SYNSYS-MIB
51 objects
Top-level infrastructure of PDU project enterprise MIB tree
Imported Objects
| SNMPv2-SMI | enterprises Integer32 IpAddress MODULE-IDENTITY NOTIFICATION-TYPE OBJECT-IDENTITY OBJECT-TYPE |
| SNMPv2-TC | DisplayString |
| OID | Name | Access | Status | Description |
|---|---|---|---|---|
| 1.3.6.1.4.1.21728 | Nodesynaccess | |||
| 1.3.6.1.4.1.21728.3 | IdentitysynSys | Top-level infrastructure of PDU project enterprise MIB tree | ||
| 1.3.6.1.4.1.21728.3.1 | NodesystemDescr | |||
| 1.3.6.1.4.1.21728.3.1.1 | ScalarsystemModel | read-only | current | The model number of the system. |
| 1.3.6.1.4.1.21728.3.1.2 | ScalarsystemName | read-only | current | The system site name or location name. |
| 1.3.6.1.4.1.21728.3.1.3 | ScalarpowerOutletNum | read-only | current | Number of AC outlets are equipped on the system. |
| 1.3.6.1.4.1.21728.3.1.4 | ScalarserialPortNum | read-only | current | Number of user serial console ports are equipped on the system. This number does not include the system Master Serial Port. |
| 1.3.6.1.4.1.21728.3.1.5 | ScalarsystemUpTime | read-only | current | systemUpTime in seconds. Read only. |
| 1.3.6.1.4.1.21728.3.1.6 | ScalarswVersion | read-only | current | Firmware version for this device. Read only. |
| 1.3.6.1.4.1.21728.3.1.7 | ScalaracCurrentSensorNumber | read-only | current | Number of AC current sensors are equipped in the unit. Energy monitoring module's current sensors are not applicable for this object. |
| 1.3.6.1.4.1.21728.3.1.8 | ScalartemperatureProbe | read-only | current | Number of temperature probe ports are equipped on the system. Note: Sensor probes may or may not be plugged-in to the ports |
| 1.3.6.1.4.1.21728.3.1.9 | ScalaracMPIModNumber | read-only | current | Number of MPI(Measured Per Inlet) energy monitoring modules are equipped in the unit. An energy monitoring module provides status for voltage, amp, wattage, KW… |
| 1.3.6.1.4.1.21728.3.2 | NodeoutletOpTables | |||
| 1.3.6.1.4.1.21728.3.2.1 | TableoutletTable | not-accessible | current | A table of outlet operation status. |
| 1.3.6.1.4.1.21728.3.2.1.1 | RowoutletEntry | not-accessible | current | Row definition for the system description table. |
| 1.3.6.1.4.1.21728.3.2.1.1.1 | ColumnoutletIndex | not-accessible | current | Index for the outlet table. |
| 1.3.6.1.4.1.21728.3.2.1.1.2 | ColumnoutletName | read-only | current | Outlet label. Read operation. |
| 1.3.6.1.4.1.21728.3.2.1.1.3 | ColumnoutletStatus | read-only | current | Outlet status. 1-On. 2-0ff. |
| 1.3.6.1.4.1.21728.3.2.1.1.4 | ColumnoutletAction | read-write | current | Turn on/off or reboot an outlet. |
| 1.3.6.1.4.1.21728.3.2.1.1.5 | ColumnoutletCurrentDraw | read-only | current | TRMS AC current draw from an outlet in Amps. This obj is applicable to MPO-system with AC current sensor for each outlet.MPO-Measured Per Outlet. |
| 1.3.6.1.4.1.21728.3.3 | NodeenviroTable | |||
| 1.3.6.1.4.1.21728.3.3.1 | ScalarcurrentAlarmThreshold | read-write | current | Maximum AC Current Draw value recorded, in unit of Amps. |
| 1.3.6.1.4.1.21728.3.3.2 | ScalarcurrentDrawStatus1 | read-only | current | Total AC current draw in amps for the first AC power bank sensor. This object is valid only if the current sensor module is installed. This object is applicabl… |
| 1.3.6.1.4.1.21728.3.3.3 | ScalarcurrentDrawStatus2 | read-only | current | Total AC current draw in amps for the second AC power bank sensor. This object is valid only if the current sensor module is installed. This object is applicab… |
| 1.3.6.1.4.1.21728.3.3.4 | ScalarcurrentDrawMax1 | read-only | current | Max. AC current being detected for the entire system or the first power bank if applicable, in unit of Amps. |
| 1.3.6.1.4.1.21728.3.3.5 | ScalarcurrentDrawMax2 | read-only | current | Max. AC current being detected for the 2nd power bank if applicable, in unit of Amps. |
| 1.3.6.1.4.1.21728.3.3.6 | ScalartemperatureUpThreshold | read-only | current | Environment temperature upper threshold in C. |
| 1.3.6.1.4.1.21728.3.3.7 | ScalartemperatureLowThreshold | read-only | current | Environment temperature low threshold in C. |
| 1.3.6.1.4.1.21728.3.3.8 | ScalartemperatureReading | read-only | current | Temperature reading in C. If value is -65, the temperature sensor is not installed. |
| 1.3.6.1.4.1.21728.3.4 | NodetrapSetting | |||
| 1.3.6.1.4.1.21728.3.4.1 | ScalartrapEnable | read-write | current | Indicates if this trap entry is enabled or not. |
| 1.3.6.1.4.1.21728.3.4.2 | ScalartrapRcvIP | read-write | current | Defines TRAP receiver IP address. |
| 1.3.6.1.4.1.21728.3.4.3 | ScalartrapCommunity | read-write | current | Trap community to be used by agent to send trap. |
| 1.3.6.1.4.1.21728.3.5 | NodeenergyStatus | |||
| 1.3.6.1.4.1.21728.3.5.1 | ScalarmpiCurrent | read-only | current | TRMS currente value measured at AC power inlet. This obj is applicable to a MPI-system. MPI-Measured Per Inlet. |
| 1.3.6.1.4.1.21728.3.5.2 | ScalarmpiVolt | read-only | current | TRMS voltage value measured at AC power inlet. This obj is applicable to a MPI-system. MPI-Measured Per Inlet. |
| 1.3.6.1.4.1.21728.3.5.3 | ScalarmpiActivePower | read-only | current | Active Power value. This obj is applicable to a MPI-system. MPI-Measured Per Inlet. |
| 1.3.6.1.4.1.21728.3.5.4 | ScalarmpiApparentPower | read-only | current | Apparent Power value. This obj is applicable to a MPI-system. MPI-Measured Per Inlet. |
| 1.3.6.1.4.1.21728.3.5.5 | ScalarmpiPowerFactor | read-only | current | PF (Power Factor) value. This obj is applicable to a MPI-system. MPI-Measured Per Inlet. |
| 1.3.6.1.4.1.21728.3.5.6 | ScalarmpiAcFrequency | read-only | current | AC Frequency value. This obj is applicable to a MPI-system. MPI-Measured Per Inlet. |
| 1.3.6.1.4.1.21728.3.5.7 | ScalarmpiAcKwh | read-only | current | Energy KWH readout value. This obj is applicable to a MPI-system. MPI-Measured Per Inlet. |
| 1.3.6.1.4.1.21728.3.5.8 | ScalarmpiAcKwhStartEPOCH | read-only | current | EPOCH value when KWH metering was started. This obj is applicable to a MPI-system. MPI-Measured Per Inlet. |
| 1.3.6.1.4.1.21728.3.100 | NodetrapEvent | |||
| 1.3.6.1.4.1.21728.3.100.0 | Nodeevent | |||
| 1.3.6.1.4.1.21728.3.100.0.1 | NotificationoutletStatusEvent | current | Outlet status change event. | |
| 1.3.6.1.4.1.21728.3.100.0.2 | NotificationoutletGroupStatusEvent | current | Outlet Group status change event. | |
| 1.3.6.1.4.1.21728.3.100.0.3 | NotificationautoPingRebootEvent | current | AutoPing and Reboot event. | |
| 1.3.6.1.4.1.21728.3.100.0.4 | NotificationtemperatureAlarmEvent | current | Environment temperature high or low threshold crossing alarm event. | |
| 1.3.6.1.4.1.21728.3.100.0.5 | NotificationtemperatureControlledOutletEvent | current | Environment temperature upper and lOWer SET POINTS triggered outlet(s) change event. | |
| 1.3.6.1.4.1.21728.3.100.0.6 | NotificationsystemPowerUpEvent | current | System powers up event. | |
| 1.3.6.1.4.1.21728.3.100.0.7 | NotificationkwhOverLimitEvent | current | Energy usage over preset limit. Current KWH reading and KWH accumulation starting EPOCH time. |