SYNSO-UPSMIB

105 objects
No module-level DESCRIPTION found.
Imported Objects
OIDNameAccessStatusDescription
1.3.6.1.4.1.9557Nodesynso
1.3.6.1.4.1.9557.1NodesynsoUpsSoftware
1.3.6.1.4.1.9557.1.1NodesyupsBasicSetting
1.3.6.1.4.1.9557.1.1.1ScalarsyupsPlatFormread-onlymandatoryThe platform which the UPS software is running on.
1.3.6.1.4.1.9557.1.1.2TablesyupsFeatureTablenot-accessiblemandatoryA table containing the supported features.
1.3.6.1.4.1.9557.1.1.2.1RowsyupsFeatureEntrynot-accessiblemandatoryAn entry representing the support information for a feature.
1.3.6.1.4.1.9557.1.1.2.1.1ColumnsyupsFeatureread-onlymandatoryThe string representing a feature.
1.3.6.1.4.1.9557.1.1.2.1.2ColumnsyupsSupportInforead-onlymandatoryThe string containing the support information for a feature.
1.3.6.1.4.1.9557.1.1.3ScalarsyupsSystemStartTimeread-onlymandatoryThe time that the UPS software starts. It is the number of seconds elapsed since 00:00:00, January 1, 1970.
1.3.6.1.4.1.9557.1.1.4ScalarsyupsSignalTyperead-writemandatoryThe signaling method between the UPS and software. When the basicSignal used, the UPS changes the voltage level of some specific pins to notify the software of…
1.3.6.1.4.1.9557.1.1.5ScalarsyupsBasicSignalDefinitionread-onlymandatoryThe signal definitions for the basic signaling UPS. The value can be the following bit combinations: SG_POWER_FAILURE_ENABLE 0x01 SG_BATTERY_LOW_ENABLE 0x02 SG…
1.3.6.1.4.1.9557.1.1.6ScalarsyupsUpsComPortread-writemandatoryThe serial port which the UPS software use to communicate with the UPS. The format varies from platform to platform. For DOS program, the format is 'portNo, po…
1.3.6.1.4.1.9557.1.1.7ScalarsyupsModemComPortread-writemandatoryThe serial port which the UPS software use to dial out when some particular events occur. The format varies from platform to platform. For DOS program, the for…
1.3.6.1.4.1.9557.1.2NodesyupsUpsExtension
1.3.6.1.4.1.9557.1.2.1ScalarsyupsUpsAlarmread-onlymandatoryIt is used internally. Each bit indicates a critical event, such as input bad, on battery, communications lost, ...,etc.
1.3.6.1.4.1.9557.1.2.2ScalarsyupsSerialNoread-onlymandatoryThe serial number of the UPS connected to the UPS software.
1.3.6.1.4.1.9557.1.2.3ScalarsyupsConfigBatteryVoltageread-onlymandatoryThe nominal battery voltage.
1.3.6.1.4.1.9557.1.2.4ScalarsyupsBatteryReplaceDateread-writemandatoryThe last battery replacement date. It represents the number of days elapsed since January 1, 1901.
1.3.6.1.4.1.9557.1.2.5ScalarsyupsNoOutletread-onlymandatoryThe total number of controllable outlets.
1.3.6.1.4.1.9557.1.2.6ScalarsyupsOutletParamterread-writemandatoryThis object is not used any more.
1.3.6.1.4.1.9557.1.2.7ScalarsyupsShutdownDependread-writemandatoryA string containing those who should perform their shutdown procedure before the UPS turns off. The agent will inform each one in the list to begin their shutd…
1.3.6.1.4.1.9557.1.2.8ScalarsyupsEnableAutoSaveread-writemandatorySetting it to 1, the agent will try to save all files opened by applications before shutting down the operation system. Setting it to 0 will disable the auto s…
1.3.6.1.4.1.9557.1.2.9ScalarsyupsShutdownOsDelayread-writemandatoryThe delay time before shutting down the operation system. When it is necessary to shut down the operation system, the agent will run the specified command file…
1.3.6.1.4.1.9557.1.2.10ScalarsyupsShutdownUpsDelayread-writemandatoryThe delay time before shutting down the UPS. Before shutting down the operation system, the agent will send a command to tell the UPS to shut down. This delay …
1.3.6.1.4.1.9557.1.2.11ScalarsyupsSaveConfigread-writemandatoryUsed to inform the agnet to save the configurations. Its value indicates which group to be saved. For example, a 1 indicates group 1 (syupsBasicSetting) to be …
1.3.6.1.4.1.9557.1.2.12ScalarsyupsNoOutletsread-onlymandatoryThe number of controllable outlets.
1.3.6.1.4.1.9557.1.2.13TablesyupsOutletTablenot-accessiblemandatoryA list of outlet table entries. The number of entries is given by the value of syupsNoOutlets.
1.3.6.1.4.1.9557.1.2.13.1RowsyupsOutletEntrynot-accessiblemandatoryAn entry containing information applicable to a particular controllable outlet.
1.3.6.1.4.1.9557.1.2.13.1.1ColumnsyupsOutletIndexnot-accessiblemandatoryThe outlet identifier.
1.3.6.1.4.1.9557.1.2.13.1.2ColumnsyupsOutletDescriptionread-writemandatoryThe outlet description.
1.3.6.1.4.1.9557.1.2.13.1.3ColumnsyupsOutletShutdownDelayread-writemandatoryThe delay time (in seconds) before turning off the outlet. Before turning off the outlet, the agent will send a shutdown command to anyone specified in the syu…
1.3.6.1.4.1.9557.1.2.13.1.4ColumnsyupsOutletShutdownDependread-writemandatoryA string containing those who should perform their shutdown procedure before the outlet turns off. The agent will inform each one in the list to begin their sh…
1.3.6.1.4.1.9557.1.2.14ScalarsyupsOutletOperatorread-writemandatoryThe operator is used to control the outlets. There are two commands: 1. 'SWITCH: OutletNo, OnOff'. The OutletNo specify the outlet. The OnOff can be 0 (off) or…
1.3.6.1.4.1.9557.1.3NodesyupsEventAction
1.3.6.1.4.1.9557.1.3.1ScalarsyupsNoEventActionEntriesread-onlymandatoryThe number of event-action items. This variable indicates the number of rows in the event-action table.
1.3.6.1.4.1.9557.1.3.2TablesyupsEventActionTablenot-accessiblemandatoryA list of event action entries. The number of entries is given by the value of syupsNoEventActionEntries.
1.3.6.1.4.1.9557.1.3.2.1RowsyupsEventActionEntrynot-accessiblemandatoryAn entry containing information applicable to a particular event action.
1.3.6.1.4.1.9557.1.3.2.1.1ColumnsyupsEventIdread-onlymandatoryThe event ID.
1.3.6.1.4.1.9557.1.3.2.1.2ColumnsyupsLogEnableread-writemandatoryWhether to log the event in the log file when it occurs. A 1 indicates enable, a 0 indicates disable.
1.3.6.1.4.1.9557.1.3.2.1.3ColumnsyupsNotifyEnableread-writemandatoryWhether to notify users when the event occurs. A 1 indicates enable, a 0 indicates disable.
1.3.6.1.4.1.9557.1.3.2.1.4ColumnsyupsNotifyDelayread-writemandatoryHow long the event must last before notifying users.
1.3.6.1.4.1.9557.1.3.2.1.5ColumnsyupsNotifyMessageread-writemandatoryThe message which will be sent when the event occurs.
1.3.6.1.4.1.9557.1.3.2.1.6ColumnsyupsNotifyPeriodread-writemandatoryHow often (in seconds) to send the message. The -1 means once.
1.3.6.1.4.1.9557.1.3.2.1.7ColumnsyupsNotifyUsersread-writemandatoryWho will receive the message when the event occurs.
1.3.6.1.4.1.9557.1.3.2.1.8ColumnsyupsEmailEnableread-writemandatoryWhether to email users when the event occurs. A 1 indicates enable, a 0 indicates disable.
1.3.6.1.4.1.9557.1.3.2.1.9ColumnsyupsEmailDelayread-writemandatoryHow long the event must last before emailing users.
1.3.6.1.4.1.9557.1.3.2.1.10ColumnsyupsEmailMessageread-writemandatoryThe additional message which will be sent when the event occurs.
1.3.6.1.4.1.9557.1.3.2.1.11ColumnsyupsEmailUsersread-writemandatoryWho will receive the mail when the event occurs.
1.3.6.1.4.1.9557.1.3.2.1.12ColumnsyupsPageEnableread-writemandatoryWhether to page users when the event occurs. A 1 indicates enable, a 0 indicates disable.
1.3.6.1.4.1.9557.1.3.2.1.13ColumnsyupsPageDelayread-writemandatoryHow long the event must last before paging users.
1.3.6.1.4.1.9557.1.3.2.1.14ColumnsyupsPageMessageread-writemandatoryThe message which will be sent when the event occurs.
1.3.6.1.4.1.9557.1.3.2.1.15ColumnsyupsPageUsersread-writemandatoryWho will receive the code when the event occurs.
1.3.6.1.4.1.9557.1.3.2.1.16ColumnsyupsCommandEnableread-writemandatoryWhether to execute the external command file when the event occurs. A 1 indicates enable, a 0 indicates disable.
1.3.6.1.4.1.9557.1.3.2.1.17ColumnsyupsCommandDelayread-writemandatoryHow long the event must last before executing the external command file.
1.3.6.1.4.1.9557.1.3.2.1.18ColumnsyupsCommandFileread-writemandatoryThe external command file which will be executed when the event occurs.
1.3.6.1.4.1.9557.1.3.2.1.19ColumnsyupsShutdownEnableread-writemandatoryWhether to shut down the system when the event occurs. A 1 indicates enable, a 0 indicates disable.
1.3.6.1.4.1.9557.1.3.2.1.20ColumnsyupsShutdownDelayread-writemandatoryHow long the event must last before shutting down the system.
1.3.6.1.4.1.9557.1.4NodesyupsHistory
1.3.6.1.4.1.9557.1.4.1ScalarsyupsMaxEventFileLengthread-writemandatoryThe maximum length (in bytes) of the event log file. UPS software will cut the first half of the file whenever the file exceeds this maximum length.
1.3.6.1.4.1.9557.1.4.2ScalarsyupsEventNumRecordsread-onlymandatoryThe total number of records in the event log file.
1.3.6.1.4.1.9557.1.4.3TablesyupsEventTablenot-accessiblemandatoryA list of event entries. Each entry represents a record in the event log file.
1.3.6.1.4.1.9557.1.4.3.1RowsyupsEventEntrynot-accessiblemandatoryAn entry representing a record in the event log file.
1.3.6.1.4.1.9557.1.4.3.1.1ColumnsyupsEventIndexread-onlymandatoryThe record number of an event entry.
1.3.6.1.4.1.9557.1.4.3.1.2ColumnsyupsEventRecordread-onlymandatoryThe string containing an event entry.
1.3.6.1.4.1.9557.1.4.4ScalarsyupsDataRecordIntervalread-writemandatoryThe number of minutes to wait between each recording to the data log file.
1.3.6.1.4.1.9557.1.4.5ScalarsyupsMaxDataFileLengthread-writemandatoryThe maximum length (in bytes) of the data log file. UPS software will cut the first half of the file whenever the file exceeds this maximum length.
1.3.6.1.4.1.9557.1.4.6ScalarsyupsDataNumRecordsread-onlymandatoryThe total number of records in the data log file.
1.3.6.1.4.1.9557.1.4.7TablesyupsDataTablenot-accessiblemandatoryA list of data entries. Each entry represents a record in the data log file.
1.3.6.1.4.1.9557.1.4.7.1RowsyupsDataEntrynot-accessiblemandatoryAn entry representing a record in the data log file.
1.3.6.1.4.1.9557.1.4.7.1.1ColumnsyupsDataIndexread-onlymandatoryThe record number of a data entry.
1.3.6.1.4.1.9557.1.4.7.1.2ColumnsyupsDataRecordread-onlymandatoryThe string containing a data entry.
1.3.6.1.4.1.9557.1.4.8ScalarsyupsHistoryOperatorread-writemandatoryThe operator which is used to operate on the history file. The command format is 'Command, File, Range'. So far, Command can be PURGE, File can be EVENT or DAT…
1.3.6.1.4.1.9557.1.4.9ScalarsyupsScopeSettingsread-writemandatoryThe string contains the settings for UPS Scope Chart, including Value Original Point, Value Unit, Time Unit, Time Interval, and Display Items. The format for t…
1.3.6.1.4.1.9557.1.5NodesyupsSchedule
1.3.6.1.4.1.9557.1.5.1ScalarsyupsNoSchEntriesread-onlymandatoryThe total number of schedule entries.
1.3.6.1.4.1.9557.1.5.2ScalarsyupsSchOperatorread-writemandatoryThe operator which is used to operate on the schedule table. There are three commands: 1. 'ADD: action, mm/dd/yyyy, hh:mm:ss, week_day, repeat' indicates to ad…
1.3.6.1.4.1.9557.1.5.3TablesyupsSchTablenot-accessiblemandatoryA list of schedule entries.
1.3.6.1.4.1.9557.1.5.3.1RowsyupsSchEntrynot-accessiblemandatoryA schedule entry.
1.3.6.1.4.1.9557.1.5.3.1.1ColumnsyupsSchIndexread-onlymandatoryThe entry number of a schedule setting.
1.3.6.1.4.1.9557.1.5.3.1.2ColumnsyupsSchStartDateread-onlymandatoryThe starting date (mm/dd/yyyy) of the schedule entry.
1.3.6.1.4.1.9557.1.5.3.1.3ColumnsyupsSchStartTimeread-onlymandatoryThe starting time (hh:mm:ss) of the schedule entry.
1.3.6.1.4.1.9557.1.5.3.1.4ColumnsyupsSchWeekDayread-onlymandatoryThe starting day of week for the schedule entry. It could be Sun(0), Mon(1), ..., and Sat(6). It is used when syupsSchRepeat is set to weekly.
1.3.6.1.4.1.9557.1.5.3.1.5ColumnsyupsSchActionread-onlymandatoryThe action of the schedule entry. It could be: General System Test (1) Quick Battery Test (2) Deep Battery Test (3) Turn On UPS (11) Turn Off UPS (21) Turn On …
1.3.6.1.4.1.9557.1.5.3.1.6ColumnsyupsSchRepeatread-onlymandatoryIt indicates the frequency of the action, it could be Once(1), Daily(2), Weekly(3) and Monthly(4).
1.3.6.1.4.1.9557.1.6NodesyupsCoworker
1.3.6.1.4.1.9557.1.6.1ScalarsyupsNoAccessControlread-onlymandatoryThe total number of access control entries.
1.3.6.1.4.1.9557.1.6.2ScalarsyupsAccessControlOperatorread-writemandatoryThe operator which is used to operate on the access control table. There are three commands: 1. 'ADD: community' indicates to add a new entry to the access con…
1.3.6.1.4.1.9557.1.6.3TablesyupsAccessControlTablenot-accessiblemandatoryA list of access control entries. Only entries in this list can have access to the agent.
1.3.6.1.4.1.9557.1.6.3.1RowsyupsAccessControlEntrynot-accessiblemandatoryAn access control entry.
1.3.6.1.4.1.9557.1.6.3.1.1ColumnsyupsAccessControlIndexread-onlymandatoryThe entry number of a access control setting.
1.3.6.1.4.1.9557.1.6.3.1.2ColumnsyupsAccessControlSettingread-onlymandatoryA string containing the community name.
1.3.6.1.4.1.9557.1.6.4ScalarsyupsNoTrapReceiverread-onlymandatoryThe total number of trap receiver entries.
1.3.6.1.4.1.9557.1.6.5ScalarsyupsTrapReceiverOperatorread-writemandatoryThe operator which is used to operate on the trap receiver table. There are three commands: 1. 'ADD: ipAddress' indicates to add a new entry to the trap receiv…
1.3.6.1.4.1.9557.1.6.6TablesyupsTrapReceiverTablenot-accessiblemandatoryA list of trap receiver entries. When an important event occurs, the agent will send traps to all the entries in the list.
1.3.6.1.4.1.9557.1.6.6.1RowsyupsTrapReceiverEntrynot-accessiblemandatoryAn trap receiver entry.
1.3.6.1.4.1.9557.1.6.6.1.1ColumnsyupsTrapReceiverIndexread-onlymandatoryThe entry number of a trap receiver setting.
1.3.6.1.4.1.9557.1.6.6.1.2ColumnsyupsTrapReceiverSettingread-onlymandatoryA string containing a trap receiver's IP address.
1.3.6.1.4.1.9557.1.7NodesyupsTraps
1.3.6.1.4.1.9557.1.7.1NotificationsyupsTrapOverTemperaturecurrentThe battery temperature is too high. This trap is persistent and is resent at one minute intervals until the UPS either turns off or the status is no longer pr…
1.3.6.1.4.1.9557.1.7.2NotificationsyupsTrapOverCurrentcurrentThe current is too high. This trap is persistent and is resent at one minute intervals until the UPS either turns off or the status is no longer present.
1.3.6.1.4.1.9557.1.7.3NotificationsyupsTrapOverVoltagecurrentThe voltage is too high. This trap is persistent and is resent at one minute intervals until the UPS either turns off or the status is no longer present.
1.3.6.1.4.1.9557.1.7.4NotificationsyupsTrapUnderVoltagecurrentThe voltage is too low. This trap is persistent and is resent at one minute intervals until the UPS either turns off or the status is no longer present.
1.3.6.1.4.1.9557.1.7.5NotificationsyupsOffFrequencycurrentThe frequency is abnormal. This trap is persistent and is resent at one minute intervals until the UPS either turns off or the status is no longer present.
1.3.6.1.4.1.9557.1.7.6NotificationsyupsLowBatterycurrentThe battery is too low. This trap is persistent and is resent at one minute intervals until the UPS either turns off or the status is no longer present.
1.3.6.1.4.1.9557.1.7.7NotificationsyupsBadBatterycurrentThe battery is bad. This trap is persistent and is resent at one minute intervals until the UPS either turns off or the status is no longer present.