SYNOLOGY-UPS-MIB

160 objects
Characteristics of the ups information
Imported Objects
NET-SNMP-TCFloat
SNMPv2-CONFMODULE-COMPLIANCE OBJECT-GROUP
SNMPv2-SMIenterprises Integer32 MODULE-IDENTITY OBJECT-TYPE
SNMPv2-TCDisplayString TEXTUAL-CONVENTION
OIDNameAccessStatusDescription
1.3.6.1.4.1.6574Nodesynology
1.3.6.1.4.1.6574.4IdentitysynoUPSCharacteristics of the ups information
1.3.6.1.4.1.6574.4.1NodeupsDevice
1.3.6.1.4.1.6574.4.1.1ScalarupsDeviceModelread-onlycurrentDevice model
1.3.6.1.4.1.6574.4.1.2ScalarupsDeviceManufacturerread-onlycurrentDevice manufacturer
1.3.6.1.4.1.6574.4.1.3ScalarupsDeviceSerialread-onlycurrentDevice serial number.
1.3.6.1.4.1.6574.4.1.4ScalarupsDeviceTyperead-onlycurrentDevice type (ups, pdu, scd, psu)
1.3.6.1.4.1.6574.4.1.5ScalarupsDeviceDescriptionread-onlycurrentDevice description.
1.3.6.1.4.1.6574.4.1.6ScalarupsDeviceContactread-onlycurrentDevice administrator name.
1.3.6.1.4.1.6574.4.1.7ScalarupsDeviceLocationread-onlycurrentDevice physical location.
1.3.6.1.4.1.6574.4.1.8ScalarupsDevicePartread-onlycurrentDevice part number.
1.3.6.1.4.1.6574.4.1.9ScalarupsDeviceMACAddrread-onlycurrentPhysical network address of the device.
1.3.6.1.4.1.6574.4.2NodeupsInfo
1.3.6.1.4.1.6574.4.2.1ScalarupsInfoStatusread-onlycurrentUPS status.
1.3.6.1.4.1.6574.4.2.2ScalarupsInfoAlarmread-onlycurrentUPS alarms
1.3.6.1.4.1.6574.4.2.3ScalarupsInfoTimeread-onlycurrentInternal UPS clock time
1.3.6.1.4.1.6574.4.2.4ScalarupsInfoDateread-onlycurrentInternal UPS clock date
1.3.6.1.4.1.6574.4.2.5ScalarupsInfoModelread-onlycurrentUPS model
1.3.6.1.4.1.6574.4.2.6NodeupsInfoMfr
1.3.6.1.4.1.6574.4.2.6.1ScalarupsInfoMfrNameread-onlycurrentUPS manufacturer
1.3.6.1.4.1.6574.4.2.6.2ScalarupsInfoMfrDateread-onlycurrentUPS manufacturing date
1.3.6.1.4.1.6574.4.2.7ScalarupsInfoSerialread-onlycurrentUPS serial number
1.3.6.1.4.1.6574.4.2.8ScalarupsInfoVendorIDread-onlycurrentVendor ID for USB devices
1.3.6.1.4.1.6574.4.2.9ScalarupsInfoProductIDread-onlycurrentProduct ID for USB devices
1.3.6.1.4.1.6574.4.2.10NodeupsInfoFirmware
1.3.6.1.4.1.6574.4.2.10.1ScalarupsInfoFirmwareNameread-onlycurrentUPS firmware
1.3.6.1.4.1.6574.4.2.10.2ScalarupsInfoFirmwareAuxread-onlycurrentAuxiliary device firmware
1.3.6.1.4.1.6574.4.2.11ScalarupsInfoTemperatureread-onlycurrentUPS temperature (degrees C)
1.3.6.1.4.1.6574.4.2.12NodeupsInfoLoad
1.3.6.1.4.1.6574.4.2.12.1ScalarupsInfoLoadValueread-onlycurrentLoad on UPS (percent)
1.3.6.1.4.1.6574.4.2.12.2ScalarupsInfoLoadHighread-onlycurrentLoad when UPS switches to overload condition (OVER) (percent)
1.3.6.1.4.1.6574.4.2.13ScalarupsInfoIDread-onlycurrentUPS system identifier
1.3.6.1.4.1.6574.4.2.14NodeupsInfoDelay
1.3.6.1.4.1.6574.4.2.14.1ScalarupsInfoDelayStartread-onlycurrentInterval to wait before restarting the load (seconds)
1.3.6.1.4.1.6574.4.2.14.2ScalarupsInfoDelayRebootread-onlycurrentInterval to wait before rebooting the UPS (seconds)
1.3.6.1.4.1.6574.4.2.14.3ScalarupsInfoDelayShutdownread-onlycurrentInterval to wait after shutdown with delay command (seconds)
1.3.6.1.4.1.6574.4.2.15NodeupsInfoTimer
1.3.6.1.4.1.6574.4.2.15.1ScalarupsInfoTimerStartread-onlycurrentTime before the load will be started (seconds)
1.3.6.1.4.1.6574.4.2.15.2ScalarupsInfoTimerRebootread-onlycurrentTime before the load will be rebooted (seconds)
1.3.6.1.4.1.6574.4.2.15.3ScalarupsInfoTimerShutdownread-onlycurrentTime before the load will be shutdown (seconds)
1.3.6.1.4.1.6574.4.2.16NodeupsInfoTest
1.3.6.1.4.1.6574.4.2.16.1ScalarupsInfoTestIntervalread-onlycurrentInterval between self tests
1.3.6.1.4.1.6574.4.2.16.2ScalarupsInfoTestResultread-onlycurrentResults of last self test
1.3.6.1.4.1.6574.4.2.17ScalarupsInfoDisplayLanguageread-onlycurrentLanguage to use on front panel
1.3.6.1.4.1.6574.4.2.18ScalarupsInfoContactsread-onlycurrentUPS external contact sensors
1.3.6.1.4.1.6574.4.2.19ScalarupsInfoEffciencyread-onlycurrentEfficiency of the UPS (ratio of the output current on the input current) (percent)
1.3.6.1.4.1.6574.4.2.20NodeupsInfoPower
1.3.6.1.4.1.6574.4.2.20.1ScalarupsInfoPowerValueread-onlycurrentCurrent value of apparent power (Volt-Amps)
1.3.6.1.4.1.6574.4.2.20.2ScalarupsInfoPowerNominalread-onlycurrentNominal value of apparent power (Volt-Amps)
1.3.6.1.4.1.6574.4.2.21NodeupsInfoRealPower
1.3.6.1.4.1.6574.4.2.21.1ScalarupsInfoRealPowerValueread-onlycurrentCurrent value of real power (Watts)
1.3.6.1.4.1.6574.4.2.21.2ScalarupsInfoRealPowerNominalread-onlycurrentNominal value of real power (Watts)
1.3.6.1.4.1.6574.4.2.22ScalarupsInfoBeeperStatusread-onlycurrentUPS beeper status (enabled, disabled or muted)
1.3.6.1.4.1.6574.4.2.23ScalarupsInfoTyperead-onlycurrentUPS type
1.3.6.1.4.1.6574.4.2.24ScalarupsInfoWatchdogStatusread-onlycurrentUPS watchdog status (enabled or disabled)
1.3.6.1.4.1.6574.4.2.25NodeupsInfoStart
1.3.6.1.4.1.6574.4.2.25.1ScalarupsInfoStartAutoread-onlycurrentUPS starts when mains is (re)applied
1.3.6.1.4.1.6574.4.2.25.2ScalarupsInfoStartBatteryread-onlycurrentAllow to start UPS from battery
1.3.6.1.4.1.6574.4.2.25.3ScalarupsInfoStartRebootread-onlycurrentUPS coldstarts from battery (enabled or disabled)
1.3.6.1.4.1.6574.4.3NodeupsBattery
1.3.6.1.4.1.6574.4.3.1NodeupsBatteryCharge
1.3.6.1.4.1.6574.4.3.1.1ScalarupsBatteryChargeValueread-onlycurrentBattery charge
1.3.6.1.4.1.6574.4.3.1.2ScalarupsBatteryChargeLowread-onlycurrentRemaining battery level when UPS switches to LB (percent)
1.3.6.1.4.1.6574.4.3.1.3ScalarupsBatteryChargeRestartread-onlycurrentMinimum battery level for UPS restart after power-off
1.3.6.1.4.1.6574.4.3.1.4ScalarupsBatteryChargeWarningread-onlycurrentBattery level when UPS switches to Warning state (percent)
1.3.6.1.4.1.6574.4.3.2NodeupsBatteryVoltage
1.3.6.1.4.1.6574.4.3.2.1ScalarupsBatteryVoltageValueread-onlycurrentThe magnitude of the present battery voltage.
1.3.6.1.4.1.6574.4.3.2.2ScalarupsBatteryVoltageNominalread-onlycurrentNominal battery voltage.
1.3.6.1.4.1.6574.4.3.2.3ScalarupsBatteryVoltageLowread-onlycurrentMinimum battery voltage, that triggers FSD status .
1.3.6.1.4.1.6574.4.3.2.4ScalarupsBatteryVoltageHighread-onlycurrentMaximum battery voltage (Ie battery.charge = 100).
1.3.6.1.4.1.6574.4.3.3ScalarupsBatteryCapacityread-onlycurrentBattery capacity (Ah)
1.3.6.1.4.1.6574.4.3.4ScalarupsBatteryCurrentread-onlycurrentThe present battery current.
1.3.6.1.4.1.6574.4.3.5ScalarupsBatteryTemperatureread-onlycurrentThe ambient temperature at or near the UPS Battery casing.
1.3.6.1.4.1.6574.4.3.6NodeupsBatteryRuntime
1.3.6.1.4.1.6574.4.3.6.1ScalarupsBatteryRuntimeValueread-onlycurrentBattery runtime (seconds)
1.3.6.1.4.1.6574.4.3.6.2ScalarupsBatteryRuntimeLowread-onlycurrentRemaining battery runtime when UPS switches to LB (seconds)
1.3.6.1.4.1.6574.4.3.6.3ScalarupsBatteryRuntimeRestartread-onlycurrentMinimum battery runtime for UPS restart after power-off (seconds)
1.3.6.1.4.1.6574.4.3.7ScalarupsBatteryAlarmThresholdread-onlycurrentBattery alarm threshold
1.3.6.1.4.1.6574.4.3.8ScalarupsBatteryDateread-onlycurrentBattery change date
1.3.6.1.4.1.6574.4.3.9ScalarupsBatteryMfrDateread-onlycurrentBattery manufacturing date
1.3.6.1.4.1.6574.4.3.10ScalarupsBatteryPacksread-onlycurrentNumber of battery packs
1.3.6.1.4.1.6574.4.3.11ScalarupsBatteryPacksBadread-onlycurrentNumber of bad battery packs
1.3.6.1.4.1.6574.4.3.12ScalarupsBatteryTyperead-onlycurrentBattery chemistry
1.3.6.1.4.1.6574.4.3.13ScalarupsBatteryProtectionread-onlycurrentPrevent deep discharge of battery
1.3.6.1.4.1.6574.4.3.14ScalarupsBatteryEnergySaveread-onlycurrentSwitch off when running on battery and no/low load
1.3.6.1.4.1.6574.4.4NodeupsInput
1.3.6.1.4.1.6574.4.4.1NodeupsInputVoltage
1.3.6.1.4.1.6574.4.4.1.1ScalarupsInputVoltageValueread-onlycurrentInput voltage
1.3.6.1.4.1.6574.4.4.1.2ScalarupsInputVoltageMaxread-onlycurrentMaximum incoming voltage seen
1.3.6.1.4.1.6574.4.4.1.3ScalarupsInputVoltageMinread-onlycurrentMinimum incoming voltage seen
1.3.6.1.4.1.6574.4.4.1.4ScalarupsInputVoltageNominalread-onlycurrentNominal input voltage
1.3.6.1.4.1.6574.4.4.1.5ScalarupsInputVoltageExtendread-onlycurrentExtended input voltage range
1.3.6.1.4.1.6574.4.4.1.6ScalarupsInputVoltageFaultread-onlycurrentInput voltage Fault
1.3.6.1.4.1.6574.4.4.2NodeupsInputTransfer
1.3.6.1.4.1.6574.4.4.2.1ScalarupsInputTransferReasonread-onlycurrentReason for last transfer to battery
1.3.6.1.4.1.6574.4.4.2.2ScalarupsInputTransferLowread-onlycurrentLow voltage transfer point
1.3.6.1.4.1.6574.4.4.2.3ScalarupsInputTransferHighread-onlycurrentHigh voltage transfer point
1.3.6.1.4.1.6574.4.4.2.4ScalarupsInputTransferLowMinread-onlycurrentsmallest settable low voltage transfer point
1.3.6.1.4.1.6574.4.4.2.5ScalarupsInputTransferLowMaxread-onlycurrentgreatest settable low voltage transfer point
1.3.6.1.4.1.6574.4.4.2.6ScalarupsInputTransferHighMinread-onlycurrentsmallest settable high voltage transfer point
1.3.6.1.4.1.6574.4.4.2.7ScalarupsInputTransferHighMaxread-onlycurrentgreatest settable high voltage transfer point
1.3.6.1.4.1.6574.4.4.2.8ScalarupsInputTransferBoostLowread-onlycurrentLow voltage boosting transfer point
1.3.6.1.4.1.6574.4.4.2.9ScalarupsInputTransferBoostHighread-onlycurrentHigh voltage boosting transfer point
1.3.6.1.4.1.6574.4.4.2.10ScalarupsInputTransferTrimLowread-onlycurrentLow voltage trimming transfer point
1.3.6.1.4.1.6574.4.4.2.11ScalarupsInputTransferTrimHighread-onlycurrentHigh voltage trimming transfer point
1.3.6.1.4.1.6574.4.4.3ScalarupsInputSensitivityread-onlycurrentInput power sensitivity
1.3.6.1.4.1.6574.4.4.4ScalarupsInputQualityread-onlycurrentInput power quality
1.3.6.1.4.1.6574.4.4.5NodeupsInputCurrent
1.3.6.1.4.1.6574.4.4.5.1ScalarupsInputCurrentValueread-onlycurrentInput current (A)
1.3.6.1.4.1.6574.4.4.5.2ScalarupsInputCurrentNominalread-onlycurrentNominal input current (A)
1.3.6.1.4.1.6574.4.4.6NodeupsInputFrequency
1.3.6.1.4.1.6574.4.4.6.1ScalarupsInputFrequencyValueread-onlycurrentInput line frequency (Hz)
1.3.6.1.4.1.6574.4.4.6.2ScalarupsInputFrequencyNominalread-onlycurrentNominal input line frequency (Hz)
1.3.6.1.4.1.6574.4.4.6.3ScalarupsInputFrequencyLowread-onlycurrentInput line frequency low (Hz)
1.3.6.1.4.1.6574.4.4.6.4ScalarupsInputFrequencyHighread-onlycurrentInput line frequency high (Hz)
1.3.6.1.4.1.6574.4.4.6.5ScalarupsInputFrequencyExtendread-onlycurrentExtended input frequency range
1.3.6.1.4.1.6574.4.5NodeupsOutput
1.3.6.1.4.1.6574.4.5.1NodeupsOutputVoltage
1.3.6.1.4.1.6574.4.5.1.1ScalarupsOutputVoltageValueread-onlycurrentOutput voltage (V)
1.3.6.1.4.1.6574.4.5.1.2ScalarupsOutputVoltageNominalread-onlycurrentNominal output voltage (V)
1.3.6.1.4.1.6574.4.5.2NodeupsOutputFrequency
1.3.6.1.4.1.6574.4.5.2.1ScalarupsOutputFrequencyValueread-onlycurrentOutput frequency (Hz)
1.3.6.1.4.1.6574.4.5.2.2ScalarupsOutputFrequencyNominalread-onlycurrentNominal output frequency (Hz)
1.3.6.1.4.1.6574.4.5.3NodeupsOutputCurrent
1.3.6.1.4.1.6574.4.5.3.1ScalarupsOutputCurrentValueread-onlycurrentOutput current (A)
1.3.6.1.4.1.6574.4.5.3.2ScalarupsOutputCurrentNominalread-onlycurrentNominal output current (A)
1.3.6.1.4.1.6574.4.6NodeupsAmbient
1.3.6.1.4.1.6574.4.6.1NodeupsAmbientTemperature
1.3.6.1.4.1.6574.4.6.1.1ScalarupsAmbientTemperatureValueread-onlycurrentAmbient temperature (degrees C)
1.3.6.1.4.1.6574.4.6.1.2ScalarupsAmbientTemperatureAlarmread-onlycurrentTemperature alarm (enabled/disabled)
1.3.6.1.4.1.6574.4.6.1.3ScalarupsAmbientTemperatureHighread-onlycurrentTemperature threshold high (degrees C)
1.3.6.1.4.1.6574.4.6.1.4ScalarupsAmbientTemperatureLowread-onlycurrentTemperature threshold low (degrees C)
1.3.6.1.4.1.6574.4.6.1.5ScalarupsAmbientTemperatureMaxread-onlycurrentMaximum temperature seen (degrees C)
1.3.6.1.4.1.6574.4.6.1.6ScalarupsAmbientTemperatureMinread-onlycurrentMinimum temperature seen (degrees C)
1.3.6.1.4.1.6574.4.6.2NodeupsAmbientHumidity
1.3.6.1.4.1.6574.4.6.2.1ScalarupsAmbientHumidityValueread-onlycurrentAmbient relative humidity (percent)
1.3.6.1.4.1.6574.4.6.2.2ScalarupsAmbientHumidityAlarmread-onlycurrentRelative humidity alarm (enabled/disabled)
1.3.6.1.4.1.6574.4.6.2.3ScalarupsAmbientHumidityHighread-onlycurrentRelative humidity threshold high (percent)
1.3.6.1.4.1.6574.4.6.2.4ScalarupsAmbientHumidityLowread-onlycurrentRelative humidity threshold low (percent)
1.3.6.1.4.1.6574.4.6.2.5ScalarupsAmbientHumidityMaxread-onlycurrentMaximum relative humidity seen (percent)
1.3.6.1.4.1.6574.4.6.2.6ScalarupsAmbientHumidityMinread-onlycurrentMinimum relative humidity seen (percent)
1.3.6.1.4.1.6574.4.7NodeupsDriver
1.3.6.1.4.1.6574.4.7.1ScalarupsDriverNameread-onlycurrentDriver name
1.3.6.1.4.1.6574.4.7.2ScalarupsDriverVersionread-onlycurrentDriver version (NUT release)
1.3.6.1.4.1.6574.4.7.3ScalarupsDriverVersionDataread-onlycurrentDriver version data
1.3.6.1.4.1.6574.4.7.4ScalarupsDriverVersionInternalread-onlycurrentInternal driver version (if tracked separately)
1.3.6.1.4.1.6574.4.7.5ScalarupsDriverPollIntervalread-onlycurrentPoll interval setup in configuration file
1.3.6.1.4.1.6574.4.7.6ScalarupsDriverPortread-onlycurrentPort setup in configuration file
1.3.6.1.4.1.6574.4.7.7ScalarupsDriverPollFrequencyread-onlycurrentPoll frequency
1.3.6.1.4.1.6574.4.7.8ScalarupsDriverProductIDread-onlycurrentProduct ID
1.3.6.1.4.1.6574.4.7.9ScalarupsDriverSnmpVersionread-onlycurrentSnmp version
1.3.6.1.4.1.6574.4.8NodeupsServer
1.3.6.1.4.1.6574.4.8.1ScalarupsServerInforead-onlycurrentServer information
1.3.6.1.4.1.6574.4.8.2ScalarupsServerVersionread-onlycurrentServer version
1.3.6.1.4.1.6574.4.9NodeupsConformance
1.3.6.1.4.1.6574.4.9.1NodeupsCompliances
1.3.6.1.4.1.6574.4.9.1.1ComplianceupsCompliancecurrentThe compliance statement for synoSystem entities which implement the SYNOLOGY SYSTEM MIB.
1.3.6.1.4.1.6574.4.9.2NodeupsGroups
1.3.6.1.4.1.6574.4.9.2.1GroupupsGroupcurrentA collection of objects providing basic information of an synology ups entity.
Type Definitions
NameSyntaxStatusDescription
NonNegativeIntegerInteger32 (0..2147483647)currentThis data type is a non-negative value.