentThis is the maximal number of entries stored in hourly energy log
1.3.6.1.4.1.12148.10.13.9.7TablecurrentMonitorEnergyLogLastHoursTablenot-accessiblecurrentThis table contains energy consumption values logged every hour in current monitor.
1.3.6.1.4.1.12148.10.13.9.7.1RowcurrentMonitorEnergyLogLastHoursEntrynot-accessiblecurrent
1.3.6.1.4.1.12148.10.13.9.7.1.1ColumncurrentMonitorEnergyLogLastHoursIndexnot-accessiblecurrentIndex used for navigating the rows 1..52 of currentMonitorEnergyLogLastHoursTable
1.3.6.1.4.1.12148.10.13.9.7.1.2ColumncurrentMonitorEnergyLogLastHoursValueread-onlycurrentEnergy consumption value logged every hour in current monitor.
1.3.6.1.4.1.12148.10.13.9.8ScalarcurrentMonitorEnergyLogLastDaysNumberOfEntriesread-onlycurrentThis is the maximal number of entries stored in daily energy log
1.3.6.1.4.1.12148.10.13.9.9TablecurrentMonitorEnergyLogLastDaysTablenot-accessiblecurrentThis table contains energy consumption values logged every day in current monitor.
1.3.6.1.4.1.12148.10.13.9.9.1RowcurrentMonitorEnergyLogLastDaysEntrynot-accessiblecurrent
1.3.6.1.4.1.12148.10.13.9.9.1.1ColumncurrentMonitorEnergyLogLastDaysIndexnot-accessiblecurrentIndex used for navigating the rows 1..52 of currentMonitorEnergyLogLastDaysTable
1.3.6.1.4.1.12148.10.13.9.9.1.2ColumncurrentMonitorEnergyLogLastDaysValueread-onlycurrentEnergy consumption value logged every day in current monitor.
1.3.6.1.4.1.12148.10.13.9.10ScalarcurrentMonitorEnergyLogLastWeeksNumberOfEntriesread-onlycurrentThis is the maximal number of entries stored in weekly energy log
1.3.6.1.4.1.12148.10.13.9.11TablecurrentMonitorEnergyLogLastWeeksTablenot-accessiblecurrentThis table contains energy consumption values logged every week in current monitor.
1.3.6.1.4.1.12148.10.13.9.11.1RowcurrentMonitorEnergyLogLastWeeksEntrynot-accessiblecurrent
1.3.6.1.4.1.12148.10.13.9.11.1.1ColumncurrentMonitorEnergyLogLastWeeksIndexnot-accessiblecurrentIndex used for navigating the rows 1..52 of currentMonitorEnergyLogLastWeekTable
1.3.6.1.4.1.12148.10.13.9.11.1.2ColumncurrentMonitorEnergyLogLastWeeksValueread-onlycurrentEnergy consumption value logged every week in current monitor.
1.3.6.1.4.1.12148.10.13.10NodeflexiMonitors
1.3.6.1.4.1.12148.10.13.10.1ScalarflexiMonitorsNumberOfUnitsread-writecurrentThis is the number of fleximonitors installed in the system.
1.3.6.1.4.1.12148.10.13.10.2TableflexiMonitorsTablenot-accessiblecurrent
1.3.6.1.4.1.12148.10.13.10.2.1RowflexiMonitorsEntrynot-accessiblecurrent
1.3.6.1.4.1.12148.10.13.10.2.1.1ColumnflexiMonitorIndexnot-accessiblecurrentIndex used for navigating the rows of flexiMonitorsTable The size of the table is defined by the system
1.3.6.1.4.1.12148.10.13.10.2.1.2ColumnflexiMonitorTyperead-onlycurrentThis shows if the fleximonitor is configured as battery monitor (1), load monitor (2), rectifier monitor (3), controller monitor(4), dcdc monitor (5), solar mo…
1.3.6.1.4.1.12148.10.13.10.2.1.3ColumnflexiMonitorIdread-onlycurrentThis is the unit index for each fleximonitor type.
1.3.6.1.4.1.12148.10.13.10.2.1.4ColumnflexiMonitorNumberOfInputsread-onlycurrentNumber of inputs in fleximonitor.
1.3.6.1.4.1.12148.10.13.10.2.1.5ColumnflexiMonitorNumberOfOutputsread-onlycurrentNumber of outputs in fleximonitor.
1.3.6.1.4.1.12148.10.13.10.2.1.6ColumnflexiMonitorNumberOfCurrentInputsread-onlycurrentNumber of current inputs in fleximonitor.
1.3.6.1.4.1.12148.10.13.10.3TableflexiMonitorInputTablenot-accessiblecurrent
1.3.6.1.4.1.12148.10.13.10.3.1RowflexiMonitorInputEntrynot-accessiblecurrent
1.3.6.1.4.1.12148.10.13.10.3.1.1ColumnflexiMonitorInputIndexnot-accessiblecurrentIndex used for navigating the rows of flexiMonitorInputTable The size of the table is defined by the flexiMonitorNumberOfInputs
1.3.6.1.4.1.12148.10.13.10.3.1.2ColumnflexiMonitorInputStatusread-onlycurrentProgrammable input status.
1.3.6.1.4.1.12148.10.13.10.3.1.3ColumnflexiMonitorInputDescriptionread-writecurrentA textual description of the programmable input. This is stored in the system controller and can be changed by the user. .
1.3.6.1.4.1.12148.10.13.10.3.1.4ColumnflexiMonitorInputTrapRepeatCounteraccessible-for-notifycurrentThe number of consecutive times this alamcondition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this tra…
1.3.6.1.4.1.12148.10.13.10.3.1.5ColumnflexiMonitorInputAlarmEnableread-writecurrentThis will enable or disable this inputs Alarm functionality. Setting 'disabled' here will turn off lock the status to 'disabled' state
1.3.6.1.4.1.12148.10.13.10.3.1.6ColumnflexiMonitorInputValueread-onlycurrentThe inputs measured Value. Depending on the type of input, this may represent a Voltage, a Temperature, a Current, a Speed or a Boolean value.
1.3.6.1.4.1.12148.10.13.10.3.1.7ColumnflexiMonitorInputConfigurationread-writecurrentConfiguration of the input type. Available configurations are: ProgIn-Normally Open(1), ProgIn-Normally Closed(2), Voltage(3), Temperature(4),Current(5),Speed(…
1.3.6.1.4.1.12148.10.13.10.4TableflexiMonitorOutputTablenot-accessiblecurrent
1.3.6.1.4.1.12148.10.13.10.4.1RowflexiMonitorOutputEntrynot-accessiblecurrent
1.3.6.1.4.1.12148.10.13.10.4.1.1ColumnflexiMonitorOutputIndexnot-accessiblecurrentIndex used for navigating the rows of flexiMonitorOutputTable The size of the table is defined by the flexiMonitorNumberOfOutputs
1.3.6.1.4.1.12148.10.13.10.4.1.2ColumnflexiMonitorOutputStatusread-onlycurrentGeneral output relays may be 'energized' or 'not energized'. 'energized' and 'not energized' correspond to normal and alarm condition respectively for normally…
1.3.6.1.4.1.12148.10.13.10.4.1.3ColumnflexiMonitorOutputDescriptionread-writecurrentA textual description of the output. This is stored in the system controller and can be changed by the user.
1.3.6.1.4.1.12148.10.13.10.5TableflexiMonitorCurrentInputTablenot-accessiblecurrent
1.3.6.1.4.1.12148.10.13.10.5.1RowflexiMonitorCurrentInputEntrynot-accessiblecurrent
1.3.6.1.4.1.12148.10.13.10.5.1.1ColumnflexiMonitorCurrentInputIndexnot-accessiblecurrentIndex used for navigating the rows of flexiMonitorInputTable The size of the table is defined by the flexiMonitorNumberOfInputs
1.3.6.1.4.1.12148.10.13.10.5.1.2ColumnflexiMonitorCurrentInputDescriptionread-onlycurrentA textual description of the programmable input. This is stored in the system controller and can be changed by the user. .
1.3.6.1.4.1.12148.10.13.10.5.1.3ColumnflexiMonitorCurrentInputPricePerKWread-writecurrentPrice per kW. To be used together with energy cost logs.
1.3.6.1.4.1.12148.10.13.10.5.1.4ColumnflexiMonitorCurrentInputCurrencyread-writecurrentThe currency used in energy cost logs.
1.3.6.1.4.1.12148.10.13.10.6ScalarflexiMonitorEnergyCostLogLastMonthsNumberOfEntriesread-onlycurrent
1.3.6.1.4.1.12148.10.13.10.7TableflexiMonitorEnergyCostLogLastMonthsTablenot-accessiblecurrent
1.3.6.1.4.1.12148.10.13.10.7.1RowflexiMonitorEnergyCostLogLastMonthsEntrynot-accessiblecurrent
1.3.6.1.4.1.12148.10.13.10.7.1.1ColumnflexiMonitorEnergyCostLogLastMonthsIndexnot-accessiblecurrentIndex used for navigating the rows 1..12
1.3.6.1.4.1.12148.10.13.10.7.1.2ColumnflexiMonitorEnergyCostLogLastMonthsMonthread-onlycurrentIndex by month
1.3.6.1.4.1.12148.10.13.10.7.1.3ColumnflexiMonitorEnergyCostLogLastMonthsEnergyread-onlycurrentEnergy in kWh
1.3.6.1.4.1.12148.10.13.10.7.1.4ColumnflexiMonitorEnergyCostLogLastMonthsCostread-onlycurrentEnergy cost
1.3.6.1.4.1.12148.10.13.10.8ScalarflexiMonitorEnergyCostLogLastYearsNumberOfEntriesread-onlycurrent
1.3.6.1.4.1.12148.10.13.10.9TableflexiMonitorEnergyCostLogLastYearsTablenot-accessiblecurrent
1.3.6.1.4.1.12148.10.13.10.9.1RowflexiMonitorEnergyCostLogLastYearsEntrynot-accessiblecurrent
1.3.6.1.4.1.12148.10.13.10.9.1.1ColumnflexiMonitorEnergyCostLogLastYearsIndexnot-accessiblecurrentIndex used for navigating the rows 1..12
1.3.6.1.4.1.12148.10.13.10.9.1.2ColumnflexiMonitorEnergyCostLogLastYearsYearread-onlycurrentIndex by year
1.3.6.1.4.1.12148.10.13.10.9.1.3ColumnflexiMonitorEnergyCostLogLastYearsEnergyread-onlycurrentEnergy in kWh
1.3.6.1.4.1.12148.10.13.10.9.1.4ColumnflexiMonitorEnergyCostLogLastYearsCostread-onlycurrentEnergy cost
1.3.6.1.4.1.12148.10.13.10.10TableflexiMonitorEnergyLogAccumulatedTablenot-accessiblecurrentThis table contains the accumulated energy consumption measured in fleximonitor
1.3.6.1.4.1.12148.10.13.10.10.1RowflexiMonitorEnergyLogAccumulatedEntrynot-accessiblecurrent
1.3.6.1.4.1.12148.10.13.10.10.1.1ColumnflexiMonitorEnergyLogAccumulatedread-onlycurrentThe accumulated energy consumption value
1.3.6.1.4.1.12148.10.13.10.11ScalarflexiMonitorEnergyLogLastHoursNumberOfEntriesread-onlycurrentThis is the maximal number of entries stored in hourly energy log
1.3.6.1.4.1.12148.10.13.10.12TableflexiMonitorEnergyLogLastHoursTablenot-accessiblecurrentThis table contains energy consumption values logged every hour in fleximonitor.
1.3.6.1.4.1.12148.10.13.10.12.1RowflexiMonitorEnergyLogLastHoursEntrynot-accessiblecurrent
1.3.6.1.4.1.12148.10.13.10.12.1.1ColumnflexiMonitorEnergyLogLastHoursIndexnot-accessiblecurrentIndex used for navigating the rows 1..52 of flexiMonitorEnergyLogLastHoursTable
1.3.6.1.4.1.12148.10.13.10.12.1.2ColumnflexiMonitorEnergyLogLastHoursValueread-onlycurrentEnergy consumption value logged every hour in fleximonitor.
1.3.6.1.4.1.12148.10.13.10.13ScalarflexiMonitorEnergyLogLastDaysNumberOfEntriesread-onlycurrentThis is the maximal number of entries stored in daily energy log
1.3.6.1.4.1.12148.10.13.10.14TableflexiMonitorEnergyLogLastDaysTablenot-accessiblecurrentThis table contains energy consumption values logged every day in fleximonitor.
1.3.6.1.4.1.12148.10.13.10.14.1RowflexiMonitorEnergyLogLastDaysEntrynot-accessiblecurrent
1.3.6.1.4.1.12148.10.13.10.14.1.1ColumnflexiMonitorEnergyLogLastDaysIndexnot-accessiblecurrentIndex used for navigating the rows 1..52 of flexiMonitorEnergyLogLastDaysTable
1.3.6.1.4.1.12148.10.13.10.14.1.2ColumnflexiMonitorEnergyLogLastDaysValueread-onlycurrentEnergy consumption value logged every day in fleximonitor.
1.3.6.1.4.1.12148.10.13.10.15ScalarflexiMonitorEnergyLogLastWeeksNumberOfEntriesread-onlycurrentThis is the maximal number of entries stored in weekly energy log
1.3.6.1.4.1.12148.10.13.10.16TableflexiMonitorEnergyLogLastWeeksTablenot-accessiblecurrentThis table contains energy consumption values logged every week in fleximonitor.
1.3.6.1.4.1.12148.10.13.10.16.1RowflexiMonitorEnergyLogLastWeeksEntrynot-accessiblecurrent
1.3.6.1.4.1.12148.10.13.10.16.1.1ColumnflexiMonitorEnergyLogLastWeeksIndexnot-accessiblecurrentIndex used for navigating the rows 1..52 of flexiMonitorEnergyLogLastWeeksTable
1.3.6.1.4.1.12148.10.13.10.16.1.2ColumnflexiMonitorEnergyLogLastWeeksValueread-onlycurrentEnergy consumption value logged every week in fleximonitor.
1.3.6.1.4.1.12148.10.13.11NodemainControlUnits
1.3.6.1.4.1.12148.10.13.11.1TablemainControlUnitsTablenot-accessiblecurrent
1.3.6.1.4.1.12148.10.13.11.1.1RowmainControlUnitsEntrynot-accessiblecurrent
1.3.6.1.4.1.12148.10.13.11.1.1.1ColumnmainControlUnitIndexnot-accessiblecurrentIndex used for navigating the rows of controlUnitTable The size of the table is defined by the system
1.3.6.1.4.1.12148.10.13.11.1.1.2ColumnmainControlUnitNumberOfTemperaturesread-onlycurrentTotal number of temperature measurements in main controller
1.3.6.1.4.1.12148.10.13.11.2TablemainControlUnitTemperatureTablenot-accessiblecurrent
1.3.6.1.4.1.12148.10.13.11.2.1RowmainControlUnitTemperatureEntrynot-accessiblecurrent
1.3.6.1.4.1.12148.10.13.11.2.1.1ColumnmainControlUnitTemperatureIndexnot-accessiblecurrentThis index denotes which row in the temperature input table. The size of the table is defined by the batteryBankNumberOfTemp
1.3.6.1.4.1.12148.10.13.11.2.1.2ColumnmainControlUnitTemperatureStatusread-onlycurrentThe status of battery temperature monitor
1.3.6.1.4.1.12148.10.13.11.2.1.3ColumnmainControlUnitTemperatureDescriptionread-writecurrentA textual description of the battery temperature monitor. This is stored in the system controller and can be changed by the user.
1.3.6.1.4.1.12148.10.13.11.2.1.4ColumnmainControlUnitTemperatureTrapRepeatCounteraccessible-for-notifycurrentThe number of consecutive times this alam condition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this tr…
1.3.6.1.4.1.12148.10.13.11.2.1.5ColumnmainControlUnitTemperatureAlarmEnableread-writecurrentThis value once enabled, the alarm condition of the monitor will be reported.
1.3.6.1.4.1.12148.10.13.11.2.1.6ColumnmainControlUnitTemperatureValueread-onlycurrentThe measured battery temperature.
1.3.6.1.4.1.12148.10.13.11.2.1.7ColumnmainControlUnitTemperatureMajorHighLevelread-writecurrentThe major high alarm limit
1.3.6.1.4.1.12148.10.13.11.2.1.8ColumnmainControlUnitTemperatureMinorHighLevelread-writecurrentThe minor high alarm limit
1.3.6.1.4.1.12148.10.13.11.2.1.9ColumnmainControlUnitTemperatureMinorLowLevelread-writecurrentThe minor low alarm limit
1.3.6.1.4.1.12148.10.13.11.2.1.10ColumnmainControlUnitTemperatureMajorLowLevelread-writecurrentThe major low alarm limit
1.3.6.1.4.1.12148.10.13.11.3TablemainControlUnitEarthFaultTablenot-accessiblecurrent
1.3.6.1.4.1.12148.10.13.11.3.1RowmainControlUnitEarthFaultEntrynot-accessiblecurrent
1.3.6.1.4.1.12148.10.13.11.3.1.1ColumnmainControlUnitEarthFaultStatusread-onlycurrentThis status value shows if the earth resistance is lower than the defined alarm level.
1.3.6.1.4.1.12148.10.13.11.3.1.2ColumnmainControlUnitEarthFaultDescriptionread-writecurrentA textual description of the earth fault monitor. This is stored in the system controller and can be changed by the user.
1.3.6.1.4.1.12148.10.13.11.3.1.3ColumnmainControlUnitEarthFaultTrapRepeatCounteraccessible-for-notifycurrentThe number of consecutive times this alam condition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this tr…
1.3.6.1.4.1.12148.10.13.11.3.1.4ColumnmainControlUnitEarthFaultAlarmEnableread-writecurrentThis value once enabled, the alarm condition of the monitor will be reported.
1.3.6.1.4.1.12148.10.13.11.3.1.5ColumnmainControlUnitEarthFaultValueread-onlycurrentThe measured value of the earth resistance in kOhm.
1.3.6.1.4.1.12148.10.13.11.3.1.6ColumnmainControlUnitEarthFaultMajorAlarmLevelread-writecurrentThe major alarm limit
1.3.6.1.4.1.12148.10.13.12NodecontrolSystemSummary
1.3.6.1.4.1.12148.10.13.12.1NodemainControlUnitsError
1.3.6.1.4.1.12148.10.13.12.1.1ScalarmainControlUnitsErrorStatusread-onlycurrentThis status value shows if the number of failed main controllers is higher than the defined alarm level.
1.3.6.1.4.1.12148.10.13.12.1.2ScalarmainControlUnitsErrorDescriptionread-writecurrentA textual description of the main control units error monitor. This is stored in the system controller and can be changed by the user.
1.3.6.1.4.1.12148.10.13.12.1.3ScalarmainControlUnitsErrorTrapRepeatCounteraccessible-for-notifycurrentThe number of consecutive times this alam condition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this tr…
1.3.6.1.4.1.12148.10.13.12.1.4ScalarmainControlUnitsErrorAlarmEnableread-writecurrentThis value once enabled, the alarm condition of the monitor will be reported.
1.3.6.1.4.1.12148.10.13.12.1.5ScalarmainControlUnitsErrorValueread-onlycurrentThe detected number of failed main controllers.
1.3.6.1.4.1.12148.10.13.12.1.6ScalarmainControlUnitsErrorMajorAlarmLevelread-writecurrentThe major alarm limit
1.3.6.1.4.1.12148.10.13.12.1.7ScalarmainControlUnitsErrorMinorAlarmLevelread-writecurrentThe minor alarm limit
1.3.6.1.4.1.12148.10.13.12.2NodesmartNodeError
1.3.6.1.4.1.12148.10.13.12.2.1ScalarsmartNodeErrorStatusread-onlycurrentThis status value shows if the number of failed smartnodes is higher than the defined alarm level.
1.3.6.1.4.1.12148.10.13.12.2.2ScalarsmartNodeErrorDescriptionread-writecurrentA textual description of the smartnode error monitor. This is stored in the system controller and can be changed by the user.
1.3.6.1.4.1.12148.10.13.12.2.3ScalarsmartNodeErrorTrapRepeatCounteraccessible-for-notifycurrentThe number of consecutive times this alam condition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this tr…
1.3.6.1.4.1.12148.10.13.12.2.4ScalarsmartNodeErrorAlarmEnableread-writecurrentThis value once enabled, the alarm condition of the monitor will be reported.
1.3.6.1.4.1.12148.10.13.12.2.5ScalarsmartNodeErrorValueread-onlycurrentThe detected number of failed smartnodes.
1.3.6.1.4.1.12148.10.13.12.2.6ScalarsmartNodeErrorMajorAlarmLevelread-writecurrentThe major alarm limit
1.3.6.1.4.1.12148.10.13.12.2.7ScalarsmartNodeErrorMinorAlarmLevelread-writecurrentThe minor alarm limit
1.3.6.1.4.1.12148.10.13.12.3NodebatteryMonitorError
1.3.6.1.4.1.12148.10.13.12.3.1ScalarbatteryMonitorErrorStatusread-onlycurrentThis status value shows if the number of failed battery monitors is higher than the defined alarm level.
1.3.6.1.4.1.12148.10.13.12.3.2ScalarbatteryMonitorErrorDescriptionread-writecurrentA textual description of the battery monitor error monitor. This is stored in the system controller and can be changed by the user.
1.3.6.1.4.1.12148.10.13.12.3.3ScalarbatteryMonitorErrorTrapRepeatCounteraccessible-for-notifycurrentThe number of consecutive times this alam condition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this tr…
1.3.6.1.4.1.12148.10.13.12.3.4ScalarbatteryMonitorErrorAlarmEnableread-writecurrentThis value once enabled, the alarm condition of the monitor will be reported.
1.3.6.1.4.1.12148.10.13.12.3.5ScalarbatteryMonitorErrorValueread-onlycurrentThe detected number of failed battery monitors.
1.3.6.1.4.1.12148.10.13.12.3.6ScalarbatteryMonitorErrorMajorAlarmLevelread-writecurrentThe major alarm limit
1.3.6.1.4.1.12148.10.13.12.3.7ScalarbatteryMonitorErrorMinorAlarmLevelread-writecurrentThe minor alarm limit
1.3.6.1.4.1.12148.10.13.12.4NodeloadMonitorError
1.3.6.1.4.1.12148.10.13.12.4.1ScalarloadMonitorErrorStatusread-onlycurrentThis status value shows if the number of failed load monitors is higher than the defined alarm level.
1.3.6.1.4.1.12148.10.13.12.4.2ScalarloadMonitorErrorDescriptionread-writecurrentA textual description of the load monitor error monitor. This is stored in the system controller and can be changed by the user.
1.3.6.1.4.1.12148.10.13.12.4.3ScalarloadMonitorErrorTrapRepeatCounteraccessible-for-notifycurrentThe number of consecutive times this alam condition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this tr…
1.3.6.1.4.1.12148.10.13.12.4.4ScalarloadMonitorErrorAlarmEnableread-writecurrentThis value once enabled, the alarm condition of the monitor will be reported.
1.3.6.1.4.1.12148.10.13.12.4.5ScalarloadMonitorErrorValueread-onlycurrentThe detected number of failed load monitors.
1.3.6.1.4.1.12148.10.13.12.4.6ScalarloadMonitorErrorMajorAlarmLevelread-writecurrentThe major alarm limit
1.3.6.1.4.1.12148.10.13.12.4.7ScalarloadMonitorErrorMinorAlarmLevelread-writecurrentThe minor alarm limit
1.3.6.1.4.1.12148.10.13.12.5NodeioUnitError
1.3.6.1.4.1.12148.10.13.12.5.1ScalarioUnitErrorStatusread-onlycurrentThis status value shows if the number of failed IO units is higher than the defined alarm level.
1.3.6.1.4.1.12148.10.13.12.5.2ScalarioUnitErrorDescriptionread-writecurrentA textual description of the IO unit error monitor. This is stored in the system controller and can be changed by the user.
1.3.6.1.4.1.12148.10.13.12.5.3ScalarioUnitErrorTrapRepeatCounteraccessible-for-notifycurrentThe number of consecutive times this alam condition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this tr…
1.3.6.1.4.1.12148.10.13.12.5.4ScalarioUnitErrorAlarmEnableread-writecurrentThis value once enabled, the alarm condition of the monitor will be reported.
1.3.6.1.4.1.12148.10.13.12.5.5ScalarioUnitErrorValueread-onlycurrentThe detected number of failed IO units.
1.3.6.1.4.1.12148.10.13.12.5.6ScalarioUnitErrorMajorAlarmLevelread-writecurrentThe major alarm limit
1.3.6.1.4.1.12148.10.13.12.5.7ScalarioUnitErrorMinorAlarmLevelread-writecurrentThe minor alarm limit
1.3.6.1.4.1.12148.10.13.12.6NodemainsMonitorError
1.3.6.1.4.1.12148.10.13.12.6.1ScalarmainsMonitorErrorStatusread-onlycurrentThis status value shows if the number of failed mains monitors is higher than the defined alarm level.
1.3.6.1.4.1.12148.10.13.12.6.2ScalarmainsMonitorErrorDescriptionread-writecurrentA textual description of the mains monitor error monitor. This is stored in the system controller and can be changed by the user.
1.3.6.1.4.1.12148.10.13.12.6.3ScalarmainsMonitorErrorTrapRepeatCounteraccessible-for-notifycurrentThe number of consecutive times this alam condition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this tr…
1.3.6.1.4.1.12148.10.13.12.6.4ScalarmainsMonitorErrorAlarmEnableread-writecurrentThis value once enabled, the alarm condition of the monitor will be reported.
1.3.6.1.4.1.12148.10.13.12.6.5ScalarmainsMonitorErrorValueread-onlycurrentThe detected number of failed mains monitors.
1.3.6.1.4.1.12148.10.13.12.6.6ScalarmainsMonitorErrorMajorAlarmLevelread-writecurrentThe major alarm limit
1.3.6.1.4.1.12148.10.13.12.6.7ScalarmainsMonitorErrorMinorAlarmLevelread-writecurrentThe minor alarm limit
1.3.6.1.4.1.12148.10.13.12.7NodeflexiMonitorError
1.3.6.1.4.1.12148.10.13.12.7.1ScalarflexiMonitorErrorStatusread-onlycurrentThis status value shows if the number of failed flexi monitors is higher than the defined alarm level.
1.3.6.1.4.1.12148.10.13.12.7.2ScalarflexiMonitorErrorDescriptionread-writecurrentA textual description of the flexi monitor error monitor. This is stored in the system controller and can be changed by the user.
1.3.6.1.4.1.12148.10.13.12.7.3ScalarflexiMonitorErrorTrapRepeatCounteraccessible-for-notifycurrentThe number of consecutive times this alam condition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this tr…
1.3.6.1.4.1.12148.10.13.12.7.4ScalarflexiMonitorErrorAlarmEnableread-writecurrentThis value once enabled, the alarm condition of the monitor will be reported.
1.3.6.1.4.1.12148.10.13.12.7.5ScalarflexiMonitorErrorValueread-onlycurrentThe detected number of failed flexi monitors.
1.3.6.1.4.1.12148.10.13.12.7.6ScalarflexiMonitorErrorMajorAlarmLevelread-writecurrentThe major alarm limit
1.3.6.1.4.1.12148.10.13.12.7.7ScalarflexiMonitorErrorMinorAlarmLevelread-writecurrentThe minor alarm limit
1.3.6.1.4.1.12148.10.13.13NodeambientTemperature
1.3.6.1.4.1.12148.10.13.13.1ScalarambientTemperatureStatusread-onlycurrentThe state of the ambient temperature can be either one of the defined enumerated values
1.3.6.1.4.1.12148.10.13.13.2ScalarambientTemperatureDescriptionread-writecurrentA textual description of the ambient temperature monitor. This is stored in the system controller and can be changed by the user.
1.3.6.1.4.1.12148.10.13.13.3ScalarambientTemperatureTrapRepeatCounteraccessible-for-notifycurrentThe number of consecutive times this alamcondition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this tra…
1.3.6.1.4.1.12148.10.13.13.4ScalarambientTemperatureAlarmEnableread-writecurrentThis value once enabled, the alarm condition of the monitor will be reported.
1.3.6.1.4.1.12148.10.13.13.5ScalarambientTemperatureValueread-onlycurrentThe highest value of the enabled ambient temperature measurements. Depending on the global setting in the Control unit, this value will be presented in Celsius…
1.3.6.1.4.1.12148.10.13.13.6ScalarambientTemperatureMajorHighLevelread-writecurrentThe major high alarm limit
1.3.6.1.4.1.12148.10.13.13.7ScalarambientTemperatureMinorHighLevelread-writecurrentThe minor high alarm limit
1.3.6.1.4.1.12148.10.13.13.8ScalarambientTemperatureMinorLowLevelread-writecurrentThe minor low alarm limit
1.3.6.1.4.1.12148.10.13.13.9ScalarambientTemperatureMajorLowLevelread-writecurrentThe major low alarm limit
1.3.6.1.4.1.12148.10.13.14NodedeltaTemperature
1.3.6.1.4.1.12148.10.13.14.1ScalardeltaTemperatureStatusread-onlycurrentThe state of the delta temperature can be either one of the defined enumerated values
1.3.6.1.4.1.12148.10.13.14.2ScalardeltaTemperatureDescriptionread-writecurrentA textual description of the delta temperature monitor. This is stored in the system controller and can be changed by the user.
1.3.6.1.4.1.12148.10.13.14.3ScalardeltaTemperatureTrapRepeatCounteraccessible-for-notifycurrentThe number of consecutive times this alamcondition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this tra…
1.3.6.1.4.1.12148.10.13.14.4ScalardeltaTemperatureAlarmEnableread-writecurrentThis value once enabled, the alarm condition of the monitor will be reported.
1.3.6.1.4.1.12148.10.13.14.5ScalardeltaTemperatureValueread-onlycurrentThe delta temperature value. Depending on the global setting in the Control unit, this value will be presented in Celsius or Fahrenheit.
1.3.6.1.4.1.12148.10.13.14.6ScalardeltaTemperatureMajorHighLevelread-writecurrentThe major high alarm limit
1.3.6.1.4.1.12148.10.13.14.7ScalardeltaTemperatureMinorHighLevelread-writecurrentThe minor high alarm limit
1.3.6.1.4.1.12148.10.13.14.8ScalardeltaTemperatureMinorLowLevelread-writecurrentThe minor low alarm limit
1.3.6.1.4.1.12148.10.13.14.9ScalardeltaTemperatureMajorLowLevelread-writecurrentThe major low alarm limit
1.3.6.1.4.1.12148.10.13.15NodeuserSuspended
1.3.6.1.4.1.12148.10.13.15.1ScalaruserSuspendedStatusread-onlycurrentThis status value shows if the number of failed attempts is higher than the defined alarm level.
1.3.6.1.4.1.12148.10.13.15.2ScalaruserSuspendedDescriptionread-writecurrentA textual description of the login failure monitor. This is stored in the system controller and can be changed by the user.
1.3.6.1.4.1.12148.10.13.15.3ScalaruserSuspendedTrapRepeatCounteraccessible-for-notifycurrentThe number of consecutive times this alam condition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this tr…
1.3.6.1.4.1.12148.10.13.15.4ScalaruserSuspendedAlarmEnableread-writecurrentThis value once enabled, the alarm condition of the monitor will be reported.
1.3.6.1.4.1.12148.10.13.15.5ScalaruserSuspendedValueread-onlycurrentThe detected number of failed attempts.
1.3.6.1.4.1.12148.10.13.15.6ScalaruserSuspendedMajorAlarmLevelread-writecurrentThe major alarm limit
1.3.6.1.4.1.12148.10.13.16ScalarcontrolSystemSaveEnergyLogread-writecurrentSave energy logs to FTP server.
1.3.6.1.4.1.12148.10.13.17ScalarcontrolSystemSaveDataLogread-writecurrentSave data logs to FTP server.
1.3.6.1.4.1.12148.10.13.18ScalarcontrolSystemNTPServerIPread-writecurrent
1.3.6.1.4.1.12148.10.13.19ScalarcontrolSystemRebootread-writecurrentReboot main controller (Smartpack 2, Smartpack S, Compack, Smartpack 2 TOUCH)
1.3.6.1.4.1.12148.10.13.20ScalarcontrolSystemSaveEventLogread-writecurrentSave event logs to FTP server.
1.3.6.1.4.1.12148.10.13.21ScalarcontrolSystemSaveAccountLogread-writecurrentSave account logs to FTP server.
1.3.6.1.4.1.12148.10.13.22ScalarcontrolSystemSetCfgFromXmlFilesread-writecurrentSet configurations from default1.XML, default2.XML and default3.XML in Default folder
1.3.6.1.4.1.12148.10.13.23ScalarcontrolSystemNumberOfGenericModbusDataread-onlycurrentNumber of genaric Modbus data configured in system
1.3.6.1.4.1.12148.10.13.24TablecontrolSystemGenericModbusDataTablenot-accessiblecurrent
1.3.6.1.4.1.12148.10.13.24.1RowcontrolSystemGenericModbusDataEntrynot-accessiblecurrent
1.3.6.1.4.1.12148.10.13.24.1.1ColumncontrolSystemGenericModbusDataIndexnot-accessiblecurrentIndex used for navigating the rows of table The size of the table is defined by the system
1.3.6.1.4.1.12148.10.13.24.1.2ColumncontrolSystemGenericModbusDataDescriptionread-onlycurrentdescription of generic Modbus data
1.3.6.1.4.1.12148.10.13.24.1.3ColumncontrolSystemGenericModbusDataValueread-onlycurrentValue of generic Modbus data
1.3.6.1.4.1.12148.10.13.24.1.4ColumncontrolSystemGenericModbusDataUnitread-onlycurrentUnit of generic Modbus data
1.3.6.1.4.1.12148.10.13.25NodedemandResponse
1.3.6.1.4.1.12148.10.13.25.1ScalardemandResponseStatusread-onlycurrentStatus of demand response
1.3.6.1.4.1.12148.10.13.25.2ScalardemandResponseMinBatteryBackupTimeread-writecurrentThis parameter set the required minimum battery backup time in minutes for this system. The controller must ensure that there always are at least the required …
1.3.6.1.4.1.12148.10.13.25.3ScalardemandResponsePowerForecastread-onlycurrentThis is an average load power in watt during last 52 hours
1.3.6.1.4.1.12148.10.13.25.4ScalardemandResponseAvailableEnergyread-onlycurrentEstimated available energy based on the battery capacity, the load power and the expected backup time of the load groups
1.3.6.1.4.1.12148.10.13.25.5ScalardemandResponseBatteryDischargePowerread-writecurrentThis parameter controls the discharge power of the battery during an DSR event. Scale is 0.01kw
1.3.6.1.4.1.12148.10.13.25.6ScalardemandResponseMaxTimeread-writecurrentThe maximum discharge duration in minutes
1.3.6.1.4.1.12148.10.13.25.7ScalardemandResponseControlread-writecurrentActivate/deactivate demand response
1.3.6.1.4.1.12148.10.13.26TablegenericAlarmMonitorTablenot-accessiblecurrentgeneric alarm monitors to be used with 3rd-party modbus devices
1.3.6.1.4.1.12148.10.13.26.1RowgenericAlarmMonitorEntrynot-accessiblecurrent
1.3.6.1.4.1.12148.10.13.26.1.1ColumngenericAlarmMonitorIndexnot-accessiblecurrent
1.3.6.1.4.1.12148.10.13.26.1.2ColumngenericAlarmMonitorStatusread-onlycurrentThe state of the alarm monitor can be either one of the defined enumerated values
1.3.6.1.4.1.12148.10.13.26.1.3ColumngenericAlarmMonitorDescriptionread-writecurrentA textual description of the generic alarm monitor. This is stored in the system controller and can be changed by the user.
1.3.6.1.4.1.12148.10.13.26.1.4ColumngenericAlarmMonitorTrapRepeatCounteraccessible-for-notifycurrentThe number of consecutive times this alamcondition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this tra…
1.3.6.1.4.1.12148.10.13.26.1.5ColumngenericAlarmMonitorAlarmEnableread-writecurrentThis value once enabled, the alarm condition of the monitor will be reported.
1.3.6.1.4.1.12148.10.13.26.1.6ColumngenericAlarmMonitorValueread-onlycurrentThe generic alarm monitor value. Scale is dependent on the scale setting of the corresponding generic modbus value.
1.3.6.1.4.1.12148.10.13.26.1.7ColumngenericAlarmMonitorUnitread-onlycurrentA textual description of the unit of generic alarm monitor.
1.3.6.1.4.1.12148.10.13.27TablegenericLogsTablenot-accessiblecurrentGeneric logs connected to the last ten generic alarm monitors (#91-#100)
1.3.6.1.4.1.12148.10.13.27.1RowgenericLogsEntrynot-accessiblecurrent
1.3.6.1.4.1.12148.10.13.27.1.1ColumngenericLogsIndexnot-accessiblecurrentgeneric log index 1...10
1.3.6.1.4.1.12148.10.13.27.1.2ColumngenericLogsAccumulatedread-onlycurrentThis is the accumulated trip log value in hours.
1.3.6.1.4.1.12148.10.13.27.1.3ColumngenericLogsDaysNumberOfEntriesread-onlycurrentThis is the maximal number of entries stored in daily log
1.3.6.1.4.1.12148.10.13.27.1.4ColumngenericLogsWeeksNumberOfEntriesread-onlycurrentThis is the maximal number of entries stored in weekly log
1.3.6.1.4.1.12148.10.13.27.1.5ColumngenericLogsMonthsNumberOfEntriesread-onlycurrentThis is the maximal number of entries stored in monthly log
1.3.6.1.4.1.12148.10.13.28TablegenericLogDaysTablenot-accessiblecurrentThis table contains daily generic log.
1.3.6.1.4.1.12148.10.13.28.1RowgenericLogDaysEntrynot-accessiblecurrent
1.3.6.1.4.1.12148.10.13.28.1.1ColumngenericLogDaysIndexnot-accessiblecurrentIndex used for navigating the rows 1..52 of genericLogDaysTable
1.3.6.1.4.1.12148.10.13.28.1.2ColumngenericLogDaysValueread-onlycurrentgeneric monitor value in minutes logged every day.
1.3.6.1.4.1.12148.10.13.29TablegenericLogWeeksTablenot-accessiblecurrentThis table contains weekly generic log.
1.3.6.1.4.1.12148.10.13.29.1RowgenericLogWeeksEntrynot-accessiblecurrent
1.3.6.1.4.1.12148.10.13.29.1.1ColumngenericLogWeeksIndexnot-accessiblecurrentIndex used for navigating the rows 1..52 of genericLogWeeksTable
1.3.6.1.4.1.12148.10.13.29.1.2ColumngenericLogWeeksValueread-onlycurrentgeneric monitor value in hours logged every week.
1.3.6.1.4.1.12148.10.13.30TablegenericLogMonthsTablenot-accessiblecurrentThis table contains monthly generic log.
1.3.6.1.4.1.12148.10.13.30.1RowgenericLogMonthsEntrynot-accessiblecurrent
1.3.6.1.4.1.12148.10.13.30.1.1ColumngenericLogMonthsIndexnot-accessiblecurrentIndex used for navigating the rows 1..52 of genericLogMonthsTable
1.3.6.1.4.1.12148.10.13.30.1.2ColumngenericLogMonthsValueread-onlycurrentgeneric monitor value in hours logged every month.
1.3.6.1.4.1.12148.10.13.31NodetariffControl
1.3.6.1.4.1.12148.10.13.31.1ScalartariffControlEnableread-writecurrentEnable/disable tariff control function
1.3.6.1.4.1.12148.10.13.31.2ScalartariffControlChargeInhibitread-writecurrentEnable/disable battery charge inhibit
1.3.6.1.4.1.12148.10.13.31.3ScalartariffControlMaxTimeread-writecurrentThe maximum discharge duration in minutes
1.3.6.1.4.1.12148.10.13.31.4ScalartariffControlBatteryVoltageStopControlread-writecurrentEnable/disable battery voltage stop control
1.3.6.1.4.1.12148.10.13.31.5ScalartariffControlBatteryVoltageStopLimitread-writecurrent
1.3.6.1.4.1.12148.10.13.31.6ScalartariffControlBatteryVoltageHysteresisread-writecurrent
1.3.6.1.4.1.12148.10.13.31.7ScalartariffControlActivateread-writecurrentActivate/deactivate demand response
1.3.6.1.4.1.12148.10.14NodealarmGroups
1.3.6.1.4.1.12148.10.14.1TablealarmGroupTablenot-accessiblecurrent
1.3.6.1.4.1.12148.10.14.1.1RowalarmGroupEntrynot-accessiblecurrent
1.3.6.1.4.1.12148.10.14.1.1.1ColumnalarmGroupIndexnot-accessiblecurrentIndex used for navigating the rows 1..49 of alarmGroupTable
1.3.6.1.4.1.12148.10.14.1.1.2ColumnalarmGroupStatusread-onlycurrentThe status of alarm group
1.3.6.1.4.1.12148.10.14.1.1.3ColumnalarmGroupDescriptionread-writecurrentA textual description of the alarm group. This is stored in the system controller and can be changed by the user.
1.3.6.1.4.1.12148.10.15NodebatteryGroup2
1.3.6.1.4.1.12148.10.15.1ScalarbatteryGroup2Statusread-onlycurrentA toplevel status for the battery group 2.The state of this reflects the status of all underlying statuses for the battery. Any change in one of the 'data moni…
1.3.6.1.4.1.12148.10.15.2ScalarbatteryGroup2Descriptionread-writecurrentA descriptive name of the battery installed in the battery group 2.
1.3.6.1.4.1.12148.10.15.3ScalarbatteryGroup2ReferenceVoltageread-writecurrentThe reference voltage of battery group 2.
1.3.6.1.4.1.12148.10.15.4ScalarbatteryGroup2FusesStatusread-onlycurrentThe state of the battery fuses/breakers can mainly be normal(1) or majorAlarm(3) and some other rarely used values .
1.3.6.1.4.1.12148.10.15.5NodebatteryGroup2Voltage
1.3.6.1.4.1.12148.10.15.5.1ScalarbatteryGroup2VoltageStatusread-onlycurrentThe status of the measured battery voltage.
1.3.6.1.4.1.12148.10.15.5.2ScalarbatteryGroup2VoltageDescriptionread-writecurrentA textual description of the battery voltage monitor. This is stored in the system controller and can be changed by the user.
1.3.6.1.4.1.12148.10.15.5.3ScalarbatteryGroup2VoltageTrapRepeatCounteraccessible-for-notifycurrentThe number of consecutive times this alamcondition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this tra…
1.3.6.1.4.1.12148.10.15.5.4ScalarbatteryGroup2VoltageAlarmEnableread-writecurrentThe measured battery voltage alarm enable/disable control
1.3.6.1.4.1.12148.10.15.5.5ScalarbatteryGroup2VoltageValueread-onlycurrentThe value of the measured battery voltage.Scale is 0.01v.
1.3.6.1.4.1.12148.10.15.5.6ScalarbatteryGroup2VoltageMajorHighLevelread-writecurrentThe Major High Battery Voltage alarm limit set voltage.Scale is 0.01v.
1.3.6.1.4.1.12148.10.15.5.7ScalarbatteryGroup2VoltageMinorHighLevelread-writecurrentThe Minor High Battery Voltage alarm limit set voltage.Scale is 0.01v.
1.3.6.1.4.1.12148.10.15.5.8ScalarbatteryGroup2VoltageMinorLowLevelread-writecurrentThe Minor Low Battery Voltage alarm limit set voltage.Scale is 0.01v.
1.3.6.1.4.1.12148.10.15.5.9ScalarbatteryGroup2VoltageMajorLowLevelread-writecurrentThe Major Low Battery Voltage alarm limit set voltage.Scale is 0.01v.
1.3.6.1.4.1.12148.10.15.6NodebatteryGroup2Currents
1.3.6.1.4.1.12148.10.15.6.1ScalarbatteryGroup2CurrentsStatusread-onlycurrentThe status of the measured battery current
1.3.6.1.4.1.12148.10.15.6.2ScalarbatteryGroup2CurrentsDescriptionread-writecurrentA textual description of the battery current monitor. This is stored in the system controller and can be changed by the user.
1.3.6.1.4.1.12148.10.15.6.3ScalarbatteryGroup2CurrentsTrapRepeatCounteraccessible-for-notifycurrentThe number of consecutive times this alam condition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this tr…
1.3.6.1.4.1.12148.10.15.6.4ScalarbatteryGroup2CurrentsAlarmEnableread-writecurrentThis value once enabled, the alarm condition of the monitor will be reported.
1.3.6.1.4.1.12148.10.15.6.5ScalarbatteryGroup2CurrentsValueread-onlycurrentThe measured total battery current. This is the sum of all the enabled shunt measurements in the system. Negative battery current indicates discharging of the …
1.3.6.1.4.1.12148.10.15.6.6ScalarbatteryGroup2CurrentsMajorHighLevelread-writecurrentThe major high alarm limit
1.3.6.1.4.1.12148.10.15.6.7ScalarbatteryGroup2CurrentsMinorHighLevelread-writecurrentThe minor high alarm limit
1.3.6.1.4.1.12148.10.15.6.8ScalarbatteryGroup2CurrentsMinorLowLevelread-writecurrentThe minor low alarm limit
1.3.6.1.4.1.12148.10.15.6.9ScalarbatteryGroup2CurrentsMajorLowLevelread-writecurrentThe major low alarm limit
1.3.6.1.4.1.12148.10.15.7NodebatteryGroup2Temperatures
1.3.6.1.4.1.12148.10.15.7.1ScalarbatteryGroup2TemperaturesStatusread-onlycurrentThe state of the battery fuses/breakers can be either one of the defined enumerated values
1.3.6.1.4.1.12148.10.15.7.2ScalarbatteryGroup2TemperaturesDescriptionread-writecurrentA textual description of the battery temperature monitor. This is stored in the system controller and can be changed by the user.
1.3.6.1.4.1.12148.10.15.7.3ScalarbatteryGroup2TemperaturesTrapRepeatCounteraccessible-for-notifycurrentThe number of consecutive times this alamcondition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this tra…
1.3.6.1.4.1.12148.10.15.7.4ScalarbatteryGroup2TemperaturesAlarmEnableread-writecurrentThis value once enabled, the alarm condition of the monitor will be reported.
1.3.6.1.4.1.12148.10.15.7.5ScalarbatteryGroup2TemperaturesValueread-onlycurrentThe highest value of the enabled battery temperature measurements. Depending on the global setting in the Control unit, this value will be presented in Celsius…
1.3.6.1.4.1.12148.10.15.7.6ScalarbatteryGroup2TemperaturesMajorHighLevelread-writecurrentThe major high alarm limit
1.3.6.1.4.1.12148.10.15.7.7ScalarbatteryGroup2TemperaturesMinorHighLevelread-writecurrentThe minor high alarm limit
1.3.6.1.4.1.12148.10.15.7.8ScalarbatteryGroup2TemperaturesMinorLowLevelread-writecurrentThe minor low alarm limit
1.3.6.1.4.1.12148.10.15.7.9ScalarbatteryGroup2TemperaturesMajorLowLevelread-writecurrentThe major low alarm limit
1.3.6.1.4.1.12148.10.15.8NodebatteryGroup2TimeLeft
1.3.6.1.4.1.12148.10.15.8.1ScalarbatteryGroup2TimeLeftStatusread-onlycurrentThe status of the estimated battery remaining backup time.
1.3.6.1.4.1.12148.10.15.8.2ScalarbatteryGroup2TimeLeftDescriptionread-writecurrentA textual description of the battery discharge time monitor. This is stored in the system controller and can be changed by the user.
1.3.6.1.4.1.12148.10.15.8.3ScalarbatteryGroup2TimeLeftTrapRepeatCounteraccessible-for-notifycurrentThe number of consecutive times this alam condition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this tr…
1.3.6.1.4.1.12148.10.15.8.4ScalarbatteryGroup2TimeLeftAlarmEnableread-writecurrentThis value once enabled, the alarm condition of the monitor will be reported.
1.3.6.1.4.1.12148.10.15.8.5ScalarbatteryGroup2TimeLeftValueread-onlycurrentThe estimated value of battery remaining backup time.
1.3.6.1.4.1.12148.10.15.8.6ScalarbatteryGroup2TimeLeftMinorAlarmLevelread-writecurrentThe minor alarm limit
1.3.6.1.4.1.12148.10.15.8.7ScalarbatteryGroup2TimeLeftMajorAlarmLevelread-writecurrentThe major alarm limit
1.3.6.1.4.1.12148.10.15.9NodebatteryGroup2RemainingCapacity
1.3.6.1.4.1.12148.10.15.9.1ScalarbatteryGroup2RemainingCapacityStatusread-onlycurrentThe status of the battery remaining capacity monitor.
1.3.6.1.4.1.12148.10.15.9.2ScalarbatteryGroup2RemainingCapacityDescriptionread-writecurrentA textual description of the battery remaining capacity monitor. This is stored in the system controller and can be changed by the user.
1.3.6.1.4.1.12148.10.15.9.3ScalarbatteryGroup2RemainingCapacityTrapRepeatCounteraccessible-for-notifycurrentThe number of consecutive times this alam condition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this tr…
1.3.6.1.4.1.12148.10.15.9.4ScalarbatteryGroup2RemainingCapacityAlarmEnableread-writecurrentThis value once enabled, the alarm condition of the monitor will be reported.
1.3.6.1.4.1.12148.10.15.9.5ScalarbatteryGroup2RemainingCapacityValueread-onlycurrentBattery remaining capacity (SOC) value estimated from the latest battery test result.
1.3.6.1.4.1.12148.10.15.9.6ScalarbatteryGroup2RemainingCapacityMinorLowLevelread-writecurrentThe minor low alarm limit
1.3.6.1.4.1.12148.10.15.9.7ScalarbatteryGroup2RemainingCapacityMajorLowLevelread-writecurrentThe major low alarm limit
1.3.6.1.4.1.12148.10.15.10NodebatteryGroup2UsedCapacity
1.3.6.1.4.1.12148.10.15.10.1ScalarbatteryGroup2UsedCapacityStatusread-onlycurrentThe status of the battery used capacity (DoD) monitor
1.3.6.1.4.1.12148.10.15.10.2ScalarbatteryGroup2UsedCapacityDescriptionread-writecurrentA textual description of the battery used capacity (DoD) monitor. This is stored in the system controller and can be changed by the user.
1.3.6.1.4.1.12148.10.15.10.3ScalarbatteryGroup2UsedCapacityTrapRepeatCounteraccessible-for-notifycurrentThe number of consecutive times this alam condition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this tr…
1.3.6.1.4.1.12148.10.15.10.4ScalarbatteryGroup2UsedCapacityAlarmEnableread-writecurrentThis value once enabled, the alarm condition of the monitor will be reported.
1.3.6.1.4.1.12148.10.15.10.5ScalarbatteryGroup2UsedCapacityValueread-onlycurrentThis is the estimated battery used capacity (DoD).
1.3.6.1.4.1.12148.10.15.10.6ScalarbatteryGroup2UsedCapacityMajorAlarmLevelread-writecurrentThe major alarm limit
1.3.6.1.4.1.12148.10.15.10.7ScalarbatteryGroup2UsedCapacityMinorAlarmLevelread-writecurrentThe minor alarm limit
1.3.6.1.4.1.12148.10.15.11NodebatteryGroup2TotalCapacity
1.3.6.1.4.1.12148.10.15.11.1ScalarbatteryGroup2TotalCapacityStatusread-onlycurrentThe status of the total capacity monitor.
1.3.6.1.4.1.12148.10.15.11.2ScalarbatteryGroup2TotalCapacityDescriptionread-writecurrentA textual description of the battery total capacity monitor. This is stored in the system controller and can be changed by the user
1.3.6.1.4.1.12148.10.15.11.3ScalarbatteryGroup2TotalCapacityTrapRepeatCounteraccessible-for-notifycurrentThe number of consecutive times this alam condition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this tr…
1.3.6.1.4.1.12148.10.15.11.4ScalarbatteryGroup2TotalCapacityAlarmEnableread-writecurrentThis value once enabled, the alarm condition of the monitor will be reported.
1.3.6.1.4.1.12148.10.15.11.5ScalarbatteryGroup2TotalCapacityValueread-onlycurrentThis is the estimated total battery capacity (installed Ah - SoH) value.
1.3.6.1.4.1.12148.10.15.11.6ScalarbatteryGroup2TotalCapacityMinorLowLevelread-writecurrentThe minor low alarm limit
1.3.6.1.4.1.12148.10.15.11.7ScalarbatteryGroup2TotalCapacityMajorLowLevelread-writecurrentThe major low alarm limit
1.3.6.1.4.1.12148.10.15.12NodebatteryGroup2Quality
1.3.6.1.4.1.12148.10.15.12.1ScalarbatteryGroup2QualityStatusread-onlycurrentThe status of the battery quality (SoH) monitor.
1.3.6.1.4.1.12148.10.15.12.2ScalarbatteryGroup2QualityDescriptionread-writecurrentA textual description of the battery quality (SoH) monitor. This is stored in the system controller and can be changed by the user
1.3.6.1.4.1.12148.10.15.12.3ScalarbatteryGroup2QualityTrapRepeatCounteraccessible-for-notifycurrentThe number of consecutive times this alamcondition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this tra…
1.3.6.1.4.1.12148.10.15.12.4ScalarbatteryGroup2QualityAlarmEnableread-writecurrentThis value once enabled, the alarm condition of the monitor will be reported.
1.3.6.1.4.1.12148.10.15.12.5ScalarbatteryGroup2QualityValueread-onlycurrentThe calculated battery quality (SoH) based on the latest battery test
1.3.6.1.4.1.12148.10.15.12.6ScalarbatteryGroup2QualityMinorAlarmLevelread-writecurrentThe minor alarm limit
1.3.6.1.4.1.12148.10.15.12.7ScalarbatteryGroup2QualityMajorAlarmLevelread-writecurrentThe major alarm limit
1.3.6.1.4.1.12148.10.15.13NodebatteryGroup2LVBD
1.3.6.1.4.1.12148.10.15.13.1ScalarbatteryGroup2LVBDStatusread-onlycurrentThe Battery Contactor is connected, disconnected, disabled or in any other alarm condition
1.3.6.1.4.1.12148.10.15.13.2ScalarbatteryGroup2LVBDDescriptionread-writecurrentA textual description of the battery LVBD monitor. This is stored in the system controller and can be changed by the user.
1.3.6.1.4.1.12148.10.15.13.3ScalarbatteryGroup2LVBDTrapRepeatCounteraccessible-for-notifycurrentThe number of consecutive times this alam condition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this tr…
1.3.6.1.4.1.12148.10.15.13.4ScalarbatteryGroup2LVBDEnableread-writecurrentThis value once enabled, the alarm condition of the LVBD will be reported.
1.3.6.1.4.1.12148.10.15.13.5ScalarbatteryGroup2LVBDValueread-onlycurrentThe measured value of the LVBD.
1.3.6.1.4.1.12148.10.15.13.6ScalarbatteryGroup2LVBDConnectVoltageread-writecurrentThe Battery Contactor's Reconnect Voltage
1.3.6.1.4.1.12148.10.15.13.7ScalarbatteryGroup2LVBDDisconnectVoltageread-writecurrentThe Battery Contactor's Disconnect Voltage
1.3.6.1.4.1.12148.10.15.14NodebatteryGroup2ChargeCurrentLimit
1.3.6.1.4.1.12148.10.15.14.1ScalarbatteryGroup2ChargeCurrentLimitEnableread-writecurrentEnable/disable of the battery charge current limitation feature; 0=disable, 1=enable.
1.3.6.1.4.1.12148.10.15.14.2ScalarbatteryGroup2ChargeCurrentLimitValueread-writecurrentBattery charging current limit value. Used only when AC source is mains feed. Note that the units measured may be i Amperes or in Deciamperes depending on glob…
1.3.6.1.4.1.12148.10.15.15NodebatteryGroup2Boost
1.3.6.1.4.1.12148.10.15.15.1ScalarbatteryGroup2BoostVoltageread-writecurrentThe Voltage at which the DC System boost charges the batteries.
1.3.6.1.4.1.12148.10.15.15.2ScalarbatteryGroup2BoostCommandread-writecurrentThis pushbutton will start or stop a manual battery boost if the system allows it.
1.3.6.1.4.1.12148.10.15.15.3ScalarbatteryGroup2BoostCurrentThresholdread-writecurrentThe boosting will terminate when the charge current drops below the BoostCurrentThreshold limit.
1.3.6.1.4.1.12148.10.15.15.4ScalarbatteryGroup2BoostManualMaxDurationread-writecurrentA protection against overcharging. When running manual boost, the boosting will always terminate at this point.
1.3.6.1.4.1.12148.10.15.16NodebatteryGroup2Test
1.3.6.1.4.1.12148.10.15.16.1ScalarbatteryGroup2TestVoltageread-writecurrentThis is the battery test end voltage. The battery test will be terminated when the voltage drops below the end voltage.
1.3.6.1.4.1.12148.10.15.16.2ScalarbatteryGroup2TestCommandread-writecurrentThis pushbutton will start or stop a manual battery test if the system allows it.
1.3.6.1.4.1.12148.10.15.16.3ScalarbatteryGroup2TestNumberOfResultsread-onlycurrentThis is the number of valid battery test results stored in controller.
1.3.6.1.4.1.12148.10.15.16.4TablebatteryGroup2TestResultTablenot-accessiblecurrentThis table contains the battery test results stored in controller.
1.3.6.1.4.1.12148.10.15.16.4.1RowbatteryGroup2TestResultEntrynot-accessiblecurrent
1.3.6.1.4.1.12148.10.15.16.4.1.1ColumnbatteryGroup2TestResultIndexnot-accessiblecurrentA index pointing to one of ten possible battery test results
1.3.6.1.4.1.12148.10.15.16.4.1.2ColumnbatteryGroup2TestResultStartDateTimeread-onlycurrentThis is the time and date when the test started.
1.3.6.1.4.1.12148.10.15.16.4.1.3ColumnbatteryGroup2TestResultDurationread-onlycurrentThis is the test duration in minutes.
1.3.6.1.4.1.12148.10.15.16.4.1.4ColumnbatteryGroup2TestResultDischargedread-onlycurrentThis is the discharged Ah during test.
1.3.6.1.4.1.12148.10.15.16.4.1.5ColumnbatteryGroup2TestResultQualityread-onlycurrentThis is the calculated battery quality (SoH)in percentage.
1.3.6.1.4.1.12148.10.15.16.4.1.6ColumnbatteryGroup2TestResultEndVoltageread-onlycurrentThis is the test end voltage in volt.
1.3.6.1.4.1.12148.10.15.16.4.1.7ColumnbatteryGroup2TestResultTestResultread-onlycurrentThis is the test result.
1.3.6.1.4.1.12148.10.15.16.4.1.8ColumnbatteryGroup2TestResultTerminationCriteriaread-onlycurrentThis is the test Termination Criteria.
1.3.6.1.4.1.12148.10.15.16.4.1.9ColumnbatteryGroup2TestResultBatteryTemperatureread-onlycurrentThis is the battery temperature
1.3.6.1.4.1.12148.10.15.16.5ScalarbatteryGroup2TestDurationread-writecurrentThis is the battery test max duration.
1.3.6.1.4.1.12148.10.15.16.6ScalarbatteryGroup2TestCfgTestTyperead-writecurrentThis is to configurate normal or simplified battery test.
1.3.6.1.4.1.12148.10.15.16.7ScalarbatteryGroup2TestEnableMaxDurationread-writecurrentThis is to enable/disable battery test max duration.
1.3.6.1.4.1.12148.10.15.17NodebatteryGroup2TempComp
1.3.6.1.4.1.12148.10.15.17.1ScalarbatteryGroup2TempCompEnableread-writecurrentEnable (1) or Disable (0) of Battery Temperature Compensated output regulation mode
1.3.6.1.4.1.12148.10.15.18NodebatteryGroup2Bank
1.3.6.1.4.1.12148.10.15.18.1ScalarbatteryGroup2BankStatusread-onlycurrentThe overall status of battery bank
1.3.6.1.4.1.12148.10.15.18.2ScalarbatteryGroup2BankNumberOfTemperaturesread-onlycurrentNumber of temperature measurements in battery bank.
1.3.6.1.4.1.12148.10.15.18.3ScalarbatteryGroup2BankNumberOfCurrentsread-onlycurrentNumber of current measurements in battery bank.
1.3.6.1.4.1.12148.10.15.18.4ScalarbatteryGroup2BankNumberOfFusesread-onlycurrentNumber of fuses installed in battery bank.
1.3.6.1.4.1.12148.10.15.18.5ScalarbatteryGroup2BankNumberOfSymmetriesread-onlycurrentNumber of fuses installed in battery bank.
1.3.6.1.4.1.12148.10.15.18.6TablebatteryGroup2BankTemperatureTablenot-accessiblecurrent
1.3.6.1.4.1.12148.10.15.18.6.1RowbatteryGroup2BankTemperatureEntrynot-accessiblecurrent
1.3.6.1.4.1.12148.10.15.18.6.1.1ColumnbatteryGroup2TemperatureIndexnot-accessiblecurrentThis index denotes which row in the temperature input table. The size of the table is defined by the batteryGroup2BankNumberOfTemperatures
1.3.6.1.4.1.12148.10.15.18.6.1.2ColumnbatteryGroup2TemperatureStatusread-onlycurrentThe status of battery temperature monitor
1.3.6.1.4.1.12148.10.15.18.6.1.3ColumnbatteryGroup2TemperatureDescriptionread-writecurrentA textual description of the battery temperature monitor. This is stored in the system controller and can be changed by the user.
1.3.6.1.4.1.12148.10.15.18.6.1.4ColumnbatteryGroup2TemperatureTrapRepeatCounteraccessible-for-notifycurrentThe number of consecutive times this alam condition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this tr…
1.3.6.1.4.1.12148.10.15.18.6.1.5ColumnbatteryGroup2TemperatureAlarmEnableread-writecurrentThis value once enabled, the alarm condition of the monitor will be reported.
1.3.6.1.4.1.12148.10.15.18.6.1.6ColumnbatteryGroup2TemperatureValueread-onlycurrentThe measured battery temperature.
1.3.6.1.4.1.12148.10.15.18.6.1.7ColumnbatteryGroup2TemperatureMajorHighLevelread-writecurrentThe major high alarm limit
1.3.6.1.4.1.12148.10.15.18.6.1.8ColumnbatteryGroup2TemperatureMinorHighLevelread-writecurrentThe minor high alarm limit
1.3.6.1.4.1.12148.10.15.18.6.1.9ColumnbatteryGroup2TemperatureMinorLowLevelread-writecurrentThe minor low alarm limit
1.3.6.1.4.1.12148.10.15.18.6.1.10ColumnbatteryGroup2TemperatureMajorLowLevelread-writecurrentThe major low alarm limit
1.3.6.1.4.1.12148.10.15.18.7TablebatteryGroup2BankCurrentTablenot-accessiblecurrent
1.3.6.1.4.1.12148.10.15.18.7.1RowbatteryGroup2BankCurrentEntrynot-accessiblecurrent
1.3.6.1.4.1.12148.10.15.18.7.1.1ColumnbatteryGroup2CurrentIndexnot-accessiblecurrentThis index denotes which row in the current input table. The size of the table is defined by the system
1.3.6.1.4.1.12148.10.15.18.7.1.2ColumnbatteryGroup2CurrentStatusread-onlycurrentThe status of battery current monitor
1.3.6.1.4.1.12148.10.15.18.7.1.3ColumnbatteryGroup2CurrentDescriptionread-writecurrentA textual description of the battery current monitor. This is stored in the system controller and can be changed by the user.
1.3.6.1.4.1.12148.10.15.18.7.1.4ColumnbatteryGroup2CurrentTrapRepeatCounteraccessible-for-notifycurrentThe number of consecutive times this alam condition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this tr…
1.3.6.1.4.1.12148.10.15.18.7.1.5ColumnbatteryGroup2CurrentAlarmEnableread-writecurrentThis value once enabled, the alarm condition of the monitor will be reported.
1.3.6.1.4.1.12148.10.15.18.7.1.6ColumnbatteryGroup2CurrentValueread-onlycurrentThe measured battery current
1.3.6.1.4.1.12148.10.15.18.7.1.7ColumnbatteryGroup2CurrentMajorHighLevelread-writecurrentThe major high alarm limit
1.3.6.1.4.1.12148.10.15.18.7.1.8ColumnbatteryGroup2CurrentMinorHighLevelread-writecurrentThe minor high alarm limit
1.3.6.1.4.1.12148.10.15.18.7.1.9ColumnbatteryGroup2CurrentMinorLowLevelread-writecurrentThe minor low alarm limit
1.3.6.1.4.1.12148.10.15.18.7.1.10ColumnbatteryGroup2CurrentMajorLowLevelread-writecurrentThe major low alarm limit
1.3.6.1.4.1.12148.10.15.18.8TablebatteryGroup2BankFuseTablenot-accessiblecurrent
1.3.6.1.4.1.12148.10.15.18.8.1RowbatteryGroup2BankFuseEntrynot-accessiblecurrent
1.3.6.1.4.1.12148.10.15.18.8.1.1ColumnbatteryGroup2FuseIndexnot-accessiblecurrentThis index denotes which row in the fuse table. The size of the table is defined by the system
1.3.6.1.4.1.12148.10.15.18.8.1.2ColumnbatteryGroup2FuseStatusread-onlycurrentThe status of battery fuse monitor
1.3.6.1.4.1.12148.10.15.18.8.1.3ColumnbatteryGroup2FuseDescriptionread-writecurrentA textual description of the battery fuse monitor. This is stored in the system controller and can be changed by the user.
1.3.6.1.4.1.12148.10.15.18.8.1.4ColumnbatteryGroup2FuseTrapRepeatCounteraccessible-for-notifycurrentThe number of consecutive times this alam condition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this tr…
1.3.6.1.4.1.12148.10.15.18.8.1.5ColumnbatteryGroup2FuseAlarmEnableread-writecurrentThis value once enabled, the alarm condition of the monitor will be reported.
1.3.6.1.4.1.12148.10.15.18.8.1.6ColumnbatteryGroup2FuseValueread-onlycurrentThe measured value of battery fuse input.
1.3.6.1.4.1.12148.10.15.18.9TablebatteryGroup2BankSymmetryTablenot-accessiblecurrent
1.3.6.1.4.1.12148.10.15.18.9.1RowbatteryGroup2BankSymmetryEntrynot-accessiblecurrent
1.3.6.1.4.1.12148.10.15.18.9.1.1ColumnbatteryGroup2BankSymmetryIndexnot-accessiblecurrentThis index denotes which row in the symmetry input table. The size of the table is defined by the batteryMonitorNumberOfSymmetries
1.3.6.1.4.1.12148.10.15.18.9.1.2ColumnbatteryGroup2BankSymmetryStatusread-onlycurrentThe status of battery symmetry monitor
1.3.6.1.4.1.12148.10.15.18.9.1.3ColumnbatteryGroup2BankSymmetryDescriptionread-writecurrentA textual description of the battery monitor symmetry. This is stored in the system controller and can be changed by the user.
1.3.6.1.4.1.12148.10.15.18.9.1.4ColumnbatteryGroup2BankSymmetryTrapRepeatCounteraccessible-for-notifycurrentThe number of consecutive times this alam condition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this tr…
1.3.6.1.4.1.12148.10.15.18.9.1.5ColumnbatteryGroup2BankSymmetryAlarmEnableread-writecurrentThis value once enabled, the alarm condition of the monitor will be reported.
1.3.6.1.4.1.12148.10.15.18.9.1.6ColumnbatteryGroup2BankSymmetryMeasureValueread-onlycurrentThe measured battery symmetry voltage in battery monitor.
1.3.6.1.4.1.12148.10.15.18.9.1.7ColumnbatteryGroup2BankSymmetryDeltaValueread-onlycurrentThe measured battery symmetry delta voltage in battery monitor.
1.3.6.1.4.1.12148.10.15.18.9.1.8ColumnbatteryGroup2BankSymmetryMajorAlarmLevelread-writecurrentThe major alarm limit
1.3.6.1.4.1.12148.10.15.18.9.1.9ColumnbatteryGroup2BankSymmetryMinorAlarmLevelread-writecurrentThe minor alarm limit
1.3.6.1.4.1.12148.10.15.19NodebatteryGroup2EnergyLog
1.3.6.1.4.1.12148.10.15.19.1ScalarbatteryGroup2EnergyLogAccumulatedread-onlycurrentThis is the accumulated energy delivered to/from battery.
1.3.6.1.4.1.12148.10.15.19.2ScalarbatteryGroup2EnergyLogLastHoursNumberOfEntriesread-onlycurrentThis is the maximal number of entries stored in battery hourly energy log.
1.3.6.1.4.1.12148.10.15.19.3TablebatteryGroup2EnergyLogLastHoursTablenot-accessiblecurrentThis table contains hourly energy log of battery.
1.3.6.1.4.1.12148.10.15.19.3.1RowbatteryGroup2EnergyLogLastHoursEntrynot-accessiblecurrent
1.3.6.1.4.1.12148.10.15.19.3.1.1ColumnbatteryGroup2EnergyLogLastHoursIndexnot-accessiblecurrentIndex used for navigating the rows 1..52 of batteryEnergyLogLastHoursTable
1.3.6.1.4.1.12148.10.15.19.3.1.2ColumnbatteryGroup2EnergyLogLastHoursValueread-onlycurrentEnergy value logged every hour.
1.3.6.1.4.1.12148.10.15.19.4ScalarbatteryGroup2EnergyLogLastDaysNumberOfEntriesread-onlycurrentThis is the maximal number of entries stored in battery daily energy log.
1.3.6.1.4.1.12148.10.15.19.5TablebatteryGroup2EnergyLogLastDaysTablenot-accessiblecurrentThis table contains daily energy log of battery.
1.3.6.1.4.1.12148.10.15.19.5.1RowbatteryGroup2EnergyLogLastDaysEntrynot-accessiblecurrent
1.3.6.1.4.1.12148.10.15.19.5.1.1ColumnbatteryGroup2EnergyLogLastDaysIndexnot-accessiblecurrentIndex used for navigating the rows 1..52 of batteryEnergyLogLastDaysTable
1.3.6.1.4.1.12148.10.15.19.5.1.2ColumnbatteryGroup2EnergyLogLastDaysValueread-onlycurrentEnergy value logged every day.
1.3.6.1.4.1.12148.10.15.19.6ScalarbatteryGroup2EnergyLogLastWeeksNumberOfEntriesread-onlycurrentThis is the maximal number of entries stored in battery weekly energy log.
1.3.6.1.4.1.12148.10.15.19.7TablebatteryGroup2EnergyLogLastWeeksTablenot-accessiblecurrentThis table contains weekly energy log of battery.
1.3.6.1.4.1.12148.10.15.19.7.1RowbatteryGroup2EnergyLogLastWeeksEntrynot-accessiblecurrent
1.3.6.1.4.1.12148.10.15.19.7.1.1ColumnbatteryGroup2EnergyLogLastWeeksIndexnot-accessiblecurrentIndex used for navigating the rows 1..52 of batteryEnergyLogLastWeekTable
1.3.6.1.4.1.12148.10.15.19.7.1.2ColumnbatteryGroup2EnergyLogLastWeeksValueread-onlycurrentEnergy value logged every week.
1.3.6.1.4.1.12148.10.15.20NodebatteryGroup2CycleLog
1.3.6.1.4.1.12148.10.15.20.1ScalarbatteryGroup2CycleLogTotalCyclesread-onlycurrentThis is the total number of battery discharge cycles.
1.3.6.1.4.1.12148.10.15.20.2ScalarbatteryGroup2CycleLogDaysNumberOfEntriesread-onlycurrentThis is the maximal number of entries stored in daily battery discharge cycle log.
1.3.6.1.4.1.12148.10.15.20.3TablebatteryGroup2CycleLogDaysTablenot-accessiblecurrentThis table contains daily battery discharge cycle log.
1.3.6.1.4.1.12148.10.15.20.3.1RowbatteryGroup2CycleLogDaysEntrynot-accessiblecurrent
1.3.6.1.4.1.12148.10.15.20.3.1.1ColumnbatteryGroup2CycleLogDaysIndexnot-accessiblecurrentIndex used for navigating the rows 1..52 of batteryCycleLogLastDaysTable
1.3.6.1.4.1.12148.10.15.20.3.1.2ColumnbatteryGroup2CycleLogDaysValueread-onlycurrentNumber of discharge cycles logged every day.
1.3.6.1.4.1.12148.10.15.20.4ScalarbatteryGroup2CycleLogWeeksNumberOfEntriesread-onlycurrentThis is the maximal number of entries stored in weeky battery discharge cycle log.
1.3.6.1.4.1.12148.10.15.20.5TablebatteryGroup2CycleLogWeeksTablenot-accessiblecurrentThis table contains weekly battery discharge cycle log.
1.3.6.1.4.1.12148.10.15.20.5.1RowbatteryGroup2CycleLogWeeksEntrynot-accessiblecurrent
1.3.6.1.4.1.12148.10.15.20.5.1.1ColumnbatteryGroup2CycleLogWeeksIndexnot-accessiblecurrentIndex used for navigating the rows 1..52 of batteryCycleLogLastWeeksTable
1.3.6.1.4.1.12148.10.15.20.5.1.2ColumnbatteryGroup2CycleLogWeeksValueread-onlycurrentNumber of discharge cycles logged every week.
1.3.6.1.4.1.12148.10.15.20.6ScalarbatteryGroup2CycleLogMonthsNumberOfEntriesread-onlycurrentThis is the maximal number of entries stored in monthly battery discharge cycle log.
1.3.6.1.4.1.12148.10.15.20.7TablebatteryGroup2CycleLogMonthsTablenot-accessiblecurrentThis table contains monthly battery discharge cycle log.
1.3.6.1.4.1.12148.10.15.20.7.1RowbatteryGroup2CycleLogMonthsEntrynot-accessiblecurrent
1.3.6.1.4.1.12148.10.15.20.7.1.1ColumnbatteryGroup2CycleLogMonthsIndexnot-accessiblecurrentIndex used for navigating the rows 1..52 of batteryCycleLogLastMonthTable
1.3.6.1.4.1.12148.10.15.20.7.1.2ColumnbatteryGroup2CycleLogMonthsValueread-onlycurrentNumber of discharge cycles logged every month.
1.3.6.1.4.1.12148.10.15.21NodebatteryGroup2Equalize
1.3.6.1.4.1.12148.10.15.21.1ScalarbatteryGroup2EqualizeVoltageread-writecurrentThe Voltage at which the DC System equalize charges the batteries.
1.3.6.1.4.1.12148.10.15.21.2ScalarbatteryGroup2EqualizeCommandread-writecurrentThis pushbutton will start or stop a manual battery equalize if the system allows it.
1.3.6.1.4.1.12148.10.15.21.3ScalarbatteryGroup2EqualizeCurrentThresholdread-writecurrentThe equalizing will terminate when the charge current drops below the EqualizeCurrentThreshold limit.
1.3.6.1.4.1.12148.10.15.21.4ScalarbatteryGroup2EqualizeManualMaxDurationread-writecurrentA protection against overcharging. When running manual equalize, the boosting will always terminate at this point.
1.3.6.1.4.1.12148.10.15.22NodebatteryGroup2AhCharged
1.3.6.1.4.1.12148.10.15.22.1ScalarbatteryGroup2AhChargedStatusread-onlycurrentThe status of the battery ah charged monitor.
1.3.6.1.4.1.12148.10.15.22.2ScalarbatteryGroup2AhChargedDescriptionread-writecurrentA textual description of the battery ah charged monitor. This is stored in the system controller and can be changed by the user
1.3.6.1.4.1.12148.10.15.22.3ScalarbatteryGroup2AhChargedTrapRepeatCounteraccessible-for-notifycurrentThe number of consecutive times this alamcondition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this tra…
1.3.6.1.4.1.12148.10.15.22.4ScalarbatteryGroup2AhChargedAlarmEnableread-writecurrentThis value once enabled, the alarm condition of the monitor will be reported.
1.3.6.1.4.1.12148.10.15.22.5ScalarbatteryGroup2AhChargedValueread-onlycurrentThe calculated battery ah (x100) charged value.
1.3.6.1.4.1.12148.10.15.22.6ScalarbatteryGroup2AhChargedMinorHighLevelread-writecurrentThe minor high alarm limit
1.3.6.1.4.1.12148.10.15.22.7ScalarbatteryGroup2AhChargedMajorHighLevelread-writecurrentThe major high alarm limit
1.3.6.1.4.1.12148.10.15.23NodebatteryGroup2AhDischarged
1.3.6.1.4.1.12148.10.15.23.1ScalarbatteryGroup2AhDischargedStatusread-onlycurrentThe status of the battery ah discharged monitor.
1.3.6.1.4.1.12148.10.15.23.2ScalarbatteryGroup2AhDischargedDescriptionread-writecurrentA textual description of the battery ah discharged monitor. This is stored in the system controller and can be changed by the user
1.3.6.1.4.1.12148.10.15.23.3ScalarbatteryGroup2AhDischargedTrapRepeatCounteraccessible-for-notifycurrentThe number of consecutive times this alamcondition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this tra…
1.3.6.1.4.1.12148.10.15.23.4ScalarbatteryGroup2AhDischargedAlarmEnableread-writecurrentThis value once enabled, the alarm condition of the monitor will be reported.
1.3.6.1.4.1.12148.10.15.23.5ScalarbatteryGroup2AhDischargedValueread-onlycurrentThe calculated battery ah (x100) discharged value.
1.3.6.1.4.1.12148.10.15.23.6ScalarbatteryGroup2AhDischargedMinorHighLevelread-writecurrentThe minor high alarm limit
1.3.6.1.4.1.12148.10.15.23.7ScalarbatteryGroup2AhDischargedMajorHighLevelread-writecurrentThe major high alarm limit
1.3.6.1.4.1.12148.10.16Nodeinverters
1.3.6.1.4.1.12148.10.16.1ScalarinvertersStatusread-onlycurrentThe overall status of inverter subsystem.
1.3.6.1.4.1.12148.10.16.2NodeinvertersError
1.3.6.1.4.1.12148.10.16.2.1ScalarinvertersErrorStatusread-onlycurrentThis status value shows if the number of failed units is higher than the defined alarm level.
1.3.6.1.4.1.12148.10.16.2.2ScalarinvertersErrorDescriptionread-writecurrentA textual description of the inverter error monitor. This is stored in the system controller and can be changed by the user
1.3.6.1.4.1.12148.10.16.2.3ScalarinvertersErrorTrapRepeatCounteraccessible-for-notifycurrentThe number of consecutive times this alamcondition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this tra…
1.3.6.1.4.1.12148.10.16.2.4ScalarinvertersErrorEnableread-writecurrentThis value once enabled, the alarm condition of the monitor will be reported.
1.3.6.1.4.1.12148.10.16.2.5ScalarinvertersErrorValueread-onlycurrentThe number of failed inverters.
1.3.6.1.4.1.12148.10.16.2.6ScalarinvertersErrorMajorAlarmLevelread-writecurrentThe major alarm limit
1.3.6.1.4.1.12148.10.16.2.7ScalarinvertersErrorMinorAlarmLevelread-writecurrentThe minor alarm limit
1.3.6.1.4.1.12148.10.16.3NodeinvertersTemperature
1.3.6.1.4.1.12148.10.16.3.1ScalarinvertersTemperatureStatusread-onlycurrentThe state of the rectifier temperature can be either one of the defined enumerated values
1.3.6.1.4.1.12148.10.16.3.2ScalarinvertersTemperatureDescriptionread-writecurrentA textual description of the rectifier temperature monitor. This is stored in the system controller and can be changed by the user.
1.3.6.1.4.1.12148.10.16.3.3ScalarinvertersTemperatureTrapRepeatCounteraccessible-for-notifycurrentThe number of consecutive times this alamcondition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this tra…
1.3.6.1.4.1.12148.10.16.3.4ScalarinvertersTemperatureAlarmEnableread-writecurrentThis value once enabled, the alarm condition of the monitor will be reported.
1.3.6.1.4.1.12148.10.16.3.5ScalarinvertersTemperatureValueread-onlycurrentThe highest value of the rectifier temperature measurements. Depending on the global setting in the Control unit, this value will be presented in Celsius or Fa…
1.3.6.1.4.1.12148.10.16.3.6ScalarinvertersTemperatureMajorHighLevelread-writecurrentThe major high alarm limit
1.3.6.1.4.1.12148.10.16.3.7ScalarinvertersTemperatureMinorHighLevelread-writecurrentThe minor high alarm limit
1.3.6.1.4.1.12148.10.16.3.8ScalarinvertersTemperatureMinorLowLevelread-writecurrentThe minor low alarm limit
1.3.6.1.4.1.12148.10.16.3.9ScalarinvertersTemperatureMajorLowLevelread-writecurrentThe major low alarm limit
1.3.6.1.4.1.12148.10.16.4NodeinvertersAcCurrent1
1.3.6.1.4.1.12148.10.16.4.1ScalarinvertersAcCurrent1Statusread-onlycurrentThe status of the measured total rectifier current.
1.3.6.1.4.1.12148.10.16.4.2ScalarinvertersAcCurrent1Descriptionread-writecurrentA textual description of the total rectifier current monitor. This is stored in the system controller and can be changed by the user
1.3.6.1.4.1.12148.10.16.4.3ScalarinvertersAcCurrent1TrapRepeatCounteraccessible-for-notifycurrentThe number of consecutive times this alamcondition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this tra…
1.3.6.1.4.1.12148.10.16.4.4ScalarinvertersAcCurrent1AlarmEnableread-writecurrentThis value once enabled, the alarm condition of the monitor will be reported.
1.3.6.1.4.1.12148.10.16.4.5ScalarinvertersAcCurrent1Valueread-onlycurrentThe value of the measured total rectifier current.
1.3.6.1.4.1.12148.10.16.4.6ScalarinvertersAcCurrent1MajorAlarmLevelread-writecurrentThe major alarm limit
1.3.6.1.4.1.12148.10.16.4.7ScalarinvertersAcCurrent1MinorAlarmLevelread-writecurrentThe minor alarm limit
1.3.6.1.4.1.12148.10.16.5NodeinvertersAcCurrent2
1.3.6.1.4.1.12148.10.16.5.1ScalarinvertersAcCurrent2Statusread-onlycurrentThe status of the measured total rectifier current.
1.3.6.1.4.1.12148.10.16.5.2ScalarinvertersAcCurrent2Descriptionread-writecurrentA textual description of the total rectifier current monitor. This is stored in the system controller and can be changed by the user
1.3.6.1.4.1.12148.10.16.5.3ScalarinvertersAcCurrent2TrapRepeatCounteraccessible-for-notifycurrentThe number of consecutive times this alamcondition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this tra…
1.3.6.1.4.1.12148.10.16.5.4ScalarinvertersAcCurrent2AlarmEnableread-writecurrentThis value once enabled, the alarm condition of the monitor will be reported.
1.3.6.1.4.1.12148.10.16.5.5ScalarinvertersAcCurrent2Valueread-onlycurrentThe value of the measured total rectifier current.
1.3.6.1.4.1.12148.10.16.5.6ScalarinvertersAcCurrent2MajorAlarmLevelread-writecurrentThe major alarm limit
1.3.6.1.4.1.12148.10.16.5.7ScalarinvertersAcCurrent2MinorAlarmLevelread-writecurrentThe minor alarm limit
1.3.6.1.4.1.12148.10.16.6NodeinvertersAcCurrent3
1.3.6.1.4.1.12148.10.16.6.1ScalarinvertersAcCurrent3Statusread-onlycurrentThe status of the measured total rectifier current.
1.3.6.1.4.1.12148.10.16.6.2ScalarinvertersAcCurrent3Descriptionread-writecurrentA textual description of the total rectifier current monitor. This is stored in the system controller and can be changed by the user
1.3.6.1.4.1.12148.10.16.6.3ScalarinvertersAcCurrent3TrapRepeatCounteraccessible-for-notifycurrentThe number of consecutive times this alamcondition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this tra…
1.3.6.1.4.1.12148.10.16.6.4ScalarinvertersAcCurrent3AlarmEnableread-writecurrentThis value once enabled, the alarm condition of the monitor will be reported.
1.3.6.1.4.1.12148.10.16.6.5ScalarinvertersAcCurrent3Valueread-onlycurrentThe value of the measured total rectifier current.
1.3.6.1.4.1.12148.10.16.6.6ScalarinvertersAcCurrent3MajorAlarmLevelread-writecurrentThe major alarm limit
1.3.6.1.4.1.12148.10.16.6.7ScalarinvertersAcCurrent3MinorAlarmLevelread-writecurrentThe minor alarm limit
1.3.6.1.4.1.12148.10.16.7NodeinvertersAcVoltage1
1.3.6.1.4.1.12148.10.16.7.1ScalarinvertersAcVoltage1Statusread-onlycurrentThe status of the measured total rectifier current.
1.3.6.1.4.1.12148.10.16.7.2ScalarinvertersAcVoltage1Descriptionread-writecurrentA textual description of the total rectifier current monitor. This is stored in the system controller and can be changed by the user
1.3.6.1.4.1.12148.10.16.7.3ScalarinvertersAcVoltage1TrapRepeatCounteraccessible-for-notifycurrentThe number of consecutive times this alamcondition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this tra…
1.3.6.1.4.1.12148.10.16.7.4ScalarinvertersAcVoltage1AlarmEnableread-writecurrentThis value once enabled, the alarm condition of the monitor will be reported.
1.3.6.1.4.1.12148.10.16.7.5ScalarinvertersAcVoltage1Valueread-onlycurrentThe value of the measured total rectifier current.
1.3.6.1.4.1.12148.10.16.7.6ScalarinvertersAcVoltage1MajorHighLevelread-writecurrentThe major alarm limit
1.3.6.1.4.1.12148.10.16.7.7ScalarinvertersAcVoltage1MinorHighLevelread-writecurrentThe minor alarm limit
1.3.6.1.4.1.12148.10.16.7.8ScalarinvertersAcVoltage1MinorLowLevelread-writecurrentThe minor alarm limit
1.3.6.1.4.1.12148.10.16.7.9ScalarinvertersAcVoltage1MajorLowLevelread-writecurrentThe minor alarm limit
1.3.6.1.4.1.12148.10.16.8NodeinvertersAcVoltage2
1.3.6.1.4.1.12148.10.16.8.1ScalarinvertersAcVoltage2Statusread-onlycurrentThe status of the measured total rectifier current.
1.3.6.1.4.1.12148.10.16.8.2ScalarinvertersAcVoltage2Descriptionread-writecurrentA textual description of the total rectifier current monitor. This is stored in the system controller and can be changed by the user
1.3.6.1.4.1.12148.10.16.8.3ScalarinvertersAcVoltage2TrapRepeatCounteraccessible-for-notifycurrentThe number of consecutive times this alamcondition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this tra…
1.3.6.1.4.1.12148.10.16.8.4ScalarinvertersAcVoltage2AlarmEnableread-writecurrentThis value once enabled, the alarm condition of the monitor will be reported.
1.3.6.1.4.1.12148.10.16.8.5ScalarinvertersAcVoltage2Valueread-onlycurrentThe value of the measured total rectifier current.
1.3.6.1.4.1.12148.10.16.8.6ScalarinvertersAcVoltage2MajorHighLevelread-writecurrentThe major alarm limit
1.3.6.1.4.1.12148.10.16.8.7ScalarinvertersAcVoltage2MinorHighLevelread-writecurrentThe minor alarm limit
1.3.6.1.4.1.12148.10.16.8.8ScalarinvertersAcVoltage2MinorLowLevelread-writecurrentThe minor alarm limit
1.3.6.1.4.1.12148.10.16.8.9ScalarinvertersAcVoltage2MajorLowLevelread-writecurrentThe minor alarm limit
1.3.6.1.4.1.12148.10.16.9NodeinvertersAcVoltage3
1.3.6.1.4.1.12148.10.16.9.1ScalarinvertersAcVoltage3Statusread-onlycurrentThe status of the measured total rectifier current.
1.3.6.1.4.1.12148.10.16.9.2ScalarinvertersAcVoltage3Descriptionread-writecurrentA textual description of the total rectifier current monitor. This is stored in the system controller and can be changed by the user
1.3.6.1.4.1.12148.10.16.9.3ScalarinvertersAcVoltage3TrapRepeatCounteraccessible-for-notifycurrentThe number of consecutive times this alamcondition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this tra…
1.3.6.1.4.1.12148.10.16.9.4ScalarinvertersAcVoltage3AlarmEnableread-writecurrentThis value once enabled, the alarm condition of the monitor will be reported.
1.3.6.1.4.1.12148.10.16.9.5ScalarinvertersAcVoltage3Valueread-onlycurrentThe value of the measured total rectifier current.
1.3.6.1.4.1.12148.10.16.9.6ScalarinvertersAcVoltage3MajorHighLevelread-writecurrentThe major alarm limit
1.3.6.1.4.1.12148.10.16.9.7ScalarinvertersAcVoltage3MinorHighLevelread-writecurrentThe minor alarm limit
1.3.6.1.4.1.12148.10.16.9.8ScalarinvertersAcVoltage3MinorLowLevelread-writecurrentThe minor alarm limit
1.3.6.1.4.1.12148.10.16.9.9ScalarinvertersAcVoltage3MajorLowLevelread-writecurrentThe minor alarm limit
1.3.6.1.4.1.12148.10.16.10NodeinvertersAcFrequencyDeviation
1.3.6.1.4.1.12148.10.16.10.1ScalarinvertersAcFrequencyDeviationStatusread-onlycurrentThe status of the measured total rectifier current.
1.3.6.1.4.1.12148.10.16.10.2ScalarinvertersAcFrequencyDeviationDescriptionread-writecurrentA textual description of the total rectifier current monitor. This is stored in the system controller and can be changed by the user
1.3.6.1.4.1.12148.10.16.10.3ScalarinvertersAcFrequencyDeviationTrapRepeatCounteraccessible-for-notifycurrentThe number of consecutive times this alamcondition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this tra…
1.3.6.1.4.1.12148.10.16.10.4ScalarinvertersAcFrequencyDeviationAlarmEnableread-writecurrentThis value once enabled, the alarm condition of the monitor will be reported.
1.3.6.1.4.1.12148.10.16.10.5ScalarinvertersAcFrequencyDeviationValueread-onlycurrentThe value of the measured total rectifier current.
1.3.6.1.4.1.12148.10.16.10.6ScalarinvertersAcFrequencyDeviationMajorHighLevelread-writecurrentThe major alarm limit
1.3.6.1.4.1.12148.10.16.10.7ScalarinvertersAcFrequencyDeviationMinorHighLevelread-writecurrentThe minor alarm limit
1.3.6.1.4.1.12148.10.16.10.8ScalarinvertersAcFrequencyDeviationMinorLowLevelread-writecurrentThe minor alarm limit
1.3.6.1.4.1.12148.10.16.10.9ScalarinvertersAcFrequencyDeviationMajorLowLevelread-writecurrentThe major alarm limit
1.3.6.1.4.1.12148.10.16.11ScalarinvertersAcFrequencyread-onlycurrent
1.3.6.1.4.1.12148.10.17NodegridInvertersObsolete
1.3.6.1.4.1.12148.10.18Noderectiverters
1.3.6.1.4.1.12148.10.18.1ScalarrectivertersStatusread-onlycurrentThe overall status of rectifier subsystem.
1.3.6.1.4.1.12148.10.18.2NoderectivertersDcCurrent
1.3.6.1.4.1.12148.10.18.2.1ScalarrectivertersDcCurrentStatusread-onlycurrentThe status of the measured total rectifier current.
1.3.6.1.4.1.12148.10.18.2.2ScalarrectivertersDcCurrentDescriptionread-writecurrentA textual description of the total rectifier current monitor. This is stored in the system controller and can be changed by the user
1.3.6.1.4.1.12148.10.18.2.3ScalarrectivertersDcCurrentTrapRepeatCounteraccessible-for-notifycurrentThe number of consecutive times this alamcondition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this tra…
1.3.6.1.4.1.12148.10.18.2.4ScalarrectivertersDcCurrentAlarmEnableread-writecurrentThis value once enabled, the alarm condition of the monitor will be reported.
1.3.6.1.4.1.12148.10.18.2.5ScalarrectivertersDcCurrentValueread-onlycurrentThe value of the measured total rectifier current.
1.3.6.1.4.1.12148.10.18.2.6ScalarrectivertersDcCurrentMajorAlarmLevelread-writecurrentThe major alarm limit
1.3.6.1.4.1.12148.10.18.2.7ScalarrectivertersDcCurrentMinorAlarmLevelread-writecurrentThe minor alarm limit
1.3.6.1.4.1.12148.10.18.3NoderectivertersError
1.3.6.1.4.1.12148.10.18.3.1ScalarrectivertersErrorStatusread-onlycurrentThis status value shows if the number of failed units is higher than the defined alarm level.
1.3.6.1.4.1.12148.10.18.3.2ScalarrectivertersErrorDescriptionread-writecurrentA textual description of the rectifier error monitor. This is stored in the system controller and can be changed by the user
1.3.6.1.4.1.12148.10.18.3.3ScalarrectivertersErrorTrapRepeatCounteraccessible-for-notifycurrentThe number of consecutive times this alamcondition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this tra…
1.3.6.1.4.1.12148.10.18.3.4ScalarrectivertersErrorEnableread-writecurrentThis value once enabled, the alarm condition of the monitor will be reported.
1.3.6.1.4.1.12148.10.18.3.5ScalarrectivertersErrorValueread-onlycurrentThe number of failed rectifiers.
1.3.6.1.4.1.12148.10.18.3.6ScalarrectivertersErrorMajorAlarmLevelread-writecurrentThe major alarm limit
1.3.6.1.4.1.12148.10.18.3.7ScalarrectivertersErrorMinorAlarmLevelread-writecurrentThe minor alarm limit
1.3.6.1.4.1.12148.10.18.4NoderectivertersTemperature
1.3.6.1.4.1.12148.10.18.4.1ScalarrectivertersTemperatureStatusread-onlycurrentThe state of the rectifier temperature can be either one of the defined enumerated values
1.3.6.1.4.1.12148.10.18.4.2ScalarrectivertersTemperatureDescriptionread-writecurrentA textual description of the rectifier temperature monitor. This is stored in the system controller and can be changed by the user.
1.3.6.1.4.1.12148.10.18.4.3ScalarrectivertersTemperatureTrapRepeatCounteraccessible-for-notifycurrentThe number of consecutive times this alamcondition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this tra…
1.3.6.1.4.1.12148.10.18.4.4ScalarrectivertersTemperatureAlarmEnableread-writecurrentThis value once enabled, the alarm condition of the monitor will be reported.
1.3.6.1.4.1.12148.10.18.4.5ScalarrectivertersTemperatureValueread-onlycurrentThe highest value of the rectifier temperature measurements. Depending on the global setting in the Control unit, this value will be presented in Celsius or Fa…
1.3.6.1.4.1.12148.10.18.4.6ScalarrectivertersTemperatureMajorHighLevelread-writecurrentThe major high alarm limit
1.3.6.1.4.1.12148.10.18.4.7ScalarrectivertersTemperatureMinorHighLevelread-writecurrentThe minor high alarm limit
1.3.6.1.4.1.12148.10.18.4.8ScalarrectivertersTemperatureMinorLowLevelread-writecurrentThe minor low alarm limit
1.3.6.1.4.1.12148.10.18.4.9ScalarrectivertersTemperatureMajorLowLevelread-writecurrentThe major low alarm limit
1.3.6.1.4.1.12148.10.18.5NoderectivertersAcOutCurrent1
1.3.6.1.4.1.12148.10.18.5.1ScalarrectivertersAcOutCurrent1Statusread-onlycurrentThe status of the measured total rectifier current.
1.3.6.1.4.1.12148.10.18.5.2ScalarrectivertersAcOutCurrent1Descriptionread-writecurrentA textual description of the total rectifier current monitor. This is stored in the system controller and can be changed by the user
1.3.6.1.4.1.12148.10.18.5.3ScalarrectivertersAcOutCurrent1TrapRepeatCounteraccessible-for-notifycurrentThe number of consecutive times this alamcondition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this tra…
1.3.6.1.4.1.12148.10.18.5.4ScalarrectivertersAcOutCurrent1AlarmEnableread-writecurrentThis value once enabled, the alarm condition of the monitor will be reported.
1.3.6.1.4.1.12148.10.18.5.5ScalarrectivertersAcOutCurrent1Valueread-onlycurrentThe value of the measured total rectifier current.
1.3.6.1.4.1.12148.10.18.5.6ScalarrectivertersAcOutCurrent1MajorAlarmLevelread-writecurrentThe major alarm limit
1.3.6.1.4.1.12148.10.18.5.7ScalarrectivertersAcOutCurrent1MinorAlarmLevelread-writecurrentThe minor alarm limit
1.3.6.1.4.1.12148.10.18.6NoderectivertersAcOutCurrent2
1.3.6.1.4.1.12148.10.18.6.1ScalarrectivertersAcOutCurrent2Statusread-onlycurrentThe status of the measured total rectifier current.
1.3.6.1.4.1.12148.10.18.6.2ScalarrectivertersAcOutCurrent2Descriptionread-writecurrentA textual description of the total rectifier current monitor. This is stored in the system controller and can be changed by the user
1.3.6.1.4.1.12148.10.18.6.3ScalarrectivertersAcOutCurrent2TrapRepeatCounteraccessible-for-notifycurrentThe number of consecutive times this alamcondition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this tra…
1.3.6.1.4.1.12148.10.18.6.4ScalarrectivertersAcOutCurrent2AlarmEnableread-writecurrentThis value once enabled, the alarm condition of the monitor will be reported.
1.3.6.1.4.1.12148.10.18.6.5ScalarrectivertersAcOutCurrent2Valueread-onlycurrentThe value of the measured total rectifier current.
1.3.6.1.4.1.12148.10.18.6.6ScalarrectivertersAcOutCurrent2MajorAlarmLevelread-writecurrentThe major alarm limit
1.3.6.1.4.1.12148.10.18.6.7ScalarrectivertersAcOutCurrent2MinorAlarmLevelread-writecurrentThe minor alarm limit
1.3.6.1.4.1.12148.10.18.7NoderectivertersAcOutCurrent3
1.3.6.1.4.1.12148.10.18.7.1ScalarrectivertersAcOutCurrent3Statusread-onlycurrentThe status of the measured total rectifier current.
1.3.6.1.4.1.12148.10.18.7.2ScalarrectivertersAcOutCurrent3Descriptionread-writecurrentA textual description of the total rectifier current monitor. This is stored in the system controller and can be changed by the user
1.3.6.1.4.1.12148.10.18.7.3ScalarrectivertersAcOutCurrent3TrapRepeatCounteraccessible-for-notifycurrentThe number of consecutive times this alamcondition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this tra…
1.3.6.1.4.1.12148.10.18.7.4ScalarrectivertersAcOutCurrent3AlarmEnableread-writecurrentThis value once enabled, the alarm condition of the monitor will be reported.
1.3.6.1.4.1.12148.10.18.7.5ScalarrectivertersAcOutCurrent3Valueread-onlycurrentThe value of the measured total rectifier current.
1.3.6.1.4.1.12148.10.18.7.6ScalarrectivertersAcOutCurrent3MajorAlarmLevelread-writecurrentThe major alarm limit
1.3.6.1.4.1.12148.10.18.7.7ScalarrectivertersAcOutCurrent3MinorAlarmLevelread-writecurrentThe minor alarm limit
1.3.6.1.4.1.12148.10.18.8NoderectivertersAcOutVoltage1
1.3.6.1.4.1.12148.10.18.8.1ScalarrectivertersAcOutVoltage1Statusread-onlycurrentThe status of the measured total rectifier current.
1.3.6.1.4.1.12148.10.18.8.2ScalarrectivertersAcOutVoltage1Descriptionread-writecurrentA textual description of the total rectifier current monitor. This is stored in the system controller and can be changed by the user
1.3.6.1.4.1.12148.10.18.8.3ScalarrectivertersAcOutVoltage1TrapRepeatCounteraccessible-for-notifycurrentThe number of consecutive times this alamcondition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this tra…
1.3.6.1.4.1.12148.10.18.8.4ScalarrectivertersAcOutVoltage1AlarmEnableread-writecurrentThis value once enabled, the alarm condition of the monitor will be reported.
1.3.6.1.4.1.12148.10.18.8.5ScalarrectivertersAcOutVoltage1Valueread-onlycurrentThe value of the measured total rectifier current.
1.3.6.1.4.1.12148.10.18.8.6ScalarrectivertersAcOutVoltage1MajorHighLevelread-writecurrentThe major alarm limit
1.3.6.1.4.1.12148.10.18.8.7ScalarrectivertersAcOutVoltage1MinorHighLevelread-writecurrentThe minor alarm limit
1.3.6.1.4.1.12148.10.18.8.8ScalarrectivertersAcOutVoltage1MinorLowLevelread-writecurrentThe minor alarm limit
1.3.6.1.4.1.12148.10.18.8.9ScalarrectivertersAcOutVoltage1MajorLowLevelread-writecurrentThe major alarm limit
1.3.6.1.4.1.12148.10.18.9NoderectivertersAcOutVoltage2
1.3.6.1.4.1.12148.10.18.9.1ScalarrectivertersAcOutVoltage2Statusread-onlycurrentThe status of the measured total rectifier current.
1.3.6.1.4.1.12148.10.18.9.2ScalarrectivertersAcOutVoltage2Descriptionread-writecurrentA textual description of the total rectifier current monitor. This is stored in the system controller and can be changed by the user
1.3.6.1.4.1.12148.10.18.9.3ScalarrectivertersAcOutVoltage2TrapRepeatCounteraccessible-for-notifycurrentThe number of consecutive times this alamcondition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this tra…
1.3.6.1.4.1.12148.10.18.9.4ScalarrectivertersAcOutVoltage2AlarmEnableread-writecurrentThis value once enabled, the alarm condition of the monitor will be reported.
1.3.6.1.4.1.12148.10.18.9.5ScalarrectivertersAcOutVoltage2Valueread-onlycurrentThe value of the measured total rectifier current.
1.3.6.1.4.1.12148.10.18.9.6ScalarrectivertersAcOutVoltage2MajorHighLevelread-writecurrentThe major alarm limit
1.3.6.1.4.1.12148.10.18.9.7ScalarrectivertersAcOutVoltage2MinorHighLevelread-writecurrentThe minor alarm limit
1.3.6.1.4.1.12148.10.18.9.8ScalarrectivertersAcOutVoltage2MinorLowLevelread-writecurrentThe minor alarm limit
1.3.6.1.4.1.12148.10.18.9.9ScalarrectivertersAcOutVoltage2MajorLowLevelread-writecurrentThe major alarm limit
1.3.6.1.4.1.12148.10.18.10NoderectivertersAcOutVoltage3
1.3.6.1.4.1.12148.10.18.10.1ScalarrectivertersAcOutVoltage3Statusread-onlycurrentThe status of the measured total rectifier current.
1.3.6.1.4.1.12148.10.18.10.2ScalarrectivertersAcOutVoltage3Descriptionread-writecurrentA textual description of the total rectifier current monitor. This is stored in the system controller and can be changed by the user
1.3.6.1.4.1.12148.10.18.10.3ScalarrectivertersAcOutVoltage3TrapRepeatCounteraccessible-for-notifycurrentThe number of consecutive times this alamcondition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this tra…
1.3.6.1.4.1.12148.10.18.10.4ScalarrectivertersAcOutVoltage3AlarmEnableread-writecurrentThis value once enabled, the alarm condition of the monitor will be reported.
1.3.6.1.4.1.12148.10.18.10.5ScalarrectivertersAcOutVoltage3Valueread-onlycurrentThe value of the measured total rectifier current.
1.3.6.1.4.1.12148.10.18.10.6ScalarrectivertersAcOutVoltage3MajorHighLevelread-writecurrentThe major alarm limit
1.3.6.1.4.1.12148.10.18.10.7ScalarrectivertersAcOutVoltage3MinorHighLevelread-writecurrentThe minor alarm limit
1.3.6.1.4.1.12148.10.18.10.8ScalarrectivertersAcOutVoltage3MinorLowLevelread-writecurrentThe minor alarm limit
1.3.6.1.4.1.12148.10.18.10.9ScalarrectivertersAcOutVoltage3MajorLowLevelread-writecurrentThe major alarm limit
1.3.6.1.4.1.12148.10.18.11NoderectivertersAcFrequencyDeviation
1.3.6.1.4.1.12148.10.18.11.1ScalarrectivertersAcFrequencyDeviationStatusread-onlycurrentThe status of the measured total rectifier current.
1.3.6.1.4.1.12148.10.18.11.2ScalarrectivertersAcFrequencyDeviationDescriptionread-writecurrentA textual description of the total rectifier current monitor. This is stored in the system controller and can be changed by the user
1.3.6.1.4.1.12148.10.18.11.3ScalarrectivertersAcFrequencyDeviationTrapRepeatCounteraccessible-for-notifycurrentThe number of consecutive times this alamcondition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this tra…
1.3.6.1.4.1.12148.10.18.11.4ScalarrectivertersAcFrequencyDeviationAlarmEnableread-writecurrentThis value once enabled, the alarm condition of the monitor will be reported.
1.3.6.1.4.1.12148.10.18.11.5ScalarrectivertersAcFrequencyDeviationValueread-onlycurrentThe value of the measured total rectifier current.
1.3.6.1.4.1.12148.10.18.11.6ScalarrectivertersAcFrequencyDeviationMajorHighLevelread-writecurrentThe major alarm limit
1.3.6.1.4.1.12148.10.18.11.7ScalarrectivertersAcFrequencyDeviationMinorHighLevelread-writecurrentThe minor alarm limit
1.3.6.1.4.1.12148.10.18.11.8ScalarrectivertersAcFrequencyDeviationMinorLowLevelread-writecurrentThe minor alarm limit
1.3.6.1.4.1.12148.10.18.11.9ScalarrectivertersAcFrequencyDeviationMajorLowLevelread-writecurrentThe minor alarm limit
1.3.6.1.4.1.12148.10.18.12ScalarrectivertersAcFrequencyread-onlycurrent
1.3.6.1.4.1.12148.10.18.13ScalarrectivertersAcOutVoltageConfigread-writecurrentSet ac output voltage
1.3.6.1.4.1.12148.10.18.14ScalarrectivertersAcOutFrequencyConfigread-writecurrentSet ac output frequency. Scale is 0.01 Hz.
1.3.6.1.4.1.12148.10.19NodefuelCells
1.3.6.1.4.1.12148.10.19.1ScalarfuelCellsStatusread-onlycurrentThe overall status of fuel cell charger subsystem.
1.3.6.1.4.1.12148.10.19.2NodefuelCellsCurrent
1.3.6.1.4.1.12148.10.19.2.1ScalarfuelCellsCurrentStatusread-onlycurrentThe status of the measured total fuel cell current.
1.3.6.1.4.1.12148.10.19.2.2ScalarfuelCellsCurrentDescriptionread-writecurrentA textual description of the total fuel cell current monitor. This is stored in the system controller and can be changed by the user
1.3.6.1.4.1.12148.10.19.2.3ScalarfuelCellsCurrentTrapRepeatCounteraccessible-for-notifycurrentThe number of consecutive times this alamcondition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this tra…
1.3.6.1.4.1.12148.10.19.2.4ScalarfuelCellsCurrentAlarmEnableread-writecurrentThis value once enabled, the alarm condition of the monitor will be reported.
1.3.6.1.4.1.12148.10.19.2.5ScalarfuelCellsCurrentValueread-onlycurrentThe value of the measured total fuel cell current.
1.3.6.1.4.1.12148.10.19.2.6ScalarfuelCellsCurrentMajorAlarmLevelread-writecurrentThe major alarm limit
1.3.6.1.4.1.12148.10.19.2.7ScalarfuelCellsCurrentMinorAlarmLevelread-writecurrentThe minor alarm limit
1.3.6.1.4.1.12148.10.19.3NodefuelCellsPower
1.3.6.1.4.1.12148.10.19.3.1ScalarfuelCellsPowerStatusread-onlycurrentThe status of the measured total fuel cell power.
1.3.6.1.4.1.12148.10.19.3.2ScalarfuelCellsPowerDescriptionread-writecurrentA textual description of the total fuel cell current monitor. This is stored in the system controller and can be changed by the user
1.3.6.1.4.1.12148.10.19.3.3ScalarfuelCellsPowerTrapRepeatCounteraccessible-for-notifycurrentThe number of consecutive times this alamcondition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this tra…
1.3.6.1.4.1.12148.10.19.3.4ScalarfuelCellsPowerAlarmEnableread-writecurrentThis value once enabled, the alarm condition of the monitor will be reported.
1.3.6.1.4.1.12148.10.19.3.5ScalarfuelCellsPowerValueread-onlycurrentThe value of the measured total fuel cell power.
1.3.6.1.4.1.12148.10.19.3.6ScalarfuelCellsPowerMajorAlarmLevelread-writecurrentThe major alarm limit
1.3.6.1.4.1.12148.10.19.3.7ScalarfuelCellsPowerMinorAlarmLevelread-writecurrentThe minor alarm limit
1.3.6.1.4.1.12148.10.19.4NodefuelCellsError
1.3.6.1.4.1.12148.10.19.4.1ScalarfuelCellsErrorStatusread-onlycurrentThis status value shows if the number of failed units is higher than the defined alarm level.
1.3.6.1.4.1.12148.10.19.4.2ScalarfuelCellsErrorDescriptionread-writecurrentA textual description of the fuel cell error monitor. This is stored in the system controller and can be changed by the user
1.3.6.1.4.1.12148.10.19.4.3ScalarfuelCellsErrorTrapRepeatCounteraccessible-for-notifycurrentThe number of consecutive times this alamcondition has been transmitted in a trap. When trap repetition is enabled, this counter increments every time this tra…
1.3.6.1.4.1.12148.10.19.4.4ScalarfuelCellsErrorEnableread-writecurrentThis value once enabled, the alarm condition of the monitor will be reported.
1.3.6.1.4.1.12148.10.19.4.5ScalarfuelCellsErrorValueread-onlycurrentThe number of failed fuel cell chargers.
1.3.6.1.4.1.12148.10.19.4.6ScalarfuelCellsErrorMajorAlarmLevelread-writecurrentThe major alarm limit
1.3.6.1.4.1.12148.10.19.4.7ScalarfuelCellsErrorMinorAlarmLevelread-writecurrentThe minor alarm limit
1.3.6.1.4.1.12148.10.19.5ScalarfuelCellsNumberOfFuelCellsread-writecurrentNumber of installed fuel cell chargers.
1.3.6.1.4.1.12148.10.19.6TablefuelCellTablenot-accessiblecurrentThis table shows the information of each fuel cell installed in the system.
1.3.6.1.4.1.12148.10.19.6.1RowfuelCellEntrynot-accessiblecurrent
1.3.6.1.4.1.12148.10.19.6.1.1ColumnfuelCellIndexnot-accessiblecurrentIndex used for navigating the rows 1..100 of fuelCellTable
1.3.6.1.4.1.12148.10.19.6.1.2ColumnfuelCellStatusread-onlycurrentThe overall status of fuel cell.
1.3.6.1.4.1.12148.10.19.6.1.3ColumnfuelCellModeread-onlycurrentThe mode value of fuel cell.
1.3.6.1.4.1.12148.10.19.6.1.4ColumnfuelCellCurrentValueread-onlycurrentThe output current value of fuel cell.
1.3.6.1.4.1.12148.10.19.6.1.5ColumnfuelCellVoltageValueread-onlycurrentThe input voltage value of fuel cell.
1.3.6.1.4.1.12148.10.19.6.1.6ColumnfuelCellPowerValueread-onlycurrentThe input voltage value of fuel cell.
1.3.6.1.4.1.12148.10.19.6.1.7ColumnfuelCellTyperead-onlycurrentType of fuel cell
1.3.6.1.4.1.12148.10.19.6.1.8ColumnfuelCellInletTemperatureread-onlycurrentThe inlet temp value of fuel cell.
1.3.6.1.4.1.12148.10.19.6.1.9ColumnfuelCellOutletTemperatureread-onlycurrentThe outlet temp value of fuel cell.
1.3.6.1.4.1.12148.10.19.6.1.10ColumnfuelCellRoomTemperatureread-onlycurrentThe room temp value of fuel cell.
1.3.6.1.4.1.12148.10.19.6.1.11ColumnfuelCellFanread-onlycurrentThe fan value of fuel cell.
1.3.6.1.4.1.12148.10.19.6.1.12ColumnfuelCellH2Storage1read-onlycurrentThe H2 storage 1 value of fuel cell.
1.3.6.1.4.1.12148.10.19.6.1.13ColumnfuelCellH2Storage2read-onlycurrentThe H2 storage 2 value of fuel cell.
1.3.6.1.4.1.12148.10.19.6.1.14ColumnfuelCellH2Storage3read-onlycurrentThe H2 storage 3 value of fuel cell.
1.3.6.1.4.1.12148.10.19.6.1.15ColumnfuelCellDO22read-onlycurrentThe DO22 value of fuel cell.
1.3.6.1.4.1.12148.10.19.6.1.16ColumnfuelCellDO23read-onlycurrentThe DO23 value of fuel cell.
1.3.6.1.4.1.12148.10.19.6.1.17ColumnfuelCellDO24read-onlycurrentThe DO24 value of fuel cell.
1.3.6.1.4.1.12148.10.19.6.1.18ColumnfuelCellDO25read-onlycurrentThe DO25 value of fuel cell.
1.3.6.1.4.1.12148.10.19.6.1.19ColumnfuelCellDO26read-onlycurrentThe DO26 value of fuel cell.
1.3.6.1.4.1.12148.10.19.6.1.20ColumnfuelCellDO27read-onlycurrentThe DO27 value of fuel cell.
1.3.6.1.4.1.12148.10.19.6.1.21ColumnfuelCellDC1currentread-onlycurrentThe DC1 current value of fuel cell.
1.3.6.1.4.1.12148.10.19.6.1.22ColumnfuelCellDC2currentread-onlycurrentThe DC2 current value of fuel cell.
1.3.6.1.4.1.12148.10.19.6.1.23ColumnfuelCellDC3currentread-onlycurrentThe DC3 current value of fuel cell.
1.3.6.1.4.1.12148.10.19.6.1.24ColumnfuelCellDC4currentread-onlycurrentThe DC4 current value of fuel cell.
1.3.6.1.4.1.12148.10.19.6.1.25ColumnfuelCellDC5currentread-onlycurrentThe DC5 current value of fuel cell.
1.3.6.1.4.1.12148.10.19.6.1.26ColumnfuelCellDC6currentread-onlycurrentThe DC6 current value of fuel cell.
1.3.6.1.4.1.12148.10.19.7NodefuelCellsEnergyLog
1.3.6.1.4.1.12148.10.19.7.1ScalarfuelCellsEnergyLogAccumulatedread-onlycurrentThis is the accumulated energy delivered from fuel cell.
1.3.6.1.4.1.12148.10.19.7.2ScalarfuelCellsEnergyLogLastHoursNumberOfEntriesread-onlycurrentThis is the maximal number of entries stored in fuel cell hourly energy log.
1.3.6.1.4.1.12148.10.19.7.3TablefuelCellsEnergyLogLastHoursTablenot-accessiblecurrentThis table contains hourly energy log of fuel cell.
1.3.6.1.4.1.12148.10.19.7.3.1RowfuelCellsEnergyLogLastHoursEntrynot-accessiblecurrent
1.3.6.1.4.1.12148.10.19.7.3.1.1ColumnfuelCellsEnergyLogLastHoursIndexnot-accessiblecurrentIndex used for navigating the rows 1..52 of fuelCellsEnergyLogLastHoursTable
1.3.6.1.4.1.12148.10.19.7.3.1.2ColumnfuelCellsEnergyLogLastHoursValueread-onlycurrentEnergy value logged every hour.
1.3.6.1.4.1.12148.10.19.7.4ScalarfuelCellsEnergyLogLastDaysNumberOfEntriesread-onlycurrentThis is the maximal number of entries stored in fuel cell daily energy log.
1.3.6.1.4.1.12148.10.19.7.5TablefuelCellsEnergyLogLastDaysTablenot-accessiblecurrentThis table contains daily energy log of fuel cell.
1.3.6.1.4.1.12148.10.19.7.5.1RowfuelCellsEnergyLogLastDaysEntrynot-accessiblecurrent
1.3.6.1.4.1.12148.10.19.7.5.1.1ColumnfuelCellsEnergyLogLastDaysIndexnot-accessiblecurrentIndex used for navigating the rows 1..52 of fuelCellsEnergyLogLastDaysTable
1.3.6.1.4.1.12148.10.19.7.5.1.2ColumnfuelCellsEnergyLogLastDaysValueread-onlycurrentEnergy value logged every day.
1.3.6.1.4.1.12148.10.19.7.6ScalarfuelCellsEnergyLogLastWeeksNumberOfEntriesread-onlycurrentThis is the maximal number of entries stored in fuel cell weekly energy log.
1.3.6.1.4.1.12148.10.19.7.7TablefuelCellsEnergyLogLastWeeksTablenot-accessiblecurrentThis table contains weekly energy log of fuel cell.
1.3.6.1.4.1.12148.10.19.7.7.1RowfuelCellsEnergyLogLastWeeksEntrynot-accessiblecurrent
1.3.6.1.4.1.12148.10.19.7.7.1.1ColumnfuelCellsEnergyLogLastWeeksIndexnot-accessiblecurrentIndex used for navigating the rows 1..52 of fuelCellsEnergyLogLastWeekTable
1.3.6.1.4.1.12148.10.19.7.7.1.2ColumnfuelCellsEnergyLogLastWeeksValueread-onlycurrentEnergy value logged every week.
1.3.6.1.4.1.12148.10.19.8ScalarfuelCellsResetread-writecurrent
1.3.6.1.4.1.12148.10.19.9ScalarfuelCellsUnlockread-writecurrent
1.3.6.1.4.1.12148.10.19.10ScalarfuelCellsSelfTestread-writecurrent