MIB Viewer

Sentry3-MIB

154 objects
This is the MIB module for the third generation of the Sentry product family. This includes the Sentry Remote Power Manager (RPM), Sentry Power Distribution Unit (PDU), Sentry Environmental Monitor (EM), Sentry Smart and Switched Cabinet Distribution Unit (CDU), and Sentry Switched -48 VDC.
Imported Objects
SNMPv2-SMIenterprises MODULE-IDENTITY NOTIFICATION-TYPE OBJECT-TYPE
SNMPv2-TCDisplayString
OIDNameAccessStatusDescription
1.3.6.1.4.1.1718NodeserverTech
1.3.6.1.4.1.1718.3Identitysentry3This is the MIB module for the third generation of the Sentry product family. This includes the Sentry Remote Power Manager (RPM), Sentry Power Distribution Un…
1.3.6.1.4.1.1718.3.1NodesystemGroup
1.3.6.1.4.1.1718.3.1.1ScalarsystemVersionread-onlycurrentThe firmware version of the system.
1.3.6.1.4.1.1718.3.1.2ScalarsystemNICSerialNumberread-onlycurrentThe serial number of the network interface card in the system.
1.3.6.1.4.1.1718.3.1.3ScalarsystemLocationread-writecurrentThe location of the system.
1.3.6.1.4.1.1718.3.1.4ScalarsystemTowerCountread-onlycurrentThe number of towers in the system.
1.3.6.1.4.1.1718.3.1.5ScalarsystemEnvMonCountread-onlycurrentThe number of environmental monitors in the system.
1.3.6.1.4.1.1718.3.1.6ScalarsystemTotalPowerread-onlycurrentThe total power consumption of all of the input feeds in the system. A non-negative value indicates the total power consumption in Watts. A negative value indi…
1.3.6.1.4.1.1718.3.1.7ScalarsystemArearead-writecurrentThe area that the footprint of the system occupies. A non-zero non-negative value indicates the area in tenths of area units as selected by the systemAreaUnit …
1.3.6.1.4.1.1718.3.1.8ScalarsystemWattsPerAreaUnitread-onlycurrentThe system Watts per area unit. A non-negative value indicates the power consumption per area unit as selected by the systemAreaUnit object. A negative value i…
1.3.6.1.4.1.1718.3.1.9ScalarsystemAreaUnitread-writecurrentThe unit of area for the systemArea and systemWattsPerAreaUnit objects. If the agent does not support this object, then the unit of area is a square foot.
1.3.6.1.4.1.1718.3.1.10ScalarsystemPowerFactorread-writecurrentThe power factor used in power calculations performed by the system.
1.3.6.1.4.1.1718.3.1.11ScalarsystemFeaturesread-onlycurrentThe key-activated features enabled in the system.
1.3.6.1.4.1.1718.3.1.12ScalarsystemFeatureKeyread-writecurrentA valid feature key written to this object will enable a feature in the system. A valid feature key is in the form xxxx-xxxx-xxxx-xxxx. A read of this object r…
1.3.6.1.4.1.1718.3.1.13ScalarsystemOutletSeqIntervalread-writecurrentThe power-on sequencing interval for all outlets.
1.3.6.1.4.1.1718.3.1.14ScalarsystemOutletRebootDelayread-writecurrentThe reboot delay for all outlets.
1.3.6.1.4.1.1718.3.1.15ScalarsystemConfigModifiedCountread-onlycurrentThe total number of times the system configuration has changed.
1.3.6.1.4.1.1718.3.2NodesystemTables
1.3.6.1.4.1.1718.3.2.1TabletowerTablenot-accessiblecurrentA table of towers.
1.3.6.1.4.1.1718.3.2.1.1RowtowerEntrynot-accessiblecurrentRow definition for the tower table.
1.3.6.1.4.1.1718.3.2.1.1.1ColumntowerIndexnot-accessiblecurrentIndex for the tower table.
1.3.6.1.4.1.1718.3.2.1.1.2ColumntowerIDread-onlycurrentThe ID of the tower.
1.3.6.1.4.1.1718.3.2.1.1.3ColumntowerNameread-writecurrentThe name of the tower.
1.3.6.1.4.1.1718.3.2.1.1.4ColumntowerStatusread-onlycurrentThe operational status of the tower.
1.3.6.1.4.1.1718.3.2.1.1.5ColumntowerInfeedCountread-onlycurrentThe number of input feeds on the tower.
1.3.6.1.4.1.1718.3.2.1.1.6ColumntowerProductSNread-onlycurrentThe product serial number of the tower.
1.3.6.1.4.1.1718.3.2.1.1.7ColumntowerModelNumberread-onlycurrentThe model number of the tower.
1.3.6.1.4.1.1718.3.2.1.1.8ColumntowerCapabilitiesread-onlycurrentThe capabilities of the tower.
1.3.6.1.4.1.1718.3.2.1.1.9ColumntowerVACapacityread-onlycurrentThe total apparent power capacity of the tower circuit. A non-negative value indicates the maximum total apparent power in Volt-Amps. A negative value indicate…
1.3.6.1.4.1.1718.3.2.1.1.10ColumntowerVACapacityUsedread-onlycurrentThe used percentage of the tower circuit total apparent power capacity (towerApparentPower / towerVACapacity x 100). A non-negative value indicates the percent…
1.3.6.1.4.1.1718.3.2.1.1.11ColumntowerActivePowerread-onlycurrentThe total active power consumption of the tower circuit. A non-negative value indicates the total active power consumption in Watts. A negative value indicates…
1.3.6.1.4.1.1718.3.2.1.1.12ColumntowerApparentPowerread-onlycurrentThe total apparent power consumption of the tower circuit. A non-negative value indicates the total apparent power consumption in Volt-Amps. A negative value i…
1.3.6.1.4.1.1718.3.2.1.1.13ColumntowerPowerFactorread-onlycurrentThe overall power factor of the tower circuit. A non- negative value indicates the overall power factor in hundredths. A negative value indicates that the over…
1.3.6.1.4.1.1718.3.2.1.1.14ColumntowerEnergyread-onlycurrentThe total energy consumption of the tower circuit. A non- negative value indicates the total energy consumption in Kilowatt-Hours. A negative value indicates t…
1.3.6.1.4.1.1718.3.2.1.1.15ColumntowerLineFrequencyread-onlycurrentThe frequency of the input feed line voltage. A non- negative value indicates the frequency in Hertz. A negative value indicates that the frequency was not ava…
1.3.6.1.4.1.1718.3.2.2TableinfeedTablenot-accessiblecurrentA table of input feeds.
1.3.6.1.4.1.1718.3.2.2.1RowinfeedEntrynot-accessiblecurrentRow definition for the input feed table.
1.3.6.1.4.1.1718.3.2.2.1.1ColumninfeedIndexnot-accessiblecurrentIndex for the input feed table.
1.3.6.1.4.1.1718.3.2.2.1.2ColumninfeedIDread-onlycurrentThe ID of the input feed.
1.3.6.1.4.1.1718.3.2.2.1.3ColumninfeedNameread-writecurrentThe name of the input feed.
1.3.6.1.4.1.1718.3.2.2.1.4ColumninfeedCapabilitiesread-onlycurrentThe capabilities of the input feed.
1.3.6.1.4.1.1718.3.2.2.1.5ColumninfeedStatusread-onlycurrentThe status of the input feed line. If the infeedCapabilities 'onSense' bit is TRUE, then all of the states are supported and indicate the sensed state of the i…
1.3.6.1.4.1.1718.3.2.2.1.6ColumninfeedLoadStatusread-onlycurrentThe status of the load measured on the input feed line. If the infeedCapabilities 'loadSense' bit is TRUE, then all of the states are supported. If the infeedC…
1.3.6.1.4.1.1718.3.2.2.1.7ColumninfeedLoadValueread-onlycurrentThe load measured on the input feed line. A non-negative value indicates the measured load in hundredths of Amps. A negative value indicates that a load value …
1.3.6.1.4.1.1718.3.2.2.1.8ColumninfeedLoadHighThreshread-writecurrentThe load high threshold value of the input feed line in Amps.
1.3.6.1.4.1.1718.3.2.2.1.9ColumninfeedOutletCountread-onlycurrentThe number of controlled and/or monitored outlets on the input feed.
1.3.6.1.4.1.1718.3.2.2.1.10ColumninfeedCapacityread-onlycurrentThe load capacity of the input feed line. A non-negative value indicates the maximum load in Amps. A negative value indicates that the capacity was not availab…
1.3.6.1.4.1.1718.3.2.2.1.11ColumninfeedVoltageread-onlycurrentThe line-to-line voltage of the input feed. A non-negative value indicates the voltage in tenths of Volts. A negative value indicates that the voltage was not …
1.3.6.1.4.1.1718.3.2.2.1.12ColumninfeedPowerread-onlycurrentThe active power consumption of the input feed phase. A non- negative value indicates the active power consumption in Watts. A negative value indicates that th…
1.3.6.1.4.1.1718.3.2.2.1.13ColumninfeedApparentPowerread-onlycurrentThe apparent power consumption of the input feed phase. A non-negative value indicates the apparent power consumption in Volt-Amps. A negative value indicates …
1.3.6.1.4.1.1718.3.2.2.1.14ColumninfeedPowerFactorread-onlycurrentThe power factor of the input feed phase. A non-negative value indicates the power factor in hundredths. A negative value indicates that the power factor was n…
1.3.6.1.4.1.1718.3.2.2.1.15ColumninfeedCrestFactorread-onlycurrentThe crest factor for the load of the input feed phase. A non-negative value indicates the crest factor in tenths. A negative value indicates that the crest fac…
1.3.6.1.4.1.1718.3.2.2.1.16ColumninfeedEnergyread-onlycurrentThe energy consumption of the input feed phase. A non- negative value indicates the energy consumption in tenths of Kilowatt-Hours. A negative value indicates …
1.3.6.1.4.1.1718.3.2.2.1.17ColumninfeedReactanceread-onlycurrentThe characterization of the phase relation between the voltage and current of the input feed phase.
1.3.6.1.4.1.1718.3.2.2.1.18ColumninfeedPhaseVoltageread-onlycurrentThe voltage measured for the input feed phase. A non- negative value indicates the voltage in tenths of Volts. A negative value indicates that the voltage was …
1.3.6.1.4.1.1718.3.2.2.1.19ColumninfeedPhaseCurrentread-onlycurrentThe current measured for the input feed phase. A non- negative value indicates the measured load in hundredths of Amps. A negative value indicates that a load …
1.3.6.1.4.1.1718.3.2.2.1.20ColumninfeedCapacityUsedread-onlycurrentThe used percentage of the input feed line load capacity (infeedLoadValue / infeedCapacity x 100). A non-negative value indicates the percentage of capacity us…
1.3.6.1.4.1.1718.3.2.2.1.21ColumninfeedLineIDread-onlycurrentThe ID of the input feed line.
1.3.6.1.4.1.1718.3.2.2.1.22ColumninfeedLineToLineIDread-onlycurrentThe line-to-line ID of the input feed.
1.3.6.1.4.1.1718.3.2.2.1.23ColumninfeedPhaseIDread-onlycurrentThe ID of the input feed phase.
1.3.6.1.4.1.1718.3.2.2.1.24ColumninfeedVACapacityread-onlycurrentThe apparent power capacity of the input feed circuit. A non-negative value indicates the maximum apparent power in Volt-Amps. A negative value indicates that …
1.3.6.1.4.1.1718.3.2.2.1.25ColumninfeedVACapacityUsedread-onlycurrentThe used percentage of the input feed circuit apparent power capacity (infeedApparentPower / infeedVACapacity x 100). A non-negative value indicates the percen…
1.3.6.1.4.1.1718.3.2.3TableoutletTablenot-accessiblecurrentA table of outlets.
1.3.6.1.4.1.1718.3.2.3.1RowoutletEntrynot-accessiblecurrentRow definition for the outlet table.
1.3.6.1.4.1.1718.3.2.3.1.1ColumnoutletIndexnot-accessiblecurrentIndex for the outlet table.
1.3.6.1.4.1.1718.3.2.3.1.2ColumnoutletIDread-onlycurrentThe ID of the outlet.
1.3.6.1.4.1.1718.3.2.3.1.3ColumnoutletNameread-writecurrentThe name of the outlet.
1.3.6.1.4.1.1718.3.2.3.1.4ColumnoutletCapabilitiesread-onlycurrentThe capabilities of the outlet.
1.3.6.1.4.1.1718.3.2.3.1.5ColumnoutletStatusread-onlycurrentThe status of the outlet. If the outletCapabilities 'onSense' bit is TRUE, then the state indicates the sensed state of the outlet, not a derived state, and 'o…
1.3.6.1.4.1.1718.3.2.3.1.6ColumnoutletLoadStatusread-onlycurrentThe status of the load measured on the outlet. If the outletCapabilities 'loadSense' bit is TRUE, then all of the states are supported. If the outletCapabiliti…
1.3.6.1.4.1.1718.3.2.3.1.7ColumnoutletLoadValueread-onlycurrentThe load measured on the outlet. A non-negative value indicates the measured load in hundredths of Amps. A negative value indicates that a load value was not a…
1.3.6.1.4.1.1718.3.2.3.1.8ColumnoutletLoadLowThreshread-writecurrentThe load low threshold value of the outlet in Amps.
1.3.6.1.4.1.1718.3.2.3.1.9ColumnoutletLoadHighThreshread-writecurrentThe load high threshold value of the outlet in Amps.
1.3.6.1.4.1.1718.3.2.3.1.10ColumnoutletControlStateread-onlycurrentThe control state of the outlet. The supported states are dependent upon the outletCapabilities 'powerControl' and 'shutdown' bits, as well as the supported fe…
1.3.6.1.4.1.1718.3.2.3.1.11ColumnoutletControlActionread-writecurrentAn action to change the control state of the outlet. If the outletCapabilities 'powerControl' bit is TRUE, then the 'on', 'off', and 'reboot' actions can be us…
1.3.6.1.4.1.1718.3.2.3.1.12ColumnoutletCapacityread-onlycurrentThe load capacity of the outlet. A non-negative value indicates the maximum load in Amps. A negative value indicates that the capacity was not available.
1.3.6.1.4.1.1718.3.2.3.1.13ColumnoutletVoltageread-onlycurrentThe voltage of the outlet. A non-negative value indicates the voltage in tenths of Volts. A negative value indicates that the voltage was not available.
1.3.6.1.4.1.1718.3.2.3.1.14ColumnoutletPowerread-onlycurrentThe active power consumption of the device plugged into the outlet. A non-negative value indicates the active power consumption in Watts. A negative value indi…
1.3.6.1.4.1.1718.3.2.3.1.15ColumnoutletApparentPowerread-onlycurrentThe apparent power consumption of the device plugged into the outlet. A non-negative value indicates the apparent power consumption in Volt-Amps. A negative va…
1.3.6.1.4.1.1718.3.2.3.1.16ColumnoutletPowerFactorread-onlycurrentThe power factor of the device plugged into the outlet. A non-negative value indicates the power factor in hundredths. A negative value indicates that the powe…
1.3.6.1.4.1.1718.3.2.3.1.17ColumnoutletCrestFactorread-onlycurrentThe crest factor for the load of the device plugged into the outlet. A non-negative value indicates the crest factor in tenths. A negative value indicates that…
1.3.6.1.4.1.1718.3.2.3.1.18ColumnoutletEnergyread-onlycurrentThe energy consumption of the device plugged into the outlet. A non-negative value indicates the energy consumption in Watt-Hours. A negative value indicates t…
1.3.6.1.4.1.1718.3.2.3.1.19ColumnoutletWakeupStateread-writecurrentThe wakeup state of the outlet.
1.3.6.1.4.1.1718.3.2.3.1.20ColumnoutletPostOnDelayread-writecurrentThe post-on delay of the outlet.
1.3.6.1.4.1.1718.3.2.4TableenvMonTablenot-accessiblecurrentA table of environmental monitors.
1.3.6.1.4.1.1718.3.2.4.1RowenvMonEntrynot-accessiblecurrentRow definition for the environmental monitor table.
1.3.6.1.4.1.1718.3.2.4.1.1ColumnenvMonIndexnot-accessiblecurrentIndex for the environmental monitor table.
1.3.6.1.4.1.1718.3.2.4.1.2ColumnenvMonIDread-onlycurrentThe ID of the environmental monitor.
1.3.6.1.4.1.1718.3.2.4.1.3ColumnenvMonNameread-writecurrentThe name of the environmental monitor.
1.3.6.1.4.1.1718.3.2.4.1.4ColumnenvMonStatusread-onlycurrentThe operational status of the environmental monitor.
1.3.6.1.4.1.1718.3.2.4.1.5ColumnenvMonWaterSensorNameread-writecurrentThe name of the water sensor.
1.3.6.1.4.1.1718.3.2.4.1.6ColumnenvMonWaterSensorStatusread-onlycurrentThe status of the water sensor.
1.3.6.1.4.1.1718.3.2.4.1.7ColumnenvMonADCNameread-writecurrentThe name of the analog-to-digital converter.
1.3.6.1.4.1.1718.3.2.4.1.8ColumnenvMonADCStatusread-onlycurrentThe status of the analog-to-digital converter.
1.3.6.1.4.1.1718.3.2.4.1.9ColumnenvMonADCCountread-onlycurrentThe 8-bit count value from the analog-to-digital converter. A non-negative value indicates the digital value retrieved from the ADC. A negative value indicates…
1.3.6.1.4.1.1718.3.2.4.1.10ColumnenvMonADCLowThreshread-writecurrentThe 8-bit count low threshold value of the analog-to-digital converter.
1.3.6.1.4.1.1718.3.2.4.1.11ColumnenvMonADCHighThreshread-writecurrentThe 8-bit count high threshold value of the analog-to-digital converter.
1.3.6.1.4.1.1718.3.2.4.1.12ColumnenvMonTempHumidSensorCountread-onlycurrentThe number of temperature/humidity sensors on the environmental monitor.
1.3.6.1.4.1.1718.3.2.4.1.13ColumnenvMonContactClosureCountread-onlycurrentThe number of contact closures on the environmental monitor.
1.3.6.1.4.1.1718.3.2.5TabletempHumidSensorTablenot-accessiblecurrentA table of temperature/humidity sensors.
1.3.6.1.4.1.1718.3.2.5.1RowtempHumidSensorEntrynot-accessiblecurrentRow definition for the temperature/humidity sensor table.
1.3.6.1.4.1.1718.3.2.5.1.1ColumntempHumidSensorIndexnot-accessiblecurrentIndex for the temperature/humidity sensor table.
1.3.6.1.4.1.1718.3.2.5.1.2ColumntempHumidSensorIDread-onlycurrentThe ID of the temperature/humidity sensor.
1.3.6.1.4.1.1718.3.2.5.1.3ColumntempHumidSensorNameread-writecurrentThe name of the temperature/humidity sensor.
1.3.6.1.4.1.1718.3.2.5.1.4ColumntempHumidSensorStatusread-onlycurrentThe operational status of the temperature/humidity sensor.
1.3.6.1.4.1.1718.3.2.5.1.5ColumntempHumidSensorTempStatusread-onlycurrentThe status of the temperature sensor.
1.3.6.1.4.1.1718.3.2.5.1.6ColumntempHumidSensorTempValueread-onlycurrentThe temperature measured by the sensor. A non-negative value indicates the measured temperature in tenths of degrees, using the scale selected by tempHumidSens…
1.3.6.1.4.1.1718.3.2.5.1.7ColumntempHumidSensorTempLowThreshread-writecurrentThe temperature low threshold value of the sensor in degrees, using the scale selected by tempHumidSensorTempScale. If the agent does not support the tempHumid…
1.3.6.1.4.1.1718.3.2.5.1.8ColumntempHumidSensorTempHighThreshread-writecurrentThe temperature high threshold value of the sensor in degrees, using the scale selected by tempHumidSensorTempScale. If the agent does not support the tempHumi…
1.3.6.1.4.1.1718.3.2.5.1.9ColumntempHumidSensorHumidStatusread-onlycurrentThe status of the humidity sensor.
1.3.6.1.4.1.1718.3.2.5.1.10ColumntempHumidSensorHumidValueread-onlycurrentThe humidity measured by the sensor. A non-negative value indicates the measured humidity in percentage relative humidity. A negative value indicates that a hu…
1.3.6.1.4.1.1718.3.2.5.1.11ColumntempHumidSensorHumidLowThreshread-writecurrentThe humidity low threshold value of the sensor in percentage relative humidity.
1.3.6.1.4.1.1718.3.2.5.1.12ColumntempHumidSensorHumidHighThreshread-writecurrentThe humidity low threshold value of the sensor in percentage relative humidity.
1.3.6.1.4.1.1718.3.2.5.1.13ColumntempHumidSensorTempScaleread-writecurrentThe scale used for temperature values. This is a global setting for all temperature values in the system. If the agent does not support this object, then the t…
1.3.6.1.4.1.1718.3.2.5.1.14ColumntempHumidSensorTempRecDeltaread-writecurrentThe temperature recovery delta (hysteresis) value of the sensor in degrees, using the scale selected by tempHumidSensorTempScale.
1.3.6.1.4.1.1718.3.2.5.1.15ColumntempHumidSensorHumidRecDeltaread-writecurrentThe humidity recovery delta (hysteresis) value of the sensor in percentage relative humidity.
1.3.6.1.4.1.1718.3.2.6TablecontactClosureTablenot-accessiblecurrentA table of contact closures.
1.3.6.1.4.1.1718.3.2.6.1RowcontactClosureEntrynot-accessiblecurrentRow definition for the contact closure table.
1.3.6.1.4.1.1718.3.2.6.1.1ColumncontactClosureIndexnot-accessiblecurrentIndex for the contact closure table.
1.3.6.1.4.1.1718.3.2.6.1.2ColumncontactClosureIDread-onlycurrentThe ID of the contact closure.
1.3.6.1.4.1.1718.3.2.6.1.3ColumncontactClosureNameread-writecurrentThe name of the contact closure.
1.3.6.1.4.1.1718.3.2.6.1.4ColumncontactClosureStatusread-onlycurrentThe status of the contact closure.
1.3.6.1.4.1.1718.3.2.7TablebranchTablenot-accessiblecurrentA table of branches.
1.3.6.1.4.1.1718.3.2.7.1RowbranchEntrynot-accessiblecurrentRow definition for the branch table.
1.3.6.1.4.1.1718.3.2.7.1.1ColumnbranchIndexnot-accessiblecurrentIndex for the branch table.
1.3.6.1.4.1.1718.3.2.7.1.2ColumnbranchIDread-onlycurrentThe ID of the branch.
1.3.6.1.4.1.1718.3.2.7.1.3ColumnbranchNameread-writecurrentThe name of the branch.
1.3.6.1.4.1.1718.3.2.7.1.4ColumnbranchCapabilitiesread-onlycurrentThe capabilities of the branch.
1.3.6.1.4.1.1718.3.2.7.1.5ColumnbranchStatusread-onlycurrentThe status of the branch.
1.3.6.1.4.1.1718.3.2.7.1.6ColumnbranchLoadStatusread-onlycurrentThe status of the load measured on the branch.
1.3.6.1.4.1.1718.3.2.7.1.7ColumnbranchLoadValueread-onlycurrentThe load measured on the branch. A non-negative value indicates the measured load in hundredths of Amps. A negative value indicates that a load value was not a…
1.3.6.1.4.1.1718.3.2.7.1.8ColumnbranchLoadHighThreshread-writecurrentThe load high threshold value of the branch in Amps.
1.3.6.1.4.1.1718.3.2.7.1.9ColumnbranchCapacityread-onlycurrentThe load capacity of the branch. A non-negative value indicates the maximum load in Amps. A negative value indicates that the capacity was not available.
1.3.6.1.4.1.1718.3.99NodeeventInformationGroup
1.3.6.1.4.1.1718.3.99.1ScalareventStatusTextread-onlycurrentThe text representation of the enumerated integer value of the status object included in a trap. The value of this object is set only when sent with a trap. A …
1.3.6.1.4.1.1718.3.99.2ScalareventStatusConditionread-onlycurrentThe condition of the enumerated integer value of the status object included in a trap. The value of this object is set only when sent with a trap. A get of thi…
1.3.6.1.4.1.1718.3.100Nodesentry3Traps
1.3.6.1.4.1.1718.3.100.0Nodeevents
1.3.6.1.4.1.1718.3.100.0.1NotificationtowerStatusEventcurrentTower status event. If enabled, this trap is sent when the towerStatus indicates an error state ('noComm', 'fanFail', 'overTemp', 'nvmFail', or 'outOfBalance')…
1.3.6.1.4.1.1718.3.100.0.2NotificationinfeedStatusEventcurrentInput feed status event. If enabled, this trap is sent when the infeedStatus indicates an error state ('offError', 'onError', 'noComm', 'offFuse', or 'onFuse')…
1.3.6.1.4.1.1718.3.100.0.3NotificationinfeedLoadEventcurrentInput feed load event. If enabled, this trap is sent when the infeedLoadStatus indicates an error state ('loadLow', 'loadHigh', 'overLoad', 'readError', or 'no…
1.3.6.1.4.1.1718.3.100.0.4NotificationoutletStatusEventcurrentOutlet status event. If enabled, this trap is sent when the outletStatus indicates an error state ('offError', 'onError', 'noComm', 'offFuse', or 'onFuse'). Th…
1.3.6.1.4.1.1718.3.100.0.5NotificationoutletLoadEventcurrentOutlet load event. If enabled, this trap is sent when the outletLoadStatus indicates an error state ('loadLow', 'loadHigh', 'overLoad', 'readError', or 'noComm…
1.3.6.1.4.1.1718.3.100.0.6NotificationoutletChangeEventcurrentOutlet on/off change event. If enabled, this trap is sent when the outletStatus changes from any 'on' state ('on', 'onWait', 'onError', or 'onFuse') to any 'of…
1.3.6.1.4.1.1718.3.100.0.7NotificationenvMonStatusEventcurrentEnvironmental monitor status event. If enabled, this trap is sent when the envMonStatus indicates an error state ('noComm'). This trap is repeated periodically…
1.3.6.1.4.1.1718.3.100.0.8NotificationenvMonWaterSensorEventcurrentEnvironmental monitor water sensor event. If enabled, this trap is sent when the envMonWaterSensorStatus indicates an error state ('alarm'). This trap is repea…
1.3.6.1.4.1.1718.3.100.0.9NotificationenvMonADCEventcurrentEnvironmental monitor analog-to-digital converter event. If enabled, this trap is sent when the envMonADCStatus indicates an error state ('countLow' or 'countH…
1.3.6.1.4.1.1718.3.100.0.10NotificationtempHumidSensorStatusEventcurrentTemperature/humidity sensor status event. If enabled, this trap is sent when the tempHumidSensorStatus indicates an error state ('lost'). This trap is repeated…
1.3.6.1.4.1.1718.3.100.0.11NotificationtempHumidSensorTempEventcurrentTemperature/humidity sensor temperature event. If enabled, this trap is sent when the tempHumidSensorTempStatus indicates an error state ('tempLow' or 'tempHig…
1.3.6.1.4.1.1718.3.100.0.12NotificationtempHumidSensorHumidEventcurrentTemperature/humidity sensor humidity event. If enabled, this trap is sent when the tempHumidSensorHumidStatus indicates an error state ('humidLow' or 'humidHig…
1.3.6.1.4.1.1718.3.100.0.13NotificationcontactClosureEventcurrentContact closure event. If enabled, this trap is sent when the contactClosureStatus indicates an error state ('alarm'). This trap is repeated periodically while…
1.3.6.1.4.1.1718.3.100.0.14NotificationbranchStatusEventcurrentBranch status event. If enabled, this trap is sent when the branchStatus indicates an error state ('offError', 'onError', 'noComm', 'offFuse', or 'onFuse'). Th…
1.3.6.1.4.1.1718.3.100.0.15NotificationbranchLoadEventcurrentBranch load event. If enabled, this trap is sent when the branchLoadStatus indicates an error state ('loadLow', 'loadHigh', 'overLoad', 'readError', or 'noComm…