T3610-MIB
74 objects
No module-level DESCRIPTION found.
Imported Objects
| RFC-1212 | OBJECT-TYPE |
| RFC-1215 | TRAP-TYPE |
| RFC1155-SMI | enterprises |
| OID | Name | Access | Status | Description |
|---|---|---|---|---|
| 1.3.6.1.4.1.22626 | Nodecomet | |||
| 1.3.6.1.4.1.22626.0 | NodetrapTest | Testing trap, testing trap by TSensor software | ||
| 1.3.6.1.4.1.22626.1 | Nodeproducts | |||
| 1.3.6.1.4.1.22626.1 | NodetrapNTPError | Error on time synchronisation via NTP | ||
| 1.3.6.1.4.1.22626.1.2 | Nodet3610 | |||
| 1.3.6.1.4.1.22626.1.2.1 | Nodevalues | |||
| 1.3.6.1.4.1.22626.1.2.1.1 | Scalartemp | read-only | mandatory | Temperature |
| 1.3.6.1.4.1.22626.1.2.1.2 | Scalarhum | read-only | mandatory | Relative humidity |
| 1.3.6.1.4.1.22626.1.2.1.3 | ScalarcompVal | read-only | mandatory | Computed value |
| 1.3.6.1.4.1.22626.1.2.1.5 | ScalartempAlarm | read-only | mandatory | Alarm on Temperature; none, high, low |
| 1.3.6.1.4.1.22626.1.2.1.6 | ScalarhumAlarm | read-only | mandatory | Alarm on Relative humidity; none, high, low |
| 1.3.6.1.4.1.22626.1.2.1.7 | ScalarcompValAlarm | read-only | mandatory | Alarm on Computed value; none, high, low |
| 1.3.6.1.4.1.22626.1.2.1.9 | ScalartempUnit | read-only | mandatory | Temperature Unit |
| 1.3.6.1.4.1.22626.1.2.1.10 | ScalarhumUnit | read-only | mandatory | Relative humidity Unit |
| 1.3.6.1.4.1.22626.1.2.1.11 | ScalarcompValUnit | read-only | mandatory | Computed value Unit |
| 1.3.6.1.4.1.22626.1.2.1.13 | ScalartempMin | read-only | mandatory | Minimal temperature |
| 1.3.6.1.4.1.22626.1.2.1.14 | ScalarhumMin | read-only | mandatory | Minimal relative humidity |
| 1.3.6.1.4.1.22626.1.2.1.15 | ScalarcompValMin | read-only | mandatory | Minimal computed value |
| 1.3.6.1.4.1.22626.1.2.1.17 | ScalartempMax | read-only | mandatory | Maximal temperature |
| 1.3.6.1.4.1.22626.1.2.1.18 | ScalarhumMax | read-only | mandatory | Maximal relative humidity |
| 1.3.6.1.4.1.22626.1.2.1.19 | ScalarcompValMax | read-only | mandatory | Maximal computed value |
| 1.3.6.1.4.1.22626.1.2.2 | Nodeglobal | |||
| 1.3.6.1.4.1.22626.1.2.2.1 | ScalarsensorName | read-only | mandatory | Device name |
| 1.3.6.1.4.1.22626.1.2.2.2 | ScalarserialNumber | read-only | mandatory | Serial number |
| 1.3.6.1.4.1.22626.1.2.2.3 | ScalardeviceType | read-only | mandatory | Device type |
| 1.3.6.1.4.1.22626.1.2.3 | NodevaluesInt | |||
| 1.3.6.1.4.1.22626.1.2.3.1 | ScalartempInt | read-only | mandatory | Temperature (value*10) |
| 1.3.6.1.4.1.22626.1.2.3.2 | ScalarhumInt | read-only | mandatory | Relative humidity (value*10) |
| 1.3.6.1.4.1.22626.1.2.3.3 | ScalarcompValInt | read-only | mandatory | Computed value (value*10) |
| 1.3.6.1.4.1.22626.1.2.3.5 | ScalartempAlarmInt | read-only | mandatory | Alarm on Temperature; 0 - No, 1 - High, 2 - Low |
| 1.3.6.1.4.1.22626.1.2.3.6 | ScalarhumAlarmInt | read-only | mandatory | Alarm on Relative humidity; 0 - No, 1 - High, 2 - Low |
| 1.3.6.1.4.1.22626.1.2.3.7 | ScalarcompValAlarmInt | read-only | mandatory | Alarm on Computed value; 0 - No, 1 - High, 2 - Low |
| 1.3.6.1.4.1.22626.1.2.4 | Nodesettings | |||
| 1.3.6.1.4.1.22626.1.2.4.1 | ScalartempLowInt | read-only | mandatory | Temperature Limit Low (value*10) |
| 1.3.6.1.4.1.22626.1.2.4.2 | ScalartempHighInt | read-only | mandatory | Temperature Limit High (value*10) |
| 1.3.6.1.4.1.22626.1.2.4.3 | ScalarhumLowInt | read-only | mandatory | Humidity Limit Low (value*10) |
| 1.3.6.1.4.1.22626.1.2.4.4 | ScalarhumHighInt | read-only | mandatory | Humidity Limit High (value*10) |
| 1.3.6.1.4.1.22626.1.2.4.5 | ScalarcompValLowInt | read-only | mandatory | Computed value Limit Low (value*10) |
| 1.3.6.1.4.1.22626.1.2.4.6 | ScalarcompValHighInt | read-only | mandatory | Computed value Limit High (value*10) |
| 1.3.6.1.4.1.22626.1.2.4.7 | ScalartempDelayInt | read-only | mandatory | Temperature alaram delay [sec] |
| 1.3.6.1.4.1.22626.1.2.4.8 | ScalarhumDelayInt | read-only | mandatory | Humidity alaram delay [sec] |
| 1.3.6.1.4.1.22626.1.2.4.9 | ScalarcompValDelayInt | read-only | mandatory | Computed value alaram delay [sec] |
| 1.3.6.1.4.1.22626.1.2.4.10 | ScalartempHystInt | read-only | mandatory | Temperature hysteresis (value*10) |
| 1.3.6.1.4.1.22626.1.2.4.11 | ScalarhumHystInt | read-only | mandatory | Humidity hysteresis (value*10) |
| 1.3.6.1.4.1.22626.1.2.4.12 | ScalarcompValHystInt | read-only | mandatory | Computed value hysteresis (value*10) |
| 1.3.6.1.4.1.22626.1.2.5 | Nodetraps | |||
| 1.3.6.1.4.1.22626.1.2.5.1 | ScalarmessageString | read-only | mandatory | Message giving more detailed information on alarms |
| 1.3.6.1.4.1.22626.1.2.6 | Nodetables | |||
| 1.3.6.1.4.1.22626.1.2.6.1 | TablehistoryTable | not-accessible | mandatory | Table of the history values |
| 1.3.6.1.4.1.22626.1.2.6.1.1 | RowhistoryEntry | not-accessible | optional | History values entries |
| 1.3.6.1.4.1.22626.1.2.6.1.1.1 | ColumnhistTemp | read-only | mandatory | Temperature reading |
| 1.3.6.1.4.1.22626.1.2.6.1.1.2 | ColumnhistHum | read-only | mandatory | Humidity reading |
| 1.3.6.1.4.1.22626.1.2.6.1.1.3 | ColumnhistCompVal | read-only | mandatory | Computed value reading |
| 1.3.6.1.4.1.22626.2 | NodetrapEmailErrLogin | SMTP error - unknown server | ||
| 1.3.6.1.4.1.22626.3 | NodetrapEmailErrAuth | SMTP error - authentication error | ||
| 1.3.6.1.4.1.22626.4 | NodetrapEmailErrSome | SMTP error - error during communication with server, unexpected return code | ||
| 1.3.6.1.4.1.22626.5 | NodetrapEmailErrSocket | SMTP error - socket error, server is not available | ||
| 1.3.6.1.4.1.22626.6 | NodetrapEmailErrDNS | SMTP error - DNS error | ||
| 1.3.6.1.4.1.22626.7 | NodetrapSOAPErrFile | SOAP error - file SOAP not found | ||
| 1.3.6.1.4.1.22626.8 | NodetrapSOAPErrDNS | SOAP error - DNS error | ||
| 1.3.6.1.4.1.22626.9 | NodetrapSOAPErrSocket | SOAP error - socket error, server is not available | ||
| 1.3.6.1.4.1.22626.10 | NodetrapSOAPErrDelivery | SOAP error - delivery error, wrong return code from server | ||
| 1.3.6.1.4.1.22626.11 | NodetrapTempHighAlarm | Trap for high alarm on temperature | ||
| 1.3.6.1.4.1.22626.12 | NodetrapHumHighAlarm | Trap for high alarm on relative humidity | ||
| 1.3.6.1.4.1.22626.13 | NodetrapCompValHighAlarm | Trap for high alarm on computed value | ||
| 1.3.6.1.4.1.22626.21 | NodetrapTempLowAlarm | Trap for low alarm on temperature | ||
| 1.3.6.1.4.1.22626.22 | NodetrapHumLowAlarm | Trap for low alarm on relative humidity | ||
| 1.3.6.1.4.1.22626.23 | NodetrapCompValLowAlarm | Trap for low alarm on computed value | ||
| 1.3.6.1.4.1.22626.31 | NodetrapTempClrAlarm | Trap for clearing alarm on temperature | ||
| 1.3.6.1.4.1.22626.32 | NodetrapHumClrAlarm | Trap for clearing alarm on relative humidity | ||
| 1.3.6.1.4.1.22626.33 | NodetrapCompValClrAlarm | Trap for clearing alarm on computed value | ||
| 1.3.6.1.4.1.22626.41 | NodetrapTempError | Trap for error on temperature | ||
| 1.3.6.1.4.1.22626.42 | NodetrapHumError | Trap for error on relative humidity | ||
| 1.3.6.1.4.1.22626.43 | NodetrapCompValError | Trap for error on computed value |